advertisement
▼
Scroll to page 2
of 36
Source Equipment Air Compressors Source Equipment Table of Contents How To Use This Section...........................................................................................................................................................................................................1 Introduction......................................................................................................................................................................................................................................1 The Four Essentials To Building a Medical Air System............................................................................................................................................1 Steps to Implementing the Medical Air System........................................................................................................................................................2 Discovery....................................................................................................................................................................................................................................... 2-3 Figure 1: Air Intake Location...................................................................................................................................................................................................2 Design..................................................................................................................................................................................................................................................3 Plant Sizing................................................................................................................................................................................................................................... 3-5 Table 1: NFPA Method - Medical Air Flow Calculation Chart......................................................................................................................... 4-5 Altitude Adjustments..................................................................................................................................................................................................................5 Table 2: Altitude Compensation Chart.............................................................................................................................................................................6 Compensating for Future Expansion................................................................................................................................................................................6 Plant Selection................................................................................................................................................................................................................................6 General Layout................................................................................................................................................................................................................................7 Specification.....................................................................................................................................................................................................................................7 Technology Comparison Chart.............................................................................................................................................................................................8 Medical Air Systems Glossary and Specifications......................................................................................................................................................9 Table 3: Medical Air Systems Glossary..............................................................................................................................................................................9 Summary of NFPA 99 Specification (Air Compressor Systems)..............................................................................................................10-17 Quick Guide to Configuration............................................................................................................................................................................................ 18 Medical Air System Inlet......................................................................................................................................................................................................... 19 Table 4: Medical Air Compressor System Intake Pipe Sizing Chart.............................................................................................................. 20 Table 5: Example 1: Calculating SCFM........................................................................................................................................................................... 21 Medical Air Scroll Compressor Specification Sheet.......................................................................................................................................22-23 Duplex Scroll Tank Mounted Horizontal Configuration Air Compressor (2.0 HP - 10.0 HP)......................................................... 24 Duplex Scroll Modular Stacking Configuration Air Compressor (2.0 HP - 20.0 HP)........................................................................... 25 Triplex Scroll Modular Stacking Configuration Air Compressor (2.0 HP - 20.0 HP)............................................................................ 26 Quadruplex Scroll Modular Stacking Configuration Air Compressor (2.0 HP - 20.0 HP)................................................................ 30 Oil-Less Reciprocating Air Compressor Specification Sheet.....................................................................................................................31-33 Duplex Reciprocating Tank Mounted Horizontal Air Compressor (1.0 HP - 5.0 HP)......................................................................... 30 Duplex Reciprocating Modular Stacking Configuration Air Compressor (1.0 HP - 20.0 HP)....................................................... 31 Triplex Reciprocating Modular Stacking Configuration Air Compressor (1.0 HP - 20.0 HP)......................................................... 32 Quadruplex Reciprocating Modular Stacking Configuration Air Compressor (1.0 HP - 20.0 HP)..............................................33 Amico Source Corporation How to Use This Section The following section is structured in a manner such that the medical air system for a project may be established and executed in a sound and simple progression. Examples are given whenever possible. The basic milestones in designing the medical air system are as follows: • Definitions – Definitions are provided in the glossary section which contains terminologies which may be frequently utilized within the Medical Air Systems section. These terms may also be helpful in understanding and specifying the appropriate medical air system. • Design – General outline pertaining to the procedural involvement in designing your Medical Air Systems. • Sizing and Selecting the Medical Air System – Step by step calculation exemplifying how to calculate the Peak Calculated Load (PCL) Requirements for the medical facility. • Installation – Steps to building your medical air systems. Introduction Medical Air Systems The NFPA 99 standards for Medical Air Compressors define an essential foundation of Medical Air Compressors as follows: air should start clean and be kept clean. For that reason, the air inhaled by the patient at the very least should be minimally equal to filtered local outdoor air. All compressors included herein are deemed suitable for medical use under The NFPA standards. For further information on NFPA compliant medical systems, please consult your Local Amico Source Corporation representative. THE FOUR ESSENTIALS TO BUILDING A MEDICAL AIR SYSTEM: 1. The intake air location must never be contaminated by placing the medical air systems in a poorly ventilated area. 2. The medical air must be available at all times, including in the event of a single fault failure. 3. The air must be dry enough to ensure no liquid water can develop under any normal operating conditions (This is not necessarily assured simply by meeting the NFPA mandated dew point). 4. Any contamination whereby the system can produce within itself under any conditions (e.g., particulate) must be removed (e.g., by filtration) before it can reach the patient. NFPA defines various rules for the construction of the air plant and the safety devices required for each machine type. Additionally, good engineering practice defines crucial elements such as after coolers, drains and traps, dryers, vibration isolation, and hundreds of other small but significant elements of good air system design. Amico Source Corporation has pre-engineered all the medical air systems in this section to warrant that they include not only the basic requirements of the principles, but also the many foundations behind good engineering. This section of the design guide also permits the user to make selections of complete medical air packages for reasons specified hereafter. It is impractical to craft a design guide encompassing all the knowledge Amico Source Corporation’s engineers have applied to the design of these systems. Nevertheless, within this design guide, you can easily locate the necessary information to ensure you can apply these systems with confidence and provide for your client a fully satisfactory medical air system. Medical air in smaller systems may be provided by manifolds in lieu of compressor systems. The sizing criteria are the same for either source type. www.amico.com 1 Steps to Implementing the Medical Air System DISCOVERY 1. Should existing equipment be incorporated along with the medical air system, determine the dimensions, type, capacity and current loading of the existing equipment. Ensure the existing equipment is compatible with the current standard. 2. Verify the number and type of all occupancies in the facility which will require medical air outlets. 3. Determine the number of ventilators required to be in service at any one time and define their type and average inlet air requirement. 4. The intake piping for a medical air compressor system should only be connected to the medical air compressor system and not used for any other purpose. It should be made of hard-drawn seamless copper, either ASTM B 819 medical gas tube, ASTM B 88 water tube (Type K, L, or M), or ASTM B 280 ACR tube, which ensures no contaminants in the form of particulate matter, odor or other gases will be added. This piping is to be labeled and equipped with intake filters that are located inside the health care facility, close to the compressor, and are easily accessible for servicing. Examine the location intended for the air intake carefully as NFPA mandates the intake be located at a minimum of 10 ft. (3 m) from any door or operable window; 20 ft. (6.1 m) above grade, and in a location likely to provide uncontaminated air under any conditions of wind or weather. The intake opening shall be turned downward and screened. It shall be accessible to authorized personnel for cleaning, inspection and servicing. If the air intake is near a loading dock or at a location where vehicles may be present, it must be relocated. It is advisable to place the intake at a height above any other intake or vent on the same roof (see Figure 1 below). For further details regarding the rules and regulation in choosing your medical air system location, please refer to the latest edition of the NFPA specification guide. Figure 1: Turned down and screened Air Intake Location 10 ft. (3 m) away from any door or operable window Consider the prevailing winds Away from obvious sources of contaminations (e.g., car exhausts) 20 ft. (6.1 m) above grade 2 Amico Source Corporation 5. Determine a routing for the intake piping and note it on the building drawings. Piping downstream of the compressor shall be routed in a manner such that it is not subjected to temperatures lower than 40 °F (4 °C). 6. Ensure the intended location for the air plant is adequately ventilated or is at minimum air conditioned. The plant will emancipate a considerable amount of heat into the surroundings. Hence, it must be factored in when selecting a compressor site; determining the adequacy of ventilation; or identifying BTU requirements for air conditioning. (BTU data is furnished in the equipment data sheet). 7. Determine the availability of electrical service. 8. If the medical air system is not already piped to the proposed location, determine the routing for the piping and note it on the building drawings. DESIGN 1. Follow directions for laying out piped medical gases. This will supply a count of outlets which is necessary for the next steps. PLANT SIZING 1. There are several available methods for sizing Medical Air. For the purpose of this design guide, only the National Fire Protection Association (NFPA) Method will be discussed. The NFPA Plant Sizing Method 1. Count all outlets within the infrastructure that will utilize the air compressor system (see Table 1 on next page). In situations in which the exact type of room cannot be located within the table, please select the one which most closely approximates the room as indicated in the chart. 2. Once the total amount of outlets are entered, the next step entails multiplying all variables across the table (left to right) to apply the simultaneous usage factor. 3. Obtain an estimate of air requirement by summing the columns (top to bottom). 4. NFPA recommends the inclusion of additional capacity for potential ventilator use. However, this ventilator factor causes significant problems and is usually the cause behind gross over-sizing for medical air plants. Therefore, extreme caution should be taken. www.amico.com 3 Table 1: NFPA Method - Medical Air Flow Calculation Please refer to the table below to obtain an average flow that is required within the facility. This chart is also available at www.amico.com. Medical Air Use Factor (%) Number of Units Beds, Rooms, Outlets SCFM 0.5 100 0 0.00 0.5 100 0 0.00 0.5 0.5 0.5 0.5 75 25 10 10 100 100 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00 0.00 2 25 0 0.00 2 2 1.5 0.5 50 10 75 10 25 100 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00 0.00 0.5 25 0 0.00 0.5 10 0 0.00 10 20 50 50 50 50 25 0 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Free Air Allowance, SCFM Location of Outlets Anesthetizing Locations Special Surgery and Cardiovascular Major Surgery and Orthopedic Minor Surgery Emergency Surgery Radiology Cardiac Catheterization Ventilators Delivery Rooms Acute Care Locations (Non-Anesthetizing) Recovery Room/Surgical (Post-Anesthesia) ICU/CCU Emergency Room Neonatal ICU Dialysis Units Recovery Rooms/OB Ventilators Sub-Acute Patient Care (Non-Anesthetizing) Nursery Patient Rooms (where shown) Exam & Treatment Rooms Pre-Op Holding Respiratory Care Pulmonary Function Lab EEG and EKG Birthing and LDRP Patient Isolation Room 4 Amico Source Corporation Per Unit Per Bed Per Room Per Outlet 3.5 0.5 2 6 1 1.5 1 1 1 1 0.5 Simultaneous Air Medical Air Use Factor (%) Number of Units Beds, Rooms, Outlets SCFM 1.5 10 0 0.00 1.5 10 0 0.00 1.5 1.5 10 10 25 100 10 50 10 0 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Free Air Allowance, SCFM Location of Outlets Other Patient Rooms Anesthesia Workroom Respirator Care Workroom Nursery Workroom Equipment Repair Med. Laboratory 3 Autopsy Sterile Supply Plaster Room Pharmacy Future Expansion Per Unit Per Bed Per Room Per Outlet 1.5 1 1 1 1 Simultaneous PEAK CALCULATED DEMAND IN SCFM BASED ON FREE AIR SCFM @ 50PSI: Air 0.00 Note: 1. The SCFM above is based on a peak OUTLET demand of 50 psi. Air compressors operate at 100 psi. When sizing a compressor, you MUST figure the compressor capacity for operation at 100 psi. 2. You need to consider several environmental factors when sizing the compressors. These include altitude, intake air temperature, and relative humidity. Variance among these factors has considerable effect on compressor selection. 3. Air outlets in labs used for analysis, research or teaching should be supplied by a separate compressed air system, not the medical air system. 4. All sizing methods are only approximations and should be used judiciously. If an existing compressor is being replaced, the operating characteristics of that compressor can be an important gauge of likely future use. For example, if an existing 5 HP compressor provides an ample amount of medical air, but the sizing tables yield much larger requirements; it may be suitable to use a smaller compromise unit as opposed to simply relying on the results from the Amico Sizing Guide. ALTITUDE ADJUSTMENTS If the compressor is to be operated at higher elevations, the peak calculated demand should be multiplied by the corresponding correction factor. Specifically, at altitudes above sea level, all medical air systems have reduced flow. In such cases, the required sizing will need to be adjusted by taking the total PCL (SCFM) and multiplying it by the correction factor (see Table 2 on next page). www.amico.com 5 Table 2: Altitude Compensation Chart Altitude Multiplier Used for Required SCFM (Hg) Sea Level 1.00 1000 ft. (305 m) 1.01 2000 ft. (609 m) 1.03 3000 ft. (900 m) 1.05 4000 ft. (1219 m) 1.06 5000 ft. (1525 m) 1.08 6000 ft. (1828 m) 1.10 7000 ft. (2133 m) 1.12 8000 ft. (2438 m) 1.15 9000 ft. (2743 m) 1.17 10,000 ft. (3048 m) 1.19 COMPENSATING FOR FUTURE EXPANSION The notion of adding capacity now for any future requirements is wise, but extreme caution is also advised. It is common to see very badly oversized air plants which were initially sized to accommodate an expansion that never occurred or that was scaled back and was not compulsory after all. In addition to the waste of investment, it generates problems associated with the operation of the system. The best method in preparing for an anticipated expansion is to opt for a plant which is adequate for the present need in a duplex or triplex system but can also be upsized for future need by simply adding additional compressors as required. When specifying for the unit, require it be purchased in preparation for additional compressor(s) yet not populated with those compressors. A representative specification would read: “provide duplex medical air plant with triplex controls and air treatment subsystem ready for a future third compressor”. Such a system provides an effective method of expanding the system capacity, is more capital-efficient, and yields better operating characteristics and reliability when it comes to air quality control. Nevertheless, it is fundamentally important that the intake, electrical service, and system piping are correctly sized for the entire expected capacity, so these larger values should be used in all calculations. PLANT SELECTION 1. Select a preferred technology (see Page 8). More specific assistance in selecting a technology may be obtained by contacting your Local Amico Source Corporation representative. 2. Choose a Horsepower from the preferred technology with the capacity closest to (but typically greater than) the Peak Calculated Load (PCL). 3. Note that for some technologies, there is more than one plant architecture. Should one or more layout be available for selection, choose the one best suited to the site conditions. If in doubt as to which arrangement is most suitable for a particular situation, contact your Local Amico Source Corporation representative for assistance. 4. Reference the Technology Comparison Chart (page 8) for the particular system selected. This chart entails all of the essential information regarding the system and should be utilized as a quick reference in all of the following steps. 6 Amico Source Corporation GENERAL LAYOUT 1. Place the plant in scale on the plan drawings in the designated location. Ensure that the plant has sufficient space on all sides for maintenance access and proper ventilation. Amico Source Corporation recommends 2 ft. (24") minimum clearance on all sides, 3 ft (36") in front of the control panel, but it is sometimes possible to reduce this clearance with exact knowledge of maintenance access requirements. Consult your Local Amico Source Corporation representative if circumstances allow for less space. 2. Place the equipment in elevation views as appropriate. 3. On the plan, finalize the routing for the intake. 4. Size the intake piping. The sizing process is iterative: a. Start with the total actual length of piping, and make an estimate for the line size (see Table 4). b. By using your estimated size, add equivalent lengths for the fittings employed. c. Check that the size of the intake piping is still suitable at the new equivalent length. Should there be any discrepancies, re-estimate the next larger size and repeat the steps above. The line may also be sized more precisely by conducting an actual calculation. Intake piping must be sized to induce no more than 4 inches water column vacuum at the compressor when all compressors are operating. (Use total capacity for this calculation with all compressors running). For unusual lengths or other circumstances, please contact your local Amico Source Corporation representative for assistance. 5. Finalize the connection to the distribution piping and size the system piping. SPECIFICATION 1. Select the sections appropriate to the technology and system layout desired. 2. Note into the specification any exceptional requirements that are necessary (e.g., soft starters, etc.). 3. Schedule in the drawings the medical air plant selected. Schedule at least: a. The capacity per compressor (per NFPA) and total system capacity. b. Horsepower per compressor. c. Voltage, Hz, and phase desired. www.amico.com 7 TECHNOLOGY COMPARISON CHART Amico Source Corporation offers several technologies for medical air, each of which has its own advantages and drawbacks. This page summarizes these as an aid in the selection of the correct technology for your specific application. Characteristics Format Scroll Dry Reciprocating Lubricated Reciprocating Rotary Screw • Modular Stacking • Modular Stacking • Modular Stacking • Horizontal Tank Mount • Horizontal Tank Mount • Horizontal Tank Mount • Skid Mount • Skid Mount • Skid Mount Lubrication Oil Free Oil Free Lubricated Oil Free dBa* 74 84 82 72 SCFM* 32.0 @ 120 psig 32.5 @ 100 psig 32.8 @ 100 psig 85 @ 100 psig LPM* 651 @ 828 kPa 920 @ 689 kPa 929 @ 689 kPa 2407 @ 689 kPa High Pressure Application Moderate Moderate Very Good Poor Maintenance Low Moderate Moderate High Advantages • Compact and low weight • Customizable configuration • High pressure application • Enclosed in a cabinet • Reliable • Extremely reliable • Very reliable • Low noise level (very quiet and vibration free) • Best efficiency CFM/HP • Low wear • Lower running temperature • No oil needed • Enclosed Unit • Suitable for high demand application • Able to produce high horsepower with one compressor unit • No oil needed Disadvantages • Less convenient when servicing large capacities • Louder than scroll • Oil needed to run • Larger in size • More vibrations • High operating cost due to the need for water to cool • High maintenance • Difficult to install Manufacturer Hitachi Hitachi * All values are taken on pump at 10 hp except Rotary Screw which is taken at 20 hp 8 Amico Source Corporation FS Curtis FS Curtis Medical Air Systems Glossary and Specifications Table 3: Medical Air Systems Glossary Definitions ACFM • Actual Cubic Feet per Minute is an expression of actual air volume, generally corrected for and reference to a particular pressure. ICFM • Conditions at the inlet of the compressor prior to any restrictions or temperature changes. (i.e., inlet filters, inter-coolers, discharge manifolds etc). Continuous Duty • Operational reference to compressors operating 24 hours a day, continuously. Continuous Duty Rated • Air compressors which can operate continuously (24 hours per day) if necessary but normally only operate on demand. Desiccant Dryer • Consists of two towers, whereby the desiccant bed in one tower dries the air stream while a purge of dry air regenerates the desiccant bed in the other tower. Dew Point • Temperature and pressure at which medical air will condense water vapor into liquid water within the medical air pipeline system. Dew Point/CO Monitor • Monitors dew point and carbon monoxide levels in medical air. Displacement • Theoretical physical volume of the air in the compressor chamber based upon 100% pumping efficiency, with no allowances made for heat, friction, clearances, or other losses in the compression cycle. Duplex System • Systems comprised of two (2) compressors, each rated for 100% Peak Calculated Load (PCL). LPM • Abbreviation for Liters per Minute; a measure of the flow rate of a gas. NTP • Normal Temperature and Pressure - generally accepted as 70˚F (20˚C), 14.969 psi/29.92" Hg barometric pressure, and 36% relative humidity. Oil-Free Compressor • Compressor with oil within the compressor but absent from the compression chamber by means of seals and visible vented distance piece, and a dry compression chamber. Oil-Less Compressor • Compressor with no oil contained within the compressor. Peak Calculated Load (PCL) • The maximum estimated demand a medical facility will require of a medical air system. • Calculated at SCFM at 100 psig. SCFM • Standard Cubic Feet per Minute is an expression of air at NTP. Simultaneous Demand • Operating reference to a condition where all compressors (Lead and Lag compressors) run simultaneously to satisfy demand in excess of lead compressor(s) capability. Triplex Systems • Medical air system with three compressors (3), each sized for 50% PCL. Quadruplex System • Medical air system with four compressors (4), each sized for 33% PCL. www.amico.com 9 SUMMARY OF NFPA 99 SPECIFICATION (AIR COMPRESSOR SYSTEMS) PART 1 – GENERAL (Medical Air) RELATED DOCUMENTS Drawings and general provisions of the Contract, including general and supplementary conditions and Division I specification section, apply to this section. SUMMARY EXTENT OF WORK 1. This section pertains to all labor, equipment and services necessary for and complementary to the installation of piped medical gas and vacuum systems (PMGVS) including: oxygen, medical air, medical vacuum, waste anesthesia gas disposal (WAGD), nitrogen, instrument air, nitrous oxide, helium, carbon dioxide, argon, dental air, dental vacuum, laboratory air and mixed gas systems as shown on the drawings and specified herein. a. Oxygen systems shall be complete to the source valve, ready for connection to the bulk gas supply system. b. Medical Vacuum, WAGD and Medical Air systems shall be complete, started, tested and ready for use. c. Nitrous Oxide, Nitrogen, Carbon Dioxide, Helium, Argon and Mixed Gas Systems shall be complete, tested and ready for use. PERFORMANCE REQUIREMENTS 1. All materials used shall be new and of the best grade and quality available and workmanship shall be first class in every respect. Contractor shall be accountable for compliance with all local, state or federal codes. 2. Provide all elements and accessories required for complete systems per latest edition of NFPA 99. 3. Contractor shall make all necessary connections to owner furnished equipment. 4. Install all piping as shown on drawings, described herein and as described in Section 15050, Basic Materials and Methods, using methods of fabrication, grading, testing, repairing, cleaning and other procedures. 5. Electrical power wiring for vacuum pump(s), medical air compressor(s), WAGD producer(s), ceiling columns, alarms, and modular accessories associated with the system(s) shall be part of the electrical contract. Any equipment supplied by a contractor requiring additional electrical services shall be the responsibility of the contractor to supply these services. 6. Perform installer pressure testing, cross connection testing and final testing per NFPA 99 most recent edition and using procedures as specified. Specifiers; if CONTRACTOR will retain Verifier, use this paragraph: 7. Retain a qualified third party verifier acceptable to the engineer and owner to perform and attest to final verification of the systems. Make corrections as needed, including additional testing in order to illustrate full and unqualified certification. Or, if OWNER will retain Verifier, use this paragraph; 7. Coordinate with owner retained verifier for final verification of the systems. Make corrections as needed, including additional testing if necessary to illustrate full and unqualified certification. 10 Amico Source Corporation COORDINATION 1. Medical Gas Contractor shall coordinate with other trades to ensure timely installations and evade conflicts and interference. 2. Work with metal stud partition installer and/or mason to ensure anchors, sleeves and similar items are provided in sufficient time to avoid delays; chases and openings are properly sized and prepared. 3. Coordinate with owner to ensure medical gas outlets, whether owner supplied or contractor supplied, in walls, ceilings and all equipment are provided by the same Medical Gas Equipment Manufacturer (MGEM) are satisfactory to the owner. 4. Coordinate with bulk cryogenic gas supplier for installation, connection and verification of bulk gas supply systems. 5. Medical Gas Contractor shall supply and install the master alarm system (including the signal wiring). The electrical contractor shall provide power wiring to each alarm panel. Medical Gas Contractor is accountable for proper termination, testing and marking of alarm panels. Termination shall be done by or under the supervision of the manufacturer of alarm panels. 6. Coordinate with Medical Gas Verifier to deliver a complete, tested medical gas installation ready for owner’s use. SUBMITTALS A. Furnish the following as one package: 1. Medical Gas Equipment Manufacturer (MGEM) submittals shall include a minimum of at least one of the following: a. Complete specifications for the product intended to be installed, dimensional drawings, and wiring schematics where appropriate. b. For other medical gas products include: • Package drawing indicating package style, dimensions when complete, method of disassembly and sizes of subsections for rigging and installation. • Compressor and package capacity expressed in CFM. • Lubrication method (if any). • Drive detail including adjustment method. • Motor including frame type, service factor, horsepower, current draw and RPM. • Air filters including type and replacement element. • Pressure regulators including type and manufacturer. • Dew point monitor including technology employed, calibration interval and annual drift in degrees. • Carbon monoxide monitor including technology employed, calibration interval, and annual drift in ppm. • Air dryers, type, manufacturer and design dew point at least -40˚F (-40˚C) at 100 psig (689 kPa • Sound pressure in dB (A) when operated within the capacity as stated in the NFPA 99. • Heat output (BTU) for the equipment. • Outlet keying system. • Alarms networking instructions. www.amico.com 11 c. Complete installation instructions for the use of the installer. d. Statement of specific compliance with paragraphs of NFPA 99's most recent edition as relevant to the equipment and as listed in those sections. e. Complete maintenance schedules. f. Warranty statement which must encompass all system components. Warranties covering only specific components or containing exclusions are not acceptable. g. Name and contact information for installation assistance, start up, warranty and service. h. Description of available Preventative Maintenance Programs for Owners review. i. Information on training programs available to maintenance personnel for owner's review. B. Medical Gas Verifier Submittals shall include: 1. Name, contact information and reference list. Reference list should include no less than three references on projects of similar size and complexity. 2. A notarized confirmation from the verifier stating that the verifier undertakes to validate this project and thus agrees to disqualify themselves from supplying any equipment which will be included in the scope of their verification. No verifier who supplies equipment shall be permitted to verify that equipment. 3. Statement declaring that the MGEM has no fiduciary interest in the verifier and that the verifier is not an agent or representative of the MGEM. 4. Statement declaring that the installing contractor has no fiduciary interest in the verifier and that the verifier has no fiduciary interest in the contractor. C. Pre-approval 1. Written pre-approval is required for equipment not exactly matching specifications. Submit the information required under Submittals above, attaching a cover letter stating the exact areas of deviation. 2. A request for pre-approval of equipment must be received by the Engineer no less than three days (72 hours) prior to bid. QUALITY ASSURANCE A. Regulatory Requirements 1. Electrical Control systems and Medical Gas Alarms are to be UL listed as assemblies with label affixed. 2. Medical air, instrument air, medical vacuum and WAGD controls are to be wired in accordance with NEC. 3. All air purification components shall be in compliance with CAGI performance verification as per ISO 8573.1 standards. 4. MGEM will include with submittals an affidavit attesting to compliance with all relevant paragraphs of NFPA 99's most recent edition. 5. MGEM personnel assembling medical air, instrument air, vacuum and WAGD plant shall meet the latest edition of NFPA 99 “Qualification of Installers” section and hold medical gas endorsements as under ASSE 6010. 6. The Contractor shall furnish documentation demonstrating that all installed piping materials were purchased cleaned and complied with the requirements of NFPA 99 5.1.10.1 and 5.1.10.2. 7. The Contractor shall furnish copies of ASSE 6010 qualifications for all workers installing medical gas piping. B. Installation and Start-up 1. The MGEM will provide authorized representatives to review installation and perform initial start-up of the system. 12 Amico Source Corporation C. Warranty 1. Warranty will be expressly complete, include all components of the system and be the responsibility of the MGEM for record only. Warranties limiting the responsibility of the MGEM for any system component for which pass through the MGEM to another manufacturer are not acceptable. 2. All source medical gas components shall be warranted by the MGEM of record for a minimum of 30 months from date of shipment. 3. Warranties shall include on site repairs including travel, labor and parts. 4. Shipping and installation costs after the first 12 months will be borne by the customer. D. Verification 1. Medical Gas Contractor shall deliver to the owner a complete system certification. PART 2 - PRODUCTS QUALIFICATION OF MANUFACTURER(S) A. The Medical Gas Equipment Manufacturer (MGEM) shall supply all of the medical-gas system(s) and shall be the manufacturer of the outlets, valves and gauges, valve boxes, alarm panels, manifolds, medical air, instrument air, vacuum and WAGD sources. B. The MGEM shall have a product specialist available to periodically check with the contractor during installation of the pipeline systems equipment. MGEM shall provide service support to the hospital after turnover. Demonstrate factory trained service technician is available within 250 miles of facility. C. Approved MGEM: Piping Systems Components and Medical Gas Alarms; a. Amico Source Corporation. b. Alternate by _____________ with pre-approval. D. MGEM shall have a minimum of 5 years of experience manufacturing medical air and vacuum systems. E. Written pre-approval is required for all equipment from other manufacturers. MEDICAL AIR COMPRESSOR SYSTEMS Specifier: Determine the size of medical air plant required and place on the medical gas schedule. 1. Provide a complete medical air source, complying with all relevant requirements of NFPA 99's latest edition and supplying medical air continuously for the life of the equipment. The unit shall be manufactured by Amico Source Corporation or pre-approved equal. 2. All components are at least duplexed and valved to allow servicing to any components devoid of interruption to the air supply of the facility. 3. Furnish a complete plant consisting of compressors, receiver, air treatment system and controls capable of providing scheduled capacity with one compressor out of service. 4. System is modular or field separable, allowing for ease of shipment and handling on site. System is completely factory assembled, requiring only interconnection between modules on site. Systems requiring site assembly other than interconnection are not acceptable (remounting of components removed for shipping is permitted). 5. The compressor modules and motors shall be fully isolated from the main compressor base by means of a four point, heavy-duty seismic restrained approved isolation system for a minimum of 95% isolation efficiency. Engineering data shall be provided to support isolation efficiency and equal weight distribution between supports. Pumps not having this feature shall have an inertia base sized for that system installed at this contractor’s expense. www.amico.com 13 6. All air systems will be equipped with a CO monitor. The monitor will have an alarm to: a) alarm if the level of CO exceeds 10 parts per million by volume (ppmv) and b) alarm and system shutdown. A. Air Compressors Specifier: select the paragraph below reflecting the preferred technology: SCROLL COMPRESSORS 1. The compressors shall be a continuous duty rated scroll type with sealed bearings. The design shall be single stage, air-cooled, consisting of one fixed and one orbiting scroll sealed with PTFE tip seals between the scroll halves and rated for 120 PSIG discharge pressure. Orbiting bearings shall be grease filled and with permanently sealed type requiring no lubrication at any time. Units requiring re-lubrication are not acceptable. Oil-less type compressor. Noise level shall not exceed 75dB (A) for duplex system, 77dB (A) for triplex system, and 79 dB (A) for quad system with pumps running at peak demand. 2. On multiple head applications, belt tightening devices are included. 3. Each compressor shall be equipped with an integral air-cooled after cooler designed for a maximum approach temperature of 15.0°F (-9 °C) complete with electronic drain valve. 4. The discharge of piping of each compressor shall incorporate an integral valve to prevent more than 1/4 revolution of reverse rotation of the scroll at shutdown. 5. System piping shall be brazed except where unions are required for service. Vibration flexes shall be made of metal and of sufficient length to achieve full isolation. 6. All required Type “K” or “L” copper tubing or brass to interconnect all compressor set components, with unions for ease of servicing. 7. The shaft driven radial fan with shroud for air cooling. 8. Compressor motors shall be a NEMA rated, open drip proof unit with 1.15 service factory suitable for _____ Volt, _____ Phases, ____Hz. 9. All moving parts (fans, pulleys and belts) shall be fully protected by an OSHA approved enclosure. 10.Monitor and numerically display the discharge air temperature at each compression chamber outlet port. 11.Initiate an alarm and shut down the compressor if discharge temperature exceeds the manufacturer’s recommended level. RECIPROCATING COMPRESSOR 1. The compressors shall be single stage, air cooled, and reciprocating type with corrosion resistant valves with stainless steel reeds. Crankcase ventilation shall be filtered to prevent dust and insects from entering the crankcase. All bearings shall be permanently lubricated and sealed; compressors that require bearings to be re-greased are not acceptable. 2. Each compressor shall be equipped with an integral air-cooled after cooler designed for a maximum approach temperature of 15.0°F (-9 °C), complete with electronic drain valve. 3. All required type “K” copper tubing or brass pipe to interconnect all compressor set components, with unions for ease of servicing. 4. Compressor motors shall be a NEMA rated, open drip proof unit with 1.15 service factor suitable for _______ Volt, ____ Phase, ___Hz. 5. All moving parts (fans, pulleys and belts) shall be fully protected by an OSHA approved enclosure. 6. All support structures shall be a minimum of 10 gauge steel. 14 Amico Source Corporation B. Receiver The receiver for a medical compressor system is to be made of ferrous and/or non-ferrous materials, be capable of withstanding a gauge pressure of 200 psi or greater. The receiver shall be sized in accordance with the requirements of the medical air compressor system and the calculated system design flow, and in compliance with all of the requirements of Section VIII, unfired pressure vessels of the ASME Boiler and Pressure Vessel Code. The receiver shall also include: 1. Receiver shall be epoxy-lined. 2. Automatic and manual drain valves. 3. Liquid level gauge. 4. Safety relief valve. 5. Screened automatic solenoid valve. 6. Test valve & muffler. 7. Equipped with a means of bypassing to allow repair without interruption to the system. C. Piping and Control Components The piping and control components for each compressor shall include: 1. Intake filters. a. A non-return valve on the outlet. b. Flexible inlet and outlet couplings. c. Inlet and outlet shut-off valves. d. Pressure relief valve(s). e. A condensate separator and drain. f. An unloader valve. g. A means of removal of the compressor for service or replacement without interruption to the system. h. The air source for the compressor shall be outdoor air and the intake shall be: • At least 10 ft. (3 m) away from any door, exhaust, other intake or operable window. • At least 20 ft. (6.1 m) above grade. • The intake opening shall be turned downward, screened, and shall be accessible to authorized personnel for cleaning, inspection and servicing. • Placed in a location where it will not draw in contamination from exhaust systems (e.g., contamination from furnaces, gasoline or diesel engines, vacuum systems or scavenging systems). • Consideration shall be given to the potential effect of prevailing winds and possible sources of airborne contamination and potential obstruction by accumulated snow. • Piping downstream of the compressor shall be routed in such a way that it is not subjected to a temperature lower than 40˚F (4˚C). • Compressor intake piping shall be made of materials approved for vacuum piping compliant with the latest NFPA 99 edition. In addition, the piping materials are assured to not contain contaminants in the form of particulate matter, odor, or other gases. www.amico.com 15 D. Control Panel and Alarm Sensors The control system is UL labeled. The control system provides automatic lead/lag sequencing and automatic alternation of pumps based on first-on/first-off principle with provision for simultaneous operation if required. Automatic activation of reserve unit, if required, will activate an audible alarm as well as a visual alarm on the display screen. 1. Control panel features: Only panel components that are commercially available and not of propriety design will be considered. a. NEMA 12 control panel enclosure. b. Full voltage motor starter shall be UL 508 E self-protected combination starters with overload protection and external operators. c. Door interlock disconnect switch. d. 90 dB alarm buzzer. e. Visible indicator of “power on” and “compressor running” for each compressor. f. Two control transformers with secondary circuit breaker. g. Hand, Off and Auto selector switches for each compressor. h. Transducer and RTD based control panel. i. The RTD will digitally display the running temperature of each discharge port and shall be field programmable to standard manufacturer’s operating parameter. j. The calibration of the pressure transducer can be set so a non-standard transducer can be used. 2. Touch screen displays and functions include: a. UL listed control panel has a NEMA 12 enclosure. b. Externally operable circuit breakers with door interlocks, control circuit transformers with fused primary and secondary circuits, H-O-A switches and magnetic starters with three leg thermal overload protection. c. Monochrome touch screen monitor with red background during fault displays the hours of operation of each pump, settings of the system and indicates any faults. d. Optional 3.5" (8.9 cm), 5.7” (14.48 cm) or 7.5” (19 cm) multicolor touch screen monitor displays the hours of operation of each pump, settings of the system and indicates any faults. e. Lighting on the H-O-A switches indicates which pump is running. f. Audible and visual local alarms are included for all alarm conditions. g. Manual reset for thermal malfunction shutdown. h. All control and alarm functions shall remain energized while any compressor or vacuum in the system remains electrically online. i. The lag compressor shall be able to start automatically if the lead compressor fails to operate. j. Digital dew point and CO readout integrated on screen, with alarm contacts. k. Digital display of the dew point (either in °F or °C) and CO in ppm on the monitor. l. Alarm contacts are provided for remote annunciation for all alarm conditions. m.Ethernet connection for remote access to panel interface through the use of a web browser. (Multicolor touch screen only) n. Language selection: English, French or Spanish. o. Available for Duplex systems and above. 16 Amico Source Corporation 3. Options (Multicolor touch screen only): a. Alarm logging. b. Alarm emailing. c. BACNET connection. d. Extra alarm points monitoring. e. Internet remote panel control via 3G cellular network (Monthly connection fee applies). f. Variable Speed Drive (VFD). 4. Panel designed with selectable options to fully match applications. a. All system settings shall be user adjustable and accessible with the system in operation and the control panel door closed (password protected). b. Adjustments can be made to pressure settings to match the customer’s requirements. c. All alarms to require manual reset. Specifier: select the paragraph below reflecting the preferred technology: 5. Standard alarms shall open on failure with local audible and visual alarms with dry contacts for the following conditions: SCROLL COMPRESSOR a. Lag pump in use b. High dew point c. High CO level d. High discharge air temperature e. Main transformer failure f. Motor overload RECIPROCATING COMPRESSOR a. Lag pump in use b. High dew point c. High CO level d. High discharge air temperature e. Main transformer failure f. Motor overload E. Air Treatment Centre Provide redundant medical air treatment systems including desiccant dryers, filters and purifiers sized for peak calculated demand. Dew point and carbon monoxide monitoring Medical Air Treatment shall include: 1. Desiccant dryers producing a -40˚F (-40˚C) pressure dew point. 2. Dryer purge flow control through an integral dew point based purge control system. Purge controllers using desiccant temperature are not acceptable. Drying units shall provide a numerical indication of the outlet dew point and initiate an alarm when the outlet dew point exceeds the manufacturer’s pre-set limit. 3. Mounted pre-filter with corrosion-resistant housing rated for 0.01 with automatic drain and element change indicator at the inlet to each dryer. 4. Final line filters rated for 0.1 particulate after filter with element change indicators, duplexed final line regulators and duplexed safety relief valves shall be factory mounted and piped at the outlet of each dryer. www.amico.com 17 Quick Guide to Configuration MODULAR STACKING CONFIGURATION New “A-Frame” modular stacking configuration allows two compressors to run simultaneously with a smaller footprint and compact design. Compressor assemblies include at least one compressor and one motor. HORIZONTAL TANK MOUNT The compressors are mounted on a horizontal tank which is large enough to accommodate bigger compressors and accessories than the Modular Stacking Configuration. This system is factory piped and wired to a single inlet, outlet and electrical connection. SKID MOUNT These systems are mounted on a separate skid. This configuration is suitable for larger compressors. This type of air system is also designed for ease of transportation. 18 Amico Source Corporation Medical Air System Inlet Below is a summary of the requirements for the medical air system inlet locations. 1. Locate the medical air inlet in an area where there will not be potential hazards such as contamination from engine exhausts, fuel storage vents, toxins or hazardous contaminants such as ethylene oxide (ETO) gas exhaust vents, medical vacuum exhaust vents, particulate matter or odor of any type. 2. Locate the medical air inlet outdoors above the roof level a minimum distance of 10 ft. (3 m) from any door, window, exhaust, other intake or opening in the building and a minimum distance of 20 ft. (6.1 m) above the ground. Intakes shall be turned down and screened or otherwise be protected against the entry of vermin or water, with screening that is to be fabricated from or composed of non-corrosive material such as stainless steel or other suitable material. 3. If a source is available that is equal to or superior to the outside air (e.g., air already filtered for use in the operating room ventilation systems), it shall be permitted to be used for the medical air compressors. This alternative source of supply air must be available on a continuous 24 hours a day, 7 days per week basis. Ventilating systems having fans with motors or drive belts located in the air stream shall not be utilized as a source of medical air intake. 4. Medical air intakes for separate compressors shall be permitted to be joined together to one common intake, provided such intake is appropriately sized. 5. Table 4 details the minimum inlet pipe sizing required based on the medical air system horsepower, configuration and the total pipe length (including elbows) in the medical air intake line. a. The medical air intakes are joined together to one common intake. b. All pipe sizes are based on copper pipe Type ”L”. c. Minimum pipe size must be preserved for the total length of inlet pipe. d. Use the next larger size pipe in the event the minimum size is not available. e. When determining the Total Pipe Length (TPL), add all straight lengths of pipe together plus the number of elbows multiplied by the effective pipe length for that pipe size. (see Table 4 on next page). www.amico.com 19 Table 4: Medical Air Compressor System Intake Pipe Sizing Unit Flow Basis SCFM@50 PSI (LPM@345kPa) Nominal Pipe Size: Allowable Equivalent Run (Feet) 1.0" 1.25" 1.5" 2.0" 2.5" 3.0" 4.0" 5.0" 6.0" Duplex 1 Hp 5.0 (141.6) 68 200 500 2000 Duplex 2 Hp 12.2 (345.5) 22 65 180 650 1800 Duplex 3 Hp 18.4 (521) 30 70 290 850 2200 Duplex 5 Hp 30.2 (855) 12 30 120 360 890 Duplex 7.5 Hp 44.2 (1252) 10 60 180 450 Duplex 10 Hp Triplex 7.5 Hp 66.3 (1877) 8 35 110 250 1000 Duplex 15 Hp Triplex 10 Hp Quad 7.5 Hp 108 (3058) 16 48 120 480 1400 Duplex 20 Hp Triplex 10 Hp 120.8 (3421) 28 70 280 810 Triplex 15 Hp 132.6 (3755) 25 60 250 750 1800 Triplex 20 Hp Quad 15 Hp 181.2 (5131) 13 33 130 400 1000 Quad 20 Hp 241.6 (6841) 19 80 240 600 Quad 20 Hp 660 (18689) 20 60 140 Quad 20 Hp 880 (24919) 13 40 95 Fittings Equivalent Lengths 20 Nominal Pipe Size 1.00" 1.25" 1.50" 2.00" 2.50" 3.50" 4.00" 5.00" 6.00" Elbows 2.5" 3.0" 4.0" 5.5" 7.0" 9.0" 12.5" 16.0" 19.0" Tee (Branch/Run) 4.5' 5.5'/.5' 7'/.5' 9'/.5' 12/.5' 15'/1' 21'/1' 27'/1.5' 34'/2' Amico Source Corporation Table 5: Example 1 - Calculating SCFM After interviewing the hospital engineer, you find that the facility; which is located 2,000 feet above sea level, has 5 minor operating rooms, 6 ICU ventilators, 18 ICU beds and 12 recovery beds. They also want to have a 25% future expansion. Calculate the total PCL for the facility's Medical Air system. Area Design Flow (Table 1) Quantity Simultaneous Use (Table 1) Total SCFM Minor Surgery 5 Rooms x 0.5 x 75 1.9 ICU Ventilators 6 Units x 3.5 x 100 21 ICU 12 beds x 2 x 100 24 Recovery Room 12 beds x 2 x 50 12 Facility PCL Requirements (SCFM) 58.9 Future Expansion (25%) 25% Facility PCL with Future Expansion (SCFM) 73.6 Altitude Compensation @ 2,000 ft… (From Table 2) 1.03 Total Facility PCL Requirements (SCFM) 75.8 1. Based on the typical ventilator requirements for specific ventilator requirements, check with ventilator manufacturer. 2. If the number of ventilators in the hospital is unknown, allow one ventilator per bed for 75% of the available ICU/NICU beds. 3. The ICU area has 18 beds and 6 ventilators. The flow required for the ventilators supersedes that of the ICU beds, so only 12 of the ICU beds are counted and added to the 6 ventilator requirements when determining total facility requirements. NOTE: To convert SCFM to LPM, multiply by 28.3 4. After reviewing Table 5 for a capacity of 75.8 SCFM, the correct sized system would be a Triplex 15 HP system. www.amico.com 21 Desiccant Air Treatment Scroll Air Compressor System Control Panel Specifications • UL listed control panel has a NEMA 12 enclosure. • Externally operable circuit breakers with door interlocks, control circuit transformers with fused primary and secondary circuits, H-O-A switches and magnetic starters with three leg overload protection. • Digital dew point monitor within control panel has alarm contacts set at +39°F (3.9 °C) and CO monitor at 10 ppm. • Digital display of the dew point (either in °F or °C) and CO in ppm on the monitor. • Dryer purge economizer and optimizer. • Touch screen monitor displays the hours of operation of each pump, settings of the system and indicates any faults. • Alarm contacts are provided for remote annunciation for all alarm points. • Lighting on the H-O-A switches indicates which pump is running. • Alarm logging within the control panel PLC (premium only). • Audible and visual local alarms are included for all required alarms and manufacturer recommended alarms. • Ethernet connection for remote panel control (premium only). • All control and alarm functions shall remain energized while any compressor in the system remains electrically online. 22 • The lag compressor shall be able to start automatically if the lead compressor fails to operate. Amico Source Corporation Desiccant Air Treatment Scroll Air Compressor System Specifications • Meets or exceeds the requirements of NFPA 99. • Package contains: oil-less reciprocating air compressors, associated equipment, one ASME air receiver, desiccant air dryer package and one control panel. • System intake, discharge and power connection at the control panel are the only field connections required. • All components are completely pre-piped and prewired to single point service connections. • All interconnecting piping and wiring are operationally tested prior to shipment. • Liquid tight conduit, fittings and junction boxes for all control and power wiring are provided. • The system shall include individual compressor inline intake filters, discharge check valves, safety relief valves, stainless steel intake and discharge flexible connectors, isolation valves, air cooled aftercoolers for each compressor, high discharge temperature shut down switches, pressure control switches as well as poly tubing for gauge and switches. Air Compressor • The compressors shall be belt driven oil-less scroll, single stage, air-cooled construction with absolutely no oil needed for operation. • Each compressor shall be equipped with isolation valve, check valve, safety valve, electric motor, belts, belt guard, aftercooler with separator and T.M.P.D. (Thermal Malfunction Protection Device). Compressor Motor • NEMA, open drip proof, 3600 RPM, continuous duty. Vibration Isolation System The compressor and motor is fully isolated from the package base by means of rubber mounts. Air Receiver • AMSE construction. • Inside of the tank shall be double epoxy coated for rust protection. • Rated for a maximum 200 psig MWP service. • Equipped with pressure gauge, safety relief valve, three way bypass, sight glass and automatic electronic tank drain with manual override. Dryer/Filter/Regulator System • NFPA 99 compliant dual desiccant air dryers with an integral, demand based, purge saving control system. • Equipped with two pre-filters, two after-filters, two pressure regulator valves, one dew point monitor, one CO monitor and multiple system safety valves. • Completely pre-piped and pre-wired to single point service connections. • There shall be two identical banks of air treatment equipment, piped in parallel and provided with valves to bypass either filter set for element replacement, maintenance and repair work while still treating medical compressed air through the other set. • Each bank consists of three stages: - 1st stage: prime efficiency coalescer with filtered differential pressure gauge and electric solenoid auto drain valve. - 2nd stage: desiccant heatless air dryer equipped with purge control. - 3rd stage: prime efficiency particulate afterfilter with differential pressure gauge and manual drain. • 208-230V, 460V, 60 Hz, three phase electrical service. Furnish and install, where shown on the drawing, a prefabricated desiccant air treatment system as manufactured by Amico Source Corporation. The service of a factory trained representative shall be made available at job site to check installation and start up as well as train operating personnel in proper operation and maintenance procedures. A start-up form shall be completed at the time of start-up by a factory trained representative. Amico Source Corporation | 85 Fulton Way, Richmond Hill, ON L4B 2N4, Canada | 71 East Industry Court, Deer Park, NY 11729, USA Toll Free Tel: 1.877.264.2697 | Tel: 905.764.0800 | Fax: 905.764.0862 www.amico.com AS-SP-DRY-SCROLL-AIR-CMPRSR 09.22.2014 www.amico.com 23 24 W Amico Source Corporation ADDITIONAL MODELS AVAILABLE UPON REQUEST 1/2 NPT DRAIN SIGHT GLASS TANK THREE VALVES BYPASS MOISTURE SEPARATOR (2 PLACES) DUPLEX CONTROL PANEL PRO IEC MONITOR PRE FILTER 0.01 µ (2 PLACES) DESICCANT DRYER SYSTEM AIR COMPRESSOR HP (kW) 2 A-SCD-D-080P-TH-N-020 (1.49) 3 A-SCD-D-080P-TH-N-030 (2.24) 5 A-SCD-D-120P-TH-N-050 (3.73) 7.5 A-SCD-D-120P-TH-N-075 (5.59) 10 A-SCD-D-120P-TH-N-100 (7.46) MODEL RECEIVER A INLET NPT L 1.0 1.0 1.0 0.75 0.75 TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 120 psig @ 50 psig @ 120 psig 80 6.2 5.6 6.2 5.6 1635 0.5 (303) (176) (159) (176) (159) (742) 80 9.2 8.5 9.2 8.5 1725 0.5 (303) (261) (241) (261) (241) (782) 120 15.2 14.1 15.2 14.1 2034 0.5 (454) (430) (399) (430) (399) (923) 120 25.2 24.0 25.2 24.0 2074 0.5 (454) (714) (680) (714) (680) (941) 120 34.8 32.0 34.8 32.0 2228 0.5 (454) (985) (906) (985) (906) (1011) 23.3 (2.15) 23.1 (2.14) 24.1 (2.24) 24.1 (2.24) 25.4 (2.35) SQ. FT. REQUIRED (M²) 52 40 28 17 11 47 36 26 16 10 28 21 16 9 6 24 18 13 8 5 19 14 10 6 4 74 74 74 74 74 5,091 7,636 12,727 19,091 25,455 SOUND LEVEL dB (A) 36 (0.91) 35 (0.89) 39 (0.99) 39 (0.99) 38 (0.97) W (M) 93 (2.36) 95 (2.41) 89 (2.26) 89 (2.26) 95 (2.41) L (M) 73 (1.85) 73 (1.85) 75 (1.91) 75 (1.91) 81 (2.06) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V (4) SLOTS 3/4" x 1 1/16" FOR ANCHORING TO FLOOR INLET FILTER (2 PLACES) CO REGULATOR H A INLET CONNECTION REGULATOR (2 PLACES) B DISCHARGE CONNECTION DEW POINT SENSOR AFTER FILTER 1 µ (2 PLACES) ELECTRIC MOTOR PUMP ISOLATION VALVE (2 PLACES) TANK MOUNTED DUPLEX SCROLL AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 10.0 HP) ADDITIONAL MODELS AVAILABLE UPON REQUEST 1 NPT DRAIN AT THE BACK OF RECEIVER DUPLEX CONTROL PANEL PRO IEC MONITOR RECEIVER (12) HOLES 5/8" DIA. FOR ANCHORING TO FLOOR SIGHT GLASS TANK THREE VALVES BYPASS REGULATOR (2 PLACES) B DISCHARGE CONNECTION HP (kW) 2 A-SCD-D-200P-SS-N-020 (1.49) 3 A-SCD-D-200P-SS-N-030 (2.24) 5 A-SCD-D-200P-SS-N-050 (3.73) 7.5 A-SCD-D-200P-SS-N-075 (5.59) 10 A-SCD-D-200P-SS-N-100 (7.46) 15 A-SCD-D-200P-SS-N-150 (11.2) 20 A-SCD-D-200P-SS-N-200 (14.9) MODEL W 1.5 1.5 1.0 1.0 1.0 0.75 0.75 A INLET NPT H L TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 120 psig @ 50 psig @ 120 psig 200 6.2 5.6 6.2 5.6 2367 0.5 (757) (176) (159) (176) (159) (1074) 200 9.2 8.5 9.2 8.5 2407 0.5 (757) (261) (241) (261) (241) (1092) 200 15.2 14.1 15.2 14.1 2531 0.5 (757) (430) (399) (430) (399) (1148) 200 25.2 24.0 25.2 24.0 2621 0.5 (757) (714) (680) (714) (680) (1189) 200 34.8 32.0 34.8 32.0 2775 0.5 (757) (985) (906) (985) (906) (1259) 200 50.4 48.0 50.4 48.0 3057 0.5 (757) (1427) (1359) (1427) (1359) (1387) 200 69.6 64.0 69.6 64.0 3297 1.0 (757) (1971) (1812) (1971) (1812) (1496) CO REGULATOR A INLET CONNECTION PUMP ISOLATION VALVE (2 PLACES) INLET FILTER (2 PLACES) AIR COMPRESSOR MOISTURE SEPARATOR (2 PLACES) DEW POINT SENSOR 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 35.8 (3.33) SQ. FT. REQUIRED (M²) 103 77 52 40 28 17 11 93 70 47 36 26 16 10 56 43 28 21 16 9 6 46 35 24 18 13 8 5 37 28 19 14 10 6 4 74 74 74 74 74 75 79 5,091 7,636 12,727 19,091 25,455 38,182 50,909 SOUND LEVEL dB (A) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) W (M) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 77 (1.96) L (M) www.amico.com 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V AFTER FILTER 1 µ (2 PLACES) DESICCANT DRYER SYSTEM PRE FILTER 0.01 µ (2 PLACES) ELECTRIC MOTOR STACK MOUNTED DUPLEX SCROLL AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 20.0 HP) 25 26 SIGHT GLASS Amico Source Corporation ADDITIONAL MODELS AVAILABLE UPON REQUEST *SYSTEM CONFIGURATION DIFFERS FROM MODEL SHOWN 1 NPT DRAIN AT THE BACK OF RECEIVER PRE FILTER 0.01 µ (2 PLACES) AFTER FILTER 1 µ (2 PLACES) DESICCANT DRYER SYSTEM TRIPLEX CONTROL PANEL PRO IEC MONITOR DEW POINT SENSOR REGULATOR (2 PLACES) B DISCHARGE CONNECTION CO REGULATOR (16) HOLES 5/8" DIA. FOR ANCHORING TO FLOOR HP (kW) 2 A-SCD-T-200P-SS-N-020* (1.49) 3 A-SCD-T-200P-SS-N-030* (2.24) 5 A-SCD-T-200P-SS-N-050* (3.73) 7.5 A-SCD-T-200P-SS-N-075* (5.59) 10 A-SCD-T-200P-SS-N-100* (7.46) 15 A-SCD-T-200P-SS-N-150 (11.2) 20 A-SCD-T-200P-SS-N-200 (14.9) MODEL W 2.0 2.0 1.25 1.25 1.25 1.0 1.0 A INLET NPT H TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 120 psig @ 50 psig @ 120 psig 200 6.2 5.6 12.4 11.2 2934 0.5 (757) (176) (159) (351) (317) (1331) 200 9.2 8.5 18.4 17.0 3028 0.5 (757) (261) (241) (521) (481) (1373) 200 15.2 14.1 30.4 28.2 3182 0.5 (757) (430) (399) (861) (799) (1443) 200 25.2 24.0 50.4 48.0 3295 0.5 (757) (714) (680) (1427) (1359) (1495) 200 34.8 32.0 69.6 64.0 3604 1.0 (757) (985) (906) (1971) (1812) (1635) 200 50.4 48.0 100.8 96.0 4106 1.0 (757) (1427) (1359) (2854) (2718) (1862) 200 69.6 64.0 139.2 128.0 4532 1.0 (757) (1971) (1812) (3942) (3625) (2056) A INLET CONNECTION PUMP ISOLATION VALVE (3 PLACES) RECEIVER INLET FILTER (3 PLACES) AIR COMPRESSOR 55.6 (5.16) 55.6 (5.16) 55.6 (5.16) 55.6 (5.16) 55.6 (5.16) 56.3 (5.24) 56.3 (5.24) SQ. FT. REQUIRED (M²) L 154 116 79 59 43 26 17 9 139 104 84 65 43 32 71 23 54 14 38 23 15 8 70 52 36 27 19 12 56 42 28 22 15 9 6 77 77 77 77 77 78 82 10,182 15,272 25,454 38,182 50,910 76,364 101,818 SOUND LEVEL dB (A) 100 (2.54) 100 (2.54) 100 (2.54) 100 (2.54) 100 (2.54) 133 (3.38) 133 (3.38) W (M) 80 (2.03) 80 (2.03) 80 (2.03) 80 (2.03) 80 (2.03) 61 (1.55) 61 (1.55) L (M) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE MOISTURE SEPARATOR (3 PLACES) TANK THREE VALVES BYPASS ELECTRIC MOTOR SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V STACK MOUNTED TRIPLEX SCROLL AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 20.0 HP) ADDITIONAL MODELS AVAILABLE UPON REQUEST 1 NPT DRAIN AT THE BACK OF RECEIVER PRE FILTER 0.01 µ (2 PLACES) AFTER FILTER 1 µ (2 PLACES) B DISCHARGE CONNECTION DESICCANT DRYER SYSTEM PRO IEC MONITOR DEW POINT SENSOR REGULATOR (2 PLACES) CO REGULATOR (16) HOLES 5/8" DIA. FOR ANCHORING TO FLOOR SIGHT GLASS A-SCD-Q-200P-SS-N-200 A-SCD-Q-200P-SS-N-150 A-SCD-Q-200P-SS-N-100 A-SCD-Q-200P-SS-N-075 A-SCD-Q-200P-SS-N-050 A-SCD-Q-200P-SS-N-030 A-SCD-Q-200P-SS-N-020 MODEL W 2 (1.49) 3 (2.24) 5 (3.73) 7.5 (5.59) 10 (7.46) 15 (11.2) 20 (14.9) HP (kW) 3.0 3.0 1.5 1.5 1.5 1.25 1.25 A INLET NPT H TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 120 psig @ 50 psig @ 120 psig 200G 6.2 5.6 18.6 16.8 3602 0.5 (757) (176) (159) (527) (476) (1634) 200G 9.2 8.5 27.6 25.5 3726 0.5 (757) (261) (241) (782) (722) (1690) 200G 15.2 14.1 45.6 42.3 3900 0.5 (757) (430) (399) (1291) (1198) (1769) 200G 25.2 24.0 75.6 72.0 4020 1.0 (757) (714) (680) (2141) (2039) (1823) 200G 34.8 32.0 104.4 96.0 4548 1.0 (757) (985) (906) (2956) (2718) (2063) 200G 50.4 48.0 151.2 144.0 5082 1.0 (757) (1427) (1359) (4282) (4078) (2305) 200G 69.6 64.0 208.8 192.0 5916 1.5 (757) (1971) (1812) (5913) (5437) (2683) INLET FILTER (4 PLACES) PUMP ISOLATION VALVE (4 PLACES) QUADRAPLEX CONTROL PANEL RECEIVER A INLET CONNECTION AIR COMPRESSOR MOISTURE SEPARATOR (4 PLACES) L 60.0 (5.56) 60.0 (5.56) 60.0 (5.56) 62.3 (5.78) 59.7 (5.55) 59.7 (5.55) 59.7 (5.55) SQ. FT. REQUIRED (M²) 205 154 105 79 57 35 22 186 139 95 72 51 31 20 112 86 57 42 31 19 12 93 70 48 36 26 16 10 8 74 56 38 29 20 12 84 80 152,727 79 114,546 79 79 79 79 76,365 57,273 38,181 22,908 15,273 SOUND LEVEL dB (A) 108 (2.74) 108 (2.74) 108 (2.74) 108 (2.74) 141 (3.58) 141 (3.58) 141 (3.58) W (M) 80 (2.03) 80 (2.03) 80 (2.03) 83 (2.11) 61 (1.55) 61 (1.55) 61 (1.55) L (M) www.amico.com 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V ELECTRIC MOTOR TANK THREE VALVES BYPASS STACK MOUNTED QUADRAPLEX SCROLL AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (2.0 HP - 20.0 HP) 27 Oil Less Reciprocating Air Compressor System Control Panel Specifications • UL listed control panel has a NEMA 12 enclosure. • Externally operable circuit breakers with door interlocks, control circuit transformers with fused primary and secondary circuits, H-O-A switches and magnetic starters with three leg overload protection. • Touch screen monitor displays the hours of operation of each pump, setting of the system and indicates any faults. • The lag compressor shall be able to start automatically if the lead compressor fails to operate. • Digital dew point monitor is located within the control panel with alarm contacts set at +39°F and the CO monitor at 10 ppm. • The dew point (either in °F or °C) and CO in ppm will be digitally displayed on the monitor. • Lighting on the H-O-A switches indicates which pump is running. • An isolation valve for maintenance is included as per NFPA 99 for each sensor. • Audible and visual local alarms are included for compressor temperature malfunction and reserve compressor in use. • Alarm contacts are provided for remote annunciation for all alarm points. • Manual reset for thermal malfunction shutdown is available. • Signal contacts control dryer purge. 28 • All control and alarm functions shall remain energized while any compressor in the system remains electrically online. Amico Source Corporation • Alarm logging within the control panel PLC (premium only) • Ethernet connection for remote panel control (premium only) Oil Less Reciprocating Air Compressor System Air Compressor System Specifications • Meets or exceeds the requirements of NFPA 99. • Package contains: oil-less reciprocating air compressors, associated equipment, one ASME air receiver, desiccant air dryer package and one control panel. • System intake, discharge, and power connection at the control panel are the only field connections required. • All components are completely pre-piped and prewired to a single point service connection. • All interconnecting piping and wiring shall be completed and operationally tested prior to shipment. • Liquid tight conduit, fittings and junction boxes for all control and power wiring are provided. • The system shall include individual compressor inline intake filters, discharge check valves of bronze construction, safety relief valves, stainless steel intake and discharge flexible connectors, isolation valves, air cooled aftercoolers for each compressor, high discharge temperature shutdown switches, pressure control switches as well as poly tubing with DISS fittings for gauges and switches. Air Compressor • The compressors shall be belt driven oil-less reciprocating, single stage, air-cooled construction with absolutely no oil needed for operation. • Each compressor will be equipped with isolation valve, check valve, safety valve, electric motor, belts, belt guard, aftercooler with separator and T.M.P.D. (Thermal Malfunction Protection Device). Compressor Motor • NEMA, open drip proof, 1800 RPM, continuous duty. • 208 V or 230-460 V, 60 Hz, 3 phase electrical service. Vibration Isolation System The compressor and motor are fully isolated from the package base by means of spring isolators (5 Hp and larger). Air Receiver • AMSE construction. • Inside of the tank shall be coated for rust protection. • Rated for a minimum 200 psig MWP service • Equipped with pressure gauge, safety relief valve, 3 way bypass, gauge glass and automatic electronic tank drain with manual override. Dryer/Filter/Regulator System • NFPA 99 compliant dual desiccant air dryers with an integral, demand based, purge saving control system • Equipped with dual pre-filters, after-filters, pressure regulator valves, dew point monitor, CO monitor and system safety valves. • It is required to meet and exceed the current code requirements shall be mounted on the compressor system base. • Completely pre-piped and pre-wired to single point service connections. • There shall be two identical banks of air treatment equipment, piped in parallel and provided with valves to bypass either filter set for element replacement, maintenance and repair work while still treating medical compressed air through the other set. • Each bank consists of three stages: - 1st stage: prime efficiency coalescer with filtered differential pressure gauge and electric solenoid auto drain valve. - 2nd stage: desiccant heatless air dryer equipped with purge control. - 3rd stage: prime efficiency particulate afterfilter with differential pressure gauge and manual drain. The service of a factory trained representative shall be made available at job site to check installation and start up as well as train operating personnel in proper operation and maintenance procedures. Amico Source Corporation | 85 Fulton Way, Richmond Hill, ON L4B 2N4, Canada | 71 East Industry Court, Deer Park, NY 11729, USA Toll Free Tel: 1.877.264.2697 | Tel: 905.764.0800 | Fax: 905.764.0862 www.amico.com AS-SP-RCP-CMPRSR 08.26.2014 www.amico.com 29 30 Amico Source Corporation ADDITIONAL MODELS AVAILABLE UPON REQUEST 1/2 NPT DRAIN SIGHT GLASS MOISTURE SEPARATOR (2 PLACES) DUPLEX CONTROL PANEL PRO IEC MONITOR AFTER FILTER 1 µ (2 PLACES) TANK THREE VALVES BYPASS PRE FILTER 0.01 µ (2 PLACES) AIR COMPRESSOR W 1 A-RED-D-080P-TH-N-010 (0.75) 1 A-RED-D-120P-TH-N-010 (0.75) 2 A-RED-D-080P-TH-N-020 (1.49) 2 A-RED-D-120P-TH-N-020 (1.49) 3 A-RED-D-080P-TH-N-030 (2.24) 3 A-RED-D-120P-TH-N-030 (2.24) 5 A-RED-D-080P-TH-N-050 (3.73) 5 A-RED-D-120P-TH-N-050 (3.73) MODEL HP (kW) RECEIVER B DISCHARGE CONNECTION 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 A INLET NPT DEW POINT SENSOR CO REGULATOR REGULATOR (2 PLACES) PUMP ISOLATION VALVE (2 PLACES) A INLET CONNECTION ELECTRIC MOTOR L TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 100 psig @ 50 psig @ 100 psig 80 4.1 3.3 4.1 3.3 1153 0.5 (303) (116) (93) (116) (93) (523) 120 4.1 3.3 4.1 3.3 1337 0.5 (454) (116) (93) (116) (93) (606) 7.8 80 6.6 7.8 6.6 1213 0.5 (303) (221) (187) (221) (187) (550) 7.8 120 6.6 7.8 6.6 1397 0.5 (454) (221) (187) (221) (187) (634) 10.1 80 9.4 10.1 9.4 1314 0.5 (303) (286) (266) (286) (266) (596) 120 10.1 9.4 10.1 9.4 1498 0.5 (454) (286) (266) (286) (266) (679) 80 18.4 15.4 18.4 15.4 1472 0.5 (303) (521) (436) (521) (436) (668) 120 18.4 15.4 18.4 15.4 1656 0.5 (454) (521) (436) (521) (436) (751) H 28.1 (2.61) 30.0 (2.79) 28.1 (2.61) 30.0 (2.79) 28.1 (2.61) 30.0 (2.79) 28.1 (2.61) 27.5 (2.55) SQ. FT. REQUIRED (M²) 28 28 17 17 11 11 6 6 26 26 16 16 10 10 6 6 16 16 9 9 6 6 3 3 4 5 13 13 8 10 10 6 6 4 8 2 5 2 3 3 72 72 73 73 74 74 76 76 2,545 5,091 5,091 7,636 7,636 12,727 12,727 SOUND LEVEL dB (A) 2,545 SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V 45 (1.14) 45 (1.14) 45 (1.14) 45 (1.14) 45 (1.14) 45 (1.14) 45 (1.14) 45 (1.14) W (M) 90 (2.29) 96 (2.44) 90 (2.29) 96 (2.44) 90 (2.29) 96 (2.44) 90 (2.29) 88 (2.24) L (M) 74 (1.88) 77 (1.96) 74 (1.88) 77 (1.96) 73 (1.85) 77 (1.96) 73 (1.85) 78 (1.98) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE DESICCANT DRYER SYSTEM INLET FILTER (2 PLACES) TANK MOUNTED DUPLEX OIL-LESS RECIPROCATING AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 5.0 HP) REGULATOR (2 PLACES) ADDITIONAL MODELS AVAILABLE UPON REQUEST 1 NPT DRAIN AT THE BACK OF RECEIVER DUPLEX CONTROL PANEL PRO IEC MONITOR RECEIVER (12) HOLES 5/8" DIA. FOR ANCHORING TO FLOOR SIGHT GLASS DESICCANT DRYER SYSTEM MODEL HP (kW) INLET FILTER (2 PLACES) 2.0 2.0 2.0 2.0 1.25 1.25 1.25 1.25 A INLET NPT H L 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 34.9 (3.25) 35.8 (3.33) 74.3 (6.90) SQ. FT. REQUIRED (M²) 103 77 52 40 28 17 11 6 93 70 47 36 26 16 10 6 56 43 28 21 16 9 6 3 46 35 24 18 13 37 28 19 14 10 6 4 5 8 2 3 72 73 74 76 78 81 84 84 2,445 5,091 7,636 12,727 19,091 25,455 38,182 50,909 SOUND LEVEL dB (A) L (M) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 77 (1.96) 87 (2.21) W (M) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 67 (1.70) 123 (3.12) www.amico.com 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 100 (2.54) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V AFTER FILTER 1µ (2 PLACES) DEW POINT SENSOR PRE FILTER 0.01µ (2 PLACES) A INLET CONNECTION TANK THREE VALVES BYPASS TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 100 psig @ 50 psig @ 100 psig 200G 4.1 3.3 4.1 3.3 1823 0.5 (757) (116) (93) (116) (93) (827) 200G 7.8 6.6 7.8 6.6 1883 0.5 (757) (221) (221) (854) (187) (187) 200G 10.1 9.4 10.1 9.4 1967 0.5 (757) (286) (266) (286) (266) (892) 200G 18.4 18.4 2191 15.4 15.4 0.5 (757) (521) (436) (521) (436) (994) 200G 28.1 23.3 28.1 23.3 2401 0.5 (757) (796) (660) (796) (660) (1089) 200G 37.1 32.5 37.1 32.5 2699 0.5 (757) (1050) (920) (1050) (920) (1224) 200G 54.7 47.7 54.7 47.7 2837 1.0 (757) (1549) (1351) (1549) (1351) (1287) 200G 73.1 61.8 73.1 61.8 3425 1.0 (757) (2070) (1750) (2070) (1750) (1554) CO REGULATOR ELECTRIC MOTOR AIR COMPRESSOR MOISTURE SEPARATOR (2 PLACES) PUMP ISOLATION VALVE (2 PLACES) 1 A-RED-D-200P-SS-N-010 (0.75) 2 A-RED-D-200P-SS-N-020 (1.49) 3 A-RED-D-200P-SS-N-030 (2.24) 5 A-RED-D-200P-SS-N-050 (3.73) 7.5 A-RED-D-200P-SS-N-075 (5.59) 10 A-RED-D-200P-SS-N-100 (7.46) 15 A-RED-D-200P-SS-N-150 (11.2) 20 A-RED-D-200P-SS-N-200 (14.9) W B DISCHARGE CONNECTION STACK MOUNTED DUPLEX OIL-LESS RECIPROCATING AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 20.0 HP) 31 32 Amico Source Corporation ADDITIONAL MODELS AVAILABLE UPON REQUEST *SYSTEM CONFIGURATION DIFFERS FROM MODEL SHOWN 1 NPT DRAIN AT THE BACK OF RECEIVER CO REGULATOR AFTER FILTER 1 µ (2 PLACES) DESICCANT DRYER SYSTEM RECEIVER PRE-FILTER 0.01 µ (2 PLACES) DEW POINT SENSOR MODEL W HP (kW) A INLET NPT 1 A-RED-T-200P-SS-N-010 (0.75) 2 A-RED-T-200P-SS-N-020 (1.49) 3 A-RED-T-200P-SS-N-030 (2.24) 5 A-RED-T-200P-SS-N-050 (3.73) 7.5 A-RED-T-200P-SS-N-075 (5.59) 10 A-RED-T-200P-SS-N-100 (7.46) 15 A-RED-T-200P-SS-N-150* (11.2) 20 A-RED-T-200P-SS-N-200* (14.9) 4.0 4.0 3.0 3.0 1.5 1.5 1.5 1.5 ELECTRIC MOTOR REGULATOR (2 PLACES) H TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 100 psig @ 50 psig @ 100 psig 200 2150 4.1 3.3 8.2 6.6 0.5 (757) (116) (93) (232) (187) (975) 200 7.8 6.6 15.6 13.2 2338 0.5 (757) (221) (187) (442) (374) (1061) 200 20.2 18.8 2464 10.1 9.4 0.5 (757) (572) (532) (1118) (286) (266) 200 18.4 2741 15.4 36.8 30.8 0.5 (757) (521) (1243) (436) (1042) (872) 200 28.1 23.3 56.2 46.6 2993 1.0 (757) (796) (660) (1591) (1320) (1358) 200 37.1 32.5 74.2 65.0 3374 1.0 (757) (1050) (2101) (1841) (1530) (920) 200 54.7 95.4 3809 47.7 109.4 1.0 (757) (1549) (1351) (3098) (2701) (1728) 200 73.1 61.8 146.2 123.6 5153 1.5 (757) (2070) (1750) (4140) (3500) (2337) PRO IEC MONITOR TRIPLEX CONTROL PANEL (16) HOLES 5/8" DIA. FOR ANCHORING TO FLOOR AIR COMPRESSOR PUMP ISOLATION VALVE (3 PLACES) B DISCHARGE CONNECTION SIGHT GLASS TANK THREE VALVES BYPASS 52.1 (4.85) 52.1 (4.85) 52.1 (4.85) 52.1 (4.85) 53.5 (4.98) 53.5 (4.98) 60.0 (5.58) 105.7 (9.43) SQ. FT. REQUIRED (M²) L 154 116 79 59 43 26 17 9 139 104 84 65 43 32 54 71 23 14 9 5 38 23 15 9 70 52 36 27 19 12 8 4 56 42 28 22 15 9 6 3 75 76 77 79 81 84 87 87 5,090 15,272 25,454 38,182 50,910 76,364 101,818 SOUND LEVEL dB (A) 10,182 SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V L (M) 75 (1.91) 75 (1.91) 75 (1.91) 75 (1.91) 77 (1.96) 77 (1.96) 65 (1.65) 87 (2.21) W (M) 100 (2.54) 100 (2.54) 100 (2.54) 100 (2.54) 100 (2.54) 100 (2.54) 133 (3.38) 175 (4.45) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 100 (2.54) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE MOISTURE SEPARATOR (3 PLACES) A INLET CONNECTION INLET FILTER (3 PLACES) STACK MOUNTED TRIPLEX OIL-LESS RECIPROCATING AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 20.0 HP) ADDITIONAL MODELS AVAILABLE UPON REQUEST 1 NPT DRAIN AT THE BACK OF RECEIVER PRE FILTER 0.01 µ (2 PLACES) AFTER FILTER 1 µ (2 PLACES) DESICCANT DRYER SYSTEM PRO IEC MONITOR QUADRAPLEX CONTROL PANEL RECEIVER DEW POINT SENSOR REGULATOR (2 PLACES) B DISCHARGE CONNECTION (16) HOLES 5/8" DIA. FOR ANCHORING TO FLOOR CO REGULATOR SIGHT GLASS A-RED-Q-200P-SS-N-200 A-RED-Q-200P-SS-N-150 A-RED-Q-200P-SS-N-100 A-RED-Q-200P-SS-N-075 A-RED-Q-200P-SS-N-050 A-RED-Q-200P-SS-N-030 A-RED-Q-200P-SS-N-020 A-RED-Q-200P-SS-N-010 MODEL W 1 (0.75) 2 (1.49) 3 (2.24) 5 (3.73) 7.5 (5.59) 10 (7.46) 15 (11.2) 20 (14.9) HP (kW) 5.0 5.0 3.0 4.0 2.0 2.0 2.0 2.0 A INLET NPT H L TANK NFPA SYSTEM CAPACITIES COMPRESSOR SCFM WEIGHT B SIZE WITH ONE COMPRESSOR (LPM) IN LBS OUTLET GALLON ON STANDBY (LPM) (KG) NPT (LITRE) @ 50 psig @ 100 psig @ 50 psig @ 100 psig 200G 4.1 3.3 12.3 9.9 2608 0.5 (757) (116) (93) (348) (280) (1183) 200G 7.8 6.6 23.4 19.8 2762 0.5 (757) (221) (187) (663) (561) (1253) 200G 10.1 9.4 30.3 28.2 2974 0.5 (757) (286) (858) (1349) (266) (799) 200G 18.4 55.2 3348 15.4 46.2 1.0 (757) (521) (436) (1563) (1308) (1519) 200G 28.1 23.3 84.3 69.9 3900 1.0 (757) (796) (660) (2387) (1979) (1769) 37.1 200G 32.5 111.3 97.5 4358 1.0 (757) (1050) (920) (3152) (2761) (1977) 200G 54.7 47.7 164.1 143.1 5146 1.5 (757) (1549) (1351) (4647) (4052) (2334) 200G 73.1 61.8 219.3 185.4 6288 1.5 (757) (2070) (1750) (6210) (5250) (2852) ELECTRIC MOTOR AIR COMPRESSOR INLET FILTER (4 PLACES) MOISTURE SEPARATOR (4 PLACES) 56.3 (5.23) 56.3 (5.23) 56.3 (5.23) 57.8 (5.37) 68.5 (6.37) 68.5 (6.37) 69.0 (6.43) 105.7 (9.83) SQ. FT. REQUIRED (M²) 205 154 105 79 57 35 22 12 186 139 95 72 51 31 20 12 112 86 57 42 31 19 12 7 93 70 48 36 26 16 10 6 74 56 38 29 20 12 8 5 89 89 152,727 86 114,546 83 81 79 78 77 76,365 57,273 38,181 22,908 15,273 7,635 SOUND LEVEL dB (A) 108 (2.74) 108 (2.74) 108 (2.74) 108 (2.74) 141 (3.58) 141 (3.58) 142 (3.61) 175 (4.45) W (M) 75 (1.91) 75 (1.91) 75 (1.91) 77 (1.96) 70 (1.78) 70 (1.78) 70 (1.78) 87 (2.21) L (M) www.amico.com 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 91 (2.31) 100 (2.54) H (M) DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE SYSTEM FLA (WITH ALL COMPRESSORS SYSTEM RUNNING) BTU/HR 208V 230V 380V 460V 575V PUMP ISOLATION VALVE (4 PLACES) TANK THREE VALVES BYPASS A INLET CONNECTION STACK MOUNTED QUADRAPLEX OIL-LESS RECIPROCATING AIR PLANT WITH DESICCANT AIR TREATMENT SYSTEM (1.0 HP - 20.0 HP) 33 www.amico.com Amico Source Corporation | www.amico.com 85 Fulton Way, Richmond Hill Ontario, L4B 2N4, Canada Toll Free Tel: 1.877.462.6426 Tel: 905.764.0800 Fax: 905.764.0862 Email: [email protected] AS-DG-NFPA-AIR-COMP 05.29.2015
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement