Ascon KX1 Temperature Controller Quick Guide
PDF
Документ
Реклама
Реклама
TEMPERATURE CONTROLLER 1/8 DIN - 48 x 96 KX1 model ube Quick Guide • ISTR-FKX1ENG03 DECLARATION OF CONFORMITY AND MANUAL RETRIEVAL DISPLAY AND KEYS KX1 is a panel mounting, Class II instrument. It has been designed with compliance to the European Directives. All information about the controller use can be found in the Engineering Manual: ISTR-MKX_-ENG0x (“x” is the revision). The Declaration of Conformity and the manual of the controller can be downloaded (free of charge) from the web-site: Unit (°C/°F) Digital input DI1 Alarm active www.ascontecnologic.com Once connected to the web-site, search: KX1 then click on KX1. In the lower part of the product page (in any language) is present the download area with links to the documents available for the controller (in the available languages). DIMENSIONS Overall dimensions (W x H x D): 48 x 96 x 75.9 mm (1.89 x 3.78 x 2.99 in.) Panel Cut-out (W x H): 45+0.6 x 89+0.6 mm (1.78+0.023 x 3.50+0.023 in.) Process Value (in eng. units) Autotune in progress (flashing) DI2 Manual mode Timer running Bar graph Set Point (auto mode) Output Value (manual mode) Param. value or State/Function (Editing mode) Output LEDs Operator Mode Access to: - Operator Commands (Timer, Setpoint selection ...) - Parameters - Configuration Warning! MODEL CODE ELECTRICAL CONNECTIONS Terminals The Hardware resources are identified by the following Model Code. Model: KX 1 A B C D E F G H I Pin: KX 1 Optional functions A None - Timer T Power Supply B 100... 240Vac (-15... +10%) H 24Vac (-25... +12%) or 24Vdc (-15... +25%) L C Input TC, PT100, PT1000, mA, mV, V + Digital Input 1 C TC, NTC, PTC, mA, mV, V + Digital Input 1 E Output OP1 D Relay (1 SPST NO, 4 A/250 Vac) R VDC for SSR (12 Vdc/20 mA) O Output OP2 E None - Relay (1 SPST NO, 2 A/250 Vac) R VDC for SSR (12 Vdc/20 mA) O Output OP3 F None - Relay (1 SPST NO, 2 A/250 Vac) R VDC for SSR Vdc (12 Vdc/20 mA) O Output OP4 G Digital I/O (see the Electrical Connections paragraph for details) D Serial Communications H TTL - RS485 Modbus S Terminal Type I Standard (screw type non removable terminal blocks) - With plug-in screw type terminal blocks E With plug-in clamp type terminal blocks M With plug-in terminal blocks (fixed part only) N q 1.4 mm - 0.055 in. max. Access to: - Set Point Decrease the displayed value or select the previous element Start the programmed function (Autotune, Auto/Man, Timer ...) Exit from Operator commands/Parameter setting/Configuration 100... 240 Vac/ Line 20... 30 Vdc/ 18... 28 Vac Neutral - 0 0 0 0 Line Confirm and go to Next parameter Access to: Increase the displayed - Operator additional information value or select the (Output value, running time ...) next element - Whenever a failure or a malfunction of the device may cause dangerous situations for persons, things or animals, please remember that the plant must be equipped with additional devices which will guarantee safety. - We warrant that the products will be free from defects in material and workmanship for 18 months from the date of delivery. Products and components that are subject to wear due to conditions of use, service life and misuse are not covered by this warranty. viale Indipendenza 56, 27029 - Vigevano (PV) - ITALIA Tel.: +39 0381 698 71, Fax: +39 0381 698 730 Sito internet: www.ascontecnologic.com E-mail: [email protected] Editing Mode L NO Stripped wire: L 5.5 mm - 0.21 in. OP3 C Note: Terminal 4 can be programmed as: - Digital Input (DI2) connecting a free of voltage contact between terminals 4 and 5; NO - 0... 12 V SSR Drive Output (OP4) connecting the load between terminals 4 and 5; C - 12 Vdc (20 mA) transmitter power supply connecting the 2 wire transmitter between terminals 4 and 1; for 3 wire transmitter connect terminal 4 to NO transmitter power supply input and terminal 1 and 2 to transmitter signal output. OP2 OP1 C Analogue input RS485 DI1 Pt1000/NTC/PTC Pt100 PV PV 4... 20 mA 3 wire transmitter OP4 (note) 12 Vdc (note) 12 Vdc (note) Model Code example: KX1-HCRRRD-Controller KX1, no timer, 100... 240 Vac, TC/PT100/PT1000/mV/V + Digital Input 1, 3 Relay Outputs, Output 4, TTL, Non removable screw type terminals. DI2 (note) 4... 20 mA 2 wire transmitter mV, V mA Thermocouple CONFIGURATION CODE The KX1 can be easily configured by the “Code Configuration” method for the most common requirements, just entering two 4-digit codes: Cod1 [LMNO] for the Input Type and Control Mode selection and Cod2 [PQRS] for the Alarms and the Service Functions. For complete controller configuration see the Engineering Manual. Note: Before starting the configuration code setting, please define and write down Cod1 and Cod2 as needed: HOW TO SET THE CONFIGURATION CODE L M N ALARM TYPES (Cod2 digits: P, Q, R) c%d1 O Absolute Alarm L MN O User c%d1 PV PV AT Press for 3 seconds to access the configuration mode PV AT Press and to enter the configuration Password 4 (default 300) PV AT Press and to enter c%d1 (Input Type and Control Mode) PV Input Type and Range L M TC J -50... +1000°C TC K -50... +1370°C TC S -50... 1760°C TC R -50... +1760°C TC T -70... +400°C Infrared J -50... +785°C Infrared K -50... +785°C PT 100/PTC KTY81-121 -200... +850°C/-55... +150°C PT 1000/NTC 103-AT2 -200... +850°C/-50... +110°C Linear 0... 60 mV Linear 12... 60 mV Linear 0... 20 mA (this selection forces Out 4 = TX) Linear 4... 20 mA (this selection forces Out 4 = TX) Linear 0... 5 V Linear 1... 5 V Linear 0... 10 V Linear 2... 10 V TC J -58... +1832°F TC K -58... +2498°F TC S -58... 3200°F TC R -58... +3200°F TC T -94... +752°F Infrared J -58... +1445°F Infrared K -58... +1445°F PT 100/PTC KTY81-121 -328... +1562°F/-67... +302°F PT 1000/NTC 103-AT2 -328... +1562°F/-58... +230°F 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 Control mode ON/OFF heating = H ON/OFF cooling = C ON/OFF with neutral zone (H/C) PID heating = H PID cooling = C PID double action (H/C) OP1 OP2 OP3 OP4 N O H AL1 AL2 AL3 0 0 NU AL1 AL2 H 0 1 C AL1 AL2 AL3 0 2 NU AL1 AL2 C 0 3 H C AL2 AL3 0 4 H AL1 AL2 C 0 5 C H AL2 AL3 0 6 NU H AL2 C 0 7 C AL1 AL2 H 0 8 NU C AL2 H 0 9 H AL1 AL2 AL3 1 0 NU AL1 AL2 H 1 1 C AL1 AL2 AL3 1 2 NU AL1 AL2 C 1 3 H C AL2 AL3 1 4 H AL1 AL2 C 1 5 C H AL2 AL3 1 6 NU H AL2 C 1 7 C AL1 AL2 H 1 8 NU C AL2 H 1 9 Time ON Absolute High Absolute Low ON ON Absolute High-Low Alarm PV Time ON Absolute External Absolute Internal Note: As default, when the alarms are active, only AL1 threshold is available at “Operator Command” level to perform non critical tasks. To protect the AL2 and AL3 thresholds against undesired changes, they are available only at “Parameters list” level (password: 20). For different configurations, see the Engineering Manual. ON ON ON Deviation Alarm PV AT P Q R c%d2 S User c%d2 Press and to enter c%d2 (Alarms and Service Functions) R Alarm 3 Q Alarm 2 PV AT Alarm 1 P Not used 0 0 Sensor break 1 1 Absolute Absolute High/Low Press to store the Configuration code Note: To leave the Configuration session without saving the settings made, press the button Deviation Band Time P Q R S Service functions activation S None 0 Wattmeter (instantaneous power expressed in kW) (note 1) 1 0 Wattmeter (Power consuption expressed in kWh/h) (note 2) 2 1 Absolute worked time (expressed in days) (note 3) 3 Absolute worked time (expressed in hours) (note 3) 4 High 2 2 2 Low 3 3 3 External High/Low 4 4 4 Internal High/Low 5 5 5 Deviation high 6 6 6 Deviation low 7 7 7 External band 8 8 8 Internal band 9 9 9 ON Deviation High Note: 1.Wattmeter Instantaneous power is continuously computed as multiplication of the Load Voltage, Load Current parameter values and the controller output instantaneous value. 2.Wattmeter power consumption is the estimated hourly energy consumption (using Load Voltage and Load Current parameter values), computed on the previous 15 minutes period. The readout is updated every 15 minutes. 3.Worked Time counter is continuously increased when the controller is turned ON. ON Deviation Low ON Band Alarm PV Band Internal Band External ON ON ON ON Time ON Parameters List (PASS: 20) (in gray the parameters related to optional features) PARAMETERS SETTING Group PV PV AT Password 2 (default: 20) Commands AT Access to parameters To Code configuration mode (cod1, cod2 tables on the front page) Control To exit the parameter setting procedure press the key (for 3 s) or wait until the timeout expiration (about 30 seconds). CONTROLLER OPERATION Set Point Heating 248.0 H035 248.0 248.0 Cooling C045 Output Value % (e.g. heating = 35%, cooling = 45%) Depending on Cod2 digit S setting 248.0 U854 Power (kW) 248.0 or Energy (Wh) Worked time (days) d854 248.0 t04.8 Timer remaining time If active key for 3 seconds or wait for the 10s timeout To return to the Normal Mode, press the sp ti Integral Time 0... 10000 s 200 td Derivative Time 0... 1000 s 50 Operative Set Point Changed operative Set Point 1 Cod1 Digit N = 0 0.1... 130 s 20.0 rcg Relative Cooling Gain 0.01... 99.99 1.00 tcc Cooling output cycle time 0.1... 130 s 20.0 Cod1 Digit N = 1 Cod1 Digit N = 1 Cod1 Digit O > 4 Cod1 Digit N = 1 Cod1 Digit O > 1 SP Set Point 1 -1999... +9999 (E.U.) SP2 Set Point 2 SP3 Set Point 3 SP4 Set Point 4 EVOTUNE is a fast and fully automatic proceDot flashes that can be started in any 248.0 248.0. while the dure condition, regardless the deviation tunE 248.0 Auto-tune from SP. is in progress The controller selects automatically Auto-tune Auto-tune started in progress the best tune method and computes the optimum PID parameters. Note: The key could be assigned by the user to other functions using the Usrb parameter setting Start Press the key for 3 s SPLL... 9999 (E.U.) nSP No. of Set Points 1... 4 AL1 Alarm 1 threshold AL1L... AL1H al2l Alarm 2 low threshold/Low limit al2H Alarm 2 high threshold/High limit tr.st run a.sp 1 run: Start If timer hold: Hold activated res: Reset ( tr.F ) Confirm/Next Active Set Point selection Confirm/Next 120.0 nsp > 2 sp3 nsp > 3 225.0 sp4 340.0 Confirm/Next AL1 250 Back to the first parameter If AL1 is active Confirm/Next 1... 9999 (E.U.) 1 -1999 -1999... +9999 (E.U.) 9999 1... 9999 (E.U.) 1 -1999 -1999... +9999 (E.U.) 9999 1 Sst Soft Start Time 0.00... 8.00 (hh.mm) 0 ssc Low Scale readout -1999... 9999 -1999 fsc High Scale readout -1999... 9999 9999 dP Number of decimals 0... 3 (linear inputs); 0... 1 (other inputs) 0 FiL Measured value Digital filter OFF; 0.1... 20.0 s nonE = Timer not used i.d.A = Delayed ON at start command i.uP.d = Activation ON at Power ON i.d.d = At start command i.P.L = Asymmetrical oscillator, start in OFF i.L.P = Asymmetrical oscillator, start in ON 0 = hh.mm 1 = mm.ss 2 = sss.d 00.01... 995.9 0 = OFF Timer Type tr.u Timer Units io4.F I/O 4 Function Digital Inputs diF.2 Digital Input 2 Function usrb Key Function di.cl Colour of the Process Value display ade Display change color threshold (when di.Cl = 0) If digit Q of Cod2 is > 1 AL3L... AL3H 0 tr.F If digit P of Cod2 is > 1 AL2L... AL2H -100... 100% I/O none 1= mm.ss 1.00 00.00... 995.9 ON = Transmitter Power Supply OUT4 = SSR out Di2C = Dig. In. from contact Di2U = 24 VDC Digital Input 0... 21 1.00 0... 21 nonE, tunE, oplo, aac, asi, chsp, st.by, str.t 0 = Change 1 = Red 2 = Green 3 = Orange 0 If digit R of Cod2 is > 1 For linear Input types only Timer management (Start, Stop, Reset) can be done using the tr.St command or the key (if programmed) or by the DI1/DI2 digital inputs (if programmed). ON 0 tunE 2 0 (OFF)... 9999 (e.u.) dis.t Display Power OFF time (mm.ss) oFF (display ON) 0.1... 99.59 nonE, Pou, Po.h, Pr.tu, Pr.td, Pr.tS, ti.uP, bG.F Bar graph Function ti.du, r.iSP Add Instrument Address 1... 254 Serial com1200, 2400, 9600 baud, munications bAud Baud rate 19.2, 38.4 kbaud Uolt Load Voltage 1... 999 (V) Wattmeter cur Load Current 1... 9999 (A) Password key for 3 seconds or wait for the 10s timeout 9999 1... 9999 (E.U.) tr.t2 Time 2 Display -1999 -1999... +9999 (E.U.) Soft Start Output value tr.t1 Time 1 sp2 1 stp diF.1 Digital Input 1 Function st Increase 1 SP sp value Decrease change 248.0 Confirm/Next nsp > 1 If more than 1 Set Point active (nsp > 1) To return to the Normal Mode, press the Alarm 3 threshold Timer Operator Command If nSP > 3 SPHL Set Point max. Value Alarm 2 threshold If nSP > 2 -1999... +9999 (E.U.) -1999... SPHL (E.U.) HAL3 AL3 hysteresis Input If nSP > 1 SPLL Set Point min. Value AL2 Soft Start Cod1 Digit N = 1 0... 9999 (E.U.) al3H Alarm 3 high threshold/High limit Press the key (3 s) or wait for the 10s time out to store the new Set Point and return to Normal Mode evoTUNE Heating output cycle time al3l Alarm 3 low threshold/Low limit 250.0 Note tc.H HSEt Hysteresis ON/OFF Control AL3 sp 248.0 0 = OFF 20 HAL1 AL1 hysteresis Set Point Change 0 = SP 0 = oFF, 1 = start 1... 9999 (Engineering Units = E.U.) al1H Alarm 1 high threshold/High limit Alarms User value Option reg = Auto, oplo = Manual, stdy = Standby 0 = SP, 1 = SP2, 2 = SP3, 3 = SP4 Proportional Band HAL2 AL2 hysteresis Increase value Decrease value Range value or selection list elements Default Pb al1l Alarm 1 low threshold/Low limit h854 Worked time (hours) Set Point Selection tune Start Auto Tune Confirm and go to Next parameter Increase the displayed value or select the next element Decrease the displayed value or select the previous element Additional Information oPEr Operative Mode Selection a.sp Parameters setting Press the key for 3 seconds Password 4 (default: 300) Description tr.St Timer status PV AT Param. See the DI1, DI2 functions table See the Key function table If Change, the colour is green if PV differs from SP less than Ade, red if higher than Ade and orange if is lower than Ade oFF Pou 1 9600 230 PAS4 Configuration access Password 0... 999 300 PAS2 Parameters access Password 0... 999 20 Modbus RTU slave protocol If digit S of Cod2 is > 1 Note: To access all the instrument features, please see the “Complete configuration procedure” in the “Engineering Manual”. Complete Configuration and Parameter setting can be easily uploaded from the controller and downloaded to other controllers using the: Configuration Key and Communication Adapter model: A-01. FUNCTION SELECTION Timer Types (selected by tr.f) (option) i.d.a Delayed ON at Start command Start OUT i.p.l Asymmetrical oscillator with start in OFF Tr.t1 Tr.t2 off ON off PWR ON i.up.d Delayed ON at Power ON OUT i.d.d Tr.t1 Tr.t2 off ON ON PWR ON OUT Reset off ON Tr.t1 off ON Tr.t2 Tr.t1 off ON Start off OUT Reset Tr.t1 ON Tr.t2 off Tr.t1 ON Tr.t2 off Tr.t1 ON Tr.t2 off usrb Key Code displayed 0 1 2 3 4 5 6 7 8 9 10 11 Code displayed nonE tune oplo aac asi chsp st.by str.t 12 Tr.t1 OUT Reset Tr.t1 Tr.t2 i.L.p Asymmetrical oscillator with start in ON PWR ON At Start command Start Start Tr.t2 dif$ Digital Inputs DI1 and DI2 Functions off 18 19 20 21 Description Disabled (OFF) (default) Alarm Reset Alarm Acknowledge (ACK) Hold of the measured value Stand by mode Manual Mode Heat with “SP” and CooL with “SP2” Timer Run/Hold/Reset [on transition] Timer Run [on transition] Available only if Timer Reset [on transition] timer option and Timer Run/Hold tr.F is NOT set to Timer Run/Reset nonE Timer Run/Reset with lock at the end of the time count Sequential Set Point selection [on transition] SP/SP2 selection Binary coding for Set Point selection on DI1 and DI2 (00 = SP, 01 = SP2, 10 = SP3, 11 = SP4) Digital inputs in parallel to the and keys (DI1 = , DI2 = ) Function Description Not used Starts auto tuning functions (default) Manual mode Alarm Reset Alarm Acknowledge Circular Set Point Selection (shows SP, SP2, SP3) Stand-by mode Starts/Stop/Reset timer ">
/
Завантажити
Просто дружнє нагадування. Ви можете переглянути документ прямо тут. Але найголовніше, наш штучний інтелект вже прочитав його. Він може пояснити складні речі простими словами, відповісти на ваші запитання будь-якою мовою та допомогти вам швидко орієнтуватися навіть у найдовших або найскладніших документах.
Реклама