CAREL e-drofan electronic controller, acqua remote terminal, e-droset terminal, remote control, e-drofan expansion card, e-drofan 4 triac, triac/relay expansion board, CANbus CANbus serial board User manual
Hirdetés
Hirdetés
e-drofan
electronic controller
User manual
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
IMPORTANT WARNINGS
CAREL bases the development of its products on several years’ experience in the
HVAC fi eld, on continuous investment in technological innovation of the product, on rigorous quality procedures and processes with in-circuit and function tests on 100% of its production, on the most innovative production technologies available on the market. CAREL and its branch offi ces/affi liates do not guarantee, in any case, that all the aspects of the product and the software included in the product will respond to the demands of the fi nal application, even if the product is built according to state-of-the-art techniques. The client (builder, developer or installer of the fi nal equipment) assumes every responsibility and risk relating to the confi guration of the product in order to reach the expected results in relation to the specifi c fi nal installation and/or equipment. CAREL in this case, through specifi c agreements, can intervene as consultant for the positive result of the fi nal start-up machine/application, but in no case can it be held responsible for the positive working of the fi nal equipment/apparatus.
The CAREL product is a state-of-the-art product, whose operation is specifi ed in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
Each CAREL product, in relation to its advanced technological level, needs a phase of defi nition / confi guration / programming / commissioning so that it can function at its best for the specifi c application. The lack of such phase of study, as indicated in the manual, can cause the fi nal product to malfunction of which CAREL can not be held responsible.
Only qualifi ed personnel can install or carry out technical assistance interventions on the product.
The fi nal client must use the product only in the manner described in the documentation related to the product itself.
Without excluding proper compliance with further warnings present in the manual, it is stressed that in any case it is necessary, for each Product of CAREL:
• To avoid getting the electrical circuits wet. Rain, humidity and all types of liquids or condensation contain corrosive mineral substances that can damage the electrical circuits. In any case, the product should be used and stored in environments that respect the range of temperature and humidity specifi ed in the manual.
• Do not install the device in a particularly hot environment. Temperatures that are too high can shorten the duration of the electronic devices, damaging them and distorting or melting the parts in plastic. In any case, the product should be used and stored in environments that respect the range of temperature and humidity specifi ed in the manual.
• Do not try to open the device in any way different than that indicated in the manual.
• Do not drop, hit or shake the device, because the internal circuits and mechanisms could suffer irreparable damage.
• Do not use corrosive chemical products, aggressive solvents or detergents to clean the device.
• Do not use the product in application environments different than those specifi ed in the technical manual.
All the above reported suggestions are valid also for the control, serial unit, programming key or nevertheless for any other accessory in the product portfolio of
CAREL.
CAREL adopts a policy of continuous development. Therefore, CAREL reserves the right to carry out modifi cations and improvements on any product described in the present document without prior notice.
The technical data in the manual can undergo modifi cations without obligation to notice.
The liability of CAREL in relation to its own product is regulated by CAREL’s general contract conditions edited on the website www.carel.com and/or by specifi c agreements with clients; in particular, within the criteria consented by the applicable norm, in no way will CAREL, its employees or its branch offi ces/affi liates be responsible for possible lack of earnings or sales, loss of data and information, cost of substitute goods or services, damage to things or persons, work interruptions, or possible direct, indirect, incidental, patrimonial, of coverage, punitive, special or consequential in any way caused damages, be they contractual, out-of-contract, or due to negligence or other responsibility originating from the installation, use or inability of use of the product, even if CAREL or its branch offi ces/affi liates have been warned of the possibility of damage.
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
WARNING: separate as much as possible the probe and digital input signal cables from the cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance. Never run power cables (including the electrical panel wiring) and signal cables in the same conduits.
Disposal of the product
In reference to European Community directive 2002/96/EC issued on 27 January
2003 and the related national legislation, please note that:
1. we cannot be disposed of as municipal waste and such waste must be collected and disposed of separately;
2. the public or private waste collection systems defi ned by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment.
3. the equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative effects on human health and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the penalties are specifi ed by local waste disposal legislation.
4 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Content
1. INTRODUCTION 7
2. USER 8
2.1 Remote acqua terminal ........................................................................................................ 8
2.1.1 Manual operation: cooling .................................................................................................................9
2.1.2 Manual operation: heating ................................................................................................................9
2.1.3 Manual operation: dehumidifi cation (DRY ....................................................................................9
2.1.4 Manual operation: fan ........................................................................................................................9
2.1.5 Automatic operation............................................................................................................................9
2.1.6 Comfort control ....................................................................................................................................10
2.1.7 Setting the clock and On/Off timer ...................................................................................................10
2.1.8 Sleep operation ....................................................................................................................................10
2.1.9 Remote off .............................................................................................................................................11
2.1.10 Alarms ...................................................................................................................................................11
2.2 e-droset terminal .................................................................................................................. 11
2.2.1 Manual operation: Cooling................................................................................................................12
2.2.2 Manual operation: Heating with or without heater .....................................................................12
2.2.3 Manual operation: Dry (dehumidifi cation) ...................................................................................12
2.2.4 Manual operation: Fan .......................................................................................................................12
2.2.5 Automatic operation ...........................................................................................................................12
2.2.6 Comfort control ..................................................................................................................................13
2.2.7 Sleep function ......................................................................................................................................13
2.2.8 Remote lock ..........................................................................................................................................13
2.2.9 Alarms ....................................................................................................................................................13
2.2.10 Occupancy function ..........................................................................................................................13
2.3 Remote control and IR receiver board ............................................................................ 14
2.3.1 Manual operation: cooling ................................................................................................................14
2.3.2 Manual operation: heating ................................................................................................................15
2.3.3 Manual operation: dehumidifi cation (DRY) ..................................................................................15
2.3.4 Manual operation: fan ........................................................................................................................15
2.3.5 Automatic operation ...........................................................................................................................15
2.3.6 Setting the clock and ON/OFF timer ..............................................................................................16
2.3.7 Sleep operation ...................................................................................................................................16
2.3.8 Keypad lock ..........................................................................................................................................16
2.3.9 Button and signal LED .......................................................................................................................17
2.3.10 Replacing the batteries .....................................................................................................................17
2.3.11 Alarms ..................................................................................................................................................17
2.4 Additional functions ............................................................................................................. 17
2.5 Troubleshooting .................................................................................................................... 17
3. INSTALLATION 18
3.1 Introduction: e-drofan and accessories .............................................................................. 18
3.2 Type of fan coil and installation.......................................................................................... 19
3.3 Installation and basic settings ............................................................................................. 20
3.3.1 Mounting ...............................................................................................................................................20
3.3.2 Connections ..........................................................................................................................................20
3.3.3 Basic settings and functions available (dip-switch) .....................................................................23
3.3.4 Programming key (copy the confi guration) ..................................................................................23
3.3.5 LCD terminal ........................................................................................................................................23
3.3.6 e-droset .................................................................................................................................................24
3.3.7 Installing the modulating valves (3 point and 0-10V, with thermal actuator) ......................25
3.3.8 Protection against electric shock and maintenance warnings .................................................25
3.3.9 Broadcast networks ..........................................................................................................................25
3.3.10 Procedure for testing the installation and alarms.......................................................................28
4. ADVANCED SETTINGS 29
4.1 Confi guration of the I/O and installer custom settings ................................................... 29
4.1.1. Modifying parameters ........................................................................................................................29
4.1.2 Probes .....................................................................................................................................................30
4.1.3 Digital inputs .........................................................................................................................................30
4.1.4 Outputs ..................................................................................................................................................31
4.1.5 Dipswitches and type of installation ................................................................................................32
4.1.6 Method for testing the installation ...................................................................................................32
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
5
6
4.2 Control algorithms ............................................................................................................... 33
4.2.1 General functions: heat enable (heating/automatic heating) ...................................................33
4.2.2 General functions: cool enable (cooling/ automatic cooling, dehumidify .............................33
4.2.3 General functions: Flush (fan on/off cycles) .................................................................................34
4.2.4 General functions: Extra Flush ........................................................................................................34
4.2.5 General functions: Autofan (fan speed selection based on the room temperature) ..........34
4.2.6 General functions: Continuous ventilation ....................................................................................34
4.2.7 General functions: Comfort ..............................................................................................................35
4.2.8 General functions: Occupancy ........................................................................................................35
4.2.9 General functions: P+I algorithm (cooling/heating/automatic) ...............................................36
4.2.10 General functions: modulating valve management ..................................................................37
4.2.11 General functions: fan speed limit .................................................................................................38
4.2.12 Manual operation: Cooling - (Management of the hot/cold water valve or cold water valve only) ..............................................................................................................................38
4.2.13 Manual operation: heating - (management of the hot/cold water valve or cold water valve only) ..............................................................................................................................39
4.2.14 Manual operation: dehumidify .......................................................................................................40
4.2.15 Manual operation: fan .....................................................................................................................40
4.2.16 Automatic operation .........................................................................................................................41
4.2.17 Compensation using the outside temperature probe ...............................................................41
4.3 Notes on the serial connection settings ........................................................................... 41
4.4 User interface (remote acqua terminal) ............................................................................ 42
4.4.1 Programming the events: timer ON, OFF and sleep ....................................................................42
4.5 User interface (remote control and IR receiver) ............................................................. 42
4.6 Alarms .................................................................................................................................... 43
4.7 List of parameters ................................................................................................................. 43
5. HYDRONIC SYSTEMS 46
5.1 Structure ................................................................................................................................. 46
5.1.1 Single node .............................................................................................................................................47
5.1.2 Integrated hybrid systems ..................................................................................................................49
5.1.3 e-drobus ..................................................................................................................................................50
5.2 Signals and diagnostics ........................................................................................................ 50
5.2.1 Alarms ....................................................................................................................................................51
5.2.2 Notes on confi guring hydronic networks ......................................................................................51
5.2.3 Notes on the serial address settings ...............................................................................................51
6. NON-HYDRONIC SUPERVISORY SYSTEMS 52
6.1 Introduzione ........................................................................................................................... 52
6.2 Easy way Acqua (rete Wireless) .......................................................................................... 52
7. TECHNICAL SPECIFICATIONS AND PRODUCT CODES 52
7.1 e-drofan ................................................................................................................................... 52
7.2 e-drofan expansion card ...................................................................................................... 53
7.3 E-drofan 4 triac expansion board ....................................................................................... 54
7.3.1 Assembly and maintenance instructions ........................................................................................54
7.2.2 Protection against electric shock and maintenance warnings ...................................................54
7.3.3 Technical specifi cations .......................................................................................................................55
7.4 e-drofan triac/relay expansion board ................................................................................ 55
7.4.1 Assembly and maintenance instructions ........................................................................................55
7.4.2 Protection against electric shock and maintenance warnings ...................................................55
7.4.3 Technical specifi cations .......................................................................................................................55
7.5.1 Assembly and maintenance instructions ........................................................................................56
7.5.3 Technical specifi cations .......................................................................................................................56
7.6 Remote acqua terminal ........................................................................................................ 56
7.8 CANbus serial board............................................................................................................. 57
7.9 Remote control ...................................................................................................................... 58
7.10 Dimensions ........................................................................................................................... 59
7.11 Codes ..................................................................................................................................... 59
7.12 Notes on the software release and compatibility ........................................................... 60 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
1. INTRODUCTION
Features of the e-drofan family:
• Remote terminal with elegant appearance and diversifi ed access to the various functions (set point modifi cation on front buttons, change operating mode etc. on side buttons). NTC probe on board;
• Built-in LCD terminal with on-board probe;
• Remote control with LCD on board;
• Dipswitch for simple confi guration by the installer;
• Control board with high number of I/O (5 digital inputs, 3 probes, 5 relay outputs);
• Possibility to create local broadcast networks (up to 5 slaves, max 30 m);
• Possibility to create extended networks (up to 1 km) using optional CANbus serial card. Flexible space management;
• Implementation of hydronic systems with synergy between the chiller controller-e-drofan using optional
CANbus serial card;
• Customisable supervisory system thanks to the numerous protocols supported (Modbus, CANbus, PlantVisor);
• Parameter programming key;
• Options for the control of modulating valves (3 point, 0/10 Vdc input).
drofan is an electronic controller for fan coil units that optimises the performance of the cooling/heating system in order to achieve maximum comfort and considerable energy savings. It is easy to install and use, and allows the rapid re-confi guration of the unit in the event where there are changes to the spaces being air-conditioned.
The network connection simplifi es the operations if the installation has a high number of fan coils, as well as offering advanced supervision and automation functions (time bands, energy savings etc.), thanks to the integration with the chiller (pCO)/heat pump or boiler controller.
The information provided below has been divided based on the area of interest: user, installation, and advanced settings (typically reserved for the manufacturer of the air-conditioning system). e-drofan - +030221266 - rel. 3.6 del 26.04.2010
7
Fig. 2.a
Fig. 2.b
8
2. USER
The user interface is the acqua remote terminal, the built-in terminal or the remote control; all the devices have a liquid crystal display for simple and user-friendly operation.
2.1 Remote acqua terminal
In summary:
• NTC probe on board to control the room temperature;
• LCD with clear symbols;
• Selection of the value displayed (temperature, set point, offset from common set point);
• Selective keypad lock (limited functions for offi ces, hotels.);
• Manual or automatic operation;
• timer ON, OFF functions;
• SLEEP function.
Below is the description of the terminal and the symbols on the liquid crystal display:
Button Meaning
Fan coil ON/OFF. If the remote ON/OFF digital input or the hydronic network is present, the function of the button may be disabled.
Used to select the desired mode: cooling, heating, dehumidify, fan, automatic operation. If the remote cooling/heating digital input or hydronic network is present, the function of the button may be disabled.
Pressing this more than once sets the fan speed (min, med, max, automatic).
Pressing this once activates the SLEEP function, pressing it again selects the number of hours the sleep function lasts (if more than three seconds have passed since the button was last pressed the function is deactivated). After pressing 9 consecutive times the function is deactivated.
Pressing this once selects the fan coil on time (UP and DOWN buttons), a second time selects the off time, and the third time exits the timer programming mode. Hold the button to set the current time.
Increases the currently selected value.
Used to modify the value of the temperature set point.
Decreased the currently selected value.
Used to modify the value of the temperature set point.
Advanced functions: After entering a password, the parameters can be modifi ed.
+
Confi rms the modifi cations made to the parameters.
Table 2.a
Legenda
1
8
9
6
7
4
5
2
3
10
11
12
13
SLEEP function limited keypad functions active alarm display temperature probe, set point or active alarm indication of hydronic network connection automatic fan speed fan speed set (min/med/max) fan and operating modes dehumidify automatic operation cooling heating with heater heating
The following section shows all the default functions available on the e-drofan; the device can in any case be reconfi gured by the manufacturer of the cooling/heating system or by the installer (according to the features of the installation), and therefore some functions may not be available; in particular, if a series of e-drofan are connected in a hydronic network (highlighted by the special symbol on the display), some settings are fi xed by the manager of the installation and cannot be modifi ed.
Important: in the event of power failures, the clock setting will be lost and needs to be reset (the time fl ashes). Modify the time using the UP and DOWN buttons, and confi rm by pressing the SET button, after which the terminal can be used. e-drofan - +030221266 - rel. 3.6 del 26.04.2010
2.1.1 Manual operation: cooling
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the cooling symbol comes on.
• Setting the set point (desired temperature) using the UP and DOWN buttons.
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the higher the speed).
The fan only starts if the temperature of the coil is low enough, so as to avoid undesired fl ows of hot air.
If this condition is not satisfi ed the cooling symbol fl ashes.
2.1.2 Manual operation: heating
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the heating symbol only or heating with heater symbol (if installed) comes on. In the latter case the electric heater is also used as a source of heat.
• Setting the set point (desired temperature) using the UP and DOWN buttons.
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the higher the speed).
The fan only starts if the temperature of the coil is high enough, so as to avoid undesired fl ows of cold air.
If this condition is not satisfi ed the heating symbol fl ashes.
If the electric heater is installed (highlighted by the special symbol on the display) the fan continues operating for 20 s even after it has been stopped. This time must also elapse even if the unit is switched off using the ON/OFF button.
2.1.3 Manual operation: dehumidifi cation (DRY
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the dehumidifi cation symbol comes on;
• Setting the set point (desired temperature) using the UP and DOWN buttons;
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the fan
operates at minimum speed.
The fan only starts if the temperature of the coil is low enough, so as to avoid unwanted fl ows of hot and humid air. If this condition is not satisfi ed, the dehumidifi cation symbol fl ashes.
The e-drofan starts in cooling mode so as to bring the room temperature near to the set point (set point +
3 °C) using the set speed, then performs fan on/off cycles at minimum speed to remove the humidity.
2.1.4 Manual operation: fan
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly so that only the fan symbol (at the bottom of the display) and the corresponding bar are on.
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is set to medium.
The fan only starts if the ambient temperature is within the range of temperature 15 to 35 °C, so as to avoid undesired fl ows of hot or cold air.
2.1.5 Automatic operation
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the automatic symbol comes on;
• Setting the set point (desired temperature) using the UP and DOWN buttons;
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the higher the speed).
The mode (heating or cooling) is decided by the electronic controller based on the deviation from the set point; if the room temperature is higher than the set point the control performs the cooling function while if it is lower it performs the heating function.
The fan only starts if the temperature of the coil is suitable to perform the heating or cooling functions.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
9
Fig. 2.c
Fig. 2.d.a
with heater
Fig. 2.d.b
without heater
Fig. 2.e
Fig. 2.f
Fig. 2.g.a automatic mode
2.1.6 Comfort control
In some installations only automatic mode is available, and the set point is decided by the manager of the installation; in these cases the user can increase or decrease the set point up to 2 °C to compensate for the different perception of the room temperature.
The value is modifi ed by pressing the UP and DOWN buttons and is displayed for 5 seconds, after which the display returns to the previous situation.
Fig. 2.g.b automatic mode with automatic comfort
Fig. 2.g.c.
comfort variation mode
2.1.7 Setting the clock and On/Off timer
e-drofan offers the possibility to perform programmed starts and stops if the room only needs to be air-conditioned at certain times of the day. To be able to use these functions, the internal clock needs to be set with the correct time, as shown below:
• Hold the timer button for 5 seconds (Fig. 2.11);
• Set the time using the UP and DOWN buttons (the time fl ashes, Fig. 2.12);
• Confi rm by pressing the SET button (the time is on steady, see Fig. 2.13).
Fig. 2.h.a
Fig. 2.h.d
timer ON display
Fig. 2.h.e
timer OFF display
Fig. 2.i
10
Fig. 2.h.b
Fig. 2.h.c
Important:
In the event of power failures, the clock setting will be lost and needs to be reset, as does the On/Off timer.
In this case, the time fl ashes and starts from 12:00. The clock can be hidden by suitably confi guring the parameters (see section “constructor”).
The timer ON (start) is set by:
• Pressing the TIMER button once;
• Setting the required start time with the UP and DOWN buttons (the time fl ashes);
• Confi rming the time with the SET button (the symbol is on steady and the current time is displayed).
The timer OFF (stop) is set as for the timer ON, with the difference that the TIMER button must be pressed twice.
The timer ON/OFF functions remain active even after the corresponding ON/OFF event has occurred; to disable these functions proceed as follows:
• Press the timer button: once to disable the timer ON or twice to disable the timer OFF (the time fl ashes);
• Press the clear button (the special symbol disappears).
2.1.8 Sleep operation
The SLEEP function is especially useful during the night-time, when the decrease in body temperature
(due to sleep) changes the perception of the room temperature.
In cooling mode the set point is increased by P18 for the number of hours set, after which the e-drofan returns to the previous situation (the SLEEP function is cancelled).
In heating mode the set point is decreased by the value of P19.
To set the sleep function, proceed as follows:
• Switch the device on using the ON/OFF button and select the operating mode;
• Press the SLEEP button repeatedly until setting the required number of hours for the function.
To cancel this function, proceed by pressing the SLEEP button again, after having waited 3 s since the button was last pressed, or pressing the button more than once until exceeding the maximum number of hours, that is 9.
The SLEEP function can be combined with the timer OFF (see Fig. 2.i).
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
2.1.9 Remote off
When the remote off symbol is present the operating mode is set to automatic (with heater, if installed) and the user can: switch the unit on/off, modify the set point and set the fan speed; the other functions are not available.
2.1.10 Alarms
The “acqua” terminal displays any alarms relating to the malfunctions of the device, shown in the summary table below. In the event of alarms, contact the relevant personnel (manager of the installation or installer/maintenance engineer) and make note of the signal to assist the response.
signal
A01
A02
A03
A04
A05
A06
A07
Cn alarm
EEPROM fault offl ine in CAN network (no communication between e-drofan and CAN board) control probe fault probe B2 or B3 fault window alarm circulating pump alarm stop from digital input serial communication fault with HYFC*
Table 2.b
Key
3
4
1
2
5
6
7
8
9
10
11
12
2.2 e-droset terminal
In summary:
• NTC probe on board to control the room temperature;
• LCD with intuitive symbols;
• selection of the value displayed (temperature, set point, offset from common set point);
• selective keypad lock (limited functions for offi ces, hotels..);
• manual or automatic operation;
• sleep and occupancy functions;
• wall mounting using the most commonly available 3 gang switch boxes.
Below is the description of the terminal and the symbols shown on the liquid crystal display: button meaning
Fan coil On/Off. If the remote ON/OFF digital input or the hydronic network is present, the function of the button may be disabled.
Used to select the desired mode: Cooling, heating, dry (dehumidifi cation), fan, automatic operation. If the remote ON/OFF digital input or the hydronic network is present, the function of the button may be disabled.
Pressing this button repeatedly sets the fan speed (min, med, max, automatic).
Pressing the button once activates the sleep function, pressing it again selects the duration of the sleep function, in hours (if more than three seconds elapse from when the button was last pressed, the function is deactivated). After 9 consecutive presses the function is deactivated.
WITH THE OCCUPANCY FUNCTION ACTIVE: Pressing this button switches the e-drofan to occupancy mode, that is, it controls the temperature according to the set point rather than based on energy savings.
Increases the currently selected value. Used to set the desired temperature.
Decreases the currently selected value. Used to set the desired temperature.
Table 2.c
heating cooling dry automatic operation occupancy function= enabled on steady= occupied on fl ashing= temporarily occupied sleep function limited keypad function fan and operating modes set fan speed (min/med/max) automatic fan speed display temperature probe or set point or active alarm code e-drofan - +030221266 - rel. 3.6 del 26.04.2010
11
Fig. 2.j
Fig. 2.k
Fig. 2.l
Fig. 2.m.a
Fig. 2.m.b
Fig. 2.m.c
Fig. 2.m.d
Fig. 2.m.e
12
Below are all the functions available by default on the e-drofan; the device may however be reconfi gured by the manufacturer of the cooling/heating system or by the installer (according to the characteristics of the installation), and therefore some functions may not be available; in particular, when using a hydronic network connection between multiple e-drofan units, some settings are defi ned by the manager of the installation and cannot be modifi ed.
2.2.1 Manual operation: Cooling
Once the device has been switched on using the ON/OFF button, proceed as follows:
• press the MODE button repeatedly until the cooling symbol comes on;
• set the set point (required temperature) using the UP and DOWN buttons;
• press the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected, the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the greater the speed).
The fan only starts if the coil temperature is low enough, so as to avoid unwanted fl ows of hot air. If this condition is not satisfi ed, the cooling symbol fl ashes.
2.2.2 Manual operation: Heating with or without heater
Once the device has been switched on using the ON/OFF button, proceed as follows:
• press the MODE button repeatedly until the heating symbol comes on. If the heater is installed it is always used;
• set the set point (required temperature) using the UP and DOWN buttons;
• press the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected, the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the greater the speed).
The fan only starts if the coil temperature is high enough, so as to avoid unwanted fl ows of cold air. If this condition is not satisfi ed, the heating symbol fl ashes.
If the electric heater is installed, the fan continues operating for 20 seconds after deactivation. This is also valid when the unit is switched off from the ON/OFF button.
2.2.3 Manual operation: Dry (dehumidifi cation)
Once the device has been switched on using the ON/OFF button, proceed as follows:
• press the MODE button repeatedly until the dehumidifi cation symbol comes on.
• setting the set point (desired temperature) using the buttons UP and DOWN.
• press the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected, the fan operates at minimum speed.
The fan only starts if the coil temperature is low enough, so as to avoid unwanted fl ows of hot air. If this condition is not satisfi ed, the cooling symbol fl ashes.
The e-drofan starts in cooling mode so as to bring the room temperature to near the set point (set point
+ 3°C) using the set fan speed, and then performs fan on/off cycles at minimum speed to remove the humidity.
2.2.4 Manual operation: Fan
Once the device has been switched on using the ON/OFF button, proceed as follows:
• press the MODE button repeatedly until only the fan symbol (at the bottom of the display) and the corresponding bar are on;
• press the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected, the fan speed is fi xed at medium.
The fan only starts if the room temperature is in the range of temperatures from 15 to 35°C , so as to avoid unwanted fl ows of hot or cold air.
2.2.5 Automatic operation
Once the device has been switched on using the ON/OFF button, proceed as follows:
• press the MODE button repeatedly until the automatic symbol comes on;
• set the set point (required temperature) using the UP and DOWN buttons;
• press the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected, the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the greater the speed).
The mode (heating or cooling) is decided by the electronic controller based on the deviation from the set point; if the room temperature is above the set point, the controller switches to cooling mode, while if it is below the set point, heating mode is activated.
The fan only starts if the coil temperature is suffi cient to perform the heating or cooling functions.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
2.2.6 Comfort control
In some installations, the set point is decided by the manager of the installation; in these cases, the user may increase or decrease the set point by 3°C to compensate for the different perception of the room temperature.
The set point is changed by pressing the UP and DOWN buttons, and is displayed for 5 seconds, after which the previous display resumes.
Automatic mode with comfort active (Fig. 2.m.f).
Comfort setting in automatic (Fig. 2.m.g).
2.2.7 Sleep function
The sleep function is especially useful at night, when the decrease in body temperature (due to sleep) changes people’s perception of the room temperature.
In cooling mode, the set point is increased by P18 for the number of hours specifi ed on the panel, after which the e-drofan returns to the previous operation (the sleep function is cancelled).
SLEEP display active (Fig. 2.m.h).
In heating mode, the set point is decreased by the value of P19.
To set the sleep function, proceed as follows:
• switch on the device using the ON/OFF button and select the operating mode;
• press the SLEEP button repeatedly until setting the desired duration of the function in hours (exceeding the maximum number of 9 hours disables the function).
To see the remaining time for the sleep function, press the sleep button once (after having waited 3 seconds since last pressed), and press it again to leave the function.
The sleep function is always cancelled after a power failure.
2.2.8 Remote lock
When the remote lock symbol is present, the operating mode is fi xed on automatic (with heater, if installed) and the user can: switch the unit on/off, change the set point and set the fan speed; the other functions are not available.
Remote lock display (Fig. 2.m.i).
Fig. 2.m.f
Fig. 2.m.h
Fig. 2.m.g
Fig. 2.m.i
2.2.9 Alarms
The e-droset terminal can display any alarms relating to malfunctions of the device; below is a table summarising the signals. In the event of alarms, contact the relevant personnel (manager of the installation or installer/maintenance technician) and advise the signal so as to assist the response.
A4
A5
A6
A7
A8
Cn signal
A1
A2
A3 alarm
EEPROM fault offl ine in CAN network (no communication between e-drofan and CAN board)
Room probe fault
Probe B2 or B3 fault
Window alarm
Circulating pump alarm
Local stop
Humidity probe absent alarm serial communication fault with HYFC*
Table 2.d
2.2.10 Occupancy function
The system will air-condition the environment to the set temperature only when this is occupied; to activate the system, simply press any button, or wait for the sensor (if installed) to detect occupancy (this is shown by the symbol of the man coming on or fl ashing on the terminal). If the environment is not occupied, air-conditioning is activated with a set point aimed at saving energy (in this case, the terminal only shows the house symbol).
Environment empty, press any button to set occupancy (Fig. 2.m.l).
Environment temporarily occupied (Fig. 2.m.m).
Fig. 2.m.l
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
13
Fig. 2.m.m
Fig. 2.n
Fig. 2.o
Fig. 2.p.a
2.3 Remote control and IR receiver board
In summary:
• Remote control of the unit (7 m);
• Lock keypad (limited user functions: offi ces, hotels ..);
• LCD on board;
• IR receiver board with 3 LEDs, 1 buzzer for the signals and 1 button (in the event of fl at batteries);
• Manual or automatic operation;
• ON, timer OFF functions;
• SLEEP function.
Below is the description of the remote control and the symbols present on the liquid crystal display: button meaning
ON/OFF: Fan coil ON/OFF. If the remote ON/OFF digital input or hydronic network is present the function of the button may be disabled
MODE: used to select the desired mode: cooling, dehumidify, fan, heating, automatic operation. If the remote ON/OFF digital input or hydronic network is present the function of the button may be disabled
UP set point: used to increase the desired temperature value
DOWN set point: used to decrease the desired temperature value
FAN: press this more than once to set the fan speed (min, med, max, auto) set clear
+
SLEEP: press once to activate the SLEEP function, press again to select the number of hours for the sleep function. After pressing 9 times the function is cancelled
TIMER ON: used to set the fan coil on time
TIMER OFF: used to set the fan coil off time
UP timer: increases the setting of the timer
DOWN timer: decreases the setting of the timer
SET: confi rms the modifi cations made to the timer settings
CLEAR: pressed after the timer ON or timer OFF buttons cancels the action of the selected timer. If pressed for 5 seconds activates the keypad lock, the only function enabled is
ON/OFF pressed for 5 seconds sets the time
Table 2.3
Legenda:
10
11
12
13
14
7
8
9
5
6
3
4
1
2 lock keypad functions data transmission in progress timer ON/OFF timer/clock display of temperature probe or set point or active alarm indication of hydronic network connection automatic fan speed set fan speed (min/med/max) fan and operating modes automatic operation cooling heating with heater heating
Dehumidify
14
The following section shows all the default functions available on the e-drofan; the device can in any case be reconfi gured by the manufacturer of the cooling/heating system or by the installer (according to the features of the installation), and therefore some functions may not be available; in particular, if a series of e-drofan are connected in a hydronic network (highlighted by the special symbol on the display), some settings are fi xed by the manager of the installation and cannot be modifi ed.
The correct reception of the functions is signalled by the sounding of the buzzer.
2.3.1 Manual operation: cooling
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the cooling symbol comes on;
• Setting the set point (desired temperature) using the UP set point and DOWN set point buttons;
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the higher the speed).
The fan only starts if the temperature of the coil is low enough, so as to avoid undesired fl ows of hot air.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
2.3.2 Manual operation: heating
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the heating symbol only or heating with heater symbol (if installed) comes on. In the latter case the electric heater is also used as a source of heat;
• Setting the set point (desired temperature) using the UP set point and DOWN set point buttons;
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the higher the speed).
The fan only starts if the temperature of the coil is high enough, so as to avoid undesired fl ows of cold air.
If the electric heater is installed the fan continues operating for 20 s even after it has been stopped. This time must also elapse even if the unit is switched off using the ON/OFF button.
Heating with heater (Fig. 2.p.b)
Heating without heater (Fig. 2.p.c)
2.3.3 Manual operation: dehumidifi cation (DRY)
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the dehumidifi cation symbol comes on;
• Setting the set point (desired temperature) using the UP set point and DOWN set point buttons;
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the fan operates at minimum speed.
The fan only starts if the temperature of the coil is low enough, so as to avoid unwanted fl ows of hot and humid air.
The e-drofan starts in cooling mode so as to bring the room temperature near to the set point (set point +
3 °C) using the set speed, then performs fan on/off cycles at minimum speed to remove the humidity.
2.3.4 Manual operation: fan
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly so that only the fan symbol (at the bottom of the display) and the corresponding bar are on;
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is set to medium.
The fan only starts if the ambient temperature is within the range of temperature 15 to 35 °C, so as to avoid undesired fl ows of hot or cold air.
2.3.5 Automatic operation
Once the device has been switched on using the ON/OFF button, proceed by:
• Pressing the MODE button repeatedly until the automatic symbol comes on;
• Setting the offset (from -2 to +2 °C) from the set point in automatic mode (25 °C, the fi nal set point thus ranges from 23 to 27 °C), using the UP set point and DOWN set point button
• Pressing the FAN button repeatedly to select the desired fan speed; if AUTO mode is selected the speed is decided by the electronic controller based on the deviation from the set point (the greater the deviation, the higher the speed).
The mode (heating or cooling) is decided by the electronic controller based on the deviation from the set point; if the room temperature is higher than the set point the control performs the cooling function while if it is lower it performs the heating function.
The fan only starts if the temperature of the coil is suitable to perform the heating or cooling functions.
If the network connection is present, the set point is decided by the manager of the installation; in these cases, the user can only increase or decrease the set point by 2°C to compensate for the different perception of the room temperature.
Fig. 2.p.b
Fig. 2.p.d
Fig. 2.p.e
Fig. 2.p.f
Fig. 2.p.c
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
15
2.3.6 Setting the clock and ON/OFF timer
e-drofan offers the possibility to perform programmed starts and stops if the room only needs to be air-conditioned at certain times of the day. To be able to use these functions, the internal clock needs to be set with the correct time, as shown below:
• Press the TIMER UP and DOWN buttons at the same time for 5 s (Fig. 2.p.g);
• Set the time using the TIMER UP and DOWN buttons (Fig. 2.p.h);
• Confi rm by pressing the SET button (see Fig. 2.p.i).
Important:
In the event of power failures, the clock setting will be lost and needs to be reset (the time is displayed correctly on the remote control), as does the ON/OFF timer. To reset the clock, clock send any command to the e-drofan.
Fig. 2.p.l
Fig. 2.p.n
Fig. 2.p.g
Fig. 2.p.m
Fig. 2.p.h
Fig. 2.p.i
The timer ON (start, Fig. 2.p.l) is set by:
• Pressing the TIMER ON button once;
• Setting the required start time with the TIMER UP and DOWN buttons;
• Confi rming the time with the SET button (the symbol is on steady and the current time is displayed).
The timer OFF (stop, Fig. 2.p.m) is set as for the timer ON, with the difference that the TIMER OFF button must be pressed.
The timer ON/OFF functions remain active even after the corresponding ON/OFF event has occurred; to disable these functions proceed as follows:
• Press the TIMER ON/OFF button;
• Press the clear button (the special symbol disappears).
2.3.7 Sleep operation
The SLEEP function is especially useful during the night-time, when the decrease in body temperature
(due to sleep) changes the perception of the room temperature.
In cooling mode the set point is increased by P18 for the number of hours set, after which the e-drofan returns to the previous situation (the SLEEP function is cancelled).
In heating mode the set point is decreased by the value of P19.
To set the sleep function, proceed as follows:
• Switch the device on using the ON/OFF button and select the operating mode;
• Press the SLEEP button repeatedly until setting the required number of hours for the function.
To cancel this function, proceed by pressing the SLEEP button again, after having waited 3 s since the button was last pressed, or pressing the button more than once until exceeding the maximum number of hours, that is, 9.
The SLEEP function can be combined with the timer OFF (see Fig. 2.p.n).
When the SLEEP function is active the brightness of the LED on the IR receiver board decreases.
2.3.8 Keypad lock
When the keypad lock symbol is present, only the ON/OFF function is enabled. To activate the lock, press the CLEAR button for 5 seconds, and to deactivate the function repeat the operation.
Fig. 2.p.o
16 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
2.3.9 Button and signal LED
The IR receiver board features a button for setting the operation if the remote control is not available (e.g. fl at batteries); pressing the button repeatedly changes the mode, in the following sequence: automatic, cooling, dehumidify, fan, heating, off. When setting the mode on the button the fan operates at minimum speed and the set point is equal to the value of parameter P01 (automatic mode set point, default= 25 °C).
Below is a list of the signals on the IR board:
Mode
OFF
COOL/DRY
HEAT
FAN
AUTOMATIC OFF
EXTRA FLUSH
Green LED
OFF
ON
OFF
ON
ON
ON
Yellow LED
OFF
ON
ON
OFF
OFF
OFF
Red LED
OFF
OFF
OFF
OFF
OFF
OFF
Table 2.f
2.3.10 Replacing the batteries
When the batteries are discharged or removed, all the settings are lost, and consequently the remote control needs to be reset according to the type of installation (heater fi tted, hydronic networks, fl ap fi tted, etc.).
In this case, proceed as follows:
• With the unit OFF, press the “Mode” and “clear” buttons at the same time for 5 seconds;
• A number of messages are displayed that correspond to the questions on the installation. Respond
YES or NO by pressing the or button and confi rming with the button set .
The settings are saved once the sequence of messages has been completed; if the procedure is not completed, all the modifi cations made are ignored.
If the information is not available, contact the relevant personnel (manager of the installation, installer..).
message meaning e-drofan model: for e-drofan HYFC****** respond NO.
Heater:
Yes: Present
No: Absent
Flap:
Yes: Present
No: Absent
Valve:
Yes: Present
No: Absent
2.3.11 Alarms
The IR receiver board uses the LED to signal the internal status, including any alarms (see the table below). Notify the maintenance personnel of the signal shown.
alarm none
EEPROM fault offl ine in CAN network room probe fault probe B2 or B3 fault window alarm circulating pump stop from digital input
Green LED Yellow LED Red LED
OFF
BLINK
ON
OFF
BLINK
OFF
OFF
BLINK
ON
BLINK
OFF
BLINK
ON
OFF
OFF
BLINK
ON
BLINK
ON
ON
ON
ON
ON
ON priority
5
6
3
4
1
2
7
Table 2.h
Hydronic network:
Yes: Present
No: Absent
Fan tile unit respond NO
Table 2.g
2.4 Additional functions
Air-conditioned rooms are normally subject to the phenomenon of air stratifi cation, due to the fact that the hot air moves upwards while the cold air moves downwards. To overcome this, the e-drofan runs fan on/off cycles (at minimum speed) once the temperature set point has been reached, so as to create a uniform room temperature. To ensure the correct measurement of the room temperature, the e-drofan runs a fan cycle for 30 s on power-up and whenever the mode is changed.
In automatic mode, this cycle is used to decide whether to heat or cool the environment.
If control is performed using the probe on the acqua terminal, these fan cycles are not performed.
2.5 Troubleshooting
Problem
The fan on one slave doesn’t start
The fan does not work at the set speed
The e-drofan does not switch on/off at the set time
Solution
The temperature of the coil may not be hot or cold enough, or alternatively the room temperature has already reached the set point. Wait; if the fan remains off for an extended period contact the relevant personnel.
The temperature of the coil may not be hot or cold enough, the initial fan cycle at minimum speed may be in progress, or alternatively the fan is operating so as to ensure a uniform temperature in the environment.
A power failure may have occurred.
Acqua terminal: reset the time and the TIMER ON/OFF or SLEEP function.
Remote control: press any button to reset the clock and the ON/OFF timer, SLEEP functions.
Table 2.7
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
17
Fig. 3.a.a
Fig. 3.a.b
Fig. 3.a.c
Fig. 3.a.d
Fig. 3.a.e
Fig. 3.a.f
Fig. 3.a.g
3. INSTALLATION
In summary:
• Easy confi guration by dipswitch;
• Creation of local networks (up to 5 slaves) without setting parameters or addresses (max 30 m);
• Possibility of control using the probe on board or the probe on the acqua terminal;
• Creation of extended networks (up to 1 km) with simple re-confi guration if the layout of the spaces is changed.
3.1 Introduction: e-drofan and accessories
The following section lists the family of devices made up of the e-drofan and its accessories: e-drofan control board HYFC00000*
Manages the fan on the fan coil and controls the temperature. Allows the connection of digital inputs for the remote control of functions such as ON/OFF, cooling/heating, economy etc. Fitted with a serial port for the network connection of a series of units.
Expansion card for e-drofan, HYVC000R0*
Allows the e-drofan to control additional loads to the fan, such as: bleed valves in the hot and cold water loops, circulating pump, power supply to the external relay for the heater and the hot and cold water requirement signal to the chiller/heat pump and boiler.
Analogue/relay output expansion board for e-drofan, HYVC000V*
Allows the e-drofan to control two actuators with 0 to 10 Vdc input (e.g. modulating valves… etc.) and control any additional loads using the two multifunction relays.
4 triac expansion board for e-drofan, HYVC000T*
Allows the e-drofan to control loads with a high number of operations (e.g. two modulating 3 point valves… etc.) using the 4 TRIAC outputs with voltage signal (230 Vac).
Triac/relay output expansion board for e-drofan, HYVC000M*
Allows the e-drofan to control loads with a high number of operations (e.g. a modulating 3 point valve… etc.) using the 2 TRIAC outputs with voltage signal (230 Vac) and directly control a 2 kW heater. A second multifunction relay is available for any additional loads.
IR receiver board for e-drofan HYIR00000*
Allows the e-drofan to receive the settings from the remote control, and displays, using 3 LEDs, the status of the unit and any alarms.
Fitted with a button for setting operation if the batteries are discharged.
Remote control for e-drofan HYHS00100*
Allows the user to control the operation of the e-drofan, including any slaves connected in the network.
The LCD ensures straightforward and user-friendly operation.
18 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
CANbus serial board for e-drofan HYSC00F0C0
Fitted on the e-drofan, this is used to create CANbus networks for centralised management and the application of advanced comfort and energy savings algorithms (integration with the chiller/heat pump or boiler).
Acqua” LCD terminal for e-drofan controller HYPA00100*
Allows the user to set the operation of the e-drofan (and any slaves connected in the network) and displays the alarms. The LCD ensures straightforward and user-friendly operation. In addition, it is fi tted with a probe that can be used for room temperature control.
Built-in “e-droset” LCD terminal for controlling the e-drofan, HYPA00300*
Ideal for wall mounting in the more commonly-used 3 gang switch boxes (Biticino, AVE, Vimar ... see the list in the corresponding paragraph). This allows the user to set the operation of the e-drofan (and any slaves connected in the network), display the alarms and air-condition the environment only if occupied
(occupancy function). The LCD ensures simple and user-friendly operation. The terminal also includes a probe that can be used to control the room temperature.
RS485 serial board HYSC00F0P0
Used to create customised (PlantVisor) or open (Modbus) supervisory systems.
Programming key PSOPZKEY00
Used to simply export the confi guration of the parameters from one e-drofan to another. Useful in systems with a large number of fan coils.
Programming key PSOPZKEYA0
Version with power supply.
Adapter for e-drofan programming key HYKA00000*
To be used together with the programming key PSOPZKEY*.
3.2 Type of fan coil and installation
The e-drofan electronic controller can control units featuring three fi xed fan speeds (motors with three windings), main and secondary heat exchangers. The expansion card can be used to manage the additional loads, such as: bleed valves in the hot and cold water loops, circulating pump, power supply to the external relay for the heater and the hot and cold water requirement signal to the chiller/heat pump and boiler. Consequently the e-drofan can be used in all types of installation (for home or similar use): 2 pipe,
4 pipe and 4 pipe with local 2 pipe loop.
For the thermodynamic features and the installation/maintenance of the fan coil, refer to the manual provided by the manufacturer.
Fig. 3.a.h
Fig. 3.a.i
Fig. 3.a.j
Fig. 3.a.k
Fig. 3.a.l
Fig. 3.a.m
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
19
3.3 Installation and basic settings
3.3.1 Mounting
The controller is mounted to the fan coil using 4 plastic turrets (manufactured by RICHCO, code SP1-
12-01) that slot into the holes on the four corners of the board, or alternatively using the special plastic supports on the specially prepared fan coils:
• dimensions (Fig. 7.a).
e-drofan dimension (Fig. 3.b.a).
e-drofan high accessories included (Fig. 3.b.b).
overall dimensions HYVC0*
Fig. 3.b.a
Fig. 3.b.b
HYVC0*
N NO4 N NO5
NO6 NO6 NO7 NO7
cold water hot water cold water contact hot water contact
DI5 B1 B2 B3
DIP
HYFC00000*
3.3.2 Connections
In summary:
• 5 digital inputs (3 can be confi gured);
• Voltage outputs for the fan;
• Optional outputs: 2 voltage outputs, 2 voltage-free contacts. Operation can be confi gured (heater, valves, circulating pump, contacts for hot/cold water request signal);
• 3 NTC probes;
• tLAN serial connection (max 5 slave, max 30 m);
• Optional CANbus serial connection (max 1 km);
• tLAN connection for remote acqua terminal (max 30 m, power supplied by e-drofan).
The user interface is represented by the remote control or the terminal (both cannot be used), in particular the latter contains a probe that can be used to control the room temperature; see the notes provided below the table of connections for the positioning of the terminal.
Some especially useful functions in certain installations (e.g. remote ON/OFF inside hotels etc.) are also available by digital inputs or via serial communication, as well as from the terminal or remote control.
Below is a diagram of the connections:
Humidity probe
HYIR0002*
serial communication
L L N N N NO3 NO2 NO1 GN Tx V+ GN Tx DI1 DI1 DI2 DI2 DI3 DI3 DI4 DI4
L N
remote
OFF summer/ winter
ECO SAFETY
HYPA0010*
HYFC00000*
GN Tx V+ GN Tx
slave1
HYFC00000*
GN Tx V+ GN Tx
HYFC00000*
slave2
.....
GN Tx V+ GN Tx
slave5
.....
20 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Key:
1
2
3
EXP
HYVC000T0*
SUPPLY
EXP
N No4 N No5 N No6
N No7
1
Fig. 3.b.d
DI5 B1 B2 B3
DIP
HYFC00000*
L L N N N No3 No
L N
multifunction voltage output (triac) multifunction 0 to 10 Vdc output multifunction relay output
EXP
HYVC000V0*
SUPPLY
EXP
GN No4 GN No5 No6 No6 No7 No7
2 3
Fig. 3.b.e
DI5 B1 B2 B3
HYFC00000*
DIP
L L N N N No3 No
L N
EXP
HYVC000M**
SUPPLY
EXP
2 A (res) 10 A (res)
N No4 N No5 No6 No6 No7 No7
1 3
Fig. 3.b.f
DI5 B1 B2 B3
DIP
HYFC00000*
L L N N N No3 No
L N
terminal meaning note e-drofan
L
N
NO1
NO2
NO3
GN, Tx, V+
GN, Tx
Phase
Neutral
Minimum fan speed (normally open).
Medium fan (speed normally open).
Maximum fan speed (normally open). tLAN: Connection to LCD terminal tLAN: Terminals for local network serial connection (master + 5 slave).
Power supply to the e-drofan and all the loads connected to the voltage outputs.
Max length: 5 m.
Cross-section: 14 to 22 AWG
Power supply to the e-drofan and all the loads connected to the voltage outputs.
Max length: 5 m.
Cross-section: 14 to 22 AWG
Max length: 5 m. Voltage output (L)
Cross-section: 14 to 22 AWG
Max length: 5 m. Voltage output (L)
Cross-section: 14 to 22 AWG
Max length: 5 m. Voltage output (L)
Cross-section: 14 to 22 AWG
Shielded cable: 3-wire + shield. Max length 30 m.
Cross-section: 14 to 22 AWG
Shielded cable: 3-wire + shield. Max length of the entire tLAN network: 30 m.
Cross-section: 14 to 22 AWG
Max length 30 m.
Inputs DI3, DI4, DI5 can be confi gured by parameters P43, P44, P45 (see section
“constructor”).
Polarity of DI2 can be confi gured by parameter P56.
Cross-section: 14 to 22 AWG
DI5 2= remote cooling/heating
3= multifunction: not used
4= multifunction: not used
5= multifunction: not used
Air intake probe (room) B1
B2
B3
DIP
Main indoor exchanger probe
Secondary indoor exchanger probe
Confi guration dipswitch: see paragraph “basic settings and functions available”.
EXP
FLAP
Connector for the expansion card (5-wire cable)
Connector for fl ap power supply (where present).
SUPPLY EXP Connector for e-drofan expansion power supply (connect using 2 wire cable).
IR Connector for the infrared receiver interface (5-wire cable). To be connected when using
JS3
SERIAL the remote control.
Connector for inserting optional power supply for compatibility with PCO serial cards.
Connector for inserting serial cards (connection to supervisory systems or local networks).
Max length 10 m. Control probe (if terminal or network connection absent, see dipswitch).
Max length 10 m
Max length 10 m
Maximum fl ap power supply cable length: 50 cm
Future uses e-drofan expansion
SUPPLY EXP Connector for e-drofan expansion power supply (connect using 2 wire cable).
EXP Connector for the expansion card (5-wire cable)
N
NO4
Neutral
Multifunction: Cold water solenoid valve power supply (when DIP4= ON, 4 pipe).
Multifunction: Local hot/cold water solenoid valve power supply (when DIP4= OFF, 2 pipe).
Multifunction: Hot water solenoid valve power supply.
NO5
NO6
Multifunction: Hot water solenoid valve power supply (when DIP4= ON, 4 pipe).
Multifunction: Water solenoid valve power supply, not used (when DIP4= OFF and DIP5=
OFF, 2 pipe).
Multifunction: heater (when DIP4= OFF and DIP5= ON).
Cold water free contact.
Cross-section: 14 to 22 AWG
Voltage output (L). Max length 5 m.
Cross-section: 14. to 22 AWG
Voltage output (L). Max length 5 m.
Cross-section: 14 to 22 AWG
Can be confi gured by parameter P40 if DIP4= OFF and DIP5= OFF.
No7 Hot water free contact.
Max length 30 m. If used to supply a load: max length 5m.
Can be confi gured by parameter P41.
Max length 30 m. If used for alimentary a load: max length 5m.
Cross-section: 14 to 22 AWG
Can be confi gured by parameter P42.
Table 3.a
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
21
22
4 triac expansion board for e-drofan, HYVC000T* terminal meaning
SUPPLY EXP Power supply connector (connect to e-drofan via 2 wire cable)
EXP E-drofan signal input connector (use 5 wire cable)
N
No4
No5
Neutral
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P39)
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P40)
No6
No7
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P41)
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P42) notes
Cross-section: 14 to 22 AWG
Cross-section: 14 to 22 AWG
Max. length 5 m
Cross-section: 14 to 22 AWG
Max. length 5 m
Cross-section: 14 to 22 AWG
Max. length 5 m
Cross-section: 14 to 22 AWG
Max. length 5 m
Analogue/relay output expansion board for e-drofan, HYVC000V* terminal meaning
SUPPLY EXP Power supply connector (connect to e-drofan via 2 wire cable)
EXP E-drofan signal input connector (use 5 wire cable)
GN
No4
Signal reference terminal
Multifunction 0 to 10 Vdc output: see the manufacturer section
(confi gurable by parameter P39)
No5
No6
No7
Multifunction 0 to 10 Vdc output: see the manufacturer section
(confi gurable by parameter P40)
Multifunction relay output: see the manufacturer section (confi gurable by parameter P41). Voltage-free contact
Multifunction relay output: see the manufacturer section (confi gurable by parameter P42). Voltage-free contact notes
Cross-section: 14 to 22 AWG
Cross-section: 14 to 22 AWG
Max. length 5 m
Keep separate from the power cable
Cross-section: 14 to 22 AWG
Max. length 5 m
Keep separate from the power cable
Cross-section: 14 to 22 AWG
Voltage-free contact: 30 m
Load power supply: 5 m
Cross-section: 14 to 22 AWG
Voltage-free contact: 30 m
Load power supply: 5 m
Triac/relay output expansion board for e-drofan, HYVC000M* terminal
No4
No5 meaning
SUPPLY EXP Power supply connector (connect to e-drofan via 2 wire cable)
EXP E-drofan signal input connector (use 5 wire cable)
N Neutral
TRIAC output with voltage signal, multifunction: see the manufacturer section (confi gurable by parameter P39)
TRIAC output with voltage signal, multifunction: see the manu-
No6 facturer section (confi gurable by parameter P40)
Multifunction relay output, 10 A resistive: see the manufacturer section (confi gurable by parameter P41). Voltage-free contact notes
No7 Multifunction relay output: see the manufacturer section (confi gurable by parameter P42). Voltage-free contact
Cross-section: 14 to 22 AWG
Cross-section: 14 to 22 AWG
Max. length 5 m
Cross-section: 14 to 22 AWG
Max. length 5 m
Cross-section: 14 to 22 AWG
Voltage-free contact: 30 m
Load power supply: 5 m
Cross-section: 14 to 22 AWG
Voltage-free contact: 30 m
Load power supply: 5 m
Size the power and connection cables to the voltage output loads based on the current input (the maximum current input of the network must not exceed 6 A).
Maximum serial board communication cable length: see the section on “technical info” or the corresponding instruction sheet.
If a local network (tLAN) is created and the remote control is used (the LCD terminal must not be fi tted), on the master (between terminals GN and V+) insert the 1.3 kOhm resistor, supplied. This operation assigns the corresponding e-drofan the role of master, and the receivers on the other e-drofans connected to the master tLAN will automatically be deactivated.
Warnings: All installation and maintenance operations must be carried out with the unit off;
Serial connections: do not use star connections (use chain connections, see the paragraph “tLAN and
Broadcast networks”). Connect the shield to terminal GN;
Avoid short-circuits between pins GN and V+ (power supply to the LCD terminal);
Adopt precautions against electrostatic discharges when handling the boards;
Do not earth terminal GN, as this may damage the instruments in the event of network connection.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
3.3.3 Basic settings and functions available (dip-switch)
The dipswitches on the fan coil board can be used to select the predefi ned settings relating to the type of fan coil and installation. Each input/output can nonetheless be reconfi gured so as to guarantee greater fl exibility; in this case (as for the advanced functions) the terminal needs to be used to modify the parameters. To perform this operation, enter the special password (refer to section “constructor”).
Set the dipswitches as follows:
1 ON=
2 ON=
3 ON=
4 ON=
5 ON=
6 ON=
Enable heat/cool functions (probe B2 on coil). Probe B3 enabled only when DIP1= ON and
DIP4= ON;
Enable remote cooling/heating digital input (DI2);
Enable remote off (some functions are disabled: timer ON, timer OFF, sleep. The operating mode is forced to “auto”);
For 4-pipe fan coils (OFF=2 pipe);
Electric heater present (when DIP 4=ON the setting is ignored and the heater is not enabled);
Control performed using the probe inside the terminal, if OFF probe B1 is used.
3.3.4 Programming key (copy the confi guration)
Once having set the parameters, the confi guration can be quickly copied to other e-drofan controllers using the programming key. Proceed as follows:
1. Switch off the previously programmed e-drofan (source);
2. Set the dipswitches inside the programming key (underneath the battery cover) to reading mode (dip
1= OFF, dip2= OFF );
3. Insert the key in the special 4 pin connector on the adapter, and connect the 8-wire cable supplied (see
Fig. 3.18);
4. Disconnect the 8-wire cable on the IR receiver board (if present) from the e-drofan;
5. Insert the 8-wire cable from the programming key adapter to the IR connector on the e-drofan board
(source), see Fig. 3.19;
6. Press the button. The red LED and then the green LED come on in succession, if the operation has been completed with success. Other signals indicate problems (refer to the corresponding instruction sheet);
7. Remove the key and the adapter; set the dipswitch to write mode (dip 1= OFF, dip2= ON ) and repeat steps 3, 4, 5, 6 to write the data to the target e-drofan;
8. Once having completed the sequence reconnect the IR receiver board on the source and target edrofan.
Important: To avoid of excessively draining the batteries in the programming key, disconnect the normally closed digital inputs on the e-drofan. If this is not possible, use the key with the power supply. The e-drofan parameters (source) can be copied to devices with the same software version or lower.
3.3.5 LCD terminal
Avoid installing the terminal in places where the ambient temperature measurement may be altered: outside walls, near doors leading to the outside, exposed to the sun, etc. (the terminal should be fastened to the wall in a horizontal position so as to allow the recirculation of air through the slits on the rear cover fastened to the wall). The terminal is fi tted inside the plastic case and is only accessible by removing the front cover (see the following fi gure).
Mounting the terminal
1. bottom view opening tab;
2. fastening holes.
HYFC0*
Fig. 3.d
ingombro sc
Fig. 3.e
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
23
Fig. 3.h
Connect the terminal and the e-drofan as shown in the fi gure on the side.
If the temperature measured by the internal probe needs to be corrected (e.g. due to installation in a less than optimum position), a set number of degrees centigrade can be added or subtracted. For these settings see section “constructor”, under the paragraph on “probes”.
Dimensions
Fig. 3.i
Fig. 3.j
3.3.6 e-droset
Avoid placing the terminal in places where the room temperature measurement may be altered: outside walls, near doors leading outside, exposed to the sun, near the fan coil etc. The terminal is located inside the plastic case and is accessible using a screwdriver.
Below is the sequence of operations for wall mounting:
• fasten the 3 gang support to the box for built-in installation using two screws;
• make the connections between the terminal and the wires in the shielded cable from the e-drofan. terminal meaning
GN (3)
Tx (2)
V+ (1) use for connection to terminal GN on the e-drofan and the shield in the shielded cable use for connection to terminal Tx on the e-drofan use for connection to terminal V+ on the e-drofan
Maximum length of the shielded connection cable: 30 m from the e-drofan;
• insert the terminal in the plastic support;
• insert the fastening “shoulders”;
• position the wallplate on the support.
The following wallplates can be used: BTicino Living International; Light; Light Tech; Matix VIMAR Idea;
Idea Rondò; Plana.
The Living International - Light Tech - Matrix brands are the property of BTicino SpA. The Idea - Idea
Rondò - Plana brands are the property of VIMAR SpA.
If the local network (tLAN) is used, the terminal assigns the role of master to the fan coil connected.
Warnings:
• all installation and maintenance operations must be carried out with the unit off;
• adopt precautions against electrostatic discharges when handling the board.
Fig. 3.k
Fig. 3.l
24
The diagram in Fig. 3.k describes the connections to be made to the e-drofan board.
If the temperature measured by the internal probe needs to be corrected (e.g. due to installation in a less than optimum position), a set number of degrees centigrade can be added or subtracted. For these settings see section “constructor”, under the paragraph on “probes”. e-drofan - +030221266 - rel. 3.6 del 26.04.2010
3.3.7 Installing the modulating valves (3 point and 0-10V, with thermal actuator)
The e-drofan can control modulating valves using a P+I algorithm, see the “manufacturer“ section for the appropriate confi guration of the parameters.
3.3.8 Protection against electric shock and maintenance warnings
Important:
The system made up of the control board (HYFC0*****) and the other optional cards (HYVC000R0*,
HYPA******, HYIR******, HYSC00F0C*, pCO serial cards etc.) represents a control device to be incorporated in class I or II appliances.
The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect the power supply before working on the board during assembly, maintenance, replacement and confi guration. The protection against short-circuits must be guaranteed by the manufacturer of the appliance that the control device in integrated into or by the fi nal installer.
3.3.9 Broadcast networks
In summary:
• Basic broadcast networks (max 5 slaves, max 30 m);
• Extended broadcast networks (up to 1 km, max 100 units) using the CANbus board;
• Simple reconfi guration from extended broadcast to hydronic system.
The network connection is used to simplify the operation of installations with multiple fan coils. For smaller environments, the tLAN can be used to create a small local network (basic broadcast) made up of a master and a maximum of 5 slaves (maximum total length: 30 m). In this case, the information is sent in one direction only: from the master to the slaves; all the settings on the master (the only unit fi tted with the terminal) are applied to the slaves. By setting DIPSWITCH 6 on the master to ON, all the fan coils perform the control functions using the probe on the terminal, while if set to OFF, each fan coil performs the control functions using its own internal probe B1.
tLAN networks can also be created using the remote control as the user interface; in this case, the e-drofan master must be fi tted with the IR receiver board and the resistor supplied must be connected between pins GN and V+.
Notes:
• A slave unit, disconnected from the network for at least 8 seconds, is automatically switched off;
• The panel only displays the status of the master;
• The slave alarms are managed locally and independently;
• If using the remote control, each fan coil performs the control functions using its own probe;
• The settings of the dipswitches present on the slave are ignored;
• The digital inputs on the slaves are disabled, with the exception of the ON/OFF and window alarm input;
• The parameters on a slave can be modifi ed by disconnecting the network and connecting the terminal.
Once the network is restored, the slave maintains the modifi cations (unless these concern the settings overwritten by the network);
• The following settings are sent by the master to the slaves: ON/OFF, mode (e.g. heating ..etc.), fan speed, SLEEP function, On/Off timer, set point, control probe (if DIP 6 on the master is ON).
Example of basic broadcast network
Fig. 3.m
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
25
To cover distances greater than the 30 m (up to 1 km in total) or connect more slaves, CANbus communication is required, using the serial board code HYSC****** (on each controller).
The following fi gure shows an example of an extended/multi-zone broadcast connection.
Fig. 3.o
Fig. 3.n
The features of the CANbus connection are the following:
• Maximum number of units connected: 100;
• Maximum number of masters: 15;
• Maximum number of slaves: subtract the number of masters from 100;
• Maximum number of slaves for each master: all slaves available;
• Maximum length of the CANbus (total): 1 km with low communication speed (65 kbit); 500 m with high communication speed (125 kbit);
• Connection cable: Shielded cable, 2 wire + shield;
• Connect the two 120 ohm resistors to the ends of the CANbus (between terminals H+ and H-).
The behaviour is the same as in the case of the tLAN. The master has the control panel and sends all the slaves the status to be repeated.
Each controller must be fi tted with a serial board and each slave must have the same address as the master it serves.
The serial address is set on the group of 10 dipswitches located on the serial board (dips 1 to 7), see the following fi gure (Fig. 3.n).
26
In the extended broadcast, the available addresses range from 1 to 15; setting 0 allows the address to be entered from the acqua terminal (see the section on “advanced settings”), in this way the system can be reconfi gured by simply connecting the terminal.
An extended broadcast installation can be easily converted to a hydronic system by modifying the serial addresses and setting a few parameters (see the section on “advanced settings” and “hydronic systems”).
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
The following table shows the settings required to confi gure the corresponding addresses (binary notation):
Dipswitch setting
ON
Address associated
Default=1 (serial address set from the acqua terminal)
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
1
2
ON
1 2 3 4 5 6 7 8 9 10
3
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
4
5
6
7
8
9
10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
11
12
13
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
14
15
Table 3.b
Dipswitches 9 and 10 are used to set the communication speed on the CANbus and must be both set in the same position.
dip 9 and 10 ON= 125 kbit/s dip 9 and 10 OFF= 62.5 kbit/s dip 8= must always remain ON for the use of the serial board on the e-drofan.
After each variation made to the position of the dipswitches, the e-drofan must be switched off and on again to make the changes operational.
The serial board is fi tted with three LEDs to display the operating status. The green LED indicates that the serial board is on (power from the e-drofan) while the yellow and red LEDs indicate the serial communication status. When starting, the two LEDs (red and yellow) come on together, in normal communication fi rst the red LED goes off, then the yellow LED, and fi nally the yellow LED (data reception in progress) or red LED (data transmission in progress) starts fl ashing. If both the LEDs are off steady communication is interrupted (the red LED continues fl ashing on the master).
Yellow LED
ON
ON
OFF fl ashing
OFF
Red LED
ON
OFF
OFF
OFF fl ashing meaning starting sequence in progress starting sequence in progress communication interrupted data reception in progress (slave) data transmission in progress (master)
Table 3.c
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
27
3.3.10 Procedure for testing the installation and alarms
Once the installation has been completed, the test procedure can be run to check the devices. The terminal is required for these functions. To enter test mode press the UP and DOWN buttons for 10 seconds with the unit connected to the power supply and in off status; the event is signalled by the buzzer, which emits a beep.
The test proceeds in steps, indicated on the terminal by the message “L” followed by an incremental number; pressing the UP button proceeds to the next step (signalled by the BEEPING of the buzzer).
After the last step, the procedure ends and the controller returns to normal operation.
step part in question
“L01” probe B1
“L02” probe B2
“L03” probe B3
“L04” digital input 1
“L05” digital input 2
“L06” digital input 3
“L07” digital input 4
“L08” digital input 5
“L09” fan
“L10” fan
“L11” fan
“L12” expansion output NO4
“L13” expansion output NO5
“L14” expansion output NO6
“L15” expansion output NO7 message fl ashing probe error probe error probe error input open input open input open input open input open message not fl ashing probe Ok probe Ok probe Ok input closed input closed input closed input closed input closed on at minimum speed, no internal check on at medium speed, no internal check on at maximum speed, no internal check output activated, voltage present (L). No internal check output activated, voltage present (L). No internal check output activated, contact closed. No internal check output activated, contact closed. No internal check
Table 3.d
During operation (as well as during the test procedure), the device may generate alarm signals displayed on both the IR receiver board and on the terminal.
The alarms are shown in section “constructor”.
28 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4. ADVANCED SETTINGS
In summary:
• General functions: inlet water temperature control;
• Algorithm to overcome the phenomenon of air stratifi cation;
• Manual operation: cooling, heating (heater management, if present), dehumidify, fan;
• Automatic operation (heater management, if present);
• Set point compensation based on the outside temperature;
• occupancy: possibility to use a second set point if the environment is not occupied (energy savings);
• control of modulating valves: three point or with 0 to 10 Vdc input.
The e-drofan provides a number of additional functions compared to traditional controllers: 5 digital inputs that can be confi gured, 3 probes, 1 dipswitch for rapid customisation on site, possibility of tLAN network connection and advanced control algorithms.
The e-drofan comes with a family of accessories (see the description in section “installer”) including: the acqua terminal (with NTC probe on board) or the remote control with corresponding receiver board, the expansion card with 4 relay outputs and the CANbus serial board for creating hydronic systems; as an alternative to the latter accessory, the 485 serial board can be installed to create customised (PlantVisor) or open (Modbus) connectivity solutions.
The following section shows, in sequence, the description of the parameters, from the confi guration of the I/O to the setting of the control algorithms. The list of parameters is shown at the end of the section.
Important: avoid parameter settings that create situations of confl ict (for example, do no not confi gure 2 digital inputs on the same e-drofan for economy operation).
4.1 Confi guration of the I/O and installer custom settings
The inputs and the outputs can be confi gured by parameter, thus giving the manufacturer complete freedom in choosing the available functions, while at the same time the installer can simply make the custom settings relating to the installation in progress (2 pipe, 4 pipe, etc.) using the dipswitches (see section “installer”).
The parameters may be set from: the acqua terminal, the programming key and the serial connection.
The following section shows some examples that help describe the controllable loads (fan, valves, heater etc.) and the corresponding confi guration of the parameters.
Example of fan coil installation in two pipe system:
Fig. 4.a
4.1.1. Modifying parameters
To display and modify the parameters, enter editing mode by pressing, with the device OFF, the mode and clear buttons for 5 seconds (password 22) and then entering the second password for parameter
P92 (password 66). To restore the default values, set parameter P91 to the value 44 (with the device
OFF).
Fig. 4.b.a
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Fig. 4.b.b
29
Fig. 4.b.c
input
DI1
DI2
DI3
DI4
DI5 probe description
B1
B2
B3
BT
Air intake probe/Outside air probe (compensation)
Main indoor exchanger probe
Secondary indoor exchanger probe/Outside air probe (compensation)
Probe inside the terminal
4.1.2 Probes
The probe readings are affected by the position of the fan coil (on the wall or the fl oor), due to the phenomenon of air stratifi cation. To overcome this problem, different offsets can be specifi ed, depending on the operating mode (heating or cooling). Faults with the control probe or one of the probes on the two exchangers will stop the fan and close the valve. By default the use of the probes must be set by dipswitch, nonetheless for the use of modulating valves and the P+I function, the probes can be set directly by parameter (the parameters must be set for all the probes and P95=1).
related parameters
P22, P58, P59, P60, P61
P62, P63
P22, P64, P65 notes
When DIP6 is OFF and P22=0: room control probe.
Enabled when DIP1= ON
Enabled when DIP1= ON and DIP4= ON
When DIP6 is ON = Room control probe.
Table 4.a.a
par
P15
P16
P17
P22
P58
P59
P60
P61
P62
P63
P64
P65 unit of measure def
0
°C/10
°C/10
°C/10
°C/10
°C/10
°C/10
°C/10
°C/10
0
0
0
0
0
0
3
0
0
0
0
0
0
0 min
0
-99
-99
-99
-99
-99
-99
-99
-99
5
5
2 max
5
127
127
127
127
127
127
127
127 setting function
Use probe B1
0= Use defi ned by dipswitch and P22
1= probe disabled
2= Cold/hot water coil probe
3= Cold water coil probe
4= Hot water coil probe
5= Control probe (WITH DIP6=OFF)
Use probe B2
See P15
Use probe B3
See P15
0= compensation disabled
1= B1 outside air probe (compensation enabled)
2= B3 outside air probe (compensation enabled)
When P15, P16, P17 is other than 0, compensation disabled probe B1 offset in cooling/dehumidify probe B1 offset in heating probe B1 offset in automatic probe BT offset as room control probe probe B2 offset in cooling/dehumidify probe B2 offset in heating probe B3 offset in heating probe B3 offset in cooling/dehumidify compensation (see corresponding paragraph)
Table 4.a.b
par
P43
P44
P45 description
ON/OFF input related parameters
4.1.3 Digital inputs
Digital inputs DI1 and DI2 have a fi xed confi guration, while the remaining inputs can be confi gured by parameter. The off status of the digital input has priority over the signals received via the serial communication, so as to allow the user (directly affected by the fl ow of cold or hot air) to switch the fan coil units off. notes when the input is closed the unit is off (even in the event of network connection). In the transition from OFF->ON the e-drofan is started, but may subsequently be switched off from the terminal or via serial connection. In the off status, the valve is closed and the fan is stopped (after any post-ventilation phase required for the heater).
Enabled when DIP2= ON
0
0 cooling/heating multifunction multifunction multifunction def
0
P43
P44
P45
Table 4.b.a
setting function
0= input disabled
1= economy (normally open)
2= window alarm (normally open) vary the set point (cooling= increase, heating= decrease) stop fan and close the valve
3= occupancy (normally open)
4= circulating pump alarm (normally open)
5= local stop (generic alarm, normally open)
6= economy (normally closed) keep the fan coil ON for half an hour stop fan and close the valve stop fan and close the valve
7= window alarm (normally closed)
8= occupancy (normally closed)
9= circulating pump alarm (normally closed)
10= local stop (normally closed) see P43 see P43
-
-
Table 4.b.c
The management of the occupancy input is described in the paragraph on the occupancy function.
The Economy function is the same as the sleep function, with the difference that it is activated/deactivated by digital input.
30 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4.1.4 Outputs
output
No1
No2
No3
No4
No5
No6
No7 description
Voltage output (L) for minimum fan speed winding.
Voltage output (L) for medium fan speed winding
Voltage output (L) for maximum fan speed winding.
Multifunction voltage (see DIP4)
Multifunction voltage (see DIP4 and DIP5)
Multifunction voltage
Multifunction voltage
-
-
related parameters
P39
P40
P41
P42
-
-
note e-drofan expansion e-drofan expansion e-drofan expansion e-drofan expansion
Table 4.c.a
par.
def.
setting
P39 5 When P95=0 the output is set by dipswitch (with dip 4 OFF the parameter is forced to 5, dip 4 ON the parameter is forced to 1). If P95=1 the output is settable by P39, the traditional heater can only be used when dipswitch= 1
0= Output disabled;
1= Cold water valve (normally open);
2= Hot water valve (normally open);
3= Chiller trigger, cold water request (normally open). Contact closed with cold/hot water valve or cold water only active (open with valve deactivated);
4= Boiler trigger, hot water request (normally open). Contact closed with cold/hot water or hot water valve only active (open with valve deactivated);
5= Cold/hot water valve (normally open). Activated with the cooling/heating request from the controller. Off when both are deactivated;
6= Heater (normally open) (set parameters P46 and P13);
7= Alarm (normally open);
8= Circulating pump (normally open). Activated when one of two valves, hot or cold water, opens. Off when are both deactivated.
9= 3-point valve + (clockwise) for cold water (hot/cold water if dip4= OFF). *
10= 3-point valve - (anticlockwise) for cold water (hot/cold water if dip4= OFF). *
11= 3-point valve + (clockwise) for hot water (deactivated if dip4= OFF). *
12= 3-point valve - (anticlockwise) for hot water (deactivated if dip4= OFF). *
P40
P41
0
3
P42 4
P95 0
13= Valve with 0 to 10 Vdc input for cold water (hot/cold water if dip4= OFF). *
14= Valve with 0 to 10 Vdc input for hot water (deactivated if dip4 = OFF). *
15= Reserved for future use
16= Reserved for future use
17= Output 0 to 10 Vdc for modulating heater control (by external module). Set parameters P111, P116. *
18= Output (triac or relay) for ON/OFF heater management (with hysteresis) on P+I. Set parameters P111, P112. *
If P95=0 the output is set by dipswitch (if dip 4 is OFF the parameter is set to 0, dip 4 ON the parameter is set to 2). When dip 4 is OFF and dip 5 is ON the parameter is set to 6, that is, heater output. If P95=1 the output can be set by P40, in any case the heater cannot be used when dip4= ON. For the other settings see P39
Vedere P39
Vedere P39
0=outputs No4 and No5 set by dipswitch 4
1=outputs No4 and No5 can be set by parameter P39 and P40 (set to 1 to enable the modulating outputs, P+I algorithm)
Table 4.c.b
* The P+I parameters need to be set, see chap. 4.2.10.
summary table of the e-drofan options
Set P39, P40, P41, P42
With P95=0 the output is set by dipswitch (with dip 4 OFF the parameter is forced to 5, dip 4 ON the parameter is forced to
1). If P95=1 the output is settable using P39
0= Output disabled
1= Cold water valve (normally open)
2= Hot water valve (normally open)
3= Chiller activation signal, cold water request (normally open).
Contact closed with cold/hot water valve or cold water only active (open with valve deactivated)
4= Boiler activation signal, hot water request (normally open).
Contact closed with cold/hot water valve or hot water only
(open with valve deactivated)
5= Cold/hot water valve (normally open). Activated with the cold or hot water request from the controller. Off when are both deactivated
6= Heater (normally open); Select e-drofan option based on the current request on the relay: 2 Aac or 10 Aac
7= Alarm (normally open)
8= Circulating pump (normally open). Activated when either the hot or cold water valve opens. Off when are both deactivated
9= 3-point valve + (clockwise) for cold water (hot/cold water if dip4=OFF). Use e-drofan 4 triac or triac/relay (triac outputs only) option*
10= 3-point valve - (anticlockwise) for cold valve (hot/cold water if dip4=OFF). Use e-drofan 4 triac or triac/relay (triac outputs only) option*
11= 3-point valve + (clockwise) for hot water (deactivated if dip4 =OFF). Use e-drofan 4 triac or triac/relay (triac outputs only) option*
12= 3-point valve - (anticlockwise) for hot water (deactivated if dip4 =OFF). Use e-drofan 4 triac or triac/relay (triac outputs only) option*
4 relay exp. HYVC000R0* 4 relay exp. HYVC000T0*
No4 No5 No6 No7 No4 No5 No6 No7 No4
0 to 10 Vdc exp.
HYVC000V0*
No5 No6 No7 No4
Triac/relay exp.
HYVC000M0*
No5 No6 No7
(rel. volt)
(rel. volt)
(rel) (rel) (triac volt)
(triac volt)
(triac volt)
(triac volt)
(0 to
10 V)
(0 to
10 V)
(rel) (rel) (triac volt)
(triac volt)
(rel 10
A)
(rel)
P39 P40 P41 P42 P39 P40 P41 P42 P39 P40 P41 P42 P39 P40 P41 P42
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
31
13= Valve with 0 to 10 Vdc input for cold water (hot/cold water if dip4=OFF). Use e-drofan 0 to 10 V/relay option*
14= Valve with 0 to 10 Vdc input for hot water (deactivated if dip4 =OFF). Use e-drofan 0 to 10V/relay option*
15= Reserved for future use
16= Reserved for future use
17= 0 to 10 Vdc output for control of modulating heaters (by external module). Set parameters P111, P116*
18= Output (triac or relay) for management of ON/OFF heaters
(with hysteresis) on P+I. Set parameters P111, P112*
Below is a possible example for 0/10V modulating actuators on 4 pipe fan coils with heating/cooling request:
Analogue output option HYVC000V**:
• output No4: P39= 13 modulating 0 to 10 V cold water valve output;
• output No5: P40= 14 modulating 0 to 10 V hot water valve output;
• output No6: P41= 3 cooling request;
• output No7: P42= 4 heating request.
Do not set modulating and non-modulating outputs at the same time (e.g. P39=1, P40=16 or P39=6 and
P40=17 etc.), as with modulating actuators control is P+I (when suitably confi gured); in any case, the following outputs can still be used: chiller activation signal, boiler activation signal and alarm. Only one output can be set as a heater.
2 pipe (active probe: B2)
4 pipe (active probes: B2,B3)
4.1.5 Dipswitches and type of installation
main coil
Functions available: cooling / heating (local hot/cold water valve)
Functions available: cooling (cold water valve) secondary coil
Functions available: heating (hot water valve) dipswitches
DIP4= OFF
DIP1= ON
DIP4= ON
DIP1= ON
Tab. 4.d
In the case of 4 pipe installations, the main and secondary coil valves are never open at the same time, and the heater is disabled.
par unit of
P12
P13
P14 measure
°C
°C/10
°C
P51 min
P52 min def min max setting
21
0
0
37
10
0
0
0
0
0
255 Temperature to enable the fan in heating, automatic heating
255 Hysteresis to enable the fan in heating/automatic heating, cooling, automatic cooling
255 Temperature to enable the fan in cooling/automatic cooling
255 Local valve, hot/cold water valve opening time
255 Local valve, hot/cold water valve closing time
Table 4.8
In case of installations where the fan coils are used in stand-alone mode, the controller cannot know in advance the value of the temperature of the water contained in the loop, the probes being in the coil therefore afterwards the valves. After a series of attempts at fi xed time intervals, it is possible to detect the temperature through the parameter P51 setting, minimum opening time, and P52, preset waiting time.
A series of attempts are performed to activate the hot/cold water valve until the exchanger reaches the temperature required to activate the fan (cool/heat enable), in which case the cycle of attempts is reset.
The hot/cold water valve is activated for the time equal to P51 and remains off respectively for the time
P52 after the fi rst attempt, for P52-5 minutes after the second attempt, for P52-10 minutes after the third attempt, off for P52 x 2 after the fourth attempt; following the four attempts the cycle restarts from point
2 (valve OFF for P52 - 5 minutes).
4.1.6 Method for testing the installation
See section “installer”.
32 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4.2 Control algorithms
In summary:
• General functions: Heat enable, Cool enable, Flush, Extra fl ush, autofan, continuous ventilation;
• Manual operation: cooling, heating (heater management, if present), dehumidify, fan;
• Automatic operation (heater management, if present);
• Set point compensation according to the outside temperature;
• Timer ON/OFF and SLEEP function;
• P+I control algorithm for modulating valves.
Below is a description of the operation of the e-drofan, divided into general functions, manual and automatic functions.
4.2.1 General functions: heat enable (heating/automatic heating)
In order to avoid undesired fl ows of cold air, the fan is only operated if the temperature of the main coil (probe B2) is high enough. If this condition is not satisfi ed the heating symbol fl ashes. DIP1 must be set to ON. The fan speed allowed (limiting the request by the control algorithm) is described in the following graph.
par.
def.
min.
max. unit of measure
P10
P11
P12
P13
P55
29
33
37
10
0
0
0
0
0
0
255
255
255
255
1
°C
°C
°C
°C/10 setting
Temperature to enable minimum fan speed in heating/automatic heating
Temperature to enable medium fan speed in heating/automatic heating
Temperature to enable maximum fan speed in heating/automatic heating
Fan activation hysteresis (heat enable/cool enable)
0 = Display heating or cooling symbols in automatic mode: deactivated
1 = Display heating or cooling symbols in automatic mode: activated
Table 4.e
If the fan is disabled by the heat enable function, the heating symbol fl ashes (the heater remains on) as a signal to the user. After the hot/cold water valve or hot water valve only is closed, the fan is stopped.
The heat enable function must be disabled when using modulating actuators (3 way valves … etc).
4.2.2 General functions: cool enable (cooling/ automatic cooling, dehumidify
In order to avoid undesired fl ows of hot air, the fan is operated only if the temperature of the coil is low enough. If this condition is not satisfi ed the cooling symbol fl ashes. The DIP1 must be set to ON. The fan speed is managed by the control algorithms or set manually.
par.
def.
min.
max.
unit of measure
P13
P14
P55
10
21
0
0
0
0
255
255
1
°C/10
°C setting
Fan activation hysteresis (heat enable/cool enable)
Temperature to enable fan in cooling, automatic cooling and dehumidify
0= Display heating or cooling symbols in automatic mode: deactivated
1= Display heating or cooling symbols in automatic mode: activated
Table 4.f
If the fan is disabled by the cool enable function, the cooling symbol fl ashes as a signal to the user. After the hot/cold water valve or cold water valve only is closed, the fan is stopped. The cool enable function must be disabled when using modulating actuators (3 way valves … etc).
1 max.
P10 P11 P12 medium
P13 min.
P13
OFF
P13
Fig. 4.c
Key:
1. speed allowed;
2. OFF main exchanger temperature (probe B2).
1
P14
ON
OFF
P13
Fig. 4.d
Key:
1. fan status;
2. main exchanger temperature (probe B2).
2
2 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
33
min.
OFF
P32 P33 P32
Fig. 4.e
P33
4.2.3 General functions: Flush (fan on/off cycles)
To overcome the phenomenon of air stratifi cation, the e-drofan operates fan on/off cycles at minimum speed, even when the room temperature has reached the set point (the local/hot/cold valve remains closed). This helps ensure the correct measurement of the room temperature if the probe on the acqua terminal is not used (control probe B1). If control is performed by probe BT, the fl ush function is disabled.
The behaviour can be modifi ed depending on the operating mode: heating, cooling, dehumidify or automatic. The fan is started after a period of inactivity (due to the set point having been reached or the heat enable or cool enable functions), equal to the value of parameter P32.
The local/hot/cold valve should be installed to use the fl ush function.
par.
def.
min. max. unit of measure
P34 0 0 3
P32
P33
2
90
0
0
255
255
min
s setting
0= Function disabled;
1= Flush function active in cooling, dehumidify and automatic OFF.
2= Flush function active in heating and automatic OFF.
3= Flush function active in heating, cooling, dehumidify and automatic OFF.
0= Flush disabled
>0: Period of fan inactivity (due to the control or fl ush function)
0= Flush disabled
>0: Fan duration
Table 4.g
4.2.4 General functions: Extra Flush
This function ensures correct operation when the acqua terminal is not fi tted (control probe B1), overcoming the phenomenon of air stratifi cation.
Whenever switching from OFF->ON or changing operating mode, the e-drofan runs a fan cycle at minimum speed (for the time P35) to make sure the room temperature is uniform.
At the end of this interval, normal operation resumes. This is especially useful in the event of automatic operation. It is deactivated if probe BT on the terminal is used for the control functions.
The local/hot/cold valve should be installed to use this function.
1 2 set point max.
P09 medium
P09 min.
OFF
P09 P09
Key:
1. heating (winter);
2. cooling (summer)
3. room temperature.
P08 P07
Fig. 4.f
P07
P09
P08
P09
3
4.2.5 General functions: Autofan (fan speed selection based on the room temperature)
The Autofan function establishes the fan speed when this is not set manually by the user.
In cooling and heating mode the speed is higher the more the room temperature deviated from the set point (including automatic cooling, automatic heating). In fan mode the speed is fi xed at the medium value for the range set by parameters P30, P31, P06 (see the paragraph below). In dehumidify mode the speed is fi xed at the minimum value.
par.
def.
min.
max. unit of
P07 7 0 measure
255 °C/10
P08 7
P09 5
0
0
255
255
°C/10
°C/10 setting
Deviation of the room temperature from the set point above which the fan is activated at medium speed
Deviation of the room temperature from the set point above which the fan is activated at maximum speed
Hysteresis of the room temperature-set point deviation
Table 4.h
4.2.6 General functions: Continuous ventilation
If required, the fan can be activated in permanent mode; the fan speed is set by the user even when the room temperature has reached the set point (in AUTOFAN the speed is set to the minimum value). The heat cool enable functions have no effect. parameter
P29 setting
0= Continuous ventilation deactivated.
1= Continuous ventilation activated.
Table 4.i
The local/hot/cold valve should be installed to use this function.
34 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4.2.7 General functions: Comfort
This function, if activated by P36, disables the modifi cation of the set point, allowing only an offset of +/-
3°C from the set value (in heat, cool, dry and automatic modes).
On the e-drofan master, the set point can be set via a serial connection (see the corresponding paragraph), while the slaves receive the set point from the related master and apply any offset (set from the terminal).
The master automatically loads the set point saved for parameter p01 when starting; this is subsequently modifi able via a serial connection. Set the logic and dependence parameters suitably.
E.g. In a hydronic system, the set point can be set on the e-drofan master and the slaves only allow modifi cations of +/- 3 C.
E.g.. In a centralised system (hotel), the room set point can be set via serial, allowing the guest the possibility to change it by +/- 3 C.
4.2.8 General functions: Occupancy
This function is used to set a second set point applied if the environment is not occupied, allowing the air-conditioning system to consume less energy and thus achieve cost savings.
The set point is increased by the value set for parameter P18 in cooling/dry mode, or decreased by the value set for P19 in heating mode.
Three typical situations have been identifi ed, represented by parameter P93 “occupancy type”; each type can be optimised using time bands (set via a supervisory system) and occupancy sensors. status of the installation occupancy type room status e-drofan operation event activating control at the set point
OFF (command sent only once from supervisory system)
ON+ECO (command sent only once from supervisory system)
0
1= meeting room
2= corridor
Unoccupied/ occupied
3= offi ce
0 Unoccupied/ occupied
1= meeting room Unoccupied
Occupied
OFF set point= economy set point= economy set point=set value.
When the occupancy timer has elapsed, e-drofan will return to set point = economy.
set point= economy
The occupancy timer is set as follows:
1. Pressing any button (except the ON/OFF button);
2. Pressing the sleep button or activation of the occupancy digital input.
2= corridor
3= offi ce
Unoccupied/ occupied
Unoccupied
Occupied set point= economy set point= set value.
When the occupancy timer has elapsed, e-drofan will return to set point = economy.
The occupancy timer is set as follows:
1. Pressing any button (except the ON/OFF button) or activation on the occupancy digital input;
2. Occupancy timer reset when pressing the sleep button or activation of the occupancy digital input.
ON ON (command sent only once from supervisory system)
0
1= meeting room Unoccupied
2= corridor
3= offi ce
Unoccupied/ occupied
Occupied
Unoccupied
Occupied
Unoccupied/ occupied set point= economy set point= set value.
When the occupancy timer has elapsed, e-drofan will return to set point = economy.
set point= economy
The occupancy timer is set as follows:
1. Pressing any button (except the ON/OFF button);
2. Pressing the sleep button or activation of the occupancy digital input.
set point= set value.
When the occupancy timer has elapsed, e-drofan will return to set point = economy set point= set value
The occupancy timer is set upon activation of the occupancy digital input.
• No digital input: Set point always = set value. Pressing the sleep button for 5 s. activates the * symbol and the set point= economy.
• With digital input:
1. Pressing any button (except the ON/OFF button) or activation on the occupancy digital input;
2. Occupancy timer reset when pressing the sleep button or activation of the occupancy digital input.
Table 4.j.a
• In all modes the change ON+ECO->ON or OFF->ON sets the “occupancy timer”, that is, on power-up the e-drofan starts with set point equal to the set value.
• In all modes (except corridor), holding the sleep button for 5 seconds the e-drofan takes set point= set value without time limits until receiving the OFF command; the set point may return to economy by pressing the sleep button again or switching the unit OFF or alternatively by disconnecting and reconnecting power to the e-drofan.
In a hydronic network the occupancy function shares the same variables as the economy/sleep functions, meaning the slaves can be forced to follow the status of the master (simply set the function on the master). In any case, the occupancy on a slave can be managed locally (obviously this must be fi tted with a terminal) by activating the function using the corresponding parameter; in this case the activation request
(following the detection of occupancy on the master) is ignored. symbol on master terminal
+
+
+
N.B.: do not use the ECONOMY digital input with the occupancy function enabled.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
35
time band
00.00
06.00
06.00
08.00
08.00
12.00
12.00
14.00
14.00
18.00
18.00
20.00
20.00
24.00
With the remote lock function active (dipswitch 3= ON) pressing the sleep button for 5 seconds does not switch to occupied mode without time limits.
Below is an example of occupancy management in a centralised system for offi ces: installation status description
Installation
OFF
The installation remains off and ignores the requests from the fan coil
ON+ECO The installation starts air-conditioning the rooms, preparing them for the arrival of the personnel.
The fan coils start from unoccupied (set point= economy, e.g. 16°C in heating) and if necessary switch to occupied according rooms
All types
• offi ce
• meeting room
Installation ON to the types shown above.
The installation controls the temperature of the rooms to ensure the comfort of the personnel.
At 8:00 all fan coils are activated at the set point= set value (e.g. 20°C in heating) for a time equal to the occupancy timer;
All types
ON+ECO
Installation ON upon expiry of the timer, the fan coils return to the management depending on the type.
The installation returns to unoccupied during the lunch break (set point= economy, e.g. 16°C in heating), maintaining • offi ce comfort only where required.
The installation starts air-conditioning the rooms again to ensure the comfort of the personnel (e.g. 20°C in heating). At 14:00 all the fan coils are activated at set point =set value (e.g. 20°C in heating) for a time equal to the occupancy timer; upon expiry
• meeting room
All types
ON+ECO of the timer, the fan coils return to the management depending on the type.
The installation returns to unoccupied due to the absence of personnel (set point= economy, e.g. 16°C in heating), maintaining comfort only where required.
Installation OFF The installation remains off and ignores the requests from the fan coil
• offi ce
• meeting room
All types
Table 4.j.b
Key:
8
9
6
7
10
1
4
5
2
3
P+I output control probe (°C) heater activation open valve close valve
P109 dead band
P112 ON/OFF heater hysteresis
P115 valve proportional band
P111 heater proportional band set point
4.2.9 General functions: P+I algorithm (cooling/heating/automatic)
The e-drofan features a P+I algorithm that is used to control modulating valves with 0 to 10 Vdc input and
3 point valves.
Control can be performed on the BT probe on the terminal (room temperature, enabled by dipswitch 6) or on one of the three probes on the e-drofan (e.g. air intake temperature), by setting the corresponding parameter.
The P+I algorithm is activated by enabling one of the modulating valve outputs and setting the proportional band and integral time parameters.
Below is a diagram showing the use of the modulating valves in heating mode.
1
100%
6 6
3
4 5
7
2
8
9
Fig. 4.h.b
10
8
The proportional band determines the temperature range within which the actuator moves from closed to maximum opening with control by the proportional term only. The extent of opening depends on the proportional and integral factors; the proportional factor opens the valve further the more temperature is below the set point, while the integral factor increases the opening of the valve if the device takes a long time to reach the set point (with the temperature above the set point the behaviour is symmetrical, that is, the valve is closed).
Low values of the proportional band cause a fast and intense response but cause system instability (swings between opening and closing of the valve); setting low values for the integral factor offers a fast response but, in this case too, the risk of the system becoming instable remains. The integral factor compensates for any misalignments between the theoretical position and the actual position of the valve (this is phenomenon typical of 3 point valves after a large number of operations).
To correctly set the proportional band and the integral time, run some tests on the fan coil system in the environment being air-conditioned, simulating high load and low load conditions and the typical variations in load. One example of the values that can be initially used is: valve proportional band P115= 30 (3°),
P114= 30 (3°) and integral time P108= 60 (that is, 600 s).
36
A parameter is featured that limits the movements of the valve so as to reduce wear and adapt the P+I output to the effective resolution in the position of the actuator; in fact, a minimum variation in the P+I e-drofan - +030221266 - rel. 3.6 del 26.04.2010
output can be established before effectively switching the output (parameter P99).
Parameter P109 is the dead band (to the sides of the set point); within this zone the algorithm accepts minimum variations of the control temperature without performing any action, the purpose is to avoid instability and limit the number of operations of the actuator in steady operation (the integral factor remains constant, while the proportional factor is equal to 0). In cooling mode, the behaviour is symmetrical.
For the effective use of the actuators, the fan is activated when the P+I output is other than zero, the fan speed can be set manually or determined by the autofan function (in this case, at least the minimum speed is guaranteed).
The position of the valve can be displayed on the Acqua terminal in the place of the set point (see parameter P37).
If a series of actuators are used with overlapping set points and proportional bands, the activation is performed in sequence, starting from the resource with the lowest cost (e.g. valve) and ending with the resource with the highest cost (e.g. heater).
The “bumpless transfer” parameter is featured that, in response to modifi cations of the P+I algorithm control parameters during the normal operation of the unit, is used to dampen any swings or over-corrections of the system, especially if the algorithm interacts with a series of devices or actuators.
The P+I parameters are shown in the following table (for the settings corresponding to the various types of valves, see the following paragraphs).
par.
description def
P99 Minimum P+I output variation for valve movement (0 to 10 V 5% and 3 point valve) and heater increase. Expressed as a % of the total P+I output.
P107 Bumpless transfer 1
0= no management of the transients for a change in actuator, variation in P+I parameters and variation in the set point.
1= gradual activation when changing actuator
2= gradual activation when changing actuator and gradual response to variations in P+I parameters
3= gradual activation when changing actuator, gradual response to variations in P+I parameters and set point
P108 Integral time 0
0= Integral factor disabled
P109 Dead band
P111 Heater control set point, expressed as an offset from the set point (ON/OFF management with hysteresis)
P112 Heater control set point heater hysteresis with ON/OFF management
P114 Cold valve proportional band
0=actuator disabled
P115 Hot valve proportional band
0=actuator disabled
P116 Modulating heater proportional band
2
30
5
0
0
0 min
0
0
0
0
0
0
0
0 max
100
3
255
255
255
255
255
255
UOM
% s *10
°C/10
°C/10
°C/10
°C/10
°C/10
0 255 °C/10
When the P+I output is other than zero, the heating/cooling request bits (depending on the mode) are set.
The P+I times for the 3 point valves or thermal valves have a resolution of 1 sec. With P+I active, the heat/cool enable functions are ignored. Set an integral time that considers the travel speed of the modulating valve used.
4.2.10 General functions: modulating valve management
The management of modulating valves requires the algorithm P+I to be enabled.
For the correct use of 3 point valves, the time taken by the valve to completely open or close needs to be entered.
par.
P97 description def
Maximum valve travel time (or 2 windings) 0 min
0 max UOM
600 s
Synchronisation
When the e-drofan is shutdown (switched from ON ->OFF), powered up, or when total closing is requested (in this case, the minimum time between two synchronisation cycles is 6 hours), a complete closing cycle is performed to ensure correct alignment between the position determined by the P+I algorithm and the real position, as there may in fact be misalignments due to mechanical wear after a signifi cant number of operations. The synchronisation procedure is only performed on the 3 point valves, while for the valves with 0 to 10 V input, the function is managed by the electronics on the actuator.
The return to normal operating conditions after a synchronisation cycle is managed according to the normal dynamics of the P+I algorithm, given that the extent of the error at the moment of synchronisation cannot be known.
Small deviations between the theoretical and the actual position are automatically compensated for by the integral factor.
Antistick
To prevent the valves from blocking (due to impurities or the entrainment of solid residues in the water circuit), set movements of the valve are performed periodically. These operations are effected only after a certain period in which the valve is inactive (for example, when the set point has been reached or when the device is off). For the valves with 0 to 10 V input, this function is managed by the electronics on the actuator.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
37
par.
description def.
min max UOM
P100 Maximum valve inactivity time after which the antistick function 4 0 255 hours is activated.
If= 0 the antistick function is disabled
P101 Forced movement due to antistick function. Considered as a % of the maximum travel set
20 0 100 % max travel
4.2.11 General functions: fan speed limit
In some applications, the fan speed needs to be limited; this is done by setting parameter P117.
par.
description def.
min max UOM
P117 Speed enabled: 0 0 1
0= all speeds enabled.
1= Only minimum speed (autofan displayed on LCD terminal, not modifi able). The fan stops only when P+I output =0.
1 set point
ON
OFF
Key:
1. status of the valve;
2. room temperature.
P06
Fig. 4.g
2
Key:
1. room temperature (B1);
2. exchanger temperature;
3. valve status;
4. fan status;
5. change mode by user;
6. extra fl ush cycle;
7. speed selected by autofan;
8. fan started by cool enable;
9. change speed by autofan;
10. valve and fan deactivated due to set point reached;
11. fl ush cycle.
38
4.2.12 Manual operation: Cooling - (Management of the hot/cold water valve or cold water valve only)
The activation of the hot/cold water or local/cold water valve is based on the set point set by the user (see the following fi gure), while the fan starts according to the cool enable function (at the speed selected by the user or decided by the autofan function).
When the room temperature (the value read by the control probe) reaches the set point, the hot/cold water or local/cold water valve is closed and the fan is stopped.
par.
P06 def.
5 min.
max.
unit of measure
0 255 °C/10 setting
Thermostat hysteresis
Table 4.k
Below is an example of the sequence for the activation of the loads on the e-drofan; the device is fi tted with a hot/cold water valve and is in cooling mode, with the fan speed established by the autofan function
(control probe B1).
1
Set +P07 set point
2
P14-P13
(cool enable)
3
ON
4
medium speed min. speed
5 6 7 8
Fig. 4.h.a
9 10 11
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4.2.13 Manual operation: heating - (management of the hot/cold water valve or cold water valve only)
The activation of the hot/cold water or local/hot water valve is based on the set point set by the user (see the following fi gure), while the fan starts according to the heat enable function (at the speed selected by the user or decided by the autofan function).
When the room temperature (the value read by the control probe) reaches the set point, the local/hot water valve is closed and the fan is stopped.
par.
P06 def.
5 min.
0 max.
unit of measure
255 °C/10 setting thermostat hysteresis
Table 4.l.a
Key:
1. valve status;
2. room temperature.
A heater can be used (when dip 5= ON) to improve the heating capacity, with a different hysteresis used according to whether the heat enable function is active. To avoid possible overheating, the fan is activated at the same time as the heater, and remains on for a time equal to P48 after it is deactivated. As a further protection, the heater is deactivated if the temperature of the coil exceeds the temperature set for parameter P47.
par
P13
P46
P47
P48 def
10
30
40
20 min
0
0
0
0 max
255
255
255
255 unit of measure setting
°C/10
°C/10 s
°C
Hysteresis for heater with heat enable active
Hysteresis for heater with heat enable not active
Maximum exchanger temperature for heater off
Post-ventilation for heater
Table 4.l.b
Key:
1. heater ON;
2. room temperature;
3. heat enable not active (with hot water);
4. valve ON;
5. heat enable active (without hot water).
1
4
4
1
ON
OFF set point
P06
Fig. 4.g
P13
P46
P06
P06
2 set point
2
2
2
P13
1
2 set point
Fig. 4.h
Below is an example of the sequence for the activation of the loads on the e-drofan in heating mode; the device is fi tted with a hot/cold water or local/hot water valve and is in heating mode, with the fan speed established by the autofan function.
1 set point
Set-P07-P09
2
P12+P13
P11+P13
P10+P13
3
ON
4 medium speed min. speed
Key:
1. room temperature (B1);
2. exchanger temperature (heat enable);
3. valve status;
4. fan status;
5. change mode by user;
6. extra fl ush cycle;
7. speed selected by autofan;
8. fan started by heat enable and change speed;
9. change speed by autofan;
10. valve and fan deactivated due to set point reached;
11. fl ush cycle.
3
5
5 6 7 8 9
Fig. 4.i
10 11 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
39
Key:
1. room temperature (B1);
2. exchan ger temperature;
3. valve status;
4. heater status
5. fan status;
6. change mode by user;
7. extra fl ush cycle;
8. valve and heater enabling after extra fl ush;
9. heater enabling for threshold exceeded with non-active
heat enable;
10. speed by autofan;
11. valve deactivated due to set point reached;
12. heater post-ventilation;
13. fl ush cycle.
P+I ALGORITHM: with the P+I algorithm, the heater output parameter must be set appropriately
• ON/OFF management with hysteresis: P39= 18 (or either
P40, P41 or P42), in which case parameters P111 (heater activation delta from set point) and P112 (hysteresis) need to be set;
• modulating heater with 0 to 10 V input: P39 or P40= 17, in which case the P+I parameters need to be set (proportional band P116 etc).
Below is a further example of a device fi tted with hot/cold water or local/hot water valve and heater; it is in heating mode, with the fan speed established by autofan.
1 set point
Set-P46
Set-P13
2
P12+P13
(heat enable)
P11+P13
P10+P13
3
ON
4
ON
5 medium speed min. speed
6 7 8 9 10
Fig. 4.j
11 12 13
ON
OFF
1
1
3 4
P06
3 °C
Fig. 4.k
P06
5
2
P49 P50 P49 P50 P49 P50
Fig. 4.l
4.2.14 Manual operation: dehumidify
Based on the set point set by the user, fi rst the room temperature is controlled, by cooling if necessary, and then the dehumidifi cation function starts.
In dehumidifi cation mode, the hot/cold water or only local/cold water valve is always open and fan on/off cycles are performed at minimum speed.
The cool enable function is always active to ensure that the temperature of the exchanger is low enough to ensure the condensation of the water vapour.
When the room temperature reaches the set point the dehumidifi cation function stops, the fan stops and the hot/cold water or only local/cold water valve is closed.
For modulating actuators, the valve is controlled as completely open or completely closed.
Key to Fig. 4.k “Management of the loads”:
1. mode;
2. room temperature;
3. fan= OFF; valve= closed;
4. dehumidify: fan= cycles at min. speed; valve= open;
5. cooling: fan= user selection; valve= open.
Key to Fig. 4.l “Local/cold water valve management”:
1. mode;
2. room temperature;
3. fan= OFF; valve= closed;
4. dehumidify: fan= cycles at min. speed; valve= open;
5. cooling: fan= user selection; valve= open.
par
P06
P49
P50 def
5
3
15
0
0 min
0 max
255
255
255 unit of measure setting
°C/10 Thermostat hysteresis min min
Fan operating time in dehumidify
Fan operating time in dehumidify
Table 4.m
ON
P30
P06 P06
OFF
P31
Key:
1. room temperature (B1).
Fig. 4.m
1
40
4.2.15 Manual operation: fan
In this mode, the hot or cold water valve is always closed and the fan operates at the speed selected by the user (in autofan, it works at medium speed). The fan only starts if the room temperature is within the range of temperatures specifi ed by parameters P31 and P30, so as to avoid undesired fl ows of hot or cold air.
par
P06
P30
P31 def
5
15
20 min
0
0
0 max
255
255
255 unit of measure setting
°C/10 Thermostat hysteresis
°C Fan enable temperature
°C Fan enable interval
Table 4.n
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4.2.16 Automatic operation
In automatic mode, the e-drofan measures the room temperature and decides which mode to activate
(cooling or heating) based on the set point defi ned by the user, the criterion is described in the graph on the side.
The fan and local/cold/hot water valve are managed as in heating/cooling mode (the fl ush function is not active). The heater is also managed as in heating mode. In automatic OFF the local/cold/hot water valve is closed and the fl ush function is active. If when entering automatic mode the room temperature falls within the hysteresis, priority is given to heating mode.
COMFORT: This function, when activated, does not allow the set point to be changed (fi xed or sent via serial connection) but only the setting of an offset of +/- 2°C around the set point.
When cooling mode is activated, the control set point is equal to the set point + P02, while in heating mode, the control set point is equal to the set point - P03.
P+I ALGORITHM: Heating or cooling mode is determined according to the graph shown on the side, subsequently the P+I algorithm is activated to manage the outputs. The mode is changed only after the deactivation of all the actuators, as a consequence the internal parameters are reset each time. It should be noted that P02, P03, P04 and P05 ensure a further activation hysteresis (in addition to the P+I dead band) and consequently the parameters need to be set appropriately. The values of parameters P04 and
P05 should be set lower than the dead band.
par.
def.
min.
max.
unit of measure setting
P01
P02
P03
22
5
5
0
0
0
255
255
255
°C
°C/10
°C/10
Set point in automatic mode
Differential in automatic OFF-cooling zone
Differential in automatic OFF-heating zone
P04
P05
P36
10
3
0
0
0
0
255 °C/10
255 °C/10
1
Cooling hysteresis in automatic
Heating hysteresis in automatic
0= Comfort function disabled
1= Enable Comfort
Table 4.o
4.2.17 Compensation using the outside temperature probe
The set point can be changed in relation to the outside temperature, so as to avoid considerable temperature differences when entering/exiting the environment or to compensate for the heat loss of the environment. The parameters differ between cooling and heating modes, and the coeffi cient applied may be positive or negative, depending on the desired effect.
par.
def.
min.
max.
unit of measure setting
P22 0 0 2 0= Compensation disabled
1= outside air probe B1 (Compensation enabled)
P23
P24
0
0
-99
-20
127
+20
°C/10
/10
2= outside air probe B3 (Compensation enabled)
Difference for compensation in cooling;
0= Compensation disabled
Coeffi cient for compensation in cooling;
0= Compensation disabled (tenths)
P25
P26
0
0
-99
-20
127
+20
°C/10
/10
Difference for compensation in heating;
0= Compensation disabled
Coeffi cient for compensation in heating;
0= Compensation disabled (tenths)
Table 4.p
Key:
1.
cooling mode
2.
room temperature
3.
compensation not active (room set pojnt unvaried)
4.
compensation active set = set + [(t.out - set - P23*P24] (cooling mode) set = set - [(set - P25) - t.out] * P26 (heating mode)
5.
room temperature set point
1
1
3
Key:
1. mode;
2. room temperature;
3. heating;
4. OFF;
5. cooling.
P05 P03 P02 P04
Fig. 4.n
1
3
P23
5
4
4
Fig. 4.o
Fig. 4.p
4
5
3
2
2
P23
5
2
4.3 Notes on the serial connection settings
A serial connection (PlantVisor or Modbus) can be used to check all the e-drofan parameters and set those that are not write protected. Below is a short description of the most signifi cant variables (for the settings see the parameter summary table).
Variable
Control probe
Set point setting
Control set point
Digital inputs and heat/cool request
Lock keypad from panel
Meaning
This variable contains the reading of the probe used to control the e-drofan (B1 or BT). The value
Type SV add Modbus add R/W
A 74 74 Read only considers any offsets, hysteresis values, control algorithms, etc.c.
Used to read and where required overwrite the value of the set point that has been set on the panel.
Especially useful if the e-drofan is operating with the comfort function active (e.g. centralised systems, such as hotels, offi ces, etc.) his variable is used to read the value of the set point used to control the e-drofan. The value considers
I
A
83
76
211
76
Read/write
Read only the hysteresis settings, compensation factors, offsets (e.g. SLEEP function), algorithms, etc.
Heat/cool request: the bits are set when the unit is in ON and the set point has not been reached.
Especially useful for energy saving functions.
Used to disable the buttons on the terminal to prevent accidental settings. Useful for centralised systems (hotels, offi ces etc).
I
I 81
78
209
206 Read/write
(CANbus only)
Tab. 4.q
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
41
par.
P36
P37
P38
P55
0
0 def.
0
0
0
0 min.
0
0
4.4 User interface (remote acqua terminal)
A number of parameters can be set to determine the information displayed on the remote acqua terminal.
max.
setting
1 Comfort: 0= Comfort function disabled
4 Display:
1= Enable Comfort
0= Display set point
255
1= Display control probe (BT or B1)
2= Display probe B2
3= Display probe B3
4= Display modulating valve position (only use for testing or service and only with ACQUA terminal)
Disable functions.
Used to reduce the number of functions available on the panel (keypad).
The settings are obtained by adding the values shown below:
1
1= automatic
2= cooling
4= dehumidifi cation
8= fan
16= heating
32= autofan
64= sleep
128= ON/OFF timer and display clock e.g. activation of automatic mode only: 2+4+8+16=30
Abilitazione simboli raffreddamento e riscaldamento in automatic:
0= simboli spenti
1= simboli accesi quando richiesto
Table 4.r
The hydronic network, if suitably confi gured, can disable some buttons on the terminal (see section
“hydronic systems”).
Enabling the TIMER ON and TIMER OFF functions (on the parameter P38) also enables the clock and the corresponding display (otherwise this is not visible).
4.4.1 Programming the events: timer ON, OFF and sleep
See the information in section “user” and the corresponding settings for the parameter P38. When the sleep function is active, in cooling mode, the set point is increased by the value set for parameter P18; in heating mode, the set point is decreased by the value contained in P19.
42
4.5 User interface (remote control and IR receiver)
The IR receiver board displays the status of the unit when the remote control is used. It also features a button for setting operation if the remote control is not available (e.g. fl at batteries); pressing the button repeatedly changes the mode, in the following sequence: automatic, cooling, dehumidify, fan, heating, off.
When setting the mode on the button the fan operates at minimum speed and the set point is equal to the value of parameter P01 (automatic mode set point).
Below is a list of the signals on the IR board: mode
OFF
COOL/DRY
HEAT
FAN
AUTOMATIC OFF
OFF EXTRA FLUSH
Green LED
OFF
ON
OFF
ON
ON
ON
Yellow LED
OFF
ON
ON
OFF
OFF
OFF
Red LED
OFF
OFF
OFF
OFF
OFF
OFF
Table 4.s.a
If any alarms are active the display of the mode is replaced by the alarm signal.
If more than one alarm is active, the alarm with the highest priority is shown.
alarm
None
EEPROM fault
Slave offl ine in CAN network
Room probe fault
Fault on probe B2 or B3 (B1 if P15 to 17 other than 0 and P95=1)
Window alarm
Circulating pump
Local stop from digital input
DL1 (green)
OFF
BLINK
ON
BLINK
OFF
BLINK
ON
OFF
DL2 (yellow) DL3 (red)
OFF
BLINK
OFF
OFF
BLINK
ON
BLINK
ON
OFF
BLINK
ON
ON
ON
ON
ON
ON priority
1
2
3
4
5
6
7
Table 4.s.b
The IR receiver board also features a buzzer that signals the correct reception of the commands sent from the remote control, as well as signalling special situations; the signals are made up of a sequence of intervals lasting 100 m/s in which the buzzer is on or off: signal
Power ON (power supply)
Correct command reception
Start
Stop
Loading default values sequence
ON
ON
ON
ON
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON sound
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
Table 4.s.c
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
4.6 Alarms
If alarms occur, the e-drofan performs certain actions to limit any possible problems; when more than one alarm is active at the same time, only the one with the highest priority is displayed: alarm
EEPROM fault at power on
Offl ine in Can network (no communication between e-drofan and CAN board)
Room probe fault
Probe B2 or B3 (B1 if P15..17 div. 0 eP95=1) fault
Window alarm
Circulating pump alarm
Local stop
Humidity probe absent alarm
A03
A04
A05
A06
A07
A08 signal
(terminal)
A01
A02 effect
Fan off (with post-ventilation for heater)
Close local/hot/cold water valves
Heater off
Tab. 4.t
notes priority
Load the default values or reset from key 1
Communication lost between e-drofan and Can 2
5
6
3
4
7
4.7 List of parameters
P Parameter
30
31
32
33
34
35
36
37
38
39
40
24
25
26
27
28
29
21
22
23
8
9
10
11
12
13
5
6
7
0
1
2
3
4
14
15
16
17
18
19
20
51
52
53
48
49
50
41
42
43
44
45
46
47
54
58
59
60
55
56
57
Software version
Set point in automatic mode
Differential in automatic OFF-cooling zone
Differential in automatic OFF-heating zone
Hysteresis for cooling in automatic
Hysteresis for heating in automatic
Thermostat hysteresis (not automatic mode)
Medium speed delta in Auto Fan
Maximum speed delta in Auto Fan
Fan speed hysteresis in Auto Fan
Minimum speed set in HEAT ENABLE
Medium speed set in HEAT ENABLE
Maximum speed set in HEAT ENABLE
HEAT ENABLE/COOL ENABLE hysteresis
COOL ENABLE set point
Use of probe B1
Use of probe B2
Use of probe St3
Increase COOL/DRY set in sleep
Decrease HEAT set in sleep
Limit ADC coeffi cient
Average ADC coeffi cient
Select outside compensation probe
Set point delta for compensation in cooling
Compensation factor in cooling
Set point delta for compensation in heating
Compensation factor in heating
Reserved use
Display modulating outputs
Enable continuous fan operation
Ventilation set point in fan mode (local & AUTO)
Ventilation diff. in fan mode (local & automatic)
FLUSH fan off time
FLUSH fan on time
FLUSH mode
Extra fl ush ventilation time
Automatic/Comfort Set point
Select probe to be displayed
Skip Panel functions
Set output 4 (see P95 and dipswitch)
Set output 5 (see P95 and dipswitch)
Set output 6
Set output 7
Select multifunction input DI3
Select multifunction input DI4
Select multifunction input DI5
Heater activation delta with heat enable not active
Max B2 temperature to switch off heaters
Flush time with heaters
Fan ON time in DRY
Fan OFF time in DRY
Valve On time during cycles
Max valve Off time during cycles
Minimum valve Off time
Serial communication mode (0=CAREL, 1=Modbus, 2=LON, use with LON serial card)
Enable cool & heat symbols in AUTOMATIC
Polarity of cooling/heating digital input
Mains frequency (0= 50 Hz; 1= 60 Hz)
Offset for probe B1 in COOL/DRY
Offset for probe B1 in HEAT
Offset for probe B1 in AUTOMATIC e-drofan - +030221266 - rel. 3.6 del 26.04.2010
def.
0
0
0
20
3
15
0
0
0
3
4
30
40
15
20
2
90
0
30
0
0
0
5
0
21
0
0
0
10
10
6
7
5
29
33
37
10
22
5
5
10
3
5
7
0
0
0
0
0
0
6
0
0
0
0
0
0
0
1
0 min.
0
0
0
0
0
0
0
0
0
0
0
0
0
-99
-20
-99
-20
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-99
-99
-99
0
0
0 max.
unit
255
255
255
255
3
255
1
4
255
18
18
15
2
127 °C/10
20
127 °C/10
20
2
3
1
°C
°C min s s
255
255 °C
255 °C/10
255 °C/10
255 °C/10
255 °C/10
255 °C/10
255 °C/10
255 °C/10
255 °C/10
255
255
°C
°C
255 °C
255 °C/10
255
6
°C
6
6
255 °C/10
255 °C/10
15
255
255
255
255
255
255
18
18
10
10
10
255 °C/10
255 °C s min min min min min
2
1
1
1
127 °C/10
127 °C/10
127 °C/10
43
Modbus
24
25
136
137
138
139
140
141
142
143
144
131
132
20
21
22
23
133
134
135
8
9
10
11
12
13
5
6
7
SPV
129
1
2
3
4
14
233
234
235
18
19
130
150
151
152
153
154
155
145
146
147
148
149
26
27
156
157
158
159
28
29
30
Carel
24
25
8
9
10
11
12
13
14
15
16
21
22
23
5
6
7
3
4
20
8
9
10
11
12
13
5
6
7
SPV
1
1
2
3
4
14
105
106
107
18
19
2
25
26
27
22
23
24
17
18
19
20
21
26
27
28
28
29
30
29
30
31
U
U
U
U
U
U access note
E.g. v3.5 = 35.
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
F
SPV
I
I
I
A
A
I
I
I
I
I
I
I
A
I
I
A
A
I
I
A
A
A
A
A
A
A
A
A
A type
I
A
A
A
A
I
I
A
I
A
I
A
I
I
I
I
I
I
I
I
I
I
I
A
A
I
A
A
A
I
I
I
P Parameter
83
84
85
86
87
88
80
81
82
89
90
91
92
93
67
68
69
70
71
72
61
62
63
64
65
66
73
74
75
76
77
78
79
Offset for probe B1 (terminal probe)
Offset for probe B2 in COOL/DRY
Offset for probe B2 in HEAT
Offset for probe St3 in COOL/DRY
Offset for probe St3 in HEAT
CAN Master/Slave
CANbus serial address
Hydronic algorithm logic
Local network address
Dependency of hydronic algorithms (on Slaves)
Serial address of Slave 1
Serial address of Slave 2
Serial address of Slave 3
Serial address of Slave 4
Serial address of Slave 5
Serial address of Slave 6
Serial address of Slave 7
Serial address of Slave 8
Serial address of Slave 9
Serial address of Slave 10
Dependency of hydronic algorithms on Slave 1
Dependency of hydronic algorithms on Slave 2
Dependency of hydronic algorithms on Slave 3
Dependency of hydronic algorithms on Slave 4
Dependency of hydronic algorithms on Slave 5
Dependency of hydronic algorithms on Slave 6
Dependency of hydronic algorithms on Slave 7
Dependency of hydronic algorithms on Slave 8
Dependency of hydronic algorithms on Slave 9
Dependency of hydronic algorithms on Slave 10
Load defaults
Factory password
Occupancy mode
94
95
96
97
Occupancy time
Disable output setting from dipswitch
Reserved use
Maximum valve travel time (2 windings)
98
99
Reserved use
Minimum P+I output variation for valve movement
100 Maximum valve inactivity time (for unblocking)
101 Forced movement for antistick function
102 Reserved use
103 Reserved use
104 Reserved use
105 Reserved use
106 Reserved use
107 Bumpless transfer
108 Integral time
109 Dead band
110 Reserved use
ON/OFF heater control offset from set point (ON/OFF manage-
111 ment with hysteresis)
112 Heating set point hysteresis for heater control
113 Reserved use
114 Cold valve proportional band
115 Hot valve proportional band
116 Modulating heater proportional band
117 Fan speed enabled
118 Reserved use
119 Reserved use
120 Reserved use
121 Reserved use
122 Reserved use
123 Reserved use
124 Presence of humidity-temperature probe sch_th
125 Reserved use
0
* Only for CANbus hydronic systems, not use for Modbus ® or Plantvisor systems.
1
0
2 def.
0
0
0
0
0
0
0
0
0
15
0
0
0
0
0
0
1
0
0
0
1
0
-30
0
0
0
0
0
0
0
0
0
0
0
0
30
5
0
0
0
0
120
5%
4
20
0
0
0
0
0
0
0
0
0
1
0
0
0 min.
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
-99
-99
-99
-99
-99
0
0
0
0
0
0
0
0
0
255 s
100 %
255 hours
% max
100 travel
1
°C
°C min
°C/10
I
A
A
A
I
I
A
A
I
I
A
I
I
I
I
I
I
A
I
A
A
A
A
A
I
I
A
I
A
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
A
I
A
SPV type
A
A
A
I
I
I
I
I
I
I max.
unit
207
7
7
7
7
7
7
7
7
7
7
255
255
3
255
1
207
207
207
207
207
207
207
125
7
207
7
207
207
127 °C/10
127 °C/10
127 °C/10
127 °C/10
127 °C/10
1 min
°C/10
°C/10
°C
3
255 s *10
255 °C/10
°C/10
255 °C/10
255 °C/10
°C/10
255 °C/10
255 °C/10
255 °C/10
1
67
68
69
36
37
38
104
99
42
43
44
41
100
101
102
47
45
46
39
40
48
103
108
109
49
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
33
34
35
36
37
38
34
35
32
39
40
41
42
43
44
45
Carel
SPV
31
32
33
174 *
175 *
176 *
177 *
178 *
179 *
180 *
181 *
182 *
183 *
184 *
185
186
187
188
189
Modbus
SPV
31
32
33
34
35
160 *
161 *
162 *
163
164 *
165 *
166 *
167 *
168 *
169 *
170 *
171 *
172 *
173 *
191
192
193
194
195
196
197
36
37
38
232
227
42
43
44
41
228
229
230
47
45
46
39
40
48
231
236
237
49 access note
F
F
F
F
F
F
F
F
F
F
U
U
F
F
U
U
F
F
F
F
F
F
U
U
U
F
U
U
F
F
F
F
F
F
F value= 44 value= 66
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
Tab. 4.u
44 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
variables only accessible from serial link probe B1 probe BT
Probe B2 probe B3 control probe virtual probe (probe set by CANbus/supervisor) control set point mode (see Table 4.z) fan (see Table 4.z)
Reserved use
ON/OFF def.
min. max.
unit
0
0
0
0
0
°C/10
°C/10
°C/10
°C/10
°C/10
0
0
0
0
0
0
0
6
3
1
°C/10
°C/10
Ind /zone (control probe
(1=B1; 0= BT)
1 continuous fan operation 0 master alarms 0 slave alarms 0
0
0
1
1
I
I
I
I
A
I
I
I
I
A
SPV type
A
A
A
A
A lock panel keypad 0 general fl ags 1 (see Table
4.z) general fl ags 2 (see Table
4.z) digital inputs (see Table
4.z) and heating/cooling request sleep/econ set point set comfort control general fl ags 3 (see
Table 4.z)
Reserved use
0
22
0 enable control virtual probe when=1 general fl ags 6 reserved use reserved use reserved use global alarm reserved use reserved use modulating valve modulating heater humidity probe H temperature probe H reserved use reserved use
0
0
0
8
-3
0
0
1
32
3
1
1
°C
°C
%
%
%
% rH
°C/10
I
I
I
I
I
I
I
I
A
A
A
A
A
I
I
I
I
I
I
I
I
I
D
88
89
90
91
1
92
77
78
79
80
81
93
94
82
83
84
85
86
75
76
70
71
72
73
Carel
SPV
70
71
72
73
74
74
75
76
77
78
79
80
81
87
Modbus
SPV notes
70 read-only
71 read-only
72 read-only
73 read-only
74 read-only
75 do not use with Plant-
Visor and Modbus®
76 read-only
198 see Table 4.z
199 see Table 4.z
200
201
202 internal use do not modify from supervisor
203 read/write
204 read-only
205 read-only for CANbus hydronic
206 systems only, do not use with Modbus® and PlantVisor
207 see Table 4.z
208 read-only see Table
4.z
209 read-only see Table
4.z
210
211
212
213 read-only
214
215 for CANbus hydronic systems only, do not use with Modbus® and PlantVisor
216
217
218
219
read-only
220
77
78 read-only
79 read-only
80 read-only
81 read-only
221
222
Tab. 4.v
6
4
5
1
2
3 mode
0 automatic automatic + heater cooling dry fan heating heating + heater
2
3 fan
0
1 auto minimum medium maximum
8
16
32
64
2
4 general fl ags 1
1 heater available reserved use reserved use
128 remote control broadcasting active reserved use lock function hydronic active
8
16
32
64
2
4 general fl ags 2
1 enable cooling active enable heating active comfort function activated
128 economy reserved use reserved use reserved use reserved use
4
8
1
2 general fl ags 3 reserved use reserved use reserved use display set/probe fl ag generali 6
1 User present (see occupancy, used by Easy Way system)
4
8
16
32 digital inputs
1 value of input 1 (remote ON/OFF)
2 value of input 2 (heating/cooling)
64
128 value of input 3 (multifunction) value of input 4 (multifunction) value of input 5 (multifunction) heating request cooling request occupied status (see occupancy) e-drofan - +030221266 - rel. 3.6 del 26.04.2010
45
address (binary), dip 1-7
0
1-15
16
21-125
126-128 mode
Can be confi gured:
Broadcast or single node
Broadcast
Reserved
Single node
Reserved
5. HYDRONIC SYSTEMS
In summary:
• Synergy between chiller controller (pCO) and e-drofan;
• Algorithms focused on energy savings;
• Algorithms focused on comfort;
• Building automation functions;
• Flexible space management;
• Reduced times for the propagation of the commands;
• Type of networks: hydro bus (dedicated area controller or built into the chiller controller), integrated hybrid (area controller built into the chiller controller);
• Possibility to install the terminal on the slaves;
• Feedback on the alarms relating to the slaves (on chiller controller/area controller and e-drofan master);
• Control of all units by the supervisory system or area controller.
The use of the CAN serial board on the e-drofan allows the creation of hydronic systems with the purpose of creating synergy between the chiller controller (pCO) and the fan coil. This interaction gives the chance to apply advanced energy savings and comfort algorithms (resident on the chiller controller), as well as implement useful building automation functions.
The CAN board has been designed to minimise the activation of the operators in the event of variations in the spaces to be air-conditioned (quite common in some installations, e.g. offi ces); in this case, simply redefi ne the roles of the master and slave on the acqua terminal or pCO controller (if present).
5.1 Structure
The single node structure is used in the hydronic systems, in which the fl ow of data is bi-directional
(unlike the broadcast structure, in which it is mono-directional); there are many consequent advantages: display the slave alarms on the master, acquire useful values for the management of the system, fi t the acqua terminal on the slaves... etc.
Maximum number of units connected
Maximum number of masters
Maximum number of slaves
Maximum number of slaves for each master
Maximum length of the CANbus (total) single node
100
64
100 minus no. of masters
10
1 km (62.5 kbit); 500 m (125 kbit)
Table 5.a
The address set using the group of 10 dipswitches on the CAN board defi nes the operating mode: note
The address can be set on the acqua terminal, parameter P67 (switch off and on again to make the new setting operational); consequently, the mode can be confi gured. Without these settings P67=1 and the e-drofan fi tted with the terminal becomes the master.
Master and slave must have the same address
Each unit (master or slave) must have different addresses
Table 5.b
Dipswitches 9 and 10 are used to set the CANbus communication speed and must be set both in the same position.
dip 9 and 10 ON= 125 kbit/s dip 9 and 10 OFF= 62.5 kbit/s dip 8= must be set to ON to use the serial board on the e-drofan
After each variation made to the position of the dipswitches, the e-drofan must be switched off and on again for the changes to become operational.
46 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
5.1.1 Single node
In this mode, the information that the master must send to all the slaves (LOGIC parameter) can be set, as well as the information accepted by each individual slave (DEPENDENCE). The set of a master and its slaves is a “zone”. All the settings are performed on the master from the panel.
Fig. 5.a
par.
P66
P67
P68
P69
P70
P71-P80 0
P81-P90 0
1
0
1
0 def.
min.
max. setting
0 0 1 e-drofan master or slave; 0= slave; 1= master
1
0
1
0
125
7
Serial address on CANbus. Can be set on the acqua terminal if the serial address specifi ed on the CAN board dipswitches is 0
Master LOGIC (see the table below)
207 485 networks serial address (used only with 485 serial board)
7 DEPENDENCE of the controller on its master (e-drofan or 0= the control ignores any data from its master pCO): 1= the controller accepts: ON/OFF, ECONOMY/ SLEEP
2= the controller accepts: ON/OFF, ECONOMY/ SLEEP, mode, comfort
3= the controller accepts: ON/OFF, ECONOMY/ SLEEP, mode, comfort, set point
4= the controller accepts: ON/OFF, ECONOMY/ SLEEP, mode, comfort, set point, fan speed
5= the controller accepts: mode, comfort, set point
6= the controller accepts: mode, comfort, set point, fan speed
7= the controller accepts: all the data from its master.
0
0
207 CANbus addresses of the slave
7 Dependence of the slave: 0= the slave ignores all data from the master
1= the slave accepts: ON/OFF, ECONOMY/ SLEEP
2= the slave accepts: ON/OFF, ECONOMY/ SLEEP, mode, comfort
3= the slave accepts: ON/OFF, ECONOMY/ SLEEP, mode, comfort, set point
4= the slave accepts: ON/OFF, ECONOMY/ SLEEP, mode, comfort, set point, fan speed
5= the slave accepts: mode, comfort, set point
6= the slave accepts: mode, comfort, set point, fan speed
7= the slave accepts: all the data from the master.
Table 5.c
The occupancy function uses the economy/sleep variables to manage the network.
Data propagated according to the LOGIC parameter
ON/OFF
ECONOMY/SLEEP
Mute ALARM (future use)
Control performed with probe value sent from the zone master (if DIP 6= ON on the master)
Control performed with probe value sent from the chiller controller (PCO)
Set point propagated by zone master
Operating mode and comfort function propagated by zone master
Fan speed propagated by zone master
Flap position propagated by zone master (future use)
Mode, comfort, set point, fan speed and fl ap position at switch OFF->ON only propagated by zone master
(a only time).
Use by zone master and slaves of the control probe value calculated as average of all the control probes in the zone (including slaves)
Different set points propagated for the various slaves in the zone. The set points are specifi ed for the related dependence parameters (the dependence is set to 7 for all the slaves in the zone) (e.g. P81= e-drofan slave1 set point etc.)
Different offsets (from zone master set point) propagated for the various slaves in the zone. The offsets are specifi ed in the related dependence parameters (the dependence is set to 7 for all the slaves in the zone)
(e.g. P81= e-drofan slave1 offset); e-drofan slave1 set point= e-drofan master set point + P81 etc.)
LOG.=1 LOG.=2 LOG.=3 LOG.=4 LOG.=5 LOG.=6 LOG.=7 **
*
Table 5.4
* the master sends the fi nal set point to the slave, performing the sum with the offset internally.
** Logic 7 reserved for future uses.
With logic = 0 no data are spread e-drofan - +030221266 - rel. 3.6 del 26.04.2010
47
Buttons locked on the terminal by the KEYLEVEL parameter
ON/OFF button
MODE button
FAN speed button
SET button
CLEAR/SLEEP button (ECON. from digital input)
TIMER button
UP button
DOWN button
* Reserved for future uses.
IMPORTANT:
Before modifying a parameter on the master (related to the confi guration of the network), the e-drofan must be set as a slave (P66= 0); once the operation has been completed, the e-drofan can be confi gured as the master.
The pCO chiller controller can deactivate some buttons on the e-drofan terminals via the hydronic network.
Following the setting of the DEPENDENCE parameter, a number of buttons on the e-drofan slave terminals are deactivated. These restrictions are required to avoid confl icts between the operation set by the master and any settings made by the user on the e-drofan slaves (using the acqua terminal).
key level=1 key level=2
key level=3
key level=4
key level=5
key level=6
key level=7
key level= 8
key
level= 9
Table 5.d
Description of the LOGIC parameter:
• LOGIC 1: The same as the broadcast, with the addition of displaying the alarms relating to the slaves on the master terminal.
• LOGIC 2: Operation as per broadcast, with the addition of displaying the alarms relating to the slaves on the master terminal; all the e-drofans in the zone are controlled based on the probe value sent by the chiller controller (pCO). Useful for algorithms resident on the pCO.
• LOGIC 3: Operation as per broadcast (with slave alarms displayed on the master terminal) but data sent only at power-up of the master. Modifi cations can be made to operation by the user controlling the slave (e.g. change fan speed to reduce noise). Useful for aligning the status of the slaves in a zone with the corresponding master (e.g. Start-up in the morning).
• LOGIC 4: The master propagates ON/OFF, ECONOMY/SLEEP and control probe; all the remaining functions can be modifi ed on the slaves. The control probe reading is the average of the probes (B1 or
BT) on all the slaves in the zone. Useful for giving priority to control of the average temperature in an environment rather than single point control (see Fig. 5.2).
• LOGIC 5: Operation as per broadcast (with slave alarms displayed on the master terminal). The master propagates different set points for each slave (these can be set on the master terminal). Useful in zones featuring slaves without terminals.
• LOGIC 6: Operation as per broadcast (with slave alarms displayed on the master terminal). The master propagates different set points for each slave (these can be set on the master terminal as offsets from the set point). Useful in zones featuring slaves without terminals.
• LOGIC 7: Reserved for future uses.
Key :
1. Average of BT on unit 1, BT unit 2, BT unit 3
Bcontrol= (21+22+23)/3= 22°C
2. Set: 23 °C
BT: 21 °C;
3. Set: 23 °C
BT: 22 °C
4. Set: 23 °C
BT: 23 °C.
Fig. 5.b
The off status, determined by ON/OFF digital input, has priority over the command sent by the master; this operation is required to allow the user to turn off the fan coil to stop the fl ow of cold air.
The area controller/chiller controller can nonetheless force the settings on the e-drofan irrespective of the dependence setting (useful in some extreme situations) and can acquire some useful information
(status of digital inputs, heating/cooling request...etc.); for this information and for the further algorithms
(comfort, energy savings.. that reside on the chiller controller (pCO)), refer to the corresponding user manual.
IMPORTANT:
If communication is interrupted between a slave e-drofan and its master (e.g. disconnection ...etc.) the slave stops automatically, nonetheless, it can be re-activated if fi tted with the acqua terminal or remote control (in this case, the device has full control over all the functions).
48 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Below is an example of the possible reconfi guration of the e-drofans if the spaces are reorganised.
Initial confi guration of a zone:
Meeting room
1
ON
OFF
HR
MAN AUTO
120 ohm slave
7
120 ohm
2 master
3
Fig. 5.c.a
Confi guration after the division of the zone into two parts:
Meeting room slave
6
Key :
1. acqua terminal;
2. P66= 1;
P71= 22;
P72= 23
P73= 24
P74= 25;
3. serial card, ID= 21
4. serial card, ID= 22;
5. serial card, ID= 23;
6. serial card, ID= 24;
7. serial card, ID= 25
2
1
ON
OFF
HR
AUTO MAN
120 ohm slave
3
120 ohm
8 slave
Fig. 5.c.b
4
5
7
1
OFF
ON
HR
MAN AUTO
6
5.1.2 Integrated hybrid systems
Integrated hybrid networks can be created, that is, single node structures with the chiller controller and only the e-drofan master (where the slaves are connected in the tLAN and without the acqua terminal).
Key :
1. acqua terminal;
2. P66= 1;
P71= 22;
P72= 25;
3. serial card, ID= 21
4. serial card, ID= 22;
5. P66= 1
P71= 24
6. ID= 23;
7. serial card, ID= 24;
8. serial card, ID= 25
Fig. 5.d
In these applications (typical in single homes) the chiller controller (pCO) carries out the functions of both chiller management and area controller (that is, sends the commands required for the management of the units connected in the network and monitors the status). A maximum of 16 e-drofan masters can be managed by the chiller controller.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
49
5.1.3 e-drobus
If only the CANbus connection is used, there is still the possibility to create networks in which the pCO acts as both chiller controller and area controller (that is, manages the 16 masters connected in the network).
To exceed the limit of 16 master units (necessary for multi-storey buildings), systems must be adopted in which one pCO only acts as area controller, while the chiller is controlled by a dedicated device
(connected to the area controller, e.g.: pCO, µCH2).
In this case, a maximum of 64 e-drofan masters can be connected to the area controller, and the remaining units (up to a maximum of 100) can be assigned as slaves to the e-drofan masters. The area controller has complete control over the masters directly connected, while as regards the slaves assigned to the master, it can only act on the related logic and dependence parameters (resident on the master).
50
Fig. 5.e
5.2 Signals and diagnostics
The CANbus serial board has three LEDs to display the serial communication status relating to the device it is installed on.
The green LED is always on when power is connected.
When the board is initialising, the red and yellow LEDs fl ash in specifi c sequences. After around 20s, when initialisation is complete, the following situations may occur: green LED yellow
LED
ON
ON
ON steady
OFF red LED
OFF
ON steady
ON
ON
ON
OFF
ON steady fl ashing
ON steady ON steady
OFF any
OFF any meaning actions
ON line (master or slave)
OFF line (slave only)
Comnunication problems between e-drofan and CANbus serial board
Serious error
Serious errorgrave
No power
OK
- check confi guration
of master
- check address P67
- check wiring
- check P69=1
- check correct connection
Contact CAREL S.p.A.
Contact CAREL S.p.A.
- check power supply
- check correct connection
Table 5.e
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
5.2.1 Alarms
The acqua terminal displays the alarms on the e-drofan it is connected to, as well as those on the corresponding slaves. When it displays the alarms on its own e-drofan, the signal starts with “A” (e.g. A04), while when displaying those relating to the slaves in the zone, the signal starts with “S” (the second number indicates which slave it refers to (from 0 to 9), while the third number indicates the alarm code).
The codes for the slave alarms (third number) are the same as described in section “constructor”, with Sn0 add: (n = Slave address): Slave not present.
The alarms on the master have priority over the slaves (see section “constructor”), the alarms on the different slaves are displayed in sequence (for each slave, the alarm with the highest priority is displayed).
The e-droset terminal only displays the index of the slave with the alarm.
Key :
1. slave alarm;
2. slave;
3. room probe fault.
Fig. 5.f
5.2.2 Notes on confi guring hydronic networks
During the confi guration of the hydronic networks, the following instructions should be observed:
IMPORTANT:
Avoid settings that create situations of confl ict.
2
3 note description
1 If confi guring a series of e-drofans, fi rst confi gure the slaves and then the corresponding master, or alternatively perform the settings with the CANbus disconnected.
4
5
With logic 5 and 6 do not connect the acqua terminals on the slaves.
The logic must be set on the master before the dependence on the slaves.
Some functions can be activated both locally (digital inputs) and remotely (via serial connection). To avoid confl icts, install the ON/OFF, ECONOMY and PRESENCE digital inputs only on the e-drofan master. The slaves can only be connected to the inputs relating to the alarms
(window alarm, circulating pump alarm and local stop).
related events
If this sequence is not observed, some buttons on the terminal connected to the slave may be locked due to of the dependence set on the master, thus preventing the correct confi guration of the slave/slaves.
The information propagated via the CANbus may be lost.
The related parameters (dependence P81-P90) may have different meanings
(see logic 5 and 6) when the logic changes. When logic is 5 (different set points) the limits are 7 to 35°C, when logic is 6 (offset from the set point on the master) the limits are -5 to +5.
The status of an e-drofan slave is continuously controlled by its master. The master is set by the area controller/chiller controller just once, which allows the subsequent modifi cation of its status (e.g. from the presence or ON/OFF inputs etc.). The continuous or periodical control of the master must be included in the area controller/chiller controller application.
In the event of confl icts between the digital input and the area controller/chiller controller, operation is not affected, however there will be intense traffi c in the serial communication, causing a decline in performance.
6
7
So as to avoid confl icts, the cooling/heating function (to be installed on the master only) must be set only by digital input or via serial communication.
The same must be applied to the remote off (settable by dipswitch).
In this regard, the dependence is set to 0 when DIP 2 or 3 is ON (only when starting), while there is still the possibility to change the dependence from the area controller/chiller controller.
The specifi cations provided for the acqua terminal are also valid when using the remote control, with the exception of the keypad lock. In fact, if a function is locked, the remote control still sends the data, which are however ignored by the e-drofan; consequently, there may be discrepancies between the information shown on the display of the remote control and the operation of the device.
The slaves should be fi tted ON/OFF digital inputs (without acqua terminal or remote control, or if ON/OFF is disabled). In this way, the user can switch the unit off to stop the fl ow of hot/cold air.
Table 5.f
5.2.3 Notes on the serial address settings
The serial address in a CAREL or Modbus ® network is assigned by the e-drofan board using parameter
P69 “local network address”.
In a CANbus network, on the other hand, the device network address is assigned by parameter P67
“CANbus serial address”. For correct communication between the CANbus serial board and the e-drofan, parameter P69 must be set to 1 (this is the default setting).
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
51
6. NON-HYDRONIC SUPERVISORY SYSTEMS
6.1 Introduction
The 485 serial board can be used to create customised supervisory systems, for example PlantVisor.
The same accessory can be used to integrate the e-drofan into ModBus systems (enable Modbus with parameter P54= 1).
6.2 Easy way Acqua (wireless network)
The “Easy Way Acqua” system is an evolution of the e-dronic system. Exploiting ZigBee wireless technology, this system ensures communication between e-drofan devices without a wired network. The e-drofan interfaces to the wireless system by fi tting a router board that acts a gateway on the supervisor serial connection.
The logic implemented in the Easy Way Acqua system is similar to tLAN and CANbus broadcast mode, as the different e-drofan devices in the same hydronic zone have identical behaviour.
In the Easy Way Acqua system, the main hydronic zone operating parameters are always accessible to the supervisor.
For details on operation of this system, see the corresponding manual.
B1
B2
B3
DIP
Terminal
L
N
No1
No2
No3
GN, Tx, V+
GN, Tx
DI1, DI2, DI3, DI4, DI5
7. TECHNICAL SPECIFICATIONS AND PRODUCT CODES
7.1 e-drofan
Assembly and installation instructions
Meaning
Phase
Neutral
Minimum fan speed (normally open). Voltage output (L)
Medium fan speed (normally open). Voltage output (L)
Maximum fan speed (normally open). Voltage output (L)
LCD panel connection
Terminals for local network serial connection (master + 5 slave)
Digital inputs, voltage-free contacts: 1=remote ON/OFF
EXP
FLAP
SUPPLY EXP
IR
JS3
SERIAL
Ambient air probe (intake)
Main exchanger probe
Secondary exchanger probe
Confi guration dipswitches: 1 ON= Enable heat/cool enable (probe B2)
2 ON= Enable remote cooling/heating
4 ON= 4 pipe fan coil (OFF=2 pipe)
6 ON = Control on terminal probe
Connector for the expansion card (5-wire cable)
Not used
Connector for expansion card power supply (2-wire cable)
Connector for the infrared receiver interface (8-wire cable).
Connector for inserting optional power supply for compatibility with pCO serial cards (future use)
Connector for inserting serial optional cards
Table 7.a
52 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Power supply
Screw terminals (external unit power supply
Relay outputs No1, No2, No3
Digital inputs
Analogue inputs
Index of protection
Storage conditions
Operating conditions
Degree of pollution
Cat. of resistance to heat and fi re
PTI of insulating materials
Class and structure of the software
Period of stress across the insulating parts
230 Vac, range -15 to 10%; 50/60 Hz; Maximum power input (excluding relay loads): 4 VA
Max voltage: 230 V
Cable cross-section: 14-22 AWG
The current input of the network (sum of the current input of the loads plus the external module) must not exceed 6 A.
Maximum current: VDE0631: 6 (2) A, 250 Vac
Minimum interval between switching cycles (each relay): 12 s (the of the manufacturer of the unit that the device will be integrated into must guarantee the correct confi guration to respond to this specifi cation)
Type of relay microswitching: 1C
Insulation between low (relay outputs) and very low voltage parts: reinforced
Electrical standard: voltage-free contact
Closing current referred to earth: 5 mA
Maximum closing resistance: 50 W
B1, B2, B3: NTC temperature probes CAREL (10 kW at 25°C).
IP00
-20T80°C, humidity 80% RH non-condensing
0T60°C, humidity <90% RH non-condensing
Normal
D all the materials have PTI
250
A long
Table 7.b
Max. cable lengths: probes: digital inputs:
LCD panel/ tLAN networks: serial communication cards: boiler control: power supply: power outputs (relay):
10 m
30 m (AWG 14-22)
30 m (AWG 14-22) refer to corresponding instruction sheet
30 m (AWG 14-22)
5 m (AWG 14-22)
30 m (AWG 14-22)
Warnings:
• All installation and maintenance operations must be carried out with the unit off;
• Use shielded cables for the serial connections: 3-wire + shield for tLAN, 2-wire + shield for networks made with optional serial cards. Do not make star connections (use chain connections). Connect the shield to terminal GN;
• Avoid short-circuits between pins GN and V+ (LCD panel power supply);
• Adopt precautions against electrostatic discharges when handling the board;
• Do not earth terminal GN.
Protection against electric shock and maintenance warnings
The system made up of the control board (HYFC0*) and the other optional cards (HYVC000R0*, HYPA*,
HYIR*, HYSC00F0C*, pCO serial cards etc.) represents a control device to be incorporated in class I or II appliances.
The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect the power supply before working on the board during assembly, maintenance, replacement and confi guration.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fi tted on, or by the installer.
Technical specifi cations
Functional characteristics
Resolution of analogue inputs:
Measurement error by temperature:
Temperature probes: interval -40 to 80°C, 0.1°C
Interval -20 to 25°C, ±0.5°C (excluding probe)
Interval 25 to 30°C, ±1°C (excluding probe)
Interval 30 to 90°C, ±1.5°C (excluding probe)
Table 7.c
Connections
See Fig. 3.c.
7.2 e-drofan expansion card
Assembly and installation instructions
Terminal
SUPPLY EXP
EXP
N
No4
No5
No6
No7
Meaning e-drofan expansion power supply connector (connect by 2 wire cable)
Connector for e-drofan expansion using 5-wire cable
Neutral
Multifunction
Voltage output (L)
Multifunction
Voltage output (L)
Cold water free contact
Hot water free contact e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Table 7.d
53
Power supply
Screw terminals
Uscite relè No4, No5, No6, No7
Insulation
Index of protection
Storage conditions
Operating conditions
Degree of pollution
Category of resistance to heat and fi re:
PTI of insulating materials:
Period of stress across the insulating parts:
Maximum cable length, voltage outputs No4 and No5: 5 m
Maximum cable length, outputs No6 and No7: 30 m (voltage-free contact), 5 m (power supply to any load).
Warnings:
• All installation and maintenance operations must be carried out with the unit off;
• Keep the power cable (relay outputs) separate from the probe cables, digital inputs, fl ap power supply,
IR receiver board, fl at connection cable to expansion and serial connections (LCD panel, tLAN networks, hydronic networks etc.);
• Adopt precautions against electrostatic discharges when handling the board (e.g. antistatic bracelet);
• If using serial communication boards, the use of output No7 may be limited to very low voltage only.
Protection against electric shock and maintenance warnings
The system made up of the control board (HYFC0*) and the other optional cards (HYVC000R0*, HYPA*,
HYIR*, HYSC00F0C*, pCO serial cards etc.) represents a control device to be incorporated in class I or II appliances.
The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fi tted on, or by the installer.
Technical specifi cations
230 Vac, range –15 to 10%; 50/60 Hz (supplied by e-drofan board); Maximum power input (excluding relay loads): 1.5 VA
Max voltage: 230 V
Cable cross-section: 14-22 AWG
The current input of the network (sum of the current input of the loads, the e-drofan, the expansion and the external module) must not exceed 6 A.
Maximum current at 250 Vac: EN60730: Resistive 2 A, Inductive: 2 A cos(
)=0.4 60000 cycles
For voltage outputs No4 and No5, respect the maximum limits described under “Screw terminals.
Minimum interval between switching cycles (each relay): 12 s (the of the manufacturer of the unit that the device will be integrated into must guarantee the correct confi guration to respond to this specifi cation)
Type of relay microswitching: 1C
Insulation between low (relay outputs) and very low voltage parts: reinforced
Insulation between voltage outputs No4, No5 and outputs No6, No7: reinforced
Insulation between outputs No6 and No7: reinforced. If using serial cards, the use of output No7 may be limited to very low voltage only. See the user manual.
IP00
-20T80°C, humidity 80% RH non-condensing
0T60°C, humidity <90% RH non-condensing
Normal
D all the materials have PTI
250 long
Table 7.e
7.3 E-drofan 4 triac expansion board
7.3.1 Assembly and maintenance instructions
terminal meaning
SUPPLY EXP Power supply connector (connect to e-drofan via 2 wire cable).
EXP E-drofan signal input connector (use 5 wire cable).
N Neutral
No4
No5
No6
No7
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P39)
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P40)
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P41)
Multifunction TRIAC output with voltage signal: see the manufacturer section (confi gurable by parameter P42)
Maximum cable length for voltage outputs No4, No5, N06, N07: 5 m.
WARNINGS
• All installation and maintenance operations must be carried out with the unit off.
• Adopt precautions against electrostatic discharges when handling the board (e.g. antistatic bracelet).
7.2.2 Protection against electric shock and maintenance warnings
The system made up of the control board (HYFC0*****) and the other optional boards (HYVC000T0*,
HYPA******, HYIR******, HYSC00F0C*, pCO serial boards etc.) represents a control device to be integrated into class I or class II appliances. The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fi tted on, or by the installer.
54 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
7.3.3 Technical specifi cations
Power supply
Screw terminals
Voltage outputs No4, No5, No6, No7
Insulation
Index of protection
Storage conditions
Operating conditions
Degree of pollution
Cat. of resistance to heat and fi re:
PTI of insulating materials:
Period of stress across the insulating parts:
230 Vac, range –15% +10%; 50/60 Hz
Maximum power input (excluding triac loads): 1.5 VA
Max voltage: 250 V
Cable cross-section: 14-22 AWG
Max current: see outputs No4-7
Maximum current at 250Vac (per individual voltage output): 0.3 A.
Type of action of the triac: electronic disconnection
Insulation between low (triac outputs) and very low voltage parts: Reinforced
Insulation between triac outputs with voltage signal No4,No5, No6,No7: Functional
IP00
-20T80 °C, humidity 80% RH non-condensing
0T60 °C, humidity <90% RH non-condensing
Normal
D all the materials have PTI
250 long
7.4 e-drofan triac/relay expansion board
7.4.1 Assembly and maintenance instructions
terminal meaning
SUPPLY EXP Power supply connector (connect to e-drofan via 2 wire cable)
EXP E-drofan signal input connector (use 5 wire cable)
N
No4
No5
No6
No7
Neutral
TRIAC output with voltage signal, multifunction: see the manufacturer section (confi gurable by parameter P39)
TRIAC output with voltage signal, multifunction: see the manufacturer section (confi gurable by parameter P40)
Multifunction relay output 10 A resistive: see the manufacturer section (confi gurable by parameter P41). Voltagefree contact
Multifunction relay output: see the manufacturer section (confi gurable by parameter P42). Voltage-free contact
Maximum cable length for voltage outputs No4, No5: 5 m
Maximum cable length for relay outputs N06, N07: 5 m
WARNINGS
• All installation and maintenance operations must be carried out with the unit off.
• Adopt precautions against electrostatic discharges when handling the board (e.g. antistatic bracelet).
7.4.2 Protection against electric shock and maintenance warnings
The system made up of the control board (HYFC0*****) and the other optional boards (HYVC000M**,
HYPA******, HYIR******, HYSC00F0C*, pCO serial boards etc.) represents a control device to be integrated into class I or class II appliances. The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fi tted on, or by the installer.
7.4.3 Technical specifi cations
Power supply
Screw terminals
Voltage outputs No4, No5
Relay output No6
Relay output No7
Insulation
Index of protection
Storage conditions
Operating conditions
Degree of pollution
Cat. of resistance to heat and fi re
PTI of insulating materials
Period of stress across the insulating parts
230 Vac, range –15% +10%; 50/60 Hz
Maximum power input (excluding triac loads): 1.5 VA
Max voltage: 250 V
Cable cross-section: 14-22 AWG
Max current: see outputs No4-7
Maximum current at 250Vac (per individual voltage output): 0.3 A
Type of action of the triac: electronic disconnection
Maximum current at 250 Vac: EN60730: Resistive 2 A, Inductive: 2 A cos( )=0.4 60000 cycles
Maximum current at 250 Vac: EN60730: Resistive 10 to 100000 cycles
Type of action/microswitching of the relay: 1C
Insulation between low (triac outputs) and very low voltage parts: Reinforced
Insulation between triac outputs with voltage signal No4,No5: Functional
Insulation between triac outputs with voltage signal No4,No5 and relay outputs No6, No7: Reinforced
Insulation between the two relay outputs No6, No7: Reinforced
IP00
-20T80 °C, humidity 80% RH non-condensing
0T60 °C, humidity <90% RH non-condensing
Normal
D all the materials have PTI
250 long e-drofan - +030221266 - rel. 3.6 del 26.04.2010
55
Power supply
Screw terminals
0 to 10 Vdc outputs No4, No5
Relay outputs No6, No7 (voltage-free contacts)
Insulation
Index of protection
Storage conditions
Operating conditions
Degree of pollution
Category of resistance to heat and fi re
PTI of insulating materials
Period of stress across the insulating parts terminal
SUPPLY EXP
EXP
GN
No4
No5
No6
No7
7.5 e-drofan relay/analogue output expansion board
7.5.1 Assembly and maintenance instructions
meaning
Power supply connector (connect to e-drofan via 2 wire cable)
E-drofan signal input connector (use 5 wire cable)
Signal reference terminal
Multifunction 0 to 10 Vdc output: see the manufacturer section (confi gurable by parameter P39)
Multifunction 0 to 10 Vdc output: see the manufacturer section (confi gurable by parameter P40)
Multifunction relay output: see the manufacturer section (confi gurable by parameter P41).Voltage-free contact
Multifunction relay output: see the manufacturer section (confi gurable by parameter P42). Voltage-free contact
Maximum cable length for 0 to 10Vdc outputs No4, No5: 5 m.
Maximum cable length for relay outputs (voltage-free contacts) N06, N07: 5 m.
WARNINGS
• all installation and maintenance operations must be carried out with the unit off.
• adopt precautions against electrostatic discharges when handling the board (e.g. antistatic bracelet).
• avoid short-circuits between terminals No4, No5 and the GN terminals.
• keep the power cable (relay outputs) separate from the cables to the 0 to 10 Vdc outputs. 7.5.2
Protection against electric shock and maintenance warnings
The system made up of the control board (HYFC0*****) and the other optional boards (HYVC000V**,
HYPA******, HYIR******, HYSC00F0C*, serial boards pCO etc.) represents a control device to be integrated into class I or class II appliances. The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fi tted on, or by the installer.
7.5.3 Technical specifi cations
230 Vac, range –15...+10%; 50/60 Hz
Maximum power input: 1.5 VA
Max voltage: 250 V
Cable cross-section: 14-22 AWG
Max current: see outputs No4-7
Minimum impedance of the 0-10 Vdc actuator input stage (damper, valve...): 10 kOhm
Maximum current at 250 Vac: - EN60730: Resistive 2 A, Inductive: 2 A cos( )=0.4 60000 cycles
Type of action/microswitching of the relay: 1C
Insulation between relay outputs No6 and No7: Reinforced
Insulation between relay outputs No6, No7 and very low voltage parts: Reinforced
Insulation between 0-10Vdc outputs and relay outputs No6,No7: Reinforced
IP00
-20T80 °C, humidity 80% RH non-condensing
0T60 °C, humidity <90% RH non-condensing
Normal
D all the materials have PTI
250 long
56
7.6 Remote acqua terminal
Assembly and installation instructions
To access the connection terminal remove the rear cover by levering the tab.
terminal meaning
GN
Tx
V+ use for connection to terminal GN on the fan coil and the shield on the shielded cable use for connection to terminal Tx on the fan coil use for connection to terminal V+ on the fan coil
Table 7.f
Maximum length of shielded connection cable: 30 m from the fan coil.
If the local network (tLAN) is used, assign the role of master to the fan coil connected.
Avoid installing the terminal in places where the ambient temperature measurement may be altered: outside walls, near doors leading to the outside, exposed to the sun, etc.
Fasten the terminal as shown in the fi gure (the terminal should be fastened to the wall in a horizontal position so as to allow the recirculation of air through the slits on the rear cover).
Warnings:
• All installation and maintenance operations must be carried out with the unit off;
• Keep the power cables (relay outputs, live cables, etc.) separate from the shielded connection cable to the fan coil;
• Adopt precautions against electrostatic discharges when handling the board.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Technical specifi cations
Power supply
Insulation
Index of protection
Storage conditions
Operating conditions
8 to 25 Vdc (supplied by the e-drofan board)
Insulation between low (relay outputs) and very low voltage parts: reinforced (guaranteed by fan coil board and shielded connection cable).
IP30
-20T80°C, humidity 80% RH non-condensing
0T60°C, humidity <90% RH non-condensing
Degree of pollution Normal
Category of resistance to heat and fi re: D
PTI of insulating materials: all the materials have PTI
250
Period of stress across the insulating parts: long
Table 7.g7.7 e-droset remote terminal
Assembly and installation instructions
Below is the sequence of operations for wall mounting:
• fasten the 3 gang support to the box for built-in installation using two screws;
• make the connections between the terminal and the wires in the shielded cable from the e-drofan. terminal
GN
Tx
V+ meaning use for connection to terminal GN on the e-drofan and the shield in the shielded cable.
use for connection to terminal Tx on the e-drofan. use for connection to terminal V+ on the e-drofan.
Table 7.h
Maximum length of the shielded connection cable: 30 m from the e-drofan;
• insert the terminal in the plastic support;
• insert the fastening “shoulders”;
• position the wallplate on the support.
• The following wallplates can be used:
Biticino Living International; Light; Light Tech; Matix
Vimar Idea; Idea Rondò; Plana
The Living International - Light Tech - Matrix brands are the property of BTicino SpA. The Idea - Idea
Rondò - Plana brands are the property of VIMAR SpA.
If the local network (tLAN) is used, the terminal assigns the role of master to the fan coil connected.
Avoid placing the terminal in places where the room temperature measurement may be altered: outside walls, near doors leading outside, exposed to the sun, near the fan coil or radiators etc.
Warnings:
• all installation and maintenance operations must be carried out with the unit off;
• keep the power cables (relay outputs, live cables, etc.) separate from the shielded connection cable to the e-drofan;
• adopt precautions against electrostatic discharges when handling the board.
TECHNICAL SPECIFICATIONS
Power supply
Insulation
Index of protection of the front panel
Storage conditions
Operating conditions
Degree of pollution
Category of resistance to heat and fi re:
8-25 Vdc (supplied by the fan coil board)
Insulation between low (e-drofan relay outputs) and very low voltage parts: reinforced (guaranteed by the e-drofan board and the shielded connection cable).
IP30
-20T80°C, humidity 80% RH non-condensing
0T60°C, humidity <90% RH non-condensing
Normal
D
Table 7.i
7.8 CANbus serial board
Assembly and installation instructions terminal
GND, H+, H-
Connettore 8 Vie
Connettore 7 vie (ove presente)
Dip switch 10 vie meaning
CANbus connection
Power and communication jack with electronic controller to be inserted in the CANbus (fan coil, pCO...).
Power and communication jack with electronic controller to be inserted in the CANbus (fan coil, pCO...).
Used to make the following settings (refer to the corresponding user manual):
DIP 1-7: Serial address of the unit that hosts the CAN board (binary notation). From 1 to 15 for broadcast networks and the remaining for the single node mode.
DIP8: ON= For use on pCO (OFF= For use on fan coil)
DIP9: CANbus speed (ON= 125 Kbit/s OFF= 62.5 Kbit/s)
DIP10: ON= Enable maximum CANbus distance (1 km). In this case the speed must be 62.5 Kbit/s
Table 7.j
Maximum cable length: 1 km at 62.5 Kbit/s, 500 m at 125 Kbit/s.
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
57
Power supply
Screw terminals
Insulation
Index of protection
Storage conditions
Operating conditions
Degree of pollution
Cat. of resistance to heat and fi re:
PTI of insulating materials:
Class and structure of the software:
Period of stress across the insulating parts:
Warnings:
All installation and maintenance operations must be carried out with the unit off.
• Use shielded cables for serial connections, 2 wires plus shield, typical impedance 120 Ohm, parasitic capacitance 40 pf/m and signal propagation time 5 ns/m;
• Adopt precautions against electrostatic discharges when handling the board;
• The serial board is not optically-isolated, do not earth.
Below is a table showing the recommended shielded cables, depending on the various installations. The codes shown comply with the required specifi cations; cables supplied by other manufacturers can be used, as long as they comply with the above requirements.
EXAMPLES Wire resistance (Ohm/km)
AWG 16
AWG 18
AWG 22
AWG 24
AWG 24
13.7
22.6
48.2
78.7
78.7
Max. cable length (km)
1.173
0.711
0.333
0.204
0.204
Belden code
9860
3074F
3105A
9841
8103
Table 7.k
Depending on the assumed length of the network, cables with a smaller cross-section may be used.
For example, if expecting a maximum length of 300 m, AWG22 cable is suffi cient.
Protection against electric shock and maintenance warnings
The system made up of the control board (including any optional cards) and the and the CAN serial board represents a control device to be incorporated in class I or II appliances. The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fi tted on, or by the installer.
Technical specifi cations
8-38 Vdc.
Maximum power input: 900 mW
Cable cross-section: 28-16 AWG
The board is not optically-isolated. Refer to the user manual of the control it is installed on
IP00
-20T80°C, humidity 80% RH non-condensing
0T60°C, humidity <90% RH non-condensing
Normal
D all the materials have PT
250
A long
Table 7.l
7.9 Remote control
Assembly and installation instructions
If using this with a master fan coil, make sure that the resistor has been inserted between terminals GN and V+ (on the fan coil) and that the receiver board HYIR****** has been connected.
Warnings:
Disconnect the power supply before performing any installation and maintenance operations on the fan coil.
Adopt precautions against electrostatic discharges when handling the fan coil board.
Technical specifi cations
Power supply
Storage conditions
Operating conditions
Degree of pollution
Type of communication
Two “AAA” 1.5V batteries.
-20T80°C, 80% RH non-condensing
0T60°C, <90% RH non-condensing
Normal. The batteries should be disposed of according to the standards in force
Infrared
Table 7.m
58 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
7.10 Dimensions
Also see Figs. 3.b.a, 3.b.b e 3.e.
Fig. 7.a
7.11 Codes
For the description of the family of e-drofan products, see section “installer”.
description quantity
Main board e-drofan: Electronic controller for fan coils, single package 1 pc
25 pcs e-drofan: Electronic controller for fan coils, multiple package
Terminal
Remote ACQUA terminal for e-drofan, single package
Remote ACQUA terminal for e-drofan, multiple package
1 pc
25 pcs
1 pc Built-in e-droset terminal for e-drofan, single package
Accessories
Programming key
Programming key with power supply
Adapter for e-drofan programming key e-drofan relay expansion card, single package e-drofan relay expansion card, multiple package
E-drofan TRIAC expansion board, single package
1 pc
1 pc
1pc
1 pc
50 pcs
1 pc
E-drofan TRIAC expansion board, multiple package
E-drofan relay/analogue output expansion board, single package
E-drofan relay/analogue output expansion board, multiple package
E-drofan TRIAC/relay expansion board, single package
E-drofan TRIAC/relay expansion board, multiple package
Serial option
CAN bus serial board for e-drofan single package
RS485 serial card for e-drofan single package
Remote control options
IR receiver board 24 cm cable multiple package 25 pcs
IR receiver board 50 cm cable multiple package 25 pcs
IR receiver board multiple package
IR receiver board + 50 cm cable multiple package
Remote control, single package
Remote control, multiple package
Probes
HP NTC probes 40 cm
HP NTC probes 60 cm
HP NTC probes 100 cm
HP NTC probes 160 cm
50 pcs
1 pc
50 pcs
1 pc
50 pcs
1 pc
1 pc
25 pcs
25 pcs
50 pcs
50 pcs
1 pc
50 pcs
50 pcs
50 pcs
50 pcs
50 pcs code
HYFC000000
HYFC000001
HYPA001000
HYPA001001
HYPA003000
PSOPZKEY00
PSOPZKEYA0
HYKA000000
HYVC000R00
HYVC000R01
HYVC000T00
HYVC000T01
HYVC000V00
HYVC000V01
HYVC000M00
HYVC000M01
HYSC00F0C0
HYSC00F0P0
HYCB000201
HYCB000501
HYIR000001
HYIR000501
HYHS001000
HYHS001001
NTC004HP0R
NTC006HP0R
NTC010HP0R
NTC016HP0R
Table 7.n
e-drofan - +030221266 - rel. 3.6 del 26.04.2010
59
7.12 Notes on the software release and compatibility
Compatibility of the system accessories based on the main functions
Main functions
Occupancy.
Comfort in all modes modulating valves e-drofan
FW
1.9
2.1
acqua FW CAN board FW e-droset
FW
1.3 (except occupancy)
1.3
4.6 1.0
4.6
1.0
-
Remote control
FW
Table 7.o
Functions added/modifi ed e-drofan 2.1
1 Added management of modulating actuators (3 point valves and valves with 0 to 10 Vdc input) e-drofan 1.9
1 Modifi ed default values P06, P07, P08, P09, P13, P14, P39, P46, P53, P61
2 Added setting of outputs No4, No5 from dipswitch 4 if enabled by P95
3 Comfort settable in all modes
4 Enable Heat/Cool from dipswitch 1 and enabling of corresponding probe on coil
5 Added occupancy function
6 Modifi ed management of the heater with or without heat enable
7 Added digital variable to enable alarm log on PlantVisor
8 Added management of e-droset built-in terminal
9 Extended parameter copy (by programming key) from e-drofan with previous version software (copy only the parameters in common)
10 Enabled use of the Modbus protocol
ACQUA 1.3
1 Modifi ed clock display and setting when starting
2 Parameter editing with index greater than 100
3 Comfort settable in all modes and extended to ±3°C
CAN board 4.6
1 Lock keypad on the e-drofan slave terminals from PCO (released from dependence)
2 Comfort settable in all modes
Table 7.p
60 e-drofan - +030221266 - rel. 3.6 del 26.04.2010
Note: _________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
Note: _________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________