advertisement
INSTALLATION
INSTRUCTIONS
FCP2400D
FCP3000D
FCP3600D
FCP4200D
FCP4800D
FCP6000D
Models
FCP2400C FCX2400C
FCP3000C
FCP3600C FCX3600C
FCP4200C
FCP4800C FCX4800C
FCP6000C FCX6000C
Require
AMF001NHA
Accessory No Heat Kit
FCP2405C
FCP2407C
FCP2410C
FCP3005C
FCP3007C
FCP3010C
FCP3605C
FCP3607C
FCP3610C
FCP4205C
FCP4207C
FCP4210C
FCP4807C
FCP4810C
FCP6010C
With
5, 7, 10KW Heater
Contents
General Information / Installation . . . . . . . . . . . .
Upflow Installations . . . . . . . . . . . . . . . . . . . . . . . .
Horizontal Installations . . . . . . . . . . . . . . . . . . . . .
Ductwork Connections
Filter Installation
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Orifice and Lines
Electrical Connections
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
Checks and Maintenance
Blower Performance
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
Sequence of Operation
Wiring Diagram
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
6
7
8
9
10
11
2
3
3
3
4
Use ONLY factory listed electric heaters.
Fan Coils
Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARN-
ING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER -- Immediate hazards which WILL result in severe personal injury or death.
WARNING -- Hazards or unsafe practices which
COULD result in severe personal injury or death.
CAUTION -- Hazards or unsafe practices which COULD result in minor personal injury or product or property damage.
Printed in U.S.A.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
CAUTION
Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
496 01 4111 03
June 2002
Installation Instructions
Figure 1
Dimensions and Clearances
Fan Coils
3/4”
8
1
/
2
”
A
12”
42”
(2--3
1
/
2
Ton)
52”
(4--5 Ton)
1”
14--
3
/
8
” (2--2
1
/
2
17--
7
/
8
” (3--3
1
/
2
” (4 Ton FCP Only)
25--
1
/
8
Ton)
Ton)
21--
1
/
2
” (5 Ton) (4 Ton FCX Only)
CLEARANCES
NO HEATERS
All Sides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
From Supply Duct . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended Service From Front . . . . . . . . . .
(Service for blower, filter if installed)
0”
0”
20”
WITH HEATERS
All Sides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
From First Three
Feet of Supply Duct to Combustibles
From Duct after Three Feet
. . . . . . . .
. . . . . . . . . . . . . . . . .
Recommended Service From Front . . . . . . . . . .
(Service for blower, filter, heaters if installed)
0”
1”
0”
20”
Filter Door
W
16--
19--
23--
1
/
27--
3
7
1
/
/
/
8
8
2
8
” (2--2
” (3--3
1
1
/
/
2
2
Ton)
Ton)
” (4 Ton FCP Only)
” (5 Ton) (4 Ton FCX Only)
21
1
/
2
”
Fire Hazard
When heaters are installed maintain clearances from combustible materials as specified on unit rating plate. Do not use plastic lined or combustible flexible ducting within 36 inches of the supply end of the air handler.
Failure to do so can result in fire, property damage, personal injury and/or death.
General Information
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes and with the
National Electrical Code NFPA70 current edition.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
The blower cabinet may be used for cooling or heat pump operation with or without electric heat. Installations without electric heat, require a No Heat Kit.The cabinet can be installed in an upflow or horizontal position (Figure 2, 3). Horizontal installations require a horizontal kit. Some models are shipped with the horizontal kit already installed.These units are not shipped with air filters installed. Filter must be field supplied, either washable or disposal type. Washable filters are available as an accessory.
Location
Select the best position which suits the installation site conditions.
The location should provide adequate structural support, space in the front of the unit for service access, clearance for return air and supply duct connections, space for refrigerant piping connections and condensate drain line connections. If heaters are being installed make sure adequate clearance is maintained from supply ductwork, See Clearances and Warning in Figure 1.
NOTE: Internal filter can be accessed from separate filter door. If the filter can NOT be easily accessed, a remote filter is recommended. Refer to ACCA Manual D for remote filter sizing.
If the unit is located in an area of high humidity, nuisance sweating of casing may occur. On these installations a wrap of 2” fiberglass insulation with a vapor barrier should be used.
2
496 01 4111 03
Fan Coils
Upflow Installations
The unit is ready to install in the upflow position without modifications.
The unit MUST be supported on the bottom ONLY and set on a supporting frame or shelf. Use screws through the bottom to anchor to supporting frame.
Figure 2 Airflow Positions
Figure 3
Installation Instructions
Airflow Positions
Non-Ducted Return Air Closet Installation
The cabinet can be installed in a closet with a false bottom to form a return air plenum, or mounted on an open platform inside the closet. Platform should be high enough to provide a free (open) area for adequate return airflow into the bottom of the cabinet.
The open area can be on the front side or a combination of front and sides, providing there is clearance on the sides between cabinet and closet. Refer to ACCA Manual D for sizing and free
area recommendations.
NOTE: Local codes may limit application of systems without a ducted return to single story dwellings.
