Chapter 6 ____________________________________________________________ ppm Conversion
CHAPTER 6
PPM CONVERSION
This chapter contains information on conversion models.
MMT330 ppm Conversion for Transformer Oils
Traditionally, moisture in transformer oil is measured by using ppm units. The ppm output shows the average mass concentration of water in oil. MMT330 has an option for ppm output provided that this has been selected when ordering the transmitter. Vaisala has this conversion readily available for mineral transformer oils.
Conversion Model with Average Coefficients
The conversion model of the MMT330 is based on the average water solubility behaviour of transformer oils. The ppm output is calculated as follows:
ppm = aw x 10
(A/(T+273.16)+B) where: aw = Water activity
A,B = Coefficients (average/oil-specific)
T = Temperature (ºC)
Generally, measurements with MMT330 give accuracy better than 10 %
of the reading. If additional accuracy is needed, see section Conversion
Model with Oil-specific Coefficients on page 140.
NOTE The internal calculation in ppm conversion uses a w
also when only %RS output is selected when ordering MMT330.
To convert %RS to a w
, divide the %RS quantity by 100: a w
= (%RS / 100)
VAISALA _______________________________________________________________________ 139
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 13 GENERAL INFORMATION
- 13 About This Manual
- 13 Contents of This Manual
- 14 Version Information
- 14 Documentation Conventions
- 15 Safety
- 15 ESD Protection
- 16 Recycling
- 16 Regulatory Compliances
- 16 EU Declaration of Conformity
- 17 DNV Type Approval
- 18 Transmitters with LAN or WLAN Interface
- 18 Transmitters with WLAN Interface
- 19 Patent Notice
- 19 Trademarks
- 19 Software License
- 19 Warranty
- 21 PRODUCT OVERVIEW
- 21 Introduction to MMT
- 22 Basic Features and Options
- 22 Structure of the Transmitter
- 24 Probe Options
- 25 Typical Applications
- 25 Methods Used for Measuring Moisture in Oil
- 25 Lubrication Oil in Paper Machines
- 26 Transformer Oil
- 29 INSTALLATION
- 29 Mounting the Housing
- 29 Standard Mounting
- 30 Wall Mounting with Wall Mounting Kit
- 31 Mounting with DIN Rail Installation Kit
- 31 Pole Installation with Installation Kit for Pole or Pipeline
- 33 Mounting Rain Shield with Installation Kit
- 34 Panel Mounting Frame
- 35 Wiring
- 35 Cable Bushings
- 36 Grounding the Cables
- 37 Grounding the Transmitter Housing
- 38 Signal and Power Supply Wiring
- 40 Connections to a 24 VAC Power Supply
- 41 MMT332 for High-Pressure Applications
- 41 MMT337 Small Pressure-Tight Probe
- 42 Installations
- 44 MMT338 for Pressurized Pipelines
- 45 Tightening the Clasp Nut
- 46 Ball Valve Installation Kit for MMT
- 49 Sampling Cell for MMT
- 50 Optional Modules
- 50 Power Supply Module
- 51 Installation
- 52 Warnings
- 55 Galvanic Isolation for Power Supply
- 55 Third Analog Output
- 56 Installation and Wiring
- 57 Relays
- 57 Installation and Wiring
- 57 Selecting the Activation State of the Relay
- 58 RS-422/485 Interface
- 59 Installation and Wiring
- 63 LAN Interface
- 64 WLAN Interface
- 65 Attaching the WLAN Antenna
- 65 Data Logger Module
- 67 8-Pin Connector
- 69 OPERATION
- 69 Getting Started
- 69 Display/Keypad (Optional)
- 69 Basic Display
- 70 Graphic History
- 72 Menus and Navigation
- 73 Changing the Language
- 73 Rounding Setting
- 73 Display Backlight Setting
- 74 Display Contrast Setting
- 74 Using Display/Keypad
- 74 Using Serial Line
- 74 Keypad Lock (Keyguard)
- 75 Menu PIN Lock
- 75 Factory Settings
- 76 Display Alarms
- 77 Configuring a Display Alarm
- 78 Using Serial Line
- 80 MI70 Link Program for Data Handling
- 81 Serial Line Communication
- 82 User Port Connection
- 82 User Port Operating Modes
- 83 Service Port Connection
- 83 Connection Cables
- 83 Installing the Driver for the USB Cable
- 84 Using the Service Port
- 84 LAN Communication
- 85 IP Configuration
- 86 Using Display/Keypad
- 87 Using Serial Line
- 88 Wireless LAN Configuration
- 89 Using Display/Keypad
- 90 Using Serial Line
- 91 Communication Protocol
- 91 Web Configuration for LAN and WLAN
- 92 Terminal Program Settings
- 92 Opening a Serial/USB connection
- 94 Opening a Telnet session (LAN/WLAN)
- 95 List of Serial Commands
- 97 Getting Measurement Message from Serial Line
- 97 Starting Continuous Outputting
- 98 Stopping Continuous Outputting
- 98 Outputting Reading Once
- 98 Assign an Alias for the SEND Command
- 99 Outputting Reading Once From All Transmitters
- 99 Communicating with a Transmitter in POLL Mode
- 99 CLOSE
- 100 Formatting Serial Line Message
- 100 FTIME and FDATE
- 101 General Settings
- 101 Changing Quantities and Units
- 101 Using Display/Keypad
- 102 Using Serial Line
- 104 Date and Time
- 104 Using Display/Keypad
- 104 Using Serial Line
- 105 Data Filtering
- 105 Using Display/Keypad
- 105 Using Serial Line
- 106 Device Information
- 107 LIGHT
- 109 Resetting Transmitter by Using Serial Line
- 109 RESET
- 109 Locking Menu/Keypad Using Serial Line
- 110 Serial Output Settings
- 110 Using Display/Keypad
- 111 Using Serial Line
- 111 SMODE
- 113 SDELAY
- 113 Data Recording
- 114 Selecting Data Recording Quantities
- 114 View Recorded Data
- 117 Deleting the Recorded Files
- 117 UNDELETE
- 118 Analog Output Settings
- 118 Changing Output Mode and Range
- 119 Analog Output Quantities
- 120 AMODE/ASEL
- 121 Analog Output Tests
- 121 ITEST
- 122 Analog Output Fault Indication Setting
- 123 Extend Analog Output Range
- 123 Operation of Relays
- 123 Quantity for Relay Output
- 123 Relay Setpoints
- 125 Hysteresis
- 125 Relay Indicating Transmitter Error Status
- 127 Enabling/Disabling Relays
- 127 Setting Relay Outputs
- 131 Testing Operation of Relays
- 131 RTEST
- 133 MODBUS
- 133 Overview of Modbus Protocol Support
- 134 Taking Modbus into Use
- 135 Enabling Serial Modbus
- 135 Using Display/Keypad (Optional)
- 135 Using Serial Line
- 136 Enabling Ethernet Modbus
- 136 Using Display/Keypad (Optional)
- 138 Using Serial Line
- 139 Diagnostic Modbus Counters
- 139 Viewing Counters Using Display/Keypad
- 139 Viewing Counters Using Service Port
- 140 Disabling Modbus
- 141 PPM CONVERSION
- 141 MMT330 ppm Conversion for Transformer Oils
- 141 Conversion Model with Average Coefficients
- 142 Conversion Model with Oil-specific Coefficients
- 142 Setting Oil Coefficients Using Serial Line
- 143 Using Display/Keypad
- 143 Determination of Oil-Specific Coefficients
- 145 MAINTENANCE
- 145 Periodic Maintenance
- 145 Cleaning
- 145 Changing the Probe Filter
- 146 Changing the Sensor
- 147 Error States
- 149 Technical Support
- 151 CALIBRATION AND ADJUSTMENT
- 152 Cleaning the Sensor
- 152 Opening and Closing the Adjustment Mode
- 153 Relative Humidity Adjustment
- 153 Using Push Buttons
- 154 Using Display/Keypad
- 155 Using Serial Line
- 156 Relative Humidity Adjustment after Sensor Change
- 156 Using Display/Keypad
- 156 Using Serial Line
- 157 Temperature Adjustment
- 157 Using Display/Keypad
- 158 Using Serial Line
- 159 Analog Output Adjustment
- 159 Using Display/Keypad
- 159 Using Serial Line
- 160 Feeding Adjustment Information
- 160 Using Display/Keypad
- 160 Using Serial Line
- 160 CTEXT
- 160 CDATE
- 161 TECHNICAL DATA
- 161 Specifications
- 161 Performance
- 161 Water Activity and Relative Saturation
- 161 Temperature
- 162 Operating Environment
- 162 Probe Specifications
- 163 Inputs and Outputs
- 163 Mechanics
- 164 Technical Specifications of Optional Modules
- 164 Power Supply Module
- 164 Analog Output Module
- 165 Relay Module
- 165 RS-485 Module
- 165 LAN Interface Module
- 165 WLAN Interface Module
- 166 Data Logger Module
- 166 Spare Parts and Accessories
- 168 Dimensions (mm/inch)
- 171 MMT337 with Swagelok Connector
- 173 MODBUS REFERENCE
- 173 Function Codes
- 174 Register Map
- 174 Data Encoding
- 174 32-Bit Floating Point Format
- 175 16-Bit Integer Format
- 176 Measurement Data (Read-Only)
- 176 Status Registers (Read-Only)
- 176 Configuration Registers
- 177 Exception Status Outputs
- 178 Diagnostic Sub-Functions
- 179 Device Identification Objects
- 179 Exception Responses