Uninterruptible Power Supply

from 350VA to 800kVA

THE SCIENCE OF CONTINUITY

The Company

AROS, a history of research and continuity.

Continuous operation is the key word for AROS. It is the company’s field of activity, a sophisticated technology upon which the efficiency of every electrical system depends. AROS has over 70 years of experience in this highly specialized sector and is currently a leading company in the field.

But continuity is also AROS

“trademark” as acknowledged by design and installation engineers: the will to strive constantly to achieve the highest production standards and to anticipate market demands. Thinking in this way brought AROS to set up the

Research and Development team of about forty persons to better respond to the market requirements. The result is that today whoever thinks about emergency power supplies thinks

AROS.

AROS was set up in 1935 and after just a few years established itself as the leading Italian manufacturer of voltage regulators, transformers and power supplies. In the fifties

AROS was the first company in

Italy to manufacture ballasts for fluorescent neon lamps and became the Italian leader in the field of components for lighting.

In the eighties it designed, developed and produced switching power supplies for

IBM computers. The company thus acquired know-how in

PWM (Pulse-Width- Modulation) technology that enabled it to enter the UPS sector. This is now the most important field of activity for AROS, which has maintained its leadership in voltage regulators and components.

Steps to success

1935 Manufacture of radio loudspeakers

1940 Production of transformers for radios and electrical power supplies

1945 Entry on the market of the first power supplies (ballasts) for fluorescent neon lamps

1950-1959 Manufacture of magnetic reactors for fluorescent and discharge lamps

1960-1969 First suppliers of components for IBM

Manufacture of ferro-resonant regulators

1970-1979 Production of electronic components for regulators

1980-1989 Manufacture of uninterruptible power supplies (UPS), switching power supplies and electronic reactors

1990-1999 Expansion of the range of UPS for various applications (IT, industrial)

2000-2008 Growth and consolidation in the Worldwide UPS market

Entering the Research and Development department is like entering the heart of AROS.

Here users’ real problems are "filtered" by means of the latest technologies and transformed into successful products.

Research

Highly trained personnel and state of the art technologies lie behind every project.

Entering the Research and

Development department means entering the heart of AROS. Here users’ real problems are “filtered” by means of the latest technologies and transformed into successful products. Environmental simulators, sophisticated analysis tools, CAD systems: super specialized devices for super specialized design engineers to predict tomorrow’s needs today, needs arising from developments in electronics and market trends. AROS dedicates its greatest resources to this team and has recently boosted the power area. This both consolidates the strength of its core business of

Uninterruptible Power Supplies

(UPS), components and voltage regulators, while mapping out its future course.

To understand the work carried out by the research team, just think of the technological

“nodes” that are hidden behind the apparent functional linearity of a UPS system. To provide a high level of efficiency, withstand strong line interference, interact with surrounding systems that may not be homogeneous, comply with complex international safety standards, minimize the level of interference emitted towards the mains and towards the environment and finally, offer a degree of reliability that is increasingly demanded by new electronic systems.

AROS products are intended for sophisticated devices

- delicate electronic systems needing protection - and sophisticated devices are required to design, develop and produce them.

New technology

Intelligent devices.

Intelligent men.

AROS products are intended for sophisticated devices - delicate electronic systems needing protection - and sophisticated devices are required to design, develop and produce them. AROS

Research Centre is at the cutting edge when it comes to the synthesis and analysis of cooling systems through the use of software for thermal analysis based on computational fluid dynamics and infrared cameras. This is just one example of how AROS engineers and technicians use state of the art computer-aided technologies to make AROS solutions increasingly competitive, not only in terms of performance and respect for the environment, but also as regards reducing operational costs.

AROS uses thermal analysis to study how the cooling properties inside a device change by modifying parameters such as the size and footprint of heat dissipators, the type and position of the fans, deflectors and ventilation grids, and by eliminating the critical areas

(caused by the recirculation or stagnation of air at high temperatures within the UPS).

All this to achieve uniform ventilation, significantly increasing the safety and performance of the system while retaining its compact size.

Quality not only as an objective but also as an indispensable condition for every product: this is AROS.

Quality

Millions of users believe in AROS because AROS believes in excellence.

Quality not only as an objective but also as an indispensable condition for every product: this is the creed that AROS abides by and which is centred around the certification of its quality system. AROS is certified

UNI EN ISO 9001:2000 for the design and development, manufacture, sales and after-sales service of its products. This certification guarantees stringent and constant control of its corporate processes. The result is not just higher product quality and reliability but also a philosophy focused on understanding customers’ present and future requirements, complying with their requests and aiming to exceed their expectations.

With so much trade taking place across borders, conformity assessment has become an important component of the world economy.

Before they are put on the market, all AROS products are subjected to testing for conformance with specifications complying with ISO 9001:2000 standards.

For AROS, a product is not technologically complete unless it

“incorporates” a level of support that resolves users’ problems.

Service

The service rendered to customers every day makes AROS a partner.

For AROS, a product is not technologically complete unless it

“incorporates” a level of support that resolves users’ problems. High resolution capacity, low intervention times: this formula has been one of the keys to its success on the domestic and worldwide markets.

A formula that finds concrete application in services such as

PowerNetGuard, the remote support service that remotely manages and controls the UPS 24 hours a day. Choosing AROS means being able to connect online with the Control centre, being informed in real time on the status of the UPS and obtaining immediate action in emergencies. AROS combines this advanced service for its users with training activities for technical and commercial operators, on its own premises or at the customer’s site.

With a highly trained team,

UPService provides a reliable and technical support and aftersales service.

The purpose of our ATI personnel is to give advice on the relevant standards affecting AROS UPS, installations, batteries and applications.

Technical information

AROS Technical Information (ATI)

AROS offers the on-line pre-sales support to distributors, installers, consultants and end customers providing information on:

• Standard products - giving detailed technical specifications and helping its customer to choose the right configuration using the Aros software package;

• Applications - providing assistance in choosing the right products;

• Customer solutions - supplying non standard products designed to match the customer specifications;

• Batteries - guiding the users to choose the right battery type and configuration;

• Installations - furnishing detailed drawings and solving any doubt about the installation;

• Standards - offering consultancy on standards applicable to its product range;

• Training - organizing sales training and products presentations to distributors or end customers.

ATI information is provided in form of technical specifications, installation manuals and software packages for UPS sizing.

Index

Uninterruptible

Power Supplies (UPS)

Frequency converter

Stabilisers

Accessories

CSS

Power problems

Technical standards

Types of Uninterruptible Power Supply (UPS)

Evaluation parameters

Power quality and mains disturbance

UPS range summary

UPS options

UPS range summary: RACK version

Options for UPS RACK version

Rapido

Alfa / Alfa Plus

Pc Planet

Syncro

Spring

Spring Rack

Sentinel 6

Sentinel 6 Rack

Sentinel XR

Sentinel 5 Plus

Flexus

Sentry Multistandard

Sentry HPS

Sentry MPS – Three Phase Output

Sentry MPS – Single Phase Output

Sentry MPS 400 Hz Frequency Converter

Voltronic 4 single-phase

Voltronic 4 three-phase

ELC Line Conditioners

RQ

Tristab-T

Tristab-Y

Software and accessories for total reliability in controls and communication

IRMS (Intelligent Redundant Multi-Switch)

CSS Configurations

Standby Power Systems p. 86 p. 88 p. 90 p. 92 p. 94 p. 96 p. 98 p. 106 p. 108

13 p. 34 p. 36 p. 38 p. 40 p. 42 p. 48 p. 52 p. 60 p. 66 p. 72 p. 80 p. 14 p. 15 p. 16 p. 18 p. 19 p. 20 p. 22 p. 24 p. 25 p. 26 p. 28 p. 30 p. 32 p. 82

Power problems

BLACKOUT,

VOLTAGE DISTURBANCES

Why an Uninterruptible Power Supply?

Data centres, servers, LAN nodes and telecommunication systems must always be protected against possible problems in the power supply. Sudden blackouts and variations in the mains supply may lead to system malfunctions and severe data losses. But even other electrical equipment can cause damage or inconvenience if there is a breakdown in the mains. Just think of the check-out systems in a supermarket, lighting systems and industrial production units, not to mention safety systems, pumping systems and automatic devices in general.

Blackout, voltage disturbances 45%

Other 55%

Power problems are caused by various sources such as distribution network faults, system switching, weather and environmental conditions, heavy equipment or simply just faulty maintenance.

The simplest and most effective way of coping with these disturbances is to install a UPS unit (UPS stands for Uninterruptible

Power Supply). Acting as an interface between the mains and the loads, the UPS guarantees the continuity and the quality of the electrical power supplied to the loads, whatever the condition of the mains may be. In fact these systems stabilise the voltage perfectly, eliminating all disturbances.

They even supply voltage when the mains fails, by means of a series of batteries which give a back up time that is generally sufficient to guarantee the safety of persons and of the system.

In order to decide which type of appliance is able to guarantee the best level of protection, you must know the types of mains problems that can disturb your systems.

TYPE OF MAINS DISTURBANCES

Undervoltage 85%

Peaks 8%

Blackout 6%

Overvoltage 1%

Peaks

+15%

Nominal voltage

-15%

0 V

Undervoltage

Overvoltage

Blackout

14

CEI, CENELEC and IEC are the recognized standardization bodies respectively at national,

European and international level. Such standardization guarantees the compliance with CE Directives.

Technical Standards

Safety

EN 62040-1-1 is the reference standards regulating the basic safety requirements for UPS used in operator access areas.

EN 62040-1-2 is the reference standards regulating general and safety requirements for UPS used in restricted access locations.

Electromagnetic Compatibility

This is the capacity of equipment to work without being disturbed

(immunity) and without disturbing (emission) other equipment due to electromagnetic disturbances on electric wires and irradiated.

EN 50091-2 and IEC 62040-2 are the reference standards which also defines the testing procedures.

Performances

The reference document is the Performance Requirements

EN 62040-3. It is a guide for a better understanding between manufacturer and user since it defines which performance must be declared as well as the relevant testing methods.

All AROS UPS’s have been designed and built in accordance with all the above standards and therefore bear the mark.

15

Types of Uninterruptible Power Supply

(UPS)

On-Line Uninterruptible

Power Supply (VFI)

On this type of UPS, also known as a double conversion UPS, the inverter draws its power continuously from the rectifier (converter). The current is completely regenerated by its transformation from AC to DC and back to AC, guaranteeing a constant level of quality, regardless of disturbance on the mains power source.

By carrying out continuous double conversion, an On-Line UPS significantly attenuates electrical noise, which might otherwise damage a computer. When the AC input supply is not within the voltage and frequency tolerances, the battery is used to power the inverter. The inverter continually supplies the critical load with a true sinewave current.

If a converter/inverter failure occurs, the continuity of the load power can be improved by activating the bypass source using a transfer switch.

Static switch

Bypass

A.C. input

Rectifier Inverter

A.C. input normal mode

Battery battery mode

A.C. output by pass mode

16

Types of Uninterruptible Power Supply

(UPS)

Line Interactive

Uninterruptible

Power Supply (VI)

On this type of UPS the inverter is connected in parallel to the AC input and also charges the battery (interactive operation in reversible mode).

When the AC input supply is not within strict amplitude and frequency tolerances, the load is powered by the inverter through the battery.

The normal inverter output waveform is a stepwave or squarewave.

This technique is rarely used for high power ratings as frequency regulation is not possible. Active Standby (or Line

Interactive) technology is a recent development made possible by the advent of microprocessors. The UPS is fully controlled by a microprocessor which monitors the quality of the mains power supply and reacts to any variations. In the event of a power problem, the UPS transfers the load to the batteries to supply stabilised power.

It is increasingly frequent to add a voltage compensation circuit, called a

“booster”, that is enabled in the event of prolonged voltage drops.

Passive Standby

Uninterruptible

Power Supply

(Off-line) (VFD)

This type of UPS, also called Off-line

UPS, is connected in parallel to the normal AC source. The current is filtered in order to attenuate the most frequent forms of disturbance. In the event of a power problem the UPS transfers the load to the batteries to supply stabilised power: the inverter only switches on when the mains fails or fluctuates outside the input voltage tolerances of the EMI filter or if it is fitted with

Automatic Voltage Stabiliser (AVS).

Static switch

Bypass

A.C. input

A.C. input

Automatic Voltage Regulator

AVR

Inverter normal mode

Battery battery mode

Bypass

A.C. input

Static switch

Battery charger

Inverter

A.C. input normal mode

Battery battery mode

A.C. output by pass mode

A.C. output

17

Evaluation parameters

Apparent power (in VA or kVA)

It is defined as:

P

APP

=V

X

I

for single-phase load

P

APP

= V x I x √

3

for three-phase loads where V is the load voltage supply and I is the current absorbed by the load in normal load conditions.

This information is normally shown on documents and/or load nameplates though it may be shown as an oversized value.

Active power (in W or kW)

It is defined as: kW = kVA x cos ϕ

(where cos ϕ means power factor PF).

The cos ϕ value of loads is very seldom indicated, therefore a correct

UPS sizing requires measurements of kVA absorbed by loads.

Experience, anyway, shows that typical loads of computer feature a

PF between 0,65 and 0,8.

Considerations on the misleading concept of

“computer power”

In the definition of the UPS rated power, the parameter values, defined as “computer power”, “switching power”, “actual power”, power a particular temperature value, etc. are sometimes indicated.

Such arbitrary parameter values have no relation with apparent power and active power; they can be neither quantified nor defined and therefore must not be used for the correct sizing of the UPS.

Crest Factor

A linear load absorbs a sinewave current that shows an effective value

(I

EFF usually measured and declared) and a peak value (I

PK

). The Crest

Factor value is defined as:

CF =

I

I

PK

EFF

The nominal value for a linear load is

CF = 1,41. Most loads applied to

UPS’s are non- linear load: they absorb distorted current with a CF value greater than 1,41 and require therefore higher peak currents thus resulting in an increased distortion of the output voltage than equivalent linear loads. Directive EN62040-3, indicates a typical non-linear load as

CF=3, used for UPS testing, which may be used in the absence of other data.

Overload

Overloads are temporary requests from electrical equipment which exceed regular operation absorption.

They are caused by current peaks which may occur when one or more users are switched on. In case the overload exceeds the admissible limits the UPS guarantees the energy supply via the automatic bypass line.

For “On line” UPS’s the transfer is effected without any break in power

(transfer time = 0 ms). The “bypass” is a safety device with independent protection and auxiliary supply able to supply the load independently from the UPS also when the UPS is switched off or broken.

Input current harmonics

The UPS battery charger rectifier absorbs a distorted current containing harmonics that are multiples to the reference 50Hz frequency. These harmonics may cause voltage distortion which may affect the normal operation of non privileged user’s.

The harmonics level of AROS UPS's complies with the present directive.

Howerver, in order to further reduce the presence of these harmonics variuos solutions are available such as the installation of Active Filetrs (Power

Factor Controlled) or different Rectifier designs.

Runtime

The batteries supplied with the UPS’s are valve regulated batteries (VRLA) known as sealed batteries with no electrolyte top-up, very low gas emission, suitable for installations in offices and public places with no need for special precautions. Batteries are normally supplied with the UPS and can either be installed in the same cabinet or in additional ones. AROS guarantees the power supply runtimes specifying the apparent load power and the power factor.

Remarks about the misleading concept of “typycal autonomy”

In defing the runtime it is often used the concept “typical autonomy (or runtime)” which has nothing to do with the real runtime based on the 100% load value expressed in W or kW (active power).

The runtime that AROS shows on all its documentation have been calculaterd at 100% of the load.

18

Power quality and mains disturbance

Electronic equipment functions properly as long as the utility is available and with high quality.

Unfortunately not always this is possible because most of the power quality events are caused by factors beyond the control of the Distribution

Company. These factors may occur either externally (in the network distribution system) or internally (in the facility when the system is located). External causes may be for example storm, lightning, high wind, tree limb contact, construction activities etc, while the internal causes may be switching of the machine, capacitor banks, fault or maintenance activities.

Depending on the events the power quality disturbances may vary in type, duration and intensity.

Typical power supply disturbances that cause major bad effects on your load are listen below.

Power outage

Power interruption for a time of more than 3s is called an outage or commonly “blackout”. This is normally caused by atmospheric accidents to the high voltage distribution network or a failure in the power supply equipment.

Undervoltage

It is a voltage reduction in amplitude for a time between 10 ms to 1 s.

expressed as a percentage from 10 and 100% of the rated voltage. This is caused for example by short circuits in the resident distribution systems or the large inrush current of the transformers.

Undervoltage

Consequences:

- Computer applications

Overheating of the electronic components with consequent operational breakdown.

- Industrial applications

Instability of asynchronous motors and loss of synchronization of synchronous motors, opening of contactors (voltage drop > 30%), power-off discharge lamps (voltage drop > 50% for 20-40 ms) with subsequent return of power after several minutes and consequent operational breakdown.

Overvoltages

Overvoltage is an increase in voltage for a time of more than 10 ms.

Overvoltages may be caused by the disconnection of major loads

(interruption in manufacturing processes of industrial companies, reduction in the speed of electric motors, arc furnaces, rolling mills, etc.) or natural events such as lightning.

Blackout

Consequences:

- Computer applications

Complete system shutdown with loss of data, possible hardware damage and long periods of employee inactivity.

- Industrial applications

Huge impact in the production activity with consequent production loss and/or unexpected safety consequence.

Consequences:

Faults in all electric/electronic equipment (100%<overvoltage<150%); e.g. damage to boards, power supplies, computers/servers, faults in lighting systems, etc.

Sag and Swell

Any short term voltage decrease

(sags) or increase (swell) for a time from half cycle to 3 seconds. It is normally caused by the equipment shutdown, circuit breaker operations, high peak current absorbed by the equipments, or short-circuit.

Consequences:

The major effects may be the loss of data or the lights flicker, very unpleasant for the people exposed to these effects.

Transients

Transients are rapid, very high overvoltages of up to 20 kV. They are caused mainly by lightning (which is random in its location, duration and amplitude) but also by faults on the high-voltage network, the switching of inductive loads or the powering of highly capacitive loads.

Consequences:

Transients destroy inadequately protected equipment (melting of wires, perforation of isolation in motors, badly-timed release of protection devices, etc.).

19

UPS range summary

Power Rating

Topology

Input Voltage

Output Voltage

Inveter Output transformer

Automatic bypass

Maintenace Internal bypass

Battery test

Deep Battery Discharge protection

ECO mode operation

SMART ACTIVE operation

STAND BY - OFF

(Emergency ligthing - EN 50171)

Frequency Converter

Multimodule Configuration

Input Harmonic Filter

Backfeed protection

Base Monitoring Software

(Watch&Save)

RS 232 port

USB port

Dry Contact

● Standard

❍ Optional

RAPIDO ALFA/ALFA PLUS PC PLANET SYNCRO SPRING SENTINEL 6

350-550VA

Line Interactive

400-600-800VA

400-600-800

1100-1600VA

Line Interactive

230V single-phase 230V single-phase

400-600-800VA 800-1000-1500

2000VA

500-800

1100-1500

2200-3000VA

700-1000-1500

2000-3000VA

Line Interactive Line Interactive Line Interactive

230V single-phase 230V single-phase 230V single-phase

On line

Double conversion

230V single-phase

230V single-phase 230V single-phase 230V single-phase 230V single-phase 230V single-phase 230V single-phase

● downloading from internet downloading from internet

● (only Plus version)

● (no mod. 400)

● (no mod. 400)

(1)

pag. 26 pag. 28 pag. 30

(1)

pag. 32

(1)

pag. 34

(1)

pag. 38

(2)

(1) Available only when the RS 232 port is not used for other functions

(2) Available on option and facturing set

(3) Only 6,5-8-10kVA

(4) Only 3Ph input

20

SENTINEL XR

3300-4000

5000-6000-6500 (4)

8000-10000VA

SENTINEL 5 PLUS

6-6,5-8-10kVA

FLEXUS

10-12-15-20kVA (1Ph)

10-12-15-20

30-40kVA (3Ph)

SENTRY MULTISTANDARD

3/1

SENTRY MULTISTANDARD

3/3

10-15-20kVA 10-15-20-30

40-60-80kVA

On line

Double conversion

230V single-phase

400V three-phase (3)

230V single-phase

On line

Double conversion

230V single-phase

400V three-phase (3)

230V single-phase

On line

Double conversion

230V single-phase (5)

400V three-phase (6)

230V single-phase (5)

400V three-phase (6) on option

On line On line

Double conversion Double conversion

230V single-phase

400V three-phase

400V three-phase

230V single-phase 400V three-phase

SENTRY HPS

3/1

8-10-15-20-30-40

60-80-100kVA

On line

Double conversion

400V three-phase

230V single-phase

SENTRY HPS

3/3

10-15-20-30-40

60-80kVA

On line

Double conversion

400V three-phase

SENTRY MPS

30-40-60-80 (1Ph)

100-120-160-200

250-300-400-500

600-800kVA (3Ph)

On line

Double conversion

400V three-phase

400V three-phase

230V single-phase (7)

400V three-phase (8)

(1)

pag. 42

pag. 48

❍ not required

pag. 52

Active Filter

pag. 60

Active Filter

pag. 63

only from 30 to 100kVA

pag. 66

pag. 66

pag. 72

● Standard

❍ Optional

(5) From 10 to 20kVA

(6) From 10 to 40kVA

(7) Only 30-40-60-80kVA

(8) From 100kVA above

21

UPS options

RAPIDO

SOFTWARE PACKAGES

Watch&Save 3000 (Professional Version)

PowerNetGuard

COMMUNICATION OPTIONS

NetMan 101 Plus - Box (TCP/IP, SNMP, HTTP)

NetMan 102 Plus - Slot (TCP/IP, SNMP, HTTP)

MultiCom 301 - Box (MODBUS/JBUS)

MultiCom 302 - Slot (MODBUS/JBUS)

MultiCom 351 - Box (serial duplexer)

MultiCom 352 - Slot (serial duplexer)

MultiCom 362 (RS232 + USB)

MultiCom 372 (additional RS232 port and EPO)

MultiCom 382 (Dry contact extension + EPO)

MultiCom 401 (PROFIBUS)

Multi I/O

USB converter

AS/400 Interface

OTHER OPTIONS

External Battery temperature sensor

Display Remote Monitor panel

Maintenance Bypass cabinet

IRMS

Input isolation transformer

Graphic Remote Panel

▲ Option available

▲ on request

ALFA/ALFA PLUS

PC PLANET

(except PC-Planet 400)

▲ on request

▲ on request

SYNCRO

▲ on request

▲ on request

SPRING

22

SENTINEL 6

SENTINEL XR

SENTINEL 5 PLUS

FLEXUS SENTRY MULTISTANDARD SENTRY HPS SENTRY MPS

▲ on request

▲ Option available

▲ up to 4kVA

▲ on request

▲ on request

▲ on request

▲ on request

23

UPS range summary: rack version

SPRING RACK SENTINEL 6 RACK

500-800-1100-1500-2200-3000VA 700-1000-1500-2200-3000VA Power Rating

Topology

Input Voltage

Line Interactive

230V single-phase

On line

Double conversion

230V single-phase

Output Voltage

Inveter Output transformer

Automatic bypass

Maintenace Internal bypass

Battery test

Deep Battery Discharge protection

ECO mode operation

SMART ACTIVE operation

STAND BY – OFF (Emergency ligthing – EN 50171)

Frequency Converter

Battery expansion capability

Backfeed protection

Base Monitoring Software (Watch&Save)

RS 232 port

USB port

Dry Contact

● Standard

❍ Optional

230V single-phase

– only 2200 and 3000VA

(1)

pag. 36

230V single-phase

(2)

(1)

pag. 40

(1) Available only when the RS 232 port is not used for other functions

(2) Function on request and set by the factory

(3) Only 6,5-8-10kVA

(4) Only 3Ph input

SENTINEL XR RACK

3300-4000-5000-6000-6500 (4)

8000-10000VA

On line

Double conversion

230V single-phase

400V three-phase (3)

230V single-phase

(1)

pag. 42

24

Options for UPS rack version

SOFTWARE PACKAGES

Watch&Save 3000

PowerNetGuard

COMMUNICATION OPTIONS

Netman 101 Plus - Box (TCP/IP, SNMP, HTTP)

Netman 102 Plus - Slot (TCP/IP, SNMP, HTTP)

MultiCom 301 - Box (MODBUS/JBUS)

MultiCom 302 - Slot (MODBUS/JBUS)

MultiCom 351 - Box (serial duplexer)

MultiCom 352 - Slot (serial duplexer)

MultiCom 362 (RS232 + USB)

MultiCom 372 (additional RS232 port and EPO)

MultiCom 382 (Dry contact extension + EPO)

MoultiCom 401 (PROFIBUS)

Multi I/O (Site Monitoring and Alarm configuration)

USB converter

AS400 Interface

Modem GSM

OTHER OPTIONS

Graphic Remote Panel

External bypass cabinet rack 16A

IRMS

▲ Option available

SPRING RACK

SENTINEL 6 RACK

SENTINEL XR RACK

▲ up to 4kVA

25

Rapido

The RAPIDO range is the ideal solution for small office and home systems

(SOHO) requiring over voltage and mains failure protection. The compactness, versatility (a push-button switch with LED-based mimic panel and user-replaceable batteries) and functionality of the RAPIDO allow it to easily fit into any small office and home environment.

When the mains fails, connected loads are powered with a pseudo sine wave supply from the inverter. For additional security users can download a version of the Watch&Save 3000 UPS monitoring and control software.

LOAD CONFIGURATOR

Load type

Personal computer

LCD Monitor

15” Monitor

Scanner, printer

Modem, TV, DVD reader,

Power (VA)*

250

70

150

200

PlayStation, Hi-Fi,

Phone, Fax

Laser printer**

*Average estimated value.

**Use the Rapido filtered power output

50

200

CHARACTERISTICS

• Maximum compactness

• 3 sockets with mains fail protection

• 1 socket with filtering for powering loads such as laser printers

• Integrated protection for telephone line/modem

• Cold start capability: the UPS can power up without a mains supply present

• User replaceable batteries

• USB interface

• Can be placed on a desktop, floor, or be wall-mounted

• Input supply and telephone cable included

• Short-circuit protection

• Auto restart (on mains return, after batteries have discharged)

• GS/TÜV marks

• Available with French (2P+T), UK or

Schuko plugs

AVAILABLE SOCKETS

ADVANCED COMMUNICATION

• Watch&Save 3000 monitoring and shut-down software for Windows

Vista, 2003, XP, 2000, Me, 98, Linux,

Mac OS X and Sun Solaris

• Plug and Play function

APPLICATIONS

• Personal computers

2-YEAR WARRANTY

FRENCH

SOCKET

ITALIAN/

SCHUKO

SOCKET

BRITISH

SOCKET

26

Rapido

Models

Power

Input

Rated voltage

Voltage range

Frequency

Output

Voltage on mains operation

Frequency on battery operation

Waveform on battery operation

Batteries

Type

Recharge time

System

Weight (kg)

Dimensions (wdh) (mm)

Tel. protection

Communication

Safety compliance

EMC conformance

Marks

Operating temperature

Colour

Altitude and relative humidity

Accessories provided

Details

Technical data

Rapido 350

350VA/225W

Rapido 550

550VA/335W

Rapido 350 Rapido 550

230 Vac

188-262 Vac

50/60 Hz

Rapido 350 Rapido 550

230 Vac

50 or 60 Hz

Pseudo sinewave

Rapido 350 Rapido 550

Maintenance-free lead-acid VRLA, AGM

6-8 h

Rapido 350

3

Rapido 550

3.1

120x320x88

RJ11/J45 connectors

On USB interface

EN 62040-1-1 and Directives 72/73 EEC, 93/68 EEC, EN 62040-3

EN 62040-2 and Directives 89/336 EEC, 92/31 EEC, 93/68 EEC

CE; GS/TÜV

O °C / +40 °C

Dark grey

6000 meters max. elevation, <95% non condensing

1 input supply cable, telephone cable

Sockets with UPS protection

(no break in power if mains fails)

Filtered socket: overvoltage protection only

USB communication port

Mains input

Phone/modem protection

27

Alfa/Alfa Plus

The Alfa series is available in 400 to

1600VA models and has been designed to protect PCs and critical peripherals in home and small office environments.

Alfa is easy to install and provides powerful, economic protection for:

IT equipment including PCs, Media

Centers, PoE, Voip and other such peripherals, TVs, Home Cinemas,

Satellite and Digital Terrestrial receivers,

DVD readers and writers, Modems and xDSL routers, Small household appliances.

CHARACTERISTICS

• Compact dimensions and ergonomic design: Alfa can be placed on a desk top or other convenient location, with easy to access connections and informative front panel.

• Front panel LCD display ( Plus version only) providing status, load and battery information and LEDs

(standard version).

• Silent running: Alfa can be used to protect other sensitive electronic devices including Home Cinemas,

CD Writers, DVD players, Satellite and Digital Terrestrial receivers.

ADVANCED COMMUNICATION

• Maximum power protection with

Watch&Save 3000 monitoring and shutdown software available for free download from our website www.aros.it.

• It is suitable for installation on PC's running Windows Vista, 2003, XP,

2000, Me, 98; Linux, Mac OSX and the Sun Solaris operating system.

APPLICATIONS

• IT equipment including PCs Media

Centers, PoE, Voip and other such peripherals

• TVs, Home Cinemas, Satellite and

Digital Terrestrial receivers, DVD readers and writers

• Modems and xDSL routers

• Small household appliances

2-YEAR WARRANTY

28

Alfa/Alfa Plus

Technical data

Models

Power

Input

Rated voltage

Voltage range

Frequency

Output

Voltage on mains operation

Frequency on battery operation

Voltage on battery operation

Batteries

Type

Recharge time

System

Weight (kg)

Dimensions (wdh) (mm)

Tel. protection

Communication

Output sockets

Safety compliance

EMC conformance

Marks

Operating temperature

Colour

Altitude and relative humidity

Accessories provided

Details

Alfa 400 Alfa 600 Alfa 800 AlfaP 400 AlfaP 600 AlfaP 800 AlfaP1100 AlfaP1600

400VA/240W 600VA/360W 800VA/480W 400VA/240W 600VA/360W 800VA/480W 1100VA/660W 1600VA/960W

Alfa 400 Alfa 600 Alfa 800 AlfaP 400 AlfaP 600 AlfaP 800 AlfaP1100 AlfaP1600

220-240 Vac

230 Vac (+20/-25%)

50/60 Hz auto sensing

Alfa 400 Alfa 600 Alfa 800 AlfaP 400 AlfaP 600 AlfaP 800 AlfaP1100 AlfaP1600

230 Vac (+/-15%)

50 or 60 Hz (+/-1%)

230 Vac (+/-10%)

Alfa 400 Alfa 600 Alfa 800 AlfaP 400 AlfaP 600 AlfaP 800 AlfaP1100 AlfaP1600

Maintenance-free lead-acid VRLA, AGM

6-8 h

Alfa 400 Alfa 600 Alfa 800 AlfaP 400 AlfaP 600 AlfaP 800 AlfaP1100 AlfaP1600

3 3.2

3.4

6.6

7

90x232x192 97x315x275 n.d.

4 IEC

RJ11/J45 connectors

USB

4 IEC or 3 Shuko/Italian or 3 french 6 IEC or 4 Shuko/Italian or 4 french

EN 62040-1-1 and Directives 72/73 EEC, 93/68 EEC, EN 62040-3

EN 62040-2 and Directives 2004/108 EC, 93/68 EC

CE

O °C / +40 °C

Dark grey

6000 meters max. elevation, <95% non condensing

2 output supply cables (IEC version), 1 USB cable (Plus version), user guide

Phone/modem protection

Sockets whit UPS protection

(no break in power if mains fails)

Alfa

400-600-800

Alfa Plus

400-600-800

USB communication port

Mains input

Alfa Plus

1100-1600

Filtered sockets: overvoltage protection only

29

PC Planet

The PC PLANET series includes the

400-600-800VA models and uses digital technology. The load is powered from the mains through an AVR to stabilise brownout, sag and surge voltages, and EMI filters to suppress spikes and transients. When the mains fails, the load is powered by the inverter with a pseudo sinewave to provide sufficient runtime for computer system shutdown using the Watch&Save 3000 software supplied as standard.

CHARACTERISTICS

• Mains power supply stabilisation and filtering (with AVR and filters for atmospheric disturbance suppression)

• Integrated protection for PC networks and telephone line/modem connections RJ11/45

• Cold start capability: the UPS can power up without a mains supply present

• High reliability with built-in battery test feature

• Supplied with 2 output cables

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME,

NT 4.0, 2000, XP, Vista and 2003 server; Mac OS X, Linux, and Unix operating systems.

• Standard USB interface

APPLICATIONS

• Personal computers

• Small computers network

2-YEAR WARRANTY

30

PC Planet

Models

Power

Input

Rated voltage

Voltage range

Frequency

Output

Voltage on mains operation

Voltage on battery operation

Frequency on battery operation

Waveform on battery operation

Batteries

Type

Recharge time

System

Weight (kg)

Dimensions (wdh) (mm)

Tel. protection

Communication

Safety compliance

EMC conformance

Marks

Operating temperature

Colour

Altitude and relative humidity

Accessories provided

Details

USB

Mains input

Technical data

PC Planet 400

400VA/240W

PC Planet 400

PC Planet 400

PC Planet 600

600VA/360W

PC Planet 600

220-240 Vac

230 Vac (+20/-26%)

50/60 Hz auto sensing

PC Planet 600

230 Vac (-8%, +10%)

230 Vac (± 5%)

50 or 60 Hz (± 0.5%)

Pseudo sinewave

PC Planet 800

800VA/480W

PC Planet 800

PC Planet 800

PC Planet 400 PC Planet 600

VRLA AGM Maintenance-free lead-acid

6-8 h

PC Planet 800

PC Planet 400

5.8

PC Planet 600 PC Planet 800

6.2

110x325x152

RJ11/RJ45 connectors

USB

EN 62040-1-1 and Directives 72/73 EEC, 93/68 EEC, EN 62040-3

EN 62040-2 and Directives 89/336 EEC, 92/31 EEC, 93/68 EEC

CE; GS/TÜV

O °C / +40 °C

Dark grey

6000 meters max. elevation, <95% non condensing

2 output supply cables, 1 serial cable, 1 telephone cable; user guide

Telephone line/

Modem connection

Output sockets

31

Syncro

The SYNCRO series includes the 800-

2000VA models and uses digital technology. The load is powered from the mains through an AVR to stabilise brownout, sag and surge voltages, and

EMI filters to suppress spikes and transients.

When the mains fails, the load is powered by the inverter with a pseudo sinewave to provide sufficient runtime for computer system shutdown using the Watch&Save 3000 software supplied as standard. The UPS also incorporates a filtered socket for PC network and telephone line cable protection.

For advanced communication and top flight performance, SYNCRO is the ideal solution for small network users requiring total control of their power system.

CHARACTERISTICS

• Mains power supply stabilisation and filtering (technology with AVR and filters for atmospheric disturbance suppression)

• Cold start capability: the UPS can power up without a mains supply present

• Auto restart at power-up

• Integrated protection for PC networks and telephone line/modem connections RJ11/45

• High reliability with built-in automatic battery test feature

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME,

NT 4.0, 2000, XP, Vista and 2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems.

• The UPS is supplied with a communications cable for Plug and

Play PC connection

APPLICATIONS

• Personal computers

• Small computers network

2-YEAR WARRANTY

32

Syncro

Technical data

Models

Power

Input

Rated voltage

Voltage range

Frequency

Output

Voltage on mains operation

Voltage on battery operation

Frequency on battery operation

Transfer time

Waveform on battery operation

Batteries

Type

Recharge time

System

Weight (kg)

Dimensions (wdh) (mm)

Protection

Tel/Modem protection

Communication

Safety compliance

EMC conformance

Surge capability

Noise

Colour

Operating temperature

Storage temperature

Relative humidity

Details

Serial interface port

Telephone line/ modem protection

Output sockets

Mains input

Syncro 800-1000-1500

Syncro 800

800VA/480W

Syncro 800

Syncro 800

Syncro 800

Syncro 1000

1000VA/600W

Syncro 1500

1500VA/900W

Syncro 1000 Syncro 1500

220-230-240 Vac

230 Vac (±25%)

50/60 Hz auto sensing

Syncro 1000 Syncro 1500

230 Vac (-8%, +10%)

230 Vac (± 5%)

50 or 60 Hz (± 0.5%)

2 ms

Pseudo sinewave

Syncro 1000 Syncro 1500

Maintenance-free lead-acid VRLA, AGM

6-8 h

Syncro 2000

2000VA/1200W

Syncro 2000

Syncro 2000

Syncro 2000

Syncro 800

14

Syncro 1000

14.5

Syncro 1500

15

140x375x180

Battery low - overcurrent - short-circuit

RJ11/RJ45 connectors

RS232 port

EN 62040-1-1 and Directive 73/23, 93/68 EEC, EN 62040-3

Syncro 2000

20

140x410x214

EN 62040-2 and Directive 89/336, 192/31 EEC, 93/68 EEC

IEC 801-5

< 40 dBA at 1 m

Dark grey

0 °C / +40 °C

-15 °C / +45 °C

< 95% non condensing

Syncro 2000

33

Spring

The SPRING series includes models from 500VA to 3000VA and uses sinewave digital technology.

The SPRING range, with its advanced communications and connectivity options, is the ideal solution for the most demanding of customers looking for superior protection and versatility.

SPRING is the best protection for network devices, rack mounted servers, conventional rack-mounted or tower servers, network storage systems.

VERY HIGH PROTECTION

The Automatic Voltage Regulation provides stabilisation from brownouts, sag and surge voltages without making use of the batteries.

Less frequent usage of the batteries means that they will be fully charged when really needed and last longer.

EMI filters then provide further protection from spikes and transients.

When the mains power supply fails, the load is powered by the inverter and receives a true SINEWAVE supply for maximum power continuity and reliability.

The UPS also incorporates a protection for PC and network, telephone line/modem connections (RJ45-RJ11).

OPTIONS

Battery box

(only 2200RT/3000RT)

HIGH AVAILABILITY

Powershare output socket provides the load-shedding of the least critical load to maximise the back up time of the most critical servers.

Hot Swappable battery from the front of the UPS allows easy and no-risks maintenance of the UPS.

Additional Battery Box and extended charging current are available in

2200RT and 3000RT for very long back up time applications.

Predictive battery testing to spot potential battery deterioration and failure. Deep discharge protection to reduce overall battery aging.

VERSATILITY

Spring (2200RT and 3000RT) can be placed directly onto the floor or mounted in 19’’ rack mount cabinets.

The front panel digital display can be easily pulled out and rotated to suit the installation format.

Tower and Rack versions includes

Emergency Power Off switch, which allows to shutdown the output power in case of emergency situations.

Cold start function enables Spring to start up when power network is not available.

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME,

NT 4.0, 2000, XP, Vista and 2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems.

• USB or RS232 serial port (selectable)

• Slot-in SNMP network adapter card

• LCD Display

APPLICATIONS

• Personal computers

• Small computers network

• Local Area Networks (LAN)

• Workstations

• Servers

• EPOS (Electronic Point Of Sales) system

2-YEAR WARRANTY

34

Spring

Models

Power

Input

Rated voltage

Voltage range

Frequency

Frequency range

Output

Rated voltage

Frequency

Waveform

Batteries

Type

Recharge time

System

Weight (kg)

Dimensions (wdh) (mm)

IEC mains input plug

IEC output sockets

Protection

Communication

Safety compliance

EMC conformance

Performance

Operating temperature

Storage temperature

Relative humidity

Noise

Details

Technical data

S 500T S 800T S 1100T S 1500T S 2000T S 2200RT S 3000RT

500VA/350W 800VA/540W 1100VA/740W 1500VA/1050W 2000VA/1350W 2200VA/1540W 3000VA/2100W

S 500T S 800T S 1100T S 1500T

230 Vac

160 V - 294 V

50/60 Hz auto sensing

± 5%

S 2000T S 2200RT S 3000RT

S 500T S 800T S 1100T S 1500T

230 Vac (-5%, -10%)

S 2000T S 2200RT S 3000RT

50 or 60 Hz auto sensing

True sinewave

S 500T S 800T S 1100T S 1500T S 2000T S 2200RT S 3000RT

VRLA AGM Maintenance-free lead-acid

4-6 h

S 500T

7,2

1 (10A)

4 (10A)

S 800T

10,6

110x383x235

S 1100T

11

S 1500T

18

S 2000T S 2200RT S 3000RT

160x425x235

18,4 31

582x438x88

32

1 (10A)

4 (10A)

1 (10A)

4 (10A)

1 (10A)

4 (10A)

1 (10A)

4 (10A)

1 (16A) 1 (16A)

8 (10A) - 1 (16A)

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

USB / RS232 / slot for interface communication

IEC / EN62040-1-1 and Directive EEC 73/23

IEC / EN62040-2 and Directive EEC 89/336

IEC / EN62040-3

0 °C / + 40 °C

-15 °C - 45 °C

< 95% non condensing

< 55 dBA

S 500T-800T-1100T

USB port

Serial interface port RS232

Telephone/ it network protection

Mains input IEC

Slot for SNMP network adapter card

Output sockets

IEC

Powershare socket

S 1500T-2000T

35

Spring Rack

The SPRING series includes models from 500VA to 3000VA and uses sinewave digital technology.The

SPRING range, with its advanced communications and connectivity options, is the ideal solution for the most demanding of customers looking for superior protection and versatility.

SPRING is the best protection for network devices, rack mounted servers, conventional rack-mounted or tower servers, network storage systems.

VERY HIGH PROTECTION

The Automatic Voltage Regulation provides stabilisation from brownouts, sag and surge voltages without making use of the batteries. Less frequent usage of the batteries means that they will be fully charged when really needed and last longer. EMI filters then provide further protection from spikes and transients.

When the mains power supply fails, the load is powered by the inverter and receives a true SINEWAVE supply for maximum power continuity and reliability.

The UPS also incorporates a protection for PC and network, telephone line/modem connections (RJ45-RJ11).

OPTIONS

Battery box

(only 2200RT/3000RT)

HIGH AVAILABILITY

Powershare output socket provides the load-shedding of the least critical load to maximise the back up time of the most critical servers.

Hot Swappable battery from the front of the UPS allows easy and no-risks maintenance of the UPS.

Additional Battery Box and extended charging current are available in tower

2200 and 3000 for very long back up time applications.

Predictive battery testing to spot potential battery deterioration and failure.

Deep discharge protection to reduce overall battery aging.

VERSATILITY

Spring RT (tower 1500, 2200 and

3000) can be placed directly onto the floor or mounted in 19’’ tower mount cabinets.

The front panel digital display can be easily pulled out and rotated to suit the installation format.

Tower and rack versions includes

Emergency Power Off switch, which allows to shutdown the output power in case of emergency situations.

Cold start function enables Spring to start up when power network is not available.

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME,

NT 4.0, 2000, XP, Vista and 2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems.

• USB or RS232 serial port (selectable)

• Slot-in SNMP network adapter card

• LCD Display

APPLICATIONS

• Personal computers

• Small computers network

• Local Area Networks (LAN)

• Workstations

• Servers

• EPOS (Electronic Point Of Sales) system

36

Spring Rack

Technical data

Models

Power

Input

Rated voltage

Voltage range

Frequency

Frequency range

Output

Rated voltage

Frequency

Waveform

Batteries

Type

Recharge time

System

Weight (kg)

Dimensions (wdh) (mm)

IEC mains input plug

IEC output sockets

Protection

Communication

Safety compliance

EMC conformance

Performance

Operating temperature

Storage temperature

Relative humidity

Noise

Details

S 500R-800R-1100R

S 500R

500VA/350W

S 500R

S 500R

S 800R S 1100R S 1500RT S 2200RT S 3000RT

800VA/540W 1100VA/740W 1500VA/1050W 2200VA/1540W 3000VA/2100W

S 800R S 1100R S 1500RT

230 Vac

160 V - 294 V

50/60 Hz auto sensing

± 5%

S 2200RT S 3000RT

S 800R S 1100R S 1500RT

230 Vac (-5%, -10%)

50 or 60 Hz auto sensing

True sinewave

S 2200RT S 3000RT

S 500R S 800R S 1100R S 1500RT

VRLA AGM Maintenance-free lead-acid

S 2200RT

4-6 h

S 3000RT

S 500R

12

S 800R

13,5

S 1100R

15,6

S 1500RT

28,7

S 2200RT

31

S 3000RT

32,8

19” x 460 x 1U 19” x 460 x 1U 19” x 582 x 2U 19” x 582 x 2U 19” x 582 x 2U 19” x 582 x 2U

1 (10A)

4 (10A)

1 (10A)

4 (10A)

1 (10A)

4 (10A)

1 (10A)

8 (10A)

1 (16A)

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

USB / RS232 / slot for interface communication

1 (16A)

8 (10A) - 1 (16A)

IEC / EN62040-1-1 and Directive EEC 73/23

IEC / EN62040-2 and Directive EEC 89/336

IEC / EN62040-3

0 °C / + 40 °C

-15 °C - 45 °C

< 95% non condensing

< 55 dBA

S 1500R

Output sockets IEC

Powershare socket

Mains input IEC

Output sockets IEC

Powershare socket

S 2200R-3000R

Serial interface port RS232

USB port

EPO

Thermal fuses

Output sockets IEC

Telephone/it network protection

Battery expansion connector

Output sockets

IEC 16A

37

Sentinel 6

The SENTINEL 6 series includes the 700-

1000-1500-2000-3000VA models and uses double conversion technology (VFI).

The load is powered continuously by the inverter with an EMI filtered, stabilised and regulated sinewave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges, even on bypass.

The UPS can power the load for long periods (using battery extension packs) or provide sufficient runtime to allow shutdown of the protected systems using the

Watch&Save 3000 software, supplied as standard, for Windows 95, 98, NT 4.0,

Me, 2000, 2003, XP, Mac OS 9.x, X,

Linux operating systems.

For outstanding power protection and communication SENTINEL 6 is the best solution for sensitive and “mission-critical” applications.

SENTINEL 6 POWER models are supplied with a larger internal charger and with their matching external battery extension packs can achieve long back up times.

CHARACTERISTICS

• Reliable, filtered, stabilised and regulated sinewave output (double conversion technology VFI in conformance with IEC

62040-3 specifications) with filters for atmospheric disturbance suppression

• High level immunity to surges (up to

150%)

• Auto restart on mains return

(programmable)

• Start-up without mains (cold start)

• GS-TÜV certification

• Power factor correction with sinusoidal input to ensure a low impact on the mains supply (UPS input power factor, close to 1)

• Wide input voltage window (110-300Vac) to reduce battery usage

• Integrated protection for PC networks and telephone line/modem connections

RJ45-RJ11

• Option to extend the back up time to several hours

• Software-programmable operating parameters

• Timer for scheduled shut-down and power up (software programmable)

• Highly reliable batteries with automatic and manual test feature

• Highly reliable system with full microprocessor control

• Breaker based input protection

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME, NT

4.0, 2000, XP, Vista and 2003 server;

Mac OS X, Linux, Novell and most popular Unix operating systems.

• Free UPS tools configuration software

• RS232 serial port

• Slot-in SNMP network adapter card.

APPLICATIONS

• Small computers network

• Local Area Networks (LAN)

• Workstations

• Servers

• EPOS (Electronic Point of Sales) system

2-YEAR WARRANTY

OPTIONS

Extended runtime solutions

(except 700VA)

Isolation transformer box (wdh) mm

• S6-700/1000/1000power/1500

158x434x231

• S6-2000/2000power

3000/3000power

158x460x340

38

Sentinel 6

Models

Power

Input

Rated voltage

Minimum voltage range

Rated frequency

Power factor

Input current

By pass

Voltage range

Frequency range

Batteries

Type

Recharge time

Output

Rated voltage

Voltage distortion

Frequency

Crest factor

Overload

System

Weight (kg)

Dimensions (wdh) (mm)

Operating temperature

Relative humidity

Protection

Communication

Compliance

Surge capability

Colour

Noise

Details

Technical data

S6-700

700VA/490W

S6-700

S6-700

S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000

POWER POWER POWER

1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W

S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000

POWER POWER POWER

220 - 230 - 240 Vac

110V up to 60% of load / 120V from 60% to 70% of load

140V from 70 to 80% of load / 160V from 80% to 100% of load

50/60 Hz ± 5Hz

> 0.97

Sinewave

S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000

POWER POWER POWER

180 - 264 Vac

Selected frequency ±5Hz

S6-700

2-4 h

S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000

POWER POWER POWER

Maintenance-free lead-acid VRLA, AGM

2-4 h 4 h 4 h -

S6-700

S6-700

12

S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000

POWER POWER POWER

Selectable 220, 230 or 240 Vac ±1.5%, Sinewave

< 2%

50 or 60 Hz auto sensing

3 : 1

110% 30’; 130% 30”; 150% 10”

S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000

POWER POWER POWER

15 14

158x400x231

8 19

158x500x231

O °C / +40 °C

34 14

192x460x340

< 95% non condensing

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

35

RS232 + communication interface slot

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

3KA 8/20

μs

Dark grey (RAL 7035)

<40 dBA

Serial interface

External battery pack soc ket

Slot for SNMP network adapter ca rd

Serial interface

External battery pack soc ket

Slot for SNMP network adapter ca rd

S6 700

Output soc kets

Input socket

Telephone/IT network protection

S6 1000-1000 power

S6 1500

S6 2000-2000 power

Output soc kets

Input soc ket

Telephone/IT network protection

Output sockets

S6 3000-3000 power

39

Sentinel 6 Rack

For outstanding power protection and communication SENTINEL 6 RACK is the best solution for sensitive and “mission-critical” applications.

The SENTINEL 6 RACK series comprises the 700-1000-1500-2200-

3000VA models and uses double conversion technology (VFI). The load is powered continuously by the inverter with an EMI filtered, stabilised and regulated sinewave supply.

The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges, even on bypass. The UPS can power the load for long periods (using battery extension packs) or provide sufficient runtime to allow shut-down of the protected computer systems using the

Watch&Save 3000 software, supplied as standard, for Windows 95, 98, Me,

2000, 2003, XP, Mac OS 9.x, X, Linux,

NT 4.0, Novell operating systems.

SENTINEL 6 RACK POWER models are supplied with a larger internal charger and with their matching external battery extension packs can achieve long back up times.

CHARACTERISTICS

• Reliable, stabilised, filtered voltage double on-line conversion technology

(VFI according to EN62040-3 specifications) with filters for the suppression of atmospheric disturbances

• High overload capability (up to 150%)

• Auto restart when mains power returns

(programmable)

• GS-TÜV certification

• Power factor correction with sinusoidal input to ensure a low impact on the mains supply (UPS input power factor, close to 1)

• Wide input voltage range (110-300Vac) to reduce battery usage

• Integrated protection for PC networks and telephone line/modem connections RJ45-RJ11

• Option to extend the back up time to several hours

• Programming of operating functions via software

• Timer for scheduled shut-down

(software programmable)

• High level reliability of the batteries

(automatic and manual test)

• High level reliability of the UPS (full microprocessor control)

• Breaker based input protection

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments: Watch&Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows

9x, ME, NT 4.0, 2000, XP, Vista and

2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems.

• The UPS is supplied with a communication cable for Plug and Play

PC connection

• UPS tools configuration software

• Emergency Power Off (EPO) contact

• RS232 serial port

• Slot-in SNMP network adapter card.

APPLICATIONS

• Local Area Networks (LAN)

• Data Centers

• Servers

• Industrial PLCs

• Cash registers

• Emergency devices (lights/alarms)

• Telecommunication devices

2-YEAR WARRANTY

OPTIONS

Extended runtime solutions

(except 700VA)

External manual bypass (wdh) mm/kg

• Rack version

438x360x2U / 6,8

• Box version

300x115x180 / 3,3

40

Sentinel 6 Rack

Models

Power

Input

Rated voltage

Minimum voltage range

Rated frequency

Rated current (A)

Power factor

By pass

Voltage tolerance

Frequency tolerance

Batteries

Type/Recharge time

Output

Rated voltage

Voltage distortion

Frequency

Crest factor (Ipeak/Irms)

Overload

System

Weight (kg)

Dimensions (wdh) (mm)

Communication

Operating temperature

Relative humidity

Protection

Compliance

Capability

Colour

Noise

Details

Technical data

S6R 700-1000-1000 power-1500

Battery extension pack socket

IEC mains input socket

Battery extension pack socket

IEC mains input socket

S6R 2200-2200 power-3000-3000 power

S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000

POWER POWER POWER

700VA/490W 1000VA/700W 1500VA/1050W 2200VA/1540W 3000VA/2100W

S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000

POWER POWER POWER

220 - 230 - 240 Vac

2.5

3.5

110V up to 60% of load/120V from 60% to 70% of load

50/60 Hz ± 5Hz

5.2

6.8

10 13.8

> 0.97

14.4

16

S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000

POWER POWER POWER

Static ± 1.5%

± 0,5%

S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000

POWER POWER POWER

Maintenance-free lead-acid VRLA, AGM / 4 h

S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000

POWER POWER POWER

220 or 230 or 240 Vac selectable ± 1,5%, Sinewave

< 2%

50 or 60 Hz selectable, ± 0,5 %

3 : 1 (up to 100% of load)

110% 30’; 130% 30”; 150% 10”

S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000

POWER POWER POWER

13 16

19"x390x2U

9 21 30 13 31 14

19”x480x2U 19"x560x3U 19"x480x2U 19"x560x3U 19"x480x2U

RS232 + communication interface slot

O °C / +40 °C, ideal for battery +15 °C / +25 °C

< 95% non condensing

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

3KA 8/20

μs

Dark grey (RAL 7035)

<40 dBA at 1 m

IEC output socket

Serial interface port

Input thermal protection

IEC output socket

Serial interface port

Input thermal protection

41

Sentinel XR

SENTINEL XR is the best solution for protecting medium sized networking applications which require the highest possible levels of reliability. The UPS is designed to support a wide applications from IT to security. SENTINEL XR is unique in that the UPS can be placed directly onto the floor or mounted in 19” rack mount cabinets. The range is available in 3300-4000-5000-6000-

8000-10000VA models. The UPS is primarily an on-line double-conversion

(VFI) technology system with further selectable operating modes that can configure the UPS to protect applications including emergency lighting, security and medical systems.

Each UPS features advanced communications and diagnostics including a digital front panel display that can turned to suit the installation format,

RS232 and USB interfaces, and an internal adaptor slot for SNMP and other interface card options.

Watch&Save 3000 software is supplied as standard.

SIMPLIFIED INSTALLATION

• The UPS can be installed as a floor standing tower or 19” rack mount

UPS. The front panel digital display can be pulled out (using the keys provided) and rotated to suite the installation format

• Low noise level (<40dBA) thanks to the digitally PWM controlled ventilation system which is load and temperature dependent, and the use of an inverter with a high switching frequency

(>20kHZ, above the audible range)

• Optional bolt-on maintenance bypass

(SENTINEL XR 5-6-8-10 kVA models) to allow service without disruption to the loads

• Performance guaranteed in temperatures up to 40°C

• Two IEC output plugs with thermal protection (SENTINEL XR 5-6-8-10 kVA)

• PowerShare output socket (2x10A

IEC) functionality on SENTINEL XR 5-

6-8-10 kVA models

SELECTABLE OPERATING MODES

• On line

• Economy Mode: selects Line

Interactive VI technology to power noncritical loads from mains and achieve up to 98% operating efficiency

• Smart Active Mode: the UPS selects automatically whether to operate in

On-line VFI technology - full system protection or Line Interactive VI mode depending on the stability of the mains supply

• Emergency: the UPS can be programmed to work only when the mains fails - suitable for emergency lighting

• Frequency conversion 50 or 60Hz

Display LCD custom

42

GUARANTEED OUTPUT QUALITY

• Even with typical distorting IT loads with crest factors of 3:1

• Increased short circuit current on the bypass

• Increased overload capacity: 150% on inverter even when mains supply has failed

• Reliable, filtered, stabilised and regulated sinewave output (double conversion technology VFI in conformity with IEC 62040-3 specifications) with filters for atmospheric disturbance suppression

• Rephasing of load as the UPS has an input power factor close to 1, with a sinusoidal input current

HIGHLY RELIABLE BATTERY

PERFORMANCE

• Automatic and manual battery tests

• Unique Low Ripple Current Discharge

(LRCD) to help prolong battery life

• Hot-swap user replaceable batteries

• Unlimited extendable back-up time using modular design Battery

Extension Packs

• Increased ride through (without batteries) on mains breaks up to 40ms and for fluctuations ranging from 84 to

276Vac

OTHER CHARACTERISTICS

• Output voltage selection: 220-230-

240Vac

• Auto restart when mains power returns programmed using the UPS Tools software supplied

• Bypass on: when the UPS is switched off, it automatically goes into bypass mode to charge the batteries

• Automatic power down due to minimum load

• End of battery discharge pre-alarm

• Delayed start up

• Completely digitally controlled

• Automatic bypass with no break in power supply

• Use of IMS (Insulated Metallic

Substrates) modules

• Status, measurements, and alarms available on the standard backlit display

• UPS can be updated digitally (flash upgradeable)

• Input protected by resettable thermally activated switch

• Back-feed protection: to avoid current being fed back into the mains should a fault occur

• Manual switch over to bypass

• Microsoft Certified Product

ADVANCED COMMUNICATION

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME, NT

4.0, 2000, XP, Vista and 2003 server;

Mac OS X, Linux, Novell and most popular Unix operating systems.

• The UPS is supplied with a communications cable for ‘Plug and

Play’ PC connection

• USB port

• RS232 serial port

• Interface card slot

APPLICATIONS

• Local Area Networks (LAN)

• Data Centers

• Servers

• Industrial PLCs

• Cash registers

• Electromedical devices

• Emergency devices (lights/alarms)

2-YEAR WARRANTY

OPTIONS

Extended runtime solutions with/without battery charger

External maintenance bypass

(except 3300VA and 4000VA)

Interface cards

Telescopic rails for rack cabinet

SUITABLE FOR

APPLICATIONS

43

Sentinel XR

Single-phase input

Single-phase output

Models

Power

Input

Rated voltage

Minimum voltage

Rated frequency

Power factor

Current distortion

By pass

Voltage range

Frequency range

Batteries

Recharge time

Output

Rated voltage

Static variation

Dynamic variation

Waveform

Voltage distortion with linear load

Voltage distortion with non-linear load

Frequency

Crest factor

Overload capacity

100% < Load < 110%

110% < Load < 125%

125% ≤ Load < 150%

Load > 150%

Technical data

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

3300VA/2300W 4000VA/2400W 5000VA/3500W 6000VA/4200W 8000VA/6400W 10000VA/8000W

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

220 - 230 - 240 Vac

164 Vac @ load 100% 84 Vac @ load 50%

50/60 Hz ± 5 Hz

> 0.98

≤ 7%

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)

Selected frequency ±5 % (user configurable)

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

4 - 6 h

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

220 - 230 - 240 Vac selectable

1,5 %

≤ 5% in 20 ms

Sinewave

< 3%

< 6%

50/60 Hz selectable

3 : 1

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

1’

4”

4”

0.5”

44

Sentinel XR

System

Weight (kg)

Dimensions (wdh) (mm) tower

Dimensions (wdh) (mm) rack

On Line Efficiency

Line-interactive/Smart Active Efficiency

Operating temperature

Relative humidity

Protection

Compliance

Communication

Colour

Noise

Accessories provided

SXRM-3300 SXRM-4000 SXRM-5000 SXRM-6000 SXRM-8000 SXRM-10000

38 40 62 64 80 85

175x520x455 175x660x455 2x175x660x455

483x520x175(4U) 2x483x660x175(4U) 483x660x175(4U)

92%

98%

O °C / +40 °C

< 95% non condensing

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

USB / RS232 + communication interface slot

Dark grey (RAL 7016)

<40 dBA at 1 m

2x10A cables; 1xIEC-16A plug; software; serial cable; plastic keys to release display; handles kit

<45 dBA at 1 m

2 cable guides; terminal board connection; software; serial cable; plastic keys to release display; handles kit

Details

SXRM 3300-4000

USB port

Serial port

Interface card slot

SNMP or additional

RS232 ports

Input thermal protection re-set

Input hardwired gland

Output hardwired glands

Battery extension pack connector

Input cable access

Output cable access

SXRM 5000-6000 SXRM 8000-10000

45

Sentinel XR

Three-phase input

Single-phase output

Models

Power

Input

Rated voltage

Minimum voltage

Rated frequency

Power factor

By pass

Voltage range

Frequency range

Batteries

Recharge time

Output

Rated voltage

Static variation

Dynamic variation

Waveform

Voltage distortion with linear load

Voltage distortion with non-linear load

Frequency

Crest factor

Overload capacity

100% < Load < 110%

110% ≤ Load < 150%

Load > 150%

Technical data

SXRT-6500

6000VA/5200W

SXRT-6500

SXRT-8000

8000VA/6400W

SXRT-10000

10000VA/8000W

SXRT-8000

400 Vac tree-phase + N

164 Vac @ load 100% - 84 Vac @ load 50%

50/60 Hz ± 5 Hz

> 0.95

SXRT-10000

SXRT-6500 SXRT-8000 SXRT-10000

180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)

Selected frequency ±5 % (user configurable)

SXRT-6500 SXRT-10000

SXRT-6500

SXRT-8000

4 - 6 h

SXRT-8000

220 - 230 - 240 Vac selectable

1,5 %

≤ 5% in 20 ms

Sinewave

< 3%

< 6%

50/60 Hz selectable

3 : 1

SXRT-10000

SXRT-6500 SXRT-8000

1’

4”

0.5”

SXRT-10000

46

Sentinel XR

System

Weight (kg)

Dimensions (wdh) (mm) tower

Dimensions (wdh) (mm) rack

On Line Efficiency

Line-interactive/Smart Active Efficiency

Operating temperature

Relative humidity

Protection

Compliance

Communication

Colour

Noise

Accessories provided

Details

SXRT-6500

64

SXRT-8000

80

2x175x660x455

2x483x660x175(4U)

92%

98%

O °C / +40 °C

SXRT-10000

85

< 95% non condensing

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-2004/108EC EN 62040-3

USB / RS232 + communication interface slot

Dark grey (RAL 7016)

<45 dBA at 1 m

2 cable guides; terminal board connection; software; serial cable; plastic keys to release display; handles kit

Battery connection

Serial port

USB port

SXRT 6500-8000-10000

Interface card slot SNMP or additional RS232 ports

Input cable access

Output cable access

47

Sentinel 5 Plus

SUITABLE FOR

APPLICATIONS

For technology, outstanding performance

(selectable operating modes: On-line,

Economy, Smart-Active and Standby/Off

- for emergency lighting applications), advanced diagnostics (standard LCD display, RS232 interfaces with

Watch&Save 3000 software included,

EPO input contact, and a network interface slot), SENTINEL 5 PLUS provides maximum protection for vital

‘mission-critical’ networks and security applications (electro-medical).

The SENTINEL 5 PLUS series includes the 6-6.5-8-10kVA single/single-phase and three/single-phase models and uses double conversion on-line technology (VFI). The load is powered continuously by the inverter with an EMI filtered, stabilised and regulated sinewave supply. The input and output

EMI filters considerably increase the immunity of the load to mains disturbances and surges, even on bypass.

Additional battery extension packs allow the standard battery runtime to be extended up to several hours.

HIGH RELIABILITY

• Full microprocessor control with nobreak static and manual by-pass.

LOW POWER CONSUMPTION

To increase efficiency up to 98%:

• Economy Mode: uses Line Interactive

VI technology to power less critical loads from the mains supply for certain periods. The function can be set from the front panel keypad or remotely using software;

• Smart Active: if the mains supply is out of range, the UPS will power the load from the inverter as an On-line UPS.

When the mains supply returns to within range again, the UPS will monitor this for a certain period before selecting Line Interactive operation.

SIMPLE TO INSTALL

• Capability to connect to a single or three phase mains supply

• Output terminal block + 2 IEC outlets for powering local equipment

(computers, modems and notebooks)

• Easy to position (integrated castors)

HIGH RELIABILITY BATTERIES

• Built-in automatic and manual battery test feature.

LOW IMPACT ON MAINS

• Power factor correction with sinusoidal input to ensure a low impact on the mains supply (UPS input power factor, close to 1) for the single-phase/singlephase series.

48

OTHER CHARACTERISTICS

• Reliable, filtered, stabilised and regulated sinewave output (double conversion on-line technology VFI according to EN62040-3 specifications) with filters for atmospheric disturbance suppression

• High level diagnostics: states, measurements and alarms available from the built-in LCD

• Very low noise level <40dBA

• Auto restart on mains return

(programmable via software)

• Standby/Off: for security applications like emergency lighting where the

UPS is switched on but the loads are powered through the bypass supply.

When the mains fails or falls outside a preset range the inverter automatically powers the load

• Back feed protection as standard: to avoid energy feeding back into the mains supply

ADVANCED COMMUNICATION

• Compatible with PowerNetGuard for remote maintenance

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME, NT

4.0, 2000, XP, Vista and 2003 server;

Mac OS X, Linux, Novell and most popular Unix operating systems.

• The UPS is supplied with a communications cable for ‘Plug and

Play’ PC connection

• RS232 serial port (double serial port optional)

• Rear panel IEC socket for supplying local loads

• EPO (Emergency Power Off) contact for remote UPS shut-down

• Interface card slot

• Microsoft certification

APPLICATIONS

• Local Area Networks (LAN)

• Data Centers

• Servers

• Industrial PLCs

• Cash registers

• Electromedical devices

• Emergency devices (lights/alarms)

• Telecommunication devices

• e-Business (Servers, Farms,

ISP/ASP/POP)

OPTIONS

Extended runtime solutions with/without battery charger

Isolation transformer box

2-YEAR WARRANTY

Display of the UPS internal temperature.

Display of the load applied to the UPS.

Display of the remaining battery backup time and battery charge percentage.

49

Sentinel 5 Plus

Technical data

Models

Power

S5P-6000

6000VA/4200W

S5P-6500

6500VA/4600W

S5P-8000

8000VA/5600W

S5P-10000

10000VA/7000W

Input

Rated voltage

Minimum voltage without battery intervention

Rated frequency

By pass

Voltage range

Frequency range

S5P-6000

230 Vac single-phase

S5P-6500 S5P-8000 S5P-10000

230 Vac single-phase or 400 Vac three-phase +N

170 Vac @ load 100% 140 Vac @ load 50%

50/60 Hz ± 5Hz

S5P-6000 S5P-6500 S5P-8000 S5P-10000

180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)

Selected frequency ±5Hz

S5P-6000 S5P-10000 Batteries

Recharge time

Output

Rated voltage

Static variation

Dynamic variation

Waveform

Voltage distortion with linear load

Voltage distortion with non-linear load

Frequency

Crest factor

Overload capacity

100% < Load < 125%

125% ≤ Load < 150%

Load ≥ 150%

S5P-6000

S5P-6000

S5P-6500

6 - 8 h

S5P-8000

S5P-6500 S5P-8000

220 - 230 - 240 Vac selectable

± 1 %

≤ 5% in 20 ms

Sinewave

< 2%

< 5%

50/60 Hz selectable or auto sensing

3 : 1

S5P-6500

2’

30 s

0.5 s

S5P-8000

S5P-10000

S5P-10000

50

Sentinel 5 Plus

System

Weight (kg)

Dimensions (wdh) (mm)

Efficiency

Line-interactive/Smart Active Efficiency

Operating temperature

Humidity

Protection

Compliance

Communication

Colour

Noise

Details

ON/OFF switch communication interface slot

IEC plugs

Bypass fuse holder

(SWBYP)

Output switch

(SWOUT)

Maintenance bypass

(SWMB)

S5P-6000

100

283x805x585

92%

S5P-6500

133

S5P-8000

134

S5P-10000

135

283x805x735

91% Single-phase Input 92% Three-phase Input

98%

O °C / +40 °C

< 95% non condensing

Overload - short-circuit - overvoltage - undervoltage - temperature - low battery

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

RS232 + remote contacts + communication interface slot

Dark grey (RAL 7016)

<40 dBA at 1 m

Serial interface port

Remote contacts connectors

Emergency Power

Off (EPO)

Battery fuse holders

(SWBT)

Input switch (SWIN)

51

Flexus

The FLEXUS series is suitable for protecting information and telecommunications systems, information networks and critical systems in general, where the risks connected with a power supply of poor quality energy could put the continuity of activities and services at risk, entailing high costs.

Flexus series is available in 10-12-15-

20kVA three-phase or single-phase input and single-phase output models and 10-

12-15-20-30-40kVA three-phase input and output models with double conversion online technology according to the VFI-SS-111 classification, as defined by IEC EN 62040-3 standard.

Flexus has been designed and produced with state-of-the-art technologies and components, in order to guarantee maximum protection for the users powered, no impact on the supply mains and energy saving.

ZERO IMPACT SOURCE

Thanks to the technology used, Flexus can solve any problem of connection in installations where the supply mains has a limited installed power, where the UPS is also powered by a generator set or where there are problems of compatibility with loads that generate current harmonics; Flexus has indeed zero impact on the power supply source, be it the mains or a generator set:

• low distortion of input current – less than 3%

• input power factor 0.99

• power walk-in function that guarantees progressive start-up of the rectifier

• delayed switching-on function, to restart the rectifier igniters when the mains returns, in case of systems with various UPS

The Flexus also acts a filter and phaseshift mechanism in respect of the supply mains ahead of the UPS, since it removes the harmonic components and the reactive power generated by the users powered.

BATTERY CARE SYSTEM

Management of the batteries is fundamental to guaranteeing operation of the power supply unit under emergency conditions. The Battery Care System consists of a series of functions and performances that permit management of the storage batteries in such a way as to obtain the best performance and to extend battery life.

Battery recharge: Flexus is suitable for working with hermetically sealed (VRLA),

AGM and GEL lead batteries, and openvase and Nickel-Cadmium batteries.

According to the type of battery, various recharge methods are available.

• One-level recharge, typical for the most commonly used VRLA AGM batteries

• Two voltage levels recharge according the IU characteristic

• Charge block system to reduce consumption of the electrolyte and further extend the life of VRLA batteries.

Display

52

FLEXIBILITY

Flexus can be used for a wide range of applications, thanks to its characteristics of configuration flexibility, accessories and options available and performance levels:

• suitable for powering capacitive loads such as blade servers, without any reduction of the active power, from 0.9

leading to 0.9 lagging (3Ph output) and from 0,8 leading to 0,8 lagging (1Ph output)

• modes of operation: On Line, Eco,

Smart Active and Stand By Off

• frequency converter mode

• Power Share sockets that can be configured in order to maintain the back-up time for the most critical loads or to be activated only when the mains goes down

• Cold Start to switch on the UPS including when the supply mains is off

• battery cabinets of various dimensions and capacity, for longer back-up times

• option to connect a temperature sensor for external battery cabinets, for recharge voltage compensation

• additional battery chargers to optimize recharge times

• optional double input of the supply mains

• isolation transformers to modify the neutral arrangements, in case of separate sources or for galvanic isolation between input and output

ADVANCED COMMUNICATION

Flexus is equipped with a graphic display that provides information, measures, states and alarms regarding the UPS in

5 different languages.

• Advanced multiplatform communication, for all operating systems and network environments:

Watch&Save 3000 monitoring and shutdown software included with

SNMP agent

• Compatible with PowerNetGuard for the remote assistance service

RS232 or USB serial port

-1

Leading Cos ϕ

(capacitive loads) cos ϕ

0,9

Flexus Output Power

100% kW

1,00 cos ϕ

1 cos ϕ

0,9

0,75

Lagging Cos ϕ

(inductive loads)

100% kVA

0,50

UPS @ Cos ϕ

0,9

Es. 20kVA - 18kW !!!

0,25

-0,8 -0,6 -0,4 -0,2 0

Reactive Power

0,2 0,4 0,6 0,8 1

• 3 slots for the installation of optional communication accessories.

• REPO (Remote Emergency Power Off)

• Input for synchronization from an external source

• Graphic mimic panel display for remote connection

SUITABLE FOR

APPLICATIONS

54

EXPANDABILITY

Flexus can work in parallel up to 6 units to increase the power availability and the reliability. The single module or the parallel system can be expanded at any time to suit additional power requirements without influencing the initial investment. Thanks to the peculiarity of the “Hot System

Expansion” feature, the new UPS can be connected in parallel while the other units are on-line and supplying regular power to the load. When the UPS is connected it will be updated automatically from the other UPS on line.

To increase the flexibility of the Flexus system, on each unit a second input is available for a synchronization with the external source other than the bypass mains. The parallel configuration may be with single or common battery.

Example of parallel card assembly

55

Flexus

Three-phase or single-phase input

Single-phase output

Models

Power (kVA)

Input

Rated voltage

Rated frequency

Frequency tolerance

Power factor at full load

Current distortion

By pass

Rated voltage

Number of phases

Voltage tolerance

Rated frequency

Frequency tolerance

Output

Rated power (kVA)

Active power with load PF from 0,8 cap. to 0,8 ind.

Output power factor

Number of phases

Rated voltage

Static variation

Dynamic variation

Crest factor (Ipeak/Irms)

Voltage distortion

Frequency

Frequency stability on battery mode

Overload at Pf 0.8

Batteries

Type

Recharge time

Technical data

FM 10

10

FM 12

12

FM 15

15

FM 20

20

FM 10 FM 12 FM 15

380- 400-415 Vac three-phase with Neutral / 220-230-240Vac single-phase

FM 20

50/60 Hz

40 ÷ 72 Hz

0.99 Pf

THDI ≤ 3%

FM 10 FM 20 FM 12 FM 15

220-230-240 Vac

1

180 ÷ 264V (selectable)

50 or 60 Hz (selectable)

±5 (selectable)

FM 10

10

8

FM 12

12

9.6

FM 15

15

12

0.8

1

220-230-240 Vac (selectable)

± 1%

± 3%

3 : 1

≤ 1% with linear load / ≤ 3% with non-linear load

50/60 Hz

0.01%

110% for 10 minutes, 133% for 1 minute, 150% for 5 seconds

FM 20

20

16

FM 10 FM 12

VRLA AGM/GEL

6 h

FM 15 FM 20

56

Flexus

Three-phase or single-phase input

Single-phase output

System

Weight with internal batteries (kg)

Dimensions (wdh) (mm)

Communication

Operating temperature

Relative humidity

Colour

Noise

Protection rating

Efficiency

Compliance

FM 10

180

FM 12

182

320x840x930

3 communication interface slots/RS232/USB

O°C - 40°C

FM 15

190

90% non condensing

Dark grey (RAL 7016)

< 52 dBA at 1 m

IP20

FM 20

195

≥ 94% in On-line mode, ≥ 98% in Economy mode

European Directives: L V 73/23/EC and 93/68/EC Low voltage directive

EMC 2004/108/EC and 89/336/EC Electromagnetic compatibility directive

Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2

Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111

Details

Powershare sockets

Remote contacts connectors

USB port

FM 10-12-15-20

Communication interface slot

Parallel board

Serial interface port

57

Flexus

Three-phase input

Three-phase output

Models

Power (kVA)

Technical data

FT 10

10

FT 10

FT 12

12

FT 15

15

FT 20

20

FT30

30

FT 12 FT 15 FT 20

380- 400-415 Vac three-phase +N

50/60 Hz

40 ÷ 72 Hz

0.99 Pf

THDI ≤ 3%

FT30

FT40

40

FT40 input

Rated voltage

Rated frequency

Frequency tolerance

Power factor at full load

Current distortion

By pass

Rated voltage

Number of phases

Voltage tolerance

Rated frequency

Frequency tolerance

FT 10 FT 12 FT 15 FT 20

380-400-415 Vac three-phase +N

3 + N

180 ÷ 264V (selectable)

50 or 60 Hz (selectable)

±5 (selectable)

FT30 FT40

Output

Rated power (kVA)

Active power with load PF from 0,9 cap. to 0,9 ind.

Output power factor

Number of phases

Rated voltage

Static variation

Dynamic variation

Crest factor (Ipeak/Irms)

Voltage distortion

Frequency

Frequency stability on battery mode

Overload at Pf 0.8

FT 10

10

FT 12

12

FT 15

15

FT 20

20

FT30

30

0.9

3 + N

380-400-415 Vac (selectable)

± 1%

± 3%

3 : 1

≤ 1% with linear load / ≤ 3% with non-linear load

50/60 Hz

0.01%

115% infinite, 125% for 10 minutes, 150% for 1 minute, 168% for 5 seconds

FT40

40

Batteries

Type

Recharge time

FT 10 FT 12 FT 15 FT 20

VRLA AGM/GEL

6 h

FT30 FT40

58

Flexus

Three-phase input

Three-phase output

System

Weight with internal batteries (kg)

Dimensions (wdh) (mm)

Communication

Operating temperature

Relative humidity

Colour

Noise

Protection rating

Efficiency

Compliance

FT 10

180

FT 12

182

FT 15

190

FT 20

195

320x840x930

3 communication interface slots/RS232/USB

FT30

480

440x850x1600

FT40

490

O°C - 40°C

90% non condensing

< 52 dBA at 1 m

Dark grey (RAL 7016)

< 48 dBA at 1 m

IP20 until 96,5% in On-line mode, until 99% in Economy mode

European Directives: L V 73/23/EC and 93/68/EC Low voltage directive

EMC 2004/108/EC and 89/336/EC Electromagnetic compatibility directive

Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2

Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111

Details

Powershare sockets

Remote contacts connectors

USB port

FT 10-12-15-20

Communication interface slot

Parallel board

Serial interface port

REPO - AS400 - USB - RS232

Connectors

Input protection

Powershare sockets

Battery fuse

FT 30-40

Input switch

(swin)

Bypass fuse holder

(SWBYP)

Slot for rel

Interface slot

Parallel connectors

(optional)

Output switch

(swout)

Maintenance bypass (SWMB)

59

Sentry Multistandard

SUITABLE FOR

APPLICATIONS

SENTRY MULTISTANDARD provides maximum protection for critical data processing networks and security applications, thanks to its advanced design, selectable operating modes and communications capabilities. Operating modes include: On-line, Economy,

Smart-Active, Standby/Off and Voltage

Stabilisation. Standard communications features include a front panel LCD with

128 potential messages, RS232 interfaces, EPO input, communications interface slot and Watch&Save 3000 management software.

The SENTRY MULTISTANDARD series includes 10-15-20kVA single/singlephase, three/single-phase and 10-15-

20-30-40-60-80 kVA three-phase models, and uses on-line double conversion technology (VFI). The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output filters considerably increase the immunity of the load to mains disturbances and surges, even on bypass.

LOW POWER CONSUMPTION

• On-line Mode: up to 92% efficiency can be achieved due to the use of

IGBT technology, increasing to 98% in one of the other operating modes

• Economy Mode: uses Line Interactive

(VI) technology to power less critical loads from the mains supply for certain periods

• Smart Active: if the mains supply is out of range, the UPS will power the load from the inverter as an On-line UPS.

When the mains supply returns to within range again, the UPS will monitor this for a certain period before selecting

Line Interactive operation.

10/30 kVA

10/30 kVA Battery cabinet

60

Fig. 1 – Block diagram UPS in parallel up to 8 units

SIMPLE TO INSTALL

• Option to connect the UPS to singlephase or three phase mains supplies

(SM series)

• Panel adjustment to offset voltage drop down long cable runs

MAXIMUM RELIABILITY

AND AVAILABILITY

• Connect up to 8 units in parallel for power capacity or redundancy

HIGH LEVEL BATTERY RELIABILITY

• Automatic battery test

• Recharge compensated for temperature

• Automatic or manual rapid charge

(boost) – duration progammable

MAINTENANCE SIMPLICITY = LOW

MTTR

For the 40 to 80 kVA models, open the door and remove the protective panel

(standards requirement) and the power components - mounted on a sliding tray

- can be pulled out to provide easy access to all the electrical and electronic components for maintenance and repair work. This particular feature means that the MTTR (Mean Time To Repair) is much lower than traditional UPS designs with less easily reached assemblies, which has longer times due to the compact size of the products and difficult access to the parts.

A large amount of maintenance information is available from the front mimic panel and LCD. In addition system operating parameters are software configurable via a local PC to allow new functions to be added or adjustments made to operating specifications.

61

SENSITIVE SUPPLY COMPATIBLE

For power supply sources that are particularly sensitive to harmonics

(generator sets or transformers of low power with respect to that of the UPS) it is often a good idea to take action to limit the harmonics injected back into the supply by the UPS.

SENTRY MULTISTANDARD series is also available with built-in active filter using high frequency Isolated Gate Bipolar

(IGBT) Technology with Digital Signal

Processor (DSP) control. The Active

Filter helps to reduce harmonics generated by the UPS into the supply which could disrupt the operation of downstream generators and transformers whose rating is closely matched to that of UPS.

advanced technology

The active filter reduces harmonic distortion of the phase and neutral currents. The Digital Signal Processor

(DSP) and the “current mode” instantly control and monitor the input current to maintain a perfect sinewave with less than 4% harmonic distortion

maximum efficiency

Thanks to the active filter Sentry

Multistandard systems have low input distortion even at low loads and their overall efficiency is not affected by generator frequency variations or line impedance

reduction of neutral current

The active filter reduces the input neutrals current by up to 3.5 times their nominal rating to help avoid oversizing input protections and conductors

maximum reliability

Sentry Multistandard systems are extremely reliable. Overall UPS performance is unaffected should the harmonic filter fail

excellent capabilities

Input distortion: (THDi) less than 4%

Input power factor: >0.99

Efficiency: up to 93%

Sentry Multistandard can also be supplied without the Active Filter for installations less sensitive to current harmonics.

OTHER CHARACTERISTICS

• Sentry Multistandard is able to supply loads with power factor from 0,8 capacitive to 0,8 inductive without derating the active power (KW)

• High level diagnostics: event log with

128 messages, states, measurements and alarms - available from the built-in

LCD in several languages

• Reduced noise levels: high frequency inverter bridge

• Back feed protection standard: to avoid energy feeding back into the mains supply (in compliance with CEI

11-20; DK5600)

• Power factor correction (input power factor, close to 1)

• By pass may be deactivated to allow operation as a frequency converter (at

50 or 60 Hz)

• Emergency operation: the UPS can be set to operate only when the mains fails (for emergency lighting)

UPS input current with optional Active Filter

Sentry Multistandard with Active Filter

(internal view)

62

-1

Leading Cos ϕ (capacitive loads) cos ϕ

0,8

Multistandard Output Power cos ϕ

0,9 100% kW

1,00 cos ϕ

1 cos ϕ

0,9

0,75

Lagging Cos ϕ (inductive loads) cos ϕ

0,8

100% kVA

-0,8 -0,6 -0,4

0,50

0,25

-0,2 0

Reactive Power

0,2 0,4 0,6 0,8 1

ADVANCED COMMUNICATION

• Compatible with TeleNetGuard for remote maintenance

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME, NT

4.0, 2000, XP, Vista and 2003 server;

Mac OS X, Linux, Novell and most popular Unix operating systems

• The UPS is supplied with a communications cable for ‘Plug and

Play’ PC connection

• Double RS232 serial ports

• Network adapter slot for SNMP agent

• Emergency Power Off (EPO) shutdown input contact

• Remote control mimic panel

APPLICATIONS

• Local Area Networks (LAN)

• Data Centers

• Servers

• Industrial PLCs

• Cash registers

• Electromedical devices

• Emergency devices (lights/alarms)

• Telecommunication devices

• e-Business (Servers, Farms,

ISP/ASP/POP)

Operating status, alarms, applied load, battery charging.

Controls and settings menu.

Language selection menu.

Battery voltages, internal operating temperatures.

OPTIONS

Input isolation transformer

Active filter

LED remote status panel

LCD based remote control panel

Graphic Display remote control panel

Empty battery cabinet for prolonged runtime

Additional battery charger

Dual input mains

40/80kVA 40/80kVA

63

Sentry Multistandard

Three- / Single-phase input

Single-phase output

Input

Rated voltage

Voltage range

Frequency range

Power factor

Current harmonic distortion

By pass

Rated voltage

Number of phases

Permitted voltage range

Rated frequency

Permitted frequency range

Batteries

Type

Recharge time

Output

Rated power (kVA)

Active power with load PF from 0,8 cap. to 0,8 ind. (kW)

Number of phases

Rated voltage

Voltage regulation range

Crest factor (Ipeak/Irms)

Distortion with linear load

Static stability

Dynamic stability

Frequency

Overload

System

Weight (kg)

Dimensions (wdh) (mm)

Remote signaling

Remote controls

Communication

Operating temperature

Relative humidity

Colour

Noise

Protection degree

Efficiency

Compliance

(1) Version with Active Filter

(2) Version with single-phase input

Technical data

SM10 SM15

230 Vac single-phase or 400 Vac three-phase + N

± 20%

45 ÷ 65 Hz

> 0.99

Sinewave absorbtion THDi <4% (3Ph input) (1)

SM20

SM10 SM15

230 Vac

1

± 15% (selectable from ± 5% to ± 25%)

50/60 Hz

± 2% (selectable from ± 1% to ± 5%)

SM20

SM10 SM15

Lead, open vase acid and VRLA, AGM / GEL; NiCd

6 h

SM20

SM10

10

8

SM15

15

12/10,5 (2)

1

230 Vac

200 ÷ 243 Vac

3 : 1

2%

± 1%

± 5% in 10 ms

50 / 60 Hz selectable

110% 125% 150% of the rated current for 5 h/10’/1’

SM20

20

16/12 (2)

SM10

From 105 to 243

SM15

From 110 to 330

450x750x1200

SM20

From 125 to 345

Volt free contacts

EPO and bypass

Double RS232/C + remote contacts + communication interface slot

O °C / +40 °C

< 95% non condensing

Dark grey (RAL 7016)

<56 dBA at 1 m

IP20

> 92% in On-Line Mode, > 98% in Economy Mode/Smart Active Mode/Standby-Off Mode/AVS Mode

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

64

Sentry Multistandard

Three-phase input

Three-phase output

Technical data

Input

Rated voltage

Voltage range

Frequency range

Power factor

Current harmonic distortion

By pass

Rated voltage

Number of phases

Permitted voltage range

Rated frequency

Permitted frequency range

Batteries

Type

Recharge time

Output

Rated power (kVA)

Active power with load PF from 0,8 cap. to 0,8 ind. (kW)

Number of phases

Rated voltage

Voltage regulation range

Crest factor (Ipeak/Irms)

Distortion with linear load

Static stability

Dynamic stability

Frequency

Overload

System

Weight (kg)

Dimensions (wdh) (mm)

Remote signaling

Remote controls

Communication

Operating temperature

Relative humidity

Colour

Noise

Protection degree

Efficiency

Compliance

ST10

ST10

ST15

ST15

ST20 ST30

400 Vac three-phase + N

ST40

± 20%

45 ÷ 65 Hz

> 0.99

Sinewave absorbtion THDi <4% (3Ph input) (1)

ST20 ST30

400 Vac

ST40

3 + N

± 15% (selectable from ± 5% to ± 25%)

50/60 Hz

± 2% (selectable from ± 1% to ± 5%)

ST60

ST60

ST80

ST80

ST10

ST10

10

8

ST15 ST20 ST30 ST40

Lead, open vase acid and VRLA, AGM / GEL; NiCd

6 h

ST60

4-8 h

ST15

15

12

ST20

20

16

ST30

30

24

ST40

40

32

3 + N

380 - 400 - 415 Vac selectable

346 ÷ 422 Vac

3 : 1

2%

± 1%

± 5% in 10 ms

50 / 60 Hz selectable

110%125% 150% of the rated current for 5h/10’/1’

ST60

60

48

ST80

ST80

80

64

ST10 ST15 ST20 ST30

From 110 to 258 From 115 to 335 From 130 to 350 From 144 to 370

450x750x1200

Volt free contacts

ST40

160

ST60

180

500x740x1400

EPO and bypass

Double RS232/C + remote contacts + communication interface slot

O °C / +40 °C

<95% non condensing

ST80

192

Dark grey (RAL 7016)

<56 dBA at 1 m <60 dBA at 1 m

IP20

> 92% in On-Line Mode, > 98% in Economy Mode/Smart Active Mode/Standby-Off Mode/AVS Mode

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

65

Sentry HPS

SENTRY HPS HM/HT provides maximum protection for vital ‘missioncritical’ networks, security applications

(electro-medical) and industrial applications thanks to its outstanding mechanical and electrical design.

The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges.

The SENTRY HPS HM/HT series uses on-line double conversion technology

(VFI) with an isolation transformer on the inverter output.

SENTRY HPS HM/HT is supplied with

Watch&Save 3000 software as standard and can be remotely monitored using the PowerNetGuard system from anywhere in the world.

Additional battery extension packs allow the standard battery runtime to be extended up to several hours.

MINIMUM IMPACT ON SUPPLIES -

EASY SOURSE

Input current distortion <4% for the

Sentry HPS with filter with sinusoidal absorption to remove the risk of resonance with other input supply users or phase shift capacitor sets. The absorbed current distortion is independent of input supply parameters such as impedance.

This enables Sentry HPS to deliver maximum performance levels regardless of the installation environment. With these input features

Sentry HPS can achieve significant savings in terms of sizing and power supply sources - isolation transformers and generators over less sophisticated power systems.

MAXIMUM BATTERY CARE

• Battery deep discharge protection

• Temperature compensating charger

• Built-in automatic and manual battery test feature

SIMPLE TO INSTALL

• Capability to install the UPS into any distribution system (neutral not required on rectifier input)

• Capability to separate the rectifier/bypass power networks and to power these from two separate sources, without Galvanic isolation

(necessary on UPS without an output transformer)

HIGH RELIABILITY

• Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications

(lighting, drives and industrial processes) and an isolation transformer on the inverter output

• Full microprocessor control with no-break static and manual bypasses

• IGBT technology

66

OTHER CHARACTERISTICS

• 0.8 power factor makes Sentry HPS suitable for powering ICT and industrial loads

• High level diagnostics: event log with

128 messages, states, measurements and alarms - available from the built-in

LCD in several languages

• BACK FEED protection: to avoid energy feeding back into the mains supply should a fault occur

OPTIONS

• Isolation transformers

• Various lead acid battery types including 5 year, 10 year and 20 year design life, VRLA, NiCad options and runtimes up to several hours

• Communications software

• Solutions for low input current distortion

• Closed loop parallel kit option (to be ordered with the unit)

SPECIFIC SOLUTIONS

The UPS can be adapted to your requirements. Please contact AROS

S.r.l. to discuss specific applications and options.

MAXIMUM RELIABILITY

AND AVAILABILITY

• Connect up to 8 units in parallel or

N+1 redundancy, even of different power ratings.

The UPS continue to work in parallel even if one of the interconnecting communication cables is disconnected (CLOSED LOOP).

LOW CONSUMPTION LEVELS

• Sentry HPS can achieve efficiencies

>98% thanks to a selectable

Economy Mode which can be used in stable electrical environments to provide power supply continuity should the mains fail.

ADVANCED COMMUNICATION

• Compatible with TeleNetGuard for remote maintenance

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME,

NT 4.0,2000, XP, Vista and 2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems

• The UPS is supplied with a cable for direct connection to the PC

(Plug and Play)

• RS232 double serial port

• Installation slot for an Emergency

Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency.

• Generator interface: enables desynchronisation of the

UPS output from a generator supply which may be subject to phase and frequency variations.

The interface also enables more economic use of the battery charger.

NO-BREAK POWER ARCHITECTURES

The Sentry HPS range features a wide range of modules and configurations that can be manufactured into one complete system to solve your power problems. Each system is therefore unique and we ask that you consult our engineers for your specific application.

APPLICATIONS

• Servers

• Local Area Network (LAN)

• Data centers

• Telecommunications

• Industrial equipment

• Electro-medical equipment

67

Sentry HPS

Fig 1- Bock diagram UPS in parallel up to 8 units

EXPANDABILITY

The units can be connected in parallel up to 8 units to increase power availability or redundancy.

The single module or the system can be expanded any time to suit power requirements without influencing the initial investment.

Thanks to the peculiarity of the “Hot

System Expansion” feature, the additional unit can be connected in parallel while the other units are on-line and supplying regular power to the load. The new UPS is on-line and will be set up automatically.

80 kVA

68

Sentry HPS

Three-phase input

Single-phase output

Models

Power (kVA)

Input

Rated voltage

Voltage range

Frequency range

Power factor

Current harmonic distortion

Soft start

By pass

Rated voltage

Permitted voltage range

Rated frequency

Permitted frequency range

Standard features

Batteries

Type

Maximum recharge current (A)

AC ripple voltage

Inverter output

Rated power (kVA)

Active power (kW)

Number of phases

Rated voltage (V)

Regulation of the output voltage

Crest factor (Ipeak/Irms)

Static stability

Dynamic stability

Frequency

Overload

Frequency stability

System

Weight (kg)

Dimensions (wdh) (mm)

Remote signaling

Remote controls

Communication

Operating temperature

Relative humidity

Colour

Noise

Protection degree

Efficiency

Compliance

Internal batteries

Technical data

HM8

8

HM8

HM10

10

HM15

15

HM20 HM30

20 30

HM40

40

HM60

60

HM80 HM100

80 100

HM10 HM15 HM20 HM30 HM40

400 Vac three-phase

± 20%

45 ÷ 65 Hz

> 0.92 with harmonic filter

< 5% with harmonic filter

0-100% in 10”

HM60 HM80 HM100

HM8

HM8

HM10 HM15 HM20 HM30 HM40

230 Vac single-phase

HM60

± 15% (selectable from ± 10% to ± 25% from front panel)

50/60 Hz

± 2% (selectable from ± 1% to ± 5% from front panel)

BackFeed protection; split bypass line

HM80 HM100

HM10 HM15 HM20 HM30 HM40 HM60

Maintenance-free lead-acid VRLA AGM / GEL; NiCd

0,2xC10

<1%

HM80 HM100

HM8

8

6.4

HM10

10

8

HM15 HM20 HM30 HM40 HM60

15

12

20

16

30

24

1

230 Vac single-phase

40

32

60

48

220 ÷ 244 Vac phase/neutral (from control panel)

3 : 1

± 1%

± 5%

50/60 Hz configurable

110% 125% 150% of the rated current for 5h/10’/1’

± 0,05% on mains failure

± 2% (selectable from ± 1% to ± 5%) with mains supply present

HM80 HM100

80

64

100

80

HM8

From 190 to 460

HM10

From 200 to 470

HM15

From 220 to 490

HM20 HM30

From 230 to 500

555x720x1200

290

HM40

340

HM60

440

HM80

520

800x740x1400

Volt free contacts

EPO and Bypass

RS232 + remote contacts

O °C / +40 °C

< 95% non condensing

Light grey (RAL 7035)

54 dBA at 1 m

>91%

Yes

60 dBA at 1 m 65 dBA at 1 m

IP20

>92%

Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

Yes Yes Yes No No No No

HM100

650

1070x

740x1400

No

70

Sentry HPS

Three-phase input

Three-phase output

Models

Power (kVA)

Input

Rated voltage

Voltage range

Frequency range

Power factor

Current harmonic distortion

Soft start

By pass

Rated voltage

Permitted voltage range

Rated frequency

Permitted frequency range

Standard features

Batteries

Type

Maximum recharge current (A)

AC ripple voltage

Inverter output

Rated power (kVA)

Active power (kW)

Number of phases

Rated voltage

Regulation of the output voltage

Crest factor (Ipeak/Irms)

Static stability

Dynamic stability

Frequency

Overload

Frequency stability

System

Weight (kg)

Dimensions (wdh) (mm)

Remote signaling

Remote controls

Communication

Operating temperature

Relative humidity

Colour

Noise

Protection degree

Efficiency

Compliance

Internal batteries

HT10

10

HT10

HT10

HT10

HT15

15

HT15

HT20

20

HT30

30

HT40

40

HT20 HT30

400 Vac three-phase

± 20%

45 ÷ 65 Hz

> 0.9 with harmonic filter

< 5% with harmonic filter

0-100% in 10”

HT40

HT60

60

HT60

HT15 HT20 HT30

400 Vac three-phase

HT40

± 15% (selectable from ± 10% to ± 25% from front panel)

50/60 Hz

± 2% (selectable from ± 1% to ± 5% from front panel)

BackFeed protection; split bypass line

HT60

HT15 HT20 HT30 HT40

Maintenance-free lead-acid VRLA AGM/GEL; NiCd

0,2xC10

<1%

HT60

HT80

80

HT80

HT80

HT80

HT10

10

8

HT15

15

12

HT20 HT30 HT40

20

16

30

24

3 + N

400 Vac

40

32

348 ÷ 424 Vac phase/neutral (from control panel)

3 : 1

± 1%

± 5%

50/60 Hz configurable

110% 125% 150% of the rated current for 5h/10’/1’

± 0,05% on mains failure;

± 2% (selectable from ± 1% to ± 5%) with mains supply present

HT60

60

48

HT80

80

64

HT10 HT15 HT20 HT30 HT40 HT60 HT80

From 210 to 480

From 220 to 490

From 230 to 500

555x720x1200

From 282 to 552

Volt free contacts

EPO and Bypass

RS232 + remote contacts

O °C / +40 °C

330 450

800x740x1400

555

Yes

54 dBA at 1 m

< 95% non condensing

Light grey (RAL 7035)

60 dBA at 1 m

IP20

62 dBA at 1 m

> 90% > 91% > 92%

Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

Yes Yes Yes No No No

71

Sentry MPS

Three-phase output

QUALITY POWER SUPPLY

SENTRY MPS is an on-line double conversion UPS (VFI SS 111 in accordance with IEC EN 62040-3) with a transformer isolated inverter. With a compact footprint and high power quality output, SENTRY MPS is designed to protect “mission critical” applications including data processing, telecommunications, industrial processes, security and electro-medical systems.

SENTRY MPS is available from 100 to

800kVA in two or four versions each with different harmonic distortion and power factor for better matching the market requirements:

• MPS (100 to 200kVA only),

• MPS LH (100 to 200kVA only),

• MPS Plus,

• MPS Sinus.

BATTERY CARE SYSTEM: MAXIMUM

LIFETIME POTENTIAL

Traditionally, when a mains supply is present the UPS charges its batteries.

Battery power is used for the inverter should the input supply fail. Efficient battery management and care is therefore essential to the overall performance of the UPS in an emergency. The SENTRY MPS Battery

Care System consists of a range of features designed to provide optimum performance and enhanced operating life:

• Dual level charging regime to optimise recharge currents and lower recharge times;

• Temperature compensation and deep discharge protection to reduce overall battery aging;

• Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries;

• Predictive battery testing to spot potential battery deterioration and failure.

SENTRY MPS is also compatible with different battery technologies: openvase lead acid and AGM and Gel

VRLA, NiCd.

MINIMUM INPACT ON SUPPLIES -

EASY SOURCE

SENTRY MPS technology removes the problems of over sizing downstream power sources, whilst improving load power factors and current harmonics.

The UPS features the latest input current absorption techniques including progressive rectifier start-up and the option to reduce battery charging currents. These features make SENTRY

MPS one of the most generator compatible and environmentally friendly

UPS available.

72

FLEXIBILITY

SENTRY MPS is suitable for a wide range of applications including IT and the most demanding industrial environments suitable for power capacitive loads such as blade servers, without any reduction of the active power, from 0,8 lagging to

0,9 leading. With a broad of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing users. Using the

AROS UPS Group Synchroniser (USG) and Parallel Systems Joiner (PSJ) sophisticated inter group parallel and redundant systems can be achieved to provide the highest possible levels of resilience and availability.

EASY INSTALLATION

SENTRY MPS has a small footprint

(only 0,64 sqm for 200kVA and 1,63 sqm for 400kVA). Front access to internal assemblies and top panel ventilation make space allocation within confined data processing or plant rooms easy. SENTRY MPS can be placed against a wall as there is no requirement for rear or side panel access for maintenance or ventilation.

-1

Leading Cos ϕ

(capacitive loads) cos ϕ 0,9 cos ϕ 0,8

MPS Output Power

100% kW

1,00 cos ϕ 1 cos ϕ 0,9

0,75

Lagging Cos ϕ

(inductive loads) cos ϕ 0,8 cos ϕ 0,7 cos ϕ 0,6

100% kVA

-0,8 -0,6 -0,4

0,50

0,25

-0,2 0

Reactive Power

0,2 0,4 0,6 0,8 1 1,2

FREQUENCY CONVERTER OPERATION

The standard UPS with 400V operating voltage can be configured on site as 50 to 60Hz frequency converter and viceversa, with or without connection to the battery. On request units 400V-50Hz input and 440V-60Hz output are also available.

For the frequency converter range

400Hz output see page 82.

ADVANCED COMMUNICATION

• Compatible with TeleNetGuard for remote maintenance

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-down software included, with

SNMP agent, for Windows 9x, ME, NT

4.0, 2000, XP, Vista and 2003 server;

Mac OS X, Linux, Novell and most popular Unix operating systems

• The UPS is supplied with a cable for direct connection to the PC (Plug and Play)

• RS232 double serial port

• Installation slot for an Emergency

Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency.

• Remote mimic panel (LED or LCD)

APPLICATIONS

• Servers

• Local Area Network (LAN)

• Data centers

• Telecommunications

• Industrial equipment

• Electro-medical equipment

OPTIONS

Input Isolation transformer

UPS Group Syncroniser (UGS)

Parallel System Joiner (PSJ)

Interface for generator

LED remote status panel

LCD based remote control panel

Graphic Display Remote panel

Empty battery cabinets for prolonged runtime

73

Fig 1- Bock diagram UPS in parallel up to 8 units

EXPANDABILITY

The units can be connected in parallel up to 8 units to increase power availability or redundancy.

The single module or the system can be expanded any time to suit power requirements without influencing the initial investment.

Thanks to the peculiarity of the “Hot

System Expansion” feature, the additional unit can be connected in parallel while the other units are on-line and supplying regular power to the load. The new UPS is on-line and will be set up automatically.

200kVA

74

DUAL BUS SYSTEM

The Dual Bus System powers the priority loads from two independent sources.

This configuration increases the redundancy and availability level of a multi-module configuration. Each bus may consist of a single module or up to

8 modules in parallel, kept in synchro by the UGS (UPS Group Synchroniser).

Fig. 2 - Dual bus System

DYNAMIC DUAL BUS SYSTEM

Two independent systems set in Dual

Bus Configuration can be merged together at any time for system expansion or maintenance thanks to the PSJ (Parallel System Joiner) option.

This provides a lot of flexibility in your installation in case of maintenance or when it is necessary to change the redundancy level of both systems.

Fig. 3 - Dynamic Dual Bus System

75

Sentry MPS

Three-phase input

Three-phase output

Models

Power (kVA)

Input

Nominal voltage

Voltage tolerance

Frequency

Power factor

Current harmonic distortion

Soft start

Permitted frequency tolerance

Standard features

Battery

Type

AC ripple current

Temperature compensation

Output

Rated power (kVA)

Active power with load PF from 0,9 cap. to 0,8 ind. (kW)

Number of phases

Nominal voltage

Static stability

Dynamic stability

Voltage distortion with linear load

Voltage distortion with non linear load

Frequency

Waveform

Crest factor (Ipeak/Ipms)

Overload

System

Remote signalling

Remote commands

Communication

Efficiency

Dimensions (wdh) (mm)

Weight (kg)

Noise level

Operating temperature

Relative humidity

Protection degree

Colour

Compliance

Classification as per IEC 62040-3

Technical data

MPS 100

100

MPS 120

120

MPS 160

160

MPS 200

200

MPS 100 MPS 120 MPS 160

380 - 400 - 415 Vac three-phase

400 V ± 20%

45 ÷ 65 Hz

>0.95 in the Sinus version

<3% in the Sinus version

0 ÷ 100% in 30’’ configurable

± 2% (selectable from ± 1% to ± 5% from the front panel)

Back Feed protection; separable bypass line

MPS 200

MPS 100 MPS 200

MPS 100

100

80

MPS 120 MPS 160

Lead, open vase acid and VRLA, AGM / GEL; NiCd

Zero

-0,5 Vx °C

MPS 120

120

96

MPS 160

160

128

3 + N

380 - 400 - 415Vac three-phase + N

± 1%

± 5% in 10 msec.

≤1%

≤3%

50 or 60 Hz configurable

Sinusoidal

3:1

110% for 60’; 125% for 10’; 150% for 1’

MPS 200

200

160

MPS 100 MPS 120 MPS 160

Voltage-free contacts (configurable)

MPS 200

EPO and bypass

Double RS232 + remote contacts + 2 communication interface slots

640

Up to 94%

800x800x1900 (base version)

650

63 ÷ 68 dBA a 1 m

770 810

0 °C / +40 °C

<95% non condensing

IP20

Light grey (RAL 7035)

Directives EEC 73/23 - 93/68 - 89/336

Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3

(Voltage Frequency Independent) VFI - SS - 111

76

Sentry MPS

Three-phase input

Three-phase output

Models

Power (kVA)

Input

Nominal voltage

Voltage tolerance

Frequency

Power factor

Current harmonic distortion

Soft start

Permitted frequency tolerance

Standard features

Battery

Type

AC ripple current

Temperature compensation

Output

Rated power (kVA)

Active power with load PF from 0,9 cap. to 0,8 ind. (kW)

Number of phases

Nominal voltage

Static stability

Dynamic stability

Voltage distortion with linear load

Voltage distortion with non linear load

Frequency

Waveform

Crest factor (Ipeak/Ipms)

Overload

System

Remote signalling

Remote commands

Communication

Efficiency

Dimensions (wdh) (mm)

Weight (kg)

Noise level

Operating temperature

Relative humidity

Protection degree

Colour

Compliance

Classification as per IEC 62040-3

Technical data

MPS 250

250

MPS 300

300

MPS 400

400

MPS 250 MPS 300

380 - 400 - 415 Vac three-phase

400 V ± 20%

45 ÷ 65 Hz

>0.95 in the Sinus version

MPS 400

<3% in the Sinus version

0 ÷ 100% in 30’’ configurable

± 2% (selectable from ± 1% to ± 5% from the front panel)

Back Feed protection; separable bypass line

MPS 250 MPS 300

Lead, open vase acid and VRLA, AGM / GEL; NiCd

Zero

-0,5 Vx °C

MPS 400

MPS 250

250

200

MPS 300

300

240

3 + N

380 - 400 - 415 Vac three-phase + N

± 1%

± 5% in 10 msec.

≤1%

≤3%

50 or 60 Hz configurable

Sinusoidal

3:1

110% for 60’; 125% for 10’; 150% for 1’

MPS 400

400

320

MPS 250 MPS 300

Voltage-free contacts (configurable)

MPS 400

EPO and bypass

Double RS232 + remote contacts + 2 communication interface slots

Up to 94%

1700

850x1630x1900

1770

70 dBA a 1 m

1000x1630x1900

2045

0 °C / +40 °C

<95% non condensing

IP20

Light grey (RAL 7035)

Directives EEC 73/23 - 93/68 - 89/336

Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3

(Voltage Frequency Independent) VFI - SS - 111

77

Sentry MPS

Three-phase input

Three-phase output

Models

Power (kVA)

Input

Nominal voltage

Voltage tolerance

Frequency

Power factor

Current harmonic distortion

Soft start

Permitted frequency tolerance

Standard features

Battery

Type

AC ripple current

Temperature compensation

Output

Rated power (kVA)

Active power with load PF from 0,9 cap. to 0,8 ind. (kW)

Number of phases

Nominal voltage

Static stability

Dynamic stability

Voltage distortion with linear load

Voltage distortion with non linear load

Frequency

Waveform

Crest factor (Ipeak/Ipms)

Overload

System

Remote signalling

Remote commands

Communication

Efficiency

Dimensions (wdh) (mm)

Weight (kg)

Noise level

Operating temperature

Relative humidity

Protection degree

Colour

Compliance

Technical data

Classification as per IEC 62040-3

MPS 500

500

MPS 600

600

MPS 800

800

MPS 500 MPS 600

380 - 400 - 415 Vac three-phase

400 V ± 20%

45 ÷ 65 Hz

>0.93 in the Sinus version

<3% in the Sinus version

0 ± 100% in 30" configurable

MPS 800

± 2% (selectable from ± 1% to ± 5% from the front panel)

Back Feed protection; separable bypass line

MPS 500 MPS 600

Lead, open vase acid and VRLA, AGM / GEL; NiCd

< 1%

-0,5 Vx °C

MPS 800

MPS 500

500

400

MPS 600

600

480

3 + N

380 - 400 - 415 Vac three-phase + N

± 1%

± 5% in 10 msec.

≤1%

≤3%

50 or 60 Hz configurable

Sinusoidal

3:1

110% for 60’; 125% for 10’; 150% for 1’

MPS 800

800

640

MPS 500 MPS 600

Voltage-free contacts (configurable)

EPO and bypass

MPS 800

Double RS232 + remote contacts + 2 communication interface slots

Up to 94%

3600

3200x980x1900

4000

4400x1000x1900

5300

78 dBA a 1 m

0 °C / +40 °C

<95% non condensing

IP20

Light grey (RAL 7035)

Directives EEC 73/23 - 93/68 - 89/336

Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3

(Voltage Frequency Independent) VFI - SS - 111

78

Sentry MPS

Single-phase output

PROTECTION FOR INDUSTRIAL

APPLICATION

MPS 1Ph is an on-line double conversion

UPS (VFI SS 111 in accordance with IEC

EN 62040-3) with transformers isolated inverter and rectifier. MPS 1Ph has a compact foot print and high quality output to provide the ultimate power protection for industrial applications: industrial processes, petrochemical, power plant, energy etc.

INDUSTRIAL ENVIRONMENT

MPS 1Ph is suitable for severe installation environments such as petrochemical manufacturing sites, where the operating conditions (levels of vibration, mechanical stress, ambient temperatures and dust ingress) require a more robust and industrialized UPS design to those installed within, for example, data centres.

HIGH Icc

A high short-circuit current (Icc = 3 In) making the UPS suitable for loads with high current peaks; during switch-on or a load step-change.

220V DC VOLTAGE

An input transformer and isolated inverter to protect the 220Vdc bus bar (from 108 to

114 blocks), the recognised industrial standard.

REDUNDANT VENTILATION

100% redundant ventilation with 50% fan loading at nominal load and each fan monitored for breakdown or failure.

MINIMUM IMPACT ON SUPPLIES - EASY

SOURCE

MPS 1Ph technology removes the problems of over sizing upstream power sources, whilst improving load power factors and current harmonics. The UPS features the latest input current absorption techniques including progressive rectifier start-up and the option to reduce battery charging currents. These features make

MPS 1Ph one of the most generator compatible and environmentally friendly

UPS available.

BATTERY CARE SYSTEM: MAXIMUM

LIFETIME POTENTIAL

Traditionally, when a mains supply is present the UPS charges its batteries.

Battery power is used for the inverter should the input supply fail. Efficient battery management and care is therefore essential to the overall performance of the

UPS in an emergency. The MPS 1Ph

Battery Care System consists of a range of features designed to provide optimum performance and enhanced operating life:

• Dual level charging regime to optimise recharge currents and lower recharge times

• Temperature compensation and deep discharge protection to reduce overall battery aging

• Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries

• Predictive battery testing to spot potential battery deterioration and failure

MPS 1Ph is also compatible with different battery technologies: open-vase lead acid and AGM and Gel VRLA, NiCd.

FLEXIBILITY

With a broad range of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing users. Using the Aros UPS Group

Synchroniser (USG) and Parallel

Systems Joiner (PSJ) sophisticated inter group parallel and redundant systems can be achieved to provide the highest possible levels of resilience and availability.

ADVANCED COMMUNICATION

• Compatible with TeleNetGuard for remote maintenance

• Advanced, multi-platform communication for all operating systems and network environments: Watch&Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows

9x, ME, NT 4.0, 2000, XP, Vista and

2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems

• The UPS is supplied with a cable for direct connection to the PC (Plug and Play)

• RS232 serial port

• Volt-free signal contacts

• EPO (Emergency Power Off) shutdown input contact

• Input for switching to bypass by remote signal

• LCD or LED-based remote control panel

• Generator interface: enables desynchronisation of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charger.

80

Sentry MPS

Three-phase input

Single-phase output

Models

Power (kVA)

Input

Nominal voltage

Voltage tolerance

Frequency

Power factor

Current harmonic distortion

Soft start

Permitted frequency tolerance

Standard features

Battery

Number of cells

Max Vdc

Temperature compensation

Output

Rated power (kVA)

Active power (kW)

Nominal voltage

Static stability

Dynamic stability

Voltage distortion with linear load

Voltage distortion with non linear load

Frequency

Crest factor (Ipeak/Ipms)

Overload

Short circuit current

System

Remote signalling

Remote commands

Communication

Efficiency

Dimensions (wdh) (mm)

Weight (kg)

Noise level

Ventilation

Operating temperature

Relative humidity

Protection degree

Colour

Compliance

Classification as per IEC 62040-3

Technical data

MPM 30

30

MPM 40

40

MPM 60

60

MPM 40

108 ÷ 114

274 V

-0,5 Vx °C

MPM 60

MPM 80

80

MPM 30 MPM 40 MPM 60

380 - 400 - 415 Vac three-phase

400 V ± 20%

45 ÷ 65 Hz

≥0.93

<5% C

0 ÷ 100% in 120’’ configurable

± 2% (selectable from ± 1% to ± 5% from the front panel)

Back Feed protection; separable bypass line

MPM 80

MPM 30 MPM 80

MPM 30

30

24

MPM 40

40

32

MPM 60

60

48

230Vac single-phase

± 1%

± 5%

<1%

<3%

50 or 60 Hz configurable

3:1

110% for 60’; 125% for 10’; 150% for 1’

3 I nom.

MPM 80

80

64

MPM 30 MPM 40 MPM 60

Voltage-free contacts

MPM 80

EPO and bypass

Double RS232 + remote contacts + 2 communication interface slots

Up to 94%

800x800x1900 1600x800x1900

850 900

63 ÷ 68 dBA a 1 m

1400

Redundant fans

0 °C / +40 °C

1500

<95% non condensing

IP20

Light grey (RAL 7035)

Directives EC 73/23 - 93/68 - 2004/108

Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3

(Voltage Frequency Independent) VFI - SS - 111

81

Sentry MPS 400 Hz

Frequency Converter

The Sentry MPS FC Series can also be used as a pure frequency converter accepting 50 or 60Hz input and supplying

400Hz output. It has a double conversion design (VFI SS 111 compliant with IEC EN

62040-3) with a transformer-isolated

Inverter.

The basic design is a solid state generator with IGBT- based Inverter controlled using

PWM techniques.

It is ideal for applications such as avionic repair workshops, hangars, aircraft ground power in civil airports and military bases.

The Sentry MPS FC offers a power range of

30 to 120kVA in several versions to suit the input current harmonic distortion and power factor requirements.

MINIMUM IMPACT

ON POWER SUPPLY – EASY SOURCES

Sentry MPS FC technology removes problems of over sizing downstream power sources, whilst improving load power factors and current harmonics.

The progressive ramping up of the rectifier at start up reduces the load surge when the

FC is powered by a generator motor.

All these features make Sentry MPS FC one of the most generator-compatible and environmentally friendly frequency converters on the market.

EASY TO INSTALL

Sentry MPS FC has a very small footprint

(only 0.86m2 for 120 kVA model). Front access to internal assemblies and top panel ventilation make space allocation very simple. Sentry MPS FC can be placed up against a wall as there is no requirement for rear or side panel access for maintenance or ventilation.

APPLICATIONS

• Aircraft ground power

• Airports

• Navy

• Military equipment

• Testing laboratories

ADVANCED COMMUNICATIONS

Compatible with TeleNetGuard for remote maintenance

• Advanced, multi-platform communication for all operating systems and network environments:

Watch&Save 3000 monitoring and shut-downsoftware included, with SNMP agent, for Windows 9x, ME,

NT 4.0, 2000, XP, Vista and 2003 server; Mac OS X, Linux, Novell and most popular Unix operating systems

• The UPS is supplied with a cable for direct connection to the PC

(Plug and Play)

• RS232 double serial port

• Installation slot for an Emergency

Power Off (EPO) interface to allow the UPS to be switched off remotely in emergency situations.

• Generator interface: enables desynchronisation of the UPS output from generator power supply which may be subject to phase and frequency variations. The interface also enables a more economic use of the battery charger.

OPTIONS

• Input Isolation transformer

• Programmable relay card

• LED remote status panel

• LCD based remote Control panel

• Remote Graphics Panel

82

Sentry MPS FC

Three-phase input

Single-phase output

Models

Power (kVA)

Input

Nominal voltage

Voltage tolerance

Frequency

Power factor

Current harmonic distortion (THDi)

Soft start

Models

Rated power (kVA)

Active power (kW)

Nominal voltage

Static stability

Dynamic stability

Voltage distortion with linear load

Voltage distortion with non linear load

Frequency

Crest factor (Ipeak/Ipms)

Overload

System

Remote signalling

Remote commands

Communication

Efficiency

Dimensions (wdh) (mm)

Weight (kg)

Noise level

Operating temperature

Relative humidity

Protection degree

Colour

Compliance

Classification as per IEC 62040-3

Technical data

MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120

30 60 80 100 120

MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120

380 - 400 - 415 Vac three-phase

400 V ± 20%

45 ÷ 65 Hz

≥0.93 (in the Plus version)

<5% (in the Plus version)

0 ÷ 100% in 120’’ configurable

MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120

30 60 80 100 120

24 48 64

208Vac 3Ph + N (settable 200 V)

80 96

± 1%

± 5%

<3%

<4%

400 Hz

3:1

110% for 60’; 125% for 10’; 150% for 1’

MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120

Voltage-free contacts

EPO and ON/OFF

Double RS232 + remote contacts + 2 communication interface slots

550x740x1200

330 600

Up to 92%

800x800x1900

620

61 to 63 dBA at 1 m

640 650

0 °C to 40 °C

<95% non condensing

IP20

Light grey (RAL 7035)

Directives EC 73/23 - 93/68 - 2004/108

Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3

(Voltage Frequency Independent) VFI - SS - 111

83

Stabilisers

WHY USE STABILISERS?

Proper operation of most electric and electronic equipment depends to a large extent on the power supply voltage that must be kept as steady and as near to the nominal value as possible. In many installations, the mains power supply tends to fluctuate for a number of reasons. So devices that overcome and correct this problem are often used and the ideal solution is a stabiliser. AROS produces a full range of electromechanical and electronic stabilisers as well as electronic line conditioners.

ELECTROMECHANICAL STABILISERS

This type of stabiliser controls the voltage output by adding or removing

(by moving a brush converter) voltage so as to restore output to the nominal value. Advantages of using an electromechanical stabiliser are:

• High quality voltage

• Insensitive to the type of load or power factor

• Low weight/power ratio

• High stabilizing accuracy

• High reliability

• Wide range of power ratings for single-phase or three-phase voltages.

ELECTRONIC STABILISERS

The operating principle of an electronic stabiliser is based on the regulation of the voltage through self-transformer sockets selected and connected to the output via static switches.

Regulation is determined by a specific electronic control circuit.

Advantages of using an electronic stabiliser are:

• No harmonic distortion

• Insensitive to the type of load or power factor

• Low weight/power ratio

• High reliability

• High voltage regulation speed.

ELECTRONIC LINE CONDITIONERS

An electronic line conditioner combines an electronic stabiliser, an isolating transformer and high attenuation

EMI/RFI filters in a single unit.

It provides maximum protection for installations susceptible to voltage fluctuations, high frequency line noise and power surges. Advantages of the line conditioners are:

• Isolation between the line and the load

• No harmonic distortion

• Insensitive to the type of load or power factor

• High voltage regulation speed

• Protection against power surges

• Protection against line noise.

85

Voltronic 4 single-phase

The VOLTRONIC 4 single-phase electronic voltage stabiliser is able to adjust the output voltage within ±3% of the rated voltage.

The main features of the VOLTRONIC 4 electronic voltage stabilisers are:

• Microprocessor full control

• Compact size

• High regulation speed

• High efficiency

• Insensitivity to load variations and power factor.

A LED panel provides information on:

• Mains input voltage exceeding regulation limits

• Mains frequency exceeding limit

• Load level

• Overload

• Alarm for input overvoltage and/or overheating (the visual alarm is accompanied by an acoustic alarm).

86

Voltronic 4 single-phase

Technical data

Nominal output voltage

Input voltage range

Frequency

Power (kVA)

Maximum output current at 230V (A)

Efficiency

Accuracy

Regulation speed (ms/V)

Accepted load variation

Load power factor

V4-500

0,5

2,4

V4-1000 V4-2000 V4-4000

220-230-240 Vac single-phase

V4-5000

-18% +14% depending on the selected output voltage

48 -62 Hz

1

4,5

2

9

4

18

5

22

98%

±3%

2

0 to 100%

Any

V4-10000

10

44

Harmonic distortion

Cooling Natural

Operating ambient temperature

Protection degree

Display indications

<0,5%

0°C ÷ 40°C

IP 20

Mains OK, load level, overload, alarms

Acoustic alarm

Input protection

Output protection

Input connection

Output connection

Fuse

Fuse

Cable with Schuko plug

Schuko socket

Active for overload, over-voltage, over-temperature

Automatic switch

Fuse

Internal terminal board

Internal terminal board

Dimensions (wdh) mm

Weight (kg)

V4-500 V4-1000

180x215x194

9 10

V4-2000

21

V4-4000

230x350x275

25

V4-5000

27

V4-10000

340x540x310

51

87

Voltronic 4 three-phase

The VOLTRONIC 4 three-phase electronic voltage stabiliser is able to adjust the output voltage within ±3% of the rated voltage.

Voltage stabilisation is performed independently on each phase.

The main features of the VOLTRONIC 4 three-phase electronic voltage stabilisers are:

• Microprocessor full control

• Compact size

• High regulation speed

• High efficiency

• Insensitivity to load variations and power factor.

A LED panel provides information on:

• Mains input voltage exceeding regulation limits

• Mains frequency exceeding limit

• Load level

• Overload

• Alarm for input overvoltage and/or overheating (the visual alarm is accompanied by an acoustic alarm).

88

Voltronic 4 three-phase

Technical data

Nominal output voltage

Input voltage range

Frequency

Power (kVA)

Maximum output current at 230V (A)

Efficiency

Accuracy

Regulation

Regulation speed (ms/V)

Overload

Accepted load variation

Load power factor

Harmonic distortion

Cooling

Operating ambient temperature

Protection degree

Display indications

Acoustic alarm

Input protection

Output protection

Input connection

Output connection

Dimensions (wdh) (mm)

Weight (kg)

V4 3F-6000

6

9

V4 3F-10000 V4 3F-12000

380/400/415 Vac + N selectable

-18% +14% depending on the selected output voltage

48 - 62 Hz

V4 3F-15000

10

15

12

18

15

22

98%

±3%

Independent on each phase

2

1,5 I

N x 5 sec

0 to 100%

Any

<0,5%

Natural Forced ventilation

0°C ÷ 40°C

IP 20

Mains OK, load level, overload, alarms

Active for overload, over temperature, irrecoverable failure

Automatic switch

Fuse on each phase

Internal terminal board

Internal terminal board

V4 3F-6000

44

V4 3F-10000 V4 3F-12000

340x540x310

48 52

V4 3F-15000

60

89

ELC Line Conditioners

The electronic line conditioners of the

ELC range have been specially designed to protect electronic control equipment such as PC’s, PLC’s, internet devices, laboratory instrumentation, data transmission and audio-video apparatus, against anomalies or interference in the power supply circuit. In particular, ELC protect against line noise and power surges ensuring effective voltage regulation.

The electronic line conditioners guarantee and effective protection as they combine an electronic stabilizer,

EMI/RFI filters and an isolating transformer in a single unit.

The equipment is controlled by a microprocessor logic that also sounds alarms in the event of overloads, overvoltage or overheating.

90

ELC Line Conditioners

Nominal input voltage

Nominal output voltage

Input voltage range

Input frequency

Power (kVA)

Max. output current at 230V (A)

Efficiency

Accuracy

Regulation speed (ms/Volt)

Overload

Accepted load variation

Load power factor

Harmonic distortion

Input peak voltage protection

Common mode rejection ratio

Primary and secondary insulation voltage

Cooling

Operating ambient temperature

Protection degree

Display indications

Acoustic alarm

Input protection

Output protection

Input connection

Output connection

Dimensions (wdh) (mm)

Weight (kg)

Technical data

ELC 1500 ELC 3000

220/230/240 Vac single-phase

220/230/240 Vac selectable, single-phase

-18% +14% depending on the selected output voltage

ELC 5000

1,5

7

48 - 62 Hz

3

14

95%

5

22

±3%

2

1,5 I

N x 5 sec

0 to 100%

Any

<0,5%

Up to 4KV - 130 Joule

70 dB

2500V input/output

Natural

0°C ÷ 40°C

IP 20

Line OK, load level, overload, alarms

Active for overload, overvoltage, overtemperature

Forced ventilation

Automatic switch

Fuses

Internal terminal board

Internal terminal board

ELC 1500

230x350x275

26

ELC 3000

340x540x310

44

ELC 5000

56

91

RQ

The RQ stabilizers belong to the electromechanical series with electronic control. They provide a perfect constant single-phase output voltage completely independent from any variation of the input voltage within the accepted voltage range.

The stabilisation of the output voltage is not affected neither by eventual harmonic distortion present in the mains nor by the value and load power factor; the output power distortion is very low (<0,2%) and the total efficiency is very high. The installation of the RQ stabilizers is very flexible: their special shape makes it easy to install them near the equipment to power or inside it. They can be mounted on the wall or in a cabinet.

92

RQ

Power (kVA)

Input voltage range

Maximum output current (A)

Regulation speed (ms/Volt)

Efficiency

Power (kVA)

Input voltage range

Maximum output current (A)

Regulation speed (ms/Volt)

Efficiency

Common characteristics

Nominal input/output voltage

Accuracy

Nominal frequency

Load variation

Load power factor

Harmonic distortion

Cooling

Operating ambient temperature

Protection degree

Dimensions (wdh) (mm)

Weight (kg)

Dimensions (wdh) (mm)

Weight (kg)

Technical data

RQ 1000

1

±25%

4

18

94%

RQ K10

10 / 7,5

±15/20%

44

18

96%

RQ 1000

275x425x260

19

RQ K10

300x565x280

50

RQ 2500

2,5 / 2

±15/20%

11

18

96%

RQ K15

15 / 10

±15/20%

65

18

98%

RQ 5000

5 / 4

±15/20%

22

18

97%

RQ K25

25 / 18

±15/20%

109

20

98%

RQ 2500

275x425x260

22

230 Vac

±1%

50/60 Hz

0 to 100%

Any

<0,2%

Natural

-5°C ÷ 40°C

IP 21

RQ 5000

275x425x260

28

RQ K15

300x565x280

55

RQ K25

405x670x1150

125

RQ 7000

300x565x280

42

RQ K35

405x670x1150

130

RQ 7000

7 / 5,5

±15/20%

31

18

98%

RQ K35

35 / 26

±15/20%

152

20

98%

93

Tristab-T

TRISTAB-T series includes several voltage stabilizers of electromechanical type with electronic control. They provide a perfect three-phase output voltage completely independent from any variation of the input voltage within the accepted voltage range. The stabilisation of the output voltage is not affected neither by eventual harmonic distortion present in the mains nor by the value and the load power factor; the distortion of the output voltage is very low (<0,2%); the total efficiency is very high. The voltage regulation is provided on the average value of threephases and then these stabilizers are suitable for maximum 50% unbalanced load. There is the possibility of choosing between two input voltage ranges according to the nominal power required (see table).

The operator panel includes a digital voltmeter which inform on the status of the line downstream on the voltage of each phase and the linked voltages.

All models (up to 60kVA) are provided with wheels for an easier positioning and handling.

94

Tristab-T

Power (kVA) with input ±15%

Power (kVA) with input ±20%

Input voltage range

Maximum output current (A)

Regulation speed (ms/Volt)

Efficiency

Power (kVA) with input ±15%

Power (kVA) with input ±20%

Input voltage range

Maximum output current (A)

Regulation speed (ms/Volt)

Efficiency

Common characteristics

Nominal input/output voltage

Accuracy

Nominal frequency

Load variation

Load power factor

Harmonic distortion

Cooling

Operating ambient temperature

Protection degree

Dimensions (wdh) (mm)

Weight (kg)

Dimensions (wdh) (mm)

Weight (kg)

Technical data

T5

5

4

±15/20%

7

18/13

95%

T75

75

60

±15/20%

107

18/13

98%

T10

10

7,5

±15/20%

14

18/13

96%

T105

105

80

±15/20%

150

18/13

98%

T15

15

12

±15/20%

21

18/13

97%

T135

135

105

±15/20%

193

18/13

98%

T175

175

135

±15/20

253

18/13

98%

T20

20

15

±15/20%

28

18/13

98%

T230

230

175

±15/20%

332

20/18

98%

T30

30

24

±15/20%

43

18/13

98%

T300

300

230

±15/20%

433

20/18

98%

T50

50

36

±15/20%

71

18/13

98%

T60

60

45

±15/20%

87

18/13

98%

T5

50

T75

605x800x1400

320

T10

360x520x1000

60

T15

110

400 Vac

±1%

50/60 Hz

0 to 100%

Any

<0,2%

Forced ventilation

-5°C ÷ 40°C

IP 21

T20

120

T30

405x670x1150

160

T105 T135

605x800x1600

480 500

T50

200

T175 T230 T300

605x850x1650 1210x800x1600 1210x850x1700

700 800 1200

T60

605x800x1400

250

95

Tristab-Y

TRISTAB-Y series includes several voltage stabilizers of electromechanical type with electronic control from 5 to

300kVA. They provide a perfect threephase output voltage completely independent from any input voltage variation within the accepted voltage range.

The stabilisation of the output voltage is not affected neither by eventual harmonic distortion present in the mains nor by the value and load power factor; the output voltage distortion is very low (<0,2%); the total efficiency is very high. In the

"Y" version the stabilising effect is obtained independently on each phase.

This solution is therefore particularly useful with unbalanced three-phase loads or single-phase loads.

For proper operation, the presence of the neutral wire is necessary. There is the possibility of choosing between two input voltage ranges according to the nominal power required (see table).

The operator panel includes a digital voltmeter which provides information on the voltage of each phase and the linked voltages. All models (up to

60kVA) are provided with wheels for an easier positioning and handling.

96

Tristab-Y

Power (kVA) with input ±15%

Power (kVA) with input ±20%

Input voltage range

Maximum output current (A)

Regulation speed (ms/Volt)

Efficiency

Power (kVA) with input ±15%

Power (kVA) with input ±20%

Input voltage range

Maximum output current (A)

Regulation speed (ms/Volt)

Efficiency

Common characteristics

Nominal input/output voltage

Accuracy

Nominal frequency

Load variation

Load power factor

Harmonic distortion

Cooling

Operating ambient temperature

Protection degree

Dimensions (wdh) (mm)

Weight (kg)

Dimensions (wdh) (mm)

Weight (kg)

Technical data

Y75

75

60

±15/20%

107

18/13

98%

Y5

5

4

±15/20%

7

18/13

95%

Y10

10

7,5

±15/20%

14

18/13

96%

Y105

105

80

±15/20%

151

18/13

98%

Y15

15

12

±15/20%

21

18/13

97%

Y135

135

105

±15/20%

193

18/13

98%

Y175

175

135

±15/20%

253

18/13

98%

Y20

20

15

±15/20%

28

18/13

98%

Y230

230

175

±15/20%

332

20/18

98%

Y30

30

24

±15/20%

43

18/13

98%

Y300

300

230

±15/20%

433

20/18

98%

Y50

50

36

±15/20%

71

18/13

98%

Y60

60

45

±15/20%

87

18/13

98%

Y5

70

Y75

605x800x1400

350

Y10

360x520x1000

75

Y105

540

Y15

110

Y135

605x800x1600

580

400 Vac

±1%

50/60 Hz

0 to 100%

Any

<0,2%

Forced ventilation

-5°C ÷ 40°C

IP 21

Y20

145

Y30

405x670x1150

170

Y175

610

Y50

190

Y230 Y300

1210x800x1600 1210x850x1700

900 1200

Y60

605x800x1400

260

97

Software and accessories for total reliability in controls and communication

Watch&Save 3000 provides detailed graphical displays.

A standard screen displays information on the load, batteries status, alarms etc.

Watch&Save 3000 - Communication software

Watch&Save 3000 provides efficient, user-friendly UPS management using bar chart displays to show major operational information such as the input voltage,

UPS load % and batteries charge %. The software also provides detailed information on fault conditions and UPS operating characteristics. Watch&Save

3000 has been developed with a client/server architecture that makes it flexible and easy to use, and provides multi-lingual and on-line support.

CHARACTERISTICS

• Sequential and priority-based shutdown: Watch&Save 3000 provides unattended shut-down of single and networked PCs, saving any active work and the most widely used applications Windows. Users can define their own shutdown procedures and establish the order in which critical computers (such as servers) are to be powered down.

• Multi-platform compatibility: Watch&Save 3000 uses the TCP/IP communications protocol to achieve standardised management and monitoring across the widest possible range of platforms. This makes it possible to monitor computers with different operating systems from a single console, for example monitoring a UNIX server from a PC with Windows and also connecting to UPS located in different geographical areas using dedicated networks (intranets) or the Internet.

• Event scheduling: Watch&Save 3000 users can program their own shutdown procedures, detailing power-off and power-up scenarios to increase system safety and, equally important, power economy.

• Messages management: Watch&Save 3000 keeps users constantly informed about the status of their local and network UPS. A list can be defined of users who should receive e-mail messages, faxes and SMS when faults or sudden blackouts occur.

• Integrated SNMP agent: Watch&Save 3000 features an integrated SNMP agent for management of the UPS. This agent is able to send all the UPS information and generate traps using the RFC 1628 MIB standard. This makes it possible to manage the UPS in compatible SNMP management stations such as HP Open View, Novell Managewise and IBM NetView.

• Wap server integrated: Watch&Save 3000 allows the user to monitor a UPS through WAP mobile phone.

• Security, easy to use and connect, communication is password protected to ensure UPS system security. Using the new discovery/browsing function, all the AROS UPS connected to a protected computer or LAN can be displayed in a list format. In the absence of a LAN connection, support is provided for modem-based communication.

98

Software and accessories for total reliability in controls and communication

All information can be displayed in block format.

GRAPHIC MONITORING OF UPS STATUS

Watch&Save 3000 is a simple but powerful AROS UPS management tool.

There are various graphic versions for all the operating systems.

DETAILED UPS PARAMETER DISPLAY

Watch&Save 3000 provides all the information required for first level diagnostics.

EVENTS LOG AND GRAPHICAL DISPLAY

All changes in UPS operating status are logged and displayed in a graphical format from which the user can monitor trends in the mains electrical parameters monitored.

PROGRAMMING OF UPS PARAMETERS

The user can select several options remotely: turn the UPS on or off, restart after a power loss and instigate a battery test.

GRAPHIC MONITORING OF UPS STATUS VERSION FOR MAC OS X

AROS Watch&Save 3000 software is the only UPS control and shut-down software running under Macintosh with a client-server cross platform architecture.

It allows integration in TCP/IP networks with Windows, Novell, IBM OS/2 and the most widely used UNIX operating systems. Watch&Save 3000 supports the

NetMan Plus series of network agents and provides multi-language support.

BLOCK AND FUNCTIONAL DIAGRAMS

Watch&Save 3000 also displays the UPS in block format providing the user with information regarding operating status.

NOTIFICATION OF ALARMS VIA E-MAIL, SMS, FAX AND VOICE

Watch&Save 3000 can be configured to forward alarm messages automatically via e-mail, SMS, fax and voice.

Operating systems supported

• Windows 98, Me, NT 4.0, 2000, 2003, XP, Vista

• Linux on processors X86, X86_64 e IA64

• Novell Netware 3.x, 4.x, 5.x, 6

• Mac OS X

• The most widely used UNIX operating systems such as:

IBM AIX, HP, SUN Solaris INTEL and SPARC, SCO Unixware and Open Server,

Silicon Graphics IRIX, Compaq Tru64 UNIX and DEC UNIX, Open BSD UNIX and FreeBSD UNIX, NCR UNIX

• HP OPEN VMS

All the trademarks indicated are the property of their respective owners.

99

Software and accessories for total reliability in controls and communication

PowerNetGuard - Supervision software

PowerNetGuard software centralises UPS management using network interface

(SNMP) communications. It is ideal for Data Centre managers and medium to large sized networks. PowerNetGuard uses the RFC1628 standard

Management Information Base (MIB) and ensures standardised UPS management wherever they are located.

CHARACTERISTICS

• Centralised control of remote UPS via Ethernet with SNMP protocol

• Multiple-level display of geographical areas, building plans, maps, etc.

• Multi-user access with various levels of security

• Compatible with NetMan Plus and RFC1628 standard network interface

(SNMP)

• Graphs of physical input and output values stored and backed up to file

• Alarm notification via e-mail and SMS

• Operating systems supported: Windows (98, ME, NT, 2000, 2003 and XP),

Linux, MacOSX, Solaris 8 and 9

Centralized control of remote UPS

1.

1.

2.

1.

1. NETMAN PLUS CONNECTION

2. THIRD PART SNMP AGENT

100

Software and accessories for total reliability in controls and communication

NetMan 101 Plus

NetMan 102 Plus

NetMan 101/102 Plus - Network agent

The NetMan Plus network agent allows UPS management across a LAN using any of the main network communication protocols - TCP/IP, HTTP and network interface (SNMP).

NetMan Plus enabled UPS integrate easily into medium and large sized networks and provide reliable communications between the UPS and management systems employed.

CHARACTERISTICS

• Configured via TELNET or a serial terminal

• Compatible with Watch&Save 3000 and PowerNETGuard control software

• Supports the network interface (SNMP) standard communication protocol with proprietary RFC 1628 and MIB

• Integrated Web server for browser-based display

• PowerNetGuard modem compatible

• Firmware upgradeable through the serial port

• E-mail sent through SMTP server

Environmental sensors

Temperature sensor

Air conditioner

ENVIRONMENTAL SENSORS

Temperature sensor

Smoke detector

The NetMan Plus environmental sensors monitor and record environmental conditions as well as activities in protected areas and at the premises where the

UPS is installed.

The environmental sensors allow extensive control and management of the environment around the UPS by monitoring the temperature, humidity, triggering devices such as fans or locks and communicating the values via web, SNMP and via the Watch&Save 3000 software. Watch&Save 3000 software can be used to manage the status of the sensors in order to send messages. Please refer to Watch&Save 3000 software for further details. NetMan plus is able to handle a maximum of 6 separate sensors.

The environmental sensors are easy and fast to install thanks to their compact size and do not need external power supply.

The connected sensors are self-learning which makes their configuration both fast and intuitive.

The following sensors are available:

- Sensor for temperature:

-55 +125 °C

- Sensor for temperature:

-55 +125 °C and humidity:

0- 100%

- Sensor for temperature:

-55 +125 °C and digital I/O:

0-12Vdc.

In 1A max out 48Vdc

Temperature sensor

APPLICATION DIAGRAM

APPLICATION DIAGRAM

101

MultiCom 301

MultiCom 302

MultiCom 351

MultiCom 352

MultiCom 362

MultiCom 372

Software and accessories for total reliability in controls and communication

MultiCom 301/302 - Protocol converter

The MultiCom 301/302 protocol converter may be used to monitor the UPS using the MODBUS/JBUS protocol on RS485 or RS232 serial lines. It will also manage a second, independent RS232 serial line that can be used to connect other devices such as the Netman Plus 101 or a PC that uses the Watch&Save

3000 software.

CHARACTERISTICS

• Port configuration for MODBUS/JBUS as RS232 or RS485

• Management of two independent serial lines

• Suitable for Building Management System (BMS) integration

• LED communication flow indicators

• Firmware upgradeable through the serial port

MultiCom 351/352 - Serial link duplexer

The MultiCom 351/352 is a serial duplexer that allows two devices to be connected to a single serial port on a UPS.

It can be used where numerous serial connections and multiple UPS polling are required, and is ideal for LAN networks with a firewall.

CHARACTERISTICS

• Cascading configuration giving a maximum of 4 serial communication ports

• LED communication flow indicators

• Firmware upgradeable through the serial port

MultiCom 362 - Serial / USB port

MultiCom 362 provides a UPS with an additional RS232 serial interface or USB port. The USB port allows the UPS to communicate with Apple Macintosh computers as well as Windows and Linux operating systems.

CHARACTERISTICS

• Compatible with USB 1 or 2

• Compatible with Watch&Save 3000

MultiCom 372 - Serial / ESD port

MultiCom 372 provides a UPS with an additional RS232 serial interface port.

The card has Emergency Power Off (EPO) and Remote Shut Down (RSD) inputs with terminal connections.

CHARACTERISTICS

• EPO and UPS shutdown interface

• 12Vdc 80mA contact option

102

MultiCom 382

Multi I/O, slot version

Multi I/O, box version

USB Converter

MultiCom 382 - Contacts / ESD board

MultiCom 382 provides a set of relay contacts to provide UPS alarm and status indication.

The contacts are connected through terminal connections. Signal contacts include Emergency Power Off (EPO), Remote Shut Down (RSD), On Battery, On

Bypass, Alarm and Low battery. The contacts are change over or normally open.

CHARACTERISTICS

• Max. 3A current at 250Vac

• Signal contact customisation

Multi I/O - Protocol converter

Multi I/O has configurable input and output signal contacts to allow UPS integration with control systems.

It can be used to connect two devices to a single UPS serial communication port. It can also communicate using the MODBUS/JBUS protocol on RS485 lines.

CHARACTERISTICS

• 8 analog/digital inputs

• 8 relay outputs to monitor UPS and mains status

• It can control two independent RS232/RS485 serial lines to monitor the UPS and its operating states using the MODBUS/JBUS protocol

• Firmware upgradeable through the serial port

USB Converter - USB serial converter

The RS232-USB converter allows UPS without a USB port to connect to

Macintosh, Windows and Linux PCs with this type of port.

CHARACTERISTICS

• Compatible with USB 1or 2

• Compatible with Watch&Save 3000

103

Multifunction I/O

MultiCom 401

Software and accessories for total reliability in controls and communication

Multifunction I/O - Serial link / contacts duplexer

Multifunction I/O is a Sentinel 6 range accessory with which you can associate the battery operation, by-pass, alarm and battery depleted status reports with dry contacts (maximum current 8A/250V). The accessory also has an input which is used to set up the configurable remote on, remote off and remote on/off functions through the UPSTools software (vers. 1.3.3 or higher).

The functions are provided for UPS with firmware version SWM020-01-16 or higher.

CHARACTERISTICS

• Max. current 8A at 250Vac

• Possibility of configuring the signal-to-contact associations

• Pass-through serial link for PC connection

MultiCom 401 - PROFIBUS

The MultiCom 401 is an accessory with which you can connect a UPS to a

Profibus DP network. With this device management and monitoring of the UPS can be integrated in a control system based on one of the field buses most widely used in industry for communication between control/automation systems and distributed I/O.

CHARACTERISTICS

• PROFIBUS DP-V1 Protocol

• Configurable address from 0 to 99

• Profidrive V2 PP05

• Configurable baud rate from 9.6 kBit/s to 12 MBit/s

• Led reporting the communication flow

104

Software and accessories for total reliability in controls and communication

Graphic Remote Panel

External Manual Bypass 16A wall mount version

KIT for AS400 and i-Series - Communication Kit

The IBM AS/400 has a single-level memory management feature that makes it compulsory for the system to be shutdown in a controlled and orderly manner.

Without UPS protection an AS/400 is not protected from mains failures.

A momentary loss of power can cause hardware damage, data corruption and a lengthy reboot period. The AROS AS/400 interface kit allows a UPS to be connected to the AS/400 to initiate an orderly system shutdown on mains failure.

CHARACTERISTICS

• Compatible with all AS/400 systems

• Supports all the AROS UPS ranges

Graphic Remote Panel

Graphic Remote Panel is a remote monitoring device that can provide a detailed

UPS status overview in real time. It is compatible with all Aros UPS with RS232 and can display values for UPS specific input and output supplies, and battery set measurements. Graphic Remote Panel has a high-definition graphical display and can report in 7 languages: English, Italian, German, French, Spanish,

Russian and Chinese. It has 3 independent serial ports, one of which allows for

UPS monitoring via the MODBUS/JBUS protocol (on either an RS485 or RS232 serial line). The others can be used with devices such as the Netman 101 Plus or a PC running Watch&Save 3000 software.

External Manual Bypass 16A

The Manual Bypass is a maintenance bypass to allow a UPS to be powered down and removed for service without disruption to the connected load(s). The External

Manual Bypass is available in wall mounted or 19” rack mount formats.

CHARACTERISTICS

• Wall or rack mount versions

• Back-feed protection

• Manual and automatic transfer functions

• Mains power present LED indicator

• IEC, UK, Schuko and hard wired connected options

105

IRMS (Intelligent Redundant Multi-Switch)

Multi-SWITCH improves electrical supply continuity. The principle of operation guarantees a higher reliability level than that achieved using a single UPS (on-line with automatic bypass) or several UPS in parallel.

PRINCIPLE OF OPERATION

The IRMS provides electrical distribution and remote management for up to eight network users, powered from two direct mains supplies or UPS or a combination of both.

The Multi-SWITCH can connect each user (up to eight, each with a maximum power demand not greater than 4A), to either of the two power sources (1 and 2). Load demand is shown on the LCD.

See “principle of operation” diagram.

PROTECTION AGAINST POWER

SUPPLY FAILURES

If one of the two power source fails or falls outside specification, IRMS will transfer the connected loads to the second power source

(switching is instantaneous even if the two sources are not in phase).

PROTECTION AGAINST LOAD FAULTS

If a fault occurs with one of the loads

(for example due to a shortcircuit or overload), IRMS will disconnect the load to prevent disruption to the others.

IRMS protects sensitive installations from both power and hardware faults.

CHARACTERISTICS

• Full protection against mains failures and load faults

• Flexible power sources: IRMS can be powered from 2 different sources (2 mains supplies, 2 UPS or a combination of both. Note than the UPS can be of a different size)

• Designed for installation in a 19” rack-mount cabinet

• LCD to provide measurements/alarms/states information

• Management software included

• Remote monitoring serial interface

• No signal connection is required between Multi-SWITCH and the power sources or supplied hardware

• Configuration software provided as standard

• Slot-in SNMP network adapter card

106

Models

Power

Input

Input voltage

Rated frequency

Maximum load for each input (A)

Input sockets

Output

Output voltage

Maximum load for each output (A)

Output sockets

Environmental

Weight (kg)

Dimensions (wdh) (mm)

Operating temperature

Relative humidity

Protection

Safety compliance

Maximum altitude

Maximum altitude (storage conditions)

Communication

Enclosure protection rating

Colour

Noise

Details

FRONT

BACK

Multi-Switch (2 inputs – 8 outputs)

8x4A output sockets

Multi-Switch (2 inputs – 8 outputs)

180 - 276 Vac

50/60 Hz

16

2 IEC 320 (16A)

Multi-Switch (2 inputs – 8 outputs)

Selection of one of the two input sources

4

8 IEC 320 10A

Multi-Switch (2 inputs – 8 outputs)

10

19”x360x2U

O °C / +40 °C

< 95% non condensing

Overcurrent - overvoltage - undervoltage - back-feed protection

EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3

3000 m

6000 m; 45 °C

RS232

IP 20

Dark grey (RAL 5004)

<35 dBA at 1 m

Output soc kets

Ethernet (option)

Serial RS232

Input thermal protection reset

Input sockets

107

CSS Configurations

Standby Power Systems

AROS uninterruptible power supplies are also designed and built for use in applications such as central supply systems for emergency lighting, security alarms and electro-medical equipment.

The CEI 64-8 V2, EN 50171 standards and other guidelines set down the characteristics and performance levels required from such systems. The main ones are summarized below:

• Up to 3 h back-up times

• Battery recharge time of under 12 h

• Galvanically isolated input/output

• High-level diagnostics – preferably from a front mimic panel

• Remote interface – normally volt-free contacts

• High short circuit current capability.

The applications require a continuous power system configured as follows:

• A standard UPS with high capacity battery charger

• An isolation transformer (option)

• A remote interface to communicate with other peripherals.

Diagrams of the various system solutions

1. Always powered

2. Powered from the mains

3. Emergency only

4. Always powered/Emergency only

108

EXAMPLE OF CSS CONFIGURATIONS

Model

Back-up times of up to 3 hours

SENTINEL 6

SENTINEL XR

SENTINEL 5 PLUS

SENTRY MULTISTANDARD

Model

Back-up times of up to 1 hours

SENTINEL 6

SENTINEL XR

SENTINEL 5 PLUS

SENTRY MULTISTANDARD

Powers loads of power up to

1600 W

2000 W

3000 W

30.000 W

Powers loads of power up to

2100 W

3500 W

7000 W

64.000 W

CHARACTERISTICS

• Full microprocessor control: for greater reliability and compactness in size

• Use of Isolated Gate Bipolar

Transistors (IGBT) technology – used in UPS for over 10 years to optimise performance (such as overloads) and reduce physical sizes

• Advanced communication interface – the units come with a volt-free contact interface and RS232/485 serial interface for communication with a local PC or computer network

• PowerNetGuard remote support service compatible for remote diagnostics and control

• Front panel LCD to display operating status, alarms, measurements and logs

• Option to expand the power and/or reliability through the parallel connection of units – 8kVA models and higher

ADVANCED COMMUNICATION

• Watch&Save 3000 supervision and shut-down software for the following operating systems: Windows 95, 98,

NT 4.0 including work station, Me,

2000, 2003, XP, Linux, Novell, Mac

OS 9.x, X, Linux, Novell.

A FULL RANGE OF CSS UNITS,

FROM 700VA TO 200KVA.

The CSS range units are comprised of the following blocks:

Rectifier: converts the alternating voltage input from the mains power supply or from an alternative source (generator) into direct current voltage.

Inverter: converts the direct current voltage supplied by the rectifier into alternating voltage. In this way the voltage is reconstructed, filtered and stabilised with regard to the input voltage.

By-pass: this allows switching between the inverter and the mains power supply. In “always powered” operating mode the CSS load is always powered from the inverter and is only switched onto the mains via the by-pass circuit in the event of a failure. In “powered from the mains” mode, the load is powered and only switched onto the inverter when there is no power from the mains. In

“emergency only” mode the load is only powered from the inverter in the event of a mains power failure. To deal with the current surges required by the powered loads at switching-on time, a

Soft Start inverter has been implemented in order to limit the value of current required. In “always powered/emergency only” two outputs can be used: one always powered

(such as for powering computer loads) and one that is only powered when there is no power from the mains (such as for powering emergency lights that by law must switch on within a maximum time of 0.5 seconds from a mains failure).

Batteries: used to feed the inverter output for the legally required time of 3 hours (if there is no generator). The batteries used are generally valve-regulated, lead-acid type, and do not require maintenance or a special installation room as they have very low gas emissions.

Compliance with Legislation

The CSS configurations complies with the relevant European regulations (and national guidelines still in force in some countries) governing such applications.

OPTIONS

• Communication interfaces: see options table for individual models

• Isolation transformers

• Second outlet emergency only

109

Notes

110

Notes

111

Graphic Design and Production:

Winning Associati - Bernareggio, Milano ITALY

Photos:

Studio Immagine 2000 - Bernareggio, Milano ITALY

Printed by:

Grafiche Stella - S. Pietro di Legnago (VR) ITALY - March 2008

Via Somalia, 20

20032 Cormano (MI) - ITALY

Ph. +39 02 66327.1

Fax: +39 02 66327.231

E-mail: [email protected]

www.aros.it

A

ROS PARTNER

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement