Machine Automation Controller NJ-series
EtherCAT(R)
Connection Guide
FANUC CORPORATION
R-30iB Robot Controller
P605-E1-01
About Intellectual Property Rights and Trademarks
Microsoft product screen shots reprinted with permission from Microsoft Corporation.
Windows is a registered trademark of Microsoft Corporation in the USA and other countries.
EtherCAT(R) is registered trademark and patented technology, licensed by Beckhoff Automation
GmbH, Germany.
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
Company names and product names in this document are the trademarks or registered trademarks of their respective companies.
Table of Contents
Applicable Devices and Device Configuration ........................................ 4
Applicable Devices .............................................................................. 4
Device Configuration ........................................................................... 5
Setting Up the Robot Controller .......................................................... 7
Allocation for PDO Communications ................................................... 8
EtherCAT Connection Procedure ............................................................ 10
Setting Up the FANUC Robot Controller ............................................ 11
Setting Up the Controller ................................................................... 20
Checking the EtherCAT Communications ......................................... 32
Initializing the Controller .................................................................... 38
Initializing the FANUC Robot Controller ............................................ 38
1.Related Manuals
1. Related Manuals
The table below lists the manuals related to this document.
To ensure system safety, make sure to always read and heed the information provided in all
Safety Precautions, Precautions for Safe Use, and Precaution for Correct Use of manuals for each device which is used in the system.
Cat. No.
W500
W501
Model
NJ501-[][][][]
NJ301-[][][][]
NJ501-[][][][]
NJ301-[][][][]
Manual name
NJ-series CPU Unit Hardware User's Manual
NJ-series CPU Unit Software User's Manual
W505 NJ501-[][][][]
NJ301-[][][][]
NJ-series CPU Unit Built-in EtherCAT(R) Port User's Manual
W504 SYSMAC-SE2[][][] Sysmac Studio Version 1 Operation Manual
B-83284EN R-30iB FANUC Robot series R-30iB/R-30iB Mate CONTROLLER
OPERATOR’S MANUAL(Basic Operation)
B-83704EN R-30iB FANUC Robot series R-30iB/R-30iB Mate CONTROLLER
EtherCAT Interface OPERATOR’S MANUAL
1
2.Terms and Definitions
2. Terms and Definitions
Term
PDO
Communications
(Communications using Process
Data Objects)
SDO
Communications
(Communications using Service
Data Objects)
Slave unit
Node address
ESI file
(EtherCAT Slave
Information file)
UOP
Digital I/O
Explanation and Definition
This method is used for cyclic data exchange between the master unit and the slave units.
PDO data (i.e., I/O data that is mapped to PDOs) that is allocated in advance is refreshed periodically each EtherCAT process data communications cycle (i.e., the period of primary periodic task).
The NJ-series Machine Automation Controller uses the PDO
Communications for commands to refresh I/O data in a fixed control period, including I/O data for EtherCAT Slave Units, and the position control data for the Servomotors.
It is accessed from the NJ-series Machine Automation Controller in the following ways.
・With device variables for EtherCAT slave I/O
・With Axis Variables for Servo Drive and encoder input slave to which assigned as an axis
This method is used to read and write the specified slave unit data from the master unit when required.
The NJ-series Machine Automation Controller uses SDO Communications for commands to read and write data, such as for parameter transfers, at specified times.
The NJ-series Machine Automation Controller can read/write the specified slave data (parameters and error information, etc.) with the
EC_CoESDORead (Read CoE SDO) instruction or the EC_CoESDOWrite
(Write CoE SDO) instruction.
There are various types of slaves such as Servo Drives that handle position data and I/O terminals that handle the bit signals.
The slave unit receives output data sent from the master, and sends input data to the master.
A node address is an address to identify a unit connected to EtherCAT.
The ESI files contain information unique to the EtherCAT slaves in XML format.
Installing an ESI file enables the Sysmac Studio to allocate slave process data and make other settings.
Peripheral I/O (UI/UO) is a group of specialized signals for robot control.
Digital I/O (DI/DO) is a group of general-purpose digital signals for data exchange with peripheral equipments.
2
3.Precautions
3. Precautions
(1) Understand the specifications of devices which are used in the system. Allow some margin for ratings and performance. Provide safety measures, such as installing safety circuit in order to ensure safety and minimize risks of abnormal occurrence.
(2) To ensure system safety, always read and heed the information provided in all Safety
Precautions and Precautions for Safe Use of manuals for each device used in the system.
(3) The user is encouraged to confirm the standards and regulations that the system must conform to.
(4) It is prohibited to copy, to reproduce, and to distribute a part or the whole of this document without the permission of OMRON Corporation.
(5) The information contained in this document is current as of August 2014. It is subject to change without notice for improvement.
The following notations are used in this document.
Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or property damage.
Precautions for Safe Use
Precautions on what to do and what not to do to ensure safe usage of the product.
Precautions for Correct Use
Precautions on what to do and what not to do to ensure proper operation and performance.
Additional Information
Additional information to read as required.
This information is provided to increase understanding or make operation easier.
Symbol
The filled circle symbol indicates operations that you must do.
The specific operation is shown in the circle and explained in text.
This example shows a general precaution for something that must do.
3
4.Overview
4. Overview
This document describes the procedure for connecting Robot Controller (R-30iB) of FANUC
Corporation (hereinafter referred to as FANUC) to NJ-series Machine Automation Controller
(hereinafter referred to as Controller) of OMRON Corporation (hereinafter referred to as
OMRON) via EtherCAT and provides the procedure for checking their connection.
Refer to Section 6 EtherCAT Settings and Section 7 EtherCAT Connection Procedure to understand the setting method and key points to operate PDO Communications of EtherCAT.
5. Applicable Devices and Device Configuration
5.1. Applicable Devices
The applicable devices are as follows:
Manufacturer
OMRON
Name
NJ-series CPU Unit
FANUC
FANUC
Robot Controller
Robot
Model
NJ501-[][][][]
NJ301-[][][][]
R-30iB (with optional EtherCAT slave function)
Refer to the following Additional Information.
Precautions for Correct Use
As applicable devices above, the devices with the models and versions listed in Section 5.2. are actually used in this document to describe the procedure for connecting devices and checking the connection.
You cannot use devices with versions lower than the versions listed in Section 5.2.
To use the above devices with versions not listed in Section 5.2 or versions higher than those listed in Section 5.2, check the differences in the specifications by referring to the manuals before operating the devices.
Additional Information
Contact sales representatives of FANUC Corporation for robots connectable to the Robot
Controller.
Additional Information
This document describes the procedure to establish the network connection. It does not provide information on operation, installation or wiring method which is not related to the connection procedure. It also does not describe the functionality or operation of the devices.
Refer to the manuals or contact the device manufacturer.
(FANUC Corporation http://www.fanuc.co.jp/eindex.htm)
This URL is the latest address at the time of this document creation.
Contact each device manufacturer for the latest information.
4
5.Applicable Devices and Device Configuration
5.2. Device Configuration
The hardware components to reproduce the connection procedure of this document are as follows:
Personal computer
(Sysmac Studio, installed,
OS: Windows7 )
NJ501-1500
(Built-in EtherCAT port)
Ethernet cable
Teach pendant
R-30iB
Manufacturer
OMRON
USB cable
OMRON
OMRON
-
-
-
FANUC
FANUC
FANUC
Name
CPU Unit
(Built-in EtherCAT port)
Power Supply Unit
Sysmac Studio
Personal computer
(OS: Windows7)
USB cable (USB 2.0 type
B connector)
Ethernet cable
Robot Controller
Model
NJ501-1500
NJ-PA3001
SYSMAC-SE2[][][]
-
-
-
R-30iB (with optional
EtherCAT slave function)
Teach pendant
Version
Ver.1.08
Ver.1.09
7DC2 series
(ver.11 or higher),
7DC3 series
ESI file
(Included with Robot
Controller) fanuc_rs_esi0001.xml 0x0001
Precautions for Correct Use
The ESI file “ver. 0x0001” shown above is used in this document to check the operations.
Precautions for Correct Use
Prepare the ESI file shown in this section beforehand.
To obtain the ESI file, contact FANUC.
Precautions for Correct Use
The connection line of EtherCAT communication cannot be shared with other Ethernet networks.
Do not use devices for Ethernet such as a switching hub.
Use the cable (double shielding with aluminum tape and braiding) of Category 5 or higher, and use the shielded connector of Category 5 or higher.
Connect the cable shield to the connector hood at both ends of the cable.
5
5.Applicable Devices and Device Configuration
Precautions for Correct Use
Update the Sysmac Studio to the version specified in this section or higher version using the auto update function.
If a version not specified in this section is used, the procedures described in Section 7 and subsequent sections may not be applicable. In that case, use the equivalent procedures described in the Sysmac Studio Version 1 Operation Manual (Cat. No. W504).
Additional Information
For specifications of the Ethernet cables and network wirings, refer to Section 4 EtherCAT
Network Wiring of the NJ-series CPU Unit Built-in EtherCAT(R) Port User's Manual (Cat. No.
W505).
Additional Information
The system configuration in this document uses USB for the connection to the Controller.
For how to install a USB driver, refer to A-1 Driver Installation for Direct USB Cable
Connection of the Sysmac Studio Version 1 Operation Manual (Cat.No. W504).
6
6.EtherCAT Settings
6. EtherCAT Settings
This section describes specifications such as the Robot Controller setup and allocation of
PDO Communications that are set in this document. This is used to connect the Controller to the Robot Controller via EtherCAT. Hereinafter, the Robot Controller is referred to as the
"Destination Device" or the "Slave Unit" in some descriptions.
6.1. Setting Up the Robot Controller
The setting of the Robot Controller is shown below.
Setting item
Node address
SMODE switch (EtherCAT board switch)
Switch on the front panel of Robot Controller Three mode switch
Switches on the Teach pendant Teach pendant enable switch
Screen setting of the Teach pendant The number of input
Set value
1 (default)
0 (fixed)
AUTO
OFF (disable)*
1
The number of output
512 points
(default)
512 points
(default)
Remote/local setup Remote
UOP auto assignment Full *
2
(default)
*
1
: When the Teach pendant enable switch is disabled, the operation of the Teach pendant is disabled. Accordingly, the Teach pendant cannot perform the jog feed, program operation, and test execution.
*
2
: The “UOP auto assignment” assigns all UOPs of input 18-points and output 20-points to I/O.
When the "UOP auto assignment" is set to "Full", the Robot Controller automatically sets the following set values of the UOP assignment.
■ UOP output
# Range Rack Slot Start
1 UO[1-8] 106 (fixed) 1 (fixed) 1
2 UO[9-16] 106 (fixed) 1 (fixed) 9
3 UO[17-20] 106 (fixed) 1 (fixed) 17
■ UOP input
# Range Rack Slot Start
1 UI[1-8]
2 UI[9-16]
106 (fixed)
106 (fixed)
1 (fixed)
1 (fixed)
1
9
3 UI[17-18] 106 (fixed) 1 (fixed) 17
Precautions for Safe Use
For explanation purpose, this document uses the settings above as an example. The user must decide actual set values according to the application to be used after verifying its safety.
7
6.EtherCAT Settings
6.2. Allocation for PDO Communications
The section describes allocation of PDO Communications between the Destination Device and the Controller.
6.2.1. Device Variables of the Controller
The PDO communications data for the Destination Device are allocated to the Controller's device variables.
The device variables and the data types are shown below.
■ Output area (from Controller to Destination Device)
Device variable name Data type Meaning
E001_OUT512_DI00_2102_01 UINT[8]
UOP inputs (UI1 to 18),
Digital inputs (DI1 to 110)
E001_OUT512_DI01_2102_02 UINT[8] Digital inputs (DI111 to 238)
E001_OUT512_DI02_2102_03 UINT[8] Digital inputs (DI239 to 366)
E001_OUT512_DI03_2102_04 UINT[8] Digital inputs (DI367 to 494)
■ Input area (from Destination Device to Controller)
Device variable name Data type Meaning
E001_IN512_DO00_3102_01 UINT[8]
UOP outputs (UO1 to 20),
Digital outputs (DO1 to 108)
E001_IN512_DO01_3102_02 UINT[8] Digital outputs (DO109 to DO236)
E001_IN512_DO02_3102_03 UINT[8] Digital outputs (DO237 to DO364)
E001_IN512_DO03_3102_04 UINT[8] Digital outputs (DO365 to DO492)
Additional Information
The device variables are named automatically from a combination of the device names and the port names.
The default device names are “E" followed by a serial number that starts from 001.
8
6.EtherCAT Settings
6.2.2. I/O Allocation for the Robot Controller
The I/O allocation for the Robot Controller is shown below.
Controller Robot Controller’s
Output variables
E001_OUT512_DI00_2102_01[0] to
E001_OUT512_DI03_2102_04[7]
64 bytes *
1
(512 bits)
EtherCAT slave
UOP input allocation
(18 points)
UI
*2
Robot Controller
#1:IMSTP
#2:Hold
:
#18:PROD_START
Digital inputs
(494 points)
DI
#1
#2
Not used
Input variables
E001_IN512_DO00_3102_01[0] to
E001_IN512_DO03_3102_04[7]
64 bytes *
1
(512 bits)
Not used
UOP output allocation
(20 points)
:
#494
#495
:
UO
*2
#1:Cmd enabled
#2:System ready
:
#20:RESERVED
Digital outputs
(492 points)
DO
#1
#2
:
#492
Not used Not used
#493
:
*
1
: In this setting example, 64 byte-data is exchanged for each input and output areas between the Controller and the Robot Controller’s EtherCAT slave.
*
2
: The “UOP auto assignment” assigns all UOPs of input 18-points and output 20-points to I/O.
Digital I/O is assigned for others.
9
7.EtherCAT Connection Procedure
7. EtherCAT Connection Procedure
This section describes the procedure for connecting the Controller to the Robot Controller via
EtherCAT.
This document explains the procedures for setting up the Controller and the Robot Controller from the factory default setting. For the initialization, refer to Section 8. Initialization Method.
7.1. Work Flow
Take the following steps to perform PDO Communications of EtherCAT.
7.2. Setting Up the FANUC Robot
Controller
↓
7.2.1. Hardware Settings
↓
7.2.2. Parameter Settings
Set up the FANUC Robot Controller.
Set the hardware switches on the Robot Controller and connect the cables.
Set the parameters for the Robot Controller.
↓
7.3. Setting Up the Controller
↓
Set up the Controller.
7.3.1. Starting the Sysmac Studio and
Installing the ESI File
↓
7.3.2. Setting Up the EtherCAT
Network Configuration
↓
7.3.3. Setting the Device Variables
Install the ESI file for the Robot Controller in the
Sysmac Studio.
Set up the EtherCAT network configuration.
Set the device variables used for the EtherCAT
Slave Unit.
↓
7.3.4. Transferring the Project Data Transfer the project data from the Sysmac Studio to the Controller.
↓
7.4. Checking the EtherCAT
Communications
↓
Confirm that the PDO Communications of EtherCAT are performed normally.
7.4.1. Checking the Connection Status Check the connection status of the EtherCAT network.
↓
7.4.2 Checking the Data that are Sent and Received
Confirm that the correct data are sent and received.
10
7.EtherCAT Connection Procedure
7.2. Setting Up the FANUC Robot Controller
Set up the FANUC Robot Controller.
7.2.1. Hardware Settings
Set the hardware switches on the Robot Controller and connect the cables.
Precautions for Safe Use
Make sure that the power supply to the Robot Controller is OFF before opening its front panel. Touching the internal board may result in electric shock or equipment damage while the power is being supplied.
1
2
Make sure that the power supply to the Robot Controller is
OFF.
*Step 3 in this section is potentially hazardous that may result in electric shock or equipment damage.
For safety, be sure to unplug the Power supply cable from the power supply source.
Check the position of the connectors and switches on the
Robot Controller.
Power switch
Emergency stop
Alarm release
Three mode switch
Start
(Front panel of Robot Controller)
11
7.EtherCAT Connection Procedure
3
Open the front panel of the
Robot Controller.
Insert the Ethernet cable from the wiring outlet located in the lower left of the rear panel on the Robot Controller, and pull out the cable toward the front panel.
(Lower left of the rear panel on Robot Controller)
4
5
Connect the Ethernet cable to the IN side of the connector on the EtherCAT board.
Confirm that the SMODE switch on the EtherCAT board is 0.
Close the front panel.
*For safety, after wiring has been completed, be sure to close the front panel before performing the subsequent steps.
Set the Three mode switch on the Robot Controller to the
AUTO side.
OUT
IN
(EtherCAT board)
T1
SMODE switch
AUTO
T2
6
Turn ON the Power switch on the Robot Controller to supply power.
* After power ON, a message appears indicating the initialization is being processed on the connected Teach pendant. Then the operation screen is displayed.
Do not start operation until the operation screen has been displayed.
(Three mode switch)
ON
OFF
(Power switch)
12
7.EtherCAT Connection Procedure
7.2.2. Parameter Settings
Set the parameters for the Robot Controller.
1
The following switch and keys are used to operate the Teach pendant.
(Refer to the right figure.)
・Switch
Teach pendant enable switch
・Keys
Function (F) keys: F1 to 5, NEXT key, MENU key, Cursor keys
(arrows), ITEM key, ENTER key, and Numeric keys: 0 to 9.
Teach pendant enable switch
Operation screen
MENU key
ITEM key
Function (F) keys: F1 to 5
NEXT key
Numeric keys: 0 to 9
(Teach pendant)
ENTER key
Cursor keys (arrows)
13
7.EtherCAT Connection Procedure
2
Turn OFF (disable) the Teach pendant enable switch on the Teach pendant.
3
4
Press the MENU key on the Teach pendant.
*After power ON, a message appears indicating the initialization is being processed. Then, the operation screen that was displayed before power OFF appears.
Do not start operation until the operation screen has been displayed.
Select 6 SETUP from the MENU 1
Menu and select EtherCAT with the cursor key.
Press the ENTER key.
* The above setting operation can be executed whatever type of configuration is displayed on the screen.
OFF ON
(Upper left of Teach pendant)
5
The SETUP EtherCAT Screen is displayed.
Confirm that the settings are made as follows:
The number of input: 512 points
The number of output: 512 points
*If any change is made to the setting, cycle the power supply.
After restarting, the changes become available.
14
6
Press the MENU key on the Teach pendant.
Select 0 --NEXT-- from the MENU 1
Menu with the cursor key.
Press the ENTER key.
7.EtherCAT Connection Procedure
7
Confirm that the screen changes to
MENU 2.
Select 6 SYSTEM – 6 Config from the MENU 2 Menu with the cursor key.
Press the ENTER key.
8
The System/Config Screen is displayed.
Press the ITEM key on the Teach pendant to display " Enter line number".
Enter 43 to display "43
Remote/Local setup".
Press the ENTER key.
15
9
The cursor moves to "43
Remote/Local setup".
Press the F4 key (CHOICE).
7.EtherCAT Connection Procedure
10
A screen menu is displayed.
Select 1 Remote with the cursor key.
Press the ENTER key.
11
Confirm that "43 Remote/Local setup" changes to Remote.
16
7.EtherCAT Connection Procedure
12
Move the cursor to "45 UOP auto assignment" with the cursor key.
Confirm that Full is indicated.
(Additional information)
* Assign I/O by changing the setting of "45 UOP auto assignment".
Press the F4 key (CHOICE) to display a screen menu and select 2
Full.
*"45 UOP auto assignment" indic ates Full.
A message appears indicating
“Clear ALL I/O assignments to
Apply this?".
Check the contents and press the
F4 key (CHOICE) to delete all the
I/O assignments.
*A message appears
indicating
"Cycle power to apply new UOP assignment".
Cycling the power supply.
After power ON, UOP is automatically assigned according to the setting.
After restarting, the System/Config
Screen is displayed.
Perform step 13.
(Additional information)
When assigning I/O by changing the setting of "45 UOP auto assignment".
17
13
Select 5 I/O - 7 UOP from the
MENU 1 Menu with the cursor key.
Press the ENTER key.
7.EtherCAT Connection Procedure
14
The I/O UOP Out Screen is displayed.
Press the F2 key (CONFIG).
15
The I/O UOP Out Screen is displayed for assignment.
Confirm that the following settings are made for RANGE, RACK,
SLOT, START.
RANGE: RACK: SLOT: START
・UO[1-8]:106:1:1
・UO[9-16]:106:1:9
・UO[17-20]:106:1:17
Confirm that STATUS is ACTIV.
*If the settings are different from the above, try again from step 3 to automatically assign UOP.
Press the F3 key (IN/OUT).
18
16
The I/O UOP In Screen is displayed.
Confirm that the following settings are made for RANGE, RACK,
SLOT, START.
RANGE: RACK: SLOT: START
・UI[1-8]:106:1:1
・UI[9-16]:106:1:9
・UI[17-18]:106:1:17
Confirm that STATUS is ACTIV.
*If the settings are different from the above, try again from step 3 to automatically assign UOP.
7.EtherCAT Connection Procedure
19
7.EtherCAT Connection Procedure
7.3. Setting Up the Controller
Set up the Controller.
7.3.1. Starting the Sysmac Studio and Installing the ESI File
Install the ESI file for the Robot Controller in the Sysmac Studio.
Install the Sysmac Studio and USB driver in the Personal computer beforehand.
1
Connect the Ethernet cable to the built-in EtherCAT port
(PORT2) of the Controller and
Controller
CPU Unit
USB cable
End Cover connect the USB cable to the peripheral (USB) port.
As shown in 5.2. Device
Configuration, connect the
Personal computer, Robot
Power Supply Unit
Ethernet cable
Controller, and Controller.
2
Turn ON the power supply to the
Controller.
3
Start the Sysmac Studio.
Click the Connect to Controller
Button.
* If a confirmation dialog for an access right is displayed at start, execute a selection to start.
4
The Connect to Controller
Dialog Box is displayed.
Select the Direct connection via
USB Option for Connection type.
Uncheck both the Upload the
project Check Box and the
Display the Troubleshooting
Dialog Box Check Box of
Operation after Connection.
Click the Connect Button.
20
7.EtherCAT Connection Procedure
5
A confirmation dialog box on the right is displayed. Check the contents and click the OK
Button.
*The displayed dialog depends on the status of the Controller used. Check the contents and click the OK or Yes Button to proceed with the processing.
6
A dialog box on the right is displayed. Check the contents and click the OK Button.
7
The Auto Connect Project
Dialog Box is displayed online.
When an online connection is established, a yellow bar is displayed on the Pane.
The left pane is called Multiview
Explorer, the top right pane is called Toolbox, the bottom right pane is called Status Monitor
Pane, and the middle pane is called Edit Pane.
Multiview
Explorer
Edit Pane
Toolbox
Status
Monitor Pane
Additional Information
For details on online connections to a Controller, refer to Section 6 Online Connections to a
Controller of the Sysmac Studio Version 1 Operation Manual (Cat. No. W504).
8
Double-click EtherCAT under
Configurations and Setup in the Multiview Explorer.
9
The EtherCAT Tab Page is displayed in the Edit Pane.
21
10
Right-click Master and select
Display ESI Library.
7.EtherCAT Connection Procedure
11
The ESI Library Dialog Box is displayed. Click the this folder link.
When the Explorer starts, close the dialog box by clicking the
Close Button.
12
The Explorer starts and a folder is opened, allowing you to install the ESI file. Copy the prepared
fanuc_rs_esi0001.xml to this folder.
22
7.EtherCAT Connection Procedure
13
Select Exit from the File Menu to exit the Sysmac Studio.
A dialog box is displayed confirming whether to save the project. If you do not need to save it, click the No Button.
*You need to restart the Sysmac
Studio after installing the ESI file.
14
In the same way as steps 3 to
10, restart the Sysmac Studio and display the ESI Library
Dialog Box.
Click the + Button of fanuc_rs_esi0001 to confirm that the FANUC R-30iB V8.20
Rev:0x00010000 device is displayed.
Confirm that an exclamation mark (warning) is not displayed.
Click the Close Button.
Precautions for Correct Use
If an exclamation mark (warning) is displayed for the ESI file, check the name of the ESI file and obtain the ESI file with a correct name. If an exclamation mark (warning) is displayed even when the name of the ESI file is correct, the file may be corrupted.
Contact the device manufacturer.
23
7.EtherCAT Connection Procedure
7.3.2. Setting Up the EtherCAT Network Configuration
Set up the EtherCAT network configuration.
Always confirm safety before you reset the Controller or any devices.
1
Right-click Master on the
EtherCAT Tab Page of the Edit
Pane, and select Write Slave
Node Address.
*If the EtherCAT Tab Page is not displayed on the Edit Pane, display it by following step 8 of
7.3.1. Starting the Sysmac
Studio and Installing the ESI
File.
A screen is displayed stating
"Get information is being executed".
2
The Slave Node Address Writing
Dialog Box is displayed.
The present value (setting node address) and FANUC R-30iB
V8.20 Rev:0x00010000 are displayed in the Actual network configuration.
3
Confirm that the node address of present value and set value is
1, respectively.
Click the Cancel Button.
*If the node address of present value is not 1, set the value to
1. Click the Write Button.
When finished, cycle the power supply to the Slave Unit.
24
4
The EtherCAT Tab Page is displayed again. Right-click
Master and select Compare
and Merge with Actual
Network Configuration.
A screen is displayed stating
"Get information is being executed".
5
The Compare and Merge with
Actual Network Configuration
Dialog Box is displayed.
Node address 1 and FANUC
R-30iB V8.20 Rev:0x00010000 are added to the Actual network configuration after the comparison.
Click the Apply actual network
configuration Button.
6
A confirmation dialog box is displayed. Check the contents and click the Apply Button.
The dialog box on the right is displayed. Click the Close
Button.
7.EtherCAT Connection Procedure
25
7
Node address 1, E001, and
FANUC R-30iB V8.20
Rev:0x00010000 are added to the Network configuration on
Sysmac Studio.
Confirm that the data above are added and click the Close
Button.
8
Node address 1, E001, and
FANUC R-30iB V8.20
Rev:0x00010000 are added to the EtherCAT Tab Page on the
Edit Pane.
7.EtherCAT Connection Procedure
26
7.EtherCAT Connection Procedure
7.3.3. Setting the Device Variables
Set the device variables used for the EtherCAT Slave Unit.
1
Select Offline from the
Controller Menu.
The yellow bar on the top of the
Edit Pane disappears.
2
Select FANUC R-30iB V8.20
Rev:0x00010000 set in the previous step in the EtherCAT
Tab Page and confirm that
Device name is E001.
*Device name can be changed as desired.
3
Double-click I/O Map under
Configurations and Setup in the Multiview Explorer.
4
The I/O Map Tab Page is displayed on the Edit Pane.
Confirm that Node1 is displayed in the Position Column and the
Slave Unit is displayed.
*To manually set a variable name for the Slave Unit, click a column under the Variable
Column and enter a name.
27
5
Right-click Node1 and select
Create Device Variable.
7.EtherCAT Connection Procedure
6
The variable names and variable types are automatically set.
Additional Information
The device variables are named automatically from a combination of the device names and the port names. The default device names are “E" followed by a serial number that starts from 001.
Additional Information
In this document, device variables are automatically named for a unit (a slave).
Device variables can also be automatically named for I/O ports.
28
7.EtherCAT Connection Procedure
7.3.4. Transferring the Project Data
Transfer the project data from the Sysmac Studio to the Controller.
Always confirm safety at the Destination Device before you transfer a user program, configuration data, setup data, device variables, or values in memory used for CJ-series Units from the Sysmac Studio.
The devices or machines may perform unexpected operation regardless of the operating mode of the CPU Unit.
1
Select Check All Programs from the Project Menu.
2
The Build Tab Page is displayed on the Edit Pane.
Confirm that "0 Errors" and "0
Warnings" are displayed.
3
Select Rebuild Controller from the Project Menu.
4
A confirmation dialog box on the right is displayed. Confirm that there is no problem and click the
Yes Button.
5
Confirm that "0 Errors" and "0
Warnings" are displayed in the
Build Tab Page.
29
6
Select Online from the
Controller Menu.
7
Select Synchronization from the Controller Menu.
8
The Synchronization Dialog Box is displayed.
Confirm that the data to transfer
(NJ501 in the right dialog) is selected. Then, click the
Transfer To Controller Button.
*After executing the Transfer To
Controller, the Sysmac Studio data is transferred to the
Controller and the data is compared.
9
A confirmation dialog box on the right is displayed. Confirm that there is no problem and click the
Yes Button.
A screen stating "Synchronizing" is displayed.
A confirmation dialog box on the right is displayed. Confirm that there is no problem and click the
No Button.
*Do not return to RUN mode.
7.EtherCAT Connection Procedure
30
10
Confirm that the synchronized data is displayed with the color specified by "Synchronized", and that a message is displayed stating "The synchronization process successfully finished".
If there is no problem, click the
Close Button.
*A message stating "The synchronization process successfully finished" is displayed if the Sysmac Studio project data and the data in the
Controller match each other.
*If the synchronization fails, check the wiring and repeat from step 1.
7.EtherCAT Connection Procedure
31
7.EtherCAT Connection Procedure
7.4. Checking the EtherCAT Communications
Confirm that the PDO Communications of EtherCAT are performed normally.
7.4.1. Checking the Connection Status
1
Check the connection status of the EtherCAT network.
Confirm that the EtherCAT communications are performed normally by checking the LED indicators on the Controller.
The LED indicators in normal status are as follows:
[NET RUN]: Lit green
[NET ERR]: Not lit
[LINK/ACT]: Flashing yellow
2
Select 0 --NEXT-- from the MENU 1
Menu of the Teach pendant on the
Robot Controller with the cursor key.
Press the ENTER key.
Select 4 STATUS from the MENU 2
Menu, and then select EtherCAT with the cursor key.
Press the ENTER key.
*The software LED "Fault" indicated by a red circle shows the following status:
Lit red (ON): Alarm occurs.
Lit green (OFF): Alarm released.
* If the software LED "Fault" is lit red
(ON), resolve the cause of the alarm and release them by performing steps 4 to 8.
(FANUC Teach pendant)
(Alarm status)
Software LEDs
32
3
Confirm that the EtherCAT communications are performed normally on the Teach pendant.
The following are displayed.
Communication status: OP
Software LED "Fault": Lit red (ON)
*Software LED "Fault" can be lit red under an error status other than an
EtherCAT error.
4
Take the following steps to release the alarm caused by other than an
EtherCAT communications error on the Robot Controller.
Select the Watch (Project) Tab
Page.
5
Enter the following names in the
Watch (Project) Tab Page for monitoring. Click an Input Name… in the Name Column to enter a new name.
E001_OUT512_DI00_2102_01[0]
E001_IN512_DO00_3102_01[0]
6
Select Binary from the pull-down list of Display format of the variable you set.
7.EtherCAT Connection Procedure
33
7
Enter 0000 0000 1000 0111 in the
Modify Column of
E001_OUT512_DI00_2102_01[0].
The Online value of
E001_OUT512_DI00_2102_01[0] changes to 0000 0000 1000 0111.
*As shown on the right figure, turn
ON UI[1](*IMSTP:immediate stop),
UI[2](*Hold: temporary stop),
UI[3](*SFSPD: safety speed), and
UI[8](Enable: ENBL).
Do not turn ON UI[6](Start: external start), UI[7](Home:
Homing),and UI[18](Prod Start: automatic operation start).
8
Press the Alarm release Button on the front panel of the Robot
Controller.
7.EtherCAT Connection Procedure
34
7.EtherCAT Connection Procedure
7.4.2. Checking the Data that are Sent and Received
Confirm that the correct data are sent and received.
Always confirm safety at the Destination Device before you transfer a user program, configuration data, setup data, device variables, or values in memory used for CJ-series Units from the Sysmac Studio.
The devices or machines may perform unexpected operation regardless of the operating mode of the CPU Unit.
1
Press the MENU key on the Teach pendant.
Select 5 I/O - 7 UOP from the
MENU 1 Menu with the cursor key.
Press the ENTER key.
2
The I/O UOP Out Screen is displayed.
On the right figure, UO[1] and UO[2] are turned ON that shows the status of the Robot Controller.
3
The Online value of
E001_IN512_DO00_3102_01[0] changes to 0000 0000 0000 0011.
*For information on how to set the
Watch Tab Page, refer to steps 5 to
8 of 7.4.1. Checking the
Connection Status.
35
4
Press the F3 key (IN/OUT).
7.EtherCAT Connection Procedure
5
The I/O UOP In Screen is displayed.
On the right figure, UI[1], UI[2],
UI[3], UI[8] of the Robot Controller are turned ON.
6
Enter 0000 0000 0000 0000 in the
Modify Column of
E001_OUT512_DI00_2102_01[0].
The Online value of
E001_OUT512_DI00_2102_01[0] changes to 0000 0000 0000 0000.
7
The I/O UOP In Screen is displayed.
Press the F3 key (IN/OUT).
36
8
The I/O UOP Out Screen is displayed.
On the right figure, UO[5] and UO[6] are turned ON that shows the status of the Robot Controller.
7.EtherCAT Connection Procedure
9
The Online value of
E001_IN512_DO00_3102_01[0] changes to 0000 0000 0011 0000.
*For information on how to release the software LED "Fault" by turning
ON UO[1](Cmd Enabled) and
UO[2](System Ready), refer to steps 4 to 8 of 7.4.1. Checking the
Connection Status.
37
8.Initialization Method
8. Initialization Method
This document explains the setting procedure from the factory default setting.
Some settings may not be applicable as described in this document unless you use the devices with the factory default setting.
8.1. Initializing the Controller
To initialize the settings of the Controller, select Clear All Memory from the Controller Menu of the Sysmac Studio. The Clear All Memory Dialog Box is displayed. Check the contents and click the OK Button.
8.2. Initializing the FANUC Robot Controller
The Robot Controller is initialized by restoring a backup of factory default parameters.
For details on how to backup and restore parameters of the Robot Controller, refer to the
FANUC Robot series R-30iB/R-30iB Mate CONTROLLER EtherCAT Interface OPERATOR’S
MANUAL(Cat.No.B-83704EN).
38
9.Revision History
9. Revision History
Revision code
01
Date of revision
Aug. 18, 2014 First edition
Revision reason and revision page
39
40
P605-E1-01
2014
0814(-)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Applicable Devices
- 8 Device Configuration
- 10 Setting Up the Robot Controller
- 11 Allocation for PDO Communications
- 13 Work Flow
- 14 Setting Up the FANUC Robot Controller
- 23 Setting Up the Controller
- 35 Checking the EtherCAT Communications
- 41 Initializing the Controller
- 41 Initializing the FANUC Robot Controller