- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- GE Security
- FireShield FS1004
- User manual
GE Security FireShield FS1004 Technical Reference Manual
Add to My manuals68 Pages
GE Security FireShield FS1004 is a fire alarm control panel that provides reliable protection for a variety of applications. With its 10 initiating device circuits (IDCs) and 4 notification appliance circuits (NACs), the FS1004 can monitor and control a wide range of fire alarm devices. The panel's advanced features, such as its built-in DACT (Dialer)/Modem (FSDACT), make it easy to transmit event messages to a monitoring station. Additionally, the FS1004's optional components, such as the Remote System Indicator (FSRSI) and Remote Zone Indicator (FSRZI-A), provide added flexibility and convenience.
advertisement
FireShield
Technical Reference Manual
P/N 3100353 • Rev 3.0 • 12MAY03
DEVELOPED BY
Phone: (941) 739-4200
Copyright © 2002
–2003
IMPORTANT INFORMATION
Limitation of liability
This product has been designed to meet the requirements of the standards listed in “Compliance statement” below.
Installation in accordance with this manual, applicable codes, and the instructions of the Authority Having
Jurisdiction is mandatory. The manufacturer shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of products beyond the cost of repair or replacement of any defective products.
The manufacturer reserves the right to make product improvements and change product specifications at any time.
While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, the manufacturer assumes no responsibility for errors or omissions.
FCC warning
This equipment can generate and radiate radio frequency energy. If this equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply within the limits for Class A digital devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment. Operation of this equipment is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference.
Compliance statement
FireShield, when properly installed, operates as a Local
Protected Premises Fire Alarm System in accordance with the following standards:
• NFPA Standard 72, 1999 Edition
• NFPA 70 National Electrical Code
• Underwriters Laboratories Standard 864, 8th Edition
• Underwriters Laboratories of Canada Standard ULC
S527-99
• Canadian Electrical Code Part I
• Standard for Installation of Fire Alarm Systems
ULC S524
• Standard for the Inspection and Testing of Fire Alarm
Systems ULC S536
FireShield also complies with Local Protective Signaling
(type L) - manual (M), automatic (A), waterflow (WF), and sprinkler supervisory (SS) for:
• Coded (C) and non-coded signaling (NC)
• Remote Station (type RS) - with RPM or FSDACT
• Auxiliary (type A) - with CTM4.7 (this may include Local with Shunt type connection to Master Box - type LS)
• Central Station (Type CS) - with FSDACT
Content
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Appendix A
Appendix B
Appendix C
Appendix D
Appendix E
System overview and operation • 1.1
System overview • 1.1
Operations overview • 1.1
Controls and indicators • 1.1
Component descriptions • 1.3
Operating the panel • 1.4
FSDACT LCD messages • 1.7
Installation • 2.1
Installation checklist • 2.1
Installing the cabinet • 2.1
Installing the Remote System Indicator • 2.2
Installing the Remote Zone Indicator • 2.3
Installing the Remote Relay Module • 2.5
Installing the Power Expander Transformer • 2.7
Installing the FSDACT • 2.8
Connecting an RPM module • 2.10
Connecting a CTM module • 2.11
Connecting an auxiliary power supply • 2.12
Installing the terminal shield • 2.12
Programming • 3.1
Overview • 3.1
Using the factory default settings • 3.2
Using an FSDACT • 3.2
Custom programming the panel • 3.2
FSDACT programming • 3.8
Maintenance • 4.1
Preventive maintenance • 4.1
Calculations • A.1
Battery calculation worksheet • A.1
Notification appliance voltage drop calculation • A.3
Notification appliance circuit maximum wire length calculation • A.4
Programming templates • B.1
Panel programming worksheet • B.1
FSDACT programming worksheet • B.2
Jumper settings and wiring diagrams • C.1
Panel specifications • D.1
Default event codes • E.1
Default Contact ID event codes • E.1
Default (4/2) event codes • E.2
FireShield Fire Alarm Control Panel Operating
Instructions • 1
Chapter 1
System overview and operation
If the optional FSDACT is installed, the panel:
• Sends a record of the event to the FSDACT LCD and to the history log
• Uses the FSDACT to transmit event messages to a monitoring station as programmed
System overview
FireShield is available in three models: three-zone, five-zone, and ten-zone. Each model is similar except for the number of initiating device circuits (IDCs) and notification appliance circuits (NACs), as shown in the following table.
Model IDCs NACs
FS302 (three-zone)
FS502 (five-zone)
FS1004 (ten-zone)
3
5
10
2
2
4
Model numbers may have the following suffixes: G or R indicates gray or red enclosure, GD or RD indicates panel with
FSDACT, GC indicates ULC panel with terminal shield, GF indicates a French ULC panel with terminal shield, and G-2 indicates 230 Vac input.
Each panel is configured for Class B operation. All models except for the three-zone can be easily converted to Class A by using two Class B circuits to make one Class A circuit.
FireShield has the following optional components:
• Remote System Indicator (FSRSI)
• Remote Zone Indicator (FSRZI-A)
• Remote Relay Module (FSRRM)
• Power Expander Transformer (XTR3A120, XTR3A230)
(ten-zone only)
• DACT (Dialer)/Modem (FSDACT)
• City Tie Module (CTM4.7)
• Reverse Polarity Module (RPM)
• Battery Cabinet (BC-2)
Refer to Chapter 2 “Installation” for optional module details.
Controls and indicators
1
2
3
4
REMOTE
DISCON-
NECT
WALK
TEST
RESET
SIGNAL
SILENCE
& DRILL
PANEL
SILENCE
ALARM TROUBLE SUP
ANNUN
TROUBLE
BATT
TROUBLE
GND
FAULT
POWER DISABLE
WALK
TEST
SIGNAL
SILENCED
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
2
3
1
ALARM TROUBLE SUP/MON
NAC 1
NAC 2
6
5
Front panel display
(1) Lamp test
Buttons
REMOTE
DISCON-
NECT
WALK
TEST
Description
Press the Remote Disconnect and Walk Test buttons simultaneously to initiate a panel lamp test. This lets you verify proper operation of the LEDs on the panel and the remote annunciators.
Operations overview
The panel operates in normal mode in the absence of any alarm, supervisory, trouble, or monitor events. In normal mode, the control panel monitors the system.
The panel operates in off-normal mode any time an event is introduced into the system. When this happens, the panel:
• Changes contact positions on appropriate common relays
• Activates alarm outputs (for alarm events only)
• Turns on the appropriate LEDs and the panel buzzer
• Executes the appropriate programmed output response for the input that signaled the event
• Communicates event information to appropriate optional components (FSRSI, FSRZI-A, CTM4.7, or RPM)
(2) Control buttons
Button
REMOTE
DISCON-
NECT
WALK
TEST
Description
Operating mode with FSDACT: Disables or enables FSDACT. Has no effect on alarm relay.
Operating mode without FSDACT: Disables or enables the common alarm relay.
Programming mode: Selects the next option.
Operating mode: Places the panel in walk test mode. The Walk Test LED is on when the panel is in walk test mode.
Programming mode: Selects the previous option.
FireShield Technical Reference Manual 1.1
System overview and operation
RESET
SIGNAL
SILENCE
& DRILL
PANEL
SILENCE
Operating mode: Initiates a panel reset.
Programming mode: Selects the next setting for the current option.
Alarm mode: Silences active notification appliances. Pressing Signal Silence a second time turns NACs back on. The Signal
Silenced LED indicates when the panel is in alarm and operating with notification appliances turned off. Visual appliances may or may not turn off when Signal Silence is pressed depending on panel programming.
Normal mode: Activates the drill function.
Turns notification appliances on according to the panel programming but does not place the panel in alarm or activate the alarm relay. Pressing Drill a second time turns off the drill function.
Programming mode: Selects the previous setting of the current program option.
Operating mode: Silences the panel and
FSRSI sounders during an active trouble, supervisory, or alarm event.
Programming mode: Saves the program setting.
(3) Indicating Device Circuits (IDCs) LEDs and controls
LED/button Description
Alarm LED
Trouble LED
Supervisory /
Monitor LED
(SUP/MON)
DISABLE
On steady when an alarm input device is activated.
On steady when there is a wiring fault on the circuit. Double-flashes when the circuit is disabled. Fast-flashes, during walk test, when the IDC is resetting.
On steady when a supervisory input device is activated. Stays on until panel is reset.
Also flashes when active if programmed as a monitor zone. Monitor zone programming option is not approved for use in Canada.
Operating mode: Renders an IDC inoperative. A disabled circuit can not initiate a change in panel state. A disabled IDC’s
Trouble LED double-flashes. If pressed when an IDC is active, it has no effect on the panel’s current state but no further activity on that IDC will be reported. Disabled IDCs remain disabled after a system reset.
Walk test mode: Selects an IDC to place it into or remove it from walk test mode.
Programming mode: Selects an IDC so that settings can be viewed or changed.
(4) Notification Appliance Circuits (NACs) LEDs and controls
LED/button Description
Trouble LED On steady when there's a wiring fault on circuit. Double-flashes when circuit is disabled.
DISABLE
Operating mode: Used to render an NAC inoperative. A disabled NAC trouble LED double-flashes. If pressed when an NAC is active, notification appliances remain active.
Once silenced, a disabled NAC does not resound unless enabled. Disabled NACs remain disabled after a system reset.
Programming mode: Selects an NAC so that settings can be viewed or changed.
(5) Common system LEDs
LED Description
Alarm
Trouble
Supervisory
Power
Disable
On steady when there is an active alarm event on any IDC.
Flashes when there's a fault with a monitored circuit or system component, when a circuit is disabled, or when panel is in walk test mode.
On steady when there is an active supervisory event on any IDC.
On when the panel has AC power.
Double-flashes when there is a disabled circuit, FSRRM, alarm relay, or FSDACT.
Pressing Disable also places the panel in the trouble state.
Annunciator
Trouble
Battery
Trouble
On steady when there is a communication failure between the panel and a remote annunciator. Also places the panel in the trouble state.
Flashes for voltage supervisory or charger trouble. Steady means placement trouble.
Also places the panel in the trouble state.
Ground Fault On steady during an active ground fault. Also places the panel in the trouble state.
Walk Test
Signal
Silenced
Flashes when performing an audible walk test. Steady indicates a silent walk test. Also places the panel in the trouble state.
On steady indicates that NAC circuits are turned off but the panel is still in alarm.
(6) LCD display when FSDACT is installed
Notes on LEDs:
During an alarm condition, all flashing
LEDs, regardless of their function, go steady.
When NAC or IDC pairs are configured for Class A operation, trouble conditions may be indicated by the Trouble LED on either NAC or IDC in the pair.
1.2
FireShield Technical Reference Manual
Component descriptions
1 2 3 4
System overview and operation
5 6 7 8
9
10
PRG
13
11 12
(1) Main AC wiring block and fuse holder:
Provides connections for 120 or 230 volt AC (primary power) from dedicated service. Includes a primary power fuse (5 A).
(2) Dual Transformer AC wiring block:
Ten-zone panel only.
Provides connections between primary side of both main and expander transformer and 120 or 230 volt AC (fused primary power).
(3) Transformer:
Changes 120 or 230 volt AC supply voltage to 24 volt AC.
(4) Power expander transformer (XTR3A120, XTR3A230):
Optional. Available for the ten-zone panel only. Provides additional primary power to increase the available NAC current for the ten-zone panel.
(5) Main circuit board:
Provides connections for all circuits.
Also includes the operator interface.
(6) FSDACT plug:
Used to connect the FSDACT to the circuit board.
(7) Operator Interface:
Includes operator controls, LED indicators, and circuit identification labels.
(8) Cabinet enclosure:
Houses the panel electronics and standby batteries. In some cases the batteries may be housed in an external battery cabinet (BC-2).
(9) FSDACT:
Optional. Digital alarm communicator transmitter. Provides LCD display for status messages and programming menus. Provides two telephone line connections for sending system messages to a compatible digital alarm communicator receiver (DACR). Includes an event history log of panel and FSDACT events.
(10) Program jumper PRG:
Used to place the panel in programming mode.
(11) Tie wrap mounts:
Nonpower-limited. Used to secure wires and to help maintain proper separation between powerlimited and nonpower-limited conductors.
(12) Tie wrap mounts:
Power-limited. Used to secure wires and to help maintain proper separation between power-limited and nonpower-limited conductors.
(13) Standby batteries:
Provide secondary/standby power to the panel electronics in the absence of primary power.
FireShield Technical Reference Manual 1.3
System overview and operation
Operating the panel
Resetting the panel
Pressing Reset places the panel in the reset state. The panel should not be reset until the appropriate authority has determined that the hazard is no longer present.
When you reset the panel:
• All LEDs on the panel light for five seconds
• The trouble and power lights remain on for an additional
15 seconds
• When reset is complete, the buzzer sounds (then turns off) and the trouble LED turns off
In this state:
• All panel indicators are temporarily cleared
• All notification appliances are turned off
• All latched IDCs are cleared
• Alarm, trouble, and supervisory relays are returned to the inactive state
• Auxiliary power (if programmed as resettable) momentarily turns off
At the conclusion of the reset, if an IDC is in an off-normal state, the panel treats the event as a new event and activates the programmed responses. Pressing Disable for the active
IDC within 30 seconds after the panel has reset turns off the
NACs and disables the IDC.
If one or more IDCs are disabled prior to initiation of the reset, those IDCs remain disabled.
If signal silence inhibit or reset inhibit is enabled, system reset is inhibited during the silence or reset inhibit period.
To reset the panel:
1. Press the Reset button.
Silencing panel and FSRSI buzzers
Both the panel and the optional FSRSI module have buzzer silence buttons. Pressing the Panel Silence button silences the buzzer on the panel and on remote FSRSIs.
Pressing the FSRSI Silence button silences the buzzer on the
FSRSI only.
To silence the panel buzzer:
1. Press the Panel Silence button on the panel.
2. Determine the type of condition that caused the buzzer to sound: alarm, trouble, supervisory, or monitor.
3. Determine the cause of the condition.
To silence an FSRSI buzzer:
1. Press the Silence button on the FSRSI.
2. Determine the type of condition that caused the buzzer to sound: alarm, trouble, supervisory, or monitor.
3. Determine the cause of the condition.
Silencing notification appliances
Pressing the Signal Silence & Drill button turns off all audible devices. Visual devices or NAC circuits may or may not turn off, depending on panel programming.
When you silence the signals, the Signal Silenced LED lights, indicating that the notification appliances are off. The panel does not indicate a trouble condition. If GENESIS, horn/strobe, or horn-only devices are used on NACs programmed for GENESIS operation, Signal Silence & Drill silences only the horns.
WARNING:
The notification appliances should not be silenced until the building is fully evacuated and the cause of the alarm has been determined.
To silence notification appliances:
1. Press the Signal Silence & Drill button.
When the auto signal silence timer is programmed
When an event activates the notification appliances, the 20minute auto signal silence timer is activated. The notification appliances are activated for the 20-minute period. When the timer expires, any NACs that are programmed as silenceable are deactivated, and the Signal Silenced LED is illuminated.
If another event takes place that activates the previously silenced notification appliances, the Signal Silenced LED turns off. At any time, you can deactivate silenceable NACs by pressing Signal Silence & Drill.
Note:
NACs activated by IDCs programmed as waterflow cannot be silenced until the activated devices are restored to normal. After the devices restore, the Signal Silence & Drill button or the auto signal silence timer can silence the NACs.
Resounding an alarm condition
Pressing the Signal Silence & Drill button again turns the audible devices back on if they were silenced.
To resound notification appliances:
1. Press the Signal Silence & Drill button.
Note:
NACs resound automatically if a new alarm (from another IDC) is received.
1.4
FireShield Technical Reference Manual
System overview and operation
Disabling an IDC
Pressing an IDC Disable button prevents the panel from responding to any status change from that IDC. When you disable an IDC:
• The common Disable LED double-flashes
• The IDC Trouble LED double-flashes
• The common Trouble LED lights and the panel goes into a trouble state
• The common trouble relay changes state
Resetting the panel has no effect on a disabled IDC, but removing all power from the panel clears the disable and enables the IDC.
Note:
During an alarm condition, all flashing LEDs go steady.
