WARRANTY. Sierra Monitor Corporation IT Series, SENTRY 5000 Applicability & effectivity, 5100-02-IT


Add to my manuals
41 Pages

advertisement

WARRANTY. Sierra Monitor Corporation IT Series, SENTRY 5000 Applicability & effectivity, 5100-02-IT | Manualzz

Model 5100-02-IT Combustible Gas Sensor Module

7.3 APPENDIX C: LIMITED WARRANTY

SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.

All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (i.e. calibration gases, batteries, sensors), nor to any damage resulting from battery leakage.

In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.

Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product.

Page: 28

Model 5100-02-IT Combustible Gas Sensor Module

7.4 APPENDIX D: REMOTE SENSOR DRAWING 5394-50

Page: 29

Model 5100-02-IT Combustible Gas Sensor Module

7.5 APPENDIX E: AUXILIARY RELAY ASSEMBLY 5394-62

Page: 30

Model 5100-02-IT Combustible Gas Sensor Module

7.6 APPENDIX F: AUXILIARY CONNECTION ASSEMBLY 5394-61

Page: 31

Model 5100-02-IT Combustible Gas Sensor Module

7.7 APPENDIX G: AUXILIARY RS-485 MULTIDROP ASSEMBLY 5394-64

Page: 32

Model 5100-02-IT Combustible Gas Sensor Module

Page: 33

Model 5100-02-IT Combustible Gas Sensor Module

7.8 APPENDIX H: MODBUS MEMORY MAP

Read Register Table

Register Description

40001 Concentration

40002

40003

Temperature

High Alarm Relay

40004

40005

Low Alarm Relay

Low Alarm Value

40006 High Alarm Value

40007 Reserved

Comments

Gas Concentration multiplied by 100

Temperature in degrees Celsius scalled by a factor of 100

Boolean indicating the High Alarm Status, 0 No Alarm, 1 High Alarm

Boolean indicating the Low Alarm Status, 0 No Alarm, 1 Low Alarm

Low alarm set point, used for activating Alarms

High alarm set point, used for activating High Alarms

40008 Reserved

40009 Reserved

40010 Reserved

40011 Trouble Bits 0 for no trouble

40012

40013

40014

40015

Trouble

High Alarm Immediate Like 40003. but never latched

Low Alarm Immediate

Random ID

1 for any trouble, 0 for no trouble

Like 40004, but never latched

Randomly generated permanent ID of sensor

40016 Restart

40017

40018

Run time – high

Run time – low

40019 Max. gas value

40020 Model

40021

40022

40023

40024

40025

Range

Units

Temperature Units

Gas Scale

Temperature Scale

In minutes

In minutes

*scale ((see 40024)

51002

*scale (see 40024)

1 is %LEL

0 is C, 1 is F

Value like 1 or 100

Value like 1 or 100

Page: 34

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • FM approved
  • Detects combustible gases
  • 4-20 mA analog output
  • Modbus RTU over RS-485
  • Auxiliary relay output
  • Remote sensor option
  • Remote alarm reset
  • Enhanced connection option
  • Auxiliary RS-485 multidrop option

Related manuals

Frequently Answers and Questions

What type of gases can the IT Series detect?
The IT Series can detect a wide range of combustible gases, including methane, propane, butane, and hydrogen.
What is the output signal of the IT Series?
The IT Series has a 4-20 mA analog output.
Can the IT Series be used with Modbus devices?
Yes, the IT Series supports Modbus RTU over RS-485.
Does the IT Series have a remote sensor option?
Yes, the IT Series can be used with a remote sensor.
Can the IT Series be reset remotely?
Yes, the IT Series can be reset remotely.
Download PDF

advertisement

Table of contents