Remote Automation Solutions CA User manual
إعلان
إعلان
Part D301745X012
June 2016
Cause and Effect Manager Program User
Manual (for ROC800-Series)
Remote Automation Solutions
Cause and Effect Manager Program User Manual (for ROC800-Series)
Revision Tracking Sheet
June 2016
This manual may be revised periodically to incorporate new or updated information. The revision date of each page appears at the bottom of the page opposite the page number. A change in revision date to any page also changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if applicable):
Page
All Pages
Initial release
Revision
June-2016
August-2014 ii Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Contents
Chapter 1 – Introduction 1
Chapter 2 – Installation 5
Chapter 3 – Configuration 13
Chapter 4 – Reference Material 29
4.2
Revised June-2016 iii
Cause and Effect Manager Program User Manual (for ROC800-Series)
[This page is intentionally left blank.] iv Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Chapter 1 – Introduction
Caution When implementing control using this product, observe best industry practices as suggested by applicable and appropriate environmental, health, and safety organizations. While this product can be used as A safety component in a system, it is NOT intended or designed to be the
ONLY safety mechanism in that system.
This chapter describes the structure of this manual and presents an overview and installation instructions of the Cause and Effect Manager
Program for the ROC800-Series Remote Operations Controller.
1.1 Scope and Organization
This document serves as the user manual for the Cause and Effect
Manager program, which is intended for use in a ROC800-Series
(ROC800). This manual describes how to download, install, and configure the Cause and Effect Manager program (referred to as the “Cause and
Effect program” or “the program” throughout the rest of this manual). You access and configure this program using ROCLINK™ 800 Configuration
Software (version 2.10 or greater) loaded on a personal computer (PC) running Windows ®
™ (32-bit), or Windows 7 (32-bit or 64bit).
2000 (with Service Pack 2), Windows XP (with
Service Pack 3), Windows Vista
The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software, the manual becomes a reference tool.
This manual has the following major sections:
Chapter 1 – Introduction
Chapter 2 – Installation
Chapter 3 – Configuration
Chapter 4 – Reference
This manual assumes that you are familiar with the ROC800 and its configuration. For more information, refer to the following manuals:
ROC800 Remote Operations Controller Instruction Manual (Part
D301217X012)
ROCLINK 800 ™ Configuration Software User Manual (for ROC800-
Series) (Part D301250X012)
1.2 Product Overview
The Cause & Effect Manager user program for the ROC800 supports up to
128 causes and 48 effects. The program is designed to allow you to configure the ROC800 to do logical operations without writing FSTs. A
Cause typically monitors a selected point that would be logically evaluated
Revised June-2016 1
Cause and Effect Manager Program User Manual (for ROC800-Series) against a user defined set-point. Any tripped Cause linked to an Effect forces the action defined in that Effect. An example of this would be a gas application monitoring multiple gas quality limits defined as Causes (BTU,
H
2
S, Nitrogen, CO
2
, etc) which are linked to a slam valve (which is the
Effect).
The layout of the configuration screens is such that you can configure logic by inputting entries from a Cause and Effect matrix. In many cases, you can input the effects and causes line by line through the entire matrix.
Features Cause precondition evaluation must be satisfied before a trip is possible.
Cause compound primary and secondary conditions that trips the cause based on “And / Or” evaluation.
Cause operators that allow selectable evaluations or operations (logical, on-change, mathematical, watchdog and data movement).
Cause condition and precondition timer delays.
Cause condition deadbands.
Caused definitions for up to 16 effect link assignments.
Cause trips that clear automatically when the condition clears or trips that are reset controlled.
Cause alarming to the ROC alarm log for trips and/or clears.
Effect active/inactive values or states that are definable.
Effect selectable option to assert those values continuously or not.
Effect usage that defines its behavior as a normal effect or a reset point
(i.e. reset push button).
Effect delay timer.
Effect last four tattletales that show the order of multiple causes tripped.
1.3 Program Requirements
The Cause and Effect program is compatible with version 3.50 (or greater) of the ROC800 firmware and with version 2.10 (or greater) of the
ROCLINK 800 software.
Program specifics include:
Note:
You must load one version of the program only depending on your available user program slot or location.
The CauseAndEffect_128x48_TLP7172.tar and the
CauseAndEffect_128x48_TLP7475.tar program files support 128 causes and 48 effects. The CauseAndEffect_64x32_TLP7172.tar and the CauseAndEffect_64x32_TLP7475.tar program files support 64 causes and 32 effects.
2 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
File Name
CauseAndEffect_128x
48_TLP7172.tar
CauseAndEffect_128x
48_TLP7475.tar
CauseAndEffect_64x32
_TLP7172.tar
CauseAndEffect_64x32
_TLP7475.tar
Target Unit/
Version
ROC800 3.50
User Defined
Point (UDP)
71, 72
ROC800 3.50
ROC800 3.50
ROC800 3.50
74, 75
71, 72
74, 75
Flash Used
(in bytes)
52,328
52,328
51,328
51,328
DRAM Used
(in bytes)
143,360
ROCKLINK
800 Version
2.10
143,360
126,976
126,976
2.10
2.10
2.10
Display
Number
71, 72
74, 75
71, 72
74, 75
Note : You must connect a PC to the ROC800’s LOI port before starting the download.
For information on viewing the memory allocation of user programs, refer to the ROCLINK 800 Configuration Software User Manual (for ROC800-
Series) (Part D301250X012).
1.3.1 License Key
License keys, when matched with valid license codes, grant access to applications such as Cause and Effect.
The term “license key” refers to the physical piece of hardware that can contain up to seven different licenses (refer to Figure 1). Each ROC800 can have none, one, or two license keys installed. If you remove a license key after enabling an application, the firmware disables the task from running. This prevents unauthorized execution of protected applications in a ROC800.
J1
U1
DOC0422A
Figure 1. License Key
Note: The Cause and Effect program requires either Cause and Effect
(for CauseAndEffect_128x48_TLP7172.tar and
CauseAndEffect_128x48_TLP7475.tar program files) or
C&E64X32 (for CauseAndEffect_64x32_TLP7172.tar and
CauseAndEffect_64x32_TLP7475.tar program files) license key depending on your requirements.
Revised June-2016 3
Cause and Effect Manager Program User Manual (for ROC800-Series)
[This page is intentionally left blank.]
4 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Chapter 2 – Installation
This section provides instructions for installing the Cause and Effect program into the ROC800. Read Section 1.3 of this manual for program requirements.
2.1 Installing the License Key
Caution
If you order the Cause and Effect program for a new ROC800, your
ROC800 is delivered with the license key installed. Go to Section 2.2.
If you order the program for an existing ROC800, you must install the license key yourself.
Failure to exercise proper electrostatic discharge precautions, such as wearing a grounded wrist strap may reset the processor or damage electronic components, resulting in interrupted operations.
When working on units located in a hazardous area (where explosive gases may be present), make sure the area is in a nonhazardous state before performing these procedures. Performing these procedures in a hazardous area could result in personal injury or property damage.
To install a license key:
1. Remove power from the ROC800.
2. Remove the wire channel cover
3. Unscrew the screws from the Central Processing Unit (CPU) faceplate.
4. Remove the CPU faceplate
5. Place the license key in the appropriate terminal slot (P4 or P6) in the
CPU
Revised June-2016
Incorrect Correct DOC0423A
Figure 2. License Key Installation
6. Press the license key into the terminal unit it is firmly seated (Refer to
Figure 2.
7. Replace the CPU faceplate.
8. Replace the screws on the CPU faceplate.
9. Replace the wire channel cover.
10. Restore Power to the ROC800.
5
Cause and Effect Manager Program User Manual (for ROC800-Series)
2.1.1 Verifying the License Key Installation
After you install the license key, you can verify whether the ROC800 recognizes the key. From the ROCLINK 800 screen, From the ROCLINK
800 screen, select Utilities > License Key Administrator. The License
Key Administrator screen displays:
Figure 3. Transfer Licenses Between a Device and a Key (Cause and Effect)
6
Figure 4. Transfer Licenses Between a Device and a Key (C&E64X32)
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
2.2 Downloading the Program
This section provides instructions for installing the program into the Flash memory on the ROC800.
To download the program using ROCLINK 800 software:
1. Connect the ROC800 to your computer using the LOI port.
2.
3.
Start and logon to ROCLINK 800.
Select Utilities > User Program Administrator from the ROCLINK menu bar. The User Program Administrator screen displays (see
Figure 3):
Revised June-2016
Figure 3. User Program Administrator
4.
5.
Click Browse in the Download User Program File frame. The Select
User Program File screen displays (see Figure 4).
Select the path and user program file to download from the CD-ROM.
(Program files are typically located in the Program Files folder on the
CD-ROM). As Figure 4 shows, the screen lists all valid user program files with the .tar extension:
7
Cause and Effect Manager Program User Manual (for ROC800-Series)
Figure 4. Select User Program File
6. Click Open to select the program file. The User Program
Administrator screen displays:
8
Figure 5. User Program Administrator
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
7. Click Download & Start to begin loading the selected programs. The following message displays:
Figure 6. Confirm Download
Note: If the User Display Conflict screen (Figure 7) displays when you click the Download & Start, choose another empty slot or select another program that is compatible with your license but with different TLP. See Section 1.3.1 for more information.
8.
Figure 7. User Display Conflict
Click Yes to begin the download. When the download completes the following message displays:
Revised June-2016
Figure 7. ROCLINK 800 Download Confirmation
9. Click OK. The User Program Administrator screen displays (see
Figure 8). Note that:
9
Cause and Effect Manager Program User Manual (for ROC800-Series)
The User Programs Installed in Device frame identifies the installed program(s).
The Status field indicates that the program is running.
Figure 8. User Program Administrator
10. Click Close. The ROCLINK 800 screen displays and the download is complete. Proceed to Chapter 3, Configuration.
2.3 MPU Loading Threshold
To maximize the performance of your ROC800 device, always verify the performance of specific application combinations before using them in the field to ensure the MPU load typically remains below 85% with peak
MPU loading levels below 95%.
To check the current MPU load at any time, select ROC > Information >
Other Information and review the value in the MPU loading field.
10 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Figure 9. MPU Loading
Revised June-2016 11
Cause and Effect Manager Program User Manual (for ROC800-Series)
[This page is intentionally left blank.]
12 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Chapter 3 – Configuration
Before you begin configuring causes and effects, a little planning is helpful. You can have up to 48 effects triggered by up to 128 causes. It is best to plan your effects first, and then decide what triggers them. The intersecting point in the matrix shows which causes trip which effects. It may be useful to use another symbol to show which trips reset automatically when the condition clears, and which ones need a manual reset.
You may wish to use a chart shown in Figure 10 as a handy way to organize your information. Notice the effects are across the top in columns, and the causes are listed down the left side of the table for easy reference:
Revised June-2016
Figure 10. Sample Matrix
13
Cause and Effect Manager Program User Manual (for ROC800-Series)
To configure the program (after logging onto ROCLINK 800 and successfully installing the program), proceed through the program screens as shown in the following sections.
Figure 11. ROCLINK 800
14 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
3.1 Effect Configuration Screen
Each Effect represents a particular action that is taken when the Causes that are linked to it are tripped or cleared. The Value When Active is the value that is applied to the PtDef selected when the Effect Is Active. The
Value When Inactive is the value that is applied to the PtDef selected when the Effect Is Not Active. Use the Assert Effect Continuously option to control writes to the effect point once or continuously. Writing one time to the output can be useful for operations such as setting a discrete output momentary parameter for a resettable output.
The screen is divided into five main sections – Effect Configuration,
Effect Usage, Effect Status, Active Link Tattletale and Effect Edit:
To access this screen:
1.
2.
3.
From the Directory Tree, select User Program > Cause and Effect
Mgr.
Double-click #75, Effect Configuration.
Double-click #1, Effect 1. The Effect Configuration screen displays:
Revised June-2016
Figure 12. Effect Configuration Screen
15
Cause and Effect Manager Program User Manual (for ROC800-Series)
4. Review and change as necessary the values in the following fields:
Field
Point Number
Description
Specifies the effect identification.
Effect Configuration
Use this area to name your effect, define the point and define the active and inactive states that will be applied.
Tag Name Sets the 10-character name for the effect.
Enable Effect If this box is checked, the effect will be processed.
If unchecked, this effect will be ignored, even when a cause is linked to it.
PtDef Sets the TLP to be controlled.
Tag Displays the tag name of the TLP specified in the
PtDef field.
Cur Value Displays the current value of the TLP specified in the PtDef field.
Value When Active Sets the value that is sent to the TLP defined in the
PtDef field.
Value When
Inactive
Sets the value that is sent to the TLP defined in the
Effect Def field whenever the effect is un-actuated.
If the field Force Value When Inactive is unchecked, the TLP defined in the PtDef field is not controlled by Value When Inactive when unactuated.
Force Value When
Inactive
Assert Effect
Continuously
Determines if the Value When Inactive value be written to the TLP defined at PtDef when the effect is un-actuated.
When checked, the Active or Inactive values are written to the PtDef selection continuously. This may be desirable to assure that the output is reasserted to the expected state. When unchecked, the program sets the state one time. This may be useful for a DO point in the momentary mode that must reset itself.
Effect Usage
This frame allows effects to be defined as reset points. Reset points are monitored by causes that require a reset before clearing from a tripped condition.
Normal (Not used as a reset)
Hard-Wired (DI
Point)
Choose this button when the effect is handled as a normal effect (this is the default).
Choose this when you wish the effect to behave as a reset point such as the input for a reset push button.
16 Revised June-2016
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field Description
Software Reset Choose this when you wish the effect to behave as a reset point that can be reset through a variable.
This variable can then be controlled through the
LCD display or set by SCADA. The program will automatically reset the field back to the Inactive
Value after it is set. The program now allows the selection of other data types besides UINT8.
Reset Code Defines a code that if matched to a Cause Reset
Code will reset those Causes when a Software or
Hard-Wired reset point is detected. Multiple codes allow multiple independent resets possibilities.
A reset point is normally a digital input point, such as a status point. For example, you may have the
“Pt Def” configured to be a DI status and the
“Actuated Value” would be the value of the digital input when the reset button is pushed. All causes that require resets (Require Reset = checked) would examine this reset effect and clear all tripped causes assuming their conditions are clear.
Effect Status
This area shows the effect active status and configures the effect delay.
Effect Active Shows whether the effect has been tripped
(actuated).
Active Link Tattletale
This area is informational related to tattletale order and tags.
1 st Trip = Cause # Shows the first cause that currently holds this effect active.
2 nd Trip = Cause # Shows the second cause that currently holds this effect active.
3 rd Trip = Cause # Shows the third cause that currently holds this effect active.
4 th Trip = Cause # Shows the fourth cause that currently holds this effect active.
Tag (1 st – 4 th Trip) Shows the cause tag name.
Current Active Link
Count
Shows the number of causes that currently activate this effect.
Inactive Message Sets a 10 character tattletale tag message when the effect is inactive. This may be useful if the first
Trip tattletale tag is displayed on the LCD and a meaningful inactive message is needed (i.e. “No
Alarms”).
Insert/Delete
This area is used to insert or delete effects within the list.
17
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field Description
Insert Inserts an effect before the Effect # indicated. This button is grayed out when waiting for the Effect # to be entered and applied and re-gray out after the action is taken. Multiple inserts are possible one at a time. The last effect will always roll off the end, so make sure there are unused spares at the end of the list.
Delete Deletes the effect at the Effect # indicated. This button is grayed out when waiting for the Effect # to be entered and applied and re-gray out after the action is taken. Multiple deletes are possible one at a time.
5.
6. delete according to what action is taken. Enter the
Effect # first and the Apply button next to un-gray the Insert/Delete buttons. The two step process is meant to prevent accidental inserts or deletes. It is not necessary to be in the screen showing that effect to operate on a particular Effect #.
Click Apply to save your changes.
Click Close to return to the ROCLINK 800 screen. Proceed to Section
3.2 to configure the Cause Configuration screen.
3.2 Cause Configuration Screen
Causes are configured to do comparisons with a true/false result that controls effects, or configured to do math functions or timing. Other features include delay timing, dynamic enabling, and compound comparisons. You can connect individual causes to one or up to 16 effects.
When the cause is true, the connected effects are actuated.
The Cause Configuration window is divided into eight main sections –
Cause Configuration, Pre-Condition, Primary Logic Section, Secondary
Logic Section, Effect Assignments, Misc Parameters, Insert/Delete and
Cause Status.
To access this screen:
1. From the Directory Tree, select User Program > Cause and Effect
Mgr.
2.
3.
Double-click Display #74 Cause Configuration.
Double-click #1, Cause 1. The Cause Configuration screen displays:
18 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Figure 13. Cause Configuration Screen
Revised June-2016
Figure 14. Cause Configuration Screen – Compound cause selected
19
Cause and Effect Manager Program User Manual (for ROC800-Series)
20
Figure 15. Cause Configuration Screen – Pre-Condition Required enabled
4. Review the values in the following fields:
Field
Point Number
Description
Specifies the cause identification.
General Cause Configuration
Configures the Cause by assigning a name for the cause, defining the cause as simple or compound, and setting whether a pre-condition is required.
Tag Name Sets a 10-character identification name for the selected cause.
Cause Enabled Enables the selected cause. Make sure that everything on the cause configuration screen is configured correctly before enabling the cause.
Simple Sets one logic section for the selected cause.
Compound Sets two logic sections (primary and secondary) for the selected cause.
Sets a pre-condition in order to activate the cause. Pre-Condition
Required
Secondary’s
Relationship with
Primary
Sets the relationship between the primary and secondary logic sections. The two valid selections are AND with Primary and OR with Primary. This parameter shows only when Compound cause is selected.
Revised June-2016
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field Description
Cause Execution Pre-Condition
Defines the pre-condition of the selected cause. This frame shows only when the Pre-Condition Required option is activated or checked in the
General Cause Configuration section.
Pre-Condition Met This read-only parameter shows if the pre-condition is met or not. commences according to the selected operator. The operator selection is located on the left side of the
StPt field. Click to select the operator. Valid operators are == (equal), >= (greater than or equal to), != (not equal), and <= (less than or equal to).
Elaps Sec This read-only parameter shows the elapsed time in seconds.
Primary Logic Section
Defines and Configures the Primary logic of the selected cause.
PtDef Sets the TLP that displays in Cur Value. This item can be any numerical point in the ROC including values from other Causes. Click to browse through the list of available parameters.
Tag Displays the tag name of the TLP specified in the
PtDef field.
Cur Value Displays the current value of the TLP specified in the
PtDef field.
Operator Sets the Cur Value and SetPt Value comparison operator. Click to select the operator.
Avaliable operators are as follows:
>=
<=
==
!=
On-Change
True if greater than or equal to
True if less than or equal to
True if equal to
True if not equal to
One-Scan Rising Cur Value, 0 to 1 transition = true
One-Scan Falling Cur Value, 1 to 0 transition = true
Watchdog Timer Resets on changing value of Cur
Value
Detects a change in the value.
Can monitor a DI accumulator to capture a brief pushbutton press.
Note: The On-Change operator always needs a Required
Reset configured to clear the Cause trip condition.
21
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field Description
Copy Data
Add
Subtract
Multiply
Divide
Modulus
Copies from PtDef to SetPt
Value. There are four different types of copies – by logicals, by parameters, logicals to parameters, parameters to logicals. The numeric value in the DeadBand field to tells the system what type of copy to make and how much data to copy.
Number Copy Type
XX Logicals
Source data located in a Logical order will be copied to the
1XX
2XX
Target data location in a Logical order.
Parameters
Source data located in a Parameter order will be copied to the Target data location in a
Parameter order.
Logicals to
Parameters
Source data located in a Logical order will be copied to the
Target data location in a Parameter
3XX order.
Parameters to
Logicals
Source data located in a Parameter order will be copied to the Target data location in a Logical order.
For example, 105 in the
DeadBand field means copy parameters 0 through 4 to parameters 1 through 5 on another TLP.
Cur Value plus the SetPt Value
Cur Value minus the SetPt Value
Cur Value times the SetPt Value
Cur Value divided by the SetPt
Value
Integer remainder of Cur Value /
SetPt Value.
22 Revised June-2016
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field Description
SetPt Def Sets the TLP of the set point value dynamic source.
Click to browse through the list of available parameters.
SetPt Value Holds the value that is used for comparisons and math functions. This field is not used for the One-
Scan or Watchdog Timer functions. If the SetPt Def field is configured (other than “Undefined”), this field gets its value from the TLP specified in SetPt Def.
Deadband or Math
Result
This field serves three purposes. When using comparison operators (>=, <=, ==, !=), it specifies a dead band value that must be exceeded before an existing true comparison can go false. For math functions (Add, Subtract, Multiply, Divide), this field holds the result of the math operation. For the Copy
Data function, this field defines the number of fields or parameters to copy. DeadBand is not used with
One-Scan or Watchdog Timer functions.
Preset Secs Sets the number of user-defined seconds for which the comparison must be true before the cause goes true. The exception is if Trip While Timer Is Timing is selected, the cause will be true during the timer period.
Elapsed Secs Displays the delay count in seconds up to the userdefined preset. When the comparison becomes true, the count (seconds) increments until it reaches the
“Preset Secs” and the cause becomes true. If at any time the comparison turns false, the count resets to zero and the cause becomes false. The exception is if Trip While Timer Is Timing is selected, the cause will be true during the timer period.
Timer Timing Indicates that the timer has been activated.
Trip While Timer is Timing
When the cause condition is met, this selection when checked, trips the cause while the timer is timing.
The cause clears when the timer expires. This setting is normally used without a Required Reset.
Secondary Logic
Section
Defines and Configures the Secondary logic of the selected cause. This section shows only if
Compound is selected in the General Cause
Configuration frame.
The Secondary Logic section has the same fields and logic as the Primary Logic section.
Effect Assignments
Links the Cause to one or more Effects.
# of Link ( 1-16) Sets the first, second, third (and so on) effect to be activated. For instance, if you wanted effect number
4 to be the first to activate, then enter 4 in the # of
Link 1 field.
# Links Currently
Active
Shows the number of effects that are currently tripped for the cause.
23
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field
Misc Parameters
Description
Allows cause logging and enables cause resetting.
Log Trips Determines if an alarm generated by the cause will be written to the ROC’s alarm log. If this field is checked, every time the cause is tripped an alarm will be logged. The log consists of the cause’s 10character tag and the value of Cur Value along with the date and time.
Require Reset? Check this box if the logic requires that a reset button needs to be pushed before the cause is set back to false. This is normally used in scenarios when the cause goes true it actuates effects that cause a shutdown and it is desired that the shutdown be maintained until a manual reset.
Log Clears Determines whether an entry will be written to the
ROC’s alarm log when this cause is cleared. If this field is checked, every time the cause is cleared an alarm will be logged. The log consists of the cause’s
10-character tag and the value of Cur Value along with the date and time.
Note: Log entries that begin with a “Z” as the first digit are cause entries. Alarms not generated by Cause & Effect are not prefixed with a Z.
Reset Code Sets a numeric value that is associated with the
Effect Reset Code, providing the reset through a button or software point. By using multiple codes, many independent resets are possible.
Minimum Trip
Secs Preset
Holds the trip state for a minimum time so a short duration trip can be detected.
Elaps Trip Secs. Shows the minimum trip timer.
Accumulated
Trips
Insert /Delete
Shows the number of times the cause has been tripped.
Edits the cause list to avoid manually retyping all the cause parameters when a shift is needed.
Insert Inserts a cause before the cause # indicated. This button is grayed out when waiting for the Effect # to be entered and applied and re-gray out after the action is taken. Multiple inserts are possible one at a time. The last cause always rolls off the end, so make sure there are unused spares at the end of the list.
Delete Deletes the cause at the Cause # indicated. This button is grayed out when waiting for the Effect # to be entered and applied and re-gray out after the action is taken. Multiple deletes are possible one at a time.
24 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Field Description according to what action is taken. Enter the Cause # first and the Apply button next to un-gray the
Insert/Delete buttons. The two step process is meant to prevent accidental inserts or deletes. It is not necessary to be in the screen showing that cause to operate on a particular Cause #.
Cause Status
Indicates the Status of the Cause. Red indicates tripped, and green indicates not tripped.
Pre-Condition Met Shows whether the Pre-Condition section has been tripped (1 for Yes, 0 for No).
Primary Section
Tripped
Secondary
Section Tripped
Shows whether the Primary section has been tripped
(1 for Yes, 0 for No).
Shows whether the Primary section has been tripped
(1 for Yes, 0 for No).
Cause Tripped Shows whether the cause has been tripped (1 for
Yes, 0 for No). If this is a compound cause and the relationship between primary and secondary was set to AND, the cause will only be tripped if both the
Primary Section and Secondary Sections are tripped.
5.
6.
Click Apply to save any changes you have made to this screen.
Click Close to return to the ROCLINK 800 screen. Proceed to Section
3.3 to save the configuration.
Revised June-2016 25
Cause and Effect Manager Program User Manual (for ROC800-Series)
3.3 Saving the Configuration
Whenever you modify or change the configuration, it is a good practice to save the final configuration to memory. To save the configuration:
1. Select ROC > Flags. The Flags screen displays:
26
Figure 16. Flags screen
2. Click Save Configuration. A verification message displays:
Figure 17. Perform screen
3. Click Yes to begin the save process. The Flash Write Status field on the Flags screen displays In Progress. When Save Configuration is complete, the Flash Write Status field on the Flags screen displays
Completed.
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
4. Click Update on the Flags screen. This completes the process of saving your new configuration.
Note: For archive purposes, you should also save this configuration to your PC’s hard drive or a removable media (such as a flash drive) using the File > Save Configuration option on the ROCLINK 800 menu bar.
Revised June-2016 27
Cause and Effect Manager Program User Manual (for ROC800-Series)
[This page is intentionally left blank.]
28 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Chapter 4 – Reference Material
This section provides tables of information on the operation of the program and the user-defined point types used by the Cause and Effect program.
For Cause and Effect large versions (Cause and Effect regular license)
Point Type 71/74 (Cause Configuration)
Point Type 72/75 (Effect Configuration)
For Cause and Effect small versions (C&E64X32 license)
Point Type 71/74 (Cause Configuration)
Point Type 72/75 (Effect Configuration)
Revised June-2016 29
Cause and Effect Manager Program User Manual (for ROC800-Series)
4.1 Point Type 71/74: Cause Configurations
Point type 71/74 contains the parameters for configuring the Cause. The program maintains either sixty-four or one-hundred-twenty-eight logical points for this point type.
Point Type 71/74: Cause Configuration
Parm
#
0
Name
Cause Tag
Access
R/W
1 Enable Cause R/W
System or
User Update Data Type Length
User AC10 10
User UINT8 1
Range
0x20 →
0x7E for each ASCII characters
0 → 1
Cause 1 to
Cause
128
0
1.31
1.31
Indicates cause tag name.
2
3
Input1 Definition
Input1 Tag
R/W
R/O
User
System
TLP
AC10
3
1
0,0,0
1
1.31
1.31
Enables the Cause.
0 = Disable
1= Enable
Selects the primary logic current.
Selects the gas meter to be used.
4
5
Cur Value 1
Function1 Type
R/W
R/W
System
User
FLOAT
UNIT8
4
1
0x20 →
0x7E for each ASCII characters
Any Floating
Number
1, 2, 3, 4, 5,
7, 8, 9, 10,
11, 12, 13,
14, 18
0
1
1.31
1.31
Shows the primary logic current value.
6
7
SetPt1 Definition
SetPt1 Value
R/W
R/W
User
User
TLP
FLOAT
3
4 Any Floating number
0,0,0
0
1.31
1.31
Selects the primary logic operator.
1. >=
2. <=
3. ==
4. !=
5. Watch Dog Timer
7. One Scan Rising
8. One Scan Falling
10. Add
11. Subtract
12. Multiply
13. Divide
14. Modulus
18. Copy Data
Sets the primary logic setpoint selection
Sets primary logic setpoint value
30 Revised June-2016
14
15
16
17
Point Type 71/74: Cause Configuration
Parm
#
8
Name
Deadband or
Result1
Access
R/W
9 Part2 Enable R/W
System or
User Update Data Type Length
User FLOAT 4
User UNIT8 1
Range
Any Floating number
0 → 1
10
11
Input2 Definition
Input2 Tag
R/W
R/O
User
System
TLP
UINT8
Cause and Effect Manager Program User Manual (for ROC800-Series)
3
1
0
0
1.31
1.31
1.31
1.31
Sets primary logic setpoint deadband or math result
Enables Secondary.
0 = Simple
1 = Compound
Selects secondary logic point.
Sets secondary logic point tag ID.
12
13
Current Value2
Function2 Type
R/O
R/W
System
User
FLOAT
UNIT8
4
1
0x20 →
0x7E for each ASCII character
Any Floating number
1, 2, 3, 4, 5,
7, 8, 9, 10,
11, 12, 13,
14, 18
0,0,0
0
1
SetPt2 Definition
SetPt2 Value
Deadband or
Result2
And/Or Mode
R/W
R/W
R/W
R/W
User
User
User
User
TLP
FLOAT
FLOAT
UINT8
3
4
4
1
Any Floating number
Any Floating number
15 → 16
0,0,0
0
0
15
1.31
1.31
1.31
1.31
1.31
1.31
Sets secondary logic current value.
Selects the primary logic operator.
1) >=
2) <=
3) ==
4) !=
5) Watch Dog Timer
7) One Scan Rising
8) One Scan Falling
10) Add
11) Subtract
12) Multiply
13) Divide
14) Modulus
18) Copy Data
Sets the primary logic setpoint.
Sets primary logic setpoint value.
Sets primary logic setpoint deadband or math result.
Sets Secondary relationship with Primary.
15 = And with Primary
16 = Or with Primary
Revised June-2016 31
Cause and Effect Manager Program User Manual (for ROC800-Series)
Point Type 71/74: Cause Configuration
Parm
#
18
Name
Cause Trip/Clear
Access
R/O
System or
User Update Data Type Length
System UINT8 1
Range
0 → 1
19 Part1 Trip/Clear
20 Part2 Trip/Clear
21 Use Digital Enabler R/W
22
23
Digi Enab Definition
Digi Enab Tag
R/W
R/O
24
25
Digi Enab Process
Value
Digi Enabler Type
R/O
R/W
26
27
Digi Enab StPt
Value
Digi Enab Result
Status
32
28
29
Enab Delay Secs
Preset
Enab Delay Secs
Elapsed
R/O
R/O
R/W
R/O
R/W
R/O
System
System
User
User
System
System
User
User
System
User
System
UINT8
UINT8
UINT8
TLP
AC10
FLOAT
UINT8
FLOAT
UINT8
UINT16
UINT16
1
1
1
4
1
2
2
0 → 1
0 → 1
0 → 1
0
0
0
0
4
1
3
10 0x20 →
0x7E for each ACII character
Any Floating number
0 → 3
0,0,0
0.0
0
Any Floating number
0 → 1
0 → 65535
0 → 65535
0.0
0
30
0
1.31
1.31
1.31
1.31
1.31
1.31
Shows Cause Tripped status.
0 = No
1 = Yes
Shows Primary Section Tripped status.
0 = No
1 = Yes
Shows Secondary Section Tripped status.
0 = No
1 = Yes
Enables pre-condition required.
0 = Disable
1 = Enable
Sets the pre-condition point type.
Sets the pre-condition point tag ID.
1.31
1.31
1.31
1.31
1.31
1.31
Sets the pre-condition point value.
Sets the pre-condition operator.
0) ==
1) !=
2) >=
3) <=
Sets pre-condition setpoint.
Shows if the pre-condition met.
0 = No
1 = Yes
Sets the pre-condition timer in seconds.
Shows the pre-condition timer in seconds.
Revised June-2016
Point Type 71/74: Cause Configuration
Parm
#
30 Pri Trip Delay Secs
Preset
Name Access
R/W
31
32
Pri Trip Delay Secs
Elapsed
Scan Interval
R/O
R/W
System or
User Update Data Type Length
User UINT16 2
System
User
UINT16
UINT8
2
1
Range
0 → 65535
0 → 65535
0 → 5
33
34
Log Alarms
Require Reset
39
40
41
42
43
35
36
37
38
Effect1
Effect2
Effect3
Effect4
Effect5
Effect6
Effect7
Effect8
Links Energized
44
45
Min Trip Secs
Preset
Min Trip Secs
Elapsed
Revised June-2016
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/O
User
User
User
User
User
User
User
User
User
User
System
User
System
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT16
UINT16
Cause and Effect Manager Program User Manual (for ROC800-Series)
1
1
1
1
1
1
1
1
1
1
1
2
2
0 → 1
0 → 1
1 → 8
1 → 8
1 → 8
1 → 8
1 → 8
1 → 8
1 → 8
1 → 8
1 → 8
0 → 65535
0 → 65535
0
0
0
0
0
0
0
0
0
0
0
0
0
3
0
0
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
Sets the Primary Logic Trip Preset in seconds.
Shows the Primary Logic Trip Elapsed in seconds.
Sets the scan interval. (Not Used)
0 = 100 ms
1 = 200 ms
2 = 500 ms
3 = 1 s
4 = 2 s
5 = 5 s
Activates the Alarm Log
1 = No
1 = Yes
Sets if Trip requires reset
1 = No
1 = Yes
Sets Effect assignment link 1
Sets Effect assignment link 2
Sets Effect assignment link 3
Sets Effect assignment link 4
Sets Effect assignment link 5
Sets Effect assignment link 6
Sets Effect assignment link 7
Sets Effect assignment link 8
Indicates if the Effects assignment links are currently active.
Sets the minimum trip in seconds preset.
Sets the minimum trip in seconds elapsed.
33
Cause and Effect Manager Program User Manual (for ROC800-Series)
Point Type 71/74: Cause Configuration
Parm
#
46
Name
Log Clears
Access
R/W
System or
User Update Data Type Length
User UINT8 1
Range
0 → 1
55
56
57
58
59
60
61
34
62
47
48
49
50
Reset Code
Sec Trip Delay
Secs Preset
Sec Trip Delay
Secs Elapsed
Pri Trip Delay Timer
Timing
R/W
R/W
R/O
R/O
51 Sec Trip Delay
Timer Timing
R/O
52
53
Accumulated Trips
Pri Trip When Timer
Timing
R/W
R/W
54 Sec Trip When
Timer Timing
R/W
Effect 9
Effect 10
Effect 11
Effect 12
Effect 13
Effect 14
Effect 15
Effect 16
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
User
User
User
System
UINT8
UINT16
UINT16
UINT8
2
1
1
2
0 → 255
0 → 65535
0 → 65535
0 → 1
0
0
0
0
System
Both
User
User
UINT8 1 0 → 1 0
UINT16
UINT8
2
1
0 → 65535
0 → 1
0
0
UINT8
User
User
User
User
User
User
User
User
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
1
1
1
1
1
1
1
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
0
0
0
0
0
0
0
0
0
0 1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
Enables logs clears to alarm log.
0 = No
1 = Yes
Sets reset code to match with effect reset code.
Sets the secondary trip preset in seconds
Sets the secondary trip elapsed in seconds
Sets the primary logic trip timer timing.
0 = Timer expired
1 = Timing
Sets the secondary logic trip timer timing.
0 = Timer expired
1 = Timing
Shows accumulated trips
Sets the secondary trip when timing timer.
0 = Normal
1 = Trip when timer timing
Sets the primary trip when timing timer.
0 = Normal
1 = Trip when timer timing
Sets the Effect assignment link 9.
Sets the Effect assignment link 10.
Sets the Effect assignment link 11.
Sets the Effect assignment link 12.
Sets the Effect assignment link 13.
Sets the Effect assignment link 14.
Sets the Effect assignment link 15.
Sets the Effect assignment link 16.
Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Point Type 71/74: Cause Configuration
Parm
#
63
Name
Watchdog Timer
Access
R/O
System or
User Update Data Type Length
System UINT16 2
Range
0 → 65535 0 13.2 Provides an incrementing counter, to validate the program’s running status.
Only updated for the first logical instance.
Revised June-2016 35
Cause and Effect Manager Program User Manual (for ROC800-Series)
4.2 Point Type 72/75: Effect Configuration
Point type 72/75 contains the parameters for configuring the Effects. The program maintains either thirty-two or sixty-four logical points for this point type, depending on the version of the program installed.
Point Type 72/75: Effect Configuration
Parm
#
0
Name
Effect Tag
Access
R/W
1 Effect Enable R/W
System or
User Update
User
User
Data
Type
AC10
UINT8
Length
10
1
Range
0x20 →
0x7E for each ASCII character
0 → 1
Default Version
Effect 1 to Effect
64
1.31
0 1.31
Description of functionality and meaning of values
Sets the Effect tag name
2
3
4
Effect Definition
Definition Tag
Now Active
R/W
R/O
R/O
User
System
System
TLP
AC10
UINT8
3
10
1
0x20 →
0x7E for each ASCII character
0 → 1
0,0,0
0
1.31
1.31
1.31
Enables effect.
0 = Disabled
1 = Enabled
Selects the Effect point type.
Shoes the Point tag ID of the selected
Effect.
5 Cur Val R/O System FLOAT 4 0.0 1.31
Indicates the Effect status.
0= No
1 = Yes
Shows the Effect current value.
6
7
8
Value When Active
Value When Not Active
Apply When Not Active
R/W
R/W
R/W
User
User
User
FLOAT
FLOAT
UINT8
4
4
1
Any Floating
Number
Any Floating
Number
Any Floating
Number
0 → 1
0.0
0.0
1
1.31
1.31
1.31
Sets Effects value when active.
Sets Effects value when not active.
9 Is Reset Pt? R/W User UINT8 1 0 → 2 0 1.31
Forces Values to apply when inactive.
0 = No
1 = Yes
Sets the Reset type.
0 = Not a reset point
1 = Hard-wired reset
2 = Software reset
36 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
Point Type 72/75: Effect Configuration
Parm
#
10
Name
1st Out Cause
Access
R/O
System or
User Update
System
11
12
13
14
15
16
17
18
19
2nd Out Cause
3rd Out Cause
4th Out Cause
1st Out Tag
2nd Out Tag
3rd Out Tag
4th Out Tag
Reset Code
Active Link Count
R/O
R/O
R/O
R/O
R/O
R/O
R/O
R/W
R/O
System
System
System
System
System
System
System
User
System
Data
Type
UINT8
UINT8
UINT8
UINT8
AC10
AC10
AC10
AC10
UINT8
UINT8
Length
1
1
1
1
10
10
10
10
1
1
Range
0 → 1
0 → 1
0 → 1
0 → 1
0x20 →
0x7E for each ASCII character
0x20 →
0x7E for each ASCII character
0x20 →
0x7E for each ASCII character
0x20 →
0x7E for each ASCII character
0 → 255
<none>
<none>
<none>
0
0 → 16
Default Version
0 1.31
0
0
0
<none>
1.31
1.31
1.31
1.31
Description of functionality and meaning of values
Indicates first cause number tattletale.
0 = none
1 = active
Indicates second cause number tattletale.
0 = none
1 = active
Indicates third cause number tattletale.
0 = none
1 = active
Indicates fourth cause number tattletale.
0 = none
1 = active
Shows first Trip Cause Tag.
0
1.31
1.31
1.31
1.31
1.31
Shows second Trip Cause Tag.
Shows third Trip Cause Tag.
Shows fourth Trip Cause Tag.
Matches reset code with cause reset code.
Shows current active link count.
Revised June-2016 37
Cause and Effect Manager Program User Manual (for ROC800-Series)
Point Type 72/75: Effect Configuration
Parm
#
20
Name
Assert Effect
Continuously
Access
R/W
System or
User Update
User
21
22
23
24
25
Active Effect Delay (Sec)
Active Effect Timer (Sec)
Tattletale Inactive
Message
Insert/Delete Edit
Command
Insert/Delete Edit Item
R/W
R/O
R/W
R/W
R/W
User
System
User
Both
Both
Data
Type
UINT8
UINT16
UINT16
AC10
UINT8
UINT8
Length
1
2
2
10
1
1
Range
0 → 1
0 → 65535
0 → 65535
0x20 →
0x7E for each ASCII character
0 → 4
Default Version
0 1.31
0
0
<none>
1.31
1.31
1.31
Description of functionality and meaning of values
Sets wether to assert effect once or continuously.
0 = Once
1 = Continuously
Sets active effect delay in seconds
Sets active effect timer in seconds
Sets Tattletale inactive message.
0
0
1.31
1.31
Allows insert/delete edit command.
0 = No command
1 = Effect insert
2 = Effect delete
3 = Cause insert
4 = Cause delete
Allows insert/delete edit item. 0, 1 → 64 for Causes,
1 → 32 for
Effects
38 Revised June-2016
Cause and Effect Manager Program User Manual (for ROC800-Series)
[This page is intentionally left blank.]
Revised June-2016 39
Cause and Effect Manager Program User Manual (for ROC800-Series)
For customer service and technical support, visit www.EmersonProcess.com/Remote/Support .
Global Headquarters,
North America, and Latin America:
Emerson Process Management
Remote Automation Solutions
6005 Rogerdale Road
Houston, TX 77072 U.S.A.
T +1 281 879 2699 | F +1 281 988 4445 www.EmersonProcess.com/Remote
Europe:
Emerson Process Management
Remote Automation Solutions
Unit 8, Waterfront Business Park
Dudley Road, Brierley Hill
Dudley UK DY5 1LX
T +44 1384 487200 | F +44 1384 487258
Middle East/Africa:
Emerson Process Management
Remote Automation Solutions
Emerson FZE
P.O. Box 17033
Jebel Ali Free Zone – South 2
Dubai U.A.E.
T +971 4 8118100 | F +971 4 8865465
Asia-Pacific:
Emerson Process Management
Remote Automation Solutions
1 Pandan Crescent
Singapore 128461
T +65 6777 8211| F +65 6777 0947
© 2014–2016 Remote Automation Solutions, a business unit of Emerson Process
Management. All rights reserved.
This publication is for informational purposes only. While every effort has been made to ensure accuracy, this publication shall not be read to include any warranty or guarantee, express or implied, including as regards the products or services described or their use or applicability.
Remote Automation Solutions (RAS) reserves the right to modify or improve the designs or specifications of its products at any time without notice. All sales are governed by RAS terms and conditions which are available upon request. RAS accepts no responsibility for proper selection, use or maintenance of any product, which remains solely with the purchaser and/or end-user.
Remote Automation Solutions