OMRON SRM1 C01-V2, C02-V2 Master Control Units Operation Manual
Advertentie
Advertentie
Cat.No. W318–E1–4
CompoBus/S
SRM1(-V2)
Master Control Units
OPERATION MANUAL
CompoBus/S
SRM1(-V2) Master Control Units
Operation Manual
Revised May 2000
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1997
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions
5 Application Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 SRM1 Features and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Procedures From System Design to Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 I/O and Data Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Specifications and Components . . . . . . . . . . . . . . . . . . . .
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Selecting an Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Installing the SRM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Wiring and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 One-to-one NT Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6 One-to-N NT Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 One-to-one PC Link Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Using the Programming Console . . . . . . . . . . . . . . . . . . .
4-1 Basic Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Test Runs and Error Processing
5-1 Startup Procedure
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Entering the Program
5-3 Test Run
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Programming Console Operation Errors
5-6 Programming Errors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7 Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Expansion Memory Unit
6-1 Overview
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Specifications and Nomenclature
6-3 Handling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
34
36
83
84
85
86
17
18
19
20
21
30
30
31
59
60
75
75
77
62
71
72 xi xii xii xii xiii xiii
11
12
15
1
2
3
7
8 vii
viii
TABLE OF CONTENTS
Appendices
A Standard Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B External Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99
115
93
97
119
About this Manual:
The SRM1 is a special CompoBus/S controller that provides remote I/O with greatly reduced wiring. A distributed I/O system with up to 32 Slaves and 256 I/O points can be constructed. There are two manuals describing the setup and operation of the SRM1: The SRM1(-V2) Operation Manual (this manual) and the
CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353).
This manual describes the system configuration and installation of the SRM1 and provides a basic explanation of operating procedures for the Programming Consoles and introduces the capabilities of the
SYSMAC Support Software (SSS). Read this manual first to acquaint yourself with the SRM1.
The CompoBus/S Operation Manual (W266) provides descriptions of the CompoBus/S system and
Units.
The CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353) provides detailed descriptions of the SRM1’s programming functions. The SYSMAC Support Software (SSS) Operation
Manuals: Basics (W247) and C-series PCs (W248) provide descriptions of SSS operations for the SRM1 and C-series PCs.
The SYSMAC-CPT Support Software Quick Start Guide (W332) and User Manual (W333) provide descriptions of ladder diagram operations in the Windows environment.
The WS02-CXPC1-E CX-Programmer User Manual (W361) and the CX-Server User Manual (W362) provide details of operations for the WS02-CXPC1-E CX-Programmer.
Please read this manual carefully and be sure you understand the information provide before attempting to install and operate the SRM1.
Section 1 describes the SRM1’s special features and functions and shows the possible system configurations.
Section 2 provides the technical specifications of the SRM1 and describes its main components.
Section 3 explains how to install and wire the SRM1. Be sure to follow the instructions contained here concerning the control panel, power supply, CompoBus/S transmissions, and RS-232C Port wiring.
Section 4 explains how to use the Programming Console. Be sure to read this section carefully if you are not already familiar with Programming Console operations.
Section 5 describes procedures for trial runs of SRM1 operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during operation.
Section 6 describes how to use the CPM1-EMU01-V1 Expansion Memory Unit. Follow the handling precautions and procedures to properly use the Unit.
Appendix A provides a list of standard models.
Appendix B provides the external dimensions.
!
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
PRECAUTIONS
This section provides general precautions for using the SRM1 and related devices.
The information contained in this section is important for the safe and reliable application of the SRM1. You must read this section and understand the information contained before attempting to set up or operate a CompoBus/S System.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xiii xiii xi
Safety Precautions
1
2
3
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
•
Personnel in charge of installing FA systems.
•
Personnel in charge of designing FA systems.
•
Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the OMRON
SRM1. Be sure to read this manual before attempting to use the software and keep this manual close at hand for reference during operation.
!
WARNING It is extremely important that an SRM1 and all CompoBus/S Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your
OMRON representative before applying a CompoBus/S System to the abovementioned applications.
3 Safety Precautions
!
WARNING Never attempt to disassemble any Units while power is being supplied. Doing so may result in serious electrical shock or electrocution.
!
WARNING Never touch any of the terminals while power is being supplied. Doing so may result in serious electrical shock or electrocution.
!
WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, in order to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents.
•
Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
•
The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
•
The PC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
xii
Application Precautions
4
5
5
!
WARNING When transferring programs to other nodes, or when making changes to I/O memory, confirm the safety of the destination node before transfer. Not doing so may result in injury.
!
Caution Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, the input signals may not be readable.
Operating Environment Precautions
Do not operate the control system in the following places.
•
Where the SRM1 is exposed to direct sunlight.
•
Where the ambient temperature is below 0
°
C or over 55
°
C.
•
Where the SRM1 may be affected by condensation due to radical temperature changes.
•
Where the ambient humidity is below 10% or over 90%.
•
Where there is any corrosive or inflammable gas.
•
Where there is excessive dust, saline air, or metal powder.
•
Where the SRM1 is affected by vibration or shock.
•
Where any water, oil, or chemical may splash on the SRM1.
!
Caution The operating environment of the CompoBus/S System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the
CompoBus/S System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
Application Precautions
Observe the following precautions when using the SRM1.
!
WARNING Failure to abide by the following precautions could lead to serious or possibly fatal injury. Always heed these precautions.
•
Always turn off the power supply to the SRM1 before attempting any of the following.
•
Assembling any devices or racks.
•
Connecting or disconnecting any cables or wiring.
!
Caution Failure to abide by the following precautions could lead to faulty operation of the
SRM1 or the system or could damage the SRM1 or CompoBus/S Units. Always heed these precautions.
•
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
•
Construct a control circuit so that power supply for the I/O circuits does not come ON before power supply for the Unit. If power supply for the I/O circuits comes ON before power supply for the Unit, normal operation may be temporarily interrupted.
•
If the operating mode is changed from RUN or MONITOR mode to PROGRAM mode, with the IOM Hold Bit ON, the output will hold the most recent status. In such a case, ensure that the external load does not exceed specifications. (If operation is stopped because of an operation error (including FALS instructions), the values in the internal memory of the CPU Unit will be saved, but the outputs will all turn OFF.) xiii
Application Precautions 5
•
Use the Units only with the power supplies and voltages specified in the operation manuals.
•
Take measures to stabilize the power supply to conform to the rated supply if it is not stable.
•
Provide circuit breakers and other safety measures to provide protection against short-circuiting in external wiring.
•
Install all Units according to instructions in the operation manuals.
•
Do not install the Units in a place where they are subject to excessive noise in order to avoid any trouble or malfunction.
•
Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunction.
•
Double-check all the wiring before turning ON the power supply. Incorrect wiring may result in burning.
•
Do not attempt to take any Units apart, to repair any Units, or to modify any
Units in any way.
•
Do not apply any impact to the Units.
•
Use the cables specified in this manual and in reference manuals. Use crimp terminals when wiring the terminal block.
•
Use a signal wire duct that is separate from the one used for high-tension lines or power lines.
•
Be sure to confirm that the switch settings and wiring are correct before turning on the power supply.
•
Check the user program for proper execution before actually running it on the
Unit. Not checking the program may result in an unexpected operation.
•
Confirm that the user programs run properly.
•
Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
•
Changing the operating mode of the PC.
•
Force-setting/force-resetting any bit in memory.
•
Changing the present value of any word or any set value in memory.
•
Before touching the Unit, be sure to first touch a grounded metallic object in order to discharge any static build-up. Not doing so may result in malfunction or damage.
•
Use, store, and transport the Units within the specifications provided in this manual.
•
Resume operation only after transferring to the new SRM1 the contents of the
DM and HR Areas required for resuming operation. Not doing so may result in an unexpected operation.
•
Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables.
•
Do not place objects on top of the cables. Doing so may break the cables.
•
When replacing parts, be sure to confirm that the rating of a new part is correct.
Not doing so may result in malfunction or burning.
•
Be sure to observe local ordinances and laws when disposing the Units.
xiv
Application Precautions 5
!
Caution The following precautions are necessary to ensure the general safety of the system. Always heed these precautions.
•
Provide double safety mechanisms to handle incorrect signals that can be generated by broken signal lines or momentary power interruptions.
•
Provide external interlock circuits, limit circuits, and other safety circuits in addition to any provided within the SRM1 to ensure safety.
!
Caution Be sure to clear the memory before turning on the power supply to the delivered
SRM1. The contents of the Data Memory (DM), Hold Relay (HR), and Counter
(CNT) Areas in the CPU Unit may be cleared and the AR 1314 flag (which turns
ON when the power interruption hold area is not held) may turn ON.
!
Caution Apply the SRM1 to a system that is not influenced by any undefined data even if the data in the DM, HR, or CNT area is cleared when the SRM1 has been turned off for a period exceeding the data backup period of the internal lithium battery.
If the AR 1414 flag is ON, the data will be held unless it is turned OFF by the I/O
Monitor, instructions, etc.
The system can be stopped by designating DM 6604 in the PC Setup so that a memory error occurs when the power interruption hold area is not held (with
AR 1314 ON)
•
A lithium battery in the CPU Unit is used to back up the counter values and the contents of the DM area, and HR area. The deterioration of the lithium battery capacity depends on the ambient temperature. The standard service life is 12 years under an ambient temperature of 40 _ C when operating 8 hours a day.
If the power remains off for a period exceeding the data backup period, the contents of the Data Memory (DM), Hold Relay (HR), and Counter (CNT)
Areas in the CPU Unit may be cleared and the AR 1314 flag (which turns ON when the power interruption hold area is not held) may turn ON.
If the contents of the CPU Unit’s program area are lost, the program stored in flash memory will be read to the CPU Unit’s program area when the SRM1 is started up because the contents in the read-only area (DM 6144 through
DM 6599) and PC Setup (DM 6600 through DM 6655) will be written to flash memory.
•
However, if the power is turned off without changing the mode even if changes are made in the read-only DM area (DM 6144 through DM 6599), or PC Setup
(DM 6600 through DM 6655) using a peripheral device, the contents of changes will not be written to flash memory. Although the data in these areas is backed up by the lithium battery, contents of changes will disappear if the service life of the lithium battery expires. In this case, programs in the flash memory will be automatically read into the user program memory.
The changes can be saved by switching the SRM1 to RUN or MONITOR mode or turning off and restarting the SRM1 soon after the changes are made.
xv
SECTION 1
Introduction
This section describes the SRM1’s special features and functions and shows the possible system configurations.
1-1 SRM1 Features and Functions
1-1-1 Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-2 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-1 Basic Configuration
1-2-2 SRM1 Models
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-3 Peripheral Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Procedures From System Design to Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 I/O and Data Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-1 I/O Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-2 Data Area Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
7
8
8
9
3
4
2
3
2
2
1
SRM1 Features and Functions
1-1 SRM1 Features and Functions
1-1-1 Features
Section 1-1
The SRM1 is a special CompoBus/S controller that provides remote I/O with greatly reduced wiring. The SRM1 has no built-in I/O terminals, but it can provide the same I/O control as earlier PCs through the Slaves (Slave Terminals) that are used for I/O.
A decentralized I/O system with up to 32 Slaves can be constructed. The system can have up to 256 I/O points and these I/O points are controlled with the CompoBus/S System’s high-speed response time of 1 ms max.
A very reliable and efficiently wired system can be constructed from special
CompoBus/S components such as Analog Terminals (SRM1-C0 j
-V2 only),
Remote Terminals, Sensor Terminals, Communications Cables, Connectors, and Terminators.
In SRM1-C0 j -V2, the CompoBus/S system can be set to operate in long-distance communications mode in addition to the previous high-speed communications mode. This allows a main line length of up to 500 m so that I/O devices can be controlled from some distance away. The SRM1-C0 j -V2 can also process analog data as well as digital I/O.
The SRM1’s compact design allows for a smaller and thinner control panel.
The SRM1 is equipped with a program capacity of 4K words and a DM capacity of 2K words.
There are two SRM1(-V2) models available: the SRM1-C02-V2, which is equipped with an RS-232C port and communications functions, and the very cost-effective SRM1-C01-V2, which is not equipped with an RS-232C port.
1-1-2 Functions
Interval Timer Function
Low-maintenance Design
Communications
The SRM1 is equipped with an interval timer which can be set from 0.5 ms to
319,968 ms in units of 0.1 ms. The timer can be set to trigger a single interrupt
(one-shot mode) or repeat scheduled interrupts (scheduled interrupt mode).
(The interrupts pause execution of the main program while an interrupt program is executed.)
Memory can be backed up without a battery by using flash memory.
The SRM1 can communicate with PCs or other devices via Host Link, 1:1 NT
Link, 1:N NT Link, 1:1 PC Link, or RS-232C communications.
Port Applicable communications functions
Peripheral Port Peripheral device connections, Host Link, and RS-232C communications
RS-232C Port Host Link, 1:1 NT Link, 1:N NT Link, 1:1 PC Link, and no-protocol
(RS-232C) communications
Programming Using the
PT
Programming is possible through the PT (Programmable Terminal) screen using an OMRON PT that contains Programming Console functions. (This applies only to the SRM1-C02-V1 and SRM1-C02-V2.)
Standard Peripheral Devices The SRM1 uses the same Programming Consoles, CX-Programmer, SYSMAC-
CPT, and SYSMAC Support Software (SSS) as the Mini H-type, CQM1,
CPM1/CPM1A, and CPM2A/CPM2C PCs.
2
System Configuration
Expansion Memory Unit
Section 1-2
The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for smallsize or micro PCs. Using the CPM1-EMU01-V1, simple on-site transfer of user programs and data memory is possible with PCs.
PERIPHERAL
RS-232C
Peripheral port
1-2 System Configuration
1-2-1 Basic Configuration
Host device
Peripheral device
CompoBus/S Communications Cable
SRM1
Slave Slave
32 Slaves max.
Slave
Terminator
3
System Configuration
1-2-2 SRM1 Models
Section 1-2
Function
Data backup
Programming
Console functions
Data processing
Communications
Connections with host devices
Instructions
Model RS-232C port
SRM1-C01-V2 No
SRM1-C02-V2 Yes
No
Yes
PT programming functions
The following table compares the functions in the SRM1(-V2) PCs with the functions in earlier SRM1 PCs.
SRM1 models
SRM1-C0 j -V2 SRM1-C0 j -V1
Backed up by a lithium battery with a minimum lifetime of 10 years at 25 _ C.
Programming can be performed through a Programming
Console connected to the peripheral port or an OMRON PT connected to the RS-232C port.
SRM1-C0
Capacitor backup j
Programming can be performed through a Programming Console connected to the peripheral port.
Bit data (ON/OFF status of bits) Bit data (ON/OFF for 16 bits) and 16-bit analog data from Analog Units
High-speed communications (previous mode) or long-distance communications mode
High-speed communications mode (previous mode) only.
Host Link, no-protocol, 1:1 NT Link, 1:N NT
Link, and 1:1 PC Link communications
The instructions in earlier SRM1 PCs plus the following instructions:
NEG(––), PID(––), SCL(66), and ZCP(––)
Host Link, no-protocol, 1:1 NT Link, and 1:1 PC
Link communications
Basic instructions: 14
Special instructions: 77 (123 variations)
Note The Analog Terminal can be used as a slave only with version-2 models. Incorrect data may be transferred if an Analog Terminal is used with the wrong model.
SRM1-C01-V2
(No RS-232C port)
SRM1-C02-V2
(With RS-232C port)
Peripheral port Peripheral port
RS-232C port
4
System Configuration Section 1-2
1-2-3 Peripheral Connections
The following peripherals can be connected to the SRM1(-V2) PCs. Refer to
Appendix A Standard Models for a complete list of connectable peripherals.
Slaves The following table shows the Slaves that can be connected. Refer to the Com-
poBus/S Operation Manual (W266) for more details.
Slave
Remote Terminals
(transistors)
Connector
Terminals
(transistors)
Remote Terminals
(relays)
Remote Terminals
(power MOSFET)
Remote Modules
Analog Input
Terminal
Analog Output
Terminal
Sensor Amplifier
Terminals
Sensor Terminals
SRT2 Series
High-speed or long-distance communications
SRT2-ID04
SRT2-ID04-1
SRT2-ID08
SRT2-ID08-1
SRT2-ID16
SRT2-ID16-1
SRT2-ID16T
SRT2-ID16T-1
SRT2-OD04
SRT2-OD04-1
SRT2-OD08
SRT2-OD08-1
SRT2-OD16
SRT2-OD16-1
SRT2-OD16T
SRT2-OD16T-1
SRT2-MD16T
SRT2-MD16T-1
SRT2-VID08S
SRT2-VID08S-1
SRT2-VID16ML
SRT2-VID16ML-1
SRT2-VOD08S
SRT2-VOD08S-1
SRT2-VOD16ML
SRT2-VOD16ML-1
SRT2-ROC08
SRT2-ROC16
SRT2-ROF08
SRT2-ROF16
None
SRT2-AD04
SRT1 Series
High-speed communications only
SRT1-ID04
SRT1-ID04-1
SRT1-ID08
SRT1-ID08-1
SRT1-ID16
SRT1-ID16-1
None
SRT1-OD04
SRT1-OD04-1
SRT1-OD08
SRT1-OD08-1
SRT1-OD16
SRT1-OD16-1
None
None
SRT1-ROC08
SRT1-ROC16
SRT1-ROF08
SRT1-ROF16
SRT1-ROF08
SRT1-ROF16
None
SRT2-DA02
SRT2-TID04S (See note 3.)
SRT2-TKD04S (See note 3.)
SRT2-ID08S (See note 3.)
SRT2-OD08S (See note 3.)
SRT2-MD08S (See note 3.)
SRT1-TID04S
SRT1-TKD04S
SRT1-ID08S
SRT1-OD08S
SRT1-MD08S
5
System Configuration Section 1-2
Slave
Bit Chain Terminal
I/O Link Unit
SRT2 Series
High-speed or long-distance communications
None
CPM1A-SRT21
SRT1 Series
High-speed communications only
SRT1-B1T
None
Compatible
Communications Modes
Note 1. SRT1-series Remote Terminals and Sensor Terminals can operate in highspeed communications mode only. Be sure to use SRT2-series Remote Terminals and Sensor Terminals when the SRM1-C0 j
-V2 is used in long-distance communications mode.
2. The Analog I/O Terminals can be used with SRM1-C0 j
-V2 only.
3. To be marketed in the near future.
The long-distance communications mode can be used between SRM1-C0 j -V2
Master Control Units and SRT2-series Slaves only, as shown in the following diagram. High-speed mode must be used if even one SRT1-series Slave is included in the CompoBus/S system.
Master Control Unit Master Control Unit
SRM1-C0 j
-V2
SRM1-C0 j
,
SRM1-C0 j
-V1
Peripheral Devices
SRT2-series Slave SRT2-series Slave
High-speed or long-distance communications mode
High-speed communications mode only
The SRM1 can use a Programming Console or a personal computer running
CX-Programmer, SYSMAC Support Software (SSS), or SYSMAC-CPT as a Peripheral Device.
Programming Console
Programming Consoles are compact Peripheral Devices that support basic functions such as writing ladder programs and monitoring SRM1 operation.
They are useful for onsite operations.
Refer to Section 4 Using a Programming Console for details on Programming
Console operations.
SYSMAC Support Software (SSS), SYSMAC-CPT, and CX-Programmer
In addition to the basic Programming Console operations, the CX-Programmer,
SYSMAC-CPT, and SSS can be used to edit ladder programs offline, save programs to disk, and perform high-level monitoring; the CX-Programmer, SYS-
MAC-CPT and SSS functions allow the user to design more efficient ladder programs. Refer to the manuals listed on the About this Manual page for details on using them.
SYSMAC Support Software (SSS)
When using the SSS, set the PC model to the “CQM1” and observe the following restrictions.
•
Addresses will be checked according to the CQM1 address ranges, which are wider than the SRM1 address ranges. Be sure to use only the allowable addresses.
•
The CQM1 has a larger memory than the SRM1 and the amount of memory available display will not be correct. Allow for the difference between capacities.
6
Procedures From System Design to Test Operation Section 1-3
Host Computers, PTs, and
PCs
•
Instructions will be displayed that are not supported by the SRM1. Do not use these instructions.
CX-Programmer and SYSMAC-CPT
The following instructions cannot be programmed when using the CX-Programmer or SYSMAC-CPT. Errors will occur if an attempt is made to transfer them from the PC to the computer: SCL(66)/@SCL(66), ZCP, NEG/@NEG, and PID.
An SRM1(-V2) can be connected an IBM PC/AT or compatible computer or OM-
RON PT through an RS-232C Adapter (CPM1-CIF01) mounted to the SRM1’s peripheral port. (Use Host Link mode when connecting a PT through an
RS-232C Adapter.)
The RS-232C port on an SRM1-C02-V2 can be used to connect directly to an
IBM PC/AT or compatible computer, OMRON PT, or PC (C200HX/HG/HE,
C200HS, CQM1, CPM1, CPM1A, CPM2A, or CPM2C). (Use Host Link mode or
NT Link mode when connecting a PT directly.)
1-3 Procedures From System Design to Test Operation
The procedures from system design to test operation are explained in the sections of this manual as follows and in the CPM1/CPM1A/CPM2A/CPM2C/
SRM1(-V2) Programming Manual (W353):
1, 2, 3...
1. System Design
Refer to 3-1 System Design.
2. Installation
Refer to 3-3 Installing the SRM1.
3. Wiring
Refer to 3-4 Wiring and Connections.
4. Creating the Ladder Program
Refer to the relevant sections in the CPM1/CPM1A/CPM2A/CPM2C/
SRM1(-V2) Programming Manual (W353) and the applicable PC manual.
5. Inputting the Program
Refer to Section 4 Using the Programming Console, Section 5 Test Runs
and Error Processing, CX-Programmer Users Manual (W346), SYSMAC
Support Software (SSS) Operation Manuals (W247 and W248), and SYS-
MAC-CPT Support Software Quick Start Guide (W332) and User Manual
(W333).
6. Test Operation
Refer to 5-1-2 SRM1 Test Run Procedure.
7
I/O and Data Area Allocations Section 1-4
1-4 I/O and Data Area Allocations
1-4-1 I/O Allocations
The input bits of SRM1 words 000 to 007, and the output bits of words 010 to 017, are allocated to the CompoBus/S Slave. These allocations are shown in the following table.
I/O Word address Bits
Inputs
Outputs
005
006
007
010
011
012
000
001
002
003
004
013
014
015
016
017
15 to 08
IN1
IN3
IN5
IN7
IN9
IN11
IN13
IN15
OUT1
OUT3
OUT5
OUT7
OUT9
OUT11
OUT13
OUT15
07 to 00
IN0
IN2
IN4
IN6
IN8
IN10
IN12
IN14
OUT0
OUT2
OUT4
OUT6
OUT8
OUT10
OUT12
OUT14
IN0 to IN15 are Input Slave node numbers, and OUT0 to OUT15 are Output
Slave node numbers.
If the maximum number of CompoBus/S devices is set to 16, then IN8 to IN15 and OUT8 to OUT15 can be used as work bits.
Words IR 008, IR 009, IR 018, and IR 019 can be used as work words.
The bits for two node number are allocated to 16-point Slaves so that all bits are in the same word. If an even node address is set, the node address that is set and the next node address following it will be used. For example, if node address
6 is set for a 16-point Output Slave, bits for node addresses OUT6 and OUT7 will be used. If an odd node address is set, the node address that is set and the previous node address will be used. For example, if node address 3 is set for a
16-point Output Slave, bits for node addresses OUT2 and OUT3 will be used.
All of the bits for one node address are allocated to a 4-point Slave. If an even numbered node address is set, bits 00 to 03 are used and bits 04 to 07 are not used. If an odd numbered node address is set, bits 8 to 11 are used and bits 12 to
15 are not used.
8
I/O and Data Area Allocations Section 1-4
Analog Terminals are allocated from 16 to 64 bits per Terminals as shown in the following table. If an allocation is not completely within the input or output area, communications will not be possible and the COMM indicator will not be lit.
I/O bits allocated
64 bits
(SRT2-AD04, 4 analog inputs)
48 bits
(SRT2-AD04, 3 analog inputs)
32 bits
(SRT2-AD04, 2 analog inputs)
(SRT2-DA02, 2 analog outputs)
16 bits
(SRT2-AD04, 1 analog input)
(SRT2-DA02, 1 analog output)
Node address setting
Even
Odd
Even
Odd
Even
Odd
Even
Odd
Node addresses used
Set address to set address + 7
Set address – 1 to set address + 6
Set address to set address + 5
Set address – 1 to set address + 4
Set address to set address + 3
Set address – 1 to set address + 2
Set address to set address + 1
Set address – 1 to set address
Address setting range
0 to 9
0 to 11
0 to 13
0 to 15
Examples
If node address 3 is set for the SRT2-DA02 and 2 analog outputs are used, 32 bits are allocated from OUT2 to OUT5.
If node address 10 is set for the SRT2-AD04 and 4 analog inputs are used, the allocated area would exceed the output area available for allocation and communications would not be possible.
1-4-2 Data Area Allocation
The relationships between the data areas and words that can be used by the
SRM1 are shown in the following table. For details, refer to the CPM1/CPM1A/
CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353).
Name
Input bits
Output bits
Work bits
SR area
HR area
AR area
LR area
DM area (Read/Write)
DM area (Read Only)
DM area (PC Setup)
TR area
TIM/CNT area
Number of words or bits
8 words
8 words
44 words
(See note 1.)
16 words
20 words
16 words
16 words
2,022 words
456 words
56 words
8 bits
128 bits
Word addresses
IR 000 to IR 007
IR 010 to IR 017
IR 008 and IR 009,
IR 018 and IR 019,
IR 200 to IR 239
IR 240 to IR 255
HR 00 to HR 19
AR 10 to AR 15
(See note 2.)
LR 00 to LR 15
DM 0000 to DM 2021
DM 6144 to DM 6599
DM 6600 to DM 6655
TR 0 to TR 7
TIM/CNT 000 to 127
Note 1. When the CompoBus/S system is used in 128-bit mode, IR 004 to IR 007 and IR 014 to IR 017 can be used as work words.
2. AR 04 to AR 07 are used for Slave status.
9
SECTION 2
Specifications and Components
This section provides the technical specifications of the SRM1(-V2) and describes its main components.
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 CompoBus/S Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
12
13
14
15
11
Specifications Section 2-1
2-1 Specifications
2-1-1 General Specifications
Supply voltage
Item
Allowable supply voltage
Power consumption
Inrush current
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Absolute humidity
Atmosphere
Terminal screw size
Power interrupt time
Weight
SRM1-C01/C02-V2
24 VDC
20.4 to 26.4 VDC
3.5 W max.
5.0 A max. (pulse width: 15 ms max.)
Conforms to IEC61000-4-4; 2 kV (power lines)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s 2 in X, Y, and
Z directions for 80 minutes each
(Time coefficient; 8 minutes
×
coefficient factor 10 = total time 80 minutes)
147 m/s 2 three times each in X, Y, and Z directions
Operating: 0
°
C to 55
°
C
Storage: –20
°
C to 75
°
C
10% to 90% (with no condensation)
Must be free from corrosive gas.
M3
DC type: 2 ms min.
150 g max.
12
Specifications Section 2-1
2-1-2 Characteristics
Control method
Item
I/O control method
Programming language
Instruction length
Types of instructions
Execution time
Program capacity
Maximum number of I/O points
Input bits
Output bits
Work bits
Special bits (SR area)
Temporary bits (TR area)
Holding bits (HR area)
Auxiliary bits (AR area)
Link bits (LR area)
Timers/Counters
Data memory
Interval timer interrupts
Memory protection
Memory backup
Self-diagnostic functions
Program checks
Peripheral port
RS-232C Port
SRM1-C01/C02-V2
Stored program method
Cyclic scan method
Ladder diagram
1 step per instruction, 1 to 5 words per instruction
Basic instructions:
Special instructions:
Basic instructions:
Special instructions:
14
81 instructions, 125 variations
0.97
µ s (LD instruction)
9.1
µ s (MOV instruction)
4,096 words
256 points
00000 to 00715 (Words not used as input words can be used as work words.)
01000 to 01715 (Bits not used as output bits can be used as work bits.)
704 bits: 00800 to 00915 (Words IR 008 and IR 009)
01800 to 01915 (Words IR 018 and IR 019)
20000 to 23915 (Words IR 200 to IR 239)
248 bits: 24000 to 25507 (Words IR 240 to IR 255)
8 bits (TR0 to TR7)
320 bits: HR 0000 to HR 1915 (Words HR 00 to HR 19)
256 bits: AR 0000 to AR 1515 (Words AR 00 to AR 15)
256 bits: LR 0000 to LR 1515 (Words LR 00 to LR 15)
128 timers/counters (TIM/CNT 000 to TIM/CNT 127)
100-ms timers: TIM 000 to TIM 127
10-ms timers (high-speed counter): TIM 000 to TIM 003
Decrementing counters and reversible counters
(Note: TIMH(15) will not time reliably if the cycle time is over 10 ms and timer numbers TIM 004 to TIM 127 are used.)
Read/Write: 2,022 words (DM 0000 to DM 2021)
Read-only: 512 words (DM 6144 to DM 6655)
One-shot mode/Scheduled interrupt mode, one bit (0.5 to 319,968 ms)
HR, AR, and DM area contents; and counter values maintained during power interruptions.
Flash memory:
The program and read-only DM area are backed up without a battery.
Lithium battery backup:
The read/write DM area, HR area, AR area, and counter values are backed up by the lithium battery whose service life extends over ten years under an ambient temperature of 25 _ C.
(Note: The lifetime of the lithium battery capacity depends on the ambient temperature. Refer to the descriptions on the next page.)
CPU Unit failure (watchdog timer), memory check, communications errors, setting errors
No END instruction, programming errors (continuously checked during operation)
One point; tool connection, Host Link, no protocol
One point (SRM1-C02-V2 only); Host Link, 1:1 NT Link, 1:N NT Link, 1:1 PC Link, no protocol
13
Specifications Section 2-1
Backup Time vs. Temperature A lithium battery in the CPU Unit is used to back up the contents in the user program area, the READ/WRITE area in the Data Memory (DM), Hold Relay (HR), the Auxiliary Memory Relay (AR), and in the data area of the Counter (CNT). The deterioration of the lithium battery capacity depends on the ambient temperature. The standard service life is 12 years under an ambient temperature of 40 _ C when operating 8 hours a day.
If the power supply is interrupted after the lithium battery capacity has deteriorated, the contents in the user program area, the READ/WRITE area in the Data
Memory (DM), Hold Relay (HR), Auxiliary Memory Relay (AR), and in the data area of the Counter (CNT) may be lost. Even if the contents of the CPU Unit’s program area are lost, however, the user program and DM read-only contents
(including the one in the PC Setup area) stored in flash memory will be read to the CPU Unit’s user program area when the SRM1 is next started up.
2-1-3 CompoBus/S Communications Specifications
Item
Communications method
Transmission method
Baud rate High-speed communications mode
Long-distance communications mode
Modulation method
Code method
Maximum number of connectible terminals
Number of points per frame
Communications High-speed cycle time communications mode
Long-distance communications mode
Communications function
Error control checks
Communications distance
Cable
High-speed communications mode
Long-distance communications mode
Vinyl-clad VCTF
JIS C 3306
Flat cable
14
CompoBus special protocol
Multi-drop, T-branch
750 kbps
Specifications
93.75 kbps
Baseband method
Manchester coding method
32: 16 IN and 16 OUT
16: 8 IN and 8 OUT
256 (128 IN and 128 OUT), when maximum number of connectible terminals is 32.
128 (64 IN and 64 OUT), when maximum number of connectible terminals is
16.
0.8 ms, when maximum number of terminals is set to 32.
0.5 ms, when maximum number of terminals is set to 16.
6.0 ms, when maximum number of terminals is set to 32.
4.0 ms, when maximum number of terminals is set to 16.
Cyclic transfer only (no message communications)
Manchester code check, frame length check, parity check, two-transfer comparison
Main line length: 100 m max.
Branch line length: 3 m max.
Total branch line length: 50 m max.
Main line length: 500 m max.
Branch line length: 6 m max.
Total branch line length: 120 m max.
Two 0.75 mm 2 conductors (2 signal wires)
Four 0.75 mm
2
conductors (2 signal wires and 2 power supply wires)
Unit Components
2-2 Unit Components
SRM1-C01-V2
4. CPU Unit status indicators
5. CompoBus/S communications status indicators
6. Peripheral/RS-232C port communications status indicators
Section 2-2
2. Peripheral port
Connector cover
SRM1-C02-V2
4. CPU Unit status indicators
5. CompoBus/S communications status indicators
6. Peripheral/RS-232C Port communications status indicators
1. Terminal block
2. Peripheral port
Connector cover
3. RS-232C Port
1) Terminal Block
2) Peripheral Port
3) RS-232C Port
1. Terminal block
These terminals connect the power supply (24 V) and the CompoBus/S transmission path. For details regarding power supply wiring, refer to 3-4-2 Power
Supply Wiring.
The Peripheral Port connects the programming tool or an RS-232C or RS-422 adapter. Be sure to use the correct cable.
The RS-232C Port connects to an RS-232C interface such as a personal computer or an OMRON PT. For details, refer to 3-4-4 RS-232C Port Wiring.
15
Unit Components
4, 5, 6) Indicators
Section 2-2
There are three types of LED indicators: CPU Unit status indicators, CompoBus/
S communications status indicators, and peripheral/RS-232C Port communications status indicators. These indicate the status of various Units, as shown in the following table.
Indicator
PWR (Green)
RUN (Green)
ERR (Red)
SD (Yellow)
RD (Yellow)
ERC (Red)
Display
ON
OFF
ON
OFF
ON
Flashing
OFF
ON
OFF
ON
OFF
ON
OFF
COMM (Yellow) Flashing
OFF
Status
Power is being supplied.
Power is not being supplied.
In RUN mode or MONITOR mode
In PROGRAM mode or fatal error has occurred.
Fatal error has occurred.
Non-fatal error has occurred.
Normal operation
CompoBus/S data is being sent.
Data is not being sent.
CompoBus/S data is being received.
Data is not being received.
A CompoBus/S communications error has occurred.
Normal operation
Data is being sent or received at the Peripheral
Port or RS-232C Port.
Data is not being sent or received.
16
SECTION 3
Installation and Wiring
This section explains how to install and wire the SRM1(-V2). Be sure to follow the instructions contained here concerning the control panel, power supply, CompoBus/S transmissions, and RS-232C Port wiring. For details regarding the wiring of CompoBus/S Terminal transmission paths and I/O, refer to the CompoBus/S Operation Manual (W266).
3-1 System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-1 Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-2 Interlock and Limit Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-3 Power Supply Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Selecting an Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Installation Site Conditions
3-2-2 Panel/Cabinet Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Installing the SRM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-1 Surface Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-2 DIN Track Installation
3-4 Wiring and Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-1 General Precautions for Wiring
3-4-2 Power Supply Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-3 CompoBus/S Transmission Line Wiring
3-4-4 RS-232C Port Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-5 Host Link Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 One-to-one NT Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6 One-to-N NT Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 One-to-one PC Link Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7-1 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7-2 Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7-3 Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7-4 PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
30
31
31
23
24
26
32
32
32
20
21
21
23
19
19
20
20
18
18
18
18
19
17
System Design Section 3-1
3-1 System Design
Take the points covered in this section into consideration when designing the system.
3-1-1 Power Supply Wiring
Separate the power supply wiring from the control system, SRM1 system, and
DC I/O system wiring.
3-1-2 Interlock and Limit Circuits
Construct an external interlock circuit if SRM1 outputs are used to perform reciprocal operations such as controlling the forward and reverse operation of a motor or if incorrect SRM1 operation could cause accidents or mechanical damage.
Also, construct an external limit circuit to prevent run-away movement in operations such as position control.
The following diagram shows an example of an interlock circuit.
SRM1
CompoBus/S transmission path
Interlock Circuit
01005
MC2
MC1 Motor forward
Slave
01006
MC1
MC2 Motor reverse
In the interlock circuit above, MC1 and MC2 cannot be ON at the same time even if SRM1 outputs 01005 and 01006 are both ON at the same time (an incorrect operation).
3-1-3 Power Supply Sequence
Time Up to the Start of Operation
The time from when the power supply is turned on to when the operation starts varies depending on the operation conditions such as power supply voltage, configuration, ambient temperature, etc. The minimum time is approximately
500 ms and the maximum is approximately 1.1 s.
Momentary Power Failure Detection
A momentary power failure (i.e., a voltage drop to less than 85% of the rated voltage) lasting less than 2 ms is not detected and the SRM1 continues to operate.
A momentary power failure lasting longer than 2 ms may cause the SRM1 to stop operation. If this occurs, operation will be automatically resumed when the rated voltage again rises above 85%.
Note The SRM1 may repeat stop/start operations if the supply voltage of less than
85% of the rated value gradually goes up or down. If this affects the equipment, etc., provide a protection circuit which shuts off the output if the supply voltage is not above the rated value.
The output status of Slaves when the SRM1 is stopped can be set on the Slave side either to have the ON/OFF status directly prior to the stop retained or to have all outputs turned OFF.
18
Selecting an Installation Site Section 3-2
3-2 Selecting an Installation Site
The SRM1 is resistant to harsh conditions and highly reliable, but installing it in a favorable site will maximize its reliability and operating lifetime.
3-2-1 Installation Site Conditions
Avoid installing the SRM1 in a site with any of the following conditions.
•
Where the SRM1 is exposed to direct sunlight.
•
Where the ambient temperature is below 0
°
C or over 55
°
C.
•
Where the SRM1 may be affected by condensation due to radical temperature changes.
•
Where the ambient humidity is below 10% or over 90%.
•
Where there is any corrosive or inflammable gas.
•
Where there is excessive dust, saline air, or metal powder.
•
Where the SRM1 is affected by vibration or shock.
•
Where any water, oil, or chemical may splash on the SRM1.
Be sure that the conditions at the installation site conform to the SRM1’s general specifications. Refer to 2-1-1 General Specifications for details.
3-2-2 Panel/Cabinet Installation
Overheating
Consider PC operation, maintenance, and surrounding conditions when installing the SRM1 in a panel or cabinet.
The operating temperature range for the SRM1 is 0
_
C to 55
_
C. Be sure that there is adequate ventilation for cooling.
•
Allow enough space for air circulation.
•
Do not install the SRM1 above equipment that generates a large amount of heat, such as heaters, transformers, or large resistors.
•
Install a cooling fan or system when the ambient temperature exceeds 55
_
C.
Control panel
Fan
Electrical Noise
SRM1
Air vent
Power lines and high-voltage equipment can cause electrical noise in the PC.
•
Do not install the SRM1 in a panel or cabinet with high-voltage equipment.
•
Allow at least 200 mm between the SRM1 and nearby power lines.
200 mm min.
Power lines
SRM1
200 mm min.
19
Installing the SRM1
Accessibility
Section 3-3
Ensure that the SRM1 can be accessed for normal operation and maintenance.
•
Provide a clear path to the SRM1 for operation and maintenance. High-voltage equipment or power lines could be dangerous if they are in the way during routine operations.
•
The SRM1 will be easiest to access if the panel or cabinet is installed about 3 to
5 feet off of the floor.
3-3 Installing the SRM1
The SRM1 can be installed on a horizontal surface or on a DIN track.
3-3-1 Surface Installation
Use the following pattern when installing an SRM1 on a horizontal surface.
Two M4 or two 4.2 dia.
(Unit: mm, with tolerance of
±
0.2 mm)
30
3-3-2 DIN Track Installation
The SRM1 can be installed on a 35-mm DIN track.
DIN Track
PFP-100N (1 m)
PFP-50N (50 cm)
End Plates
(PFP-M)
20
Wiring and Connections Section 3-4
Installation
Lower the SRM1 so that the notch on the back of the Unit catches the top of the
DIN Track. Push the Unit forward until the lock snaps into place.
Removal
Pry the lock down with a standard screwdriver and pivot the Unit upward to remove it.
Screwdriver
3-4 Wiring and Connections
3-4-1 General Precautions for Wiring
I/O Line Noise To avoid noise, do not run CompoBus/S transmission lines in the same duct or conduit as power lines.
Hanging Ducts
Leave at least 300 mm between the ducts, as shown in the following diagram.
CompoBus/S transmission lines
Control cables and
SRM1 power lines
Power cables
300 mm min.
300 mm min.
21
Wiring and Connections Section 3-4
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown in the following diagram.
CompoBus/S transmission lines
Control cables and
SRM1 power lines Power cables
Metal plate (iron)
200 mm min.
Conduit
Separate the CompoBus/S transmission lines, power and control lines, and power cables, as shown in the following diagram.
CompoBus/S transmission lines
Control cables and
SRM1 power lines Power cables
Terminal Connections
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉ
Always use crimp connectors for the SRM1’s power lines and transmission lines.
Use M3 terminal screws and tighten the screws securely (to a torque of
0.48 N
S
m).
Recommended Terminals: Use the terminals shown below.
Fork terminal
Round terminal
6.0 mm max.
6.0 mm max.
22
Wiring and Connections Section 3-4
3-4-2 Power Supply Wiring
Applicable Power Supply Use a power supply that conforms to specifications of at least 24 VDC and 3.5 W.
OMRON’s S82K-00724 is recommended (input: 100 VAC; output: 24 VDC,
7.5 W).
Note The above power supply is for a case where the CompoBus/S Slave is separated from the power supply. Refer to the CompoBus/S Operation Manual
(W266) when supplying power to the whole system including the Slave.
Wiring Connections Wire the power supply as shown in the following diagram.
+
24 VDC
Note Be sure to ground the ground terminal of the power supply.
3-4-3 CompoBus/S Transmission Line Wiring
Applicable Cable Be sure to use the specified cable, and do not mix flat cable and VCTF cable.
Cable
Special-purpose flat cable
VCTF cable
Model number
XBIT-W10
---
Specifications
4-conductor flat cable:
0.75 mm 2
2-conductor Vinyl-clad
VCTF JIS C3306
VCTF 0.75x2C
23
Wiring and Connections
Wiring Connections
Section 3-4
Wire the CompoBus/S transmission lines as shown in the following diagram.
Slave terminal block
BD
H
BD
L
BD H
BD L
3-4-4 RS-232C Port Wiring
Connector Pin Arrangement The following diagram shows the connector pin arrangement for the RS-232C port, i.e., the SRM1 (SRM1-C02-V2) and RS-232C Adapter (CPM1-CIF01).
RD
1
SD 2
3
RS
CS
4
5
6
7
8
9 SG
Cable Connections The following diagrams show the communications cable connections between the RS-232C port, i.e., the SRM1 (SRM1-C02-V2) and RS-232C Adapter
(CPM1-CIF01), and the various external devices.
Signal
CD
RD
SD
ER
SG
DR
RS
CS
CI
IBM PC/AT or
Compatible
Computer
8
9
6
7
Pin No.
1
4
5
2
3
RS-232C Port
Pin No.
1
4
5
2
3
6
7
8
Hood
Signal
–
SD
RD
RS
CS
–
–
–
SG
24
Wiring and Connections
OMRON PT or PC*
Signal
–
SD
RD
RS
CS
–
–
–
SG
Pin No.
1
2
3
4
5
6
7
8
9
RS-232C Port
Pin No.
1
2
3
4
5
6
7
8
Hood
Signal
–
SD
RD
RS
CS
–
–
–
SG
*Host Link or NT Link with an OMRON PT, or 1:1 PC Link with a SYS-
MAC C200HX/HE/HG/HS, CQM1, or CPM1 Programmable Controller.
Section 3-4
(Recommended Cables)
XW2Z-200T: 2 m
XW2Z-500T: 5 m
3G2A9-AL004-E
Link Adapter
Signal
FG
SD
RD
RS
CS
DR
SG
–
–
6
7
4
5
Pin No.
1
2
3
8
9
ER 20
1:1 Connection
RS-232C Port
6
7
4
5
Pin No.
1
2
3
8
Hood
Signal
–
SD
RD
RS
CS
–
–
–
SG
Signal
FG
SD
RD
RS
CS
DR
SG
–
–
3G2A9-AL004-E
Link Adapter
8
9
6
7
Pin No.
1
2
3
4
5
ER 20
1:N Connection
RS-232C Port
Pin No.
1
2
3
4
5
6
7
8
Hood
Signal
–
SD
RD
RS
CS
–
–
–
SG
25
Wiring and Connections
Ribbon line
(red)
Ribbon line
(black)
Signal
–
RD
SD
RS
CS
–
–
–
SG
NT-AL001
Pin No.
1
2
3
4
5
6
7
8
9
1:1 Connection
RS-232C Port
Pin No.
1
2
3
4
5
6
7
8
Hood
Signal
–
SD
RD
RS
CS
–
–
–
SG
Section 3-4
Ribbon line
(red)
Ribbon line
(black)
Signal
–
RD
SD
RS
CS
–
–
–
SG
NT-AL001
Pin No.
1
2
3
4
5
6
7
8
9
1:N Connection
RS-232C Port
Pin No.
1
2
3
4
5
6
7
8
Hood
Signal
–
SD
RD
RS
CS
–
–
–
SG
3-4-5 Host Link Connections
Host Link is a command/response communications system in which commands are transmitted from the host computer and corresponding responses are returned from the destination SRM1. Host Link commands can be used to read/ write data in SRM1 data areas and read/write settings. Either the peripheral port or RS-232C port can be used.
SRM1
Host Link computer
Command
Response
Note For details on PC Setup settings, refer to 1-1 PC Setup or 4-4-1 Host Link Com-
munications) in the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming
Manual (W353).
26
Wiring and Connections
One-to-one Host Link
Connection
Section 3-4
The SRM1 can be connected to an IBM PC/AT or compatible computer or a Programmable Terminal, as shown in the following diagram.
IBM PC/AT or compatible computer
PT
SRM1 SRM1
One-to-one Host Link Cables The cables differ depending on whether the peripheral port or RS-232C port is used.
Peripheral Port Connection
SRM1
OMRON PT
WX2Z-200T
WX2Z-500T
RS-232C Adapter
CPM1-CIF01
IBM PC/AT or compatible computer
CQM1-CIF02
Note Set the RS-232C Adapter mode setting switch to “HOST.”
27
Wiring and Connections
RS-232C Port Connection
Section 3-4
SRM1
OMRON PT
WX2Z-200T
WX2Z-500T
IBM PC/AT or compatible computer
Note For details regarding RS-232C connections, refer to 3-4-4 RS-232C Port Wiring.
One-to-N Host Link Connection
IBM PC/AT or compatible computer
Link Adapter
3G2A9-AL004-E
NT-AL001 SRM1 RS-422
Adapter
SRM1
28
Wiring and Connections Section 3-4
One-to-N Host Link Cables Up to 32 SRM1s can be connected to the computer via the peripheral port or
RS-232C port.
IBM PC/AT or compatible computer
Link Adapter
3G2A9-AL004-E
Signal
RDB
–
SG
–
SDB
RDA
FG
–
SDA
D-sub 9-pin
Pin No.
1
2
3
4
5
6
7
8
9
Make a straight RS-232C cable connection between the 3G2A9-AL004-E
Link Adapter the personal computer, and match each SD, RD, and SG.
SRM1
NT-AL001
Connecting Cables
(Refer to page 26.)
RS-422 Adapter
CPM1-CIF11
SRM1
Note 1. The maximum total length of the RS-422 cable is 500 meters.
2. Turn ON the termination resistance switches for only the Link Adapters or
RS-422 Adapters at both ends of the Host Link network.
3. Crimp-type terminals must be used for Link Adapter and RS-422 Adapter terminal wiring. For details, refer to 3-4-1 General Precautions for Wiring.
29
One-to-N NT Link Section 3-6
3-5 One-to-one NT Link
High-speed communications can be achieved by providing a direct access through the use of the 1:1 NT Link between the SRM1 and Programmable Terminal (PT). The RS-232C port can be used for NT Link. A 1:1 NT Link is only possible with a Master Control Unit that has an RS-232C port (SRM1-C02,
SRM1-C02-V1, or SRM1-C02-V2).
SRM1
Programmable Terminal
NT Link Cable Connections The SRM1 can be connected to a PT via the RS-232C port, as shown in the following illustration. For details regarding RS-232C connections, refer to 3-4-4
RS-232C Port Wiring.
SRM1
Programmable Terminal
XW2Z-200T
XW2Z-500T
PC Setup Settings Set the RS-232C port’s communications mode to 1:1 NT Link in DM 6645 in the
PC Setup. For details, refer to 1-1 PC Setup or 4-4-3 One-to-one NT Link Com-
munications in the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming
Manual (W353).
3-6 One-to-N NT Link
The 1:N NT Link allows an SRM1-C02-V2 PC to be connected to as many as 8
OMRON Programmable Terminals (PTs) and direct access provides high-speed communications. The RS-232C port is used to make the 1:N NT Link.
SRM1
OMRON PT
30
One-to-one PC Link Connections
Cable Connections
Section 3-7
The 1:N NT Link is possible only with the SRM1-C02-V2 PCs, which have an
RS-232C port.
The SRM1 can be connected to OMRON PTs via the RS-232C port, as shown in the following illustration. OMRON PTs that support the 1:N NT Link must be used.
SRM1
Programmable Terminals
RS-422
NT-AL001
Adapter
Connecting Cable
PC Setup Settings
Note 1. For details on RS-422A connections, refer to the Programmable Terminal’s
Operation Manual.
2. For details on RS-232C connections, refer to 3-4-4 RS-232C Port Wiring.
Set the RS-232C port’s communications mode to 1:N NT Link in DM 6645 in the
PC Setup. For details, refer to 1-1 PC Setup or 4-4-4 One-to-N NT Link Commu-
nications in the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming
Manual (W353).
3-7 One-to-one PC Link Connections
3-7-1 Basics
An SRM1 can be linked one-to-one to an SRM1, CQM1, CPM1, CPM1A,
CPM2A, CPM2C, C200HS, or C200HX/HE/HG PC. One PC acts as the Master and the other as the Slave to link up to 256 bits in the LR area (LR 0000 to LR
1515). In the following example, an SRM1 is linked one-to-one to another SRM1.
SRM1 SRM1
WRITE
READ
LR 00
LR 07
LR 08
Link bits
WRITE area
READ area
LR 15
RS-232C Port RS-232C Port
Link bits
READ area
LR 00
LR 07
LR 08
WRITE area
LR 15
READ
WRITE
31
One-to-one PC Link Connections Section 3-7
3-7-2 Restrictions
•
Only the SRM1-C02-V2, which has an RS-232C port, can be used for a 1:1 PC
Link.
•
The only SRM1 words that can be used for link relay are the 16 words from
LR 00 to LR 15. Therefore, these words must also be used at the CQM1 or
C200HX/HE/HG/HS when linking any of these PCs one-to-one with an SRM1.
It is not possible for words LR 16 to LR 63 to be linked one-to-one with an
SRM1.
3-7-3 Cable Connections
Use RS-232C cable to connect an SRM1 with another SRM1, CQM1, CPM1,
CPM1A, CPM2A, CPM2C, C200HS, or C200HX/HE/HG Programmable Controller.
SRM1
XW2Z-200T
XW2Z-500T
RS-232C Port
RS-232C Port
CQM1
C200HX/HG/HE/HS
CPM1 + RS-232C Adapter
Note For details regarding RS-232C connections, refer to 3-4-4 RS-232C Port Wiring.
3-7-4 PC Setup Settings
Set the RS-232C port’s communications mode to 1:1 PC Link (Slave) or 1:1 PC
Link (Master) in DM 6645 in the PC Setup. For details, refer to 1-1 PC Setup or
4-4-5 One-to-one PC Link Communications in the CPM1/CPM1A/CPM2A/
CPM2C/SRM1(-V2) Programming Manual (W353).
32
SECTION 4
Using the Programming Console
This section explains how to use the Programming Console. Be sure to read this section carefully if you are not already familiar with Programming Console operations.
4-1 Basic Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Compatible Programming Consoles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Connecting the Programming Console
4-1-3 Changing the SRM1’s Mode
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-2 Clearing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-3 Reading/Clearing Error Messages
4-2-4 Buzzer Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-5 Reading UM Area Information
4-2-6 Setting Expansion Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-7 Setting and Reading a Program Memory Address and Monitoring I/O Bit Status
4-2-8 Instruction Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-9 Bit Operand Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-10 Inserting and Deleting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-11 Entering or Editing Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-12 Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-13 Bit, Digit, Word Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-14 Differentiation Monitor
4-2-15 Binary Monitor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-16 Three-Word Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-17 Signed Decimal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-18 Unsigned Decimal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-19 Three-Word Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-20 Changing Timer, Counter SV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-21 Hexadecimal, BCD Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-22 Binary Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-23 Signed Decimal Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-24 Unsigned Decimal Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-25 Force Set, Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-26 Clear Force Set/Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-27 Hex-ASCII Display Change
4-2-28 Displaying the Cycle Time
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52
53
54
50
51
51
52
47
47
49
50
42
43
44
55
56
56
57
57
58
40
40
41
41
36
37
38
39
34
34
35
35
36
33
Basic Operations Section 4-1
4-1 Basic Operations
This section provides information on connecting and using a Programming Console. Refer to 5-5 Programming Console Operation Errors for details on errors that might occur during Programming Console operations.
4-1-1 Compatible Programming Consoles
There are two Programming Consoles that can be used with the SRM1: the
CQM1-PRO01-E and the C200H-PRO27-E. The key functions for these Programming Consoles are identical.
Press and hold the Shift Key to input a letter shown in the upper-left corner of the key or the upper function of a key that has two functions. For example, the
CQM1-PRO01-E’s AR/HR key can specify either the AR or HR Area; press and release the Shift Key and then press the AR/HR Key to specify the AR Area.
CQM1-PRO01-E
(A 2-m connecting cable is attached.)
C200H-PRO27-E
(Use a C200H-CN222 (2 m) or C200H-
CN422 (4 m) Connecting Cable.)
LCD display
Mode selector
SRM1 operating mode
Instruction keys
Numeric keys
Operation keys
The following keys are labeled differently on the CQM1-PRO01-E and the
C200H-PRO27-E, but the operation of the keys in each pair is identical.
C200H-PRO27-E Keys CQM1-PRO01-E Keys
AR
HR
HR
SET
PLAY
SET
RESET
REC
RESET
34
Basic Operations Section 4-1
4-1-2 Connecting the Programming Console
Connect the Programming Console’s connecting cable to the SRM1’s peripheral port, as shown below.
Panel Installation The C200H-PRO27-E Programming Console can be installed in a control panel as shown in the following diagram. (The C200H-ATT01 Mounting Bracket is sold separately.)
Mounting Bracket
Mounting hole dimensions
(DIN43700 standards)
Two screws
186
+1.1
–0
92
+0.8
–0
Panel thickness: 1.0 to 3.2 mm
Allow at least 80 mm for the cable connector above the Programming Console.
37
15
At least 80 mm is required.
Either connector may be used.
About 70 mm is required.
4-1-3 Changing the SRM1’s Mode
Once the Programming Console has been connected, its mode switch can be used to change the SRM1’s PC mode. The mode display (<PROGRAM>,
<MONITOR>, or <RUN>) will appear on the Programming Console screen.
•
No key operations can be performed while the mode display is displayed on the Programming Console screen. Press CLR to clear the display so that key operations can be performed.
•
If the SHIFT Key is pressed while the mode switch is turned, the original display will remain on the Programming Console’s screen and the mode display won’t appear.
35
Programming Console Operations Section 4-2
MONITOR
RUN PROGRAM
•
The SRM1 will enter RUN mode automatically if a Peripheral Device such as a
Programming Console isn’t connected when the SRM1 is turned on (when
DM 6600 is #0000).
MONITOR
RUN PROGRAM
MONITOR
RUN PROGRAM
Mode display
<PROGRAM> BZ <MONITOR> BZ <RUN> BZ
CLR
Operation
Initial display
00000
Operation
SHIFT CLR
PROGRAM Mode
MONITOR Mode
RUN Mode
The SRM1 program isn’t executed in PROGRAM mode. Use PROGRAM mode to create and edit the program, clear memory, or check the program for errors.
The SRM1 program is executed in MONITOR mode and I/O is processed just as it is in RUN mode. Use MONITOR mode when testing the system by monitoring the SRM1’s operating status, force-setting and resetting I/O bits, changing the
SV/PV of timers and counters, etc.
This is the SRM1’s normal operating mode. The SRM1’s operating status can be monitored from a Peripheral Device, but bits can’t be force-set/force-reset and the SV/PV of timers and counters can’t be changed.
!
Caution Be sure to check the system thoroughly before executing the SRM1 program to prevent any accidents that might occur when the program is first started.
4-2 Programming Console Operations
4-2-1 Overview
Name
Clearing memory
Reading/clearing error messages
Buzzer operation
Reading UM area information
Setting an expansion instruction
Setting a program memory address
The following table lists the programming and monitoring operations that can be performed from a Programming Console. Refer to the rest of this section for details on operational procedures.
Function
Clears all or part of the Program Memory and any data areas that are not read-only, as well as the contents of the Programming Console’s memory.
Displays and clears error messages and displays MESSAGE instruction messages.
Turns on and off the buzzer that sounds when Programming Console keys are pressed.
Reads the state of area setting and capacity in the user memory.
Reads and sets the function code assignment of an expansion instruction.
Sets the specified program memory address when reading, writing, inserting and deleting programs.
36
Programming Console Operations Section 4-2
Name
Reading a program memory address
Instruction search
Bit operand search
Function
Reads the contents of the Program Memory. Displays the status of the currently displayed bit in PROGRAM and MONITOR modes.
Finds occurrences of the specified instruction in the program.
Finds occurrences of the specified operand bit in the program.
Inserting and deleting instructions
Entering or editing programs
Inserts or deletes instructions from the program.
Overwrites the contents of the current Program Memory to either input a program for the first time or to change a program that already exists.
Checking the program Checks for programming errors and displays the program address and error when errors are found.
Bit, digit, word monitor Monitors the status of up to 16 bits and words, although only 3 can be shown on the display at one time.
Multiple address monitor
Monitors the status of up to 6 bits and words simultaneously.
Differentiation monitor Monitors the up or down differentiation status of a particular bit.
Binary monitor
3-word monitor
Monitors the ON/OFF status of any word’s 16 bits.
Monitors the status of three consecutive words.
Converts the contents of the specified word from signed hexadecimal (two’s complement format) to signed decimal for display.
Converts hexadecimal data in a word to unsigned decimal for display.
Signed decimal monitor
Unsigned decimal monitor
3-word data modification
Changing timer, counter SV 1
Changing timer, counter SV 2
Hexadecimal, BCD data modification
Binary data modification
Signed decimal data modification
Changes the contents of one or more of the 3 consecutive words displayed in the 3-Word
Monitor operation.
Changes the SV of a timer or counter.
Makes fine adjustment changes to the SV of the timer or counter.
Changes the BCD or hexadecimal value of a word being monitored.
Changes the status of a word’s bits when the word is being monitored.
Unsigned decimal data modification
Force set/reset
Changes the decimal value of a word being monitored as signed decimal data. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format.)
Changes the decimal value of a word being monitored as unsigned decimal data. A change into hexadecimal data is made automatically.
Forces bits ON (force set) or OFF (force reset.)
Clear force set/reset
Hex-ASCII display change
Displaying the cycle time
Restores the status of all bits which have been force set of reset.
Converts word data displays back and forth between 4-digit hexadecimal data and ASCII.
Displays the current average cycle time (scan time.)
4-2-2 Clearing Memory
This operation is used to clear all or part of the Program Memory and any data areas that are not read-only, as well as the contents of the Programming Console’s memory. This operation is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
All Clear
Before beginning to program for the first time or when installing a new program, clear all areas.
The following procedure is used to clear memory completely.
1, 2, 3...
1. Bring up the initial display by pressing the CLR key repeatedly.
37
Programming Console Operations Section 4-2
2. Press the SET, NOT, and then the RESET Key to begin the operation.
SET NOT RESET
00000MEMORY CLR?
HR CNT DM
3. Press the MONTR Key to clear memory completely.
MONTR
00000MEMORY CLR
END HR DM
!
Caution The PC Setup (DM 6600 through DM 6655) will be cleared when this operation is performed.
Partial Clear It is possible to retain the data in specified areas or part of the Program Memory.
To retain the data in the HR, TC, or DM Areas, press the appropriate key after pressing SET, NOT, and RESET. Any data area that still appears on the display will be cleared when the MONTR Key is pressed.
The HR Key is used to specify both the AR and HR Areas, the CNT Key is used to specify the entire timer/counter area, and the DM Key is used to specify the DM
Area.
It is also possible to retain a portion of the Program Memory from the first memory address to a specified address. After designating the data areas to be retained, specify the first Program Memory address to be cleared. For example, input 030 to leave addresses 000 to 029 untouched, but to clear addresses from 030 to the end of Program Memory.
As an example, follow the procedure below to retain the timer/counter area and
Program Memory addresses 000 through 122:
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
3. Press the CNT Key to remove the timer/counter area from the data areas shown on the display.
CNT
00000MEMORY CLR?
HR DM
4. Press 123 to specify 123 as the starting program address.
B
1
C
2
D
3
00123MEMORY CLR?
HR DM
5. Press the MONTR Key to clear the specified regions of memory.
MONTR
00000MEMORY CLR
END HR DM
4-2-3 Reading/Clearing Error Messages
This operation is used to display and clear error messages. It is possible to display and clear non-fatal errors and MESSAGE instruction messages in any mode, but fatal errors can be displayed and cleared in PROGRAM mode only.
OK
RUN
OK
MONITOR
OK
PROGRAM
Before inputting a new program, any error messages recorded in memory should be cleared. It is assumed here that the causes of any of the errors for which error messages appear have already been taken care of. If the buzzer sounds when an attempt is made to clear an error message, eliminate the cause of the error, and then clear the error message. (Refer to Section 5 Test
Runs and Error Processing for troubleshooting information.)
38
Programming Console Operations
Key Sequence
Section 4-2
Follow the procedure below to display and clear messages.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN and then the MONTR Key to begin the operation. If there are no messages, the following display will appear:
FUN MONTR
ERR/MSG CHK OK
If there are messages, the most serious message will be displayed when the
MONTR Key is pressed. Pressing MONTR again will clear the present message and display the next most serious error message. Continue pressing
MONTR until all messages have been cleared. These are some examples of error messages:
A memory error:
MONTR
MEMORY ERR
A system error:
MONTR
SYS FAIL FAL01
A message:
MONTR
MATERIAL USED UP
All messages cleared:
MONTR
ERR/MSG CHK OK
!
Caution Check to be sure that no equipment is affected when turning the SRM1’s power supply on or off, or when entering the password. Be careful not to cause any accidents when starting or stopping SRM1 operation.
4-2-4 Buzzer Operation
This operation is used to turn on and off the buzzer that sounds when Programming Console keys are pressed. This buzzer will also sound whenever an error occurs during PC operation. Buzzer operation for errors is not affected by this setting.
This operation is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
Key Sequence Follow the procedure below to turn the key-input buzzer on and off.
1, 2, 3...
1. Press the CLR, SHIFT, and then the CLR Key to bring up the mode display.
In this case the PC is in PROGRAM mode and the buzzer is on.
<MONITOR> BZ
2. Press the SHIFT and then the 1 Key to turn off the buzzer.
39
Programming Console Operations Section 4-2
SHIFT
B
1
<MONITOR>
The buzzer will not sound when “BZ” is not displayed.
3. Press the SHIFT and then the 1 Key again to turn the buzzer back on.
<MONITOR> BZ
SHIFT
B
1
4-2-5 Reading UM Area Information
This operation is used to display the status of settings in the User Memory (UM) area, and its capacity.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
CLR
2. Press the FUN and VER Keys.
FUN VER
CM LAD
00 04.1
I/O command area size
User program area size
4-2-6 Setting Expansion Instructions
This operation is used to read and change the function codes assigned to certain instructions.
Set the expansion instructions before inputting the program. The SRM1 will not operate properly if the function codes in the program are assigned incorrectly.
When setting the expansion instructions, set the PC Setup’s DM 6602 bits 8 through 11 to “1.”
Two function codes cannot be assigned to a single instruction.
For the SRM1 expansion instruction default settings, refer to the
/CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353).
Read
Set
OK
No
RUN
OK
No
MONITOR
OK
OK
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
CLR
2. Press the EXT Key to display the settings.
EXT
INST TBL READ
FUN017:ASFT
3. Use the Up and Down Arrow Keys to scroll through the function codes and read their corresponding instructions.
↓
/
↑
INST TBL READ
FUN061:INI
40
Programming Console Operations Section 4-2
4. To change the function code assignment, press the CHG Key.
CHG
INST TBL CHG?
FUN061:INI~????
5. Use the Up and Down Arrow Keys to display the available instructions.
↓ ↑
INST TBL CHG?
FUN061:INI ~HEX
/
6. Press the WRITE Key to make the setting.
WRITE
INST TBL READ
FUN061:HEX
4-2-7 Setting and Reading a Program Memory Address and Monitoring
I/O Bit Status
This operation is used to display the specified program memory address and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
When a program is input for the first time, it is generally written to Program
Memory starting from address 000. Because this address appears when the display is cleared, it is not necessary to specify it.
When inputting a program starting from other than 000 or to read or modify a program that already exists in memory, the desired address must be designated.
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or
MONITOR mode.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
2. Input the desired address. It is not necessary to input leading zeroes.
C
2
A
0
A
0
00200
3. Press the Down Arrow Key.
↓
00200READ OFF
LD 00000
In the RUN or MONITOR mode, ON/OFF status of the bit will be displayed.
4. Press the Up and Down Arrow Keys to scroll through the program.
↓
↑
00201READ ON
AND 00001
00200READ OFF
LD 00000
4-2-8 Instruction Search
This operation is used to find occurrences of the specified instruction in the program and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
41
Programming Console Operations Section 4-2
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or
MONITOR mode.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address from which the search will begin and press the Down Arrow Key. It is not necessary to input leading zeroes.
B
1
A
0
A
0
↓
00100
TIM 001
3. Input the instruction to be found and press the SRCH Key. In this case, the search is for LD instructions.
In this case, the next LD instruction is at address 200, as shown below.
LD
SRCH
00200SRCH
LD 00000
4. Press the Down Arrow Key to display the instruction’s operands or press the
SRCH Key to search for the next occurrence of the instruction.
5. The search will continue until an END instruction or the end of Program
Memory is reached. In this case, an END instruction was reached at address 397.
Indicates the address of END instruction.
SRCH
00397SRCH
END (001)00.4KW
Indicates the amount used by the user program in units of 0.1 Kwords.
4-2-9 Bit Operand Search
This operation is used to find occurrences of the specified operand bit in the program and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
The status of any displayed bit will be shown if the PC is in RUN or MON-
ITOR mode.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the operand address. It is not necessary to input leading zeroes.
SHIFT
CONT
#
F
5
00000CONT SRCH
CONT 00005
3. Press the SRCH Key to begin the search.
SRCH
00200CONT SRCH
LD 00005
4. Press the SRCH Key to search for the next occurrence of the operand bit.
5. The search will continue until an END instruction or the end of Program
Memory is reached. In this case, an END instruction was reached.
Indicates the address of END instruction.
SRCH
00397CONT SRCH
END (001)00.4KW
Indicates the amount used by the user program in units of 0.1 Kwords.
42
Programming Console Operations Section 4-2
4-2-10 Inserting and Deleting Instructions
This operation is used to insert or delete instructions from the program. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
To demonstrate this operation, an IR 00105 NO condition will be inserted at program address 00206 and an IR 00103 NO condition deleted from address
00205, as shown in the following diagram.
Original Program
Address Instruction Operands
00100 00101 00103 00104
01000
00201 00102
Delete
00105
Insert
END(01)
Delete
00205
00206
00207
00208
AND
AND NOT
OUT
END(01)
00103
00104
01000
-
Insert
Insertion
Deletion
Follow the procedure below to insert the IR 00105 NO condition at address
00206.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address where the NO condition will be inserted and press the
Down Arrow Key. It is not necessary to input leading zeroes.
C
2
A
0 6
↓
00206READ
AND NOT 00104
3. Input the new instruction and press the INS Key.
AND
B
1
A
0
F
5 INS
00206 INSERT?
AND 00105
4. Press the Down Arrow Key to insert the new instruction.
↓
00207 INSERT END
AND NOT 00104
Note After inserting more than one word instruction, specify the set values
(operands). After inputting the set values, press the WRITE Key.
Follow the procedure below to delete the IR 00103 NO condition at address
00205.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address where the NO condition will be deleted and press the
Down Arrow Key. It is not necessary to input leading zeroes.
C
2
A
0
F
5
↓
00205READ
AND 00103
3. Press the DEL Key.
DEL
00205 DELETE?
AND 00103
4. Press the Up Arrow Key to delete the specified instruction.
If the instruction has more operands, the operands will be deleted automatically with the instruction.
↑
00205 DELETE END
AND 00105
43
Programming Console Operations Section 4-2
After completing the insertion and deletion procedures, use the Up and Down
Arrow Keys to scroll through the program and verify that it has been changed correctly, as shown in the following diagram.
Corrected Program
00100 00101 00105 00104
Address Instruction Operands
01000
00201 00102
END(01)
00205
00206
00207
00208
AND
AND NOT
OUT
END(01)
00105
00104
01000
-
4-2-11 Entering or Editing Programs
This operation is used to enter or edit programs. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
The same procedure is used to either input a program for the first time or to change a program that already exists. In either case, the current contents of
Program Memory is overwritten.
The program shown in the following diagram will be entered to demonstrate this operation.
00002
TIM 000
#0123
12.3 s
Address Instruction
00200
00201
LD
TIM
MOV(21)
#0100
LR 10
00202 MOV(21)
00203 ADB(50)
ADB(50)
#0100
#FFF6
DM 0000
IR
Operands
00002
000
#0123
LR
#0100
10
#0100
#FFF6
DM 0000
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Specify the address where the program will begin.
3. Input the address where the program will begin and press the Down Arrow
Key. It is not necessary to input leading zeroes.
C
2
A
0
A
0
↓
00200
4. Input the first instruction and operand.
LD
C
2
00200
LD 00002
44
Programming Console Operations Section 4-2
5. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00201READ
NOP (000)
If a mistake was made inputting the instruction, press the Up Arrow Key to return to the previous program address and input the instruction again. The mistaken instruction will be overwritten
6. Input the second instruction and operand. (In this case it isn’t necessary to enter the timer number, because it’s 000.) Press the WRITE Key to write the instruction to Program Memory.
TIM [Timer number] WRITE
00201 TIM DATA
#0000
7. Input the second operand (123 to specify 12.3 seconds) and press the
WRITE Key. The next program address will be displayed.
B
1
C
2
D
3 WRITE
00202READ
NOP (000)
If a mistake was made inputting the operand, press the Up Arrow Key to return to display the mistaken operand, press the CONT/# Key and 123 again.
The mistaken operand will be overwritten.
Note Counters are input in the same basic way as timers except the CNT
Key is pressed instead of the TIM Key.
8. Input the third instruction and its operands. First input the instruction by pressing the FUN Key and then the function code (21 in this case).
FUN
C
2
B
1
00202
MOV (021)
Note To input a differentiated instruction, press the NOT Key after entering the function code. The “@” symbol will be displayed next to differentiated instructions. Press the NOT Key again to change back the instruction back to a non-differentiated instruction. The “@” symbol will disappear. To change an instruction after it has been entered, simply scroll through the program until the desired instruction is displayed and press the NOT Key. The “@” symbol should be displayed next to the instruction.
9. Press the WRITE Key to write the instruction to Program Memory. The input display for the first operand will be displayed.
WRITE
00202 MOV DATA A
000
•
Writing Hexadecimal, BCD Constant
10. Input the first operand.
CONT
#
B
1
A
0
A
0
00202 MOV DATA A
#0100
Press the WRITE Key to write the instruction to Program Memory. The input display for the second operand will appear.
WRITE
00202 MOV DATA B
000
45
Programming Console Operations Section 4-2
•
Writing a Word Address
11. Input the second operand.
*EM
LR
B
1
A
0
00202 MOV DATA B
LR 10
Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00203READ
NOP (000)
Note When an instruction operand is input, the bit or word designation can be omitted.
12. Input the next instruction.
FUN
F
5
A
0
00203
ADB (050)
Press the WRITE Key to write the instruction to Program Memory.
WRITE
00203 ADB DATA A
000
•
Writing an Unsigned Decimal Number
13. The first operand is input as an unsigned integer.
CONT
#
SHIFT TR NOT
00203 ADB DATA A
#00000
Input the value of the operand from 0 to 65535.
C
2
F
5 6
00203 ADB DATA A
#00256
Note If an erroneous input is made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
14. Restore the hexadecimal display.
SHIFT TR
00203 ADB DATA A
#0100
Note If an input is made outside of the permissible range, a buzzer will sound and the hexadecimal display will not be displayed.
WRITE
00203 ADB DATA B
000
15. The second operand is input as a signed integer.
CONT
#
SHIFT TR
00203 ADB DATA B
#+00000
Input the value of the operand from –32,768 to 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
RESET
B
1
A
0
00203 ADB DATA B
#Ć00010
Note If an erroneous input is made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
46
Programming Console Operations Section 4-2
16. Restore the hexadecimal display.
SHIFT TR
00203 ADB DATA B
#FFF6
Note If an input is made outside of the permissible range, a buzzer will sound and the hexadecimal display will not be displayed.
WRITE
00203 ADB DATA C
000
17. Input the final operand and then press the WRITE Key.
EM
DM
WRITE
00203 ADB DATA C
DM 0000
00204READ
NOP (000)
4-2-12 Checking the Program
This operation checks for programming errors and displays the program address and error when errors are found. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
Error Messages
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH
00000PROG CHK
CHK LVL (0Ć2)?
3. Input the desired check level (0, 1, or 2). The program check will begin when the check level is input, and the first error found will be displayed.
A
0
00178CIRCUIT ERR
OUT 00200
Note Refer to 5-6 Programming Errors for details on check levels.
4. Press the SRCH Key to continue the search. The next error will be displayed. Continue pressing the SRCH Key to continue the search.
The search will continue until an END instruction or the end of Program
Memory is reached. A display like this will appear if the end of Program
Memory is reached:
SRCH
00300NO END INST
END
A display like this will appear if an END instruction is reached:
SRCH
00310PROG CHK
END (001) 00.3KW
For a listing of program check error messages, refer to Section 5 Test Runs and
Error Processing.
4-2-13 Bit, Digit, Word Monitor
This operation is used to monitor the status of up to 16 bits and words, although only three can be shown on the display at any one time. Operation is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
47
Programming Console Operations Section 4-2
Program Read then Monitor When a program address is being displayed, the status of the bit or word in that address can be monitored by pressing the MONTR Key.
Bit Monitor
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the desired program address and press the Down Arrow Key.
C
2
A
0
A
0
↓
00200READ
TIM 000
3. Press the MONTR Key to begin monitoring.
MONTR
CLR
T000
1234
If the status of a bit is being monitored, that bit’s status can be changed using the Force Set/Reset operation. Refer to page 56 for details.
If the status of a word is being monitored, that word’s value can be changed using the Hexadecimal/BCD Data Modification operation. Refer to page 53 for details.
4. Press the CLR Key to end monitoring.
00200
TIM 000
Follow the procedure below to monitor the status of a particular bit.
Word Monitor
Multiple Address
Monitoring
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the bit address of the desired bit and press the MONTR Key.
SHIFT
CONT
#
B
1 MONTR
00001
^ ON
The Up or Down Arrow Key can be pressed to display the status of the previous or next bit.
The displayed bit’s status can be changed using the Force Set/Reset operation. Refer to page 56 for details.
3. Press the CLR Key to end monitoring.
CLR
00000
CONT 00001
Follow the procedure below to monitor the status of a particular word.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the word address of the desired word.
SHIFT
CH
*DM
*EM
LR
B
1
00000
CHANNEL LR 01
3. Press the MONTR Key to begin monitoring.
MONTR
cL01
FFFF
The Up or Down Arrow Key can be pressed to display the status of the previous or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD
Data Modification operation. Refer to page 53 for details.
4. Press the CLR Key to end monitoring.
CLR
00000
CHANNEL LR 01
The status of up to six bits and words can be monitored simultaneously, although only three can be shown on the display at any one time.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
48
Programming Console Operations Section 4-2
2. Input the address of the first bit or word and press the MONTR Key.
TIM MONTR
T000
0100
3. Repeat step 2 up to 6 times to display the next addresses to be monitored.
SHIFT
CONT
#
B
1 MONTR
00001 T000
^ OFF 0100
EM
DM
MONTR
D000000001 T000
0000^ 0FF 0100
If 4 or more bits and words are being monitored, the bits and words that do not appear on the display can be displayed by pressing the MONTR Key. If the MONTR Key is pressed alone, the display will shift to the right.
If more than six bits and words are input, monitoring of the bit or word input first will be canceled.
4. Press the CLR Key to stop monitoring the leftmost bit or word and clear it from the display.
CLR
00001 T000
^ 0FF 0100
5. Press the SHIFT+CLR Keys to end monitoring altogether.
SHIFT CLR
00000
CONT 00001
Note Press the SHIFT + CLR Keys to return to the display with the multiple address monitoring state unchanged. Press the SHIFT + MONTR Keys to display the retained multiple address monitoring state. The monitoring states can be retained for 6 bits and words.
4-2-14 Differentiation Monitor
This operation is used to monitor the up or down differentiation status of a particular bit. When detected, the up or down differentiation will be displayed and the buzzer will sound. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
4-2-13 Bit, Digit, Word Monitor. If 2 or more bits are being monitored, the desired bit should be leftmost on the display.
In this case the differentiation status of LR 00 will be monitored.
L0000āāā00001āāāH0000
^ OFFāāā^ OFFāāā^ OFF
2. To specify up-differentiation monitoring, press the SHIFT and then the Up
Arrow Key. The symbols “U@” will appear.
SHIFT
↑
L000000001H0000
U@OFF^ OFF^ OFF
Indicates waiting for the bit to turn ON.
To specify down-differentiation monitoring, press the SHIFT and then the
Down Arrow Key. The symbols “D@” will appear.
SHIFT
↓
L0000āāā00001āāāH0000
D@OFF^ OFF ^ OFF
49
Programming Console Operations Section 4-2
3. The buzzer will sound when the specified bit goes from off to on (for up-differentiation) or from on to off (for down-differentiation).
L0000āāā00001āāāH0000
^ON ^ OFF ^ OFF
4. Press the CLR Key to end differentiation monitoring and return to the normal monitoring display.
CLR
L0000āāā00001āāāāH0000
^OFF ^OFF ^OFF
4-2-15 Binary Monitor
This operation is used to monitor the ON/OFF status of any word’s 16 bits. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described in 4-2-13 Bit, Digit, Word Monitor. The desired word should be leftmost on the display if two or more words are being monitored.
c010
0000
(Word monitor)
2. Press the SHIFT and then the MONTR Key to begin binary monitoring. The
ON/OFF status of the selected word’s 16 bits will be shown along the bottom of the display. A 1 indicates a bit is on, and a 0 indicates it is off.
SHIFT MONTR
c010 MONTR
0000000000000000
Bit 15 Bit 00
The status of force-set bits is indicated by “S,” and the status of a force-reset bits is indicated by “R,” as shown below.
c010 MONTR
000S0000000R0000
Force-set bit Force-reset bit
Note a) The status of displayed bits can be changed at this point. Refer to
4-2-22 Binary Data Modification for details.
b) The Up or Down Arrow Key can be pressed to display the status of the previous or next word’s bits.
3. Press the CLR Key to end binary monitoring and return to the normal monitoring display.
CLR
c010
0000
4-2-16 Three-Word Monitor
This operation is used to simultaneously monitor the status of three consecutive words. In RUN mode or MONITOR mode, changes are displayed as they occur. The 3-word monitor operation can be used during I/O monitoring, including multiple address monitoring. Refer to 4-2-13 Bit, Digit, Word Monitor.
OK
RUN
OK
MONITOR
OK
PROGRAM
50
Programming Console Operations Section 4-2
1, 2, 3...
1. Monitor the status of the first of the three words according to the procedure described in 4-2-13 Bit, Digit, Word Monitor.
If two or more words are being monitored, the desired first word should be leftmost on the display.
c200
89AB
(Word monitor)
2. Press the EXT Key to begin 3-word monitoring. The status of the selected word and the next two words will be displayed, as shown below. In this case,
DM 0000 was selected.
EXT
c202 c201 c200
0123 4567 89AB
The Up and Down Arrow Keys can be used to shift one address up or down.
The status of the displayed words can be changed at this point. Refer to
4-2-19 3-word Data Modification.
3. Press the CLR Key to end 3-word monitoring and return to the normal monitoring display. The rightmost word on the 3-word monitor display will be monitored.
CLR
c200
89AB
4-2-17 Signed Decimal Monitor
This operation converts the contents of the specified word from signed hexadecimal (two’s complement format) to signed decimal for display. The operation can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor with sign. During multiple address monitoring, the leftmost word will be converted.
(Multiple address monitor)
c200 cL0020000
FFF0 0000^ OFF
2. Press the SHIFT+TR Keys to display the leftmost word as signed decimal.
SHIFT TR
c200
Ć00016
At this point, the contents of the displayed word can be changed with a signed-decimal input. Refer to 4-2-23 Signed Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal display and return to normal monitoring.
CLR
c200 cL0020000
FFF0 0000^ OFF
4-2-18 Unsigned Decimal Monitor
This operation is used to convert hexadecimal data in a word to unsigned decimal for display. The operation can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK
RUN
OK
MONITOR
OK
PROGRAM
51
Programming Console Operations Section 4-2
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor without sign. During multiple address monitoring and 3-word monitoring, the leftmost word will be converted.
Multiple address monitoring
c200 cL0020000
FFF0 0000^ OFF
2. Press the SHIFT+TR+NOT Keys to display the leftmost word as unsigned decimal.
SHIFT TR NOT
c200
65520
At this point, the contents of the displayed word can be changed with an unsigned-decimal input. Refer to 4-2-24 Unsigned Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal display and return to normal monitoring.
CLR
c200 cL0020000
FFF0 0000^ OFF
4-2-19 Three-Word Data Modification
This operation is used to change the contents of one or more of the 3 consecutive words displayed in the 3-Word Monitor operation. It is possible in
MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired words according to the procedure described 4-2-16 3-Word Monitor.
(3-word monitor)
D0002D0001D0000
0123 4567 89AB
2. Press the CHG Key to begin 3-word data modification. The cursor will appear next to the contents of the leftmost word.
CHG
D0002 3CH CHG?
00123 4567 89AB
3. Input the new value for the leftmost word on the display and press the CHG
Key if more changes will be made.
(Input the new value and press the WRITE Key to write the changes in memory if no more changes will be made.)
B
1 CHG
D0002 3CH CHG?
0001 4567 89AB
4. Input the new value for the middle word on the display and press the CHG
Key if the rightmost word will be changed. Input the new value and press the
WRITE Key to write the changes in memory if the rightmost word will not be changed. (In this case, it will not.)
C
2
D
3
E
4 WRITE
D0002D0001D0000
0001 0234 89AB
Note If the CLR Key is pressed before the WRITE Key, the operation will be cancelled and the 3-word monitor display will return without any changes in data memory.
4-2-20 Changing Timer, Counter SV
There are two operations that can be used to change the SV of a timer or counter. They are possible in MONITOR or PROGRAM mode only. In MONI-
TOR mode, the SV can be changed while the program is being executed.
52
Programming Console Operations Section 4-2
No
RUN
OK
MONITOR
OK
PROGRAM
The timer or counter SV can be changed either by inputting a new value or by incrementing or decrementing the current SV.
Inputting a New SV
Constant
This operation can be used to input a new SV constant, as well as to change an
SV from a constant to a word address designation and vice versa. The following examples show how to input a new SV constant and how to change the SV from a constant to an address.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
B
1 SRCH
00201SRCH
TIM 001
3. Press the Down Arrow Key and then the CHG Key.
↓
CHG
00201DATA?
T001 #0134 #????
4. At this point a new SV constant can be input or the SV constant can be changed to a word address designation a) To input a new SV constant, input the constant and press the WRITE
Key.
B
1
C
2
E
4 WRITE
00201 TIM DATA
#0124
SHIFT b) To change to a word address designation, input the word address and press the WRITE Key.
CH
*DM
AR
HR
B
1
A
0 WRITE
00201 TIM DATA
HR 10
Incrementing and
Decrementing a Constant
This operation can be used to increment and decrement an SV constant. It is possible only when the SV has been entered as a constant.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM SRCH
00201SRCH
TIM 000
3. Press the Down Arrow, CHG, and then the EXT Key.
↓
CHG EXT
00201DATA ? U/D
T000 #0123 #0123
The constant on the left is the old SV and the constant on the right will become the new SV constant in step 5.
4. Press the Up and Down Arrow Keys to decrement and increment the constant on the right. (In this case the SV is incremented once.)
↓
00201DATA ? U/D
T000 #0123 #0124
5. Press the CLR Key twice to change the timer’s SV to the new value.
CLR CLR
00201 TIM DATA
#0124
4-2-21 Hexadecimal, BCD Data Modification
This operation is used to change the BCD or hexadecimal value of a word being monitored using the procedure described in 4-2-13 Bit, Digit, Word
Monitor. It is possible in MONITOR or PROGRAM mode only.
53
Programming Console Operations Section 4-2
No
RUN
OK
MONITOR
OK
PROGRAM
Words SR 253 to SR 255 cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described in 4-2-13 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired word should be leftmost on the display.
D0000
0119
(Word monitor)
2. Press the CHG Key to begin hexadecimal, BCD data modification.
CHG
PRES VAL?
D0000 0119 ????
3. Input the new PV and press the WRITE Key to change the PV.
The operation will end and the normal monitoring display will return when the WRITE Key is pressed.
C
2
A
0
A
0 WRITE
D0000
0200
4-2-22 Binary Data Modification
This operation is used to change the status of a word’s bits when the word is monitored using the procedure described in 4-2-15 Word Monitor. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
Bits SR 25300 to SR 25507 and timer/counter flags cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described
4-2-15 Word Monitor.
(BInary monitor)
c010 MONTR
1000010101010101
Bit 15
2. Press the CHG Key to begin binary data modification.
Bit 00
CHG
c010 CHG?
1000010101010101
A flashing cursor will appear over bit 15. The cursor indicates which bit can be changed.
54
Programming Console Operations Section 4-2
3. Three sets of keys are used to move the cursor and change bit status: a) Use the Up and Down Arrow Keys to move the cursor to the left and right.
↓ ↓
c010 CHG?
1000010101010101 b) Use the 1 and 0 keys to change a bit’s status to on or off. The cursor will move one bit to the right after one of these keys is pressed.
B
1
c010 CHG?
1010010101010101 c) Use the SHIFT+SET and SHIFT+RESET Keys to force-set or force-reset a bit’s status. The cursor will move one bit to the right after one of these keys is pressed. The NOT Key will clear force-set or force-reset status.
Note Bits in the DM Area cannot be force-set or force-reset.
4. Press the WRITE Key to write the changes in memory and return to the binary monitor.
WRITE
c010 MONTR
1010010101010101
4-2-23 Signed Decimal Data Modification
This operation is used to change the decimal value of a word being monitored as signed decimal data. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format).
Words SR 253 to SR 255 cannot be changed.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points may operate unexpectedly.
1, 2, 3...
1. Monitor (signed decimal) the status of the word for which the present value is to be changed.
D0200
Ć00016
(Signed decimal monitor)
2. Press the CHG Key to begin decimal data modification.
CHG
PRES VAL?
D0200Ć00016
3. Input the new PV and press the WRITE Key to change the PV. The operation will end and the signed-decimal monitoring display will return when the
WRITE Key is pressed.
The PV can be set within a range of –32,768 and 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
RESET
D
3
C
2 7 6 8 WRITE
D0200
Ć32768
Press the CLR Key or the SHIFT and TR Keys to return to the normal monitoring display.
If an erroneous input has been made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
55
Programming Console Operations Section 4-2
4-2-24 Unsigned Decimal Data Modification
This operation is used to change the decimal value of a word being monitored as unsigned decimal data. A change into hexadecimal data is made automatically.
Words SR 253 to SR 255 cannot be changed.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points may operate unexpectedly.
1, 2, 3...
1. Monitor (unsigned decimal) the status of the word for which the present value is to be changed.
c200
65520
(Unsigned decimal monitor)
2. Press the CHG Key to begin decimal data modification.
CHG
PRES VAL?
c200 65520
3. Input the new PV and press the WRITE Key to change the PV. The operation will end and the decimal-without-sign monitoring display will return when the
WRITE Key is pressed.
The PV can be set within a range of 0 to 65,535.
D
3
C
2 7 6 8 WRITE
c200
32768
Press the CLR Key or the SHIFT and TR Keys to return to the normal monitoring display.
If an erroneous input has been made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
4-2-25 Force Set, Reset
This operation is used to force bits ON (force set) or OFF (force reset) and is useful when debugging the program or checking output wiring. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
4-2-13 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired bit should be leftmost on the display.
(Multiple address monitor)
0000020000
^ OFF^ ON
56
Programming Console Operations Section 4-2
2. Press the SET Key to force the bit ON or press the RESET Key to force the bit OFF.
SET
0000020000
ON^ ON
The cursor in the lower left corner of the display indicates that the force set/ reset is in progress. Bit status will remain ON or OFF only as long as the key is held down; the original status will return one cycle after the key is released.
3. Press the SHIFT+SET or SHIFT+RESET Keys to maintain the status of the bit after the key is released. In this case, the force-set status is indicated by an “S” and the force-reset status is indicated by an “R.”
To return the bit to its original status, press the NOT Key or perform the Clear
Force Set/Reset operation. Refer to 4-2-26 Clear Force Set/Reset for details.
Forced status will also be cleared when the PC’s operating mode is changed
(unless SR 25211 is ON, in which case forced status will not be cleared when changing from PROGRAM to MONITOR mode) or when operation stops as the result of a fatal error or power interruption.
4-2-26 Clear Force Set/Reset
This operation is used to restore the status of all bits which have been force set or reset. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET and then the RESET Key. A confirmation message will appear.
00000FORCE RELE?
SET
RESET
Note If the wrong key is mistakenly pressed, press CLR and start again from the beginning.
3. Press the NOT Key to clear the force-set/reset status of bits in all data areas.
NOT
00000FORCE RELE
END
4-2-27 Hex-ASCII Display Change
This operation is used to convert word data displays back and forth between
4-digit hexadecimal data and ASCII. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired word(s) according to the procedure described in 4-2-13 Bit, Digit, Word Monitor.
D0000D0001
4142 3031
(Multiple address monitor)
2. Press the TR Key to switch to ASCII display. The display will toggle between hexadecimal and ASCII displays each time the TR Key is pressed.
TR
TR
D0000D0001
"AB" 3031
D0000D0001
4142 3031
57
Programming Console Operations Section 4-2
4-2-28 Displaying the Cycle Time
This operation is used to display the current average cycle time (scan time).
It is possible only in RUN or MONITOR mode while the program is being executed.
OK
RUN
OK
MONITOR
No
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the MONTR Key to display the cycle time.
MONTR
00000SCAN TIME
012.1MS
There might be differences in displayed values when the MONTR Key is pressed repeatedly. These differences are caused by changing execution conditions.
“MS” in the display indicates the unit “ms” for the cycle time.
58
SECTION 5
Test Runs and Error Processing
This section describes procedures for test runs of SRM1 operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during operation.
5-1 Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-1 Flowchart for Configuring and Checking the System . . . . . . . . . . . . . . . . . . . . . .
5-1-2 SRM1 Test Run Procedure
5-1-3 Flash Memory Precautions
5-2 Entering the Program
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-1 Before Programming
5-2-2 Clearing Memory
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-3 Ladder Programming Example
5-2-4 Writing the Program
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-5 Checking the Program
5-3 Test Run
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-1 Non-fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-2 Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-3 Identifying Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-4 User-defined Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-5 Reading/Clearing Error Messages
5-5 Programming Console Operation Errors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Programming Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7 Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
71
72
72
62
62
64
68
60
60
60
61
62
74
75
75
77
72
73
73
59
Startup Procedure
5-1 Startup Procedure
5-1-1 Flowchart for Configuring and Checking the System
Check the following items when configuring the system.
SRM1 Slave Unit
Section 5-1
CompoBus/S transmission line wiring
SRM1 startup
Power supply connection
Node number setting
CompoBus/S communications mode setting
I/O device connections
End
1
No.
2
3
4
5
Items to check
CompoBus/S transmission line wiring
Contents
Is the CompoBus/S transmission cable securely connected, and with no loose terminal screws?
Is the end of the transmission path (i.e., the farthest from the
SRM1) connected to a termination resistance?
Power supply connection
Slave settings
Slave I/O connections
CompoBus/S communications mode setting
Is the wiring correct?
Are there any loose terminal screws?
Are there any short-circuited connectors?
Is the bit allocation correct?
Have the node numbers been set properly, with no duplication?
Is the wiring correct?
Are there any loose terminal screws?
Are there any short-circuited connectors?
Is the CompoBus/S communications mode setting correct?
Reference
Pages 23, 24
Also refer to the
CompoBus/S
Operation
Manual (W266)
Pages 23, 24
Page 8
Refer to the
CompoBus/S
Operation
5-1-2 SRM1 Test Run Procedure
1, 2, 3...
1. Power Supply Application a) Check the SRM1’s power supply voltage and terminal connections.
b) Check the CompoBus/S transmission line terminal connections and the
Slave’s node number and power supply.
c) Check the I/O devices’ power supply voltage and terminal connections.
d) Turn on the power supply. Turn on the power supply starting from the
Slave.
e) Check that the “PWR” indicator lights.
60
Startup Procedure Section 5-1 f) Use the Programming Console to set the SRM1 to PROGRAM mode.
g) Use the Programming Console to set the maximum number of Slaves
(bits 00 to 03 of DM 6603) and the CompoBus/S communications mode
(bits 04 to 07 of DM 6603). (The SRM1’s power must be turned OFF and then ON again to enable new settings in DM 6603.) h) Check that the “SD” and “RD” indicators light.
2. I/O Wiring Checks a) With the SRM1 in PROGRAM mode, check the output wiring by turning on the output bits with the force set and force reset operations.
Refer to 4-2-25 Force Set, Reset for details.
b) Check the input wiring with the SRM1’s input indicators or the Programming Console’s monitor operations. Check the input wiring with the
Slaves input indicators, the Programming Console’s I/O monitoring, or the Programming Console’s multiple address monitoring.
3. Test Run
Use a Programming Console to set the SRM1 to RUN or MONITOR mode and check that the “RUN” indicator lights.
4. Program Input a) Use the Programming Console, SYSMAC-CPT, or SYSMAC Support
Software (SSS) to write the program.
b) Check the sequence of operation.
Note When using the SYSMAC-CPT Support Software, set the PC model to “SRM1.” When using the SYSMAC Support Software, set the PC model to “CQM1.”
5. Debugging
Correct any programming errors that are detected.
5-1-3 Flash Memory Precautions
The SRM1 uses the flash memory to hold the contents of the user program memory, the read-only DM area (DM 6144 through DM 6599), and PC Setup
(DM 6600 through DM 6655). Observe the following precautions to protect the flash memory and ensure proper operation.
1, 2, 3...
1. Perform either one of the following to write the above contents onto the flash memory.
a) Switch the SRM1 to RUN or MONITOR mode.
b) Restart the power supply to the SRM1.
Note If the power is turned off without changing the mode after making changes in the above areas using a Peripheral Device, the changes will not be written to flash memory. Although the data in these areas is backed up by a lithium battery, the changes will be lost if the battery fails or is removed because the program in the flash memory will be automatically read into the user program memory. The standard service life of the lithium battery is ten years minimum under an ambient temperature of 25
°
C.
2. When the SRM1 is operated for the first time after changing the program memory, the read-only DM area (DM 6144 through DM 6599), or PC Setup
(DM 6600 through DM 6655), it will take about 850 ms longer than usual before the SRM1 starts. Be sure to take this one-time startup delay into account.
61
Entering the Program Section 5-2
3. If one of the following three operations is performed in MONITOR or RUN mode, a “cycle time over” warning will not be issued. When performing online edit operation, take the I/O response time of the SRM1 into account. The
SRM1 will extend the cycle time for up to 850 ms and interrupts will be disabled while the program or PC Setup is being overwritten.
•
Program changes with the online edit operation
•
Changes to the read-only DM area (DM 6144 through DM 6599)
•
Changes to the PC Setup (DM 6600 through DM 6655)
5-2 Entering the Program
5-2-1 Before Programming
Connecting the
Programming Console
Connect the cable from the Programming Console (CQM1-PRO01-E or C200H-
PRO27-E) to the SRM1’s Peripheral Port.
5-2-2 Clearing Memory
This operation is used to clear all or part of the Program Memory and any data areas that are not read-only, as well as the contents of the Programming Console’s memory. This operation is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
All Clear
Before beginning to program for the first time or when installing a new program, clear all areas.
The following procedure is used to clear memory completely.
1, 2, 3...
1. Bring up the initial display by pressing the CLR key repeatedly.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
SET NOT RESET
00000MEMORY CLR?
HR CNT DM
3. Press the MONTR Key to clear memory completely.
MONTR
00000MEMORY CLR
END HR CNT DM
!
Caution Check to be sure that no equipment is affected when turning the SRM1’s power supply on or off, or when entering the password. Be careful not to cause any accidents when starting or stopping SRM1 operation.
Partial Clear It is possible to retain the data in specified areas or part of the Program Memory.
To retain the data in the HR, TC, or DM Areas, press the appropriate key after pressing SET, NOT, and RESET. Any data area that still appears on the display will be cleared when the MONTR Key is pressed.
62
Entering the Program Section 5-2
The HR Key is used to specify both the AR and HR Areas, the CNT Key is used to specify the entire timer/counter area, and the DM Key is used to specify the DM
Area.
It is also possible to retain a portion of the Program Memory from the first memory address to a specified address. After designating the data areas to be retained, specify the first Program Memory address to be cleared. For example, input 030 to leave addresses 000 to 029 untouched, but to clear addresses from 030 to the end of Program Memory.
As an example, follow the procedure below to retain the timer/counter area and
Program Memory addresses 000 through 122:
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
3. Press the CNT Key to remove the timer/counter area from the data areas shown on the display.
CNT
00000MEMORY CLR?
HR DM
4. Press 123 to specify 123 as the starting program address.
B
1
C
2
D
3
00123MEMORY CLR?
HR DM
5. Press the MONTR Key to clear the specified regions of memory.
63
Entering the Program Section 5-2
5-2-3 Ladder Programming Example
In this example, the SRM1’s distributed I/O is used to control a lift (e.g., a dumb waiter) connecting a kitchen on the first floor and a customer serving area on the second floor.
SRM1
SRT1-ROC08
Node #1
(Output word 10, bits 8 to 15)
SRT1-ID04
Node #1
(Input word 0, bits 8 to 11)
MC2
LS2
LS22
MC22
MC21
L2
PB2
LS21
64
SRT1-ROC08
Node #0
(Output word 10, bits 0 to 7)
SRS1-T
SRT1-ID04
Node #0
Input word 0, bits 0 to 3
MC1
LS1
LS11
MC12
MC11
L1
PB1
Entering the Program Section 5-2
Explanation of Operations Initially, the lift is on the first floor (where the kitchen is located) and LS1 is ON.
The door is open and LS12 is ON. L1 is ON, and the first-floor indicator light is on.
When food is placed on the lift and the “up” button is pressed to turn ON PB1,
MC11 turns ON and the door closes. After the door has closed, LS11 turns ON.
MC1 turns ON and the lift begins to go up. L1 turns OFF and the first floor indicator light turns off.
When the lift reaches the second floor (the customer serving area), L2 turns ON,
MC1 turns OFF and the lift stops. L2 turns ON and the second-floor indicator light turns on. MC22 turns ON and the second-floor door opens.
When the food is taken from the lift and the “down” button is pressed, PB2 turns
ON. MC21 turns ON and the door closes. After the door has closed, LS21 turns
ON. MC2 turns ON and the lift begins to go down. L2 turns OFF and the secondfloor indicator light turns off.
When the lift reaches the first floor again, LS1 turns ON. MC2 turns OFF and the lift stops. L1 turns ON and the first-floor indicator light turns ON. MC12 turns ON and the door opens.
Sequence Program Diagram
PB1
X1
X1
LS22
LS11 MC12
X1 LS11 LS2 MC2
LS2
X1 LS2 MC21
PB2
X2
LS12
X2 LS21 MC22
X2 LS21 LS1 MC1
LS1
X2 LS1 MC11
X1
MC11 1F closed
MC1 Down
L2 2F indicator light
MC22 2F open
X2
MC21 2F closed
MC2 Up
L1 1F indicator light
MC12 1F open
65
Entering the Program
I/O Allocation
Wd
Bit addresses are assigned as follows for inputs and outputs.
Input
Wd Wd
Output
Wd
Section 5-2
66
Entering the Program Section 5-2
Ladder Program
PB1
00001
LS22
00103
(1) 00000
X1
00900
Following the sequence program and I/O allocation, create the ladder program.
X1
00900
LS11
00000
MC12
01003
(2) 00004
X1
00900
LS11
00000
LS2
00102
MC2
01100
(3) 00008
(4) 00013
LS2
00102
X1
00900
LS2
00102
MC21
01102
(5) 00015
PB2
00101
LS12
00003
(6) 00019
X2
00901
X2
00901
LS21
00100
MC22
01103
(7) 00023
X2
00901
LS21
00100
LS1
00002
MC1
01000
(8) 00027
(9) 00032
LS1
00002
X2
00901
LS1
00002
MC11
01002
(10) 00034
X1
00900
MC11
01002
1F closed
MC1
01000
Down
L2
01101
2F indicator light
MC22
01103
2F open
X2
00901
MC21
01102
2F closed
MC2
01100
Up
L1
01001
1F indicator light
MC12
01003
1F open
(11) 00038
Mnemonic Coding List
END(01)
The following table shows the mnemonic coding for the ladder program. The subsequent pages explain the procedure for entering the program using the
Programming Console.
Program reference
(1)
(2)
(3)
(4)
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
0010
00011
00012
00013
00014
Step Instruction
LD
OR
AND NOT
OUT
LD
AND NOT
AND NOT
OUT
LD
AND
AND NOT
AND NOT
OUT
LD
OUT
Data
00001
00900
00103
00900
00900
00000
01003
01002
00900
00000
00102
01100
01000
00102
01101
67
Entering the Program Section 5-2
Program reference
(5)
(6)
(7)
(8)
(9)
(10)
(11)
00026
00027
00028
00029
00030
00031
00032
00033
00034
00035
00036
00037
00038
00015
00016
00017
00018
00019
00020
00021
00022
00023
00024
00025
Step Instruction
LD
AND
AND NOT
OUT
LD
OR
AND NOT
OUT
LD
AND NOT
AND NOT
OUT
LD
AND
AND NOT
AND NOT
OUT
LD
OUT
LD
AND
AND NOT
OUT
END (01)
5-2-4 Writing the Program
Use the following procedure to write the program, according to the coding sheet.
The numbers in parentheses are in reference to the previous ladder program.
•
(1) Writing Steps 00000 to 00003
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
2. Input the first instruction and bit address 00001. It is not necessary to input leading zeroes.
LD
B
1
00000
LD 00001
3. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00001READ
NOP (000)
4. Input OR and bit address 00900.
OR 9
A
0
A
0
00001
OR 00900
5. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00002READ
NOP (000)
Data
01102
00901
00100
00002
01000
01100
00002
01001
00901
00001
01002
01003
---
00900
00102
01102
01103
00101
00901
00003
00901
00901
00100
01103
68
Entering the Program Section 5-2
6. Input AND, NOT and bit address 00103.
AND NOT
B
1
A
0
D
3
00002
AND NOT 00103
7. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00003READ
NOP (000)
8. Input the OUT instruction and bit address 00900.
OUT 9
A
0
A
0
00003
OUT 00900
9. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00004READ
NOP (000)
•
(2) to (11) Writing Steps 00004 to 00038
Enter steps 00004 to 00038 as follows:
(2) 00004
LD 9
A
0
A
0 WRITE
00005
AND NOT
A
0 WRITE
00006
AND NOT
B
1
A
0
A
0
D
3 WRITE
(3)
00007
OUT
B
1
A
0
A
0
C
2 WRITE
00008
LD 9
A
0
A
0 WRITE
00009
AND
A
0 WRITE
00010
AND NOT
B
1
A
0
C
2 WRITE
(4)
(5)
00011
AND NOT
B
1
B
1
A
0
A
0 WRITE
00012
OUT
B
1
A
0
A
0
A
0 WRITE
00013
LD
B
1
A
0
C
2 WRITE
00014
OUT
B
1
B
1
A
0
B
1 WRITE
00015
LD 9
A
0
A
0 WRITE
00016
AND
B
1
A
0
C
2 WRITE
00017
AND NOT
B
1
B
1
A
0
C
2 WRITE
00018
OUT
B
1
B
1
A
0
D
3 WRITE
69
Entering the Program
(6)
(7)
(8)
(9)
00019
LD
00020
OR
B
1
A
0
9
A
0
B
1 WRITE
B
1 WRITE
00021
AND NOT
D
3 WRITE
00022
OUT 9
A
0
B
1 WRITE
00023
00024
LD
AND
9
A
0
B
1 WRITE
NOT
B
1
A
0
A
0 WRITE
00025
AND NOT
B
1
B
1
A
0
D
3 WRITE
00026
OUT
B
1
B
1
A
0
C
2 WRITE
00027
LD
00028
AND
9
A
0
B
1
A
0
B
1 WRITE
A
0 WRITE
00029
AND NOT
C
2 WRITE
00030
AND NOT
B
1
A
0
A
0
A
0 WRITE
00031
OUT
B
1
B
1
00032
LD
C
2 WRITE
A
0
A
0 WRITE
00033
OUT
B
1
A
0
A
0
B
1 WRITE
(10) 00034
LD 9
A
0
B
1 WRITE
00035
AND
C
2 WRITE
00036
AND NOT
B
1
A
0
A
0
C
2 WRITE
00037
OUT
B
1
A
0
A
0
D
3 WRITE
(11) 00038
FUN
A
0
A
0
B
1 WRITE
Section 5-2
70
Test Run Section 5-3
5-2-5 Checking the Program
This operation checks for programming errors and displays the program address and error when errors are found. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH
00000PROG CHK
CHK LVL (0Ć2)?
3. Input the desired check level (0, 1, or 2). The program check will begin when the check level is input, and the first error found will be displayed.
Note Refer to 5-6 Programming Errors for details on check levels and error displays.
4. Press the SRCH Key to continue the search. The next error will be displayed. Continue pressing the SRCH Key to continue the search.
A display like this will appear if an END instruction is reached without any errors being found:
SRCH
00017PROG CHK
END (001) 00.1KW
If errors are displayed, edit the program to correct the errors and check the program again. Continue checking the program until all errors have been corrected.
5-3 Test Run
Run the SRM1 in MONITOR mode to check the program. Then follow the procedure described below to perform a test run.
1, 2, 3...
1. Change the mode switch to RUN mode.
MONITOR
RUN PROGRAM
<RUN> BZ
2. Check the SRM1’s LED indicator status. If the SRM1 is operating properly, the PWR, RUN, SD, and RD indicators should all be lit, the COMM indicator should flash, and all other indicators should be unlit. If the indicator status is anything other than this, refer to 5-4 Error Processing.
3. Turn ON either PB1 or PB2 and check to see whether the operations are executed as described in Explanation of Operations in 5-2-3 Ladder Pro-
gramming Example. If the program is not executed, or the operations are different from those described in Explanation of Operations, check the program and the I/O wiring.
Note For checking the program, refer to 5-6 Programming Errors and the Program-
ming Manual.
71
Error Processing Section 5-4
5-4 Error Processing
The SRM1 is equipped with a variety of self-diagnosis functions to help identify and correct errors that might occur and reduce down time.
Errors are divided into two categories based on their severity. Fatal errors are more serious errors which stop SRM1 operation. Non-fatal errors are less serious and don’t stop SRM1 operation.
5-4-1 Non-fatal Errors
SRM1 operation and program execution will continue after one or more of these errors have occurred. Although SRM1 operation will continue, the cause of the error should still be corrected and the error cleared as soon as possible.
When one of these errors occurs, the POWER and RUN indicators will remain lit and the ERR/ALM indicator will flash.
Message
SYS FAIL FAL**
(** is 01 to 99 or 9B.)
FAL No.
Meaning and appropriate response
01 to 99 An FAL(06) instruction has been executed in the program. Check the FAL number to determine conditions that would cause execution, correct the cause, and clear the error.
9B An error has been detected in the PC Setup. Check flags AR 1300 to AR 1302, and correct as directed.
AR 1300 ON: An incorrect setting was detected in the PC Setup (DM 6600 to
DM 6614) when power was turned on. Correct the settings in PROGRAM Mode and turn on the power again.
AR 1301 ON: An incorrect setting was detected in the PC Setup (DM 6615 to
DM 6644) when switching to RUN Mode. Correct the settings in PROGRAM Mode and switch to RUN Mode again.
AR 1302 ON: An incorrect setting was detected in the PC Setup (DM 6645 to
DM 6655) during operation. Correct the settings and clear the error.
SCAN TIME OVER F8
Communication Error
(no message)
None
Watchdog timer has exceeded 100 ms. (SR 25309 will be ON.)
This indicates that the program cycle time is longer than recommended. Reduce cycle time if possible. (The SRM1 can be set so that this error won’t be detected.)
If an error occurs in CompoBus/S communications, the COMM indicator will be off and the ERC indicator will be lit. There is no error flag. Check the Slave and the connecting cables and restart.
The COMM indicator will be OFF if an error occurs in communications through the
Peripheral Port or RS-232C Port. AR 0804 will be ON if an error occurred in communications through the RS-232C port. AR 0812 will be ON if an error occurred in communications through the peripheral port. Check the connecting cables and restart.
5-4-2 Fatal Errors
SRM1 operation and program execution will stop and all outputs from the SRM1 will be turned OFF when any of these errors have occurred. SRM1 operation cannot be restarted until the SRM1 is turned off and then on again or the Programming Console is used to switch the SRM1 to PROGRAM mode and clear the fatal error.
72
Error Processing Section 5-4
All SRM1 indicators will be OFF for the power interruption error. For all other fatal operating errors, the POWER and ERR/ALM indicators will be lit. The RUN indicator will be OFF.
Message
Power interruption
(no message)
MEMORY ERR
NO END INST
SYS FAIL FALS**
(** is 01 to 99 or 9F.)
FALS
No.
None
Meaning and appropriate response
F1
Power has been interrupted for at least 10 ms. Check power supply voltage and power lines. Try to power-up again.
AR 1308 ON: An unspecified bit area exists in the user program. Check the program and correct errors.
AR 1309 ON: An error has occurred in the flash memory. Since the number of writings to the flash memory has exceeded the specified level, replace the SRM1.
AR 1310 ON: A checksum error has occurred in read-only DM (DM 6144 to DM 6599).
Check and correct the settings in the read-only DM area.
AR 1311 ON: A checksum error has occurred in the PC Setup. Initialize all of the PC
Setup and reinput.
AR 1312 ON: A checksum error has occurred in the program. Check the program and correct any errors detected.
AR 1314 ON: Power interruption hold area was not held. Clear the error and reset the settings of the power interruption hold area.
AR 1315 ON: An error has occurred in CompoBus/S communications. If the error cannot be corrected, replace the SRM1.
END(01) is not written in the program. Write END(01) at the end of the program.
F0
01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to determine the conditions that caused execution, correct the cause, and clear the error.
9F The cycle time has exceeded the FALS 9F Cycle Time Monitoring Time (DM 6618).
Check the cycle time and adjust the Cycle Time Monitoring Time if necessary.
5-4-3 Identifying Errors
Errors can be identified from error messages displayed on the Programming
Console, error flags in the SR or AR areas, and the error code in SR 25300 to
SR 25307.
Error Messages
Error Flags
Error Code
Error messages generated by the self-diagnosis function can be read from a
Programming Console or host computer running SYSMAC Support Software.
When the self-diagnosis function detects a hardware error, it will turn on the corresponding error flags in the SR and AR areas.
When an error is detected by the self-diagnosis function, the corresponding error code is written to SR 25300 to SR 25307. (The error code is an 2-digit hexadecimal code.)
5-4-4 User-defined Errors
There are three instructions that the user can use to define his own errors or messages. FAL(06) causes a non-fatal error, FAL(07) causes a fatal error, and
MSG(46) sends a message to the Programming Console or host computer connected to the SRM1.
FAILURE ALARM – FAL(06) FAL(06) is an instruction that causes a non-fatal error. The following will occur when an FAL(06) instruction is executed:
1, 2, 3...
1. The ERR indicator on the SRM1 will flash, but operation will continue.
2. The instruction’s 2-digit BCD FAL number (01 to 99) will be written to
SR 25300 to SR 25307.
The FAL numbers can be set arbitrarily to indicate particular conditions. The same number cannot be used as both an FAL number and an FALS number.
To clear an FAL error, correct the cause of the error and then execute FAL 00 or clear the error using the Programming Console.
73
Error Processing Section 5-4
SEVERE FAILURE ALARM –
FALS(07)
1, 2, 3...
1. Program execution will be stopped and outputs will be turned OFF.
2. The ERR indicator on the SRM1 will be lit.
3. The instruction’s 2-digit BCD FALS number (01 to 99) will be written to
SR 25300 to SR 25307.
The FALS numbers can be set arbitrarily to indicate particular conditions. The same number cannot be used as both an FAL number and an FALS number.
To clear an FALS error, switch the SRM1 to PROGRAM Mode, correct the cause of the error, and then clear the error using the Programming Console.
MESSAGE – MSG(46)
FALS(07) is an instruction that causes a fatal error. The following will occur when an FALS(07) instruction is executed:
MSG(46) is used to display a message on the Programming Console. The message, which can be up to 16 characters long, is displayed when the instruction’s execution condition is ON.
5-4-5 Reading/Clearing Error Messages
This operation is used to display and clear error messages. It is possible to display and clear non-fatal errors and MESSAGE instruction messages in any mode, but fatal errors can be displayed and cleared in PROGRAM mode only.
OK
RUN
OK
MONITOR
OK
PROGRAM
Key Sequence
Before inputting a new program, any error messages recorded in memory should be cleared. It is assumed here that the causes of any of the errors for which error messages appear have already been taken care of. If the buzzer sounds when an attempt is made to clear an error message, eliminate the cause of the error, and then clear the error message. (Refer to 5-7 Trouble-
shooting Flowcharts for troubleshooting information.)
Follow the procedure below to display and clear messages.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN and then the MONTR Key to begin the operation. If there are no messages, the following display will appear:
ERR/MSG CHK OK
AND MONTR
If there are messages, the most serious message will be displayed when the
MONTR Key is pressed. Pressing MONTR again will clear the present message and display the next most serious error message. Continue pressing
MONTR until all messages have been cleared. These are some examples of error messages:
A memory error:
MEMORY ERR
MONTR
A system error:
MONTR
SYS FAIL FAL01
A message:
MONTR
MATERIAL USED UP
All messages cleared:
MONTR
ERR/MSG CHK OK
74
Programming Errors Section 5-6
!
Caution Check to be sure that no equipment is affected when turning the SRM1’s power supply on or off, or when entering the password. Be careful not to cause any accidents when starting or stopping SRM1 operation.
5-5 Programming Console Operation Errors
The following error messages may appear when performing operations on the
Programming Console. Correct the error as indicated and continue with the operation.
Message Meaning and appropriate response
REPL ROM An attempt was made to write to write-protected memory. Set bits
00 to 03 of DM 6602 to “0.”
PROG The instruction at the last address in memory is not NOP(00). Erase all unnecessary instructions at the end of the program.
ADDR OVER An address was set that is larger than the highest memory address in Program Memory. Input a smaller address.
SETDATA
ERR
FALS 00 has been input, and “00” cannot be input. Reinput the data.
I/O NO. ERR A data area address has been designated that exceeds the limit of the data area, e.g., an address is too large. Confirm the requirements for the instruction and re-enter the address.
5-6 Programming Errors
These errors in program syntax will be detected when the program is checked using the Program Check operation.
Three levels of program checking are available. The desired level must be designated to indicate the type of errors that are to be detected. The following table provides the error types, displays, and explanations of all syntax errors. Check level 0 checks for type A, B, and C errors; check level 1, for type A and B errors; and check level 2, for type A errors only.
75
Programming Errors Section 5-6
Type
A
B
C
Message
?????
Meaning and appropriate response
The program has been damaged, creating a non-existent function code. Re-enter the program.
CIRCUIT ERR The number of logic blocks and logic block instructions does not agree, i.e., either LD or LD NOT has been used to start a logic block whose execution condition has not been used by another instruction, or a logic block instruction has been used that does not have the required number of logic blocks. Check your program.
OPERAND
ERR
NO END
INSTR
A constant entered for the instruction is not within defined values. Change the constant so that it lies within the proper range.
There is no END(01) in the program. Write END(01) at the final address in the program.
LOCN ERR An instruction is in the wrong place in the program. Check instruction requirements and correct the program.
JME UNDEFD A JME(05) instruction is missing for a JMP(04) instruction.
Correct the jump number or insert the proper JME(04) instruction.
DUPL The same jump number or subroutine number has been used twice. Correct the program so that the same number is only used once for each.
SBN UNDEFD The SBS(91) instruction has been programmed for a subroutine number that does not exist. Correct the subroutine number or program the required subroutine.
STEP ERR
IL-ILC ERR
STEP(08) with a section number and STEP(08) without a section number have been used incorrectly. Check
STEP(08) programming requirements and correct the program.
IL(02) and ILC(03) are not used in pairs. Correct the program so that each IL(02) has a unique ILC(03).
Although this error message will appear if more than one
IL(02) is used with the same ILC(03), the program will executed as written. Make sure your program is written as desired before proceeding.
JMP-JME ERR JMP(04) and JME(05) are not used in pairs. Make sure your program is written as desired before proceeding.
SBN-RET ERR If the displayed address is that of SBN(92), two different subroutines have been defined with the same subroutine number. Change one of the subroutine numbers or delete one of the subroutines. If the displayed address is that of
RET(93), RET(93) has not been used properly. Check requirements for RET(93) and correct the program.
COIL DUPL The same bit is being controlled (i.e., turned ON and/or
OFF) by more than one instruction (e.g., OUT, OUT NOT,
DIFU(13), DIFD(14), KEEP(11), SFT(10)). Although this is allowed for certain instructions, check instruction requirements to confirm that the program is correct or rewrite the program so that each bit is controlled by only one instruction.
JMP UNDEFD JME(05) has been used with no JMP(04) with the same jump number. Add a JMP(04) with the same number or delete the JME(05) that is not being used.
SBS UNDEFD A subroutine exists that is not called by SBS(91). Program a subroutine call in the proper place, or delete the subroutine if it is not required.
76
Troubleshooting Flowcharts Section 5-7
5-7 Troubleshooting Flowcharts
Use the following flowcharts to troubleshoot errors that occur during operation.
Main Check
Error
PWR indicator lit?
Yes
No
No
RUN indicator lit?
Yes
ERR indicator flashing?
Yes
No
Yes ERC indicator lit?
No
Check power supply. (See page 78.)
Check for fatal errors. (See page 79.)
Check for non-fatal errors. (See page 80.)
Check for CompoBus/S transmission errors.
(See page 81.)
RD indicator lit or flashing?
Yes
No
Be sure SRM1 and Slaves are in the same communications mode.
COMM indicator not lit on any Slave?
No
Yes
No
Is I/O sequence normal?
Yes
Operating environment normal?
Yes
CompoBus/S
No
Replace the SRM1.
Be sure SRM1 and Slaves are in the same communications mode.
Check Slave I/O wiring and I/O devices.
Check operating environment. (See page 82.)
If the LED indicators are all normal (i.e., ERC off, SD lit, and RD lit), yet there is a communication error, check the following points. (For details on the Slaves, refer to the CompoBus/S Operation Manual (W266).)
•
Are the Slave’s I/O power supply and I/O wiring okay?
•
Are the Slave’s power supply and address settings okay? Is the Slave itself operating properly?
•
Is the termination correctly connected to the end of the transmission line (i.e.
the end farthest from the SRM1)?
77
Troubleshooting Flowcharts Section 5-7
•
Are the lengths of the main line and the branch lines, and the total length, all within the prescribed limits?
•
Are flat cables and VCTF cables mixed together among the transmission lines?
Power Supply Check
Power indicator not lit.
Is power being supplied?
Yes
No
No
Connect power supply.
Is PWR indicator lit?
Yes
Is voltage adequate?
No
Yes
No
Set supply voltage within acceptable limits.
Is PWR indicator lit?
Yes
Are there any loose terminal screws or broken wires?
No
Yes
No
Tighten screws or replace wires.
Is PWR indicator lit?
Yes
Replace the Power
Supply Unit.
End
78
Troubleshooting Flowcharts
Fatal Error Check
RUN indicator not lit.
No
Is the ERR indicator lit?
Yes
Determine the cause of the error with the Programming Console.
Section
Yes
Is mode displayed on
Programming Console?
No
Is mode displayed on
Programming Console?
Yes
No
Turn the power supply off, and then ON again.
Is a fatal error displayed?
No
Switch to RUN or
MONITOR mode.
Yes
Identify the error, eliminate its cause, and clear the error.
5-7
Is the RUN indicator lit?
Yes
End
No
Replace the SRM1.
79
Troubleshooting Flowcharts
Non-fatal Error Check
Section 5-7
ERR indicator flashing.
Determine the cause of the error with the Programming Console.
Is a non-fatal error indicated?
No
Yes
Identify the error, eliminate its cause, and clear the error.
Is the ERR indicator flashing?
Not lit
Flashing
End
Replace the SRM1.
80
Troubleshooting Flowcharts
CompoBus/S Transmission Error Check
ERC indicator lit.
Is the RD indicator lit?
Yes
No
Check the transmission lines for broken lines, short circuits, or incorrect termination resistance.
Check the CompoBus/S communications mode setting.
Check all of the Slaves’ power supplies.
No
Is the RD indicator lit?
Yes
Yes
Section
Is the ERC indicator lit?
No
5-7
Check the Slave’s status using the
Peripheral Device
Error Flag.
Is the Peripheral
Device Error Flag set to ON?
No
Yes
No
Check the corresponding Slave’s power supply, wiring, and the
Unit itself.
Any error with the corresponding
Slave?
Replace the SRM1.
Eliminate the error in the Slave.
End
81
Troubleshooting Flowcharts
Environmental Conditions Check
Section 5-7
Environmental conditions check
Is the ambient temperature below 55
°
C?
Yes
No
Consider using a fan or cooler.
Is the ambient temperature above
0
°
C?
Yes
No
Is the ambient humidity between 10% and
90%?
Yes
No
Is noise being controlled?
Yes
Consider using a heater.
Consider using an air conditioner.
No
Install surge protectors or other noise-reducing equipment at noise sources.
Is the installation environment okay?
End.
Yes
No
Consider constructing an instrument panel or cabinet.
82
SECTION 6
Expansion Memory Unit
This section describes how to use the CPM1-EMU01-V1 Expansion Memory Unit. Follow the handling precautions and procedures to properly use the Unit.
6-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-1 Memory Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-2 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Specifications and Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-2 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-1 Mounting/Removing EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-2 PC Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-3 Uploading Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-4 Downloading Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
85
86
86
87
88
89
84
84
84
85
85
83
Overview
6-1 Overview
Section 6-1
The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for smallsize or micro PCs. Using the CPM1-EMU01-V1, simple on-site transfer of user programs and data memory between PCs is possible.
Uploading
Peripheral port
Downloading
PERIPHERAL
RS-232C
SRM1 (-V2)
Note The “PLC” in the “DOWNLOAD TO PLC” Button indicates PCs (Programmable
Controllers).
6-1-1 Memory Areas
The memory areas that are uploaded or downloaded vary with the button used as shown in the following table.
Button UPLOAD + DM UPLOAD
Ladder program and expansion instructions
DM 6144 to 6655
Read from PC to
EEPROM.
Read from PC to
EEPROM.
Not affected.
DOWNLOAD TO
PLC
All contents of
EEPROM written to PC.
Note For details on program size, DM area, and the availability of expansion instructions, refer to the relevant PC manual.
6-1-2 Precautions
•
Do not attempt to use the CPM1-EMU01-V1 for any applications other than those described here. Doing so may result in malfunction.
•
Do not attempt to upload or download data between different types of PC. Doing so may result in malfunction.
•
Do not download when the PC is in RUN or MONITOR mode. If downloading is performed when the PC is running, it will automatically switch to PROGRAM mode and operation will stop.
•
Do not attempt to disassemble, repair, or modify the CPM1-EMU01-V1. Any attempt to do so may result in malfunction, fire, or electric shock.
•
After downloading has been completed, be sure to confirm the user program, data, and expansion instruction information. Not doing so may result in faulty operation.
84
Specifications and Nomenclature Section 6-2
•
Before touching the EEPROM or the CPM1-EMU01-V1, first touch a grounded metallic object to discharge any static build-up. Not doing so may result in malfunction or damage.
6-2 Specifications and Nomenclature
6-2-1 Specifications
Item
Supported PCs
Read/Write memory areas
Connector
Communications setting
EEPROM (See note 1.)
Current consumption
Dimensions
Weight
Specifications
CPM1, CPM1A, CPM2A, CPM2C, SRM1 (-V2),
CQM1, CQM1H
User program: 15.2 Kwords max.
Data memory: DM 6144 to DM 6655
(Read-only DM and PC Setup)
Expansion instructions: 18 instructions
Connector compatible with CPM1, CPM1A, CPM2A,
SRM1 (-V2), and CQM1 PCs.
For CPM2C and CQM1H PCs, connect via
CS1W-CN114 or CPM2C-CN111 Connecting Cable.
1 start bit, 7 data bits, even parity, 2 stop bits,
9,600 bps
256-Kbit EEPROM
ATMEL: AT28C256
OMRON: EEROM-JD
129 mA max.
Main body (not including cables or connectors):
57
×
92
×
38 mm (W
×
H
×
D)
200 g max. (not including EEPROM)
Note 1. The EEPROM must be purchased separately.
2. For general specifications, refer to the relevant PC manual.
6-2-2 Nomenclature
Peripheral Port
Connector
Lock Lever
Indicator
UPLOAD + DM Button
EEPROM Socket
DOWNLOAD to PLC Button
UPLOAD Button
Lock Lever
For mounting and removing EEPROM.
DOWNLOAD TO PLC Button
Writes all EEPROM data (ladder programs, data memory etc.) to the PC.
UPLOAD + DM Button
Reads PC user program and contents of
DM 6144 to DM 6655 to EEPROM.
UPLOAD Button
Reads only PC user program to EEPROM.
Note The “PLC” in the “DOWNLOAD TO PLC” Button indicates PCs (Programmable
Controllers).
85
Handling Section 6-3
LED Indicator
CONNECT
(green)
OFF
ON
Blinking
ON
OFF
OFF
ERR (red)
OFF
OFF
OFF
Blinking
ON
Blinking
Meaning
Not connected to PC (power supply OFF).
Connected to a recognized PC.
Uploading/downloading data.
Host link communications error, retry by user.
PC model and EEPROM data not compatible.
One of the following errors has occurred:
An unrecognized PC is connected.
An EEPROM error (EEPROM not present, EEPROM defect, or no program to download) or checksum error.
6-3 Handling
6-3-1 Mounting/Removing EEPROM
!
Caution Do not mount or remove the EEPROM with the CPM1-EMU01-V1 connected to the PC. Doing so may damage the EEPROM.
Mounting EEPROM
1, 2, 3...
1. Lift up the lock lever.
2. Straighten the pins on the EEPROM, line up with the socket and lower into the socket, as shown in the following diagram. If the EEPROM is loose, place it in the center of the socket.
Lift up the lock lever.
EEPROM
Insert the EEPROM.
3. Gently hold down the EEPROM and pull down the lock lever.
Pull down the lock lever.
86
Handling Section 6-3
Removing EEPROM Lift up the lock lever and detach the EEPROM.
6-3-2 PC Connections
!
Caution Mount the EEPROM to the CPM1-EMU01-V1 before connecting the
CPM1-EMU01-V1 to the PC.
!
Caution Do not disconnect the CPM1-EMU01-V1 from the PC when the indicator is blinking green.
CPM1, CPM1A, CPM2A,
CQM1, and SRM1 (-V2)
PCs
When connecting to the CPM1, CPM1A, CPM2A, CQM1 or SRM1 (-V2),insert the connector into the peripheral port making sure that the connector is oriented correctly.
•
Insert the connector until it securely locks into place.
•
Connections are not possible to the RS-232C port or any other port.
Peripheral port
Connection to SRM1 (-V2)
CPM2C and CQM1H PCs
Peripheral Port
Communications
Settings
When connecting to the CPM2C or CQM1H, connect to the peripheral port via the CPM2C-CN111 or CS1W-CN114 Connecting Cable. Also, set the pins on the CPU Unit’s DIP switch as follows:
CPM2C
CQM1H
Pin 1: ON (see note)
Pin 2: ON
Pin 5: ON (see note)
Pin 7: ON
Note If pin 1 on the CPM2C or pin 5 on the CQM1H is OFF, connection is still possible if the peripheral port is set to the defaults.
The peripheral port must be set to the default communications settings shown below.
Start bit: 1
Data bits: 7
Stop bits: 2
Parity: Even
87
Handling
Disconnecting
Section 6-3
Baud rate: 9,600 bps
Press the levers on the top and bottom of the connector inwards to unlock the connector and pull out as shown in the following diagram.
Note Do not attempt to remove the connector by pulling the cable.
6-3-3 Uploading Programs
Ladder programs and the contents of data memory can be uploaded to the
EEPROM using the following procedure. The buttons used will determine whether the contents of data memory are uploaded or not.
Peripheral port
PERIPHERAL
RS-232C
88
Button
Ladder program and expansion instructions
DM6144 to 6655
UPLOAD + DM
Read from PC to
EEPROM.
UPLOAD
Read from PC to
EEPROM.
Not affected.
Note Use a Phillips screwdriver or other tool with a diameter of 3.0 mm max. and a blade length of 10 mm min. to press the upload button.
3.0 dia. max.
10 mm min.
Uploading is possible even if the PC is in RUN or MONITOR mode.
Handling
Operation Procedure
Section
Start
Mount the EEPROM to the
CPM1-EMU01-V1.
Connect the CPM1-EMU01-V1 to the
PC’s peripheral port.
After 2 or 3 s, check if the indicator is lit green.
No
Yes
Select the memory area to be uploaded.
See the note on the right.
Mount the EEPROM to the CPM1-EMU01-V1 before connecting to the PC.
Check the orientation of the connector before connecting the CPM1-EMU01-V1.
Note If the indicator is not lit at all, lit red or blinks red, uploading will not be possible. In this case, check the following items.
•
Is the connector properly connected?
•
Is the EEPROM properly mounted?
•
Are the EEPROM specifications correct?
•
Are the peripheral port communications settings correct?
Upload both the ladder program and DM 6144 to
DM 6655.
Upload only the ladder program.
6-3
Press the UPLOAD+DM
Button.
Press the UPLOAD Button.
Check if the indicator is blinking green
(indicating that uploading has started).
No
Yes
Check if the indicator is lit green (indicating that uploading has been successfully completed).
See the note above.
See the note above.
No
Yes
Remove the Expansion Memory Unit from the PC.
End
6-3-4 Downloading Programs
Ladder programs and the contents of data memory can be downloaded from the
EEPROM to the PC using the procedure given below. When downloading, note the following points.
89
Handling Section 6-3
!
Caution If the PC is in RUN or MONITOR mode when downloading is started, it will automatically switch to PROGRAM mode and operation will stop. Confirm that no adverse effects will occur to the system before downloading. Not doing so may result in unexpected operation.
Note 1. If the PC is in RUN or MONITOR mode, switch the PC mode to PROGRAM mode.
2. Confirm that the program or other data to be downloaded to the PC is compatible with the PC before downloading.
3. For the CQM1 or CQM1H, when downloading programs that use user-assigned function codes for expansion instructions, be sure that pin 4 on the
CPU Unit’s DIP switch is ON. If these programs are downloaded while the pin is OFF, the assignments for the expansion instructions will return to their default settings.
4. After downloading has been completed, be sure to confirm the user program, data, and expansion instructions.
5. When the DOWNLOAD TO PLC Button is pressed, all EEPROM data (ladder programs, data memory etc.) is written to the PC.
Peripheral port
PERIPHERAL
RS-232C
90
Handling
Operation Procedure
Start
Section
Mount the EEPROM to the
CPM1-EMU01-V1.
Mount the EEPROM to the
CPM1-EMU01-V1 before downloading.
Change the mode of the PC to PRO-
GRAM mode.
Confirm the safety of the system.
Connect the CPM1-EMU01-V1 to the
PC’s peripheral port.
Confirm the orientation of the connector before connecting the CPM1-EMU01-V1.
After 2 or 3 s, check if the indicator is lit green.
No
Yes
Press the DOWNLOAD TO PLC Button.
See the note on the right.
Check if the indicator is blinking green (indicating that downloading has started).
See the note above.
No
Yes
Check if the indicator is lit green
(indicating that downloading has been successfully completed).
No
Yes
Remove the Expansion Memory Unit from the PC.
See the note above.
Note If the indicator is not lit at all, lit red or blinks red, downloading will not be possible. In this case, check the following items.
•
Is the connector properly connected?
•
Is the EEPROM properly mounted?
•
Are the EEPROM specifications correct?
•
Are the peripheral port communications settings correct?
6-3
Check the program.
End
Before actual operation, check the contents of the ladder program and the DM area, as well as the expansion instruction settings.
91
Appendix A
Standard Models
There are three possible power supply configurations.
•
Network Power Supply:
Power is provided from a single source over a network, using special-purpose flat cable.
•
Multiple Power Supply:
Power must be provided separately for communications and I/O. The power supply for communications can be provided via special-purpose flat cable, but the power supply for I/O cannot.
•
Local Power Supply:
Power can be provided from a single source, which can be a source other than the special-purpose flat cable.
SRT1-series Remote Terminals and Sensor Terminals can operate in high-speed communications mode only. Be sure to use SRT2-series Remote Terminals and Sensor Terminals when the SRM1(-V2) is used in long-distance communications mode.
The Analog I/O Terminals can be used with SRM1(-V2) PCs only.
Remote Terminals
SRT2 Series
High-speed or long-distance communications
SRT2-ID04
SRT2-ID04-1
SRT2-ID08
SRT2-ID08-1
SRT2-ID16
SRT2-ID16-1
SRT2-ID16T
SRT2-ID16T-1
SRT2-OD04
SRT2-OD04-1
SRT2-OD08
SRT2-OD08-1
SRT2-OD16
SRT2-OD16-1
SRT2-OD16T
SRT2-OD16T-1
SRT2-ROC08
SRT2-ROC16
SRT2-ROF08
SRT2-ROF16
SRT2-MD16T
SRT2-MD16T-1
SRT1 Series
High-speed communications only
SRT1-ID04
SRT1-ID04-1
SRT1-ID08
SRT1-ID08-1
SRT1-ID16
SRT1-ID16-1
None
SRT1-OD04
SRT1-OD04-1
SRT1-OD08
SRT1-OD08-1
SRT1-OD16
SRT1-OD16-1
None
SRT1-ROC08
SRT1-ROC16
SRT1-ROF08
SRT1-ROF16
None
Specifications
4 transistor inputs, multiple power supply, NPN
4 transistor inputs, multiple power supply, PNP
8 transistor inputs, multiple power supply, NPN
8 transistor inputs, multiple power supply, PNP
16 transistor inputs, multiple power supply, NPN
16 transistor inputs, multiple power supply, PNP
16 transistor inputs, multipoint common terminal, multiple power supply, NPN
16 transistor inputs, multipoint common terminal, multiple power supply, PNP
4 transistor outputs, multiple power supply, NPN
4 transistor outputs, multiple power supply, PNP
8 transistor outputs, multiple power supply, NPN
8 transistor outputs, multiple power supply, PNP
16 transistor outputs, multiple power supply, NPN
16 transistor outputs, multiple power supply, PNP
4 transistor outputs, multiple power supply, NPN
16 transistor outputs, multiple power supply, PNP
8 relay outputs, local power supply
16 relay outputs, local power supply
8 power MOSFET relay outputs, local power supply
16 power MOSFET relay outputs, local power supply
8 transistor inputs/8 transistor outputs, multipoint common terminal, multiple power supply, NPN
8 transistor inputs/8 transistor outputs, multiple power supply, PNP
93
Standard Models Appendix A
Connector Terminals
Model
SRT2-VID08S
SRT2-VID08S-1
SRT2-VID16ML
SRT2-VID16ML-1
SRT2-VOD08S
SRT2-VOD08S-1
SRT2-VOD16ML
SRT2-VOD16ML-1
Specifications
8 transistor inputs, sensor cable connector, multiple power supply, NPN
8 transistor inputs, sensor cable connector, multiple power supply, PNP
16 transistor inputs, MIL connector, multiple power supply, NPN
16 transistor inputs, MIL connector, multiple power supply, PNP
8 transistor outputs, sensor cable connector, multiple power supply, NPN
8 transistor outputs, sensor cable connector, multiple power supply, PNP
16 transistor outputs, MIL connector, multiple power supply, NPN
16 transistor outputs, MIL connector, multiple power supply, PNP
Note All the above models support both high-speed and long-distance communications modes.
