WIKA DI35 Operating instructions


Add to my manuals
64 Pages

advertisement

WIKA DI35 Operating instructions | Manualzz

Operating instructions

Digital indicator, model DI35-D

EN

Digital indicator for panel mounting

EN

Operating instructions model DI35-D Page 3 - 61

© 2017 WIKA Alexander Wiegand SE & Co. KG

All rights reserved.

WIKA ® is a registered trademark in various countries.

Prior to starting any work, read the operating instructions!

Keep for later use!

2 WIKA operating instructions digital indicator, model DI35-D

Contents

Contents

1. General information

2. Design and function

2.1 Overview, version for panel mounting . . . . . . . . . . . . . . . . 7

6

7

2.2 Overview, version in desktop case . . . . . . . . . . . . . . . . . 8

2.3 Description . . . . . . . . . . . . . . . . . . . . . . . . . 9

2.4 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . 9

3. Safety 10

3.1 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . 10

3.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . 11

3.3 Improper use. . . . . . . . . . . . . . . . . . . . . . . . . 11

3.4 Personnel qualification . . . . . . . . . . . . . . . . . . . . . 12

3.5 Labelling, safety marks . . . . . . . . . . . . . . . . . . . . . 13

4. Transport, packaging and storage 14

4.1 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . 14

4.2 Packaging and storage . . . . . . . . . . . . . . . . . . . . . 14

5. Commissioning 15

5.1 Requirements for the installation location . . . . . . . . . . . . . . . 15

5.2 Mounting, version for panel mounting . . . . . . . . . . . . . . . . 15

5.3 Mounting, version in desktop case . . . . . . . . . . . . . . . . . 16

5.4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . 16

5.4.1 Notes on installation. . . . . . . . . . . . . . . . . . . . 16

5.4.2 Pin assignment, version for panel mounting . . . . . . . . . . . . 17

5.4.3 Pin assignment, version in desktop case . . . . . . . . . . . . . 18

5.5 Interface connector . . . . . . . . . . . . . . . . . . . . . . 19

5.6 Switching on the digital indicator . . . . . . . . . . . . . . . . . . 19

5.7 Connection examples, version for panel mounting . . . . . . . . . . . . 20

6. Operation 22

6.1 Key functions. . . . . . . . . . . . . . . . . . . . . . . . . 22

6.2 Accessing and exiting programming mode. . . . . . . . . . . . . . . 22

6.3 Navigating in the menu . . . . . . . . . . . . . . . . . . . . . 23

6.4 Changing numerical values . . . . . . . . . . . . . . . . . . . . 23

6.5 Accessing or clearing MIN/MAX values . . . . . . . . . . . . . . . . 23

6.6 Switching display between measuring inputs . . . . . . . . . . . . . . 24

EN

WIKA operating instructions digital indicator, model DI35-D 3

Contents

EN

7. Description of program numbers 25

7.1 Setting measuring inputs. . . . . . . . . . . . . . . . . . . . . 25

7.1.1 Input signal . . . . . . . . . . . . . . . . . . . . . . . 25

7.1.2 Start and end value . . . . . . . . . . . . . . . . . . . . 26

7.1.3 Number of decimal places. . . . . . . . . . . . . . . . . . 27

7.1.4 Offset adjustment . . . . . . . . . . . . . . . . . . . . 27

7.2 General settings . . . . . . . . . . . . . . . . . . . . . . . 27

7.2.1 Default display. . . . . . . . . . . . . . . . . . . . . . 27

7.2.2 Switching of measuring inputs . . . . . . . . . . . . . . . . 28

7.2.3 Refresh rate . . . . . . . . . . . . . . . . . . . . . . 29

7.2.4 Measuring time . . . . . . . . . . . . . . . . . . . . . 29

7.2.5 Display brightness . . . . . . . . . . . . . . . . . . . . 29

7.3 Arithmetic function . . . . . . . . . . . . . . . . . . . . . . . 29

7.4 Setting the analogue output (option) . . . . . . . . . . . . . . . . . 30

7.4.1 Start and end value . . . . . . . . . . . . . . . . . . . . 30

7.4.2 Reference value . . . . . . . . . . . . . . . . . . . . . 31

7.4.3 Output signal . . . . . . . . . . . . . . . . . . . . . . 31

7.4.4 Example. . . . . . . . . . . . . . . . . . . . . . . . 31

7.5 Setting the serial interface (option) . . . . . . . . . . . . . . . . . 32

7.6 Setting user authorisations . . . . . . . . . . . . . . . . . . . . 33

7.6.1 Authorisation levels . . . . . . . . . . . . . . . . . . . . 33

7.6.2 Cancelling the password protection . . . . . . . . . . . . . . 33

7.7 Setting special functions . . . . . . . . . . . . . . . . . . . . . 34

7.7.1 Function of the digital input . . . . . . . . . . . . . . . . . 34

7.7.2 Function of the multi-function key . . . . . . . . . . . . . . . 34

7.7.3 TARE function . . . . . . . . . . . . . . . . . . . . . . 34

7.7.4 HOLD function . . . . . . . . . . . . . . . . . . . . . 35

7.8 Setting switching outputs . . . . . . . . . . . . . . . . . . . . 36

7.8.1 Flashing display on reaching the switch points . . . . . . . . . . . 36

7.8.2 Reference value . . . . . . . . . . . . . . . . . . . . . 36

7.8.3 Switch points . . . . . . . . . . . . . . . . . . . . . . 37

7.8.4 Switch behaviour . . . . . . . . . . . . . . . . . . . . . 37

7.9 Linearising sensors . . . . . . . . . . . . . . . . . . . . . . 42

7.10 Reading the serial number . . . . . . . . . . . . . . . . . . . . 44

7.11 Restoring factory settings . . . . . . . . . . . . . . . . . . . . 44

4 WIKA operating instructions digital indicator, model DI35-D

Contents

8. Faults 44

9. Maintenance and cleaning 47

9.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 47

9.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 47

10. Dismounting, return and disposal 48

10.1 Dismounting, version for control panel . . . . . . . . . . . . . . . . 48

10.2 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

10.3 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . 48

11. Specifications 49

Appendix 1: Overview of program numbers 55

Declarations of conformity can be found online at www.wika.com.

EN

WIKA operating instructions digital indicator, model DI35-D 5

1. General information

1. General information

EN

■ The digital indicator described in these operating instructions has been designed and manufactured using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during production. Our management systems are certified to ISO 9001 and ISO 14001.

■ These operating instructions contain important information on handling the instrument. Working safely requires that all safety instructions and work instructions are observed.

■ Observe the relevant local accident prevention regulations and general safety regulations for the instrument's range of use.

■ The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and readily accessible to skilled personnel at any time. Pass the operating instructions on to the next operator or owner of the instrument.

■ Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.

■ The general terms and conditions contained in the sales documentation shall apply.

■ Subject to technical modifications.

■ Further information:

- Internet address:

- Relevant data sheet:

- Application consultant: www.wika.de / www.wika.com

AC 80.03

Tel.: +49 9372 132-0

Fax: +49 9372 132-406 [email protected]

6 WIKA operating instructions digital indicator, model DI35-D

2. Design and function

2. Design and function

2.1 Overview, version for panel mounting

 

     

Designation

 Key [☼]

Key [▼]

Key [▲]

 Key [○]

 Switch point display

 Mounting element with clamping screw

 7-segment display

 Product label

Description

Programming mode is accessed

Changes to a deeper parameter level

MIN memory is accessed

Changes lower limit values

Changes between parameters

Changes parameter values

MAX memory is accessed

Changes lower limit values

Changes between parameters

Changes parameter values

Multi-function key

Displays the status of the switching outputs

Used for fixing

Displays measured values, program numbers or parameters

Contains product information

WIKA operating instructions digital indicator, model DI35-D 7

EN

EN

2. Design and function

2.2 Overview, version in desktop case

(267 incl.

displa

250

mm

inc l. An zeig e un d A

250 m sste cke r oh ne G ege nste cke r)

170

mm

Plug A Plug C

3

2

4

1

4

3

5 6 1

2

3

2

4

1

1

4

6

2

8

5

3

7

Plug B Plug D

Designation

 Digital indicator (→ for description see chapter 2.1)

 Mains plug with switch

 Plug A (measuring input 1)

 Plug B (measuring input 2)

 Plug C (switching outputs)

 Plug D (transmitter power supply, analogue output, serial interface)

8 WIKA operating instructions digital indicator, model DI35-D

2. Design and function

2.3 Description

The model DI35 digital indicator is a multi-function and very accurate instrument for a wide variety of measuring tasks.

The DI35-D is equipped with two inputs for standard signals (0/4 … 20 mA and DC 0 …

10 V) that can be used in any combination. The display can show one of the two input signals or a calculated value. Calculations can be made by means of the four basic arithmetic operations (+ - * /) and an additional constant multiplier.

In addition, both versions offer the possibility to calibrate sensors and linearise using up to 30 points. This allows further adaptation of the displayed values to different sensor signals and application requirements. The standard features are completed by a transmitter power supply, a HOLD function and a TARE function for the correction of offset shifts and sensor drifts. The sampling rate and display time can be configured and the display can be dimmed. Unauthorised alteration of the set instrument parameters can be prevented via different user levels, in conjunction with a freely selectable access code.

Optionally available are up to four freely configurable switch contacts, an analogue output signal and a serial interface.

EN

Functions

Calculation function (4 basic calculation types, constant multiplier)

Analogue output

Retrieval of the MIN/MAX value

HOLD and TARE function

Linearisation of the measuring input

Semiconductor switching outputs (option)

Switch point display (option)

Adjustable switch points (option)

2.4 Scope of delivery

Version for panel mounting

Digital indicator

Sealing

2 mounting elements

Operating instructions

Unit characters

WIKA operating instructions digital indicator, model DI35-D 9

2. Design and function / 3. Safety

EN

Version in desktop case

Digital indicator

Mains connection cable with connector per CEE 7/4

Operating instructions

Unit characters

Mating connector connections

In place of the mains connection cable supplied, other mains connection cables can be used so long as they fulfil the following characteristics:

Connector per IEC 60320 C13 for connection to the instrument

Protective conductor available

Cable is certified and approved by a recognised notified body for the country of operation

Cross-check scope of delivery with delivery note.

3. Safety

3.1 Explanation of symbols

DANGER!

... identifies hazards caused by electrical power. Should the safety instructions not be observed, there is a risk of serious or fatal injury.

WARNING!

... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.

CAUTION!

... indicates a potentially dangerous situation that can result in light injuries or damage to equipment or the environment, if not avoided.

Information

... points out useful tips, recommendations and information for efficient and trouble-free operation.

10 WIKA operating instructions digital indicator, model DI35-D

3. Safety

3.2 Intended use

The DI35 digital indicator is designed for the evaluation and display of sensor signals.

With the switching outputs, it is possible to realise simple control functions.

The digital indicator is suitable only for indoor applications with pollution degree 2 and overvoltage category II.

This is a class B instrument for emissions and is intended for use in industrial environments. In other environments, e.g. residential or commercial installations, it can interfere with other equipment under certain conditions. In such circumstances the operator is expected to take the appropriate measures.

Only use the digital indicator in applications that lie within its technical performance limits (e.g. max. ambient temperature).

→ For performance limits see chapter 11 “Specifications”.

The instrument has been designed and built solely for the intended use described here, and may only be used accordingly.

The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.

EN

3.3 Improper use

WARNING!

Injuries through improper use

Improper use of the instrument can lead to hazardous situations and injuries.

▶ Refrain from unauthorised modifications to the instrument.

▶ Do not open the instrument.

▶ Do not use the instrument within hazardous areas.

Any use beyond or different to the intended use is considered as improper use.

WIKA operating instructions digital indicator, model DI35-D 11

3. Safety

EN

3.4 Personnel qualification

WARNING!

Risk of injury should qualification be insufficient

Improper handling can result in considerable injury and damage to equipment.

▶ The activities described in these operating instructions may only be carried out by personnel who have the qualifications described below.

Skilled electrical personnel

Skilled electrical personnel are understood to be personnel who, based on their technical training, know-how and experience as well as their knowledge of country-specific regulations, current standards and directives, are capable of carrying out work on electrical systems and independently recognising and avoiding potential hazards. The skilled electrical personnel have been specifically trained for the work environment they are working in and know the relevant standards and regulations. The skilled electrical personnel must comply with current legal accident prevention regulations.

12 WIKA operating instructions digital indicator, model DI35-D

3. Safety

3.5 Labelling, safety marks

Product label, panel mounting

Power supply:

Input:

Product no:

Product code:

18...30V / 10...40V (max. 15VA)

2 x DC 0...10V ; DC 0/4...20mA

46855373

DI35-D-2Y5C32B-Z

Serial no: Serial No.

Alarm outputs

21 22 23 24 25 26 27 28 29 30 31 32

Interface

RS-232

(not insulated)

41 42 43

Internal bridge

1 2 3 4 5 6 7 8 9 10 11 12 13 14

+ +

0/4-20mA 0/4-20mA

0-5/10V 0-5/10V

 Pin assignment

 Serial number

 Specifications

Product label, desktop case

Pin assignment

Serial number

Serial no:

Alarm outputs

Serial no.

21 22 23 24 25 26 27 28 29 30 31 32

Internal bridge

1 2 3 4 5 6 7 8 9 10 11 12 13 14

+ +

0/4-20mA 0/4-20mA

0-5/10V 0-5/10V

EN

Symbols

Before mounting and commissioning the instrument, ensure you read the operating instructions!

WIKA operating instructions digital indicator, model DI35-D 13

4. Transport, packaging and storage

4. Transport, packaging and storage

EN

4.1 Transport

Check the digital indicator for any damage that may have been caused by transport.

Obvious damage must be reported immediately.

CAUTION!

Damage through improper transport

With improper transport, damage to property can occur.

▶ When unloading packed goods upon delivery as well as during internal transport, proceed carefully and observe the symbols on the packaging.

▶ With internal transport, observe the instructions in chapter 4.2

“Packaging and storage”.

4.2 Packaging and storage

Do not remove packaging until just before mounting.

Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for repair).

Permissible conditions at the place of storage:

Storage temperature: -20 ... +80 °C

Humidity: 0 ... 75 % relative humidity (no condensation)

Avoid exposure to the following factors:

Direct sunlight or proximity to hot objects

Mechanical vibration, mechanical shock (putting it down hard)

Soot, vapour, dust and corrosive gases

Store the digital indicator in its original packaging in a location that fulfils the conditions listed above. If the original packaging is not available, pack and store the instrument as described below:

1. Wrap the instrument in a plastic film.

2. Place the instrument, along with shock-absorbent material, in the packaging.

14 WIKA operating instructions digital indicator, model DI35-D

5. Commissioning

5. Commissioning

If the instrument is transported from a cold into a warm environment, the formation of condensation may result in instrument malfunction. Before putting it into operation, wait for the instrument temperature and the room temperature to equalise.

EN

5.1 Requirements for the installation location

■ In the vicinity there should be no magnetic or electrical fields, e.g. from transformers,

■ radio-telephones or electrostatic discharges.

In the vicinity there should be no strong heat sources. The permissible operating temperature must not be exceeded (max. 50 °C).

The installation location must conform to pollution degree 2.

No direct sunlight or proximity to hot objects

No mechanical vibration, mechanical shock (putting it down hard)

No soot, vapour, dust and corrosive gases

5.2 Mounting, version for panel mounting

107,0

120

,0

3,0

96,0 139

,0

 Mounting element with clamping screw

 Sealing

Cutting out the control panel

Control panel thickness max. 15 mm

Panel cutout 92.0

+0.6

x 45.0

+0.3

mm

Recommended mounting grid: 120 mm horizontal, 96 mm vertical

WIKA operating instructions digital indicator, model DI35-D 15

5. Commissioning

EN

Installing the digital indicator

1. As required, slide the unit characters into the window provided via the lateral channel.

2. Remove the mounting elements.

3. Slide the seal over the digital indicator.

4. Slide the digital indicator into the control panel from the front.

Check the seal is properly seated.

5. Lock the mounting elements into place and tighten the clamping screws (max. 0.1 Nm).

5.3 Mounting, version in desktop case

▶ Connect the digital indicator to the socket using the mains connection lead.

5.4 Electrical connection

5.4.1 Notes on installation

The voltage supply must comply with overvoltage category II.

With the panel mounting version, protect the voltage supply with a slow fuse of max.

0.5 A. With the desktop case version, the fuse is integrated.

For the panel-mounting version, a suitable isolation device must be provided.

Route the signal input lines and signal output lines separately.

Route outward and return lines side-by-side.

Galvanically isolated potentials must be connected to a suitable point (e.g. earth or plant ground).

For high-accuracy requirements and small measuring signals, the sensor wires must be shielded and twisted. The shield should be connected at one end only to a suitable equipotential bonding (e.g. measurement ground).

Avoid electrostatic discharges in the area of the terminals.

16 WIKA operating instructions digital indicator, model DI35-D

5. Commissioning

5.4.2 Pin assignment, version for panel mounting

Terminal assignment (upper terminal block)

Switching outputs Serial interface

21 22 23 24 25 26 27 28 29 30 31 32 41 42 43

GND (RS)

RS 232

EN

GND (RS)

RS 485

For further information see chapter 11 “Specifications”

Terminal assignment (lower terminal block)

1 2

+

3 4 5 6 7 8 9 10 11 121314 l + l + l + l + L N

+

0/4 ... 20 mA l +

0/4 ... 20 mA l

0 ... 10 V 0 ... 10 V

For further information see chapter 11 “Specifications”

WIKA operating instructions digital indicator, model DI35-D 17

EN

5. Commissioning

5.4.3 Pin assignment, version in desktop case

Plug A (measuring input 1) Plug C (switching outputs)

Plug B (measuring input 2)

Plug D (digital input, analogue output, serial interface)

Power supply:

Input:

Product no:

Product code:

Serial no:

Alarm outputs

100..240V (max. 15VA)

2 x DC 0...10V ; DC 0/4...20mA

46857171

DI35-D-2W5CZJB-Z

Serial no.

21 22 23 24 25 26 27 28 29 30 31 32

Internal bridge

1 2 3 4 5 6 7 8 9 10 11 12 13 14

+ +

0/4-20mA 0/4-20mA

0-5/10V 0-5/10V

Suitable mating connectors are included in the delivery.

Depending on the version, not all connections are available (instruments without switch points do not feature a plug C, instruments without analogue output and serial interface do not feature plug D).

18 WIKA operating instructions digital indicator, model DI35-D

5. Commissioning

5.5 Interface connector

RS-232

The RS-232 interface cables must be connected 1:1 (TxD to TxD and RxD to RxD).

PC or

PLC

DI35

EN

RS-485

The RS-485 interface is connected via a shielded data cable with twisted pairs. At each end of the bus segment, a termination of the bus lines must be connected. This is needed in order to ensure safe data transfer over the bus. For this, a resistor (120 Ω) is inserted between data B (+) and data A (-).

PC or PLC

DATA B (+)

DATA A (―)

DI35

Where interfaces are not galvanically isolated, the potential reference between the interface and the measuring input can lead to a compensating current. This compensating current can influence the measuring signals.

5.6 Switching on the digital indicator

▶ Connect the power supply.

⇒ Segment test is carried out. Check the correct operation of all LEDs

Software type and software version are displayed.

⇒ Digital indicator is ready for operation.

WIKA operating instructions digital indicator, model DI35-D 19

EN

5. Commissioning

5.7 Connection examples, version for panel mounting

2-channel measurement with current signals, 2-wire transmitter, AC 100 ... 240 V supply

Input 1 Input 2

Analogue output

Transmitter power supply

Power supply

AC 100 ... 240 V

2-channel measurement with voltage signals, 3-wire transmitter, DC 10 ... 40 V supply

Input 1 Input 2

Analogue output

Transmitter power supply

Power supply

20

DC 10 ... 40 V

WIKA operating instructions digital indicator, model DI35-D

5. Commissioning

1-channel measurement with current signal in conjunction with digital signal and transmitter power supply, 2-wire transmitter, DC 100 ... 240 V supply

Input 1 Input 2

Analogue output

Transmitter power supply

Power supply EN

AC 100 ... 240 V

WIKA operating instructions digital indicator, model DI35-D 21

6. Operation

EN

6. Operation

6.1 Key functions

Key

Key [☼]

Key [☼] + [▼] [▲]

Key [▼]

Key [▲]

Key [○]

Function

Programming mode is accessed

Pressing < 1 s: Changes the cursor position

Pressing > 1 s: Saves all parameters

Scrolls through the program numbers (PN)

Pressing > 1 s: Automatically starts cycle

Pressing < 1 s: Selects or changes parameter

Pressing > 1 s: Switches the input channel display

Pressing < 1 s: Selects or changes parameter

Pressing > 1 s: Switches the input channel display

Multi-function key

Selects functions (e.g. HOLD or TARE)

6.2 Accessing and exiting programming mode

Accessing programming mode

▶ Press [☼].

⇒ Digital indicator is in programming mode

Lowest available program number is displayed.

→ Available program numbers are dependent upon the authorisation level, see chapter

7.6.1 “Authorisation levels”.

Exiting the programming mode

If no keys are pressed within 7 seconds, the digital indicator switches back to display mode.

22 WIKA operating instructions digital indicator, model DI35-D

6. Operation

6.3 Navigating in the menu

[☼]

PN0

[☼] 1s

[

▲/▼

]

[☼]+

[ ▲] [☼]+

[ ▼]

Parameter 1

Parameter 2

Parameter 3

PN1

[☼]+

[ ▲]

PN...

[☼]+

[ ▼]

[☼] 1s

[ ▲/▼ ]

6.4 Changing numerical values

Parameter [☼] 1. Zahl

[ ▲] [▼]

[☼] 1s

-9999 … 99999

[☼]

6.5 Accessing or clearing MIN/MAX values

Accessing MIN value

▶ Press [▼].

⇒ MIN value is displayed 7 s.

Accessing MAX value

▶ Press [▲].

⇒ MAX value is displayed 7 s.

Clearing MIN/MAX values

▶ Press [▼] + [▲].

⇒ Horizontal bars are displayed.

MIN/MAX values are cleared.

2. Zahl

[ ▲] [▼]

[ ▲]

[ ▼]

The MIN/MAX values are lost when the instrument is switched off.

EN

WIKA operating instructions digital indicator, model DI35-D 23

6. Operation

EN

6.6 Switching the display between measuring inputs

The switching of measuring inputs changes between the display values of the measuring inputs and the display value of the arithmetic calculation. The display value of the arithmetic calculation is only displayed when this has been configured.

The following methods are supported:

Method

Static

Triggered

Cyclic

Description

A preset display value is shown for the duration of the trigger signal.

With each trigger pulse, the measuring input is switched further (series Ch1, Ch2, Ar).

The change is made cyclically over a preset time interval

(series Ch1, Ch2, Ar).

For the trigger signal, the multi-function button or the digital input can be used (for programming, see chapter 7.6 “Switching of measuring inputs”)

Before each change, the description of the measuring input is displayed.

Measuring input 1 = Ch1

Measuring input 2 = Ch2

Arithmetic calculation = Ar

24 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

7. Description of program numbers

For an overview of the program numbers see appendix 1 “Overview of program numbers”

7.1 Setting measuring inputs

7.1.1 Input signal

The digital indicator features two measuring inputs. Each measuring input can be set for a different input signal.

EN

PN Function

0 Input signal, measuring input 1

5 Input signal, measuring input 2

Parameter

Factory calibration

1 = DC 0 ... 10 V

2 = 0 ... 20 mA

3 = 4 ... 20 mA

Sensor calibration

4 = DC 0 ... 10 V

5 = 0 ... 20 mA

6 = 4 ... 20 mA

Parameters 1 ... 3 Used for standardised input signals. There must be no signal applied to the measuring input. The corresponding display values can be manually assigned.

→ For assigning display values, see chapter 7.1.2 “Start and end value”

Parameters 4 ... 6 Used for non-standardised input signals. The signal must be applied to the measuring input and the corresponding display value manually assigned.

→ For assigning display values, see chapter 7.1.2 “Start and end value”

WIKA operating instructions digital indicator, model DI35-D 25

7. Description of program numbers

EN

7.1.2 Start and end value

With this value pair, the measuring signal is assigned the desired indication value.

PN Function

1

2

6

7

End value (end of measuring range)

Measuring input 1

Start value (start of measuring range)

Measuring input 1

End value (end of measuring range)

Measuring input 2

Start value (start of measuring range)

Measuring input 2

Parameter

-9999 ... 99999

-9999 ... 99999

-9999 ... 99999

-9999 ... 99999

Procedure for standard signals

▶ Set the corresponding display values.

Procedure for non-standard input signals

1. Apply the end value of the input signal to the measuring input.

2. Select PN 1/PN 6.

3. Set the display value.

4. Press [☼].

⇒ Input signal is associated with display value.

5. Apply the start value of the input signal to the measuring input.

6. Select PN 2/PN 7.

7. Set the display value.

8. Press [☼].

⇒ Input signal is associated with display value.

Display values are assigned.

26 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

7.1.3 Number of decimal places

Specifies the number of decimal places that are displayed on the screen. This parameter has no influence on the scaling of the indication value.

PN

3

8

Function Parameter

Number of decimal places, measuring input 1 00000 ... 0.0000

Number of decimal places, measuring input 2 00000 ... 0.0000

7.1.4 Offset adjustment

The input signal is shifted in parallel by the offset value.

PN

4

9

Function

Offset value, measuring input 1

Offset value, measuring input 2

Parameter

-9999 ... 99999

-9999 ... 99999

EN

This parameter can be altered directly by making a tare if this was triggered through the multi-function button or the digital input.

7.2 General settings

7.2.1 Default display

Defines the measuring input which should be displayed as standard.

PN

10

Function

Default display

Parameter

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

→ For arithmetic function see chapter 7.3 “Arithmetic function”.

WIKA operating instructions digital indicator, model DI35-D 27

7. Description of program numbers

EN

7.2.2 Switching of measuring inputs

The switching of measuring inputs changes between the display values of the measuring inputs and the display value of the arithmetic calculation. The display value of the arithmetic calculation is only displayed when this has been configured.

The following methods are supported:

Method

Static

Triggered

Cyclic

Description

A preset display value is shown for the duration of the trigger signal.

With each trigger pulse, the measuring input is switched further (series

Ch1, Ch2, Ar).

The change is made cyclically over a preset time interval (series Ch1,

Ch2, Ar).

For the trigger signal, the multi-function button or the digital input can be used (see chapter 7.7 “Setting special inputs”, PN 53/PN 54)

Before each change, the description of the measuring input is displayed.

Measuring input 1 = Ch1

Measuring input 2 = Ch2

Arithmetic calculation = Ar

PN

11

Function

Switching of measuring inputs

Parameter

0 = Key [▼] [▲] (triggered)

1 = Measuring input 1 (static)

2 = Measuring input 2 (static)

3 = Arithmetic function (static)

4 = Multi-function key (triggered)

5 = Cyclic (5 s)

6 = Cyclic (10 s)

7 = Cyclic (20 s)

28 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

7.2.3 Refresh rate

The refresh rate determines how often the display values are updated. With strongly fluctuating input signals, it is recommended that the refresh rate is adjusted (refresh rate

> 1s).

The refresh rate acts only on the presentation of the display values. Switching outputs and other functions are not affected.

EN

PN

13

Function

Refresh rate

Parameter

0.1 ... 10.0 s (default 1 s)

7.2.4 Measuring time

PN

14

Function

Measuring time

Parameter

0.04 ... 10.0 s (two measuring inputs)

0.02 ... 10.0 s (one measuring input)

7.2.5 Display brightness

PN

19

Function

Display brightness

Parameter

0 ... 9 (0 = bright, 9 = dark)

7.3 Arithmetic function

Calculation type

Addition

Subtraction

Multiplication

Ratio

Percent

Formula

(Measuring input 1 + measuring input 2) ∙ constant

(Measuring input 1 + measuring input 2) ∙ constant

(Measuring input 1 ∙ measuring input 2) ∙ constant

(Measuring input 1 / measuring input 2) ∙ constant

(Measuring input 1 ∙100 ) / measuring input 2

Calculation type

Addition

Subtraction

Multiplication

Ratio

Percent

Example applications

Inflow and outflow quantities, weighing technology

Differential measurement (e.g. differential pressure)

Power and energy measurement

Mixing ratios

Percentage ratios

WIKA operating instructions digital indicator, model DI35-D 29

EN

16

17

18

7. Description of program numbers

PN

15

Function

Calculation type

Constant

Number of decimal places of constants

Number of decimal places of calculation

Parameter

1 = Measuring input 1 ∙ constant

2 = Measuring input 2 ∙ constant

3 = Addition

4 = Subtraction

5 = Multiplication

6 = Ratio

7 = Percent

-9999 ... 99999

00000 ... 0.0000

00000 ... 0.0000

With the calculation of the arithmetic function, all set decimal points are included (PN 3, PN 8, PN 17, PN 18)

7.4 Setting the analogue output (option)

The analogue output gives the measured values of the digital indicator as a standard signal (DC 0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA).

7.4.1 Start and end value

The analogue output can be assigned any measuring input. The output signal is updated simultaneously with the measuring input. The refresh rate is determined by the configured measuring time. The start and end value for the analogue signal can be assigned user-defined measured values.

The start and end value defines at which display value the minimum and maximum output signal will be given. The display value is dependent upon the setting of the input signal ( see chapter 7.1.1 “Input signal”)

PN

20

21

Function

Full scale

Start value

Parameter

-9999 ... 99999

-9999 ... 99999

30 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

7.4.2 Reference value

The reference value is the value which is given via the analogue output.

PN

22

Function

Reference value

Parameter

0 = Analogue output deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

7.4.3 Output signal

PN

23

Function

Output signal

Parameter

0 = DC 0 ... 10 V

1 = 0 ... 20 mA

2 = 4 ... 20 mA

In addition, the output signal must be set via the DIP switch on the rear of the instrument.

DC 0 ... 10 V = Switch set to the right

0/4 ... 20 mA = Switch set to the left

With the desktop case, the output signal is determined via the assignment of plug D (see pin assignment).

7.4.4 Example

A rotational speed of 0 ... 3,000 min-1 should be transmitted to a control room via

4 ... 20 mA. The rotational speed sensor is connected to measuring input 1.

1. Set the end value to 3,000.

2. Set the start value to 0.

3. Set the reference value to 1.

4. Set the output signal to 2.

5. Set the DIP switch.

⇒ Analogue output is set.

EN

WIKA operating instructions digital indicator, model DI35-D 31

7. Description of program numbers

7.5 Setting the serial interface (option)

PN

34

Function

Interface properties

Parameter

0 = Standard mode

1 = Sending mode

EN

Interface properties

Standard mode

(= Configuration mode)

Sending mode

Description

In this mode, the digital indicator can be configured. Responses will only be transmitted on request.

The current measured value can be queried via “A↵”.

Measured values are sent cyclically. The cycle corresponds to the set measuring time.

Cancel sending mode

The sending mode is cancelled on receipt of “> ↵” and the instrument returns to standard mode.

Activate sending mode

Restart the digital indicator or transmit the command “S ↵”.

Protocol structure

Display values are transmitted in ASCII format. Minus signs and decimal points can be displayed directly on a terminal display or processed by a PLC. Leading spaces are disabled with transmission. With an over- or underrange, hyphens are transmitted

“- - - - - ↵”.

Example: “0.00 ↵”; “-9.99 ↵” ; “999.99 ↵”; “-123.45”; “ - - - - - ↵”; “Lbr ↵”

The display values can be processed or stored on a PC via a terminal program.

Settings

Point-to-point connection

Transmission rate 9,600 baud

8 data bits without parity

1 stop bit

32 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

7.6 Setting user authorisations

7.6.1 Authorisation levels

Via the user authorisation, it is possible to limit which settings can be made by the operator. The authorisations can be allocated in different authorisation levels.

Function

Changing the display brightness

Allocating the locking code

Reading the serial number

Changing switch points

Setting the switching output

Setting the interface

Setting the analogue output

Setting measuring inputs

Carrying out a linearisation

Inputting a release code

Changing the authorisation level

PN

59 ... 95

32 ... 34

20 ... 22

0 ... 18

100 ... 170

51

52

Authorisation level

1 2 3 4 5 6 7 8

19

50

200       

61, 71, 81, 91       

-

     

   

   

  

  

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

The authorisation levels can only be changed if the release code corresponds to the locking code (password protection). On delivery, both parameters are set to the value

0000, whereby the programming lockout is deactivated.

-

-

-

-

-

-

-

PN

50

51

52

Function

Locking code

Release code

Authorisation level

Parameter

0000 ... 9999

0000 ... 9999

0 ... 8

7.6.2 Cancelling the password protection

The password protection is cancelled when the release code corresponds to the locking code.

EN

If the locking code is lost, the instrument can be reset by the manufacturer.

WIKA operating instructions digital indicator, model DI35-D 33

7. Description of program numbers

EN

7.7 Setting special functions

7.7.1 Function of the digital input

PN

53

Function

Function of the digital input

Parameter

0 = Deactivated

1 = Switching the measuring input

2 = HOLD

3 = TARE

7.7.2 Function of the multi-function key

PN

54

Function

Function of the multi-function key

Parameter

0 = Deactivated

1 = Switching the measuring input

2 = HOLD

3 = TARE

7.7.3 TARE function

The TARE function sets the display value of the stored measuring input to zero. The difference between zero and the display value is stored as an offset value.

The TARE function overrides a previously programmed offset shift of the measuring inputs (PN 4/9). Should the TARE function be used during a measurement, the offset shift has to be reprogrammed.

The TARE function can be activated through the multi-function key or the digital input

(→ see chapter 7.7 “Setting special functions”). The key must be activated for at least 3 seconds.

The tare operation is represented as follows:

34 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

PN

55

Function

TARE function

Parameter

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Measuring input 1 + 2

7.7.4 HOLD function

The HOLD function freezes the current display value. This is signalled via a flashing display.

The HOLD function can be activated through the multi-function key or the digital input (→ see chapter 7.7 “Setting special functions”).

The HOLD function can be switched statically or triggered.

Method

Static

Triggered

Description

A display value is frozen for the duration of the trigger signal.

The display value is frozen as soon the trigger is activated for a short time. The function is reset when the trigger is activated again.

PN

56

Function

HOLD function

Parameter

0 = Deactivated

1 = Triggered

2 = Static

EN

WIKA operating instructions digital indicator, model DI35-D 35

7. Description of program numbers

EN

7.8 Setting the switching outputs

The switching outputs can be configured independently. Each switching output can be assigned a separate measuring input. The switching outputs react to the measuring input at any time, regardless of which measuring input is shown on the digital display.

7.8.1 Flashing display on reaching the switch points

A switch point being exceeded can be signalled via a simultaneous flashing of the

7-segment display and switch point display.

PN

59

Function

Flashing display

Parameter

0 = not flashing

1 = at switch point 1

2 = at switch point 2

3 = at switch point 3

4 = at switch point 4

5 = at switch point 1 + 2

6 = at switch point 3 + 4

7 = at switch point 1 + 2 + 3 + 4

Reading the switching status

The switching status of the switching outputs can be read from the switch point display.

Switch point display

7.8.2 Reference value

The reference value is the value to which the switching output reacts.

PN

60

70

80

90

Function

Reference value, switching output 1

Reference value, switching output 2

Reference value, switching output 3

Reference value, switching output 4

Parameter

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

36 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

7.8.3 Switch points

PN

61

71

81

91

Function

Switch point, switching output 1

Switch point, switching output 2

Switch point, switching output 3

Switch point, switching output 4

Parameter

-9999 ... 99999

-9999 ... 99999

-9999 ... 99999

-9999 ... 99999

7.8.4 Switch behaviour

84

94

65

93

64

74

75

85

95

82

92

63

73

83

PN

62

72

Function

Hysteresis, switching output 1

Hysteresis, switching output 2

Hysteresis, switching output 3

Hysteresis, switching output 4

Switching function, switching output 1

Switching function, switching output 2

Switching function, switching output 3

Switching function, switching output 4

Switching delay, switching output 1

Switching delay, switching output 2

Switching delay, switching output 3

Switching delay, switching output 4

Delay type, switching output 1

Delay type, switching output 2

Delay type, switching output 3

Delay type, switching output 4

Parameter

1 ... 99999

0 = Normally closed

1 = Normally open

0 ... 10 seconds

0 = none

1 = Switch-on delay

2 = Switch-off delay

3 = Switch-on and switch-off delay

EN

WIKA operating instructions digital indicator, model DI35-D 37

7. Description of program numbers

EN

Normally open

Below the switch point, the switching output is switched off. On reaching the switch point, the switching output is switched on.

The switching output is switched off only when the switch point, less the hysteresis, is reached.

38 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

Normally closed

Below the switch point, the switching output is switched on. On reaching the switch point, the switching output is switched off.

The switching output is switched on only when the switch point, less the hysteresis, is reached.

EN

WIKA operating instructions digital indicator, model DI35-D 39

7. Description of program numbers

EN

Switch-on delay

The switching output is switched on only when the input signal remains above the switch point for at least the set switching delay.

This function prevents an unwanted switching of the switching output as a result of a short-term fluctuation of the input signal.

40 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

Switch-off delay

The switching output is switched off only when the input signal remains under the switch point for at least the set switching delay.

This function prevents an unwanted switching of the switching output as a result of a short-term fluctuation of the input signal.

EN

WIKA operating instructions digital indicator, model DI35-D 41

7. Description of program numbers

EN

7.9 Linearising sensors

Non-linear sensors can be linearised with up to 30 interpolation points per measuring input.

At each interpolation point, the input signal is assigned a new display value manually.

The analogue output is also linearised since it is proportional to the display values.

Each interpolation point must have a higher input signal than the previous. The corresponding display values can be freely assigned.

PN

100

Function

Number of interpolation points, measuring input 1

Parameter

0 ... 30

101 ... 130 Display value for interpolation point, measuring input 1 -9999 ... 99999

140 Number of interpolation points, measuring input 2 0 ... 30

141 ... 170 Display value for interpolation point, measuring input 2 -9999 ... 99999

Procedure

1. Set the number of interpolation points under PN 100/PN 140.

2. Apply the input signal for the first interpolation point, PN 101/PN 141, at the measuring input.

3. Set the desired display value under PN 101/PN 141.

⇒ Input signal is associated with display value.

4. Repeat steps 2 + 3 for all interpolation points.

⇒ Input signal is linearised.

42 WIKA operating instructions digital indicator, model DI35-D

7. Description of program numbers

Example

Linearisation of a pressure sensor for 0 ... 100 mbar with an output signal of 0 ... 20 mA.

Programming with 5 interpolation points.

Non-linear range 0 ... 75 mbar.

Interpolation point

PN 2

PN 101

PN 102

PN 103

PN 104

PN 105

PN 1

Pressure

[mbar]

40

60

75

0

15

30

100

Transmitter output signal [mA]

0.5

3.3

6.2

9.2

11.4

14.7

20

Display value [mbar] before linearisation after linearisation

2.5

0.0

16.5

31.0

46

57

73.5

100.0

15.0

30.0

40.0

60.0

75.0

100.0

For PN 101 this means:

With a pressure of 15 mbar, the transmitter delivers an output signal of 3.3 mA instead of 3.0 mA. Therefore, before correction, the display shows 16.5 mbar. This value is adjusted to 15.0 mbar using the interpolation point.

EN

100

90

80

70

40

30

20

10

60

50

104

105

102

103

101

10 20 30 40 50 60 70 80 90 100 110

WIKA operating instructions digital indicator, model DI35-D 43

7. Description of program numbers / 8. Faults

7.10 Reading the serial number

PN

200

Function

Serial number

Parameter

0 ... 99999

EN

7.11 Restore factory settings

The factory settings can only be restored if the programming lock PN 50 allows access to all PNs or HELP is displayed. All application-specific data will be lost.

1. Switch off the power supply.

2. Press the multi-function key.

3. Apply power supply and hold the multi-function key for 2 s.

⇒ Factory settings are restored.

8. Faults

CAUTION!

Physical injuries and damage to property and the environment

If faults cannot be eliminated by means of the measures listed above, the instrument must be taken out of service immediately.

▶ Ensure that pressure or signal is no longer present and protect against accidental commissioning.

▶ Contact the manufacturer.

▶ If a return is needed, follow the instructions given in chapter 10.2

“Returns”.

Faults

Instrument shows permanent overrange

Causes

One of the measuring inputs has a very high measured value

With a measuring input with a small voltage signal, this is only connected on one side or the input is open

Not all activated interpolation points are parameterised

The arithmetic result gives an overrange

Measures

Check measuring path

Check relevant parameter

44 WIKA operating instructions digital indicator, model DI35-D

8. Faults

Faults

Instrument shows a permanent underrange

Instrument displays “HELP”

Display values are changing in very large jumps

Program numbers are not available

Causes

One of the measuring inputs has a very small measured value

With a measuring input with a small voltage signal, this is only connected on one side or the input is open

Not all activated interpolation points are parameterised

The arithmetic result gives an underrange

Error in the configuration memory

With a division, the measured value of the divisor is very small small

Access through user authorisation denied

Set sensor type is preventing the desired program number from being parameterised

The analogue output is an option. If this is not implemented, then the program numbers are hidden

Instrument displays “Err1”

Digital input does not react

Measures

Check measuring path

Check relevant parameter

Restore factory settings and re-enter the settings

Check measuring path

Contact the manufacturer

Measure input current of digital input. It should lie between 1 ... 3 mA.

EN

WIKA operating instructions digital indicator, model DI35-D 45

8. Faults

EN

Overrange and underrange display

Each over- or underrange of a measuring input relates to a defined display. This definition ensures that the appropriate switch points go to a defined state.

Calculation type

Addition

Subtraction

Multiplication

Division

Percent

Channel 1

Overrange

Underrange

OK or overrange

OK or underrange

Overrange

Overrange

Underrange

OK or overrange

OK or underrange

Overrange

Overrange

Underrange

OK or overrange

OK or underrange

Overrange

Overrange

Underrange

OK

OK

Overrange

Underrange

OK

OK

Channel 2

OK or overrange

OK or underrange

Overrange

Underrange

Underrange

OK or overrange

OK or underrange

Overrange

Underrange

Underrange

OK or overrange

OK or underrange

Overrange

Underrange

Underrange as required as required

Overrange

Underrange as required as required

Overrange

Underrange

Results

Overrange

Underrange

Overrange

Underrange

Overrange

Overrange

Underrange

Overrange

Underrange

Overrange

Overrange

Underrange

Overrange

Underrange

Overrange

Overrange

Underrange

Underrange

Underrange

Overrange

Underrange

Underrange

Underrange

Illustration of overrange Illustration of underrange

46 WIKA operating instructions digital indicator, model DI35-D

9. Maintenance and cleaning

9. Maintenance and cleaning

9.1 Maintenance

This digital indicator is maintenance-free.

Repairs must only be carried out by the manufacturer.

9.2 Cleaning

DANGER!

Danger to life caused by electric current

Upon contact with live parts, there is a direct danger to life.

▶ Only clean the case and contacts when the current is disconnected.

CAUTION!

Unsuitable cleaning agents

Cleaning with unsuitable cleaning agents may damage the instrument and the product label.

▶ Do not use any aggressive cleaning agents.

▶ Do not use any hard or pointed objects.

▶ Do not use any abrasive cloths or sponges.

EN

1. Disconnect the digital indicator from the supply.

2. Wipe the instrument surface using a soft, damp cloth.

WIKA operating instructions digital indicator, model DI35-D 47

10. Dismounting, return and disposal

10. Dismounting, return and disposal

EN

10.1 Dismounting, version for control panel

1. Disconnect the digital indicator from the supply.

2 .

Disconnect the electrical connection.

3 .

Remove the mounting elements.

4. Pull the digital indicator out of the control panel.

10.2 Return

Strictly observe the following when shipping the instrument:

All instruments delivered to WIKA must be free from any kind of hazardous substances

(acids, bases, solutions, etc.) and must therefore be cleaned before being returned.

When returning the instrument, use the original packaging or a suitable transport packaging.

Information on returns can be found under the heading “Service” on our local website.

10.3 Disposal

Incorrect disposal can put the environment at risk.

Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the country-specific waste disposal regulations.

48 WIKA operating instructions digital indicator, model DI35-D

11. Specifications

11. Specifications

Specifications

Digital indicator

Principle

Character size

Indication range

Display rate

Memory

Inputs

Inputs

Digital input

Input signals, version for panel mounting

Input signals, version in desktop case

Input configuration

7-segment LED, red, 5-digit, brightness adjustable in 10 gradations

14 mm

-9999 ... 99999

0.1 ... 10.0 seconds

EEPROM (parameter memory), data preservation > 100 years

2 x input for standard signals

< 2.4 V off, >10 V on, max. DC 30 V, Ri ≈ 5 kΩ

0 ... 20 mA, R i

4 ... 20 mA, R i

DC 0 ... 10 V, R i

≈ 50 Ω

≈ 50 Ω

≈ 150 kΩ

4 ... 20 mA, R i

≈ 50 Ω

Selectable via terminal connections and menu-driven programming

Accuracy

Temperature error

Measuring principle

Resolution

Measuring time

Transmitter power supply

Analogue output (option)

Number and type

Output signal

Error

Internal resistance

See the following tables “Accuracy/measuring errors of the input signals”

50 ppm/K, at ambient temperature T

U

T

U

> 40 °C

< 20 °C or

Sigma/delta

24 bit (with 1 second measuring time)

0.02 ... 10.0 s, with 1-channel measurement

0.04 ... 10.0 s, with 2-channel measurement

DC 24 V, max. 50 mA, galvanically isolated

1 analogue output (galvanically isolated)

4 ... 20 mA (12-bit), load ≤ 500 Ω

0 ... 20 mA (12-bit), load ≤ 500 Ω

DC 0 ... 10 V (12-bit), load ≥ 100 kΩ

0.1 % in the range 20 ... 40 °C

50 ppm/K outside temperature error

100 Ω (with measuring input DC 0 ... 10 V)

EN

WIKA operating instructions digital indicator, model DI35-D 49

11. Specifications

EN

Specifications

Switching output (option)

Number and type

Load capacity

Number of switching operations

2 or 4 switch contacts (relays), freely programmable

AC 250 V, 5 A (resistive load)

DC 30 V, 5 A (resistive load)

0.5 ∙105 at max. contact load

5 ∙ 106 mechanical

Isolation in accordance with DIN EN 50178

Parameters in accordance with DIN EN 60255

Voltage supply

Power supply

Power consumption

Electrical connection

See product label

Power supply galvanically isolated

AC 100 ... 240 V, 50/60 Hz, DC 100 ... 240 V

DC 10...40 V, AC 18 ... 30 V, 50/60 Hz

Overvoltage category II

Max. 15 VA

Removable plug-in terminal

Wire cross-section up to 2.5 mm²

Serial interface (option)

Interface

Protocol

Baud rate

Cable length

See product label

RS-232 (not galvanically isolated)

RS-232 (galvanically isolated)

RS-485 (not galvanically isolated, only for point-to-point connection)

RS-485 (galvanically isolated, only for point-to-point connection)

Manufacturer-specific ASCII

9,600 baud, no parity, 8 data bits, 1 stop bit

RS-232: max. 3 m

RS-485: max. 1,000 m

Case, panel mounting

Material

Ingress protection

Glass-fibre reinforced polycarbonate, black

Front: IP65, rear: IP00 (per IEC 60529)

Weight approx. 350 g

Recommended mounting grid 120 mm horizontal, 96 mm vertical

Mounting Sliding mounting elements, fixed via screws, for wall thicknesses up to 15 mm

50 WIKA operating instructions digital indicator, model DI35-D

11. Specifications

Specifications

Case, desktop case

Material

Ingress protection

Weight

Fuse

Front, rear, side plates: aluminium, black, powder-coated

Cover, base plate: hard paper, black (Pertinax)

IP40 (per IEC 60529) approx. 1.6 kg

Integrated fuse 0.5 A medium-acting (not to be changed by operator)

Operating conditions

Permissible ambient temperatures

Humidity

Requirements for the installation location

Operation: 0 ... 50 °C

Storage: -20 ... +80 °C

0 ... 75 % r. h. annual mean, without condensation

Pollution degree 2

No direct sunlight or proximity to hot objects

No mechanical vibration, mechanical shock (putting it down hard)

No soot, vapour, dust or corrosive gases

This is a class B instrument for emissions and is intended for use in industrial environments. In other environments, e.g. residential or commercial installations, it can interfere with other equipment under certain conditions. In such circumstances the operator is expected to take the appropriate measures.

EN

Accuracy/measuring errors of the input signals

Inputs with factory calibration

Input signals Measuring span

Current signals 0 ... 20 mA

4 ... 20 mA

Measuring error in

% of the measuring span 1)

≤ ±0.02 % ±1 digit

≤ ±0.02 % ±1 digit

Minimum measuring time

1-channel measurement

2-channel measurement

0.02 s

0.02 s

0.04 s

0.04 s

WIKA operating instructions digital indicator, model DI35-D 51

11. Specifications

EN

Input signals Measuring span

Measuring error in

% of the measuring span 1)

-

Minimum measuring time

1-channel measurement

2-channel measurement

Voltage signals DC 0 ... 18 mV

DC 0 ... 35 mV

DC 0 ... 75 mV

DC 0 ... 150 mV

DC 0 ... 300 mV

DC 0 ... 600 mV

≤ ±0.06 % ±1 digit

≤ ±0.06 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.03 % ±1 digit

≤ ±0.03 % ±1 digit

≤ ±0.03 % ±1 digit

DC 0 ... 1,250 mV ≤ ±0.03 % ±1 digit

DC 0 ... 2,500 mV ≤ ±0.03 % ±1 digit

DC 0 ... 5 V ≤ ±0.02 % ±1 digit

DC 0 ... 10 V ≤ ±0.01 % ±1 digit

Thermocouples

Type B, PtRh-PtRh

Type E, NiCr-CuNi

Type J, Fe-CuNi

-100 ... +1,810 °C ≤ ±0.10 % ±1 digit

-260 ... +1,000 °C ≤ ±0.06 % ±1 digit

-210 ... +1,200 °C ≤ ±0.05 % ±1 digit

Type K, NiCr-Ni

Type L, Fe-CuNi

Type N, NiCrSi-NiSI

Type R, PtRh-Pt

Type S, PtRh-Pt

Type T, Cu-CuNi

-250 ... +1,271 °C

-200 ... +900 °C

-250 ... +1,300 °C

0 ... 1,760 °C

0 ... 1,760 °C

-240 ... +400 °C

Resistance thermometer 2)

Pt100 (2-/4-wire) -200 ... +850 °C

≤ ±0.05 % ±1 digit

≤ ±0.06 % ±1 digit

≤ ±0.06 % ±1 digit

≤ ±0.07 % ±1 digit

≤ ±0.06 % ±1 digit

≤ ±0.07 % ±1 digit

≤ ±0.04 % ±1 digit

Pt100 (3-wire)

Pt200 (2-/4-wire)

Pt200 (3-wire)

Pt500 (2-/4-wire)

Pt500 (3-wire)

Pt1000 (2-/4-wire)

Pt1000 (3-wire)

-200 ... +850 °C

-200 ... +850 °C

-200 ... +850 °C

-200 ... +850 °C

-200 ... +850 °C

-200 ... +850 °C

-200 ... +850 °C

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0.02 s

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0.04 s

1) The indication of the measuring error applies to ambient temperatures of 20 ... 40 °C and the measuring time of 1 s.

2) The indications for Pt100 3-/4-wire apply at a max. lead resistance of 10 Ω.

52 WIKA operating instructions digital indicator, model DI35-D

11. Specifications

Inputs for sensor calibration

Input signals Measuring span Measuring error in

% of the measuring span 1)

-

-

-

-

-

-

0.02 s

-

-

-

-

-

-

0.02 s

0.02 s

-

-

Minimum measuring time

1-channel measurement

2-channel measurement

-

Current signals

Voltage signals

Resistance (2-,

3-, or 4-wire)

0 ... 2 mA

0 ... 5 mA

0 ... 20 mA

4 ... 20 mA

DC -18 ... +18 mV

DC -35 ... +35 mV

DC -75 ... +75 mV

DC -150 ... +150 mV

DC -300 ... +300 mV

DC -500 ... +600 mV

≤ ±0.02 % ±1 digit

≤ ±0.02 % ±1 digit

≤ ±0.02 % ±1 digit

≤ ±0.02 % ±1 digit

≤ ±0.06 % ±1 digit

≤ ±0.06 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.03 % ±1 digit

≤ ±0.03 % ±1 digit

≤ ±0.03 % ±1 digit

DC -500 ... +1,250 mV ≤ ±0.03 % ±1 digit

DC -500 ... +2,500 mV ≤ ±0.03 % ±1 digit

DC -1 ... +5 V ≤ ±0.02 % ±1 digit

DC -1 ... +10 V

0 Ω ... 100 Ω

0 Ω ... 1 kΩ

0 Ω ... 10 kΩ

≤ ±0.01 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

≤ ±0.04 % ±1 digit

1) The indication of the measuring error applies to ambient temperatures of 20 ... 40 °C and the measuring time of 1 s.

-

-

-

-

-

-

0.04 s

-

-

-

-

-

-

0.04 s

0.04 s

EN

WIKA operating instructions digital indicator, model DI35-D 53

11. Specifications

Dimensions in mm

Panel mounting

EN

120

,0 including fixing attachments ließlic h Befe stigun g

3,0

DI35

Sealing ng

96,0

Inser mm e eins chli eßli ch A

139

,0 nsc hlus skle

Einb auti efe tion depth including connection terminal

Desktop case

(267 incl.

(267

displa

mm

inc l. An zeig

250 e un d A

250

,0 m nsc m sste cke r oh ne G ege nste cke r) y and coupler connectors without mating connector)

54

170

mm

WIKA operating instructions digital indicator, model DI35-D

Appendix 1: Overview of program numbers

Appendix 1: Overview of program numbers

Parameter PN Function

Measuring input 1

0 Measuring input

Factory setting

0

1

2

3

4

Full scale

Start value

Decimal places

Offset adjustment

Measuring input 2

5 Measuring input

6

7

8

9

Full scale

Start value

Decimal places

Offset adjustment

0 = N/A

Factory calibration

1 = DC 0 ... 10 V

2 = 0 ... 20 mA

3 = 4 ... 20 mA

Sensor calibration

4 = DC 0 ... 10 V

5 = 0 ... 20 mA

6 = 4 ... 20 mA

-9999 ... 99999

-9999 ... 99999

00000 ... 0.0000

-9999 ... 99999

0 = N/A

Factory calibration

1 = DC 0 ... 10 V

2 = 0 ... 20 mA

3 = 4 ... 20 mA

Sensor calibration

4 = DC 0 ... 10 V

5 = 0 ... 20 mA

6 = 4 ... 20 mA

-9999 ... 99999

-9999 ... 99999

00000 ... 0.0000

-9999 ... 99999

10000

0

00000

0

0

10000

0

00000

0

2

2

2

2

2

2

2

2

2

Authorisation level

2

EN

WIKA operating instructions digital indicator, model DI35-D 55

Appendix 1: Overview of program numbers

PN Function

General settings

10 Default display

EN

11 Switching of measuring inputs

13 Refresh rate

14 Measuring time

Parameter Factory setting

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

0 = Key [▼] [▲] (triggered)

1 = Measuring input 1

(static)

2 = Measuring input 2

(static)

3 = Arithmetic function

(static)

4 = Multi-function key

(triggered)

5 = Cyclic (5 s)

6 = Cyclic (10 s)

7 = Cyclic (20 s)

0.1 ... 10.0 s

0.04 ... 10.0 s (two measuring inputs)

0.02 ... 10.0 s (one measuring input)

0 ... 9

3

0

1.0

0.2

3 19 Display brightness

Arithmetic function

15 Calculation type 3

16 Constant

17 Number of decimal places of constants

18 Number of decimal places of calculation

1 = Measuring input 1 ∙ constant

2 = Measuring input 2 ∙ constant

3 = Addition

4 = Subtraction

5 = Multiplication

6 = Ratio

7 = Percent

-9999 ... 99999

00000 ... 0.0000

00000 ... 0.0000

1

00000

00000

2

2

2

2

2

2

8

2

Authorisation level

2

56 WIKA operating instructions digital indicator, model DI35-D

Appendix 1: Overview of program numbers

PN Function

Analogue output (option)

20 Full scale

21 Start value

22 Reference value

23 Output signal

Interface

34 Interface properties

User authorisation

50 Locking code

51 Release code

52 Authorisation level

Special functions

53 Function of the digital input

54 Function of the multifunction key

55 TARE function

56 HOLD function

Parameter

-9999 ... 99999

-9999 ... 99999

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

0 = DC 0 ... 10 V

1 = 0 ... 20 mA

2 = 4 ... 20 mA

2

0 = Standard mode

1 = Transmission mode

0000 ... 9999

0000 ... 9999

0 ... 8

0

0 = Deactivated

1 = Switching the measuring input

2 = HOLD

3 = TARE

0 = Deactivated

1 = Switching the measuring input

2 = HOLD

3 = TARE

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Measuring input 1 + 2

0 = Deactivated

1 = Triggered

2 = Static

0

0

0

0

0000

0000

8

Factory setting

10000

0

3

8

0

0

2

2

2

2

Authorisation level

4

4

2

2

2

EN

WIKA operating instructions digital indicator, model DI35-D 57

EN

Appendix 1: Overview of program numbers

PN Function

59 Flashing display

Switching output 1

60 Reference value

61 Switch point

62 Hysteresis

63 Switching function

64 Switching delay

65 Delay type

Switching output 2

70 Reference value

71 Switch point

72 Hysteresis

73 Switching function

74 Switching delay

75 Delay type

Parameter

0 = Deactivated

1 = at switch point 1

2 = at switch point 2

3 = at switch point 3

4 = at switch point 4

5 = at switch point 1 + 2

6 = at switch point 3 + 4

7 = at switch point 1 + 2 +

3 + 4

Factory setting

0

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

-9999 ... 99999

1 ... 99999

0 = Normally closed

1 = Normally open

0 ... 10.0 seconds

0 = none

1 = Switch-on delay

2 = Switch-off delay

3 = Switch-on and switchoff delay

1

1000

1

1

0.0

1

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

-9999 ... 99999

1 ... 99999

0 = Normally closed

1 = Normally open

0 ... 10.0 seconds

0 = none

1 = Switch-on delay

2 = Switch-off delay

3 = Switch-on and switchoff delay

1

1000

1

1

0.0

1

6

6

6

6

6

Authorisation level

6

6

6

6

6

6

6

6

58 WIKA operating instructions digital indicator, model DI35-D

Appendix 1: Overview of program numbers

PN Function

Switching output 3

80 Reference value

81 Switch point

82 Hysteresis

83 Switching function

84 Switching delay

85 Delay type

Switching output 4

90 Reference value

91 Switch point

92 Hysteresis

93 Switching function

94 Switching delay

95 Delay type

Parameter Factory setting

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

-9999 ... 99999

1 ... 99999

0 = Normally closed

1 = Normally open

0 ... 10.0 seconds

0 = none

1 = Switch-on delay

2 = Switch-off delay

3 = Switch-on and switchoff delay

1

1000

1

1

0.0

1

0 = Deactivated

1 = Measuring input 1

2 = Measuring input 2

3 = Arithmetic function

-9999 ... 99999

1 ... 99999

0 = Normally closed

1 = Normally open

0 ... 10.0 seconds

0 = none

1 = Switch-on delay

2 = Switch-off delay

3 = Switch-on and switchoff delay

1

1000

1

1

0.0

1

6

6

6

6

6

6

6

6

6

6

6

Authorisation level

6

EN

WIKA operating instructions digital indicator, model DI35-D 59

Appendix 1: Overview of program numbers

PN Function Parameter

EN

Linearisation

100 Number of interpolation points

Measuring input 1

101

...

130

Display value for interpolation point

Measuring input 1

140 Number of interpolation points

Measuring input 2

141

...

170

Display value for interpolation point

Measuring input 2

Serial number

200 Reading the serial number

0 ... 30

-9999 ... 99999

0 ... 30

-9999 ... 99999

0 ... 99999

Factory setting

0

Authorisation level

2

0

2

2

2

8

60 WIKA operating instructions digital indicator, model DI35-D

WIKA operating instructions digital indicator, model DI35-D 61

EN

EN

62 WIKA operating instructions digital indicator, model DI35-D

WIKA operating instructions digital indicator, model DI35-D 63

EN

64

WIKA Alexander Wiegand SE & Co. KG

Alexander-Wiegand-Straße 30

63911 Klingenberg • Germany

Tel. +49 9372 132-0

Fax +49 9372 132-406 [email protected]

www.wika.de

WIKA operating instructions digital indicator, model DI35-D