To disable an IDC:
1. Press the Disable button for the IDC that you want to disable.
Disabling a NAC
When you disable an NAC:
• The common Disable LED double-flashes
• The NAC Trouble LED double-flashes
• The common Trouble LED lights and the panel goes into a trouble state
• The common trouble relay changes state
Resetting the panel has no effect on a disabled NAC, but removing all power from the panel clears the disable and enables the NAC.
To disable a NAC:
1. Press the Disable button for the NAC that you want to disable.
Re-enabling an IDC or NAC
You can re-enable a disabled IDC or NAC. When you reenable an IDC or NAC:
• The common Disable LED turns off
• The IDC or NAC trouble LED turns off
• The common Trouble LED turns off and the panel returns to normal
• The IDC or NAC LEDs are updated to show current status (e.g. if the IDC or NAC is in trouble, the Trouble
LED lights). After enabling an IDC, alarms from that IDC are inhibited for 30 seconds. During this time the IDC can be disabled to avoid an unwanted alarm.
To re-enable an IDC or NAC:
1. Press the Disable button for the IDC or NAC you want to re-enable.
Using the drill command
You can use the drill command to activate all of the notification appliance circuits. Pressing Drill activates all audibles and visuals according to the panel programming, but does not activate the Alarm relay. The FSDACT can be programmed to transmit a drill condition, but it will never report the drill as an alarm. Drill will not operate with an active alarm or supervisory event at the panel.
To perform a fire drill:
1. Press and hold the Signal Silence & Drill button for one second.
2. To stop the drill, press and hold the Signal Silence & Drill button for one second.
Using the walk test command
A walk test lets you test IDC zones without having to create an actual alarm condition. You can conduct a walk test in silent or audible mode. In silent mode the audible devices
(NACs) do not sound. Walk test will not operate with an active alarm or supervisory event at the panel.
Zones should be placed in walk test one at a time. This allows the balance of the system to remain in service.
In a walk test, the panel responds to the first signal it receives and ignores all others on that IDC until it clears that signal or the panel is reset. The input must be restored to the normal state before the next input is tested. When the input is restored, the panel automatically resets the circuit being tested. The automatic reset takes eight seconds. After the circuit is reset the next device can be tested.
The panel terminates the walk test if any of the following occur:
• The panel enters an alarm or supervisory state
• There are 30 minutes of inactivity on the zone being tested
• The panel is reset
• Walk Test is pressed
When you press Walk Test:
• The Walk Test LED flashes for an audible walk test and is steady for a silent walk test
• The panel enters a trouble state. There is no fire protection for the IDC in walk test. If an unselected IDC goes into alarm or trouble, all programmed outputs operate as programmed.
FireShield Technical Reference Manual 1.5
System overview and operation
The IDC you are testing behaves as follows:
• For alarm events, the appropriate panel, FSRSI, and
FSRZI-A LEDs and buzzers are turned on
• In the audible test mode the notification appliances sound for a number of times equal to the zone number (e.g. three rings for zone three)
• After activation, the panel resets the IDC. This will take eight seconds. During the reset period, the IDC trouble
LED fast-flashes. If the device being tested is not restored, the IDC does not reset. If the device is restored
(no alarm is present) the panel is ready to test another device or detector.
• If auxiliary power is programmed as resettable, the auxiliary power is deactivated while the zone is reset
• Input zones programmed as waterflow with retard require
10 to 15 seconds of activation to initiate the test signals
• For trouble events, the appropriate LEDs and the buzzers are turned on. In the audible (NAC) test mode a onesecond pulse sounds on the audible devices. After sounding, the zone resets in preparation for continued testing.
• For ground fault events, the appropriate LEDs and the buzzers are turned on. In the audible (NAC) test mode a one-second pulse sounds on the audible devices. After sounding, the zone resets in preparation for continued testing.
To conduct an audible walk test:
1. Press the Walk Test button once.
2. Press the Disable button for the IDC you want to test.
3. Conduct your walk test for the IDC.
4. When you are finished testing an IDC, press the Disable button to turn off the walk test for that IDC.
5. Select another IDC to walk test (steps 2 through 4) or exit from the walk test by pressing the Walk Test button.
To conduct a silent walk test:
1. Press the Walk Test button two times.
2. Press the Disable button for the IDC you want to test.
3. Conduct your walk test for the IDC.
4. When you are finished testing an IDC, press the Disable button to turn off the walk test for that IDC.
5. Select another IDC to walk test (steps 2 through 4) or exit from the walk test by pressing the Walk Test button.
Conducting lamp tests
Panel lamp test
A panel lamp test lights all the LEDs on the panel, FSRSIs, and FSRZI-As so you can verify proper operation.
To test panel lamps:
1. Press and hold the Remote Disconnect and Walk Test buttons simultaneously.
2. Verify proper operation of all LEDs on the panel.
During lamp tests the LCD displays:
DB# xx P: x.yy.zz
D: x.yy.zz
Where: DB# is the database revision number
P: x.yy.zz is the main panel version
D: x.yy.zz is the FSDACT version
FSRSI and FSRZI-A lamp test
FSRSI and FSRZI-A modules can be installed individually or in groups to create a complete remote annunciator. You can perform a local lamp test on the FSRSI and FSRZI-A. An
FSRSI is required to initiate this function.
To do an FSRSI and FSRZI-A lamp test:
1. Press and hold the FSRSI Silence button for five seconds.
2. Verify proper operation of all LEDs on the FSRSI and
FSRZI-As.
1.6
FireShield Technical Reference Manual
FSDACT LCD messages
Message
Peripheral trouble
Battery Bad
Battery Missing
AC Failure
Charger Trouble
Ground Fault
Transformer 2 TR
AUX Power Troub
Internal Comm TR
RRM(s) disabled
Dialing...
DACT Configuration
TRBL
DACT Delivery TR
DACT Line 1 Trbl
DACT Line 2 Trbl
Description
The panel lost communications with the peripherals
The battery is bad and needs to be replaced
The battery is no longer connected
The panel lost AC power
The panel detected a battery charger trouble condition. The charger may not be able to charge the batteries.
The panel detected a ground fault
The panel detected a trouble condition in the Power Expander Transformer
The panel detected a trouble condition in the AUX power circuit.
Panel-to-FSDACT communication fault
One or more FSRRMs are disabled
The FSDACT is dialing a DACR
FSDACT is not programmed or has unverified changes
FSDACT failed to deliver a message to the receiver or CMS
A ground fault or line fault has been detected on Line 1 of the FSDACT
A ground fault or line fault has been detected on Line 2 of the FSDACT
System overview and operation
FireShield Technical Reference Manual 1.7
System overview and operation
1.8
FireShield Technical Reference Manual
Chapter 2
Installation
Installation checklist
Prepare the site: Make sure the installation location is free from construction dust and debris and extreme temperature ranges and humidity.
Unpack the equipment
Install the cabinet: See “Installing the cabinet” for cabinet dimensions.
Remove the clear protective plastic from the front panel display
Install optional components (FSRSI, FSDACT, etc.):
See module installation instructions in this chapter.
Set the panel jumpers: See Appendix C or the panel label.
Review wire routing: See Appendix C or the panel label.
Connect the field wiring: See Appendix C or the panel label. Meter for opens, grounds, and shorts before connecting.
Connect AC power and ground: See Appendix C or the panel label. Panel can not be started on batteries only.
WARNING: Make sure that the AC power circuit breaker is off before connecting wires to the terminal block.
Connect batteries: See Appendix C or the panel label.
Program the panel: Refer to Chapter 3.
Test for proper operation
Panel dimensions
Model D1 [1] D2 D3 D4 D5 [1]
Threeand fivezone
16.5 in
(41.9
cm)
3.75 in
(9.5 cm)
9.13 in
(23.2
cm)
10.5 in
(26.67
cm)
14.23 in
(36.14
cm)
Tenzone
23.65 in
(60 cm)
3.75 in
(9.5 cm)
7.75 in
(19.7
cm)
21.27 in
(54.0
cm)
16.25 in
(41.27
cm)
[1] Add 1-1/2 in (3.81 cm) to D1 and D5 dimensions for trim kit.
D1
D2 D3
Surface mounting holes
D5
D4
Installing the cabinet
Cabinets can be surfaced mounted or semi-flush mounted. See the “Panel dimensions” figure and table for framing and mounting dimensions.
To surface mount the cabinet:
1. Position the cabinet on the finished wall surface.
2. Fasten the cabinet to the wall surface where indicated.
To semi-flush mount the cabinet:
1. Frame the interior wall as required to support the full weight of the cabinet and standby batteries.
2. Install (optional) semi-flush trim to cabinet.
3. Fasten the cabinet to the framing studs where indicated.
FireShield Technical Reference Manual 2.1
Installation
Installing the Remote System Indicator
The Remote System Indicator (FSRSI) is a supervised remote annunciator that provides remote LED indication of power, alarm, supervisory, trouble, and ground fault conditions. A sounder gives audible indication during a trouble, alarm, or supervisory condition. The sounder can be silenced with the
FSRSI Silence switch.
Note:
You must run the Find Annunciators program option after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. For more information see Chapter 3 “Programming.”
Specifications
Max. per system: 2
Voltage range
Minimum: 21 Vdc
Maximum: 25 Vdc
Current requirements
Standby: 12 mA
Alarm: 48 mA
Max. circuit capacitance: 0.03
µ
F
Max. circuit resistance: 13 ohms
Wire size
Minimum: 18 AWG (0.75 sq mm)
Maximum: 12 AWG (2.5 sq mm)
Compatible electric box: ANSI/NEMA OS1-1996 1-3 gang electrical box
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
LEDs and buzzer
LED State
Power (green) On
Alarm (red) On
Description
AC power present
Active alarm state
LED State
Supervisory
(yellow)
On
Trouble (yellow) On
Ground fault
(yellow)
On
Buzzer On
On (temporal)
On (slow pulse)
On (intermittent)
Off
Description
Active supervisory device
System trouble
System ground fault
System trouble
Alarm condition
Supervisory condition
AC fail
Normal or silenced
Jumper setup
Jumper Name Description
J2 Group jumper
Allows two FSRSIs to be connected to the same panel.
Install the jumper on only one of the two FSRSIs.
Note: For jumper location, refer to the FSRSI wiring diagram.
Installation instructions
A single FSRSI can be mounted in a standard, single gang electrical box (ANSI/NEMA OS1-1996) using the single gang cover plate that is included. Up to three FSRZI-As with or without an FSRSI can be mounted in an approved multiple gang electrical box (ANSI/NEMA OS1-1996) with appropriate two, three, or four gang cover plates (model numbers FSAT-2, FSAT-3, or FSAT-4).
Caution:
Make sure all power is disconnected from the panel before installing. Observe static-sensitive handling practices.
To install the FSRSI:
1. Verify that all field wiring is free of opens, shorts, and ground faults.
2. Connect wires to the FSRSI as shown (see wiring diagram).
3. Using the two plain machine screws provided, mount the module to the electrical box.
Note:
If you are using a surface mounting box, you must install washers (provided) between the FSRSI and the surface mounting box.
4. Using the white machine screws provided with the faceplate, mount the faceplate to the module.
5. Connect the wires to the terminals in the control panel.
6. Program the FSRSI using the Find Annunciators program option. Refer to Chapter 3 “Programming.”
2.2
FireShield Technical Reference Manual
Compatible electrical box
Installation
Installing the Remote Zone Indicator
The Remote Zone Indicator (FSRZI-A) is a supervised remote annunciator that provides remote LED indication of IDCs in alarm state. The FSRZI-A indicates conditions for five IDCs.
The IDC groups are set by jumpers to indicate zones 1–5 or zones 6–10. Paper inserts are provided for labeling the LEDs.
Note:
You must run the Find Annunciators program option after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. For more information see Chapter 3 “Programming.”
Installing the FSRSI in an electrical box
Wiring diagram
From control panel or previous device
Communication in -
Communication in +
24 V in +
24 V in -
24V IN
- +
C IN
+ -
C OUT
+ -
Group
J2
24 V out +
24 V out -
Communication out -
Communication out +
To next device
Notes
1. All wiring is supervised and power limited.
2. 24 V out (aux power) must be programmed as nonresettable.
Specifications
Max. per system
FS302 (three-zone): 2
FS502 (five-zone): 2
FS1004 (ten-zone): 4
Voltage range
Minimum: 21 Vdc
Maximum: 25 Vdc
Current requirements
Standby: 8 mA
Alarm: 35 mA
Max. circuit capacitance: 0.03
µ
F
Max. circuit resistance: 13 ohms
Wire size
Minimum: 18 AWG (0.75 sq mm)
Maximum: 12 AWG (2.5 sq mm)
Compatible electric box: ANSI/NEMA OS1-1996 1-3 gang electrical box
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
FireShield Technical Reference Manual 2.3
Installation
Jumper setup
Jumper Name Description
J2
J3
Reserved for future use
Zone 6 -
10 jumper
N/A
Sets the five LEDs to report alarms in zones 6 - 10. [1]
J4
J5
Zone 1- 5 jumper
Group jumper
Sets the five LEDs to report alarms in zones 1 - 5. [1]
Allows two FSRZI-As to be connected to the same panel and set to the same zone output option.
Install the jumper on FSRZI-As in only one of the two groups.
[1] Install only one zone jumper on J3 or J4.
Note: For jumper location, refer to the FSRZI-A wiring diagram.
Installation instructions
A single FSRZI-A can be mounted in a standard, single gang electrical box (ANSI/NEMA OS1-1996) using the single gang cover plate that is included. Up to three FSRZI-As with or without an FSRSI can be mounted in an approved multiple gang electrical box (ANSI/NEMA OS1-1996) with appropriate two, three, or four gang cover plates (model numbers FSAT-2, FSAT-3, or FSAT-4).
Caution:
Make sure all power is disconnected from the panel before installing. Observe static-sensitive handling practices.
Wiring diagram
Compatible electrical box
Installing the FSRZI-A in an electrical box
Communication in -
Communication in +
24 V in +
24 V in -
From control panel or previous device
J5
J4
J3
J2
24V IN
- +
C IN
+ -
To install the FSRZI-A:
1. Verify that all field wiring is free of opens, shorts, and ground faults.
2. Connect wires to the FSRZI-A as shown (see wiring diagram).
3. Using the two plain machine screws provided, mount the module to the electrical box.
Note:
If you are surface mounting the FSRZI-A, you must install washers (provided) between the FSRZI-A and the surface mount box.
4. Using the two white machine screws provided with the faceplate, mount the faceplate to the module.
5. Connect the wires to the terminals in the control panel.
6. Program the FSRZI-A using the Find Annunciators program option. Refer to Chapter 3 “Programming.”
24 V out +
24 V out -
Communication out -
Communication out +
To next device
Notes
1. All wiring is supervised and power limited.
2. 24 V out (aux power) must be programmed as nonresettable.
2.4
FireShield Technical Reference Manual
Installation
Installing the Remote Relay Module
The Remote Relay Module (FSRRM) provides five dry contact relay outputs. The outputs can be wired as both normally open and normally closed. The outputs can be set to common or zone notifications (see the “Command options” table below). Installing the appropriate jumper (JP3 - JP5) configures the dry contact relay output options.
Five diagnostic LEDs provide visual indication of the status of each relay. If the LED is lit, the relay is energized. If the LED is off, the relay is de-energized. If configured for common operation the trouble relay and the power relay will be energized when the system is normal.
Note:
You must run the Find Annunciators program option after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. For more information see Chapter 3 “Programming.”
Common operation current requirements
Standby: 30 mA
Alarm: 41 mA
Max. circuit capacitance: 0.03
µ
F
Max. circuit resistance: 13 ohms
Relay ratings: 30 Vdc @ 1 A (resistive load)
Wire size
Minimum: 18 AWG (0.75 sq mm)
Maximum: 12 AWG (2.5 sq mm)
Mounting: MFC-A cabinet or listed fire alarm enclosure
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
Jumper setup
DISABLE
JP1
OUTPUTS
JP1 IN
ACTIVE
DS4
OUT 1
DS5
OUT 2
MODULE TYPE
JP2
ZONE 11-15
JP3
ZONE 6-10
JP4
ZONE 1-5
JP5
COMMON
#1
JP6
#2
GROUP
JP6 IN
JP6 OUT
DS2
OUT 3
DS3
OUT 4
DS1
OUT 5
Specifications
Max. per system
FS302 (three-zone): 4
FS502 (five-zone): 4
FS1004 (ten-zone): 6
Voltage range
Minimum: 21 Vdc
Maximum: 25 Vdc
Zoned operation current requirements
Standby: 8 mA
Alarm: 65 mA
Command options
Jumper
JP1
JP2
JP3
JP4
JP5
Name Description
Disable jumper
Disables all outputs. This allows the installer to test the system while the
FSRRM is disabled. Removing the jumper reactivates the FSRRM.
The disable jumper is supervised.
With the disable jumper in place, the panel displays Trouble, Annunciator
Trouble, Disable, sounds the panel buzzer, and de-energizes any energized relay.
Reserved for future use.
Zone 6 -
10 jumper
Zone 1- 5 jumper
Common jumper
Sets the five dry contacts to report events on zones 6 through 10. See
“Command options” table. [1]
Sets the five dry contacts to report events on zones 1 through 5. See
“Command options” table. [1]
Sets the five dry contacts to report common events. See “Command options” table. [1]
JP6 Group jumper
The group jumper (JP6) allows two
FSRRMs to be connected to the same panel and set to the same output option. Install the jumper (JP6) to only one of the two grouped
FSRRMs.
[1] Install only one zone jumper on J3 or J4 or J5.
Module type Jumper Output 1 Output 2 Output 3 Output 4
Common
Zone 1 - 5
JP5
JP4
Alarm
Zone 1
Trouble [1]
Zone 2
Supervisory
Zone 3
Monitor
Zone 4
Zone 6 - 10 JP3 Zone 6 Zone 7 Zone 8 Zone 9
[1] Under normal conditions the relay is energized (the internal LED is lit). Loss of power de-energizes the relay.
Output 5
Power [1]
Zone 5
Zone 10
FireShield Technical Reference Manual 2.5
Installation
Installation instructions
The FSRRM snaps into a snap track (shipped with the
FSRRM), which mounts inside a listed fire alarm enclosure.
The FSRRM can be positioned in the snap track with the terminal block facing vertically or horizontally.
Caution:
Make sure all power is disconnected from the panel before installing. Observe static-sensitive handling practices.
To install the FSRRM:
1. Mount the MFC-A cabinet using the installation sheet provided (P/N 387453).
2. Drill mounting holes in the snap track using the template provided (P/N 3100463). These holes will align to the mounting holes on the MFC-A. An optional extended track (P/N FSRRM-S11) is available for mounting two to four FSRRM modules.
3. Mount the snap track to the MFC-A cabinet.
MFC-A
5. Verify that all wiring is free of opens, shorts, and ground faults.
6. Connect the FSRRM to the panel or other peripheral devices.
7. Power up the panel and confirm that all relays are in the correct state before connecting the field wiring.
8. Connect field wires to the FSRRM as shown in the wiring diagram. Be sure connection will not adversely affect controlled devices (e.g. elevators, fans, etc.).
9. Connect wiring to the controlled devices.
10. Program the FSRRM using the Find Annunciators program option. Refer to Chapter 3 “Programming.”
Wiring diagram
From control panel or previous device
Communication in +
Communication in -
[1] [1]
To next device
Communication out -
Communication out +
24 V in -
24 V in +
[1]
[2] [2]
Snap track
Snap track
MFC-A
Snap track
Snap track
24V IN
+ -
C IN
- +
C OUT
- +
[2]
OUT 3
NO C NC
[2]
OUT 1
NO C NC
[2]
24V OUT
+ -
X
OUT 5
NO C NC
OUT 4
NO C NC
OUT 2
NO C NC
[1]
24 V out -
24 V out +
To next device
4. Insert one side of the FSRRM into the first snap track slot and snap in the opposite side.
Mount in first slot only
Notes
[1] Supervised and power limited.
[2] Must be connected to a power limited source.
3. 24 V out (aux power) must be programmed as nonresettable.
Service and troubleshooting
If the Disabled and Annunc Trouble LED are lit but no IDC or
NAC is disabled then the FSRRM output is disabled.
RRM
Snap track
2.6
FireShield Technical Reference Manual
Installing the Power Expander
Transformer
The Power Expander Transformer (XTR3A120, XTR3A230) provides additional primary AC power to increase the NAC capacity for the ten-zone panel. It provides an additional 2.5
amps of NAC current. The Power Expander Transformer installs in the cabinet with four nuts (provided). The input side of the Power Expander Transformer connects to 120 Vac or
230 Vac through the Dual Transformer AC Wiring Block. Its output connects to the circuit board (J4) with the attached cable harness. One Power Expander Transformer can be installed in the 10-zone panel.
Note:
The Power Expander Transformer does not work with the three-zone or five-zone panels.
Installation
3. Connect the cable harness to J4 on the circuit board. Push the cable harness until the connector clicks into place.
4. Connect the incoming power wires to the dual transformer
AC wiring block above the existing transformer.
5. Secure the incoming power wires to the side of the control panel with the tie strap provided.
Main AC wiring block and fuse holder
From 120 Vac, 15 A, 60 Hz
Dedicated branch circuit
—OR—
From 230 Vac, 15 A, 50/60 Hz
Dedicated branch circuit
N L
Cabinet
Fuse
Dual transformer
AC wiring block
N2 L2
N L
Specifications
Power input
120 Vac @ 60 Hz (P/N XTR3A120)
230 Vac @ 50/60 Hz (P/N XTR3A230)
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
Fuse: Primary winding has thermal current protection and is not field serviceable
Note:
Input current rating is included with the overall ten-zone ratings.
Installation instructions
Caution:
Make sure all power is disconnected from the panel before installing. Observe static-sensitive handling practices.
To install the Power Expander Transformer:
1. Position the Power Expander Transformer so that the mounting holes align with the four mounting studs on the control panel cabinet.
2. Secure the transformer to the panel using the four nuts provided.
Tie wrap mounts
Main transformer
Main controller board
TB1
Mounting studs
XTR
(optional transformer)
J4
Plug connector
Power Expander Transformer installation and wiring
FireShield Technical Reference Manual 2.7
Installation
Installing the FSDACT
The FSDACT is a digital alarm communicator transmitter
(DACT) that transmits panel events to a compatible digital alarm communicator receiver (DACR). Messages are transmitted over standard loop-start telephone lines. The dialer is capable of split reporting to two different account and telephone numbers.
In addition to the DACT functions, this module includes:
• An alphanumeric LCD to display system
messages and programming prompts
• An event history log of panel and DACT events, viewable through compatible software
• A modem for uploading and downloading panel configuration, history, and current status to a PC running compatible software
Note:
The FSDACT modem is only rated for 2400 baud communication. Some PC modems may not be compatible with this baud rate.
The FSDACT can be programmed to operate as a single or dual line DACT/Modem/LCD display, a Modem/LCD display, or an LCD display only. For the FSDACT to be
NFPA 72 CS compliant, the following is required:
1. The factory installed warning label must be removed from the FSDACT's line two phone jack.
2. A second phone line, independent of that used for line one must be connected to phone jack two.
3. The FSDACT must be programmed for dual line operation.
4. The FSDACT must be programmed for a daily transmission test frequency.
UL 864 compliance requires the dual line setting.
The FSDACT can be configured for attended or unattended downloading. JP1 is a wire loop (located near the top of the
FSDACT) that controls which download method is used.
Leaving the JP1 wire loop intact configures the FSDACT for attended downloading. The panel will not allow changes to the panel or dialer configuration unless the program jumper is inserted. It will allow changes to receiver information (account code, telephone numbers, etc.). UL requires the red wire loop to be intact for all remote station systems.
Cutting the JP1 wire loop configures the FSDACT for unattended downloading. This means that the program jumper need not be inserted to accept any panel or dialer configuration changes.
NFPA 72 1999 edition states in 7-1.6.2.1 that reacceptance testing shall be performed after any change to site-specific software.
"All components, circuits, systems operations, or site-specific software functions known to be affected by the change or identified by a means that indicates the system operational changes shall be 100 percent tested. In addition, 10 percent of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, also shall be tested, and correct system operation shall be verified. A revised record of completion in accordance with 1-6.2.1 shall be prepared to reflect any changes.”
For additional download security, the FSDACT can be programmed to perform a call back function. This call back option applies whether the FSDACT is configured for attended or unattended downloading.
Specifications
Current requirements
Standby: 40 mA
Alarm: 60 mA
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
Phone line type: one or two loop-start lines on a public, switched network
Phone line connector: RJ31/38X (C31/38X). Two 7 ft plug cords are shipped with the FSDACT.
FCC registration number: US: EDWAL01BFSDACT
Ringer equivalence number: 0.1
Industry Canada Registration number: IC: 3944-FSDACT
Connection between panel and FSDACT: 6-pin connector
Communication formats: Contact ID (SIA DC-05) and
EST 4/2 (SIA DC-02 P3 with hexadecimal event codes)
Installation instructions
Note:
It is not necessary to remove the main panel board from the cabinet to install the dialer.
Caution:
Make sure all power is disconnected from the panel before removing or installing an FSDACT. Failure to disconnect power will damage the panel and the FSDACT.
Observe static-sensitive handling practices.
To install the FSDACT:
1. Remove the blank insert from the display window.
2. Remove the clear protective plastic film from the
FSDACT LCD display.
2.8
FireShield Technical Reference Manual
3. Use JP1 to configure the FSDACT for attended or unattended downloading:
• Attended: leave the JP1 wire intact
• Unattended: cut the JP1 wire
4. Install the dialer to the back of the circuit board. Align the
LCD display with the opening in the circuit board.
5. Secure the dialer to the circuit board with the two machine screws provided.
6. Connect the power cable to J2 on the control panel.
7. Connect RJ31X/C31X jacks to the supplied cables.
8. Connect the telephone circuits as required.
Phone cables
(supplied)
JP1 jumper wire
Line 1
Line 2
Circuit board
To wall phone jack
RJ31 jacks
FSDACT installation and telephone circuit connection
The FSDACT is listed for use with the following DACRs
Receiver
Ademco
FBII
Osborne-Hoffman
Models
685
CP220
OH 2000
Formats
EST 4/2*, Contact ID
EST 4/2*, Contact ID
EST 4/2*, Contact ID
Radionics
Silent Knight
D6500
9000
EST 4/2*
EST 4/2*
Sur-Gard MLR1, MLR2,
MCDI TLR, TLR+
EST 4/2*, Contact ID
* EST 4/2 is SIA DCS-02 P3 with the ability to transmit hexadecimal event codes.
Installation
FCC Information
1.
The dialer complies with Part 68 of the FCC rules. The dialer’s FCC certification number and Ringer Equivalence Number (REN) is displayed on the panel’s programming label and in this manual. This information must be provided to the telephone company if requested.
2.
Two FCC compliant telephone cords with 8-pin modular plugs at both ends are supplied with the FSDACT. The dialer is designed to be connected to the telephone network using the supplied cord and an
RJ31X or RJ38X jack, which must also comply with FCC Part 68 rules.
3.
The REN is used to determine the maximum number of devices that may be connected to a single telephone circuit. All telephone devices are assigned a REN. The sum of the RENs for all connected devices may not exceed five. The maximum REN may vary in some areas. Contact the local telephone provider for more information.
4.
If the dialer causes harm to the telephone network, the telephone company will notify you an advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC, if you believe it is necessary.
5.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the dialer. If this happens, the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
6.
If trouble is experienced with the dialer, for repair or warranty information, contact the manufacturer at: (941) 739-4200. If the dialer is causing harm to the telephone network, the telephone company may request you disconnect the dialer until the problem is resolved.
7.
No repairs may be performed on the dialer by the user.
8.
The dialer can not be used on public coin phones or party line service provided by the telephone company.
Industry Canada Information
NOTICE: This equipment meets the applicable Industry Canada Terminal
Equipment Technical Specifications. This is confirmed by the registration number. The abbreviation, IC, before the registration number signifies that registration was performed based on a Declaration of Conformity indicating that Industry Canada technical specifications were met. It does not imply that
Industry Canada approved the equipment.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection.
The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
NOTICE: The Ringer Equivalence Number (REN) for this terminal equipment is 0.1. The REN assigned to each terminal equipment provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed five.
FireShield Technical Reference Manual 2.9
Installation
Connecting an RPM module
The Reverse Polarity Module (RPM) is an interface between
FireShield and a reverse polarity receiver. It provides offpremises signal transmission for systems that must comply with NFPA requirements. When used as a reverse polarity remote station transmitter, it can be connected to either a single circuit (alarm or alarm and trouble) or up to three circuits (alarm, supervisory, and trouble).
Note:
For detailed information and wiring, refer to the RPM installation sheet P/N 3100430.
Below are application diagrams for using the RPM.
Note:
The RPM must be mounted in an MFC-A enclosure immediately adjacent to the panel and in conduit.
Alarm transmitted only
FireShield
TB3
NO
TRBL C
NC
NO
SUP
NO
ALM
C-
C+
24VOUT
+
From ALRM on RPM
(brown wire)
From COM on RPM
(black wire)
From +24 on RPM
(red wire)
Alarm and trouble transmitted on a single circuit
Note:
JP1 on the RPM must be OUT.
FireShield
TB3
NO
TRBL C
NC
NO
SUP
NO
ALM
C-
C+
24VOUT
+
From TRBL on RPM
(yellow wire)
From ALRM on RPM
(brown wire)
From COM on RPM
(black wire)
From +24 on RPM
(red wire)
Alarm, supervisory, and trouble transmitted on separate circuits
Note:
JP1 on the RPM must be IN.
FireShield
TB3
NO
TRBL C
NC
NO
SUP
NO
ALM
C-
C+
24VOUT
+
From TRBL on RPM
(yellow wire)
From SUPV on RPM
(orange wire)
From ALRM on RPM
(brown wire)
From COM on RPM
(black wire)
From +24 on RPM
(red wire)
2.10
FireShield Technical Reference Manual
Installation
Connecting a CTM module
The CTM4.7 City Tie Module is an interface between the control panel notification appliance circuit and a master box. It provides off-premises signal transmission for systems that must comply with NFPA requirements for Auxiliary
Protective Systems. The CTM4.7 activates a local energy fire alarm box, which provides a 24 Vdc alarm signal (current limited at 200 mA). The 4.7 K
Ω
end of line resistor required by the NAC is built in to the CTM4.7.
Requirements
When connecting a CTM to the panel, the following hardware and programming requirements must be met:
• The NAC used must be dedicated to CTM use only
• All alarm zones must be programmed to activate the dedicated NAC
• The NAC used must not be programmed for Signal
Silence
Specifications
Power: Nominal 24 Vdc @ 200 mA
Municipal box operation: Nominal 24 Vdc
Maximum wiring resistance: 25
Ω
Trip current: 200 mA into 14.5
Ω
coil
Maximum current: 300 mA
Standby current: 20 mA
Mounting: Single gang box
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
The following are wiring diagrams showing how the polarity switches during an alarm condition.
Panel in normal condition
Normal condition
Panel in alarm condition
Alarm condition
CTM4.7
[4]
+
_
_
2
1
[3]
+
[5]
Notification appliance circuit
1
2
+ [1] [2]
+
_
_
Master box
Municipal circuit
Notes
[1] 200 mA into a 14.5
Ω
trip coil max., loop resistance = 25
Ω
[2] This circuit is nonpower-limited and is supervised for grounds and opens, but not shorts
[3] Supervised and power-limited
[4] NAC must be programmed for continuous signal
[5] CTM4.7 must be mounted in the same room as the panel
CTM4.7
[4]
_
+
+
_
2
1
[3]
[5]
Notification appliance circuit
1
2
_
[1] [2] _
+
+
Master box
Municipal circuit
FireShield Technical Reference Manual 2.11
Installation
Connecting an auxiliary power supply
Aux power supplied by the panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed fire alarm power supply.
When using an auxiliary power supply, you must connect the
-24 Vdc auxiliary terminal at the panel to the -24 Vdc output terminal of the listed auxiliary power supply used to power
FireShield devices.
Note:
For detailed wiring information, refer to the installation instructions that came with the auxiliary power supply.
Aux. Power
+
FireShield
FACP
-
To Devices
24 Vdc @ 0.5 A Max.
Installing the terminal shield
The terminal shields for the three, five, and ten zone panels
(model numbers ending in GC or GF) required for Canadian installation, cover and protect the wire connections at the terminal blocks.
