Scroll Air Compressor


Add to my manuals
36 Pages

advertisement

Scroll Air Compressor | Manualzz
Source Equipment
Air Compressors
Source Equipment
Table of Contents
How To Use This Section...........................................................................................................................................................................................................1
Introduction......................................................................................................................................................................................................................................1
The Four Essentials To Building a Medical Air System............................................................................................................................................1
Steps to Implementing the Medical Air System........................................................................................................................................................2
Discovery....................................................................................................................................................................................................................................... 2-3
Figure 1: Air Intake Location...................................................................................................................................................................................................2
Design..................................................................................................................................................................................................................................................3
Plant Sizing................................................................................................................................................................................................................................... 3-5
Table 1: NFPA Method - Medical Air Flow Calculation Chart......................................................................................................................... 4-5
Altitude Adjustments..................................................................................................................................................................................................................5
Table 2: Altitude Compensation Chart.............................................................................................................................................................................6
Compensating for Future Expansion................................................................................................................................................................................6
Plant Selection................................................................................................................................................................................................................................6
General Layout................................................................................................................................................................................................................................7
Specification.....................................................................................................................................................................................................................................7
Technology Comparison Chart.............................................................................................................................................................................................8
Medical Air Systems Glossary and Specifications......................................................................................................................................................9
Table 3: Medical Air Systems Glossary..............................................................................................................................................................................9
Summary of NFPA 99 Specification (Air Compressor Systems)..............................................................................................................10-17
Quick Guide to Configuration............................................................................................................................................................................................ 18
Medical Air System Inlet......................................................................................................................................................................................................... 19
Table 4: Medical Air Compressor System Intake Pipe Sizing Chart.............................................................................................................. 20
Table 5: Example 1: Calculating SCFM........................................................................................................................................................................... 21
Medical Air Scroll Compressor Specification Sheet.......................................................................................................................................22-23
Duplex Scroll Tank Mounted Horizontal Configuration Air Compressor (2.0 HP - 10.0 HP)......................................................... 24
Duplex Scroll Modular Stacking Configuration Air Compressor (2.0 HP - 20.0 HP)........................................................................... 25
Triplex Scroll Modular Stacking Configuration Air Compressor (2.0 HP - 20.0 HP)............................................................................ 26
Quadruplex Scroll Modular Stacking Configuration Air Compressor (2.0 HP - 20.0 HP)................................................................ 30
Oil-Less Reciprocating Air Compressor Specification Sheet.....................................................................................................................31-33
Duplex Reciprocating Tank Mounted Horizontal Air Compressor (1.0 HP - 5.0 HP)......................................................................... 30
Duplex Reciprocating Modular Stacking Configuration Air Compressor (1.0 HP - 20.0 HP)....................................................... 31
Triplex Reciprocating Modular Stacking Configuration Air Compressor (1.0 HP - 20.0 HP)......................................................... 32
Quadruplex Reciprocating Modular Stacking Configuration Air Compressor (1.0 HP - 20.0 HP)..............................................33
Amico Source Corporation
How to Use This Section
The following section is structured in a manner such that the medical air system for a project may be established and
executed in a sound and simple progression. Examples are given whenever possible.
The basic milestones in designing the medical air system are as follows:
• Definitions – Definitions are provided in the glossary section which contains terminologies which may be frequently utilized within the Medical Air Systems section. These terms may also be helpful in understanding and specifying the appropriate medical air system.
• Design – General outline pertaining to the procedural involvement in designing your Medical Air Systems.
• Sizing and Selecting the Medical Air System – Step by step calculation exemplifying how to calculate the
Peak Calculated Load (PCL) Requirements for the medical facility.
• Installation – Steps to building your medical air systems.
Introduction
Medical Air Systems
The NFPA 99 standards for Medical Air Compressors define an essential foundation of Medical Air Compressors
as follows: air should start clean and be kept clean. For that reason, the air inhaled by the patient at the very least
should be minimally equal to filtered local outdoor air.
All compressors included herein are deemed suitable for medical use under The NFPA standards. For further
information on NFPA compliant medical systems, please consult your Local Amico Source Corporation
representative.
THE FOUR ESSENTIALS TO BUILDING A MEDICAL AIR SYSTEM:
1. The intake air location must never be contaminated by placing the medical air systems in a poorly ventilated area.
2. The medical air must be available at all times, including in the event of a single fault failure.
3. The air must be dry enough to ensure no liquid water can develop under any normal operating conditions
(This is not necessarily assured simply by meeting the NFPA mandated dew point).
4. Any contamination whereby the system can produce within itself under any conditions (e.g., particulate) must
be removed (e.g., by filtration) before it can reach the patient.
NFPA defines various rules for the construction of the air plant and the safety devices required for each machine
type. Additionally, good engineering practice defines crucial elements such as after coolers, drains and traps, dryers,
vibration isolation, and hundreds of other small but significant elements of good air system design. Amico Source
Corporation has pre-engineered all the medical air systems in this section to warrant that they include not only
the basic requirements of the principles, but also the many foundations behind good engineering. This section of
the design guide also permits the user to make selections of complete medical air packages for reasons specified
hereafter. It is impractical to craft a design guide encompassing all the knowledge Amico Source Corporation’s
engineers have applied to the design of these systems. Nevertheless, within this design guide, you can easily locate
the necessary information to ensure you can apply these systems with confidence and provide for your client a fully
satisfactory medical air system. Medical air in smaller systems may be provided by manifolds in lieu of compressor
systems. The sizing criteria are the same for either source type.
www.amico.com
1
Steps to Implementing the Medical Air System
DISCOVERY
1. Should existing equipment be incorporated along with the medical air system, determine the dimensions,
type, capacity and current loading of the existing equipment. Ensure the existing equipment is compatible
with the current standard.
2. Verify the number and type of all occupancies in the facility which will require medical air outlets.
3. Determine the number of ventilators required to be in service at any one time and define their type and
average inlet air requirement.
4. The intake piping for a medical air compressor system should only be connected to the medical air
compressor system and not used for any other purpose. It should be made of hard-drawn seamless copper,
either ASTM B 819 medical gas tube, ASTM B 88 water tube (Type K, L, or M), or ASTM B 280 ACR tube, which
ensures no contaminants in the form of particulate matter, odor or other gases will be added. This piping
is to be labeled and equipped with intake filters that are located inside the health care facility, close to the
compressor, and are easily accessible for servicing. Examine the location intended for the air intake carefully
as NFPA mandates the intake be located at a minimum of 10 ft. (3 m) from any door or operable window; 20
ft. (6.1 m) above grade, and in a location likely to provide uncontaminated air under any conditions of wind
or weather. The intake opening shall be turned downward and screened. It shall be accessible to authorized
personnel for cleaning, inspection and servicing. If the air intake is near a loading dock or at a location where
vehicles may be present, it must be relocated. It is advisable to place the intake at a height above any other
intake or vent on the same roof (see Figure 1 below). For further details regarding the rules and regulation in
choosing your medical air system location, please refer to the latest edition of the NFPA specification guide.
Figure 1:
Turned down
and screened
Air Intake Location
10 ft. (3 m) away from any
door or operable window
Consider the prevailing winds
Away from
obvious sources of
contaminations
(e.g., car exhausts)
20 ft. (6.1 m) above grade
2
Amico Source Corporation
5. Determine a routing for the intake piping and note it on the building drawings. Piping downstream of the
compressor shall be routed in a manner such that it is not subjected to temperatures lower than 40 °F (4 °C).
6. Ensure the intended location for the air plant is adequately ventilated or is at minimum air conditioned. The
plant will emancipate a considerable amount of heat into the surroundings. Hence, it must be factored in
when selecting a compressor site; determining the adequacy of ventilation; or identifying BTU requirements
for air conditioning. (BTU data is furnished in the equipment data sheet).
7. Determine the availability of electrical service.
8. If the medical air system is not already piped to the proposed location, determine the routing for the piping
and note it on the building drawings.
DESIGN
1. Follow directions for laying out piped medical gases. This will supply a count of outlets which is necessary for
the next steps.
PLANT SIZING
1. There are several available methods for sizing Medical Air. For the purpose of this design guide, only the
National Fire Protection Association (NFPA) Method will be discussed.
The NFPA Plant Sizing Method
1. Count all outlets within the infrastructure that will utilize the air compressor system (see Table 1 on next page).
In situations in which the exact type of room cannot be located within the table, please select the one which
most closely approximates the room as indicated in the chart.
2. Once the total amount of outlets are entered, the next step entails multiplying all variables across the table
(left to right) to apply the simultaneous usage factor.
3. Obtain an estimate of air requirement by summing the columns (top to bottom).
4. NFPA recommends the inclusion of additional capacity for potential ventilator use. However, this ventilator
factor causes significant problems and is usually the cause behind gross over-sizing for medical air plants.
Therefore, extreme caution should be taken.
www.amico.com
3
Table 1: NFPA Method - Medical Air Flow Calculation
Please refer to the table below to obtain an average flow that is required within the facility. This chart is also available
at www.amico.com.
Medical Air
Use Factor (%)
Number of Units
Beds, Rooms,
Outlets
SCFM
0.5
100
0
0.00
0.5
100
0
0.00
0.5
0.5
0.5
0.5
75
25
10
10
100
100
0
0
0
0
0
0
0.00
0.00
0.00
0.00
0.00
0.00
2
25
0
0.00
2
2
1.5
0.5
50
10
75
10
25
100
0
0
0
0
0
0
0.00
0.00
0.00
0.00
0.00
0.00
0.5
25
0
0.00
0.5
10
0
0.00
10
20
50
50
50
50
25
0
0
0
0
0
0
0
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Free Air Allowance, SCFM
Location of Outlets
Anesthetizing Locations
Special Surgery and
Cardiovascular
Major Surgery and
Orthopedic
Minor Surgery
Emergency Surgery
Radiology
Cardiac Catheterization
Ventilators
Delivery Rooms
Acute Care Locations
(Non-Anesthetizing)
Recovery Room/Surgical
(Post-Anesthesia)
ICU/CCU
Emergency Room
Neonatal ICU
Dialysis Units
Recovery Rooms/OB
Ventilators
Sub-Acute Patient Care
(Non-Anesthetizing)
Nursery
Patient Rooms
(where shown)
Exam & Treatment Rooms
Pre-Op Holding
Respiratory Care
Pulmonary Function Lab
EEG and EKG
Birthing and LDRP
Patient Isolation Room
4
Amico Source Corporation
Per
Unit
Per
Bed
Per
Room
Per
Outlet
3.5
0.5
2
6
1
1.5
1
1
1
1
0.5
Simultaneous
Air
Medical Air
Use Factor (%)
Number of Units
Beds, Rooms,
Outlets
SCFM
1.5
10
0
0.00
1.5
10
0
0.00
1.5
1.5
10
10
25
100
10
50
10
0
0
0
0
0
0
0
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Free Air Allowance, SCFM
Location of Outlets
Other Patient Rooms
Anesthesia Workroom
Respirator Care
Workroom
Nursery Workroom
Equipment Repair
Med. Laboratory 3
Autopsy
Sterile Supply
Plaster Room
Pharmacy
Future Expansion
Per
Unit
Per
Bed
Per
Room
Per
Outlet
1.5
1
1
1
1
Simultaneous
PEAK CALCULATED DEMAND IN SCFM
BASED ON FREE AIR SCFM @ 50PSI:
Air
0.00
Note:
1. The SCFM above is based on a peak OUTLET demand of 50 psi. Air compressors operate at 100 psi. When sizing
a compressor, you MUST figure the compressor capacity for operation at 100 psi.
2. You need to consider several environmental factors when sizing the compressors. These include altitude,
intake air temperature, and relative humidity. Variance among these factors has considerable effect on
compressor selection.
3. Air outlets in labs used for analysis, research or teaching should be supplied by a separate compressed air
system, not the medical air system.
4. All sizing methods are only approximations and should be used judiciously. If an existing compressor is being
replaced, the operating characteristics of that compressor can be an important gauge of likely future use. For
example, if an existing 5 HP compressor provides an ample amount of medical air, but the sizing tables yield
much larger requirements; it may be suitable to use a smaller compromise unit as opposed to simply relying
on the results from the Amico Sizing Guide.
ALTITUDE ADJUSTMENTS
If the compressor is to be operated at higher elevations, the peak calculated demand should be multiplied by the
corresponding correction factor. Specifically, at altitudes above sea level, all medical air systems have reduced flow.
In such cases, the required sizing will need to be adjusted by taking the total PCL (SCFM) and multiplying it by the
correction factor (see Table 2 on next page).
www.amico.com
5
Table 2: Altitude Compensation Chart
Altitude
Multiplier Used for Required SCFM (Hg)
Sea Level
1.00
1000 ft. (305 m)
1.01
2000 ft. (609 m)
1.03
3000 ft. (900 m)
1.05
4000 ft. (1219 m)
1.06
5000 ft. (1525 m)
1.08
6000 ft. (1828 m)
1.10
7000 ft. (2133 m)
1.12
8000 ft. (2438 m)
1.15
9000 ft. (2743 m)
1.17
10,000 ft. (3048 m)
1.19
COMPENSATING FOR FUTURE EXPANSION
The notion of adding capacity now for any future requirements is wise, but extreme caution is also advised. It
is common to see very badly oversized air plants which were initially sized to accommodate an expansion that
never occurred or that was scaled back and was not compulsory after all. In addition to the waste of investment, it
generates problems associated with the operation of the system. The best method in preparing for an anticipated
expansion is to opt for a plant which is adequate for the present need in a duplex or triplex system but can also
be upsized for future need by simply adding additional compressors as required. When specifying for the unit,
require it be purchased in preparation for additional compressor(s) yet not populated with those compressors. A
representative specification would read: “provide duplex medical air plant with triplex controls and air treatment
subsystem ready for a future third compressor”. Such a system provides an effective method of expanding the system
capacity, is more capital-efficient, and yields better operating characteristics and reliability when it comes to air
quality control. Nevertheless, it is fundamentally important that the intake, electrical service, and system piping are
correctly sized for the entire expected capacity, so these larger values should be used in all calculations.
PLANT SELECTION
1. Select a preferred technology (see Page 8). More specific assistance in selecting a technology may be
obtained by contacting your Local Amico Source Corporation representative.
2. Choose a Horsepower from the preferred technology with the capacity closest to (but typically greater than)
the Peak Calculated Load (PCL).
3. Note that for some technologies, there is more than one plant architecture. Should one or more layout be
available for selection, choose the one best suited to the site conditions. If in doubt as to which arrangement
is most suitable for a particular situation, contact your Local Amico Source Corporation representative for
assistance.
4. Reference the Technology Comparison Chart (page 8) for the particular system selected. This chart entails
all of the essential information regarding the system and should be utilized as a quick reference in all of the
following steps.
6
Amico Source Corporation
GENERAL LAYOUT
1. Place the plant in scale on the plan drawings in the designated location. Ensure that the plant has sufficient
space on all sides for maintenance access and proper ventilation. Amico Source Corporation recommends 2
ft. (24") minimum clearance on all sides, 3 ft (36") in front of the control panel, but it is sometimes possible to
reduce this clearance with exact knowledge of maintenance access requirements. Consult your Local Amico
Source Corporation representative if circumstances allow for less space.
2. Place the equipment in elevation views as appropriate.
3. On the plan, finalize the routing for the intake.
4. Size the intake piping. The sizing process is iterative:
a. Start with the total actual length of piping, and make an estimate for the line size (see Table 4).
b. By using your estimated size, add equivalent lengths for the fittings employed.
c. Check that the size of the intake piping is still suitable at the new equivalent length. Should there be
any discrepancies, re-estimate the next larger size and repeat the steps above. The line may also be
sized more precisely by conducting an actual calculation. Intake piping must be sized to induce no
more than 4 inches water column vacuum at the compressor when all compressors are operating.
(Use total capacity for this calculation with all compressors running).
For unusual lengths or other circumstances, please contact your local Amico Source Corporation
representative for assistance.
5. Finalize the connection to the distribution piping and size the system piping.
SPECIFICATION
1. Select the sections appropriate to the technology and system layout desired.
2. Note into the specification any exceptional requirements that are necessary (e.g., soft starters, etc.).
3. Schedule in the drawings the medical air plant selected.
Schedule at least:
a. The capacity per compressor (per NFPA) and total system capacity.
b. Horsepower per compressor.
c. Voltage, Hz, and phase desired.
www.amico.com
7
TECHNOLOGY COMPARISON CHART
Amico Source Corporation offers several technologies for medical air, each of which has its own advantages
and drawbacks. This page summarizes these as an aid in the selection of the correct technology for your specific
application.
Characteristics
Format
Scroll
Dry Reciprocating
Lubricated
Reciprocating
Rotary Screw
• Modular Stacking
• Modular Stacking
• Modular Stacking
• Horizontal Tank Mount
• Horizontal Tank Mount
• Horizontal Tank Mount
• Skid Mount
• Skid Mount
• Skid Mount
Lubrication
Oil Free
Oil Free
Lubricated
Oil Free
dBa*
74
84
82
72
SCFM*
32.0 @ 120 psig
32.5 @ 100 psig
32.8 @ 100 psig
85 @ 100 psig
LPM*
651 @ 828 kPa
920 @ 689 kPa
929 @ 689 kPa
2407 @ 689 kPa
High Pressure Application
Moderate
Moderate
Very Good
Poor
Maintenance
Low
Moderate
Moderate
High
Advantages
• Compact and low weight
• Customizable configuration
• High pressure application
• Enclosed in a cabinet
• Reliable
• Extremely reliable
• Very reliable
• Low noise level (very quiet
and vibration free)
• Best efficiency CFM/HP
• Low wear
• Lower running
temperature
• No oil needed
• Enclosed Unit
• Suitable for high
demand application
• Able to produce high
horsepower with one
compressor unit
• No oil needed
Disadvantages
• Less convenient when
servicing large capacities
• Louder than scroll
• Oil needed to run
• Larger in size
• More vibrations
• High operating cost
due to the need for
water to cool
• High maintenance
• Difficult to install
Manufacturer
Hitachi
Hitachi
* All values are taken on pump at 10 hp except Rotary Screw which is taken at 20 hp
8
Amico Source Corporation
FS Curtis
FS Curtis
Medical Air Systems Glossary and Specifications
Table 3: Medical Air Systems Glossary
Definitions
ACFM
• Actual Cubic Feet per Minute is an expression of actual air volume,
generally corrected for and reference to a particular pressure.
ICFM
• Conditions at the inlet of the compressor prior to any restrictions or
temperature changes. (i.e., inlet filters, inter-coolers, discharge manifolds
etc).
Continuous Duty
• Operational reference to compressors operating 24 hours a day,
continuously.
Continuous Duty Rated
• Air compressors which can operate continuously (24 hours per day) if
necessary but normally only operate on demand.
Desiccant Dryer
• Consists of two towers, whereby the desiccant bed in one tower dries
the air stream while a purge of dry air regenerates the desiccant bed in
the other tower.
Dew Point
• Temperature and pressure at which medical air will condense water
vapor into liquid water within the medical air pipeline system.
Dew Point/CO Monitor
• Monitors dew point and carbon monoxide levels in medical air.
Displacement
• Theoretical physical volume of the air in the compressor chamber based
upon 100% pumping efficiency, with no allowances made for heat,
friction, clearances, or other losses in the compression cycle.
Duplex System
• Systems comprised of two (2) compressors, each rated for 100% Peak
Calculated Load (PCL).
LPM
• Abbreviation for Liters per Minute; a measure of the flow rate of a gas.
NTP
• Normal Temperature and Pressure - generally accepted as 70˚F (20˚C),
14.969 psi/29.92" Hg barometric pressure, and 36% relative humidity.
Oil-Free Compressor
• Compressor with oil within the compressor but absent from the
compression chamber by means of seals and visible vented distance
piece, and a dry compression chamber.
Oil-Less Compressor
• Compressor with no oil contained within the compressor.
Peak Calculated
Load (PCL)
• The maximum estimated demand a medical facility will require of a
medical air system.
• Calculated at SCFM at 100 psig.
SCFM
• Standard Cubic Feet per Minute is an expression of air at NTP.
Simultaneous Demand
• Operating reference to a condition where all compressors (Lead and Lag
compressors) run simultaneously to satisfy demand in excess of lead
compressor(s) capability.
Triplex Systems
• Medical air system with three compressors (3), each sized for 50% PCL.
Quadruplex System
• Medical air system with four compressors (4), each sized for 33% PCL.
www.amico.com
9
SUMMARY OF NFPA 99 SPECIFICATION (AIR COMPRESSOR SYSTEMS)
PART 1 – GENERAL (Medical Air)
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including general and supplementary conditions and Division I
specification section, apply to this section.
SUMMARY EXTENT OF WORK
1. This section pertains to all labor, equipment and services necessary for and complementary to the installation
of piped medical gas and vacuum systems (PMGVS) including: oxygen, medical air, medical vacuum, waste
anesthesia gas disposal (WAGD), nitrogen, instrument air, nitrous oxide, helium, carbon dioxide, argon, dental
air, dental vacuum, laboratory air and mixed gas systems as shown on the drawings and specified herein.
a. Oxygen systems shall be complete to the source valve, ready for connection to the bulk gas supply
system.
b. Medical Vacuum, WAGD and Medical Air systems shall be complete, started, tested and ready for use.
c. Nitrous Oxide, Nitrogen, Carbon Dioxide, Helium, Argon and Mixed Gas Systems shall be complete,
tested and ready for use.
PERFORMANCE REQUIREMENTS
1. All materials used shall be new and of the best grade and quality available and workmanship shall be first class
in every respect. Contractor shall be accountable for compliance with all local, state or federal codes.
2. Provide all elements and accessories required for complete systems per latest edition of NFPA 99.
3. Contractor shall make all necessary connections to owner furnished equipment.
4. Install all piping as shown on drawings, described herein and as described in Section 15050, Basic Materials
and Methods, using methods of fabrication, grading, testing, repairing, cleaning and other procedures.
5. Electrical power wiring for vacuum pump(s), medical air compressor(s), WAGD producer(s), ceiling columns,
alarms, and modular accessories associated with the system(s) shall be part of the electrical contract. Any
equipment supplied by a contractor requiring additional electrical services shall be the responsibility of the
contractor to supply these services.
6. Perform installer pressure testing, cross connection testing and final testing per NFPA 99 most recent edition
and using procedures as specified.
Specifiers; if CONTRACTOR will retain Verifier, use this paragraph:
7. Retain a qualified third party verifier acceptable to the engineer and owner to perform and attest to final
verification of the systems. Make corrections as needed, including additional testing in order to illustrate full
and unqualified certification.
Or, if OWNER will retain Verifier, use this paragraph;
7. Coordinate with owner retained verifier for final verification of the systems. Make corrections as needed,
including additional testing if necessary to illustrate full and unqualified certification.
10
Amico Source Corporation
COORDINATION
1. Medical Gas Contractor shall coordinate with other trades to ensure timely installations and evade conflicts and
interference.
2. Work with metal stud partition installer and/or mason to ensure anchors, sleeves and similar items are provided
in sufficient time to avoid delays; chases and openings are properly sized and prepared.
3. Coordinate with owner to ensure medical gas outlets, whether owner supplied or contractor supplied, in
walls, ceilings and all equipment are provided by the same Medical Gas Equipment Manufacturer (MGEM) are
satisfactory to the owner.
4. Coordinate with bulk cryogenic gas supplier for installation, connection and verification of bulk gas supply
systems.
5. Medical Gas Contractor shall supply and install the master alarm system (including the signal wiring). The
electrical contractor shall provide power wiring to each alarm panel. Medical Gas Contractor is accountable for
proper termination, testing and marking of alarm panels. Termination shall be done by or under the supervision
of the manufacturer of alarm panels.
6. Coordinate with Medical Gas Verifier to deliver a complete, tested medical gas installation ready for owner’s use.
SUBMITTALS
A. Furnish the following as one package:
1. Medical Gas Equipment Manufacturer (MGEM) submittals shall include a minimum of at least one of the
following:
a. Complete specifications for the product intended to be installed, dimensional drawings, and wiring
schematics where appropriate.
b. For other medical gas products include:
• Package drawing indicating package style, dimensions when complete, method of disassembly
and sizes of subsections for rigging and installation.
• Compressor and package capacity expressed in CFM.
• Lubrication method (if any).
• Drive detail including adjustment method.
• Motor including frame type, service factor, horsepower, current draw and RPM.
• Air filters including type and replacement element.
• Pressure regulators including type and manufacturer.
• Dew point monitor including technology employed, calibration interval and annual drift in
degrees.
• Carbon monoxide monitor including technology employed, calibration interval, and annual drift
in ppm.
• Air dryers, type, manufacturer and design dew point at least -40˚F (-40˚C) at 100 psig (689 kPa
• Sound pressure in dB (A) when operated within the capacity as stated in the NFPA 99.
• Heat output (BTU) for the equipment.
• Outlet keying system.
• Alarms networking instructions.
www.amico.com
11
c. Complete installation instructions for the use of the installer.
d. Statement of specific compliance with paragraphs of NFPA 99's most recent edition as relevant to the
equipment and as listed in those sections.
e. Complete maintenance schedules.
f. Warranty statement which must encompass all system components. Warranties covering only specific
components or containing exclusions are not acceptable.
g. Name and contact information for installation assistance, start up, warranty and service.
h. Description of available Preventative Maintenance Programs for Owners review.
i. Information on training programs available to maintenance personnel for owner's review.
B. Medical Gas Verifier Submittals shall include:
1. Name, contact information and reference list. Reference list should include no less than three references on
projects of similar size and complexity.
2. A notarized confirmation from the verifier stating that the verifier undertakes to validate this project and thus
agrees to disqualify themselves from supplying any equipment which will be included in the scope of their
verification. No verifier who supplies equipment shall be permitted to verify that equipment.
3. Statement declaring that the MGEM has no fiduciary interest in the verifier and that the verifier is not an agent
or representative of the MGEM.
4. Statement declaring that the installing contractor has no fiduciary interest in the verifier and that the verifier has
no fiduciary interest in the contractor.
C. Pre-approval
1. Written pre-approval is required for equipment not exactly matching specifications. Submit the information
required under Submittals above, attaching a cover letter stating the exact areas of deviation.
2. A request for pre-approval of equipment must be received by the Engineer no less than three days (72 hours)
prior to bid.
QUALITY ASSURANCE
A. Regulatory Requirements
1. Electrical Control systems and Medical Gas Alarms are to be UL listed as assemblies with label affixed.
2. Medical air, instrument air, medical vacuum and WAGD controls are to be wired in accordance with NEC.
3. All air purification components shall be in compliance with CAGI performance verification as per ISO 8573.1
standards.
4. MGEM will include with submittals an affidavit attesting to compliance with all relevant paragraphs of NFPA 99's
most recent edition.
5. MGEM personnel assembling medical air, instrument air, vacuum and WAGD plant shall meet the latest edition
of NFPA 99 “Qualification of Installers” section and hold medical gas endorsements as under ASSE 6010.
6. The Contractor shall furnish documentation demonstrating that all installed piping materials were purchased
cleaned and complied with the requirements of NFPA 99 5.1.10.1 and 5.1.10.2.
7. The Contractor shall furnish copies of ASSE 6010 qualifications for all workers installing medical gas piping.
B. Installation and Start-up
1. The MGEM will provide authorized representatives to review installation and perform initial start-up of the
system.
12
Amico Source Corporation
C. Warranty
1. Warranty will be expressly complete, include all components of the system and be the responsibility of the
MGEM for record only. Warranties limiting the responsibility of the MGEM for any system component for which
pass through the MGEM to another manufacturer are not acceptable.
2. All source medical gas components shall be warranted by the MGEM of record for a minimum of 30 months
from date of shipment.
3. Warranties shall include on site repairs including travel, labor and parts.
4. Shipping and installation costs after the first 12 months will be borne by the customer.
D. Verification
1. Medical Gas Contractor shall deliver to the owner a complete system certification.
PART 2 - PRODUCTS
QUALIFICATION OF MANUFACTURER(S)
A. The Medical Gas Equipment Manufacturer (MGEM) shall supply all of the medical-gas system(s) and shall
be the manufacturer of the outlets, valves and gauges, valve boxes, alarm panels, manifolds, medical air,
instrument air, vacuum and WAGD sources.
B. The MGEM shall have a product specialist available to periodically check with the contractor during
installation of the pipeline systems equipment. MGEM shall provide service support to the hospital after
turnover. Demonstrate factory trained service technician is available within 250 miles of facility.
C. Approved MGEM: Piping Systems Components and Medical Gas Alarms;
a. Amico Source Corporation.
b. Alternate by _____________ with pre-approval.
D. MGEM shall have a minimum of 5 years of experience manufacturing medical air and vacuum systems.
E. Written pre-approval is required for all equipment from other manufacturers.
MEDICAL AIR COMPRESSOR SYSTEMS
Specifier: Determine the size of medical air plant required and place on the medical gas schedule.
1. Provide a complete medical air source, complying with all relevant requirements of NFPA 99's latest edition
and supplying medical air continuously for the life of the equipment. The unit shall be manufactured by Amico
Source Corporation or pre-approved equal.
2. All components are at least duplexed and valved to allow servicing to any components devoid of interruption
to the air supply of the facility.
3. Furnish a complete plant consisting of compressors, receiver, air treatment system and controls capable of
providing scheduled capacity with one compressor out of service.
4. System is modular or field separable, allowing for ease of shipment and handling on site. System is completely
factory assembled, requiring only interconnection between modules on site. Systems requiring site assembly
other than interconnection are not acceptable (remounting of components removed for shipping is permitted).
5. The compressor modules and motors shall be fully isolated from the main compressor base by means of a
four point, heavy-duty seismic restrained approved isolation system for a minimum of 95% isolation efficiency.
Engineering data shall be provided to support isolation efficiency and equal weight distribution between
supports. Pumps not having this feature shall have an inertia base sized for that system installed at this
contractor’s expense.
www.amico.com
13
6. All air systems will be equipped with a CO monitor. The monitor will have an alarm to: a) alarm if the level of CO
exceeds 10 parts per million by volume (ppmv) and b) alarm and system shutdown.
A. Air Compressors
Specifier: select the paragraph below reflecting the preferred technology:
SCROLL COMPRESSORS
1. The compressors shall be a continuous duty rated scroll type with sealed bearings. The design shall be single
stage, air-cooled, consisting of one fixed and one orbiting scroll sealed with PTFE tip seals between the scroll
halves and rated for 120 PSIG discharge pressure. Orbiting bearings shall be grease filled and with permanently
sealed type requiring no lubrication at any time. Units requiring re-lubrication are not acceptable. Oil-less type
compressor. Noise level shall not exceed 75dB (A) for duplex system, 77dB (A) for triplex system, and 79 dB (A)
for quad system with pumps running at peak demand.
2. On multiple head applications, belt tightening devices are included.
3. Each compressor shall be equipped with an integral air-cooled after cooler designed for a maximum approach
temperature of 15.0°F (-9 °C) complete with electronic drain valve.
4. The discharge of piping of each compressor shall incorporate an integral valve to prevent more than 1/4
revolution of reverse rotation of the scroll at shutdown.
5. System piping shall be brazed except where unions are required for service. Vibration flexes shall be made of
metal and of sufficient length to achieve full isolation.
6. All required Type “K” or “L” copper tubing or brass to interconnect all compressor set components, with unions
for ease of servicing.
7. The shaft driven radial fan with shroud for air cooling.
8. Compressor motors shall be a NEMA rated, open drip proof unit with 1.15 service factory suitable for
_____ Volt, _____ Phases, ____Hz.
9. All moving parts (fans, pulleys and belts) shall be fully protected by an OSHA approved enclosure.
10.Monitor and numerically display the discharge air temperature at each compression chamber outlet port.
11.Initiate an alarm and shut down the compressor if discharge temperature exceeds the manufacturer’s
recommended level.
RECIPROCATING COMPRESSOR
1. The compressors shall be single stage, air cooled, and reciprocating type with corrosion resistant valves with stainless
steel reeds. Crankcase ventilation shall be filtered to prevent dust and insects from entering the crankcase. All
bearings shall be permanently lubricated and sealed; compressors that require bearings to be re-greased are
not acceptable.
2. Each compressor shall be equipped with an integral air-cooled after cooler designed for a maximum approach
temperature of 15.0°F (-9 °C), complete with electronic drain valve.
3. All required type “K” copper tubing or brass pipe to interconnect all compressor set components, with unions
for ease of servicing.
4. Compressor motors shall be a NEMA rated, open drip proof unit with 1.15 service factor suitable for _______ Volt, ____ Phase, ___Hz.
5. All moving parts (fans, pulleys and belts) shall be fully protected by an OSHA approved enclosure.
6. All support structures shall be a minimum of 10 gauge steel.
14
Amico Source Corporation
B. Receiver
The receiver for a medical compressor system is to be made of ferrous and/or non-ferrous materials, be capable of
withstanding a gauge pressure of 200 psi or greater. The receiver shall be sized in accordance with the requirements
of the medical air compressor system and the calculated system design flow, and in compliance with all of the
requirements of Section VIII, unfired pressure vessels of the ASME Boiler and Pressure Vessel Code. The receiver shall
also include:
1. Receiver shall be epoxy-lined.
2. Automatic and manual drain valves.
3. Liquid level gauge.
4. Safety relief valve.
5. Screened automatic solenoid valve.
6. Test valve & muffler.
7. Equipped with a means of bypassing to allow repair without interruption to the system.
C. Piping and Control Components
The piping and control components for each compressor shall include:
1. Intake filters.
a. A non-return valve on the outlet.
b. Flexible inlet and outlet couplings.
c. Inlet and outlet shut-off valves.
d. Pressure relief valve(s).
e. A condensate separator and drain.
f. An unloader valve.
g. A means of removal of the compressor for service or replacement without interruption to the system.
h. The air source for the compressor shall be outdoor air and the intake shall be:
• At least 10 ft. (3 m) away from any door, exhaust, other intake or operable window.
• At least 20 ft. (6.1 m) above grade.
• The intake opening shall be turned downward, screened, and shall be accessible to authorized
personnel for cleaning, inspection and servicing.
• Placed in a location where it will not draw in contamination from exhaust systems (e.g.,
contamination from furnaces, gasoline or diesel engines, vacuum systems or scavenging
systems).
• Consideration shall be given to the potential effect of prevailing winds and possible sources of
airborne contamination and potential obstruction by accumulated snow.
• Piping downstream of the compressor shall be routed in such a way that it is not subjected to a
temperature lower than 40˚F (4˚C).
• Compressor intake piping shall be made of materials approved for vacuum piping compliant
with the latest NFPA 99 edition. In addition, the piping materials are assured to not contain
contaminants in the form of particulate matter, odor, or other gases.
www.amico.com
15
D. Control Panel and Alarm Sensors
The control system is UL labeled. The control system provides automatic lead/lag sequencing and automatic
alternation of pumps based on first-on/first-off principle with provision for simultaneous operation if required.
Automatic activation of reserve unit, if required, will activate an audible alarm as well as a visual alarm on the display
screen.
1. Control panel features:
Only panel components that are commercially available and not of propriety design will be considered.
a. NEMA 12 control panel enclosure.
b. Full voltage motor starter shall be UL 508 E self-protected combination starters with overload
protection and external operators.
c. Door interlock disconnect switch.
d. 90 dB alarm buzzer.
e. Visible indicator of “power on” and “compressor running” for each compressor.
f. Two control transformers with secondary circuit breaker.
g. Hand, Off and Auto selector switches for each compressor.
h. Transducer and RTD based control panel.
i. The RTD will digitally display the running temperature of each discharge port and shall be field
programmable to standard manufacturer’s operating parameter.
j. The calibration of the pressure transducer can be set so a non-standard transducer can be used.
2. Touch screen displays and functions include:
a. UL listed control panel has a NEMA 12 enclosure.
b. Externally operable circuit breakers with door interlocks, control circuit transformers with fused
primary and secondary circuits, H-O-A switches and magnetic starters with three leg thermal overload
protection.
c. Monochrome touch screen monitor with red background during fault displays the hours of operation
of each pump, settings of the system and indicates any faults.
d. Optional 3.5" (8.9 cm), 5.7” (14.48 cm) or 7.5” (19 cm) multicolor touch screen monitor displays the
hours of operation of each pump, settings of the system and indicates any faults.
e. Lighting on the H-O-A switches indicates which pump is running.
f. Audible and visual local alarms are included for all alarm conditions.
g. Manual reset for thermal malfunction shutdown.
h. All control and alarm functions shall remain energized while any compressor or vacuum in the system
remains electrically online.
i. The lag compressor shall be able to start automatically if the lead compressor fails to operate.
j. Digital dew point and CO readout integrated on screen, with alarm contacts.
k. Digital display of the dew point (either in °F or °C) and CO in ppm on the monitor.
l. Alarm contacts are provided for remote annunciation for all alarm conditions.
m.Ethernet connection for remote access to panel interface through the use of a web browser.
(Multicolor touch screen only)
n. Language selection: English, French or Spanish.
o. Available for Duplex systems and above.
16
Amico Source Corporation
3. Options (Multicolor touch screen only):
a. Alarm logging.
b. Alarm emailing.
c. BACNET connection.
d. Extra alarm points monitoring.
e. Internet remote panel control via 3G cellular network (Monthly connection fee applies).
f. Variable Speed Drive (VFD).
4. Panel designed with selectable options to fully match applications.
a. All system settings shall be user adjustable and accessible with the system in operation and the
control panel door closed (password protected).
b. Adjustments can be made to pressure settings to match the customer’s requirements.
c. All alarms to require manual reset.
Specifier: select the paragraph below reflecting the preferred technology:
5. Standard alarms shall open on failure with local audible and visual alarms with dry contacts for the following
conditions:
SCROLL COMPRESSOR
a. Lag pump in use
b. High dew point
c. High CO level
d. High discharge air temperature
e. Main transformer failure
f. Motor overload
RECIPROCATING COMPRESSOR
a. Lag pump in use
b. High dew point
c. High CO level
d. High discharge air temperature
e. Main transformer failure
f. Motor overload
E. Air Treatment Centre
Provide redundant medical air treatment systems including desiccant dryers, filters and purifiers sized for peak
calculated demand. Dew point and carbon monoxide monitoring Medical Air Treatment shall include:
1. Desiccant dryers producing a -40˚F (-40˚C) pressure dew point.
2. Dryer purge flow control through an integral dew point based purge control system. Purge controllers using
desiccant temperature are not acceptable. Drying units shall provide a numerical indication of the outlet dew
point and initiate an alarm when the outlet dew point exceeds the manufacturer’s pre-set limit.
3. Mounted pre-filter with corrosion-resistant housing rated for 0.01 with automatic drain and element change
indicator at the inlet to each dryer.
4. Final line filters rated for 0.1 particulate after filter with element change indicators, duplexed final line
regulators and duplexed safety relief valves shall be factory mounted and piped at the outlet of each dryer.
www.amico.com
17
Quick Guide to Configuration
MODULAR STACKING CONFIGURATION
New “A-Frame” modular stacking configuration allows
two compressors to run simultaneously with a smaller
footprint and compact design. Compressor assemblies
include at least one compressor and one motor.
HORIZONTAL TANK MOUNT
The compressors are mounted on a horizontal tank which
is large enough to accommodate bigger compressors and
accessories than the Modular Stacking Configuration. This
system is factory piped and wired to a single inlet, outlet
and electrical connection.
SKID MOUNT
These systems are mounted on a separate skid. This
configuration is suitable for larger compressors. This type
of air system is also designed for ease of transportation.
18
Amico Source Corporation
Medical Air System Inlet
Below is a summary of the requirements for the medical air system inlet locations.
1. Locate the medical air inlet in an area where there will not be potential hazards such as contamination from
engine exhausts, fuel storage vents, toxins or hazardous contaminants such as ethylene oxide (ETO) gas
exhaust vents, medical vacuum exhaust vents, particulate matter or odor of any type.
2. Locate the medical air inlet outdoors above the roof level a minimum distance of 10 ft. (3 m) from any door,
window, exhaust, other intake or opening in the building and a minimum distance of 20 ft. (6.1 m) above the
ground. Intakes shall be turned down and screened or otherwise be protected against the entry of vermin or
water, with screening that is to be fabricated from or composed of non-corrosive material such as stainless
steel or other suitable material.
3. If a source is available that is equal to or superior to the outside air (e.g., air already filtered for use in the
operating room ventilation systems), it shall be permitted to be used for the medical air compressors. This
alternative source of supply air must be available on a continuous 24 hours a day, 7 days per week basis.
Ventilating systems having fans with motors or drive belts located in the air stream shall not be utilized as a
source of medical air intake.
4. Medical air intakes for separate compressors shall be permitted to be joined together to one common intake,
provided such intake is appropriately sized.
5. Table 4 details the minimum inlet pipe sizing required based on the medical air system horsepower,
configuration and the total pipe length (including elbows) in the medical air intake line.
a. The medical air intakes are joined together to one common intake.
b. All pipe sizes are based on copper pipe Type ”L”.
c. Minimum pipe size must be preserved for the total length of inlet pipe.
d. Use the next larger size pipe in the event the minimum size is not available.
e. When determining the Total Pipe Length (TPL), add all straight lengths of pipe together plus the
number of elbows multiplied by the effective pipe length for that pipe size.
(see Table 4 on next page).
www.amico.com
19
Table 4: Medical Air Compressor System Intake Pipe Sizing
Unit
Flow Basis
SCFM@50 PSI
(LPM@345kPa)
Nominal Pipe Size:
Allowable Equivalent Run (Feet)
1.0"
1.25"
1.5"
2.0"
2.5"
3.0"
4.0"
5.0"
6.0"
Duplex 1 Hp
5.0
(141.6)
68
200
500
2000
Duplex 2 Hp
12.2
(345.5)
22
65
180
650
1800
Duplex 3 Hp
18.4
(521)
30
70
290
850
2200
Duplex 5 Hp
30.2
(855)
12
30
120
360
890
Duplex 7.5 Hp
44.2
(1252)
10
60
180
450
Duplex 10 Hp
Triplex 7.5 Hp
66.3
(1877)
8
35
110
250
1000
Duplex 15 Hp
Triplex 10 Hp
Quad 7.5 Hp
108
(3058)
16
48
120
480
1400
Duplex 20 Hp
Triplex 10 Hp
120.8
(3421)
28
70
280
810
Triplex 15 Hp
132.6
(3755)
25
60
250
750
1800
Triplex 20 Hp
Quad 15 Hp
181.2
(5131)
13
33
130
400
1000
Quad 20 Hp
241.6
(6841)
19
80
240
600
Quad 20 Hp
660
(18689)
20
60
140
Quad 20 Hp
880
(24919)
13
40
95
Fittings Equivalent Lengths
20
Nominal Pipe Size
1.00"
1.25"
1.50"
2.00"
2.50"
3.50"
4.00"
5.00"
6.00"
Elbows
2.5"
3.0"
4.0"
5.5"
7.0"
9.0"
12.5"
16.0"
19.0"
Tee (Branch/Run)
4.5'
5.5'/.5'
7'/.5'
9'/.5'
12/.5'
15'/1'
21'/1'
27'/1.5'
34'/2'
Amico Source Corporation
Table 5: Example 1 - Calculating SCFM
After interviewing the hospital engineer, you find that the facility; which is located 2,000 feet above sea level, has 5
minor operating rooms, 6 ICU ventilators, 18 ICU beds and 12 recovery beds. They also want to have a 25% future
expansion. Calculate the total PCL for the facility's Medical Air system.
Area
Design Flow
(Table 1)
Quantity
Simultaneous
Use (Table 1)
Total
SCFM
Minor Surgery
5 Rooms
x
0.5
x
75
1.9
ICU Ventilators
6 Units
x
3.5
x
100
21
ICU
12 beds
x
2
x
100
24
Recovery Room
12 beds
x
2
x
50
12
Facility PCL Requirements (SCFM)
58.9
Future Expansion (25%)
25%
Facility PCL with Future Expansion (SCFM)
73.6
Altitude Compensation @ 2,000 ft… (From Table 2)
1.03
Total Facility PCL Requirements (SCFM)
75.8
1. Based on the typical ventilator requirements for specific ventilator requirements, check with ventilator
manufacturer.
2. If the number of ventilators in the hospital is unknown, allow one ventilator per bed for 75% of the available
ICU/NICU beds.
3. The ICU area has 18 beds and 6 ventilators. The flow required for the ventilators supersedes that of the ICU
beds, so only 12 of the ICU beds are counted and added to the 6 ventilator requirements when determining
total facility requirements.
NOTE: To convert SCFM to LPM, multiply by 28.3
4. After reviewing Table 5 for a capacity of 75.8 SCFM, the correct sized system would be a Triplex 15 HP system.
www.amico.com
21
Desiccant Air Treatment
Scroll Air Compressor System
Control Panel Specifications
• UL listed control panel has a NEMA 12 enclosure.
• Externally operable circuit breakers with door
interlocks, control circuit transformers with fused
primary and secondary circuits, H-O-A switches and
magnetic starters with three leg overload protection.
• Digital dew point monitor within control panel has alarm
contacts set at +39°F (3.9 °C) and CO monitor at 10 ppm.
• Digital display of the dew point (either in °F or °C) and CO
in ppm on the monitor.
• Dryer purge economizer and optimizer.
• Touch screen monitor displays the hours of operation
of each pump, settings of the system and indicates
any faults.
• Alarm contacts are provided for remote annunciation for
all alarm points.
• Lighting on the H-O-A switches indicates which
pump is running.
• Alarm logging within the control panel PLC
(premium only).
• Audible and visual local alarms are included for all
required alarms and manufacturer recommended
alarms.
• Ethernet connection for remote panel control
(premium only).
• All control and alarm functions shall remain energized
while any compressor in the system remains
electrically online.
22
• The lag compressor shall be able to start automatically if
the lead compressor fails to operate.
Amico Source Corporation
Desiccant Air Treatment
Scroll Air Compressor System
Specifications
• Meets or exceeds the requirements of NFPA 99.
• Package contains: oil-less reciprocating air
compressors, associated equipment, one ASME air
receiver, desiccant air dryer package and one control
panel.
• System intake, discharge and power connection
at the control panel are the only field connections
required.
• All components are completely pre-piped and prewired to single point service connections.
• All interconnecting piping and wiring are
operationally tested prior to shipment.
• Liquid tight conduit, fittings and junction boxes for all
control and power wiring are provided.
• The system shall include individual compressor inline
intake filters, discharge check valves, safety relief
valves, stainless steel intake and discharge flexible
connectors, isolation valves, air cooled aftercoolers for
each compressor, high discharge temperature shut
down switches, pressure control switches as well as
poly tubing for gauge and switches.
Air Compressor
• The compressors shall be belt driven oil-less scroll,
single stage, air-cooled construction with absolutely
no oil needed for operation.
• Each compressor shall be equipped with isolation
valve, check valve, safety valve, electric motor, belts,
belt guard, aftercooler with separator and T.M.P.D.
(Thermal Malfunction Protection Device).
Compressor Motor
• NEMA, open drip proof, 3600 RPM, continuous duty.
Vibration Isolation System
The compressor and motor is fully isolated from the package
base by means of rubber mounts.
Air Receiver
• AMSE construction.
• Inside of the tank shall be double epoxy coated for rust
protection.
• Rated for a maximum 200 psig MWP service.
• Equipped with pressure gauge, safety relief valve, three
way bypass, sight glass and automatic electronic tank
drain with manual override.
Dryer/Filter/Regulator System
• NFPA 99 compliant dual desiccant air dryers with an
integral, demand based, purge saving control system.
• Equipped with two pre-filters, two after-filters, two
pressure regulator valves, one dew point monitor, one CO
monitor and multiple system safety valves.
• Completely pre-piped and pre-wired to single point
service connections.
• There shall be two identical banks of air treatment
equipment, piped in parallel and provided with valves
to bypass either filter set for element replacement,
maintenance and repair work while still treating medical
compressed air through the other set.
• Each bank consists of three stages:
- 1st stage: prime efficiency coalescer with filtered
differential pressure gauge and electric solenoid
auto drain valve.
- 2nd stage: desiccant heatless air dryer equipped
with purge control.
- 3rd stage: prime efficiency particulate afterfilter with
differential pressure gauge and manual drain.
• 208-230V, 460V, 60 Hz, three phase electrical service.
Furnish and install, where shown on the drawing, a prefabricated desiccant air treatment system as manufactured by Amico Source Corporation.
The service of a factory trained representative shall be made available at job site to check installation and start up as well as train operating personnel in
proper operation and maintenance procedures. A start-up form shall be completed at the time of start-up by a factory trained representative.
Amico Source Corporation | 85 Fulton Way, Richmond Hill, ON L4B 2N4, Canada | 71 East Industry Court, Deer Park, NY 11729, USA
Toll Free Tel: 1.877.264.2697 | Tel: 905.764.0800 | Fax: 905.764.0862
www.amico.com
AS-SP-DRY-SCROLL-AIR-CMPRSR 09.22.2014
www.amico.com 23
24
W
Amico Source Corporation
ADDITIONAL MODELS AVAILABLE UPON REQUEST
1/2 NPT DRAIN
SIGHT GLASS
TANK THREE
VALVES BYPASS
MOISTURE SEPARATOR
(2 PLACES)
DUPLEX CONTROL
PANEL
PRO IEC MONITOR
PRE FILTER 0.01 µ
(2 PLACES)
DESICCANT DRYER SYSTEM
AIR COMPRESSOR
HP
(kW)
2
A-SCD-D-080P-TH-N-020 (1.49)
3
A-SCD-D-080P-TH-N-030 (2.24)
5
A-SCD-D-120P-TH-N-050 (3.73)
7.5
A-SCD-D-120P-TH-N-075 (5.59)
10
A-SCD-D-120P-TH-N-100 (7.46)
MODEL
RECEIVER
A
INLET
NPT
L
1.0
1.0
1.0
0.75
0.75
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 120 psig
@ 50 psig @ 120 psig
80
6.2
5.6
6.2
5.6
1635
0.5
(303)
(176)
(159)
(176)
(159)
(742)
80
9.2
8.5
9.2
8.5
1725
0.5
(303)
(261)
(241)
(261)
(241)
(782)
120
15.2
14.1
15.2
14.1
2034
0.5
(454)
(430)
(399)
(430)
(399)
(923)
120
25.2
24.0
25.2
24.0
2074
0.5
(454)
(714)
(680)
(714)
(680)
(941)
120
34.8
32.0
34.8
32.0
2228
0.5
(454)
(985)
(906)
(985)
(906)
(1011)
23.3
(2.15)
23.1
(2.14)
24.1
(2.24)
24.1
(2.24)
25.4
(2.35)
SQ. FT.
REQUIRED
(M²)
52
40
28
17
11
47
36
26
16
10
28
21
16
9
6
24
18
13
8
5
19
14
10
6
4
74
74
74
74
74
5,091
7,636
12,727
19,091
25,455
SOUND
LEVEL
dB (A)
36
(0.91)
35
(0.89)
39
(0.99)
39
(0.99)
38
(0.97)
W
(M)
93
(2.36)
95
(2.41)
89
(2.26)
89
(2.26)
95
(2.41)
L
(M)
73
(1.85)
73
(1.85)
75
(1.91)
75
(1.91)
81
(2.06)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
(4) SLOTS 3/4" x 1 1/16"
FOR ANCHORING
TO FLOOR
INLET FILTER
(2 PLACES)
CO REGULATOR
H
A
INLET
CONNECTION
REGULATOR
(2 PLACES)
B
DISCHARGE
CONNECTION
DEW POINT SENSOR
AFTER FILTER 1 µ
(2 PLACES)
ELECTRIC MOTOR
PUMP ISOLATION VALVE
(2 PLACES)
TANK MOUNTED DUPLEX SCROLL AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 10.0 HP)
ADDITIONAL MODELS AVAILABLE UPON REQUEST
1 NPT DRAIN
AT THE BACK
OF RECEIVER
DUPLEX CONTROL PANEL
PRO IEC MONITOR
RECEIVER
(12) HOLES 5/8" DIA.
FOR ANCHORING
TO FLOOR
SIGHT GLASS
TANK THREE
VALVES BYPASS
REGULATOR
(2 PLACES)
B
DISCHARGE
CONNECTION
HP
(kW)
2
A-SCD-D-200P-SS-N-020 (1.49)
3
A-SCD-D-200P-SS-N-030 (2.24)
5
A-SCD-D-200P-SS-N-050 (3.73)
7.5
A-SCD-D-200P-SS-N-075 (5.59)
10
A-SCD-D-200P-SS-N-100 (7.46)
15
A-SCD-D-200P-SS-N-150 (11.2)
20
A-SCD-D-200P-SS-N-200
(14.9)
MODEL
W
1.5
1.5
1.0
1.0
1.0
0.75
0.75
A
INLET
NPT
H
L
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 120 psig
@ 50 psig @ 120 psig
200
6.2
5.6
6.2
5.6
2367
0.5
(757)
(176)
(159)
(176)
(159)
(1074)
200
9.2
8.5
9.2
8.5
2407
0.5
(757)
(261)
(241)
(261)
(241)
(1092)
200
15.2
14.1
15.2
14.1
2531
0.5
(757)
(430)
(399)
(430)
(399)
(1148)
200
25.2
24.0
25.2
24.0
2621
0.5
(757)
(714)
(680)
(714)
(680)
(1189)
200
34.8
32.0
34.8
32.0
2775
0.5
(757)
(985)
(906)
(985)
(906)
(1259)
200
50.4
48.0
50.4
48.0
3057
0.5
(757)
(1427)
(1359)
(1427)
(1359)
(1387)
200
69.6
64.0
69.6
64.0
3297
1.0
(757)
(1971)
(1812)
(1971)
(1812)
(1496)
CO REGULATOR
A
INLET
CONNECTION
PUMP ISOLATION
VALVE
(2 PLACES)
INLET FILTER
(2 PLACES)
AIR COMPRESSOR
MOISTURE SEPARATOR
(2 PLACES)
DEW POINT SENSOR
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
35.8
(3.33)
SQ. FT.
REQUIRED
(M²)
103
77
52
40
28
17
11
93
70
47
36
26
16
10
56
43
28
21
16
9
6
46
35
24
18
13
8
5
37
28
19
14
10
6
4
74
74
74
74
74
75
79
5,091
7,636
12,727
19,091
25,455
38,182
50,909
SOUND
LEVEL
dB (A)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
W
(M)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
77
(1.96)
L
(M)
www.amico.com
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
AFTER FILTER 1 µ
(2 PLACES)
DESICCANT DRYER SYSTEM
PRE FILTER 0.01 µ
(2 PLACES)
ELECTRIC MOTOR
STACK MOUNTED DUPLEX SCROLL AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 20.0 HP)
25
26
SIGHT GLASS
Amico Source Corporation
ADDITIONAL MODELS AVAILABLE UPON REQUEST
*SYSTEM CONFIGURATION DIFFERS FROM MODEL SHOWN
1 NPT DRAIN
AT THE BACK
OF RECEIVER
PRE FILTER 0.01 µ
(2 PLACES)
AFTER FILTER 1 µ
(2 PLACES)
DESICCANT DRYER
SYSTEM
TRIPLEX CONTROL PANEL
PRO IEC MONITOR
DEW POINT SENSOR
REGULATOR
(2 PLACES)
B
DISCHARGE
CONNECTION
CO REGULATOR
(16) HOLES 5/8" DIA.
FOR ANCHORING
TO FLOOR
HP
(kW)
2
A-SCD-T-200P-SS-N-020* (1.49)
3
A-SCD-T-200P-SS-N-030* (2.24)
5
A-SCD-T-200P-SS-N-050* (3.73)
7.5
A-SCD-T-200P-SS-N-075* (5.59)
10
A-SCD-T-200P-SS-N-100* (7.46)
15
A-SCD-T-200P-SS-N-150 (11.2)
20
A-SCD-T-200P-SS-N-200
(14.9)
MODEL
W
2.0
2.0
1.25
1.25
1.25
1.0
1.0
A
INLET
NPT
H
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 120 psig
@ 50 psig @ 120 psig
200
6.2
5.6
12.4
11.2
2934
0.5
(757)
(176)
(159)
(351)
(317)
(1331)
200
9.2
8.5
18.4
17.0
3028
0.5
(757)
(261)
(241)
(521)
(481)
(1373)
200
15.2
14.1
30.4
28.2
3182
0.5
(757)
(430)
(399)
(861)
(799)
(1443)
200
25.2
24.0
50.4
48.0
3295
0.5
(757)
(714)
(680)
(1427)
(1359)
(1495)
200
34.8
32.0
69.6
64.0
3604
1.0
(757)
(985)
(906)
(1971)
(1812)
(1635)
200
50.4
48.0
100.8
96.0
4106
1.0
(757)
(1427)
(1359)
(2854)
(2718)
(1862)
200
69.6
64.0
139.2
128.0
4532
1.0
(757)
(1971)
(1812)
(3942)
(3625)
(2056)
A
INLET
CONNECTION
PUMP ISOLATION VALVE
(3 PLACES)
RECEIVER
INLET FILTER
(3 PLACES)
AIR COMPRESSOR
55.6
(5.16)
55.6
(5.16)
55.6
(5.16)
55.6
(5.16)
55.6
(5.16)
56.3
(5.24)
56.3
(5.24)
SQ. FT.
REQUIRED
(M²)
L
154
116
79
59
43
26
17
9
139
104
84
65
43
32
71
23
54
14
38
23
15
8
70
52
36
27
19
12
56
42
28
22
15
9
6
77
77
77
77
77
78
82
10,182
15,272
25,454
38,182
50,910
76,364
101,818
SOUND
LEVEL
dB (A)
100
(2.54)
100
(2.54)
100
(2.54)
100
(2.54)
100
(2.54)
133
(3.38)
133
(3.38)
W
(M)
80
(2.03)
80
(2.03)
80
(2.03)
80
(2.03)
80
(2.03)
61
(1.55)
61
(1.55)
L
(M)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
MOISTURE SEPARATOR
(3 PLACES)
TANK THREE
VALVES BYPASS
ELECTRIC MOTOR
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
STACK MOUNTED TRIPLEX SCROLL AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 20.0 HP)
ADDITIONAL MODELS AVAILABLE UPON REQUEST
1 NPT DRAIN
AT THE BACK
OF RECEIVER
PRE FILTER 0.01 µ
(2 PLACES)
AFTER FILTER 1 µ
(2 PLACES)
B
DISCHARGE
CONNECTION
DESICCANT DRYER
SYSTEM
PRO IEC MONITOR
DEW POINT SENSOR
REGULATOR
(2 PLACES)
CO REGULATOR
(16) HOLES 5/8" DIA.
FOR ANCHORING
TO FLOOR
SIGHT GLASS
A-SCD-Q-200P-SS-N-200
A-SCD-Q-200P-SS-N-150
A-SCD-Q-200P-SS-N-100
A-SCD-Q-200P-SS-N-075
A-SCD-Q-200P-SS-N-050
A-SCD-Q-200P-SS-N-030
A-SCD-Q-200P-SS-N-020
MODEL
W
2
(1.49)
3
(2.24)
5
(3.73)
7.5
(5.59)
10
(7.46)
15
(11.2)
20
(14.9)
HP
(kW)
3.0
3.0
1.5
1.5
1.5
1.25
1.25
A
INLET
NPT
H
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 120 psig
@ 50 psig @ 120 psig
200G
6.2
5.6
18.6
16.8
3602
0.5
(757)
(176)
(159)
(527)
(476)
(1634)
200G
9.2
8.5
27.6
25.5
3726
0.5
(757)
(261)
(241)
(782)
(722)
(1690)
200G
15.2
14.1
45.6
42.3
3900
0.5
(757)
(430)
(399)
(1291)
(1198)
(1769)
200G
25.2
24.0
75.6
72.0
4020
1.0
(757)
(714)
(680)
(2141)
(2039)
(1823)
200G
34.8
32.0
104.4
96.0
4548
1.0
(757)
(985)
(906)
(2956)
(2718)
(2063)
200G
50.4
48.0
151.2
144.0
5082
1.0
(757)
(1427)
(1359)
(4282)
(4078)
(2305)
200G
69.6
64.0
208.8
192.0
5916
1.5
(757)
(1971)
(1812)
(5913)
(5437)
(2683)
INLET FILTER
(4 PLACES)
PUMP ISOLATION VALVE
(4 PLACES)
QUADRAPLEX CONTROL
PANEL
RECEIVER
A
INLET
CONNECTION
AIR COMPRESSOR
MOISTURE SEPARATOR
(4 PLACES)
L
60.0
(5.56)
60.0
(5.56)
60.0
(5.56)
62.3
(5.78)
59.7
(5.55)
59.7
(5.55)
59.7
(5.55)
SQ. FT.
REQUIRED
(M²)
205
154
105
79
57
35
22
186
139
95
72
51
31
20
112
86
57
42
31
19
12
93
70
48
36
26
16
10
8
74
56
38
29
20
12
84
80
152,727
79
114,546
79
79
79
79
76,365
57,273
38,181
22,908
15,273
SOUND
LEVEL
dB (A)
108
(2.74)
108
(2.74)
108
(2.74)
108
(2.74)
141
(3.58)
141
(3.58)
141
(3.58)
W
(M)
80
(2.03)
80
(2.03)
80
(2.03)
83
(2.11)
61
(1.55)
61
(1.55)
61
(1.55)
L
(M)
www.amico.com
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
ELECTRIC MOTOR
TANK THREE
VALVES BYPASS
STACK MOUNTED QUADRAPLEX SCROLL AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 20.0 HP)
27
Oil Less
Reciprocating Air Compressor System
Control Panel Specifications
• UL listed control panel has a NEMA 12 enclosure.
• Externally operable circuit breakers with door
interlocks, control circuit transformers with fused
primary and secondary circuits, H-O-A switches and
magnetic starters with three leg overload protection.
• Touch screen monitor displays the hours of operation
of each pump, setting of the system and indicates
any faults.
• The lag compressor shall be able to start automatically if
the lead compressor fails to operate.
• Digital dew point monitor is located within the control
panel with alarm contacts set at +39°F and the CO
monitor at 10 ppm.
• The dew point (either in °F or °C) and CO in ppm will be
digitally displayed on the monitor.
• Lighting on the H-O-A switches indicates which
pump is running.
• An isolation valve for maintenance is included as per
NFPA 99 for each sensor.
• Audible and visual local alarms are included for
compressor temperature malfunction and reserve
compressor in use.
• Alarm contacts are provided for remote annunciation for
all alarm points.
• Manual reset for thermal malfunction shutdown is
available.
• Signal contacts control dryer purge.
28
• All control and alarm functions shall remain energized
while any compressor in the system remains electrically
online.
Amico Source Corporation
• Alarm logging within the control panel PLC
(premium only)
• Ethernet connection for remote panel control
(premium only)
Oil Less
Reciprocating Air Compressor System
Air Compressor
System Specifications
• Meets or exceeds the requirements of NFPA 99.
• Package contains: oil-less reciprocating air
compressors, associated equipment, one ASME air
receiver, desiccant air dryer package and one control
panel.
• System intake, discharge, and power connection
at the control panel are the only field connections
required.
• All components are completely pre-piped and prewired to a single point service connection.
• All interconnecting piping and wiring shall be
completed and operationally tested prior to
shipment.
• Liquid tight conduit, fittings and junction boxes for all
control and power wiring are provided.
• The system shall include individual compressor
inline intake filters, discharge check valves of bronze
construction, safety relief valves, stainless steel intake
and discharge flexible connectors, isolation valves,
air cooled aftercoolers for each compressor, high
discharge temperature shutdown switches, pressure
control switches as well as poly tubing with DISS
fittings for gauges and switches.
Air Compressor
• The compressors shall be belt driven oil-less
reciprocating, single stage, air-cooled construction
with absolutely no oil needed for operation.
• Each compressor will be equipped with isolation
valve, check valve, safety valve, electric motor, belts,
belt guard, aftercooler with separator and T.M.P.D.
(Thermal Malfunction Protection Device).
Compressor Motor
• NEMA, open drip proof, 1800 RPM, continuous duty.
• 208 V or 230-460 V, 60 Hz, 3 phase electrical service.
Vibration Isolation System
The compressor and motor are fully isolated from
the package base by means of spring isolators (5 Hp
and larger).
Air Receiver
• AMSE construction.
• Inside of the tank shall be coated for rust protection.
• Rated for a minimum 200 psig MWP service
• Equipped with pressure gauge, safety relief valve, 3 way
bypass, gauge glass and automatic electronic tank drain
with manual override.
Dryer/Filter/Regulator System
• NFPA 99 compliant dual desiccant air dryers with an
integral, demand based, purge saving control system
• Equipped with dual pre-filters, after-filters, pressure
regulator valves, dew point monitor, CO monitor and
system safety valves.
• It is required to meet and exceed the current code
requirements shall be mounted on the compressor
system base.
• Completely pre-piped and pre-wired to single point
service connections.
• There shall be two identical banks of air treatment
equipment, piped in parallel and provided with valves
to bypass either filter set for element replacement,
maintenance and repair work while still treating medical
compressed air through the other set.
• Each bank consists of three stages:
- 1st stage: prime efficiency coalescer with filtered
differential pressure gauge and electric solenoid
auto drain valve.
- 2nd stage: desiccant heatless air dryer equipped
with purge control.
- 3rd stage: prime efficiency particulate afterfilter with
differential pressure gauge and manual drain.
The service of a factory trained representative shall be made available at job site to check installation and start up as well as train operating personnel in
proper operation and maintenance procedures.
Amico Source Corporation | 85 Fulton Way, Richmond Hill, ON L4B 2N4, Canada | 71 East Industry Court, Deer Park, NY 11729, USA
Toll Free Tel: 1.877.264.2697 | Tel: 905.764.0800 | Fax: 905.764.0862
www.amico.com
AS-SP-RCP-CMPRSR 08.26.2014
www.amico.com 29
30
Amico Source Corporation
ADDITIONAL MODELS AVAILABLE UPON REQUEST
1/2 NPT DRAIN
SIGHT GLASS
MOISTURE SEPARATOR
(2 PLACES)
DUPLEX CONTROL PANEL
PRO IEC MONITOR
AFTER FILTER 1 µ
(2 PLACES)
TANK THREE
VALVES BYPASS
PRE FILTER 0.01 µ
(2 PLACES)
AIR COMPRESSOR
W
1
A-RED-D-080P-TH-N-010 (0.75)
1
A-RED-D-120P-TH-N-010 (0.75)
2
A-RED-D-080P-TH-N-020 (1.49)
2
A-RED-D-120P-TH-N-020 (1.49)
3
A-RED-D-080P-TH-N-030 (2.24)
3
A-RED-D-120P-TH-N-030 (2.24)
5
A-RED-D-080P-TH-N-050 (3.73)
5
A-RED-D-120P-TH-N-050 (3.73)
MODEL
HP
(kW)
RECEIVER
B
DISCHARGE
CONNECTION
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
A
INLET
NPT
DEW POINT SENSOR
CO REGULATOR
REGULATOR
(2 PLACES)
PUMP ISOLATION VALVE
(2 PLACES)
A
INLET
CONNECTION
ELECTRIC MOTOR
L
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET
GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 100 psig
@ 50 psig @ 100 psig
80
4.1
3.3
4.1
3.3
1153
0.5
(303)
(116)
(93)
(116)
(93)
(523)
120
4.1
3.3
4.1
3.3
1337
0.5
(454)
(116)
(93)
(116)
(93)
(606)
7.8
80
6.6
7.8
6.6
1213
0.5
(303)
(221)
(187)
(221)
(187)
(550)
7.8
120
6.6
7.8
6.6
1397
0.5
(454)
(221)
(187)
(221)
(187)
(634)
10.1
80
9.4
10.1
9.4
1314
0.5
(303)
(286)
(266)
(286)
(266)
(596)
120
10.1
9.4
10.1
9.4
1498
0.5
(454)
(286)
(266)
(286)
(266)
(679)
80
18.4
15.4
18.4
15.4
1472
0.5
(303)
(521)
(436)
(521)
(436)
(668)
120
18.4
15.4
18.4
15.4
1656
0.5
(454)
(521)
(436)
(521)
(436)
(751)
H
28.1
(2.61)
30.0
(2.79)
28.1
(2.61)
30.0
(2.79)
28.1
(2.61)
30.0
(2.79)
28.1
(2.61)
27.5
(2.55)
SQ. FT.
REQUIRED
(M²)
28
28
17
17
11
11
6
6
26
26
16
16
10
10
6
6
16
16
9
9
6
6
3
3
4
5
13
13
8
10
10
6
6
4
8
2
5
2
3
3
72
72
73
73
74
74
76
76
2,545
5,091
5,091
7,636
7,636
12,727
12,727
SOUND
LEVEL
dB (A)
2,545
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
45
(1.14)
45
(1.14)
45
(1.14)
45
(1.14)
45
(1.14)
45
(1.14)
45
(1.14)
45
(1.14)
W
(M)
90
(2.29)
96
(2.44)
90
(2.29)
96
(2.44)
90
(2.29)
96
(2.44)
90
(2.29)
88
(2.24)
L
(M)
74
(1.88)
77
(1.96)
74
(1.88)
77
(1.96)
73
(1.85)
77
(1.96)
73
(1.85)
78
(1.98)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
DESICCANT DRYER SYSTEM
INLET FILTER
(2 PLACES)
TANK MOUNTED DUPLEX OIL-LESS RECIPROCATING AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 5.0 HP)
REGULATOR
(2 PLACES)
ADDITIONAL MODELS AVAILABLE UPON REQUEST
1 NPT DRAIN AT
THE BACK OF RECEIVER
DUPLEX CONTROL PANEL
PRO IEC MONITOR
RECEIVER
(12) HOLES 5/8" DIA.
FOR ANCHORING TO FLOOR
SIGHT GLASS
DESICCANT DRYER SYSTEM
MODEL
HP
(kW)
INLET FILTER
(2 PLACES)
2.0
2.0
2.0
2.0
1.25
1.25
1.25
1.25
A
INLET
NPT
H
L
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
34.9
(3.25)
35.8
(3.33)
74.3
(6.90)
SQ. FT.
REQUIRED
(M²)
103
77
52
40
28
17
11
6
93
70
47
36
26
16
10
6
56
43
28
21
16
9
6
3
46
35
24
18
13
37
28
19
14
10
6
4
5
8
2
3
72
73
74
76
78
81
84
84
2,445
5,091
7,636
12,727
19,091
25,455
38,182
50,909
SOUND
LEVEL
dB (A)
L
(M)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
77
(1.96)
87
(2.21)
W
(M)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
67
(1.70)
123
(3.12)
www.amico.com
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
100
(2.54)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
AFTER FILTER 1µ
(2 PLACES)
DEW POINT SENSOR
PRE FILTER 0.01µ
(2 PLACES)
A
INLET
CONNECTION
TANK THREE
VALVES BYPASS
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 100 psig
@ 50 psig @ 100 psig
200G
4.1
3.3
4.1
3.3
1823
0.5
(757)
(116)
(93)
(116)
(93)
(827)
200G
7.8
6.6
7.8
6.6
1883
0.5
(757)
(221)
(221)
(854)
(187)
(187)
200G
10.1
9.4
10.1
9.4
1967
0.5
(757)
(286)
(266)
(286)
(266)
(892)
200G
18.4
18.4
2191
15.4
15.4
0.5
(757)
(521)
(436)
(521)
(436)
(994)
200G
28.1
23.3
28.1
23.3
2401
0.5
(757)
(796)
(660)
(796)
(660)
(1089)
200G
37.1
32.5
37.1
32.5
2699
0.5
(757)
(1050)
(920)
(1050)
(920)
(1224)
200G
54.7
47.7
54.7
47.7
2837
1.0
(757)
(1549)
(1351)
(1549)
(1351)
(1287)
200G
73.1
61.8
73.1
61.8
3425
1.0
(757)
(2070)
(1750)
(2070)
(1750)
(1554)
CO REGULATOR
ELECTRIC MOTOR
AIR COMPRESSOR
MOISTURE SEPARATOR
(2 PLACES)
PUMP ISOLATION VALVE
(2 PLACES)
1
A-RED-D-200P-SS-N-010 (0.75)
2
A-RED-D-200P-SS-N-020 (1.49)
3
A-RED-D-200P-SS-N-030 (2.24)
5
A-RED-D-200P-SS-N-050 (3.73)
7.5
A-RED-D-200P-SS-N-075 (5.59)
10
A-RED-D-200P-SS-N-100 (7.46)
15
A-RED-D-200P-SS-N-150 (11.2)
20
A-RED-D-200P-SS-N-200 (14.9)
W
B
DISCHARGE
CONNECTION
STACK MOUNTED DUPLEX OIL-LESS RECIPROCATING AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 20.0 HP)
31
32
Amico Source Corporation
ADDITIONAL MODELS AVAILABLE UPON REQUEST
*SYSTEM CONFIGURATION DIFFERS FROM MODEL SHOWN
1 NPT DRAIN AT
THE BACK OF RECEIVER
CO REGULATOR
AFTER FILTER 1 µ
(2 PLACES)
DESICCANT DRYER
SYSTEM
RECEIVER
PRE-FILTER 0.01 µ
(2 PLACES)
DEW POINT SENSOR
MODEL
W
HP
(kW)
A
INLET
NPT
1
A-RED-T-200P-SS-N-010 (0.75)
2
A-RED-T-200P-SS-N-020 (1.49)
3
A-RED-T-200P-SS-N-030 (2.24)
5
A-RED-T-200P-SS-N-050 (3.73)
7.5
A-RED-T-200P-SS-N-075 (5.59)
10
A-RED-T-200P-SS-N-100 (7.46)
15
A-RED-T-200P-SS-N-150* (11.2)
20
A-RED-T-200P-SS-N-200* (14.9)
4.0
4.0
3.0
3.0
1.5
1.5
1.5
1.5
ELECTRIC MOTOR
REGULATOR
(2 PLACES)
H
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET
GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 100 psig
@ 50 psig @ 100 psig
200
2150
4.1
3.3
8.2
6.6
0.5
(757)
(116)
(93)
(232)
(187)
(975)
200
7.8
6.6
15.6
13.2
2338
0.5
(757)
(221)
(187)
(442)
(374)
(1061)
200
20.2
18.8
2464
10.1
9.4
0.5
(757)
(572)
(532)
(1118)
(286)
(266)
200
18.4
2741
15.4
36.8
30.8
0.5
(757)
(521)
(1243)
(436)
(1042)
(872)
200
28.1
23.3
56.2
46.6
2993
1.0
(757)
(796)
(660)
(1591)
(1320)
(1358)
200
37.1
32.5
74.2
65.0
3374
1.0
(757)
(1050)
(2101)
(1841)
(1530)
(920)
200
54.7
95.4
3809
47.7
109.4
1.0
(757)
(1549)
(1351)
(3098)
(2701)
(1728)
200
73.1
61.8
146.2
123.6
5153
1.5
(757)
(2070)
(1750)
(4140)
(3500)
(2337)
PRO IEC MONITOR
TRIPLEX CONTROL
PANEL
(16) HOLES 5/8" DIA.
FOR ANCHORING TO FLOOR
AIR COMPRESSOR
PUMP ISOLATION VALVE
(3 PLACES)
B
DISCHARGE
CONNECTION
SIGHT GLASS
TANK THREE
VALVES BYPASS
52.1
(4.85)
52.1
(4.85)
52.1
(4.85)
52.1
(4.85)
53.5
(4.98)
53.5
(4.98)
60.0
(5.58)
105.7
(9.43)
SQ. FT.
REQUIRED
(M²)
L
154
116
79
59
43
26
17
9
139
104
84
65
43
32
54
71
23
14
9
5
38
23
15
9
70
52
36
27
19
12
8
4
56
42
28
22
15
9
6
3
75
76
77
79
81
84
87
87
5,090
15,272
25,454
38,182
50,910
76,364
101,818
SOUND
LEVEL
dB (A)
10,182
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
L
(M)
75
(1.91)
75
(1.91)
75
(1.91)
75
(1.91)
77
(1.96)
77
(1.96)
65
(1.65)
87
(2.21)
W
(M)
100
(2.54)
100
(2.54)
100
(2.54)
100
(2.54)
100
(2.54)
100
(2.54)
133
(3.38)
175
(4.45)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
100
(2.54)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
MOISTURE SEPARATOR
(3 PLACES)
A
INLET
CONNECTION
INLET FILTER
(3 PLACES)
STACK MOUNTED TRIPLEX OIL-LESS RECIPROCATING AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 20.0 HP)
ADDITIONAL MODELS AVAILABLE UPON REQUEST
1 NPT DRAIN
AT THE BACK
OF RECEIVER
PRE FILTER 0.01 µ
(2 PLACES)
AFTER FILTER 1 µ
(2 PLACES)
DESICCANT DRYER
SYSTEM
PRO IEC MONITOR
QUADRAPLEX CONTROL PANEL
RECEIVER
DEW POINT SENSOR
REGULATOR
(2 PLACES)
B
DISCHARGE
CONNECTION
(16) HOLES 5/8" DIA.
FOR ANCHORING
TO FLOOR
CO REGULATOR
SIGHT GLASS
A-RED-Q-200P-SS-N-200
A-RED-Q-200P-SS-N-150
A-RED-Q-200P-SS-N-100
A-RED-Q-200P-SS-N-075
A-RED-Q-200P-SS-N-050
A-RED-Q-200P-SS-N-030
A-RED-Q-200P-SS-N-020
A-RED-Q-200P-SS-N-010
MODEL
W
1
(0.75)
2
(1.49)
3
(2.24)
5
(3.73)
7.5
(5.59)
10
(7.46)
15
(11.2)
20
(14.9)
HP
(kW)
5.0
5.0
3.0
4.0
2.0
2.0
2.0
2.0
A
INLET
NPT
H
L
TANK
NFPA SYSTEM CAPACITIES
COMPRESSOR SCFM
WEIGHT
B
SIZE
WITH ONE COMPRESSOR
(LPM)
IN LBS
OUTLET GALLON
ON STANDBY (LPM)
(KG)
NPT
(LITRE) @ 50 psig @ 100 psig
@ 50 psig @ 100 psig
200G
4.1
3.3
12.3
9.9
2608
0.5
(757)
(116)
(93)
(348)
(280)
(1183)
200G
7.8
6.6
23.4
19.8
2762
0.5
(757)
(221)
(187)
(663)
(561)
(1253)
200G
10.1
9.4
30.3
28.2
2974
0.5
(757)
(286)
(858)
(1349)
(266)
(799)
200G
18.4
55.2
3348
15.4
46.2
1.0
(757)
(521)
(436)
(1563)
(1308)
(1519)
200G
28.1
23.3
84.3
69.9
3900
1.0
(757)
(796)
(660)
(2387)
(1979)
(1769)
37.1
200G
32.5
111.3
97.5
4358
1.0
(757)
(1050)
(920)
(3152)
(2761)
(1977)
200G
54.7
47.7
164.1
143.1
5146
1.5
(757)
(1549)
(1351)
(4647)
(4052)
(2334)
200G
73.1
61.8
219.3
185.4
6288
1.5
(757)
(2070)
(1750)
(6210)
(5250)
(2852)
ELECTRIC MOTOR
AIR COMPRESSOR
INLET FILTER
(4 PLACES)
MOISTURE SEPARATOR
(4 PLACES)
56.3
(5.23)
56.3
(5.23)
56.3
(5.23)
57.8
(5.37)
68.5
(6.37)
68.5
(6.37)
69.0
(6.43)
105.7
(9.83)
SQ. FT.
REQUIRED
(M²)
205
154
105
79
57
35
22
12
186
139
95
72
51
31
20
12
112
86
57
42
31
19
12
7
93
70
48
36
26
16
10
6
74
56
38
29
20
12
8
5
89
89
152,727
86
114,546
83
81
79
78
77
76,365
57,273
38,181
22,908
15,273
7,635
SOUND
LEVEL
dB (A)
108
(2.74)
108
(2.74)
108
(2.74)
108
(2.74)
141
(3.58)
141
(3.58)
142
(3.61)
175
(4.45)
W
(M)
75
(1.91)
75
(1.91)
75
(1.91)
77
(1.96)
70
(1.78)
70
(1.78)
70
(1.78)
87
(2.21)
L
(M)
www.amico.com
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
91
(2.31)
100
(2.54)
H
(M)
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
SYSTEM FLA
(WITH ALL COMPRESSORS
SYSTEM
RUNNING)
BTU/HR
208V 230V 380V 460V 575V
PUMP ISOLATION VALVE
(4 PLACES)
TANK THREE
VALVES BYPASS
A
INLET
CONNECTION
STACK MOUNTED QUADRAPLEX OIL-LESS RECIPROCATING AIR PLANT
WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 20.0 HP)
33
www.amico.com
Amico Source Corporation | www.amico.com
85 Fulton Way, Richmond Hill
Ontario, L4B 2N4, Canada
Toll Free Tel: 1.877.462.6426
Tel: 905.764.0800
Fax: 905.764.0862
Email: [email protected]
AS-DG-NFPA-AIR-COMP 05.29.2015

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement