Figure 5 Clearances—Front, side and rear
REAR
0 to 5" (127mm)
Rear clearance depends on anchoring method
Liebert eXM TXC
0" Required
Liebert
eXM
0" Required
FRONT
Minimum of 36" (914mm) required for foot traffic with door fully open
11 Liebert
®
eXM
™
TXC
™
Installation Drawings
2.0
I
NSTALLATION
D
RAWINGS
Figure 6 Liebert eXM TXC Main components
Neutral
Busbar
TB2
TB1
Ground
Busbar
Transformers
FRONT
With Cover
FRONT
Door Removed
Figure 7 Busbars—Liebert eXM TXC
23.6" (600mm)
37.5" (953mm)
TB1
Neutral Busbar
(See DETAIL A)
Ground Busbar
(See DETAIL A)
TB2
78.5"
(1994mm)
RIGHT SIDE
Panel Removed
EXM15010
Rev. 1
7.5"
(191mm)
See DETAILS B and C
3.5"
(89mm)
∅ 0.437"
(11mm)
10 Typical
Transformers
1.75"
(44mm)
Typical
DETAIL A
Ground and Neutral
Busbars
0.5"
(13mm)
1.5"
(38mm)
Typical
FRONT VIEW with Door Removed
RIGHT SIDE VIEW with Panel Removed
Notes:
1. All dimentions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. If maintenance bypass cabinet is attached to UPS, Liebert will supply
the interconnection cables.
5. Use 255A panelboard for 10k - 40kVA only. Use 400A panelboard for
60 - 100kVA only.
1.75"
(44mm)
∅ 0.440" (11mm)
12 Typical
2.25"
(57mm)
2.25"
(57mm)
DETAIL B
1.75"
(44mm)
1.75"
(44mm)
1.75"
(44mm)
∅ 0.438" (11mm)
28 Typical
EXM16014
Rev. 1
Liebert
®
eXM
™
TXC
™
12
Installation Drawings
Figure 8 Lineup arrangement, Liebert eXM with Liebert eXM TXC
47.5" (1208mm)
23.6"
(600mm)
23.6"
(600mm)
78.7"
(2000mm)
NOTES
1. All dimensions are in inches (mm).
2. 24" (610mm) minimum clearance above unit for air exhaust.
36" (914mm) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. All wiring is to be in accordance with national and local electrical codes.
8. All battery cabinets must be positioned on the left side of the UPS.
EXM13003
Rev. 1
UPS
Dual Transformer
Cabinet
FRONT VIEW
13 Liebert
®
eXM
™
TXC
™
Installation Drawings
Figure 9 Outline drawing, Liebert eXM TXC for Liebert eXM, 10-100kVA
See Detail A
20.4"
(519mm)
15.3"
(387mm)
Leveler
Ventilation
TOP
24" (608mm)
23.6"
(600mm)
BOTTOM
39.8" (1010mm)
34.5"
(876mm)
28.3"
(718mm)
Caster
DETAIL A
Notes
1. 24" [610] minimum clearance above unit for
air exhaust. 36" [914] front access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size
and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in
separate conduits.
6. All wiring is to be in accordance with national and
local electrical codes.
78.7"
(2000mm)
FRONT RIGHT SIDE
EXM12009
Rev. 1
Liebert
®
eXM
™
TXC
™
14
Installation Drawings
Figure 10 Liebert eXM TXC transformer location
Transformer, T1
Transformer, T2
RIGHT SIDE
REAR OF CABINET
15 Liebert
®
eXM
™
TXC
™
Figure 11 Bend radius - Top feed power connections, 10-100kVA system
Installation Drawings
Table 2
NOTE
Interconnection wiring between the UPS and bypass distribution cabinet is supplied by
Emerson when the Liebert eXM TXC and Liebert eXM UPS are ordered as a system.
Hardware torque values
Hardware Two Belleville Washers
M10 (3/8")
M12 (1/2")
240 lb-in. (27 Nm)
428 lb-in (48Nm)
Liebert
®
eXM
™
TXC
™
16
Specifications
3.0
S
PECIFICATIONS
Table 3 Physical standards and parameters
Dual Transformer Cabinet Parameters
Standard Color
Front Door Opening (for serviceability)
Degree of Protection for UPS Enclosure
Minimum Clearance, Top
Minimum Clearance, Back
Minimum Clearance, Sides
Cable Entrance
Standards & Conformities
Environmental
Storage Temperature Range, °F (°C)
Operating Temperature Range, °F (°C)
Relative Humidity
Maximum Altitude Above MSL, ft (m)
Values
Black (ZP-7021)
More than 180°
IP 20 (with and without front door open)
24" (610mm)
0" (5" [127mm] when seismic brackets are used)
0"
Top or Bottom
UL 71778 5th Ed.; CSA 22.2 107.3-14
ISTA Procedure 1H; WEEE
-13°F to 158°F (-25°C to 70°C)
32°F to 104°F (0 to 40°C)
32°F to 86°F (0-30°C) when seismic brackets are used
Up to 95% Non-Condensing
(Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) -
1% Maximum kW derate / 100m rise between 1500-3000m
Table 4 Liebert eXM TXC, 10-100k, mechanical characteristics
Mechanical Characteristics
Dimensions, W x D x H, in (mm)
Color
Protection Degree IEC (60529)
Rated Power, kVA
40
60
80
100
10
15
20
30
Values
23.625 x 39.375 x 78.75 (600 x 1000 x 2000)
ZP 7021 (Black)
IP20 (finger-proof with front doors open or closed)
Weight, lb (kg)
785 (356)
819 (371)
919 (417)
1192 (541)
1245 (565)
1495 (678)
1765 (801)
1969 (893)
17 Liebert
®
eXM
™
TXC
™
Specifications
Table 5
Liebert eXM
TXC Rating kVA
10
15
20
30
40
60
80
100
Liebert eXM TXC heat dissipation, both transformers, full load
Liebert eXM
TXC Heat
Dissipation
208:208 Transformer
BTU/Hr (kWH)
3514 (1.030)
4802 (1.408)
5822 (1.706)
10024 (2,938)
10816 (3.170)
15006 (4.398)
19750 (5.788)
19204 (5.628)
Liebert eXM
TXC Heat
Dissipation
220:208 Transformer
BTU/Hr (kWH)
3132 (0.918)
4278 (1.254)
5186 (1.520)
9076 (2.660)
9854 (2.888)
13696 (4.014)
17934 (5.256)
16944 (4.966)
Liebert eXM
TXC Heat
Dissipation
480:208 Transformer
BTU/Hr (kWH)
3276 (0.960)
4026 (1.180)
5466 (1.602)
9896 (2.900)
10686 (3.132)
13710 (4.018)
19026 (5.576)
21216 (6.218)
Liebert eXM
TXC Heat
Dissipation
600:208 Transformer
BTU/Hr (kWH)
3322 (0.974)
3992 (1.170)
5362 (1.572)
9998 (2.930)
10714 (3.140)
13710 (4.018)
19032 (5.578)
21190 (6.210)
NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for Rectifier and Bypass inputs. Recommended cable sizes are suitable for operation at a maximum temperature of 104°F (40°C).
Table 6
Cable Size
#6AWG
#4AWG
#2-3AWG
#1AWG
#1/0AWG
#2/0AWG
#3/0AWG
#4/0AWG
250kcmil
300kcmil
350kcmil
400kcmil
500kcmil
600kcmil
700kcmil
750kcmil
Recommended lug sizes (compression type) M10, 3/8" bolt
T&B Copper
Two Hole
256-030695-868
256-030695-733
54811BE
54857BE
256-30695-593
54862BE
54864BE
54866BE
54868BE
54870BE
54872BE
54874BE
54876BE
54878BE
54879BE
54880BE
T&B Aluminum
Two Hole
60250
60256
60262
60267
60269
60273
60275
60277
60278
—
—
—
—
—
60238
60244
Table 7 Busbar torque for power wiring
Bolt Shaft Size
3/8" (M10)
1/2" (M12)
Torque
Lb-in (Nm)
192 (22)
428 (48)
Liebert
®
eXM
™
TXC
™
18
Specifications
Table 8 Terminal block torque with compression lugs for control wiring
AWG Wire Size or Range
#22 - #14
Torque
Lb-in (Nm)
3.5 to 5.3
(0.4 to 0.6)
NOTE
Refer to the manufacturer’s data for proper torque for circuit breaker power connections.
Table 9 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, rectifier input, with
480V:208V transformer
Liebert
eXM TXC
Rating kVA
Maximum
Rectifier
Input
Current, A Phase
10
15
20
30
15
23
31
46
3W + G
3W + G
3W + G
3W + G
40
60
80
100
61
91
122
152
3W + G
3W + G
3W + G
3W + G
See Notes on Tables on page 21.
Recommended
Upstream
Protection, A
80
125
175
200
20
30
40
60
75°C Wire
Current A
Total
85
150
200
205
40
40
40
65
Copper
Wire
(1) #8
(1) #8
(1) #8
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) 4/0
Aluminum
Wire
(1) #8
(1) #8
(1) #8
(1) #4
(1) #2
(1) 1/0
(1) 3/0
(1) 250 kcmil
Bolt Size
M10
M10
M10
M10
M10
M10
M10
M10
Table 10 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, bypass input, with
480V:208V transformer
Liebert
eXM TXC
Rating kVA
Maximum
System Input
Current, A Phase
10
15
20
30
13
19
25
38
3W + G
3W + G
3W + G
3W + G
40
60
80
100
50
74
99
124
3W + G
3W + G
3W + G
3W + G
See Notes on Tables on page 21.
Recommended
Upstream
Protection, A
70
100
125
175
20
25
35
50
75°C Wire
Current A
Total
85
150
200
205
40
40
40
65
Copper
Wire
(1) #8
(1) #8
(1) #8
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) 4/0
Aluminum
Wire
(1) #8
(1) #8
(1) #8
(1) #4
(1) #2
(1) 1/0
(1) 3/0
(1) 250 kcmil
Bolt Size
M10
M10
M10
M10
M10
M10
M10
M10
19 Liebert
®
eXM
™
TXC
™
Specifications
Table 11 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, rectifier input, with
600V:208V transformer
Liebert
eXM TXC
Rating kVA
10
15
Maximum
Rectifier Input
Current, A
12
18
20
30
40
60
25
37
49
73
80
100
98
122
See Notes on Tables on page 21.
Phase
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
Recommended
Upstream
Protection, A
20
25
35
50
70
100
125
175
75°C Wire
Current A
Total
40
40
40
50
85
100
130
150
Copper
Wire
(1) #8
(1) #8
(1) #8
(1) #8
(1) #4
(1) #3
(1) #1
(1) 1/0
Aluminum
Wire
(1) #8
(1) #8
(1) #8
(1) #6
(1) #3
(1) #1
(1) 2/0
(1) 3/0
Bolt Size
M10
M10
M10
M10
M10
M10
M10
M10
Table 12 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, bypass input, with
600V:208V transformer
Liebert
eXM TXC
Rating kVA
Maximum
System Input
Current, A
30
40
60
80
10
15
20
10
15
20
30
40
60
79
100 99
See Notes on Tables on page 21.
Phase
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
Recommended
Upstream
Protection, A
15
20
30
40
60
80
100
125
75°C Wire
Current A
Total
40
40
40
50
85
150
200
205
Copper
Wire
(1) #8
(1) #8
(1) #8
(1) #8
(1) #6
(1) #3
(1) #1
(1) 1/0
Aluminum
Wire
(1) #8
(1) #8
(1) #8
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) 3/0
Bolt Size
M10
M10
M10
M10
M10
M10
M10
M10
Table 13 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, rectifier input, with
208V:208V or 220V:220V transformer
Liebert
eXM TXC
Rating kVA
Maximum
Rectifier
Input
Current, A
30
40
60
80
10
15
20
36
53
71
107
141
211
281
100 352
See Notes on Tables on page 21.
Phase
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
Recommended
Upstream
Protection, A
150
200
300
400
450
45
70
90
75°C Wire
Current A
Total
65
85
100
175
230
335
460
510
Copper
Wire
Aluminum
Wire
Bolt
Size
(1) #6
(1) #4
(1) #3
(1) #4
(1) #2
(1) #1
M10
M10
M10
(1) 2/0
(1) 4/0
(1) 400 kcmil
(2) 4/0
(1) 4/0
(1) 300 kcmil
(2) 4/0
(2) 300 kcmil
M10
M10
M10
M10
(2) 250 kcmil (2) 400 kcmil M10
Liebert
®
eXM
™
TXC
™
20
Specifications
Table 14 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, bypass input, with
208V:208V or 220V:220V transformer
Liebert
eXM TXC
Rating kVA
10
15
Maximum
System Input
Current, A
29
43
20
30
40
60
58
87
116
172
80
100
229
286
Phase
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
Recommended
Upstream
Protection, A
40
60
80
110
150
225
300
400
75°C Wire
Current A
Total
65
85
100
150
230
285
350
460
Copper
Wire
(1) #6
(1) #4
Aluminum
Wire
(1) #4
(1) #2
Bolt
Size
M10
M10
(1) #3
(1) 1/0
(1) #1
(1) 3/0
M10
M10
(1) 4/0 (1) 300 kcmil M10
(1) 300 kcmil (1) 400 kcmil M10
(2) 2/0
(2) 4/0
(2) 4/0 M10
(2) 300 kcmil M10
Table 15 Liebert eXM TXC Inrush Multiplier
Liebert eXM
TXC Rating kVA
TXC
480V:208V
30
40
60
80
10
15
20
11.7
11.3
7.8
7.4
7.65
6.7
7.1
100 7.1
Note: Inrush Current = NFLA x Tabel Value
TXC
600V:208V
11.1
7.85
8.3
7.85
8.5
7.45
7.1
7.8
TXC
208V:208V
8.9
6.4
6.4
6.4
6.8
5.1
6.2
6.9
TXC
220V:220V
10.8
10.2
7.7
7.7
8.2
6.2
7.5
7.4
Notes on Tables
Notes apply to Tables 9 through 14.
1. Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Recommended overcurrent protection is based on 80% rated devices.
*The recommended overcurrent protection represents 125% of nominal full load current
(continuous) per NEC 215.
2. Maximum input current is controlled by the current limit setting.
3. Recommended AC input external overcurrent protection is based on 80% rated devices and maximum input current limit setting.
4. Recommended AC output external overcurrent protection is based on 80% rated devices and full rated output current.
5. Input power factor of 0.99 is used for the calculations.
21 Liebert
®
eXM
™
TXC
™
Liebert
®
eXM
™
TXC
™
22
Specifications
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2014 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
SL-25655_REV0_05-15
Emerson Network Power
Liebert www.emerson.com
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257