Site Preparation and Installation
2.5.3 Piping Connections
Details for refrigerant (R-22) loop piping are in 2.4.3 - Piping Connections and Coolant Require-
Figure 12 Piping connections - indoor air-cooled centrifugal fan condensing unit
Condenser Coil
Scroll
Compressor
High Pressure
Switch
Liquid Injection
Valve Bulb
Hot Gas Bypass
Solenoid Valve
Suction Line Male Quick
Connect Coupling
Suction Line Female Quick
Connect Coupling *
3/8" (9.5mm) FLR
Pressure Relief Valve
3 - Way Head
Pressure
Control Valve
Hot Gas Bypass
Control Valve
Check
Valve
Sight Glass
Sensing Bulb
External Equalizer
Liquid Injection
Valve
Service Access
Ports
Liquid Line
Solenoid Valve
*
Liquid Line Male Quick
Connect Coupling
Liquid Line Female Quick
Connect Coupling
Filter
Drier
Expansion Valve
Receiver Heater
Pressure Limiting
Switch
Lee - Temp
Receiver
Pressure Balancing
Valve
(Two circuits required, single circuit shown for clarity)
Evaporator Coil DPN000236_Rev0
2.5.4 Electrical Connections - Condensing Unit
Refer to 2.4.4 - Electrical Connections, Evaporator or Chilled-Water Unit and Figure 14 for
general wiring requirements and cautions. Refer to electrical schematic when making connections.
Refer to unit serial tag for full load amp and wire size amp ratings.
Power Connections
The condensing unit requires its own power source and earth ground, with a disconnect switch to isolate the unit for maintenance.
NOTE
Refer to serial tag for full load amp and wire size amp ratings
Control Connections
Field-supplied control wires must be connected between the evaporator and the condensing unit (See
Figure 14 and the electrical schematic on the units for more details.) Seven (7) wires are required
between the evaporator and condensing unit. Eighth and ninth wires are required on systems with hot gas bypass.
20
Site Preparation and Installation
Figure 13 Indoor air-cooled centrifugal condensing unit dimensions and pipe connections
Customer supplied threaded rods for module support from ceiling (1/2" minimum diameter recommended) (typ. 4).
13/16"
(21mm)
23 7/8 "
(606mm)
66 9/32 "
(1683.5mm)
CABINET
DIMENSION
59 13/16 "
(1519mm)
1 13/16 "
(40mm)
40 5/32 "
(1020mm)
CABINET
DIMENSION
19 1/32 "
(483mm)
8 13/16 "
(224mm)
1 3/32 "
(26mm)
16 5/16 "
(414mm)
26 3/8 "
(670mm)
42 17/32 "
(1080.3mm)
THREADED ROD
CENTERS
NOTE: Unit is spaced evenly in
reference to threaded
rod centers.
9/16" (14mm) dia. holes for threaded rods (typ. 2 each end)
64 1/4 "
(1632mm)
THREADED ROD
CENTERS
Hanger
Bracket
Shaded area indicates a recommended clearance of
30" (762mm) for component access and removal.
Air Inlet
Air Outlet
7/8" (22mm) & 1 1/8" (29mm) dia. knockouts electrical entrance for high voltage connection
Single Point Power Kit connection from Evaporator.
System 1 (3Ton) Suction Line Connection,
Aeroquip #11 Male.
System 2 (5Ton) Suction Line Connection,
Aeroquip #12 Male.
System 1 (3Ton) Liquid Line Connection,
Aeroquip #6 Male.
System 2 (5Ton) Liquid Line Connection,
Aeroquip #10 Male.
7/8" (22.2mm) dia. knockout electrical entrance for alternate control panel low voltage routing.
21
7/8" (22.2mm) dia. electrical entrance for low voltage connection.
DPN000248_Rev1
Site Preparation and Installation
Figure 14 Indoor air-cooled centrifugal condenser electrical connections
Field Supplied Unit Disconnect
Switch when Factory Unit
Disconnect Switch is not
Supplied.
Electric Service not by Liebert.
Line VoltageElectric Power Supply
Conduit.
Removable
Access Panels
Connection Terminal for
Field Supplied Earth
Grounding Wire.
Optional Factory Installed
Disconnect Switch.
Openings for Field Supplied
24V NEC Class 2 Wiring
Between Condensing Unit and
Fan/Coil Unit.
Low VoltageElectric Power
Supply Conduit Entrance.
6 "
(152.4mm)
4 "
(101.6mm) supplied 24V NEC class 2 wiring. See note 2.
Wire connections from evaporator module:
1. 24V GND System 1
2. 24V Supply System 1
3. High Pressure Alarm System 1
4. Hot Gas Bypass Connection System 1
(only on units with hot gas bypass.
If no hot gas bypass, connection is
provided in the evaporator module.
Connect wire 4 and wire 2 to the
24V supply).
5. 24V GND System 2
6. 24V Supply System 2
7. High Pressure Alarm System 2
8. Hot Gas Bypass Connection System 2
(only on units with hot gas bypass.
If no hot gas bypass, connection is
provided in the evaporator module.
Connect wire 8 and wire 6 to the
24V supply).
9. 24V GND Condenser Fan
10. 24V SUPPLY Condenser Fan
16 1/2 "
(419.1mm)
8 1/2 "
(215.9mm)
12 1/2 "
(317.5mm)
NOTES:
1. Refer to specification sheet for full load amp. and wire size amp. ratings.
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m) or not
to exceed 1 volt drop in control line.
DPN000249_Rev0
22
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 9 DX Evaporator Section
- 9 Chilled-Water Model
- 9 Air-Cooled Condensing Unit (Indoor Centrifugal)
- 9 Air-Cooled Condensing Unit (Outdoor Prop Fan)
- 9 Water/Glycol Condensing Unit (Indoor)
- 14 Figure 1 System configurations-air cooled systems
- 14 Figure 2 System Configurations-water/glycol systems
- 15 Figure 3 System Configurations-chilled water systems
- 17 Figure 5 Close coupled installation
- 18 Filter Box
- 18 Connections for Ducted Systems
- 18 Table 5 Evaporator external static pressure (60) at 3750 CFM (6371 CMH)
- 19 Drain Line
- 19 Figure 6 Drain installation
- 20 Condensate Pump
- 20 Figure 7 Condensate pump installation
- 20 Humidifier Water Supply Line
- 21 Chilled-Water Piping-Chilled-water Systems Only
- 21 Figure 8 General arrangement diagram - chilled-water systems
- 22 Refrigerant (R-22) Piping
- 22 Table 6 Recommended refrigerant line sizes
- 22 Figure 9 Refrigerant piping diagram
- 23 Total refrigerant = Units and Lines
- 23 Table 7 8-ton unit refrigerant charge
- 23 Table 8 Line charges (field piping)*
- 23 Quick Connect Fittings
- 23 Table 9 Refrigerant quick connect sizes and torque
- 24 Figure 10 Evaporator or chilled-water unit dimensional data
- 25 Power Connections
- 25 Control Connections (10-wire on air-cooled, 8-wire on water/glycol cooled)
- 26 Figure 11 Evaporator unit electrical connections
- 27 General Considerations
- 27 Considerations for Specific Applications
- 28 Figure 12 Piping connections - indoor air-cooled centrifugal fan condensing unit
- 28 Power Connections
- 28 Control Connections
- 29 Figure 13 Indoor air-cooled centrifugal condensing unit dimensions and pipe connections
- 30 Figure 14 Indoor air-cooled centrifugal condenser electrical connections
- 31 Power Connections
- 31 Control Connections
- 32 Figure 15 Electrical field connections - outdoor condensing unit
- 33 Figure 16 Footprint dimensions - outdoor condensing unit
- 34 Figure 17 Piping and electrical connections - outdoor condensing unit
- 35 Water/Glycol Piping Considerations
- 35 Condensing Unit Fluid Requirements
- 35 Regulating Valve
- 35 Control Connections
- 36 Figure 18 Indoor water/glycol condensing unit dimensional data
- 37 Figure 19 Indoor water/glycol condensing unit electrical field connections
- 38 Figure 20 System piping with indoor water/glycol-cooled condensing unit
- 39 Figure 21 Optional free cooling coil (3-way valve) on water/glycol units
- 40 Figure 22 Optional free cooling coil (3-way valve) on air-cooled units
- 47 Table 12 Setup functions, default values and allowable ranges
- 49 Table 14 Equipment switch settings (unit control board)
- 49 Table 15 Switch settings (wallbox board)
- 51 Figure 24 Control menu
- 52 Figure 25 Control board (inside evaporator)
- 52 Figure 26 Wall box board
- 54 System Activation
- 55 Air-Cooled Systems
- 55 Water/Glycol Systems
- 59 Air Distribution
- 59 Blower Removal (Evaporator)
- 60 Suction Pressure
- 60 Discharge Pressure
- 60 Table 16 Typical discharge pressures
- 60 Thermostatic Expansion Valve
- 60 Air-Cooled Condensing Units
- 60 Coaxial Condensers (Water/Glycol-Cooled Condensing Units)
- 61 Regulating Valves (Water/Glycol Condensing Units)
- 61 Glycol Solution Maintenance
- 61 Hot Gas Bypass (Optional)
- 62 Replacement Procedures
- 64 Replacing the Humidifier Canister
- 64 Table 17 Humidifier control board DIP switch settings