Mitsubishi FDEJ71HKXE2B Specifications


Add to my manuals
170 Pages

advertisement

Mitsubishi FDEJ71HKXE2B Specifications | Manualzz
FDC-HKXR
20. INVERTER DRIVEN MULTI-INDOOR
UNIT HEAT RECOVERY CLIMATE
CONTROL SYSTEM
Simultaneous heating &
Cooling 3 Pipe System
(
)
(OUTDOOR UNIT)
Alternative refrigerant R407C use models
FDCP2001HKXRE2, 2501HKXRE2
(INDOOR UNIT)
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTWJ28HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
90HKXE2B
112HKXE2B
140HKXE2B
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDRJ22HKXE2
28HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDUMJ36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDEJ36HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
112HKXE2B
140HKXE2B
FDKJ22HKXE2
28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
935
FDC-HKXR
CONTENTS
20.1 GENERAL INFORMATION ...................................................................... 937
20.1.1 Specific features ............................................................................... 937
20.1.2 How to read the model name ........................................................... 939
20.1.3 Table of models ................................................................................. 939
20.1.4 Table of indoor units panel (Optional) ............................................ 939
20.2 SELECTION DATA................................................................................... 940
20.2.1 Specifications .................................................................................... 940
20.2.2 Range of usage & limitations ........................................................... 966
20.2.3 Exterior dimensions.......................................................................... 967
20.2.4 Exterior appearance.......................................................................... 993
20.2.5 Piping system .................................................................................... 996
20.2.6 Selection chart .................................................................................. 997
20.2.7 Characteristics of fan ....................................................................... 1011
20.2.8 Noise level ......................................................................................... 1016
20.3 ELECTRICAL DATA ................................................................................ 1022
20.3.1 Electrical wiring ................................................................................ 1022
20.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 1032
20.5 APPLICATION DATA ............................................................................... 1045
20.5.1 Installation of indoor unit ................................................................. 1046
20.5.2 Installation of the remote controller (Optional Parts) .................... 1046
20.5.3 Installation of outdoor unit............................................................... 1046
20.5.4 Refrigerant piping ............................................................................. 1051
20.5.5 Electrical wiring ................................................................................ 1058
20.5.6 Test run .............................................................................................. 1066
20.6 MAINTENANCE DATA............................................................................. 1068
20.6.1 Diagnosis of Microcomputer circuit ................................................ 1068
936
FDC-HKXR
20.1 GENERAL INFORMATION
20.1.1 Specific features
(1) Fuzzy control
(a) Response speed and stability are enhanced.
• The system automatically controls changes of return air temperature, set temperature and room temperature according to
the fuzzy control.
• The system response speed, can keep room temperature constant, and can adjust room temperature to set temperature
quickly.
Inverter Hz
Set temp.
Temp. difference
Gradient of temp.
operation
FUZZY operation
Temp.
(Return air thermistor)
E.E.V. pulse
(b) Elimination of temperature irregularity as the time of operation ON/OFF control
• The system finely controls the compressor to room temperature according to the temperature sensor, air conditions room
temperature consistently and improves cooling or heating feeling in each room (or minimize influence of shutdown in
other room).
(2) Super lynk system
• Non polar 2-core signal wires for indoor, outdoor units by means of the automatic polarity selection.
• In addition, the max. 48 units can be controlled with a pair of signal wires. The high speed transmission method same as
the computer network system [start up of 48 units can be completed within a few seconds by the determination of operation
mode and the start of operation].
• As separate power supplies for the indoor and the outdoor units are employed, a pair of 2 signal wires only are required for
the inter connecting wiring of indoor and outdoor units regardless of the number of units so that the installation work can
be simplified, the cost of wiring work can be curtailed and causes of wiring error can be minimized.
937
FDC-HKXR
(3) Installation of automatic address setting function
• The address setting method are divided into three types according to wiring method: “Automatic Address Setting,”
“Remote control Address Setting.” and “Manual Address Setting.” In case of the Automatic Address Setting, no
address needs be set as usual.
(4) Connectable indoor capacity
Capacity from 50% to 130% is possible.
• FDCP2001HKXRE2
Number of connectable units: 1 to 8 units
Connectable capacity: 11000 ~ 29200 W
• FDCP2501HKXRE2
Number of connectable units : 1 to 8 units
Connectable capacity: 13200 ~ 37100 W
(5) Cooling opetation down to -5˚C outdoor temperature
(6) Indoor units are available with 9 capacities, in 9 types and 54 models.
● 9 capacities…22(0.8 HP), 28(1 HP), 36(1.25 HP), 45(1.6 HP), 56(22 HP), 71(2.5 HP), 90(3.2 HP), 112(4 HP) and 140(5 HP).
● 9 types…Ceiling recessed type(FDT), 2-way outlet ceiling recessed type(FDTW), 1-way outlet ceiling recessed type(FDTS),
Cassetteria type(FDR), Satellite ducted type(FDUM), Ceiling suspension type(FDE), Wall mounted type(FDK), Floor standing
exposed type(FDFL) and Floor standing hidden type(FDFU).
(7) Vertical blow or horizontal blow type can be selected for the outdoor unit.
horizontal blow
Standard
Vertical blow
Using an adapter
(Optional)
(8) Long piping design offeres One way piping length of 100 m
● Indoor and outdoor units can have a level difference of up to 50 m, with a one way piping length of up to 100 m. This is the topclass long piping design in the industry. A level difference of as much as 15 m between indoor units ensures that the system can
meet a wide variety of air conditioning requirements in any building.
(9) Layout free refrigerant piping
The branch type piping makes the system flexible enough to satisfy any layout plan on the floor or in a room.
(10) Improvement of serviceability
(a) Failures of indoor unit and outdoor units are shown on the liquid crystal display on the remote controller.
● Failures of indoor unit and outdoor units can be checked by remote controller.
(b) Easy checking of outdoor inspection LED.
● The LED can be checked without removing the service panel, and faulty units can be easily indentified out of several units.
938
FDC-HKXR
20.1.2 How to read the model name
Example:
FDC
P 2001 H KXR E
2
CE marking model
Application power source...See the specifications
Multi KXR series
Heat pump type
Nominal capacity
R407C models
Model name
Indoor unit
: FDT, FDTW, FDTS, FDR, FDUM
FDE, FDK, FDFL, FDFU
Outdoor unit : FDC
20.1.3 Table of models
Capacity
Model
22
28
36
45
56
71
90
112
140
Ceiling recessed type
(FDT)
2-way outlet ceiling recessed type
(FDTW)
1-way outlet ceiling recessed type
(FDTS)
Cassetteria type
(FDR)
Stellite ducted type
(FDUM)
Ceiling suspension type
(FDE)
Wall mounted type
(FDK)
Floor standing exposed type
(FDFL)
Floor standing hidden type
(FDFU)
Outdoor units tobe combined
FDC
FDCP224HKXRE2
(8 Horse Power)
FDCP280HKXRE2
(10 Horse Power)
20.1.4 Table of indoor units panel (Optional)
Model
FDT
FDTW
(Standard type)
FDTW
(Attachment of ceiling material type)
FDTS
FDR
(Silent type)
FDR
(Canvas type)
Parts Model
Capacity:28,36,45,56,
71,90,112,140
Capacity:28,45,56
Capacity:71,90
Capacity:112,140
Capacity:28,45,56
Capacity:71,90
Capacity:112,140
Capacity:22,28,36,45
Capacity:71
Capacity:22,28,45,56
Capacity:71,90
Capacity:112,140
Capacity:22,28,45,56
Capacity:71,90
Capacity:112,140
T-PSA-32W-E
TW-PSA-22W-E
TW-PSA-32W-E
TW-PSA-42W-E
TW-PSB-28W-E
TW-PSB-38W-E
TW-PSB-48W-E
TS-PSA-26W-E
TS-PSA-36W-E
R-PNLS-26W-E
R-PNLS-36W-E
R-PNLS-46W-E
R-PNLC-26W-E
R-PNLC-36W-E
R-PNLC-46W-E
939
FDC-HKXR
20.2 SELECTION DATA
20.2.1 Specifications
(1) Indoor unit
(a) Ceiling recessed type (FDT)
Models FDTJ28HKXE2, 36HKXE2
Models
Item
FDTJ28HKXE2(3)
FDTJ36HKXE2(3)
Nominal cooling capacity*1
W
2800
3600
Nominal heating capacity*2
W
3200
4000
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 37 Me: 34 Lo: 33
mm
Unit:260
840
840
Panel:30
950
950
Unit:24 Panel:7
kg
Refrigerant equipment
Heat exchanger
Louver fine & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Turbo fan 1
Motor
W
17 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 12 Me: 10 Lo: 9
Fresh air intake
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 6.35(1/4"), Gas line: 12.7(1/2")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas line)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTJ28,36 type
Panel Part No.
T-PSA-32W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
940
FDC-HKXR
Models FDTJ45HKXE2, 56HKXE2, 71HKXE2
Models
FDTJ45HKXE2(3)
FDTJ56HKXE2(3)
W
4500
5600
7100
W
5000
6300
8000
Item
1
Nominal cooling capacity*
Nominal heating capacity*2
Power source
FDTJ71HKXE2(3)
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 38 Me: 35 Lo: 34
mm
Unit:260
kg
Hi: 40 Me: 38 Lo: 36
840
840
Panel:30
950
950
Unit:24 Panel:7
Refrigerant equipment
Heat exchanger
Louver fine & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Turbo fan
Motor
1
20 1
W
25 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 15 Me: 12 Lo: 10
Fresh air intake
Hi: 16 Me: 13 Lo: 11
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
mm(in)
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTJ45,56,71 type
Panel Part No.
T-PSA-32W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
941
FDC-HKXR
Models FDTJ90HKXE2, 112HKXE2, 140HKXE2
Models
FDTJ90HKXE2(3)
FDTJ112HKXE2(3)
W
9000
11200
14000
W
10000
12500
16000
Item
1
Nominal cooling capacity*
Nominal heating capacity*2
Power source
FDTJ140HKXE2(3)
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 42 Me: 40 Lo: 38
Unit: 260
Panel:30
mm
kg
840
950
Hi: 49 Me:46 Lo: 42
840
950
Unit: 320
Panel:30
Unit:24 Panel:7
Hi: 50 Me: 47 Lo: 45
840
950
Unit:28 Panel:7
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Turbo fan
Motor
Unit:30 Panel:7
1
80 1
50 1
W
840
950
Starting method
130 1
Line starting
Air flow(Standard)
Hi: 21 Me: 15 Lo: 12
CMM
Hi: 28 Me: 24 Lo: 21
Fresh air intake
Hi: 30 Me: 26 Lo: 22
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
mm(in)
Liquid line: 9.52(3/8")
Gas line: 19.05(3/4")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTJ90,112,140 type
Panel Part No.
T-PSA-32W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
942
FDC-HKXR
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B
Models
Item
FDTWJ28HKXE2B(3)
FDTWJ45HKXE2B(3)
FDTWJ56HKXE2B(3)
Nominal cooling capacity*1
W
2800
4500
5600
Nominal heating capacity*2
W
3200
5000
6300
Power source
1 Phase 220/240V 50Hz
Noise level
dB(A)
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 39 Me:36 Lo: 33
mm
Unit:280 817 620
kg
Panel:8
1055
680
Unit:19 Panel:7
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Turbo fan 1
Motor
30 1
W
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 14 Me: 12 Lo: 10
Fresh air intake
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
mm(in)
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTWJ28,45,56 type
Panel Part No.
Standard type
Attachment of ceiling material type
TW-PSA-22W-E
TW-PSB-28W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
943
FDC-HKXR
Models FDTWJ71HKXE2B, 90HKXE2B
Models
FDTWJ71HKXE2B(3)
Item
FDTWJ90HKXE2B(3)
Nominal cooling capacity*1
W
7100
9000
Nominal heating capacity*2
W
8000
10000
dB(A)
Hi: 41 Me: 38 Lo: 35
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
Hi: 41 Me: 39 Lo: 36
Unit:330
1054
kg
620
Panel:8
1300
680
Unit:26 Panel:9
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillay tube
Air handling equipment
Fan type & Q'ty
Turbo fan 1
Motor
35 1
W
40 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 16 Me: 13 Lo: 11
Hi: 19 Me: 16 Lo: 12
Fresh air intake
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8"),Gas line: 15.88(5/8")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTWJ71,90 type
Panel Part No.
Standard type
Attachment of ceiling material type
TW-PSA-32W-E
TW-PSB-38W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
944
FDC-HKXR
Models FDTWJ112HKXE2B, 140HKXE2B
Models
FDTWJ112HKXE2B(3)
Item
FDTWJ140HKXE2B(3)
1
Nominal cooling capacity*
W
11200
14000
Nominal heating capacity*2
W
12500
16000
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 44 Me: 41 Lo: 38
mm
Hi: 45 Me: 42 Lo: 39
Unit:345
1524
kg
620
Panel:8
1770
Unit:38 Panel:11
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Turbo fan
Motor
680
40
W
2
50
2
Starting method
2
Line starting
Air flow(Standard)
Hi: 28 Me: 25 Lo: 23
CMM
Hi: 32 Me: 28 Lo: 24
Fresh air intake
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8"),Gas line: 19.05(3/4")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas linse)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTWJ112,140 type
Panel Part No.
Standard type
Attachment of ceiling material type
TW-PSA-42W-E
TW-PSB-48W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
945
FDC-HKXR
(c) 1-way outlet ceiling recessed type (FDTS)
Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B
Model
Item
FDTSJ22HKXE2B(3)
FDTSJ28HKXE2B(3)
FDTSJ36HKXE2B(3)
Nominal cooling capacity*1
W
2200
2800
3600
Nominal heating capacity*2
W
2500
3200
4000
dB(A)
Hi: 39 Lo: 38
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
mm
Net weight
Kg
Hi: 40 Me: 39 Lo: 38
Unit:194
1040
650
Panel:10
1290
770
Unit:26 Panel:6
Refrigerant equipment
Heat exchanger
Louver fine & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan 2
Motor
35
W
Starting method
1
Line starting
Air flow(Standard)
Hi: 11 Lo: 8
CMM
Hi: 12 Me: 11 Lo: 10
Fresh air intake
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 6.35(1/4"),Gas line: 12.7(1/2")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Model
FDTSJ22,28,36 type
Panel Part No.
With Auto Swing
TS-PSA-26W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for Europern nations which
require CE marking.
946
FDC-HKXR
Models FDTSJ45HKXE2B, 71HKXE2B
Model
FDTSJ45HKXE2B(3)
Item
FDTSJ71HKXE2B(3)
1
Nominal cooling capacity*
W
4500
7100
Nominal heating capacity*2
W
5000
8000
Power source
1 Phase 220/240V 50Hz
Noise level
dB(A)
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 43 Me: 40 Lo: 38
Unit:194
Panel:10
mm
kg
1040
1290
Hi: 44 Me: 40 Lo: 38
Unit:194
Panel:10
650
770
Unit:26 Panel:6
Refrigerant equipment
Heat exchanger
1300
1500
650
790
Unit:30 Panel:7
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan 2
Motor
Centrifugal fan 4
40 1
W
25 2
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 14 Me: 12 Lo: 10
Hi: 18 Me: 15 Lo: 12
Fresh air intake
Possible
Air filter, Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
mm(in)
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Decorative Panel
Optional parts
Outdoor units to be combined
FDCP2001HKXRE2, 2501HKXRE2
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
1
27
19
35
24
Heating*2
20
7
6
Operation
Cooling*
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Item
Panel Part No.
With Auto Swing
Model
FDTSJ45 type
TS-PSA-26W-E
FDTSJ71 type
TS-PSA-36W-E
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
947
FDC-HKXR
(d) Cassetteria type (FDR)
Models FDRJ22HKXE2, 28HKXE2
Models
FDRJ22HKXE2(4)
Item
Air inlet panel
Panel model (Option)
FDRJ28HKXE2(4)
Silent panel
Canvas panel
Silent panel
Canvas panel
R-PNLS-26W-E
R-PNLC-26W-E
R-PNLS-26W-E
R-PNLC-26W-E
Nominal cooling capacity*1
W
2200
2800
Nominal heating capacity*2
W
2500
3200
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
kg
Hi: 41 Me: 39 Lo: 36
Hi: 42 Me: 40 Lo: 37
Hi: 42 Me: 40 Lo: 37
Hi: 43 Me: 41 Lo: 38
Unit:355 750 635
Unit:(299+α) 750 635 Unit:355 750 635
Unit:(299+α) 750 635
Panel:10 1040 750 Panel:10 864 585
Panel:10 1040 750 Panel:10 864 585
Unit:30
Panel:7
Unit:30
Panel:5
Unit:30
Panel:7
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Unit:30
Panel:5
Centrifugal fan 2
Motor
40 1
W
50 1
Starting method
Line starting
Air flow(Standard)
Hi: 10 Me: 9 Lo: 8
CMM
Available static pressure
( at Me)
Pa(mmAq)
Hi: 12 Me: 11 Lo: 10
Standard:45(4.5), Hi speed:85(8.5)
Fresh air intake
Side or back
Air filter Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 6.35(1/4"),Gas line: 12.7(1/2")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Silent panel, Canvas panel, Canvas duct
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1)The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2)This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3)Canvas panel is used in combination with following canvas duct
Canvas duct: HA01503
(4)The number "2",following the type of each model,represents"CE-marked model"especially for European Union, and for European nations which
require CE marking.
(5)Add the canvas duct lenght to the unit height for the canvas type.
948
FDC-HKXR
Models FDRJ45HKXE2, 56HKXE2
Models
FDRJ45HKXE2(4)
Item
Air inlet panel
Panel model (Option)
FDRJ56HKXE2(4)
Silent panel
Canvas panel
Silent panel
Canvas panel
R-PNLS-26W-E
R-PNLC-26W-E
R-PNLS-26W-E
R-PNLC-26W-E
Nominal cooling capacity*1
W
4500
5600
Nominal heating capacity*2
W
5000
6300
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
kg
Hi: 43 Me: 40 Lo: 37
Hi: 44 Me: 41 Lo: 38
Hi:43 Me: 40 Lo: 37
Unit:(299+α) 750 635 Unit:355 750 635
Unit:(299+α) 750 635
Unit:355 750 635
Panel:10 1040 750 Panel:10 864 585
Panel:10 1040 750 Panel:10 864 585
Unit:30
Panel:7
Unit:30
Panel:5
Unit:30
Panel:7
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan
Motor
Hi: 44 Me: 41 Lo: 38
W
Unit:30
Panel:5
2
55 1
Starting method
Line starting
Air flow(Standard)
Available static pressure
( at Me)
CMM
Hi: 14 Me: 12 Lo: 11
Pa(mmAq)
Standard:50(5.0), Hi speed:85(8.5)
Fresh air intake
Side or back
Air filter Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Silent panel, Canvas panel, Canvas duct
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1)The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
2
20
7
6
Operation
Heating*
Standards
ISO-T1,JIS B8616
(2)This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3)Canvas panel is used in combination with following canvas duct
Canvas duct: HA01503
(4)The number "2",following the type of each model,represents"CE-marked model"especially for European Union, and for Europearn nations which
require CE marking.
(5)Add the canvas duct lenght to the unit height for the canvas type.
949
FDC-HKXR
Models FDRJ71HKXE2, 90HKXE2
Models
FDRJ71HKXE2(4)
Item
Air inlet panel
Panel model (Option)
FDRJ90HKXE2(4)
Silent panel
Canvas panel
Silent panel
Canvas panel
R-PNLS-36W-E
R-PNLC-36W-E
R-PNLS-36W-E
R-PNLC-36W-E
Nominal cooling capacity*1
W
7100
9000
Nominal heating capacity*2
W
8000
10000
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
kg
Hi: 43 Me: 40 Lo: 37
Hi: 44 Me: 41 Lo: 38
Hi: 43 Me: 40 Lo: 37
Hi: 44 Me: 41 Lo: 38
Unit:(299+α) 950 635 Unit:355 950 635
Unit:(299+α) 950 635
Unit:355 950 635
Panel:10 1240 750 Panel:10 1064 585
Panel:10 1240 750 Panel:10 1064 585
Unit:35
Panel:8
Unit:35
Panel:6
Unit:35
Panel:8
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Unit:35
Panel:6
Centrifugal fan 2
Motor
W
100 1
90 1
Starting method
Line starting
Air flow(Standard)
Hi: 18 Me: 16 Lo: 14
CMM
Available static pressure
( at Me)
Pa(mmAp)
Hi: 20 Me: 18 Lo: 15
Standard:45(4.5), Hi speed:80(8.0)
Fresh air intake
Side or back
Air filter Q'ty
Long life filter
Shock & vibration absorber
1(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 9.52(3/8"),Gas line: 15.88(5/8")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Silent panel, Canvas panel, Canvas duct
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1)The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
2
20
7
6
Operation
Heating*
Standards
ISO-T1,JIS B8616
(2)This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3)Canvas panel is used in combination with following canvas duct
Canvas duct: HA01490
(4)The number "2",following the type of each model,represents"CE-marked model"especially for European Union, and for European nations which
require CE marking.
(5)Add the canvas duct lenght to the unit height for the canvas type.
950
FDC-HKXR
Models FDRJ112HKXE2, 140HKXE2
Models
FDRJ112HKXE2(4)
Item
Air inlet panel
Panel model (Option)
FDRJ140HKXE2(4)
Silent panel
Canvas panel
Silent panel
Canvas panel
R-PNLS-46W-E
R-PNLC-46W-E
R-PNLS-46W-E
R-PNLC-46W-E
Nominal cooling capacity*1
W
11200
14000
Nominal heating capacity*2
W
12500
16000
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
dB(A)
Hi: 45 Me: 42 Lo: 38
mm
Unit:406 1370 635
Panel:10 1660 750
kg
Unit:50
Panel:9
Hi: 46 Me: 43 Lo: 39
Hi: 46 Me: 43 Lo: 39
Unit:(350+α) 1370 635 Unit:406 1370 635
Panel:10 1484 585
Panel:10 1660 750
Unit:50
Panel:7
Unit:(350+α) 1370 635
Panel:10 1484 585
Unit:52
Panel:9
Unit:52
Panel:7
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Hi: 47 Me: 44 Lo: 40
Centrifugal fan 3
Motor
W
45 1,
90 1
50 1,
Starting method
100 1
Line starting
Air flow(Standard)
Hi: 28 Me: 25 Lo: 22
CMM
Available static pressure
( at Me)
Pa(mmAq)
Hi: 34 Me: 31 Lo: 27
Standard:50(5.0), Hi speed:80(8.0)
Fresh air intake
Side or back
Air filter Q'ty
Long life filter
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 9.52(3/8"),Gas line: 19.05(3/4")
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
Silent panel, Canvas panel, Canvas duct
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1)The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
2
20
7
6
Operation
Heating*
Standards
ISO-T1,JIS B8616
(2)This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3)Canvas panel is used in combination with following canvas duct
Canvas duct: HA01484
(4)The number "2",following the type of each model,represents"CE-marked model"especially for European Union, and for European nations which
require CE marking.
(5)Add the canvas duct lenght to the unit height for the canvas type.
951
FDC-HKXR
(e) Satellite ducted type (FDUM)
Models FDUMJ36HKXE2, 45HKXE2
Models
FDUMJ36HKXE2(3)
Item
FDUMJ45HKXE2(3)
Nominal cooling capacity*1
W
3600
4500
Nominal heating capacity*2
W
4000
5000
dB(A)
Hi: 34 Me: 32 Lo: 29
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 35 Me: 32 Lo: 29
mm
299
kg
750
635
34
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan
Motor
2
50 1
W
55 1
Starting method
Line starting
Air flow(Standard)
Hi: 12 Me: 11 Lo: 10
CMM
Available static pressure
( at Me)
Pa(mmAq)
Hi: 14 Me: 12 Lo: 11
Standard:50(5), Hi speed:85(8.5)
Fresh air intake
Side
_
Air filter, Q'ty
Shock & vibration absorber
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 6.35(1/4"),Gas line: 12.7(1/2")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
952
FDC-HKXR
Models FDUMJ56HKXE2, 71HKXE2, 90HKXE2
Models
Item
FDUMJ56HKXE2(3)
FDUMJ71HKXE2(3)
FDUMJ90HKXE2(3)
1
Nominal cooling capacity*
W
5600
7100
9000
Nominal heating capacity*2
W
6300
8000
10000
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
Hi: 35 Me: 32 Lo: 29
299
750
kg
Hi: 35 Me: 32 Lo: 29
635
299
34
Hi: 36 Me: 33 Lo: 30
950
635
40
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan 2
Motor
W
55 1
90 1
Starting method
100 1
Line starting
Air flow(Standard)
CMM
Available static pressure
( at Me)
Hi: 14 Me: 12 Lo: 11
Pa(mmAq)
Hi: 18 Me: 16 Lo: 14
Hi: 20 Me: 18 Lo: 15
Standard:50(5), Hi speed:85(8.5)
Fresh air intake
Side
_
Air filter, Q'ty
Shock & vibration absorber
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8"),Gas line: 15.88(5/8")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
953
FDC-HKXR
Models FDUMJ112HKXE2, 140HKXE2
Models
FDUMJ112HKXE2(3)
Item
FDUMJ140HKXE2(3)
Nominal cooling capacity*1
W
11200
14000
Nominal heating capacity*2
W
12500
16000
dB(A)
Hi: 38 Me: 35 Lo: 32
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 39 Me: 37 Lo: 34
mm
350
kg
1370
635
57
59
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan 3
Motor
W
45 1,
50 1, 100 1
90 1
Starting method
Line starting
Air flow(Standard)
Available static pressure
( at Me)
CMM
Hi: 28 Me: 25 Lo: 22
Hi: 34 Me: 31 Lo: 27
Pa(mmAq)
Standard:60(6), Hi speed:90(9)
Standard:60(6), Hi speed:85(8.5)
Fresh air intake
Side
_
Air filter, Q'ty
Shock & vibration absorber
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8"),Gas line: 19.05(3/4")
mm(in)
Flare piping
Connecting method
Connectable with VP25
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
954
FDC-HKXR
(f) Ceiling suspension type (FDE)
Models FDEJ36HKXE2B, 45HKXE2B
Models
Item
FDEJ36HKXE2B(3)
FDEJ45HKXE2B(3)
4500
Nominal cooling capacity*1
W
3600
Nominal heating capacity*2
W
4000
5000
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 43 Me:40 Lo: 38
mm
184
kg
1000
650
22
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve + Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan 2
Motor
40 1
W
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 14 Me: 12 Lo: 10
Fresh air intake
Not possible
Air filter, Q'ty
Polypropylene net
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 6.35(1/4"), Gas line: 12.7(1/2")
Flare piping
Connecting method
Connectable with VP20
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
955
FDC-HKXR
Models FDEJ56HKXE2B, 71HKXE2B
Models
FDEJ56HKXE2B(3)
Item
FDEJ71HKXE2B(3)
1
Nominal cooling capacity*
W
5600
7100
Nominal heating capacity*2
W
6300
8000
dB(A)
Hi: 43 Me:40 Lo: 38
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
184
kg
1000
Hi: 44 Me:40 Lo: 38
650
184
1260
22
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve + Capillary tube
Air handling equipment
Fan type & Q'ty
650
27
Centrifugal fan 2
Centrifugal fan 4
W
40 1
25 2
CMM
Hi: 14 Me: 12 Lo: 10
Motor
Starting method
Line starting
Air flow(Standard)
Fresh air intake
Hi: 18 Me: 15 Lo: 12
Not possible
Air filter, Q'ty
Polypropylene net
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 9.52(3/8"), Gas line: 15.88(5/8")
Flare piping
Connecting method
Connectable with VP20
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
956
FDC-HKXR
Models FDEJ112HKXE2B, 140HKXE2B
Models
FDEJ112HKXE2B(3)
Item
FDEJ140HKXE2B(3)
1
Nominal cooling capacity*
W
11200
14000
Nominal heating capacity*2
W
12500
16000
dB(A)
Hi: 49 Me:46 Lo: 42
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
239
kg
1260
Hi: 50 Me:47 Lo: 42
650
239
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve +Capillary tube
Air handling equipment
Fan type & Q'ty
650
40
Refrigerant equipment
Heat exchanger
Centrifugal fan
Centrifugal fan
3
W
35 1 + 55 1
CMM
Hi: 28 Me: 25 Lo: 22
Motor
1470
34
4
55 2
Starting method
Line starting
Air flow(Standard)
Fresh air intake
Hi: 34 Me: 30 Lo: 26
Not possible
Polypropylene net
Air filter, Q'ty
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 9.52(3/8"), Gas line: 19.05(3/4")
Flare piping
Connecting method
Connectable with VP20
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
957
FDC-HKXR
(g) Wall mounted type (FDK)
Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2
Models
Item
FDKJ22HKXE2(3)
FDKJ28HKXE2(3)
FDKJ36HKXE2(3)
FDKJ45HKXE2(3)
Nominal cooling capacity*1
W
2200
2800
3600
4500
Nominal heating capacity*2
W
2500
3200
4000
5000
dB(A)
Hi: 42 Lo: 37
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 42 Me:40 Lo: 37
mm
375
kg
950
Hi: 44 Me:41 Lo: 37
194
19
Refrigerant equipment
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve + Capillary tube
Air handling equipment
Fan type & Q'ty
Tangential fan 1
Motor
W
30 1
35 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 9 Lo: 8
Hi: 10 Me: 9 Lo: 8
Fresh air intake
Hi: 11.5 Me: 10 Lo: 8
Not possible
Air filter, Q'ty
Polypropylene net
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 6.35(1/4"), Gas line: 12.7(1/2")
Flare piping
Connecting method
Connectable with I.D. 16mm
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
Accessories
—
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
958
FDC-HKXR
Models FDKJ56HKXE2, 71HKXE2
Model
FDKJ56HKXE2(3)
FDKJ71HKXE2(3)
W
5600
7100
W
6300
Item
1
Nominal cooling capacity*
Nominal heating capacity*2
8000
Power source
1 Phase 220/240V 50Hz
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Hi: 46 Me:43 Lo: 39
mm
375 1148
kg
Hi: 47 Me:44 Lo: 40
194
375
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve + Capillary tube
Air handling equipment
Fan type & Q'ty
Tangential fan 1
W
194
22
Refrigerant equipment
Heat exchanger
Motor
1436
20
Tangential fan 2
40 1
45 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 17 Me: 15 Lo: 13
Fresh air intake
Hi: 21 Me: 18 Lo: 15
Not possible
Air filter, Q'ty
Polypropylene net
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKX-S-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 9.52(3/8"), Gas line: 15.88(5/8")
Flare piping
Connecting method
Connectable with I.D. 16mm
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
959
FDC-HKXR
(h) Floor standing exposed type (FDFL)
Models FDFLJ28HKXE2, 45HKXE2, 71HKXE2
Model
Item
FDFLJ28HKXE2(3)
FDFLJ45HKXE2(3)
FDFLJ71HKXE2(3)
Nominal cooling capacity*1
W
2800
4500
7100
Nominal heating capacity*2
W
3200
5000
8000
dB(A)
Hi: 41 Me:38 Lo: 36
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
630
kg
Hi: 43 Me:41 Lo: 40
1196
225
630
32
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve + Capillary tube
Air handling equipment
Fan type & Q'ty
Centrifugal fan
W
2
30 1
40 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 12 Me: 11 Lo: 10
Hi: 14 Me: 12 Lo: 10
Fresh air intake
Hi: 18 Me: 15 Lo: 12
Not possible
Air filter, Q'ty
Polypropylene net
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKXFL-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
mm(in)
Flare piping
Connecting method
Connectable with VP20
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
960
225
40
Refrigerant equipment
Heat exchanger
Motor
1481
FDC-HKXR
(i) Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2
Model
Item
FDFUJ28HKXE2(3)
FDFUJ45HKXE2(3)
FDFUJ56HKXE2(3)
FDFUJ71HKXE2(3)
Nominal cooling capacity*1
W
2800
4500
5600
7100
Nominal heating capacity*2
W
3200
5000
6300
8000
dB(A)
Hi: 41 Me:38 Lo: 36
Power source
1 Phase 220/240V 50Hz
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
mm
Hi: 43 Me:41 Lo: 40
630
1077
kg
225
630
25
Louver fins & inner grooved tubing
Refrigerant control
Electronic Expansion Valve + Capillary tube
Centrifugal fan
Motor
W
225
32
Refrigerant equipment
Heat exchanger
Air handling equipment
Fan type & Q'ty
1362
2
30 1
40 1
Starting method
Line starting
Air flow(Standard)
CMM
Hi: 12 Me: 11 Lo: 10
Hi: 14 Me: 12 Lo: 10
Fresh air intake
Hi: 18 Me: 15 Lo: 12
Not possible
Air filter, Q'ty
Polypropylene net
Shock & vibration absorber
2(Washable)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane foam
Operation control
Operation switch
Remote control switch (Optional:RCD-HKXFL-E2)
Room temperature control
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Safety equipment
Installation data
Refrigerant piping size
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
mm(in)
Flare piping
Connecting method
Connectable with VP20
Drain hose
Necessary (both Liquid & Gas lines)
Insulation for piping
Mounting kit
_
Accessories
Optional parts
FDCP2001HKXRE2, 2501HKXRE2
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Cooling*1
27
19
35
24
Heating*2
20
7
6
Operation
Standards
ISO-T1,JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
961
FDC-HKXR
(2) Outdoor unit
Models FDCP2001HKXRE2, 2501HKXRE2
Models
Item
FDCP2001HKXRE2(3)
Power source
FDCP2501HKXRE2(3)
3 Phase 380/415V 50Hz
Nominal cooling capacity*1
W
22400
Nominal heating capacity*2
W
25000
28000
31500
60
dB(A)
Noise level
Exterior dimensions
Height
Width
Depth
mm
Net weight
1700
kg
Refrigerant equipment
compressor type & Q' ty
Motor
1350
600
340
361
RS5555HAS11
RS5570HAS11
5.5
kW
7.5
Starting method
Direct start
Capacity control
%
Crankcase heater
W
100 ~ 22.0
40
Louver fines & inner grooved tubing
Heat exchanger
Refrigerant control
Expansion Valve +Capillary tube
Refrigerant
R407C
Quantity
kg
11
Refrigerant oil
2.5 (MA32)
Defrost control
MC controlled De-Icer
Air handling equipment
Fan type & Q'ty
Centrifugal fan 2
Motor
W
100 2
Starting method
Direct start
Air flow(Standard)
CMM
175
Shock & vibration absorber
Rubber mount (for compressor)
Compressor overheat protection, overeurrent protection, power transformer overheating
protection, abnormal high pressure protection
Safety equipment
Installation data
Refrigerant piping size
mm(in)
Liquid line: 12.7(1/2")
Intake line: 25.4(1")
Discharge line: 19.05(3/4")
Connecting method
Liquid line: 12.7(1/2")
Intake line: 28.58(11/8")
Discharge line: 19.05(3/4")
Brazing
Drain
Hole for drain( 20
Insulation for piping
6pcs)
Necessary (both Liquid &Gas lines)
Discharge gas side connection piping (for pervice valve and back direction connections),
intake gas side connection piping (for operation valve and back direction connections)
Accessories
Indoor units to be combined
FDTJ28, 36, 45, 56, 71, 90, 112, 140HKXE2
FDTWJ28, 45, 56, 71, 90, 112, 140HKXE2B
FDTSJ22, 28, 36, 45, 71HKXE2B
FDRJ22, 28, 45, 56, 71, 90, 112, 140HKXE2
FDUMJ36, 45, 56, 71, 90, 112, 140HKXE2
FDEJ36, 45, 56, 71, 112, 140HKXE2B
FDKJ22, 28, 36, 45, 56, 71HKXE2
FDFLJ28, 45, 71HKXE2
FDFUJ28, 45, 56, 71HKXE2
Notes (1) The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in JIS-B8616.
(2) The refrigerant quantity in the connecting pipe is not included Charge it additionally at the site.
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
(4) When an individual flow divide controller is used a pipe part set is required.
Flow divide controller part No. list
Type
Individual flow divide controller
Part No.
FDCP2001,2501
HPFD01R-E
Type
For 3 pipes (for horizontal division)
For 3 pipes (for vertical division)
962
Part No.
FDCP2001,2501
DIS-IKXR3-E
DIS-VIKXR3-E
FDC-HKXR
(3) Operation chart
Since the Multi KXR series air conditioner units are free multitype to which the indoor units of different capacity and different
model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual
operation characteristics of indoor and outdoor units are shown. For the combined operation characteristics, calculate them with the
method shown in the next page.
(a) Operating characteristic of outdoor unit
Models
Item
Cooling input
kW
Heating input
Cooling running current
A
Heating running current
Inrush current (MAX.)
(380 V/415 V)
FDCP2001HKXRE2
FDCP2501HKXRE2
10.2/10.2
12.4/12.4
8.4/8.4
9.2/9.2
15.9/14.6
21.8/20.0
13.3/12.2
15.6/14.3
5
5
97/97
86/86
96/96
90/90
A
Cooling power factor
%
Heating power factor
Note (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(b) Operating characteristic of indoor unit
FDT Series
(220 V/240 V)
Models
FDT Series
71
90
112
140
Power input (kW)
28
0.09/0.10
0.10/0.12
0.10/0.12
0.11/0.13
0.17/0.20
0.21/0.24
Running current (A)
0.40/0.44
0.45/0.49
0.47/0.50
0.50/0.55
0.75/0.81
0.93/1.02
Item
36
45
56
FDTW Series
(220 V/240 V)
Models
FDTW Series
28
Item
45
56
71
90
112
140
Power input (kW)
0.09/0.10
0.10/0.11
0.12/0.13
0.18/0.20
0.20/0.24
Running current (A)
0.43/0.44
0.48/0.50
0.57/0.59
0.86/0.89
0.90/0.98
FDTS Series
(220 V/240 V)
Models
Item
FDTS Series
45
71
Power input (kW)
0.07/0.08
0.10/0.11
0.12/0.15
Running current (A)
0.33/0.36
0.43/0.46
0.58/0.63
22
28
36
FDR, FDUM Series
(220 V/240 V)
Models
Item
FDR, FDUM Series
22
28, 36
71
90
112
140
Power input (kW)
0.09/0.11
0.11/0.13
45
0.14/0.16
56
0.15/0.17
0.16/0.19
0.24/0.28
0.28/0.32
Running current (A)
0.41/0.46
0.51/0.56
0.63/0.67
0.68/0.71
0.73/0.79
1.07/1.17
1.28/1.32
FDE Series
(220 V/240 V)
Models
Item
FDE Series
36
45
56
71
112
140
Power input (kW)
0.10/0.11
0.12/0.15
0.20/0.24
0.24/0.29
Running current (A)
0.43/0.46
0.58/0.63
0.90/0.98
1.10/1.20
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.
963
FDC-HKXR
FDK, FDFL, FDFU Series
(220 V/240 V)
Models
Item
FDK Series
22
28
36
FDFL, FDFU Series
45
56
71
28
45,56
71
Power input (kW)
0.05/0.06
0.06/0.07
0.08/0.09
0.09/0.11
0.09/0.10
0.09/0.10
0.09/0.10
Running current (A)
0.26/0.28
0.31/0.33
0.36/0.39
0.41/0.48
0.41/0.42
0.40/0.41
0.40/0.41
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.
(c) Calculation of total operation characteristics
Since the operation characteristics of series Multi-KXR depend on combination of indoor unit, calculate the total operation
characteristics of the system by using the formulas below according to specifications of each indoor unit or outdoor unit.
1) Total power input
Total power input (kW) = Power input of outdoor unit + ∑ (Power input of indoor unit)
2) Total running current
Total running current (A) = Running current of outdoor unit + [∑ (Running current) × 2/3]
3) Total power factor
—
Total power factor (%) = [Total power input (W) / √ 3 × Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions)
Operation Voltage ········Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit·······························Outdoor unit: FDCP2501HKXRE2 × 1 unit
Indoor unit: FDTJ71HKXE2 × 2 units
FDTJ45HKXE2 × 2 units
Operation characteristics of each unit
(Cooling/Heating)
Models
FDCP2501HKXRE2
FDTJ71HKXE2
FDTJ45HKXE2
Power input (kW)
12.4/9.2
0.10/0.10
0.10/0.10
Running current (A)
21.8/15.6
0.47/0.47
0.45/0.45
Item
1 Total power input (kW)
(Cooling) 12.4 + (0.10 × 4) = 12.8 (kW)
(Heating) 0.2 + (0.10 × 4) = 9.6 (kW)
2 Total running current (A)
.
(Cooling) 21.8 + (0.47 × 2 + 0.45 × 2) × 2 =. 23.0 (A)
3
.
(Heating) 15.6 + (0.47 × 2 + 0.45 × 2) × 2 =. 16.8 (A)
3
3 Total power factor (%)
964
(Cooling)
12.8 × 1000
—
√ 3 × 23.0 × 380
.
× 100 =. 85 %
(Heating)
9.6 × 1000
—
√ 3 × 16.8 × 380
.
× 100 =. 87%
FDC-HKXR
• Correction factor of compressor power input
Model FDCP2001HKXRE2
Model FDCP2501HKXRE2
1.0
Power consumption correction coefficietnt
Power consumption correction coefficietnt
1.0
0.8
0.6
0.4
0.2
Total capacity of indoor units
operating simulataneously
45
105
(Below, the coefficients
are the same.)
164
224
0.8
0.6
0.4
0.2
Total capacity of indoor units
operating simulataneously
(Below, the coefficients
are the same.)
45
90 105
(Below, the coefficients
are the same.)
164
224
280
(Below, the coefficients
are the same.)
965
FDC-HKXR
20.2.2 Range of usage & limitations
System
FDCP2001HKXRE2
FDCP2501HKXRE2
Item
Indoor intake air temperature
(Upper, lower limits)
Refer to the selection chart.
Outdoor air temperature
(Upper, lower limits)
Indoor units
that can be
used in
combination
1 to 8 units
Number of connected units
Total capacity
11000 to 29200w
Single direction piping lenght
13200 to 37100w
Indoor unit MAX 100m
Piping length after first division
MAX 30m
Difference in
height between
indoor and outdoor
units
When above outdoor unit
MAX 50m
When below outdoor unit
MAX 10m
MAX 15m
Difference in height between indoor units
Indoor unit atmosphere (behind ceiling)
temperrature and humidity
Compressor
stop/start
frequency
Dew point temperature 28
1 cycle time
6 min or more(from stop to stop or from start to start)
Stop time
Power source
voltage
or less, relative humidity 80% or less
3 min or more
Voltage fluctuation
_ 10% of rated voltage
Within +
Voltage drop during start
_ 15% of rated voltage
Within +
Interval unbalance
Within _+ 3% of rated voltage
Allowable length of refrigerant piping, Height difference between indoor and outdoor unit
Individual flow divide controller
Outdoor unit
(Max 70m )
Indoor unit
Max 30m
First branch
Max 15m
50m
(Outdoor unit is lower : 10m)
(Highest indoor unit)
Individual flow divaide
controller
Max 30m
(Lowest indoor unit)
Between the outdoor unit and first branch (main piping): Max 70m (actual length)
Between the first branch and each indoor unit : Max 30m (each indoor unit) (actual length)
Note (1) The indoor unit and individual flow divide controller positions should be within the range of the reach of the
connections of the wires that come with the individual flow divide contoroller
966
FDC-HKXR
20.2.3 Exterior dimensions
(1) Indoor unit
(a) Ceiling recessed type (FDT)
Models FDTJ28HKXE2, 36HKXE2, 45HKXE2, 56HKXE2, 71HKXE2, 90HKXE2
Unit : mm
Decorative Panel
Holes for
suspension bolts
(M10 to M8 ×4pcs.)
860~890 (Ceiling hole size)
Fresh air
opening for ducting
780 (Suspension bolts pitch )
950
630
C
400
B→
Liquid piping
28, 36, 45 type: φ6.35(1/4")
56, 71, 90 type: φ9.52(3/8")
Gas piping
28, 36, 45 type: φ12.7(1/2")
56, 71, 90 type: φ15.88(5/8")
267
Drain hose (Accessories)
(Local setting)
332
420
637
D
422
675 (Suspension bolts pitch)
Exhaust air
opening for ducting
310
Air outlet
Air inlet grille
VIEW A
840
Suspension bolts
Hole for wiring
Control box
260
30
↑
A
187
137
95
VIEW B
Holes for
tapping screws
6-φ4.0
Holes for
tapping screws
4-φ4.0
55
140
25
Space for installation and service
VIEW C
1000
42
80
140
112
100
113
140
160
33
60
Obstacle
or more
210
45 or more
Lug for
suspension bolts
700 or less
(Max. Drain up)
295~325
Drain
(Connectable with VP25)
1000
or more
VIEW D
967
FDC-HKXR
Models FDTJ112HKXE2, 140HKXE2
Unit : mm
Decorative Panel
Holes for
suspension bolts
(M10 to M8 ×4pcs.)
860~890 (Ceiling hole size)
Fresh air
opening for ducting
780 (Suspension bolts pitch )
950
630
C
400
B→
Liquid piping
φ9.52(3/8")
267
Drain hose (Accessories)
(Local setting)
332
420
637
D
422
675 (Suspension bolts pitch)
Exhaust air
opening for ducting
Air outlet
310
Air inlet grille
VIEW A
Gas piping
φ19.05(3/4")
840
Drain
(Connectable with VP25)
Lug for
suspension bolts
Control box
55
700 or less
(Max. Drain up)
VIEW B
Space for installation and service
140
25
VIEW C
1000
Obstacle
or more
42
VIEW D
140
112
100
113
140
160
33
60
80
968
320
A
Holes for
tapping screws
6-φ4.0
Holes for
tapping screws
4-φ4.0
187
Hole for wiring
30
→
45 or more
95
137
270
295~325
1000
or more
FDC-HKXR
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B
Unit : mm
Drain hose
(Accessories)
(Local setting)
278
64
47
Hole
Suspension
fitting
Fresh air opening for ducting
(knock out)
97
50
Holes of
tapping screws
5 - φ4
264
91
Center of
panel
640
70
Suspension bolts
(M10 × 4 pcs.)
(Ceiling hole size)
446
Control
box
(Suspension bolts pitch)
97
417
468
310
98
90
95
885 (Suspension bolts pitch)
40
120
1015 (Ceiling hole size)
VIEW A
460
178
200
130
295~
325
200
750 or less
280
Hole Hole
364
310
230
169
8
Hole Hole
74
20
124
Hole for wiring
20
Drain(VP20)
(Natural drainage)
Exhaust air opening for ducting
(knock out)
Holes for
tapping screws
8 – φ4
Decorative Panel
1055
Air outlet
Air inlet
100
or more
1000or more
360
680
160
Space for installation and service
160
↑
A
140
100
130
Liquid piping
28, 45 tipe :
φ6.35(1/4")
56 type :
φ9.52(3/8")
148
240
20
Gas piping
28, 45type:
φ12.7(1/2")
56 type:
φ15.88(5/8")
Drain(VP25)
(condensate
pump drain)
207
240
10
620
405
(Max. Drain up)
178
10
20
56
227
817
56
100
or more
1500
or more
1500
or more
Obstruction
45
965
45
969
FDC-HKXR
Models FDTWJ71HKXE2B, 90HKXE2B
Unit : mm
1054
382
240
240
200
200
295~
325
Liquid piping
φ9.52(3/8")
↑
240
Holes for
tapping screws
8 – φ4
128
Drain (VP25)
(condensate
pump drain)
Hole for wiring
20
Drain (VP20)
(Natural drainage)
Exhaust air opening for ducting
(knock out)
Decorative Panel
64
Gas piping
φ15.88(5/8")
230
8
750 or less
Hole
78
20
310
A
20
10
364
330
Hole
88
640
50
95
620
410
100
140
10
148
460
VIEW A
219
212
Hole
20
66
(Max. Drain up)
66
264
Suspension
fitting
Fresh air opening
for ducting
(knock out)
97
50
Holes of
taping screws
5 – φ4
277
Center of
panel
Suspension bolts
(M10 × 4 pcs.)
(Ceiling hole size)
70
446
Control
box
310
278
97
540
(Suspension bolts pitch)
590
90
95
1130 (Suspension bolts pitch)
40
Drain hose
(Accesories)
(Local setting)
120
1260 (Ceiling hole size)
Space for installation and service
Air outlet
Air inlet
160
100
or more
1000or more
1300
100
or more
160
360
680
Obstruction
45
970
1210
45
1500
or more
1500
or more
FDC-HKXR
Models FDTWJ112HKXE2B, 140HKXE2B
310
50
64
110
103
Hole
130
70
50
Suspension
fitting
Fresh air opening
for ducting
(knock out)
97
Center of
panel
640 (Ceiling hole size)
Control
box
Holes for
tapping
screws
5-ø4
Suspension bolts
(M10 × 4 pcs.)
97
775
264
(Local setting)
446
(Suspension bolts pitch)
825
90
95
1730 (Ceiling hole size)
1600 (Suspension bolts pitch)
40
278
Drain hose
(Accessories)
VIEW A
200
345
255
A→
Hole
20
78
Holes for
tapping screws
8-ø4
128
Exhaust air opening for ducting
(knock out)
20
10 20
Gas piping
ø15.88(5/8")
Drain(VP25)
(condensate
pump drain)
410
364
310
Liquid piping
ø9.52(3/8")
230
Drain(VP20)
(Natural
drainage)
8
140
Hole
620
292
240
200
100
240
295~
325
10
234
672
Max. drain up
240
750 or less
612
20
66
163
1524
66
Hole for wiring
1770
Air outlet
Air inlet
160
100
or more
1000 or more
680
360
160
Space for installation and service
100
or more
1500
or more
1500
or more
Obstruction
45
1680
45
Decorative Panel
971
FDC-HKXR
(c) 1-Way outlet ceiling recessed type (FDTS)
Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B, 45HKXE2B
70
35
50
25
383
25
168
Panel center
200
45
250
150
60
285
315
180
435
90
Drain hose (Accessories)
(Local setting)
VIEW A
Suspension bolts
(M10×4 pcs.)
295~325
235
940
115
194
←C
10
165
100
600 or less
Max. Drain up
70
710 (Ceiling hole size)
B→
600 (Suspension bolts pitch) 40
555
Holes for tapping screws
(φ4-6pcs.)
290
70
60
1230 (Ceiling hole size)
990 (Suspension bolts pitch)
Unit : mm
140
Fresh air
opening for ducting
(Knock out)
Fresh air
opening for ducting
(knock out)
100
50
A
↓
Fresh air
opening for ducting
(Knock out)
30
30
205
85
Air outlet
920
245
Fresh air
opening for ducting
(Knock out)
85
125
40
90
290
140
60
50
770
100
35
Air inlet grille
70
45
45
1200
45
70
140
1290
Holes for
tapping screws
(φ4.0 − 6 pcs.)
VIEW B
Decorative Panel
30
45
15
650
30
Space for installation and service
415
275
100 or
more
215
1000 or more
370
Liquid piping
φ6.35(1/4")
100 or
more
155
105
110
Obstacle
Gas piping
φ12.7(1/2")
Drain (VP25)
(Condensate pump drain)
Hole for wiring
(φ35)
VIEW C
972
100 or
more
FDC-HKXR
Model FDTSJ71HKXE2B
Unit : mm
1440 (Ceiling hole size)
1250 (Suspension bolts pitch)
675
70
200
60
Drain hose(Accessories)
(Local setting)
295~325
1200
200
165
170
30
10 194
100
600 or less Max. Drain up
Suspension bolts
(M10×4pcs.)
150
VIEW A
90
100
45
250
140
35
50
25
168
Panel center
←C
30
70
Fresh air
opening for ducting
(Knock out)
Air outlet
1180
210
35
60
100
Air inlet grille
140
50
40
90
85
110
770
70
290
45
70
140
Holes for
tapping screws
(φ4-6pcs.)
VIEW B
45
1410
45
1500
Decorative Panel
30 45
15 30
650
Space for installation and service
415
275
100 or
more
110
215
Gas piping
φ15.88(5/8")
1000 or more
370
Liquid piping
φ9.52(3/8")
155
105
710 (Ceiling hole size)
145
575
Fresh air
opening for ducting
(Knock out)
Holes for tapping screws
290
(φ4-6pcs.)
383
70 600 (Suspension bolts pitch) 40
285
315
25
↑
B
Fresh air
opening for ducting
(knock out)
70
Fresh air
opening for ducting
45
(knock out)
100
50
←
A
100 or
more
100 or
more
Obstacle
Drain (VP25)
(Condensate pump drain)
Hole for wiring
(φ35)
VIEW C
973
FDC-HKXR
(d)
Cassetteria type (FDR)
Model FDRJ22HKXE2
Silent Panel (Model: R-PNLS-26W-E)
Unit : mm
980 (Ceiling hole size)
786 (Suspension bolts pitch)
433
353
71
45
Panel center
70
465
405
↑
213
MIN95
40
MIN156
MIN81
650 or less
MIN320
480
A
Drain(VP25)
(Natural drainage)
460
Holes for
tapping screws
4-φ4.0
150
1040
45
φ170
φ170
950
Air inlet
45
75
φ149
90
Fresh air
opening for ducting
(Knock out)
Obstacle
974
50 or more
Air inlet
VIEW A
75
100 or
more
45
1000
or more
Space for installation and service
750
510
Exhaust air
opening for ducting
(Knock out)
VIEW B
100 or
more
Hole for
wiring
(φ35)
250
45
205
635
510
355~369
00
φ2
MIN225
80
MIN206
295~325
405
B→
VIEW C
Liquid piping
φ6.35(1/4")
Max. Drain up
Gas piping
φ12.7(1/2")
345
405
Drain
(Connectable with VP25)
Supply air duct
750
150
59
690(Ceiling hole size)
45
545(Suspension bolts pitch)
275
69
Control box
Suspension bolts
(M10×4pcs.)
Fresh air
opening for ducting
(Knock out)
284
C
↓
270
Drain hose (Accessories)
(Local setting)
137
75
57
FDC-HKXR
Model FDRJ22HKXE2
Canvas Panel (Model: R-PNLC -26W-E)
804 (Ceiling hole size)
786 (Suspension bolts pitch)
353
433
9
45
Fresh air opening
for ducting
(Knock out)
284
69
150
193
69
Drain
(Connectable
with VP25)
Liquid piping
φ6.35(1/4")
Gas piping
φ12.7(1/2")
Control box
Panel center
352
525 (Ceiling hole size)
90
↓
45
545 (Suspension bolt pitch) 70
C
Drain hose (Accessories)
(Load setting)
9
Unit : mm
405
59
VIEW C
71
Supply air duct
Max. Drain up
465
149
199
40
405
260
↓
Drain (VP20)
(Natural drainage)
Canvas duct
(Optional parts)
480
274
35
130
B
510
299
405
345
635
150~300
295~325
750
600 or less
Suspension bolts
(M10×4pcs.)
80
Hole for
wiring
(φ35)
↑
A
250
460
213
150
Holes for
tapping screws
864
φ170
φ170
Fresh air opening for ducting
(Knock out)
Air inlet
45
75
774
45
45
205
90
345
Exhaust air opening for ducting
(Knock out)
585
φ149
75
45
VIEW B
Air inlet
100
or more
1000 or more
Space for installation and service
100
or more
50
VIEW A
or more
Obstacle
975
FDC-HKXR
Models FDRJ28HKXE2, 45HKXE2, 56HKXE2
Silent Panel (Model: R-PNLS-26W-E)
Unit : mm
980 (Ceiling hole size)
786 (Suspension bols pitch)
137
Fresh air
opening for ducting
(Knock out)
(Local setting)
353
284
45
panel center
71
Supply air duct
150
690 (Ceiling hole size)
545 (Suspension bolt pitch)
45
59
405
75
275
270
Control box
70
69
C↓
VIEW C
Drain
(Connectable with VP25)
Gas piping
28, 45 type: φ12.7 (1/2")
56 type: φ15.88 (5/8")
Liquid piping
28, 45 type: φ6.35 (1/4")
56 type: φ9.52 (3/8")
635
Drain (VP20)
(Natural drainage)
205
213
1040
45
45
950
Air inlet
45
150
Hole for wiring
(φ35)
250
460
Holes for
tapping screws
φ149
40
MIN81
↑A
MIN95
0
φ20
405
MIN156
MIN320
MIN225
B→
465
MIN206
245
320
480
355~369
185
510
650 or less
295~325
750
Suspension bolts
(M10 × 4pcs.)
Max. Drain up
80
φ170
75
433
φ170
90
Fresh air opening
for ducting
(Knock out)
510
Exhaust air opening for ducting
(Knock out)
more
1000
100 or
or more
Obstacle
976
100 or
50 or
more
more
Air inlet
VIEW A
75
Space for installation and service
45
VIEW B
750
57
Drain hose (Accessories)
FDC-HKXR
Models FDRJ28HKXE2, 45HKXE2, 56HKXE2
Canvas Panel (Model: R-PNLC-26W-E)
Unit : mm
Drain hose (Accessories)
804 (Ceiling hole size)
9
786 (Suspension bolts pitch)
353
284
Fresh air opening for ducting
(Knock out)
45
C↓
Control box
150
193
69
Drain
(Connectable with VP25)
Panel center
Liquid piping
28, 45 type: φ6.35 (1/4")
56 type: φ9.52 (3/8")
Gas piping
28, 45 type: φ12.7 (1/2")
56 type: φ15.88 (5/8")
352
525 (Ceiling hole size)
90
(Local setting)
9
45
545 (Suspension bole pitch) 70
433
59
Supply air duct
405
VIEW C
71
149
40
405
260
35
B→
465
199
245
130
320
480
274
185
635
510
299
295~325
750
600 or less
Suspension bolts
(M10 × 4pcs.)
Max. Drain up
80
00
φ2
↑
A
205
Hole for
wiring
(φ35)
150~
300
Canvas duct
(Optional parts)
Drain (VP20)
(Natural drainage)
250
460
213
φ149
864
φ170
Fresh air
opening for ducting
(Knock out)
75
Air inlet
φ170
45
75
774
45
45
45
150
Holes for tapping screws
4-φ4.0
345
Exhaust air opening for ducting
(Knock out)
585
90
VIEW B
1000
100 or
more
or more
Space for installation and service
100 or
more
50 or
Air inlet
VIEW A
more
Obstacle
977
FDC-HKXR
Models FDRJ71HKXE2, 90HKXE2
Silent Panel (Model: R-PNLS-36W-E)
Unit : mm
1180 (Ceiling hole size)
986 (Suspension bolts pitch)
533
137
453
Drain hose (Accessories)
(Local setting)
Fresh air opening for ducting
(Knock out)
45
Panel center
71
465
Drain (VP20)
(Natural drainage)
↑A
MIN95
40
405
MIN156
MIN320
Hole
for wiring
(φ35)
250
460
213
205
1240
150
φ149
Holes for
tapping screws
(4-φ4.0)
1150
45
φ170
45
Air inlet
φ170
Fresh air opening
for ducting
(Knock out)
45
90
510
Exhaust air opening for ducting
(Knock out)
VIEW B
or more
1000 or
100
more
100 or
more
50 or
more
Obstacle
VIEW A
978
75
Air inlet
45
Space for installation and service
750
MIN225
0
480
MIN81
φ20
635
510
355~369
215
B→
80
MIN206
285
650 or less
285
165
Liquid piping
φ9.52(3/8")
295~325
950
VIEW C
Drain
(Connectable with VP25)
Gas piping
φ15.88(5/8")
Suspension bolts
(M10×4pcs.)
500
Max. Drain up
Supply air duct
150
45
545 (Suspension bolts pitch)
59
75
275
270
Control box
690 (Ceiling hole size)
69
C↓
70
284
75
57
FDC-HKXR
Models FDRJ71HKXE2, 90HKXE2
Canvas Panel (Model: R-PNLC-36W-E)
Unit : mm
Drain hose (Accessories)
(Local setting)
1004 (Ceilinghole hole size)
986 (Suspension bolts pitch)
453
69
Drain
(Connectable
with VP25)
Control box
Liquid piping
φ9.52(3/8")
59
71
Supply air duct
950
510
480
465
405
149
260
35
B→
40
215
199
285
635
80
274
285
295~325
130
165
VIEW C
299
Suspension bolts
(M10 × 4pcs.)
500
Gas piping
φ15.88(5/8")
Max. Drain up
352
Panel center
150
45
Fresh air opening for ducting
(Knock out)
284
C↑
193
45 545 (Suspension bolts pitch)
90
525 (Ceiling hole size)
70
533
9
600 or less
9
Drain (VP20)
(Natural drainage)
Canvas duct
(Optional Parts)
150~300
0
φ20
Hole
for wiring
(φ35)
↑A
250
460
45
974
Air inlet
45
φ170
90
VIEW B
Air inlet
75
Exhaust air opening for ducting
(Knock out)
45
Fresh air opening for ducting
(Knock out)
345
φ170
585
150
Holes of tapping screws
(4-φ4)
75
φ149
1064
213
45
205
VIEW A
1000
100
or more
or more
Space for installation and service
100
or more
50
or more
Obstacle
979
FDC-HKXR
Models FDRJ112HKXE2, 140HKXE2
Silent Panel (Model: R-PNLS-46W-E)
Unit : mm
1600 (Ceiling hole size)
1406 (Suspension bolts pitch)
663
270
58
45
Panerl center
Supply air duct
175
320
320
70
Liquid piping
φ19.05(3/4")
295~325
320
VIEW C
80
(Max. Drain up)
1370
495
Drain
(Connectable with VP25)
76
Gas piping
φ19.05(3/4")
Suspension bolts
(M10 ×4pcs.)
235
635
510
480
465
405
40
φ20
MIN 96
MIN156
MIN206
Drain (VP20)
(Natural drainage)
MIN81
↑A
406~420
B→
650 or less
MIN320
0
MIN276
Fresh air
opening for ducting
(Knock out)
150
Control box
690 (Ceiling hole size)
69
45
287
75
275
C
↑
545
(Suspension bolts pitch)
743
57
Drain hose (Accessories)
(Local setting)
137
Hole
for wiring
(I.D.φ35)
155
460
1660
45
75
Air inlet
45
1570
45
45
Holes of tapping screws
4-φ4
150
φ149
213
75
205
φ170
90
Exhaust air opening for dacting
(Knock out)
VIEW B
1000
or more
Space for installation and service
100
or more
100
or more
Obstacle
980
510
750
φ170
Fresh air opening
for ducting
(Knock out)
Air inlet
VIEW A
50
or more
FDC-HKXR
Models FDRJ112HKXE2, 140HKXE2
Canvas Panel (Model: R-PNLC-46W-E)
Unit : mm
1424 (Ceiling hole size)
1406 (Suspension bolts pitch)
743
663
150
Drain
(Connecteble with VP25)
495
Liquid piping
φ9.52(3/8")
59
1370
465
405
86
0
200
295~325
250
235
510
325
320
635
480
350
320
600 or less
320
130
175
80
Max. Drain up
71
Supply air duct
VIEW C
Gas piping
φ19.05(3/4")
310
352
Panel center
40
70
45
69
Control box
Suspension bolts
(M10 × 4pcs.)
Fresh air opening for ducting
(Knock out)
284
C↑
193
Drain hose (Accessories)
(Local setting)
9
45
90
545 (Suspension bolts pitch)
525 (Ceiling hole size)
9
φ20
Hole
for wiring
(φ35)
150~300
Canvas duct
(Optional parts)
↑A
213
150
Holes of tapping screws
(4-φ4)
φ170
φ170
Fresh air opening
for ducting
(Knock out)
460
1484
1394
45
45
Air inlet
45
205
φ149
155
Drain (VP20)
(Natural drainage)
75
B→
345
585
90
Exhaust air opening for ducting
(Knock out)
75
Air inlet
45
VIEW B
Space for installation and service
1000
100
or more
or more
VIEW A
100
or more
50
or more
Obstacle
981
FDC-HKXR
(e) Satellite ducted type (FDUM)
Models FDUMJ36HKXE2, 45HKXE2, 56HKXE2
Unit : mm
786 (Suspension bolts pitch)
750
18
80
B
205
Hole of
tapping screws
(4-φ4)
Drain hose (Accessories)
(Local setting)
Drain
(Connectable with VP25)
284
A→
213
φ149
Control box
φ170
Liquid piping
36, 45 type: φ6.35(1/4")
56 type: φ9.52(3/8")
118
472
(Suspension bolts pitch)
45
↑
18
59
Fresh air opening
for ducting
(Knock out)
Gas piping
36, 45 type: φ12.7(1/2")
56 type: φ15.88(5/8")
71
Supply air duct
φ170
90
Exhaust air opening for ducting
(Knock out)
295~325
750
185
Max.Drain up
VIEW A
320
245
Suspension bolts
(M10×4pcs.)
80
30
635
510
480
465
0
40
149
199
274
299
600 or less
35
130
405
φ20
460
Drain (VP20)
(Natural drainage)
660
45
50
200
200
Hole for wiring
45
200
50
170
620
Holes for tapping screws
(12-φ4)
VIEW B
982
Return air duct
1100
100
35
59
630
200
35
Space for installation and service
Inspection space
FDC-HKXR
Models FDUMJ71HKXE2, 90HKXE2
Unit : mm
986 (Suspension bolts pitch)
950
18
472
(Suspension bolts pitch) 45
↑
18
80
B
205
284
118
A→
59
71
213
Holes of
tapping screws
4-φ4
φ149
Control box
Drain hose (Accessories)
(Local setting)
Drain
(Connectable with VP25)
φ170
Liquid piping
φ9.52(3/8")
Fresh air opening
Gas piping
for ducting
φ15.88(5/8")
(Knock out)
φ170
90
Exhaust air opening for ducting
(Knock out)
Supply air duct
VIEW A
295~325
35
635
510
480
465
405
40
30
149
Suspension bolts
(M10×4pcs.)
130
80
199
215
299
274
285
Max.Drain up
285
600 or less
950
165
0
φ20
460
Drain (VP20)
(Natural drainage)
860
45
4×200=800
45
50
Space for installation and service
Inspection
space
Holes for tapping screws
Return air duct
100
1300
35
620
830
200
170
59
35
50
Hole for wiring
VIEW B
983
FDC-HKXR
Models FDUMJ112HKXE2, 140HKXE2
Unit : mm
1406 (Suspension bolts pitch)
1370
↑
18
205
80
B
Holes of
tapping screws
(4-φ4)
213
φ149
Control box
284
A→
Drain hose (Accessories)
(Local setting)
Drain
(Connectable with VP25)
Liquid piping
φ9.52(3/8")
58
76
Supply air duct
320
320
295~325
235
φ170
Fresh air opening
for ducting
(Knock out)
Exhaust air opening for ducting
(Knock out)
635
80
30
510
480
465
405
200
250
325
0
350
φ20
600 or less
86
130
40
Suspension
bolts
(M10×4pcs.)
90
VIEW A
Max.Drain up
320
φ170
Gas piping
φ19.05(3/4")
1370
175
150
472
118 (Suspension bolts pitch) 45
18
460
Drain (VP20)
(Natural drainage)
1280
45
6×200=1200
60
Space for installation and service
1250
Return air duct
VIEW B
984
620
1720
210
35
Holes for tapping screws
(18-φ4)
100
240
70
35
45
60
Holes for wiring
Inspection
space
FDC-HKXR
(f)
Ceiling suspension type (FDE)
Models FDEJ36HKXE2B, 45HKXE2B, 56HKXEB2
Unit : mm
984 (Suspension bolts pitch)
15
15
Holes for suspension bolts
(M8 to M10 × 4 pcs. Not included)
The brackets face out
When the unit is half
recesed a bove
the ceiling
195
275
135
46
94
191
150
7
50
184
50
The brackets face interior
When the unit is
suspended beneath
the ceiling
Liquid piping
Gas piping
605
45
900 (Suspension bolts pitch)
940
30
650
30
185
1000
Air outlet
Drain hole
connection (1)
225
248
10
290
Drain hole
connection
46
Note (1) The slope of drain piping inside the unit is
Liquid piping
able to take incline of 10 mm
36, 45 type: φ6.35 (1/4")
56 type: φ9.52 (3/8")
Drain piping
connection
Air inlet grille
Space for installation and service
30
55
35
Gas piping
36, 45 type: φ12.7(1/2")
56 type: φ15.88(5/8")
100
or more
300
30
or more
20
150
or more
5
or more
Obstacles
Model FDEJ71HKXE2B
Unit : mm
1244 (Suspension bolts pitch)
15
15
The brackets face out
When the unit is half
recesed a bove
the ceiling
Holes for suspension bolts
(M8 to M10 × 4 pcs. Not included)
Liquid piping
605
135
Gas piping
275
45
195
1160 (Suspension bolts pitch)
50
46
94
184
150
The brackets face interior
When the unit is
suspended beneath
the ceiling
191
7
50
650
30
1200
30
185
1260
Drain hole
connection (1)
225
Air outlet
Air inlet grille
248
290
35
55
30
Gas piping
φ15.88(5/8")
100
or more
300
20
30
Drain piping
connection
Space for installation and service
or more
Drain hole
connection
10
Liquid piping
φ9.52 (3/8")
46
Note (1) The slope of drain piping inside the unit is
able to take incline of 10 mm
150
or more
5
or more
Obstacles
985
FDC-HKXR
Model FDEJ112HKXE2B
Unit : mm
1244 (Suspension bolts pitch)
15
15
Holes for suspension bolts
(M8 to M10 × 4pcs. Not included)
The brackets face out
When the unit is half
recesed a bove
the ceiling
66
50
1200
30
Liguid piping
584
275
174
Gas piping
135
94
46
30
246
150
The brackets face interior
When the unit is
suspended beneath
the ceiling
239
7
50
1160 (Suspension bolt pitch)
650
1260
Drain hole connection (1)
185
225
Air outlet
266
290
Drain hole
connection
10
Liquid piping
φ9.52 (3/8")
46
Note (1) The slope of drain hose inside the unit is
able to take incline of 10 mm
Air inlet grille
Drain piping connection
(VP20)
Space for installation and service
35
55
Gas piping
φ19.05 (3/4")
30
100
or more
300
30
or more
20
150 or more
5
or more
Obstacles
Model FDEJ140HKXE2B
Unit : mm
1454 (Suspension bolts pitch)
15
15
Holes for suspension bolts
(M8 to M10 × 4pcs. Not included)
66
1410
1470
30
275
Liquid piping
135
Gas piping
94
246
150
The brackets face interior
When the unit is
suspended beneath
the ceiling
584
174
7
50
239
1370 (Suspension bolts pitch)
50
650
30
46
The brackets face out
When the unit is half
recesed a bove
the ceiling
Drain hole connection (1)
185
225
Air outlet
266
Air inlet grille
290
30
Gas piping
φ19.05 (3/4")
100
or more
300
55
150 or more
Obstacles
986
Drain hose connection
(VP20)
Space for installation and service
20
35
or more
Drain hole
connection
30
10
Liquid piping
φ9.52 (3/8")
46
Note (1) The slope of drain piping inside the unit is
able to take incline of 10 mm
5
or more
FDC-HKXR
(g) Wall mounted type (FDK)
Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2
Unit : mm
950
23
387
387
130
23
4
194
7.7
59
65
710
155
820
155 77.5
25 25
20 20 25 20 20
77.5
65
155
Space for installation and service
200
Mounting plate
φ8 × 48 pcs.
(Holes on
mounting plate)
150
200
or
more
or
more
Available space
for rear connection
45
Hole on wall for
rear connection 55
105
φ70
58
90
165
10 38 50
165
Detail of mounting plate
Outlet for piping
(On both side)
or more
65
8
10 64
375
280
←A
Outlet for
electric wiring
Piping cover
Gas piping φ 12.7 (1/2")
Liquid piping
608 φ 6.35 (1/4")
60 55
Drain hose
0.7 m
712
VIEW A (Rear side)
Model FDKJ56HKXE2
Unit : mm
1148
23
486
486
130
23
7.7
4
194
65
155
144
Space for installation and service
φ8 × 48 pcs.
(Holes on
mounting plate)
712
150
200
or
more
or
more
Available space
for rear connection
45
Piping cover
Hole on wall for
rear connection 55 Gas piping φ 15.88 (5/8")
105
φ70
Liquid piping
608 φ 9.52 (3/8")
200
Mounting plate
or more
155
Detail of mounting plate
Outlet for piping
(On both side)
65
10 38 50
144
1018
197.5
155
197.5
25 25
20 20 25 20 20
10 64
59
8
908
65
58
90
Outlet for
electric wiring
375
280
←A
260
55
Drain hose
0.7 m
VIEW A (Rear side)
987
FDC-HKXR
Model FDKJ71HKXE2
23
Unit : mm
1436
486
387
387
130
23
194
4
7.7
Outlet for piping
(On both side)
65
377.5
155
108
Space for installation and service
Mounting plate
200
10 38 50
377.5
Detail of mounting plate
150
200
or
more
or
more
45
φ8 × 48 pcs.
(Holes on
mounting
plate)
or more
155
108
1306
155
25 25
20 20 25 20 20
8
10 64
59
65
1196
65
58
90
Outlet for
electric wiring
375
280
←A
Piping cover
Hole on wall for 55 Gas piping φ 9.52 (3/8")
rear connection
105
Liquid piping
φ70
608 φ 15.88(5/8")
550
Drain hose
0.7 m
55
Available space for rear connection
712
VIEW A (Rear side)
(h) Floor standing exposed type (FDFL)
Models FDFLJ28HKXE2, 45HKXE2, 71HKXE2
Unit : mm
Note (1) Value in ( ) indicates 71 type.
Space for installation and service
205
180
23
600
177
Remote-controller
mounting part
225
150 or more
166
1000 or more
786
(1071)
150 or
more
205
10
126
Slotted hole for
wall mounting
4-12×24
Floor piping space
or
more
1196
(1481)
600
or more
Floor
Control box
80
220
184
234
315
630
250
Expansion valve box
Level adjusting screw
(Accessory)
197
223
750
(1035)
93
148
223
98
195
988
Gas piping (Accessory)
28,45 type:φ12.7(1/2")
71 type:φ15.88(5/8")
197
225
32
Floor fixing metal brakcet
(Accessory)
10×30 long hole
Drain piping
Flexible tube
PT20A female screw
Air filter
806
(1091)
195
Liquid piping
28,45 type:φ6.35(1/4")
71 type:φ9.52(3/8")
FDC-HKXR
(i) Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2
Note (1) Value in (
Unit : mm
) indicates 71 type.
Slotted hole for
wall mounting
4-12 x 24
Space for installation and service
110
600
1000
126
166
786
(1071)
167
Peri cover Peri cover
45
100
600
100
100
810(1095)
722(1007)
20
225
105 110
Expansion valve box
Control box
80
220
184
234
315
630
250
Drain piping Flexible tube
PT20A female screw
Air filter
30
197
Level adjusting
screw
(Accessory)
750(1035)
98
32
Floor fixing metal braket
(Accessory)
10 x 30 long hole
Gas piping (Accessory)
28,45type : ø12.7(1/2")
56,71type : ø15.88(5/8")
Liquid piping
28,45type : ø6.35(1/4")
56,71type : ø9.52(3/8")
806(1091)
989
FDC-HKXR
(2) Remote controller (Optional parts)
Wall
0.3mm2, 3cores (O.D.φ5.6)
Wire
(Recessed)
LCD display
Junction box
(Locally Purchased)
120
16
Remote controller mounting dimensions
120
60
46
47
17
7
120
89
83.5
For the passage
after wiring
♦ Usable JIS box, JIS C 8336
⋅ Switch box for 1 piece (without cover)
(use of the mark hole as illustrated on the left)
⋅ Switch box for 2 pieces
(use of the mark hole as illustrated on the left)
(without cover)
(use of the mark hole as illustrated on the left)
(when installing the cover)
Notes (1) Allowable length of remote controller
cable: 600 m
Allowable rang of wire thickness and length
Remote controller outline
990
Standard Within 0.3 mm2
0.5 mm2
0.75 mm2
1.25 mm2
2 mm2
× Within 100 m
× Within 200 m
× Within 300 m
× Within 400 m
× Within 600 m
FDC-HKXR
(3) Individual flow divide controller (Optional Part)
HPFD01R-E
117.5
Indoor refrigerant piping connection pipe
Liquid pipe φ9.52 (3/8") flare. with included different diameter adapter coupling
φ6.35 (1/4") pipe
Hanging bolt position
(M10 provided at site)
61
Indoor connection wire (length 200)
(with insert terminal)
Outdoor refrigerant piping connection pipe
Liquid pipe φ9.52 (3/8") flare. with included different diameter adapter coupling
φ6.35 (1/4") pipe
37.5
73.5
Indoor refrigerant piping connection pipe
Gas pipe φ15.88 (5/8") flare. included
φ12.7 (1/2") different diameter adapter
coupling with φ19.05 (3/4") cutoff pipe
Accessory discharge gas pipe (with strainer)
51.5
32
32
173
173
265
245
Outdoor refrigerant piping connection pipe
Discharge gas pipe φ12.7 (1/2") flare. included
different diameter adapter coupling with
φ15.88 (5/8") pipe
40 40
Outdoor refrigerant piping connection pipe
Intake gas pipe φ15.88 (5/8") flare. included
different diameter adapter coupling φ19.05
(3/4") with φ12.7 (1/2") cutoff pipe
37.5
53
77.5
117.5
235
65.5
310
155
(When connected to the included intake gas piping)
• Inspection door
150 or
more
Service space
Top
Front
Inspection door
150
Front
or more
( 450)
150
or more
Bottom
Notes (1) Do not operate the unit without the indoor unit connected
(5) Use the indoor unit connection capacity to select a different
to the individual flow divide controller.
(2) Be sure to install the included strainer in the outdoor
discharge gas connection pipe.
(3) Do not install the flow divide controller upside down.
Install so that the body is level.
diameter adapter coupling from the foliowing table. (Use the
flare nuts that are included with the flow divide controller.)
For indoor
gas piping
(4) Weight: 6 kg
1 unit
OD15.88
ID12.7
ID19.05
Different diameter adapter coupling
For indoor For outdoor For outdoor For outdoor
liquid piintake gas dischage gas liquid pipping
piping
piping
ing
1 unit
1 unit
1 unit
1 unit
OD9.52
ID6.35
OD15.88
ID12.7
ID19.05
OD12.7
ID15.88
OD9.52
ID6.35
991
Wire entry hole
(φ50)
15
640
35
36
24
250
850
pass-through hole
(φ100)
Back
50 Piping and wiring bottom
118
Drain waste water
hole
(6-φ20)
170
φ19.05 (3/4")
Refrigerant discharge gas
piping connection pipe
Anchor bolt hole
(4 locations for M10)
150
250
240
163
80
250
187
168
145
2001: with φ25.4 (1") pipe
2501: with φ28.58 (1 1/8") pipe
Refrigerant Intake gas
piping connection pipe
φ12.7 (1/2") flare
Refrigerant liquid
piping connection pipe
98
65
(
Installation
example
L4
L3
L2
L1
)
Suction
Suction
Service
space
Dimensions
L2
500
200
0
Open
I
Refrigerant piping exit hole
(φ88)
II
0
200
500
Open
L4
500
200
500
500
III
Unit: mm
Notes (1) Be sure to fasten down the unit with the anchor bolts.
(2) If in a location with strong winds, position the air discharge outlet
piping
perpendicular to the wind direction.
(3) Provide at least 1 m of space above the unit.
100
105
Power supply
entry hole
(φ50)
Dimensions after connecting included refrigerant
(Top view)
40
625
Signal wire connection terminal box
50
Drain waste water hose
hole
(φ45)
645
terminal
Models FDCP2001HKXRE2, 2501HKXRE2
52
100
30
nection
box
350
50
75 Power supply con-
Power supply
entry hole
(φ50)
110
Power supply entry hole
(φ35)
Refrigerant gas piping exit hole
(φ65)
Refrigerant piping
exit hole
(φ88)
205
100
513
110
Refrigerant
liquid piping
connection
pipe
108
1700
524
143
78
190
150
100
1350
(4) Outdoor unit
15
L3
992
L1
600
FDC-HKXR
FDC-HKXR
20.2.4 Exterior appearance
(1) Indoor unit
(a) Ceiling recessed type (FDT)
● Decorative panel
Pearl white
(b) 2-way outlet ceiling recessed type (FDTW)
Air outlet
Air inlet
● Decorative panel
(i) Standard type
Panel part No.
Type
Panel color
With Auto swing
Pearl white
TW-PSA-22W-E
TW-PSA-32W-E
Applicable model
FDTW28, 45, 56 type
TW-PSA-42W-E
FDTW71, 90 type
FDTW112, 140 type
(ii) Attachment of ceiling material type
Panel part No.
Type
Panel color
With Auto swing
Misty white
TW-PSB-28W-E
TW-PSB-38W-E
TW-PSB-48W-E
Applicable model
FDTW28, 45, 56 type
FDTW71, 90 type
FDTW112, 140 type
993
FDC-HKXR
(c) 1-way outlet ceiling recessed type (FDTS)
Panel
Ceramic white
Air inlet grille
Ceramic white
● Decorative panel
Panel part No.
TS-PSA-26W-E
TS-PSA-36W-E
Type
Panel color
With Auto swing
Misty white
Applicable model
FDTS22, 28, 36, 45 type
FDTS71 type
(d) Cassetteria type (FDR)
Silent panel type
Canvas-duct panel type
Ceramic white
Ceramic white
(e) Satellite ducted type (FDUM) .......................................... Zinc steel plate
(f)
Ceiling suspension type (FDE)
Gray
(Vertical fins)
Gray
(Frame)
994
Ceramic white
(Front panel)
Ceramic white
(Air inlet grille)
Ceramic white
(Side panel)
Ceramic white
(Front panel)
FDC-HKXR
(g) Wall mounted type (FDK)
3
2
No.
Parts name
1
Side plate
2
Front panel
3
Air inlet grill
4
Air outlet louver
5
Bottom plate
6
Right and Left
louvers
Color
1
1
4
6
5
Ceramic white
Light gray
(h) Floor standing exposed type (FDFL)
Dark gray
(Air outlet grill)
Ceramic white
(Body)
Black
(Bottom plate)
(i)
Floor standing hidden type (FDFU) ........................ Zinc steel plate
(2) Outdoor unit
Models FDCP224HKXRE2, 280HKXRE2
Polar white
995
FDE series have external installation
as the expansion valve box.
Indoor unit B
Intake Thermistor (Th1-A)
ø9.52
(3/8")
-
Note (1) The solenoid valve is open during magnetic inductance and closed when there is not magnetic inductance.
Open
-
Closed
Open
Closed
20VF
Open
-
20VU
-
Partial load
During
discharge
temperature and
dome bottom
temperature
control
Intake gas piping
Brazing
63H2
DPR1
(
)
20SL
D
(
63L
SV2
)
4-way valve
(For after heat exchange)
Discharge
piping
thermistor
(ThO-D)
(Suction)
Receiver
SV1
Capacity control solenoid valve
20 Full
20 Partial
VF load
VU load
SV3
63H1
D
S C
Flare connection
Dome bottom thermistor
(Tho-c)
Service valve
(With charge port)
Compressor
Check joint
(HP)
Service
valve
63H4
(with charge
port)
63H3
Flange
DPR2
20SS
E
(LP)
Fusible plug
DPR3
Check joint
(liquid)
SVS
Heat exchange
thermistor
(ThO-R)
Heating
Strainer
(1)
(4) Flow divide controller solenoid valve action chart
(3) Function of thermistor
ThO-A : For low outside air cooling/heating, frost removal control
Power
Power
CoolHeatsupply
supply
Blower
Detrost
ThO-R : For frost removal control
ing
ing
OFF
ON
ThO-D : For Discharge piping temperature control
SVH
Closed
Closed
Closed
Open
Closed
Closed
ThO-C : For dome bottom temperature control
ThI-R : For fan control during heating
SVC
Closed
Open
Open
Closed
Open
Open
For frost prevention during cooling
Note (1) Including for pauses, stops, and errors.
(1)
SVL
Outside temperature thermistor
(ThO-A)
(2) Preset point of protective devices
63H1 : 3.24 open, 2.65 closed MPa (33 open, 27 closed kgf/cm2) [for protective]
63H2 : 2.26 open, 2.84 closed MPa (23 open, 29 closed kgf/cm2) [for high-pressure control (Hz decrease)]
63H3 : 2.50 open, 2.11 closed MPa (25.5 open, 21.5 closed kgf/cm2) [for high-pressure decrease control]
63H4 : 1.67 open, 1.86 closed MPa (17 open, 19 closed kgf/cm2) [for high-pressure increase control]
63L : 1.96 open, 2.75 closed MPa (20 open, 28 closed kgf/cm2) [for low-pressure increase control]
DPR1,2 : 1.77 open MPa (18 open kgf/cm2) DPR3 : 2.35 open MPa (24 open kgf/cm2)
ø12.7
(1/2")
Liquid
piping
Brazing
Brazing
ø19.05
(3/4")
Discharge gas
piping
2001 : ø25.4
2501 : ø28.58
Service
valve
(with charge
port)
Cooling
Models FDCP2001HKXRE2, 2501HKXRE2
SV1
Full load
During compressor capacity control
SVL
SVG
SVL
SVG
To the units in the following
order. (A maximum or 8 units
can be connected.)
SVH
SVC
SVH
SVC
Flow divide controller
(1) Solenoid valve operation chart
Heat exchange
thermistor
(Th1-R)
Air heartexchanger
ø15.88
(5/8")
Electronic
Strainer expansion valve
Indoor unit A
Flare connection
Check
joint
(Release)
4-way valve
(Discharge)
(For before heat exchange)
Oil separator
Refrigerant flow
Accumulator
996
Sub-cooling coil
Outdoor unit
FDC-HKXR
20.2.5 Piping System
FDC-HKXR
20.2.6 Selection chart
(1) Correct the cooling and heating capacity in accordance with the conditions as follows.The net cooling and heating capacity can
be,obtained in the following way.
Indoor unit
Each indoor unit = System performance Indoor unit capacity
Indoor unit capacity when operating simultaneously.
Outdoor unit
Performance from connected capacity correction coefficient from indoor and
outdoor temperature conditions (correction coefficient from piping distance System performance = correction coefficient from difference between indoor and outdoor temperature) (correction coefficient from condensation when heating).
Note: Refer to page 997 and 998 for the correction coefficient.
(a) Coefficient of cooling and heating capacity in relation to temperatures
Heating
Cooling
1.1
Heating
1.0
0.9
0.8
0.7
Range in which
use is possible
0.6
Outdoor dry bulb
temperature (˚CDB)
Cooling
1.2
Indoor dry bulb
temperature (˚CDB)
Performance correction coefficient
1.3
20
22
24
26
43
40
35
30
25
20
26
24
0
–5
14
16
18
Indoor wet bulb temperature (˚CWB) JIS
20
22
27
25
20
15
10
18.5
-10
-5
0
5
10
15
JIS
Outdoor wet bulb temperature (˚CWB)
(b) Correction of cooling and heating capacity in relation to one way length of refrigerant piping.
Equivalent piping length [m] (1)
Cooling
Heating
5
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
30
0.94
0.995
35
0.925
0.995
40
0.915
0.99
45
0.9
0.99
50
0.89
0.985
Equivalent piping length [m]
Cooling
Heating
55
0.875
0.985
60
0.865
0.98
65
0.85
0.98
70
0.84
0.975
75
0.825
0.975
80
0.815
0.97
85
0.8
0.97
90
0.79
0.965
95
0.775
0.965
100
0.765
0.96
Equivalent piping length [m]
Cooling
Heating
105
0.745
0.96
110
0.74
0.955
115
0.725
0.955
120
0.715
0.95
125
0.7
0.95
Note (1) Equivalent piping length can be obtained by calculating as follows.
Equivalent piping length = Real gas piping length + Number of bends in gas piping × Equivalent piping length of bends.
Unit : m/one part
Equivalent length of each joint
Gas piping size
Joint (90˚elbow)
φ12.7
0.10
φ15.88
0.10
φ19.05
0.15
φ25.4
0.15
φ28.58
0.20
997
FDC-HKXR
(c) When the outdoor unit is located at a lower height than the indoor unit in cooling operation and when
the outdoor unit is located at a higher height than the indoor unit in heating operation, the following
values should be subtracvted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
5m
10 m
15 m
20 m
25 m
30 m
0.01
0.02
0.03
0.04
0.05
0.06
35 m
40 m
45 m
50 m
0.07
0.08
0.09
0.10
(d) Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
-11
-9
-7
-5
-3
-1
1
3
5
0.95
0.94
0.93
0.91
0.88
0.86
0.87
0.92
1.00
The correction factors will change drastically according to weather conditions. So necessary adjustment
should be made empirically according to the weather data of the particulsr area.
(2) Correction of outdoor unit capacity according to capacity of indoor unit to be operated simultaneously
FDCP2001HKXRE2
Total capacity of indoor units operating simultaneously
998
FDC-HKXR
FDCP2501HKXRE2
Total capacity of indoor units operating simultaneously
Capacity Correction Calculations (The procedure for both cooling and heating is the same.)
Example Conditions
• Unit (50 Hz)
Outdoor unit FDCP2501HKXRE2 1 unit
Indoor unit FDTJ90HKXE2 - 1 unit
FDTJ140HKXE2 - 1 unit
FDTWJ28HKXE2B - 1 unit
FDTSJ22HKXE2B - 1 unit
• Piping length (Shall be common among units) .......... 60 meters (suitable length)
• Difference in height between indoor and ........... 15 meters
outdoor units
(Outdoor unit is lower)
• Air conditions .......... Outdoor air temperature 33˚CDB
Indoor temperature 26˚CDB 19 ˚CWB
Corrction when
cooling?
Outdoor unit performance correction
1 Total connection capacity from indoor unit ... 901 unit + 1401 unit + 281 unitt + 221 unit = 280
. . 28kW (From table above)
=
2 Performance correction from indoor and outdoor temperatures
. 28.5kW
28 1.02 =
.
3 Performance correction from piping length and difference in height between indoor and outdoor units
. . 23.8kW (Actual performance)
28.5 (0.865 - 0.03) =
Performance correction of indoor unit
Performance correction of indoor unit = System performance Indoor unit capacity
Total capacity of indoor units
operating simultaneously
[Example] FDTJ90HKXE2
90 .
23.8 =. 7.65kW
280
Performance of indoor unit
FDTJ90HKXE2 ................... 7.65kW (Actual performance)
FDTJ140HKXE2 ................ 11.9kW (Actual performance)
FDTWJ28HKXE2B .......... 2.38kW (Actual performance)
FDTSJ22HKXE2B .......... 1.87kW (Actual performance)
999
FDC-HKXR
(3) Sensible heat capacity
(a) FDT Series
Model FDTJ28HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
12
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
2.89
2.83
2.76
2.68
2.60
2.53
2.46
SHC
2.58
2.55
2.52
2.49
2.46
2.43
2.40
18.0°CWB
TC
2.98
2.91
2.85
2.77
2.70
2.63
2.56
SHC
2.60
2.57
2.55
2.52
2.49
2.46
2.43
19.0°CWB
TC
3.05
2.99
2.92
2.86
2.80
2.72
2.64
SHC
2.61
2.59
2.56
2.54
2.52
2.49
2.46
20.0°CWB
TC
3.13
3.07
3.01
2.95
2.88
2.81
2.74
SHC
2.63
2.61
2.58
2.56
2.54
2.51
2.49
21.0°CWB
TC
3.21
3.15
3.09
3.02
2.95
2.89
2.83
SHC
2.64
2.62
2.60
2.58
2.55
2.53
2.51
22.0°CWB
TC
3.28
3.22
3.16
3.10
3.04
2.98
2.91
SHC
2.6
2.6
2.6
2.5
2.5
2.5
2.5
Model FDTJ36HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
12
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
3.72
3.64
3.55
3.45
3.35
3.25
3.16
SHC
3.19
3.16
3.12
3.08
3.04
3.00
2.96
18.0°CWB
TC
3.83
3.75
3.66
3.57
3.47
3.38
3.29
SHC
3.22
3.19
3.15
3.11
3.08
3.04
3.00
19.0°CWB
TC
3.93
3.84
3.76
3.68
3.60
3.50
3.40
SHC
3.24
3.20
3.17
3.14
3.11
3.07
3.04
20.0°CWB
TC
4.02
3.95
3.87
3.79
3.71
3.61
3.52
SHC
3.25
3.22
3.20
3.17
3.14
3.10
3.07
21.0°CWB
TC
4.12
4.05
3.97
3.88
3.80
3.72
3.64
SHC
3.27
3.24
3.21
3.18
3.15
3.13
3.10
22.0°CWB
TC
4.21
4.14
4.06
3.99
3.91
3.83
3.75
SHC
3.2
3.2
3.2
3.2
3.1
3.1
3.1
Model FDTJ45HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
15
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
4.65
4.55
4.44
4.31
4.19
4.07
3.95
SHC
3.99
3.95
3.90
3.85
3.80
3.75
3.71
18.0°CWB
TC
4.78
4.68
4.58
4.46
4.34
4.23
4.11
SHC
4.02
3.98
3.94
3.89
3.85
3.80
3.76
19.0°CWB
TC
4.91
4.80
4.70
4.60
4.50
4.37
4.25
SHC
4.05
4.01
3.97
3.93
3.89
3.84
3.80
20.0°CWB
TC
5.03
4.93
4.83
4.73
4.64
4.52
4.40
SHC
4.07
4.03
3.99
3.96
3.92
3.88
3.84
21.0°CWB
TC
5.15
5.06
4.96
4.86
4.75
4.65
4.55
SHC
4.09
4.05
4.02
3.98
3.94
3.91
3.87
22.0°CWB
TC
5.27
5.18
5.08
4.98
4.88
4.78
4.68
SHC
4.1
4.0
4.0
4.0
3.9
3.9
3.9
Model FDTJ56HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
15
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
5.78
5.66
5.52
5.36
5.21
5.06
4.92
SHC
4.48
4.43
4.36
4.30
4.23
4.17
4.10
18.0°CWB
TC
5.95
5.83
5.70
5.55
5.40
5.26
5.11
SHC
4.51
4.46
4.40
4.34
4.28
4.22
4.16
Note (1) Symbols are as follows :
1000
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
19.0°CWB
TC
6.11
5.98
5.85
5.72
5.60
5.44
5.29
SHC
4.53
4.47
4.42
4.37
4.32
4.26
4.19
20.0°CWB
TC
6.26
6.14
6.01
5.89
5.77
5.62
5.48
SHC
4.54
4.49
4.44
4.40
4.35
4.29
4.24
21.0°CWB
TC
6.41
6.30
6.18
6.04
5.91
5.78
5.66
SHC
4.55
4.51
4.46
4.41
4.36
4.32
4.27
22.0°CWB
TC
6.55
6.44
6.32
6.20
6.08
5.95
5.83
SHC
4.5
4.5
4.4
4.4
4.3
4.3
4.2
FDC-HKXR
Model FDTJ71KHXE2
Air flow
3
(m /min)
16
Indoor air temperature
Outdoor
air temp.
17.0°CWB
(°CDB)
TC
7.33
7.18
7.00
6.80
6.60
6.42
6.23
27
29
31
33
35
37
39
SHC
5.31
5.24
5.15
5.06
4.97
4.89
4.81
18.0°CWB
TC
7.55
7.39
7.22
7.04
6.85
6.67
6.48
SHC
5.34
5.27
5.19
5.11
5.03
4.95
4.87
19.0°CWB
TC
7.75
7.58
7.41
7.26
7.10
6.90
6.70
SHC
5.35
5.28
5.21
5.14
5.07
4.99
4.91
20.0°CWB
TC
7.94
7.78
7.63
7.47
7.31
7.13
6.94
SHC
5.36
5.29
5.23
5.16
5.10
5.02
4.95
21.0°CWB
TC
8.13
7.99
7.83
7.66
7.49
7.33
7.16
SHC
5.36
5.30
5.24
5.17
5.11
5.04
4.98
22.0°CWB
TC
8.31
8.17
8.02
7.86
7.70
7.55
7.39
SHC
5.3
5.3
5.2
5.1
5.1
5.0
5.0
Model FDTJ90HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
21
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
9.30
9.10
8.87
8.62
8.37
8.14
7.90
SHC
6.82
6.72
6.62
6.51
6.39
6.29
6.19
18.0°CWB
TC
9.57
9.37
9.15
8.92
8.69
8.45
8.22
SHC
6.85
6.76
6.67
6.56
6.46
6.36
6.26
19.0°CWB
TC
9.82
9.60
9.40
9.20
9.00
8.75
8.50
SHC
6.87
6.78
6.69
6.61
6.52
6.42
6.31
20.0°CWB
TC
10.06
9.86
9.67
9.47
9.27
9.04
8.80
SHC
6.88
6.80
6.72
6.64
6.56
6.46
6.37
21.0°CWB
TC
10.31
10.13
9.93
9.71
9.50
9.30
9.10
SHC
6.89
6.82
6.74
6.65
6.57
6.49
6.42
22.0°CWB
TC
10.53
10.35
10.16
9.96
9.77
9.57
9.37
SHC
6.8
6.8
6.7
6.6
6.5
6.5
6.4
Model FDTJ112HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
28
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
11.57
11.32
11.04
10.73
10.42
10.12
9.83
SHC
8.71
8.60
8.47
8.33
8.20
8.07
7.94
18.0°CWB
TC
11.91
11.66
11.39
11.10
10.81
10.52
10.23
SHC
8.76
8.65
8.54
8.41
8.29
8.16
8.04
19.0°CWB
TC
12.22
11.95
11.69
11.45
11.20
10.89
10.57
SHC
8.79
8.68
8.57
8.47
8.37
8.24
8.11
20.0°CWB
TC
12.52
12.28
12.03
11.78
11.54
11.24
10.95
SHC
8.81
8.71
8.61
8.51
8.42
8.30
8.19
21.0°CWB
TC
12.82
12.60
12.35
12.08
11.82
11.57
11.32
SHC
8.82
8.74
8.64
8.54
8.44
8.34
8.25
22.0°CWB
TC
13.10
12.88
12.64
12.40
12.15
11.91
11.66
SHC
8.8
8.7
8.6
8.5
8.4
8.3
8.2
Model FDTJ140HKXE2
Air flow
3
(m /min)
30
Indoor air temperature
Outdoor
air temp.
(°CDB)
17.0°CWB
TC
14.46
14.15
13.80
13.41
13.02
12.66
12.29
27
29
31
33
35
37
39
SHC
10.29
10.15
9.98
9.80
9.62
9.45
9.28
18.0°CWB
TC
14.88
14.57
14.24
13.87
13.51
13.15
12.78
SHC
10.34
10.20
10.04
9.88
9.72
9.55
9.40
19.0°CWB
TC
15.27
14.94
14.62
14.31
14.00
13.61
13.22
SHC
10.36
10.21
10.07
9.94
9.81
9.64
9.47
20.0°CWB
TC
15.65
15.34
15.04
14.73
14.42
14.06
13.69
SHC
10.37
10.24
10.11
9.98
9.85
9.70
9.55
21.0°CWB
TC
16.03
15.75
15.44
15.11
14.77
14.46
14.15
SHC
10.37
10.26
10.13
10.00
9.86
9.74
9.62
22.0°CWB
TC
16.38
16.10
15.81
15.50
15.19
14.88
14.57
SHC
10.3
10.2
10.1
10.0
9.8
9.7
9.6
Note (1) Symbols are as follows :
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
1001
FDC-HKXR
(b) FDTS Series
Model FDTSJ22HKXE2B
Air flow
3
(m /min)
11
Indoor air temperature
Outdoor
air temp.
(°CDB)
17.0°CWB
TC
2.27
2.22
2.17
2.11
2.05
1.99
1.93
27
29
31
33
35
37
39
SHC
2.04
2.02
2.00
1.98
1.95
1.93
1.91
18.0°CWB
TC
2.34
2.29
2.24
2.18
2.12
2.07
2.01
SHC
2.06
2.04
2.02
2.00
1.98
1.95
1.93
19.0°CWB
TC
2.40
2.35
2.30
2.25
2.20
2.14
2.08
SHC
2.08
2.06
2.04
2.02
2.00
1.98
1.95
20.0°CWB
TC
2.46
2.41
2.36
2.31
2.27
2.21
2.15
SHC
2.09
2.07
2.05
2.03
2.02
2.00
1.98
21.0°CWB
TC
2.52
2.48
2.43
2.37
2.32
2.27
2.22
SHC
2.10
2.08
2.07
2.05
2.03
2.01
2.00
22.0°CWB
TC
2.57
2.53
2.48
2.44
2.39
2.34
2.29
SHC
2.11
2.09
2.08
2.06
2.04
2.03
2.01
Model FDTSJ28HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
12
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
2.90
2.83
2.77
2.69
2.60
2.54
2.45
SHC
2.58
2.55
2.52
2.49
2.46
2.43
2.40
18.0°CWB
TC
2.98
2.92
2.85
2.78
2.72
2.63
2.55
SHC
2.60
2.57
2.55
2.52
2.49
2.46
2.43
19.0°CWB
TC
3.06
3.00
2.93
2.87
2.80
2.73
2.65
SHC
2.62
2.59
2.57
2.54
2.52
2.49
2.46
20.0°CWB
TC
3.12
3.07
3.02
2.95
2.88
2.82
2.75
SHC
2.63
2.61
2.59
2.56
2.54
2.52
2.49
21.0°CWB
TC
3.21
3.14
3.09
3.04
2.97
2.90
2.83
SHC
2.64
2.62
2.60
2.58
2.56
2.54
2.51
22.0°CWB
TC
3.29
3.23
3.16
3.10
3.05
2.98
2.92
SHC
2.66
2.64
2.61
2.59
2.58
2.55
2.53
Model FDTSJ36HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
12
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
3.73
3.64
3.56
3.46
3.35
3.26
3.15
SHC
3.20
3.16
3.13
3.09
3.04
3.01
2.96
18.0°CWB
TC
3.84
3.75
3.66
3.58
3.49
3.38
3.28
SHC
3.22
3.19
3.15
3.12
3.08
3.04
3.00
19.0°CWB
TC
3.94
3.86
3.77
3.69
3.60
3.51
3.41
SHC
3.24
3.21
3.18
3.15
3.11
3.08
3.04
20.0°CWB
TC
4.02
3.95
3.88
3.79
3.71
3.62
3.54
SHC
3.25
3.23
3.20
3.17
3.14
3.11
3.07
21.0°CWB
TC
4.13
4.04
3.97
3.90
3.82
3.73
3.64
SHC
3.27
3.24
3.21
3.19
3.16
3.13
3.10
22.0°CWB
TC
4.23
4.15
4.06
3.98
3.92
3.84
3.75
SHC
3.28
3.26
3.23
3.20
3.18
3.15
3.12
Model FDTSJ45HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
14
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
4.66
4.55
4.45
4.33
4.19
4.08
3.94
SHC
3.86
3.82
3.77
3.72
3.66
3.62
3.56
18.0°CWB
TC
4.80
4.69
4.58
4.47
4.37
4.22
4.10
SHC
3.89
3.85
3.80
3.76
3.71
3.66
3.61
Note (1) Symbols are as follows :
1002
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
19.0°CWB
TC
4.92
4.82
4.72
4.61
4.50
4.39
4.26
SHC
3.91
3.87
3.83
3.79
3.75
3.70
3.65
20.0°CWB
TC
5.02
4.94
4.85
4.74
4.64
4.53
4.42
SHC
3.92
3.89
3.85
3.81
3.77
3.73
3.69
21.0°CWB
TC
5.16
5.05
4.96
4.88
4.77
4.66
4.55
SHC
3.94
3.90
3.87
3.84
3.80
3.76
3.72
22.0°CWB
TC
5.28
5.18
5.08
4.98
4.91
4.80
4.69
SHC
3.95
3.92
3.88
3.85
3.82
3.78
3.75
FDC-HKXR
Model FDTSJ71HKXE2B
Air flow
3
(m /min)
18
Indoor air temperature
Outdoor
air temp.
(°CDB)
17.0°CWB
TC
7.36
7.19
7.01
6.83
6.60
6.43
6.22
27
29
31
33
35
37
39
SHC
5.56
5.49
5.41
5.33
5.23
5.15
5.06
18.0°CWB
TC
7.57
7.40
7.23
7.06
6.89
6.66
6.48
SHC
5.59
5.52
5.45
5.37
5.30
5.21
5.13
19.0°CWB
TC
7.77
7.61
7.44
7.27
7.10
6.93
6.72
SHC
5.61
5.55
5.48
5.41
5.34
5.27
5.18
20.0°CWB
TC
7.92
7.80
7.65
7.48
7.31
7.14
6.97
SHC
5.61
5.56
5.50
5.44
5.37
5.30
5.24
21.0°CWB
TC
8.14
7.97
7.82
7.70
7.53
7.36
7.19
SHC
5.63
5.57
5.51
5.46
5.40
5.33
5.27
22.0°CWB
TC
8.34
8.18
8.01
7.85
7.74
7.57
7.40
SHC
5.64
5.58
5.52
5.46
5.42
5.36
5.30
(c) FDR Series
Model FDRJ22HKXE2
Air flow
3
(m /min)
10
Indoor air temperature
Outdoor
air temp.
(°CDB)
17.0°CWB
TC
2.28
2.23
2.17
2.12
2.05
1.99
1.93
27
29
31
33
35
37
39
SHC
2.05
2.02
2.00
1.98
1.95
1.93
1.90
18.0°CWB
TC
2.35
2.29
2.24
2.19
2.13
2.06
2.01
SHC
2.06
2.04
2.02
2.00
1.98
1.95
1.93
19.0°CWB
TC
2.41
2.36
2.31
2.25
2.20
2.15
2.08
SHC
2.08
2.06
2.04
2.02
2.00
1.98
1.96
20.0°CWB
TC
2.46
2.42
2.37
2.32
2.27
2.21
2.16
SHC
2.09
2.07
2.06
2.04
2.02
2.00
1.98
21.0°CWB
TC
2.52
2.47
2.42
2.38
2.33
2.28
2.23
SHC
2.10
2.08
2.06
2.05
2.03
2.01
2.00
22.0°CWB
TC
2.58
2.53
2.48
2.43
2.40
2.35
2.29
SHC
2.11
2.09
2.08
2.06
2.05
2.03
2.01
Model FDRJ28HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
12
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
2.90
2.83
2.77
2.69
2.60
2.54
2.45
SHC
2.58
2.55
2.52
2.49
2.46
2.43
2.40
18.0°CWB
TC
2.98
2.92
2.85
2.78
2.72
2.63
2.55
SHC
2.60
2.57
2.55
2.52
2.49
2.46
2.43
19.0°CWB
TC
3.06
3.00
2.93
2.87
2.80
2.73
2.65
SHC
2.62
2.59
2.57
2.54
2.52
2.49
2.46
20.0°CWB
TC
3.12
3.07
3.02
2.95
2.88
2.82
2.75
SHC
2.63
2.61
2.59
2.56
2.54
2.52
2.49
21.0°CWB
TC
3.21
3.14
3.09
3.04
2.97
2.90
2.83
SHC
2.64
2.62
2.60
2.58
2.56
2.54
2.51
22.0°CWB
TC
3.29
3.23
3.16
3.10
3.05
2.98
2.92
SHC
2.66
2.64
2.61
2.59
2.58
2.55
2.53
Model FDRJ45HKXE2
Air flow
3
(m /min)
14
Indoor air temperature
Outdoor
air temp.
(°CDB)
17.0°CWB
TC
4.66
4.55
4.45
4.33
4.19
4.08
3.94
27
29
31
33
35
37
39
SHC
3.86
3.82
3.77
3.72
3.66
3.62
3.56
18.0°CWB
TC
4.80
4.69
4.58
4.47
4.37
4.22
4.10
SHC
3.89
3.85
3.80
3.76
3.71
3.66
3.61
19.0°CWB
TC
4.92
4.82
4.72
4.61
4.50
4.39
4.26
SHC
3.91
3.87
3.83
3.79
3.75
3.70
3.65
20.0°CWB
TC
5.02
4.94
4.85
4.74
4.64
4.53
4.42
SHC
3.92
3.89
3.85
3.81
3.77
3.73
3.69
21.0°CWB
TC
5.16
5.05
4.96
4.88
4.77
4.66
4.55
SHC
3.94
3.90
3.87
3.84
3.80
3.76
3.72
22.0°CWB
TC
5.28
5.18
5.08
4.98
4.91
4.80
4.69
SHC
3.95
3.92
3.88
3.85
3.82
3.78
3.75
Note (1) Symbols are as follows :
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
1003
FDC-HKXR
Model FDRJ56HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
14
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
5.80
5.67
5.53
5.39
5.21
5.07
4.91
SHC
4.36
4.30
4.24
4.18
4.10
4.04
3.97
18.0°CWB
TC
5.97
5.84
5.70
5.57
5.43
5.25
5.11
SHC
4.39
4.33
4.27
4.21
4.16
4.08
4.02
19.0°CWB
TC
6.13
6.00
5.87
5.73
5.60
5.47
5.30
SHC
4.40
4.35
4.29
4.24
4.18
4.13
4.06
20.0°CWB
TC
6.25
6.15
6.04
5.90
5.77
5.63
5.50
SHC
4.40
4.36
4.32
4.26
4.21
4.16
4.10
21.0°CWB
TC
6.42
6.28
6.17
6.07
5.94
5.80
5.67
SHC
4.41
4.36
4.32
4.28
4.23
4.18
4.13
22.0°CWB
TC
6.57
6.45
6.32
6.19
6.10
5.97
5.84
SHC
4.42
4.37
4.32
4.28
4.25
4.20
4.15
Model FDRJ71HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
18
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
7.36
7.19
7.01
6.83
6.60
6.43
6.22
SHC
5.56
5.49
5.41
5.33
5.23
5.15
5.06
18.0°CWB
TC
7.57
7.40
7.23
7.06
6.89
6.66
6.48
SHC
5.59
5.52
5.45
5.37
5.30
5.21
5.13
19.0°CWB
TC
7.77
7.61
7.44
7.27
7.10
6.93
6.72
SHC
5.61
5.55
5.48
5.41
5.34
5.27
5.18
20.0°CWB
TC
7.92
7.80
7.65
7.48
7.31
7.14
6.97
SHC
5.61
5.56
5.50
5.44
5.37
5.30
5.24
21.0°CWB
TC
8.14
7.97
7.82
7.70
7.53
7.36
7.19
SHC
5.63
5.57
5.51
5.46
5.40
5.33
5.27
22.0°CWB
TC
8.34
8.18
8.01
7.85
7.74
7.57
7.40
SHC
5.64
5.58
5.52
5.46
5.42
5.36
5.30
Model FDRJ90HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
20
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
9.32
9.11
8.89
8.66
8.37
8.15
7.88
SHC
6.71
6.61
6.51
6.40
6.27
6.17
6.05
18.0°CWB
TC
9.59
9.38
9.16
8.95
8.73
8.44
8.21
SHC
6.74
6.64
6.55
6.45
6.36
6.23
6.13
19.0°CWB
TC
9.85
9.65
9.43
9.22
9.00
8.78
8.51
SHC
6.76
6.67
6.58
6.49
6.39
6.30
6.19
20.0°CWB
TC
10.04
9.88
9.70
9.49
9.27
9.05
8.84
SHC
6.75
6.68
6.60
6.52
6.43
6.34
6.25
21.0°CWB
TC
10.31
10.10
9.92
9.76
9.54
9.32
9.11
SHC
6.76
6.67
6.60
6.54
6.45
6.37
6.28
22.0°CWB
TC
10.57
10.37
10.15
9.95
9.81
9.59
9.38
SHC
6.76
6.69
6.60
6.53
6.47
6.39
6.31
Model FDRJ112HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
28
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
11.60
11.33
11.07
10.77
10.42
10.15
9.81
SHC
8.72
8.60
8.48
8.35
8.20
8.08
7.93
18.0°CWB
TC
11.94
11.67
11.40
11.13
10.86
10.51
10.21
SHC
8.77
8.66
8.54
8.42
8.31
8.16
8.04
Note (1) Symbols are as follows :
1004
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
19.0°CWB
TC
12.25
12.01
11.74
11.47
11.20
10.93
10.60
SHC
8.80
8.70
8.59
8.48
8.37
8.26
8.12
20.0°CWB
TC
12.50
12.30
12.07
11.80
11.54
11.27
11.00
SHC
8.80
8.72
8.63
8.52
8.42
8.31
8.20
21.0°CWB
TC
12.84
12.57
12.34
12.14
11.87
11.60
11.33
SHC
8.83
8.72
8.64
8.56
8.46
8.36
8.26
22.0°CWB
TC
13.15
12.90
12.63
12.39
12.21
11.94
11.67
SHC
8.84
8.75
8.65
8.56
8.49
8.39
8.30
FDC-HKXR
Model FDRJ140HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
34
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
14.50
14.17
13.83
13.47
13.02
12.68
12.26
SHC
10.78
10.63
10.48
10.31
10.12
9.97
9.78
18.0°CWB
TC
14.92
14.59
14.25
13.92
13.58
13.13
12.77
SHC
10.84
10.69
10.55
10.40
10.26
10.07
9.91
19.0°CWB
TC
15.32
15.01
14.67
14.34
14.00
13.66
13.24
SHC
10.88
10.75
10.60
10.46
10.32
10.19
10.01
20.0°CWB
TC
15.62
15.37
15.09
14.76
14.42
14.08
13.75
SHC
10.87
10.77
10.65
10.52
10.38
10.25
10.12
21.0°CWB
TC
16.04
15.71
15.43
15.18
14.84
14.50
14.17
SHC
10.90
10.77
10.66
10.56
10.43
10.30
10.18
22.0°CWB
TC
16.44
16.13
15.79
15.48
15.26
14.92
14.59
SHC
10.91
10.80
10.67
10.56
10.47
10.35
10.23
(d) FDUM Series
Model FDUMJ36HKXE2
Air flow
3
(m /min)
12
Indoor air temperature
Outdoor
air temp.
17.0°CWB
(°CDB)
TC
3.73
3.64
3.56
3.46
3.35
3.26
3.15
27
29
31
33
35
37
39
SHC
3.20
3.16
3.13
3.09
3.04
3.01
2.96
18.0°CWB
TC
3.84
3.75
3.66
3.58
3.49
3.38
3.28
SHC
3.22
3.19
3.15
3.12
3.08
3.04
3.00
19.0°CWB
TC
3.94
3.86
3.77
3.69
3.60
3.51
3.41
SHC
3.24
3.21
3.18
3.15
3.11
3.08
3.04
20.0°CWB
TC
4.02
3.95
3.88
3.79
3.71
3.62
3.54
SHC
3.25
3.23
3.20
3.17
3.14
3.11
3.07
21.0°CWB
TC
4.13
4.04
3.97
3.90
3.82
3.73
3.64
SHC
3.27
3.24
3.21
3.19
3.16
3.13
3.10
22.0°CWB
TC
4.23
4.15
4.06
3.98
3.92
3.84
3.75
SHC
3.28
3.26
3.23
3.20
3.18
3.15
3.12
Model FDUMJ45HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
14
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
4.66
4.55
4.45
4.33
4.19
4.08
3.94
SHC
3.86
3.82
3.77
3.72
3.66
3.62
3.56
18.0°CWB
TC
4.80
4.69
4.58
4.47
4.37
4.22
4.10
SHC
3.89
3.85
3.80
3.76
3.71
3.66
3.61
19.0°CWB
TC
4.92
4.82
4.72
4.61
4.50
4.39
4.26
SHC
3.91
3.87
3.83
3.79
3.75
3.70
3.65
20.0°CWB
TC
5.02
4.94
4.85
4.74
4.64
4.53
4.42
SHC
3.92
3.89
3.85
3.81
3.77
3.73
3.69
21.0°CWB
TC
5.16
5.05
4.96
4.88
4.77
4.66
4.55
SHC
3.94
3.90
3.87
3.84
3.80
3.76
3.72
22.0°CWB
TC
5.28
5.18
5.08
4.98
4.91
4.80
4.69
SHC
3.95
3.92
3.88
3.85
3.82
3.78
3.75
Model FDUMJ56HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
14
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
5.80
5.67
5.53
5.39
5.21
5.07
4.91
SHC
4.36
4.30
4.24
4.18
4.10
4.04
3.97
18.0°CWB
TC
5.97
5.84
5.70
5.57
5.43
5.25
5.11
SHC
4.39
4.33
4.27
4.21
4.16
4.08
4.02
19.0°CWB
TC
6.13
6.00
5.87
5.73
5.60
5.47
5.30
SHC
4.40
4.35
4.29
4.24
4.18
4.13
4.06
20.0°CWB
TC
6.25
6.15
6.04
5.90
5.77
5.63
5.50
SHC
4.40
4.36
4.32
4.26
4.21
4.16
4.10
21.0°CWB
TC
6.42
6.28
6.17
6.07
5.94
5.80
5.67
SHC
4.41
4.36
4.32
4.28
4.23
4.18
4.13
22.0°CWB
TC
6.57
6.45
6.32
6.19
6.10
5.97
5.84
SHC
4.42
4.37
4.32
4.28
4.25
4.20
4.15
Note (1) Symbols are as follows :
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
1005
FDC-HKXR
Model FDUMJ71HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
18
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
7.36
7.19
7.01
6.83
6.60
6.43
6.22
SHC
5.56
5.49
5.41
5.33
5.23
5.15
5.06
18.0°CWB
TC
7.57
7.40
7.23
7.06
6.89
6.66
6.48
SHC
5.59
5.52
5.45
5.37
5.30
5.21
5.13
19.0°CWB
TC
7.77
7.61
7.44
7.27
7.10
6.93
6.72
SHC
5.61
5.55
5.48
5.41
5.34
5.27
5.18
20.0°CWB
TC
7.92
7.80
7.65
7.48
7.31
7.14
6.97
SHC
5.61
5.56
5.50
5.44
5.37
5.30
5.24
21.0°CWB
TC
8.14
7.97
7.82
7.70
7.53
7.36
7.19
SHC
5.63
5.57
5.51
5.46
5.40
5.33
5.27
22.0°CWB
TC
8.34
8.18
8.01
7.85
7.74
7.57
7.40
SHC
5.64
5.58
5.52
5.46
5.42
5.36
5.30
Model FDUMJ90HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
20
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
9.32
9.11
8.89
8.66
8.37
8.15
7.88
SHC
6.71
6.61
6.51
6.40
6.27
6.17
6.05
18.0°CWB
TC
9.59
9.38
9.16
8.95
8.73
8.44
8.21
SHC
6.74
6.64
6.55
6.45
6.36
6.23
6.13
19.0°CWB
TC
9.85
9.65
9.43
9.22
9.00
8.78
8.51
SHC
6.76
6.67
6.58
6.49
6.39
6.30
6.19
20.0°CWB
TC
10.04
9.88
9.70
9.49
9.27
9.05
8.84
SHC
6.75
6.68
6.60
6.52
6.43
6.34
6.25
21.0°CWB
TC
10.31
10.10
9.92
9.76
9.54
9.32
9.11
SHC
6.76
6.67
6.60
6.54
6.45
6.37
6.28
22.0°CWB
TC
10.57
10.37
10.15
9.95
9.81
9.59
9.38
SHC
6.76
6.69
6.60
6.53
6.47
6.39
6.31
Model FDUMJ112HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
28
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
11.60
11.33
11.07
10.77
10.42
10.15
9.81
SHC
8.72
8.60
8.48
8.35
8.20
8.08
7.93
18.0°CWB
TC
11.94
11.67
11.40
11.13
10.86
10.51
10.21
SHC
8.77
8.66
8.54
8.42
8.31
8.16
8.04
19.0°CWB
TC
12.25
12.01
11.74
11.47
11.20
10.93
10.60
SHC
8.80
8.70
8.59
8.48
8.37
8.26
8.12
20.0°CWB
TC
12.50
12.30
12.07
11.80
11.54
11.27
11.00
SHC
8.80
8.72
8.63
8.52
8.42
8.31
8.20
21.0°CWB
TC
12.84
12.57
12.34
12.14
11.87
11.60
11.33
SHC
8.83
8.72
8.64
8.56
8.46
8.36
8.26
22.0°CWB
TC
13.15
12.90
12.63
12.39
12.21
11.94
11.67
SHC
8.84
8.75
8.65
8.56
8.49
8.39
8.30
Model FDUMJ140HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
34
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
14.50
14.17
13.83
13.47
13.02
12.68
12.26
SHC
10.78
10.63
10.48
10.31
10.12
9.97
9.78
18.0°CWB
TC
14.92
14.59
14.25
13.92
13.58
13.13
12.77
SHC
10.84
10.69
10.55
10.40
10.26
10.07
9.91
Note (1) Symbols are as follows :
1006
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
19.0°CWB
TC
15.32
15.01
14.67
14.34
14.00
13.66
13.24
SHC
10.88
10.75
10.60
10.46
10.32
10.19
10.01
20.0°CWB
TC
15.62
15.37
15.09
14.76
14.42
14.08
13.75
SHC
10.87
10.77
10.65
10.52
10.38
10.25
10.12
21.0°CWB
TC
16.04
15.71
15.43
15.18
14.84
14.50
14.17
SHC
10.90
10.77
10.66
10.56
10.43
10.30
10.18
22.0°CWB
TC
16.44
16.13
15.79
15.48
15.26
14.92
14.59
SHC
10.91
10.80
10.67
10.56
10.47
10.35
10.23
FDC-HKXR
(e) FDE Series
Model FDEJ36HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
14
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
3.73
3.64
3.56
3.46
3.35
3.26
3.15
SHC
3.34
3.30
3.26
3.23
3.18
3.15
3.10
18.0°CWB
TC
3.84
3.75
3.66
3.58
3.49
3.38
3.28
SHC
3.36
3.33
3.30
3.26
3.23
3.18
3.15
19.0°CWB
TC
3.94
3.86
3.77
3.69
3.60
3.51
3.41
SHC
3.39
3.36
3.32
3.29
3.26
3.23
3.19
20.0°CWB
TC
4.02
3.95
3.88
3.79
3.71
3.62
3.54
SHC
3.40
3.38
3.35
3.32
3.29
3.26
3.23
21.0°CWB
TC
4.13
4.04
3.97
3.90
3.82
3.73
3.64
SHC
3.42
3.39
3.37
3.34
3.31
3.28
3.25
22.0°CWB
TC
4.23
4.15
4.06
3.98
3.92
3.84
3.75
SHC
3.44
3.41
3.38
3.35
3.34
3.31
3.28
Model FDEJ45HKXE2B
Air flow
3
(m /min)
14
Indoor air temperature
Outdoor
air temp.
17.0°CWB
(°CDB)
TC
4.66
4.55
4.45
4.33
4.19
4.08
3.94
27
29
31
33
35
37
39
SHC
3.86
3.82
3.77
3.72
3.66
3.62
3.56
18.0°CWB
TC
4.80
4.69
4.58
4.47
4.37
4.22
4.10
SHC
3.89
3.85
3.80
3.76
3.71
3.66
3.61
19.0°CWB
TC
4.92
4.82
4.72
4.61
4.50
4.39
4.26
SHC
3.91
3.87
3.83
3.79
3.75
3.70
3.65
20.0°CWB
TC
5.02
4.94
4.85
4.74
4.64
4.53
4.42
SHC
3.92
3.89
3.85
3.81
3.77
3.73
3.69
21.0°CWB
TC
5.16
5.05
4.96
4.88
4.77
4.66
4.55
SHC
3.94
3.90
3.87
3.84
3.80
3.76
3.72
22.0°CWB
TC
5.28
5.18
5.08
4.98
4.91
4.80
4.69
SHC
3.95
3.92
3.88
3.85
3.82
3.78
3.75
Model FDEJ56HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
14
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
5.80
5.67
5.53
5.39
5.21
5.07
4.91
SHC
4.36
4.30
4.24
4.18
4.10
4.04
3.97
18.0°CWB
TC
5.97
5.84
5.70
5.57
5.43
5.25
5.11
SHC
4.39
4.33
4.27
4.21
4.16
4.08
4.02
19.0°CWB
TC
6.13
6.00
5.87
5.73
5.60
5.47
5.30
SHC
4.40
4.35
4.29
4.24
4.18
4.13
4.06
20.0°CWB
TC
6.25
6.15
6.04
5.90
5.77
5.63
5.50
SHC
4.40
4.36
4.32
4.26
4.21
4.16
4.10
21.0°CWB
TC
6.42
6.28
6.17
6.07
5.94
5.80
5.67
SHC
4.41
4.36
4.32
4.28
4.23
4.18
4.13
22.0°CWB
TC
6.57
6.45
6.32
6.19
6.10
5.97
5.84
SHC
4.42
4.37
4.32
4.28
4.25
4.20
4.15
Model FDEJ71HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
18
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
7.36
7.19
7.01
6.83
6.60
6.43
6.22
SHC
5.56
5.49
5.41
5.33
5.23
5.15
5.06
18.0°CWB
TC
7.57
7.40
7.23
7.06
6.89
6.66
6.48
SHC
5.59
5.52
5.45
5.37
5.30
5.21
5.13
19.0°CWB
TC
7.77
7.61
7.44
7.27
7.10
6.93
6.72
SHC
5.61
5.55
5.48
5.41
5.34
5.27
5.18
20.0°CWB
TC
7.92
7.80
7.65
7.48
7.31
7.14
6.97
SHC
5.61
5.56
5.50
5.44
5.37
5.30
5.24
21.0°CWB
TC
8.14
7.97
7.82
7.70
7.53
7.36
7.19
SHC
5.63
5.57
5.51
5.46
5.40
5.33
5.27
22.0°CWB
TC
8.34
8.18
8.01
7.85
7.74
7.57
7.40
SHC
5.64
5.58
5.52
5.46
5.42
5.36
5.30
Note (1) Symbols are as follows :
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
1007
FDC-HKXR
Model FDEJ112HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
28
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
11.60
11.33
11.07
10.77
10.42
10.15
9.81
SHC
8.72
8.60
8.48
8.35
8.20
8.08
7.93
18.0°CWB
TC
11.94
11.67
11.40
11.13
10.86
10.51
10.21
SHC
8.77
8.66
8.54
8.42
8.31
8.16
8.04
19.0°CWB
TC
12.25
12.01
11.74
11.47
11.20
10.93
10.60
SHC
8.80
8.70
8.59
8.48
8.37
8.26
8.12
20.0°CWB
TC
12.50
12.30
12.07
11.80
11.54
11.27
11.00
SHC
8.80
8.72
8.63
8.52
8.42
8.31
8.20
21.0°CWB
TC
12.84
12.57
12.34
12.14
11.87
11.60
11.33
SHC
8.83
8.72
8.64
8.56
8.46
8.36
8.26
22.0°CWB
TC
13.15
12.90
12.63
12.39
12.21
11.94
11.67
SHC
8.84
8.75
8.65
8.56
8.49
8.39
8.30
Model FDEJ140HKXE2B
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
34
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
14.50
14.17
13.83
13.47
13.02
12.68
12.26
SHC
10.78
10.63
10.48
10.31
10.12
9.97
9.78
18.0°CWB
TC
14.92
14.59
14.25
13.92
13.58
13.13
12.77
SHC
10.84
10.69
10.55
10.40
10.26
10.07
9.91
19.0°CWB
TC
15.32
15.01
14.67
14.34
14.00
13.66
13.24
SHC
10.88
10.75
10.60
10.46
10.32
10.19
10.01
20.0°CWB
TC
15.62
15.37
15.09
14.76
14.42
14.08
13.75
SHC
10.87
10.77
10.65
10.52
10.38
10.25
10.12
21.0°CWB
TC
16.04
15.71
15.43
15.18
14.84
14.50
14.17
SHC
10.90
10.77
10.66
10.56
10.43
10.30
10.18
22.0°CWB
TC
16.44
16.13
15.79
15.48
15.26
14.92
14.59
SHC
10.91
10.80
10.67
10.56
10.47
10.35
10.23
(f) FDK Series
Model FDKJ22HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
9
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
2.27
2.22
2.17
2.11
2.05
1.99
1.93
SHC
2.04
2.02
2.00
1.98
1.95
1.93
1.91
18.0°CWB
TC
2.34
2.29
2.24
2.18
2.12
2.07
2.01
SHC
2.06
2.04
2.02
2.00
1.98
1.95
1.93
19.0°CWB
TC
2.40
2.35
2.30
2.25
2.20
2.14
2.08
SHC
2.08
2.06
2.04
2.02
2.00
1.98
1.95
20.0°CWB
TC
2.46
2.41
2.36
2.31
2.27
2.21
2.15
SHC
2.09
2.07
2.05
2.03
2.02
2.00
1.98
21.0°CWB
TC
2.52
2.48
2.43
2.37
2.32
2.27
2.22
SHC
2.10
2.08
2.07
2.05
2.03
2.01
2.00
22.0°CWB
TC
2.57
2.53
2.48
2.44
2.39
2.34
2.29
SHC
2.11
2.09
2.08
2.06
2.04
2.03
2.01
Model FDKJ28HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
10
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
2.90
2.83
2.77
2.69
2.60
2.54
2.45
SHC
2.58
2.55
2.52
2.49
2.46
2.43
2.40
18.0°CWB
TC
2.98
2.92
2.85
2.78
2.72
2.63
2.55
SHC
2.60
2.57
2.55
2.52
2.49
2.46
2.43
Note (1) Symbols are as follows :
1008
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
19.0°CWB
TC
3.06
3.00
2.93
2.87
2.80
2.73
2.65
SHC
2.62
2.59
2.57
2.54
2.52
2.49
2.46
20.0°CWB
TC
3.12
3.07
3.02
2.95
2.88
2.82
2.75
SHC
2.63
2.61
2.59
2.56
2.54
2.52
2.49
21.0°CWB
TC
3.21
3.14
3.09
3.04
2.97
2.90
2.83
SHC
2.64
2.62
2.60
2.58
2.56
2.54
2.51
22.0°CWB
TC
3.29
3.23
3.16
3.10
3.05
2.98
2.92
SHC
2.66
2.64
2.61
2.59
2.58
2.55
2.53
FDC-HKXR
Model FDKJ36HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
10
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
3.73
3.64
3.56
3.46
3.35
3.26
3.15
SHC
2.93
2.89
2.86
2.82
2.77
2.73
2.68
18.0°CWB
TC
3.84
3.75
3.66
3.58
3.49
3.38
3.28
SHC
2.95
2.91
2.88
2.84
2.81
2.76
2.72
19.0°CWB
TC
3.94
3.86
3.77
3.69
3.60
3.51
3.41
SHC
2.96
2.93
2.90
2.86
2.83
2.79
2.75
20.0°CWB
TC
4.02
3.95
3.88
3.79
3.71
3.62
3.54
SHC
2.97
2.94
2.91
2.88
2.85
2.81
2.78
21.0°CWB
TC
4.13
4.04
3.97
3.90
3.82
3.73
3.64
SHC
2.98
2.95
2.92
2.89
2.86
2.83
2.80
22.0°CWB
TC
4.23
4.15
4.06
3.98
3.92
3.84
3.75
SHC
2.98
2.96
2.93
2.90
2.88
2.85
2.82
Model FDKJ45HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
11.5
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
4.66
4.55
4.45
4.33
4.19
4.08
3.94
SHC
3.54
3.49
3.44
3.39
3.33
3.28
3.22
18.0°CWB
TC
4.80
4.69
4.58
4.47
4.37
4.22
4.10
SHC
3.56
3.51
3.46
3.42
3.37
3.31
3.26
19.0°CWB
TC
4.92
4.82
4.72
4.61
4.50
4.39
4.26
SHC
3.57
3.53
3.48
3.44
3.40
3.35
3.30
20.0°CWB
TC
5.02
4.94
4.85
4.74
4.64
4.53
4.42
SHC
3.57
3.54
3.50
3.46
3.42
3.37
3.33
21.0°CWB
TC
5.16
5.05
4.96
4.88
4.77
4.66
4.55
SHC
3.58
3.54
3.51
3.47
3.43
3.39
3.35
22.0°CWB
TC
5.28
5.18
5.08
4.98
4.91
4.80
4.69
SHC
3.59
3.55
3.51
3.47
3.45
3.41
3.37
Model FDKJ56HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
17
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
5.80
5.67
5.53
5.39
5.21
5.07
4.91
SHC
4.75
4.69
4.64
4.57
4.50
4.44
4.37
18.0°CWB
TC
5.97
5.84
5.70
5.57
5.43
5.25
5.11
SHC
4.78
4.73
4.67
4.62
4.56
4.49
4.43
19.0°CWB
TC
6.13
6.00
5.87
5.73
5.60
5.47
5.30
SHC
4.81
4.76
4.71
4.65
4.60
4.55
4.48
20.0°CWB
TC
6.25
6.15
6.04
5.90
5.77
5.63
5.50
SHC
4.82
4.78
4.74
4.69
4.64
4.59
4.54
21.0°CWB
TC
6.42
6.28
6.17
6.07
5.94
5.80
5.67
SHC
4.84
4.79
4.75
4.71
4.66
4.62
4.57
22.0°CWB
TC
6.57
6.45
6.32
6.19
6.10
5.97
5.84
SHC
4.86
4.81
4.77
4.72
4.69
4.65
4.60
Model FDKJ71HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
21
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
7.36
7.19
7.01
6.83
6.60
6.43
6.22
SHC
5.95
5.87
5.80
5.72
5.63
5.56
5.47
18.0°CWB
TC
7.57
7.40
7.23
7.06
6.89
6.66
6.48
SHC
5.99
5.92
5.85
5.78
5.71
5.62
5.54
19.0°CWB
TC
7.77
7.61
7.44
7.27
7.10
6.93
6.72
SHC
6.02
5.96
5.89
5.82
5.75
5.69
5.61
20.0°CWB
TC
7.92
7.80
7.65
7.48
7.31
7.14
6.97
SHC
6.03
5.98
5.93
5.86
5.80
5.73
5.67
21.0°CWB
TC
8.14
7.97
7.82
7.70
7.53
7.36
7.19
SHC
6.06
5.99
5.94
5.89
5.83
5.77
5.71
22.0°CWB
TC
8.34
8.18
8.01
7.85
7.74
7.57
7.40
SHC
6.07
6.02
5.96
5.90
5.86
5.81
5.75
Note (1) Symbols are as follows :
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
1009
FDC-HKXR
(g) FDFL, FDFU Series
Models FDFLJ28HKXE2, FDFUJ28HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
12
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
2.90
2.83
2.77
2.69
2.60
2.54
2.45
SHC
2.58
2.55
2.52
2.49
2.46
2.43
2.40
18.0°CWB
TC
2.98
2.92
2.85
2.78
2.72
2.63
2.55
SHC
2.60
2.57
2.55
2.52
2.49
2.46
2.43
19.0°CWB
TC
3.06
3.00
2.93
2.87
2.80
2.73
2.65
SHC
2.62
2.59
2.57
2.54
2.52
2.49
2.46
20.0°CWB
TC
3.12
3.07
3.02
2.95
2.88
2.82
2.75
SHC
2.63
2.61
2.59
2.56
2.54
2.52
2.49
21.0°CWB
TC
3.21
3.14
3.09
3.04
2.97
2.90
2.83
SHC
2.64
2.62
2.60
2.58
2.56
2.54
2.51
22.0°CWB
TC
3.29
3.23
3.16
3.10
3.05
2.98
2.92
SHC
2.66
2.64
2.61
2.59
2.58
2.55
2.53
Models FDFLJ45HKXE2, FDFUJ45HKXE2
Air flow
3
(m /min)
14
Indoor air temperature
Outdoor
air temp.
(°CDB)
17.0°CWB
TC
4.66
4.55
4.45
4.33
4.19
4.08
3.94
27
29
31
33
35
37
39
SHC
3.86
3.82
3.77
3.72
3.66
3.62
3.56
18.0°CWB
TC
4.80
4.69
4.58
4.47
4.37
4.22
4.10
SHC
3.89
3.85
3.80
3.76
3.71
3.66
3.61
19.0°CWB
TC
4.92
4.82
4.72
4.61
4.50
4.39
4.26
SHC
3.91
3.87
3.83
3.79
3.75
3.70
3.65
20.0°CWB
TC
5.02
4.94
4.85
4.74
4.64
4.53
4.42
SHC
3.92
3.89
3.85
3.81
3.77
3.73
3.69
21.0°CWB
TC
5.16
5.05
4.96
4.88
4.77
4.66
4.55
SHC
3.94
3.90
3.87
3.84
3.80
3.76
3.72
22.0°CWB
TC
5.28
5.18
5.08
4.98
4.91
4.80
4.69
SHC
3.95
3.92
3.88
3.85
3.82
3.78
3.75
Models FDFLJ71HKXE2, FDFUJ71HKXE2
Air flow
3
(m /min)
Outdoor
air temp.
(°CDB)
18
27
29
31
33
35
37
39
Indoor air temperature
17.0°CWB
TC
7.36
7.19
7.01
6.83
6.60
6.43
6.22
SHC
5.56
5.49
5.41
5.33
5.23
5.15
5.06
18.0°CWB
TC
7.57
7.40
7.23
7.06
6.89
6.66
6.48
SHC
5.59
5.52
5.45
5.37
5.30
5.21
5.13
Note (1) Symbols are as follows :
1010
TC
: Total cooling capacity (kW)
SHC
: Sensible heat capacity (kW)
19.0°CWB
TC
7.77
7.61
7.44
7.27
7.10
6.93
6.72
SHC
5.61
5.55
5.48
5.41
5.34
5.27
5.18
20.0°CWB
TC
7.92
7.80
7.65
7.48
7.31
7.14
6.97
SHC
5.61
5.56
5.50
5.44
5.37
5.30
5.24
21.0°CWB
TC
8.14
7.97
7.82
7.70
7.53
7.36
7.19
SHC
5.63
5.57
5.51
5.46
5.40
5.33
5.27
22.0°CWB
TC
8.34
8.18
8.01
7.85
7.74
7.57
7.40
SHC
5.64
5.58
5.52
5.46
5.42
5.36
5.30
FDC-HKXR
20.2.7 Characteristics of fan
(1) Cassetteria type (FDR)
How to interpret the blower characteristics table
● External static pressure table
Duct specs.
40(4)
45(4.5) 85(8.5) 45(4.5) 85(8.5)
FDR45
56 type
FDR71 type
14
-
-
18
30(3) 65(6.5) 45(4.5) 80(8)
50(5)
85(8.5)
FDR90 type
20
25(2.5) 60(6) 45(4.5) 80(8)
50(5)
85(8.5)
FDR112 type
28
40(4)
70(7)
50(5)
80(8) 55(5.5) 85(8.5)
FDR140 type
34
40(4)
70(7)
50(5)
80(8) 55(5.5) 85(8.5)
Static pressure Pa (mmAq)
45(4.5) 85(8.5) 50(5)
-
90(9)
50(5) 85(8.5) 50(5)
90(9)
20(2)
0(0)
-20(-2)
2 Square duct blowout...........
Internal resistance decreases more
than the standard round duct
(ø200 3-spot). 3Pa (0.3mmAq) at
17 m3/nin. (External static pressure increases in reverse.)
ium
ed
-
-
M
-
12
rd
da
an
10
FDR28 type
w
Lo
FDR22 type
St
Stan- High(4) Stan- High(4) Stan- High(4)
dard speed dard speed dard speed
Type
1 2-spot blowout.....................
Internal resistance increases more
than the standard 3-spot blowout.
Approx. 14Pa(1.4mmAq) at
17m3/min
Example : Case of FDRJ71HKXE2
Square duct (3)
rd
da
an h
St Hig
Standard (2)
rd
da
an
St
Air flow
(m3 /min)
1 spot (1)
closing
Unit : Pa (mmAq)
2-spot blower
internal resistance
[Standard]
3-spot blower
internal resistance
Square duct blower
internal resistance
3 Suction panel.......................
When the suction panel is not
used with the ceiling return type,
the part of internal resistance related to the panel decrease. 3Pa
20
(0.3mmAq) at 17mm3/min.
Internal resistance without
withoutsuction
suctionpanel
panel
Internal resistance without filter
13 14
Notes (1) 1 spot closing: Round duct flange at center is removed and shield with a
special panel (option).
(2) Standard: Ø200 duct are installed at all blowout holes.
(3) Square duct: All round ducts are removed and replaced with special
square duct flanges (option).
(4) When operating at a high speed, invert the connection of white and red
connectors on the flank of control box.
16
18
Air flow (m3 /min)
Model FDRJ28HKXE2
Model FDRJ22HKXE2
120(12)
100(10)
Hi
d
ee
sp it
h
Hig w lim
Lo
gh
m
9
0(0)
(0)0
[Standard]
2-spot blower internal resistance
Square duct blower internal resistance
Internal resistance without suction panel
Internal resistance without filter
8
•Hi
diu
Me
m
(0)0
[Standard]
1-spot blower internal resistance
Square duct blower internal resistance
ard
iu
•
ard
nd
h
20(2)
nd
ig
•H
Sta
Static pressure Pa (mmAq)
gh
40(4)
ed
ow
•M
•L
20(2)
Hi
rd
rd
rd
da
da
an
an
S per
Up
Sta
da
St
60(6) ndard it
lim
ta
w
ium
ed
•Lo
ed
pe
ard
•M
hs
nd
Hig w
Sta
Lo
an
40(4)
•
ed
ed
pe
h s it
g
i
m
H w li
Lo
d•
pe
gh
ee
d•
sp
ee
gh
Hi
80(8)
sp
St
ard t
nd limi
Sta per
Up
gh
hs
60(6)
Hi
Hig
d
ee
sp imit
h
l
g
80(8)
Hi per
H
Up
Hi
M igh
Lo gh
e
di sp
w sp
um ee
ee
d
d
St
Static pressure Pa (mmAq)
100(10)
d•
ee
sp it
h
im
Hig per l
Up
10
(-2)-20
Air flow (m3/min)
(-2)-20
Internal resistance without filter
11
Upper
limit
Lower
limit
Internal resistance without suction panel
10
12
14
15.5
Upper
limit
Lower
limit
Air flow (m3/min)
1011
FDC-HKXR
Models FDRJ45HKXE2, 56HKXE2
Model FDRJ71HKXE2
120(12)
120(12)
d•
pee
h sr limit
g
i
H pe
Up
Hi
e
sp
it
ed
•M
ed
60(6)
lim
r
pe
Up
it
ow
gh
S
Hi
ta
ium
rd•
a
nd
gh
gh
Hi
gh
Hi
s
gh
sp
ar
w
•L
an
St
rd
gh
Hi
d•
da
ium
ed
•M
rd
da
ow
2-spot blower internal resistance
(0)0
[Standard]
2-spot blower internal resistance
Square duct blower internal resistance
[Standard] 3-spot blower internal resistance
(-2)-20
12
14
Air flow (m /min)
13 14
Lower
limit
18
20
Upper
limit
120(12)
100(10)
100(10)
gh
ee
sp
igh
gh
sp
ium
ed
M
d
ee
gh
sp
ow
li
•L
St
•
ed
60(6)
rd•
nda
t
Sta er limi
p
p
Hi
U
g
h
Hi
gh
sp
ee
d•
H
sp
ee
igh
d•
M
ed
ee
d
Lo
w
it
ium
sp
h
Hig
lim
Hi
gh
ow
um
edi
M
rd•
m
diu
Me
•
rd
da
an
St
gh
•L
rd
da
an
Hi
•
rd
nda
w
Lo
20(2)
w
•Lo
ed
St
an
da
rd
•
spe
40(4)
St
da
an
Hi
Sta
•
ard
nd
20(2)
t
mi
Static pressure Pa (mmAq)
d•
ee
40(4)
80(8)
H
d•
Hi
e
sp
gh
Hi ow
L
•
ard t
nd limi
a
t
r
S pe
Up
d•
ee
sp mit
h
i
l
Hig per
Up
Hi
gh
Hi
d•
ee
sp mit
h
i
Hig per l
Up
Sta
Static pressure Pa (mmAq)
16
Air flow (m3/min)
Model FDRJ112HKXE2
120(12)
60(6)
(-2)-20
Internal resistance without suction panel
Internal resistance without filter
15.5
Upper
limit
3
Model FDRJ90HKXE2
80(8)
(0)0
Square duct blower internal resistance
Internal resistance without suction panel
Internal resistance without filter
10
Lower
limit
•L
d
an
Hi
Lo
an
gh
w
Lo
20(2)
lim
St
gh
d
St
•Hi
ard
40(4)
ee
nd
d
ee
sp
Sta
m
diu
Me
rd•
nda
Sta
•
ard
nd
Sta
Static pressure Pa (mmAq)
Hi
ium
40(4)
e
pe
Hi
lim
d•
ee
sp
d•
ed
•M
ed
h
Hig
gh
ee
p
dU
80(8)
it
w
•Lo
ed
e
sp
lim
r
pe
Hi
sp
e
sp
•
imit
er l
p
•Up
ard
60(6) Stand
20(2)
it
gh
gh
Hi
rd
da
an
St w
Lo
80(8)
100(10)
Static pressure Pa (mmAq)
100(10)
2-spot blower
internal resistance
(0)0
3-spot blower
internal resistance
0(0)
4-spot blower internal resistance[Standard]
3 - spot blower internal resistance[Standard]
Square duct blower internal resistance
Square duct blower internal resistance
(-2)-20
Internal resistance without suction panel
Internal resistance without filter
14
Lower
limit
1012
17
-2(-20)
Internal resistance without suction panel
Internal resistance without filter
20
Air flow (m3/min)
22
Upper
limit
21 22
Lower
limit
25
28
Air flow (m3/min)
31
Upper
limit
FDC-HKXR
Model FDRJ140HKXE2
120(12)
d
ee
sp
m
iu
da
an
St
w
Lo
d•
ee
sp
d
ee
sp it
h
g
m
Hi w li
Lo
a
St
40(4)
h
ig
ed
M
d•
gh
60(6)
•H
ee
•
rd t
da limi
n
a r
St ppe
U
Hi
H
rd•
igh
20(2)
•M
rd
w
da
Lo
d•
ar
an
St
nd
Static pressure Pa (mmAq)
h
ig
H
sp
80(8)
gh
Hi
•
ed
pe it
s
m
gh li
Hi per
p
U
100(10)
ium
ed
3-spot blower
internal resistance
(0)0
(0)0
4-spot blower internal resistance
[Standard]
Square duct blower internal resistance
Internal resistance without suction panel
Internal resistance without filter
24
Lower
limit
26
30
34
3
Air flow (m /min)
(-2)-20
38
Upper
limit
1013
FDC-HKXR
(2) Satellite ducted type (FDUM)
● External static pressure table
Duct specs.
1 spot
closing
Standard
Square duct
How to interpret the blower characteristics table
Example : Case of FDUMJ71HKXE2
40(4)
90(9)
50(5)
90(9)
18
35(3.5)
70(7)
50(5)
85(8.5) 55(5.5)
FDUM90 type
20
30(3)
65(6.5)
50(5)
85(8.5) 55(5.5)
FDUM112 type
28
50(5)
80(8)
60(6)
FDUM140 type
34
50(5)
75(7.5)
60(6)
90(9)
90(9)
90(9)
65(6.5)
95(9.5)
85(8.5) 65(6.5)
95(9.5)
Note (1) For high speed operation, insert the white connector and the red
connector beside the control box in other places respectively.
Static pressure Pa (mmAq)
50(5)
85(8.5)
rd
da
an um
St edi
M
85(8.5)
50(5)
w
50(5)
-
Lo
-
-
rd
-
14
da
12
an
FDUM36 type
FDUM45
56 type
FDUM71 type
St
Stan- High(4) Stan- High(4) Stan- High(1)
dard speed dard speed dard speed
Type
rd
da
an gh
St H i
Air flow
(m3 /min)
Unit : Pa (mmAq)
20(2)
2-spot blower
internal resistance
0(0)
-10(-1)
3-spot blower
internal resistance
Square duct blower
internal resistance
-20(-2)
13 14
16
18
20
Air flow (m /min)
3
1 2-spot blowout.....................
Internal resistance increases more than
the standard 3-spot blowout. Approx.
14Pa(1.4mmAq) at 17m3/min
2 Square duct blowout...........
Internal resistance decreases more than
the standard round duct (ø200 3-spot).
3Pa(0.3mmAq) at 17 m3/min. (External
static pressure increases in reverse.)
Model FDUMJ36HKXE2
Models FDUMJ45HKXE2, 56HKXE2
120(12)
er
pp
100(10)
U
d•
t
imi
l
spe
100(10)
igh
•H
Static pressure Pa (mmAq)
gh
ard
nd
Sta
ard
nd
Static pressure Pa (mmAq)
Hi
ium
•
ium
ed
•M
rd
20(2)
Sta
a
nd
Sta w
Lo
igh
•H
ard
nd
ium
Sta
ed
•M
ard
nd
Sta
w
Lo
rd•
d
ee
sp it
h
Hig w lim
Lo
40(4)
0(0)
Square duct blower internal resistance
-10(-1)
-20(-2)
1014
it
lim
d
Me
d•
er
p
•Up
0(0)
2-spot blower internal resistance
d•
ee
ard
nd
Sta
ee
sp
60(6)
sp
gh
e
sp
ow
lim
d•L
it
w
•Lo
ed
a
nd
Sta
h
Hig
Hi
ee
80(8)
gh
ium
•
ed
ed
•M
pe
ed
hs
Hig w
Lo
20(2)
sp
Hi
d•
gh
ee
pe
hs
40(4)
Hi
sp
Hig
•
ard
nd limit
a
t
S per
Up
gh
gh
Hi
80(8)
Hi
•
ed
spe it
h
m
Hig per li
Up
e
h
Hig
10
12
14
10
Lower
limit
Air flow (m3/min)
Upper
limit
Lower
limit
2-spot blower internal resistance
[Standard]
Square duct blower internal resistance
12
Air flow (m3/min)
14
15.5
Upper
limit
FDC-HKXR
Model FDUMJ71HKXE2
Model FDUMJ90HKXE2
120(12)
120(12)
100(10)
ee
da
an
ow
St
L
d•
gh
Hi
rd•
40(4)
Sta
w
ium
Me
rd•
20(2)
ed
2-spot blower internal resistance
nda
•Lo
ard
•M
rd
nd
da
Sta
Static pressure Pa (mmAq)
d•
ee
p
s it
gh lim
Hi w
Lo
sp
Static pressure Pa (mmAq)
m
iu
ed
M
d•
ee
sp
U
rd•
da
60(6) Stan
gh
an
diu
0(0)
t
mi
r li
e
pp
Hi
St
20(2)
gh
Hi
gh
m
iu
w
d•
r
da
an
St w
Lo
Lo
d•
ee
sp
40(4)
h
ig
•H
Hi
ed
M
d•
gh
Hi
d
ee
sp it
h
ig lim
H ow
L
d
ee
sp
d•
ee
sp
ee
•
rd
da limit
n
a
St per
Up
h
ig
H
gh
80(8)
sp
60(6)
d•
ee
sp it
h
m
Hig per li
Up
Hi
gh
Hi
80(8)
100(10)
d
ee
sp mit
h
i
l
g
Hi per
Up
(0)0
m
[Standard]
3-spot blower internal resistance
Square duct blower internal resistance
(-1)-10
0(0)
(-2)-20
2-spot blower internal resistance
-10(-1)
3-spot blower internal resistance
13 14
Lower
limit
16
18
Square duct blower internal resistance
20
Upper
limit
Air flow (m3/min)
14
Lower
limit
Model FDUMJ112HKXE2
120(12)
100(10)
igh
•M
rd
ed
Static pressure Pa (mmAq)
H
d•
r
da
an
da
Static pressure Pa (mmAq)
St
40(4)
rd
ium
0(0)
3-spot blower internal resistance
ium
20(2)
ow
•L
rd
da
an
ed
d
ee
sp it
h
g
m
Hi w li
Lo
an
St
St
rd
•M
da
an
St w
Lo
da
um
an
ow
St
40(4)
60(6)
L
d•
igh
ee
ow
d•
H
sp
ar
gh
d•
L
Hi
ee
•
ed
spe it
h
Hig w lim S
tan
Lo
d
h
ig
ium
i
ed
ed
•
rd
da limit
n
a
St per
Up
•M
d•
M
H
80(8)
ee
d
ee
sp
igh
sp
d•
gh
d•H
ee
sp
ee
h
sp
ig
gh
d
ee
sp imit
h
l
g
Hi per
Up
H
Hi
100(10)
Hi
d•
pee
h s limit
g
i
H er
p
Hi
Up
gh
it
r lim
ppe
U
•
rd
Hi
gh
nda
60(6) Sta
sp
20(2)
22
Upper
limit
Model FDUMJ140HKXE2
120(12)
80(8)
17
20
Air flow (m3/min)
3-spot blower internal resistance
0(0)
4-spot blower internal resistance[Standard]
4-spot blower internal resistance
(-1)-10
(-1)-10
Square duct blower internal resistance
Square duct blower internal resistance
24
21
Lower
limit
25
28
Air flow (m3/min)
31
Upper
limit
Lower
limit
26
30
34
Air flow (m3/min)
38
Upper
limit
1015
FDC-HKXR
20.2.8 Noise level
Notes (1) The data are based on the following conditions.
Ambient air tempetature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit 35˚C DB
(2) The data in the chart are measuted in an unechonic room.
(3) The noise levels measured in the field are usually higher than the data because of reflection.
(1) Indoor unit
Measured based on JIS B 8616
Mike position as below Mike position as below
(a) Ceiling recessed type (FDT)
1.5m
Mike (center & low points)
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
125
250
500
1000
2000
4000
20
8000
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
20
8000
4000
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
125
250
500
1000
2000
4000
20
8000
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
70
N70
60
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
70
63
60
N60
50
N50
40
40
N40
30
30
N2
N30
0
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
20
8000
4000
250
500
1000
2000
20
8000
4000
Model FDTJ140HKXE2
Noise level 50 dB (A) at HIGH
47 dB (A) at MEDIUM
45 dB (A) at LOW
70
50
125
Mid octave band frequency (Hz)
N70
60
N30
0
20
Mid octave band frequency (Hz)
Model FDTJ90HKXE2
Model FDTJ112HKXE2
Noise level 42 dB (A) at HIGH
Noise level 49 dB (A) at HIGH
40 dB (A) at MEDIUM
46 dB (A) at MEDIUM
38 dB (A) at LOW
42 dB (A) at LOW
70
Sound pressure level
(Standard 0.0002µ bar) dB
70
N70
Model FDTJ71HKXE2
Noise level 40 dB (A) at HIGH
38 dB (A) at MEDIUM
36 dB (A) at LOW
Sound pressure level
(Standard 0.0002µ bar) dB
70
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
Models FDTJ28HKXE2, 36HKXE2 Models FDTJ45HKXE2, 56HKXE2
Noise level 37 dB (A) at HIGH
Noise level 38 dB (A) at HIGH
34 dB (A) at MEDIUM
35 dB (A) at MEDIUM
33 dB (A) at LOW
34 dB (A) at LOW
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B Model FDTWJ71HKXE2B
56HKXE2B
Measured based on JIS B 8616
Noise level 39 dB (A) at HIGH
Noise level 41 dB (A) at HIGH
Mike position as below
36 dB (A) at MEDIUM
38 dB (A) at MEDIUM
33 dB (A) at LOW
35 dB (A) at LOW
Mike position as below
70
70
70
Mike (center & low points)
60
60
N60
50
50
N50
40
40
N40
30
30
20
63
125
250
500
1000
2000
4000
Mid Octave Band Frequency (Hz)
1016
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
70
N70
Souud Pressure Level
(standard 0.0002µ bar)
1.5m
Souud Pressure Level
(standard 0.0002µ bar)
N70
N30
N2
0
20
8000
20
63
125
250
500
1000
2000
4000
Mid Octave Band Frequency (Hz)
20
8000
FDC-HKXR
Model FDTWJ90HKXE2B
Model FDTWJ112HKXE2B
Model FDTWJ140HKXE2B
Noise level 41 dB (A) at HIGH
Noise level 44 dB (A) at HIGH
Noise level 45 dB (A) at HIGH
39 dB (A) at MEDIUM
41 dB (A) at MEDIUM
42 dB (A) at MEDIUM
36 dB (A) at LOW
38 dB (A) at LOW
39 dB (A) at LOW
70
70
70
60
N60
50
50
N50
40
40
N40
30
30
N2
125
250
0
500
60
60
50
50
N50
40
40
N40
30
30
1000
2000
4000
N2
20
8000
63
125
250
500
60
60
N60
50
50
N50
40
40
N40
30
30
N30
0
20
1000
2000
4000
N2
20
8000
N30
0
20
63
Mid Octave Band Frequency (Hz)
Mid Octave Band Frequency (Hz)
70
N70
N60
N30
20
63
Souud Pressure Level
(standard 0.0002µ bar)
Souud Pressure Level
(standard 0.0002µ bar)
60
70
N70
N70
Souud Pressure Level
(standard 0.0002µ bar)
70
125
250
500
1000
2000
4000
20
8000
Mid Octave Band Frequency (Hz)
(c) 1-way outlet ceiling recessed type (FDTS)
Measured based on JIS B 8616
Mike position as below
1.5m
Mike (center & low points)
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
Model FDTSJ45HKXE2B
Noise level 43 dB (A) at HIGH
40 dB (A) at MEDIUM
38 dB (A) at LOW
Sound pressure level
(Standard 0.0002 µ bar) dB
70
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
Model FDTSJ22HKXE2B
Models FDTSJ28HKXE2B, 36HKXE2B
Noise level 39 dB (A) at MEDIUM
Noise level 40 dB (A) at HIGH
38 dB (A) at LOW
39 dB (A) at MEDIUM
38 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDTSJ71HKXE2B
Noise level 44 dB (A) at HIGH
40 dB (A) at MEDIUM
38 dB (A) at LOW
Mid octave band frequency (Hz)
1017
FDC-HKXR
(d) Cassetteria type (FDR)
Unit
1.5m
Measured based on JIS B 8616
Mike position as below
Mike (center & low points)
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDRJ28HKXE2
Models FDRJ45HKXE2, 56HKXE2
Noise level 43 dB (A) at HIGH
Noise level 44 dB (A) at HIGH
41 dB (A) at MEDIUM
41 dB (A) at MEDIUM
38 dB (A) at LOW
38 dB (A) at LOW
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
(i) Canvas duct Panel type
Model FDRJ22HKXE2
Noise level 42 dB (A) at HIGH
40 dB (A) at MEDIUM
37 dB (A) at LOW
1.5m
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Models FDRJ71HKXE2, 90HKXE2
Model FDRJ112HKXE2
Model FDRJ140HKXE2
Noise level 44 dB (A) at HIGH
Noise level 46 dB (A) at HIGH
Noise level 47 dB (A) at HIGH
41 dB (A) at MEDIUM
43 dB (A) at MEDIUM
44 dB (A) at MEDIUM
38 dB (A) at LOW
39 dB (A) at LOW
40 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
1018
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
(ii) Silent Panel type
Model FDRJ22HKXE2
Model FDRJ28HKXE2
Models FDRJ45HKXE2, 56HKXE2
Noise level 43 dB (A) at HIGH
Noise level 42 dB (A) at HIGH
Noise level 41 dB (A) at HIGH
39 dB (A) at MEDIUM
40 dB (A) at MEDIUM
40 dB (A) at MEDIUM
37 dB (A) at LOW
37 dB (A) at LOW
36 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
FDC-HKXR
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Models FDRJ71HKXE2, 90HKXE2
Model FDRJ112HKXE2
Model FDRJ140HKXE2
Noise level 43 dB (A) at HIGH
Noise level 45 dB (A) at HIGH
Noise level 46 dB (A) at HIGH
40 dB (A) at MEDIUM
42 dB (A) at MEDIUM
43 dB (A) at MEDIUM
37 dB (A) at LOW
38 dB (A) at LOW
39 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
(d) Satellite ducted type (FDUM)
Measured based on JIS B 8616
Mike position as below
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Noise level 34 dB (A) at HIGH
32 dB (A) at MEDIUM
29 dB (A) at LOW
Models FDUMJ45HKXE2, 56HKXE2 Model FDUMJ90HKXE2
71HKXE2
Noise level 36 dB (A) at HIGH
Noise level 35 dB (A) at HIGH
32 dB (A) at MEDIUM
33 dB (A) at MEDIUM
30 dB (A) at LOW
29 dB (A) at LOW
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDUMJ36HKXE2
1.5m
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDUMJ112HKXE2
Model FDUMJ140HKXE2
Noise level 38 dB (A) at HIGH
Noise level 39 dB (A) at HIGH
35 dB (A) at MEDIUM
37 dB (A) at MEDIUM
32 dB (A) at LOW
34 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
1019
FDC-HKXR
1m
(f) Ceiling suspension type (FDE)
Unit
1m
Measured based on JIS B 8616
Mike position as below
Noise level 44 dB (A) at HIGH
40 dB (A) at MEDIUM
38 dB (A) at LOW
Mid octave band frequency (Hz)
Model FDEJ112HKXE2B
Noise level 49 dB (A) at HIGH
46 dB (A) at MEDIUM
42 dB (A) at LOW
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDEJ71HKXE2B
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Models FDEJ36HKXE2B, 45HKXE2B
56HKXE2B
Noise level 43 dB (A) at HIGH
40 dB (A) at MEDIUM
38 dB (A) at LOW
Mike (front & low point)
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDEJ140HKXE2B
Noise level 50 dB (A) at HIGH
47 dB (A) at MEDIUM
42 dB (A) at LOW
Mid octave band frequency (Hz)
(g) Wall mounted type (FDK)
Measured based on JIS B 8616
Mike position as below
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
1020
Model FDKJ45HKXE2
Noise level 44 dB (A) at HIGH
41 dB (A) at MEDIUM
37 dB (A) at LOW
Sound pressure level
(Standard 0.0002 µ bar) dB
60
N60
50
Mike
(Center & low points)
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
70
N70
60
1m
Models FDKJ28HKXE2, 36HKXE2
Noise level 42 dB (A) at HIGH
40 dB (A) at MEDIUM
37 dB (A) at LOW
Model FDKJ22HKXE2
Noise level 40 dB (A) at HIGH
37 dB (A) at LOW
70
1m
Unit
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
FDC-HKXR
Model FDKJ56HKXE2
Noise level 46 dB (A) at HIGH
43 dB (A) at MEDIUM
39 dB (A) at LOW
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Model FDKJ71HKXE2
Noise level 47 dB (A) at HIGH
44 dB (A) at MEDIUM
40 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
(h) Floor standing exposed type (FDFL)
(i) Floor standing hidden type (FDFU)
Measured based on JIS B 8616
Mike position as below
Indoor unit
Mike (front & at low point)
1m
1m
Models FDFLJ 45HKXE2,71HKXE2
FDFUJ45HKXE2, 56HKXE2
71HKXE2
Noise level 43 dB (A) at HIGH
41 dB (A) at MEDIUM
40 dB (A) at LOW
Sound pressure level
(Standard 0.0002 µ bar) dB
Sound pressure level
(Standard 0.0002 µ bar) dB
Models FDFLJ28HKXE2
FDFUJ28HKXE2
Noise level 41 dB (A) at HIGH
38 dB (A) at MEDIUM
36 dB (A) at LOW
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
(2) Outdoor unit (FDC)
Microphone
position of
noise meter
˚
Elevation
45
Note (1) The microphone position is as shown
below.
(JIS - B8616 · Coolong)
It is the maximum noise level point
which locates on the vertical face 1 m
apart from unit side face.
1m
1m
Sound pressure level
(Standard 0.0002 µ bar) dB
Models FDCP2001HKXRE2, 2501HKXRE2
Noise level 60 dB (A)
70
70
60
60
50
50
40
40
30
30
63
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
1021
B
TB
A
N
BL
BL
WH
RD
Y/GN
Fan motor
Internal thermostat for FMI
Capacitor for FMI
Drain motor
Float switch (For overflow prevention)
Louver motor
Limit switch
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For DM)
Auxiliary relay (For LM)
ThI-A
ThI-R
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
1
2
X2
Thermistor
Thermistor
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Parts name
WH
M
12
X3
3
CnD
10
OR
H
4
1
2
X4
CnR
9
1
2
CnI
FS
CnI
WH
J5
J6
J2
X5
X4
X3
X2
X1
J7
J3
X6
220/240V
CnW1
Parts name
Val
Fuse
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Spark killer
CnR
DM
F
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
SK
Mark
CFI
SK
CnF
11
CnF
FMI
(49FI)
2
L
13
X6
1
Y/GN 5 Y/GN
Printed circuit board
CnJ
LM
CnJ
3
X5
X1
WH
J4
SW5
SW6
1 2 3
CnB
CnS
CnN
CnH
CnT
CnA
GR
Mark
SW5-3
SW5-2
SW5-1
Color
Red
White
Yellow
Yellow/Green
Mark
Test run of condensate pump motor
Normal
OFF
Normal
ON
OFF
Run Stop
Reverse Invalid
Heating temp. shift + 3°C
Input
signal
Function
Remote
controller
RD WH BK
Thc
RD
WH
Y
Y/GN
Thl-R
SM
ON
OFF
ON
Option
Thl-A
X Y Z
BK
BK
BK
LS
XR4
BK
Color
Y
Z
X
BK
BK
CnS2
XR5
Black
Blue
Brown
Gray
Orange
BK
WH
RD
BK
BK
BK
GR
XR2
RD
Y
BK
XR3
OR
RD
Y
XR1
CnA2
OR
Function of switches
BK
BL
BR
GR
OR
Mark
Color mark
ON
OFF 1 2 3 4
ON
OFF
SW4
Check
SW1 SW2 SW3
Normal
LED·G LED·R
HA
CnZ
CnW2
BL
BL
RD
Checker
17V
8V
RD
CnE
Trl
Models All models
Mark
CnO
CnK2
2
1
(a) Ceiling recessed type (FDT)
FMI
49FI
CFI
DM
FS
LM
LS
SM
X1,2,3,6
X4
X5
Y/GN
CnK
WH
RD
(1) Indoor unit
Mark
Parts name
F(3.15A)RD
20.3.1 Electrical wiring
Meaning of marks
Outdoor
unit
(Signal
line)
Power
source
TB
L
WH
RD
OR
OR
WH
WH
BL
RD
BK
BK
BK
RD
BL
WH
WH
OR
BR
BR
BK
BK
WH
WH
GR
RD
RD
1022
WH
CnU
FDC-HKXR
20.3 ELECTRICAL DATA
FMI
49FI
CFI
DM
FS
LM
LS
SM
X1,2,3,6
X4
X5
Mark
BL
BL
Parts name
B
A
TB
Y/GN
WH
RD
F(3.15A)
Fan motor
Internal thermostat for FMI
Capacitor for FMI
Drain motor
Float switch (For overflow prevention)
Louver motor
Limit switch
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For DM)
Auxiliary relay (For LM)
Meaning of marks
Outdoor unit
(Signal line)
N
L
TB
Y/GN
Y/GN
ThI-A
ThI-R
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
Mark
Note (1)
RD
2
1
CnF2
UH
OR
M
OR
CnF2
L
WH
CFI2
CnFC2 OR
FMl2
H
Printed circuit board
1
UH
12
11
13
CnF1
L
X2
10
CnI1
CnFC1 OR
OR
CnF1
OR
M
14
X6
WH
FMl1
H
X3
X1
Thermistor
Thermistor
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Parts name
F
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
SK
Mark
4
CnD
CnR
Parts name
CnI
SK
CnR
FS DM
CnI
9
X4
Fuse
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Spark killer
1. FMI2 is equipped with only for 112,140.
CnO
CnK2
BL
CnK
BL
WH
RD
BK
Power
source
RD
RD
WH
WH
BL
WH
WH
GR
RD
RD
WH
WH
BR
BR
RD
RD
WH
WH
3
Val
CnJ
LM
CnJ
X5
OR
OR
WH
WH
CnU
J6
J2
LED·G
J7
J3
SW1
J8
J4
SW4
ON
OFF 1 2 3 4
SW6
SW5
SW3
Check
LED·R
HA
Mark
CnB
CnS
CnN
CnH
CnT
Mark
SW5-3
SW5-2
SW5-1
BK
WH
RD
RD
WH
Y
Y/GN
Mark
Remote
controller
WH
Thc
Test run of condensate pump motor
Normal
ON
Normal
Color
Red
White
Yellow
Yellow/Green
Option
Reverse Invalid
Run Stop
Heating temp. shift + 3°C
Input
signal
LS
Z Y X
BK
Function
Z
Y
X
TB
BK
BK
Thl-R
Thl-A
XR4
XR2
SM
OFF
OFF
ON
OFF
ON
BK
RD
XR5
XR3
XR1
28~56H CASES
CnS2
BK
BK
BK
BK
BK
BK
GR
BK
GR
WH
OR
RD
Y
WH
CnA2
OR
RD
Y
Function of switches
Color
Black
Blue
Brown
Gray
Orange
Color mark
BK
BL
BR
GR
OR
CnA
Checker
CnW2
BL
BL
RD
RD
ON
OFF 1 2 3 4
SW2
8V
17V
CNZ
CnE
Normal
X6
Trl
J6 has 71H ~ 90H
only shorted.
J5
J1
X5
X4
X3
X2
X1
CnW1
WH
220/240V
WH
FDC-HKXR
(b) 2-way outlet ceiling recessed type (FDTW)
Models All models
1023
*1
FMI1,2
49FI
CFI1,2
DM
FS
LM
LS
SM
X1,2,3
X4
X5
RD
L
H
RD
CnF2
OR
Y/GN
WH
CnW4
RD
8V
CnM
CnB2
RD
CnK2
BL
CnK
BL
CnW3
BL
BL
RD
CnW2
CnO
Y/GN
BL
BL
CnW4
BL
17V
BL
RD
RD
WH
WH
RD
RD
Trl
WH
WH
220/240V
RD
CnL
RD
2
1
*1
Val
RD
L
H
OR
X1
CnF3
X2
CnD
CFl2
UH
BR
OR
CnF3
FMl2
(49FI)
M
Parts name
ThI-A
ThI-R
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
Mark
Thermistor
Thermistor
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Parts name
(2) *1 FMI2 is equipped with only for FDTSJ71HKXE2B.
CFI1
UH
BR
OR
CnF2
FMI1
(49FI)
M
Fan motor
Internal thermostat for FMI
Capacitor for FMI
Drain motor
Float switch
Louver motor
Limit switch
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For DM)
Auxiliary relay (For LM)
Meaning of marks
Mark
BL
Y/GN
F(3.15A)
BR
RD
L
8
6
CnF2
CFI1
UH
BR
OR
OR
*2
X3
CnF2
Cn Cn
F6 F5
H
FMl1
(49FI)
M
7
X3
X2
X1
CnI
FS
SK
CnI
9
X5
X4
F
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
SK
Mark
Fuse
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Spark killer
Parts name
Notes (1) FDTSJ22HKXE2B is different from others as indicated with *2 in the diagram below.
B
BL
RD
RD
BL
BL
BL
BK
BK
Outdoor unit
(Signal line)
TB
A
N Y/GN
RD
Y/GN
Y/GN
WH
WH
Power
source
L
TB
BL
BL
RD
RD
RD
RD
Y/GN
BK
BK
BL
BL
BL
WH
WH
WH
WH
WH
Y/GN
Y/GN
BK
BR
BR
BK
BK
BK
GR
RD
RD
WH
BR
BR
X4
5
WH
CnR
SK
CnR
4
DM
RD
RD
WH
WH
WH
OR
OR
X5
CnJS
3
CnJS
LM
OR
WH
1024
WH
CnU
HA
CNZ
J5
J1
J6
J2
J7
J3
SW6
J4
ON 1 2 3 4
OFF
SW5
SW3 SW4
ON 1 2
3
OFF
SW2
BK
RD
WH
Mark
SW5-3
SW5-2
SW5-1
Color
Red
White
Yellow
Yellow/Green
Test run of condensate pump motor
Normal
OFF
Normal
ON
OFF
Run Stop
Reverse Invalid
Heating temp. shift + 3°C
Input
signal
ON
OFF
ON
Mark
Remote
controller
RD WH BK
Thc
X Y Z
Option
SM
RD
WH
Y
Y/GN
Y
Z
X
TB
LS
Thl-R
Thl-A
XR4
XR2
Function
CnB2
BK
RD
WH
BK
BK
BL
BK
RD
BL
CnJS
CnN2
BK
BK
CnH2
BK
XR5
BL
BK
BK
XR3
XR1
OR
RD
Y
BK
GR
CnA2
Color
Black
Blue
Brown
Gray
Orange
CnB
CnS
CnN
CnH
CnT
OR
RD
Y
BK
GR
Function of switches
BK
BL
BR
GR
OR
Mark
Color mark
SW1
Normal Check
LED·G LED·R
Checker
CnE
CnA
Printed circuit board
FDC-HKXR
(c) 1-way outlet ceiling recessed type (FDTS)
Models All models
BL
BL
WH
Y/GN
CnS
Y/GN
CnO
CnK2
BL
CnK
BL
WH
RD
2
X1
CnF4
X2
Val
8
L
Printed circuit board
1
OR
OR
WH
Y/GN
CnD
CFl1
UH
CnF4
CnF2
H
6
CnF4
FMI1
(49FI)
M
7
X3
L
BL
X3
X2
X1
CnF2
CnF5
H
OR
OR
CnF5
FMI2
(49FI)
M
BK
X4
Parts name
Fan motor
Capacitor for FMI
Drain motor
Float switch
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For DM)
Internal thermostat for FMI
Thermistor
Thermistor
Mark
FMI1,2
CFI1,2
DM
FS
SM
X1,2,3
X4
49FI
ThI-A
ThI-R
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
F
Mark
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Fuse
Parts name
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
SK
Mark
5
4
CnRI
CnI
FS
CnI
CnRI
Parts name
CnRI
CnR
DM SK
CnR
CnRI
9
X4
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Spark killer
CnF3
CFI2
UH
CnF5
*1
CnF3
Note (1) *1 FMI2 is equipped with only for FDRJ112HKXE2,140HKXE2.
B
A
TB
N
Meaning of marks
Outdoor
unit
(Signal line)
Power
source
F(3.15A)
BK
RD
Y/GN
Y/GN
BL
TB
L
BL
RD
RD
BL
BL
BK
BK
BK
RD
RD
BR
BR
WH
WH
RD
RD
BL
Y/GN
Y/GN
BL
RD
WH
WH
BL
BK
BK
BK
BR
BR
BR
WH
BR
BR
BK
RD
RD
BK
WH
WH
WH
GR
RD
RD
RD
RD
WH
RD
SW6
1 2 3
SW5
J5
J3
J6
J4
OR
RD
Y
BK
GR
Y
X
BK
Color
Black
Blue
Brown
Gray
Orange
Remote
controller
RD WH BK
Thc
X Y Z
CnA2
TB
BK
Mark
SW5-3
SW5-2
SW5-1
Test run of condensate pump motor
Normal
OFF
Normal
ON
OFF
Run Stop
Reverse Invalid
Color
Red
White
Yellow
Yellow/Green
Heating temp. shift + 3°C
Input
signal
Function
Mark
RD
WH
Y
Y/GN
SM
ThI-R
ON
OFF
ON
Option
ThI-A
XR4
XR2
Function of switches
Mark
BK
BL
BR
GR
OR
BK
BK
CnN3
BK
BK
CnN2
Z
XR3
XR1
XR5
CnH2
CnB
BK
WH
RD
OR
RD
Y
BK
GR
RD
RD
BK
BK
Color mark
J7
ON 1 2 3 4
OFF
ON
OFF
CnN
SW3 SW4
Check
Normal
SW2
LED·R
LED·G
SW1
HA
CnZ
CnH
CnW2
BL
17V
BL
RD
8V
Checker
TrI
CnE
CnW1
WH
200/240V
WH
CnT
CnA
CnU
FDC-HKXR
(d) Cassetteria type (FDR)
Models All models
1025
Mark
Parts name
Fan motor
Capacitor for FMI
Drain motor
Float switch (For overflow prevention)
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For DM)
Internal thermostat for FMI
Thermistor
Thermistor
Meaning of marks
FMI1,2
CFI1,2
DM
FS
SM
X1,2,3
X4
49FI
ThI-A
ThI-R
Y/GN
BL
CnM
CnO
CnK2
BL
CnK
BL
B
N
TB
A BL
RD
WH
Y/GN
F(3.15A)
WH
TB
L RD
2
1
X1
CnF4
X2
Val
L
8
BL
H
Y/GN
WH
CnF4
OR
OR
CFI1
UH
Mark
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED R
LED G
F
Parts name
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Fuse
X1
X2
L
BL
M
BK
CnF2
Mark
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
SK
X3
H
X4
OR
OR
CnF5
FMI2
(49FI)
CnF5
CnD
CnF4
CnF2
6
FMI1
(49FI)
M
7
X3
Printed circuit board
RD
Note (1) 1 FMI2 is equipped with only for FDUMJ112HKXE2, 140HKXE2.
Outdoor
unit
(Signal line)
Power
source
BL
RD
WH
BK
BK
BK
BR
BR
BK
RD
RD
RD
Y/GN
Y/GN
WH
RD
RD
BL
BL
BL
Y/GN
WH
WH
WH
Y/GN
BL
BL
BK
BK
BK
BR
BR
BR
CnF3
CFI2
UH
CnF5
*1
CnF3
4
SK
Parts name
5
CnG
CnRI
CnR
DM
CnR
CnRI
X4
9
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Spark killer
WH
BR
BR
BK
RD
RD
BK
WH WH
WH
GR
RD
RD
RD
RD
1026
WH
CnU
CnRI
CnI
FS
CnI
CnRI
Check
Normal
J5
J3
J6
J4
SW6
ON
OFF 1 2 3 4
SW5
ON
OFF 1 2 3
CnN
CnA
BK
Z
Y
CnB
BK
X
TB
WH
RD
OR
RD
Y
BK
GR
Mark
BK
BK
OR
RD
Y
BK
GR
Black
Blue
Brown
Gray
Orange
Color
Remote
controller
RD WH BK
Thc
X Y Z
CnA3
OR
RD
Y
BK
GR
SW5-3
SW5-2
SW5-1
Mark
Color
Red
White
Yellow
Yellow/Green
Mark
RD
WH
Y
Y/GN
Test run of condensate pump motor
Normal
OFF
Normal
ON
OFF
Run Stop
Reverse Invalid
Heating temp. shift + 3
Input
signal
Function
SM
Thl-R
Thl-A
Option
ON
OFF
ON
Function of switches
BK
BL
BR
GR
OR
BK
BK
BK
BK
CnH2
CnN2 CnN3
RD/BK
RD/BK
CnA2
RD
RD
BK
XR1
XR2
XR3
XR4
XR5
Color mark
J7
CnT
CnH
SW1 SW2 SW3 SW4
LED·R
HA
LED·G
CnZ
Checker
CnE
BL
17V
8V
RD
CnW2
Trl
CnW1
WH
220/240V
WH
FDC-HKXR
(e) Satellite ducted type (FDUM)
Models All models
B
A
TB
Mark
FMI1,2
CFI1,2
49FI
LM
LS
SM
X1,2,3
X5
ThI-A
ThI-R
WH
RD
WH
Y/GN
RD
BL
BL
CnM
BL
BL
RD
RD
CnO
CnK2
BL
CnK
BL
CnW3
Y/GN
CnK2
CnW4
BL
17V
BL
CnW2
RD
WH
RD
2
1
VaI
*1
L
X3
X2
X1
OR
OR
H60
CnF3
FMI2
(49FI)
M
X5
X4
BR
Y/GN
CnD
CFI2
H50
CnF3
X2
X1
L
8
H
6
OR
OR
CnF2
FMI1
(49FI)
M
Cn
F6
7
X3
CFI1
UH
CnF2
Cn
F5
Fan motor
Capacitor for FMI
Internal thermostat for FMI
Louver motor
Limit switch
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For LM)
Thermistor
Thermistor
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
F
Mark
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Fuse
Parts name
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
SK
Mark
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Spark killer
Parts name
Note (1) *1 FMI2 is equipped with only for FDEJ71HKXE2B,112HKXE2B,140HKXE2B.
Parts name
BL
BL
CnW4
WH
200/240V
8V
RD
WH
CnL
Tr1 RD
RD
Y/GN
RD
WH
Meaning of marks
Outdoor unit
(Signal line)
N
F(3.15A)
RD
RD
BL
L
BK
TB
RD
RD
Power
source
BK
BK
WH
WH
RD
Y/GN
Y/
GN
WH
WH
BL
BL
BK
BR
BR
SK
OR
OR
X5
CnJS
3
5
CnJS
LM
OR
WH
WH
WH
WH
RD
J5
J1
Mark
J4
Color
Black
Blue
Brown
Gray
Orange
J7
J3
Mark
SW5-3
SW5-2
SW5-1
Mark
CnB2
BK
RD
WH
Y
Y/GN
BK
WH
RD
RD
WH
BK
BL
Test run of condensate pump motor
Normal
OFF
Normal
Remote
controller
ON
OFF
Run Stop
X Y Z
RD WH BK
Thc
Color
Red
White
Yellow
Yellow/Green
Reverse Invalid
Z
Y
X
TB
SM
LS
ThI-R
ThI-A
XR4
XR2
Heating temp. shift + 3°C
Input
signal
BK
BK
CnN2
BK
CnH2
BK
XR5
XR3
XR1
GR
CnS CnS2
BL
RD
RD
BK
BK
GR
ON
OFF
ON
Y
Y
BK
RD
BK
OR
RD
OR
Function
CnB
CnN
CnH
CnT
Function of switches
BK
BL
BR
GR
OR
J6
J2
SW6
ON
OFF 1 2 3 4
ON
OFF 1 2 3
SW5
SW1 SW2 SW3 SW4
Normal Check
LED·G LED·R
HA
CnZ
Color mark
9
Checker
CnE
CnA
Printed circuit board
Option
CnU
FDC-HKXR
(f) Ceiling suspension type (FDE)
Models All models
1027
FMI
CFI
49FI
LM
LS
SM
X1,2,3
X5
ThI-A
ThI-R
Y/GN
BL
BL
Y/GN
CnF1
Parts name
H
WH
OR
OR
CnF1
CnF2
M
BL
BL
FMI1
(49FI)
L
BK
BK
*1
RD
RD
Y/GN
WH
WH
Fan motor
Capacitor for FMI
Internal thermostat for FMI
Louver motor
Limit switch
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Auxiliary relay (For LM)
Thermistor
Thermistor
Meaning of marks
Mark
B
TB
A
WH
F(3.15A)
Y/GN
CnO
CnK2
BL
CnK
BL
WH
RD
VaI
CnF1
Y/GN
X2
X1
Printed circuit board
2
1
7
OR
OR
5
H
OR
OR
CnF1
6
CnF2
M
CnF1
FMI
(49FI)
L
8
X3
CFI
X3
X2
X1
CnD
X5
GR
9
LM
CnJ
CnJ
3
X5
CFI
SW1
SW2
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
F
Mark
Indoor unit address ten's place
Indoor unit address unit's place
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Fuse
Parts name
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
Mark
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
Parts name
Note (1) FDKJ22HKXE2 is different from others as indicated with *1 in the diagram below.
Outdoor unit
(Signal line)
N
RD
RD
RD
Power
source
WH
BL
BL
TB
L
BK
BK
RD
WH
WH
WH
OR
OR
WH
WH
1028
J5
Normal
Check
LED·R
HA
CnZ
LED·G
J3
J6
J4
J7
SW6
1 2 3 4
CnB
CnN
CnH
CnT
OR
Z
Y
Mark
SW5-3
SW5-2
SW5-1
Color
Red
White
Yellow
Yellow/Green
Test run of condensate pump motor
Normal
OFF
Normal
ON
OFF
Run Stop
Reverse Invalid
Heating temp. shift + 3°C
Input
signal
ON
OFF
ON
Mark
RD
WH
Y
Y/GN
Function
Remote
controller
RD WH BK
Thc
Color
Black
Blue
Gray
Orange
BK
WH
SM
LS
ThI-R
ThI-A
XR4
XR2
X Y Z
BK
BL
TB
RD
X
BK
CnS2
BL
BK
CnN2
BK
XR5
XR3
XR1
CnS
RD
RD
BK
BK
GR
BK
Y
RD
Function of switches
BK
BL
GR
OR
Mark
Color mark
ON
OFF
ON 1 2 3
OFF
SW5
CnA
CnW2
BL
BL
RD
RD
Checker
17V
8V
CnE
TrI
SW1 SW2 SW3 SW4
CnW1
WH
220/
240V
WH
Option
CnU
FDC-HKXR
(g) Wall mounted type (FDK)
Models All models
Parts name
Fan motor
Capacitor for FMI
Internal thermostat for FMI
Stepping motor (For Exp.v)
Auxiliary relay (For FMI)
Thermistor
Thermistor
Indoor unit address ten's place
Indoor unit address unit's place
Mark
FMI
CFI
49FI
SM
X1,2,3
ThI-A
ThI-R
SW1
SW2
B
TB
A
BL
BL
Y/GN
WH
SW3
SW4
SW6
Trl
Val
LED·R
LED·G
F
Mark
Y/GN
Val
Parts name
2
1
X1
CnS
X2
Y/GN
Outdoor unit address ten's place
Outdoor unit address unit's place
Change of heat pume type
Transformer
Varistor
Indication lamp (Red)
Indication lamp (Green)
Fuse
CnK2
BL
CnK
BL
WH
RD
Y/GN
L
8
WH
BK
BK
CnF
H
6
CnA-Z
TB
mark
mark
XR1
XR2
XR3
XR4
XR5
Mark
CnD
CnF
FMI
(49FI)
M
7
X3
5
9
Parts name
J5
Connector ( mark)
Terminal block
Terminal (F)
Connector
Operation indication (DC12)
Heating indication (DC12)
ON indication for CM (DC12)
Check indication (DC12)
Distant operation
WH
CFI
X3
X2
X1
Trl
J3
J6
J4
J7
SW6
1 2 3 4
SW5
1 2 3
CnB
CnN
CnH
CnT
CnA
Mark
RD
RD
BK
BK
Black
Blue
Gray
Orange
XR4
Z
Y
X
TB
Mark
SW5-3
SW5-2
SW5-1
X Y Z
Color
Red
White
Yellow
Yellow/Green
Mark
RD
WH
Y
Y/GN
Remote
controller
RD WH BK
Thc
Test run of condensate pump motor
Normal
OFF
Normal
ON
OFF
Run Stop
Reverse Invalid
Heating temp. shift + 3°C
Input
signal
ON
OFF
ON
SM
Function
Thl-R
Thl-A
Color
BK
WH
RD
BK
CnN
BK
BK
CnH2
BK
XR5
XR3
XR2
GR
XR1
Y
BK
GR
BK
Function of switches
BK
BL
GR
OR
OR
Y
RD
CnA2
RD
OR
Color mark
Printed circuit board
ON
OFF
ON
OFF
SW1 SW2 SW3 SW4
Check
Normal
HA
Checker
CnW2
17V
8V
LED·R
BL
BL
RD
RD
LED·G
CnZ
CnE
CnW1
WH
220/
240V
WH
Models All models
Meaning of marks
Outdoor
unit
(Signal line)
N
RD
RD/Y
RD
Power
source
F (3.15)
BL
BL
BL
RD
RD
BK
BK
BK
TB
L
GR
WH
WH
Option
RD
FDC-HKXR
(h) Floor standing exposed type (FDFL)
(i) Floor standing hidden type (FDFU)
1029
FDC-HKXR
(2) Individual flow divide controller
Power source
(between indoor unit)
Power source
1 phase 220/240V 50Hz
Notes (1) This illustration shows the circuit diagram for when 1 indoor
unit is connected with a central flow divide controller and relay
kit (flow divide controller accessory).
(2) “.......” denotes the local wiring.
(3) The option shows when a remote start/stop and monitoring kit is
connected.
• Meaning of marks
SVH
High-pressure gas solenoid valve
SVC
Low-pressure gas solenoid valve
SVL
Liquid solenoid valve
SVG
Bypass solenoid valve
XR, X1, XR1 Operation output
XH, X2, XR2 Heat output
1030
XR3
Thermal ON output
XR4
Inspection output
CM
FM1,2
IM
52C
49F1,2
CH
CF1,2
X1
X2
X3
X4
X7
X8~10
X11
X12
X13
X14
X20
20SS
Mark
Parts name
Compressor motor
Fan motor (outdoor unit)
Motor for cooling inverter
Magnetic contactor for CM
Internal thermostat for FMo
Crankcase heater
Capacitor for FMo
Auxiliary relay (for 52C)
Auxiliary relay (for 20SS)
Auxiliary relay (for 20SL)
Auxiliary relay (for SV1)
Auxiliary relay (for 20VF, 20VU)
Auxiliary relay (for FMo1)
Auxiliary relay (for FMo2)
Auxiliary relay (for SVS)
Auxiliary relay (for SVL)
Auxiliary relay (for SV2)
Auxiliary relay (for SV3)
4way valve (front heat exchanger)
Meaning of marks
Notes (1) “.......” denotes the local wiring.
(2)
and
of TB2 are the signal
wire terminal blocks (5V).
20SL
20VF
20VU
SV1
SV2
SV3
SVS
SVL
63H1
63H2
63H3
63H4
63L
Tho-A
Tho-C
Tho-D
Tho-R
CT1,2
NR
Mark
4way valve (rear heat exchanger)
Solenoid valve (full)
Solenoid valve (partial)
Solenoid valve (compressor cooling)
Solenoid valve (excessive cooling heat exchanger by-pass)
Solenoid valve (discharge gas by-pass)
Solenoid valve (for front heat exchanger stoppage)
SOlenoid valve (rear heat exchanger stoppage)
High Pressure switch (for protection)
High Pressure switch (for control)
High Pressure switch (high pressure control)
High Pressure switch (high pressure control)
Low Pressure switch (low pressure control)
Thermistor (outdoor air temp)
Thermistor (dome temp)
Thermistor (discharge temp)
Thermistor (outdoor H.X. temp)
Current sensor
Noise killer
Parts name
SK
SA
Tr
Va1,2,3,4
TB1,2
F
CnA~Y
SW1
SW2
SW3-1
SW3-2
SW3-3
LED1
LED2
LED3-5
LD1
LD2-4
Mark
Parts name
Spark killer
Arrestor
Transformer
Varistor
Terminal block
Fuse
Connector ( mark)
Unit No.10 rank of outdoor unit
Unit No.1 rank of outdoor unit
L.E.D. reset
Defrost change
Prevention of snow accumulation
Indication lamp (red)
Indication lamp (Green)
Indication lamp (Yellow)
Indication lamp (Green)
Indication lamp (red)
(3) Use 0.75 to 2mm2 × 2 core wire for the indoor and
outdoor connection signal wire.
(4) The signal wiring shall be separate from the powe
supply wiring.
Power source
3 Phase 380/415V 50Hz (415/200V, 380/200V)
Color
Black
Blue
Brown
Green
Gray
SW3-7
SW3-6
SW3-5
SW3-4
Mark
Test mode
Regular operation
OFF
Regular operation
ON
Compulsory operation
OFF
Heating trial operation
ON
Cooling trial operation
OFF
Regular operation
OFF
ON
Trial operation
Function
Color
Orange
Red
White
Yellow
Yellow/green
Mark
OR
RD
WH
Y
Y/GN
ON
Function of switches
BK
BL
BR
GN
GR
Mark
Color mark
FDC-HKXR
(3) Outdoor unit
Models FDCP2001HKXRE2, 2501HKXRE2
1031
FDC-HKXR
20.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Remote controller (Optional parts)
FDR,FDUM,FDFL and FDFU series are not provided with AUTO SWING switch.
Panel shown below will appear if you open the cover. All contents of display on the LCD are indicated simultaneously for
the purpose of explanation.
Pull the knob on the cover to this side to open it downward.
Filter sign
Operation mode display
When this sign is indicated, clean the filter.
Displays the operation mode that
has been selected.
Remote display
Heating
preparation display
This is displayed when the unit is controlled
with an individual controller during normal operation.
(Also displayed when the air conditioner is stopped.)
Operation/
Inspection indicator lamp
During operation: Green lamp flashes.
In case of error: Red lamp flashes.
Central display
This is displayed when the unit is
controlled with the optional central console.
On/Off switch
Timer operation display
Contents of timer operation are displayed.
(Also displayed when the air conditioner
is stopped.)
CENTER REMOTE F I L T E R AUTODRYCOOLFANHOT
PROGRAM TIMER
FILTER AUTO LIFT
ON
Setting
temperature display
SET TEMP
Outdoor No.
Return air
temperature display
Displays the temperature
that has been set.
FILTER
RESET
TIMER
CHECK
SET
TEMP
T I M E
Fan speed display
Displays the fan speed that has been set.
FAN
Hi
Mi
Lo
OFF
A M
P M
KEEP
Use this switch to start or stop the
air conditioner. First push on the
switch starts the unit and second
push stops it. (The switch can be
operated without opening the cover.)
Filter reset switch
Use this switch to reset (erase) the filter
sign display.
(Press the switch after cleaning the air filter.)
F A N
SPEED
AUTO
SWING
Displays the return air temperature.
MODE
Note
Indicated value may be different
from actual reading on a thermometer
or other instrument but this is
notnecessarily an error.
Auto swing display
Indicates the swing louver condition.
Mode switch
Cover
Inspection switch
Use this switch when servicing the unit.
Timer switch
Use this switch to select operation
modes.
Fan speed switch
Use this switch to set a fan speed.
Auto swing switch
Use this switch when selecting contents of timer operation.
Use this switch to operate or stop
the swing louver.
Set switch
Temperature/
Time setting switch
Use this switch to set a time for the timer.
Use this switch to set the room
temperature or time on the timer.
1032
FDC-HKXR
(2) Automatic Operation
Once the [Auto] mode is selected by remote control, the operating mode is automatically selected according to the setting temperature
and the intake air temperature of the indoor unit and cooling or heating operation is performed. The determination is performed
when the thermostat has been in the OFF mode for 10 minutes or more continuously.
Notes (1) No determination is made if the mode setting is cooling, dehumidify or heating
and the cooling and heating thermostats have been in the off mode for 10 minutes
in the automatic operation mode.
(2) If set to automatic operation mode when the intake temperature is within ± 2 ˚C in
relation to the setting temperature, the same operation as the previous automatic
+2
operation will be performed. (Note that it will be the heating mode when first
Room temperature setting
turned on after the power has been turned off.)
Cooling operation
Heating operation
-2
Room temperature (detected atThI-A) (deg.)
(3) Operations of major functional items under each operation mode
Operation mode
Cooling
Heating
fan
Dehumidify
Functional item
Thermostat ON Thermostat OFF
Thermostat ON Thermostat OFF
Defrost
Indoor unit fan
Remote controller Remote controller Remote controller Remote controller Intermittent
operation
command
command
command
command
→
/
Indoor unit electronic
expansion valve
According to determined frequency Fully closed
Fully closed
Fully open
According to determined frequency
/
Compressor
According to determined frequency
Fully closed
Outdoor unit fan
→
/
Drain motor
Solenoid valve (20VU)
/
/
/
Solenoid valve (20 VF)
/
/
/
Four-way valve (20 SL,S)
Individual definitions
Solenoid valve (SV1, L,S)
Individual definitions
Notes(1) : ON,: OFF, /: ON or OFF
(2) Cooling and heating also include auto mode.
(3) Off if jumper wire (J3) is short circulated (factory setting) and open.
(4) Cooling operation
(a) Cooling
1) If the sum of selected and required frequencies is not larger than the maximum frequency, the required frequencies listed in the
following table apply. If the sum of required frequencies is larger than the maximum frequency, the required frequencies divided
proportionally apply.
Frequency bands for indoor unit models
Model (Indoor)
Category
All series
22 model 28 model 36 model 45 model 56 model 71 model 90 model 112 model 140 model
Required frequency (Hz)
10 ~ 15
10 ~ 20
10 ~ 25
10 ~ 25
15 ~ 30
15 ~ 40
15 ~ 50
35 ~ 60
35 ~ 70
Selected frequency (Hz)
5 ~ 15
5 ~ 20
5 ~ 25
5~ 25
5 ~ 30
5 ~ 40
5 ~ 50
5 ~ 60
5 ~ 70
Notes (1) Frequency during cooling is 45 Hz.
(2) The required frequency is counted in the unit of 5 Hz and the selected frequency in the unit of 1 Hz.
2) This indoor unit electronic expansion valve (EEV) controls opening of each indoor unit corresponding to decision frequency.
Also, the thermostat is sampled in pitch of 20 second.
(b) Cooling thermostat off
(i) When all thermostata of indoor unit in a module are turned off, the indoor units operate in the cooling thermostat off
mode per outdoor unit module.
(ii) When the decision frequency to indoor units is less than 5Hz, or when the demand frequency reaches to the OFF area
according to fuzzy operation, the ndoor units will select the cooling thermostat of mode.
1033
FDC-HKXR
(5)
Dehumidifying (Thermal dry)
D
C
Low -2
B
A
+2
▲
High
Room temperature
setting point
• Indoor unit fan will be operated in
D block as shown below.
20 sec.
Lo
OFF
4 min.
Temperature check
(6)
22 model
28 model
36 model
45 model
56 model
71 model
90 model
112 model
140 model
Compressor
Indoor unit electronic expansion valve
Indoor unit fan
Outdoor unit fan
Indoor unit frequency (Hz)
Operation block
• This cooling operation is mainly for dehumidifying, with which the compressor, indoor and outdoor fans are operated in the patterns as listed
in the following table and in accordance with operation blocks switched with the room temperature sensor. The operation blocks are selected
by checking the return air temperature at 4-minute intervals. Respective functional items are operated in each operation block as shown by the
following table.
Operation block
A
B
C
D
Item
10
15
20
20
25
30
40
50
60
10
10
0
10
10
0
15
10
0
15
10
0
15
15
0
20
15
0
25
15
0
40
35
0
45
35
0
Sum of frequencies on combined indoor units
Frequency adaptation
Me
Lo
Lo
Lo↔OFF
Operationt
Operationt
Operationt
Stop
Temperature check
Heating operation
(a) Heating
• This is same as the cooling operation.
(b) Heating operation with thermostat OFF
1) Intermittent fan operation control
a) When the jumper wire J3 on the indoor PCB is shorted (installed at shipping),the fan of the unit of which the thermostat is
turned OFF during heating is operated in the Lo mode, and the indoor fan is turned OFF if the temperature rises 1˚C or more
than the return air temperature at the thermostat OFF.
b) Indoor fan OFF condition is maintained for 5 minutes and then the operation is reset at the Lo mode again. After operating
for 2 minutes in the Lo mode, return air temperature is checked and, if it is 1˚C or higher, the indoor fan is turned OFF or, if
it is not higher than 1˚C, the Lo mode operation continues.
Notes (1) If the heating thermostat has been turned OFF, the temperature is indicated on the remote controller only when the indoor fan is operated in the Lo
mode. When it is OFF, the room temperature at the end of Lo operation is indicated.
(2) If the operation is changed to the defrosting mode while the heating thermostat is at OFF or the thermostat is turned OFF during defrosting, the indoor
fan is turned OFF.
(3) Residual operation of heater is dominant over this control.
2) Fan stop control
a) If the jumper wire J3 on the indoor PCB (installed at shipment) is opened or the thermostat is turned OFF during heating
operation with the remote control sensor operating, the fan on the indoor unit is turned OFF.
(c) Hot start (Prevention of cold draft during heating)
If the required frequency in the room is other than 0 Hz at the start of heating operation, the indoor fan is controlled in
accordance with the temperature of indoor air heat exchanger (detected with ThI-R).
(Setting blow rate)
Stop
Indoor air heat exchanger temperature (˚C)
1034
Notes(1) When the hot start (the compressor is operating and the indoor unit fan is not operating at the setting
blow rate) is going on, the heating preparation is displayed (LCD on the remote controller).
(2) When the required frequency is other than 0 Hz, once the blower should start, it will not stop even
if the temperature drops below 20˚C.
(3) After the blower has been turned OFF for 7 minutes, the blower is operated regardless of the heat
exchanger temperature. (For 7 minutes after completion of defrosting during defrosting operation)
FDC-HKXR
(7) Value shift adjustment of room air temperature detection in heating
Under the standard specifications, the room temperature is adjusted at the setting temperature by controlling the indoor unit
capacity based on the setting temperature of thermostat and the suction air temperature.
However, where the unit is installed in the ceiling and warm air tends to stay around the ceiling, temperature in the living space may
not be adjusted at the setting temperature. In such occasion, it is recommended to change the setting of dip switch SW5-2, which is
found on the PCB of the indoor unit, to ON position so that the capacity control is tripped at +3 above the setting temperature of
thermostat and thus the heating feeling will improve.
High
Heating
capacity
-1
High
Heating
capacity
Low
+1
Low
Heating
capacity
Thermostat setting temperature
+2
+4
Heating
capacity
Thermostat setting temperature
Standard
With SW5-2 "ON"
Note (1) Refer to page 911 for position of SW
(8) Auto Swing Control (Excepted FDR, FDUM, FDFL, FDFU models)
(a) Have a louver motor to move the louvers up and down for the so called “AUTO SWING” function.
(b) The louver auto swing starts when the AUTO SWING switch is pressed once and stops when the AUTO SWING switch is
pressed again. The louver position is displayed on the LCD on the remote controller. During auto swing, the
position displayed on the LDC changes, but the positions of the louvers and the display are not coordinated. (The louvers
swing3-4 times per minute but the display changes once per second.)
(c) Stopping the louvers
When the AUTO SWING switch is pressed to stop the louver movement, the LCD louver-position display stops and the louvers
stop when they come to the position displayed on the LCD. There are four louver stop position on the LCD. (When jumper wire
J2 on the indoor unit printed circuit borad is cut, the louvers stop immediately at the AUTO SWING switch is pressed to stop
them and the LCD display changes to show this posiition. Refer to page 180 for position of jumper wire J2.
(d) Movement of louver when the power supply to the controller controlling 4 positions of the louver is switched on.
When power supply is switched on, the louver will automatically swing about 2 times (without operating remote controller).
This is an action for the microcomputer to confirm the louver position in order to input the cycle of the luver motor (LM) to the
microcomputer with the limit switch (LS) pushing the louver motor (LM). If the LS action is not input to the microcomputer, the
louver will stop within 1 minute after the power supply is switched on and will not move from then on.
(e) Keeping the louvers horizontal during heating
While HOT KEEP is displayed (during hot start operation or when the thermostat has turned off during heating operation),
the louvers stay in the horizontal position to prevent cold drafts, independent of the setting of the AUTO SWING switch (auto
swing or stop). The louver position display of LCD displays continuously the original position before this control operation.
When the HOT KEEP display goes out, both the louver and the LCD display return to their previous positions. (However,
after the power supply to the unit is switched on, the louvers swing two times as a check of the power source frequency,
regardless of the setting of the ON/OFF or AUTO SWING switches.)
(9) FILTER sign
When the operation time (time when the ON/OFF switch is turned to ON) is counted up at 600 hours (1), the filter sign on the remote
controller flickers.
This condition can be reset any time with the “Filter reset” switch. It is effective also to turn power OFF to reset.
Note (1) The function is invalidated if the jumper wire (J4) is opened. (See page 911 for the location of PCB.)
1035
FDC-HKXR
(10) Condensate pump motor (DM) control (Only FDT, FDTW, FDTS, FDR, FDUM models)
(a) Drain motor is started no sooner than the compressor is turned ON during cooling or dehumidifying operation. The drain motor
continues to operate for 2 minutes after the stop of unit operation, stop with the error stop, thermostat stop and at switching
from cooling or dehumidifying operation to blowing or heating operation. When there is any unit subjected to oil return
control, the drain motor is operated for 3 minutes at such occasion.
Note (1) Drain motor may be operated forcibly by turning ON the dip switch SW5-3 on the PCB. Turn the switch OFF to stop the drain motor.
(b) Overflow detection is always operable by means of the float switch regardless of operation modes. If the overflow is detected
(or when the float switch is disconnected or its wire is broken), operation is stopped with the error stopped. (FDT, FDTW,
FDTS, FDR and FDUM) If the overflow is detected while the drain motor is stopped, the drain motor is operated for 3 minutes
and then the overflow detection is performed to judge whether it is normal or not.
Indoor unit operation mode
OFF
(1)
COOL
DRY
During compressor ON
FAN
(2)
HEAT
Control A
During compressor OFF
Notes (1) Including OFF and error stop during
COOL, DRY, FAN and HEAT.
(2) Including “FAN” operation due to unmatch
of operation mode.
Control B
• Flow chart of drain motor operation
Float switch operation (Contactor : Open)
Control B
Operation mode?
Control A
*1
NO
Drain motor ON
Error stop E9
Drain motor ON
3 minutes
after float operation?
Compressor OFF
YES
3 minutes
after float operation?
Drain motor OFF
NO
10 seconds after
drain motor OFF?
YES
Reset
Operation
Reset
Drain motor OFF
Error stop E9 continues
Float SW?
Operation
End
Float SW?
Float operation?
Error stop E9
Drain motor 3-minute ON
Drain motor ON continues
* 1 In the flow in the frame of broken line, operations of operation mode change and thermostat reset are effective and operated immediately upon selection. However,
the compressor ON command is not transmitted.
(i) Control A
a) If the float switch detects the draining, operation is stopped with the error stop (E9 is displayed) and operate the drain pump.
b) Float switch is checked 3 minutes later on the unit stopped by the error and, if the error persists still, the drain motor is left
at ON but, if the error has already been reset, the drain motor is turned OFF. E9 is displayed till the error is reset.
(ii) Control B
a) If the float switch detects the draining, the expansion valve is closed, the drain motor is turned ON for 3 minutes and, as 10
seconds elapses after the drain motor OFF, the float switch is checked. If the result is normal, the operation stops in the
normal way while, if it is not normal, E9 is displayed, the drain motor is turned ON and the operation stops with the error
stop with the expansion valve being closed completely. (It is left at ON while the draining is detected.)
1036
FDC-HKXR
(11) Defrosting
(a) Conditions for starting defrosting
When all the following conditions are met, the defrosting operation will start:
-2°C
Outdoor unit heat exchanger temp.
(ThO-R)
1) The cumulative operating time of the compressor
comes up to 45 minutes after completion of a
defrosting operation, or it comes up to 30 minutes
after a heating operation starts (the remote controller
is turned on).
2) Five minutes has passed after the compressor was
turned off and on.
3) Five minutes has passed after end of outdoor unit
fan motor control.
4) After all the above conditions have been met, the
temperature of the heat exchanger sensor (ThO-R)
has been below the defrosting start temperature
for three minutes in succession.
)
-2
-5°C
-10°C
In i
-15°C
Ini
ti a
ti a
t
t
io n
n
ti o
em
te m
p.
p
f
.o
o
de
ef
fd
fro
ros
s
g
tin
tin
g
a
(C
a
(S t
se
nd
of
ard
ON
3
SW
)
Zone for initiate temp. of defrost
-20°C
-20°C
-15°C
-10°C
-5°C
0°C
5°C
10°C
Outdoor air temperature (ThO-A)
(b) Operation of functional components in defrosting
Defrosting
Finishing of
defrosting, Finishing of
start defrosting defrosting
Heating
Defrosting start
1 min.
Frequency
95Hz
1 min.
Designated Hz
0
65Hz
4 min.
65Hz
0
1'45"
1'45"
Outdoor unit fan ON
or
OFF
ON
or
OFF
5 sec.
4-way valve
(20SL,SS)
Solenoid valve
(SVL,SVS)
[Indoor unit electronic
expansion valve (EEV)]
Heating unit
(include, pause)
COOL, DRY unit
(include, pause)
Target Hz
5 sec.
ON
ON
ON
or
OFF
ON
or
OFF
Full open
to Hz
<Pause, stop>
(Open of about 7%)
to Hz
<Pause, stop>
(Open of about
7%)
to Hz
ON
or
OFF
Full open
Closed
<Pause, 0>
to Hz
<Pause, Closed>
Full open
FAN unit,
Stop unit and COOL, DRY unit
Output of heating
Closed, 0
Closed
ON
or
OFF
ON
or
OFF
Heating
Defrosting operation
Heating
(c) Conditions for finishing Defrosting
When any of the following conditions is met, the defrosting finishing operation will start.
1) When the temperature of the heat exchanger sensor (ThO-R) increases adove 20°C
2) When 12 minutes has passed after start of defrosting.
1037
FDC-HKXR
(12) Multiple Units Control-Simultaneous Control of 16 unit with one remote controller
(a) Function
Multiple units (even of outdoor different systems, 16 units maximum) can be simultaneously controlled by using a remote
control switch (a special order item). The remote control switch is used to set the “operation mode”, and all the unit can be
operated and stopped at intervals of 0.5 to 1 second in the order of unit number. Thermostat and protective functions of each
unit functions independently.
Note(1) When part of the group gets out of order (the protective device operates), the relevant unit comes to an abnormal stop, but other normal units keep operating.
(b) Wiring Procedures
(i) Lay power cable of each unit and signal wire as usual. (Remove the remote control switches from all units excluding only one unit.)
Lay wiring for the remote controller separately from power cable and wires for all other electrical equipment.
(ii) Arrange the terminal block (X, Y, Z) of the remote controller as shown next page for the simultaneous control, and lay
cross over in each indoor unit.
Signal (1)
wire
Outdoor
unit
Signal wire
Indoor
unit
No.1
Indoor
unit
No.2
Outdoor
unit
(1)
Indoor
unit
No.3
Indoor
unit
No.16
(2)
(2)
Remote control
signal wire
Remote control
signal wire
Notes (1) The overall length of the signal wire shall be less than 1000m.
(2) The length of remote control signal wire and crossover for remote controller between room shall be less than 600m.
(13) External control (remote display)/control of input signal
(a) External control (remote display) output
Following output connectors (CNT) are provided on the control circuit board of indoor unit.
(i)
Operation output: Power to engage DC 12V relay (provided by the customer) is outputted during operation.
(ii) Heating output: Power to engage DC 12V relay (provided by the customer) is outputted during the heating operation.
(iii) Compressor ON output: Power to engage DC 12V relay (provided by the customer) is outputted while the compressor is
operating.
(iv) Error output: When any error occurs, the power to engage DC 12V relay (provided by the customer) is outputted.
(b) Control of input signal
(Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote control
unit.) Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the
indoor unit. However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
(i) At shipping from factory (SW5-1 on PCB OFF)
1) Input signal to CnT OFF → ON [Edge input] Air conditioner ON
2) Input signal to CnT ON → OFF [Edge input] Air conditioner OFF
ON
ON
CnT Input
OFF
A Unit
OFF
B Unit
ON
ON
ON
OFF
OFF
ON
ON
OFF
1038
OFF
OFF
OFF
FDC-HKXR
(ii) When SW5-1 on the PCB of indoor unit is turned on at the field.
Input signal to CnT becomes valid at OFF → ON only and the motion of air conditioner [ON/OFF] is inverted.
ON
CnT Input
OFF
A Unit
OFF
ON
OFF
OFF
ON
OFF
OFF
B Unit
ON
OFF
(14) Snow Fan Control
Set the dip switch SW3-3 (See page 1075) on the outdoor unit control circuit board to ON, and the outdoor fan of a standing unit
is operated at the Hi speed for 10 seconds every 10 minutes when the outdoor air temperature drops below 3°C.
ON
OFF
5°C
3°C
(Outdoor air temperature)
(15) Control of Coompressor Capacity
Notes (1) Full load operation frequency:
35Hz~95Hz(every 5Hz)
(2) Hot gas bypass operation frequency:
35Hz~45Hz(every 5Hz)
(3) The change-over occurs when 5 minutes of more
operation time has passed.
Capacirty
Fu
ll
lo
ad
When the load is set as low as less than 35Hz of full load operation frequency (1) to expand the capacity control range in the low
load area, a hot gas bypass (2) (full load conversion frequency:23Hz to 35Hz) is selected. (20VF: OFF, 20VU: ON)
Also, when the full load conversion frequency comes to over 35Hz
during a hot gas bypass operation, a full load operation is selected.
The compressor starts with a hot gas bypass all the time and, after
15 seconds, selects the load and the frequency according to the
demand(decision) frequency.
Hot gas bypass
0 10 20 3035 40 45 50 55 60 70 80 90
Ferquency (Hz)
(16) High pressure control
The high pressure control consists of the HP protection, HP-A control, HP-B control and LP control and the order of priority
among them is assigned as HP protection >HP-A > LP > HP-B down > HP-B up.
HP protection
Pressure switch [If 63H1: 3.24 open/2.65 close MPa (33 Open/27 close kgf/cm2) is actuated twice within 45 minutes, the
operation is stopped due to the error and the check and indication (Remote controller: E40, indoor LED-green; repeated flickers,
red: dark, outdoor LED-green; reperted flickers, red; 3 flickers) are performed. In case of initial operation, however, the
compressor is stopped and after a delay of 3 minutes it returns to the normal operation.]
HP-A control
• If the pressure switch (63H2) is actuated, the outdoor blower is opreated in the Hi mode (for the operations of patterns A1 to C1)
or stopped (for the operations of patterns C2 to E2) and, if it is still actuated 2 minutes after a drop of 10 Hz in the inverter
frequency, the frequency is dropped futher by 10 Hz. (Minimum frequency is specified at the partial load of 35 Hz.)
• Operation returns to the normal mode after operating with the frequency control at off(1) 6 minutes after the 63H2 having been reset.
Note (1): If the high pressure A control is released,the frequency is raised by 5 Hz and retained at the level for 3 minutes. The
frequency is then raised by 5 Hz at 3-minute intervals till it returns to the normal operation.
1039
FDC-HKXR
LP,HP-B controls
Under these controls, the high and low level pressures are controlled with the solenoid valves, outdoor fan and other so as to
operate the outdoor unit in the optimum condition in accordance with changing load on the indoor unit.
Operation patterns consist of the following 12 types and respective functional parts are controlled per each pattern.
Table of operation patterns and operations of functional parts
Operation
Pattern
A1
A2
B1
B2
B3
C1
C2
D1
D2
D3
E1
E2
Four-way valve
20SS
20SL
SVS
Solenoid Valve
SVL
SV2
SV3
Fan motor
FM02
FM01
HI
HI
HI
HI
HI
HI
Me
HI
HI
Me
Me
HI
HI
HI
HI
HI
HI
Notes (1) and mean ON and OFF respectively.
(2) Hi and Me mean the high and medium temperature operations respectively.
(3) When the fan motor FM01 is in the Me mode, the solenoid valve SV3 is interlocked via a relay. (SV2 open)
• LP control
If the pressure switch [63L: 1.96 close/2.75 open MPa (20 close/28 open kgf/cm2)] is actuated, the operation pattern is changed
by one step in the direction of A1 to E2 so as to raise the low level pressure by controlling the heat exchanger capacity.
• HP-B down control
If the pressure switch [63H3: 2.11 close/2.50 open MPa (21.5 close/25.5 open kgf/cm2)] is actuated, it enters the HP-B down
control and the operation pattern is changed by one step in the direction of E2 to A1 so as to lower the high level pressure by
controlling the heat exchanger capacity.
• HP-B up control
If the pressure switch [63H4: 1.86 close/1.67 open MPa (19.0 close/17.0 open kgf/cm2)] is actuated, it enters the HP-B up
control and the operation pattern is changed by one step in the direction of A1 to E2 so as to raise the high level pressure by
controlling the heat exchanger capacity.
• Setting the initial operation pattern
Indoor load
Initial operation pattern
When the compressor is started, the operation starts wish one of the following
Cooling only
A1
operation patterns in accordance with the indoor load.
A1
Cooling > Heating
B1
Cooling
=
Heating
• Timing to change operation pattern
C2
Heating
<
Cooling
Operation pattern is changed by one step at the actuation of the pressure switch (63L,
D1
Heating only
63H3 or 63H4). Once the operation pattern is changed, the same operation pattern is
maintained for 2 minutes.
However, when the frequency which was requested from the indoor side has changed 20 Hz or more, the operation pattern is
changed by one step at the actuation of the pressure swich even if it is within 2 minutes.
• Changing of operation pattern after a larger change of load
Operation pattern
When the indoor load has changed largely like a case when scales of
Change from heating large to cooling large
To A1
heating/cooling loads have been inverted, for example, the operation
Change from cooling large to heating large
To D3
pattern is changed as follows.
1040
FDC-HKXR
(17) Compressor operating frequency increase control
(a) In the case that at least one in-door unit requires the maximum frequency supply during cooling or heating operation for 6
minutes continuously, the compressor operating frequency is increased by 10 Hz. After that, the maximum frequency is
increased by 10 Hz every continuous 6 minutes; however, the upper limit is 30 Hz.
(b) When requirement of the maximum frequency ceases, the control is released.
(c) When the protective function of frequency suppressing is activated during control, the protective motion is performed at the
condition of increased frequency as the base.
(Example: When the current safe is activated at the condition of +20 Hz compensation)
50
Current safe
Required Hz
40
from in-door unit
Current safe released
In-door unit
requirement
30
With +20 Hz
compensation
60
Compressor
operating Hz
50
Without +20 Hz
compensation
40
(18) Control at heating change over
When one of the in-door units is changed over from "Cooling (including automatic), dehumidification and ventilating mode" to
"Heating (including automatic) mode", or from "Heating mode" to "Cooling, dehumidification and ventilating mode", the
following control is performed.
(a) During compressor is operating
1) The heating output is kept at the output condition just before cooling/heating change over for 2 minutes and 45 seconds,
after that the heating output of in-door unit where cooling/heating has been changed is changed over.
2) The 4 way valve (20SL, 20SS) is changed over at 2 minutes after the compressor stopped.
3) The compressor starts operation with the operation pattern shown in the following diagram after 3 minutes' stop.
Heating
Operation
mode
Cooling
In-door
unit
Heating
output
ON
OFF
2 min. and 45 sec.
2 min. and 45 sec.
3 min.
3 min.
ON
Compressor
OFF
2 min.
4 way valve
(20SL, 20SS)
2 min.
ON
or
OFF
Initial operation
pattern
Initial operation
pattern
(b) When the compressor has kept on stopping for 2 minutes and 45 seconds or more:
1) The heating output is changed over immediately.
2) The motion of compressor and 4 way valve is the same manner as described in Article (a).
(c) When the stop time of compressor is less than 2 minutes and 45 seconds:
1) The heating output is changed over after 2 minutes and 45 seconds has passed since the compressor stop.
2) The motion of compressor and 4 way valve is the same manner as described in Article (a).
1041
FDC-HKXR
(19) Devices related to unit protection and maintenance
(a) Test Run Mode
The test run mode can be set from the outside by using the switch SW3-4,5 on the outdoor unit control circuit board
(i) Switch function
Switch
SW3-4
SW3-5
Function
ON
• To operate all connected indoor units.
• Indoor units demands the maximum frequency and outdoor units are operated with the maximum frequency
according to request from the indoor unit.
OFF
• Normal operation
ON
• When SW3-4 is set to ON: Cooling operation
OFF
• When SW3-4 is set to ON: Heating operation
(ii) The maximum frequency of outdoor unit in test run operation (At the time of rated capacity)
Model
FDCP2001,2501 type
Maximum operation frequency (Hz)
95
Remarks : Fuzzy control is not performed in test run operation.
(Operation is executed.) Other controls are effective.
(b) Expansion Valve Control for oil Return
After the compressor operated for 10 hours, and when the compressor is turned, stop the compressor to collect refrigerant
oil, turn off the thermostat, and fully open indoor unit expansion valves of FAN and adnormally stopped units one by one.
(Open expansion valves in the sequence that addresses were registered to outdoor units and not of the address number.
(c) High Pressure Control in Heating Operation
When (63H2) [2.84 close/2.26 open MPa (29.0 close/23.0 open kgf/cm2)] operates, the compressor revolution decrease 10
Hz, and outdoor unit fan stops preventing pressure increase. Frequency control is canceled after 6 minutes from reset of
63H2, then the compressor returns to the normal operation.
Note (1) Detail of Frequency Control Canceling Operation
When a high pressure control is canceled, the frequency increases 5 Hz, and the frequency is retained for 3 minutes. The
frequency increases 5 Hz every 3 minutes to the normal operation.
(d) Discharge gas Temperature Control (All Operation Modes)
When the discharge gas temperature (discharge gas thermistor : ThO-D) increases above the set point, the temperature (detected
with ThO-D) is controlled by opening and closing the liquid bypass solenoid valve (SV1) and by lowering the frequency.
Note (1) ThO-D > 115°C .......SV1-Open [ThO-D < 108°C Closes]
The expansion valve of operating indoor unit open 5% approx.
ThO-D > 120°C .......The frequency is lowered 10Hz each time at intervals of 2 minutes (Lower Limit: 35 Hz of the
full load or a hot gas bypass.) (ThO-D = < 115°C are canceled)
ThO-D > 130°C.......abnormal stop
[The operation can be resumed at a temperature bellow 90°C]
(e) Compressor Control at the during of startup
(i)
Inrush Current the compressor with 5Hz to the starting.
Also, at the time of startup, fully open the expansion valve of the indoor unit in the operator cab for 4 minutes.
(ii) Protective Start of Compressor
When the inverter starts, the compressor start under protection.
Operate with hot gas bypass up to 35 Hz after the start, operate with full loads of 60 Hz for 15 seconds, then operate
with the decision frequency. When the frequency is higher than 65 Hz, they operate with 65 Hz for one minute 45
seconds after the start. But when the compressor starts first time after the power is turned on, and when the compressor
starts after stop for more than 6 hours, it increases the frequency 5 Hz each minute for 13 minutes.
1042
FDC-HKXR
(iii) Three minutes delay timer
The compressor (inverter) will remain in stop state for 3 minutes, when the compressor is stopped by thermostat, ON/OFF
swich, and /or by occurrence of trouble. When the power source is turned ON, the 3-minutes delay timer is cancelled.
(f) Detection Control of Electricity Supply to Crank Case Heater
When an operation starts less than 6 hours after the power is turned on (electricity is supplied to CH), the frequency is
controlled as follows:
(to the decision frequency)
(Hz)
70
60
50
40
30
20
5Hz/minutes
10
0
5
10
15
20
25
Notes (1) When the operation stops within 33 minutes, this
control is executed at the time of the second or later
startup.
(2) Operate with hot gas bypass up to 35 Hz, then with 60
Hz for 15 seconds.
30 33 (minutes)
(g) Open-phase Protection
When the T-phase voltage of the secondary side of 52C is 0V, an abnormal stop will occur and the inspection displays
(Remote controller : E34, indoor unit green LED : Continuous flashing, red LED : OFF, outdoor unit green LED : red LED
: 2 times flash) will appear.
(h) Current Safe Control
The operation corrent is automatically controlled.
When the operation current at the converter inlet increases, the frequency is lowered 5 Hz by 5 Hz so that the operation
current does not increase above the set point.
Lower limit frequency: Hot gas bypass 35 Hz
1) Retain the operations with hot gas bypass of 35 Hz for 3 minutes, and when it is foud to be the current safe value, stop the
inverter, operate them with hot gas bypass 3minutes later for 3 minutes. When the frequency is below the current safe
value, operate them with full loads of 35 Hz, cancel the frequency control to bring them back to the normal operation.
2) When the decision frequency under the fuzzy control get lower than the current safe frequency during a current safe
control, bring them back to the normal operation. When the current value comes to the current cancel value during a
current safe control, retain the frequency for 3 minutes, then cancel the frequency control.
(i) Current Cut Control
This control aims to prevent over current in the converter. When the current increases above the set point, stop the inverter
immediately, then let is reset by itself 3 minutes later. After the self-reset, start the inverter with 35 Hz, and increase the
frequency 5 Hz every 3 minutes to let it return to the fuzzy indication frequency. When the current is cut four times in 15
minutes, turn off 52C bring it to an abnomal stop and the inspection displays (Remote controller : E42, indoor unit green LED
: Continuous flashing, red LED : OFF, outdoor green LED : Continuous flashing,and red LED : 1 time flash will appear.
(j) Protection of Power Transistor from Overheat
When the temperature of the power transistor increases to the set temperature, stop the inverter immediately and let is reset
by itself 3 minutes later. If the power transistor is overheated again within 2 hours, turn off 52C, bring it to an abnormal
stop and the inspection displays (Remote controller : E41, indoor unit green LED : Continuous flashing, red LED : OFF,
outdoor unit green LED : Continuous flashing, red LED : 4 times flash) will appear.
1043
FDC-HKXR
(k) Protection of Power Transistor from Overheat
When the temperature of the power transistor increases to the set temperature, stop the inverter immediately and let is reset
by itself 3 minutes later. If the power transistor is overheated again within 2 hours, turn off 52C, bring it to an abnormal
stop and the inspection displays (Remote controller : E41, indoor unit green LED : Continuous flashing, red LED : OFF,
outdoor unit green LED : Continuous flashing, red LED : 4 times flash) will appear.
(l) Protection of Number of Connected indoor Units
When the number of connected indoor units exceeds the quantities shown in the table below, they will come to an abnormal
stop, and the inspection displays (Remote controller E43, indoor unit green LED : Continuous flashing, red LED : OFF,
outdoor unit green LED : Continuous flashing, red LED : 7 times flash) will appear.
Number of connected units
FDCP2001 type
FDCP2501 type
8 units
8 units
(m) Frost prevention during cooling
To prevent frost during a cooling operation, check temperature (to be detected with ThI-R) of the indoor unit heat exchanger
and lower the frequency of indoor unit (opening of expansion valve) when the temperature drops below 3°C.
When the heat exchanger temperature is below 2°C for more than 2 minutes, turn off the thermostat and start a ventilating
operation. If the heat exchanger temperature rises above 16°C after the thermostat is turned off, reset it to a cooling operation.
But this operation shall not be executed for 10 minutes after the thermostat is turned on.
Also when temperatures of standing units have been below 2°C for an hour in succession, turn off the compressor for 3
minutes.
(n) Control of Temperature under Dome
The liquid bypass solenoid valve (SV1) is controlled according to the temperature of the thermistor (ThO-C) under the dome
fitted to the compressor.
Full Load
Open
Close
55°C
1044
Hot gas bypass
Open
Close
65°C
30°C
40°C
ThO-C > 65°C SV1 open
ThO-C > 40°C SV1 open
ThO-C < 55°C SV1 close
ThO-C < 30°C SV1 close
FDC-HKXR
20.5 APPLICATION DATA
SAFETY PRECAUTIONS
• Please read these “Safety Precautios” first then accurately execute the installation work.
• Though the precautionary points indicated herein are divided under two headings,
WARNING and
CAUTION , those
points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in
the
WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in
the
CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
• After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain
operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual.
Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
• This system should be applied to places of office, restautant, residence and the like. Application to
inferior environment such as engineering shop could cause equipment malfunction.
• Please entrust installation to either the company which sold you the equipment or to a professional
contractor. Defects from improper installations can be the cause of water leakage, electric shocks
and fires.
• Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires.
• When a large air-conditioning system is installed to a small room, it is necessary to have a prior
planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the
equipment, and make the installation accordingly. In the rare event that a refrigetant leakage and
exceeding of threshold concentration does occur, there is the danger of a resullant oxygen deficiency
accident.
• For installation, confirm that the installation site can sufficiently support heavy weight. When strength
is insufficient, injury can result from a falling of the unit.
• Execute the prescribed installation construction to prepare for earthquakes and the strong winds of
typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling
over of the unit.
• For electrical work, please see that a licensed electrician executes the work while followig the safety
standards related to electrical equipment, and local requlations as well as the installation instructions,
and that only exclusive use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of
electric shocks and fires.
• Accurately connect wiring using the proper cable, and insure that the external force of the cable is not
conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
• Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper
installation can also result in heat generation or fire.
• When setting up or moving the location of the air-conditioner, do not mix air etc. or anything other
than the designated refrigerant within the refrigeration cycle.
• Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refrigerant leakage.
CAUTION
• Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or
a telephone ground wire. Improper placement of ground wires can result in electric shock.
• The installation of an earth leakage breaker is necessary depending on the established location of the
unit. Not installing an earth leakage breaker may reslut in electric shock.
• Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
• For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally
insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
1045
FDC-HKXR
20.5.1 Installation of indoor unit
This is same as multi KX series. Refer to page 841~881.
20.5.2 Installation of the remote controller (Optional parts)
This is same as multi KX series. Refer to page 882.
20.5.3 Installation of outdoor unit
(1) Selection of installation location
(a)
A palce where air will not be stagnant.
(b)
A place where the exhaust air will not be shorteyeled.
(c)
A place with enough space for air flow around the unit.
(d)
A place where the unit will not be affected by other heat sources.
(when there are multiple units installed or when units have another heat source)
(e)
A void installing the unit in places that are subject to sea air, sulfureous gas of the type found in hot springs, or any other
(f)
A place where smooth drainage of rain water and water formed by defrosting is acceptable.
(g)
In heating operation, snow deposit on the heat-exchanger of outdoor unit must be prevented for keeping the normal
corrosive or flammable gas.
performance capacity.
•
Snow-hood no outdoor unit as in drawing, will reduce the frequency of defrost operation.
When installing the snow hood, take care so that the air outlet of the snow hood will not face directly into the most
windy direction.
•
(h)
Design the base higher than possible snow deposit.
A place where air outlet port is not exposed to strong wind.
(2) Installation space
A place with enough space for air inlet, air outlet and service space.
(a) Independent installation
Dimension
Installation
example
Unit: mm
I
II
III
Distance
1)
L1
open
open
500
L2
0
500
500
L3
200
200
200
L4
500
0
500
When there are obstacles on the sides and at the rear side of the unit
Note (1) The unit can be installed bringing the right side close to the obstacle. In that case, provide a space over 500
mm to the left side.
1046
FDC-HKXR
2)
When there is an obstacle above the unit
Note (1) The side air outlet indicates that a wind direction
variable adapter available on the optional parts is
fitted to the unit.
3)
When there is an obstacle (are obstacles) on the side (in front side of and at the rear side) of the
unit
4)
When there is an obstacle above the unit as well
5)
When there is no obstacle above the unit
Note (1) The side air outlet and the up air outlet indicate
that wind direction variable adapters available on
the optional parts are fitted to the unit.
6)
When installed in a narrow space (there are obstacles in front side of and at the rear side of the
unit.)
[Remarks]
When there is a space above the unit, install the unit in the
same way as you do when there is an obstacle (are obstacles)
on a side (in front side of and at the rear side) of the unit.
1047
FDC-HKXR
7)
Installation where there is obstacle on all four sides.
Note (1) The up air outlet indicates that a wind direction
variable adaptor available on the optional parts
is fitted on the unit.
(b)
Installation of multiple units
1) Continuous installation on side-to-side [The front side is open]
[Keep a space of more than 10 mm between the units]
Note (1) There shall be no obstacle above the unit.
[Remarks] When the unit is installed continuously side by side, any multiple units can be installed.
2) Continuous Installation on side-to-side [There are obstacles in front side of and at the rear side of
the unit.]
[Keep a space of more than 10 mm between the units]
Note (1) The obstacle at the rear side shall be lower than the unit, and the obstacle in front side shall be less than
1000 mm.
[Remarks] When the unit is installed continuously side by side, any multiple units can be installed.
Note (1) When an up air outlet is selected optionally,
the obstacle in front can be made lower than
the unit.
1048
FDC-HKXR
3) Face-to-face installation
Dimension
Distance
L1
Item
Diagonal
1500 or more
1000 or more
500 or more
500 or more
Up air outlet
Unit: mm
L2
Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
4) Side-to-side & face-to-face installation
[Keep a space of more than 10 mm between the unit]
Dimension
Distance
L1
Item
Diagonal
1500 or more
1000 or more
800 or more
800 or more
Up air outlet
Unit: mm
L2
Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
5) In the case where the unit is exposed to strong wind.
a) Face the unit air outlet at a 90º angle from the direction of the wind.
b) Securing outdoor unit (in the case of exposure to severe weather conditions)
Fix the unit in the following way.
•
Use overtuming prevention brackets.
•
Rig with wires.
(Use rigging wires that are resistant to corrosion and sufficient in
strength. For example SUS304-W1, wire thick-ness 2.9 mm)
1049
FDC-HKXR
(3) Installation
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following.
(a)
Fix the unit to the foundation with anchor bolts.
Unit: mm
1050
(b)
When installing the unit, be sure to fix the pedestal of the unit with bolts.
(c)
Install the unit securely not to be fallen by earthquake or strong of wind.
(d)
Prepare a concrete foundation referring to the above figure.
FDC-HKXR
20.5.4 Refrigerant piping
(1) Precautions no refrigerant piping work for prevention against compressor lock
Compressor trouble including lock and motor burn-out is due to faulty parts but mainly concerned in installation and refrigerant
piping conditions, The precautions for refrigerant piping are as belows.
(a) Be sure to perform brazing while flowing nitrogen.
1)
Without flowing nitrogen gas, a lot of oxide film (CU2O) is generated. In particular, in case of for building with many
2)
A foreign material (oxide film) causes clogging of the capillary tube or expansion valve, leading to non-cooling (non-
brazed portions, oxide film is so much generated that this causes a fatal failure in the air conditioning system.
heating), abnormal discharge temperature, compressor lock due to a faulty oil return. In some cases, a lot of foreign
materials block the oil return hole of the accumulator, thereby causing a compressor lock. (This lock trouble may occur
repeatedly 2 or 3 times.)
(b) Don’t admit water (waterdrops, condensation) into the piping.
1)
Use a copper piping that is free from water (waterdrops,
condensation).
2)
Don’t perform refrigerant piping work while it rains.
3)
To suspend outdoor piping work, perform curing to prevent
water admission.
Bad effects of water
•
Capillary tube and expansion valve clogging
•
Refrigerant hydrolysis → “Acid” generation
There will be directly conected to serious
→ Iron/copper corrosion
•
trouble such as compressor lock or burn-
Crystal foreign material (clathrate compound)
out of the compressor motor.
generation resulting from reaction on refrigerating
machine oil
(c) Don’t admit dust or foreign particles in the pipe.
Various foreign particles are included in air conditioners that caused trouble. Be careful about them.
(Concrete fragments, cement, sand, paint, metal powder (copper refuse after deburring, etc.), etc.
(d) Adopt the specified dimensions for pipes.
Too thick:
Improper charge volume
Compressor lock
Faulty oil return (insufficient gas flow rate)
Too long (L):
Overcharge
Liquid back
Compressor lock
Faulty oil return
(e) Be sure to support the refrigerant piping with support fittings.
1)
The pipe vibrates and expands/shinks during operation. Without proper supports, a load is concentrated partially and
cracks and collapse occur on the piping, thereby causing a unit failure.
2)
A support should be provided at intervals of 2 or 3 m so as not to partially concentrate a load.
1051
FDC-HKXR
(2) Refrigerant piping size selection
Branch line
Outdoor unit
connection pipe
Indoor unit
connection pipe
Downstream indoor
unit capacity total (1)
less than 160
22,28,36,45
(not including 160) less than 90
type
90 or more (not including 90)
FDCP2001
type
FDCP2501
type
160 or
more
Liquid
piping
φ12.7 × 1.0
mm
φ12.7 × 1.0
mm
φ12.7 × 1.0
mm
φ9.52 × 0.8
mm
φ9.52 × 0.8
mm
Intake gas
piping
φ25.4 × 1.4
mm
φ28.58 × 1.4
mm
φ25.4 × 1.4
mm
φ19.05 × 1.2
mm
φ15.88 × 1.0
mm
Discharge
gas piping
φ19.05 × 1.2
mm
φ19.05 × 1.2
mm
φ19.05 × 1.2
mm
φ15.88 × 1.0
mm
φ12.7 × 1.0
mm
Flow divide controller
connection pipe
56,71,90
type
112,140
type
models
Indoor
side
Outdoor
side
φ6.35 × 0.8
mm
φ9.52 × 0.8
mm
φ9.52 × 0.8
mm
φ9.52 × 0.8
mm
φ9.52 × 0.8
mm
φ12.7 × 1.0
mm
φ15.88 × 1.0
mm
φ19.05 × 1.2
mm
φ15.88 × 1.0
mm
φ15.88 × 1.0
mm
φ12.7 × 1.0
mm
Notes (1) This shows the total capacity of the indoor units connected after indicated branch pipe.
(2) 1 flow divider pipe set is required for each division.
Branch pipe set part shapes (DIS-1KXR3-E)
Name
Part shape
φ25.4
φ19.05
φ19.05
φ15.88
φ12.7
φ19.05
φ12.7
Branch pipe
1
Discharge gas piping
1
Liquid piping
1
Intake gas piping
(FDCP2501HKXRE2)
φ6.35
128
φ12.7
φ12.7
Intake gas piping
Notes (1) Each flow divider pipe is
surrounded with insulation.
(2) Each pipe is cut off in the
middle of the diameter that
is used in that locality.
φ12.7
424 φ15.88
φ9.52
1
φ12.7
94.5
2
φ25.4
φ15.88 φ19.05
519
ID
φ15.88
Remarks
φ12.7
φ19.05
φ15.88
1
Quantity
φ15.88
φ25.4
119
ID
φ19.05
φ9.52
Symbol
3
247
a
OD
25.4
Reducer
ID
28.58
100
Shapes of accessory parts for brunch pipe set for vertical divides (DIS-V1KXR3-E)
φ19.05
φ19.05
φ12.7
Intake gas piping
φ19.05
φ6.35
φ12.7
Branch pipe
100
—
ID28.58
OD25.4
100
—
OD
19.05
Reference 1: Be sure to install the
vertical flow divider
coupling (both) for
gas and liquid) as
"vertical divide" as
illustrated below.
128
Floor
247
Notes (1) Insulation is provided to
all flow divider pipes.
(2) Cut off the flow divider
pipes in the center to
match the diameter of the
piping used on site.
ID
φ25.4
φ12.7
φ9.52
φ15.88
φ12.7
φ15.88
φ12.7
424
φ9.52
Discharge
gas piping
3
φ19.05
120
94.5
285
ID φ15.88
φ15.88
φ25.4
φ15.88
φ19.05
φ12.7
φ19.05
φ12.7
φ15.88
98
130
1
2
1052
Classification Symbol
Branch pipe
ID
Liquid piping
Intake gas piping
Classification Symbol
FDC-HKXR
(Example)
Outdoor unit
Discharge gas piping
Liquid piping
Intake gas piping
Flow divider
pipe set for vertical divides
Indoor unit
Individual flow
divide controller
(DIS-V1KXR3E)
Indoor unit
Individual flow
divide controller
When the outdoor unit are installed at a higher level than the individual flow divide controller and a vertical flow
divider is required for the piping connections of 2 or more individual flow divide controllers for 1 module, use
the "flow divider pipe set" for vertical divides.
Flow divider pipe set for vertical divides Part No. DIS-V1KXR3-E
Shapes of individual flow divide controller accessories (HPFD1R-E)
Name
Reducer
For outdoor
For outdoor intake
Application discharge gas piping and indoor gas piping
Quantity
For outdoor and
indoor liquid piping
2
1
In Sulation
Relay kit
For pipe cover
For controller
2
Piping connection Number of divisions
1
OD9.52
OD15.88
OD12.7
Strainer coupline
For outdoor
discharge gas piping
Shape
ID15.88
Code
ID
19.05
ID
12.7
A
ID6.35
B
C
Example of piping
Outdoor unit: FDCP2501HKXRE2
[Total capacity: 348 (34800w)]
FDCP
Outdoor unit 2501HKXRE2
A
Branch
piping 1
B
Branch piping 2 Branch piping 3
D
C
Branch piping 4
F
G
H
a
b
c
112
71
56
Individual flow divide controller
Indoor unit
Branch piping 5
I
d
J
e
K
f
E
Individual flow divide controller
45
36
28
Indoor unit
1053
FDC-HKXR
Good
Note 1: When making branch connections (for both gas and liquid lines), be sure that the proper
horizontal branches and vertical branches are used.
No
No
Vertically
Good
Floor
Floor
Horizontally
Floor
Floor
• Selection piping size
Item
Piping size(mm)
Selection procedure
A
Same as the outdoor unit piping size (FDCP2501HKRE2)
B
Total capacity of connected indoor units
Intake
gas line
Gas line
ø19.05
ø28.58
Liquid line
ø12.7
(236)
ø19.05
ø25.4
ø12.7
ø19.05
ø9.52
C
Total capacity of connected indoor units
(165)
ø15.88
D
Total capacity of connected indoor units
(109)
ø15.88
ø19.05
ø9.52
E
Total capacity of connected indoor units
(64)
ø12.7
ø15.88
ø9.52
ø19.05
ø9.52
F
Total capacity of connected indoor units
(112)
ø15.88
G
Total capacity of connected indoor units
(71)
ø12.7
ø15.88
ø9.52
H
Total capacity of connected indoor units
(56)
ø12.7
ø12.7
ø6.35
ø12.7
ø6.35
I
Total capacity of connected indoor units
(45)
ø12.7
J
Total capacity of connected indoor units
(36)
ø12.7
ø12.7
ø6.35
K
Total capacity of connected indoor units
(28)
ø12.7
ø6.35
a
Indoor unit piping size
(112)
ø12.7
ø19.05
b,c
Indoor unit piping size
(71,56)
ø15.88
ø9.52
d~f
Indoor unit piping size
(45,36,28)
ø12.7
ø6.35
ø9.52
• Selection of branch piping size.
Selection procedure
Item
Branch pipng set
Branch piping 1
Horizontal branch piping set – down-flow indoor unit capacity total.
(348) DIS-1KXR3-E
Branch piping 2
Horizontal branch piping set – down-flow indoor unit capacity total.
(236) DIS-1KXR3-E
Branch piping 3
Horizontal branch piping set – down-flow indoor unit capacity total.
(165) DIS-1KXR3-E
Branch piping 4
Vertical branch piping set – down-flow indoor unit capacity total.
(109) DIS-V1KXR3-E
Branch piping 5
Vertical branch piping set – down-flow indoor unit capacity total.
(64) DIS-V1KXR3-E
Piping connection instructions (for the above example)
Process the included reducer as illustrated below.
Use the flare nuts included with the individual flow divide controller.
When the indoor unit capacity is 90 or more
A type
Use reducer A and process the φ12.7
portion into a flare.
( OD12.7 → ID15.88 )
ID19.05(Brazing)
ID19.05(Brazing)
B type
70 or more
Cut off reducer B using a pipe cutter
as shown in the illustration and make a
flare.
( OD15.88 → ID19.05 )
ID15.88(Brazing)
Reducer B (accessory)
When the indoor unit capacity is 50 or less
Reducer C (accessory)
B type
70 or more
ID6.35(Brazing)
ID6.35(Brazing)
Cut off reducer B using a pipe cutter
as shown in the illustration and make a
flare.
( OD15.88 → ID12.7 )
ID12.7(Brazing)
ID12.7(Brazing)
Reducer B (accessory)
1054
FDC-HKXR
(3) Specification of unit piping (Pipe diameter. Connecting method)
(a) Unit
1)
Outdoor unit
Unit: mm (in)
Item
Model
2)
Gas line
Pipe diameter
FDCP2001HKXRE2
φ25.4 (1")
FDCP2501HKXRE2
φ28.58 (1 1/8")
Pipe diameter
Connecting method
φ12.7 (1/2")
Brazing
Brazing
φ12.7 (1/2")
Indoor unit
Unit: mm (in)
Gas line
Item
Pipe diameter
Model
3)
Liquid line
Connecting method
Liquid line
Connecting method
Pipe diameter
22, 28 type
φ12.7 (1/2")
36 type
φ12.7 (1/2")
45 type
φ12.7 (1/2")
56, 71, 90 type
φ15.88 (5/8")
φ9.52 (3/8")
112, 140 type
φ19.05 (3/4")
φ9.52 (3/8")
Connecting method
φ6.35 (1/4")
φ6.35 (1/4")
φ6.35 (1/4")
Flare
Flare
Tightening torque
φ6.35 (1/4") Flare nut
16~20N · m (1.6 ~ 2.0 kg·m)
φ9.52 (3/8") Flare nut
40~50N · m (4 ~ 5 kg·m)
φ12.7 (1/2") Flare nut
40~50N · m (4 ~ 5 kg·m)
φ15.88 (5/8") Flare nut
90~120N · m (9 ~ 12 kg·m)
φ19.05 (3/4") Flare nut
100~140N · m (10 ~ 14 kg·m)
Gas side flange bolt
30~40N · m (3 ~ 4 kg·m)
(b) Refrigerant piping connection
1) Pipes can be connected in four directions, but electric wire can be done in five directions.
2) Select the optimum connecting direction taking into account the installation conditions of outdoor unit and the
positional relations with indoor units.
3) For connections to the operation valves and attendant piping, connect gas pipes first, then liquid pipes.
• Remove the seal on the flange of the gas side service valve.
• Place the accessory packing between the flanges of the gas side service valve and of the attendant piping for gas before
connection.
1055
FDC-HKXR
(c) How to connect piping
1)
Connection to front directions.
a) Remove the front hall blank, pass through he hole the intake gas side, gas side and liquid pipes. and then connect then
to the service valves and the on-site piping. (Because the liquid side pipe is on-site piping, bend it to the dimensions
shown in the illustration at low.)
80
88
75
103
97
250
85
70
100
62 65
80
145
187
2)
Connection to lower direction.
a) Cut off the accessory intake gas side connection pipe and then connect to the intake gas side atraight pipe.
b) Remove the back hall blank, pass through the hole the intake gas side, discharge gas side, and liquid pipes, and then
connect them to the operation valve and the on-site piping. (Because the liquid side pipe is on-site piping, bend it to the
dimensions shown in the illustration at left.)
85
62 65 80
70
100
65
Intake gas side
(Accessory)
Liquid pipe
(On-site piping)
60
Intake gas side
connection pipe
(Accessory)
75
43
(Accessory)
250
Gas side
connection pipe
Back
40
105
107 100
1056
Half-brank
FDC-HKXR
(4) Heat insulation
(i) There is a need to insulate both gas and liquid piping with heat insulation for protection against heat and
condensation.
1) Always use heat insulation to prevent condensation on the gas piping from becoming drain water and
causing leakage during cooling and to prevent people from being burned by the high temperature of the
surface of the gas piping as discharge gas flows through it.
2) Use heat insulation (pipe cover) on the flare connection sections of the indoor unit.
(Insulate both the gas and liquid piping.)
3) Insulate both the gas and liquid piping. Apply the insulation so that is tight against the piping and free of
gaps. Route the connecting wires with the insulation and wrap the entire bundle with exterior tape.
;
;;;
;;;
;;;
;;;
;;;
;;;
Wires for connecting indoor
and outdoor units
Liquid piping
Exterior tape
Gas lines
Insulation
Use insulation material with good resistance heat properties (120 ˚C or more).
(5) Air-tight test
(a)
When conducting an air-tight test of local piping, connect the piping to the check joint of the evacuating pipe connected to
the gas side service valve, and keep the service valve closed. The air-tight test pressure shall be 3.23MPa(33 kgf/cm2.)
(b)
To conduct the test, pressurize the check joint of evacuating pipe by nitrogen gas as shown below. The local piping
including indoor units can be tested as for airtightness.
(6) Evacuating
Evacuating can be completed faster by evacuating both the check joint on the liquid side service valve and the check joint of the
evacuating gas pipe (accessory) connected to the gas side operation valve at the same time. (Of course, evacuating is possible
even through the liquid side check joint only.)
1057
FDC-HKXR
(7) Refrigerant charge amount
(a) Additional; charge amount
Item
Additional charge amount
per 1 m of liquid pipe
Factory charge amount at time of shipment
Indoor unit
φ12.7
φ9.52
φ6.35 Outdoor unit
Model
FDCP2001HKXRE2
0.12 kg/m 0.06 kg/m 0.03 kg/m
11.0 kg
Holding charged
FDCP2501HKXRE2
Remarks
Additional refrigerant
Charge is not required
Notes (1) When the refrigerant piping length exceeds the length that additional refrigerant charge is not required, charge
additional refrigerant based on to calculated amount of refrigerant per unit piping length.
(2) The unit is holding charge type that all of the refrigerant is charged in the outdoor unit and in the indoor unit only
a small amount of refrigerant is filled for prevention of the air entry.
Calculation of amount of refrigerant to be charged in local piping
The amount refrigerant additionally charged in local piping depends on connection pipe size but not on indoor unit type.
[Amount of refrigerant to be charged in the local piping = Actual length of liquid pipe × Amount of
refrigerant additionally charged per meter of liquid pipe]
[Example] Amount of refrigerant additionally changed = (I1 × 0.12) + (I2 × 0.06) + (I3 × 0.03)
I1 : Overall length (m) of φ12.7 liquid pipe
I2 : Overall length (m) of φ9.52 liquid pipe
I3 : Overall length (m) of φ6.35 liquid pipe
Following precautions must be observed when the model is adapted to R407C.
(1) Tools and related components should be changed when handling a different kind of refrigerant in order to prevent mixing of different oils.
Gauge manifold and charge hose, particularly, should never be used after using them for R22.
(2) Charge cylinder should not be used. Otherwise, the refrigerant composition may change when charging R407C into the cylinder.
(3) Refrigerant should be charged in the liquid phase from the container. Charging the refrigerant in the gaseous phase could change the
refrigerant composition substantially.
(4) Volume of refrigerant to be taken out in the liquid phase from the container should be up to 90% of necessary quantity (in weight percent)
as a standard.
(5) Refrigerant should not be replenished even if a leakage is discovered because it could change the refrigerant composition substantially.
When a leakage is discovered, replace with new refrigerant in the specified volume. However, it could be replenished temporarily in case of
an emergency.
20.5.5 Electrical wiring
(1)
Power supply wiring
(a)
Outdoor unit power supply (A separate power supply is used for the indoor unit)
Item
Model
Short-circuit breaker
Ground wire
Power Power supply Wire Wire circuit breaker (A) (Use
for both pround/
overload and short- Thickness Screw type
supply wiring thickness length
(mm)
(mm2)
(m) Rated current Switch capacity circuit production)
FDCP2001HKXRE2
3-phase
380/415V
FDCP2501HKXRE2
50Hz
5.5/5.5
46/54
40/40
30/30
40A100mA 0.1sec or less
8.0/8.0
47/58
60/60
50/50
50A100mA 0.1sec or less
5.5/5.5
M6
(b) Indoor unit power supply
Item
Supported
outdoor model
Thickness of Circuit Wire circuit Short-circuit breaker Signal wire thikness (mm2)
Power Power supply Wire power supply Breaker
breaker (Use for both pround/
wire
between Switch
luse rated current overload and short- Between outdoor Between
supply wiring thickness length indoorunits
capacity
(A)
circuit production) and indoor units indoor units
(mm2)
(m)
(mm2)
(A)
FDCP2001HKXRE2
1-phase
220/240V
FDCP2501HKXRE2
50Hz
1058
2.0/2.0
37/37 2.0/2.0
20/20
20/20
20A30mA 0.1sec or less
2 core ×
0.75 ~ 2.0
Same as
at left
FDC-HKXR
(c) Individual flow divide controller (Same power supply with the indoor units)
Power supply
wiring thickness
(mm2 × number of wires)
Item
Power supply
Supported model
Signal wire thickness
(mm2 × number of wires)
1-phase
2.0/2.0 × 2
220/240V
50Hz
Note (1) Do not misconnect the central flow divide controller signal wire.
2.0 × 2
HPFD1R-E
(2) Precaution in electric wiring.
(a) Use separate power supplies for the outdoor and indoor units respectiveliy (Standard specification)
(b) Signal wiring (for indoor and outdoor units)
Double-core cable with a diameter 0.75 to 2 mm2 should be used for the signal wires.
Never make the indoor and outdoor connecting signal line use “co-axial cable” or “strand” with the
power wiring for indoor and outdoor unit and other ower line.
(Never use a multiconductor wire together with power line. It may cause erroneous operation.)
Do not connect high voltage wires 220/240 V or 380/415 V to signal wires. as these wires are DC 5V. Signal wires
should be connected so that the terminal Nos. conform with each other for between outdoor and between indoor units.
However, they will work properly if different polarities are connected.
(Connect (A) and (A), (B)and (B).)
Do not strand or run the remote control cord with power line, electric line, etc.
The total length of the signal wires Should be 1000m or less.
Recommended signal wire list
Name
No.
Symbol
1
Vinyl cabtire round cord
VCTF double-core 0.75 to 2 mm2
2
Vinyl cabtire round cable
VCT double-core 0.75 to 2 mm2
3
Control vinyl insulated, vinyl sheathed cable
CVV double-core 0.75 to 2 mm2
4
Shielding wire
MVVS double-core 0.75 to 2 mm2
When No. 4 shielding wire is used, always ground the single wire side of the shielding wire . In addition, using the shielding
wire is helpful to prevent the incorrect connection between 5V DC and 220/240V or 380/415V AC because the
discrimination from the power supply wire is clear.
(3) Wiring system Diagram
Power source (outdoor unit side)
3-Phase 380/415V 50Hz
Earth leakage
breaker
Outdoor Unit
Circult breaker
Signal wire (between outdoor and indoor unit)
Power source wire
[Individual flow divide controller accessory wire (2m)]
Earth
Individual flow divide controllor
Individual flow divide controller accessory wire (2m)
Relay kit (Individual flow divide controller accessory)
Signal wire (between indoor units)
Circult breaker
Earth leakage
breaker
Indoor
Unit
Signal wire [Relay kit accessory (2m)]
1
2
3
4
5
6
7
8
Power source (indoor unit side)
1-Phase 220/240V 50Hz
Remote
controller
Remote controller wire
1059
FDC-HKXR
Outdoor/Indoor units connection procedures
Outdoor unit
AB
Individual flow
divide controllor
Power source (indoor unit side)
Power source wire
[Individual flow divide controller accessory wire (2m)
To next units by turn
L
•
N
C
N
U
Individual flow divide controller accessory wire (2m)
Cn Cn
B T4
Cn
T
L
•
N
AB
XYZ
C
N
U
Cn Cn
B T4
1
Relay kit
(Individual flow divide controller acessory)
Cn
T
Indoor unit
2
XYZ
Signal wire (between indoor unit)
AB
XYZ
Remote controller wire
XYZ
Remote
controller
Signal wire [Relay kit accessory (2m)]
Signal wire
Do not connect high voltage wire 380/415V to signal wires, as these wires are DC 5V. Signal wires should be connected so that
the terminal Nos. conform with each other for between outdoor and between indoor units. However, they will work properly if
different polarities are connected. (Connect (A) and (A), (B) and (B).)
Sensor inlet
Signal wire inlet
Outdoor control box
Signal wire (Between outdoor and indoor units)
Be sure to let the signal wire get in through the signal wire inlet.
(4) Indoor and outdoor signal wiring
(a) If only one Outdoor unit is used
Outdoor signal teminal block
A
B
Double cores
0.75 ~ 2 mm2
Total length of signal wires: 1000 m or less
A
B
A
B
A
B
Indoor signal terminal block
Notes (1) The indoor and outdoor signal wiring are without polarity
B
B
B
B
A
A
A
A
Either of the above wiring is correct.
(2) For connection to the terminal block, use as M3.5 (5/32) round eye-let terminal is shown below.
7 mm or less
1060
FDC-HKXR
(b) If plural outdoor units are used
1) A maximum of 48 indoor units can be connected by using the crossover wiring method, with 2 wires for
each side of the outdoor and indoor units.
Outdoor unit
Outdoor unit
AB
AB
Outdoor unit
Outdoor unit
AB
AB
Double cores
0.75 ~ 2 mm2
Total length of signal wires: 1000 m or less
AB
AB
Indoor unit
AB
Indoor unit
AB
Indoor unit
Indoor unit
2) Indoor/outdoor wiring method for multiple floors.
Outdoor
unit
Outdoor
unit
Outdoor
unit
Outdoor
unit
Double cores
0.75 ~ 2 mm2
Total length of signal wires: 1000 m or less
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
3) Loop wiring is inhibited
Outdoor
unit
Outdoor
unit
Outdoor
unit
Outdoor
unit
Loop wiring of signal wires is inhibiteed
Wiring at the Portion indicated by a
dotted line is inhibited.
(No)
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
(5) Remote controller wiring
(a) Wiring for controlling only one indoor unit.
X
Y
Z
Red White Black
X
Y
Z
Red White Black
Indoor unit
terminal blocks
Note (1) Cables for the remote controller have polarity. Be sure
to connect terminal blocks with the same numbers. If
mis wiring occurs, E1 is displayed and disables the
unit from operating.
Remote controller
terminal blocks
1061
FDC-HKXR
(b) When controlling plural units.
1) Use the same procedure shown in the drawing above for the wiring of the power supply, both indoor and outdoor units and
remote controller
When the wiring length for the remote controller exceeds 100 m, use the wiring procedure shown in the drawing below.
2) Connect each of the indoor units for group controlling (3 cables)
a) Connect the cables to the terminal blocks of X, Y, and Z for the indoor unit remote controller. Since the cables have polarity,
be sure to connect them to terminal blocks with the same numbers.
b) Use cables of more than 0.5 mm2 (Flexible and easily moved)
c) The total length of cables for crossover connection and the remote controller should be less than 600 m.
Allowable range of wire thickness and length
Standard Within
0.3mm2 × Within 100m
0.5mm2 × Within 200m
0.75mm2 × Within 300m
1.25mm2 × Within 400m
2mm2
× Within 600m
3) When there is more than one outdoor unit, they can be controlled by one remote controller.
4) One remote controller is capable of controlling up to 16 units in group.
Note (1) Use shielded cables, when wiring in parallel with cables for other power supply or when there is a possibility of being
affected by outer noise such as noise from a high-frequency unit.
Outdoor unit
Unit address
A B
No.01
Outdoor unit
Unit address
A B
No.02
Indoor unit
(Outdoor unit
address No.01)
(Indoor unit
address No.00)
A B
Indoor unit
(Outdoor unit
address No.02)
(Indoor unit
address No.03)
Indoor unit
(Outdoor unit
address No.01)
(Indoor unit
address No.01)
A B
Indoor unit
(Outdoor unit
address No.02)
(Indoor unit
address No.04)
Indoor unit
(Outdoor unit
address No.01)
(Indoor unit
address No.02)
A B
A B
A B
Indoor unit
(Outdoor unit
address No.02)
(Indoor unit
address No.05
A B
Remote controller
(c) Settings for main and secondary units when multiple remote controllers are used.
Up to two remote controllers can be used for each indoor
Remote control signal wire (has
unit (or each group of indoor units).
Indoor unit
polarity)
X
Y
Z
1) There are two methods for arranging this. One
Match X Y and Z and connect.
method is to take a remote control connection wire
(3-strand) from the indoor unit for the secondary
remote control. The other method is to use a jumper
wire from the main remote control.
2) Set the remote control switch for the secondary unit (SW4) to
X
Y
Z
X
Y
Z
secondary unit. (It was set to main unit a the factory.)
Note (1) The remote controller sensor setting is only enabled on the main remote controller.
Be sure to position the main remote controller in a location where it can detect
the room temperature.
1062
Remote
control
SW4
Main
Remote
control
SW4
Secondary
FDC-HKXR
(6) Setting of unit address
Addresses can be set either with the automatic address setting, remote control address setting or manual address setting depending
on the combinations of address switches (see table) of the indoor and outdoor units. Operate the address switches before turning
power on.
Indoor unit
Outdoor unit
Address setting method
Outdoor No.
Outdoor No.
Indoor No.
Auto address
49
49
49
Remote control address
00 ~ 47
49
49
Manual address
00 ~ 47
00 ~ 47
00 ~ 47
At the shipment from factory, outdoor Nos. of the outdoor unit are set at 49, both the output and indoor Nos. of the indoor units
are set at 49 and the setting method is set for the automatic addressing.
Address No. setting
Set the setting SW1 - 4 on the indoor PCB and the setting SW1 and 2 on the outdoor PCB as listed below.
On indoor PCB
On outdoor PCB
SW1, 2 (blue)
For setting of indoor No. (orders of 10 and 1)
SW3, 4 (green)
For setting of outdoor No. (orders of 10 and 1)
SW1, 2 (green)
For setting of outdoor No. (orders of 10 and 1)
SW2 (SW4) Order of 1
0 1
2 3
4
Order of 10
SW1(SW3)
SW1
(SW3)
order of 10
Order of 10
SW2(SW4)
0 1
9
7 8
2 3
Insert the tip of flat head
(precision) screwdriver
here and point the arrow
at a desired No.
9
0
1
2
3
4
5
6
7
8
0
00
01
02 03
04
05
06
07
08 09
1
10
11
12 13
14
15
16
17
18 19
2
20
21
22 23
24
25
26
27
28 29
3
30
31
32 33
34
35
36
37
38 39
4
40
41
42 43
44
45
46
47
48 49
Use 48 and 49 for setting the auto or remote
control address.
4
5 6
Order of 1
Notes (1) Outdoor No. is provided on the outdoor and indoor PCB's and indicates which outdoor unit is connected with
which indoor unit via a refrigerant pipe. Indoor and outdoor units connected with a refrigerant pipe must have
the same No.
(2) Indoor No. is used to identify a particular indoor unit. The No. should never be duplicated.
(a) Auto address setting
This setting is used when wiring on the basis of outdoor unit.
Outdoor unit
No. 49
AB
AB
Indoor unit
AB
Indoor unit
AB
Indoor unit
Remote controller
Remote controller
Remote controller
AB
Indoor unit
Wires cannot be connected across
different refrigerant lines.
1063
FDC-HKXR
1)
2)
3)
Set the address switch of outdoor unit at 49. (This is set at 49 at shipment from factory.)
Set the address switch of indoor unit at 49. (This is set at 49 at shipment from factory)
Turn power on for the indoor and outdoor units. Addresses are set automatically. (No. in a range of 0 - 11.)
For the auto address setting, power must be ON for both the indoor and outdoor units. If power is supplied to the indoor
unit only, "Outdoor No." is indicated on the remote controller. In such occasion, turn power ON also for the outdoor unit.
4) No. will be set within approx. 1 minute after turning power on.
5) If you press the inspection switch of the remote controller after setting the No., the address of indoor unit will be displayed.
The outdoor unit No. 49 will also be displayed.
6) Auto address setting is allowed also when controlling plural number of units with single remote controller. However, the
connection cannot be made across different refrigeration lines.
Information 1) Once addresses are set, they are retained on the microcomputer even after turning power off.
2) Even if the wiring is arranged on the basis of outdoor units, (2) remote control address setting and (3) manual
address setting can be used.
Erasing of addresses set with the automatic address setting
On the remote controller, press the "Fan speed" switch while holding down both the switches "Check" and "Timer".
Memory of address is erased. If the power supply to the indoor and outdoor units is turned off later, the system returns to
the state of no address setting. Then one of the three address setting methods can be selected by changing combinations of
the address switches.
(b) Setting of remote control addresses
This setting is used when connecting a plural number of indoor and outdoor units with the super link. This is applicable when using
single remote controller.
Figures in ( ) indicate address No.
by the remote control
ine "- - -" shows the refrigerant piping.
Address No. by the
remote control
Outdoor unit
Outdoor unit
No.00
No.01
AB
Indoor unit
Indoor unit
(Outdoor No. 00)
(Indoor No. 00)
(Outdoor No. 01)
(Indoor No. 03) A
AB
Indoor unit
Indoor unit
(Outdoor No. 00)
(Indoor No. 01) A
(Outdoor No. 01)
(Indoor No. 04)
B
1064
AB
Remote controller
Remote controller
Indoor unit
Indoor unit
(Outdoor No. 00)
(Indoor No. 02)
(Outdoor No. 01)
(Indoor No. 05)
Remote controller
B
Remote controller
Remote controller
1)
2)
3)
4)
AB
AB
AB
Remote controller
Set the address of outdoor unit with a number in a range of 0 - 47 avoiding duplication with any other outdoor unit.
Leave intact the address switch on the indoor unit PCB at 49 as set at the shipment from factory.
Turn power on. Then you can proceed the remote control address setting.
Set the outdoor No. corresponding to each indoor unit, using the remote controller. Set next the indoor No. of indoor unit
in a range or 0 - 47 avoiding duplication with any other unit connected in the group.
FDC-HKXR
Detail of setting from the remote controller
1) If the power switch is turned on, the outdoor No. on the display flashes, and "--" on the return air temperature display
section and "U--" on the time display section are lit.
If power is not supplied to the outdoor unit, the outdoor No. only lights and you cannot set the address. In such occasion,
to turn power on also for the outdoor unit.
2) Indoor No. increases 0, 1, 2, ... and up at each push on the room temperature setting ▲ switch. Press the room temperature
setting ▼ to reduce the outdoor No. 0, 47, 46, 45 ... and down. Stop to press the switches when a desired No. is indicated.
3) Press the Set switch so that the outdoor unit display changes from flashing to firm lighting and the outdoor No. is set.
Simultaneously, "U" indicating the indoor unit No. starts to flash.
4) Set the indoor No. in the same way with the room temperature setting switches ▲ and ▼.
5) After completing the setting, press the Set switch so that the "U" display changes from flashing to firm lighting and the
figures of outdoor No. and indoor No. on display start to flash.
6) Confirming the outdoor No. and indoor No. being correct, press the Set switch again.
If you like to change these Nos., press the "Check" switch so that it returns to the state of the step 2) and you can resume
the address setting.
7) This is all for the address setting. The address display will go off 5 seconds later.
Note (1) Once the addresses are set, they are retained on the microcomputer even after turning power off. If you need to
change the address, proceed as follows.
Change of address
Hold down the "Check" switch on the remote controller for more than 5 seconds. Outdoor No. on display flashes and you can
set new addresses. Set the outdoor and indoor address Nos. same as described above. New addresses can be set.
Erasing the addresses set by the remote control address setting
Holding down both the switches "Check" and "Timer", press the "Fan speed" switch. Addresses in the memory are erased.
Turn power off on the indoor and outdoor units so that it returns to the no address setting condition and you can set the
addresses with one of the three methods of address setting by changing combinations of the address switches.
(c) Manual address setting
This setting is used when connecting plural number of outdoor and indoor units with the super link, and is applicable when
controlling with more than one remote controller. (You can use only one remote controller of course.)
Turn power off before operating the address switches. Change of address is disabled when power is supplied.
Line "- - -" indicates the refrigerant piping. Figure in the figure indicates the address
number determined with the address switch.
Address No.
by address switch
Outdoor unit
Outdoor unit
No.01
No.02
2)
3)
AB
Indoor unit
Indoor unit
(Outdoor No. 01)
(Indoor No. 00)
(Outdoor No. 02)
(Indoor No. 04)
AB
AB
Indoor unit
Indoor unit
(Outdoor No. 01)
(Indoor No. 02)
(Outdoor No. 02)
(Indoor No. 05)
AB
AB
Indoor unit
Indoor unit
(Outdoor No. 01)
(Indoor No. 03)
(Outdoor No. 02)
(Indoor No. 06)
Remote controller
1)
AB
AB
AB
Remote controller
Using the address switch (green) on the outdoor unit PCB, set the address of the outdoor unit in a range of 00 - 47 avoiding
duplication with any other outdoor unit.
Using the address switch (green) on the indoor unit PCB, set the outdoor No. at the same No. as the outdoor unit which is
connected with a refrigerant pipe.
Using the address switch (blue), set the indoor No. of indoor unit in a range of 00 - 47 avoiding duplication with any other
unit on the connection.
1065
FDC-HKXR
20.5.6 Test run
(1) Before starting operation
(a)
Measure resistances between the electrical parts terminal block and grounded area using a 500 V Megger, insulator.
Resistance must be higher than 1 MΩ.
(b)
Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hours to energize the
crankcase heater in advance of operation.
(c)
Make sure that the compressor bottom has been warmed.
(d)
Be sure to fully open the service valves (on both the gas and liquid sides) of the outdoor unit. If being operated without
opening, the valve may be got out of order.
Note (1) When the service valve is closed, be sure to check that evacuation is completed or a refrigerant is charged.
(2) Test run
(a)
If it is impossible, a test run of indoor units can be conducted by using the switches No. 4 and No. 5 of [SW-3] on
the outdoor unit circuit board irrespective of ON/OFF conditions of CnS and the remote controller.
No. 4 of [Sw3]
• All connected indoor units operate when the
switch is set to ON.
Test run
• Indoor units request the maximum frequency
and the outdoor unit operates with the maximum frequency shown in the table below according to requests from indoor units.
Normal
• Select cooling or heating according to input to
No. 5 of [SW3].
No. 5 of [Sw3]
• Turn this on makes it possible to conduct cooling operation when [SW3] No. 4 is turned on.
• When the switch is set to OFF, these units
can be operated with the remote controller
or by external input.
• Turning this off makes it possible to conduct heating operation when [SW3]’s No. 4 is turned off.
[Remark]
This operation has priority over other option commands with the center console.
At the time of trial operation, the maximum frequencies are follows. Protective devices are effectively controlled, and
frequencies are controlled to become smaller.
Models
Maximum frequency
for operation (Hz)
(b)
FDCP2001HKXRE2
FDCP2501HKXRE2
95
95
The frequency for operation can be monitored with yellow LEDs on the indoor unit circuit board. Relations between
LED lighting condition and frequency are as follows.
Notes (1)
Inverter frequency monitor
mark: Flashing
mark: Stays OFF
(2) Relation between LED3 ~5
LED3
and operation frequency
LED4
• LED3 .......... 40 Hz
LED5
• LED4 .......... 20 Hz
Operation
0 ~ 35
frequency
35 ~ 45
45 ~ 55
55 ~ 65
65 ~ 75
75 ~ 85
85 ~ 95 95 ~ 110
• LED5 .......... 10 Hz
• Operation frequency =
CAUTION: After end of a test run order, set No. 4 of [SW3] to OFF
Frequency indicated by
LED3 ~ 5 + 25
1066
FDC-HKXR
(3) Cooling test run operation (Cooling test run can be performed in winter.)
(a)
Operation method
● In the normal cooling mode, hold down the “Temperature Set” switch while pushing the “Set” switch.
● Setting temperature is changed at 5˚C and the cooling test run is operated for 30 minutes.
It stops after 30 minutes.
(b)
During cooling test run operation
● If ON/OFF switch is pressed or a mode other than the cooling is selected by the “Mode” switch, the cooling test run
operation is released or returns to the specified operation mode.
● If the “Temperature set” switch is pressed, the setting temperature changed at 18˚C and the cooling test run operation is
released but the cooling operation continues.
● It is effective when any switches other than the above are pressed.
(c)
During the cooling test run operation, the setting temperature changed at 5°C but any other control and protective
functions are operable just like in the normal operation.
● If any error occurs, the location of error is indicated on the remote controller display or with the condition of flashing of
inspection lamp (red) on the main unit controller. Remove the cause of trouble before starting operation again.
(4) Delivery
(a)
Explain how to operate the indoor unit to your customer according to the accessory owner’s manual.
(b) Persuade the customer not to turn off the power switch even if the unit is not used for along time. The
air conditioner can start operation any time when your customer want to heating or cooling his room.
(The bottom of the compressor is heated with the crank case heater, and compressor troubles can be
prevented when the cooling or heating season sets in.)
1067
FDC-HKXR
20.6. MAINTENANCE DATA
20.6.1 Diagnosis of Microcomputer circuit
(1) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection
display and normal display lamps on PCBs of indoor/ outdoor units
The microcomputer detects errors on electrical components, whitch include the microcomputer itself, errors on the power supply line
and errors (overload, etc.) on the refrigerant circuit and the location of trouble is displayed (with the combination of error symbols of
remote controller, normal (green) and inspection (red) display LED on PCBs of indoor/outdoor units.) When any error occurs, check
first the inspection display. It will guide you to the trouble point and assist you to complete the repair work quikly.
Error code of the remote controller is recorded on the microcomputer after the trouble has been reset automatically so that, if you
press the inspection switch of remote controller, the error code and the number of unit in trouble are displayed for 10 sec., The
inspection display lamp on the indoor/outdoor unit PCB keeps flashing (glowing) even after the trouble was reset automatically.
Inspection lamp on the indoor unit PCB is turned off if the remote controller is reset.
1) Inspection / normal: List of power display
Remote
controller
Section
Display section
LCD
At power ON: Displays always the return air temperature and Center/ Remote.
Error code
LCD
At error: Displays E1 ~ E46 or blank depending on the kings of error.
Indoor/outdoor
unit
Normal display
Error display
Normaly display
Inverters
Contents of display
Power supply display
Inspection display
1068
Display
Error display
Red-LED
Green-LED
Red-LED
Green-LD1
At error: Flash continuously (indicates the occurrence of error).
At power ON (normal): Flash continuously.
At error: Off or continuous glowing or irregular illumination.
At error: Flash 1 ~ 3 times/ 5 sec for indoor unit depending on the kinds of error,
continuous flash, irregular illumination or off.
At error: Flash 1 ~ 9 times/ 10 sec for outdoor unit. depending on the kinds of
error, continuous flash, irregular illumination or off.
At power ON (normal): Flash continuously
At error: off or continuous glowing or irregular illumination.
Red-LD2
At error: Lights when the power transistor overheats (for 3 minutes or more).
Red-LD3
At error: Lights upon occurrence of a current-cut (held for 3 minutes).
Red-LD4
At error: Lights when a transmisson error occurs between outdoor unit inverters.
1 time flash
Stays OFF
2 time flash
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
E11
E12
Keeps flashing
1 time flash
Keeps flashing
E10
E28
Stays OFF
Keeps flashing
E9
Stays OFF
Stays OFF
1 time flash
1 time flash
Keeps flashing
1 time flash
Keeps flashing
2 time flash
E7
Keeps flashing
2 time flash
3 time flash
Keeps flashing
Keeps flashing
32-sec time flash
Stay OFF or Lights
continuously
2 time flash
Stays OFF
Keeps flashing
Keeps flashing
3 time flash
Stays OFF
Stays OFF
Keeps flashing
Keeps flashing
Stays OFF
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Stay OFF or Lights
continuously
Keeps flashing
Keeps flashing
Stays OFF
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Stays OFF
Lights continuously
Stays OFF
Keeps flashing
Lights continuously
Red
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
32-sec time flash
6 time flash
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stay OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Outdoor unit LED
Green
Indoor unit LED
Red
Green
E6
E5
E3
E2
E1
No-indication
Remote
controller
error code
Remote controller thermistor failure
Outdoor No,
0 ~ 47
48, 49
Indoor No,
48, 49
0 ~ 47
Address No. combination error or addressing is performed with the following
combinations.
Remote controller addresses have been set while more than one units of remote
controller are connected.
When multi-unit control by remote controller is performed, the number of units is
over (more than 17 units). Two remote controllers are provided for one controller
is performed.
The float SW operates (with FS only). Drain up kit wiring fault.
Indoor unit return air thermistor failure
Indoor unit heat exchanger thermistor failure
Outdoor unit microcomputer failure
Indoor/outdoor transmission error. Wire A and B swapping after power ON.
The corresponding outdoor unit address No is not found. (Detected only during
opreation) Indoor/outdoor signal line wire breaking Indoor unit PCB fault.
Outdoor unit power supply OFF (detected only during operation)
No. duplication at remote controller addressing
No. duplication at indoor unit addressing. More than 49 indoor unit are connected.
The PAC remote controller is connected to the KX. The remote controller wire Y is
open. The remote controller wires X and Y are reversely connected. (The LED
flash twice a second.) Two remote controllers are provided.* For wire breaking at
power ON,the LED is OFF.
Indoor unit PCB fault
The remote controller wires are connected to A and B on the terminal block.
The indoor/outdoor signal wire are connected in loop form. The indoor unit
microcomputer runs away.
Remote controller wires X and Y are reversely connected.* For wire breaking at
power ON, the LED is OFF. Remote controller wire is open. (X wire breaking: A
beep is produced and no indication is made. Z wire breaking: No beep and no
indication) The remote controller wires Y and Z are reversely connected. (32-sec
time flash)
Power OFF, L3 phase wiring is open, power source failure
Indoor unit PCB fault, CPU runaway
Normal
Cause
2) Check Indicator Table
Whether a failure exists or not on the indoor unit and outdoor unit can be known by the contents of remote controller error code, indoor / outdoor unit green LED (power pilot lamp and
microcomputer normality pilot lamp) or red LED (check pilot lamp).
FDC-HKXR
1069
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
E31
E34
E36
E37
E38
E39
E40
1070
E41
E42
E43
E45
E46
Stays OFF
7 time flash
9 time flash
1 time flash
4 time flash
3 time flash
Keeps flashing
Keeps flashing
Keeps flashing
5 time flash
2 time flash
8 time flash
Red
Automatic address setting and remote controller address setting or manual address
setting coexists in the same network.
The number of connectable units is exceeded.
Transmission error between inverter and outdoor unit PCB
Abnormal current cut of compressor (CM1)
Power transistor overheat
63H1 operation
Discharge temperature thermistor failure
Outside temperature sensor failure
Outdoor unit heat exchanger thermistor
failure
Discharge temperature abnormality.
52C secondary side L3-phase wiring is open. Inverters error.
Outdoor unit No. duplication. Outdoor unit address No. is not set for super lynk
wiring. Outdoor unit address No. is changed in the power ON status.
Cause
1.
2.
4.
Outdoor No.
3.
Outdoor No.
Outdoor No.
5.
6.
Then, remote controller address setting can be performed.
Turn off the indoor and outdoor power supplies, and set the address switch on the PCB of the outdoor unit to any of 0 to 47. After setting, turn on the indoor and outdoor power supplies.
The above shows the case of remote controller address setting. There is a unit for which the address switch on the PCB of the outdoor unit connected on the same network is set at "49".
(2) When the following displays (6 patterns) coexist:
at once by pressing the operation switch.
abnormality occurs on only a unit. In this case, the remote controller for the unit in which a drain abnormality occurred does not indicate the failure but stops. It is also stopped
Notes (1) Even if an abnormality occurs in a part of indoor units, outdoor units continue to operate. However, in case of a drain abnormality, the outdoor units stop even when an
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Green
Red
Outdoor unit LED
Green
Indoor unit LED
Remote
controller
error code
FDC-HKXR
FDC-HKXR
3) Display sequence of error, inspection display lamp
a) One kind error
Display corresponding to the error is shown.
b) More than one errors.
Section
Error code of remote controller
Display section
• Displays the error of higher prority (When plural errors are persisting.)
Inspection LED(red) of indoor unit
PCB
Inspection LED (red) of outdoor unit
PCB
••••••
• Displays the present errors.
(When a new error has occurred after the former error was reset.)
c) Timing of error detection
• Indoor unit side.
Error detail
Error code
Timing of error detection
Transmission error of remote controller
indoor unit
When the transmission error continuously for 2 min.
CPU is out of control
Resetting was performed at the rate of 1 time per second. An abnormal
stop occurred 120 times running.
Transmission error between
indoor/outdoor units
A check was made once every 20 second. An abnormal stop occurred 7
time running.
Broken wire of heat exchanger
thermistor
After a compressor ON command, this failure was detected for 5 second
in the period of 2 minutes to 2 minutes and 20 seconds.
Broken wire of indoor unit return air
thermistor
This failure was detected continuously for 5 seconds.
Drain error(float switch motion)
At the thermostat ON state, an abnormal stop occurred immediately after
the float switch operated.
- At a stop or the thermostat OFF state, the condensate motor was turned
on for 3 minutes after the float switch operated.
After that, an abnormal stop occurred when the float switch operated in
10 seconds.
1071
FDC-HKXR
• Outdoor unit side
Error detail
Error code
Timing of error detection
52C secondary side L3-phase wiring is open.
An abnormal stop occurs when the L3-phase voltage is 0 V for 5 seconds running.
(Detected with 52C ON only)
Discharge temperature abnormality
A stop occurs when this abnormality occurs for 2 seconds running at 130°C
After a stop for 3 minutes, an recovery is automatically made.
An abnormal stop occurs when this abnormality occurs twice for 60 minutes.
(The abnormal state is held for 45 minutes.)
Broken wire of heat exchanger thermister
Broken wire of outdoor temperature
thermister
This failure is detected when it occurs for 5 seconds running in the period of 2
minutes to 2 minutes and 20 seconds with the compressor ON. An abnormal stop
occurs when this failure occurs 3 times for 40 minutes.
Broken wire of discharge thermister
This failure is detected when it occurs for 5 seconds running in the period of 10
minutes to 10 minutes and 20 seconds with the compressor ON. An abnormal stop
occurs when this failure occurs 3 times for 40 minutes.
Hight pressure cut
An abnormal stop occurs when this abnormality occurs 2 times for 40 minutes.
Power transistor overheat
A stop occurs at 90°C or more. After 3 minutes, a recovery was automatically
made at 83°C or less. Abnormal stop occurs when this abnormality occurs 2 times
for 2 hours.
Current cut
An abnormal stop occurs when this abnormality occurs 4 times for 15 minutes.
Excessive number of outdoor units
This error is detected when the number of connectable units is set over the
specified value at remote control addressing.
Transmission error between inverter and
outdoor unit PCB
When an transmission error continues for 10 seconds, the 52C is turned off. With
a delay of 3 minutes, a recovery is automatically made. An abnormal stop occurs
when this error occurs 4 times for 15 minutes.
d) Recording and reset of error
Error display
Error code
Indoor unit
lamp (red)
Reset
Memory
• Saves in memory the mode(1) of • Stop the unit operation by pressing the ON/OFF switch of
higher priority
remote controller.
•
Operation
can be started again if the error has been reset.(2)
inspection • Cannot save in memory
Outdoor unit inspection • Saves in memory the mode(1) of
higher priority
lamp (red)
Notes (1) Priority is in the order of E1 > ... > E10 > ... > 45.
(2) Reset is disabled for 45 min. at the error of outdoor unit or compressor overcurrent or the discharge gas temperature
error.
e) Reset of error code in memory (when the error has been reset.)
Indoor unit: Press the Timer switch and the Stop switch while the Inspection switch of wired remote controller is held
down or detach the power supply connector (CnW2) of indoor unit PCB and connect again or turn OFF the power.
Outdoor unit: Detach the power supply connector (CNA2) of outdoor unit PCB and connect again or turn OFF the power
supply or turn on and off the SW3-1.
(2) Procedures of trouble diagnosis
When any error occurs, inspect in following sequence. Detailed explanation on each step is given later in this text.
Error
Power supply check
(indoor/outdoor unit)
Replacement or repair of defective
parts Test run/adjustment
Check of inspection display [Indoor/outdoor unit PCB, remote
controller or Indication board]
Check of unit
controller
Power supply reset (1)
Check of inspection display [Indoor/outdoor unit PCB, remote
controller or Indication board]
Note (1) It means the operation to turn off the power and back on again more than 1 min. later in order to reset the
malfunction of microcomputer due to the effect of power supply conditions or accidental noise.
1072
FDC-HKXR
(a) Diagnosis by the power supply reset
When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc.
Check at the indoor unit side.
Error
Are the return air
temperature and Center/
Remote displayed on the
remote controller?
YES
Is any error
code display?
NO
NO
YES
Check the error
code displayed
Power switch OFF
Power supply line error
ON/OFF
switch OFF
Does the error
code disappear?
NO
Microcomputer
out of control
YES
Turn off the wiring breaker (power
supply) and back on again 1min. later. (Power supply reset)
ON/OFF
switch OFF
Does start operation
with display of cooling degree: Hi, thermostat: 23°C?
NO
Power supply line error
See page 1077
YES
Does the error repeat
NO
Cause is accidental (noise, etc.)
and the unit is normal.
YES
Check of error code
Errors due to external noise, etc.
Error code may be displayed or the error may not be displayed normally even if the controller is normal because of external noise
source(1) or joined or parallel arrangement of power cables and signal wires. It is because the wire of remote controller, wired
remote controller signal wires for multiple units or the network signal wires may be influenced by external noises whitch are
judged as signals by the microcomputer whitch reacts mistakenly.
When there is any noise source, it is necessary to the shield wire for the remote controller and signal wires.
Note (1) High frequency medical machine, rectifier motor application device, thyristor, broadcast transmission tower, power
transmission line, power line of electric train, automatic door motor, elevator (voltage drop), wireless telephone, high
voltage power distribution line, computer, personal compouter and their cables.
There do not necessarily always cause problems but they can be a source of electrical noise.
1073
FDC-HKXR
(2)
Reference Effect of noise
• When noises inturude into the remote controller.
Abnormal or irregular display such as the flashing of irrelevant display (lamp) (for example, LEDs of cooling and heating
illuminated simultaneously or the like) is observed even if the remote controller is not operated or the remote controller and,
as the result, the operation of units may be disabled or similar abnormal phenomenons are observed.
• When noises intruded into the microcomputer of printed circuit board; State of operation becomes abnormal such as the units
perform irregular operation while the remote controller is not operated, the operation cannot be stopped with the remote
controller, etc.
Electro magnetic noise prevention(example)
• Cover the entire surface of control box or
the inside of unit cover with the cover foil
or cover the enitre unit with a wire net.
Use the shield or
twist pair wires
Interisified shielding
of control section
Signal wire
Make a positive
ground
Remote controller wire
(Indoor unit)
Outdoor
unit
(Indoor unit)
l2
Shut off electrically the
noise source or put it in
a shield room.
Beware of noises
transmitted via air.
Cutting machine
welder High
frequency
l1
Put in a steel case Remote controller
Separate from cutting machine as for as
possible. This is very effective because
the effect of noise is in inverse
proportion to 1.5 times of distance.
•Insert in a steel pipe to shield.
Power
cable
Unless it has a sufficient current
capacity, mini split current drops
momentarily at the start/stop of
cutting machine.
Distribution
board
Avoid supply from the same
distribution board to prevent troubles
by the power source propagation.
Install the line filter at the power
supply of cutting machine of mini split
(Positive grounding is necessary.)
(b) Eroor diagnosis procedures at the indoor unit side
The error diagnosis for indoor units is the same as for the Multi KX Series. For details, please refer to the section for the KX
Series found on pages 910 to 917.
(c) Error diagnosis procedures at the outdoor unit side
At the error diagnosis related to the outdoor unit, check at first the error code of remote controller and the illumination patterns of
norma l and inspection display lamps in the same manner as the case of indoor unit.
Then estimate the outline, the cause and the location of error based on the pattern and proceed to the inspection and repair. Since
the self diagnosis function by means of the microcomputers of indoor/outdoor units provide the judgement of error of
microcomputers them selves irregularity power supply line, overload, etc. caused by the installation space, inadequate volume of
refrigerant etc., the location and cause of trouble will be discovered without difficulty.
In addition, the display lamps error code of indoor/outdoor units is kept flashing, (except when the power supply is
interrupted)after the irregularity is automatically recovered to give irregularity information to the service presonnel. If any mode
of higher priority than the error retained in memory occurs after the reset of error, it is switched to that mode and saved in the
memory.
(i) Replacement parts assembly related to the outdoor unit PCB
Outdoor unit PCB, outdoor unit inverter PCB, power transistor module, diode module, capacitor, reactor, noise filter, thermistor,
1074
FDC-HKXR
(ii) Parts layout on the outdoor unit PCB
Operation output
18
17
16
19
20
23
• Function of DIP switch
CNH 2
Name
CNY(White)
2
CNI(White)
L6
7
2
L9
ON
IC4
SW2
CNE(White)
X1 9 83
ON
External input
SW3-2
Outdoor unit
number address
setting switch
(SW: Order of 1)
OFF
ON
SW3-3
OFF
Outdoor unit
number address
setting switch
(SW: Order of 10)
Name
ON
Checker
6
IC3
SW
Test
Forced
Heat Cool
Trial
Snowing
Defrosting
Reset
J3
J2
J1
OFF
L7
L8
L10
IC8
IC5
C5
R17
R18
IC10
+
+
52×4
SK7
R15
R16
R9
PC5
IC13
SW1
ON
SW3-1
Failare
SW3-4
IC7
IC9
C8
52×7
OFF
SK8
ON
SW3-5
2
CNB(Red)
2
CND(Yellow)
2
CNU(Blue)
2
CNC(Black)
C4
ZNR
+
IC2
CNA1
−+
∼
−
+ +
DS217V
3
IC14
C1
2
ZD3
ZD2
ZD4
ZD5
3
CT
8V1
−
C3
200V
DS1
DS3
+
VR1
IC15
IGø
ICI
øGI
OFF
Reference
page
Trial
operation
1042
Regular
operation
Cooling
trail operation
1042
Heating
trail operation
OFF
Regulat
operation
ON
Test mode
OFF
Regular
operation
• Function of jumper wires
Model
Serial
4
CNA2
PCB power supply connector
(Secondary side)
PCB power supply connector
(Primary side)
Function
Compulsory
operation
Thermistor
SW3-7
Function Reference
page
Check LED
reset
Normal
operation
Easy to start
defrosting
1037
Normal
operation
Measure
against
snow
1039
Normal
operation
ON
SW3-6
CNX(White)
IC6
C9
R19
C10
52×1
SK1
+
R20
C6
+
C12
4
+
C13
C11
52×2
ZD1
52×3
SK3
+
SK2
5
+
C23
C19
C18
IC12
10
9
C20
R8
PC4 R10
R5
PC3 R7
R3
PC2 R6
R2
R1
PC1 R4
C17
~
S OUT
GND
52×14
SK4
8
~
IC11
C15
6
52×13
SK6
7
~
52×12
SK5
11
~
52×11
SK10
12
C16
~
SK11
13
52×9
SK13
52×10
5V
CNS(Black)
SK9
52×8
12V
15
J1
J2
J3
FDCP2001
With With None(1)
FDCP2501
With With None(1)
Note (1) “None” means that jumper wire
is not provided on the PCB or
the connection is cut.
• Replacement procedure of indoor unit microcomputer printed circuit board
Microcomputer printed circuit board can replaced with following procedure.
1) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of pats number.)
Model
Parts No.
FDCP2001, 2501HKXRE2
PCB505A012L
Notes (1)
Inverter frequency monitor
(2) Relation between LED3~5
LED3
and operation frequency
• LED3......40Hz
LED4
• LED4......20Hz
LED5
Operation
frequency 0~35
mark: Flashing
mark: Stays OFF
• LED5......10Hz
35~45
45~55
55~65
65~75
75~85
85~95
95~100
• Operation frequency =
Frequency indicated by
LED3~5 + 25
1075
FDC-HKXR
(iii) Check procedure depending on indication lamps (For the outdoor unit)
1
[Error on the outdoor unit signal line]
Error display:
(Detected during operation only)
Indoor unit
Red LED
2 time flash
Green LED
Keeps flashing
Outdoor unit
Red LED
Stays OFF
Green LED
Stays OFF
Power supply
checked between R~N or
terminal block
YES
Is there
AC 17V checked
between CNA2 (blue) ~ (blue)
and AC 8V between (red)
~ (red) of outdoor unit
transfomer?
YES
Power supply
reset
Is it
YES
Normalized?
NO
NO
Power not supplied.
Power supply wiring
error→Repair.
NO
•Blown fuse (3.15A) →Replacement
• Defective transformer→
Replcement
• Broken power supply wire in
the unit Repair
Defective outdoor
unit PCB
Outdoor unit
Red LED
Green LED
Stays OFF
Is the pairing of
Indoor/outdoor units OK?
Keeps flashing
NO(1)
Change of unit number setting
Note (1) NO outdoor unit corresponding to the indoor
unit.
1076
YES
Is the connection
of network signal
wires good?
NO
Repair the door connection, broken wire of
network signal wires.
Unit is normal
FDC-HKXR
2
[Outdoor unit signal line error, power supply error]
Error display:
Indoor unit
Red LED
2time flash
Green LED
Keeps flashing
Outdoor unit
Red LED
Stays OFF
Green LED
Stays OFF
(1)
Did turn off
the power of outdoor
unit during
operation?
YES
Power supply
ON
NO(1)
• Blown fuse?
• Broken or loose wire at L1, L2 or N
Phase?
• Was not there the power failure?
Note (1) This case is limited to the separate power supplies to indoor/outdoor units. (Combination of (indoor unit) red LED 2
time flash and (outdoor unit) green LED stays off means that the power supply to the outdoor unit has been
interrupted during operation.)
Outdoor unit
Red LED
Stays OFF or
keeps flashing
Green LED
Stays OFF or
Lights continuously
Power supply reset
Is it
normalized?
Malfunction due to noise, etc.
(Out of control CPU of outdoor
unit due to noise during power on)
YES
NO
Defective outdoor unit
PCB→Replacement (Defective network communication circuit)
(1)
Outdoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Signal wire poor
connection at outdoor
unit?
YES
Repair
NO
(2)
Signal wire poor
contact between indoor/
outdoor units?
YES
Repair
NO
Power supply reset
Notes (1) Check for poor connection (Iooseness, misconnection) at outdoor unit terminal block
and broken signal wires between outdoor
units.
(2) Check the poor connection or broken signal
wires between indoor/outdoor units.
Is it
normalized
YES
Unit is normal.
(Malfunction by
accidental noise)
Defective outdoor unit
PCB→Replacement (Defective network communication circuit)
1077
FDC-HKXR
3
[Duplicated unit No. of outdoor units]
Error display:
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Red LED
Green LED
Is the unit
No. duplicated on
outdoor units?
YES
Outdoor unit
8 time flash
Keeps flashing
Correction
NO
Defective outdoor unit PCB
Replacement (Defective unit
No. read circuit)
4
[Open phase at L3 phase of 52C secondary side (CM2)]
Error display:
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Note (1) When the PCB is defective, the flash patterns of outdoor
unit red LED, green LED may become irregular.
Red LED
Green LED
Outdoor unit
2 time flash (1)
Keeps flashing
(1)
YES
52C secondary side L3
phase open?
Notes (1) When voltage is detected at 52C primary side but not at the
secondary side, check also 52C (broken coil, poor contact).
(2) When voltage is detected at 52C primary side L3 phase and
there is no error at 52C, the outdoor unit PCB (defective
52X01 circuit or 52X01 ) or indoor unit PCB (defective
thermostat circuit) is defective.
Repair
NO
(2)
Defective outdoor unit PCB
Replacement
(Defective CT circuit)
5
[Discharge temperature error]
Error display:
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Is the
discharge gas thermistror characteristics
normal?
YES
Red LED
Green LED
Discharge gas
temperature error?
(At cooling/heating
operation)
Outdoor unit
5 time flash (1)
Keeps flashing
Check the unit side.
• Insufficient refrigerant
Charge the refrigerant (measure)
• Is it the oveload operation?
NO
Discharge pipe thermistor replacement
Is the unit
normalized
Error stop
Operable
NO
Defective outdoor unit
PCB
Replacement
(Defective discharge gas
thermistor input circuit)
1078
90ºC 130ºC
Discharge pipe temp.
Check the unit side.
• During cooling: Is FM0 operating?
• During heating: Is FM1 operating?
Are service valves (both liquid,
gas) fully opened during both
cooling and heating.
• Is the installation space of indoor/
outdoor unit adequate?
• Is there any short circuit air flow
for indoor/outdoor units?
FDC-HKXR
6
[Defective outdoor unit heat exchanger thermistor]
Error display:
Outdoor unit
Indoor unit
Red LED
Stays OFF
Green LED
Keeps flashing
Is the outdoor
unit heat exchanger
hermistor connector
OK?
YES
Red LED
Keeps flashing
Green LED
Keeps flashing
Are the outdoor
unit heat exchnger thermistor
characteristics OK, is there
any broken wire?
NO
YES
NO
Defective outdoor unit PCB →
Replacement (Defective outdoor
unit heat exchanger thermistor
input circuit)
Outdoor unit heat exchanger
thermistor (ThO-R) Resistance
temperature characteristics
Defective outdoor unit
heat exchanger thermistor
→ Replacement
15
Resistance (kΩ)
Repair
10
5k Ω at 25°C
5
0
10
20
30
40
50
Temperature (°C)
[Defective outdoor temperature thermistor]
Error display:
Outdoor unit
Red LED
Stays OFF
Green LED
Keeps flashing
Is the outdoor
air temperature thermistor
connector connection
OK?
NO
Repair
YES
Red LED
Keeps flashing
Green LED
Keeps flashing
Is the outdoor
temperature thermistor
characteristics OK, is there
no broken wire?
YES
Defective outdoor unit PCB →
Replacement (Defective outdoor
temperature thermistor input
cicuit)
NO
Defective outdoor
temperature thermistor
→ Replacement
400
Temperature-resistance
characteristics of outdoor
temperature thermistor (ThO-A)
300
200
40
30
T < 0°C
20
T > 0°C
100
0
-50
10
0
50
Temperature [T] (°C)
Thermistor resistance (kΩ) [T > 0°C]
Indoor unit
Thermistor resistance (kΩ) [T < 0°C]
7
0
1079
FDC-HKXR
[Defective discharge gas thermistor]
Error display:
Outdoor unit
Red LED
Stays OFF
Green LED
Keeps flashing
Is the
discharge gas thermistor
connector connection
OK?
Red LED
Keeps flashing
Green LED
Keeps flashing
Are thr discharge
gas thermistor characteristics
OK, is there no
broken wire?
YES
NO
NO
Defective discharge gas
thermistor → Replacement
Repair
9
T<
= 80°C
5
50
0
0
Stays OFF
Keeps flashing
Red LED
Green LED
20
50
80 100 120
Temperature [T] (°C)
3 time flash
Keeps flashing
At 63H1 operation
Did 63H1, operate?
NO
Defective outdoor unit PCB →
Replacement (Defective 63H1,
input circuit)
YES
1. During cooling
• Is the outdoor unit fan motor operating?
• Is there no short circuit air circulation for the outdoor
unit?
• Is there sufficient space for air inlet & outlet?
2. During heating
• Is the gas side service valve fully opened?
• Is the indoor unit heat exchanger thermistor detached
from the detector case?
• Is the filter clogged?
• Is the outdoor unit fan controlled by due to defective
63H2?
3. During colling / heating
• Is the refrigerant charge excessive?
Note (1) When the wire of 63H1 is broken from the moment of power on, the error E 40 is displayed 40 minutes later.
If the operation is started in this period of time, the operation changes to the thermostat OFF state during cooing,
and cool wind blow stops during heating operation.
1080
10
T>
= 80°C
Outdoor unit
Indoor unit
Green LED
100
Temperature-resistance
characteristics of discharge
gas thermistor(ThO-D)
[63H, motion]
Error display:
Red LED
Defective outdoor unit PCB →
Replacement (Defective discharge gas thermistor input circuit)
YES
0
Thremistor resistance (kΩ) [T >
= 80°C]
Indoor unit
Thremistor resistance (kΩ) [T <
= 80°C]
8
FDC-HKXR
10
[Power transistor overheating]
Error display:
Outdoor unit
Indoor unit
Red LED
Stays OFF
Green LED
Red LED
Keeps flashing
Does
the
FMO
rotate?
YES
Power transistor
overheating(1)
4 time flash
Green LED
Keeps flashing
Is the
outdoor unit
installation
space
proper?
YES
NO
Does the
IM (Inverter
cooling fan)
rotate?
YES
NO
YES
Defective
inverter
(Refer to 1090 page)
NO
Repair
Note (1) The LD2 on the inverter control PCB lights for 3 minutes. Fin thermostat set value: 90°C open/83°C close
11
[Current cut]
Error display:
Outdoor unit
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
Green LED
1 time flash
Keeps flashing
Remarks: When current-cut occurs immediately after a start (the Hz value does not increase), check the LD3 on the inverter PCB if an error
code is not indicated on the remote controller and the compressor does not operate. When this LD3 is ON, see the next page.
Is the current
(U,V,W) of the
compressor at the
normal level?
YES
NO
• Is the power supply voltage
correct (not too hight)?
• Are the power supply wires
oppropriate(not too thin)?
• Is not it operated under
overload
• Isn't the compressor locked?
• Is the insulation or winding resistance of the
compressor motor proper?
• Is the electronic expansion valve closed?
• Is the installation space of indoor/outdoor unit
adequate?
• Is there any short circuit on the indoor/outdoor
unit
• During cooling: Is FMO operating?
• At heating:
• Is FM1 operating?
• Is the service valve (gas side) opened fully?
• Is the filter clogged?
YES
Power supply
reset
NO
Defective
inverter
(Refer to 1090 page)
YES
Unit is normal
(Malfunction by
accidental noise)
Notes (1) The LD3 lights for 3 minutes.
(2) For details of the check procedure, see the next page.
1081
FDC-HKXR
Current cut is indicated and the compressor cannot operate
Is the insullaiton
resistance of the compressor(1)
proper?
Disconnect the compressor wiring
NO
Defective compressor
YES
The compressor can operate
Is the current
cut function activated?
Notes (1) When a short-circuit or ground-fault occurs
in the compressor motor, the current cut
function is also activated.
Notes (1) If the insulation resistance is 10MΩ or more,
it is normal.
Notes (1) The insulation resistance may considerably
drop depending on the refrigerant volume in
the compressor, but this is not faulty.
(2) 1-2 seconds after a start:
FDCP2001 type: Approx. 32 A
FDCP2501 type: Approx. 37 A
YES
Defective inverter
(Refer to 1090 page)
NO
Is the output
voltage of the inverter
normal?
NO
Defective inverter
(Refer to 1090 page)
YES
When the compressor wiring is
performed, the unit can operate.
Isn't the stating
current(2) excessive?
YES
Defective compressor
NO
Defective inverter
Inverter output voltage
Frequency
Unit: V (AC)
35 Hz
40 Hz
65 Hz
75 Hz
80 Hz
95 Hz
Model
All models
(outdoor unit)
1082
95 ~ 98
104 ~ 107 167 ~ 173 180 ~ 190 195 ~ 197 198 ~ 203
FDC-HKXR
12
[Excessive number of indoor units connected]
Error display:
Outdoor unit
Indoor unit
Red LED
Stays OFF
Green LED
Red LED
Keeps flashing
7 time flash
Green LED
Keeps flashing
(1)
Doesn't the number
of indoor unit connected exceed
the specified
value?
YES
Repair
Notes (1) The maximum number of connectable unit of each model is as
follows: 9.
(2) Outdoor No. setting check for indoor units (to see if outdoor No. is
of other system)
(3) In case of auto addressing erase the
addresses stored in memory and
perform re-setting.
NO
Power supply reset
Is it
normalized
YES
Defective indoor outdoor
unit PCB → Replacement
NO
Unit is normal
(malfunction by
accidental noise)
13
[Transmission error between inverter and Outdoor unit PCB]
Error display:
Check that the 52C is ON. With the 52C ON, power is supplied to the inverter PCB.
Outdoor unit
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
9 time flash
Green LED
Keeps flashing
Does the
LD1 (Green) on the
inverter PCB
flash?
NO
NO
• Defective inverter PCB
• Defective outdoor unit PCB
The inverter PCB cannot receive signals
YES
Does the LD4
(red) on the inverter PCB
light? (2)
Is the
power supply
line normal?
YES
Defective inverter PCB
NO
Repair
NO
• Defective inverter PCB
• Defective outdoor unit PCB
• Broken Cnl in No.5 (See next page)
- The outdoor unit PCB cannot receive signals.
- The inverter PCB cannot send signals.
- The watch dog signal cannot be taken.
Notes (1) Make a check referring to Troubleshooting for Inverter (page 1090).
(2) When receiving fails, the LD4 comes on at once. If the outdoor unit cannot receive signals for 10 seconds, the 52C is turned OFF.
Accordingly, the ON state can be checked only in this period of 10 seconds.
1083
FDC-HKXR
• When communication is checked by the connector CnI, each value will be as follows.
Contents of communication
Connector
CnI
14
1
Common
2
12V power supply
3
Transmission from outdoor unit
4
Reception from outdoor unit
5
Watch dog (communication from inverter PCB to outdoor unit PCB)
6
Inverter overheat
7
Current cut
12V
Green LED
Swings at 4.5~5V
Outdoor unit
Stays OFF
Red LED
Keeps flashing
Are automatic
address and manual address
coexstent on the same
network
Green LED
YES
Stays OFF
Keeps flashing
Repair to manual address
NO
Defective outdoor unit
PCB → Replacement
(d) How to advance checks for each faulty symptom
(i) Inspection method when there is no error display
1)
Four way valve does not switch during heating operation
Power supply
detected between outdoor
unit terminal 5 ~PCB
faston terminal 6
(black)?
NO
Defective outdoor unit
PCB → Replacement
1084
YES
Swings at 2~4V
5V: normal
0V: abnormal
Indoor unit
Red LED
Swings at 11~11.5V
[Automatic address setting and manual address
setting coexstents in the same network]
Error display:
V(analog tester)
0V
Defective 20 S →
Replacement
FDC-HKXR
2)
Louver motor does not operate
Inspect at the indoor unit side.
Does the
louver operate at
power on?
Operate more than
1 min. later
NO
Is LM wire
bloken?
YES
NO
Is LM
locked?
Defective indoor
unit PCB
YES
YES
Replace LM
Repair the wire
Is the louver
YES
operated with the remote
controller
NO
Normal
NO
Note (1) LM:Louver motor
LS:Limit switch
It is normal
if it stops with
2 pushes on LS
Turn off and back on again
the power and check the
motion of LS
Does the louver
link push the LS till
a click sound is
heard?
NO
Adjust LS lever and
check again
YES
Defective LS →
Replacement
Defective indoor unit PCB
→Replacemet
3)
When the indoor unit blower does not operate
Inspect at the indoor unit side.
All of cooling,
blower heating,thermaldry
do not operate
When some modes only
operate.
NO
Defective indoor unit PCB →
Replacement
YES
Check with the Hi, Me, Lo of
blower mode.
Check FMI
Is Voltage detected
between CNF
terminals?
NO
Defective indoor unit PCB →
Replacement
YES
Defective FMI, capacitor
(CF I) → Replacement
1085
FDC-HKXR
4)
Heating operation does not start
NO
Is heat
outputted?
Defective indoor unit PCB → Replace.
YES
(1)
Are solenoid
valve control relays
OK?
NO
Defective relay → Replace.
YES
Is AC 200V applied
at shunt controller connector
CnB?
YES
Defective SVH (high
pressure gas side solenoid
valve) → Replace.
1086
NO
Defective relay (XH) → Replace.
Note (1) This is applicable only when a concentrated
shunt controller is used.
FDC-HKXR
(3) When the remote controller indication is nomal but the compressor cannot operate:
(No check indication)
• Give instructions so that the requested best frequency may be output,
irrespective of the thermostat condition, from outdoor to indoor. A ccordingly, if the indoor/outdoor transmission is faulty, the compressor cannot
operate.
• When the SW3-4 is turned on, error indication is not provided if the indoor
unit is not connected.
At remote controller operation, check if E3 (no mate) or E5 (transmission
error) is indicated.
Turn on the SW3-4 on the outdoor unit PCB
(See page 1075)
NO
Do voltage appear at
the 52C coil?
Is the 52C turned ON?
YES
YES
Defective 52C → Replacement
NO
Defective outdoor PCB
Can the compressor
operate?
YES
Continued from
the next page
• Is the indoor unit suction thermistor
nomal?
• Doesn't the thermistor stop?
NO
Does the LD1 (green) on
the inverter PCB blink?
NO
Defective inverter PCB
(See page 1091)
YES
Turn off the SW3-4 on the outdoor unit PCB
Strap the connector Cn15 on the inverter
PCB(1)
Full load to command an unconditonal
35Hz operation from the inverter PCB
Turn on the 52C forcedly
(Manual operation)
Can the
compressor operate
YES
Defective outdoor unit
control PCB
NO
Does a voltage
appear at U.V and W of
the compressor?
NO
Defective inverter PCB
(See page 1091)
YES
Defective compressor
Notes (1) The expansion valve of the indoor unit may be closed or the indoor unit fan may stop. After the compressor is operated, stop it at once.
Otherwise, this will cause a failure to the compressor.
(2) The next page shows a checking procedure using only the outside unit.
1087
FDC-HKXR
(4) Proceduer for checking the outdoor unit irrespective of indoor/outdoor transmission
Turn off the outdoor unit power supply
(Or pull out the connector CnA2 on the outdoor unit PCB)
Set 45 in outdoor unit No.
Turn ON the outdoor unit PCB(SW3-7)
Turn ON the outdoor unit power supply
Open the 63H1
Is the 52C
turnd ON?
(When connecting the CnA2 on the outdoor unit PCB)
(Pull out Faston No.17 on the PCB)
NO
Does a voltage
Appear at the 52C coil.
YES
Defective 52C
NO
YES
Defective outdoor unit PCB
YES
Can the compressor
operate at 35Hz?
Defective outdoor unit PCB or
indoor unit PCB
NO
Turn OFF the outdoor unit power supply
Return outdoor unit NO. to the installation state.
1
(Continued to the previous page)
Note (1) When using this procedure, the indoor unit enters a transmission error state. In the indoor unit the expansion valve may be closed or
the fan may stop.
Note( 1) After the compressor is operated, stop it at once.
Note (1) Otherwise, it will cause a failure to the compressor.
1088
FDC-HKXR
(5) Procedure for checking the inverter (No output is provided at the compressor (U,V and W).)
NO
Is the
52C ON?
Check the control PCB on
the outdoor unit side
NO
Power line failure
NO
Does the LD1
(green) on the inverter
PCB flash?
Does DC280V
appear at the connector
Cn2 on the inverter
PCB
NO
(3)
The remote controller error
code E45 is indicated
(See page 1083)
YES
YES
Turn OFF the power supply and pull
out the connectors Cn13 and 14
Defective inverter PCB
Turn ON the power supply
Does DC1.5~1.6V
appear at the connectors
CN13 an 14 on the
inverter PCB?
(1)
YES
NO
Defective inverter PCB
(2)
Defective power transistor
Notes (1) Cn13 and Cn14 check points
Tester bar
+
Cn13-7
Cn13-6
Cn13-11
Cn13-10
Cn13-15
Cn13-14
Cn14-1
Cn14-4
Cn14-2
Cn14-5
Cn14-3
Cn14-6
Voltage
1.5~
1.6V
(2) Check the wirng between the power transistor
module and inverter PCB. If it is normal,
judge that the power transistor module is
fauly.
(3) The 52C turns on, then turn off in 10 seconds.
This is repeated 3 times and E45 is indicated.
(iii) Cooling(heating) effectiveness is low. (Check the refrigerant volume and refrigerating cycle in addition to
the following items.)
1) For low cooling effectiveness
a) Check if the protective function operates with the result that the operating frequency of the compressor goes below the
specified frequency value.
Note (1) When the current safe control and discharge temperature control are activated, the frequency is lowered.
b) Check if the operation of the indoor unit expansion valve is normal or there is no clogging.
c) Check if the anti-frost function operates.
Procedure for Checking Indoor unit Electronic Expansion Valve Operation
Check the indoor unit controller to expansion valve output according to the following procedure.
Measure the voltage value appearing at the pin on the control side of the expansion valve (SM) connector CnA (white, 6P
(5-conductor), and also the duration of voltage application.
Orange~Gray, Yellow~Gray
Approx DC5V(2) for 15 seconds(1) when the power supply is turned on.
Red ~Gray, Black ~Gray
Notes (1) After the power supply is turned on, the voltage is about 5 V for 8 seconds, decreases momentarily, and then is kept
at about 5 V for about 7 seconds.
(2) When a measurement is made with a digital multitester, voltages of 6-3 V are output in sequence.
}
When the above duration and voltage value can be verified, the indoor unit controller is normal.
If the expansion valve does not operate (no operating sound is produced) though a voltage is provided, the expansion valve is
faulty.
By changing the setting of the thermostat, the expansion valve is operated in about 20 seconds. Like the above, a DC voltage
of about 5 V can be checked at the connector CnA.
2) Low heating effectiveness.
a) Check if the operating frequency of the compressor is lowered below the specified frequecny because the protective
function is activated.
Note (1) When high pressure control [63H2 ON: 2.26 open/2.84 closeMPa (23 open/29 close kgf/cm2)], current safe
control and discherge temperature control is exerted, the frequecny is lowered.
b) Check if the operation of the outdoor unit expansion valve is normal, or if any clogging occurs.
1089
FDC-HKXR
◆ Troubleshooting on the inverter side
(1) Troubleshooting procedure (For the details of 1 to 7, refer to Outfoor Unit Check Pointd on the next page.)
NO
Check the outdoor unit
control PCB.
NO
Is DC280V is
YES
provided at the Cn2 on
the inverter PCB?
Is 52C turned ON?
Does
the LD1 (green)
on the inverterYES
PCB
flashing
YES
Defective inverter PCB
→ Replacement.
NO
1
Defective inverter PCB
→ Replacement
NO
Is DC280V
provided between
+ and - of the
capacitor?
Is an outdoor
provided at the Cn13
YES
and 14 on the inverter
PCB?
YES
2
Defective power transistor
module → Replacement
NO
Is AC200V
provided at U, V and
YES
W on the power
transistor module?
Check the wire between the
capacitor and Cn2 and check
the connector.
NO
3
Is the capacitor
normal?
YES
Check the compressor.
YES
NO
Defective capacitor
→ Replacement.
YES
4
Is there continuity
in the reactor?
NO
Defective reactor
→ Replacement.
NO
Defective resistance R1
→ Replacement.
NO
Defective 73X
→ Replacement.
YES
5
Is the resistance
value of the resistance
R1 is proper?
YES
Is the 73X good?
(FDCP2501 type only)
YES
6
Is the diode
module good?
NO
Defective diode module
→ Replacement.
YES
7
Is there continuity
in the noise filter?
YES
Check the 52C.
1090
NO
Defective noise filter
→ Replacement.
N
L3
L2
L1
TB
Green
Control board
Normality LED2 check: If this
LED flashing, the operation of
the microcomputer is normal.
Red
LED1 LED2
*
CNA2
CNA1
52C
1
2
3
4
5
6
7
Noise filter
When the tester bars are reversed, the resistance value is
about 10 ~ 20 Ω
8
~
~
~
Cn1
Inverter overheating
Current cut
6
7
4
5
Reception from outdoor unit
3
Watch dog (communication from the inverter
circuit board to the outdoor unit PCB)
12 V power supply
Transmission from outdoor unit
2
Common
Contents of communication
1
Connector
5V: normal, 0V: abnormal
5V: normal, 0V: abnormal
Swings between 2V and 4V.
Swings between 4.5V and 5V.
Swings between 11V and 11.5V.
12V
0V
V (analog tester)
6.8 Ω
Tester bar
(black)
Green
Red
Red
Red
LD1 LD2 LD3 LD4
Cn5
it is normal.
LD2: Power transistor overheating
LD3: Current cut
LD4: Serial transmission error
On the above occasion, these LDs light up.
Frequency
95~98
35Hz
104~107
40Hz
+
Cn13
Resistance
module
Cn8 Cn10 Cn12
Cn7 Cn9 Cn11
23F
Cn3
*
1 2 3 6 7 10 11 14 15
167~173
65Hz
1
Cn14- 6
Cn14- 5
Cn14- 3
Cn14- 2
Cn13-15 DC 1.5 ~
1.6V
Cn14- 1
Cn14- 4
Cn13-14
Cn13- 7
Cn13-11
Cn13- 6
Voltage
Cn13-10
(-)
(+)
Tester bars
Inverter PCB output check:
Disconnect the connector and measure the signal output to the power
transistor module.
Cn14
W
V
U
180~190
75Hz
1 2 3 4 5 6 9 12 14
Power transistor module
Check the appearance for crack or damage.
FDC 2001, 2501 type
Modells
195~197
80Hz
CM
198~203
95Hz
Power transistor output check:
Disconnect the Faston terminal of the compressor and measure the output voltage.
(The output 2001 is for the case whese the inverter is not loaded.)
Unit: V (AC)
2
Inverter circuit board
Cn2
1 2 3 4
check:
* LD1
When this LED flashing every 0.5 second,
1
2
3
4
5
6
7
+
3
Tester bar
(red)
Mark
Check the appeaeance for damage
and blister and check the charging
characteristic with a tester.
(The indicator swings and returns
slowly. After changing the polarity,
perform the same operation. If the
indicator returns, this is regarded as
normal.)
Capacitor check:
4
CT
DC280V
Reactor continuity check:
After disconnecting the connector and make a continuity
check. At that time, there should be continuity.
+
FDCP2001, 2501
Resistor R1 inspection
R1
5
When a check is made at the connector Cn1, the values become usually as shown in the following table.
Transformer
Transformer check: Disconnect the
connector CNA1. There should be
continuity on the primary side.
Tr
Power check:
Measure the power at the L1, L2, L3
and N on the terminal block TB.
Fuse check: There should be continuity.
*
7
When the
result is OK
Cn1
Noise filter check: There should be continuity.
Tester bar
+
~
+
~
Cn1
Outdoor Unit Check Points
Check the part marked * while the power supply is turned ON.
Make checks after the power supply is turned OFF,
or after removing each part.
6
Power cable check: To see if there is continuity and
connections are correct.
Diode module check
FDC-HKXR
1091
FDC-HKXR
MEMO
1092
19.2.1 Specifications
(1) Indoor unit
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTWJ28HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
90HKXE2B
112HKXE2B
140HKXE2B
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDRJ22HKXE2
28HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDUMJ36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDEJ36HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
112HKXE2B
140HKXE2B
FDKJ22HKXE2
28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
(2) Outdoor unit
Refrigerant R22 use models
FDCJ140HKXE2B
224HKXE2B
280HKXE2B
Alternative refrigerant R407C use models
FDCP140HKXE2B
224HKXE2B
280HKXE2B
19.2.3 Exterior dimensions
(1) Indoor unit
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTWJ28HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
90HKXE2B
112HKXE2B
140HKXE2B
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDRJ22HKXE2 (Silent Panel) (Canvas Panel) FDUMJ36HKXE2
28HKXE2 (Silent Panel) (Canvas Panel)
45HKXE2
45HKXE2 (Silent Panel) (Canvas Panel)
56HKXE2
56HKXE2 (Silent Panel) (Canvas Panel)
71HKXE2
71HKXE2 (Silent Panel) (Canvas Panel)
90HKXE2
90HKXE2 (Silent Panel) (Canvas Panel)
112HKXE2
112HKXE2 (Silent Panel) (Canvas Panel)
140HKXE2
140HKXE2 (Silent Panel) (Canvas Panel)
FDEJ36HKXE2B FDKJ22HKXE2
45HKXE2B
28HKXE2
56HKXE2B
36HKXE2
71HKXE2B
45HKXE2
112HKXE2B
56HKXE2
140HKXE2B
71HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
(2)Remote controller (optional parts)
(3) Outdoor unit
Refrigerant
R22 use models
FDCJ140HKXE2B
224HKXE2B
280HKXE2B
Alternative refrigerant
R407C use models
FDCP140HKXE2B
224HKXE2B
280HKXE2B
19.2.6 Selection chart
(1) Correct the cooling and heating capacity in
accordance with the conditions as follows.
(2) Correction
Correction of
of outdoor
outdoor unit
unit capacity
capacity according
according to
to capacity
capacity
of indoor unit to be operated simultaneously
FDCJ/FDCP140HKXE2B
224HKXE2B
280HKXE2B
(3)Sensible heat capacity
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDUMJ36HKXE2 FDEJ36HKXE2B
45HKXE2
45HKXE2B
56HKXE2
56HKXE2B
71HKXE2
71HKXE2B
90HKXE2
112HKXE2B
112HKXE2
140HKXE2B
140HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
FDRJ22HKXE2
28HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDKJ22HKXE2
28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
19.3.1 Electrical wiring
(1) Indoor unit
(a) Ceiling recessed type(FDT) Modles All models
(b) 2-Way outlet ceiling recessed type(FDTW) Models All models
(c) 1-Way outlet ceiling recessed type(FDTS) Models All models
(d) Cassetteria type(FDR) Models All models
(e) Satellite ducted type(FDUM) Models All models
(f) Ceiling suspension type(FDE) Models All models
(g) Wall mounted type(FDK) Models All models
(h) Floor standing exposed type(FDFL) Modles All models
(i) Floor standing hidden type(FDFU) Modles All models
(2) Outdoor unit
Refrigerant R22 use models
FDCJ140HKXE2B
224HKXE2B
280HKXE2B
Alternative refrigerant R407C use models
FDCP140HKXE2B
224HKXE2B
280HKXE2B
19.5
APPLICATION DATA
SAFETY PRECAUTIONS
19.5.1 Installation of indoor unit
(1) Ceiling recessed type(FDT)
(2) 2-Way outlet ceiling recessed type(FDTW)
(3) 1-Way outlet ceiling recessed type(FDTS)
(4) Cassetteria type(FDR)
(5) Satellite ducted type(FDUM)
(6) Ceiling suspension type(FDE)
(7) Wall mounted type(FDK)
(8) Floor standing exposed type(FDFL)
(9) Floor standing hidden type(FDFU)
19.6 MAINTENANCE DATA
(1)Before starting troubleshooting (P904 ~ P908)
(2)Procedures of trouble diagnosis (P908 ~ P933)
(3)Trouble diagnosis at the inverter side (P933 ~ P934)
20.2.1 Specifications
(1) Indoor unit
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTWJ28HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
90HKXE2B
112HKXE2B
140HKXE2B
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDRJ22HKXE2
28HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDUMJ36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDEJ36HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
112HKXE2B
140HKXE2B
FDKJ22HKXE2
28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
(2) Outdoor unit
Alternative refrigerant R407C use models
FDCP2001HKXRE2
2501HKXRE2
20.2.3 Exterior dimensions
(1) Indoor unit
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTWJ28HKXE2B
45HKXE2B
56HKXE2B
71HKXE2B
90HKXE2B
112HKXE2B
140HKXE2B
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDRJ22HKXE2 (Silent Panel) (Canvas Panel) FDUMJ36HKXE2
28HKXE2 (Silent Panel) (Canvas Panel)
45HKXE2
45HKXE2 (Silent Panel) (Canvas Panel)
56HKXE2
56HKXE2 (Silent Panel) (Canvas Panel)
71HKXE2
71HKXE2 (Silent Panel) (Canvas Panel)
90HKXE2
90HKXE2 (Silent Panel) (Canvas Panel)
112HKXE2
112HKXE2 (Silent Panel) (Canvas Panel)
140HKXE2
140HKXE2 (Silent Panel) (Canvas Panel)
FDEJ36HKXE2B FDKJ22HKXE2
45HKXE2B
28HKXE2
56HKXE2B
36HKXE2
71HKXE2B
45HKXE2
112HKXE2B
56HKXE2
140HKXE2B
71HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
(2)Remote controller (optional parts)
(3) Individual flow divide controller (Optional Part)
(4) Outdoor unit
Alternative refrigerant R407C use models
FDCP2001HKXRE2
2501HKXRE2
20.2.6 Selection chart
(1) Correct the cooling and heating capacity in
accordance with the conditions as follows.
(2) Correction
Correction of
of outdoor
outdoor unit
unit capacity
capacity according
according to
to capacity
capacity
of indoor unit to be operated simultaneously
Alternative refrigerant R407C use models
FDCP2001HKXRE2
2501HKXRE2
(3)Sensible heat capacity
FDTJ28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDTSJ22HKXE2B
28HKXE2B
36HKXE2B
45HKXE2B
71HKXE2B
FDUMJ36HKXE2 FDEJ36HKXE2B
45HKXE2
45HKXE2B
56HKXE2
56HKXE2B
71HKXE2
71HKXE2B
90HKXE2
112HKXE2B
112HKXE2
140HKXE2B
140HKXE2
FDFLJ28HKXE2
45HKXE2
71HKXE2
FDFUJ28HKXE2
45HKXE2
56HKXE2
71HKXE2
FDRJ22HKXE2
28HKXE2
45HKXE2
56HKXE2
71HKXE2
90HKXE2
112HKXE2
140HKXE2
FDKJ22HKXE2
28HKXE2
36HKXE2
45HKXE2
56HKXE2
71HKXE2
20.3.1 Electrical wiring
(1) Indoor unit
(a) Ceiling recessed type(FDT) Modles All models
(b) 2-Way outlet ceiling recessed type(FDTW) Models All models
(c) 1-Way outlet ceiling recessed type(FDTS) Models All models
(d) Cassetteria type(FDR) Models All models
(e) Satellite ducted type(FDUM) Models All models
(f) Ceiling suspension type(FDE) Models All models
(g) Wall mounted type(FDK) Models All models
(h) Floor standing exposed type(FDFL) Modles All models
(i) Floor standing hidden type(FDFU) Modles All models
(2) Individual flow divide controller
(3) Outdoor unit
Alternative refrigerant R407C use models
FDCP2001HKXRE2
2501HKXRE2
20.5
APPLICATION DATA
SAFETY PRECAUTIONS
20.5.1 Installation of indoor unit
(1) Ceiling recessed type(FDT)
(2) 2-Way outlet ceiling recessed type(FDTW)
(3) 1-Way outlet ceiling recessed type(FDTS)
(4) Cassetteria type(FDR)
(5) Satellite ducted type(FDUM)
(6) Ceiling suspension type(FDE)
(7) Wall mounted type(FDK)
(8) Floor standing exposed type(FDFL)
(9) Floor standing hidden type(FDFU)
20.6.1 Diagnosis of Microcomputer circuit
(1) Confirmation of the error code on the remote
controller (by pressing the inspection switch) and the
inspection display and normal display lamps on PCBs
of indoor/ outdoor units
(P1068 ~ P1072)
(2) Procedures of trouble diagnosis
(P1072 ~ P1087)
(3) When the remote controller indication is nomal but
the compressor cannot operate:(No check indication)
(P1087 ~ P1091)