Model 5100-02-IT Combustible Gas Sensor Module
7.3 APPENDIX C: LIMITED WARRANTY
SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (i.e. calibration gases, batteries, sensors), nor to any damage resulting from battery leakage.
In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.
Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product.
Page: 28
Model 5100-02-IT Combustible Gas Sensor Module
7.4 APPENDIX D: REMOTE SENSOR DRAWING 5394-50
Page: 29
Model 5100-02-IT Combustible Gas Sensor Module
7.5 APPENDIX E: AUXILIARY RELAY ASSEMBLY 5394-62
Page: 30
Model 5100-02-IT Combustible Gas Sensor Module
7.6 APPENDIX F: AUXILIARY CONNECTION ASSEMBLY 5394-61
Page: 31
Model 5100-02-IT Combustible Gas Sensor Module
7.7 APPENDIX G: AUXILIARY RS-485 MULTIDROP ASSEMBLY 5394-64
Page: 32
Model 5100-02-IT Combustible Gas Sensor Module
Page: 33
Model 5100-02-IT Combustible Gas Sensor Module
7.8 APPENDIX H: MODBUS MEMORY MAP
Read Register Table
Register Description
40001 Concentration
40002
40003
Temperature
High Alarm Relay
40004
40005
Low Alarm Relay
Low Alarm Value
40006 High Alarm Value
40007 Reserved
Comments
Gas Concentration multiplied by 100
Temperature in degrees Celsius scalled by a factor of 100
Boolean indicating the High Alarm Status, 0 No Alarm, 1 High Alarm
Boolean indicating the Low Alarm Status, 0 No Alarm, 1 Low Alarm
Low alarm set point, used for activating Alarms
High alarm set point, used for activating High Alarms
40008 Reserved
40009 Reserved
40010 Reserved
40011 Trouble Bits 0 for no trouble
40012
40013
40014
40015
Trouble
High Alarm Immediate Like 40003. but never latched
Low Alarm Immediate
Random ID
1 for any trouble, 0 for no trouble
Like 40004, but never latched
Randomly generated permanent ID of sensor
40016 Restart
40017
40018
Run time – high
Run time – low
40019 Max. gas value
40020 Model
40021
40022
40023
40024
40025
Range
Units
Temperature Units
Gas Scale
Temperature Scale
In minutes
In minutes
*scale ((see 40024)
51002
*scale (see 40024)
1 is %LEL
0 is C, 1 is F
Value like 1 or 100
Value like 1 or 100
Page: 34