BEA MULTI-SENSOR HUB User guide
Oglas
Oglas
DESCRIPTION
M R
H S n T X
ACTIV8 ONE ON = IXIO
Output 1: Green LED
Output 2: Red LED
Door controller connector
DIP-switches
LED SIGNAL
1 + 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
Input 1: Green LED
Input 2: Red LED
Sensor connectors
Yellow LED
Confirmation push button
GREEN
ON
Output 1
Input 1
RED
ON
Output 2
Input 2
LED switches ON during detection
Active mode
LED switches OFF during detection
Passive mode
YELLOW flashing
Awaiting confirmation
DIP-switch setting
TECHNICAL SPECIFICATIONS
Max. load current:
Supply voltage:
Output to door controller:
Monitoring input from door controller:
Input from each sensor:
Monitoring output to each sensor:
Monitoring response time:
LEDs:
Norm conformity:
Temperature range:
Dimensions:
Housing material:
Length of sensor cables:
Length of power cable:
Lifetime:
2 A
12 V DC - 24 V DC +10% (min. 16 V DC @ max. load current)
2 galvanical isolated outputs (OPTOFET; U
MAX
= 42 V DC; I
MAX
= 100 mA) maximum output power dissipation: 200 mW off-state leakage current: 10 µA on-state maximum resistance: 20 Ohms
1 galvanical isolated input (Optocoupler; max 30 V DC (6 mA)); voltage threshold: logic high: >10 V DC (2 mA); logic low: <1 V DC
2 non-isolated inputs
1 non-isolated output (U
OUT
= U
SUPPLY
; I
MAX
= 50 mA) from 200µs to 50ms (depending on sensors & hub setting) red & green for status display of each connected sensor red & green for hub output status display orange for DIP-switch status change display
Electromagnetic compatibility (EMC) according to 2004/108/EEC
EN ISO 13849-1:2006 Performance Level "c”, CAT 2
EN 62061:2005 SIL 2 from -25° to +60° (for indoor use only)
70 mm (L) x 55 mm (H) x 25 mm (D)
ABS (translucent blue)
2.70 m
2.60 m designed for minimum 10 years
Specifications are subject to changes without prior notice.
For more information concerning the monitoring cycle, see application note on monitoring by voltage.
1/2
WIRING
2.
ON
1 2 3 4 5 6 7 8 9 10
1.
MULTI-SENSOR HUB
OUTPUT 1
OUTPUT 2
GREEN
BROWN
YELLOW
WHITE
GREY
PINK
RED
BLUE
DOOR CONTROLLER
24V DC
GND
IN 1
IN 1
IN 2
IN 2
TEST +
TEST -
1. Connect the sensors (from 1 to 4) to the sensor connectors starting from the left using the cables that have connectors on both ends.
Attention! Never use the 4SAFE power cable to connect the Hub to the door controller.
2. Connect the cable with only one connector from the Hub to the door controller (see wiring diagram).
DIP-SWITCH SETTINGS
1
2
Number of sensors connected to the Hub
ON
1 2 3 4 5 6 7 8 9 10
1 sensor
3 Type of sensor connected to the Hub
4 Logic Output 1
ON
1 2 3 4 5 6 7 8 9 10
2 sensors
ON
1 2 3 4 5 6 7 8 9 10
ON 4SAFE
OFF
ACTIV8 ONE
IXIO
ON
1 2 3 4 5 6 7 8 9 10
ON Passive
OFF Active
ON
1 2 3 4 5 6 7 8 9 10
3 sensors
ON
1 2 3 4 5 6 7 8 9 10
4 sensors
Only one type of sensor can be connected simultaneously.
Do not mix sensor types.
Check the output logic on the connected sensors.
The output logic has to be the same on the Hub and on all connected sensors (see LED-signal).
5 Logic Output 2
ON
1 2 3 4 5 6 7 8 9 10
ON Passive
OFF Active
Check the output logic on the connected sensors.
The output logic has to be the same on the Hub and on all connected sensors (see LED-signal).
6 Relay debounce avoids the bouncing of the relay contact during a monitoring request
ON
1 2 3 4 5 6 7 8 9 10
ON ON
OFF OFF
Recommended when the monitoring input is connected to a relay output on the door controller.
Set to OFF for a faster response time.
7
8
9
Monitoring mode
The monitoring has to be active on all connected sensors!
Monitoring cycle time in asynchronous mode
Monitoring type
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON Asynchronous
OFF Synchronous
ON
10 min
OFF 20 sec
The Hub sends a monitoring request to all connected sensors every x seconds (according to DIP 8 setting), independent of the door controller.
When the door controller sends a monitoring request to the Hub, it answers immediately giving the result of the last monitoring cycle.
The Hub sends a monitoring request to all connected sensors only when the door controller sends a monitoring request to the Hub. The response time on monitoring request is dependent on response time of the connected sensors.
The Hub sends a monitoring request to all connected sensors every 10 minutes (only in asynchronous mode).
The Hub sends a monitoring request to all connected sensors every 20 seconds (only in asynchronous mode).
ON
1 2 3 4 5 6 7 8 9 10
ON
OFF
Standard voltage monitoring
Signal output
100 Hz
Most frequently used type of monitoring using test input.
Only if your door controller is compatible with this type of monitoring.
10 Not used
YELLOW OFF
After changing one or more DIP-switch settings, the yellow
LED flashes. Confirm the new setting(s) by pushing the push button until the LED switches off. The setting is confirmed.
BEA SA - LIEGE Science Park - Allée des Noisetiers 5 - B-4031 Angleur - T +32 4 361 65 65 - F +32 4 361 28 58 - [email protected] - www.bea.be