5291598-LTG-B-1216
DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
TECHNICAL GUIDE
SINGLE PACKAGE
AIR CONDITIONER / GAS HEAT
16 SEER – R-410A – 208/230V - 3 PHASE
3 THRU 5 NOMINAL TONS
65 - 125 MBH HEAT INPUT
MODELS: PCG6*36 THRU 60
• Operating Efficiency - All PCG6 model gas units provide a
minimum AFUE of 81.0% in heating and 16.0 SEER, 12.0
EER rating for cooling operation. All models meet California
Low-Nox requirements of 40 ng/joule emission level for Air
Quality Management Districts. All PCG6 models utilize a
multi-stage compressor for maximum comfort and efficiency.
• On Site Flexibility - All model sizes use a compact design
cabinet. Field convertible duct connections from side flow to
downflow allows the installer to have greater flexibility with
less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
ensure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
ensure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
• Utility Connections Made Easy - Gas and electric utility
access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
®
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.luxaire.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 1-Year limited parts warranty.
Standard 5-Years limited compressor warranty.
10-Years gas heat exchanger warranty.
*See limited warranty certificate in User’s Information Manual for details
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 6289 standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder
paint finish ensure less fading when exposed to sunlight, and
provides superior corrosion resistance (1000 hour salt spray
tested).
Continued on next page.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5291598-LTG-B-1216
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from all
sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of scroll bypass
and a temperature sensor which protect the compressor if
undesirable operating conditions occur.
• More Attractive Appearance - A single-piece top cover
containing a top-discharge outdoor fan arrangement requires
less square footage on installation and provides a wider variety of installations. The one-piece design adds greater water
integrity. Rounded corners with water drip edges add to the
attractive appearance.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils use tin-coated copper
tubing with aluminum fins for effective heat transfer.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping. This
allows compact location on multi-unit applications.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The uniquely formed base pan also aids in sound
attenuation with its structural design. This design strategically places embossments in the pan for optimum strength
and rigidity.
• Fan System - All models operate over a wide range of
design conditions with an enhanced ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Simple Control Circuit - A low voltage gas heat printed circuit board contains a status/diagnostic indicator light. Field
thermostat wiring connects to color coded leads using twist
on wire connections. Cooling controls use contactor and
relays for simple application and troubleshooting. Mate-nlock plug connectors are used. The electrical control box is
not located in the compressor compartment. The controls are
mounted to allow the separate access panel to be removed
for trouble shooting and maintenance without affecting the
normal system operating pressures. All wiring internal to the
unit is color/number coded.
2
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor de-energizes until
pressure reaches 450 psi.
• Heat Exchangers - Gas heat exchangers use corrosionresistant, stainless-steel tubular construction to provide longlife, trouble-free operation. Gas heat exchangers are offered
with lifetime warranties as standard with registration.
• Post Purge Induced Draft Combustion - Exhausts combustion products from the heat exchanger upon completion
of the heating cycle to prolong the heat exchanger life.
• Spark To Burner Ignition - No pilot assembly required,
which provides more consistent ignition in gas heating mode.
This ignition is highly reliable, durable and eliminates nuisance lockouts.
• Multi Port In-shot Burners - No field adjustment is required
to mix the air and gas for natural gas or propane use. These
burners are constructed of high-grade corrosion-resistant,
aluminized steel.
• Low Maintenance - Long life, permanently lubricated outdoor and evaporator fan motor bearings need no annual
maintenance, adding greater reliability to the unit. Slide-out
blower assembly can be easily removed for cleaning.
• Easy Service Access - Individual access panels covering
the electrical and gas controls makes servicing easy. Removing this panel will allow easy removal of the blower assembly
for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
• Loss of Charge Switch - All models include a loss of charge
switch to provide safe shutdown of compressor.
• Filter Frame Kit - All 3 phase units include a filter frame kit
which is shipped inside the unit from production. Field installation is required.
Johnson Controls Unitary Products
5291598-LTG-B-1216
NOMENCLATURE
PCG
4
A
24
50
2
X
1
A
1
2
3
4
5
6
7
8
9
1. Model Family
PCG - packaged A/C with gas heat,
PHG - packaged heat pump with gas heat,
PCE - packaged A/C with electric heat,
PHE - packaged heat pump with electric heat
5. Gas Heating Input BTU/Hr x 1000
050 = 50,000 BTU/Hr. input, blank = electric heat
2. Nominal Cooling Efficiency
4 = 14 SEER, 6 = 16 SEER, etc.
7. NOx Approval
X = low-NOx, blank = not low-Nox
3. Cabinet Size
A = small 35 x 51, B = large 45 x 51
8. Generation Level
1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000
24 = 24,000 BTU, etc.
9. Revision Level
A = original release, B = second release
6. Voltage-Phase-Frequency
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
Examples:
PHG4B421002X1A is a dual fuel, 14 SEER, 3-1/2 ton, large cabinet, single-stage heat, 100,000 BTU gas heat, 230 volt, single phase, low-NOx
model (first generation, first release)
COMPONENT LOCATION
FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)
CONTROL BOARD
TRANSFORMER
BLOWER MOTOR
HIGH VOLTAGE
CONTACTOR
TXV
PRESSURE SWITCH
INDOOR COIL
DRAFT INDUCER BLOWER
INDOOR BLOWER
GAS VALVE
COMPRESSOR
GAS HEAT
EXCHANGER
REMOVABLE
BASE RAILS
BURNER
ASSEMBLY
A0297-001
UNIT LIMITATIONS
Model
All Models
Unit Voltage
208/230-3-60
Johnson Controls Unitary Products
Min
187
Unit Limitations
Applied Voltage
Max
252
Outdoor DB Temp
Max (°F)
125
3
5291598-LTG-B-1216
ACCESSORIES
• Propane Conversion Kit (S1-1NP0704) - Kit includes
burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane.
• Economizer for Downflow Applications
(S1-2EE04708424, S1-2EE04708524) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design ensures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single enthalpy and dual
enthalpy are also available.
• Economizer for Horizontal Applications
(S1-2EE04708624, S1-2EE04708724) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design ensures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single enthalpy and dual
enthalpy are also available.
• Single/Dual Enthalpy Sensor (S1-2EC04700624) - Sensor
replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry
bulb temperature from outdoors plus the enthalpy content of
the outdoor air.
• CO2 Sensor Kit (S1-2AQ04700824) - Sensor kit detects
CO2 levels automatically and overrides the economizer
when CO2 levels rise above the preset limits.
• Outdoor Temp. Sensor Kit
(S1-2EC04700724S1-2EC04700724V) - Additional outdoor
air temp sensor kit used with economizers.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
• Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 14 inch high roof curbs.
• Manual Outdoor Damper
(S1-1FA0502, S1-1FA0501) - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct
mounted side supply/return applications. Includes hood and
screen assembly.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic and electro-mechanical thermostats. All units can operate with a single stage heat thermostat, but requires a multistage thermostat for cooling.
• Low Ambient Kit (S1-2LA04701024) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PCG6*
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCG6* price pages
for more details.
4
Johnson Controls Unitary Products
5291598-LTG-B-1216
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. Package units give you the flexibility and
choices you need in today’s market. These packaged cooling/
heating air conditioners are designed for outdoor installation.
Only utility and duct connections are required at the point of
installation. The single-stage gas fired heaters have stainless
steel tubular heat exchangers and spark to burner ignition.
They are available in natural gas with field conversion to
propane.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heating units, designed for outdoor installation.
For SEER ratings, refer to technical literature. They shall have
built in, equal size, field convertible duct connections for supply/
return or horizontal supply/return. The units shall be factory
wired, piped, charged with R-410A Refrigerant and factory
tested prior to shipment. All unit wiring shall be both numbered
and color coded. All models shall be rated in accordance with
DOE and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed and classified to ANSI
Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of G-90 galvanized, powderpainted steel, certified at 1000 hours salt spray test per ASTMB117 standards. The unit top shall be a single piece design,
with drip edges and no-seam corners to provide optimum water
integrity. Unit shall have a rigidly mounted outdoor coil guard to
provide protection from objects and personnel after installation.
Indoor blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit. Condensate pan shall be internally sloped and
conform to ASHRAE 62-89 self-draining standards, with 3/4”
NPT female ridged mount connection.
Johnson Controls Unitary Products
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of +/- 10% of the unit
nameplate voltage.
b. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
Coils:
a. Indoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced tin-coated copper tubes with all joints brazed.
b. Indoor coil shall be of the direct expansion, draw through
design.
c. Outdoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
d. Outdoor coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components
shall include:
a. Thermal expansion devices (TXVs) shall be factory
mounted and provided.
b. Filter/strainer to eliminate any foreign matter.
5
5291598-LTG-B-1216
GAS HEATING SECTION (If Equipped)
Heat exchanger and exhaust system shall be constructed of
corrosion-resistant materials and shall be designed with
induced draft combustion with post purge logic and redundant
main gas valve. The heat exchanger shall be of the tubular
type, constructed of stainless steel for corrosion resistance and
allowing minimum mixed air entering temperature of 40 ºF.
Burners shall be of the in-shot type, constructed of
aluminumized steel. All gas piping shall enter the unit cabinet at
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(es) (manual reset).
d. Flame proving controls.
All gas heat models will meet the California requirement for
emissions of less than 40 nanograms per Joule (California
requirement on single phase models only).
PHYSICAL DATA
NOMINAL TONNAGE
MODELS
PCG6B48
4.0
PCG6B36
3.0
PCG6B42
3.5
PCG6B60
5.0
Gross Capacity @ AHRI A point (MBH)
36.5
43.3
49.1
60.0
AHRI net capacity (MBH)
36.0
42.5
48.0
58.0
EER
12.5
12.5
12.5
12.0
SEER
16.0
16.0
16.0
16.0
Nominal CFM
1200
1400
1600
2000
AHRI Cooling Performance
3.0
3.4
3.6
4.6
R410A
R410A
R410A
R410A
11-8
11-2
13-8
14-0
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI Gas Heat Performance
Heating model
065
100
065
100
065
100
125
065
100
125
Heat input - High Fire (KBtu)
65
100
65
100
65
100
125
65
100
125
Heat output - High Fire (KBtu)
52
81
52
81
52
81
101
52
81
101
Heat input - Low Fire (KBtu)
43
65
43
65
43
65
82
43
65
82
Heat output - Low Fire (KBtu)
34
53
34
53
34
53
66
34
53
66
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
No. burners
2
3
2
3
2
3
4
2
3
4
No. stages
2
2
2
2
2
2
2
2
2
2
AFUE %
Temperature Rise Range - High Fire (°F)
40-70
40-70
40-70
40-70
Temperature Rise Range - Low Fire (°F)
25-55
25-55
25-55
25-55
Max. Static Pressure w.c.
0.5
0.5
0.5
0.5
Max. Outlet Air Temp. (°F)
180
180
180
180
Gas piping connection (in.)
1/2
1/2
1/2
1/2
Length
51-1/4
51-1/4
51-1/4
51-1/4
Width
45-3/4
45-3/4
45-3/4
45-3/4
Height
49
49
53
55
Scroll
Scroll
Scroll
Scroll
2
2
2
2
25.9
Dimensions (inches)
Compressor
Type
Stages
Condenser Coil Data
Face area (Sq. Ft.)
19.5
19.5
23.8
Rows
2
2
2
2
Fins per inch
22
22
22
22
Tube diameter
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Continued on next page.
6
Johnson Controls Unitary Products
5291598-LTG-B-1216
PHYSICAL DATA (Continued)
NOMINAL TONNAGE
PCG6B36
3.0
PCG6B42
3.5
MODELS
PCG6B48
4.0
PCG6B60
5.0
Evaporator Coil Data
Face area (Sq. Ft.)
6.3
6.3
6.3
Rows
3
3
3
4
Fins per inch
16
16
16
16
Tube diameter
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
TXV
TXV
TXV
TXV
Refrigerant control
6.3
Condenser Fan Data
Fan diameter (Inch)
26
26
26
26
Type
Prop
Prop
Prop
Prop
Drive type
Direct
1
Direct
Direct
Direct
1
1
1
1/3
1/3
1/3
1/3
No. speeds
Motor HP each
RPM
850
850
850
850
Nominal total CFM
3200
3200
3200
3200
Direct Drive Evaporator Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
11 x 10
11 x 10
11 x 10
11 x 10
Centrifugal
Centrifugal
Centrifugal
Centrifugal
1/2
3/4
3/4
1
1200 Max
3/4
1200 Max
1200 Max
1200 Max
48
48
48
48
B
B
B
B
Filters
Filter Size
Quantity - Size
Johnson Controls Unitary Products
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters.
For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for replacement
filter sizes. Filter sizes: A=20x20, B=20x30.
7
5291598-LTG-B-1216
COOLING PERFORMANCE DATA - 3 TON (LOW SPEED) - MODEL NO. PCG6B36
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
34.8
34.1
2.35
33.2
32.4
2.56
31.5
30.7
2.77
30.2
29.1
3.03
28.8
27.4
3.29
25.6
23.7
3.61
22.5
20.1
3.92
19.4
16.5
4.23
80
62
41.4
28.8
2.20
39.0
27.6
2.40
36.6
26.4
2.61
34.7
25.1
2.90
32.7
23.9
3.20
28.5
21.5
3.55
24.4
19.1
3.88
20.4
16.8
4.22
600
75
62
41.7
25.1
2.19
39.2
23.7
2.39
36.7
22.2
2.59
34.1
21.0
2.86
31.5
19.8
3.13
27.8
17.5
3.49
24.2
15.2
3.84
20.6
13.0
4.19
80
67
46.0
25.4
2.16
43.6
24.2
2.36
41.2
22.9
2.57
38.9
21.6
2.84
36.6
20.4
3.11
32.8
18.5
3.48
29.1
16.6
3.83
25.5
14.7
4.19
80
72
49.1
20.5
2.13
47.3
19.5
2.33
45.5
18.4
2.52
42.3
17.0
2.78
39.2
15.7
3.05
35.3
13.9
3.41
31.6
12.1
3.77
27.9
10.4
4.13
80
57
37.3
36.8
2.30
35.4
34.8
2.51
33.5
32.9
2.71
31.6
30.9
2.98
29.6
28.8
3.24
26.1
25.0
3.56
22.6
21.3
3.87
19.2
17.6
4.17
80
62
41.2
32.1
2.16
38.8
30.7
2.37
36.3
29.4
2.57
34.0
28.3
2.85
31.7
27.1
3.13
27.7
24.1
3.49
23.8
21.1
3.83
20.0
18.1
4.18
800
75
62
41.5
27.8
2.16
38.8
26.3
2.36
36.1
24.8
2.56
33.4
23.5
2.83
30.6
22.2
3.09
26.8
19.8
3.46
23.0
17.6
3.82
19.3
15.4
4.18
80
67
44.6
26.7
2.13
42.6
25.9
2.34
40.7
25.0
2.54
38.3
24.0
2.80
36.0
23.0
3.07
31.7
20.8
3.44
27.5
18.7
3.79
23.2
16.6
4.15
80
72
47.3
21.0
2.11
45.7
20.3
2.31
44.2
19.6
2.50
41.2
18.2
2.76
38.1
16.8
3.02
33.9
14.8
3.39
29.8
12.9
3.74
25.7
11.0
4.10
80
57
39.7
39.4
2.25
37.6
37.3
2.46
35.4
35.1
2.66
33.0
32.7
2.92
30.5
30.2
3.19
26.5
26.3
3.50
22.7
22.5
3.81
18.9
18.7
4.11
80
62
41.0
35.4
2.13
38.5
33.9
2.33
36.0
32.4
2.53
33.3
31.4
2.80
30.7
30.4
3.06
26.9
26.7
3.43
23.2
23.0
3.78
19.6
19.4
4.14
1000
75
62
41.2
30.6
2.13
38.4
28.9
2.33
35.6
27.3
2.54
32.7
25.9
2.80
29.8
24.5
3.06
25.7
22.2
3.44
21.8
20.0
3.80
17.9
17.7
4.17
80
67
43.1
28.0
2.11
41.7
27.6
2.31
40.2
27.2
2.51
37.8
26.4
2.77
35.4
25.6
3.03
30.5
23.2
3.40
25.8
20.9
3.76
21.0
18.5
4.12
80
72
45.4
21.5
2.09
44.2
21.2
2.29
42.9
20.8
2.48
40.0
19.4
2.74
37.1
17.9
2.99
32.4
15.8
3.36
27.9
13.7
3.72
23.4
11.7
4.07
80
72
48.4
12.8
2.17
46.6
17.9
2.37
44.7
22.9
2.57
42.6
21.3
2.83
40.4
19.8
3.09
37.0
18.3
3.48
33.7
16.9
3.86
30.4
15.5
4.24
80
57
43.8
40.6
2.20
42.1
39.0
2.40
40.4
37.4
2.61
38.3
35.3
2.87
36.2
33.2
3.13
32.7
30.7
3.52
29.3
28.2
3.90
25.9
25.7
4.29
80
62
44.6
38.7
2.20
42.2
38.0
2.40
39.8
37.3
2.61
37.1
35.7
2.87
34.3
34.1
3.13
31.2
30.9
3.52
28.1
27.9
3.90
25.0
24.8
4.29
1400
75
62
43.5
32.5
2.20
41.2
31.7
2.40
38.9
30.9
2.59
36.3
29.5
2.85
33.7
28.1
3.11
30.2
26.3
3.51
26.8
24.5
3.88
23.4
22.8
4.26
80
67
48.0
32.0
2.24
45.5
31.4
2.44
43.0
30.8
2.64
40.1
29.5
2.90
37.2
28.2
3.15
33.5
26.6
3.54
29.8
25.2
3.91
26.1
23.7
4.29
80
72
50.2
25.0
2.25
48.9
24.1
2.46
47.5
23.3
2.67
44.8
22.2
2.92
42.1
21.1
3.17
38.3
19.6
3.56
34.6
18.1
3.94
30.9
16.6
4.31
COOLING PERFORMANCE DATA - 3 TON (HIGH SPEED) - MODEL NO. PCG6B36
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
8
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
38.5
36.0
2.02
37.1
34.6
2.21
35.6
33.3
2.41
33.9
31.6
2.68
32.2
29.8
2.94
29.4
27.8
3.34
26.7
25.7
3.74
24.1
23.7
4.13
80
62
41.0
32.3
2.04
38.7
31.4
2.24
36.3
30.5
2.43
34.1
29.4
2.69
31.9
28.2
2.95
29.0
26.5
3.35
26.1
24.8
3.73
23.3
23.1
4.11
1000
75
62
40.0
27.5
2.03
32.0
25.6
3.08
24.1
23.7
4.13
27.9
23.5
3.54
31.7
23.2
2.95
28.8
21.8
3.35
25.9
20.4
3.73
23.1
18.9
4.11
80
67
43.2
27.7
2.07
41.6
26.7
2.27
40.1
25.7
2.47
37.4
24.6
2.73
34.8
23.4
2.99
31.6
22.0
3.38
28.4
20.5
3.76
25.3
19.1
4.14
80
72
46.6
0.6
2.09
44.3
11.6
2.29
41.9
22.5
2.48
40.3
20.5
2.74
38.7
18.5
3.00
35.7
17.1
3.40
32.8
15.8
3.78
29.9
14.4
4.16
80
57
41.2
38.3
2.11
39.6
36.8
2.31
38.0
35.3
2.51
36.1
33.4
2.77
34.2
31.5
3.03
31.0
29.2
3.43
28.0
27.0
3.82
25.0
24.7
4.21
80
62
42.8
35.5
2.12
40.4
34.7
2.32
38.1
33.9
2.52
35.6
32.5
2.78
33.1
31.2
3.04
30.1
28.7
3.43
27.1
26.4
3.82
24.1
24.0
4.20
1200
75
62
41.7
30.0
2.12
36.6
28.6
2.74
31.5
27.3
3.36
32.1
26.5
3.20
32.7
25.7
3.03
29.5
24.0
3.43
26.4
22.4
3.81
23.3
20.9
4.19
80
67
45.6
29.9
2.15
43.6
29.1
2.35
41.5
28.2
2.55
38.8
27.0
2.81
36.0
25.8
3.07
32.5
24.3
3.46
29.1
22.8
3.84
25.7
21.4
4.21
Johnson Controls Unitary Products
5291598-LTG-B-1216
COOLING PERFORMANCE DATA - 3.5 TON (LOW SPEED) - MODEL NO. PCG6B42
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
30.2
29.7
0.97
27.7
27.3
1.13
25.2
25.0
1.29
22.4
22.2
1.48
19.6
19.4
1.67
17.0
16.8
1.94
14.5
14.4
2.19
12.0
11.9
2.45
80
62
33.8
26.3
0.96
32.0
25.4
1.11
30.1
24.5
1.26
27.0
22.4
1.47
23.9
20.3
1.68
20.4
18.0
1.94
17.0
15.8
2.20
13.6
13.5
2.45
800
75
62
24.4
23.9
0.93
23.2
22.6
1.09
22.1
21.2
1.25
21.1
20.2
1.45
20.1
19.2
1.66
18.8
17.9
1.92
17.5
16.6
2.17
16.2
15.3
2.42
80
67
36.3
21.8
0.98
34.8
21.3
1.14
33.3
20.9
1.29
31.1
19.6
1.49
28.9
18.3
1.68
25.0
17.6
1.94
21.2
17.0
2.19
17.4
16.3
2.44
80
72
39.4
18.2
0.98
37.3
17.5
1.10
35.1
16.9
1.22
34.4
16.0
1.43
33.8
15.0
1.63
29.8
13.4
1.90
25.8
11.9
2.16
21.9
10.3
2.42
80
57
33.3
32.0
0.97
30.3
29.5
1.13
27.2
27.0
1.28
24.1
23.9
1.48
21.0
20.9
1.69
18.6
18.4
1.95
16.2
16.1
2.20
13.9
13.7
2.46
80
62
36.0
29.6
0.97
34.0
28.7
1.12
32.0
27.8
1.27
29.0
25.8
1.48
26.0
23.7
1.69
22.2
20.6
1.95
18.4
17.6
2.20
14.7
14.6
2.46
1000
75
62
26.3
25.8
0.94
25.4
24.7
1.09
24.6
23.6
1.24
23.5
22.5
1.45
22.5
21.4
1.66
21.1
20.0
1.92
19.8
18.6
2.18
18.5
17.3
2.44
80
67
37.9
23.8
1.00
36.6
23.6
1.15
35.3
23.5
1.30
33.0
22.2
1.49
30.7
21.0
1.69
27.0
20.2
1.95
23.4
19.3
2.20
19.8
18.5
2.45
80
72
40.4
19.3
1.00
38.9
19.0
1.11
37.5
18.7
1.23
35.8
17.6
1.44
34.1
16.5
1.64
31.3
14.9
1.91
28.7
13.3
2.17
26.0
11.7
2.43
80
57
36.4
34.4
0.97
32.8
31.7
1.12
29.2
29.0
1.27
25.9
25.7
1.48
22.5
22.3
1.70
20.2
20.0
1.96
18.0
17.8
2.21
15.8
15.6
2.47
80
62
38.2
32.8
0.97
36.0
31.9
1.13
33.9
31.1
1.28
31.0
29.1
1.49
28.2
27.1
1.70
23.9
23.2
1.96
19.8
19.4
2.21
15.8
15.6
2.47
1200
75
62
28.1
27.6
0.94
27.6
26.8
1.09
27.1
26.0
1.24
26.0
24.8
1.45
24.8
23.6
1.66
23.4
22.1
1.93
22.0
20.7
2.19
20.7
19.3
2.46
80
67
39.5
25.9
1.01
38.4
25.9
1.15
37.3
26.0
1.30
34.9
24.8
1.50
32.5
23.7
1.70
29.0
22.7
1.95
25.6
21.7
2.20
22.1
20.8
2.45
80
72
41.3
20.4
1.01
40.6
20.5
1.13
40.0
20.5
1.25
37.2
19.3
1.45
34.4
18.0
1.65
32.9
16.3
1.92
31.5
14.7
2.18
30.1
13.1
2.44
80
62
51.4
42.4
2.39
49.3
41.8
2.65
47.1
41.2
2.91
42.9
37.6
3.22
38.8
34.0
3.54
34.4
31.0
4.00
30.1
28.2
4.44
25.8
25.4
4.88
1520
75
62
32.8
31.9
2.36
33.6
32.4
2.64
34.5
33.0
2.91
34.3
32.7
3.26
34.1
32.4
3.61
32.5
30.7
4.07
31.0
29.2
4.52
29.5
27.6
4.97
80
67
52.8
32.3
2.27
51.8
32.6
2.54
50.8
32.9
2.80
47.3
32.2
3.20
43.8
31.6
3.59
39.4
29.5
3.97
35.2
27.4
4.35
30.9
25.4
4.73
80
72
56.7
24.5
2.26
56.7
25.4
2.61
56.6
26.4
2.95
54.0
24.8
3.28
51.4
23.3
3.60
46.8
21.5
4.05
42.4
19.7
4.49
37.9
18.0
4.93
COOLING PERFORMANCE DATA - HIGH - 3.5 TON (HIGH SPEED) - MODEL NO. PCG6B42
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
Johnson Controls Unitary Products
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
43.6
41.7
2.19
39.9
38.6
2.44
36.1
35.5
2.68
33.3
32.8
3.02
30.5
30.0
3.35
27.9
27.5
3.81
25.4
25.0
4.25
22.9
22.5
4.69
80
62
47.7
36.8
2.22
45.2
35.7
2.46
42.7
34.6
2.71
39.4
33.0
3.03
36.0
31.4
3.35
32.6
29.1
3.81
29.3
26.9
4.25
25.9
24.7
4.69
1120
75
62
30.8
29.9
2.17
31.1
29.9
2.43
31.4
29.9
2.69
30.5
29.0
3.05
29.7
28.1
3.40
28.2
26.6
3.87
26.8
25.1
4.32
25.4
23.7
4.78
80
67
50.0
30.0
2.16
49.1
29.6
2.42
48.3
29.2
2.67
45.2
27.8
3.04
42.0
26.4
3.41
38.0
24.7
3.82
34.1
23.0
4.21
30.3
21.3
4.61
80
72
55.0
23.2
2.16
53.4
23.2
2.46
51.8
23.2
2.77
49.9
22.0
3.09
48.0
20.9
3.41
44.3
19.2
3.86
40.6
17.6
4.30
37.0
15.9
4.74
80
57
45.8
43.7
2.29
41.9
40.5
2.54
38.0
37.3
2.79
35.2
34.5
3.12
32.3
31.7
3.45
29.5
29.0
3.90
26.7
26.3
4.35
24.0
23.6
4.79
80
62
49.6
39.6
2.30
47.2
38.8
2.56
44.9
37.9
2.81
41.2
35.3
3.13
37.4
32.7
3.45
33.5
30.1
3.90
29.7
27.6
4.34
25.9
25.1
4.78
1320
75
62
31.8
30.9
2.26
32.4
31.2
2.53
33.0
31.4
2.80
32.4
30.8
3.16
31.9
30.2
3.51
30.4
28.7
3.97
28.9
27.2
4.42
27.4
25.6
4.87
80
67
51.4
31.2
2.22
50.5
31.1
2.48
49.6
31.1
2.74
46.2
30.0
3.12
42.9
29.0
3.50
38.7
27.1
3.90
34.7
25.2
4.28
30.6
23.4
4.67
80
72
55.8
23.8
2.21
55.0
24.3
2.54
54.2
24.8
2.86
52.0
23.4
3.18
49.7
22.1
3.51
45.5
20.3
3.96
41.5
18.6
4.39
37.5
17.0
4.83
80
57
48.1
45.8
2.39
44.0
42.5
2.64
39.9
39.2
2.90
37.0
36.3
3.22
34.1
33.5
3.54
31.0
30.5
4.00
28.0
27.5
4.44
25.1
24.6
4.89
9
5291598-LTG-B-1216
COOLING PERFORMANCE DATA - 4 TON (LOW SPEED) - MODEL NO. PCG6B48
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
34.3
32.3
1.67
32.4
30.4
1.86
30.4
28.6
2.05
27.3
26.2
2.39
24.2
23.8
2.72
21.9
21.5
3.15
19.6
19.3
3.56
17.3
17.0
3.98
80
62
37.4
28.7
1.64
34.5
27.4
1.83
31.6
26.0
2.03
29.1
23.9
2.36
26.7
21.8
2.68
23.6
20.3
3.16
20.6
18.8
3.63
17.6
17.4
4.10
900
75
62
36.3
24.7
1.65
34.1
21.0
1.85
32.0
17.4
2.04
28.2
18.1
2.43
24.5
18.8
2.82
20.8
17.0
3.22
17.1
15.1
3.60
13.5
13.3
3.98
80
67
41.1
24.9
1.63
38.7
23.5
1.79
36.3
22.1
1.96
34.0
20.8
2.37
31.6
19.4
2.78
27.3
19.1
3.16
23.2
18.8
3.53
19.1
18.6
3.91
80
72
45.6
20.0
1.49
43.8
18.9
1.73
42.0
17.8
1.97
39.1
16.5
2.30
36.1
15.1
2.63
32.6
13.6
3.06
29.2
12.2
3.47
25.7
10.7
3.89
80
57
37.5
34.8
1.63
35.2
32.8
1.85
33.0
30.7
2.07
29.4
28.0
2.41
25.8
25.4
2.74
23.1
22.7
3.17
20.4
20.1
3.58
17.7
17.4
3.99
80
62
39.7
32.1
1.61
36.8
30.2
1.83
33.9
28.2
2.05
31.1
26.6
2.38
28.2
25.0
2.72
24.7
22.5
3.17
21.2
20.0
3.61
17.8
17.5
4.05
1100
75
62
38.7
27.2
1.62
36.6
23.2
1.84
34.5
19.1
2.06
29.9
19.9
2.42
25.3
20.8
2.78
21.1
18.0
3.20
16.9
15.3
3.60
12.7
12.5
4.00
80
67
43.6
27.2
1.59
41.0
25.8
1.82
38.4
24.4
2.05
35.7
22.9
2.39
33.1
21.5
2.74
29.0
21.1
3.14
25.0
20.8
3.53
21.0
20.4
3.92
80
72
48.0
21.8
1.52
46.2
20.7
1.76
44.5
19.6
2.01
41.2
18.0
2.33
37.9
16.4
2.65
33.9
14.7
3.09
30.1
13.0
3.51
26.3
11.4
3.93
80
57
40.6
37.4
1.58
38.1
35.1
1.84
35.5
32.9
2.10
31.4
29.9
2.43
27.4
26.9
2.76
24.2
23.9
3.18
21.2
20.9
3.59
18.2
17.9
4.00
80
62
42.1
35.5
1.58
39.1
33.0
1.82
36.2
30.5
2.06
33.0
29.3
2.41
29.7
28.2
2.75
25.7
24.6
3.18
21.8
21.1
3.60
17.9
17.6
4.01
1300
75
62
41.1
29.8
1.58
39.1
25.3
1.83
37.1
20.8
2.08
31.6
21.8
2.41
26.2
22.8
2.74
21.3
19.0
3.18
16.6
15.4
3.60
11.9
11.8
4.02
80
67
46.2
29.6
1.56
43.3
28.1
1.84
40.4
26.6
2.13
37.5
25.1
2.42
34.6
23.6
2.70
30.6
23.2
3.12
26.8
22.7
3.53
22.9
22.3
3.93
80
72
50.3
23.6
1.55
48.7
22.5
1.79
47.0
21.5
2.04
43.4
19.5
2.36
39.7
17.6
2.68
35.3
15.7
3.12
31.1
13.9
3.54
26.8
12.1
3.97
80
62
54.3
45.2
2.88
52.1
31.7
3.06
49.9
18.2
3.25
46.1
28.9
3.67
42.3
39.7
4.09
38.3
36.5
4.60
34.5
33.5
5.09
30.7
30.4
5.58
1800
75
62
55.6
38.2
2.87
53.3
40.0
3.14
51.0
41.8
3.41
47.2
37.2
3.75
43.4
32.6
4.08
38.9
25.1
4.52
34.5
17.9
4.95
30.1
10.6
5.39
80
67
56.9
35.0
2.90
54.9
35.5
3.19
52.8
36.0
3.47
48.9
34.4
3.81
45.1
32.7
4.15
40.9
30.9
4.65
36.8
29.1
5.13
32.7
27.3
5.62
80
72
60.1
28.1
2.89
59.1
36.5
3.20
58.1
44.9
3.50
54.2
34.9
3.85
50.3
25.0
4.19
45.7
22.9
4.68
41.2
20.8
5.17
36.7
18.8
5.65
COOLING PERFORMANCE DATA - HIGH - 4 TON (HIGH SPEED) - MODEL NO. PCG6B48
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
10
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
46.5
45.7
2.66
43.8
43.3
2.93
41.1
41.0
3.19
40.3
39.8
3.55
39.4
38.6
3.91
34.6
34.0
4.42
29.9
29.5
4.91
25.2
25.0
5.41
80
62
54.3
41.3
2.72
51.2
40.2
3.06
48.2
39.1
3.39
45.2
37.3
3.66
42.2
35.5
3.93
37.5
33.1
4.49
33.0
30.7
5.03
28.4
28.4
5.58
1400
75
62
55.5
35.4
2.72
52.2
34.1
2.98
48.8
32.9
3.24
46.3
31.1
3.58
43.8
29.3
3.92
39.1
27.4
4.43
34.6
25.5
4.92
30.1
23.6
5.41
80
67
56.6
35.0
2.93
54.8
33.8
3.11
52.9
32.6
3.29
49.4
31.2
3.72
45.9
29.7
4.15
41.7
27.8
4.65
37.7
26.0
5.14
33.6
24.2
5.62
80
72
59.6
27.8
2.75
58.3
27.0
3.13
56.9
26.1
3.51
53.8
24.6
3.77
50.7
23.1
4.03
46.5
21.2
4.58
42.4
19.3
5.12
38.2
17.5
5.66
80
57
47.9
47.2
2.76
44.9
44.3
3.03
42.0
41.5
3.29
40.1
39.4
3.64
38.1
37.4
4.00
34.0
33.4
4.51
30.0
29.6
5.00
26.0
25.8
5.50
80
62
54.3
43.3
2.80
51.7
35.9
3.06
49.1
28.6
3.32
45.6
33.1
3.67
42.2
37.6
4.01
37.9
34.8
4.54
33.8
32.1
5.06
29.6
29.4
5.58
1600
75
62
55.6
36.8
2.80
52.7
37.0
3.06
49.9
37.3
3.33
46.8
34.1
3.66
43.6
30.9
4.00
39.0
26.2
4.47
34.5
21.7
4.94
30.1
17.1
5.40
80
67
56.8
35.0
2.92
54.8
34.7
3.15
52.9
34.3
3.38
49.2
32.8
3.77
45.5
31.2
4.15
41.3
29.3
4.65
37.2
27.6
5.13
33.2
25.8
5.62
80
72
59.9
28.0
2.82
58.7
31.7
3.16
57.5
35.5
3.51
54.0
29.8
3.81
50.5
24.1
4.11
46.1
22.0
4.63
41.8
20.1
5.14
37.5
18.1
5.66
80
57
49.2
48.7
2.86
46.1
45.3
3.13
43.0
41.9
3.39
39.9
39.1
3.74
36.8
36.2
4.09
33.4
32.9
4.59
30.1
29.8
5.09
26.8
26.6
5.58
Johnson Controls Unitary Products
5291598-LTG-B-1216
COOLING PERFORMANCE DATA - 5 TON (LOW SPEED) - MODEL NO. PCG6B60
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
44.6
44.6
1.77
42.1
42.1
2.05
39.6
39.6
2.34
36.5
36.5
2.69
33.4
33.4
3.04
30.0
30.0
3.56
26.7
26.7
4.07
23.4
23.4
4.57
80
62
51.1
43.1
1.77
47.6
41.4
2.05
44.2
39.6
2.33
40.6
37.6
2.67
37.0
35.5
3.02
34.0
32.8
3.48
31.1
30.3
3.93
28.3
27.7
4.38
1100
75
62
50.5
36.8
1.77
46.8
35.0
2.14
43.1
33.3
2.51
39.8
31.4
2.87
36.4
29.5
3.23
32.7
27.2
3.62
29.0
25.0
4.00
25.3
22.8
4.39
80
67
55.7
36.5
1.74
52.1
34.9
2.11
48.5
33.3
2.48
44.8
31.4
2.74
41.0
29.5
3.00
36.5
27.4
3.46
32.1
25.4
3.91
27.7
23.4
4.35
80
72
59.9
30.0
1.90
57.3
28.5
2.08
54.8
26.9
2.26
50.8
25.1
2.61
46.9
23.2
2.96
42.1
21.2
3.43
37.4
19.2
3.87
32.7
17.2
4.32
80
57
47.1
47.1
1.87
44.3
44.3
2.15
41.6
41.6
2.43
38.3
38.3
2.78
35.0
35.0
3.13
31.3
31.3
3.62
27.8
27.8
4.10
24.3
24.3
4.58
80
62
53.0
47.5
1.87
49.4
45.6
2.15
45.8
43.8
2.42
41.8
40.9
2.77
37.8
37.8
3.13
34.3
34.3
3.59
30.9
30.9
4.03
27.5
27.5
4.47
1300
75
62
51.7
40.0
1.88
48.4
38.1
2.20
45.1
36.2
2.51
41.5
34.2
2.87
37.8
32.2
3.23
33.6
29.6
3.66
29.4
27.1
4.07
25.3
24.6
4.49
80
67
57.4
39.4
1.84
53.9
37.8
2.16
50.3
36.2
2.48
46.3
34.3
2.79
42.3
32.3
3.10
37.3
30.1
3.56
32.5
28.0
4.01
27.6
25.9
4.46
80
72
61.8
31.6
1.92
59.6
30.2
2.14
57.4
28.7
2.36
53.0
26.8
2.71
48.5
25.0
3.07
43.3
22.7
3.53
38.3
20.6
3.98
33.2
18.4
4.43
80
57
49.5
49.5
1.98
46.6
46.6
2.25
43.7
43.7
2.52
40.1
40.1
2.87
36.5
36.5
3.22
32.7
32.7
3.69
28.9
28.9
4.13
25.1
25.1
4.58
80
62
54.9
51.8
1.98
51.2
49.9
2.24
47.4
47.4
2.51
43.0
43.0
2.88
38.6
38.6
3.25
34.6
34.6
3.70
30.6
30.6
4.13
26.7
26.7
4.57
1500
75
62
53.0
43.3
1.99
50.1
41.2
2.25
47.1
39.1
2.52
43.2
37.0
2.88
39.3
34.9
3.24
34.5
32.0
3.70
29.9
29.2
4.14
25.2
25.2
4.59
80
67
59.2
42.4
1.94
55.7
40.8
2.22
52.1
39.2
2.49
47.9
37.2
2.84
43.6
35.1
3.20
38.1
32.9
3.66
32.8
30.7
4.11
27.5
27.5
4.56
80
72
63.8
33.3
1.94
61.9
31.9
2.20
60.1
30.4
2.45
55.1
28.6
2.81
50.2
26.7
3.17
44.6
24.3
3.63
39.1
21.9
4.09
33.7
19.6
4.54
80
72
77.7
38.2
3.14
75.5
46.7
3.51
73.4
55.3
3.89
68.6
43.3
4.17
63.9
31.4
4.44
58.7
29.3
5.00
53.8
27.2
5.54
48.8
25.1
6.09
80
57
63.5
63.5
3.26
57.2
57.2
3.53
50.9
50.9
3.80
46.8
46.8
4.16
42.8
42.8
4.52
38.9
38.9
5.03
35.1
35.1
5.54
31.4
31.4
6.04
80
62
72.3
63.4
3.30
68.1
31.9
3.42
64.0
0.3
3.55
59.2
26.7
4.04
54.3
53.0
4.53
49.5
48.7
5.04
44.9
44.5
5.54
40.2
40.2
6.04
2000
75
62
68.8
52.2
3.30
64.7
56.8
3.56
60.6
60.6
3.83
56.8
52.7
4.17
53.0
43.9
4.51
48.3
29.1
4.92
43.8
14.7
5.33
39.3
0.3
5.74
80
67
75.1
51.5
3.34
71.3
49.8
3.62
67.4
48.0
3.90
62.4
45.7
4.25
57.4
43.3
4.60
52.3
41.1
5.11
47.4
39.0
5.61
42.5
36.8
6.11
80
72
78.3
39.1
3.35
76.9
57.8
3.66
75.4
75.4
3.97
70.2
54.5
4.32
64.9
32.6
4.66
59.6
30.4
5.17
54.4
28.2
5.66
49.3
26.1
6.16
COOLING PERFORMANCE DATA - 5 TON (HIGH SPEED) - MODEL NO. PCG6B60
CONDENSER
ENTERING AIR
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
Johnson Controls Unitary Products
ID CFM
IDDB
IDWB
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
80
57
59.2
59.2
2.80
54.3
54.3
3.07
49.3
49.3
3.33
48.7
48.7
3.71
48.0
48.0
4.09
42.5
42.5
4.60
37.0
37.0
5.10
31.6
31.6
5.60
80
62
68.9
55.8
2.86
64.1
53.9
3.25
59.2
52.0
3.65
55.4
49.6
3.87
51.6
47.2
4.10
46.6
43.9
4.71
41.8
40.7
5.29
37.0
37.0
5.88
1600
75
62
66.5
47.0
2.87
61.7
45.4
3.13
57.0
43.7
3.39
53.9
41.4
3.74
50.7
39.1
4.09
45.9
36.8
4.61
41.3
34.7
5.12
36.6
32.5
5.63
80
67
71.8
46.7
3.21
68.4
44.9
3.34
65.1
43.0
3.47
60.5
41.0
3.95
55.9
39.1
4.44
50.9
36.9
4.96
46.0
34.7
5.46
41.1
32.6
5.96
80
72
77.1
37.2
2.93
74.2
35.7
3.37
71.3
34.2
3.81
67.1
32.2
4.02
62.8
30.3
4.23
57.9
28.2
4.84
53.1
26.2
5.43
48.2
24.2
6.01
80
57
61.3
61.3
3.03
55.7
55.7
3.30
50.1
50.1
3.57
47.8
47.8
3.94
45.4
45.4
4.30
40.7
40.7
4.82
36.1
36.1
5.32
31.5
31.5
5.82
80
62
70.6
59.6
3.08
66.1
42.9
3.34
61.6
26.2
3.60
57.3
38.2
3.96
53.0
50.1
4.31
48.1
46.3
4.87
43.4
42.6
5.42
38.6
38.6
5.96
1800
75
62
67.6
49.6
3.08
63.2
51.1
3.35
58.8
52.5
3.61
55.3
47.0
3.96
51.8
41.5
4.30
47.1
33.0
4.77
42.5
24.7
5.23
37.9
16.4
5.68
80
67
73.5
49.1
3.28
69.9
47.3
3.48
66.3
45.5
3.68
61.5
43.3
4.10
56.7
41.2
4.52
51.6
39.0
5.04
46.7
36.9
5.54
41.8
34.7
6.04
11
5291598-LTG-B-1216
COIL GUARD
HIGH VOLTAGE
CONNECTION 7/8”
C
HIGH VOLTAGE
CONNECTION 1-3/32”
COMBUSTION AIR INTAKE
HEAT EXCHANGER ACCESS PANEL
COMPRESSOR
ACCESS PANEL
EXHAUST HOOD
CONDENSATE
DRAIN
BLOWER
ACCESS
PANEL
A
B
LOW VOLTAGE CONNECTION
GAS SUPPLY
CONTROL ACCESS
PANEL
A0296-001
UNIT DIMENSIONS
Model
A
51-1/4
51-1/4
51-1/4
51-1/4
36
42
48
60
Dimensions
B
45-3/4
45-3/4
45-3/4
45-3/4
C
49
49
53
55
UNIT CLEARANCES1 2
Direction
Distance (in.)
Direction
Distance (in.)
Top3
36
Power Entry (Right Side)
36
Side Opposite Ducts
36
Left Side
24
Duct Panel
0
Bottom4
1
NOTES:
1.
2.
3.
4.
A 1" clearance must be provided between any combustible material and the supply air duct work.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
Units may be installed on combustible materials made from wood or class A, B or C roof covering materials only if factory base rails are left in place as shipped.
INDOOR BLOWER SPECIFICATIONS
Motor
Model
HP
RPM
EFF.
SF
36065
1/2
Variable
0.8
1.0
Frame
48
36100, 42065. 42100, 48065, 48100, 48125
3/4
Variable
0.8
1.0
48
60065, 60100, 60125
1
Variable
0.8
1.0
48
SOUND PERFORMANCE
Model
(Tons)
36
42
48
60
Sound Rating1
dB (A)
74
74
74
76
125
58.5
63.5
63.5
72.3
250
61.8
63.9
63.9
65.0
Octave Band Centerline Frequency (Hz)
500
1000
2000
65.4
66.5
60.7
62.3
65
64
62.3
65
64
63.9
64
60
4000
54.8
54.1
54.1
55.5
8000
49.8
46.6
46.6
49.0
NOTES:
1. Rated in accordance with AHRI Standard 270.
12
Johnson Controls Unitary Products
5291598-LTG-B-1216
ELECTRICAL DATA
Model
Compressor
Voltage
36065
36100
42065, 42100
48065, 48100, 48125
60065, 60100, 60125
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
OD Fan
Motor
Supply
Blower Motor
RLA
LRA
MCC
FLA
FLA
11.6
11.6
14.2
14.0
16.2
73.0
73.0
88.0
83.1
110.0
18.1
18.1
22.1
21.9
25.3
1.7
1.7
1.7
1.7
1.7
3.8
5.4
5.4
5.4
7.0
MCA1
(Amps)
Max Fuse2/
Breaker3 Size
(Amps)
20.0
21.6
24.9
24.6
29.0
30
30
35
35
40
NOTES:
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.
"D"
CENTER OF
GRAVITY
COMPRESSOR
"C"
"A"
FRONT
OF UNIT
X
Y
"B"
A0295-001-TG
WEIGHTS & DIMENSIONS
Model
36065
36100
42065
42100
48065
48100
48125
60065
60100
60125
Weight (lbs.)
Shipping
Operating
466
461
473
468
500
495
502
497
520
515
528
523
533
528
537
532
541
536
548
543
Johnson Controls Unitary Products
Center of Gravity
X
Y
28
15
28
15
28
15
28
15
28
15
28
15
28
15
29
15
28
15
27
15
A
161
163
175
176
189
169
164
174
177
151
4 Point Load Location (lbs.)
B
C
113
96
114
101
123
104
124
101
116
93
139
115
145
124
142
124
140
117
167
141
D
91
90
93
96
117
100
95
92
102
84
13
5291598-LTG-B-1216
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION
Model
0.1
0.2
SCFM
SCFM
A
1371
1354
B
1293
1246
High Cool
C
1232
1178
D
1058
999
A
1153
1095
B
1015
952
Low Cool
C
882
805
D
805
718
36065
A
1126
1067
B
1015
952
High Heat
C
955
886
D
910
836
A
970
902
B
818
732
Low Heat
C
766
674
D
721
625
A
1374
1333
B
1304
1260
High Cool
C
1233
1186
D
1063
1006
A
1120
1067
B
1025
966
Low Cool
C
882
812
D
821
746
36100
A
1704
1667
B
1506
1468
High Heat
C
1322
1278
D
1251
1205
A
1392
1352
B
1251
1205
Low Heat
C
1139
1087
D
984
922
A
1555
1518
B
1473
1435
High Cool
C
1374
1333
D
1216
1168
A
1233
1186
B
1139
1087
Low Cool
C
1025
966
D
964
900
42065
A
1120
1067
B
1063
1006
High Heat
C
964
900
D
882
812
A
1101
1047
B
923
856
Low Heat
C
821
746
D
735
655
A
1555
1518
B
1473
1435
High Cool
C
1374
1333
D
1216
1168
A
1233
1186
B
1139
1087
Low Cool
C
1025
966
D
964
900
42100
A
1704
1667
B
1506
1468
High Heat
C
1322
1278
D
1251
1205
A
1392
1352
B
1251
1205
Low Heat
C
1139
1087
D
984
922
Continued on next pages. See notes at end of table.
14
Jumper Position
0.3
SCFM
1303
1206
1131
931
1036
884
741
642
1006
884
821
774
837
659
593
540
1298
1218
1137
937
1004
892
716
641
1645
1441
1238
1157
1318
1157
1027
841
1494
1406
1298
1117
1137
1027
892
816
1004
937
816
716
982
766
641
533
1494
1406
1298
1117
1137
1027
892
816
1645
1441
1238
1157
1318
1157
1027
841
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1257
1209
1148
1084
1152
1098
1028
938
929
853
1077
1012
859
762
694
635
979
899
810
751
802
709
646
582
501
415
625
556
523
436
376
294
945
860
777
718
802
709
646
582
584
508
721
642
661
592
537
453
742
659
599
527
540
456
397
314
314
234
473
377
413
314
251
172
1255
1204
1145
1100
1170
1116
1055
1007
965
915
1085
1029
871
806
735
678
944
882
813
758
823
756
684
625
480
412
633
559
552
475
392
321
1612
1572
1520
1477
1404
1358
1302
1259
1077
1030
1191
1138
1107
1051
987
938
1276
1226
1168
1123
1107
1051
987
938
839
785
968
907
769
700
625
564
1459
1414
1360
1318
1368
1320
1264
1220
1145
1100
1255
1204
1064
1007
942
892
1085
1029
965
915
968
907
839
785
684
625
823
756
596
534
742
672
944
882
813
758
735
678
871
806
742
672
596
534
480
412
633
559
919
857
787
732
538
473
688
616
552
475
392
321
266
189
435
353
1459
1414
1360
1318
1264
1220
1368
1320
1255
1204
1145
1100
942
892
1064
1007
1085
1029
965
915
839
785
968
907
823
756
684
625
596
534
742
672
1612
1572
1520
1477
1302
1259
1404
1358
1191
1138
1077
1030
987
938
1107
1051
1276
1226
1168
1123
987
938
1107
1051
968
907
839
785
625
564
769
700
0.8
SCFM
1008
865
790
582
697
528
359
247
664
528
453
396
472
265
190
131
1044
953
861
628
707
575
366
276
1419
1203
975
884
1067
884
733
515
1261
1164
1044
838
861
733
575
485
707
628
485
366
680
426
276
147
1261
1164
1044
838
861
733
575
485
1419
1203
975
884
1067
884
733
515
0.9
SCFM
934
813
738
523
643
467
297
193
608
467
391
333
410
211
142
102
993
896
799
550
635
494
270
174
1384
1159
920
824
1017
824
663
430
1220
1119
993
775
799
663
494
398
635
550
398
270
606
334
174
100
1220
1119
993
775
799
663
494
398
1384
1159
920
824
1017
824
663
430
1.0
SCFM
878
767
690
459
588
402
228
118
551
402
324
265
343
136
63
53
933
834
736
484
569
427
199
101
1327
1101
859
761
957
761
598
361
1162
1060
933
712
736
598
427
329
569
484
329
199
541
264
101
85
1162
1060
933
712
736
598
427
329
1327
1101
859
761
957
761
598
361
Johnson Controls Unitary Products
5291598-LTG-B-1216
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION (Continued)
Model
Jumper Position
0.1
0.2
SCFM
SCFM
A
1851
1809
B
1689
1652
High Cool
C
1614
1578
D
1374
1333
A
1473
1435
B
1374
1333
Low Cool
C
1322
1278
D
1286
1241
48065
A
1120
1067
B
1063
1006
High Heat
C
964
900
D
882
812
A
1101
1047
B
923
856
Low Heat
C
821
746
D
735
655
A
1851
1809
B
1689
1652
High Cool
C
1614
1578
D
1374
1333
A
1473
1435
B
1374
1333
Low Cool
C
1322
1278
D
1286
1241
48100
A
1704
1667
B
1506
1468
High Heat
C
1322
1278
D
1251
1205
A
1392
1352
B
1251
1205
Low Heat
C
1139
1087
D
984
922
A
1851
1809
B
1689
1652
High Cool
C
1614
1578
D
1374
1333
A
1473
1435
B
1374
1333
Low Cool
C
1322
1278
D
1286
1241
48125
A
2114
2046
B
1982
1930
High Heat
C
1785
1746
D
1614
1578
A
2114
2046
B
1982
1930
Low Heat
C
1490
1452
D
1357
1315
A
2149
2114
B
2013
1977
High Cool
C
1936
1900
D
1719
1685
A
1629
1591
B
1558
1516
Low Cool
C
1453
1406
D
1410
1361
60065
A
1276
1219
B
1133
1068
High Heat
C
1025
950
D
844
748
A
1228
1169
B
1086
1017
Low Heat
C
844
748
D
786
666
Continued on next page. See notes at end of table.
Johnson Controls Unitary Products
0.3
SCFM
1781
1630
1554
1298
1406
1298
1238
1197
1004
937
816
716
982
766
641
533
1781
1630
1554
1298
1406
1298
1238
1197
1645
1441
1238
1157
1318
1157
1027
841
1781
1630
1554
1298
1406
1298
1238
1197
1974
1887
1720
1554
1974
1887
1423
1278
2077
1941
1864
1642
1546
1469
1355
1307
1158
995
868
651
1104
940
651
593
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1746
1707
1656
1609
1504
1461
1597
1556
1520
1477
1424
1382
1145
1100
1255
1204
1368
1320
1264
1220
1145
1100
1255
1204
1191
1138
1077
1030
1032
984
1149
1095
944
882
813
758
735
678
871
806
742
672
596
534
480
412
633
559
919
857
787
732
538
473
688
616
552
475
392
321
266
189
435
353
1746
1707
1656
1609
1504
1461
1597
1556
1520
1477
1424
1382
1145
1100
1255
1204
1368
1320
1264
1220
1145
1100
1255
1204
1191
1138
1077
1030
1032
984
1149
1095
1612
1572
1520
1477
1302
1259
1404
1358
1191
1138
1077
1030
987
938
1107
1051
1276
1226
1168
1123
987
938
1107
1051
968
907
839
785
625
564
769
700
1746
1707
1656
1609
1504
1461
1597
1556
1520
1477
1424
1382
1145
1100
1255
1204
1368
1320
1264
1220
1145
1100
1255
1204
1191
1138
1077
1030
1032
984
1149
1095
1914
1874
1815
1745
1752
1697
1844
1806
1687
1647
1596
1551
1424
1382
1520
1477
1914
1874
1815
1745
1752
1697
1844
1806
1386
1339
1283
1240
1123
1077
1234
1182
2030
1989
1948
1905
1816
1772
1898
1860
1822
1783
1739
1695
1508
1465
1600
1555
1502
1455
1409
1362
1329
1280
1423
1375
1305
1255
1207
1153
1155
1100
1255
1204
1098
1040
987
927
793
730
922
849
788
713
654
591
433
372
563
494
1039
976
922
861
728
664
863
786
563
494
433
372
370
314
514
453
0.8
SCFM
1552
1404
1324
1044
1164
1044
975
930
707
628
485
366
680
426
276
147
1552
1404
1324
1044
1164
1044
975
930
1419
1203
975
884
1067
884
733
515
1552
1404
1324
1044
1164
1044
975
930
1696
1643
1494
1324
1696
1643
1183
1021
1859
1726
1649
1418
1315
1232
1100
1044
869
680
505
168
806
617
168
263
0.9
SCFM
1518
1368
1286
993
1119
993
920
872
635
550
398
270
606
334
174
100
1518
1368
1286
993
1119
993
920
872
1384
1159
920
824
1017
824
663
430
1518
1368
1286
993
1119
993
920
872
1645
1604
1459
1286
1645
1604
1139
969
1816
1677
1597
1372
1266
1181
1047
992
818
634
458
115
757
573
115
180
1.0
SCFM
1460
1310
1228
933
1060
933
859
810
569
484
329
199
541
264
101
85
1460
1310
1228
933
1060
933
859
810
1327
1101
859
761
957
761
598
361
1460
1310
1228
933
1060
933
859
810
1582
1545
1402
1228
1582
1545
1080
908
1768
1630
1551
1327
1220
1135
997
938
761
579
415
105
700
519
105
38
15
5291598-LTG-B-1216
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION (Continued)
Model
Jumper Position
High Cool
Low Cool
60100
High Heat
Low Heat
High Cool
Low Cool
60125
High Heat
Low Heat
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
0.1
SCFM
2149
2013
1936
1719
1629
1558
1453
1410
1739
1558
1410
1323
1594
1323
1181
1025
2149
2013
1936
1719
1629
1558
1453
1410
2259
2093
1908
1760
2259
1965
1701
1683
0.2
SCFM
2114
1977
1900
1685
1591
1516
1406
1361
1705
1516
1361
1270
1553
1270
1118
950
2114
1977
1900
1685
1591
1516
1406
1361
2221
2059
1872
1726
2221
1929
1666
1648
0.3
SCFM
2077
1941
1864
1642
1546
1469
1355
1307
1664
1469
1307
1213
1507
1213
1049
868
2077
1941
1864
1642
1546
1469
1355
1307
2183
2023
1835
1685
2183
1893
1623
1604
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
2030
1989
1948
1905
1816
1772
1898
1860
1822
1783
1739
1695
1508
1465
1600
1555
1502
1455
1409
1362
1329
1280
1423
1375
1305
1255
1207
1153
1155
1100
1255
1204
1620
1577
1530
1487
1329
1280
1423
1375
1255
1204
1155
1100
1052
993
1156
1104
1462
1415
1369
1321
1052
993
1156
1104
980
913
857
795
654
591
788
713
2030
1989
1948
1905
1816
1772
1898
1860
1822
1783
1739
1695
1508
1465
1600
1555
1502
1455
1409
1362
1329
1280
1423
1375
1305
1255
1207
1153
1155
1100
1255
1204
2142
2099
2060
2015
1896
1852
1977
1938
1792
1753
1709
1665
1552
1510
1641
1598
2142
2099
2060
2015
1769
1724
1851
1813
1580
1535
1488
1445
1468
1424
1560
1515
0.8
SCFM
1859
1726
1649
1418
1315
1232
1100
1044
1441
1232
1044
933
1274
933
743
505
1859
1726
1649
1418
1315
1232
1100
1044
1975
1805
1619
1463
1975
1678
1397
1377
0.9
SCFM
1816
1677
1597
1372
1266
1181
1047
992
1393
1181
992
880
1223
880
696
458
1816
1677
1597
1372
1266
1181
1047
992
1931
1760
1566
1413
1931
1628
1351
1330
1.0
SCFM
1768
1630
1551
1327
1220
1135
997
938
1348
1135
938
821
1178
821
640
415
1768
1630
1551
1327
1220
1135
997
938
1882
1712
1522
1370
1882
1580
1305
1284
NOTES:
1.
2.
3.
4.
5.
6.
16
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
5291598-LTG-B-1216
ADDITIONAL STATIC RESISTANCE
Size (Tons)
036 (3.0)
042 (3.5)
048 (4.0)
060 (5.0)
CFM
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
Wet Indoor Coil Economizer1
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
BOTTOM DUCT DIMENSIONS (Inches)
Filter/Frame Kit
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
'
9,(:/22.,1*83
$7%277202)81,7
&
$
5(7851
$,5'8&7
(
%
$
6833/<
$,5'8&7
)
Model
36, 42, 48, 60
A
14
B
13.5
$
C
5
D
3.5
E
47.5
F
42
REAR DUCT DIMENSIONS (Inches)
NOTES:
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation. Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.
6833/<
$,5'8&7
5(7851
$,5'8&7
$
Model
36, 42, 48, 60
Johnson Controls Unitary Products
$
%
A
13.6
$
B
14
17
5291598-LTG-B-1216
UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A0324-001
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
TO GAS
SUPPLY LINE
18
CONTROL WIRING TO
INDOOR THERMOSTAT
A0325-001
Johnson Controls Unitary Products
5291598-LTG-B-1216
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO GAS
SUPPLY LINE
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT
Johnson Controls Unitary Products
SUPPLY
AIR DUCT
A0326-001
19
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2016 by Johnson Controls, Inc. All rights reserved.
York International Corp.
5005 York Drive
Norman, OK 73069
5291598-LTG-B-1216
Supersedes: 5291598-LTG-A-1016

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement