475 Field Communicator User`s Manual


Add to my manuals
114 Pages

advertisement

475 Field Communicator User`s Manual | Manualzz

3-6 HART Functionality

Transferring Configurations to a PC Application

You can transfer configurations (.hcf files) from the 475 Field Communicator to AMS

Device Manager or the Field Communicator Easy Upgrade Utility. After you transfer the configuration, you can perform different operations depending on the application used.

AMS Device Manager

Use AMS Device Manager to open, edit, compare, and transfer saved configurations.

A Handheld or Field Communicator Interface kit for AMS Device Manager (version 6.2 or higher) lets you use the 475 Field Communicator with AMS Device Manager.

If the System Card does not appear as a storage location in AMS Device Manager, copy the configurations from the System Card into the Internal Flash in the 475 Field

Communicator before connecting to AMS Device Manager. See “Copying a Saved

Configuration” on page 3-5 for instructions. Then access the Internal Flash location to

open, edit, and save the configurations in AMS Device Manager. See the AMS Device

Manager Books Online for more information on connecting and transferring configurations.

Field Communicator Easy Upgrade Utility

Use the Easy Upgrade Utility to back up, transfer, and print the configurations saved in your 475 Field Communicator. See the Easy Upgrade Utility Help for more information about connecting and transferring configurations.

WORKING ONLINE WITH

HART DEVICES

Connecting to a HART

Device

The 475 Field Communicator can communicate with a device from the control room, on the bench, or any wiring termination point in the loop. Connect the 475 Field

Communicator with the appropriate connectors in parallel with the device or load resistor. The HART connectors are not polarity sensitive.

A minimum of 250 ohms resistance must be present in the HART loop for the 475 Field

Communicator to function properly. For information about Intrinsically Safe

connections, see Appendix B.

HART Communication Terminals

Three terminals for the lead set are on the top of the 475 Field Communicator. Each red terminal is a positive connection for its protocol. The black terminal is a common terminal shared by both protocols. An access door ensures only one pair of terminals

is exposed at any one time; see Figure 3-2. Several markings indicate which pair of

terminals is for which protocol.

HART Functionality

Figure 3-2. HART Communication Terminals and Access Door

Access Door Communication Terminals

3-7

HART Communication Terminal Markings

NOTE

The lead set must be used to communicate with a wired or wireless device. The 475

Field Communicator cannot communicate wirelessly with devices.

Wiring Diagrams

Figure 3-3 shows how to connect the 475 Field Communicator to a HART loop.

Figure 3-3. Connecting to a HART Loop

HART Device

+ -

+

-

RL

250Ω

-

+ mA

+

Current

Meter

-

+

+

Power

Supply

-

Figure 3-4 shows how to connect the 475 Field Communicator directly to the terminals

of a HART device.

Figure 3-4. Connecting Directly to a HART Device

HART Device

+

-

RL

250Ω

-

+ -

+ mA

+ -

+

+

Power

Supply

-

Current

Meter

3-8 HART Functionality

Figure 3-5 shows how to connect the optional 250 ohm resistor. Attaching a resistor is

necessary if less than 250 ohms resistance is present in the HART loop.

Figure 3-5. Connecting with a 250 Ohm Resistor

HART Device

+

Power

Supply

+ –

Optional 250-Ohm

Load Resistor

To temporarily install the optional 250 ohm load resistor:

1. Insert the load resistor into the lead set jacks.

2. Open the loop to allow connection of the resistor in series in the loop.

3. Close the loop using the lead set connectors.

Figure 3-6 shows how to connect the 475 Field Communicator directly to the

communication terminals on a wireless device.

Figure 3-6. Connecting to a wireless device

Wireless Device

Battery

Communication Terminals

HART Functionality

Displaying the Connected

HART Devices

3-9

After the device is connected, double-tap HART Application from the Field

Communicator Main Menu. The HART Application automatically polls for connected

devices using the selected polling options. See “Changing the HART Polling Options” on page 3-15 for information on modifying these options.

NOTE

Communication errors, such as a device appearing at multiple addresses, can occur when polling addresses greater than 15 on a loop with both HART revision 5 or earlier and HART revision 6 or higher devices.

For many devices, an Online menu similar to Figure 3-7 is the first menu to appear

when connected to a HART device and is the root menu for the device. This menu displays critical, up-to-date process information that is continuously updated, including device setup, primary variable (PV), analog output (AO), PV lower range value (LRV), and PV upper range value (URV). If a different Online menu appears, see your device documentation for details on the available menu options. The menus and configuration parameters for devices vary because they are defined in the device description. See your device documentation for more information.

NOTE

Dynamic variables shown while online represent the digital data being sent from the device.

Figure 3-7. HART Online Menu Example

Because the Online menu displays important information, some submenus display the

HOME button to return you to the HART Online menu.

3-10

Interpreting the HART Icon

Saving a Device

Configuration

HART Functionality

A beating HART icon appears at the top of the window when the 475 Field

Communicator is communicating with a device. See the table below for the icons and their meanings.

Table 3-1. HART Icons

Icon Meaning

The 475 Field Communicator is communicating with a live, online HART device.

The 475 Field Communicator is communicating with a HART loop with a device in burst mode.

The 475 Field Communicator is running in shout/deaf mode, which helps the

475 communicate with a device when it is on a noisy loop.

The 475 Field Communicator is running in shout/deaf mode and communicating to a HART loop with a device in burst mode.

Communication is not occurring. This is common when only non-dynamic parameters are listed.

When you save a configuration from a connected device, it is saved as a device configuration.

To save the configuration in the connected device:

1. Ensure the 475 Field Communicator is connected to a HART loop or directly to the device and turn on the 475 Field Communicator.

2. Double-tap HART Application from the Field Communicator Main Menu. The

HART Online menu appears.

3. Tap Save. The Save button will not appear if you have already saved the configuration while connected to the device. You may need to make a change to the configuration or disconnect and then reconnect to the device to resave.

a.To set the location where the configuration will be saved, double-tap Location, select an option, and tap ENTER. b.To specify a name for the configuration, double-tap Name, enter the name, and tap ENTER.

4. Tap Save. If the configuration already exists, a message appears. Tap YES to overwrite the older version with the new version, or tap NO to return to the Save as window.

HART Functionality

Displaying Device Setup

Options

3-11

The Device Setup on the HART Online menu accesses every configurable parameter for the connected device. Some devices may not display a Device Setup menu. Check your device documentation for more information. Double-tap Device setup to view the process variables, diagnostics and service, basic setup, detailed setup, and review menus.

Process Variables

The Process Variables menu lists all process variables and their values. Process variables are continuously updated when this window is displayed.

Diagnostics and Service

The Diagnostics and Service menu offers device and loop tests as well as calibration options. The diagnostics and service operations that are available vary widely from device to device and are defined in the device description.

The Test device menu lists the status as well as self and master test of the device. Test device initiates a diagnostic routine at the device and can report an electronics failure, as well as other failures that can affect performance.

Loop test is used to set the output of the device at a specified analog value, and may be used to test the integrity of the loop and the operation of indicators, recorders, or similar devices in the loop.

Calibration is used to perform such operations as performing a sensor trim, D/A trim, and scaled D/A trim.

Basic setup

The Basic setup menu provides quick access to a number of configurable parameters including tag, unit, range values, and damping.

The options available in the Basic setup menu are the most fundamental tasks that can be performed with a device. These tasks are a subset of the options available under the Detailed setup menu.

The Tag identifies a specific device. Changing the unit option affects the engineering units that are displayed. Changing range values modifies the analog output scaling.

Changing damping affects the response time of the transmitter and is often used to smooth the output when there are rapid input variations.

A modified parameter is highlighted yellow and an asterisk appears to indicate the change has not been sent to the device. Tap Send to update the device.

Figure 3-8. Modified Parameter Example

3-12

Displaying Graphics

HART Functionality

Detailed setup

The Detailed setup menu provides access to every editable device parameter and all device functions. The Detailed setup menu varies widely from one HART device to another. Functions in this menu can include tasks such as characterization, configuration, and sensor and output trims.

Review

The Review menu lists all of the static parameters read from the connected device, including information about the device and sensor setup and limitations. It also may include information about the connected device such as tag, materials of construction, and device software revision.

The HART Application offers graphical views of device data by using the enhanced

Electronic Device Description Language (EDDL) technology. Device data can be presented as images, charts, and graphs. These options appear as items in the HART

Online menu and its submenus. The placement of the graphics in the menus varies from device to device because it is determined by the device manufacturer.

To view the graphical representations, you need a device using an enhanced device description. Only devices using an enhanced EDDL device description offer graphical

representations of data. See Appendix C for more information about the Graphics

functionality.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents