AUTOSTART 710 (AS710S) series
PROGRAMMABLE GENERATOR CONTROLLER
The Autostart 710 provides the control features needed for the automatic start, load transfer and shutdown of a standby generator or pump. Microprocessor technology allows the Autostart 710 to be programmed for use in a wide range of engine and generator control applications.
Key features
•
Automatic or manual operation, selected by key-switch or optional rotary switch.
•
32 character, back-lit liquid crystal display (LCD), showing operating mode, system status, timer information, generator RPM/Hz., oil pressure and engine temperature
•
Full programmability of engine control options, timers, trip levels, fault options and input/output configurations
•
Comprehensive fault protection and alarm system:low oil pressure and high engine temperature alarms
(using analogue or switch sensors), engine overspeed and underspeed, emergency stop, start fail, charge fail, high and low battery voltage, 3 programmable fault inputs.
•
6 programmable outputs, each configurable to one of over 30 function types.
•
Pin compatibility with Keystart 9700 range, allowing standardisation of panel wiring
Operation
The AS710’s operating mode is selected by use of a 3 position switch:–
Off/reset. Removes power from the unit, disabling the engine and resetting a latched fault condition.
Automatic start-up, load transfer and return to standby in response to a mains fail or remote start condition, with full fault protection.
Manual start and stop of the generator, either immediately on selecting manual mode or by use of remote push button switches.
Green and amber LEDs around the switch indicate the selection of Auto or Manual modes. On keyswitch versions, the key is common to all units and is removable in the Off and Auto positions only.
Control Outputs
The following outputs are provided:-
•
Single pole, switched +ve relay outputs for the control of engine fuel and starter motor circuits.
•
Switched +ve outputs for signalling auto and manual modes, plus a –ve DC output for Off/reset.
•
6 function programmable outputs (see overleaf).
Fault Protection and Alarm System
In Auto or Manual modes, Autostart shuts down and latches out the generator on detection of low oil pressure, high engine temperature, overspeed, start fail or emergency stop faults.
The Autostart may also be set up to shut down the generator on a low generator frequency or speed condition.
3 additional inputs may be used with remote fault switches
(giving a ‘shutdown’ or ‘warning’ response), or as control inputs with remote contacts or panel switches (see overleaf).
Non-latching, 'warning only' alarms are provided for high and low battery volts, charge fail and mag. pickup fail conditions.
Product Specification
Power supply:
Operating voltage: steady state range
crank brown-out
Current consumption
Inputs:
DC inputs (inputs 1 - 5, mains fail): positive input voltage range negative input voltage range
Generator AC input: operating voltage range frequency measurement range
Magnetic pickup: operating voltage range frequency measurement range
Outputs:
Start and fuel relays
Programmable outputs 1 – 3
Programmable output 4
Programmable output 5
(default setting: common alarm)
Programmable output 6
(default setting: gen. contactor)
Auto & Manual outputs
Off/reset output
General:
5 – 40 V DC continuous, to 0 V for <= 100 mSec typically 150 mA
80% to 100% of battery +ve
–1V to +2V w.r.t. battery –ve
90 – 300 V AC rms
0 – 99 Hz.
7 – 80 V AC rms
0 – 10 kHz
(all ratings for resistive load)
+ ve DC (switched SPNO contact)
16A max. @ 24 V DC
– ve DC (open collector transistor)
250mA max. @ 33 V DC
– ve DC (switched SPNO contact)
5A max. @ 24 V DC
+ ve DC (switched SPNO contact)
5A max. @ 24 V DC volt free SPNO relay contacts
5A max. @ 240 V AC
+ ve DC (switched), 250 mA max.
– ve DC (switched), 250 mA max.
Overall dimensions (W x H x D)
Panel cut-out size
Weight
Operating ambient temperature
Case sealing
96 x 96 x 162 mm
DIN standard 92 x 92 mm approx. 650 g
–10 to +55
IP22 o C
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Programmable functions
The Autostart 710 has over 30 programmable functions:-
Timers:-
Start delay; preheat, crank and crank cool (dwell) times; alarm override time; warm-up delay, mains restore delay; engine cool (run on, off load) time, speed signal delay.
Inputs:-
Inputs 1 and 2 are dedicated for use with low oil pressure and high engine temperature sensors, switch or analogue type. Inputs 3, 4 and 5 may be programmed for a range of uses, including shutdown or warning faults, manual restore
(of mains), test off load, alarm mute, etc. The inputs can be set up to work with remote contacts which either open or close when active, with wiring to either +ve or –ve DC.
Outputs:-
6 programmable outputs, each of which may be set to give one of over 30 signalling or control ‘actions’, including: Preheat (4 types), Energised to Stop Fuel,
Louvre Control, Generator Available, Common Alarm,
Alarm (muteable), Shutdown Fault, Warning Fault,
Overspeed, Start Fail, individual faults (1 - 5), etc.
Other System parameters:-
Crank release (by engine RPM, generator Hz. or charge alternator WL voltage), underspeed and overspeed trip levels (Hz. or RPM); maximum number of start attempts; high and low battery voltage warning levels; enable or disable loading of generator in manual mode.
When ordering, please specify:-
AS710S
Switch option:-
K = keyswitch
R = rotary (knob) switch
Generator AC voltage:-
D = 230 VAC
C = 110 VAC
Typical Connection mains contactor
L O A D
L1L2 L3 N
M
A
I
N
S
L1
L2
L3
N
Rear Facia & Electrical Connection
13
14
15
9
10
11
12
7
8
5
6
3
4
1
2
9
10
11
12
7
8
5
6
1
2
3
4
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
–ve DC supply
Charge fail input
5 – 40 VDC
+ ve DC power supply
+ ve DC (relays)/Emerg. stop
Magnetic pickup input
Output 1
Output 2
– ve DC
250 mA max
A800 enable output
Output 3: – ve, < 250mA
Output 4: – ve DC, 5 A max.
Remote start/mains fail input
- No connection -
Off output: – ve, < 250mA
Manual output
Auto output
+ ve DC
250mA max.
Accessories:gen.
contactor
Communications Port
24
25
26
27
28
29
30
20
21
22
23
16
17
18
19
Input 1: low oil pressure
Input 2: high engine temp.
Input 3: programmable
Input 4: programmable
Input 5: programmable
Index Pin
Fuel output
Starter output
+ve DC
16 A max.
Output 5 (alarm): + ve, < 5A
NO
CO
Output 6 (gen. contctr) volt free, 5 A max.
– ve
Man. Start Man. Stop
Live
Neutral
Generator AC
300 VAC max.
AS7PROG Hand held programmer key-pad
AS7CA 9 way (interface) to 9 way (PC) comms lead
AS7CB
AS7CC
9 way (interface) to 25 way (PC) comms lead
RS232 communications local interface
AS7CD
AS7CK
RS232 communications modem interface
AS7xx communication and programming software
MCCB
L1
L2
L3
N
E
R
A
G
E
N
T
O
R
+ve DC
Fuse
+
–
WL
L1 L2 L3 N
UVR500
1 2 3 4 5 6
Reset
Magnetic
Pickup
MCR
RPO4
RPO3
RPO2
RPO1
Emerg.
stop
MCR1
GCR1
5A
3
4
1
2
16
17
18
19
20
7
8
5
6
22
23
9
10
11
24
25
26
12
13
14
AUTOSTART
710
27
28
29
15 30
GCR
1A
Manual Auto
RST
RFL inputs
Fuel
Starter
RAL
Alarm
–ve DC
Since 1939
Frank W. Murphy Manufacturer
PO Box 470248, Tulsa, Oklahoma 74147, USA
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146 email: [email protected]
web: http://www.fwmurphy.com
Frank W. Murphy Ltd.
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Tel: + 44 1722 410055 Fax + 44 1722 410088
Pour service en Français, tél: + 44 1722 410697 email: [email protected]
web: http://www.fwmurphy.co.uk
Frank W. Murphy Ltd. en France
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89
Direct usine Tel: + 44 1722 410697 email: [email protected]
Frank W. Murphy Pte, Ltd.
No. 2 Tuas South Street 2, Sprintecs Building
02-01/02, Singapore 637895
Tel: + 65 863 1398 Fax: + 65 863 0208 email: [email protected]
Frank W. Murphy Southern Division
PO Box 1819, Rosenberg, Texas 77471, USA
Tel: + 1 281 342 0297 Fax: + 1 281 341 6006 email: [email protected]
Murphy Switch of California
41343 12th Street West, Palmdale, CA 93551, USA
Tel: + 1 661 272 4700 Fax: + 1 661 947 7570 email: [email protected]
web: http://www.murphyswitch.com
Macquarrie Corporation
1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558 email: [email protected]
Murphy de Mexico S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P. México 78384
Tel: + 52 48 206264 Fax: + 52 48 206336 email: [email protected]