Saftronics FP5/GP5 CIMR-P5U Variable Torque Inverter User’s Manual
Quảng cáo
Quảng cáo
FP5/GP5 Series
User’s Manual
Variable Torque Inverter
(with software version 5110/5120 and newer)
!
WARNING
PRECAUTIONS
1) Read this manual in its entirety before installing or operating the
FP5/GP5 inverter. This manual applies to inverters with software versions 5110 and 5120 only and is not intended to be used in conjunction with any other software.
2) Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
3) The FP5/GP5 internal capacitor may be charged even after the power supply is turned OFF. To prevent electrical shock, disconnect all power before servicing the inverter. Then wait at least five minutes after the power supply is disconnected and all LEDs are extinguished.
4) Do not perform a withstand voltage test or a megger test on any part of the FP5/GP5. This electronic equipment uses semiconductors and is vulnerable to high voltage.
5) Do not remove the operator unless the power supply is turned OFF.
Never touch the printed control board while the power supply is turned ON.
6) The FP5/GP5 is suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes, 480 Volts maximum
(460V class units), 240 Volts maximum (230V class units).
Failure to observe these and other precautions highlighted in this manual will expose the user to high voltages, resulting in equipment damage, serious injury or death.
NOTICE
Printed April, 1999. The information contained within this document is the proprietary property of Saftronics, Inc., and may not be copied, reproduced or transmitted to other parties without the expressed written authorization of Saftronics, Inc.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Saftronics is constantly improving its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Saftronics assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2 FP5/GP5User’s Manual
Contents
CONTENTS
Section Description Page
1 RECEIVING & INSTALLATION
1.1 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 S PECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GP5/FP5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 P RELIMINARY I NSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . 11
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Checking the Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . 11
Identifying the Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.4 M OUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Choosing a Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Removing and Replacing the Digital Operator . . . . . . . 14
Removing and Replacing the Front Cover. . . . . . . . . . . 14
Dimensions/Heat Loss. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.5 W
IRING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
FP5/GP5 Connection Diagram . . . . . . . . . . . . . . . . . 19
Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Terminal Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wire and Terminal Screw Sizes . . . . . . . . . . . . . . . . . . . 25
Control Circuit Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2 OPERATION
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.1 T RIAL O PERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Display at Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operation Checkpoints . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Basic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.2 D IGITAL O PERATOR D ISPLAY . . . . . . . . . . . . . . . . . . . . . . . 35
2.3 LED D ESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.4 O PERATION M ODE S ELECTION . . . . . . . . . . . . . . . . . . . . . . 37
3 PROGRAMMING FEATURES
3.1 FP5/GP5 P ARAMETERS (n001~n116) . . . . . . . . . . . 41
3.2 P
ARAMETER
S
ET
-
UP
& I
NITIALIZATION
. . . . . . . . . . . . . . . 49
3.3 FP5/GP5 O PERATION . . . . . . . . . . . . . . . . . . . . . . . . 50
Accel/decel time adjustment . . . . . . . . . . . . . . . . . . . . . . 50
Automatic fault retry . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Automatic restart after momentary power loss . . . . . . . 51
Carrier frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
FP5/GP5 User’s Manual 3
Contents
Current limit (Stall prevention). . . . . . . . . . . . . . . . . . . . 52
DC injection braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Energy savings control . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Frequency agree set point . . . . . . . . . . . . . . . . . . . . . . . . 57
Frequency meter or ammeter . . . . . . . . . . . . . . . . . . . . . 58
Frequency meter or ammeter calibration . . . . . . . . . . . . 58
Frequency signal adjustment. . . . . . . . . . . . . . . . . . . . . . 58
Jog operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Jump frequencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
MODBUS communication . . . . . . . . . . . . . . . . . . . . . . . 61
Motor overload detection . . . . . . . . . . . . . . . . . . . . . . . . 62
Multi-step speed selection. . . . . . . . . . . . . . . . . . . . . . . . 64
Phase loss detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PID Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Reverse run prohibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Soft-start characteristics . . . . . . . . . . . . . . . . . . . . . . . . . 68
Speed limit adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Stopping method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Torque adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Torque detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Tripless operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
V/f pattern adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Slip compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
3.4 I
NPUTS
& O
UTPUTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Multi-function input signals . . . . . . . . . . . . . . . . . . . . . . 78
Analog input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Multi-function output signals . . . . . . . . . . . . . . . . . . . . . 83
4 DIAGNOSTICS
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4.1 M AINTENANCE & I NSPECTION . . . . . . . . . . . . . . . . . . . . . . 87
Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Parts Replacement Schedule. . . . . . . . . . . . . . . . . . . . . . 87
4.2 A
LARM
& F
AULT
D
ISPLAY
. . . . . . . . . . . . . . . . . . . . . . . . . 88
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fault Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Motor Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
A APPENDIX
A-1 B
RAKING
C
ONNECTION
D
IAGRAMS
. . . . . . . . . . . . . . . . . . 94
A-2 D IGITAL O PERATOR M ONITOR D ISPLAY . . . . . . . . . . . . . . 95
A-3 CE C
ONFORMANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
- CHAPTER 1 -
RECEIVING &
INSTALLATION
Section Description
1 RECEIVING & INSTALLATION
Page
1.1 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 S
PECIFICATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
FP5/GP5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 P RELIMINARY I NSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . 11
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Checking the Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . 11
Identifying the Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.4 M OUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Choosing a Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Removing and Replacing the Digital Operator . . . . . . . 14
Removing and Replacing the Front Cover. . . . . . . . . . . 14
Dimensions/Heat Loss. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.5 W
IRING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
FP5/GP5 Connection Diagram . . . . . . . . . . . . . . . . . 19
Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Terminal Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wire and Terminal Screw Sizes . . . . . . . . . . . . . . . . . . . 25
Control Circuit Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
FP5/GP5 User’s Manual 5
Chapter 1 - Receiving & Installation
Introduction
1.1 INTRODUCTION
The FP5/GP5 is a series of
high quality,
full featured inverters.
With a power range of 5 to 500 HP, it provides all the functionality of prior series, in a compact, low cost package. This functionality includes
proprietary features like full-range automatic torque boost, electronic thermal motor overload, energy savings and PID operation, lownoise operation and various other features. It also features a new digital operator for simple programming. Utilizing the latest microprocessor technology, members of the design team have collaborated to make the FP5/GP5 the world’s first optimized inverter specifically designed for variable torque and constant torque applications.
This manual details installation, start-up and operating procedures for the
FP5/GP5 series adjustable frequency drive controller. Descriptions of diagnostic and troubleshooting procedures are also included herein.
6 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Specifications
1.2 SPECIFICATIONS
FP5/GP5
Inverter Model
CIMR-P5U
Rated Output
Current (A)-VT**
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 -
Motor Output (HP) * 0.5 1 2 3 5 7.5 10 20 25 -
Capacity (kVA) 1.2 2.3 3.0 4.2 6.7 9.5 13 19 24 -
3.2 6 8 11 17.5
27 36 54 68 -
Rated Output
Current (A)-CT**
3.2
6 8 11 17.5 25 33 49 64 -
Max. Voltage
3-Phase, 200/208/220/230V
(Proportional to input voltage)
Rated Output Frequency 0.1 to 400 Hz
Overload Capacity - VT 120% Rated Output Current for 1 minute
Overload Capacity - CT 150% Rated Output Current for 1 minute y Input Current (A) 3.9 7.2 9.6 13.2 21 33 44 65 82 -
Rated Voltage & 3-Phase
Frequency 220 - 230V, 50/60Hz
Voltage Fluctuation +10%, -15%
Frequency Fluctuation ±5%
CIMR-P5U 40P4 40P7 41P5 42P2 43P7 44P0 45P5 47P5 4011 4015
Motor Output (HP) * 0.5 1 2 3 5 7.5 10 15 20 25
Capacity (kVA) 1.4 2.6 3.7 4.7 6.1 8.6 11 14 21 26
Rated Output
Current (A)-VT**
1.9 3.6 5.1 6.6 8.5 11.7 14.8 21.0 28.6 34.0
Rated Output
Current (A)-CT**
1.9
3.6
5.1
6.6
8.5
11.7 14.8 18
Max. Voltage #
3-Phase, 380/400/415/440/460V
(Proportional to input voltage)
Rated Output Frequency 0.1 to 400 Hz
28.6 34.0
Overload Capacity-VT**
120% Rated Output Current for 1 minute
(Model 47P5 is rated 150% / 1 minute)
Overload Capacity-CT** 150% Rated Output Current for 1 minute y Input Current (A) 2.3 4.3 6.1 8.0 10.2 14.0 17.8 26.0 35.0 40.0
Rated Voltage &
Frequency
#
3-Phase
380 -440 - 460V, 50/60Hz
Voltage Fluctuation +10%, -15%
Frequency Fluctuation ±5%
* HP ratings based on standard NEMA 4-pole motor data.
#
For 380V operation, the motor rated current must be less than or equal to the inverter
rated current.
** VT: Variable Torque rating (n116=1), CT: Constant Torque rating (n116=0)
Note: Shaded areas indicate factory settings.
FP5/GP5 User’s Manual 7
Chapter 1 - Receiving & Installation
Specifications
Control Method Sine wave PWM with full-range, automatic torque boost
Frequency Control
Range
0.1 to 400 Hz
Frequency Accuracy Digital command: 0.01%, Analog command: 0.1%
Frequency Setting ResoDigital Operator Reference: 0.1Hz, lution Analog Reference: 0.06Hz (@60Hz)
Output Frequency Resolution
0.01 Hz
Frequency Setting 0 to +10VDC (20k Ω ), 4-20mA (250 Ω )
Accel/Decel Time
0.0 to 3600.0 sec.
(Accel/Decel time setting independently: 0.1 sec )
Braking Torque Approx. 20%
No. of V-f Patterns 1 preset V/f pattern and 1 custom pattern
Motor Overload Protection
Instantaneous Overcurrent
Electronic thermal overload relay (I
2
T)
Motor coasts to stop at approx. 200% rated output current.
Fuse Protection Motor coasts to stop at blown fuse.
Overload Motor coasts to stop after 1 min. at rated overload capacity.
Overvoltage
Motor coasts to a stop if converter output voltage exceeds 410VDC
(820VDC at 460V input)
Undervoltage
Motor coasts to stop if converter output voltage drops below user adjustable value
Momentary Power Loss
Immediate stop after 15 ms or longer power loss. (Continuous system operation during power loss less than 2 sec is equipped as standard.)
Heatsink Overheat Thermistor - OH1, OH2
Stall Prevention
Stall prevention at acceleration/deceleration and constant speed operation
Ground Fault Provided by electronic circuit
Power Charge Indication Charge LED stays on until voltage drops below 50VDC
Input Phase Loss Single-phase protection ns Location Indoor (protected from corrosive gases and dust)
Ambient
Temperature
+14 to 104°F (-10 to 40°C) for NEMA 1 type (not frozen)
+14 to 113°F (-10 to 45°C) for open chassis type
Storage
Temperature
-4 to 140°F (-20 to 60°C)
Humidity 95% RH (non-condensing)
Vibration 9.8m/s
2
(1G) less than 20Hz, up to 1.96m/s
2
(0.2G) at 20 to 50Hz
8 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Specifications
FP5/GP5
Inverter Model
CIMR-P5U 2018 2022 2030 2037 2045 2055 2075
Motor Output (HP) * 30 40 50 60 75 100 125
Capacity (kVA) 30 37 50 61 70 85 110
Rated Output
Current (A) - VT **
80 104 130 160 192 248 312
Rated Output
Current (A) - CT **
64 83 104 128 154 198 250
Max. Voltage
3-Phase, 200/208/220/230V
(Proportional to input voltage)
Rated Output Frequency 0.1 to 400 Hz
Overload Capacity - VT ** 120% Rated Output Current / 1 minute
Overload Capacity - CT ** 150% Rated Output Current / 1 minute
—
Input Current (A) 88 119 143 176 212 270 344 —
Rated Voltage &
Frequency
3-Phase
220 - 230V, 50/60Hz
Voltage Fluctuation +10%, -15%
Frequency Fluctuation ±5%
CIMR-P5U 4018 4022 4030 4037 4045 4055 4075 4110 4160 4185 4220 4300
Motor Output (HP) * 30 40 50 60 75 100 150 200 250 300 400 500
Capacity (kVA) 31 40 50 61 73 98 130 170 230 260 340 460
Rated Output
Current (A) - VT **
Rated Output
Current (A) - CT **
41 52 65 80 96 128 180 240 302 380 506 675
32 42 52 64 77 102 144 182 242 304 404 540
Max. Voltage
#
3-Phase, 380/400/415/440/460V
(Proportional to input voltage)
Rated Output Frequency 0.1 to 400 Hz
Overload Capacity - VT ** 120% Rated Current / 1 minute
Overload Capacity - CT ** 150% Rated Current / 1 minute
Input Current (A) 46 58 72 88 106 141 198 264 330 456 608 810
Rated Voltage &
Frequency
#
3-Phase
380 -440 - 460V, 50/60Hz
Voltage Fluctuation +10%, -15%
Frequency Fluctuation ±5%
* HP ratings based on standard NEMA 4-pole motor data.
#
For 380V operation, the motor rated current must be less than or equal to the inverter
rated current.
** VT: Variable Torque rating (n116=1), CT: Constant Torque rating (n116=0)
Note: Shaded areas indicate factory settings.
FP5/GP5 User’s Manual 9
Chapter 1 - Receiving & Installation
Specifications
Control Method Sine wave PWM with full-range, automatic torque boost
Frequency Control Range 0.1 to 400 Hz
Frequency Accuracy Digital command: 0.01%, Analog command: 0.1%
Frequency Setting
Resolution
Digital Operator Reference: 0.1Hz,
Analog Reference: 0.06Hz (@60Hz)
Output Frequency
Resolution
0.01 Hz
Frequency Setting 0 to +10VDC (20k Ω ), 4-20mA (250 Ω )
Accel/Decel Time
0.0 to 3600.0 sec.
(Accel/Decel time setting independently: 0.1 sec )
Braking Torque Approx. 20%
No. of V-f Patterns 1 preset V/f pattern and 1 custom pattern
Motor Overload Protection Electronic thermal overload relay (I
2
T)
Instantaneous Overcurrent Motor coasts to stop at approx. 180% rated output current.
Fuse Protection Motor coasts to stop at blown fuse.
Overload Motor coasts to stop after 1 min. at rated overload capacity.
Overvoltage
Motor coasts to stop if converter output voltage exceeds 410VDC
(820VDC at 460V input)
Undervoltage
Motor coasts to stop if converter output voltage drops below user adjustable value
Momentary Power Loss
Immediately stop after 15 ms or longer power loss. (Continuous system operation during power loss less than 2 sec is equipped as standard.)
Heatsink Overheat Thermistor - OH1, OH2
Stall Prevention Stall prevention at acceleration/deceleration and constant speed operation
Ground Fault Provided by electronic circuit
Power Charge Indication Charge LED stays on until voltage drops below 50VDC
Input Phase Loss Single-phase protection
Location Indoor (protected from corrosive gases and dust)
Ambient Temperature
+14 to 104°F (-10 to 40°C) for NEMA 1 type (not frozen)
+14 to 113°F (-10 to 45°C) for open chassis type
Storage Temperature -4 to 140°F (-20 to 60°C)
Humidity 95% RH (non-condensing)
Vibration 9.8m/s 2 (1G) less than 20Hz, up to 1.96m/s 2 (0.2G) at 20 to 50Hz
10 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Preliminary Inspection
1.3 PRELIMINARY INSPECTION
Receiving
After unpacking the FP5/GP5:
· Verify that the part numbers on the drive nameplate match the numbers on your purchase order or packing slip.
· Check the unit for physical damage which may have occurred during shipping. If any part of the drive is missing or damaged, notify the carrier and your Saftronics representative immediately.
· Verify that all internal hardware (i.e. components, screws, etc.) is seated properly and fastened securely.
· If the drive will be stored after receiving, place it in its original packaging and store according to temperature specifications on page 8.
Checking the Nameplate
Inverter Inverter
Input Spec.
Output Spec.
Lot No.
Serial No.
UL File No.
INPUT :
CIMR-P5U43P7
SPEC :
AC 3PH 380-440V 50Hz
10.2A
380-460V 60Hz
43P71F_
OUTPUT : AC 3PH 0-460V 6.1kVA 8.5A
LOT NO : MASS : 4.5 kg
SER NO :
UL FILE NO :
E131457
Mg
Mass
Figure 1 Nameplate Example of American Model P5U43P7
CIMR - P5 U 4 3P7 1 F
Inverter
FP5/GP5 Series
Revision symbol
Specifications
A: Japanese specifications
E: European specifications
U: American specifications
Enclosure
0: Open chassis
1: NEMA 1 (IP20)
Voltage Class
2: 3-phase, 230V
4: 3-phase, 460V
Figure 2 Nameplate Description
Model Designation
3P7 to 300
See Specifications, pp 7-10
FP5/GP5 User’s Manual 11
Chapter 1 - Receiving & Installation
Preliminary Inspection
Identifying the Parts
Protective Cover (top/bottom)
Front Cover
DRIVE FWD REV
0 P
4 Mounting Holes
Digital Operator
JVOP-130P
Heatsink
Nameplate
Ventilation Slots
Figure 3 Parts Identification - Model P5U43P7
12 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Mounting
1.4 MOUNTING
!
CAUTION
PRECAUTIONS
1) When preparing to mount the FP5/GP5, lift it by its base. Never lift it by the front cover.
2) Mount the inverter onto nonflammable material.
3) The FP5/GP5 generates heat. For the most effective cooling possible, mount it vertically. For more details, refer to “Dimensions/
Heat Loss” on pages 15 & 16 and “Clearances” on page 17.
4) When mounting units in an enclosure, install a fan or other cooling device to keep the intake air temperature below 113°F (45°C).
Failure to observe these precautions may result in equipment damage.
Choosing a Location
Be sure that the inverter is mounted in a location protected against the following conditions:
· Extreme cold and heat. Use only within the ambient temperature range:
14 to 104°F (-10 to 40°C).
· Direct sunlight (not for use outdoors)
· Rain, moisture
· High humidity
· Oil sprays, splashes
· Salt spray
· Dust or metallic particles in the air
· Corrosive gases (e.g. sulfurized gas) or liquids
· Radioactive substances
· Combustibles (e.g. thinner, solvents, etc.)
· Physical shock, vibration
· Magnetic noise (e.g. welding machines, power devices, etc.)
FP5/GP5User’s Manual 13
Chapter 1 - Receiving & Installation
Mounting
Removing and Replacing the Digital Operator
To remove the digital operator from the front cover, push the operator lever in the direction shown by arrow 1 and lift the digital operator in the direction shown by arrow 2 (see Figure 4).
To replace the digital operator, engage the operator onto retaining tabs A in the direction shown by arrow 1 and then onto retaining tabs B in the direction shown by arrow 2, locking the digital operator into place (see
Figure 5).
Front Cover 2
Digital Operator
1
Digital Operator
2
Retaining
Tabs A
Figure 4 Removing the Digital Operator
Front Cover
1
Retaining
Tabs B
Figure 5 Replacing the Digital Operator
Removing and Replacing the Front Cover
To remove the front cover, first remove the digital operator (see previous section). Then squeeze the cover on both sides in the direction shown by arrows 2 and lift the cover in the direction shown by arrow 3.
1
2
Front Cover
3
2
Figure 6 Removing and Replacing the Front Cover
14 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Mounting
Dimensions/Heat Loss
Open Chassis Type (IP00)
Voltage
Model
CIMR
-P5U
20P4
Open Chassis Dimensions in inches (mm)
W H D W1 H1 H2
Mass lbs (kg)
Heat Loss (W)
Heat sink
Inside unit
Total
15 50 65
21P5 40 80 120
22P2 80 60 140
230V
460V
25P5
27P5
2011
2015
2018
2022
7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8)
12 (5.5) 210 90 300
13 (6) 235 110 345
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5) 24 (11)
12.80 (325) 17.72 (450) 11.22 (285) 10.83 (275) 17.13 (435) 0.30 (7.5) 62 (28)
425 160 585
525 200 725
655 230 885
830 280 1110
2030
2037
2045
2055
4055
4075
16.73 (425) 26.57 (675) 13.78 (350) 12.60 (320) 25.59 (650) 0.49 (12.5)
134 (61) 1050 500 1550
137 (62) 1250 700 1950
18.70 (475) 31.50 (800) 13.78 (350) 14.57 (370) 30.51 (775) 0.49 (12.5) 176 (80)
17.91 (455) 32.28 (820) 13.78 (350) 13.78 (350) 31.30 (795) 0.49 (12.5)
1550 750 2300
1950 1000 2950
2075 22.64 (575) 36.42 (925) 15.75 (400) 17.52 (445) 35.24 (895) 0.59 (15) 298 (135) 2300 1300 3600
40P4
40P7 5.51 (140) 11.02 (280) 6.30 (160) 4.96 (126) 10.47 (266) 0.28 (7)
6.5 (3)
10 50 60
20 65 85
41P5 8.8 (4) 30 80 110
42P2 65 60 125
43P7 5.51 (140) 11.02 (280) 7.09 (180) 4.96 (126) 10.47 (266) 0.28 (7) 10 (4.5) 80 65 145
44P0 120 80 200
45P5
47P5
7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8) 13 (6)
135 85 220
240 120 360
4011
4015
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5) 24 (11)
305 150 455
390 180 570
4018
4022
12.80 (325) 17.72 (450) 11.22 (285) 10.83 (275) 17.13 (435) 0.30 (7.5) 60 (27)
465 195 660
620 260 880
4030 705 315 1020
4037 12.80 (325) 24.61 (625) 11.22 (285) 10.83 (275) 24.02 (610) 0.30 (7.5) 97 (44) 875 370 1245
4045 970 415 1385
174 (79) 1110 710 1820
176 (80) 1430 890 2320
4110 14.76 (375)
17.52 (445) 35.24 (895) 0.59 (15)
298 (135) 1870 1160 3030
4185
4220
3400 1510 4910
37.40 (950) 57.09 (1450) 17.13 (435) 29.53 (750) 55.12 (1400) 0.98 (25) 794 (360)
4740 2110 6850
4300 37.80 (960) 62.99 (1600) 17.91 (455) 29.53 (750) 61.02 (1550) 0.98 (25) 926 (420) 6820 2910 9730
FP5/GP5User’s Manual 15
Chapter 1 - Receiving & Installation
Mounting
Enclosed Type (NEMA 1, IP20)
Voltage
230V
460V
Model
(CIMR-
P5U)
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
W H D W1 H1 H2
Mass lbs (kg)
5.51 (140) 11.02 (280) 6.30 (160) 4.96 (126) 10.47 (266) 0.28 (7) 6.5 (3)
5.51 (140) 11.02 (280) 7.09 (180) 4.96 (126) 10.47 (266) 0.28 (7) 10 (4.5)
7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8)
9.84 (250)
12.99 (330)
NEMA 1 Dimensions in inches (mm)
14.96 (380)
24.02 (610)
0.30 (7.5)
3.44 (87.5)
12 (5.5)
13 (6)
24 (11)
71 (32)
2030
2037
2045
2055
16.93 (430) 38.78 (985) 13.78 (350) 12.60 (320) 25.59 (650) 8.37 (212.5)
148 (67)
150 (68)
18.90 (480) 43.70 (1110) 13.78 (350) 14.57 (370) 30.51 (775) 8.37 (212.5) 192 (87)
2075 22.83 (580) 50.79 (1290) 15.75 (400) 17.52 (445) 35.24 (895) 10.63 (270) 320 (145)
40P4
40P7 5.51 (140) 11.02 (280) 6.30 (160) 4.96 (126) 10.47 (266) 0.28 (7)
6.5 (3)
41P5 8.8 (4)
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
4022
4030
4037
5.51 (140) 11.02 (280) 7.09 (180) 4.96 (126) 10.47 (266) 0.28 (7) 10 (4.5)
7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8) 13 (6)
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5) 24 (11)
12.99 (330) 24.02 (610) 11.22 (285) 10.83 (275) 17.13 (435) 3.44 (87.5) 68 (31)
12.99 (330) 106 (48)
4045
30.91 (785)
11.22 (285) 10.83 (275) 24.02 (610)
3.44 (87.5)
33.46 (850) 6.00 (152.5)
4055
4075
4110
18.11 (460) 44.49 (1130) 13.78 (350) 13.78 (350) 31.30 (795) 8.37 (212.5)
14.76 (375)
17.52 (445) 35.24 (895) 10.63 (270)
187 (85)
190 (86)
320 (145)
16 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Mounting
W1
W
D
Front View Side View
Figure 7 FP5/GP5 Dimension Diagram
Clearances
When mounting the FP5/GP5, allow sufficient clearances for effective cooling as shown below:
1.97in (50mm)
4.72in (120mm)
Air
1.18in (30mm)
1.97in (50mm)
4.72in (120mm)
Air
Front View Side View
Figure 8 FP5/GP5 Clearances
Notes:
1) The required clearances at the top, bottom, and both sides of the inverter are the same for both open chassis and NEMA 1 enclosures.
2) For inverter models 25HP and less (230V & 460V), remove the top and bottom covers to convert NEMA 1 units to open chassis
3) Allowable intake air temperature:
Open chassis: 14°F to 113°F (-10°C to +45°C)
NEMA 1: 14°F to 104°F (-10°C to 40°C)
4) When mounting units in an enclosure, install a fan or other cooling device to limit the air temperature within the inverter to below 113°F (45°C).
FP5/GP5 User’s Manual 17
Chapter 1 - Receiving & Installation
Wiring
1.5 WIRING
!
CAUTION
PRECAUTIONS
1) Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
2) Connect the power supply wiring to terminals L1, L2 and L3 on the main circuit input section. DO NOT connect the power supply wiring to output terminals T1, T2 and T3.
3) Connect the motor wiring to terminals T1, T2 and T3 on the main circuit output section.
4) Never touch the output circuit directly or place the output line in contact with the inverter enclosure.
5) Do not connect a phase-advancing capacitor or an LC/RC noise filter to the output circuit.
6) The motor wiring must be less than 328ft (100m) in length and in a separate conduit from the input power wiring.
7) Control wiring must be less than 164ft (50m) in length and in a separate conduit from both the motor wiring and the power wiring.
8) Tighten the screws on the main circuit and control circuit terminals.
9) Low voltage wires shall be wired with Class 1 wiring.
10)Please observe national electrical code (NEC) when wiring electrical devices.
Failure to observe these precautions may result in equipment damage.
Inspection
After wiring is complete, verify that:
All wiring is correctly installed.
Excess screws and wire clippings are removed from inside of the unit.
Screws are securely tightened.
Exposed wire has no contact with other wiring or terminals.
18 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Wiring
FP5/GP5 Standard Connection Diagram
230V: Models 20P4 through 27P5
460V: Models 40P4 through 4015
B1 B2
DC Link Reactor (option)
⊕ 1
⊕ 2
L1
L2
L3
T1
T2
T3
IM
Ground
230V units: 100 Ω or less
460V units: 10 Ω or less
Multi-Function
Contact Inputs
S1 - Fixed
S2
S3
S4
S5
S6
SC (Com)
Gate Drive
PWM
8 bit
0~10V AM
(Com) AC
Multi-Function
Analog Outputs
G
Analog Inputs
Input FI selectable
4~20mA or
0~10V
0~+10V
4~20mA
FS
FV
FI
(+15V)
(20k Ω )
(250 Ω )
FC (0V)
A/D
10 bit
Digital
Operator
Serial Port
RS-232
(10-pin)
G
MA
MB
MC
M1
M2
Multi-Function
Contact Outputs
250VAC, 1A or less
30VDC, 1A or less
Figure 9 FP5/GP5 Terminal Diagram
FP5/GP5 User’s Manual 19
Chapter 1 - Receiving & Installation
Wiring
FP5/GP5 Standard Connection Diagram
Ground
230V units: 100 Ω or less
460V units: 10 Ω or less
L1
L2
L3
L11
L21
L31
Multi-Function
Inputs
S1 - Fixed
S2
S3
S4
S5
S6
SC (Com)
Gate Drive
PWM
8 bit
230V: Models 2018 through 2075
460V: Models 4018 through 4160
0~10V AM
(Com) AC
T1
T2
T3
IM
Multi-Function
Analog Outputs
G
Analog Inputs
Input FI selectable
4~20mA or
0~10V
0~+10V
4~20mA
FS
FV
FI
(+15V)
(20k Ω )
(250 Ω )
FC (0V)
A/D
10 bit
Digital
Operator
Serial Port
RS-232
(10-pin)
G
MA
MB
MC
M1
M2
Multi-Function
Relay Outputs
250VAC, 1A or less
30VDC, 1A or less
Figure 10 FP5/GP5 Terminal Diagram
20 FP5/GP5User’s Manual
Chapter 1 - Receiving & Installation
Wiring
Main Circuit Wiring
Input Wiring
· Molded-Case Circuit Breaker (MCCB)
Be sure to connect MCCBs or fuses between the AC main circuit power supply and FP5/GP5 input terminals L1, L2 and L3, to protect the power supply wiring.
· Ground Fault Interrupter
When connecting a ground fault interrupter to input terminals L1, L2 and L3, select one that is not affected by high frequency.
Examples: NV series by Mitsubishi Electric Co., Ltd. (manufactured in or after 1988), EGSG series by Fuji Electric Co., Ltd.
(manufactured in or after 1984).
· Magnetic Contactor (MC)
Inverters can be used without an MC installed on the power supply side.
An MC can be used instead of an MCCB to apply the main circuit power supply. However, when an MC is switched OFF on the primary side, dynamic braking does not function and the motor coasts to stop.
The load can be operated/stopped by closing/opening the MC on the primary side. However, frequent switching may cause the inverter to malfunction.
When using a braking resistor unit, use an MC to break the power supply side of the inverter in the event of a dynamic braking overload relay trip.
Otherwise, if the inverter malfunctions, the braking resistor unit may be burned out.
· Terminal Block Connection Sequence
Input power supply phases can be connected to any terminal regardless of the order of L1, L2 and L3 on the terminal block.
· AC Reactor
When connecting an inverter (230V/460V, 25HP or less) to a large capacity power supply transformer (600kVA or more), or when switching a phase-advancing capacitor, excessive peak current flows through the input power supply circuit, which may damage the converter section. In such cases, install a DC reactor (optional) between inverter
⊕
1 and
⊕
2 terminals, or an AC reactor (optional) on the input side. Installation of a reactor is also effective for improving power factor on the power supply side.
FP5/GP5 User’s Manual 21
Chapter 1 - Receiving & Installation
Wiring
· Surge Suppressor
For inductive loads (i.e. magnetic contactors, magnetic relays, magnetic valves, solenoids, magnetic brakes, etc.) connected near the inverter, use a surge suppressor across the coils to limit the transients on the supply lines.
Output Wiring
· Motor Connection
Connect motor lead wires to output terminals T1, T2 and T3. Verify that the motor rotates in the forward direction (CCW: counterclockwise when viewed from the motor load side) with the forward run command.
If the motor rotation is incorrect, exchange any two of the motor leads.
· Magnetic Starter
Do not connect a magnetic starter or a magnetic contactor to the output circuit. If the motor load is connected or disconnected while the inverter is running, the inverter overcurrent protective circuitry may trip.
· Thermal Overload Relay
An electronic overload protective function (I
2 t) is incorporated into the inverter. However, when driving several motors with one inverter, or when switching between multiple windings of a multiple winding motor, use an external thermal overload relay(s). In this case, set parameter n034 to “Disabled”.
· Wiring Distance Between Inverter and Motor
If the total wiring distance between inverter and motor is excessively long and the inverter carrier frequency (IGBT switching frequency) is high, harmonic leakage current from the wiring will adversely affect the inverter and peripheral devices. If the wiring distance is long, reduce the inverter carrier frequency as described below. Carrier frequency can be set by parameter n054.
Wiring Distance Between Inverter and Motor
Wiring Distance between
Inverter and Motor
Carrier Frequency *
(Set value of parameter n054)
Up to 164 ft.
(50m)
15kHz or less
(6)
Up to 328 ft.
(100m)
10kHz or less
(4)
More than 328 ft.
(100m)
5kHz or less
(2)
* Increasing the carrier frequency above the factory default value requires current derating. Contact your Saftronics representative for details.
22 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Wiring
Grounding
· Ground Resistance
230V class: 100
Ω
or less, 460V class: 10
Ω
or less.
· Never ground the FP5/GP5 in common with welding machines, motors, or other high-current electrical equipment. Run all ground wiring in a separate conduit.
· Use ground wiring as specified in “Wire and Terminal Screw Sizes” on page 25, and keep the length as short as possible.
· When using several FP5/GP5 units side by side, ground the units as shown in Figure 10, (a) or (b). Do not loop the wires as shown in (c).
(a) Acceptable (b) Acceptable (c) Not Acceptable
Figure 11 Grounding Example of 3 FP5/GP5 Inverters
FP5/GP5 User’s Manual 23
Chapter 1 - Receiving & Installation
Wiring
Terminal Functions
230V Class Terminal Functions
Model CIMR-P5U 20P4 to 27P5 2011 to 2015 2018 to 2075
Nominal Motor Output 0.5 to 10HP 20 to 25HP 30 to 125HP
L1
L2 Main circuit input power supply
L3
L11
L21
L31
---
Main circuit input power supply
T1
T2
T3
B1
B2
Inverter output
Braking resistor unit ---
⊕ 1
⊕ 2
DC reactor (
⊕ 3 ---
⊕ 1 -
DC power supply ( ⊕
⊕ 2)
1 - )
DC reactor (
Braking unit (
⊕
DC power supply (
⊕
1 -
⊕
3 -
⊕ 2)
1 -
)
)
Ground terminal (Ground resistance: 100 Ω or less)
---
460V Class Terminal Functions
Model CIMR-P5U 40P4 to 4015 4018 to 4045 4055 to 4160 4185 to 4300
Nominal Motor Output 0.5 to 25HP 30 to 75HP 100 to 250HP 300 to 500HP
L1
L2
Main circuit input power supply
Main circuit input power supply
L3
L11
Main circuit input power supply
--- --L21
L31
T1
T2 Inverter output
T3
B1
B2
Braking resistor unit ---
⊕ 1
⊕ 2 r s 200 s 400
DC reactor ( ⊕ 1 - ⊕ 2)
DC power supply ( ⊕ 1 - )
---
---
Cooling fan power supply
(Control power supply) r - s 200: 200 to 230 VAC input r - s 400: 380 to 460 VAC input
Ground terminal (Ground resistance: 10 Ω or less)
24 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Wiring
Wire and Terminal Screw Sizes
230V Class Wire Size
Circuit
Model
CIMR-
Terminal Symbol
P5U20P4
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
Terminal
Screw
Wire Size * Max. Torque
AWG mm 2 lb-in (N·m)
M4 14 - 10 2 - 5.5 12.4 (1.4)
Wire Type
P5U20P7
P5U21P5
L1, L2, L3, ,
L1, L2, L3, ,
⊕
⊕
1,
1,
⊕
⊕
2, B1, B2, T1, T2, T3
2, B1, B2, T1, T2, T3
M4 14 - 10 2 - 5.5 12.4 (1.4)
M4
14 - 10 2 - 5.5
12 - 10 3.5 - 5.5
12.4 (1.4)
P5U22P2
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
P5U23P7
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
M4 12 - 10 3.5 - 5.5 12.4 (1.4)
M4 10 5.5 12.4 (1.4)
Main
Control
P5U25P5
P5U27P5
P5U2011
P5U2015
P5U2018
P5U2022
P5U2030
P5U2037
P5U2045
P5U2055
P5U2075
Common to all models
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
M5
8 8
10 - 8 5.5 - 8
22.1 (2.5)
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
M5
8 8
10 - 8 5.5 - 8
22.1 (2.5)
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
M6
4 22
8 8
45.1 (5.1)
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3 M8 3 30 90.3 (10.2)
M6 8 8 45.1 (5.1)
L1, L2, L3, L11, L21, L31, T1, T2, T3
M8
3 30
6 14
90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3
M8
2 38
6 14
90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 4/0 100 203.6 (23.0)
M8 4 22 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P 60 x 2P 203.6 (23.0)
M8 4 22 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P 60 x 2P 203.6 (23.0)
M8 4 22 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P 60 x 2P 203.6 (23.0)
M8 3 30 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M12 4/0 x 2P 100 x 2P 349.6 (39.5)
S1, S2, S3, S4, S5, S6, SC
FV, FI, FS, FC
AM, AC, M1, M2, MA, MB, MC
M8 1 50 90.3 (10.2)
Stranded
0.5 - 1.25
- 20 - 16 -
Solid
0.5 - 1.25
G M3.5 20 - 14 0.5 - 2 8.9 (1.0)
* Wire sizes are based on 75°C copper wire.
Power cable:
600V vinyl sheathed wire or equivalent
Twisted shielded wire with Class 1 wiring
Note:
Voltage drop should be considered when determining wire size. Voltage drop can be calculated using the following equation:
Phase-to phase voltage drop (V)
= 3 wire resistance ( Ω /km) x wiring distance (m) x current (A) x 10
-3
Select a wire size so that voltage drop will be less than 2% of the normal rated voltage.
FP5/GP5 User’s Manual 25
Chapter 1 - Receiving & Installation
Wiring
460V Class Wire Size
Circuit
Model
CIMR-
Terminal Symbol
P5U40P4 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
P5U40P7 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
P5U41P5 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
P5U42P2 L1, L2, L3, ,
P5U43P7
L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
Terminal
Screw
Wire Size * Max. Torque
AWG mm 2 lb-in (N·m)
M4 14 - 10 2 - 5.5 12.4 (1.4)
M4
M4
M4
M4
14 - 10 2 - 5.5
12 - 10 3.5 - 5.5
14 - 10 2 - 5.5
12 - 10 3.5 - 5.5
14 - 10 2 - 5.5
12 - 10 3.5 - 5.5
14 - 10 2 - 5.5
12 - 10 3.5 - 5.5
12.4 (1.4)
12.4 (1.4)
12.4 (1.4)
12.4 (1.4)
M4 12 - 10 3.5 - 5.5 12.4 (1.4)
Wire Type
P5U45P5
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
P5U47P5
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
M5 8 - 6 8 - 14 22.1 (2.5)
Main
Control
P5U4011
P5U4015
P5U4018
P5U4022
P5U4030
P5U4037
P5U4045
P5U4055
P5U4075
P5U4110
P5U4160
P5U4185
P5U4220
P5U4300
Common to all models
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3 M5 8 - 6 8 - 14 22.1 (2.5)
M6 8 - 6 8 - 14 45.1 (5.1)
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3 M5 8 - 6 8 - 14 22.1 (2.5)
M6 8 - 6 8 - 14 45.1 (5.1)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M6 6 14 45.1 (5.1)
M8 8 - 6 8 - 14 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M6 4 22 45.1 (5.1)
L1, L2, L3, L11, L21, L31, T1, T2, T3
M8 4 22 90.3 (10.2)
M8
4 22
4 22
90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3
L1, L2, L3, L11, L21, L31, T1, T2, T3
M8
M8
3 30
4 22
1 50
3 30
90.3 (10.2)
90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 4/0 100 203.6 (23.0)
M8 1 50 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P 60 x 2P 203.6 (23.0)
M8 1/0 60 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P 60 x 2P 203.6 (23.0)
M8 1/0 60 90.3 (10.2)
L1, L2, L3, L11, L21, L31, T1, T2, T3 M12 4/0 x 2P 100 x 2P 349.6 (39.5)
L1, L2, L3, , ⊕ 1, ⊕ 3, T1, T2, T3
M8 4/0 100 90.3 (10.2)
M16
650MCM x 2P
325 x 2P 867.4 (98.0)
M8 650MCM 325 90.3 (10.2) r, s200, s400 M4 20 - 10 0.5 - 5.5 12.4 (1.4)
L1, L2, L3, , ⊕ 1, ⊕ 3, T1, T2, T3
M16
650MCM x 2P
325 x 2P 867.4 (98.0)
M8 650MCM 325 90.3 (10.2) r, s200, s400 M4 20 - 10 0.5 - 5.5 12.4 (1.4)
L1, L2, L3, , ⊕ 1, ⊕ 3, T1, T2, T3
M16
650MCM x 2P
325 x 2P 867.4 (98.0)
M8 650MCM 325 90.3 (10.2) r, s200, s400 M4 20 - 10 0.5 - 5.5 12.4 (1.4)
S1, S2, S3, S4, S5, S6, SC
FV, FI, FS, FC
AM, AC, M1, M2, MA, MB, MC
- 20 - 16
Stranded
0.5 - 1.25
-
Solid
0.5 - 1.25
G M3.5 20 - 14 0.5 - 2 8.9 (1.0)
Power cable:
600V vinyl sheathed wire or equivalent
Twisted shielded wire with Class 1 wiring
* Wire sizes are based on 75°C copper wire.
26 FP5/GP5 User’s Manual
Chapter 1 - Receiving & Installation
Wiring
JST Closed Loop Connectors
Wire Size *
AWG mm 2
Terminal Screw JST Closed-Loop Connectors (Lugs)
Max. Torque lb-in (N·m)
20 0.5
18 0.75
16 1.25
14 2
12 - 10 3.5 - 5.5
M3.5 1.25 - 3.5 8.9 (1.0)
M4 1.25 - 4 12.4 (1.4)
M3.5 1.25 - 3.5 8.9 (1.0)
M4 1.25 - 4 12.4 (1.4)
M3.5 1.25 - 3.5 8.9 (1.0)
M4 1.25 - 4 12.4 (1.4)
M3.5 2 - 3.5 8.9 (1.0)
M4 2 - 4 12.4 (1.4)
M5 2 - 5 22.1 (2.5)
M6 2 - 6 45.1 (5.1)
M8 2 - 8 90.3 (10.2)
M4 5.5 - 4 12.4 (1.4)
M5 5.5 - 5 22.1 (2.5)
M6 5.5 - 6 45.1 (5.1)
M8 5.5 - 8 90.3 (10.2)
M5 8 - 5 22.1 (2.5)
8 8
6 14
M6 8 - 6 45.1 (5.1)
M8 8 - 8 90.3 (10.2)
M6 14 - 6 45.1 (5.1)
M8 14 - 8 90.3 (10.2)
4 22
M6 22 - 6 45.1 (5.1)
M8 22 - 8 90.3 (10.2)
3 - 2 30 - 38 M8 38 - 8 90.3 (10.2)
1 - 1/0 50 - 60
M8 60 - 8 90.3 (10.2)
M10 60 - 10 203.6 (23.0)
3/0 80 80 - 10 203.6 (23.0)
4/0 100 100 - 12 349.6 (39.5)
400MCM 200 200 - 12 349.6 (39.5)
650MCM 325
M12 x 2 325 - 12 349.6 (39.5)
M16 325 - 16 867.4 (98.0)
Note:
The use of a JST closed-loop connector (lug) is recommended to maintain proper clearances. Please contact your Saftronics representative for more information.
FP5/GP5 User’s Manual 27
Chapter 1 - Receiving & Installation
Wiring
Control Circuit Wiring
The following table outlines the functions of the control circuit terminals.
Control Circuit Terminals
Classification
Terminal Function Description Signal Level
M1
M2
MA
MB
S1 Forward run/stop Forward run when closed, stop when open
S2 Reverse run/stop
Reverse run when closed, stop when open
S3 External fault input
Fault when closed, normal state when open
S4 Fault reset input Reset when closed
S5 Multi-step speed reference 1 Enabled when closed
Multi-function contact inputs (n036 to n040)
S6 Multi-step speed reference 2 Enabled when closed
SC Sequence input common terminal —
FS +15V Power supply output For analog command +15V power supply
+15V (allowable current 20mA max.)
FV Frequency reference input (voltage) 0 to +10V/100% n043 = “FV=MSTR”:
FV enabled
0 to +10V (20k Ω )
FI Frequency reference input (current) 4 to 20mA/100% 4 to 20mA (250
FI enabled
Ω )
FC Common terminal 0V —
G
Connection to shield sheath of signal lead
— —
MC
During running (N.O. contact) Closed when running
Fault contact output
(N.O./N.C. contact)
Fault when closed between terminals MA and MC
Fault when open between terminals MB and MC
Multi-function contact
Photo-coupler insulation
Input: +24VDC 8mA output (n042) Dry contact
Contact capacity:
Multi-function contact output (n041)
250VAC 1A or less
30VDC 1A or less
AM Frequency meter output
AC Common
0 to +10V
2mA or less
G
Figure 12 Control Circuit Terminal Arrangement
Insert the wire into the lower part of the terminal block and connect tightly with a screwdriver.
0.28in (7mm) max
0.02in (0.6mm) max
0.14in (3.5mm) max
Figure 13 Wiring the Control Circuit Terminal
28 FP5/GP5 User’s Manual
Chapter 2 - Operation
- CHAPTER 2 -
OPERATION
Section Description
2 OPERATION
Page
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.1 T RIAL O PERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Digital Operator Display at Power-up . . . . . . . . . . . . . . 31
Operation Checkpoints . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Basic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.2 D IGITAL O PERATOR D ISPLAY . . . . . . . . . . . . . . . . . . . . . . . 35
2.3 LED D
ESCRIPTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.4 O PERATION M ODE S ELECTION . . . . . . . . . . . . . . . . . . . . . . 37
FP5/GP5 User’s Manual 29
Chapter 2 - Operation
Precautions
!
WARNING
PRECAUTIONS
1) Only turn ON the input power supply after replacing the front cover.
Do not remove the cover while the inverter is powered up.
2) When the retry function (n060) is selected, do not approach the inverter or the load, since it may restart suddenly after being stopped.
3) Since the Stop key can be disabled by a function setting, install a separate emergency stop switch to disconnect power or fault the inverter.
4) Do not touch the heatsink or braking resistor, due to very high temperatures.
5) Since it is very easy to change operation speed from low to high speed, verify the safe working range of the motor and machine before operation.
6) Install a separate holding brake, if necessary.
7) Do not check signals during operation.
8) All inverter parameters have been preset at the factory. Do not change the settings without thorough review of the possible consequences.
Failure to observe these precautions may result in equipment damage, serious personal injury, or death.
30 FP5/GP5 User’s Manual
Chapter 2 - Operation
Trial Operation
2.1 TRIAL OPERATION
To ensure safety, prior to initial operation, disconnect the machine coupling so that the motor is isolated from the machine. If initial operation must be performed while the motor is still coupled to the machine, use great care to avoid potentially hazardous conditions. Check the following items before a trial run:
· Wiring and terminal connections are proper.
· Wire clippings and other debris removed from the unit.
· Screws are securely tightened.
· Motor is securely mounted.
· All items are correctly grounded.
Digital Operator Display at Power-Up (JVOP-130P)
When the system is ready for operation, turn ON the power supply. Verify that the inverter powers up properly. If any problems are detected, turn
OFF the power supply immediately. The digital operator display illuminates as shown below when the power supply is turned ON.
DRIVE FWD REV
REMOTE
SEQ REF
F requency R ef
0.0
HZ
Fref Fout Iout
FLA PID kWsav kWout
F/R Montr Accel Decel
Vmtr V/F Fgain Fbias
PRGM
DIGITAL OPERATOR
JVOP-130P
DSPL
LOCAL
REMOTE
RUN
ENTER
STOP
RESET
Operation Mode Indicators:
DRIVE: Lit when in operation mode.
FWD: Lit when there is a forward run command input.
REV: Lit when there is a reverse run command input.
SEQ: Lit when the run command from the control circuit terminal is enabled.
REF: Lit when the frequency reference from control circuit terminals 13 and 14 is enabled.
Display Section:
2 line ×
16 character alphanumeric LCD that displays data for monitoring, user parameters, and set values.
Keys:
Execute operations such as setting user parameters, monitoring, and auto-tuning.
Figure 14 Digital Operator Display at Power-up (JVOP-130P)
FP5/GP5 User’s Manual 31
Chapter 2 - Operation
Trial Operation
Operation Checkpoints:
· Motor rotates smoothly.
· Motor rotates in the correct direction.
· Motor has no abnormal vibration and is not noisy.
· Acceleration and deceleration are smooth.
· Unit is not overloaded.
· Status indicator LEDs and digital operator display are correct.
Basic Operation
The inverter will operate after receiving a frequency reference. There are two operation modes for the FP5/GP5:
· Run command from the digital operator.
· Run command from the control circuit terminals.
Operation by Digital Operator
The diagram below shows a typical operation pattern using the digital operator. Pressing the LOCAL/REMOTE key once while the inverter is stopped places the inverter in the LOCAL mode. The digital operator,
JVOP-130P, can then be used to start and stop and change the reference.
4 5 6
1 2 3
Forward
15Hz
Power
ON
Forward Run Reverse Run
Frequency Setting Frequency Reference Change
Reverse
60Hz
Stop
Figure 15 Operation Sequence by Digital Operator
32 FP5/GP5 User’s Manual
Chapter 2 - Operation
Trial Operation
Typical Operation Example by Digital Operator (JVOP-130P)
Description Key Sequence Digital Operator Display
(1) Power ON
· Displays frequency reference value. REMOTE LED (SEQ, REF) ON
Operation Condition Setting
· Select LOCAL mode.
LOCAL
REMOTE
Frequency Ref
0.0 Hz
REMOTE LED (SEQ, REF) OFF
(2) Frequency Setting
· Change frequency reference value.
Change the value by depressing
Frequency Ref
15.0 Hz
· Write-in set value.
· Select output frequency monitor display.
(3) Forward Run
· Forward run (15Hz)
ENTER
DSPL
RUN
(4) Frequency Reference Value Change (15~60Hz)
· Select frequency reference value display.
· Change set value.
DSPL
Depress 15 times
Change the value by depressing
Frequency Ref
15.0 Hz
Output Freq
0.0 Hz
Output Freq
15.0 Hz
RUN LED ON
Frequency Ref
15.0 Hz
Frequency Ref
60.0 Hz
· Write-in set value.
· Select output frequency monitor display.
ENTER
DSPL
Frequency Ref
60.0 Hz
Output Freq
60.0 Hz
(5) Reverse Run
· Select reverse run. DSPL
Depress 3 times.
Switch to “rev” by depressing
Forward/Reverse
For
· Write-in set value.
ENTER
Forward/Reverse rev
REVERSE LED (REV) ON
Forward/Reverse rev
· Select output frequency monitor display.
(6) Stop
· Decelerates to stop.
DSPL
Depress 13 times.
STOP
RESET
Output Freq
60.0 Hz
Output Freq
0.0 Hz
RUN LED OFF STOP LED ON
FP5/GP5 User’s Manual 33
Chapter 2 - Operation
Trial Operation
Operation by Control Circuit Terminal Signal
The diagram below shows a typical operation pattern using the control circuit terminal signals.
Forward
60Hz
4
1 2 3
Power ON Operation
Frequency Setting
Stop
Figure 16 Operation Sequence by Control Circuit Terminal Signal
Typical Operation Example by Control Circuit Terminal Signal
Description Key Sequence Digital Operator Display
(1) Power ON
· Displays frequency reference value.
REMOTE mode is preset at the factory.
Frequency Ref
0.0 Hz
REMOTE LED (SEQ, REF) ON
(2) Frequency Setting
· Input frequency reference voltage (current) by control circuit terminal FV or FI and verify the input value by the digital operator.
Frequency Ref
60.0 Hz
For reference voltage 10V
Output Frequency Display
· Write-in set value.
DSPL
Output Freq
0.0 Hz
(3) Forward Run
· Close between control circuit terminals S1 and SC to perform forward run.
Output Freq
60.0 Hz
RUN LED ON
(4) Stop
· Open between control circuit terminals S1 and SC to stop operation.
Output Freq
0.0 Hz
STOP LED ON
(RUN LED blinking during deceleration)
34 FP5/GP5 User’s Manual
Chapter 2 - Operation
Digital Operator Display
2.2 DIGITAL OPERATOR DISPLAY
All functions of the FP5/GP5 are accessed using the JVOP-130P Digital Operator. Below are descriptions of the display and keypad sections.
DRIVE FWD REV
REMOTE
SEQ REF
F requency R ef
0.0
HZ
Fref Fout Iout kWout
F/R Montr Accel Decel
Vmtr V/F Fgain
FLA PID kWsav
Fbias
PRGM
DIGITAL OPERATOR
JVOP-130P
DSPL
LOCAL
REMOTE
RUN
ENTER
STOP
RESET
Display Key
Scrolls through display monitors and Quick-
Start parameters, and allows access to all parameters.
Operation Mode Indicators:
DRIVE: Lit when in operation mode.
FWD: Lit when there is a forward run command input.
REV: Lit when there is a reverse run command input.
SEQ: Lit when the run command from the control circuit terminal or serial communication is enabled.
REF: Lit when the frequency reference from control circuit terminals FV or FI, or serial communication is enabled.
Display (LCD)
Displays set values of each function or monitoring values such as output frequency and current (2 line × 16 character alphanumeric).
Enter Key
Displays the current value of each parameter and allows new values to be entered.
Increase/Decrease Keys
Changes set values or parameter numbers.
∧ : Increment key
∨ : Decrement key
Operation Command Keys
Operation command keys operate the inverter.
STOP/RESET: Red LED lights after depressing STOP key.
Inverter operation is stopped. (resets operation after faults; reset is disabled while run command is ON)
RUN: Red LED lights after depressing RUN key.
Inverter operation begins
Operation Mode Selection Key
Alternate between REMOTE and LOCAL (digital operator) operation.
Figure 17 Digital Operator Display at Power-up
FP5/GP5 User’s Manual 35
Chapter 2 - Operation
LED Description
2.3 LED DESCRIPTION
Simple operation of the FP5/GP5 is possible, by using the quick-start displays.
Quick-Start Displays (Example of CIMR-P5U23P7)
Description Key Sequence Digital Operator Display Remarks
Power ON
Frequency reference setting/monitoring
Output frequency monitor
Output current monitor
Output power monitor
FWD/REV run command selection
Monitor selection
Acceleration time
Deceleration time
Input voltage
V/f pattern selection
Frequency reference gain
Frequency reference bias
Motor rated current
PID selection
Energy saving selection
Parameter Number/data
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
DSPL
Input Voltage
230.0 VAC
V/f Selection
60Hz Preset
Terminal FV Gain
100%
Terminal FV Bias
0%
Motor rated FLA
19.6A
PID Mode
Disabled
Energy Sav Sel
Disabled
Parameter n002
Oper Mode Select
Frequency Ref
0.0 Hz
Output Freq
0.0 Hz
Output Amps
0.0 A
Output Power
0.0 kW
Forward/Reverse
For
Monitor U-01
Frequency Ref
Accel Time 1
10.0 Sec
Decel Time 1
10.0 Sec
Depress
[ENTER] key to display the monitor value.
Set/read is enabled only during stop.
Depress
[ENTER] key to display data.
36 FP5/GP5 User’s Manual
Chapter 2 - Operation
Operation Mode Selection
2.4 OPERATION MODE SELECTION (n002, Oper Mode Select)
The FP5/GP5 has two operation modes: LOCAL and REMOTE
(see table below for description). These two modes can be selected by the digital operator “LOCAL/REMOTE” key only when operation is stopped.
The operation mode selected can be verified by observing the SEQ and
REF LEDs on the digital operator (as shown below). The operation mode is set to REMOTE (run by control circuit terminals FV and FI frequency reference and run command from control circuit terminals) prior to shipment. Multi-function contact inputs from control circuit terminals S3 to
S6 are enabled in both operation modes.
· LOCAL: Both frequency reference and run command are set by the digital operator. Remote SEQ and REF LEDs go OFF.
· REMOTE: Master frequency reference and run command can be selected as described in the table below.
Parameter n111, LOC/REM Change, will determine if the inverter will acknowledge a previously closed run input during a switchover from
LOCAL to REMOTE mode.
· When n111 is set to “Cycle Extern Run”, the inverter will not start if the run input is closed during the transition from LOCAL to
REMOTE.
· When n111 is set to “Acept Extern Run”, the inverter will immediately start if the run input is closed during the transition from
LOCAL to REMOTE.
Operation Mode Selection
LED
Display
LCD
Display
0 SEQ=OPR REF=OPR Operation by run command from digital operator
1 SEQ=TRM REF=OPR Operation by run command from control circuit terminal
2 SEQ=OPR REF=TRM Operation by run command from digital operator
3 SEQ=TRM REF=TRM Operation by run command from control circuit terminal
4 SEQ=OPR REF=COM Operation by run command from digital operator
5 SEQ=TRM REF=COM Operation by run command from control circuit terminal
6 SEQ=COM REF=COM Operation by run command from serial communication
7 SEQ=COM REF=OPR Operation by run command from serial communication
8 SEQ=COM REF=TRM Operation by run command from serial communication
Reference Selection
OFF Master frequency reference from digital operator
ON Master frequency reference from digital operator
OFF Master frequency reference from control circuit terminals
FV and FI
ON Master frequency reference from control circuit terminals
FV and FI
OFF Master frequency reference set by serial communication
ON Master frequency reference set by serial communication
ON Master frequency reference set by serial communication
ON Master frequency reference from digital operator
ON Master frequency reference from control circuit terminals
FV and FI
REF
LED
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
FP5/GP5 User’s Manual 37
This page intentionally left blank.
38 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
- CHAPTER 3 -
PROGRAMMING
FEATURES
Section Description
3 PROGRAMMING FEATURES
Page
3.1 FP5/GP5 P ARAMETERS (n001~n116) . . . . . . . . . . . 41
3.2 P
ARAMETER
S
ET
-
UP
& I
NITIALIZATION
. . . . . . . . . . . . . . . 49
3.3 FP5/GP5 O PERATION . . . . . . . . . . . . . . . . . . . . . . . . 50
Accel/decel time adjustment . . . . . . . . . . . . . . . . . . . . . . 50
Automatic fault retry . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Automatic restart after momentary power loss . . . . . . . 51
Carrier frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Current limit (Stall prevention). . . . . . . . . . . . . . . . . . . . 52
DC injection braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Energy savings control . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Frequency agree set point . . . . . . . . . . . . . . . . . . . . . . . . 57
Frequency meter or ammeter . . . . . . . . . . . . . . . . . . . . . 58
Frequency meter or ammeter calibration . . . . . . . . . . . . 58
Frequency signal adjustment. . . . . . . . . . . . . . . . . . . . . . 58
Jog operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Jump frequencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
MODBUS communication . . . . . . . . . . . . . . . . . . . . . . . 61
Motor overload detection . . . . . . . . . . . . . . . . . . . . . . . . 62
Multi-step speed selection. . . . . . . . . . . . . . . . . . . . . . . . 64
Phase loss detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PID Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Reverse run prohibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Soft-start characteristics . . . . . . . . . . . . . . . . . . . . . . . . . 68
Speed limit adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . 69
FP5/GP5 User’s Manual 39
Chapter 3 - Programming Features
Stopping method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Torque adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Torque detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Tripless operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
V/f pattern adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Slip compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
3.4 I NPUTS & O UTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Multi-function input signals . . . . . . . . . . . . . . . . . . . . . . 78
Analog input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Multi-function output signals . . . . . . . . . . . . . . . . . . . . . 83
40 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Parameters
3.1 FP5/GP5 Parameters (n001~n116)
No. Function Name
(LCD Operator Display)
n001 Parameter selection/ initialization
(Password)
n002 Operation mode selection
(Oper Mode Select)
n003 Input voltage
(Input Voltage)
n004 Stopping method
(Stopping Method)
Description Factory
Default
0: n001 read and set, n002~n116 read only
1: n001~n035 read and set, n036~n116 read only
2: n001~n053 read & set, n054~n116 read only
3: n001~n116 read and set
4, 5: Not used
6: 2-wire initialization (Japanese specifications)
7: 3-wire initialization (Japanese specifications)
8: 2-wire initialization (American specifications)
9: 3-wire initialization (American specifications)
LED Setting LCD Setting Operation Reference
0 SEQ=OPR REF=OPR Operator Operator
1 SEQ=TRM REF=OPR Terminal Operator
2 SEQ=OPR REF=TRM Operator Terminal
3 SEQ=TRM REF=TRM Terminal Terminal
4 SEQ=OPR REF=COM Operator Serial com
5 SEQ=TRM REF=COM Terminal Serial com
6 SEQ=COM REF=COM Serial com Serial com
7 SEQ=COM REF=OPR Serial com Operator
8 SEQ=COM REF=TRM Serial com Terminal
1 49
SEQ=TRM
REF=TRM
User
Setting
Ref.
Page
37
Unit: 0.1V
Setting range: 150.0~255.0V (510V for 460V units)
LED Setting LCD Setting Description
0 Ramp to stop Ramp to stop
1 Coast to stop Coast to stop
230.0V
(460.0V)
Ramp to
Stop
70
n005 Motor rotation
(Motor Rotation)
n006 Prohibit reverse operation
(Reverse Oper)
n007 Local/remote key function
(Local/Remote Key)
LED Setting LCD Setting Description
0 Rotate C.C.W. CCW shaft rotation
1 Rotate C.W. CW shaft rotation
LED Setting LCD Setting Description
0 Rev Allowed Reverse operation enabled
1 Rev Prohibited Reverse operation disabled
LED Setting LCD Setting
0 Disabled
1 Enabled
LED Setting LCD Setting Description
n008 Stop key function
(Oper STOP Key)
n009 Frequency reference setting method from operator
(Operator MOP)
n010 V/f pattern selection
(V/f Selection)
1 Enabled Stop key is always enabled
LED Setting LCD Setting
0 Enter not used
1 Enter key used
LED Setting LCD Setting Description
n011 Maximum frequency
(Max Frequency)
n012 Maximum voltage
(Max Voltage)
n013 Base frequency
(Base Frequency)
1 60 Hz Preset Fixed V/f pattern
Unit: 0.1Hz
Setting range: 50.0~400.0Hz
Unit: 0.1V
Setting range: 0.1~255.0V (510V for 460V units)
Unit: 0.1Hz
Setting range: 0.2~400.0Hz
Rotate
C.C.W.
Rev
Allowed
Enter key used
60 Hz
Preset
68
Enabled 37
Enabled -
-
-
75,96
60.0Hz 76
230.0V 76
60.0Hz 76
FP5/GP5 User’s Manual 41
Chapter 3 - Programming Features
FP5/GP5 Parameters
No. Function Name
(LCD Operator Display)
Description Factory
Default
User
Setting
Ref.
Page
n014 Mid. output frequency
(Mid Frequency)
n015 Mid. frequency voltage
(Mid Voltage)
n016 Minimum output frequency
(Min Frequency)
n017 Minimum output voltage
(Min Voltage)
n018 Acceleration time 1
(Accel Time 1)
n019 Deceleration time 1
(Decel Time 1)
n020 Acceleration time 2
(Accel Time 2)
n021 Deceleration time 2
(Decel Time 2)
n022 S-curve selection
(S-Curve Select)
Unit: 0.1Hz
Setting range: 0.1~399.9Hz
Unit: 0.1V
Setting range: 0.1~255.0V (510V for 460V units)
Unit: 0.1Hz
Setting range: 0.1~10.0Hz
Unit: 0.1V
Setting range: 0.1~50.0V (510V for 460V units)
Unit: 0.1s (1s for 1000s and above)
Setting range: 0.0~3600s
Unit: 0.1s (1s for 1000s and above)
Setting range: 0.0~3600s
Unit: 1s
Setting range: 0~255s
Unit: 1s
Setting range: 0~255s
LED Setting LCD Setting
0 No S-curve
1 0.2s
2 0.5s
3 1.0s
3Hz 76
17.2V
(34.4V)
76
1.5Hz 76
11.5V
(23.0V)
76
10.0s 50,96
10.0s 50,96
10.0s 50
10.0s 50
0.2s 68
n023 Display mode
(Display Units)
n024 Frequency reference 1
(Reference 1)
n025 Frequency reference 2
(Reference 2)
Setting Display
0 0.1Hz
1 0.1%
2~39 rpm (input # of motor poles)
40~3999 custom
Setting depends on n023 setting.
Range: 0~9999
Setting depends on n023 setting.
Range: 0~9999
0 -
0.0Hz 64,95
0.0Hz 64
n026 Frequency reference 3
(Reference 3)
n027 Frequency reference 4
(Reference 4)
Setting depends on n023 setting.
Range: 0~9999
Setting depends on n023 setting.
Range: 0~9999
0.0Hz 64
0.0Hz 64
n028 Not used - - - -
n029 Not used - - - -
n030 Jog frequency
(Jog Reference)
Setting depends on n023 setting.
Range: 0~9999
6.0Hz 60
n031 Frequency upper limit
(Ref Upper Limit)
n032 Frequency lower limit
(Ref Lower Limit)
Unit: 1%
Setting range: 0~109%
Unit: 1%
Setting range: 0~100%
100% 69
0% 69
n033 Motor rated current
(Motor Rated FLA)
Unit: 0.1A Range: 10~200% inverter rated current
Unit is 1A, when setting is more than 1,000A kVA dependent
62,96
42 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Parameters
No. Function Name
(LCD Operator Display)
n034 Motor thermal protection
(Motor OL Sel)
n035 Stop method selection -
OH1- for inverter overheat pre-alarm
(OH1 Stop Method)
LED Setting
Description Factory
Default
LCD Setting Description
0 Disabled Protection disabled
1 STD Motor/8 min General-purpose motor (time constant 8 min.)
STD
Motor/
8 min
User
Setting
2 STD Motor/5 min General-purpose motor (time constant 5 min.)
3 INV Motor/8 min Blower-cooled motor (time constant 8 min.)
4 INV Motor/ 5 min Blower-cooled motor (time constant 5 min.)
LED Setting LCD Setting Description
Continue
Oper
0 Ramp STOP/Decel 1 Ramp to stop - Decel 1
(fault)
Ref.
Page
62
-
1 Coast to STOP Coast to stop (fault)
2 Ramp STOP/Decel 2 Ramp to stop - Decel 2
(fault)
n036 Multi-function input selection 1
(Terminal S2 Sel)
3 Continue Oper Continue operation
(alarm) at 80% of frequency reference
LED LCD
Setting Setting Description
0 Reverse RUN (2W) Reverse run (2-wire sequence)
1 FWD/REV Cmd (3W) Fwd / Rev command (3-wire sequence)
2 Ext Fault (NO) External fault (normally open)
3 Ext Fault (NC) External fault (normally closed)
4 Fault Reset Fault reset
5 LOCAL/REMOTE Sel Local / Remote selection
6 COM/INV Sel Serial com/inverter selection (Fref, RUN command)
7 STOP Cmd/Dec2 NO Fast stop using Decel 2 (normally open)
8 STOP Cmd/Dec2 NC Fast stop using Decel 2 (normally closed)
9 Master Fref Sel Master freq. ref. selection (FV-open or
FI-closed)
10 Multi-Step Spd 1 Multi-step speed reference command 1
11 Multi-Step Spd 2 Multi-step speed reference command 2
12 Not Used Not used
13 JOG Command Jog reference (n030)
14 Acc/Dec Switch Accel / Decel time selection
15 Ext Baseblk (NO) External baseblock (normally open)
16 Ext Baseblk (NC) External baseblock (normally closed)
17 SpdSrch (MAXFRQ) Speed search from maximum frequency
18 SpdSrch (SETFRQ) Speed search from set frequency
19 Param Lockout Parameter setting enable / disable
20 PID I Reset PID integral value reset
21 PID Disable PID control enable / disable
22 Timer Start Cmd Timer function
23 OH3 Input External overheat alarm (OH3)
24 Ref Sample Hold Analog reference sample hold command
25 KEB Cmd (NO) Inertia ridethrough command (normally open)
26 KEB Cmd (NC) Inertia ridethrough command (normally closed)
27 Hold Command Accel / Decel hold command
28 PID Polarity Sel Inverse PID enable / disable
Reverse
RUN
(2W)
78
FP5/GP5 User’s Manual 43
Chapter 3 - Programming Features
FP5/GP5 Parameters
No. Function Name
(LCD Operator Display)
n037 Multi-function input 2
(Terminal S3 Sel)
n038 Multi-function input 3
(Terminal S4 Sel)
n039 Multi-function input 4
(Terminal S5 Sel)
n040 Multi-function input 5
(Terminal S6 Sel)
Description Factory
Default
User
Setting
Ref.
Page
Set items are same as n036.
(When n036=”FWD/REV Cmd (3W), “In Use By
Other” is displayed, and setting is prohibited)
Ext
Fault
(NO)
Set items are same as n036. Fault
Reset
Set items are same as n036.
(When n040=”Up/Down Control”, “In Use By Other is displayed, and setting is prohibited)
Set items are same as n036.
Multi-
Step
Spd 1
Multi-
Step
Spd 2
LED
Setting LCD Setting Description
29 Up / Down control Up / Down command (Terminal
S5=Up command, and terminal
S6=Down command).
LED
Setting LCD Setting Description
78
78
78
78
Fault 83 n041 Multi-function output selection 1
(Terminal MA Sel) 0 Fault Fault
1 During Running During running
2 At Speed Frequency agree
3 At Desired Speed Desired frequency agree
4 Freq Detection 1 Frequency detection 1
5 Freq detection 2 Frequency detection 2
6 OverTrq Det (NO) Over/Undertorque detection (normally open)
7 OverTrq Det (NC) Over/Undertorque detection (normally closed)
8 Baseblocked During baseblock
9 Operation Mode Local mode
10 Ready Inverter operation ready
11 Timer Output Timer function
12 Auto-Restarting During auto restart
13 OL Pre-Alarm OL pre-alarm (80% OL1 or OL2)
14 Freq Ref Loss Frequency reference loss
15 Set By COM Cntl Closed by serial communication
16 PID Fdbk Loss PID feedback loss
17 OH1 Alarm OH1 Alarm (set if n035 set to "3")
Set items are as same as n041 During
Running
n042 Multi-function output selection 2
(Terminal M1 Sel)
n043 Master analog input selection - FV or FI terminal
(Analog Input Sel)
LED LCD
Setting Setting FV FI Remarks
0 FV=MSTR FI=AUX Master Aux. Enable
1 FV=AUX FI=MSTR Aux. Master Enable
2 FV=RST FI=MSTR Fault reset Master Disable
Enable: FV/FI switchover function is enabled.
Disable: FV/FI switchover function is disabled.
Note: When PID is enabled (n084 ≠ 0),
FV terminal = PID reference, and
FI terminal = PID feedback.
LED
LCD Setting Description
FV=MSTR
FI=AUX
83
82
n044 Aux. analog input selection
(Terminal FI Sel)
n045 Frequency reference retention
(MOP Ref Memory)
n046 Operation method for frequency reference loss detection
(Ref Loss Detect)
0 0-10VDC 0~10V input (Jumper J1 must be cut)
1 4-20mA 4~20mA input
LED
LCD Setting Description
0 Memorize Fref Retained in frequency reference 1 (n024)
1 Not Memorized Not retained after power-down
LED
LCD Setting Description
0 Not detected No detection
1 Run @ n047 Fref Continue to run at n047 setting
4-20mA 82
Memorize
Fref
Not
Detected
44 FP5/GP5 User’s Manual
82
82
Chapter 3 - Programming Features
FP5/GP5 Parameters
No. Function Name
(LCD Operator Display)
n047 Frequency reference level at loss of Fref
(Fref Lvl@F Loss)
n048 Terminal FV gain
(Terminal FV Gain)
n049 Terminal FV bias
(Terminal FV Bias)
n050 Terminal FI gain
(Terminal FI Gain)
n051 Terminal FI bias
(Terminal FI Bias)
n052 Multi-function analog output AM
(Terminal AM Sel)
n053 Analog monitor gain
(Terminal AM Gain)
n054 Carrier frequency
(Carrier Freq Sel)
n055 Momentary power loss ridethrough method
(PwrL Selection)
n056 Speed search level - decel time fixed at 2 sec
(SpdSrch Current)
n057 Minimum baseblock time
(Min Baseblock t)
n058 V/f reduction level during speed search
(SpdSrch V/f)
n059 Power loss ridethrough time
(PwrL Ridethru t)
n060 Automatic retry attempts
(Num of Restarts)
n061 Fault contact selection during automatic retry
(Restart Sel)
n062 Jump frequency 1
(Jump Freq 1)
n063 Jump frequency 2
(Jump Freq 2)
n064 Jump frequency bandwidth
(Jump Bandwidth)
Description Factory
Default
Unit: 1%
Setting range: 0~100% of setting Fref
User
Setting
Ref.
Page
80% 82
Unit: 1%
Setting range: 0~200%
Unit: 1%
Setting range: -100~100%
Unit: 1%
Setting range: 0~200%
Unit: 1%
Setting range: -100~100%
LED
LCD Setting Monitor
0 Output Freq Output frequency
1 Output Amps Output current
2 Output kWatts Output power
3 DC Bus Voltage DC bus voltage
Unit: 0.01
Setting range: 0.01~2.00
Unit: 1
Setting range: 1~6 (x2.5kHz), 7~9 (custom pattern)
LED LCD
Setting Setting Method
0 Not Provided Not provided
1 2 Seconds Max Continuous operation after power recovery within 2s
2 CPU Power Active Continuous operation after power recovery within control logic time (no fault output)
Unit: 1% Setting range: 0~200%
100% = inverter rated current
Unit: 0.1s
Setting range: 0.5~10.0s
Unit:1%
Setting range: 0~100%
Unit: 0.1s
Setting range: 0.0~2.0s
Unit: 1 time
Setting range: 0~10
LED
Setting LCD Setting Description
0 Activate Flt Rly Closed during fault retry
1 No Rly Output Open during fault retry
Unit: 0.1Hz
Setting range: 0.0~400.0Hz
Unit: 0.1Hz
Setting range: 0.0~400.0Hz
Unit: 0.1Hz
Setting range: 0.0~25.5Hz
100% 59,96
0% 59,96
100% 59
0% 59
Output
Freq kVA dependent kVA dependent kVA dependent
Activate
Flt Rly
58
1.00 58 kVA dependent
Not
Provided
51
51
110% 74
71
-
-
0 51
-
0.0Hz 60
0.0Hz 60
1.0Hz 60
FP5/GP5 User’s Manual 45
Chapter 3 - Programming Features
FP5/GP5 Parameters
No. Function Name
(LCD Operator Display)
n065 Elapsed timer selection
(Elapsed Timer)
n066 Elapsed timer 1
(Elapsed Time 1)
n067 Elapsed timer 2
(Elapsed Time 2)
n068 DC injection current
(DCInj Current)
n069 DC injection time at stop
(DCInj Time @ Stop)
n070 DC injection time at start
(DCInj Time @ Start)
n071 Torque compensation gain
(Torq Comp Gain)
n072 Stall prevention during deceleration
(StallP Decel Sel)
n073 Current limit/Stall prevention level during acceleration
(StallP Accel Lvl)
n074 Current limit/Stall prevention level during running
(StallP Run Level)
n075 Frequency agree set point
(Freq Det Level)
n076 Frequency agree detection width
(Freq Det Width)
n077 Over/Undertorque detection OL3
(Torq Det Sel)
Description Factory
Default
LED
LCD Setting Description
0 Time Power is ON Accumulate time during power on
1 Time Running Mtr Accumulate time during running
Time
Running
Mtr
User
Setting
Ref.
Page
* -
-
Unit: 1 hour Range: 0~9999
* Initial value becomes 0 only when initialized during CPF4 occurrence.
* -
Unit: 10,000 hours Range: 0~27
* Initial value becomes 0 only when initialized during CPF4 occurrence.
50% 54,75 Unit: 1%
Setting range: 0~100%
100% = inverter rated current
Unit: 0.1s
Setting range: 0.0~10.0s
Unit: 0.1s
Setting range: 0.0~10.0s
0.0s 54
0.0s 55,75
Unit: 0.1
Setting range: 0.0~3.0
(normally, no adjustment is necessary)
LED
Setting LCD Setting
0 Disabled
1 Enabled
1.0 72
Enabled 54
Unit: 1% Setting range: 30~200%
When level is set to 200%, current limit during acceleration is disabled.
Unit: 1% Setting range: 30~200%
When level is set to 200%, current limit during running is disabled.
Unit: 0.1Hz
Setting range: 0.0~400.0Hz
Unit: 0.1Hz
Setting range: 0.0~25.5Hz
LED
Setting LCD Setting Description
0 Disabled Detection disabled
1 OT/Spd Agree/Alm Overtorque detection at speed agree; continue running after detection.
(Alarm)
2 OT/Run/Alm Overtorque detection at run; continue running after detection. (Alarm)
3 OT/Spd Agree/Flt Overtorque detection at speed agree; coast to stop after detection. (Fault)
4 OT/Run/Flt Overtorque detection at run; coasts to stop after detection. (Fault)
5 UT/Spd Agree/Alm Undertorque detection at speed agree; continue running after detection. (Alarm)
6 UT/Run/Alm Undertorque detection at run; continue running after detection. (Alarm)
7 UT/Spd Agree/Flt Undertorque detection at speed agree; coast to stop after detection.
(Fault)
8 UT/Run/Flt Undertorque detection at run; coast to stop after detection. (Fault) kVA dependent kVA dependent
0.0Hz 57,84
2.0Hz 84
Disabled
52
53
73
46 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Parameters
No. Function Name
(LCD Operator Display)
n078 Over/Undertorque detection level OL3
(Torq Det Level)
n079 Over/Undertorque detection delay time OL3
(Torq Det Time)
n080 On-delay timer
(On-Delay Timer)
n081 Off-delay timer
(Off-Delay Timer)
n082 DB resistor overheat function rH
(DB Resistor Prot)
n083 Input phase loss detection level SPI
(In Ph Loss Lvl)
n084 PID selection
(PID Mode)
n085 Feedback calibration gain
PID
(PID Fdbk Gain)
n086 Proportional gain PID
(PID P Gain)
n087 Integral time PID
(PID I Time)
n088 Derivative time PID
(PID D Time)
n089 Limit of integral value PID
(PID I Limit)
n090 Feedback loss detection
PID
(PID FdbkLoss Sel)
n091 Feedback loss detection level PID
(PID FdbkLoss Lvl)
n092 Feedback loss detection delay time PID
(PID FdbkLoss Tim)
n093 PID output selection
(PID Output Sel)
n094 Sleep function start level
PID
(Sleep Start Lvl)
n095 Sleep function delay time
PID
(Sleep Delay Time)
Unit: 1%
Description Factory
Default
Setting range: 30~200%
100% = inverter rated current
Unit: 0.1s
Setting range: 0.1~10.0s
Unit: 0.1s
Setting range: 0.0~25.5s
Unit: 0.1s
Setting range: 0.0~25.5s
LED
Setting LCD Setting Description
0 Disabled No DB protection calculated or provided
1 Enabled Protection provided for Yaskawa 3% ED resistor
Unit: 1%
Setting range: 1~100%
When setting is 100%, this function is disabled.
LED
Setting LCD Setting Description
0 Disabled PID disabled
1 Enabled D=Fdbk PID enabled
2 Enabled D=Fdfwd PID w / Feed forward
3 Enabled RevFdbk PID w / Inverted feedback
Unit: 0.01
Setting range: 0.00~10.00
Unit: 0.01
Setting range: 0.0~10.0
Unit: 0.1s
Setting range: 0.0~100.0s
Unit: 0.01s
Setting range: 0.00~1.00s
Unit: 1%
Setting range: 0~109%
LED
Setting LCD Setting Description
0 Disabled Detection is disabled.
1 Multi-function Output Only Detection is enabled.
Unit: 1%
Setting range: 0~100%
Unit: 0.1s
Setting range: 0.0~25.5s
LED
Setting LCD Setting
0 Not Inverted
1 Inverted
Unit: 0.1Hz
Setting range: 0.0~400.0Hz
Unit: 0.1s
Setting range: 0.0~25.5s
160% 74
0.1s 74
0.0s 80
0.0s 80
Disabled
7% 65
Disabled
1.00 66
1.0 66
10.0s 66
0.00s 66
100% 67
Disabled
Not
Inverted
User
Setting
Ref.
Page
66,96
0% -
-
-
1.0s 66
67
0.0Hz 67
0.0s 67
FP5/GP5User’s Manual 47
Chapter 3 - Programming Features
Parameter Set-up & Initialization
No. Function Name
(LCD Operator Display)
n096 Energy saving selection
(Energy Save Sel)
n097 Energy saving gain K2
(Energy Save Gain)
n098 Energy saving voltage lower limit at 60Hz
(EngSavVLLmt@60Hz)
n099 Energy saving voltage lower limit at 6Hz
(EngSavVLLmt@6Hz)
n100 Time of average kW -
Energy saving
(EngSavTime/AvgkW)
n101 Modbus time over detection
(MODBUS Timeout)
Description Factory
Default
LED
Setting LCD Setting Description
0 Disabled Energy saving is disabled.
1 Enabled Energy saving is enabled.
Disabled
Unit: 0.01
Setting range: 0.00~655.0 (0=No energy saving) kVA dependent
Unit: 1%
Setting range: 0~120%
Unit: 1%
Setting range: 0~25%
Unit: 1 = 25ms
Setting range: 0~200
n102 MODBUS stop method at communication error CE
(MODBUS Fault Stop)
n103 MODBUS frequency reference unit
(MODBUS Fref Unit)
n104 MODBUS slave address
(MODBUS Address)
n105 MODBUS BPS selection
(MODBUS Baud Rate)
n106 MODBUS parity selection
(MODBUS Parity) n107 Slip compensation gain
(Slip Comp Gain) n108 Motor no-load current
(Mtr No-Load Amp) n109 Slip compensation primary delay time constant
(Slip Comp Delay) n110 Operator connection fault detection selection
(Oper Detect Flt) n111 Local / Remote changeover function selection
(LOC/REM Change)
LED
Setting LCD Setting Description
0 Disabled Time Over Detection is disabled.
1 Enabled Time Over Detection is enabled.
LED
Setting LCD Setting Stop method
0 Ramp STOP/Decel 1 Ramp to stop - Decel 1 (fault)
1 Coast to STOP Coast to stop (fault)
2 Ramp STOP/Decel 1 Ramp to stop - Decel 2 (fault)
3 Continue Oper Continue operation (alarm)
LED
Setting LCD Setting Stop method
0 1=0.1Hz 0.1Hz / 1
1 2=0.01Hz 0.01Hz / 1
2 3000=100% 100% / 30000
3 1=0.1% 0.1% / 1
Unit: 1
Setting range: 0~31
LED
Setting LCD Setting
0 2400 Baud
1 4800 Baud
2 9600 Baud
LED
Setting LCD Setting
0 No parity
1 Even parity
2 Odd parity
Unit: 0.1% [of Base Frequency (n013)]
Setting range: 0.0 ~ 9.9%
Unit: 1% [of Motor Rated Current (n033)]
Setting range: 0 ~ 99%
Unit: 0.1s
Setting range: 0.0 ~ 25.5s
LED
Setting LCD Setting
0: Disabled
1: Enabled
LED
Setting LCD Setting
0 Cycle Extern RUN command
1 Acept Extern RUN command
Coast to
STOP
No parity
Cycle
Extern
RUN
User
Setting
Ref.
Page
55,96
55
75% 55
12% 55
1 -
Enabled
1=0.1Hz
9600 Baud
2.0s 77
Disabled
-
-
62
1 62
61
61
0.0% 77
30% -
-
37
48 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
No. Function Name
(LCD Operator Display) n112 Low frequency OL start point
(Low Freq OL2 Start) n113 0Hz continuous operation level
(OL2_Level_@_0 Hz) n114 Not used n115 kVA selection
(Inverter kVA Sel) n116 CT / VT selection
(CT / VT Selection)
Description Factory
Default
Unit: 0.1Hz
Setting range: 0.0 ~ 10.0Hz
User
Setting
Ref.
Page
6.0Hz -
Unit: 1%
Setting range: 25 ~ 100%
50% -
- - - -
Unit: 1
Setting range: PC5 (0~8, 20~29), P5(9~F, 2A~35) kVA
Dependent
-
LED
Setting LCD Setting Description
0: CT Operation Constant torque
1: VT Operation Variable torque
- 7,9
3.2 PARAMETER SET-UP & INITIALIZATION
Parameter Selection/Initialization (n001, Password)
The following table describes data which can be set or read when parameter n001 is set.
Setting Parameters that can be set Parameters that can be viewed
0
(parameter read-only)
1
(factory default)
n001 n001 to n116
n001 to n035 n001 to n116
2 n001 to n053 n001 to n116
3 n001 to n116 n001 to n116
4, 5 Not used
6 Initialize: 2-wire sequence (Japanese specifications)
7 Initialize: 3-wire sequence (Japanese specifications)
8 Initialize: 2-wire sequence (American specifications)
9 Initialize: 3-wire sequence (American specifications)
FP5/GP5 User’s Manual 49
Chapter 3 - Programming Features
FP5/GP5 Operation
3.3 FP5/GP5 OPERATION
Accel/Decel Time Adjustment
Output
Frequency
Accel Time 1
(n018)
Decel Time 1 (n019)
Accel Time 2 (n020)
Decel Time 2* (n021)
Decel Time 1* (n019)
Time
FWD (REV) Run Command
ON OFF ON
Accel/Decel Time Selection
(Terminals S2 to S6)
ON
* When “deceleration to stop” is selected (n004 = “Ramp to STOP”)
Figure 18 Timing Diagram of Accel/Decel Time Adjustment
When any of the multi-function input terminal selections (n036, n037, n038,
n039 or n040) is set to “Acc/Dec Switch”, accel/decel times can be selected by opening or closing the appropriate terminal (S2, S3, S4, S5 or S6).
At OPEN: n018 (accel time 1), n019 (decel time 1)
At CLOSED: n020 (accel time 2), n021 (decel time 2)
Parameter No. Name Unit Setting Range Factory Default
n018 Acceleration time 1 0.1s * 0.0 to 3600s 10.0s
n019 Deceleration time 1 0.1s * 0.0 to 3600s 10.0s
n020 Acceleration time 2 0.1s * 0.0 to 3600s 10.0s
n021 Deceleration time 2 0.1s * 0.0 to 3600s 10.0s
* Setting unit is 1s for 1,000s and above.
· Acceleration time
Sets the time necessary for the output frequency to move from 0Hz to maximum output frequency (n011).
· Deceleration time
Set the time necessary for the output frequency to move from maximum output frequency (n011) to 0Hz.
50 FP5/GP5User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
Automatic Fault Retry (n060, Num of Restarts)
After a fault occurs, the inverter can automatically restart. The number of retry attempts can be set up to 10 times via parameter n060. The inverter can be set to automatically restart after the following faults occur:
· Overcurrent (OC)
· Overvoltage (OV)
· Undervoltage PUV (UV1)
· Ground fault (GF)
· Regenerative transistor fault (RR)
The number of retry attempts are cleared to “0” in the following cases:
· If no other fault occurs within 10 minutes after retry.
· When the fault reset signal is ON (closed) after the fault is detected.
· Power supply is turned OFF.
Automatic Restart After Momentary Power Loss (n055, PwrL Selection)
When momentary power loss occurs, operation restarts automatically. The run command must remain closed for this feature to function properly.
LED Setting LCD Setting Description
0 Not Provided Not provided (factory default)
1 * 2 Seconds Max Continuous operation after power recovery within 2 seconds
2 ** CPU Power Active Continuous operation after power recovery within control logic time (no fault output)
* Holds the operation signal to continue operation after recovery from momentary power loss.
** When “CPU Power Active” is selected, operation restarts if power supply voltage returns to its normal level (level before power loss). No fault signal is output.
Carrier Frequency (n054, Carrier Freq Sel)
This function sets the inverter output transistor switching frequency (carrier frequency). This is used to reduce motor noise and leakage current.
The factory setting for carrier frequency is the maximum allowable carrier frequency at which inverter rated current can continuously be generated. Consult the factory when increasing the carrier above the default values.
Carrier Frequency (kHz) Metallic Noise from Motor Leakage Current
LED Setting LCD Setting
1 2.5
2 5.0
3 8.0
Louder Smaller
4 10.0
5 12.5
6 15.0
Inaudible Larger
FP5/GP5 User’s Manual 51
Chapter 3 - Programming Features
FP5/GP5 Operation fc = carrier frequency
2.5kHz
fc = carrier frequency
2.5kHz
1.0kHz
fc = 12 fout 1.0kHz
fc = 24 fout
83.3Hz 208.3Hz
fout
41.6Hz 104.1Hz
n054 = “Synchronous 1” n054 = “Synchronous 2” fc = carrier frequency
2.5kHz
fout
1.0kHz
fc = 36 fout
27.7Hz 69.4Hz
n054 = “Synchronous 3” fout
Figure 19 Custom Setting of Carrier Frequency Patterns
Current Limit (Stall Prevention)
This function automatically adjusts the output frequency in response to an increase in load current to continue operation without tripping the inverter.
· Stall Prevention Level During Acceleration (n073, StallP Accel Lvl)
The current limit level during acceleration can be set in units of 1%
(inverter rated current = 100%).
Factory setting: kVA dependent
A setting of 200% disables current limit during acceleration. During acceleration, if the output current exceeds the value set for n073, acceleration stops and frequency is maintained. When the output current goes down below the value set for parameter n073, acceleration resumes at the normal acceleration rate.
52 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
Motor Current n073
Output Frequency
Time
Time
* Holds the output frequency to limit the load current.
*
Figure 20 Stall Prevention During Acceleration
In the constant output area [output frequency
≥
base frequency (n013)], the current limit level during acceleration is changed by the following equation:
Current Limit Level During
Accel in Constant Output Area
=
Current Limit Level During
Acceleration (n073)
×
Base Frequency (n013)
Output Frequency
· Stall Prevention Level During Running (n074, StallP Run Level)
The stall prevention level during running can be set in units of 1%
(inverter rated current = 100%).
Factory setting: kVA dependent
A setting of 200% disables current limit during running. During speed agree, if the output current exceeds the value set for parameter n074, then deceleration is initiated.
While the output current exceeds the value set for n074, deceleration continues. When the output current goes below the value set for parameter n074, acceleration begins at the normal acceleration rate bringing the motor to the set frequency.
Motor Current n074
Time
Output Frequency
Time
* Decreases the output frequency to limit the load current.
*
Figure 21 Stall Prevention During Running
FP5/GP5 User’s Manual 53
Chapter 3 - Programming Features
FP5/GP5 Operation
· Stall prevention during deceleration (n072, StallP Decel Sel)
To prevent overvoltage during deceleration, the inverter automatically extends the deceleration time according to the value of main circuit DC voltage. When using an optional braking resistor for the FP5/GP5, set parameter n072 to”0”.
LED Setting LCD Setting Stall Prevention During Deceleration
0 Disabled Disabled (when optional braking resistor mounted)
1 Enabled Enabled (factory default)
Frequency
Extends the deceleration time to prevent overvoltage fault.
Time
Set Deceleration Time
Figure 22 Stall Prevention During Deceleration
DC Injection Braking
· DC Injection Braking Current (n068, DCInj Current)
DC injection braking current can be set in increments of 1%.
(100% = inverter rated current)
· DC injection Braking Time at Stop (n069, DCInj Time @ Stop)
DC injection braking time at stop can be set in increments of 0.1 second. When parameter n069 is set to “0”, DC injection braking at stopping is disabled. n016
Min. Output Frequency n069
DC injection Braking
Time at Stop
Figure 23a DC Injection Braking Time at Stop
When coast to stop is selected in the stopping method selection (n004),
DC injection braking at stop is disabled.
54 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
· DC injection Braking Time at Start (n070)
DC injection braking time at start can be set in increments of 0.1 second. When parameter n070 is set to “0”, DC injection braking at starting is disabled. n016
Min. Output Frequency n070
DC injection Braking
Time at Start
Figure 23b DC Injection Braking Time at Start
Energy Saving Control
To enable energy saving control, set energy saving selection (n096, Energy
Sav Sel) to “1”.
LED Setting LCD Setting Description
0 Disabled Energy saving is disabled (factory default).
1 Enabled Energy saving is enabled.
Since the parameters used in the energy saving control mode have been preset at the factory to the optimum values, it is not necessary to adjust them under normal operation. If your motor characteristics differ greatly from those of standard induction motors, refer to the following description to adjust the parameters.
Energy Saving Control Mode
· Energy Saving Gain K2 (n097, Energy Save Gain)
Use this energy saving gain when running in the energy saving control mode to calculate the voltage at which motor efficiency will be greatest, and set it as the output voltage reference. This value is preset at the factory to the standard induction motor value prior to shipment. As the energy saving gain increases, output voltage decreases.
· Energy Saving Voltage Lower Limit ( n098, EngSavVLLmt@60Hz; n099, EngSavVLLmt@ 6Hz)
Sets the output voltage lower limit. If the voltage reference value calculated in the energy saving mode is smaller than the specified lower
FP5/GP5 User’s Manual 55
Chapter 3 - Programming Features
FP5/GP5 Operation limit, this lower limit value is output as the voltage reference value. The lower limit value is set in order to prevent stalling at light loads. Set voltage limits at 6Hz and 60Hz; a value obtained by linear interpolation should be used to set any limit values other than at 6Hz or 60Hz. Setting is made as a percentage of motor rated voltage.
Voltage
255V* n098 n099
Lower Limit
6Hz 60Hz
Frequency
* This value is doubled for 460V class inverters.
Figure 24 Energy Saving Voltage Lower Limit
56 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5Operation
Frequency Agree Set Point (n075, Freq Det Level)
When multi-function contact output selections n041 or n042 are set to “Freq
Det 1” or “Freq Det 2”, frequency detection is enabled. This function is activated when the output frequency is above or below the frequency agree set point (n075).
· Output frequency
≤
Frequency agree set point
Set n041 or n042 to “Freq Det 1”.
Release Width
+2Hz
Frequency Agree Set Point n075
Output Frequency
Frequency Detection
Signal
ON ON
Figure 26 Frequency Agree Set Point Example
(Fout
≤
Frequency Agree Set Point)
· Output frequency
≥
Frequency agree set point
Set n041 or n042 to “Freq Det 2”.
Release Width
-2Hz
Frequency Agree Set Point n075
Output Frequency
Frequency Detection
Signal
ON
Figure 27 Frequency Agree Set Point Example
(Fout ≥ Frequency agree set point)
FP5/GP5 User’s Manual 57
Chapter 3 - Programming Features
FP5/GP5 Operation
Frequency Meter or Ammeter (n052, Terminal AM Sel)
This parameter selects whether the signal (on terminals AM and AC) is proportional to output frequency, output current, output power, or DC bus voltage for external monitoring.
Setting Analog Monitor Output Selection
Output Freq Output frequency (10V/max. frequency) - factory default
Output Amps Output current (10V/inverter rated current)
Output kWatts Output power (10V/inverter rated power)
DC Bus Voltage DC bus voltage [10V/400VDC (230V class), 10V/800VDC (460V class)]
Frequency Meter or Ammeter Calibration (n053, Terminal AM Gain)
This function is used to adjust the analog monitor output signal level.
Frequency Meter/Ammeter
(3V 1mA full-scale)
Analog
Output n053
AM
+ -
FM
10V
AC
3V n0
53
=1
.0
n053=
0.3
0 100%
Monitor Variable
Figure 28 Frequency Meter/Ammeter Calibration
Parameter n053 determines the slope of the signal output on terminal AM for the variable being monitored. Increasing this value increases the slope.
Refer to Figure 28.
Frequency Signal Adjustment
When the frequency reference is given by an analog signal at control circuit terminals FV and FI, the relation between analog voltage (or current) and frequency reference can be set.
Frequency Reference
Max. Output Frequency
×
Gain
100
Max. Output Frequency
×
Bias
100
0V 10V
(4mA) (20mA)
( ) indicates when current reference input is selected.
Figure 29 Frequency Signal Adjustment
58 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
· Terminal FV Gain (n048, Terminal FV Gain)
The analog input voltage value for the maximum output frequency
(n011) can be set in units of 1%, from 0 to 200%.
Factory setting: 100%
· Terminal FV Bias (n049, Terminal FV Bias)
The frequency reference that is generated when the analog input is 0V can be set in units of 1%, from -100% to 100%. (n011: maximum output frequency = 100%)
Factory setting: 0%
· Terminal FI Gain (n050, Terminal FI Gain)
The analog input current value for the maximum output frequency
(n011) can be set in units of 1%, from 0 to 200%.
Factory setting: 100%
· Terminal FI Bias (n051, Terminal FI Bias)
The frequency reference that is generated when the analog input is 4mA can be set in units of 1%, from -100% to 100%. (n011: maximum output frequency = 100%)
Factory setting: 0%
· Examples
To operate the inverter with a frequency reference of 0% to 100% at a 0 to 5V input:
Max. Output
Frequency (100%)
0%
Figure 30 Frequency Signal Adjustment Example - 0 to 5V input
Gain: Parameter n048 = “200”
Bias: Parameter n049 = “0”
FP5/GP5 User’s Manual 59
Chapter 3 - Programming Features
FP5/GP5 Operation
To operate the inverter with a frequency reference of 50% to 100% at a
0 to 10V input:
Max. Output
Frequency (100%)
50%
0V 10V
Figure 31 Frequency Signal Adjustment Example - 0 to 10V input
Gain: Parameter n048 = “100”
Bias: Parameter n049 = “50”
Jog Operation
Multi-function inputs (Terminals S2 to S6) can be programmed to function as a jog reference selection. Operation can then be enabled at the jog frequency reference set in parameter n030 by activating this input. A
“RUN” command must also be given to start the inverter. When multistep speed references 1 or 2 are input simultaneously with the jog frequency reference, the jog frequency reference has priority.
Name Parameter No. Setting
Jog frequency reference n030 6.0Hz (Factory default)
Multi-function contact input selection (S2 to S6) n036, n037, n038, n039, n040
Set to “Jog Command” for any parameter.
Jump Frequencies (n062, Jump Freq 1; n063, Jump Freq 2, n064, Jump Bandwidth)
This function enables the “jumping” of critical frequencies so that systems can operate without excessive vibration or noise. Setting the value to
0.0Hz disables this function.
Set jump frequency 1 or 2 such that n062
≤
n063. If this condition is not satisfied, the inverter displays the parameter setting error “OPE6”.
Output Frequency n063 n062 n064 n064 Frequency
Reference
Figure 32 Jump Frequencies
60 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
MODBUS Communication
The FP5/GP5 can perform serial transmission by using a programmable controller (PLC) and MODBUS communication. MODBUS is composed of one master PLC and 1 to 31 (maximum) slave inverters. In signal transmission between master and slave units, the master unit always starts transmission and the slave units respond to it.
The master unit performs signal transmission with one slave unit at a time. Hence, different address numbers must be assigned to each slave unit in advance and the master unit specifies a number to perform signal transmission. The slave unit which receives the command from the master unit executes the function and returns the response to the master unit.
Communication Specifications
· Interface: RS-485, RS-422 (communication interface card SI-K2/P must be mounted.)
· Synchronization: Asynchronous
· Transmission parameter: Baud rate: selectable from 2400, 4800,
9600 BPS (parameter n105)
Data length: fixed at 8 bits
Parity: parity/no parity, even/odd selectable (parameter n106)
Stop bit: fixed at 1 bit
· Protocol: In accordance with MODBUS
· Maximum number of units to be connected: 31 units (when RS-485 is used)
Data to be Sent/Received by Communication
Data to be sent/received by communication are run commands, frequency reference, fault contents, inverter status and parameter setting/reading.
· Operation Mode Selection (n002, Oper Mode Select)
Select the run command and frequency reference input method in parameter n002. To provide a run command and/or frequency reference by communication, set this parameter to a selection that contains
“COM” for SEQ and/or REF. Regardless of this selection, monitoring of running status, parameter setting/reading, fault reset and multi-function input commands from the PLC are possible. The multi-function input command becomes “OR” with the command input from control circuit terminals S2 to S6.
FP5/GP5 User’s Manual 61
Chapter 3 - Programming Features
FP5/GP5 Operation
· MODBUS Frequency Reference Unit (n103, MODBUS Fref Unit)
The frequency reference units from the PLC and in the frequency reference and output frequency monitors (by communication) are set with parameter n103. The output frequency resolution of the FP5/GP5 is 0.1Hz. Even if the frequency reference unit is changed to 0.01Hz in parameter n103, the value in the hundredth digit of the received frequency reference is rounded off internally. When 30,000/100% in units of 0.1% is selected, the value is rounded off in the same way.
· MODBUS Slave Address (n104, MODBUS Address)
Sets the slave address number. It is necessary to set the address number so that it will not overlap with the address number of another slave unit connected on the same transmission line.
Note: To change the values set in parameters n104 to n106 and enable new settings, it is necessary to cycle power after entering the desired values.
Motor Overload Detection
The FP5/GP5 protects against motor overload with a UL-recognized, built-in electronic thermal overload relay function.
· Motor Rated Current (n033, Motor Rated FLA)
Set to the rated current value shown on the motor nameplate.
Note: setting to 0.0A disables the motor overload protection function.
· Motor overload protection selection (n034, Motor OL Sel)
LED Setting LCD Setting Electronic Thermal Characteristics
0 Disabled Protection disabled
1 STD Motor / 8 min Applied to general-purpose motor, standard rating (Class 20 overload)
2 STD Motor / 5 min Applied to general-purpose motor, short time rating (Class 10 overload)
3 INV Motor / 8 min Applied to blower-cooled / inverter duty motor, standard rating (Class 20 overload)
4 INV Motor / 5 min Applied to blower-cooled / inverter duty motor, short time rating (Class 10 overload)
The electronic thermal overload function estimates motor temperature, based on inverter output current and time, to protect the motor from overheating. When the electronic thermal overload relay is activated, an
“oL1” error occurs, shutting OFF the inverter output and preventing excessive overheating in the motor.
When operating with one inverter connected to one motor, an external thermal relay is not needed. When operating several motors with one inverter, install a thermal relay on each motor. In this case, set parameter n034 to “Disabled”.
62 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
· General-purpose and Blower-cooled Motors
Induction motors are classified as general-purpose or blower-cooled motors, based on their cooling capabilities. Hence, the motor overload detection function operates differently for each of these two motor types.
Cooling Effectiveness Torque Characteristics
Electronic Thermal
Overload
180
155
140
60s
Short time
Standard
Rating
Effective when operated at
50/60Hz from commercial power supply.
100
80
55
38
0
20
Frequency (Hz)
Base Frequency 60Hz
(V/f for 60Hz, 230V Input Voltage)
During continuous operation at low speeds, the load must be limited in order to limit motor temperature rise.
“OL1” error (motor overload protection is enabled when motor is continuously operated at 50/60Hz or less at
100% load).
180
150
100
60s
Short time
Standard
Rating
Effective when operated at low speeds (approx. 6Hz).
55
38
0
6 60 120
Frequency (Hz)
Base Frequency 60Hz
(V/f for 60Hz, 230V Input Voltage)
Use blower-cooled motor for continuous operation at low speeds.
Effective when operated at low speeds (approx. 6Hz).
FP5/GP5 User’s Manual 63
Chapter 3 - Programming Features
FP5/GP5 Operation
Multi-Step Speed Selection
This function allows the programming of up to 4 preset speeds, through multi-function contact input selections.
4-step speed selection
n002 = “SEQ=X REF=OPR”, where “X” can be TRM, OPR, or COM
n024 = 30.0Hz (factory default = 0.0Hz)
n025 = 40.0Hz (factory default = 0.0Hz)
n026 = 50.0Hz (factory default = 0.0Hz)
n027 = 60.0Hz (factory default = 0.0Hz)
n039 = 9 (multi-function contact input terminal S5)
n040 = 10 (multi-function contact input terminal S6)
FWD Run/Stop
REV Run/Stop
External Fault
Fault Reset
Multi-step Speed Ref. 1
Multi-step Speed Ref. 2
S1
S2
S3
S4
S5
S6
SC
Multi-function
Contact Input
Figure 33 Multi-step Speed Selection - Control Circuit Terminals
(n026)
50.0Hz
(n027)
60.0Hz
Frequency
Reference
(n024)
30.0Hz
(n025)
40.0Hz
FWD (REV) Run/Stop
ON
Multi-step Speed Ref. 1
(Terminal S5)
Multi-step Speed Ref. 2
(Terminal S6)
ON
ON
ON
Figure 34 Multi-step Speed Operation - Timing Diagram
64 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
Phase Loss Protection
· Input Phase Loss Detection (n083, In Ph Loss Lvl)
The input phase loss detection circuit monitors the DC bus current ripple and activates when one of the input phases are lost. The detection circuit calculates the maximum and minimum values of the DC bus voltage in
1.28 second intervals, and compares the difference (
∆
V) between these values with the input phase loss detection level (n083). If
∆
V
≥
n083, then input phase loss is detected; and after the input phase loss detection delay time (fixed at approximately 10 seconds), an SPI fault occurs, and the motor coasts to stop.
No. Name Description
n083 Input phase loss detection level Unit: 1%
Setting range: 1 to 100% of input voltage
Factory
Default
7%
Input phase loss detection is disabled in the following cases:
· Parameter n083 is set to “100%”
· A Stop command is input
· Input magnetic contactor (MC) shuts OFF
· CPU A/D converter fault (CPF5)
· During deceleration
· Output current
≤
30% of Inverter rated current
FP5/GP5 User’s Manual 65
Chapter 3 - Programming Features
FP5/GP5 Operation
PID Control
To enable PID control, set PID selection (n084) to “Enabled”, according to the description below.
LED Setting LCD Setting Description
0 Disabled PID disabled (factory default)
1 Enabled D=Fdbk PID enabled (deviation is D-controlled.)
2 Enabled D=Fdfwd PID with feed forward (feedback value is D-controlled)
3 Enabled Rev Fdbk PID with inverted feedback
Then select the PID control setpoint value and detected feedback value setpoint as follows:
· Setpoint Value Selection
The control circuit terminal FV voltage signal (0 to 10V) or multi-step speed parameters n024 to n027 can be used to select the PID setpoint value.
Control circuit terminal FV voltage signal:
Set operation mode selection (n002) to “SEQ=OPR REF=TRM” or
“SEQ=TRM REF=TRM”.
Multi-step speed constants (n024 to n027):
Set operation mode selection (n002) to “SEQ=OPR REF=OPR” or
“SEQ=TRM REF=OPR”.
(combination of multi-step speed reference and jog frequency reference)
· Detected Value Setting
The control circuit terminal FI current signal (4 to 20mA) or voltage signal (0 to 10V) can be used to set the PID detected value.
Control circuit terminal FI current signal:
Set aux. analog input selection (n044) to “4-20mA”.
Control circuit terminal FI voltage signal:
Set operation mode selection (n044) to “0-10VDC”.
(Cut jumper J1 on the control PCB board.)
66 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
Intended
Value
+
(Deviation) -
Detected
Value n085
Feedback
Calibration
Gain n084
1
D n088
+
+
2
Z -1
3
P
I Limit n087 n089
D
1 or 3 n088
2
+
+
+
±109%
Limit n084
0 n093
1
0
Sleep
Function n094, n095 n084
1, 2, or 3
Frequency
Reference
Inverted
Characteristic
Enabled
Figure 35a PID Control Block Diagram
Notes:
1) Value I is reset to”0” in the following cases:
· When operation stops
· When the integral value reset signal is input by multi-function contact input selection (Any of parameters n036 to n040 are set to “PID I Reset”).
2) The upper limit of value I can be set by parameter n089.
Increase the value of parameter n089 to upgrade control capability by integration.
If the control system vibrates and it cannot be stopped by adjusting the integral time, output lag filter time, etc., decrease the set value of parameter n089.
3. PID control can be canceled by a multi-function contact input signal.
By setting any of parameters n036 to n040 to “PID Disable” and by closing the contact during running, PID control is disabled and the setpoint value signal itself is used as a frequency reference signal.
4. Inverse PID characteristics can be obtained by setting parameter n093 to
“Inverted”.
5. The PID Sleep feature can be used to automatically turn off the inverter output when the PID output value falls below the sleep function level (n094) for longer than the sleep function time (n095). The inverter will resume normal operation when the PID output is greater than the sleep level for longer than the sleep time. Setting parameter n094 to “0.0” disables this feature.
PID Output n094 (Sleep Level)
Internal RUN
Command
RUN Command
During Run n095 n095
(Sleep Time)
Stays High
Stays High
Figure 35b PID Control Timing Chart
FP5/GP5 User’s Manual 67
Chapter 3 - Programming Features
FP5/GP5 Operation
Reverse Run Prohibit (n006, Reverse Oper)
A “reverse run disabled” setting does not accept a reverse run command from the control circuit terminal or the digital operator. This setting is used in applications where a reverse run command can cause problems.
LED Setting LCD Setting Description
0 REV Allowed Reverse run enabled (factory default)
1 REV Prohibited Reverse run disabled
Soft-Start Characteristics (n022, S-Curve Select)
An S-curve pattern is used to reduce shock and provide smooth transitions during machine acceleration and deceleration.
LED Setting LCD Setting Description
0 No S-Curve S-curve not provided
1 0.2 Sec 0.2 second (factory default)
2 0.5 Sec 0.5 second
3 1.0 Sec 1.0 second
Note: The S-curve time is the time to reach the set accel/decel rate (as determined by the accel/ decel time settings).
Frequency Reference
Output Frequency
Output Frequency
S-curve Characteristic
Time (Tsec)
Figure 36 S-curve Characteristic Timing Diagram
Time
68 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
The following figure shows FWD/REV run switching during deceleration to stop.
FWD Run Command
REV Run Command
Acceleration Deceleration
Min. Output Frequency n016
DC Injection Braking
Time at Stop n069
Output Frequency
Min. Output Frequency n016
Acceleration Deceleration
Figure 37 S-curve Characteristics - FWD/REV Operation
Speed Limit Adjustment
Internal
Frequency
Reference
Frequency Reference
Upper Limit (n031)
Frequency Reference
Lower Limit (n032)
Set Frequency Reference
Figure 38 Setting Frequency Upper and Lower Limits
· Frequency Reference Upper Limit (n031, Ref Upper Limit)
The upper limit of the frequency reference can be set in increments of
1%. (n011: maximum output frequency = 100%)
Factory setting: 100%
· Frequency Reference Lower Limit (n032, Ref Lower limit)
The lower limit of the frequency reference can be set in increments of
1%. (n011: maximum output frequency = 100%)
Factory setting: 0%
When operating at a frequency reference of 0Hz, operation continues at the frequency reference lower limit. However, when the lower limit is set to less than the minimum output frequency (n016), operation stops.
FP5/GP5 User’s Manual 69
Chapter 3 - Programming Features
FP5/GP5 Operation
Stopping Method (n004, Stopping Method)
This function selects the stopping method suitable for the particular application.
LED Setting LCD Setting Description
0 Ramp to STOP Deceleration to stop (factory default)
1 Coast to STOP Coast to stop
2 Coast w/Timer 1 Coast to stop with timer 1 (run command cycle)
3 Coast w/Timer 2 Coast to stop with timer 2 (auto-start after time out)
· Deceleration to Stop (n004 = “Ramp to STOP”)
Output Frequency
Decel time 1 (n019)
Min. Output Frequency (Frequency at
DC Injection Braking Start - n016)
Factory Default: 1.5Hz
Run Command
ON
DC injection Braking Time at Stop (n069)
Factory Default: 0.5 s
OFF
Figure 39 Stopping Method - Deceleration to Stop
Upon removal of the FWD (REV) run command, the motor decelerates at a deceleration rate determined by the time set in deceleration time 1
(n019) and DC injection braking is applied immediately before when the minimum output frequency (n016) is reached. If the deceleration time is short or the load inertia is large, an overvoltage fault (OV) may occur during deceleration. In this case, increase the deceleration time or install an optional braking resistor .
Braking torque: w/o braking resistor, approx. 20% of motor rated torque w/ braking resistor, approx. 150% of motor rated torque
· Coast to Stop (n004 = “Coast to STOP”)
Output frequency Inverter output is shut OFF when stop command is given.
Run command
ON
OFF
Figure 40 Stopping Method - Coast to Stop
Upon removal of the FWD (REV) run command, the motor coasts.
70 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
· Coast to Stop with Timer 1 (n004 = “Coast w/Timer 1”)
Output Frequency
Decel Time 1
(n019)
Accel Time 1
(n018)
Coasting
Time
Minimum baseblock time (n057)
FWD (REV)
Run Command ON ON ON
Run Command Disabled
Figure 41 Example of Stopping Method - Coast to Stop w/ Timer 1
Upon removal of the run command, the inverter output is immediately removed, allowing the motor to coast. If the run command is re-applied before the minimum baseblock time (n057) elapses, the run command is not accepted.The run command must be cycled to be acknowledged. An initial run command will be accepted if applied after the minimum baseblock time elapses.
· Coast to Stop with Timer 2 (n004 = “Coast w/Timer 2”)
Output Frequency
Decel Time 1
(n019)
Accel Time 1
(n018)
Coasting
Time
Minimum baseblock time (n057)
FWD (REV)
Run Command ON ON
Figure 42 Example of Stopping Method - Coast to Stop w/ Timer 2
Operation is disabled during the minimum baseblock time (n057) after a stop command is given. A run command will be accepted, but operation does not start until the minimum baseblock time runs out. The inverter does not operate during the baseblock time, as shown in Figure 42.
FP5/GP5 User’s Manual 71
Chapter 3 - Programming Features
FP5/GP5 Operation
Torque Adjustment (n071, Torq Comp Gain)
Motor torque can be adjusted by changing the V/f pattern (n010) or by adjusting the torque compensation gain (n071). For details on setting the
V/f pattern, see “V/f Pattern Adjustment”, on page 75.
· Full-range Automatic Torque Boost
The motor torque requirement changes according to load conditions.
Full-range automatic torque boost adjusts the output motor voltage according to the required torque. The FP5/GP5 automatically adjusts the voltage during constant-speed operation as well as during acceleration.
The required torque is calculated by the inverter. The optimum motor voltage will be output to ensure tripless operation and power savings.
Output voltage
∝
Torque compensation gain × Required torque
Voltage
Required torque ⇒ Increase voltage
Frequency
Figure 43 Torque Characteristics
Normally, no adjustment is necessary for torque compensation gain
(n071, factory default: “1.0”). When the wiring distance between the inverter and the motor is long, or when the motor generates vibration, change the torque compensation gain.
Increasing torque compensation gain increases motor torque, but an excessive increase may cause the following:
· Inverter trips due to motor overexcitation
· Motor overheat or excessive vibration
If adjustment is necessary, adjust in 0.1 increments.
72 FP5/GP5User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
Torque Detection
The over/undertorque detection circuit will activate when the motor load causes the motor current to go above or below torque detection level (n078) respectively. When the over/undertorque condition is detected, alarm signals are sent to multi-function output terminals MA, MB and/or M1.
To output an over/undertorque detection signal, set multi-function contact output selection n041 or n042 to “6” (N.O. contact) or “7” (N.C. contact).
Inverter Rated Current
Motor Current n078
* *
Time
Multi-function Contact
Output Signal
(Overtorque Detection Signal)
Terminal MA, MB, M1
ON ON n079 n079
* Release width (hysteresis) during overtorque detection is 5% of the inverter rated current level.
Figure 43 Torque Characteristics
· Over/undertorque Detection Function Selection (n077, Torq Det Sel)
LED
Setting
LCD Setting Description
0 Disabled Detection disabled (factory default)
1 OT/SpdAgree/Alm
Overtorque detection begins at speed agree; continue running after detection. (Alarm)
2 OT/Run/Alm Overtorque detection at run; continue running after detection. (Alarm)
3 OT/SpdAgree/Flt
Overtorque detection begins at speed agree; coast to stop after detection. (Fault)
4 OT/Run/Flt Overtorque detection at run; coasts to stop after detection. (Fault)
5 UT/SpdAgree/Alm
Undertorque detection begins at speed agree; continue running after detection. (Alarm)
6 UT/Run/Alm Undertorque detection at run; continue running after detection. (Alarm)
7 UT/SpdAgree/Flt
Undertorque detection begins at speed agree; coast to stop after detection. (Fault)
8 UT/Run/Flt Undertorque detection at run; coast to stop after detection. (Fault)
Notes:
· To detect torque during acceleration or deceleration, select a setting that contains
“RUN”.
· To continue operation after over/undertorque detection, select a setting that contains
“Alm”. During detection, the digital operator displays “oL3” alarm (blinking).
· To stop the inverter after an over/undertorque detection fault, select a setting that contains “Flt”. During detection, the digital operator displays “oL3” fault.
FP5/GP5 User’s Manual 73
Chapter 3 - Programming Features
FP5/GP5 Operation
· Over/undertorque Detection Level (n078, Torq Det Level)
Sets the torque detection current level in units of 1%
Inverter rated current: 100%
Factory default: 160%
· Over/undertorque Detection Time (n079, Torq Det Time)
The over/undertorque detection delay time inserts a delay, between the time motor current exceeds or falls below the over/undertorque detection current level (n078) and when the over/undertorque detection function is enabled.
Factory default: 0.1 second
If the time during which motor current exceeds or falls below the over/ undertorque detection level (n078) is longer than the over/undertorque detection time (n079), the over/undertorque detection function is enabled.
Tripless Operation
When starting into a coasting motor, use the speed search command or
DC injection braking at start, to prevent a drive trip and motor burnout.
· Speed search
This function allows the restart of a coasting motor without the necessity to stop. It is useful during inverter bypass operation, when switching between the motor receiving power directly from the line to the inverter.
Set the multi-function contact input selection (n036 to n40) to “SpdSrch
(MAXFREQ)” (start search command from maximum output frequency) or “SpdSrch (SETFREQ)” (start search command from the set frequency).
Build a sequence so that the FWD (REV) run command is input at the same time as the search command, or after the search command. If the run command is input before the search command, the search command is not effective. Below is a timing diagram of the search command input:
ON
ON
FWD (REV) Run Command
Speed Search Command
Max. Output Frequency or
Frequency Reference at
Run Command Input
Output Frequency
Min. Baseblock
Time (n057)
Speed Search Start
(Condition: Inverter Output Current
≥
Speed Search
Operation
[ ] [
Speed Detection Agree
(Condition: Inverter Output Current
< n056 Speed Search Level)
]
Figure 44 Search Command Input Timing Diagram
74 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
· DC Injection Braking at Start (n068, DCInj Current; n070, DCInj Time@Start)
This function restarts a coasting motor after first applying it with DC injection braking. DC injection braking time at start (n070) is set in units of 0.1 second. DC injection braking current is set in parameter
n068 in units of 1%. When parameter n070 is set to “0”, DC injection braking is disabled and acceleration starts from the minimum output frequency. n016
Min. Output Frequency n070
DC Injection Braking
Time at Start
Figure 45 DC Injection Braking at Starting
V/f Pattern Adjustment (n010, V/f Selection)
Set the V/f pattern using parameter n010 as described below. It may be necessary to change the V/f pattern when using a high-speed motor, or when special torque adjustment is required in the application.
Set values: “60Hz Preset”: Fixed V/f pattern
“User defined V/f”: Custom V/f pattern can be set
Set the V/f pattern according to the following:
· n010 = “60Hz Preset” (Factory default value)
Set parameter n010 to “60Hz Preset” when a standard 50/60Hz, 230/
460V motor is selected. This setting provides a standard linear V/Hz pattern. Parameters n011 through n017 cannot be adjusted.
· n010 = “User defined V/f” (Custom V/f pattern)
Set parameter n010 to “User defined V/f” when a variable torque pattern is required. Parameters n011 through n017 can then be adjusted manually to customize a special V/f pattern. The default settings for parameters n011 through n017 when n010 = “User defined V/f” comprise the standard variable torque pattern.
FP5/GP5 User’s Manual 75
Chapter 3 - Programming Features
Inputs & Outputs
Be sure to satisfy the following conditions for setting parameters
n011 to n017:
n016
≤
n014 < n013
≤
n011
Voltage n012 n015 n017
0 n016 n014 n013 n011
Figure 46 Custom V/f Pattern Setting
Frequency
Parameter
No.
Name Unit Setting Range
Factory
Default
(n010=60Hz
Preset)
Factory
Default
(n010=User defined V/f)
n011 Maximum output frequency 0.1 Hz 50.0 to 400 Hz 60.0 Hz 60.0 Hz
n012 Maximum voltage 0.1 V 0.1 to 255 V * 230 V * 230 V *
n013 Maximum voltage output frequency (base frequency)
0.1 Hz 0.2 to 400 Hz 60.0 Hz 60.0 Hz
n014 Mid. output frequency 0.1 Hz 0.1 to 399.9 Hz 3.0 Hz 30.0 Hz
n015 Mid. output frequency voltage 0.1 V 0.1 to 255 V * 17.2 V * 57.5 V *
n016 Minimum output frequency 0.1 Hz 0.1 to 10.0 Hz 1.5 Hz 1.5 Hz
n017 Minimum output frequency voltage
0.1 V 0.1 to 50.0 V * 11.5 V * 11.5 V *
* For 460V class units, the value is twice that of 230V class units.
Increasing the voltage in the V/f pattern increases motor torque, however, an excessive increase may cause:
· Inverter fault trips as a result of motor overexcitation
· Motor overheat or excessive vibration
Increase voltage gradually while checking the motor current.
76 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
Inputs & Outputs
Slip Compensation
The slip compensation feature allows better speed regulation to be obtained by adjusting the output frequency according to the changing load. This feature compensates for the slip of the motor.
Slip Compensation Gain (n107, Slip Comp Gain)
This parameter is used to input the slip of the motor. The setting is entered as a percent of base frequency (n013). The default value for n107 is 0.0% which disables this feature. To properly set the parameter, use the following equation: n107 =
Synchronous Speed - Full Load Speed
Synchronous Speed
Where: Synchronous Speed =
120
×
Rated Frequency
# of Motor Poles
Full Load Speed = Motor Nameplate Speed
Slip Compensation Primary Delay Time (n109, Slip Comp Delay)
This parameter sets how fast the inverter output frequency responds to changing loads. A long time will cause a sluggish response (a large momentary speed droop). A short time will cause a fast response (less speed droop). Too short of a time may cause instability.
FP5/GP5 User’s Manual 77
Chapter 3 - Programming Features
Inputs & Outputs
3.4 INPUTS & OUTPUTS
Multi-function Input Signals (n036 to n040)
Multi-function contact input terminal S2 to S6 functions can be changed when necessary by setting parameters n036 to n040, respectively. None of these parameters can receive a setting common with the other (no duplication).
· Terminal S2 function: set via parameter n036
· Terminal S3 function: set via parameter n037
· Terminal S4 function: set via parameter n038
· Terminal S5 function: set via parameter n039
· Terminal S6 function: set via parameter n040
Multi-function Input Signals Ref.
LED Setting LCD Setting Description Remarks Page
0 Reverse RUN (2W) Reverse run (2-wire sequence) Only parameter n036 can be set to this value.
1 FWD/REV Cmd (3W) Fwd / Rev command (3-wire sequence) Only parameter n036 can be set to this value.
2
3
4
Ext Fault (NO) External fault (normally open)
Ext Fault (NC) External fault (normally closed)
Fault Reset Fault reset
Inverter stops at fault when external fault signal is input. Digital operator displays “EFX”.
Inverter stops at fault when external fault signal is input. Digital operator displays “EFX”.
Resets fault. Fault reset is disabled during run command input.
79
-
-
5 LOCAL/REMOTE Sel Local / Remote selection — 79
6 COM/INV Sel Serial com/inverter selection (Fref, RUN command) — 79
7
8
9
STOP Cmd/Dec2 NO Fast stop using Decel 2 (normally open)
STOP Cmd/Dec2 NC Fast stop using Decel 2 (normally closed)
Master Fref Sel Master freq. ref. selection (FV-open or FI-closed)
Decelerates to stop by decel time 2 (n021) when fast stop is input.
Decelerates to stop by decel time 2 (n021) when fast stop is input.
Master frequency reference input level (voltage input at “open”, current input at “closed”) can be selected.
-
-
-
10 Multi-Step Spd 1 Multi-step speed reference command 1 —
11 Multi-Step Spd 2 Multi-step speed reference command 2 —
64
12 Not Used Not used — -
13 JOG Command Jog reference (n030) — 59
14 Acc/Dec Switch Accel / Decel time selection — 49
15
16
Ext Baseblk (NO) External baseblock (normally open)
Ext Baseblk (NC) External baseblock (normally closed)
Coasting signal. Motor starts coasting when the signal is input. Digital operator displays “bb” (blinking).
Coasting signal. Motor starts coasting when the signal is input. Digital operator displays “bb” (blinking).
-
17 SpdSrch (MAXFRQ) Speed search from maximum frequency Speed search command signals.
18 SpdSrch (SETFRQ) Speed search from set frequency Speed search command signals.
19 Param Lockout Parameter setting enable / disable
Permission or prohibition of constant setting from the digital operator or serial communication (setting disabled at “closed”, enabled at “open”) can be selected.
20 PID I Reset PID integral value reset —
21 PID Disable PID control enable / disable —
74
-
67
22 Timer Start Cmd Timer function — 80
23
24
OH3 Input External overheat alarm (OH3)
Ref Sample Hold Analog reference sample hold command
When this signal is input, the digital operator displays “OH3” (blinking). Inverter continues operation.
Analog frequency reference is sampled at “closed” and held at “open”.
-
80
25 KEB Cmd (NO) Inertia ridethrough command (normally open) — —
26 KEB Cmd (NC) Inertia ridethrough command (normally closed) — —
27 Hold Command Accel / Decel hold command — —
28 PID Polarity Sel Inverse PID enable / disable — —
29 UP/DOWN Cmd UP/DOWN Command Only parameter n040 can be set to this value. 81
* 2 to 6 are displayed in _ corresponding to S2 to S6, respectively.
Factory settings: n036 = “Reverse RUN (2W)”, n037 = “Ext Fault (NO)”, n038 = “Fault
Reset”, n039 = “Multi-Step Spd 1”, n040 = “Multi-Step Spd 2”
78 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
Inputs & Outputs
S1
FWD Run/Stop
S2
REV Run/Stop
SC
Figure 47a Terminal Function at 2-Wire Sequence Selection (setting: n036=”Reverse RUN (2W)”)
Stop
Start
S1
S2
S3
SC
Run Command
(Run when “Closed”)
Stop Command
(Stop when “Open”)
FWD/REV Run Selection
(FWD Run when “Open”
REV Run when “Closed”)
Figure 47b Terminal Function at 3-Wire Sequence Selection (setting: n036=”FWD/REV Cmd (3W )”)
· Local/Remote Selection (setting: “LOCAL/REMOTE Sel”)
Selects whether the run command is received from the digital operator or the control circuit terminal. Local/Remote selection is available only while the inverter is stopped.
Open: Run according to the setting of operation mode selection (n002).
Closed: Frequency reference and run command from the digital operator.
Example: Set n002 to “SEQ=TRM REF=TRM”.
Open: Frequency reference from control circuit terminals FV & FI, and run command from control circuit terminals S1 and S2.
Closed: Frequency reference and run command from the digital operator.
· Serial Communication/Control Circuit Terminal Selection (setting:
“COM/INV Sel”)
Selects operation reference by serial communication or by the control circuit terminal. This selection is available only during stop.
Open: run according to the setting of operation mode selection (n002).
Closed: Frequency reference and run command from serial communication.
FP5/GP5 User’s Manual 79
Chapter 3 - Programming Features
Inputs & Outputs
Example: Set n002 to “SEQ=TRM REF=TRM”.
Open: Frequency reference from control circuit terminals FV & FI, and run command from control circuit terminals S1 and S2.
Closed: Frequency reference and run command from serial communication.
· Timer Function (setting: “Timer Start Cmd”)
The timer function is used in conjunction with the multi-function contact output (parameter n041 or n042 set to “Timer Output”).
When the timer function input is “closed” for longer than the ON-delay timer (n080), the timer function output closes.
When the timer input is “open” for longer than the OFF-delay timer
(n081), the timer function output opens.
Multi-function Contact
Input: Timer Function
ON
ON
ON ON ON
ON
ON ON ON
ON
Multi-function Contact
Output: Timer Function n080 n081 n080 n081
Figure 48 Timing Diagram of Timer Function
· Analog Reference Sample/Hold Selection (setting:”Ref Sample Hold”)
This feature allows a single analog signal to be used among multiple inverters to “sample and hold” separate speeds. Each inverter can be commanded to acknowledge the reference at different times. If the analog reference sample/hold input terminal is “closed” for 100ms or longer, the analog frequency reference is sampled; when it opens, the analog frequency reference is held.
Analog Input
Fref
100ms 100ms
Closed
Open t1 t2 t3
Figure 49 Sample/Hold Selection - Analog Reference
Note: t1, t3 - Reference is sampled once with an input closure of 100ms or longer.
t2 - Reference is not sampled with an input closure of less than 100ms.
80 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
Inputs & Outputs
· Up/Down Command (setting: n040 = “Up/Down Control”)
With the FWD (REV) run command entered, a change in frequency is performed by inputting the Up or Down commands to control circuit terminals S5 and S6, so that operation can be performed at the desired speed. When the Down command is specified for terminal S6 by setting n040=”Up/Down Control”, any function set to terminal S5 via parameter
n039 becomes disabled; terminal S5 becomes an input terminal for the
Up command and terminal S6 an input terminal for the Down command.
Control Circuit Terminal S5 (UP command) Closed Open Open Closed
Control Circuit Terminal S6 (DOWN command) Open Closed Open Closed
Operation Status Accel Decel Hold Hold
FWD Run
UP Command S5
DOWN Command S6
Upper Limit Speed
Lower Limit Speed
Output Frequency
Frequency Agree Signal
U: Up (accelerating) status
D: Down (decelerating) status
H: Hold (constant speed) status
UI: Up status, with clamping at upper limit speed
DI: Down status, with clamping at lower limit speed
Figure 50 Timing Diagram of UP/DOWN Command Input
Notes:
1) When the UP/DOWN command is selected, the upper limit speed is set regardless of frequency reference.
Upper limit speed = Maximum output frequency (n011)
× Frequency reference upper limit (n031) /100
2) The lower limit value is either the analog frequency from control circuit terminals FV or
FI, or the frequency reference lower limit (n032), whichever is larger.
3) When the FWD (REV) run command is input, operation starts at the lower limit speed without an UP/DOWN command.
4) If the jog frequency reference is input while the drive is running by the UP/DOWN command, the jog frequency reference has priority.
FP5/GP5User’s Manual 81
Chapter 3 - Programming Features
Inputs & Outputs
Analog Input Signals
· Master Analog Input Selection (n043, Analog Input Sel)
To input the master frequency reference from the control circuit terminal, use terminal FV (0 to 10V) or terminal FI (4 to 20mA), by setting parameter n043.
LED Setting LCD Setting Master Frequency Reference Terminal Input Level
0 FV=MSTR FI=AUX FV (factory default) 0 to 10V input
1 FV=AUX FI=MSTR FI 4 to 20mA input
· Auxiliary Analog Input Selection (n044, Terminal FI Sel)
From the factory, terminal FI is set to accept a 4-20mA signal. To change the control circuit terminal FI input level from current to voltage, set parameter
n044 according to the table below, and be sure to cut the “J1” jumper on the control PCB. The J1 jumper is located near terminal FI on the control PCB.
LED Setting LCD Setting Input Level
0 * 0-10 VDC 0 to 10V input
1 4-20 mA 4 to 20mA input (factory default)
* To set parameter n044 to “0”, cut jumper J1 on the inverter control PCB board.
· Frequency Reference Retention (n045, MOP Ref Memory)
Effective when UP/DOWN or Sample/Hold commands are selected for multifunction contact inputs. To retain the held frequency reference at power OFF, set parameter n045 to”Memorize Fref”. When n045=”Memorize Fref”, the last sampled/held reference will be memorized during power down. When power is re-applied, a run command will run the inverter at this previous speed. When n045=”Not Memorized”, the last sampled/held frequency will be lost at power down. Upon power-up, a new reference will need to be sampled.
LED Setting LCD Setting Description
0 Memorize Fref Held frequency retained in frequency reference 1 - n024 (factory default)
1 Not Memorized Not retained
· Operation Method for Frequency Reference Loss Detection (n046, Ref
Loss Detect)
Selects the frequency reference if the frequency reference from the control circuit terminal decreases rapidly (lost signal).
LED Setting LCD Setting Description
0 Not Detected Detection disabled (factory default)
1 RUN @ n047 Fref Detection enabled, continue to run at n047 value × previous reference.
If the frequency reference decreases by 90% within 400ms (when detection is enabled), operation continues at reference equal to the n047 value
×
previous reference.
82 FP5/GP5User’s Manual
Multi-function Output Signals (n041, Terminal MA Sel; n042, Terminal M1 Sel)
Multi-function output terminal MA, MB and M1 functions can be changed when necessary by setting parameters n041 and n042.
· Terminal MA and MB functions: set via n041
· Terminal M1 functions: set via n042
Factory defaults: n041 = “Fault”, n042 = “During Running”
Multi-function Output Signals
LED
Setting
LCD Setting Description Remarks
Ref.
Page
0 Fault Fault “Closed when inverter fault occurs. -
1 During Running During running “Closed when either FWD or REV run command is input or when the inverter outputs voltage.
2 At Speed Frequency agree - 84
3 At Desired Speed Desired frequency agree - 84
-
4 Freq Detection 1 Frequency detection - 57
5 Freq Detection 2 Frequency detection - 57
6 OverTrq Det (NO) Overtorque detection (N.O. contact) - 73
7 OverTrq Det (NC) Overtorque detection (N.C. contact) - 73
8 BaseBlocked During baseblock “Closed when inverter output shuts OFF. -
9 Operation Mode Operation mode “Closed” when run command or frequency reference from digital operator is selected.
-
10 Ready Inverter operation ready “Closed” when no inverter fault does not occur and the inverter can be operated.
11 Timer Output Timer function - 80
12 Auto-Restarting Automatic restart “Closed” during fault retry operation. 51
13 OL Pre-Alarm OL pre-alarm Outputs an alarm before inverter and motor overload protection are enabled. Pre-alarm level is
150% for 48 sec for the inverter and more than
80% of the overload protection time for the motor.
-
-
14 Freq Ref Loss Frequency reference loss Closes a contact when detecting a loss of reference condition.(See page 82 for n046).
15 Set By Com Cntl Output from serial communication Activates contact output independently from inverter operation by a command from serial communication (MODBUS).
82
-
16 PID Fdbk Loss PID feedback loss Detects a rapid decrease in feedback and outputs a contact when the PID control mode is set.
Detects when the feedback value decreases less than the detection level (n091) for longer than the feedback loss detection delay time (n092); the inverter continues operation.
17 OH1 Alarm OH1 alarm “Closed” during heat sink overtemperature (digital operator displays “OH1” blinking).
47
-
FP5/GP5 User’s Manual 83
Chapter 3 - Programming Features
Frequency Agree (setting: “At Speed”)
See Figure 51 below for an example of selecting the frequency agree signal as the function of output terminals MA, MB or M1.
Detection Width ±2Hz
Release Width ±4Hz
Frequency Reference
Output Frequency
Frequency Agree Signal ON
Figure 51 Example of Frequency Agree Signal (setting: “At Speed”)
Desired Frequency Agree (setting: “At Desired Speed”)
See Figure 52 below for an example of selecting the desired frequency agree signal as the function of output terminals MA, MB or M1.
Detection Width ±2Hz
Release Width ±4Hz
Desired Frequency Agree
Set Point (n075)
Output Frequency
Desired Frequency Agree Signal ON
Figure 52 Example of Desired Frequency Agree Signal (setting: “At Desired Speed”)
84 FP5/GP5 User’s Manual
Chapter 4 - Diagnostics
- CHAPTER 4 -
DIAGNOSTICS
Section Description
4 DIAGNOSTICS
Page
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4.1 M AINTENANCE & I NSPECTION . . . . . . . . . . . . . . . . . . . . . . 87
Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Parts Replacement Schedule. . . . . . . . . . . . . . . . . . . . . . 87
4.2 A LARM & F AULT D ISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . 88
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fault Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Motor Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
FP5/GP5 User’s Manual 85
Chapter 4 - Diagnostics
Precautions
!
WARNING
PRECAUTIONS
1) Never touch high voltage terminals in the inverter.
2) Replace all protective covers before powering up the inverter. When removing the cover, be sure to shut OFF the power supply to the inverter.
3) Perform maintenance or inspection only after verifying that the charge
LED has gone OFF, after the main circuit power supply is turned OFF.
4) Only authorized personnel should be permitted to perform maintenance, inspections or parts replacement.
Failure to observe these precautions highlighted in this manual will expose the user to high voltages, resulting in equipment damage, serious injury or death.
!
CAUTION
PRECAUTIONS
1) The control PCB board employs CMOS ICs. Do not touch the CMOS elements.
2) Do not connect or disconnect wiring or connectors while power is applied to the circuit.
Failure to observe these precautions may result in equipment damage.
86 FP5/GP5 User’s Manual
Chapter 4 - Diagnostics
Maintenance & Inspection
4.1 MAINTENANCE & INSPECTION
This section describes basic maintenance and inspection procedures for the FP5/GP5.
Periodic Inspection
The FP5/GP5 will function longer if it is kept clean, cool and dry, and if all precautions highlighted in this manual are observed. Periodically inspect the inverter as described in the table below to prevent accidents and to ensure high performance with high reliability.
To prevent electrical shock, disconnect all power before servicing the inverter. Then wait at least five minutes after the power supply is disconnected and all LEDs are extinguished.
Component Check Corrective Action
External Terminals,
Connectors, Mounting
Screws, etc.
Loose screws or connectors Securely tighten.
Heatsink Build-up of dust and dirt
Printed Circuit Board
(PCB)
Accumulation of conductive dust or oil
Blow with dry, compressed air [39.2
× 10
4
to 58.8 × 10 pressure].
4
Pa (4 to 6kg·cm
2
)
Blow with dry, compressed air [39.2
× 10
4
to 58.8 × 10
4
Pa (4 to 6kg·cm pressure]. If dust and oil cannot be removed, replace the board.
2
)
Cooling Fan For abnormal noise and vibration Replace the cooling fan.
Power Components Accumulation of dust and dirt
Blow with dry, compressed air [39.2
× 10 4 to 58.8 × 10 4 Pa (4 to 6kg·cm2) pressure].
Smoothing Capacitor Discoloration or odor Replace the capacitor or the inverter.
Parts Replacement Schedule
Replace the following parts periodically, for long, safe, trouble-free operation of the FP5/GP5:
Parts Approximate Interval Remarks
Cooling Fan 2 to 3 years Replace with new one.
Smoothing Capacitor 5 years Replace with new one (after inspection).
Breakers or Relays -- Decide after inspection.
Fuses 10 years Replace with new one.
Aluminum Electrolytic
Capacitor on PCB Board
5 years Replace with new one (after inspection).
FP5/GP5 User’s Manual 87
Chapter 4 - Diagnostics
Alarm & Fault Displays
4.2 ALARM & FAULT DISPLAYS
This section describes the alarm and fault displays, explanations for fault conditions, and corrective actions to be taken if the FP5/GP5 malfunctions.
Alarm Display
Unlike faults, alarms do not activate fault contact outputs. After the cause of the alarm is corrected, the inverter returns to its former operation status automatically.
Alarm Display and Explanations
LCD Operator
Alarm Display
Contents Description
U v
Undervoltage
(blinking) o
V
Overvoltage
(blinking)
Undervoltage detection Undervoltage has been detected.
OV during stop
Main circuit DC voltage exceeds the overvoltage detection level while the inverter output is OFF.
o H1
Overheat 1
(blinking) o L3
Overload 3
(blinking) bb
Base Block
(blinking)
EF
Ext Fault
(blinking)
Heatsink overheating
Overtorque detection
External baseblock
Simultaneous forward/ reverse run commands
When heatsink temperature ≥ OH1 detection level, continuous operation at 0H1 detection is selected.
When inverter output current > n078 (overtorque detection level), continuous operation at overtorque detection is selected.
External baseblock command is input from control circuit terminal.
Both forward and reverse run commands are simultaneously input for over 500ms.
MODBUS transmission waiting
When parameter n002 (operation method selection) is set to “4” or above, the inverter has not received the normal data from serial communication after power ON.
CE
Modbus Com Err
(blinking) o
H3
Overheat 3
(blinking)
CALL
Waiting Message
(blinking) o PE1
KVA Setting Err
Inverter kVA setting fault Inverter kVA setting error.
o PE3
MF Input Error
Multi-function contact input setting error
One of the following setting errors occurred in the multifunction contact input selection (n036 to n040).
· Two or more of the same values are set.
· Both 15 and 16 are set at the same time.
· Both 22 and 25 are set at the same time.
· Either of n036 to n039 are set to “25” or “26”.
o
PE5
V/f Error
V/f data setting error Setting error of n011 to n017 (V/f data) o PE6
Parameter Error
Parameter setting error
One of the following setting errors occurred.
· n062 (jump frequency 1) > n063 (jump frequency 2)
· n031 (frequency upper limit) < n032 (frequency lower limit)
· n033 (motor rated current) < 10% of inverter rated current, or n033 > 200% of inverter rated current setting
88 FP5/GP5 User’s Manual
Chapter 4 - Diagnostics
Alarm & Fault Displays
Fault Display
When the FP5/GP5 detects a fault, the fault is displayed on the digital operator and a fault contact output is activated after which the motor coasts to a stop. Check the causes listed in the table below and take the corresponding corrective actions. To reset the inverter, remove any run command and apply the reset input signal or depress the RESET key on the digital operator, or cycle power. If taking the corrective actions described does not solve the problem, contact your Saftronics representative immediately.
Fault Diagnosis and Corrective Actions
LCD
Operator-
Fault
Display
U v 1
Undervoltage 1
U v 2
Undervoltage 2
U v 3
Undervoltage 3
Main circuit undervoltage
(PUV)
Control circuit undervoltage
(CUV)
Undervoltage in the control circuit during running.
· Check the power supply wiring.
· Correct the line voltage
MC fault
Name Description Corrective Action
Undervoltage in the DC main circuit during running.
The pre-charge contactor opened during running.
o C
Overcurrent
Overcurrent (OC)
The inverter output current exceeded the OC level.
· Check the motor coil resistance.
· Extend the accel/decel time.
· Check the motor insulation.
· Multi-meter check.
o
V
Overvoltage
Overvoltage (OV)
The main circuit DC voltage exceeded the OV level.
Detection level
230V class: approx. 400VDC or less
460V class: approx. 800VDC or less
Extend the deceleration time, add braking circuit.
GF
Ground
Fault
PUF
DC Bus
Fuse
Ground fault (GF)
Main circuit fault (PUF)
Inverter output grounding current exceeded 50% of inverter rated current.
·The DC bus fuse is blown.
·The output transistors were damaged.
· Check that motor insulation has not deteriorated.
· Check that connection between inverter and motor is not damaged.
Check for damaged transistor, load side short circuit, grounding, etc.
FP5/GP5 User’s Manual 89
Chapter 4 - Diagnostics
Alarm & Fault Displays
LCD
Operator-
Fault
Display
* o H1
Overheat
1
Name Description Corrective Action
Heatsink overheat (OH1) o H2
Overheat
2 o L1
Overload 1 o L2
Overload 2
* o L3
Overload 3
Heatsink overheat (OH2)
Motor overload (OL1)
Inverter overload (OL2)
Overtorque detection (OL3)
The transistor heatsink temperature exceeded the allowable value
(Fin temperature > OH1 detection level). Check the fan and ambient temperature.
The transistor heatsink temperature exceeded the allowable value
(Fin temperature > OH2 detection level).
Inverter output exceeded the motor overload level (see n012).
Inverter output exceeded the inverter overload level.
Inverter output current exceeded the overtorque detection level (n078).
Reduce the load.
Reduce the load, extend the acceleration time.
SC
Short Circuit
Load short-circuit (SC) Inverter output (load) is short-circuited.
· Check the motor coil resistance.
· Check the motor installation.
EF5
External
Fault 5
EF6
External
Fault 6
SPI
Input Pha
Loss
SPo
Output
Pha Loss
EF0
Opt External Flt
EF2
External
Fault 2
EF3
External
Fault 3
EF4
External
Fault 4
External fault from serial communication
External fault at terminal S2
External fault at terminal S3
External fault at terminal S4
External fault at terminal S5
External fault at terminal S6
Excessive ripple in the DC bus
Fault occurred in the external control circuit.
Fault occurred in the external control circuit.
· Inverter input power supply has open phase.
· Large unbalance in input line voltage.
Check the external control circuit.
Check the condition of the input terminal. If the LED lights when terminal is not connected, replace the inverter.
· Check the line voltage.
· Re-tighten the output terminal screws.
Output open-phase Inverter output has open phase. · Check the output wiring.
90 FP5/GP5 User’s Manual
Chapter 4 - Diagnostics
Alarm & Fault Displays
LCD
Operator-
Fault
Display
*CE
Modbus
Com Err
Name Description Corrective Action
MODBUS transmission fault
Control data cannot be received normally.
Check the transmission devices or signals.
CPF0
Com-Err
(Op +Inv)
CPF1
Com-Err
(Op +Inv)
Control circuit fault 1
(CPFO)
Digital operator transmission fault
Control circuit fault 2
(CPF1)
Digital operator transmission fault
· Transmission between the inverter and digital operator cannot be established 5 seconds after supplying power.
· MPU peripheral element check fault
(on-line)
· Transmission between the inverter and digital operator is established once after supplying power, but later transmission fault continues for more than 2 seconds.
· MPU peripheral element check fault
(on-line).
· Insert the digital operator connector again.
· Check the control circuit wiring.
· Replace the control card.
· Insert the digital operator connector again.
· Check the digital control circuit wiring.
· Replace the control card.
CPF4
Eprom
Error
CPF5
External
A/O Err
EEPROM fault (CPF4)
CPU A/D converter fault
(CPF5)
Inverter PCB control board fault. Replace the control card.
rr
Dyn Brk
Trans r h
Dyn Brk
Res
Regenerative brake transistor failure
Dynamic braking transistor has failed
Dynamic brake resistor overheat (DB resistor overload)
Dynamic brake resistor duty cycle value exceeded (>3% ED)
· Check dynamic brake resistance.
· Check for proper wiring of dynamic brake resistor.
· Replace power board.
· Check for excessive load.
· Increase deceleration time.
· Increase time between decelerations.
o P r
Operator
Failure
LCD operator disconnected The LCD operator has been disconnected
· Check LCD operator wiring.
· Check parameter n110
CPF5
EPROM
R/W Err
Parameter read/write error EPROM life cycle has been exceeded
· Check control card wiring.
· Replace the control card.
* Stopping method selection is available for these faults.
FP5/GP5 User’s Manual 91
Appendix
Contents
Motor Faults
If a motor fault occurs, follow the checkpoints listed in the table below and take the corresponding corrective actions. If taking the corrective actions described does not solve the problem, contact your Saftronics representative immediately.
Motor Faults and Corrective Actions
Fault Check Point Corrective Action
Motor does not rotate
Motor rotation reverses
Motor rotates, but variable speed not available.
Motor r/min. too high or too low
Motor r/min not stable during operation
Power supply voltage applied to power supply terminals L1, L2, L3? Charge LED is ON?
Use rectifier type voltmeter to test. Voltage output to output terminals T1, T2, T3 correct?
· Turn ON power supply.
· Turn OFF power supply, and then ON again.
· Check power supply voltage.
· Make sure terminal screws are tight.
Turn OFF power supply, then turn ON again.
Motor locks due to excessive load? Reduce the load and release the lock.
Fault displayed in operator display? Check troubleshooting table.
FWD or REV run command entered? Check the wiring.
Frequency setting voltage entered?
· Check the wiring.
· Check frequency setting voltage.
Operation mode setting correct?
Wiring of terminals T1, T2, T3 correct?
Check the operation mode selection
(n002).
Match wiring to the phase order of the motor leads U, V, W.
FWD and REV wiring run signals entered? Correct the wiring.
Wiring of frequency setting circuit correct?
Check the operation mode selection
(n002).
Operation mode setting correct?
Check the operation mode selection
(n002).
Load excessively large? Reduce the load.
Motor ratings (number of poles, voltage correct?)
Accel/decel speed change ratio for gears, etc. correct?
Check motor nameplate specifications.
Check speed changer (gears, etc.)
Maximum frequency set value correct? Check the maximum frequency set value.
Use rectifier voltmeter. Voltage between motor terminals not excessive/reduced?
Check V/f characteristics values.
Load excessively large? Reduce the load.
Load variation excessively large?
· Reduce the load variation.
· Increase inverter motor capacity.
3-phase or single-phase power supply used?
For 3-phase power supply, open phase?
· For 3-phase power supply, check the wiring if power supply is open phase.
· For single-phase power supply, connect
AC reactor to the power supply.
92 FP5/GP5 User’s Manual
Appendix
Table of Contents
APPENDIX
Section Description
A APPENDIX
Page
A-1 B
RAKING
C
ONNECTION
D
IAGRAMS
. . . . . . . . . . . . . . . . . . 94
A-2 D IGITAL O PERATOR M ONITOR D ISPLAY . . . . . . . . . . . . . . 95
A-3 CE C
ONFORMANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
FP5/GP5 User’s Manual 93
Appendix A-1
Braking Connection Diagrams
A-1 BRAKING CONNECTION DIAGRAMS
Braking Resistor Unit
230V: 5~25HP
460V: 5~25HP
Overload Relay Trip Contact
1 2
P B
Braking Resistor Unit
MCCB
L1
L2
L3
MC
L1
L2
L3
B1 B2
VS-616PC5
T1
T2
T3
M
THRX OFF
ON
MC
Overload Relay Trip Contact of Braking Resistor Unit
1 2
MC
MC
SA
THRX
SA
TRX
SA
TRX
MC MA
Fault Contact
Figure 53 External Control Circuit for FP5/GP5 Braking Resistor Connection
230V: 20~25HP
+ 3
Braking Unit
-
P
N
Level
Detection
3 4
P0 P
B
B
1 2
Braking Resistor
Unit
Overload Relay Trip Contact
3 & 4 output signal to multi-function fault input.
Figure 54 External Control Circuit for FP5/GP5 Braking Unit Connection ( CDBR Type)
94 FP5/GP5 User’s Manual
Appendix A-2
Digital Operator Monitor Display
A-2 DIGITAL OPERATOR MONITOR DISPLAY
The following table describes the contents of the digital operator monitor display.
Digital Operator Monitor Display
Name
(LCD Operator Display)
Frequency Reference
(Frequency Ref)
Output Frequency
(Output Freq)
Output Current
(Output Amps)
Output Power
(Output Power)
Description
· Frequency reference can be monitored/set.
· Setting/display unit depends on display mode (n023).
· Output frequency is displayed.
· Display unit depends on display mode (n023).
Output current is displayed in units of 0.1A (1A for 1,000A and above).
FWD/REV Run Command
(Forward/Reverse)
Output power is displayed in units of 0.1kW (1kW for 1,000kW and above).
· FWD/REV run command can be monitored/set.
· Setting enabled during run command from digital operator.
· FWD run displays “Forward”, REV run displays “Reverse”.
The following conditions can be monitored.
No. Contents
U-01 Frequency reference
U-02 Output frequency
U-03 Output current
U-04 Output voltage reference is displayed in units of 1V.
U-05 DC voltage is displayed in units of 1V.
U-06 Output power
Input terminal status is displayed (terminals S1 to S6).
_ 11 11 11
Monitor
(Monitor U-XX)
U-07
1: S1 closed
1: S2 closed
1: S3 closed
1: S4 closed
1: S5 closed
1: S6 closed
Always blank
Inverter status is displayed.
11
-
1 11 11
U-08
1: During run
1: Reverse run
1: Inverter ready
1: Fault
1: MODBUS error
Always blank
1: MA-MC output OFF
1: M1-M2 output OFF
FP5/GP5 User’s Manual 95
Appendix A-2
Digital Operator Monitor Display
Name
(LCD Operator Display)
Description
Monitor
(Monitor U-XX)
U-09 Last 4 faults are displayed.
U-10 Last 4 digits of software revision number are displayed.
Elapsed time is displayed as follows:
X X X X X X Elapsed time (in units of 1 hour)
U-11
U-12 U-10 (last 4 digits)
U-11 (first 2 digits)
Acceleration time 1 (n018) can be set/read in units of 0.1s
(1s for 1,000s and above).
Deceleration time 1 (n019) can be set/read in units of 0.1s
(1s for 1,000s and above).
279,620 hours maximum
U-13 PID feedback is displayed in units of 0.1Hz.
U-15 Kilowatt-hour meter (4 least significant digits)
U-16 Kilowatt-hour meter (2 most significant digits)
Acceleration Time 1
(Accel Time 1)
Deceleration Time 1
(Decel Time 1)
V/f Pattern Selection
(V/f Selection)
Frequency Reference Gain
(Terminal FV Gain)
Frequency Reference Bias
(Terminal FV Bias)
Motor Rated Current
(Motor rated FLA)
PID Selection
(PID Mode)
Energy Saving Selection
(Energy sav Sel)
PRGM Mode
(Parameter nXXX)
V/f pattern selection (n010) can be set during stop.
Frequency reference gain (n048) can be set during stop.
Frequency reference bias (n049) can be set during stop.
Motor rated current (n033) can be set during stop.
PID selection (n084) can be set during stop.
Energy saving selection (n096) can be set during stop.
Parameters can be set/read during stop.
FP5/GP5 User’s Manual 96
Appendix A-3
CE Conformance
A-3 CE Conformance (Applicable to 460V Models Only)
CE CONFORMANCE - Low Voltage Directive (LVD) Compliance
B1 B2
⊕ 1
⊕ 2
L1
L2
L3
T1
T2
T3
1
IM
Multi-Function
Inputs
S1 - Fixed
S2
S3
S4
S5
S6
SC (Com)
Gate Drive
3
PWM
8 bit
0~10V AM
(Com) AC
Multi-Function
Analog Outputs
Analog Inputs
Input FI selectable
4~20mA or
0~10V
0~+10V
4~20mA
G
FS (+15V)
FV
FI
(20k
(250
FC (0V)
Ω
Ω
)
)
A/D
10 bit
Serial Port
RS-232
(10-pin)
Digital
Operator
G
MA
MB
MC
M1
M2
2
Multi-Function Contact Outputs
250VAC, 1A or less
30VDC, 1A or less
(overvoltage category 2)
Figure 11 FP5/GP5 Terminal Diagram
•
These circuits are hazardous and are separated from accessibility by protective separation.
‚
These circuits are not separated from hazardous circuits by protective separation, but only with basic insulation. These circuits cannot be accessed and must not be interconnected with any circuits which are accessible, unless they are isolated from accessible circuits by supplemental insulation. These circuits can be connected only to the following circuits:
30VDC or less (overvoltage category 2)
250VAC or less (overvoltage category 2)
ƒ
These circuits are not separated from hazardous circuits by protective separation, but only with basic insulation. These circuits cannot be accessed and must not be interconnected with any circuits which are accessible, unless they are isolated from accessible circuits by supplemental insulation.
FP5/GP5 User’s Manual 97
Appendix A-3
CE Conformance
CE CONFORMANCE - Electro-Magnetic Compatibility (EMC) Compliance
In order to conform to EMC standards, exclusive-use methods are required for line filter application, cable shielding and inverter installation. An outline of the methods follows.
The line filter and the inverter must be mounted on the same metal plate. The filter should be mounted as close to the inverter as practical. Keep cable as short as possible.
The metal plate should be securely grounded. The ground of the line filter and inverter must be bonded to the metal plate with as much area as possible.
For line power input cable, screened cable is recommended at least within the panel.
The screen of the cable should be connected to a solid ground. For the motor cable, screened cable (max. 20m) must be used and the screen of the motor cable is connected to ground at both ends by a short connection, using as large an area as practical.
The following table and figures show the line filter list for EMC standards and the installation/wiring of inverter and line filter.
Line Filter List for EMC Standards
Inverter
Model
CIMR-
P5Uxxxx
Model
Line Filter (Manufactured by Schaffner)
Rated
Current
(A)
Mass
(kg)
Dimensions (mm)
W
×
D
×
H
40P4
40P7
41P5
42P2
FS4874-7/07 7 1.1 50
×
126
×
255
43P7
44P0
45P5
47P5
FS4874-18/07 18 1.7 55
FS4874-30/07 30 1.8 60
×
×
142
150
×
×
305
335
4011
FS4874-42/07 42 2.8 70
×
185
×
329
4015
4018 FS4874-55/07 55 3.1 80
×
185
×
329
4022
FS4874-75/34 75 4.0 80
×
220
×
329
4030
4037 FS4874-100/35 100 5.5 90
×
220
×
379
4045 FS4874-130/35 130 7.5 110
×
240
×
429
4055 FS4874-180/07 180 11 110
×
240
×
438
4075 FS4874-300/99 300 15 300
×
564
×
160
4110
FS4874-400/99 400 22 300
×
564
×
160
4160
4185 FS4874-500/99 500 19.5 300
×
564
×
160
4220 FS4874-600/99 600 20.5 300
×
564
×
160
4300 FS4874-900/99 900 33.5 300
×
564
×
160
FP5/GP5 User’s Manual 98
Appendix A-3
CE Conformance
L2 L1
L3 GND
Ground Bonds (Remove any paint)
Line
Power
Filter
Load
Inverter
W
Cable Length:
Max. 40cm
Metal Plate
Motor Cable: Max. 20m
Ground Bonds
(Remove any paint)
IM
Fig. 12 Installation of Line Filter and Inverter (Models FP5/GP5 40P4 to 4015)
L2 L1
L3 GND
Ground Bonds
(Remove any paint)
Line
Power
Filter
Load
Inverter
L3 W
Cable Length:
Max. 40cm
Metal Plate
Motor Cable: Max. 20m
Ground Bonds
(Remove any paint)
IM
Fig. 13 Installation of Line Filter and Inverter (Models FP5/GP5 4018 to 4300)
FP5/GP5 User’s Manual 99
Appendix A-3
CE Conformance
Safety Warnings and Operating Information for Inverters
Introduction
Depending on their protection rating configuration, parts of inverters can have live, uninsulated and hot surfaces during operation. If housing components, the control unit or terminal covers are removed, incorrect installation and operation can lead to serious injuries and damage to other installations. It is thus absolutely essential to observe all the warnings and instructions in the operating manual. Installation, setup and maintenance should only be performed by properly qualified staff. (IEC 364 / Cenelec HD 384 or DIN VDE 0100 and IEC 664 or DIN VDE. The applicable national safety and accident prevention regulations must also be observed.) For the purpose of observance of the safety requirements qualified staff are defined as individuals who are familiar with the installation, setup and operation of the converters and who have the proper qualifications for this work.
Proper use for intended purpose
Inverters are designed for installation in electrical systems or machines. A converter installed in a machine may only be activated if the machine conforms to the provisions of
EU directive 89/392/EEC (machine directives). EN 60204 must also be observed. The converter may also only be operated if the requirements of the EMC directive (89/336/
EEC) are also satisfied. This frequency converter conforms to the requirements of the lowvoltage directive, 73/23/EEC. The harmonized standards of the prEN 50178/DIN VDE
0160 series have been applied, in combination with EN 660439-1 / VDE 06600 Part 500 and EN 60146 / VDE 0558. The specifications on the ratings plate and the specifications and connection requirements described in the documentation must be observed at all times.
Transportation and storage
All instructions for transport, storage and proper handling must be observed. Climatic and environmental conditions must conform to the requirements of prEN 50178.
Installation
The converters must be installed and cooled in compliance with the regulations outlines and referred to in the documentation. The cooling air flow direction is an important requirement that must be observed. This means that the unit may only be installed and operated in the specified orientation (e.g. upright). All distances specified must also be observed. The converters must be protected against excessive stresses. No components may be bent and no distances required for proper insulation may be changed. To prevent the risk of static electricity damage never touch electronic components or contacts.
Electrical connections
All national safety regulations (e.g. VBG 4) must be observed when working on live equipment. The electrical installation of the units must conform to the applicable regulations. For further information please refer to the documentation. In particular, please take care to observe all installation instructions as regards proper EMC immunity, e.g. for shielding, earthing, location of filters and cable routing. This also applies for equipment with CE approvals. Compliance with the EMC legislation limits is the responsibility of the machine or system manufacturer.
RCCBs
For information on the use of RCCBs with inverters please contact your supplier or
Saftronics representative.
Operation
In some systems it may be necessary to install additional monitoring and protective facilities to comply with the applicable safety and accident prevention regulations. The only changes permitted are to the operator software of the inverters. Please note that the capacitors can remain charged for up to around 5 minutes after the frequency converter has been disconnected from the power supply. You should thus always wait for a short period before opening the unit and touching the electrical connections.
FP5/GP5 User’s Manual 100
Appendix A-3
CE Conformance
EU Manufacturer’s Declaration
Products
Static inverter, series FP5/GP5
Scope
Saftronics inverters are components (BDM* , defined by IEC 22G/21CDV) designed exclusively for installation in machines or systems (end products) by qualified re-users
(e.g. mechanical engineering manufacturers).
Responsibility
As a component manufacturer we are responsible for the provision of installation instructions. These can be found in the installation guidelines publication EZZ006908.
Our products have been tested by authorized bodies pursuant to the requirements of the standards listed below. The products conform to these standards, subject to due and proper observation of the installation instructions provided in section 10 of this manual:
Immunity — EMC resistance pursuant to EN50082-2, Part 2:
EN 61000-4-2 Resistance to static discharge
EN 61000-4-4 Resistance to high-speed transients and bursts
EN 61000-4-8 Testing of resistance to magnetic fields with power systems frequencies
ENV 50140 Resistance to high-frequency magnetic fields
ENV 50141 Resistance to conducted interference
Emissions — EMC interference emissions pursuant to EN50081-2, Part 2:
EN 55011 Class A or B limit curve under the conditions described in the operating instructions in the installation guidelines, EZZ006908.
Always observe all the safety instructions provided in this product documentation!
FP5/GP5 User’s Manual 101