Remote I/O Terminals
Model
SRT1-ROF08
SRT1-ROF16
16 inputs, NPN, PCB-mounting type
16 outputs, NPN, PCB-mounting type
Specifications
Note The above models do not support long-distance communications mode.
Sensor Amplifier Terminals
SRT2 Series SRT1 Series
High-speed or long-distance communications
High-speed communications only
SRT2-TID04S (See note.) SRT1-TID04S
SRT2-TKD04S (See note.) SRT1-TKD04S
SRT2-XID04S (See note.) SRT1-XID04S
SRT2-XKD04S (See note.) SRT1-XKD04S
Note To be marketed in the near future.
Specifications
4 inputs (1 word x 4), network power supply
4 inputs (4 words x 1), network power supply
4 inputs (1 word x 4), Expansion Sensor Amplifier Terminal
4 inputs (4 words x 1), Expansion Sensor Amplifier Terminal
Analog I/O Terminals
Model
SRT2-AD04
SRT2-DA02
Specifications
4 analog inputs (settable to 1, 2, 3, or 4 inputs), network power supply
2 analog outputs (settable to 1 or 2 outputs), network power supply
Note All the above models support both high-speed and long-distance communications modes.
Sensor Terminals
SRT2 Series
High-speed or long-distance communications
SRT2-ID08S (See note.)
SRT2-OD08S (See note.)
SRT2-MD08S (See note.)
SRT1 Series
High-speed communications only
SRT1-ID08S
SRT1-OD08S
SRT1-MD08S
Note To be marketed in the near future.
Specifications
8 inputs, network power supply
8 outputs, local power supply
4 inputs, 4 outputs, network power supply
Bit Chain Terminal
Model
SRT1-B1T
Specifications
8 inputs/outputs (I/O set via switch), local power supply
Note The above model does not support long-distance communications mode.
94
Standard Models Appendix A
CPM1A/CPM2A I/O Link Unit
Model
CPM1A-SRT21
Specifications
8 inputs, 8 outputs
Exchanges data with CPM1A/CPM2A CPU Unit.
Note All the above models support both high-speed and long-distance communications modes.
Connection Devices
Communications Cables
Model Specifications
Commercially available VCTF cable (JIS C3306), 0.75 mm 2 x 2 conductors
SCA1-4F10 Special Flat Cable, 100 m, 0.75 mm 2 x 4 conductors
Specified Communications Cables
#9409
Model
Belden
Manufacturer Comments
USA manufacturer
Note The electrical characteristics of the above cable are the same as those of the following: VCTF cable (JIS
C3306), 0.75 mm
2
x 2 conductors. It can thus be used with the same specifications as the VCTF cable listed above.
Connectors and Terminal Blocks
Name
Branch Crimp Connector
Model
SCN1-TH4
Extension Crimp Connector
Terminating Resistor Crimp
Connector
Terminal-block Terminator
SCN1-TH4E
SCN1-TH4T
SRT1-T
Comments
Connector used to branch from the main line. Can be used only on the Special Flat Cable.
Used to extend the Special Flat Cable.
A connector equipped with terminating resistance. Can be used only on the Special Flat Cable.
A terminal block equipped with terminating resistance. Can be used either on the Special Flat Cable or VCTF cable.
SRM1 RS-232C Port Connecting Cable
Model
CQM1-CIF02
Name Specifications
Peripheral Port Conversion Cable For connecting IBM PC/AT compatible computers. (Cable length: 3.3 m)
RS-422 Adapter
Model
CPM1-CIF11
Name
RS-422 Adapter
Specifications
For level conversion between the
Peripheral Port and RS-422
Link Adapters
Model
NT-AL001 Link Adapter
Name Specifications
One RS-232C connector and one
RS-422 terminal block.
Power supply: 5 VDC; 150 mA
95
Standard Models Appendix A
Link Adapter for IBM PC/AT-compatible Computers
Model
3G2A9-AL004-E Link Adapter
Name Specifications
One RS-232C connector, one RS-422 connector, and one fibre-optic connector.
Power supply: 100/200 VAC
Peripheral Devices
Model
CQM1-PRO01-E
Name
CQM1 Programming Console
Specifications
With cable (2 m)
C200H-PRO27-E C200H Programming Console
C200H-CN222
C200H-CN422
C200H-ATT01
WS02-CXPC1-E
C500-ZL3AT1-E
C200H-PRO27-E Connecting
Cable
Mounting Bracket
CX-Programmer
SYSMAC Support Software
Hand-held, with backlight; requires the
C200H-CN222 or C200H-CN422, see below.
Cable length: 2 m
Cable length: 4 m
For panel mounting.
MS-Windows 95/98 (CD-ROM) for Ver.
2.0 or higher
3.5”, 2HD for IBM PC/AT compatible
WS01-CPTB1-E
CPM1-EMU01-V1
SYSMAC-CPT
Expansion Memory Unit
For IBM PC/AT or compatible computers
(3.5” disks (2HD) and CDROM)
Uploads the ladder program and
DM 6144 to DM 6655 from the PC to the EEPROM and downloads the ladder program and DM 6144 to DM
6655 from the EEPROM to the PC.
EEROM-JD EEPROM 256 K bit
96
Appendix B
External Dimensions
The external dimensions of the SRM1 are as shown in the following diagram.
15
(Unit: mm)
4
5
8
30
40
5
60
36
When mounting a Peripheral Device, be sure to allow sufficient space as shown in the following diagram.
(Unit: mm)
70
97
*DM
1:1 PC Link
ACP add count input address
AND area area prefix arithmetic shift
ASCII
AR Area
AUTOEXEC.BAT
back-up basic instruction baud rate
BCD
BCD calculation binary binary calculation binary-coded decimal bit bit address
Glossary
Indirectly addressed DM area. See indirect address and DM area.
A link created between two PCs to create common data in their LR areas.
See add count input.
An input signal used to increment a counter when the signal changes from OFF to ON.
A number used to identify the location of data or programming instructions in memory.
A logic operation whereby the result is true if and only if both premises are true.
In ladder-diagram programming the premises are usually ON/OFF states of bits or the logical combination of such states called execution conditions.
See data area and memory area.
A one or two letter prefix used to identify a memory area in the PC. All memory areas except the IR and SR areas require prefixes to identify addresses in them.
A shift operation wherein the carry flag is included in the shift.
Short for American Standard Code for Information Interchange. ASCII is used to code characters for output to printers and other external devices.
A PC data area allocated to flags and control bits.
An MS DOS file containing commands automatically executed at startup.
A copy made of existing data to ensure that the data will not be lost even if the original data is corrupted or erased.
A fundamental instruction used in a ladder diagram. See advanced instruction.
The data transmission speed between two devices in a system measured in bits per second.
See binary-coded decimal.
An arithmetic calculation that uses numbers expressed in binary-coded decimal.
A number system where all numbers are expressed in base 2, i.e., numbers are written using only 0’s and 1’s. Each group of four binary bits is equivalent to one hexadecimal digit. Binary data in memory is thus often expressed in hexadecimal for convenience.
An arithmetic calculation that uses numbers expressed in binary.
A system used to represent numbers so that every four binary bits is numerically equivalent to one decimal digit.
The smallest piece of information that can be represented on a computer. A bit has the value of either zero or one, corresponding to the electrical signals ON and OFF. A bit represents one binary digit. Some bits at particular addresses are allocated to special purposes, such as holding the status of input from external devices, while other bits are available for general use in programming.
The location in memory where a bit of data is stored. A bit address specifies the data area and word that is being addressed as well as the number of the bit within the word.
99
bit designator bit number bit-control instruction block building-block PC bus bus bar byte call
Carry Flag central processing unit
CH channel character code checksum clock pulse clock pulse bit common data communications cable comparison instruction
Glossary
An operand that is used to designate the bit or bits of a word to be used by an instruction.
A number that indicates the location of a bit within a word. Bit 00 is the rightmost
(least-significant) bit; bit 15 is the leftmost (most-significant) bit.
An instruction that is used to control the status of an individual bit as opposed to the status of an entire word.
See logic block and instruction block.
A PC that is constructed from individual components, or “building blocks.” With building-block PCs, there is no one Unit that is independently identifiable as a
PC. The PC is rather a functional assembly of Units.
A communications path used to pass data between any of the Units connected to it.
The line leading down the left and sometimes right side of a ladder diagram. Instruction execution proceeds down the bus bar, which is the starting point for all instruction lines.
A unit of data equivalent to 8 bits, i.e., half a word.
A process by which instruction execution shifts from the main program to a subroutine. The subroutine may be called by an instruction or by an interrupt.
A flag that is used with arithmetic operations to hold a carry from an addition or multiplication operation, or to indicate that the result is negative in a subtraction operation. The carry flag is also used with certain types of shift operations.
A device that is capable of storing programs and data, and executing the instructions contained in the programs. In a PC System, the central processing unit executes the program, processes I/O signals, communicates with external devices, etc.
See word.
See word.
A numeric (usually binary) code used to represent an alphanumeric character.
A sum transmitted with a data pack in communications. The checksum can be recalculated from the received data to confirm that the data in the transmission has not been corrupted.
A pulse available at specific bits in memory for use in timing operations. Various clock pulses are available with different pulse widths, and therefore different frequencies.
A bit in memory that supplies a pulse that can be used to time operations. Various clock pulse bits are available with different pulse widths, and therefore different frequencies.
Data that is stored in a memory of a PC and which is shared by other PCs in the same the same system. Each PC has a specified section(s) of the area allocated to it. Each PC writes to the section(s) allocated to it and reads the sections allocated to the other PCs with which it shares the common data.
Cable used to transfer data between components of a control system and conforming to the RS-232C or RS-422 standards.
An instruction used to compare data at different locations in memory to determine the relationship between the data.
100
Completion Flag condition
CONFIG.SYS
constant control bit control data control signal
Control System controlled system count pulse counter
CPU Unit
CTS
CY cycle cycle time cyclic interrupt data area data area boundary data disk data length
Glossary
A flag used with a timer or counter that turns ON when the timer has timed out or the counter has reached its set value.
A symbol placed on an instruction line to indicate an instruction that controls the execution condition for the terminal instruction. Each condition is assigned a bit in memory that determines its status. The status of the bit assigned to each condition determines the next execution condition. Conditions correspond to LOAD,
LOAD NOT, AND, AND NOT, OR, or OR NOT instructions.
An MS DOS file containing environment settings for a personal computer.
An input for an operand in which the actual numeric value is specified. Constants can be input for certain operands in place of memory area addresses. Some operands must be input as constants.
A bit in a memory area that is set either through the program or via a Programming Device to achieve a specific purpose, e.g., a Restart Bit is turned ON and
OFF to restart a Unit.
An operand that specifies how an instruction is to be executed. The control data may specify the part of a word is to be used as the operand, it may specify the destination for a data transfer instructions, it may specify the size of a data table used in an instruction, etc.
A signal sent from the PC to effect the operation of the controlled system.
All of the hardware and software components used to control other devices. A
Control System includes the PC System, the PC programs, and all I/O devices that are used to control or obtain feedback from the controlled system.
The devices that are being controlled by a PC System.
The signal counted by a counter.
A dedicated group of digits or words in memory used to count the number of times a specific process has occurred, or a location in memory accessed through a TIM/CNT bit and used to count the number of times the status of a bit or an execution condition has changed from OFF to ON.
See central processing unit.
An acronym for clear-to-send, a signal used in communications between electronic devices to indicate that the receiver is ready to accept incoming data.
See Carry Flag.
One unit of processing performed by the CPU Unit, including ladder program execution, peripheral servicing, I/O refreshing, etc.
The time required to complete one cycle of CPU Unit processing.
See scheduled interrupt.
An area in the PC’s memory that is designed to hold a specific type of data.
The highest address available within a data area. When designating an operand that requires multiple words, it is necessary to ensure that the highest address in the data area is not exceeded.
A floppy disk used to same user programs, DM area contents, comments, and other user data.
In communications, the number of bits that is to be treated as one unit in data transmissions.
101
Glossary data link data trace
An automatic data transmission operation that allows PCs or Units within PC to pass data back and forth via common data areas.
A common data area established through a data link.
data link area data movement instruction An instruction used to move data from one location in memory to another. The data in the original memory location is left unchanged.
data sharing The process in which common data areas or common data words are created between two or more PCs.
A process in which changes in the contents of specific memory locations are recorded during program execution.
data transfer debug decimal decrement default
Moving data from one memory location to another, either within the same device or between different devices connected via a communications line or network.
A process by which a draft program is corrected until it operates as intended.
Debugging includes both the removal of syntax errors, as well as the fine-tuning of timing and coordination of control operations.
A number system where numbers are expressed to the base 10. In a PC all data is ultimately stored in binary form, four binary bits are often used to represent one decimal digit, via a system called binary-coded decimal.
Decreasing a numeric value, usually by 1.
definer destination
A value automatically set by the PC when the user does not specifically set another value. Many devices will assume such default conditions upon the application of power.
A number used as an operand for an instruction but that serves to define the instruction itself, rather that the data on which the instruction is to operate. Definers include jump numbers, subroutine numbers, etc.
The location where an instruction places the data on which it is operating, as opposed to the location from which data is taken for use in the instruction. The location from which data is taken is called the source.
differentiated instruction differentiation instruction digit digit designator
DIN track
DIP switch direct output distributed control
An instruction that is executed only once each time its execution condition goes from OFF to ON. Non-differentiated instructions are executed for each scan as long as the execution condition stays ON.
An instruction used to ensure that the operand bit is never turned ON for more than one scan after the execution condition goes either from OFF to ON for a
Differentiate Up instruction or from ON to OFF for a Differentiate Down instruction.
A unit of storage in memory that consists of four bits.
An operand that is used to designate the digit or digits of a word to be used by an instruction.
A rail designed to fit into grooves on various devices to allow the devices to be quickly and easily mounted to it.
Dual in-line package switch, an array of pins in a signal package that is mounted to a circuit board and is used to set operating parameters.
A method in which program execution results are output immediately to eliminate the affects of the cycle time.
A automation concept in which control of each portion of an automated system is located near the devices actually being controlled, i.e., control is decentralized and ‘distributed’ over the system. Distributed control is a concept basic to PC
Systems.
102
DM area
DM word downloading
EEPROM electrical noise
EPROM error code
Error Log Area even parity event processing exclusive NOR exclusive OR execution condition execution cycle execution time extended counter extended timer
FA factory computer
Glossary
A data area used to hold only word data. Words in the DM area cannot be accessed bit by bit.
A word in the DM area.
The process of transferring a program or data from a higher-level or host computer to a lower-level or slave computer. If a Programming Device is involved, the Programming Device is considered the host computer.
Electrically erasable programmable read-only memory; a type of ROM in which stored data can be erased and reprogrammed. This is accomplished using a special control lead connected to the EEPROM chip and can be done without having to remove the EEPROM chip from the device in which it is mounted.
Random variations of one or more electrical characteristics such as voltage, current, and data, which might interfere with the normal operation of a device.
Erasable programmable read-only memory; a type of ROM in which stored data can be erased, by ultraviolet light or other means, and reprogrammed.
A numeric code generated to indicate that an error exists, and something about the nature of the error. Some error codes are generated by the system; others are defined in the program by the operator.
An area used to store records indicating the time and nature of errors that have occurred in the system.
A communication setting that adjusts the number of ON bits so that it is always even. See parity.
Processing that is performed in response to an event, e.g., an interrupt signal.
A logic operation whereby the result is true if both of the premises are true or both of the premises are false. In ladder-diagram programming, the premises are usually the ON/OFF states of bits, or the logical combination of such states, called execution conditions.
A logic operation whereby the result is true if one, and only one, of the premises is true. In ladder-diagram programming the premises are usually the ON/OFF states of bits, or the logical combination of such states, called execution conditions.
The ON or OFF status under which an instruction is executed. The execution condition is determined by the logical combination of conditions on the same instruction line and up to the instruction currently being executed.
The cycle used to execute all processes required by the CPU Unit, including program execution, I/O refreshing, peripheral servicing, etc.
The time required for the CPU Unit to execute either an individual instruction or an entire program.
A counter created in a program by using two or more count instructions in succession. Such a counter is capable of counting higher than any of the standard counters provided by the individual instructions.
A timer created in a program by using two or more timers in succession. Such a timer is capable of timing longer than any of the standard timers provided by the individual instructions.
Factory automation.
A general-purpose computer, usually quite similar to a business computer, that is used in automated factory control.
103
FAL error
FALS error fatal error
FCS flag flicker bit floating-point decimal force reset force set forced status frame checksum function code hardware error header code hexadecimal host computer host interface host link
HR area
I/O bit
I/O capacity
Glossary
An error generated from the user program by execution of an FAL(06) instruction.
An error generated from the user program by execution of an FALS(07) instruction or an error generated by the system.
An error that stops PC operation and requires correction before operation can continue.
See frame checksum.
A dedicated bit in memory that is set by the system to indicate some type of operating status. Some flags, such as the carry flag, can also be set by the operator or via the program.
A bit that is programmed to turn ON and OFF at a specific frequency.
A decimal number expressed as a number (the mantissa) multiplied by a power of 10, e.g., 0.538 x 10
–5
.
The process of forcibly turning OFF a bit via a programming device. Bits are usually turned OFF as a result of program execution.
The process of forcibly turning ON a bit via a programming device. Bits are usually turned ON as a result of program execution.
The status of bits that have been force reset or force set.
The results of exclusive ORing all data within a specified calculation range. The frame checksum can be calculated on both the sending and receiving end of a data transfer to confirm that data was transmitted correctly.
A two-digit number used to input an instruction into the PC.
An error originating in the hardware structure (electronic components) of the PC, as opposed to a software error, which originates in software (i.e., programs).
A code in an instruction that specifies what the instruction is to do.
A number system where all numbers are expressed to the base 16. In a PC all data is ultimately stored in binary form, however, displays and inputs on Programming Devices are often expressed in hexadecimal to simplify operation.
Each group of four binary bits is numerically equivalent to one hexadecimal digit.
A computer that is used to transfer data to or receive data from a PC in a Host
Link system. The host computer is used for data management and overall system control. Host computers are generally small personal or business computers.
An interface that allows communications with a host computer.
An interface connecting a PC to a host computer to enable monitoring or program control from the host computer.
A memory area that preserves bit status during power interrupts and used as work bits in programming.
A bit in memory used to hold I/O status. Input bits reflect the status of input terminals; output bits hold the status for output terminals.
The number of inputs and outputs that a PC is able to handle. This number ranges from around one hundred for smaller PCs to two thousand for the largest ones.
104
I/O delay
I/O device
I/O interrupt
I/O point
I/O refreshing
I/O response time
I/O Unit
I/O word
IBM PC/AT or compatible increment indirect address initialization error initialize input input bit input device input point input signal install instruction
Glossary
The delay in time from when a signal is sent to an output to when the status of the output is actually in effect or the delay in time from when the status of an input changes until the signal indicating the change in the status is received.
A device connected to the I/O terminals on I/O Units. I/O devices may be either part of the Control System, if they function to help control other devices, or they may be part of the controlled system.
An interrupt generated by a signal from I/O.
The place at which an input signal enters the PC System, or at which an output signal leaves the PC System. In physical terms, I/O points correspond to terminals or connector pins on a Unit; in terms of programming, an I/O points correspond to I/O bits in the IR area.
The process of updating output status sent to external devices so that it agrees with the status of output bits held in memory and of updating input bits in memory so that they agree with the status of inputs from external devices.
The time required for an output signal to be sent from the PC in response to an input signal received from an external device.
The Units in a PC that are physically connected to I/O devices to input and output signals. I/O Units include Input Units and Output Units, each of which is available in a range of specifications.
A word in the IR area that is allocated to a Unit in the PC System and is used to hold I/O status for that Unit.
A computer that has similar architecture to, that is logically compatible with, and that can run software designed for an IBM PC/AT computer.
Increasing a numeric value, usually by 1.
An address whose contents indicates another address. The contents of the second address will be used as the actual operand.
An error that occurs either in hardware or software during the PC System startup, i.e., during initialization.
Part of the startup process whereby some memory areas are cleared, system setup is checked, and default values are set.
The signal coming from an external device into the PC. The term input is often used abstractly or collectively to refer to incoming signals.
A bit in the IR area that is allocated to hold the status of an input.
An external device that sends signals into the PC System.
The point at which an input enters the PC System. Input points correspond physically to terminals or connector pins.
A change in the status of a connection entering the PC. Generally an input signal is said to exist when, for example, a connection point goes from low to high voltage or from a nonconductive to a conductive state.
The preparation necessary to use a program or software package, such as the
LSS or SSS, on a computer.
A direction given in the program that tells the PC of the action to be carried out, and the data to be used in carrying out the action. Instructions can be used to simply turn a bit ON or OFF, or they can perform much more complex actions, such as converting and/or transferring large blocks of data.
105
Glossary instruction block instruction execution time The time required to execute an instruction. The execution time for any one instruction can vary with the execution conditions for the instruction and the operands used in it.
instruction line
A group of instructions that is logically related in a ladder-diagram program. A logic block includes all of the instruction lines that interconnect with each other from one or more line connecting to the left bus bar to one or more right-hand instructions connecting to the right bus bar.
A group of conditions that lie together on the same horizontal line of a ladder diagram. Instruction lines can branch apart or join together to form instruction blocks. Also called a rung.
interface interlock interrupt (signal)
An interface is the conceptual boundary between systems or devices and usually involves changes in the way the communicated data is represented. Interface devices perform operations like changing the coding, format, or speed of the data.
A programming method used to treat a number of instructions as a group so that the entire group can be reset together when individual execution is not required.
An interlocked program section is executed normally for an ON execution condition and partially reset for an OFF execution condition.
A signal that stops normal program execution and causes a subroutine to be run or other processing to take place.
interrupt program inverse condition
JIS jump jump number ladder diagram (program) ladder diagram symbol
A program that is executed in response to an interrupt.
See normally closed condition.
An acronym for Japanese Industrial Standards.
A type of programming where execution moves directly from one point in a program to another, without sequentially executing any instructions in between.
A definer used with a jump that defines the points from and to which a jump is to be made.
A form of program arising out of relay-based control systems that uses circuit-type diagrams to represent the logic flow of programming instructions. The appearance of the program is similar to a ladder, and thus the name.
A symbol used in drawing a ladder-diagram program.
ladder instruction
Ladder Support Software
An instruction that represents the conditions on a ladder-diagram program. The other instructions in a ladder diagram fall along the right side of the diagram and are called terminal instructions.
A software package installed on a IBM PC/AT or compatible computer to function as a Programming Device.
least-significant (bit/word) See rightmost (bit/word).
LED Acronym for light-emitting diode; a device used as for indicators or displays.
leftmost (bit/word) link
The highest numbered bits of a group of bits, generally of an entire word, or the highest numbered words of a group of words. These bits/words are often called most-significant bits/words.
A hardware or software connection formed between two Units. “Link” can refer either to a part of the physical connection between two Units or a software connection created to data existing at another location (i.e., data links).
106
Glossary load logic block logic block instruction logic instruction
The processes of copying data either from an external device or from a storage area to an active portion of the system such as a display buffer. Also, an output device connected to the PC is called a load.
A group of instructions that is logically related in a ladder-diagram program and that requires logic block instructions to relate it to other instructions or logic blocks.
An instruction used to locally combine the execution condition resulting from a logic block with a current execution condition. The current execution condition could be the result of a single condition, or of another logic block. AND Load and
OR Load are the two logic block instructions.
Instructions used to logically combine the content of two words and output the logical results to a specified result word. The logic instructions combine all the same-numbered bits in the two words and output the result to the bit of the same number in the specified result word.
LR area
LSS main program mark trace masked bit masking megabyte memory area message number mnemonic code
A data area that is used in data links.
See Ladder Support Software.
All of a program except for subroutine and interrupt programs.
A process in which changes in the contents of specific memory locations are recorded during program execution.
A bit whose status has been temporarily made ineffective.
‘Covering’ an interrupt signal so that the interrupt is not effective until the mask is removed.
A unit of storage equal to one million bytes.
Any of the areas in the PC used to hold data or programs.
A number assigned to a message generated with the MESSAGE instruction.
A form of a ladder-diagram program that consists of a sequential list of the instructions without using a ladder diagram.
MONITOR mode most-significant (bit/word) See leftmost (bit/word).
NC input An input that is normally closed, i.e., the input signal is considered to be present when the circuit connected to the input opens.
negative delay
A mode of PC operation in which normal program execution is possible, and which allows modification of data held in memory. Used for monitoring or debugging the PC.
nesting
NO input noise interference non-fatal error
A delay set for a data trace in which recording data begins before the trace signal by a specified amount.
Programming one loop within another loop, programming a call to a subroutine within another subroutine, or programming one jump within another.
An input that is normally open, i.e., the input signal is considered to be present when the circuit connected to the input closes.
Disturbances in signals caused by electrical noise.
A hardware or software error that produces a warning but does not stop the PC from operating.
107
Glossary normal condition normally closed condition normally open condition
NOT
OFF
OFF delay offset
ON
ON delay one-shot bit one-to-one link online edit operand operand bit operand word operating modes operating error
OR output output bit
See normally open condition.
A condition that produces an ON execution condition when the bit assigned to it is OFF, and an OFF execution condition when the bit assigned to it is ON.
A condition that produces an ON execution condition when the bit assigned to it is ON, and an OFF execution condition when the bit assigned to it is OFF.
A logic operation which inverts the status of the operand. For example, AND
NOT indicates an AND operation with the opposite of the actual status of the operand bit.
The status of an input or output when a signal is said not to be present. The OFF state is generally represented by a low voltage or by non-conductivity, but can be defined as the opposite of either.
The delay between the time when a signal is switched OFF (e.g., by an input device or PC) and the time when the signal reaches a state readable as an OFF signal (i.e., as no signal) by a receiving party (e.g., output device or PC).
A positive or negative value added to a base value such as an address to specify a desired value.
The status of an input or output when a signal is said to be present. The ON state is generally represented by a high voltage or by conductivity, but can be defined as the opposite of either.
The delay between the time when an ON signal is initiated (e.g., by an input device or PC) and the time when the signal reaches a state readable as an ON signal by a receiving party (e.g., output device or PC).
A bit that is turned ON or OFF for a specified interval of time which is longer than one scan.
See 1:1 PC Link.
The process of changed the program directly in the PC from a Programming Device. Online editing is possible in PROGRAM or MONITOR mode. In MONITOR mode, the program can actually be changed while it is being
The values designated as the data to be used for an instruction. An operand can be input as a constant expressing the actual numeric value to be used or as an address to express the location in memory of the data to be used.
A bit designated as an operand for an instruction.
A word designated as an operand for an instruction.
One of three PC modes: PROGRAM mode, MONITOR mode, and RUN mode.
An error that occurs during actual PC operation as opposed to an initialization error, which occurs before actual operations can begin.
A logic operation whereby the result is true if either of two premises is true, or if both are true. In ladder-diagram programming the premises are usually ON/OFF states of bits or the logical combination of such states called execution conditions.
The signal sent from the PC to an external device. The term output is often used abstractly or collectively to refer to outgoing signals.
A bit in the IR area that is allocated to hold the status to be sent to an output device.
108
output device output point output signal overflow overseeing overwrite parity parity check
PC
PC configuration
PC System
PCB
PC Setup
Peripheral Device peripheral servicing port positive delay
Power Supply Unit present value printed circuit board
PROGRAM mode
Programmable Controller
Glossary
An external device that receives signals from the PC System.
The point at which an output leaves the PC System. Output points correspond physically to terminals or connector pins.
A signal being sent to an external device. Generally an output signal is said to exist when, for example, a connection point goes from low to high voltage or from a nonconductive to a conductive state.
The state where the capacity of a data storage location has been exceeded.
Part of the processing performed by the CPU Unit that includes general tasks required to operate the PC.
Changing the content of a memory location so that the previous content is lost.
Adjustment of the number of ON bits in a word or other unit of data so that the total is always an even number or always an odd number. Parity is generally used to check the accuracy of data after being transmitted by confirming that the number of ON bits is still even or still odd.
Checking parity to ensure that transmitted data has not been corrupted.
See Programmable Controller.
The arrangement and interconnections of the Units that are put together to form a functional PC.
With building-block PCs, all of the Units connected up to, but not including, the
I/O devices. The boundaries of a PC System are the PC and the program in its
CPU Unit at the upper end; and the I/O Units at the lower end.
See printed circuit board.
A group of operating parameters set in the PC from a Programming Device to control PC operation.
Devices connected to a PC System to aid in system operation. Peripheral devices include printers, programming devices, external storage media, etc.
Processing signals to and from peripheral devices, including refreshing, communications processing, interrupts, etc.
A connector on a PC or computer that serves as a connection to an external device.
A delay set for a data trace in which recording data begins after the trace signal by a specified amount.
A Unit that connected to a PC that provides power at the voltage required by the other Units.
The current value registered in a device at any instant during its operation. Present value is abbreviated as PV. The use of this term is generally restricted to timers and counters.
A board onto which electrical circuits are printed for mounting into a computer or electrical device.
A mode of operation that allows inputting and debugging of programs to be carried out, but that does not permit normal execution of the program.
A computerized device that can accept inputs from external devices and generate outputs to external devices according to a program held in memory. Programmable Controllers are used to automate control of external devices. Although single-unit Programmable Controllers are available, building-block Programmable Controllers are constructed from separate components. Such Programmable Controllers are formed only when enough of these separate components are assembled to form a functional assembly.
109
programmed alarm programmed error programmed message
Programming Console
Programming Device
PROM prompt protocol
PV
RAM
RAS read-only area refresh relay-based control reserved bit reserved word reset response code response format response monitoring time
Restart Bit result word
110
Glossary
An alarm given as a result of execution of an instruction designed to generate the alarm in the program, as opposed to one generated by the system.
An error arising as a result of the execution of an instruction designed to generate the error in the program, as opposed to one generated by the system.
A message generated as a result of execution of an instruction designed to generate the message in the program, as opposed to one generated by the system.
The portable form of Programming Device for a PC.
A Peripheral Device used to input a program into a PC or to alter or monitor a program already held in the PC. There are dedicated programming devices, such as Programming Consoles, and there are non-dedicated devices, such as a host computer.
Programmable read-only memory; a type of ROM into which the program or data may be written after manufacture, by a customer, but which is fixed from that time on.
A message or symbol that appears on a display to request input from the operator.
The parameters and procedures that are standardized to enable two devices to communicate or to enable a programmer or operator to communicate with a device.
See present value.
Random access memory; a data storage media. RAM will not retain data when power is disconnected.
An acronym for reliability, assurance, safety.
A memory area from which the user can read status but to which data cannot be written.
The process of updating output status sent to external devices so that it agrees with the status of output bits held in memory and of updating input bits in memory so that they agree with the status of inputs from external devices.
The forerunner of PCs. In relay-based control, groups of relays are interconnected to form control circuits. In a PC, these are replaced by programmable circuits.
A bit that is not available for user application.
A word in memory that is reserved for a special purpose and cannot be accessed by the user.
The process of turning a bit or signal OFF or of changing the present value of a timer or counter to its set value or to zero.
A code sent with the response to a data transmission that specifies how the transmitted data was processed.
A format specifying the data required in a response to a data transmission.
The time a device will wait for a response to a data transmission before assuming that an error has occurred.
A bit used to restart part of a PC.
A word used to hold the results from the execution of an instruction.
retrieve retry return reversible counter reversible shift register right-hand instruction rightmost (bit/word) rising edge
ROM rotate register
RS-232C interface
RUN mode rung scan scan time scheduled interrupt
SCP seal self diagnosis self-maintaining bit series servicing
Glossary
The processes of copying data either from an external device or from a storage area to an active portion of the system such as a display buffer. Also, an output device connected to the PC is called a load.
The process whereby a device will re-transmit data which has resulted in an error message from the receiving device.
The process by which instruction execution shifts from a subroutine back to the main program (usually the point from which the subroutine was called).
A counter that can be both incremented and decremented depending on the specified conditions.
A shift register that can shift data in either direction depending on the specified conditions.
See terminal instruction.
The lowest numbered bits of a group of bits, generally of an entire word, or the lowest numbered words of a group of words. These bits/words are often called least-significant bits/words.
The point where a signal actually changes from an OFF to an ON status.
Read only memory; a type of digital storage that cannot be written to. A ROM chip is manufactured with its program or data already stored in it and can never be changed. However, the program or data can be read as many times as desired.
A shift register in which the data moved out from one end is placed back into the shift register at the other end.
An industry standard for serial communications.
The operating mode used by the PC for normal control operations.
See instruction line.
The process used to execute a ladder-diagram program. The program is examined sequentially from start to finish and each instruction is executed in turn based on execution conditions.
See cycle time.
An interrupt that is automatically generated by the system at a specific time or program location specified by the operator. Scheduled interrupts result in the execution of specific subroutines that can be used for instructions that must be executed repeatedly at a specified interval of time.
See subtract count input.
See self-maintaining bit.
A process whereby the system checks its own operation and generates a warning or error if an abnormality is discovered.
A bit that is programmed to maintain either an OFF or ON status until set or reset by specified conditions.
A wiring method in which Units are wired consecutively in a string.
The process whereby the PC checks a connector or Unit to see if special processing is required.
111
set set value shift input signal shift register signed binary signed decimal software error software protect source (word) special instruction
SR area
SSS store subroutine subroutine number subtract count input
SV switching capacity synchronous execution syntax syntax error
Glossary
The process of turning a bit or signal ON.
The value from which a decrementing counter starts counting down or to which an incrementing counter counts up (i.e., the maximum count), or the time from which or for which a timer starts timing. Set value is abbreviated SV.
An input signal whose OFF to ON transition causes data to be shifted one bit.
One or more words in which data is shifted a specified number of units to the right or left in bit, digit, or word units. In a rotate register, data shifted out one end is shifted back into the other end. In other shift registers, new data (either specified data, zero(s) or one(s)) is shifted into one end and the data shifted out at the other end is lost.
A binary value that is stored in memory along with a bit that indicates whether the value is positive or negative.
One-word signed hexadecimal values stored in the two’s complement format can be displayed at the Programming Console as decimal values from –32,768 to 32,767.
An error that originates in a software program.
A means of protecting data from being changed that uses software as opposed to a physical switch or other hardware setting.
The location from which data is taken for use in an instruction, as opposed to the location to which the result of an instruction is to be written. The latter is called the destination.
An instruction input with a function code that handles data processing operations within ladder diagrams, as opposed to a basic instruction, which makes up the fundamental portion of a ladder diagram.
A memory area containing flags and other bits/words with specific functions.
See SYSMAC Support Software.
The process of recording a program written into a display buffer permanently in memory.
A group of instructions placed separate from the main program and executed only when called from the main program or activated by an interrupt.
A definer used to identify the subroutine that a subroutine call or interrupt activates.
An input signal used to decrement a counter when the signal changes from OFF to ON.
See set value.
The maximum voltage/current that a relay can safely switch on and off.
Execution of programs and servicing operations in which program execution and servicing are synchronized so that all servicing operations are executed each time the programs are executed.
The form of a program statement (as opposed to its meaning).
An error in the way in which a program is written. Syntax errors can include
‘spelling’ mistakes (i.e., a function code that does not exist), mistakes in specifying operands within acceptable parameters (e.g., specifying read-only bits as a destination), and mistakes in actual application of instructions (e.g., a call to a subroutine that does not exist).
112
Glossary
SYSMAC Support Software A software package installed on a IBM PC/AT or compatible computer to function as a Programming Device.
system configuration The arrangement in which Units in a System are connected. This term refers to the conceptual arrangement and wiring together of all the devices needed to comprise the System.
system error system error message
An error generated by the system, as opposed to one resulting from execution of an instruction designed to generate an error.
An error message generated by the system, as opposed to one resulting from execution of an instruction designed to generate a message.
system setup terminal instruction timer
TR area
TR bit trace
Operating environment settings for a Programming Device, e.g., the LSS or
SSS.
An instruction placed on the right side of a ladder diagram that uses the final execution conditions of an instruction line.
A location in memory accessed through a TIM/CNT bit and used to time down from the timer’s set value. Timers are turned ON and reset according to their execution conditions.
A data area used to store execution conditions so that they can be reloaded later for use with other instructions.
A bit in the TR area.
An operation whereby the program is executed and the resulting data is stored to enable step-by-step analysis and debugging.
trace memory transfer transmission distance trigger trigger address
UM area
Unit unit number unmasked bit unsigned binary unsigned decimal
A memory area used to store the results of trace operations.
The process of moving data from one location to another within the PC, or between the PC and external devices. When data is transferred, generally a copy of the data is sent to the destination, i.e., the content of the source of the transfer is not changed.
The distance that a signal can be transmitted.
A signal used to activate some process, e.g., the execution of a trace operation.
An address in the program that defines the beginning point for tracing. The actual beginning point can be altered from the trigger by defining either a positive or negative delay.
The memory area used to hold the active program, i.e., the program that is being currently executed.
In OMRON PC terminology, the word Unit is capitalized to indicate any product sold for a PC System. Most of the names of these products end with the word
Unit.
A number assigned to some Units to facilitate identification when assigning words or other operating parameters.
A bit whose status is effective. See masked bit.
A binary value that is stored in memory without any indication of whether it is positive or negative.
One-word hexadecimal values can be displayed at the Programming Console as decimal values from 0 to 65,535.
113
uploading watchdog timer
WDT word word address work area work bit work word write protect switch write-protect
Glossary
The process of transferring a program or data from a lower-level or slave computer to a higher-level or host computer. If a Programming Devices is involved, the Programming Device is considered the host computer.
A timer within the system that ensures that the scan time stays within specified limits. When limits are reached, either warnings are given or PC operation is stopped depending on the particular limit that is reached.
See watchdog timer.
A unit of data storage in memory that consists of 16 bits. All data areas consists of words. Some data areas can be accessed only by words; others, by either words or bits.
The location in memory where a word of data is stored. A word address must specify (sometimes by default) the data area and the number of the word that is being addressed.
A part of memory containing work words/bits.
A bit in a work word.
A word that can be used for data calculation or other manipulation in programming, i.e., a ‘work space’ in memory. A large portion of the IR area is always reserved for work words. Parts of other areas not required for special purposes may also be used as work words.
A switch used to write-protect the contents of a storage device, e.g., a floppy disk. If the hole on the upper left of a floppy disk is open, the information on this floppy disk cannot be altered.
A state in which the contents of a storage device can be read but cannot be altered.
114
A–B accessibility, 20 allocations data areas, 9
I/O, 8
ASCII, converting displays, Programming Console, 57 binary data, modifying, Programming Console, 54 bit status, force-set/reset, Programming Console, 56 bits, searching, Programming Console, 42 buzzer operation, Programming Console, 39
C cabinet installation, precautions, 19
Programming Console installation, 35 cable connections
NT Link
1:1, 30
1:N, 31
RS-232C, 24 characteristics, 13 check levels, program checks, 75 checking, program syntax, Programming Console, 47, 71 clearing, memory areas, Programming Console, 37, 62 communications
CompoBus/S specifications, 14 errors, 72
Host Link connections, 26 modes, 6
NT Link, 30
PC Link, 1:1, 31
CompoBus/S communications specifications, 14 wiring, 23 components, Units, 15 conduit installation, 22 configuration, 3 counters, changing SV, Programming Console, 52 crimp connectors, 22 cycle time, displaying, Programming Console, 58
Index
D data, modifying, Programming Console, 52, 53, 54, 55, 56 data areas, 9 data link, 31 decimal data with sign. See signed decimal data decimal data without sign. See unsigned decimal data differentiated instructions, entering, 45 dimensions, 97
DIN track, installation, 20 displays converting between hex and ASCII, Programming Console,
57 cycle time, Programming Console, 58 downloading, programs, 89 duct installation, 21
E
EEPROM mounting/removing, 86 specifications, 85 electrical noise, preventing, 19, 21
ERR/ALM indicator flashing, 72 lit, 73 errors communications, 72 error processing, 59 fatal, 72 identifying, 73 non-fatal, 72 programming, 75
Programming Console operations, 75 reading/clearing messages, Programming Console, 38, 74 user-defined errors, 73 expansion instructions, setting, Programming Console, 40–41
Expansion Memory Unit, 83 connections, 87
F
FAL numbers, 72
FAL(06), 73
FALS numbers, 72
FALS(07), 74 fatal errors, troubleshooting, 79 features, 2 flash memory, precautions, 61 force-set/reset clearing, Programming Console, 57
Programming Console, 56 functions, 2
115
H hexadecimal data, converting displays, Programming Console,
57 high-speed communications mode, 6 host computer, connecting, 26
Host Link, connections, 26
Host Link communications
1:1, 27 cables, 27
1:N, 28 cables, 29
Index unsigned decimal data, Programming Console, 56
MONITOR mode, description, 36 monitoring
3-word monitor, Programming Console, 50–51 binary monitor, Programming Console, 50 differentiation monitor, Programming Console, 49–50 signed decimal monitor, Programming Console, 51 status, Programming Console, 47 unsigned decimal monitor, Programming Console, 51–52
MSG(46), 74
I
I/O allocation, 8
I/O line noise, preventing, 21
IBM PC/AT or compatible computer, 7 indicators, 16 flashing ERR/ALM indicator, 72 lit ERR/ALM indicator, 73 installation
DIN track, 20 horizontal surface, 20 precautions, 19 instructions inserting and deleting, Programming Console, 43 searching, Programming Console, 41 interlock circuit, example, 18 interval timer, 2
N noise, preventing electrical noise, 19, 21 non-fatal errors, troubleshooting, 80
NT Link
1:1, 30
1:N, 30
NT Link communications
1:1, 30
1:N, 30 cable connections, 30, 31
L–M limit circuit, 18 lithium battery, backup time vs. temperature, xv, 14 long-distance communications mode, 6 memory backup, 2
Expansion Memory Unit, 83 memory areas clearing, Programming Console, 37, 62 partial clear, 38, 62 uploading/downloading, 84 messages, reading/clearing, 38, 74 mode, changing the PC mode, 35 models, SRM1 models, 4 modifying binary data, Programming Console, 54 data, Programming Console, 52 hexadecimal/BCD data, Programming Console, 53 signed decimal data, Programming Console, 55
SV, Programming Console, 52
O–P operating conditions, troubleshooting, 82 overheating, 19 panel, Programming Console installation, 35 panel installation, precautions, 19
PC Link communications, 1:1, 31 cable connections, 32 restrictions, 32
PC mode, changing, 35
Peripheral Devices, connecting, 6 peripheral port, 15 peripherals, 5
IBM PC/AT or compatible computer, 7
Programming Consoles, 6
PT, 7
Slaves, 5
SYSMAC Support Software, 6
SYSMAC-CPT, 6 power failure, 18 momentary, 18 power supply, 18 troubleshooting, 78 wiring, 18, 23 precautions general, xi uploading/downloading, 84 program memory, setting address and reading content, Programming Console, 41
PROGRAM mode, description, 36
116
Programmable Terminal. See PT programming checks for syntax, Programming Console, 47, 71–72 errors, 75 inserting and deleting instructions, Programming Console,
43–44 searching, Programming Console, 41–42 setting and reading a memory address, Programming Console, 41
Programming Console connecting, 6, 35 keys, 34 models, 34 operations, 36 programs checking, check levels, 75 downloading, 89 entering and editing, Programming Console, 44 uploading, 88
PT, 2, 7
Index specifications, 12
CompoBus/S communications, 14
Expansion Memory Unit, 85
SSS. See SYSMAC Support Software startup procedure, 60 status, monitoring, Programming Console, 47
SV, modifying, Programming Console, 52 syntax, checking the program, Programming Console, 47, 71
SYSMAC Support Software, connecting, 6
SYSMAC-CPT, 6, 7 connecting, 6 system, configuration, 3
R–S
RS-232C cable connections, 24 wiring, 24
RS-232C Adapter, 7, 24
RS-232C port, 15
RUN mode, description, 36 scheduled interrupts, 2 search instruction, Programming Console, 41–42 operands, Programming Console, 42 signed decimal data modifying, Programming Console, 55 monitoring, 51
Slaves, list, 5
T–W temperature, effect on capacitor backup, 14 terminal block, 15 test run, procedure, 60, 71 timers, changing SV, Programming Console, 52 troubleshooting, 77 fatal errors, 79 non-fatal errors, 80 operating conditions, 82 power supply, 78
UM area information, reading, Programming Console, 40 unsigned decimal data modifying, Programming Console, 56 monitoring, 51–52 uploading, programs, 88 wiring
CompoBus/S, 23 power supply, 23 precautions, 21
RS-232C, 24
117
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W318-E1-4
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
1
2
3
4
Date
April 1997
November 1997
April 1999
May 2000
Revised content
Original production
Corrections and modifications resulting from the upgrade to “-V1.”
Information on the SYSMAC-CPT Support Software added throughout the manual.
Page 41: Second operand display for step 10 corrected.
Corrections and modifications resulting from the upgrade to “-V2.”
Added Section 6 Expansion Memory Unit.
Updated Precautions.
Page 3: Added information on the CPM1-EMU01-V1 Expansion Memory Unit.
Page 12: Removed “1G” and “15G” from the table.
Pages 38 to 58, 62, 63, and 71: Corrected contents of displays.
Page 83: Removed notes from the table.
Page 86: Added models related to the CX-Programmer and Expansion Memory Unit.
119