advertisement
The function can be disabled and it is a setting characteristic of the single protection units.
The start-up function enables the protection threshold (S, I and G) to be changed during a time interval lasting “ts”, starting from
“start-up”. The latter must be intended as follows:
-Passage of at least one of the phase currents above the activation threshold of the adjustable Start-Up with SD TestBus2, Ekip
Connect or PR010/T (0.1…10In, by 0.1In steps); A new start-up is possible after the current has dropped below this threshold.
I
Start-Up Threshold I2
Threshold I2
Threshold Start-Up activation
Activation of Start-Up ts time
The start-up time is common to all the protections involved.
Range: 0.1s … 30s, with steps of 0.01s.
t
13.2.9.2.3 Zone selectivity “S”
The zone selectivity function, guaranteed only if an auxiliary voltage is provided, enables the area of the fault to be isolated, only isolating the part of plant nearest to the fault, while keeping the rest of the plant operational.
This is done by connecting all the zone selectivity outputs of the releases belonging to the same zone to one another (ZSO=K51/
SZout) and taking this signal to the zone selectivity input (ZSI=K51/SZin) of the next release on the supply side. If the wiring has been done correctly, all the zone selectivity inputs of the last circuit-breakers in the chain and all the outputs of the circuit-breakers at the head of each chain must be empty.
ZSO
1
RELAY 1
ZSI
1
RELAY 0
ZSI
0
ZSO
2
RELAY 2
ZSI
2
ZSO n
RELAY n
ZSI n
ZSO 1a
RELAY 1a
Area 1
RELAY 1b Area 2 Area n
As a practical example, the figure above shows a fault on the load side of the “Relay 1a” isolated by the latter without the “Relay
1” or the “Relay 0” being affected; a fault immediately downstream from the “Relay 1” will be isolated by the latter without the
“Relay 0” being affected, thus ensuring that the Areas 2...n remain operational.
The ZSO output can be connected to a maximum of 20 ZSI relays on the supply side in the selectivity chain.
Model
WARNING: The maximum length of cable for zone selectivity, between two units, is 300 meters.
Use corded shielded two-wire cable (see note A to par. 11.2.2).
The shield must only be earthed on the circuit-breaker of the supply-side relay (ZSI side).
Operation is only guaranteed when there is an auxiliary voltage.
The following logical table is implemented to manage the Zone Selectivity Input (ZSI) and Zone Selectivity Output (ZSO) signals:
Zone selectivity
Excluded
Excluded
Excluded
Excluded
Inserted
Inserted
Inserted
Inserted
I f
> I
2
NO
NO
YES
YES
NO
NO
YES
YES
ZSI signal
0
1
0
1
0
1
0
1
ZSO signal
0
0
0
0
0
1
1
1
Trip T
No trip
No trip t
2
programmed t
2
programmed
No trip
No trip t selectivity t
2
programmed
The time t
2
must be set at a value higher than or equal to t selectivity
+50 ms, on the CB on the supply side, not required on the first one in the chain.
“I”
The protection is enabled/disabled from the menu.
In the case where zone selectivity “S” is active, during the trip of the relay for “I”, the ZSO output signal is activated in any case
L2234
L2778
L4681
L5179
L5439
Apparatus Emax Scale
Doc. No 1SDH000460R0002 Page No
53/161
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Description
- 7 General characteristics
- 7 External front view of the circuit-breaker
- 7 Rating plate
- 7 Circuit-breaker rating plate
- 7 Disconnector rating plate
- 8 Moving part construction characteristics
- 8 Fixed part construction characteristics
- 9 Checking on receipt
- 9 Storage, lifting and weights
- 10 Installation
- 10 Installation room
- 10 Installation of the fi xed circuit-breaker
- 10 of the withdrawable circuit-breaker
- 10 Preparation of the fi xed part
- 11 Installation of the fi xed part
- 11 Installation of the fi xed part on board a ship
- 11 Installation of the fl ange on the compartment door
- 12 Connections to the power circuit
- 12 Shapes of the terminals
- 12 according to the types of terminals
- 14 Assembly procedure for the connection busbars
- 14 Earthing
- 14 Wiring the circuit-breaker auxiliary circuits
- 14 Interfacing elements for fi xed circuit-breakers
- 15 Withdrawable circuit-breaker
- 16 open (closing) or vice versa
- 17 Putting into service
- 17 General procedures
- 18 Instructions for use
- 18 Operating and signalling parts
- 19 Circuit-breaker closing and opening procedures
- 20 Racking-in/out operation
- 22 Maintenance
- 22 Warning
- 22 Maintenance programme
- 22 Switch life
- 23 Maintenance program
- 23 First level maintenance operations
- 23 Preliminary operations
- 23 Checks and general cleaning
- 23 the switch and the control panel
- 24 Dismantling tab and cap
- 24 Mechanical control
- 25 Electrical and mechanical accessories
- 25 Protection releases
- 25 Test with SD Testbus2 (optional)
- 25 Maintenance operations; fi nal checks
- 25 Interlock
- 26 Second level maintenance operations
- 26 Preliminary operations
- 26 General checks and cleaning
- 27 Dismantling the tab, cap and arcing chambers
- 28 Mechanical control
- 28 Electrical and mechanical accessories
- 28 Checking contact wear
- 29 Protection releases
- 29 Test with SD Testbus2 (optional)
- 29 Maintenance operations; fi nal checks
- 30 Interlock
- 30 Extractable
- 31 Measures to be taken for any operating anomalies
- 32 Accessories
- 32 Electrical accessories
- 34 Mechanical locks
- 36 Spare parts and retrofi tting
- 37 Protection releases - General notes
- 37 Safety notes
- 38 Notes for dielectric stiffness tests
- 38 Abbreviations and notes
- 38 Abbrevations
- 38 Notes
- 39 SACE PR121/P Release - Identifi cation
- 39 Standard
- 39 Specifi cations
- 39 General
- 39 Electrical characteristics
- 39 Self-supply
- 40 Auxiliary power supply
- 40 Environmental characteristics
- 40 Communication bus
- 40 Protection functions
- 40 Calculating the RMS
- 40 Measuring Function
- 40 Watchdog
- 41 Description of the protection functions
- 41 Protection “L
- 41 12.2.6.1.1 Thermal memory “L
- 41 Protection “S
- 41 12.2.6.2.1 Thermal memory “S
- 41 Protection “I
- 41 Protection “G
- 41 Protection against instantaneous short-circuit “Iinst
- 41 Summary table of protections
- 42 Table of measurements
- 42 Trip curves
- 42 Trip curves for functions L-I
- 43 Trip curves for functions L-S(t=k)-I
- 44 Trip curves for function G
- 44 Other functions
- 44 Indication of the cause of the trip and trip test button
- 44 Putting into service
- 44 Connections
- 44 CS and TC connection check
- 44 Current sensor connection for external neutral
- 45 User interface
- 45 Trip Test
- 45 Initial settings
- 46 Changing protection functions
- 46 Example of settings
- 46 PR121/P default settings
- 46 Operating instructions / Operation in service
- 46 Neutral adjustment
- 46 Neutral adjustment specifi cations
- 47 Replacing an electronic release
- 47 for the PR121/P unit
- 47 Optical signals
- 48 Troubleshooting
- 48 In the case of a fault
- 48 Accessories
- 48 ABB SACE PR010/T test and confi guration unit
- 48 BT030 USB communication unit
- 48 PR021/K and HMI030 units
- 48 PR030/B power supply unit
- 48 Flex interfaces
- 49 SACE PR122/P Release - Identifi cation
- 49 Standard
- 49 Specifi cations
- 49 General
- 50 Electrical characteristics
- 50 Self-supply
- 50 Auxiliary power supply
- 50 Powered by the PR120/V module
- 50 Environmental characteristics
- 50 Description of inputs/outputs
- 50 Binary inputs
- 50 Binary outputs
- 51 Communication bus
- 51 Protection functions
- 51 Calculating the RMS
- 51 Mains frequency
- 51 Harmonic distortion
- 51 Circuit-breaker state
- 51 Measurement functions
- 52 Watchdog
- 52 Description of the protection functions
- 52 Protection “L
- 52 13.2.9.1.1 Thermal memory “L
- 52 Protection “S
- 52 13.2.9.2.1 Thermal memory “S
- 52 13.2.9.2.2 Start-up threshold “S
- 53 13.2.9.2.3 Zone selectivity “S
- 53 Protection “I
- 54 13.2.9.3.1 Start-up threshold “I
- 54 Protection “MCR” against closing on short-circuit
- 54 Protection “G
- 54 13.2.9.5.1 Start-up threshold “G
- 54 13.2.9.5.2 Zone selectivity “G
- 54 Protection against phase unbalance “U
- 55 the relay “OT
- 55 Load control function
- 55 ADDITIONAL PR120/V MODULE)
- 55 13.2.9.9.1 Protection “UV
- 55 13.2.9.9.2 Protection “OV
- 55 13.2.9.9.3 Protection “RV
- 56 13.2.9.9.4 Protetion “U
- 56 WITH THE ADDITIONAL PR120/V MODULE)
- 56 for the PR122/P
- 57 for the PR122/P with the optional PR120/V module
- 57 13.2.9.12.2 Table of measurements
- 58 Trip curves
- 58 13.2.10.1. Trip curves for functions L-I
- 59 13.2.10.3. Trip curves for functions L-S(t=k)-I
- 60 with IEC 60255-3 (type A)
- 60 with IEC 60255-3 (type B)
- 61 with IEC 60255-3 (type C)
- 61 13.2.10.7. Trip curves for function G
- 62 13.2.10.8. Trip curves for function U
- 62 13.2.10.9. Trip curves for function UV
- 63 13.2.10.10. Trip curves for function OV
- 63 13.2.10.11. Trip curves for function RV
- 64 13.2.10.12. Trip curves for function RP
- 64 Putting into service
- 64 Connections
- 64 Current sensor connection for external neutral
- 65 VT connections
- 65 CS and TC connection test
- 65 Initial settings
- 66 Password management
- 66 Replacing an electronic release
- 66 Installation
- 66 Uninstalling
- 67 User interface
- 67 Use of pushbuttons
- 68 Read and Edit modes
- 68 Changing parameter
- 70 Modifi cation of basic confi guration
- 71 Default settings
- 72 Operating instructions / Operation in service
- 73 Protections menu
- 73 Protections menu table
- 74 Measurements Menu
- 75 Measurements Menu table
- 75 Settings Menu
- 75 Settings Menu table
- 76 Neutral adjustment
- 76 13.5.4.2.1 Neutral adjustment specifi cations
- 76 Mains frequency settings
- 76 Modules
- 76 13.5.4.4.1 PR120/V MEASURING Module
- 76 13.5.4.4.2 PR120/D-M - COM module
- 76 13.5.4.4.3 PR120/K - SIGNALLING module
- 76 13.5.4.4.4 PR120/D - BT module
- 76 13.5.4.4.5 Settings for the Local Bus unit
- 77 Test Menu
- 77 Test Menu table
- 77 Information Menu
- 77 Information on the trip and opening data
- 78 Defi nition of alarms and signals in the PR122/P unit
- 78 Optical signals
- 78 Electrical signals
- 79 Table of error and warning messages
- 80 Error messages displayed in pop-up windows
- 80 Troubleshooting PR122/P unit
- 81 In the case of a fault
- 81 Accessories
- 81 ABB SACE PR010/T test and confi guration unit
- 81 BT030 USB communication unit
- 81 PR021/K and HMI030 units
- 81 PR030/B power supply unit
- 81 Flex interface
- 82 SACE PR123/P Release - Identifi cation
- 82 Standard
- 82 Specifi cations
- 82 General
- 83 Electrical characteristics
- 83 Self-powering
- 83 Auxiliary power supply
- 83 Powered by the PR120/V module
- 83 Environmental characteristics
- 83 Description of inputs/outputs
- 83 Binary input
- 83 Binary outputs
- 83 Communication bus
- 83 Protection functions
- 84 Rms calculation
- 84 Mains frequency
- 84 Harmonic distortion
- 84 Circuit-breaker state
- 84 Measurement functions
- 85 Watchdog
- 85 Description of the protection functions
- 85 Protection “L
- 85 14.2.9.1.1 Thermal memory “L
- 85 Protection “S
- 85 14.2.9.2.1 Thermal memory “S
- 86 14.2.9.2.2 Start-up threshold “S
- 86 14.2.9.2.3 Zone selectivity“S
- 87 Double S
- 87 Directional Protection “D
- 87 14.2.9.4.1 Start-up threshold “D
- 87 14.2.9.4.2 (Directional) zone selectivity “D
- 88 Protection “I
- 89 14.2.9.5.1 Start-up threshold “I
- 89 Protection against closing on short-circuit “MCR
- 89 Protection “G
- 89 14.2.9.7.1 Start-up threshold “G
- 89 14.2.9.7.2 Zone selectivity “G
- 89 Protection against phase unbalance “U
- 90 the relay “OT
- 90 14.2.9.10. Load control function
- 90 14.2.9.11. Voltage protections “UV”, “OV”, “RV”, “U
- 90 14.2.9.11.1 Protection “UV
- 90 14.2.9.11.2 Protection “OV
- 90 14.2.9.11.3 Protection “RV
- 90 14.2.9.11.4 Protection “U
- 91 14.2.9.12. Protection against reverse active power “RP
- 91 14.2.9.13. Frequency protections “UF”, “OF
- 91 14.2.9.14. Double protections setting
- 91 for the PR123/P
- 93 14.2.9.16. Table of measurements
- 93 Trip curves
- 94 14.2.10.2. Trip curves for functions L-S(t=k)-I
- 94 14.2.10.3. Trip curves for function G
- 95 with IEC 60255-3 (tipo A)
- 95 with IEC 60255-3 (tipo B)
- 96 with IEC 60255-3 (tipo C)
- 96 14.2.10.7. Trip curves for function D
- 97 14.2.10.8. Trip curves for function U
- 97 14.2.10.9. Trip curves for function UV
- 98 14.2.10.10. Trip curves for function OV
- 98 14.2.10.11. Trip curves for function RV
- 99 14.2.10.12. Trip curves for function RP
- 99 Putting into service
- 99 Connections
- 99 Current sensor connection for external neutral
- 100 VT connections
- 100 CS and TC connection test
- 100 Initial settings
- 101 Password management
- 101 Replacing an electronic release
- 101 Installation
- 101 Uninstalling
- 102 User interface
- 102 Use of pushbutton
- 103 Read and Edit modes
- 103 Changing parameters
- 105 Modifi cation of basic confi guration
- 106 Default settings
- 107 Operating instructions / Operation in service
- 108 Protections Menu
- 108 Protections Menu table
- 110 Measurements Menu
- 110 Measurements Menu table
- 111 Settings Menu
- 111 Settings Menu table
- 111 Neutral adjustment
- 112 14.5.4.2.1 Neutral adjustment specifi cations
- 112 Mains frequency settings
- 112 Modules
- 112 14.5.4.4.1 PR120/V - MEASURING module
- 112 14.5.4.4.2 PR120/D-M - COM module
- 112 14.5.4.4.3 PR120/K - SIGNALLING module
- 112 14.5.4.4.4 PR120/D - BT module
- 112 14.5.4.4.5 Settings for the Local Bus unit
- 113 Test Menu
- 113 Test Menu table
- 113 Information Menu
- 113 Information on the trip and opening data
- 114 Optical signals
- 114 Electrical signals
- 114 Table of error and warning messages
- 115 Error messages displayed in pop-up windows
- 116 Troubleshooting PR123/P unit
- 117 In the case of a fault
- 117 Accessories
- 117 ABB SACE PR010/T test and confi guration unit
- 117 BT030 USB communication unit
- 117 PR021/K and HMI030 units
- 117 PR030/B power supply unit
- 117 Flex interface
- 118 Modules
- 118 PR120/V - MEASURING Module
- 118 General characteristics
- 118 Front view
- 118 Releases complete with the module
- 118 the PR120/V module
- 119 Operating instructions / Operation in service
- 121 Table of submenus for the PR120/V module
- 121 Measurements Menu table
- 122 Measurements Menu
- 122 15.1.5.4.1 Historicals
- 122 15.1.5.4.2 Trips
- 122 15.1.5.4.3 Events
- 122 15.1.5.4.4 Measurements
- 123 15.1.5.4.6 Energy
- 123 15.1.5.4.7 Peak factor
- 123 15.1.5.4.8 Mains frequency
- 123 15.1.5.4.9 Contact wear
- 123 15.1.5.4.10 Waveforms
- 124 Electrical characteristics of the transformers
- 125 PR120/D-M - COM communication module
- 125 General characteristics
- 125 Front view
- 125 Releases complete with the module
- 125 Power supply
- 125 Connection
- 125 Communication functions available
- 125 PR120/D-M - COM module menu
- 126 PR120/K signalling module
- 126 General characteristics
- 126 Front view
- 126 Releases complete with the module
- 126 Characteristics of the digital input
- 126 Characteristics of the signalling contacts
- 126 Power supply
- 127 PR120/K module menu
- 127 Confi gurable input
- 127 Input confi guration settings
- 127 Input function settings (ACTION)
- 127 Setting the input enabling delay
- 128 PR120/K module menu layout
- 129 wireless communication module
- 129 General characteristics
- 129 Front view
- 129 Releases complete with the module
- 129 Power supply
- 129 Connection
- 130 Appendices
- 130 PR021/K outside signalling unit
- 130 General information
- 130 Power supply
- 130 General characteristics of the signalling relays
- 130 Relay functions
- 130 PR021/K signalling unit menu
- 131 PR021/K unit menu table
- 131 Important note
- 131 SD-Testbus
- 132 Data Logger (recorder)
- 132 General characteristics
- 132 Description of the Data Logger menu
- 132 Enabling the Data Logger
- 132 Setting the sampling frequency
- 132 Setting the standard stop events (triggers)
- 133 Setting the stopping delay
- 133 Restart/Stop Data Logger
- 133 Recording time windows
- 134 by the Data Logger system
- 134 from the Data Logger system
- 134 Access to saved data from the system
- 135 and status of the Data Logger
- 135 Data logger commands from the system
- 135 Table showing list of events
- 135 selectable from the relay
- 136 function, for PR120/K and PR021/K
- 136 Residual current protection function Rc
- 136 General
- 137 Putting into service
- 137 Rc test menu
- 137 Flex interface
- 138 Overall dimensions
- 152 Circuit diagrams
- 152 Caption
- 153 Description of fi gures
- 154 Incompatibilities
- 154 Notes