www.altronics.com.au
®
A 4572 Emergency
Evacuation Controller
Operating Instructions
-This half rack unit has both Alert and Evacuation tones based on Australian standard AS1670.4. The unit is triggered via standard alert/evac switches on the front of the unit or via remote trigger contacts on the rear. It features a 24V switched output which is enabled when the Alert, Evac or Chime tones are triggered. It is powered from a 24V DC source and features a line out facility and Voice Over.
Features
• Level controls for alert/evac, bell and voice over
• Front panel alert/evac/bell and cancel switches
• External contacts for alert, evac or bell by switching to ground
• All tones crystal locked
• Emergency tones can be configured for momentary or continuous operation
• 1U half rack cabinet
• Tones conform to AS 1670.4
• Compatible with fire indicator boards & break glass alarms
• Remote operation of alert , evac, bell tones & cancel.
• Local operation of alert, evac and bell
• Evac voice over message on board
• Bell chime facility
• Switched 24V DC out for override relays on volume controls
• Switched 24V DC out for strobe operation for alert mode.
• Switched 24V DC out for strobe operation for evac mode.
• Switched 24VDC out for bell mode.
• On-board timer for remote alert activation adjustable from 30secs to 7.5min in 30 second increments. Switches from alert to evac after preset time.
• Auxiliary level output
• 10 year warranty
• Australian designed and manufactured
Distributed by Altronic Distributors Pty. Ltd. Perth. Western Australia.
Phone: 1300 780 999 Fax: 1300 790 999 Internet: www.altronics.com.au
Proudly Assembled in Australia
REDBACK A 4572 Emergency Evacuation Controller
Wiring Up The Unit
Power Connections
24VDC input is provided via 2.1mm DC jack.
Microphone Input
Microphone input is provided by 3 pin euro block connection.
Remote Contacts (Rear of unit)
Provision has been made for four remote contacts on the back of the unit. These are all activated by closing the corresponding contact
(connecting the terminals together).
Alert contact: These contacts are for remote triggering of the alert tone ie: for use with Fire Indicator Boards, break glass alarms etc.
These contacts can be set to either continuous or momentary operation via dip switch 5. ( refer Table 2)
In continous mode the alert tone will continue while the alert contact is triggered.
In momentary mode the alert tone will continue to sound after a momentary trigger of the alert contact.
Evac Contacts: These contacts are for remote triggering of the evac tone. Connecting these terminals together will activate the evac tone. These contacts can be set to either continuous or momentary operation via dip switch 5. ( refer Table 2)
In continous mode the evacuation tone will continue while the evac contact is triggered.
In momentary mode the evacuation tone will continue to sound after a momentary trigger of the evac contact.
Cancel contact: These contacts are for remote cancelling of the alert or evac tones.
The alert, evac and cancel remote contacts can be triggered with the
Altronics A 2078A remote wall plate (see figure 3 - typical wiring diagram) or any closing contact.
Bell Chime Contacts: These contacts are for remote triggering of the bell chime sound. This bell chime can be used for signalling lunch breaks, start of classes, and can be triggered from a time clock or similar device. For details of this, see Installation instructions for the bell tone. Connecting these terminals will activate the bell.
Audio Output:
This output consists of stereo RCA sockets with an output of 0dBm into a 600
Ω input. This is suitable for most PA amplifier auxiliary inputs.
24V Output Connections:
Switched 24V Out: These contacts are for connection of override relays in remote volume controls. An override relay is necessary where attenuators are used so that the alert tone, evac tone or message is broadcast at full volume regardless of the volume setting on the individual volume control (attenuator).
The override relay can be set to “NORMAL” mode when connection is made between the N/O (normally open) contact and the GND connection. In this configuration 24V appears when any of the alert tone, evac tone, voice over message or paging functions are activated.
The override relay can be set to “FAILSAFE” mode when connection is made between the N/C (normally closed) contact and the GND connection. In this configuration 24V is removed when any of the alert tone, evac tone, voice over message or paging functions are activated.
Alert/Evac 24V Out: These contacts are for switched 24V outputs whenever the alert or evac tones are activated. These may be used to run external systems such as strobes in unusually noisy environments.
These operate in the same manner as the switched 24V out contacts ie: connection between the N/O contact and the GND contact will operate in NORMAL mode and connection between the N/C contact and the GND will operate in FAILSAFE mode.
Bell 24V Out: These contacts are for operating an external relay used to operate something like a lunch bell etc.
These operate in the same manner as the switched 24V out contacts ie: connection between the N/O contact and the GND contact will operate in NORMAL mode and connection between the N/C contact and GND will operate in FAILSAFE mode.
DIP Switches:
Switches 1-4 Evacuation Timer Settings: These switches control the time period before the unit switches from the alert to the evac tone
(rear contacts only). This time period can be switched from 30s to 7.5
minutes in 30s increments. See table 1 for more information. Factory preset is 30s.
Page 2
DIP Switch Settings
Auto Evac DIP Switch
Timer 1
30 sec ON
2
OFF
3
OFF
4
OFF
60 sec OFF ON OFF OFF
90 sec ON ON OFF OFF
120 sec OFF OFF ON OFF
150 sec ON OFF ON OFF
180 sec OFF ON ON OFF
210 sec ON ON ON OFF
240 sec OFF OFF OFF ON
270 sec ON OFF OFF ON
300 sec OFF ON OFF ON
330 sec ON ON OFF ON
360 sec OFF OFF ON ON
390 sec ON OFF ON ON
420 sec OFF ON ON ON
450 sec ON ON ON ON
DIP sw.
5
6
DIP sw.
7
8
DIP switch 5 & 6 settings
OFF
Latched/Continuous operation of alert & evac on rear contacts
ON
Momentary operation of alert & evac on rear contacts
Voice-over off
Table 2.
DIP switch 7 & 8 bell options
OFF
Latched/Continuous operation
Latched/Continuous tone
ON
Momentary operation
Repeating bong
Table 3.
Voice-over on
Table 1.
REDBACK A 4572 Emergency Evacuation Controller
1
Figure 2. Rear panel
1. DC Fuse
2. 24VDC Input
3. DIP Switches 1-8
2 3 4 5
4. Contacts Cancel/Evac/Alert/Bell
5. 24V Output Switched/Bell/Evac/Alert
6. Microphone Input
6 7 8
7. Audio Output
8. Volume Level Chime/Tones/Voiceover
9. Message Record Button
9
Switch 5: DIP switch 5 is used to set the ‘Alert and Evac’ contacts to momentary or alternate (See ‘Remote Contacts’ on page 2).
Switch 6 Voice Over Setting: DIP switch 6 is used to configure the voice over message.
OFF: Voice over will not play during the evac cycle
ON: Voice over will play during the evac cycle.
Switch 7 Bell Setting:
DIP switch 7 sets the bell to either continuous or momentary mode.
This is regardless of the bell being activated via the front bell switch or the rear bell contact.
In continuous operation the bell will sound for as long as the bell switch or rear contact is triggered.
In momentary operation the bell will sound for only a short period regardless of how long the bell is triggered.
OFF: Latched/Continuous operation
ON: Momentary operation
Switch 8 Bell Output Setting: DIP switch 8 sets the bell output to either a continuous or repeating “bong” tone.
OFF: Single continuous tone
ON: Repeating “bong” tone
Record Button: This button is used to activate recording mode for voice over message.
Alert/Evac Switches (Front Panel):
The alert and Evac switches on the front of the unit both work in momentary mode. ie. The alert tone will continue to sound after the alert switch is momentarily pressed and the evac tone will continue to sound after the evac switch is momentarily pressed. There is no automatic alert to evac switch-over option associated with the front panel switches.
Note 1: The tone that is being sounded (ie alert, evac, bell) will be indicated by the illumination of the relevant front panel indicator.
Note 2: To cancel a tone either use the remote cancel contacts or the front cancel button. Note the cancel button will need to be depressed for 2 seconds. This is to prevent accidental cancelling of a tone.
Rear Panel Volume Controls:
Tones: This sets the output level of the alert & evac tones.
Chime: This sets the output level of the bell.
V/over: This sets the output level of the message voice over.
Instructions for Use
Mains Power Switch. This switches 24V DC power to the unit on and off.
LED Power Indicator. This LED will be lit when the unit is being powered.
Alert/Evac Tones: If the alert tone is triggered via the rear contacts and is set to continue the alert tone will sound for a preset time determined by DIP switches 1-4 (see Table 1). After this preset time the unit will automatically switch over to the evacuation tone. The unit will sound the evac tone for four cycles, sound the voice over message twice (if selected “on” via dip switch 6), then sound the evac tone for four cycles, and continue in this evac/voice over sequence until the tone is cancelled. The tone can be cancelled by triggering the cancel trigger on the rear of the unit or by pressing the cancel switch on the front of the unit.
Recording of Voice Over Message
1. Connect a microphone to the 3 pin euro block on the rear of the unit.
2. Hold down the record button on the rear of the unit. Recording will start when the button is pressed and held. Recording will continue until the button is released. The recorded message will play back when the record button is released.
3. To re-record the message simply follow repeat step 2.
Page 3
REDBACK A 4572 Emergency Evacuation Controller
PA Amplifier
Alert
Strobe
Evac
Strobe
Bell
Attenuators
A 2078B Remote
Wallplate
RCA Out 24V Switched Outputs
A 4572
Contacts
Fire Board
Figure 3. Typical system wiring diagram.
Symptom
Low Level Recording
Troubleshooting
Solution
Ensure that a good quality mic is being used and the operator is speaking clearly into the mic.
Mic Volume Level is Low Adjust Mic Volume
Alert/Evac Tone Levels are Low Adjust Tone Volume
No power to unit.
Check fuse and replace with M205 type 500mA fuse if required. Check power to unit. If power is OK,and unit still fails to power up, refer to authorised servicing centre.
Specifications
OUTPUT LEVEL:....................................................................0dBm
DISTORTION:........................................................................0.01%
FREQ. RESP.: ..........................................................140Hz - 20kHz
SIGNAL TO NOISE RATIO:
Alert/Evac/Chime: ............................................-70dB typically
INPUT SENSITIVITY:
Mic: ....................................................................2mV Balanced
OUTPUT CONNECTORS:
Audio Output:...............................................RCA Stereo Socket
Switched 24V DC Out: ....................................Screw Terminals
Alert 24V DC Out :.........................................Screw Terminals
Evac 24V DC Out: ...........................................Screw Terminals
Bell 24V DC Out:.............................................Screw Terminals
PLEASE NOTE: Maximum combined output load should not exceed
1Amp.
INPUT CONNECTORS:
Mic: ........................................................3 Pin Screw Terminals
24V DC Power:.................................................2.1mm DC jack
Remote Alert, Evac, Bell, Cancel: ..................Screw Terminals
CONTROLS:
Mic Input:..............................................................Rear Volume
Alert, Evac, Bell Tones: ........................................Rear Volume
Voice over: ............................................................Rear Volume
Power:.................................................................On/Off Switch
Alert Switch: ........................................Illuminated Push Switch
Evac Switch: ........................................Illuminated Push Switch
Bell Switch: ..........................................Illuminated Push Switch
Cancel Switch:.......................................................Push Switch
INDICATORS: ...............................................Power on, Record LED
POWER SUPPLY:................................................................24V DC
DIMENSIONS: .............................................
≈ 210W x 145D x 44H
WEIGHT:...........................................................................
≈ 0.4 kg
COLOUR:................................................................................Black
* Specifications subject to change without notice.