Residential & Light Commercial HVAC
Ultra Quiet Series
Electric Air Handler
11⁄2 thru 5 Tons
208/230 Volt, 1-Phase, 60 Hz
The Fedders multi-position air handlers, when
matched with our air conditioners or heat pumps,
offer a complete line of quiet, efficient split
systems for today’s heating and cooling equipment.
Easy To Install And Service
Breaker accessible from front of unit when heater applied
Performance
External Access to heater circuit breakers pull / disconnects
Dual rated 208/230 volt operation
Provisions for field installed electrical connections from
either side of air handler cabinet
1 1⁄2 to 5 tons
External sweat refrigerant connections
Built in filter rack
TXV – factory installed standard, which precisely controls
refrigerant distribution for improved comfort and cost savings
Standard Features
Pressure taps on suction and liquid line
Corrosion resistant condensate drain pan. Primary and
secondary drain
Multiposition installation, upflow or horizontal left standard,
horizontal right and downflow with minor modifications
Optional Features
3-speed, permanently-lubricated PSC direct drive blower
motor is resilient mounted for ultra quiet, vibration-free
operation and flexible installation
Field installed heater packages from 5 kW – 20 kW
Foil faced insulation reduces noise and bacterial growth and
features an easy to clean surface area
5-year limited parts warranty
All indoor coils have copper tubing and aluminum fins
Time Delay relay comes standard and allows for retro-fit installations
3/4" primary and secondary drains on all models
Warranty
Rated in Accordance with ARI Standard 210/240.
Certification Applies Only When Used with
Proper Components as Listed with ARI.
Additional rating information
can be found at www.aridirectory.org
MODEL
TONS
REFRIGERANT
AIR FLOW
RANGE
(CFM)
DIMENSIONS
H x W x D (in)
RECOMMENDED
FILTER SIZE
H x W x D (in)
SHIP/
OPERATIONS
WEIGHT (lbs)
AFPB24A1
1.5 - 2
R-22
625 – 900
43 3/8 x 18 x 22
16 x 20 x 1
115 / 109
AFPB24B1
1.5 - 2
R-22
615 – 880
43 3/8 x 18 x 22
16 x 20 x 1
120 / 113
AFPB36A1
2.5 - 3
R-22
950 – 1,260
43 3/8 x 18 x 22
16 x 20 x 1
120 / 113
AFPC48A1
3.5 - 4
R-22
1,190 – 1,590
48 3/8 x 22 x 26
20 x 25 x 1
161 / 152
AFPC48B1
4
R-22
1,195 – 1,590
48 3/8 x 22 x 26
20 x 25 x 1
167 / 160
AFPC60A1
5
R-22
1,340 – 1,895
48 3/8 x 22 x 26
20 x 25 x 1
167 / 160
AZFPC60B1
5
R-410A
1,340 – 1,895
48 3/8 x 22 x 26
20 x 25 x 1
167 / 160
Product Specifications
PHYSICAL DATA
MODEL NUMBER
AFPB24A1
AFPB24B1
AFPB36A1
AFPC48A1
AFPC48B1
AFPC60A1
AZFPC60B1
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
MINIMUM CIRCUIT AMPACITY MCA (AMPS)
15
15
15
15
15
15
15
MAXIMUM OVERCURRENT PROTECTIVE DEVICE - MOCP (AMPS)
15
15
15
15
15
15
15
ELECTRIC DATA (208/230 VOLT, SINGLE PHASE, 60 Hz)
VOLTAGE
BLOWER
FAN MOTOR TYPE
PSC
HP
BLOWER DIMENSIONS
1/6
1/6
1/3
1/2
1/2
3/4
3/4
9x7
9x7
9 x 10
9x8
9x8
10 x 9
10 x 9
5.8
5.8
5.8
COIL DATA
TYPE
A-COIL
COIL FACE AREA (ft 2)
4
4
4
O.D.
ROWS / FPI
5.8
3/8"
2 - 14
3 - 14
3 - 14
3 - 12
4 - 12
3 - 12
4 - 12
LIQUID LINE CONNECTION SIZE (IN. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
SUCTION LINE CONNECTION SIZE (IN. OD)
3/4
7/8
7/8
7/8
7/8
7/8
7/8
16 x 20 x 1
16 x 20 x 1
16 x 20 x 1
20 x 25 x 1
20 x 25 x 1
20 x 25 x 1
20 x 25 x 1
REFRIGERANT LINE CONNECTION
FILTER DATA
RECOMMENDED FILTER SIZE (H X W X D) (in)
(FILTER NOT SUPPLIED)
Clearance to Combustible Material
Clearances from the air handler to the combustibles are zero inches from all sides, top, and bottom; one inch from discharge
air plenum; and the duct within 36 inches of the plenum.
2
Specifications subject to change without notice.
Product Specifications
AIRFLOW PERFORMANCE
MODEL
NUMBER
AFPB24A1
AFPB24B1
AFPB36A1
AFPC48A1
AFPC48B1
AFPC60A1
AZFPC60B1
MEASURED STATIC PRESSURE INLET TO OUTLET
(INCHES WATER COLUMN)
BLOWER
SPEED
0.20
0.30
0.40
0.50
0.60
HIGH
925
900
850
795
690
MEDIUM
800
760
745
670
N/A
LOW
655
625
600
N/A
N/A
HIGH
905
880
830
780
680
MEDIUM
785
735
730
655
N/A
LOW
645
615
590
N/A
N/A
HIGH
1440
1350
1260
1180
1040
MEDIUM
1300
1220
1050
940
860
LOW
1160
1070
950
880
780
HIGH
1680
1640
1590
1520
1430
MEDIUM
1440
1410
1380
1340
1250
LOW
1240
1220
1190
1150
1100
HIGH
2230
2105
1990
1895
1725
MEDIUM
1950
1930
1840
1770
1590
LOW
1360
1360
1350
1340
1080
Specifications applicable to upflow and horizontal applications.
Air flow shown at the following conditions:
- No heat elements in Air Handler. Decrease CFM 2% for 5 kW, 7.5 kW or 10 kW heat kits. Decrease CFM 1% for 15 kW or 20 kW heat kits.
- 60 Hertz – 230 volts. Decrease CFM 6% for 208 volt operations.
- Dry coil airflow shown.
3
Specifications subject to change without notice.
Accessories
ELECTRIC HEATER KITS
PART NUMBER
DESCRIPTION
USE WITH MODEL SIZE
EEC05N1
5 KW, SINGLE PHASE, WITHOUT CIRCUIT BREAKER
ALL
EEC05B1
5 KW, SINGLE PHASE, WITH CIRCUIT BREAKER
ALL
EEC07N1
7.5 KW, SINGLE PHASE, WITHOUT CIRCUIT BREAKER
ALL
EEC07B1
7.5 KW, SINGLE PHASE, WITH CIRCUIT BREAKER
ALL
EEC10N1
10 KW, SINGLE PHASE, WITHOUT CIRCUIT BREAKER
ALL
EEC10B1
10 KW, SINGLE PHASE, WITH CIRCUIT BREAKER
ALL
EEC15B1
15 KW, SINGLE PHASE, WITH CIRCUIT BREAKER
AFPB36A1, AFPC48A1, AFPC48B1,
AFPB60A1, AZFPB60B1
EEC20B1
20 KW, SINGLE PHASE, WITH CIRCUIT BREAKER
AFPB36A1, AFPC48A1, AFPC48B1,
AFPB60A1, AZFPB60B1
ELECTRIC HEAT - ELECTRICAL DATA
SINGLE CIRCUIT SUPPLY
kW
240 Phase
VAC
No. of
Supply
Circuits
MBTUH
208/240
Heat
Load
Amps
Min.
Max.
Wire À Fuse Á
Ampacity Size
Wire Size Â
Ground Size Á
DUAL CIRCUIT SUPPLY
Min. Wire Ampacity À Max. Fuse Size Á
AWG
MM2
AWG
MM2
Ckt 1
Ckt 2
Ckt 1
Ckt 2
Wire Size Â
Ckt 1
Ckt 2
Ground Size Â
Ckt 1
Ckt 2
AWG / MM2 AWG / MM2 AWG / MM2 AWG / MM2
0
1
1
-
-
5.0
15
14
2.1
14
2.1
-
-
-
-
-
-
-
-
5*
1
1
14.8 / 17.1
20.9
30
30
10
5.3
10
5.3
-
-
-
-
-
-
-
-
7.5*
1
1
22.1 / 25.6
31.3
43
50
8
8.4
10
5.3
-
-
-
-
-
-
-
-
10*
1
1
29.5 / 34.1
41.7
57
60
6
13.3
10
5.3
-
-
-
-
-
-
-
-
15*
1
1 or 2
44.3 / 51.2
62.5
83
90
4
21.2
8
8.4
57
26
60
30
6 / 13.3 10 / 5.3 10 / 5.3 10 / 5.3
20*
1
1 or 2
59.0 / 68.2
83.4
109
110
2
33.6
6
13.3
57
53
60
60
6 / 13.3 10 / 13.3 10 / 5.3 10 / 5.3
NOTES:
*kW does not include motor watts.
