SERVICE MANUAL MUZ-HJ25VA - E1 MUZ-HJ35VA - E1


Add to my manuals
36 Pages

advertisement

SERVICE MANUAL MUZ-HJ25VA - E1 MUZ-HJ35VA - E1 | Manualzz

SPLIT-TYPE AIR CONDITIONERS

OUTDOOR UNIT

SERVICE MANUAL

Models

MUZ-HJ25VA

MUZ-HJ35VA

-

-

E1

E1

HFC

utilized

R410A

No. OBH648

Indoor unit service manual

MSZ-HJ•VA Series (OBH647)

MUZ-HJ25VA

MUZ-HJ35VA

NOTE:

RoHS compliant products have <G> mark on the spec name plate.

CONTENTS

1. TECHNICAL CHANGES ··································· 3

2. PART NAMES AND FUNCTIONS ····················· 3

3. SPECIFICATION ················································ 4

4. NOISE CRITERIA CURVES ······························ 5

5. OUTLINES AND DIMENSIONS ························ 6

6. WIRING DIAGRAM ············································ 7

7. REFRIGERANT SYSTEM DIAGRAM ··············· 8

8. PERFORMANCE CURVES ······························· 9

9. ACTUATOR CONTROL ··································· 18

10. SERVICE FUNCTIONS ···································· 19

11. TROUBLESHOOTING ····································· 19

12. DISASSEMBLY INSTRUCTIONS ···················· 33

PARTS CATALOG (OBB648)

Use the specifi ed refrigerant only

Never use any refrigerant other than that specified.

Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.

Correct refrigerant is specified in the manuals and on the spec labels provided with our products.

We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.

<Preparation before the repair service>

Prepare the proper tools.

Prepare the proper protectors.

Provide adequate ventilation.

After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug.

Discharge the capacitor before the work involving the electric parts.

<Precautions during the repair service>

Do not perform the work involving the electric parts with wet hands.

Do not pour water into the electric parts.

Do not touch the refrigerant.

Do not touch the hot or cold areas in the refrigeration cycle.

When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to

touch the live parts.

OBH648

2

1

TECHNICAL CHANGES

MUZ-HJ25VA -

E1

MUZ-HJ35VA -

E1

1. New model

2

PART NAMES AND FUNCTIONS

MUZ-HJ25VA MUZ-HJ35VA

Air inlet

(Back and side)

Piping

Drain hose

Air outlet

Drain outlet

ACCESSORIES

Drain socket 1

OBH648

3

3

SPECIFICATION

Outdoor model

MUZ-HJ25VA MUZ-HJ35VA

Capacity

Power supply

Cooling

Rated frequency (Min.-Max.)

Heating

Breaker Capacity

Power input 1 (Total)

Running current 1

(Total)

Cooling

Heating

Cooling kW

A

W

Power factor 1 (Total)

Cooling

Heating

%

Starting current 1 (Total) A

Coeffi cient of performance

(COP) 1 (Total)

Cooling

Heating

Model

Output

Compressor

Current 1

Cooling

Heating

Refrigeration oil (Model)

Model

Fan motor

Current 1

Dimensions W × H × D

Weight

Dehumidifi cation Cooling

W

A

L

A mm kg

/h

Air fl ow 1 m 3 /h

Sound level 1

Cooling

Heating dB(A) rpm Fan speed

Fan speed regulator

Refrigerant fi lling capacity (R410A) kg

NOTE: Test conditions are based on ISO 5151.

Cooling: Indoor Dry-bulb temperature 27°C

Outdoor Dry-bulb temperature 35°C

Heating: Indoor Dry-bulb temperature 20°C

Outdoor Dry-bulb temperature 7°C

Refrigerant piping length (one way): 5 m

1 Measured under rated operating frequency.

Specifi cations and rated conditions of main electric parts

Model

Item

Smoothing capacitor

Diode module

Fuse

Power module

Expansion valve coil

Reactor

Switching power transistor

Circuit protection

Terminal block

Relay

R.V. coil

(C61)

(DB61)

(DB65)

(F701, F801)

(IC700)

(LEV)

(L61)

(IC821)

(PTC64)

(TB)

(X61)

(X63)

(X64)

(21S4)

Single phase, 230 V, 50 Hz

2.5 (1.3 - 3.0) 3.15 (1.4 - 3.5)

3.15 (0.9 - 3.5) 3.6 (1.1 - 4.1)

10

730

870

3.7

1,040

995

4.9

4.8

85

90

4.2

3.42

3.62

KNB065FUJHC

500

3.3

3.8

92

90

4.9

3.03

3.62

KNB073FUVHC

550

4.4

4.4

0.32 (NEO22)

RA6V21-BD

0.23

699 × 538 × 249

24

0.4

1,890

50

50

840

1

0.70

25

0.6

1,890

50

50

840

1

0.72

Wet-bulb temperature 19°C

Wet-bulb temperature 6°C

MUZ-HJ25VA

8 A 600 V

800 μF 420 V

15 A 600 V

10 A 600 V

T3.15AL250V

12 VDC

18 mH

30 A 600 V

33 Ω

3 P

3 A 250 V

3 A 250 V

20 A 250 V

220 - 240 VAC

MUZ-HJ35VA

10 A 600 V

OBH648

4

4

NOISE CRITERIA CURVES

MUZ-HJ25VA MUZ-HJ35VA

FUNCTION SPL(dB(A))

COOLING

HEATING

50

50

LINE

90

80

70

NC-70

60

NC-60

50

NC-50

40

NC-40

30

20

10

NC-30

APPROXIMATE

THRESHOLD OF

HEARING FOR

CONTINUOUS

NOISE

63 125

NC-20

250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

FUNCTION SPL(dB(A))

COOLING 50

HEATING 50

LINE

90

80

70

NC-70

60

NC-60

50

NC-50

40

NC-40

30

20

10

NC-30

APPROXIMATE

THRESHOLD OF

HEARING FOR

CONTINUOUS

NOISE

63 125

NC-20

250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

Test conditions

Cooling : Dry-bulb temperature 35°C

Heating : Dry-bulb temperature 7°C Wet-bulb temperature 6°C

OUTDOOR UNIT

1m

MICROPHONE

OBH648

5

5

OUTLINES AND DIMENSIONS

MUZ-HJ25VA MUZ-HJ35VA

REQUIRED SPACE

Air in

Drain hole ø33

100 mm or more

100 mm or more

Air in

Unit : mm

100 mm or more

349.5

Air out

2 - 10.3 X 19.3 Oval hole

200 mm or more

350 mm or more

17.9

249

Liquid refrigerant pipe joint

Refrigerant pipe (flared) ø6.35

Gas refrigerant pipe joint

Refrigerant pipe (flared) ø9.52

40°

43°

121

259

500

699 55.7

121.4

OBH648

6

6

WIRING DIAGRAM

MUZ-HJ25VA

MUZ-HJ35VA

OBH648

7

7

REFRIGERANT SYSTEM DIAGRAM

MUZ-HJ25VA MUZ-HJ35VA

Refrigerant pipe ø9.52

(with heat insulator)

Flared connection

Muffler

(HJ35 only)

4-way valve

Stop valve

(with service port)

Discharge temperature thermistor

RT62

Muffler

Compressor

Outdoor heat exchanger

Defrost thermistor

RT61

Strainer

#100

Flared connection

Capillary tube

ø

3.0 ×

ø

1.4 × 260

Refrigerant pipe ø6.35

(with heat insulator)

Stop valve

(with strainer)

LEV

R.V. coil heating OFF cooling ON

Refrigerant flow in cooling

Refrigerant flow in heating

Unit : mm

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE

Refrigerant piping: m

Max. Length

A

Max. Height difference

B Gas

Piping size O.D: mm

Liquid

MUZ-HJ25VA

MUZ-HJ35VA

20 12 9.52

6.35

Indoor unit

Max. Height difference

B

Max. Length

A

Outdoor unit

ADDITIONAL REFRIGERANT CHARGE (R410A : g)

Model

MUZ-HJ25VA

MUZ-HJ35VA

Outdoor unit precharged

700

720

Refrigerant piping length (one way)

5 m 6 m 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m

0 0 0 20 40 60 80 100 120 140 160 260

Calculation: X g = 20 g/m (Refrigerant piping length (m) - 7)

NOTE : Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.

OBH648

8

8 PERFORMANCE CURVES

MUZ-HJ25VA MUZ-HJ35VA

The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.

(1) GUARANTEED VOLTAGE

198 ~ 264 V, 50 Hz

(2) AIR FLOW

Air flow should be set at MAX.

(3) MAIN READINGS

(1) Indoor intake air wet-bulb temperature :

(2) Indoor outlet air wet-bulb temperature :

(3) Outdoor intake air dry-bulb temperature :

(4) Total input:

(5) Indoor intake air dry-bulb temperature :

°C WB

°C WB

°C DB

W

°C DB

}

Cooling

(6) Outdoor intake air wet-bulb temperature :

(7) Total input :

}

Heating

Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.

°C WB

W

How to measure the indoor air wet and dry bulb temperature difference

1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.

2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.

Cover the thermometers to prevent direct rays of the sun.

3. Check that the air filter is cleaned.

4. Open windows and doors of room.

5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.

6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.

7. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT OUTDOOR UNIT

Wet and dry bulb thermometers

FRONT VIEW

Wet and dry bulb thermometers

BACK VIEW

OBH648

9

8-1. CAPACITY AND INPUT CURVES

5.6

5.1

4.6

4.1

7.2

6.7

6.1

5.6

5.1

4.5

8.0

7.4

6.8

6.2

Cooling capacity

1.5

1.4

1.3

1.2

1.1

1.0

0.9

Indoor intake air W et-bulb temperat ure (°C)

26

24

18 20 25 30 35

Outdoor intake air Dry-bulb temperature (°C)

40 45 46

22

20

18

6.1

5.6

5.1

4.6

4.1

3.6

6.8

6.2

5.6

5.1

4.5

4.0

1.3

1.2

1.1

Total input (cooling)

26

24

1.0

0.9

0.8

18 20 25

Indoor

intake air W et-bulb temperature (°C)

30 35

Outdoor intake air Dry-bulb temperature (°C)

40 45 46

22

20

18

20.6

19.0

17.4

15.8

14.3

12.7

11.1

9.5

22.9

21.1

19.3

17.6

15.8

14.1

12.3

10.5

Indoor intake ai r Drybulb temperature (°C)

Indoor

intake air Drybulb temperat ure (°C)

Outdoor intake air Wet-bulb temperature (°C)

Outdoor intake air Wet-bulb temperature (°C)

NOTE: The above broken lines are for the heating operation without any frost and

defrost operation.

OBH648

10

8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR

MUZ-HJ25VA

1.5

Correction of Cooling capacity

1.5

Correction of Cooling total input

1.5

Correction of Heating capacity

1.5

Correction of Heating total input

1.0

0.5

1.0

0.5

1.0

0.5

1.0

0.5

0 50 100

150 (Hz)

0 50 100

150 (Hz)

0 50 100

150 (Hz)

0 50 100

150 (Hz)

The operational frequency of compressor

The operational frequency of compressor The operational frequency of compressor

The operational frequency of compressor

1.0

0.5

MUZ-HJ35VA

1.5

Correction of Cooling capacity

1.5

Correction of Cooling total input

1.5

Correction of Heating capacity

1.5

Correction of Heating total input

1.0

0.5

1.0

0.5

1.0

0.5

0 50 100

150 (Hz)

0 50 100

150 (Hz)

0 50 100

150 (Hz)

0 50 100

150 (Hz)

The operational frequency of compressor

The operational frequency of compressor The operational frequency of compressor

The operational frequency of compressor

8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION

<Test run operation>

1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).

2. Test run operation starts and continues to operate for 30 minutes.

3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.

4. Indoor fan operates at High speed.

5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).

6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.

OBH648

11

8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT

COOL operation

Both indoor and outdoor unit are under the same temperature/humidity condition.

Operation: TEST RUN OPERATION (Refer to 8-3.)

Outdoor low pressure

MUZ-HJ25VA

(kgf/cm

2

[Gauge])(MPa [Gauge])

9

0.9

MUZ-HJ35VA

(kgf/cm

2

[Gauge])(MPa [Gauge])

8

0.8

Dry-bulb temperature (°C) Relative humidity (%)

20 50

25

30

60

70

8

0.8

7

0.7

7

0.7

6

0.6

6

0.6

5

0.5

5

0.5

4

0.4

4 0.4

15 18 20

50

25

60

30

70

32

Ambient temperature(°C)

Ambient humidity(%)

35

(°C)

(%)

3 0.3

15 18 20

50

25

60

30

70

32

Ambient temperature(°C)

Ambient humidity(%)

35

(°C)

(%)

NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).

The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm

2

[Gauge])

Outdoor unit current

MUZ-HJ25VA

5 6

MUZ-HJ35VA

4

3

5

4

2

15

18

20

50

25

60

30

70

32

Ambient temperature (°C)

Ambient humidity(%)

35

(°C)

(%)

HEAT operation

Condition:

Indoor

Dry bulb temperature (°C) 20.0

Wet bulb temperature (°C) 14.5

Operation: Test run operation (refer to 8-3.)

3

15

18

20

50

25

60

30

70

32

Ambient temperature (°C)

Ambient humidity(%)

35

(°C)

(%)

2

1

Outdoor

7 15 20.0

6 12 14.5

Outdoor unit current

3.0

MUZ-HJ25VA

3.0

MUZ-HJ35VA

2.5

2.0

1.5

0 5 10 15 20

Ambient temperature (°C)

25

OBH648

2.5

2.0

1.5

0 5 10 15 20

Ambient temperature (°C)

25

12

PERFORMANCE DATA COOL operation a t Rated frequency

MUZ-HJ25VA

CAPACITY: 2.5 kW SHF: 0.89 INPUT: 730 W

INDOOR

DB (°C)

INDOOR

WB (°C)

22

24

26

18

20

22

24

26

18

20

26

18

20

22

22

24

26

24

26

18

20

24

26

18

20

22

24

26

18

20

22

18

20

22

24

18

20

22

24

18

20

22

24

20

22

18

20

18

20

22

18

30

30

30

31

31

31

29

29

30

30

28

29

29

29

32

32

32

31

31

32

32

27

27

28

28

28

28

26

27

27

27

26

26

26

26

21

21

24

24

25

25

25

25

23

23

24

24

22

22

22

23

3.35

1.98

0.59

3.45

1.62

0.47

2.94

2.91

0.99

3.06

2.66

0.87

3.19

2.39

0.75

3.35

2.11

0.63

3.45

1.76

0.51

2.94

2.94

1.00

3.06

2.79

0.91

3.19

2.52

0.79

3.35

2.24

0.67

3.45

1.90

0.55

2.94

2.94

1.00

3.06

2.91

0.95

3.19

2.65

0.83

3.35

2.38

0.71

3.45

2.04

0.59

2.94

2.94

1.00

3.06

3.03

0.99

3.19

2.77

0.87

3.35

2.51

0.75

3.45

2.17

0.63

2.94

2.94

1.00

3.06

3.06

1.00

3.19

2.90

0.91

3.35

2.65

0.79

3.45

2.31

0.67

OUTDOOR DB (°C)

21 25 27 30

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

2.94

2.09

0.71

3.06

1.81

0.59

584

613

2.81

2.94

2.00

1.73

0.71

0.59

613

650

2.70

2.85

1.92

1.68

0.71

0.59

642

664

2.60

2.75

1.85

1.62

0.71

0.59

672

694

2.94

2.20

0.75

3.06

1.93

0.63

3.19

1.63

0.51

2.94

2.32

0.79

584

613

635

584

2.81

2.94

3.08

2.81

2.11

1.85

1.57

2.22

0.75

0.63

0.51

0.79

613

650

675

613

2.70

2.85

3.00

2.70

2.03

1.80

1.53

2.13

0.75

0.63

0.51

0.79

642

664

694

642

2.60

2.75

2.88

2.60

1.95

1.73

1.47

2.05

0.75

0.63

0.51

0.79

672

694

723

672

3.06

2.05

0.67

3.19

1.75

0.55

2.94

2.44

0.83

3.06

2.17

0.71

613 2.94

1.97

0.67

650 2.85

1.91

0.67

664 2.75

1.84

0.67

694

635 3.08

1.69

0.55

675 3.00

1.65

0.55

694 2.88

1.58

0.55

723

584 2.81

2.33

0.83

613 2.70

2.24

0.83

642 2.60

2.16

0.83

672

613 2.94

2.09

0.71

650 2.85

2.02

0.71

664 2.75

1.95

0.71

694

3.19

1.88

0.59

3.35

1.57

0.47

2.94

2.56

0.87

3.06

2.30

0.75

3.19

2.01

0.63

3.35

1.71

0.51

2.94

2.67

0.91

3.06

2.42

0.79

3.19

2.14

0.67

3.35

1.84

0.55

3.45

1.48

0.43

2.94

2.79

0.95

3.06

2.54

0.83

3.19

2.26

0.71

635

664

584

613

635

664

584

613

635

664

701

584

613

635

3.08

3.23

2.81

2.94

3.08

3.23

2.81

2.94

3.08

3.23

3.35

2.81

2.94

3.08

1.81

1.52

2.45

2.20

1.94

1.64

2.56

2.32

2.06

1.77

1.44

2.67

2.44

2.18

0.59

0.47

0.87

0.75

0.63

0.51

0.91

0.79

0.67

0.55

0.43

0.95

0.83

0.71

675

701

613

650

675

701

613

650

675

701

737

613

650

675

3.00

3.15

2.70

2.85

3.00

3.15

2.70

2.85

3.00

3.15

3.30

2.70

2.85

3.00

1.77

1.48

2.35

2.14

1.89

1.61

2.46

2.25

2.01

1.73

1.42

2.57

2.37

2.13

0.59

0.47

0.87

0.75

0.63

0.51

0.91

0.79

0.67

0.55

0.43

0.95

0.83

0.71

694

723

642

664

694

723

642

664

694

723

759

642

664

694

2.88

3.05

2.60

2.75

2.88

3.05

2.60

2.75

2.88

3.05

3.20

2.60

2.75

2.88

1.70

1.43

2.26

2.06

1.81

1.56

2.37

2.17

1.93

1.68

1.38

2.47

2.28

2.04

0.59

0.47

0.87

0.75

0.63

0.51

0.91

0.79

0.67

0.55

0.43

0.95

0.83

0.71

723

759

672

694

723

759

672

694

723

759

781

672

694

723

664 3.23

1.90

0.59

701 3.15

1.86

0.59

723 3.05

1.80

0.59

759

701 3.35

1.57

0.47

737 3.30

1.55

0.47

759 3.20

1.50

0.47

781

584 2.81

2.78

0.99

613 2.70

2.67

0.99

642 2.60

2.57

0.99

672

613 2.94

2.56

0.87

650 2.85

2.48

0.87

664 2.75

2.39

0.87

694

635 3.08

2.31

0.75

675 3.00

2.25

0.75

694 2.88

2.16

0.75

723

664 3.23

2.03

0.63

701 3.15

1.98

0.63

723 3.05

1.92

0.63

759

701 3.35

1.71

0.51

737 3.30

1.68

0.51

759 3.20

1.63

0.51

781

584 2.81

2.81

1.00

613 2.70

2.70

1.00

642 2.60

2.60

1.00

672

613 2.94

2.67

0.91

650 2.85

2.59

0.91

664 2.75

2.50

0.91

694

635 3.08

2.43

0.79

675 3.00

2.37

0.79

694 2.88

2.27

0.79

723

664 3.23

2.16

0.67

701 3.15

2.11

0.67

723 3.05

2.04

0.67

759

701 3.35

1.84

0.55

737 3.30

1.82

0.55

759 3.20

1.76

0.55

781

584

613

584

613

635

664

701

2.81

2.94

635 3.08

2.55

0.83

675 3.00

2.49

0.83

694 2.88

2.39

0.83

723

664 3.23

2.29

0.71

701 3.15

2.24

0.71

723 3.05

2.17

0.71

759

701 3.35

1.98

0.59

737 3.30

1.95

0.59

759 3.20

1.89

0.59

781

584 2.81

2.81

1.00

613 2.70

2.70

1.00

642 2.60

2.60

1.00

672

613 2.94

2.91

0.99

650 2.85

2.82

0.99

664 2.75

2.72

0.99

694

635 3.08

2.68

0.87

675 3.00

2.61

0.87

694 2.88

2.50

0.87

723

664 3.23

2.42

0.75

701 3.15

2.36

0.75

723 3.05

2.29

0.75

759

701 3.35

2.11

0.63

737 3.30

2.08

0.63

759 3.20

2.02

0.63

781

2.81

2.94

3.08

3.23

3.35

2.81

2.79

2.81

2.94

2.80

2.55

2.24

1.00

0.95

1.00

1.00

0.91

0.79

0.67

613

650

613

650

675

701

737

2.70

2.85

2.70

2.85

3.00

3.15

3.30

2.70

2.71

2.70

2.85

2.73

2.49

2.21

1.00

0.95

1.00

1.00

0.91

0.79

0.67

642

664

642

664

694

723

759

2.60

2.75

2.60

2.75

2.88

3.05

3.20

2.60

2.61

2.60

2.75

2.62

2.41

2.14

1.00

0.95

1.00

1.00

0.91

0.79

0.67

672

694

672

694

723

759

781

NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

OBH648

13

PERFORMANCE DATA COOL operation a t Rated frequency

MUZ-HJ25VA

CAPACITY: 2.5 kW SHF: 0.89 INPUT: 730 W

INDOOR

DB (°C)

INDOOR

WB (°C)

24

26

18

20

26

18

20

22

22

24

26

24

26

18

20

22

24

26

18

20

22

18

20

22

24

26

18

20

22

24

26

18

20

22

24

18

20

22

24

22

18

20

22

18

20

18

20

18

20

22

24

31

31

32

32

30

31

31

31

32

32

32

29

29

30

30

30

30

28

29

29

29

28

28

28

28

26

27

27

27

27

27

26

26

26

26

25

25

25

25

22

23

23

23

21

21

22

22

24

24

24

24

OUTDOOR DB (°C)

35 40 46

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

2.45

1.74

0.71

715 2.25

1.60

0.71

759 2.08

1.47

0.71

788

2.58

1.52

0.59

745 2.40

1.42

0.59

781 2.23

1.31

0.59

825

2.45

1.84

0.75

715 2.25

1.69

0.75

759 2.08

1.56

0.75

788

2.58

1.62

0.63

745 2.40

1.51

0.63

781 2.23

1.40

0.63

825

2.73

1.39

0.51

774 2.55

1.30

0.51

818 2.38

1.21

0.51

847

2.45

1.94

0.79

715 2.25

1.78

0.79

759 2.08

1.64

0.79

788

2.58

1.73

0.67

745 2.40

1.61

0.67

781 2.23

1.49

0.67

825

2.73

1.50

0.55

774 2.55

1.40

0.55

818 2.38

1.31

0.55

847

2.45

2.03

0.83

715 2.25

1.87

0.83

759 2.08

1.72

0.83

788

2.58

1.83

0.71

745 2.40

1.70

0.71

781 2.23

1.58

0.71

825

2.73

1.61

0.59

774 2.55

1.50

0.59

818 2.38

1.40

0.59

847

2.88

1.35

0.47

803 2.70

1.27

0.47

839 2.55

1.20

0.47

876

2.45

2.13

0.87

715 2.25

1.96

0.87

759 2.08

1.81

0.87

788

2.58

1.93

0.75

745 2.40

1.80

0.75

781 2.23

1.67

0.75

825

2.73

1.72

0.63

774 2.55

1.61

0.63

818 2.38

1.50

0.63

847

2.88

1.47

0.51

803 2.70

1.38

0.51

839 2.55

1.30

0.51

876

2.45

2.23

0.91

715 2.25

2.05

0.91

759 2.08

1.89

0.91

788

2.58

2.03

0.79

745 2.40

1.90

0.79

781 2.23

1.76

0.79

825

2.73

1.83

0.67

774 2.55

1.71

0.67

818 2.38

1.59

0.67

847

2.88

1.58

0.55

803 2.70

1.49

0.55

839 2.55

1.40

0.55

876

3.03

1.30

0.43

832 2.85

1.23

0.43

869 2.68

1.15

0.43

905

2.45

2.33

0.95

715 2.25

2.14

0.95

759 2.08

1.97

0.95

788

2.58

2.14

0.83

745 2.40

1.99

0.83

781 2.23

1.85

0.83

825

2.73

1.93

0.71

774 2.55

1.81

0.71

818 2.38

1.69

0.71

847

2.88

1.70

0.59

803 2.70

1.59

0.59

839 2.55

1.50

0.59

876

3.03

1.42

0.47

832 2.85

1.34

0.47

869 2.68

1.26

0.47

905

2.45

2.43

0.99

715 2.25

2.23

0.99

759 2.08

2.05

0.99

788

2.58

2.24

0.87

745 2.40

2.09

0.87

781 2.23

1.94

0.87

825

2.73

2.04

0.75

774 2.55

1.91

0.75

818 2.38

1.78

0.75

847

2.88

1.81

0.63

803 2.70

1.70

0.63

839 2.55

1.61

0.63

876

3.03

1.54

0.51

832 2.85

1.45

0.51

869 2.68

1.36

0.51

905

2.45

2.45

1.00

715 2.25

2.25

1.00

759 2.08

2.08

1.00

788

2.58

2.34

0.91

745 2.40

2.18

0.91

781 2.23

2.02

0.91

825

2.73

2.15

0.79

774 2.55

2.01

0.79

818 2.38

1.88

0.79

847

2.88

1.93

0.67

803 2.70

1.81

0.67

839 2.55

1.71

0.67

876

3.03

1.66

0.55

832 2.85

1.57

0.55

869 2.68

1.47

0.55

905

2.45

2.45

1.00

715 2.25

2.25

1.00

759 2.08

2.08

1.00

788

2.58

2.45

0.95

745 2.40

2.28

0.95

781 2.23

2.11

0.95

825

2.73

2.26

0.83

774 2.55

2.12

0.83

818 2.38

1.97

0.83

847

2.88

2.04

0.71

803 2.70

1.92

0.71

839 2.55

1.81

0.71

876

3.03

1.78

0.59

832 2.85

1.68

0.59

869 2.68

1.58

0.59

905

2.45

2.45

1.00

715 2.25

2.25

1.00

759 2.08

2.08

1.00

788

2.58

2.55

0.99

745 2.40

2.38

0.99

781 2.23

2.20

0.99

825

2.73

2.37

0.87

774 2.55

2.22

0.87

818 2.38

2.07

0.87

847

2.88

2.16

0.75

803 2.70

2.03

0.75

839 2.55

1.91

0.75

876

3.03

1.91

0.63

832 2.85

1.80

0.63

869 2.68

1.69

0.63

905

2.45

2.45

1.00

715 2.25

2.25

1.00

759 2.08

2.08

1.00

788

2.58

2.58

1.00

745 2.40

2.40

1.00

781 2.23

2.23

1.00

825

2.73

2.48

0.91

774 2.55

2.32

0.91

818 2.38

2.16

0.91

847

2.88

2.27

0.79

803 2.70

2.13

0.79

839 2.55

2.01

0.79

876

3.03

2.03

0.67

832 2.85

1.91

0.67

869 2.68

1.79

0.67

905

NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

OBH648

14

PERFORMANCE DATA COOL operation a t Rated frequency

MUZ-HJ35VA

CAPACITY: 3.15 kW SHF: 0.87 INPUT: 1040 W

INDOOR

DB (°C)

INDOOR

WB (°C)

24

26

18

20

26

18

20

22

22

24

26

24

26

18

20

22

24

26

18

20

22

18

20

22

24

26

18

20

22

24

26

18

20

22

24

18

20

22

24

22

18

20

22

18

20

18

20

18

20

22

24

31

31

32

32

30

31

31

31

32

32

32

29

29

30

30

30

30

28

29

29

29

28

28

28

28

26

27

27

27

27

27

26

26

26

26

25

25

25

25

22

23

23

23

21

21

22

22

24

24

24

24

OUTDOOR DB (°C)

21 25 27 30

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

3.70

2.55

0.69

832 3.54

2.45

0.69

874 3.40

2.35

0.69

915 3.28

2.26

0.69

957

3.86

2.20

0.57

874 3.70

2.11

0.57

926 3.59

2.05

0.57

3.70

2.70

0.73

832 3.54

2.59

0.73

874 3.40

2.48

0.73

3.86

2.35

0.61

874 3.70

2.26

0.61

926 3.59

2.19

0.61

4.02

1.97

0.49

905 3.87

1.90

0.49

962 3.78

1.85

0.49

3.70

2.85

0.77

832 3.54

2.73

0.77

874 3.40

2.62

0.77

946

915

946

988

915

3.47

3.28

3.47

3.62

3.28

1.98

2.39

2.11

1.78

2.52

0.57

0.73

0.61

0.49

0.77

988

957

988

1030

957

3.86

2.51

0.65

874 3.70

2.41

0.65

926 3.59

2.33

0.65

4.02

2.13

0.53

905 3.87

2.05

0.53

962 3.78

2.00

0.53

3.70

3.00

0.81

832 3.54

2.87

0.81

874 3.40

2.76

0.81

3.86

2.66

0.69

874 3.70

2.55

0.69

926 3.59

2.48

0.69

946 3.47

2.25

0.65

988

988 3.62

1.92

0.53

1030

915 3.28

2.65

0.81

957

946 3.47

2.39

0.69

988

4.02

2.29

0.57

905 3.87

2.21

0.57

962 3.78

2.15

0.57

988 3.62

2.06

0.57

1030

4.22

1.90

0.45

946 4.06

1.83

0.45

998 3.97

1.79

0.45

1030 3.84

1.73

0.45

1082

3.70

3.15

0.85

832 3.54

3.01

0.85

874 3.40

2.89

0.85

3.86

2.82

0.73

874 3.70

2.70

0.73

926 3.59

2.62

0.73

915

946

3.28

3.47

2.78

2.53

0.85

0.73

957

988

4.02

2.45

0.61

905 3.87

2.36

0.61

962 3.78

2.31

0.61

988 3.62

2.21

0.61

1030

4.22

2.07

0.49

946 4.06

1.99

0.49

998 3.97

1.94

0.49

1030 3.84

1.88

0.49

1082

3.70

3.29

0.89

832 3.54

3.15

0.89

874 3.40

3.03

0.89

3.86

2.97

0.77

874 3.70

2.85

0.77

926 3.59

2.77

0.77

915

946

3.28

3.47

2.92

2.67

0.89

0.77

957

988

4.02

2.61

0.65

905 3.87

2.52

0.65

962 3.78

2.46

0.65

988 3.62

2.35

0.65

1030

4.22

2.24

0.53

946 4.06

2.15

0.53

998 3.97

2.10

0.53

1030 3.84

2.04

0.53

1082

4.35

1.78

0.41

998 4.22

1.73

0.41

1050 4.16

1.70

0.41

1082 4.03

1.65

0.41

1113

3.70

3.44

0.93

832 3.54

3.30

0.93

874 3.40

3.16

0.93

3.86

3.13

0.81

874 3.70

3.00

0.81

926 3.59

2.91

0.81

915 3.28

3.05

0.93

957

946 3.47

2.81

0.81

988

4.02

2.77

0.69

905 3.87

2.67

0.69

962 3.78

2.61

0.69

988 3.62

2.50

0.69

1030

4.22

2.41

0.57

946 4.06

2.32

0.57

998 3.97

2.26

0.57

1030 3.84

2.19

0.57

1082

4.35

1.96

0.45

998 4.22

1.90

0.45

1050 4.16

1.87

0.45

1082 4.03

1.81

0.45

1113

3.70

3.59

0.97

832 3.54

3.44

0.97

874 3.40

3.30

0.97

915 3.28

3.18

0.97

957

3.86

3.28

0.85

874 3.70

3.15

0.85

926 3.59

3.05

0.85

4.02

2.93

0.73

905 3.87

2.83

0.73

962 3.78

2.76

0.73

946

988

3.47

3.62

2.95

2.64

0.85

0.73

988

1030

4.22

2.57

0.61

946 4.06

2.48

0.61

998 3.97

2.42

0.61

1030 3.84

2.34

0.61

1082

4.35

2.13

0.49

998 4.22

2.07

0.49

1050 4.16

2.04

0.49

1082 4.03

1.98

0.49

1113

3.70

3.70

1.00

832 3.54

3.54

1.00

874 3.40

3.40

1.00

3.86

3.43

0.89

874 3.70

3.29

0.89

926 3.59

3.20

0.89

915

946

3.28

3.47

3.28

3.08

1.00

0.89

957

988

4.02

3.09

0.77

905 3.87

2.98

0.77

962 3.78

2.91

0.77

988 3.62

2.79

0.77

1030

4.22

2.74

0.65

946 4.06

2.64

0.65

998 3.97

2.58

0.65

1030 3.84

2.50

0.65

1082

4.35

2.30

0.53

998 4.22

2.24

0.53

1050 4.16

2.20

0.53

1082 4.03

2.14

0.53

1113

3.70

3.70

1.00

832 3.54

3.54

1.00

874 3.40

3.40

1.00

915 3.28

3.28

1.00

957

3.86

3.59

0.93

874 3.70

3.44

0.93

926 3.59

3.34

0.93

4.02

3.25

0.81

905 3.87

3.14

0.81

962 3.78

3.06

0.81

946

988

3.47

3.62

3.22

2.93

0.93

0.81

988

1030

4.22

2.91

0.69

946 4.06

2.80

0.69

998 3.97

2.74

0.69

1030 3.84

2.65

0.69

1082

4.35

2.48

0.57

998 4.22

2.41

0.57

1050 4.16

2.37

0.57

1082 4.03

2.30

0.57

1113

3.70

3.70

1.00

832 3.54

3.54

1.00

874 3.40

3.40

1.00

3.86

3.74

0.97

874 3.70

3.59

0.97

926 3.59

3.48

0.97

915

946

3.28

3.47

3.28

3.36

1.00

0.97

957

988

4.02

3.41

0.85

905 3.87

3.29

0.85

962 3.78

3.21

0.85

988 3.62

3.08

0.85

1030

4.22

3.08

0.73

946 4.06

2.97

0.73

998 3.97

2.90

0.73

1030 3.84

2.81

0.73

1082

4.35

2.65

0.61

998 4.22

2.57

0.61

1050 4.16

2.54

0.61

1082 4.03

2.46

0.61

1113

3.70

3.70

1.00

832 3.54

3.54

1.00

874 3.40

3.40

1.00

915 3.28

3.28

1.00

957

3.86

3.86

1.00

874 3.70

3.70

1.00

926 3.59

3.59

1.00

4.02

3.57

0.89

905 3.87

3.45

0.89

962 3.78

3.36

0.89

946 3.47

3.47

1.00

988

988 3.62

3.22

0.89

1030

4.22

3.25

0.77

946 4.06

3.13

0.77

998 3.97

3.06

0.77

1030 3.84

2.96

0.77

1082

4.35

2.83

0.65

998 4.22

2.74

0.65

1050 4.16

2.70

0.65

1082 4.03

2.62

0.65

1113

NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

OBH648

15

PERFORMANCE DATA COOL operation a t Rated frequency

MUZ-HJ35VA

CAPACITY: 3.15 kW SHF: 0.87 INPUT: 1040 W

INDOOR

DB (°C)

INDOOR

WB (°C)

24

26

18

20

26

18

20

22

22

24

26

24

26

18

20

22

24

26

18

20

22

18

20

22

24

26

18

20

22

24

26

18

20

22

24

18

20

22

24

22

18

20

22

18

20

18

20

18

20

22

24

31

31

32

32

30

31

31

31

32

32

32

29

29

30

30

30

30

28

29

29

29

28

28

28

28

26

27

27

27

27

27

26

26

26

26

25

25

25

25

22

23

23

23

21

21

22

22

24

24

24

24

OUTDOOR DB (°C)

35 40 46

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

3.09

2.13

0.69

1019 2.84

1.96

0.69

1082 2.61

1.80

0.69

1123

3.24

1.85

0.57

1061 3.02

1.72

0.57

1113 2.80

1.60

0.57

1175

3.09

2.25

0.73

1019 2.84

2.07

0.73

1082 2.61

1.91

0.73

1123

3.24

1.98

0.61

1061 3.02

1.84

0.61

1113 2.80

1.71

0.61

1175

3.43

1.68

0.49

1102 3.21

1.57

0.49

1165 2.99

1.47

0.49

1206

3.09

2.38

0.77

1019 2.84

2.18

0.77

1082 2.61

2.01

0.77

1123

3.24

2.11

0.65

1061 3.02

1.97

0.65

1113 2.80

1.82

0.65

1175

3.43

1.82

0.53

1102 3.21

1.70

0.53

1165 2.99

1.59

0.53

1206

3.09

2.50

0.81

1019 2.84

2.30

0.81

1082 2.61

2.12

0.81

1123

3.24

2.24

0.69

1061 3.02

2.09

0.69

1113 2.80

1.93

0.69

1175

3.43

1.96

0.57

1102 3.21

1.83

0.57

1165 2.99

1.71

0.57

1206

3.62

1.63

0.45

1144 3.40

1.53

0.45

1196 3.21

1.45

0.45

1248

3.09

2.62

0.85

1019 2.84

2.41

0.85

1082 2.61

2.22

0.85

1123

3.24

2.37

0.73

1061 3.02

2.21

0.73

1113 2.80

2.05

0.73

1175

3.43

2.09

0.61

1102 3.21

1.96

0.61

1165 2.99

1.83

0.61

1206

3.62

1.78

0.49

1144 3.40

1.67

0.49

1196 3.21

1.57

0.49

1248

3.09

2.75

0.89

1019 2.84

2.52

0.89

1082 2.61

2.33

0.89

1123

3.24

2.50

0.77

1061 3.02

2.33

0.77

1113 2.80

2.16

0.77

1175

3.43

2.23

0.65

1102 3.21

2.09

0.65

1165 2.99

1.95

0.65

1206

3.62

1.92

0.53

1144 3.40

1.80

0.53

1196 3.21

1.70

0.53

1248

3.81

1.56

0.41

1186 3.59

1.47

0.41

1238 3.37

1.38

0.41

1290

3.09

2.87

0.93

1019 2.84

2.64

0.93

1082 2.61

2.43

0.93

1123

3.24

2.63

0.81

1061 3.02

2.45

0.81

1113 2.80

2.27

0.81

1175

3.43

2.37

0.69

1102 3.21

2.22

0.69

1165 2.99

2.06

0.69

1206

3.62

2.06

0.57

1144 3.40

1.94

0.57

1196 3.21

1.83

0.57

1248

3.81

1.72

0.45

1186 3.59

1.62

0.45

1238 3.37

1.52

0.45

1290

3.09

2.99

0.97

1019 2.84

2.75

0.97

1082 2.61

2.54

0.97

1123

3.24

2.76

0.85

1061 3.02

2.57

0.85

1113 2.80

2.38

0.85

1175

3.43

2.51

0.73

1102 3.21

2.35

0.73

1165 2.99

2.18

0.73

1206

3.62

2.21

0.61

1144 3.40

2.08

0.61

1196 3.21

1.96

0.61

1248

3.81

1.87

0.49

1186 3.59

1.76

0.49

1238 3.37

1.65

0.49

1290

3.09

3.09

1.00

1019 2.84

2.84

1.00

1082 2.61

2.61

1.00

1123

3.24

2.89

0.89

1061 3.02

2.69

0.89

1113 2.80

2.50

0.89

1175

3.43

2.64

0.77

1102 3.21

2.47

0.77

1165 2.99

2.30

0.77

1206

3.62

2.35

0.65

1144 3.40

2.21

0.65

1196 3.21

2.09

0.65

1248

3.81

2.02

0.53

1186 3.59

1.90

0.53

1238 3.37

1.79

0.53

1290

3.09

3.09

1.00

1019 2.84

2.84

1.00

1082 2.61

2.61

1.00

1123

3.24

3.02

0.93

1061 3.02

2.81

0.93

1113 2.80

2.61

0.93

1175

3.43

2.78

0.81

1102 3.21

2.60

0.81

1165 2.99

2.42

0.81

1206

3.62

2.50

0.69

1144 3.40

2.35

0.69

1196 3.21

2.22

0.69

1248

3.81

2.17

0.57

1186 3.59

2.05

0.57

1238 3.37

1.92

0.57

1290

3.09

3.09

1.00

1019 2.84

2.84

1.00

1082 2.61

2.61

1.00

1123

3.24

3.15

0.97

1061 3.02

2.93

0.97

1113 2.80

2.72

0.97

1175

3.43

2.92

0.85

1102 3.21

2.73

0.85

1165 2.99

2.54

0.85

1206

3.62

2.64

0.73

1144 3.40

2.48

0.73

1196 3.21

2.35

0.73

1248

3.81

2.33

0.61

1186 3.59

2.19

0.61

1238 3.37

2.06

0.61

1290

3.09

3.09

1.00

1019 2.84

2.84

1.00

1082 2.61

2.61

1.00

1123

3.24

3.24

1.00

1061 3.02

3.02

1.00

1113 2.80

2.80

1.00

1175

3.43

3.06

0.89

1102 3.21

2.86

0.89

1165 2.99

2.66

0.89

1206

3.62

2.79

0.77

1144 3.40

2.62

0.77

1196 3.21

2.47

0.77

1248

3.81

2.48

0.65

1186 3.59

2.33

0.65

1238 3.37

2.19

0.65

1290

NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

OBH648

16

PERFORMANCE DATA HEAT operation at Rated frequency

MUZ-HJ25VA

CAPACITY: 3.15 kW INPUT: 870 W

INDOOR

DB (°C)

15

21

26

Q

1.98

1.89

1.70

-10

INPUT

566

609

653

Q

2.39

2.27

2.11

-5

INPUT

679

722

766

Q

2.80

2.68

2.49

0

INPUT

OUTDOOR WB (°C)

5

Q INPUT

766 3.21

827

Q

3.62

800

844

3.06

2.90

861

905

3.47

3.31

10

INPUT

879

905

948

Q

4.00

3.84

3.69

15

INPUT

905

931

974

Q

4.41

4.24

20

INPUT

922

966

4.10

1001

MUZ-HJ35VA

CAPACITY: 3.6 kW INPUT: 995 W

INDOOR

DB (°C)

15

21

26

Q

2.27

2.16

1.94

-10

INPUT

647

697

746

Q

2.74

2.59

2.41

-5

INPUT

776

826

876

Q

3.20

3.06

2.84

0

INPUT

OUTDOOR WB (°C)

5

Q INPUT

876 3.67

945

Q

4.14

915

965

3.49

3.31

985

1035

3.96

3.78

10

INPUT Q

15

INPUT

1005 4.57

1035

1035 4.39

1065

1085 4.21

1114

Q

20

INPUT

5.04

1055

4.84

1104

4.68

1144

NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature

OBH648

17

9

ACTUATOR CONTROL

MUZ-HJ25VA MUZ-HJ35VA

9-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

5 seconds 15 seconds

ON

Compressor

OFF

ON

Outdoor fan motor

OFF

9-2. R.V. COIL CONTROL

Heating . . . . . . . . . . . . . . . . . OFF

Cooling . . . . . . . . . . . . . . . . . ON

Dry . . . . . . . . . . . . . . . . . . . . ON

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

<COOL> <HEAT>

5 seconds 5 seconds

Compressor

ON

OFF

R.V.coil

ON

OFF

Outdoor fan motor

ON

OFF

9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

Sensor

Discharge temperature thermistor

Indoor coil temperature thermistor

Defrost thermistor

Fin temperature thermistor

Purpose

Protection

Cooling: Coil frost prevention

Heating: High pressure protection

Cooling: High pressure protection

Heating: Defrosting

Protection

Compressor LEV

○ ○

Actuator

Outdoor fan motor

R.V. coil

Indoor fan motor

○ ○

○ ○

○ ○

OBH648

18

10

SERVICE FUNCTIONS

MUZ-HJ25VA MUZ-HJ35VA

10-1. CHANGE IN DEFROST SETTING

<JS> When the JS wire of the inverter P.C. board is cut/ soldered, the defrost finish temperature is changed. (Refer to

11-6-1.)

JS

Jumper wire

Soldered

(Initial setting)

None

(Cut)

Defrost fi nish temperature (°C)

8

11

10-2. PRE-HEAT CONTROL SETTING

PRE-HEAT CONTROL

When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 20°C or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)

<JK> When the JK wire of the inverter P.C. board is cut, pre-heat control is activated. (Refer to 11-6.1)

NOTE : When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.

11

TROUBLESHOOTING

MUZ-HJ25VA MUZ-HJ35VA

11-1. CAUTIONS ON TROUBLESHOOTING

1. Before troubleshooting, check the following:

1) Check the power supply voltage.

2) Check the indoor/outdoor connecting wire for miswiring.

2. Take care of the following during servicing

1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.

2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.

3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.

4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the

components.

5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

<Incorrect>

<Correct>

Lead wiring

Housing point

3. Troubleshooting procedure

1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.

2) Before servicing, check that the connector and terminal are connected properly.

3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.

4) Refer to 11-2 and 11-3.

OBH648

19

11-2. FAILURE MODE RECALL FUNCTION

Outline of the function

This air conditioner can memorize the abnormal condition which has occurred once.

Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.

This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.

1. Flow chart of failure mode recall function for the indoor/outdoor unit

Operational procedure

The cause of abnormality cannot be found because the abnormality does not recur.

Setting up the failure mode recall function

Turn ON the power supply.

<Preparation of the remote controller>

While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

Hold down the other two buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1

Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?

Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2

No

(OFF)

1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.

Indoor unit is normal.

But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way.

Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2)

Judgment of indoor/outdoor abnormality

Yes

(Blinks)

Before blinking, does the upper lamp of OPERATION INDICA-

TOR lamp stay ON for 3 seconds?

Stays ON for 3 seconds (without beep):

The outdoor unit is abnormal.

No

Yes

The indoor unit is abnormal.

Check the blinking pattern, and identify the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.)

Make sure to check at least two consecutive blinking cycles. 2

The outdoor unit is abnormal.

Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 11-2.3)

Make sure to check at least two consecutive blinking cycles. 3

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures.

Turn OFF the power supply and turn it ON again.

Press RESET button of the remote controller.

Repair the failure parts.

Deleting the memorized abnormal condition

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.

Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.

2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2. Blinking pattern when the indoor unit is abnormal:

2.5-second OFF

Blinking at 0.5second interval 2.5-second OFF

Blinking at 0.5second interval

ON

OFF

Beeps

Repeated cycle

Beeps

Repeated cycle

3.Blinking pattern when the outdoor unit is abnormal:

Blinking at 0.5-

2.5-second OFF 3-second ON second interval

ON

OFF

No beep

Repeated cycle

Beeps

2.5-second OFF

Beeps

Repeated cycle

3-second ON

No beep

Repeated cycle

OBH648

20

Blinking at 0.5second interval

Beeps

Repeated cycle

2. Flow chart of the detailed outdoor unit failure mode recall function

Operational procedure

The outdoor unit might be abnormal.

Check if outdoor unit is abnormal according to the following procedures.

Make sure that the remote controller is set to the failure mode recall function.

With the remote controller headed towards the indoor unit, press TOO

COOL or TOO WARM button to adjust the set temperature to 25°C. 1

1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.

Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?

Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2

Yes

(Blinks )

No

(OFF)

The outdoor unit is abnormal.

Check the blinking pattern, and identify the abnormal point with the outdoor unit failure mode table (11-2.3.).

Make sure to check at least two consecutive blinking cycles. 2

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures.

Turn OFF the power supply and turn it ON again.

Press RESET button of the remote controller.

The outdoor unit is normal.

Release the failure mode recall function according to the left mentioned procedure.

Repair the failure parts.

Deleting the memorized abnormal condition

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" (11-2.1.).

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.

Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.

2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2.Blinking pattern when outdoor unit is abnormal:

2.5-second OFF 3-second ON

ON

OFF

No beep

Repeated cycle

Blinking at 0.5second interval

Beeps

2.5-second OFF 3-second ON

No beep

Repeated cycle

Blinking at 0.5second interval

Beeps

Repeated cycle

OBH648

21

3. Outdoor unit failure mode table

The upper lamp of

OPERATION

INDICATOR lamp

(Indoor unit)

Abnormal point

(Failure mode/protection)

LED indication

(Outdoor P.C. board)

1-time fl ash

2.5 seconds

OFF

2-time fl ash

2.5 seconds

OFF

3-time fl ash

2.5 seconds

OFF

4-time fl ash

2.5 seconds

OFF

5-time fl ash

2.5 seconds

OFF

6-time fl ash

2.5 seconds

OFF

7-time fl ash

2.5 seconds

OFF

9-time fl ash

2.5 seconds

OFF

10-time fl ash

2.5 seconds

OFF

11-time fl ash

2.5 seconds

OFF

14-time fl ash

2.5 seconds

OFF

Indoor/outdoor communication, receiving error

Indoor/outdoor communication, receiving error

Outdoor power system

Discharge temperature thermistor

Defrost thermistor

Fin temperature thermistor

P.C. board temperature thermistor

Compressor synchronous abnormality (Compressor start-up failure protection)

Discharge temperature

High pressure

Fin temperature/ P.C. board temperature

Nonvolatile memory data

Power module

Discharge temperature

DC voltage

Each phase current of compressor

Stop valve (Closed valve)

4-way valve/

Pipe temperature

1-time fl ash every

2.5 seconds

— —

Any signals from the inverter P.C. board cannot be received normally for

3 minutes.

Although the inverter P.C. board sends signal "0", signal "1" has been received

30 consecutive times.

Overcurrent protection cut-out operates 3 consecutive times within

1 minute after the compressor gets started.

Thermistor shorts or opens during compressor running.

•Refer to 11-5. How to check miswiring and serial signal error.

•Refer to 11-5. How to check miswiring and serial signal error.

Reconnect connectors.

Refer to 11-5. "How to check inverter/ compressor".

Check stop valve.

• Refer to 11-5.

"Check of outdoor thermistors".

Defective outdoor thermistors can be identifi ed by checking the blinking pattern of

LED.

3-time fl ash

2.5 seconds OFF

4-time fl ash

2.5 seconds OFF fl ash

2.5 seconds OFF

12-time fl ash

2.5 seconds OFF

7-time fl ash

2.5 seconds OFF

5-time fl ash

2.5 seconds OFF

Waveform of compressor current is distorted.

Temperature of discharge temperature thermistor exceeds 116°C, compressor stops.

Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.

• Check refrigerant circuit and refrigerant

• amount.

Refer to 11-5. "Check of LEV".

Temperature indoor coil thermistor exceeds 70°C in HEAT mode.

Temperature defrost thermistor exceeds 70°C in COOL mode.

• Check refrigerant circuit and refrigerant

• amount.

Check stop valve.

Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 80 °C or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 78 °C.

Nonvolatile memory data cannot be read properly.

• compressor connector.

Refer to 11-5. "How to check inverter/

• compressor".

Check stop valve.

Reconnect compressor connector.

Refer to 11-5. "How to check inverter/ compressor".

Check around outdoor unit.

Check outdoor unit air passage.

Refer to 11-5. "Check of outdoor fan motor".

• Replace the inverter

P.C. board.

6-time fl ash

2.5 seconds OFF

8-time fl ash

2.5 seconds OFF

9-time fl ash

2.5 seconds OFF

14-time fl ash

2.5 seconds OFF

16-time fl ash

2.5 seconds OFF

The interface short circuit occurs in the output of the power module (IC700).

The compressor winding shorts circuit.

Temperature of discharge temperature thermistor has been 50°C or less for

20 minutes.

DC voltage of inverter cannot be detected normally.

• Refer to 11-5. "How to check inverter/ compressor".

Refer to 11-5. "Check of LEV".

Check refrigerant circuit and refrigerant amount.

• Refer to 11-5. "How to check inverter/ compressor".

Each phase current of compressor cannot be detected normally.

• Check stop valve.

Closed valve is detected by compressor current.

The 4-way valve does not work properly.

The indoor coil thermistor detects an abnormal temperature.

Check 4-way valve.

Replace inverter P.C. board.

Indoor/outdoor mode recall function

Outdoor unit failure mode recall function

NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (11-3.).

OBH648

22

11-3. TROUBLESHOOTING CHECK TABLE

Condition Remedy

1

Outdoor unit does not operate.

1-time fl ash every

2.5 seconds

'Outdoor unit stops and restarts 3 minutes later' is repeated.

16-time fl ash

2.5 seconds OFF

2-time fl ash

2.5 seconds OFF

3-time fl ash

2.5 seconds OFF

Outdoor power system

Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started, or failure of restart of compressor has repeated 24 times.

Reconnect connector of compressor.

Refer to 11-5. "How to check inverter/compressor".

• Check stop valve.

• Refer to 11-5. "Check of outdoor thermistors".

2

3

4

5

6

7

8

9

10

11

12

13

14

16

17

18

19

20

21

Outdoor unit operates.

6-time fl ash

2.5 seconds OFF

11-time fl ash

2.5 seconds OFF

14-time fl ash

2.5 seconds OFF

4-time fl ash

2.5 seconds OFF

5-time fl ash

2.5 seconds OFF

8-time fl ash

2.5 seconds OFF

12-time fl ash

2.5 seconds OFF

13-time fl ash

2.5 seconds OFF

1-time fl ash

2.5 seconds OFF

3-time fl ash

2.5 seconds OFF

4-time fl ash

2.5 seconds OFF

5-time fl ash

2.5 seconds OFF

7-time fl ash

2.5 seconds OFF

8-time fl ash

2.5 seconds OFF

9-time fl ash

2.5 seconds OFF

Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor, defrost thermistor, P.C. board temperature thermistor or outdoor heat exchanger temperature thermistor shorts or opens during compressor running.

Outdoor control system

Nonvolatile memory data cannot be read properly.

Serial signal

(The upper lamp of OPERATION INDICATOR lamp of the indoor unit lights up or fl ashes 7-time.)

The communication fails between the indoor and outdoor unit for 3 minutes.

Stop valve/

Closed valve

Outdoor unit

(Other abnormality)

4-way valve/

Pipe temperature

Overcurrent protection

Closed valve is detected by compressor current.

Outdoor unit is defective.

The 4-way valve does not work properly.

The indoor coil thermistor detects an abnormal temperature.

Large current fl ows into power module.

When overcurrent protection occurs within 10 seconds after compressor starts, compressor restarts after 15 seconds.

Replace inverter P.C. board.

Refer to 11-5. "How to check miswiring and serial signal error.

Check stop valve.

• Refer to 11-2.2. "Flow chart of the detailed outdoor unit failure mode recall function".

Refer to 11-5. "Check of R.V. coil".

Replace inverter P.C. board.

Reconnect connector of compressor.

Refer to 11-5. "How to check inverter/compressor".

Check stop valve.

Discharge temperature overheat protection

Fin temperature

/P.C. board temperature thermistor overheat protection

High pressure protection

Temperature of discharge temperature thermistor exceeds

116 °C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.

• Check refrigerant circuit and refrigerant amount.

• Refer to 11-5. "Check of LEV".

Temperature of fi n temperature thermistor on the heat sink exceeds 80 °C or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 78 °C.

Indoor coil thermistor exceeds 70 °C in HEAT mode. Defrost thermistor exceeds 70 °C in COOL mode.

The waveform of compressor current is distorted.

Check around outdoor unit.

Check outdoor unit air passage.

Refer to 11-5. "Check of outdoor fan motor".

• Check refrigerant circuit and refrigerant amount.

• Check stop valve.

Reconnect connector of compressor.

Refer to 11-5. "How to check inverter/compressor".

Compressor synchronous abnormality

Each phase current of compressor

DC voltage

Frequency drop by current protection

Frequency drop by high pressure protection

Each phase current of compressor cannot be detected normally.

DC voltage of inverter cannot be detected normally.

When the input current exceeds 5.4 A (HJ25)/6.1 A (HJ35), compressor frequency lowers.

Temperature of indoor coil thermistor exceeds 55 °C in HEAT mode, compressor frequency lowers.

• Refer to 11-5. "How to check inverter/compressor".

• Refer to 11-5. "How to check inverter/compressor".

The unit is normal, but check the following.

Check if indoor fi lters are clogged.

Check if refrigerant is short.

Check if indoor/outdoor unit air circulation is short cycled.

Frequency drop by defrosting in COOL mode

Frequency drop by discharge temperature protection

Outside temperature thermistor protection

Low discharge temperature protection

PAM protection

PAM: Pulse Amplitude Modulation

Indoor coil thermistor reads 8 °C or less in COOL mode, compressor frequency lowers.

Temperature of discharge temperature thermistor exceeds

111 °C, compressor frequency lowers.

When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.

Temperature of discharge temperature thermistor has been

50°C or less for 20 minutes.

The overcurrent fl ows into IC821 (Switching power transistor) or the bus-bar voltage reaches 320 V or more, PAM stops and restarts.

Inverter check mode The connector of compressor is disconnected, inverter check mode starts.

• Check refrigerant circuit and refrigerant amount.

Refer to 11-5. "Check of LEV".

Refer to 11-5. "Check of outdoor thermistors".

• Refer to 11-5. Check of outdoor thermistors.

Refer to 11-5. "Check of LEV".

Check refrigerant circuit and refrigerant amount.

This is not malfunction. PAM protection will be activated in the following cases:

1 Instantaneous power voltage drop. (Short time power failure)

2 When the power supply voltage is high.

• Check if the connector of the compressor is correctly connected.

Refer to 11-5. "How to check inverter/compressor".

NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.

2. LED is lighted during normal operation.

Inverter P.C. board

MUZ-HJ25/35

The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.

(Example) When the fl ashing frequency is “2”.

0.5-second ON

0.5-second ON

LED

Flashing

ON

2.5-second OFF

2.5-second OFF

OFF

OBH648

23

11-4. TROUBLE CRITERION OF MAIN PARTS

MUZ-HJ25VA MUZ-HJ35VA

Part name Check method and criterion

Defrost thermistor

(RT61)

Measure the resistance with a tester.

Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.

Discharge temperature thermistor (RT62)

Fin temperature thermistor

(RT64)

Measure the resistance with a tester.

Before measurement, hold the thermistor with your hands to warm it up.

Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.

Measure the resistance between the terminals with a tester.

(Part temperature -10 ~ 40°C)

Normal

Compressor (MC)

U-V

U-W

V-W

MUZ-HJ25VA

2.01 ~ 2.86 Ω

MUZ-HJ35VA

1.20 ~ 1.72 Ω

Outdoor fan motor (MF)

INNER FUSE

RA6V21-AB

152

+0

-5

°C CUT OFF

RA6V21-BB

126 ± 2: CUT OFF

Measure the resistance between the terminals with a tester.

(Part temperature -10 ~ 40°C)

Color of lead wire

WHT – BLK

BLK – RED

RA6V21-AB

305 ~ 374 Ω

247 ~ 304 Ω

Normal

RA6V21-BB, BD

222 ~ 272 Ω

245 ~ 300 Ω

R.V. coil (21S4)

Measure the resistance between the terminals with a tester.

(Part temperature -10˚C ~ 40°C)

Normal

1.19 ~ 1.78 kΩ

Expansion valve coil (LEV)

Measure the resistance using a tester.

(Part temperature: -10 ~ 40°C)

Color of lead wire

WHT – RED

RED – ORN

YLW – BRN

BRN – BLU

Normal

37 ~ 54 Ω

WHT

RED

ORN

Figure

WHT

2

RED BLK

3

W

1

V

U

FUSE

BLK

RED

WHT

LEV

OBH648

24

11-5. TROUBLESHOOTING FLOW

A How to check inverter/compressor

Disconnect the connector (CN61) between compressor and the power module (IC700).

Check the voltage between terminals.

Are the voltages balanced?

Yes

Check the compressor.

No

See 11-5. “Check of open phase”.

Replace the inverter P.C. board.

See 11-5. “Check of compressor”.

B Check of open phase

● With the connector between the compressor and the power module disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between the terminals.

Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)

<< Operation method>>

Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-

TION : Refer to 8-3.)

<<Measurement point>>

At 3 points

BLK (U)-WHT (V)

BLK (U)-RED (W)

WHT(V)-RED (W)

Measure AC voltage between the lead wires at 3 points.

NOTE : 1. Output voltage varies according to power supply voltage.

2. Measure the voltage by analog type tester.

3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)

OBH648

25

C Check of compressor

Refer to 11-5. “Check of compressor winding”.

Is the compressor normal?

Yes

Refer to 11-5. “Check of compressor operation time”.

Does the compressor operate continuously?

Yes

OK.

No

No

Replace the compressor.

Refer to 11-5. “Check of compressor start failure”.

D Check of compressor winding

● Disconnect the connector (CN61) between the compressor and power module, and measure the resistance between the compressor terminals.

<<Measurement point>>

At 3 points

BLK-WHT

BLK-RED

WHT-RED

<<Judgement>>

Measure the resistance between the lead wires at 3 points.

Refer to 11-4.

0 [Ω] ················Abnormal [short]

Infinite [Ω] ·······Abnormal [open]

NOTE : Be sure to zero the ohmmeter before measurement.

E Check of compressor operation time

● Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current.

method>>

Start heating or cooling operation by pressing EMERGENCY

OPERATION switch on the indoor unit.

(TEST RUN OPERATION: Refer to 8-3.)

<<Measurement>>

Measure the time from the start of compressor to the stop of compressor due to overcurrent.

<<Judgement>>

0 second

1 second

2 seconds

10 seconds

10 minutes

Compressor starts

Abnormal

(IC700 failure)

(Compressor winding short)

Abnormal

(Compressor lock out)

(Starting defect)

Abnormal

(Poor contact,)

(Outdoor P.C. board defect)

(Disconnected connector)

Abnormal

(Refrigerant circuit defect)

(Closed valve)

Normal

OBH648

26

F Check of compressor start failure

Make sure that ~ is normal.

•Electrical circuit check

. Contact of the compressor connector (Including CN61)

. Output voltage of inverter P.C. board and balance of them (See 11-5. )

. Direct current voltage between DB61(+) and (-) on the inverter P.C. board

. Voltage between outdoor terminal block S1-S2

Does the compressor run for 10 seconds or more after it starts?

No

Yes

After the compressor is heated with a drier, does the compressor start? 1

Yes

Compressor start failure. Activate pre-heat control.

(Refer to 10-2. "PRE-HEAT CONTROL SETTING")

No

Check the refrigerant circuit.

Check the stop valve.

Replace the compressor.

1

Heat the compressor with a drier for about 20 minutes.

Do not recover refrigerant gas while heating.

Heating part

G Check of outdoor thermistors

Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.

Is the thermistor normal? (Refer to 11-6.1.)

Yes

No

Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.

Reconnect the connector of thermistor.

Turn ON the power supply and press EMERGENCY OPERATION switch.

Does the unit operate for 10 minutes or more without showing thermistor abnormality?

Yes

No

OK.

(Cause is poor contact.)

Thermistor

Defrost

Discharge temperature

Fin temperature

Symbol

RT61

RT62

RT64

Replace the inverter P.C. board.

Connector, Pin No.

Between CN641 pin 1 and pin 2

Between CN641 pin 3 and pin 4

Between CN642 pin 1 and pin 2

Board

Inverter P.C. board

OBH648

27

H Check of R.V. coil

First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4.

In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector although any signal is not being transmitted to R.V. coil.

Check if CN721 is connected.

Unit operates COOL mode even if it is set to HEAT mode.

Disconnect connector (CN61) between the compressor and the power module.

Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).

Is there 230 VAC between CN721 and

on the inverter P.C. board 3 minutes after the power supply is turned ON?

Yes

Replace the 4-way valve.

No

Replace the inverter

P.C. board.

Unit operates HEAT mode even if it is set to COOL mode.

Disconnect connector (CN61) between the compressor and the power module.

Turn ON the power supply and press

EMERGENCY OPERATION switch twice (HEAT mode).

Is there 230 VAC between CN721 and

on the inverter P.C. board 3 minutes after the power supply is turned ON?

No

Replace the 4-way valve.

Yes

Replace the inverter

P.C. board.

I Check of outdoor fan motor

Check the resistance of fan motor. (Refer to

11-4.)

Is the resistance of fan motor normal?

Yes

No

Disconnect the connector CN771 on the inverter P.C. board.

Disconnect the connector (CN61) between compressor and power transistor module.

Turn ON the power supply and press the

EMERGENCY OPERATION switch.

Does the upper lamp of

OPERATION

INDICATOR lamp on the indoor unit light up?

Replace the outdoor fan motor.

After 3 minutes, is there voltage 230 VAC between CN771 and

on the inverter P.C. board?

Yes

Replace the outdoor fan motor.

No

Replace the inverter

P.C. board.

OBH648

28

J Check of power supply

Disconnect the connector (CN61) between compressor and power module.

Turn ON power supply and press

EMERGENCY OPERATION switch.

DB61

250 - 370 VDC

Does the upper lamp of OPERATION

INDICATOR lamp on the indoor unit light up?

Yes

No

Is there voltage 250 - 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board?

(Refer to 11-6.1.)

No

Yes

Check the electric parts in main circuit.

Rectify indoor/outdoor connecting wire.

Yes

Is there voltage 230 VAC between the indoor terminal block S1 and S2?

Dose LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)

If light up, OK.

Yes

If fl ash, refer to 11-3.

No

No

Inverter P.C. board

(Solder side)

Replace the indoor electronic control P.C. board.

Replace the inverter

P.C. board.

K Check of LEV (Expansion valve)

Turn ON the power supply.

<Preparation of the remote controller>

While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

Hold down the other two buttons for another 3

seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed.

Then release the buttons.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1

Expansion valve operates in full-opening direction.

Do you hear the expansion valve "click, click·······"?

Do you feel the expansion valve vibrate on touching it ?

No

Yes

OK

1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.

Is LEV coil properly fi xed to the expansion valve?

Yes

No

Does the resistance of LEV coil have the characteristics?

(Refer to 11-4.)

No

Yes

Replace the LEV coil.

Properly fi x the LEV coil to the expansion valve.

Measure each voltage between connector pins of CN724 on the inverter P.C. board.

1. Pin (-) — Pin (+)

2. Pin (-) — Pin (+)

3. Pin (-) — Pin (+)

4. Pin (-) — Pin (+)

Is there about 3 ~ 5 VAC between each?

NOTE: Measure the voltage by an analog tester.

Yes

Replace the expansion valve.

NOTE : After check of LEV, do the undermentioned operations.

1. Turn OFF the power supply and turn ON it again.

2. Press RESET button on the remote controller.

OBH648

29

No

Replace the inverter P.C. board.

L How to check miswiring and serial signal error

Turn OFF the power supply.

Is there rated voltage in the power supply?

No

Yes

1. Turn ON the power supply.

2. Press the emergency operation switch.

Check the power supply.

No

Initializing the determination of the power receiving system

The microprocessor may have mistaken the unit as a model receiving power from the outdoor unit. Follow the procedure below to start the determination of the power receiving system all over again.

1. Hold down the emergency operation switch for 30 seconds. (Do not release the switch even though a buzzer beeps once in about 5 seconds. Keep holding down the switch until a buzzer beeps again for

1 second after 30 seconds. Figure 1)

2. Turn off the power supply.

3. Wait for about 30 seconds.

4. Turn on the power supply.

5. Press the emergency operation switch.

6. The relay 52C will be turned on in 3 minutes.

Has the relay 52C been turned on 3 minuets later ?

[The relay will be turned on in 3 to 7 seconds by short circuiting the timer short mode point (Refer to 10-7.).]

Yes

Has the miswiring or the serial error been indicated?

No

Yes

Indication of miswiring

Indication of serial signal error

OPERATION

INDICATOR lamp

Continuous blinks

Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?

Yes

No

Correct them.

A

Figure 1

Buzzer

ON

0.5-second

OFF

Beeps Beeps

Emergency operation switch

ON

OFF

5-second

1-second

Beeps

B

Turn OFF the power supply. Make sure again that the indoor/outdoor connecting wire is correctly connected. With the indoor/outdoor connecting wire connected, short circuit between S2 and S3 on the outdoor terminal block. 1

<Preparation of the remote controller>

While pressing both OPERATION SELECT button and

TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

Hold down the other two buttons for another 3 seconds.

Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons.

(Setting up the failure mode recall function)

ON

30-second

A

Turn OFF inverter-controlled lighting equipment.

Turn OFF the power supply and then turn ON again.

Press the emergency operation switch.

After the relay

52C is turned on

3 minutes later, is miswiring or the serial signal error indicated?

Yes

B

No

Reinstall either the unit or the light away from each other.

Attach a fi lter on remote control receiving section of the indoor unit.

OBH648

OFF

Aim the remote controller at the indoor unit, and press

OPERATE/STOP (ON/OFF) button. The relay 52C will be turned on, and the outdoor unit will be energized.

1 Make sure that the wiring is correct. If the procedure is performed without correcting miswiring, it may lead to damage to the P.C. board.

Is the rated supply voltage applied between the S1 and S2 on the outdoor terminal block? (Check of supply voltage)

Yes

No

Is there any problem in the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact with the terminal block?

No

Is there approximately 250 VDC

– 370 VDC between DB61(+) and

DB61 (–) on the indoor inverter

P.C. board? (Voltage check of the inverter P.C. board)

Yes

No

Replace the indoor inverter

P.C. board. 2

Does the LED on the inverter P.C. board repeat "3.6-second-OFF and

0.8-second-ON quick blinking" for

3 minutes after the outdoor unit is energized?

(Check the blinking pattern within 3 minutes after LED is turned on. After 3 minutes, LED will blink 6 times whether the inverter P.C. board is normal or not.)

Yes

2 Be careful of 140

VDC – 280 VDC residual charge in the capacitor on the main inverter circuit.

No

Replace the indoor inverter

P.C. board. 2

Replace the indoor electronic control

P.C. board. 3

3 Be sure to release the failure-mode recall function after checking.

30

Yes

Replace the indoor/ outdoor connecting wire.

M Electromagnetic noise enters into TV sets or radios

Is the unit earthed?

Yes

No

Earth the unit.

Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?

No

Yes

Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?

No

Yes

Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.

Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.

Are the antennas damaged?

Is the coaxial cable damaged?

Is there any poor contact in the antenna wiring?

No

Yes

Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?

No

Yes

Replace or repair the antenna.

Replace or repair the coaxial cable.

Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.

Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring).

Check the following before asking for service.

1. Devices affected by the electromagnetic noise

TV sets, radios (FM/AM broadcast, shortwave)

2. Channel, frequency, broadcast station affected by the electromagnetic noise

3. Channel, frequency, broadcast station unaffected by the electromagnetic noise

4. Layout of ;

indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver

5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise

6. Presence or absence of amplifi er such as booster

7. Operation condition of air conditioner when the electromagnetic noise enters in

1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.

2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.

3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.

4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.

OBH648

31

11-6. TEST POINT DIAGRAM AND VOLTAGE

1. Inverter P.C. board

MUZ-HJ25VA MUZ-HJ35VA

Back side of unit

DB61

250 V - 370 VDC

(+)

(-)

230 VAC

Smoothing capacitor (C61)

Fuse (F801)

T3.15AL250V

Output to drive outdoor fan motor (CN771)

R.V. coil

(CN721)

Fuse (F701)

T3.15AL250V

Output to drive compressor

(LDW,

LDV,

LDU)

230 VAC

LED

Front side of unit

LEV connector

(CN724)

Jumper wire for changing defrost setting (JS)

Jumper wire for pre-heat control setting (JK)

100

Defrost thermistor (RT61)

90

80

70

60

50

40

30

20

10

0

-20 -10 0 10 20 30 40

Temperature (°C)

OBH648

700

Discharge temperature thermistor (RT62)

600

500

400

300

200

100

0

0 10 20 30 40 50 60 70 80 90 100 110 120

Temperature (°C)

32

200

Fin temperature thermistor (RT64)

180

160

140

120

100

80

60

40

20

0

0 10 20 30 40 50 60 70 80

Temperature (°C)

12

DISASSEMBLY INSTRUCTIONS

<"Terminal with locking mechanism" Detaching points>

The terminal which has the locking mechanism can be detached as shown below.

There are two types (refer to (1) and (2)) of the terminal with locking mechanism.

The terminal without locking mechanism can be detached by pulling it out.

Check the shape of the terminal before detaching.

(1) Slide the sleeve and check if there is a locking lever or not.

(2) The terminal with this connector has the

locking mechanism.

Sleeve

Locking lever

Slide the sleeve.

Pull the terminal while pushing the locking lever.

Hold the sleeve, and pull out the terminal slowly.

Connector

12-1. MUZ-HJ25VA MUZ-HJ35VA

OPERATING PROCEDURE

1. Removing the cabinet and the panels

(1) Remove the screw fixing the service panel.

(2) Pull down the service panel and remove it.

(3) Disconnect the power supply and indoor/outdoor connecting wire.

(4) Remove the screws fixing the top panel.

(5) Remove the top panel.

(6) Remove the screws fixing the cabinet.

(7) Remove the cabinet.

(8) Remove the fixing screws of the terminal block support and the back panel. (Photo 4)

(9) Remove the screws fixing the back panel.

(10) Remove the back panel.

Photo 1

NOTE: Turn OFF power supply before disassembly.

PHOTOS

Screws of the top panel

Photo 2

Screws of the top panel

Direction to remove

Screws of the service panel

Photo 3

Screws of the cabinet

Screws of the back panel

Screw of the cabinet

Hooks

OBH648

33

OPERATING PROCEDURE

2. Removing the inverter assembly, inverter P.C. board

(1) Remove the cabinet and the panels. (Refer to 1.)

(2) Disconnect the lead wire to the reactor and the following connectors:

<Inverter P.C. board>

CN721 (R.V. coil)

CN771 (Fan motor)

CN641 (Defrost thermistor and discharge temperature thermistor)

CN724 (LEV)

(3) Remove the compressor connector (CN61).

(4) Remove the screws fixing the heat sink support and the separator.

(5) Remove the inverter assembly.

(6) Remove the screw of the earth wire and the screw of the terminal block support.

(7) Remove the screw of the terminal block and remove the terminal block.

(8) Remove the heat sink support from the P.C. board support.

(9) Unhook the catch of the inverter P.C. board and remove the inverter P.C. board from the P.C. board support.

PHOTOS

Photo 4

Screw of the heat sink and the separator

Screws of the terminal block support and the back panel

3. Removing the R.V. coil

(1) Remove the cabinet and the panels. (Refer to 1.)

(2) Disconnect the following connectors:

<Inverter P.C. board>

CN721 (R.V. coil)

(3) Remove the R.V. coil.

Photo 5 (Inverter assembly)

Heat sink

Heat sink support

P.C. board support

Screw of the earth wire

Terminal block support

Inverter

P.C. board

Screw of the terminal block support

OBH648

34

OPERATING PROCEDURE

4. Removing the discharge temperature thermistor and the defrost thermistor

(1) Remove the cabinet and the panels. (Refer to 1.)

(2) Disconnect the lead wire to the reactor and the following connectors:

<Inverter P.C. board>

CN641 (Defrost thermistor and discharge temperature thermistor)

(3) Pull out the discharge temperature thermistor from its holder.

(4) Pull out the defrost thermistor from its holder.

Photo 6

PHOTOS

Brazed part of the 4-way valve

5. Removing the outdoor fan motor

(1) Remove the cabinet and the panels. (Refer to 1.)

(2) Disconnect the following connectors:

<Inverter P.C. board>

CN771 (Fan motor)

(3) Remove the fan motor lead wire from where it is fastened on the separator.

(4) Remove the propeller nut.

(5) Remove the propeller.

(6) Remove the screws fixing the fan motor.

(7) Remove the fan motor.

Brazed part of the

4-way valve

Photo 7

Defrost thermistor

Suction pipe brazed part

R.V. coil

Screws of the reactor

Photo 8

Discharge pipe brazed part

Discharge temperature thermistor

6. Removing the compressor and the 4-way valve

(1) Remove the cabinet and the panels. (Refer to 1.)

(2) Remove the inverter assembly. (Refer to 2.)

(3) Remove the screws of the reactor and remove the reactor.

(4) Remove the screws of the separator and remove the separator.

(5) Remove the terminal cover and the compressor lead wire.

(6) Recover gas from the refrigerant circuit.

NOTE:

Recover gas from the pipes until the pressure gauge shows 0 kg/cm 2 (0 MPa).

(7) Detach the brazed part of the suction and the discharge pipe connected with the compressor.

(8) Remove the nuts of compressor legs.

(9) Remove the compressor.

(10) Detach the brazed part of pipes connected with the

4-way valve.

Propeller

Screws of the outdoor fan motor

OBH648

35

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

© Copyright 2012 MITSUBISHI ELECTRIC CORPORATION

Distributed in Dec. 2012. No. OBH648

Made in Japan

New publication, effective Dec. 2012

Specifications are subject to change without notice.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement