Smart Wireless Gateway

Reference Manual

00809-0200-4420, Rev HB

January 2015

Reference Manual

00809-0200-4420, Rev HB

Smart Wireless Gateway

Smart Wireless Gateway

January 2015

NOTICE

Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the Contents before installing, using, or maintaining this product.

Within the United States, Emerson Process Management has two toll-free assistance numbers:

Global Service Center

Software and Integration Support

1-800-833-8314 (United States)

+63-2-702-1111 (International)

Customer Central

Technical support, quoting, and order-related questions.

1-800-999-9307 (7:00 am to 7:00 pm CST)

North American Response Center

Equipment service needs.

1-800-654-7768 (24 hours—includes Canada)

Outside of the United States, contact your local Emerson Process Management representative.

The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.

For information on Rosemount nuclear-qualified products, contact your local Emerson

Process Management Sales Representative.

i

Reference Manual

00809-0200-4420, Rev HB

Table of Contents

January 2015

Contents

1

Section 1: Overview

1.1

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.2

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.3

Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.4

Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.5

Return of materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.6

Product recycling/disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2

Section 2: Initial Connection

2.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.2

System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3

Initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3.1

Prepare PC/laptop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3.2

Connections and power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.3.3

Configure the Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.3.4

System backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

3

Section 3: Mounting and Connection

3.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

3.1.1

General considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

3.1.2

Physical description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

3.2

Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

3.2.1

Pipe mount. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

3.2.2

Bracket mount (alternate). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

3.3

Remote antenna (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

3.4

Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

3.4.1

Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

3.4.2

Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

3.4.3

RS-485. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

3.4.4

Terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

3.4.5

Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Table of Contents iii

Table of Contents

January 2015

Reference Manual

00809-0200-4420, Rev HB

4

Section 4: Software Setup

4.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

4.2

System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

4.3

Software installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

4.4

Security Setup Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

4.4.1

Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

4.5

AMS Wireless Configurator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

4.5.1

Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

4.6

Licensing and credits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

5

Section 5: Host Integration

5.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

5.2

Network architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

5.3

Internal firewall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

5.4

Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

5.4.1

Communication settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

5.4.2

Register mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38

5.5

Ethernet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41

6

Section 6: Troubleshooting

7

Section 7: Glossary

A

Appendix A: Product Specifications

A.1

Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51

A.2

Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

A.3

Communication specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

A.4

Self-organizing network specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53

A.5

System security specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

A.6

Dimensional drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55

A.7

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57

A.8

Accessories and spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

iv Table of Contents

Reference Manual

00809-0200-4420, Rev HB

Table of Contents

January 2015

B

Appendix B: Product Certifications

B.1

Approved manufacturing locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

B.2

Telecommunication compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

B.3

FCC and IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

B.4

Ordinary Location Certification for FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

B.5

European Union Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60

C

Appendix C: DeltaV™ Ready

C.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63

C.2

Latency considerations in control logic design and operation. . . . . . . . . . . . . . . .63

C.3

Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63

C.4

Mounting and connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64

C.5

Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64

D

Appendix D: Redundancy

D.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67

D.2

Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67

D.3

Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67

D.4

Mounting and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70

D.5

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74

D.6

Gateway replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75

Table of Contents v

Table of Contents

January 2015

Reference Manual

00809-0200-4420, Rev HB vi Table of Contents

Reference Manual

00809-0200-4420, Rev HB

Section 1: Overview

January 2015

Section 1

1.1

Overview

Safety messages

Instructions and procedures in this manual may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Refer to these safety messages before performing an operation preceded by this symbol.

1.2

Failure to follow these installation guidelines could result in death or serious injury.

Make sure only qualified personnel perform the installation.

Explosions could result in death or serious injury.

 Verify the operating atmosphere of the device is consistent with the appropriate hazardous locations certifications.

Electrical shock could cause death or serious injury.

 Use extreme caution when making contact with the leads and terminals.

Introduction

The Smart Wireless Gateway connects WirelessHART ® self-organizing networks with host systems and data applications. Modbus ® communications over RS-485 or Ethernet LAN provide universal integration and system interoperability. The optional OPC functionality from the

Gateway offers a means to connect to newer systems and applications while providing a richer set of data.

The Smart Wireless Gateway provides industry leading security, scalability, and data reliability.

Layered security ensures that the network stays protected. Additional devices can be added at anytime. There is no need to configure communication paths because the Gateway manages the network automatically. This feature also ensures that WirelessHART field devices have the most reliable path to send data.

Overview

1

2

Section 1: Overview

January 2015

1.3

Reference Manual

00809-0200-4420, Rev HB

What is included?

The box containing the Smart Wireless Gateway contains several items essential to the complete installation and operation of the Gateway.

Smart Wireless Gateway

Quick Start Guide

Software pack, 2 disk set

Mounting hardware

Conduit plugs, 4

Conduit adapters (optional)

If an optional remote antenna has been ordered, it will be in a separate box containing:

Remote mount antenna

Mounting hardware

Lightning arrestor

Cable [1 or 2 pieces that total 50 ft, (15,2 m) in length]

Coaxial sealant

Manual

This manual will help to install, configure, operate, and maintain the Gateway.

Section 1: Overview

This section introduces the product and describes what components may be found in the box. It also includes details for services and support as well as return and disposal of the product.

Section 2: Initial Connection

This section describes how to connect to the Gateway for the first time and what settings should be configured before placing it on a live control network. It is important to note that some

Gateways are used in stand-alone applications and do not reside on a network. In these cases, it is still important to configure the items outlined in this section.

Section 3: Mounting and Connection

This section describes how to properly mount the Gateway and make electrical connections, including electrical wiring, grounding, and host system connections. This section also describes how to mount the optional remote antenna.

Section 4: Software Setup

This section describes the installation and setup of the optional software included with the

Smart Wireless Gateway. This software will aid in secure host integration as well as wireless field device configuration.

Section 5: Host Integration

This section describes how to connect the Gateway to a host system and integrate data gathered from the field device network. It covers network architectures, security, and data mapping.

Overview

Reference Manual

00809-0200-4420, Rev HB

1.4

1.5

Section 1: Overview

January 2015

Section 6: Troubleshooting

This section provides troubleshooting tips as well as information to contact technical support over the phone or through email.

Section 7: Glossary

The glossary defines terms used throughout this manual or that appear in the web interface of the Smart Wireless Gateway.

Appendices

The appendices provide additional and more specific information on a variety of subjects including Product Specifications and Product Certifications.

Service support

Global Service Center

Software and Integration Support

United States 1 800 833 8314

International 63 2 702 1111

Customer Central

Technical Support, quoting, and order related questions

United States 1 800 999 9307 (7:00 a.m. to 7:00 p.m. CST)

Asia Pacific 65 6777 8211

Europe/Middle East/Africa 49 8153 9390

Return of materials

To expedite the return process outside of North America, contact your Emerson Process

Management representative.

Within the United States, call the Emerson Process Management Response Center toll-free number 1 800 654 7768. The center, which is available 24 hours a day, will assist you with any needed information or materials.

The center will ask for product model and serial numbers, and will provide a Return Material

Authorization (RMA) number. The center will also ask for the process material to which the product was last exposed.

Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of, and understand, the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data

Sheet (MSDS) for each hazardous substance identified must be included with the returned goods.

Overview

3

Section 1: Overview

January 2015

1.6

Reference Manual

00809-0200-4420, Rev HB

Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.

4

Overview

Reference Manual

00809-0200-4420, Rev HB

Section 2 Initial Connection

Section 2: Initial Connection

January 2015

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5

System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6

Initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6

2.1

Initial Connection

Failure to follow these installation guidelines could result in death or serious injury.

Only qualified personnel should perform the installation.

Explosions could result in death or serious injury.

 Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.

Electrical shock could cause death or serious injury.

Use extreme caution when making contact with the leads and terminals.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:

This device may not cause harmful interference.

This device must accept any interference received, including interference that may cause undesired operation.

This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.

Overview

This section describes how to connect to the Gateway for the first time and what settings should be configured before placing it on a live control network. It is important to note that some

Gateways are used in stand-alone applications and do not reside on a network. In these cases, it is still important to configure the items outlined in this section.

Before the Gateway can be permanently mounted and connected to a live control network, it needs to be configured with an IP address. This is done by forming a private network between the gateway and a PC/laptop. The following items are needed to complete this section:

Gateway

PC/laptop

24 VDC (nominal) power supply

Note

If the Gateway was ordered with the DeltaV

Ready option, it has been configured to operate on a DeltaV control network, and the Initial Configuration Section does not need to be completed.

Only setting the password is required.

5

6

Section 2: Initial Connection

January 2015

2.2

2.3

2.3.1

Reference Manual

00809-0200-4420, Rev HB

System requirements

The following requirements apply to the PC/laptop used to configure the Gateway. Additional requirements may apply if using the optional Security Setup Utility or AMS ® Wireless

Configurator. See 00809-0200-4420, Rev HB for more information.

Web browser applications

Mozilla Firefox

®

1.5 or higher

Microsoft ® Internet Explorer ® 6.0 or higher

Ethernet

10/100BaseTX Ethernet communication protocol

Initial setup

Prepare PC/laptop

5.

6.

3.

4.

1.

2.

The PC/laptop will need to be configured to form a private network before communicating to the Gateway. The network settings can be found in the control panel of the PC/laptop. To configure these settings:

Find and open the Control Panel (Generally found from the Start Menu).

Open Network Connections.

Select Local Area Connection.

Right click the mouse and select Properties from the list.

Select Internet Protocol (TCP/IP), then select Properties.

From the General tab, select Use the following IP address.

7.

8.

9.

10.

Set the IP Address to “192.168.1.12” and select Tab.

A Subnet mask of 255.255.255.0 should fill in automatically.

Select OK to close the Internet Protocol (TCP/IP) window.

Select Close on the Local Area Connection window.

2.

3.

Internet proxies will need to be disabled through the PC/laptop’s default internet browser.

1.

Find and open the default internet browser (typically Microsoft Internet Explorer).

4.

Find the Tools menu and select Internet Options.

From the Connections tab, select LAN Settings.

Under Proxy Server, verify the boxes for Automatically Detect Settings and Use a proxy

server for your LAN are unchecked.

Initial Connection

Reference Manual

00809-0200-4420, Rev HB

2.3.2

Section 2: Initial Connection

January 2015

5.

6.

Select OK to close the Local Area Network (LAN) Settings window.

Select OK to close the Internet Options window.

The PC/laptop is now set up to form a private network and to communicate with the Gateway.

Note

Connecting to the Gateway's secondary Ethernet port will require different network settings.

Please see Table 2-1 for additional network settings.

Table 2-1. Default IP Addresses

Ethernet 1

Ethernet 2

Ethernet 1 (DeltaV Ready)

Ethernet 2 (DeltaV Ready)

Gateway

192.168.1.10

192.168.2.10

10.5.255.254

10.9.255.254

PC/laptop

192.168.1.12

192.168.2.12

10.5.255.200

10.9.255.200

Subnet

255.255.255.0

255.255.255.0

255.254.0.0

255.254.0.0

Connections and power

Physically connect the PC/laptop to the Gateway by connecting one end to the Ethernet port on the back of the PC/laptop. Connect the other end to the Ethernet 1 port on the Gateway.

Figure 2-1

shows the standard terminal block diagram. Once the Gateway and PC/laptop are connected, wire a 24 VDC (nominal) power supply with a capacity of at least 250 mA to the

Gateway power input terminals.

Figure 2-1. Standard Terminal Block

24 VDC

(nominal)

Power Input

Serial

Modbus Not Used Not Used

+ S A B + S S +

Case

Ethernet 2 with Power

(Covered)

Ethernet 2

(Secondary)

Ethernet 1

(Primary)

+ -

Not Used

S S -

Not Used

+

Initial Connection

When making physical connections to the Gateway it is important to use the electrical conduit entries located on the bottom of the housing. Connecting through the open terminal block cover (the lower cover) may stress the connections and damage the

Gateway.

7

8

Section 2: Initial Connection

January 2015

2.3.3

Reference Manual

00809-0200-4420, Rev HB

Configure the Gateway

It is now possible to log into the Gateway for the first time and begin configuration for placement on a live control network. The following items need to be configured:

Security passwords

Time settings

TCP/IP network settings

Use the following procedure to log in to the Gateway:

1.

Open a standard web browser (typically Microsoft Internet Explorer).

4.

5.

2.

3.

Enter “192.168.1.10” in the address bar.

Acknowledge the security to proceed.

In the User Name field, enter “admin”.

In the Password field, enter “default”.

The web browser will now be directed to the Gateway’s default home page. There is a navigation menu located on the left hand side with four main areas.

Diagnostics: view status of communications, client server parameters, and more

Monitor: screens created by the user to view data from field devices

Explorer: basic view of values from field devices

Setup: configure the Gateway for operations, security, and host system integration

Security passwords

There are four-role based user accounts for the gateway with varying levels of access. The table below describes this access.

Table 2-2. Role Based Access User Accounts

Role

Executive

Operator

Maintenance

User name Web interface access exec oper maint

Administrator admin

Read-only access

Read-only access

Configure HART ® device settings

Configure Modbus ® communications

Configure Modbus register mapping

Configure OPC browse tree

Configure Active Advertising

Includes all maintenance privileges

Configure Ethernet network settings

Configure WirelessHART ®

Set passwords

Set time settings

network settings

Set home page options

Configure custom point pages

Restart applications

Initial Connection

Reference Manual

00809-0200-4420, Rev HB

Section 2: Initial Connection

January 2015

2.

3.

Each of the initial passwords for the user accounts is default. It is recommended, for security purposes, that these passwords are changed. The administrator password should be appropriately noted when changed. If it is lost, please contact Emerson Process Management for technical support.

To change the User Accounts Passwords:

1.

Navigate to System Settings>Users>User accounts.

Set the new password for each role based user account, and confirm.

Click Submit.

Note

It is suggested that the default security settings in System Settings>Users>User accounts be changed to the local IT best practices or the Normal setting after initial login. Strong or custom settings are available for more robust passwords. For more information on this screen and others please see the User Interface Terminology Guide (document number 00809-0600-4420).

Time settings

The Gateway is the timekeeper for the WirelessHART network, so it is imperative that the

Gateway’s time is accurate for timestamp data to be meaningful. Time settings can be found by navigating to System Settings>Time.

There are three ways to set the Gateway time:

Network Time Protocol (recommended)

This option uses a Network Time Protocol (NTP) server to slowly adjust the Gateway’s time in order to match the time of the control network. Enter the IP address for the NTP server and select the packet version (1, 2, 3, or 4).

Set with PC Time

This option will match the Gateway’s time to that of the PC/laptop.

Manual Entry

This option allows the user to enter a specific date (MM:DD:YY) and time (HH:MM:SS).

Note

Network Time Protocol (NTP) is recommended for the best network performance because it always adjusts time to match the network time server.

Initial Connection

9

Section 2: Initial Connection

January 2015

Figure 2-2. Time Settings

Reference Manual

00809-0200-4420, Rev HB

10

TCP/IP network settings

Use caution when making changes to the TCP/IP network settings. If they are lost or improperly configured, it may be impossible to log into the Gateway. Contact the network administrator for information on the proper TCP/IP network settings to apply.

Prior to the gateway being installed and connected to a live control network, it should be configured with an IP address, as well as other TCP/IP network settings.

Request the following configuration items from the network administrator:

Specify an IP address, or use a DHCP server

Hostname

Domain Name

IP address

Netmask

Gateway

Obtaining an IP address from a DHCP server is not recommended, since the Gateway operation will be dependent upon the availability of the DHCP server. For maximum gateway availability it is best practice to specify an IP address.

Initial Connection

Reference Manual

00809-0200-4420, Rev HB

Section 2: Initial Connection

January 2015

6.

7.

4.

5.

2.

3.

To change the TCP/IP Network Settings:

1.

Navigate to System Settings>Gateway>Ethernet Communication.

Select Specify an IP address (recommended).

Enter the following:

Hostname

Domain Name

IP Address

Netmask

Gateway

Click Submit.

When prompted, click Restart apps.

Click Yes to confirm restart.

Close the web browser.

Note

Once the IP Address of the Gateway has been changed, communications to the web interface will be lost. Restart the web browser, then log back into the Gateway using the new IP address and other TCP/IP network settings. The PC/laptop TCP/IP network settings may need to be changed.

Initial Connection

11

Section 2: Initial Connection

January 2015

Figure 2-3. Ethernet Settings

Reference Manual

00809-0200-4420, Rev HB

2.3.4

12

System backup

4.

5.

6.

1.

2.

The Gateway has a System Backup and Restore feature that saves all user-configured data. It is best practice that a System Backup be performed periodically throughout the installation and configuration process.

3.

Navigate to System Settings>Gateway>Backup And Restore>Save Backup.

Click Save Backup.

The Gateway collects the configuration date and when the file download pop up appears, click Save.

Enter a save location and file name.

Enter Save.

Click Return to form.

Note

System backup contains user passwords and keys used for encrypting communication. Store downloaded system backups in a secure location.

Initial Connection

Reference Manual

00809-0200-4420, Rev HB

Section 3

Section 3: Mounting and Connection

January 2015

Mounting and Connection

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13

Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14

Remote antenna (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16

Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19

Explosions could result in death or serious injury.

 Verify that the operating atmosphere of the device is consistent with the appropriate hazardous locations certifications.

Electrostatic discharge can damage electronics.

 Use proper personal grounding before handling electronics or making contact with leads and terminals.

Electrical shock could cause death or serious injury. If the device is installed in a high-voltage environment and a fault condition or installation error occurs, high voltage may be present on transmitter leads and terminals.

 Use extreme caution when making contact with the leads and terminals.

Failure to follow these installation guidelines could result in death or serious injury.

Make sure only qualified personnel perform the installation.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:

This device may not cause harmful interference.

This device must accept any interference received, including interference that may cause undesired operation.

This device must be installed to ensure a minimum antenna separation distance of

20 cm from all persons.

3.1

3.1.1

Overview

This section describes how to properly mount the Gateway and make electrical connections, including electrical wiring, grounding, and host system connections. This section also describes how to mount the optional remote antenna.

General considerations

The Smart Wireless Gateway may be mounted in any general purpose location. Be sure the covers are secured tightly to prevent exposure of any electronics to moisture and contamination.

The Gateway should be mounted in a location that allows convenient access to the host system network (process control network) as well as the wireless field device network.

Mounting and Connection

13

Section 3: Mounting and Connection

January 2015

3.1.2

3.2

Reference Manual

00809-0200-4420, Rev HB

Physical description

For dimensional drawing information refer to 00809-0200-4420, Rev HB. The cast aluminum housing encloses the electronics circuitry of the Gateway. The front of the enclosure has an upper cover and a junction box cover. The upper cover provides access to the electronics and radio. The junction box cover provides access to the terminal block.

To open either cover, use a ¼-in. bladed screwdriver to remove the appropriate screw on the unhinged side of the enclosure.

Mounting

Find a location where the Gateway has optimal wireless performance. Ideally this will be 15-25 ft. (4,6 - 7,6 m) above the ground or 6 ft. (2 m) above obstructions or major infrastructure.

Figure 3-1

shows an example gateway installation.

Figure 3-1. Gateway Installation

E E

(4,6-7,6 m)

A A

A. Control Room

B. Ground

C. Gateway

D. Mast or Pipe

E. Infrastructure

14

Mounting and Connection

Reference Manual

00809-0200-4420, Rev HB

3.2.1

Section 3: Mounting and Connection

January 2015

Pipe mount

2.

3.

The following hardware and tools are needed to mount the Gateway to a 2-in. pipe:

Two 5 /

16

-in. u-bolts (supplied with Gateway)

2-in. mounting pipe

½-in. socket-head wrench

Mount the Gateway using the following procedure:

1.

Insert one u-bolt around the pipe, through the top mounting holes of the Gateway enclosure, and through the washer plate.

Use a 1 /

2

-in. socket-head wrench to fasten the nuts to the u-bolt.

Repeat for the second u-bolt and the lower mounting holes.

Figure 3-2. Pipe Mount

3.2.2

Bracket mount (alternate)

The following hardware and tools are needed to mount the Gateway to a support bracket:

Four 15 /

16

-in. bolts

Mounting support bracket

3 /

8

-in. drill

1 /

2

-in. socket-head wrench

Mount the Gateway using the following procedure:

1.

Drill four 3 /

8

-in. (9,525 mm) holes spaced 3.06-in. (77 mm) apart horizontally and

11.15-in. (283 mm) apart vertically in the support bracket, corresponding with the holes on the Gateway enclosure.

2.

Using a 1 /

2

-in. socket-head wrench, attach the Gateway to the support bracket with four

15 /

16

-in. bolts.

Mounting and Connection

15

Section 3: Mounting and Connection

January 2015

3.3

Remote antenna (optional)

Reference Manual

00809-0200-4420, Rev HB

The remote antenna options provide flexibility for mounting the Gateway based on wireless connectivity, lightning protection, and current work practices.

When installing remote mount antennas for the Smart Wireless Gateway, always use established safety procedures to avoid falling or contact with high-power electrical lines.

Install remote antenna components for the Smart Wireless Gateway in compliance with local and national electrical codes and use best practices for lightning protection.

Before installing consult with the local area electrical inspector, electrical officer, and work area supervisor.

The Smart Wireless Gateway remote antenna option is specifically engineered to provide installation flexibility while optimizing wireless performance and local spectrum approvals.

To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change the length of cable or the antenna type.

If the supplied remote mount antenna kit is not installed per these instructions, Emerson

Process Management is not responsible for wireless performance or non-compliance with spectrum regulations.

3.

4.

1.

2.

The remote mount antenna kit includes coaxial sealant for the cable connections for the lightning arrestor and antenna.

Find a location where the remote antenna has optimal wireless performance. Ideally this will be

15-25 ft (4,6 - 7,6 m) above the ground or 6 ft (2 m) above obstructions or major infrastructure.

To install the remote antenna use one of the following procedures:

Installation of WL2/WN2 option (outdoor applications)

5.

6.

Mount the antenna on a 1.5-2 inch pipe mast using the supplied mounting equipment.

Connect the lightning arrestor directly to the top of the Gateway.

Install the grounding lug, lock washer, and nut on top of the lightning arrestor.

Connect the antenna to the lightning arrestor using the supplied coaxial cable ensuring the drip loop is not closer than 1 foot (0,3 m) from the lightning arrestor.

Use the coaxial sealant to seal each connection between the wireless field device, lightning arrestor, cable, and antenna.

Ensure the mounting mast, lightning arrestor, and Gateway are grounded according to local/national electrical code.

Note

Any spare lengths of coaxial cable should be placed in 12 inch (0,3 m) coils.

16

Mounting and Connection

Reference Manual

00809-0200-4420, Rev HB

Figure 3-3. Installation of WL2/WN2 Option

B

Section 3: Mounting and Connection

January 2015

A

A. Control Building

B. Remote Antenna

C. Cable

D. Drip Loop

H

F

G

E

G

D

C

E. Lightning Arrestor

F. Gateway

G. Ground

H. Earth

5.

6.

3.

4.

1.

2.

Installation of WL3/WL4 Option (indoor to outdoor applications)

7.

Mount the antenna on a 1.5-2 inch pipe mast using the supplied mounting equipment.

Mount the lightning arrestor near the building egress.

Install the grounding lug, lock washer, and nut on top of lightning arrestor.

Connect the antenna to the lightning arrestor using the supplied coaxial cable ensuring the drip loop is not closer than 1 foot (0,3 m) from the lightning arrestor.

Connect the lightning arrestor to the Gateway using the supplied coaxial cable.

Use the coaxial sealant to seal each connection between the Gateway, lightning arrestor, cable, and antenna.

Ensure that the mounting mast, lightning arrestor, and Gateway are grounded according to local/national electrical codes.

Note

Any spare lengths of coaxial cable should be placed in 12 inch (0,3 m) coils.

Mounting and Connection

17

Section 3: Mounting and Connection

January 2015

Figure 3-4. Installation of WL3/WL4 Option

B

Reference Manual

00809-0200-4420, Rev HB

A

F

G

E

G

H

D

C

E. Lightning Arrestor

F. Gateway

G. Ground

H. Earth

A. Control Building

B. Remote Antenna

C. Cable

D. Drip Loop

Note: Weather proofing is required!

The remote mount antenna kit includes coaxial sealant for the cable connections for the lightning arrestor, antenna, and Gateway. The coaxial sealant must be applied to guarantee performance of the wireless field network. See

Figure 3-5 for details on how to apply weather

proofing.

Figure 3-5. Applying Coaxial Sealant to Cable Connections

18

Mounting and Connection

Reference Manual

00809-0200-4420, Rev HB

3.4

3.4.1

Section 3: Mounting and Connection

January 2015

Table 3-1. Remote Antenna Kit Options

Kit option Antenna

WL2

WL3

WL4

WN2

1 /

2

Wavelength

Dipole

Omni-Directional

+6 dB Gain

1 /

2

Wavelength

Dipole

Omni-Directional

+6 dB Gain

1 /

2

Wavelength

Dipole

Omni-Directional

+6 dB Gain

1 /

2

Wavelength

Dipole

Omni-Directional

+8 dB Gain

Cable 1

50 ft. (15,2 m)

LMR-400

30 ft. (9,1 m)

LMR-400

40 ft. (12,2 m)

LMR-400

25 ft. (7,6 m)

LMR-400

Cable 2

N/A

20 ft. (6,1 m)

LMR-400

10 ft. (3,0 m)

LMR-400

N/A

Lightning arrestor

Head mount, jack to plug

Gas discharge tube

0.5 dB insertion loss

In-line, jack to jack

Gas discharge tube

0.5 dB insertion loss

In-line, jack to jack

Gas discharge tube

0.5 dB insertion loss

Head mount, jack to plug

Gas discharge tube

0.5 dB insertion loss

Connecting

All connections to the Gateway can be made at the terminal block, which is located in the lower junction box section of the enclosure. The terminal block label is located on the inside of the

lower cover. See Figure 3-6 for the standard terminal block label.

The junction box portion of the enclosure has four conduit entries for power and communications wiring. Do not run communication wiring in conduit or open trays with power wiring, or near heavy electrical equipment.

Install the included conduit plugs in any unused conduit openings. For NEMA

®

4X and IP65 requirements, use thread seal (PTFE) tape or paste on male threads to provide a watertight seal.

Grounding

The Gateway enclosure case should always be grounded in accordance with national and local electrical codes. The most effective grounding method is a direct connection to earth ground with minimal impedance. Ground the Gateway by connecting the external grounding lug to earth ground. The connection should be 1 Ω or less. The external ground lug is located below the Gateway enclosure and is identified by the following symbol:

3.4.2

Ethernet

The Gateway is equipped with two 10/100BaseTX Ethernet communications ports (see

Figure 3-6

). These connections can be used to access the Gateway’s web interface and to communicate Modbus TCP and OPC protocols.

The primary Ethernet port (Ethernet 1) is used to connect to the host system or other application systems. The secondary Ethernet port (Ethernet 2) can be used as a back up connection or a maintenance port for local access to the Gateway.

Mounting and Connection

19

Section 3: Mounting and Connection

January 2015

Reference Manual

00809-0200-4420, Rev HB

Figure 3-6. Terminal Block Diagram

24 VDC

(nominal)

Power Input

Serial

Modbus

+ S A B

Case

+

Not Used

S S

Not Used

+

Ethernet 2 with Power

(Covered)

Ethernet 2

(Secondary)

Ethernet 1

(Primary)

+ -

Not Used

S S -

Not Used

+

3.4.3

Ethernet connections should use Cat5E shielded cable to connect to an Ethernet hub, switch, or router. The maximum cable length should not exceed 328 ft. (100 m).

Note

Unless dual Ethernet ports were specified at the time of order, the secondary Ethernet port

(Ethernet 2) will not be active.

RS-485

The Gateway may be ordered with an optional RS-485 (serial) connection (

Figure 3-6 ). It is

referenced by the A and B Serial Modbus terminals. This connection is used to communicate

Modbus RTU on an RS-485 data bus.

Use 18 AWG single twisted shielded pair wiring to connect the Gateway to the RS-485 data bus.

The total bus length should not exceed 4000 ft. (1220 m). Connect the Tx + (positive, transmit) wire to terminal A and the Rx - (negative, receive) wire to terminal B. The wiring shield should be trimmed close and insulated from touching the Gateway enclosure or other terminations.

If the existing data bus uses a 4 wire Full Duplex configuration, see Figure 3-7

to convert to a

2-wire Half Duplex configuration.

Figure 3-7. Convert from Full to Half Duplex

Tx

Rx

Tx

Rx

(A)

(B)

20

Mounting and Connection

Reference Manual

00809-0200-4420, Rev HB

3.4.4

Section 3: Mounting and Connection

January 2015

Terminating resistors

Three DIP switches are provided to enable various terminating resistors to the RS-485 data bus.

The switches are found inside the electronics housing near the top center of the main circuit

board ( Figure 3-8

).

Figure 3-8. RS-485 Resistor DIP Switches

DIP Switches

470Ω Pull-down Resistor Main Circuit Board

120Ω Terminating Resistor

Radio

Electronics

470Ω Pull-up Resistor

Switches 1 and 3 are connected to pull-up and pull down resistors. Switch 1 is for the Tx + (A) line and Switch 3 is for the Rx – (B) line. These 470 Ù resistors are used to prevent noise from being interpreted as valid communications during periods when no actual communications are occurring. Only one set of pull-up and pull-down resistors should be active on the RS-485 data bus at time.

Switch 2 is connected to a 120 Ω terminating resistor. This resistor is used to dampen signal reflections on long cable runs. RS-485 specifications indicate that the data bus should be terminated at both ends (

Figure 3-9 ). However termination should only be used with high data

rates (above 115 kbps) and long cable runs.

Figure 3-9. Typical Half Duplex (2-wire) Network

Up to 4000 ft. (1220 m)

A

Device 1

Device 2

B

Device N

(up to 32 possible)

Terminators required only for high data rates and long cable runs

Mounting and Connection

21

Section 3: Mounting and Connection

January 2015

3.4.5

Reference Manual

00809-0200-4420, Rev HB

Power

The Gateway is designed to be powered by 24 VDC (nominal) and requires 250 mA of current.

The positive and negative connections are found on the left side of the terminal block

(

Figure 3-6

). An additional case ground is found on the left side of the junction box enclosure.

Connect supply power to the positive + and negative – power terminals found on the left side of the terminal block (

Figure 3-6 ). Recommended torque is 7 in-lbs and the gauge is 12 to 22 AWG.

An additional internal case ground can be found on the left side of the enclosure. The wiring should include an external power shut-off switch or circuit breaker that is located near the

Gateway.

Note

Using an uninterruptible power supply (UPS) is recommended to ensure availability should there be a loss of power.

22

Mounting and Connection

Reference Manual

00809-0200-4420, Rev HB

Section 4

4.1

Software Setup

Section 4: Software Setup

January 2015

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23

System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24

Software installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25

Security Setup Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26

AMS Wireless Configurator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 28

Licensing and credits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30

Overview

This section discusses the installation and setup of the optional software included with the

Smart Wireless Gateway. This software is not required for the wireless field network to operate; however, it will aid in secure host integration as well as wireless field device configuration. The following table describes what items are installed and on which disk they can be found.

Table 4-1. Software Applications

Name

Security Setup Utility

AMS ® Wireless

Configurator

Network

Configuration

Description

This utility allows the setup of SSL enabled communications between the Gateway and host system.

This application allows complete configuration of wireless field devices and provides added security through drag and drop provisioning.

This application configures AMS Wireless

Configurator to interface to a Wireless

Network or a HART

®

Modem.

Location

Disk 1

Disk 2

Disk 2

Additional system components may be installed depending on the current configuration of the system.

Software Setup

23

Section 4: Software Setup

January 2015

4.2

Reference Manual

00809-0200-4420, Rev HB

System requirements

Table 4-2. PC Hardware

Minimum requirements

Intel ™ Core 2 Duo, 2.0 GHz

1 GB Memory

1.5 GB free hard disk space

Recommended requirements

Intel Core 2 Quad, 2.0 GHz or greater

3 GB Memory or Greater

2 GB or more of free hard disk space

Note

Additional hard disk space is required for SNAP-ON

applications. The minimum monitor requirements are 1024 x 768 resolution and 16-bit color.

Table 4-3. Supported Operating Systems

Operating system

Windows ™ XP

Windows Server 2003

Windows Server 2003 R2

Windows Server 2008

Windows Server 2008 R2

Windows 7

Windows 7

Version

Professional, Service Pack 3

Standard, Service Pack 2

Standard, Service Pack 2

Standard, Service Pack 2

Standard, Service Pack 1

Professional, Service Pack 1

Enterprise, Service Pack 1

Note

Only 32-bit versions of the operating systems are supported for AMS Wireless Configurator.

24

Software Setup

Reference Manual

00809-0200-4420, Rev HB

4.3

Section 4: Software Setup

January 2015

Software installation

6.

7.

8.

4.

5.

2.

3.

The software can be found on the 2 disk pack, included with the Gateway. Depending on the PC system configuration, installation may take 30-35 minutes. Installing both disks in order is recommended. The Security Setup Utility is located on Disk 1. To install the software:

1.

Exit/close all Windows programs, including any running in the background, such as virus scan software.

2.

3.

Insert Disk 1 into the CD/DVD drive of the PC.

Follow the prompts.

AMS Wireless Configurator is located on Disk 2. To install the software:

1.

Exit/close all Windows programs, including any running in the background, such as virus scan software.

Insert Disk 2 into the CD/DVD drive of the PC.

Select Install from the menu when the AMS Wireless Configurator setup begins.

Follow the prompts.

Allow AMS Wireless Configurator to reboot PC.

Do not remove the disk from the CD/DVD drive.

Installation will resume automatically after login.

Follow the prompts.

Note

If the autorun function is disabled on the PC, or installation does not begin automatically, double click D:\SETUP.EXE (where D is the CD/DVD drive on the PC) and select OK.

Software Setup

25

Section 4: Software Setup

January 2015

4.4

Reference Manual

00809-0200-4420, Rev HB

Security Setup Utility

The Security Setup Utility enables secure communications between the Gateway and host system, asset management software, data historians, or other applications. This is done by encrypting the standard data protocols (AMS Wireless Configurator, Modbus TCP, Ethernet/IP ™ , and OPC) used by the Gateway and making them available through various proxies within the

Security Setup Utility. These proxies can function as a data server for other applications on the control network. The Security Setup Utility can support multiple Gateways at once and each proxy can support multiple client application connects.

Figure 4-1

shows a typical system architecture using the Security Setup Utility.

Figure 4-1. Typical Host System Architecture Using Security Setup

26

Note

OPC communications requires the use of the Security Setup Utility regardless of whether encryption is required.

Software Setup

Reference Manual

00809-0200-4420, Rev HB

4.4.1

Section 4: Software Setup

January 2015

Setup

4.

5.

2.

3.

In the Security Setup Utility add a new proxy for each Gateway based on the communication protocol that is being used. For example, add an OPC proxy for each Gateway that is communicating OPC.

Use the following procedure to add a new proxy in the Security Setup Utility:

1.

Open the Security Setup Utility.

Select EDIT>NEW, then select the type of new proxy to be added.

Right click on the new proxy entry and select Properties.

Enter the target Gateway’s Hostname and IP Address.

Select OK.

8.

9.

6.

7.

Select FILE>SAVE.

When prompted for authentication, enter the admin password for the target Gateway.

Select OK.

Repeat

Step 2 Step 8 to added additional proxies.

10.

Select FILE>EXIT to close the Security Setup Utility.

During this process, the Gateway will exchange security certificates (digital signatures) with the proxy.

Figure 4-2. Security Setup Utility

Software Setup

27

Section 4: Software Setup

January 2015

4.5

4.5.1

28

Reference Manual

00809-0200-4420, Rev HB

AMS Wireless Configurator

AMS Wireless Configurator helps deploy and configure wireless field devices. It provides an integrated operating environment that leverages the full capabilities of WirelessHART ® , including embedded data trending, charting, and graphical display capabilities provided by enhanced EDDL technology.

Display and modify device configuration

View device diagnostics

View process variables

Provision a wireless device using the drag-and-drop operation so it can join a Gateway’s self-organizing network

Enhance AMS Wireless Configurator functionality with the AMS Wireless SNAP-ON

Application

Restrict access to AMS Wireless Configurator functions through the use of security permissions

See the release notes for information specific to the current release of AMS Wireless

Configurator. To display the release notes, select START>PROGR>AMS WIRELESS

CONFIGURATOR>HELP.

Setup

AMS Wireless Configurator supports connectivity to a Wireless Network and a HART Modem.

Both of these interfaces must be configured through the Network Configuration application. To run this application, select START>PROGR>DEVICE MANAGER>NETWORK CONFIGURATION.

Note

Do not have the Security Setup Utility running at the same time as the Network Configuration application or a configuration error might occur.

8.

9.

10.

6.

7.

4.

5.

2.

3.

Use the following procedure to configure a wireless network for AMS Wireless Configurator:

1.

Open the Network Configuration application.

Select Add.

Select Wireless Network and select Install.

Select Next.

Enter a name for the wireless network and select Next.

Enter the HostName or IP Address for the Gateway and select Add.

Repeat

Step 6 if multiple Gateways need to be added.

Check the box to Enable Secure Communications with the Smart Wireless Gateway.

Select Finish to close the configuration window.

Select Close to exit the Network Configuration application.

Software Setup

Reference Manual

00809-0200-4420, Rev HB

Figure 4-3. Wireless Network in the Network Configuration

Section 4: Software Setup

January 2015

Software Setup

7.

8.

9.

10.

11.

4.

5.

6.

2.

3.

Use the following procedure to configure a HART modem for AMS Wireless Configurator:

1.

Open the Network Configuration application.

Click Add…

Select HART modem and click Install…

Click Next.

Enter a name for the HART modem and click Next.

Select the HART master type (default is AMS Wireless Configurator will be Primary HART master) and click Next.

Select the COM port for the HART modem and click Next.

Check the box to Check to support Multi Drop devices.

Check the box to Include WirelessHART Adapter.

Click Finish to close the configuration window.

Click Close to exit the Network Configuration application.

29

Section 4: Software Setup

January 2015

4.6

Reference Manual

00809-0200-4420, Rev HB

Licensing and credits

The latest licensing agreements are included on each disk of the software pack.

“This product includes software developed by the OpenSSL Project for use in the OpenSSL

Toolkit. (http://www.openssl.org/)”

“This product includes software written by Eric Young ([email protected])”

30

Software Setup

Reference Manual

00809-0200-4420, Rev HB

Section 5

5.1

5.2

Host Integration

Section 5: Host Integration

January 2015

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 31

Network architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 31

Internal firewall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 35

Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36

Ethernet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 41

Overview

This section describes how to connect the Gateway to a host system and integrate data gathered from the field device network. It covers network architectures, security, and data mapping.

In accordance with Emerson WirelessHART ® security guidelines, the Emerson Gateway should be connected to the host system via a LAN (Local Area Network) and not a WAN (Wide Area

Network).

Network architecture

Physical connection types are important when determining the network architecture and what protocols can be used for integration. Ethernet is the primary physical connection type and

RS-485 is available an optional connection type. The following network architecture diagrams will help when integrating data from the Gateway into the host system.

Ethernet

An Ethernet connection supports Modbus ® TCP, OPC, AMS ® Wireless Configurator,

Ethernet/IP ™ , and HART ® TCP protocols. Using this connection type, the Gateway is wired directly to a control network (see

Figure 5-1 ) using a network switch, router, or hub. There are

often two networks for redundancy purposes.

Host Integration 31

Section 5: Host Integration

January 2015

Figure 5-1. Ethernet LAN Architecture

A

Reference Manual

00809-0200-4420, Rev HB

D

B

C

A. Engineering Station

B. Primary Control Network

C. Secondary Control Network

D.Controller and I/O

E. Smart Wireless Gateway

E

Fiber optic (optional)

A Fiber optic connection supports Modbus TCP, OPC, AMS Wireless Configurator, and HART TCP protocols. Using this connection type, the Gateway is wired to a fiber optic switch (see

Figure 5-2

).

Note

A fiber optic connection requires a third party copper Ethernet to fiber optic Ethernet converter.

32 Host Integration

Reference Manual

00809-0200-4420, Rev HB

Figure 5-2. Fiber Optic LAN Architecture

A

Section 5: Host Integration

January 2015

B

D

C

E

G

F

H

A. Engineering Station

B. Primary Control Network

C. Secondary Control Network

D.Controller and I/O

E.Fiber Optic Switch

F. Fiber Optic

G. Copper to Fiber Converter

H. Smart Wireless Gateway

RS-485 (serial)

An RS-485 connection supports Modbus RTU protocol. Using this connection type, the Gateway is wired to an RS-485 bus which typically leads to a serial I/O card or Modbus I/O card (see

Figure 5-3

). Up to 31 Gateways can be connected to a single I/O card in this manner.

Host Integration 33

Section 5: Host Integration

January 2015

Figure 5-3. RS-485 LAN Architecture

A

D

B

C

E

F

Reference Manual

00809-0200-4420, Rev HB

A. Engineering Station

B. Primary Control Network

C. Secondary Control Network

D.Controller and I/O

G

E Serial I/O Card

F. RS485 Bus

G. Smart Wireless Gateway

34 Host Integration

Reference Manual

00809-0200-4420, Rev HB

5.3

Section 5: Host Integration

January 2015

Internal firewall

The Gateway supports an internal firewall that inspects both incoming and outgoing data packets. TCP ports for communication protocols are user configurable, including user specified port numbers and the ability to disable ports.

The Gateway’s internal firewall settings can be found by navigating to System Settings>

Protocols>Protocols and Ports.

Figure 5-4. Security Protocols Page (Internal Firewall)

Host Integration 35

Section 5: Host Integration

January 2015

5.4

5.4.1

Reference Manual

00809-0200-4420, Rev HB

Modbus

The Gateway supports both Modbus RTU over the RS-485 serial port and Modbus TCP over

Ethernet. It functions as a sub device on the Modbus network and must be polled by a Modbus master or client (host system).

Communication settings

It is import that the Modbus communication settings in the Gateway match the setting in the

Modbus master or client. Please refer to host system documentation for more information on how to configure these settings. The Modbus communication settings can be found by navigating to System Settings>Protocols>Modbus.

Figure 5-5. Modbus Communications Page

36

One Modbus Address: When this option is selected, this address is used by the Gateway for

Modbus RTU communications.

Multiple Modbus Addresses: When this option is selected, a new column for address will appear on the Modbus mapping page.

Modbus TCP Port: This is the TCP/IP port the Gateway uses for Modbus TCP (Ethernet). To change TCP/IP port settings, see the Internal Firewall section for more details.

Host Integration

Reference Manual

00809-0200-4420, Rev HB

Section 5: Host Integration

January 2015

Host Integration

Baud Rate: The data rate or speed of serial communications. This setting is only required for

Modbus RTU.

Parity: This setting determines parity (none, even, or odd) to use for error checking purposes.

This setting is only required for Modbus RTU.

Stop Bits: This setting determines the number (1 or 2) of stop bits to use when ending a message. This setting is only required for Modbus RTU.

Response delay time (ms): This setting determines how long (ms) the Gateway waits before responding to a Modbus request. This setting is only required for Modbus RTU.

Unmapped register read response?: This is the value returned by the Gateway if the Modbus master requests a register with no data assigned to it (empty register). It is recommended this be set to zero fill to prevent errors.

Floating point representation: This setting determines if the Gateway uses floating point values or integer values. There are three options for this setting.

Float uses 32 bit floating point values.

Round rounds the data value to the nearest whole number.

Scaled uses scaled integers to offset negative values or increase decimal point resolution. The equation for scaled integers is: y = Ax - (B - 32768)

Where: y = Scaled integer returned by the Gateway

A = Gain for scaled integer value x = Measured value from wireless field device

B = Offset for scaled integer value

Use swapped floating point format?: This setting switches which register is sent first for a floating point value. This setting is only used for floating point values.

Incorporate value’s associated status as error?: This setting will cause the Gateway to report a predetermined value when a communications or critical diagnostic error is received from the wireless field device. The value is user configurable depending on which floating point representation is chosen. See Value reported for error below.

Value reported for error (floating point): This setting determines what value is reported if the wireless field device reports a failure or stops communicating to the Gateway. This setting is used for floating point values. The choices are NaN (not a number), +Inf (positive infinity), -Inf

(negative infinity), or Other (user specified).

Value reported for error (rounded and native integer): This setting determines what value is reported if the wireless field device reports a failure or stops communicating to the Gateway.

This setting is used for rounded or scaled integers. The choice is a user specified value between

-32768 and 65535.

Scaled floating point maximum integer value: This determines the maximum integer value for the purpose scaling integers. 999-65534

37

Section 5: Host Integration

January 2015

5.4.2

Reference Manual

00809-0200-4420, Rev HB

Use global scale gain and offset?: This setting determines if a global gain and offset is applied for scaled integers or if each value has a unique gain and offset. Unique gain and offsets are found on the Modbus Mapping page.

Global scale gain: This value is multiplied to the data values for the purpose of scaling integers.

If global scaling is not selected, a gain value will be available for each separate data value on the

Modbus Mapping page.

Global scale offset: This value is added to the data values for the purpose of scaling integers. If global scaling is not selected, an offset value will be available for each separate data value on the

Modbus Mapping page.

Register mapping

Register Mapping is the process of assigning data points from wireless field devices to Modbus registers. These registers can then be read by a Modbus master or client. Modbus register mapping can be found by navigating to System Settings>Protocols>Modbus.

Figure 5-6. Modbus Register Map Page

38

To add a new data point to the Modbus register map:

1.

Select Add New entry.

2.

Complete all of the table entries for the new data point (note that the entry columns may vary based on the Modbus communications settings).

Host Integration

Reference Manual

00809-0200-4420, Rev HB

Section 5: Host Integration

January 2015

3.

4.

Repeat for each new data point.

Select Submit.

5.

When changes have been accepted, select Return to form.

Address: This is the Modbus RTU address used by the Gateway for this data point. It is possible to group data points assigning them the same address (i.e. all data points from the same process unit can have the same address). This column only appears if Multiple Modbus Addresses is selected on the Modbus Communications page.

Register: This is the Modbus register number used for this data value. Modbus registers hold two bytes (16 bits) of information; therefore 32 bit floats and integers require two Modbus registers. Each data point needs a unique Modbus register number, unless they are assigned different addresses. Register numbers 0-19999 are reserved for Boolean (bit, coil, binary, etc…) values. Register numbers 20000+ are reserved for floating point or integer values.

Point Name: This is a two part name for the data point. The first part is the HART Tag of the wireless field device which is producing the data. The second part is the parameter of the wireless field device.

Note

Point Name is entered as <HART Tag.PARAMETER>. Point Name can be entered using the list of values (…) or manually entered. The following table gives a list of standard device parameters which may be considered for Modbus register mapping.

Table 5-1. Device Parameters Available

Parameter Description

PV

SV

TV

QV

RELIABILITY

ONLINE

PV_HEALTHY

SV_HEALTHY

Primary Variable

Secondary Variable

Tertiary Variable

Quaternary Variable

A measure of connectivity to the Gateway

Wireless communications status

Health status for PV

Health status for SV

TV_HEALTHY Health status for TV

QV_HEALTHY Health status for QV

Data type

32-bit float

32-bit float

32-bit float

32-bit float

32-bit float

Boolean

Boolean

Boolean

Boolean

Boolean

PV, SV, TV, and QV (dynamic variables) will vary by device type. Please refer to the device’s documentation for more information on what value is represented by each dynamic variable.

RELIABILITY and ONLINE relate to wireless communications. RELIABILITY is the percentage of messages received from the wireless field device. ONLINE is a true/false indication of whether the device is communicating on the wireless network.

Host Integration

**_HEALTHY parameters are a true/false indication of the health of a particular variable (** = dynamic variable – PV, SV, etc…). These parameters incorporate critical diagnostics from the wireless field device as well as communication status.

39

Section 5: Host Integration

January 2015

40

Reference Manual

00809-0200-4420, Rev HB

Note

The **_HEALTHY parameters are a great indication of the health and communications status of the data values.

State (state value): The value of a data point which drives a Modbus output of 1. For example, if a data point is reported as either True or False, a state value of True will report a 1 for True and 0 for False. A state of False will report a 0 for True and a 1 for False. State is only required for register numbers 0-19999 (Boolean, bit, coil, binary, etc…).

Invert: This check box will invert the Modbus output from a 1 to a 0 or a 0 to a 1. Invert is only used for Boolean values using register numbers 0-19999.

Gain: This value is multiplied to the data value for the purpose of scaling integers. Gain is only required if scaled is chosen on the Modbus communications page and globe gain and offset is not chosen.

Offset: This value is added to the data value for the purpose of scaling integers. Offset is only required if scaled is chosen on the Modbus communications page and globe gain and offset is not chosen.

Predefined Modbus registers

In addition to user configurable parameters, the Gateway also supports a list of predefined

Modbus registers with diagnostics and test parameters. The following table is a list of the predefined Modbus registers.

Table 5-2. Predefined Modbus Registers

Description

Current Year (1)

Current Month (1)

Current Day (1)

Current Hour (1)

Current Minute (1)

Current Second (1)

Messages Received

Corrupt Messages Received

Messages Sent With Exception

Messages Sent Count

Valid Messages Ignored

Constant Float 12345.0

SYSTEM_DIAG.HART_DEVICES

SYSTEM_DIAG.ADDITIONAL_STATUS_0

SYSTEM_DIAG.ADDITIONAL_STATUS_1

SYSTEM_DIAG.ADDITIONAL_STATUS_2

SYSTEM_DIAG.ADDITIONAL_STATUS_3

Register

49009

49010

49011

49012

49014

49015

49016

49017

49018

49001

49002

49003

49004

49005

49006

49007

49008

Data type

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32-bit int

32 float

32-bit int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

Host Integration

Reference Manual

00809-0200-4420, Rev HB

5.5

Section 5: Host Integration

January 2015

Table 5-2. Predefined Modbus Registers

Description Register

SYSTEM_DIAG.ADDITIONAL_STATUS_4

SYSTEM_DIAG.ADDITIONAL_STATUS_5

SYSTEM_DIAG.ADDITIONAL_STATUS_6

49019

49020

49021

SYSTEM_DIAG.ADDITIONAL_STATUS_7

SYSTEM_DIAG.ADDITIONAL_STATUS_8

49022

49023

SYSTEM_DIAG.ADDITIONAL_STATUS_9

49024

SYSTEM_DIAG.ADDITIONAL_STATUS_10

49025

SYSTEM_DIAG.ADDITIONAL_STATUS_11

49026

SYSTEM_DIAG.ADDITIONAL_STATUS_12

49027

SYSTEM_DIAG.UNREACHABLE

SYSTEM_DIAG.UPTIME

49028

49029

SYSTEM_DIAG.TEST_BOOLEAN

SYSTEM_DIAG.TEST_BYTE

SYSTEM_DIAG.TEST_UNSIGNED_BYTE

SYSTEM_DIAG.TEST_SHORT

49031

49032

49033

49034

SYSTEM_DIAG.TEST_UNSIGNED_SHORT

49035

SYSTEM_DIAG.TEST_INT

49036

SYSTEM_DIAG.TEST_UNSIGNED_INT

SYSTEM_DIAG.TEST_FLOAT

49038

49040

Data type

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

8-bit unsigned int

32-bit int

32-bit int

Boolean

8-bit int

8-bit unsigned int

16-bit int

16-bit unsigned int

32-bit int

32-bit unsigned int

32-bit float

Ethernet/IP

Communication settings

It is important that the Ethernet/IP communication settings in the Gateway match the setting in the Ethernet/IP master or client. Please refer to host system documentation for more information on how to configure these settings. Or to the reference manual for Ethernet/IP technical document 00809-0500-4420. The Ethernet/IP communication settings can be found by navigating to System Settings>Protocols>EtherNet/IP. Network architectures should reflect that of a DeltaV system see 00809-0200-4420, Rev HB.

Note

Ethernet/IP can be integrated with any approved Ethernet/IP ODVA member. Other protocols such as HARTIP are still functional within the Gateway. See the Product Data Sheet (document number 00813-0200-4420) for ordering options.

Host Integration 41

Section 5: Host Integration

January 2015

Figure 5-7. Ethernet/IP Communications Page

Reference Manual

00809-0200-4420, Rev HB

42

Table 5-3. System Settings>Protocols>EtherNet/IP

Terms Description

Assembly Object Type Ethernet/IP use Static assembly object.

Ethernet/IP TCP Port The TCP Port used to access Ethernet/IP TCP data directly from the Gateway.

Ethernet/IP UDP Ports The UDP Ports used to access Ethernet/IP UDP data directly from the

Gateway.

Incorporate value’s associated status as error?

If the HART variable status indicates a critical failure or if there is a loss of communications, it will be reported through the Ethernet/IP member.

Value reported for error (floating point)

NaN

+Inf

-Inf

Chooses what value is reported if the value’s associated status indicates a critical failure. Only used if the Gateway is using float representation

Not a number is reported if the value’s associated status indicates a critical failure.

Positive infinity is reported if the value’s associated status indicates a critical failure.

Negative infinity is reported if the value’s associated status indicates a critical failure.

Other

Value reported for error (native integer)

User defined value is reported if the value’s associated status indicates a critical failure.

User defined value is reported if the value’s associated status indicates a critical failure. Only used if the Gateway is using integer representation.

Host Integration

Reference Manual

00809-0200-4420, Rev HB

Section 5: Host Integration

January 2015

Unmapped parameter read response?: This is the value returned by the Gateway if the

Ethernet/IP master requests a register with no data assigned to it (empty register). It is recommended this be set to zero fill to prevent errors.

Parameter mapping

Register Mapping is the process of assigning data points from wireless field devices to

Ethernet/IP registers. These registers can then be read by a Ethernet/IP master or client.

Ethernet/IP register mapping can be found by navigating to System Settings>Protocols>

EtherNet/IP>EtherNet/IP Member Map.

Figure 5-8. Ethernet/IP Register Map Page

Host Integration

Table 5-4. Summary of Terms Used for the Ethernet/IP Mapping Page

Terms

Input Instance

Output Instance

Member

Point Name

New entry

<<First

<<Previous

Search

Description

Ethernet/IP Input Static Assembly Instance - 496 bytes

Ethernet/IP Output Static Assembly Instance - 496 bytes

Ethernet/IP Instance Member in which data will get produced or consumed

Assigned data point in the format HARTtag.parameter

Creates a new entry in this table

Navigates to the first page of this table

Navigates to the previous page of this table

Finds the next occurrence of the characters entered into this field

43

Section 5: Host Integration

January 2015

Reference Manual

00809-0200-4420, Rev HB

Table 5-4. Summary of Terms Used for the Ethernet/IP Mapping Page

1.

2.

Terms

Next>>

Last>>

Delete Selected

Select All

Select None

Select Errors

Submit

Description

Navigates to the next page of this table

Navigates to the last page of this table

Removes the selected entry from this table

Selects all table entries

De-selects all table entries

Selects all table entries that have an error message

Accepts all changes (highlighted in yellow)

To add a new data point to the Ethernet/IP register map:

Select New entry.

Complete all of the table entries for the new data point (note that the entry columns may vary based on the Ethernet/IP communications settings).

3.

4.

Repeat for each new data point.

Select Submit.

5.

When changes have been accepted, select Return to form.

See

Table 5-1 on page 39 for options of parameters that can be mapped.

44 Host Integration

Reference Manual

00809-0200-4420, Rev HB

Section 6 Troubleshooting

Section 6: Troubleshooting

January 2015

Troubleshooting

Note

For more information see the user interface terminology guide (document number

00809-0600-4420).

This section provides basic troubleshooting tips for the Smart Wireless Field Network. To receive technical support by phone:

Global Service Center

Software and Integration Support

United States 1 800 833 8314

International 63 2 702 1111

Customer Central

Technical Support, quoting, and order related questions

United States 1 800 999 9307 (7:00 a.m. to 7:00 p.m. CST)

Asia Pacific 65 6777 8211

Europe/Middle East/Africa 49 8153 9390

Or email the wireless specialists at: [email protected]

Table 6-1. Troubleshooting Initial Connection

Issue

Web browser returns page not found

Troubleshooting steps

1. Connect the Gateway and PC/laptop

2. Verify the Gateway is properly powered, 24 VDC (nominal) and 250 mA. Open the upper cover and verify if any indicator lights are on.

3. Verify which Ethernet port is being used on the Gateway.

4. Verify the IP address for the Gateway (default primary port is 192.168.1.10, default secondary port is 192.168.2.10 or for DeltaV Ready Gateway’s default primary port is 10.5.255.254, default secondary port is 10.9.255.254).

5. Verify the IP address of the PC/laptop is in the same subnet range as the Gateway

(i.e. If the Gateway IP is 155.177.0.xxx, then the PC/Lap IP address should be

155.177.0.yyy).

6. Disable internet browser proxy settings.

1. Verify the IP address of the PC/laptop is in the same subnet range as the Gateway

(i.e. If the Gateway IP is 155.177.0.xxx, then the PC/Lap IP address should be

155.177.0.yyy).

Can not find

Gateway after changing IP address

Can not find

Gateway using

Secondary

Ethernet

Port

Can not log into the

Gateway

1. Verify which Ethernet port is being used on the Gateway.

2. Verify the IP address for the Gateway (default primary port is 192.168.1.10, default secondary port is 192.168.2.10).

3. Verify the IP address of the PC/laptop is in the same subnet range as the Gateway

(i.e. If the Gateway IP is 155.177.0.xxx, then the PC/Lap IP address should be

155.177.0.yyy).

1. Verify the user name and password. The administrator user name is admin and the default password is default. See Table 2-1.

45

Section 6: Troubleshooting

January 2015

Reference Manual

00809-0200-4420, Rev HB

Table 6-2. Troubleshooting AMS

®

Wireless Configurator

Issue

Gateway does not appear in

AMS Wireless

Configurator

Wireless devices do not appear under the Gateway

Wireless device appears with red HART

® symbol

Device configuration items are grayed out

Troubleshooting steps

1. Verify the Security Setup Utility is installed on the same PC as AMS Wireless

Configurator.

2. Setup a wireless network interface using the Network Configuration application.

See Section 4: Software Setup.

3. Verify if the wireless network interface is configured for Secure Gateway

Communications.

4. Verify secure/unsecure AMS Wireless Configurator protocol settings in the

Gateway. Log on to the Gateway and navigate to SETUP > SECURITY >

PROTOCOLS.

5. Restart AMS Wireless Configurator data server. Right click on AMS Wireless

Configurator server icon in the Windows system tray (lower right corner) and select stop server.

1. Verify wireless devices are connected to the Gateway. Log on to the Gateway and navigate to EXPLORER.

2. Right click on wireless network and select rebuild hierarchy.

1. Install latest device support files from AMS Wireless Configurator. Go to www.emersonprocess.com > BRANDS > AMS SUITE > AMS DEVICE MANAGER >

DEVICE DESCRIPTION (DDs).

1. Verify whether current or historical information is being displayed. This setting is displayed at the bottom of each device configuration screen. Configuration requires the Current setting.

2. For security purposes a configuration timeout is applied to sessions that have been idle for more than 30 minutes. Log back into AMS Wireless Configurator.

Table 6-3. Troubleshooting Wireless Field Devices

Issue

Wireless device does not appear on the network

Wireless device appears in the join failure list

Wireless device appears with service denied

Troubleshooting steps

1. Verify the device has power.

2. Verify the device is within effect communications range.

3. Verify the proper Network ID has been entered into the device.

1. Re-enter the Network ID and Join Key into the device.

1. Verify the total number of devices on the network (100 max).

2. Go to SETUP > NETWORK > BANDWIDTH and click analyze bandwidth

(Note: any changes will require the network to reform)

3. Reduce the update rate for the device.

46 Troubleshooting

Reference Manual

00809-0200-4420, Rev HB

Section 6: Troubleshooting

January 2015

Table 6-4. Troubleshooting Modbus Communications

Issue

Can not communicate using Modbus RTU

Can not communicate using Modbus TCP

Can not communicate using secure

Modbus TCP

Troubleshooting steps

1. Verify the use of RS-485.

2. Verify wiring connections. See Section 3: Mounting and Connection .

3. Verify if termination is required.

4. Verify that Modbus serial communications setting in the Gateway match the

Modbus Host settings. Log on to the Gateway and navigate to SETUP >

MODBUS > COMMUNICATIONS.

5. Verify the Modbus address for the Gateway.

6. Verify Modbus register mapping in the Gateway. Log on to the Gateway and navigate to SETUP > MODBUS > MAPPING.

1. Verify secure / unsecure Modbus protocol settings in the Gateway. Log on to the Gateway and navigate to SETUP > SECURITY > PROTOCOLS.

2. Verify the Modbus TCP communications settings in the Gateway. Log on to the Gateway and navigate to SETUP > MODBUS > COMMUNICATIONS.

3. Verify Modbus register mapping in the Gateway. Log on to the Gateway and navigate to SETUP > MODBUS > MAPPING.

1. Verify the Security Setup Utility has been installed.

2. Configure a Secure Modbus Proxy for the Gateway. See Section 4: Software

Setup .

3. Verify secure / unsecure Modbus protocol settings in the Gateway. Log on to the Gateway and navigate to SETUP > SECURITY > PROTOCOLS.

4. Verify the Modbus TCP communications settings in the Gateway. Log on to the Gateway and navigate to SETUP > MODBUS > COMMUNICATIONS.

5. Verify Modbus register mapping in the Gateway. Log on to the Gateway and navigate to SETUP > MODBUS > MAPPING.

Table 6-5. Troubleshooting OPC Communications

Issue

OPC application can not find a

Gateway OPC server

Gateway OPC server does not show any Gateways

Gateway OPC server does not show any data tags

Troubleshooting steps

1. Verify the Security Setup Utility has been installed on the same PC as the OPC application.

2. Configure an OPC proxy for the Gateway. See Section 4: Software Setup.

1. Configure an OPC proxy for the Gateway. See Section 4: Software Setup.

1. Configure the Gateway OPC Browse Tree. Log on to the Gateway and navigate to SETUP > OPC > OPC BROWSE TREE.

2. Verify the connection status for the OPC proxy in the Security Setup Utility.

3. Verify if the OPC proxy is configured for secure or unsecure communications.

4. Verify secure / unsecure OPC protocol settings in the Gateway. Log on to the

Gateway and navigate to SETUP > SECURITY > PROTOCOLS.

5. Verify network firewall and port settings.

Troubleshooting 47

Section 6: Troubleshooting

January 2015

Reference Manual

00809-0200-4420, Rev HB

Table 6-6. Troubleshooting Ethernet/IP

Issue

The Gateway is not publishing the parameters

Troubleshooting steps

1. Verify connection is established with Ethernet/IP. Navigate to

SETUP > SECURITY > PROTOCOLS

2. Reference technical document 00809-0500-4420: Installation manual to connect to an Allen Bradley system.

48 Troubleshooting

Reference Manual

00809-0200-4420, Rev HB

Section 7: Glossary

January 2015

Section 7 Glossary

This glossary defines terms used throughout this manual or that appear in the web interface of the Smart Wireless Gateway.

Term

Access Control List

Active Advertising

Baud Rate

Burst Rate

Certificate

Connectivity

Device ID

DHCP

Domain

Gateway

Definition

A list of all devices that are approved to join the network. Each device will also have a unique join key. Also referred to as a white list.

An operational state of the network manager that causes the entire wireless field network to send messages looking for new or unreachable devices to join the network.

Communication speed for Modbus ® RTU.

The interval in which a wireless field device transmits measurement and status data to the Gateway. Same as Update Rate.

A digital signature used to authenticate a client/server while using encrypted communications.

Typically refers to a combination of communication statistics and link reliability of a wireless field device. May also refer to the connection between the Gateway and the Host System.

A hexidecimal number that provides unique device identification.

Dynamic Host Configuration Protocol: Used to automatically configure the

TCP/IP parameters of a device.

A unique designator on the internet comprised of symbols separated by dots such as: this.domain.com

Refers to the Smart Wireless Gateway.

HART Tag

Host Name

HTML

HTTP

HTTPS

Join Failure

Join Key

Latency

Netmask

The device’s electronic tag that the Gateway uses for all host integration mapping. Refers to the HART ® long tag (32 characters, used for HART 6 or

7 devices) or the HART message (32 characters, only used for HART 5 wired devices connected via a WirelessHART adapter)

A unique designator in a domain associated with the IP address of a device such as: device.this.domain.com. In that example the hostname is device.

Hyper Text Markup Language: The file format used to define pages viewed with a web browser.

Hyper Text Transfer Protocol: The protocol that defines how a web server sends and receives data to and from a web browser.

HTTP over an encrypted Secure Sockets Layer (SSL)

When a wireless field device fails to join the WirelessHART on access control list, etc.)

®

network. Most join failures are due to security reasons (missing or incorrect join key, not

Hexadecimal security code that allows wireless field devices to join the wireless field network. This code must be identical in the device and the

Gateway.

The time from when a message leaves a wireless field device until it reaches the Gateway.

A string of 1's and 0's that mask out or hide the network portion of an IP address leaving only the host component.

Glossary

49

Section 7: Glossary

January 2015

Reference Manual

00809-0200-4420, Rev HB

Term Definition

Network I.D.

Network Manager

NTP

Path

Path Stability

Primary Interface

Private Network/LAN

Reliability

RSSI

Secondary Interface

Security Setup Utility

Numeric code that associates wireless field devices to the Gateway. This code must be identical in the device and the gateway.

Operational function within the Smart Wireless Gateway that automatically handles all device connections and scheduling of wireless data.

Network Time Protocol. Used to keep the system time synchronized with a network time server.

A wireless connection between two devices in a wireless network. Also referred to as a hop.

A measure of connectivity between two devices in the wireless network.

Calculated as the ratio of the number of received messages over the number of expected messages.

Ethernet 1 or Fiber Optic port that is used for primary host communications.

A local connection between a Smart Wireless Gateway and a PC/laptop.

This network is used for commissioning and configuration of the Gateway.

A measure of connectivity between the Gateway and a wireless field device. Calculated as the ratio of the number of received messages over the number of expected messages. Takes into account all paths.

Received signal strength indication (dBm) for the wireless field device.

Ethernet 2 port that is used for backup connection or a maintenance port for local access.

A software application that enables secure communications between the

Gateway and host system, asset management software, data historians, or other applications.

Self-Organizing Network Mesh network technology in which a network manager automatically handles all device connections and scheduling of wireless data.

Service Denied The device has been denied bandwidth and can not publish its regular updates.

TCP/IP Transmission Control Protocol/Internet Protocol. The protocol that specifies how data is transmitted over Ethernet.

Update Rate

Wireless Field Device(s)

Wireless Field Network

The interval in which a wireless field device transmits measurement and status data to the Gateway. Same as Burst Rate.

WirelessHART field devices that are a part of the wireless field network.

Wireless Plant Network

WirelessHART network, consisting of Smart Wireless Gateway and multiple wireless field devices.

Industrial Wi-Fi network, used to integrate the Wireless Field Network into the control network.

50

Glossary

Reference Manual

00809-0200-4420, Rev HB

Appendix A: Product Specifications

January 2015

Appendix A Product Specifications

A.1

Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51

Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 52

Communication specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 52

Self-organizing network specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 53

System security specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 54

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57

Accessories and spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 58

Functional specifications

Input voltage

10.5-30 VDC

Current draw

Operating Current Draw is based on 3.6 Watts power consumption.

Momentary startup Current Draw up to twice operating Current Draw.

250

125

Operating

Region

30

12 24

Voltage (VDC)

Radio frequency power output from antenna

Maximum of 10 mW (10 dBm) EIRP

Maximum of 40 mW (16 dBm) EIRP for WN2 High Gain option

Environmental

Operating Temperature Range:

-40 to 158 °F (-40 to 70 °C)

Operating Humidity Range:

10-90% relative humidity

Product Specifications

51

Appendix A: Product Specifications

January 2015

A.2

A.3

EMC performance

Complies with EN61326-1:2006.

Antenna options

Integrated Omni-directional Antenna

Optional remote mount Omni-directional Antenna

Physical specifications

Weight

10 lb. (4,54 kg)

Material of construction

Housing

Low-copper aluminum, NEMA ® 4X

Paint

Polyurethane

Cover gasket

Silicone Rubber

Antenna

Integrated Antenna: PBT/PC

Remote Antenna: Fiber Glass

Certifications

Class I Division 2 (U.S.)

Equivalent Worldwide

Communication specifications

Isolated RS485

2-wire communication link for Modbus ® RTU multidrop connections

Baud rate: 57600, 38400, 19200, or 9600

Protocol: Modbus RTU

Reference Manual

00809-0200-4420, Rev HB

52

Product Specifications

Reference Manual

00809-0200-4420, Rev HB

Appendix A: Product Specifications

January 2015

Wiring: Single twisted shielded pair, 18 AWG. Wiring distance is approximately 4000 ft.

(1,524 m)

Ethernet

10/100base-TX Ethernet communication port

Protocols: Modbus TCP, OPC, EtherNet/IP ™ , HART ® -IP, https (for Web Interface)

Wiring: Cat5E shielded cable. Wiring distance 328 ft. (100 m).

Modbus

Supports Modbus RTU and Modbus TCP with 32-bit floating point values, integers, and scaled integers.

Modbus Registers are user-specified.

OPC

OPC server supports OPC DA v2, v3

EtherNet/IP

Supports EtherNet/IP protocol with 32-bit Floating Point values and Integers. EtherNet/IP

Assembly Input-Output instances are user configurable. EtherNet/IP specifications are managed and distributed by ODVA.

A.4

Self-organizing network specifications

Protocol

IEC 62591(WirelessHART ® ), 2.4 - 2.5 GHz DSSS.

Maximum network size

100 wireless devices @ 8 sec.

50 wireless devices @ 4 sec.

25 wireless devices @ 2 sec.

12 wireless devices @ 1 sec.

Supported device update rates

1, 2, 4, 8, 16, 32 seconds or 1 - 60 minutes

Network size/latency

100 Devices: less than 10 sec.

50 Devices: less than 5 sec.

Data reliability

>99%

Product Specifications

53

Appendix A: Product Specifications

January 2015

A.5

Reference Manual

00809-0200-4420, Rev HB

System security specifications

Ethernet

Secure Sockets Layer (SSL) enabled (default) TCP/IP communications

Smart Wireless Gateway access

Role-based Access Control (RBAC) including Administrator, Maintenance, Operator, and

Executive. Administrator has complete control of the Gateway and connections to host systems and the self-organizing network.

Self-organizing network

AES-128 Encrypted WirelessHART, including individual session keys. Drag and Drop device provisioning, including unique join keys and white listing.

Internal firewall

User Configurable TCP ports for communications protocols, including Enable/Disable and user specified port numbers. Inspects both incoming and outgoing packets.

Third party certification

Wurldtech: Achilles Level 1 certified for network resiliency

National Institute of Standards and Technology (NIST): Advanced Encryption Standard (AES)

Algorithm conforming to Federal Information Processing Standard Publication 197 (FIPS-197).

54

Product Specifications

Reference Manual

00809-0200-4420, Rev HB

A.6

Dimensional drawings

Figure A-1. Smart Wireless Gateway

3.51

(89)

2.93

(74,42)

9.02

(229 )

2.81

(71, 4)

2.525

(64, 14)

Appendix A: Product Specifications

January 2015

12.03

(306)

11.15

(283)

A

2.96

(75)

A. Lower Cover (remove for electrical connections)

6.72 ( 171)

4.78 (121)

3.08 (78)

B

1.59 (40)

A

3.99 (101)

A. Ground Lug

B. 1 / 2 inch NPT Conduit Connection (4 Places)

Dimensions are in inches (millimeters).

Product Specifications

55

Appendix A: Product Specifications

January 2015

A

F

D

A A

B

D

G

E

C

D

H

E

I

D

A

Reference Manual

00809-0200-4420, Rev HB

A. Antenna

B. 20 ft. (6,1 m) cable

C. 10 ft. (3,0 m) cable

D. Lightning Arrestor

E. Interchangeable cables

56

F. 50 ft. (15,2 m) cable

G. 30 ft. (9,1 m) cable

H. 40 ft. (12,2 m) cable

I. 25 ft. (7,6 m) cable

Remote omni-antenna kit

The Remote Omni-Antenna kit includes sealant tape for remote antenna connection, as well as mounting brackets for the antenna, Lightning Arrestor, and the Smart Wireless Gateway.

Lightning protection is included on all the options. WL3 and WL4 provide lightning protection along with the ability to have the gateway mounted indoors, the antenna mounted outdoors, and the lightning arrestor mounted at the building egress.

Note

The coaxial cables on the remote antenna options WL3 and WL4 are interchangeable for installation convenience.

Product Specifications

Reference Manual

00809-0200-4420, Rev HB

Appendix A: Product Specifications

January 2015

A.7

Ordering information

Table A-1. Smart Wireless Gateway Ordering Information

The Standard offering represents the most common options. The starred options () should be selected for best delivery.

__ The Expanded offering is subject to additional delivery lead time.

Model Product description

1420 Smart Wireless Gateway

Power input

A 24 VDC Nominal (10.5-30 VDC)

Ethernet communications - physical connection

1 (1)(2)

2 (3)(4)

Ethernet

Dual Ethernet

Wireless update rate, operating frequency, and protocol

A3 User Configurable Update Rate, 2.4 GHz DSSS, WirelessHART

Serial communication

N

A (5)

None

Modbus RTU via RS485

Ethernet communication - data protocols

2

4

5 (6)

6

(6)

Webserver, Modbus TCP/IP, AMS Ready, HART-IP

Webserver, Modbus TCP/IP, AMS Ready, HART-IP, OPC

DeltaV Ready

Ovation Ready

8

9

Webserver, EtherNet/IP, AMS Ready, HART-IP

Webserver, EtherNet/IP, Modbus TCP/IP, AMS Ready, HART-IP

Options

(include with selected model number)

Product certifications

N7

NF

KD

N3

N4

N5

N6

N1

ND

FM Division 2, Non-incendive

CSA Division 2, Non-incendive

ATEX Type n

ATEX Dust

IECEx Type n

IECEx Dust

FM & CSA Division 2, Non-incendive and ATEX Type n

China Type n

TIIS Type n

Redundancy options

RD (7)(8)(9) Gateway Redundancy

Product Specifications

57

Appendix A: Product Specifications

January 2015

Reference Manual

00809-0200-4420, Rev HB

Table A-1. Smart Wireless Gateway Ordering Information

The Standard offering represents the most common options. The starred options () should be selected for best delivery.

__ The Expanded offering is subject to additional delivery lead time.

Adapters

J1

J2

CM 20 Conduit Adapters

PG 13.5 Conduit Adapters

J3 3 /

4

NPT Conduit Adapters

Antenna options

(10)

WL2

WL3

WL4

WN2

(11)

Remote Antenna Kit, 50 ft. (15.2 m) cable, Lightning Arrestor

Remote Antenna Kit, 20 ft. (6.1 m) and 30 ft. (9.1 m) cables, Lightning Arrestor

Remote Antenna Kit, 10 ft. (3.0 m) and 40 ft. (12.2 m) cables, Lightning Arrestor

High-Gain, Remote Antenna Kit, 25 ft. (7.6m) cable, Lightning Arrestor

Typical model number: 1420 A 2 A3 A 2 N5

(1) Single active 10/100 baseT Ethernet port with RJ45 connector.

(2) Additional ports disabled.

(3) Dual active 10/100 baseT Ethernet ports with RJ45 connectors.

(4) Multiple active ports have separate IP addresses, firewall isolation, and no packet forwarding.

(5) Convertible to RS232 via adaptor, not included with Gateway.

(6) Includes Webserver, Modbus TCP, AMS Ready, HART-IP, and OPC.

(7) Requires the selection of Dual Ethernet option code 2.

(8) Not available with DeltaV Ready option code 5.

(9) Not available with EtherNet/IP option codes 8 and 9

(10) The WL2, WL3, WL4, and WN2 options require minor assembly.

(11) Not available in all countries.

A.8

Accessories and spare parts

Table A-2. Accessories

Item description

AMS Wireless SNAP-ON ™ , 1 Gateway License

AMS Wireless SNAP-ON, 5 Gateway Licenses

AMS Wireless SNAP-ON, 10 Gateway Licenses

AMS Wireless SNAP-ON, 5-10 Upgrade Licenses

Serial Port HART Modem and Cables only

USB Port HART Modem and Cables only

Table A-3. Spare Parts

Item description

Spare Kit, WL2 Replacement (1) ,

Remote Antenna, 50 ft. (15,2 m) Cable, and Lightning Arrestor

Spare Kit, WL3 Replacement

(1)

,

Remote Antenna, 20/30 ft. (6,1/9,1 m) Cables, and Lightning Arrestor

Spare Kit, WL4 Replacement

(1)

,

Remote Antenna, 10/40 ft. (3,0/12,2 m) Cables, and Lightning Arrestor

Spare Kit, WN2 Replacement

(1)

,

High Gain, Remote Antenna, 25 ft. (7.6 m) Cable, and Lightning Arrestor (2)

(1) Can not upgrade from integral to remote antenna.

(2) Not available in all countries.

Part number

01420-1644-0001

01420-1644-0002

01420-1644-0003

01420-1644-0004

03095-5105-0001

03095-5105-0002

Part number

01420-1615-0302

01420-1615-0303

01420-1615-0304

01420-1615-0402

58

Product Specifications

Reference Manual

00809-0200-4420, Rev HB

Appendix B: Product Certifications

January 2015

Appendix B Product Certifications

B.1

B.2

B.3

B.4

Approved manufacturing locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59

Telecommunication compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59

FCC and IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59

Ordinary Location Certification for FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59

European Union Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 60

Approved manufacturing locations

Rosemount Inc. – Chanhassen, Minnesota, USA

Emerson Process Management GmbH & Co. - Karlstein, Germany

Emerson Process Management Asia Pacific Private Limited - Singapore

Beijing Rosemount Far East Instrument Co., Limited - Beijing, China

Telecommunication compliance

All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification.

Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.

FCC and IC

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.

Ordinary Location Certification for FM

As standard, the Gateway has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health

Administration (OSHA).

Product Certifications

59

Appendix B: Product Certifications

January 2015

B.5

Reference Manual

00809-0200-4420, Rev HB

North America

N5 FM Division 2, Non-Incendive

Certificate: 3028321

Nonincendive for Class I, Division 2, Groups A, B, C, and D.

Suitable for Class II, III, Division 2, Groups E, F, and G.

Enclosure Type 4X

Temperature Code: T4 (-40 °C ≤ T a

≤ 60 °C)

Canadian Standards Association (CSA)

N6 CSA Division 2

Certificate: 1849337

Suitable for Class I, Division 2, Groups A, B, C, and D.

Install per Rosemount drawing 01420-1011.

Temperature Code: T4 (-40 °C ≤ T a

≤ 60 °C)

CSA Enclosure Type 4X

European Union Directive Information

The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting your local sales representative.

ATEX Directive (94/9/EC)

Emerson Process Management complies with the ATEX Directive.

Electro Magnetic Compatibility (EMC) (2004/108/EC)

Emerson Process Management complies with the EMC Directive.

Radio and Telecommunications Terminal Equipment Directive (R&TTE)(1999/5/EC)

Emerson Process Management complies with the R&TTE Directive

60

Europe

N1 ATEX Type n

Certificate: Baseefa 07ATEX0056X

ATEX Marking: II 3 G

Ex nA nL IIC T4 (-40 °C ≤ T a

≤ 60 °C)

Special Conditions for Safe Use (X):

1.

2.

The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

The Apparatus is not capable of withstanding the 500V insulation test required by

Clause 9.4 of EN 60079-15: 2005. This must be taken into account when installing the apparatus.

Product Certifications

Reference Manual

00809-0200-4420, Rev HB

Appendix B: Product Certifications

January 2015

Certificate: Baseefa 07ATEX0057X

ATEX Marking: II 3 D

Ex tD A 22 IP66 T135 (-40 °C ≤ T a

≤ 60 °C)

Maximum working voltage = 28 V

Special Condition for Safe Use (X):

1.

The surface resistivity of the antenna is greater than 1G Ω. To avoid electrostatic charge build-up, it must not be rubbed with a dry cloth or cleaned with solvents.

N7 IECEx Type n

Certificate: IECEx BAS 07.0012X

Ex nA nL IIC T4 (-40 °C ≤ T a

≤ 60 °C)

Maximum working voltage = 28 V

Special Conditions for Safe Use (X):

1.

The apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.8.1 of IEC 60079-15: 2005. This must be taken into account during installation.

2.

The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

NF IECEx Dust

Certification : IECEx BAS 07.0013

Ex tD A22 IP66 T135 (-40 °C ≤ T a

≤ 60 °C)

Maximum working voltage = 28 V

Combinations

KD Combination of N5, N6, and N1.

Product Certifications

61

Appendix B: Product Certifications

January 2015

Reference Manual

00809-0200-4420, Rev HB

62

Product Certifications

Reference Manual

00809-0200-4420, Rev HB

Appendix C DeltaV ™ Ready

C.1

C.2

C.3

Appendix C: DeltaV Ready

January 2015

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63

Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63

Mounting and connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 64

Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 64

Overview

Native integration with DeltaV enables the Smart Wireless Gateway to be autosensed and easily commissioned for seamless integration with all DeltaV applications: Explorer, Diagnostics, and

Control Studio. WirelessHART ® devices can be easily added to the wireless field network and then reconciled through DeltaV Explorer and assigned to analog channels through drag and drop assignment.

Latency considerations in control logic design and operation

Since the DeltaV wireless I/O scanner software requests updates for 1/5 of the devices each second, DeltaV receives updates on a particular field device once every 5 seconds. That is not necessarily synchronized with the update rate of the field device. Also, there is some latency between when the field device takes a process sample and when it is permitted to pass its value onto the wireless network. Status update responses can also increase latency in some instances.

So for example, if a device updates once every 8 seconds, and wireless network latency is 2 seconds, the amount of time that could pass between when an event occurred in the field and before it is available to the DeltaV I/O bus is between zero and 15 (8+2+5) seconds. The update period of the DeltaV control module should be added to that total to determine the range of latencies before an event in the field can be acted upon by the control system.

Operators should be made aware that the update rate of wireless measurements on operator screens are somewhat slower than those from wired devices. For example, if the operator initiates a valve movement, it can be 5-15 seconds before confirming feedback appears on the operator screen. Any control logic designed along the same principles should also take the update rates and latencies into account as well.

Requirements

DeltaV

Version 10.3 or newer.

Smart Wireless Gateway

DeltaV Ready option (Data Protocol option 5). See

“Ordering information” on page 57

.

63

Appendix C: DeltaV Ready

January 2015

C.4

Reference Manual

00809-0200-4420, Rev HB

Mounting and connecting

Mount the DeltaV Ready Gateway in the same manner as a standard Gateway. ( “Mounting” on page 16 ). The Gateway should be mounted in a location that allows convenient access to the

DeltaV control network as well as the wireless field network.

Connect the Gateway’s primary Ethernet port (Ethernet 1) into the DeltaV primary control network. If the dual Ethernet option (Physical Connection code 2) was ordered with the

Gateway, connect the secondary Ethernet port (Ethernet 2) into the DeltaV secondary control network.

Figure C-1. Delta V Control Network Architecture

A

D

B

C

C.5

A. Pro+ Engineering Station

B. Primary Control Network

C. Secondary Control Network

E

D. Controller and I/O

E. Smart Wireless Gateway

Setup

2.

3.

Out of the box the Smart Wireless Gateway is pre-configured for use on the DeltaV control network. In the DeltaV Explore application, the Gateway will automatically appear in the

Decommissioned Nodes folder.

To setup a wireless network will require 3 steps:

1.

Commission the Gateway.

Assign wireless device tags.

Assign Gateway to controller and download.

64

Reference Manual

00809-0200-4420, Rev HB

Appendix C: DeltaV Ready

January 2015

Figure C-2. Decommissioned Nodes Folder within DeltaV Explorer

New Wireless Gateway

Commission the Gateway using the following procedure:

1.

Select START>PROGRAMS>DELTAV>ENGINEERING> DELTAV EXPLORE to launch the

DeltaV Explorer application.

2.

Expand the folder SYSTEM CONFIGURATION >PHYSICAL

NETWORK>DECOMMISSIONED NODES.

3.

4.

Right click on the Smart Wireless Gateway and select Commission.

Enter a name for the Gateway and select OK.

5.

Select YES when prompted to Auto-Sense Wireless Gateway.

At this time the Reconcile I/O window will appear. The purpose of this screen is to assign

WirelessHART devices to DeltaV I/O channel. This allows the wireless device to be referenced in other DeltaV applications like Control Studio.

Figure C-3. Assign WirelessHART Devices to DeltaV I/O Channel

65

Appendix C: DeltaV Ready

January 2015

Reference Manual

00809-0200-4420, Rev HB

3.

4.

1.

2.

5.

6.

2.

3.

Assign wireless device tags using the following procedure:

1.

Drag and drop WirelessHART device from the Unassigned Wireless HART Devices: list to the Channels: list.

Repeat this process for each wireless device until all have been assigned.

Select OK to continue.

Next the Gateway will need to be assigned to a DeltaV Controller and download all. Assign and download the Gateway using the following procedure:

Right click on the Gateway and select Assign…

Use the browse window and select the desired controller.

Select OK to close the assignment window.

Right click on the Gateway and select Download.

Follow the download dialog.

Select OK to close the download window.

Figure C-4. Gateway Context Menu (Right Click)

Now the Gateway and wireless devices are fully commissioned and available to use in other

DeltaV applications. When new devices are added to the wireless network, they will need to be assigned to DeltaV channels through the reconcile process (right click on Gateway and select configure IO).

Note

Logging in to the Gateway is not possible using the default TCP/IP network setting. If the

Gateway is decommissioned, use an IP address 10.5.255.254. If the Gateway is commissioned, right click on the Gateway in DeltaV Explore and select Wireless Gateway Web Interface.

66

Reference Manual

00809-0200-4420, Rev HB

Appendix D Redundancy

D.1

D.2

D.3

Appendix D: Redundancy

January 2015

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 67

Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 67

Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 67

Mounting and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 70

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 74

Gateway replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 75

Overview

Redundancy for the Smart Wireless Gateway increases the availability of the wireless field network by providing two sets of physical hardware which operate as a single Gateway system.

This section covers setup and installation of a redundant Gateway system. It also covers diagnostics and integration to help monitor the health of the redundant Gateway system.

Where to mount the respective antennas

Illustration of maximum redundancy including dual switch and UPS

Understanding how the fail over works and experience to expect

How to leverage the multimaster capability for Modbus

®

integrations

Requirements

Smart Wireless Gateway

Firmware Version 4.3.19 or greater is recommended

RD option for Gateway Redundancy

Static IP Address

Must have matching output protocols (e.g. Modbus or OPC) on each Gateway.

Host system

Ethernet connection for Modbus TCP or OPC DA communications

Serial (RS-485) connection for Modbus RTU communications

Setup

When configuring redundant Smart Wireless Gateways, it is only necessary to configure one system. The other Gateway will be configured automatically when it is paired with the first

Gateway.

67

Appendix D: Redundancy

January 2015

Reference Manual

00809-0200-4420, Rev HB

4.

5.

2.

3.

Choose one Gateway as the starter Gateway. For the purposes of this document, it will be referred to as Gateway A. The other Gateway will be referred to as Gateway B.

To configure redundancy system settings:

1.

Connect a PC/laptop to the Ethernet 1 port on Gateway A.

Log in using the admin user account.

Navigate to System Settings>Gateway>Redundancy.

Gateway A’s factory serial number will be assigned to Gateway A.

Gateway B’s factory serial number will be assigned to Gateway B.

The Gateway names will be used in diagnostic messages and host system integration to help identify each Gateway. It is recommended that these names be marked on each physical

Gateway, in addition to the configuration settings.

Selecting left or right for Gateway A is for visualization purposes only. It has no effect on performance or functionality.

Figure D-1. System Settings>Gateway>Redundancy

68

Reference Manual

00809-0200-4420, Rev HB

Figure D-2. Redundancy Status

Appendix D: Redundancy

January 2015

5.

6.

7.

2.

3.

4.

After the redundancy system settings have been configured, the two Gateways must be connected and undergo a pairing process.

To pair both Gateways and form a redundant system:

1.

Connect a PC/laptop to the primary Ethernet port on Gateway A.

Log in using the admin user account.

Navigate to Diagnostics>Advanced>Redundancy Status.

Connect the secondary Ethernet port on Gateway A to the secondary Ethernet port on

Gateway B (see Figure D-3 on page 70 , Redundancy Setup Connections

).

A dialog will appear on the page; select Form redundant pair.

Wait for the Pairing to redundant peer status to turn green.

Select Return to page.

69

Appendix D: Redundancy

January 2015

Figure D-3. Redundancy Setup Connections

A B

Reference Manual

00809-0200-4420, Rev HB

D.4

C

F

E

E. Primary Ethernet

F. Secondary Ethernet

A. Gateway A

B. Gateway B

C. PC / Laptop

Once the Gateways have finished the pairing process, Gateway A will appear as the current active Gateway on the left hand side and Gateway B will be the standby Gateway on the right

(note that left/right hand appearance can be changed on the Redundancy System Settings page). If significant configuration changes need to be downloaded to the standby Gateway, it may temporarily go offline shortly after the pair process is complete. This is expected behavior and does not represent instability in the system.

Mounting and connections

Redundant Gateways follow similar mounting and connection practices as a standalone

Gateway. Please refer to Section 3: Mounting and Connection for more information. In addition to the standard practices, the following considerations should be taken when installing redundant Gateways.

Mounting

The redundant Gateways should be mounted in a location that allows convenient access to the process control network as well and provides good coverage for the wireless field network.

The redundant Gateway antennas should be mounted at the same height and be spaced between 3 ft to 9 ft (1m to 3m) horizontally. This is to ensure that they provide identical coverage for the wireless field network and to help eliminate coverage gap in the event of a switch over.

Ethernet

An Ethernet connection to the host system will support Modbus TCP, OPC, AMS ® Wireless

Configurator, and HART IP protocols. When using this architecture, connect the secondary

70

Reference Manual

00809-0200-4420, Rev HB

Appendix D: Redundancy

January 2015

Ethernet port on Gateway A directly to the secondary Ethernet port on Gateway B. Then connect the primary Ethernet ports for both Gateways to a process control network using sepa-

rate/redundant network switches. See Figure D-4

Ethernet Connection Architecture.

Figure D-4. Ethernet Connection Architecture

A

B

C

F

A. Engineering Station

B. Process Control Network

C. Gateway A

D. Primary Ethernet

D

E

G

E. Secondary Ethernet

F. Gateway B

G. Primary Ethernet

Note

The primary Ethernet port for each Gateway should be connected to separate network switches on the same process control network. Consult a control system administrator for more details about available redundant network switches.

Simplex RS-485

A simplex RS-485 host connection supports Modbus RTU protocol. When using this architecture, connect the secondary Ethernet port on Gateway A directly to the secondary

Ethernet port on Gateway B. Then wire the RS-485 ports for both Gateways in parallel to a single

serial card at the host system. See Figure D-5

Simplex RS-485 Architecture.

71

Appendix D: Redundancy

January 2015

Figure D-5. Simplex RS-485 Architecture

A

B

C

E

D

Reference Manual

00809-0200-4420, Rev HB

A. Engineering Station

B. Process Control Network

C. Controller and I/O

F

D. Serial Card

E. RS-485 Bus

F. Secondary Ethernet

Note

In either a simplex or dual RS-485 architecture, the primary Ethernet ports can be connected to an asset management network to provide connectivity to AMS Device Manager or AMS Wireless

Configurator.

Dual RS-485

A Dual RS-485 host connection support Modbus RTU protocol. When using this architecture, connect the secondary Ethernet port on Gateway A directly to the secondary Ethernet port on

Gateway B. Then wire the RS-485 ports for both Gateways separately to dual serial cards at the host system. See

Figure D-6 Dual RS-485 Architecture.

72

Reference Manual

00809-0200-4420, Rev HB

Figure D-6. Dual RS-485 Architecture

A

Appendix D: Redundancy

January 2015

B

C D

E

E

A. Engineering Station

B. Process Control Network

C. Controller and I/O

F

D. Dual Serial Card

E. RS-485 Bus

F. Secondary Ethernet

Note

By default, only the active Gateway in a redundant system will respond to Modbus polling requests. If simultaneous polling is desired, login to the Gateway web interface, navigate to

Setup>Modbus>Communications and set “Respond when running as redundant standby?” to

Yes. Only use this setting in a dual RS-485 architecture.

Power

Power for the redundant Gateways should be applied after all primary and secondary Ethernet and RS-485 connections have been made. Using separate uninterruptable power supplies (UPS) is recommended to ensure availability of the redundant Gateway system.

73

Appendix D: Redundancy

January 2015

D.5

Reference Manual

00809-0200-4420, Rev HB

Diagnostics

The redundant system will perform many diagnostic checks to verify the health and connectivity of the system.

Figure D-7. Redundancy Status (Diagnostics>Advanced>Redundancy Status)

74

These diagnostics can also be mapped to Modbus registers or OPC tags. The following table covers what diagnostics are included on the Redundancy Status page as well as how they can be mapped as parameters in Modbus or OPC.

Table D-1. Redundancy Diagnostics

Data type Parameter Description

REDUNDANT_HEALTHY

RF_COVERAGE_FAILURE

REDUNDANT_A_ONLINE

Overall redundancy status indicating the system is ready for a switch-over

Check to verify that both Gateways have the same

RF coverage of the wireless field network

Operational status of Gateway A

REDUNDANT_A_MASTER Indication if Gateway A is the active system

REDUNDANT_A_PING

Indication if Gateway A is able to ping designated host IP address

REDUNDANT_A_ETH0

REDUNDANT_B_ONLINE

Electrical connection status of the primary Ethernet port for Gateway A

Operational status of Gateway B

REDUNDANT_B_MASTER Indication if Gateway B is the active system

REDUNDANT_B_PING

Indication if Gateway B is able to ping designated host IP address

REDUNDANT_B_ETH0

Electrical connection status of the primary Ethernet port for Gateway A

Boolean

Boolean

Boolean

Boolean

Boolean

8-bit unsigned int

Boolean

Boolean

Boolean

8-bit unsigned int

Reference Manual

00809-0200-4420, Rev HB

Appendix D: Redundancy

January 2015

2.

3.

In addition to the redundancy diagnostics, an additional check may be configured to test network connectivity to a host system or other application. The redundant system will use this check to determine the best connectivity option and which Gateway should be set to the active

Gateway.

To configure network connectivity check:

1.

Navigate to System Settings>Gateway>Ethernet Communication.

Enter the host system IP address in the Check Network Connectivity IP Address field.

Select Save Changes.

Figure D-8. Network Connectivity Check

(System Settings>Gateway>Ethernet Communication)

D.6

Gateway replacement

When replacing or reintroducing a Gateway in a redundant system, always connect both the primary and secondary Ethernet connections before powering the standby Gateway. If the

Gateway is being reintroduced (i.e. it was a part of the original redundant system), it will automatically rejoin the redundant system. If the Gateway is new or has been set to default configuration, it will need to be paired to the current active Gateway. Navigate to System Set-

tings>Gateway>Redundancy and follow the recommended actions on that page or follow the procedure above to pair Gateways and form a redundant system.

75

Appendix D: Redundancy

January 2015

Reference Manual

00809-0200-4420, Rev HB

76

Reference Manual

00809-0200-4420, Rev HB

January 2015

Rosemount World Headquarters

Emerson Process Management

6021 Innovation Blvd

Shakopee, MN 55379, USA

+1 800 999 9307 or +1 952 906 8888

+1 952 949 7001

[email protected]

North America Regional Office

Emerson Process Management

8200 Market Blvd.

Chanhassen, MN 55317, USA

+1 800 999 9307 or +1 952 906 8888

+1 952 949 7001

[email protected]

Latin America Regional Office

Emerson Process Management

1300 Concord Terrace, Suite 400

Sunrise, Florida, 33323, USA

+1 954 846 5030

+1 954 846 5121

[email protected]

Europe Regional Office

Emerson Process Management Europe GmbH

Neuhofstrasse 19a P.O. Box 1046

CH 6340 Baar

Switzerland

+41 (0) 41 768 6111

+41 (0) 41 768 6300

[email protected]

Asia Pacific Regional Office

Emerson Process Management Asia Pacific Pte Ltd

1 Pandan Crescent

Singapore 128461

+65 6777 8211

+65 6777 0947

[email protected]

Middle East and Africa Regional Office

Emerson Process Management

Emerson FZE P.O. Box 17033,

Jebel Ali Free Zone - South 2

Dubai, United Arab Emirates

+971 4 8118100

+971 4 8865465

[email protected]

Standard Terms and Conditions of Sale can be found at: www.rosemount.com/terms_of_sale.

DeltaV, SNAP-ON, and the Emerson logo are trademarks and/or service marks of

Emerson Electric Co.

AMS is a registered trademark of Emerson Process Management.

Rosemount and the Rosemount logotype are registered trademarks of Rosemount

Inc.

WirelessHART and HART are registered trademarks of the HART Communication

Foundation.

Mozilla Firefox is a registered trademark of The Mozilla Foundation.

Internet Explorer and Microsoft are registered trademarks of Microsoft Corporation in the United States and other countries.

Windows is a trademark of Microsoft Corporation in the United States and other countries.

NEMA is a trademark and service mark of the National Electrical Manufacturers Association.

Intel is a registered trademark of Intel Corporation in the U.S. and/or other countries.

EtherNet/IP is a trademark of ControlNet International under license by ODVA.

All other marks are the property of their respective owners.

© 2015 Rosemount, Inc. All rights reserved.