Mitsubishi Electric KA60VA is a powerful air conditioner that provides efficient cooling and heating for your home. With its impressive airflow and fan speed, it can maintain a comfortable temperature even in large rooms. It also features a range of user-friendly functions, such as a remote control for easy operation and a timer to program your desired settings. Additionally, the KA60VA boasts a stylish design that will complement your home décor.
advertisement
OC321A.qxp 06.8.28 3:45 PM Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
September 2006
No.OC321
REVISED EDITION-B
Indoor unit
[Model names]
SEZ-KA35VA
SEZ-KA50VA
SEZ-KA60VA
SEZ-KA71VA
[Service Ref.]
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
Revision:
•RoHS PARTS LIST is added in REVISED EDITION-B.
•Some descriptions have been modified.
•Please void OC321
REVISED EDITION-A.
Note:
• This manual describes only service data of the indoor units.When servicing outdoor units, please refer to the service manual
No.OC322, OC323 together with this manual.
• RoHS compliant products have <G> mark on the spec name plate.
• For servicing of RoHS compliant products, refer to the RoHS Parts List.
INDOOR UNIT
Model name indication
CONTENTS
1. PART NAMES AND FUNCTIONS ········2
2. SPECIFICATIONS·································4
3. OUTLINES AND DIMENSIONS············9
4. WIRING DIAGRAM·····························10
5. REFRIGERANT SYSTEM DIAGRAM·······11
6. TROUBLESHOOTING ························12
7. DISASSEMBLY PROCEDURE···········22
8. PARTS LIST········································25
9. RoHS PARTS LIST·····························27
10. OPTIONAL PARTS ·····························29
TEMP.
ON/OFF
WIRED REMOTE
CONTROLLER
OC321A.qxp 06.8.28 3:45 PM Page 2
1 PART NAMES AND FUNCTIONS
Indoor Unit
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
Air outlet
Air outlet duct flange
Air inlet
(Selecting the either back side or bottom side)
Wired remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
●
Operation buttons
Start/Stop button
Fan Speed button
Set Temperature buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the door
TEMP.
ON/OFF
MENU
BACK MONITOR/SET
PAR-21MAA
ON/OFF
DAY
CLOCK OPERATION
FILTER
CHECK TEST
CLEAR
Filter button
(<return sign> button)
Test Run button
Service button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To preceding operation number
Ventilation button
( Operation button)
To next operation number
2
OC321A.qxp 06.8.28 3:45 PM Page 3
● Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is supported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
˚F˚C
TIME SUN MON TUE WED THU FRI SAT
TIMER Hr ON
AFTER AFTER OFF
ERROR CODE
˚F˚C
ONLY1Hr.
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller sensor is used.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set.
If the simple or Auto Off timer is set, shows the time remaining.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
Low and downward during COOL or DRY mode. (Operation varies according to model.)
The indicator goes off after one hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Caution
● Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
● If you press a button for a feature that is not installed in the indoor unit, the remote controller will display the “Not Available” message.
If you are using the remote controller to operate multiple indoor units, this message will appear only if the feature is not present at the parent unit.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappears then start the operation.
3
OC321A.qxp 06.8.28 3:45 PM Page 4
2 SPECIFICATIONS
Indoor model
Function
Power supply
Capacity Air flow (High/Low)
Power outlet
Running current ✽ 1
Power input Rated frequency
Auxiliary heater
Fan motor current ✽ 1
Model
Winding resistance (at20 : )
Dimensions W o H o D
Weight
Air direction
Sound level (High/Low)
Fan speed (High/Low)
Fan speed regulator
External satatic pressure
Thermistor TH1 (at 25 : )
Thermistor TH2 (at 25 : )
Thermistor TH5 (at 25 : )
K /h
A
A
W
A(kW)
A
" mm kg dB(A) rpm
Pa k k k
"
"
"
SEZ-KA35VA.TH
Cooling
Single phase
230V, 50Hz
780/600
10
0.40
Heating
60
—
0.22
PK6V19-EF
WHT-BLK : 257 BLK-BLU : 20
BLU-YLW : 27 YLW-BRN : 14
BRN-RED : 51(at 26 : )
1100 o 270 o 700
33.5
1
35/30
770/630
3
Std : 30 Max : 50
10
10
10
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor D.B. 27 : W.B. 19 :
Outdoor D.B. 35 : W.B. 24 :
Heating : Indoor D.B. 20 : W.B. 15 :
Outdoor D.B. 7 : W.B. 6 :
Refrigerant piping length (one way): 5m
✽ 1 Measured under rated operating frequency.
SEZ-KA50VA.TH
Cooling Heating
Single phase
230V, 50Hz
1020/720
20
0.55
80
—
0.27
PK6V32-EF
WHT-BLK : 166 BLK-BLU : 52
BLU-YLW : 19 YLW-BRN : 8
BRN-RED : 40(at 26 : )
1100 o 270 o 700
33.5
1
39/31
840/640
3
Std : 30 Max : 50
10
10
10
Specifications and rating conditions of main electric parts
INDOOR UNIT
Model
Item
Indoor fan capacitor
Fuse
Varistor
(C1)
(FUSE)
(ZNR)
Terminal block
Indoor fan motor thermal fuse
(TB)
SEZ-KA35VA.TH SEZ-KA50VA.TH SEZ-KA60VA.TH SEZ-KA71VA.TH
SEZ-KA35/50VA.TH : 2.5
+ 440V SEZ-KA60VA.TH : 3.0
+ 440V SEZ-KA71VA.TH : 4.0
+ 440V
250V 6.3A
ERZV10D471
TO OUTDOOR UNIT : 3P TO WIRED REMOTE CONTROLLER : 2P
141 : i
3 :
4
OC321A.qxp 06.8.28 3:45 PM Page 5
Indoor model
Function
Power supply
Capacity Air flow (High/Low)
Power outlet
Running current ✽ 1
Power input Rated frequency
Auxiliary heater
Fan motor current ✽ 1
Model
Winding resistance
Dimensions W o H o D
Weight
Air direction
Sound level(High/Low)
Fan speed(High/Low)
Fan speed regulator
External satatic pressure
Thermistor TH1 (at 25 : )
Thermistor TH2 (at 25 : )
Thermistor TH5 (at 25 : )
K /h
A
A
W
A(kW)
A
" mm kg dB(A) rpm
Pa k k k
"
"
"
SEZ-KA60VA.TH
Cooling
Single phase
230V, 50Hz
1200/720
20
0.65
Heating
100
—
0.39
PK6V50-EF
WHT-BLK : 103 BLK-BLU : 57
BLU-YLW : 15 YLW-BRN : 7
BRN-RED : 29 (at 26 : )
1100 o 270 o 700
33.5
1
43/32
890/660
3
Std : 30 Max : 50
10
10
10
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor D.B. 27 : W.B. 19 :
Outdoor D.B. 35 : W.B. 24 :
Heating : Indoor D.B. 20 : W.B. 15 :
Outdoor D.B. 7 : W.B. 6 :
Refrigerant piping length (one way): 5m
✽ 1 Measured under rated operating frequency.
SEZ-KA71VA.TH
Cooling
Single phase
230V, 50Hz
1200/720
20
0.60
Heating
130
—
0.51
PK4V60-EA
WHT-BLK : 108 BLK-BLU : 29
BLU-YLW : 26 YLW-BRN : 14
BRN-RED : 34 (at 26 : )
1100 o 270 o 700
35
1
43/32
1050/690
3
Std : 30 Max : 50
10
10
10
5
OC321A.qxp 06.8.28 3:45 PM Page 6
NOISE CRITERION CURVES
SEZ-KA35VA.TH
NOTCH
High
Low
<50Hz>
SPL(dB)
35
30
LINE
90
80
SEZ-KA50VA.TH
90
80
NOTCH
High
Low
<50Hz>
SPL(dB)
39
31
LINE
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
20
10
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125
NC-20
250 500 1000 2000
BAND CENTER FREQUENCIES, Hz
4000 8000
SEZ-KA60VA.TH
SEZ-KA71VA.TH
NOTCH
High
Low
<50Hz>
SPL(dB)
43
32
LINE
90
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
20
10
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125 250 500 1000 2000
BAND CENTER FREQUENCIES, Hz
4000
NC-20
8000
80
UNIT
70
NC-70
60
NC-60
External static
pressure 30Pa
1.5m
50
NC-50
40
MICROPHONE
NC-40
30
NC-30
20
10
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125
NC-20
250 500 1000 2000
BAND CENTER FREQUENCIES, Hz
4000 8000
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
6
OC321A.qxp 06.8.28 3:45 PM Page 7
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KA35VA.TH
Corrected Air flow
Cooling
1.1
Fan Performance
Recommended range 1.0
80
0.9
0.8
60 5
Heating
10 15
Air flow ( K / X )
20
40
1.3
20
1.2
1.1
1.0
0
5 7 10 15
Air flow ( K / X )
20 25
0.9
0.8
5 10 15
Air flow ( K / X )
20
SEZ-KA50VA.TH
Corrected Airflow
Cooling
Fan Performance
Recommended range
1.1
80
60
1.0
0.9
0.8
5
Capacity
Input
25
25
Capacity
Input
10 15
Air flow ( K / X )
20 25
40
Heating
20
1.2
1.1
0
5 10 15 20
Air flow ( K / X )
25
1.0
0.9
0.8
5 10 15
Air flow ( K / X )
20 25
7
OC321A.qxp 06.8.28 3:45 PM Page 8
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KA60VA.TH
80
60
40
Fan Performance
Recommended range
20
0
5 10 15
Air flow ( K / X )
20 25
1.3
1.2
1.1
1.0
0.9
1.1
1.0
0.9
0.8
Corrected Air flow
Cooling
Capacity
Input
10 15 20
Air flow ( K / X )
Heating
25 30
10 15 20
Air flow ( K / X )
25 30
SEZ-KA71VA.TH
Fan Performance
Recommended range
80
60
40
20
0
5 10 15
Air flow ( K / X )
20 25
1.3
1.2
1.1
1.0
0.9
1.1
1.0
0.9
0.8
Corrected Air flow
Cooling
Capacity
Input
10 15 20
Air flow ( K / X )
Heating
25 30
10 15 20
Air flow ( K / X )
25 30
8
OC321A.qxp 06.8.28 3:45 PM Page 9
3 OUTLINES AND DIMENSIONS
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
Air inlet (rear side) dimensions
42 930
(Inlet size)
In case of bottom side suction, mount the PLATE (A) on the rear side.
After installation, remove the transportation support PLATE (B).
Unit : mm
Air inlet (bottom side) dimensions
PLATE (A)
29
77.5
100
50
27
7 x 100=700
955
24{ 2.9 holes
1016
Air inlet
(rear side) w Select the either back side or bottom side.
PLATE (B) x 2
150
77
450
Electrical parts box
51 930
(Inlet size)
39 77.5
100 7 x
100=700
955
24{ 2.9 holes
Access door
Service space
(It is necessary to maintain a working
service area from the ceiling.)
Suspension bolt
M10 or 3/8
(procure locally)
40
50
100 7 x
100=700
9 x 2{ 2.9 holes
880
Air outlet
1070
Suspension bolt pitch
(1070)
(Suspension bolt pitch)
Air outlet duct flange
(10) 50
Refrigerent pipe (gas)
Refrigerent pipe (liquid)
Wiring entry
Terminal block
Electrical parts box
1100
Air inlet
(bottom side)
Access door w Select the either back side or bottom side.
2 x 2holes
{ 2.9
Air outlet duct flange
94 80
350
Electrical parts box
Drain plug R1 (male)
Models
SEZ-KA35VA
SEZ-KA50VA
SEZ-KA60VA
SEZ-KA71VA
Refrigerent pipe
(liquid)
{ 6.35mm
flared connection
1/4F
{ 6.35mm
flared connection
1/4F
{ 6.35mm
flared connection
1/4F
{ 9.52mm
flared connection
3/8F
Refrigerent pipe
(gas)
{ 9.52mm
flared connection
3/8F
{ 12.7mm
flared connection
1/2F
{ 15.88mm
flared connection
5/8F
{ 15.88mm
flared connection
5/8F
9
OC321A.qxp 06.8.28 3:45 PM Page 10
4 WIRING DIAGRAM
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
MF
TB4
S1
S2
S3
TO OUTDOOR
UNIT
C1
ORN
RED
1 2 3 4 5 6
1 2 3 4 5 6
7
7
8
8
<fig: w
1>
MODELS
KA35
KA50
KA60
KA71
SW2
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
1 2 3 4 5 6 7
WHT
(FAN)
FAN
X6 X5 X4
X6 X5 X4
SWE
ON
OFF
SW2
ON
OFF
1 2 3 4 5
SW3
ON
OFF
1 2 3 4 5
CN32
CN2L
CN51 CN41
See fig: w
1
[LEGEND]
SYMBOL
P.B
I.B
CN2L
CN32
CN41
SWE
X4
X5
X6
ZNR
CN51
CN90
FUSE
LED1
LED2
LED3
SW2
SW3
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CENTRALLY CONTROL
CONNECTOR(WIRELESS)
FUSE(T6.3AL250V)
POWER SUPPLY(I.B)
POWER SUPPLY(I.B)
TRANSMISSION(INDOOR-OUTDOOR)
SWITCH(CAPACITY CODE)
SWITCH(MODE SELECTION)
SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR LL)
RELAY(FAN MOTOR Lo)
RELAY(FAN MOTOR Hi)
VARISTOR
SYMBOL
C1
MF
TB4
TB15
TH1
TH2
TH5
NAME
CAPACITOR(FAN MOTOR)
FAN MOTOR
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0 ° C/15k Ω ,25 ° C/5.4k
Ω DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0
°
C/15k
Ω
,25
°
C/5.4k
Ω
DETECT)
COND./EVA.TEMP.THERMISTOR
(0
°
C/15k
Ω
,25
°
C/5.4k
Ω
DETECT)
NOTES: 1.Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make
wiring matching terminal numbers(S1,S2,S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal(block).
4.Since the indoor fan motor(MF) is connected with 50Hz power,
if 60Hz power is used, change the wiring connection shown in
fig: w 2.
<fig: w 2>
50
Indoor Fan Motor(MF) for 60Hz
BLUE 60
YELLOW
BLUE w For details on how to operate self-diagnosis,
refer to the technical manuals etc.
10
CN90
P.B
1 2 3 AC220-240V
CNSK(RED)
1 3
RED
(POWER
BOARD)
CNDK
FUSE
1 3
ORN
(POWER)
CND
LED3
1 3
BLU
(CONTROL)
CN3C
I.B
TRANS
ZNR
WHT
(POWER
BOARD)
CN2D
1
2
BLK
WHT
LED1
BLK
CN29
RED
(2 PHASE) (INTAKE)
CN20
1 2 1 2
LED2
WHT
(LIQUID)
CN21
1 2
BLU
(REMOCON)
CN22
1 2
1 2
DC13.1V
CN2S(WHT)
TH5 TH1 TH2
TB15
1
2
} TO MA-REMOTE
CONTROLLER
DC8.7-13V
OC321A.qxp 06.8.28 3:45 PM Page 11
5 REFRIGERANT SYSTEM DIAGRAM
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
Heat exchanger
Condenser/evaporator temperature thermistor
(TH5)
Strainer
#50
Refrigerant GAS pipe connection
(Flare)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Room temperature thermistor (TH1)
Distributor with strainer
#50
Pipe temperature thermistor/liquid
(TH2)
Strainer
#50
11
OC321A.qxp 06.8.28 3:45 PM Page 19
6-5. TEST POINT DIAGRAM
6-5-1. Indoor power board
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
CN2S
Connect to the indoor controller board (CN2D) between 1 to 3 12.6-13.7V DC (Pin 1 (+))
CNSK
Connect to the indoor controller board
(CNDK) between 1 to 3 220-240V AC
19
OC321A.qxp 06.8.28 3:45 PM Page 20
6-5-2. Indoor controller board
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
Non polarity
CND
Power supply input
(220~240V AC)
CN2D
Connector to the indoor power board (CN2S)
(12.5~13.7V DC)
LED1
Power supply
(I.B)
LED2
Power supply
(R.B)
LED3
Transmission
(Indoor/outdoor)
–
–
CN22
}
Remote controller connecting wire
(10.4~14.6V DC)
CN20
Room temperature thermistor (TH1)
CN21
Pipe temperature thermistor/Liquid
(TH2)
FUSE
(6.3A 250V)
CNDK
Connect to the indoor power board (CNSK)
(220~240V AC)
CN29
Condenser/evaporator temperature thermistor
(TH5)
CN41
Connector
(HA terminal-A)
FAN
Fan motor output
CN51
Centrally control
CN2L
Connector
(LOSSNAY)
Jumper connector
J11~J15
Unit setting
SW3
Mode selection
SWE
Emergency operation
SW2
Capacity setting
20
OC321A.qxp 06.8.28 3:45 PM Page 21
6-6. TROUBLE CRITERION OF MAIN PARTS
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
Part name
Room temperature thermistor
(TH1)
Pipe temperature thermistor/liquid
(TH2)
Condenser/evaporator temperature thermistor
(TH5)
Indoor fan motor
(MF)
Check method and criterion
Measure the resistance with a tester.
(Part temperature 10
°
C ~ 30
°
C)
Normal
8k
Ω
~20k
Ω
Abnormal
Opened or short-circuited
P
BLK BLU YLW BRN RED ORN
WHT
P : Thermal fuse
141
±
3˚C
GRN
YLW
Measure the resistance between the terminals with a tester.
(Coil wiring temperature 10
°
C ~ 30
°
C)
WHT-BLK
BLK-BLU
BLU-YLW
YLW-BRN
BRN-RED
KA35VA
270~244
Ω
19~21
Ω
25~29
Ω
13~15
Ω
48~54
Ω
Normal
KA50VA
157~175
Ω
49~55
Ω
18~20
Ω
7~9
Ω
38~42
Ω
KA60VA
97~109
Ω
54~60
Ω
14~16
Ω
6~8
Ω
27~31
Ω
KA71VA
103~113
Ω
28~30
Ω
25~27
Ω
13~15
Ω
32~36
Ω
Abnormal
Opened or short-circuited
21
OC321A.qxp 06.8.28 3:45 PM Page 22
7 DISASSEMBLY PROCEDURE
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
OPERATING PROCEDURE
1. Removing the electrical parts
(1) Remove 2 screws of electrical cover and electrical parts cover.
(See Photo 1)
● Indoor controller board (I.B)
● Terminal block (TB4,TB15)
● Indoor power board (P.B)
● Fan motor capacitor (C1)
(See Photo 2)
Photo 1
PHOTOS
Service panel
(Pipe temperature thermistor / liquid)
Electrical parts cover
Drain pan Set screws
2. Removing the pipe temperature thermistor (TH2)
(1) Remove the electrical parts cover. (Refer to 1)
(2) Remove 2 screws of service panel and service panel.
(See Photo 3)
(3) Remove the thermistor (TH2) from the holder.
(See Photo 4)
(4) Remove the connector (CN21) from the indoor controller board and pull the white wire of thermistor
(TH2) out.
Service panel
(Condenser / evaporator temperature thermistor)
Set screws
(for drain pan)
Front panel
Photo 2
Terminal block (TB15)
Terminal block (TB4)
Indoor controller box
Fan motor capacitor
3. Removing the condenser / evaporator temperature thermistor (TH5)
(1) Remove the electrical parts cover. (Refer to 1)
(2) Remove the service panel. (See Photo 3)
(3) Remove the thermistor (TH5) from the holder.
(See Photo 4)
(4) Remove the connector (CN29) from the indoor controller board and pull the black wire of thermistor
(TH5) out.
Indoor controller board Indoor power board
Photo 3
Screws
Photo 4
Pipe temperature thermistor / liquid
(TH2)
Service panel
22
Screws Condenser / evaporator temperature thermistor (TH5)
OC321A.qxp 06.8.28 3:45 PM Page 23
OPERATING PROCEDURE
4. Removing the room temperature thermistor (TH1)
(1) Remove the electrical parts cover. (Refer to 1)
(2) Remove 12 screws of front panel and the front panel at fan side.
(See Photo 1)
(3) Remove the thermistor (TH1) from the separator panel.
(See Photo 6)
(4) Disconnect the connector (CN20)from the indoor controller board and pull the lead wire of thermistor (TH1) out.
Photo 5
Claws
PHOTOS
Motor bands
Photo 6
Claws
Screws
Fan casing
Fan casing
Fan motor
Separator panel
Fan motor
5. Removing the sirocco fan and the fan motor (MF).
(1) Remove the electrical parts cover. (Refer to 1)
(2) Remove 12 screws of front panel and the front panel at fan side. (See Photo 1)
(3) Disconnect the connector of the fan motor lead wire.
(See Photo 2)
(4) Undo the 4 claws and remove the fan claws.(down side)
<Either left or right> (See Photo 5)
(5) Remove the motor bands.
<A screw each on left and right.> (See Photo 5)
(6) Disconnect the earth wire from the fan motor leg.
(See Photo 7)
(7) Remove the fan motor and the sirocco fan by assembly.
(See Photo 7)
(8) Unscrew set screw and remove the sirocco fan.
<Either left or right> (See Photo 7)
Photo 7
Room temperature thermistor (TH1)
Set screw
Earth wire
23
OC321A.qxp 06.8.28 3:45 PM Page 24
OPERATING PROCEDURE
6. Removing the drain pan
(1) Unscrew each set screw on the right and left, and remove the drain pan pushing it toward the the back.
(See Photo 1)
Photo 8
PHOTOS
Screws
7. Removing the heat exchanger
(1) Remove the drain pan. (Refer to 6)
(2) Remove the 16 screws and the Under flange at heat exchanger side. (See Photo 8)
(3) Remove the 4 screws of heat exchanger.( 2 screws each on left and right) (See Photo 9)
(4) Remove the thermistor (TH2) from the holder.
(Refer to 2)
(5) Remove the thermistor (TH5) from the holder.
(Refer to 3)
(6) Remove the 3 screws and the service panel.
(See Photo 9)
(7) Put the heat exchanger down to the fan motor and pull it toward you.
(See Photo 9)
Under flange
Photo 9
Screws for heat exchanger
Service panel
Screws for service panel
24
Heat exchanger
OC321A.qxp 06.8.28 3:45 PM Page 25
8 PARTS LIST (non-RoHS compliant)
INDOOR UNIT
STRUCTURAL PARTS
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
1
15 14 13 12
2
3
11
10
9
8
7
4 5 6
No.
Parts No.
Parts name Specification
1 E07 039 086 LEFT SIDE PANEL
2 E07 039 500 SIROCCO FAN
3 E02 179 505 FAN MOTOR RUBBER MOUNT
E07 039 300 FAN MOTOR PK6V19-EF
4
E07 040 300 FAN MOTOR
E07 041 300 FAN MOTOR
PK6V32-EF
PK6V50-EF
E07 223 300 FAN MOTOR
5 E07 159 308 ROOM TEMPERATURE THERMISTOR
PK4V60-EA
6 E07 039 000 FRONT PANEL
7
8
9
E07 039 700 DRAIN PAN
E07 154 309
CONDENSER / EVAPORATOR
TEMPERATURE THERMISTOR
E07 159 307 PIPE TEMPERATURE THERMISTOR / LIQUID
E07 143 620 INDOOR HEAT EXCHANGER
10
E07 144 620
E07 145 620
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
E07 223 620 INDOOR HEAT EXCHANGER
11 E07 039 808 RIGHT LEG
12 E07 143 085 RIGHT SIDE PANEL
13 E07 143 293 SEPARATOR ASSY
14 E07 039 809 LEFT LEG
15 E07 039 290 BASE
1
2
1
2
1
1
1
1
1
1
1
2
2
1
Q'ty/set
35
SEZ-KA · VA.TH
50 60 71
1 1 1 1
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2
1
2
1
1
2
1
1
2
1
1
2
1
Remarks
(Drawing No.)
<2PCS/SET>
Wiring
Diagram
Recommended
Symbol Q'ty
Price
Unit Amount
MF
MF
MF
MF
TH1
TH5
TH2
25
OC321A.qxp 06.8.28 3:45 PM Page 26
INDOOR UNIT
ELECTRICAL PARTS
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
6
7
5
4
TEMP.
ON/OFF
8
9
3
1
2
Part numbers that is circled is not shown in the figure.
No.
Parts No.
Parts name Specification
1
E07 159 447 INDOOR CONTROLLER BOARD
E07 160 447 INDOOR CONTROLLER BOARD
E07 161 447 INDOOR CONTROLLER BOARD
E07 223 447 INDOOR CONTROLLER BOARD
2
3
E02 661 385 VARISTOR
E07 006 382 FUSE
4 E07 154 440 INDOOR POWER BOARD
250V/6.3A
5
E02 063 351 FAN MOTOR CAPACITOR 2.5
+ /440VAC
E02 138 351 FAN MOTOR CAPACITOR 3.0
+ /440VAC
6
7
E02 064 351 FAN MOTOR CAPACITOR 4.0
+ /440VAC
E07 156 375 TERMINAL BLOCK 2P
E07 162 375 TERMINAL BLOCK 3P
8
9
E07 159 426 REMOTE CONTROLLER
E07 018 089 REMOTE CONTROLLER CABLE
10 E07 039 449 CONTROLLER COVER
1
1
1
1
1
1
1
1
1
35
1
Q'ty/set
SEZ-KA ·VA.TH
50 60 71
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring Recom-
Diagram mended
Symbol Q'ty
Price
Unit Amount
P.B
C1
C1
C1
TB15
TB4
R.B
I.B
I.B
I.B
I.B
ZNR
FUSE
26
OC321A.qxp 06.8.28 3:45 PM Page 27
9 RoHS PARTS LIST
INDOOR UNIT
STRUCTURAL PARTS
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
1
15 14 13 12
11
2
3
10
9
8
7
4 5 6
No.
Parts No.
Parts name Specification
1
2
3
4
5
6
7
8
9
G E17 039 086 LEFT SIDE PANEL
G E17 039 500 SIROCCO FAN
G E12 179 505 FAN MOTOR RUBBER MOUNT
G E17 039 300 FAN MOTOR PK6V19-EF
G E17 040 300 FAN MOTOR PK6V32-EF
G E17 041 300 FAN MOTOR PK6V50-EF
G E17 223 300 FAN MOTOR PK4V60-EA
G E17 159 308 ROOM TEMPERATURE THERMISTOR
G E17 039 000 FRONT PANEL
G
G
G
E17 039 700 DRAIN PAN
E17 154 309
CONDENSER / EVAPORATOR
TEMPERATURE THERMISTOR
E17 159 307 PIPE TEMPERATURE THERMISTOR / LIQUID
G E17 143 620 INDOOR HEAT EXCHANGER
10
G
G
E17 144 620 INDOOR HEAT EXCHANGER
E17 145 620 INDOOR HEAT EXCHANGER
G E17 223 620 INDOOR HEAT EXCHANGER
11 G E17 039 808 RIGHT LEG
12 G E17 143 085 RIGHT SIDE PANEL
13 G E17 143 293 SEPARATOR ASSY
14 G E17 039 809 LEFT LEG
15 G E17 039 290 BASE
1
2
1
2
1
1
1
1
1
1
1
2
2
1
Q'ty/set
35
SEZ-KA · VA.TH
50 60 71
1 1 1 1
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2
1
2
1
1
2
1
1
2
1
1
2
1
Remarks
(Drawing No.)
<2PCS/SET>
Wiring Recom-
Diagram mended
Symbol Q'ty
Price
Unit Amount
MF
MF
MF
MF
TH1
TH5
TH2
27
OC321A.qxp 06.8.28 3:45 PM Page 28
INDOOR UNIT
ELECTRICAL PARTS
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
6
7
5
4
TEMP.
ON/OFF
8
9
3
1
2
Part numbers that is circled is not shown in the figure.
No.
Parts No.
Parts name Specification
G E17 159 447 INDOOR CONTROLLER BOARD
G E17 160 447 INDOOR CONTROLLER BOARD
1
G E17 161 447 INDOOR CONTROLLER BOARD
G E17 223 447 INDOOR CONTROLLER BOARD
2
3
4
5
G E12 661 385 VARISTOR
G E17 006 382 FUSE 250V/6.3A
G E17 154 440 INDOOR POWER BOARD
G E12 063 351 FAN MOTOR CAPACITOR 2.5
+ /440VAC
G E12 138 351 FAN MOTOR CAPACITOR 3.0
+ /440VAC
6
G E12 064 351 FAN MOTOR CAPACITOR 4.0
+ /440VAC
G E17 156 375 TERMINAL BLOCK 2P
7 G E17 162 375 TERMINAL BLOCK
8 G E17 159 426 REMOTE CONTROLLER
9 G E17 018 089 REMOTE CONTROLLER CABLE
10 G E17 039 449 CONTROLLER COVER
3P
1
1
1
1
1
1
1
1
1
Q'ty/set
SEZ-KA ·VA.TH
35 50 60 71
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring Recom-
Diagram mended
Symbol Q'ty
Price
Unit Amount
I.B
I.B
I.B
I.B
ZNR
FUSE
P.B
C1
C1
C1
TB15
TB4
R.B
28
OC321A.qxp 06.8.28 3:45 PM Page 29
10 OPTIONAL PARTS
AIR FILTER
Applied unit
SEZ-KA35VA.TH
SEZ-KA50VA.TH
SEZ-KA60VA.TH
SEZ-KA71VA.TH
Models
PAC - 1000 FT
29
OC321A.qxp 06.8.28 3:45 PM Page 30
30
OC321A.qxp 06.8.28 3:45 PM Page 31
31
OC321A.qxp 06.8.28 3:45 PM Page 32
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Sep. 2006 No.OC321 REVISED EDITION-B PDF 7
Distributed in Oct. 2005 No.OC321 REVISED EDITION-A PDF 8
Distributed in Feb. 2005 No.OC321 PDF 8
Made in Japan
New publication, effective Sep. 2006
Specifications subject to change without notice.