Liebert eXM TXC
NOTICE
Risk of improper wiring connection. Can cause equipment damage.
The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between bypass cabinet and UPS.
NOTES
1. All interconnection hardware supplied by Emerson.
2. AC connections must be made to the UPS module before attaching Liebert eXM TXC to UPS module.
3. Liebert eXM TXC’s must attach to the right side only of the Liebert eXM UPS.
4. Refer to the individual drawing of each piece of equipment for additional details.
Table 1 Wiring for Liebert eXM TXC to Liebert eXM
Run
A
E
C
H
B
C
D
From
Utility Source #1
Utility Neutral #1
Utility Ground #1
Utility Source #2
Utility Neutral #2
Utility Ground #2
TXC GEC
To
TXC Rectifier Input
TB1
TXC Neutral Busbar
TXC Ground Busbar
TXC Bypass Input TB2
TXC Neutral Busbar
TXC Ground Busbar
Customer GEC
Conductors
Phase A, B, C
Neutral
Ground
Phase A, B, C
Neutral
Ground
GEC
Figure 2 Schematic - Liebert eXM TXC to Maintenance Bypass Cabinet
Customer
Main Input
TB1
Phase A
Phase B
Phase C
W04
W05
W06
X-A
H1
H2
Isolation
Transformer
T1
X-B
X-C
H3
X0
W11
W12
W13
W14
Utility Input
Ground to
Unit Frame
Phase A
Phase B
Phase C
Customer
Bypass Input
TB2
W01
W02
W03
Customer
Input Neutral
Customer
Ground Busbar
Ground to
Unit Frame
X-A
H1
H2
Isolation
Transformer
T2
X-B
X-C
H3
X0
W07
W08
W09
W10
Ground to
Unit Frame
Ground Electrode
(See Note 2)
W15
W16
TB2
CIN
CMG
TB4
Narrow Side Mount
Maintenance Bypass Cabinet
Wiring Legend
Factory Supplied
Field Supplied
NOTES:
1. Wiring furnished by the factory. Consult the installation manual for UPS connections
2. Customer-furnished grounding electrode conductor is to be installed in accordance with
National Electric Code Article 250-26.
3. Refer to Liebert
eXM MBC manual SL-25652 for additional details about connections to Liebert eXM UPS.
607503
Rev. 1
Liebert
®
eXM
™
TXC
™
8
1.3
Bolting Cabinets Together
NOTE
UPS wiring must be completed before the cabinets are bolted together.
1. Line up cabinets so that mounting holes are aligned.
Figure 3 Bolting Liebert eXM UPS to a Liebert eXM TXC
Liebert eXM TXC
A
Hex Head
Bolt,
M10 x 30mm
Washer Split,
M10
Washer Flat,
M10
Place cabinets so mounting holes are aligned.
A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet.
DETAIL A
2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the
UPS side or from the Liebert eXM TXC side, whichever is more convenient.
!
WARNING
Risk of heavy units tipping over while being moved. Can cause property damage, injury and death.
The Liebert eXM TXC and battery cabinets must be properly prepared and secured for lifting.
Improper lifting may cause the cabinets to fall, causing equipment damage, personal injury and death.
Emerson recommends lifting the units with one of the following methods:
• Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism.
• Placing suitable straps on the Liebert eXM TXC. The straps must go under the unit to be lifted.