To install the terminal shield:
1. Remove the four corner mounting screws from the circuit board. Refer to the diagram below for location.
2. Mount the supplied standoffs to the four corner locations where you removed the screws.
3. Mount the terminal shield to the standoffs using the screws you removed in step 1. Refer to the diagram below.
Standoff
+
UL Listed
Aux. Power Source
-
To Devices
Requiring Additional
Power
2.12
FireShield Technical Reference Manual
Chapter 3
Programming
ANNUN
TROUBLE
16
BATT
TROUBLE
8
GND
FAULT
4
Binary numbers
WALK
TEST
2
Bottom row of LEDs
SIGNAL
SILENCED
1
Overview
Program options and settings
The features and functions of FireShield can be customized through programming. To customize the panel, you choose a program option, then choose a setting for that option. This chapter shows you how to program the panel.
Programming methods
FireShield panels can be programmed using either of two methods.
First, you can use the panel’s LEDs and switches, with or without an FSDACT installed.
Second, you can use a PC with an FSDACT installed. PC programming requires an optional software package, the
FireShield Configuration Utility (model number FSCU). Refer to the FSCU online help system for complete programming instructions.
Programming LEDs
In programming mode, the top row of panel LEDs indicates which program option is selected. Each LED is assigned a binary number, and the total value of the top row equals the option number. If you are not familiar with binary numbers, you can simply match the pattern of the LEDs with the programming instructions.
ALARM
16
TROUBLE
8
SUP
4
Binary numbers
POWER
2
Top row of LEDs
DISABLE
1
FSDACT display
If you are using the optional FSDACT to program the panel, each option and setting is displayed on the LCD display.
The top row of the LCD displays the program option, and the bottom row displays the setting for that option. You can use the programming buttons to step through the options and select the settings you want.
Programming buttons
The panel buttons take on a different function when the panel is in programming mode. The following table shows the buttons and describes what they do in programming mode.
Button Description
REMOTE
DISCON-
NECT
Selects the next program option. The top row of LEDs and the FSDACT LCD change to show the option selected.
WALK
TEST
Selects the previous program option. The
top row of LEDs and the FSDACT LCD change to show the option selected.
RESET
SIGNAL
SILENCE
& DRILL
PANEL
SILENCE
Selects the next setting for the current option. The bottom row of LEDs and the
FSDACT LCD change to show the setting selected.
Selects the previous setting for the current option. The bottom row of LEDs and the
FSDACT LCD change to show the setting selected.
Saves the setting you selected for the current program option.
Each option has a number of possible settings. The bottom row of panel LEDs indicates which setting is selected for the current option. The settings are detailed below in “Custom programming the panel.” Again, each LED is assigned a binary number, and the total value of the bottom row equals the setting number.
The values of all LEDs lit on a single row are added to determine the option or setting number. For example, if the
Gnd Fault, Walk Test, and Signal Silenced LEDs are lit, the value is 7 (4+2+1). This means that setting seven for the current option is selected.
FireShield Technical Reference Manual 3.1
Programming
Using the factory default settings
The panel comes from the factory programmed with a predefined set of defaults. The default settings are:
Find annunciators
Auto signal silence timer
None found
None
Aux power reset No
Signal silence/reset inhibit timer None
IDC zone types Alarm (unverified)
All IDCs activate all NACs
IDC class
NAC class
NAC output (NAC1 – NAC4)
NAC silenceable
Class B
Class B
GENESIS
Silenceable
For a more detailed list of defaults, see Appendix B,
“Programming templates.”
If you want to use the factory programmed settings as they are, you do not need to perform any programming. If you do
not want to use the panel’s default settings, refer to “Custom programming the panel.”
Note:
You must run the Find Annunciators program option after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. These include the FSRSI, FSRZI-A, and FSRRM.
Reloading the factory default settings
When you reload defaults, you return the panel to the factoryprogrammed settings. The primary purpose for loading the defaults is to return the panel to its original settings if the need arises. You can then start fresh by using these settings or custom program one or more options.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Load Defaults No
Do not load default settings
Load default settings
Yes
Key: = OFF, = ON
To reload the default settings:
1. Install program jumper PRG.
The panel common LEDs flash and the panel enters a trouble state. The trouble buzzer sounds.
2. Press Remote Disconnect to select the Load Defaults program option.
3. Press Reset to select Yes, the setting to reload the factory default settings.
4. Press Panel Silence to perform the reload.
The trouble buzzer sounds a long beep as confirmation.
5. Exit program mode by removing the program jumper or continue to the next topic to custom program the panel.
Refer to “Custom programming the panel” for more information.
Using an FSDACT
If you have an FSDACT connected to your system, it must be recognized by the panel before programming. Also, if you remove an FSDACT from your system, it must be removed from the panel’s memory.
To do this, install the program jumper (PRG), then remove the program jumper. This allows the panel to recognize that an
FSDACT was installed or removed from the system.
Custom programming the panel
FireShield functionality can be custom programmed when the factory defaults do not meet your needs. The following options can be custom programmed: defaults annunciators
3. Auto signal silence timer
4. Aux power reset
5. Signal silence/reset inhibit timer
6. IDC zone types (and NACs that activate) class
8. NAC output
10. NAC silenceable
11. Program FSDACT (if installed)
Tip:
We recommend that you program the options in the order they are listed. This matches the order of the LEDs as you increment through each option. The lighting pattern of the
LEDs corresponds to the program option you are programming and follows the binary number pattern associated with each row of LEDs.
3.2 FireShield Technical Reference Manual
Programming
Getting started
You should complete the programming templates found in
Appendix B before you program the panel. NFPA 72 requires that you keep a copy of these sheets on file.
The following table and procedures prepare the panel for custom programming.
1. Program load defaults
In this topic, you do not need to load the defaults. To load the default settings, see the topic “Reloading the factory default settings,” above.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Load Defaults
No
Does not load default settings
Loads the default settings
Yes
Key: = OFF, = ON
To get started:
1. Install program jumper PRG.
The top rows of LEDs flash and the panel enters a trouble state. The trouble buzzer sounds.
2. Press Remote Disconnect to advance to the first programming option (Load Defaults).
The LEDs stop flashing, the Disable LED (binary value 1) lights, and “Load Defaults” is displayed on the FSDACT
LCD display (if installed). The trouble buzzer turns off; however, the panel is still in a trouble state.
The Signal Silenced LED is on, showing that setting No is selected.
3. You can press Reset to step through the settings available for this option (No or Yes). Notice how the Signal
Silenced and Walk Test LEDs switch to indicate the different options.
You are now ready to program your panel.
Notes
• You can exit program mode at any time by removing the program jumper. All saved program selections remain intact. When the jumper is removed, the panel resets.
• If no buttons are pressed for 90 seconds, the system returns to the initial program start state with the top row of LEDs flashing and the buzzer sounding.
To program the panel
If no programming is required for a particular option, it can be skipped. You can use Remote Disconnect to advance to the next option or Walk Test to return to the previous option. To save your changes, you must press Panel Silence before advancing to the next option.
2. Program find annunciators
Description: Verifies and logs each remote annunciator
(FSRSI, FSRZI-A, and FSRRM) connected to your system.
Notes
• This process may take up to 40 seconds. During this time do not remove the program jumper. If the program jumper is removed, you must power down and power up the panel to get back into the programming mode.
• The Find Annunciators program option must be performed if you are using remote annunciators (FSRSI,
FSRZI-A, or FSRRM) or if you add or remove a remote annunciator from your system.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Find Annunc xx now on bus
Does not look for devices.
Find devices
Logs all devices connected to the panel.
To find remote annunciators:
1. Press Remote Disconnect to select the program option.
If an FSDACT is installed, the lower line of the LCD displays “xx now on bus” where xx is the number of devices (between 0 and 12).
2. Press Reset to select Find devices.
3. Press Panel Silence to begin finding devices.
The bottom row of LEDs flashes and the second line of the LCD displays “Finding devices” while the panel searches for all remote annunciators.
When the search is complete, the bottom row of LEDs shows (in binary) the number of devices found. The second line of the LCD displays “was xx now yy.” The number of devices found (now) should equal the number of devices installed. If not, there is a wiring or device problem.
4. To end programming now, remove the program jumper.
Otherwise, continue with “Program auto signal silence timer,” below.
3. Program auto signal silence timer
Description: A timer that, when programmed, automatically silences the NAC circuits 20 minutes after the last alarm event.
FireShield Technical Reference Manual 3.3
Programming
Program option
Top LEDs/LCD
Auto Sig Sil
Setting
Bottom LEDs/LCD
None
Description
NACs stay on until Signal
Silence is pressed
Sil aft 20 mins
NACs automatically turn off after twenty minutes
To program the auto signal silence timer:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
4. Program aux power reset
Description: Causes a temporary interruption of aux power when Reset is pressed. This is so that four-wire smoke detectors can be reset. If this is not programmed, pressing
Reset has no effect on the aux power output.
Caution:
This option must be set to No (continuous) if remote annunciators or relays are being used.
Program option
Top LEDs/LCD
Aux Power Reset
Setting
Bottom LEDs/LCD
Description
No
Continuous 24 Vdc on
AUX PWR terminals
Yes
Resettable 24 Vdc on
AUX PWR terminals
To program aux power reset:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
5. Program signal silence/reset inhibit timer
Description: Programs all NACs with a one-minute silence inhibit. This means that, the NACs cannot be silenced and the panel cannot be reset during their first minute of activation.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Sig Sil Inhibit None
Inhibit one min
Signal Silence/Reset operational immediately after NACs turn on
Signal Silence/Reset operational one minute after NACs turn on
To program the signal silence/reset inhibit timer:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
6. Program IDC zone types
Description: Selects the type and functionality of each IDC.
Note:
See the FireShield ULI and ULC compatibility lists P/N
3100468 for restrictions.
Default: Alarm - unverified, with all NACs active
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Program IDC Alarm-unverified
Alarm-verified
Retard-waterflow
Alarm-unverified: For circuits with smoke detectors and contact devices. All activations are immediately considered as alarms.
Circuit can not be restored until devices are restored to normal and panel is reset.
Alarm-verified: For circuits with smoke detectors and contact devices. 2-wire smoke detector activations are verified (delayed and confirmed) before activating an alarm. 4-wire smoke detectors and contact devices are not verified and immediately considered as alarms.
Circuit can not be restored until devices are restored to normal and panel is reset.
Waterflow (retard): For connection of both vane type and pressure flow switches. Device activation must be maintained for at least 15 seconds before being considered an alarm.
NACs activated by waterflow IDCs can not be silenced until activated devices restore to normal
(panel reset not required).
Circuit can not be restored until devices are restored to normal and panel is reset.
3.4 FireShield Technical Reference Manual
Programming
Waterflow
Ret-wf/superv
Supervisory
Monitor
Wf-supervisory
Waterflow (no retard):
For connection of both vane type and pressure flow switches. Activations are immediately considered as alarms.
NACs activated by waterflow IDCs can not be silenced until activated devices restore to normal
(panel reset not required).
Circuit can not be restored until devices are restored to normal and panel is reset.
Waterflow (retard) /
supervisory (latching):
Special IDC that allows connection of both waterflow and supervisory devices on the same 2wire circuit. Requires the use of two resistors (3.6 k
Ω and 1.1 kΩ). The waterflow portion of the circuit functions the same as IDC Type 3 Waterflow
(retard) and the supervisory portion functions the same as
IDC Type 7 Supervisory
(latching).
Waterflow (no retard) /
supervisory (latching):
Special IDC that allows the connection of both waterflow and supervisory devices on the same 2wire circuit. Requires the use of two resistors (3.6 k
Ω and 1.1 kΩ). See
“Waterflow (no retard)” and “Supervisory
(latching)” settings for additional information.
Supervisory (latching):
For the connection of supervisory devices.
Momentary activation of normally open devices immediately places the panel in a supervisory state and turns on supervisory LEDs and relays. Circuit can not be restored until devices are restored to normal and panel is reset.
Monitor: Monitoring of normally open switches for other functions (fire door position, etc.). Not approved for use under
ULC 527 in Canada.
To program IDC zone types:
1. Press Remote Disconnect to select the program option.
For new panels, the Trouble LED of IDC 1 lights.
Otherwise, the Trouble LED of the last IDC programmed lights. To select an IDC for programming, press the IDC
Disable button.
2. Press Reset to select the desired IDC zone type.
Note:
If you program an IDC as a waterflow/supervisory, a supervisory activation will not turn on the outputs
(NACs and relays). Only a waterflow activation will turn on the outputs.
3. Program which NAC activates for the IDC.
The Trouble LED for the NAC lights to indicate which
NAC is associated with the IDC. Press the NAC Disable button to deselect (or reselect) it for activation.
The default is that each alarm or waterflow IDC activates all NACs. Only alarm, waterflow, and supervisory can operate NACs. Alarm and supervisory IDCs should not be assigned to the same NACs. Monitor zones can not be assigned to NACs.
4. Press Panel Silence to save your selection for the IDC.
The trouble buzzer sounds a long beep as confirmation.
5. Select the next IDC for programming by pressing its
Disable button.
The corresponding Trouble LED lights to indicate your selection.
6. Program the IDC by repeating steps 2 through 4, above.
Complete this procedure for each IDC before moving on to the next program option.
7. Program IDC classes
Description: Programs the IDCs as either Class B or Class A.
This option only appears for panels that can be configured as
Class A. All IDC types except the two combination waterflow/ supervisory options can be configured as Class A
For Class A operation, you need to configure a pair of IDCs, one odd and one even. When you change the class of an IDC, you must change the class of both IDCs in the pair.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
IDC wired as Class B
IDC Class Class B
IDC wired as Class A
Class A
FireShield Technical Reference Manual 3.5
Programming
To program IDC classes:
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
1. Press Remote Disconnect to select the program option.
The last programmed IDC Trouble LED stays lit.
2. Press Reset to select Class A or Class B.
3. Press Panel Silence to save your selection.
The trouble buzzer sounds a long beep as confirmation.
4. Program each IDC class by pressing the IDC Disable button to light the IDC Trouble LED. When the Trouble
LED is lit, you can program the IDC class by repeating steps 2 and 3 above.
Note:
Make sure you set the IDC jumpers to match the class for which you program the IDC.
8. Program NAC classes
Description: Programs the NACs as either Class B or Class A.
For Class A operation, you need to configure a pair of NACs, one odd and one even. When you change the class of an NAC, you must change the class of both NACs in the pair.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
NAC wired as Class B
NAC Class Class B
NAC wired as Class A
Class A
NAC Output Continuous
Temporal
GENESIS
To program NAC outputs:
NAC outputs
continuous signal: For strobes and notification appliances that selfgenerate a temporal pattern.
NAC outputs temporal
(3-3-3) signal: Universal
3-3-3 pattern required for evacuation signals by
NFPA 72. Used when notification appliances are not capable of selfgenerating a temporal pattern.
GENESIS sync/silence:
Used with Genesis and
Enhanced Integrity horns and strobes. Genesis and
Enhanced Integrity appliances maintain synchronization per UL
1971. For Genesis devices, it allows connected horns to be silenced while strobes on the same 2-wire circuit continue to flash until the panel is reset.
To program NAC classes:
1. Press Remote Disconnect to select the program option.
For new panels, the Trouble LED of NAC 1 lights.
Otherwise, the Trouble LED of the last NAC programmed lights. To select a NAC for programming, press the NAC
Disable button.
2. Press Reset to select Class A or Class B.
Note:
Whenever NAC pairs are programmed for Class A, output pairs must be programmed for the same output types.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
4. Program each NAC class by pressing the NAC Disable button to light the NAC Trouble LED. When the Trouble
LED is lit, you can program the NAC class by repeating steps 2 and 3 above.
Note:
Make sure you set the NAC jumpers to match the class for which you program the NAC.
1. Press Remote Disconnect to select the program option.
The last programmed NAC Trouble LED stays lit.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
4. Program the output for each NAC by pressing the NAC
Disable button to light the Trouble LED for that NAC.
When the Trouble LED is lit, you can program the NAC by repeating steps 2 and 3 above.
Note:
Whenever NAC pairs are programmed for Class A, output pairs must be programmed for the same output types.
10. Program NAC as Silenceable
Description: Programs the NAC as silenceable. If set to No, the NAC, when activated, cannot be silenced using the Signal
Silence & Drill button or the auto signal silence feature. It can only be silenced with a panel reset.
9. Program NAC outputs
Description: Programs the output of each NAC.
