FW Murphy MConfigPro Configuration Software Installation and Operations Manual
Below you will find brief information for Configuration Software MConfigPro. The MConfigPro software is designed to allow you to modify the configuration of a Centurion controller to provide a simple and easy-to-use interface to adjust features such as sequence of operation, setpoint s, timers, faults, and displays. This user-friendly interface will enable you to download the configurations from your PC to the Centurion controller via a serial or USB connection.
Advertisement
Advertisement
MConfigPro
Configuration Software
Installation and Operations Manual
00-02-0602
08-31-06
Section 50
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time. The latest version of this manual can be found at www.fwmurphy.com.
Please read the following information before installing.
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT:
• Read and follow all installation instructions.
• Please contact FW MURPHY if you have any questions.
Table of Contents
About MConfigPro .................................................................................................................. 1
Installing MConfigPro............................................................................................................. 1
System Requirements ..................................................................................................1
Installation Instructions.................................................................................................2
Installing USB Driver .............................................................................................................. 4
MConfigPro Application GUI Overview ................................................................................ 6
Launching the Application ............................................................................................6
Menus and Tool Bars ...................................................................................................6
Opening Wizard ...........................................................................................................8
Saving Files..................................................................................................................9
Navigating MConfigPro ..............................................................................................10
Main Menu List Screen Definitions ..................................................................................... 12
Version and Security ..................................................................................................12
Digital Inputs ..............................................................................................................14
Digital Outputs............................................................................................................16
Digital Assignments....................................................................................................17
Analog Inputs .............................................................................................................18
Analog Outputs ..........................................................................................................20
Thermocouple ............................................................................................................21
Setpoints ....................................................................................................................22
Global Timers.............................................................................................................24
Maintenance Timers...................................................................................................26
Events ........................................................................................................................27
Startup .......................................................................................................................29
RPM Controls.............................................................................................................30
Control Outputs ..........................................................................................................32
States .........................................................................................................................34
Miscellaneous ............................................................................................................36
PID .............................................................................................................................38
Comm Port Settings ...................................................................................................40
Guidelines for Configuring MConfigPro............................................................................. 41
Defining the System ...................................................................................................41
System of Protection ..................................................................................................42
System of Operation ..................................................................................................42
System of Interface ....................................................................................................43
Configuration Download Instructions ................................................................................ 43
Comm. Port Settings ..................................................................................................43
About MConfigPro
MConfigPro is a pc-based configuration software for the Centurion controller. The easy-to-use interface enables you to modify features of the Centurion such as:
• timers
• faults
• displays
File transfer utilities for configuration and firmware upgrades are provided so that once the configuration is set, it may be downloaded from your pc to the Centurion via a serial or USB connection.
Installing MConfigPro
System Requirements
A serial port (RS485/232) or USB 1.1 connection is required for transferring the configuration from MConfigPro to the Centurion.
While the MConfigPro software will function on any pc or laptop running Windows, it will not perform transfers using the USB driver unless the operating system supports USB. USB supported operating systems include Win98SE, NT, and XP.
Serial transfers using standard communication ports (COM1, COM2) should be possible on all
Windows platforms.
The MConfigPro software and USB driver provide efficient use of your hard drive, using only 3-
5 MB of disk space after installation.
Section 50 00-02-0602
Installation Instructions
Follow the steps below to install the MConfigPro software on a pc or laptop.
1. Insert the MConfigPro CD into the CD drive of your computer. The installation menu is displayed.
2. Select “Install MConfigPro” from the menu. An Installation Wizard is launched.
Click on [Next] to continue.
3. The License Agreement for the product is displayed. You may print the agreement by clicking on the [Print] button displayed beneath the agreement.
4. Once you have read the License Agreement, click the “I agree with the terms in the license agreement.” Then click [Next].
5. You will be asked for a destination folder for the program. You may accept the suggested directory or you may select a different directory by clicking the
[Change] button and browse to the destination folder. Once the destination folder is determined, click [Next] to continue.
Section 50 00-02-0602
6. The Wizard is now ready to install the program. Click on the [Install] button to begin. This may take several minutes.
7. When the installation is complete, the following screen appears. Click [Finish].
Section 50 00-02-0602
Installing USB Driver
If you will be using a USB connection device to download the configuration into the Centurion controller, you will need to install the USB driver. Follow the instructions listed below to install the USB Driver.
1. Insert the MConfigPro CD into the CD drive of your computer. The installation menu is displayed.
2. Select “Install USB Driver” from the menu. An “Install Driver” dialog box displays a destination folder for the program. You may accept the suggested directory or you may select a different directory by clicking the [Browse] button to locate the destination folder.
3. Once the destination folder is determined, click [Install].
Section 50 00-02-0602
4. The following dialog box will appear to indicate Microsoft has not tested the device driver with the XP operating system.
The manufacturer of the royalty-free USB driver has elected not to seek Windows
Logo approval. Therefore, you should read the message carefully and understand the impact it may have on critical systems before accepting responsibility for continuing with the installation.
Select [Continue Anyway] to continue with the installation of the USB driver.
5. Because the device driver installs two items, the “Software Installation” dialog box will appear a second time. Select [Continue Anyway].
6. Once the driver is installed the following dialog box will appear. Click [OK].
7. From the MConfigPro Installation Menu, select “Exit”.
Section 50 00-02-0602
MConfigPro Application GUI Overview
This section provides instructions for launching the MConfigPro application, identifies the application features that are accessible through the menu bar, and defines general navigation.
Launching the Application
To launch the application you may either double-click the MConfigPro application icon located on your desktop, or select “MConfigPro Design” from the list of programs under your
“Start” menu. The following dialog box is displayed.
Click on the [Run] button to launch the application.
NOTE: You may turn off this dialog box from displaying each time you launch the application by de-selecting the check box “Always ask before opening this file”, located in the lower left corner.
Menus and Tool Bars
The tools provide one-click access to creating a new file, opening an existing file, saving the currently displayed file, or printing the current file. These same functions are available from the
“File” drop-down menu.
Section 50 00-02-0602
The “View” drop-down menu provides a list of configurable settings that may be viewed or changed. These same settings are also displayed and available in the “Main Menu List” window of the user interface when a configuration file is being displayed.
Selecting “Options” displays a dialog box that allows you to select the boards you are using.
The “Tools” menu allows you to upload from or download to the Centurion device.
“Help” provides a link to the FW Murphy website, and will launch an e-mail when “Contact Us” is selected. At this time, there is no online help available.
Section 50 00-02-0602
Opening Wizard
When you click on the new file icon or select File/New from the menus, the Opening Wizard is displayed. It contains three tabs labeled “New”, “Existing”, and “Recent”.
The “New” tab contains several templates to use as guidelines for setting up reciprocating compressors, screw compressors, and pumps. There is also a “Blank” template to be used for setting up new files and does not contain any pre-configured data.
The “Existing” tab displays the current location where files are being stored. You may select from this list or browse to locate the desired file.
The “Recent” tab displays the most recent files that have been created or updated.
Section 50 00-02-0602
Saving Files
When saving files you may select a file extension specific to the type of equipment you are configuring. This helps to differentiate the file types when you are browsing through the file names. There are four file extensions to choose from.
.cfp Pump
The default file extension .mcp is used unless a different extension is specified. To select a different extension, click the “Save as type:” pull-down menu and select the desired extension.
Section 50 00-02-0602
Navigating MConfigPro
Navigating the MConfigPro application interface is versatile and easy. It contains two main windows, or sections of information. The left window contains the “Main Menu List” of available features and settings available for configuration. This is the same list that is displayed on the
View pull down menu. When a new file is created, the “Main Menu List” is the only window displayed until a process is selected.
Section 50 00-02-0602
Selecting items from the “Main Menu List” will populate the remaining window with the appropriate information. In most cases, the window will contain three sections of information. In the upper left, a list of processes (A) or options is displayed. When you click on any of these options, the corresponding data fields (B) are displayed in the upper right section. You may click on these fields and enter the appropriate configuration information. The upper right section may also contain helpful guidelines for entering data.
The bottom portion (C) of the window contains the same information as the upper right, but in a spreadsheet format containing all the entries listed in the upper section. You may edit either the upper or lower sections as desired.
Section 50 00-02-0602
Main Menu List Screen Definitions
This section provides field definitions for each item in the Main Menu List and can be used as a reference when setting up your configuration files. An example of each screen will be displayed, followed by a table listing all editable fields and their descriptions.
Version and Security
Section 50 00-02-0602
Field
Version
Date
Time
Description
Description
Non-editable, system generated. The Revision number reflects the version of MConfigPro that created the file or last updated it. If the version is different from the current MConfigPro version, choosing
File/Save will update the file version to that of the current
MConfigPro version.
Non-editable, system generated. Date reflects the date of the last save (or creation date). This is updated with the current date when
‘Save’ or ‘Save As’ is chosen from the File menu.
Non-editable, system generated. This Time reflects the time of the last save (or creation time). This is updated with the current Time when ‘Save’ or ‘Save As’ is chosen from the File menu.
15 character description of your choice to identify the configuration.
Allows access to all setup menus except the super user menu.
Standard Security
Password
Must be zero or range from 100 to 65535 and cannot be the same as the Super User Password. Entering a value of 0 disables the password and provides no security.
NOTE: Passwords are required for the Centurion display only.
Passwords have no function within the Centurion controller.
Super User Password Allows access to all setup menus, super user menu and provides additional functions like “Reset Fault History” which should not be available to most operators.
Must be a range from 100 to 65535 and cannot be zero or the same as the Standard Security Password.
Section 50 00-02-0602
Digital Inputs
Section 50 00-02-0602
Field
Description
In Use
Type
Enable Delay
Delay Type
Delay (Secs)
Description
Entries are provided for each of the 32 digital input devices. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Active inputs must be set to “In Use” in order to show up on subsequent configuration screens. Once the input is set to “In Use”, the entry turns to bolded text.
NO = Normally Open
NC = Normally Closed
Check to enable delay.
• Debounce – provides a timed condition for processing the digital input. The input must be active for the duration of the delay before it will be recognized as active by the controller application.
Once recognized, the digital input must be inactive for the duration of the delay before it will be recognized as inactive by the controller application.
This type of signal condition is useful in process conditions such as unstable tank levels.
• Pulse – provides a timed transition condition for processing the digital input. The input will reset the timer each time the input changes condition. If the input does not change conditions in the delay period specified, the controller will signal the event system.
Pulse Delay Type also provides tracking counters for number of transitions and last and current pulse duration. This information is available on the Centurion display.
Number of seconds associated with the delay
Section 50 00-02-0602
Digital Outputs
Field
Description
In Use
Type
Description
Entries are provided for each of the 10 digital output devices. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Active outputs must be set to “In Use” in order to show up on subsequent configuration screens. Once the output is set to “In Use”, the entry turns to bolded text.
NO = Normally Open
NC = Normally Closed
Section 50 00-02-0602
Digital Assignments
Field
Description
Value
State Description
2
Entries are provided for each of the 11 digital assignments.
• Start Annunciation – start delay
• Alarm Annunciation - alarm
• Shutdown Annunciation – fault anytime (not state specific)
10-13
• Running Annunciation – warm-up, stop (electric motor types
12
3
4,17
7
7-13
7-13
9-14 need to rely on motor out)
• Loaded Annunciation – run loaded
• Preheat Output - preheat
• Lube Output – pre-lube / post-lube
• Crank – crank only
• Ignition Output – crank ⇒ ! crank stop ⇒stop
• Fuel Output – crank ⇒ ! crank stop ⇒stop on
List of “In Use” digital outputs to select from.
Section 50 00-02-0602
Analog Inputs
Section 50 00-02-0602
Field
Description
In Use
Type
Dec.
Moving Average
Offset
Span
Min
Max
Units
Section 50
Description
Entries are provided for each of the 20 analog input devices. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Active inputs must be set to “In Use” in order to show up on subsequent configuration screens. Once the input is set to “In Use”, the entry turns to bolded text.
• 0-5V
• 4-20mA
(calculated)
Choose from 0-3 decimal places. Only selectable for inputs 13-20.
Choices are 1, 2, and 4. Adjust to settle unstable readings.
Raw Count Offset, the lowest reading expected from the device.
The span from the lowest to highest reading expected from the device.
Minimum engineering scale. In most cases, 0 addresses a typical application and is the default value. These values are represented as
0 to 10,000 (0.00 to 100.00%). The decimal is implied. For analog inputs, the engineering units are completely at the discretion of the user. An example might be:
A PXT-100 would have a Min=0 and Max=100 (PSIG)
A PXT-30V30 would have a Min=-14.7 and Max=30 (PSIG)
NOTE: Used to define the input scaled in engineering units. Dual scales are not supported.
Maximum engineering scale. These values are represented as 0 to
10,000 (0.00 to 100.00%). The decimal is implied.
NOTE: Used to define the input scaled in engineering units. Dual scales are not supported.
Defines the unit type, span, min, and max. When no other unit of measure is applicable, blank can be selected.
• PSI
• F
• C
• RPM
• KPa
• VDC
• Amp
• mV
• mA
• “Hg
• “WC
• %
00-02-0602
Analog Outputs
Field
Description
In Use
Type
Offset
Span
Min
Max
Section 50
Description
Entries are provided for each of the 6 analog output devices. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Active outputs must be set to “In Use” in order to show up on subsequent configuration screens. Once the output is set to “In Use”, the entry turns to bolded text. mA mA
Raw Count Offset, the lowest reading expected from the device.
Raw Count Span, the span from the lowest to highest reading expected from the device.
Minimum engineering scale. In most cases, 0% addresses a typical application and is the default value. Analog outputs use relative terms of Percent (%) for Min and Max because the position is typically 0% output or 100% output with some proportional change in between.
Maximum engineering scale. In most cases, 100% addresses a typical application and is the default value.
00-02-0602
Thermocouple
Field
Description
In Use
Type
Offset
Description
16 entries are provided for thermocouple devices. The system generated names may be changed to a more descriptive name of your choice.
Active devices must be set to “In Use” in order to show up on subsequent configuration screens. Once the device is set to “In Use”, the entry turns to bolded text.
J Type - Typical for most general purpose applications; provides greater accuracy.
K Type - High temperature applications; less accuracy.
Range is -20 to +20
Section 50 00-02-0602
Setpoints
There are 128 configurable setpoints that may be edited. Setpoints further configure variable range input types such as mpu, analog, or thermocouple by defining a threshold, exception or any other out-of-limit event that may require action. Multiple setpoints are often applied to a process and they may be configured as often as needed to meet changing conditions.
Common alarm and shutdown setpoints a user might configure include:
Setpoints may also be configured for other processes besides alarm and shutdown settings.
For example, a setpoint provides a less flexible, but simpler alternative to controlling the pump’s start and stop functions.
Section 50 00-02-0602
Field
Description
In Use
Signal Type
Base
GT/LT
Value
Description
128 setpoints are provided. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Active setpoints must be set to “In Use” in order to show up on subsequent configuration screens. Once the device is set to “In Use”, the entry turns to bolded text.
Signal type of setpoint
• Unused
• Analog
• Thermocouple
• RPM
• Battery V (tenths)
• PID
Base information is determined by Signal Type selection:
Analog = list of “in use” analog devices to select from
Thermocouple = list of “in use” thermocouple devices to select from
RPM = RPM speed source specified in Miscellaneous dialog
Battery V (tenths) = External DC voltage supply as measured by the controller represented as XX.X Volts
PID = list of “in use” PID devices to select from. Output from PID 1 thru 4.
In reference to value of setpoint.
• GT = Greater Than
• LT = Less Than
Value of setpoint.
Section 50 00-02-0602
Global Timers
Generally, global timers affect process I/O and the arming of associated events. All event types can be associated with, and locked out by Bx, C, or Sx timers.
Section 50 00-02-0602
Field
Description
Value
Description
There are 13 available global timers.
• B1 – The first global timer used for delaying an event condition detection. The timer starts in a running State (10-
13) depending on which ones have been marked “In Use”.
B1 is also known as the “Lockout timer.”
• B2 – The second global timer used for delaying an event condition detection. B2 is also known as a secondary
“Lockout Timer.” This timer runs in parallel with B1.
• C – The delay allowing a clear reading before beginning testing for the arming of Class C events. The typical time for most applications is 2 seconds.
• S1 thru S5 – Users have up to five (5) options to assign additional special global timers to signals. The Sx timers begin concurrently with the Bx timers.
• NF – No Flow: The global delay used for delaying the triggering of a no flow event. This global no flow timer is enabled after B1 expires, and begins timing after the expiration of any of the pulse transition times configured in the digital input dialog.
• Test – Time given to allow for maintenance testing of end devices without triggering a fault or shutdown condition.
The timer initiates when switched to test mode.
• Ignition on Delay – Time delay before the assigned ignition output turns on. This is typically used to delay ignition until engine crank rollover can occur.
• Fuel On Delay – Time delay before the assigned fuel valve output is turned on. This is typically used to delay fuel until ignition has been turned on.
• Ignition Off Delay – Time delay before the assigned ignition output turns off. This is typically used to burn remaining fuel vapors after the fuel valve is turned off.
Timer value.
Section 50 00-02-0602
Maintenance Timers
Field
Description
In Use
Value (Hours)
Description
10 entries are provided for maintenance settings for timer duration.
The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Maintenance timers must be set to “In Use” in order to show up on subsequent configuration screens. Once the timer is set to “In Use”, the entry turns to bolded text.
Timer value units specified in hours.
Section 50 00-02-0602
Events
Field
Description
In Use
Event Type
Section 50
Description
128 programmable events are provided. The system generated names may be changed to a more descriptive name of your choice.
The description name will be displayed on the Centurion controller when there is an event. The field length for description is 23 characters.
Events must be set to “In Use” in order to show up on subsequent configuration screens. Once the event is set to “In Use”, the entry turns to bolded text.
Event type:
• Unused
• Alarm – activates alarm banner and alarm output (if assigned) but does not affect process
• Message – same as alarm except the alarm output is not activated
• Stop – Interrupts process and begins shutdown. Once process is stopped, the state engine recycles. (State 1 – Panel Ready)
• Fault SD – fault shut down. Interrupts process and begins shutdown. Activates shutdown banner and snapshot page is captured. Faults are first out.
00-02-0602
Field
Class
Event Clear
Signal Type
Signal
Description
• ESD – emergency shut down. Same as Fault SD except the process stops and state engine skips all other steps and proceeds to state 19 (Shutdown).
Refers to the Global Timers
• A – always
• B1 or B2
• C
• S1 thru S5
• NF
Action required to clear the fault or event:
• Requires
Reset
• Unused
• Digital
• Setpoint
• State
Tmr
• Maint
Exp
• Sequence
• NF Timer Exp
Signal options are based on Signal Type
• Unused = unavailable
• Digital = list of digital “in use” devices to choose from
• Setpoint = list of “in use” setpoints to choose from
• State Tmr Exp = PANEL READY, STOP ENGINE, or
SHUTDOWN
• Maint Tmr Exp = list of “in use” maintenance timers to choose from
• Sequence = None, Overcrank, Crank Fault, PowerUp,
Start, Stop, Reset, CAN Comms Fail
• NF Timer Exp = Global NF Timer
Section 50 00-02-0602
Startup
Field
Auto Start
Enable Remote on
Power Up
Remote Mode Enable
Digital Input
Use single Digital
Input to Start/Stop
Start (or Start/Stop)
Digital Input
Stop Digital Input
Reset Digital Input
Use single Setpoint to Start/Stop
Start (or Start/Stop)
Setpoint
Stop Setpoint
Description
When set to Yes, automatically proceeds from state 1 (Panel Ready) to next “In Use” state when no shutdown conditions exist.
Yes or No
None or list of “In Use” digital inputs
Yes or No
None or list of “In Use” digital inputs
None or list of “In Use” digital inputs
None or list of “In Use” digital inputs
Yes or No
None or list of “In Use” setpoints
None or list of “In Use” setpoints
Section 50 00-02-0602
RPM Controls
Section 50 00-02-0602
Field
Description
Signal Type
Value
Description
5 entries are provided for RPM controls.
• RPM Control Output
• Cooldown
• Warmup
RPM
RPM
• Wait to Load RPM
• Run Loaded RPM
Signal Type options are based on the RPM type listed in Description
• RPM Control Output = Control Output
• Cooldown RPM = none
• Warmup RPM = none
• Wait to Load RPM = none
• Run Loaded RPM = none
Value of Signal Type:
• For RPM Control Output, a list of “In Use” Control Outputs
• For other Signal types, the target RPM control setpoint for that
State
Section 50 00-02-0602
Control Outputs
Control Outputs allow you to define up to eight (8) outputs to augment control not otherwise defined by digital output assignments. These outputs may be defined as analog output, digital output, single pulsed digital output, or two pulsed digital outputs.
