- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Mitsubishi Heavy Industries
- FDC508HES3
- Owner's manual
advertisement
A I R C O N D I T I O N I N G & H E AT P U M P S Y S T E M S
S E R V I C E G U I D E
Including outdoor unit (FDC 6 Series and 8 Series)
FDT 4-Way Cassette
FDEN Ceiling Suspended
FDKN Wall Mounted
FDR Ducted Cassette
FDU Ducted - High Static
This guide is to assist site service engineers with commissioning of systems and to provide information for maintenance and fault finding.
CONTENTS
Operation
Wireless Remote Controller
Wired Remote Controller
Outline of Microcomputer Control Function
Pages 1 - 15
Page 1
Page 2
Page 3
Operation Control Function by the Wired Remote Controller Page 11
Operation Control Function by the Outdoor Controller Page 12
Safety Precautions Page 16
Maintenance
Servicing
Troubleshooting for Refrigeration Circuit
Diagnosing of Microchip Circuit
Pages 17 - 31
Page 17
Page 18
Page 19
8.4
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Wireless remote controller
Models FDTN (P), FDEN (P), FDKN (P) series
(a) Remote controller
OPERATION MODE indicator
Indicates selected operation mode
CAUTION
Cooling only air-conditioner has the display of “COOL”, “DRY” and “FAN” only.
Fan speed
Indicates the selected fan speed
Signal sender
Signals are sent to the air conditioner from here.
Filter reset indicator
The
FILTER
mark is indicated when the
FILTER RESET button is pressed.
Auto swing
Indicates the selection of swing louver.
Timer ON time
Indicates the timer ON time.
When the timer mode is “CONT” or “OFF”, the present time is indicated.
AUTO COOL DRY FAN HEAT
FILTER
FAN HI LO
°
C
ON AM
PM
OFF AM
PM
Temperature indicator
Set temperature is indicated.
Timer OFF time
Indicated the timer OFF time.
When the timer mode is “CONT” or
“OFF”, there is no indication.
MODE TEMP ON/OFF
OPERATION MODE select button
This button, whenever pressed, changes the mode in the following order.
AUTO ➞
➞
➞ DRY
HEAT FAN
CAUTION
Cooling only air-conditioner changes the mode in the following order.
COOL ➞ DRY ➞ FAN
FAN SPEED button
Every time when the button is pressed, the mode is sequentially changed HI
→
LOW.
FAN SPEED AIR FLOW FILTER
TIMER
ACL
SET
TIME
ON/OFF button
When the button is pressed, the air conditioner is started, and when the button is pressed once again, it is stopped. (When the air conditioner is stopped, the present time only is indicated.
When the air conditioner is operating, details of setting are indicated.)
ROOM TEMP. button
Room temperature is set within the range of 18-30˚C by operating the ∆
,
∇ or button.
Filter button
Used to reset (turn off) the filter sign.
(Press for more than 1 second.)
Press the button only after completing the filter cleaning.
Air flow direction button
Used to start or stop the swing louver.
Timer mode button
Every time when the button is pressed, the mode is sequentially changed CONT
→
ON
→
OFF
→
PROGRAM.
Reset switch
Used to reset the microcomputer when something is wrong on the remote controller display.
• Above figure shows all indications for the purpose of explanation, but practically only the pertinent parts are indicated.
(b) Indoor unit indicators
Model FDTN(P) series
Model FDKN (P) series
TIME button
Used to set the present time and the timer operation time.
Set button
Used to switch from the hour to minute or vice versa when setting the present time or timer operation time.
Clock switch
Press this before setting the present time.
Remote controller signal receiver.
RUN LAMP (GREEN)
Light up : Air conditioner is operating.
TIMER/CHECK (YELLOW)
Light up : Timer mode operating.
Flashing : When some error occurs.
1
Model FDEN (P) series
Heavy Duty
RUN CHECK ON/OFF
RUN LAMP (GREEN)
Illuminates during operation.
CHECK LAMP (YELLOW)
When a malfunction occurs, the lamp flashing.
BACK UP SWITCH
When the remote controller is missing or defective, this switch can start and stop the air conditioner.
Use the back up switch when the battery is exhausted, or when the remote controller is missing or defective.
Usually operate the air conditioner with remote controller.
(2) Wired remote controller
Models FDT, FDR, FDU, FDFL series
FDR, FDU and FDFL series are not provided with AUTO SWING switch.
Panel shown below will appear if you open the cover. All contents of display on the LCD are indicated simultaneously for the purpose of explanation.
Pull the knob on the cover to this side to open it downward.
Remote controller signal receiver
Filter sign
When this sign is indicated, clean the filter.
Remote display
This is displayed when the unit is controlled with an individual controller during normal operation.
(Also displayed when the air conditioner is stopped.)
Central display
This is displayed when the unit is controlled with the optional central console.
Operation mode display
Displays the operation mode that has been selected.
(Cooling only air-conditioner has the display of "COOL" ,"DRY" and "FAN" only.)
Heating preparation display
Operation/
Inspection indicator lamp
During operation: Green lamp flashes.
In case of error: Red lamp flashes.
On/Off switch
Use this switch to start or stop the air conditioner.First push on the switch starts the unit and second push stops it. (The switch can be operated without opening the cover.)
Timer operation display
Contents of timer operation are displayed.
(Also displayed when the air conditioner is stopped.)
Setting temperature display
Displays the temperature that has been set.
Fan speed display
Displays the fan speed that has been set.
Filter reset switch
Use this switch to reset (erase) the filter sign display.
(Press the switch after cleaning the air filter.)
CENTER REMOTE FILTER
PROGRAM TIMER
AUTODRYCOOLFANHEAT HEAT HOT
KEEP
SET TEMP
ON
A M
P M
OFF E
°
C
FAN
Hi
Mi
Lo
Outdoor No.
° C
FILTER
RESET
TIMER
T E M P
T I M E
CHECK SET
F A N
SPEED
A U T O
SWING
MODE
Return air temperature display
Displays the return air temperature.
Note
Indicated value may be different from actual reading on a thermometer or other instrument but this is not necessarily an error.
Auto swing display
Indicates the swing louver condition.
Cover
Mode switch
Use this switch to select operation modes.
Inspection switch
Use this switch when servicing the unit.
Timer switch
Use this switch when selecting contents of timer operation.
Set switch
Use this switch to set a time for the timer.
Fan speed switch
Use this switch to set a fan speed.
Auto swing switch
Use this switch to operate or stop the swing louver.
Temperature/
Time setting switch
Use this switch to set the room temperature or time on the timer.
2
(3) Outline of microcomputer control function
(a) Operation control function by the indoor controller
1) Automatic operation (Only heat pump type)
If the Auto mode is selected on the remote control device, the selection of cooling or heating can be made automatically depending on the room temperature (and the temperature of indoor heat exchanger). (When the switching between the cooling and the heating is made within 3 minutes, the compressor will not operate for 3 minutes.) This will make much easier the switching of cooling/heating at the change of season and can be adapted to the unmanned operation at bank cash dispenser.
Heating operation
Cooling operation
Setting room temp.
Room temp. (detected at Th
1-A
) [deg]
Suspended heating operation
Notes (1) During the automatic switching of cooling/heating the room temperature is controlled based on the setting of room temperature (DIFF:
±
}1 deg)
(2) If the temperature of indoor heat exchanger rises beyond 63˚C during the heating operation, it is switched automatically to the cooling operation. For an hour after this switching, the heating operation is suspended regardless of the temperature as shown at left.
Ready for heating
Indoor heat exchanger temperature (˚C)
2) Room temperature control (Differential of thermostat)
Heating operation Cooling operation
ON (52C)
OFF (52C) OFF (52C)
-1 +1
Set temp.by thermostat
Temperature difference between thermostat set temp.
and return air temp. (Detected by ThI-A)
-1
+1
Set temp.by thermostat
Temperature difference between thermostat set temp. and return air temp. (Detected by ThI-A)
3) Control parts operation during cooling and heating
Function
Control part
Compressor
4-way valve
Outdoor fan
Indoor fan
Louver motor
Condensate motor
Cooling
Thermostat
ON
×
Thermostat
OFF
×
×
×
Fan
–
×
×
×
Thermostat
ON
×
(2min. ON)
×
(2min. ON)
Note(1) :ON
×
:OFF
/
×
:According to control other than temperature control.
Heating
Thermostat
OFF
×
Defrost
×
×
/ ×
/ ×
×
×
×
(2min. ON)
HOT START
Thermostat
ON
×
Dry
Thermostat
OFF
×
×
×
×
(2min. ON)
3
4) Dehumidifying operation (“THERMAL DRY”)
The compressor, the indoor fan motor and the outdoor fan motor are operated intermittently under thermistor (ThI-A) control according to the appropriate operation block, to provide cooling operation for the dehumidifying.
Operation block
D C B A
Low -2 +3 High
Pattern of operation
CM, FM
O
: ON
O p e r a t i o n block
Thermal drying starting
(for 8 or 16 minutes after operation started)
A
B
Set temp. by thermostat
FM
I
: ON
Normal thermal dry operation
(after completion of thermal drying)
(16 minutes) (8 minutes)
Continuous cooling operation (FM
I
:Lo)
• Cooling operation (Thermostat ON)
• Indoor fan operating with the setting air flow.
• When the thermostat is turned off, the indoor fan operates for 30 seconds with the Lo operation in the wind blowing mode and then stops.
(8 minutes)
CM, FM
FM
I
0
(8 minutes) (8 minutes)
C
CM, FM
0
FM
I
CM, FM
0
FM
I
D
(8 minutes) All stoppage
Notes (1) Operation block A B : Normal cooling operation for 16 minutes after operation is started.
Operation stops by thermostat when the set temperature is reached.
After 16 minutes, normal thermal drying operation starts.
Operation block C D : Operation as above is performed for 8 minutes.
After 8 minutes, normal thermal drying operation starts.
(2) In normal operation, the temperature is checked at 8 minute intervals after normal thermal drying operation is started, to determine which operation block is to the selected.
Operation block A thermal drying is carried out if the thermostat set temperature is constant.
5) Hot spurt (Only heat pump type)
In the hot spurt mode, the control is conducted at the level +2 higher than the setting temperature at the start of heating operation.
The hot spurt is canceled either after the initial thermostat OFF, when the indoor heat exchanger temperature reaches 61˚C or 60 minutes after the start of the mode.
Room temperature (deg)
4
6) FM control with the heating thermostat turned off (For cold draft prevention) (Only heat pump type)
In order to prevent a cold draft while the heating thermostat is turned off, the indoor blower is controlled in response to the temperature of the indoor heat exchanger as illustrated below. It should be noted that if SW3-4 on the indoor PCB is turned off, the indoor blower will stop so far as the temperature of the indoor heat exchanger is lower than 40˚C. It will be turned to the Lo operation 5 minutes later.
(Setting air flow)
Lo
Note (1) After the thermostat is reset, it returns to the hot start control.
40 45
7) Hot start (Cold draft prevention during heating) (Only heat pump type)
1) If the indoor heat exchanger temperature is lower than 30˚C when the heating operation has started, the following indoor blower control is performed.
(1) In case of the thermostat off condition: Lo operation
(2) In case of the thermostat on condition : Stop
(3) If the indoor heat exchanger temperature exceeds 30˚C or 7 minutes after the beginning of hot start, the hot start terminates and it returns to the setting airflow of the blower.
2) If the indoor heat exchanger temperature is lower than 30˚C when the unit is heating under the thermo-ON condition, the indoor fan operates in the Lo mode. As the temperature rises higher than 30 ˚C or 7 minutes after the beginning of hot start, the hot start terminates and it returns to the setting air flow.
8) Indoor fan control during defrost operation (Only heat pump type)
1) The indoor fan operation is changed from the setting airflow to the Lo operation 40 seconds before the start of defrost operation (when the defrost thermostat is turned ON) and stops if the indoor heat exchanger temperature drops below 20˚C.
2) After the stop as described in 1)-above, the control will be conducted as illustrated below depending on the indoor heat exchanger temperature.
Lo
Stop
20 30
Indoor heat exchanger temperature(˚C)
3) If the indoor heat exchanger temperature rises beyond 30˚C of 7 minutes after the end of defrosting, the indoor fan control related to the defrosting is completed.
5
9) Condensate pump motor (DM) control (Only FDTN (P), FDT, FDR models)
During the cooling or Dehumidifying operation, the condensate pump motor (DM) is synchronized with the start of compressor operation. If the operation is switched from the operation stop, error stop, thermostat stop and the cooling of defrosting operation to the fan or heating operation, the drain motor continues to operate for 2 minutes after the switching.
Overflow detection by means of the float switch is always on regardless of the operation mode. If an overflow occurs (or the float switch is not connected or the wire is broken), the operation is interrupted as the error stop and the drain motor is operated until the state of float switch is normalized.
10) Defrost control (FDC 6 series only)
Defrost operation is precisely controlled with the defrost thermostat (23DH 1, 2 ) and a timer.
a) Defrost starting conditions
Defrost operation will start only when all of following conditions are met.
1) When the compressor operation time accumulated after the start of heating operation exceeds 30 minutes.
2) When the compressor operation time accumulated after the end of defrost operation exceeds 45 minutes.
3) When the defrost thermostat (23DH1) is turned ON (-6˚C) b) Defrost terminating condition
If the defrost thermostat (23DH2) is turned OFF (12˚C) or 12 minutes after the start of defrost operation, the defrost operation is canceled and it returns to the heating operation.
11) 4-way valve control (1 phase models only)
In order to maintain the pressure balance after the stop of compressor during cooling, dehumidifying and heating operation. the 4way valve is controlled repeatedly as illustrated below.
Compressor (During cooling, heating)
ON
OFF
4-way valve
(During cooling)
(During heating)
ON
OFF
ON
OFF
120 sec.
50 sec.
180 sec. or over
12) Frost prevention during cooling (For indoor heat exchanger)
In order to prevent the frosting during cooling operation, the temperature of indoor unit heat exchanger (detected by Th
I-R
) is checked 9 min, after the compressor operation start and the unit operation.
This cycle is not operated for 9 min. after the resetting of this frost prevention mechanism.
Cooling operation
OFF (52C)
2.5˚C 10˚C
Indoor heat exchanger (ThI-R)
6
13) Compressor inching prevention control a) Compressor 3 minutes delay control
The compressor will remain in stop state for three minutes. When the compressor is stopped by thermostat, ON/OFF switch, and/or by occurrence of trouble. When the power source is turned ON, the three-minute delay timer is cancelled.
b) Compressor 3 minutes forced operation control
Compressor cannot be stopped for 3 minutes after it started. However, it will be stopped immediately when the thermostat is turned off due to the operation stop initiated by the ON/OFF switch or the change of operation mode.
Note (1) Both the error control and the protective control take priority over this control.
14) Overload protection during heating
If an overload condition has been detected by the indoor heat exchanger temperature and it has continued for more than 2 seconds during heating, the compressor is stopped. The compressor is started after a delay of 3 minutes and, if the overload condition is detected again whithin 60 minutes after the initial detection, the compressor is stopped with the error stop.
Heating operation
61 68
Indoor heat exchanger temperature(˚C)
15) Automatic restart control
If there is interruption of power while the unit is operating, the unit operates after power restoration under the same condition as prior to the power interruption. However the compressor will only be able to start three minutes after the power restoration.
Furthermore, if the timer was operating prior to the power interruption, the unit remains stopped even after the restoration of service.
Note (1) Becomes invalid if the dip switch SW3-1 on the indoor PC board is at OFF (SW3-1 is set at ON when unit is shipped from the factory).
16) Thermistor disconnection detection control a) Detection of indoor return air thermistor disconnection
¡ If there is detection of a disconnection on the return air thermistor in 10 seconds after turning the power ON, the compressor is stopped. If there is a second disconnection on the return air thermistor detected within 60 minutes, there is emergency stop.
Note (1) If the first disconnection on the return air thermistor is detected for a period of 6 continuous minutes, there is emergency stop. If there is no detection of a second disconnection on the return air thermistor whithin 60 minutes, the first detection becomes invalid.
b) Detection of heat exchanger thermistor disconnection
¡ If a disconnection is detected on the heat exchanger thermistor in 20 seconds after the compressor has been operating for
2 minutes, the compressor is stopped. If a second disconnection on the heat exchanger thermistor line is detected within
60 minutes, there is emergency stop.
Note (1) If the first disconnection on the heat exchanger thermistor is detected for a period 6 continuous minutes, there is emergency stop.
If there is no detection of second disconnection on the heat exchanger thermistor within 60 minutes, the first detection becomes invalid.
7
17) Drain detection (Only FDTN(P), FDT, FDR models) a) If there is detection of a drain abnormality during cooling operation, the drain pump goes ON for 5 minutes and the compressor which had been running comes to a stop.
Overflow detection is carried out at all times with the float switch regardless of operational mode. If an overflow is generated
(or if the float switch is not yet connected or has been disconnected). there is emergency stop (while the Check lamp (yellow) blinks 4 times) the drain motor operates until reset of the float switch.
b) If a drain abnormality is detected during cooling operation, there is emergency stop (while the Check lamp (yellow) blinks 4 times) to stop the compressor, and the drain pump is operated with the drain motor until reset of the float switch.
c) If a drain abnormality is detected during a stop state or fan operation, there is forced operation of the drain pump for 5 minutes. After 5 minutes have elapsed, the drain motor stops if the float switch is reset. Otherwise, there is emergency stop
(wile the Check lamp (yellow) blinks 4 times) and the drain motor operates until the float switch is reset.
d) If the float switch is not connected or if there is a disconnection, there is emergency stop.
18) Low voltage guard control
If the power source voltage remains at a value of 80% of rating or less for 3 continuous minutes during operation of the compressor, the compressor stops (52C OFF). Furthermore, if the power source voltage remains at a figure of 15% of rating or greater after 3 minutes have elapsed since stopping the compressor, there is restarting of the compressor (52C ON). Moreover, during stoppage of the compressor, the Run lamp (green) blinks 2 times.
Note (1) When starting the compressor for the first time after turning the operational switch ON, there is starting regardless of the power source voltage. Furthermore, if dip switch SW 3-2 on the internal substrate is OFF, this becomes invalid. (Switch SW 3-2 is set to ON upon shipment from the factory).
19) Refrigerant shortage error
When 52C is ON when operating in cooling (including automatic cooling), if heat exchanger sensor temperature for the indoor unit (Th
I
-R) does not drop to 25
°
C or less for 40 minutes 5 minutes or more after the start of operation, an abnormal stop due to insufficient refrigerant is performed.
20) External control (remote display)/control of input signal
¡ External control (remote display) output
Following output connectors (CNT) are provided on the control circuit board of indoor unit.
¡ Operation output: Power to engage DC 12V relay (provided by the customer) is outputted during operation.
¡ Heating output: Power to engage DC 12V relay (provided by the customer) is outputted during the heating operation.
¡ Compressor ON output: Power to engage DC 12V relay (provided by the customer) is outputted while the compressor is operating.
¡ Error output: When any error occurs, the power to engage DC 12V relay (provided by the customer) is outputted.
¡ Control of input signal
(Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote control unit.)
Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor unit.
However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
8
¡ At shipping from factory [FDTN (P), FDEN (P), FDKN (P) models : J3 (SW5-3), FDT, FDR, FDU, FDFL models : J5 (SW5-2) ] on PCB OFF]
¡ Input signal to CnT OFF →
ON [Edge input] ... Air conditioner ON
¡ Input signal to CnT ON →
OFF [Edge input] ... Air conditioner OFF
ON ON
CnT input
OFF OFF OFF
ON
ON ON ON
Unit A
OFF OFF
Remote controller operation OFF
Remote controller operation ON
(Last operation has priority.)
¡ When J3 (SW5-3) [FDTN (P), FDEN (P), FDKN (P) models] or J5 (SW5-2) [FDT, FDR, FDU, FDFL models] on the PCB of indoor unit is turned on at the field.
Input signal to CnT becomes Valid at OFF Æ ON only and the motion of air conditioner [ON/OFF] is inverted.
ON ON
CnT input
Unit A
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
Remote controller operation OFF
Remote controller operation ON
(Last operation has priority.)
21) Auto Swing Control (Excepted FDR, FDU, FDFL models)
¡ Have a louver motor to move the louvers up and down for the so called “auto swing” function.
¡ The louver auto swing starts when the AUTO SWING key is pressed once and stops when the AUTO SWING key is pressed again. The louver position is displayed on the LCD on the remote controller. During auto swing, the position displayed on the
LCD changes, but the positions of the louvers and the display are not coordinated. (The louvers swing 3 - 4 times per minute but the display changes once per second.)
¡ Stopping the louvers
When the AUTO SWING key is pressed to stop the louver movement, the LCD louver-position display stops and the louvers stop when they come to the position displayed on the LCD. There are four louver stop position on the LCD. (When jumper wire
J7 [FDTN (P), FDEN (P) models] or J3 [FDT model] on the indoor unit printed circuit board is cut, the louvers stop immediately at the AUTO SWING key is pressed to stop them and the LCD display changes to show this position. (Excepted FDKN (P) model)
¡ Movement of louver when the power supply to the controller controlling 4 positions of the louver is switched on. (Only FDT model)
When power supply is switched on, the louver will automatically swing about 2 times (without operating remote controller).
This is an action for the microcomputer to confirm the louver position in order to input the cycle of the louver motor (LM) to the microcomputer with the limit switch (LS) pushing the louver motor (LM). If the LS action is not input to the microcomputer, the louver will stop within 1 minute after the power supply is switched on and will not move from then on.
9
¡ Keeping the louvers horizontal during heating (Only heat pump type)
While HOT KEEP is displayed (during hot start operation or when the thermostat has turned off during heating operation), the louvers stay in the horizontal position to prevent cold drafts, independent of the setting of the AUTO SWING key (auto swing or stop). The louver position display of LCD displays continuously the original position before this control operation.
When the HOT KEEP display goes out, both the louvers and the LCD display return to their previous position.
(However, after the power supply to the unit is switched on, the louvers swing two times as a check of the power source frequency, regardless of the settings of the ON / OFF or AUTO SWING keys).
22) Using 1 remote controller to control multiple units (indoor units - up to 16 units) (Only FDT, FDR, FDU, FDFL models) a) Function
A single remote control switch can be used for group control of multiple units (indoor units - up to 16 units). All units in the group that have had the remote control switch set at [Operating Mode] can be turned on and off in order of the unit number.
This functions independently of the thermostat and protection functions of each unit.
Notes (1) The unit number is set by a switch (SW1) on the circuit board for the indoor unit.
Set SW1 : 0~F
Outdoor unit
0 1 2 3 4 F
Indoor/Outdoor connection wire Refrigerant piping
0 1 2 3 4 F indoor unit
Remote controller wire
Remote controller
(2) If unit number is not important, random can be used. However, setting in order from 0, 1, 2, to F will ensure setting without error.
b) Display to remote controller
(i) Return air temperature, by remote or center and heating preparation: Displays for the youngest unit for the remote mode (center mode if there is no remote mode) of the units in operation.
(ii) Inspection and filter sign: Displays either to the first corresponding unit.
c) Confirmation of connected units
Each push of the inspection switch on the remote control displays the units connected in sequential order from the youngest unit.
d) Error
(i) If an error occurs (protection device activation) with some of the units in the group, those units will have an error stop, but the properly operating units will continue operation.
(ii) Wiring outline
Route the wire connecting each of the indoor and outdoor units as it would be for each unit. Use the terminal block (X,
Y, Z) for the remote control for the group controller and use a jumper wire among each of the rooms.
10
(b) Operation control function by the wired remote controller
(i) The following is the sequence of operation for the remote controller operation mode switch.
DRY COOL FAN HEAT AUTO
(ii) CPU reset
This functions when the " inspection " and " filter reset switch " on the remote controller are pushed simultaneously. It operates in the same manner as the power reset.
(iii) Power outage compensation function.
¡ This is enabled by setting dip switch SW3 on the remote control circuit board to ON.
¡ It records the normally used remote control modes. Once power has been restored, it restarts operation by using the contents of the memory. Note that the stop positions for auto swing and the timer mode are cancelled.
Parts layout on the remote controller PCB
Z
BLACK
Y
WHITE
X
RED
Q1
Q3
R4
R7
R28
Q2
R18
IC1
TYPE
SW1
REMOTE
THERMO
SW2
POWEP OFF
GUARAMTY
SW3
DIP switched
(SW1 ~ SW4)
TEMP DISP.
J1
FAN SPEED
J2
Jumper wires (J1 ~ J4)
• Function of DIP switched
SW
1
SW
2
SW
3
Switch
ON
OFF
ON
OFF
ON
OFF
Function
Cooling only type
Heat pump type
Remote control sensor - Enabled
Remote control sensor - Disabled
Power outage compensation - ON
Power outage compensation - OFF
TIMER FUNC.
J3
SWING
DISP.
J4
• Function of Jumper wires
J1
J2
J3
J4
Switch
Wich
None (1)
Wich
None (1)
Wich
None (1)
Wich
None (1)
Function
Inlet temperature display - Enabled
Inlet temperature display - Disabled
Fan display - 3 speeds
Fan display - 2 speeds
Timer function - Enabled (Normal)
Timer function - Disabled
Auto swing display - ON
Auto swing display - OFF
Note (1) 'None' means that jumper wire is not provided on the PCB or the connection ic cut.
11
(c) Operation control function by the outdoor controller (Only FDC(P)208~508 type, FDC808, 1008 type)
1) Control for outdoor unit fan a) Cooling Operation
The speed of the fan for the outdoor unit is controlled by the temperature of the heat exchanger (Tho-R detection) and the outdoor air temperature (Tho-A).
B Zone
Models FDC(P)208~508 type
F Zone
A Zone
E Zone
D Zone
C Zone
15 18 31 33
Outdoor air temperature (
°
C)
Description of control for fan for outdoor unit
Model
Fan motor
C Zone
A Zone
Zone
D Zone
E Zone
C Zone
B Zone D Zone
E Zone
F Zone
B Zone
Models FDC808, 1008 type
A Zone
FDC(P)208~308 type
FM
0
Hi
Hi
Hi
Hi
Hi
Lo
Hi
32 48 57 63
Heat exchanger temperature (
°
C)
FDC(P)408, 508 type
FM
01
(Up)
Hi
Hi
Hi
Hi
FM
02
(Lo)
Hi
OFF
OFF
Hi
Hi
Lo
Hi
OFF
OFF
Hi
D Zone
C Zone
20 25
Outdoor air temperature (
°
C)
44 48
Heat exchanger temperature (
°
C)
Description of control for fan for outdoor unit
Zone
Fan motor
A Zone
B Zone
C Zone
D Zone
FM
01
(Left)
Hi
Hi
Lo
FM
02
(Right)
Hi
OFF
OFF b) Heating Operation
1 Stop control for outdoor fan
When the high pressure switch (63H
2
) operates, the fan for the outdoor unit is stopped to control the high pressure switch.
63H
2
settings
Models FDC208~1008 type
2.5 OFF/2.06 ON (MPa)
[25.5 OFF/21 ON (kgf/cm 2 )]
Models FDCP208~508 type
2.79 OFF/2.26 ON (MPa)
[28.5 OFF/23 ON (kgf/cm 2 )]
2 Tap control for outdoor fan
When the high pressure switch (63H
2
) is closed, the outdoor fan is controlled by the detected heat of the outdoor heat exchanger thermistor (Tho-R) and the detected heat of the outdoor air temperature thermistor (Tho-A).
E Zone
C Zone
A Zone
D Zone
B Zone
9 11 17 19
Outdoor air temperature (
°
C)
-3 0
Heat exchanger temperature (
°
C)
Description of control for fan for outdoor unit
Model
Fan motor
A Zone
C Zone
FDC(P)208~308 type
FM
0
Hi
Hi
FDC(P)408, 508 type
FM
01
(Up) FM
02
(Lo)
Hi
Hi
OFF
Hi
FDC808,1008 type
FM
01
(Left) FM
02
(Right)
Hi
Hi
OFF
Hi D Zone
Zone B Zone
E Zone
C Zone
D Zone
Hi
Lo
Hi
Hi
Lo
Hi
Hi
OFF
OFF
Hi
Hi
Hi
Hi
OFF
Hi
Note (1) When the fan for the outdoor unit is started when the outdoor air temperature is more than 12
°
C, it will operate at high speed for 3 seconds and then switch to low speed. After operating a low speed for 4 minutes, it will be transferred to controlled speed.
12
2) Control of fan for outdoor unit for de-icing
If DIP switch SW5-2 on the printed circuit board for the outdoor unit is set to on, the fan on the outdoor unit which has been stopped will operate for 10 seconds at Hi speed every 10 minutes when the outdoor air temperature is 3
°
C or less.
Outdoor fan operates at Hi speed
Outdoor fan stopped
3 5
Outdoor air temperature (
°
C)
3) Discharge temperature control during cooling/heating (Only case of FDC(P)208~508 type)
As the discharge gas temperature (detected with Th
O-
D) rises during cooling/heating operation, the capillary bypass and the liquid bypass solenoid valve (SV1) are opened so that the abnormal rise of discharge gas temperature is prevented.
SV -open
SV -close
108 115
Discharge gas temp (
°
C)
4) Defrost control
Defrost operation will start when the temperature of the heat exchanger for the outdoor unit (Tho-R detection) and the outdoor air temperature (Tho-A detection) enter the start of defrost range shown in the figure below.
Initiation temp. of defrosting (Detected by Tho-R, Tho-A)
-5
-10
-15
Zone for initiate temp. of defrost
Initiation temp. of defrosting
(
°
C)
[Th
0
-R]
-20
-20 -15 -10 -5
Outdoor air temperature (
°
0
C) [Th
0
-A]
5 10
Note (1) If DIP switch SW5-1 on the printed circuit board for the outdoor unit is set to on, defrost operation will begin when temperature of the heat exchanger for the outdoor unit reaches -7
°
C.
a) Defrost Operation
Switching of the control of the 4-way selector valve during defrost operation can be performed by enabling/disabling the jumper wire (J17) on the printed circuit board for the outdoor unit.
(i) J17 None (4-way selector valve ON during heater operation)
Defrost operation is performed with the compressor on, the fan for the outdoor unit off and the 4-way selector valve off.
(ii) J17 With (4-way selector valve OFF during heater operation)
Defrost operation is performed with the compressor on, the fan for the outdoor unit off and the 4-way selector valve on.
b) Defrost finished
(i) Once defrost operation has started, it will finish after the cumulative operating time of the compressor has reached 12 minutes (factory setting: SW5-1 OFF).
Note (1) This time will become 14 minutes if the DIP switch (SW5-1) on the printed circuit board on the outdoor unit is set to on.
(ii) Switching of the defrost recovery time can be performed by enabling/disabling the jumper wire (J18) on the printed circuit board for the outdoor unit.
J18 (SW6-2) With: 14
°
C, J18 (SW6-2) None: 18
°
C
13
5) Compressor protecting function (Microcomputer and phase protection relay) a) Overcurrent control
(i) When a 52C secondary L
1
-phase continues for 0.5 seconds and when it is more than the set value (detection at current sensor CT), the compressor is stopped. The compressor is restarted after a 3-minute delay if the detection current is less than 1.5 to 2A. If this condition is re-detected 5 times within 60 minutes of the first occurrence, an abnormal stop of the unit is performed.
(ii) If 60 minutes passes and the detected current after the first to the fourth stoppage is not less than 1.5~2A, an abnormal stop of the unit is performed.
b) Open-phase protection
When a 52C secondary detection current continues for 4 seconds when the compressor is on and when it is less than 1.5 to 2
A, it is determined to be a open-phase of the 52C secondary N-phase, and the compressor is stopped. The compressor is restarted after a 3-minute delay and if this condition is re-detected within 60 minutes of the first occurrence, an abnormal stop of the unit is performed.
c) Detection of abnormal discharge temperature (Only case of FDC(P)208~508 type)
(i) When an abnormally high temperature is detected at the discharge pipe of the compressor (Tho-D detection), the compressor is stopped. The compressor is restarted after a 3-minute delay and if this condition is re-detected 5 times within 60 minutes of the first occurrence, an abnormal stop of the unit is performed.
Operable
Error stop
90 135
Discharge pipe temp. (
°
C)
(ii) If 60 minutes passes and the detected temperature after the first to the fourth stoppage is not less than 90
°
C, an abnormal stop of the unit is performed.
Note (1) Once an abnormal discharge temperature has occurred, restarting cannot be performed for 45 minutes. [Detection temperature less than 3
°
C]. (In failure mode, resetting cannot be performed by remote control.)
Operation is possible after 45 minutes. (Cleared by resetting power source.) d) Cooling overload protection
State of overload during cooling operation is detected (with Tho-R) based on the temperature of outdoor heat exchanger and the unit operation is stopped / Immediate reset after repair
Operable
Error stop
60
°
C 70
°
C
Outdoor heat exchanger temp. e) Thermistor [Discharge piping (Only case of FDC(P)208~508 type), Heat exchanger and outdoor air thermistor] disconnected wire
(i) If there is a disconnected wire or if there is a big difference in performance characteristics, an abnormal stop of the unit is performed. e Restore after repairing.
14
6) High-pressure protection by high-pressure make-or-break device (63H
1
)
(Only case of FDCP208~508 and FDC808, 1008 type) a) If the pressure rises and 63H
1
is operated (opened), the compressor is stopped. After a 3-minute delay, the compressor is restarted. An abnormal stop is performed when 63H
1
is opened five times within 60 minutes of the first operation. e Restore after repairing.
b) An abnormal stop is performed at the first occurrence if 63H
1
remains open after 60 minutes have passed from the first time the compressor was stopped.
Note (1) Once 63H
1
has been restored after an abnormal stop, the unit can be restarted using the remote control.
7) Compressor motor protection (Only case of FDC808, 1008 type)
The same detection control as 63H
1
will be performed when the internal thermostat 49C operates due to a rise in the windings of the compressor motor. The setting values of the internal thermostat 49C are 90
°
C open and 73
°
C close.
8) Control of the closing and opening of the service valve (Only heat pump type) a) When the compressor is ON for the first time after turning on the power, the heating operation starts regardless of any setting.
b) If the 63H
2
turns OFF(open) within 10 seconds after the compressor is ON, the power will turn off as abnormal stop.
c) To recover from the abnormal stop, turn on the power again after the 63H 2 is ON(closed).
d) If the 63H 2 doesn't turn OFF(open) within 10 seconds after the compressor is ON, the operation immediately changes to the
“set mode” to start normal operation.
9) Test run a) For a test run, it is possible to use the dip switches SW5-3 and SW5-4 on the printed circuit board in the outdoor unit.
SW5-3
ON SW5-4
OFF Normal
OFF Test run for cooling
ON Test run for heating b) Test run time is 30 minutes. Protective devices are effectively controlled.
15
8.5
APPLICATION DATA
SAFETY PRECAUTIONS
• Please read these “Safety Precautions” first then accurately execute the installation work.
• Though the precautionary points indicated herein are divided under two headings. WARNING and CAUTION , those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
• After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual.
Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
• This system should be applied to places of office, restaurant, residence and the like. Application to inferior environment such as engineering shop could cause equipment malfunction.
• Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires.
• Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires.
• When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you perchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur, there is the danger of a resultant oxygen deficiency accident.
• For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit.
• Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
• For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires.
• Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
• Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire.
• When setting up or moving the location of the air-conditioner, do not mix air etc. or anything other than the designated refrigerant (R22) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
• Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refrigerant leakage.
CAUTION
• Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground wire. Improper placement of ground wires can result in electric shock.
• The installation of an earth leakage breaker is necessary depending on the established location of the unit.
Not installing an earth leakage breaker may result in electric shock.
• Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
• For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
16
8.6
MAINTENANCE DATA
8.6.1
Servicing
(1) Evacuation
The evacuation is a procedure to purge impurities, such as noncondensable gas, air, moisture from the refrigerant equipment by using a vacuum pump. Since the refrigerant R22 and R407C is very insoluble in water, even a small amount of moisture left in the refrigerant equipment will freeze, causing what is called ice clogging.
Evacuation procedure
Make sure that the both service valves of gas and liquid line are fully opened.
(a) Check to ensure that there is no internal pressure in the unit. If there is an internal pres-
Outdoor unit sure, it should be relived through the service port.
(b) Connect the charging hose of the gauge manifold to the service port of the gas piping.
Close high pressure valve 2 of gange manifold.
(c) Connect the charging hose A to a vecuum pump.
Repeat evacuation in the following sequence.
Flare connection
Service hoses
Start the vacuum pump.
h
Compond pressure gauge indicates -0.1 MPa (-76 cmHg) h
Operate the vacuum pump for more than 10 minutes after -0.1MPa
(-76 cmHg) Hg is indicated.
h
Close low pressure valves 1 of gauge manifold.
h
Stop the vacuum pump.
Liquid line
Indoor unit
Gas line service port
Charging hose
A
1
Lo Hi
2 Gauge manifold
3
Refrigerant cylinder
Vacuum pump
Notes (1) Refer to the exterior-view drawing for the position of the service valve.
(2) When connecting of the service valve, flare connection for both the indoor and outdoor unit.
Notes (1) Do not use the refrigerant pressure to expel air.
(2) Do not use the compressor for evacuation.
(3) Do not operate the compressor in a vacuum condition.
17
(2) Refrigerant charging
(a) After the evacuation shown in the above, change the connection of the charge hose A to the refrigerant cylinder.
(b) Purge air from the charge hose A .
First loosen the connecting portion of the charge hose at the gauge manifold side and open valve 3 for a few seconds, and then immediately retighten it after observing that gas has blown out from loosened connecting portion.
(c) Open valves 1 and 3 then gas refrigerant begins flowing from the cylinder into the unit.
When refrigerant has been charged into the unit to some extent, refrigerant flow becomes stagnant. When that happens, start the compressor in cooling cycle until the system is filled with the specified amount of gas, then close valves 1 and 3 and remove the gauge manifold. Cover the service port with caps and tighten them securely.
(d) Check for gas leakage by applying a gas leak detector around the piping connection.
(e) Start the air conditioner and make sure of its operating condition.
8.6.2
Trouble shooting for refrigerant circuit
(1) Judgement of operating condition by operation pressure and temperature difference
Making an accurate judgement requires a skill that is acquired only after years of experience, one trouble may lead to an another trouble from a single trouble source and several other troubles may exist at the same time which comes from a undetected different trouble source.
Filtering out the trouble sources can be done easier by comparing with daily operating conditions. Some good guides are to judge the operating pressure and the temperature difference between suction air and delivery air.
Following are some pointers,
Indication
Circuit
High side
Low side
High side
Low side
High side
Low side
Pressure
¡
¡
¡
High side
Low side
High side
Low side
Trouble cause
¡
¡
¡
1) Excessive overcharging of refrigerant
2) Mixture of non condensable gas (air etc.)
Ineffective compression
¡ (defective compressor)
1) Insufficient refrigerant in circuit
2) Clogging of strainer
3) Gas leakage
4) Clogging of air filter (in cooling)
5) Decrease in heat load (in cooling)
6) Locking of indoor fan (in cooling)
¡ 1) Locking of outdoor unit fan (in cooling)
2) Dirty outdoor heat exchanger (in cooling)
3) Mixture of non condensable gas (air etc.)
¡
¡
1) Too high temperature of room
18
8.6.3
Diagnosing of microcomputer circuit
(1) Selfdiagnosis function
(a) Indoor unit side
(i) Only case of wireless remote control model.
Check indicator table
Failure mode on the indoor unit indicated by flashing Yellow LED and Green LED.
Indoor unit LED
Yellow Green
1 time flash
2 time flashes
4 time flashes
5 time flashes
6 time flashes
–
Failure at: Contents of the failure
–
–
–
–
–
2 time flashes
Indoor unit heat exchanger thermistor
Indoor unit circuit board
Indoor unit air return thermistor
Indoor unit circuit board
Failure in drainage
Float switch
Indoor circuit board
Insufficient refrigerant
Indoor unit heat exchanger thermistor
Indoor unit circuit board
Installation and operating conditions
Indoor unit heat exchanger thermistor
Indoor unit circuit board
Low voltage protection
• Indoor unit heat exchanger thermistor defective (element defective or broken wire).
Defective connection of connector for thermistor.
Indoor unit circuit board defective (defective thermistor input circuit)?
•
•
Indoor unit return thermistor defective (element defective or broken wire).
Defective connection of connector for thermistor.
Indoor unit circuit board defective (defective thermistor input circuit)?
•
•
•
•
•
•
Failure with the condensate pump (DM), or open circuit or disconnection of connector with the condensate pump.
Malfunctioning of the float switch (erroneous functioning)
Indoor unit circuit board defective (defective float switch input circuit)
Indoor unit circuit board defective (defective DM driving output circuit)
•
•
•
•
Gas leak.
Indoor unit heat exchanger thermistor defective (short circuit).
Indoor unit circuit board defective (defective thermistor input circuit)?
Heating overload (temperature of heat exchanger for indoor unit abnormally high)
•
Indoor unit heat exchanger thermistor defective (short circuit)?
Indoor unit circuit board defective (defective thermistor input circuit)?
• When the power source voltage is 80% of rating or lower.
Note (1) Inspection LED display has a cycle of 8 seconds (flashing time of 0.5 seconds).
(ii) Only case of wired remote control model.
Table of inspection items based on error codes
Error Code
E1
E6
E7
E8
E9
E10
E57
Failure at:
Operating switch wire
(signal noise)
Circuit board for operating switch or indoor unit
Indoor unit heat exchanger thermistor
Indoor unit circuit board
Indoor unit air inlet thermistor
Indoor unit circuit board
Installation and operating conditions
Indoor unit heat exchanger thermistor
Contents of the failure
•
• Defective connection or broken wire for operating switch signal wire.
Signal noise has entered the operating switch wire.
• Is the circuit board for the operating switch or the circuit board for the indoor unit is defective
(communication circuit defective)?
• Indoor unit heat exchanger thermistor defective (element defective or broken wire). Defective connection of connector for thermistor.
• Indoor unit circuit board defective (defective thermistor input circuit)?
• Indoor unit return thermistor defective (element defective or broken wire). Defective connection of connector for thermistor.
• Indoor unit circuit board defective (defective thermistor input circuit)?
• Heating overload (temperature of heat exchanger for indoor unit abnormally high)
• Indoor unit heat exchanger thermistor defective (short circuit).
• Indoor unit circuit board defective (defective thermistor input circuit)?
• Failure with the condensate pump (DM), or open circuit or disconnection of connector with the condensate pump.
• Malfunctioning of the float switch (erroneous functioning)
Indoor unit circuit board
Failure in drainage
Float switch
Indoor circuit board
Number of indoor units connected
Insufficient refrigerant
•
•
• Indoor unit circuit board defective (defective float switch input circuit)
• Indoor unit circuit board defective (defective DM driving output circuit)
1 Remote controller for multiple unit control, 17 or more indoor units connected
Gas leak.
Indoor unit heat exchanger thermistor
Indoor unit circuit board
• Indoor unit heat exchanger thermistor defective (short circuit).
• Indoor unit circuit board defective (defective thermistor input circuit)?
19
(3) Error diagnosis procedures at the indoor unit side
To diagnose the error, measure the voltage (AC, DC), resistance, etc. at each connector around the circuit board of indoor unit based on the inspection display or the operation state of unit (no operation of compressor or blower, no switching of 4-way valve, etc.). If any defective parts are discovered, replace with the assembly of parts as shown below.
(a) Single-unit replacement parts for circuit board of indoor unit.
(Peripheral electric parts for circuit board.)
Indoor unit printed circuit board, thermistor (return, heat exchanger), operating switches, limit switches, transformers, fuses.
Note (1) Use normal inspection methods to determine the condition of strong electrical circuits and frozen cycle parts.
(b) Replacement procedure of indoor unit microcomputer printed circuit board
Microcomputer printed circuit board can be replaced with following procedure.
(i) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.)
Model
FDTN(P), FDEN(P)
FDKN(P)208
Parts number
PJA505A069
PHA505A007
Model
FDKN(P)258, 308
FDT, FDR, FDU, FDFL
Parts number
PHA505A008
PJA505A092Z
Parts layout on the indoor unit PCB
Models: FDTN (P), FDEN (P) series
SW3
SW2 (Only case of FDTN)
(Optional : For auto lift panel)
9 7 6 3 4 8 13 SW4
Power supply
52X6
52X5 52X4 52X7 52X1 52X2 52X3
SW3 SW2
SW4
SW5
For test mode selection
(Shortcircuit : Test mode)
Thermistor
(Return air, heat exchanger)
SW5
Receiving unit
Indiction lamps
Transformer, primary side
Transformer, secondary side for PCB
CNV CNT
External input / output function
Model: FDKN (P) series
For test mode selection
(Shortcircuit : Test mode)
Thermistor
(Return air, heat exchanger)
SW5
SW3
SW4
External input / output function
Receiving unit
Transformer, secondary side for PCB
Transformer, primary side
Power supply
20
• Function of jumper wires
Name
J1(SW5-1)
J2(SW5-2)
J3(SW5-3)
J4(SW4-1)
J5(SW4-2)
With
None
With
None
With
None
With
None
With
None
With
J6(SW4-3)
None
With
J7(SW4-4)
*1
None
With
J7(SW4-4) None
Function
1 Phase model
3 Phase model
Cooling only type
Heat pump type
Pulse input
Step input
—
Antifrost 2.5˚C
Antifrost 1˚C
With abnormality resetting
Without abnormality resetting
4 position louver control: valid
4 position louver control: invalid
FDKN208 type
FDKN258, 308 type
Note (1) *1 J7 (SW4-4) is for switching models on the FDKN (P) Series.
• Function of DIP switched (SW3)
Switch
SW3-1
SW3-2
SW3-3
SW3-4
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Function
Power off guaranteed
No power off guaranteed
With low-voltage detection control
Without low-voltage detection control
Power up mode (UHi-Lo)
Mild mode (Hi-Lo)
Indoor fan is Lo when heating thermostat is OFF.
Indoor fan is OFF when heating thermostat is OFF.
Model: FDT, FDR, FDU, FDFL series
SW4
SW2 (Only case of FDT)
(Optional : For auto lift panel)
SW3
9 7 6 3 4 8 13
52X6
52X5 52X4 52X7 52X1 52X2 52X3
SW4
SW5
SW2
SW1
SW3
SW1 address switch
SW5
For test mode selection
(Shortcircuit : Test mode)
Power supply
Thermistor
(Return air)
Thermistor
(Heat exchanger)
CNV CNT
Transformer, primary side Transformer, secondary side for PCB
• Function of DIP switched (SW3)
Switch
SW3-1
SW3-2
SW3-3
SW3-4
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Function
Power off guaranteed
No power off guaranteed
With low-voltage detection control
Without low-voltage detection control
Power up mode (UHi-Lo)
Mild mode (Hi-Lo)
Indoor fan is Lo when heating thermostat is OFF.
Indoor fan is OFF when heating thermostat is OFF.
External input / output function
• Function of DIP switched (SW4, 5)
Switch
SW4-1(J1)
SW4-2(J2)
SW4-3(J3)
SW5-1(J4)
SW5-2(J5)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Function
Antifrost 2.5˚C
Antifrost 1˚C
With abnormality resetting
Without abnormality resetting
4 position louver control: valid
4 position louver control: invalid
1 Phase model
3 Phase model
Step input
Pulse input
(ii) Please match the settings of control switching switches (SW3, SW4, SW5) to the settings they had before they were replaced. With these switches, if the printed circuit had a jumper wire before being replaced, set to jumper wire ON if there was a jumper wire and jumper OFF is these was not.
(iii) Connect the fast-on terminals and connectors that are to the circuit board for the micro-computer.
Connect by matching the wire color of the fast-on terminal with the color printed on the circuit board for the micro-computer.
Note (1) When connecting to the fast-on connection for the circuit board for the micro-computer, use care so as not to excessively distort the circuit board.
21
(c) Inspection method when there are fault lamps (display lamps on indoor unit).
(i) Only case of wireless remote control model
1 Defective indoor unit heat exchanger thermistor
Return air thermistor (Th
I-
A)
Indoor unit heat exchanger thermistor
(Th
I-
R)
Resistance temperature characteristics
Indoor unit
Check Lamp (yellow) 1 time flash
Defective indoor unit PCB Replacement (Defective indoor unit heat exchanger thermistor input circuit)
15
Is the indoor unit heat exchanger thermistor connector connection OK?
NO
Correction
YES
YES
Are characteristics of indoor unit heat exchanger thermistor OK or is not there any broken wire?
NO
Defective indoor unit heat exchanger thermistor Replacement
10
5
5k
Ω
at 25˚C
0 10 20 30 40
Temperature (˚C)
Note (1) 22.5 k
Ω
at -6˚C
50
2 Defective return air thermistor
Indoor unit
Check Lamp (yellow) 2 time flashes
Is the return air thermistor connector connection OK?
NO
Correction
YES
Is the return air thermistor characteristics
OK or is there a broken wire?
NO
Defective return air thermistor Replacement
YES
Defective indoor unit PCB
Replacement (Defective return air thermistor input circuit)
Note (1) Characteristics as per the above graph.
3 Drain abnormality
Indoor unit
Check Lamp (yellow) 4 time flashes
Is there any overflow?
NO
Is the float switch tripper?
NO
Defective indoor unit PCB Replacement (Defective DM driving output circuit, defective float switch input circuit)
YES
YES
Is the angle of drain piping good. Is there any problem?
Repair or replace the float switch
YES
Defective indoor unit PCB Replacement (Defective condensate motor output circuit)
NO
Is there output for condensate motor
(DM)?
(1)
Repair
YES
¡Check DM broken wire, burning, locking.
¡Are there any DM connector loose.
¡Are there any PCB faston terminal loose.
¡Are there any DM wire broken.
Note (1) Check if power source is there between DM connectors.
22
23
4 Abnormality casued by insufficient refrigerant.
Indoor unit
Check Lamp (yellow) 5 time flashes
Note (1) Refer to previous page for heat exchanger thermistor temperature resistance characteristic values.
Are the characteristic values for the heat exchanger thermistor OK?
YES
NO
Is the amount of refrigerant circulation good? (If refrigerant is insufficient, the capillary tubes may be plugged.)
YES
Printed circuit board for indoor unit no good replace.
NO
Replace heat exchanger thermistor.
Charge with refrigerant.
Replace capillary tubes.
5 Heating overload
Indoor unit
Check Lamp (yellow) 6 time flashes
Is the air filter clogged?
NO
Is the indoor unit heat exchanger thermistor connector connection OK?
NO
Correction
YES
YES
Washing
Are the heat exchanger thermistor characteristics OK, is
there no short circuit?
NO
Defective heat exchanger thermistor Replacement
YES
Note (1) To see whether or not it is overloaded, check the following:
( uIs the inside/outside air temperature too high?
uIs there any short circuit?
uIs the refrigerant excessive?
)
(1)
Is the heating under overload?
YES
NO
Defective indoor unit PCB
Replacement (Defective indoor unit heat exchanger thermistor input circuit)
Adjustment
(ii) Only case of wired remote control model
1 Error display : e 1 [Communication error between control switch ~ Indoor unit PCB]
• Normal voltage for control switch wiring (DC)
Between X and Z : 10.5 ~ 10.8 V
Between Y and Z : 5 ~ 10.8 V
Unit is normal
(Intrusion of accidental
noise on the control switch
cord)
YES
Is there
DC 10.8V between control switch circuit board connector (CnB) X
(Red) to Z
(Black)?
YES
Does the voltage oscillate between DC6 and 10V between control switch circuit board connector
(CnB) Y (White) to Z (Black)?
YES
Does the voltage oscillate between DC6 and
10V between indoor unit
PCB connector (CNB)
2 (White) to 3
(Black)?
YES Power supply reset
Is it normalized?
NO
NO NO
NO
Is there
DC 10.8V between indoor unit
PCB connector (CNB)
1 (Red) to 3
(Black)?
YES
Defective control switch PCB
The control switch wiring
(white) or (black) is broken or have a defective connection.
Defective control switch
PCB Replacement
Defective indoor unit PCB
Replacement
(1)
NO
Note (1) If it is normalized by changing PCB, judge the control switch or indoor unit PCB (Communication error between control switch and unit) is detective.
Defective indoor unit PCB
The control switch wiring (red) or (black) is broken or have a defective connection.
2 Error display : e 6 [Defective indoor unit heat exchanger thermistor]
Return air thermistor (Th
I-
A)
Indoor unit heat exchanger thermistor
(Th
I-
R)
Resistance temperature characteristics
Defective indoor unit PCB Replacement (Defective indoor unit heat exchanger thermistor input circuit)
15
Is the indoor unit heat exchanger thermistor connector connection OK?
NO
Correction
YES
YES
Are characteristics of indoor unit heat exchanger thermistor OK or is not there any broken wire?
NO
Defective indoor unit heat exchanger thermistor Replacement
10
5
5k
Ω
at 25˚C
0 10 20 30 40
Temperature (˚C)
Note (1) 22.5 k
Ω
at -6˚C
50
3 Error display : e 7 [Defective return air thermistor]
Is the return air thermistor connector connection OK?
NO
Correction
YES
Is the return air thermistor characteristics
OK or is there a broken wire?
NO
Defective return air thermistor Replacement
YES
Defective indoor unit PCB
Replacement (Defective return air thermistor input circuit)
Note (1) Characteristics as per the above graph.
4 Error display : e 8 [Heating overload]
Is the air filter clogged?
YES
Washing
NO
Is the indoor unit heat exchanger thermistor connector connection OK?
NO
Correction
YES
Are the heat exchanger thermistor characteristics OK, is
there no short circuit?
NO
Defective heat exchanger thermistor Replacement
YES Is the heating
(1) under overload?
YES
NO
Defective indoor unit PCB
Replacement (Defective indoor unit heat exchanger thermistor input circuit)
Note (1) To see whether or not it is overloaded, check the following:
( s Is the inside/outside air temperature too high?
sIs there any short circuit?
sIs the refrigerant excessive?
)
Adjustment
24
5 Error display : e 9 [Failure in drainage]
Is there any overflow?
NO
Is the float switch tripped?
NO
Defective indoor unit PCB Replacement (Defective DM driving output circuit, defective float switch input circuit)
YES
YES
Is the angle of drain piping good. Is there any problem?
Repair or replace the float switch
YES
Defective indoor unit PCB Replacement (Defective condensate motor output circuit)
NO
Is there output for condensate motor
(DM)?
(1)
Repair
YES
¡Check DM broken wire, burning, locking.
¡Are there any DM connector loose.
¡Are there any PCB faston terminal loose.
¡Are there any DM wire broken.
Note (1) Check if power source is there between DM connectors.
6 Error display : e 10 [1 Remote controller for multiple unit control Exceeding connected units (17 units or more)]
Are
17 or more unites connected to 1 remote controller?
NO
Remote controller defective
Replace
YES
Change to 16 units or less.
7 Error display : e 57 [Insufficient refrigerant]
Are the heat exchanger
(1) thermistor characteristic normal?
YES
Inspect at the unit side.
Insufficient refrigerant
NO
Defective heat exchanger thermistor Replacement
Recharge with (weighed amount) of refrigerant.
Inspect at the unit side.
During cooling
• Is indoor fan operating?
• Is the service valve (gas and liquid side) opened fully?
• Is there no short circuit?
Is the unit normalized?
NO
Defective indoor unit PCB
Replacement (Defective indoor unit heat exchanger thermistor input circuit)
Note (1) Refer to previous page for heat exchanger thermistor heat resistance characteristic values.
25
(4) Outdoor unit side (FDC(P)208~508 type, FDC808, 1008 type)
Check Indicator Table
Failure mode on the outdoor unit is indicated by flashing both Green LED (LED-G) and Red LED (LED-R) on the printed circuit board.
Outdoor unit LED
Red
Stays OFF
Failure at: Contents of the failure
Green
Keeps flashing
Stays OFF
Stays OFF
1 time flash
2 time flashes
Power wiring
Installation or operation status
Normal/Power is supplied.
• The outdoor power wiring is in reversed phase.
• Open phase at L3 phase (primary side).
• Incorrect set-up of outdoor unit PCB.
• Over current of the compressor motor.
• Open phase at L2 phase (secondary wiring of 52C) of compressor.
• Defective outdoor unit PCB.
• The wiring (secondary wiring of 52C) to the compressor is open.
Stays OFF
Stays OFF
Stays OFF
1 time flash
1 time flash
1 time flash
1 time flash
1 time flash
3 time flashes
4 time flashes
5 time flashes
1 time flash
2 time flashes
3 time flashes
4 time flashes
5 time flashes
CM wiring
Installation or operation status
Outdoor heat exchanger thermistor
Installation or operation status
Discharge gas thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
Discharge gas
thermistor
Installation or operation status
Failure to open the service valve
• The outdoor heat exchanger temperature is too high [70
°
C or over].
• Failure with the outdoor heat exchanger thermistor.
• The discharge gas temperature is too high.
• Failure with the discharge gas thermistor.
• Failure or open circuit with the outdoor heat exchanger thermistor or
imperfect connection of the connector.
• Failure or open circuit with the outdoor temperature thermistor or
imperfect connection of the connector.
• Failure with the discharge gas thermistor or imperfect connection of the
connector.
• The high pressure is too high or it went up (63H
1
, 49C).
• Closing of the service valve on the liquid/gas side.
“Check Indicator” is resetted when power supply is turned off once and the failure is fixed.
(a) Procedure for diagnosing trouble for outdoor unit
When diagnosing trouble for the outdoor unit, check the flashing and turns of the inspection indicator lamp (red LED) and fault indicator lamp (green LED) to obtain a general concept of the nature of the problem. Then inspect and perform repair.
1) Unit replacement parts related to printed circuit board for outdoor unit.
Micro-computer for outdoor unit, microcomputer, printed circuit board, thermistor (heat exchanger, discharge piping and outdoor air), fuses and transformer.
2) Summary of replacement for micro-computer for outdoor unit a) Check the following part number
Model
1 phase model
Parts No.
PCA505A046ZN
Model
3 phase model
Parts No.
PCA505A046ZS
Model
FDC808, 1008 model
Parts No.
PCA505A046ZC b) Set the overcurrent value using the overcurrent setting switch (SW3) for CM. Refer to the following table at the setting.
• Table of switch (SW3) setting
Model
Setting value (A)
FDC208HEN3A
FDCP208HEN3A
FDC258HEN3A
FDCP258HEN3A
FDC308HEN3
FDCP308HEN3
FDC308HES3
FDCP308HES3
FDC408HES3
FDCP408HES3
FDC508HES3
FDCP508HES3
FDC808HES3 FDC1008HES3
12 15 23 9 12 15 24 34
Table of switch setting
Make ON/OFF setting for each switch No.
( : ON, : OFF)
26
Parts layout on the outdoor unit PCB
Inspection display lamp
(LED·Red)
63H1 63H1
63H2 63H2
CNA1
PCB power supply connector
(Primary side)
Inspection display lamp
(LED·Green)
PCB power supply connector
(Secondary side)
SW3
CNA2
CNE
CT1
• Function of DIP switched (SW4)
SW4
2
(J4)
1 (J3)
ON
OFF
4 (J9)
3
(J5) ON
OFF
ON
OFF
ON
OFF
ON
OFF
Spare
Function
1 Phase model
3 Phase model
–
Compressor unit switching
Rotary
Reciprocal
Scroll
CNL
CNQ
SW6 SW4 SW5
• Function of DIP switched (SW5)
1
SW5
ON
OFF
2
ON
OFF
3
4
ON
OFF
ON
OFF
Function
Defrost Switching
Snow protection control
Test run Switch
Actual spot
Ordinary
Enabled
Disabled
Test run
Normal
Test run for heating
Test run for cooling
• Function of DIP switched (SW6)
1
(J17)
SW6
ON
OFF
2
(J18)
3
(J19)
ON
OFF
ON
4
(J20)
OFF
ON
OFF
Function
4-Way Valve Control
Defrost Circulation
Temperature Switching
63HI Abnormal detection switching
3 minute delay when power is turned on Switching
Enabled
Disabled
14˚C
18˚C
Enabled
Disabled
Enabled
Disabled
• Function of jumper wire
Name
With
J21
None
Function
Service valve open/close check control enabled.
Service valve open/close check control disabled.
27
(b) Inspection method when there are fault lamps (outdoor unit LED)
1 Open phase at L
3
phase (Primary side)
Red LED
Green LED
Outdoor unit
1 time flash
Stays OFF
Is
L
3
phase at primary side at open phase
NO
Defective outdoor unit PCB
Replacement
YES
Correction
2 Overcurrent of the compressor motor
Red LED
Green LED
Outdoor unit
2 time flashes
Stays OFF
Power supply checked at
L
1
-
L
2
,
L
1
-
L
3
or
L
2
-
L
3
phase of 52C secondary side?
YES
(1)
Compressor overcurrent?
NO
Defective outdoor unit PCB
Replacement (Defective
CT input circuit)
NO
YES
• 3 Phase: Open phase at
or
L
2
phase
L
1
• Is the power supply voltage correct
(not too low)?
• Are the power supply wires appropriate (not too thin)?
• Is the overcurrent setting correct
(SW3 setting)?
• Is not it operated under overload?
• Defective 52C
• 3 phase: Broken wire at
L
1
or
L
2 phase between 52C ~ CM or
TB
1
~ 52C
Inspect at the unit side.
• During cooling: Is FM
0 operating?
• At heating:
Is FM
1 operating?
Is the service valve (gas side) opened fully?
Is the filter clogged?
• Is it overcharged?
• Is the installation space of indoor outdoor unit adequate?
• Is there any short circuit on the indoor/ outdoor unit?
Note (1) Measure and check the current value.
Confirm that the overcurrent setting by SW
3
of outdoor unit PCB is correct.
3 The wiring (secondary wiring of 52C) to the compressor is open.
Red LED
Green LED
Outdoor unit
3 time flashes
Stays OFF
(1)
52C secondary side
L
2
or
L
3
phase open?
NO
(2)
Defective outdoor unit PCB
Replacement
(Defective CT circuit)
YES
Repair
Notes (1) When voltage is detected at 52C primary side
L
2
or
L
3 phase but not at the secondary side, check also 52C (broken coil, poor contact).
(2) When voltage is detected at 52C primary side
L
2
or
L
3 phase and there is no error at 52C (52C is energized if TB
1
L
2
or
L
3
terminal and 52C coil secondary side connector are short circuited), the outdoor unit PCB (defective X
01 circuit or X
01
) or indoor unit PCB (defective thermostat circuit) is defective.
28
4 The outdoor heat exchanger temperature is too high (70
°
C or over)
Red LED
Green LED
Outdoor unit
4 time flashes
Stays OFF
Are the heat
(1) exchanger thermistor
Charateristisc
Normal?
NO
Heart exchanger thermistor replacement
YES
Is the unit normalized
NO
Defective outdoor unit
PCB Replacement
(Defective heat exchanger thermistor input circuit)
(1)
Cooling, overload operation?
Check the unit side closely
• Is outdoor fan motor operating?
• Is the outdoor unit shortcircuited?
• Is the installation space adequate?
• Is there too much refrigerant?
Note (1) Outdoor unit heat exchanger thermistor detects the state of cooling overload operation.
Reset
Error stop
60
°
C 70
°
C
Outdoor unit heat exchanger temperature
5 The discharge gas temperature is too high. (Only case of FDC(P)208~508 type)
Red LED
Green LED
Outdoor unit
5 time flashes
Stays OFF
Is the discharge gas thermistror characteristics normal?
NO
Discharge pipe thermistor replacement
YES
Discharge gas temperature error?
(At cooling/heating operation)
Check the unit side.
• Insufficient refrigerant
Charge the refrigerant (measure)
• Is it the overload operation?
Check the unit side.
• During cooling: Is FMo operating?
• During heating: Is FM
I
operating?
Are control valves (both liquid, gas) fully opened during both cooling and heating.
• Is the installation space of indoor/
outdoor units adequate?
• Is there any short circuit air flow
for indoor/outdoor units?
Is the unit normalized
NO
Defective outdoor unit
PCB Replacement
(Defective discharge gas thermistor input circuit)
Error stop
Operable
90
°
C 135
°
C
Discharge pipe temp.
6 Defective outdoor unit heat exchanger thermistor
Red LED
Green LED
Outdoor unit
1 time flash
1 time flash
Is the outdoor unit heat exchanger themistor connector
OK?
YES
NO
Repair
Are the outdoor unit heat exchanger themistor characteristics OK, is there any broken wire?
YES
Defective outdoor unit PCB
Replacement (Defective outdoor unit heat exchanger thermistorinput circuit)
15
10
NO
Defective outdoor unit heat exchanger thermistor
Replacement
5
Outdoor unit heat exchanger thermistor (Th
O-
R) Resistance temperature characteristics
5k
Ω
at 25
°
C
0
°
C 10
°
C 20
°
C 30
°
C 40
°
C
Temperature
Note (1) 22k
Ω
at -6
°
C
50
°
C
29
7
Defective outdoor temperature thermistor
Red LED
Green LED
Outdoor unit
2 time flashes
1 time flash
Is the outdoor air temperature thermistor connector connection
OK?
NO
Repair
YES
Is the outdoor temperature thermistor characteristics OK, is there no broken wire?
NO
Defective outdoor temperature thermistor
Replacement
YES
400
Defective outdoor unit PCB
Replacement (Defective outdoor temperature thermistor input circuit)
Temperature-resistance characteristics of outdoor temperature thermistor (Th
O-
A)
40
300 30
200
100
T < 0
°
C
T > 0
°
C
20
10
0
–50
°
C
0
0
°
C
Temperature [T]
50
°
C
8 Defective discharge gas thermistor (Only case of FDC(P)208~508 type)
Red LED
Green LED
Outdoor unit
3 time flashes
1 time flash
Is the discharge gas thermistor connector connection
OK?
NO
Repair
YES
Are the discharge gas thermistor characteristics
OK, is there no broken wire?
YES
NO
Defective discharge gas thermistor Replacement
Defective outdoor unit PCB
Replacement (Defective discharge gas thermistor input circuit)
Temperature-resistance characteristics of discharge gas thermistor (Th
O-
D)
100
T< 80
°
C
T> 80
°
C
10
50 5
0
0
°
C 20
°
C 50
°
C 80
°
C 100
Temperature [T]
°
C 120
°
C
0
30
9 High pressure error [63H
1
] (Only case of FDCP208~508 type)
Red LED
Green LED
Outdoor unit
4 time flashes
1 time flash
Did 63H
1 operate?
YES
At 63H1 opration
•
Is the outdoor unit fan motor operating?
•
Is there no shortcircuit in the outdoor unit?
•
Is sufficient space reserved for suction or discharge?
•
Is not the refrigerant charge excessive?
NO
Defective outdoor unit PCB
Replacement (Defective 63H
1
, input circuit)
63H1, 49C operation (Only case of FDC808, 1008 type)
Red LED
Green LED
Outdoor unit
4 time flashes
1 time flash
Did 63H
1
,operate?
NO
Defective outdoor unit PCB
Replacement (Defective 63H
1
, input circuit)
YES
At 63H
1
operation
1. During cooling
• Is the outdoor unit fan motor operating?
• Is there no short circuit air circulation for thr outdoor unit?
• Is there sufficient space for air inlet & outlet?
2. During heating
• Is the gas side service valve fully opened?
• Is the indoor unit heat exchanger sensor detached from the detector case?
• Is the filter clogged?
• Is the outdoor unit fan controlled by due to defective
63H
2
?
3. During colling/heating
• Is the refrigerant charge excessive?
At 49C operation
During cooling/heating
• Isn't there insufficient refrigerant?
(Isn't there gas leakage?)
• Isn't there a missing phase (
L
1
or
L
2
phase)?
10 Failure to open the service valve
Red LED
Green LED
Outdoor unit
5 time flashes
1 time flash
This abnormality will be indicated only when the compressor is ON for the time after turning on the power. (Refer to page 331)
31
AIR CONDITIONING AND HEAT PUMP SYSTEMS
NOTICE
The installation of this equipment must comply with all
NATIONAL, STATE and LOCAL CODES.
This Service Guide does not cover all installation circumstances and is meant for guidance only and therefore will not form part of any legally binding contract. An installation guide is provided with the air conditioning equipment.
CE
This Air Conditioner complies with: -
EMC Directive 89/336/EEC
LV Directive 73/23/EEC
3D Air Sales Ltd
Sales & Marketing Office
850 Brighton Road,
Purley, Surrey, CR8 2BH
Telephone: 020 8668 1112
Facsimile: 020 8668 1113
3D Air Sales (Ireland) Ltd
Unit 21, Western Industrial Estate,
Nass Road, Dublin12, Ireland
Telephone: 01 450 9433
Facsimile: 01 450 9799
3D Air Sales Ltd
Warehouse, Sales Admin., Spares, Warranty
Anglia House, Priors Way,
Coggeshall, Essex, CO6 1TL
Telephone: 01376 565 505
Facsimile: 01376 565 525
3D Air Sales Ltd
Scottish Sales Office
McGregor House, Southbank Business Park,
Kirkintilloch, Glasgow, G66 1XF
Telephone: 0141 777 5007
Facsimile: 0141 777 5009
advertisement
Related manuals
advertisement