3.6 FireShield Technical Reference Manual
Programming
Program option
Top LEDs/LCD
NAC Silenceable
Setting
Bottom LEDs/LCD
Description
No
Yes
NAC does not turn off when Signal Silence is pressed
NAC turns off when
Signal Silence is pressed
Note:
It is not necessary to select this option for waterflow
IDCs. NACs assigned to waterflow IDCs can not be silenced as long as the IDC has an active input. The IDC remains in the alarm state until the panel is reset.
If the auto signal silence feature is programmed, the panel silences the associated NAC when the waterflow switch is no longer active and the timer has expired.
If Signal Silence & Drill is pressed when a waterflow circuit is active, the associated NAC circuit does not silence until the waterflow condition is no longer active.
To program the NACs as silenceable:
1. Press Remote Disconnect to select the program option.
The last programmed NAC Trouble LED stays lit.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
4. Program each NAC by pressing the NAC Disable button to light the Trouble LED for that NAC. When the Trouble
LED is lit, you can program the zone by repeating steps 2 and 3 above.
11. Programming the FSDACT
Description: Initiates the FSDACT for programming. This option is not displayed if you do not have a FSDACT; you can proceed to “Finishing up,” below.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Program DACT No
Yes
Does not switch to
FSDACT programming mode.
Automatically switches the panel to FSDACT programming mode.
To program the FSDACT:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select Yes or No.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
If you selected Yes, the panel automatically switches to
FSDACT programming mode and “DACT Programming” is displayed on the LCD. Refer the next topic “FSDACT programming” for complete programming instructions.
If you selected No, proceed to “Finishing up,” below. You can return to FSDACT programming at any time.
Tip:
If no panel programming is needed, you can go directly to this program option by following these steps:
1. Insert the program jumper.
2. Press Remote Disconnect.
3. Press Walk Test.
Finishing up
To finish up:
1. Remove the program jumper PRG.
You can store the suitcase jumper on one pin.
2. Panel programming is complete.
3. The panel will reset. At the conclusion of the reset, make sure the panel is free of troubles. If IDC or NAC trouble
LEDs are on, check to see that the jumper settings match the program options selected.
4. Test all circuits and panel functions to make sure that the panel was programmed correctly.
FireShield Technical Reference Manual 3.7
Programming
FSDACT programming
Programming the FSDACT sets up the dialer for communication with the central monitoring station. It also sets a number of other options such as date, time, phone numbers, etc. Many of the options have default settings, which are detailed below. These settings can be changed if desired.
Programming buttons
The panel buttons function in the following way when in
FSDACT programming mode.
Button descriptions
Button Description
Selects the next program option
REMOTE
DISCON-
NECT
Selects the previous program option
WALK
TEST
RESET
SIGNAL
SILENCE
& DRILL
PANEL
SILENCE
Selects the next setting for the current option.
Also increments through the digits of numeric entries such as telephone numbers
Selects the previous setting for the current option
Also decrements through the digits of numeric entries such as telephone numbers
Saves the setting you selected for the current program option
Advances cursor to the next digit of a field
(e.g. entering a phone number)
Note: When pressed in the last digit of a field, the information is saved and the next program option is displayed
Tip:
In this chapter we tell you to press Reset to scroll through each list of settings. However, to enter a setting that’s near the end of the list, it may be faster to press Signal Silence & Drill to move backwards through the list of selections.
Digit descriptions
The following table describes the function of each digit that can be entered in FSDACT programming fields.
Digit Telephone number 4.2 event codes
0 to 9
A
B
C
DTMF A
DTMF B
Hexadecimal A (10)
Hexadecimal B (11)
Hexadecimal C (12)
Digit
D
E
Telephone number 4.2 event codes
Hexadecimal D (13)
Hexadecimal E (14) last digit)
, DTMF , (used for a pause between digits)
Getting started
You should complete the programming templates found in
Appendix B before you program the panel. NFPA 72 requires that you keep a copy of these sheets on file.
Follow the steps below to prepare the panel for FSDACT programming. If you are already in programming mode, skip the first three steps and start at number four below.
To get started:
1. Install program jumper PRG.
Panel common LEDs flash and the panel enters a trouble state. The trouble buzzer sounds.
2. Press Remote Disconnect to advance to the first programming option (Load Defaults).
The LEDs stop flashing, the Disable LED (binary 1) lights, and Load Defaults is displayed on the LCD. The trouble buzzer turns off; however, the panel is still in a trouble state.
3. Do not load defaults. Press Walk Test until “DACT
Programming” is displayed.
4. Press Reset until Yes is selected.
5. Press Panel Silence to begin FSDACT programming.
The panel automatically switches to FSDACT programming mode and “DACT Programming” is displayed on the LCD.
6. Enter your password. Refer to “Programming the
FSDACT” below.
Note:
You can exit from programming mode at any time by removing the program jumper. All saved program selections will remain intact.
3.8 FireShield Technical Reference Manual
Programming the FSDACT
When you program the FSDACT, you’ll follow these general steps:
1. Enter your passcode
2. Load default settings
3. Edit
4. Enter date
5. Enter the time
6. Select the FSDACT mode
7. Enter the (DACR1) primary phone number
8. Enter the (DACR1) secondary phone number
9. Enter the (DACR1) account code
10. Select the DACR1 alarm format
11. Select the restore option for CMS one
12. Enter retry count one
13. Enter retry time one
14. Enter the (DACR2) primary phone number
15. Enter the (DACR2) secondary phone number
16. Enter the (DACR2) account code
17. Select the DACR2 alarm format
18. Select the restore option for CMS two
19. Enter retry count two
20. Enter retry time two
21. Select tone or pulse dialing
22. Select AC fail delay time
23. Enter the transmission test time
24. Select the transmission test frequency
25. Enter the number of rings to answer
26. Select the ring type
27. Enable (disable) call back
28. Enter the call back phone number
Tip:
If you save an incorrect digit, press Walk Test then
Remote Disconnect. This returns the cursor to the first digit.
Press Panel Silence until the cursor is at the incorrect digit.
Enter the correct digit, then press Panel Silence to save and advance to the next digit.
1. Enter your passcode
Description: Access to dialer programming is passcode restricted. For security, the default passcode should be changed as part of the installation. (To change the passcode, refer to “Edit passcode,” below.)
Format: 7 digits
Default: 1111111
To enter your passcode:
1. Press Reset (or Signal Silence & Drill) to scroll through the setting list until the first digit of your passcode is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
Programming
3. Press Reset (or Signal Silence & Drill) until the next digit of your passcode is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
6. When you press Reset at the last digit, the system automatically advances you to the next program option.
2. Load default settings
Description: Loads the factory default settings for each program option.
Settings: Yes = Loads the default settings
No = Does not load the default settings
Default: No
To load default settings:
1. Press Reset to select Yes or No.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
3. Edit your passcode
Description: You have the option to change your passcode or continue with programming.
Format: 7 digits
Default: No default
To skip changing your passcode:
1. Press Remote Disconnect to advance to the next program option.
To change your passcode:
1. Press Reset until the first digit of your new passcode is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
6. When you press Panel Silence at the last digit, the system automatically advances you to the next program option.
4. Enter the date
Description: Sets the current date.
Format: MMDDYYYY
Default: 01012002
FireShield Technical Reference Manual 3.9
Programming
Tip:
Don’t forget that you can press Reset or Signal Silence &
Drill to scroll through the list of settings. It may be faster to press Signal Silence & Drill to scroll backwards through the settings.
To enter the current date:
1. Press Reset until the correct month is displayed.
2. Press Panel Silence to save the month setting and advance to the day setting.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the correct day is displayed.
4. Press Panel Silence to save the day setting and advance to the year setting.
The trouble buzzer sounds a long beep as confirmation.
5. Press Reset until the correct year is displayed.
6. Press Panel Silence to save the year setting and advance to the next option.
The trouble buzzer sounds a long beep as confirmation.
5. Enter the time
Description: Sets the current time.
Format: HHMM
Default: 0000
To enter the current time:
1. Press Reset until the correct hour is displayed.
2. Press Panel Silence to save the hour setting and advance to the minute setting.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the correct minute is displayed.
4. Press Panel Silence to save the minute setting and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
6. Select the FSDACT mode
Description: Determines how the FSDACT operates.
Settings: Single Line DACT
Dual Line DACT (required by UL 864)
Modem/LCD
LCD only only
Default: Dual Line DACT
To select the desired FSDACT mode:
1. Press Reset to select the desired format.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
Note:
If Single Line DACT is selected, dual line programming is skipped. If Modem/LCD only is selected, all account and receiver related programming is skipped. If LCD only is selected, all account, receiver, and telephone related programming is skipped.
7. Enter the (DACR1) primary phone number
Note:
If a DACR1 primary phone number is not entered, skip
“Enter the (DACR1) secondary phone number” through
“Enter retry count one,” inclusive.
Description: Specifies the primary phone number that is used to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
Tip:
If you save an incorrect digit, press Walk Test then
Remote Disconnect. This returns the cursor to the first digit.
Press Panel Silence until the cursor is at the incorrect digit.
Enter the correct digit, then press Panel Silence to save and advance to the next digit.
To enter the primary phone number:
1. Press Reset until the first digit of the phone number is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
Note:
If less than 20 digits are entered, press Panel
Silence again or Remote Disconnect to advance to the next program option.
6. When you press Panel Silence at the last digit (20th digit), the system automatically advances you to the next program option.
8. Enter the (DACR1) secondary phone number
Description: Specifies the secondary phone number that is used to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
To enter the secondary phone number, follow the same steps you used to enter the primary phone number. (See “Enter the
(DACR1) primary phone number” above.)
3.10 FireShield Technical Reference Manual
Programming
9. Enter the (DACR1) account code
Description: Sets the account code for DACR1. This is the code that is used by the monitoring facilities receiver to identify the panel location and response information. Use a leading zero to enter a three-digit account code as four digits.
Format: 4 digits
Default: FFFF
12. Enter retry count one
Description: Sets the maximum number of failed attempts to deliver an alarm to a DACR.
Settings: 5 – 10 retries
Default: 5 (retries)
To enter retry count one:
To enter the account code:
1. Press Reset until the first digit of the account code is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
6. When you press Panel Silence at the last digit, the system automatically advances you to the next program option.
1. Press Reset to change the retry count.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
13. Enter retry time one
Description: Sets the delay time before trying to resend an alarm to a DACR.
Format: 2 digits max (5 – 10 seconds)
Default: 5 (seconds)
To enter retry time one:
10. Select the DACR1 alarm format
Description: Specifies the type of alarm format the monitoring facility (DACR) will accept. Selecting either Contact ID or 4/2 loads default event codes (see Appendix E for more information).
Settings: Contact ID
EST 4/2 (SIA DC-02 P3 with hexadecimal event codes)
Default: Contact ID
To select the DACR1 alarm format:
1. Press Reset to select the desired format.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
1. Press Reset to enter the retry time.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
14. Enter the (DACR2) primary phone number
Note:
If a DACR2 primary phone number is not entered, skip
“Enter the (DACR2) secondary phone number” through
“Enter retry count two,” inclusive.
Description: Specifies the primary phone number that is used to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
11. Select the restore option for CMS one
Description: Determines whether or not restoration events are sent to the first central monitoring station.
Settings: Send restores restores
Default: Send restores
To select the restore option:
1. Press Reset to select the restore option for CMS one.
2. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
To enter the primary phone number:
1. Press Reset until the first digit of the phone number is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
Note:
If less than 20 digits are entered, press Panel
Silence again or Remote Disconnect to advance to the next program option.
FireShield Technical Reference Manual 3.11
Programming
6. When you press Reset at the last digit (20th digit), the system automatically advances you to the next program option.
Settings: Send restores restores
Default: Send restores
15. Enter the (DACR2) secondary phone number
Description: Specifies the secondary phone number that is used to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
To enter the secondary phone number, follow the same steps you used to enter the primary phone number. (See “Enter the
(DACR2) primary phone number” above.)
To select the restore option:
1. Press Reset to select the restore option for CMS two.
2. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
16. Enter the (DACR2) account code
Description: Sets the account code for DACR2. This is the code that is used by the monitoring facilities receiver to identify the panel location and response information.
Format: 4 digits
Default: FFFF
19. Enter retry count two
Description: Sets the maximum number of failed attempts to deliver an alarm to a DACR.
Settings: 5 – 10 retries
Default: 5 (retries)
To enter retry count two:
To enter the account code:
1. Press Reset until the first digit of the account code is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
6. When you press Reset at the last digit, the system automatically advances you to the next program option.
17. Select the DACR2 alarm format
Description: Specifies the type of alarm protocol the DACR will accept.
Settings: Contact ID
EST 4/2 (SIA DC-02 P3 with hexadecimal event codes)
Default: Contact ID
To select the DACR2 alarm format:
1. Press Reset to select the desired format.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
1. Press Reset to change the retry count.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
20. Enter retry time two
Description: Sets the delay time before trying to resend an alarm to a DACR.
Format: 2 digits max (5 – 10 seconds)
Default: 5 (seconds)
To enter retry time two:
1. Press Reset to change the retry time.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
21. Select tone or pulse dialing
Description: Specifies whether the phone line is set up for tone dialing or pulse dialing.
Settings: Tone
Pulse
Default: Pulse
Note:
Touch tone is recommended where available.
To select tone or pulse dialing:
18. Select the restore option
Description: Determines whether or not restoration events are sent to the second central monitoring station.
1. Press Reset to select tone or pulse dialing for line 1.
2. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
3.12 FireShield Technical Reference Manual
Programming
3. Press Reset to select tone or pulse dialing for line 2.
4. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
22. Select AC fail delay time
Description: The AC fail delay lets you set the amount of time before the panel signals that it is operating with insufficient or no AC power.
Settings: 6 hours (central station)
15 hours (remote station)
Default: 6 hours
To select the AC fail delay time:
1. Press Reset to select the desired AC fail delay time.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
23. Enter the transmission test time
Description: Specifies the time of day the transmission test message is sent to the CMS. Values are in 24-hour time.
Format: 0000 – 2359
Default: 0217
To enter the transmission test time:
1. Press Reset to enter the hour.
2. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset to enter the minutes.
4. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
24. Select the transmission test frequency
Description: Specifies the number of days between sending a transmission test message to the CMS.
Note:
NFPA 72 and UL 864 require daily tests for commercial systems.
Settings: 0 = None
1
2 = 30 days
Default: 1 (daily)
To select the transmission test frequency:
1. Press Reset to select the transmission test frequency.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
25. Enter the number of rings to answer
Description: Sets the number of rings that are ignored before answering an incoming modem call.
Settings: 0 – 15 rings
Default: 5 (rings)
To enter the number of rings:
1. Press Reset to change the number of rings to answer.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
26. Select the ring type
Description: Specifies the type of ring expected when an incoming call is received.
Default: Ring type (additional options to be added in future release). DACT answers any ring type after programmed ring count.
To select the ring type:
1. Press Reset to select ring type.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
27. Enable (disable) call back
Description: Call back adds increased security when uploading or downloading. When an incoming call is received on line one, the panel establishes a connection and waits for a valid password. If call back is not enabled, uploading or downloading begins. If call back is enabled, the panel disconnects the incoming call and dials the programmed call back number. Once the connection is reestablished, uploading or downloading can begin.
Settings: No
Yes
Default: No
To enable (disable) call back:
1. Press Reset to select enable (disable) call back.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
FireShield Technical Reference Manual 3.13
Programming
28. Enter the call back phone number
Description: Specifies the phone number that is used for call back.
Format: Up to 20 digits
Default: Blank
To enter the call back phone number:
1. Press Reset until the first digit of the phone number is displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
Note:
If less than 20 digits are entered, press Panel
Silence again or Remote Disconnect to advance to the next program option.
6. When you press Reset at the last digit (20th digit), the system automatically advances you to the next program option.
Event notification programming
Event notification programming determines where events are sent. Events can be sent to the primary, secondary, or both central monitoring stations (CMS), or you can choose not to send the event at all.
To program event notification, follow these general steps:
1. Select CMS locations for event reporting
2. Enter the system trouble restore code
Note:
If you are only using one central monitoring station and are using the default settings, no further programming is required. You can exit from programming by removing the program jumper.
The first event notification programming option after completing “Select the restore option” is “Panel Tst Rcvr.”
Twenty-one event receiver locations must be programmed using steps described below, under “Select CMS locations for event reporting.”
CS Tst Rcvr
CS AB Tst Rcvr
Walk Tst Rcvr
Drill Rcvr
Reset Rcvr
Program Mode Rcvr
DACT Disab Rcvr
Panel Sil Rcvr
Signal Sil Rcvr
Grd Fault Rcvr
Low Batt Rcvr
Mis Batt Rcvr
Int Comm Tr Rcvr
AC Fail Rcvr
Charger Tr Rcvr
Xfrmr 2 Tr Rcvr
Aux Pwr Tr Rcvr
Periph Trb Rcvr
Line 1 Trb Rcvr
Line 2 Trb Rcvr
Delivery Tr Rcvr
After programming the receiver locations, continue with the steps described under “Enter the system trouble restore code.”
1. Select CMS locations for event reporting
Description: Specifies which CMS receives each event.
Settings: None
1
CS
CS 1 and 2
Default: CS 1
To select the CMS locations for event reporting:
1. Press Reset to select the desired CMS location.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
3. Repeat steps 1 and 2 to set the CMS location for each option.
4. When you reach the last option, proceed to "Enter the system trouble restore code" below.
2. Enter the system trouble restore code
Description: Sets the code that is transmitted to the CMS with trouble restoral events.
Format: 1 digit (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” This can be changed if needed.
To enter the system trouble restore code:
1. Press Reset to increment the restore code if it needs to be changed.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
3.14 FireShield Technical Reference Manual
Programming
Circuit programming
Circuit programming defines the routes and codes used to report IDC and NAC events. Unless the options described below are changed, the factory default event codes are sent to
CS 1 only. If the default selections are acceptable, you can skip to “End programming” below.
Note:
IDC disabled and NAC disabled events are automatically routed to the receiver you select for the IDC trouble activation and NAC trouble activation events.
To program the circuits, you’ll follow these general steps:
1. Select the receiver for each IDC event
2. Select the receiver for each NAC trouble event
3. Set up or change system event codes
4. Set up or change IDC event codes
5. Set up or change the IDC zone restoration code
6. Set up or change the NAC trouble code
7. Set up or change the NAC trouble restoration code programming
To select the receiver for each IDC event:
1. Select an IDC for programming by pressing the Disable button for that IDC.
2. Determine the zone type assigned to the selected IDC.
Refer to the “Panel programming worksheet” you completed.
3. Use the table shown above to determine which event types need to be configured.
4. Press Remote Disconnect or Walk Test to select the desired event type.
5. Press Reset to select the desired receiver.
6. Press Panel Silence to save the setting.
The trouble buzzer sounds a long beep as confirmation.
7. Repeat steps 4 and 5 for each event type you need to configure.
8. Repeat steps 1 through 7 for each IDC you want to program.
9. When the required IDCs have been programmed, press
Remote Disconnect to advance to the next program option.
1. Select the receiver for each IDC event
Description: Determines where alarm, waterflow, trouble, supervisory, and monitor IDC events are reported.
An IDC has five possible events. You only need to program those events that apply to the zone type of the selected IDC.
For example, if the IDC is configured as alarm-verified (or alarm-unverified) you only need to configure the alarm and trouble events. You don’t need to select a receiver for the waterflow, supervisory, or monitor events for that IDC.
The following table lists the events that apply to each zone type.
2. Select the receiver for each NAC trouble event
Description: Determines where an NAC trouble event is reported.
Note:
You must program each NAC during this step.
Settings: None
1
CS
CS 1 and 2
Default: CS 1
Zone type Alarm Waterflow Trouble Supervisory Monitor
Alarm X X
To select the receiver for each NAC trouble event:
Waterflow X X
Waterflow / X X X
1. Select an NAC for programming by pressing the Disable button for that NAC.
Supervisory
2. Press Reset to select the desired receivers.
Supervisory X X
Monitor X X
3. Press Panel Silence to save the setting.
The trouble buzzer sounds a long beep as confirmation.
Settings: None
CS
2
CS 1 and 2
4. Repeat steps 1 through 3 for each NAC you want to program.
5. When all NACs have been programmed, press Remote
Disconnect to advance to the next program option.
Default: CS 1
3. Set up or change system event codes
Description: Defines the 4/2 event codes (reset, drill, trouble silence, etc.) that are sent to the CMS for system level events.
FireShield Technical Reference Manual 3.15
Programming
Format: 2 digits (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” These can be changed if needed.
Note:
If you are using Contact ID or the default 4/2 codes, you can skip ahead to “End programming” now.
To change system event codes:
1. Press Reset or Signal Silence & Drill to scroll to the event code that you want to change.
2. Press Reset to change the first digit of the code.
3. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
4. Press Reset to change the second digit.
5. Press Panel Silence to save.
6. Press Reset to advance to the next event code.
4. Set up or change IDC event codes
Description: Defines the 4/2 event codes (alarm, sup, trouble, etc.) that are sent to the CMS for IDC events.
Format: 2 digits (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” These can be changed if needed.
To change IDC event codes:
1. Select an IDC for programming by pressing the Disable button for that IDC.
2. Press Reset or Signal Silence & Drill to scroll to the event code that you want to change.
3. Press Reset to change the first digit of the code.
4. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
5. Press Reset to change the second digit.
6. Press Panel Silence to save.
7. Repeat steps 1 through 6 for each IDC you want to program.
8. Press Reset to advance to the next event code.
5. Set up or change the IDC zone restoration code
Description: Sets the 4/2 event code that is transmitted to the
CMS for an IDC restoral event.
Format: 1 digit (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” This can be changed if needed.
To change the IDC zone restoration code:
1. Press Reset to change the IDC zone restoration code.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
6. Set up or change the NAC trouble code
Description: Sets the 4/2 event code that is transmitted to the
CMS for a NAC trouble event.
Format: 2 digits (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” This can be changed if needed.
To change the NAC trouble code:
1. Select an NAC for programming by pressing the Disable button for that NAC.
2. Press Reset to change the first digit of the code.
3. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
4. Press Reset to change the second digit.
5. Press Panel Silence to save.
6. Repeat steps 1 through 5 for each NAC you want to program.
7. Press Reset to advance to the next program option.
7. Set up or change the NAC trouble restoration code
Description: Sets the 4/2 event code that is transmitted to the
CMS for a NAC restoral event.
Format: 1 digit (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” This can be changed if needed.
To change the NAC trouble restoration code:
1. Press Reset to change the NAC trouble restoration code.
2. Press Panel Silence to save and advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
8. End programming
Programming is complete.
To end programming:
3.16 FireShield Technical Reference Manual
The system takes you back to the beginning of FSDACT programming (Program DACT).
2. Remove the program jumper PRG.
You can store the jumper on one pin of the jumper.
Editing previously programmed information
You may find it necessary to change information that you previously programmed (e.g. if a phone number changes).
To edit previously programmed information:
1. Install program jumper PRG.
2. Press Remote Disconnect until “DACT Programming” is displayed.
3. Press Reset until Yes selected.
4. Press Panel Silence to save.
6. Press Remote Disconnect to advance to the programming option you want to change.
The currently stored data is displayed.
7. Edit the program option with the desired setting.
Use the program buttons to enter the information.
8. Press Panel Silence to save.
9. Edit other program options as needed.
10. Exit from program mode by removing jumper PRG.
Other FSDACT options
The following options can only be changed using the
FireShield Configuration Utility. Refer to the FireShield
Configuration Utility online help system for details on programming these options.
Swinger shutdown
Description: Automatically inhibits transmission of a single event more consecutive times than the value entered.
Format: 0 – 255
Default: 0 (none)
Contact ID
Contact ID codes can only be changed when using the configuration utility.
FireShield Technical Reference Manual
Programming
3.17
Programming
3.18 FireShield Technical Reference Manual
Chapter 4
Maintenance
Preventive maintenance
Before commencing testing, notify all areas where the alarm sounds and off-premises locations that receive alarm and trouble transmissions that testing is in progress.
• Records of all testing and maintenance shall be kept as required by the authority having jurisdiction.
• Required tools:
-Slotted screwdriver, insulated
-Digital multimeter
-1.1 k
Ω
, 1 W resistor
-12 in (30.5 cm) jumper lead with alligator clips
-Panel door key
-Sound level meter
• A complete check of installed field wiring and devices should be made at regular intervals in accordance with
NFPA 72, Canadian Electrical Code Part I, ULC S524, and S536 requirements. This includes testing all alarm and supervisory initiating devices and circuits and any off-premises connections.
• Panel operation should be verified in the alarm, supervisory, and trouble modes.
• To ensure that the panel can be powered when primary power is lost, the batteries should be periodically inspected, tested, and replaced (at a minimum) every four years.
Preventive maintenance schedule
Refer to NFPA 72, Chapter 7 Inspection, Testing, and
Maintenance, Canadian Electrical Code Part I, ULCS524, or
ULCS536 for more information on required inspection and testing methods and frequency of fire alarm systems and devices. For detector sensitivity and functionality testing, refer to the detector manufacturer's installation instructions.
Canadian tests for grounds, opens, and shorts
ULC requires that you test ground fault, open circuit, and short circuit indications.
For ground fault tests, directly short one leg of the circuit to chassis ground
.
The Ground Fault and Trouble LEDs must light.
For NAC and IDC open circuit tests, remove the EOL resistor from the last device on the circuit. The Trouble LED must light.
For NAC short circuit testing, place a short across each NAC output individually. The individual NAC LED must light as well as the common LED.
For AUX power short circuit testing, place a short across the
+24 V and -24 V at the panel. The common trouble LED must light.
For communications testing, place a short across C+ and C-.
The annunciator trouble LED must light.
FireShield Technical Reference Manual 4.1
Maintenance
4.2
FireShield Technical Reference Manual
Appendix A
Calculations
Battery calculation worksheet
Use this worksheet to determine the minimum amperage capacity required for the panel's standby battery. You can obtain operating current requirements for notification appliances from their respective installation sheets.
Notes
[1] Base panel includes the main controller board with no load, only EOL resistors.
Standby
Current (mA)
Base panel [1]
FSDACT (optional)
Aux current (see Form A)
IDC detector current [see Form B]
NAC 1 load [see page A.3]
NAC 2 load [see page A.3]
NAC 3 load [see page A.3]
NAC 4 load [see page A.3]
0
0
0
0
(40)
[3]
Total current
Required standby and alarm time ×
Standby current: three-zone - 110 mA, five-zone - 120 mA, ten-zone - 145 mA
Alarm current: three-zone - 145 mA, five-zone - 170 mA, ten-zone - 250 mA)
[2] The maximum battery size the panel can charge is 18 Ah
(Power-Sonic P/N PS-12180-NB or equivalent). Refer to
"Panel specifications" in Chapter 2 for more information.
If batteries over 7 Ah are required for the three- and fivezone panels, you must use the BC-2 battery cabinet. Refer to installation sheet P/N 3100027.
[3] Use maximum value or actual calculated value from
Form B. The IDC alarm current is included in the panel alarm current.
Alarm
Current (mA)
(60)
Standby time 24 or
60 hour
× mAh +
Alarm time 5 min = 0.083 hr
10 min = 0.167 hr
15 min = 0.250 hr
30 min = 0.500 hr mAh
Battery amp hour total =
Minimum battery size [2]
=
= mAh
÷
1000
Ah
×
1.2
Ah
FireShield Technical Reference Manual A.1
Calculations
Form A
Module
FSRSI [1]
FSRZI-A [1]
FSRRM common [1]
FSRRM zone [1]
Other AUX
Total AUX [5] [6]
Quantity
Standby current
(mA)
Qty
×
Standby current (mA)
12
8
30
8
Alarm current
(mA)
48
35
41
65
Qty
×
Alarm current (mA)
Form B
(Note: Calculate IDC detector load or use maximum load.)
IDC
Quantity of detectors [2]
Detector current
(mA) [3]
Total standby current [4]
(quantity x current in mA)
IDC1
IDC2
IDC3
IDC4
IDC5
IDC6
IDC7
IDC8
IDC9
IDC10
Total current for all IDCs =
Max IDC standby current: FS302 = 4.5 mA, FS502 = 7.5 mA, and FS1004 = 15.0 mA
Notes
[1] Use of FSRSI, FSRZI-A, and FSRRM is limited as follows: Three- and five-zone panels support 2 FSRSIs, 2 FSRZI-As, and 4
FSRRMs, ten-zone panels support 2 FSRSIs, 4 FSRZI-As, and 6 FSRRMs.
[2] See the FireShield UL and ULC Compatibility List (P/N 3100468) for the maximum number of detectors per IDC.
[3] See FireShield UL and ULC Compatibility List (P/N 3100468) for detector current ratings.
[4] Maximum current per IDC may not exceed 1.5 mA.
[5] Aux power supplied by panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed fire alarm power supply.
[6] When using an auxiliary power supply, you must connect the -24 OUT connection on the panel to the negative connection on the auxiliary power supply. Refer to the installation section for more information.
A.2
FireShield Technical Reference Manual
Calculations
Notification appliance voltage drop calculation
NAC 1 voltage drop calculations
Circuit length Total circuit current [2] feet x amps x
Wire resistance per 1000 ft [1]
Ω ÷
1000 =
Voltage drop
Panel voltage
[4] –
Voltage drop
=
End of line voltage [3]
Voltage drop
Panel voltage
÷ [4] =
Voltage drop %
NAC 2 voltage drop calculations
Circuit length Total circuit current [2] feet x amps x
Wire resistance per 1000 ft [1]
Ω ÷
1000 =
Voltage drop
Panel voltage
[4] –
Voltage drop
=
End of line voltage [3]
Voltage drop
Panel voltage
÷ [4] =
Voltage drop %
NAC 3 voltage drop calculations
Circuit length feet x
Total circuit current [2] amps x
Wire resistance per 1000 ft [1]
Ω ÷
1000 =
Voltage drop
Panel voltage
[4] –
Voltage drop
=
End of line voltage [3]
Voltage drop
Panel voltage
÷
[4] =
Voltage drop %
NAC 4 voltage drop calculations
Circuit length Total circuit current [2] feet x amps x
Wire resistance per 1000 ft [1]
Ω ÷
1000 =
Voltage drop
Panel voltage
Voltage drop
End of line voltage [3]
Voltage drop
Panel voltage
Voltage drop %
[4] – = ÷ [4] =
Notes
[1] Use 3.5
Ω
for 12 AWG and 2.5 sq mm wire, 5.2
Ω
for 14 AWG and 1.5 sq mm wire, 8.0
Ω
for 16 AWG and 1.0 sq mm wire, and 13.0
Ω
for 18 AWG and 0.75 sq mm wire.
[2] Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device.
[3] Cannot drop below 17 Vdc.
[4] 18.6 V for 230 V at 50 Hz, 18.8 V for 230 V 60 at Hz, 18.9 V for 120 V at 60 Hz
FireShield Technical Reference Manual A.3
Calculations
Notification appliance circuit maximum wire length calculation
Use this worksheet to determine the maximum wire length of a notification appliance circuit. Fill in one worksheet for each
NAC connected to the panel.
Wire length matrix
Wire lengths in the following table are based on a voltage drop of 1.9 volts or 10% and total load at the end of the line.
Maximum wire length
Current required
18 AWG 16 AWG 14 AWG 12 AWG
0.25
0.50
0.75
1.00
1.25
1.50
584
292
194
146
116
92
950
474
316
236
190
158
1460
730
486
364
292
242
2170
1084
722
542
434
362
Maximum signal loss allowed [1]
Wire resistance per 1000 ft/pair [2]
×
÷
1000
V
Ω
Total operating current required [3]
Maximum circuit length
÷
Notes
[1] 1.6 V for 230 V at 50 Hz
1.8 V for 230 V at 60 Hz
1.9 V for 120 V at 60 Hz
[2] Use 3.5
Ω
for 12 AWG and 2.5 sq mm wire, 5.2
Ω
for 14
AWG and 1.5 sq mm wire, 8.0
Ω
for 16 AWG and 1.0 sq mm wire, and 13.0
Ω
for 18 AWG and 0.75 sq mm wire.
[3] Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device.
A ft
A.4
FireShield Technical Reference Manual
Appendix B
Programming templates
Panel programming worksheet
Project name _____________________________ Project address ___________________________________________________________
Programmed by __________________________ Date ____________ Tested by ____________________________ Date ____________
[1] Load defaults
[2] Find annunciators
No (1) Yes (2)
Peripherals installed
Peripherals found
[3] Auto NAC silence timer
[4] Aux power reset
None (1)
No (1)
[5] Signal silence inhibit timer
None (1)
20 minutes (2)
Yes (2)
1 minute (2)
ALARM
Panel LEDs and binary number values
TROUBLE SUP POWER DISABLE
16
ANNUN
TROUBLE
16
8
BATT
TROUBLE
4
Binary values
GND
FAULT
8 4
Binary values
2
WALK
TEST
2
1
SIGNAL
SILENCED
1
[6] IDC zone types
Alarm-unverified (1)
Alarm-verified (2)
Waterflow (retard) (3)
Waterflow (no retard) (4)
Waterflow (retard) / supervisory(latching) (5)
Waterflow (no retard) / supervisory(latching) (6)
Supervisory (latching) (7)
Monitor (8)
NAC Assignment
NAC1
NAC2
NAC3
NAC4
[7] IDC class
Class B (1)
Class A (2)
IDC1
IDC1
IDC2
IDC2
IDC3
IDC3
IDC4
IDC4
IDC5
IDC5
IDC6
IDC6
IDC7
IDC7
IDC8
IDC8
IDC9
IDC9
IDC10
IDC10
[8] NAC classes
Class B (1)
Class A (2)
[9] NAC outputs
Continuous (1)
Temporal (3-3-3) (2)
GENESIS synch/silence (3)
[10] NAC silenceable
NAC1
No (1)
Yes (2)
NAC2
No (1)
Yes (2)
NAC3 NAC4
No (1)
Yes (2)
No (1)
Yes (2)
[ ] = Top row of LEDs binary number value
( ) = Bottom row of LEDs binary number value
= Factory default settings
Button definitions (programming mode)
Remote disconnect - Selects next option
Walk test - Selects previous option
Reset - Selects next setting
Signal Silence & Drill - Selects previous setting
Panel Silence - Saves program setting
FireShield Technical Reference Manual B.1
Programming templates
FSDACT programming worksheet
DACT setup
Access passcode
Load defaults
Edit passcode
Date
Time
DACT mode
(0 – 9, A – F) 1111111
Yes No
(0 – 9, A – F)
(MMDDYYYY) 01012002
(HHMM) 0000
Single line DACT Dual line DACT Modem/LCD
Receiver 1 (DACR1) Setup
Phone 1
Phone 2
Account
Format
Restores
Retry Count
(0 – 9, A – F) FFFF
Contact ID
Send Restores
(05 – 10) 05
EST 4/2
No Restores
Retry Time (05 – 10) 05
LCD only
Ex. 19415551212
Ex. 19415551212
Receiver 2 (DACR2) Setup
Phone 1
Phone 2
Account
Format
Restores
Retry Count
Retry Time
Contact ID
(0 – 9, A – F) FFFF
EST 4/2
Send Restores
(05 – 10) 05
(05 – 10) 05
No Restores
Ex. 19415551212
Ex. 19415551212
DACT Dialing Properties Setup
Tone/Pulse Line 1 Tone
Tone/Pulse Line 2 Tone
AC Fail Delay
Transmission Test Time
6 Hours
Transmission Test Freq.
Pulse
Pulse
15 Hours
(0000 – 2359) 0217
(00 – 02) 01
Rings to Answer
Ring Type
Callback Enable
Callback Number
(00 – 15) 05
Ring type
No
DACT answers any ring type after programmed ring count
Yes
Note: Default settings are shown in boldface type.
B.2
FireShield Technical Reference Manual
Programming templates
System event reporting setup
Event Where to report the event
Panel test
Panel abnormal test
Walk test
Drill
Reset
Program mode
DACT Disabled
Panel silence
Signal silence
Ground fault
Low battery
Missing battery
Internal comm trouble
AC fail
Charger trouble
Transformer 2 trouble
Aux power trouble
Peripheral trouble
DACT line 1 trouble
DACT line 2 trouble
DACT delivery trouble
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 1
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
System trouble restoral (4/2 code)
Zone settings - IDC 2
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
None
None
None
None
None
(0 – F) D
Zone settings - IDC 1
Note: For IDCs, program only those events that apply to the IDC zone type you specified on the “Panel programming worksheet.”
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Where to report the event
None CS 1
None
None
CS 1
CS 1
None
None
CS 1
CS 1
CS 2
CS 2
CS 2
CS 2
CS 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
4/2 event code
11
21
71
31
51
Where to report the event
CS 1
CS 1
CS 1
CS 1
CS 1
CS 2
CS 2
CS 2
CS 2
CS 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
4/2 event code
12
22
72
32
52
Zone settings - IDC 3
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Where to report the event
None CS 1
None
None
None
CS 1
CS 1
CS 1
None
CS 1
Note: Default settings are shown in boldface type.
CS 2
CS 2
CS 2
CS 2
CS 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
73
33
53
4/2 event code
13
23
4/2 event code
AA
69
6B
6A
AC
66
6C
6C
65
6D
68
6E
67
AB
C1
AE
CA
DF
6F
AF
AD
FireShield Technical Reference Manual B.3
Programming templates
Zone settings - IDC 4
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Zone settings - IDC 5
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Zone settings - IDC 6
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Zone settings - IDC 7
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Where to report the event
None
None
None
None
None
CS 1
CS 1
CS 1
CS 1
CS 1
Where to report the event
None CS 1
None
None
None
None
CS 1
CS 1
CS 1
CS 1
Where to report the event
None
None
CS 1
CS 1
None
None
None
CS 1
CS 1
CS 1
Where to report the event
None CS 1
None
None
CS 1
CS 1
None
None
CS 1
CS 1
Zone settings - IDC 8
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Where to report the event
None
None
CS 1
CS 1
None
None
None
CS 1
CS 1
CS 1
Zone settings - IDC 9
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Where to report the event
None
CS 1
None
None
CS 1
CS 1
None
None
CS 1
CS 1
Note: Default settings are shown in boldface type.
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
4/2 event code
14
24
74
34
54
4/2 event code
15
25
75
35
55
76
36
56
4/2 event code
16
26
4/2 event code
17
27
77
37
57
78
38
58
4/2 event code
18
28
4/2 event code
19
29
79
39
59
B.4
FireShield Technical Reference Manual
Zone settings - IDC 10
Event
Alarm activation
Waterflow activation
Trouble activation
Supervisory activation
Monitor activation
Where to report the event
None
None
None
None
None
CS 1
CS 1
CS 1
CS 1
CS 1
Zone restoral (4/2 code)
NAC settings - NAC 1
Event
Trouble activation
(0 – F) E
Where to report the event
None CS 1
NAC settings - NAC 2
Event
Trouble activation
Where to report the event
None
CS 1
NAC settings - NAC 3
Event
Trouble activation
Where to report the event
None CS 1
NAC settings - NAC 4
Event
Trouble activation
Where to report the event
None CS 1
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
CS 2
NAC Trouble restoral (4/2 code) (0 – F) D
Other FSDACT options
Note: These options can only be changed using the FireShield Configuration Utility.
Swinger shutdown (0 – 255) 000
Contact ID codes
Code Description Code
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
CS 1 & 2
Description
Programming templates
4/2 event code
1A
2A
7A
3A
5A
4/2 event code
61
4/2 event code
62
4/2 Event code
63
4/2 event code
64
Note: Default settings are shown in boldface type.
FireShield Technical Reference Manual B.5
Programming templates
Contact ID codes
Code Description Code Description
B.6
FireShield Technical Reference Manual
Appendix C
Jumper settings and wiring diagrams
Three-zone panel
D EGN
FireShield Technical Reference Manual C.1
Jumper settings and wiring diagrams
REMOTE MODULE AND
REMOTE RELAY WIRING [6]
C–
C+
24VDC+
24VDC–
POWER
ALARM
SUP
TBL
GND FLT
SILENCE
LMPTST
REMOTE
RELAY
MODULE
(RRM)
TYPICAL FOUR-WIRE
SMOKE DETECTOR CIRCUIT [2] [3] [7]
IDC1+
24VDC+
24VDC–
IDC1–
UL/ULC LISTED
EOL RELAY
(shown energized)
4.7 k
Ω
WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [8]
IDC1+
IDC1–
WF WF
1.1 k
Ω
SS SS
3.6 k
Ω
NOTES
1 All wiring is power-limited except for AC power and battery wiring. All wiring is supervised unless noted otherwise.
[2] Class A wiring not supported
[3] Listed EOLRs must be installed as shown for proper supervision
[4] For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k
(P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations
Ω
[5] Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state.
Keep power-limited wiring in the shaded area and nonpower-limited wiring in the unshaded area at all times.
[6] Requires continuous 24 Vdc from the AUX Power terminals or a power-limited UL/ULC listed compatible fire signaling power supply
[7] IDC circuits do not support alarm verification using fourwire smokes. Requires resettable 24 Vdc from AUX
Power terminals.
[8] Combination circuits consist of waterflow switches (WF) and their associated valve tampers (SS).
[9] Automatic and manually activated alarm initiating devices can be installed on the same IDC circuit regardless of circuit type except for combination circuits
(option 6, setting 5 and 6)
[10] Relay circuits can only be connected to power-limited sources
[11] Installation limits under jurisdiction of local authority
[12] Refer to the
FireShield Technical Reference Manual
(P/N 3100353) for the topic "Installing the FSDACT."
C.2
FireShield Technical Reference Manual
Five-zone panel
Jumper settings and wiring diagrams
D EGN
FireShield Technical Reference Manual C.3
Jumper settings and wiring diagrams
REMOTE MODULE AND
REMOTE RELAY WIRING [6]
C–
C+
24VDC+
24VDC–
POWER
ALARM
SUP
TBL
GND FLT
SILENCE
LMPTST
REMOTE
RELAY
MODULE
(RRM)
TYPICAL FOUR-WIRE
SMOKE DETECTOR CIRCUIT [2] [3] [7]
IDC1+
24VDC+
24VDC–
IDC1–
UL/ULC LISTED
EOL RELAY
(shown energized)
4.7 k
Ω
WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [8]
IDC1+
IDC1–
WF WF
1.1 k
Ω
SS SS
3.6 k
Ω
NOTES
1 All wiring is power-limited except for AC power and battery wiring. All wiring is supervised unless noted otherwise.
[2] Class A wiring not supported
[3] Listed EOLRs must be installed as shown for proper supervision
[4] For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k
(P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations
Ω
[5] Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state.
Keep power-limited wiring in the shaded area and nonpower-limited wiring in the unshaded area at all times.
[6] Requires continuous 24 Vdc from the AUX Power terminals or a power-limited UL/ULC listed compatible fire signaling power supply
[7] IDC circuits do not support alarm verification using fourwire smokes. Requires resettable 24 Vdc from AUX
Power terminals.
[8] Combination circuits consist of waterflow switches (WF) and their associated valve tampers (SS).
[9] Automatic and manually activated alarm initiating devices can be installed on the same IDC circuit regardless of circuit type except for combination circuits
(option 6, setting 5 and 6)
[10] Relay circuits can only be connected to power-limited sources
[11] Installation limits under jurisdiction of local authority
[12] Refer to the
FireShield Technical Reference Manual
(P/N 3100353) for the topic "Installing the FSDACT."
C.4
FireShield Technical Reference Manual
Ten-zone panel
Jumper settings and wiring diagrams
FireShield Technical Reference Manual C.5
Jumper settings and wiring diagrams
REMOTE MODULE AND REMOTE RELAY WIRING [6]
C–
C+
24VDC+
24VDC–
POWER
ALARM
SUP
TBL
GND FLT
SILENCE
LMPTST
REMOTE
RELAY
MODULE
(RRM)
IDC1+
24VDC+
24VDC–
IDC1–
IDC2+
IDC2–
TYPICAL FOUR-WIRE
SMOKE DETECTOR CIRCUIT [2] [3] [7]
UL/ULC LISTED
EOL RELAY
(shown energized)
4.7 k
Ω
WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [10]
(Only Class B allowed)
1.1 k
Ω 3.6 k
Ω
IDC1+
IDC1–
WF WF SS SS
NOTES
1.
All wiring is power-limited except for AC power and battery wiring. All wiring is supervised unless otherwise noted.
[2] Dashed lines show Class A wiring
[3] Listed EOLRs must be installed as shown for proper supervision. EOLRs are not required for Class A operation.
[4] For UL installations use EOLR P/N EOL3.6-1.1 which includes
Ω Ω resistor. For ULC installations use EOL-P1 and select the 1.1
[5] Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state.
[6] Requires continuous 24 Vdc from the AUX Power terminals or a power-limited UL/ULC listed compatible fire signaling power supply
[7] IDC circuits do not support alarm verification using four-wire smokes. Requires resettable 24 Vdc from
AUX Power terminals.
[8] 5.0 A total with optional transformer (P/N XTR3A120 or XTR3A230
[9] Automatic and manually activated alarm initiating devices can be installed on the same IDC circuit regardless of circuit type except for combination circuits (option 6, setting 5 and 6)
[10] Combination circuits consist of waterflow switches
(WF) and their associated valve tampers (SS)
[11] Relay circuits can only be connected to power-limited sources
[12] Installation limits under jurisdiction of local authority
[13] Refer to the
FireShield Technical Reference Manual
(P/N 3100353) for the topic "Installing the FSDACT."
C.6
FireShield Technical Reference Manual
Appendix D
Panel specifications
Initiating device circuits (IDCs)
Notification appliance circuits (NACs)
Power supply
NAC voltage rating
Maximum NAC current
Environmental
Terminal rating
Serial communications
Class B
Class A
Class B
Class A
AC input
120 Vac 60 Hz
230 Vac 50/60 Hz
Base panel current draw (standby)
Base panel current draw (alarm)
Battery placement
Maximum auxiliary current
Auxiliary output
IDC max. detector standby current
IDC circuit
IDC operating voltage
Compatibility ID
Alarm contact
Trouble contact
Supervisory contact
Batteries
FS302 three-zone panel
3
FS502 five-zone panel FS1004 ten-zone panel
5 3 1 10 8 6 4 2 0
0
2
0
2
1
0
2 0
4
1 2
2
3 4
0
5
0
2.0 amps total
1.5 amps each
1.5 amps total
0.8 amps
0.4 amps
0
0.8 amps
0.4 amps
1
3.0 amps total
24 Vfwr
1.5 amps each
2.5 amps total
0 1 2
3.0 amps (expandable to 5.5 amps)
1.5 amps each - 2.5 amps total for
NAC1 + NAC2 or NAC3 + NAC4
5.0 amps with optional expander transformer
1.6 amps - incl. optional exp. transformer
0.8 - incl. optional exp. transformer
110 mA
145 mA
120 mA
170 mA
Up to two 7 Ah batteries will fit in the panel.
Note: If batteries greater than 7 Ah are required, you must use the BC-2 battery cabinet. Refer to installation sheet P/N 3100027.
0.5 amps (may be programmed as resetable)
19 to 25.7 Vdc
145 mA
250 mA
Up to two 18 Ah batteries will fit in the panel.
1.5 mA (See FireShield UL and ULC Compatibility List (P/N 3100468) for maximum quantity of detectors per circuit.)
Maximum loop resistance: 13
Ω
Maximum loop capacitance: 0.03
µ
F
16.3 to 25.7 Vdc
100
Form A N.O. 30 Vdc @ 1 A (resistive load)
Form C 30 Vdc @ 1 A (resistive load)
Form A N.O. 30 Vdc @ 1 A (resistive load)
Temperature: 0 to 49 °C (32 to 120 °F)
Humidity: 5 to 93% RH, noncondensing
All terminals rated for 12 to18 AWG (0.75 to 2.5 sq mm)
Asynchronous communications maximum resistance: 13
Ω
Maximum capacitance: 0.03
µ
F
Batteries must be sealed lead acid type only. Maximum charging capacity = 18 Ah.
FireShield Technical Reference Manual D.1
Panel specifications
D.2
FireShield Technical Reference Manual
Appendix E
Default event codes
Default Contact ID event codes
Code Description
Fire alarm – general
11000001
11000002
11000003
11000004
11000005
11000006
11000007
11000008
11000009
Fire IDC 1
Fire IDC 2
Fire IDC 3
Fire IDC 4
Fire IDC 5
Fire IDC 6
Fire IDC 7
Fire IDC 8
Fire IDC 9
11000010 Fire IDC10
Fire alarm – waterflow (sprinkler)
11300001
11300002
11300003
11300004
11300005
11300006
11300007
11300008
11300009
11300010
Fire alarm – bypass
Waterflow IDC 1
Waterflow IDC 2
Waterflow IDC 3
Waterflow IDC 4
Waterflow IDC 5
Waterflow IDC 6
Waterflow IDC 7
Waterflow IDC 8
Waterflow IDC 9
Waterflow IDC 10
57000001
57000002
57000003
57000004
57000005
57000006
57000007
57000008
57000009
57000010
Supervisory – general
20000001
20000002
20000003
20000004
20000005
20000006
20000007
20000008
20000009
20000010
Fire bypass IDC 1
Fire bypass IDC 2
Fire bypass IDC 3
Fire bypass IDC 4
Fire bypass IDC 5
Fire bypass IDC 6
Fire bypass IDC 7
Fire bypass IDC 8
Fire bypass IDC 9
Fire bypass IDC 10
Fire supervisory IDC 1
Fire supervisory IDC 2
Fire supervisory IDC 3
Fire supervisory IDC 4
Fire supervisory IDC 5
Fire supervisory IDC 6
Fire supervisory IDC 7
Fire supervisory IDC 8
Fire supervisory IDC 9
Fire supervisory IDC 10
FireShield Technical Reference Manual
32000001
32000002
32000003
32000004
NAC – bypass
52000001
52000002
52000003
52000004
System events
33000000
35100000
35200000
35400000
53000000
55100000
60100000
60200000
60700000
60800000
62700000
62800000
30100000
30100000
30200000
30500000
30800000
30900000
31000000
31100000
31200000
31500000
32800000
Trouble – zone
37300001
37300002
37300003
37300004
37300005
37300006
Fire trouble (380 Sensor trouble) IDC 1
Fire trouble (380 Sensor trouble) IDC 2
Fire trouble (380 Sensor trouble) IDC 3
Fire trouble (380 Sensor trouble) IDC 4
Fire trouble (380 Sensor trouble) IDC 5
Fire trouble (380 Sensor trouble) IDC 6
37300007
37300008
37300009
37300010
Fire trouble (380 Sensor trouble) IDC 7
Fire trouble (380 Sensor trouble) IDC 8
Fire trouble (380 Sensor trouble) IDC 9
Fire trouble (380 Sensor trouble) IDC 10
Monitor point/zone – active
14000001
14000002
14000003
14000004
14000005
14000006
14000007
14000008
14000009
14000010
NAC – trouble
General alarm IDC 1
General alarm IDC 2
General alarm IDC 3
General alarm IDC 4
General alarm IDC 5
General alarm IDC 6
General alarm IDC 7
General alarm IDC 8
General alarm IDC 9
General alarm IDC 10
Trouble NAC 1
Trouble NAC 2
Trouble NAC 3
Trouble NAC 4
Bypass NAC 1
Bypass NAC 2
Bypass NAC 3
Bypass NAC 4
AC failure
Transformer 2 trouble
Battery bad
Reset
Internal communications fault
Charger trouble
Ground fault
Battery missing
Auxiliary power trouble
Panel silence
Signal silence
Peripheral trouble
DACT line 1 trouble
DACT line 2 trouble
DACT delivery trouble
RRM bypass
DACT disabled
Drill
Panel test
Walk test
Panel abnormal test
Program mode entry
Program mode exit
E.1
Default event codes
Default (4/2) event codes
DB
DC
DD
DE
DF
E<N>
E<N>
B5
BB
BC
BD
BE
BF
C1
D6
D7
D8
D9
DA
C2
CA
D<N:1-4>
D5
6C
6D
6E
6F
7<N>
8<N>
9<N>
A<N:1-4>
A5
AA
AB
AC
AD
AE
AF
B<N:1-4>
Code
1<N>
2<N>
3<N>
4
5<N>
68
69
6A
6B
6<N:1-4>
65
66
67
Description
Fire alarm activation events
Waterflow alarm activation events
Supervisory signal activation events
Not used
Monitor signal activation events
NAC trouble activation events
Aux power trouble activation
Ground fault activation
DACT delivery trouble
DACT line 1fail
AC loss
Transformer 2 trouble
Charger trouble
Battery missing/Battery bad
FSRSI, FSRZI, FSRRM trouble
DACT line 2 fail
DACT abnormal test
IDC trouble activation
IDC disabled (not configurable)
IDC enabled (not configurable)
NAC disabled (not configurable)
FSRRM outputs disabled (not configurable)
Internal communication trouble
Panel reset
Signal silence activated
Drill activated
DACT disabled
Walk test activated
NAC enabled (not configurable)
FSRRM outputs enabled (not configurable)
Panel reset restore (not configurable)
Signal silence ended (not configurable)
Drill ended (not configurable)
DACT enabled (not configurable)
Walk test ended (not configurable)
Program mode entry
Program mode exit (not configurable)
Panel silence activated
NAC trouble restoration
Aux power trouble restoration
Ground fault restoration
DACT delivery trouble restore
DACT line 1 restoration
AC loss restoration
Transformer 2 restoration
Charger trouble restoration
Battery missing/Battery bad restore
FSRSI, FSRZI, FSRRM restoration
DACT line 2 restoration
DACT normal test
Fire alarm restoration
Waterflow alarm restoration
E.2
Code
E<N>
E<N>
Description
Supervisory restoration
Monitor restoration
F<N> IDC trouble restoration
Note: N is the circuit number.
FireShield Technical Reference Manual
Z
Index
4
4/2 event codes • E.2
A
alarm
IDC zone type • 3.4
LED • 1.2
resounding an alarm condition • 1.4
signal silenced LED • 1.2
annunciator trouble LED • 1.2
auto NAC silence timer description • 3.3
operation • 1.4
programming • 3.3
aux power reset description • 3.4
programming • 3.4
auxiliary power supply installing • 2.12
B
battery calculation • A.1
battery trouble LED • 1.2
binary numbers
LEDs • 3.1
buttons disable IDC • 1.2
disable NAC • 1.2
operating mode • 1.1
programming mode • 1.1, 3.1
buzzer
FSRSI • 2.2
silencing FSRSI buzzer • 1.4
silencing panel buzzer • 1.4
C
cabinet dimensions • 2.1
installing • 2.1
MFC-A • 2.6
semi-flush mount • 2.1
surface mount • 2.1
calculations battery • A.1
NAC maximum wire length • A.4
NAC voltage drop • A.3
checklist installation checklist • 2.1
class A programming • 3.5, 3.6
wiring • C.1, C.3, C.5
class B programming • 3.5, 3.6
wiring • C.1, C.3, C.5
command options
FSRRM • 2.5
component descriptions • 1.3
contact ID codes • E.1
CTM description • 2.11
installing • 2.11
wiring • 2.11
FireShield Technical Reference Manual
D
default event codes
FSDACT • E.1
defaults factory defaults • 3.2
reloading the factory defaults • 3.2
disable
IDC • 1.2, 1.5
LED • 1.2
NAC • 1.2, 1.5
disabled events • 3.15
drill drill button • 1.2
using the drill command • 1.5
E
enable re-enable IDC or NAC • 1.5
enclosure • See cabinet event notification programming
FSDACT • 3.14
F
find peripherals description • 3.3
programming • 3.3
FireShield Configuration Utility • 3.1
FSCU • 3.1
FSDACT • 1.3
4/2 event codes • E.2
changing password • 3.9
contact ID • E.1
default event codes • E.1
description • 2.8
digit descriptions • 3.8
display • 3.1
editing programed information • 3.17
event notification programming • 3.14
getting started (programming) • 3.8
installing • 2.8
panel programming • 3.2
password • 3.9
programming • 3.7, 3.8, 3.9
programming buttons • 3.8
FSRPM description • 2.10
installing • 2.10
wiring • 2.10
FSRRM command options • 2.5
description • 2.5
installation instructions • 2.6
jumper setup • 2.5
MFC-A • 2.6
service and troubleshooting • 2.6
specifications • 2.5
wiring • 2.6
FSRSI buzzer • 1.4, 2.2
description • 2.2
installation instructions • 2.2
jumper setup • 2.2
lamp test • 1.6
Z.1
Index
LEDs • 2.2
specifications • 2.2
wiring • 2.3
FSRZI-A description • 2.3
installation instructions • 2.4
jumper setup • 2.4
lamp test • 1.6
LEDs • 2.3
specifications • 2.3
wiring • 2.4
G
ground and open tests • 4.1
ground fault LED • 1.2
I
IDC alarm LED • 1.2
disable • 1.5
disable button • 1.2
programming class A or class B • 3.5
programming zone types • 3.4
re-enabling • 1.5
supervisory/monitor LED • 1.2
IDC disabled event • 3.15
IDC trouble LED • 1.2
initiating device circuit • See IDC inputs
IDC zone types • 3.4
installation checklist • 2.1
installing auxiliary power supply • 2.12
cabinet • 2.1
CTM • 2.11
FSDACT • 2.8
FSRPM • 2.10
FSRRM • 2.5
FSRSI • 2.2
FSRZI-A • 2.3
metal dead front • 2.12
power expander transformer • 2.7
J
jumper
10-zone panel settings • C.5
3-zone panel settings • C.1
5-zone panel settings • C.3
FSRRM • 2.5
FSRSI • 2.2
FSRZI-A • 2.4
program jumper • 1.3, C.1, C.3, C.5
L
lamp test • 1.1
conducting a panel lamp test • 1.6
conducting an FSRSI and FSRZI-A lamp test • 1.6
LEDs binary number value • 3.1
FSRSI • 2.2
FSRZI-A • 2.3
programming • 3.1
system • 1.2
load defaults description • 3.3, 3.9
programming • 3.3, 3.9
Z.2
M
maintenance • 4.1
metal dead front installing • 2.12
MFC-A
FSRRM • 2.6
monitor
IDC zone type • 3.4
LED • 1.2
N
NAC disable • 1.5
disable button • 1.2
maximum wire length • A.4
programming class A or class B • 3.6
programming outputs • 3.6
programming silence inhibit timer • 3.4
programming silenceable • 3.6
re-enabling • 1.5
silencing • 1.4
trouble LED • 1.2
voltage drop calculation • A.3
NAC disabled event • 3.15
notification appliance circuit • See NAC
O
open and ground tests • 4.1
operation operating the panel • 1.4
overview • 1.1
outputs
NAC outputs • 3.6
overview operation • 1.1
system • 1.1
P
panel silencing buzzer • 1.4
panel silence button operating mode • 1.2
programming mode • 3.1
password changing FSDACT • 3.9
FSDACT • 3.9
power expander transformer • 1.3
description • 2.7
installation instructions • 2.7
specifications • 2.7
wiring • 2.7
power LED • 1.2
program jumper • 1.3, C.1, C.3, C.5
program mode exiting • 3.2
programming auto NAC silence timer • 3.3
aux power reset • 3.4
buttons • 3.1
find peripherals • 3.3
FSCU • 3.1
FSDACT • 3.8, 3.9
IDC class • 3.5
IDC zone types • 3.4
installing jumper • 3.2
load defaults • 3.3, 3.9
NAC class • 3.6
FireShield Technical Reference Manual
NAC output • 3.6
NAC silence inhibit timer • 3.4
NAC silenceable • 3.6
options • 3.2
overview • 3.1
templates • B.1
programming methods • 3.1
R
remote disconnect button operating mode • 1.1
programming mode • 1.1, 3.1
remote relay module • See FSRRM remote system indicator • See FSRSI remote zone indicator • See FSRZI-A reset button operating mode • 1.2
programming mode • 1.2, 3.1
resetting the panel • 1.4
S
semi-flush mount cabinet • 2.1
service and troubleshooting
FSRRM • 2.6
signal silence & drill button alarm mode • 1.2
normal mode • 1.2
programming mode • 1.2, 3.1
silencing
FSRSI buzzer • 1.4
notification appliances • 1.4
panel buzzer • 1.4
specifications
FSRRM • 2.5
FSRSI • 2.2
FSRZI-A • 2.3
panel • D.1
power expander transformer • 2.7
supervisory
IDC zone type • 3.4
LED • 1.2
surface mount cabinet • 2.1
T
tie wrap mounts • 1.3
trouble LED • 1.2
trouble silence button programming mode • 1.2
U
ULC tests • 4.1
W
walk test audible • 1.6
LED • 1.2
overview • 1.5
silent • 1.6
using the walk test command • 1.5
walk test button operating mode • 1.1
programming mode • 1.1, 3.1
waterflow
IDC zone type • 3.4
wiring
10-zone panel • C.5
3-zone panel • C.1
5-zone panel • C.3
class A • C.1, C.3, C.5
class B • C.1, C.3, C.5
CTM • 2.11
FSRPM • 2.10
FSRRM • 2.6
FSRSI • 2.3
FSRZI-A • 2.4
NAC maximum wire length • A.4
power expander transformer • 2.7
Index
FireShield Technical Reference Manual Z.3
Index
Z.4
FireShield Technical Reference Manual
Frame these instructions and mount on the wall next to the control panel.
For additional information, refer to the FireShield
Technical Reference Manual P/N 3100353.
RESPONDING TO ALARM SIGNALS
1. Evacuate the area.
2. Notify the proper authorities immediately and state the nature and location of the emergency.
3. Be prepared to provide directions to firefighters when they arrive.
TO SILENCE ALARM NOTIFICATION SIGNALS
WARNING! Alarm notification signals should not be silenced until after all occupants have been evacuated.
1. Press Signal Silence & Drill.
The Signal Silenced LED turns on and all audible notification circuits turn off. New alarm events turn the notification circuits back on.
Note: Panel programming may delay alarm silence for up to one minute, may prevent alarm silencing when water flows through the sprinkler system, and may not turn off visible notification circuits.
TO RETURN THE SYSTEM TO NORMAL AFTER AN
ALARM OR SUPERVISORY EVENT
1. Make sure all smoke detectors are free from smoke and all manual pull stations are reset.
2. Press Reset.
Note: Panel programming may delay panel reset for up to one minute after alarm notification circuits turn on.
TO INITIATE A FIRE DRILL
1. Press Signal Silence & Drill.
All audible notification circuits turn on. This function will not automatically notify the fire department.
TO PERFORM A LAMP TEST (panel and remote annunciators)
1.
Press and hold the Remote Disconnect and Walk
Test buttons simultaneously.
TO PERFORM A REMOTE ANNUNCIATOR LAMP
TEST
1.
2.
Press and hold the Silence button on the RSI for five seconds.
LEDs on remote annunciators will remain on until silence button is released.
RESPONDING TO TROUBLE SIGNALS
1. Silence the panel buzzer.
2. Investigate the cause of the trouble and notify the authorized service personnel immediately.
FireShield Fire Alarm Control Panel
Operating Instructions
TO SILENCE THE PANEL BUZZER
1. Press Panel Silence.
The buzzer turns off. Any new events turn the buzzer back on. Trouble conditions not cleared resound the buzzer after a predetermined time.
WARNING! Trouble conditions may affect the panel's ability to provide early detection and indication of a fire.
Clear trouble conditions immediately.
RESPONDING TO SUPERVISORY SIGNALS
1. Silence the panel buzzer.
2. Investigate the cause of the supervisory signal and notify the authorized service personnel immediately.
RESPONDING TO MONITOR SIGNALS
1. Silence the panel buzzer.
2. Investigate the cause of the monitor signal and notify the authorized service personnel immediately.
PERIODIC TEST RECOMMENDATIONS
See “Maintenance,” in the FireShield Technical
Reference Manual for test instructions and references.
Installed by
Name:
Company:
Address:
Phone:
Per NFPA 72
Protected Premises Fire Alarm System, Local
Auxiliary Fire Alarm System
Remote Supervising Station Fire Alarm System
Central Station
Date:
For service contact
Company:
Address:
Phone:
Acceptance Inspection by
Date:
Operating Instruction Placard
FireShield - Fire Alarm Control Panel
P/N: 3100470 REV: 2.0
1 / 1
advertisement
Key Features
- 10 initiating device circuits (IDCs)
- 4 notification appliance circuits (NACs)
- Built-in DACT (Dialer)/Modem (FSDACT)
- Optional Remote System Indicator (FSRSI)
- Optional Remote Zone Indicator (FSRZI-A)