À Ampacities and over current protection based on largest air handler motor load. Refer to specific name plate for exact ampacity
and overcurrent protection size.
Minimum wire ampacity values are used for sizing field power conductors. Refer to the National Electrical Code (latest version), Article 310,
for sizing conductors. NOTE: when more than three current-carrying conductors are in the same conduit, the conductor's ampacity must be derated.
Á Maximum size fuse or HACR-type circuit breaker for field wiring protection.
 Wire size based on 75°C copper wire with no more than three current-carrying conductors in the same conduit.
All wiring must conform to the National Electrical Code and all local codes.
4
Specifications subject to change without notice.
DIMENSIONS
A
I
H
F
INLET WIDTH
ACCESS COVER
TO TXV
B
D
E
G PTH
DE
ET
L
IN
C
LOW VOLT
CONNECTIONS
LINE
VOLTAGE
KNOCKOUTS
Product Specifications
Specifications subject to change without notice.
5
Electric Air Handler
Residential & Light Commercial Air Handler
Model Number Identification
R-22 Models
A F P B 24 A 1 * A
Product Type
A = Air Handler
Brand
Motor
Electrical Designation
P = PSC
1 = 208 / 230 Volts, 1 Phase, 60 Hz
2 = 220 Volts, 1 Phase, 50 Hz
3 = 208 / 230 Volts, 3 Phase, 60 Hz
4 = 460 Volts, 3 Phase, 60 Hz
5 = 230 Volts, 3 Phase, 50 Hz
6 = 380 Volts, 3 Phase, 50 Hz
Chassis Size
B = 43 3/8"H x 18"W x 22"D
C = 48 3/8"H x 22"W x 26"D
Nominal BTUH
24 = 18,000/24,000 BTU/H (5.28 kW) / (7.03 kW)
36 = 30,000/36,000 BTU/H (8.79 kW) / (10.55 kW)
42 = 42,000 BTU/H (12.31 kW)
48 = 48,000 BTU/H (14.07 kW)
60 = 60,000 BTU/H (17.58 kW)
Design Series
A = A Series
R-410A Models
A Z F P C 60 B 1 * A
Product Type
Electrical Designation
A = Air Handler
1 = 208 / 230 Volts, 1 Phase, 60 Hz
2 = 220 Volts, 1 Phase, 50 Hz
3 = 208 / 230 Volts, 3 Phase, 60 Hz
4 = 460 Volts, 3 Phase, 60 Hz
5 = 230 Volts, 3 Phase, 50 Hz
6 = 380 Volts, 3 Phase, 50 Hz
410A Refrigerant
Brand
Motor
Design Series
P = PSC
A = A Series
Nominal BTUH
Chassis Size
24 = 18,000/24,000 BTU/H (5.28 kW) / (7.03 kW)
36 = 30,000/36,000 BTU/H (8.79 kW) / (10.55 kW)
42 = 42,000 BTU/H (12.31 kW)
48 = 48,000 BTU/H (14.07 kW)
60 = 60,000 BTU/H (17.58 kW)
B = 43 3/8"H x 18"W x 22"D
C = 48 3/8"H x 22"W x 26"D
Fedders Corporation
505 Martinsville Rd.
Liberty Corner, NJ 07938 USA
(908) 604-8686
Form No. F-13AH
All product specifications reflect available information at the printing of this brochure.
Fedders reserves the right to revise or modify products and/or specifications without notice.
Copyright ©2007 Fedders North America, Inc. Fedders is a registered trademark of Fedders North America, Inc.
FD-015-0407-k
6