Horizontal Left and Right Installations
Units that are shipped with the horizontal drain pan installed are set up for horizontal left hand airflow. They must have the drain pan repositioned for right hand airflow. All other units must have the horizontal drain pan kit installed for either left or right hand applications. For installation of the drain pan, refer to the installation instructions included with the horizontal drain pan kit, and the following.
CAUTION
A field-fabricated auxiliary drain pan, with a seperate drain is
REQUIRED for all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan. In some localities, local codes require an auxiliary drain pan for ANY horizontal installation.
Drain Pan Installation / Conversion for Right Hand
Airflow
See Figure 4
1. Remove coil access panel and carefully pull Coil/Horizontal Drain Pan Assembly out.
2. Separate horizontal drain pan from coil drain pan. The coil drain pan fits snuggly inside the horizontal pan.
496 01 4111 03
3. Position side of coil drain pan into horizontal drain pan trough on deep end of pan on right side of coil.
4 Remove coil drip flanges from A--coil and reinstall on right side of coil (same side as horizontal drain pan).
5. Remove the coil support bracket from the left side of the cabinet and reinstall bracket on the right side of the cabinet.
6. Install drain plugs as required in back side of horizontal drain pan. Install plugs in A coil drain pan to prevent air leaks.
7. Slide coil assembly into cabinet being careful not to tear insulation.
NOTE: Be sure A coil pan fits into the support bracket on the back side of the cabinet and that pan is under the flange of the bracket on the right side. The brackets fit over the top edge of the A coil drain pan to hold it when it’s put into the horizontal position.
8. Refer to Restrictor Orifice Selection and change restrictor if necessary, then install coil access panel.
Cabinet can now be placed on it’s side for horizontal airflow.
Suspended Cabinet Installation
1. The cabinet may be supported on a frame or shelf, or it may be suspended.
2. Use metal strapping or threaded rod with angle iron supports under the auxiliary drain pan to suspend cabinet.
These supports MUST run parallel with the length of the cabinet (Figure 5 ).
3. Ensure that there is adequate room to remove service and access panels after installing supporting brackets.
4. Place Styrofoam blocks in auxiliary drain pan to support cabinet.
Duct Connections
Supply Duct
Supply duct must be attached to the outside of flange on outlet end of unit. Flexible connectors may be used if desired. Maintain clearances from supply duct to combustibles when heaters are installed. See Figure 1 and unit rating plate.
Return Duct
Return duct should be attached to bottom of unit using sheet metal screws or other fasteners.
3
Installation Instructions
Figure 4
Horizontal Drain Pan
Fan Coils
Drip Flange mounts to top two holes in coil plate
Horizontal Drain Pan
(Left Hand Airflow)
Coil Support Bracket
(Right Hand Airflow)
Filter Door
Coil Support Bracket
Coil Access Panel
Drip Flanges
(Left Hand Airflow)
Coil Support Bracket
(Left Hand Airflow)
Plug drains on back side
Horizontal Drain Pan
(Right Hand Airflow)
Drip Flanges
(Right Hand Airflow)
Filter Installation
Filters must be field supplied. The blower cabinet is set up for an internal filter or a remote filter grille or other means may be provided. Refer to ACCA Manual D for remote filter sizing.
To install an internal filter, remove screw securing filter door and slide filter into unit. Some filters are marked for airflow direction, make sure arrow points towards blower if marked. Washable filters are offered as an accessory. Disposable filter sizes are listed in Filter Static Pressure Drop Table.
Figure 5
Horizontal Installation
4
Drain
Lines
Refrigerant
Lines
Field-Fabricated
Drain Pan
Supports MUST run parallel with blower cabinet
496 01 4111 03
Fan Coils
Condensate Drain Connections
The unit is provided with 3/4” National Pipe Thread (NPT) condensate drains. (Figure 1). Any drain can be used as a primary or secondary drain. Condensate drain lines should be installed in a manner that does not obstruct access to the filter.
There is a secondary drain fitting supplied with the unit that will convert any of the primary condensate drain connections into a secondary drain connection. This fitting should be installed in any of the primary drain connections to convert it to a secondary drain.
1. Connect the drain lines to the appropriate drain fittings. 3/4”
PVC or other type of drain line may be used. The drain line must not be smaller than the drain fitting.
2. Install a trap in the drain line below the bottom of the drain pan and pitch the drain lines down from the coil at least l/4” per foot of run. Horizontal runs over 15 feet long must also have an anti--siphon air vent (stand pipe), installed ahead of the horizontal run. An extremely long horizontal run may require an oversized drain line to eliminate air trapping.
3. Route to the outside or to a floor drain, laundry tray or waste line (sewer). Check local codes before connecting to a sewer line.
4. Insulate drain lines where sweating could cause water damage.
Restrictor Orifice Selection
A restrictor orifice is located in a fitting at the distributor. The factory installed restrictor orifice is identified on the unit rating plate.
The restrictor orifice may require changing to obtain best performance. Refer to the restrictor charts furnished with the outdoor unit.
Changing Restrictor Orifice
1. Remove the liquid line fitting and replace restrictor orifice.
(STANDARD RIGHT HAND THREAD)
2. Make sure the restrictor is installed with the rounded end toward the feeder tubes. See Figure 7.
Refrigerant Line Connections
Size refrigerant lines according to information provided with outdoor condensing unit. Route the refrigerant lines to the coil in a manner that will not obstruct service access to the unit or removal of the filter.
1. Remove rubber plugs from refrigerant connections using a pulling and twisting motion. Hold refrigerant lines to avoid bending or distorting.
2. Remove the coil door before brazing refrigerant connections to prevent damage to paint finish.
3. Fit refrigerant lines into coil connections and remove the tubing plate and slide plate over the refrigerant lines to assure sufficient room for brazing.
4. Reinstall tubing plate and door and install the gasket, provided with the unit, over the suction and liquid lines into the tubing plate recess to ensure an air seal around the coil.
See Figure 8.
Installation Instructions
5. If a gravity drain cannot be used, install a condensate pump. Install the pump as close to the indoor section as possible.
Waste Line Connection
If the condensate line is to be connected to a waste line, an open trap must be installed ahead of the waste line to prevent escape of sewer gases. NEVER CONNECT THE DRAIN LINE DIRECTLY
TO A WASTE LINE. ALWAYS INCLUDE AN AIR GAP AND
TRAP, (Figure 6). Be sure to keep the trap filled with water during the winter or off season.
Figure 6
Condensate Drain to Waste Line
Air Gap Above
Liquid Level
Condensate
Line
Trap
Figure 7
Figure 8
Gasket
Sewer Line
Restrictor Orifice
Nut and Liquid Line with Strainer
Restrictor Orifice
Rounded End
Feeder Tubes
Refrigerant Lines
Refrigerant Lines
Tubing Plate
Recessed
Area
For Gasket
496 01 4111 03
5
Installation Instructions
Electrical Connections
Fan Coils
Electrical shock hazard.
Turn OFF electric power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
Failure to do so can result in property damage, personal injury and/or death.
All electrical work MUST conform with the requirements of local codes and ordinances and the National Electrical Code NFPA 70 current edition.
The low voltage transformer and the fan control are standard on all models and are prewired at the factory. Line voltage connections are made to the heater accessory or the wire pigtails in the unit.
Low Voltage Control Connections
The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models. If power supply is 208 volt, the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label.
Field supplied low voltage wiring can enter the unit on the top left hand corner or the left hand side panel. When using the left hand side panel entrance, the low voltage wiring must be fed through the entrance hole in the bottom of the control box.
Install the strain relief bushing (supplied with unit) in the selected hole and a hole plug (supplied with unit) in the unused hole.
Connect the field wiring at the screw terminals of the control board. Refer to Figures 9, 10.
Keep the low voltage wiring as short as possible inside the control box.
Complete connections between indoor blower, outdoor section, indoor thermostat and electronic outdoor thermostat (accessory) according to instruction provided with the Condenser Installation
Instructions or those provided with the accessory and refer to Fig-
ures 11&12.
Overcurrent Protection
The power supply wiring to the unit MUST be provided with overcurrent protection. Governing codes may require this to be fuses
ONLY or circuit breakers.
For blower cabinets without heaters, a 15 amp circuit may be used.
Line Voltage Connections
Line voltage wiring may be brought into the unit through the top right--hand corner or the right--hand side panel. The correct hole size required by the conduit fitting must be punched at the pilot hole location. Plug the unused pilot hole with a hole plug (supplied with unit).
Connect field wiring to appropiate terminals on electric heater or the wire pigtails. All line voltage connections must be made with copper wire.
Line Voltage Connection
1. Provide line voltage power supply (208V--240V) from a separate circuit(s). Size per table or table in heater manual.
2. Connect line voltage to the lugs with the Black and Yellow wires, or to circuit breakers or wire leads from heaters. Refer to Figure 9 for FCP----D Series and Figure 10 for
FCP----C and FCX and wiring diagram.
Figure 9
Low Voltage
Connections
Electrical Controls -- (FCP----D Series)
Matching Receptable
For Electric Heater
(Unplug Connector)
Pigtails for
Line Voltage
(Yellow and Black) and
Ground Connection
(Green)
Figure 10 Electrical Controls
Low Voltage
Connections
Matching Receptable
For No Heat Kit or Electric Heater
Filler Plate
(FCP/X48--60)
Flanges Together
Adapter Plate
(FCP36--42, FCX36)
No Heat Kit
Lugs for
Line Voltage and Ground
Connections
6
496 01 4111 03
Fan Coils
No Heat Kit Installation
(FCP ----C and FCX)
If electric heat is not used, install accessory No Heat Kit.
1. Locate adapter and filler plates, with screws inside package.
2. Attach adapter plate and filler plate to bracket if required to match cabinet, Refer to Figure 10.
3. Secure the electric heat accessory with four screws.
4. Connect the plug from No Heat Kit wiring into the receptacle on the control board on the side of the cabinet.
CAUTION
Do not attempt to force plug as it only fits one way.
Grounding Connection
Use a copper conductor(s) from the Green ground wire on the unit or ground lugs on the electric heater to a grounded connection in the electric service panel or a properly installed grounding rod.
