- Computers & electronics
- Networking
- Gateways/controllers
- Rosemount
- Smart Wireless Gateway
- Product information
advertisement
Section 5: Host Integration
January 2015
5.4.2
Reference Manual
00809-0200-4420, Rev HB
Use global scale gain and offset?: This setting determines if a global gain and offset is applied for scaled integers or if each value has a unique gain and offset. Unique gain and offsets are found on the Modbus Mapping page.
Global scale gain: This value is multiplied to the data values for the purpose of scaling integers.
If global scaling is not selected, a gain value will be available for each separate data value on the
Modbus Mapping page.
Global scale offset: This value is added to the data values for the purpose of scaling integers. If global scaling is not selected, an offset value will be available for each separate data value on the
Modbus Mapping page.
Register mapping
Register Mapping is the process of assigning data points from wireless field devices to Modbus registers. These registers can then be read by a Modbus master or client. Modbus register mapping can be found by navigating to System Settings>Protocols>Modbus.
Figure 5-6. Modbus Register Map Page
38
To add a new data point to the Modbus register map:
1.
Select Add New entry.
2.
Complete all of the table entries for the new data point (note that the entry columns may vary based on the Modbus communications settings).
Host Integration
Reference Manual
00809-0200-4420, Rev HB
Section 5: Host Integration
January 2015
3.
4.
Repeat for each new data point.
Select Submit.
5.
When changes have been accepted, select Return to form.
Address: This is the Modbus RTU address used by the Gateway for this data point. It is possible to group data points assigning them the same address (i.e. all data points from the same process unit can have the same address). This column only appears if Multiple Modbus Addresses is selected on the Modbus Communications page.
Register: This is the Modbus register number used for this data value. Modbus registers hold two bytes (16 bits) of information; therefore 32 bit floats and integers require two Modbus registers. Each data point needs a unique Modbus register number, unless they are assigned different addresses. Register numbers 0-19999 are reserved for Boolean (bit, coil, binary, etc…) values. Register numbers 20000+ are reserved for floating point or integer values.
Point Name: This is a two part name for the data point. The first part is the HART Tag of the wireless field device which is producing the data. The second part is the parameter of the wireless field device.
Note
Point Name is entered as <HART Tag.PARAMETER>. Point Name can be entered using the list of values (…) or manually entered. The following table gives a list of standard device parameters which may be considered for Modbus register mapping.
Table 5-1. Device Parameters Available
Parameter Description
PV
SV
TV
QV
RELIABILITY
ONLINE
PV_HEALTHY
SV_HEALTHY
Primary Variable
Secondary Variable
Tertiary Variable
Quaternary Variable
A measure of connectivity to the Gateway
Wireless communications status
Health status for PV
Health status for SV
TV_HEALTHY Health status for TV
QV_HEALTHY Health status for QV
Data type
32-bit float
32-bit float
32-bit float
32-bit float
32-bit float
Boolean
Boolean
Boolean
Boolean
Boolean
PV, SV, TV, and QV (dynamic variables) will vary by device type. Please refer to the device’s documentation for more information on what value is represented by each dynamic variable.
RELIABILITY and ONLINE relate to wireless communications. RELIABILITY is the percentage of messages received from the wireless field device. ONLINE is a true/false indication of whether the device is communicating on the wireless network.
Host Integration
**_HEALTHY parameters are a true/false indication of the health of a particular variable (** = dynamic variable – PV, SV, etc…). These parameters incorporate critical diagnostics from the wireless field device as well as communication status.
39
Section 5: Host Integration
January 2015
40
Reference Manual
00809-0200-4420, Rev HB
Note
The **_HEALTHY parameters are a great indication of the health and communications status of the data values.
State (state value): The value of a data point which drives a Modbus output of 1. For example, if a data point is reported as either True or False, a state value of True will report a 1 for True and 0 for False. A state of False will report a 0 for True and a 1 for False. State is only required for register numbers 0-19999 (Boolean, bit, coil, binary, etc…).
Invert: This check box will invert the Modbus output from a 1 to a 0 or a 0 to a 1. Invert is only used for Boolean values using register numbers 0-19999.
Gain: This value is multiplied to the data value for the purpose of scaling integers. Gain is only required if scaled is chosen on the Modbus communications page and globe gain and offset is not chosen.
Offset: This value is added to the data value for the purpose of scaling integers. Offset is only required if scaled is chosen on the Modbus communications page and globe gain and offset is not chosen.
Predefined Modbus registers
In addition to user configurable parameters, the Gateway also supports a list of predefined
Modbus registers with diagnostics and test parameters. The following table is a list of the predefined Modbus registers.
Table 5-2. Predefined Modbus Registers
Description
Current Year (1)
Current Month (1)
Current Day (1)
Current Hour (1)
Current Minute (1)
Current Second (1)
Messages Received
Corrupt Messages Received
Messages Sent With Exception
Messages Sent Count
Valid Messages Ignored
Constant Float 12345.0
SYSTEM_DIAG.HART_DEVICES
SYSTEM_DIAG.ADDITIONAL_STATUS_0
SYSTEM_DIAG.ADDITIONAL_STATUS_1
SYSTEM_DIAG.ADDITIONAL_STATUS_2
SYSTEM_DIAG.ADDITIONAL_STATUS_3
Register
49009
49010
49011
49012
49014
49015
49016
49017
49018
49001
49002
49003
49004
49005
49006
49007
49008
Data type
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32-bit int
32 float
32-bit int
8-bit unsigned int
8-bit unsigned int
8-bit unsigned int
8-bit unsigned int
Host Integration
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 9 Safety messages
- 9 Introduction
- 10 Manual
- 11 Service support
- 11 Return of materials
- 12 Product recycling/disposal
- 13 Overview
- 14 System requirements
- 14 Initial setup
- 14 Prepare PC/laptop
- 15 Connections and power
- 16 Configure the Gateway
- 20 System backup
- 21 Overview
- 21 General considerations
- 22 Physical description
- 22 Mounting
- 23 Pipe mount
- 23 Bracket mount (alternate)
- 24 Remote antenna (optional)
- 27 Connecting
- 27 Grounding
- 27 Ethernet
- 29 Terminating resistors
- 30 Power
- 31 Overview
- 32 System requirements
- 33 Software installation
- 34 Security Setup Utility
- 35 Setup
- 36 AMS Wireless Configurator
- 36 Setup
- 38 Licensing and credits
- 39 Overview
- 39 Network architecture
- 43 Internal firewall
- 44 Modbus
- 44 Communication settings
- 46 Register mapping
- 49 Ethernet/IP
- 59 Functional specifications
- 60 Physical specifications
- 60 Communication specifications
- 61 Self-organizing network specifications
- 62 System security specifications
- 63 Dimensional drawings
- 65 Ordering information
- 66 Accessories and spare parts
- 67 Approved manufacturing locations
- 67 Telecommunication compliance
- 67 FCC and IC
- 67 Ordinary Location Certification for FM
- 68 European Union Directive Information
- 71 Overview
- 71 Latency considerations in control logic design and operation
- 71 Requirements
- 72 Mounting and connecting
- 72 Setup
- 75 Overview
- 75 Requirements
- 75 Setup
- 78 Mounting and connections
- 82 Diagnostics
- 83 Gateway replacement