Liebert eXM TXC

NOTICE

Risk of improper wiring connection. Can cause equipment damage.

The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between bypass cabinet and UPS.

NOTES

1. All interconnection hardware supplied by Emerson.

2. AC connections must be made to the UPS module before attaching Liebert eXM TXC to UPS module.

3. Liebert eXM TXC’s must attach to the right side only of the Liebert eXM UPS.

4. Refer to the individual drawing of each piece of equipment for additional details.

Table 1 Wiring for Liebert eXM TXC to Liebert eXM

Run

A

E

C

H

B

C

D

From

Utility Source #1

Utility Neutral #1

Utility Ground #1

Utility Source #2

Utility Neutral #2

Utility Ground #2

TXC GEC

To

TXC Rectifier Input

TB1

TXC Neutral Busbar

TXC Ground Busbar

TXC Bypass Input TB2

TXC Neutral Busbar

TXC Ground Busbar

Customer GEC

Conductors

Phase A, B, C

Neutral

Ground

Phase A, B, C

Neutral

Ground

GEC

Figure 2 Schematic - Liebert eXM TXC to Maintenance Bypass Cabinet

Customer

Main Input

TB1

Phase A

Phase B

Phase C

W04

W05

W06

X-A

H1

H2

Isolation

Transformer

T1

X-B

X-C

H3

X0

W11

W12

W13

W14

Utility Input

Ground to

Unit Frame

Phase A

Phase B

Phase C

Customer

Bypass Input

TB2

W01

W02

W03

Customer

Input Neutral

Customer

Ground Busbar

Ground to

Unit Frame

X-A

H1

H2

Isolation

Transformer

T2

X-B

X-C

H3

X0

W07

W08

W09

W10

Ground to

Unit Frame

Ground Electrode

(See Note 2)

W15

W16

TB2

CIN

CMG

TB4

Narrow Side Mount

Maintenance Bypass Cabinet

Wiring Legend

Factory Supplied

Field Supplied

NOTES:

1. Wiring furnished by the factory. Consult the installation manual for UPS connections

2. Customer-furnished grounding electrode conductor is to be installed in accordance with

National Electric Code Article 250-26.

3. Refer to Liebert

eXM MBC manual SL-25652 for additional details about connections to Liebert eXM UPS.

607503

Rev. 1

Liebert

®

eXM

TXC

8

1.3

Bolting Cabinets Together

NOTE

UPS wiring must be completed before the cabinets are bolted together.

1. Line up cabinets so that mounting holes are aligned.

Figure 3 Bolting Liebert eXM UPS to a Liebert eXM TXC

Liebert eXM TXC

A

Hex Head

Bolt,

M10 x 30mm

Washer Split,

M10

Washer Flat,

M10

Place cabinets so mounting holes are aligned.

A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet.

DETAIL A

2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the

UPS side or from the Liebert eXM TXC side, whichever is more convenient.

!

WARNING

Risk of heavy units tipping over while being moved. Can cause property damage, injury and death.

The Liebert eXM TXC and battery cabinets must be properly prepared and secured for lifting.

Improper lifting may cause the cabinets to fall, causing equipment damage, personal injury and death.

Emerson recommends lifting the units with one of the following methods:

• Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism.

• Placing suitable straps on the Liebert eXM TXC. The straps must go under the unit to be lifted.

9 Liebert

®

eXM

TXC