Parker L5351 DeviceNet Communication Interface Technical Manual
Reklama
Reklama
Technical Manual
HG353798 Issue 3
Copyright Parker SSD Drives, Inc 2008
All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed by a Parker SSD Drives company without written permission from Parker SSD Drives Inc.
Although every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to make amendments or correct omissions. Parker SSD Drives cannot accept responsibility for damage, injury, or expenses resulting therefrom.
Please read this information BEFORE installing the equipment.
Intended Users
This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation.
The information given is intended to highlight safety issues, and to enable the user to obtain maximum benefit from the equipment.
Application Area
The equipment described is intended for industrial motor speed control.
Personnel
Qualified personnel should carry out installation, operation and maintenance of the equipment. A qualified person is someone who is technically competent and familiar with all safety information and established safety practices; with the installation process, operation and maintenance of this equipment; and with all the hazards involved.
REFER TO YOUR MAIN PRODUCT MANUAL FOR SPECIFIC
SAFETY INFORMATION ABOUT THE DEVICE YOU ARE
CONTROLLING
!
Introduction
Installing the Cards
Connecting the L5351
Configuring Link
Configuring DeviceNet
Troubleshooting
Sample Configurations
Technical Specifications
4
6
1
3
10
23
27
32
!"#$ "$% & " %
This manual covers the hardware and software installation for configuring DeviceNet to interface with the Link system. The reader should have the software, RSLogix, RSNetWorx, RSLinx, and
Configuration Editor/DSD installed on the computer and a working knowledge of the software prior to configuring the DeviceNet interface.
Contact the supplier of the above software if any difficulties are encountered installing the software installing.
$ ' $# $#(& $#
The following hardware is required for DeviceNet set-up and operation:
• L5351 Link card installed in a L5392 or L5300.
• DeviceNet scanner card installed in a PLC.
• a 24VDC Supply (> 1 amp rating)
• A PC running Windows 95/98 or NT
)%*"' $# $#(& $#
Rockwell / Allen Bradley
• RS Logix, RS NetWorx, and RS Linx
SSD Drives
• Configuration Editor >5.10 or DSD
• The L5351 DeviceNet LinkCard and the EDS file (electronic data sheet) are shipped from Eurotherm Drives.
% * +&$ " % ) )
Configuring the L5351 consists of two basic parts. The first is configurating the host Link module with the definition of “register” function blocks and their and interconnection with other Link function blocks on the Link fiber-optic ring. The L5351 appears as an I/O device to the rest of the Link system. The second resides in the
DeviceNet master (such as a PLC DeviceNet Scanner module) and defines the number and type of parameters to transfer and how to map them to PLC memory.
Each node on the DeviceNet network can transfer a maximum of 127 words. The L5351 is a node on the network. A maximum of three
L5351’s can be inserted into each L5300 or L5392. Each card is considered a separate node. As a result, the Link system, using three
L5351 LinkCards in one L5300 or L5392, can transfer a maximum of
381 words. The PLC will be the limiting factor. Allen Bradley’s PLC 5, using DeviceNet scanner card equipped with two ports, has the maximum capability of processing 357 words. Allen Bradley’s SLC
500, using DeviceNet scanner card equipped with one port, has the maximum capability of processing 150 words.
!"#$ )" + " # $ )
This chapter covers the installation of the L5351 LinkCard in a L5392
LinkStation. Prior to handling the cards, discharge any static electricity from your person by using a proper ESD protection kit. If you do not have an ESD kit, touch a panel ground to discharge any static electricity from your person. Take necessary precautions to disconnect and lockout any power sources that might be affected while doing this procedure.
Step 1. Remove the cover .
Disconnect power and remove all connections from the L5392 or
L5300.
Squeeze the tabs on each side of the L5392 or L5300. This allows you to remove the plastic cover.
Step 2. Inserting the L5351 Link Card .
Insert the L5351 Link Card(s) into the desired slot(s). Slot number 1 is usually reserved for the L5311 RTNX card. If you do not have a L5311 card in your system the L5351 can be inserted into any one of the four available slots. Make note of the slot the L5351 card location.
Step 3. Replace the cover .
Replace the cover by inserting the plastic cover until the tabs on the side snap into place.
!"#$ % # " + " #
This chapter describes the electrical connections to the L5351
LinkCard.
The communications cable should be two-pair, shielded, twisted pairs.
The end to end length and the wire gauge will determine the baud rate used around the network.
The following table shows the maximum cable length using the two different types of cable and the different baud rates.
Data Rates 125 KBPS 250 KBPS 500 KBPS
500 m
(1,640 ft)
250 m
(820 ft)
100 m
(328 ft)
Thick Trunk Length
Signal and drain
(18 gauge)
Power (15 gauge)
Thin Trunk Length
Signal (24 gauge)
Power and drain
(22 gauge)
Maximum Drop
Length
100 m
(328 ft)
6m
(20 ft)
100 m
(328 ft)
6m
(20 ft)
100 m
(328 ft)
6m
(20 ft)
Cumulative Drop
Length
156 m
(512 ft)
78 m
(256 ft)
This table lists of the connections to the L5351 LinkCard.
Pin Number Wire Color
1 Black
Abbreviation
V-
39 m
(128 ft)
Description
Power Return
2
3
Blue
Clear
Data Low
Shield
Data Line
Shield
4 White Data High Data Line
5 Red V+ Positive Voltage
The supply voltage to V- and V+ can be supplied locally using an external power supply or over the network using the PLC power supply.
The voltage range is 11 vdc to 24 vdc. The voltage is generally supplied by the PLC. The LinkCard L5351 current consumption at 24
VDC is 30 mA.
!"#$ % * +&$ + ,
This chapter covers making a simple Link DeviceNet configuration.
The example uses a L5392 with the L5351 was installed in slot J2.
The L5311 RTN card is inserted in slot J1.
Step 1. Select BLOCK :: LINKCARD :: L5351
This inserts the DeviceNet handler block in the configuration. This block is used to identify the MAC id number, Baud rate, L5351 site location and the order of the DeviceNet registers.
Step 2. Insert the types of registers you require for your system.
The example configuration has one of each type (Bit, Unsigned and
Signed registers).
Step 3. Double-click on the DeviceNet handler block to enter the L5351 site address, Mac Id number, baud rate, and the
DeviceNet registers.
Note. The order of the registers in the DeviceNet handler must match the scanner card in the PLC. If the order is does not match communications between the L5351 card and the PLC will fail.
Step 4. Double-click on the register blocks to enter the instance number. Instance numbers are assigned to each type of blocks. The instance numbers start at 1 and increase with each consecutive block.
Note.
Each type of register has its own set of instance numbers. The example configuration, there is only one instance of each register type so each is assigned an instance number 1.
The links inside your configuration are connected in the same fashion as the normal I/O modules. The example configuration was made using pushbuttons, meters, and potentiometers. Refer to the appendices for a complete copy of the configuration.
!"#$ % * +&$ + ## #"
This chapter contains information about the setup and configuration of the DeviceNet Scanner interface. The example uses a SLC 5/04 PLC and 1747-SDN-scanner card.
Installing the EDS file
Step 1. Launch RSNetWorx for DeviceNet.
Step 2. Select “Tools :: EDS WIZARD …”.
The EDS Installation Wizard welcome screen will appear.
The EDS Wizard creates a directory and registers the L5351 EDS file.
The Wizard guides the reader through this process.
Step 3. Select the “Register an EDS file(s)” option .
Step 4.
Step 5.
Step 6.
Enter the location of your EDS file; “a:” in this example .
Click the Choose File button .
Select the EDS file; L5351a.eds and click the Open button .
This fills in the EDS path. Note that the figure below shows the path to the K: drive. The previous example figures would have a path like A:\L5351a.eds.
Step 7. The Wizard tests the EDS file .
Step 8. Leave the graphic image unchanged and click the “Next” button to continue .
Step 9. Click the “Finish” button to exit the Wizard .
Communications Setup
Step 1. Install the DeviceNet scanner card in the PLC rack .
In the example, the scanner card is installed in slot number two.
After installing of the DeviceNet scanner card in your PLC, it is necessary to configure the card with the correct number and type of registers. The configuration of the scanner card is done through the DeviceNet network.
Launch RSLinx before programming of the devices on your
DeviceNet network.
Step 2. Click on the COMMUNICATIONS :: CONFIGURE
DRIVERS .
Step 3. Select “DeviceNet Drivers” .
Step 4. Select the driver for the scanner card you are using. The example is using a 1770-KFD .
RSLinx will poll the interface for settings that may already be loaded. If the interface has been preloaded, it may be necessary to modify the address, baud rates, and the port selection.
The software will automatically go on-line with the interface.
If a PLC driver is also installed, the PLC driver cannot be running at the same time as the DeviceNet driver. Stop the PLC driver by highlighting the driver and clicking the stop button.
With the DeviceNet driver running, close the configure window and minimize the RSLinx program. The RSLinx program needs to run in the background.
The following figure shows how the RSLinx program should look when the communication network is up and running.
Configuring the DeviceNet Scanner
After completing the communications set-up, start programming the
DeviceNet module. Launch RSNetWorx program.
Step 1. Select the communication adapter that is being used for your application .
The example used the 1770-KFD and 1747-SDN rev 3. Doubleclicking on the icon places the selected device in the DeviceNet network.
Step 2. Select the L5351 EDS file from VENDOR ::
EUROTHERM CONTROLS LIMITED :: UNKNOWN
DEVICE TYPE 100 :: L5351 LINKCARD .
This is the file that was installed previously in this chapter. Doubleclicking the L5351 icon places it on the DeviceNet network.
Step 3. Double-click on the scanner icon in the network window on the right .
This will display the information for the scanner and allow the scanner parameters to be programmed.
The scanner card is configured with the exact number of bytes that are being used in the DeviceNet network. In the example Link configuration, one of each type of register was selected (Bit, Signed, and Unsigned registers).
REGISTER TYPE
BIT
SIGNED
UNSIGNED
TRANSMIT
1 WORD / 2 BYTES
16 WORDS / 32
BYTES
16 WORDS / 32
BYTES
RECEIVE
1 WORD / 2 BYTES
16 WORDS / 32
BYTES
16 WORDS / 32
BYTES
The total number of bytes being transmitted and received can be determined by multiplying the total number of words by 2. The example program has a total of 66 transmit bytes and 66 receive bytes. The number of bytes being transferred to/from the DeviceNet scanner and the Link registers must match. If the number of bytes does not match, the communications will fail. These values are setup for the scanner card in the RSNetWorx program.
The scanlist is a list of available devices. The L5351 Linkcard should be appear on the left side. If it does not, return to the beginning of this chapter for details on the installing the EDS file.
Add the L5351 to the scanlist by highlighting it in the available devices list and clicking the “>” button. When the L5351 has been moved the scanlist should appear like the above picture.
Step 4. Editing I/O parameters .
Click on the button labeled “Edit I/O Parameters,” this will allow the parameters to be changed. Select the “Polled” checkbox and enter the Rx and Tx sizes. Set the “Poll Rate” to Every Scan.
Note. The example has a total of 66 transmit bytes and 66 receive bytes.
Mapping
Our example is using a SLC 5/04; this PLC uses messages to transfer the data. Click on the tab labeled Input or Output to enter the mapping. Enter the map manually or use the AutoMap feature.
Automap fills in all the addresses automatically. You must assign a map for both Inputs and Outputs.
Enabling the DeviceNet Scanner
The DeviceNet scanner card is enabled by writing to the first output bit of the slot where the card is located. In the example, the scanner card is located in slot 1 in the PLC. In the program, B3: 0 writes to O: 1.0, which is the enable bit.
!"#$ "$%& #) %%" +
The following table is a list of codes that can appear on the DeviceNet scanner card.
Description Action Numeric
Code
Display
Summary
0-63 Display is node address Normal operation.
70 Module failure Duplicate address check.
Change Module address to another available address.
71
72
73
74
75
Illegal data in scan list table
(node number alternately flashes).
Reconfigure scan list table and remove any illegal data.
Slave device stopped communications (node number alternately flashes).
Check field devices and verify connections.
Device’s identity information does not match the electronic key in scan list table entry (node number alternately flashes).
Data overrun on port detected
Verify that the correct device is at this node number. Make sure that the device at the flashing node address matches the desired electronic key.
Modify your configuration and check for invalid data. Check network communication traffic.
No network traffic at all has been detected.
Verify connections.
76
77
78
No direct network traffic for scanner has been detected
None. The scanner hears other network communication.
Data size returned does not match scan list table entry
(node number alternately flashes)
Slave device in scan list table does not exist (node number alternately flashes).
Reconfigure your module and change the addressing.
Add the device to the network or delete the scan list entry for that device.
Numeric
Code
Display
Summary
79
80
Description
Module has failed to transmit a message
Action
Make sure your module is connected to a valid network. Check for disconnected cables.
Module is in the idle mode. No action required. Enable control bit to put module in the Run mode
81
82
83
84
85
86
88
90
91
Module is in the fault mode No specific action. Examine alternating number to determine fault.
Error detected in sequence of fragmented I/O messages from device
(node number alternately flashes).
Slave device is returning error responses when module attempts to communicate (node number alternately flashes).
Check scan list table for slave device to make sure that input and output data lengths are correct. Check slave configuration.
Check accuracy of scan list table entry.
Check slave device configuration.
Module is initializing
DeviceNet channel.
Data size returned is bigger than expected.
Device is producing idle state data while the scanner is in Run mode.
This is not an error. At power up and reset, the module displays all 14 segments of the node address and status display
LEDs.
User has disabled communication port.
Bus-off condition detected on comm. port.
This code will clear when initialization is complete.
Check scan list table entry for accuracy.
Check slave node configuration
Check device configuration/slave node status.
None
Reconfigure your module. Check module command register.
Check DeviceNet connections and physical media integrity. Check system failed slave devices or other possible sources of networ interference.
Numeric
Code
Display
Summary
92
Description
No network power detected on comm. port.
Action
Provide network power. Make sure that scanner drop cable is providing network to scanner comm.. port.
95
97
Application flash update in progress.
Module halted by user.
98, 99 Unrecoverable firmware or hardware failure.
None. Do not disconnect the module while applicatio FLASH is in progress. You will lose any existing data in the scanner’s memory.
Restart the module.
Service or replace your scanner module.
L5351 DeviceNet LinkCard Module Status LED
This bi-color (green – red) LED provides device status. The table below shows the LED states.
Status
Power Off Off
LED state Reason
• No power applied to the device
• Host Link2 module is not running its configuration
Device needs commissioning because of missing, incomplete or incorrect configuration
Device in standby
Needs to be commissioned
Device operational
Minor Fault
Unrecoverable fault
Flashing green
Green
Flashing Red
Red
Device Selftesting
Flashing Red and Green
The device is operating in a normal condition
Recoverable fault
Device has identified an unrecoverable fault. May need replacing.
Device in self-test mode
L5351 DeviceNet LinkCard Network Status LED
This bi-color (green – red) LED indicates the status of the communications link. The table below defines the different states of the Network Status LED.
Status LED state Reason
Power Off or not on-line
Off
On-line but not connected
Link OK, online, connected
Connection time-out
Critical Link failure
Flashing green
Green
Flashing Red
Red
Communication faulted
Received
Identify
Communication
Fault Request
Long Protocol
Flashing Red and Green
The device is not on-line
• The device has not yet completed the Dup_MAC_ID test
• The device may not have power applied to it Check
Module Status LED
The device is on-line, but has no connections in the established state
• Passed the Dup_MAC_ID test, is on line but has no established connections
• For a Group 2 only device:
Device is not allocated to a master
The device is on-line, has connections in the established state
• For a Group 2 only device:
Device is allocated to a master
One or more I/O connections are in the timed-out state
Failed communication device.
The device has detected an error that has rendered it incapable of communicating on the network
Could be Dup_MAC_ID or Bus-off
Specific communication faulted device. The device has detected a network access error and is in the Communication Faulted state.
It has subsequently received and accepted an Identify
Communication Faulted requested-Long protocol message
!!# .
) / ! # % * +&$ " % )
LINK CONFIGURATION
## #"0 % * +&$ " %
## #"0 % * +&$ " % % "1
!
) 2 3
This example uses a PLC-5/15 PLC and 1771-SDN-scanner card.
Configuring a system for use with a PLC 5 processor is similar to SLC
500 processor. The Link configuration is the same. The differences are in the configuring of the DeviceNet scanner card and in the PLC program.
The PLC 5 uses block transfers to move the data in and out of the plc processor. Insert a generic block transfer read and a generic block transfer write into the plc ladder program. Setup the block transfers as follows.
BLOCK TRANSFER READ VALUE
Rack
Group
Module
Control Block
Data File
Length
Continuous
0
0
0
GENERIC BLOCK TRANSFER
The rack where the scanner card is located.
The slot number in the rack
Always zero for single slot addressing
N11:0 Control register location
(5 consecutive registers required)
N10:1 First word of the data file
62
No
Length of data transfer from the scanner
Always select no
BLOCK TRANSFER
WRITE
Rack
VALUE GENERIC BLOCK TRANSFER
Group
Module
Control Block
Data File
Length
Continuous
0
0
The rack where the scanner card is located.
The slot number in the rack
0 Always zero for single slot addressing
N11:20 Control register location
(5 consecutive registers required)
N9:1 First word of the data file
62
No
Length of data transfer to the scanner
Always select no
#
!!# .
"#
2
Operating temperature
Storage temperature
Humidity
Enclosure Rating
Supply
Supply Voltage
Current Consumption
Power Dissipation
5VDC, supplied by backplane
11 - 24VDC, supplied by network
120 mA @ 5VDC, 30 mA @ 24VDC
0.8 W
)!# * " % )
0°C to 50°C (32 to 122 0 F)
-10 °C to +70 °C (14 to 158 0 F)
85% RAH. in a dry, non-condensing environment
Touchsafe IP20. To be mounted inside a SSD Drives L53XX series enclosure
Connection Types
Baud Rate
Data Types
Transport Class Trigger
Indicators supported
DeviceNet loading
Transfer delay
Configurability
Explicit messaging and polled I/O connections provided via Predefined
Master/Slave connection set.
Fragmentation supported for both polled I/O and explicit connections
125K, 250K and 500Kbaud
Bits, Unsigned Integers ( LINK Ordinals), signed integers ( LINK values)
Server Transport class 2
Network status bi-color LED, Module status bi-color LED
27 mA
Typically < 7 ms LINK input to DeviceNet output and vice-versa
LinkCard configuration performed using ConfigEd. DeviceNet network and PLC programmed independently
5 pin Phoenix Combicon or equivalent. Cable connector part number MSTB
2.5/5-ST-5.08-AU
Connector type
Physical
Height
Width
Depth
Weight
120mm (4.72 in)
32mm (1.25 in)
90mm (3.54in)
0.16 kg (0.35 lbs)