Mitsubishi FX2N Programmable Logic Controller PLC Connection Guide
Below you will find brief information for FX2N. This guide provides essential HMI settings and device addressing details for connecting to the Mitsubishi FX2N series PLC. It outlines recommended parameters such as RS485 4W interface, 19200 baud rate, data bits, parity, and stop bits. The document also includes notes on pass-through mode communication and special settings to enhance download/upload speeds, making it a comprehensive resource for establishing reliable HMI-PLC connections.
Advertisement
Advertisement
Advertisement
Key features
Supports Mitsubishi FX2N series PLCs
Recommended RS485 4W interface (options for RS232/RS485)
Multiple baud rate options: 9600 to 115200
Pass-through mode for HMI-PLC communication
Enhanced download/upload speed in pass-through mode (LW-9903 setting)
Detailed device address ranges for input/output relays, timers, counters, and data registers
Frequently asked questions
This guide supports the Mitsubishi FX2N series PLC.
Recommended settings include PLC type Mitsubishi FX2N, PLC I/F RS485 4W, Baud rate 19200, Data bits 7, Parity Even, Stop bits 1, and PLC station number 0.
To enhance the speed of download/upload PLC program in pass-through mode, you should set LW-9903 to 2.