Orion SS 1016 and newer VCM Controller Technical Guide
광고
광고
www.orioncontrols.com
VCM - Component & System
Wiring - Technical Guide
Use For VCM Controller Code: SS1016 & Newer Wiring
For VAV/CAV & MUA II Wiring Information, See Component &
System Wiring Technical Guide - Form: OR-WIRE-TGD-01B
Table Of Contents
System Configurations Installation & Commissioning ................................................................................... 5
Stand Alone System Wiring .................................................................................................................................................................................. 6
Stand Alone - Computer Connection With Remote Link ....................................................................................................................................... 7
Stand Alone - Computer Connection With IP-Link ................................................................................................................................................ 8
Interconnected System Wiring ............................................................................................................................................................................. 9
Interconnected - Computer Connection With Remote Link ................................................................................................................................ 10
Interconnected - Computer Connection With IP-Link .......................................................................................................................................... 11
Networked Single Loop System With CommLink Only ...................................................................................................................................... 12
Networked Single Loop System With MiniLink PD Only ..................................................................................................................................... 13
Networked Single Loop System With CommLink & MiniLink PD ........................................................................................................................ 14
Networked Single Loop - Computer Connection With Remote Link .................................................................................................................. 15
Networked Single Loop - Computer Connection With IP-Link ........................................................................................................................... 16
Networked Multiple Loop System Wiring ........................................................................................................................................................... 17
Networked Multiple Loop - Computer Connection With Remote Link ................................................................................................................ 18
Networked Multiple Loop - Computer Connection With IP-Link ......................................................................................................................... 19
Systems Overview ............................................................................................................................................................................................ 20
General Information ........................................................................................................................................................................................ 20
System Installation .............................................................................................................................................................................................. 21
Wiring Considerations .................................................................................................................................................................................... 21
Installation Procedures ................................................................................................................................................................................... 22
System Commissioning ...................................................................................................................................................................................... 27
Transformer & Wire Sizing - Devices Without Modular Connectors ................................................................................................................ 28
Transformer Sizing & Cabling - Devices With Modular Connectors ................................................................................................................. 29
VCM Controller Wiring .................................................................................................................................... 31
VCM Controller Wiring ........................................................................................................................................................................................ 32
VCM Controller Addressing ................................................................................................................................................................................ 33
Outdoor Air, Return Air & Supply Air Temperature Sensor Wiring .................................................................................................................... 34
Economizer Actuator Wiring ............................................................................................................................................................................... 35
Space Temperature Sensor & Remote Supply Air Reset Wiring ....................................................................................................................... 36
Supply Fan VFD & Bypass Damper Actuator Wiring ........................................................................................................................................ 37
Suction Pressure Transducer Without Digital Compressor - Wiring ................................................................................................................. 38
Suction Pressure Transducer With Digital Compressor - Wiring ...................................................................................................................... 39
Expansion Board Jumper Settings ..................................................................................................................................................................... 40
Binary Input Board Wiring .................................................................................................................................................................................. 41
Outdoor Humidity Sensor Wiring ........................................................................................................................................................................ 42
Return Air Humidity Sensor Wiring ..................................................................................................................................................................... 43
Indoor Air Humidity Sensor Wiring ..................................................................................................................................................................... 44
Building Pressure Sensor, Actuator & VFD Wiring ............................................................................................................................................ 45
CO2 Sensor Wiring ............................................................................................................................................................................................ 46
4 Relay Output Expansion Board Wiring ........................................................................................................................................................... 47
Modulating Heating & Cooling Wiring .................................................................................................................................................................. 48
Return Air Bypass Wiring ................................................................................................................................................................................... 49
VAV/Zone Controller Diagrams ....................................................................................................................... 51
VAV/Zone Controller Board Wiring .................................................................................................................................................................... 52
Slaved Zone Wiring ............................................................................................................................................................................................ 53
3 Relay Output Expansion Board Wiring ........................................................................................................................................................... 54
3 Relay Output Expansion Board Wiring (Cont’d) ............................................................................................................................................. 55
3 Relay Output Expansion Board Wiring (Cont’d) ............................................................................................................................................. 56
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected]
Visit our web site at www.orioncontrols.com
Form: OR-VCMWIRE-TGD-01B Copyright 2006 WattMaster Controls, Inc.
AAON
® is a registered trademark of AAON, Inc., Tulsa, OK.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
This document is subject to change without notice.
Table Of Contents
Communication Devices Diagrams ................................................................................................................ 57
System Manager Modular Cable Connections ................................................................................................................................................... 58
System Manager Modular Cable Pigtail - Wiring Schematic .............................................................................................................................. 59
System Manager Modular Cable Pigtail - Wiring Detail ...................................................................................................................................... 60
Modular Service Tool Connections .................................................................................................................................................................... 61
CommLink II Wiring & Cabling Connections ........................................................................................................................................................ 62
MiniLink Polling Device Wiring Using Modular Connectors ................................................................................................................................ 63
MiniLink Polling Device Wiring Using Wire Terminals ......................................................................................................................................... 64
Power/Comm Board Wiring - When Used For Local Loop Devices ................................................................................................................. 65
Power/Comm Board Wiring - When Used For Network Loop Devices ............................................................................................................ 66
RS-232 Serial Port To USB Port Converter ........................................................................................................................................................ 67
Add-On Devices Diagrams ............................................................................................................................. 69
Lighting Panel Wiring For Standard Lighting Contactors ................................................................................................................................... 70
Lighting Panel Wiring For GE® Latching Relay Lighting Contactors ................................................................................................................. 71
GPC-17 Controller Wiring ................................................................................................................................................................................... 72
GPC Plus Wiring .................................................................................................................................................................................................. 73
GPC Plus Controller - Address Switch Setting .................................................................................................................................................. 74
GBD Controller - CO2 Apllications Wiring .......................................................................................................................................................... 75
GBD Controller - CO2 Applications Wiring (Cont’d) ........................................................................................................................................... 76
GBD Controller - Space Temp. Sensor Averaging Wiring .................................................................................................................................. 77
GBD Controller - Space Temp. Sensor Averaging Wiring (Cont’d) .................................................................................................................... 78
GBD Controller Adress Switch Setting .............................................................................................................................................................. 79
Miscellaneous Diagrams & Technical Information ....................................................................................... 81
Modular Room Sensor Wiring ............................................................................................................................................................................ 82
Over Voltage Board Wiring ................................................................................................................................................................................ 83
MODGAS II Controller Wiring When Used With The VCM Controller ................................................................................................................. 84
MODGAS II Controller Wiring With HVAC Unit Controls By Others ................................................................................................................... 85
MHGRV II Controller Wiring When Used With VCM Controller ........................................................................................................................... 86
MHGRV II Controller Wiring With HVAC Unit Controls By Others ...................................................................................................................... 87
Supply Air Sensor Location & Wiring ................................................................................................................................................................. 88
Supply Air Sensor Location & Wiring (Cont’d) ................................................................................................................................................... 89
Supply Air Sensor Location & Wiring (Cont’d) ................................................................................................................................................... 90
Chip Locations .................................................................................................................................................................................................... 91
Chip Locations (Cont’d) ...................................................................................................................................................................................... 92
Chip Installation Procedures ............................................................................................................................................................................... 93
Temperature & Humidity Sensor Voltage-Resistance Tables ............................................................................................................................ 94
Pressure Sensors Voltage-Resistance Tables ................................................................................................................................................. 95
Component & System Wiring 3
4 Component & System Wiring
System Configurations
Installation &
Commissioning
Component & System Wiring 5
Stand Alone System Wiring
Typical Stand Alone System
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
TB1
T G R
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
RED (24 VAC)
CLEAR (GND)
GREEN (GND)
24 VAC
(6 VA)
1
4
7
DEC
2
5
8
0
UP
3
6
9
PREV
ESC
DOWN
CLEAR
ENTER
NEXT
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
Modular System Manager
Line Voltage
Note: Either A Modular
System Manager, A
Modular Service Tool
Or A PC With Prism
Software Installed Can
Be Used To Program
And Configure The
Orion System.
Mode
Selection
STATUS PREV
SETPOINTS
UP
ESC
DOWN
CLEAR
NEXT
SCHEDULES
OVERRIDES
ENTER
ALARMS
CONFIGURATION
BALANCE - TEST
ON
1
4
7
DEC
2
5
8
0
3
6
9
Modular Service Tool
Connect To Optional
CommLink (When Used)
For Optional CommLink, Remote Link
And Computer Connections, See Page 2
Of This Drawing.
HVAC Unit Controller
(1 MEG)
24 VAC
(8 VA)
Line Voltage
6
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
JOB NAME
FILENAME
O-System-Stand-Alone.CDR
DATE:
PAGE
1 of 3
03/13/06
DRAWN BY:
B. Crews
DESCRIPTION:
Stand Alone System
Wiring & Connection Diagram
Component & System Wiring
Stand Alone - Computer Connection With Remote Link
Optional Computer Connection Diagram
Using Remote Link For Remote Connection
Note: CommLink Is Only Required If
Alarm Callout, Remote Computer
Connection Or Direct Computer
Connection To System Is Desired.
Remote Link Is Only Required If
Alarm Callout Or Remote Computer
Connection Is Required.
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
T G R
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
CommLink
Front View of CommLink
Note: Set CommLink
Internal Switch To “Single”
C L II
STATUS
C O N T R O L S
Back View of CommLink
SERIAL #
REMOTE LINK
(DTE)
COMPUTER
(DCE)
T G R
110 VAC To
24 VAC
Power Pack
9 Pin
Female
End
Dedicated Telephone
Outlet
(By Others)
TELCO
LINE
Telephone
Cable
Assembly
SERIAL #
TELCO
LINE
9 Pin
Female
Connector
Connect To Computer
8 Conductor
Modular Cable
Assembly
Serial Port
Molded
Cable Assembly
SERIAL DATA
25 Pin
Male End
POWER
9VDC @
500mA
Personal Computer
(By Others)
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
Back View of Remote Link
R emote
L ink
C O N T R O L S
Front View of Remote Link
Remote Link
(Optional)
110 VAC To
9 VDC
Power Pack
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
Component & System Wiring
JOB NAME
FILENAME
O-System-Stand-Alone.CDR
DATE:
PAGE
2 of 3
03/13/06
DRAWN BY:
B. Crews
DESCRIPTION:
Stand Alone System
Wiring & Connection Diagram
7
Stand Alone - Computer Connection With IP-Link
Optional Computer Connection Diagram
Using IP-Link For Remote Connection
Note: CommLink Is Only Required If Alarm Callout,
Remote Computer Connection Or Direct Computer
Connection To System Is Desired. IP-Link Is Only
Required If E-mail Alarm Notification Or Remote
Computer Connection Is Required.
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
T G R
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Note:
1.Set CommLink Internal Switch To “Single”.
2. Replace CommLink EPROM With IP-Link
EPROM Supplied With IP-Link Kit
CommLink
Front View of CommLink
C L II
STATUS
C O N T R O L S
Back View of CommLink
SERIAL #
REMOTE LINK
(DTE)
COMPUTER
(DCE)
T G R
110 VAC To
24 VAC
Power Pack
Connect Ethernet RJ45
Cable Assembly
(By Others)
To 10 BaseT Connection
On Ethernet Router
Or Modem
(By Others)
9 Pin
Female
End
Connect Ethernet
RJ45 Cable
Assembly
To 10BaseT Port
On IP-Link
10BaseT
9 Pin
Female
Connector
Connect To Computer
8 Conductor
Modular Cable
Assembly
Serial Port
Molded
Cable Assembly
Supplied With
IP-Link Kit
9 Pin Male End
Connect To Serial
Port On IP-Link
Serial
9VDC
Mode
Back View of IP-Link
Personal Computer
(By Others)
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
A
C
T
LN
K
R
C
V
S
E
R
Connect ne
PWR
110 VAC To
9 VDC
Power Pack Front View of IP- Link
IP-Link
(Optional)
8
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
JOB NAME
FILENAME
O-System-Stand-Alone.CDR
DATE:
PAGE
3 of 3
03/13/06
DRAWN BY:
B. Crews
DESCRIPTION:
Stand Alone System
Wiring & Connection Diagram
Component & System Wiring
Interconnected System Wiring
Typical Interconnected System
Note: Either A Modular
System Manager, A
Modular Service Tool
Or A PC With Prism
Software Installed Can
Be Used To Program
And Configure The
Orion System.
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
TB1
1
4
7
DEC
2
5
8
0
UP
3
6
9
PREV
ESC
DOWN
CLEAR
ENTER
NEXT
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
Modular System Manager
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
RED (24 VAC)
CLEAR (GND)
GREEN (GND)
24 VAC
(6 VA)
Line Voltage
T G R
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Mode
Selection
STATUS PREV
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
1
4
7
DEC
UP
ESC DOWN CLEAR
ENTER
2
5
8
0
3
6
9
NEXT
Modular Service Tool
Connect To Optional
CommLink (When Used)
For Optional CommLink, Remote Link
And Computer Connections, See Page 2
Of This Drawing.
HVAC Unit Controller
(1 MEG)
24 VAC
(8 VA)
Line Voltage
HVAC Unit Controller
(1 MEG)
24 VAC
(8 VA)
Line Voltage
HVAC Unit Controller
(1 MEG)
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
JOB NAME
24 VAC
(8 VA)
Line Voltage
FILENAME
O-System-Interconnected.CDR
DATE:
PAGE
1 of 3
06/20/03
DRAWN BY:
B. Crews
DESCRIPTION:
Interconnected System
Wiring & Connection Diagram
Component & System Wiring 9
Interconnected - Computer Connection With Remote Link
Optional Computer Connection Diagram
Using Remote Link For Remote Connection
T G R
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Note: CommLink Is Only Required If
Alarm Callout, Remote Computer
Connection Or Direct Computer
Connection To System Is Desired.
Remote Link Is Only Required If
Alarm Callout Or Remote Computer
Connection Is Required.
CommLink
Front View of CommLink
Note: Set CommLink
Internal Switch To “Single”
C L II
STATUS
C O N T R O L S
Back View of CommLink
SERIAL #
REMOTE LINK
(DTE)
COMPUTER
(DCE)
T G R
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
110 VAC To
24 VAC
Power Pack
9 Pin
Female
End
Dedicated Telephone
Outlet
(By Others)
TELCO
LINE
Telephone
Cable
Assembly
SERIAL #
TELCO
LINE
9 Pin
Female
Connector
Connect To Computer
8 Conductor
Modular Cable
Assembly
Serial Port
Molded
Cable Assembly
SERIAL DATA
25 Pin
Male End
POWER
9VDC @
500mA
Personal Computer
(By Others)
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
Back View of Remote Link
R emote
L ink
C O N T R O L S
Front View of Remote Link
Remote Link
(Optional)
110 VAC To
9 VDC
Power Pack
10
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
JOB NAME
FILENAME
O-System-Interconnected.CDR
DATE:
PAGE
2 of 3
06/20/03
DRAWN BY:
B. Crews
DESCRIPTION:
Interconnected System
Wiring & Connection Diagram
Component & System Wiring
Interconnected - Computer Connection With IP-Link
Optional Computer Connection Diagram
Using IP-Link For Remote Connection
Note: CommLink Is Only Required If Alarm Callout,
Remote Computer Connection Or Direct Computer
Connection To System Is Desired. IP-Link Is Only
Required If E-mail Alarm Notification Or Remote
Computer Connection Is Required.
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
T G R
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Note:
1.Set CommLink Internal Switch To “Single”.
2. Replace CommLink EPROM With IP-Link
EPROM Supplied With IP-Link Kit
CommLink
Front View of CommLink
C L II
STATUS
C O N T R O L S
Back View of CommLink
SERIAL #
REMOTE LINK
(DTE)
COMPUTER
(DCE)
T G R
110 VAC To
24 VAC
Power Pack
Connect Ethernet RJ45
Cable Assembly
(By Others)
To 10 BaseT Connection
On Ethernet Router
Or Modem
(By Others)
9 Pin
Female
End
Connect Ethernet
RJ45 Cable
Assembly
To 10BaseT Port
On IP-Link
10BaseT
9 Pin
Female
Connector
Connect To Computer
8 Conductor
Modular Cable
Assembly
Serial Port
Molded
Cable Assembly
Supplied With
IP-Link Kit
9 Pin Male End
Connect To Serial
Port On IP-Link
Serial
9VDC
Mode
Back View of IP-Link
Personal Computer
(By Others)
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
A
C
T
LN
K
R
C
V
S
E
R
Connect ne
PWR
110 VAC To
9 VDC
Power Pack Front View of IP- Link
IP-Link
(Optional)
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
Component & System Wiring
JOB NAME
FILENAME
O-System-Interconnected.CDR
DATE:
PAGE
3 of 3
06/20/03
DRAWN BY:
B. Crews
DESCRIPTION:
Interconnected System
Wiring & Connection Diagram
11
Networked Single Loop System With CommLink Only
485LOOP
12
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
Component & System Wiring
Networked Single Loop System With MiniLink PD Only
485LOOP
P5
TB1
C1
T
SHLD
R POWER & COMM
DIST. BOARD
YS101856
REV. 0
P2
TB2
24
VAC
LD1
POWER
R1
F1
P4
P3
P1
TB1
C1
T
SHLD
R
POWER & COMM
DIST. BOARD
YS101856
REV. 0
P2
TB2
24
VAC
LD1
POWER
R1
F1
P5
P4
P3
P1
VREF
X1
15
P3
32
16
P5
ADD
LD
T
SH
R
LD
T
SH
R
TB4
TB3
AIN1
AIN2
+5V
TB2
C
D GN
24VA
TB1
Component & System Wiring 13
Networked Single Loop System With CommLink & MiniLink PD
14
485LOOP
TB1
C1
T
SHLD
R
POWER & COMM
DIST. BOARD
YS101856
REV. 0
P2
TB2
24
VAC
LD1
POWER
R1
F1
P5
P4
P3
P1
TB1
C1
T
SHLD
R
POWER & COMM
DIST. BOARD
YS101856
REV. 0
P2
TB2
24
VAC
LD1
POWER
R1
F1
P5
P4
P3
P1
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
X1
V1
15
32
16
14
P3
D
P5
AD
R
SHLD
T
LD
T
SH
R
TB4
TB3
+5V
AIN1
AIN2
TB2
C
D GN
24VA
TB1
Component & System Wiring
Networked Single Loop - Computer Connection With Remote Link
485LOOP
Component & System Wiring
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
DET
SIG
RDY
REC
SND
PWR
15
Networked Single Loop - Computer Connection With IP-Link
16
485LOOP
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
Component & System Wiring
Networked Multiple Loop System Wiring
485LOOP
P5
TB1
C1
T
SHLD
R POWER & COMM
DIST. BOARD
YS101856
REV. 0
P2
TB2
24
VAC
LD1
POWER
R1
F1
P4
P3
P1
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
Component & System Wiring
TB1
C1
T
SHLD
R POWER & COMM
DIST. BOARD
YS101856
REV. 0
P2
TB2
24
VAC
LD1
POWER
R1
F1
P5
P4
P3
P1
X1
C3
VREF
CX2
R4
D1
CX2
32
16
P3 P5
ADD
U15
CX15
AIN1
AIN2
+5V
TB2
R27
R26
R25
V1 R31
24VAC
GND
TB1
T
SHLD
R
TB4
TB3
R
T
SHLD
CX1
R3
X1
D oLoop
VREF
CX2
R4
iniLinkP
CX14
U15
P3
32
16
P5
ADD
T
SHLD
R
TB4
TB3
R
SHLD
T
R27
R26
R25
V1 R31
AIN1
AIN2
+5V
TB2
24VAC
GND
TB1
ConnectT
3M
17
Networked Multiple Loop - Computer Connection With Remote Link
18
485LOOP
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
REC
SND
PWR
DET
SIG
RDY
Component & System Wiring
Networked Multiple Loop - Computer Connection With IP-Link
Component & System Wiring
485LOOP
COMP
LOOP
RLINK
GND
24V
POWER
485LOOP
19
Systems Overview
General Information
The Orion system components can be configured into several types of systems. It is a good idea to become familiar with the different types of systems and their architecture by reading the information in this section and looking at the configuration diagrams in the System Configurations Installation & Commissioning section of this manual. The information below is designed to help you understand how the system components integrate with each other and the available configuration options.
System Types
Four different system configurations are available depending on the type and number of controllers that you have on your system.
Networked Single Loop
The Networked Single Loop system, as its name implies, consists of a single communications loop. This loop utilizes a network device to share information that is broadcast from one controller to all controllers on the loop. The system can consist of the following devices.
1.
A series of VCM Controllers that utilizes a network device to share information that is broadcast from one controller to all controllers on the loop.
2.
A single VCM controller and a series of VAV/Zone controllers. A network device is used to share information which is broadcast back and forth between all controllers on the loop.
1.
Stand Alone
(See Pages 6 Through 8 For Connection Diagrams)
2.
Interconnected
(See Pages 9 Through 11 For Connection Diagrams)
3.
Networked Single Loop
(See Pages 12 Through 16 For Connection Diagrams)
4.
Networked Multiple Loop
(See Pages 17 Through 19 For Connection Diagrams)
These systems require a network device in the form of either a CommLink communications interface or a MiniLink Polling Device. Both network devices may also be used together. Programming and status monitoring are accomplished by the following methods.
1.
By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both devices.
2.
A computer interface can also be used in conjunction with the other operators interfaces listed above, or by itself. This requires a CommLink and a personal computer with the
Prism computer front end software installed.
System Type Definitions
Stand Alone
This system consists of a single VCM controller. Programming and status monitoring are accomplished by one or more of the following methods.
When using the MiniLink Polling Device alone, only the System Manager or Modular Service Tool can be used to program and monitor the system. With the addition of the CommLink, the Prism computer front end software and a PC can be used to program and monitor the system in addition to the Modular Service Tool or Modular System Manager.
1.
By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both devices.
2.
A computer interface can also be used in conjunction with the other operators interfaces listed above, or by itself. This requires a CommLink and a personal computer with the
Prism computer front end software installed.
Interconnected
This system consists of a group of VCM Controllers interconnected with communication cable to allow programming from one central location. Broadcasting between controllers is not available. Programming and status monitoring are accomplished by one or more of the following methods.
Networked Multiple Loop
This Networked Multiple Loop System consists of two or more loops, each being called ‘Local Loops’, with one ‘Network Loop’ that ties the
“Local Loops” together. Each of these loops can consist of one of the following groups of controllers.
1.
A series of VCM controllers.
2.
A single VCM controller and a series of VAV/Zone controllers.
To form the Networked Multiple Loop System the following network devices are required.
1.
By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both devices.
2.
A computer interface can also be used in conjunction with the other operators interfaces listed above, or by itself. This requires a CommLink and a personal computer with the
Prism computer front end software installed.
1.
A MiniLink Polling Device is required per loop (Local
Loop). This allows the controllers to share information that is broadcast from one controller to all controllers on that local loop.
2.
One CommLink is required for the entire system. It resides on the Network Loop and allows for communications between all the local loops and provides for global broadcasts to all controllers on the entire system.
20 Component & System Wiring
Programming and status monitoring are accomplished by one or more of the following methods.
1.
By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both devices. The System Manager or Modular Service Tool connect to any “Local Loop” on the system.
2.
A computer interface can also be used in conjunction with the other operators interfaces listed above, or by itself. This requires a personal computer with the Prism computer front end software installed.
outside air humidity to all local loops on the entire networked system.
It may also be used to broadcast space temperature from a GPC Plus or
GPC-17 controller to any controllers on the local loop that do not contain their own space temperature sensor.
On a Networked Single Loop VAV/Zone system, the CommLink can be used to broadcast information such as, internal schedule, supply air temperature, fan and heat status, unoccupied calls for heating and cooling and forced modes of operation to and from the VAV/Zone controllers.
Network Communications Devices
MiniLink Polling Device
The MiniLink Polling device is used in the following applications.
1.
This device is required on all Zoning applications. It is optional on single loop VAV systems.
2.
This device is required on each local loop of all Networked
Multiple Loop systems
System Installation
Wiring Considerations
Before beginning installation, please study the wiring diagrams for the controllers you are using with your particular application. These diagrams appear in this Component & System Wiring Technical Guide and can also be found in the technical guide supplied with your specific controllers. Wire and transformer sizing instructions and examples are located on page 28 through 29 of this manual.
This device is responsible for local loop broadcasts only. It always resides on the local loop.
For a Networked Single Loop VCM system, this device can be used for tenant logging and alarm reporting to a Modular System Manager. It can be used to broadcast information like outside air temperature or outside air humidity to all devices on the local loop. It can also be used to broadcast space temperature from a GPC Plus or GPC-17 controller to any controllers on this loop that do not have their own space temperature sensor.
Most of the Orion controllers are equipped with modular connections, and in some cases are equipped with both modular and wiring terminal blocks. We recommend (when possible) using modular cables instead of hard wiring to wiring terminal blocks, to save installation time and eliminate wiring errors. In some cases, however, hard wiring is unavoidable. The table below lists the various Orion devices/controllers and their available termination type(s) for communications and power wiring.
For a Networked Single Loop VAV system, the MiniLink Polling Device can be used for tenant logging and alarm reporting to a Modular
System Manager. It must be used to broadcast information such as, internal schedule, supply air temperature, fan and heat status, unoccupied calls for heating and cooling from the VAV/Zone controllers, and forced modes of operation.
For a Networked Single Loop Zoning system, this device must be used for zone voting, because it calculates the heating and cooling totals on the loop and broadcasts cooling, venting, and heating modes to the VAV controller. It can also be used for tenant logging and alarm reporting to the Modular System Manager.
CommLink
The CommLink device is used in the following applications.
1.
A CommLink is required on all Networked Multiple Loop
Systems
2.
A CommLink is optional on all Networked Single Loop
Systems
3.
A CommLink is required on any system when a computer interface is desired
The CommLink is responsible for local loop broadcasts on a Networked
Single Loop system, and on this type of system, the on board jumper must be set to “Single”. This device is responsible for network broadcasts on Networked Multiple Loop systems. On this type of system, the on board jumper must be set to “Multi”.
For a Networked Single Loop VCM system, this device can be used for tenant logging and alarm reporting to a Modular System Manager. It can also be used to broadcast information like outside air temperature or
Component & System Wiring
Communications And Power Wiring
Terminations For Orion Products
Orion
Controller Or
Device
Available Power
And Communications
Connections
Modular
Connectors
Only
Wire
Terminals
Only
Both
Modular
Connectors
And Wire
Terminals
VAV/Zone
Power/Comm Board
MiniLink PD
CommLink II
*System Manager
GPC Plus
9
9
9
9
9
9
Lighting Controller
9
* The System Manager is supplied with a pigtail connector that has a modular plug on one end and stripped wires on the other end. The pigtail is used to allow wiring connection to the HVAC unit controller wire terminals and to a
24 VAC power transformer on systems that do not use Power/Comm boards.
21
System Installation
Power/Comm Board Requirements
Standard Connection Configurations and Use
Power/Comm boards are typically used on Networked, Single and
Multiple Loop systems to transfer 24 VAC power and “Local Loop” communications to VAV/Zone controllers, System Managers or other
Power/Comm boards.
The Power/Comm board must always be powered by its own dedicated 24 VAC transformer connected to it’s 2-wire, 24VAC input terminals (TB1).
Local Loop communications are transferred to the Power/Comm Board via a modular cable connected to its “Comm In” modular connector input terminal (P2). This modular cable connection can originate from the “Local Loop” modular connector of the MiniLink PD for this loop, another Power/Comm board output on the same loop or a VAV/Zone controller or System Manager output on the same loop. If desired a
Power/Comm board can be connected to the “Local Loop” by hard wiring a 2-wire shielded cable connected between it’s 3-wire communications input terminal (TB1) and a VCM controller, a Power/Comm board or the MiniLink PD “Local Loop”, 3-wire communications terminal.
For detailed wiring diagrams, see the Power/Comm board wiring diagrams in the “Communication Devices Diagrams” section of this manual.
For Power/Comm board transformer sizing see the last 2 pages of the
“Systems Configurations Installation & Commissioning” section of this manual.
Alternative Connection Configuration and Use
If desired, the Power/Comm board can also be used to transfer both 24
VAC power and “Network Loop” communications to multiple MiniLink
PDs. Connection between the MiniLink PD(s) and Power/Comm board(s) is accomplished by using modular cables between the Power/
Comm boards modular output connectors and the MiniLink PD(s) “Network Loop” modular input connectors. When a Power/Comm board is used to connect power and communications to MiniLink PDs in this manner, that particular Power/Comm board cannot also be used to share communications and/or power with VAV/Zone controllers or System
Manager(s).
Warning: Do not ground the 24 VAC transformer that is to be used with the Power/Comm board. Grounding of the transformer will damage the Power/Comm board and all boards connected to it. A separate transformer must be used for each Power/Comm board. No exceptions. Do not connect any other devices to the transformer used for the Power/Comm board!
For detailed wiring diagrams, see the Power/Comm board wiring diagrams in the “Communication Devices Diagrams” section of this manual.
MiniLink Polling Device (MiniLink PD)
Standard Connection Configurations Use
The MiniLink PD is used on Networked Single and Multiple Loop systems to provide two way communications between all devices on it’s “Local Loop” and to all the other “Network Loop” devices on the entire system. The MiniLink PD is equipped with both modular connectors and hard wiring terminal blocks for connection of 24 VAC power,
“Local Loop” and “Network Loop” communications.
Each MiniLink PD is normally hard wired to a 24 VAC power source connected to its 24 VAC input terminal (TB1). “Network Loop” communications are transferred between multiple MiniLink PDs by modular cables connected to their “Network Loop” modular connectors (P3 and P5). A CommLink must be connected to one of the MiniLink PDs on the system by using a 2-wire shielded cable connected between its 3wire “Network Loop” communications terminal block (TB4) and to the
CommLink’s “485 Loop” terminals block. Transfer of “Local Loop” communication from the MiniLink PD to a Power/Comm board is made by using a modular cable connected between the MiniLink PD “Local
Loop” modular connector (P4) and the Power/Comm board modular
“Comm In” connector (P2). If desired as an alternative, transfer of
“Local Loop” communication from the MiniLink PD to a Power/Comm board can be made by hard wiring a 2-wire shielded cable connected between the MiniLink PD’s 3-wire communications terminal (TB1) and the 3-wire communications input (TB1) on the Power/Comm Board.
Installation Procedures
The installation procedures that follow are based on recommended methods of wiring connection and controller installation. Installation procedures vary depending on the type of system you are installing. The system you are installing could be a “Stand Alone”, “Interconnected”, “Networked Single Loop” or “Networked Multiple Loop” system. The Networked System also has installation variations based on the type of components you are installing for that system. The following information explains the procedures for all of these systems. Please find the system and components that closely match your system and follow the outlined procedures.
Stand Alone Systems
See the “Stand Alone System Wiring”on pages 6 through 8 of this manual for detailed wiring diagrams. Also see pages 28 and 29 for wire and transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface devices.
1.
Install a 24 VAC, 8 VA minimum, transformer for the
VCM controller and wire from transformer to controller using 18 gauge minimum, 2 wire cable for power.
Observe polarity on power wiring.
2.
The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector.
For Power/Comm board transformer sizing see the last 2 pages of the
“Systems Configurations Installation & Commissioning” section of this manual.
22 Component & System Wiring
3.
The Modular System Manager comes supplied with a 12 foot modular cable with a modular connector on one end and stripped wires on the other. Run 18 gauge, 2 conductor shielded cable for communications from the controller’s 3 wire communications terminal to a junction box. Run 18 gauge minimum, 2 wire, power wires from a separate 24
VAC, 6 VA minimum transformer into the junction box.
Splice the modular cable to the communications and power wire inside of the junction box by making solid connections, using wire nuts or butt splice connectors. See the wiring diagram in this section for correct wiring color coding and connection.
4.
If a CommLink is used for a computer interface, connect communications using 18 gauge, 2 conductor with shield cable. Connect from the controller’s 3 wire communications connector to the CommLink’s 3 wire communications connector. For this type of system, the
CommLink needs to have its internal jumper set to
“Single”.
5.
Use 18 gauge minimum, 2 wire cable for all 24 VAC power wiring. Be sure to maintain polarity on all boards. If a
CommLink is connected , use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
6.
Before powering up the controller, set the desired board address on the controller (usually 1).
Interconnected Systems
See the “Interconnected System Wiring”on pages 9 and 11 of this manual for detailed wiring diagrams. Also see pages 28 and 29 for wire and transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface devices.
1.
Connect all controllers in a daisy chain or star ring format using 18 gauge, 2 conductor shielded cable for communications. Install separate 24 VAC, 8 VA minimum, transformer for each controller and wire to transformers using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards.
2.
The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector.
3.
The Modular System Manager comes supplied with a 12 foot modular cable with a modular connector on one end and stripped wires on the other. If the Modular System
Manager is to be mounted in a remote location, run 18 gauge, 2 conductor shielded cable for communications from the controller’s 3 wire communications terminal to a junction box. Run 18 gauge minimum, 2 wire, power wires from a separate 24 VAC, 6 VA minimum transformer into the junction box. Splice the modular cable to the communications and power wire inside of the junction box by making solid connections, using wire nuts or butt splice connectors. See the wiring diagram in this section for correct wiring color coding and connection.
4.
If a CommLink is used to provide for connection to a computer interface, connect communications using 18 gauge, 2 conductor shielded cable. Connect from one of the controller’s 3 wire communications connectors to the
CommLink’s 3 wire communications connector. For this type of system, theCommLink needs to have its internal jumper set to “Single”.
5.
Use 18 gauge minimum, 2 wire cable for all 24 VAC power wiring. Be sure to maintain polarity on all boards. If a
CommLink is installed, use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
6.
Before powering up the controllers, set the board addresses from 1-60.
Networked Single Loop Systems
See the “Networked System - Single Loop Wiring” on pages 12 through
16 of this manual for detailed wiring. Also see pages 28 and 29 for wire and transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface devices.
Loop Containing VCM Controllers Only
1.
Connect all controllers in a daisy chain or star ring format using 18 gauge, 2 conductor shielded cable for communications. Install separate 24 VAC, 8 VA minimum, transformer for each controller and wire to transformers using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards.
2.
Connect 2 conductor shielded cable from one of the controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Local Loop”. Use 18 gauge wire for power and observe polarity on all boards.
3.
If only a CommLink II is used, connect 2 conductor shielded cable from one of the controller’s 3 wire communications connector to the CommLink’s 3 wire communications connector. If only the CommLink II is used, the CommLink’s internal jumper must be set to
“Single”. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
4.
If both the MiniLink Polling Device and the CommLink II are used, connect 2 conductor shielded cable from one of the controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Local Loop”. Connect 2 wire shielded cable from the
CommLink’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Network Loop”. When a MiniLink PD and a CommLink are used, the CommLink’s internal jumper must be set to
“Multi”. Install a separate 24 VAC, 8 VA minimum, transformer for the MiniLink PD and wire to transformer using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards.
Component & System Wiring 23
System Installation
5.
The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector.
6.
The Modular System Manager comes supplied with a 12foot modular cable with a modular connector on one end and stripped wires on the other. If the System Manager is to be mounted in remote location, run 18 gauge, 2 conductor shielded cable for communications from one of the controller’s 3 wire communications terminals to a junction box. Run 18 gauge, 2 wire, 24 VAC power wires supplied by a separate transformer into the junction box.
Splice modular cable to the communications and power wire inside of the junction box using solid connections from wire nuts or butt-splice connectors. The Modular
System Manager MUST always be connected on the
“Local Loop”, never the “Network Loop”.
Notes:
Only communications, not power, is transferred from the MiniLink Polling Device to the Power/
Comm board via the modular cable. Both power and communications are transferred from the
Power/Comm board to the VAV/Zone controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This transformer cannot be shared with any other board.
Do not ground the transformer that is connected to the Power/Comm board. The transformer should be sized for the required VA by using the information found on page 29 of this manual.
Loops Containing VCM controllers with VAV/Zone Controllers and MiniLink PD Only
1.
Connect all controllers in a daisy chain or star ring format using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM controller and wire from transformer to the VCM controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24
VAC transformer sized for the required VA load for each
Power/Comm Board on the loop and wire from each transformer to its Power/Comm board. Observe polarity on all boards.
2.
Connect 2 conductor shielded cable from the VCM controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
”Local Loop”. Use 18 gauge minimum, 2 wire cable for all power wiring and be sure to maintain polarity on all boards.
3.
Using a modular cable, connect from the MiniLink PD’s modular connector marked “Local Loop” to a
Power/Comm board’s modular input connector.
4.
Using modular cables, connect from the Power/Comm board’s modular output connectors to the VAV/Zone controllers. The VAV/Zone controllers connect together using modular cables from each VAV/Zone controller to the next controller and/or to a Power/Comm Board. A maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone controllers connected to it.
5.
The Modular System Manager can connect to any
VAV/Zone controller or directly to one of the Power/Comm board’s modular output connectors.
VCM with VAV/Zone Controllers and CommLink Only
1.
Connect all controllers in a daisy chain or star ring format using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM controller and wire from transformer to the VCM controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24
VAC, transformer sized for the required VA load for each
Power/Comm Board on the loop and wire from each transformer to its Power/Comm board. Observe polarity on all boards.
2.
Connect 2 conductor shielded cable from the VCM controller’s 3 wire communications connector to the
CommLink’s 3 wire communications connector. The
CommLink’s on-board jumper should be set to “Single”.
3.
Use 18 gauge minimum, 2 wire cable for all 24 VAC power wiring. Be sure to maintain polarity on all boards. Use the
110 VAC/24 VAC power supply furnished with the
CommLink for its power source.
4.
Using 2 conductor shielded cable, connect from the
CommLink’s 3 wire communications connector to the
Power/Comm board’s or VCM controller’s 3 wire communications input connector.
5.
Using modular cables, connect from the Power/Comm board’s modular output connectors to the VAV/Zone controllers. The VAV/Zone controllers connect together using modular cables from each VAV/Zone controller to the next controller and/or to a Power/Comm Board. A maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone controllers connected to it.
6.
The Modular System Manager can connect to any VAV/
Zone controller or directly to one of the Power/Comm board’s modular output connectors.
24 Component & System Wiring
Notes:
Both power and communications are transferred from the Power/Comm board to the VAV/Zone controllers and the Modular System Manager.
Only communications is transferred from Power/
Comm board to Power/Comm board.
Notes:
Only communications, not power, is transferred from the MiniLink Polling Device to the Power/
Comm board via the modular cable. Both power and communications are transferred from the
Power/Comm board to the VAV/Zone controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This transformer cannot be shared with any other board.
Do not ground the transformer that is connected to the Power/Comm board. The transformer should be sized for the required VA by using the information found on page 29 of this manual.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This transformer cannot be shared with any other board.
Do not ground the transformer that is connected to the Power/Comm board. The transformer should be sized for the required VA by using the information found on page 29 of this manual.
VCM with VAV/Zone Controllers MiniLink PD and CommLink
1.
Connect all controllers in a daisy chain or star ring format using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM controller and wire from transformer to the VCM controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24
VAC transformer sized for the required VA load for each
Power/Comm Board on the loop and wire from each transformer to its Power/Comm board. Observe polarity on all boards.
2.
Using 2 conductor shielded cable, connect from the
VCM controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Use 18 gauge minimum wire for power and observe polarity on all boards.
3.
Using a modular cable, connect from the MiniLink PD’s modular connector marked “Local Loop” to a
Power/Comm board’s modular input connector.
4.
Using modular cables, connect from the Power/Comm board’s modular output connectors to the VAV/Zone controllers. The VAV/Zone controllers connect together using modular cables from each VAV/Zone controller to the next controller and/or to a Power/Comm Board. A maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone controllers connected to it.
5.
The System Manager can connect to any VAV/Zone controller or directly to one of the Power/Comm board’s modular output connectors.
6.
Using 2 conductor shielded cable, connect from the
CommLink’s 3 wire communications connector to the
MiniLink’s 3 wire communications connector marked
“Network Loop”. When a MiniLink PD and a CommLink are used together, the CommLink’s internal jumper must be set to “Multi”.
Networked Multiple Loop Systems
See the “Networked System - Multiple Loop Wiring”on pages 17 through
19 of this manual for detailed wiring diagrams. Also see pages 28 and
29 for wire and transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface devices.
Local Loops containing VCM Controllers with VAV/Zone Controllers
1.
Using 18 gauge minimum, 2 wire cable for power, install a
24 VAC, 8 VA minimum, transformer for the VCM controller and wire from the transformer to the VCM controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24 VAC, transformer sized for the required VA load for each Power/Comm Board on the loop and wire from each transformer to its Power/Comm board.
Observe polarity on all boards.
2.
Using 2 conductor shielded cable, connect from the
VCM controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Use 18 gauge minimum wire for power and observe polarity on all boards.
3.
Using a modular cable, connect from the MiniLink PD’S modular connector marked “Local Loop” to the
Power/Comm board’s modular input connector.
4.
Using modular cables, connect from the Power/Comm board’s modular output connectors to the VAV/Zone controllers. The VAV/Zone controllers connect together using modular cables from each VAV/Zone controller to the next controller and/or to a Power/Comm Board. A maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone controllers connected to it.
5.
Repeat the above steps for each local loop containing
VCM Controllers with VAV/Zone Controllers.
Component & System Wiring 25
System Installation
6.
The Modular System Manager can connect to any
VAV/Zone controller on the entire system or directly to one of the Power/Comm board’s modular output connectors using modular cable. The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controllers is located near the communications connector.
7.
Using 2 conductor shielded cable, connect from the
CommLink’s 3 wire communications connector to one
MiniLink PD’s 3 wire communications connector marked
“Network Loop”. The CommLink’s internal jumper must be set to “Multi”. The CommLink only needs to be connected to one of the MiniLink PDs on the system.
8.
Using a modular cable, connect from each MiniLink
PD’s modular connector marked “Network Loop” to the next MiniLink PD’s “Network Loop” modular input connector using modular cable. Connect all the remaining
MiniLink PD’s in the same manner using a daisy chain or star ring format.
Notes:
Both power and communications are transferred from the Power/Comm board to the VAV/Zone controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This transformer cannot be shared with any other board.
Do not ground the transformer that is connected to the Power/Comm board. The transformer should be sized for the required VA by using the information found on page 29 of this manual.
Loops Containing VCM Controllers without VAV/Zone Controllers
1.
Connect all VCM controllers on the loop in a daisy chain or star ring format using 18 gauge minimum, 2 conductor shielded cable for communications.
Install a separate 24 VAC, 8 VA minimum, transformer for each controller and wire to its transformer using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards.
2.
Connect 2 conductor shielded cable from one of the controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Local Loop”. Use 18 gauge wire for power and observe polarity on all boards.
3.
Connect 2 wire shielded cable from the CommLink’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Network Loop”. The
CommLink’s internal jumper must be set to “Multi”. Use the 110 VAC/24 VAC power supply furnished with the
CommLink for its power source. Only one MiniLink PD on the system should connect to the CommLink. Install a separate 24 VAC, 8 VA minimum, transformer for each
MiniLink PD and wire to transformer using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards. Each MiniLink PD’s address switch should be set with a unique address between 1 and 60.
4.
Using a modular cable, connect from the each MiniLink
PD’s modular connector marked “Network Loop” to the next MiniLink PD’s “Network Loop” modular input connector using modular cable. Connect all the remaining
MiniLink PD’s in the same manner using a daisy chain or star ring format.
5 The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controllers is located near the communications connector.
6.
If your system has other loops that have VAV/Zone controllers, the Modular System Manager can connect to any VAV/Zone controller on the entire system or directly to one of the Power/Comm board’s modular output connectors using modular cable. If you do not have any loops with
VAV/Zone controllers, the Modular System Manager also is supplied with a 12 foot modular cable with a modular connector on one end and stripped wires on the other. If the Modular System Manager is to be mounted in remote location, run 18 gauge, 2 conductor shielded cable for communications from one controller’s 3 wire
MiniLink PD’s in the same manner using a daisy chain or star ring format.
26 Component & System Wiring
System Commissioning
The following information is a brief overview of the procedures required to commission a typical Orion System. Select the type of system that you have and follow the procedures listed for that system.
Stand Alone System
1.
Be sure that the controller is set at address 1.
2.
Apply power to the controller.
3.
Verify diagnostics LED indicator for proper operation. See technical guide for the specific controller, the location of the diagnostic LED, and controller start-up sequence.
4.
Connect an operators interface device for programming the controller.
Interconnected System
1.
Be sure that the controllers are addressed from 1 to 60.
2.
Apply power to the controllers.
3.
Verify diagnostics LED indicator for proper operation of all controllers. See technical guide for each specific controller, the location of the diagnostic LED, and each controller’s start-up sequence.
4.
Connect an interface device to one of the controllers for programming all of the controllers for operation
Networked Systems
1.
Address each MiniLink PD from 1 to 60
2.
On a loop of VCM controllers, address the controllers from 1 to 59
3.
On a VAV or Zoning system, address VAV/Zone controllers from 1 to 58. Address the VCM controller to 59
4.
On a VAV or Zoning system, apply power in the following order: a.
VCM controller b.
MiniLink Polling Device c.
CommLink d.
Power/Comm boards
5.
Verify diagnostics LED indicator for proper operation of all controllers. See technical guide for each specific controller, the location of the diagnostic LED, and each controller’s start-up sequence.
6.
If a computer is used, connect it to the CommLink to access all of the controllers on the entire system for programming.
7.
If a computer is not used, and if a Modular System Manger is not already connected on the local loop, connect a
Modular Service Tool to one of the controllers to perform programming of all controllers on the entire system.
Component & System Wiring 27
Transformer & Wire Sizing - Devices Without Modular Connectors
24VAC Power - Transformer & Wire Sizing Considerations for Devices Without Modular Connectors
Some installers like to use one large 24VAC transformer to power several devices. This is allowable as long as polarity is maintained to each device on the transformer circuit.
Warning:
If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommends using a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity.
Using separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioning transformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several devices, the following transformer and wire sizing information is presented to help the installer correctly supply 24VAC power to the devices.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.
Each GPC Plus Controller requires 8 VA @ 24VAC power. In the examples below we have a total of 8 GPC Plus Controllers.
8 GPC Plus Controllers @ 8VA each................ 8 x 8VA = 64VA.
The above calculation determines that our transformer will need to be sized for a minimum of 64VA if we are to use one transformer to power all the controllers.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a voltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire
16ga wire.................................0.00034 = voltage drop per 1’ length of wire
14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.
Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 64VA controller load =
0.0346
Volts/Ft.
WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by the number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 75 VA transformer with no more than a
2 Volt drop at the farthest controller from the transformer..
2 (Volts total allowable voltage drop)
= 57.80
feet
0.0346 (Voltage drop per 1 ft. @ 64VA load)
Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown in our examples below).
It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size, transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory that the farthest controller on the circuit is supplied with a minimum of 22 Volts.
B C
B
B C D E
A
120 / 24VAC
120 / 24VAC
A
Distance A to B cannot exceed 57.80 Ft.
A
120 / 24VAC
Distance from A to B cannot exceed 115.60 Ft.
Distance from A to C cannot exceed 115.60 Ft.
Distance from A to B cannot exceed 230.40 Ft.
Distance from A to C cannot exceed 230.40
Ft.
Distance from A to D cannot exceed 230.40
Ft.
Distance from A to E cannot exceed 230.40
Ft.
JOB NAME
Component Power Requirements
VCM Controller.........................8VA
GPC Plus Controller .................8VA
GPC-17 Controller ....................10VA
Lighting Panel Controller ..........10VA
GBD Controller ........................ 6VA
MiniLink Polling Device............. 6VA
28
FILENAME
O-VCMWRSIZ1A.CDR
DATE:
PAGE
1 of 2
03/09/06
DRAWN BY:
B. CREWS
DESCRIPTION:
Orion VCM System
Wire & Transformer Sizing
Component & System Wiring
Transformer Sizing & Cabling - Devices With Modular Connectors
24VAC Power - Transformer & Cabling Considerations for Devices With Modular Connectors
Modular devices include the VAV/Zone Controller, Modular
System Manager & MiniLink Polling Device. When sizing transformers for the devices it is important to design your layout so that the fewest number of Power/Comm distribution boards and the least number of transformers can be used.
The polarity problem discussed in regards to other devices that do not have modular connections is not an issue with the modular devices as they cannot be connected with reversed polarity because of the modular board connectors and cable.
Also the prefabricated cable is always 16 gauge. Wire size selection is therefore not an issue with the modular devices.
However, the same minimum voltage rules apply to modular devices as with other non-modular devices. In order to simplify wiring design and layout with modular devices the following rules apply:
Power/Comm Board maximum transformer size = 100VA.
This is due to the board circuitry and fusing. Each modular device is to be calculated at 6VA. This allows for a maximum of 16 devices per Power/Commboard. If more than 16 devices are required, multiple Power/Comm boards must be used.
No more than 6 modular devices allowed per branch circuit.
(The Power/Comm board has a total of 4 branch circuits)
The longest total run per branch circuit is 240 Ft. This is due to voltage drop on the prefabricated cable.
Below are some examples of transformer sizing and branch circuit design.
6 Devices Maximum Per Branch Circuit
16 Devices At 6 VA = 96 VA
Use 100 VA Transformer
13 Devices At 6 VA = 78 VA
Use 80 VA Transformer
Power/Comm
Board
120 / 24VAC
100 VA
Transformer
Minimum
See Warning
Note Below
A
Power/Comm
Board
120 / 24VAC
80 VA
Transformer
Minimum
See Warning
Note Below
A
12 Devices At 6 VA = 72 VA
Use 75 VA Transformer
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
6 Devices Maximum Per Branch Circuit
6 Devices At 6 VA = 36 VA
Use 40 VA Transformer
Power/Comm
Board
120 / 24VAC
75 VA
Transformer
Minimum
See Warning
Note Below
A
Power/Comm
Board
120 / 24VAC
40 VA
Transformer
Minimum
See Warning
Note Below
A
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
JOB NAME
WARNING!
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED
WITH THE POWER/COMM BOARDS. GROUNDING OF THE
TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND
ALL BOARDS CONNECTED TO IT. A SEPARATE TRANSFORMER
MUST BE USED FOR EACH POWER/COMMBOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE
TRANSFORMER USED FOR THE POWER/COMM BOARD!
FILENAME
O-VCMWRSIZ1A.CDR
DATE:
PAGE
03/09/06
DRAWN BY:
B. CREWS
DESCRIPTION:
Orion VCM System
Wire & Transformer Sizing
Component & System Wiring 29
30 Component & System Wiring
VCM Controller Wiring
Component & System Wiring 31
VCM Controller Wiring
32
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller And/Or
MiniLink PD On Local Loop.
OE331-21-VCM
VCM Controller Board
Local Loop
RS-485
9600 Baud
1
RN1
CX1
U1
TB1
COMM
T
SHLD
R
CX5
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
LD6
COMM
LD7
PWR
1
U5
RS-485
COMM
HH
LD8
LED1
C1
R1
LD9
LED2
P1
+VREF
5.11V
TEST POINT
U7
RV1
VREF ADJ
EWDOG
R28
See Individual
Component Wiring
Diagrams For Detailed
Wiring Of Analog Inputs
And Outputs
U2
CX2
RAM
U6
U3
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
CX6
INPUTS
TB3
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
RN5
GND
C10
GND
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
C20
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
U13
CX13
U15
CX15
U10
CX10
R15
C14
R19
U14
U12
CX14
C15
R22
R24
R25
CX12
U4
CX4
1
U9
PAL
C7
1
D12
R13
SC1
D19
R26
PRESSURE
SENSOR
EXPANSION
Splice If Req’d
VR1
L1
VR2
Notes:
1.) Connect FRP Tubing To The High Pressure
Port (Bottom Tube) Of The Staic Pressure
Transducer And Route The Tubing To The
Static Pressure Pickup Probe Location. Leave
The Port Marked “LO” Open To Atmosphere.
2.) The Static Pressure Pickup Probe Should
Ideally Be Mounted With The Probe Pointing
At A 90 Degree Angle To The Supply Air Flow
Direction. It Should Be Located In A Straight
Section Of The Supply Air Duct At A Distance
From The Unit Discharge That Is Approximately
Equal To 2/3 The Length Of The Longest
Supply Air Duct Run. Also Ideally The Probe
Should Be Located Not Less Than 3 Duct
Diameters Downstream And 2 Duct Diameters
Upstream Of Any Elbow Or Takeoff In The
Ductwork.
OE271
Static Pressure
Transducer
Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
2 Amp Maximum Load.
Connect To
Expansion Board
Base (When Used)
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192
0PS
9936
R6
C9
MC34064A
C13
C16
TB4
GND
R - 24VAC
G - Fan ON/OFF Only
24VAC
Relay Output Dry Contacts
R2 Thru R5 May Be User Configured
For The Following:
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
Note: A Total Of 20 Relays Are Available By
Adding Relay Expansion Boards. All Expansion
Board Relay Outputs Are User Configurable As
Listed Above.
GND
Line Voltage
24VAC
Size Transformer For
Correct Total Load.
VCM Controller = 8 VA
Power Consumption. If
Economizer Option Is Used
The Economizer Actuator
VA load Must Also Be
Considered When Sizing
The Transformer.
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
JOB NAME
FILENAME
OVCM-MainWire-1A.CDR
DATE:
PAGE
02/28/06
1 of 1
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller
Main Board Wiring
Component & System Wiring
VCM Controller Addressing
This Switch Should Be
In The OFF Position
As Shown
ADDRESS
ADDRESS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
ADDRESS
ADD
ADD
Controller
Address Switch
Address Switch Shown Is
Address Switch Shown Is
Set For Address 1
Set For Address 13
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 60
Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Caution
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.
INPUTS
TB3
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
RN5
GND
GND
C10
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
D8
PU4
D9
PU5
D11
PU7
D14
PU1
D6
PU2
D7
PU3
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
U13
CX13
U15
U10
CX10
R15
C14
R19
U14
U12
CX14
C15
R22
R24
R25
C20
CX15
CX12
R26
PRESSURE
SENSOR
EXPANSION
VR1
C7
D12
R13
SC1
D19
L1
VR2
R6
C9
C13
C16
TB4
GND
24VAC
Component & System Wiring
JOB NAME
FILENAME
OVCM-Address-1A.CDR
DATE:
PAGE
1 of 1
03/08/06
DRAWN BY:
B. Crews
DESCRIPTION:
OE331-21-VCM Orion VCM Controller
Address Switch Setting
33
Outdoor Air, Return Air & Supply Air Temperature Sensor Wiring
OE250
Outdoor Air
Temperature Sensor
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All Conduit
Fittings With Silicone Sealant.
OE231
Supply Air Temperature Sensor
(See Caution Note Below Regarding
Connection Location)
34
Mount In HVAC
Unit Supply
Air Duct
OE231
Return Air Temperature Sensor
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
Mount In HVAC
Unit Return
Air Duct
OE331-21-VCM
VCM Controller Board
Caution:
If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply Air Temperature
Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the
Supply Air Temperature Sensor must be connected to the MHGRV II controller.
See the Miscellaneous Diagrams & Technical
Information section in the back of this manual for detailed connection diagrams when using MODGAS II or MHGRV II controllers.
If you have either of these controllers on your HVAC unit and connect a Supply Air Temperature Sensor to the VCM controller, your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on each HVAC unit.
JOB NAME
FILENAME
OVCM-OA-SA-RASnsr-Wr-1A.CDR
DATE:
PAGE
1 of 2
02/28/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
OA, SA and RA Temperature Sensors
Component & System Wiring
Economizer Actuator Wiring
Note:
When Return Air Bypass Control Is Used This Actuator
Will Control Only The Outdoor Air Damper Actuator. The
Return Air Damper Is Controlled By A Separate
Actuator. For All Other Units The Return Air And
Outdoor Air Dampers Use The Same Actuator With The
Dampers Linked Together.
Economizers Damper Actuator
(Belimo Actuator Shown)
COM 1
GND
24 VAC
2-10 VDC
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
24 VAC Power Source
Sized For Actuator VA Load
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PRESSURE
SENSOR
OE331-21-VCM
VCM Controller Board
Component & System Wiring
JOB NAME
FILENAME
OVCM-EconoAct-Wr1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Economizer Actuator
35
Space Temperature Sensor & Remote Supply Air Reset Wiring
36
OE210,OE211, OE212 or OE213
Space Temperature Sensor
TEMP
GND
AUX
Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply Air
Temperature Reset Signal Option (by Others) May Be
Connected To AIN7 On The VCM Controller. Only
One Option Is Allowed, Not Both.
Remote Supply Air
Temperature Reset Signal
(By Others)
0-5 VDC or 0-10 VDC Signal
GND
10kOhm
AIN7
GND
10kOhm
Pullup Resistor PU7 Must Be
Removed When Using The
Remote Supply Air Temperature
Reset Signal Input
JOB NAME
FILENAME
OVCM-Spc-RemSA-Rst-Wr1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Space Sensor & Remote Supply Air Temp. Reset
Component & System Wiring
Supply Fan VFD & Bypass Damper Actuator Wiring
Caution:
The VFD Unit Must Be Configured
For 0-10 VDC Input. The Input
Resistance At The VFD Must Not
Be Less Than 1000 Ohms When
Measured At The VFD Terminals
With All Input Wires Removed.
Supply Fan Variable Frequency Drive
(By Others)
VFD 0-10VDC Input
+
_
GND
24 VAC Power Source
Sized For Actuator VA Load
Note:
Either The Supply Fan
Variable Frequency Drive
Option Or The Bypass
Damper Actuator Option May
Be Connected To AOUT2 On
The VCM Controller. Only
One Option Is Allowed, Not
Both.
Bypass Damper Actuator
(Belimo Actuator Shown)
COM 1
GND
24 VAC
0-10 VDC
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
Component & System Wiring
JOB NAME
FILENAME
OVCM-ZoneByp-SFVFD-Wr1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Supply Fan VFD or Bypass Damper Actuator
37
Suction Pressure Transducer Without Digital Compressor - Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
OE275-01-NDC
Suction Pressure Transducer
With Signal Conditioner
(250 PSIG)
Transducer Cable
With Built-In Signal
Conditioner
WH
BK
RD
Note:
Use This Diagram Only For Applications Without
Copeland Digital Scroll Compressors. For Applications
With Copeland Digital Scroll Compressors See The
Wiring Detail For Suction Pressure Transducers With
Copeland Digital Scroll Compressors.
Pullup Resistor PU5
Must Be Removed
+VDC
AIN5
GND
OE331-21-VCM
VCM Controller Board
38
JOB NAME
FILENAME
OVCM-SuctPress-WO-DSC-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Suction Pressure Transducer W/O DSC
Component & System Wiring
Suction Pressure Transducer With Digital Compressor - Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Connect To VCM Controller
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To
Next Expansion Base Board
(When Used)
D3
R20
PWR LD1
OE275-01-NDC
Suction Pressure
Transducer
(250 PSIG)
RD
WH
BK
P4 SHLD
P3
P2
EXC
OUT
P1 COM
Copeland Digital
Compressor
Controller
P5
P6
C1
C2
Note:
Use This Diagram Only For Applications With
Copeland Digital Scroll Compressors. For Applications
Without Copeland Digital Scroll Compressors See The
Wiring Detail For Suction Pressure Transducers Without
Copeland Digital Scroll Compressors.
Component & System Wiring
AOUT2
1.5 - 5 VDC
GND
OE352 or OE353 Expansion Base Board
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
JOB NAME
FILENAME
OVCM-SuctPressW-DSC-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Suction Pressure Transducer W/O DSC
39
Expansion Board Jumper Settings
OE356 - 4 BINARY INPUT BOARD #1
R5
R1
OPTO1
BIN 1
BIN 2
BIN 3
BIN 4
R6
R8
OPTO2
R2
R3
R10
COM
R12
4 DIG. IN MOD. I/O BD.
YS101788
R4
CX2
U2
CX1
U1
ADDRESS JMPR
OE356 - 4 BINARY INPUT BOARD #2
R1
R5
OPTO1
BIN 1
BIN 2
BIN 3
R6 R2
R8
OPTO2
R3
BIN 4
R10
COM
R12
4 DIG. IN MOD. I/O BD.
YS101788
R4
CX2
U2
CX1
U1
ADDRESS JMPR
OE354 - 4 ANALOG INPUT 1 ANALOG OUTPUT BOARD
AIN1
R5
AIN2
R6
AIN3
AIN4
R7
GND
R8
R9
AOUT1
D5
PU1
C2
PU2
C3
PU3
C4
PU4
C5
C1
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
ADDRESS JMPR
8 LM35
R10
YS101784
VOLTAGE JUMPER J03 MUST BE IN PLACE
VOLTAGE JUMPERS J01, J02 & J04 MUST BE REMOVED
PULLUP RESISTORS PU1, PU2, PU3 & PU4 MUST BE REMOVED
OE357 - 4 RELAY OUTPUT BOARD #1
4RLY IO BD.
YS101790
K1
K2
K3
K4
OE355 - 4 ANALOG OUTPUT BOARD
Q1
CX2
AOUT1
AOUT2
AOUT3
AOUT4
GND
D1
R6
D2
R7
D3
R8
D4
R9
R2
Q2
R3
Q3
R4
Q4
4 AOUT MOD. I/O BD.
R5
YS101786
CX3
U2
U3
CX1
U1
ADDRESS JMPR
PHIL
PHIL
HA
TL
AN
ADDRESS JMPR
ADDRESS JMPR
OE357 - 4 RELAY OUTPUT BOARD #2
ADDRESS JMPR
OE357 - 4 RELAY OUTPUT BOARD #3
ADDRESS JMPR
OE357 - 4 RELAY OUTPUT BOARD #4
40
JOB NAME
FILENAME
OVCM-EXP-JMPR-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Expansion Board Address & Jumper Settings
Component & System Wiring
Binary Input Board Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each OE352 - 2 Slot Expansion Base
Board. 20 VA Minimum Power
Required For Each OE353 - 4 Slot
Expansion Base Board
Modular Cable
Connect To VCM Controller
Modular Cable
Connect To Next Expansion Board
(When Used)
Hood On - N.O. Contact
Dirty Filter - N.O. Contact
Proof Of Flow - N.O. Contact
Remote Forced Occupied - N.O. Contact
BIN1
BIN2
BIN3
BIN4
COM
Remote Forced Heating - N.O. Contact
Remote Forced Cooling - N.O. Contact
Smoke Detector - N.C. Contact
Remote Forced Dehumidification - N.O. Contact
BIN1
BIN2
BIN3
BIN4
COM
D3
R20
PWR LD1
R5
OPTO1
BIN 1
BIN 2
BIN 3
BIN 4
COM
R6
R8
R10
OPTO2
R12
4 DIG. IN MOD. I/O BD.
YS101788
R5
OPTO1
BIN 1
BIN 2
BIN 3
BIN 4
COM
R6
R8
R10
OPTO2
R12
4 DIG. IN MOD. I/O BD.
YS101788
R1
R2
R3
R4
R1
R2
R3
R4
CX2 CX1
U2
U1
CX2 CX1
U2
U1
OE352 2 Slot Or OE353 - 4 Slot Expansion Board
As Required
Component & System Wiring
JOB NAME
FILENAME
OVCM-BinInput-Brds-Wr-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Binary Input Expansions Boards
41
Outdoor Humidity Sensor Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC.
Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
OE265-13
OA Humidity Sensor
Connect To VCM Controller
Connect To Next
Expansion Base Board
(When Used)
4 3 2 1
ON
Jumpers Must Be
Set as Shown For
Correct
O-5 VDC
Operation
1 & 3 Are Off
2 & 4 Are On
4 3 2 1
ON
6 5 4 3 2 1
ON
Span
Zero
6 5 4 3 2 1
ON
Jumpers Must Be
Set as Shown For
Normal
Operation Of
Sensor
1, 2, 4, 5 & 6 Are
Off
3 Is On
D3
R20
PWR LD1
AIN1
0-5 VDC Input
GND
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
PU3
C3
PU4
C4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784 Pullup Resistor PU1 Must
Be Removed As Shown
Jumper J01 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
42
JOB NAME
FILENAME
OVCM-OA-HumSensorWr-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Outdoor Air Humidity Sensor
Component & System Wiring
Return Air Humidity Sensor Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
4 3 2 1
ON
Jumpers Must Be Set as Shown For Correct
O-5 VDC Operation
1 & 3 Are Off
2 & 4 Are On
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
OE265-14
RA Humidity Sensor
Connect To VCM Controller
Connect To Next
Expansion Base Board
(When Used)
Span
Zero
4 3 2 1
ON
6 5 4 3 2 1
ON
AIN2
0-5 VDC Input
GND
Pullup Resistor PU2 Must
Be Removed As Shown
D3
R20
PWR LD1
AIN1
R5
AIN2
R6
AIN3
AIN4
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
PU3
C3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J02 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
6 5 4 3 2 1
ON
Jumpers Must Be
Set as Shown For
Normal
Operation Of
Sensor
1, 2, 4, 5 & 6 Are
Off
3 Is On
Component & System Wiring
JOB NAME
FILENAME
OVCM-RA-HumSensorWr-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Return Air Humidity Sensor
43
Indoor Air Humidity Sensor Wiring
WARNING!!
Observe Polarity! All boards must be wired with
GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
OE265-11
Space Humidity Sensor
Zero Span
4 3 2 1
ON
6 5 4 3 2 1
ON
AIN2
0-5 VDC Input
GND
Pullup Resistor PU2 Must
Be Removed As Shown
4 3 2 1
ON
6 5 4 3 2 1
ON
Jumpers Must Be Set as Shown For
Correct
O-5 VDC Operation
1 & 3 Are Off
2 & 4 Are On
Jumpers Must Be
Set as Shown For
Normal
D3
R20
PWR LD1
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
R8
R9
AOUT1
D5
R10
PU1
PU2
C2
PU3
C3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J02 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
44
JOB NAME
FILENAME
OVCM-Spc-HumSensorWr-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Space Humidity Sensor Wiring
Component & System Wiring
Building Pressure Sensor, Actuator & VFD Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each OE352 - 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each OE353 - 4 Slot Expansion Base Board
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturers
Wiring Instructions
Modular Cable
Connect To VCM Controller
Modular Cable
Connect To Next Expansion Board
(When Used)
Building Pressure Control
Damper Actuator
(0-10 VDC)
COM 1
+ 2
Y1 3
Building Pressure
Relief FAN VFD
(0-10 VDC)
+
COM
Either The Building Pressure
Control Damper Actuator (Used for
Reverse Building Pressure Control
Applications)Or The Building
Pressure Relief Fan VFD Control
Can Be Used, Not Both.
D3
R20
PWR LD1
Orion - OE258 Building Pressure
Transducer
EXC
OUT
COM
AIN4
GND
AOUT1
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
PU3
C3
PU4
C4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Plastic Tubing To Building
Pressure Sensing Locations
OE352 2 Slot Or OE353 - 4 Slot Expansion Board
As Required - OE353 Is Shown
Component & System Wiring
JOB NAME
FILENAME
OVCM-BPS-BPA-BPVFD-Wr-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Building Pressure Sensor, Actuator & VFD Wiring
45
CO2 Sensor Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Connect To VCM Controller
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To Nex
Expansion Base Board
(When Used)
OE255 or OE256
(0-10VDC Signal)
AIN3
0-10 VDC Input
GND
Pullup Resistor PU3 Must
Be Removed As Shown
D3
R20
PWR LD1
AIN1
R5
AIN2
R6
AIN3
AIN4
R7
GND
R8
R9
AOUT1
D5
R10
PU1
PU2
C2
C3
PU3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J03 Must
Be In Place As Shown
OE352 or OE353 Expansion Base Board
46
JOB NAME
FILENAME
OVCM-CO2-SensorWr-1A.CDR
DATE:
PAGE
03/06/06
DRAWN BY: B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
1 of 1
Component & System Wiring
4 Relay Output Expansion Board Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each OE352 - 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each OE353 - 4 Slot Expansion Base Board
Modular Cable
Connect To VCM Controller
Modular Cable Connect To
Next Expansion Base Board
(When Used)
Configurable Relay Output # 6
Configurable Relay Output # 7
Configurable Relay Output # 8
Configurable Relay Output # 9
Configurable Relay Output # 10
Configurable Relay Output # 11
Configurable Relay Output # 12
Configurable Relay Output # 13
Configurable Relay Output # 14
Configurable Relay Output # 15
Configurable Relay Output # 16
Configurable Relay Output # 17
D3
R20
PWR LD1
AC
:
-PS
AC
:
-PS
4RLY IO BD.
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
4RLY IO BD.
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
4RLY IO BD.
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
4RLY IO BD.
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
AC
:
-PS
YS101790
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
YS101790
AC
:
-PS
OMRON
24VDC
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
CONTACT
UL5A250V
G5L-114P
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
YS101790
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
AC
:
-PS
OMRON
24VDC
CONTACT
UL5A250V
G5L-114P
YS101790
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
74HC04N
74HC04N
74HC04N
74HC04N
PCF8574P
PCF8574P
PCF8574P
PCF8574P
ULN2803A/
ULN2803A/
ULN2803A/
ULN2803A/
U1
U2
U1
U2
U1
U2
U1
U2
Configurable Relay Output # 18
Configurable Relay Output # 19
Configurable Relay Output # 20
Configurable Relay Output # 21
Note:
All Relay Outputs Are
Normally Open And Rated
For 24 VAC Power Only.
2 Amp Maximum Load.
OE352 2 Slot Or OE353 - 4 Slot Expansion Board
As Required - OE353 Is Shown
JOB NAME
FILENAME
OVCM-Exp-RelayBrd-Wr-1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Relay Output Expansion Board
Component & System Wiring 47
Modulating Heating & Cooling Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VACto-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together.
Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Connect To VCM Controller
Connect To Next
Expansion Board
(When Used)
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
The Cooling Device Used Can
Be A Modulating Chilled Water
Valve or A Digital Scroll
Compressor. If Using A Digital
Scroll Compressor Please See
Digital Scroll Detailed Wiring
Information In This Manual.
Modulating Heating Device
(By Others)
0-10 VDC or 2-10 VDC
(Configurable)
+
_
GND
The Heating Device Used Can Be A
Modulating Hot Water Valve, Modulating
Steam Valve or SCR Controlled Electric
Heating Coil.
AOUT1
AOUT2
GND
D3
R20
PWR LD1
AOUT1
AOUT2
AOUT3
AOUT4
GND
4 AOUT MOD. I/O BD.
R7
D3
R8
D4
R9
D1
R6
D2
Q1
Q2
R2
Q3
R3
Q4
R4
R5
YS101786
CX2
CX3
U2
U3
CX1
U1
Modulating Cooling Device
(By Others)
0-10 VDC, 2-10 VDC or 1.5-5.0 VDC
(Configurable)
+
_
GND
The Cooling Device Used Can Be A
Modulating Chilled Water Valve or A Digital
Scroll Compressor. If Using A Digital Scroll
Compressor Please See Digital Scroll
Detailed Wiring Information In This Manual.
OE352 or OE353 Expansion Base Board
48
Note:
1.)The Modulating Cooling Device Used Must Be Capable Of
Accepting Either A 0-10 VDC, 2-10 VDC Or 1.5-5.0 VDC Input.
The AOUT2 Output Voltage Is User Configurable For These Voltages
The Modulating Heating Devices Used Must Be Capable Of
Accepting Either A 0-10 VDC Or 2-10 VDC Input.
The AOUT1
Output Voltage Is User Configurable For These Voltages.
These
Voltage Outputs Must Be Configured When You are Setting-up The
VCM Controller(s) Operating Parameters. See the VCM Controller
Operator Interfaces Technical Guide For Complete Controller
Programming and Configuration Information.
2.) Each Modulating Heating Or Cooling Device Used On The VCM
Controller Must Have (1) Relay Output Configured For Each Device
Used, In Order To Enable The Modulating Heating And/Or Cooling
Device's Sequence. This Relay Output Must Be Configured When
Setting-up The VCM Controller Operating Parameters. See the VCM
Controller Operator Interfaces Technical Guide For Complete
Controller Programming and Configuration Information.
JOB NAME
FILENAME
OVCM-ModHeat-Cool-Wr1A..CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Modulating Heating and Cooling
Component & System Wiring
Return Air Bypass Wiring
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VACto-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together.
Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Connect To VCM Controller
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To Next
Expansion Board
(When Used)
Return Air
Damper Actuator
(2-10 VDC)
COM 1
+ 2
Y1 3
Return Air Bypass
Damper Actuator
(2-10 VDC)
COM 1
+ 2
Y1 3
Belimo Actuator
Wiring Shown.
Consult Factory For
Other Manufacturers
Wiring Instructions
2-10 VDC
2-10 VDC
AOUT3
AOUT4
GND
D3
R20
PWR LD1
AOUT1
AOUT2
AOUT3
AOUT4
GND
4 AOUT MOD. I/O BD.
R7
D3
R8
D4
R9
D1
R6
D2
Q1
Q2
R2
Q3
R3
Q4
R4
R5
YS101786
CX2
CX3
U2
U3
CX1
U1
OE352 or OE353 Expansion Base Board
Component & System Wiring
JOB NAME
FILENAME
OVCM-RA-Byp-Wr1A.CDR
DATE:
PAGE
1 of 1
03/06/06
DRAWN BY:
B. Crews
DESCRIPTION:
VCM Controller Wiring Detail
Return Air Bypass
49
50 Component & System Wiring
VAV/Zone Controller
Diagrams
Component & System Wiring 51
VAV/Zone Controller Board Wiring
This Switch Must Be
In The ON Position
As Shown
ADDRESS ADD
1
2
4
8
16
32
TOKEN
NET
ADD
RES
S
ADD
ADD
RES
S
ADD
Controller
Address Switch
Address Switch Shown Is
Set For Address 9
The Address For Each Controller
Must Be Between 1 And 58 And Be
Unique To The Other Controllers
On The Local Loop
Address Switch Shown Is
Set For Address 13
Airflow Probe
(For Pressure Independent Applications Only)
VAV/Zone Controller Board
Lo Hi
ADD
SW1
16
32
4
2
8
1
NET
PJ1
Room Sensor
NORMAL
OVR
W
A
R
M
E
R
C
O
O
L
E
R
Supply Air
Temperature
Sensor
(See Note 3)
(WH) T
Locate In Supply Duct
Near Zone Damper
(Bare) SHLD
(RD) 24 VAC
PJ3
PJ4
R25
TB2
GND
AIN
PJ2
0
Zone Actuator
1
To Optional Relay
Expansion Board
Power/Comm Cable
From Power/Comm Distribution Board
Or Previous VAV/Zone Controller
Power/Comm Cable To
Next VAV/Zone Controller or
Power/Comm Distribution Board
52
(BK) R
(BR) GND
Pin Layout Diagram
(GR) GND
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
2.) All communication wiring to be 2 conductor twisted pair with shield.
Use Belden #82760 or equivalent.
3.)The Supply Air Sensor is not required when the VAV/Zone Controller is connected to an Orion VAV/CAV or VCM Unit Controller board. A global supply air temperature is broadcast by the VAV/CAV or VCM Unit
Controller. The Supply Air Sensor is only required if the VAV/Zone
Controller is required to operate as a “Stand Alone” controller.
JOB NAME
FILENAME
O-VAV-ZoneWire1.CDR
DATE:
PAGE
05/18-06
DRAWN BY:
B. Crews
DESCRIPTION:
OE324-00-VAVZ Orion VAV/Zone Controller
1 of 1
Component Wiring Diagram
Component & System Wiring
Slaved Zone Wiring
EXPANSION ACTUATOR
PJ1 PJ2
HZ000095
ZONE ACTUATOR #1
(MASTER)
0 1
MODULAR CABLE
OE267
(PL101824) BYPASS AND
SLAVE INTERFACE CARD
CLOSE
OPEN
GND
FDBK
PJ2
GND
OPEN
CLOSE
PJ1
(OE324) ZONE CONTROLLER BOARD
OE520, OE736, OE742
SLAVED- ZONE ACTUATOR #2
(WHEN USED)
MODULAR CABLE
OE282
HZ000095
SLAVED-ZONE ACTUATOR #1
0 1 0 1
(PL101824) BYPASS AND
SLAVE INTERFACE CARD
OE282
MODULAR
CABLE
HZ000095
(PL101824) BYPASS AND
SLAVE INTERFACE CARD
OE282
MODULAR
CABLE
HZ000095
PJ1
GND
OPEN
CLOSE
NOT USED FOR
THIS APPLICATION
PJ2
FDBK
GND
OPEN
CLOSE
PJ1
GND
OPEN
CLOSE
PJ2
FDBK
GND
OPEN
CLOSE
NOT USED FOR
THIS APPLICATION
Note:
1.) A Slave Wiring Adapter (OE267) consisting of a bypass & slave interface card and modular cable is supplied with the OE523 Round
Slaved-Zone Damper, OE738 Rectangular Slaved-Zone Damper Kit and the OE282-03 Slaved Zone Package. It is required when attaching slave actuator(s) to the master zone damper. The bypass & slave interface card should be mounted in the control enclosure of the master zone damper. It is mounted by fastening the plastic snap-track to the control enclosure with sheet metal screws. Connect modular cables to the bypass and slave interface card and the master zone actuator as shown.
JOB NAME
FILENAME
O-SLVZONEWIRE.CDR
DATE:
PAGE
1
C O N T R O
08-26-02
DRAWN BY:
B. CREWS
DESCRIPTION:
Orion Systems
Slaved-Zone Wiring
L S
Component & System Wiring 53
3 Relay Output Expansion Board Wiring
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
C2
C4
VR1
24VAC
COM
24 VAC Transformer Supplied
& Wired by Others. Size For
Required Contactor(s) Load.
PJ1
Q3
RLY
1
Q2
RLY
2
Q1 RLY
3
C1
LM358
U1
C6
C3
C5
2RAOUT BD.
YS101714
REV. 3
V4
TB2
1
COM
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
Q4
TB1 GND
C1
1st Stage Heat Contactor
C3
C2
2nd Stage Heat Contactor
3rd Stage Heat Contactor
Note:
3 Stage Heating is Attained by Sizing All 3
Heating Elements For Equal KW Output. Each
Element Should be Sized for 1/3 of the Total KW
Output Required. To Achieve 3 Stage Heating the
System would be Configured to Energize
Contactor C1 for First Stage Heat. For 2nd Stage
Heat the System Would be Configured to Deenergize Contactor C1 and Energize Contactor C2
& C3. For 3rd Stage Heat the System Would be
Configured to Leave Contactor C2 & C3 Energized and also Energize Contactor C1.
24 VAC Contactor(s)
Supplied & Installed
By Others. 2 Amp
Max. Load Each.
Typical Wiring for
Single Duct Terminal with Electric Heat
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
PJ1
Q3
RLY
1
Q2 RLY
2
Q1
RLY
3
C1
LM358
U1
C6 C3
C5
2RAOUT BD.
YS101714
REV. 3
V4
TB2
1
COM
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
Q4
TB1 GND
24VAC
COM
24 VAC Transformer Supplied
& Wired by Others. Size For
Required Fan Relay Load.
Fan Relay
R1
24 VAC Fan Relay
Supplied & Installed
By Others. 2 Amp
Max. Load.
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted & Wired by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
PJ1
C2
C4
VR1
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
Q3
RLY
1
Q2 RLY
2
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
Q1
RLY
3
C1
LM358
U1
C6 C3
C2
C4
Typical Wiring for
Fan Terminal Unit with Cooling Only
C5
VR1
Q4
2RAOUT BD.
YS101714
REV. 3
V4
TB2
1
COM
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
TB1 GND
24VAC
COM
24 VAC Transformer Supplied &
Wired by Others. Size For Required
Fan Relay & Contactor(s) Load.
Fan Relay
R1
C1
C3
1st Stage Heat Contactor
C2
2nd Stage Heat Contactor
3rd Stage Heat Contactor
Note:
3 Stage Heating is Attained by Sizing All 3 Heating
Elements For Equal KW Output. Each Element Should be
Sized for 1/3 of the Total KW Output Required. To Achieve 3
Stage Heating the System would be Configured to Energize
Contactor C1 for First Stage Heat. For 2nd Stage Heat the
System Would be Configured to De-energize Contactor C1 and Energize Contactor C2 & C3. For 3rd Stage Heat the
System Would be Configured to Leave Contactor C2 & C3
Energized and also Energize Contactor C1.
JOB NAME
24 VAC Fan
Relay &
Contactor(s)
Supplied &
Installed By
Others. 2
Amp Max.
Load Each.
Typical Wiring for
Fan Terminal Unit with Electric Heat
Notes:
1.) All Wiring to be in Accordance With Local & National Electrical Codes
& Specifications.
FILENAME
O-OE322-3RELAY1OUTBD.CDR
DATE:
PAGE
1 of 3
09/26/06
DRAWN BY:
B. Crews
DESCRIPTION:
OE322 - 3 Relay -1 Analog Output Board
Component Wiring Diagram
54 Component & System Wiring
3 Relay Output Expansion Board Wiring (Cont’d)
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted & Wired by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted & Wired by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
PJ1
PJ1
Q3
RLY
1
Q1 RLY
3
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
Q3
RLY
1
Q2 RLY
2
Q1
RLY
3
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
Q2
RLY
2
C1
LM358
U1
C6
C3
C2
C4
C1
LM358
U1
C6 C3
C2
C4
C5
2RAOUT BD.
YS101714
REV. 3
V4
TB2
COM
1
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
Q4
TB1 GND
VR1
C5
2RAOUT BD.
YS101714
REV. 3
V4
TB2
COM
1
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
Q4
TB1 GND
VR1
0-10 VDC Signal
HWV
Supply Power
Of Required Voltage
To Valve Motor
(By Others)
24 VDC Power Only
(12 Watts Max.)
Is Available From TB3
Terminals (+V & GND)
0-10 VDC Modulating
Hot Water Valve Supplied & Installed by Others
Typical Wiring For
Single Duct Terminal
With Modulating Hot
Water Heat
24VAC
24 VAC Transformer Supplied &
Wired by Others. Size For Required
Fan Relay Load.
COM
R1
Fan Relay
0-10 VDC Signal
HWV
Supply Power
Of Required Voltage
To Valve Motor
(By Others)
24 VDC Power Only
(12 Watts Max.)
Is Available From TB3
Terminals (+V & GND)
0-10 VDC Modulating
Hot Water Valve Supplied & Installed by Others
24 VAC Fan Relay Supplied and
Installed by Others. 2 Amp Max.
Load For Fan Relay.
Typical Wiring For
Fan Terminal Unit
With Modulating
Hot Water Heat
Notes:
1.) All Wiring to be in Accordance With Local & National Electrical Codes
& Specifications.
Component & System Wiring
JOB NAME
FILENAME
O-OE322-3RELAY1OUTBD.CDR
DATE:
PAGE
2 of 3
09/26/06
DRAWN BY:
B. Crews
DESCRIPTION:
OE322 - 3 Relay -1 Analog Output Board
Component Wiring Diagram
55
3 Relay Output Expansion Board Wiring (Cont’d)
24VAC
COM
24 VAC - Transformer Supplied and Installed by Others. Size For
Required HW Valve Load.
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted & Wired by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
PJ1
Q3
RLY
1
Q2
RLY
2
Q1
RLY
3
C1
LM358
U1
C6 C3
C5
2RAOUT BD.
YS101714
REV. 3
V4
TB2
COM
1
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
Q4
TB1 GND
HWV
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
C2
C4
VR1
24 VAC HW Valve Supplied and
Installed by Others. 2 Amp Max. Load.
Typical Wiring for
Single Duct Terminal
With 2 Position HW Valve
WattMaster Part #OE322
Relay Expansion Board w/ Modular Cable
Supplied by WattMaster
Mounted & Wired by Others
Connect To VAV/Zone Controller
Using Modular Cable Supplied
By WattMaster
PJ1
Q3
RLY
1
Q2 RLY
2
WattMaster Part # BK000047
Snaptrack Supplied by WattMaster
Mounted by Others. Remove Control
Board from Snaptrack & Mount Snaptrack on Box
Q1 RLY
3
C1
LM358
U1
C6 C3
C2
C4
C5
2RAOUT BD.
YS101714
REV. 3
V4
TB2
COM
1
V3
2
3
TB3
+V
GND
V1
V5
ANALOG
OUT
+
Q4
24VAC
COM
Fan Relay
R1
24 VAC - Transformer Supplied and Installed by Others. Size For
Required Fan Relay and HW
Valve Load.
HWV
TB1 GND
24 VAC Fan Relay and HW Valve Supplied and Installed by
Others. 2 Amp Max. Load Each For HW Valve and Fan Relay.
VR1
Typical Wiring for
Fan Terminal
With 2 Position HW Valve
Notes:
1.) All Wiring to be in Accordance With Local & National Electrical Codes
& Specifications.
56
JOB NAME
FILENAME
O-OE322-3RELAY1OUTBD.CDR
DATE:
PAGE
3 of 3
09/26/06
DRAWN BY:
B. Crews
DESCRIPTION:
OE322 - 3 Relay -1 Analog Output Board
Component Wiring Diagram
Component & System Wiring
Communication Devices
Diagrams
Component & System Wiring 57
System Manager Modular Cable Connections
Modular System Manager
Front Cover
DEC
MINUS
PREV
UP
ESC DOWN CLEAR
ENTER
NEXT
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
U7
YS101830PREV.
2PMODULARPSYSTEM
MANAGER
R1
R4
U1
74HC259
U2
U3
CX4
RN1
C3
CX5
X2
CX6
U6
U4
U8
74HC573
CX7
SC1
P1
P2
U3
82B715
PJ1
R11
R12
D1
R5
R6
D2
DSPY1
R13
L1
R10
D4
CX10
C6
VAR1
U11
C7 C8
U12
V62C518256L-70P 75176
R14
74HC540
U14
RV1
R7
Modular System Manager
Back of Front Cover
58
Power/Comm Cables To
Power/Comm Distribution Board,
Or VAV/Zone Controllers On
Local Loop. See Page 2 Of This
Drawing For Wiring With A Stand
Alone Controller.
System Manager Wiring Using Modular Cables
See Page 2 and 3 of this Diagram for Alternate Hard Wiring Information
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
2.) All modular power/comm cables are to be WattMaster part number
PCC-xx or PCCE-xx cables.
JOB NAME
FILENAME
O-SYSTEMMGRWIRE1A.CDR
DATE:
PAGE
1 of 3
02/11/04
DRAWN BY:
B. Crews
B. Light
DESCRIPTION:
OE392 Orion Modular System Manager
Component Wiring Diagram
Component & System Wiring
System Manager Modular Cable Pigtail - Wiring Schematic
U7
YS101830PREV.
2PMODULARPSYSTEM
MANAGER
R1
R4
U1
74HC259
U2
U3
CX4
RN1
C3
CX5
X2
CX6
U6
U4
U8
74HC573
CX7
SC1
P1
P2
U3
82B715
PJ1
R11
R12
D1
R5
R6
D2
DSPY1
R13
L1
R10
D4
CX10
C6
VAR1
U11
C7 C8
75176
U12
V62C518256L-70P
R14
74HC540
U14
RV1
R7
Modular System Manager
Back of Front Cover
Use Supplied Modular
Cable With Stripped Ends
For Connection To Terminal
Block And Transformer
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
RED (24 VAC)
BROWN (GND)
GREEN (GND)
T
SHLD
R
Controller Board
Class 2 Transformer
Rated For 6 VA Minimum
System Manager Wiring Schematic For Using The Pigtail
See Page 1 of this Diagram for Modular Cable Connection Information
See Page 3 of this Diagram for Additional Pigtail Wiring Details
JOB NAME
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
FILENAME
O-SYSTEMMGRWIRE1A.CDR
DATE:
PAGE
2 of 3
DRAWN BY:
B. Crews
B. Light
DESCRIPTION:
OE392 Orion Modular System Manager
Component Wiring Diagram
Component & System Wiring 59
System Manager Modular Cable Pigtail - Wiring Detail
U7
YS101830PREV.
2PMODULARPSYSTEM
R1
R4
U1
74HC259
U2
U3
CX4
RN1
C3
CX5
X2
CX6
U6
U4
U8
74HC573
CX7
SC1
P1
P2
U3
82B715
PJ1
R11
R12
D1
R5
R6
D2
DSPY1
R13
L1
R10
D4
CX10
C6
VAR1
U11
C7 C8
75176
U12
V62C518256L-70P
R14
74HC540
U14
RV1
R7
Modular System Manager
Back of Front Cover
HZ000121
Modular Pigtail Cable
Supplied With System Manager
Handy Box , Conduit,
Fittings, Wire Nuts,
Butt Splices Etc.,
( By Others)
RED
(24
VA
C)
(G
ND)
BRO
W
N
GREEN
(GND)
2-Conductor Shielded
18-Guage
Communications Wire
T
SHLD
R
LINE
VOLTAGE
Controller Board
Drain Wire (Shld)
Class 2 Transformer
Rated For 6 VA Minimum
(By Others)
60
LINE VOLTAGE
System Manager Wiring Details For Using The Pigtail
See Page 1 of this Diagram for Modular Cable Connection Information
See Page 2 of this Diagram for Pigtail Wiring Schematic
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
JOB NAME
FILENAME
O-SYSTEMMGRWIRE1A.CDR
DATE:
PAGE
3 of 3
02/11/04
DRAWN BY:
B. Crews
B. Light
DESCRIPTION:
OE392 Orion Modular System Manager
Component Wiring Diagram
Component & System Wiring
Modular Service Tool Connections
Optional Connection For
Controllers Without DIN Connector
PL101904 Adapter Board
T
erminal
Block Base
(Remove Terminal Block)
COMM
T
SHLD
R
Female DIN Connector
Connector Cable
Mode
Selection
STATUS PREV
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
7
DEC
1
4
UP
ESC
DOWN
CLEAR
ENTER
2
5
8
0
3
6
9
NEXT
Male DIN Connector
Typical Controller Board
The Modular Service Tool Can Be Connected To Most
Controllers By Plugging One End Of The Supplied
Cable Into the Modular Service Tool DIN Connector
And The Other End Into The DIN Connector On The
Controllers.
Some Controllers Without DIN Connectors Require
Use Of The Supplied PL101904 Adapter Board Shown
Above. To Connect With Adapter Board, First Unplug
COMM Terminal Block From Controller Board. Plug
PL101904 Adapter Board Terminal End Into Terminal
Block Base On Controller. Plug DIN Connector Cable
Into DIN Connector On PL101904 Adapter Board . See
Optional Connection For Controllers Without DIN
Connector Above For Illustration Of This Connection.
Modular Service Tool
Be Sure The Modular Service
Tool Is Connected To The
Supplied Power Pack Or Has
Fresh Batteries Installed Before
Attempting Programming Of The
Controller. Be Sure The Power Is
Turned Off On The Modular
Service Tool Before Connecting
The Cable To The Controller.
Power On Button
JOB NAME
FILENAME
G-ModServiceTool1A.CDR
DATE:
PAGE
1 of 1
02/11/04
DRAWN BY:
B. Crews
DESCRIPTION:
OE391 Modular Service Tool
Connection Diagram
Component & System Wiring 61
CommLink II Wiring & Cabling Connections
Commlink II Communications Interface
(Jumper Set For Multiple Loop)
Part #OE361-04
(DTE) (DCE)
T G R
POWER
2
4
V
G
N
D
CommLink Is Supplied With 110/24VAC Power Supply.
If Desired A Transformer (By Others)
May Be Wired To The CommLink Instead
Required VA For Transformer
CommLink = 14VA Max.
24VAC
Line Voltage
See Note 1
120/24 Vac
Transformer
Part # PX000015
Molded Modem Cable.
Part #HZ000098
Supplied With CommLink
RS-485
19200 Baud
Connect To First Device On Loop. See
System Application Documentation For
Your Specific Systems Controller
Connection & Wiring Information
Connect Supplied RJ12 Modular Phone Cable
To Supplied 9 Pin Or 25 Pin Connector As Reqd
By Your Computer Com Port Connection All Communication Loop
Wiring Is Straight Through
4 Piece Computer
Cable Kit.
Part # HZ000112
Supplied With
CommLink
T
SH
R
T
SH
R
T
SH
R
T
SH
R
Caution:
Disconnect All Communication Loop Wiring
From The CommLink Before Removing Power
From The CommLink. Reconnect Power And Then
Reconnect Communication Loop Wiring.
25 Pin
Male
9 Pin
Female
25 Pin
Female
Connect To Remote Link
Only
.
Remote Link Is Part # OE419-04
Caution: Do Not Use The “Molded Cable” To
Connect To The Computer (DCE) Connector.
This Cable Is Only To Be Used To Connect
From The CommLink (DTE) Connection To The
Remote Link (When Used).
Use 25 Pin Or 9 Pin Connector As
Required By Available Serial (COM) Port
On Computer.
Caution: Do Not Use The “25 Pin Or 9 Pin Cable” To
Connect To The Remote Link (DTE) Connector. This
Cable Is Only To Be Used To Connect From The
CommLink (DCE) Connection To The Computer
(When Used) Serial Port (COM) Connection.
PIN 1
COMM DRIVER CHIP
( U1 )
EPROM CHIP
MULTI
SINGLE
Note:
Place Jumper Between
Pins 1 & 2 for Multiple
Loop Applications &
Between Pins 2 & 3 for
Single Loop Applications
See Note 4.
CommLink Jumper Switch Settings
JOB NAME
Notes:
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
4.)CommLink Is Usually Shipped With The
Jumper In The Multiple Loop
Configuration. Check The Application
Documentation For Your Specific System
For Correct Jumper Position Setting.
3.)All Communication Wiring To Be
2 Conductor Twisted Pair With
Shield. Use Belden #82760 Or
Equivalent.
FILENAME
G-CommLinkWire.CDR
DATE:
PAGE
1
02/11/04
DRAWN BY:
B. CREWS
DESCRIPTION:
OE361-04
CommLink II Wiring
62 Component & System Wiring
MiniLink Polling Device Wiring Using Modular Connectors
ADD
ADD
C1
R3
X1
C3
CX1
CX6
P3
R24
D1
1
R1
CX2
VREF
CX2
R4
Component & System Wiring
V1
R26
R25
R27
CX15
CX14
CX13
U15
U13
U14
R
SHLD
T
TB4
TB3
T
SHLD
R
AIN1
AIN2
+5V
GND
TB2
24VAC
D4
GND
TB1
R31
8
4
2
1
16
32
ADD
P5
24VAC
GND
T
SHLD
R
P2
63
MiniLink Polling Device Wiring Using Wire Terminals
AD
D
ADD
64
CX1
C1
R3
X1
C3
CX6
VREF
CX2
R4
P3
D1
1
R1
CX2
R24
R26
R25
V1
R27
CX15
CX14
CX13
U15
U13
U14
R
SHLD
T
TB4
TB3
T
SHLD
R
AIN1
AIN2
+5V
GND
TB2
24VAC
D4
GND
TB1
R31
2
1
4
8
16
32
ADD
P5
24VAC
GND
T
SHLD
R
T
SHLD
R
T
SHLD
R
Component & System Wiring
Power/Comm Board Wiring - When Used For Local Loop Devices
WARNING!
DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!
Power/Comm Cable From Other Power/Comm Board,
System Manager, Or VAV/Zone Controller On Local Loop
If This Is The First Power/Comm Board On The Local Loop,
No Connection Is Required. See Note 2.
Line Voltage
24VAC
Connect To VAV/CAV Controller
If This Is First Power/Comm Board
On Local Loop - Otherwise No
Connection Is Required. See Note 2.
Local Loop RS-485
9600 Baud
T
SH
All Comm Loop Wiring Is
Straight Thru
T
SH
T
SH
T
SH
R R R R
24VAC Transformer (By Others)
See System Configuration Installation &
Commissioning Section Of This Manual
For Detailed Sizing Information
4 Amp Slow Blow Fuse
COMMPIN
CAUTION!
No MinLink PDs Can Be
Connected To The Same
Power/Comm Board(s) That
Are Used To Supply Power
And Communications For
VAV/Zone Controllers And
System Manager On The
Local Loop.
25
4A
D1
V1
OUT
COMM POWER&
Note:
Diagram Shown Is For Wiring Of
Power/Comm Board When Used
For Connecting Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards . See Page 2
Of This Drawing For Wiring When
Power/Comm Board Is Used For
Connection Of MiniLink Polling
Devices On The Network Loop.
Local Loop RS-485
9600 Baud
Power/Comm Cable To Other Power/Comm Board(s),
System Manager, Or VAV/Zone Controllers On Local Loop Only.
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
2.) All modular power/comm cables are to be WattMaster part number
PCC-xx or PCCE-xx cables. All other communication wiring to be 2 conductor twisted pair with shield (Belden #82760 or equivalent).
JOB NAME
FILENAME
O-Pwr-CommWire1A.CDR
DATE:
PAGE
1 of 2
02/11/004
DRAWN BY:
B. Crews
DESCRIPTION:
OE365-01 Orion Power/Comm Board
Component Wiring Diagram
Component & System Wiring 65
Power/Comm Board Wiring - When Used For Network Loop Devices
WARNING!
DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!
Comm/Power Cable From Other Power/Comm
Board Used For Connecting MiniLink PDs Or Previous MiniLink
PD On Network Loop. If This Is The First Power/Comm Board
On The Network Loop, This Power/Comm Cable Connection Is
Not Required. Instead Use The 3 Pole Terminal Block
Communication Connection As Shown Below And Connect
To The CommLink. See Note 2.
Line Voltage
24VAC
Use To Connect CommLink When
This Is the First Power/Comm Board
On The Network Loop. Otherwise No
Connection Is Required. See Note 2.
Network Loop RS-485
192000 Baud
T
SH
All Comm Loop Wiring Is
Straight Thru
T
SH
T
SH
T
SH
R R R R
24VAC Transformer (By Others)
See System Configuration Installation &
Commissioning Section Of This Manual
For Detailed Sizing Information
4 Amp Slow Blow Fuse
COMMPIN
CAUTION!
No Local Loop Devices
(VAV/Zone Controllers,
System Manager(s) Etc..)
Can Be Connected To The
Same Power/Comm Board(s)
That Are Used To Supply
Power And Communications
For MinLink PDs On The
Network Loop.
25
4A
D1
V1
OUT
COMM POWER&
Note:
Diagram Shown Is For Wiring When
Power/Comm Board Is Used For
Connection Of MiniLink Polling
Devices On The Network Loop.
For Wiring Of Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards On The Local
Loop See Page 1 Of This Drawing
For Wiring .
Network Loop RS-485
19200 Baud
66
Connect Power/Comm Cables To Other Power/Comm
Or MiniLink PDs On The Network Loop Only.
Distribution Board,
Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
2.) All modular power/comm cables are to be WattMaster part number
PCC-xx or PCCE-xx cables. All other communication wiring to be 2 conductor twisted pair with shield (Belden #82760 or equivalent).
JOB NAME
FILENAME
O-Pwr-CommWire1A.CDR
DATE:
PAGE
2 of 2
02/11/004
DRAWN BY:
B. Crews
DESCRIPTION:
OE365-01 Orion Power/Comm Board
Component Wiring Diagram
Component & System Wiring
RS-232 Serial Port To USB Port Converter
Cable Length = 12 inches
Features & Specifications
:
Converts a USB port into a 9-pin male RS-232 serial port capable of speeds up to 115 Kbps.
The USB Serial Adapter is designed to make serial port expansion quick and simple.
Installs as a standard Windows COM port,
Full RS-232 modem control signals,
RS-232 data signals; TxD, RxD, RTS, CTS, DSR, DTR, DCD, RI,
GND
Self Powered by USB port
Supports Windows 98/SE, ME & 2000 and XP
Packages Includes
:
USB-232 Converter cable with short 12inch USB Type A end
Installation Instructions
USB Driver CD for win98/ME/2K/XP
Top View
End View
SERIAL #
REMOTE LINK
(DTE)
CommLink
COMPUTER
(DCE)
T G R
9 Pin
Female
Connect 9 Pin Serial
Cable Supplied With
CommLink To Port
Labeled “Computer (DCE)
On CommLink As Shown
9 Pin Serial Cable
Assembly Supplied With
CommLink
Connect 9 Pin Serial
Cable Supplied With
CommLink To USB
Serial Adapter As Shown
Installing the USB adapter
Follow the instructions provided inside the USB Serial Adapter package for installation and driver setup of the USB Serial Adapter.
A CD-ROM is included that contains the correct drivers.
Changing the COM ports:
To change the COM port to a different COM port is accomplished by changing the COM port I/O range in the Windows Device
Manager.
Right-click on "My Computer"
Click the "Device Manager" tab.
Click the "+" by "Ports"
Select "USB to Serial Port (COM5)"
Click the "Properties" button
Click the "Resources" Tab.
Uncheck the box that says "Use automatic settings".
Select the "Input/Output range"
Click the "Change Settings " button.
Click the little arrows until you find an appropriate setting.
"02E8-02EF" should give you a COM4 setting after you restart the computer.
Make sure to click "OK" on all screens.
Use the following settings to get the following COM ports:
COM1 - 3F8h-03FFh
COM2 - 2F8h-02FFh
COM3 - 3E8h-03EFh
COM4 - 2E8h-02EFh
USB Serial
Adapter
Connection Detail
Component & System Wiring
Connect To
USB Port
On Computer
JOB NAME
FILENAME
USB-RS232Cnvrt1A.CDR
C O N T R O
DATE: 08/20/03
PAGE
1
DRAWN BY:
DESCRIPTION:
B. CREWS
OE299
RS-232 to USB Converter
L S
67
68 Component & System Wiring
Add-On Devices Diagrams
Component & System Wiring 69
Lighting Panel Wiring For Standard Lighting Contactors
Required VA For Transformer
Each Controller = 25VA Max.
See Note 1
Caution: If Lighting Contactor Coil Current
Draw Is More Than 2 Amps And/Or Does
Not Use A 24VAC Coil, A Pilot Duty Relay
That Has A Current Draw Of Less Than 2
Amps @ 24VAC Must Be Used To Energize
The Lighting Contactor. A Separate
Transformer Rated For The Total Lighting
Contactor(s)Or Pilot Relay Current Draw
Must Always Be Used To Power The Circuit.
Line Voltage
Light Sensor (Optional)
GND
Line Voltage
24V
Lighting Contactors Or
Pilot Duty Relays
(By Others)
Light Circuit 1
C1
Light Circuit 2
C2
Light Circuit 3
C3
Light Circuit 4
C4
Light Circuit 5
C5
Light Circuit 6
C6
Light Circuit 7
C7
!
!
Note:
!
All Circuit Board Contacts Are N.O.
All Contacts Are Rated For 2 Amps @
24VAC Pilot Duty Only
Do Not Apply Any Voltage Greater Than
24VAC
All Lighting Contactors
Must Be Wired For N.C.
Operation So That System
Fails To Lights On Mode.
This Switch Must Be
In The ON Position
As Shown
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop
24VAC
GND
K1
K2
K3
K4
K5
K6
K7
These Switches Should Be
In The OFF Position
As Shown
CPU
PAL
Lighting Panel Controller
ANALOG
INPUTS
+V
+V
1
2
7
8
G
G
3
4
5
6
ANALOG
OUTPUTS
A1
A2
G
T
SH
R
T
SH
R
Momentary Pushbuttons
(Optional)
Override Circuit #1
Override Circuit #2
Override Circuit #3
Override Circuit #4
Override Circuit #5
Override Circuit #6
Override Circuit #7
Local Loop RS-485
Communications To Other
Controllers On The Local
Loop
Note:
Set-up, Programming And Monitoring Of The Lighting
Panel Controller Requires The Use Of A Personal
Computer And Prism Software.
ADD
ADD
70
Controller
Address Switch
Address Switch Shown Is
Set For Address 1
Address Switch Shown Is
Set For Address 13
Caution!
Controller Must Have Address Switch Set Between 1 And 60
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
JOB NAME
FILENAME
O-LightingPnlStd1.CDR
DATE:
PAGE
1
02/12/04
DRAWN BY:
B. Crews
DESCRIPTION:
OE310 Lighting Panel Controller Wiring
Using Standard Lighting Relays
Component & System Wiring
Lighting Panel Wiring For GE
®
Latching Relay Lighting Contactors
Required VA For Transformer
Each Controller = 25VA Max.
See Note 1
Line Voltage
Caution: If Lighting Contactor Coil Current Draw Is More Than 2
Amps And/Or Does Not Use A 24VAC Coil, A Pilot Duty Relay
That Has A Current Draw Of Less Than 2 Amps @ 24VAC Must
Be Used To Energize The Lighting Contactor. A Separate
Transformer Rated For The Total Lighting Contactor(s) Or Pilot
Relay Current Draw Must Always Be Used To Power The Circuit.
Light Sensor
(Optional)
Typical Wiring Shown For Circuit #1
All Other Circuits Are To Be Wired
Identically. Up to 7 Lighting Circuits May
Be Wired To Each Lighting Panel Controller.
Line Voltage
Light Circuit 1
Light Circuit 2
Light Circuit 3
24VAC
GND
K1
K2
K3
CPU
7
8
5
6
3
4
G
G
ANALOG
INPUTS
+V
+V
1
2
ANALOG
OUTPUTS
A1
A2
G
Momentary Pushbuttons
(Optional)
Override Circuit #1
!
!
Note:
!
All Circuit Board
Contacts Are N.O.
All Contacts Are
Rated For 2 Amps
@ 24VAC Pilot
Duty Only
Do Not Apply Any
Voltage Greater
Than 24VAC
Override Circuit #2
Override Circuit #3
Override Circuit #4
Override Circuit #5
Override Circuit #6
Override Circuit #7
Note:
Set-up, Programming
And Monitoring Of
The Lighting Panel
Controller Requires
The Use Of A
Personal Computer
And PrismSoftware.
Light Circuit 4
K4
Light Circuit 5
K5
Light Circuit 6
K6 PAL
Light Circuit 7
K7
T
SH
R
T
SH
R
All switches
(1 thru 4) must be in the
“ON” position
Lighting Panel Controller
OFF
24VAC
ON
GE Lighting Relay- Circuit #1
(By Others)
This Switch Must Be
In The ON Position
As Shown
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop
ADD
Local Loop RS-485
Communications To Other
Controllers On The Local
Loop
These Switches Should Be
In The OFF Position
As Shown
ADD
R4
R5
R6
R7
R8
R1
R2
R3
Light Circuit 1
Light Circuit 2
Light Circuit 3
Light Circuit 4
Light Circuit 5
Light Circuit 6
Light Circuit 7
Ground
24V
Ribbon Connector
Relay Expansion Board
Controller
Address Switch
Address Switch Shown Is
Set For Address 1
Address Switch Shown Is
Set For Address 13
Caution!
Controller Must Have Address Switch Set Between 1 And 60
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
JOB NAME
FILENAME
O-LightingPnl-GE1.CDR
DATE:
PAGE
1
02/12/04
DRAWN BY:
B. Crews
DESCRIPTION:
OE310 Lighting Panel Controller Wiring
Using GE Latching Relays
Component & System Wiring 71
GPC-17 Controller Wiring
Required VA For Transformer
Each Controller = 25VA Max.
Line Voltage
Line Voltage
See Note 1
Relay Outputs
To Devices As
Required
By Application
24VAC
GND
K1
K2
K3
K4
K5
K6
K7
CPU
PAL
ANALOG
INPUTS
5
6
7
3
4
+V
+V
1
2
8
G
G
ANALOG
OUTPUTS
A1
A2
G
T
SH
R
T
SH
R
Analog Inputs And/Or
Digital Inputs
From Devices As
Required By
Application
!
!
Note:
!
All Circuit Board
Contacts Are N.O.
All Contacts Are
Rated For 2 Amps
@ 24VAC Pilot
Duty Only
Do Not Apply Any
Voltage Greater
Than 24VAC
Note:
Set-up, Programming
And Monitoring Of
The GPC-17
Controller Requires
The Use Of A
Personal Computer
And Prism Software.
All switches
(1 thru 4) must be in the
“ON” position
Ribbon Connector
GPC-17 Controller
Local Loop RS-485
Communications To Other
Controllers
And/Or System Manager
Optional Relay Expansion Board
R4
R5
R6
R7
R8
R1
R2
R3
Ground
24V
Ribbon Connector
Relay
Outputs to
Devices
As
Required
By
Application
This Switch Must Be
In The ON Position
As Shown
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop
ADD
These Switches Should Be
In The OFF Position
As Shown
ADD
Address Switch Shown Is
Set For Address 1
Controller
Address Switch
Address Switch Shown Is
Set For Address 13
Caution!
Controller Must Have Address Switch Set Between 1 and 60
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
72
PWR
Analog Output
To Device
(0-10 VDC)
ANALOG OUT1
+
-
ANALOG OUT2
+
-
ANALOG OUT3
+
-
ANALOG OUT4
+
-
RN1
JOB NAME
Optional
Analog
Output
Board
FILENAME
O-GPC-17CNTRL1A.CDR
DATE:
PAGE
1
02/12/04
DRAWN BY:
B. Crews
DESCRIPTION:
OE310-21-GPC
GPC-17 Controller
Component & System Wiring
GPC Plus Wiring
All Communication Loop Wiring Is
Straight Through
T To T, R To R, SHLD To SHLD
Connect To
Next Device On
The Local Loop
Local Loop RS-485
9600 Baud
Mini DIN Connector
For Connection Of Modular
Service Tool
Pull-up Resistor- Typical
Analog Inputs AIN1Thru AIN7
Can Be Used For 10kOhm
Type III Thermistor, 0-5VDC
Signal, 4-20mA Signal Or Dry
Contact Closure Inputs.
As Required.
Note: When Using Sensors or
Transducers With 4-20 mA Input
Signal, The Pull-up Resistor For
The Input Being Used Must Be
Removed From The Controller
Board And A 250 Ohm Resistor
Must Be Wired Between The Input
Terminal And The Ground Terminal
On The Controller Board
OE331-21-GPCPLUS
GPC Plus Controller
U3
1
RN1
CX1
U1
U2
CX2
U4
CX4
TB1
COMM
T
SHLD
R
CX5
U5
LD6
COMM
LD7
PWR
1
RS-485
COMM
HH
RAM
LD8
LED1
C1
R1
LD9
LED2
U7
RV1
P1
+VREF
5.11V
TEST POINT
VREF ADJ
EWDOG
R28
INPUTS
ADDRESS
TB3
+VDC
AIN1
AIN2
AIN3
AIN4
RN5
AIN5
GND
C10
GND
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
U6
C20
ADD
4
8
2
1
16
32
TOKEN
NETWORK
JP1
X2
R15
C14
R19
C15
R22
R24
R25
CX15
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
U10
U14
CX10
U12
CX14
CX6
CX12
PRESSURE
SENSOR
R26
EXPANSION T'STAT
1
U9
PAL
VR1
C7
1
D12
R13
SC1
D19
L1
VR2
Not Used
Splice If Req’d
Analog Input AIN6 Can Only Be Used
For Connection Of A Static Pressure
Transducer With Modular Connector
Connect To
Expansion Board
Base (When Used)
Warning:
24 VAC Must Be Connected So That All
Ground Wires Remain Common. Failure To
Do So Will Result In Damage To The
Controller
S.P.
Transducer
D3
R14
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
9936
MC34064A
U8
NE5090NPB3192
0PS
R6
C9
C13
C16
TB4
GND
24VAC
PWR LD1
Connect Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere
4 Additional Relay Outputs
Are Available By Using The
OE357 4 Relay Output
Expansion Board. The
OE352 2 Slot Expansion
Base Board Is also
Required To Mount The
OE357 Board.
AC AC UL5A250V UL5A250V
CONTACT
G5L-114P
24VDC
OMRON
-PS
OMRON
-PS
AC AC UL5A250V UL5A250V
CONTACT
G5L-114P
24VDC
AC AC
-PS
AC AC
-PS
YS101790
OMRON
24VDC
UL5A250V UL5A250V
CONTACT
G5L-114P
OMRON
UL5A250V UL5A250V
CONTACT
G5L-114P
24VDC
K1
K2
K3
RN1
K4
LM358N LM358N
GND
Line Voltage
24VAC
24VAC Transformer
10 VA Mini mum
74HC04N
ULN2803A/
PCF8574P
24VAC Power
For Relay Outputs
5 Relay Outputs Are
Available On Board For
On/Off Control Of
Equipment. When
Required 4 Additional
Relay Outputs Are
Available By Using The
Optional OE357 4 Relay
Output Expansion
Board. See Below.
U1
U2
CX3
OE357
4 Relay Output
Board
YS101780
I/O I/O OTMODULAR TMODULAR LO 2SL 2S
R5
R4
R6
Jumper
Setting
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
OE352 2 Slot Expansion Base Board
JOB NAME
FILENAME
G-GPC-PlusCNTRL1A.CDR
DATE:
PAGE
1 Of 2
03/08/05
DRAWN BY:
B. Crews
DESCRIPTION:
OE331-21-GPCPLUS
GPC Plus Controller
Component & System Wiring 73
GPC Plus Controller - Address Switch Setting
This Switch Should Be
In The OFF Position
As Shown
ADDRESS
ADDRESS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
ADDRESS
ADD
ADD
Note:
The Power To The Controller Must Be Removed
And Reconnected After Changing The Address
Switch Settings In Order For Any Changes To
Take Effect.
Caution
Disconnect All Communication Loop Wiring
From The Controller Before Removing Power
From The Controller. Reconnect Power And
Then Reconnect Communication Loop Wiring.
Address Switch Shown Is
Set For Address 1
Controller
Address Switch
Address Switch Shown Is
Set For Address 13
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop.
For Auto-Zone Systems The Address Must Be
Set Between 18 to 30
For All Other Systems The Address Can Be Set
Between 1 to 59
INPUTS
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
C10
GND
AOUT1 C12
AOUT2
AIN7
GND
PJ1
C17
D15
D9
PU5
D11
PU7
D14
PU1
D6
PU2
D7
PU3
D8
PU4
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
JP1
X2
U13
CX13
U15
R15
CX10
U12
C14
R19
U14
CX14
C15
R22
R24
R25
C20
CX15
CX12
R26
PRESSURE
SENSOR
EXPANSION
VR1
C7
D12
R13
SC1
D19
L1
VR2
R6
C9
C13
C16
TB4
GND
24VAC
JOB NAME
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
74
FILENAME
G-GPC-PlusCNTRL1A.CDR
DATE:
PAGE
2 Of 2
03/08/05
DRAWN BY:
B. Crews
DESCRIPTION:
OE331-21-GPCPLUS
GPC Plus Controller
Component & System Wiring
GBD Controller - CO2 Apllications Wiring
Connect The GBD To
The Same Local
Communications Loop
As The Controller
That Will Be
Receiving the GBD
Broadcast
GBD Device
Communications Wire
Must Be 2 Conductor
Twisted Pair With
Shield, Belden #82760
Or Equivalent.
All Wiring Must Be
Straight Through,
R To R, T To T And
SHLD To SHLD.
Available Inputs
For Connection
4-20mA Signal
See Page 2 For
Detailed CO
2
Sensor Wiring
Available
0-10 VDC
Proportional
Output Signal
Available
10 VDC Fixed
Output Signal
U3
1
RN1
CX1
U1
U2
CX2
CX4
U4
RLY1
TB1
COMM
T
SHLD
R
CX5
RLY2
U5
PAL
COMM
PWR
1
RS-485
COMM
HAND
HELD
RAM EPROM
TUC-5R/5R-PLUS
(1 MEG)
YS101816 REV 4
RLY3
LED1
U6
R1
LED2
RN3
+VREF
C1
U7
TEST POINT
5.11V
RV1
VREF ADJ
R28
INPUTS
TB3
ADDRESS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
C4
RN5
GND
AOUT1
AOUT2
AIN7
GND
C17
C10
C12
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
PJ1
JP1
1
2
4
8
16
32
TOKEN
NETWORK
X2
C20
CX10
R15
C14
R19
C15
R22
R24
R25
U14
U12
CX14
CX15
U10
CX12
R26
PRESSURE
SENSOR
T'STAT
EXPANSION
CX6
1
U9
VR1
D12
R13
SC1
RLY4
RLY5
C7
D19
L1
VR2
M
C13
U11
R6
U8
C9
9936
MC34064A
C16
V1
R1
R2
R3
R4
R5
V5
TB2
V4
TB4
GND
24VAC
Note:
All Relay Contacts
Are N.O. & Rated
For 2 Amps
Maximum @ 24VAC
Available Relay #1
24 VAC Output
Closes On Rise
Above Minimum
24 VAC Pilot Duty
Relay (By Others)
Available Relay #2
24 VAC Output
Closes On Rise
Above Maximum
GND
24VAC
R1
24 VAC Pilot Duty
Relay (By Others)
R2
OE331-21-AVG
GBD Device Wiring
Line Voltage
24 VAC Transformer
20VA Minimum
Notes:
1.) The GBD Can Either Be Used
With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD Device.
Up to 2 GBD Devices Can Be
Located On Each Local Loop.
2.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
Component & System Wiring
OE331-21-AVG-GBD-Wire1A.CDR
DATE:
PAGE
1 of 5
10/07/05 DRAWN BY:
B. CREWS
DESCRIPTION:
OE331-21- AVG
GBD Device Wiring
75
GBD Controller - CO2 Applications Wiring (Cont’d)
The Pullup Resistor For The Analog
Be Used On The GBD.
They Can Be Wired
To AIN1, AIN2, AIN3, AIN4,
AIN5 And AIN7 As
Desired. Only 4-20mA
Used.
250 Ohm-1%
Resistor Supplied
INPUTS
TB3
+VDC
AIN1
C4
RN5
AIN2
AIN3
AIN4
AIN5
GND
C10
GND
AOUT1
AOUT2
AIN7
C17
GND
PJ1
C12
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
To Must Be Removed For Proper
Operation Of The GBD Device.
Warning
:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
JP1
X2
24 VAC Transformer
20VA Minimum
TB4
GND
C20
Must Be Wired
As Shown For
Each Sensor Used
PRESSURE
SENSOR
CX15
24VAC
EXPANSION T'STAT
VR1
VR2
GBD Device
Typical Wiring
Shown For Input
AIN3. Wiring For
Other Inputs Is
Identical.
OE255 or OE256
(4-20mA Signal)
Pin Designations
1. - Not Used
2. - Not Used
3. Relay Norm Open
4. Relay Common
5. Relay Norm Closed
6. 4-20mA Output
7. Signal Ground
8. 0-10V Output
GND
24VAC
Pin Designations
1. AC+/DC+
2. AC/GND
OE331-21-AVG
GBD Device Wiring
76
Notes:
1.) The GBD Can Either Be Used
With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD Device.
Up to 2 GBD Devices Can Be
Located On Each Local Loop.
2.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
3.) Set-up, Programming And
Monitoring Of The GBD Device
Requires The Use Of A Personal
Computer And Prism Software.
4.) All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
OE331-21-AVG-GBD-Wire1A.CDR
DATE:
PAGE
2 of 5
10/07/05 DRAWN BY:
B. CREWS
DESCRIPTION:
OE331-21- AVG
GBD Device Wiring
Component & System Wiring
GBD Controller - Space Temp. Sensor Averaging Wiring
Connect The GBD To
The Same Local
Communications Loop
As The Controller
That Will Be
Receiving the GBD
Broadcast
GBD Device
Communications Wire
Must Be 2 Conductor
Twisted Pair With
Shield, Belden #82760
Or Equivalent.
All Wiring Must Be
Straight Through,
R To R, T To T And
SHLD To SHLD.
Available Inputs
For Connection of
Space Temperature
Sensors. See Page
4 For Detailed
Space Temperature
Sensor Wiring
U3
1
RN1
CX1
U1
U2
CX2
CX4
U4
RLY1
TB1
COMM
T
SHLD
R
CX5
RLY2
U5
PAL
COMM
PWR
1
RS-485
COMM
HAND
HELD
RAM EPROM
TUC-5R/5R-PLUS
(1 MEG)
YS101816 REV 4
RLY3
LED1
U6
R1
LED2
RN3
+VREF
C1
U7
TEST POINT
5.11V
RV1
VREF ADJ
R28
INPUTS
TB3
ADDRESS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
C4
RN5
GND
AOUT1
AOUT2
AIN7
GND
C17
C10
C12
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
PJ1
JP1
1
2
4
8
16
32
TOKEN
NETWORK
X2
C20
CX10
R15
C14
R19
C15
R22
R24
R25
U14
U12
CX14
CX15
U10
CX12
R26
PRESSURE
SENSOR
T'STAT
EXPANSION
CX6
1
U9
VR1
D12
R13
SC1
RLY4
RLY5
C7
D19
L1
VR2
M
C13
U11
R6
U8
9936
R1
R2
R3
R4
R5
C9
MC34064A
V5
TB2
C16
V1
V4
TB4
GND
24VAC
GND
24VAC
OE331-21-AVG
GBD Device Wiring
When Used For Space Temperature Sensor Averaging Applications
Line Voltage
24 VAC Transformer
20VA Minimum
Notes:
1.) The GBD Can Either Be Used
With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD Device.
Up to 2 GBD Devices Can Be
Located On Each Local Loop.
2.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
3.) Set-up, Programming And
Monitoring Of The GBD Device
Requires The Use Of A Personal
Computer And Prism Software.
4.) All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
Component & System Wiring
OE331-21-AVG-GBD-Wire1A.CDR
DATE:
PAGE
3 of 5
10/07/05 DRAWN BY:
B. CREWS
DESCRIPTION:
OE331-21- AVG
GBD Device Wiring
77
GBD Controller - Space Temp. Sensor Averaging Wiring (Cont’d)
Up to (6) Temperature Sensors
Can Be Used On The GBD.
They Can Be Wired
To AIN1, AIN2, AIN3, AIN4,
AIN5 And AIN7 As
Desired.
Typical Wiring
Shown For Input
AIN3. Wiring For
Other Inputs Is
Identical.
INPUTS
TB3
+VDC
AIN1
C4
RN5
AIN2
AIN3
AIN4
AIN5
GND
C10
GND
AOUT1
AOUT2
AIN7
C17
GND
PJ1
C12
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
JP1
X2
Warning
:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
24 VAC Transformer
20VA Minimum
TB4
GND
C20
CX15
24VAC
PRESSURE
SENSOR
EXPANSION T'STAT
GBD Device
VR1
VR2
OE210 Space Temperature Sensor
TMP
GND
OE331-21-AVG
GBD Device Wiring
When Used For Space Temperature Sensor Averaging Applications
78
Notes:
1.) The GBD Can Either Be Used
With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD Device.
Up to 2 GBD Devices Can Be
Located On Each Local Loop.
2.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
3.) Set-up, Programming And
Monitoring Of The GBD Device
Requires The Use Of A Personal
Computer And Prism Software.
4.) All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
OE331-21-AVG-GBD-Wire1A.CDR
DATE:
PAGE
4 of 5
10/07/05 DRAWN BY:
B. CREWS
DESCRIPTION:
OE331-21- AVG
GBD Device Wiring
Component & System Wiring
GBD Controller Adress Switch Setting
This Switch Should Be
In The OFF Position
As Shown
ADDRESS
ADDRESS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
ADDRESS
ADD
ADD
Controller
Address Switch
Address Switch Shown Is
Address Switch Shown Is
Set For Address 1
Set For Address 13
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 60
Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Caution
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.
INPUTS
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
C10
C12
AOUT2
AIN7
GND
PJ1
C17
D15
C20
D8
PU4
D9
PU5
D11
PU7
D14
PU1
D6
PU2
D7
PU3
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
U13
CX13
U15
CX15
U10
CX10
R15
C14
R19
U14
U12
CX14
C15
R22
R24
R25
CX12
R26
PRESSURE
SENSOR
EXPANSION
VR1
C7
D12
R13
SC1
D19
L1
VR2
R6
C9
C13
C16
TB4
GND
24VAC
Notes:
1.) The GBD Can Either Be Used
With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD Device.
Up to 2 GBD Devices Can Be
Located On Each Local Loop.
2.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
3.) Set-up, Programming And
Monitoring Of The GBD Device
Requires The Use Of A Personal
Computer And Prism Software.
4.) All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
Component & System Wiring
OE331-21-AVG-GBD-Wire1A.CDR
DATE:
PAGE
5 of 5
10/07/05 DRAWN BY:
B. CREWS
DESCRIPTION:
OE331-21- AVG
GBD Device Wiring
79
80 Component & System Wiring
Miscellaneous Diagrams
& Technical Information
Component & System Wiring 81
Modular Room Sensor Wiring
2.75“
0.88“
OVR
C
O
O
L
E
R
W
A
R
M
E
R
2.00“
YS101858
REV 0
THERM1
PJ1
R2
R1
0.25“
Room Sensor Typical Dimensions
Wall Cut-Out Dimensions
When Sensor Is To Be
Mounted Without
Handy Box (By Others)
OVR
W
A
R
M
E
R
C
O
O
L
E
R
OVR
W
A
R
M
E
R
C
O
O
L
E
R
OE210-02
Modular Room Sensor -
Plain
Temp
°
F
Resistance* Voltage
Ohms @ Input*
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822 ........4.474
5 ...............60552 ........4.390
10 ..............52500 ........4.297
15 ..............45902 ........4.200
20 ..............40147 ........4.095
25 ..............35165 ........3.982
30 ..............30805 ........3.862
35 ..............27140 ........3.737
40 ..............23874 ........3.605
OE211-02
Modular Room Sensor
With Override
OE212-02
Modular Room Sensor
With Setpoint Adjust
Temperature Sensor Resistance/Voltage Chart
Temp
°
F
Resistance* Voltage
Ohms @ Input*
45 ..............21094 ........3.470
50 ..............18655 ........3.330
52 ..............17799 ........3.275
54 ..............16956 ........3.217
56 ..............16164 ........3.160
58 ..............15385 ........3.100
60 ..............14681 ........3.042
62 ..............14014 ........2.985
64 ..............13382 ........2.927
66 ..............12758 ........2.867
68 ..............12191 ........2.810
Temp
°
F
Resistance* Voltage
Ohms @ Input*
69 ..............11906 ........2.780
70 ..............11652 ........2.752
71 ..............11379 ........2.722
72 ..............11136 ........2.695
73 ..............10878 ........2.665
74 ..............10625 ........2.635
75 ..............10398 ........2.607
76 ..............10158 ........2.570
78 ..............9711 ..........2.520
80 ..............9302 ..........2.465
82 ..............8893 ..........2.407
Temp
°
F
Resistance* Voltage
Ohms @ Input*
84 ..............8514 ..........2.352
86 ..............8153 ..........2.297
88 ..............7805 ..........2.242
90 ..............7472 ..........2.187
95 ..............6716 ..........2.055
100 ............6047 ..........1.927
105 ............5453 ..........1.805
110 ............4923 ..........1.687
115 ............4449 ..........1.575
120 ............4030 ..........1.469
OE213-02
Modular Room Sensor
With Setpoint Adjust
& Override
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered). Connect as shown below.
82
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the sensor leads as shown in the illustration below. If the voltage is above 5.08 VDC, then the sensor or wiring is "open." If the voltage is less than 0.05
VDC, the sensor or wiring is shorted.
JOB NAME
+
MODULAR
SENSOR
FILENAME
O-MODRMSENS1.CDR
-
+
T
SHLD
-
DATE:
PAGE
1
10/11/01 DRAWN BY:
DESCRIPTION:
B. CREWS
OE210-02, OE211-02, OE212-02, OE213-02
Modular Room Sensor
Component & System Wiring
Over Voltage Board Wiring
OE-268 Over Voltage Board
NOTE: This board goes between the supply transformers low voltage output and the controllers low voltage input.
WattMaster Controllers do not like to see more than
28 VAC on their input side. When the line voltage to the transformer is too high, generally the output side of the transformer (low voltage) is too high, thus requiring this
Over Voltage Board.
+
HV POWER BD.
YS101750
REV 1.0
C2
D1
R3
AC_IN GND
TB1
INPUT
24-32VAC
R2
C3
TRANSFORMER
D2
U1
R1
+
+V GND
TB2
POWER
OUTPUT
Note:
This output is DC voltage. Our controllers will accept DC voltage if the voltage is above 28 VDC.
Warning
This board is designed to power one controller with expansion boards only.
To the 24 VAC input side of WattMaster Controller
LINE VOLTAGE
Component & System Wiring
JOB NAME
FILENAME
OE268-OVBoard.cdr
DATE:
PAGE
C O N T R O L
8/9/02
DRAWN BY:
Barry Light
DESCRIPTION:
OE-268 Over Voltage Board
S
1
83
MODGAS II Controller Wiring When Used With The VCM Controller
84
Note:
1.) When The MODGAS II Controller Is Used With The VCM
Controller It Must Have (1) Relay Output On The VCM Controller
Configured For The MODGAS II Controller In Order To Function
Correctly. This Relay Output Must Be Configured When Setting-up
The Controller(s) Operating Parameters. See the VCM Controller
Operator Interfaces Technical Guide For Complete Controller
Programming and Configuration Information.
Low Speed
CR2
Hi Speed
CR1
Supply
Air Temp.
Sensor
Mount In
Unit Supply
Air Duct
Heat Enable
Signal (24 VAC)
W1
K3
K2 FT
K1
TB1
COM
AUX
LO SPD
FAN
O
F
F
R4
O
F
F
STATUS
GND
AUX IN
HEAT EN
RST IN
SAT
+VDC
R3
R1
R1
P
D2
R9
R8
D1
R7
P
VR1
CX2
POWER
R1
1
C7
U5
D9
V5
VOUT
GND
C13
TB4
2 Gas
Valves Can
Be Connected
As Shown
GV2
GV1
40 VA
Transformer
Minimum
I2C IN
Line
24VAC
GND
Modular Cable Connects To
HVAC Unit Controller
L1
L2
CR1-B
N.C.
CR1-A
N.O.
CR2-1
SC
Speed
Control
Motor
N.O.
Induced
Air Blower
Caution:
If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply Air Temperature Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the Supply Air Temperature Sensor must be connected to the MHGRV II controller. If you have either of these controllers on your HVAC unit and have a Supply Air Temperature Sensor connected to the VCM controller, your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on an HVAC unit.
Wiring For MODGAS II When Used With Orion VCM Controller
JOB NAME
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
FILENAME
O-MODGASII-VCM-Wr1.CDR
DATE:
PAGE
1
03/09/06
DRAWN BY:
B. Crews
DESCRIPTION:
AAON MODGAS II Wiring
When Used With Orion VCM Controller
Component & System Wiring
MODGAS II Controller Wiring With HVAC Unit Controls By Others
D9
V5
VOUT
GND
TB4
C13
2 Gas
Valves Can
Be Connected
As Shown
GV2
GV1
Line
40 VA
Transformer
Minimum
24VAC
GND
Low Speed
CR2
Hi Speed
CR1
Supply
Air Temp.
Sensor
Mount In
Unit Supply
Air Duct
Heat Enable
Signal (24 VAC)
W1
0-10VDC
External Reset
Signal
-
+
L1
CR1-B
N.O.
K3
K2 FT
K1
TB1
COM
AUX
LO SPD
FAN
O
F
F
R4
O
F
F
STATUS
GND
AUX IN
HEAT EN
RST IN
SAT
+VDC
R3
R1
R1
P
D2
R9
R8
D1
R7
P
VR1
CX2
POWER
R1
1
C7
U5
I2C IN
N.C.
CR2-1
SC
Speed
Control
Motor
Induced
Air Blower
CR1-A
N.O.
L2
Wiring For MODGAS II When HVAC Unit Controls Are By Others
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
Component & System Wiring
JOB NAME
FILENAME
O-MODGASII-No-Wire1.CDR
DATE:
PAGE
1
02/17/04 DRAWN BY: B. Crews
DESCRIPTION:
AAON MODGAS II Wiring
When Used Without Orion Controls
85
MHGRV II Controller Wiring When Used With VCM Controller
Fan
C1
Compressor
C2
HGR Solenoid Valve
2 Position HGR Valve (Optional)
Reheat
Modulating
HG Valve
Green
Red
White
Black
Condensor
Modulating
HG Valve
Green
Red
White
Black
Mount In Supply
Air Duct
See Caution Note
Below
Supply
Air Temperature
Sensor
Modular Cable
Connect To
HVAC Unit
Controller
“AUX” Relay LED
“VALVE” Relay LED
“COMP” Relay LED
“FAN” Relay LED
YS101894 REV 1
HOT GAS REHEAT
SERIAL #
24 VAC
R23
CX5
TB3
R2
CG/HR
CR/HG
CW/HW
CB/HB
U1
+VDC
GND
GND
AUX IN
RST IN
RHT EN
HTG OVR
CLG OVR
GND
SAT
T
SHLD
D2
R4
PU
R12
R
R17
VR1
R9
R8
D4
R13
R7
D3
R6
R5
D6
R11
R1
D5
R3
R3
CX2
R1
1
D1
R20
C12
ADD
1
2
4
8
16
32
64
128
RESET LIMIT
ADD
1
2
4
8
16
32
64
128
SETPOINT
R40
R39
PJ1
R18
R19
R31
D11
R38
GND
+24VAC
TB4
Reset Limit
DIP Switch
(Not Used
For This
Application)
Setpoint
DIP Switch
(Not Used
For This
Application)
“POWER” LED
“STATUS” LED
EPROM Chip
RAM Chip
86
Caution:
If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply
Air Temperature Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the Supply Air Temperature Sensor must be connected to the MHGRV II controller.
If you have either of these controllers on your HVAC unit and have a Supply Air Temperature Sensor connected to the VCM controller, your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on an HVAC unit.
Wiring For MHGRVII When Used With Orion VCM Controller
40 VA
Transformer
Minimum
Line
JOB NAME
Notes:
1.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
FILENAME
O-AAON-MHGRVII-VCM1A.CDR
DATE:
PAGE
1
03/09/06 DRAWN BY: B. Crews
DESCRIPTION:
AAON MHGRV II Controller
When Used With Orion VCM Controller
Component & System Wiring
MHGRV II Controller Wiring With HVAC Unit Controls By Others
Fan
C1
Compressor
C2
HGR Solenoid Valve
2 Position HGR Valve (Optional)
Reheat
Modulating
HG Valve
Green
Red
White
Black
Condensor
Modulating
HG Valve
Green
Red
White
Black
0-10VDC
External Reset
Signal
+
-
H1 (Dehumidification)
Heating Override
Cooling Override
Mount In Supply
Air Duct
“AUX” Relay LED
“VALVE” Relay LED
“COMP” Relay LED
“FAN” Relay LED
YS101894 REV 1
HOT GAS REHEAT
SERIAL #
24 VAC
R23
CX5
TB3
R2
CG/HR
CR/HG
CW/HW
CB/HB
U1
+VDC
GND
GND
AUX IN
RST IN
RHT EN
HTG OVR
CLG OVR
GND
SAT
T
SHLD
D2
R4
PU
R12
R
R17
R9
R8
D4
R13
R7
D3
R6
R5
VR1
D6
R11
R1
D5
R3
R3
CX2
R1
1
D1
R20 C12
ADD
1
2
4
8
16
32
64
128
RESET LIMIT
ADD
1
2
4
8
16
32
64
128
SETPOINT
R40
R39
PJ1
R18
R19
R31
D11
R38
GND
+24VAC
TB4
Reset Limit
DIP Switch
(Not Used
For This
Application)
Setpoint
DIP Switch
(Not Used
For This
Application)
“POWER” LED
“STATUS” LED
EPROM Chip
RAM Chip
Supply
Air Temperature
Sensor
40 VA
Transformer
Minimum
Wiring For MHGRV II When HVAC Unit Controls Are By Others
Line
JOB NAME
Notes:
1.)All Wiring To Be In Accordance With
Local And National Electrical Codes and Specifications.
FILENAME
O-SA-MHGRVII-Wire1a.CDR
DATE:
PAGE
1
02/17/04
DRAWN BY:
B. Crews
DESCRIPTION:
AAON MHGRV II Controller
When Used Without Orion Controls
Component & System Wiring 87
Supply Air Sensor Location & Wiring
VCMBoard
U2 CX2 U3 CX3
CX4
LD1
1
RN1
CX1
U1
U4
RELAY1
TB1
COMM
T
SHLD
LD2
RELAY2
R
LD6
CX5
U5
COMM
RS-485
COMM
RAM EPROM
LD7
PWR
1
TUC-5R PLUS
YS101718 REV. 3
U6
LD8
LED1
C1
LD9
LED2
R1
+VREF
5.11V
TEST POINT
CX6
U7
INPUTS
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
RV1
VREF ADJ
+VDC
GND
C4
RN5
C10
EWDOG
R28
1
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
JP1
X2
CX10
CX12
U9
AOUT1
C12
U13
R15
TB3
AOUT2
AIN
7
GND
C17
PJ1
D15
U15
CX13
C14
R19
C15
R22
R24
R25
U14
U12
CX14
C20
PAL
1
RELAY3
C7
D12
R13
SC1
D19
LD3
LD4
RELAY4
LD5
RELAY5
L1
R26
PRESSURE
SENSOR
EXPANSION
T'STAT
VR1 VR2
R6
R1
R2
R3
R4
R5
U8
C9
V1
V2
V3
TB2
V4
V5
C13
C16
TB4
GND
24VAC
TB3
R2
CG/HR
CR/HG
CW/HW
CB/HB
U1
+VDC
GND
GND
AUX IN
RST IN
RHT EN
HTG OVR
CLG OVR
GND
SAT
T
D2
R4
PU
R12
SHLD
R
PJ1
MHGRV II Board
YS101894 REV 1
HOT GAS REHEAT
SERIAL #
R17
VR1
R9
R8
D4
R13
R7
D3
R6
R5
R18
D6
R11
R1
D5
R3
R3
R23
CX5
CX2
R20 C12
R19
R1
1
D1
ADD
1
2
4
8
16
32
64
128
RESET LIMIT
ADD
1
2
4
8
16
32
64
128
SETPOINT
R40
R39
R31
D11
R38
GND
+24VAC
TB4
MODGAS II Board
K3
K2
K1
TB1
COM
AUX
LO SPD
FAN
F
R4
O
F
F
STATUS
GND
AUX IN
HEAT EN
RST IN
SAT
+VDC
R3
R1
R1
P
D2
R9
R8
D1
R7
P
VR1
CX2
POWER
R1
1
C7
U5
I2C IN
D9
V5
VOUT
GND
C13
TB4
2
I C IN
Expansion Board (s) Connection
(When Used)
SA Sensor Wiring Location
VCM Controller with MODGAS II & MHGRV II
VCM Board
U2 CX2 U3 CX3
LD1
1
RN1 CX1
U1
U4
CX4
RELAY1
TB1
COMM
T
SHLD
LD2
RELAY2
R
CX5
LD6
U5
INPUTS
+VDC
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
TB3
C4
RN5
C10
GND
AOUT1
AOUT2
AIN
7
GND
C17
PJ1
COMM RS-485
COMM
1
LD7
PWR
LD8
LED1
C1
R1
LD9
LED2
U7
RV1
+VREF
5.11V
TEST POINT
VREF ADJ
EWDOG
R28
RAM
U6
EPROM
TUC-5R PLUS
YS101718 REV. 3
CX6
1
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
CX10
JP1
X2
CX12
U9
C12
D15
U13
U15
CX13
C15
R22
R24
R25
C20
R15
C14
R19
U14
U12
CX14
PAL
1
RELAY3
LD3
C7
D12
R13
SC1
D19
LD4
RELAY4
LD5
RELAY5
L1
R26
PRESSURE
SENSOR
EXPANSION
T'STAT
VR1
VR2
R6
C9
C13
C16
TB4
GND
24VAC
U8
R1
R2
R3
R4
R5
TB2
V4
V5
V1
V2
V3
MODGAS II Board
Supply
Air Temperature
Sensor
K3
K2
K1
TB1
COM
AUX
LO SPD
FAN
O
F
F
R4
CX2
Supply
Air Temperature
Sensor
F
F
STATUS
GND
AUX IN
HEAT EN
RST IN
SAT
+VDC
VR1
R3
R1
R1
P
D2
R9
R8
D1
R7
P
I2C IN
POWER
R1
1
C7
U5
D9
V5
VOUT
GND
C13
TB4
2
I C OUT
Expansion Board (s) Connection
(When Used)
SA Sensor Wiring Location
VCM Controller with MODGAS II Only
JOB NAME
Caution:
If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply Air Temperature Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the Supply Air Temperature Sensor must be connected to the MHGRV II controller. If you have either of these controllers on your HVAC unit and have a Supply Air Temperature Sensor connected to th VCM controller, your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on an HVAC unit. If expansion boards
FILENAME
O-SA-MHGR-MODG-VCM1a
DATE:
PAGE
1 of 3
03/09/06
DRAWN BY:
B. Crews
DESCRIPTION:
Supply Air Sensor Wiring
Configurations and Connection Diagrams
88 Component & System Wiring
Supply Air Sensor Location & Wiring (Cont’d)
VCMBoard
U2 CX2 U3 CX3
LD1
1
RN1 CX1
U1
U4
CX4
RELAY1
TB1
COMM
T LD2
SHLD
R
CX5
RELAY2
LD6
U5
INPUTS
+VDC
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT1
COMM RS-485
COMM
LD7
PWR
LD8
LED1
1
C1
R1
LD9
LED2
+VREF
5.11V
TEST POINT
U7
RV1
VREF ADJ
EWDOG
R28
C4
RN5
C10
C12
U13
RAM
U6
EPROM
TUC-5R PLUS
YS101718 REV. 3
CX6
1
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
CX10
JP1
X2
CX12
U9
TB3
AOUT2
AIN
7
GND
C17
PJ1
D15
U15
CX13
R15
C14
R19 U14
U12
CX14
C15
R22
R24
R25
C20
PAL RELAY3
1
C7
D12
R13
SC1
D19
LD3
LD4
RELAY4
LD5
RELAY5
L1
R26
PRESSURE
SENSOR
EXPANSION
T'STAT
VR1 VR2
R6
C9
R1
R2
R3
R4
R5
U8
V1
V2
V3
TB2
V4
V5
C13
C16
TB4
GND
24VAC
Supply
Air Temperature
Sensor
MHGRV II Board
YS101894 REV 1
HOT GAS REHEAT
SERIAL #
ADD
1
2
4
8
16
32
64
128
RESET LIMIT
ADD
1
2
4
8
16
32
64
128
SETPOINT
R40
R39
R23
CX5
TB3
R2
CG/HR
CR/HG
CW/HW
CB/HB
U1
+VDC
GND
GND
AUX IN
RST IN
RHT EN
HTG OVR
CLG OVR
GND
SAT
T
SHLD
D2
R4
PU
R12
R
R17
R7
D3
R6
R5
R9
R8
D4
R13
VR1
D6
R11
R1
D5
R3
R3
CX2
R1
1
R20
C12
D1
GND
+24VAC
TB4
R19
PJ1
R31
R18 D11
R38
To Other Expansion Board (s)
(When Used)
Supply
Air Temperature
Sensor
2
I C IN
2
I C OUT
Expansion Board (s) Connection
(When Used)
SA Sensor Wiring Location
VCM Controller with MHGRV II Only
VCM Board
U2 CX2 U3 CX3
CX4
LD1
1
RN1 CX1
U1
U4
RELAY1
TB1
COMM
T LD2
SHLD
RELAY2
R
LD6
CX5
U5
PAL RELAY3
INPUTS
+VDC
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
TB3
C4
RN5
GND
AOUT1
AOUT2
AIN
7
GND
C17
PJ1
C10
COMM RS-485
COMM
1
LD7
PWR
LD8
LED1
C1
R1
LD9
LED2
U7
RV1
+VREF
5.11V
TEST POINT
VREF ADJ
EWDOG
R28
RAM
U6
EPROM
TUC-5R PLUS
YS101718 REV. 3
CX6
1
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
CX10
JP1
X2
CX12
U9
C12
D15
U13
U15
CX13
C15
R22
R24
R25
C20
R15
C14
R19
U14
U12
CX14
C7
1
D12
R13
SC1
D19
LD3
LD4
RELAY4
LD5
RELAY5
L1
R26
PRESSURE
SENSOR
EXPANSION
T'STAT
VR1
VR2
U8
R6
C9
V1
V2
V3
R1
R2
R3
R4
R5
TB2
V4
V5
C13
C16
TB4
GND
24VAC
2
I C IN
2
I C OUT
Expansion Board (s) Connection
(When Used)
SA Sensor Wiring Location
VCM Controller Only
JOB NAME
Caution:
If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply Air Temperature Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the Supply Air Temperature Sensor must be connected to the MHGRV II controller. If you have either of these controllers on your HVAC unit and have a Supply Air Temperature Sensor connected to the VCM controller, your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on an HVAC unit. If expansion boards are used they can be connected via modular cable to any IC2 connector on the loop.
FILENAME
O-SA-MHGR-MODG-VCM1a
DATE:
PAGE
2 of 3
03/09/06
DRAWN BY:
B. Crews
DESCRIPTION:
Supply Air Sensor Wiring
Configurations and Connection Diagrams
Component & System Wiring 89
Supply Air Sensor Location & Wiring (Cont’d)
MHGRV II Board
YS101894 REV 1
HOT GAS REHEAT
SERIAL #
ADD
1
2
4
8
16
32
64
128
RESET LIMIT
ADD
1
2
4
8
16
32
64
128
SETPOINT
R40
R39
R23
CX5
TB3
R2
CG/HR
CR/HG
CW/HW
CB/HB
U1
+VDC
GND
GND
AUX IN
RST IN
RHT EN
HTG OVR
CLG OVR
GND
SAT
D2
R4
T
PU
R12
SHLD
R
R17
R9
R8
D4
R13
R7
D3
R6
R5
CX2
R1
1
VR1
D6
R11
R1
D5
R3
R3
D1
R20
C12
GND
+24VAC
TB4
R19 R31
PJ1
R18
D11
R38
MODGAS II Board
K3
K2
K1
TB1
COM
AUX
LO SPD
FAN
F
R4
O
F
F
STATUS
R3
R1
R1
P
GND
AUX IN
HEAT EN
RST IN
SAT
+VDC
VR1
D1
R7
PU1
D2
R9
R8
CX2
POWER
R1
1
C7
U5
D9
V5
VOUT
GND
C13
TB4
I2C IN
Pullup Resistor “PU1” Must Be
Removed From The MODGAS II Board
For This Configuration
VR1
D1
R7
PU1
POWER
I2C IN
Supply
Air Temperature
Sensor
SA Sensor Wiring
HVAC Unit Control By Others and both MODGAS II & MHGRV II Controller
MODGAS II Board
K3
K2
Supply
Air Temperature
Sensor
K1
TB1
COM
AUX
LO SPD
FAN
O
F
F
R4
O
F
F
STATUS
GND
AUX IN
HEAT EN
RST IN
SAT
+VDC
VR1
R3
R1
R1
P
D2
R9
R8
D1
R7
P
CX2
POWER
R1
1
I2C IN
C7
U5
D9
V5
VOUT
GND
TB4
C13
Supply
Air Temperature
Sensor
MHGRV II Board
YS101894 REV 1
HOT GAS REHEAT
SERIAL #
ADD
1
2
4
8
16
32
64
128
RESET LIMIT
ADD
1
2
4
8
16
32
64
128
SETPOINT
R40
R39
R23
CX5
TB3
R2
CG/HR
CR/HG
CW/HW
CB/HB
U1
+VDC
GND
GND
AUX IN
RST IN
RHT EN
HTG OVR
CLG OVR
GND
SAT
T
SHLD
D2
R4
PU
R12
R
R17
R7
D3
R6
R5
R9
R8
D4
R13
VR1
D6
R11
R1
D5
R3
R3
CX2
R1
1
D1
R20 C12
GND
+24VAC
TB4
R19
PJ1 R31
R18
D11
R38
90
SA Sensor Wiring Location
HVAC Unit Control By Others and MODGAS II Only
SA Sensor Wiring Location
HVAC Unit Controls By Others and MHGRV II Only
JOB NAME
FILENAME
O-SA-MHGR-MODG-VCM1a
DATE:
PAGE
3 of 3
03/09/06
DRAWN BY:
B. Crews
DESCRIPTION:
Supply Air Sensor Wiring
Configurations and Connection Diagrams
Component & System Wiring
Chip Locations
Comm Driver Chip
(U5) Pin 1
RAM Chip
(U2) Pin 1
TB1
COMM
T
SHLD
1
RN1
CX1
U1
U2
CX2
U3
EPROM Chip
(U3) Pin 1
U4
CX4
U5
LD6
COMM
LD7
PWR
1
RS-485
COMM
HH
RAM EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
LD8
LED1
P1
C1
R1
LD9
LED2
U7
+VREF
5.11V
TEST POINT
EWDOG
RV1
VREF ADJ
R28
U6
CX6
1
INPUTS
TB3
ADDRESS
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
R15
C14
R19
C15
R22
R24
R25
C20
CX15
U10
U14
CX10
U12
CX14
CX12
U9
PAL
C7
1
D12
R13
SC1
D19
PRESSURE
SENSOR
R26
EXPANSION T'STAT
VR1
L1
VR2
7824CT
M
PAL Chip
(U4) Pin 1
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
V1
V2
V3
U8
NE5090NPB3192
0PS
9936
R6
C9
MC34064A
C13
C16
TB4
GND
24VAC
OE331 - VCM Controller
EXPANSION
ACTUATOR
K1 K2
EEPROM
PAL Chip
(U9) Pin 1
C2
C4
CX9
U9
RN1
JP2:ON=VAV
OFF=VVT
JP2
C12
Q1
D1
Q3
R38
U4
R21
C9 C10
R22
C11
SCAN
REC
U5
C8
D4
Q2
D2
R23
P3
P1
P2
HAND HELD
U7
AIRFLOW
SPACE SENSOR
C13
L1
PWR
R32
485
DRIVER
DE IN THE USA
R33
C14
EPROM Chip
(U10) Pin 1
Comm Driver Chip
(U8) Pin 1
OE324 - VAV/Zone Controller
PAL Chip
(U7) Pin 1
EPROM Chip
(U11) Pin 1
RAM Chip
(U12) Pin 1
U7
YS101830PREV.2
MODULAR
SYSTEM MANAGER
U1
R1
R4
U3
U2
CX4
U4
RN1
CX5
C3
X2
CX6
U6
CX7
U8
SC1
P1
P2
VAR1
U11
U3
PJ1
D1
R5
R6
D2
R11
R12
C7
DSPY1
R13
L1
R10
D4
CX10
C8
C6
U12
R14
RS-485P
COMM
U14
Comm Driver Chip
(U13) Pin 1
OE392 System Manager
RV1
R7
Comm Driver Chip
(U1) Pin 1
TB1
GND 24VAC
TB2
R1
C1
J01
COMM
GND
C2
J1
CR2
C5
L1
R9
U8
CX8
U6
CX7
P1
R2
U1
CX1
COMPUTER
DCE PORT
P P P2
MODEM
DTE PORT
YS101693 REV 3
MADE IN U.S.A.
C3
U2
P
CX5
Y1
C4
R10
C7
U10
CX10
U11
CX11
U9
CX9
C6
C8
C9
MULTI
SINGLE
U7
C10
Y2
C11
C12
SERIAL NUMBER
D1 D2 D3
MODEL
TP1
GND
EPROM Chip
(U11) Pin 1
Single/Multi
Loop Jumper
(J04)
OE361-04 Commlink II
Warning!
Use Extreme Caution When Removing Any Chips
To Avoid Damaging Any Circuit Board Traces Which
Are Under The Chip.
Be Sure That Any Small Screwdriver Or Other
Sharp Object Used To Remove The Chip Does Not
Come Into Contact With The Printed Circuit Board
Surface.
A Small Screwdriver May Be Inserted Between The
Chip And The Socket To Aid In Removal Of The Chip.
Be Very Careful Not To Insert The Screwdriver Under
The Socket!! Damage To The Board Is Not Covered
By Warranty.
Component & System Wiring
JOB NAME
FILENAME
O-DRCHPREP.CDR
DATE:
PAGE
1 of 3
03/09/06
DRAWN BY:
B. CREWS
DESCRIPTION:
Orion Components
Chip Replacement Information
91
Chip Locations (Cont’d)
Comm Driver Chip
(U5) Pin 1
RAM Chip
(U2) Pin 1
EPROM Chip
(U3) Pin 1
U3
CX1
1
RN1 U2
CX2
CX4
U1
U4
TB1
COMM
T
SHLD
R
CX5
U5
LD6
COMM
LD7
PWR
1
RS-485
COMM
HH
RAM
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
LD8
LED1
R1
C1
LD9
LED2
P1
U7
+VREF
5.11V
TEST POINT
EWDOG
RV1
VREF ADJ
R28
INPUTS
ADDRESS
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
C12
AOUT1
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
U6
C20
CX15
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
R15
U10
C14
R19
U14
C15
R22
R24
R25
CX10
U12
CX14
CX6
CX12
1
U9
PAL
1
C7
D12
R13
SC1
D19
L1
7824CT
PRESSURE
SENSOR
R26
EXPANSION T'STAT
VR1 VR2
M
PAL Chip
(U4) Pin 1
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
9936
R6
C9
MC34064A
C13
C16
TB4
GND
24VAC
OE330 - GPC Plus & GBD Controller
Comm Driver
Chip
(U1) Pin 1
Display Must Be Removed
To Access Driver Chip
RV1
CONT.
P3
1
CX1
PAL Chip
(U6) Pin 1
EPROM Chip
(U10) Pin 1
RN1
CX7
U7
U4
CX8
C3
C4
CX9
X2
SC1
C5 CX11
U10
SERIAL #
SYSM HAND HELD
YS101890
REV 2
C6
C7
C8
U12
L1
B1
B2
P2
SERIAL #
TB4
REC
OUT1
OUT2
OUT3
D33
C31
LED DISPLAY
PWR
R61
C32
R60
R59
U15
U14
C24
R49
R50
OUT1
CX13
R48
OUT2
C17
5.11V
ADJ
C16
D7
D9
R32
D11
D13
D15
C18
RAM
C19
EPROM
PJ1
D1
D3
D5
R7
R8
R9
R10
R11
R12
PU
ANALOG
INPUTS
+V
PU
+V
PU
1
2
R17
R18
R19
R20
R13
R14
R15
R16
3
PU
4
PU
5
6
7
PU
8
PU
G
G
R21
R22
JO1
THERM 8
PU
TB1
ANALOG
OUTPUTS
A1
A2
CX1
G
TB2
EXP
BUSS
OUT3
OUT4
OUT4
R23
R24
R25
RN1
R1
OUT5
OUT6
OUT7
OUT5
OUT6
OUT7
RAM Chip
(U11) Pin 1
RN2 PAL
R6
CX2
R29
R30
EPROMChip
(U10) Pin 1
COMM
R27
TERM
T
SH
R C B
JO2
A
C2
TB3
PAL Chip
(U6) Pin 1
Comm Driver Chip
(U3) Pin 1
OE310 - GPC-17 Controller &
Lighting Controller
Polling Device
EPROM Chip
(U3) Pin 1
Polling Device
RAM Chip
(U4) Pin 1
P2
Polling Device
PAL Chip
(U2) Pin 1
U1
RV1
YS101818P552
P1
C4
U3
CX3
BOARD
PROCESSOR X1
CX4
C1 C2
U4
CX5
U5
LED 1
LED 2
POWER
C12
VR2
U1
U2
C3 CX1 U6
CX6
EPROM RAM
R2
WDOG
D4
R31
C7
UL LABEL
C8
0-10V
4-20mA
THERM
AIN1 AIN2
OFF=0-5V
0-10V
4-20mA
THERM
PROC.
DRIVER
LD6
LOOP
DRIVER
LOCAL LOOP
NETWORK
DRIVER
LD5
NETWORK
LOOP
LD4
EPROM
U6
U10
MiniLink
EPROM Chip
(U6) Pin 1
U7
CX7
RN2
U11
YS101900
MINILINK
POLLING
DEVICE
REV. 1
RN3
SERIAL #
C9
X2
R28
R29
R30
C10
D5
C11
SW1
P4
Processor
Comm Driver Chip
(U15) Pin 1
Local Loop
Comm Driver Chip
(U13) Pin 1
Network Loop
Comm Driver Chip
(U14) Pin 1
OE364-22 - MiniLink Polling Device
JOB NAME
92
OE391 - Service Tool
FILENAME
O-DRCHPREP.CDR
DATE:
PAGE
2 of 3
03/09/06
DRAWN BY:
B. CREWS
DESCRIPTION:
Orion Components
Chip Replacement Information
Component & System Wiring
Chip Installation Procedures
Small Flathead
Screwdriver
Gently Rock Chip Side To Side And Then
Lift Straight Up To Remove Chip From
Chip Socket.
I.C. Puller
Chip
Chip Socket
Using I.C. Puller To Remove Socketed Chip
Printed Circuit
Board
Gently Lift The Chip On One End And Rock Chip
Back And Forth With Screwdriver As Shown.
Repeat This Process On The Other End Of Chip.
Alternate This Process On Both Ends Of Chip Until
The Chip Is Free From The Chip Socket.
Direction Of Pull
Using Screwdriver To Remove Socketed Chip
Chip
Chip Socket
Printed Circuit
Board
WARNING!
Be sure the chip you have selected to replace is a socketed chip. Not all driver chips on the boards are field replaceable. Only socketed chips may be removed and replaced in the field. All other chips that are not socketed will require sending the board to the WattMaster factory for repair.
If you try to remove a chip that is not socketed it will destroy the circuit board.
Once you have determined that the chip needing replacement is indeed a socketed chip please proceed in the following manner.
Remove the communications loop connector and then the 24VAC power connector on the controller before attempting to change any components.
DAMAGE
will occur if components are removed or installed with power applied.
If you are unsure how to safely remove the chip or about the correct pin placement, please consult the factory before proceeding.
Damage to the board caused by failure to correctly remove or install the chip is not covered by the
WattMaster warranty.
Use extreme care to avoid inserting the screwdriver or I.C. Puller under the socket. You must insert the tip of the screwdriver or ends of the I.C. Puller between the body of the chip and the chip socket.
Each chip
MUST
be installed with Pin 1 in the correct location. Installing the chip “backwards” will in most cases destroy the device when power is reapplied.
Pin 1 can be located by looking for the notch in the end of the chip. Pin 1 on "some" chips is identified with a dot.
Be certain that
ALL
pins are lined up in the socket before pressing the chip in. Failure to properly line up the pins will result in damage to the chip.
This is a
VERY
common error -
BE CAREFUL.
Only after confirming that the chip has been correctly installed with Pin 1 in the proper position and that the pins are lined up and none are bent or out of the socket, should communication or power wiring be reconnected to the board. Tp prevent possible damage always reconnect the power wiring first and then the communication wiring.
Notch
Dot
Pin1
Chip
Chip Socket
Top View Of Socketed Chip Assembly
Printed Circuit
Board
End View Of Socketed Chip Assembly
Socket
Dot
Pin 1
Printed
Circuit
Board
Typical RS-485 Communications
Driver Chip Detail
Component & System Wiring
JOB NAME
FILENAME
O-DRCHPREP.CDR
DATE:
PAGE
3 of 3
03/09/06
DRAWN BY:
B. CREWS
DESCRIPTION:
Orion Components
Chip Replacement Information
93
Temperature & Humidity Sensor Voltage-Resistance Tables
Sensor Checks
The following sensor voltage and resistance tables are provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly, check voltage and/or resistance to confirm that the sensor is operating correctly per the tables. Please follow the notes and instructions below each chart when checking sensors.
Temp
(ºF)
Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors
Resistance
(Ohms)
Voltage @
Input (VDC)
Temp
(ºF)
Resistance
(Ohms)
Voltage @
Input (VDC)
Temp
(ºF)
Resistance
(Ohms)
Voltage @
Input (VDC)
10 52500 4.297 68 12191 2.810 100 6047 1.927
15 45902 4.200 69 11906 2.780 105 5453 1.805
20 40147 4.095 70 11652 2.752 110 4923 1.687
25 35165 3.982 71 11379 2.722 115 4449 1.575
30 30805 3.862 72 11136 2.695 120 4030 1.469
35 27140 3.737 73 10878 2.665 125 3656 1.369
40 23874 3.605 74 10625 2.635 130 3317 1.274
45 21094 3.470 75 10398 2.607 135 3015 1.185
50 18655 3.330 76 10158 2.577 140 2743 1.101
52 17799 3.275 78 9711 2.520 145 2502 1.024
54 16956 3.217 80 9302 2.465 150 2288 0.952
56 16164 3.160 82 8893 2.407
58 15385 3.100 84 8514 2.352
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered). Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
OE265-03 Relative Humidity Transmitter – Humidity vs. Voltage
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
0% 1.00 26% 2.04 52% 3.08 78% 4.12
2% 1.08 28% 2.12 54% 3.16 80% 4.20
4% 1.16 30% 2.20 56% 3.24 82% 4.28
6% 1.24 32% 2.28 58% 3.32 84% 4.36
8% 1.32 34% 2.36 60% 3.40 86% 4.44
10% 1.40 36% 2.44 62% 3.48 88% 4.52
12% 1.48 38% 2.52 64% 3.56 90% 4.60
14% 1.56 40% 2.60 66% 3.64 92% 4.68
16% 1.64 42% 2.68 68% 3.72 94% 4.76
18% 1.72 44% 2.76 70% 3.80 96% 4.84
20% 1.80 46% 2.84 72% 3.88 98% 4.92
22% 1.88 48% 2.92 74% 3.96 100% 5.00
24% 1.96 50% 3.00 76% 4.04
OE265-03 Relative Humidity Sensor
Testing Instructions:
Use the voltage column to check the Humidity Sensor while connected to a powered expansion board. Read voltage with meter set on DC volts.
Place the “-”(minus) lead on terminal labeled GND and the “+” lead on terminal AIN4 on the Analog Input/Output Expansion Board.
94 Component & System Wiring
Pressure Sensors Voltage-Resistance Tables
OE271 Duct Static Pressure Sensor
This sensor is used to sense duct static pressure for the Orion system controllers. The OE271 sensor is a 0-5” W.C. pressure range, 0-5 VDC voltage range sensor. Use the table and testing information below to check for proper sensor operation.
OE258 Building Pressure Sensor
This sensor is used to sense building pressure for the Orion system controllers. The OE258 sensor is a -0.25” to +0.25” W.C. pressure range,
0-5 VDC voltage range sensor. Use the table and testing information below to check for proper sensor operation.
OE271 Duct Static Pressure Sensor
OE258 Building Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC) (VDC)
0.00 0.25 2.60 2.20
0.10 0.33 2.70 2.28
0.20 0.40 2.80 2.35
0.30 0.48 2.90 2.43
0.40 0.55 3.00 2.50
0.50 0.63 3.10 2.58
0.60 0.70 3.20 2.65
0.70 0.78 3.30 2.73
0.80 0.85 3.40 2.80
0.90 0.93 3.50 2.88
1.00 1.00 3.60 2.95
1.10 1.08 3.70 3.03
1.20 1.15 3.80 3.10
1.30 1.23 3.90 3.18
1.40 1.30 4.00 3.25
1.50 1.38 4.10 3.33
1.60 1.45 4.20 3.40
1.70 1.53 4.30 3.48
1.80 1.60 4.40 3.55
1.90 1.68 4.50 3.63
2.00 1.75 4.60 3.70
2.10 1.83 4.70 3.78
2.20 1.90 4.80 3.85
2.30 1.98 4.90 3.93
2.40 2.05 5.00 4.00
2.50 2.13
OE271 Pressure Sensor Testing Instructions
Use the voltage column to check the Duct Static Pressure Sensor while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the 0-5 pin terminal on (JP1) with the jumper removed. Be sure to replace the jumper after checking.
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC) (VDC)
-0.25 0.00 0.01 2.60
-0.24 0.10 0.02 2.70
-0.23 0.20 0.03 2.80
-0.22 0.30 0.04 2.90
-0.21 0.40 0.05 3.00
-0.20 0.50 0.06 3.10
-0.19 0.60 0.07 3.20
-0.18 0.70 0.08 3.30
-0.17 0.80 0.09 3.40
-0.16 0.90 0.10 3.50
-0.15 1.00 0.11 3.60
-0.14 1.10 0.12 3.70
-0.13 1.20 0.13 3.80
-0.12 1.30 0.14 3.90
-0.11 1.40 0.15 4.00
-0.10 1.50 0.16 4.10
-0.09 1.60 0.17 4.20
-0.08 1.70 0.18 4.30
-0.07 1.80 0.19 4.40
-0.06 1.90 0.20 4.50
-0.05 2.00 0.21 4.60
-0.04 2.10 0.22 4.70
-0.03 2.20 0.23 4.80
-0.02 2.30 0.24 4.90
-0.01 2.40 0.25 5.00
0.00 2.50
OE258 Building Pressure Sensor Testing Instructions
Use the voltage column to check the Building Static Pressure Sensor while connected to a powered expansion board. Read voltage with meter set on DC volts. Place the “-”(minus) lead on terminal labeled GND and the “+” lead on terminal AIN4 on the Analog Input/Output Expansion Board.
Component & System Wiring 95
Form: OR-VCMWIRE-TGD-01B Printed in the USA September 2006
All rights reserved
WattMaster Controls Inc.
•
8500 NW River Park Drive
•
Copyright 2006
Parkville, Mo.
•
64152