Note that Control Outputs 1 through 4 are directly related to Proportional Integral Derivative
(PID) calculation loops and are further defined in the PID dialog screens. For example, PID 1 is assigned its control from Control Output 1, PID 2 from Control Output 2, and so on.
Section 50 00-02-0602
Field
Description
In Use
Ctrl Output Type
Output 1
Output 2
Description
8 entries are provided for configurable control outputs. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 17 characters.
Active outputs must be set to “In Use” in order to show up on subsequent configuration screens. Once the output is set to “In Use”, the entry turns to bolded text.
• None
• Analog
• 2 Pulsed Digital
• 1 Pulsed Digital
• Digital
List of “In Use” digital or analog outputs. Dependent on Ctrl Output
Type selected.
List of “In Use” digital outputs. This selection is only available for Ctrl
Output Type 2 Pulsed Digital
Increase Max on Time Assign value to increase Max On Time. Set limit of maximum on-time for increase pulses.
Increase OFF Time
Incr. Changeover
Pulse ON Time
Incr. Changeover
Pulse OFF Time
Set fixed off-time for Increase pulses.
Set fixed on-time for single pulse on direction change for increase.
Set fixed off-time for single pulse on direction change for increase.
Decrease Max On time
Set limit of maximum on-time for Decrease pulses.
Decrease OFF Time
Set fixed off-time for Decrease pulses.
Decr. Changeover
Set fixed on-time for single pulse on direction change for Decrease.
Pulse ON Time
Decr. Changeover
Set fixed off-time for single pulse on direction change for Decrease.
Pulse OFF Time
Increase/Decrease Pulse Settings
For Increase Settings
Available when the "Ctrl Output Type" is set to 1 or 2 pulsed digital.
For Decrease Settings and Changeover
Available when the "Ctrl Output Type" is set to 2 pulsed digital.
Section 50 00-02-0602
States
States 6 thru 8 (A) are designated for engine cranking and therefore perform differently than other states. When State 8 (Crank Rest) either times out or meets the permissive, it recycles back to State 6 (Crank Stop). This cycle will continue until a permissive is met in State 7
(Crank).
States 10 thru 13 (B) are the Running states. States 11 and 12 work in tandem to perform load and unload functions. When State 11 (Wait to Load) times out or meets the permissive, it then cycles to State 12. When State 12 (Run Loaded) times out or meets the permissive it cycles back to State 11. This cycle will continue until an event or Stop occurs.
To prevent the cycle, set the time in State 12 to 65535 and do not use a permissive.
Section 50 00-02-0602
Field
State
Description
In Use
Timer (Secs)
Permissive Type
Permissive
Ctrl Out 1
Ctrl Out 2
Ctrl Out 3
Ctrl Out 4
Ctrl Out 5
Ctrl Out 6
Ctrl Out 7
Ctrl Out 8
Section 50
Description
1. Panel Ready
2. Start Delay
3. Preheat
4. Prelube
5. Start Valve
6. Crank Stop
7. Crank
8. Crank Rest
9. Motor On
10. Warmup
11. Wait to Load
12. Run Loaded
13. Cool Down
14. Stop Engine
15. Motor Off
16. Stop Valve
17. Post Lube
18. Restart Delay
19. Shutdown
The state names can be changed. The field length is 13 characters.
NOTE: Crank must have a permissive. Crank Stop and
Crank Rest will not proceed on to other states.
The system generated names may be changed to a more descriptive name of your choice. The field length is 13 characters.
Active states must be set to “In Use” in order to show up on subsequent configuration screens. Once the state is set to “In Use”, the entry turns to bolded text.
When set to 65535, there is No Timeout
Input
• Setpoint
Expiration
• Maint Timer Exp
• NF Timer Exp
When any permissive type is chosen, a list of “In Use” items for that base is shown.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
Value can be 0-100, or if -1, leave alone.
00-02-0602
Miscellaneous
Section 50 00-02-0602
Field
Description
Signal Type
Value
Description
13 miscellaneous entries are provided:
• Number of Crank Attempts
• Magnetic Input Teeth
• RPM
Source
• Crank EndZero RPM Error Signal
• Oil Pressure Source
• Water Temperature Source
• Suction Pressure Source
• Discharge
Source
• Ignition Off in Crank Rest
• Fuel Off in Crank Rest
• Core Temp Adjustment (tenths)
Temp
Units
Signal Type is based on which entry is selected in Description. Not all entries use signal types.
• RPM Source = None, Analog, Magnetic Input
• Crank EndZero RPM Error Signal = None, Digital, Setpoint
• Oil Pressure Source = None, Analog
• Water Temperature Source = None, Analog, Thermocouple
• Suction Pressure Source = None, Analog
• Discharge Pressure Source = None, Analog
Value data is based on which entry is selected in Description. Not all entries require a value.
• Number of Crank Attempts – number of crank attempts
• Magnetic Input Teeth – number of flywheel teeth
• Ignition Off in Crank Rest – Yes or No
• Fuel Off in Crank Rest – Yes or No
• Core Temp Adjustment (tenths) – adjustment degrees in tenths
• Expansion degrees in tenths
• Temperature Units – C (Celsius) or F (Fahrenheit)
Section 50 00-02-0602
PID
Up to four (4) Proportional Integral Derivative (PID) calculation loops may be configured in
MConfigPro. A PID provides a constant feedback loop, in which the PID can correct for a measured process variable against a desired setpoint , output the corrective action to the process and wait for and recalculate the next measurement. The ultimate goal of the PID is to reduce the error to zero.
During the time a PID is enabled, the PID always overrides control output settings found in the states dialog. Recall that PID 1 assumes control of control output 1, PID 2 assumes control of control output 2, and so on.
Field
Description
In Use
Flag
Section 50
Description
4 entries are provided to setup PIDs. The system generated names may be changed to a more descriptive name of your choice. The field length for description is 13 characters.
Active PIDs must be set to “In Use” in order to show up on subsequent configuration screens. Once the PID is set to “In Use”, the entry turns to bolded text.
• Increase Flag – increase on increasing difference
• Decrease Flag – decrease on increasing difference
00-02-0602
Field
Enable Type
Feedback Type
Description
• Not
• All
Enabled
• Run Loaded State
• All Running States
• None
• Analog
• Thermocouple
• RPM
• PID
Options based on the feedback type.
Feedback Base
Setpoint
The desired goal—the target feedback base value.
RampTime (250ms)
Time interval for the PID to calculate error.
Deadband
Value around the setpoint during which the PID will not calculate error.
Minimum Output
Maximum Output
Proportional
Integral
Percentage as minimum output.
Percentage as maximum output.
The output value that is proportional to the change of error.
To prevent the PID from oscillating or overshooting the setpoint, assign a value to “reset” the system to produce zero error, or nudge the process variable to the setpoint . This value is typically set to zero.
Derivative
Value to rate of change of error. This value is typically set to zero.
MaxRate of Change
Percentage rate of change over which would cause harm to the
Override Type
system.
• None
• Digital
• Setpoint
Override Signal
Override Ramp
Amount
Options based on the Override Type.
Determine the increments in a given direction (positive or negative) that the setpoint should be altered to regain balanced processes. In the example of the discharge and suction pressure application, this value would indicate how much the PID should resist its goal in reaching the setpoint.
Override Ramp Time
Time interval value to wait before making the next adjustment
Override Max Change A maximum allowed change. This represents the total amount of change allowed into or out of the ramp amount from the setpoint. The maximum change value should be large enough to effect change.
Section 50 00-02-0602
Comm Port Settings
Field
Description
Value
Description
• Modbus Address Port 1
• Comm Port 1
• Delay Modbus Reply Port 1 (ms)
• BaudRate Port 1
• Comm Port 2
• Delay Modbus Reply Port 2 (ms)
• BaudRate Port 2
Based on entry selected in description
• Comm Port 1 = RS232 or RS485
• BaudRate Port 1 = 9600, 19200, 38400, 57600, or 115200
• Comm Port 2 = RS232 or RS485
• BaudRate Port 2 = 9600, 19200, 38400, 57600, or 115200
Section 50 00-02-0602
Guidelines for Configuring MConfigPro
This section provides guidelines for setting up common configuration items in MConfigPro such as inputs, outputs, setpoints, timers, alarms, and events, etc. for pumps, reciprocating compressors, and screw compressors. For detailed screen/field information, refer to the chapter titled “Main Menu List - Screen Definitions”.
There is a logical sequence to follow when configuring the Centurion. These sequences will be explained in four separate topics. They are:
• Defining the System
Defining the System
The first step in defining the system is to gather information for setting up your analog and/or digital devices and control outputs. For your convenience, you may want to make a checklist of this information for entering into MConfigPro. Once this information has been entered, it will be available for subsequent configuration options.
The following items from the Main Menu List allow you to define the system. Refer to the chapter titled “Main Menu List - Screen Definitions” for information on field options you will be entering.
I/O Scheme
Define the I/O scheme of devices you have:
• Digital Input/Output devices
• Analog Input/Output devices
Control Output
Define Control Outputs, based on control type (analog, digital, 1 or 2 pulsed digital)
Global Timers
What are the manufacturers suggested specifications for protection to create the necessary setpoints? This information can usually be found in the equipment manual that came with the product.
Maintenance Timers
What are the recommended intervals for maintenance? This information can usually be found in the equipment manual that came with the product.
Section 50 00-02-0602
System of Protection
This portion of the configuration allows you to setup events to define when a system will indicate an alarm, a message, or will be shutdown. It also allows for defining how an alarm is cleared.
Shutdowns may be defined by the following types:
• Stop – a controlled stop under normal conditions
• Fault SD – abnormal conditions with minimal consequences (not catastrophic)
• ESD – immediate emergency shutdown
The following items from the Main Menu List allow you to define the system of protection.
Refer to the chapter titled “Main Menu List - Screen Definitions” for information on field options you will be entering.
Events
What steps need to be taken to shutdown equipment on Stop, Fault SD, or ESD conditions?
What types of alarms or messages need to be defined and how will they be acknowledged?
System of Operation
The sequences to be defined for system of operation determine the day-to-day, normal operation of your equipment. The following items from the Main Menu List allow you to define the system of operation. Refer to the chapter titled “Main Menu List - Screen Definitions” for information on field options you will be entering.
Startup
What are the procedures for initiating a start?
RPM Control
Consideration point: If control outputs exist, do they need RPM control?
States
States reflects all steps from evaluating conditions, to controlling start, stop, and running the equipment. The ideal operating condition is Run Loaded.
Miscellaneous
The miscellaneous menu option contains various options to be set that don’t directly relate to process I/O. They control items such as number of crank attempts and oil pressure source and water temperature source.
PID
PID runs as a parallel process to System of Operation. Determine at what point or state type it is enabled.
Section 50 00-02-0602
System of Interface
This sequence determines the communication port setup for downloading the MConfigPro configuration files. It also determines how information is displayed on the Centurion. The following items from the Main Menu List allow you to define the system of interface. Refer to the chapter titled “Main Menu List - Screen Definitions” for information on field options you will be entering.
Comm Port Settings
Determine which type of connection will be used:
• Serial Connection (RS-232 or RS-485)
Specify behavior of communication ports. Specify how to represent various information coming from the comm ports.
Display Screens
This step is only necessary if the system of interface is the Centurion display.
Configuration Download Instructions
Once your configuration files are setup, you may download them to the Centurion controller through either a USB port, or serial port (Com1 or Com2).
Comm. Port Settings
Before you can download files to the Centurion controller, the communication port settings must be established for serial ports Com1 or Com2.
Section 50 00-02-0602
(THIS PAGE INTENTIONALLY LEFT BLANK)
Section 50 00-02-0602
MURPHY, the Murphy logo, Centurion
™, and MConfigPro are registered and/or common law trademarks of
Murphy Industries, Inc. This document, including textual matter and illustrations, is copyright protected by Murphy
Industries, Inc., with all rights reserved. (c) 2005 Murphy Industries, Inc. Other third party product or trade names referenced herein are the property of their respective owners and are used for identification purposes only.
Section 50 00-02-0602
Download
Advertisement
Key features
Easy-to-use interface
Modify configuration features
Download configuration to Centurion
File transfer utilities
Configuration and firmware upgrades
Frequently asked questions
A serial port (RS485/232) or USB 1.1 connection is required for transferring the configuration from MConfigPro to the Centurion.
USB supported operating systems include Win98SE, NT, and XP.
The MConfigPro software and USB driver provide efficient use of your hard drive, using only 35 MB of disk space after installation.