Surface Control Manager User Manual
(for ROC800-Series and
FloBoss
™
107 Controllers)
Remote Automation Solutions
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Revision Tracking Sheet
January 2017
This manual may be revised periodically to incorporate new or updated information. The revision date of each page appears at the bottom of the page opposite the page number. A change in revision date to any page also changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if applicable):
Page
All Pages
All Pages
Initial release
Revision
January-2017
August-2016
September-2014 ii Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Contents
Chapter 1 – Introduction 1
1.1
Scope and Organization ..................................................................................................................... 1
1.2
Product Overview ............................................................................................................................... 2
1.3
Program Requirements ...................................................................................................................... 2
1.3.1
License Key .......................................................................................................................... 3
Chapter 2 – Installation 5
2.1
Installing the License Key .................................................................................................................. 5
2.1.1
Installing the License Key for the ROC800 .......................................................................... 5
2.1.2
Installing the License Key for the FB107 .............................................................................. 6
2.1.3
Verifying the License Key Installation (for ROC800) ............................................................ 7
2.2
Downloading the Program .................................................................................................................. 8
2.2.1
Surface Control Program ...................................................................................................... 8
2.2.2
PMCB Calculation Blocks Program .................................................................................... 12
2.3
MPU Loading Threshold (ROC800) ................................................................................................. 16
Chapter 3 – Configuration 17
3.1
PMSC Action Blocks Screen ............................................................................................................ 18
3.2
PMSC Utilities Screens .................................................................................................................... 25
3.2.1
PMSC Utilities Screen – PMSC Effects Tab ...................................................................... 27
3.2.2
PMSC Utilities Screen – Time Count Tab .......................................................................... 29
3.2.3
PMSC Utilities Screen – Accumulators/Outputs Tab ......................................................... 32
3.2.4
PMSC Utilities Screen – Alarm Blocks Tab ........................................................................ 35
3.2.5
PMSC Utilities Screen – Action Block Domain Statuses Tab ............................................ 38
3.3
PMCB Calculation Blocks ................................................................................................................ 42
3.4
Saving the Configuration .................................................................................................................. 47
3.5
Sample Configurations ..................................................................................................................... 48
3.5.1
Controlling a Pump based on Tank Level .......................................................................... 48
3.5.2
Connecting Two Blocks with an AND Statement ............................................................... 49
3.5.3
Connecting Two Block with an OR Statement ................................................................... 51
3.5.4
Setting Up a Class B Bypass ............................................................................................. 54
3.5.5
Creating a Timed Maintenance Bypass ............................................................................. 56
Chapter 4
– Reference
59
4.1
Point Type 68/28: Action Blocks ...................................................................................................... 60
4.2
Point Type 71/31: Utilities ................................................................................................................ 68
4.3
Point Type 218: Calculation Blocks (for ROC800) ........................................................................... 75
4.4
Point Type 27/39: Calculation Blocks (for FB107) ........................................................................... 78
Appendix A – PMCB Calculation Blocks – Supported Functions
87
A.1
Calculations: Rules and Guidelines ................................................................................................. 87
A.1.1
Execution Order .................................................................................................................. 87
A.1.2
Order of Operators ............................................................................................................. 87
A.1.3
Parentheses ....................................................................................................................... 88
A.1.4
Operands ............................................................................................................................ 88
Revised January-2017 Contents iii
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
A.2
Operators ......................................................................................................................................... 89
A.2.1
Mathematical Operators ..................................................................................................... 89
A.2.2
Comparison Operators ....................................................................................................... 90
A.2.3
Bitwise Operators ............................................................................................................... 91
A.2.4
Logical Operators ............................................................................................................... 92
A.3
Functions ......................................................................................................................................... 92
A.3.1
AND(): Logical AND ........................................................................................................... 92
A.3.2
OR(): Logical OR ................................................................................................................ 93
A.3.3
Boolean Calculations using AND(), OR() and NOT(!) Operators ....................................... 93
A.3.4
ABS(): Absolute Value ........................................................................................................ 93
A.3.5
INT(): Integer Value ............................................................................................................ 94
A.3.6
MOD(): Modulus ................................................................................................................. 94
A.3.7
POW(): Raise To The Power Of ......................................................................................... 95
A.3.8
SUM(): Summation ............................................................................................................. 95
A.3.9
MIN(): Minimum Value ........................................................................................................ 95
A.3.10
MAX(): Maximum Value ..................................................................................................... 95
A.3.11
IIF(): Inline IF ...................................................................................................................... 96
A.3.12
BFI(): Boolean FAN-IN ....................................................................................................... 96
A.3.13
BFO(): Boolean FAN-OUT ................................................................................................. 96
A.3.14
FOR(): FOR Loop ............................................................................................................... 98 iv Contents Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Chapter 1 – Introduction
Caution When implementing control using this product, observe best industry practices as suggested by applicable and appropriate environmental, health, and safety organizations. While this product can be used as A safety component in a system, it is NOT intended or designed to be the
ONLY safety mechanism in that system.
This chapter describes the structure of this manual and presents an overview and installation instructions of the Surface Control Manager program for the ROC800-Series Remote Operations Controller and the
FloBoss
™
107 Flow Computer.
Note:
The Surface Control Manager program (v407_00_XXXblk.tar) comes with PMCB Calculation Blocks (Display #218) for
ROC800. For FloBoss 107, it is a separate program. For installation procedures, refer to Section 2.2.2 – PMCB
Calculation Blocks Program for details.
1.1 Scope and Organization
This document serves as the user manual for the Surface Control
Manager program, which is intended for use in a ROC800-Series
(ROC800) and FloBoss 107 (FB107). This manual describes how to download, install, and configure the Surface Control Manager program
(referred to as the “Surface Control program” or “the program” throughout the rest of this manual). You access and configure this program using ROCLINK
™
800 Configuration Software (version 2.30 or greater) loaded on a personal computer (PC) running Microsoft
®
Windows
®
2000 (with Service Pack 2), Windows XP (with Service
Pack 3), Windows Vista
™
(32-bit), or Windows 7 (32-bit and 64-bit).
The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software, the manual becomes a reference tool.
This manual has the following major sections:
Chapter 1 – Introduction
Chapter 2 – Installation
Chapter 3 – Configuration
Chapter 4 – Reference
Appendix A – PMCB Calculation Blocks – Supported Functions
This manual assumes that you are familiar with the ROC800 or FB107 and its configuration. For more information, refer to the following manuals:
FloBoss
™
107 Flow Manager Instruction Manual (Part
D301232X012)
Revised January-2017 Introduction 1
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
ROC800-Series Remote Operations Controller Instruction Manual
(Part D301217X012)
ROCLINK
™
800 Configuration Software User Manual (for
FloBoss
™
107) (Part D301249X012)
ROCLINK
™
800 Configuration Software User Manual (for
ROC800-Series) (Part D301250X012)
ROCLINK
™
800 Configuration Software User Manual (for
ROC800L) (Part D301246X012)
1.2 Product Overview
The two main functional areas on a well pad are the well itself
(“downhole”) and the equipment on the surrounding ground (“surface management”). “Surface control” refers to the ability to manage both the control logic of that equipment as well as any maintenance bypass requirements for that equipment and surface shut-in of wells. The
Surface Control Management application enables you to configure the
ROC800 or the FB107 to perform logical control and maintenance bypass using “action blocks.” Action blocks are configurable program components that drive effects (such as valves opening or closing). The
FB107 program supports 48 action blocks; the ROC800 programs support 48, 96, 144 or 192 action blocks. Additionally, a quartet of utilities accompanies each action block. These utilities provide the sequential effects for an action block, monitor run times (to calculate run and down times for air compressors, engines, and other equipment), accumulate values (for today, yesterday, this month, previous month, and for a running period), and provide configurable outputs (analog outputs, pulse outputs, etc.).
The Surface Control Program has an added feature – PMCB Calculation
Blocks. This program enables you to specify complex mathematical or logical (Boolean) equations for entry in a free-form style. These equations typically would either not be suited (too complex) for entry in
Action Blocks or Cause & Effect, or possibly you prefer to save Action
Blocks by processing all math and some logic problems in the PMCB
Calculation Blocks program.
1.3 Program Requirements
The Surface Control Manager program is compatible with version 3.52
(or greater) of the ROC800 firmware, version 1.31 (or greater) of the
ROC800L firmware, version 1.61 (or greater) of the FB107 firmware, and with version 2.30 (or greater) of the ROCLINK 800 software.
Program specifics include:
Note:
Load only one version of the program, depending on your action blocks and utilities requirements:
2 Introduction Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
The PMSC_v407_00_48blk.tar program file supports 48 action blocks, 4 calc blocks and 16 utilities and installs in a
ROC800 which requires only 1 license.
The PMSC_v407_00_96blk.tar program file supports 96 action blocks, 8 calc block and 32 utilities and installs in a
ROC800 which requires 2 licenses.
The PMSC_v407_00_144blk.tar programs file supports 144 action blocks, 12 calc blocks and 48 utilities and installs in a
ROC800 which requires 3 licenses.
The PMSC_v407_00_192blk.tar programs file supports 192 action blocks, 16 calc blocks and 64 utilities and installs in a
ROC800 which requires 4 licenses.
The PMSC_v407_XX_5.bin supports 48 action blocks and
16 utilities and installs in an FB107 which requires only 1 license.
File Name
Target Unit/
Version
User
Defined
Point (UDP)
Flash Used
(in bytes)
DRAM Used
(in bytes)
ROCKLINK
800 Version
PMSC_v407_00_48blk.tar
PMSC_v407_00_96blk.tar
ROC800 3.52
ROC800L 1.31
ROC800 3.52
ROC800L 1.31
PMSC_v407_00_144blk.tar
ROC800 3.52
ROC800L 1.31
PMSC_v407_00_192blk.tar
ROC800 3.52
ROC800L 1.31
PMSC_v407_XX_5.bin
PMCB_v400_01_3.bin
PMCB_v400_01_6.bin
FB107 1.61
FB107 1.61
FB107 1.61
68, 71, 218
68, 71, 218
68, 71, 218
68, 71, 218
28, 31
27
39
130,345
130,345
130,345
130,345
62,808
32,651
32,651
172,032
172,032
172,032
172,032
16,384
16,384
16,384
2.30
2.30
2.30
2.30
2.30
2.30
2.30
Display
Number
68, 71, 218
68, 71, 218
68, 71, 218
68, 71, 218
28, 31
27
39
For information on viewing the memory allocation of user programs, refer to the following manuals;
ROCLINK
™
800 Configuration Software User Manual (for
FloBoss
™
107) (Part D301249X012)
ROCLINK
™
800 Configuration Software User Manual (for
ROC800-Series) (Part D301250X012)
ROCLINK
™
800 Configuration Software User Manual (for
ROC800L) (Part D301246X012)
1.3.1 License Key
License keys, when matched with valid license codes, grant access to applications such as the Surface Control Manager program.
Revised January-2017 Introduction 3
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
For ROC800, the term “license key” refers to the physical piece of hardware that can contain up to seven different licenses (refer to Figure
1). Each ROC800 can have none, one, or two license keys installed. If you remove a license key after enabling an application, the firmware disables the task from running. This prevents unauthorized execution of protected applications in a ROC800.
J1
U1
DOC0422A
Figure 1-1. License Key
Note:
The Surface Control Manager program for ROC800 requires up to 3 PMSC license keys depending on your program requirement. Refer to the Note on Section 1.3 for more information regarding the program and its corresponding license key requirements.
For FB107, Remote Automation Solutions delivers software licenses on secure USB drives. You must install the PMSC license key to use the
Surface Control Manager program.
4 Introduction Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Chapter 2 – Installation
This section provides instructions for installing the Surface Control
Manager program into the ROC800 or FB107. Read Section 1.3 of this manual for program requirements.
2.1 Installing the License Key
Section 2.1.1 provides license key installation instructions for ROC800 and Section 2.1.2 provides license key installation instructions for
FB107.
2.1.1 Installing the License Key for the ROC800
If you order the Surface Control Manager program for a new FB107 or
ROC800, your FB107 or ROC800 is delivered with the license key installed. Go to Section 2.2.
If you order the program for an existing ROC800, you must install the license key yourself.
Caution
Failure to exercise proper electrostatic discharge precautions, such as wearing a grounded wrist strap may reset the processor or damage electronic components, resulting in interrupted operations.
When working on units located in a hazardous area (where explosive gases may be present), make sure the area is in a non-hazardous state before performing these procedures. Performing these procedures in a hazardous area could result in personal injury or property damage.
To install a license key:
1. Remove power from the ROC800.
2. Remove the wire channel cover.
3. Unscrew the screws from the Central Processing Unit (CPU) faceplate.
4. Remove the CPU faceplate.
5. Place the license key in the appropriate terminal slot (P4 or P6) in the CPU.
Revised January-2017
Figure 2-1. License Key Installation
6. Press the license key into the terminal unit until it is firmly seated
(refer to Figure 2).
7. Replace the CPU faceplate.
Installation 5
DOC0423A
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
8. Replace the screws on the CPU faceplate.
9. Replace the wire channel cover.
10. Restore power to the ROC800.
11. Proceed to Section 2.1.3 to verify your license keys.
2.1.2 Installing the License Key for the FB107
A license is required to use the Surface Control Manager program. To install a license on the FB107:
1. Insert the USB license key in a USB port on your PC.
2. Select Utilities > License Key Administrator > Transfer Between
DEVICE and KEY from the ROCLINK 800 menu bar. The
Transfer Licenses Between a Device and a Key screen displays:
6
Figure 2-2. Transfer Licenses Between a Device and a Key
Note: This screen has three sections. The upper portion (Licenses on Device) shows any software licenses installed on the
FB107. The middle portion (Licenses on Key) shows software licenses on the license key. The lower portion of the screen (License Key Event Log) provides a rolling log of the last eight events related to this license key.
3. Select the key-based license you want to transfer to the FB107
( PMSC , as shown in Figure 2-2).
4. Click Move to Device. ROCLINK moves the license from the key to the FB107 and updates the screen.
Installation Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 2-3. License Installed
Note: An FB107 can hold up to six different licenses, although you can install only one instance of each license on the FB107.
When you click Move to Device, ROCLINK 800 moves only one instance of the license onto the FB107 and automatically decreases the license quantity on the USB key by one.
5. Verify the license name displays in the Licenses on Device section of the screen. Proceed to Section 2.2 to download the user program.
2.1.3 Verifying the License Key Installation (for ROC800)
After you install the license key, you can verify whether the ROC800 recognizes the key. From the ROCLINK 800 screen, From the
ROCLINK 800 screen, select Utilities > License Key Administrator.
The License Key Administrator screen displays:
Revised January-2017 Installation 7
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 2-4. Transfer Licenses Between a Device and a Key
2.2 Downloading the Program
Section 2.2.1 provides downloading instructions of the Surface Control
Program for ROC800 or FB107 and Section 2.2.2 downloading instructions of the PMCB Calculation Blocks for FB107.
2.2.1 Surface Control Program
This section provides instructions for installing the program into the
Flash memory on the ROC800 or FB107.
To download the program using ROCLINK 800 software:
1. Connect the ROC800 or the FB107 to your computer using the LOI port.
2. Start and logon to ROCLINK 800.
3. Select Utilities > User Program Administrator from the
ROCLINK menu bar. The User Program Administrator screen displays (see Figure 2-5):
8 Installation Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 2-5. User Program Administrator
4. Click Browse in the Download User Program File frame. The Select
User Program File screen displays (see Figure 2-6).
Note: If you install the program in the ROC800, choose any available user program slot. If you use FB107, the program installs automatically in user program slot 5.
5. Select the path and user program file to download from the CD-
ROM. (Program files are typically located in the Program Files folder on the CD-ROM). As Figure 2-6 shows, the screen lists all valid user program files with the .tar (for ROC800) or .bin (for
FB107) extension:
Revised January-2017 Installation 9
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 2-6. Select User Program File
6. Click Open to select the program file. The User Program
Administrator screen displays:
10
Figure 2-7. User Program Administrator
7. Click Download & Start to begin loading the selected programs.
The following message displays:
Installation Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 2-8. Confirm Download
8. Click Yes to begin the download. When the download completes the following message displays:
Figure 2-9. ROCLINK 800 Download Confirmation
9. Click OK. The User Program Administrator screen displays (see
Figure 2-10). Note that:
The User Programs Installed in Device frame identifies the installed program(s).
The Status field indicates that the program is running.
Revised January-2017 Installation 11
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
12
Figure 2-10. User Program Administrator
10. Click Close. The ROCLINK 800 screen displays and the download is complete. Proceed to Chapter 3, Configuration.
2.2.2 PMCB Calculation Blocks Program
This section provides instructions for installing the PMCB Calculation
Blocks program into the Flash memory on the FB107.
Notes:
The PM Calculation Blocks program installs separately into the
FB107.
There are two versions of the PMCB Calculation Blocks program are included. Installation and operation are identical between programs, but they use different point type locations, different display numbers, and are loaded into different program slots on the
FB107. PMCB_v400_01_3.bin loads into user program location 3 and User Defined Point (UDP) 27. PMCB_v400_01_6.bin loads into user program location 6 and User Defined Point (UDP) 39. Install the program version that avoids point type conflicts with currently installed programs.
This document shows the installation of PMCB_v400_01_3.bin. The installation process and functionality is the same for all version of the Calculation Blocks program.
To download the program using ROCLINK 800 software:
1. Connect the FB107 to your computer using the LOI port.
Installation Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
2. Start and logon to ROCLINK 800.
3. Select Utilities > User Program Administrator from the
ROCLINK menu bar. The User Program Administrator screen displays (see Figure 2-11):
Figure 2-11. User Program Administrator
4. Click Browse in the Download User Program File frame. The Select
User Program File screen displays (see Figure 2-12).
5. Select the path and user program file to download from the CD-
ROM. (Program files are typically located in the Program Files folder on the CD-ROM). As Figure 2-12 shows, the screen lists all valid user program files with the .BIN extension:
Revised January-2017
Figure 2-12. Select User Program File
Installation 13
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
6. Click Open to select the program file. The User Program
Administrator screen displays. As shown in Figure 2-13, note that the Download User Program File frame identifies the selected program and that the Download & Start button is active:
14
Figure 2-13. User Program Administrator
7. Click Download & Start to begin loading the selected programs.
The following message displays:
Figure 2-14. Confirm Download
Note: For the FB107, ROCLINK800 assigns program positions based on memory allocations. For this reason, the
PMCB_v400_01_3.bin program automatically installs as program 3. For PMCB_v400_01_6.bin program automatically installs as program 6.
Installation Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
8. Click Yes to begin the download. During the download, the program performs a warm start, creates an event in the event log, and when the download completes displays the following message:
Figure 2-15. ROCLINK 800 Download Confirmation
9. Click OK. The User Program Administrator screen displays (see
Figure 2-16). Note that:
The User Programs Installed in Device frame identifies the loaded program.
The Status field indicates that the program is running.
Revised January-2017
Figure 2-16. User Program Administrator
10. Click Close and proceed to Section 3.3 – PMCB Calculation Blocks to configure the program.
Installation 15
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
2.3 MPU Loading Threshold (ROC800)
To maximize the performance of your ROC800 device, always verify the performance of specific application combinations before using them in the field to ensure the MPU load typically remains below 85% with peak MPU loading levels below 95%.
To check the current MPU load at any time, select ROC > Information
> Other Information and review the value in the MPU loading field.
Figure 2-17. MPU Loading
16 Installation Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Chapter 3 – Configuration
After you have loaded the Surface Control Manager program on the
FB107 or the ROC800, you configure the program using three programspecific screens:
PMSC Action Blocks
PMSC Utilities
PMCB Calculation Blocks
To configure the program (after logging onto ROCLINK 800 and successfully installing the program), proceed through the program screens as shown in the following sections.
You can access all the program-specific screens from the main
ROCLINK 800 screen:
Note: The configuration screens of the Surface Control Manager program for both the ROC800 and the FB107 platforms are identical.
Revised January-2017
Figure 3-1. ROCLINK 800
Configuration 17
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.1 PMSC Action Blocks Screen
The screen has five main sections:
Block Logic Operation– Use this section to define the logic for each action block.
Bypasses– Use this section to configure temporary overrides for the result of the raw action block logic.
Chain– Use this section to logically link one action block to another.
Action Output– Use this section to define any actions to be performed when the action block is “true”. These actions can include writing to a defined parameter, moving a value, or shutting down another aspect of an associated user program, such as Tank
Manager or Well Optimization.
Alarm Logging– Use this section to generate alarms in the device alarm log, based on the status changes of the action block.
To access this screen:
1. From the Directory Tree, select User Program > Program #1,
PMSC_v407_00_48blk.
2. Double-click Display #68, PMSC Action Blocks.
Note: This section shows how to access the access the Action
Blocks screen for the ROC800. To access the Action Blocks for FB107, double-click Display #28, PMSC Action Blocks.
3. Double-click #1, Block 1. The PMSC Action Blocks screen displays:
Note: Depending on the device (ROC800 or FB107) and the version of the program installed, you may have up to 144 of these screens, one for each action block.
18 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Revised January-2017
Figure 3-2. PMSC Action Blocks Screen
4. Review the values in the following fields:
Field Description
Block Logic Operation
Block Tag Sets the action block tag name.
Enable Enables the action block when checked.
Input Pt Def Sets the TLP source of the input value.
Input Value Displays the input’s live value.
Operator Selects a mathematical or logical operator from the dropdown list. Click to select a valid operator:
GT (>) – If the Input Value is greater than the
Set Pt Value for the Delay Preset time, the block is set true.
GE (>=) – If the Input Value is greater than or equal to the Set Pt Value for the Delay
Preset time, the Block is set true.
LT (<) – If the Input Value is less than the Set
Pt Value for the Delay Preset time, the block is set true.
LE (<=) – If the Input Value is less than or equal to the Set Pt Value for the Delay
Preset time, the block is set true.
Configuration 19
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
EQ (==) – If the Input Value is equal to the
Set Pt Value for the Delay Preset time, the block is set true.
NE (!=) – If the Input Value is not equal to the
Set Pt Value for the Delay Preset time, the block is set true.
Watchdog – Monitors the Input Value, if it does not change for the Delay Preset time, the block is set true.
Trip on Change – If the Input Value is different than the Set Pt Value, the block is set true.
pEdge – Monitors the Input Value for a transition from 0 to 1, block is set true for one scan.
nEdge - Monitors the Input value for a transition from 1 to 0, block is set true for one scan.
Bitwise AND (&) – Compares each bit in the
Input Value to the Set Pt Value. If both bits are true (1), the block is set true.
Bitwise OR – Compares each bit in the Input
Value to the Set Pt Value. If either bit matches, the block is set true.
Add (+) – Adds Input Value to Set Pt Value and displays the results in the Math Result field.
Subtract (-) – Subtracts the Set Pt Value from the Input Value and displays the results in the Math Result field.
Multiply (*) – Multiplies the Input Value by
Set Pt Value and displays the results in the
Math Result field.
Divide (/) – Divides the Input Value by the
Set Pt Value and displays the results in the
Math Result field.
Modulus (%) – Or remainder of the Input
Value divided by the Set Pt Value. Example:
17 modulus 3 = 2, or 17/3 = 5 with a remainder of 2 displayed in the Math Result field.
Soft Input Reset Timer – Monitors the Input
Value for a transition from 0 to 1. Once this transition occurs the block is set true and a time delay starts for the amount of seconds specified in the Delay Preset field. When the timer expires the block is set to false and the
Input Value is forced back to a zero.
Set Pt Def Selects the TLP source of the Set Pt Value.
Set Pt Value Shows the value of the point defined in the
Set Pt Def field. If you leave this field undefined, you can manually enter this value.
20 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
Preset Sets the delay in seconds. This delay is either for an on delay for logic functions or for soft input rest timer. (See function description above.)
Elapsed Shows the time delay that has elapsed, starts counting up from zero to the Preset time and status changes when the Preset time is reached.
Deadband / Math
Result
Sets the deadband for clearing the comparator logic or displays the Math Result for math functions.
Block Trip Status
(Before Bypass)
Displays the logic block trip indicator based only on the block logic operation, before any bypasses are applied.
Bypasses
Types Currently
Active
Demand Bypass
(Latched)
Shows the bypasses that are currently active.
Remote
Bypasses
Activates the manual latched bypass when selected. This value could be set or removed from an FST or from an action block.
Allows you to browse other action blocks to be used to define bypass functionality. When the remote action block is true, the bypass for this block is true.
Note: If the Use Action Block is un-checked, click to select a TLP in the system.
Valid bypass types are:
Latched – Bypassed while the Remote
Bypass block is true.
Class B – Bypassed for the amount of time in the Class B Timer field once the Remote
Bypass block is true.
Class C - Bypassed until the block clears once the Remote Bypass block is true.
Class B w/C override - Bypassed for the amount of time in the Class B Timer field or unless the Block clears before the timer expires once the Remote Bypass block is true.
Sets the timer for Class B bypass. Class B Timer
Seconds – Preset
Class B Timer
Seconds –
Elapsed
Class C
Deadband / Arm
Delay –
Deadband EU
Class C
Deadband / Arm
Delay – Preset
Shows the elapsed time for Class B bypass.
Sets the deadband for Class C bypass.
Sets the timer for Class C bypass.
Revised January-2017 Configuration 21
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
Class C
Deadband / Arm
Delay – Elapsed
Block Trip Status
(After Bypass)
Chain
Shows the elapsed time for Class C bypass.
Shows the combined status of the logic block and the bypass block. For example, if the logic block is true and the bypass is not in effect, then the status is true. If the logic block is true and the bypass is in effect, then the status is false.
To Allows you to browse a previous action block to compare results with based on the chain type.
Type Sets the logic of chain. Click to select an available logic type:
AND – If the chained block and current block are true, the Chain Trip Status is true.
OR – If the chained block or current blocks are true, the Chain Trip Status is true.
NAND – If the chained block and current block are false, the Chain Trip Status is true.
XOR Either – If one of the chained block and current block is true and the other false, the
Chain Trip Status is true.
XOR Local – If the chained block is set to false and current block is set to true, the
Chain Trip Status is true.
XOR Remote – If current block is set to false and chained block is set to true, the Chain
Trip Status is true.
Seal-In – If the current block is set to true and the previous block or the current chain status are set to true, the Chain Status is true until the current block status after bypass is false
PWM Lo-Duty – If the current block is set to true and the previous block is false, the Chain
Status is true for one second then toggles false for the remaining seconds in the Chain
Delay Preset time. The cycle repeats while the condition remains the same, the Preset time must be more than two seconds
PWM-Hi-Duty – If the current block is set to true and the previous block is false, the Chain
Status is false for one second then toggles true for the remaining seconds in the Chain
Delay Preset time. The cycle repeats while the condition remains the same, the Preset time must be more than two seconds
Is End of Chain Indicates when this block is the end of a chain of previous blocks.
Delay Sets the delay Preset timer and shows the
Elapsed time.
22 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
OR Chain First
Out
Shows the number of the action block that is tripped in a chain of or blocks.
Chain Trip Status Shows the number of the action block that is tripped in a chain of OR blocks.
Note: This field displays only when the Chain
Type is OR.
Action Output
Block/Chain Trip Selects the status that trips the output. Valid values are:
True if Block True – Output is driven true if the Block Trip Status (After Bypass) is true on this action block.
True if Chain True – Output is driven true if the Chain Status is true on this action block.
True if Either True – Output is driven true if the Block Trip Status (After Bypass) or the
Chain Status is true on this action block.
True if Both True – Output is driven true if the Block Trip Status (After Bypass) and the
Chain Status is true on this action block.
Instance Trip
Status
Shows the status of the Output Action.
Type Selects the type of Output desired from this action block. Valid values are:
PSD (Permanent Shutdown) – When selected a submenu of available Applications
(Domains) displays allowing you to select the instance from the other applications you wish to permanently shutdown. A manual reset is required after the shutdown occurs.
TSD (Temporary Shutdown) – When selected a submenu of available Applications
(Domains) displays allowing you to select the instance from the other applications you wish to temporarily shutdown. An automatic reset occurs after the shutdown clears.
DO (Binary Action) – Allows you to select a
Binary Field to which the signal is sent.
Discrete signals can be sent in the following format:
Force 1True & 0False
Force 0True & 1False
Poke 1True
Poke 0True
Poke 1True & 0False
Poke 0True & 1False
Force 1True & Poke 0False
Force 0True & Poke 1False
Force 1True
Force 0True
Revised January-2017 Configuration 23
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
24
Field
SSD Domains
Description
Move Value – Two Functions:
1. When using Math Operators, the Result is moved to the defined Output TLP.
2. When using Comparator Operators, the
Input Value is moved to the Output TLP when the block is true.
VAL (to Result Reg) – Pushes the value in the Output TLP into the internal Result
Register of PMSC.
SAV (from Result Reg) – Pulls the internal
Result Register value from PMSC and pushes it into the Output TLP.
No Action – No output action will take place when the block is set true.
Provides the ability to shutdown aspects of other associated programs (such as Tank
Manager or Well Optimization), based on the result of the action block. Once a domain has been selected, the instances of that domain for which the block action should apply must also be selected.
PMTM Wells – Sets either a (Permanent
Shutdown) PSD or a (Temporary Shutdown)
TSD to the associated Well defined in PM
Tank Manager, Allocated Well Values/Trip
Point.
PMTM Loadouts – Sets either a PSD or TSD to the associated Haul HMI/Station
Permissive. A PSD stops a haul in progress and a TSD pauses a haul in progress.
PMv 3.3x Wells – Sets either a PSD or TSD to the associated Production Manager version 3 wells.
PMWO Wells – Sets either a PSD or TSD to the associated well in PMWO 4.x.
PMSC Effects – Sets a PSD or TSD to the associated effect in PMSC Utilities.
Note: The SSD Domains are only visible when the Action Output Type has been set to PSD or TSD.
Alarm Logging
Alarm Logging Activates logging in the ROC Alarm Log if the action block sets (if the Log Inst Trips option is selected) or clears (if the Log Inst Clears option is selected).
First Out Shows the First Out tag of the action block that was first tripped in a chain for which the current block is a part.
5. Click Apply to save your changes.
6. Click Close to return to the ROCLINK 800 screen. Proceed to
Section 3.2 to configure the PMSC Utilities Screen.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.2 PMSC Utilities Screens
The PMSC Utilities screen allows you to configure the following tabs:
PMSC Effects
Time Count
Accumulators/Outputs
Alarm Blocks
Action Block Domain Statuses
To access this screen:
1. From the Directory Tree, select User Program > Program #1,
PMSC_v407_00_48blk.
2. Double-click Display #71, PMSC Utilities.
Note: This section shows how to access the access the Utilities screen for the ROC800. To access the Action Blocks for
FB107, double-click Display #31, PMSC Utilities.
3. Double-click #1, Inst 1. The PMSC Utilities screen displays:
Revised January-2017 Configuration 25
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
26
Figure 3-3. PMSC Utilities Screen
4. Follow Section 3.2.1 through Section 3.2.4 to configure the PMSC
Effects, Time Count, Accumulations/Outputs, and the Action Block
Domain Statuses tabs.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.2.1 PMSC Utilities Screen – PMSC Effects Tab
Use this screen (which displays when you first access the PMSC
Utilities screen) to configure various aspects of an effect triggered by an action block. Each effect represents a particular action that is taken when the action blocks that are linked to it are tripped or cleared. The action that is taken is the writing of a value out to a user defined parameter. Different values to be written are defined for when the effect is tripped vs. when the effect is not tripped. This allows for creating of custom actions, such as driving a discrete valve or a panel annunciation.
In addition to configuring effects, this tab allows you to configure outputs separately. You can:
Control the output by multiple action blocks.
Write values to analog type controls (analog outputs, PID setpoints, and so on).
Revised January-2017 Configuration 27
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
28
Figure 3-4. PMSC Utilities Screen – PMSC Effects tab
1. Review and complete the values in the following fields:
Field
Effect Tag
Enable
PtDef
Value When
Tripped
Value When Not
Tripped
Description
Identifies the specific effect being defined.
Enables the effect.
Sets the output to be driven.
Sets the value to be driven to the PtDef when the effect is Tripped (true).
Sets the value to be driven to the PtDef when the effect is Not Tripped (false).
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
Output the Value
When Not
Tripped
Assert Output
Continuously
During
Allows the output to be either driven or not driven when the effect is false. You typically use this option when the effect needs to be manually reset. Select this option to enable the effect to drive the signal each way. If you do not select this option, the signal is driven only when the effect is true.
Selects how to assert effect output to the parameter defined by the PtDef field. When the “Neither State” option is selected, then the output parameter is written to one time on state change, and not written to again (until the next state change). When the other options are selected (“Tripped State Only”,
“UnTripped State Only”, and “Both States”), the configured value is written to the output parameter continuously.
Cur Outp Value Shows the current output value.
Effect Trip Status Indicates the status of the effect trip. Valid values are 1 (tripped, red box with yellow letters; active) and 0 (not tripped, blue box with white letters; inactive).
First-Out Int#
Click to select valid options.
Neither State
Tripped State Only
UnTripped State Only
Both States
First-Out Tag
Trips Require
Reset
Shows the numerical values of the action block that first tripped this effect.
Shows the tag of the action block that tripped this effect.
The user program automatically checks this box upon a PSD type trip that is connected to the effect.
The user program automatically unchecks this box upon a TSD type trip that is connected to the effect.
A user can override the automatic selection after the trip has occurred (check or uncheck it).
When the box is checked, even though action block that caused the trip is in the cleared
(normal) state, the effect will stay tripped until a reset action is performed.
When the box is unchecked the effect is cleared as soon as any tripped action blocks
(connected to the effect) are cleared.
Revised January-2017 Configuration 29
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
2.
Field Description
Remote Reset
Command TLP
Click to select a TLP in the ROC800 or FB107 used to reset this effect. For example, a TLP you might select is a discrete input or soft point value. When the effect is ready to be reset, any positive value written to the TLP performs the reset.
The same remote TLP may be used to reset several different effects.
The user program automatically resets the value of the remote TLP back to zero after processing.
Note: This field shows only if you check or select the Trips Require Reset option.
Reset Command Identifies a local reset field which can be mapped to HMIs, etc. Any positive value entered will cause a reset action. The value in this field is reset to zero after processing. This field is entirely independent fr om the “Remote
Reset Command TLP ” field. The two fields logically act as an “OR” in resetting the effect.
Click Apply to save any changes you have made to this screen.
3. Proceed to Section 3.2.2 to configure the Utilities Screen – Time
Count tab.
3.2.2 PMSC Utilities Screen – Time Count Tab
Use this screen to configure the time counter of the Surface Control manager program. Use this utility to set “timers” for equipment on a well site to remind you to perform preventive maintenance (such as for a compressor after a certain number of hours).
To access this screen:
1. Select the Time Count tab on the PMSC Utilities screen. The
Time Count screen displays:
30 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 3-5. PMSC Utilities Screen – Time Count tab
Revised January-2017 Configuration 31
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
2. Review the values in the following fields:
Field
Counter Tag
Enable
Run-Time Pt Def
Value
Cur Status
Update Interval
Mins Tdy
Mins Ydy
Hours Tdy
Hours Ydy
Pct Tdy
Pct Ydy
Mins TMon
Mins PMon
Hours TMon
Hours PMon
Pct TMon
Pct PMon
Contact Hr
Description
Identifies the specific counter being defined.
Select to enable the time counter.
Sets the point to be monitored to define if the
On Counter or the Off Counter Advances.
This value is compared using the following logical functions:
GT (>)
GE (>=)
LT (<)
LE (<=)
EQ (==)
NE (!=).
Defines the value to be compared to the Run-
Time Pt Def.
Indicates if comparison statement written above is True (ON) or False (OFF).
Defines how often the accumulating counters update their associated values in the ROC.
The calculation always runs every second, but to save MPU load the updating accumulators are only written out to the ROC points based on this parameter.
This display-only field shows Accumulated
On minutes and Off minutes Today.
This display-only field shows Accumulated
On minutes and Off minutes Yesterday.
This display-only field shows Accumulated
On hours and Off hours Today.
This display-only field shows Accumulated
On hours and Off hours Yesterday.
This display-only field shows Percent of time
On and Off Today.
This display-only field shows Percent of time
On and Off Yesterday.
This display-only field shows Accumulated
On minutes and Off minutes This Month.
This display-only field shows Accumulated
On minutes and Off minutes Previous Month.
This display-only field shows Accumulated
On hours and Off hours This Month.
This display-only field shows Accumulated
On hours and Off hours Previous Month.
This display-only field shows Percent of time
On and Off This Month.
This display-only field shows Percent of time
On and Off Previous Month.
Sets the hour, in military hour format, at which the accumulators roll up the Days On and Off
Times.
32 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field
Clear Now!
Description
Select this option to clear all accumulators and reset them to zero. The system automatically clears this field checkbox is auto cleared and the accumulation for On and Off time begin anew.
3.
4.
Click Apply to save any changes you have made to this screen.
Proceed to Section 3.2.3 to configure the PMSC Utilities Screen –
Accumulators/Output tab.
3.2.3 PMSC Utilities Screen – Accumulators/Outputs Tab
The functionality on this screen changes, depending on the mode you select. There are 4 possible modes:
Accumulate a Rate – This function provides daily, monthly, and running total accumulation for a flowrate you specify. The flowrate comes from a metering device providing a rate in the form of an analog or HART input, a pulse input EU value rate, or a flow calculation you implement. The flowrate integrates once per second, and that incremental amount of accumulation adds to the daily, monthly, and running totals.
Accumulate a Running Total – This functionally also provides daily, monthly, and running totals. The totals, however comes from a smart meter or other device that provides an incremental accumulator value (commonly provided to the ROC800 or FB107 from a Modbus connection). The program determines the increment per second based on this accumulator input. The incremental values are added to the daily, month, and running totals. If applicable, the rollover of this incremental accumulator input value is automatically determined.
Output a 4-20mA Signal – This option provide a method to link a process variable from the internal database of the device to an
Analog Output (AO) point, therefore providing a 4-20 mA signal.
The signal can be of any form, but is commonly used for flowrate values, valve positions, or other process variables you send to another device or system.
Output a Pulse at an Interval – Allows you to generate a reoccurring pulse signal to another devices or system. Typically, this is used to send a pulse (via a ROC800 or FB107 discrete output) that represents an accumulated amount of flow. For example, If you have a daily flowrate in MCF, you can generate a pulse for every unit of
MCF that is measured by the ROC800 or FB107.
To access this screen:
1. Select the Accumulators/Outputs tab on the PMSC Utilities screen.
The Accumulation/Outputs screen displays:
Revised January-2017 Configuration 33
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
34
Figure 3-6. PMSC Utilities Screen – Accumulators/Outputs tab
2. Review the values in the following fields:
Field
Accum/Out Tag
Enable
Description
Identifies the specific accum/output being defined.
Enables this instance of the
Accumulator/Output.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field
Mode
Input Def
Time Basis
Output Def
Update Interval
Contact Hour
Cur Month
Cur Day
Description
Selects the type of accumulator or output for this instance. Click to select a valid option:
Accumulate a Rate – Accumulates the flow rate defined in the Input Def field.
Accumulate a Running Total – Accumulates the accumulated value defined in the Input
Def field. This should be an accumulator that does not reset each day at contract hour. Rollover is handled internally every scan period.
Output a 4-20ma Signal – Sends the value specified in the Input Def field to the AO defined in the Output Def and forces the 4-20 mA signal to update.
Generate a Pulse at an Interval – Sends a
Pulse Command to the DO defined in the
Output Def parameter when the flow rate defined in the Input Def parameter accumulates a value greater than the value specified in the DO Out Pulse Interval.
Defines the input used in the mode selected.
Defines the frequency of the flow rate in the
Input Definition. Available time periods are
Second, Minute, Hour and Day. For all modes besides the 4-20 mA output mode.
Sets the output to be used. In the 4-20 mA
Output and Pulse Output mode this should point to an AO or a DO. In the Flow
Accumulation mode it should point to a softpoint value. The selected softpoint value defines the first of seven consecutive values to store the following accumulators:
1 = Today
2 = Yesterday
3 = This Month
4 = Previous Month
5 = Running Accum
6 = This Hour
7 = Previous Hour
Defines how often the accumulators update their associated values in the ROC. The calculation always runs every second, but to save MPU load the program only writes updated accumulator values to the ROC points based on this parameter.
Sets the hour, in military times, at which the accumulators roll up the Days Accumulated
Flows.
Shows the chronological number of the current month. Valid values are 1-12.
Shows the chronological number of the current day. Valid values are 1-31.
Revised January-2017 Configuration 35
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field
Flags
Description
Provides functions for managing and clearing the accumulator values being stored in an associated SoftPoint.
Click to select the option:
Normal Operations – Operates as configured
Force End Of Day – Forces all Accumulators to roll up at that instant and restart their daily at zero
Force end of Month – Forces all Accumulators to roll up at that instance, including Monthly
Flush Running Accum – Clears the daily
Accumulator but does not roll up
Cold Start Accumulator Set – Clears all
Accumulators
3. Click Apply to save any changes you have made to this screen.
4. Proceed to Section 3.2.4 to configure the PMSC Utilities Screen –
Alarm Blocks tab.
3.2.4 PMSC Utilities Screen – Alarm Blocks Tab
Use this screen to configure the alarm point of the Surface Control manager program. Use this utility to set three alarm point mechanisms per instance.
To access this screen:
1. Select the Alarm Blocks tab on the PMSC Utilities screen. The
Alarm Blocks screen displays:
36 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Revised January-2017
Figure 3-7. PMSC Utilities Screen – Alarm Blocks tab
2. Review the values in the following fields:
Field
Alarm Tag
Alarm Point
Definition
Alarm Point
Current Value
Description
Sets a 10-character (for the ROC800) or an 8character (for the FB107) alarm identification.
Click to designate the TLP for the alarm to be monitored. This field shows a valid entry
(not Undefined) the value of the specified point will be displayed in the field on the right
(Alarm Point Current Value) whether alarming is enabled or not.
Displays the value of the point specified to the left (Alarm Point Definition). If the Alarm Point
Definition is Undefined or Scanning is set to
“Disable” the current value or any userentered value here will remain unchanged.
Configuration 37
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
38
Field Description
Alarm Enable
Alarm Type
Selects to Enable the Alarm Point Current
Value is monitored for alarm conditions and the alarm code can be a positive number (an alarm condition exists).
Selects to Disable the alarm code will always be zero.
Selects to Analog, the Alarm Point Current
Value is compared to each of the four possible alarm type setpoints (Low, Low Low,
High, High High) for setting alarms along with the Deadband value for clearing alarms.
Selects to Boolean, the Alarm Point Current
Value is compared Boolean Alarm. A Boolean
Alarm is generated when the current value equals the Boolean Alarm “Set on” value.
Note: Zero and One are the only legal values for the Boolean Alarm Type. If the
Alarm Point Current value can possibly be any other value the Alarm Type should be set to Analog as no Boolean alarm will be generated for values no exactly equal to the Boolean Alarm
“Set on” value.
SRBX
RBX on Set Selects to Enable an RBX attribute is set for the alarm when any “Alarm Set” is logged.
This causes any Comm Port with SRBX Mode
Enabled to process the alarm setting.
Selects Disable ….
RBX on Clear Selects to Enable an RBX attribute is set for the alarm when any “Alarm Clear” is logged.
This causes any Comm Port with SRBX Mode
Enabled to process the alarm setting.
Selects Disable ….
Scanning Selects to Enable the Alarm Point Current
Value is the value of the point defined in the
Alarm Point Definition field.
Selects to Disable the program and will not change the Alarm Point Current Value.
High High
High
Sets the High High alarm value. The Alarm
Point Current Value is greater than or equal to the High High value. The alarm remains in effect until the Alarm Point Current Value goes less than High High Value minus the
Deadband value.
Note: This field displays only if you select
Analog in the Alarm Type.
Sets the High alarm value.
The Alarm Point
Current Value is greater than or equal to the
High value. The alarm remains in effect until the Alarm Point Current Value goes less than
High Value minus the Deadband value.
Note: This field displays only if you select
Analog in the Alarm Type.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field
Low
Low Low
Boolean Alarm
Deadband
Alarm Code
Description
Sets the Low alarm value. The Alarm Point
Current Value is less than or equal to the Low value. The alarm remains in effect until the
Alarm Point Current Value goes greater than
Low Value plus the Deadband value.
Note: This field displays only if you select
Analog in the Alarm Type.
Sets the Low Low alarm value. The Alarm
Point Current Value is less than or equal to the Low Low value. The alarm remains in effect until the Alarm Point Current Value goes greater than Low Low Value plus the
Deadband value.
Note: This field displays only if you select
Analog in the Alarm Type.
Sets the boolean value that will determine when an alarm is triggered. For example, if the input alarm point definition is a discrete value where normal operation is a value of
“0”, the option for “Set on 1” should be selected.
Note: This field displays only if you select
Boolean in the Alarm Type.
Sets the Deadband value.
Note: This field displays only if you select
Analog in the Alarm Type.
This display-only field shows the alarm values:
1 = Low Alarm
2 = Low Low Alarm
4 = High Alarm
8 = High High Alarm
32 = Boolean Alarm
128 = Manual Alarm
3. Click Apply to save any changes you have made to this screen.
4. Proceed to Section 3.2.5 to configure the PMSC Utilities Screen
– Action Block Domain Statuses tab.
3.2.5 PMSC Utilities Screen – Action Block Domain Statuses Tab
The Action Block Domain Statuses reports the health of other associated user programs (if installed), such as Tank Manager or Well
Optimization. To access this screen:
To access this screen:
1. Select the Action Block Domain Statuses tab on the PMSC
Utilities screen. The Action Block Domain Statuses screen displays:
Revised January-2017 Configuration 39
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
40
Figure 3-8. PMSC Utilities Screen – Action Block Domain Statuses tab
2. Review the values in the following fields:
Field
Point Number
Description
Selects the logical instance you want to configure.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
Tank Mgr Well #
1
Shows the status of any Tank Manager
Allocation Wells. The number beside the field name refers to the point number of the Tank
Manager allocation well instance you are viewing. This is not necessarily related to the
PMSC Effect or utilities on this display (of the same logical instance). If you change the
Point Number, this field can provide the status of up to 4, 8, or 12 wells, depending on the version of the Tank Manager program you install.
Note: The Tank Manager program supports up to 12 allocation wells, thus the numbers greater than 12 have no configuration effect.
SSD Set This section is checked if the System Shut
Down (SSD) is set for this well.
PSD Set This section is checked if the Permanent
Shutdown (PSD) is set to this well.
TSD Set This section is checked if the Temporary
Shutdown (TSD) is set to this well.
Trip Code Sets the numerical code of First Out action block that tripped this instance.
Tank Mgr Load
Out # 1
Shows the status of any Tank Manager Truck
Load Out Terminals. The number beside the field name refers to the point number of the
Tank Manager Load Out Terminal instance you are viewing. This is not necessarily related to the PMSC Effect or utilities on this display (of the same logical instance). If you change the Point Number, this field can provide the status of up to 6 loading terminals in the ROC800 and 2 loading terminals in the
FB107.
Note: The Tank Manager program supports up to 2 (for FB107) or 6 (for ROC800) loading terminals, thus the numbers greater than 2 (for FB107) or 6 (for
ROC800) have no configuration effect.
SSD Set This section is checked if the System Shut
Down (SSD) is set to this Load Terminal.
PSD Set This section is checked if the Permanent
Shutdown (PSD) is set to this Load Terminal.
TSD Set This section is checked if the Temporary
Shutdown (TSD) is set to this Load Terminal.
Trip Code Sets the numerical code of First Out Action
Block that tripped this instance.
Revised January-2017 Configuration 41
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
Well Opt Mgr
Well # 1
Shows the status of any Well Optimization
Manager Wells. The number beside the field name refers to the point number of the well instance you are viewing. This is not necessarily related to the PMSC Effect or utilities on this display (of the same logical instance). As you change the Point Number, this field can provide the status of up to 4, 8, or 12 wells, depending on the version of the
Well Optimization Manager program you install.
Note: The Well Optimization Manager program supports up to 12 optimization wells, thus the numbers greater than
12 have no configuration effect.
SSD Set This section is checked if the System Shut
Down (SSD) is set to this well.
PSD Set This section is checked if the Permanent
Shutdown (PSD) is set to this well.
TSD Set This section is checked if and (Temporary
Shutdown) TSD is set to this well.
Trip Code Sets the numerical code of First Out Action
Block that tripped this instance.
PM v3.3x Well # 1 Shows the status of any Production Manager version 3 Wells. The number beside the field name refers to the point number of the well instance you are viewing. This is not necessarily related to the PMSC Effect or utilities on this display (of the same logical instance). If you change the Point Number at the top of this display, this field can provide the status of up to 4 wells provided by
Production Manager version 3.
Notes:
The Well Optimization Manager program supports up to 4 optimization wells, thus the numbers greater than 4 have no configuration effect.
These domain statuses are provided for backwards compatibility with previous versions of Production Manager. If
Production Manager version 3.3x is in use, then these domain statuses are applicable. If Well Optimization Manager is in use (or no Well Optimization program), then these domain statuses are NOT applicable. This is not valid if you install both the PM v3.3x and the
Well Optimization Manager programs in the same unit.
SSD Set This section is checked if the System Shut
Down (SSD) is set to this well.
PSD Set This section is checked if the Permanent
Shutdown (PSD) is set to this well.
42 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
TSD Set This section is checked if and Temporary
Shutdown (TSD) is set to this well.
Trip Code Sets the numerical code of First Out Action
Block that tripped this instance.
PMSC Effect # 1 Shows the domain status of PMSC Effects.
The number beside the field name refers to the point number of the instance or utilities you view. This can be up 12, 24, or 36 depending on your user program version. See program specifics note in Section 1.3.
SSD Set This section is checked if the System Shut
Down (SSD) is set to this Effect.
PSD Set This section is checked if the Permanent
Shutdown (PSD) is set to this Effect.
TSD Set This section is checked if the Temporary
Shutdown (TSD) is set to this Effect.
Trip Code Sets the numerical code of First Out action block that tripped this instance.
3. Click Apply to save any changes you have made to this screen.
4. Proceed to Section 3.3 to configure the PMCB Calculation Blocks.
3.3 PMCB Calculation Blocks
The PMCB Calculation Blocks display allows the configuration of up to four inputs/input arrays and up to three calculations per instance. A 10character tag field is provided for each input and calculation.
To access this screen:
1. From the Directory Tree, select User Program > Program #1,
PMSC_v407_00_48blk.
2. Double-click Display #218, PMCB Calculation Blocks.
Note: This section shows how to access the access the PMCB
Calculation Blocks screen for the ROC800. To access the
PMCB Calculation Blocks for FB107, double-click Display
#27, PMCB Calculation Blocks or Display #39, PMCB
Calculation Blocks.
3. Double-click #1, Calculation Block 1. Select the Calc Blocs tab and the screen displays:
Revised January-2017 Configuration 43
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
44
Figure 3-9. PMCB Calculation Blocks- Calc Blocks tab
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
4. Review and complete the values in the following fields:
Field Description
Enabled Executes calculations, when selected. Any defined inputs will be updated (displayed) wheth er the “Enabled” checkbox is checked or not.
Default: Unchecked
Description Sets a 20-character calculation instance identification.
Input Variables
Description Sets the input (defined at Input Definition).
Input Definition Defines the inputs to be used in the calculation.
The input selected is either a single data point or the starting parameter of an array of data points.
Default: Undefined
Qty in Array Sets the quantity of data points for the defined input. Arrays are automatically indexed by parameter (softpoints and FST registers) or by instance (all others). If you enter a number that exceeds the maximum quantity permitted, the program will change the entry to the maximum quantity.
Default: 1
Array quantity limits are:
1. Logical (Instance) Indexing:
I/O Card Point Types: Currently limited to the quantity of channels on the physical
IO card.
Non-I/O Card Point Types: Limited to the total number of instances and not to exceed 40 bytes (example 10 floats maximum).
2. Parameter Indexing:
Soft Point parameters and FST Registers
(all other arrays use logical indexing): All contiguous parameters must be the same data type as the defined parameter and not exceed 40 bytes.
Effectively: 50 doubles, 10 floats, 10
shorts or 10 bytes
Value Sets the value of the defined data point. If the array quantity is greater than one, this field automatically hides itself.
Calculation
Calculation
String
You enter a 40-character free-form text mathematical equation or logical expression.
If you enter an invalid expression, a carat will appear under the left most invalid character.
Validated Validates each calculation string upon change. If the string is valid the program checks this box and if “Enabled” is checked, the calculation is performed.
Revised January-2017 Configuration 45
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Field Description
Error Number Displays the character position of the first error (left to right) if the calculation string is invalid. If the calculation string is valid, the value is set to zero.
Char Displays the invalid character reference in the
“Error Number” filed. When the calculation string is valid, this field is blank.
Results
Results
Description
Results Value
You enter a 10-character text to describe the results (calculation).
Displays the numerical result of the calculation. If the calculation contains a
Boolean Fan Out (BFO()), Integer Fan Out
(IFO()) or For Loop (FOR()) function, the result value displayed may be the first of an array of values (indexed by parameter only).
Results Output
Definition
Defines the output point of the result value. If the calculation contains a Boolean Fan Out
(BFO()), Integer Fan Out (IFO()) or For Loop
(FOR()) function, the defined point may be the first of an array of points (indexed by parameter only).
5. Select the Supported Functions tab and the screen displays:
46 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Figure 3-10. PMCB Calculation Blocks- Supported Functions tab
For more details, refer to Appendix A – PMCB Calculation Blocks –
Supported Functions.
Revised January-2017 Configuration 47
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.4 Saving the Configuration
Whenever you modify or change the configuration, it is a good practice to save the final configuration to memory. To save the configuration:
1. Select ROC > Flags. The Flags screen displays:
48
Figure 3-11. Flags
2. Click Save Configuration. A verification message displays:
Figure 3-12. Save Verification
3. Click Yes to begin the save process. The Flash Write Status field on the Flags screen displays In Progress. When the Save Configuration completes, the Flash Write Status field on the Flags screen displays
Completed.
4. Click Update on the Flags screen. This completes the process of saving your new configuration.
Note: For archive purposes, you should also save this configuration to your PC’s hard drive or a removable media (such as a flash drive) using the File > Save Configuration option on the ROCLINK 800 menu bar.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.5 Sample Configurations
This section presents several sample configurations. While these examples may not precisely conform to your site, they may provide useful guidelines on how to implement similar controls at your site.
3.5.1 Controlling a Pump based on Tank Level
7
3
4
1
2
5
6
4
Figure 3-13. PMSC Action Blocks - Controlling a Pump based on Tank Level
1. Browse for the Tank Level Input using the Input Pt Def TLP selection.
2. Select the operator. In this case, the pump needs to start when the level is greater than [GT (>)] the Set Pt Value.
3. Specify the Set Pt Value at which the pump is to start.
4. Specify the Deadband. The difference between the Set Pt Value and the deadband is the level at which the pump stops. In this case, the pump starts at 12 feet rising and stops at 4 feel falling (12 -8 =
4).
5. Define the Action Output Type. In this case, the program writes to a DO directly.
Revised January-2017 Configuration 49
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
6. Browse for the DO to be driven using the Action Item Pt Def.
7. Enable the action block and Apply.
Optional considerations:
A delay time could be added to eliminate spikes on the trip point.
An effect could be driven rather than writing directly to an output.
3.5.2 Connecting Two Blocks with an AND Statement
50
Figure 3-14. PMSC Action Blocks – Connecting two Blocks with an AND statement
In this case, two Hi Levels on separate tanks must both trip in order to shut down a well. Configure Hi Level 1 as shown in Figure 3-14.
Figure 3-15 shows the configuration of Hi Level 2.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
6
3
1
2
5
4
Figure 3-15. PMSC Action Blocks – Configuring High Level 2
1. Connect Hi Level 2 to Hi Level 1 by browsing for the previous block.
Note: Chained blocks always reference a previous block and never the following block.
2. Select AND as the Chain Type.
3. Since this block controls the output, set the Block/Chain Trip to
True if Chain True.
4. Select PSD as Action Output Type (since, in this case, the action is to permanently shut down a well)
5. Select the version of the Surface Control Manager program you preinstall.
6. Select the Well instance.
7. Click Apply to save your changes.
Revised January-2017 Configuration 51
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.5.3 Connecting Two Block with an OR Statement
1
2
52
Figure 3-16. PMSC Action Blocks – Configuring Lo Level 1
In this case, either of two Lo Levels on separate tanks can shut down a
Loadout Terminal and trip an ESD. Configure Lo Level 1 as shown in
Figure 3-16.
1. Configure an action block to monitor a level transmitter and trip when the level reaches less than 4 units, after an elapsed time of 5 seconds.
2. Configure the Action Output Type to PSD – to permanently shut down the LoadOut Terminal #1 and trip Effect #1.
3. Configure Lo Level 2 as shown in Figure 3-17.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
1
2
Figure 3-17. PMSC Action Blocks – Configuring Lo Level 2
1. Configure an action block to monitor a level transmitter and trip when the level reaches less than 4 units, after an elapsed time of 5 seconds.
2. Configure the Action Output Type to PSD – to permanently shut down the LoadOut Terminal #1 and trip Effect #1.
3. Consequently, either an action block, Lo Level 1, or Lo Level 2 trips the Loadout Terminal and the ESD effect.
Revised January-2017 Configuration 53
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
54
Figure 3-18. PMSC Utilities – Configuring ESD
See Section 3.2.1 in this manual for further information on configuring an effect.
Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.5.4 Setting Up a Class B Bypass
1
Figure 3-19. PMSC Action Blocks – Setting up a Class B Bypass
1. Configure an action block to monitor a start signal. a. In this case monitor a DI for a Positive Edge Transition (pEdge). b. This block goes true for one scan.
Revised January-2017 Configuration 55
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
1
2
3
Figure 3-20. PMSC Action Blocks – Configuring Lo Line
To configure an action block that needs to be bypassed for a period of time:
1. Browse for the action block that monitors the Start Action.
2. Select Class B as the Remote Bypass type.
3. Enter the amount of time to bypass this block in the Class B Timer
Seconds Preset once the Start Action is true.
56 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
3.5.5 Creating a Timed Maintenance Bypass
1
Figure 3-21. PMSC Action Blocks – Creating a Timed Maintenance Bypass
Configure an action block to monitor a softpoint value that is not connected to real IO (such as softpoint byte field).
1. Use the Operator Soft Input Reset Timer.
2. Set the amount of time this block is true in the Delay Preset field once the Input Value is true.
3. When the Delay Preset time expires, the block goes false.
Revised January-2017 Configuration 57
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
1
2
Figure 3-22. PMSC Action Blocks – Configuring Hi Line
To configure an action block needing a timed maintenance bypass:
1. Select the action block that monitors the Maintenance Bypass function.
2. Select Latched for the Remote Bypass.
3. The block is bypassed as long as the MaintBypass action block remains true.
58 Configuration Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Chapter 4 – Reference
This section provides information of point types and parameters used by the Surface Control Manager and Calculation Blocks program.
For Action Blocks
Point Type 68 (ROC800)
Point Type 28 (FB107)
For Utilities
Point Type 71 (ROC800)
Point Type 31 (FB107)
For Calculation Blocks
Point Type 218 (ROC800)
Point Type 27 (Slot #3) or Alternate #39 (Slot #6) (FB107)
Revised January-2017 Reference 59
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
4.1 Point Type 68/28: Action Blocks
Point type 68 (for ROC800) or point type 28 (for FB107) contains the parameters for configuring the action blocks. For the ROC800, the program maintains 48, 96, 144 or 192 instances of this point type (based on the size of the installed program); for the FB107, the program maintains 48 instances of the point type.
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
0
Name
Block Tag
Access
R/W
System or User
Update
User
1
2
3
4
5
Enable
Input Pt Def
Input Value
Statement Operator
Setpoint Def
R/W
R/W
R/O
R/W
R/W
User
User
System
User
User
Data
Type
AC10
UINT8
TLP
FLOAT
TLP
FLOAT
Length
10
1
3
4
1
3
Range
0x20
0x7E for each ASCII character
0 - 1
Any Valid IEEE numeric TLP
Any floating point number
0 - 17
Any Valid IEEE numeric TLP
Default
Block #”
(# = logical number)
0
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the tag name for action block.
0,0,0
0.0
0,0,0
0.0
4.03.05 Enables action block.
0 = Disabled
1 = Enabled
4.03.05 Sets the TLP source of the input value.
4.03.05 Displays the input value from the TLP.
4.03.05 Selects a logical or mathematical operator.
0 = GT (>)
1 = GE (>=)
2 = LT (<)
3 = LE (<=)
4 = EQ (==)
5 = NE (!=)
6 = Watchdog
7 = Trip On Change
8 = pEdge
9 = nEdge
10 = Bitwise AND (&)
11 = Bitwise OR
12 = Add (+)
13 = Subtract (-)
14 = Multiply (*)
15 = Divide (/)
16 = Modulus (%)
17 = Soft Input Reset Timer
4.03.05 Selects the TLP source of the
Setpoint value.
60 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
6
Name
Setpoint Value
Access
R/W
System or User
Update
User
Data
Type
UINT16
Length
4
7 Delay Sec Preset
8
9
Delay Sec Elapsed
Action Db Result
10 Refined Block Status
11 Block Action Type
12 Block Action Item Pt Def R/W
13 Block DO Behavior
Revised January-2017
R/O
R/W
R/O
R/W
R/W
R/W
System
User
System
User
User
User
User
UINT16
FLOAT
UINT8
TLP
UINT8
TLP
UINT8
2
2
4
1
1
3
1
Reference
Range
Any floating number
0 - 65535
0 - 65535
Any floating number
0 - 1
0-6
Any Valid IEEE numeric TLP
0 - 9
Default
0
0
0.0
0
0,0,0
0
0,0,0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Displays live Set Pt Value from
TLP or user entered manual value.
4.03.05 Sets the delay in seconds that is either for an on delay for logic functions or for soft input rest timer.
4.03.05 Shows the delay elapse time.
4.03.05 Sets the Deadband for logic operators or math result for mathematical operators.
4.03.05 Shows the block trip status after bypass.
0 = False
1 = True
4.03.05 Sets the Action Output type.
0 = PSD (Permanent
Shutdown)
1 = TSD (Temporary
Shutdown)
2 = DO (Binary Action)
3 = Move Value
4 = VAL (to Result Register)
5 = SAV (from Result Register)
6 = No Action
4.03.05 Sets the action Item Pt Def TLP selection, only visible with DO,
Move Value, VAL, and SAV.
4.03.05 Selects the Action Output DO
(Binary Action) behavior.
0 = Force 1True & 0False
1 = Force 0True & 1False
2 = Poke 1True
3 = Poke 0True
4 = Poke 1True & 0False
5 = Poke 0True & 1False
6 = Force 1True & Poke 0F
7 = Force 0True & Poke 1F
8 = Force 1True
9 = Force 0True
61
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
14
Name
Raw Block Status
Access
R/O
System or User
Update
System
Data
Type
UINT8
Length
1
62
15 Bypasses Active
16 Chain Status
17 Trip Status
18
19
Chain With Inst
Chain With What Aspect
R/W
R/W
20 Chain Type
21 Chain First Out
R/O
R/O
R/O
R/W
R/O
System
System
System
User
User
User
System
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
1
1
1
1
1
1
1
Reference
Range
0 - 1
0 - 31
0-1
0-1
0-# Logicals (48,
96, 144)
0-2
0-8
0-# Logicals (48,
96, 144)
Default
0
0
0
0
0
2
1
0
Version
Description of Functionality and Meaning of Values
4.03.05 Blocks trip status before bypass.
0 = False
1 = True
4.03.05 Shows the bypasses that are currently active.
0 = None
Bit 0 = Local Latched
Bit 1 = Remote Latched
Bit 2 = Class B
Bit 3 = Class C
Bit 4 = Class B/C
4.03.05 Chain trip status.
0 = False
1 = True
4.03.05 Shows the instance trip status.
0 = False
1 = True
4.03.05 Sets a chain to a block instance.
4.03.05 Sets a status to chain to from block instance.
0 = Block Status
1 = Chain Status (After Bypass)
2 = Inst Status
4.03.05 Selects the Chain Type to compare with chained block instance and associated status.
0 = AND
1 = OR
2 = NAND
3 = XOR_EITHER
4 = XOR_LOCAL
5 = XOR_REMOTE
6 = SEAL-IN
7 = PWM LO-DUTY
8 = PWM HI-DUTY
4.03.05 Shows OR chain first out number, only visible with Chain
Type OR.
Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
22
Name
SSD Destination
Domains
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
23
24
25
26
27
28
29
30
31
Is End of Chain
Chain Delay Sec Preset
Chain Delay Sec
Elapsed
Apply Action Upon
1 st Remote Bypass Inst
2 nd Remote Bypass Inst
3 rd Remote Bypass Inst
1 st Remote Bypass Type
2 nd Remote Bypass
Type
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
User
User
System
User
User
User
User
User
User
UINT8
UINT16
UINT16
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
1
2
2
1
1
1
1
1
1
Range
0-31
0 - 1
0 - 65535
0 - 65535
0 - 3
0-# Logicals (48,
96, 144)
0-# Logicals (48,
96, 144)
0-# Logicals (48,
96, 144)
0 - 3
0 - 3
Default
0
0
0
0
0
0
0
0
0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the SSD domains for
Action Output Type PSD or
TSD.
Bit 0 = PMTM Wells
Bit 1 = PMTM Loadouts
Bit 2 = PMWO Wells
Bit 3 = PMv3.3x Wells
Bit 4 = PMSC Effects
4.03.05 Indicates the last block in a chain.
0 = False
1 = True
4.03.05 Sets the delay in seconds as an on delay for the chain trip status.
4.03.05 Shows the chain delay elapsed time in seconds.
4.03.05 Sets the Action Output
Block/Chain Trip logic.
0 = True if Block True
1 = True if Chain True
2 = True if Either True
3 = True if Both True
4.03.05 Remote Bypass 1 block instance selection.
4.03.05 Remote Bypass 2 block instance selection.
4.03.05 Remote Bypass 3 block instance selection.
4.03.05 Remote Bypass 1 bypass type.
0 = Latched
1 = Class B
2 = Class C
3 = Class B/C
4.03.05 Remote Bypass 2 bypass type.
0 = Latched
1 = Class B
2 = Class C
3 = Class B/C
Revised January-2017 Reference 63
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
64
42
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
32
Name
3 rd Remote Bypass
Type
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
33
34
35
36
37
38
39
40
41
Local Latched Bypass
Class C Byp Deadband
EU
Class B Timer Preset
Sec
Class C Arm Delay Sec
Class B Elap Sec
Class C DB Arm Delay
Elap
Is a Browseable Bypass
R/W
R/W
R/W
R/O
R/O
R/W
Log Instance Trips
Log Instance Clears
Inst FO Tag Ref
R/W
R/W
R/W
R/O
User
User
User
User
System
System
User
User
User
System
UINT8
FL
UINT16
UINT16
UINT16
UINT16
UINT8
UINT8
UINT8
UINT8
1
2
2
1
1
2
2
1
1
1
Reference
Range
0 - 3
0 - 1
Any floating point number
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0-1
0 - 1
0 - 1
0-# Logicals (48,
96, 144)
Default
0
0
0.0
300
5
0
0
0
0
0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Remote Bypass 3 bypass type.
0 = Latched
1 = Class B
2 = Class C
3 = Class B/C
4.03.05 Enables or disables the Local
Bypass – Demand Bypass
(Latched), manual bypass.
0 = Disabled
1 = Enabled
4.03.05 Sets the Deadband value for
Class C bypass.
4.03.05 Sets the Class B Preset timer in seconds.
4.03.05 Sets the Class C Arm Delay
Preset timer in seconds.
4.03.05 Shows the Class B timer elapsed time in seconds.
4.03.05 Shows the Class C timer elapsed time in seconds.
4.03.05 Determines if block selected as a bypass is a valid selection, this parameter is not visible.
4.03.05 Enables or disables Alarm
Logging, log instance trips.
0 = No log
1 = Log Trips
4.03.05 Enables or disables Alarm
Logging, log instance clears.
0 = No log
1 = Log Clears
4.03.05 Sets the tag number of FO tripped instance.
Revised January-2017
44 SSD TM Well List 9-12 R/W
45 SSD LoadOut List
46 SSD WO Well List 1-8
47 SSD WO Well List 9-12 R/W
Revised January-2017
R/W
R/W
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
43
Name
SSD TM Well List 1-8
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
User
User
User
User
UINT8
UINT8
UINT8
UINT8
1
1
1
1
Reference
Range
0 - 255
0 - 15
0 - 63
0 - 255
0 - 15
Default
0
0
0
0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the SSD Domains link to
PMTM Wells 1-8.
Bit 0 = Well 1
Bit 1 = Well 2
Bit 2 = Well 3
Bit 3 = Well 4
Bit 4 = Well 5
Bit 5 = Well 6
Bit 6 = Well 7
Bit 7 = Well 8
4.03.05 Sets the SSD Domains link to
PMTM Wells 9-12.
Bit 0 = Well 9
Bit 1 = Well 10
Bit 2 = Well 11
Bit 3 = Well 12
4.03.05 Sets the SSD Domains link to
PMTM LoadOuts 1-6.
Bit 0 = LoadOut 1
Bit 1 = LoadOut 2
Bit 2 = LoadOut 3
Bit 3 = LoadOut 4
Bit 4 = LoadOut 5
Bit 5 = LoadOut 6
4.03.05 Sets the SSD Domains link to
PMWO Wells 1-8.
Bit 0 = Well 1
Bit 1 = Well 2
Bit 2 = Well 3
Bit 3 = Well 4
Bit 4 = Well 5
Bit 5 = Well 6
Bit 6 = Well 7
Bit 7 = Well 8
4.03.05 Sets the SSD Domains link to
PMWO Wells 9-12.
Bit 0 = Well 9
Bit 1 = Well 10
Bit 2 = Well 11
Bit 3 = Well 12
65
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
48
Name
SSD PM v3.30 Well List
1-6
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
Range
0 - 63
66
49 SSD PMSC Effects 1-8 R/W
50 SSD PMSC Effects 9-16 R/W
51 SSD PMSC Effects 17-
24
R/W
User
User
User
UINT8
UINT8
UINT8
1
1
1
Reference
0 - 255
0 - 255
0 - 255
Default
0
0
0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the SSD Domains link to
PMv3.3x Wells 1-8.
Bit 0 = Well 1
Bit 1 = Well 2
Bit 2 = Well 3
Bit 3 = Well 4
Bit 4 = Well 5
Bit 5 = Well 6
4.03.05 SSD Domains link to PMSC
Effects 1-8.
Bit 0 = Effect 1
Bit 1 = Effect 2
Bit 2 = Effect 3
Bit 3 = Effect 4
Bit 4 = Effect 5
Bit 5 = Effect 6
Bit 6 = Effect 7
Bit 7 = Effect 8
4.03.05 Sets the SSD Domains link to
PMSC Effects 9-16.
Bit 0 = Effect 9
Bit 1 = Effect 10
Bit 2 = Effect 11
Bit 3 = Effect 12
Bit 4 = Effect 13
Bit 5 = Effect 14
Bit 6 = Effect 15
Bit 7 = Effect 16
4.03.05 Sets the SSD Domains link to
PMSC Effects 17-24.
Bit 0 = Effect 17
Bit 1 = Effect 18
Bit 2 = Effect 19
Bit 3 = Effect 20
Bit 4 = Effect 21
Bit 5 = Effect 22
Bit 6 = Effect 23
Bit 7 = Effect 24
Revised January-2017
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
52
Name
SSD PMSC Effects
25-32
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
53 SSD PMSC Effects
33-36
54 Remote Bypass Status R/O
55 Prev Scan Trip Status
56 Bypass Location Type 1 R/W
57 Bypass Location Type 2 R/W
Revised January-2017
R/W
R/W
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
User
System
User
User
User
UINT8
UINT8
UINT8
UINT8
UINT8
1
1
1
1
1
Reference
Range
0 - 255
0 - 15
0
0-1
0-1
0-1
Default
0
0
0
0
0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the SSD Domains link to
PMSC Effects 25-32.
Bit 0 = Effect 25
Bit 1 = Effect 26
Bit 2 = Effect 27
Bit 3 = Effect 28
Bit 4 = Effect 29
Bit 5 = Effect 30
Bit 6 = Effect 31
Bit 7 = Effect 32
4.03.05 Sets the SSD Domains link to
PMSC Effects 33-36.
Bit 0 = Effect 33
Bit 1 = Effect 34
Bit 2 = Effect 35
Bit 3 = Effect 36
4.03.05 Shows the Trip status of remote bypasses.
Bit 0 = Remote Bypass 1
Status
Bit 1 = Remote Bypass 2
Status
Bit 2 = Remote Bypass 3
Status
4.03.05 The block status after bypass of the previous, this parameter is not displayed.
4.06.00 Determines if remote bypass 1 is activated by another action block, or by a user selected
TLP.
0 = User Selected TLP
1 = Remote Action Block
4.06.00 Determines if remote bypass 2 is activated by another action block, or by a user selected
TLP.
0 = User Selected TLP
1 = Remote Action Block
67
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
58
Name
Bypass Location Type 3
Access
R/W
System or User
Update
User
59
60
61
62
63
Remote Bypass TLP
Def 1
Remote Bypass TLP
Def 2
Remote Bypass TLP
Def 3
SSD PMSC Effects
41-48
SSD PMSC Effects
49-56
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
Data
Type
UINT8
Length
1
TLP
TLP
TLP
UINT8
UINT8
3
3
3
1
1
Range
0-1
Any Valid Numeric
TLP
Any Valid Numeric
TLP
Any Valid Numeric
TLP
0 - 255
0 - 255
Default
0
0,0,0
0,0,0
0,0,0
0
0
Version
Description of Functionality and Meaning of Values
4.06.00 Determines if remote bypass 3 is activated by another action block, or by a user selected
TLP.
0 = User Selected TLP
1 = Remote Action Block
4.06.00 Sets the TLP source for remote bypass 1, if the type is set to use a TLP definition.
4.06.00 Sets the TLP source for remote bypass 2, if the type is set to use a TLP definition.
4.06.00 Sets the TLP source for remote bypass 3, if the type is set to use a TLP definition.
4.06.00 Sets the SSD Domains link to
PMSC Effects 41-48.
Bit 0 = Effect 41
Bit 1 = Effect 42
Bit 2 = Effect 43
Bit 3 = Effect 44
Bit 4 = Effect 45
Bit 5 = Effect 46
Bit 6 = Effect 47
Bit 7 = Effect 48
4.06.00 Sets the SSD Domains link to
PMSC Effects 49-56.
Bit 0 = Effect 49
Bit 1 = Effect 50
Bit 2 = Effect 51
Bit 3 = Effect 52
Bit 4 = Effect 53
Bit 5 = Effect 54
Bit 6 = Effect 55
Bit 7 = Effect 56
68 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 68 (ROC800) or Point 28 (FB107): Action Blocks
Param
#
64
Name
SSD PMSC Effects
57-64
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
Range
0 - 255
Default
0
Version
Description of Functionality and Meaning of Values
4.06.00 Sets the SSD Domains link to
PMSC Effects 57-64.
Bit 0 = Effect 57
Bit 1 = Effect 58
Bit 2 = Effect 59
Bit 3 = Effect 60
Bit 4 = Effect 61
Bit 5 = Effect 62
Bit 6 = Effect 63
Bit 7 = Effect 64
Revised January-2017 Reference 69
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
4.2 Point Type 71/31: Utilities
Point type 71 (for ROC800) or point type 31 (for FB107) contains the parameters for configuring the utilities. For the ROC800, the program maintains 12, 24, or 36 instances of this point type (depending on the size of the installed program); for the FB107, the program maintains 16 instances of this point type.
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
0
Name
Instance Tag
Access
R/W
System or User
Update
User
1
2
3
4
Run Time Enable
Run Time Pt Def
RT Operator
RT Setpoint
R/W
R/W
R/W
R/W
User
User
User
User
Data
Type
AC10
UINT8
TLP
UINT8
FL
Length
10
1
3
1
4
Range
0x20
0x7E for each ASCII character
0 - 1
Any Valid IEEE numeric TLP
0 - 5
Default
Inst #
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the tag name for utilities.
0
0,0,0
0
0.0
4.03.05 Enables time count.
0 = Disabled
1 = Enabled
4.03.05 Sets the Run-Time Pt Def TLP selection.
4.03.05 Sets the logical operator for run-time comparison.
0 = GT (>)
1 = GE (>=)
2 = LT (<)
3 = LE (<=)
4 = EQ (==)
5 = NE (!=)
4.03.05 Sets the setpoint value.
5 RT Clear Now R/W User UINT8 1
Any floating point number
0 - 1 0
6
7
8
9
RT Status
RT ON Mins Tdy
RT ON Mins Ydy
RT ON Mins TMonth
R/O
R/O
R/O
R/O
System
System
System
System
UINT8
FL
FL
FL
1
4
4
4
0 - 1
Any positive floating point number
Any positive floating point number
Any positive floating point number
0
0.0
0.0
0.0
4.03.05 Clears all run-time accumulators.
0 = Normal
1 = Clear Accums
4.03.05 Shows the status of live runtime.
0 = False
1 = True
4.03.05 Shows the Run-time ON minutes today.
4.03.05 Shows the Run-time ON minutes yesterday.
4.03.05 Shows the Run-time ON minutes this month.
70 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
22
23
24
25
26
27
28
17
18
19
20
21
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
10
Name
RT ON Mins PMonth
Access
R/O
System or User
Update
System
11
12
RT ON Hours Tdy
RT ON Hours Ydy
R/O
R/O
System
System
13
14
15
16
RT ON Hours TMonth
RT ON Hours PMonth
RT ON Pct Tdy
RT ON Pct Ydy
R/O
R/O
R/O
R/O
System
System
System
System
RT ON Pct Ydy
RT ON Pct PMonth
RT OFF Mins Tdy
RT OFF Mins Ydy
RT OFF Mins TMonth
RT OFF Mins PMonth
RT OFF Hours Tdy
RT OFF Hours Ydy
RT OFF Hours TMonth
RT OFF Hours PMonth
RT OFF Pct Tdy
RT OFF Pct Ydy
R/O
R/O
R/O
R/O
R/O
R/O
R/O
R/O
R/O
R/O
R/O
R/O
System
System
System
System
System
System
System
System
System
System
System
System
Revised January-2017
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
Data
Type
FL
FL
FL
Length
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Range
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Any positive floating point number
Reference
Default
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Version
Description of Functionality and Meaning of Values
4.03.05 Shows the Run-time ON minutes previous month.
4.03.05 Shows the Run-time ON hours today.
4.03.05 Shows the Run-time ON hours yesterday.
4.03.05 Shows the Run-time ON hours this month.
4.03.05 Shows the Run-time ON hours previous month.
4.03.05 Shows the Run-time ON percent today.
4.03.05 Shows the Run-time ON percent yesterday.
4.03.05 Shows the Run-time ON percent month.
4.03.05 Shows the Run-time ON percent previous month.
4.03.05 Shows the Run-time OFF minutes today.
4.03.05 Shows the Run-time OFF minutes yesterday.
4.03.05 Shows the Run-time OFF minutes this month.
4.03.05 Shows the Run-time OFF minutes previous month.
4.03.05 Shows the Run-time OFF hours today.
4.03.05 Shows the Run-time OFF hours yesterday.
4.03.05 Shows the Run-time OFF hours this month.
4.03.05 Shows the Run-time OFF hours previous month.
4.03.05 Shows the Run-time OFF percent today.
4.03.05 Shows the Run-time OFF percent yesterday.
71
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
29
Name
RT OFF Pct TMonth
Access
R/O
System or User
Update
System
30
31
RT OFF Pct PMonth
Contract Hour
R/O
R/W
System
User
32
33
34
Cur Day in Use
Cur Month in Use
Accum / Prop Out
Mode
R/O
R/O
R/W
System
System
User
35
36
37
38
39
AC/PO Enable
AC/PO Input Def
AC/PO Output Def
AC/PO Time Basis
Prop Out Pulse Interval
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
Data
Type
FL
FL
UINT8
UINT8
UINT8
UINT8
UINT8
TLP
TLP
UINT8
FL
Length
4
4
1
Range
Any positive floating point number
Any positive floating point number
0 - 23
1
1
1
1
3
3
1
4
1 - 31
1 - 12
0 - 3
0 - 1
Any Valid IEEE numeric TLP
Any Valid IEEE numeric TLP
0 - 3
Any floating point number
Default
0.0
0.0
0
Day
Month
0
0
0,0,0
0,0,0
3
1000.0
Version
Description of Functionality and Meaning of Values
4.03.05 Shows the Run-time OFF percent month.
4.03.05 Shows the Run-time OFF percent previous month.
4.03.05 Sets the number of hours when transition occurs between days.
4.03.05 Shows the Current day of the month.
4.03.05 Shows the Current month.
4.03.05 Selects the Accum/Prop Output
Mode.
0 = Accumulate a Rate
1 = Accumulate a Running
Total
2 = Output a 4-20ma Signal
3 = Generate a Pulse at an
Interval
4.03.05 Enables accumulator / proportional output.
0 = Disabled
1 = Enabled
4.03.05 Sets the TLP source for Input
Value.
4.03.05 Sets the TLP source for Output
Value.
4.03.05 Sets the Time basis for
Accum/Prop Output.
0 = Per Day
1 = Per Hour
2 = Per Minute
3 = Per Second
4.03.05 Sets the DO Output Pulse
Interval to send out a pulse, only visible when Mode is set to
Generate a Pulse at an
Interval.
72 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
40
Name
Prop Out Interval
Accum
Access
R/W
System or User
Update
User
41
42
43
48
49
50
44
45
46
47
PMSC Effect Enable
PMSC Effect Def
Effect Trip Status
Effect Cur Output
Value
Value When Tripped
Value When Not
Tripped
Apply When Not
Tripped
Assert Output
Continuously
Effect Requires Preset
1 st Out PMSC Block
Revised January-2017
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
User
User
User
User
Data
Type
FL
UINT8
TLP
UINT8
FL
FL
FL
UINT8
UINT8
UINT8
UINT8
1
1
1
Length
4
Range
Any positive floating point number
1
3
1
4
4
4
1
0 - 1
Any Valid IEEE numeric TLP
0 - 1
Any floating point number
Any floating point number
Any floating point number
0 - 1
Default
0.0
0,0,0
0
1.0
0.0
Version
Description of Functionality and Meaning of Values
4.03.05 Sets the Current Interval
Accumulation. This is only visible when Mode is set to
Generate a Pulse at an
Interval.
4.03.05 Enables Effect.
0 = Disabled
1 = Enabled
4.03.05 Selects the Effect Output Pt
Def TLP selection.
4.03.05 Enables the Effect Trip Status.
0 = Inactive
1 = Active
4.03.05 Effect Output Current Value
1.0
1
1
0 - 3
0 - 1
0-# Logicals
(48, 96, 144)
0
0
4.03.05 Value when Effect is active.
4.03.05 Value when Effect is inactive.
4.03.05 Output the Value When Not
Tripped.
0 = Disabled
1 = Enabled
4.03.05 Asserts Output Continuously
During selected state.
0 = Neither State
1 = Tripped State Only
2 = UnTripped State Only
3 = Both States
4.03.05 Enables Reset for tripped
Effect.
0 = Disabled
1 = Enabled
4.03.05 Sets the Instance number of first tripped action block.
Reference 73
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
51
Name
Ready For Reset
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
Range
0 - 1
74
52
53
Remote Reset TLP
Reset Status
54 Prev Effect State
55 Write Update Period
56 AC/PO Flags
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
TLP
UINT8
UINT8
UINT8
UINT8
3
1
1
1
1
Reference
Any Valid IEEE numeric TLP
0-255
0-2
0 - 60
0 - 4
Default
0
0,0,0
0
0
0
0
Version
Description of Functionality and Meaning of Values
4.03.05 Shows the status that effect is ready to be reset for a PSD action block trip that has cleared, only visible when Trips
Require Reset is checked and eEffect is ready to be reset.
4.03.05 Activates the Remote Reset
Command TLP selection.
4.03.05 The reset command that holds the value that must be entered to reset a trip in a PSD condition.
4.03.05 Shows the previous state of the effect.
0 = Inactive
1 = Active, not ready for reset
2 = Active, ready for reset
4.03.05 Sets the Update Interval for
Time Count.
1 = 1 Second
2 = 2 Seconds
3 = 3 Seconds
4 = 4 Seconds
5 = 5 Seconds
6 = 6 Seconds
10 = 10 Seconds
12 = 12 Seconds
15 = 15 Seconds
20 = 20 Seconds
30 = 30 Seconds
60 = 60 Seconds
4.03.05 Selects the flag for Accum/Prop
Outputs. This is only visible when mode is set to
Accumulate a Rate or
Accumulate a Running Total.
0 = Normal Operation.
1 = Force End of Day
2 = Force End of Month
3 = Flush Running Accum
4 = Cold Start Accumulator Set
Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
59
60
61
62
63
64
65
66
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
57
Name
Effect First Out Tag
Access
R/O
System or User
Update
System
58 Perm Shutdown Set R/W User
Data
Type
AC10
UINT8
Length
10
1
Range
0x20
0x7E for each ASCII character
0 - 31
67
Temp Shutdown Set
Any SSD Set
Trip Code TM Well
Trip Code TM LoadOut
Trip Code WO Well
Trip Code PMv3 Well
Trip Code PMSC
Effects
Max Logicals
User Prog Watchdog
Timer
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
User
User
User
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT16
1
1
1
1
1
1
1
1
2
0 - 31
0 - 31
0 - 254
0 - 254
0 - 254
0 - 254
0 - 254
48,96,144
0-65535
0
0
0
0
0
48
Default Version
Description of Functionality and Meaning of Values
<clear> 4.03.05 Shows the tag of first tripped action block.
0
0
0
0
4.03.05 Sets the status of PSD trips.
Bit 0 = Tank Mgr Well #1
Bit 1 = Tank Mgr LoadOut #1
Bit 2 = Well Opt Mgr Well #1
Bit 3 = PMv3.3 Well #1
Bit 4 = PMSC Effect #1
4.03.05 Sets the status of TSD trips.
Bit 0 = Tank Mgr Well #1
Bit 1 = Tank Mgr LoadOut #1
Bit 2 = Well Opt Mgr Well #1
Bit 3 = PMv3.3 Well #1
Bit 4 = PMSC Effect #1
4.03.05 Sets the status of any SSD tripped.
Bit 0 = Tank Mgr Well #1
Bit 1 = Tank Mgr LoadOut #1
Bit 2 = Well Opt Mgr Well #1
Bit 3 = PMv3.3 Well #1
Bit 4 = PMSC Effect #1
4.03.05 Sets the Trip Code for PMTM
Well reset.
4.03.05 Sets the Trip Code for PMTM
LoadOut reset.
4.03.05 Sets the Trip Code for PMWO
Well reset.
4.03.05 Sets the Trip Code for PMv3.3
Well reset.
4.03.05 Sets the Trip Code for PMSC
Effect reset.
4.03.05 Sets the maximum number of logical, depending on PMSC version.
4.03.05 Used to verify that program is still running, time counter that increments once per second.
Revised January-2017 Reference 75
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
68
Name
Alarm Pt Tag 1
Access
R/W
System or User
Update
User
76
69
71
72
73
74
75
Alarm Pt Indef TLP 1
Alarm Pt Input Val 1
Alarm Pt Mode Val 1
Alarm Pt Code Val 1
Alarm Pt Low Val 1
Alarm Pt Low Low Val
1
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
Data
Type
AC10
TLP
FL
UINT8
UINT8
FL
FL
Length
10
3
Range
0x20
0x7E for each ASCII character
Any Valid Numeric
TLP
4
1
1
4
Any Valid IEEE
Floating Point
Number
0 - 255
0 - 255
Default Version
Description of Functionality and Meaning of Values
“Alarm 1”
4.06.00 Sets the tag for the Alarm Point
1.
0,0,0
0
0
0
-10.0
4.06.00
4.06.00
Sets the TLP source for the variable to be monitored for the alarm block instance.
The current value of the input parameter for the alarm block.
4.06.00 Defines the actions for the alarm block.
Bit 0 = Boolean Alarm – Set on
0 / Set on 1
Bit 1 = Alarm Type – Analog /
Boolean
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Alarm Enable – Disable
/ Enable
Bit 5 = SRBX on Clear
Bit 6 = SRBX on Set
Bit 7 = Scanning – Disable /
Enable
4.06.00 Provides an indication of all active alarms.
Bit 0 = Low Alarm
Bit 1 = Low Low Alarm
Bit 2 = High Alarm
Bit 3 = High High Alarm
Bit 4 = Not Used
Bit 5 = Boolean
Bit 6 = Not Used
Bit 7 = Scanning Disabled
4.06.00 Value for a Low Alarm in engineering units.
4
Reference
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
-20.0 4.06.00 Value for a Low Low Alarm in engineering units.
Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
76
Name
Alarm Pt High Val 1
Access
R/W
System or User
Update
User
77
78
79
80
81
82
Alarm Pt High High Val
1
Alarm Pt Deadband Val
1
Alarm Pt Tag 2
Alarm Pt Indef TLP 2
Alarm Pt Input Val 2
Alarm Pt Mode Val 2
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
Data
Type
FL
FL
FL
AC10
TLP
FL
UINT8
Length
4
4
4
10
3
Range
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
0x20
0x7E for each ASCII character
Any Valid Numeric
TLP
4
1
Any Valid IEEE
Floating Point
Number
0 - 255
Default
110.0
Version
Description of Functionality and Meaning of Values
4.06.00 Value for a High Alarm in engineering units.
120.0
10.0 4.06.00 Provides a range (+/-) that the live input value may move between without causing another alarm.
“Alarm 2” 4.06.00 Sets the tag for the Alarm Point
2.
0,0,0
4.06.00 Value for a High High Alarm in engineering units.
0
0
4.06.00 Sets the TLP source for the variable to be monitored for the alarm block instance.
4.06.00 The current value of the input parameter for the alarm block.
4.06.00 Defines the actions for the alarm block.
Bit 0 = Boolean Alarm
– Set on
0 / Set on 1
Bit 1 = Alarm Type
– Analog /
Boolean
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Alarm Enable
– Disable
/ Enable
Bit 5 = SRBX on Clear
Bit 6 = SRBX on Set
Bit 7 = Scanning
– Disable /
Enable
Revised January-2017 Reference 77
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
83
Name
Alarm Pt Code Val 2
Access
R/W
System or User
Update
User
Data
Type
UINT8
84
85
86
87
88
89
90
91
Alarm Pt Low Val 2
Alarm Pt Low Low Val
2
Alarm Pt High Val 2
Alarm Pt High High Val
2
Alarm Pt Deadband Val
2
Alarm Pt Tag 3
Alarm Pt Indef TLP 3
Alarm Pt Input Val 3
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
User
User
FL
FL
FL
FL
FL
AC10
TLP
FL
Length
1
4
4
4
4
4
10
3
4
Range
0 - 255
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
0x20
0x7E for each ASCII character
Any Valid Numeric
TLP
Any Valid IEEE
Floating Point
Number
Default
0
-10.0
Version
Description of Functionality and Meaning of Values
4.06.00 Provides an indication of all active alarms.
Bit 0 = Low Alarm
Bit 1 = Low Low Alarm
Bit 2 = High Alarm
Bit 3 = High High Alarm
Bit 4 = Not Used
Bit 5 = Boolean
Bit 6 = Not Used
Bit 7 = Scanning Disabled
4.06.00 Value for a Low Alarm in engineering units.
-20.0
110.0
4.06.00 Value for a Low Low Alarm in engineering units.
4.06.00 Value for a High Alarm in engineering units.
120.0 4.06.00 Value for a High High Alarm in engineering units.
10.0 4.06.00 Provides a range (+/-) that the live input value may move between without causing another alarm.
“Alarm 3”
4.06.00 Sets the tag for the Alarm Point
3.
0,0,0
0
4.06.00
4.06.00
Sets the TLP source for the variable to be monitored for the alarm block instance.
The current value of the input parameter for the alarm block.
78 Reference Revised January-2017
93 Alarm Pt Code Val 3
94 Alarm Pt Low Val 3
95
96
Alarm Pt Low Low Val
3
Alarm Pt High Val 3
R/W
R/W
97
98
Alarm Pt High High Val
3
Alarm Pt Deadband Val
3
R/W
R/W
Revised January-2017
R/W
R/W
User
User
User
User
User
User
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
92
Name
Alarm Pt Mode Val 3
Access
R/W
System or User
Update
User
Data
Type
UINT8
Length
1
UINT8
FL
FL
FL
FL
FL
1
4
4
4
4
4
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Any Valid IEEE
Floating Point
Number
Reference
Range
0 - 255
0 - 255
Default
0
0
-10.0
Version
Description of Functionality and Meaning of Values
4.06.00 Defines the actions for the alarm block.
Bit 0 = Boolean Alarm – Set on
0 / Set on 1
Bit 1 = Alarm Type – Analog /
Boolean
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Alarm Enable
– Disable
/ Enable
Bit 5 = SRBX on Clear
Bit 6 = SRBX on Set
Bit 7 = Scanning
– Disable /
Enable
4.06.00 Provides an indication of all active alarms.
Bit 0 = Low Alarm
Bit 1 = Low Low Alarm
Bit 2 = High Alarm
Bit 3 = High High Alarm
Bit 4 = Not Used
Bit 5 = Boolean
Bit 6 = Not Used
Bit 7 = Scanning Disabled
4.06.00 Value for a Low Alarm in engineering units.
-20.0
110.0
4.06.00 Value for a Low Low Alarm in engineering units.
4.06.00 Value for a High Alarm in engineering units.
120.0
10.0
4.06.00 Value for a High High Alarm in engineering units.
4.06.00 Provides a range (+/-) that the live input value may move between without causing another alarm.
79
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 71 (ROC800) or Point Type 31 (FB107): Utilities
Param
#
99
Name
Time Counter Tag
Access
R/W
System or User
Update
User
100 Max Accum Inter-Scan R/W User
Data
Type
AC10
FL
Length
10
4
Range
0x20
0x7E for each ASCII character
Any Valid IEEE
Floating Point
Number
Default
“Time Cnt
1”
Version
Description of Functionality and Meaning of Values
4.06.00 Sets the tag for the time counter instance.
100.0 4.06.00 Maximum accepted inter-scan accumulation difference in engineering units.
80 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
4.3 Point Type 218: Calculation Blocks (for ROC800)
Point type 218 contains the parameters for the configuration of the PM Calculation Blocks of the program. The program maintains 4, 8, 12 or
16 instances of this point type (based on the size of the installed program).
Point Type 218 (for ROC800): Calculation Blocks
Param
#
0
Name
Calculation Block X
Access
R/W
System or User
Update
User
Data
Type
String20
Length
20
1
2
3
4
5
6
7
8
9
10
11
12
13
Calculation Enable
Input Description A
Input Description B
Input Description C
Input Description D
Input TLP A
Input TLP B
Input TLP C
Input TLP D
Input Value A
Input Value B
Input Value C
Input Value D
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
User
User
User
Both
Both
Both
Both
UINT8
String10
String10
String10
String10
TLP
TLP
TLP
TLP
Double
Double
Double
Double
10
10
10
10
3
3
3
3
8
8
8
8
Range
Printable ASCII
Characters
01
Printable ASCII
Characters
Printable ASCII
Characters
Printable ASCII
Characters
Printable ASCII
Characters
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any Double-Float
Value
Any Double-Float
Value
Any Double-Float
Value
Any Double-Float
Value
Default Version
Description of Functionality and Meaning of Values
Calc
Block X
0
4.07.00 Tag for the Calculation block
4.07.00 Solve Calculations for X, Y, and
Z
0 = NO
1 = YES
<blank> 4.07.00 Description of Input A
<blank> 4.07.00 Description of Input B
<blank> 4.07.00 Description of Input C
<blank> 4.07.00 Description of Input D
Undefined 4.07.00 Starting Location of Input A
Undefined 4.07.00 Starting Location of Input B
Undefined 4.07.00 Starting Location of Input C
Undefined 4.07.00 Starting Location of Input D
0.0
0.0
0.0
0.0
4.07.00 Value of Input A (when array size = 1)
4.07.00 Value of Input B (when array size = 1)
4.07.00 Value of Input C (when array size = 1)
4.07.00 Value of Input D (when array size = 1)
Revised January-2017 Reference 81
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 218 (for ROC800): Calculation Blocks
Param
#
14
Name
Calculation String X
Access
R/W
System or User
Update
User
Data
Type
String40
Length
40
15
16
17
Calculation String Y
Calculation String Z
Calculation Valid X
R/W
R/W
R/W
User
User
System
String40
String40
UINT8
40
40
1
Range
All Numbers, A-D,
X-Z, letters in function names, parenthesis, math operators
All Numbers, A-D,
X-Z, letters in function names, parenthesis, math operators
All Numbers, A-D,
X-Z, letters in function names, parenthesis, math operators
01
Default Version
Description of Functionality and Meaning of Values
<blank> 4.07.00 Free-Form calculation including variables, operators and functions
<blank> 4.07.00 Free-Form calculation including variables, operators and functions
<blank> 4.07.00 Free-Form calculation including variables, operators and functions
18
19
23
24
25
26
20
21
22
Calculation Valid Y
Calculation Valid Z
Calc Error Char NumX
Calc Error Char NumY
Calc Error Char NumZ
Result Description X
Result Description Y
Result Description Z
Result Value X
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
System
System
System
System
System
User
User
User
System
UINT8
UINT8
UINT8
UINT8
UINT8
String10
String10
String10
Double
1
1
1
1
1
10
10
10
8
01
01
040
040
040
Printable ASCII
Characters
Printable ASCII
Characters
Printable ASCII
Characters
Any Double-Float
Value
0
0
4.07.00 Is Calculation string X valid?
0 = NO
1 = YES
4.07.00 Is Calculation string Y valid?
0 = NO
1 = YES
0 4.07.00 Is Calculation string Z valid?
0 = NO
1 = YES
0
0
0
4.07.00 X Error Located at Char
Number
4.07.00 Y Error Located at Char
Number
4.07.00 Z Error Located at Char
Number
<blank> 4.07.00 Description of Result X
<blank> 4.07.00 Description of Result Y
<blank> 4.07.00 Description of Result Z
0.0 4.07.00 Value of Result X
82 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
30
31
32
33
34
35
36
Point Type 218 (for ROC800): Calculation Blocks
Param
#
27
Name
Result Value Y
Access
R/O
System or User
Update
System
Data
Type
Double
28
29
Result Value Z
TLP Forwarding X
R/O
R/W
System
User
Double
TLP
Length
8
8
3
TLP Forwarding Y
TLP Forwarding Z
R/W
R/W
User
User
TLP
TLP
3
3
37
Input Array Qty A
Input Array Qty B
Input Array Qty C
Input Array Qty D
Max Logicals
UProg Watchdog Timer
R/W
R/W
R/W
R/W
R/O
R/O
User
User
User
User
System
System
UINT8
UINT8
UINT8
UINT8
UINT8
UINT16
1
1
1
1
1
2
Range
Any Double-Float
Value
Any Double-Float
Value
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
110
110
110
110
4, 8, 12, 16
065535
Default
0.0
Version
Description of Functionality and Meaning of Values
4.07.00 Value of Result Y
0.0 4.07.00 Value of Result Z
Undefined 4.07.00 Forwarding Location for Result
X
Undefined 4.07.00 Forwarding Location for Result
Y
Undefined 4.07.00 Forwarding Location for Result
Z
1 4.07.00 Quantity of Values in Input A
1
1
4.07.00
4.07.00
Quantity of Values in Input B
Quantity of Values in Input C
1
4, 8, 12,
16
0
4.07.00 Quantity of Values in Input D
4.07.00 Number of Calculation
Instances
4.07.00 Continually Changing Values
Revised January-2017 Reference 83
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
4.4 Point Type 27/39: Calculation Blocks (for FB107)
Point type 27 (Slot #3)/Alternate #39 (Slot #6) contains the parameters for the configuration of the PM Calculation Blocks of the program.
The program supports 4 logicals of point type 27 or 39.
Point Type 27/39 (for FB107): Calculation Blocks
Param
#
0
Name
Calculation Tag
Access
R/W
System or User
Update
User
Data
Type
String20
Length
20
1
2
3
4
5
6
7
8
9
10
11
12
13
Calculation Enable
Input Description A
Input Description B
Input Description C
Input Description D
Input TLP A
Input TLP B
Input TLP C
Input TLP D
Input Value A
Input Value B
Input Value C
Input Value D
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
User
User
User
Both
Both
Both
Both
UINT8
String10
String10
String10
String10
TLP
TLP
TLP
TLP
Float
Float
Float
Float
10
10
10
10
3
3
3
3
4
4
4
4
Range
Printable ASCII
Characters
01
Printable ASCII
Characters
Printable ASCII
Characters
Printable ASCII
Characters
Printable ASCII
Characters
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any Floating number
Any Floating number
Any Floating number
Any Floating number
Default Version
Description of Functionality and Meaning of Values
Calc
Block X
0
4.00.01 Tag for the Calculation block
4.00.01 Solve Calculations for X, Y, and
Z
0 = NO
1 = YES
<blank> 4.00.01 Description of Input A
<blank> 4.00.01 Description of Input B
<blank> 4.00.01 Description of Input C
<blank> 4.00.01 Description of Input D
Undefined 4.00.01 Starting Location of Input A
Undefined 4.00.01 Starting Location of Input B
Undefined 4.00.01 Starting Location of Input C
Undefined 4.00.01 Starting Location of Input D
0.0
0.0
0.0
0.0
4.00.01
4.00.01
4.00.01
4.00.01
Value of Input A (when array size = 1)
Value of Input B (when array size = 1)
Value of Input C (when array size = 1)
Value of Input D (when array size = 1)
84 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
18
19
23
24
25
26
27
20
21
22
Point Type 27/39 (for FB107): Calculation Blocks
Param
#
14
Name
Calculation String X
Access
R/W
System or User
Update
User
Data
Type
String40
Length
40
15
16
17
Calculation String Y
Calculation String Z
Calculation Valid X
R/W
R/W
R/W
User
User
System
String40
String40
UINT8
40
40
1
Range
All Numbers, A-D,
X-Z, letters in function names, parenthesis, math operators
All Numbers, A-D,
X-Z, letters in function names, parenthesis, math operators
All Numbers, A-D,
X-Z, letters in function names, parenthesis, math operators
01
Default Version
Description of Functionality and Meaning of Values
<blank> 4.00.01 Free-Form calculation including variables, operators and functions
<blank> 4.00.01 Free-Form calculation including variables, operators and functions
<blank> 4.00.01 Free-Form calculation including variables, operators and functions
Calculation Valid Y
Calculation Valid Z
Calc Error Char NumX
Calc Error Char NumY
Calc Error Char NumZ
Result Description X
Result Description Y
Result Description Z
Result Value X
Result Value Y
Revised January-2017
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/O
System
System
System
System
System
User
User
User
System
System
UINT8
UINT8
UINT8
UINT8
UINT8
String10
String10
String10
Float
Float
1
1
1
1
1
01
01
040
040
040
10
10
10
4
4
Printable ASCII
Characters
Printable ASCII
Characters
Printable ASCII
Characters
Any Floating number
Any Floating number
Reference
0
0
4.00.01 Is Calculation string X valid?
0 = NO
1 = YES
4.00.01 Is Calculation string Y valid?
0 = NO
1 = YES
0 4.00.01 Is Calculation string Z valid?
0 = NO
1 = YES
0
0
0
4.00.01 X Error Located at Char
Number
4.00.01 Y Error Located at Char
Number
4.00.01 Z Error Located at Char
Number
<blank> 4.00.01 Description of Result X
<blank> 4.00.01 Description of Result Y
<blank> 4.00.01 Description of Result Z
0.0
0.0
4.00.01
4.00.01
Value of Result X
Value of Result Y
85
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Point Type 27/39 (for FB107): Calculation Blocks
Param
#
28
Name
Result Value Z
Access
R/O
System or User
Update
System
29 TLP Forwarding X R/W User
30
31
32
33
34
35
TLP Forwarding Y
TLP Forwarding Z
Input Array Qty A
Input Array Qty B
Input Array Qty C
Input Array Qty D
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
User
User
User
36
37
Max Logicals
UProg Watchdog Timer
R/O
R/O
System
System
UINT8
UINT16
Data
Type
Float
TLP
TLP
TLP
UINT8
UINT8
UINT8
UINT8
Length
4
3
3
3
1
1
1
1
1
2
Range
Any Floating number
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
Any TLP of a
Numeric Field
110
110
110
110
4, 8, 12, 16
065535
Default
0.0
Version
Description of Functionality and Meaning of Values
4.00.01 Value of Result Z
Undefined 4.00.01 Forwarding Location for Result
X
Undefined 4.00.01 Forwarding Location for Result
Y
Undefined 4.00.01 Forwarding Location for Result
Z
1 4.00.01 Quantity of Values in Input A
1
1
4.00.01
4.00.01
Quantity of Values in Input B
Quantity of Values in Input C
1
4
0
4.00.01 Quantity of Values in Input D
4.00.01
Number of Calculation
Instances
4.00.01 Continually Changing Values
86 Reference Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Appendix A – PMCB Calculation Blocks – Supported
Functions
This appendix describes the following PMCB Calculation Blocks
Configuration Utilities:
Calculations: Rules and Guidelines
Operators
Functions
A.1 Calculations: Rules and Guidelines
A.1.1 Execution Order
All inputs are updated: A through D, instance by instance.
Each calculation is solved: X through Z, instance by instance.
Outputs are forwarded as each calculation is solved.
Rank
13 High
7
6
5
4
12
11
10
9
8
A.1.2 Order of Operators
There must be an equal number of opening and closing parentheses.
Each calculation string is broken down into operators, each with a pair of operands (an operation).
Operations are grouped by level (quantity) of enclosed parentheses.
The groups are solved in order from most nested to least (no parentheses).
Each operation within a parentheses group is solved in order by priority of precedence (highest to lowest). Refer to Table A-1.
Priorities of Precedence.
Within a group, operations of the same priority of precedence are solved from left to right.
Table A-1. Priorities of Precedence
Description
Functions () (ABS, INT, IIF, POW, MOD, AND, OR, MIN, MAX, SUM, BFI, BFO, IFI, IFO, FOR)
Unary NOT (!), Unary Minus (-)
Exponential Operators (**, //)
Multiplication (*); Division (/)
Addition (+); Subtraction (-)
Not Implemented
Analog Comparisons (<, <=, >, >=)
Discrete Comparisons (=, !=)
Bitwise AND (&)
Bitwise Exclusive OR (^)
Revised January-2017 PMCB Calculation Blocks – Supported Functions 87
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Rank
3
2
1 Low
Description
Bitwise Inclusive OR (|)
Logical AND (&&)
Logical OR (||)
A.1.3 Parentheses
Enclose Function Arguments
The OR functions has three arguments (enclosed by parentheses) and the AND function has four arguments (one of them is the OR function result). The OR function is solved first as it is nested within the AND function.
Determine Order If Operations
There are six mathematical operations to solve the equation above:
- (a**2) is solved first (regardless of priority of precedence) as it is within the inner-most (most nested, highest group level) set of parentheses. The last (sixth) operation solved is the division
(r/1000) as it is the only operation outside of any parentheses
(lowest parentheses group level).
- There are four operations within the single parentheses. Of these, the multiplication (3 (r)) is solved first (2 nd
overall) based on priority of precedence (priority = 10) and left-most position.
Then the other multiplication (7b) is solved (3 rd
overall) as it is the same priority.
- Then the two addition operations are solved left-most (4 th overall) than next to the right (r+12) (5 th
overall).
A.1.4 Operands
Operands may consist of the following:
Constants
Any numerical value such as 3, 7.5 or 123.457
Variables o Input Letters (A, B, C or D) or (a, b, c, d) as case does not matter. o Result Letters (X, Y or Z) or (x, y, Z)
88 PMCB Calculation Blocks – Supported Functions Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
External References
Definition: A variable (listed above) that is proceeded by a ‘$’ and an instance number (1-based).
$3C refers to the C input variable from instance 3.
$5Y refers to the Y result from instance 5.
$4B:2 refers to the 2 nd element of array input variable B from instance 4.
Array References
Definition: A variable letter that is followed by a ‘:’ and an array element number.
The input variable array must have at least the number of elements
(quantity in array) as specified in the array reference.
A:3 refers to the third element of input array variable A.
$5B:2 refers to the second element of array input variable B from instance 5.
Bitwise References
Definition: A variable or reference followed by a ‘#’ and bit number (1-based).
The bitwise value is taken as a single digital bit to be a value of either 1 (True) or 0 (False).
Bitwise references are typically used with coded items such as alarm or status codes.
B#6 refers to the sixth bit of input variable B.
C:3#4 refers to the fourth bit of the third element of input array C.
$6B:2#5 refers to the fifth bit of the second element of input array
B from instance 6.
A.2 Operators
A.2.1 Mathematical Operators
Addition (+)
Subtraction (-)
Multiplication (*), (Two Operands in sequence)
Revised January-2017
Even though there are no multiplication operators (*) in this equation, there are two multiplication operations to be solved.
When two operands are in sequence (there is no operator between them) such as in (ab) a multiplication operation is implied.
An operand followed immediately by an opening parenthesis, such as (3(r)) implies a multiplication operation (an operand always follows an opening parenthesis).
PMCB Calculation Blocks – Supported Functions 89
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Division (/)
In all cases of a divide-by-zero the result will be zero.
Raised to the Power Of (Exponents) (**)
This operator must be between the base and an exponent.
The other method is use a POW () function with an exponent value less than one.
In this example the square root of sixty four equals eight. Z = 8.
In the above examples these operations are performed before any multiplication or division operations within the same parentheses group per the priority precedence (priority 11before priority 10).
A.2.2 Comparison Operators
Result: All comparison operation give either a 1 (True) or 0 (False ) value.
In this equation above, X = 7 when ‘a’ is greater than or equal to
300 (7*1) and X = 0 when ‘a’ is less than 300 (7*0). The one or zero result of the first operation is multiplied by 7 in the second operation.
A comparison is required as the first argument of an IIF() function.
Operators o Greater Than (>) o Greater Than or Equal To (>=) o Less Than (<) o Less than or Equal To (<=) o Equal to (=) o Not Equal To (!=)
The greater than and less than (analog) operations are solved before the equal to and not equal to (digital) operations per priority or precedence (priority 7 before priority 6).
90 PMCB Calculation Blocks – Supported Functions Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
A.2.3 Bitwise Operators
Examines numbers by Binary representation
Example of 8-bit binary values:
00000001 = 1 or 2
0
00000010 = 2 or 2
1
00000100 = 4 or 2
2
00001000 = 8 or 2
3
00010000 = 16 or 2
4
00100000 = 32 or 2 5
01000000 = 64 or 2
6
10000000 = 128 or 2
7
01010101 = 85 or (64 + 16 + 4 + 1)
Bitwise AND (&)
The corresponding (equal value) bits of both operands are multiplied together, so that if both bits in the compared position are
1 the bit in the resulting binary representation is also 1.
Example:
01010101 (decimal 85)
& 00110011 (decimal 51)
= 00010001 (decimal 17)
Bitwise OR (|)
The corresponding (equal value) bits of both operands are added together and if the result is greater than zero, so that if either of the bits in the compared position are 1 the bit in the resulting binary representation is also 1.
Example:
01010101 (decimal 85)
| 00110011 (decimal 51)
= 01110111 (decimal 119)
Bitwise Exclusive OR (*)
The corresponding (equal value) bits of both operands are added together and if the result equals one, so that one and only one of the two bits in the compared position are 1 the bit in the resulting binary representation is also 1.
Example:
01010101 (decimal 85)
^ 00110011 (decimal 51)
= 01100110 (decimal 102)
Revised January-2017 PMCB Calculation Blocks – Supported Functions 91
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
A.2.4 Logical Operators
Work only with Boolean (True/False) expressions.
Logical AND (&&)
The left and right operands are multiplied together, so that if both are true (greater than zero) the result is also true (1).
If ‘a’ is greater than 50 AND ‘b’ is less than or equal to 50, X will equal 1 (True). Otherwise X = 0 (False).
Logical OR (||)
The left and right operands are added together, so that if either are true (greater than zero) the result is also true (1).
If ‘a’ is greater than 50 OR ‘b’ is less than or equal to 50, X will equal 1 (True). If both are false, then X = 0 (False).
Logical NOT (!)
Works as a prefix to a single Boolean expression. It flips the true/false state of the Boolean expression so that a true expression becomes false and a false expression becomes true.
X=1 (True) when ‘b’ is greater than 50 as the ‘!’ flips the value of the binary expression.
A.3 Functions
A.3.1 AND(): Logical AND
Format: AND (expr1, expr2, ….)
Two or more arguments are required (extensible)
The number of arguments is limited to the 40-character string size.
The Boolean value of all the arguments are multiplied together, so that if they are all true (1) the function result is true (1).
The return value is either true (1) or false (1).
Y =1 when “C:1” is true AND “C:2” is false (the NOT) AND the
OR () function is true AND “C:6” is true. Otherwise Y = 0.
92 PMCB Calculation Blocks – Supported Functions Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
A.3.2 OR(): Logical OR
Format: AND (expr1, expr2, ….)
Two or more arguments are required (extensible)
The number of arguments is limited to the 40-character string size.
The Boolean value of all the arguments are added together, so that if any of them all true (1) the function result is true (1).
The return value is either true (1) or false (1).
The OR() function = 1 when “C:3” is true OR “C:4” is true OR
“C:5” is true. Otherwise Y = 0.
A.3.3 Boolean Calculations using AND(), OR() and NOT(!)
Operators
Example Calculation Y = AND (A:1, !A:2, OR (A:3, !A:4, A:5),
!A:6)
This an example of the type of discrete (Boolean) logic calculations are possible.
This example show how just input array ‘A’ and result ‘Y’ can replace the following rung of ladder logic:
A.3.4 ABS(): Absolute Value
Format: ABS(expr)
Takes a single argument, however it may be a compound expression.
Revised January-2017 PMCB Calculation Blocks – Supported Functions 93
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
If (expr < 0) the function returns (expr * (-1)). Otherwise it returns
(expr).
Y cannot equal a negative value regardless of ‘a’ or ‘b’ being negative. Absolute value actually is an expression value’s distance from zero.
A.3.5 INT(): Integer Value
Format: INT(expr)
Takes a single argument, however it may be a compound expression.
Removes the fractional part of the expression and returns the whole number value (the value to the left of the decimal point).
The integer value is never rounded up before dropping the fractional value.
Y = 47.0. The fractional part of the sum is dropped.
Z = 46.0. The fractional part 0.8 and 0.9 are both dropped off before the addition operation.
A.3.6 MOD(): Modulus
Format: MOD(dividend, divisor)
Requires exactly two arguments (dividend and divisor)
The divisor (second argument) must not be zero or else the function will simply return a zero value.
Returns the remainder value (the integer part is dropped) of the
(dividend / divisor) Euclidean division operation.
Z = 7 as the wjole number value of the quotient (3 from 3.7) is multiplied by the divisor (3*10 = 30). The result 37 – 30 = 7 is the remainder value.
Note that this remainder (Euclidean) is different from the mantissa
(0.7).
94 PMCB Calculation Blocks – Supported Functions Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
A.3.7 POW(): Raise To The Power Of
Format: POW(base, exponent)
Requires exactly two arguments (base and exponent)
Negative exponents are treated as the inverse of the calculation with the absolute value of the exponent: when the exponent = 2: pow(b,
-2) converts to: 1.0 / POW(b, 2).
Roots: An exponent value of 0.5 can be used to obtain a square root. POW(100, 0.5) = 10.
A.3.8 SUM(): Summation
Format: SUM(value1, value2, value3, …)
The number of argument is limited to the 40-character string size.
All arguments are added together and the sum is returned.
Example of possible arguments formats: SUM(ABS(a), 2b, c~, d:1).
Note: The tilde (~) specifies all the values are in an input array. If there are four elements in the ‘C’ input array, then this example effectively uses seven input arguments rather than four.
A.3.9 MIN(): Minimum Value
Format: MIN(value1, value2, value3, …)
The number of arguments is limited to the 40-character string size.
The lowest (minimum) argument value of all the arguments is returned.
Example of possible arguments formats: MIN(ABS(a), 2b, c~, d:1).
Note: The tilde (~) specifies all the values are in an input array. If there are four elements in the ‘C’ input array, then this example effectively uses seven input arguments rather than four.
A.3.10 MAX(): Maximum Value
Format: MAX(value1, value2, value3, …)
The number of arguments is limited to the 40-character string size.
The lowest (maximum) argument value of all the arguments is returned.
Example of possible arguments formats: MAX(ABS(a), 2b, c~, d:1).
Revised January-2017 PMCB Calculation Blocks – Supported Functions 95
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
Note: The tilde (~) specifies all the values are in an input array. If there are four elements in the ‘C’ input array, then this example effectively uses seven input arguments rather than four.
A.3.11 IIF(): Inline IF
Format: IIF(comparison (Boolean) expression, value when Arg1 is true, value when Arg1 is false)
Must contain three arguments.
Example: IIF(a > b, ac, bc); when ‘a’ is greater than ‘b’ the function value is ‘a’ times ‘c’. Otherwise it is ‘b’ times
‘c’
As with other functions a function can be embedded within another.
Example: IFF(a > b, IFF(b >c, c, d), b); this calculation value may equal either ‘b’, ‘c’ or ‘d’.
A.3.12 BFI(): Boolean FAN-IN
Format: BFI(array1 [Array2, Array3, …])
Arguments are assumed to be input arrays, so no tilde (~) is used.
One or more arguments are accepted (see below) but only the first
32 bytes will be processed.
‘a’ and ‘b’ are both 10-byte softpoint byte arrays. Twenty bytes will be packed into the result (X).
Example: BFI(a, b). Both arguments reference an array of a softpoint Byte 1 through Byte 10. The lowest significant bit comes from Byte 1 of the ‘a’ softpoint. The highest significant bit comes from Byte 10 of the ‘b’ softpoint.
A.3.13 BFO(): Boolean FAN-OUT
Format: BFO(array1 [Array2, Array3, …])
Arguments are assumed to be input arrays, so no tilde (~) is used.
One or more arguments are accepted (see below) but only the first
32 bytes will be processed.
‘c’ and ‘d’ are both 10-byte softpoint byte arrays. Twenty bytes will be packed into the result (X).
96 PMCB Calculation Blocks – Supported Functions Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
The BFO() function works in reverse of BFI() and backwards from every other function. The source to be unpacked is located in the results field. This field (X, Y, or Z) must have a valid Output
Definiition and it must be set to an integer field Such as a soft point
ByteX, ShortX or LongX.
The arguments (Input variables) specify the arrays where the unpacked data is placed.
Example: BFO(c, d). Both arguments reference an array of a softpoint Byte 1 through Byte 10. The lowest significant bit comes from Byte 1 of the ‘c’ softpoint. The highest significant bit comes from Byte 10 of the ‘d’ softpoint.
In this example, the softpoint Byte fields (1-10) in softpoints #1 and
#2 are effectively copied into the Byte fields of spoftpoints #3 and
#4.
Revised January-2017 PMCB Calculation Blocks – Supported Functions 97
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
A.3.14 FOR(): FOR Loop
Format: FOR(Math, # Calculations)
Requires exactly two arguments (Math and # Calculations).
Repeats a math equation multiple times, to be used with array variables.
Example: FOR((A:1*18/10)+32, 10). This performs a simple temperature unit conversion 10 times. It assumes the variable A has been defined as an array, with 10 consecutive elements.
The function is to be used in conjunction with Output Definition functionality, which allows the multiple results to be written out to separate parameters.
The FOR function must be at the very start of the calculation string, and all calculation contents must be contained inside it. Inputs that are not followed by the ":" element specifiers are not incremented.
They use the same value for each iteration.
98 PMCB Calculation Blocks – Supported Functions Revised January-2017
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
[This page is intentionally left blank.]
Revised January-2017 PMCB Calculation Blocks – Supported Functions 99
Surface Control Manager Program User Manual (ROC800-Series and FloBoss 107)
For customer service and technical support, visit www.EmersonProcess.com/Remote/Support .
Global Headquarters,
North America, and Latin America:
Emerson Automation Solutions
Remote Automation Solutions
6005 Rogerdale Road
Houston, TX 77072 U.S.A.
T +1 281 879 2699 | F +1 281 988 4445 www.EmersonProcess.com/Remote
Europe:
Emerson Automation Solutions
Remote Automation Solutions
Unit 8, Waterfront Business Park
Dudley Road, Brierley Hill
Dudley UK DY5 1LX
T +44 1384 487200 | F +44 1384 487258
Middle East/Africa:
Emerson Automation Solutions
Remote Automation Solutions
Emerson FZE
P.O. Box 17033
Jebel Ali Free Zone – South 2
Dubai U.A.E.
T +971 4 8118100 | F +971 4 8865465
Asia-Pacific:
Emerson Automation Solutions
Remote Automation Solutions
1 Pandan Crescent
Singapore 128461
T +65 6777 8211| F +65 6777 0947
© 2014–2017 Remote Automation Solutions, a business unit of Emerson Automation
Solutions. All rights reserved.
This publication is for informational purposes only. While every effort has been made to ensure accuracy, this publication shall not be read to include any warranty or guarantee, express or implied, including as regards the products or services described or their use or applicability.
Remote Automation Solutions (RAS) reserves the right to modify or improve the designs or specifications of its products at any time without notice. All sales are governed by RAS terms and conditions which are available upon request. RAS accepts no responsibility for proper selection, use or maintenance of any product, which remains solely with the purchaser and/or end-user.