- No category
advertisement
Chapter 6
Certification
Section 6.4
EMI and Environmental Type Tests
The RSG2300 has passed the following EMI and environmental tests.
IEC 61850-3 EMI Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
ESD
Radiated RFI
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
IEC 61000-4-4 Burst (Fast Transient)
IEC 61000-4-5 Surge
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports a
Signal Ports
IEC 61000-4-6 Induced (Conducted) RFI
DC Power Ports
AC Power Ports
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV Line-to-Earth,
+/- 2 kV Line-to-Line
+/- 2 kV Line-to-Earth,
+/- 1 kV Line-to-Line
+/- 4 kV Line-to-Earth,
+/- 2 kV Line-to-Line
10 V
IEC 61000-4-8 Magnetic Field
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports a
Enclosure Ports
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
Voltage Dips and
Interrupts (DC
Power Ports)
Voltage Dips and
Interrupts (A. C.
Power Ports)
Damped Oscillatory
DC Power Ports
AC Power Ports
AC Power Ports
40 A/m, Continuous,
1000 A/m for 1 s
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for 50 periods
2.5 kV Common,
1 kV Differential
Mode @1 MHz
IEC 61000-4-16
IEC 61000-4-17
Mains Frequency Voltage
Ripple on DC
Power Supply
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
DC Power Ports
30 V Continuous,
300 V for 1s
10%
38
RUGGEDCOM RSG2300
Installation Guide
Severity Levels
4
4
4
3
4
3
4
3
3
EMI and Environmental Type Tests
RUGGEDCOM RSG2300
Installation Guide
Chapter 6
Certification
Test
IEC 60255-5
Description
Dialiectric Strength Signal Ports
H.V. Impulse
DC Power Ports
AC Power Ports
Signal Ports
Test Levels
2 kVAC (Fail-
Safe Relay Output)
1.5 kVDC
2 kVAC
5 kV (Fail-Safe
Relay Output)
5 kV
Severity Levels
IEC 1613/C37.90
IEC 1613/C37.90.1
Dialiectric Strength
H.V. Impulse
Oscillatory
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Fast Transient Signal Ports
DC Power Ports
IEEE C37.90.2
IEC 1613/C37.90.3
Radiated RFI
ESD
AC Power Ports
Earth Ground Ports a
Enclosure Ports
Enclosure Contact
Enclosure Air a
Only applicable to functional earth connections separated from the safety earth connection.
5 kV (Fail-Safe
Relay Output)
5 kV
5 kV
2 kVAC
1.5 kVDC
2 kVAC
2.5 kV Common
Mode @1 MHz
2.5 kV Common,
1 kV Differential
Mode @1 MHz
+/- 4 kV @ 2.5 kHz
+/- 4 kV
35 V/m
+/- 8 kV
+/- 15 kV
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RSG2300 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for copper ports.
Test
IEEE C37.90.3
IEEE C37.90.2
IEEE C37.90.1
ESD
Radiated RFI
Fast Transient
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
Test Levels
+/-8 kV
+/-15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
EMI and Environmental Type Tests 39
Chapter 6
Certification
Test
Oscillatory
Description
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
IEEE C37.90
IEEE C37.90
H.V. Impulse
Dielectric Strength
Environmental Type Tests
Test
IEC 60068-2-1
Description
Cold Temperature
IEC 60068-2-2
IEC 60068-2-30
Dry Heat
Humidity (Damp Heat, Cyclic)
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Test Ad
Test Bd
Test Db
IEC 60068-21-1
IEC 60068-21-2
Vibration
Shock
RUGGEDCOM RSG2300
Installation Guide
Test Levels
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV Common Mode @1MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
5 kV (Fail-Safe Relay Output)
5 kV
5 kV
2 kVAC
1.5 kVDC
2 kVAC
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
2g @ 10-50 Hz
30 g @ 11 ms
40 EMI and Environmental Type Tests
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 1.1 Feature Highlights
- 8 1.2 Ports, Controls and Indicator LEDs
- 11 2.1 Mounting the Device
- 12 2.1.1 Mounting the Device to a Rack
- 13 2.1.2 Mounting the Device on a DIN Rail
- 13 2.1.3 Mounting the Device to a Panel
- 14 2.2 Connecting Power
- 15 2.2.1 Connecting AC Power
- 16 2.2.2 Connecting DC Power
- 18 2.2.3 Wiring Examples
- 20 2.3 Connecting the Failsafe Alarm Relay
- 21 2.4 Grounding the Device
- 21 2.5 Connecting to the Device
- 22 2.6 Cabling Recommendations
- 23 2.6.1 Protection On Twisted-Pair Data Ports
- 23 2.6.2 Gigabit Ethernet 1000Base-TX Cabling Recommendations
- 26 3.1 Copper Ethernet Ports
- 27 3.2 Fiber Optic Ethernet Ports
- 27 3.3 SFP Optic Ethernet Ports
- 28 3.3.1 Installing an SFP Optical Port
- 29 3.3.2 Removing an SFP Optical Port
- 30 3.4 GBIC Optic Ethernet Ports
- 30 3.4.1 Installing a GBIC Optical Port
- 31 3.4.2 Removing a GBIC Optical Port
- 33 4.1 Power Supply Specifications
- 33 4.2 Failsafe Relay Specifications
- 34 4.3 Supported Networking Standards
- 34 4.4 Copper Ethernet Port Specifications
- 34 4.4.1 Copper Fast (10/100 Mbps) Ethernet Port Specifications
- 35 4.4.2 Copper Gigabit Ethernet (1 Gbps) Port Specifications
- 35 4.5 Fiber Optic Ethernet Port Specifications
- 36 4.5.1 10FL Ethernet Optical Specifications
- 36 4.5.2 Fast Ethernet (10/100 Mbps) Optical Specifications
- 37 4.5.3 Gigabit Ethernet (1 Gbps) Optical Specifications
- 38 4.6 Operating Environment
- 38 4.7 Mechanical Specifications
- 43 6.1 Agency Approvals
- 43 6.2 FCC Compliance
- 43 6.3 Industry Canada Compliance
- 44 6.4 EMI and Environmental Type Tests