Figure 5 Clearances—Front, side and rear

REAR

0 to 5" (127mm)

Rear clearance depends on anchoring method

Liebert eXM TXC

0" Required

Liebert

eXM

0" Required

FRONT

Minimum of 36" (914mm) required for foot traffic with door fully open

11 Liebert

®

eXM

TXC

Installation Drawings

2.0

I

NSTALLATION

D

RAWINGS

Figure 6 Liebert eXM TXC Main components

Neutral

Busbar

TB2

TB1

Ground

Busbar

Transformers

FRONT

With Cover

FRONT

Door Removed

Figure 7 Busbars—Liebert eXM TXC

23.6" (600mm)

37.5" (953mm)

TB1

Neutral Busbar

(See DETAIL A)

Ground Busbar

(See DETAIL A)

TB2

78.5"

(1994mm)

RIGHT SIDE

Panel Removed

EXM15010

Rev. 1

7.5"

(191mm)

See DETAILS B and C

3.5"

(89mm)

∅ 0.437"

(11mm)

10 Typical

Transformers

1.75"

(44mm)

Typical

DETAIL A

Ground and Neutral

Busbars

0.5"

(13mm)

1.5"

(38mm)

Typical

FRONT VIEW with Door Removed

RIGHT SIDE VIEW with Panel Removed

Notes:

1. All dimentions are in inches (mm).

2. Control wiring and power wiring must be run in separate conduits.

3. All wiring is to be in accordance with national and local electrical codes.

4. If maintenance bypass cabinet is attached to UPS, Liebert will supply

the interconnection cables.

5. Use 255A panelboard for 10k - 40kVA only. Use 400A panelboard for

60 - 100kVA only.

1.75"

(44mm)

∅ 0.440" (11mm)

12 Typical

2.25"

(57mm)

2.25"

(57mm)

DETAIL B

1.75"

(44mm)

1.75"

(44mm)

1.75"

(44mm)

∅ 0.438" (11mm)

28 Typical

EXM16014

Rev. 1

Liebert

®

eXM

TXC

12

Installation Drawings

Figure 8 Lineup arrangement, Liebert eXM with Liebert eXM TXC

47.5" (1208mm)

23.6"

(600mm)

23.6"

(600mm)

78.7"

(2000mm)

NOTES

1. All dimensions are in inches (mm).

2. 24" (610mm) minimum clearance above unit for air exhaust.

36" (914mm) front access required for service.

3. Keep cabinet within 15 degrees of vertical.

4. Top and bottom cable entry available through removable

access plates.

Remove, punch to suit conduit size and replace.

5. Unit bottom is structurally adequate for forklift handling.

6. Control wiring and power wiring must be run in

separate conduits.

7. All wiring is to be in accordance with national and local electrical codes.

8. All battery cabinets must be positioned on the left side of the UPS.

EXM13003

Rev. 1

UPS

Dual Transformer

Cabinet

FRONT VIEW

13 Liebert

®

eXM

TXC

Installation Drawings

Figure 9 Outline drawing, Liebert eXM TXC for Liebert eXM, 10-100kVA

See Detail A

20.4"

(519mm)

15.3"

(387mm)

Leveler

Ventilation

TOP

24" (608mm)

23.6"

(600mm)

BOTTOM

39.8" (1010mm)

34.5"

(876mm)

28.3"

(718mm)

Caster

DETAIL A

Notes

1. 24" [610] minimum clearance above unit for

air exhaust. 36" [914] front access required for service.

2. Keep cabinet within 15 degrees of vertical.

3. Top and bottom cable entry available through removable

access plates. Remove, punch to suit conduit size

and replace.

4. Unit bottom is structurally adequate for forklift handling.

5. Control wiring and power wiring must be run in

separate conduits.

6. All wiring is to be in accordance with national and

local electrical codes.

78.7"

(2000mm)

FRONT RIGHT SIDE

EXM12009

Rev. 1

Liebert

®

eXM

TXC

14

Installation Drawings

Figure 10 Liebert eXM TXC transformer location

Transformer, T1

Transformer, T2

RIGHT SIDE

REAR OF CABINET

15 Liebert

®

eXM

TXC

Figure 11 Bend radius - Top feed power connections, 10-100kVA system

Installation Drawings

Table 2

NOTE

Interconnection wiring between the UPS and bypass distribution cabinet is supplied by

Emerson when the Liebert eXM TXC and Liebert eXM UPS are ordered as a system.

Hardware torque values

Hardware Two Belleville Washers

M10 (3/8")

M12 (1/2")

240 lb-in. (27 Nm)

428 lb-in (48Nm)

Liebert

®

eXM

TXC

16

Specifications

3.0

S

PECIFICATIONS

Table 3 Physical standards and parameters

Dual Transformer Cabinet Parameters

Standard Color

Front Door Opening (for serviceability)

Degree of Protection for UPS Enclosure

Minimum Clearance, Top

Minimum Clearance, Back

Minimum Clearance, Sides

Cable Entrance

Standards & Conformities

Environmental

Storage Temperature Range, °F (°C)

Operating Temperature Range, °F (°C)

Relative Humidity

Maximum Altitude Above MSL, ft (m)

Values

Black (ZP-7021)

More than 180°

IP 20 (with and without front door open)

24" (610mm)

0" (5" [127mm] when seismic brackets are used)

0"

Top or Bottom

UL 71778 5th Ed.; CSA 22.2 107.3-14

ISTA Procedure 1H; WEEE

-13°F to 158°F (-25°C to 70°C)

32°F to 104°F (0 to 40°C)

32°F to 86°F (0-30°C) when seismic brackets are used

Up to 95% Non-Condensing

(Operating and Non-Operating)

4920 (1500) (as per IEC 62040/3) -

1% Maximum kW derate / 100m rise between 1500-3000m

Table 4 Liebert eXM TXC, 10-100k, mechanical characteristics

Mechanical Characteristics

Dimensions, W x D x H, in (mm)

Color

Protection Degree IEC (60529)

Rated Power, kVA

40

60

80

100

10

15

20

30

Values

23.625 x 39.375 x 78.75 (600 x 1000 x 2000)

ZP 7021 (Black)

IP20 (finger-proof with front doors open or closed)

Weight, lb (kg)

785 (356)

819 (371)

919 (417)

1192 (541)

1245 (565)

1495 (678)

1765 (801)

1969 (893)

17 Liebert

®

eXM

TXC

Specifications

Table 5

Liebert eXM

TXC Rating kVA

10

15

20

30

40

60

80

100

Liebert eXM TXC heat dissipation, both transformers, full load

Liebert eXM

TXC Heat

Dissipation

208:208 Transformer

BTU/Hr (kWH)

3514 (1.030)

4802 (1.408)

5822 (1.706)

10024 (2,938)

10816 (3.170)

15006 (4.398)

19750 (5.788)

19204 (5.628)

Liebert eXM

TXC Heat

Dissipation

220:208 Transformer

BTU/Hr (kWH)

3132 (0.918)

4278 (1.254)

5186 (1.520)

9076 (2.660)

9854 (2.888)

13696 (4.014)

17934 (5.256)

16944 (4.966)

Liebert eXM

TXC Heat

Dissipation

480:208 Transformer

BTU/Hr (kWH)

3276 (0.960)

4026 (1.180)

5466 (1.602)

9896 (2.900)

10686 (3.132)

13710 (4.018)

19026 (5.576)

21216 (6.218)

Liebert eXM

TXC Heat

Dissipation

600:208 Transformer

BTU/Hr (kWH)

3322 (0.974)

3992 (1.170)

5362 (1.572)

9998 (2.930)

10714 (3.140)

13710 (4.018)

19032 (5.578)

21190 (6.210)

NOTE

The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for Rectifier and Bypass inputs. Recommended cable sizes are suitable for operation at a maximum temperature of 104°F (40°C).

Table 6

Cable Size

#6AWG

#4AWG

#2-3AWG

#1AWG

#1/0AWG

#2/0AWG

#3/0AWG

#4/0AWG

250kcmil

300kcmil

350kcmil

400kcmil

500kcmil

600kcmil

700kcmil

750kcmil

Recommended lug sizes (compression type) M10, 3/8" bolt

T&B Copper

Two Hole

256-030695-868

256-030695-733

54811BE

54857BE

256-30695-593

54862BE

54864BE

54866BE

54868BE

54870BE

54872BE

54874BE

54876BE

54878BE

54879BE

54880BE

T&B Aluminum

Two Hole

60250

60256

60262

60267

60269

60273

60275

60277

60278

60238

60244

Table 7 Busbar torque for power wiring

Bolt Shaft Size

3/8" (M10)

1/2" (M12)

Torque

Lb-in (Nm)

192 (22)

428 (48)

Liebert

®

eXM

TXC

18

Specifications

Table 8 Terminal block torque with compression lugs for control wiring

AWG Wire Size or Range

#22 - #14

Torque

Lb-in (Nm)

3.5 to 5.3

(0.4 to 0.6)

NOTE

Refer to the manufacturer’s data for proper torque for circuit breaker power connections.

Table 9 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, rectifier input, with

480V:208V transformer

Liebert

eXM TXC

Rating kVA

Maximum

Rectifier

Input

Current, A Phase

10

15

20

30

15

23

31

46

3W + G

3W + G

3W + G

3W + G

40

60

80

100

61

91

122

152

3W + G

3W + G

3W + G

3W + G

See Notes on Tables on page 21.

Recommended

Upstream

Protection, A

80

125

175

200

20

30

40

60

75°C Wire

Current A

Total

85

150

200

205

40

40

40

65

Copper

Wire

(1) #8

(1) #8

(1) #8

(1) #6

(1) #4

(1) #2

(1) 1/0

(1) 4/0

Aluminum

Wire

(1) #8

(1) #8

(1) #8

(1) #4

(1) #2

(1) 1/0

(1) 3/0

(1) 250 kcmil

Bolt Size

M10

M10

M10

M10

M10

M10

M10

M10

Table 10 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, bypass input, with

480V:208V transformer

Liebert

eXM TXC

Rating kVA

Maximum

System Input

Current, A Phase

10

15

20

30

13

19

25

38

3W + G

3W + G

3W + G

3W + G

40

60

80

100

50

74

99

124

3W + G

3W + G

3W + G

3W + G

See Notes on Tables on page 21.

Recommended

Upstream

Protection, A

70

100

125

175

20

25

35

50

75°C Wire

Current A

Total

85

150

200

205

40

40

40

65

Copper

Wire

(1) #8

(1) #8

(1) #8

(1) #6

(1) #4

(1) #2

(1) 1/0

(1) 4/0

Aluminum

Wire

(1) #8

(1) #8

(1) #8

(1) #4

(1) #2

(1) 1/0

(1) 3/0

(1) 250 kcmil

Bolt Size

M10

M10

M10

M10

M10

M10

M10

M10

19 Liebert

®

eXM

TXC

Specifications

Table 11 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, rectifier input, with

600V:208V transformer

Liebert

eXM TXC

Rating kVA

10

15

Maximum

Rectifier Input

Current, A

12

18

20

30

40

60

25

37

49

73

80

100

98

122

See Notes on Tables on page 21.

Phase

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

Recommended

Upstream

Protection, A

20

25

35

50

70

100

125

175

75°C Wire

Current A

Total

40

40

40

50

85

100

130

150

Copper

Wire

(1) #8

(1) #8

(1) #8

(1) #8

(1) #4

(1) #3

(1) #1

(1) 1/0

Aluminum

Wire

(1) #8

(1) #8

(1) #8

(1) #6

(1) #3

(1) #1

(1) 2/0

(1) 3/0

Bolt Size

M10

M10

M10

M10

M10

M10

M10

M10

Table 12 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, bypass input, with

600V:208V transformer

Liebert

eXM TXC

Rating kVA

Maximum

System Input

Current, A

30

40

60

80

10

15

20

10

15

20

30

40

60

79

100 99

See Notes on Tables on page 21.

Phase

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

Recommended

Upstream

Protection, A

15

20

30

40

60

80

100

125

75°C Wire

Current A

Total

40

40

40

50

85

150

200

205

Copper

Wire

(1) #8

(1) #8

(1) #8

(1) #8

(1) #6

(1) #3

(1) #1

(1) 1/0

Aluminum

Wire

(1) #8

(1) #8

(1) #8

(1) #6

(1) #4

(1) #2

(1) 1/0

(1) 3/0

Bolt Size

M10

M10

M10

M10

M10

M10

M10

M10

Table 13 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, rectifier input, with

208V:208V or 220V:220V transformer

Liebert

eXM TXC

Rating kVA

Maximum

Rectifier

Input

Current, A

30

40

60

80

10

15

20

36

53

71

107

141

211

281

100 352

See Notes on Tables on page 21.

Phase

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

Recommended

Upstream

Protection, A

150

200

300

400

450

45

70

90

75°C Wire

Current A

Total

65

85

100

175

230

335

460

510

Copper

Wire

Aluminum

Wire

Bolt

Size

(1) #6

(1) #4

(1) #3

(1) #4

(1) #2

(1) #1

M10

M10

M10

(1) 2/0

(1) 4/0

(1) 400 kcmil

(2) 4/0

(1) 4/0

(1) 300 kcmil

(2) 4/0

(2) 300 kcmil

M10

M10

M10

M10

(2) 250 kcmil (2) 400 kcmil M10

Liebert

®

eXM

TXC

20

Specifications

Table 14 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, bypass input, with

208V:208V or 220V:220V transformer

Liebert

eXM TXC

Rating kVA

10

15

Maximum

System Input

Current, A

29

43

20

30

40

60

58

87

116

172

80

100

229

286

See Notes on Tables below.

Phase

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

3W + G

Recommended

Upstream

Protection, A

40

60

80

110

150

225

300

400

75°C Wire

Current A

Total

65

85

100

150

230

285

350

460

Copper

Wire

(1) #6

(1) #4

Aluminum

Wire

(1) #4

(1) #2

Bolt

Size

M10

M10

(1) #3

(1) 1/0

(1) #1

(1) 3/0

M10

M10

(1) 4/0 (1) 300 kcmil M10

(1) 300 kcmil (1) 400 kcmil M10

(2) 2/0

(2) 4/0

(2) 4/0 M10

(2) 300 kcmil M10

Table 15 Liebert eXM TXC Inrush Multiplier

Liebert eXM

TXC Rating kVA

TXC

480V:208V

30

40

60

80

10

15

20

11.7

11.3

7.8

7.4

7.65

6.7

7.1

100 7.1

Note: Inrush Current = NFLA x Tabel Value

TXC

600V:208V

11.1

7.85

8.3

7.85

8.5

7.45

7.1

7.8

TXC

208V:208V

8.9

6.4

6.4

6.4

6.8

5.1

6.2

6.9

TXC

220V:220V

10.8

10.2

7.7

7.7

8.2

6.2

7.5

7.4

Notes on Tables

Notes apply to Tables 9 through 14.

1. Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Recommended overcurrent protection is based on 80% rated devices.

*The recommended overcurrent protection represents 125% of nominal full load current

(continuous) per NEC 215.

2. Maximum input current is controlled by the current limit setting.

3. Recommended AC input external overcurrent protection is based on 80% rated devices and maximum input current limit setting.

4. Recommended AC output external overcurrent protection is based on 80% rated devices and full rated output current.

5. Input power factor of 0.99 is used for the calculations.

21 Liebert

®

eXM

TXC

Liebert

®

eXM

TXC

22

Specifications

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

© 2014 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert is a registered trademark of Liebert Corporation.

All names referred to are trademarks or registered trademarks of their respective owners.

SL-25655_REV0_05-15

Emerson Network Power

Liebert www.emerson.com

Technical Support / Service

Web Site

www.liebert.com

Monitoring

[email protected]

800-222-5877

Outside North America: +00800 1155 4499

Single-Phase UPS & Server Cabinets

[email protected]

800-222-5877

Outside North America: +00800 1155 4499

Three-Phase UPS & Power Systems

800-543-2378

Outside North America: 614-841-6598

Environmental Systems

800-543-2778

Outside the United States: 614-888-0246

Locations

United States

1050 Dearborn Drive

P.O. Box 29186

Columbus, OH 43229

Europe

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD) Italy

+39 049 9719 111

Fax: +39 049 5841 257

Asia

29/F, The Orient Square Building

F. Ortigas Jr. Road, Ortigas Center

Pasig City 1605

Philippines

+63 2 687 6615

Fax: +63 2 730 9572

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals