10 - INSTALLATION - Vent and combustion air

10.10.2 - Determine location

Locate the vent termination using the following guidelines:

1. The total length of piping for vent must not exceed the limits given in the

Section 10.4.

2. You must consider the surroundings when terminating the vent: a. Position the vent termination where vapors will not damage nearby shrubs, plants or air conditioning equipment or be objectionable.

b. The flue products will form a noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views.

c. Prevailing winds could cause freezing of condensate and water/ ice buildup where flue products impinge on building surfaces or plants.

d. Avoid possibility of accidental contact of flue products with people or animals.

e. Do not locate the terminations where wind eddies could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.

f. Do not terminate above any door or window. Condensate can freeze, causing ice formations.

g. Locate or guard vent to prevent condensate damage to exterior finishes.

4. The vent piping must terminate in an elbow pointed outward as shown in

WARNING!!!

WARNING!!!

Do not exceed the maximum lengths of the outside vent piping shown in Figures 10-12 or 10-13.

Excessive length exposed to the outside could cause freezing of condensate in the vent pipe, resulting in potential boiler shutdown.

5. Maintain clearances as shown in

Figure 10-11

(get references to

“Mechanical draft vent terminal”

only). Also maintain the following: a. Vent must terminate:

• At least 6 feet from adjacent walls.

• No closer than 12 inches below roof overhang.

• At least 7 feet above any public walkway.

• At least 3 feet above any forced air intake within 10 feet.

• No closer than 4 feet below or horizontally from any door or window or any other gravity air inlet.

b. Do not terminate closer than 4 feet horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet horizontally.

Item unique to CANADA: vent system shall terminate at least 6 ft from electrical and gas meters.

6. Locate termination so it is not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.

CAUTION!!!

Increase the grade clearances of the snow line quote

Figure 10-16 Vent position of a Direct vent boiler and of a Mechanical draft boiler (not sealed)

48