advertisement
adjustment
The neutral protection is normally set to a current value 50% of the adjustment made on the phases.
In some installations, where particularly high harmonics occur, the current circulating on the neutral may be higher than that of the phases.
I
In the SACE PR122/P release, this protection can be set for the following values: n
N= 50% - 100% - 150% - 200% * I n
.
13.5.4.2.1 Neutral adjustment specifications
Neutral (InN) adjustment must meet the following formula: I
1 x I n
NIu.
In case of a four-pole CB, this setting is checked by the relay which signals any failure through a Led (see par. 13.6.1), and adjusts the parameter independently to the accepted limits.
In case of a three-pole CB with external neutral, the relay performs no checks and user must correct the settings.
E.g.: With CB E1B800 with a 400A Rating Plug, Iu = 800A and I1 = 1In, I n
With CB E1B800 with a 800A Rating Plug, Iu = 800A and I1 = 1In I n
N adjustment may be: 50-100-200%.
N adjustment may be: 50-100%.
Note 1: I
1
=1I n
setting is intended as the maximum adjustment of the protection against overloads. Actual maximum allowable adjustment must take into account any temperature derating, terminals used and altitude, or In (rating plug)≤ 50% of circuit breaker size.
WARNING: Failure to comply with the setting limits for “I
1 consequent risks even for the operator.
” and “I n
N” can cause circuit-breaker damage with
In any case, the relay records any setting error between I
1 par. 13.6.3). For four-pole CBs only.
and the Neutral setting and it signals this by means of the warning (see
13.5.4.3. Mains frequency settings
In the mains frequency menu, you can choose between the frequency values: 50, 60Hz.
2/8 Password
1/2 Settings
Circuit Breaker
Main Frequency
Modules
Enter
0***
Mains Frequency
50 Hz
60 Hz
4 P
50 Hz Enter password
Enter
13.5.4.4. Modules
When you access the Settings menu, there is a set of menus available relating to the modules.
13.5.4.4.1 PR120/V MEASURING Module
1/4 1/5
Modules
MEASURING module
COM module
SIGNALLING module
MEASURING module
Voltage Transf
Rated voltage
Positive Power flow
Absent
In the measuring module you must enter a password and can then opt for the absence or presence of the voltage transformer.
Moreover, you can select the values of the primary voltage (100, 115, 120, ... 1000V) and secondary voltage (100, 110, ... 230V).
The power flow can be LOW HIGH or HIGH LOW. After entering a password you can choose whether the neutral connection is to be Absent or Present. For three-pole CBs only
13.5.4.4.2 PR120/D-M - COM module
Modules 2/4
MEASURING module
COM module
SIGNALLING module
Communication parameters
COM module
Local / Remote
Serial Address
Baudrate
1/5
Local
The local or remote modes can be selected after entering a password. The serial address can be displayed after entering a password. The Baud Rate can be set on the values 9600 and 19200 bit/s. The physical protocol provides for the options: (8,E,1),
(8,0,1), (8,N,2), (8,N,1). The addressing can be selected as standard Modbus or ABB. For further information on the PR120/D-M communication module, see paragraph 15.2 in this manual..
13.5.4.4.3 PR120/K - SIGNALLING module
For a thorough examination of the signalling module, refer to the corresponding section of the module, paragraph 15.3.
13.5.4.4.4 PR120/D - BT module
This module is for wireless communication based on the Bluetooth standard between the PR122/P protection release and a laptop with a Bluetooth port. For further information, see the description of the module in paragraph 15.4.
13.5.4.4.5 Settings for the Local Bus unit
If the PR021/K unit is connected, you need to enable the local bus by selecting present.
Model L2234
L2778
L4681
L5179
L5439 Apparatus
Doc. no.
Emax
1SDH000460R0002
Scale
Page No
76/161
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Description
- 7 General characteristics
- 7 External front view of the circuit-breaker
- 7 Rating plate
- 7 Circuit-breaker rating plate
- 7 Disconnector rating plate
- 8 Moving part construction characteristics
- 8 Fixed part construction characteristics
- 9 Checking on receipt
- 9 Storage, lifting and weights
- 10 Installation
- 10 Installation room
- 10 Installation of the fi xed circuit-breaker
- 10 of the withdrawable circuit-breaker
- 10 Preparation of the fi xed part
- 11 Installation of the fi xed part
- 11 Installation of the fi xed part on board a ship
- 11 Installation of the fl ange on the compartment door
- 12 Connections to the power circuit
- 12 Shapes of the terminals
- 12 according to the types of terminals
- 14 Assembly procedure for the connection busbars
- 14 Earthing
- 14 Wiring the circuit-breaker auxiliary circuits
- 14 Interfacing elements for fi xed circuit-breakers
- 15 Withdrawable circuit-breaker
- 16 open (closing) or vice versa
- 17 Putting into service
- 17 General procedures
- 18 Instructions for use
- 18 Operating and signalling parts
- 19 Circuit-breaker closing and opening procedures
- 20 Racking-in/out operation
- 22 Maintenance
- 22 Warning
- 22 Maintenance programme
- 22 Switch life
- 23 Maintenance program
- 23 First level maintenance operations
- 23 Preliminary operations
- 23 Checks and general cleaning
- 23 the switch and the control panel
- 24 Dismantling tab and cap
- 24 Mechanical control
- 25 Electrical and mechanical accessories
- 25 Protection releases
- 25 Test with SD Testbus2 (optional)
- 25 Maintenance operations; fi nal checks
- 25 Interlock
- 26 Second level maintenance operations
- 26 Preliminary operations
- 26 General checks and cleaning
- 27 Dismantling the tab, cap and arcing chambers
- 28 Mechanical control
- 28 Electrical and mechanical accessories
- 28 Checking contact wear
- 29 Protection releases
- 29 Test with SD Testbus2 (optional)
- 29 Maintenance operations; fi nal checks
- 30 Interlock
- 30 Extractable
- 31 Measures to be taken for any operating anomalies
- 32 Accessories
- 32 Electrical accessories
- 34 Mechanical locks
- 36 Spare parts and retrofi tting
- 37 Protection releases - General notes
- 37 Safety notes
- 38 Notes for dielectric stiffness tests
- 38 Abbreviations and notes
- 38 Abbrevations
- 38 Notes
- 39 SACE PR121/P Release - Identifi cation
- 39 Standard
- 39 Specifi cations
- 39 General
- 39 Electrical characteristics
- 39 Self-supply
- 40 Auxiliary power supply
- 40 Environmental characteristics
- 40 Communication bus
- 40 Protection functions
- 40 Calculating the RMS
- 40 Measuring Function
- 40 Watchdog
- 41 Description of the protection functions
- 41 Protection “L
- 41 12.2.6.1.1 Thermal memory “L
- 41 Protection “S
- 41 12.2.6.2.1 Thermal memory “S
- 41 Protection “I
- 41 Protection “G
- 41 Protection against instantaneous short-circuit “Iinst
- 41 Summary table of protections
- 42 Table of measurements
- 42 Trip curves
- 42 Trip curves for functions L-I
- 43 Trip curves for functions L-S(t=k)-I
- 44 Trip curves for function G
- 44 Other functions
- 44 Indication of the cause of the trip and trip test button
- 44 Putting into service
- 44 Connections
- 44 CS and TC connection check
- 44 Current sensor connection for external neutral
- 45 User interface
- 45 Trip Test
- 45 Initial settings
- 46 Changing protection functions
- 46 Example of settings
- 46 PR121/P default settings
- 46 Operating instructions / Operation in service
- 46 Neutral adjustment
- 46 Neutral adjustment specifi cations
- 47 Replacing an electronic release
- 47 for the PR121/P unit
- 47 Optical signals
- 48 Troubleshooting
- 48 In the case of a fault
- 48 Accessories
- 48 ABB SACE PR010/T test and confi guration unit
- 48 BT030 USB communication unit
- 48 PR021/K and HMI030 units
- 48 PR030/B power supply unit
- 48 Flex interfaces
- 49 SACE PR122/P Release - Identifi cation
- 49 Standard
- 49 Specifi cations
- 49 General
- 50 Electrical characteristics
- 50 Self-supply
- 50 Auxiliary power supply
- 50 Powered by the PR120/V module
- 50 Environmental characteristics
- 50 Description of inputs/outputs
- 50 Binary inputs
- 50 Binary outputs
- 51 Communication bus
- 51 Protection functions
- 51 Calculating the RMS
- 51 Mains frequency
- 51 Harmonic distortion
- 51 Circuit-breaker state
- 51 Measurement functions
- 52 Watchdog
- 52 Description of the protection functions
- 52 Protection “L
- 52 13.2.9.1.1 Thermal memory “L
- 52 Protection “S
- 52 13.2.9.2.1 Thermal memory “S
- 52 13.2.9.2.2 Start-up threshold “S
- 53 13.2.9.2.3 Zone selectivity “S
- 53 Protection “I
- 54 13.2.9.3.1 Start-up threshold “I
- 54 Protection “MCR” against closing on short-circuit
- 54 Protection “G
- 54 13.2.9.5.1 Start-up threshold “G
- 54 13.2.9.5.2 Zone selectivity “G
- 54 Protection against phase unbalance “U
- 55 the relay “OT
- 55 Load control function
- 55 ADDITIONAL PR120/V MODULE)
- 55 13.2.9.9.1 Protection “UV
- 55 13.2.9.9.2 Protection “OV
- 55 13.2.9.9.3 Protection “RV
- 56 13.2.9.9.4 Protetion “U
- 56 WITH THE ADDITIONAL PR120/V MODULE)
- 56 for the PR122/P
- 57 for the PR122/P with the optional PR120/V module
- 57 13.2.9.12.2 Table of measurements
- 58 Trip curves
- 58 13.2.10.1. Trip curves for functions L-I
- 59 13.2.10.3. Trip curves for functions L-S(t=k)-I
- 60 with IEC 60255-3 (type A)
- 60 with IEC 60255-3 (type B)
- 61 with IEC 60255-3 (type C)
- 61 13.2.10.7. Trip curves for function G
- 62 13.2.10.8. Trip curves for function U
- 62 13.2.10.9. Trip curves for function UV
- 63 13.2.10.10. Trip curves for function OV
- 63 13.2.10.11. Trip curves for function RV
- 64 13.2.10.12. Trip curves for function RP
- 64 Putting into service
- 64 Connections
- 64 Current sensor connection for external neutral
- 65 VT connections
- 65 CS and TC connection test
- 65 Initial settings
- 66 Password management
- 66 Replacing an electronic release
- 66 Installation
- 66 Uninstalling
- 67 User interface
- 67 Use of pushbuttons
- 68 Read and Edit modes
- 68 Changing parameter
- 70 Modifi cation of basic confi guration
- 71 Default settings
- 72 Operating instructions / Operation in service
- 73 Protections menu
- 73 Protections menu table
- 74 Measurements Menu
- 75 Measurements Menu table
- 75 Settings Menu
- 75 Settings Menu table
- 76 Neutral adjustment
- 76 13.5.4.2.1 Neutral adjustment specifi cations
- 76 Mains frequency settings
- 76 Modules
- 76 13.5.4.4.1 PR120/V MEASURING Module
- 76 13.5.4.4.2 PR120/D-M - COM module
- 76 13.5.4.4.3 PR120/K - SIGNALLING module
- 76 13.5.4.4.4 PR120/D - BT module
- 76 13.5.4.4.5 Settings for the Local Bus unit
- 77 Test Menu
- 77 Test Menu table
- 77 Information Menu
- 77 Information on the trip and opening data
- 78 Defi nition of alarms and signals in the PR122/P unit
- 78 Optical signals
- 78 Electrical signals
- 79 Table of error and warning messages
- 80 Error messages displayed in pop-up windows
- 80 Troubleshooting PR122/P unit
- 81 In the case of a fault
- 81 Accessories
- 81 ABB SACE PR010/T test and confi guration unit
- 81 BT030 USB communication unit
- 81 PR021/K and HMI030 units
- 81 PR030/B power supply unit
- 81 Flex interface
- 82 SACE PR123/P Release - Identifi cation
- 82 Standard
- 82 Specifi cations
- 82 General
- 83 Electrical characteristics
- 83 Self-powering
- 83 Auxiliary power supply
- 83 Powered by the PR120/V module
- 83 Environmental characteristics
- 83 Description of inputs/outputs
- 83 Binary input
- 83 Binary outputs
- 83 Communication bus
- 83 Protection functions
- 84 Rms calculation
- 84 Mains frequency
- 84 Harmonic distortion
- 84 Circuit-breaker state
- 84 Measurement functions
- 85 Watchdog
- 85 Description of the protection functions
- 85 Protection “L
- 85 14.2.9.1.1 Thermal memory “L
- 85 Protection “S
- 85 14.2.9.2.1 Thermal memory “S
- 86 14.2.9.2.2 Start-up threshold “S
- 86 14.2.9.2.3 Zone selectivity“S
- 87 Double S
- 87 Directional Protection “D
- 87 14.2.9.4.1 Start-up threshold “D
- 87 14.2.9.4.2 (Directional) zone selectivity “D
- 88 Protection “I
- 89 14.2.9.5.1 Start-up threshold “I
- 89 Protection against closing on short-circuit “MCR
- 89 Protection “G
- 89 14.2.9.7.1 Start-up threshold “G
- 89 14.2.9.7.2 Zone selectivity “G
- 89 Protection against phase unbalance “U
- 90 the relay “OT
- 90 14.2.9.10. Load control function
- 90 14.2.9.11. Voltage protections “UV”, “OV”, “RV”, “U
- 90 14.2.9.11.1 Protection “UV
- 90 14.2.9.11.2 Protection “OV
- 90 14.2.9.11.3 Protection “RV
- 90 14.2.9.11.4 Protection “U
- 91 14.2.9.12. Protection against reverse active power “RP
- 91 14.2.9.13. Frequency protections “UF”, “OF
- 91 14.2.9.14. Double protections setting
- 91 for the PR123/P
- 93 14.2.9.16. Table of measurements
- 93 Trip curves
- 94 14.2.10.2. Trip curves for functions L-S(t=k)-I
- 94 14.2.10.3. Trip curves for function G
- 95 with IEC 60255-3 (tipo A)
- 95 with IEC 60255-3 (tipo B)
- 96 with IEC 60255-3 (tipo C)
- 96 14.2.10.7. Trip curves for function D
- 97 14.2.10.8. Trip curves for function U
- 97 14.2.10.9. Trip curves for function UV
- 98 14.2.10.10. Trip curves for function OV
- 98 14.2.10.11. Trip curves for function RV
- 99 14.2.10.12. Trip curves for function RP
- 99 Putting into service
- 99 Connections
- 99 Current sensor connection for external neutral
- 100 VT connections
- 100 CS and TC connection test
- 100 Initial settings
- 101 Password management
- 101 Replacing an electronic release
- 101 Installation
- 101 Uninstalling
- 102 User interface
- 102 Use of pushbutton
- 103 Read and Edit modes
- 103 Changing parameters
- 105 Modifi cation of basic confi guration
- 106 Default settings
- 107 Operating instructions / Operation in service
- 108 Protections Menu
- 108 Protections Menu table
- 110 Measurements Menu
- 110 Measurements Menu table
- 111 Settings Menu
- 111 Settings Menu table
- 111 Neutral adjustment
- 112 14.5.4.2.1 Neutral adjustment specifi cations
- 112 Mains frequency settings
- 112 Modules
- 112 14.5.4.4.1 PR120/V - MEASURING module
- 112 14.5.4.4.2 PR120/D-M - COM module
- 112 14.5.4.4.3 PR120/K - SIGNALLING module
- 112 14.5.4.4.4 PR120/D - BT module
- 112 14.5.4.4.5 Settings for the Local Bus unit
- 113 Test Menu
- 113 Test Menu table
- 113 Information Menu
- 113 Information on the trip and opening data
- 114 Optical signals
- 114 Electrical signals
- 114 Table of error and warning messages
- 115 Error messages displayed in pop-up windows
- 116 Troubleshooting PR123/P unit
- 117 In the case of a fault
- 117 Accessories
- 117 ABB SACE PR010/T test and confi guration unit
- 117 BT030 USB communication unit
- 117 PR021/K and HMI030 units
- 117 PR030/B power supply unit
- 117 Flex interface
- 118 Modules
- 118 PR120/V - MEASURING Module
- 118 General characteristics
- 118 Front view
- 118 Releases complete with the module
- 118 the PR120/V module
- 119 Operating instructions / Operation in service
- 121 Table of submenus for the PR120/V module
- 121 Measurements Menu table
- 122 Measurements Menu
- 122 15.1.5.4.1 Historicals
- 122 15.1.5.4.2 Trips
- 122 15.1.5.4.3 Events
- 122 15.1.5.4.4 Measurements
- 123 15.1.5.4.6 Energy
- 123 15.1.5.4.7 Peak factor
- 123 15.1.5.4.8 Mains frequency
- 123 15.1.5.4.9 Contact wear
- 123 15.1.5.4.10 Waveforms
- 124 Electrical characteristics of the transformers
- 125 PR120/D-M - COM communication module
- 125 General characteristics
- 125 Front view
- 125 Releases complete with the module
- 125 Power supply
- 125 Connection
- 125 Communication functions available
- 125 PR120/D-M - COM module menu
- 126 PR120/K signalling module
- 126 General characteristics
- 126 Front view
- 126 Releases complete with the module
- 126 Characteristics of the digital input
- 126 Characteristics of the signalling contacts
- 126 Power supply
- 127 PR120/K module menu
- 127 Confi gurable input
- 127 Input confi guration settings
- 127 Input function settings (ACTION)
- 127 Setting the input enabling delay
- 128 PR120/K module menu layout
- 129 wireless communication module
- 129 General characteristics
- 129 Front view
- 129 Releases complete with the module
- 129 Power supply
- 129 Connection
- 130 Appendices
- 130 PR021/K outside signalling unit
- 130 General information
- 130 Power supply
- 130 General characteristics of the signalling relays
- 130 Relay functions
- 130 PR021/K signalling unit menu
- 131 PR021/K unit menu table
- 131 Important note
- 131 SD-Testbus
- 132 Data Logger (recorder)
- 132 General characteristics
- 132 Description of the Data Logger menu
- 132 Enabling the Data Logger
- 132 Setting the sampling frequency
- 132 Setting the standard stop events (triggers)
- 133 Setting the stopping delay
- 133 Restart/Stop Data Logger
- 133 Recording time windows
- 134 by the Data Logger system
- 134 from the Data Logger system
- 134 Access to saved data from the system
- 135 and status of the Data Logger
- 135 Data logger commands from the system
- 135 Table showing list of events
- 135 selectable from the relay
- 136 function, for PR120/K and PR021/K
- 136 Residual current protection function Rc
- 136 General
- 137 Putting into service
- 137 Rc test menu
- 137 Flex interface
- 138 Overall dimensions
- 152 Circuit diagrams
- 152 Caption
- 153 Description of fi gures
- 154 Incompatibilities
- 154 Notes