Mitsubishi GT15 1595, 1585V, 1585, 1575V, 1575, 1572, 1565, 1562, 1555, 1550 Graphic Operation Terminal User's Manual
विज्ञापन
विज्ञापन
SAFETY PRECAUTIONS
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product.
In this manual, the safety precautions are ranked as "DANGER" and "CAUTION".
DANGER
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Note that the caution level may lead to a serious accident according to the circumstances. Always follow the instructions of both levels because they are important to personal safety.
Please save this manual to make it accessible when required and always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
Some failures of the GOT, communication unit or cable may keep the outputs on or off.
An external monitoring circuit should be provided to check for output signals which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
If a communication fault (including cable disconnection) occurs during monitoring on the GOT, communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative.
For bus connection: The CPU becomes faulty and the GOT becomes inoperative.
For other than bus connection: The GOT becomes inoperative.
A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur.
Not doing so can cause an accident due to false output or malfunction.
Do not use the GOT as the warning device that may cause a serious accident.
An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect output or malfunction.
A
- 1
[DESIGN PRECAUTIONS]
DANGER
Incorrect operation of the touch switch(s) may lead to a serious accident if the GOT backlight is gone out.
When the GOT backlight goes out, the POWER LED flickers (green/orange) and the display section turns black and causes the monitor screen to appear blank, while the input of the touch switch(s) remains active.
This may confuse an operator in thinking that the GOT is in "screensaver" mode, who then tries to release the GOT from this mode by touching the display section, which may cause a touch switch to operate.
Note that the following occurs on the GOT when the backlight goes out.
•The POWER LED flickers (green/orange) and the monitor screen appears blank
The display section of the GT1595-X is an analog-resistive type touch panel.
If you touch the display section simultaneously in 2 points or more, the switch that is located around the center of the touched point, if any, may operate.
Do not touch the display section in 2 points or more simultaneously.
Doing so may cause an accident due to incorrect output or malfunction.
CAUTION
Do not bundle the control and communication cables with main-circuit, power or other wiring.
Run the above cables separately from such wiring and keep them a minimum of 100mm (3.94in.) apart.Not doing so noise can cause a malfunction.
Do not press the GOT display section with a pointed material as a pen or driver.
Doing so can result in a damage or failure of the display section.
[MOUNTING PRECAUTIONS]
DANGER
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT main unit to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the communication unit, printer unit, option function board or multi-color display board onto/ from the GOT.
Not doing so can cause the unit to fail or malfunction.
When installing the multi-color display board, wear an earth band etc. to avoid the static electricity.Not doing so can cause a unit corruption.
A
- 2
CAUTION
Use the GOT in the environment that satisfies the general specifications described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in the specified torque range.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the GOT.
[MOUNTING PRECAUTIONS]
CAUTION
When loading the communication unit or printer unit to the GOT, fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, failure or malfunction due to the damage of the screws or unit.
When mounting the multi-color display board onto the GOT, tighten the mounting screws within the specified torque range.
Loose tightening may cause the unit and/or GOT to malfunction due to poor contact.
Overtightening may damage the screws, unit and/or GOT; they might malfunction.
Push the option function board onto the corresponding connector until it clicks, so that it will be secured firmly.
Push the multi-color display board onto the corresponding connector so that it will be secured firmly.
When inserting a CF card into the GOT, push it into the insertion slot until the CF card eject button will pop out.
Failure to do so may cause a malfunction due to poor contact.
When inserting/removing a CF card into/from the GOT, turn the CF card access switch off in advance.
Failure to do so may corrupt data within the CF card.
When removing a CF card from the GOT, make sure to support the CF card by hand, as it may pop out.
Failure to do so may cause the CF card to drop from the GOT and break.
[WIRING PRECAUTIONS]
DANGER
Be sure to shut off all phases of the external power supply used by the system before wiring.
Failure to do so may result in an electric shock, product damage or malfunctions.
A
- 3
[WIRING PRECAUTIONS]
CAUTION
Please make sure to ground FG terminal and LG terminal of the GOT power supply section by applying
Class D Grounding (Class 3 Grounding Method) or higher which is used exclusively for the GOT.
Not doing so may cause an electric shock or malfunction.
Terminal screws which are not to be used must be tightened always at torque 0.5 to 0.8 N · m.
Otherwise there will be a danger of short circuit against the solderless terminals.
Use applicable solderless terminals and tighten them with the specified torque.
If any solderless spade terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
Tighten the terminal screws of the GOT power supply section in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction.
The module has an ingress prevention label on its top to prevent foreign matter, such as wire offcuts, from entering the module during wiring.
Do not peel this label during wiring.
Before starting system operation, be sure to peel this label because of heat dissipation.
Plug the bus connection cable by inserting it into the connector of the connected unit until it "clicks".
After plugging, check that it has been inserted snugly.
Not doing so can cause a malfunction due to a contact fault.
Plug the communication cable into the connector of the connected unit and tighten the mounting and terminal screws in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
[TEST OPERATION PRECAUTIONS]
DANGER
Before performing the test operations of the user creation monitor screen (such as turning ON or
OFF bit device, changing the word device current value, changing the settings or current values of the timer or counter, and changing the buffer memory current value), read through the manual carefully and make yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to perform significant operation for the system.
False output or malfunction can cause an accident.
A
- 4
[STARTUP/MAINTENANCE PRECAUTIONS]
DANGER
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Connect the battery correctly.
Do not discharge, disassemble, heat, short, solder or throw the battery into the fire.
Incorrect handling may cause the battery to generate heat, burst or take fire, resulting in injuries or fires
Before starting cleaning or terminal screw retightening, always switch off the power externally in all phases.
Not switching the power off in all phases can cause a unit failure or malfunction.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
CAUTION
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.
When unplugging the cable connected to the unit, do not hold and pull the cable portion.
Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault.
Do not drop the module or subject it to strong shock.
A module damage may result.
Do not drop or give an impact to the battery mounted to the unit.
Doing so may damage the battery, causing the battery fluid to leak inside the battery.
If the battery is dropped or given an impact, dispose of it without using.
Before touching the unit, always touch grounded metal, etc. to discharge static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
[BACKLIGHT REPLACEMENT PRECAUTIONS]
DANGER
Be sure to shut off all phases of the external power supply of the GOT (and the PLC CPU in the case of a bus topology) and remove the GOT from the control panel before replacing the backlight (when using the GOT with the backlight replaceable by the user).
Not doing so can cause an electric shock.
Replacing a backlight without removing the GOT from the control panel can cause the backlight or control panel to drop, resulting in an injury.
A
- 5
[BACKLIGHT REPLACEMENT PRECAUTIONS]
CAUTION
Wear gloves for the backlight replacement when using the GOT with the backlight replaceable by the user.
Not doing so can cause an injury.
Before replacing a backlight, allow 5 minutes or more after turning off the GOT when using the GOT with the backlight replaceable by the user.
Not doing so can cause a burn from heat of the backlight.
[DISPOSAL PRECAUTIONS]
CAUTION
When disposing of the product, handle it as industrial waste.
[TRANSPORTATION PRECAUTIONS]
CAUTION
When transporting lithium batteries, make sure to treat them based on the transport regulations.
(Refer to Appendix 3 for details of the regurated units.)
Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of this manual, as they are precision devices.
Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportation.
A
- 6
REVISIONS
Print Date
Oct., 2004
Mar., 2005
Apr., 2005
Sep., 2005
Manual Number
SH(NA)-080528ENG-A First edition
The manual number is given on the bottom left of the back cover.
Revision
SH(NA)-080528ENG-B Compatible with GT Designer2 Version2.09K
Partial corrections
Chapter 6, Section 7.3.2, 8.2 to 8.6 8.2 to 8.4, 8.4.3, Section 9.1 to 9.3
9.1 to 9.2, Section 10.1 to 10.6 10.1 to 10.5, Section 12.1 to 12.6 12.1 to
12.5, Section 13.1, 13.2 to 13.6 13.3 to 13.7, Section 14.1 to 14.2 14.1,
Section 15.1 to 15.2 15.1, Section 16.1 to 16.2 16.1, Chapter 18, Section
18.6 18.3, 18.3 to 18.5 18.4 to 18.6, Section 19.1, 19.2
Partial additions
SAFETY PRECAUTIONS, Section 2.1, 2.2.2, Section 3.2, Section 4.1, 4.2, 4.3,
Section 5.3, Section 7.3.1, 7.5.1, 7.5.2, Section 8.3, Appendix 1, 2, 4
Additions
Section 10.6, Section 12.6, Section 13.2
SH(NA)-080528ENG-C
Partial corrections
Section 4.1, 4.2, 4.3, 7.1.2, 7.5.2, 18.6, Appendix 1, Chapter 5 to 19 6 to 20,
Appendix 2 to 4 3 to 5
Additions
Chapter 5, Appendix 2
SH(NA)-080528ENG-D Compatible with GT Designer2 Version 2.18U
Partial corrections
Chapter 1, Section 1.1, 1.2, Section 2.1, 2.2, 2.2.1, 2.2.2, Section 4.1 to 4.4,
Section 5.1, 5.1.3, 5.2.5, 5.4.2, Section 6.3, Section 7, 7.4, Section 8.1, 8.1.1,
8.1.2, 8.2, 8.3, 8.5.1, 8.5.2, 8.6.2, 8.7.3, 8.7.4, 8.11, 8.11.1, Section 9, 9.1, 9.2,
9.3.1, to 9.3.3, Section 10, 10.1.2 to 10.1.4, 10.2.2, 10.2.3, Chapter 11, 11.1,
11.1.1 to 11.1.3, 11.2.2, 11.2.3, 11.3.1, 11.3.2, 11.4.2, 11.5.1 to 11.5.3, Section
12.1.1 to 12.1.3, Section 13, 13.1.2, 13.1.3, 13.2.1, 13.2.2, 13.2.4, 13.3.2 to
13.3.4, 13.4.2, 13.5.2, 13.6.1 to 13.6.3, 13.7, 13.7.1, 13.7.2, 13.7.4, 13.7.5,
Chapter 14, 14.1.2, 14.2.1, 14.3.1 to 14.3.3, 14.4.2, 14.5.2, 14.6.2, 14.7.1,
14.7.2, Section 15.1.2, Section 16.1.3, Section 17.1.3, Chapter 18, 18.1, 18.2,
18.3, 18.3.1, 18.3.2, 18.4, Section 20.1, 20.2, Appendix 5
Partial corrections
Section 5.3.2, 5.3.3, Section 6.2, 6.5, Section 8.4.1, 8.7.2, 8.8.1, 8.10.1, 8.10.2,
Section 10.2.1, Section 11.2.1, 11.3.3, Section 13.1.5, Section 14.1.1, Section
19.2, 19.4, 19.5, 19.6.1, 19.6.2, Appendix 1, 3
Additions
Section 3.2.1 to 3.2.4, 3.3.1, 3.3.2, Section 4.1, Section 8.5.3, Section 11.6,
11.8, Section 13.8, 13.9, 13.10, Section 18.5
Section 4.1 to 4.3 Section 4.2 to 4.4
Section 11.6 Section 11.7
A
- 7
Print Date
Jan., 2006
Jun., 2006
Manual Number Revision
SH(NA)-080528ENG-E Compatible with GT Designer2 Version2.27D
Partial corrections
SAFETY PRECAUTIONS, Chapter 1, Section 2.1, Section 8.1.1, 8.5 to
8.11 8.6 to 8.12, Section 9.2, 9.3, Section 10.1.3, Section 11.1, 11.7.2, Section
13.7.4, 13.10.4
Partial additions
Section 2.2, Section 6.3, Section 13.1.5, 13.2.4, Chapter 14, Section 19.4,
Section 20.2, Appendix 1, 3, 5
Additions
Section 8.5, Section 14.8, 14.9
SH(NA)-080528ENG-F Compatible with GT Designer2 Version2.32J
Partial corrections
Chapter 1, Section 1.1, 2.1, 2.2, 4.1, 4.2, 4.3, 4.4, 5.3.1, 5.4.2, 8.4, 8.5.2, 8.9,
9.3, 11.2.2, 11.3.2, 11.4.2, 11.5.2, 11.7.2, 11.8.2, 12.1.3, 13.1.5, 13.2.2, 13.2.3,
13.2.4, 13.3.1, 13.3.3, 13.4.2, 13.4.3, 13.5.2, 13.5.3, 13.6.2, 13.6.3, 13.7.2,
13.7.3, 13.8.2, 13.8.3, 13.9.2, 13.10.2, 13.10.3, 14.3.2, 14.4.2, 14.5.2, 14.6.2,
14.7.2, 14.9, 18.3.1, 18.4, 18.5.2
Partial additions
Chapter 1, Section 2.2.1, 2.2.2, 3.2.1 ~ 3.2.4, 3.3.1, 3.3.2, 5.3.2, 5.3.3, 6.2, 6.3,
7.1, 7.4, 8.1.2, 8.3.1, 8.7, 8.8, 8.10, 8.11, 8.12, 8.13, 9.2, 9.3.1, 10.1.3, Chapter
11, Section 11.1.1, 11.1, 2, 11.5.1, 11.7.1, 11.8.1, Chapter 14, Section 14.1.1,
14.2.1, 19.6.1, 20.2, Appendix 1, 3, 5
Additions
Section 3.2.5, 4.5, 5.3.4, 8.6, 11.9 ~ 11.11, 13.11, 14.8
Japanese Manual Version SH-080507-H
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
© 2004 MITSUBISHI ELECTRIC CORPORATION
A
- 8
INTRODUCTION
Thank you for choosing the Mitsubishi Graphic Operation Terminal.
Before using the equipment, please read this manual carefully to use the equipment to its optimum.
CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A - 9
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A - 9
2. SYSTEM CONFIGURATION 2 - 1 to 2 - 18
3. SPECIFICATIONS 3 - 1 to 3 - 14
Performance Specifications 3 - 2
Power Supply Specifications 3 - 13
Part Names and Settings of the GT1595
Part Names and Settings of the GT1585
A
- 9
Part Names and Settings of the GT157
Part Names and Settings of the GT156
Part Names and Settings of the GT155
5. EMC AND LOW VOLTAGE DIRECTIVE 5 - 1 to 5 - 18
Requirements to Meet EMC Directive 5 - 1
Requirements for Conpliance with the Low Voltage Directive 5 - 6
EMC Directive-Compliant System Configuration 5 - 9
Precautions for Wiring/Connecting the EMC Directive-Compliant Product 5 - 13
Control Panel Inside Dimensions for Mounting GOT
Control Panel Inside Temperature and Mounting Angle
A
- 10
Multi-Color Display Board 8 - 9
8.11 USB Environmental Protection Cover 8 - 39
A
- 11
10. COMMUNICATION INTERFACE SETTING (COMMUNICATION
Communication Detail Settings 10 - 12
11. DISPLAY AND OPERATION SETTINGS (GOT SET UP) 11 - 1 to 11 - 39
Brightness, Contrast Adjustment 11 - 12
Utility Call Key Setting 11 - 20
Adjusting the Touch Panel Position
(Touch panel calibration Setting) 11 - 23
Touch panel calibration setting function . . . . . . . . . . . . . . . . . . . 11 - 23
A
- 12
(Transparent Mode Setting) 11 - 29
11.10 Video Display Settings 11 - 34
11.11 RGB Display Settings 11 - 38
12. CLOCK SETTINGS AND BATTERY STATUS DISPLAY
(TIME SETTING AND DISPLAY) 12 - 1 to 12 - 5
Time Setting and Display 12 - 1
(PROGRAM/DATA CONTROL) 13 - 1 to 13 - 103
A
- 13
Advanced Recipe Information 13 - 42
13.10 Special Data Information 13 - 79
13.11 Operation Log Information 13 - 87
14. GOT SELF CHECK (DEBUG & SELF CHECK) 14 - 1 to 14 - 29
A
- 14
NETWK Unit Status Display 14 - 20
Display example of the NETWK unit status display (MELSECNET/H communication unit) . . . 14 - 21
15. CLEANING OF DISPLAY SECTION (CLEAN) 15 - 1 to 15 - 2
16. MAINTENANCE TIME NOTIFICATION SETTING (MAINTENANCE
TIMING SETTING) 16 - 1 to 16 - 4
Maintenance Timing Setting 16 - 2
A
- 15
17. ADDITION TIMES RESET FOR MAINTENANCE TIME NOTIFICATION
(ADDITION TIMES RESET) 17 - 1 to 17 - 2
18. INSTALLATION OF COREOS, BOOTOS AND STANDARD MONITOR OS
BootOS and Standard Monitor OS Required for installation
Prior Preparations for Installing BootOS and Standard Monitor OS
BootOS and Standard Monitor OS Installation Using Memory Card 18 - 4
When installing the different version of BootOS, standard monitor OS 18 - 8
19. MAINTENANCE AND INSPECTION 19 - 1 to 19 - 16
Battery Voltage Low Detection and Battery Replacement
Backlight Shutoff Detection and Replacement 19 - 5
20. ERROR MESSAGE AND SYSTEM ALARM 20 - 1 to 20 - 17
List of Error Message/System Alarm
Troubleshooting in Bus Connection 20 - 14
Troubleshooting for Monitoring 20 - 17
Appendix 1 External Dimensions
A
- 16
Appendix 2 Confirming of Versions and Conformed standards
Appendix 3 Usage Condition of Utility Function
Appendix 4 Transportation Precautions App- 19
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series) App- 20
INDEX Index- 1 to Index- 4
A
- 17
ABOUT MANUALS
The following manuals are also related to this product.
In necessary, order them by quoting the details in the tables below.
Related Manuals
Manual Name
GT SoftGOT1000 Version2 Operating Manual
Describes the screen configuration, functions and using method of GT SoftGOT1000.
(Sold separately)
GT Designer2 Version2 Basic Operation/Data Transfer Manual (For GOT1000 Series)
Describes methods of the GT Designer2 installation operation, basic operation for drawing and transmitting data to GOT1000 series.
(Sold separately)
*1
GT Designer2 Version2 Screen Design Manual (For GOT1000 Series) 1/3
GT Designer2 Version2 Screen Design Manual (For GOT1000 Series) 2/3
GT Designer2 Version2 Screen Design Manual (For GOT1000 Series) 3/3
Describes specifications and settings of the object functions used in GOT1000 series.
(Sold separately)
*1
GOT1000 Series Connection Manual (1/2)
GOT1000 Series Connection Manual (2/2)
Describes system configurations of the connection method applicable to GOT1000 series and cable creation method.
(Sold separately)
*1
GOT1000 Series Extended/Option Functions Manual
Describes extended functions and option functions applicable to GOT series.
(Sold separately)
*1
GOT1000 Series Gateway Functions Manual
Describes specifications, system configurations and setting method of the gateway function.
(Sold separately)
*1
*1 The manual in PDF-format is included in the GT Works2 and GT Designer2 products.
Manual Number
(Model Code)
SH-080602ENG
(1D7M48)
SH-080529ENG
(1D7M24)
SH-080530ENG
(1D7M25)
SH-080532ENG
(1D7M26)
SH-080544ENG
(1D7M32)
SH-080545ENG
(1D7M33)
A
- 18
ABBREVIATIONS AND GENERIC TERMS IN THIS MANUAL
Abbreviations and generic terms used in this manual are described as follows.
GOT
Abbreviations and generic terms
GT SoftGOT1000
GT1595
GT1585
GT1595-X
GT1585V-S
GT1585-S
GT1575V-S
GOT1000 Series
GT157
GT156
GT155
GT1575-S
GT1575-V
GT1575-VN
GT1572-VN
GT1565-V
GT1562-VN
GT1555-Q
GT1550-Q
GOT900 Series
GOT800 Series
Abbreviation of GT SoftGOT1000
Description
Abbreviation of GT1595-XTBA, GT1595-XTBD
Abbreviation of GT1585V-STBA
Abbreviation of GT1585-STBA, GT1585-STBD
Abbreviation of GT1575V-STBA
Abbreviation of GT1575-STBA, GT1575-STBD
Abbreviation of GT1575-VTBA, GT1575-VTBD
Abbreviation of GT1575-VNBA, GT1575-VNBD
Abbreviation of GT1572-VNBA, GT1572-VNBD
Abbreviation of GT1565-VTBA, GT1565-VTBD
Abbreviation of GT1562-VNBA, GT1562-VNBD
Abbreviation of GT1555-QTBD, GT1555-QSBD
Abbreviation of GT1550-QLBD
GT15 , GT15
GT1155-Q
GT1150-Q
Abbreviation of GT1595, GT1585, GT157 , GT156 , GT155
Abbreviation of GT1155-QSBD
Abbreviation of GT1150-QLBD
Handy
GOT
GT1155HS-Q Abbreviation of GT1155HS-QSBD
GT1150HS-Q Abbreviation of GT1150HS-QLBD
GT11 , GT11 Abbreviation of GT1155-Q, GT1150-Q, GT11 Handy GOT
Abbreviation of GOT-A900 series, GOT-F900 series
Abbreviation of GOT-800 series
Communication unit
Abbreviations and generic terms
Bus connection unit
Serial communication unit
RS-422 conversion unit
Ethernet communication unit
MELSECNET/H communication unit
MELSECNET/10 communication unit
CC-Link communication unit
Interface converter unit
*1 A9GT-QJ71LP23 + GT15-75IF900 set
*2 A9GT-QJ71BR13 + GT15-75IF900 set
*3 A8GT-J61BT13 + GT15-75IF900 set
GT15-QBUS,
GT15-75QBUSL,
GT15-RS2-9P,
GT15-RS2T4-9P,
GT15-J71E71-100
GT15-QBUS2,
GT15-75QBUS2L,
GT15-RS4-9S,
Description
GT15-RS2T4-25P
GT15-J71LP23-25, GT15-J71BR13
GT15-75J71LP23-Z
*1
, GT15-75J71BR13-Z
*2
GT15-J61BT13,
GT15-75IF900
GT15-75J61BT13-Z *3
GT15-ABUS,
GT15-75ABUSL,
GT15-RS4-TE
GT15-ABUS2,
GT15-75ABUS2L
A
- 19
Option unit
Abbreviations and generic terms
Printer unit
Video input unit
RGB input unit
Video / RGB input unit
RGB output unit
Option
Abbreviations and generic terms
Backlight
Option function board
Multi-color display board
Protective Sheet
USB environmental protection cover
Stand
Memory card CF card
Memory card adaptor
Attachment
Battery
Software
Abbreviations and generic terms
GT Works2 Version
GT Designer2 Version
GT Designer2
GT Converter2
GT Simulator2
GT SoftGOT1000
GT SoftGOT2
GX Developer
GX Simulator
Document Converter
GT15-PRN
GT15V-75V4
GT15V-75R1
GT15V-75V4R1
GT15V-75ROUT
Description
Description
GT15-90XLTT, GT15-80SLTT, GT15-70SLTT, GT15-70VLTT,
GT15-70VLTN, GT15-60VLTT, GT15-60VLTN
GT15-FNB, GT15-QFNB,
GT15-QFNB48M, GT11-50FNB
GT15-XHNB, GT15-VHNB
GT15-90PSCB, GT15-90PSGB,
GT15-80PSCB, GT15-80PSGB,
GT15-90PSCW,
GT15-80PSCW,
GT15-90PSGW,
GT15-80PSGW,
GT15-70PSCB, GT15-70PSGB, GT15-70PSCW, GT15-70PSGW,
GT15-60PSCB, GT15-60PSGB, GT15-60PSCW, GT15-60PSGW,
GT15-50PSCB, GT15-50PSGB, GT15-50PSCW, GT15-50PSGW,
GT11-50PSCB, GT11-50PSGB, GT11-50PSCW, GT11-50PSGW,
GT11H-50PSC
GT15-UCOV, GT11-50UCOV
GT15-90STAND, GT15-80STAND, GT15-70STAND, A9GT-50STAND,
GT05-50STAND
GT05-MEM-16MC, GT05-MEM-32MC, GT05-MEM-64MC,
GT05-MEM-128MC, GT05-MEM-256MC
GT05-MEM-ADPC
GT15-60ATT-97, GT15-60ATT-96
GT15-BAT, GT11-50BAT
Description
SW D5C-GTWK2-E,
SW D5C-GTD2-E,
SW D5C-GTWK2-EV
SW D5C-GTD2-EV
Abbreviation of screen drawing software GT Designer2 for GOT1000/GOT900 series
Abbreviation of data conversion software GT Converter2 for GOT1000/GOT900 series
Abbreviation of screen simulator GT Simulator 2 for GOT1000 / GOT900 series
Abbreviation of monitoring software GT SoftGOT1000
Abbreviation of monitoring software GT SoftGOT2
Abbreviation of SW D5C-GPPW-E(-EV)/SW D5F-GPPW-E type software package
Abbreviation of SW D5C-LLT-E(-EV) type ladder logic test tool function software packages
(SW5D5C-LLT (-EV) or later versions)
Abbreviation of document data conversion software Document Converter for GOT1000 series
A
- 20
License (for GT SoftGOT1000)
Abbreviations and generic terms
License
License (for GT SoftGOT2)
Abbreviations and generic terms
License
License FD
Others
Abbreviations and generic terms
Omron PLC
KEYENCE PLC
Sharp PLC
JTEKT PLC
Toshiba PLC
HITACHI PLC
Matsushita PLC
Yaskawa PLC
Yokogawa PLC
Allen-Bradley PLC
SIEMENS PLC
OMRON temperature controller
FUJI temperature controller
YAMATAKE temperature controller
RKC temperature controller
GOT (server)
GOT (client)
Windows font
Intelligent function module
GT15-SGTKEY-U, GT15-SGTKEY-P
Description
Description
A9GTSOFT-LKEY-P (For DOS/V PC)
SW5D5F-SGLKEY-J (For PC CPU module)
Description
Abbreviation of PLC manufactured by OMRON Corporation
Abbreviation of PLC manufactured by KEYENCE
Abbreviation of PLC manufactured by SHARP Corporation
Abbreviation of PLC manufactured by JTEKT Corporation
Abbreviation of PLC manufactured by TOSHIBA CORPORATION
Abbreviation of PLC manufactured by Hitachi Industrial Equipment Systems Co., Ltd.
Abbreviation of PLC manufactured by Matsushita Electric Works, Ltd
Abbreviation of PLC manufactured by YASKAWA Electric Corporation
Abbreviation of PLC manufactured by Yokogawa Electric Corporation
Abbreviation of PLC manufactured by Allen-Bradley
Abbreviation of PLC manufactured by SIEMENS
Abbreviation of temperature controller manufactured by OMRON
Abbreviation of temperature controller manufactured by Fuji Electric Systems Co., Ltd.
Abbreviation of temperature controller manufactured by YAMATAKE
Abbreviation of temperature controller manufactured by RKC
Abbreviation of GOTs that use the server function
Abbreviation of GOTs that use the client function
Abbreviation of TrueType font and OpenType font available for Windows
Indicates the modules other than the PLC CPU, power supply module and I/O module that are mounted to the base unit.
A
- 21
HOW TO READ THIS MANUAL
1
Functions
This manual describes functions available for the GT Designer2 Version2.32J.
For the added functions by the product version upgrade, refer to the list of functions added by GT
Desiger2 version upgrade in Appendices.
2
Symbols
Following symbols are used in this manual.
Remark
Refers to the information required.
Refers to the supplementary explanations for reference.
Indicates the items in which the detailed explanation is described (manual, chapter, section, item of the manual).
. . . .
Indicates the operation steps.
Menu and items are differentiated with parentheses.
[ ] : refers to the menu of GOT utility.
: refers to the button in the dialog
box of GOT utility.
* The above is different from the actual page, as it is provided for explanation only.
A
- 22
PACKING LIST
After unpacking, confirm that the following parts are included.
Model Description Quantity
GOT 1
GT1595-X
Installation fitting 8
GT15 General Description
GT1585V-S,
GT1585-S,
GT1575V-S,
GT1575-S,
GT1575-V,
GT1575-VN,
GT1572-VN,
GT1565-V,
GT1562-VN,
GT1555-Q,
GT1550-Q
GOT
Installation fitting
GT15 General Description
The following products are included a spare for the plastic fixing screw of the GOT.
• GT1585-S: Hardware Version B or earlier (Apr.,2005)
• GT1575-S: Hardware Version B or earlier (Apr.,2005)
• GT1575-V: Hardware Version D or earlier (Apr.,2005)
• GT1565-V: Hardware Version D or earlier (Apr.,2005)
1
1
4
1
A
- 23
1. OVERVIEW
1
About GOT
GOT is installed on the panel surface of control panel or operating panel and connects to the PLC in the control panel. GOT carries out switch operation, lamp display, data display, and message display etc.
PLC
For display screen, two kinds of display screens, user-created screen and utility screen are available.
Connector for program
(1) User-created Screen
User screen is a screen drawn by GT Designer2.
The objects of "Touch switch", "Lamp display", "Comment display", and "Numeric display" can be laid out arbitrarily to be displayed.
GOT
Moreover, the multiple screens created by GT Designer2 can be overlapped and switched to be displayed.
For details, refer to the following.
GT Designer2 Version Basic Operation/Data Transfer Manual
GT Designer2 Version Screen Design Manual
(2) Utility Screen
Utility screen is a screen prepared beforehand for GOT.
Installing BootOS or standard OS in the GOT from GT Designer2 enables utility screen displaying.
The utility screen has menus as [Brightness/contrast adjustment screen] and [GOT memory check screen] etc.
For details, refer to the following.
Chapter 9 to Chapter 17
1
- 1
1
2
About Manual
The following manuals related to GOT1000 series are available. Refer to each manual in accordance with the intended use.
(1) Installation of the software programs Drawing Data transfer
For operations from creating project data to transferring data to GOT, refer to the following manuals.
2
Purpose
Installing product on PC
Creating projects
Creating screens
GT Designer2 Version Basic
Operation/Data Transfer Manual *1
Detailed
GT Designer2 Version
Screen Design Manual *1
Detailed
Detailed
Drawing figures
Detailed
Making Common Settings
Overview
Placing/Setting objects
Overview
Transferring data to GOT
*1 Stored in the GT Works2/GT Designer2 in PDF format.
Detailed
Detailed
Detailed
3
4
5
6
7
8
1
- 2
(2) Installing a GOT Connecting to a controller
For the operations from installing a GOT to communicating with a controller, refer to the following manuals.
Purpose
Confirming part names and specifications of the GOT
(Included)
GT15 General Description
GT11 General Description
GT15 User's Manual
GT11 User's Manual
GOT1000 Series
Connection Manual *1
Overview Detailed
Confirming the GOT installation method
Overview
Confirming the mounting method for extension units or option devices
Confirming the PLC connection method
Detailed
Detailed Overview
Detailed
Confirming the utility operation method
Detailed
Confirming error codes (system alarm) displayed on the GOT
Detailed
1
- 3
*1 Stored in the GT Works2/GT Designer2 in PDF format.
(3) Other manuals
The following manuals are also available.
The following manuals are stored in the GT Works2/GT Designer2 in PDF format.
(a) GOT1000 Series Extended/Option Functions Manual
Describes functions for more efficient debugging as the ladder monitor function, system monitor function and A list edit function.
(b) GOT1000 Series Gateway Functions Manual
Describes how to use the gateway function.
(c) GT SoftGOT1000 Version Operating Manual
Describes how to use the GT SoftGOT1000 and various functions.
(d) GT Simulator2 Version Operating Manual
Describes how to simulate the created project data with the GT Simulator2.
(e) GT Converter2 Version Operating Manual
Describes how to use the GT Converter2.
1.1 Features
(1) Improved monitoring performance and connectivity to FA devices
• Using of TFT color liquid crystal display (high intensity, wide angle view and high definition type) provides clear full-color display and displays small characters clearly. (Displays digital images of
BMP and other formats in 65536 colors.) *1
• Provides multi-language display function based on Unicode2.1 True Type font and high-speed drawing of beautiful text.
• High speed monitoring through high speed communication at maximum of 115.2kbps.
• High speed display and high speed touch switch response.
(2) More efficient GOT operations including screen design, startup, adjustment, management and maintenance works
• 9MB user memory is included as standard. (Memory capacity can be expanded up to 57MB by increasing the option memory) *1
• CF card interface is included as standard
• Font installation is available to increase the system fonts.
• Combined use of 4 types of alarms (system alarm, user alarm, alarm history, alarm popup display) realizes more efficient alarm notification.
• Maintenance timing report function is available that measures the backlight energization time and notifies of maintenance time.
• The USB connector is positioned on the GOT front. This enables the system startup to be performed more efficiently using FA device startup tool, and eliminates the necessity of indirect works (opening and closing the control panel, cable replacement, cable rewiring) in order to improve the working efficiency.
• The blown backlight bulb can be confirmed even during screen saving, with the blinked POWER
LED at backlight shutoff detection.
(3) Enhanced support of FA device setup tools
• Transferring or monitoring the sequence programs using the personal computer connected to
GOT, during direct connection to Q, QnA, A or FX series PLC CPU, or computer link connection to A, QnA or Q series (FA Transparent function).
1
2
3
4
5
6
*1 The specifications differ depending on the GOT to be used.
For the specifications, refer to the following.
3.2 Performance Specifications
7
8
1.1 Features 1
- 4
1.2 Rough Pre-operation Procedure
The outline procedure before operating GOT is shown.
Start
Install GT Designer2 in the PC.
Refer to GT Designer2 Version
Basic Operation/Data Transfer Manual
Create project data.
Refer to GT Designer2 Version Screen Design Manual
Wire for the GOT power supply.
Mount the option function board or multi-color display board.
(As necessary)
Refer to Chapter 7 WIRING
Refer to Chapter 8 Option.
When transfer data via a cable.
When transfer data via the memory card.
Connect GOT and PC with a USB cable or
RS-232 cable.
Insert the memory card in the PC.
Install and download the OS program, project data installed in the PC to the GOT.
1) Install standard monitor OS, communication driver,
extended function OS, option OS to the GOT.
After installation is completed, the GOT
automatically restarts.
2) Download the project data created by the PC.
*1
Write the OS, program, project data installed in the PC in the memory card.
1) Write the standard monitor OS, communication
driver, extended function OS, option OS, project
data in the memory card.
Refer to GT Designer2 Version
Basic Operation/Data Transfer
Manual
Refer to Chapter 18 INSTALLATION
OF COREOS, BOOTOS AND
STANDARD OS in this manual for the operations of GOT.
Install the memory card to the GOT to install and download the standard monitor OS, communication driver, extended function OS, option OS, project data to the GOT.
Mount units to GOT.
Check the Communication settings.
Connect the GOT and controller with a cable.
Turn on the power supply of GOT and the system of the connection destination.
Refer to Chapter 8 OPTION.
Refer to GOT1000 Series Connection Manual.
Start the monitor.
End
* 1 Project data can be also downloaded/uploaded via Ethernet.
For download/upload of project data via Ethernet, BootOS and standard monitor OS should be installed in the
GOT in advance so that the GOT and PC can communicate with each other via Ethernet by setting
Communication Settings.
Refer to the following manual for details.
GT Designer2 Version Basic Operation/Data Transfer Manual (Chapter 8 TRANSFERRING DATA)
1
- 5
1.2 Rough Pre-operation Procedure
2. SYSTEM CONFIGURATION
2.1 Overall Configuration
The overall configuration of GOT is as follows.
For the connection methods applicable to GOT1000 series and cable, refer to the following.
GOT1000 Series Connection Manual
Option function board Multi-color display board Protective sheet Stand 3
CF card
4
Extension unit
RS-422 conversion unit
Personal computer
Commercially available
GOT
Battery
5
Bar code reader
6
Memory card
Commercially available
7
CF card Memory card adaptor
8
2.1 Overall Configuration 2
- 1
1
2
2.2 Component List
(1) Explanation of the GOT model name
G T 1 5 7 5 V
Power type
Panel color type
Display device type
Resolution
A : 100 to 240VAC
D : 24VDC
B : Black
T : TFT color (High intensity, Wide angle view)
N : TFT color
S : STN color
L : STN monochrome
X : 1024 768 (XGA)
S : 800 600 (SVGA)
V : 640 480 (VGA)
Q : 320 240 (QVGA)
Video/RGB
Model type
V: Video/RGB compliant
- : (None)
5 : 65536/4096/256 colors*1
2 : 16 colors
0 : Monochrome (White/Black), 16 gray scale
Screen size type
9 : 15"
8 : 12.1"
7 : 10.4"
6 : 8.4"
5 : 5.7"
GOT 1000 series GT15/GT11
*1 For GOTs that can display 65536 colors, refer to the following.
3.2 Performance Specifications
(2) Explanation of the option model name
G T
90 : Dedicated for 15"
80 : Dedicated for 12.1"
75 : Common for 15", 12.1",10.4", 8.4",
(Partially common for 5.7 ") *1
70 : Dedicated for 10.4"
60 : Dedicated for 8.4"
50 : Dedicated for 5.7"
15 : Dedicated for GT15
11 : Dedicated for GT11,
(Partially common for GT15/GT11) *2
09 :
05 :
01 :
Common for GT15/GT11
*1 The bus connection unit (GT15-75QBUSL, GT15-75QBU2L, GT15-75ABUSL,
GT15-75ABUS2L), can also be used with GT155 .
*2 The USB environmental protection cover (GT11-50UCOV) can be used for both the GT15 and GT11.
2
- 2
2.2 Component List
(3) Third party PLC connection cable
G T 0 9 C n
Connector pin type of the connection target
(For third party PLC side)
P: Plug (male)
S: Socket (female)
T: Solderless terminal
C: Preparatory soldering
Number of connector pins
(Indicates the number of terminals for solderless or preparatory-soldered terminals.)
Cable distinction numbers for one manufacturer's products
(Two-digit sequence number: 01, 02, ...)
* When cable distinction is needed for one manufacture's
products
Example) Wirings are different for each PLC type.
Connecting targets are different, such as servo,
inverter, temperature controller.
Cable classification 01: For OMRON PLC
02: For YASKAWA PLC
03: For YOKOGAWA PLC
04: For HITACHI PLC
05: For TOSHIBA PLC
06: For SHARP PLC
07: For Allen-Bradley PLC
08: For SIEMENS PLC
09: For MATSUSHITA PLC
11: For KEYENCE PLC
12: JTEKT PLC
Application classification
(For GOT1000 side)
R4: For RS422 communication
R2: For RS232 communication
Length classification
* Indicated in 10cm unit.
Example) 3m : 30
30m: 300
Third party PLC connection cable
(Commonly used for GT15 and GT11)
1
2
3
4
5
6
7
8
2.2 Component List 2
- 3
2.2.1
GOT
GOT
Product name Model name
GT1595-XTBA
GT1595-XTBD
GT1585V-STBA
GT1585-STBA
GT1585-STBD
GT1575V-STBA
GT1575-STBA
GT1575-STBD
GT1575-VTBA
GT1575-VTBD
GT1575-VNBA
GT1575-VNBD
GT1572-VNBA
GT1572-VNBD
GT1565-VTBA
GT1565-VTBD
Specifications
15" (1024 768 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 100 to 240VAC, Memory size 9MB
15" (1024 768 dots), TFT color liquid crystal (high intensity, wide angle view), 65536 colors*, 24VDC, memory size 9MB
12.1" (800 600 dots), TFT color liquid crystal (high intensity, wide angle view), 65536 colors*, video/RGB compliant, 100 to 240VAC, memory size
9MB
12.1" (800 600 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 100 to 240VAC, Memory size 9MB
12.1" (800 600 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 24VDC, Memory size 9MB
10.4" (800 600 dots), TFT color liquid crystal (high intensity, wide angle view), 65536 colors*, video/RGB compliant, 100 to 240VAC, memory size
9MB
10.4" (800 600 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 100 to 240VAC, Memory size 9MB
10.4" (800 600 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 24VDC, Memory size 9MB
10.4" (640 480 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 100 to 240VAC, Memory size 9MB
10.4" (640 480 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 24VDC, Memory size 9MB
10.4" (640 480 dots), TFT color liquid crystal,
256 colors, 100 to 240VAC, Memory size 5MB
10.4" (640 480 dots), TFT color liquid crystal,
256 colors, 24VDC, Memory size 5MB
10.4" (640 480 dots), TFT color liquid crystal,
16 colors, 100 to 240VAC, Memory size 5MB
10.4" (640 480 dots), TFT color liquid crystal,
16 colors, 24VDC, Memory size 5MB
8.4" (640 480 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 100 to 240VAC, Memory size 9MB
8.4" (640 480 dots), TFT color liquid crystal, (high intensity, wide angle view), 65536 colors*, 24VDC, Memory size 9MB
(Continued to next page)
2
- 4
2.2 Component List
2.2.1 GOT
GOT
Product name Model name
GT1562-VNBA
GT1562-VNBD
GT1555-QTBD
GT1555-QSBD
GT1550-QLBD
Specifications
8.4" (640 480 dots), TFT color liquid crystal,
16 colors, 100 to 240VAC, Memory size 5MB
8.4" (640 480 dots), TFT color liquid crystal,
16 colors, 24VDC, Memory size 5MB
5.7" (320 240 dots), TFT color liquid crystal (high intensity, wide angle view), 65536 colors*, 24VDC, memory size 9MB
5.7" (320 240 dots), STN color liquid crystal, 4096 colors, 24VDC, memory size 9MB
5.7" (320 240 dots), STN monochrome liquid crystal, 16 (Grayscale),
24VDC, memory size 9MB
*: For GOTs that can display 65536 colors, refer to the following.
3.2 Performance Specifications
1
2
3
4
5
6
7
8
2.2 Component List
2.2.1 GOT
2
- 5
2.2.2
Option
Communication unit (Sold separately)
Product name Model name
GT15-QBU
Bus connection unit
GT15-QBUS2
GT15-ABUS
GT15-ABUS2
GT15-75QBUSL
GT15-75QBUS2L
GT15-75ABUSL
GT15-75ABUS2L
Serial communication unit
GT15-RS2
GT15-RS4
GT15-RS4-TE
Ethernet communication unit
GT15-J71E71-100
MELSECNET/H communication unit
GT15-J71LP23-25
GT15-J71BR13
Description
For QCPU (Q Mode)/Motion controller CPU (Q Series) connection (standard model)
For terminal GOT, 1 Channel
For intermediary and terminal GOTs, 2 channels
For A/QnACPU/Motion controller CPU (A Series) connection (standard model)
For terminal GOT, 1 Channel
For intermediary and terminal GOTs, 2 channels
For QCPU (Q Mode)/Motion controller CPU (Q Series) connection (slim model)
For terminal GOT, 1 Channel
For intermediary and terminal GOTs, 2 channels
For A/QnACPU/Motion controller CPU (A Series) connection (slim model)
For terminal GOT, 1 Channel
For intermediary and terminal GOTs, 2 channels
For RS-232 interface connection, connector type
For RS-422 interface connection, connector type
For RS-422 interface connection, terminal block type
Ethernet (100Base-TX/10Base-T) unit
MELSECNET/10 communication unit
CC-Link communication unit
GT15-75J71LP23-Z
GT15-75J71BR13-Z
GT15-J61BT13
GT15-75J61BT13-Z
Optical double loop unit
Coaxial bus unit
Optical loop unit
(A9GT-QJ71LP23 + GT15-75IF900 set)
Coaxial bus unit
(A9GT-QJ71BR13 + GT15-75IF900 set)
Intelligent device station unit
CC-LINK Ver. 2 compliant
Intelligent device station unit
(A8GT-J61BT13 + GT15-75IF900 set)
Interface converter unit
GT15-75IF900 Conversion unit for GOT-A900/GOT800 series communication unit
QCPU (Q Mode) bus connection cable (Sold separately)
Product name
Q extension cable
GOT-to-GOT connection cable
Model name
GT15-QC06B
GT15-QC12B
GT15-QC30B
GT15-QC50B
GT15-QC100B
Cable length 0.6m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 10m
Description
For connecting QCPU and GOT
For connecting GOT and GOT
2
- 6
2.2 Component List
2.2.2 Option
Product name
Q long distance connection cable
GOT-to-GOT long distance connection cable
Model name
GT15-QC150BS
GT15-QC200BS
GT15-QC250BS
GT15-QC300BS
GT15-QC350BS
Description
Cable length 15m
Cable length 20m
Cable length 25m
Cable length 30m
Cable length 35m
For long distance connection (13.2m or longer) of QCPU and GOT (A9GT-QCNB is necessary)
For long distance connection of GOT and GOT
1
2
3
4
7
8
5
6
2.2 Component List
2.2.2 Option
2
- 7
QnA/ACPU/Motion controller (A series) bus connection cable (Sold separately)
Product name
Small-size CPU extension cable
GOT-to-GOT connection cable
Large-size CPU extension cable
Model name
GT15-A1SC07B
GT15-A1SC12B
Cable length 0.7m
Cable length 1.2m
Cable length 3m
Cable length 5m
Description
For connecting QnAS/AnSCPU/Motion controller
CPU (A series) and GOT
GT15-A1SC30B
GT15-A1SC50B
GT15-A1SC05NB
GT15-A1SC07NB
GT15-A1SC30NB
GT15-A1SC50NB
GT15-C12NB
GT15-C30NB
For connecting QnAS/AnSCPU and GOT
Cable length 0.45m
Cable length 0.7m
For connecting QnAS/AnSCPU/motion controller
CPU (A series) and A7GT-CNB
Cable length 3m
Cable length 5m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 0.6m
For connecting QnAS/AnSCPU and A7GT-CNB
For connecting QnA/ACPU/Motion controller
CPU (A series /Extension base) and GOT
GT15-C50NB
GT15-AC06B
GT15-AC12B
GT15-AC30B
Cable length 1.2m
Cable length 3m
For connecting QnA/ACPU/Motion controller
CPU (A series /Extension base) and A7GT-CNB
GT15-AC50B
GT15-A370C12B
GT15-A370C25B
Cable length 5m
GT15-A370C12B-S1 Cable length 1.2m
For connecting Motion controller CPU (A series /
GT15-A370C25B-S1 Cable length 2.5m
Extension base) and GOT
Cable length 1.2m
Cable length 2.5m
For connecting Motion controller CPU (A series /
Extension base) and A7GT-CNB
GT15-C100EXSS-1
Small-size CPU long distance connection cable
GOT-to-GOT long distance connection cable
A0J2HCPU connection cable
Buffer circuit cable
GT15-C200EXSS-1
GT15-C300EXSS-1
GT15-C07BS
GT15-C12BS
GT15-C30BS
GT15-C50BS
GT15-C100BS
GT15-C200BS
GT15-C300BS
GT15-J2C10B
GT15-EXCNB
Cable length 10.6m For long distance connection of QnAS/AnSCPU/ motion controller CPU (A series) and GOT
Cable length 20.6m
For connecting A7GT-CNB and a combined product of the GT15-EXCNB and GT15-C BS (for
Cable length 30.6m
long distance connection)
Cable length 0.7m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 10m
Cable length 20m
Cable length 30m
For connecting GOT and GOT
Cable length 1m
Cable length 0.5m
For connecting A0J2HCPU power supply module
(A0J2-PW) and GOT
Combined with GT15-C BS, can be used as
GT15-C EXSS-1
2
- 8
2.2 Component List
2.2.2 Option
Connection cables for MITSUBISHI PLCs (Sold separately)
Product name Model name Description
GT01-C10R4-8P Cable length 1m
FXCPU direct connection cable,
FX communication function extension board connection cable
GT01-C30R4-8P Cable length 3m
GT01-C100R4-8P Cable length 10m
GT01-C200R4-8P Cable length 20m
For connecting FXCPU (MINI DIN 8 pins connector) and GOT
For connecting FXCPU communication function extension board (MINI DIN 8 pins connector) and GOT
GT01-C300R4-8P Cable length 30m
RS-422 cable
GT01-C30R4-25P Cable length 3m
QnA/A/FXCPU direct connection cable, computer link connection cable
GT01-C100R4-25P Cable length 10m
GT01-C200R4-25P Cable length 20m
For connecting QnA/ACPU/Motion controller
CPU (A series)/FX (FX
1
,FX
2
,FX
2C
) and GOT
For connecting FA-CNV CBL and GOT
For connecting computer link module/serial communication module and GOT
GT01-C300R4-25P Cable length 30m
GT09-C30R4-6C Cable length 3 m
Computer link connection cable
GT09-C100R4-6C Cable length 100 m
GT09-C200R4-6C Cable length 200 m
For connecting computer link module/serial communication module and GOT
GT09-C300R4-6C Cable length 300 m
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option
2
- 9
RS-232 cable
Product name Model name
QCPU direct connection cable
GT01-C30R2-6P
FX communication function extension board connection cable,
FX communication function adapter connection cable, data transfer cable
GT01-C30R2-9S
Cable length 3m
Cable length 3m
FX communication function adaptor connection cable, data transfer cable
GT01-C30R2-25P Cable length 3m
Description
For connecting QCPU and GOT
For connecting FXCPU communication function extension board (D-sub 9 pins connector), FXCPU communication function adapter (D-sub 9 pins connector) and GOT
For connecting personal computer (Drawing software) (D-sub 9 pins: female) and GOT
(D-sub 9 pins: female)
For connecting FXCPU communcation function adaptor (D-sub 25 pins connector) and GOT
For connecting personal computer (Drawing software) (D-sub 25 pins: male) and GOT
(D-sub 9 pins: female)
Computer link connection cable
GT09-C30R2-9P Cable length 3 m
GT09-C30R2-25P Cable length 3 m
For connecting computer link module/serial communication module and GOT
2
- 10
2.2 Component List
2.2.2 Option
Connection cables for OMRON PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40101-9P Cable length 3m
GT09-C100R40101-9P Cable length 10m
GT09-C200R40101-9P Cable length 20m
For connecting GOT to OMRON PLC, serial communication module, serial communication board
GT09-C300R40101-9P Cable length 30m
GT09-C30R40102-9P Cable length 3m
GT09-C100R40102-9P Cable length 10m
GT09-C200R40102-9P Cable length 20m
GT09-C300R40102-9P Cable length 30m
For connecting GOT to OMRON rack type host link unit, communication board
GT09-C30R20101-9P Cable length 3m
For connecting GOT to OMRON PLC, serial communication module, communication board, serial communication board
GT09-C30R20102-25P Cable length 3m For connecting GOT to OMRON connection cable
GT09-C30R20103-25P Cable length 3m For connecting GOT to OMRON rack type host link unit
Connection cables for KEYENCE PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R41101-5T Cable length 3m
GT09-C100R41101-5T Cable length 10m
GT09-C200R41101-5T Cable length 20m
GT09-C300R41101-5T Cable length 30m
GT09-C30R21101-6P
GT09-C30R21102-9S
GT09-C30R21103-3T
Cable length 3m
Cable length 3m
Cable length 3m
For connecting GOT to KEYENCE multi-communication unit
For connecting GOT to KEYENCE PLC
For connecting GOT to KEYENCE multi-communication unit
For connecting GOT to KEYENCE multi-communication unit
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option
2
- 11
Connection cables for JTEKT PLCs (Sold separately)
Product name
Model name
RS-422 cable
GT09-C30R41201-6C Cable length 3 m
GT09-C100R41201-6C Cable length 10 m
GT09-C200R41201-6C Cable length 20 m
GT09-C300R41201-6C Cable length 30 m
Description
For connecting GOT to JTEKT PLC
RS-232 cable
GT09-C30R21201-25P Cable length 3 m For connecting GOT to JTEKT PLC
Connection cables for SHARP PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40601-15P Cable length 3m
GT09-C100R40601-15P Cable length 10m
GT09-C200R40601-15P Cable length 20m
GT09-C300R40601-15P Cable length 30m
GT09-C30R40602-15P Cable length 3m
GT09-C100R40602-15P Cable length 10m
GT09-C200R40602-15P Cable length 20m
For connecting GOT to SHARP PLC
For connecting GOT to SHARP PLC
GT09-C300R40602-15P Cable length 30m
GT09-C30R40603-6T Cable length 3m
GT09-C100R40603-6T Cable length 10m
GT09-C200R40603-6T Cable length 20m
For connecting GOT to SHARP link unit
GT09-C300R40603-6T Cable length 30m
GT09-C30R20601-15P Cable length 3m For connecting GOT to SHARP PLC
GT09-C30R20602-15P Cable length 3m For connecting GOT to SHARP PLC
Connection cables for TOSHIBA PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40501-15P Cable length 3m
GT09-C100R40501-15P Cable length 10m
GT09-C200R40501-15P Cable length 20m
GT09-C300R40501-15P Cable length 30m
GT09-C30R40502-6C Cable length 3m
GT09-C100R40502-6C Cable length 10m
GT09-C200R40502-6C Cable length 20m
For connecting GOT to TOSHIBA PLC
For connecting GOT to TOSHIBA PLC
GT09-C300R40502-6C Cable length 30m
GT09-C30R40503-15P Cable length 3m
GT09-C100R40503-15P Cable length 10m
GT09-C200R40503-15P Cable length 20m
For connecting GOT to TOSHIBA PLC
GT09-C300R40503-15P Cable length 30m
GT09-C30R20501-9P Cable length 3m For connecting GOT to TOSHIBA PLC
GT09-C30R20502-15P Cable length 3m For connecting GOT to TOSHIBA PLC
2
- 12
2.2 Component List
2.2.2 Option
Connection cables for HITACHI PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40401-7T Cable length 3m
GT09-C100R40401-7T Cable length 10m
GT09-C200R40401-7T Cable length 20m
For connecting GOT to HITACHI intelligent serial port module
GT09-C300R40401-7T Cable length 30m
GT09-C30R21101-6P
GT09-C30R21103-3T
Cable length 3m
For connecting GOT to HITACHI PLC, intelligent serial port module
Cable length 3m For connecting GOT to HITACHI PLC
Connection cables for MATSUSHITA PLCs (Sold separately)
Product name
Model name
RS-232 cable
GT09-C30R20901-25P Cable length 3m
GT09-C30R20902-9P
GT09-C30R20903-9P
GT09-C30R20904-3C
Cable length 3m
Cable length 3m
Cable length 3m
Description
For connecting GOT to MATSUSHITA RS422/232C conversion adapter
For connecting GOT to the tool port or RS232C port of
MATSUSHITA PLC, computer communication unit
For connecting GOT to the RS232C port of MATSUSHITA
PLC
For connecting GOT to the RS232C port of MATSUSHITA
PLC
Connection cables for YASKAWA PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40201-9P Cable length 3m
GT09-C100R40201-9P Cable length 10m
GT09-C200R40201-9P Cable length 20m
GT09-C300R40201-9P Cable length 30m
GT09-C30R40202-14P Cable length 3m
GT09-C100R40202-14P Cable length 10m
GT09-C200R40202-14P Cable length 20m
GT09-C300R40202-14P Cable length 30m
For connecting GOT to YASKAWA MEMOBUS module
For connecting GOT to YASKAWA PLC
GT09-C30R20201-9P Cable length 3m
GT09-C30R20202-15P Cable length 3m
GT09-C30R20203-9P Cable length 3m
GT09-C30R20204-14P Cable length 3m
For connecting GOT to YASKAWA PLC
GT09-C30R20205-25P Cable length 3m For connecting GOT to YASKAWA MEMOBUS module
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option
2
- 13
Connection cables for YOKOGAWA PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40301-6T Cable length 3m
GT09-C100R40301-6T Cable length 10m
GT09-C200R40301-6T Cable length 20m
GT09-C300R40301-6T Cable length 30m
GT09-C30R40302-6T Cable length 3m
GT09-C100R40302-6T Cable length 10m
GT09-C200R40302-6T Cable length 20m
For connecting GOT to YOKOGAWA PC link module
GT09-C300R40302-6T Cable length 30m
GT09-C30R20301-9P
GT09-C30R20302-9P
Cable length 3m
For connecting GOT to YOKOGAWA CPU port/D-Sub 9-pin conversion cable
Cable length 3m For connecting GOT to YOKOGAWA PC link module
Connection cables for Allen-Bradley PLCs (Sold separately)
Product name
RS-232 cable
Model name
GT09-C30R20701-9S
Description
Cable length 3m For connecting GOT to Allen-Bradley PLC
Connection cables for SIEMENS PLCs (Sold separately)
Product name
RS-232 cable
Model name
GT09-C30R20801-9S
Description
Cable length 3m For connecting GOT to SIEMENS HMI Adapter
RS-422 conversion unit (Sold separately)
Product name
RS-422 conversion unit
Model name
GT15-RS2T4-9P
GT15-RS2T4-25P conversion unit
Description
RS-422 side connector 9 pins
RS-422 side connector 25 pins
Bus extension connector box (Sold separately)
Product name
Bus extension connector box
Model name
A9GT-QCNB
Description
For QCPU (Q Mode)/Motion controller CPU (Q series) long distance
(13.2m or longer) bus connection
Bus connector conversion box (Sold separately)
Product name
Bus connector conversion box
Model name
A7GT-CNB
Description
For QnA/ACPU/Motion controller CPU (A series) long distance bus connection (For conversion from large type connector to small type connector)
2
- 14
2.2 Component List
2.2.2 Option
CF card (Sold separately)
Product name
CF card
Model name
GT05-MEM-16MC
GT05-MEM-32MC
GT05-MEM-64MC
GT05-MEM-128MC
GT05-MEM-256MC
Flash ROM 16MB
Flash ROM 32MB
Flash ROM 64MB
Flash ROM 128MB
Description
Flash ROM 256MB
Commercially-available CF card
*2
*2: Some models with the operations checked by our company are usable.
For the operation-checked models, refer to "List of valid devices applicable for GOT1000 series" (T10-0039) separately available.
The Technical News above is available as a reference at the information site for Mitsubishi industrial automation products MELFANSweb home page.
(MELFANSweb website: http://wwwf2.mitsubishielectric.co.jp/english/index.html)
Bar code reader (Sold separately)
Product name
Bar code reader
Model name Description
Commercially-available bar code reader
*3
*3: Some models with the operations checked by our company are usable.
For the operation-checked models, refer to "List of valid devices applicable for GOT1000 series" (T10-0039) separately available.
The Technical News above is available as a reference at the information site for Mitsubishi industrial automation products MELFANSweb home page.
(MELFANSweb website: http://wwwf2.mitsubishielectric.co.jp/english/index.html)
Memory card adaptor (Sold separately)
Product name Model name
Memory card adaptor GT05-MEM-ADPC
Description
CF card to memory card (Type II) conversion adaptor
Option function board (Sold separately)
Product name Model name
Option function board
GT15-FNB
GT15-QFNB
GT15-QFNB16M
GT15-QFNB32M
GT15-QFNB48M
Description
Option function board
Applicable for MELSEC-A/FX ladder monitor function
Option function board
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multichannel function
Option function board with add-on memory (Option function+16MB)
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multichannel function
Option function board with add-on memory (Option function+32MB)
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multichannel function
Option function board with add-on memory (Option function+48MB)
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multichannel function
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option
2
- 15
Multi color display board (Sold separately)
Product name Model name Description
Multi-color display board
GT15-XHNB
Multi-color display board for XGA (For 65536-color display)
Multi-color display board for SVGA/VGA (For 65536-color display)
GT15-VHNB Multi-color display board for SVGA/VGA (For 65536-color display)
*4: To use it for a SVGA or VGA GOT, install the following OS to the GOT.
*4
(Cannot be used for a SVGA or VGA GOT without installing the OS.)
BootOS Ver. 02.01.00.E or later
Standard monitor OS: Ver. 02.01.00 or later
For how to install the OS, refer to GT Designer2 Version Basic Operation/Data Transfer Manual.
Option unit (Sold separately)
Product name Model name
Printer unit GT15-PRN
Video input unit GT15V-75V4
RGB input unit GT15V-75R1
Video/RGB input unit GT15V-75V4R1
RGB output unit GT15V-75ROUT
Description
For connecting a printer
USB slave (PictBridge) 1 channel
For NTSC/PAL input 4 channels
For analog RGB input 1 channel
For NTSC/PAL (4ch)/analog RGB (1ch) mixed input
For analog RGB output
Dedicated printer connection cable (Sold separately)
Product name
Dedicated printer connection cable
Model name
GT09-C30USB-5P
*5 Cable length 3m
*5: At printer unit purchase, it is included with the unit.
Stand (Sold separately)
Product name
Stand
Model name
GT15-90STAND
GT15-80STAND
GT15-70STAND
GT05-50STAND
Stand for 15"
Stand for 12.1"
Stand for 8.4"/10.4"
Stand for 5.7"
Description
For connecting GOT (USB mini) to printer (USB)
Description
Battery (Sold separately)
Product name
Battery
Model name
GT15-BAT
Description
Battery for clock data and maintenance report data backups
2
- 16
2.2 Component List
2.2.2 Option
Protective sheet (Sold separately)
Product name
Protective sheet
Model name
GT15-90PSCB
GT15-90PSGB
GT15-90PSCW
GT15-90PSGW
GT15-80PSCB
GT15-80PSGB
GT15-80PSCW
GT15-80PSGW
GT15-70PSCB
GT15-70PSGB
GT15-70PSCW
GT15-70PSGW
GT15-60PSCB
GT15-60PSGB
GT15-60PSCW
GT15-60PSGW
GT15-50PSCB
GT15-50PSGB
GT15-50PSCW
GT15-50PSGW
15" protective sheet
12.1" protective sheet
10.4" protective sheet
8.4" protective sheet
5.7" protective sheet
Description
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: white) 5 sheets
Antiglare (Frame: white) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: white) 5 sheets
Antiglare (Frame: white) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: white) 5 sheets
Antiglare (Frame: White) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: white) 5 sheets
Antiglare (Frame: white) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: white) 5 sheets
Antiglare (Frame: white) 5 sheets
Backlight (Sold separately)
Product name
Backlight
*6
Model name
GT15-90XLTT
GT15-80SLTT
GT15-70SLTT
Description
For 15" high intensity, wide angle view TFT (XGA) GT1595-X
For 12.1" high intensity, wide angle view TFT (SVGA) GT1585V-S, GT1585-S
GT15-70VLTT
GT15-70VLTN
GT15-60VLTT
GT15-60VLTN
For 10.4" high intensity, wide angle view TFT (SVGA) GT1575-S
For 10.4" high intensity, wide angle view TFT (SVGA,
VGA)
GT1575V-S, GT1575-V
For 10.4" TFT (VGA)
For 8.4" high intensity, wide angle view TFT (VGA)
For 8.4" TFT (VGA)
*6: At GOT purchase, it is installed in the main unit.
GT1575-VN, GT1572-VN
GT1565-V
GT1562-VN
USB environmental protection cover (Sold separately)
Product name Model name
GT15-UCOV
Description
Environmental cover for USB interface on the GOT main unit front side (For complying IP67) USB environmental protection cover
*7
GT11-50UCOV
Environmental cover for USB interface on the GOT main unit front side (For complying IP67)
*7: At GOT purchase, it is installed in the main body.
15", 12.1", 10.4", 8.4"
5.7"
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option
2
- 17
Attachment (Sold separately)
Product name
Attachment
Model name
GT15-60ATT-96
GT15-60ATT-97
For 8.4" attachment
Description
A97 GOT GT1565
Drawing software (Sold separately)
Product name
GT Designer2
Model name
SW D5C-GTD2-J
( indicates the version)
*8
Description
Drawing software for GOT1000/GOT900 series
* 8: The is assigned with an integer 2 or more.
PC connection cable (Sold separately)
Product name Model name
GT01-C30R2-9S Cable length 3m
Project data transfer cable
GT01-C30R2-25P
GT01-C20USB-5P
GT09-C30USB-5P
Cable length 3m
Cable length 2m
Cable length 3m
Description
For connecting GOT (D sub 9-pin female) and PC (D sub 9-pin female)
For connecting GOT (D sub 9-pin female) and PC (D sub 25-pin male)
For connecting GOT (USB mini) and PC
(USB)
For connecting GOT (USB mini) and PC
(USB)
2
- 18
2.2 Component List
2.2.2 Option
3. SPECIFICATIONS
3.1 General Specifications
Operating ambient temperature *1
Item
Display section 0 to 50°C
Other than display section
Storage ambient temperature
0 to 55°C
-20 to 60°C
Operating ambient humidity *6
Storage ambient humidity *6
10 to 90% RH, non-condensing
10 to 90% RH, non-condensing
Vibration resistance
Shock resistance
*2
Specifications
Conforms to
JIS B3502 and
IEC61131-2
Under intermittent vibration
Under continuous vibration
Frequency
5 to 9Hz
9 to 150Hz
5 to 9Hz
9 to 150Hz
Acceleration
-
9.8m/s
-
4.9m/s
2
2
Halfamplitude
3.5mm
-
1.75mm
-
Sweep Count
10 times each in X, Y and Z directions
Conforms to JIS B3502, IEC 61131-2 (147 m/s
2
, 3 times each in X, Y and Zdirections)
No corrosive gas Operating atmosphere
Operating altitude
*3
Installation location
2000 m (6562 ft) max.
Inside control panel
Overvoltage category
*4
Pollution degree
*5
Cooling method
II or less
2 or less
Self-cooling
*1 When mounting an extension unit on the upper stage of MELSECNET/H communication unit (GT15-J71LP23-25,
GT15-J71BR13) or CC-Link communication unit (GT15-J61BT13), the operating ambient temperature must be reduced 5°C against the maximum values described in general specifications.
*2 When using the MELSECNET/10 communication unit (GT15-75J71LP23-Z, GT15-75J71BR13-Z) or CC-Link communication unit (GT15-75J61BT13-Z), refer to the manual of the communication unit you use. (Differs with the specification of GOT.)
*3 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.
*4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.
*5 This index indicates the degree to which conductive material is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
*6 The wet-bulb temperature is 39°C or less for STN LCDs.
2
3
4
5
6
7
8
1
3.1 General Specifications 3
- 1
3.2 Performance Specifications
The performance specifications of the GT15 is as follows.
• 3.2.3 GT1575V-S, GT1575-S, GT1575-V, GT1575-VN, GT1572-VN
3.2.1
GT1595-X
3
- 2
Display section
*1
Backlight
Type
Screen size
Resolution
Display size
Display character
Display color
Display angle
Intensity of LCD only
Intensity adjustment
Life
Life
Item
*3
Number of Touch key
Key size
Number of objects that Touch panel can be simultaneously
Human sensor touched
Life
Detection length
Detection range
Detection delay time
C drive
Life (Number of Memory
*4 write times)
Battery
Backup target
Life
Buzzer output
Specifications
GT1595-XTBA GT1595-XTBD
TFT color liquid crystal display (High intensity and wide angle view)
15"
1,024 768 dots
304.1(12.0)(W) 228.1(8.98)(H) [mm](inch)
16-dot standard font: 64 characters 48 lines
12-dot standard font : 85 characters 64 lines
65536color
*2
Left/Right : 75 degrees
Top : 50 degrees
Bottom : 60 degrees
450 [cd/m²]
8-level adjustment
Approx. 52,000 h (Operating ambient temperature : 25°C)
Cold cathode fluorescent tube (replaceable) backlight shutoff detection function is included
Backlight off/screen saving time can be set.
Approx. 50,000 h or longer
(Time when display luminance reaches 50% at the operating ambient temperature of 25°C)
3,072 objects/screen (48 lines 64 columns)
Minimum 16 x 16 dots (per key)
Simultaneous presses not allowed
(Only 1 point can be touched)
1 million times or more (operating force 0.98N max.)
1(39.37) [m](inch)
Left/Right/Top/Bottom: 70 degrees
0 to 4s
Built-in flash memory 9Mbytes (for storing project data and OS)
100,000 times
GT15-BAT lithium battery (Option)
Clock data and maintenance time notification data
Approx. 5 years (Operating ambiant temperature of 25°C)
Single tone (tone length adjustable)
(Continued to next page)
3.2 Performance Specifications
3.2.1 GT1595-X
Item
RS-232
*6
Specifications
RS-232, 1ch
GT1595-XTBA
Application :
GT1595-XTBD
Transmission speed : 115,200/57,600/38,400/19,200/9,600/4,800 bps
Connector shape : D-sub 9-pin (Male)
For communicating with a controller or connecting a personal computer (Project data upload/doxnload, OS
Built-in interface
USB installation, transparent function)
USB (Full Speed 12Mbps), 1ch
Connector shape : Mini-B
Application : PC communication ( screen data upload/download, OS installation and FA transparent function)
Compact flash slot, 1ch
Connector shape : TYPE I CF card
Application : Data transfer, data storage
Option function board For option function board mounting, 1ch
Multi-color display board For multi-color display board mounting, 1ch
Extension unit
*6
Buzzer output
Protective structure
For communication unit/option unit mounting, 2ch
Single tone (tone length adjustable)
Inside the enclosure: IP67
*5
Outside the enclosure: IP2X
External dimension
397(15.6)(W) x 296(11.7)(H) 61(2.40)(D)[mm](inch) (Excluding USB environmental protection cover)
Panel cutting dimensions
Weight
Compatible software package
(GT Designer2 Version)
4.9kg (mounting fixtures are not included)
2.17T or later 2.32J or later
*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel due to its characteristics.
It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Please note that these dots appear due to its characteristic and are not caused by product defect.
*2 With the hardware version indicated below, it will be 256 colors when the multi-color display board is not installed.
For how to confirm the function version, refer to the following.
Appendix Confirming of Versions and Conformed Standards
Item
GT1595
Model
GT1595-XTBA A
Function version
*3 The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*4 ROM in which new data can be written without deleting the written data.
*5 Compliant with IP67 when the USB environmental protection cover is attached. Compliant with IP2X at the USB interface only when a USB cable is connected. Note that this does not guarantee all users' operation environment.
*6 When using multiple extension units and a bar code reader, the total current of the extension units and bar code reader must not be greater than the total current that the GOT can supply.
For current values of extension units and bar code reader and the total current that the GOT can supply, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.8 Multi-channel Function)
1
2
3
4
5
6
7
8
3.2 Performance Specifications
3.2.1 GT1595-X
3
- 3
3.2.2
GT1585V-S, GT1585-S
Display section*1
Backlight
Touch panel
Human
Sensor
Memory
*4
Battery
Item
Display color
GT1585V-STBA
Specifications
GT1585-STBA
Type
Screen size
Resolution 800 600
Display size 246(9.69)(W) 184.5(7.26)(H) [mm](inch)
Display character
16-dot standard font: 50 characters 37 lines
12-dot standard font: 66 characters 50 lines
65536color *2
GT1585-STBD
TFT color liquid crystal display (High intensity and wide angle view)
12.1”
Left/Right : 60 degrees
Display angle
Intensity of LCD only
Intensity adjustment
Life
Top : 40 degrees
Bottom : 50 degrees
350 [cd/m
2
]
8-level adjustment
Approx. 50,000 h (Operating ambient temperature : 25°C)
Cold cathode fluorescent tube (replaceable) backlight shutoff detection function is
Life *3
Number of touch keys included.
Backlight off/screen saving time can be set.
Approx. 50,000 h or longer
(Time when display luminance reaches 50% at the operating ambient temperature of 25
°
C)
1,900 objects/screen
(Matrix structure of 38 lines 50 columns)
Minimum 16 16 dots (16 8 dots for the last line only) (per key) Key size
Number of objects that can be simultaneously touched
Life
Detection length
Detection range
Detection delay time
C drive
Life (Number of write times)
Maximum of 2 objects
1 million times or more (operating force 0.98N max.)
1(39.37) [m](inch)
Left/Right/Top/Bottom: 70 degrees
0 to 4s
Built-in flash memory 9Mbytes (for storing project data and OS)
100,000 times
Backup target
Life
GT15-BAT lithium battery (Option)
Clock data and maintenance time notification data
Approx. 5 years (Operating ambient temperature of 25
°
C)
(Continued to next page)
3
- 4
3.2 Performance Specifications
3.2.2 GT1585V-S, GT1585-S
1
Built-in interface
RS-232
USB
Item
*6
RS-232, 1ch
GT1585V-STBA
Application
Specifications
GT1585-STBA GT1585-STBD
Transmission speed : 115,200/57,600/38,400/19,200/9,600/4,800 bps
Connector shape : D-sub 9-pin (Male)
: For communicating with a controller or connecting a personal computer (Project data upload/download, OS installation, transparent function)
USB (Full Speed 12Mbps), 1ch
Connector shape : Mini-B
Application : PC communication (screen data upload/download, OS installation and FA transparent function)
Compact flash slot, 1ch
Connector shape : TYPE I CF card
Application : Data transfer, data storage
Option function board For option function board mounting, 1ch
Multi-color display board For multi-color display board mounting, 1ch
Extension unit *6 For communication unit/option unit mounting, 2ch
Buzzer output
Protective structure
Single tone (tone length adjustable)
Inside the enclosure: IP67 *5
Outside the enclosure: IP2X
External dimensions
316(12.44)(W) × 242(9.53)(H) × 52(2.05)(D) [mm](inch) (Excluding USB environmental protection cover)
Panel cutting dimensions
Weight
Compatible software package
(GT Designer2 Version)
302(11.89)(W) × 228(8.98)(H)[mm](inch)
2.8 kg (mounting fixtures are not included)
2.32J or later 2.04E or later 2.17T or later
*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel due to its characteristics.
It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Please note that these dots appear due to its characteristic and are not caused by product defect.
*2 With the hardware version indicated below, it will be 256 colors when the multi-color display board is not installed.
For how to confirm the function version, refer to the following.
Appendix Confirming of Versions and Conformed Standards
Item
GT1585
Model
GT1585-STBA
GT1585-STBD
A
A
Function version
*3 The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*4 ROM in which new data can be written without deleting the written data.
*5 Compliant with IP67 when the USB environmental protection cover is attached. Compliant with IP2X at the USB interface only when a USB cable is connected. Note that this does not guarantee all users' operation environment.
*6 When using multiple extension units and a bar code reader, the total current of the extension units and bar code reader must not be greater than the total current that the GOT can supply.
For current values of extension units and bar code reader and the total current that the GOT can supply, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.8 Multi-channel Function)
2
3
4
5
6
7
8
3.2 Performance Specifications
3.2.2 GT1585V-S, GT1585-S
3
- 5
3.2.3
GT1575V-S, GT1575-S, GT1575-V, GT1575-VN, GT1572-VN
3
- 6
Display section
*1
Backlight
Touch panel
Human sensor
Item
Type
Screen size
Resolution
Display size
Display character
Display color
Display angle
Specifications
GT1575V-STBA
GT1575-STBA,
GT1575-STBD
GT1575-VTBA,
GT1575-VTBD
GT1575-VNBA,
GT1575-VNBD,
GT1572-VNBA,
GT1572-VNBD
TFT color liquid crystal (LCD of high intensity and wide angle view)
10.4"
800 600dots
211(8.31)(W) 158(6.22)(H)[mm](inch)
640 480dots
16-dot standard font:
50 characters 37 lines
12-dot standard font:
66 characters 50 lines
65536color
*2
Left/Right/Top/
Bottom:
85 degrees
Left/Right: 50 degrees
Top: 35 degrees
Bottom: 45 degrees
TFT color liquid crystal
16-dot standard font:40 characters 30 lines
12-dot standard font:53 characters 40 lines
GT1575-VN:
256color
GT1572-VN:
16color
Left/ Right/Top/
Bottom:
85 degrees
Left/Right: 45 degrees
Top: 30 degrees
Bottom: 20 degrees
Intensity of LCD only 400[cd/m 2 ]
Intensity adjustment 8-level adjustment
280[cd/m 2 ] 380[cd/m 2 ] 200[cd/m 2 ]
4-level adjustment
Life
Life
*3
Number of touch keys
Key size
Approx. 50,000 h
(Operating ambient temparature: 25°C)
Cold cathode fluorescent tube (replaceable) backlight shutoff detection function is included.
Backlight off/screen saving time can be set.
Approx. 40,000 h or longer (Time when display luminance reaches 50% at the operating ambient temperature of 25°C)
1,900 objects/screen
(Matrix structure of 38 lines 50 columns)
Minimum 16 16 dots (16 8 dots for the last line only)(per key)
Approx. 41,000 h
(Operating ambient temparature:25°C)
1,200 objects/screen (Matrix structure of
30 lines 40 columns)
Minimum 16 16 dots (per key)
Number of objects that can be simultaneously touched
Life
Detection length
Maximum of 2 objects
1 million times or more (operating force 0.98 max.)
None
Detection range None
Detection delay time None
(Continued to next page)
3.2 Performance Specifications
3.2.3 GT1575V-S, GT1575-S, GT1575-V, GT1575-VN, GT1572-VN
1
Specifications
Memory *4
Item
C drive
GT1575V-STBA
GT1575-STBA,
GT1575-STBD
Built-in flash memory 9Mbytes
(for storing project data and OS)
GT1575-VTBA,
GT1575-VTBD
GT1575-VNBA,
GT1575-VNBD,
GT1572-VNBA,
GT1572-VNBD
Built-in flash memory 5Mbytes
(for storing project data and OS)
Life (Number of write times)
100,000 times
Batery
Backup target
Life
RS-232 *6
GT15-BAT lithium battery (Option)
Clock data and maintenance time notification data
Approx. 5 years (Operating ambient temperature of 25°C)
RS-232, 1ch
Transmission speed: 115,200/57,600/38,400/19,200/9,600/4,800 bps
Connector shape: D-sub 9-pin (Male)
Application: For communicating with a controller or connecting a personal computer (Project data upload/download, OS installation, FA transparent function)
USB (Full Speed 12 Mbps), 1ch
Built-in interface
USB
Connector shape: Mini-B
Application: For connecting a personal computer (Project data upload/download,
OS installation and FA transparent function)
Compact flash slot, 1ch
CF card Connector shape: TYPE I
Application: Data transfer, data storage
Option function board For option function board mounting, 1ch
Multi-color display board For multi-color display board mounting, 1ch
Cannot be used.
(Even installed,
65536 colors will not be displayed.)
Extension unit *6
Buzzer output
Protective structure
For communication unit/option unit mounting, 2ch
Single tone (tone length adjustable)
Outside the enclosure: IP67*5
Inside the enclosure: IP2X
External dimensions
(Excluding USB environmental protective cover)
Panel cutting dimensions
Weight
Compatible software package
(GT Designer2 Version)
289(11.38)(W) 200(7.87)(H)[mm](inch)
2.3 kg
(mounting fixtures
2.4 kg are not included)
(mounting fixtures are not included)
GT1575-STBA: GT1575-VTBA:
GT1575V-STBA:
2.32J or later
2.04E or later
GT1575-STBD:
2.04E or later
GT1575-VTBD:
2.3 kg (mounting fixtures are not included)
2.17T or later
2.17T or later 2.17T or later
*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel due to its characteristics.
It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Please note that these dots appear due to its characteristic and are not caused by product defect.
2
3
4
5
6
7
8
3.2 Performance Specifications
3.2.3 GT1575V-S, GT1575-S, GT1575-V, GT1575-VN, GT1572-VN
3
- 7
*2 With the hardware version indicated below, it will be 256 colors when the multi-color display board is not installed.
For how to confirm the function version, refer to the following.
Appendix Confirming of Versions and Conformed Standards
Item
GT1575
Model
GT1575-STBA
GT1575-STBD
GT1575-VTBA
GT1575-VTBD
A
A
A
A
Function version
*3 The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*4 ROM in which new data can be written without deleting the written data.
*5 Compliant with IP67 when the USB environmental protection cover is attached. Compliant with IP2X at the USB interface only when a USB cable is connected. Note that this does not guarantee all users' operation environment.
*6 When using multiple extension units and a bar code reader, the total current of the extension units and bar code reader must not be greater than the total current that the GOT can supply.
For current values of extension units and bar code reader and the total current that the GOT can supply, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.8 Multi-channel Function)
3
- 8
3.2 Performance Specifications
3.2.3 GT1575V-S, GT1575-S, GT1575-V, GT1575-VN, GT1572-VN
3.2.4
GT1565-V, GT1562-VN
1
Display section
*1
Backlight
Touch panel
Human sensor
Memory
*4
Battery
Type
Intensity of LCD only
Intensity adjustment
Life
Item
Screen size
Resolution
Display size
Display character
Display color
Display angle
Specifications
GT1565-VTBA, GT1565-VTBD GT1562-VNBA, GT1562-VNBD
TFT color liquid crystal (LCD of high
TFT color liquid crystal intensity and wide angle view)
8.4"
640×480dots
171(6.73)(W)×128(5.04)(H)[mm](inch)
16-dot standard font: 40 characters × 30 lines
12-dot standard font: 53 characters × 40 lines
65536color
*2
Left/Right : 65degrees
16color
Left/Right : 45degrees
Top : 50 degrees
Bottom : 60 degrees
Top
Bottom
: 20 degrees
: 20 degrees
380[cd/m
2
]
8-level adjustment
150[cd/m
2
]
4-level adjustment
Approx. 41,000 h (Operating ambient temperature: 25°C)
Cold cathode fluorescent tube (replaceable) backlight shutoff detection function is included.
Backlight off/screen saving time can be set.
Approx. 40,000 h or longer
Life
*3
Key size
Number of objects that
(Time when display luminance reaches 50% at the operating ambient temperature of 25°C)
Numbers of touch key 1,200 objects/screen (Matrix structure of 30 lines × 40 columns)
Minimum 16 × 16 dots (par key) can be simultaneously Maximum of 2 objects touched
Life
Detection length
Detection range
Detection delay time
C drive
1 million times or more (operating force 0.98N max.)
None
None
None
Built-in flash memory 9Mbytes
(for string project data and OS)
Built-in flash memory 5Mbytes
(for string project data and OS)
Life (Number of write times)
100,000 times
Backup target
Life
GT-15BAT lithium battery (Option)
Clock data and maintenance time notification data
Approx. 5 years (Operating ambient temperature of 25°C)
(Continued to next page)
2
3
4
5
6
7
8
3.2 Performance Specifications
3.2.4 GT1565-V, GT1562-VN
3
- 9
Item
RS-232
*6
Specifications
GT1565-VTBA, GT1565-VTBD GT1562-VNBA, GT1562-VNBD
RS-232, 1ch
Transmission speed : 115,200/57,600/38,400/19,200/9,600/4,800 bps
Connector shape : D-sub 9-pin (Male)
Application : For communicating with a controller or connecting a personal computer (Project data upload/download, OS installation and FA transparent function)
USB (Full Speed 12 Mbps), 1ch
Built-in interface
USB
Connector shape : Mini-B
Application : For communicating a personal computer (Project data upload/
(Excluding USB environmental protective cover)
Panel cutting dimensions
Weight
Compatible software package
(GT Designer2 Version) download, OS installation and FA transparent function)
Compact flash slot, 1ch
Connector shape : TYPE 1 CF card
Application : Data transfer, data storage
Option function board For option function board mounting, 1ch
Multi-color display board
For multi-color display board mounting, Cannot be used. (Even installed, 65536
1ch colors will not be displayed.)
Extension unit
*6
Buzzer output
Protective structure
For communication unit/option unit mounting, 2ch
Single tone (tone length adjustable)
Outside the enclosure: IP67
*5
Inside the enclosure: IP2X
External dimensions
241(9.49)(W)×190(7.48)(H)×52(2.05)(D)[mm](inch)
227(8.94)(W)×176(6.93)(H)[mm](inch)
1.9 kg (mounting fixtures are not included)
GT1565-VTBA:2.04E or later,
GT1565-VTBD:2.17T or later
2.17T or later
*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel due to its characteristics.
It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Please note that these dots appear due to its characteristic and are not caused by product defect.
*2 With the hardware version indicated below, it will be 256 colors when the multi-color display board is not installed.
For how to confirm the function version, refer to the following.
Appendix Confirming of Versions and Conformed Standards
Item
GT1565
Model
GT1565-VTBA
GT1565-VTBD
A
A
Function version
*3 The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*4 ROM in which new data can be written without deleting the written data.
*5 Compliant with IP67 when the USB environmental protection cover is attached. Compliant with IP2X at the USB interface only when a USB cable is connected. Note that this does not guarantee all users' operation environment.
*6 When using multiple extension units and a bar code reader, the total current of the extension units and bar code reader must not be greater than the total current that the GOT can supply.
For current values of extension units and bar code reader and the total current that the GOT can supply, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.8 Multi-channel Function)
3
- 10
3.2 Performance Specifications
3.2.4 GT1565-V, GT1562-VN
3.2.5
GT1555-Q, GT1550-Q
1
Display section
*1
Backlight
Touch panel
Human sensor
Memory
*3
Battery
Type
Item
GT1555-QTBD
TFT color liquid crystal
Specifications
GT1555-QSBD
(LCD of high intensity and STN color liquid crystal wide angle view)
5.7"
STN monochrome liquid crystal
GT1550-QLBD
Screen size
Resolution
Display size
Display character
Display color
Display angle
Intensity of LCD only
Intensity adjustment
Contrast adjustment
Life
115(4.53)(W) 86(3.39)(H)[mm](inch)
16-dot standard font: 20 characters 15 lines
12-dot standard font: 26 characters 20 lines
65536color
*2
Left/Right : 70 degrees
Top : 70 degrees
4096color
Left/Right : 55 degrees
Top : 65 degrees monochrome
(16-level)
Left/Right : 45 degrees
Top : 20 degrees
Bottom : 50 degrees
400[cd/m
2
]
8-level adjustment
Bottom
380[cd/m
2
]
: 70 degrees Bottom
220[cd/m
2
]
: 40 degrees
None 16-level adjustment
Approx. 50,000 h (Operating ambient temperature: 25°C)
Cold cathode fluorescent tube (nonreplaceable) backlight shutoff detection function is included.
Backlight off/screen saving time can be set.
Life
*2
Approx. 75,000 h or longer
(Time when display luminance reaches 50% at the operating ambient temperature of 25°C)
Approx. 58,000 h or longer
(Time when display luminance reaches 50% at the operating ambient temperature of 25°C)
Numbers of touch key 300 objects/screen (Matrix structure of 15 lines 20 columns)
Key size Minimum 16 16 dots (par key)
Number of objects that can be simultaneously Maximum of 2 objects touched
Life
Detection length
Detection range
Detection delay time
C drive
1 million times or more (operating force 0.98N max.)
None
None
None
Built-in flash memory 9Mbytes
(for string project data and OS)
Life (Number of write times)
100,000 times
Backup target
Life
GT15-BAT lithium battery (Option)
Clock data and maintenance time notification data
Approx. 5 years (Operating ambient temperature of 25°C)
(Continued to next page)
2
3
4
5
6
7
8
3.2 Performance Specifications
3.2.5 GT1555-Q, GT1550-Q
3
- 11
Item
GT1555-QTBD
RS-232, 1ch
Specifications
GT1555-QSBD GT1550-QLBD
Transmission speed: 115,200/57,600/38,400/19,200/9,600/4,800 bps
Connector shape: D-sub 9-pin (Male)
RS-232
*5
Application: For communicating with a controller or connecting a personal computer (Project data upload/download, OS installation and FA transparent function)
USB (Full Speed 12 Mbps), 1ch
Built-in interface USB download, OS installation and FA transparent function)
Compact flash slot, 1ch
Connector shape: TYPE 1 CF card
Application: Data transfer, data storage
Option function board For option function board mounting, 1ch
Extension unit
*5
Buzzer output
Protective structure
For communication unit/option unit mounting, 1ch
Single tone (tone length adjustable)
Outside the enclosure: IP67
*4
Inside the enclosure: IP2X
External dimensions
(Excluding USB environmental protective cover)
Panel cutting dimensions
Weight
Compatible software package
(GT Designer2 Version)
Connector shape: Mini-B
Application: For communicating a personal computer (Project data upload/
153(6.0)(W) 121(4.8)(H)[mm](inch)
1.1 kg (mounting fixtures are not included)
2.30G or later
*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel due to its characteristics.
It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Flickers may be observed depending on the display color. Please note that these dots and flickers appear due to its characteristic and are not caused by product defect.
*2 The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*3 ROM in which new data can be written without deleting the written data.
*4 Compliant with IP67 when the USB environmental protection cover is attached. Compliant with IP2X at the USB interface only when a USB cable is connected. Note that this does not guarantee all users' operation environment.
*5 When using multiple extension units and a bar code reader, the total current of the extension units and bar code reader must not be greater than the total current that the GOT can supply.
For current values of extension units and bar code reader and the total current that the GOT can supply, refer to the following manual.
GT Designer2 Version Screen Design Manual (2-8 Multi-channel Function)
3
- 12
3.2 Performance Specifications
3.2.5 GT1555-Q, GT1550-Q
3.3 Power Supply Specifications
The following describes the power supply specifications for the GT51.
• 3.3.1 For GOTs powered from the 100 to 240VAC power supply
• 3.3.2 For GOTs powered from the 24VDC power supply
Remark Operation at momentary failure
• If an instantaneous power failure occurs in the power supply and continues for more than the permissible period, the GOT will be reset.
• Make sure to power on the unit more than 5 seconds after power-off.
3.3.1
For GOTs powered from the 100 to 240VAC power supply
1
2
3
Specifications
Item
GT1595-XTBA
GT1585V-STBA,
GT1585-STBA
GT1575V-STBA, GT1575-
STBA, GT1575-VTBA,
GT1575-VNBA, GT1572-
VNBA, GT1565-VTBA,
GT1562-VNBA
Input power supply voltage
Input frequency
Input max. apparent power
Power consumption
At backlight off
Inrush current
0.5 to 0.8 [N•m]
39W or less
40A or less (4ms)
(maximum load)
Permissible instantaneous power failure time
20ms (100VAC or longer)
Noise immunity
Dielectric withstand voltage
Insulation resistance
Applicable wire size
Applicable solderless terminal
1,500Vp-p noise voltage, 1µs noise width (when measuring with a noise simulator under 25 to 60Hz noise frequency)
1500VAC for 1 minute across power terminals and earth
10M or more across power terminals and earth by a 500V DC insulation resistance tester
0.75 to 2 [mm
2
]
Solderless terminal for M3 screw RAV1.25-3, V2-S3.3, V2-N3A,
FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
100 to 240VAC (+10% -15%)
50/60Hz 5%
110VA (maximum load)
56W or less 41W or less
30W or less
50A or less (4ms)
(maximum load)
28W or less
45A or less (4ms)
(maximum load)
4
5
6
7
8
3.3 Power Supply Specifications
3.3.1 For GOTs powered from the 100 to 240VAC power supply
3
- 13
3.3.2
For GOTs powered from the 24VDC power supply
Item
Input power supply voltage
Power consumption
At backlight off
Inrush current
Specifications
GT1595-XTBD GT1585-STBD
GT1575-STBD,
GT1575-VTBD,
GT1575-VNBD,
GT1572-VNBD,
GT1565-VTBD,
GT1562-VNBD
24VDC (+25%, -20%)
57W or less
(2380mA/
24VDC)
32W or less
(1330mA/
24VDC)
43W or less
(1790mA/
24VDC)
30W or less
41W or less
(1710mA/
24VDC)
(1250mA/24VDC)
100A or less
(4ms)
(maximum load)
115A or less
(1ms)(maximum load)
GT1555-QTBD GT1555-QSBD
18W or less
(750mA/
24VDC)
17W or less
(710mA/
24VDC)
13W or less (540mA/24VDC)
GT1550-QLBD
15W or less
(620mA/
24VDC)
60A or less (1ms)(maximum load)
Permissible instantaneous power failure time
10 ms or less
Noise immunity
Dielectric withstand voltage
500Vp-p noise voltage, 1 s noise width (when measuring with a noise simulator under 25 to 60Hz noise frequency)
500VAC for 1 minute across power terminals and earth
Insulation resistance
Applicable tightening torque
(Terminal block terminal screw)
10M or larger by insulation resistance tester
Applicable wire size 0.75 to 2 [mm²]
Applicable solderless terminal Solderess terminal for M3 screw RAV1.25-3, V2-S3.3, V2-N3A, FV2-N3A
0.5 to 0.8 [N•m]
3
- 14
3.3 Power Supply Specifications
3.3.2 For GOTs powered from the 24VDC power supply
4. PART NAME AND SETTINGS
4.1 Part Names and Settings of the GT1595
16)
2), 3)
1)
4)
14)
5)
GOT rear face
7) 13)
6)
17)
8)
15)
9)
10)
11) 12)
4.1 Part Names and Settings of the GT1595 4
- 1
7
8
5
6
3
4
1
2
No.
1)
Name
POWER LED
Description
Lit in green
Lit in orange
: Power is correctly supplied
: Screen saving
Blinks in orange/green : Blown back light bulb
Not lit : Power is not supplied
2)
3)
4)
5)
Display screen
Touch key
USB interface
RS-232 interface
Displays the Utility and the user creation screen.
For operating the touch switches in the Utility and the user creation screen
For connecting a personal computer
(Connector type: MINI-B)
For communicating with a controller or connecting a personal computer
(Connector type: D sub 9-pin)
Power input terminal, LG terminal, FG terminal
For installing an extension unit
6) Power terminal
7) Extension unit interface
8) CF card interface
9) CF card access LED
For installing a CF card
Lit : CF card accessed
Not lit : CF card not accessed
10) CF card access switch
Used for stopping the access to the CF card before removing the CF card from the GOT
ON : CF card being accessed (CF card removal prohibited)
OFF : CF card not accessed (CF card removal possible)
11)
12)
Optional function board interface
Multi-color display board interface *1
For installing the optional function board
For installing the multi-color display board
13) Reset switch
Hardware reset switch
(Inoperative in the bus connection or with the bus connection unit installed)
14) Hole for unit installation fitting Hole for inserting the unit installation fitting
15) Battery holder Houses the battery.
16) Human sensor
17) Installation switch
Sensor that detects human movement
Used for OS installations at the GOT startup
*1 For the multi-color display board, refer to the following.
Remark Connector used for the RS-232 interface
The specification of the cconnector used for the RS-232 interface of GT1595 is as follows.
Manufacturer :DDK Ltd.
Mode name :17LE-23090-27 (D4CK) or equivalent product
4
- 2
4.1 Part Names and Settings of the GT1595
4.2 Part Names and Settings of the GT1585
17)
2), 3)
1)
5)
15)
6)
GOT rear face
8) 14)
7)
9)
16)
10)
11)
4)
12) 13)
4.2 Part Names and Settings of the GT1585 4
- 3
7
8
5
6
3
4
1
2
4
- 4
No.
1)
2)
3)
4)
5)
6)
7)
Name
POWER LED
Display screen
Touch key
Video/RGB interface
USB interface
RS-232 interface
Power terminal
8) Extension unit interface
9) CF card interface
10) CF card access LED
*1
11) CF card access switch
Description
Lit in green
Lit in orange
: Power is correctly supplied
: Screen saving
Blinks in orange/green : Blown back light bulb
Not lit : Power is not supplied
Displays the utility and the user creation screen.
For operating the touch switches in the utility and the user creation screen
For installing the video input unit, RGB input unit, video/RGB input unit, or RGB output unit
For connecting a personal computer
(Connector type: MINI-B)
For communicating with a controller or connecting a personal computer
(Connector type :D sub 9-pin)
Power input terminal, LG terminal, FG terminal
For installing an extension unit
For installing a CF card
Lit : CF card accessed
Not lit : CF card not accessed
Used for stopping the access to the CF card before removing the CF card from the GOT
ON : CF card being accessed (CF card removal prohibited)
OFF : CF card not accessed (CF card removal possible)
12)
13)
Optional function board interface
Multi-color display board interface *2
For installing the optional function board
For installing the multi-color display board
14) Reset switch
Hardware reset switch
(Inoperative in the bus connection or with the bus connection unit installed)
15) Hole for unit installation fitting Hole for inserting the unit installation fitting
16) Battery holder
17) Human sensor
Houses the battery.
Sensor that detects human movement
*1 It is provided for the GT1585V-S only.
*2 For the multi-color display board, refer to the following.
Remark Connector used for the RS-232 interface
The specification of the connector used for the RS-232 interface of GT1585 is as follows.
GOT model name
GT1585V-STBA
GT1585V-STBD
GT1585-STBA
GT1585-STBD
Hardware version
A (March, 2006) or later
A (March, 2006) or later
B (April, 2005) or before
C (April, 2005) or later
A (July, 2005) or later
Connector
Manufacturer: DDK Ltd.
Model name: 17LE-23090-27 (D4CK) or equivalent product
Manufacturer: Honda Tsushin Kogyo Co., Ltd.
Model name: GM-C9RMDU11 or equivalent product
Manufacturer: DDK Ltd.
Model name: 17LE-23090-27 (D4CK) or equivalent product
4.2 Part Names and Settings of the GT1585
4.3 Part Names and Settings of the GT157
2), 3)
1)
5)
15)
6)
GOT rear face
8) 14)
7)
9)
16)
10)
11)
4)
12) 13)
4.3 Part Names and Settings of the GT157 4
- 5
7
8
5
6
3
4
1
2
No.
1)
Name
POWER LED
Description
Lit in green
Lit in orange
: Power is correctly supplied
: Screen saving
Blinks in orange/green : Blown back light bulb
Not lit : Power is not supplied
Displays the utility and the user creation screen.
2) Display screen
3)
4)
5)
6)
7)
8)
9)
Touch key
Video/RGB interface
USB interface
RS-232 interface
Power terminal
Extension unit interface
CF card interface
10) CF card access LED
*1
11) CF card access switch
For operating the touch switches in the utility and the user creation screen
For installing the video input unit, RGB input unit, video/RGB input unit, or RGB output unit
For connecting a personal computer
(Connector type: MINI-B)
For communicating with a controller or connecting a personal computer
(Connector type: D sub 9-pin)
Power input terminal, LG terminal, FG terminal
For installing an extension unit
For installing a CF card
Lit : CF card accessed
Not lit : CF card not accessed
Used for stopping the access to the CF card before removing the CF card from the GOT
ON : CF card being accessed (CF card removal prohibited)
OFF : CF card not accessed (CF card removal possible)
12)
Optional function board interface
For installing the optional function board
13)
Multi-color display board interface
*2
14) Reset switch
For installing the multi-color display board
(For GT1575-VN and GT1572-VN, 65536 color display is not supported even with the multi-color display board installed.)
Hardware reset switch
(Inoperative in the bus connection or with the bus connection unit installed)
15) Hole for unit installation fitting Hole for inserting the unit installation fitting
16) Battery holder Houses the battery.
*1 It is provided for the GT1575V-S only.
*2 For the multi-color display board, refer to the following.
3.2.3 GT1575V-S, GT1575-S, GT1575-V, GT1575-VN, GT1572-VN
4
- 6
4.3 Part Names and Settings of the GT157
Remark Connector used for the RS-232 interface
The specification of the connector used for the RS-232 interface of GT157 is as follows.
GOT model name
GT1575-STBA
GT1575-STBD
GT1575-STBA
GT1575-STBD
GT1575-VTBA
Hardware version
A (March, 2006) or later
A (March, 2006) or later
B (April, 2005) or before
C (April, 2005) or later
A (July, 2005) or later
D (April, 2005) or before
Connector
Manufacturer: DDK Ltd.
Model name: 17LE-23090-27 (D4CK) or equivalent product
Manufacturer: Honda Tsushin Kogyo Co., Ltd.
Model name: GM-C9RMDU11 or equivalent product
Manufacturer: DDK Ltd.
Model name: 17LE-23090-27 (D4CK) or equivalent product
Manufacturer: Honda Tsushin Kogyo Co., Ltd.
Model name: GM-C9RMDU11 or equivalent product
GT1575-VTBD
GT1575-VNBA
GT1575-VNBD
GT1572-VNBA
GT1572-VNBD
E (April, 2005) or later
A (July, 2005) or later
A (July, 2005) or later
A (July, 2005) or later
A (September, 2005) or later
A (September, 2005) or later
Manufacturer: DDK Ltd.
Model name: 17LE-23090-27 (D4CK) or equivalent product
1
2
3
4
5
6
7
8
4.3 Part Names and Settings of the GT157 4
- 7
4.4 Part Names and Settings of the GT156
2), 3)
1)
4)
14)
5)
GOT rear face
7) 13)
6)
8)
9)
10)
15)
11) 12)
4
- 8
4.4 Part Names and Settings of the GT156
No.
1)
2)
3)
4)
5)
6) Power terminal
7) Extension unit interface
8) CF card interface
9)
Display screen
Touch key
Name
POWER LED
USB interface
RS-232 interface
CF card access LED
10) CF card access switch
Description
Lit in green
Lit in orange
: Power is correctly supplied
: Screen saving
Blinks in orange/green : Blown back light bulb
Not lit : Power is not supplied
Displays the utility and the user creation screen.
For operating the touch switches in the utility and the user creation screen
For connecting a personal computer
(Connector type: MINI-B)
For communicating with a controller or connecting a personal computer
(Connector type: D sub 9-pin)
Power input terminal, LG terminal, FG terminal
For installing an extension unit
For installing a CF card
Lit : CF card accessed
Not lit : CF card not accessed
Used for stopping the access to the CF card before removing the CF card from the GOT
ON : CF card being accessed (CF card removal prohibited)
OFF : CF card not accessed (CF card removal possible)
11)
12)
Optional function board interface
Multi-color display board interface
*1
For installing the optional function board
For installing the multi-color display board (For GT1562-VN, 65536 color display is not supported even with the multi-color display board installed.)
13) Reset switch
Hardware reset switch
(Inoperative in the bus connection or with the bus connection unit installed)
14) Hole for unit installation fitting Hole for inserting the unit installation fitting
15) Battery holder Houses the battery.
*1 For the multi-color display board, refer to the following.
Remark Connector used for the RS-232 interface
The specification of the connector used for the RS-232 interface of GT156 is as follows.
Manufacturer: DDK Ltd.
Model name : 17LE-23090-27(D4CK) or corresponding product
1
2
3
4
5
6
7
8
4.4 Part Names and Settings of the GT156 4
- 9
4.5 Part Names and Settings of the GT155
8)
2),3)
1)
4)
13)
15)
11)
7)
GOT rear face
5) 14) 6)
9)
10)
12)
4
- 10
4.5 Part Names and Settings of the GT155
No.
1)
Name
POWER LED
Description
Lit in green: Power is correctly supplied
Lit in red: Screen saving
Blinks in red: Blown back light bulb
Not lit: Power is not supplied
2)
3)
4)
5)
Display screen
Touch key
USB interface
RS-232 interface
Displays the Utility and the user creation screen
For operating touch switches in the Utility and the user creation screen
For connecting a personal computer
(Connector type: MINI-B)
For communicating with a controller or connecting a personal computer
(Connector type: D sub 9-pin)
Power input terminal, FG terminal
For installing an extension unit
6) Power terminal
7) Extension unit interface
8) CF card interface
9) CF card access LED
10) CF card access switch
For installing a CF card
Lit: CF card accessed
Not lit: CF card not accessed
Used for stopping the access to the CF card before removing the CF card from the GOT
ON: CF card being accessed
(CF card removal prohibited)
OFF: CF card not accessed
(CF card removal possible)
11)
Optional function board interface
For installing the optional function board
12) Reset switch
Hardware reset switch
(Inoperative in the bus connection or with the bus connection unit installed)
13) Hole for unit installation fitting Hole for inserting the unit installation fitting
14) Battery holder
15) Protective ground terminal
Houses the battery
For earthing
Remark Connector used for the RS-232 interface
The specification of the connector used for the RS-232 interface of GT155 is as follows.
Manufacturer: DDK Ltd.
Model name : 17LE-23090-27(D4CK) or corresponding product
1
2
3
4
5
6
7
8
4.5 Part Names and Settings of the GT155 4
- 11
5. EMC AND LOW VOLTAGE
DIRECTIVE
For the products sold in European countries, the conformance to the EMC Directive, which is one of the
European Directives, has been a legal obligation since 1996. Also, conformance to the Low Voltage
Directive, another European Directives, has been a legal obligation since 1997.
Manufacturers who recognize their products must conform to the EMC and Low Voltage Directive are required to declare that their products conform to these Directives and put a "CE mark" on their products.
5.1 Requirements to Meet EMC Directive
EMC Directives are those which require "any strong electromagnetic force is not output to the external.:
Emission (electromagnetic interference)" and "It is not influenced by the electromagnetic wave from the external.: Immunity (electromagnetic sensitivity)".
Items 5.1.1 thru 5.1.3 summarize the precautions to use GOT and configure the mechanical unit in order to match the EMC directives.
Though the data described herein are produced with our best on the basis of the requirement items and standards of the restrictions gathered by Mitsubishi, they do not completely guaranteed that all mechanical unit manufactured according to the data do not always match the above directives. The manufacturer itself which manufactures the mechanical unit must finally judge the method and others to match the EMC directives.
5
- 1
5.1 Requirements to Meet EMC Directive
5.1.1
EMC directive
The standards of the EMC Directive are shown below.
Applied standard
EN61000-6-4 :2001
Test standard
EN55011
Radiated noise
*1
EN55011
Conducted noise
*1
EN61000-4-2
Electrostatic immunity
*1
Test details
Electromagnetic emissions from the product are measured.
Electromagnetic emissions from the product to the power line is measured.
Standard value
30M-230MHz QP:
30dB V/m (30m in measurement range)
*2, *3
230M-1000MHz QP:
37dB V/m(30m in measurement range)
*2, *3
150k-500kHz QP:79dB,
Mean:66dB
*2
500k-30MHz QP:73dB,
Mean:60dB
*2
Immunity test in which static electricity is applied to the cabinet of the equipment.
±4kV Contact discharge
±8kV Aerial discharge
EN61000-4-3
Radiated field AM modulation
*1
Immunity test in which field is irradiated to the product.
EN61131-2 :2003
EN61000-4-4
Fast transient burst noise
*1
EN61000-4-5
Surge immunity
*1
Immunity test in which burst noise is applied to the power line and signal lines.
Immunity test in which lightening surge is applied to the product.
80-1000MHz:10V/m
1.4-2GHz:10V/m
80%AM modulation@1kHz
Power line:2kV
Digital I/O(24V or higher):1kV
(Digital I/O(24V or less))
> 250V
(Analog I/O, signal lines)
> 250V
AC power type
Power line (between line and ground):
±2kV
Power line (between lines)
: ±1kV
Data communication port
: ±1kV
DC power type
Power line (between line and ground):
±0.5kV
Power line (between lines)
: ±1kV
EN61000-4-6
Conducted RF immunity
*1
Immunity test in which a noise inducted on the power and signal lines is applied.
Power line: 3V
Data communication port: 3V
Instantaneous power failure and voltage dips immunity
Radiated RF immunity
Test for checking normal operations at instantaneous power failure
Test for checking normal operations when the power supply unit input voltage is fluctuated.
AC power type
0.5 cycle (interval 1s or more)
DC power type
10 ms (interval 1s or more)
AC power type
47Hz: 85V, 264V
63Hz: 85V, 264V
DC power type
20.4V, 28.8V
5.1 Requirements to Meet EMC Directive
5.1.1 EMC directive
5
- 2
1
2
3
4
5
6
7
8
Applied standard
EN61131-2 :2003
Test standard
Third harmonic immunity
External power supply fluctuation immunity
Test details
Test for checking normal operations when the AC power waveform mixed with third harmonic wave is input.
Test for checking if the unit becomes faulty with a transient voltage of the internal and external input sides of the power supply unit or unit power supply.
Standard value
47Hz: 85V (phase 180 ° , distortion rate
10%)
63Hz: 132V (phase 0 ° , distortion rate
10.9%)
AC power type
47Hz: 85V
63Hz: 264V
DC power type
19.2V, 30V
*1: The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.
The above test items are conducted in the condition where the GOT is installed on the conductive control panel and combined with the Mitsubishi PLC.
*2: QP: Quasi-peak value, Mean : Average value
*3: The above test items are conducted in the following conditions.
30M-230MHz QP: 40dB V/m (10m in measurement range)
230M-1000MHz QP: 47dB V/m (10m in measurement range)
5
- 3
5.1 Requirements to Meet EMC Directive
5.1.1 EMC directive
5.1.2
Control panel
The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.
It not only assure the safety but also has a large effect to shut down the noise generated from GOT, on the control panel.
(1) Control panel
(a) The control panel must be conductive.
(b) When fixing a top or bottom plate of the control panel with bolts, do not coat the plate and bolt surfaces so that they will come into contact.
And connect the door and box using a thick grounding cable in order to ensure the low impedance under high frequency.
(c) When using an inner plate to ensure electric conductivity with the control panel, do not coat the fixing bolt area of the inner plate and control panel to ensure conductivity in the largest area as possible.
(d) Ground the control panel using a thick grounding cable in order to ensure the low impedance under high frequency.
(e) The diameter of cable holes in the control panel must be 10cm (3.94in.). In order to reduce the chance of radio waves leaking out, ensure that the space between the control panel and its door is small as possible.
Attach some EMI gaskets to fill up the space and suppress the leakage of radio waves.
Out test have been carried out on a panel having the damping characteristics of 37dB max. and 30dB mean (measured by 3m method with 30 to 300MHz).
(2) Connection of power and ground wires
Ground and power supply wires for the GOT must be connected as described below.
(a) Provide a grounding point near the GOT. Short-circuit the LG and FG terminals of the GOT
(LG: line ground, FG: frame ground) and ground them with the thickest and shortest wire possible (The wire length must be 30cm (11.18in.) or shorter.) The LG and FG terminals function is to pass the noise generated in the PC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.
Note) A long conductor will become a more efficient antenna at high frequency.
(b) The earth wire led from the earthing point must be twisted with the power supply wires. By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.
1
2
3
4
5
6
7
8
5.1 Requirements to Meet EMC Directive
5.1.2 Control panel
5
- 4
5.1.3
Noise filter (power supply line filter)
The noise filter (power supply line filter) is a device effective to reduce conducted noise. Except some models, installation of a noise filter onto the power supply lines is not necessary. However conducted noise can be reduced if it is installed. (The noise filter is generally effective for reducing conducted noise in the band of 10MHz or less.) Usage of the following filters is recommended.
Model name
Manufacturer
Rated current
Rated voltage
FN343-3/01
SCHAFFNER
3A
FN660-6/06
SCHAFFNER
6A
250V
ZHC2203-11
TDK
3A
The precautions required when installing a noise filter are described below.
(1) Do not install the input and output cables of the noise filter together to prevent the output side noise will be inducted into the input side cable where noise has been eliminated by the noise filer.
Input side
(power supply side)
Input side
(power supply side)
Induction
Filter Filter
Output side
(device side)
Output side
(device side)
(a) Installing the input and output cables together will cause noise induction.
(b) Separate the input cable from the output cable.
(2) Connect the noise filter’s ground terminal to the control panel with the shortest cable as possible
(approx. 10cm (3.94 in.) or less).
5
- 5
5.1 Requirements to Meet EMC Directive
5.1.3 Noise filter (power supply line filter)
5.2 Requirements for Conpliance with the Low
Voltage Directive
The Low Voltage Directive requires each device which operates with power supply ranging from 50VAC to
1000V and 75VDC to 1500V to satisfy necessary safety items.
In the Sections from 5.2.1 to 5.2.5, cautions on installation and wiring of the GOT to conform to the Low
Voltage Directive requires are described.
We have put the maximum effort to develop this material based on the requirements and standards of the
Directive that we have collected.
However, compatibility of the devices which are fabricated according to the contents of this manual to the above Directive is not guaranteed. Each manufacturer who fabricates such device should make the final judgement about the application method of the Low Voltage Directive and the product compatibility.
5.2.1
Standard subject to GOT
Standard applied to GOT:EN61131-2 Programmable controllers - Equipment requirements and tests
EN60950-1 Safety of Information Technology Equipment
5.2.2
Power supply
The insulation specification of the GOT was designed assuming installation category II. Be sure to use the installation category II power supply to the GOT.
The installation category indicates the durability level against surge voltage generated by lightning strike.
Category I has the lowest durability; category IV has the highest durability.
1
2
3
4
5
Category IV Category III Category II
Installation Category
Category I
Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution.
6
7
8
5.2 Requirements for Conpliance with the Low Voltage Directive
5.2.1 Standard subject to GOT
5
- 6
5.2.3
Control panel
Because the GOT is open type equipment (device designed to be stored within another device), be sure to use it only when installed in a control panel.
(1) Shock protection
In order to prevent those who are unfamiliar with power facility, e.g., an operator, from getting a shock, make sure to take the following measures on the control panel.
(a) Store the GOT within the control panel locked, and allow only those who are familiar with power facility to unlock the panel.
(b) Build the structure in order that the power supply will be shut off when the control panel is opened.
(2) Dustproof and waterproof features
The control panel also provides protection from dust, water and other substances. Insufficient ingression protection may lower the insulation withstand voltage, resulting in insulation destruction.
The insulation in the GOT is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or better.
Pollution level1 :An environment where the air is dry and conductive dust does not exist.
Pollution level2 :An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust.
Generally, this is the level for inside the control panel equivalent a control room or on the floor of a typical factory.
Pollution level3 :An environment where conductive dust exits and conductivity may be generated due to the accumulated dust.
An environment for a typical factory floor.
Pollution level4 :Continuous conductivity may occur due to rain, snow, etc. An outdoor environment.
5.2.4
Grounding
The following ground terminal is applicable. Use it in the grounded status.
Be sure to ground the grounding for the safety reasons and EMC Directives.
Functional grounding : Improves the noise resistance.
5
- 7
5.2 Requirements for Conpliance with the Low Voltage Directive
5.2.3 Control panel
5.2.5
External wiring
(1) External devices
When a device with a hazardous voltage circuit is externally connected to the GOT, select a model which complies with the Low Voltage Directive's requirements for isolation between the primary and secondary circuits.
(2) Insulation requirements
Dielectric withstand voltages are shown in the following table.
Reinforced Insulation Withstand Voltage
(Installation Category II, source : IEC664)
Rated voltage of hazardous voltage area
150 VAC or below
300 VAC or below
Surge withstand voltage (1.2/50 s)
2500V
4000V
1
2
3
4
5
6
7
8
5.2 Requirements for Conpliance with the Low Voltage Directive
5.2.5 External wiring
5
- 8
5.3 EMC Directive-Compliant System Configuration
The information of the EMC Directive-compliant models is obtained from the information site for Mitsubishi industrial automation products MELFANSweb homepage (MELFANSweb website: http:// wwwf2.mitsubishielectric.co.jp/english/index.html).
5.3.1
GOT
Use any of the following GOTs with which CE mark logo is printed on the rating plate.
For how to confirm the hardware version of a GOT, refer to the following.
Appendix 2 Confirming of Versions and Conformed standards
When using a GOT other than shown below, the system does not conform to the EMC Directive.
GT1595
GT1585
GT157
GT156
Item Model
GT1595-XTBA
GT1585-STBA
GT1585-STBD
GT1575-STBA
GT1575-STBD
GT1575-VTBA
GT1575-VTBD
GT1575-VNBA
GT1575-VNBD
GT1572-VNBA
GT1572-VNBD
GT1565-VTBA
GT1565-VTBD
GT1562-VNBA
GT1562-VNBD
Hardware version of the GOT
(Production year and month)
Version B or later (Jan., 2006)
Version C or later (Apr., 2005)
Version B or later (Jan., 2006)
Version C or later (May, 2005)
Version B or later (Jan., 2006)
Version E or later (May, 2005)
Version B or later (Jan., 2006)
Version K or later (Jan., 2006)
Version B or later (Mar., 2006)
Version K or later (Jan., 2006)
Version B or later (Jan., 2006)
Version E or later (Apr., 2005)
Version B or later (Nov., 2005)
Version J or later (Nov., 2005)
Version B or later (Mar., 2006)
5
- 9
5.3 EMC Directive-Compliant System Configuration
5.3.1 GOT
5.3.2
Connection method
Use the following methods to connect with the GOT to ensure compliance with the EMC Directive.
: Compliant with EMC Directive : Not compliant with EMC Directive
GT15 Connection method
Bus connection
Direct connection to CPU
Computer link connection
MELSECNET/H connection (PLC to PLC network)
MELSECNET/10 connection (PLC to PLC network)
CC-Link connection (intelligent device station)
CC-Link connection (via G4)
Ethernet connection
Other connections *2
*1: For details about each connection method, refer to the GOT1000 Series
Connection Manual.
*2: When connecting the GOT to other controllers as a PLC manufactured by other company, create the cable (by the user) and configure the system to meet the EMC Directive specifications for the connected device.
(
Connected devices
If connecting to the PLC or microcomputer other than Mitsubishi products
(MELSEC-Q series, MELSEC-QnA series or MELSEC-A series) please refer to the
EMC Directive compliance manual for that specific device.
1
2
3
4
5
6
7
8
5.3 EMC Directive-Compliant System Configuration
5.3.2 Connection method
5
- 10
5.3.3
When the communication unit is used
Use the following communication unit with the GOT to ensure compliance with the EMC Directive.
The GOT does not comply with the EMC Directive when connected with other than followings.
Connection method Communication unit used
GT15-QBUS
Hardware version of the communication unit
(Production year and month)
Version D or later
(Oct., 2005)
Bus connection
Direct connection to CPU
Computer link connection
Ethernet connection
GT15-QBUS2
GT15-ABUS
GT15-ABUS2
GT15-75QBUSL
GT15-75QBUS2L
GT15-75ABUSL
GT15-75ABUS2L
GOT RS-232 interface
GT15-RS2T4-9P
GT15-RS2-9P
GT15-RS4-9S
GOT RS-232 interface
GT15-RS2T4-9P
GT15-RS2-9P
GT15-RS4-9S
GT15-J71E71-100
Version C or later
(Oct., 2005)
Version G or later
(Mar., 2005)
Version A or later
Version D or later
(Jan., 2006)
Version A or later
Version D or later
(Jan., 2006)
Version B or later
(Mar., 2005)
Microcomputer connection
Third party PLC connection
Temperature controller
GOT RS-232 interface
GT15-RS2T4-9P
GT15-RS2-9P
GT15-RS4-9S
GOT RS-232 interface
GT15-RS2T4-9P
GT15-RS2-9P
GT15-RS4-9S
GOT RS-232 interface
GT15-RS2T4-9P
GT15-RS2-9P
GT15-RS4-9S
GT15-RS4-TE
Version A or later
Version D or later
(Jan., 2006)
Version A or later
Version D or later
(Jan., 2006)
Version D or later
(Jan., 2006)
The GOT does not comply with the EMC Directive when it is used with the following unit.
Product name Model name
MELSECNET/H communication unit GT15-J71LP23-25, GT15-J71BR13
MELSECNET/10 communication unit GT15-75J71LP23-Z, GT15-75J71BR13-Z
CC-Link communication unit GT15-J61BT13, G15-75J61BT13-Z
5
- 11
5.3 EMC Directive-Compliant System Configuration
5.3.3 When the communication unit is used
5.3.4
When the option unit is used
The following shows EMC Directive compliance of option units.
: Compliant with EMC Directive : Not compliant with EMC Directive
Product name Model name EMC Directive
Printer unit* GT15-PRN
Version B or later (Feb.,2006)
Video input unit
RGB input unit
GT15V-75V4R1
GT15V-75V4
Video/RGB input unit GT15V-75R1
RGB output unit GT15V-75ROUT
*: For the printer to be connected, configure the system in accordance with the EMC Directive specifications for the printer as requested by the printer manufacturer.
5.3.5
Cables
(1) Applicable cables
Refer to the GOT1000 Series Connection Manual for the applicable cables for connecting a GOT and PLC.
(2) Adjusting a cable for the EMC Directive compliance
Modify the cables (including user-produced cable) to ensure compliance with the EMC Directive.
For details, refer to Section 5.4.2.
1
2
3
4
5
6
7
8
5.3 EMC Directive-Compliant System Configuration
5.3.4 When the option unit is used
5
- 12
5.4 Precautions for Wiring/Connecting the EMC
Directive-Compliant Product
Wire and connect GOT1000 series equipments as instructed below. If the GOT1000 series equipments are configured in a way different from the following instructions, the system may not comply with EMC directives.
5.4.1
Power and ground wires wiring method
(1) Power and ground wires wiring method
Connect the power wire and connection cable as shown in the illustration, and be sure to attach a ferrite core (TDK Corporation type ZCAT3035-1330) within the range shown below.
Lead the power wire and ground wire as shown in Section 5.1.2 (2).
Always ground the LG and FG wires.
(a) 100-240VAC GOT power section
GOT power supply section
INPUT
100-240VAC
(LG) (FG)
Ferrite core
(ZCAT3035-1330)
(b) 24VDC GOT power section
INPUT
24VDC
(LG) (FG)
Ferrite core
(ZCAT3035-1330)
5
- 13
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.1 Power and ground wires wiring method
5.4.2
Processing connection cables
Process the cable used with the GOT with the following method.
When processing the cable, ferrite core, cable clamp and shielding material are required.
The cable clamp used by Mitsubishi Electric for the EMC specification compatibility test is shown below.
• TDK corporation brand ZCAT3035-1330 Ferrite Core
• Mitsubishi Electric Model AD75CK cable clamp
• Japan Zipper Tubing Co., Ltd. Zipper tube SHNJ type
(1) BUS connection cable
(a) For GT15-QC B, GT15-QC BS
• Peel the sheath (with the length shown below) at both ends of the cable, and expose the shield braided wire for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
GOT side PLC/GOT side
1
2
3
360 or less
(14.17)
40
(1.57)
40
(1.57)
360 or less
(14.17) Unit : mm (inch)
(b) For GT15-C BS
• Cut the connection wire protruding from both ends of the cable to the lengths shown below.
• Attach the ferrite core to the cable in the position as illustrated below and insert the ground wire into the ferrite core.
• Peel the sheath (with the length shown below) at both ends of the cable, and expose the shield braided wire for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
GOT side
Ferrite Core
(ZCAT3035-1330)
PLC/GOT side
4
5
6
60 or less
(2.36)
360 or less
(14.17)
40
Ground wires
(280mm (11.0 inch))
40
(1.57) (1.57)
60 or less
(2.36)
360 or less
(14.17) Unit : mm (inch)
7
8
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2 Processing connection cables
5
- 14
(c) For other bus connection cables
• Wind cable shield material around the cable, and pull out the grounding braided wire of the cable shield material with the length shown below.
• Attach the ferrite core to the cable in the position as illustrated below and insert the braided wire for grounding into the ferrite core.
GOT side
Ferrite Core
(ZCAT3035-1330)
PLC side
80
(3.15)
40 or less
(1.57)
Cable shield material
Grounding braided wire
(200mm (7.87 inch))
Grounding braided wire
(50mm (1.97 inch))
(3.15)
40 or less
(1.57)
80
Unit : mm (inch)
(2) CPU direct connection and computer link connection
• Peel the sheath (with the length shown below) of the cable to expose the shield braided wire for grounding. (For grounding with cable clamps (refer to Section 5.4.3))
(a) For RS-232 cable
GOT side PLC side
230 or less
(9.06)
40
(1.57)
(b) RS-422 cable (For AC30/100/300R4-25P)
GOT side PLC side
Unit : mm (inch)
230 or less
(9.06)
40
(1.57)
Unit : mm (inch)
5
- 15
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2 Processing connection cables
(3) Ethernet connection
• Strip the outer insulation layer at both ends of the cable by the length shown below to expose the braided shield for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
• Attach the ferrite core to the cable in the position as illustrated below.
GOT side
Ferrite Core
(ZCAT3035-1330)
PLC side
1
2
120 or less
(4.72)
230 or less
(9.06)
40
(1.57)
40
(1.57)
400 or less
(15.75)
Unit : mm (inch)
(4) PLC (manufactured by other company), microcomputer, temperature controller, inverter, servo amplifier or CNC connection
Produce the cable (RS-232 cable, RS-422 / 485 cable) for connecting the GOT to a controller with reference to the GOT1000 Series Connection Manual.
Configure the system to meet the EMC Directive specifications for the connected device when connecting the GOT to a controller.
The following gives the instructions to ensure the machinery comply with the EMC
Directive. However, the manufacturer of the machinery must finally determine how to make it comply with the EMC Directives: if it is actually compliant with the EMC
Directives.
3
4
5
6
7
8
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2 Processing connection cables
5
- 16
(a) For RS-422 / 485 cable
• Each signal wire (excluding SG and FG) should be made into a two power wires and connected, then twisted.
SDA
SDB
RDA
RDB
RDA
RDB
SDA
SDB
• Make the SG wire more than two wires and connect.
• Peel the sheath (with the length shown below) of the created cable to expose the shield braided wire for grounding. (For grounding with cable clamps (refer to Section 5.4.3))
GOT side PLC side
230 or less
(9.06)
40
(1.57)
(b) For RS-232 cable
• Use a twisted pair style for each signal wire (except SG, FG) with SG.
Unit : mm (inch)
RD
SD
DTR
DSR
SD
RD
DSR
DTR
SG SG
• Peel the sheath (with the length shown below) of the created cable to expose the shield braided wire for grounding. (For grounding with cable clamps (refer to Section 5.4.3))
GOT side PLC side
230 or less
(9.06)
40
(1.57)
5
- 17
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2 Processing connection cables
Unit : mm (inch)
5.4.3
Grounding the cable
Ground the cable and grounding wire to the control panel where the GOT and base unit are installed.
1) Ground the braided shield portion
of the cable to the control panel
with the cable clamp (AD75CK).
Braided shield
1
2
3
Cable clamps
For the cable clamp attaching details, refer to AD75CK-type Cable
Clamping Instruction Manual <IB-
68682>.
a) For GT15-C EXSS-1 and
GT15-C BS
Ground the ground wire to the
FG terminal of the GOT power
supply section.
4
5
6
GOT FG terminal FG wire
Bus connection cable b) For other bus connection
cables
Ground the braided wire for
grounding to the control panel
by tightening a screw.
7
8
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.3 Grounding the cable
5
- 18
6. INSTALLATION
CAUTION
• Use the GOT in the environment that satisfies the general specifications described in this manual.
Do not expose the GOT to dust, lamp soot, conductive dust, corrosive gas, or combustible gas; hightemperature, condensing, wind or rain; or to vibrations and impact.
Failure to do so can cause an electric shock, fire, malfunction or product damage or deterioration.
• Do not drop chips or wire scraps near the ventilation window of the GOT when processing screw holes or wiring.
Failure to do so can cause a fire, failure or malfunction.
• Tighten the mounting screws within the specified torque range.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short-circuit or malfunction due to the damage of the screws or the unit.
• Make sure to install the connection cable to the connector specified during the power OFF.
Failure to do so may cause a malfunction due to the poor contact.
6.1 Control Panel Inside Dimensions for Mounting GOT
Mount the GOT onto the control panel while considering the control panel inside dimensions.
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to the GOT.
Therefore, consider the connector dimensions and bending radius of the cable as well for installation.
6.2 Panel Cutting Dimensions
Make holes in the panel according to the dimensions list below.
Also, ensure 10mm spaces in upper and lower parts of the panel for mounting fixtures.
A
* Panel thickness: 2 to 4 mm or less
GOT
GT1595
GT1585
GT157
GT156
GT155
A [mm] (inch)
383.5(15.1)
(+2(0.08), 0(0))
302(11.89)
(+2(0.08), 0(0))
289(11.38)
(+2(0.08), 0(0))
227(8.94)
(+2(0.08), 0(0))
153(6.02)
(+2(0.08),0(0))
B [mm] (inch)
282.5(11.12)
(+2(0.08), 0(0))
228(8.98)
(+2(0.08), 0(0))
200(7.87)
(+2(0.08), 0(0))
176(6.93)
(+2(0.08), 0(0))
121(5)
(+2(0.08),0(0))
6
- 1
6.1 Control Panel Inside Dimensions for Mounting GOT
6.3 Mounting Position
When mounting the GOT, the following clearances must be left from the other device.
1
2
E
C D
Type
GOT or Bus connection unit
*1
is fitted
Bus connection unit
*2
or serial communication unit fitted
RS-422 Conversion unit is fitted
Ethernet communication unit is fitted
A
MELSECNET/10 communication unit (coaxial) is fitted
CC-Link communication unit
(GT15-75J61BT13-Z) fitted
CC-Link communication unit (GT15-J61BT13) fitted
MELSECNET/10 communication unit (optical) fitted
MELSECNET/H communication unit (coaxial) fitted
3
GT1595 GT1585
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
51(2.01) or more
GT157
50(1.97)
or more
[31(1.22) or more]
50(1.97) or more
[31(1.22) or more]
68(2.68) or more
Panel thickness: 2 to 4mm
(0.08 to 0.16inch)
GT155 GT156
50(1.97) or more
[36(1.47) or more]
50(1.97) or more
[36(1.47) or more]
73(2.87) or more
65(2.26) or more
65(2.26) or more
50 (1.97) or more
[20 (0.79) or more]
50 (1.97) or more
[20 (0.79) or more]
50 (1.97) or more
[20 (0.79) or more]
—
50 (1.97) or more
[40 (1.58) or more]
—
50 (1.97) or more
[20 (0.79) or more]
—
50(1.97) or more
[32(1.26) or more]
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
[26(1.02) or more]
50(1.97) or more
[24(0.95) or more]
50(1.97) or more
[43(1.69) or more]
50(1.97) or more
[38(1.5) or more]
50(1.97) or more
[48(1.89) or more]
50(1.97) or more
—
72(2.84) or more
(Continued to next page)
6.3 Mounting Position 6
- 2
4
5
6
7
8
B
C
D
E
A
Type
MELSECNET/H communication unit (optical) fitted
GT1595 GT1585 GT157 GT156
50 (1.97) or more [20 (0.79) or more]*3
GT155
Printer unit fitted
Video input unit fitted
RGB input unit fitted
Video/RGB input unit fitted
RGB output unit fitted
(When the CF card is not used)
50(1.97) or more
[20(0.79) or more]
—
50(1.97) or more
[31(1.22) or more]
50 (1.97) or more
[20 (0.79) or more]
*4
—
—
—
50(1.97) or more
[36(1.47) or more]
—
50 (1.97) or more
[20 (0.79) or more]
*5
50 (1.97) or more
[20 (0.79) or more]
*5
50 (1.97) or more
[20 (0.79) or more]
*5
80(3.15) or more
[20(0.79) or more]
—
—
—
50(1.97) or more [20(0.79) or more]
50(1.97) or more
—
—
—
—
(When the CF card is used) 50(1.97) or more [20(0.79) or more]
100(3.94) or more
50(19.7) or more
[20(0.79) or more]
100(39.4) or more
[20(0.79) or more]
Unit: mm (inch)
*1
For GT15-75QBUSL, GT15-75QBUS2L, GT15-75ABUSL, or GT15-75ABUS2L only
*2
For GT15-QBUS, GT15-QBUS2, GT15-ABUS, or GT15-ABUS2 only
*3
This value differs depending on the cable used.
Please contact your local Mitsubishi (Electric System) Service.
The value indicated in the table is a reference value.
*4
This value is for use of the coaxial cable 3C-2V (JIS C 3501).
MODEL GT15V-75V4R1 Video/RGB Input Unit MODEL GT15V-75V4 Video Input Unit MODEL
GT15V-75R1 RGB Input Unit User's Manual (Section 2.4.1 Specifications of the cables (coaxial cables) used when displaying video images)
*5 This value differs depending on the cable used.
If the bending radius of the cable used is greater than the value specified above, apply the value of the cable used.
The values enclosed in parenthesis apply to the case where no other equipment generating radiated noise
(such as a contactor) or heat is installed.
However, keep the ambient temperature of the GOT to 55°C or lower even in such a case.
The required lead-in allowance for cables may be larger than the size of A above depending on the unit or cable used.
For the lead-in allowance for cables at the bottom of the GOT, refer to the following.
Appendix 1 External Dimensions
6
- 3
6.3 Mounting Position
6.4 Control Panel Inside Temperature and Mounting
Angle
When mounting the main unit to a control panel or similar, set the display section as shown below.
When the temperature inside the control panel is 40 to 55°C or less, the mounting angle should be in the range 60 to 105 degrees.
1
2
GOT
105°
Display section 60°
Control panel, etc.
• The GOT will be deteriorated earlier if it is used at the mounting angle other than the above. Therefore, the temperature inside the control panel should be within 40°C.
*: When mounting an extension unit on the upper stage of MELSECNET/H communication unit (GT15-
J71LP23-25, GT15-J71BR13) or CC-Link communication unit (GT15-J61BT13), the operating ambient temperature must be reduced 5°C against the maximum values described in general specifications.
6.5 Installation Procedure
The GOT mounting procedure is as follows.
For the panel cutting dimensions of each GOT, refer to the following.
Section 6.2 Panel Cutting Dimensions
1 Insert the GOT into the panel opening from the front side.
3
4
5
GOT
6 panel opening
7
8
6.4 Control Panel Inside Temperature and Mounting Angle 6
- 4
2 Place the mounting fixtures (included with GOT) on the mounting fixture attaching part of the GOT, and fix them by tightening the mounting screws in the torque range of 0.36 to 0.48N·m.
(Failure to do so may distort the panel and make a surface waviness on the protective sheet.)
Magnified figure Magnified figure
For GT1595-X: Fix the GOT with 8 mounting fixtures.
For other than GT1595-X: Fix the GOT with
4 mounting fixtures.
3 A protection film is attached on the display section of GOT prior to shipment.
Remove the film when the installation is compelted.
6
- 5
6.5 Installation Procedure
7. WIRING
DANGER
Before starting wiring, always switch off the GOT power externally in all phases.
Not doing so may cause an electric shock, product damage or malfunction.
CAUTION
Please make sure to ground FG terminal and LG terminal of the GOT power supply section by applying Class D Grounding (Class 3 Grounding Method) or higher which is used exclusively for the
GOT.
Not doing so may cause an electric shock or malfunction.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
Tighten the terminal screws of the GOT power supply section in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction.
This section describes wiring to the GOT power supply section.
For the connection to a controller, refer to the following manual.
GOT1000 Series Connection Manual
For external dimensions of connection cable, refer to the following.
Appendix 1 External Dimensions
Remark General preventive measures against noise
There are two kinds of noises: Radiated noise that is transmitted into the air and
Conductive noise that is directly transmitted along connected lines.
Countermeasures must be taken considering both kinds of noises and referring to the following 3 points.
(1) Protecting against noise
(a) Keep signal lines away from noise sources such as a power cable or a highpower drive circuit.
(b) Shield the signal lines.
(2) Reducing generated noise
(a) Use a noise filter, etc. to reduce the level of the noise generated due to a source such as a high-power motor drive circuit.
(3) Releasing noise to the ground
(a) Make sure to connect the ground cable to the ground.
(b) Use a short and thick cable to lower its impedance.
(c) Ground the power system and the control system separately.
7
- 1
2
3
4
5
6
7
8
1
7.1 Power Supply Wiring
Wiring the power section of the GT155 when using an extension unit
Be sure to wire the power section before connecting a cable to the extension unit.
If connecting a cable to the extension unit before wiring the power section, the terminal block of the power section will be blocked by the cable and the power section cannot be wired.
• Make wiring connections to the power supply, I/O equipment and power equipment separately by system as shown below.
When frequent noise is identified, connect an isolation transformer.
Wiring diagram for power supply
Main power
GOT power
Isolation transformer
GOT
T1
I/O power
I/O equipment
Main circuit power
Main circuit equipment
• Twist 100V AC, 200V AC or 24V DC cable as closely as possible and connect the cable of the minimum length between modules.
Also, use the thickest cable as possible (Max. 2mm 2 ) to minimize the voltage drop.
Use M3 solderless terminals and securely tighten them with a tightening torque of 0.5 to 0.8N•m so that no problem will result.
• Separate the 100V AC, 200V AC or 24V DC cable from the main circuit lines (high voltage, large current) and/or I/O signal lines.
Keep a distance of 100mm or more.
• As measures against surge due to lightning, connect a lightning surge absorber as shown below.
Lightning surge absorber connection
AC
E1
GOT
I/O equipment
E2
Lightning surge absorber
7
- 2
1. Separate the grounding of the lightning surge absorber (E1) from the grounding of the GOT (E2).
2. Select an appropriate lightning surge absorber so that the supply voltage does not exceed the maximum allowable circuit voltage of the surge absorber even when it rises to the maximum.
7.1 Power Supply Wiring
7.2 Wiring of Connection Cables
• Keep the connection cables away from the main circuit lines (high voltage, large current) or I/O signal lines.
• When using GT15-C EXSS-1 or GT15C BS, perform the grounding in the following steps.
About GOT terminal block
The terminal block layout of a GOT differs depending on the model.
Before wiring, confirm the terminal layout of the GOT to be used.
(1) When using GT15-C EXSS-1
PLC
Not connected
GOT
(GT15-C BS)
FG
LG
N
L
(GT15-EXCNB)
OUT IN
L N LG FG
2SQ cables to
FG terminals,
28cm or less
1 Connect the LG and FG terminals of the terminal block on the GOT unit power and ground them with a cable.
2 Use the GT15-C BS's FG cable of 28cm or less.
3 Do not connect the GT15-EXCNB's FG ground cable.
4 Connect the GT15-C BS's FG cable on the GOT side to FG of the GOT unit power's terminal block.
5 Connect the GT15-C BS's FG cable on the PLC side to FG of the PLC's power supply module.
6 Connect the LG and FG terminals of the terminal block on the PLC and ground them with a cable.
(2) When using GT15-C BS
For the both side GOTs, connect the LG and FG terminals of the terminal block on the GOT unit power and ground them with a cable.
1
2
3
4
5
6
7
8
7.2 Wiring of Connection Cables 7
- 3
7.3 Grouding
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible.
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
GOT
Grounding
Other device
GOT
Grounding
Other device
GOT
Other device
(1) Independent ground
...... Best condition
(2) Shared grounding
...... Good condition
(3) Common grounding
...... Not allowed
• Use the cable of 2mm 2 or more for grounding.
Set the grounding point closer to the GOT to make the grounding cable short as possible.
1
Example of independent grounding
Power equipment
(servo, etc.)
CN1A CN1B
FG
LG
CN2 CN3
PLC
Connection cable
FG
FG
LG
GOT
Ground terminal block
Panel grounding
Ground terminal block Grounding for control system
Grounding for power system
* Ground the control system, especially modules communicating each other, to one end.
2
Example of shared grounding
Power equipment
(servo, etc.)
CN1A CN1B
FG
LG
CN2 CN3
FG
PLC
Connection cable
GOT
FG
LG
Panel grounding
Panel grounding
Use a short and thick cable as much as possible.
* Ground the system to one end.
7
- 4
7.3 Grouding
Recommended terminal shape
3.2
6.2mm or less
6.2mm or less
3.2
Terminal screw
Solderless terminal
Terminal screw
Solderless terminal
When wiring one cable to one terminal
When wiring two cables to one terminal
Applicable solderless terminal RAV1.25- 3, V2- S3.3, V2- N3A, FV2- N3A
1
2
3
4
5
6
7
8
7.3 Grouding 7
- 5
7.4 Power Supply Connection
This section provides an example for connecting power cables and ground cables to the power terminals situated on the back of the GOT.
100/110V AC
AC
Fuse
AD
DC
24V DC
GOT
In the case of 100V AC
INPUT
100-240VAC
(LG) (FG)
GOT
INPUT
24VDC
+
(LG) (FG)
In the case of 24V DC (other than GT155 )
(FG)
INPUT
24VDC
+
GOT
In the case of 24V DC (GT155 )
7
- 6
Ground cables
Grounding
Precautions for wiring to the power supply section
1. For 100V AC, 200V AC or 24V DC cable, use the thickest cable as possible (Max.
2mm 2 ) and start twisting them at the position closest to the connected terminals.
To prevent a short circuit due to loose screws, use the solderless terminal with insulation sleeve.
2. When connection is made between LG and FG terminals, be sure to connect them to the ground.
Otherwise, the system becomes susceptible to noise.
Since the LG terminal has potential equal to a half of the input voltage, touching the terminal may lead to an electric shock.
3. When grounding the GT155 , ground it with the ground terminal equipped at the lower-left corner on the GOT main unit back face.
(Refer to the above.)
Use the FG power terminal for connecting the FG wire of the bus connection cable.
7.4 Power Supply Connection
8. OPTION
8.1 CF Card
The CF card is used to transfer the OS or project data and to save data of the alarm history function or other functions.
Refer to the following for details
13. FILE DISPLAY AND COPY (PROGRAM/DATA CONTROL)
8.1.1
Applicable CF card
The following CF cards are applicable for GT15
.
Mode
GT05-MEM-16MC
GT05-MEM-32MC
GT05-MEM-64MC
GT05-MEM-128MC
GT05-MEM-256MC
Description
Flash ROM 16MB
Flash ROM 32MB
Flash ROM 64MB
Flash ROM 128MB
Flash ROM 256MB
Commercially-available CF card
*1
*1: Some models with the operations checked by our company are usable.
For the operation-checked models, refer to "List of valid devices applicable for GOT1000 series" (T10-0039) separately available.
The Technical News above is available as a reference at the Information site for Mitsubishi industrial automation products.
(MELFANSweb website: http://wwwf2.mitsubishielectric.co.jp/english/index.html)
2
3
4
5
6
The flash PC card of the GOT-A900 series
In the GT15 , the flash PC card for GOT-A900 series cannot be used.
Use the CF card which is described in the above.
7
1
8
8.1 CF Card
8.1.1 Applicable CF card
8
- 1
8.1.2
Installing and removing procedures of the CF card
Install/remove the CF card with the power supply of GOT is OFF or CF card access switch is "OFF".
1
Installing
1 Turn the CF card access switch of the GOT off.
When using other than the GT155 When using the GT155
2 Open the cover of the CF card interface.
Insert and install the CF card into the CF card interface with its front side outside.
When using other than the GT155
CF Card top face
When using the GT155
CF Card top face
CF card eject button
For the following GOTs, after installing the CF card, turn the CF card eject button to
90 degree while being pulled.
• GT1585-S, GT1575-S: Hardware version B (April, 2005) or earlier
• GT1575-V, GT1565-V: Hardware version D (April, 2005) or earlier
8
- 2
8.1 CF Card
8.1.2 Installing and removing procedures of the CF card
3 Close the cover of the CF card interface. Set the CF card access switch to "ON".
When using other than the GT155 When using the GT155
8.1 CF Card
8.1.2 Installing and removing procedures of the CF card
8
- 3
7
8
5
6
3
4
1
2
2
Removing
1 Set the CF card access switch of the GOT to "OFF", and make sure that the CF card access LED turns off. (When the CF card access LED turns off, the CF card can be removed even during the GOT power on.)
When using other than the GT155 When using the GT155
2 Open the cover of the CF card interface.
Push the CF card eject button of the GOT.
(The CF card eject button is pulled out after pushing at once.)
When using other than the GT155
When using the GT155
8
- 4
8.1 CF Card
8.1.2 Installing and removing procedures of the CF card
1
CF card eject button
For the following GOTs, after opening the cover of the CF card interface, raise the
CF card eject button.
• GT1585-S, GT1575-S: Hardware version B (April, 2005) or earlier
• GT1575-V, GT1565-V: Hardware version D (April, 2005) or earlier
2
3 Push the CF card eject button of the GOT to lift the CF card and remove it.
When using other than the GT155 When using the GT155
5
Precautions for removing the CF card
1. While the CF card access LED is on, do not install/remove the CF card or power off the GOT.
To do so may cause data corruption or malfunction.
2. When ejecting the CF card, support it by hand since it may pop out.
Failure to do so may cause a fall of the CF card leading to failure or damage of the card.
3. Do not install/remove the CF card while downloading the monitor data or other data by the RS-232 transmission.
To do so may cause a faulty communication of the GT Designer2 and the data cannot be downloaded normally.
6
7
8
8.1 CF Card
8.1.2 Installing and removing procedures of the CF card
8
- 5
3
4
8.2 Memory Card Adaptor
The memory card adaptor is used to convert the CF card into the memory card (Type II).
The memory card (Type II) is used to transmit the OS, project data and to save the data of alarm history function or other functions by installing it to the PC which is equipped with the CMCIA interface.
Refer to the following for the details related to CF card.
8.2.1
Applicable memory card adaptor
The following memory card adaptor is applicable for GT15
Mode
GT05-MEM-ADPC
.
Description
Converts the CF card into a memory card
8.2.2
Installing procedure
Fit the memory card in the memory card adaptor.
CF card Memory card adaptor
8
- 6
8.2 Memory Card Adaptor
8.2.1 Applicable memory card adaptor
8.3 Option Function Board
The optional function board is used to extend the option function and the built-in flash memory.
Refer to the following for the functions requiring the optional function board.
GT Designer2 Version Screen Design Manual
8.3.1
Applicable option function board
The following option function boards are applicable for GT15
GT15-FNB
GT15-QFNB
Model
GT15-QFNB16M
GT15-QFNB32M
GT15-QFNB48M
.
Description
Option function board
Applicable for MELSEC-A/FX ladder monitor function
Option function board
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multi-channel function
Option function board with add-on memory (Option function + 16MB)
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multi-channel function
Option function board with add-on memory (Option function + 32MB)
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multi-channel function
Option function board with add-on memory (Option function + 48MB)
Applicable for MELSEC-Q/QnA/A/FX ladder monitor function, multi-channel function
8.3.2
Installing procedure
1 Power OFF the GOT.
2 Detach the expansion unit cover (I/F-1 side) of GOT rear face.
1
2
3
4
5
6
7
8
8.3 Option Function Board
8.3.1 Applicable option function board
8
- 7
3 Install the optional function board in the option function board interface.
(When the expansion unit is installed in GOT, detach the installed extension unit. And, do not touch the board in the GOT when install the optional function board.)
4 After the installation of option function board, attach the expansion unit cover.
5 For installation of expansion unit, install the expansion unit.
8
- 8
8.3 Option Function Board
8.3.2 Installing procedure
8.4 Multi-Color Display Board
The multi-color display board is used when supporting 65536 display colors.
With some GOT hardware versions, 65536 colors are available even without the multi-color display board installed.
For GOTs requiring installation of the multi-color display board, refer to the following.
3.2 Performance Specifications
8.4.1
Applicable multi-color display board
The following multi-color display board is applicable for GT15 .
GT15-XHNB
Model Description
Multi-color display board for XGA (For 65536-color display)
Multi-color display board for SVGA/VGA (For 65536-color display)
*1
GT15-VHNB Multi-color display board for SVGA/VGA (For 65536-color display)
*1: To use it for a SVGA or VGA GOT, install the following OS to the GOT.
(Cannot be used for a SVGA or VGA GOT without installing the OS.)
BootOS Ver. 02.01.00.E or later
Standard monitor OS: Ver. 02.01.00 or later
For how to install the OS, refer to GT Designer2 Version Basic Operation/Data Transfer Manual.
1
2
3
4
When using GT1575-VN, GT1572-VN, GT1562-VN
For GT1575-VN, GT1572-VN and GT1562-VN, 65536 color display is not supported even with the multi-color display board installed.
8.4.2
Installing procedure
5
1 Power OFF the GOT.
2 Remove the expansion unit cover (I/F-2 side) of GOT rear face.
6
3 Install the multi-color display board in the multi-color display board interface.
(When the extension unit is installed in GOT, remove the installed extension unit. And, do not touch the board in the GOT when install the multi-color display board.)
7
8
8.4 Multi-Color Display Board
8.4.1 Applicable multi-color display board
8
- 9
4 After the installation, tighten a fixing screw within the specified torque range (0.25 to 0.35N·m).
8
- 10
8.4 Multi-Color Display Board
8.4.2 Installing procedure
8.5 Printer Unit
Printer unit is used for connecting a printer to GOT.
For details of the connection type, refer to the following.
GOT1000 Series Connection Manual
8.5.1
Printer unit type
The following type of printer unit can be used for GT15
GT15-PRN
Model name
.
Description
83g (including connector holder and cable clamp)
8.5.2
Installing procedure
This section describes how to install printer on GOT.
A printer unit and another extension unit can be installed on a GOT together.
Refer to the following item after implementing the steps described in this section.
One printer unit can be installed at either 1st to 3rd stage of the exteded interface.
8.7.3 Installing multiple extension units in layers
1
Cable connection
1 Connect the dedicated printer connection cable to the printer unit.
1
2
3
4
5
Dedicated printer connection cable
2 Attach the accessory connector holder to the dedicated printer connection cable and tighten the screw of connector holder with tightening torque of 0.36 to 0.48N m.
6
7
Connector holder
8
8.5 Printer Unit
8.5.1 Printer unit type
8
- 11
3 Depending on the use environment such as when fastening cable is difficult, attach a cable clamp to the printer unit.
Be sure to attach the cable clamp to section A (see the following figure) with its band positioned outside and press it until it clicks.
For the band inserting direction, refer to the arrow.
(As a cable clamp, "RST-1NB" manufactured by TAKEUCHI INDUSTRY CO.LTD. is used.)
A
Cable clamp
4 Insert the dedicated printer connection cable in the looped cable clamp band and pull the band to fasten the cable.
2
Unit installation
1 Power off the GOT.
2 Remove one extension unit cover of the GOT.
3 Fit the printer unit along the groove of the GOT case.
8
- 12
8.5 Printer Unit
8.5.2 Installing procedure
In the case a cable clamp is attached
4 Fasten the printer unit by tightening its mounting screws (2 places) with tightening torque of 0.36 to 0.48
N m.
1
2
In the case a cable clamp is attached
5 When mounting any extension unit in a later stage, refer to the following.
8.7.3 Installing multiple extension units in layers
6 When not installing an extension unit on the unit that has been installed, stick accessory labels on the top of mounting screws (2 places) to cover the top of them in order to avoid receiving electrostatic charge.
Keep the connector cover and label fixed.
3
Accessory labels
4
Connector cover
Label
5
6
7
8
8.5 Printer Unit
8.5.2 Installing procedure
8
- 13
(1) Precautions for connecting the dedicated printer connection cable (USB cable)
• Wait 5s or more between the connection and disconnection of the dedicated printer connection cable.
If connecting or disconnecting the dedicated printer connection cable shortly after disconnecting or connecting the cable, the GOT may not operate normally.
• Do not connect or disconnect the dedicated printer connection cable during printing.
Doing so can cause the GOT operate incorrectly.
• Connected printer may not be recognized in rare cases.
When printer is not recognized, disconnect the dedicated printer connection cable once and connect it again.
• When the printer has been connected to a personal computer and used before it is connected to GOT, power on the printer again and connect it to
GOT.
• Any printer cannot be connected to GOT via USB hub.
• Do not connect any device to the printer while GOT is connected to it.
• Do not connect any device other than printer to the printer unit.
(2) Cable connection/disconnection
When connecting and disconnecting the dedicated printer connection cable, leave an interval of at least 3 seconds.
(3) Printer unit removal
To remove the printer unit, detach it from specified direction ( PULL) so as not to break the connector.
(4) Cable clamp
• Pulling out the cable clamp band
The cable clamp band can be pulled out after cable treatment.
Pull out the band with pressing the tab of the cable clamp outward using a driver etc.
• Removing from the printer unit
The dedicated printer connection cable can be removed from the unit with the cable clamp attached.
Remove the cable clamp by pressing it in both directions (arrow A).
A
8
- 14
(5) Screw of the connector holder
Do not remove the screw attached to the connector holder.
In the case the screw is removed, do not use any other screw.
Doing so may damage the unit.
8.5 Printer Unit
8.5.2 Installing procedure
8.6 Video/RGB Unit
The video/RGB unit is used to connect a video camera, personal computer, or commercially available display to a GOT.
For details on the connection types, refer to the following.
GOT1000 Series Connection Manual
• Video/RGB unit
Images taken with a video camera and a personal computer display can be displayed on the GOT.
• Video input unit
Images taken with a video camera can be displayed on the GOT.
• RGB input unit
A personal computer display can be displayed on the GOT.
• RGB output unit
A GOT display can be displayed on a commercially available display.
8.6.1
Video/RGB unit types
There are the following types of video/RGB units.
Model name
GT15V-75V4
GT15V-75R1
GT15V-75V4R1
GT15V-75ROUT
Description
For NTSC/PAL input 4 channels
For analog RGB input 1 channel
For NTSC/PAL (4ch)/analog RGB (1ch) mixed input
For analog RGB output
8.6.2
Installing procedure
This section explains how to install a video/RGB unit on a GOT.
A video/RGB unit can also be installed together with another extension unit.
When installing a video/RGB unit together with some other extension unit, after executing the procedure in this section, refer to the following.
One video/RGB unit can be installed only in the first stage of the extension interface.
8.7.3 Installing multiple extension units in layers
1
2
3
4
5
6
1 Power OFF the GOT.
2 Remove the expansion unit covers (I/F-1 side and I/F-2 side) of the GOT rear face.
7
8
8.6 Video/RGB Unit
8.6.1 Video/RGB unit types
8
- 15
3 Install the extend interface relay board on the Extend I/F-2 side of the GOT.
After the installation, detach the connector cover from the extend interface relay board.
Remove the connector cover
4 Install the video/RGB unit in the expansion unit interface of the GOT rear face.
(When the extension unit is installed in GOT, remove the installed extension unit. And, do not touch the board in the GOT when install the video/RGB unit.)
5 After the installation, tighten the mounting screws (4 places) in the specified torque range (0.36 to 0.48N·m).
8
- 16
8.6 Video/RGB Unit
8.6.2 Installing procedure
6 Tighten the extend interface relay board installed by the step range (0.36 to 0.48N·m). (2 places)
within the specified torque
1
2
3
Removing the video/RGB unit
(
Before removing the unit, unscrew the extend interface relay board fixing screws.
above 6
)
7 When installing an extension unit on the unit, refer to the following.
8.7.3 Installing multiple extension units in layers
When not installing an extension unit on the outer layer, cover the top of mounting screws (4 places) with accessory labels in order to avoid receiving static electricity.
Keep the connector cover fixed.
Keep the seal stuck as it is.
4
5
6
7
8
8.6 Video/RGB Unit
8.6.2 Installing procedure
8
- 17
8.7 Communication Unit
The communication unit is used to relate the GOT expansion unit interfaces to the system at the connection destination.
Refer to the following for the details of connection statuses.
GOT1000 Series Connection Manual
8.7.1
Applicable communication unit
The following communication units are applicable for GT15 .
Product name Model Description
Bus connection unit
GT15-QBUS *1
GT15-QBUS2
GT15-ABUS
*1
GT15-ABUS2
*1
*1
GT15-75QBUSL
GT15-75QBUS2L
GT15-75ABUSL
GT15-75ABUS2L
For QCPU (Q mode)/motion controller CPU (Q series) connection (standard model)
For A/QnACPU/motion controller CPU (A series) connection (standard model)
For QCPU (Q mode)/motion controller CPU (Q series) connection (slim model)
For A/QnACPU/motion controller CPU (A series) connection (slim model)
For last GOT, 1 connector
For intermediary and last GOT, 2 connectors
For last GOT, 1 connector
For intermediary and last GOT, 2 connectors
For last GOT, 1 connector
For intermediary and last GOT, 2 connectors
For last GOT, 1 connector
For intermediary and last GOT, 2 connectors
Serial communication unit
GT15-RS2-9P
*1
GT15-RS4-9S
*1
GT15-RS4-TE
*1
For RS-232 interface connection, connector type
For RS-422 interface connection, connector type
For RS-422 interface connection, terminal block type
Ethernet communication unit
GT15-J71E71-100 Ethernet (100Base-TX/10Base-T) unit
MELSECNET/H communication unit
MELSECNET/10 communication unit
CC-Link communication unit
GT15-J71LP23-25
*2 Optical double loop unit
GT15-J71BR13
*2 Coaxial bus unit
GT15-75J71LP23-Z
Optical loop unit
(A9GT-QJ71LP23 + GT15-75IF900 set)
GT15-75J71BR13-Z
Coaxial bus unit
(A9GT-QJ71BR13 + GT15-75IF900 set)
GT15-J61BT13
*2
Intelligent device station unit
CC-LINK Ver. 2 compliant
GT15-75J61BT13-Z
Intelligent device station unit
(Set of A8GT-61BT13+GT15-75IF900)
Interface converter unit
GT15-75IF900 Conversion unit for GOT-A900/GOT800 series communication unit
*1 When using this unit, use a standard monitor OS and communication driver of GT Designer2 Version2.15R or later.
With a standard monitor OS and communication driver of an older version, the GOT has cannot recognize the unit to perform monitoring.
*2 This can be used with the GT1585-STBA and GT1575-STBA of hardware version C or later or the GT1575-VTBA and GT1565-VTBA of hardware version E or later
8
- 18
8.7 Communication Unit
8.7.1 Applicable communication unit
8.7.2
Installing procedure
This section describes how to install a communication unit on a GOT.
A communication unit can also be installed together with another extension unit.
When installing a communication unit together with some other extension unit, after executing the procedure in this section, refer to the following.
8.7.3 Installing multiple extension units in layers
1
Bus connection unit
(1) GT15-QBUS, GT15-ABUS
1 Power OFF the GOT.
2 Remove one of the extension unit covers of the GOT.
1
2
3
4
5
3 Fit the communication unit along the groove of the GOT case.
6
4 Fasten the communication unit by tightening its mounting screws (2 places) with tightening torque of 0.36 to 0.48 N·m
7
8
8.7 Communication Unit
8.7.2 Installing procedure
8
- 19
5 When installing an extension unit on the unit that has been installed, refer to the following.
8.7.3 Installing multiple extension units in layers
When not installing an extension unit on the unit that has been installed, in order to avoid receiving electrostatic, stick accessory labels to cover the top of mounting screws (2 places).
Keep the connector cover fixed.
Keep the seal stuck as it is.
Accessory labels
Connector cover
Seal
(2) GT15-QBUS2, GT15-ABUS2
1 Power OFF the GOT.
2 Remove the expansion unit covers (I/F-1 side and I/F-2 side) of the GOT rear face.
3 Install the extend interface relay board on the Extend I/F-2 side of the GOT.
After the installation, detach the connector cover from the extend interface relay board.
For GT155 , the extension interface relay board is not needed.
Remove the connector cover
8
- 20
8.7 Communication Unit
8.7.2 Installing procedure
4 Install the communication unit in the expansion unit interface of the GOT rear face.
(When the extension unit is installed in GOT, remove the installed extension unit. And, do not touch the board in the GOT when install the communication unit.)
1
2
5 After the installation, tighten the mounting screws (4 places) in the specified torque range (0.36 to 0.48N·m).
3
4
6 Tighten the extend interface relay board installed by the step range (0.36 to 0.48N·m). (2 places)
within the specified torque 5
6
Removing the GT15-QBUS2, GT15-ABUS2
(
Before removing the unit, unscrew the extend interface relay board fixing screws.
above 6
)
7
8
8.7 Communication Unit
8.7.2 Installing procedure
8
- 21
7 When installing an extension unit on the outer layer, refer to the following.
8.7.3 Installing multiple extension units in layers
When not installing an extension unit on the outer layer, cover the top of mounting screws (4 places) with accessory labels in order to avoid receiving static electricity.
Keep the connector cover fixed.
Keep the seal stuck as it is.
(3) GT15-75QBUSL, GT15-75QBUS2L, GT15-75ABUSL, GT15-75ABUS2L
1 Power OFF the GOT.
2 Remove the expansion unit covers (I/F-1 side and I/F-2 side) of the GOT rear face.
3 Install the communication unit in the expansion unit interface of the GOT rear face.
(When the extension unit is installed in GOT, remove the installed extension unit. And, do not touch the board in the GOT when install the communication unit.)
8
- 22
8.7 Communication Unit
8.7.2 Installing procedure
4 After the installation, tighten the mounting screws (4 places) in the specified torque range (0.42 to 0.57N·m).
1
2
5 Paste the provided seals after tightening the mounting screws in order to avoid receiving electrostatic.
3
.
2
Serial communication unit, Ethernet communication unit
(1) Unit installation
The following explanation uses the Ethernet communication units as an example.
The serial communication unit can be installed with the same procedure.
1 Power OFF the GOT.
2 Remove one extension unit cover of the GOT.
4
5
3 Fit the communication unit along the groove of the GOT case.
6
7
8
8.7 Communication Unit
8.7.2 Installing procedure
8
- 23
4 Fasten the communication unit by tightening its mounting screws (2 places) with tightening torque of 0.36 to 0.48 N·m.
5 When installing an extension unit on the outer layer, refer to the following.
8.7.3 Installing multiple extension units in layers
When not installing an extension unit on the outer layer, cover the top of mounting screws (4 places) with accessory labels in order to avoid receiving static electricity.
Keep the connector cover fixed.
Keep the seal stuck as it is.
Accessory labels
Connector cover
Seal
Remove the serial communication unit, Ethernet communication unit
If you remove the serial communication unit or Ethernet communication unit, detach it from specified direction (shown PULL) so as not to break a connector.
8
- 24
8.7 Communication Unit
8.7.2 Installing procedure
(2) Terminal block socket installation (For GT15-RS4-TE only)
1 Insert the terminal block socket in the serial communication unit.
1
2
A
2 Fasten the terminal block by tightening the terminal block fixing screws (2 places) with the tightening torque of 0.20 to 0.25 N·m.
(Extended figure of part A)
3
4
A terminal block fixing screw
When attaching or removing a communication cable
When attaching or removing a communication cable to/from the terminal block socket, detach the terminal block socket from the connector.
(When extension units are installed in multiple layers, the units do not have to be removed from the GOT main unit.)
5
6
7
8
8.7 Communication Unit
8.7.2 Installing procedure
8
- 25
3
MELSECNET/10 communication unit, CC-Link communication unit
1 Power off the GOT.
2 Remove the two extension unit covers of the GOT.
3 Fit the GT15-75IF900 along the groove of the GOT case.
4 Fasten the GT15-75IF900 by tightening its mounting screws (3 places) with tightening torque 0.36 to
0.48 N·m.
5 Attach the communication unit fixing brackets (3 places) to GT15-75IF900, then fasten them with tightening torque of 0.36 to 0.48 N·m.
8
- 26
8.7 Communication Unit
8.7.2 Installing procedure
6 Mount the network unit (A9GT-QJ71LP23 or A9GT-QJ71BR13) or CC-Link communication unit (A8GT-
J61BT13) to GT15-75IF900.
1
2
7 Fasten the unit fixing brackets (3 places) with tightening torque of 0.36 to 0.48N·m.
4
MELSECNET/H communication unit, CC-Link communication unit (GT15-J61B13)
(1) Unit installation
1 Power OFF the GOT.
2 Remove the expansion unit covers (I/F-1 side and I/F-2 side) of the GOT rear face.
5
6
3
4
7
8
8.7 Communication Unit
8.7.2 Installing procedure
8
- 27
3 Install the extend interface relay board on the Extend I/F-2 side of the GOT.
After the installation, detach the connector cover from the extend interface relay board.
For GT155 , the extension interface relay board is not needed.
Remove the connector cover
4 Install the communication unit in the expansion unit interface of the GOT rear face.
(When the extension unit is installed in GOT, remove the installed extension unit. And, do not touc the board in the GOT when install the communication unit.)
5 After the installation, tighten the mounting screws (4 places) in the specified torque range (0.36 to 0.48N·m).
8
- 28
8.7 Communication Unit
8.7.2 Installing procedure
6 Tighten the extend interface relay board installed by the step range (0.36 to 0.48N·m). (2 places)
within the specified torque
1
2
3
Removing the MELSECNET/H communication unit, CC-Link communication unit
(GT15-J61BT13)
(
Before removing the unit, unscrew the extend interface relay board fixing screws.
above 6
)
7 When installing an extension unit on the unit that has been installed, refer to the following.
8.7.3 Installing multiple extension units in layers
When not installing an extension unit on the unit that has been installed, in order to avoid receiving electrostatic, stick accessory labels to cover the top of mounting screws (4 places).
Keep the connector cover fixed.
Keep the seal stuck as it is.
4
5
6
(2) Terminal block socket installation (For GT15-J61BT13 only)
1 Insert the terminal block socket in CC-Link communication unit.
7
A
8
8.7 Communication Unit
8.7.2 Installing procedure
8
- 29
2 Fasten the terminal block by tightening the terminal block fixing screws (2 places) with the tightening torque of 0.20 to 0.25 N·m.
(Extended figure of part A)
A terminal block fixing screw
When attaching or removing a communication cable
When attaching or removing a communication cable to/from the terminal block socket, detach the terminal block socket from the connector.
(When extension units are installed in multiple layers, the units do not have to be removed from the GOT main unit.)
8
- 30
8.7 Communication Unit
8.7.2 Installing procedure
8.7.3
Installing multiple extension units in layers
This section describes how to install another extension units on the extension units that has been installed on the GOT.
When no extension units is installed on the GOT, apply the steps in this section after installing an extension units.
• Printer unit (
• Video/RGB unit (
• Communication unit (
1 Remove the connector cover and seal from the installed extension units.
1
2
Connector cover
Seal
3
4
2 Install the unit on the unit that has been installed.
5
6
3 After installing the unit, fasten it by tightening the mounting screws (2 places) with tightening torque of
0.36 to 0.48N·m.
7
8
8.7 Communication Unit
8.7.3 Installing multiple extension units in layers
8
- 31
4 When installing another extension unit on the unit that has been installed, implement the above operations of
to .
4 When not installing an extension unit on the unit that has been installed, in order to avoid receiving electrostatic, stick accessory labels to cover the top of mounting screws.
4 Keep the connector cover fixed.
4 Keep the seal stuck as it is.
5
Accessory labels
Connector cover
Seal
(1) Installation position for a communication unit that occupies two extend I/Fs
Install a communication unit that occupies two extend I/Fs, such as the following, directly to the GOT main unit.
It cannot be installed on the back stage of another communication unit.
If a video/RGB unit has been installed, install the communication unit on the back stage of that video/RGB unit.
• Bus connection unit (GT15-QBUS2, GT15-ABUS2, GT15-75QBUS2L,
GT15-75ABUS2L only)
(
• MELSECNET/10 communication unit
(
MELSECNET/10 communication unit, CC-Link communication unit)
• CC-Link communication unit
(
MELSECNET/10 communication unit, CC-Link communication unit)
• MELSECNET/H communication unit
(
MELSECNET/H communication unit, CC-Link communication unit (GT15-J61B13))
• CC-Link communication unit (GT15-J61BT13)
(
MELSECNET/H communication unit, CC-Link communication unit (GT15-J61B13))
(2) Installing the GT15-75QBUSL, GT15-75QBUS2L, GT15-75ABUSL, GT15-
75ABUS2L
These cannot be installed on the back stage of a video/RGB unit. For bus connection, use the GT15-QBUS, GT15-QBUS2, GT15-ABUS, or GT15-ABUS2.
8
- 32
8.7 Communication Unit
8.7.3 Installing multiple extension units in layers
(3) Removing video/RGB unit, bus connection unit (GT15-QBUS2, GT15-ABUS2),
MELSECNET/H communication unit, CC-Link communication unit (GT15-
J61BT13)
Before removing the unit, unscrew the extend interface board fixing screws.
• Video/RGB unit
(
• Bus connection unit (GT15-QBUS2, GT15-ABUS2)
(
• MELSECNET/H communication unit
(
MELSECNET/H communication unit, CC-Link communication unit (GT15-J61B13))
• CC-Link communication unit (GT15-J61BT13)
(
MELSECNET/H communication unit, CC-Link communication unit (GT15-J61B13))
1
2
3
4
5
6
7
8
8.7 Communication Unit
8.7.3 Installing multiple extension units in layers
8
- 33
8.8 RS-422 Conversion Unit
The RS-422 conversion unit is inserted to the GOT RS-232 connector to enable the RS-422 communication by RS-232/RS-422 conversion.
Refer to the following for the details of connection statuses.
GOT1000 Series Connection Manual
8.8.1
Applicable RS-422 conversion unit
The following RS-422 conversion units are applicable for GT15
Model name
GT15-RS2T4-9P
GT15-RS2T4-25P
RS-232-RS-422 conversion unit
.
Description
RS-422 side connector 9 pins
(15", 12.1", 10.4", 8.4")
RS-422 side connector 25 pins
(15", 12.1", 10.4", 8.4")
Notes on using the RS-422 conversion unit
1. Use GT15-RS2T4-25P when you switched to use from the GOT-A900 series.
Use GT15-RS2T4-9P when you newly use the GOT1000 series.
2. Set to [ON] by [5V supply] at [Communication settings] of the utility.
(
10.1.4 Communication setting display operation)
8.8.2
Installing procedure
1 Power OFF the GOT.
2 Installs the RS-422 conversion unit in the RS-232 interface of the GOT rear face.
3 Tighten the fixing screws in the specified torque range (0.36 to 0.48N·m) after the installation.
8
- 34
8.8 RS-422 Conversion Unit
8.8.1 Applicable RS-422 conversion unit
8.9 Battery
Battery is used to backup data when the power supply of GOT is OFF.
The data which can be backed-up with the battery is shown below.
• Present time (Clock data) (
12.1 Time Setting and Display)
• Maintenance time notification data (
16.1 Maintenance Timing Setting)
8.9.1
Applicable battery
The following battery is applicable for GT15
Model
GT15-BAT
.
Description
Battery for backup of clock data and maintenance timing setting data.
8.9.2
Battery specifications
Item
Type
Initial voltage
Nominal current
Storage life
Total power stoppage time
Lithium content
Application
Specifications
Magnesium manganese dioxide lithium primary battery
3.0V
1800mAh
Approx.5 years (Operating ambient temperature of 25°C)
Refer to Section 8.9.4 Battery life
0.49g
For backup of clock data and maintenance timing setting data.
1
2
3
4
5
8.9.3
Battery replacement procedure
Replace battery periodically by referring to Section 8.9.4 Battery life.
1 Keep the GOT power supply on for 10 minutes or more, and turn it off. (Executes step
5 minutes of powering the GOT power supply off.)
to 6 within
2 Remove the battery holder form the GOT backside.
For other than GT155 For GT155
6
7
3 Remove the old battery from the holder and disconnect the connector.
4 Connect the new battery to the connector.
5 Insert the battery into the holder and set it into the GOT backside.
6 Turn the GOT power supply on.
8.9 Battery
8.9.1 Applicable battery
8
- 35
8
7 Check if the battery condition is normal within the utility.
Refer to the following for the details of battery status display.
12. CLOCK SETTINGS AND BATTERY STATUS DISPLAY (TIME SETTING AND
1. Precautions after battery replacement
Make sure to turn on the GOT power supply once upon completion of battery replacement.
Failure to do so may decrease the battery life.
2. When the 2- slot type extension unit is connected to GT156 .
Before installing or replacing the battery, disconnect the unit.
(When connecting or disconnecting the unit, be sure to power off the GOT and
PLC.)
8.9.4
Battery life
Life span of the battery set in the GOT is shown below.
Operating ambient temperature of 0 to 45°C
Battery life
Operating ambient temperature of 45 to 55°C
5 years 3 years
Data backup time after detection of battery voltage low*
14 days
*: In the following conditions, the data backup time is 5 minutes after the power supply is turned off.
• The battery connector is disconnected.
• The battery lead is disconnected.
Battery life and replacement time
1. Battery life reference: Approx.5 years in actual use (Operating ambient temperature of 25°C)
Battery replacement time reference: 4 to 5 years
Calculate the natural discharge amount of the battery, as necessary.
2. Check if the battery condition is normal within the utility.
Refer to the following for the details of battery status display.
12. CLOCK SETTINGS AND BATTERY STATUS DISPLAY (TIME
8
- 36
8.9 Battery
8.9.4 Battery life
8.10 Protective Sheet
The protection sheet is used to protect the operation surface from damage or dirt when the touch key of GOT display section is operated.
8.10.1 Applicable protective sheet
The following protective sheets are applicable for GT15 .
When giving priority to brightness, select the clear protective sheet; when giving priority to preventing glare, select the anti-glare protective sheet.
Product name
Protective sheet
Model
GT15-90PSCB
GT15-90PSGB
GT15-90PSCW
*1
GT15-90PSGW
*1
GT15-80PSCB
GT15-80PSGB
GT15-80PSCW
*1
GT15-80PSGW
*1
GT15-70PSCB
GT15-70PSGB
GT15-70PSCW
*1
15" protective sheet
Protection sheet for 12.1"
Protection sheet for 10.4"
Description
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: White) 5 sheets
Antiglare (Frame: White) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: White) 5 sheets
Antiglare (Frame: White) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: White) 5 sheets
GT15-70PSGW
*1
GT15-60PSCB
GT15-60PSGB
Antiglare (Frame: White) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
GT15-60PSCW
*1
GT15-60PSGW
*1
GT15-50PSCB
GT15-50PSGB
Protection sheet for 8.4"
Clear (Frame: White) 5 sheets
Antiglare (Frame: White) 5 sheets
Clear 5 sheets
Antiglare 5 sheets
GT15-50PSCW
*1
GT15-50PSGW
*1
5.7" protective sheet
Clear (Frame: white) 5 sheets
Antiglare (Frame: white) 5 sheets
*1 Because the frame section is white, use this when making the GOT front face (other than the display section) white.
1
2
3
4
5
6
7
8
8.10 Protective Sheet
8.10.1 Applicable protective sheet
8
- 37
8.10.2 Installing procedure
1 Remove the old protective sheet from the GOT, and clean the GOT surface.
2 Peel the release paper from the back of the new protective sheet, and attach its adhesive side to the GOT display section.
When attaching the protective sheet, make sure to fit it on the display section closely without leaving any clearance between them.
3 Peel the protective film off the protective sheet.
Remark Replacement time of protective sheet
Check the status of the protection sheet visually by to the daily inspection.
The visibility becomes worse when there is too much dirt and cracks, causing malfunction. Proceeds replacement promptly.
8
- 38
8.10 Protective Sheet
8.10.2 Installing procedure
8.11 USB Environmental Protection Cover
The USB environment cover protects the USB connector on the front face of GOT from dust, water, and oil.
The GOT is installed with the USB environment cover at factory shipment.
Replace when damage and deterioration are caused.
8.11.1 Applicable USB environmental protecton cover
The following USB environmental protection cover is applicable for GT15
Model
GT15-UCOV
GT11-50UCOV
.
Description
Environmental cover for USB interface on the GOT main unit front side
(For complying IP67)
(For 15", 12.1", 10.4", 8.4")
Environmental cover for USB interface on the GOT main unit front side
(For complying IP67)
(For 5.7")
8.11.2 Installing procedure
1
2
3
4
1 Fix the USB environmental protection cover to the GOT by tightening its upper fixing screw within the specified torque range (0.36 to 0.48 N·m). (It is advisable to set the USB environmental protection cover along a guiding hole which is provided in the GOT, as it will make the installation easier.)
For other than GT155 For GT155
Guiding hole
Guiding hole
5
2 When the USB interface is not used, also tighten the lower fixing screw of the USB environmental protection cover within the specified torque range (0.36 to 0.48 N·m). (IP67 compliant)
For other than GT155 For GT155
6
7
8
8.11 USB Environmental Protection Cover
8.11.1 Applicable USB environmental protecton cover
8
- 39
3 When the USB interface is used, remove the lower fixing screw of the USB environmental protection cover, and connect the USB cable. (IP67 incompliant)
For other than GT155 For GT155
Precautions when the USB environment cover is opened
Environmental protective structure of USB interface is "IP2X" when the USB environmental cover is opened.
8
- 40
8.11 USB Environmental Protection Cover
8.11.2 Installing procedure
8.12 Stand
Stand is used to fix the GOT to standing status in order to debug the monitor screen data easily.
8.12.1 Applicable stand
The following stand is applicable for GT15
Product name
Stand
Model
GT15-90STAND
GT15-80STAND
GT15-70STAND
GT05-50STAND
.
Stand for 15"
Stand for 12.1"
Stand for 8.4"/10.4"
Stand for 5.7"
8.12.2 Installing procedure
Description
(1) GT15-90STAND, GT15-80STAND, GT15-70STAND
1 Set the stand so that the front side of the GOT to be mounted faces the front.
For GT15-70STAND, the surface to be used to set the GOT changes according to the GOT mounted.
2 Adjust the mounting angle of GOT with the angle adjusting screw of the stand.
3 Put the GOT into the Stand from the front side and fix it using the fixtures.
For the GOT mounting method, refer to the following.
1
2
3
4
5
6
For GT15-90 STAND,GT15-80 STAND For GT15-70 STAND
7
8
8.12 Stand
8.12.1 Applicable stand
8
- 41
(2) GT05-50STAND
1 Determine the angle for installing the GOT.
1 Slide the angle adjustment fitting as shown below to determine the angle.
1 The angle can be adjusted to 75°, 65°, 55° or 45°.
1 When installing multiple units to the GOT, use the stand with 75 or 65 degrees for securing leadin allowances for cables at the bottom of the GOT.
2 Once the angle is determined, insert the angle adjustment fitting's fixing hook into the hook insertion section on the bottom of the stand.
3 Securely tighten the fixing screw.
4 Insert the GOT from the front of Stand and install it to Stand.
Refer to the GT15 User's Manual for details on installing the GOT.
5 After the installation, perform wiring, etc.
8
- 42
8.12 Stand
8.12.2 Installing procedure
8.13 Attachment
The attachment is used to replace A960GOT, AC97 GOT to GT156 (8.4").
If use attachment when replace A960GOT or AC97 GOT to GT156 , there is no need of additional processing as mounting hole of the inside control panel etc. which is used for A960GOT, A97 GOT.
8.13.1 Applicable attachment
The following attachments are applicable for GT156 .
Model
GT15-60ATT-96
Description
A960GOT GT156
Attachment for 8.4"
GT15-70ATT-97 A97 GOT GT156
8.13.2 Installing procedure
1 Hang the two upper hooks on the upper part over the mounting holes in the control panel.
1
2
3
4
2 While lifting the attachment upward, hang the two lower hooks on the lower part of the control panel.
3 Fix the attachment to the control panel with four clamp screws in the torque range of 0.82 to 1.10N·m.
5
6
5
6
4 Place the GOT into the attachment from the front, and fix it by tightening the mounting screws included with the GOT in the torque range of 0.36 to 0.48N·m.
7
Precautions when the attachment is installed
• The attachment can be used when the mounting panel thickness is 1.2 to 3mm.
If the installation panel thickness exceeds 3mm, the GOT cannot be replaced by using the attachment.
• Replacing GOT with the attachment does not compliant with the standard IP65,
IP67, NEMA4 of the waterproof and dustproof.
8.13 Attachment
8.13.1 Applicable attachment
8
- 43
8
9. UTILITY FUNCTION
Utility is a function, which carries out connection of GOT and controller, screen display and operation method settings, program/data control and self-check etc.
Refer to the following for the utility function list.
9.1 Utility Execution
For utility execution, utility has to be displayed by installing BootOS and standard monitor OS in the C drive
(built in flash memory).
There are following three types for the installing BootOS and standard monitor OS methods.
1) GT Designer2 GOT
Via USB interface or
RS-232 interface GOT • Installed directly from the GT Designer2
GT Designer2
BootOS or standard OS installation
2) GT Designer2 Memory card GOT
OS file write
BootOS or standard monitor OS installation
GOT
• When GOT is remote, installed easily
using the memory card
Memory card
Install the memory card in GOT
GT Designer2
3) GOT Memory card GOT
OS file upload
GOT
BootOS, standard monitor OS installation
GOT
• Install OS from GOT to GOT using
memory card
Memory card
Install the memory card in GOT
Refer to the following for the installation which uses GT Designer2.
GT Designer2 Version Basic Operation/Data Transfer Manual
Refer to the following for the installation which uses GOT.
18. INSTALLATION OF COREOS, BOOTOS AND STANDARD MONITOR OS
9
- 1
9.1 Utility Execution
9.2 Utility Function List
The items in the following list can be set/operated on the utility screens.
Item
Detail settings
Functions overview
Setting of channel number for the communication interface and assignment of communication driver
Setting of communication parameter
Sequence program protection key word setting (When FX series PLC is connected)
Sequence program protection key word deleting (When FX series PLC is connected)
Sequence program protection status cancel (When FX series PLC is connected)
Setting of opening screen time
Setting of screen saving time
Setting of screen saving back light ON/OFF
Switching message language (Japanese/English/Chinese (Simplified)/Chinese
(Traditional)/Korean/German)
Battery alarm display ON/OFF setting
Human sensor Effective/Invalid setting
Display
Sensor detect level setting
Displaying sensor detect time
Sensor off delay setting
Brightness, contrast
Operation
Liquid crystal intensity setting
Setting of buzzer volume
Window move buzzer
Key sensitivity setting
Key reaction speed setting
Security level change (security password input of each object)
Setting of the menu call key
Security setting
*2
Utility call key
Touch panel adjustment
Touch panel coordinates adjustment
Q/QnA ladder monitor
*3
Transparent mode settings
Setting of data storage location for the MELSEC-Q/QnA ladder monitoring function
Channel No. setting for the communication target device in using the FA transparent function
Video/RGB Setting
Video Unit Settings
Video Display Settings
RGB Display Settings
Time setting & display
*4
Setting of the video input signal and resolution
Setting of the captive area size for each video channel, the color tone, contrast, brightness, and color intensity
Setting of the RGB clock phase, horizontal screen position, and vertical screen position
Selection of base clock
Display current time of clock.
Set current time of clock.
Display of battery status
*1: It is necessary to carry out the following items by GT Designer2.
• Installation of communication drivers
• Allocation of channel numbers and communication drivers
*2: It is necessary to set the security level by GT Designer2.
*3: This is not supported by the GT1555-Q or GT1550-Q.
*4: If necessary please install the battery.
9.2 Utility Function List 9
- 2
OS information
Item
Project Information
Alarm information
Historical graph display
Tally graph display
Advanced Recipe information
Advanced Recipe Record List
Logging information
Operation log information
Hard copy information
Memory card format
Memory Information
Special data information
Functions overview
Installing OS
Uploading OS
Property display of OS (Kind, version, and date)
Data check of system file (OS)
Downloading project file
Uploading project file
Project file deleting
Copying project file (A drive A drive)
Property display of project file (Date, version and screen title)
Data check of project file
Deleting alarm log file
Copying alarm log file
G1A CSV conversion (Convert from G1A of the alarm file to CSV)
G1A TXT conversion (Convert from G1A of the alarm file to TXT)
Displaying historical graph of alarm file
Tally graph display of alarm file
G1P CSV conversion (Convert from G1 of the advanced recipe file to CSV)
G1P TXT conversion (Convert from G1 of the advanced recipe file to TXT)
Deleting advanced recipe file or folder
Copying advanced recipe file
Moving advanced recipe file or folder
Changing advanced recipe folder name
Creating a new advanced recipe folder or file
Loading record data
Saving record data
Matching record data
Deleting device data
G1L CSV conversion (Convert from G1L of logging file to CSV)
G1L TXT conversion (Convert from G1L of logging file to TXT)
Deleting logging file or folder
Copying logging file
Moving logging file or folder
Changing logging folder name
Creating a new logging folder
G1O CSV conversion (Conversion from G1O of operation log file to CSV)
G1O TXT conversion (Conversion from G1O of operation log file to TXT)
Deletion of an operation log file or folder
Copying of an operation log file
Moving of an operation log file
Changing of an operation log file name
Creating of a new operation log folder
Displaying and searching of the list of operation logs
Deleting hard copy file
Copying hard copy file
Formatting memory card
Displaying memory space of GOT
Displaying file/holder name, data size and creation date and time of the file or folder
Deleting file/holder of the special data
Checking file of the special data
Downloading the special data written in the A drive (Standard CF Card) to C drive
(built in flash memory)
9
- 3
9.2 Utility Function List
Item
System monitor
Ladder monitor
A List editor
FX list editor
Debug
Intelligent module monitor
Network monitor
Motion monitor
Servo amplifier monitor
CNC monitor
Memory check
Drawing check
Self check
Font check
Touch panel check
I/O check
Network unit status display
System alarm display
GOT start time
Clean
Functions overview
Monitoring and testing PLC devices, monitoring and changing values in the special module buffer memory
Displaying ladder monitor, executing hard copy
Changing sequence programs or parameters of the ACPU
Editing FXCPU sequence program in a list
Monitoring buffer memory or changing data of an intelligent function module with the dedicated screen, monitoring signal statuses of an I/O module
Monitoring the network status of the MELSECNET/H, MELSECNET/10,
MELSECNET (II) or MELSECNET/B
Monitoring the servo of a motion controller CPU (Q series), setting parameters
Executing various monitor functions of servo amplifier, parameter changes, test operations, etc
Executing position display monitor, alarm diagnosis monitor, tool offset/param, and program monitor equivalent to the MELDAS dedicated display
A drive (standard CF card) memory check
C drive (Built-in Flash Memory) memory check
Liquid crystal missing bits check, color check, drawing check, display check and overlapping display check
Installed fonts check
Touch panel operation check
Connecting target check
Self-loopback check
*5
Monitoring of the LED status display for the MELSECNET/H communication unit and CC-Link communication unit (GT15-J61BT13)
Displaying of error information etc.
Displaying GOT errors, CPU errors, network errors
Resetting GOT errors
Displaying GOT start date and time, current time, accumulated operating hours
Display the screen to clean the display section.
Maintenance timing setting
*6
Black light maintenance timing setting.
Display section maintenance time notification period setting.
Setting of touch key maintenance notification count.
Setting of Built-in flash memory maintenance notification count.
Addition times reset
*6
Function to reset the value of the backlight maintenance notification time, display section maintenance notification time, touch key maintenance notification count, built-in flash memory maintenance notification count which has been additioned for the maintenance report function.
*5: It is necessary to install the RS-232 connector for the test. (
*6: It is necessary to install the option function board and the battery.
9.2 Utility Function List 9
- 4
9.3 Utility Display
To display setting screens fot each utility, the main menu has to be displayed first.
(1)
(2)
(1) Main menu
The menu items that can be set at the GOT utility are displayed.
Touching a menu item in the main menu will display the setting screen or following selection screen for the item.
In this manual, with a few special exceptions, explanations are given primarily using the GT1575-V screens.
(2) System message switch button
This button switches the language used for the utility or system alarms.
When touching the Language button, the Select Language screen is displayed.
1 Touch the button of a language to be displayed and then
OK
button, and the language is selected. *1
9
- 5
9.3 Utility Display
2 Touching the button restarts the GOT and the language on the utility is switched to the selected one.
*1: Only selectable languages are displayed.
The selectable languages differ depending on the fonts installed in the GOT.
For details of the fonts, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.3 Specifications of Applicable Characters)
When starting the GOT without selecting any language or the selected language and the installed fonts are not matched
The following screen will be displayed.
Touching the button of a desired language restarts the GOT and the language is switched to the selected one.
9.3 Utility Display 9
- 6
9.3.1
Display operation of main menu
The following three types of operation can display the main menu.
(Display the main menu after installing the basic OS from GT Designer2 to the GOT built in flash memory.)
(1) When project data is undownloaded
If the power supply of GOT turns ON, the main menu is displayed automatically after title display.
Main menu
GOT power supply ON
(2) When touching menu call key
If you touch the menu call key while user-created screen is displayed, the main menu is displayed.
The menu call key can be set by the GOT utility or GT Designer2.
(The menu call key is set in the position as described below at factory shipment.)
Model name
GT1595
GT1585, GT157
,
GT156
,
GT155
Default setting at factory shipment
1-point press on the GOT screen upper left corner
Simultaneous 2-point presses on the GOT screen upperright and left corners
Menu call key
1-point touch on the upper-left corner
Main menu
Menu call key
Simultaneous 2-point touch
9
- 7
9.3 Utility Display
9.3.1 Display operation of main menu
(1) Prohibited simultaneous 2-point presses on the GT1595-X
In the case of using a GT1595-X, do not touch 2 points or more on the GOT screen simultaneously.
Touching 2 points or more simultaneously may activate a part other than the touched point.
(2) When setting menu call key to 1-point
When having set [Pressing time] of the menu call key setting screen to other than
"0 (s)", keep pressing the touch panel for the period set to [Pressing time] or more before leaving the finger from the touch panel.
For menu call key setting, refer to the following.
(3) When touching special function switch (utility)
If you touch the special function switch (utility) while user-created screen is displayed, the main menu is displayed.
The special function switch (utility) can be set as a touch switch that is displayed on a user-created
.
screen by GT Designer2
Main menu
Special function switch
(Utility)
For the details of the special function switch, refer to the following.
GT Designer2 Version Screen Design Manual
Remark Locking the utility display by password
When you try to display the utility main menu while the password is set to the GOT by GT Designer2, the display for password input will be appeared.
(The password setting of GT Designer2 is in the common menu.)
9.3 Utility Display
9.3.1 Display operation of main menu
9
- 8
When the password is not matched, displays the error message.
When touching
OK
, the screen returns to the monitor screen.
(1) Input operation of password
1) Input the password after touching
0
to
9
,
A
to
F
key.
2) Define the password by touching
Enter
key, after password input.
3) To correct the input character, touch
Del
key to delete the correcting character and reinput/retype the new character.
(2) Password input cancel operation
When button is touched, it returns to the monitor screen.
Refer to the following for the details related to the password setting.
GT Designer2 Version Screen Design Manual
9
- 9
9.3 Utility Display
9.3.1 Display operation of main menu
9.3.2
Utility basic configuration
The basic configuration of utility is as follows.
Title display Close/Return button
Scroll key
Screen
(1) Title display
The screen title name is displayed in title display part.
As the screen is composed of multiple layers, the title including these layers is displayed.
Title display
Title display
(2) Close/Return button
When a middle screen of the layers is displayed, if the of screen is touched, returns to the previous screen.
(Close/return) button in the right corner
If this button is touched when directly displayed from monitor screen, the screen is closed and returns to monitor screen.
(3) Scroll button
For screens in which the content does not fit on one screen page, there is a right or down scroll button on the screen.
Scroll one line/column window
9.3 Utility Display
9.3.2 Utility basic configuration
9
- 10
9.3.3
Basic operation of settings change
1
Change of setting value
Setting item Select button
Setting item Select button
1 Touch the select button (setting point) on the screen.
According to the setting item, the button requires selecting setting value, inputting value or displaying other setting screen.
• ON Key: It is a key for selecting the setting value. Repeats with each touch
ON OFF
.
• Numerical Key: It is a key for inputting the numerical value. It displays the keyboard on the bottom of the screen when touched.
In the above mentioned screen example, there is no setting item which displays the keyboard. For the operation of keyboard refer to the next page.
Touching
Enter
confirms the numerical input.
When the setting range exists it repeats the numerical without displaying keyboard.
Example: 4800bps 9600bps 19200bps
• Setting...
Key: It shifts to the setting screen of each setting item when touched.
(Displays the another setting screen.)
2 Setting contents are reflected if
OK
button is touched.
3 If touch button without touching
OK
button, the dialogue mentioned below is displayed.
9
- 11
9.3 Utility Display
9.3.3 Basic operation of settings change
2
Keyboard operation
1 Touch the numerical value to be changed.
2 Keyboard for numerical input is displayed and cursor is displayed simultaneously.
The key board display position chanegs by the position of numerical value touched.
(At the time of numerical input, displayed in the position which will not interrupt the inputting.)
Cursor
Keyboard
3 Input numeric with keyboard.
•
•
•
•
•
•
0
to
9
Key : Input the numeric.
Enter
Cancel
Key
Key
Key
: Touching the
Enter
key completes numeric input and closes the keyboard.
: Touching the
Cancel
key cancels numeric input and closes the keyboard.
: Moves the cursor to the right or left side.
Available only if any selectable item is at the right/left side of the cursor.
Del
Key :
Del
key is used when canceling the input by 1 character.
key and the key which is not mentioned do not function.
4 If
Enter
key is touched, numeric input is completed and keyboard is closed.
9.3 Utility Display
9.3.3 Basic operation of settings change
9
- 12
10. COMMUNICATION INTERFACE
SETTING (COMMUNICATION SETTING)
In the communication setting, the communication interface names and the related communication channel, communication driver names display and channel numbers are set.
Moreover, in the communication detail settings, the communication interface details are set. (Communication parameters setting)
10.1 Communication Setting
10.1.1 Communication setting functions
Function
Channel-Driver assign
Channel no. (Ch No.) setting
Communication parameters setting
Description
Change the assignment of channel No. and communication driver name.
Set the channel numbers of the communication interface (Standard interface/
Extend interface).
Set communication parameters of communication devices.
10.1.2 Communication setting display operation
(
Main menu
Touch
[Communication
setting]
Communication setting
10
- 1
10.1 Communication Setting
10.1.1 Communication setting functions
10.1.3 Communication setting contents
This section describes setting items and display contents for Communication Setting.
(4)
(4)
(2)
(5)
(5)
(3)
(2)
(5)
(1)
9
10
11
(1) Channel-Driver assign
Channel No. can be assigned to the communication driver installed in the GOT.
(a) Communicating without setting [Communication Setting] of GT Designer2
Even without setting [Communication Setting] on GT Designer2, communication with controller is available by assigning channel No. with this function.
(
10.1.4 Channel-Driver assign operation)
(b) Changing the assignment of communication drivers to channels in the utility
Without using GT Designer2, the assignment of communication drivers to channels can be changed.
(When change a communication driver, the alternative communication driver has to be installed in GOT in advance.)
(2) Standard interface display BOX
Display the communication interface included as standard in GT15 .
There are the following 2 types.
RS232 ••••• For communicating with PC (GT Designer2), controller
USB •••••••• For communicating with PC (GT Designer2)
(3) Extend interface display BOX
The name of the unit installed in the extend interface is displayed.
(Displays [None] when any unit is not mounted.)
For details of each uint, refer to the following.
Extend interface
12
13
14
15
16
GOT front face
USB interface (Standard interface)
GOT rear face
RS-232 interface (Standard interface)
10.1 Communication Setting
10.1.3 Communication setting contents
10
- 2
(4) Channel number specification menu BOX
Set channel No. to use with standard interface or extend interface.
Refer to this section (5) for driver that can be assigned to each channel.
0: Set when the communication interface is not used.
1 to 4 :Set when connecting to a controller (Bar code reader is excluded.)
8: Set when connecting with bar code reader.
9: Set when connecting with PC (GT Designer2). (For USB and RS-232 interface, the simultaneous setting is possible. However, when either interface is during communication, communication is not possible for another interface.)
*: Set when using gateway functions (when non-Ethernet connections are used for controllers), Ethernet download function, printer, video display, RGB display, or RGB output.
• 5 to 7 can not be set.
• Fixed to 9 for the USB interface.
(5) Driver display BOX
The name of communication driver assigned to the channels or the driver set with the
Communication Setting of GT Designer2 is displayed.
The displayed names are shown below.
Driver name
Q BUS (Q)
A/QnA BUS
A/QnA/Q CPU, QJ71C24
MELSEC-FX
AJ71QC24
AJ71UC24/C24
MELSECNET/H
MELSECNET/10
CC-Link Ver. 2 (ID)
CC-Link(ID)
CC-Link(G4)
E71 Connection
Compatible connection type Displayed interface
Corresponding channel No.
Bus connection
Direct CPU connection, computer link connection, CNC connection
Direct CPU connection
Computer link connection
(
Extend interface display
BOX
(
Standard interface display BOX: RS232
Computer link connection
(
Extend interface display
BOX
1 to 4
MELSECNET/H connection (PLC to PLC network)
MELSECNET/10 connection (PLC to PLC network), CNC connection
CC-Link connection (intelligent device station)
Ver. 2
CC-Link connection (Intelligent device station)
CC-Link connection (Via G4)
Ethernet connection, CNC connection
(
Extend interface display
BOX
(Continue to next page)
10
- 3
10.1 Communication Setting
10.1.3 Communication setting contents
Driver name Compatible connection type Displayed interface
Corresponding channel No.
OMRON SYSMAC
KEYENCE KV-700/1000
SHARP JW
JTEKT TOYOPUC-PC
OMRON PLC connection
KEYENCE PLC connection
SHARP PLC connection
JTEKT PLC connection
TOSHIBA PROSEC T/V
HITACHI HIDIC H
TOSHIBA PLC connection
HITACHI PLC connection
HITACHI HIDIC H2
MATSUSHITA MEWNET-FP MATSUSHITA PLC connection
YASKAWA PLC connection YASKAWA GL
YOKOGAWA FA500/FA-M3/
STARDOM
YOKOGAWA PLC connection
AB SLC500, AB 1:N
AB MicroLogix
SIEMENS S7-200
SIEMENS S7-300/400
Microcomputer connection
OMRON THERMAC/
INPANEL NEO
Allen-Bradley PLC connection
SIEMENS PLC connection
Microcomputer connection
OMRON temperature controller connection
FUJI PXR/PXG/PXH
YAMATAKE SDC/DMC
RKC SR Mini HG
FREQROL 500/700
MELSERVO-J3, J2S/M
Barcode
E71/Gateway
Gateway
Ethernet download
Printer
Video/RGB Input
RGB Output
FUJI temperature controller connection
YAMATAKE temperature controller
RKC temperature controller connection
Inverter connection
Servo amplifier connection
Barcode reader connection
Ethernet connection and gateway function
Gateway function
At Ethernet download
Printer connection
Video/RGB Input
RGB Output
Host (PC)
(
Standard interface display BOX: RS232
(
Extend interface display
BOX
(
Extend interface display
BOX
1 to 4
*
*
*
*
8
1 to 4
*
At transfer of OS or project data, FA transparent function
(
Standard interface display BOX: RS232/USB
9
Display [None] in the driver display BOX in case of the followings.
• The communication driver is not installed. (
• In channel number specification menu BOX, [0] is set.
• The communication unit type and the communication driver are mutually not corresponding at the extend interface side.
When set the channel number to [9], the communication driver [Host (PC)] is automatically assigned.
9
10
11
12
13
14
15
16
10.1 Communication Setting
10.1.3 Communication setting contents
10
- 4
Precautions for communications between GOT and controller
(1) Installing communication driver and downloading Communication Setting
The followings below are required for the communication interface to communicate with the controller.
1) Installing communication drivers (Up to 4 communication drivers)
2) Assigning the channel number and communication driver for the communication interface
3) Downloading the contents (project data) assigned in 2).
Perform1), 2), 3) by GT designer2.
Refer to the following for details.
• GT Designer2Version
Screen Design Manual
(3.7 Communication Interface Setting (Communication Settings))
• GT Designer2Version
Basic Operation/Data Transfer Manual
(8.3.1 Downloading project data [PC to GOT])
(2) When Communication Setting has not been downloaded.
The GOT automatically assigns the installed communication driver in the order of
1 to 4 as follows.(Only the extend interface is assigned automatically.)
1)
3)
2)
4)
10
- 5
1) ChNo.1, CCommunication driver installed at 1st
2) ChNo.2, CCommunication driver installed at 2nd
3) ChNo.3, CCommunication driver installed at 3rd
4) ChNo.4, CCommunication driver installed at 4th
(a) After communication driver is assigned automatically.
When saving the settings to the GOT with
OK
button after the automatic assignment of communication driver, automatic assignment will not be performed at the next time and after.
10.1 Communication Setting
10.1.3 Communication setting contents
(b) Priority against [Communication Settings] of GT Designer2
If download the communication settings to the GOT with GT Designer2 after the automatic assignment, the GOT will operate with the communication settings of the GT Designer2. (The GOT operates with the latest communication settings.)
(3) When the communication driver does not match with the unit that is installed in the
GOT
An error is displayed on the GOT when displaying [Communication setting].
If an error is displayed, confirm the combination of the communication driver and communication unit.
Refer to the following manual for the combination.
GOT1000 Series Connection Manual (System Configuration in each chapter)
9
10
11
12
13
14
15
16
10.1 Communication Setting
10.1.3 Communication setting contents
10
- 6
10.1.4 Communication setting display operation
1
Channel-Driver assign operation
The following describes how to operate the Channel-Driver assign.
The example of changing to direct CPU connection (Communication driver: "A/QnA/QCPU, QJ71C24,
MELDAS C6*") for the GOT of computer link connection (Communication driver: [AJ71QC24]) is used.
Before the operation
The GOT automatically restarts after executing this setting.
If project data has been downloaded, the GOT starts monitoring of the controller after restarting.
Execute this setting after carefully confirming the safety.
1 Install communication driver "A/QnA/
QCPU, QJ71C24, MELDAS C6*" to GOT.
(Download of [Communication Setting] from GT Designer is not required.)
After installing communication driver, touch
[Communication Setting].
2 Touch the
Change assignment
button on the dislayed screen as shown left.
(Continued to next page)
10
- 7
10.1 Communication Setting
10.1.4 Communication setting display operation
3 As the communication driver ([A/QnA/
QCPU, QJ71C24]) installed in the GOT is displayed, touch it.
9
10
11
4 The screen returns to the Channel-Driver assign screen. Touch the
OK
button.
5 Touch the button and return to the
Communication Setting screen.
12
13
6 Confirm that the selected communication driver ([A/QnA/QCPU, QJ71C24]) is assigned.
7 After the confirmation, touch the button.
OK
8 Touch the button to restart GOT.
9
14
15
16
10.1 Communication Setting
10.1.4 Communication setting display operation
10
- 8
2
Channel number setting operation
1 Touch channel number specification menu BOX to be set.
keyboard
2 The cursor for the channel number specification menu BOX is displayed.
Simultaneously the keyboard for a numerical input is displayed.
3 Input the channel number from the keyboard and touch
Enter
key, and the value is defined.
Simultaneously, the name of the communication driver corresponding to the channel number assigned by GT Designer2 is displayed in the driver display BOX.
10
- 9
10.1 Communication Setting
10.1.4 Communication setting display operation
9
3
Communication detail settings switching operation
1 If you touch the driver display BOX, the screen switches to the detailed setting screen of the related controller device.
(
10.2 Communication Detail Settings)
4
5V power supply setting operation
When connecting a controller to the RS-232 interface, whether to supply 5VDC power or not to the controller through 9 pins can be selected.
Thus, it is not necessary to connect an external power supply.
When setting the RS-232 interface to "9" (Host (PC)), the 5V supply is automatically changed to [NO].
1 Touch [5V supply].
10
11
12
13
2 Select and define whether 5V power supply is supplied or not.
14
15
16
10.1 Communication Setting
10.1.4 Communication setting display operation
10
- 10
3 After setting completion, [ ] is displayed indicating that 5V power supplying setting is on.
10
- 11
10.1 Communication Setting
10.1.4 Communication setting display operation
10.2 Communication Detail Settings
10.2.1 Communication detail settings functions
Function
Communication parameters setting
Keyword setting
Key word deleting
Key word protection cancel
Keyword protection
Description
Set various communication parameters of communication devices.
The settable parameters differ according to the communication device.
For the FX series PLCs, key word for protecting program in the PLC can be set.
For the FX series PLCs, key word for protecting program in the PLC can be deleted.
For the FX series PLCs, the program protection status in the PLC can be cancelled.
For the FX series PLCs, the cancelled program protection status in the PLC can be returned to the protection status again.
9
10
11
10.2.2 Communication detail settings display operation
1 Touch the driver display BOX of the communication parameter to be set in the communication setting screen.
12
13
14
15
16
10.2 Communication Detail Settings
10.2.1 Communication detail settings functions
10
- 12
2 The screen switches to the communication detail setting screen.
Set communication parameters from this screen.
Refer to the following for the setting change operation.
9.3.3 Basic operation of settings change
Communication parameter
Communication parameter setting by Designer2
Set the communication parameters for each communication driver at
[Communication Settings] in [System Environment] of GT Designer2.
When change the communication parameters after downloading project data, change the setting at communication detail setting of GOT.
GT Designer2 Version Screen Design Manual
(3.7 Communication Interface Setting (Communication setting))
10
- 13
10.2 Communication Detail Settings
10.2.2 Communication detail settings display operation
10.2.3 Display contents of communication detail settings
The contents of Communication Detail Settings varies according to driver type.
This section explains setting items different from the communication detail settings of the GT Designer2.
For setting items other than described in this section, refer to the following manual.
GT Designer2 Version
Screen Design Manual
(3.7 Communication Interface Setting (Communication Settings))
9
10
11
12
13
14
15
16
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
10
- 14
(1) MELSEC-FX
Key word registration, deletion and protection delete
1
Registration
Register key words.
1 Touching the
Regist
key pop-up displays the keyboard for inputting a keyword.
2 Input a keyword and touch the
Enter
key, and the registration completes.
1 Up to 8 characters can be set for keyword with using A to F and 0 to 9.
PLC connected
When registering keyword and 2nd keyword
FX CPU compatible with
2nd keyword
FX CPU not compatible with 2nd keyword
[Registration condition]*1 can be selected.
Setting
When registering keyword only
[Registration condition]*1 cannot be selected.
*1 [Registration condition]
The access restriction can be selected from [Read/Write Protect], [Write Protect], and [All Protect].
For access restriction on each setting, refer to the following manual.
The User's Manual of the FX series PLC you are using
10
- 15
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
9
(1) How to select a keyword protection level
For equipments that are allowed to operate the FX PLC on line, 3 levels of protection level can be set.
When performing monitoring or changing settings with any on-line equipment is required, set password with referring to the following.
(a) When setting keyword only
Select a protection level by the initial letter of keyword.
All operation protect: Set a keyword with initial letter of "A", "D" to "F", or "0" to
"9".
Anti-plagiarism: Set a keyword with initial letter of "B".
Incorrect write protect: Set a keyword with initial letter of "C".
(b) When setting keyword and 2nd keyword
Select a protection level by [Registration condition].
(2) Monitoring availability at each keyword protection level
Device monitoring availability at each keyword protection level is shown in the following.
Item
When registering keyword only
All operation protect
Antiplagiarism
Incorrect write protect
When registering keyword and 2nd keyword
All on-line operation protect
Read/ write protect
Write protect
Keyword not registered or protection cancelled
Monitoring devices
Changing devices
T, C set value and file register
(D1000 and the following)
Other than the above
(3) Difference between all online operations prohibition and all operations prohibition
When specifying All online operations prohibited, displaying devices and inputting data with a programming tool or GOT are all prohibited.
When all operations are prohibited, displaying devices and inputting data with the
GOT are enabled while all operations using a programming tool are prohibited.
10
11
12
13
14
15
16
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
10
- 16
2
Deletion
Delete a registered keyword.
1 Touching the
Regist
key pop-up displays the keyboard for inputting a keyword.
2 Input a key word and touch the
Enter
key, and the keyword is deleted.
PLC connected
FX CPU compatible with 2nd keyword
FX CPU not compatible with 2nd keyword
Input a keyword to delete.
Setting
Input the keyword to delete only into the keyword.
The 2nd keyword will be ignored.
3
Protection delete
Delete the protection by key word in order to access to a FX PLC to which a key word is registered.
1 Touching the
Clear
key pop-up displays the keyboard for inputting a keyword.
2 Input a keyword and touch the
Enter
key to delete the protection.
PLC connected
FX CPU compatible with 2nd keyword
FX CPU not compatible with 2nd keyword
Input a keyword to delete the protection.
Setting
Input a keyword to delete only into the keyword.
The 2nd keyword will be ignored.
4
Protection
Reset the keyword in which protection has been deleted to the protection status.
1 Touch the
Protect
key, and the keyword goes to a protected status.
10
- 17
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
11. DISPLAY AND OPERATION SETTINGS
(GOT SET UP)
Setting screen for display and setting screen for operation can be displayed from GOT setup.
In the setting screen for display and the setting screen for operation, the following settings can be set.
Reference page
Display
Item Description
Opening screen time, screen save time, screen save backlight, language, battery alarm display, human sensor, sensor detect level, sensor detect time, sensor off delay
Brightness
Buzzer volume, window move buzzer volume, Key sensitivity,
Key reaction speed
Security setting Operation
Utility call key
Touch panel calibration
Q/QnA ladder monitor
Data save location
Transparent mode Ch No.
Video/RGB
Setting
Video unit, video display, RGB display
11-2
11-13
11-15
11-19
11-21
11-24
11-27
11-30
11-9
9
10
11
12
13
14
15
16
11
- 1
11.1 Display Settings
11.1.1 Display setting functions
Setting regarding display is possible.
The items which can be set are shown below. When each item part is touched, the respective setting becomes possible.
Items Description
Opening screen time
Screen save time
Screen save backlight
The title display period at the main unit boot can be set.
The period from the user stops the touch panel operation till the screen save function starts can be set.
Whether turn ON or OFF the backlight simultaneously at the screen save function start can be specified.
Setting range
0 to 60 seconds
*1
<At factory shipment: 5 seconds >
0 to 60 minutes
<At factory shipment: 0 minutes>
ON/OFF
<At factory shipment: OFF>
Language
*3
Confirmation of the current language and switching language can be performed regarding with the language displayed by utility and dialogue.
(Japanese)
(English)
(Chinese
(Simplified))
(Traditional))
(Chinese
(Korean)
(German)
<At factory shipment: User's selection>
Battery alarm display
Whether to display system alarm when the voltage of the GOT internal battery has dropped can be specified.
The brightness can be adjusted.
<At factory shipment: OFF>
Brightness, Contrast
11.2 Brightness, Contrast Adjustment
Human sensor
Screen saver status cancel by human sensor can be set to Effective or Invalid.
Effective/Invalid
<At factory shipment: Effective>
Sensor detect level
*2
The sensor detect level can be set.
0 to 10
<At factory shipment:10>
Sensor detect time
*2
The time corresponding to the [Sensor detect level] is displayed. (setting is disabled)
When the [Sensor detect level] is changed, the corresponding time is reflected by touching
Enter
button.
0 to 4
<At factory shipment: 4sec>
11
- 2
11.1 Display Settings
11.1.1 Display setting functions
Items
Sensor off delay
Description
The time period from when the human sensor detects no human movement until the Human
Sensor Detection Signal (System Signal 2-1.b5) turns OFF can be set.
Setting range
0Min 10Sec to 60Min 0Sec
<At factory shipment: 0Min
10Sec>
*1: If setting 0, the title screen is not hidden.
The title screen is always displayed for 4 seconds or longer (which changes depending on the project data contents).
*2: The monitoring time corresponding to the sensor detect level (0 to 10) is as follows.
As the sensor detect level becomes greater, the sensitivity of the human sensor becomes higher.
0
4
Sensor detect level
Monitoring time [s]
10
0
9
0.1
8
0.2
7
0.4
6
0.8
5
1
4
1.5
3
2
2
2.5
*3: Only selectable languages are displayed.
The selectable languages differ depending on the fonts installed in the GOT.
For details of the fonts, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.3 Specifications of Applicable Characters)
1
3
9
10
11
(1) Display setting by GT Designer2
Set title display period, screen save time and screen save backlight at [GOT set up] in [System Environment] of GT Designer2.
When change a part of the setting after downloading the project data, change the setting by [Display] screen of the GOT.
GT Designer2 Version Screen Design Manual
(3.8 Setting of the GOT display and operation (GOT setup) )
(2) Screen save time
Using the system information function can compulsorily switch the controller to the screen saving status (Forced Screen Saver Disable Signal) or disable the screen save time (Automatic Screen Saver Disable Signal) set with Utility.
GT Designer2 Version Screen Design Manual
(3.6 Setting System Information)
(3) Screen save backlight
When [Screen save backlight] is set to [ON], using the system information function
(Backlight OFF output signal) can switch the backlight OFF from the controller.
When [Screen save backlight] is set to [OFF], the above signal has no effect on the screen save backlight.
GT Designer2 Version Screen Design Manual
(3.6 Setting System Information)
12
13
14
15
16
11.1 Display Settings
11.1.1 Display setting functions
11
- 3
(4) Display control by human sensor (Specific to GT1595-X, GT1585V-S, GT1585-S)
The human sensor is a function that releases the GOT from the screen saving mode without the necessity to touch the GOT.
This function releases the GOT from the screen saving mode when the operator has come closer to the GOT.
Approach Go away Approach Go away
Operator motion
"Sensor detect"
Human Sensor
Detection Signal
"System Signal 2.b5"
ON
"Sensor
OFF delay"
"Sensor
OFF delay"
OFF
Screen saving mode released
Screen saving mode active
Screen saving
"Screen save time"
When there is no operator around the GOT for the time set as "Sensor OFF delay", the "Human Sensor
Detection Signal" turns OFF.
When the time set as the "Screen save time" elapses after the "Human Sensor Detection Signal" turns
OFF, the GOT enters the screen saving mode.
Refer to the following manual for the Human Sensor Detection Signal (System
Signal 2-1.b5).
GT Designer2 Version Screen Design Manual
(3.6 Setting System Information)
(5) When setting the human sensor to invalid (Specific to GT1595-X, GT1585V-S,
GT1585-S)
Even if setting the human sensor to invalid by the utility, the Human Sensor
Detection Signal (System Signal 2-1.b5) turns ON when the human sensor detects human movement.
Unintended operation may result, therefore, if controlling the Forced Screen Saver
Enable Signal (System Signal 1-1.b1) and Human Sensor Detection Signal associating them with each other by a sequence program, etc.
When setting the human sensor to invalid, review the related sequence program, etc.
11
- 4
11.1 Display Settings
11.1.1 Display setting functions
11.1.2 Display operation of display setting
(
Main menu
GOT setup
Touch
[GOT setup]
Touch
[Display]
Display
Touch an item to change settings
13
Restart after setting change
If return the display to the GOT setup screen by touching the button after the setting of each item is changed and touch the the GOT will restart.
button on the GOT setup screen,
After GOT restarts, it is displayed with the changed settings.
If restarted the GOT by powering OFF the GOT without the procedure above, the setting contents are canceled without reflected.
14
If touch , the GOT restarts and the changes are reflected.
15
16
11.1 Display Settings
11.1.2 Display operation of display setting
11
- 5
11
12
9
10
11.1.3 Display setting operations
1
Opening screen, screen save time
1 If touching the setting (numerical), keyboard is displayed. Input numeric with the keyboard.
2 Setting contents are defined if is touched.
OK
button
3 If touch button without touching
OK button, the dialog mentioned left is displayed.
4 If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
11
- 6
11.1 Display Settings
11.1.3 Display setting operations
2
Screen save backlight, battery alarm display
9
1 Setting item is changed if setting item is touched. (ON OFF)
2 Setting contents are defined if is touched.
OK
button
10
11
3 If touch button without touching
OK
button, the dialog mentioned left is displayed.
12
4 If close the display setting and GOT setup screens after completing the setting of all restarts and reflects the setting contents.
13
14
15
16
11.1 Display Settings
11.1.3 Display setting operations
11
- 7
3
Language
1 Touch the setting item to display the Select
Language screen.
2 When touching the button of a desired language, the language is selected and the screen returns to the Display screen. *1
3 Touching the set contents.
OK
button determines the
The displayed language will not be changed until is performed.
11
- 8
11.1 Display Settings
11.1.3 Display setting operations
4 If touch button without touching
OK button, the dialog mentioned left is displayed.
9
10
5 If close the display setting and GOT setup screens after completing the setting of all restarts and reflects the setting contents.
*1: Only selectable languages are displayed.
The selectable languages differ depending on the fonts installed in the GOT.
For details of the fonts, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.3 Specifications of Applicable Characters)
4
Brightness, Contrast
Refer to the following for brightness, contrast setting.
11.2 Brightness, Contrast Adjustment
11
12
13
14
15
16
11.1 Display Settings
11.1.3 Display setting operations
11
- 9
5
Human sensor
1 Setting item is changed if setting item is touched. (Effective Invalid)
2 Setting contents are defined if is touched.
OK
button
3 If touch button without touching
OK button, the dialog mentioned left is displayed.
4 If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
11
- 10
11.1 Display Settings
11.1.3 Display setting operations
6
Sensor detect level, sensor off delay
9
1 If touching the setting (numerical), keyboard is displayed. Input numeric with the keyboard.
To move the cursor, touch the or button.
2 Setting contents are defined if is touched.
OK
button
10
11
3 If touch button without touching
OK button, the dialog mentioned left is displayed.
12
13
4 If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
14
15
16
11.1 Display Settings
11.1.3 Display setting operations
11
- 11
11.2 Brightness, Contrast Adjustment
11.2.1 Functions of the brightness, contrast
The brightness and contrast can be adjusted.
Function
Brightness setting
Contrast adjustment
Description
Brightness of display part can be adjusted by 8 levels. (4 levels for the GT1575-
VN, GT1572-VN or GT1562-VN)
The display section contrast can be adjusted by 16 levels. (GT1555-QSBD,
GT1550-QLBD)
11.2.2 Display operation of brightness, contrast
(
Main menu
GOT setup Display
Touch
[GOT setup]
Touch
[Display]
Touch [Brightness,
contrast]
Brightness, contrast adjustment adjust the brightness.
11
- 12
11.2 Brightness, Contrast Adjustment
11.2.1 Functions of the brightness, contrast
11.2.3 Operating the brightness, contrast
9
1 Brightness can be adjusted by touching
+
,
-
key of brightness adjustment.
2 Setting contents are defined if is touched.
OK
button
10
11
3 If touch
OK
button without touching button, the dialog mentioned left is displayed.
12
4 If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
13
14
15
16
11.2 Brightness, Contrast Adjustment
11.2.3 Operating the brightness, contrast
11
- 13
11.3 Operation settings
11.3.1 Operation setting functions
Setting regarding GOT operation can be set.
The items which can be set are described below. If touch the each item part, the respective setting becomes possible.
Function Description
Buzzer volume setting
Window move buzzer volume setting
Buzzer volume setting can be changed.
Whether turn ON/OFF buzzer when move window can be selected.
Setting range
OFF/SHORT/LONG
<At factory shipment:
SHORT>
ON/OFF
<At factory shipment:
ON>
Security level change screen can be displayed.
Security setting screen change
Utility call key screen change
Key sensitivity setting
Utility call key setting screen can be displayed.
The touch panel sensitivity when touching the GOT screen can be set.
E.g. a setting can be changed when double-touch is made when touching the GOT screen only once. (For preventing chattering)
Touch panel reading error can be corrected.
1 to 8
*1
Touch panel calibration
11.6 Adjusting the Touch Panel Position
(Touch panel calibration Setting)
*1 Relation between the [Key sensitivity] setting and [Key reaction speed]
The larger the set value in [Key sensitivity] is, the shorter the time taken from touching the touch panel until the GOT responds becomes.
E.g. decrease the value set for [Key sensitivity] when double-touch is made when touching the GOT screen only once. (Decrease the reaction speed.)
The relation between the [Key sensitivity] setting and [Key reaction speed] is as follows.
[Key sensitivity] setting
[Key reaction speed]
Quick response Slow response
8 7 6 5 4 3 2 1
- 20ms- 10ms
0ms
(Standard)
+ 30ms + 60ms + 120ms + 240ms + 480ms
11
- 14
Operation settings by GT Designer2
Set buzzer volume and window move buzzer volume by [GOT setup] in [System
Environment] of GT Designer2.
When change a part of the setting, change the setting by the GOT display setting after downloading the project data.
GT Designer2 Version Screen Design Manual
(3.8 Setting of the GOT display and operation (GOT setup))
11.3 Operation settings
11.3.1 Operation setting functions
11.3.2 Display operation of display setting
(
Main menu
GOT setup
Touch
[GOT setup]
Operation settings
Touch
[Operation]
Touch an item to change settings
9
10
11
12
13
Restart after setting change
If return the display to the GOT setup screen by touching the button after the setting of each item (excluding the security setting) is changed and touch the button on the GOT setup screen, the GOT will restart.
After GOT restarts, it is displayed with the changed settings.
If restarted the GOT by powering OFF the GOT without the procedure above, the setting contents are canceled without reflected.
14
If touch , the GOT restarts and the changes are reflected.
15
16
11.3 Operation settings
11.3.2 Display operation of display setting
11
- 15
11.3.3 Setting operation of operation
1
Buzzer volume, window move buzzer
1 Setting items are changed if setting item is touched.
Buzzer volume :
SHORT LONG
Window move buzzer: OFF
OFF
ON
2 Setting contents are defined if is touched.
OK
button
3 If touch button without touching
OK button, the dialog mentioned left is displayed.
2
Security setting
Refer to the following for the security setting operation
3
Utility call key
Refer to the following for the utility call key operation
4 If close the display setting and GOT setup screens with button after completing the setting of all items to change, GOT restarts and reflects the setting contents.
11
- 16
11.3 Operation settings
11.3.3 Setting operation of operation
4
Key sensitivity setting
9
1 If touching the setting items, keyboard is displayed.
Input numeric with the keyboard.
2 The key response speed corresponding to the [Key sensitivity] setting is displayed.
3 Touching the setting.
OK
button determines the
10
11
5
Touch panel adjustment
Refer to the following for touch panel adjustment operation.
11.6 Adjusting the Touch Panel Position (Touch panel calibration Setting)
12
13
14
15
16
11.3 Operation settings
11.3.3 Setting operation of operation
11
- 17
11.4 Security Level Change
11.4.1 Security level change functions
Changes the security level to the same security level set by each object or screen switch.
To change the security level, input the password of the security level which is set in GT Designer2.
Security level setting .....................
GT Designer2 Version
(5.8 Security function)
Screen Design Manual
Password setting...........................
GT Designer2 Version Screen Design Manual
(3.5 Set Password)
Restrictions on screen display
The security level change screen cannot be displayed when project data do not exist in GOT.
Change the security level after downloading the project data to GOT.
11.4.2 Displaying the security level change
(
Main menu
GOT setup
Operation settings
Touch
[GOT setup]
Touch
[Operation]
Touch
[Security setting]
Security setting
Touch
[Security level change]
Security level change
Input the password of the security level which is set in
GT Designer2.
11
- 18
11.4 Security Level Change
11.4.1 Security level change functions
11.4.3 Security level change operation
1
Password input operation
9
1 By touching
0
to
9
,
A
to
F
key, the password of the changed security level is input.
2 When correcting the input character, touch
Del
key to delete the correcting character and input the password again.
10
11
3 After inputting password, touch the key.
Enter
When the password matches, the normal completion message is displayed. When the password does not match, an error message is displayed.
4 If
OK
button is touched it returns to the password input screen again.
12
13
14
5 If button is touched it returns to security setting screen.
15
Remark About forgetting to return to the original level after changing security level temporarily
When use GOT after temporarily changing the security level, do not forget to return the security level to the original level.
16
11.4 Security Level Change
11.4.3 Security level change operation
11
- 19
11.5 Utility Call Key Setting
11.5.1 Utility call key setting function
The key position for calling the main menu of the utility can be specified.
For the key position, 1 or 2 points can be specified from 4 corners on the screen.
When specifying 1 point, a setting to switch the screen to the utility by keeping pressing the key position is available.
This prevents a switching to the utility by an unintentional operation.
The number of key positions that can be set differs depending on the GOT type.
Model name
GT1595
GT1585, GT157 , GT156 , GT155
1 point
1 or 2 points
The number of settable key positions
Operation settings by GT Designer2
Set the utility call key at [GOT set up] in [System Environment] of GT Designer2.
When change a part of the setting after downloading the project data, change the setting by [Display] screen of the GOT.
GT Designer2 Version Screen Design Manual
(3.8 Setting of the GOT display and operation (GOT setup))
11.5.2 Utility call key display operation
(
Main menu
GOT setup
Operation settings
Touch
[GOT setup]
Touch
[Operation] Touch
[Utility call key]
Menu call key
Touch buttons to set for the menu call key
11
- 20
11.5 Utility Call Key Setting
11.5.1 Utility call key setting function
11.5.3 Utility call key setting operation
9
1 Touch or displayed at the 4 corners of the setting screen.
The button repeats every touch.
with
Set the corner to be set to a key position to
.
10
11
2 When setting 1 point, specify time for keeping pressing the key position to switch to the utility.
Touch the time input area.
3 Touching the input area displays a keyboard.
Input numerical value from the keyboard.
4 Touching setting.
OK
button determines the
12
13
5 If touch button without touching button, the dialog mentioned left is displayed.
OK
14
15
6 If close the display setting and GOT setup screens with button after completing the setting of all items to change, GOT restarts and reflects the setting contents.
16
11.5 Utility Call Key Setting
11.5.3 Utility call key setting operation
11
- 21
(1) When using GT1595-X
For the key position, 1 point only can be set.
(2) Setting another key position when two
Change either key position from to
You cannot select three have been already set
before making the setting.
at the same time.
Example: Changing the 2 points of the upper left and right corners to those of the upper left and lower left corners.
Change right corner to at the upper
.
Change left corner to at the lower
.
11
- 22
11.5 Utility Call Key Setting
11.5.3 Utility call key setting operation
11.6 Adjusting the Touch Panel Position
(Touch panel calibration Setting)
9
11.6.1 Touch panel calibration setting function
Touch panel reading error can be corrected.
Normally the adjustment is not required, however, the difference between a touched position and the object position may occur as the period of use elapses.
When any difference between a touched position and the object position occurs, correct the position with this function.
Before adjustment After adjustment
Run Stop Run Stop
10
11
12
The [Run] will operate though you intended to touch the [Stop] button.
The [Stop] button can be touched without fail.
11.6.2 Touch panel calibration setting display operation
13
(
Main menu
GOT setup Operation settings
Touch
[GOT setup]
Touch
[Operation]
Touch
[Touch panel calibration] 14
Touch panel calibration
15
Perform touch panel adjustment
16
11.6 Adjusting the Touch Panel Position (Touch panel calibration
Setting)
11
- 23
11.6.3 Touch panel calibration operation
Touch the point displayed on the screen with the finger one by one to make the setting.
1 Touch the upper left.
point displayed on the
Be sure to touch the center of the precisely.
2 Touch the upper right.
point displayed on the
3 Touch the lower left.
point displayed on the
11
- 24
11.6 Adjusting the Touch Panel Position (Touch panel calibration
Setting)
4 Touch the lower right.
point displayed on the
9
10
5 When the setting is completed, the message shown left is displayed.
Touching the
OK previous screen.
button returns to the
11
12
15
16
13
14
11.6 Adjusting the Touch Panel Position (Touch panel calibration
Setting)
11
- 25
11.7 Q/QnA Ladder Monitor
11.7.1 Q/QnA ladder monitor setting function
The data used for ladder monitor function can be saved.
Saving the ladder data cuts out the need for reading the ladder data from PLC CPU at the next GOT start-up, enabling to start the ladder monitoring earlier.
Refer to the following manual for details of the ladder monitoring function.
GOT1000 Series Extended/Option Functions Manual
Function
Data save location
Description
Select the ladder data storage location of the Q/QnA ladder monitor.
Setting range
C: Flash Memory/A: Standard CF Card/Not store
<Default: C: Flash Memory>
(1) Ladder data to be saved
(a) The ladder data to be saved is used by the GOT to execute ladder monitoring.
The ladder data can be saved in the CF card with this function, however it cannot be copied in the PC to be referred/edited with GX Developer, etc.
For the name of ladder data to be saved, refer to the following.
(b) The ladder data saved in the built-in flash memory and standard CF card (file name: CIRDAT) can be deleted by selecting [Project information] of
[Program/Data control].
13.3.4 Operation of project information
(2) For the GT1555-Q, GT1550-Q
This setting is not provided for these models since they do not support the
MELSEC-Q/QnA ladder monitor.
11
- 26
11.7 Q/QnA Ladder Monitor
11.7.1 Q/QnA ladder monitor setting function
11.7.2 Display operation of Q/QnA ladder monitor
Main menu GOT setup
Touch
[GOT setup] Touch [Q/QnA ladder monitor]
[Q/QnA ladder monitor]
Select the ladder data storage location of the
Q/QnA ladder monitor.
13
Restart after setting change
If return the display to the GOT setup screen by touching the button after the setting of each item is changed and touch the button on the GOT setup screen, the GOT will restart.
After GOT restarts, it is displayed with the changed settings.
If restarted the GOT by powering OFF the GOT without the procedure above, the setting contents are canceled without reflected.
14
If touch , the GOT restarts and the changes are reflected.
15
16
11.7 Q/QnA Ladder Monitor
11.7.2 Display operation of Q/QnA ladder monitor
11
- 27
11
12
9
10
11.7.3 Q/QnA ladder monitor setting operation
1 Setting items are changed if setting item is touched.
C: Flash Memory
A: Standard CF card
Not store
2 By touching the reflected.
OK
button, the setting is
3 If touch button without touching
OK button, the dialog mentioned left is displayed.
4 Touching the button restarts GOT.
After restarting, GOT operates with changed value.
11
- 28
11.7 Q/QnA Ladder Monitor
11.7.3 Q/QnA ladder monitor setting operation
11.8 Transparent Settings
(Transparent Mode Setting)
9
11.8.1 Function of the transparent mode
When using the multi-channel function, the channel No. of a controller to which the FA transparent function is executed can be specified.
For the multi-channel function, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.8 Multi-channel Function)
Also, refer to the following manual for the FA transparent function.
GOT1000 Series Connection Manual (33 FA TRANSPARENT FUNCTION)
10
11
Function
ChNo.
Description
The channel No. of a controller to which the FA transparent function is executed can be set.
Setting range
When using other than the GT155
When using the
GT155
1/2/3/4
<Default: 1>
1/2
<Default: 1>
12
11.8.2 Displaying the transparent mode
13
(
Main menu
Touch
[GOT setup]
GOT setup
Touch
[Transparent mode]
14
Transparent mode
15
Touch the channel
No. display area of ChNo.
16
11.8 Transparent Settings (Transparent Mode Setting)
11.8.1 Function of the transparent mode
11
- 29
11.8.3 Operation the transparent mode
1
1 Touching the transparent ChNo. (numerical part) on the left, the keyboard is displayed.
Input numerical value by the keyboard.
2 Touching the
OK selected setting.
button reflects the
3 Touching the the
OK
button without touching
button displays the dialog mentioned left is displayed.
4 If close the display setting and GOT setup screens with button after completing the setting of all items to change, GOT restarts and reflects the setting contents.
11
- 30
11.8 Transparent Settings (Transparent Mode Setting)
11.8.3 Operation the transparent mode
11.9 Video Unit Settings
9
11.9.1 Functions of the video unit settings
The video input signal and resolution can be selected.
Item Description
10
Video Unit Settings
The input signal and resolution can be selected.
Setting range
Input signal: NTSC, PAL
<At factory shipment: NTSC>
Resolution: 640 480,
720 480
*
<At factory shipment : 640 >
11
*: Only when PAL is selected
Input signal settings
Set the input signal as follows according to the output format for the video camera or the like connected.
If the settings made differ from these, video images may not be displayed correctly.
12
Output format for video camera or the like
NTSC format
PAL format
EIA format
CCIR format
NTSC
PAL
NTSC
PAL
Input signal setting
13
14
15
16
11.9 Video Unit Settings
11.9.1 Functions of the video unit settings
11
- 31
11.9.2 Displaying the video unit settings
Main Menu
(
Touch
[GOT setup]
Communication setting
( 10.1 Communication Setting)
GOT setup
Touch
[Video/RGB Setting]
Video/RGB setting
Touch
[Video Unit Settings]
Touch
[Video/RGB]
Video Unit Settings
Touch an item to be set
11
- 32
11.9 Video Unit Settings
11.9.2 Displaying the video unit settings
11.9.3 Operating the video unit settings
9
1 When you touch the setting item, the setting contents change.
Input signal : PAL
NTSC
Resolution : 720 480
640 480
2 When you touch the
Confirm
button, the setting contents are determined.
10
11
3 If you touch the button without touching the
Confirm
button, the dialog box on the left is displayed.
12
4 After completing the settings for all the items you want to change in [Video Unit
Settings], when closing [Video Unit
Settings] and [Video/RGB Setting]/
[Communication Setting] with the button, the GOT is restarted, and the new setting contents are reflected.
13
14
15
16
11.9 Video Unit Settings
11.9.3 Operating the video unit settings
11
- 33
11.10 Video Display Settings
11.10.1 Functions of the video display settings
The target for the video settings and the preview channel can be selected and the captive area and image quality can be set.
Item
Video Display Settings
Description
The target for the video settings and the preview channel can be selected and the captive area
(in the horizontal direction and vertical direction) and image quality (color tone, contrast, brightness, color intensity) can be set.
The captive area and image quality can be set for each channel.
Setting range
Channel 1/2/3/4
<At factory shipment : 1>
Captive area Horizontal: -100 to 100
<At factory shipment: 0>
Vertical: -100 to 100
<At factory shipment: 0>
Image Quality and Color Tone: -100 to 100
<At factory shipment: 0>
Contrast: -100 to 100
<At factory shipment: 0>
Brightness : -100 to 100
<At factory shipment: 0>
Intensity : -100 to 100
<At factory shipment: 0>
11
- 34
11.10 Video Display Settings
11.10.1 Functions of the video display settings
11.10.2 Displaying the video display settings
Main Menu
(
GOT setup
Touch
[GOT steup]
Touch
[Video/RGB Setting]
Communication Settings
( 10.1 Communication Setting)
Video/RGB Setting
Touch
[Video Display Settings]
9
10
Touch
[Video/RGB]
Video Display Settings
11
12
Touch an item to be set
13
14
15
16
11.10 Video Display Settings
11.10.2 Displaying the video display settings
11
- 35
11.10.3 Operating the video display settings
1 Select a video channel No. to be displayed.
The video image for the selected channel
No. is previewed.
2 To change the captive area or image quality, touch the display section of each item.
Captive Area : Refer to to 6 .
Image Quality : Refer to 7 to 10 .
3 The captive area (horizontal direction/ vertical direction) for the selected channel
No. can be changed.
Moves the captive area a certain distance in the direction.
Moves the captive area to the touched position.
Moves the captive area a certain distance in the direction.
Touching status.
Default
returns to the default
4 When touching the
Confirm
button, the setting contents are determined.
5 If you touch the button without touching the
Confirm
button, the dialog box on the left is displayed.
11
- 36
11.10 Video Display Settings
11.10.3 Operating the video display settings
6 After completing all the items to set, if you touch the button, the display returns to the preview screen .
9
7 The image quality (color tone, contrast, brightness, color intensity) for the selected channel No. can be changed.
10
Changes the number a certain amount in the direction.
Changes the number to the touched position.
Changes the number a certain amount in the direction.
11
Touching
Default
returns to the default status.
When touching
Copy CH1
, the image quality (color tone, contrast, brightness, color intensity) for the selected channel No. is matched with the image quality settings for Channel No. 1 (
CH1
).
8 When touching the
Confirm
button, the setting contents are determined.
12
9 If you touch the button without touching the
Confirm
button, the dialog box on the left is displayed.
13
10 After completing all the items to set, if you touch the button, the display returns to the preview screen .
11 After completing the settings for all the items you want to change in the video display settings, when closing [Video
Display (Preview)] with the button, the display returns to [Video/RGB Setting].
14
15
Precautions for setting
Incorrect settings may disrupt or stop the video image.
(If this happens, returning the settings to their default values restores normal display.
This phenomenon depends on the video camera or other device connected.
Use setting values that provide proper display.
16
11.10 Video Display Settings
11.10.3 Operating the video display settings
11
- 37
11.11 RGB Display Settings
11.11.1 Functions of the RGB display settings
The RGB clock phase and screen position can be set.
Item
RGB Display Settings
Description
The RGB clock phase
*
and screen position (horizontal direction and vertical direction) can be set.
Setting range
ClockPhase: -100 to 100
<At factory shipment: 0>
Display position Horizontal: -100 to 100
<At factory shipment: 0>
Vertical: -100 to 100
<At factory shipment: 0>
*: Adjust when a noise is displayed along the horizontal direction or characters are blotted or the contours are unclear.
11.11.2 Displaying the RGB display settings
(
Main Menu
GOT setup Video/RGB Setting
Touch
[GOT setup]
Touch
[RGB Display Settings]
Communication Settings
( 10.1 Communication Setting)
Touch
[Video/RGB Setting]
Touch
[Video/RGB]
RGB Display Settings
Touch an item to be set
11
- 38
11.11 RGB Display Settings
11.11.1 Functions of the RGB display settings
11.11.3 Operating the RGB display settings
9
1 The clock phase and screen display position (horizontal direction/vertical direction) can be changed.
10
Changes the number a certain amount in the direction.
Changes the number to the touched position.
Changes the number a certain amount in the direction.
2 When touching the
Confirm
button, the setting contents are determined.
11
3 If you touch the button without touching the
Confirm
button, the dialog box on the left is displayed.
12
13
4 After completing all the items to set, if you touch the button, the display returns to
[Video/RGB Setting].
14
Precautions for setting
If the value for [Horizontal] or [Vertical] is too large, RGB display may not be performed or the display may be disrupted or stopped.
If this happens, return the settings to their default values and make settings in the range where RGB display is possible.
15
16
11.11 RGB Display Settings
11.11.3 Operating the RGB display settings
11
- 39
12. CLOCK SETTINGS AND BATTERY
STATUS DISPLAY
(TIME SETTING AND DISPLAY)
The clock display setting items and the time when displayed the setting screen are displayed.
(While displaying clock and the seting screen, the display time does not change.)
The voltage status of the built-in battery is also displayed.
12.1 Time Setting and Display
12.1.1 Time setting and display functions
Time settings and displaying of the status of GOT built-in battery are possible.
Function Description
Clock setting
Clock display
GOT internal battery voltage status
Setup the method to adjust the time between GOT clock data and clock data of controller connected to the GOT.
Carry out the display and setup of GOT clock data.
Displays GOT internal battery voltage status.
12.1.2 Display operation of clock display and setting
Reference page
Main menu
(
Time setting & display
Touch [Time setting & display]
Set the Clock settings and Time settings
12
- 1
12.1 Time Setting and Display
12.1.1 Time setting and display functions
12.1.3 Operating the time setting & display
9
1
Clock setting
Setup the method to adjust the time between GOT data and the clock data of controller connected to the GOT.
Setting Description
Adjust the time of GOT clock data to the clock data of controller.
10
Adjust
Same as setting in [GOT setup] in [System Environment] of GT Designer2.
GT Designer2 Version Screen Design Manual (2.5 Clock Function)
Adjust the time of controller clock data to the clock data of GOT.
11
Broadcast
None
Same as setting in [GOT setup] in [System Environment] of GT Designer2.
GT Designer2 Version Screen Design Manual (2.5 Clock Function)
No adjustment of clock data.
Adjust the GOT and controllers to the controller whose clock data is used as a base.
12
Adjust/Broadcast
It is same as set in the GOT setup in System Environment of the GT Designer2.
GT Designer2 Version Screen Design Manual (2.5 Clock Function)
13
1 If touch the setup item, the setup contents is changed.
Adjust
Broadcast
None
Adjust/Broadcast
2 If touch
OK is reflected.
button, the setup contents
14
15
16
12.1 Time Setting and Display
12.1.3 Operating the time setting & display
12
- 2
3 If touch
OK
button without touching
button, the dialog mentioned left is displayed.
4 If touch button, GOT restarts. After restart, GOT operates with the changed settings.
(1) When connecting to an external device which does not have clock function
If set to [Adjust] or [Broadcast] for clock setting while the GOT is connected to external devices (PLC or microcomputers) which do not have clock function, the clock data will not be adjusted.
Refer to the following for the list of PLC installed with clock function.
GT Designer2 Version Screen Design Manual
(2.5.3 PLC CPUs with clock function)
(2) Clock setting when using the multi-channel function
The channel No. of a controller whose clock is used as a base or adjusted cannot be set by the utility.
The controller whose clock is used as a base or adjusted can be set by GT
Designer2.
For channel settings, refer to the following.
GT Designer2 Version Screen Design Manual
(2.5.1 Synchronizing clock data between GOT and PLC CPU)
(3) Setting of clock setting and battery
The battery is not installed in GOT at purchase. When select [Broadcast] or
[None] in clock setting, set the clock of the GOT once with installing the optional battery to the GOT.
(4) Operation setting by GT Designer2
Carry out the setting of clock setting in [GOT set up] in [System Environment] of
GT Designer2.
To change a part of the setting after downloading the project data, change the setting at the display setting of GOT.
GT Designer2 Version Screen Design Manual
(3.8 Setting of GOT Display and Operation (GOT Setup))
12
- 3
12.1 Time Setting and Display
12.1.3 Operating the time setting & display
2
Clock display
Carry out the display and seting of GOT clock data.
The setup methods of clock data are shown below.
9
1 If touch the clock display section, the keyboard for input is displayed and the clock update stops.
2 Input time with the keyboard by referring to the table below. Input the scheduled time when the operation of is to be carried out since the input time is reflected at the time of the operation of .
2 The day of the week is displayed automatically according to the input date.
10
11
3
0
to
9
Key Input numeric value in cursor position.
/
Key
Key Move the cursor.
Del
Key
Enter
Cancel
Key
Key
Description
Move the cursor to the left by one character when
Del
Key is touched while inputting year, month, day, time, minutes, seconds.
Carry out nothing when touched other than when inputting the above.
Close the keyboard after the input time is displayed in clock display.
The update of the clock display does not restart even if the keyboard is closed.
The update of the clock display restarts with the operation of .
Cancel the input time and returns the time of clock display to the time at which the keyboard was displayed and close the keyboard.
The update of the clock display does not restart even if the keyboard is closed.
The update of the clock display restarts with the operation of .
3 If touch
OK
button, the setting contents are reflected and the clock display update re-starts.
4 If touch button, the GOT restarts if the clock settings is changed, or the screen closes if clock settings is not changed.
If touch
OK
button without touching
button, the dialog shown left is displayed and the changed contents are cancelled and the screen is closed.
12
13
14
15
16
12.1 Time Setting and Display
12.1.3 Operating the time setting & display
12
- 4
3
GOT internal battery voltage status
Displays battery voltage status.
Display
Normal
Low/None
Status
Normal
Low voltage
When the battery voltage is low, replace the battery immediately.
Refer to the following for battery replacement procedure.
12
- 5
12.1 Time Setting and Display
12.1.3 Operating the time setting & display
13. FILE DISPLAY AND COPY
(PROGRAM/DATA CONTROL)
9
OS, project data (screen data) or alarm data which is written in the GOT or memory card can be displayed and data can be transferred between GOT and memory card.
The format of the memory card is also possible.
13.1 Data Storage Location
10
13.1.1 Drive name allocation
For the GOT built in flash memory or standard CF card, the following drive names (A drive and C drive) are allocated.
Drive name Allocation
A drive
C drive
Standard CF card
Built in flash memory
11
12
15
16
13
14
13.1 Data Storage Location
13.1.1 Drive name allocation
13
- 1
13.1.2 Data type and the storage location
1
System
The data storage location and transferring (write/read) route for each data type are shown below.
GOT main unit
BootOS
OS
Project data
Install
Download
(C drive)
Built-in flash memory
Upload
Project data
PC
GT Designer2 BootOS
OS
Install
Download
Project data
Upload
BootOS
OS
Project data
(A Drive)
Standard CF card
(when installed in GOT)
Copy files on Windows R
Project data
Write
BootOS
Project data + OS
Inserting/Removing
Standard CF card
(when installed in PC)
13
- 2
13.1 Data Storage Location
13.1.2 Data type and the storage location
9
2
At maintenance
GOT main unit
(C drive)
Built-in flash memory
Copy
Alarm
Hard copy
Copy
Alarm
Hard copy
(A Drive)
Resource data upload
Alarm
Recipe
Logging
Hard copy
PC
GT Designer2
10
11
Standard CF card
(when installed in GOT)
Alarm
Recipe
Logging
Hard copy
Copy files on Windows R
12
Inserting/Removing
Alarm
Recipe
Logging
Hard copy
Standard CF card
(when installed in PC)
13
Install, Download, Write :
Upload, Read :
The data of the build in flash memory (Project data, etc.) can be saved even if the battery voltage becomes low.
OS
Item
BootOS
Project data
Alarm
Data type
BootOS
Standard monitor OS
PLC communication driver
Extended function OS
Option OS
Project data
(Including recipe setting, alarm conditions, time action, and GOT setup.)
Alarm data
(Extended alarm log file and alarm log file)
Recipe data (Advanced recipe file, Recipe file)
Storage location
Built in flash memory (C drive)
Standard CF card (A drive) orbuilt in flash memory (C drive)
*1
Recipe
Standard CF card (A drive)
Logging
Logging (Logging file)
*1
Hard copy
Image file (Hard copy function)
When use the project data stored in the standard CF card (A drive) with GOT, use the project data with the CF card installed to
GOT.
14
15
16
13.1 Data Storage Location
13.1.2 Data type and the storage location
13
- 3
13.1.3 OS version confirmation
Confirm the OS version carefully when install BootOS and standard monitor OS.
When OS is installed, GOT checks and compares the OS version automatically.
(1) When install BootOS
When the BootOS to be installed has the older major version, GOT displays the installation disapproving message to cancel the installtion so that the older version may not be written.
(Even when the version of the BootOS to be installed has the same or later version, the version information and the dialog for selecting continue/not continue will be displayed.)
When installing from the standard CF card, the dialog is displayed by the main unit.
When installing from GT Designer2 via USB or RS-232, the dialog is displayed by the GT
Designer2.
(2) When install standard monitor OS, communication driver, option OS
When standard monitor OS, communication driver, or option OS has already been installed, the version information of the OS which has been installed and the dialog for selecting continue/not continue will be displayed.
Moreover, when the different versions will coexist amoung all OSs (standard monitor OS, communication driver, and option OS) by installing OS, the installation disapproving dialog will be displayed and the installation process is canceled.
(3) When download project data
GOT automatically compares the version between the project data to be downloaded and the installed OS.
When the versions are different, the dialog confirming whether to install the OS together is displayed.
When downloading the project data from the memory card, storing the project data and OS beforehand is recommended.
The version of each OS installed in the GOT can be confirmed by [Property] of [OS information] screen.
Explanation of OS version
01.00.00A
BootOS version
Appears only when the property of the BootOS is displayed.
Minor version
Major version
Refer to the following for details of the screen display operation.
13
- 4
13.1 Data Storage Location
13.1.3 OS version confirmation
9
Version confirmation of BootOS by rating plate
Confirm the version of BootOS installed in the GOT at product shipment by rating plate of GOT rear face.
GRAPHIC OPERATION TERMINAL
MODEL GT1575-VTBA
IN 100V to 240V AC 50/60 Hz
POWER MAX 90VA
SERIAL 00004701 AA00001-A
MITSUBISHI ELECTRIC MADE IN JAPAN
BACKLIGHT GT15-70VLTT
A A
BootOS version
10
11
12
13
14
15
16
13.1 Data Storage Location
13.1.3 OS version confirmation
13
- 5
13.1.4 Capacity confirmation of the project data downloading location
When download the project data, confirm the capacity of the user area in the drive to which transferred, the transferred project data size, the transfer size and buffering area size of the optional function OS in advance to judge whether to carry out the download.
The capacities can be confirmed by GT Designer2.
Refer to the following for details.
GT Designer2 Version Basic Operation/Data Transfer Manual
(8.1.2 Drive capacity required for data transfer)
13
- 6
13.1 Data Storage Location
13.1.4 Capacity confirmation of the project data downloading location
13.1.5 Display file
The display screen and storage destination for each type of data are shown below.
The file name and contents of each data can be displayed with property display of the utility.
BootOS
Item Display screen
Storage destination
(Drive name/folder name)
Standard CF card A:\G1BOOT\ *2 or
Built-in flash memory C:\G1BOOT\ *2
Standard monitor
OS
Standard monitor OS system screen data
Standard monitor OS system screen management information file
Standard monitor OS (monitor function)
6 8-dot font (ASCII characters)
24-dot numerical HQ font
32-dot numerical HQ font
TrueType numerical font
12-dot standard font
16-dot standard font
OS information screen
Standard CF card A:\G1SYS\
*2 or
Built-in flash memory C:\G1SYS\
*2
Extended function OS
Option OS
Communication driver
Project data
*1
Resource data
User-created screen data
Comment data
12-dot HQ fonts (Mincho/Gothic)
16-dot HQ fonts (Mincho/Gothic)
TrueType (Mincho/Gothic)
Advanced alarm log file CSV file *4
Advanced alarm log file TXT file *4
Advanced alarm log file binary file
*4
Alarm log file CSV file
*4
Hard copy file BMP file *4
Hard copy file JPG file *4
Advanced recipe file CSV file
Advanced recipe file TXT file
*4
*4
Advanced recipe file binary file *4
Project information screen
Alarm information screen
Hard copy
information screen
Advanced recipe information screen
Standard CF card A:\PROJECT1\ or
Standard CF card A:\
*2*3
Built-in flash memory C:\PROJECT1\
*2*3
With GT Designer2, any folder name or file name can be specified.
*2
Operation log file CSV file
*4
Operation log file TXT file
*4
Operation log file binary file *4
Operation log information screen
*1 The user-created screen data, comment data, and font data are displayed as project data.
*2 Each folder is created automatically when a file is installed, downloaded, or uploaded.
*3 The folder names and file names can be set at [System Settings] in [System Environment] of GT Designer2 .
GT Designer2 Version Screen Design Manual (3.1 GOT/Controller Type Setting)
*4 A serial number is automatically added to file names.
9
10
11
12
13
14
15
16
13.1 Data Storage Location
13.1.5 Display file
13
- 7
13.2 OS Information
13.2.1 Function of OS information
Each file name/folder name of BootOS and OS (Standard monitor OS, communication driver and optional function OS) by which each drive (A: Standard CF card, C: Built-in flash memory) holds can be displayed in lists.
Installation and uploading of the files are also possible.
Function Description
Information display of files and folders Displays the kind, name, data size, creation date and time of the file or folder.
Install
Upload
Property display
Data check
All OS files written in the A drive (Standard CF card) can be installed in the C drive
(Built in flash memory).
All OS files in the C drive (Built in flash memory) can be uploaded to the A drive
(Standard CF card).
Displays the property (file name, data size, type, version and creation date) of the file.
Data check of files is possible.
Reference page
13.2.2 Display operation of OS information
Main menu
(
Program/Data control
Touch
[Program/Data control]
Touch [OS information]
OS information
Operate BootOS and OS file.
13
- 8
13.2 OS Information
13.2.1 Function of OS information
13.2.3 Display example of OS information
9
10
(1)
(7)
(2) (3)
(4)
(5) (6)
(8) (9)
11
Number
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Item
Select drive
Kind
Name
Path name
Size
Date and time
The size of drive
Description
The target drive which displays file or folder can be selected.
When the CF card is not installed, [A: Built-in CF Card] is not displayed.
Indicates whether the displayed name is for file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
The file name or folder name which is stored in the selected drive or folder is displayed.
When the file name or folder name exceeds 20 characters, the exceeding characters (the 21th character or after) are not displayed.
The path name of the currently displayed drive/folder is displayed.
Displays the size of the file displayed in Name.
The date and time when each file was created are displayed.
Displays the size in use and the entire size of the drive which is selected by drive selection.(Only the size in use is displayed when selecting the C drive.)
Execution switch of each function.
Operation switch
Number of folders and files
Displays the total number of the displayed files and folders.
12
13
14
15
Remark Displayed folders and files
For the folders and files displayed, refer to the following.
16
13.2 OS Information
13.2.3 Display example of OS information
13
- 9
13.2.4 Operation of OS information
1
Display operation of OS information
1 If touch a drive in [Select drive], the information of the first folder of the touched drive is displayed.
2 If touch a folder name, the information of the touched folder is displayed.
3 If touch a folder name of ". .", the information of the folder in one higher hierarchy is displayed.
4 If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5 If touch a file name, the touched file name is selected and inverted.
6 Refer to the following for operation of installation, upload, property, data check.
Installation ..............
Upload....................
Property..................
Data check ............
this section
this section
this section
this section
7 Touching button closes the screen.
13
- 10
13.2 OS Information
13.2.4 Operation of OS information
9
2
Installation operation
BootOS and OS which are written in the A drive (Standard CF card) can be installed in GOT.
1 Install the CF card to which the BootOS or
OS to install is written to the GOT.
Refer to the following for inserting/ removing method of CF card.
2 Touch [A: Built-in CF Card] for drive selection.
3 Touching
Install
button starts the install.
10
11
12
4 When the installation is completed, the dialog shown left is displayed.
5 GOT restarts if touch
OK
button.
13
14
15
16
13.2 OS Information
13.2.4 Operation of OS information
13
- 11
3
Upload operation
BootOS and OS in the C drive (Built in flash memory) can be uploaded to the A drive (Standard CF card).
The CF card after uploading can be used for installing the OS on another GOT.
18. INSTALLATION OF COREOS, BOOTOS AND STANDARD MONITOR OS.
1 Install the CF card used as the uploading destination to GOT.Refer to the following for inserting/removing method of CF card.
2 Touch [A: Built-in CF Card] of [Select drive].
3 Touching
Upload
starts the uploading.
4 When the upload is completed, the dialog shown left is displayed.
Touching
OK
closes the dialog.
13
- 12
13.2 OS Information
13.2.4 Operation of OS information
9
4
Property display operation
Displays the property of the file stored in the selected folder.
1 If touch
Property
button after selecting the property displaying target folder, the
Property display shown left is displayed.
In Property display, the following information is displayed for each file selected by .
Item
Name
Size
Description
Displays the file name.
Displays the file size.
Type
Displays the following items according to the file type.
Boot
Basic
: BootOS
: Standard monitor OS
Extend
Option
Comm.
: Extended function OS
: Optional function OS
: Communication driver
Version Displays the version of BootOS and OS.
Date and time
Displays the date and time of the file creation.
2 If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
3 Touching button returns the screen to the previous screen display.
10
11
12
13
14
15
16
13.2 OS Information
13.2.4 Operation of OS information
13
- 13
5
Data check operation
Carries out data check of the selected system file.
Dialog at data check normal 1 Touch
Data check
button after selecting a data check target file.
The dialog mentioned left will be displayed after executing data check.
2 Touching
OK
button closes the dialog.
Dialog at data check abnormal
13
- 14
13.2 OS Information
13.2.4 Operation of OS information
13.3 Project Information
13.3.1 Functions of the project information
The project data files stored in each drive (A: standard CF card, C: built in flash memory) can be displayed by lists.
In addition, the files can be downloaded, uploaded, deleted or copied, etc.
Function Description Reference page
Information display of files and folders Displays the kind, name, data size, the creation date and time of the file or folder.
Delete
Copy
Property display
Data check
Deletes project data.
Copies project data. (Enabled to copy only from the A drive to the A drive)
Displays the project data creation date, author name and the version of GT
Designer2.
Data check of the file can be executed.
Download
Setup
Upload
Setup cancel
Downloads the project data written in the A drive (Standard CF card) to C drive
(Built in flash memory).
The project data to be displayed can be selected.
Uploads the project data written in the C drive (Built in flash memory) to the A drive
(Standard CF card).
Cancels the item which is selected for the project data to be displayed.
13.3.2 Display operation of project information
9
10
11
12
13
Main menu
(
Program/Data control
Touch
[Program/Data control]
Touch
[Project information]
14
Project Information
15
Operate Project data file.
16
13.3 Project Information
13.3.1 Functions of the project information
13
- 15
13.3.3 Display example of project information
(1)
(6)
(2) (3) (4) (5)
(7) (8)
Number
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Name
Item
Select drive
Path name
Size
Date and time
The size of drive
Operation switch
Description
The drive by which a file or folder is displayed can be selected.
When the CF card is not connected, [A: Built-in CF card] is not displayed.
The project data (Project Folder) in the selected drive is displayed.
When the name exceeds 18 characters, the 19th and later characters are not displayed.
The project data being monitored on the GOT is preceded by "*%".
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
Displays the date and time when each file is installed.
Displays the size in use and the entire size of the drive which is selected by drive selection. (Only the size in use is displayed when selecting the C drive.)
Displays the execution switch of functions (download, upload, etc.) which can be carried out in [Project information].
Number of folders and files
Displays the total number of the displayed files and folders.
Remark Displayed folders and files
For the folders and files displayed, refer to the following.
13
- 16
13.3 Project Information
13.3.3 Display example of project information
13.3.4 Operation of project information
1
Display operation of project information
2
Delete operation
This operation deletes the selected file.
9
1 Touch the drive in Select drive. The project data in that drive will be displayed.
2 Touch the project data. It is then selected and highlighted.
3 Refer to the following for operation of delete, copy, property, data check, download, upload.
Delete.....................
this section
Copy.......................
this section
Property .................
this section
Data check .............
Download, setup
this section
this section ...............................
Upload, setup cancel
...............................
this section
4 Touching button closes the screen.
10
11
12
13
1 Touch and select the file to delete.
2 Screen mentioned left is displayed if
Delete
button is touched.
Confirm the deletion targeted file is specified correctly.
If touch
If touch canceled.
OK
button, the file is deleted.
Cancel
button, the deletion is
14
15
3 When the deletion completes, the dialog box shown left is displayed.
If touch
OK
button, the dialog is closed.
16
13.3 Project Information
13.3.4 Operation of project information
13
- 17
3
Copy operation
The file in the A drive is copied to another directory of the A drive.
Copy to/from C drive is disabled.
1 Install CF card in the PC, in which create a folder for the copy destination.
Set the same character with [System
Setting] of [System Environment] of GT
Designer2 for the folder name.
GT Designer2 Version Screen
Design Manual
(3.1 GOT/Controller Type Setting)
2 Install the CF card mentioned above to
GOT.
Refer to the following for inserting/ removing method of CF card.
3 Open [Project Information] screen to select the file to copy.
4 If touch
Copy
button, the message
[Please select a destination.] is displayed in the left bottom of the screen.
5 If the copy destination folder is touched, the screen display is changed to the folder of copy destination.
At this time, it cannot be copied into the same folder where the file exists.
Select other folders.
6 If touch
Next
button, the dialog mentioned left is displayed.
13
- 18
13.3 Project Information
13.3.4 Operation of project information
7 Touch
If there is no file of the same name in the copy destination folder, starts to copy.
When there is a file of the same name in the copy destination folder, the dialog mentioned left is displayed without starting the copy.
If copy, in this case, the copied file is overwritten to the project data in the copy destination folder.
If touch
OK
button, starts to copy.
If touch
Cancel
button, cancels to copy.
8 When copying completes, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
9
10
11
12
4
Property display operation
Displays the property of the project data in the selected folder.
1 If touch
Property
button after selecting the project data to display the property, the property is displayed as shown left.
In property display, the following information is displayed.
Item
Date
Author
Drawing
S/W version
Description
Displays the creation date of the file.
Displays the author of the project data.
Displays name and version of the drawing software by which the project data is created.
2 If touch button, the screen scrolls up/down line by line.
3 If touch button, the screen scrolls up/down by one screen.
4 If touch button, the property display is closed and returned to the previous screen.
13
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13
- 19
5
Data check operation
Carrys out data check of the selected project file.
Dialog at data check normal 1 Touch the
Data check
button after selecting the file for data check.
The data check is executed and the result is displayed by the dialog shown left.
2 If touch
OK
button, the dialog is closed.
Dialog at data check abnormal
13
- 20
13.3 Project Information
13.3.4 Operation of project information
9
6
Download operation/setup operation
(1) Download operation
Transfers the project data stored in the A drive (Standard CF Card) to the C drive (Built in flash memory). (The GOT monitors using the data in the C drive.)
Before download operation
(1) Setup cancel
When the project data in the A drive is set up, the project data cannot be downloaded to the C drive.
Execute setup cancel ( (2) Setup cancel) before downloading the project data.
(2) Project data to be stored in a CF card
When storing the project data from GT Designer2 to CF card, select [C: Built-in flash memory] for [Project Data] in the [Boot Drive].
10
11
12
(Continued to next page)
13
1 Install a CF card in the GOT
Refer to the following for inserting/ removing method of CF card.
2 Touch [A: Standard CF Card] in Select drive
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13
- 21
.
3 If touch the
Download
button, the dialog mentioned left is displayed.
Touching the downloading.
OK
button executes
4 If any project data with the same name exists in the C drive, the screen shown left is displayed without starting downloading.
In this case, the project data of the C drive is overwritten with the project data of the A drive when downloaded.
Touching the downloading.
Cancel
button cancels the
5 When the downloading is completed, the dialog mentioned left is displayed.
Touching the
GOT.
OK
button restarts the
13
- 22
13.3 Project Information
13.3.4 Operation of project information
(2) Setup operation
Sets the project data stored in the A drive (Standard CF Card) to be used in the GOT.
(The GOT monitors using the data in the A drive.))
Before setup operation
When storing project data from GT Designer2 to CF card, select [A: Standard CF
Card] for [Project Data] in [Boot Drive].
9
10
11
1 Install a CF card in the GOT.
For how to install a CF card, refer to the following.
2 Touch [A: Standard CF Card] in Select drive.
12
13
3 If touch the
Download
button, the dialog mentioned left is displayed.
If touch executed.
OK
button, the setup is
14
15
6 When the setup is completed, the dialog mentioned left is displayed.
Touching the
GOT.
OK
button restarts the
16
13.3 Project Information
13.3.4 Operation of project information
13
- 23
7
Upload/setup cancel operation
(1) Upload operation
By upload operation, the project data is transferred from the C drive (Built in flash memory) to the A drive (Standard CF Card).
The CF card after uploading can be used for downloading project data to another GOT.
Before setup operation
The project data cannot be uploaded to the A drive when the project data of the A drive is set up.
Execute setup cancel ( project data.
(2) Setup cancel operation) before uploading the
1 TTouch [A: Standard CF Card] in Select drive.
2 If touch the
Upload
button, the screen mentioned left is displayed.
3 Touching the uploading.
OK
button executes
4 If any project data with the same name exists in the A drive, the screen shown left is displayed without starting uploading.
In this case, touching the
OK
button overwrites the project data of the A drive with the project data with the same name of the A drive.
Touching the
Cancel uploading.
button cancels
5 When the uploading is completed, the dialog mentioned left is displayed.
Touching the
GOT.
OK
button restarts the
13
- 24
13.3 Project Information
13.3.4 Operation of project information
(2) Setup cancel operation
By setup cancel, setup is canceled.
.
9
1 Touch [A: Standard CF Card] in Select drive.
2 If touch the
Upload
button, the screen mentioned left is displayed.
3 If touch the executed.
OK
button, setup cancel is
10
11
4 When the setup cancel is completed, the dialog mentioned left is displayed.
Touching the
GOT.
OK
button restarts the
After restart, the GOT monitors with the project data in the C drive.
12
13
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13
- 25
13.4 Alarm Information
13.4.1 Function of alarm information
The extended alarm log file or alarm log file held by each drive (A: Built-in CF card, C: Flash Memory) is displayed.
The functions below can be carried out for files.
For details of Advanced Alarm, refer to the following manual.
GT Designer2 Version Screen Design Manual (8 ALARM)
Function Description
Information display of files and folders Displays name, data size, creation date and time of file or folder.
G1A CSV conversion Converts the G1A file of advanced alarm log file to CSV file.
G1A TXT conversion
Deletion
Converts the G1A file of advanced alarm log file to TXT file.
Deletes file.
Copy
Graph
Copys file.
Displays the advanced alarm watch result by historical graph or tally graph.
Reference page
13.4.2 The display operation of alarm information
(
Main menu
Program/Data control
Touch
[Program/Data control]
Touch
[Alarm information]
Alarm information
Operate Extended alarm log file or Alarm log file.
13
- 26
13.4 Alarm Information
13.4.1 Function of alarm information
13.4.3 The display example of alarm information
9
10
(1)
(7)
(2) (3)
(4)
(5)
(6)
(8) (9)
11
Number
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Item
Select drive
Kind
Name
Path name
Size
Date and time
The size of drive
Description
The drive which displays file or folder can be selected.
When CF card is not installed, [A: Built-in CF card] is not displayed.
Indicates whether the displayed name is file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
Displays the file name or folder name.
For the long file/folder name, entire part may not be displayed.
Confirm the nondisplayed part with the
Copy
button, etc.
(
After confirmation, touch the
Cancel
button to cancel the operation.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
The date and time when each file was created are displayed.
Displays the size in use and the entire size of the drive which is selected by drive selection. (Only the size in use is displayed when selecting the C drive.)
Execution switch of each function.
Operation switch
Number of folders and files
Displays the total number of the displayed files and folders.
12
13
14
13
- 27
15
Display of creation date and time
The creation date and time display is not updated even if a file is created or updated while displaying the alarm information display screen.
If close the screen currently displayed (moving the screen to the folder of the upper hierarchy, etc.) and display the screen again, the updated contents are displayed.
16
Remark Folders and files displayed
For the folders and files displayed, refer to the following.
13.4 Alarm Information
13.4.3 The display example of alarm information
13.4.4 Alarm information operation
1
The display operation of alarm information
1 If touch a drive of select drive, the information of the touched drive is displayed.
2 If touch a folder name, the information of the touched folder is displayed.
3 If touch a folder of ". .", the information of the folder of the one upper hierarchy is displayed.
4 If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5 If touch a file name, the file is selected.
6 Refer to the following for G1A CSV,
G1A TXT, delete, copy, graph operations.
G1A CSV ,
this section
this section
Delete.....................
Copy.......................
Graph .....................
this section
this section
7 If touch button, the screen is closed.
13
- 28
13.4 Alarm Information
13.4.4 Alarm information operation
9
2
G1A CSV conversion operation, G1A TXT conversion operation
The selected G1A file is converted to CSV file or TXT file.
1 Touch and select the G1A file which is to be converted to CSV file or TXT file.
2 The following dialogue is displayed when touching the following button according to the file type to convert to.
• CVS file:
G1A->CSV
Button
• TXT file :
T X T->CSV
Button
10
11
(Example: Dialogue when button is touched)
G1A->CSV
3 Touch
When the file, whose name is the same, exists in the destination folder, the dialog showed at left appears without starting the conversion.
If touch the file.
OK
button, overwrites the
If touch
Cancel conversion.
button, cancels the
4 The message of completion is displayed in dialogue when conversion is completed.
If touch
OK
button, the dialog is closed.
12
13
14
15
16
13.4 Alarm Information
13.4.4 Alarm information operation
13
- 29
3
Deletion operation
Deletes selected files.
1 Touch and select the file to delete.
2 If touch
Del
button, the dialog mentioned left is displayed.
If touch
If touch canceled.
OK
button, the file is deleted.
Cancel
button, the deletion is
3 When the deletion is completed, the completion dialog is displayed.
If touch
OK
button, the dialog is closed.
13
- 30
13.4 Alarm Information
13.4.4 Alarm information operation
4
Copy operation
Copies the selected file.
9
1 Touch and select the file to copy.
2 If touch
Copy
button, the message
[Please select a destination.] is displayed in the left bottom of the screen.
3 If the copy destination folder is touched, the screen display is changed to the folder of copy destination.
At this time, it cannot be copied into the same folder where the file exists.
Select other folders.
10
11
4 If touch
Next
button, the following dialog shown left is displayed.
12
13
5 Touch
If there is a file of the same name in the copy destination folder, the following dialog is displayed without starting the copy.
If touch the file.
OK
button, overwrites the
If touch
Cancel
button, cancels to copy.
14
6 When the copy is completed, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
15
16
13.4 Alarm Information
13.4.4 Alarm information operation
13
- 31
5
Graph operation
Displays the selected extended alarm log file in a graph.
When the extended alarm watch (advanced user alarm, advanced system alarm) is set in history mode, the selected extended alarm log file is displayed in historical graph (
(1) Historical graph display).
When set in accumulation mode, displayed it in tally graph (
Refer to the following for details related to setting of the extended alarm watch.
GT Designer2 Version Screen Design Manual (8 ALARM)
1
1 Touch and select the G1A file to display in a graph.
2 If touch
Graph
button, displays the historical graph or tally graph according to the setting of the extended alarm watch.
2
3 When move a graph, operate as follows.
• If touch / button, moves the graph up/down line by line.
• If touch / button, moves the graph up/down by one screen.
• If touch / button, moves the graph to left/right by one column.
• If touch / button, moves the graph to left/right by one screen.
4 If touch button, closes the graph.
(Example: Historical graph)
13
- 32
13.4 Alarm Information
13.4.4 Alarm information operation
(1) Historical graph display
• Displays the generated time ( ), confirmed time ( ) and restored ( ) time of each alarm.
• Displays the time scales by 30 minutes interval in the bottom of the graph.
• The alarms generated in the order of registering alarm are displayed.
• By the name of each alarm, the contents set for the message of the general alarms by GT Designer2 are displayed with up to 12 characters of full-size character (up to 24 half-size characters).
The 13th of full-size character and after (the 25th and after for half-size character) are not displayed.
• The graph displays the alarm within up to 26 lines in one screen.
11
12
(2) Tally graph display
13
14
• Displays the generated frequency of each alarm by the sideways bar chart.
• By the name of each alarm, the contents set for the message of the general alarms by GT Designer2 are displayed with up to 12 characters of full-size character (up to 24 half-size characters).
The 13th of full-size character and after (the 25th and after for half-size character) are not displayed.
• The graph displays the alarm within up to 26 lines in one screen.
15
16
13.4 Alarm Information
13.4.4 Alarm information operation
13
- 33
9
10
13.5 Hard Copy Information
13.5.1 The function of hardcopy information
Carries out delete, copy and move to the file created by the hardcopy function.
Refer to the following manual for details of hard copy function.
GT Designer2 Version Screen Design Manual (13.2 Hard Copy)
Function Description
Information display of files and folders Displays the kind, name, data size, creation date and time of the file or folder.
Delete Deletes the file.
Copy Copies the file.
13.5.2 The display operation of hardcopy information
Reference page
(
Main menu
Program/Data control
Touch [Program/Data control]
Touch [Hard copy information]
Hard copy information
Operate the Hard copy file
13
- 34
13.5 Hard Copy Information
13.5.1 The function of hardcopy information
13.5.3 Display exmaple of hardcopy information
9
10
(1)
(7)
(2) (3)
(4)
(5)
(6)
(8) (9)
11
Number
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Item
Select drive
Kind
Name
Path name
Size
Date and time
The size of drive
Description
The drive which displays file or folder can be selected.
When CF card is not installed, [A: standard CF Card] is not displayed.
Indicates whether the displayed name is file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
Displays the file name or folder name.
For the long file/folder name, entire part may not be displayed.
Confirm the nondisplayed part with the
Copy
button, etc.
(
After confirmation, touch the
Cancel
button to cancel the operation.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
Displays the creation date and time of each file.
Displays the size in use and the entire size of the drive which is selected by drive selection. (Only the size in use is displayed when selecting the C drive.)
Execution switch of each function.
Operation switch
Number of folders and files
Displays the total number of the files and folders displayed.
12
13
14
13
- 35
15
Display of the creation date and time
The creation date and time display is not updated even if a file is created or updated while displaying the hardcopy information.
To display the updated creation date and time, close the screen currently displayed
(by moving to the upper hierarchy folder, etc.) and display the screen again.
16
Remark Displayed folders and files
For the folders and files displayed, refer to the following.
13.5 Hard Copy Information
13.5.3 Display exmaple of hardcopy information
13.5.4 The operation of hardcopy information
1
Display operation of hardcopy information
1 If touch a drive of select drive, the information of the touched drive is displayed.
2 If touch a folder name, the information in the touched folder is displayed.
3 If touch a name of the folder of ". .", the information in the folder of one higher hierarchy is displayed.
4 If touch button of the scrollbar, scrolls up/down line by line.
If touch button, the screen scrolls up/down by one screen.
5 If touch a file name, the file is selected.
6 Refer to the following for the operation of delete and copy.
Delete.....................
Copy.......................
this section
this section
7 If touch button, closes the screen.
13
- 36
13.5 Hard Copy Information
13.5.4 The operation of hardcopy information
2
Delete operation
Deletes the selected file.
9
1 Touch and select the file to delete.
2 If touch
Del
button, the screen mentioned left is displayed.
If touch
If touch deletion.
OK
button, deletes the file.
Cancel
button, cancel the
10
11
3 When the deletion is completed, the completion dialog is displayed.
If touch
OK
button, the dialog is closed.
12
13
14
15
16
13.5 Hard Copy Information
13.5.4 The operation of hardcopy information
13
- 37
3
Copy operation
Copies the selected file.
1
2
1 Touch and select the file to copy.
2 If touch
Copy
button, the dialog [Please select a destination.] is displayed in the left bottom of the screen.
3 If touch the folder of the copy destination, the screen display is changed to the folder of copy destination.
The copied file cannot be copied to its own folder.Select the different folder.
4 If touch
Next
button, the dialog box shown left is displayed.
5 Touch
If there is a file of the same name in the copy destination folder, the screen shown left is displayed without starting to copy.
If touch the
OK
button, overwrites the file.
If touch
Cancel
button, cancels to copy.
6 When the copy is completed, the dialog of completion is displayed.
If touch
OK
button, the dialog is closed.
13
- 38
13.5 Hard Copy Information
13.5.4 The operation of hardcopy information
13.6 Memory Card Format
13.6.1 Function of the memory card format
Formats the memory card.
13.6.2 Display operation of memory card format
(
Main menu
Program/Data control
Touch [Program/Data control]
Memory card format
Select the drive and format.
Touch [Memory card format]
13.6 Memory Card Format
13.6.1 Function of the memory card format
13
- 39
15
16
13
14
11
12
9
10
13.6.3 Operating the memory card format
1 Install the memory card to GOT.
Refer to the following for inserting/ removing method of memory card.
2 Touch and select the drive to format by drive selection.
3 If touch
Format
button, the password input screen is displayed.
4 Type touch key. The dialog box shown on the left will appear. (The password is fixed to 1111.)
Confirm the contents of the dialog.
When execute the memory card format,
When cancel the memory card format,
5 If touch
OK
button by , the dialog mentioned left is displayed for reconfirm.
6 Reconfirm whether to format the memory card.
If touch
If touch
OK formatting.
button, starts formatting.
Cancel
button, cancels
13
- 40
13.6 Memory Card Format
13.6.3 Operating the memory card format
7 When the formatting is completed, the completion dialog mentioned left is displayed.
8 If touch
OK
button, closes the dialog.
9
10
Remark Restrictions on formatting
• When use an unformatted memory card in GOT, format the memory card by PC.
GOT cannot format the unformatted memory card.
• The formatting of GOT does not change the file system (Example: FAT16) of the memory card and inherits the file system before formatting.
11
12
13
14
15
16
13.6 Memory Card Format
13.6.3 Operating the memory card format
13
- 41
13.7 Advanced Recipe Information
Before using advanced recipe information
For writing/reading into/from a controller with this function or editing of advanced recipe file on the personal computer, refer to the following manual.
Specifications and operating procedure are described.
GT Designer2 Version Screen Design Manual
(13.1 Advanced Recipe Function)
13.7.1 Function of advanced recipe information
For the advanced recipe file used in advanced recipe function, copy/delete/file output are available.
In addition, it is possible to writing/reading into/from a controller by using this function, without creating the screen to operate the advanced recipe. (Advanced recipe setting of GT Designer2 is required.)
Description Refer to Function
Displaying file, folder data
The file/folder name, data size and creating date & time are displayed.
G1P file of advanced recipe file is converted to CSV file.
conversion
Advanced
Recipe
Information screen conversion
Del
Copy
Move
Rename
Create Folder
Create G1P
Load record
G1P file of advanced recipe file is converted to Unicode text file.
File or folder is deleted.
File is copied.
File is moved.
File name is changed.
New folder is created.
New G1P file of advanced recipe file is created.
Selected record value is loaded in the device of controller.
Advanced
Recipe
Record List screen
Save record
Match records
Delete Device
Value
The device of controller is saved in selected record.
Selected record is verified to the device value of controller.
The device value contained in selected record is deleted.
13
- 42
13.7 Advanced Recipe Information
13.7.1 Function of advanced recipe information
13.7.2 Operation of advanced recipe information display
(
Main menu
Program/Data control
Touch [Program/Data control]
Touch [Advanced
Recipe Information]
[Advanced Recipe Information]
Operate advanced recipe file.
13.7 Advanced Recipe Information
13.7.2 Operation of advanced recipe information display
13
- 43
15
16
13
14
11
12
9
10
13.7.3 Example of advanced recipe information display
1
Advanced recipe information screen
(1)
(7)
(2) (3) (4) (5) (6)
(8) (9)
(4)
(5)
(6)
(7)
(8)
(9)
Number
(1) Drive
(2) Kind
(3) Name
Item
Path name
Size
Creating date & time
Drive size
Operation switch
Number of folders and files
Description
[A: Built-in CF card] is displayed. (Even if CF card is not installed, this message appears.)
Indicates whether the displayed name is file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
Displays the file name or folder name.
For the long file/folder name, entire part may not be displayed.
(
Confirm the nondisplayed part with the Rename button, etc.
After confirmation, touch the Cancel button to cancel the operation.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
The date and time when each file was created are displayed.
Displays the used/entire size of drive selected by select drive.
Execution switch of each function.
Displays the total number of the displayed files and folders.
About the displayed file
The files other than that for advanced recipe are not displayed on the advanced recipe information screen.
Remark Folders and files displayed
For the folders and files displayed, refer to the following.
13
- 44
13.7 Advanced Recipe Information
13.7.3 Example of advanced recipe information display
2
Advanced recipe record list screen
Touching the
Excute
button on the advanced recipe information screen after selecting the advanced recipe file, this screen appears.
Records selected in each advanced recipe file can be displayed or saved/loaded.
9
10
(1) (2) (3) (4) (5)
(6)
Number
(1)
(2)
No.
Attr
Item
(3)
(4)
(5)
(6)
Record Comment
File Name
Setting No.
Name
Date and time
Operating switch
Description
Record No. of advanced recipe file is displayed.
Attribution of record is displayed.
Attribution of record can be changed with GT Designer2.
V : Record can be loaded/saved
(Record whose value is selected.)
VP : Record only for loading
(Record whose value is selected and cannot be changed.)
Blanc : Record only for saving
(Record whose value is deleted or not selected.)
P : Record unusable (reserved area)
(Record whose value is not selected and cannot be changed.)
Record Comment is displayed.
Path and name of recipe file are displayed.
Recipe No. is displayed.
Recipe name is displayed.
Date and time when record comment is updated are displayed.
Execution switch of each function.
11
12
13
14
15
16
13.7 Advanced Recipe Information
13.7.3 Example of advanced recipe information display
13
- 45
13.7.4 Advanced recipe information operation
1
Display operation of advanced recipe information
1 If touch a drive of select drive, the information of the touched drive is displayed.
2 If touch a folder name, the information of the touched folder is displayed.
3 If touch a folder of ". .", the information of the folder of the one upper hierarchy is displayed.
4 If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5 If touch a file name, the file is selected.
6 For operation of operating switches, refer to the following.
this section
Delete ................
Copy ..................
Move ..................
Rename .............
this section
this section
this section
this section
Create Folder.....
Create G1P........
Execute....
this section
this section 8
this section 9 to 12
7 If touch button, the screen is closed.
13
- 46
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
9
2
G1P CSV conversion operation, G1P TXT conversion operation
Advanced recipe file (G1P file) is converted to CSV file or Unicode text file that can be displayed/edited on personal computer.
1 Touch and select the G1P file which is to be converted to CSV file or Unidcode text file.
2 Touch the following button in accordance with destination file type.
• CSV file :
G1P->CSV
button
• Unicode text file :
G1P->TXT
button
10
11
3 Select the target folder.
(Selecting a folder is not needed for outputting directly below the drive.)
12
(Example: Dialog if the G1P->CSV button is touched.)
(Continued to next page)
13
4 If touch the
Excute
button, the dialog shown left is displayed.
Touch the
OK
button.
(While executing, "Processing..." message appears on the screen.)
14
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 47
13
- 48
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
5 When the file, whose name is the same, exists in the destination folder, the dialog shown left appears without starting the conversion. If touch the
OK
button, overwrites the file.
If touch
Cancel
button, cancels the conversion.
6 The message of completion is displayed in dialogue when conversion is completed.
If touch
OK closed.
button, the dialog is
3
Delete operation
Folder and file to be used on advanced recipe are deleted.
1 Touch and select the file/folder to delete.
9
10
11
2 If touch
Del
button, the dialog mentioned left is displayed.
If touch deleted.
OK
button, the file/folder is
(While executing, "Processing..." message appears on the screen.)
If touch
Cancel
button, the deletion is canceled.
12
13
3 When the deletion is completed, the completion dialog is displayed.
If touch closed.
OK
button, the dialog is
14
4 When it cannot be deleted, the dialog showed at left appears. (Only when deleting folder is executed.)
5 Verify that there is no file in the folder and execute the delete operation again.
(
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 49
4
Copy operation
Folder to be used in advanced recipe is copied.
1 Touch and select the file to copy.
2 Touch the
Copy
button.
13
- 50
(Continued to next page)
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
3 Select the target folder.
(Selecting a folder is not needed for outputting directly below the drive.)
At this time, it cannot be copied into the same folder where the file exists.
Select other folders.
4 If touch
Excute
button, the following dialog shown left is displayed.
(While executing, "Processing..." message appears on the screen.)
5 If there is a file of the same name in the copy destination folder, the following dialog is displayed without starting the copy.
If touch the file.
OK
If touch
Cancel
button, overwrites the
button, cancels to copy.
6 When the copy is completed, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
9
10
5
Move operation
Files to be used in advanced recipe are moved.
11
1 Select the file to be moved by touching it.
2 Touch the
Move
button.
12
3 Select the target folder.
(Selecting a folder is not needed for moving directly below the drive.)
13
14
(Continued to next page)
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 51
13
- 52
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
4 If touch the
Execute
button, the dialog shown left is displayed.
Touch the
OK
button.
(While executing, "Processing..." message appears on the screen.)
5 When any file with the same name exists in the destination folder, the dialog shown left appears without starting the movement.
Touching the file.
OK
button overwrites the
If touch the moving.
button, cancels
6 When moving is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
9
6
Rename operation
File name to be used in advanced recipe is changed.
1 Select the file to be renamed by touching.
10
11
2 If touch the button, displays the screen shown left, then input the file name to be renamed.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
12
13
3 If touch the
Enter dialog shown left.
button, displays the
4 If touch the renaming file.
OK
button, starts
(While executing, "Processing..." message appears on the screen.)
14
5 When renaming is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the 15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 53
7
Folder create operation
Folder to be used in advanced recipe is created.
1 Touch the
Create Folder
button.
6
13
- 54
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
2 The input key window shown left appears, then input the file name to be created.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
3 If touch the
Enter dialog shown left.
button, displays the
4 If touch the folder.
OK
button, starts creating
5 When creating folder is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
9
8
G1P file create operation
Advanced recipe file (G1P file) is created.
When advanced recipe is only executed on Utility, advanced recipe file should be created with this function in advance.
1 Touch the
Create G1P
button.
10
(Continued to next page)
11
2 The screen to select the advanced recipe setting is displayed.
Select the advanced recipe setting to be used for new file.
After selecting, touch the
Next
button.
12
13
3 As the input key window is displayed, input the file name for new file.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
14
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 55
13
- 56
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
4 If touch the
Enter
button, the dialog shown left is displayed.
Touch the
OK
button.
5 When the file, whose name is the same, exists in the destination folder, the dialog shown left appears without starting the creation.
Touching the the file.
OK
button overwrites
If touch the creating.
button, cancels
6 When creating is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
9
9
Record load operation
Selected record value is loaded in the device of controller.
1 Select the recipe file and touch the
Excute
button.
10
11
2 As the Advanced Recipe Record List screen is displayed, select the record comment to which you want to load the device value.
12
13
3 If touch the
Load record
GOT PLC
button, the dialog shown left is displayed.
4 If touch the record.
OK
button, starts loading 14
5 When loading is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 57
10
Record save operation
Device value of a controller is saved in the selected record.
1 Select the recipe file and touch the
Excute
button.
2 As the Advanced Recipe Record List screen is displayed, select the record comment for saving the device value.
(Continued to next page)
13
- 58
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
3 If touch the
Save record
PLC GOT
button, the screen shown left is displayed.
For changing the record comment of saving destination, input the record comment.
By touching the following button, input text type is changed.
A-Z
:English capital a-z
:English minuscule
0-9
:Numeric/Symbol
Other than alphanumeric and symbol can not be inputted.
If record comment is not changed, it is not need to input.
9
4 If touch the
Enter
button, the dialog shown left is displayed.
5 If touch the record.
OK
button, starts saving
10
6 When saving is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
11
12
13
14
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 59
11
Record match operation
Verifies weather selected record matches to the device value of the controller.
After executing loading/saving with advanced recipe, verifies weather its contents are reflected.
1 Select the recipe file and touch the
Excute
button.
(Continued to the next page)
13
- 60
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
2 As the Advanced Recipe Record List screen is displayed, select the record comment for matching the device value.
3 If touch the
Match records
GOT PLC
button, dialog shown left is displayed.
4 If touch the
OK matching record.
button, starts
5 When matching is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
9
10
6 If selected record does not match to the device value of controller, the dialog shown left is displayed.
11
12
13
14
15
16
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13
- 61
12
Device value delete operation
The device value of selected record is deleted (without value) and changed to record only for reading.
(The record name is not deleted.)
1 Select the recipe file and touch the
Excute
button.
2 As the Advanced Recipe Record List screen is displayed, select the record comment to be deleted.
(If the data of which attribution contains
"P" can not be deleted.)
3 If touch the
Delete Dvice
Value
button, the dialog shown left is displayed.
4 If touch the device value.
OK
button, starts deleting
(The "Processing..." message is displayed on the screen.)
5 When deleting is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
13
- 62
13.7 Advanced Recipe Information
13.7.4 Advanced recipe information operation
13.7.5 Precautions
1
Precautions for create/delete
(1) When creating folder/file
(a) Number of characters set for folder or file name.
GOT recognizes file location according to path explained below.
Specify folder or file name, and total characters of path cannot exceed 78 characters.
Users only can rename folder or file name.
(Other than folder/file name is automatically printed.)
Example, CSV file Path in memory card (for GT15)
A :\ Folder name \
(2 characters)
Drive name
(1 character)
(1 character)
File name .CSV
Extension
(4 characters)
Max. 78 characters
9
10
11
12
Remark If folder is assigned the hierarchy.
The \ mark is displayed between folder name and folder name, folder name and file name.
The \ mark is also counted as one character.
13
(b) Character strings that cannot be set
The following character strings cannot be used as a folder name or a file name. Even small characters of those cannot be used.
• COM1 to COM9 • LPT1 to LPT9
• NUL • PRN
• AUX
• CLOCK$
• CON
In addition, the folder/file name showed below cannot be used.
• The folder name which begins with G1.
• Folder name and file name which begin with . (period).
• Folder name and file name which finish with . (period).
• Folder name and file name which have only . (one period) or ..(two periods).
(2) For deleting the folder
The folder in which the file exists cannot be deleted.
Delete the folder after having deleted the files.
In addition, on the advanced recipe information screen, the file other than that for advanced recipe is not displayed on GOT. When the folder, in which there is no file displayed on the screen, cannot be deleted, confirm whether there is other file in memory card by using personal computer, etc.
14
15
16
13.7 Advanced Recipe Information
13.7.5 Precautions
13
- 63
2
Precautions for operation
(1) Precautions during folder/file operation (Create/Delete/Copy/File output, etc)
Even if CF card access switch has been turned OFF while GOT is processing folders and files, the processing continues to be executed.
(Example: Even if CF card access switch has been turned OFF while GOT is creating a folder, the folder is created.)
Therefore, do not pull out the CF card while the "Processing..." message is on the screen after CF card access switch has been turned OFF.
(2) While GOT is accessing to other file (Alarm data, etc)
When folder/file processing for the advanced recip is excecuted while the GOT is in access to other file (CF card access LED ON), the GOT executes folder/file processing for the Advanced Recipe after the processing for other file has completed.
Therefore, it may take some time to finish the process of advanced recipe folder/file.
(The "Processing..." message is displayed on the screen.)
Remark Estimation of processing time
The process may take time depending on the setting of advanced recipe file to be operated. (The more number of blocks increases, the longer it takes to process advanced recipe folder/file.)
(Reference value)
Direct connection to QCPU and CPU(device point:32767 points setting, transmission speed: 115200bps)
• When the block setting number to1: about 17 seconds
• When the block setting number to 2048: about 4 minutes
(3) For executing the saving/loading of device value with advanced recipe file which has been moved or whose name has been changed.
Adjust [Recipe File] setting of advanced recipe setting with GT Designer2 to file which has been moved or whose name has been changed.
After the setting has been changed, download the advanced recipe setting to GOT.
13
- 64
13.7 Advanced Recipe Information
13.7.5 Precautions
13.8 Logging Information
13.8.1 Function of logging information
Logging files created with the logging function can be copied, deleted or renamed, etc.
Without using a personal computer, you can manage logging files on the GOT.
For details of the logging function, refer to the following manual.
GT Designer2 Version Screen Design Manual (11.3 Logging Function)
Function
Displaying file, folder data
Description
The file/folder name, data size and creating date & time are displayed.
G1L file of logging file is converted to CSV file.
conversion conversion
Del
Copy
Move
Rename
Create Folder
G1L file of logging file is converted to Unicode text file.
File or folder is deleted.
File is copied.
Folder is moved.
File name is changed.
New folder is created.
Refer to
15
16
13
14
11
12
9
10
13.8 Logging Information
13.8.1 Function of logging information
13
- 65
13.8.2 Display operation of logging information
Main menu
(
Program/Data control
Touch [Program/Data control]
Touch [Logging
Information]
[Logging Information]
Operate Logging file.
13
- 66
13.8 Logging Information
13.8.2 Display operation of logging information
13.8.3 Example of logging information display
9
10
(1)
(7)
(2) (3)
(4)
(5) (6)
(8) (9)
11
(4)
(5)
(6)
(7)
(8)
(9)
Number
(1) Drive
(2) Kind
(3) Name
Item
Path name
Size
Creating date & time
Drive size
Operation switch
Number of folders and files
Description
[A: Built-in CF card] is displayed. (Even if CF card is not installed, this message appears.)
Indicates whether the displayed name is file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
Displays the file name or folder name.
For the long file/folder name, entire part may not be displayed.
(
Confirm the nondisplayed part with the Rename button, etc.
After confirmation, touch the Cancel button to cancel the operation.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
The date and time when each file was created are displayed.
Displays the used/entire size of drive selected by select drive.
Execution switch of each function.
Displays the total number of the displayed files and folders.
About the displayed file
The files other than that for logging are not displayed on the logging information screen.
Remark Folders and files displayed
For the folders and files displayed, refer to the following.
12
13
14
15
16
13.8 Logging Information
13.8.3 Example of logging information display
13
- 67
13.8.4 Logging information operation
1
Display operation of logging information
1 If touch a drive of select drive, the information of the touched drive is displayed.
2 If touch a folder name, the information of the touched folder is displayed.
3 If touch a folder of ". .", the information of the folder of the one upper hierarchy is displayed.
4 If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5 If touch a file name, the file is selected.
6 For operation of operating switches, refer to the following.
G1L CSV ,
this section
Delete ................
Copy ..................
Move ..................
Rename .............
Create Folder.....
this section
this section
this section
this section
this section
7 If touch button, the screen is closed.
13
- 68
13.8 Logging Information
13.8.4 Logging information operation
9
2
Operation of G1L CSV conversion G1L TXT conversion
Logging file (G1L file) is converted to CSV file or Unicode text file that can be displayed/edited on personal computer.
1 Touch and select the G1L file which is to be converted to CSV file or Unidcode text file.
2 Touch the following button in accordance with destination file type.
• CSV file :
G1L->CSV
button
• Unicode text file :
G1L->TXT
button
10
11
3 Select the target folder.
(Selecting a folder is not needed for outputting directly below the drive.)
12
(Example: Dialog if the G1L->CSV button is touched.)
(Continued to next page)
13
4 If touch the
Excute
button, the dialog shown left is displayed.
Touch the
OK
button.
(While executing, "Processing..." message appears on the screen.)
14
15
16
13.8 Logging Information
13.8.4 Logging information operation
13
- 69
13
- 70
13.8 Logging Information
13.8.4 Logging information operation
5 When the file, whose name is the same, exists in the destination folder, the dialog shown left appears without starting the conversion. If touch the
OK
button, overwrites the file.
If touch
Cancel
button, cancels the conversion.
6 The message of completion is displayed in dialogue when conversion is completed.
If touch
OK closed.
button, the dialog is
3
Delete operation
Folder and file to be used on logging are deleted.
9
1 Touch and select the file/folder to delete.
10
11
2 If touch
Del
button, the dialog mentioned left is displayed.
If touch deleted.
OK
button, the file/folder is
(While executing, "Processing..." message appears on the screen.)
If touch
Cancel
button, the deletion is canceled.
12
13
3 When the deletion is completed, the completion dialog is displayed.
If touch closed.
OK
button, the dialog is
14
4 When it cannot be deleted, the dialog showed at left appears. (Only when deleting folder is executed.)
5 Verify that there is no file in the folder and execute the delete operation again.
(
15
16
13.8 Logging Information
13.8.4 Logging information operation
13
- 71
4
Copy operation
Folder to be used in logging is copied.
1 Touch and select the file to copy.
2 Touch the
Copy
button.
13
- 72
(Continued to next page)
13.8 Logging Information
13.8.4 Logging information operation
3 Select the target folder.
(Selecting a folder is not needed for outputting directly below the drive.)
At this time, it cannot be copied into the same folder where the file exists.
Select other folders.
4 If touch
Excute
button, the following dialog shown left is displayed.
(While executing, "Processing..." message appears on the screen.)
5 If there is a file of the same name in the copy destination folder, the following dialog is displayed without starting the copy.
If touch the file.
OK
button, overwrites the
If touch
Cancel
button, cancels to copy.
5
Move operation
An operation log file is moved.
(Continued to next page)
6 When the copy is completed, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
9
10
11
1 Select the file to be moved by touching it.
2 Touch the
Move
button.
12
3 Select the target folder.
(Selecting a folder is not needed for moving directly below the drive.)
13
14
15
16
13.8 Logging Information
13.8.4 Logging information operation
13
- 73
13
- 74
13.8 Logging Information
13.8.4 Logging information operation
4 If touch the
Execute
button, the dialog shown left is displayed.
Touch the
OK
button.
(While executing, "Processing..." message appears on the screen.)
5 When only file with the same name exists in the destination folder, the dialog shown left appears without starting the movement.
Touching the the file.
OK
button overwrites
If touch the moving.
button, cancels
6 When moving is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
6
Rename operation
An operation log file is changed.
9
1 Select the file to be renamed by touching.
10
11
2 If touch the button, displays the screen shown left, then input the file name to be renamed.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
12
13
3 If touch the
Enter dialog shown left.
button, displays the
4 If touch the renaming file.
OK
button, starts
(While executing, "Processing..." message appears on the screen.)
14
5 When renaming is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the 15
16
13.8 Logging Information
13.8.4 Logging information operation
13
- 75
7
Folder create operation
An operation log folder is created.
1 Touch the
Create Folder
button.
2 The input key window shown left appears, then input the file name to be created.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
3 If touch the
Enter dialog shown left.
button, displays the
4 If touch the folder.
OK
button, starts creating
5 When creating folder is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
13
- 76
13.8 Logging Information
13.8.4 Logging information operation
13.9 Memory Information
13.9.1 Memory information functions
Displays the flash memory empty area size available for the user of each drive and Boot drive empty area size.
Confirming memory empty space is enabled without connecting a personal computer.
13.9.2 Memory information display operation
9
10
(
Main menu
Touch [Program/Data control]
Program/Data control
Touch
[Memory Information]
[Memory Information]
11
12
13
Check memory information.
14
15
16
13.9 Memory Information
13.9.1 Memory information functions
13
- 77
13.9.3 Memory information display example
(1)
(2)
No.
Item
(1) Flash memory empty area size
(2) Boot drive empty area size
Description
Indicates the memory space of each drive available for the user to store files or folders.
The [A: Standard CF Card] is not displayed when CF card is not installed.
Indicates the empty area size of boot drive specified by the user.
13
- 78
13.9 Memory Information
13.9.3 Memory information display example
13.10 Special Data Information
13.10.1 Special data information function
Special data used in the intelligent unit monitor function or others can be copied, deleted, downloaded, or uploaded.
For details of special data, refer to the following manual.
GT Designer2 Version
Basic Operation/Data Transfer Manual
(8.1 Data Types and Sizes Transferred to the GOT)
Reference page Function
Information display of files and folders
Delete
Property
Data check
Download
Displays the name, data size, creation date and time of file or folder.
Deletes a file or holder.
Description
Displays the property of special data.
Copies a file.
Downloads the special data written in the A drive (Standard CF Card) to the C drive (Built-in flash memory).
13.10.2 Special data information display operation
(
Main menu
Program/Data control
9
10
11
12
13
Touch [Program/Data control]
[Special data information]
Touch [Special data information]
14
Operate Project data file.
15
16
13.10 Special Data Information
13.10.1 Special data information function
13
- 79
13.10.3 Special data information display example
(1)
(7)
(2) (3) (4) (5) (6)
(8) (9)
Number
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Kind
Name
Item
Select drive
Path name
Size
Date and time
The size of drive
Operation switch
Number of folders and files
Description
The drive by which a file or folder is displayed can be selected.
When the CF card is not installed, [A: Built-in CF card] is not displayed.
Indicates whether the displayed name is file or folder.
In the case of file, displays the extension; in the case of folder, displays "DIR".
Displays the name of special data in the selected drive.
When the name exceeds 18 characters, the 19th and later characters are not displayed.
The special data being monitored on the GOT is preceded by "*%".
Displays the path name of drive /folder which is currently displayed.
Displays the size of the file displayed in Name.
Displays the date and time when each file is installed.
Displays the size in use and the entire size of the drive which is selected by drive selection.(Only the size in use is displayed when selecting the C drive.)
Displays switch of each function executable in the Special data information (download, upload, etc.).
Displays the total number of displayed files and folders.
Remark Folders and files displayed
For the folders and files displayed, refer to the following.
13
- 80
13.10 Special Data Information
13.10.3 Special data information display example
13.10.4 Special data information operation
9
1
Special data information display operation
1 If touch a drive in [Select drive], the special data in the drive is displayed.
2 Refer to the following for operation of delete, property, data check and download.
• Delete.......................
in this section
• Property....................
• Data check ...............
• Download..... ............
in this section
in this section
in this section
3 Touching the button closes the screen.
10
11
12
13
14
15
16
13.10 Special Data Information
13.10.4 Special data information operation
13
- 81
2
Delete operation
Deletes the selected file.
1 Touch and select the file to delete.
2 If touch the
Delete
button, the screen mentioned left is displayed.
Check if the deletion target file is specified correctly.
Touching the
Touching the deletion.
OK
button deletes the file.
button cancels the
3 When the detection is completed, the dialog mentioned left is displayed.
If touch the closed.
OK
button, the dialog is
13
- 82
13.10 Special Data Information
13.10.4 Special data information operation
3
Property display operation
Displays the property of selected special data.
3
9
1 Touch the
Property
button after selecting a special data to display Property as shown left.
In Property display, the following information is displayed.
2
Date
Item
Author
Drawing S/W version
Description
Displays date and time of file creation.
Displays the author of the project data.
Displays name and version of the drawing software by which the project is created.
2 If touch the button, the screen scrolls up/down line by line.
3 If touch the button, screen scrolls up/ down by one screen.
4 If touch the , the property display is closed and returned to the previous screen.
10
11
12
13
14
15
16
13.10 Special Data Information
13.10.4 Special data information operation
13
- 83
4
Data check operation
Checks the selected special data.
Dialog when data is normal 1 Select a data check target file and touch the
Data check
button.
The data check is executed and the result is displayed by the dialog shown left.
2 If touch the closed.
OK
button the dialog is
Dialog when data is error
13
- 84
13.10 Special Data Information
13.10.4 Special data information operation
5
Download operation
Transfers the special data written in the A drive (Standard CF Card) to the C drive (Built-in flash memory)
9
Special data to be stored in a CF card
When storing the project data from GT Designer2 to CF card, select [C: Built-in flash memory] for [Project Data] in [Boot Drive].
10
11
1 Install a CF card on the GOT
Refer to the following for inserting/ removing method of CF card.
2 Touch [A: Standard CF Card] in Select drive.
12
13
(Continued to next page)
14
15
16
13.10 Special Data Information
13.10.4 Special data information operation
13
- 85
13
- 86
13.10 Special Data Information
13.10.4 Special data information operation
3 If touch the
Download
button, the screen mentioned left is displayed. Downloading is executed when the touched.
OK
button is
4 If there is a project data of the same name in the C drive, the screen shown left is displayed.
If touch the
OK
button, the project data is downloaded and the project data in the C drive is overwritten. Downloading is canceled when the
Cancel
button is touched
5 When the downloading is completed, the dialog mentioned left is displayed.
Touching the
OK
button restarts the GOT.
13.11 Operation Log Information
13.11.1 Function of operation log information
Operation log files created with the operation log function can be copied, deleted or renamed, etc.
Without using a personal computer, you can manage operation log files on the GOT.
For details of the operation log function, refer to the following manual.
GT Designer2 Version Screen Design Manual (15.2 Operation Log Function)
Function
Displaying file, folder data
Description
The file/folder name, data size and creating date & time are displayed.
conversion
G1O file of operation log file is converted to CSV file.
G1O file of operation log file is converted to Unicode text file.
conversion
Del
Copy
Move
Rename
Create Folder
List
File or folder is deleted.
File is copied.
Folder is moved.
File name is changed.
New folder is created.
Displays operation logs in a list and allows searching.
Refer to
9
10
11
12
13
14
15
16
13.11 Operation Log Information
13.11.1 Function of operation log information
13
- 87
13.11.2 Display operation of operation log information
Main menu
(
Program/Data control
Touch [Program/Data control]
Touch [Operation log Information]
[Operation log Information]
Operate Operation log file.
13
- 88
13.11 Operation Log Information
13.11.2 Display operation of operation log information
13.11.3 Example of operation log information display
9
10
(1)
(7)
(2) (3)
(4)
(5) (6)
(8) (9)
11
(4)
(5)
(6)
(7)
(8)
(9)
Number
(1) Drive
(2) Kind
(3) Name
Item
Path name
Size
Creating date & time
Drive size
Operation switch
Number of folders and files
Description
[A: Built-in CF card] is displayed. (Even if CF card is not installed, this message appears.)
Indicates whether the displayed name is file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
Displays the file name or folder name.
For the long file/folder name, entire part may not be displayed.
(
Confirm the nondisplayed part with the Rename button, etc.
After confirmation, touch the Cancel button to cancel the operation.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
The date and time when each file was created are displayed.
Displays the used/entire size of drive selected by select drive.
Execution switch of each function.
Displays the total number of the displayed files and folders.
About the displayed file
The files other than that for operation log are not displayed on the operation log information screen.
Remark Folders and files displayed
Refer to the following for the details of folders and files displayed.
12
13
14
15
16
13.11 Operation Log Information
13.11.3 Example of operation log information display
13
- 89
13.11.4 Operation log information operation
1
Display operation of operation log information
1 If touch a drive of select drive, the information of the touched drive is displayed.
2 If touch a folder name, the information of the touched folder is displayed.
3 If touch a folder of ". .", the information of the folder of the one upper hierarchy is displayed.
4 If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5 If touch a file name, the file is selected.
6 For operation of operating switches, refer to the following.
Delete ................
Copy ..................
Move ..................
Rename .............
Create Folder.....
List .....................
this section
this section
this section
this section
this section
this section
this section 8
7 If touch button, the screen is closed.
13
- 90
13.11 Operation Log Information
13.11.4 Operation log information operation
9
2
Operation of G1O CSV conversion G1O TXT conversion
Operation log file (G1O file) is converted to CSV file or Unicode text file that can be displayed/edited on personal computer.
1 Touch and select the G1O file which is to be converted to CSV file or Unidcode text file.
2 Touch the following button in accordance with destination file type.
• CSV file :
G1O->CSV
button
• Unicode text file :
G1O->TXT
button
10
11
3 Select the target folder.
(Selecting a folder is not needed for outputting directly below the drive.)
12
(Example: Dialog if the G1O->TXT button is touched.)
(Continued to next page)
13
4 If touch the
Excute
button, the dialog shown left is displayed.
Touch the
OK
button.
(While executing, "Processing..." message appears on the screen.)
14
15
16
13.11 Operation Log Information
13.11.4 Operation log information operation
13
- 91
13
- 92
13.11 Operation Log Information
13.11.4 Operation log information operation
5 When the file, whose name is the same, exists in the destination folder, the dialog shown left appears without starting the conversion. If touch the
OK
button, overwrites the file.
If touch
Cancel
button, cancels the conversion.
6 The message of completion is displayed in dialogue when conversion is completed.
If touch
OK closed.
button, the dialog is
9
3
Delete operation
Folder and file to be used on operation log are deleted.
1 Touch and select the file/folder to delete.
10
11
2 If touch
Del
button, the dialog mentioned left is displayed.
If touch deleted.
OK
button, the file/folder is
(While executing, "Processing..." message appears on the screen.)
If touch
Cancel
button, the deletion is canceled.
12
13
3 When the deletion is completed, the completion dialog is displayed.
If touch closed.
OK
button, the dialog is
14
4 When it cannot be deleted, the dialog showed at left appears. (Only when deleting folder is executed.)
5 Verify that there is no file in the folder and execute the delete operation again.
(
15
16
13.11 Operation Log Information
13.11.4 Operation log information operation
13
- 93
4
Copy operation
An operation log file is copied.
1 Touch and select the file to copy.
2 Touch the
Copy
button.
13
- 94
(Continued to next page)
13.11 Operation Log Information
13.11.4 Operation log information operation
3 Select the target folder.
(Selecting a folder is not needed for outputting directly below the drive.)
At this time, it cannot be copied into the same folder where the file exists.
Select other folders.
4 If touch
Excute
button, the following dialog shown left is displayed.
(While executing, "Processing..." message appears on the screen.)
5 If there is a file of the same name in the copy destination folder, the following dialog is displayed without starting the copy.
If touch the file.
OK
button, overwrites the
If touch
Cancel
button, cancels to copy.
5
Move operation
An operation log file is moved.
6 When the copy is completed, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
9
10
11
1 Select the file to be moved by touching it.
2 Touch the
Move
button.
12
(Continued to next page)
3 Select the target folder.
(Selecting a folder is not needed for moving directly below the drive.)
13
14
15
16
13.11 Operation Log Information
13.11.4 Operation log information operation
13
- 95
13
- 96
13.11 Operation Log Information
13.11.4 Operation log information operation
4 If touch the
Execute
button, the dialog shown left is displayed.
Touch the
OK
button.
(While executing, "Processing..." message appears on the screen.)
5 When only file with the same name exists in the destination folder, the dialog shown left appears without starting the movement.
Touching the the file.
OK
button overwrites
If touch the moving.
button, cancels
6 When moving is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
6
Rename operation
An operation log file is changed.
9
1 Select the file to be renamed by touching.
10
11
2 If touch the button, displays the screen shown left, then input the file name to be renamed.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
12
13
3 If touch the
Enter dialog shown left.
button, displays the
4 If touch the renaming file.
OK
button, starts
(While executing, "Processing..." message appears on the screen.)
14
5 When renaming is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the 15
16
13.11 Operation Log Information
13.11.4 Operation log information operation
13
- 97
7
Folder create operation
An operation log folder is created.
1 Touch the
Create Folder
button.
2 The input key window shown left appears, then input the file name to be created.
By touching the following button, input text type is changed.
A-Z
:English capital
0-9
:Numeric/Symbol
3 If touch the
Enter dialog shown left.
button, displays the
4 If touch the folder.
OK
button, starts creating
5 When creating folder is completed, completion dialog is displayed.
If touch the dialog.
OK
button, closes the
13
- 98
13.11 Operation Log Information
13.11.4 Operation log information operation
9
8
List display
Displays operation logs in an operation log file in a list.
1 Touch and select a file for displaying the list.
10
11
2
List
Touching the List button displays the list.
In the list, the following contents can be checked.
Display items: Date
Time
Screen No.
Operation type
Value after change
3 To display the details of an operation log, touch the row for that operation log to select it. The color of the row is inverted (white black).
12
13
14
15
4 Touching the selected row again displays the detailed information for the operation log.
Touch the xxxx button to close the dialog.
16
13.11 Operation Log Information
13.11.4 Operation log information operation
13
- 99
13
- 100
13.11 Operation Log Information
13.11.4 Operation log information operation
5 Touching
Search
in the list enables searching of a log using the following items.
Item: Date
Time
6 Input the date or time to be searched.
7 Touching the
Enter dialog on the left.
button displays the
OK
Touch the OK button.
(When processing is being executed, the "Processing" message is displayed on the screen.)
8 The results found are displayed and the dialog on the left is displayed.
To continue a search, touch the button.
OK
To stop a search, touch the button.
Cancel
9 When searching is completed, a completion message is displayed in the dialog.
10 Touching the dialog.
OK
button closes the
9
10
11
11
12
12
13
13
14
15
16
13.11 Operation Log Information
13.11.4 Operation log information operation
13
- 101
13.11.5 Precautions
1
Precautions for create/delete
(1) When creating folder/file
(a) Number of characters set for folder or file name.
GOT recognizes file location according to path explained below.
Specify folder or file name, and total characters of path cannot exceed 78 characters.
Users only can rename folder or file name.
(Other than folder/file name is automatically printed.)
Example, CSV file Path in memory card (for GT15)
A :\ Folder name \
(2 characters)
Drive name
(1 character)
(1 character)
File name .CSV
Extension
(4 characters)
Max. 78 characters
Remark If folder is assigned the hierarchy.
The \ mark is displayed between folder name and folder name, folder name and file name.
The \ mark is also counted as one character.
(b) Character strings that cannot be set
The following character strings cannot be used as a folder name or a file name. Even small characters of those cannot be used.
• COM1 to COM9 • LPT1 to LPT9 • AUX
• NUL • PRN • CLOCK$
• CON
In addition, the folder/file name showed below cannot be used.
• The folder name which begins with G1.
• Folder name and file name which begin with . (period).
• Folder name and file name which finish with . (period).
• Folder name and file name which have only . (one period) or ..(two periods).
(2) For deleting the folder
The folder in which the file exists cannot be deleted.
Delete the folder after having deleted the files.
In addition, on the operation log information screen, the file other than that for operation log is not displayed on GOT. When the folder, in which there is no file displayed on the screen, cannot be deleted, confirm whether there is other file in memory card by using personal computer, etc.
13
- 102
13.11 Operation Log Information
13.11.5 Precautions
9
2
Precautions for operation
(1) Precautions during folder/file operation (Create/Delete/Copy/File output, etc)
Even if CF card access switch has been turned OFF while GOT is processing folders and files, the processing continues to be executed.
(Example: Even if CF card access switch has been turned OFF while GOT is creating a folder, the folder is created.)
Therefore, do not pull out the CF card while the "Processing..." message is on the screen after CF card access switch has been turned OFF.
10
11
12
13
14
15
16
13.11 Operation Log Information
13.11.5 Precautions
13
- 103
14. GOT SELF CHECK (DEBUG & SELF CHECK)
The GOT can display the screen for debugging or self-checking.
The following describes the functions available as the debugging and self checking function.
Item
Debug
Self check
Description
System monitor, Ladder monitor, A list editor, List editor for MELSEC-A, intelligent module monitor, Network monitor, Q motion monitor, servo amplifier monitor and CNC monitor
Memory check, Drawing check, Font check, Touch panel check, I/O check,
NETWK unit status display
Reference page
System alarm display
GOT start time
GOT errors, CPU errors, network errors
Time when the GOT was started
14.1 Debug
In this manual, the overview of the debugging function and the operation procedure until displaying the screen are described.
For display contents and operation procedure of debuggings, refer to the following manual.
GOT1000 Series Extended/Option Functions Manual
14.1.1 The Debug function
The Debug function is designed to confirm the device status of PLC CPU and to make the response for PLC system trouble more efficient.
The following shows the functions that can be performed with the Debug function.
Item
System monitor
Ladder monitor*
A list editor
FX list editor
Intelligent unit monitor
Network monitor
Description
The device of PLC CPU and buffer memory of intelligent function module can be monitored or tested.
The program of PLC CPU can be monitored in ladder format.
The sequence program of ACPU can be list edited.
The sequence program of FXCPU can be list edited.
Buffer memory in the intelligent function module can be monitored or the data can be changed on the dedicated screen.
And the signal status of I/O modules can be monitored.
The network status of the MELSECNET/H, MELSECNET/10, MELSECNET(II), and
MELSECNET/B can be monitored.
Motion monitor
Servo amplifier monitor
The servo monitoring and parameter settings of the motion controller CPU (Q series) are available.
Various monitor functions, parameter change, test operation, etc. of the servo amplifier are available.
CNC monitor
Functions equivalent to the MELDAS dedicated display, such as Position Display Monitor,
Alarm Diagnosis Monitor, Tool Offset/Param, and Program Monitor, are available.
* This is not supported by the GT155 .
14
- 1
14.1 Debug
14.1.1 The Debug function
14.1.2 Display operation of Debug
(
Main menu
Debug & self check
Touch
[Debug].
Touch
[Debug & self check].
Debug is displayed.
(For System monitor)
9
Debug
Touch the debug to be operated.
10
11
12
13
14
15
16
14.1 Debug
14.1.2 Display operation of Debug
14
- 2
14.2 Self check
14.2.1 Self check function
Carries out self-check of screen data or memory etc. The items which can be self-checked are as follows.
Items Description
Carries out write/read check of the memory card and built-in flash memory
Reference page
Memory check
[Password]
5 9 2 0
Drawing Check
Font check
Carries out missing bit check, color check and drawing check.
Displays the character data on the screen to check visually.
Touch panel Check
Checks whether there are no dead zone area in the Touch key minimum unit
(16 dots x 16 dots).
I/O check Carries out RS-232 connecting target confirmation and self-loopback check.
NETWK unit status display
Displays the LED status, error information, etc. of the installed MELSECNET/H communication unit or CC-Link communication unit (GT15-J61BT13).
14
- 3
14.2 Self check
14.2.1 Self check function
14.3 Memory Check
14.3.1 Memory check function
Memory check function carries out the write/read check of A drive (Built-in CF card) and C drive (Built-in flash memory)
Function Description
A drive memory check Checks whether the memory (CF card) of the A drive can be read/written normally.
C drive memory check
Checks whether the memory (Built-in flash memory) of the C drive can be read/written normally.
14.3.2 Display operation of memory check
(
Main menu
Debug & self check Self check
9
10
11
Touch
[Self check]
Touch
[Memory check]
12
Touch
[Debug & self check]
13
Memory check
14
Select the memory to check
and touch [Check].
15
Remark Mounting condition of optional devices (board)
The mounting status of option function board and multi-color display board is displayed on the lower left of the memory check screen.
When mounted : The model numbers of the mounted option function board and multi-color display board are displayed.
When not mounted: "None" is displayed.
14.3 Memory Check
14.3.1 Memory check function
14
- 4
16
14.3.3 Memory check operation
Carries out write/read check of memory.
When drive is not displayed
When the drive (memory) to check is not displayed, confirm the mounting procedure or memory type with reference to the following.
• CF card inserting/removing method (
When no faults are found in mounting, etc, a memory failure may be arosen.
Replace the memory card or built-in flash memory (C drive).
For details of built-in flash memory, contact your local Mitsubishi (Electric System)
Service.
The following example explains about Memory Check using built-in flash memory (C drive).
For the Bulit-in CF card (A drive) memory check, install the CF card before carrying out the same key operations as built-in flash memory.
1 Select [Flash Memory] in the Memory check setting screen.
If select displayed.
OK
button, the numeric keyboard window is
If select
Cancel
button, returns to the initial menu.
2 Touch to input password (
Enter
.
5 9 2 0
) and touch
If touch
Enter
,executes read/write check for the built-in flash memory, which is completed in around 10 seconds.
14
- 5
14.3 Memory Check
14.3.3 Memory check operation
3
4
5
6
Remark Password change
The password cannot be changed.
When input password error, the cancel dialog is displayed.
If touch
OK check screen.
, returns to the Memory
When error is found in memory
When error is found by memory check, the dialog indicating the area in which the error occurred is displayed.
In case of error, contact your local
Mitsubishi (Electric System) Service.
If touch
OK check screen.
, returns to the Memory
14.3 Memory Check
14.3.3 Memory check operation
14
- 6
15
16
13
14
11
12
9
10
14.4 Drawing Check
14.4.1 Drawing check function
The drawing check function carries out display checks as missing bit check, color check, basic figure display check, move check among screens.
14.4.2 Display operation of drawing check
(
Main menu
Debug & self check Self check
Touch
[Self check]
Touch
[Display check]
Touch
[Debug & self check]
Display check
Start Drawing check
If touch the [Drawing check] of Display check, the screen for drawing check is displayed.
Touch
[Drawing check]
Notes on drawing check
Missing bits is occurred in the following cases.
1. There are parts drawn in different color with the filled color.
2. There are parts of basic figure and drawing patterns which are not drawn according to the layout and procedures described in "Section 13.3.3 Display and
Operation of Drawing Check".
When missing bits occurs, contact your local Mitsubishi (Electric System) Service.
14
- 7
14.4 Drawing Check
14.4.1 Drawing check function
14.4.3 Drawing check operation
The screen for drawing check can be displayed by touching [Drawing check] on the Display check menu.
1
Before execute drawing check
Touching the upper right part of the screen proceeds to the next check in each step during drawing check.
Touching the upper left part of the screen returns to the
[Display check] screen.
Upper-left touch position
Upper-right touch position
9
10
11
1 Missing bit, Color Check
By touching the upper-right part of the screen, the entire screen color changes in the following order: black red purple green light blue yellow white.
Check missing bit and color visually.
12
13
Black Red Purple Green Light blue Yellow White
To 2) Basic figure check screen
If touch the upper right part of the screen at the final color (white screen), the following 2) Basic figure check screen is displayed.
14
15
16
14.4 Drawing Check
14.4.3 Drawing check operation
14
- 8
2 Basic figure check
Check whether there is no shape transformation of basic figure or display losses.
The basic figure drawn has 4 types: 1. Filled circle, 2. Line, 3. Rectangle, 4. Ellipse.
To (a) Pattern 1of (3) Move check among screens
14
- 9
14.4 Drawing Check
14.4.3 Drawing check operation
3 Move check among screens
(a) Pattern 1: Shape transformation, color check
The drawn figures are displayed in order and at regular intervals.
If the shape and color are displayed visually in order, it is normal.
To Pattern 2
Pattern 1
(b) Pattern 2: Shape transformation, color check
The drawn figures are displayed in order and at regular intervals.
If the shape and color are displayed visually in order, it is normal.
To Pattern 3
Pattern 2
15
16
13
14
11
12
9
10
14.4 Drawing Check
14.4.3 Drawing check operation
14
- 10
(c) Pattern 3: Shape transformation, color check
The overlaped shapes of pattern 1 and pattern 2 are displayed.
If the shape and color are displayed visually in order, it is normal.
To Pattern 4
(d) Pattern 4: Shape Check
The drawn figures are displayed in order and at regular intervals.
If the shape and color are displayed visually in order, it is normal.
If touch the upper right part of the screen, returns to [Display check] screen.
To [Display check]
The main screen image after the screen information read and write is executed
14
- 11
14.4 Drawing Check
14.4.3 Drawing check operation
14.5 Font Check
9
14.5.1 Font check function
The font check is a function which confirms fonts installed in GOT. The character data of the font is displayed on the upper left part of the screen one by one.
14.5.2 Display operation of Font check
10
(
Main menu
Debug & self check Self check
11
Touch
[Display check]
Touch
[Debug & self check]
Touch
[Self check]
12
Display check
Touch
[Font check]
Starts font check
When touch [Font check] of the [Display check],
Font check starts.
13
14
Notes on Font Check
Judged as normal if the following characters are correctly displayed. (UNICODE)
Alphabetic characters etc. : 0 x 0000 to 0 x 04F9 (From basic Latin to Kirill)
Hangul characters
Kanji
: 0 x AC00 to 0 x D7A3 (Hangul / Hangul auxiliary)
: 0 x 4E00 to 0 x 9FA5 (CJK integrated Kanjis)
If the characters above are not displayed correctly, the fonts may not be installed.
Install the standard monitor OS again.
15
16
14.5 Font Check
14.5.1 Font check function
14
- 12
14.5.3 Font check operation
Font check starts by touching [Font Check] in the [Display check] screen.
The character data of the built-in font (in the built-in flash memory) can be checked visually to confirm the font drawings by displaying the character data serially on the screen.
1
Before execute font check
Touching the upper right part of the screen proceeds to the next check in each step during Font check.
Touching the upper left part of the screen returns to the
[Display check] screen.
Upper-left touch position
Upper-right touch position
8
9
10
11
6
7
4
5
2
3
1 The installed font data is displayed by touching the upper right part of the screen.
Font data
Option fonts
To display optional fonts, the followings are required.
• The option font installation
• Option function board installation
The option fonts are displayed at the end.
12
14
- 13
14.5 Font Check
14.5.3 Font check operation
14.6 Touch Panel Check
9
14.6.1 Touch panel check function
Touch panel check is a function which checks whether there is no dead zone area in touch key minimum unit
(16 dots x 16 dots).
14.6.2 Display operation of Touch panel check
10
(
Main menu
Debug & self check Self check
11
Touch
[Debug & self check]
Touch
[Self check] Touch
[Touch panel check]
12
Starts Touch panel check
When touch [Touch panel check] of [Display check],
Touch panel check starts.
13
14
Notes on Touch panel check
If the touched part is not filled with yellow color, there are the following two possible causes.
1. Display part failure
2. Touch panel failure
In that case, contact your local Mitsubishi (Electric System) Service.
15
16
14.6 Touch Panel Check
14.6.1 Touch panel check function
14
- 14
14.6.3 Touch panel check operations
If touch [Touch panel check] of self-check, a black-filled screen is displayed over the entire screen area.
1 Touch a part of the screen.
The touched part becomes a yellow-filled display.
Black-filled screen
Yellow color
2 If touch the upper left part, returns to the self-check.
Upper-left touch position
Remark Checking the upper left part of the screen
Only the upper left part of the screen cannot be filled with yellow.
If returnes to the self-check by touching the upper left part, judge that the upper left area operates normally.
14
- 15
14.6 Touch Panel Check
14.6.3 Touch panel check operations
14.7 I/O Check
14.7.1 I/O check function
The I/O check is a function which checks whether GOT and PLC can communicate with each other.
If I/O check ends normally, the communication interface and the connection cable hardwares are normal.
To execute I/O check, the communication driver has to be installed in GOT in advance from GT Designer2.
Refer to the following for the details related to the installation of the communication driver.
GT Designer2 Version Basic Operation/Data Transfer Manual
(8. TRANSFERRING DATA)
9
10
Precautions for executing I/O check function
Only the [RS-232 Interface] communication interface can carry out the I/O check function.
(The connection with RS-422 is possible by installing the RS-422 conversion unit to the RS-232 interface.)
11
14.7.2 Display operation of I/O Check
12
(
Main menu
Debug & self check Self check
Touch
[Self check]
13
Touch
[Debug & self check]
Touch
[I/O check]
14
I/O check
15
16
14.7 I/O Check
14.7.1 I/O check function
14
- 16
14.7.3 I/O Check Operation
1
Connecting target confirmation
If touch [CPU] button, the connecting target confirmation communication check is carried out.
1 After the CPU communication starts normally, the dialog mentioned right notifying that it is on checking, untill the connecting target confirmation communication ends normally.
2 When the connecting target confirmation communication ends, its result is notified by dialog.
If the connecting target confirmation communication ends normally, the dialog notifying of the normal termination mentioned right is displayed. If touch
[I/O check].
OK
button after confirming the result, returns to
If the dialog mentioned right is displayed after selecting connecting target confirmation or during CPU communication check, confirm the following.
• No misconnection with CPU
( GOT1000 Series Connection Manual)
• No hardware error
( GOT1000 Series Connection Manual)
• No missettings of parameter
(
10.2 Communication Detail Settings)
If touch
OK
button in the dialog After confirming the result, returns to [I/O check].
14
- 17
14.7 I/O Check
14.7.3 I/O Check Operation
2
Self-loopback
If touch [Self], the hardware check of RS-232 interface is carried out.
1 For preparation for the self-loopback communication check, insert the connector for self-loopback check
(Customer purchased) shown in the diagram right in the
RS-232 interface.
For this connector, short 2 and 3 pins, 7 and 8 pins and 4 and 6 pins, respectively.
Display unit (rear face)
RS-232 interface
9
10
11
2 After selecting [Self], the transferred data and received data are verified through the self-loopback connector. If data can not be received during data transmission, the dialog shown right is displayed, which notifies the self-loopback connector failure, self-loopback connector communication error or RS-
232 interface hardware failure.
12
13
3 During check, the dialog shown right is displayed.
14
4 When the all checks ended normally, the dialog shown right is displayed. If touch
OK contents, the GOT restarts.
button after confirming the
15
16
14.7 I/O Check
14.7.3 I/O Check Operation
14
- 18
5 If an error occurs, the dialog is displayed, which notifies the
GOT terminates abnormally at that point and at which byte the error occurred. If a verification error occurs, the RS-232 interface hardware may be faulty.
If touch
OK
button in the dialog, the GOT restarts.
14
- 19
14.7 I/O Check
14.7.3 I/O Check Operation
14.8 NETWK Unit Status Display
9
14.8.1 Functions of the NETWK unit status display
The network unit status display is a function that uses the communication units below to monitor the network status.
• MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13)
• CC-Link communication unit (GT15-J61BT13)
The LED status or error status of a network module can be checked.
For the corrective actions for errors that occur on the network, refer to the following manual.
The Reference Manual of the MELSECNET/H or MELSECNET/10 network system
(PLC to PLC network) to be used
The Userís Manual of the CC-Link system master/local module to be used
10
11
14.8.2 Displaying the NETWK unit status display
(
Main menu
Debug & self check Self check
12
Touch
[Self check].
Touch
[Debug & self check].
Touch
[NETWK unit status display].
13
NETWK unit status display
14
15
16
14.8 NETWK Unit Status Display
14.8.1 Functions of the NETWK unit status display
14
- 20
14.8.3 Display example of the NETWK unit status display (MELSECNET/H communication unit)
1
MELSENCNET/H
communication unit
GT15-J71LP23-25
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(a)
(b)
GT15-J71BR13
(c)
(d)
(e)
(f)
(g)
(h)
14
- 21
14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
(1) LED status
Displays the MELSECNET/H communication unit operation status.
No.
RUN
Item
LED color
*
Green
Lit
Data link normal
(a)
MNG
S.MNG
D.LINK
T.PASS
SW.E.
Green
Green
Green
Green
Green
Operating as control station
Operating as sub control station
Not lit
Data link error
Operating other than as control station
Operating other than as sub control station
Data link stopped
Baton pass not executed
Normal
(b)
M/S.E.
PRM.E.
GOT R/W
CRC
OVER
AB.IF
TIME
DATA
UNDER
LOOP
SD
RD
Green
Green
Green
Red
Red
Red
Red
Red
Red
Red
Green
Green
Data link being executed
Baton pass being executed
Switch setting error
Duplicate station number and control station error
Parameter error
Accessed from GOT
Code check error
Data entry delay error
All reception data 1
Time limit exceeded
Reception data error
Send data error
Forward/reverse loop reception error
Sending data
Receiving data
Normal
Normal
Not accessed from GOT
Normal
Normal
Normal
Normal
Normal
Normal
Normal
*: For monochrome display, it is displayed as (lit) or (not lit).
(2) Loop information
Displays the MELSECNET/H communication unit loop status.
No.
Item
(c)
F loop*
R loop*
FLoopBK Sta*
RLoopBK Sta*
Loop Back *
Description
Displays the status (Normal/NG) of the F loop.
Displays the status (Normal/NG) of the R loop.
Displays the F loopback station execution status (No per/Number of the station at which loopback is executed).
Displays the R loopback station execution status (No per/Number of the station at which loopback is executed).
Displays the loopback status (No per/Perf).
No per: Loop normal, forward loop error, reverse loop error,
data link not possible
Perf: During loopback
*: For the GT15-J71BR13, "---" is displayed.
9
10
11
12
13
14
15
16
14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
14
- 22
(3) Data link information
Displays the MELSECNET/H communication unit data link information (communication status, cause of communication suspension, cause of communication stop).
No.
Item
(d) Com Status
(e) Cause of Ssp
(f) Cause of Stop
Description
Displays the communication status of the host.
D-Link in prog. : FData link being executed
D-Link Stop(A)
D-Link Stop (H)
B-Pass exec (No Area)
B-Pass exec (Param Err)
B-Pass exec (Param unreceived)
Disconnect (No B-Pass)
Disconnect (Line Err)
Testing
Reset. in prgr.
: Cyclic transmission stopped from other station
: Cyclic transmission stopped by host
: Host B/W send no allocation
: Error in host parameters
: Common parameters not received
: Station numbers duplicated, cable not connected
: Cable not connected
: Testing online/offline
: Hardware failure
Displays the cause of disabled communication (transient transmission) of the host.
Normal Comm : Communicating normally
Offline
Offline test
: Offline
: Testing offline
Initialize
Change Ctrl Sta
Testing Online
Baton Missing
Baton Duplicated
Dup Sta No
Dup Ctrl Sta
Rcv Retry Err
: Error (error code: F101, F102, F105)
: Error (error code: F104, F106)
: FError (error code: F103, F109, F10A)
: Error (error code: F107)
: Error (error code: F108)
: Error (error code: F10B)
: Error (error code: F10C)
: Error (error code: F10E)
Send Retry Err
Time Out Err
Abnormal Line
Disconnection
No Own Sta Baton
Other (error code)
: Error (error code: F10F)
: Error (error code: F110)
: Error (error code: F112)
: Error (error code: F11B)
: Error (error code: F11F)
: Error (error code: displayed)
Displays the cause of disabled data link (cyclic transmission) of the host.
Normal : Communicating normally
StopOrder
No Shared Param
Bad Shared Param
: Cyclic transmission of all stations stopped from host
or other station
: Parameters cannot be received
: Set parameter error
Bad Self Sta CPU
Com Aborted
: A medium/critical error occurred in the host CPU
: Host data link error occurred
(4) Transient status
Displays the number of transient transmission errors and the error code.
No.
(g) Transmission Err
(h) ErrCode
Item Description
Displays the number of transient transmission errors.
For other than the
GT155
Error histories of 16 errors are displayed in 16 lows from the latest.
Only the latest error history is
For the GT155 displayed as only a single low is provided.
14
- 23
14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
2
CC-Link communication unit
(a)
(b)
(c)
11
12
(1) LED status
Displays the CC-Link communication unit (GT15-J61BT13) operation status.
No.
Item
LED color
Lit Not lit
RUN Green Running normally
WDT error occurred or unit being reset
ERR.
Red
All station communication error
No communication error occurred or unit being reset
Blink
There is a communication error station or duplicated station numbers.
(a)
TIME
MST
SW
LINE
S MST
M/S
LOCAL
PRM
GOT R/W
Red
Green
Red
Red
Green
Red
Green
Red
Green
No responses from all stations due to cable breakage or transmission path affected by noise
Operating as master station
Switch setting error
Cable breakage error
Operating as standby master station
Duplicate master station error
Operating as local station
Parameter error
Accessed from GOT
Responses from all stations
Operating other than as master station
No switch setting error
No cable breakage error
Operating other than as standby master station
No duplicate master station error
Operating other than as local station
No parameter error
Not accessed from GOT
13
14
15
16
14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
14
- 24
9
10
(2) Data link information
Displays the CC-Link communication unit (GT15-J61BT13) data link startup status and error status.
No.
Item Description
(b) D-Link Boot Status
Displays the data link startup status.
D-Link in prog.
D-Link Offline
Initialize
Parameter wait
Disconnect (No Polling)
Disconnect (Line Err)
Disconnect (Other)
Testing Line
Testing Pram Setup
Auto Reconnecting
Reset. in prgr.
: Data link being executed
: Data link being stopped
: Set to the initial status
: Parameter not received
: In cut-off status with no inquiry from master station
: In cut-off status due to line error
: In cut-off status due to other causes
: Line test being executed
: Parameter setting test being executed from master station
: Return processing being executed automatically
: CC-Link communication unit being reset
(GOT reset status)
(c) Error Status
Displays the status of the current error.
Normal
Invalid TransPath
Invalid Parameter
CRC Error
Time Out Error
Abort Error
Invalid Setup
Other Abnormality
: Normal status
: Transmission path error detected
: Parameter error detected
: Reception data error detected
: Timeout error detected in data reception
: Error detected in data communication
: Invalid station number, station type, transmission speed, or mode setting detected
: Error due to some other cause detected
14
- 25
14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
14.9 System Alarm Display
9
14.9.1 System alarm display function
System alarm display is the function to display error code and error message when an error occurs in GOT, controller or network.
System alarms can be reset on the System alarm display screen.
For details of system alarm, refer to the following manual.
GT Designer2 Version Screen Design Manual (8. ALARM)
14.9.2 Displaying the system alarm display
10
11
(
Main menu
[Debug & self check]
Touch [System alarm display].
Touch [Debug & self check].
12
System alarm display
When touching Reset , the system alarm display on the
GOT is reset.
13
14
15
16
14.9 System Alarm Display
14.9.1 System alarm display function
14
- 26
14.9.3 Operating the system alarm display
1
System Alarm display resetting
1 Eliminate each cause of the system alarm being occurred.
Error causes can be identified by the error code, error message and channel No. displayed on the System alarm display screen.
(
Touch.
2 Touch the alarms.
Reset button to reset system
(1) Before resetting System Alarm display
Eliminate each cause before resetting system alarms.
Without eliminating causes, System Alarm display cannot be reset even when touching the [Reset] button.
(2) Processings with reset operation
The following data in the system information are also reset.
• GOT error code (Write device)
• GOT error detection signal (System Signal 2-1.b13)
14
- 27
14.9 System Alarm Display
14.9.3 Operating the system alarm display
14.10 GOT Start Time
14.10.1 GOT start time function
GOT start time is the function to display the following date and time.
• Start time of GOT
• Current time of GOT
• Operating hours of GOT
14.10.2 Display operation of GOT start time
(
Main menu
[Debug & self check]
Touch [GOT start time].
Touch [Debug & self check].
GOT start time
15
16
13
14
11
12
9
10
14.10 GOT Start Time
14.10.1 GOT start time function
14
- 28
14.10.3 Display of GOT start time
Start Time
Item
Current Time
Operating hours
Description
Displays the time when the GOT was powered on or reset-restarted (OS installation, communication setting change).
Displays the current time.
Displays operating hours of the GOT.
The displayed operating hours is the accumulated time while GOT is powered on or resetrestarted (OS installation, communication setting change).
When powering off or reset-restarting the GOT, the operating hours is cleared.
To display correct time
Set the clock of GOT.( 12.1 Time Setting and Display)
When the clock has not been set, the correct time is not displayed at [Start Time] and [Current Time].
Remark Time displayed at [Operating hours]
[Operating hours] is displayed irrespective of [Start Time] and [Current Time].
When changing the clock of the GOT, [Operating hours] does not match with the difference between [Current Time] and [Start Time]. ([Operating hours] is not the time calculated from [Current Time] and [Start Time].)
The time displayed at [Operating hours] is a reference for the accumulated time while GOT is powered on or reset-restarted (OS installation, communication setting change).
14
- 29
14.10 GOT Start Time
14.10.3 Display of GOT start time
15. CLEANING OF DISPLAY SECTION
(CLEAN)
In utility, the screen can be set as not to be effected by touching the screen when clean with clothes.
Refer to the below for the cleaning procedure.
15.1 Clean
15.1.1 Display operation of Clean
(
Main menu
Clean
9
10
11
12
Touch [Clean]
13
Even if touch points other than the upper left corner and upper right corner of the screen, the GOT does not operates.
14
15
16
15.1 Clean
15.1.1 Display operation of Clean
15
- 1
15.1.2 Operation of Clean
After cleaning the screen, touch the screen following the instruction displayed.
After touching the screen, the screen returns to the Main Menu.
Depending on the GOT to use, either of the following screens is displayed.
• Display pattern 1
• Display pattern 2
15
- 2
15.1 Clean
15.1.2 Operation of Clean
16. MAINTENANCE TIME
NOTIFICATION SETTING
(MAINTENANCE TIMING SETTING)
Energization time, touch count and writing times used as standard for the maintenance time are set.
When use the maintenance timing function, battery and option function board are required.
Refer to the following below for details of battery and option function board.
9
10
11
14
15
12
13
16
16
- 1
16.1 Maintenance Timing Setting
16.1.1 Function of the maintenance timing setting
When use maintenance time notification function, battery and option function button are required.
When setting the maintenance notifying time, refer to the life descrived in Section 3.2 Performance
Specifications as a guide to set time or count.
The maintenance time notification is output by the following two methods.
• Outputs to GOT special register (GS680).
• Outputs as system alarm
For details of the GOT special register and system alarm, refer to the following.
GT Designer2 Version Screen Design Manual
Item
Backlight maintenance time notification period.
(0 to 100000 hour)
Display section maintenance time notification period
(0 to 100000 hour)
Switching OFF the maintenance time notification output
The maintenance time notification setting which has been set once is not switched
OFF even if changing its setting.
Switch OFF the maintenance time notification by the following methods.
• Execute addition time reset.
• Switch OFF each bit of "maintenance time notification cancel information
(GS638)".
Description Setting range Unit
Maintenance points
Reference page
Sets energization time for the maintenance notification output.
When 0, no message notification.
The time is counted only when backlight is lit, in every ten minutes.
Sets energization time for the maintenance notification output.
When 0, no message notification.
The time is counted only when energized, in every ten minutes.
0 to 100
<At factory shipment: 0>
0 to 100
<At factory shipment: 0>
1000 hours
1000 hours
18-5
Touch key maintenance time notification count
(0 to 2000000times)
Sets touch key touching count for the maintenance notification output.
When 0, no message notification.
Counts by every screen touch.
Built-in flash memory maintenance time notification count
(0 to 1000000times)
Sets built-in flash memory writing count for the maintenance notification output.
When 0, no message notification.
Counts by every writing in built-in flash memory.
0 to 200
<At factory shipment: 0>
0 to 200
<At factory shipment: 0>
10000 times
1000 times
By using system alarm, the message that notifies that the maintenance time is near or it is already maintenance time is displayed.
For the display of the system alarm, refer to the following.
20. ERROR MESSAGE AND SYSTEM ALARM
For the display of the system alarm, refer to the following.
GT Designer2 Version Screen Design Manual
16
- 2
16.1 Maintenance Timing Setting
16.1.1 Function of the maintenance timing setting
16.1.2 Display operation of maintenance timimg setting
(
Main menu
Maintenance time notification settings
Touch [Maintenance timing setting]
For the addition times as power on addition time, refer to the following.
16.1 Maintenance Timing Setting
16.1.2 Display operation of maintenance timimg setting
16
- 3
15
16
13
14
11
12
9
10
16.1.3 Operating the maintenance timing setting
1 Touch a select button (item to be set) on the screen.
•
Numerical
Key: If touched, displays the keyboard in the bottom part of the screen.
(For keyboard operation, refer Section 9.3.3 Basic operation of settings change
page.)
Define the numerical input by
Enter
.
Remark
If touch
Enter is displayed.
after inputting the value out of the setting range, the alarm message
Example:
2 If touch
OK
button, the settings are reflected.
3 If touch button instead of touching displayed, and the screen closes.
OK
button, the settings are canceled after the dialog below is
4 If touch button, GOT restarts.
5 After restart, GOT operates with the changed settings.
16
- 4
16.1 Maintenance Timing Setting
16.1.3 Operating the maintenance timing setting
17. ADDITION TIMES RESET FOR
MAINTENANCE TIME NOTIFICATION
(ADDITION TIMES RESET)
Displays the present value of Backlight maintenance time notification period, Display section maintenance time notification period, Touch key maintenance time notification count and Built-in flash memory maintenance time notification count which are additioned for the maintenance time notification, respectively and resets these values.
17.1 Addition times reset
17
18
19
17.1.1 Addition times reset function
Item
Backlight power on addition time reset
Display power on addition time reset
Description
Function to reset the power on addition times to "0".
Function to reset the power on addition times to "0".
Touch key pushing addition times reset Function to reset the pushing addition times to "0".
Build in flash memory writing addition times reset Function to reset the writing addition times to "0".
20
17.1.2 Display operation of Addition times reset
Addtion times reset
(
Main menu
Touch [Addtion times reset]
Addition time
17.1 Addition times reset
17.1.1 Addition times reset function
17
- 1
17.1.3 Operation of Addition times reset
1 If touch
Reset
button of each item, the addition time or the addition count becomes "0".
2 If touch
OK
button, the reset value is reflected.
3 If touch button instead of touching
OK below is displayed, and the screen closes.
button, the changed contents are canceled after the dialog
4 If touch button, GOT restarts.
5 After restart, GOT operates with the changed settings.
Addition times resetting timing
It is convenient to reset addition times when replace backlight, display section, touch panel or built-in flash memory.
17
- 2
17.1 Addition times reset
17.1.3 Operation of Addition times reset
18. INSTALLATION OF COREOS, BOOTOS
AND STANDARD MONITOR OS
17
In order to execute the GOT utility, it is necessary to install BootOS and standard monitor OS on the GOT C drive (built-in flash memory).
(BootOS is installed in the GOT at factory shipment. It is not necessary to install BootOS when upgrading of it is unnecessary. )
This chapter explains the installation using GOT.
GT Designer2 Memory card GOT
Write OS file BootOS or standard monitor OS installation
GOT
When GOT is remote, installed easily using the memory card
Memory card
Install the memory card in GOT
GT Designer2
GOT Memory card GOT
OS file upload
BootOS, standard monitor OS installation
GOT GOT
Install OS from GOT to GOT using memory card
Memory card
Install the memory card in GOT
For details of the installation using GT Designer2, refer to the following.
GT Designer2 Version Basic Operation/Data Transmission Manual
18
19
20
CoreOS
In 18.1 to 18.4 of this chapter, only BootOS and standard monitor OS are described.
For CoreOS, refer to the following.
18
- 1
18.1 BootOS and Standard Monitor OS Required for installation
Under-mentioned BootOS and Standard monitor OS are necessary to execute utility.
OS name
BootOS
Standard monitor
OS
Function overview
Requied for the control of GOT and the communication between PC and GOT.
Installed at factory shipment.
(BootOS can be installed from GT Designer2 or the CF card. When installed from GT Designer2 or the CF card, GOT is initialized to be the factory shipment status. Standard monitor OS must be pre-installed in the GOT when installing the BootOS again.)
Required for the GOT operation as the monitoring function of GOT, installation and deletion of the OS file or project data, touch key control or display function of the screen and guidance.
System screen data
System screen management information file
TrueType numerical font
12-dot standard font (Gothic)
16-dot standard font (Mincho)
16-dot standard font (Gothic)
Required for display and operation of the user-created screen and utility screen.
Not installed in GOT at factory shipment.
Install it from GT Designer2 or the memory card.
At installation, select [Mincho] or [Gothic] for the 16-dot standard font.
Storage location
Built-in flash memory
C: \G1BOOT\
Built-in flash memory
C:\G1SYS\
18
- 2
18.1 BootOS and Standard Monitor OS Required for installation
18.2 Prior Preparations for Installing BootOS and
Standard Monitor OS
17
For the installation using GOT, the memory card storing BootOS or standard monitor OS is required.
For the method of writing BootOS and standard monitor OS in the memory card, the following two methods are available.
(1) [To Memory Card] from GT Designer2
GT Designer2 Version Basic Operation/Data Transfer Manual
8.9 Transferring Data Using a Memory Card (PC memory card GOT)
(2) Uploading from other GOT (BootOS or standard monitor OS has been installed)
13. FILE DISPLAY AND COPY (PROGRAM/DATA CONTROL)
18
19
Precautions on writing BootOS, standard monitor OS in memory card
When writing BootOS, standard monitor OS, etc. in the memory card, be sure to execute by the utility of other GOT or GT Designer2.
The installation is not executed properly with the memory card to which uploaded from the utility of GOT or copied by softwares other than GT Designer2.
Note the available capacity of the memory card.
The available capacity of BootOS and standard monitor OS can be confirmed by [To
Memory Card] of GT Designer2.
20
Capacity of standard monitor OS
18.2 Prior Preparations for Installing BootOS and Standard Monitor OS 18
- 3
18.3 BootOS and Standard Monitor OS Installation Using
Memory Card
There are the following two types for the BootOS,standard monitor OS installation.
(1) Installing when starting the GOT
(
All the OS and project data stored in the memory card are transferred to the GOT when powering on the GOT. This installing method is effective in the following cases.
• The GOT utility cannot be displayed.
• The standard monitor OS is not installed.
(2) Installing using the Program/Data control function (Utility)
(
By operating the utility, select OS or project data stored in the memory card and transfer them to the GOT.
18
- 4
Precautions on installing BootOS, standard monitor OS
(1) Installing both BootOS and standard monitor OS
After completing BootOS installation, install standard monitor OS.
When installing BootOS, the built-in flash memory in the GOT is initialized and goes to the status at factory shipment. (All OS and project data are erased.)
BootOS is installed in the GOT at factory shipment. It is not necessary to install
BootOS when not upgrading it.
(2) Copying project data using a CF card
After installing BootOS, standard monitor OS, and other OS, download the project data.
At this time, match the version of the standard monitor OS in the GOT with the version of the standard monitor OS with which the project data was created.
(3) When OS and project data are in the CF card (when using GT Designer2)
For a 2-point press installation, after the OS installation is complete, the project data is downloaded.
When installing with the utility, install the OS and download the project data from their respective operation screens.
(4) Installation cannot be interrupted.
Do not perform any of the following during a BootOS or standard monitor OS installation.
Failure to do so may result in installation failure, causing the GOT malfunction.
• Powering off the GOT
• Pressing the reset button of the GOT
• Turning off the CF card access switch of the GOT
• Removing the CF card
If the installation failure and the GOT malfunction occur, take the following action.
• If BootOS installation failed
Install CoreOS.
(
• If standard monitor OS installation failed:
Install BootOS.
(
18.3.1Installing when starting the GOT)
18.3 BootOS and Standard Monitor OS Installation Using Memory Card
18.3.1 Installing when starting the GOT
The displayed message is different depending on the installation condition of standard monitor OS. When the screen requesting operation is displayed, operate the GOT according to the instructions on the screen.
17
1
Operation procedure
1 Power OFF GOT and CF card access switch. Insert the CF card in which BootOS, standard monitor OS or project data is stored in the CF card interface of GOT.
2 Switch ON the CF card access switch of GOT.
18
3 Power on the GOT.
• For GT1595
Power on the GOT while pressing the installation switch (S.MODE switch) on the back of the GOT. (1point press installation function)
• For GT1585, GT157 , GT156 , GT155
Power on the GOT while touching the upper and left of the GOT screen. (2-point presses installation function)
Installation switch
( S. MODE)
19
20
Simultaneous
2-point touch
For GT1595
For GT1585, GT157 , GT156 ,
GT155
4 BootOS, standard monitor OS is installed in the built-in flash memory.
The CF card access LED is lit during install execution.
Do not pull out the CF card or power OFF the GOT while the CF card access LED is lit.
Now installing BootOS.
5 GOT restarts automatically after installation is completed.
(When standard monitor OS is already installed, GOT restarts by touching
OK
button.)
Reboot.
6 After confirming normal restart, switch OFF the CF card access switch of GOT. When it is confirmed that
CF card access LED is not lit, remove the CF card from the CF card interface of GOT.
18.3 BootOS and Standard Monitor OS Installation Using Memory Card
18.3.1 Installing when starting the GOT
18
- 5
18.3.2 Installation method using the program/data control function (Utility)
For details of program/data control function, refer to the following.
13. FILE DISPLAY AND COPY (PROGRAM/DATA CONTROL)
Precautions on executing program/data control function
When execute program/data control function, standard monitor OS has to be installed in GOT in advance. Thus, this function cannot be used for the initial installation of BootOS, standard monitor OS after purchasing GOT.
Install standard monitor OS by the following two methods.
(1) GT Designer2
(2) Installing when starting the GOT
1
Operation procedure
1 Power OFF the GOT. After CF card access LED is off, install the CF card in which BootOS, standard monitor OS or project data is stored in the CF card interface of GOT.
2 Switch ON the CF card access switch of GOT.
3 Display the program/data control function screen (Utility) on the GOT, and install BootOS, standard monitor OS from the CF card to GOT.
Touch [Install]
18
- 6
18.3 BootOS and Standard Monitor OS Installation Using Memory Card
18.3.2 Installation method using the program/data control function
4 CF card access LED is lit during install execution.
Do not pull out the CF card or power OFF the GOT while the CF card access card is lit.
19
5 GOT restarts automatically after the installation is completed.
Reboot.
6 After confirming that GOT restarted normaly, switch OFF the CF card access switch of GOT. Confirm the
CF card access LED is not lit, remove the CF card from the CF card interface of GOT.
20
17
18
18.3 BootOS and Standard Monitor OS Installation Using Memory Card
18.3.2 Installation method using the program/data control function
18
- 7
18.4 When installing the different version of BootOS, standard monitor OS
(1) BootOS installation
When installing BootOS, GOT compares the version of the BootOS to be installed with the version of BootOS which is already installed.
If the major version of BootOS to be installed is old, execute the following operations to prevent it from being rewritten.
(When installing from GT Designer2, a message is displayed on the personal computer screen.
Follow the instructions in that message.)
(a) When only BootOS is stored in the CF card
The message indicating disabled installation is displayed.
Touch the
OK
button to cancel installation.
After canceling installation, restart the GOT.
(b) When BootOS, standard monitor OS, and other OS are stored in the CF card
Skip the BootOS installation and install standard monitor OS and other OS.
If the standard monitor OS is already stored on the GOT, the following message is displayed.
Touching the
OK
button executes installation.
Touching the
Cancel
button cancels installation.
After executing or canceling installation, restart the GOT.
18
- 8
18.4 When installing the different version of BootOS, standard monitor
OS
(c) When the version is the same or newer regardless of the data stored in the CF card (conditions
(a) and (b) above)
The version information and a dialog for selecting whether or not to continue installation are displayed.
17
18
19
<GOT screen when BootOS is installed from memory card.>
If touch
OK
button, installation is executed.
If touch
Cancel
button, installation is canceled.
(2) Standard monitor OS installation
Match the version of each OS file when installing standard monitor OS.
Standard monitor OS cannot be installed if the version of each OS file does not match.
When the installation process is discontinued.
Standard monitor OS : 1.
O.
O
Communication driver :
Optional function OS :
2.
2.
O.
O.
O
O
When the installation process is normally executed.
Standard monitor OS : 2.
O.
O
Communication driver :
Optional function OS :
2.
2.
O.
O.
O
O
20
Please match the number.
18.4 When installing the different version of BootOS, standard monitor
OS
18
- 9
Checking method of BootOS, standard monitor OS version
1.
Check the version of BootOS or standard monitor OS installed in GOT at [OS information] of the utility.
Refer to the following for details.
2.
Check the version of BootOS installed in GOT at product shipment on the rating plate on GOT rear face.
GRAPHIC OPERATION TERMINAL
MODEL GT1575-VTBA
IN 100 240VAC 50/60Hz
POWER MAX 90VA
SERIAL 00004701 AA00001-A
MITSUBISHI ELECTRIC MADE IN JAPAN
BACKLIGHT GT15-70VLTT
A A
BootOS version
18
- 10
18.4 When installing the different version of BootOS, standard monitor
OS
18.5 CoreOS
17
Install CareOS only when the GOT will not be the status of factory shipment even when BootOS is installed.
Normally, the CoreOS has not to be installed.
Precautions for installing CoreOS
When executing the CoreOS installation once, it cannot be canceled on the way.
Do not attempt the followings to cancel the installation on the way.
The GOT may not operate.
• Powering the GOT off.
• Pressing the GOT reset button.
If the GOT does not operate, please consult your local Mitsubishi (Electric
System) Service center or representative.
If the GOT does not recover even when installing the CoreOS, the error may be caused by a hardware failure.
Please consult your local Mitsubishi (Electric System) Service center or representative.
18.5.1 Installing the CoreOS
18
19
20
1
Before installing the CoreOS
(1) Installing procedureThe CoreOS can be installed only when using a memory card.
Installation via USB/RS-232/Ethernet is not available.
(2) Memory card to be used
Memory card of 32MB or more is required.
(3) Boot OS
When installing the CoreOS, the latest BootOS is also installed automatically.
(Operation by the user is not required.)
18.5 CoreOS
18.5.1 Installing the CoreOS
18
- 11
2
Installing the CoreOS
1 Write the CoreOS from GT Designer2 to the CF card.
For details of GT Designer2 operation, refer to the following manual.
GT Designer2 Version Basic Operation/Data Transfer Manual
(8. TRANSFERRING DATA)
2 After confirming that the GOT is powered off, install the CF card in the GOT.
After installing, switch the CF card access switch on.
3 Powering the GOT on displays the following screen.
To cancel the installation, power the GOT off and remove the CF card.
18
- 12
18.5 CoreOS
18.5.1 Installing the CoreOS
4 Turning the CF card access switch off executes Core OS installation.
5 When the installation is completed, the dialog as shown below is displayed.
(The POWER LED of the GOT blinks (green/orange) at the installation completion.)
Confirm that the message is displayed and power the GOT off.
19
20
17
18
6 Remove the CF card after powering the GOT off.
7 Powering the GOT on again displays the screen as shown below.
(The GOT goes to the status of factory shipment.)
Install OS (Standard monitor OS, communication driver, etc.) or download project data as required.
For how to install each OS or download project data, refer to the following manual.
GT Designer2 Version Basic Operation/Data Transfer Manual
(8. TRANSFERRING DATA)
18.5 CoreOS
18.5.1 Installing the CoreOS
18
- 13
18.5.2 When the CoreOS cannot be installed
When the CoreOS cannot be installed, confirm the following item.
If the CoreOS cannot be installed even after checking the following item, the error may be caused by a hardware failure.
Please consult your local Mitsubishi (Electric System) Service center or representative.
Error
The CoreOS installation is not executed even when installing the CF card in the GOT.
GOT error. Contact your local sales office.
Action
(1) Check whether the CF card access switch of the GOT is on.
If the switch is off, switch it on.
(2) The writing from the GT Designer2 to the memory card may not have been completed normally.
Execute the writing from the GT Designer2 to the memory card again.
The GOT main unit is broken.
Please consult your local Mitsubishi (Electric System) Service center or representative.
The message is displayed on the GOT
CF card error.
Installation will be cancelled.
Check whether the CF card can be used.
Optional unit has been connected to extension I/F slot.
The optional unit should be removed before starting installation.
Installation will be canceled.
GOT type and OS version do not match.
Installation will be canceled.
The version of OS is not acceptable to this GOT.
Installation will be canceled.
Confirm the version of OS.
Memory card access switch is off.
Turn on the switch and restart the GOT.
Installation will be canceled.
The CF card is defective.
(1) Format the CF card and re-execute.
(2) Replace the CF card.
Remove the extension unit installed on the GOT.
The GOT type selected at [Core OS write] of the GT Designer2 is not correct.
Confirm the GOT type and perform [Core OS write] again.
Install CoreOS from the latest GT Designer2.
The CF card access switch is off. Turn the switch on and restart the
GOT.
18
- 14
18.5 CoreOS
18.5.2 When the CoreOS cannot be installed
19. MAINTENANCE AND INSPECTION
17
DANGER
• Connect the battery correctly.
Do not discharge, disassemble, heat, short, solder or throw the battery into the fire.
These may cause the buttery to burst or fire.
• Do not touch the terminals while the power is on.
Doing so can cause an electric shock.
• Before starting cleaning or retightening the terminal screws, always switch off the external power supplies used in the system in all phases.
Cleaning or retightening the terminal screws while the power is on may cause an electric shock.
• Before changing the backlight, always switch off the GOT power externally in all phases (when the GOT is connected to the bus, the PLC CPU power must also be switched off externally in all phases) and remove the GOT from the control panel.
Not switching off the power in all phases may cause an electric shock.
Not removing the unit from the control panel can cause injury due to a drop.
CAUTION
• Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction or fire.
• Do not touch the conductive and electronic parts of the GOT directly.
Doing so can cause a unit malfunction failure.
• The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.
• When unplugging the cable connected to GOT, do not hold and pull the cable portion.
Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault.
• Before insert/remove the connection cable, power off the GOT.
Not doing so can cause a failure or malfunction.
• When replacing the backlight, use the gloves.
Otherwise, it may cause you to be injured.
• Start changing the backlight more than 5 minutes after switching the GOT power off.
Not doing so can cause a burn due to the heat of the backlight.
• Do not drop or give an impact to the battery mounted on the unit.
Doing so can cause the battery to be damaged due to the drop or the impact, making the battery liquid to leak in the battery.
Do not use but dispose the battery that is dropped or given an impact.
• Before touching the unit, be sure to touch grounded metal or similar objects to discharge the static electricity from human body.
Not doing so can cause a failure or malfunction of the unit.
• When disposing of the product, handle it as industrial waste.
The GOT does not include consumable components that will cause the shorten life.
However, the battery, liquid crystal screen and backlight have each life length.
It is recommended to replace the battery, backlight periodically.
(For the replacement of the liquid crystal screen, please consult Mitsubishi (Electric System) Service.)
Refer to the following section for the lives of the battery, liquid crystal screen and backlight.
3.2 Performance Specifications
18
19
20
19
- 1
19.1 Daily Inspection
Daily inspection items
No.
1
Inspection Item
GOT mounting status
Loose terminal screws
Inspection
Method
Check for loose mounting screws.
Retighten screws with screwdriver
Criterion
Securely mounted
Not loose
Action
Retighten screws within the specified torque range.
Retighten terminal screws
2
Connection status
Proximate solderless terminals
Visual check Proper intervals Correct
Loose connectors Visual check Not loose
Retighten connector fixing screws
Replace with new one
3
Usage status
Dirt on protection sheet Visual check
Foreign material attachment
Visual check
Not outstanding
No foreign matter sticking
Remove clean
Refer to the following for the model names of the protection sheet or the replacement procedure.
19.2 Periodic Inspection
Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved or modified or the wiring changed.
No.
Inspection Item Inspection Method Action
1
Surrounding environment
Ambient temperature
Make measurement with thermometer or hygrometer
Measure corrosive gas
Criterion
Display section 0 to 40°C
Other portions 0 to 55°C
10 to 90%RH
For use in control panel, temperature inside control panel is ambient temperature
2
3
4
GOT with
100-240V
AC power
GOT with
24VDC power
Mounting status
Connection status
Ambient humidity
Atmosphere
Power supply voltage check
Input polarity of 24VDC power
Looseness
Dirt, foreign matter
Loose terminal screws
Proximate solderless terminals
Loose connectors
100 to 240VAC
Measure voltage across terminals.
24VDC
Measure voltage across terminals.
Move module
Visual check
Retighten screws with screwdriver
Visual check
Visual check
No corrosive gas
85 to 242VAC
Left : -
Right : +
Change supply power
Change wiring
Should be mounted firmly Retighten screws
No dirt, foreign matter sticking
Remove, clean
Not loose
Proper intervals
Not loose
Retighten terminal screws
Correct
Retighten connector fixing screws
(Continued to next page)
19
- 2
19.1 Daily Inspection
17
No.
Inspection Item
5 Battery
Inspection Method Criterion
Check [GOT internal battery voltage status] in [Time setting & display] of the Utility.
No alarm appears
19.3 Cleaning Method
Use GOT always in a clean condition.
To clean the GOT, wipe the dirty part with a soft cloth using neutral detergent or ethanol.
Clean
Action
Replace with new battery when the current battery has reached the specified life span, even if battery voltage low is not displayed.
18
19
20
Precautions for cleaning
Do not use solvents such as acetone, benzene, toluene and alcohol, since they may cause the protective sheet to be deformed or the dissolvable paint on the surface to peel off.
In addition, do not use spray solvents since they may cause the electrical failure of the GOT and peripheral devices.
19.3 Cleaning Method 19
- 3
19.4 Battery Voltage Low Detection and Battery
Replacement
The battery is used for backing up the present time or the maintenance time notification data.
It is recommended that you replace battery periodically.
Refer to the following for the replacement procedure.
The battery voltage low detection can be confirmed by the utility and system alarm.
Refer to the following for details of the battery status display by the utility.
12. CLOCK SETTINGS AND BATTERY STATUS DISPLAY (TIME SETTING AND
By using system alarm, the message that notifies the battery voltage has decreased can be displayed at the battery voltage low on the screen of the GOT.
To display the following message on system alarm, set [Battery alarm display] to "ON".
11.1.1 Display setting functions
System alarm
500 Warning! Built-in battery voltage is low.
Refer to the following for details of the system alarm display.
GT Designer2 Version Screen Design Manual (8. ALARM)
Battery replacement timing
When detecting voltage low, replace the battery immediately.
Data can be saved for 14 days after the battery voltage low detection and cannot be saved after that.
19
- 4
19.4 Battery Voltage Low Detection and Battery Replacement
19.5 Backlight Shutoff Detection and Replacement
17
The backlight is built into GOT for the liquid crystal display.
When GOT detects backlight shutoff, the POWER LED blinks green/orange alternately.
The brightness of the backlight decreases with the lapse of usage period. When backlight shutoff is detected or the display becomes unclear, replace the backlight.
When replace the backlight, refer to "19.6 Backlight Replacement".
18
(1) Life of backlight
The usable duration of backlight can be extended by setting to [Screen saving backlight off] in the utility of GOT (GOT set up).
Refer to the following for details.
11. DISPLAY AND OPERATION SETTINGS (GOT SET UP)
(2) Replacement time of backlight
The backlight replacement time can be set by the utility of GOT (Maintenance timing setting) with reference to the life of backlight.
Refer to the following for details.
16. MAINTENANCE TIME NOTIFICATION SETTING (MAINTENANCE TIMING
Moreover, when system alarm is used, the message that notifies of the backlight replacement time can be displayed on the GOT screen.
19
20
System alarm
502 Warning! Backlight needs replacement soon.
Refer to the following for the system alarm display.
GT Designer2 Version Screen Design Manual (8. ALARM)
Precautions for the backlight shutoff status
In the backlight shutoff status, the touch key operates.
Early replacement of backlight is recommended.
19.5 Backlight Shutoff Detection and Replacement 19
- 5
19.6 Backlight Replacement
This section explains the backlight replacing methods.
19.6.1 Applicable backlight
The following backlights are applicable for GT15
Model name
GT15-90XLTT
GT15-80SLTT
GT15-70SLTT
GT15-70VLTT
GT15-70VLTN
GT15-60VLTT
GT15-60VLTN
.
Description
For 15" high intensity, wide angle view TFT
(XGA)
For 12.1" high intensity, wide angle view
TFT (SVGA)
For 10.4" high intensity, wide angle view
TFT (SVGA)
For 10.4" high intensity, wide angle view
TFT (SVGA, VGA)
For 10.4" TFT (VGA)
For 8.4" high intensity, wide angle view TFT
(VGA)
For 8.4" TFT (VGA)
GT1595-X
Target GOT
GT1585V-S, GT1585-S
GT1575-S
GT1575V-S, GT1575-V
GT1575-VN, GT1572-VN
GT1565-V
GT1562-VN
19.6.2 Replacement procedure of backlight
1
For GT15-90XLTT
1 Power off the GOT.
2 Disconnect the power supply cable and communication cable.
Remove the GOT from the control panel.
3 Remove the expansion unit cover on the right side of the GOT.
Remove the expansion unit, e.g. bus connection unit, if it is mounted.
4 Remove the GOT rear fixing screws (8 pcs.) with a screwdriver.
A
19
- 6
19.6 Backlight Replacement
19.6.1 Applicable backlight
5 Remove the case after passing the battery holder through the mounting hole.
When removing, take care of not cutting the cable of the battery holder.
(Expanded figure of part A in )
19
6 Disconnect the cable connector of the upper (H01) backlight and the cable connector of the lower (H02) backlight from the GOT side connectors.
20
A
7 Pull the upper backlight by pressing the projecting part of the rubber holder that fixes the backlight with a minus driver to unfasten the backlight.
In the same way, pull the lower backlight by pressing the projection part of the rubber holder that fixes the backlight with a minus driver to unfasten it.
(Expanded figure of part A in
6
)
A jut of the rubber holder
17
18
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
19
- 7
8 Pull the upper backlight out through the hole for backlight replacement on the upper part of the GOT.
In the same way, pull the lower backlight out through the hole for backlight replacement on the lower part of the GOT.
Hole for backlight replacement
9 Mount a new backlight in the reverse procedure of removal.
When inserting a new backlight through the hole for backlight replacement of the GOT main unit, take care not to damage the sheath of the cable.
And push the backlight in securely until the projection part of the rubber holder is fixed.
Also assemble the case in the reverse procedure of disassembly. (Tighten the GOT rear fixing screws within the torque range of 0.36 to 0.48N·m).
When mounting the case, take care of not biting the cables between the case and the GOT.
2
For GT15-80SLTT, GT15-70SLTT, GT15-70VLTT, GT15-70VLTN
Backlight replacement varies with the hardware version of the applicable GOT.
Before replacement, please confirm the hardware version.
(
Appendix 2 Confirming of Versions and Conformed standards)
Type
GT1585V-STBA
GT1585-STBA
GT1585-STBD
GT1575V-STBA
GT1575-STBA
GT1575-STBD
GT1575-VTBA
GT1575-VTBD
GT1575-VNBA
GT1575-VNBD
GT1572-VNBA
GT1572-VNBD
Hardware version
A (March, 2006) or later
B (April, 2005) or earlier
C (March, 2005) or later
A (Jul, 2005) or later
A (March, 2006) or later
B (April, 2005) or earlier
C (March, 2005) or later
A (Jul, 2005) or later
D (April, 2005) or earlier
E (March, 2005) or later
A (Jul, 2005) or later
A (Sep, 2005) or later
A (Sep, 2005) or later
A (Sep, 2005) or later
A (Sep, 2005) or later
Reference
(1) Replacement procedure 1
(2) Replacement procedure 2
(1) Replacement procedure 1
(1) Replacement procedure 1
(1) Replacement procedure 1
(2) Replacement procedure 2
(1) Replacement procedure 1
(1) Replacement procedure 1
(2) Replacement procedure 2
(1) Replacement procedure 1
(1) Replacement procedure 1
(1) Replacement procedure 1
(1) Replacement procedure 1
(1) Replacement procedure 1
(1) Replacement procedure 1
(1) Replacement 1
1 Power off the GOT.
2 Disconnect the power supply cable and communication cable.
Remove the GOT from the control panel.
19
- 8
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
3 Remove the expansion unit cover from the right side of the GOT.
Remove the expansion unit, e.g. bus connection unit, if it is mounted.
17
18
4 Remove the GOT rear fixing screws (8 pcs.) with a screwdriver.
19
A
5 Remove the case after passing the battery holder through the mounting hole. When removing, take care of not cutting the cable of the battery holder.
(Expanded figure of part A in )
20
6 Pull up the backlight drive board, and disconnect the cable connector of the backlight from the connector of the backlight drive board.
When replacing GT15-80SLTT, remove the cable from the cable holder.
(When replacing GT15-80SLTT)
Cable holder
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
19
- 9
7 Press the backlight fixing latch (black) with your finger, and pull out the backlight to the left.
When pulling the backlight, press the packing with your finger so that the backlight will not be hit with the packing.
(When replacing GT15-80SLTT) (When replacing GT15-70SLTT, GT15-70VLTT or GT15-70VLTN)
Latch
Latch
Packing
8 Mount a new backlight in the reverse procedure of removal.
Also assemble the case in the reverse procedure of disassembly.
(Tighten the GOT rear fixing screws within the torque range of 0.36 to 0.48 N·m).
When mounting the case, take care of not biting the cables between the case and the GOT.
(2) Replacement 2
1 Power off the GOT.
2 Disconnect the power supply cable and communication cable.
Remove the GOT from the control panel.
3 Remove the expansion unit cover from the right side of the GOT.
Remove the expansion unit, e.g. bus connection unit, if it is mounted.
4 Remove the GOT rear fixing screws (8 pcs.) with a screwdriver, and remove the case.
Screw A must be tighten in the torque range of 0.186 to 0.245 N·m, as it is made of plastic.
A
19
- 10
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
17
5 Pull up the backlight drive board, and disconnect the cable connector of the backlight from the connector of the backlight drive board.
18
6 Press the backlight fixing latch (black) with your finger, and pull out the backlight to the left.
When pulling the backlight, press the packing with your finger so that the backlight will not be hit with the packing.
(When replacing GT15-80SLTT) (When replacing GT15-70SLTT, GT15-70VLTT or GT15-70VLTN) 19
Latch
Latch
20
Packing
7 Mount a new backlight in the reverse procedure of removal.
Also assemble the case in the reverse procedure of disassembly.
(Tighten the GOT rear fixing screws within the following torque range:
Screw A: 0.186 to 0.245 N·m, Other screws: 0.36 to 0.48 N·m).
When mounting the case, take care of not biting the cables between the case and the GOT.
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
19
- 11
3
For GT15-60VLTT or GT15-60VLTN
Backlight replacement varies with the hardware version of the applicable GOT.
Before replacement, please confirm the hardware version.
(
Appendix 2 Confirming of Versions and Conformed standards)
Type
GT1565-VTBA
GT1565-VTBD
GT1562-VNBA
GT1562-VNBD
Hardware version
D (April, 2005) or earlier
E (March, 2005) or later
A (Jul, 2005) or later
A (Sep, 2005) or later
A (Sep, 2005) or later
Reference
(2) Replacement procedure 2
(1) Replacement procedure 1
(1) Replacement procedure 1
(3) Replacement procedure 3
(3) Replacement procedure 3
(1) Replacement 1
1 Power off the GOT.
2 Disconnect the power supply cable and communication cable.
Remove the GOT from the control panel.
3 Remove the expansion unit cover on the right side of the GOT.
Remove the expansion unit, e.g. bus connection unit, if it is mounted.
4 Remove the GOT rear fixing screws (8 pcs.) with a screwdriver.
A
5 Remove the case after passing the battery holder through the mounting hole.When removing, take care of not cutting the cable of the battery holder.
(Expanded figure of part A in )
19
- 12
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
6 Disconnect the cable connector of the upper (H01) backlight and the cable connector of the lower (H02) backlight from the GOT side connectors.
(Expanded figure of part A in 6 )
17
18
A
B
B
7 Remove the cables of the upper connector (H01) from the 2 slits (black).
Similarly, remove the cables of the upper connector (H02) from the 2 slits (black).
(Expanded figure of part B in 6 )
19
8 Press the upper backlight fixing latch (black) with your finger, and pull out the backlight to the left.
Similarly, press the lower backlight fixing latch (black) with your finger, and pull out the backlight to the left.
20
Latch
9 Mount a new backlight in the reverse procedure of removal.
10 When connecting the cable connectors of the backlight and the GOT unit, connect by crossing the cable connectors each other as the below.
Also assemble the case in the reverse procedure of disassembly. (Tighten the GOT rear fixing screws within the torque range of 0.36 to 0.48N·m).
When mounting the case, take care of not biting the cables between the case and the GOT.
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
19
- 13
(2) Replacement 2
1 Power off the GOT.
2 Disconnect the power supply cable and communication cable.
Remove the GOT from the control panel.
3 Remove the expansion unit cover on the right side of the GOT.
Remove the expansion unit, e.g. bus connection unit, if it is mounted.
4 Remove the GOT rear fixing screws (8 pcs.) with a screwdriver, and remove the case.
Screw A must be tighten in the torque range of 0.186 to 0.245 N·m, as it is made of plastic.
A
5 Disconnect the cable connector of the upper (H01) backlight and the cable connector of the lower (H02) backlight from the GOT side connectors.
6 Press the upper backlight fixing latch (black) with your finger, and pull out the backlight to the left.
Similarly, press the lower backlight fixing latch (black) with your finger, and pull out the backlight to the left.
7 Mount a new backlight in the reverse procedure of removal.
Also assemble the case in the reverse procedure of disassembly. (Tighten the GOT rear fixing screws within the following torque range: Screw A: 0.186 to 0.245 N·m, Other screws: 0.36 to 0.48N·m.)
When mounting the case, take care of not biting the cables between the case and the GOT.
19
- 14
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
(3) Replacement 3
1 Power off the GOT
2 Disconnect the power supply cable and communication cable.
Remove the GOT from the control panel.
3 Remove the expansion unit cover on the right side of the GOT.
Remove the expansion unit, e.g. bus connection unit, if it is mounted.
17
18
19
4 Remove the GOT rear fixing screws (8 pcs.) with a screwdriver.
A
5 Remove the case after passing the battery holder through the mounting hole. When removing, take care of not cutting the cable of the battery holder.
(Expanded figure of part A in (4))
20
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
19
- 15
6 Disconnect the cable connector of the backlight from the GOT side connector.
B
A
(Expanded figure of part A in 6 )
7 Remove the cables from the 2 slits (black).
(Expanded figure of part B in (6))
8 Press the backlight fixing latch (black) with your finger, and pull out the backlight to the left.
Latch
9 Mount a new backlight in the reverse procedure of removal.
When connecting the cable connector of the backlight to the GOT side connector, connect by it as shown below.
Also attach the case in the reverse procedure of removal. (Tighten the GOT rear fixing screws within the torque range of 0.36 to 0.48N·m).
When attaching the case, take care of not biting the cables between the case and the GOT.
19
- 16
19.6 Backlight Replacement
19.6.2 Replacement procedure of backlight
20. ERROR MESSAGE AND SYSTEM
ALARM
17
This chapter describes the error message and system alarm displayed in the GOT.
As the error code and error message displaying functions when an error occurs at the GOT, controller or network, there are two kinds: system alarm and advanced system alarm.
The error code can also be confirmed in the error code storage area of the system information function.
In addition, the channel No. at which error has occurred can be confirmed with the GOT special register
(GS262 to 264).
For details of system alarm, advanced system alarm, system information and GOT special register, refer to the following.
18
19
GT Designer2 Version Screen Design Manual
20.1 Error Contents Display
This section describes the example for displaying error code and error message on GOT with advanced system alarm.
1
Popup-displaying the error code and error message
If an error occurs, the error code and error message can be popup-displayed on the front of the monitor screen.
As alarms are popup-displayed regardless of the screen type, the error occurred will not be overlooked.
20
A 1254
B 348
A 1254
B 348
04/6/1 13:20 Power module
Pop up generated alarms regardless of the screen.
2
Displaying error code and error message in a list.
If error has occurred, error code and error message can be displayed on the list set with the screen.
Multiple errors can be displayed, or the history of display can be recorded.
Occurred
04/6/1 10:25
04/6/1 8:05
Message
Temp. error
Fuse error
Restore Check
11:25 10:45
Create a screen to display alarms, and confirm the details of the alarms and take measures.
20.1 Error Contents Display 20
- 1
Error code and reference manual
Error source Error code Description
Channel
No. storage destination
*
1
Reference
Controller
GOT
0 to 99
(Value of D9008)
Error code of CPU (for ACPU)
100 to 299
300 to 399
Error code of the following controllers
• FXCPU*
2
• Third party PLC
• Temperature controller
(OMRON temperature controller only)
Error code of the GOT main unit function
400 to 499
500 to 699
Error code of the GOT communication function
Error code of the GOT main unit function
GS263
GS262*
4
User's manual of the ACPU connected with GOT
User's manual of the
FXCPU connected with
GOT
When connecting a thirdparty PLC, deal with the error according to the error message.
Network
CPU
800 to 999
1000 to 10000
(Value of SD0)
Error code of network
Error code of CPU
(for QCPU, QnACPU)
GS264
GS263
Reference manual of the network connected with
GOT
User's manual of the QCPU and QnACPU connected with GOT
User's manual of the servo amplifier connected to GOT
Servo amplifier*
3
20016 to 20237 Error code of servo amplifier
*1 For details of GOT special registers (GS262 to 264), refer to the following manual.
GT Designer2 Version Screen Design Manual (2.9.1 GOT internal devices)
*2 The assigned error code for FXCPU is 100 to 109, which displays the status of M8060 to M8069.
(Example) When the error code (100) error occurs, correct the error according to the M8060 description.
*3 The error code displayed on GOT is calculated by changing the error code (Hexadecimal) displayed on the servo amplifier to the decimal number and adding 20000 to it.
When referring to the manual of servo amplifier by the error code displayed as a GOT system alarm, subtract
20000 from the GOT error code and change its lower three digits to the hexadecimal number.
(Example: When GOT system alarm is 20144, the error code of servo amplifier becomes 90H.)
*4 Channel No. will not be stored depending on the error code.
For channel No. storage availability for each error code, refer to the following.
20.2 List of Error Message/System Alarm
20
- 2
20.1 Error Contents Display
20.2 List of Error Message/System Alarm
17
The system alarm detected with GOT is shown below.
Error code
Error message Action
303
304
306
307 Monitor device not set
308
309
310
311
312
315
Set monitor points too large. Decrease setting points.
Set trigger points too large. Decrease setting points.
No project data.
Download screen data.
No comment data.
Download comment.
Device reading error.
Correct device.
Project data does not exist or out of range.
No. of alarm has exceeded upper limit.
Delete restored alarm.
No. of sampling has exceeded upper limit.
Delete collected data.
Device writing error.
Correct device.
316
Cannot display or input operation value. Review expression.
Decrease the number of objects from the displayed screen.
For the number of maximum objects for 1 screen, refer to the following.
GT Designer2 Version Screen Design Manual
The number of objects using Sampling/Cycle during ON/
Cycle during OFF exceeds 100.
Decrease the number of objects.
The project data is not downloaded to the built-in flash memory.
Download the project data to the built-in flash memory.
The monitor device of the object is not set.
Set the monitor device of the object.
The comment file does not exist.
Create the comment file and download to GOT.
The error occurred when reading a continuous device.
Correct the device.
1. Specified base screen / window screen does not exist in the project data.
2. Specified base screen / window screen is out of the permissible area. Specify the existing base screen / window screen.
The number of alarm histories that can be observed by the alarm history display function has exceeded the maximum points.
Delete the restored history to decrease the number of alarm histories.
The collection frequency exceeded the upper limit when
"Store Memory" and "Accumulate/Average" were set in the scatter graph.
1. Approve "Clear trigger" setup in the scatter graph.
2. Set the "Operation at frequency over time" to "Initialize and
Continue" in scatter graph.
Error occurred while writing in the device.
Correct the device.
In indirect specification of comment/parts number, the data operation result exceeded the range in which device type can be expressed.
Review the data operational expression, in order not exceeding the range in which the device type can be expressed.
Channel
No. storage 18
19
20
20.2 List of Error Message/System Alarm 20
- 3
Error code
Error message Action
317
320
322
330
Too high frequency of data collection.
Review conditions.
Specified object does not exist or out of range.
Dedicated device is out of range. Confirm device range.
Insufficient memory media capacity. Confirm M-card capacity.
331
Memory card not installed or M-CARD switched OFF
Data of an object, to which [Collect data only when trigger conditions are satisfied] is set, are collected too frequently, or the number of objects has exceeded the number of objects collectable simultaneously.
1. Set a longer cycle for trigger occurrence to each object.
2. Make the settings so that 257 or more display triggers of objects, to which [Collect data only when trigger conditions are satisfied] is set, do not occur simultaneously.
The part file does not exist.
Create the part file and download to GOT.
The monitored device No. is out of the permissible area of the targeted PLC CPU.
Set the device within the range that can be monitored by the monitored PLC CPU and parameter settings.
Available memory of the memory card is insufficient.Confirm the available memory of the memory card.
The available memory can be confirmed by system information screen, which is described in GT Designer2
Version Screen Design Manual.
The memory card is not installed or in the drive access switch is OFF in drive.
1. Install the memory card in the specified drive.
2. Turn ON the access switch.
Memory card is not formatted or formatted incorrectly.
Format the memory card.
332
333
334
335
Memory media is not formatted.
Unable to overwrite.
Memory card is writeprotected.
Memory media error.
Replace memory media.
Memory card battery voltage low. Replace battery.
Memory card is write-protected.
Cancel the write-protection of memory card.
Memory card is faulty.
Replace the memory card.
The battery voltage of the memory card is low.
Replace the battery of the memory card.
340
Printer error or power failure
341 Printer error
Printer is faulty or the printer power supply has not been turned on.
1. Confirm the printer.
2. Turn on the power supply of the printer.
Printer is faulty or the printer power supply has not been turned on.
1. Confirm the printer.
2. Turn on the power supply of the printer.
Channel
No. storage
20
- 4
20.2 List of Error Message/System Alarm
Error code
Error message Action
342
353
354 Recipe file write error
355 Recipe file read error
356
357
KBF module fuse blown.
Check the module or external power source.
Unable to write Recipe file. Confirm memory card is inserted.
File system error occurred in PLC. Confirm file register.
Error in specified PLC drive Confirm PLC drive
Error occurred at the external I/O interface module.
1. If an external power supply (24VDC) is not supplied, supply the external power supply.
2. If an external power supply is supplied, replace the external
I/O interface module.
343
KBF module status error.
Load KBF module properly.
352
Recipe file make error.
Reboot GOT after inserting memory card.
The external I/O interface module is not installed correctly.
Install the external I/O interface module correctly.
345
BCD/BIN conversion error
Correct data
351
Recipe file error. Confirm content of recipe file.
Any value that cannot be converted to a BCD/BIN value is being displayed/input.
1. Change the device data to be displayed to the BCD value.
2. Correct the input value to the 4 digits integer.
The contents of the recipe file are not normal.
1. Confirm the contents of the recipe files in the memory card.
2. Reboot the GOT after deleting the recipe file in the memory card (format).
Failed to generate recipe file.
Reboot the GOT after installing the memory card.
Failed to write in the recipe file.
1. Confirm the write-protection of the memory card.
2. Confirm the contents of the memory card.
3. Do not pull out the memory card while recipe is operating.
Error occurred while writing in the recipe file.
Do not unplug the memory card while recipe is operating.
Error occurred while writing in the recipe file.
1. Do not unplug the memory card while recipe is operating.
2. Confirm the contents (device value) of the recipe file in the memory card.
Error occurred in the specified file register when executing the recipe function by specifying the file register name.
1. Execute the recipe function again after confirming the file register name.
2. Execute the recipe function again after formatting the PC memory in the specified PLC CPU drive with GX
Developer.
When executing the recipe function specifying the file register name, error occurred in PLC CPU drive.
1. Execute the recipe function again after confirming the specified PLC CPU drive.
2. Execute the recipe function again after formatting the PC memory in the specified PLC CPU drive with GX
Developer.
Channel
No. storage
17
18
19
20
20.2 List of Error Message/System Alarm 20
- 5
Error code
Error message Action
358
359
360
370
0 divisor division error.
Confirm operation expression.
Upper and lower limit value error. Confirm value setting.
402
PLC file access failure.
Confirm PLC drive.
Processing from another peripheral device.
Execute it after.
Communication timeout.
Confirm communication pathway or modules.
When the recipe function is executed specifying the file register name, PLC CPU file register could not be accessed.
1. Execute the recipe function again after confirming the specified PLC CPU drive / file register name. (When you specify drive 0, execute the recipe function again after changing to other drives.)
2. Confirm whether the memory card is write-protected, and execute the recipe function again.
When the recipe function is executed specifying the file register name, other peripherals carry out the process to the file register.
Wait until the processing of other peripherals end, and execute the recipe function again.
Zero division occurred by the data operational expression.
Review the data operational expression so that the divisor should not become 0.
The setting of lower/upper limit value is [Upper limit < Lower limit].
Correct the setting so as to be "Upper limit Lower limit".
The time-out error occurred during communicating.
1. Confirm the cable omission, the communication unit mounting status and status of the PLC.
Channel No. is not displayed in error code or error message in the case an error occurs when using the multichannel function.
Refer to the following manual to identify the channel No. in error.
GOT1000 Series Connection Manual (Description of
"Checking for normal monitoring" of each connection type)
2. This error may occur when the load of PLC CPU becomes heavier while accessing other stations. In such case, transfer the data of the other station to the host station PLC
CPU and monitor them at the host.
3. Put COM instruction when the PLC scanning is long.
Channel
No. storage
20
- 6
20.2 List of Error Message/System Alarm
Error code
Error message Action
403
SIO status error. Confirm communication pathway or modules.
406
Specified station access is out of range. Confirm station no.
407
410
411
Accessed other network by NET/10 unit. Change network setting.
Cannot perform operation because of PLC run mode. stop the PLC.
Memory cassette is writeprotected. Check the memory cassette.
Either of the overrun error, parity bit error or flaming error was generated when the RS-422 / RS-232 communication was received.
Confirm the cable omission, the communication module mounting status, status of the PLC.and the transmission speed of the computer link.
Channel No. is not displayed in error code or error message in the case an error occurs when using the multi-channel function.
Refer to the following manual to identify the channel No. in error.
GOT1000 Series Connection Manual (Description of
"Checking for normal monitoring" of each connection type)
1. Station numbers other than master/local station are specified at the CC-Link connection (via G4).
2. A PLC CPU other than QCPU is accessed.
Confirm the station number of the project data.
A other network (other than MELSECNET/10) when the unit is connected to is accessed MELSECNET/10 (PLC to PLC network).
Confirm Network No. of the project data, in order for not accessing other networks.
The operation, which could not be performed during RUN of
PLC CPU, was performed.
Stop the PLC CPU.
The memory cassette installed in the PLC CPU is EPROM or
E
2
PROM, and it is in a protected status.
Confirm the memory cassette installed in PLC CPU.
412
Cannot read/write device protected by keyword.
Remove keyword.
The key word is set in PLC CPU.
Cancel the key word.
420
421
422
E71 specification is
ASCII.
E71 is set as read-only.
Clear setting.
Not communicating between CPU and E71.
Confirm CPU error.
[ASCII code] is selected in [Ethernet operations] of the PLC side setting.
Select [Binary code].
The Ethernet module on the PLC side is set in read-only.
Set the Ethernet module on the PLC side to write-enabled.
PLC CPU error. Communication between PLC CPU and the
PLC side Ethernet module impossible.
Confirm whether there is error in PLC CPU by GX Developer etc. (Confirm buffer memory)
Channel
No. storage
17
18
19
20
20.2 List of Error Message/System Alarm 20
- 7
20
- 8
Error code
Error message Action
Channel
No. storage
423
Insufficient network table information. Add station no.
424
448
450
Same sta. on GOT & project data. Review communication parameter.
PLC cannot handle as requested. Correct devices.
Path has changed or timeout occurred in redundant system.
The station number set in the project data does not exist in the Ethernet setting of GT Designer2.
Add the station number set in the project data to the Ethernet setting of GT Designer2.
(Set the station number so that it becomes the same as the station number of the PLC CPU side Ethernet module set by the parameter of GX Developer.)
The station number set in the GOT's utility is the same as the station number set by the GT Designer2 Ethernet setting (the station number of the PLC side Ethernet module) or by the project data.
Confirms the following contents so that the multiple station numbers should not be the same.
1. Confirm the station number of GOT by the utility of GOT.
2. Confirm the station number set by the project data.
3. Confirm the station number set by the Ethernet setting.
(Set by the parameter of GX Developer.)
A device outside the range of QnACPU file registers and the buffer memory was specified.
Correct the monitor device by setting file register of the PLC
CPU.
The path has been switched or timeout occurred in the redundant system.
1. Check the PLC CPU to know if the path has been switched.
2. Check the cable connection status, the communication unit installation status, and the PLC CPU status.
3. This error may occur when the load of the PLC CPU becomes heavier when accessing other stations. In such a case, transfer the data of the other stations to the host station PLC CPU and monitor them at the host.
4. Perform one of the following operations if the PLC scanning time is long: COM instruction/Extension of END processing/Setting of the number of processing times for general data/Data update batch processing.
451
Q redundant system settings and current config. do not match.
Change the Q redundant setting in accordance with the actual
Q redundant CPU system.
460 Communication unit error
480
Communication channel not set. Set channel number on Utility.
1. Reset the power of the GOT.
2. Replace the unit.
Channel (CH.No.1 to 4) to communicate with a controller is not set.
1. After setting the Communication Settings on the GT
Designer2, download it to the GOT.
2. Change the channel assignment in the Communication
Setting on the utility.
*1
20.2 List of Error Message/System Alarm
Error code
Error message Action
Turn the power of the PLC and GOT on again.
Channel
No. storage
481
482
Communication unit not mounted to the slot of active channel.
Too many same units are mounted. Confirm the no of units.
483
Simultaneous mounting of the units are not allowed.
The interface where the channel (CH No.1 to 4) is set does not have a communication unit installed.
1. Install a communication unit to the interface where the channel (CH No.1 to 4) is set.
2. Change assignment of the channel (CH No.1 to 4) in the
Communication Setting.
Units are mounted on the GOT exceeding the maximum number of mountable units.
Check the number of units, and remove unnecessary units.
Two or more units which cannot be mounted on the GOT simultaneously are mounted.
Check the mounted units, and remove unnecessary units.
484
Unit mounted incorrectly.
Move the unit to correct position.
The unit is not mounted on the GOT in the correct position.
Confirm the mounting position of the unit.
485
486
Too many units mounted on GOT. Reduce units.
Communication unit not corresponded to set communication driver.
*1
*1
*1
*1
Units are mounted on the GOT exceeding the maximum number of mountable units.
Check the number of units, and remove unnecessary units.
The communication driver set in the Communication Setting and the communication unit installed on the GOT do not match.
1. Check whether the communication driver set in the
Communication Setting is correct.
2. Check whether any incorrect communication unit has been installed on the GOT.
*1
*1
487
Please turn on the PLC and the GOT again.
488
489
490
491
500
Too many units mounted on GOT. Reduce units.
Inactive channel has been selected at
Communication Settings.
Simultaneous mounting of the units are not allowed.
Too many units mounted on GOT. Reduce units.
Warning! Built-in battery voltage is low.
Units are mounted on the GOT exceeding the maximum number of mountable units.Check the number of units, and remove unnecessary units.
Inactive channel No. has been set in the project data.
1. Check whether any unnecessary channel No. has been set in the project data.
2. Check whether channel Nos. set in the project data are set in the Communication Settings.
Two or more units which cannot be mounted on the GOT simultaneously are mounted.Check the mounted units, and remove unnecessary units.
Units are mounted on the GOT exceeding the maximum number of mountable units.Check the number of units, and remove unnecessary units.
The voltage of the GOT built-in battery is decreased.
Replace the GOT built-in battery.
*1
*1
*1
*1
17
18
19
20
20.2 List of Error Message/System Alarm 20
- 9
Error code
Error message Action
502
Warning! Backlight needs replacement soon.
503
504
505
506
507
Warning! Display section needs replacement soon.
Warning! Touch panel needs replacement soon.
Warning! Built-in Flash
ROM needs replacement soon.
Warning! Backlight needs replacement.
Warning! Display section needs replacement.
The dedicated GS is notifying that the backlight power on addition time has reached 80% or more of the set time.
The GOT can be restored by executing the addition times reset function after replacing the backlight. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition time.
The dedicated GS is notifying that the display section power on addition time has reached 80% or more of the set time.
The GOT can be restored by executing the addition times reset function after replacing the display section. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition time.
The dedicated GS is notifying that the touching count of the touch key has reached 80% or more of the set count number.
The GOT can be restored by executing the addition times reset function after replacing the touch key. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition times.
The dedicated GS is notifying that the built-in flash memory writing times have reached 80% or more of the set times.
The GOT must be replaced. In that case, Data backup and resetting are needed. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition times.
The dedicated GS is notifying that the backlight power on addition time has reached the set time or more.
The GOT can be restored by executing the addition times reset function after replacing the backlight. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition time.
The dedicated GS is notifying that the display section power on addition time has reached the set time or more.
The GOT can be restored by executing the addition times reset function after replacing the display section. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition time.
Channel
No. storage
20
- 10
20.2 List of Error Message/System Alarm
Error code
Error message Action
508
509
Warning! Built-in Flash
ROM needs replacement.
Change the GOT.
510
520
521
522
524
525
530
Warning! Touch panel needs replacement.
Device writing error.
Correct device.
Unable to read/write alarm log files under different projects.
535 Cannot open image file.
536
Clock data input out of range
Insufficient Flash ROM capacity
Insufficient user memory
(RAM) capacity
Unnecessary file deleted to create new file.
Improper monitor device.
Confirm monitor channel.
Image file error or invalid file format.
The dedicated GS is notifying that the touching count of the touch key has reached the set count number or more.
The GOT can be restored by executing the addition times reset function after replacing the touch key. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition times.
The dedicated GS is notifying that the built-in flash memory writing times have reached the set times or more.
The GOT must be replaced. In that case, Data backup and resetting are needed. The GOT can also be restored by turning off the notification signal manually. In such a case, turn it OFF after setting a value greater than the addition times.
The value that is input as clock data is out of the input enabled range.
In this case, the input value is not accepted.
Confirm the input range of the value to be input as clock data, and input the proper value again.
The capacity for the buffering area is insufficient in the build in flash memory
1. Confirm whether there are no mistakes in specified buffering area size.
2. Install the option function board with add-on memory.
The capacity for the buffering area is insufficient in the user memory (RAM)
1. Confirm whether there are no mistakes in specified buffering area size.
2. Install the option function board with add-on memory.
The old file of different contents has been deleted and a new file has been created.
Note that the old file is deleted and the new file is created if the file of the same name with different contents exists when creating files.
When writing in the device, error occurred.
Correct the device.
Unable to read the alarm log file saved by the different project.
Confirm where to store the alarm log file and alarm log file.
The channel of the specified monitor target does not exist or the channel is not the monitor target.
Confirm the monitor target channel of the screen data.
1. Confirm whether the memory card is installed.
2. Confirm whether the CF card access switch of the GOT is
ON.
3. Confirm whether any file exists in the memory card.
1. Confirm whether the image file in the memory card is normal.
2. Confirm whether any image file of invalid format is stored.
Channel
No. storage
17
18
19
20
20.2 List of Error Message/System Alarm 20
- 11
20
- 12
Error code
Error message Action
540
Auto repeat error. Confirm system information.
550 Invalid key code
560
561
570
571
581
582
583
584
585
586
587
Language switch failure.
Install optional functions.
Language switch failure.
Load expansion memory board.
Recipe device points too large.
Capacity shortage of user memory (RAM)
Abnormal Advanced recipe file
Cannot generate
Advanced recipe file.
Unable to save device value to Advanced recipe file.
Advance recipe file save error
Advanced recipe file upload error
Specified Advanced recipe number does not exist.
Specified record number does not exist.
Error occurred while executing the auto repeat function of the touch switch object.
Confirm the followings.
1. Confirm that the other system error has not occurred during auto repeat.
2. Confirm that any error information is not stored in the system information/GS during auto repeat.
The key code input execution trigger was ON with the nontarget key code set in the key code storage device.
Confirm the key code supported by the object where error occurs.
Switched language specifying KANJI other than Japanese without the option OS installed.
Install the option OS.
Switched language specifying a KANJI region other than
Japanese without the option function board with add-on memory installed.
Install the option function board with add-on memory.
The number of the set points of the recipe device exceeds the specified range.
Put the number of the set points of the recipe device within the specified range.
There is no empty area/space in D drive.
Format the D drive in the memory to secure free area.
Advanced Recipe cannot be executed for advanced recipe file with incorrect contents. Delete the advanced recipe file from the memory card.
Cannot generate advanced recipe file. Confirm the following and execute recipe processing again.
1. Confirm whether the memory card is installed.
2. Confirm whether the CF card access switch of the GOT is
ON.
3. Confirm the available memory of the memory card.
Unable to save device value to advanced recipe file.
1. Confirm the write-protection of memory card.
2. Confirm whether the attribute of saving file is for reading only.
An error has occurred during the advanced recipe file writing.
Do not pull the memory card out while the Advanced Recipe is operating.
An error has occurred during the advanced recipe file reading.
Do not pull the memory card out while the Advanced Recipe is operating.
The advanced recipe of non-existing number is about to be executed.
Execute advanced recipe of existing number.
The advanced record of non-existing number is about to be executed.
Execute record of existing number.
Channel
No. storage
20.2 List of Error Message/System Alarm
Error code
Error message Action
588
589
590
591
Cannot save recipe data to read only record.
Recipe device save error.
Recipe file does not exist.
Recipe device upload error. Recipe device value does not exist.
Advanced Recipe error.
Check recipe data.
Saving recipe is about to be executed to the record of which recipe device value cannot be edited.
Make the recipe device value of the record editable with
Advanced Recipe Setting of GT Designer2 or specify the record of which recipe device value can be edited.
Saving recipe is about to be executed to the advanced recipe setting that is set for not using file.
Specify the advanced recipe setting that uses file.
Loading recipe is about to be executed to the record of which recipe device value is not set.
Specify the record of which recipe device value is set.
The advanced recipe setting is not correct.
Confirm the advanced recipe setting of the project data and download it to the GOT again.
595 Logging file error.
596
600
Logging setting does not exist or setting value error.
Unsupported version of printer unit.
601 Printer unit error.
Logging file error.
When collecting data again, delete logging files and management files.
The logging setting specified in the historical trend graph setting does not exist.
Review the historical trend graph setting and specify a logging setting that exists.
The version of OS installed in the GOT is not compatible with the printer unit.
Install the extended function OS (Printer) with the latest GT
Designer2.
The printer unit is installed incorrectly. The built-in flash memory of the printer unit is broken or the guaranteed life has been elapsed.
Check that the printer unit is installed correctly.
When the printer unit has been installed correctly, the built-in flash memory is broken or the guaranteed life has been elapsed. Replace the printer unit with new one.
602
Video/RGB unit not mounted
1. Check if the video/RGB input unit is installed.
2. Check if the GOT used supports video/RGB input.
*1 When an error occurs, "FF H " is stored to the channel No.
Channel
No. storage
17
18
19
20
20.2 List of Error Message/System Alarm 20
- 13
20.3 Troubleshooting in Bus Connection
When connect GOT and PLC CPU with bus connection, and the cause is not clear in "20.2 List of Error
Message/System Alarm", execute the following troubleshooting.
Refer to the following for details concerning the bus connection.
GOT1000 Series Connection Manual
20.3.1 Locating error positions
Explanation regarding the method of specifying the error part.
(Please refer to User's Manual of used PLC CPU for details related to the PLC CPU error and special register.)
(1) How to locate error positions:
(a) Use of peripheral devices
Using the peripheral devices such as GX Developer, check what type of the error occurs on the PLC CPU and, based on the error message on the PLC CPU, check each module and cable for installation and earthing statuses.
20
- 14
(b) Error timing
Check the timing of errors.
1)An error occurs when the power is turned on or immediately after the PLC is reset:
The error may be detected by the initial processing of the PLC CPU.
In this case, because the faulty module may not be identified, use only an END instruction for the sequence program and remove the modules one by one until the error does not occur.
When the error is eliminated after a specific module has been removed, the module may be causing the error.
2) An error occurs after a specific operation or several seconds:
The error may occur in the sequence program. Check the error step where the error may occur and the sequence program in that step.
The sequence program can be diagnosed throughout by merely using an END instruction for the sequence program.
3) An error occurs when a specific device operates:
The mis-operation may be caused by noise.
Check that any signal line such as bus cable is not laid out too close to the operating device.
If the line is too close to the device, separate the line 100 mm or more from the device.
(c) Locating the module where an error occurs:
Based on the PLC CPU error codes and special resister information, locate a specific module where an error occurs.
By the method stated above, correct the sequence program or replace the faulty module with a new one, and check whether the error occurs.
If the error continues to occur, it may have another cause.
Referring to 20.3.2 "Further locating error positions", locate the error position further.
20.3 Troubleshooting in Bus Connection
20.3.1 Locating error positions
20.3.2 Further locating error positions
17
If the function of the PLC cannot be recovered even when the module on which an error occurs is replaced with a new one, the error may be caused by the effect from another module.
Disconnect the extension cables and bus connection cables in order from the modules starting from the module located furthest from the operating position in the system, and check for the status of occurrence of the error each time the cables are disconnected until the error does not occur.
The module or extension cables/bus-connection cables disconnected immediately before the error does not occur are considered to cause the error.
Examples of the ways of further locating error positions are shown below. (When use the extension base unit
QnASCPU)
Example 1: Example 2:
Turn off the power of the GOT.
Turn off the power of the GOT.
Turn off the power of the PLC.
Turn off the power of the PLC.
Disconnect the bus-connection cable
(IN side) from the final stage GOT.
Disconnect the bus-connection cable
(OUT side) from the GOT located one stage before the final stage.
Turn on the power of the PLC.
Turn on the power of the PLC.
Turn on the power of the GOT.
Turn on the power of the GOT.
If an error does not occur, the final stage GOT may be faulty.
If an error does not occur, the final stage GOT and the bus-connection cable before the final stage may be faulty.
Repeat the examples 1 and 2 above to locate error positions.
18
19
20
Notes on narrowing the error part range
1. When disconnecting the extension base units in order, use only an END instruction for the sequence program, and any error resulting from the sequence program will not occur, and the status of occurrence of errors will be obtained easily.
2. When the frequency of occurrence of an error is low, check the error by taking a rather long time with the modules disconnected.
The checks stated above are effective to locate a noise invading route when the mis-operation is caused by noise.
20.3 Troubleshooting in Bus Connection
20.3.2 Further locating error positions
20
- 15
20.3.3 Specific example of troubleshooting
Taking the following system as an example, troubleshooting is shown when PLC CPU error occurred. (When
QnASCPU and the extension base unit are used)
PLC
(main base unit)
GOT 1) GOT 2)
Extension cable
PLC
(extension base unit) Bus connection cable
Bus connection cable
Start
Check the error code/step appearing on the PLC CPU.
(Obtain the status of the error and the location where the error occurs.)
The SP. UNIT DOWN message appears on PLC CPU.
Turn off the power of the GOT.
Turn off the power of the PLC.
Replace the faulty PLC CPU with a new one.
Turn on the power of the PLC.
Turn on the power of the GOT.
The error occurs further (not on PLC CPU).
Turn off the power of the GOT.
Turn off the power of the PLC.
Disconnect the bus-connection cable from the GOT 2) at IN side
(to further locate the error positions).
Turn on the power of the PLC.
Turn on the power of the GOT.
The error occurs further
(not on the GOT 2) (bus connection unit)).
Turn off the power of the GOT.
Turn off the power of the PLC.
Disconnect the bus-connection cable from the GOT 1) at OUT side
(to further locate the error positions).
Turn on the power of the PLC.
Turn on the power of the GOT.
The error will not occur.
The bus-connection cable connecting the GOT 1) to the GOT 2) is judged faulty.
Replace the faulty bus-connection cable with a new one.
End
20
- 16
20.3 Troubleshooting in Bus Connection
20.3.3 Specific example of troubleshooting
20.4 Troubleshooting for Monitoring
This section describes the countermeasures when GOT does not display the monitor screen.
GOT does not display the screen
POWER LED of GOT is off.
YES
Turn on the power supply of GOT
NO
GOT POWER LED is lit in orange
YES
Backlight OFF during screen saving is set.
The setting of screen saving can be set in the GOT utility menu. *1
NO
System Information function (System Signal 1) is set.
NO
YES
The bit of Forced Screen Saver Enable
Signal may be ON. Confirm the bit status.
When "ON", set the bit to "OFF". *2
GOT POWER LED blinks in orange/green
YES
Backlight bulb is blown.
Replace the backlight with a new one.
(
19.5 Backlight Shutoff Detection and
NO
The possible cause is a GOT hardware fault.
Please consult your local Mitsubishi (Electric System) Service center or representative, explaining a detailed description of the problem.
*1 For utility menu, refer to the following.
11. DISPLAY AND OPERATION SETTINGS (GOT SET UP)
*2 For the details of the forced screen saver enable signal, refer to the following.
GT Designer2 Version Screen Design Manual
19
20
17
18
20.4 Troubleshooting for Monitoring 20
- 17
APPENDICES
Appendix 1 External Dimensions
(1) GT1595
397(15.6)
320(12.6)
App
- 1
Appendix 1 External Dimensions
320(12.6)
382(15.0)
Unit:mm(inch)
(2) GT1585
316(12.44)
263(10.35)
250(9.84)
301(11.85)
Unit: mm (inch)
19
20
17
18
Appendix 1 External Dimensions App
- 2
(3) GT157
303(11.93)
252(9.92)
222(8.74)
288(11.34)
Unit: mm (inch)
App
- 3
Appendix 1 External Dimensions
(4) GT156
241(9.49)
175.5(6.91)
175.5(6.91)
226(8.90)
Unit: mm (inch)
19
20
17
18
Appendix 1 External Dimensions App
- 4
(5) GT155
167(6.57)
110(4.33)
110(4.33)
152(5.98)
Unit: mm (inch)
App
- 5
Appendix 1 External Dimensions
(6) Depth dimension when an extension unit is installed
GOT rear face
100 (3.94) or more
Extension unit
B
R
C
A
* D * 1
Other equipment
17
GOT side face
GOT type Dimension of *
GT1595 55 (2.17)
GT1585 46 (1.81)
GT157
43 (1.69)
GT156
46 (1.81)
GT155 54 (2.13)
Unit: mm (inch)
18
19
(a) GT1595
Model name
GT15-QBUS,
GT15-QBUS2
GT15-ABUS,
GT15-ABUS2
GT15-75QBUSL,
GT15-75QBUS2L
GT15-75ABUSL,
GT15-75ABUS2L
GT15-RS2-9P*2,
GT15-RS4-9S*2
GT15-RS4-TE*2
GT15-J71E71-100
GT15-J71LP23-25
GT15-J71BR13
GT15-J61BT13
GT15-75J71LP23-Z
GT15-75J71BR13-Z
GT15-75J61BT13-Z
GT15-PRN
A
95(3.74)
73.5(2.89)
B
95(3.74)
73.5(2.89)
123(4.84)
72.5(2.85)
33.5(1.32)
38(1.5)
*2
*4
87.5(3.44)
47(1.85)
*4
130(5.12)
80(3.15)
52(2.05) 123(4.84)
C
0(0)
-
*4
0
0
*4
21(0.83)
0(0)
45.5(1.79)
21(0.83)
D
21(0.83)
R
(bending radius of the cable)
55(2.17)
36(1.42)
20
8(0.32)
55(2.17)
36(1.42)
30(1.18)
24(0.95)
*4
30(1.18)
28(1.1)
*4
50(1.97)
18(0.71)
Unit: mm (inch)
Appendix 1 External Dimensions App
- 6
(b) GT1585
Model name
GT15-QBUS,
GT15-QBUS2
GT15-ABUS,
GT15-ABUS2
GT15-75QBUSL,
GT15-75QBUS2L
GT15-75ABUSL,
GT15-75ABUS2L
GT15-RS2-9P*2,
GT15-RS4-9S*2
GT15-RS4-TE*2
GT15-J71E71-100
GT15-J71LP23-25
GT15-J71BR13
GT15-J61BT13
GT15-75J71LP23-Z
GT15-75J71BR13-Z
GT15-75J61BT13-Z
GT15-PRN
GT15V-75V4*5
GT15V-75R1*5
GT15V-75V4R1*5
GT15V-75ROUT*5
A
95(3.74)
73.5(2.89)
B C
28(1.1)
8.5(0.34)
D
18(0.71)
R
(bending radius of the cable)
55(2.17)
36(1.42)
55(2.17)
36(1.42)
95(3.74)
73.5(2.89)
28(1.1)
8(0.32)
5(0.2)
72.5(2.85)
33.5(1.32)
38(1.5)
*2
*4
87.5(3.44)
47.0(1.85)
*3
64(2.52)
80(3.15)
9.5(0.37)
0(0)
-
*4
23.5(0.93)
0
*3
18(0.71)
16(0.63)
45.5(1.79)
52(2.05)
132(5.2)
77(3.03)
BNC:
182(7.17)
RGB:
77(3.03)
77(3.03)
0(0)
68(2.68)
13(0.51)
BNC:68
(2.68)
RGB:13
(0.51)
13(0.51)
18(0.71)
30(1.18)
24(0.95)
*4
30(1.18)
28(1.1)
*3
50(1.97)
18(0.71)
20(0.79)
32(1.26)
BNC:20(0.79)
RGB:32(1.26)
32(1.26)
Unit: mm (inch)
App
- 7
Appendix 1 External Dimensions
(c) GT157
Model name
GT15-QBUS,
GT15-QBUS2
GT15-ABUS,
GT15-ABUS2
GT15-75QBUSL,
GT15-75QBUS2L
GT15-75ABUSL,
GT15-75ABUS2L
GT15-RS2-9P*2,
GT15-RS4-9S*2
GT15-RS4-TE*2
GT15-J71E71-100
GT15-J71LP23-25
GT15-J71BR13
GT15-J61BT13
GT15-75J71LP23-Z
GT15-75J71BR13-Z
GT15-75J61BT13-Z
GT15-PRN
GT15V-75V4*6
GT15V-75R1*6
GT15V-75V4R1*6
GT15V-75ROUT*6
A
95(3.74)
73.5(2.89)
B
17
C
42(1.65)
22.5(0.89)
D
21(0.83)
R
(bending radius of the cable)
55(2.17)
36(1.42)
18
95(3.74) 42(1.65) 8(0.32)
73.5(2.89)
72.5(2.85)
33.5(1.32)
38(1.5)
*2
*4
87.5(3.44)
47(1.85)
*4
80(3.15)
22(0.87) 8(0.32)
50(1.97)
47(1.85)
23.5(0.93)
0(0)
-
*4
37.5(1.48)
0
*4
21(0.83)
45.5(1.79)
33(1.3)
52(2.05)
132(5.2)
77(3.03)
BNC:132
(5.2)
RGB:77
(3.03)
77(3.03)
50(1.97)
47(1.85)
2(0.08)
85(3.35)
30(1.18)
BNC:85
(3.35)
RGB:30
(1.18)
30(1.18)
21(0.83)
55(2.17)
36(1.42)
30(1.18)
24(0.95)
*4
30(1.18)
28(1.1)
*4
50(1.97)
18(0.71)
20(0.79)
32(1.26)
BNC:20(0.79)
RGB:32(1.26)
32(1.26)
Unit: mm (inch)
19
20
Appendix 1 External Dimensions App
- 8
(d) GT156
Model name
GT15-QBUS,
GT15-QBUS2
GT15-ABUS,
GT15-ABUS2
GT15-75QBUSL,
GT15-75QBUS2L
GT15-75ABUSL,
GT15-75ABUS2L
GT15-RS2-9P*2,
GT15-RS4-9S*2
GT15-RS4-TE*2
GT15-J71E71-100
GT15-J71LP23-25
GT15-J71BR13
GT15-J61BT13
GT15-75J71LP23-Z
GT15-75J71BR13-Z
GT15-75J61BT13-Z
GT15-PRN
A
95(3.74)
73.5(2.89)
B C
47(1.85)
27.5(1.08)
D
23(0.91)
R
(bending radius of the cable)
55(2.17)
36(1.42)
95(3.74)
73.5(2.89)
72.5(2.85)
33.5(1.32)
38(1.5)
*3
*4
87.5(3.44)
47(1.85)
*4
80(3.15)
47(1.85)
10(0.39)
27(1.12)
45(1.77)
42(1.65)
28.5(1.12)
0(0)
-
*4
45.5(1.79)
5(0.2)
*4
23(0.91)
47.5(1.87)
38(1.5)
52(2.05) 45(1.77) 7(0.28) 23(0.91)
55(2.17)
36(1.42)
30(1.18)
24(0.95)
*4
30(1.18)
28(1.1)
*4
50(1.97)
18(0.71)
Unit: mm (inch)
App
- 9
Appendix 1 External Dimensions
(e) GT155
Model name A B C D
R
(bending radius of the cable)
GT15-QBUS,
GT15-QBUS2
GT15-ABUS,
GT15-ABUS2
GT15-75QBUSL,
GT15-75QBUS2L
GT15-75ABUSL,
GT15-75ABUS2L
GT15-RS2-9P*2,
GT15-RS4-9S*2
GT15-RS4-TE*2
GT15-J71E71-100
GT15-J71LP23-25
GT15-J71BR13
GT15-J61BT13
GT15-PRN
95(3.74)
73.5(2.89)
95(3.74)
73.5(2.89)
72.5(2.85)
16.2(0.64)
78.8(3.1)
57.3(2.26)
78.8(3.1)
57.3(2.26)
56.3(2.22)
23(0.91)
10(0.39)
55(2.17)
36(1.42)
55(2.17)
36(1.42)
30(1.18)
33.5(1.32)
38(1.5)
*3
87.5(3.44)
47(1.85)
52(2.05)
17.3(0.68)
21.8(0.86)
*3
71.3(2.81)
30.8(1.18)
35.8(1.41)
23(0.91)
24(0.95)
*3
30(1.18)
28(1.1)
18(0.71)
Unit: mm (inch)
*1 The depth dimension is as follows when units allowing multiple stages are installed.
GOT model name
GT1595
GT1585
GT157
2-stage
42.5(1.67)
39.5(1.56)
42.5(1.67)
3-stage
64.5(2.54)
61.5(2.42)
64.5(2.54)
GT156 44.5(1.67) 66.5(2.62)
GT155 44.5(1.67) 66.5(2.62)
Unit: mm (inch)
*2 For cables prepaired by the user, the dimensions are different.
*3 This dimension is applied when the external dimension of cable connector is 21.5mm. (Refer to the following figure.) The dimension varies depending on the connector used.
17
18
19
20
GT15-J71E71-100
Cable connector
*4 For cable details of GT15-75J71LP23-Z (Optical loop unit), consult the local office of Mitsubishi Electric System &
Service, Co., Ltd.
*5 GT1585V-S
*6 GT1575V-S
Appendix 1 External Dimensions App
- 10
(7) External dimensions of the communication cable
External dimensions of the bus connection cable connector
Cable model
GT15-QC B
GT15-QC BS
GT15-C NB
GT15-AC B
GT15-A1SC B
GT15-A1SC NB
GT15-J2C B
GT15-370C B-S1
GT15-C EXSS-1
GT15-C BS
GT15-EXCNB
Cable length (m(ft.))
0.6(2), 1.2(3.9),3(10),5(20), 10(33)
15(49),20(66),25(82),30(98),35(120)
1.2(3.9),3(10),5(20)
0.6(2), 1.2(3.9),3(10),5(20)
0.7(2), 1.2(3.9),3(10) 5(20)
0.45(1.5),1.2(3.9),3(10),5(20)
1(3)
1.2(3.9),2.5(8.2)
10.6(34.8),20.6(67.6),30.6(100)
10(33),20(66),30(98)
0.5(2)
Dimensions (mm) and shape of the connector
GOT side
Fig. 3
PLC side
Fig. 3
Fig. 3
Fig. 1
Fig. 2
Fig. 1
Fig. 4
Fig. 1
Fig. 4
Fig. 4
Fig. 4
Fig. 5
Fig. 3
Fig. 2
Fig. 2
Fig. 1
Fig. 2
Fig. 6
Fig. 4
Fig. 4
Fig. 4
Fig. 4
*1: The GT15-C EXSS/GT15-C BS cable has a grounding wire (1 m).
Be sure to connect the wire to control panels.
*2: The GT15-C EXSS-1 is the set product consisting of (GT15-EXCNB+GT15-C BS). (Refer to Fig. A)
Fig.A
Fig.4
PLC side
Fig.5
(GT15-EXCNB) buffer circuit cable
Fig.4
GOT side
Fig.4
(GT15-C BS) extension cable
33.0 (1.30)
11.5
(0.45)
Fig.1
Fig.2
60.0 (2.36)
20.0
(0.79)
Fig.3
35.0 (1.38)
10.0
(0.39)
Fig.4
33.0 (1.30)
12.4
(0.49)
Fig.5
75.0 (2.95)
20.5
(0.81)
Fig.6
55.3 (2.18)
6.0
(0.24)
5.0
(0.2)
2.2 (0.1)
Unit : mm (inch)
App
- 11
Appendix 1 External Dimensions
Appendix 2 Confirming of Versions and Conformed standards
17
1
Rating plate
The GOT hardware version, function version, and the standards conformed by a GOT can be confirmed at the rating plate on the GOT rear face.
18
B
A A
Hardware version
B
Function version
Conformed standard
Back light model The applicable back light model is described
2
Packing box
The standards conformed by a GOT can be confirmed by the label on the packing box.
Note that the position of the label differs depending on the model or shipment date.
19
20
The conformed standards
(such as CE) are described.
Appendix 2 Confirming of Versions and Conformed standards App
- 12
Appendix 3 Usage Condition of Utility Function
p Display
The function which can be used differs according to the GOT type.
Moreover, there are the function which can be set with drawing software and the function which cannot be set.
Item
Detail settings
Functions overview
: Applicable : Not applicable : Not required
GT15
GT Soft
GOT
1000
GT11
Drawing
Setting
Setting of channel number for the communication interface and assignment of communication driver
Setting of communication parameter
Sequence program protection key word setting (When FX series PLC is connected)
Sequence program protection key word deleting (When FX series PLC is connected)
Sequence program protection status cancel (When FX series PLC is connected)
Setting of opening screen time
Setting of screen saving time
Setting of screen saving back light ON/OFF
Switching of message language (Japanese/English/
Chinese (Simplified)/Chinese (Traditional)/Korean/German)
Battery alarm display ON/OFF setting
Human sensor Effective/Invalid setting
*2
Sensor detect level setting
Displaying sensor detect time
Sensor off delay setting
Brightness, contrast
Liquid crystal intensity setting
Liquid crystal contrast setting
(Continued to next page)
App
- 13
Appendix 3 Usage Condition of Utility Function
Operation
Item Functions overview
Security setting *3
Menu call key
Touch panel calibration
Correcting touch position reading error
: Applicable : Not applicable : Not required
GT15
GT Soft
GOT
1000
GT11
Drawing
Setting
Setting of buzzer volume
Window move buzzer
Setting of key sensitivity
Displaying of key reaction speed
Changing of security level (object unit security password input)
Setting of the utility call key
17
18
19
20
Q/QnA ladder monitor
Transparent mode settings
Setting of data storage location for the MELSEC-Q/QnA ladder monitoring function
Setting communication target channel Nos. when the FA transparent function is used.
Video/RGB Setting
Video Unit Settings Setting of the video input signal and resolution
Video Display
Settings
RGB Display
Settings
Setting of the captive area size for each video channel, the color tone, contrast, brightness, and color intensity
Setting of the RGB clock phase, horizontal screen position, and vertical screen position
Selection of base clock
Time setting & display
*3
Display current time of clock.
Set current time of clock.
Display of battery status
Appendix 3 Usage Condition of Utility Function App
- 14
Item
OS information
Project Information
Functions overview
Installing OS
Uploading OS
Property display of OS (Kind, version, and date)
Data check of system file (OS)
Downloading project file
: Applicable : Not applicable : Not required
GT15
GT Soft
GOT
1000
GT11
Drawing
Setting
Uploading project file
Project file deleting
Copying project file (A drive A drive)
Property display of project file (Date, version and screen title)
Data check of project file
(Continued to next page)
App
- 15
Appendix 3 Usage Condition of Utility Function
Item Functions overview
: Applicable : Not applicable : Not required
GT15
GT Soft
GOT
1000
GT11
Drawing
Setting
Deleting alarm log file
Copying alarm log file
Alarm information G1A CSV conversion (Convert from G1A of the alarm file to CSV)
G1A TXT conversion (Convert from G1A of the alarm file to TXT)
Historical graph display
Displaying historical graph of alarm file
Tally graph display Tally graph display of alarm file
G1P CSV conversion (Convert from G1P of the advanced recipe file to CSV)
G1P TXT conversion (Convert from G1P of the advanced recipe file to TXT)
Deleting advanced recipe file or folder
Advanced Recipe information Copying advanced recipe file
Moving advanced recipe file or folder
Changing advanced recipe folder name
Creating a new advanced recipe folder or file
Loading record data
Advanced Recipe
Record List
Saving record data
Matching record data
Deleting device data
17
18
19
20
Logging information file to CSV) file to TXT)
Deleting logging file or folder
Copying logging file
Moving logging file
Changing logging file name
Creating a new logging folder or file
(Continued to next page)
Appendix 3 Usage Condition of Utility Function App
- 16
Item
Operation log information
Hard copy information
Memory card format
Memory information
Special data information
System monitor
Ladder monitor
A List editor
FX list editor
Debug
Intelligent module monitor
Network monitor
Motion monitor
Servo amplifier monitor
CNC monitor
Functions overview
: Applicable : Not applicable : Not required
GT15
GT Soft
GOT
1000
GT11
Drawing
Setting
G1O CSV conversion (Conversion from G1L of operation log file to CSV)
G1O TXT conversion (Conversion from G1O of logging file to TXT)
Deletion of a operation log file or folder
Copying of an operation log file
Moving of an operation log file
Changing of an operation log file name
Creating of a new operation log folder
Displaying and searching of the list of operation logs
Deleting hard copy file
Copying hard copy file
Formatting memory card
Displaying memory space of GOT
Displaying file/folder name, data size and creation date and time
Deleting file or folder of special data
Checking file of special data
Downloading special data written in the A drive (Standard
CF card) to C drive (Built-in flash memory)
Monitoring and testing PLC devices, monitoring and changing values in the special module buffer memory
Displaying ladder monitor, executing hard copy
Changing sequence programs or parameters of the ACPU
Editing sequence programs of the FXCPU in a list
Monitoring or changing data of intelligent function module buffer memory on the dedicated screen, monitoring signal statuses of an I/O module
Monitoring the network status of MELSECNET/H,
MELSECNET/10, MELSECNET (II), MELSECNET/B
Monitoring servos of motion controller CPU (Q series), setting parameters
Executing various monitoring functions of servo amplifier, changing parameters, testing operations
Executing position display monitor, alarm diagnosis monitor, tool offset/param, program monitor, etc. equivalent to the
MELDAS dedicated display
(Continued to next page)
App
- 17
Appendix 3 Usage Condition of Utility Function
Item
Memory check
Drawing check
Functions overview
: Applicable : Not applicable : Not required
GT15
GT Soft
GOT
1000
GT11
Drawing
Setting
A drive (Standard CF card) memory check
C drive (Built-in Flash Memory) memory check
D drive (Built-in SRAM) memory check
Liquid crystal missing bits check, color check, drawing check, display check and overlapping display check
Installed fonts check Font check
Touch panel check Touch panel operation check
Self check
Connecting target check
I/O check
Self-loopback check
*5
NETWK unit status display
Monitoring of the LED status display of the MELSECNET/H communication unit and CC-Link communication unit
(GT15-J61BT13)
Displaying of error information etc.
System alarm display
GOT start time
Displaying GOT errors, CPU errors, network errors
Resetting GOT errors
Displaying GOT start date and time, current time, accumulated operating hours
Clean Display the screen to clean the display section.
Black light maintenance timing setting.
Maintenance timing setting
*6
Display section maintenance time notification period setting.
Setting of touch key maintenance notification count.
Setting of Built-in flash memory maintenance notification count.
Addition times reset
*6
Function to reset the value of the backlight maintenance notification time, display section maintenance notification time, touch key maintenance notification count, built-in flash memory maintenance notification count which has been additioned for the maintenance report function.
*1: It is necessary to carry out the following items by GT Designer2
• Installation of communication driver
• Allocation of channel number and communication driver
*2: The following display and operations are not allowed with the GT11.
• Chinese (Traditional) cannot be displayed.
• Japanese and Chinese (Simplified) cannot be selected on the GOT screen.
(Japanese and Chinese (Simplified) fonts cannot be installed at the same time.)
*3: It is necessary to set the security level by GT Designer2
*4: If necessary please install the battery.
*5: It is necessary to install the RS-232 connector for the test. (
*6: It is necessary to install the option function board and the battery.
17
18
19
20
Appendix 3 Usage Condition of Utility Function App
- 18
Appendix 4 Transportation Precautions
When transporting lithium batteries, make sure to treat them based on the transport regulations.
Appendix 4.1 Relevant models
The battery for the GOT1000 Series is classified as shown in the table below.
Product name
Battery for GOT1000 Series
Model
GT15-BAT
Description
Lithium battery
Handled as
Non-dangerous goods
Appendix 4.2 Transportation guidelines
Products are packed properly in compliance with the transportation regulations prior to shipment. When repacking any of the unpacked products to transport it to another location, make sure to observe the IATA
Dangerous Goods Regulations, IMDG Code and other local transportation regulations.
For details, please consult your transportation company.
App
- 19
Appendix 4 Transportation Precautions
Appendix 5 List of Functions Added by GT Designer2
Version Upgrade (For GOT1000 Series)
17
The following describes the functions added by version upgrade of the GT Designer2 Version2.32J.
For using the following functions, use GT Designer2 or OS of the corresponding version or later.
1
Added GOT main unit /Communication unit
Target Models
GT1595-XTBA
GT1595-XTBD
GT1585-STBD
GT1585V-STBA
GT1575-STBD
GT1575V-STBA
GT1575-VTBD
GT1575-VNBA, GT1575-VNBD, GT1572-VNBA, GT1572-VNBD
GT1565-VTBD
GT1562-VNBA, GT1562-VNBD
GT1555-QTBD, GT1555-QSBD, GT1550-QLBD
GT1155-HS-QSBD to GT1150-HS-QLBD
GT SoftGOT1000
GT15-QBUS(2), GT15-ABUS(2), GT15-RS2-9P, GT15-RS4-9S, GT15-RS4-TE
Version of GT
Designer2
2.18U
2.32J
2.18U
2.32J
2.18U
2.32J
2.18U
2.18U
2.18U
2.18U
2.32J
2.18U
2.27D
2.18U
Version of OS
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
-
Standard monitor OS [02.02.**]
Communication driver
For communication drivers used in each connection, use [02.02.**] or above.
2
Added connection types
Item
Bus connection
Direct connection to CPU
Computer link connection
MELSECNET/H connection (PLC to PLC network)
Description
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to FX3U series
Supporting automatic system switching for QCPU redundant system
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to MELSECNET/H
(PLC to PLC network)
Version of GT
Designer2
2.09K
2.09K
2.18U
2.32J
2.09K
2.25B
2.32J
Version of OS
GT
15
GT Soft
GOT1000
GT
11
Communication driver
Bus(Q) [01.02.**]
Communication driver
A/QnA/QCPU,QJ71C24 [01.02.**]
Communication driver
MELSEC-FX[02.02.**]
Communication driver
A/QnA/QCPU, QJ71C24,
MELDAS C6* [03.00.**]
Communication driver
A/QnA/QCPU,QJ71C24 [01.02.**]
-
Communication driver
MELSECNET/H [03.00.**]
(Continued to next page)
18
19
20
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
App
- 20
Item Description
MELSECNET/10 connection (PLC to PLC network)
CC-Link connection
(Intelligent device station)
Supporting connection to MELSECNET/
10 PLC to PLC connection)
Supporting connection to Q172HCPU,
Q173HCPU
Supporting automatic system switching for QCPU redundant system
Supporting connection to CC-Link
(Intelligence device station)
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to CC-Link Ver.2
CC-Link connection (Via
G4)
Ethernet connection
OMRON PLC connection
Supporting connection to CC-Link (Via
G4)
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to the Ethernet
Supporting connection to Q172HCPU,
Q173HCPU
Supporting automatic system switching for QCPU redundant system
Extended device range monitored
(The setting of TIM or CNT up to 4095, etc.)
Supporting delay time setting
Version of GT
Designer2
2.09K
2.32J
2.09K
2.32J
2.09K
2.09K
2.32J
2.09K
2.27D
Version of OS
Communication driver
MELSECNET/10 [01.02.**]
Communication driver
MELSECNET/10 [03.00.**]
Communication driver
CC-LINK(ID) [01.02.**]
Communication driver
CC-Link Ver2 (ID) [03.00.**]
Communication driver
CC-LINK(G4) [01.02.**]
KEYENCE PLC connection
SHARP PLC connection
TOSHIBA PLC connection
JTEKT PLC connection
Supporting connection to KEYENCE PLC
Supporting connection to SHARP PLC
Supporting connection to TOSHIBA PLC
Supporting connection to JTEKT PLC
HITACHI PLC connection
MATSUSHITA
PLC connection
Supporting connection to HITACHI PLC
Supporting connection to MATSUSHITA
PLC
Supporting connection to FPΣ
2.18U
2.09K
2.09K
2.32J
2.09K
2.09K
2.18U
GT
15
GT Soft
GOT1000
GT
11
Communication driver
QJ71E71/AJ71(Q)E71
[01.02.**]
Communication driver
QJ71E71/AJ71(Q)E71 [03.00.**]
Communication driver
OMRON SYSMAC
[01.02.**]
Communication driver
OMRON SYSMAC
[02.04.**]
Communication driver
KEYENCE KV700/1000 [02.02.**]
Communication driver
SHARP JW [01.02.**]
Communication driver
TOSHIBA PROSEC T/V
[01.02.**]
Communication driver
JTEKT TOYOPUC-PC [03.00.**]
Communication driver
HITACHI HIDIC H [01.02.**]
HITACHI HIDIC H (Protocol 2)
[01.02.**]
Communication driver
MATSUSHITA MEWNET-FP
[01.02.**]
Communication driver
MATSUSHITA MEWNET-FP
[02.02.**]
(Continued to next page)
App
- 21
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
Item Description
YOKOGAWA PLC connection
Supporting connection to STARDOM
Allen-Bradley PLC connection
SIEMENS PLC connection
Microcomputer connection
Can use L device by MicroLogix 1000/
1200/1500 series
Supporting connection to SIEMENS S7-
200 series
Supporting XON/XOFF control
Supporting interrupt extension
OMRON temperature controller connection
FUJI temperature controller connection
YAMATAKE temperature controller connection
RKC temperature controller connection
Inverter connection
Supporting connection to OMRON temperature controller
Supporting connection to FUJI temperature controller
Supporting connection to YAMATAKE temperature controller
Supporting connection to RKC temperature controller
Supporting connection to inverter
Version of GT
Designer2
2.32J
2.18U
2.18U
2.32J
Version of OS
Communication driver
YOKOGAWA STARDOM/FA-M3
[03.00.**]
Communication driver
AB MicroLogix [02.02.**]
Communication driver
SIEMENS S7-200 [02.02.**]
Communication driver
Computer [03.00.**]
2.18U
Communication driver
OMRON THERMAC / INPANEL
NEO [02.02.**]
2.32J
2.18U
2.18U
2.18U
Communication driver
FUJI PXR/PXG/PXH [03.00.**]
Communication driver
YAMATAKE SDC/DMC [02.02.**]
CNC connection Supporting connection to CNC
Servo amplifier connection
Supporting connection to servo amplifier
Supporting connection to MELSERVO-J3 series
Supporting writing to the E
2
PROM area in parameter writing
Supporting the point table setting for MR-
J2S-*CP
Supporting the test run mode
Bar code reader connection
Supporting connection to barcode reader
Supporting connection to 2D-code reader
2.18U
2.09K
2.18U
2.32J
2.32J
2.32J
2.09K
2.27D
GT
15
GT Soft
GOT1000
GT
11
Communication driver
RKC SR Mini HG(MODBUS)
[02.02.**]
Communication driver
FREQROL 500/700 [02.02.**]
Communication driver
A/QnA/QCPU, QJ71C24,
MELDAS C6 * [02.02.**]
A/QnAQJ71E71/AJ71(Q)E71
[02.02.**]
MELSECNET/10 [02.02.**]
CC-Link(ID) [02.02.**]
Communication driver
MELSERVO-J2S/M [01.02.**]
Communication driver
MELSERVO-J3,J2S/M [02.02.**]
Communication driver
MELSERVO-J3, J2S/M [03.00.**]
Communication driver
MELSERVO-J3, J2S/M [03.00.**]
Communication driver
MELSERVO-J3, J2S/M [03.00.**]
Extended function OS
Barcode [01.02.**]
Extended function OS
Barcode [02.04.**]
(Continued to next page)
17
18
19
20
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
App
- 22
Item
Printer connection
Description
Supporting connection to printer
Supporting the FA transparent function via
USB
Version of GT
Designer2
2.27D
2.09K
Version of OS
Extended function OS
Printer [02.04.**]
GT15
Standard monitor OS [01.02.**]
GT11
Standard monitor OS [01.02.**]
Boot OS [01.02.**.C]
FA transparent
MT Developer (via USB), MR Configurator and FR Configurator are added as compatible software.
GX Configuration and PX Developer are added as compatible software.
2.27D
2.32J
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Multiple-GT11 connection
Connection with multiple GT11s 2.09K
Standard monitor OS [01.02.**]
GT
15
GT Soft
GOT1000
GT
11
App
- 23
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
3
Added GT Designer2 functions
Item Description
Ethernet download Downloading the project data via Ethernet
Basic comment, comment group
Library workspace
Copying comments in column unit on
Basic Comment or Comment Group, etc.
Improved library structure and added import function
Improved user library structure, expanded the user library registration capacity, copying the figure data to the user library, etc.
Project data matching
Copy ON
Copy OFF
Data View
Batch Edit
OFF
Import, Export
ON
Screen Preview
Wizard
Screen script, project script
Auxiliary setting
Expansion /
Reduction
Addition of fixed frame figure
Matching project data stored in GOT and project data opened on GT Designer2
Enables copying of only characters in lamp display, touch switch and comment display.
Enables editing of the settings for advanced alarm observation (advanced user alarm), alarm history, advanced recipe function and recipe function in the
CSV file format and other format.
Enables printing of header and footer
Enables changing of the settings for the respective objects in grouped objects
Enables global replacement of channel
No.
Enables checking for security level switching and language switching in image after switching
Wizard for setting the GOT type, controller type and communication settings when creating a new project
Settings on the Script Edit dialog are available for screen script and project script.
Setting of maintaining screen numbers of the screens being displayed (System
Information) during screen switching is added.
Supports expansion/reduction when multiple objects and shapes are selected.
Version of GT
Designer2
2.09K
Version of OS
Standard monitor OS [01.02.**]
2.09K
2.09K
2.18U
2.18U
2.09K
2.18U
2.18U
2.18U
2.18U
2.18U
2.18U
2.18U
2.27D
2.27D
2.32J
-
-
-
-
Standard monitor OS [01.02.**]
-
-
-
-
-
-
-
-
-
-
GT
15
GT Soft
GOT1000
GT
11
17
18
19
20
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
App
- 24
Figure
4
Added common settings/object functions
Item Description
JPEG file reading enabled
Version of GT
Designer2
2.09K
Version of OS
Standard monitor OS [01.02.**]
2.09K
Standard monitor OS [01.02.**]
Text
Standard font
Windows fonts applicable
Enables specifyng of background color.
• Japanese 12dot
• Japanese 16dot Gothic
• Japanese 16dot Mincho
• Japanese (supporting Europe) 12dot
• Japanese (supporting Europe) 16dot
Gothic
• Japanese (supporting Europe) 16dot
Mincho
• Chinese (Simplified) 12dot
• Chinese (Simplified) 16dot Mincho
• Chinese (Simplified) (supporting
Europe) 12dot
• Chinese (Simplified) (supporting
Europe) 16dot Mincho
2.32J
2.04E
2.27D
Standard monitor OS [03.00.**]
Standard monitor OS [01.01**]
Standard monitor OS [02.04.**]
Boot OS [G]
KANJI Region Supporting Chinese (Traditional) 2.18U
Standard monitor OS [02.02.**]
Option OS
Standard font (Chinese:
Traditional)
[02.02.**]
GOT internal device
GOT Type
Station No.
Switching Function
System alarm information, printer status information, and GT SoftGOT1000 end device are added.
Supporting vertical installation type display
Designation of the channel No. for which station No. is switched is possible.
2.27D
2.18U
2.18U
Standard monitor OS [02.04.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Language
Switching Device
Language switching device can be used.
2.00A
2.18U
Standard monitor OS [01.00.**]
Standard monitor OS [02.02.**]
Password Setting
System information
Password can be set for the connection of motion controller and servo amplifier.
System information of report function and print are added.
D drive automatic recovery status notification signal is added.
2.18U
2.27D
2.32J
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
App
- 25
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
Item
GOT Setup
Clock Setting
Startup Logo
Handy GOT
Setting
Dialog window
Operation log
Comment
Key Window
Object rename
Lamp
Touch switch
Numerical input
ASCII Display /
ASCII Input
Description
In clock management, both adjust and broadcast can be set.
Data save device of MELSEC-Q / QnA ladder monitor data can be set at GT
Designer2.
Time setting for call key ON until the start up of utility can be set (for 1-point pressing).
Alarm can be set to be displayed in system language switching or battery drops.
Designation of the channel No. used for adjusting and broadcasting is possible.
Function for setting any screen for the
GOT startup screen
Setting of the grip switch LED of handy
GOT
System messages to be displayed on
GOT can be customized or created by the user.
Version of GT
Designer2
2.18U
Version of OS
Standard monitor OS [02.02.**]
2.18U
2.18U
2.27D
2.18U
2.09K
2.18U
2.27D
-
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
Standard monitor OS [02.02.**]
Standard monitor OS [01.02.**]
Boot OS [01.02.**.C]
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
Function to save the GOT operation performed by the user as a history
Comment group can be used.
2.32J
2.00A
2.18U
Standard monitor OS [03.00.**]
Option OS
Operation Log [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
User defined key window display can be switched in synchronization with the language switching device.
In the user defined key window, input range (maximum value) and input range
(minimum value) are displayed.
Function to allow setting of object name
Windows fonts applicable
Windows fonts applicable
Data change switch can be used.
Setting for displaying an input value at the input target object position is possible.
Function to store NULL (0x00) at the end of input characters
2.18U
2.18U
2.32J
2.09K
2.09K
2.32J
2.32J
2.18U
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [01.02.**]
Standard monitor OS [01.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Function to convert characters input in
Kana into Kanji
2.18U
2.27D
Standard monitor OS [02.02.**]
Option OS
KANA KANJI (JP) [02.02.**]
Standard monitor OS [02.04.**] Alignment setting is added.
Setting for displaying an input value at the input target object position is possible.
2.32J
Standard monitor OS [03.00.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
17
18
19
20
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
App
- 26
Item
User alarm
Alarm history
Advanced Alarm
Parts Display
Parts Movement
Panelmeter
Trend graph
Line graph
Bar graph
Statistics graph
Scatter graph
Historical Trend
Graph
Logging Function
Description
Number of alarms settable for GT11 is extended to the same as GT15 (Up to
8192 alarms).
Number of alarms settable for GT11 is extended to the same as GT15 (Up to
3072 alarms).
Function to save alarm history data to the
A drive (standard CF card) for GT11
Function to display the cursor by touching an alarm, and function to output the corresponding comment No. to a device
Function for detecting alarm even at the fall of bit device with Advanced User
Alarm
Function for using BMP/JPEG data in memory card as parts
Version of GT
Designer2
2.27D
2.27D
2.27D
2.32J
2.09K
2.09K
2.09K
2.09K
Windows fonts applicable
Up to 101 points can be set for scale, value number.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Function to display the data collected by the logging function in trend graph format
Function to collect and accumulate device values
2.27D
2.27D
2.32J
2.27D
2.32J
2.27D
2.32J
2.27D
2.32J
2.27D
2.32J
2.18U
2.18U
Version of OS
Standard monitor OS [02.04.**]
Standard monitor OS [02.04.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [01.02.**]
Standard monitor OS [01.02.**]
Standard monitor OS [01.02.**]
Standard monitor OS [01.02.**]
Standard monitor OS [02.04.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.01.**]
GT
15
GT Soft
GOT1000
GT
11
Standard monitor OS [02.02.**]
Option OS
Logging [02.02.**]
(Continued to next page)
App
- 27
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
Item
Recipe function
Advanced Recipe
Report function
Description
Number of devices settable for one recipe in GT11 is extended to the same as GT15
(Up to 8192 devices).
Function to save recipe data of GT11 in
CSV file format
Version of GT
Designer2
2.27D
2.27D
Function to save recipe data to the A drive
(standard CF card) for GT11
The extended function of the existing recipe function
Function to print the colleted data
Hard copy function Compatible with the printer output
2.27D
2.09K
2.27D
2.27D
2.09K
Version of OS
Standard monitor OS [02.04.**]
Option OS
Recipe [02.04.**]
Standard monitor OS [02.04.**]
Option OS
Recipe [02.04.**]
Standard monitor OS [02.04.**]
Option OS
Recipe [02.04.**]
Standard monitor OS [01.02.**]
Option OS
Advanced recipe [01.02.**]
Standard monitor OS [02.04.**]
Extended function OS
Report [02.04.**]
Standard monitor OS [02.04.**]
Extended function OS
Printer [02.04.**]
Standard monitor OS [01.00.**]
Barcode
Video display
Function for loading the data read with bar cord reader to PLC CPU
Number of settable devices is extended from 32 to 1024 points.
Space (0x20) or NULL (0x00) can be selected for blank device.
Function to display an image taken by a video camera on the GOT
2.27D
2.27D
2.32J
2.32J
Standard monitor OS [02.04.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Extended function OS
Video/RGB [03.00.**]
Standard monitor OS [03.00.**]
Extended function OS
Video/RGB [03.00.**]
RGB display
Function to display the personal computer screen on the GOT
Set overlay screen
Test function
Number of screens that can be called on
GT11 is extended to the same as GT15
(Up to 2047 screens).
Function for changing device value with displaying test window.
Project Script
Function to execute scripts in unit of project file
Screen Script
Object Script
Key Code
Function to execute scripts in unit of screen
Function to execute scripts in unit of object
Key codes for increment key and decrement key are added.
Key code for historical trend graph is added.
Key code used for Kana Kanji conversion is added.
Key codes for user ID ascending/ descending order movement of cursor are added.
2.27D
2.09K
2.00A
2.18U
2.00A
2.18U
2.18U
2.18U
2.18U
2.18U
2.27D
Standard monitor OS [02.04.**]
Standard monitor OS [02.02.**]
Standard monitor OS [01.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [01.00.**]
Standard monitor OS [02.02.**]
Option OS
Object Script [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
GT
15
GT Soft
GOT1000
GT
11
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
App
- 28
17
18
19
20
5
Other functions added
Item Description
Utility
Network unit status display
Displays details in OS information, project information, alarm information, hard copy information and advance recipe information properties.
Function to display the status of
MELSECNET/H communication unit and
CC-Link communication unit
Unlimited installation of extended function
OSs and option
OSs
Extended function OS and option OS can be installed unlimitedly.
(Conventionally, the limit was 10.)
System monitoring function
Network monitor function
Function for monitoring/testing device of
PLC CPU or buffer memory of intelligent function module
Supporting display of Chinese (Simplified/
Traditional), German, Korean
Function to monitor the network status of
MELSECNET/H, MELSECNET/10, etc.
Supporting display of Chinese (Simplified/
Traditional), German, Korean
Version of GT
Designer2
2.18U
2.32J
2.18U
2.09K
2.27D
2.18U
2.27D
Version of OS
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
BootOS [02.02.**.E]
Extended function OS
System monitor [01.02.**]
Ladder monitoring function
Supporting display of Chinese (Simplified/
Traditional), German, Korean
Intelligent module monitor function
Supporting language switching
(Japanese/Korean) for displaying file name and title of the sequence program
Function to monitor and change the data of intelligent function module buffer memory using a dedicated screen
List editor for
MELSEC-A
Function for displaying sequence program loaded to CPU on GOT
Function for displaying/editing sequence program saved from ACPU with list mode
2.09K
2.27D
2.27D
2.18U
2.09K
GT
15
GT Soft
GOT1000
GT
11
Extended function OS
System monitor [02.04.**]
Option OS
Network monitor [02.02.**]
Option OS
Network monitor [02.04.**]
Option OS
Ladder monitor for MELSEC-A
[01.02.**]
Ladder monitor for MELSEC-Q/
QnA [01.02.**]
Ladder monitor for MELSEC-FX
[01.02.**]
Option OS
Ladder monitor for MELSEC-Q/QnA
[02.04.**]
Ladder monitor for MELSEC-FX
[02.04.**]
Option OS
Ladder monitor for MELSEC-Q/QnA
[02.04.**]
Option OS
Intelligent module monitor
[02.02.**]
Option OS
List editor for MELSEC-A
[01.02.**]
(Continued to next page)
App
- 29
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
list mode
List editor for
MELSEC-FX
Supporting display of Chinese (Simplified)
Servo amplifier monitor function
Q motion monitor function
CNC monitor function
Supporting display of Chinese (Simplified/
Traditional), German and Korean
(GT11 supports display of Chinese
(Simplified/Traditional) and Korean)
Function to monitor the servo amplifier and also to change parameters, execute test run, etc.
Function to execute servo monitor and parameter setting for motion controller
CPU (Q series)
Parameter setting is enabled for
Q172HCPU/Q173HCPU.
Function to monitor the MELDAS that is connected to the GOT
Multi-channel function function
Item
Gateway function
Document display
Supporting the FTP server function
Enables transfer of binary data by the FTP server function.
Description
Function to display / edit the sequence program read out from the FXCPU in the
Function to monitor multiple controllers with a single unit of GOT
Function for monitoring each controller from one GOT/PC or sending a mail from
GOT
Function to display document on the GOT
Version of GT
Designer2
2.18U
2.27D
2.27D
Version of OS
Option OS
List editor for MELSEC-FX
[02.02.**]
Extended function OS
List editor for MELSEC-FX
[02.04.**]
Extended function OS
List editor for MELSEC-FX
[02.04.**]
2.18U
2.18U
2.32J
2.18U
2.18U
2.09K
2.18U
2.32J
2.32J
Option OS
Servo amplifier monitor [02.02.**]
Option OS
Q motion monitor [02.02.**]
Standard monitor OS [03.00.**]
Option OS
CNC monitor [02.02.**]
Standard monitor OS [02.02.**]
Communication driver
Use the communication driver,
[02.02.**] or later for each connection.
Option OS
Gateway function (Mail)
[01.02.**]
Gateway function (Server, Client)
[01.02.**]
Option OS
Gateway functionFTP [02.02.**]
Option OS
Gateway (FTP) [03.00.**]
Standard monitor OS [03.00.**]
Option OS
Document Display [03.00.**]
GT
15
GT Soft
GOT1000
GT
11
17
18
19
20
Appendix 5 List of Functions Added by GT Designer2 Version Upgrade
(For GOT1000 Series)
App
- 30
INDEX
[A]
A list editor........................................................... 14-1
Addition times reset for maintenance time notification
Addition times reset function ............................ 17-1
Display operation of addition times reset ......... 17-1
Operation of Addition times reset..................... 17-2
Advanced Recipe Information ........................... 13-44
Alarm information .............................................. 13-28
Alarm information operation ........................... 13-30
Function of alarm information......................... 13-28
The display operation of alarm information .... 13-28
Attachment .................................................. 2-14,8-33
Applicable attachment...................................... 8-33
Installing procedure.......................................... 8-33
[B]
Backlight ...................................................... 2-14,19-6
Backlight replacement...................................... 19-6
Backlight shutoff detection and replacement ... 19-5
Bar code reader................................................... 2-12
Basic operation of settings change...................... 9-11
Basic OS................................................................ 9-1
Battery ......................................................... 2-13,8-27
Applicable battery............................................. 8-27
Battery life ........................................................ 8-28
Battery replacement procedure........................ 8-27
Battery specifications ....................................... 8-27
Battery status display .......................................... 12-1
GOT internal battery status display.................. 12-5
Boot OS ......................................................... 9-1,18-1
Brightness, contrast adjustment ........................ 11-12
Brightness adjustment function ...................... 11-12
Display operation of brightness, contrast ....... 11-12
Buffer circuit cable ................................................. 2-6
Bus connection unit ....................................... 2-5,8-14
Bus connector conversion box ............................ 2-11
Bus extension connector box .............................. 2-11
Communication detail settings functions ........ 10-12
Display contents of communication detail settings..
Key word registration, deletion and protection delete
Communication interface setting ......................... 10-1
Communication setting ........................................ 10-1
Communication setting contents ...................... 10-2
Communication setting display operation. 10-1,10-7
Communication setting functions ..................... 10-1
Communication unit ....................................... 2-5,8-14
Applicable communication unit......................... 8-14
Installing procedure .......................................... 8-15
Component list....................................................... 2-2
Connection cables for MITSUBISHI PLCs............. 2-7
Control panel inside dimensions for mounting GOT ...
Control panel inside temperature and mounting angle
[D]
Daily inspection.................................................... 19-2
Dedicated printer connection cable ..................... 2-13
Display and operation settings............................. 11-1
Display operation of display setting.................. 11-5
Display setting functions .................................. 11-2
Display setting operations ................................ 11-6
Drawing check ..................................................... 14-7
Display operation of drawing check ................. 14-7
Drawing check function .................................... 14-7
Drawing check operation.................................. 14-8
Drawing software ................................................. 2-15
[C]
CC-Link communication unit.......................... 2-5,8-14
CF card.......................................................... 2-12,8-1
Applicable CF card............................................. 8-1
Installing and removing procedures of the CF card .
Clean ................................................................... 15-1
Cleaning method .............................................. 19-3
Display operation of clean................................ 15-1
Operation of clean............................................ 15-2
Cleaning of display section.................................. 15-1
Communication detail settings........................... 10-12
Communication detail settings display operation .....
[E]
EMC AND LOW VOLTAGE DIRECTIVE............... 5-1
Error message and system alarm........................ 20-1
List of error message/system alarm ................. 20-3
Ethernet communication unit ......................... 2-5,8-14
Explanation of the GOT model name .................... 2-2
Explanation of the option model name .................. 2-2
External dimensions ..........................................App-1
[F]
File display and copy ........................................... 13-1
Data type and the storage location .................. 13-2
Display file ........................................................ 13-7
Drive name allocation....................................... 13-1
OS version confirmation ................................... 13-4
Font check ......................................................... 14-12
Display operation of font check ...................... 14-12
Font check function ........................................ 14-12
Index
- 1
[G]
General specifications ........................................... 3-1
GOT self check.................................................... 14-1
GOT set up .......................................................... 11-1
GOT Start Time ................................................. 14-22
Display of GOT start time............................... 14-23
Display operation of GOT start time............... 14-22
GOT start time function.................................. 14-22
GOT-to-GOT connection cable.............................. 2-5
GOT-to-GOT long distance connection cable ....... 2-5
GT Designer2 ...................................................... 2-15
[H]
Hard copy information ....................................... 13-36
The display operation of hardcopy information ........
The function of hardcopy information............. 13-36
The operation of hardcopy information .......... 13-38
[I]
I/O check ........................................................... 14-16
Display operation of I/O check ....................... 14-16
I/O check function .......................................... 14-16
I/O check operation........................................ 14-17
Installation of boot OS and standard OS ............. 18-1
Boot OS and standard OS installation using CF card
Boot OS and standard OS required for installation..
Program / data control function........................ 18-6
The 2-point presses installation function.......... 18-5
Installation procedure ............................................ 6-3
Interface converter unit.................................. 2-5,8-14
[L]
Ladder monitor .................................................... 14-1
Large-size CPU extension cable ........................... 2-6
Logging information ........................................... 13-67
[M]
Font check operation ..................................... 14-13
Maintenance time notification setting .................. 16-1
Display operation of maintenance timimg setting ....
Maintenance time notification function............. 16-2
Operation of maintenance time notification...... 16-4
MELSECNET/10 communication unit............ 2-5,8-14
Memory card adaptor .................................... 2-12,8-5
Applicable memory card adaptor ....................... 8-5
Memory card format .......................................... 13-41
Display operation of memory card format ...... 13-41
Format operation of memory card.................. 13-42
Memory card format ....................................... 13-41
Memory check ..................................................... 14-4
Display operation of memory card ................... 14-4
Memory check function .................................... 14-4
Memory check operation.................................. 14-5
Memory information ........................................... 13-81
Mounting position................................................... 6-2
Multi color display board ................................ 2-13,8-8
Applicable multi-color display board................... 8-8
Installing procedure of the multi-color display board
[O]
Operation of system alarm................................. 14-21
Display operation of system alarm ................. 14-20
System Alarm Display .................................... 14-20
System alarm display function ....................... 14-20
Operation settings.............................................. 11-14
Display operation of display setting................ 11-15
Operation setting functions ............................ 11-14
Setting operation of operation ........................ 11-16
Option .................................................................... 2-5
Option function board .................................... 2-12,8-6
Applicable option function board ........................ 8-6
Installing procedure of the option function board 8-6
OS Information
Display operation of OS information .............. 13-10
OS information................................................... 13-10
Function of OS information ............................ 13-10
Operation of OS information .......................... 13-12
Overall configuration.............................................. 2-1
[P]
Packing list...........................................................A-22
Panel cutting dimensions....................................... 6-1
Part names and settings of the GT1565 ................ 4-7
Part names and settings of the GT1575 ................ 4-5
PC connection cable............................................ 2-15
Performance specifications.................................... 3-2
Periodic inspection............................................... 19-2
Power supply specifications................................. 3-10
Power supply wiring............................................... 7-2
Grouding ............................................................ 7-4
Power supply connection ................................... 7-6
Wiring of connection cables ............................... 7-3
Printer unit ........................................................... 2-13
Installing procedure.......................................... 8-10
Printer unit type ................................................ 8-10
Program/data control ........................................... 13-1
Project information............................................. 13-17
Display operation of project information......... 13-17
Function of OS information ............................ 13-17
Operation of project information..................... 13-19
Protective sheet ........................................... 2-14,8-29
Applicable protective sheet .............................. 8-29
Installing procedure.......................................... 8-30
17
18
19
20
Index
- 2
[Q]
Q extension cable.................................................. 2-5
Q long distance connection cable.......................... 2-5
Q/QnA ladder monitor setting ............................ 11-26
QCPU (Q mode) bus connection cable ................. 2-5
QnA/ACPU/Motion controller (A series) bus connection cable.................................................... 2-6
[R]
Rough pre-operation procedure ............................ 1-5
RS-232 cable......................................................... 2-7
RS-422 cable......................................................... 2-7
RS-422 conversion unit ............................... 2-11,8-26
Applicable RS-422 conversion unit .................. 8-26
Installing procedure.......................................... 8-26
[S]
Screen data transfer cable .................................. 2-15
Security level change ........................................ 11-18
Security change display operation ................. 11-18
Security level change functions...................... 11-18
Security level change operation ..................... 11-19
Small-size CPU extension cable ........................... 2-6
Small-size CPU long distance connection cable ... 2-6
Special Data Information ................................... 13-83
Stand ........................................................... 2-13,8-32
Applicable stand............................................... 8-32
Installing procedure.......................................... 8-32
Standard OS........................................................ 18-1
System configuration ............................................. 2-1
System monitor.................................................... 14-1
[T]
Third party PLC connection cable ......................... 2-3
Time setting and display...................................... 12-1
Clock setting operations................................... 12-2
Display operation of clock display and setting . 12-1
Time setting and display functions ................... 12-1
Touch panel calibration ..................................... 11-23
Touch panel check ............................................ 14-14
Display operation of touch panel check ......... 14-14
Touch panel check function ........................... 14-14
Touch panel check operations ....................... 14-15
Transparent function setting .............................. 11-29
Transportation Precautions ............................. App-25
Troubleshooting
Troubleshooting for monitoring ...................... 20-16
Troubleshooting in bus connection ................ 20-13
[U]
Usage condition of utility function .................... App-10
USB environmental protection cover ................... 8-31
Applicable USB environmental protecton cover8-31
Installing procedure.......................................... 8-31
Utility basic configuration..................................... 9-10
Utility call key setting ......................................... 11-20
Utility call key display operation ..................... 11-20
Utility call key setting function ........................ 11-20
Utility call key setting operation ...................... 11-21
Utility display.......................................................... 9-5
Display operation of main menu......................... 9-7
Main menu ......................................................... 9-5
Password ........................................................... 9-8
System message switch button.......................... 9-5
Utility execution...................................................... 9-1
Utility function list ................................................... 9-2
Index
- 3
WARRANTY
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range
If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company.
However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module.
[Gratis Warranty Term]
The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place.
Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs.
[Gratis Warranty Range]
(1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product.
(2) Even within the gratis warranty term, repairs shall be charged for in the following cases.
1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design.
2. Failure caused by unapproved modifications, etc., to the product by the user.
3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided.
4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced.
5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage.
6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi.
7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.
2. Onerous repair term after discontinuation of production
(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.
Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc.
(2) Product supply (including repair parts) is not available after production is discontinued.
3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ.
4. Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
5. Changes in product specifications
The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.
6. Product application
(1) In using the Mitsubishi graphic operation terminal, the usage conditions shall be that the application will not lead to a major accident even if any problem or fault should occur in the graphic operation terminal device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault.
(2) The Mitsubishi graphic operation terminal has been designed and manufactured for applications in general industries, etc.
Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or Public service purposes shall be excluded from the graphic operation terminal applications.
In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical applications, incineration and fuel devices, manned transportation equipment for recreation and amusement, and safety devices, shall also be excluded from the graphic operation terminal range of applications.
However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi representative outlining the special requirements of the project, and providing that all parties concerned agree to the special circumstances, solely at the users discretion.
Microsoft Windows, Windows NT are registered trademarks of Microsoft Corporation in the United States and other countries.
Ethernet is a trademark of Xerox Co., Ltd. in the United States.
Other company and product names herein may be either trademarks or registered trademarks of their respective owners.
डाउनलोड