D ATA S HEET
Network Communication Modules
2800 Network Cards
NCM-W Features:
Supports twisted-pair wire medium
Two programmable data thresholds
Transformer coupling provides electrical isolation between nodes
Pluggable terminal wiring with strain relief
Data is regenerated at each node
Repeaters are available to increase signal
Repeaters may be utilized to switch media type
Up to 1000m between nodes in a point-to-point fashion (actual distance varies with wire quality)
NCM-F Features
Supports multi-mode fibre optic cable
Data is immune to all environmental noise
Optical isolation prevents ground loops
FireSense 2800 Network fibre-optic medium
Fibre Type – 62.5/125 micrometers (multimode)
Maximum attenuation is 8 dB with 62.5/125 µm cable and 4.2dB with 50/125 µm cable
Wavelength: 820 nanometres (use standard 850 nm fibre)
Connectors: ST ® style
312.5 Kbaud transmission rate
Data is regenerated at each node
Description:
The Network Communication Module (NCM) provides FireSense’s AFP-2800 Fire Alarm Control Panels with a means to connect to the FireSense 2800 Network. Three types of NCM are available: NCM-W for connecting nodes with twisted-pair wire and NCM-F for connecting nodes with multi-mode fibre optic cable and NCM-SMOF for connecting single-mode fibre-optic cable.
Mixing Wire and Fibre on the same Network –
In some networks, it may be necessary to mix twisted-pair wire and multimode fibre optic cable. In these instances a 2800-NET-WF-R may be used as an interface between wire and multi-mode fibre.
Products
N-NCM-W
Network Media
Wire
N-NCM-F
N-NCM-SMOF
N-HS-NCM-MF
Multimode Optical Wire
Single Mode Optical Fibre
High Speed Multi Mode Fibre
N-HS-NCM-MF-SF
N-HS-NCM-W
N-HS-NCM-SF
N-HS-NCM-W-MF
N-HS-NCM-W-SF
N-HS-NET-WF-R
N-HS-NET-W-R
High Speed Multi Mode-Single Mode Fibre
High Speed Wire
High Speed Single Mode Optical Fibre
High Speed Wire to Multimode Optical Fibre
High Speed Wire to Single Mode Optical Fibre
High Speed Network Wire to Fibre Repeater
High Speed Network Wire to Wire Repeater
G:\Documents\Datasheets\Word Datasheets\2800 Network Cards.Doc RevDate: 9 September 2015
NSW (Head Office)
18-20 Brookhollow Ave
Baulkham Hills NSW 2153
Tel 02 8850 2888
Fax 02 8850 2999 www.firesense.com.au
VIC (Branch Office)
4/297 Ingles St
Port Melbourne VIC 3207
Tel 03 9646 4557
Fax 03 9646 4558
QLD (Branch Office)
2/225 Queensport Rd Nth
Murarrie QLD 4172
Tel 07 3890 8842
Fax 07 3890 8894