Figure 11
Typical Low Voltage Schematic
G
C
O
Y
W
2
W
1
Heat Pump with Electric Heat
R
Staging
Thermostat
Y
Outdoor Unit
O
R
BL
W
Installation Instructions
Figure 12
Thermostat
R
G
Y
W
Typical Low Voltage Schematic
Cooling Only
Outdoor Unit
Y
Y
W
1
W
2
G Y H O C R
Indoor Blower
Thermostat
R
G
Y
W
Cooling with Electric Heat
Y
Y
Outdoor Unit
W
1
W
2
G Y H O C R
Indoor Blower
W
1
W
2
G Y H O C R
Indoor Blower
Electrical Data
Volts
240
208
Heater
1086081
05KW
1086082
07KW
1086083
10KW
Supply Circuit
Phase
1
1
Hertz
60
60
Supply
Circuit
No.
Single
Single
Nomi-
Supply Heating Heat-
Voltage BTUH
240 16,832
208
240
208
240
208
12,287
24573
18430
32,765
24,574
KW
4.8
3.6
7.2
5.4
9.6
7.2
KW Per
Element
4.8
3.6
3.6
2.7
4.8
3.6
Supply
Circuit
No.
Single
Single
Single
Single
Single
Single
Maximum
Motor
AMPS.
6.0
6.0
Total
AMPS.
6.0
6.0
Branch
Circuit
Ampacity
7.5
7.5
Heater
KW Per Heater
Circuit
4.8
3.6
7.2
5.4
9.6
7.2
AMPS.
20.0
17.3
30.0
26.0
40.0
34.7
Maxi-
Motor
AMPS.
6.0
6.0
6.0
6.0
6.0
6.0
Maximum
Overcurrent
Protective
Device
(AMPS.)
15
15
Total
AMP
S
23.3
36.0
32.0
46.0
40.7
Branch
Circuit
Ampacity
32.5
29.2
45.0
40.0
57.5
50.8
No.
2
75
Recommended
Supply Wire
0
C. Copper
Max.
Size Length (Ft)
14 104
No.
Ground
Wire
Size
1 14
2
Maximum
Overcurrent
14
Protective
Device
(AMPS.)
35
30
45
40
60
60
90 1 14
75
Recommended
Supply Wire
0
C. Copper
Max.
Ground
Wire
No.
Size Length (F No.
Size
2 10 61 1 10
2
2
2
2
2
8
6
10
8
6
59
70
68
85
83
1
1
1
1
1
10
10
10
10
10
496 01 4111 03
7
Installation Instructions Fan Coils
Adjusting Thermostat Anticipator
Set the heat anticipator of the thermostat to the proper value. See instructions provided with the thermostat before making this adjustment.
Heater Size -- KW
05
07, 10
Anticipator Setting
.24
.32
HEATER STAGING
ELECTRIC
HEATER
VOLTAGE
05KW
07KW
10KW
208--240/1/60
208--240/1/60
208--240/1/60
208V
3.6
TOTAL HEAT
240V
4.8
5.4
7.2
7.2
9.6
ELECTRIC HEATER STATIC PRESSURE DROP -- IN. WG.
1200
1300
1400
1500
1600
1700
1800
1900
2000
CFM
600
700
800
900
1000
1100
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
5 KW
0.01
0.01
0.01
0.01
0.01
0.01
Staging
The heater elements are turned on in increments. Refer to Staging Table. In addition on heaters larger than 5KW, the heat can be staged (1st & 2nd) either through an indoor thermostat or by using an outdoor thermostat. This satisfies staging requirements imposed by some electric utilities on heaters larger than 6 kilowatts.
A control signal (24V) from W1 on the Indoor T’stat to W1 on the control board energizes the 1st stage of heat. A control signal
(24V) to W2 on the control board energizes the second stage of electric heat. To turn ON both stages at the same time, using one control signal, W1 and W2 are jumpered together.
If the indoor thermostat does not have staging capabilities, accessory electronic outdoor thermostats are available that will control two stages of electric heat.
208V
3.6
2.7
3.6
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
7.5 KW
0.01
0.01
0.01
0.01
0.01
0.01
240V
4.8
3.6
4.8
208V
--
2.7
3.6
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
10 KW
0.01
0.01
0.01
0.01
0.01
0.01
240V
--
3.6
4.8
8
496 01 4111 03
Fan Coils Installation Instructions
Changing Motor Speed
The blower motor comes from the factory wired for high or Med speed. To change the blower speed, disconnect the black wire at the blower motor terminal block and reconnect at the desired blower speed tap.
Air Flow Check
For proper system operation, the air flow through the indoor coil should be between 350 and 450 cfm per ton of cooling capacity.
The air flow through the unit can be determined by measuring the external static pressure to the unit and selecting the motor speed tap that will most closely provide the required air flow.
1. Set up to measure external static pressure at the supply and return duct connections (Figure 13).
2. Drill holes in the ducts for pressure taps, pitot tubes, or other accurate pressure sensing devices.
3. Connect these taps to a level inclined manometer or draft gauge.
4. Ensure the coil and filter are clean, and all the registers are open.
5. Determine the external static pressure with the blower operating.
6. Refer to the Air Flow Data tables, page 9 to find the speed tap that will most closely provide the required air flow for the system.
7. Refer to Changing the Motor Speed in these instructions if the speed tap is to be changed.
8. Recheck the external static pressure with the new speed tap, and confirm speed tap selection.
Temperature Rise Check
Temperature rise is the difference between the supply and return air temperatures.
NOTE: The temperature rise can be adjusted by changing the heating speed tap at the unit’s blower terminal block. Refer to the unit’s Installation Instructions for airflow information.
Figure 13
Static Pressure Check
Supply
Indoor
Section
Incline
Manometer
Return
1. To check the temperature rise through the unit, place thermometers in the supply and return air ducts as close to the unit as possible.
2. Open ALL registers and duct dampers.
3. Set thermostat Heat--Cool selector to HEAT.
4. Set the thermostat temperature setting as high as it will go.
5. Turn electric power ON.
6. Operate unit AT LEAST 5 minutes, then check temperature rise.
NOTE: The maximum outlet air temperature for all models is
200°F (93.3°C).
7. Set thermostat to normal temperature setting.
8. Turn electric power OFF.
9. Be sure to seal all holes in ducts if any were created during this process.
Airflow 220V / 50 Hz Models Only
NOTES: Performance based on unit with horizontal drain pan installed, dry coil, no filter, Deduct Filter Static
MODEL
FCP2400D
FCP3000D
FCP3600D
FCP4200D
FCP4800D
FCP6000D
BLOWER SPEED
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
AIRFLOW PERFORMANCE 220 -- 1 --50 HZ
0.1
885
873
775
1,225
1,160
1,034
1,384
1,311
1,168
1,578
1,446
1,198
1,657
1,518
1,258
1,960
1,869
1,759
0.2
825
811
728
1,175
1,115
1,001
1,328
1,260
1,131
1,527
1,402
1,184
1,603
1,472
1,244
1,902
1,815
1,715
0.3
723
708
645
1,067
1,014
919
1,206
1,146
1,038
1,399
1,288
1,111
1,469
1,352
1,167
1,748
1,670
1,585
0.4
643
573
558
1,031
980
886
1,165
1,107
1,002
1,338
1,224
1,073
1,405
1,285
1,126
1,702
1,626
1,545
0.5
499
380
416
891
847
765
1,007
957
865
1,143
1,037
927
1,200
1,089
973
1,485
1,419
1,351
496 01 4111 03
0.6
297
266
188
794
747
667
897
844
754
964
876
805
1,012
920
845
1,317
1,252
1,202
9
Installation Instructions Fan Coils
Airflow Based on dry coil, no filter, no electric heat. Deduct heater static shown in heater static table.
Deduct filter static shown in filter static table. Deduct .05 for wet coil. Deduct .10 for Horizontal Kit (FCP) only.
FCP24
SP IN. WG.
FCP60 SP IN. WG.
SPEED
LOW
VOLTAGE
230V
208V
0.1
743
561
0.2
743
561
0.3
739
561
0.4
715
560
0.5
671
544
0.6
601
512
0.7
510
459
SPEED
LOW
VOLTAGE
230V
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1643 1671 1670 1650 1607 1549 1474
MED
HIGH
230V
208V
230V
208V
972
789
942
789
897
787
1108 1052 992
1027 1027 974
851
775
936
910
773
737
859
836
686
656
765
751
593
569
653
651
MED
HIGH
208V
230V
208V
230V
208V
1337 1355 1369 1373 1360 1332 1282
2059 2023 1974 1910 1827 1739 1635
1735 1738 1728 1688 1636 1574 1483
2453 2369 2272 2165 2056 1933 1813
2339 2259 2167 2073 1971 1862 1741
FCP30
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
1104 1069 1028
0.4
976
0.5
926
0.6
851
0.7
784
940 908 870 832 780 723 666
1327 1277 1222 1161 1087 1022 940
1192 1153 1108 1049 989 930 834
1457 1396 1333 1267 1184 1107 1032
1378 1316 1260 1192 1117 1055 968
FCX24
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
737
586
943
798
0.2
723
571
896
778
1092 1023 946
1015 955 888
0.3
682
549
832
731
0.4
627
514
752
672
849
800
0.5
559
466
668
598
753
704
0.6
475
394
560
510
632
596
0.7
333
280
443
388
515
489
FCP36
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
0.4
0.5
1111 1089 1059 1027 985
0.6
927
0.7
860
924 908 877 851 801 748 698
1415 1382 1341 1291 1232 1170 1092
1209 1185 1154 1120 1069 1019 937
1668 1611 1556 1486 1410 1330 1237
1494 1456 1410 1352 1283 1209 1130
FCX36
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
0.4
1069 1039 1004 956
0.5
898
0.6
825
0.7
740
898 861 827 785 730 675 599
1347 1302 1249 1187 1121 1041 946
1170 1129 1095 1037 975 909 817
1572 1504 1437 1362 1279 1186 1076
1423 1368 1313 1246 1176 1075 986
FCP42
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1132 1129 1128 1105 1072 1026 944
929 926 922 908 886 841 802
1520 1489 1449 1400 1338 1269 1192
1279 1272 1255 1228 1187 1135 1055
1769 1711 1645 1569 1490 1406 1313
1618 1575 1524 1465 1402 1325 1239
FCX48
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
0.4
0.5
1105 1093 1079 1066 1036
0.6
982
0.7
917
909 897 887 871 845 814 757
1501 1485 1456 1412 1358 1287 1196
1255 1243 1223 1206 1177 1127 1056
1870 1821 1758 1694 1598 1502 1390
1615 1597 1555 1509 1462 1386 1270
FCP48
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1120 1113 1107 1094 1076 1045 1004
913 903 889 876 865 845 810
1538 1531 1511 1479 1435 1380 1301
1257 1266 1256 1242 1215 1174 1122
1922 1877 1818 1751 1679 1590 1481
1653 1643 1617 1571 1517 1444 1366
FCX60
SPEED
LOW
MED
HIGH
VOLTAGE
230V
208V
230V
208V
230V
208V
SP IN. WG.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1658 1642 1605 1543 1474 1393 1291
1370 1371 1358 1337 1291 1236 1150
1966 1905 1829 1740 1641 1527 1405
1733 1696 1645 1581 1502 1414 1310
2239 2137 2029 1916 1806 1683 1543
2141 2047 1952 1849 1739 1620 1495
*WASHABLE
FILTER SIZE
14
17
21
24
1
/
3
/
4
4
1
/
4
3
/
4
X 20
X 20
X 20
X 20
1
1
/
/
4
4
1
/
4
1
/
4
FILTER STATIC PRESSURE DROP*
DISPOSABLE
FILTER SIZE
14 X 20
18 X 20
20 X 20
25 X 20
600
0.05
--------
--------
--------
800
0.09
------
------
------
CFM
1000 1200 1400 1600 1800 2000
0.13
0.19
-----------
0.09
0.12
0.17
0.22
------
------
------
------
------
------
------
------
0.12
0.15
0.19
------
0.09
0.11
0.14
0.18
10
MODEL
FCP24 / FCX24 / FCP30
FCP36 / FCX36 / FCP42
FCP48
FCX48 / FCP60 / FCX60
496 01 4111 03
Blower Coils Installation Instructions
Mode
Constant Blower
(Fan Switch ON)
Sequence Of Operation
Thermostat to Control Board 24 volt
Control
State
Control Function
Cooling Only Unit With Electric Heat
G On Fan On.
Y & G
Off
On
Fan Off.
Compressor On, Fan On.
Cooling Only Unit
(Thermostat calls for
Cooling)
Cooling Only Unit
(Thermostat calls for
Heat)
Heat Pump
(Thermostat calls for
Cooling)
Heat Pump
(Thermostat calls for
Heat)
Heat Pump cannot maintain proper temp.
Electric Heat Temperature satifised
Heat Pump
(Goes into Defrost
G & W1 & W2
Y & G
Y & G & W1 & W2
Off
On
Off
On
Off
Compressor Off, 60 Second Delay -- Then Fan Off.
Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.
2nd then1st Stage Of Heat Off. 6 sec delay, then Fan Off.
Y & G & O
Heat Pump With Electric Heat
On Compressor On, Reversing Valve Energized, Fan On.
Off
On
Compressor Off, 60 Second Delay And Then Fan Off.
Compressor On, Fan On
1st Stage Of Heat On, then 2nd Stage Of Heat On
2nd then 1st Stage Of Heat Off
Y & G & O & W1 & W2 On
Off
Reversing valve switches unit to cooling, 1st Stage Of Heat
On, then 2nd Stage Of Heat On
Reversing valve switches back to heating, 2nd then 1st Stage
Of Heat Off
Compressor Off, 60 Second Delay And Then Fan Off.
Heat Pump
(Room temp. satifised)
Heat Pump
(Emergency Heat)
Y & G
G & W1 & W2
Off
On
Off
Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.
2nd then 1st Stage Of Heat Off. 6 sec delay, then Fan Off.
NOTE: Electric Heat Elements are controlled by relays with a delay sequence from the logic board to provide sequencing between elements.
Limit Operation
The temperature limit responds to over--temperature conditions in the air duct. If the temperature limit trips, the electric heater relays will be de--energized and the fan relay will be energized. Once the limit resets, the control will resume normal operation. If the limit trips four times during a single call for heat, the control will go into a 1 hour soft lockout. During the soft lockout, the fan relay will respond to thermostat inputs but the heater relays are disabled. If the control detects a limit trip during the soft lockout, the control will go into a hard lockout. Once in a hard lockout, the fan relay is locked on and the heater relays are disabled. Turning the power to the unit off and then on will clear this state.
496 01 4111 03
11
Installation Instructions Fan Coils
12
POWER SUPPLY: 208/230-1-60 USE COPPER CONDUCTORS ONLY.
KEY: HIGH VOLT; LOW VOLT.
FAN
CNTRL
BRD
COM
TFMR
PRIMARY
240
FAN COM
O
V
Y
Y
R
FUSE
R
FAN SPD
BK
BK
O
BL
BL
G/y
GRD
BR
BR
CAP
G/y
BLW
MTR
COM
HI
MED
*
Y
BK
GRD
Y
LOW
GRD
BK
BASE UNIT WITH NO-HEAT KIT AMF001NH INSTALLED
*SEE INSTALLATION MANUAL FOR PROPER HEATING AND COOLING
FACTORY PRE-SET SPEED CONNECTIONS FOR YOUR UNIT.
BL
O
R
O
LIMIT
Y
BL
O
3 Kw &
5 Kw
BK
GY
GY
R
BK
1
O
GRD
Y
Y
BK
AMFK03CH / AMFK05CH ELECTRIC HEATER
BL
O
R
O
LIMIT
Y
1
BK
Y
BL
BK
1
BL
O
BL
O
V
7.5 & 10 Kw
BK
V
BK
GY
GY
R
O
Y
GRD
Y
BK
*
AMFK07CH / AMFK10CH ELECTRIC HEATER
R
LIMIT
Y
Y
Y
O
O
BL
BL
BL
15 Kw
V
BK
BL
O
V
BK
BL
O
GY
BK
BL
O
GY
GY
R
O
Y
AMFK14CH ELECTRIC HEATER
*AMFK15CH ELECTRIC HEATER (2 LIMITS)
GRD
GRD
Y
BK
Y
BK
BL
BL
R
LIMIT
R
Y
Y
BL
BL
R
LIMIT
O
O
Y
Y
BK
1
BL
V
20 Kw
BL
O
BL
O
GY
BL
BK
O
GY
BK
V
BK
GRD
Y
BL
GY
R
O
BL
BK
V
O
GRD
Y
BK
R
AMFK20CH ELECTRIC HEATER
R
LIMIT
Y
BL
Y BL
O
R
LIMIT
O
Y
BK
Y
Y
BL
Y
BL
BK
O
V
BK
BL
O
BL
GY
BK
O
GY
25 Kw
GRD
GRD
W
V
GY
R
O
BK
1
Y
BL
BK
O
BL
BL
W
BK
O
V
Y
BK
Y
BK
Y
BK
GRD
BL
BL
BL
R
LIMIT
AMFK25CH ELECTRIC HEATER
Y BL
R
LIMIT
O
R
Y
BL
O
Y
BL
Y
Y
Y
30Kw
BL
BK
V
O
BL
BK GY
O
BK
BL
O
GY
GRD
BL
BK
BL
O
W BK W
O
BK
BL
O
V
GRD
W
V
GY
R
O
BK
1
Y
AMFK30CH ELECTRIC HEATER
Y
Y
Y
GRD
BK
BK
BK
1087757
496 01 4111 03
Fan Coils
CC
V
BB
AA
496 01 4111 03
8
H
K
15
16
B
19
EE
DD
HH
P
W
X
2
1
A
17
18
14
9
Y
10
C
3 4
5
D 7
R
Q
Installation Instructions
O
Z2
11
Z1
13
12
FF
1
2
A
GG
U
S
C
T
D B
4
C
JJ
7
L
38--20--21
38--20--26
13
Installation Instructions Fan Coils
KEY
NO.
DESCRIPTION
PART
NUMBER
3
3
4
2
2
3
2
2
2
2
2
1
2
2
2
Coil, Evaporator
Manifold, Evaporator
Housing, Flow Control
4
4
4
4
4
4
4
4
Distributor
Restrictor, .057
.065
.073
.078
.079
.092
Valve, Expansion
6
7
7
5
5
5
5
5
Adapter, Flow Control with Liquid Tube
Distributor Assembly
Pan, Drain, 15"
19"
8
8
7
7
9
22"
26"
Pan, Drain Horizontal
Control, Fan Timer
10 Transformer
11 Motor, Blower
11
11
11
12 Mount, Blower Motor
12
12
13 Wheel, Blower
13
13
13
14 Capacitor, 5MFD, 370V
14 10MFD, 370V
14 15MFD, 370V
15 Block, Terminal
16 Heater, 5KW, W/ Term. Bk
16 7KW, W/ Term. Bk
16 10KW, W/ Term. Bk
17 Relay
18 Switch, Limit
19 Fuse Link
Not Stocked -
1082961 1 1 1 1 1 -
-
1085679 1 1 1 1 1 -
1082914
1082963
1082964
1082984
1087520
1083253
1 1 1 1 1 -
1 1 1 1 1 -
-
1 1 1 1 -
1 1 1
-
1 -
1083310
1083258
1082972
1 -
-
1 -
1
1082973
1062727
1085975
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 1 1
-
1 1 1 1
1093424
1054027
1053112
1053661
1053712
1 1 1 1 1 -
1 1 1 1 1 -
-
1 1 1 1 1 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 1 1 1 1 -
-
-
1 1 1 1 -
-
-
-
-
-
-
-
-
-
-
-
-
1082871
1082873
1087340
1 1 1 -
-
1 1 -
1 -
1082860
1082864
1082862
1082857
1
1 1 1 1 1 1 1 1 1 1 -
-
1 1 1 1 1 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 1 1 1 1 -
-
-
1 1 1 1 -
-
-
-
-
-
-
-
-
-
-
-
-
1082966 1 1 1 -
Not Stocked -
-
1082775 1 1 1 1 1 1 1 1 1 1 1 -
1082776
1082777
1085353
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
-
1 1 1 1 1
1082619
1082621
1085914
1082611
1087048
1083044
1083045
1083046
1050254
1002801
609227
600585
600586
600587
96839
1094954
1094956
1094959
1087753
1087682
1 1 1 1 1 1 -
1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 -
1 -
1 1 1 1
1 1 1 1 1
-
-
-
-
-
-
-
-
-
-
-
-
-
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 1 1
1 -
1 -
-
-
-
1 1 -
-
-
-
-
1
1 1 1 1 1 1 -
1 1 1 1 1 -
-
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 -
1 1
1 1 1 1 1 -
1 -
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
1 1 1
1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1087683
1087684
1084529
1084734
1087811
1 1 1 1 -
1 1 1 1 1 -
-
1 1 1 1 1 1 -
1 2 2 1 2 2 1 2 2 1 2 2 2 2 2 -
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
-
1 2 2 1 2 2 1 2 2 1 2 2 2 2 2
-
14
496 01 4111 03
Fan Coils Installation Instructions
KEY
NO.
DESCRIPTION
PART
NUMBER
Q
R
S
S
P
Q
Q
Q
O
P
P
P
O
O
K
L
O
H
K
C
D
B
B
B
B
A
A
B
A
A
Baffle, Top
Plate, Triangular
Plug, Drain Pan
Plug, Drain Pan
Plate, Tubing
Grommet, Tubing Plate
Bracket, Coil Hold Down
Panel, Rear Blower Deck
Panel, Front Blower Deck
Panel,Side Blower Deck
Bracket, Control Fan
Bracket, Drain Pan
V
W
V
V
T
U
S
S
V
Stop, Coil
Adapter, Filter
Panel, Top
Housing, Blower
W
W
W
X Panel, Blower Cutoff
X
X
Y Clamp, Capacitor
Z1 Rail, Blower R.H.
Z2 Rail, Blower L.H.
AA Door, Coil Access
AA
AA
AA
BB Door, Blower Access
BB
BB
BB
CC Door, Filter Access
CC
CC
CC
DD Plate, Heater Adapter
EE Plate, Heater Filler
FF Clamp. Tube
GG Shield, Condensate
)(
)(
)(
HH Plate, Heater Closure
HH
HH
JJ Adapter, Male (Drain)
Harness, Wire
Harness, Wire (Clos. Plate)
Manual, Installation
1084530
1082954
1082955
1082956
1082779
1082780
1082924
1082904
1082782
1083241
1082965
1085601
1085603
1085602
1082602
1082604
1082844
1082845
1082846
1086694
1085372
1085373
1085374
1082622
1082847
1082848
1082849
1085371
1082609
1082927
1082928
1082929
1083349
1084788
1087710
1087711
1087712
1087713
1087343
1087195
1087193
1087194
1082607
1082616
1082949
1095020
1085504
1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 -
-
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
1
2 2 2 2 2 2 -
2 2 2 2 2 -
-
2 2 2 2 2 2 2 2 2 2 -
2 -
2 2 2 2 -
2 2 2 2 2
2 4 2 2 2 2 4 2 2 2 2 4 2 2 2 2 4 2 2 2 2 4 2 2 2 4 2 4 4 4 4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 1 1 -
1 1
1 1 1 1 1 1 -
1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
1 1 1 -
1 1
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
1 1 1 -
1 1
2 2 2 2 2 2 2 2 2 2 2 -
2 2 2 2 2 2 2 2 2 2 2 -
2 2 2 2 -
2 2 2 -
2 2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
-
1 1 1 -
1 1
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 -
1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 -
1 -
1 1 1 1 -
1 1 1 1 1
1 1 1 1 1 1 -
1 1 1 1 1 -
-
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 1 1 1 1 1 1 -
1 -
1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1085521
1087718
1087719
1087720
1087721
1087729
1087726
1087727
1087728
1087730
1087731
1087732
1087733
1084606
1084608
1063118
1083333
1084926
1084927
1084928
1085010
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 -
1 -
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 -
1 -
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
1 1 1 -
1 1
1 1 1 1 1 1 1 1 1 1 -
1 -
-
-
-
1 1 1 1 1 1 1 1 1 1 1 -
1 1 1 1 -
1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
1 1 1
1 1 1 1 1 1 1 1 1
* 1 1 1 1
2 2 2 2 2 2 2 2 2 2
1
-
-
-
-
-
-
-
-
-
-
-
-
-
1
-
-
-
-
-
-
-
-
-
-
-
-
-
1 -
-
-
-
-
-
-
-
-
-
-
-
-
1 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 -
-
-
-
-
-
-
-
-
-
-
1 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1086021
1084929
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 -
49601411100 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
496 01 4111 03
15
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement