Omron Computer Hardware CQM1H-SCB41 User manual
Below you will find brief information for SYSMAC CQM1H CQM1H-SCB41. The Serial Communications Board expands the connectivity of your CQM1H-series PC with two serial ports (RS-232C and RS-422A/485). It supports various communication modes, including Host Link, protocol macros for custom device integration, no-protocol communication for simple data exchange, PC 1:1 data links, and NT Link modes for Programmable Terminals. This manual provides instructions on installation.
Advertisement
Advertisement
Cat.No. W365–E1–1 SYSMAC CQM1H Series CQM1H-SCB41 Serial Communications Board OPERATION MANUAL SYSMAC CQM1H Series CQM1H-SCB41 Serial Communications Board Operation Manual Produced September 1999 Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property. DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage. ! OMRON Product References All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product. The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense. The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else. Visual Aids The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc. OMRON, 1999 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication. v About this Manual: This manual describes the installation and operation of the SYSMAC CQM1H-series CQM1H-SCB41 Serial Communications Board and includes the sections described below. The Serial Communications Board is classified as an Inner Board. Read this manual and all related manuals listed in the following table carefully and be sure you understand the information provided before attempting to install and operate a Serial Communications Board. Name Cat. No. Contents SYSMAC CQM1H-series CQM1H-SCB41 Serial Communications Board Operation Manual W365-E1-1 Describes the use of the Serial Communications Board to perform serial communications with external devices, including hardware and the usage of standard system protocols for OMRON products. Host Link communications commands are described in the SYSMAC CQM1H-series Programmable Controllers Programming Manual (W364). Creating protocol macros is described in the CX-Protocol Operation Manual (W344). Describes the installation and operation of the CQM1H-series PCs. SYSMAC CQM1H-series Programmable Controllers Operation Manual W363-E1-1 SYSMAC CQM1H-series Programmable Controllers Programming Manual W364-E1-1 Describes the ladder diagram programming instructions supported by CQM1H-series PCs, Host Link commands, and other programming information. SYSMAC WS02-PSTC1-E CX-Protocol Operation Manual W344-E1-1 Describes the use of the CX-Protocol to create protocol macros as communications sequences to communicate with external devices. Section 1 introduces the hardware and software functions of the Serial Communications Board, including the serial communications modes, system configurations, and specifications. Section 2 describes the components of the Serial Communications Board, how to connect it in the CPU Unit, and how to connect it to external devices. Section 3 describes the settings, control bits, flags, and status information available in the CPU Unit for use with the Serial Communications Board. Section 4 describes the procedure and other information required to use Host Link communications. Section 5 describes the procedure and other information required to use protocol macros. Section 6 provides information required to use no-protocol communications on a Serial Communications Board port. Section 7 provides information required to create 1:1 data links through a Serial Communications Board port. Section 8 describes the procedure and other information required to use 1:N-mode and 1:1-mode NT Links to Programmable Terminals (PTs). Section 9 describes the troubleshooting and maintenance procedures for the Serial Communications Boards. Appendix A to Appendix N provide the specifications of the standard system protocols. ! WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given. vii TABLE OF CONTENTS PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xiii xiii xv SECTION 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1-1 1-2 1-3 1-4 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protocol Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 4 8 8 SECTION 2 Board Components and Installation . . . . . . . . . . . . . . . . . 9 2-1 2-2 2-3 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 14 17 SECTION 3 Default Settings and Related Bits/Flags . . . . . . . . . . . . . . 27 3-1 3-2 3-3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 28 30 SECTION 4 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . 33 4-1 4-2 4-3 4-4 4-5 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changes from Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 36 39 45 53 SECTION 5 Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 5-1 5-2 5-3 5-4 5-5 5-6 5-7 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Restrictions in Using the CX-Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protocol Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 65 66 70 76 80 85 SECTION 6 No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . 97 6-1 6-2 6-3 6-4 viii Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 100 101 102 TABLE OF CONTENTS SECTION 7 Communications for 1:1 Data Links . . . . . . . . . . . . . . . . 7-1 7-2 7-3 7-4 107 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using 1:1 Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 109 110 111 SECTION 8 NT Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . 113 8-1 8-2 8-3 Overview of NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 116 117 SECTION 9 Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . 119 9-1 9-2 9-3 9-4 Front-panel Indicator Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cleaning and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 121 130 132 Appendices A Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B CompoWay/F Master Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C E5jK Digital Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D E5jK Digital Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E E5ZE Temperature Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F E5ZE Temperature Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G E5jJ Temperature Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H ES100j Digital Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I K3Tj Intelligent Signal Processor Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J V500/V520 Bar Code Reader Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K 3Z4L Laser Micrometer Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L Visual Inspection System Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M V600/V620 ID Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N Hayes Modem AT Command Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 137 153 171 187 209 229 243 283 305 317 349 367 403 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411 419 ix PRECAUTIONS This section provides general precautions for using the Serial Communications Boards. The information contained in this section is important for the safe and reliable application of the Serial Communications Boards and the PC in general. You must read this section and understand the information contained before attempting to set up or operate a PC system containing a Serial Communications Board. 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Applicable Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1-1 Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1-2 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xiii xiii xv xv xv xv xi Conformance to EC Directives 1 3 Intended Audience This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent). • Personnel in charge of installing FA systems. • Personnel in charge of designing FA systems. • Personnel in charge of managing FA systems and facilities. 2 General Precautions The user must operate the product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative. Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms. This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation. ! WARNING It is extremely important that a Serial Communications Board and all related units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a Serial Communications Board to the above mentioned applications. 3 Safety Precautions ! WARNING Never attempt to disassemble any Units while power is being supplied. Doing so may result in electric shock. ! WARNING The CPU Unit refreshes I/O even when the program is stopped (i.e., even in PROGRAM mode). Confirm safety thoroughly in advance before changing the status of any part of memory allocated to I/O Units, Inner Boards, or Dedicated I/O Units. Any changes to the data allocated to any Unit may result in unexpected operation of the loads connected to the Unit. Any of the following operation may result in changes to memory status. • Transferring I/O memory data to the CPU Unit from a Programming Device. • Changing present values in memory from a Programming Device. • Force-setting/-resetting bits from a Programming Device. • Transferring I/O memory files from a Memory Card or EM file memory to the CPU Unit. • Transferring I/O memory from a host computer or from another PC on a network. ! WARNING Never touch any of the terminals while power is being supplied. Doing so may result in electric shock. ! Caution xii Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, input signals may not be read properly. Conformance to EC Directives 4 5 Operating Environment Precautions ! Caution Do not operate the control system in the following locations: • Locations subject to direct sunlight. • Locations subject to temperatures or humidity outside the range specified in the specifications. • Locations subject to condensation as the result of severe changes in temperature. • Locations subject to corrosive or flammable gases. • Locations subject to dust (especially iron dust) or salts. • Locations subject to exposure to water, oil, or chemicals. • Locations subject to shock or vibration. ! Caution Take appropriate and sufficient countermeasures when installing systems in the following locations: • Locations subject to static electricity or other forms of noise. • Locations subject to strong electromagnetic fields. • Locations subject to possible exposure to radioactivity. • Locations close to power supplies. ! Caution 5 The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system. Application Precautions Observe the following precautions when using the PC. ! WARNING Failure to abide by the following precautions could lead to serious or possibly fatal injury. Always heed these precautions. • Always ground the system to 100 Ω or less when installing the system to protect against electrical shock. • Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock. • Assembling the Units or mounting the Serial Communications Board. • Setting DIP switches or rotary switches. • Connecting or wiring the cables. • Connecting or disconnecting the connectors. ! Caution Failure to abide by the following precautions could lead to faulty operation or the PC or the system or could damage the PC or PC Units. Always heed these precautions. • Do not turn OFF the power supply while transferring protocol macro data. • Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes. xiii 5 Conformance to EC Directives • Always discharge static electricity by touching a grounded metal part before mounting the Serial Communications Board. • Always discharge static electricity by touching a grounded metal part before connecting cable connectors to RS-232C or RS-422A/485 port of the Serial Communications Board. • Be sure that the connectors, terminal blocks, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction. • Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation. • Changing the operating mode of the PC. • Force-setting/force-resetting any bit in memory. • Changing the present value of any word or any set value in memory. • Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction. • Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit. • Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction. • Confirm polarities before connecting RS-422A/485 cables. Some devices require that SDA/B and RDA/B or signal polarities be reversed. • Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning. • Check the user programming (ladder program, protocol macro data, etc.) for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation. • Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation. • Circuit boards have sharp or pointed edges, such as those on the leads of electrical parts. Do not touch the back of printed boards or mounted sections with your bare hands. • Connect or set terminating resistance correctly when using RS-422A/485 cables. • During transportation and storage, cover the circuit boards with conductive materials to prevent them from being damaged by static electricity caused by LSIs or ICs and keep them within the specified storage temperature. • Refer to Section 2 Board Components and Installation and correctly wire and install the Units. • Do not attempt to take any Units apart, to repair any Units, or to modify any Units in any way. • Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning. xiv 6 Conformance to EC Directives 6 Conformance to EC Directives 6-1 Applicable Directives • EMC Directives • Low Voltage Directive 6-1-1 Concepts EMC Directives OMRON devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or machines. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer. EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel in which the OMRON devices are installed. The customer must, therefore, perform final checks to confirm that devices and the overall machine conform to EMC standards. Note Applicable EMC (Electromagnetic Compatibility) standards are as follows: EMS (Electromagnetic Susceptibility): EN61131-2 EMI (Electromagnetic Interference): EN50081-2 (Radiated emission: 10-m regulations) Low Voltage Directive Always ensure that devices operating at voltages of 50 to 1,000 VAC or 75 to 1,500 VDC meet the required safety standards for the PC (EN61131-2). 6-1-2 Conformance to EC Directives The CQM1H-series PCs comply with EC Directives. To ensure that the machine or device in which a CQM1H-series PC is used complies with EC directives, the PC must be installed as follows: 1, 2, 3... 1. The PC must be installed within a control panel. 2. Reinforced insulation or double insulation must be used for the DC power supplies used for the I/O power supplies. 3. PCs complying with EC Directives also conform to the Common Emission Standard (EN50081-2). When a PC is built into a machine, however, noise can be generated by switching devices using relay outputs and cause the overall machine to fail to meet the Standards. If this occurs, surge killers must be connected or other measures taken external to the PC. The following methods represent typical methods for reducing noise, and may not be sufficient in all cases. Required countermeasures will vary depending on the devices connected to the control panel, wiring, the configuration of the system, and other conditions. 6-1-3 EMI Measures The CQM1H-series PCs conform to the Common Emission Standards (EN50081-2) of the EMC Directives. However, the noise generated from Serial Communications Board communications cables may not satisfy these standards. In such a case, commercially available ferrite cores must be placed on the communications cable or other appropriate countermeasures must be provided external to the PC. xv 6 Conformance to EC Directives Recommended Ferrite Cores The following ferrite core (data line noise filter) is recommended: 0443-164151 by Fair-Rite Products Corp. Low impedance, 25 MHz: 90 Ω, 100 MHz: 160 Ω Recommended Mounting Method Mount the core on one turn of the communications cable, as shown in the following illustration. Mount the cores as closely to the end of the communications cable as possible, as shown in the following illustration. Serial Communications Board xvi SECTION 1 Introduction This section introduces the hardware and software functions of the Serial Communications Board, including the serial communications modes, system configurations, and specifications. 1-1 1-2 1-3 1-4 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-1 Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-2 Serial Communications Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-4 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-5 Mounting Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protocol Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-1 Host Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-2 Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-3 No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-4 PC 1:1 Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-5 NT Links –– 1:N Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-6 NT Links –– 1:1 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-1 Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-2 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 2 2 3 4 4 5 5 6 6 7 7 8 8 8 8 1 Section Basic Operating Procedure 1-1 1-1 Overview 1-1-1 Model Number Name Model Serial Communications Board Specifications CQM1H-SCB41 One RS-232 port One RS-422A/485 port 1-1-2 Serial Communications Boards The Serial Communications Board is an Inner Board for the CQM1H-series PCs. One Board can be installed in Inner Board slot 1 of a CQM1H-series CPU Unit. The Board cannot be installed in slot 2. The Board provides two serial communications ports for connecting host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Consoles). This makes it possible to easily increase the number of serial communications ports for a CQM1Hseries PC. Port 1: RS-232C Port 2: RS-422A/485 1-1-3 Features The Serial Communications Board is an option that can be mounted in the CPU Unit to increase the number of serial ports without using an I/O slot. It supports protocol macros (which are not supported by the ports built into the CPU Units), allowing easy connection to general-purpose devices that have a serial port. Inside controlled machine Serial Communications Board RS-232C RS-422A/485 Temperature controller or other device OR Bar code reader Dedicated controller or other device or other device External device with RS-232C or RS-422A/485 port Both RS-232C and RS-422A/485 ports are provided. The RS-422A/485 port enables 1:N connections to general-purpose external devices without going through Converting Link Adapters. The 1:N connections can be used with protocol macros or 1:N-mode NT Links. 2 Section Protocol Overview 1-1 1-1-4 System Configuration The following serial communications modes are supported by the Serial Communications Board: Host Link (SYSMAC WAY), protocol macro, no-protocol, 1:1 Data Links, 1:N-mode NT Link, and 1:1-mode NT Link modes. The devices shown in the following diagram can be connected. Note The 1:1-mode NT Link and 1:N-mode NT Link communications modes use different protocols that are not compatible with each other. General-purpose external device Protocol macros Programmable Terminal (PT) NT Link C-series PC Programming Device (excluding Programming Console) Host computer 1:1 Data Link Host Link Host Link No-protocol RS-232C CQM1H-series CPU Unit Serial Communications Board RS-422A/485 General-purpose external device Programmable Terminal (PT) C-series PC Protocol macros NT Link 1:1 Data Link No-protocol Programming Device (excluding Programming Console) Host computer Host Link Host Link Note An NT-AL001-E Converting Link Adapter can be used to convert between RS-232C and RS-422A/485. This Link Adapter requires a 5-V power supply. Power is provided by the RS-232C port on the Serial Communications Board when the Link Adapter is connected to it, but must be provided separately when connecting the Link Adapter to other devices. 3 Section Basic Operating Procedure 1-2 1-1-5 Mounting Location Slot 2: Not mountable Slot 1: Mount here The Serial Communications Board can be installed in Inner Board slot 1 of a CQM1H-series CPU Unit. The Board cannot be installed in slot 2. Serial Communications Board 1-2 Protocol Overview The following six serial communications modes can be used as required for each serial communications port on the Serial Communications Board. • Host Link: For connections to host computers, personal computer peripheral devices, or Programmable Terminals • Protocol Macros: For communications with general-purpose external devices using protocols • No-protocol: For connections to general-purpose devices for no-protocol communications using TXD(––) and RXD(––) instructions • 1:1 Data Links: For 1:1 data links with a C-series PC, including another CQM1H • 1:N-mode NT Link: For communications with one or more Programmable Terminals (PTs) • 1:1-mode NT Link: For communications with one PT Communications Ports and Serial Communications Modes Board Serial Communications Boards Serial communications mode Port RS-232C (port 1) RS-422A/ 485 (port 2) Peripheral Host Link bus or (SYSMAC Programming WAY) Console bus No OK Protocol macro Noprotocol 1:1 Data Link 1:N-mode NT Link 1:1-mode NT Link OK OK OK No OK OK (See note 1) OK (See note 1) OK (See note 2) OK (See note 2) OK (See note 2) OK (See note 2) Note 4 OK (See note 1) 1. A 4-wire connection must be used when using Host Link, no-protocol, or 1:1 Data Link communications with an RS-422A/485 connector. 2. The PT Programming Control functions are not supported. Connection examples for the serial communications modes are shown in the following sections. Section Protocol Overview 1-2 1-2-1 Host Link Mode In Host Link Mode, C-mode Host Link commands can be sent from a computer, PT, or other host to read or write I/O memory in the PC or to control the PC’s operating modes. The TXD(––) instruction can be used to send ASCII data to the host. This is called slave-initiated communications or unsolicited communications. Note 1. Programming Devices can also be connected in Host Link mode. 2. A 4-wire connection must be used when using an RS-422A/485 port. Sending C-mode Host Link Commands Host computer Serial Communications Board Response Host Link command Slave-initiated Communications Host computer TXD(––) PC initiates communication. Data CQM1H Serial Communications Board 1-2-2 Protocol Macros Data transfer procedures (called protocols) with general-purpose external devices can be created as macros using the CX-Protocol to match the communications specifications of the external device (but, half-duplex communications and start-stop synchronization must be used). These protocols are stored in the Serial Communications Boards from the CXProtocol, and enable data to be exchanged with general-purpose external devices simply by executing the PMCR(––) instruction in the CPU Unit. Standard system protocols for exchanging data with OMRON devices (such as Temperature Controllers, Intelligent Signal Processors, Bar Code Readers, and Modems) are provided as a standard feature in the Serial Communications Boards and the CX-Protocol. The CX-Protocol can also be used to change the standard system protocols according to user requirements. Serial Communications Board PMCR (––) CQM1H External device with RS-232C port RS-232C Message Protocol made specifically for the required communications specifications Note There are some restrictions in using the CX-Protocol to manipulate protocols or perform other operations for the CQM1H-series Serial Communications Board. These restrictions are described below. 5 Section Basic Operating Procedure 1-2 • Pin 8 on the DIP switch on the front of the CQM1H-series CPU Unit must be turned ON to use the CX-Protocol. While pin 8 is ON, you will not be able to use any of the CPU Unit or Board ports for the CX-Programmer, SYSMAC-CPT, or SYSMAC Support Software. • The model of PC must be set to the C200HG and the model of CPU Unit must be set to the CPU43. • Refer to 5-2 Restrictions in Using the CX-Protocol for further details. 1-2-3 No-protocol Communications The TXD(––) and RXD(––) instructions can be used in the ladder program to send and receive data without conversion through the RS-232C port to and from an external device. A start code can be sent before the data and an end code can be sent after it. Alternately, the amount of data being sent can be specified. A communications frame, however, cannot be created according to the specifications of the partner device, providing less flexibility than protocol macros. Retry processing, data form conversions, controlling processing based on a response, and other communications procedures cannot be performed. No-protocol communications are suitable for communications with bar code readers and other devices that only send data or printers and other devices that only receive data. Note A 4-wire connection must be used when using an RS-422A/485 port. Serial Communications Board TXD(––) or RXD(––) CQM1H External device with RS-232C port RS-232C OR Data only 1-2-4 PC 1:1 Data Links Two PCs can be connected via RS-232C cable to create a data link between them of up to 64 words in the LR area. The link words written by one PC are automatically transferred to the other PC for reading. One of the following three ranges of words can be set to be linked: LR 00 to LR 63, LR 00 to LR 31, or LR 00 to LR 15 A 1:1 Data Link communications system can be created between the CQM1H and another CQM1H, or between the CQM1H and the CQM1, C200HX/HG/HE, C200HS, CPM1, CPM1A, CPM2A, CPM2C, or SRM1(-V2). 6 Section Protocol Overview 1-2 Note A 4-wire connection must be used when using an RS-422A/485 port. Serial Communications Board CQM1H or other C-series PC CQM1H RS-232C Master PC LR 00 to Master area (sent) LR 31 LR 32 to Slave area (received) Slave PC LR 00 to Master area (received) LR 31 LR 32 to Slave area (sent) LR 63 LR 63 1-2-5 NT Links –– 1:N Mode A PC can be connected to one or more Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PC is allocated to the Status Control Areas and the Status Notification Areas used by the PTs, as well as to display objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PC to be controlled and monitored by operations from the PTs, without the use of a ladder diagram programming in the PC. Up to eight PTs can be connected to a PC. Note The user does not need to be aware of NT Link commands. The user only has to allocate the PC memory to the PTs. Serial Communications Board CQM1H Serial Communications Board CQM1H 1:N 1:1 RS-422A/485 PT PT PT 1-2-6 NT Links –– 1:1 Mode The functionality of the 1:1 mode is the same as that of the 1:N mode, but only a 1:1 connection is possible. The 1:1 and 1:N modes are not compatible as protocols. Serial Communications Board CQM1H 1:1 PT 7 Section Basic Operating Procedure 1-3 1-4 Specifications 1-3-1 Serial Communications Board Device name Serial Communications Board Model number CQM1H-SCB41 Classification CQM1H-series Inner Board Supporting CPU Units CQM1H-CPU51/61 Number of mountable Boards/PC and mounting location Serial communications Port 1 ports Port 2 Protocols Port 1 Port 2 Software interface with CPU Unit One Board per PC maximum, must be in Inner Board slot 1 PC Setup settings DM 6550 to DM 6559 (in read-only DM area in CPU Unit) RS-232C RS-422A/485 Host Link, protocol macro, no-protocol, 1:1 Data Link, 1:N-mode NT Link or 1:1-mode NT Link can be selected for each port. IR 200 to IR 207 (words for Inner Board slot 1) Set from Programming Device Current consumption (see note) 200 mA max. at 5 V DC Dimensions 25 × 110 × 107 (mm) (W × H × D) Weight 90 g max. Standard accessories Socket: XM2SA-0901 (OMRON) (two included) Hood: XM2SA-0911-E (OMRON) (two included, ESD compatible) Note The current consumption is for one Serial Communications Board. Power is supplied from the CQM1H When an NT-AL001-E Link Adapter is connected to the Serial Communications Board, power is supplied to the Link Adapter from the Board. A current consumption of 150 mA must be added for each Link Adapter that is connected. In the above specifications, “x” indicates that 150 mA must be added for each port to which an NT-AL001-E Link Adapter is connected to provide the required 5-V power supply. 1-3-2 General Specifications Conform to SYSMAC CQM1H-series CPU Unit specifications. 1-4 Basic Operating Procedure An overview of the basic operating procedure is provided here. Details are provided in sections 4 to 8 of this manual according to the serial communications mode. 1, 2, 3... 1. Turn OFF the power supply to the PC. 2. Mount the Board. 3. Connect the Board and the external device(s). 4. Turn ON the power supply to the PC. 5. Set the PC Setup settings from a Programming Device (e.g., Programming Console or CX-Protocol). 6. Execute communications. Use the control bits, flags, and words allocated in the IR area in the ladder program to control communications. 8 SECTION 2 Board Components and Installation This section describes the components of the Serial Communications Board, how to connect it in the CPU Unit, and how to connect it to external devices. 2-1 2-2 2-3 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-2 RS-232C Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-3 RS-422A/485 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-4 Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-1 Mounting the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-2 External Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-3 Mounting Height and Connector Cover Dimensions . . . . . . . . . . . . . . . . . . . . . . 2-2-4 Precautions in Handling the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-1 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-2 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-3 Reducing Electrical Noise for External Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-4 Port Applicability and Restrictions for 2-Wire/4-Wire Connections . . . . . . . . . . . 2-3-5 Recommended RS-232C Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-6 Recommended RS-422A/485 Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-7 Wiring Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-8 Soldering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-9 Assembling Connector Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-10 Connecting to the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 11 12 13 14 14 15 15 16 17 17 18 18 19 20 21 23 25 25 26 9 Section Installation 2-1 2-1 Component Names and Functions The components of the Serial Communications Board are described in this section. Serial Communications Board (Inner Board slot 1) Port 1: RS-232C Terminating resistance switch Applicable Connectors Socket: XM2SA-0901 (OMRON) Hood: XM2SA-0911-E (OMRON) (Two of each are included with the Board) 2-wire or 4-wire switch Port 2: RS-422A/485 2-1-1 Indicators Board Indicators There are three LED indicators on the Board, as described below. RDY: Lit when the Board is operational (green) RDY COMM1 COMM2 COMM1: Lit when data is being sent or received on the RS-232C port (Yellow) COMM2: Lit when data is being sent or received on the RS-442A/485 port (Yellow) Indicator RDY 10 Color Green COMM1 Yellow COMM2 Yellow Status Lit Meaning Flashing Operating normally, and protocol macro preparations have been completed. There is an error in the PC Setup settings for the Board or in the protocol macros contained in the Board. Not lit Flashing Not lit Flashing Not lit A hardware error has occurred in the Board. Port 1 is being used for sending or receiving. Port 1 is not being used for sending or receiving. Port 2 is being used for sending or receiving. Port 2 is not being used for sending or receiving. Section Wiring 2-1 A Serial Communications Board is mounted as an Inner Board in the CPU Unit and thus affects the CPU Unit ERR/ALM indicator. CPU Unit Indicators Indicator Color ERR/ALM Red Status Meaning Lit Fatal error Flashing Non-fatal error Not lit Normal operation If a fatal error occurs, the CPU Unit will stop operation in either RUN or MONITOR mode. If a non-fatal error occurs, the CPU Unit will continue operation in either RUN or MONITOR mode. The CPU Unit is operating normally. This indicator will also not be lit when a watchdog timer error occurs. If an error in the Inner Board is the cause of the error indicated on the ERR/ALM indicator, the Inner Board Error Flag (SR 25415) will turn ON and information on the error will be stored in AR 0400 to AR 0407. Refer to Section 9 Troubleshooting and Maintenance for details. 2-1-2 RS-232C Port Protocol Host Link Communications method Synchronization Baud rate Half-duplex No-protocol Protocol macros 1:1 Data Links 1,200/2,400/4,800/9,600/ 19,200 bps 19,200 bps 38,400 bps 19,200 bps Connections 1:1 1:1 NT Links 1:1 1:1 1:1 Start-stop synchronization (asynchronous) (1:N possible using Converting Link Adapters) Transmission distance Interface 1:N NT Links (1:N possible using Link Adapters) 15 m max. (See note) Complies with EIA RS-232C Note The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. Connector Pin Layout Pin No. Note Abbreviation Signal name I/O 1 (See note 1) FG Shield --- 2 SD Send data Output 3 RD Receive data Input 4 RTS (RS) Request to send Output 5 CTS (CS) Clear to send Input 6 (See note 2) 5V Power supply --- 7 DSR (DR) Data set ready Input 8 DTR (ER) Output 9 SG Data terminal ready (See note 4) Signal ground Shell (See note 1) FG Shield --- --- 1. Pin No. 1 and the shell are connected to the ground terminal (GR) of the Power Supply Unit inside the Serial Communications Board. Therefore, the cable shield can be grounded by grounding GR of the Power Supply Unit. 2. Pin 6 (5 V) is required when the NT-AL001-E Link Adapter is connected. For details on connection methods, refer to 2-3 Wiring. 11 Section Installation ! Caution 2-1 Do not connect the 5-V power supply of pin 6 to any external device other than an NT-AL001-E Link Adapter. Otherwise, the external device and the Serial Communications Board may be damaged. The following cables are provided for connection to NT-AL001-E Link Adapters. We recommend that these cables be used. NT-AL001-E connecting cables: XW2Z-070T-1 (0.7 m) XW2Z-200T-1 (2 m) Applicable Connectors Socket: XM2A-0901 (OMRON) or equivalent Hood: XM2S-0911-E (OMRON, conforms to ESD) or equivalent One Socket and one Hood are provided for each port. Recommended Cables UL2464 AWG28 5P IFS-RVV-SB (UL-approved, Fujikura Ltd.) AWG28 5P IFVV-SB (not UL-approved, Fujikura Ltd.) UL2464-SB (MA) 5P 28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.) CO-MA-VV-SB 5P 28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.) Cable length: 15 m max. 2-1-3 RS-422A/485 Port Protocol Host Link No-protocol Protocol macros 1:1 Data Links Communications method 4-wire, 1:1 Half-duplex 1:N NT Links 1:1 NT Links OK OK OK OK OK OK 4-wire, 1:N OK OK OK No OK No 2-wire, 1:1 No No OK No OK No 2-wire, 1:N No No OK No OK No Synchronization Baud rate Start-stop synchronous (asynchronous) 1,200/2,400/4,800/9,600/ 19,200 bps 19,200 bps 38,400 bps 19,200 bps Connections 1:N (N: 32 Units max.) 1:1 1:N (N: 8 Units max.) 1:1 Transmission distance Interface 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) Complies with EIA RS-485 Connector Pin Layout Pin No. Note Abbreviation Signal name I/O 1 (See note 1) SDA Send data – Output 2 (See note 1) SDB Send data + Output 3 NC Not used --- 4 NC Not used --- 5 NC Not used --- 6 (See note 1) RDA Receive data – Input 7 NC Not used --- 8 (See note 1) RDB Receive data + Input 9 NC Not used --- Shell (See note 2) FG Shield --- 1. When 2-wire connections are used, use pins 1 and 2, or pins 6 and 8. 2. The shell is connected to the ground terminal (GR) of the Power Supply Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit. 12 Section Wiring 2-1 The internal circuits for port 2 are shown below. Internal Circuits Pin 8: RDB (+) Receiver Terminating resistance: 200 Ω Terminating resistance switch Pin 6: RDA (–) 2-wire/4-wire switch Pin 2: SDB (+) Driver Pin 1: SDA (–) ! Caution Confirm polarities before connecting RS-422A/485 cables. Some devices require that SDA/B and RDA/B or signal polarities be reversed. Applicable Connectors Socket: XM2A-0901 (OMRON) or equivalent Hood: XM2S-0911-E (OMRON, conforms to ESD) or equivalent One Socket and one Hood are provided for each port. Recommended Cables CO-HC-ESV-3P 7/0.2 (Hirakawa Hewtech Corp.) Cable length: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) 2-1-4 Switches The TERM and WIRE switches are on the front panel of the Serial Communications Board. Refer to page 10 for a diagram of the Board. Terminating Resistance Switch When an RS-422/485 port is used, turn ON the switch if the Serial Communications Board is on the end of the transmission line. Refer to information on specific serial communications modes for the ON/OFF settings. Label TERM Name Terminating resistance switch Settings OFF: Terminating resistance OFF Factory setting OFF: Terminating resistance OFF ON: Terminating resistance ON 2-Wire or 4-Wire Switch When an RS-422/485 port is used, set the switch to 2 when 2-wire connections are used, and set the switch to 4 when 4-wire connections are used. Label WIRE Name 2-wire or 4-wire switch Settings 2: 2-wire Factory setting 2: 2-wire 4: 4-wire Note Host Link, no-protocol, and 1:1 Data Link modes cannot use 2-wire RS-422A/485 communications. Always use 4-wire connections when using RS-422A/485 communications for these serial communications modes. Refer to 2-3 Wiring for connections. 13 Section Installation 2-2 2-2 Installation 2-2-1 Mounting the Board This section describes how to mount a Serial Communications Board in Inner Board slot 1 of a CPU Unit. Slot 1 is the slot on the left. Only one Serial Communications Board can be installed in each CPU Unit. Note 1. The Serial Communications Board cannot be mounted in Inner Board slot 2. 2. Always turn OFF the power before installing or removing the Serial Communications Board. Installing or removing the Serial Communications Board with the power ON can cause the CPU Unit to malfunction, damage internal components, or cause communications errors. 3. Before handling the Serial Communications Board, touch a grounded metallic object in order to discharge any static build-up from your body. 1, 2, 3... 1. Press the catches at the top and bottom of the Inner Board slot 1 compartment cover. Press the top catch. Press the bottom catch. 2. Remove the compartment cover. Inner Board Connector 3. Insert the Serial Communications Board. 14 Section Wiring 2-2 2-2-2 External Dimensions Unit: mm CS1W-SCB41 Mounted in the CPU Unit 110 25 107 2-2-3 Mounting Height and Connector Cover Dimensions When mounting the Serial Communications Board, make sure to provide space for the mounting height and connector cover dimensions shown below. Serial Communication Unit mounted in the CPU Unit Connecting Cable connector 123 223 Note The mounting heights shown above are applicable when the attached connectors, connector covers, and recommended cables are used. The mounting height may differ when other connectors, connector covers, and cables are used. Determine the mounting height, taking into account the connectors, connector covers, and the minimum bending radius of the cables. 15 Section Installation 2-2 2-2-4 Precautions in Handling the Board • Turn OFF the power supply to the CPU Unit before mounting or removing the Board. • Turn OFF the power supply to the CPU Unit before before connecting or disconnecting Board connectors or wiring. • Separate the port connector lines from the high-tension or power lines to reduce external noise. • Leave the port cover attached when not using a communications port. Port cover 16 Section Wiring 2-3 2-3 Wiring 2-3-1 Connectors Prepare connecting cables for port 1 (RS-232C) and port 2 (RS422A/485) using the Sockets and Hoods provided with the Board and the recommended cables. Connection methods vary with the serial communications mode that is being used. Refer to the following sections for connection examples. Host Link: Protocol macros: No-protocol: 1:1 Data Links: NT Links: Section 4 Host Link Communications Section 5 Protocol Macros Section 6 Non-protocol Communications Section 7 Communications for 1:1 Data Links Section 8 NT Link Communications Hood Socket Standard Connectors (for Both RS-232C and RS-422A/485) Name Model Socket XM2A-0901 Hood XM2S-0911-E Socket: XM2A-0901 Specifications Used together (provided with For 9-pin, metric Serial screws, conforms Communications to ESD Board). 9-pin male Hood: XM2S-0911-E Recommended Cables RS-232C Cables Model UL2464 AWG28×5P IFS-RVV-SB (UL-approved) AWG28×5P IFVV-SB (not UL-approved) UL2464-SB (MA) 5P×AWG28 (7/0.127) (UL-approved) CO-MA-VV-SB 5P×AWG28 (7/0.127) (not UL-approved) Manufacturer Fujikura Ltd. Hitachi Cable, Ltd. 17 Section Installation 2-3 RS-422A/485 Cable Model Manufacturer CO-HC-ESV-3P×7/0.2 Hirakawa Hewtech Corp. Refer to pages 11 and 12 for the connector pin layouts. Refer to 2-3-5 Recommended RS-232C Wiring Examples and 2-3-6 Recommended RS-422A/485 Wiring Examples for wiring examples, and to 2-3-7 Wiring Connectors for wiring methods. Standard cables are available for connection to personal computers and PTs. Refer to Section 4 Host Link Communications for personal computer cables and to your PT user’s manual for PT cables. 2-3-2 Wiring Precautions • Before connecting or disconnecting the communications cables, always make sure that the PC is turned OFF. • Tighten the communications connector screws firmly with your fingers. • Serial Communications Boards can be connected to various devices. For compatibility, refer to the operation manuals for the devices to which they are to be connected. 2-3-3 Reducing Electrical Noise for External Wiring Observe the following precautions for external wiring. • When multi-conductor signal cable is being used, avoid using I/O wires and other control wires in the same cable. • If wiring racks are running in parallel, allow at least 300 mm between the racks. Low-current cables Communications cables Control cables PC power supply and general control circuit wiring Power cables 300 mm min. 300 mm min. Power lines Ground to 100 Ω or less. • If the I/O wiring and power cables must be placed in the same duct, they must be shielded from each other using grounded steel sheet metal. Communications cables PC power supply and general control circuit wiring Power lines Steel sheet metal 200 mm min. Ground to 100 Ω or less. 18 Section Wiring 2-3 2-3-4 Port Applicability and Restrictions for 2-Wire/4-Wire Connections The following table shows the port connections that can be used for each serial communications mode. RS-232C port Serial communications mode 1:1 RS-422A/485 port 1:N 4-wire 1:1 Host Link OK Protocol macros OK No-protocol OK 1:1 Data Links OK 1:N-mode NT Links OK 1:1-mode NT Links OK Note OK (See note 2) No No 2-wire 1:N OK No No OK OK OK OK OK OK No No OK No No No OK OK OK OK OK No No No 1. The 1:N connection method can be used by converting between RS-232C and RS-422A/485 through NT-AL001-E Converting Link Adapters. 2. Use 4-wire connections between the Converting Link Adapters. 3. The 2-wire RS-422A/485 connections cannot be used for Host Link communications. Use 4-wire connections. The transmission circuits for 2-wire and 4-wire connections are different, as shown in the following diagram. Example of 2-Wire Connections 2/4-wire switch (DPDT) 2/4-wire switch (DPDT) Other Unit Other Unit Board Note NT-AL001-E Link Adapter Settings 1:N OK Example of 4-Wire Connections Board 1:1 Other Unit Not connected Other Unit 1. Use the same transmission circuit (2-wire or 4-wire) for all nodes. 2. Do not use 4-wire connections when the 2/4-wire switch on the Board is set to 2-wire. The NT-AL001-E Link Adapter has a DIP switch for setting RS-422A/485 communications conditions. When connecting the Board, refer to the DIP switch settings shown in the following table. 19 Section Installation Pin Function 2-3 1 Not used. Always set this pin to ON. Factory setting ON 2 Built-in terminating resistance setting ON 3 ON: Connects terminating resistance. OFF: Disconnects terminating resistance. 2/4-wire setting OFF 4 2-wire: Set both pins to ON. 4-wire: Set both pins to OFF. OFF 5 Transmission mode (See note) ON Constant transmission: Set both pins to OFF. Transmission performed when CTS signal in RS-232C interface is at high level: Set pin 5 to OFF and pin 6 to ON. 6 OFF Transmission performed when CTS signal in RS-232C interface is at low level: Set pin 5 to ON and pin 6 to OFF. Note When connecting to a CQM1H-series CPU Unit, turn OFF pin 5 and turn ON pin 6. 2-3-5 Recommended RS-232C Wiring Examples It is recommended that RS-232C cables be connected as described below, especially when the Serial Communications Board is used in an environment where it is likely to be subject to electrical noise. 1, 2, 3... 1. Always use shielded twisted-pair cables as communications cables. Model Manufacturer UL2464 AWG28x5P IFS-RVV-SB (UL-approved) AWG28x5P IFVV-SB (not UL-approved) UL2464-SB (MA) 5Px28AWG (7/0.127) (UL-approved) CO-MA-VV-SB 5Px28AWG (7/0.127) (not UL-approved) Fujikura Ltd. Hitachi Cable, Ltd. 2. Combine signal wires and SG (signal ground) wires in a twisted-pair cable. At the same time, bundle the SG wires to the connectors on the Serial Communications Board and the remote device. 3. Connect the shield of the communications cable to the Hood (FG) terminal of the RS-232C connector on the Serial Communications Board. At the same time, ground the ground (GR) terminal of the Power Supply Unit to 100 Ω or less. 4. A connection example is shown below. Example: Twisted-pair Cable Connecting SD-SG, RD-SG, RTS-SG, and CTS-SG Terminals Actual Wiring Example Serial Communications Board Pin Twist the braided shield to make SG signal wires it thinner and connect to Pin No. 1 (FG). Cover this section with heat-shrink tube to avoid contact with other sections. Remote device Signal Signal SD RD RTS CTS SG Hood FG FG RD SD CTS RTS SG FG Bundle the SG wires. Aluminum foil Shield XM2S-0911-E 20 Section Wiring 2-3 Note The Hood (FG) is internally connected to the ground terminal (GR) on the Power Supply Unit. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit. Although there is conductivity between the Hood (FG) and pin 1 (FG), connect the Hood (FG) to the shield because the Hood (FG) has smaller contact resistance with the shield than pin 1 (FG), and thus provides better noise resistance. Serial Communications Board Power Supply Unit Ground to 100 Ω or less Hood and GR are internally connected. Grounding the GR terminal grounds the Hood (FG). 2-3-6 Recommended RS-422A/485 Wiring Examples Recommended RS-422A/485 Cable We recommend the following wiring methods to ensure quality transmissions for RS-422A/485 communications. 1, 2, 3... 1. Always use shielded twisted-pair cables for the communications cables. Model CO-HC-ESV-3Px7/0.2 Manufacturer Hirakawa Hewtech Corp. 2. Connect the shield of the communications cable to the Hood (FG) of the RS-422A/485 connector on the Serial Communications Board. At the same time, ground the ground (GR) terminal of the Power Supply Unit to 100 Ω or less. Note Always ground the shield only at the Board end. Grounding both ends of the shield may damage the device due to the potential difference between the ground terminals. Connection examples are shown below. 2-Wire Connections Serial Communications Board Remote device Pin Signal Hood Signal Shield 21 Section Installation 2-3 4-Wire Connections Serial Communications Board Remote device Signal Signal Pin Hood Shield Using a 3G2A9-AL001 Link Adapter Serial Communications Board Pin Signal 3G2A9-AL001 Pin Signal Remote device Signal Signal Pin RS-422 interface Hood Signal Pin Remote device Signal Using an NT-AL001-E RS-232C/RS-422 Link Adapter Serial Communications Board NT-AL001-E Pin Signal Pin Signal Signal Pin RD SD CTS RTS 5V DSR DTR SG SD RD RTS CTS 5V DSR DTR SG Hood FG Remote device Signal Remote device Shield (See note.) Signal Note The following cables are available for this connection. Length Model 70 cm XW2Z-070T-1 2m XW2Z-200T-1 It is recommended that one of these cables be used to connect the RS-232C port on the Serial Communications Board to the NT-AL001-E Converting Link Adapter. 22 Section Wiring 2-3 Note The Hood (FG) is internally connected to the ground terminal (GR) on the Power Supply Unit. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit. Serial Communications Board Power Supply Unit Ground to 100 Ω or less Hood and GR are internally connected. Grounding the GR terminal grounds the Hood (FG). 3. Be sure to turn ON the terminating resistance at the last Unit at the end of the RS-422A/485 cable. 2-3-7 Wiring Connectors Use the following steps to wire connectors. Cable Preparation See the following diagrams for the length of the cable portion to be cut in each step. Shield Connected to Hood (FG) 1, 2, 3... 1. Cut the cable to the required length. 2. Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield. 25 mm (RS-422A) 40 mm (RS-232C) 3. Trim off the braided shield using scissors so that the remaining shield length is 10 mm. 10 mm 4. Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm. 5 mm 23 Section Installation 2-3 5. Fold back the braided shield. 6. Wrap aluminum foil tape around the folded shield. Aluminum foil tape Shield Not Connected to Hood (FG) 1, 2, 3... 1. Cut the cable to the required length. 2. Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield. 25 mm (RS-422A) 40 mm (RS-232C) 3. Trim off all the braided shield using scissors. 4. Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm. 5 mm 5. Wrap adhesive tape around the conductor from which the braided shield was removed. Adhesive tape 24 Section Wiring 2-3 2-3-8 Soldering 1, 2, 3... 1. Thread a heat-shrinking tube through each conductor. 2. Temporarily solder each conductor to the corresponding connector terminals. 3. Completely solder each conductor. Soldering iron Heat-shrinking tube Inside diameter: 1.5 mm, l = 10 4. Return the heat-shrinking tube to the soldered portion, then heat the tube to shrink it in place. Heat-shrinking tube 2-3-9 Assembling Connector Hood Assemble the connector Hood as shown below. End connected to FG Adhesive tape End not connected to FG Aluminum foil tape Grounding plate 25 Section Installation 2-3-10 Connecting to the Board Tighten the screws firmly with your fingers. 26 2-3 SECTION 3 Default Settings and Related Bits/Flags This section describes the settings, control bits, flags, and status information available in the CPU Unit for use with the Serial Communications Board. 3-1 3-2 3-3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 28 30 27 Section PC Setup Settings 3-1 3-2 Overview The following settings, control bits, flags, and information are available in the CPU Unit memory for use with the Serial Communications Board. Contents Addresses PC Setup settings for the Serial Communications Board Control bits, flags, and status information for the Inner Board slot 1 Error flags and information for Inner Boards Port 1: DM 6555 to DM 6559 Port 2: DM 6550 to DM 6554 IR 200 to IR 207 SR 25415: Inner Board Error Flag AR 04: Inner Board Error Code CX-Protocol (for protocol macro mode operation) Serial Communications Board CPU Unit Flash memory Backup battery PC Setup settings (DM 6550 to DM 6559) Inner Board Slot 1 Area (IR 200 to IR 207) Protocol macro data (for protocol macro mode operation) Protocol macro data Read constantly Refreshed Inner Board Error Flag and Error Code (SR 25415 and AR 04) 3-2 PC Setup Settings Settings for the Serial Communications Board can be made from a Programming Device in the following words of the PC Setup. Port 1: DM 6555 to DM 6559 Port 2: DM 6550 to DM 6554 The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed. The settings in these words depend on the serial communications mode that is being used. Refer to the following sections for details. Host Link: Protocol macros: No-protocol: 1:1 Data Links: NT Links: Section 4 Host Link Communications Section 5 Protocol Macros Section 6 Non-protocol Communications Section 7 Communications for 1:1 Data Links Section 8 NT Link Communications An overview of the PC Setup settings for the Serial Communications Board is given next. The default setting for each word is all zeros (0000). 28 Section PC Setup Settings Word(s) Bit(s) DM 6550 (port 2) 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 1: Settings in DM 6551 (DM 6556 for port 1) 04 to 07 CTS control settings 0: Disable; 1: Set Host Link, noprotocol, 1:1 Data Links 08 to 11 Link words for 1:1 Data Link (when bits 12 to 15 are set to 3) 0: LR 00 to LR 63; 1: LR 00 to LR 31; 2: LR 00 to LR 15 1:1 Data Link master (link words) or or DM 6555 (port 1) 12 to 15 DM 6551 (port 2) DM 6556 (port 1) DM 6552 (port 2) DM 6557 (port 1) DM 6553 (port 2) DM 6558 (port 1) Function 3-2 Applicable mode Host Link, noprotocol, protocol macros Maximum Programmable Terminal unit number (when bits 12 to 15 are set to 5) NT Link (max. 1 to 7 (BCD) unit number) Serial communications mode All modes 0: Host Link; 1: No-protocol; 2: 1:1 Data Link slave; 3: 1:1 Data Link master; 4: NT Link in 1:1 mode; 5: NT Link in 1:N mode; 6: Protocol macro 00 to 07 Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Host Link, noprotocol, protocol macros 08 to 15 Frame format Start Length Stop Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bit Even 04: 1 bit 7 bits 2 bit Odd 05: 1 bit 7 bits 2 bit None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bit Even 10: 1 bit 8 bits 2 bit Odd 11: 1 bit 8 bits 2 bit None Transmission delay 0000 to 9999 (BCD): Set in units of 10 ms, e.g., a setting of 0001 equals 10 ms Host Link, noprotocol, protocol macros Host Link unit number 00 to 31 (BCD) Start code enable 0: Disable; 1: Set End code enable 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF Start code (No-protocol) 00 to FF (hexadecimal) When bits 12 to 15 of DM 6553 or DM 6558 are set to 0 Hex: Number of bytes received 00: Default setting (256 bytes) 01 to FF: 1 to 255 bytes Host Link 00 to 15 00 to 07 08 to 11 12 to 15 DM 6554 (port 2) 00 to 07 DM 6559 (port 1) 08 to 15 Host Link, noprotocol No-protocol No-protocol No-protocol No-protocol When bits 12 to 15 of DM 6553 or DM 6558 are set to 1 Hex: End code (No-protocol) 00 to FF (hexadecimal) 29 Section PC Setup Settings 3-3 3-3 Control Bits, Flags, and Status Information Control bits, flags, and status information for the Serial Communications Board is available in the Inner Board Slot 1 area. The addresses in this area are as follows: Inner Board Slot 1 Area: IR 200 to IR 207 The following bits are often used in Protocol Macro Mode. Refer to 5-6 Control Bits, Flags, and Status Information for details. Word Bits IR 200 00 01 02 03 to 10 11 12 13 14 15 00 to 03 IR 201 04 05 Function Serial Communications Board Hardware Error Flag Board Identification Error Flag (hardware error) Protocol Data Error Flag Not used. Port 2 Protocol Macro Execution Error Flag Port 1 Protocol Macro Execution Error Flag Port 2 PC Setup Error Flag Port 1 PC Setup Error Flag PC Setup Error Flag Port 1 Error Code 0: Normal operation 1: Parity error 3: Overrun error 4: FCS error 6: Checksum error 7: Command error Communications Error Flag Transmission Enabled Flag Communications modes All modes Protocol macro All modes All modes 2: Framing error 5: Timeout error Turns ON when transmission is enabled, OFF when transmissions are being processed for TXD(––). Host Link or No-protocol Use with flag as an execution condition for TXD(––) when using No-protocol or Host Link Mode. 06 Reception Completed Flag 07 Turns ON when receptions for RXD(––) have been completed in No-protocol Mode. Reception Overflow Flag 08 to 11 12 13 In No-protocol Mode, turns ON when the next data is received before previous data is read out using RXD(––). Sequence Abort Completion Flag Protocol macro Port 2 Error Code All modes 0: Normal operation 1: Parity error 2: Framing error 3: Overrun error 4: FCS error 5: Timeout error 6: Checksum error 7: Command error Communications Error Flag Host Link or Transmission Enabled Flag No-protocol Turns ON when transmission is enabled, OFF when transmissions are being processed for TXD(––). 14 Use with flag as an execution condition for TXD(––) when using No-protocol or Host Link Mode. Reception Completed Flag 15 Turns ON when receptions for RXD(––) have been completed in No-protocol Mode. Reception Overflow Flag In No-protocol Mode, turns ON when the next data is received before previous data is read out using RXD(––). Sequence Abort Completion Flag Protocol macro 30 Section PC Setup Settings Word Bits Function IR 202 00 to 07 Port 1 Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.) Repeat counter PV (00 to FF hexadecimal) Reception counter 00 to 15 IR 203 00 to 07 00 to 15 IR 204 00 01 02 to 07 08 to 11 12 to 15 IR 205 00 to 03 04 to 07 08 to 14 15 IR 206 00 to 03 04 to 07 08 to 14 15 IR 207 00 01 02 03 04 05 06 to 07 08 IR 208 to IR 215 3-3 Communications modes NT Link in 1:N mode Protocol macro No-protocol The number of bytes of data received in No-protocol Mode (Hex). Reset to 0 when data is read out using RXD(––). Port 2 Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.) NT Link in 1:N mode Repeat counter PV (00 to FF hexadecimal) Protocol macro Reception counter No-protocol The number of bytes of data received in No-protocol Mode (Hex). Reset to 0 when data is read out using RXD(––). Protocol macro Port 1 Tracing Flag Port 2 Not used. Port 1 Protocol Macro Error Code 0: Normal operation 1: No protocol macro function 2: Sequence number error 3: Data read/write area overflow Port 2 4: Protocol data grammar error 5: Protocol macro execution error during port initialization Port 1 Completed Reception Case Number Completed Step Number Not used. IR 204 (bits 08 to 11) Data Stored Flag 0: No data stored; 1: Data stored Port 2 Completed Reception Case Number Completed Step Number Not used. IR 204 (bits 12 to 15) Data Stored Flag 0: No data stored; 1: Data stored Port 1 Serial Communications Port Restart Bits Port 2 Port 1 Continuous Trace Start/Stop Bits Port 2 Port 1 Shot Trace Start/Stop Bits Port 2 Not used. Port 1 Protocol Macro Executing Flag (instruction execution) 09 10 11 12 Transfer Step Error Processing Flag Sequence End Completion Flag Forced Abort Bit Port 2 Protocol Macro Executing Flag (instruction execution) 13 14 15 00 to 15 Transfer Step Error Processing Flag Sequence End Completion Flag Forced Abort Bit Not used. Protocol macro Protocol macro All modes Protocol macro No-protocol or Protocol macro Protocol macro No-protocol or Protocol macro Protocol macro --- 31 Section PC Setup Settings Word Bit(s) SR 254 15 AR 04 00 to 07 32 3-3 Function Inner Board Error Flag Turns ON when an error occurs in an Inner Board mounted in slot 1 or slot 2. The error code for slot 1 is stored in AR 0400 to AR 0407 and the error code for slot 2 is stored in AR 0408 to AR 0415. Slot 1 Inner Board Error Code (Hex) 00: Normal 01, 02: Hardware error 10: Serial Communications Board error SECTION 4 Host Link Communications This section describes the procedure and other information required to use Host Link communications. 4-1 4-2 4-3 4-4 4-5 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-2 Host Link Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-1 Types of Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-2 Standard Cables from Board to Personal Computer . . . . . . . . . . . . . . . . . . . . . . . Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-1 Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-2 Example Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-3 Host Link Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-4 End Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changes from Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5-1 RS-232C Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5-2 RS-422A/485 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 35 36 36 39 39 44 45 45 48 51 52 53 53 55 33 Section Connections 4-1 4-1 Host Link Communications A Host Link System can be used to send C-mode Host Link commands from a host (e.g., personal computer or PT) to a PC to read/write I/O memory, control operating modes, etc. The PC can also use the TXD(––) instruction to send specified I/O memory data to the host for slave-initiated communications. Refer to the CQM1H-series PC Programming Manual for details on C-mode commands. Host-initiated Communications Communications in a Host Link System are normally started by a host computer. Command Host computer CQM1H-series PC Response The host sends a command to the PC. The PC processes the command and returns a response to the host computer. This process is repeated, allowing the host computer to monitor and control PC operation. Slave-initiated Communications The PC can also initiate communications with the host to send data, as may be necessary when errors occur on the line controlled by the PC or to confirm the operating status of the host. ASCII data Host computer CQM1H-series PC When the TXD(––) instruction is executed in the ladder program of the PC, the contents of the I/O memory words specified for the instruction is converted to ASCII and sent to the host. There is no response to this transmission. TXD(––) Instruction TXD(48) reads N bytes of data beginning from words S, converts it to ASCII, and outputs the data from the specified port as a Host Link command. Up to 122 bytes (61 words) of data can be sent. Refer to the CQM1H-series PC Programming Manual for details. TXD(48) S First source word C Control word N Number of bytes: 4 digits BCD, 0000 to 0061 The format of the Host Link command generated by TXD(––) is shown below. The command header code is EX and is followed by the specified data converted to ASCII. There is no response to the EX command. @ x 101 x 100 Node No. E X Send data (ASCII) Header code 122 characters max. FCS ↵ Terminator Note If the PC is sending a response to a Host Link command when the TXD(––) instruction is executed, the EX command for TXD(––) will be sent after the response. If TXD(––) is executed in Host Link Mode, the specified data is converted to ASCII before being sent. If TXD(––) is executed in No-protocol Mode, the specified data is sent without conversion. 34 Section Application Procedure 4-1 4-1-1 Host Link Communications Host Link communications are supported by all CQM1H-series CPU Units. A Serial Communications Board can be used to connect a single PC to more than one host computer for Host Link communications, including slave-initiated communications. Host Link communications provide the following features. Connect One Computer to Multiple PCs An RS-422A/485 port can be used to connect one host computer to up to 32 CQM1H-series PCs. Computer Monitoring and Control of PCs Host Link communications enable the host computer to monitor or control PC operations and to read and write I/O memory in the PCs. Redundant Error Checking Both vertical and horizontal (FCS) parity checks are performed on communications data to achieve essentially error-free communications. Combining error checking and retry processing goes one step further to eliminate nearly all the effects of communications problems. Simultaneous Usage of Both Ports The Serial Communications Board provides two serial communications ports that can be used simultaneously to connect to two different networks of host computers in addition to the connections made directly from the built-in CPU Unit ports. Slave-initiated Communications Communications can be performed either by sending a command from a host and having the PC return a response, or by sending data from a PC to the host. Note A Host Link connection can also be used to connect the PC to a Programming Device running on a personal computer. The following two modes can be used to connect to computers running Programming Devices. Only the Host Link Mode can be used for the Serial Communications Board. Serial communications Features mode Host Link Functions as a communications protocol with standard host computers. Either 1:1 or 1:N connections are possible. Slower than a peripheral bus connection. Connection is possible through a modem or Optical Link Adapter, and long-distance and 1:N connections are possible using RS-422A/485. Peripheral bus Enables high-speed communications. A peripheral bus connection is thus the normal mode used to connect to a computer running the CX-Programmer. Only 1:1 connections are possible. With the CQM1H, the baud rate of the Programming Device is detected when the connection is made. 35 Section Connections 4-2 4-1-2 Host Link Specifications Item Description Communications mode Half-duplex (Full-duplex for slave-initiated communications) Synchronization Start-stop (asynchronous mode) Baud rate (see note 1) RS-232C port and RS-422A/485 ports: 1,200/2,400/4,800/9,600/19,200 bps Communications distance (see note 1) Connection configuration Number of connected Units Frame structure Error check codes Command flow and support Default setting: 9,600 bps RS-232C port: 15 m max. (see note 2) RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using an Converting Link Adapters.) RS-422A/485 port: 1:N (N = 32 Units max.) 32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection) C-mode Host Link commands Header: @, address: (Host Link unit number) 0 to 31 (BCD) Data: Header code + text Error check code: FCS Terminator: *+CR Vertical parity: Even, odd. or none FCS (horizontal parity converted to ASCII) Command flow Commands Contents Host computer to C-mode Host Link 1:1 or 1:N communications with directly connected PC commands PCs (The specified frame format must be prepared on the host computer and then sent.) PC to host computer Transmission delay time Data only Communications using TXD(––) from CPU Unit. No response from host. Host computer to PC Connection between the host computer and PC must be 1:1. 0 to 99,990 ms (set in PC Setup in 10-ms units) The delay is from the return of a response by the PC until a response can be returned to the next command received from the host. PC to host computer The delay is from the beginning of TXD(––) execution until execution of the next TXD(––) can be started. Note 1. Confirm the baud rates and communications distance supported by connected devices. 2. The maximum cable length for RS-232C is 15 m. 4-2 Application Procedure 1, 2, 3... 1. Turn OFF the power supply to the PC. 2. Mount the Board. 3. Connections Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-4522A/485 port. The host computer can be connected to a PC 1:1, or NT-AL001-E Converting Link Adapters can be used to convert from RS-232C to RS-422A/485 to connect the host computer to PCs 1:N. Standard connection examples are 36 Section Application Procedure 4-2 shown below. Perform other processing as required, such as setting switches on the external device(s). Serial Communications Board RS-232C RS-232C RS-422A /485 3G2A9-AL001 RS-422A /485 NT-AL001-E Terminating resistance ON, 5-V power supply required Terminating resistance ON The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required. 4. Turn ON power. 5. Set the PC Setup settings for the Serial Communications Board. Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559. Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed. The following table shows the standard settings. Port 1 Port 2 Bit(s) Default setting Function DM 6555 DM 6550 00 to 03 0 Hex Standard port settings (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 04 to 07 0 Hex CTS control disabled 08 to 11 --- Not used. 12 to 15 0 Hex Communications mode 0: Host Link DM 6556 DM 6551 00 to 07 08 to 15 ----- Baud rate: invalid Frame format: Invalid DM 6557 DM 6552 00 to 15 0000 Hex Transmission delay: 0 ms DM 6558 DM 6553 00 to 07 08 to 11 12 to 15 00 BCD ----- Node number 00 Not used. Not used. 37 Section Connections 4-2 6. Program the host and the CPU Unit and execute the programs. Host-initiated Communications: Host Link Commands A program must be prepared in the host to send Host Link commands to the PC and receive responses. Program to send commands and receive responses Host Response Serial Communications Board Command PC-initiated Communications: TXD(––) Instruction TXD(––) must be included in the ladder program to send data from the PC to the host. Program to send responses Host Serial Communications Board TXD(––) Data CPU Unit 38 Section Application Procedure 4-3 4-3 Connections 4-3-1 Types of Connection Port connections for Host Link communications are shown in the following table. Up to 32 nodes can be connected for 1:N connections. Port Configuration 1:1 RS-232C Schematic diagram RS-232C RS-232C RS-422A/485 NT-AL001-E NT-AL001-E RS-232C Resistance ON Resistance ON 5-V power RS-232C 1:N RS-422A/485 RS-232C NT-AL001-E Resistance ON RS-232C 5-V power RS-422A/485 NT-AL001-E Resistance ON RS-232C RS-232C 1:1 NT-AL001-E RS-422A/485 RS-232C Resistance ON 5-V power RS-422A/485 1:N Resistance ON 3G2A9-AL001 RS-422A /485 RS-232C NT-AL001-E Resistance ON 5-V power RS-422A /485 Resistance ON Note 1. Four-wire connections must be used for RS-422A/485 connections with Host Link communications. 2. “Resistance ON” indicates the terminating resistance must be turned ON. 3. “5-V power” indicates that a 5-V power supply is required for the Link Adapter. Refer to the Link Adapter manual for details. A 5-V power supply is not required for a Link Adapter connected to a Serial Communications Board because power is supplied from pin 6 of the connector. 4. The maximum cable length for RS-232C is 15 m. Connection Examples The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 2-3 Wiring for actual wiring methods. 39 Section Connections 4-3 Host Computer Connections 1:1 Connections Using RS-232C Ports IBM PC/AT or Compatible Computers Serial Communications Board Computer Signal Pin RS-232C interface Pin Signal CD RD SD DTR SG DSR RTS CTS CI FG SD RD RTS CTS 5V DSR DTR SG RS-232C interface D-sub, 9-pin connector (female) D-sub, 9-pin connector (male) Using NT-AL001-E Converting Link Adapters Computer RS-232C Interface Shield NT-AL001-E Link Adapter Signal RS-232C Pin Signal FG SD RD RTS CTS NC SD RD RTS CTS 5V DSR DTR SG DSR DTR SG Signal Pin Serial Communications Board NT-AL001-E Link Adapter RS-422A Pin Signal Signal Pin RS-232C (See note) NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin Terminal block connector (male) Terminal block DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON D-sub, 9-pin connector (male) Pin Signal FG SD RD RTS CTS 5V DSR DTR SG RS-232C Interface D-sub, 9-pin connector (male) 5-V (+) power (–) Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m ! Caution 40 Do not use the 5-V power from pin 6 of the RS-232C port for anything but the NT-AL001-E Link Adapter. Using this power supply for any other external device may damage the Serial Communications Board or the external device. Section Application Procedure 4-3 1:N Connections Using RS-232C Ports Computer Signal FG SD RS-232C RD Interface RTS CTS DSR DTR SG 5-V (+) power (–) NT-AL001-E Link Adapter Shield Pin Signal Signal Pin RS-422A Pin Signal NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin Terminal block connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF Serial Communications Board NT-AL001-E Link Adapter Signal Pin RS-232C (See note) Pin Signal FG SD RD RS-232C RTS Interface CTS 5V DSR DTR SG NC SD RD RTS CTS 5V DSR DTR SG DIP Switch Settings Pin 1: ON Pin 2: OFF (no terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON NT-AL001-E Link Adapter Pin Signal D-sub, 9-pin connector (male) Serial Communications Board Signal Pin RS-232C Pin (See note) NC SD RD RTS CTS 5V DSR DTR SG DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON Signal FG SD RD RS-232C RTS Interface CTS 5V DSR DTR SG D-sub, 9-pin connector (male) Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 41 Section Connections 1:1 Connections Using RS-422A/485 Ports NT-AL001-E Link Adapter Computer Serial Communications Board Pin Signal Signal FG SD RS-232C RD Interface RTS CTS DSR DTR SG 5-V (+) power (–) Shield Pin Signal Pin Signal NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin Terminal block connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF 42 RS-422A / 485 Interface Hood Terminating resistance ON 4-wire 4-3 Section Application Procedure 4-3 1:N Connections Using RS-422A/485 Ports Serial Communications Board 3G2A9-AL001 Link Adapter NT-AL001-E Link Adapter Computer Signal FG SD RS-232C RD Interface RTS CTS Pin Signal Pin Signal Shield RS-422A/ 485 Interface Hood Terminating resistance OFF 4-wire Signal Pin D-sub, 9-pin connector (male) D-sub, 9-pin Terminal block connector (male) 5-V (+) power (–) Pin Signal RS-422A/ 485 Interface NC SD RD RTS CTS 5V DSR DTR SG DSR DTR SG Shield Signal Pin Signal Pin Serial Communications Board Shield DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF Pin Signal RS-422A/ 485 Interface Hood Terminating resistance ON (last node) 4-wire Serial Communications Board NT-AL001-E Link Adapter Computer RS-422A Shield Signal RS-232C Interface FG SD RD RTS CTS DSR DTR SG 5-V (+) power (–) RS-232C Pin Signal Pin Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin Terminal block connector (male) RS-422A/ 485 Interface Hood Terminating resistance OFF 4-wire Serial Communications Board Pin Signal DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF RS-422A/ 485 Interface Hood Terminating resistance ON (last node) 4-wire 43 Section Connections 4-3 4-3-2 Standard Cables from Board to Personal Computer Board port Computer RS-232C port (D-sub, 9-pin female) IBM PT/AT or compatible Computer port D-sub, 9-pin male Network type Host Link (SYSMAC WAY) Model Length XW2Z-200S-CV 2m XW2Z-500S-CV 5m Remarks Conforms to ESD. The following Connecting Cables can be used to connect an RS-232C to the computer. Board port Computer RS-232C port (D-sub, 9-pin female) IBM PT/AT or compatible Computer port D-sub, 9-pin male Network type Host Link (SYSMAC WAY) Model Length XW2Z-200S-V 2m XW2Z-500S-V 5m Remarks --- Preparing an RS-232C Cable for the Computer The following cables and connectors can be used to manufacture a cable to connect the Serial Communications Board to the PC. Applicable Connectors The following connector connects to the Serial Communication Board. Name Socket Hood Model Specifications Used together (provided with Board). XM2A-0901 XM2S-0911-E 9-pin male For 9-pin socket, metric screws, ESD countermeasures The following connector connects to an IBM PC/AT or compatible Name Socket Hood Model Specifications Used together. XM2D-0901 XM2S-0913 9-pin male For 9-pin socket, inch screws IBM PC/AT or compatible (9-pin, male) RS-232C port on Serial Communications Board CQM1H CPU Unit Hood: XM2S-0913 Socket: XM2D-0901 (9-pin, female) Recommended cable Hood: XM2S-0911-E Socket: XM2A-0901 Hood and Socket provided with Board. Recommended Cables UL2464 AWG28 5P IFS-RVV-SB (UL-approved, Fujikura Ltd.) AWG28 5P IFVV-SB (not UL-approved, Fujikura Ltd.) UL2464-SB (MA) 5P 28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.) CO-MA-VV-SB 5P 28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.) 44 Section Application Procedure 4-4 4-4 Host Link Communications 4-4-1 Protocol Host Link communications are executed by means of an exchange of commands and responses between the host computer and the PC. The command or response data that is transferred in one exchange is known as a frame and one frame can contain up to 131 characters of data. The frame formats for Host Link commands transmitted from the host computer and responses returned from the PC are described below. The PC automatically returns an ASCII-code response when it receives an ASCII-code command from the host computer. The host computer must have a program that controls the transmission and reception of the commands and responses. Command Frame Format @ When transmitting a command from the host computer, prepare the command data in the format shown below. x 101 x 100 Node No. Header code Text FCS ↵ Terminator The header code and text depend on the Host Link command being transmitted. When a compound command is transmitted, there will be a second sub-header code. The FCS (Frame Check Sequence) code is calculated at the host computer and set in the command frame. The FCS calculation is described later in this section. The command frame may be up to 131 characters long. A command of 132 characters or more must be divided into more than one frame. To split the command, use a carriage return delimiter (↵, CHR$(13)) instead of a terminator. A terminator must be used at the end of the last frame. When dividing commands such as WR, WL, WC, or WD that execute write operations, be careful not to divide into separate frames data that is to be written into a single word. You must divide frames so that they coincide with the divisions between words. Item @ Function An “@” symbol must be placed at the beginning of every command. Destination Identify the PCs by the Host Link node numbers (0 to 31) set in DM Node No. 6558 and DM 6553 of the PC Setup. Header code Set the 2-character command code. x 101 x 100 Node No. Set the command parameters. FCS Set a 2-character Frame Check Sequence code. Terminator Set two characters, “” and the carriage return (CHR$(13)) to indicate the end of the command. A normal response from the PC is returned in the format shown below. Prepare a program at the host so that the response data can be interpreted and processed. Normal Response Frame Format @ Text x 161 x 160 Header code End code Text FCS ↵ Terminator The header code and text depend on the Host Link command that was received. The end code indicates the completion status of the command (e.g., whether or not an error has occurred). 45 Section Connections 4-4 When the response is longer than 131 characters, it will be divided into more than one frame. A carriage return delimiter (↵, CHR$(13)) instead of a terminator will automatically be set at the end of the frame. A terminator will be set at the end of the last frame. Item Error Response Frame Format Function @ An “@” symbol is placed at the beginning of every response. Local Host Link Node No. The PC’s Host Link node number set in DM 6553 or DM 6558 of the PC Setup. Header code The 2-character command code is returned. End code The status of command execution is returned (normal end code). Text The results of the command are returned. FCS The 2-character Frame Check Sequence code is returned. Terminator Two characters, “” and the carriage return (CHR$(13)) indicate the end of the response. An error response from the PC is returned in the format shown below. Prepare a program at the host so that the response data can be interpreted and processed. @ x 101 x 100 Node No. x 161 x 160 Header code End code FCS ↵ Terminator The header code and text depend on the Host Link command that was received. The end code indicates the completion status of the command (e.g., whether or not an error has occurred). Item FCS (Frame Check Sequence) 46 Function @ An “@” symbol is placed at the beginning of every response. Local Host Link Node No. The PC’s Host Link node number set in DM 6553 or DM 6558 of the PC Setup. Header code The 2-character command code is returned. End code The status of command execution is returned (error code). FCS The 2-character Frame Check Sequence code is returned. Terminator Two characters, “” and the carriage return (CHR$(13)) indicate the end of the response. When a frame is transmitted, an FCS code is placed just before the delimiter or terminator in order to check whether an error has occurred in the transmission. The FCS is 8-bit data converted into two ASCII characters. The 8-bit data is the result of an EXCLUSIVE OR performed on the data from the beginning of the frame until the end of the text in that frame (i.e., just before the FCS). Calculating the FCS each time a frame is received and checking the result against the FCS Section Application Procedure 4-4 that is included in the frame makes it possible to check for data errors in the frame. @ 1 0 R R 0 0 Node No. Header code 0 1 4 Text 2 FCS ↵ Terminator FCS calculation range ASCII code Communications Sequence @ 40 1 31 0 30 R 52 1 Calculation result 31 0100 0000 EOR 0011 0001 EOR 0011 0000 EOR 0101 0010 0011 0100 ↓ 4 0001 0010 ↓ Converted to hexadecimal. 2 Handled as ASCII characters. The right to send a frame is called the “transmission right.” The Unit that has the transmission right is the one that can send a frame at any given time. The transmission right is traded back and forth between the host computer and the PC each time a frame is transmitted. An example sequence for multiframe communications between the host computer and PC is described below. Multiframe communications are handled by exchanging delimiters and then using terminators to indicate the last frame. • The host computer sets a delimiter at the end of the first command frame and transmits the frame. • When the PC receives the delimiter, it returns the same delimiter to the host computer. • After receiving the delimiter from the PC, the host computer transmits the next frame. • Delimiters are used to send the rest of the frames. • When the host computer sends the last command frame, it sets a terminator at the end. • When the PC receives a frame with a terminator, it sends the response. • If there was more than one response frame, delimiters would be used here too. Frame 2 (command) Frame 3 (command) Text Text Text FCS Delimiter FCS Delimiter FCS Terminator Frame 1 (command) @ Unit No. Header code Host computer PC Delimiter Delimiter @ Unit No. Header code End code Text FCS Terminator Frame (response) 47 Section Connections 4-4 The TXD(––) instruction can be used to transmit data from the PC’s data area to the host computer. There is no response from the host computer. The TXD(––) instruction will be executed after the response has been transmitted if TXD(––) is executed while a response to a Host Link command is being returned to the host computer. Using the TXD(––) Instruction Host computer PC No response @ Unit No. Header code Text FCS Terminator 4-4-2 Example Programs The following type of program must be prepared in the host computer to receive the data. This program allows the computer to read and display the data received from the PC while a Host Link read command is being executed to read data from the PC. 10 ’CQM1H SAMPLE PROGRAM FOR EXCEPTION 20 CLOSE 1 30 CLS 40 OPEN ”COM:E73” AS #1 50 KEYIN 60 INPUT ”DATA ––––––––”,S$ 70 IF S$=” ” THEN GOTO 190 80 PRINT ”SEND DATA = ”;S$ 90 ST$=S$ 100 INPUT ”SEND OK? Y or N?=”,B$ 110 IF B$=”Y” THEN GOTO 130 ELSE GOTO KEYIN 120 S$=ST$ 130 PRINT #1,S$ ’Sends command to PC 140 INPUT #1,R$ ’Receives response from PC 150 PRINT ”RECV DATA = ”;R$ 160 IF MID$(R$,4,2)=”EX” THEN GOTO 210 ’Identifies command from PC 170 IF RIGHT$(R$,1)<>”” THEN S$=” ”:GOTO 130 180 GOTO KEYIN 190 CLOSE 1 200 END 210 PRINT ”EXCEPTION!! DATA” 220 GOTO 140 Command Transmission Example Program for FCS 48 This example shows a BASIC subroutine program for executing an FCS check on a frame received by the host computer. 400 *FCSCHECK 410 L=LEN(RESPONSE$) 420 Q=0:FCSCK$=” ” 430 A$=RIGHT$(RESPONSE$,1) 440 PRINT RESPONSE$,A$,L 450 IF A$=”*” THEN LENGS=LEN(RESPONSE$)-3 ELSE LENGS=LEN(RESPONSE$)-2 460 FCSP$=MID$(RESPONSE$,LENGS+1,2) ’ . ... FCS data received 470 FOR I=1 TO LENGS ’ . .......... Number of characters in FCS Section Application Procedure 4-4 480 Q=ASC(MID$(RESPONSE$,I,1)) XOR Q 490 NEXT I 500 FCSD$=HEX$(Q) 510 IF LEN(FCSD$)=1 THEN FCSD$=”0”+FCSD$ ’FCS result 520 IF FCSD$<>FCSP$ THEN FCSCK$=”ERR” 530 PRINT”FCSD$=”;FCSD$,”FCSP$=”;FCSP$,”FCSCK$=”;FCSCK$ 540 RETURN Note TXD(––) Application Example 1. Normal reception data includes the FCS, delimiter or terminator, and so on. When an error occurs in transmission, however the FCS or some other data may not be included. Be sure to program the system to cover this possibility. 2. In this program example, the CR code (CHR$(13)) is not entered for RESPONSE$. When including the CR code, make the changes in lines 430 and 450. This example shows a program for using the RS-232C port in the Host Link mode to transmit 10 bytes of data (DM 0000 to DM 0004) to a computer. From DM 0000 to DM 0004, “1234” is stored in every word. The default values are assumed for all of the PC Setup (i.e., the RS-232C port is used in Host Link mode, the node number is 00, and the standard communications parameters are used.) 00100 20105 @TXD(––) DM 0000 #0100 #0010 If SR 20105 (the Transmission Ready Flag) is ON when IR 00100 turns ON, ten bytes of data (DM 0000 to DM 0004) will be transmitted. The transmitted data will appear on the host computer’s screen as follows, assuming the text being sent is “1234” in all specified words: @00EX1234123412341234123459*CR Communications Control Signals and Communications Timing The PC Setup has a setting that can be used to enable CTS control. If CTS control is enabled, processing will be placed on standby until the CS input turns ON after the RS output ON signal is sent for a transmission from the Serial Communications Board. Connect the RS output from the host to the CS input on the Board and perform flow control at the host. 49 Section Connections Setting a Transmission Delay A transmission delay can be set in the PC Setup to create a minimum interval between sending a response from the PC to a Host Link command until the beginning of sending the response to the next command. The delay is not used in the response to the first command. The delay will affect responses to other commands only if the normal time for the response comes before the time set for the transmission delay has expired. If the delay time has already expired when the next command is received, the response will be spent immediately. If the delay time has not expired, the response will be delayed until the time set for the transmission delay has expired. The operation of the transmission delay for responses to host commands is illustrated below. Transmission delay Transmission delay Response sent Response to 1st command 4-4 Response sent Response to 2nd command Transmission delay Response sent Response to 3rd command Response sent Response to 4th command Time The transmission delay will also be effective in PC-initiated communications as a minimum interval between sending commands to the host. The delay is not used in sending the first command. The delay will affect other commands only if the time set for the transmission delay has not expired when the next command is ready to be sent. If the delay time has already expired when the next command is ready, the command will be spent immediately. If the delay time has not expired, the command will be delayed until the time set for the transmission delay has expired. The operation of the transmission delay for PC-initiated communications is illustrated below. Transmission delay Transmission delay Command sent 1st TXD(––) command 50 Command sent 2nd TXD(––) command Transmission delay Command sent 3rd TXD(––) command Command sent 4th TXD(––) command Time Section Application Procedure 4-4 4-4-3 Host Link Commands The Host Link commands listed in the following table can be sent to the CQM1H for Host Link communications. Refer to the CQM1H-series Programming Manual for details. PC mode Header code Name RR RUN Valid MON Valid PRG Valid IR/SR AREA READ RL Valid Valid Valid LR AREA READ RH Valid Valid Valid HR AREA READ RC Valid Valid Valid TC PV READ RG Valid Valid Valid TC STATUS READ RD Valid Valid Valid DM AREA READ RE Valid Valid Valid EM AREA READ RJ Valid Valid Valid AR AREA READ WR Not valid Valid Valid IR/SR AREA WRITE WL Not valid Valid Valid LR AREA WRITE WH Not valid Valid Valid HR AREA WRITE WC Not valid Valid Valid TC PV WRITE WG Not valid Valid Valid TC STATUS WRITE WD Not valid Valid Valid DM AREA WRITE WE Not valid Valid Valid EM AREA WRITE WJ Not valid Valid Valid AR AREA WRITE R# Valid Valid Valid SV READ 1 R$ Valid Valid Valid SV READ 2 R% Valid Valid Valid SV READ 3 W# Not valid Valid Valid SV CHANGE 1 W$ Not valid Valid Valid SV CHANGE 2 W% Not valid Valid Valid SV CHANGE 3 MS Valid Valid Valid STATUS READ SC Valid Valid Valid STATUS WRITE MF Valid Valid Valid ERROR READ KS Not valid Valid Valid FORCED SET KR Not valid Valid Valid FORCED RESET FK Not valid Valid Valid MULTIPLE FORCED SET/RESET KC Not valid Valid Valid FORCED SET/RESET CANCEL MM Valid Valid Valid PC MODEL READ TS Valid Valid Valid TEST RP Valid Valid Valid PROGRAM READ WP Not valid Not valid Valid PROGRAM WRITE QQ Valid Valid Valid COMPOUND COMMAND XZ Valid Valid Valid ABORT (command only) Valid Valid Valid INITIALIZE (command only) EX Valid Valid Not valid TXD RESPONSE (response only) IC --- --- --- Undefined command (response only) 51 Section Connections 4-4 4-4-4 End Codes The response (end) codes listed in the following table are returned in the response frame for Host Link commands. When two or more errors occur, the end code for the first error will be returned. End code 00 Contents Probable cause Corrective measures Normal completion No problem exists. Not executable in RUN mode Not executable in MONITOR mode The command that was sent cannot be executed when the PC is in RUN mode. The command that was sent cannot be executed when the PC is in MONITOR mode. 03 UM write-protected The PC’s UM is write-protected. 04 Address over The program address setting in an read or write command is above the highest program address. 13 FCS error The FCS is wrong. 14 Format error 15 Entry number data error The command format is wrong, or a command that cannot be divided has been divided, or the frame length is smaller than the minimum length for the applicable command. The data is outside of the specified range or Correct the data and transfer the too long. command again. 16 Command not supported 18 Frame length error 01 02 Hexadecimal data has not been specified. The operand specified in an SV Read or SV Change command does not exist in the program. --Check the relation between the command and the PC mode. Turn OFF pin 1 of the CPU Unit’s DIP switch (SW1). Check the program. Check the FCS calculation method. If there was influence from noise, transfer the command again. Check the format and transfer the command again. Check search data or the search starting point. The maximum frame length of 132 bytes was Check the command and divide it exceeded. into multiple frames if necessary. If the frame exceeds 280 bytes, the Reception Overflow Flag will be turned ON and there will not be a response. The read SV exceeded 9,999, or an I/O memory batch read was executed when items to read were not registered for compound command. The UM is write-protected. 19 Not executable 23 User memory protected A3 Aborted due to FCS error in transmission data A4 Aborted due to format error in transmission data Aborted due to entry number data error in transmission data Turn OFF the write-protection An FCS error occurred in the second or later Correct the command data and transfer the command again. frame, or there were two bytes or less of data in an intermediate or final frame for multiple writing. The command format did not match the number of bytes in the second or later frame. There was an entry number data error in the second or later frame, a data length error, or data was not set in hexadecimal. Aborted due to frame length error in transmission data The length of the second and later frames exceeded the maximum of 128 bytes. A5 A8 52 Register items to read before attempting batch read. Section Application Procedure 4-5 A response will not be received with some errors, regardless of the command. These errors are listed in the following table. Error Parity, overrun, or framing error during command reception. (Same even for commands address to other Units.) PC operation The Communications Error Flag will be turned ON, an error code will be registered, and receptions will be reset. (The error will be cleared automatically if communications restart normally.) The Communications Error Flags are as follows: Peripheral port: AR 0812 Built-in RS-232C port: AR 0804 Serial Communications Board port 1: IR 20104, Serial Communications Board port 2: IR 20112 The command will be discarded. A command is received that does not have the @ character at the beginning of the first frame. Incorrect node number (Not a local unit or over The command will be discarded. 31) The data in an intermediate or final frame for An FCS error will occur. multiframe writes is 2 bytes or longer. 4-5 Changes from Previous Products There are differences between Host Link Systems created using the CQM1Hseries Serial Communications Boards in comparison to Host Link Systems created with Host Link Units and CPU Units in other PC product series. These differences are described in this section. 4-5-1 RS-232C Ports Take the following differences into consideration when changing from an existing Host Link System to one using an RS-232C port on a CQM1H-series CPU Unit or Serial Communications Boards. Previous products C-series Host Link Units Model number 3G2A5-LK201-E C500-LK203 3G2A6-LK201-E Changes required for CQM1H-series product Wiring The connector has been changed from a 25-pin to a 9-pin connector. The CQM1H-series products do not support the ST1, ST2, and RT signals and wiring them is not required. Other The following changes are necessary for systems that sync with ST1, ST2, and RT. Synchronized transfers will no longer be possible. Half-duplex transmissions will be possible with the CQM1H-series product, but the host computer’s communications program, hardware, or both will need to be altered. The following changes are necessary for systems that did not sync with ST1, ST2, and RT. C200H-LK201 The connector has been changed from a 25-pin to a 9-pin connector. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CQM1H command specifications. (See note.) It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CQM1H command specifications. (See note.) 53 Section Connections Previous products C-series CPU Units Model number SRM1 4-5 Changes required for CQM1H-series product Wiring Other No changes have been made in wiring. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. No changes have been made in wiring. No changes have been made in wiring. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. CVM1/CV-CPU No changes have been made in wiring. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. CV500-LK201 Port 1: The connector has been changed from a 25-pin to a 9-pin connector. The following changes are necessary for half-duplex transmissions that use CD. CPM1 CPM1A CPM2A/CPM2C CQM1-CPU-E C200HS-CPU-E C200HX/HG/HECPU-E CS1-series CPU Unit CS1-series Serial Communications Board or Unit CVM1 or CV-series CPU Units CVM1 or CV-series Host Link Unit C200HW-COM-E CS1G/H-CPU CS1W-SCB21/41 CS1W-SCU21 Port 2 set for RS-232C: The SG signal has been changed from pin 7 to pin 9. Check the system for timing problems when using SEND(90), RECV(98), or CMND(––) to initiate communications from the PC or timing problems in sending commands from the host computer. If necessary, switch to full-duplex transmissions. The following changes are necessary for full-duplex transmissions that do not use CD. Half-duplex It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode Host Link commands is different for C-series Host Link Units and CQM1H-series Serial Communications Boards. A host computer program previously used for C-series Host Link Units may not function correctly if used for CQM1H-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. 54 Section Application Procedure 4-5 4-5-2 RS-422A/485 Ports Take the following differences into consideration when changing from an existing Host Link System to one using an RS-422A/485 port on a CQM1H-series Serial Communications Board. Previous products C-series Host Link Units Model number 3G2A5-LK201-E C200H-LK202 3G2A6-LK202-E C200HX/HG/HE Communications Board C200HW-COM-E CS1-series CPU Unit CS1G/H-CPU CS1-series Serial Communications Board or Unit CS1W-SCB21/41 CS1W-SCU21 CVM1 or CV-series CPU Units CVM1/CV-CPU CVM1 or CV-series Host Link Unit CV500-LK201 Changes required for CQM1H-series product Wiring Wiring pins have been changed as shown below. SDA: Pin 9 to pin 1 SDB: Pin 5 to pin 2 RDA: Pin 6 to pin 6 RDB: Pin 1 to pin 8 SG: Pin 3 to Not connected FG: Pin 7 to pin Connector hood No changes have been made in wiring. No changes have been made in wiring. No changes have been made in wiring. Other It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CQM1H command specifications. (See note.) It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CQM1H command specifications. Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode Host Link commands is different for C-series Host Link Units and CQM1H-series Serial Communications Boards. A host computer program previously used for C-series Host Link Units may not function correctly if used for CQM1H-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. 55 SECTION 5 Protocol Macros This section describes the procedure and other information required to use protocol macros. 5-1 5-2 5-3 5-4 5-5 5-6 5-7 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-1 Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-2 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-3 Using the Protocol Macro Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-4 Storage Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Restrictions in Using the CX-Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protocol Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7-1 Executing Communications Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7-2 Ladder Program Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7-3 Ladder Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 58 58 63 65 65 66 70 76 80 85 85 87 88 57 Section Using Protocol Macros 5-1 5-1 Overview of the Protocol Macro Functions 5-1-1 Protocol Macros The protocol macro function is used to control devices by using the PMCR(––) instruction in the ladder program to execute the data communications sequences (protocols) with the various communications devices, such as generalpurpose devices, connected to the RS-232C or RS-422A/485 port. Standard system protocols are provided in the Serial Communications Board for controlling OMRON devices (such as Digital Controllers and Temperature Controllers). Using the Protocol Support Tool called the CX-Protocol, the protocol macro function can be used to create new protocols for commercially available measuring instruments and devices, and to create protocols by modifying one of the standard system protocols. The standard system protocols are also provided with the CX-Protocol. For details on the use of the CX-Protocol and the protocol macro function, refer to the CX-Protocol Operation Manual (W344). 5-1-2 Features The main features of the protocol macro functions are described below. For details, refer to the CX-Protocol Operation Manual (W344). Wide Range of Communications Protocols Communications are possible with virtually any general-purpose external device, provided it has an RS-232C or RS-422A/485 port, supports half-duplex communications, and supports start-stop synchronization. Customized Send and Receive Frames Send frames (command + data and other send frames) and receive frames (response and other frames) can be created and registered according to the communications frame specifications of the external device. Communications-related Functions Error check code calculations, frame length calculations during sending, and ASCII⇔Hexadecimal conversion of numeric data are supported. Send/Receive Monitoring Receive wait monitoring, receive completion monitoring, and send completion monitoring are supported. If monitoring times are exceeded, either send/receive processing can be terminated or retry processing can be performed. Retry Processing Send/receive retry processing can be automatically executed when an error occurs, simply by setting the number of retries. PC Read/Write Variables in Send Frames and Receive Frames Variables for reading PC memory can be included in the send frames. These can be used as destination addresses or data when reading PC data. Variables for writing to PC memory can be also included in the actual receive frames. These can be used to write the contents of destination addresses or data to the PC during reception. Switch 1:N Communications or the Data Write Destinations Using Repeat Processing Repeat processing (repeat counters) for send/receive processing can be specified in communications sequences. This enables the same data to be sent by switching destination addresses during communications 1:N (N = 32 max. due to restrictions in the physical layer) or by switching the PC memory write destination addresses during data reception. PC Interrupts During Data Reception An interrupt can be created in the PC’s CPU Unit during data reception, and an interrupt program can be executed in the CPU Unit. Next Process Switching According to Receive Messages The contents of up to 15 expected receive messages can be compared with the message actually received to determine the next process. 58 Section Using Protocol Macros 5-1 Protocol Macro Function Specifications Item Number of protocols (20 max.) Number of sequences (1,000 max.) Per protocol Number of sequences Number of messages Number of reception matrixes Protocol data memory Description Can be created and registered with the Protocol Support Tool (CX-Protocol). 60 max. 300 max. 100 max. Communications mode Flash memory in the Serial Communications Board (Retained even when the power supply to the PC is turned OFF.) Using the CPU Unit’s PMCR(––) instruction (specifying the sequence number) Half-duplex Synchronous mode Start-stop synchronization (asynchronous mode) Baud rate (see note) RS-232C port and RS-422A/485 ports: 1,200/2,400/4,800/9,600/19,200 bps Sequence execution condition Communications distance (see note) Connection configuration Number of connected Units Maximum number of data exchange words between PC and protocol macro function Operand setting Default setting: 9,600 bps RS-232C port: 15 m max. RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using a Converting Link Adapter.) RS-422A/485 port: 1:N (N = 32 Units max.) 32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection) 127 words Including the word that specifies the number of words (1 word) Link word setting 128 words O1, O2, I1, and I2: 128 words total Direct setting 128 words Maximum number of words per data attribute 59 Section Using Protocol Macros Item Sequence contents (step common parameters) 5-1 Description Number of steps per sequence Transmission control parameters Response notification method (operand) 16 max. X-on/X-off flow, RTS/CTS flow, delimiter control, or contention control, and modem control can be selected. Scan notification or interrupt notification (i.e., writing the receive data in the I/O memory area specified in the 3rd operand of the PMCR(––) instruction) can be selected. Scan notification: Writes the receive data to I/O memory during CPU Unit scanning. Monitoring time during send/receive processing Link word setting 60 Interrupt notification: Writes the receive data to I/O memory as soon as it is received, and at the same time specifies the execution of the interrupt program for the CPU Unit. Scan method Yes (fixed) Interrupt Yes notification Interrupt Yes notification for reception case number Receive wait, receive completion, or send completion can be monitored. Setting range: 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 min Area in which data is exchanged between the CPU Unit and the Serial Communications Board during Serial Communications Board refreshing. Two areas are possible for each device: An area for storing receive data and an area for storing send data. Section Using Protocol Macros Item Step contents 5-1 Description Commands Repeat counter Retry count Send wait time With or without response write (operand) Next processing Error processing Send message Send only (SEND), receive only (RECEIVE), or send and receive (SEND&RECEIVE) 1 to 255 times 0 to 9 (Only when the command is SEND&RECEIVE) 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 min (Only when the command is SEND or SEND&RECEIVE) When receive processing is completed (when the receive data is stored in the area specified in the 3rd operand of the PMCR(––) instruction), whether or not to store the received messages can be selected. When a step has ended normally, End (sequence completed), Next (proceed to the next step No.), Goto (go to the specified step No.), or Abort (interrupt the step and terminate that sequence) can be selected. When a step has ended abnormally, End, Next, Goto, or Abort can be selected. Consists of a header (*1), address (*2), length, Data sent to the data (*2), error check code (*3), and terminator specified address when the command (*1). is SEND or For an explanation of *1, *2, and *3, see the SEND&RECEIVE. following pages. Receive message Data sent from the specified address when the command is RECEIVE or SEND&RECEIVE. Reception matrix When the command is RECEIVE or SEND&RECEIVE, sets the expected receive messages (15 max.), and switches to the next processing according to the message received. Specifies the receive messages and the next processing for each of cases No. 00 to No. 15. Of the maximum 16 cases, one case must be set as “Other” in the receive messages (in addition to the set receive messages). Note The baud rate and the communications distance sometimes depend on the remote device. 61 Section Using Protocol Macros Item Message contents *1: Header and terminator data attributes *2: Data attributes of addresses and data in send/ receive messages 5-1 Description Constant ASCII data, hexadecimal data, or control code Constant Variables ASCII data, hexadecimal data, or control code (with an address, no control code is possible) No conversion, conversion to ASCII data, or conversion to hexadecimal data (the read/write direction can be specified) Desig(X, Y) nation X: Effective address (where read from, or where written to) method Y: Data size (1 to 256) X Note The data size is the number of bytes on the transmission path. Word Word read (I/O Specify using Set leading designation memory to address + n the 2nd opersend data) (The linear exand of the pression aN + PMCR(––) b, including reinstruction. peat counter Specify using N, is also posa link word. sible for n.) I/O memory direct designation Word write (re- Specify using ceive data to the 3rd operI/O memory) and of the PMCR(––) instruction. Specify using a link word. I/O memory direct designation Y Wild card * Repeat counter Linear expression including repeat counter N Wild card * Word designation 62 aN + b Any data or address can be received (only in receive messages) a: 0 to 255; b: 1 to 255 N: Repeat counter value Can be received regardless of the length (only in receive messages) Word read (I/O Specify using Set leading memory to address + n the 2nd opersend data) (The linear exand of the pression aN + PMCR(––) b, including reinstruction. peat counter Specify using N, is also posa link word. sible for n.) I/O memory direct designation Section Using Protocol Macros Item Message contents (continued) 5-1 Description *3: Error check codes Maximum length of send/receive messages LRC, LRC2, CRC-CCITT, CRC-16, SUM, SUM1, and SUM2 can be calculated. 256 bytes. Maximum number of data attributes registered in one message 96 attributes (see note 1) Maximum number of 30 attributes (see note 2) write data attributes registered in one message Trace function A total of up to 1,700 bytes (characters) of time-series data can be traced in send and receive messages. Changes to the step No. and control signals such as RTS and CTS can also be traced. Note 1. The CX-Protocol can be used to register up to 96 attributes per message. 2. A macro syntax error will occur when the protocol macro is executed if more than 31 write attributes are registered in one message. 5-1-3 Using the Protocol Macro Function The following three methods are available for using the protocol macro function. Using the Standard System Protocols CPU Unit When connecting OMRON devices, data is sent and received between the CQM1H-series CPU Unit and these devices by specifying the sequence number of the standard system protocol provided in the Serial Communications Board and CX-Protocol, and executing the sequence using the PROTOCOL MACRO instruction (PMCR(––)). The CX-Protocol is not required to use the standard system protocols. Serial Communications Board Standard system protocol Sequence No. 001 Sequence number Messages Sequence No. specification Step 0 *Send/receive messages are stored in the area one or more words after the send data address or the receive data address specified in the PMCR(––) instruction. Step 1 RS-232C or RS-422A/485 OMRON devices I/O memory Shared memory I/O refreshing Note The devices for which standard system protocols are provided are listed below. For details, refer to 5-7 Using Protocol Macros. Digital Controllers (E5K, ES100), Temperature Controllers (E5ZE, E5J), Intelligent Signal Processors (K3T), Bar Code Readers (V500/V520), Laser Micrometers (3Z4L), Visual Inspection Units (F200/F300/F350), ID Controllers (V600/V620), Hayes Modem AT Command, and devices supporting the CompoWay/F protocol. 63 Section Using Protocol Macros Modifying Standard System Protocols 5-1 If there is no standard system protocol for the required OMRON product or you wish to modify part of the protocol, you can use the CX-Protocol to modify a standard system protocol, transfer this as a separate communications sequence to the Serial Communications Board, and execute the PMCR(––) instruction. Modifying and transferring standard system protocols Serial Communications Board CPU Unit Sequence No. specification Modified standard system protocol Command execution (SEND, RECEIVE, SEND&RECEIVE) Messages Step 0 Sequence number Step 1 Step 2 RS-232C or RS-422A/485 General-purpose external device I/O memory Shared memory I/O refreshing Creating a New Protocol When connecting a general-purpose external device that has an RS-232C or RS-422A/485 port, use the CX-Protocol to create a new protocol containing the communications specifications for the general-purpose external device, transfer these specifications to the Serial Communications Board, and execute the PMCR(––) instruction. Creating and transferring a new protocol Serial Communications Board CPU Unit Newly created protocol Sequence number Step 0 Sequence No. specification Command execution (SEND, RECEIVE, SEND&RECEIVE) Messages Step 1 RS-232C or RS-422A/485 Step 2 General-purpose external device I/O memory Shared memory I/O refreshing 64 Section Using Protocol Macros 5-2 In this manual, the protocol structure is explained in simple terms, and examples are given of the use of the PMCR(––) instruction when controlling OMRON devices using standard system protocols. For details on the protocols, the method of modifying the standard system protocols, and the method of creating new sequences, refer to the CX-Protocol Operation Manual (W344). 5-1-4 Storage Memory The protocol macros are stored in flash memory in the Serial Communications Board and will be saved even if power to the CQM1H is turned OFF. The PC Setup settings for the Serial Communications Board are stored in memory in the CPU Unit with a battery backup. 5-2 Restrictions in Using the CX-Protocol There are some restrictions in using the CX-Protocol to manipulate protocols or perform other operations for the CQM1H-series Serial Communications Board. These restrictions are described below. • Pin 8 on the DIP switch on the front of the CQM1H-series CPU Unit must be turned ON to use the CX-Protocol. While pin 8 is ON, you will not be able to use any of the CPU Unit or Board ports for the CX-Programmer, SYSMAC-CPT, or SYSMAC Support Software. • The model of PC must be set to the C200HG and the model of CPU Unit must be set to the CPU43. • Refer to the following table for details and for other restrictions. Unless specified, the functionality of the CX-Protocol will be the same as for the C200HX/ HG/HE. Item Restriction CQM1H DIP switch settings Turn ON pin 8 on the DIP switch on the front of the CQM1H-series CPU Unit before attempting to use the CX-Protocol. You will not be able to use the CX-Protocol while pin 8 is OFF. Procedure Turn ON pin 8 before using the CX-Protocol. Turn OFF pin 8 after you are finished using the CX-Protocol. While pin 8 is ON, you will not be able to use any of the CPU Unit or Board ports for the CX-Programmer, SYSMAC-CPT, or SYSMAC Support Software. Always turn OFF pin 8 after you are finished using the CX-Protocol. PC model setting (to create new protocols) Set the model of PC to the C200HG and the model of CPU Unit to the CPU43-E. 1. Select New from the File Menu. 2. Select C200HG from the Change PLC Dialog Box. 3. Select CPU43-E from the Settings Dialog Box. Transferring protocols to the computer You will not be able to upload the data for the standard system protocols from the Board to the computer. If an attempt is made, the transfer will be canceled and the following message will appear. (The standard system protocol data in the Board will not be affected.) --- Decompiler has detected an error. No protocol data or invalid protocol list on upload. It is likely that the previous download was interrupted or the PMSU memory has been cleared/damaged. Try to download a valid protocol and retry upload. You will be able to download protocol data from the computer to the Board (including data for the standard system protocols) and will then be able to upload the data. To modify the standard system protocols for your applications, modify the data provided with the CX-Protocol and then download the data to the Board. 65 Section Using Protocol Macros Item Communications port settings on the Board Restriction Procedure Use the same communications port settings for the Board as those used for the C200HX/HG/HE. The communications port names will be as follows: Communications Port A will be port 1 on the Board. Communications Port B will be port 2 on the Board. I/O memory operations: PLC Memory Window 5-3 Use I/O memory addresses only within the ranges supported by the CQM1H. Do not attempt to edit addresses IR 256 and higher in the IR Area (displayed without the prefix) even though these addresses will be displayed. The following restrictions apply when transferring I/O memory. 1. Double-click the PC icon while online. 2. Double-click the Communications Port A or Communications Port B Icon in the Project Window. 3. Make the settings in the Communications Port Settings Dialog. 1. Click the PC icon and select Memory from the pop-up menu. The PLC Memory Window will be displayed. 2. Select the I/O memory areas and address to be displayed or edited in the Data Area Workspace. 1. Double-click the memory area in the Data Area Workspace. The PLC Data Table will be displayed. When transferring from the computer to the PC, do not select All. Use Selection or Range and specify a range 2. Specify the range of addresses to be that lies between IR 000 and IR 255. transferred if necessary. Error log I/O tables When transferring from the PC to the computer, do not select All. Use Visible area only or Selection and specify a range that lies between IR 000 and IR 255. The error log cannot be used. If it is displayed, the contents will not agree with the error log in the CQM1H. The I/O tables are not necessary for the CQM1H and will be disabled. If an attempt is made to create I/O tables, the following message will be displayed and the I/O tables will not be created. 3. Select Transfer to PLC via Online or Transfer from PLC via Online from the Online Menu. ----- ! The PLC does not contain an IO Table. 5-3 Application Procedure 1, 2, 3... 1. Turn OFF the power to the PC. 2. Install the Board. 3. Connect the system. Connect the external devices using RS-232C or RS-422 cable. The settings of the TERM and WIRE switches on the front panel of the Board will need to be changed if the RS-422A/485 port on the Serial Communications Board is used. Serial Communications Board Terminating resistance ON External device External device External device Terminating resistance ON External device Connect a Programming Console, the CX-Programmer, or the CX-Protocol to the CPU Unit as required. 4. Turn ON power to the PC. 5. Set the PC Setup settings for the Serial Communications Board. Use the Programming Console, CX-Programmer, or CX-Protocol to set the settings in DM 6550 to DM 6559. 66 Section Using Protocol Macros 5-3 Note The PC Setup settings for the Serial Communications Board are read constantly during PC operation. It is not necessary to restart the PC after changing these settings. The default settings are shown in the following table. These are the standard settings for protocol macros. Port 1 DM 6555 Port 2 DM 6550 Bit(s) Setting Function 00 to 03 0 Hex Standard port settings (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 04 to 07 08 to 11 12 to 15 ----6 Hex ------- Not used. Not used. Communications mode: Protocol macro Baud rate setting disabled. Frame format setting disabled. Not used. DM 6556 DM 6551 DM 6557 DM 6552 00 to 07 08 to 15 00 to 15 DM 6558 DM 6553 00 to 15 --- Not used. DM 6559 DM 6554 00 to 15 --- Not used. 6. Run the system as described below in Using Standard System Protocols or in Using User-created Protocols. Using Standard System Protocols Executed with PMCR(––) CPU Unit Uses standard system protocol No. 600 External device Example: K3N Series Digital Panel Meter Serial Communications Board 1, 2, 3... 1. Setting the Send Data Refer to information on the 2nd operand of PMCR(––) in Appendix B CompoWay/F Master Protocol and set the number of send data words in S, and set the send data starting in S+1. 2. Coding PMCR(––) The following example shows how to use a Serial Communications Board to read the present value for a K3N-series Digital Panel Meter using the CompoWay/F Master standard system protocol sequence No. 600: Send/Receive with ASCII Conversion and Response. Input condition Protocol Macro Executing Flag PMCR #1600 DM0000 1: Use port 1, 600: Sequence No. 600 First word of send data DM1000 First storage word for receive data If the input condition turns ON when the Protocol Macro Executing Flag (IR 20708 for Port 1) is OFF, communications sequence No. 600 of the standard system protocol in the Serial Communications Board is called, and data is sent and received via port 1 of the Serial Communications Board. 67 Section Using Protocol Macros 5-3 Send Data S:D00000 D00001 D00002 D00003 D00004 D00005 D00006 0007 0000 0101 000C C000 0000 0001 7 words from D00000 to D00006 K3N node No. : 00 CompoWay/F command “0101” (reads the K3N present value) Number of send bytes CompoWay/F command send data (Variable type, read start address, 00, number of elements) Receive Data D:D00010 D00011 D00012 D00013 0004 4 words from D00010 to D00013 Response code is stored. The read data (in this case, the present value of K3N) is stored. 3. Executing the PMCR(––) instruction 4. For details on confirming operation, see Section 12 Tracing and I/O Memory Monitoring in the CX-Protocol Operation Manual (W344). • Transmission Line Tracing The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced. • I/O Memory Monitoring Monitors send/receive data and the status of the various flags. Using User-created Protocols CX-Protocol CPU Unit Use the CX-Protocol to create protocols. PMCR(––) External device Serial Communications Board Section references in the following procedure refer to the CX-Protocol Operation Manual (W344). 1, 2, 3... 1. For details on designing protocols, see Section 4 and Section 5. a) Create a communications sequence status transition chart. b) From the status transition chart, divide the processing contents into sequence steps. c) Determine the send/receive message contents. 2. Use the CX-Protocol to create and send a project (protocol data). a) Creating a new project: See 5.1 Creating a New Project or Protocol. b) Creating a new communications sequence: See 5.2 Creating a New Sequence or 7.1 Setting a Sequence. c) Creating steps: See 5.2 Creating a New Sequence and 8.1 Setting a Step. d) Creating messages: See 9.1 Setting a Message. Note After creating messages, steps can also be created by specifying message names. 68 Section Using Protocol Macros 5-3 e) Transferring the created project to the Board: See 11.1 Transferring and Reading Protocol Data between Personal Computers and Serial Communications Boards. 3. Create the ladder program. a) Setting Send Data • Specifying Operands Set the send data in the I/O memory after the S+1 operand of the PMCR(––) instruction. Set the number of send data words (including S itself) in S. • Direct Designations Set the send data in the I/O memory specified by the read variables in the send message. • Specifying Link Words Set the send data in the O1 or O2 area of the Link Word Area. b) Coding PMCR(––) Input condition Protocol Macro Executing Flag PMCR #1100 DM0000 DM1000 1: Use port 1, 600: Sequence No. 100 First word of send data First storage word for receive data If the input condition turns ON when the Protocol Macro Executing Flag (IR 20708 for port 1) is OFF, communications sequence No. 100 registered in the Serial Communications Board is called, and data is sent and received via port 1 of the Serial Communications Board. The amount of send data depends on the number of words specified in DM 0000 (the number of words after DM 0001 plus 1 for DM 0000 itself), and is sent from the next word after DM 0001. S: DM 0000 Number of words Send data Number of send words plus 1 for DM 0000 Number of words The receive data is stored in consecutive words beginning with DM 1000, and the number of words actually stored in DM 1000 (the number of words after DM 1001 plus 1 for DM 1000 itself) is stored. D: DM 1000 DM 1001 Number of words Receive data Number of receive words plus 1 for DM 1000 Number of words c) Execute PMCR(––) 4. For details on the confirming operation, see Section 12 Tracing and I/O Memory Monitoring. • Transmission Line Tracing The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced. • I/O Memory Monitoring Monitors send/receive data and the status of the various flags. 69 Section Using Protocol Macros 5-4 5-4 Connections This section describes the connections for protocol macros. Up to 32 nodes can be used for 1:N connections. Port RS-232C Configuration Schematic diagram 1:1 RS-232C RS-232C interface NT-AL001-E Resistance ON NT-AL001-E 5-V power RS-422A/485 RS-232C Resistance ON RS-232C interface NT-AL001-E RS-422A/485 RS-232C Resistance ON RS-232C RS-422A/ 485 interface RS-422A/485 interface 1:N NT-AL001-E RS-232C RS-422A/485 Resistance ON Resistance ON 3G2A9-AL001 NT-AL001-E RS-422A/485 interface RS-422A RS-232C Resistance/485 ON Resistance ON NT-AL001-E RS-232C interface NT-AL001-E RS-232C Resistance RS-232C ON RS-232C RS-422A/485 RS-232C Resistance ON 5-V power RS-422A/485 1:1 RS-422A/485 interface RS-422A/485 NT-AL001-E RS-422A/485 70 RS-232C interface RS-232C Resistance ON 5-V power Section Using Protocol Macros Port RS-422A/485 Configuration 5-4 Schematic diagram 1:N RS-422A/485 interface RS-422A/485 Resistance ON Resistance ON RS-422A/485 interface 3G2A9-AL001 Resistance ON RS-422A/485 Resistance ON RS-232C interface NT-AL001-E RS-232C Resistance ON RS-422A/485 RS-232C Resistance ON RS-232C 5-V power Note 1. The maximum cable length for RS-232C is 15 m. 2. The maximum combined cable length for RS-422A/485 is 500 m including branch lines. 3. The maximum cable length is limited to 2 m when an NT-AL001-E Link Adapter is connected. 4. Branch lines must be a maximum of 10 m long. Connection Examples The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 2-3 Wiring for actual wiring methods. Connecting RS-232C Ports 1:1 Connections to E5CK Controller Serial Communications Board Signal Pin FG SD RD RTS CTS DSR DTR SG RS-232C Shield OMRON E5CK Controller Terminal Signal SD RD SG Terminal block D-sub, 9-pin connector (male) 71 Section Using Protocol Macros 5-4 Connecting a Host Computer with NT-AL001-E Converting Link Adapters Serial Communications Board RS-232C NT-AL001-E Link Adapter Signal Pin Shield Pin Signal RS-232C Interface FG SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) NT-AL001-E Link Adapter Signal Pin Pin RS-422A NC SD RD RTS CTS 5V DSR DTR SG Signal Signal Pin Computer RS-232C NC SD RD RTS CTS 5V DSR DTR SG Signal FG SD RD RS-232C RTS Interface CTS DSR DTR SG (See note) Terminal block D-sub, 9-pin connector (male) Terminal block D-sub, 9-pin connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF (4-wire) Pin 4: OFF Pin 5: OFF Pin 6: ON DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF (4-wire) Pin 4: OFF Pin 5: OFF Pin 6: OFF D-sub, 9-pin connector (female) 5-V (+) power (–) Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m Connections to a Modem Modem FG SD RD RTS CTS DSR SG CD Serial Communications Board RS-232C port FG SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) ST2 RT DTR CI ST1 D-sub, 25-pin connector 72 Section Using Protocol Macros 5-4 1:N Connections Using RS-232C Ports Device supporting RS-422A/485 communications (4-wire) Serial Communications Board NT-AL001-E Signal Pin RS-232C Pin Signal Signal Pin Shield RS-232C interface FG SD RD RTS CTS 5V DSR DTR SG NC SD RD RTS CTS 5V DSR DTR SG Signal RS-422A /485 interface Device supporting RS-422A/485 communications (4-wire) Signal (See note) D-sub, 9-pin connector (male) RS-422A Shield D-sub, 9-pin Terminal block connector (male) RS-422A /485 interface DIP SW Pin 1: ON Pin 2: ON Terminating resistance Pin 3: OFF 4-wire Pin 4: OFF Pin 5: OFF Pin 6: ON Serial Communications Board RS-232C Signal Pin Shield RS-232C interface FG SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) NT-AL001-E Pin Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG (See note) D-sub, 9-pin Terminal block connector (male) Device supporting RS-422A/485 communications (2-wire) Signal RS-422A /485 interface Device supporting RS-422A/485 communications (2-wire) Signal RS-422A /485 interface DIP SW Pin 1: ON Pin 2: ON Terminating resistance Pin 3: ON 2-wire Pin 4: ON Pin 5: OFF Pin 6: ON Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 73 Section Using Protocol Macros 1:1 Connections Using RS-422A/485 Ports Device supporting RS-422A/485 communications (2-wire) Serial Communications Board Signal Pin Shield Signal Pin /485 interface RS-422A /485 interface Serial Communications Board Signal RS-422A Shield RS-422A /485 interface Hood Hood D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) Serial Communications Board RS-422A Signal Pin Shield Pin Signal RS-422A /485 interface Signal Pin NC SD RD RTS CTS 5V DSR DTR SG Hood D-sub, 9-pin connector (male) Terminating resistance ON 4-wire Terminal block D-sub, 9-pin connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF 74 Computer NT-AL001-E Link Adapter Signal RS-232C FG SD RD RS-232C RTS Interface CTS DSR DTR SG D-sub, 9-pin connector (male) 5-V (+) power (–) Device supporting RS-422A/485 communications (4-wire) Signal RS-422A /485 interface 5-4 Section Using Protocol Macros 5-4 1:N Connections Using RS-422A/485 Ports Device supporting RS-422A/485 communications (2-wire) Serial Communications Board Signal Pin Signal RS-422A/ 485 interface RS-422A/ 485 interface Hood Device supporting RS-422A/485 communications (2-wire) D-sub, 9-pin connector (male) Terminating resistance ON 4-wire Signal RS-422A/ 485 interface Serial Communications Board Signal Pin Device supporting RS-422A/485 communications Shield (4-wire) 3G2A9-AL001 Pin Signal RS-422A/ 485 Interface Signal Signal Pin RS-422A/ 485 interface RS-422A/ 485 interface Hood D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) Signal Pin Terminating resistance ON 4-wire Device supporting RS-422A/485 communications (4-wire) Shield Signal RS-422A/ 485 interface Serial Communications Board NT-AL001-E Link Adapter Signal Pin Pin Signal RS-422A/ 485 Interface Pin D-sub, 9-pin connector (male) Shield Shield Signal FG SD RD RTS CTS NC SD RD RTS CTS 5V DSR DTR SG Hood Terminating resistance ON 4-wire Signal RS-232C Interface DSR DTR SG DIP Switch D-sub, 9-pin conPin 2: OFF, nector (male) otherwise same as below. (+) 5-V (–) power NT-AL001-E Link Adapter Pin DIP Switch Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG Shield Terminal block D-sub, 9-pin connector (male) Shield Signal FG SD RD RTS CTS RS-232C Interface DSR DTR SG (+) 5-V (–) power 75 Section Using Protocol Macros 5-5 5-5 Protocol Structure Protocols consist of communications sequences. A sequence consists of steps. These steps can be repeated, or they can be branched or ended depending on the responses received. A step consists of a command, send/receive messages, processing results, and the next process (which depends on the processing results). Example: Reading the process values for a Temperature Controller Protocol Transmission of process value reading message and reception of response message Communications sequence Step 0 Step 1 Messages A protocol consists of processing sequences (such as reading the process value for a Temperature Controller) for a general-purpose external device. A sequence consists of a group of steps, each of which consists of a send/receive/ control command, send/receive message, processing result, and a next step that depends on the processing results. For example, with a sequence that reads the process value for a Temperature Controller, the sequence sends the send message for the connected Temperature Controller (a character string in which the Process Value Read command is inserted between the header + address and the check code + terminator) and receives the receive message (a character string in which the Process Value Read command response is inserted between the header + address and the check code + terminator). Command Send message (Example: PROCESS VALUE READ command) CPU Unit SEND Header Address Send data Check Terminator code Receive message (Example: Response) RECEIVE Header Address Send data Check code RS-232C or RS-422A/485 Terminator Serial Communications Board General-purpose external device 76 Section Using Protocol Macros 5-5 Depending on the response received, the user can either choose to resend the same send message (retry processing), or to perform the next process (for example, read the process value for a Temperature Controller with a different address). One protocol One-step structure With the SEND, RECEIVE, or SEND&RECEIVE command Sequence No. 000 to 999 (60 sequences max./protocol) Step 0 Step 1 Transmission control parameter Link word setting Step 0 Step 1 Command (see Note 1) Messages (see note 2) Send/receive processing monitoring time Response notification method Y 15 steps max. Retry? Normal end 15 steps max. (See note 3.) N (error) N (no) Message list (see note 2) Send message list Y Repeated N (no) Next process Error processing Next step Header Address Data Check Terminator To specified step Receive message list Sequence end Sequence interrupt Header Address Data Check Terminator Reception matrix list (see note 2) Reception matrix Case No. 15 Case No. 00 Receive message Next process Note 1. The SEND, RECEIVE, or SEND&RECEIVE commands can be used. 2. Three types of reception matrix are available for switching the processing, depending on whether the messages are send messages, receive (wait) messages, or multiple receive (wait) messages. Unlike sequences, these matrixes are managed as lists. 3. Retries are possible on for the SEND&RECEIVE command. Sequence Parameters Parameter Transmission control parameters Link words Monitoring time Response notification method Meaning Control methods, such as flow control Settings for shared words between the PC and the Serial Communications Board. Monitoring time for send/receive processing Timing for writing received data to I/O memory in the PC 77 Section Using Protocol Macros Step Parameters Parameter Command Meaning One of the following: SEND, RECEIVE, or SEND&RECEIVE Messages Send message Receive message Send message and receive message The message sent for SEND. The expected message for RECEIVE. Reception matrix A group of expected messages that can be used to switch to different next processes when RECEIVE or SEND&RECEIVE is used. The message sent and the expected message for SEND&RECEIVE. Repeat counter The number of times to repeat the step (0 to 255). The repeat counter can be used to change send/receive messages. Retry count Used for SEND&RECEIVE to retry the command for errors (0 to 9). Send wait time Used for SEND or SEND&RECEIVE to create a wait time before sending data. Response write enable (for operand specification) Specification of whether or not to write the received data to memory. Next process Specifies the next step or to end the sequence when the current step is completed normally. Error processing Specifies the next step or to end the sequence when the current step ends in an error. Standard System Protocol Example Process Value Read Sequence for E5K Controller Read Protocol Level Sequence Steps 78 5-5 Item Setting Link words Transmission control parameters Response notification method Reception wait time Tr Reception finished wait time Tfr Send finished wait time Tfs --Modem control Step number Repeat counter Command Retry count Send wait time Send message Receive message Response write enable Next process Error process 00 Reset/001 SEND&RECEIVE 3 --SD (00) _1 RV (00) _1 Write End Abort Scan 3s 3s 3s Section Using Protocol Macros Level Send message SD (00) _1 Item Header <h> Terminator <t> Error check code <c> Length <l> Address <a> Message edited 5-5 Setting “@” [2A0D] LRC (horizontal parity) (0) (2 bytes of ASCII) --$ (R (1) ) ,2) <h> + <a> + “1” + “00” + “0000” + <c> + <t> Data Receive message RV (00) _1 Header <h> Terminator <t> Error check code <c> Length <l> Address <a> Message edited “@” [2A0D] LRC (horizontal parity) (0) (2 bytes of ASCII) --& (R (1) ) ,2) <h> + <a> + “00” + “00” + & (W (1) ,4) + <c> + <t> Data Handling Communications Problems for Standard System Protocols The CQM1H-series PCs provide standard system protocols to enable communications with OMRON components without having to create communications sequences. The sequences in the standard system protocols can be executed merely by setting operands for the PMCR(––) instruction. Processing for communications line problems during communications for the standard system protocols are set to normal settings, as shown in the following table. If these settings are not suitable to the application or if improvements are desired, use the CX-Protocol to modify the following settings in the required sequences. For details on the use of the CX-Protocol, refer to the CX-Protocol Operation Manual (W344). Refer to the appendices for the settings in the standard system protocols. Level Sequence parameters Step parameters Item Link words Transmission control parameters Response notification method Reception wait time Tr Reception finished wait time Tfr Send finished wait time Tfs Repeat counter Command Retry count Send wait time Send message Receive message Response write enable Next process Error process Possible changes in settings No reason to change. The monitoring times are set to 3 seconds for most sequences. The settings are different for send-only and receive-only sequences, as well as for sequences that require time for responses. No reason to change. The retry count is general set to 3 retries (4 tries total) for sequences that use the SEND&RECEIVE command. Different settings are used for sequences that have other commands. No reason to change. 79 Section Using Protocol Macros 5-6 5-6 Control Bits, Flags, and Status Information Control bits, flags, and status information for the Serial Communications Board are available in the Inner Board Slot 1 area. The addresses in this area are as follows: Inner Board Slot 1 Area: IR 200 to IR 207 All of the bits in the following table are initialized (cleared) when power to the PC is turned ON, when the mode is changed between PROGRAM and RUN/MONITOR mode, when the STUP(––) instruction is executed to change the serial communications mode, or when the communications port is restarted. The bits are also reset at the timing indicated in the Reset column in the table. Word IR 200 Bits 00 Name and Function Serial Communications Board Hardware Error Flag Turns ON if an error occurs in the Board. Replace the Board if this flag will not turn OFF even after remounting the Board securely or mounting it in a different CPU Unit. 01 Classification System error Set Reset When error occurs Power ON Board Identification Error Flag (hardware error) Replace the Board if this flag turns ON. 02 Protocol Data Error Flag This flag turns ON if an error is detected in the protocol data checksum when the power is turned ON. The ERR indicator on the CPU Unit will also flash and the RDY indicator will flash. 11 This error may occur if the communications connector becomes disconnected or the PC power is turned OFF during protocol data transfer. Use the CX-Protocol to transfer of the protocol data again. Port 2 Protocol Macro Execution Error Flag The flag turns ON when the protocol macros are not supported (error code 1), there is a sequence number error (error code 2), an attempt was made to write data receive data at an illegal address (error code 3), or a protocol data syntax error occurred (error code 4). 12 Port 1 Protocol Macro Execution Error Flag 13 Same as IR 20011. PC Setup Error Flags 14 15 Bit 15 turns ON if a Setup error occurs in the PC Setup settings for the Board. Bit 14 will turn ON if the error is for port 1. Bit 13 will turn ON if the error is for port 2. Correct the PC Setup. The defaults will be used for the settings causing th error. 80 Normal completion of protocol data transfer Start of sequence Power ON Section Using Protocol Macros Word Bits IR 201 00 to 03 Name and Function Port 1 Error Code (Transmission Error Status) When an error occurs during transmissions for a protocol macro, an error code will be output to these bits. 0: Normal operation 1: Parity error Classification Transmission error 5-6 Set Reset When error occurs Start of sequence 2: Framing error Error codes 3 to 7 are not possible for protocol macros. These error codes are the same regardless of the serial communications mode. IR 20104 will also turn ON except when the error code contains all zeros. SEND&RECEIVE retry processing will be performed for any error. 04 If communications are recovered through protocol macro retry processing, the error code will be cleared, but will be maintained even if a different error occurs during the retry. Port 1 Communications Error Flag This flag turns ON when an error occurs in the communications path between the communications port and the external device or when communications parameters are not set correctly. The operation of this flag is the same regardless of the serial communications mode. Details on the error are output as an error code to IR 20100 to IR 20103. 07 12 Sequence This flag turns ON when a sequence has been aborted due status to ABORT in the next process or in the error process. It will be OFF if an abort has not occurred. TransmisPort 2 Error Code (Transmission Error Status) sion error Same as bits IR 20100 to IR 20103, but works together with IR 20112. Port 2 Communications Error Flag 15 Same as bits IR 2014, but works together with IR 20108 to IR 20111. Port 2 Sequence Abort Completion Flag 08 to 11 Port 1 Sequence Abort Completion Flag Save as IR 20107. IR 202 00 to 07 Port 1 Repeat Counter PV (00 to FF hexadecimal) The repeat counter variable N is set. The value is cleared when the sequence execution starts. Sequence status Sequence status When sequence is aborted When error occurs When sequence is aborted When repeat count is refreshed The present value N varies according to the method used to initialize the value. For resets, the variable N is set to 0 when the step is started, and the step is executed according to the set number of times. For holds, the variable N for the present value is held when the step is started, and the step is executed according to the set number of times. IR 203 00 to 07 If the Repeat Counter Setting Value is set to read word R ( ), and 0 is read, then 0 will be stored and this step will be skipped (the next process setting will be ignored), and the sequence will move to the next step (+ 1). For details, refer to the CX-Protocol Operation Manual (W344). Port 2 Repeat Counter PV (00 to FF hexadecimal) Same as IR 20200 to IR 20207. 81 Section Using Protocol Macros Word IR 204 Bits 00 Name and Function Port 1 Tracing Flag Classification Tracing Port 2 Tracing Flag 08 to 11 Same as IR 20400. Port 1 Protocol Macro Error Code The list of error codes is provided at the end of this table on page 85. Start of sequence or end of trace Protocol macro status When error occurs Start of sequence Sequence status When matrix is received If error code 1, 2, 3, or 4 is stored, the Port 1 Protocol Macro Execution Error Flag (IR 20111) will be turned ON, the ERR/ALM indicator on the CPU Unit will flash, and a non-fatal error will occur. When an error occurs, the error code is held until the next sequence starts. The error must be cleared from a Programming Console or other Programming Device after the cause of the error has been eliminated. IR 205 12 to 15 Port 2 Protocol Macro Error Code 00 to 03 Same as IR 20408 to IR 20411, but works together with IR 20112. Port 1 Executed Reception Case No. (code) Reception matrix case numbers 0 to 15 (0 to F hex) are stored for which reception has been completed. The number is cleared when the sequence execution starts. 04 to 07 15 IR 206 00 to 03 The Executed Reception Case No. is stored only when the reception matrix is set using the RECEIVE or SEND&RECEIVE command. If a reception matrix is not set, the case number will be set to 0 (cleared) when another command is executed. Port 1 Completed Step Number Step numbers 0 to 15 (0 to F hex) are stored for the steps for which execution has been completed. IR 204 Port 1 Data Stored Flag 0: No data stored; 1: Data stored in IR 20408 to IR 20411 Port 2 Executed Reception Case No. (code) Same as IR 20500 to IR 20503. IR 205 82 04 to 07 Port 2 Completed Step Number 15 Same as IR 20504 to IR 20507. IR 204 Port 2 Data Stored Flag 0: No data stored; 1: Data stored in IR 20412 to IR 20415 Reset Start of trace According to instructions from the CX-Protocol, this flag is turned ON while time-series data for send and receive messages is being traced. 01 Set 5-6 When step is executed Protocol macro Sequence status When error occurs When matrix is received When step is executed Protocol macro When error occurs Section Using Protocol Macros Word IR 207 Bits Name and Function 00 Port 1 Restart Bit 01 The communications port will be restarted when this bit is turned ON by the user. Port 2 Restart Bit Classification Port status 5-6 Set Reset User-set or STUP(––) After settings are changed and port restarted From CX-Protocol From CX-Protocol Same as IR 20700. 02 Port 1 Continuous Trace Start/Stop Bit The CX-Protocol will start a continuous trace when the bit is turned ON. The trace is ended when the bit is turned OFF. 03 Tracing The CPU Unit will manipulate the Shot Trace Bit and Continuous Trace Bit when trace operations are performed from the CX-Protocol. Do not manipulate these bits directly from a ladder diagram. Port 2 Continuous Trace Start/Stop Bit Same as IR 20702. 04 Port 1 Shot Trace Start/Stop Bit The CX-Protocol will start a one-shot trace when the bit is turned ON. The trace is ended when the bit is turned OFF. At end of short trace The Serial Communications Board will be cleared when the trace buffer becomes full. 05 The CPU Unit will manipulate the Shot Trace Bit and Continuous Trace Bit when trace operations are performed from the CX-Protocol. Do not manipulate these bits directly from a ladder diagram. Port 2 Shot Trace Start/Stop Bit Same as IR 20704. 83 Section Using Protocol Macros Word IR 207 Bits 08 Name and Function Port 1 Protocol Macro Executing Flag (instruction execution) This flag is turned ON when a PMCR(––) instruction (sequence) is executed. The flag will remain OFF if execution fails. Classification Protocol macro status 5-6 Set Reset At instruction execution At completion of execution Step error At compare error after reception Start of sequence Sequence status End of sequence Abort processing User-set User-set Protocol macro status At instruction execution At completion of execution Step error At compare error after reception Start of sequence Sequence status End of sequence Abort processing User-set When the sequence is completed and receive data is written, the flag is turned OFF after all the receive data has been written to I/O memory. This flag is turned OFF when the sequence is completed (either when it is ended by End, or when it is ended by Abort). When the scan response notification method is set for the sequence, first a check is made to see if the received data has been written to I/O memory before the Protocol Macro Executing Flag is turned OFF. 09 Port 1 Transfer Step Error Processing Flag This flag is turned ON when a step has ended abnormally. It is turned OFF if the step ends normally as a result of a retry. 1: Step ended abnormally 0: Step ended normally 10 Port 1 Sequence END Completion Flag This flag is turned ON when a sequence is completed for the next process or for an error process with an END command. Setting END when a sequence has ended normally and setting ABORT when the sequence has ended abnormally enables this flag to be used to determine whether or not the sequence execution has ended normally. 11 1: Sequence ended 0: Sequence not ended Port 1 Forced Abort Bit Protocol processing will be aborted when this bit is turned ON. (Processing may be completed if the bit is turned ON too late.) 12 13 Port 2 Protocol Macro Executing Flag (instruction execution) Same as IR 20708. Port 2 Transfer Step Error Processing Flag Same as IR 20709. 14 Port 2 Sequence END Completion Flag Same as IR 20710. 15 Port 2 Forced Abort Bit Same as IR 20711. 84 User-reset Section Using Protocol Macros 5-7 Error Codes The contents of the error codes are shown in the following table. Code Error contents 0 No error Protocol macro execution Executed 2 Sequence Number Error Not executed The sequence number specified by the PMCR(––) instruction does not exist in the Board. 3 Receive Data/Write Area Exceeded Error 4 When data is written or read to the CPU Unit, the specified area range was exceeded. Protocol Data Syntax Error Execution stops after the error occurs. A code that cannot be executed occurs while the protocol macro was executed. (Example: A header occurs after a terminator.) 5 Protocol Macro Execution Error During Port Initialization Execution stops after the error occurs. This error occurs when the PMCR instruction is executed while the port is being initialized (i.e., while the serial communications port is being restarted or while the serial communications mode in the PC Setup of the Serial Communications Board is being modified using the STUP instruction or the Programming Device). 5-7 Using Protocol Macros 5-7-1 Executing Communications Sequences Use the PMCR(––) instruction to execute communications sequences. PMCR(––) Instruction Specifications Control data First send word First receive data storage word Control Data: C 15 00 C: Digits 2 to 4 (bits 00 to 11): Communications sequence number (000 to 999) Digit 1 (bits 12 to 15): Port specifier 1: Port 1 (RS-232C) 2: Port 2 (RS-422A/485) First Send Data Word: S S specifies the first word of the words containing the data required for sending. 15 S S+1 00 Number of send words Total number of words including S Send data : : : : S+n 85 Section Using Protocol Macros 5-7 The number of send words in S+1 and the following words is stored in S. The setting range is 0001 to 0129 (4 digits BCD). S is also included in the number of words. Note When there is no send data, set S to #0000. If any other constant or a word address is set, an error will occur, the Error Flag (SR 25503) will turn ON, and PMCR(––) will not be executed. First Receive Data Storage Word (D) D specifies the first word of the area used to store the receive data. If a word address is specified for D and a response is requested, the data through the highest location received in the reception buffer will be stored in memory starting at D+1. The number of words that was stored starting at D+1 will be stored in D. D is included in the number of words. 15 00 D Number of receive words D+1 Receive data : : : : Total number of words including D D+n The number of words of receive data in D+1 and the following words is stored in D. The range is 0001 to 0129 (4 digits BCD). D is also included in the number of words. Note When there is no receive data, set D to to a dummy word address. If any constant is set, an error will occur, the Error Flag (SR 25503) will turn ON, and PMCR(––) will not be executed. PMCR(––) Operation When PMCR(––) is executed, the communications sequence specified in bits 00 to 11 of C is executed for the port specified in bits 12 to 15 of C (port 1 or 2). If an operand is specified as a variable in the send message, data starting in S+1 for the number of words specified in S is used as the send data. If an operand is specified as a variable in the receive message, data will be received in words starting from D+1 and the number of words of received data will be automatically stored in D. Flags Name Address ON OFF Error Flag SR 25503 Indirectly addressed DM or EM word is non-existent. (Content of DM/EM word is not BCD, or the area boundary has been exceeded.) Other times. Another PMCR(––) instruction was already in progress when the instruction was executed (IR 20708 or IR 20712 is ON). The port specifier was not 1 or 2. Note: PMCR(––) will not be executed when SR 25503 is ON. 86 Section Using Protocol Macros 5-7 Operand Areas and Address Ranges Area C IR and SR Areas IR 000 to IR 255 S HR Area HR 00 to HR 99 AR Area AR 00 to AR 27 LR Area LR 00 to LR 63 Timer and Counter Area Data Memory (DM) Area Extended Data Memory (EM) Area TIM/CNT000 to TIM/CNT511 Indirect DM address Indirect EM address Constant Area *DM 0000 to *DM 6655 D IR 000 to IR 252 DM 0000 to DM 6655 DM 0000 to DM 6143 EM 0000 to EM 6143 *EM 0000 to *EM 6143 See description of control data. #0000 to #FFFF --- 5-7-2 Ladder Program Structure When creating a ladder program, note the following points. • To ensure that a PMCR(––) instruction is not executed while another PMCR(––) instruction is being executed, use the Protocol Macro Executing Flag in an NC input condition. • Use an OFF condition for the Protocol Macro Executing Flag and perform processing to read the results of sequence execution, or perform processing when a sequence ends in an error. Programming Example Protocol Macro Executing Flag Input condition 20708 PMCR 20708 DIFD (14) A A Reading of sequence execution results Processing of sequence errors 87 Section Using Protocol Macros 5-7 5-7-3 Ladder Program Example The following diagram shows an example in which sequence number 000 (Present Value Read) for a Temperature Controller (E5K Read Protocol) is executed using the protocol for an OMRON Temperature Controller connected to port 2 (RS-422A/485) of a Serial Communications Board. Connections Serial Communications Board 32 Units max. Port 2 RS-422A/485 Specifies the Temperature Controller Unit No. , sends the PRESENT VALUE READ command send data, and receives the present value set in the response in the specified word. Send data Receive data Temperature Temperature Controller E5K Controller E5K Unit No. 00 Unit No. 01 Temperature Controller E5K Unit No. 31 32 Units max. Send Word Allocation for Sequence No. 000 (Present Value Read) First word of send data S Number of send data words S+1 (Undefined) Unit No. Word Contents (data format) Data S Number of send data words (4-digit BCD) 0002 (fixed) S+1 Unit No. (2-digit BCD) 00 to 31 Receive Word Allocation for Sequence No. 000 (Present Value Read) Receive data storage words D D+1 88 Number of receive data words Present value Word Contents (data format) Data D Number of receive data words (4-digit BCD) 0002 D+1 Present value (4-digit BCD) Scaling Lower limit to upper limit Section Using Protocol Macros Operand Settings for the PMCR(––) Instruction 5-7 Reading the present value of E5K Unit No. 03 and storing it in DM 0201 C: Control data PMCR #0000 D00100 1 0 0 D00200 0 0000: Sequence No. 000 Port 1 S: First send data word S: S+1: DM 0100 DM 0101 Number of send data words = 2 Unit No. = 03 D: First receive data storage word D: D+1: DM 0200 DM 0201 Present value Number of receive data words = 2 Present value is stored. (4-digit BCD) 89 Section Using Protocol Macros Ladder Programming Example Input condition 000000 The following diagram shows an example in which sequence number 000 (PRESENT VALUE READ) of a Temperature Controller (E5K Read System) is executed using the PMCR(––) instruction. If the sequence has been completed normally, the present value that has been read is transferred to another word. Protocol Macro Executing Flag 20708 PMCR #1000 DM 0100 DM 0200 Protocol Macro Executing Flag 20708 DIFD (14) 00100 Input condition 000100 5-7 Protocol Macro Executing Flag 20708 If input condition IR 00000 is ON and the Protocol Macro Executing Flag IR 20708 is OFF, then sequence No. 000 is executed for Serial Communications Board port 1 and the present value is stored in DM 0201 and after. If Protocol Macro Executing Flag IR 20708 turns OFF, IR 00100 turns ON (and remains ON for one cycle). Step Error Processing Flag 20709 MOV (21) DM 0201 Step Error Processing Flag DM 0300 If Protocol Macro Executing Flag IR 20708 is OFF and Step Error Processing Flag IR 20709 is OFF when IR 00100 turns ON, then the data received in DM 0201 is moved to DM 0300. 20709 FAL (06) 01 If IR 00100 is ON (sequence end) and Step Error Processing Flag IR 20709 is ON, the sequence has ended abnormally and a FAL(06) instruction (FAILURE ALARM AND RESET instruction) is executed. Protocol Macro Executing Flag IR 20708 Sequence executed Sequence completed Sequence re-executed 00100 One cycle When sequence ended normally: Step Error Processing Flag IR 20709 Present value in DM 0201 moved to DM 0300 FAL instruction executed When sequence ended abnormally: Step Error Processing Flag IR 20709 Precaution on Reception Failures for PMCR(––) The reception buffer is cleared to all zeros just before the communications sequence is executed. If programming is included in the ladder diagram to periodically read, it should be designed to read the data only when receptions are successful, and not when the contents of the buffer has been cleared to all zeros. The above ladder programming shows one way to achieve this. 90 Section Using Protocol Macros 5-7 Transmission Methods Although the following two transmission methods are commonly used, only halfduplex transmissions are supported for CQM1H protocol macros. Half-duplex: Data can be sent only one direction at a time. A B Or A B Full-duplex: Data can be sent in both directions at the same time. B A The use of half-duplex transmissions presents some restrictions. Data received from just before the SEND operation through the end of the SEND operation cannot be received as receive data for the next RECEIVE operation because the reception buffer is cleared just before a sequence is executed and at the end of the SEND operation (i.e., for the SEND and SEND&RECEIVE commands). Transmission mode Half-duplex Reception buffer cleared Data reception Character trace Just before sequence execution and at the end of SEND operation for SEND or SEND&RECEIVE commands Between end of SEND operation and end of RECEIVE operation or between the end of SEND operation and just before beginning of next SEND operation All characters while tracing is being performed An example timing chart for the above situation is shown below. Sequence execution Reception buffer cleared Receive Send Receive Data received See note 1. Character trace Note 1. Data received before the completion of the SEND operation will be lost, but it will be included in the character trace. 2. There is a time lag between the completion of data send processing and the end of the SEND operation. This time lag is time t1 and is shown in the following table. If the response from the external device is too quick, any receive data entering between the end of sending data for the SEND operation and the completion of the SEND operation will not be received. SEND operation Data send processing t1 Quick response Time lag (see table) Data not received here Data reception Reception buffer cleared 91 Section Using Protocol Macros 5-7 Time Lag t1 Baud rate (b/s) Lag time (ms) 1,200 30 2,400 15 4,800 8 9,600 5 19,200 3 Note The lag time shown above is an approximate value. It may become longer depending on the protocol macro processing. Error Flags for Overrun, Framing, and Parity Errors When an overrun, framing, or parity error is detected during a protocol macro, the receive data will be stored in the reception buffer along with error information. The error flags will operate as described next. Receive Data with Error Information that Matches Expected Receive Messages The expected receive message received for the RECEIVE operation is found in the reception buffer and handled as receive data. If the receive data contains error information, the corresponding error flags are turned ON. The following example shows reception of 100 bytes of data that matches an expected receive message. Error flags ON 100 bytes Parity errors Receive Data with Error Information that Does Not Match Expected Receive Messages If there is no expected receive message that matches the receive data, the data is discarded and the error flags are not affected. The trace information will contain any error information entering the reception buffer up to the capacity of the trace data. The following example illustrated what happens when there is no expected receive message that matches the receive data. Discarded Error flags are not changed. In the following ladder programming, sequence number 000 (E5K Digital Controller Read) is executed through PMCR(––) to read the PV from the Digital Con- 92 Section Using Protocol Macros 5-7 troller. When sequence execution has been completed, the PV is transferred to words to store it. Execution Protocol Macro Execondition cuting Flag 00000 20708 PMCR #1000 DM 0100 Protocol Macro Executing Flag If IR 20708 is OFF when the execution condition turns ON, sequence #000 is executed and the PV is stored in DM 0201. DM 0200 20708 DIFD (14) 00100 Protocol Macro Transfer Step Error Executing Flag Processing Flag 00100 20708 When IR 20708 changes from ON to OFF, IR 00100 will turn ON for one cycle. 20709 MOV (21) DM 0201 If IR 00100 is ON, IR 20708 is OFF, and IR 20709 is OFF, the PV in DM 0201 is moved to DM 0300. DM 0300 Transfer Step Error Processing Flag 20709 FAL (07) 01 Protocol Macro Executing Flag (IR 20708) If IR 00100 is ON and IR 20709 is ON, an error will have occurred in the sequence and a non-fatal error is generated. 1 0 Sequence executed Sequence completed Sequence executed 1 IR 00100 Sequence executed normally: Error in sequence execution: Transfer Step Error Processing Flag (IR 20709) Transfer Step Error Processing Flag (IR 20709) 0 1 0 1 cycle PV in DM 0201 moved to DM 0300 FAL executed 1 0 Processing When a Sequence Ends Abnormally As shown in the following examples, if END is set when a sequence ends normally and ABORT is set when a sequence ends abnormally, it is possible to determine whether each sequence has ended normally or abnormally by using the Sequence End Completion Flag and the Sequence Abort Completion Flag. 93 Using Protocol Macros Example 1 Sequence Step No. 00 Section 5-7 Error Sequence ended abnormally Example 2 Sequence Step No. 00 Error Error Sequence ended abnormally Step No. 01 Step No. 01 Step No. 02 Sequence ended abnormally Error Sequence ended normally Sequence ended normally Sequence ended normally When the Sequence Ends Normally When the Sequence Ends Normally Protocol Macro Executing Flag Protocol Macro Executing Flag Sequence executed Sequence completed Sequence re-executed Sequence executed Sequence completed Sequence re-executed Sequence End Completion Flag Sequence End Completion Flag Error processing for step No. 00 Step Error Processing Flag Step Error Processing Flag When the Sequence Ends Abnormally When the Sequence Ends Abnormally Protocol Macro Executing Flag Protocol Macro Executing Flag Sequence executed Sequence completed Sequence Abort Completion Flag Sequence re-executed Sequence executed Sequence completed Sequence re-executed Sequence Abort Completion Flag Error processing for step No. 00 Step Error Processing Flag Step Error Processing Flag Note 94 The Step Error Processing Flag is used to see whether error processing has been executed for an individual step in a sequence, and not for the overall steps. Therefore, as shown in Example 2 above, after executing error processing during a sequence (step No. 00), the flag will remain ON, even if the next step ends normally. Care is therefore required because it is not always possible to use this flag to determine whether the overall sequence has ended abnormally. Section Using Protocol Macros 5-7 Precautions on Using the Force Abort Bit The Protocol Macro Executing Flag will turn OFF as soon as the Forced Abort Bit is turned ON from the ladder program. The Forced Abort Bit must remain ON for at least 15 ms longer than the CPU Unit cycle time. Thus, the sequence will not be aborted if the Forced Abort Bit is turned OFF as soon as the Protocol Macro Executing Flag turns OFF. If only the Protocol Macro Execution Flag is used in an NC condition for PMCR(––), PMCR(––) will be executed during abort processing, and system error (FAL 9C) will occur. Wait at least 15 ms longer than the cycle time after turning ON the Forced Abort Bit before executing the next protocol macro. In the following example, the Forced Abort Bit is turned ON and an interlock is created for the PMCR(––) instruction for 30 ms before the Forced Abort Bit is turned OFF. Execution condition Protocol Macro Executing Flag Forced Abort Bit PMCR Abort condition T000 A A A TIMH 000 #0003 T000 20711 Forced Abort Bit Abort condition A T000 30 ms 1 cycle Forced Abort Bit (IR 20711) Protocol Macro Executing Flag (IR 20708) 95 SECTION 6 No-protocol Communications This section provides information required to use no-protocol communications on a Serial Communications Board port. 6-1 6-2 6-3 6-4 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-1 TRANSMIT – TXD(––) and RECEIVE – RXD(––) . . . . . . . . . . . . . . . . . . . . . . 6-4-2 TXD(––) Communications Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-3 RXD(––) Communications Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-4 Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 100 101 102 102 104 104 105 97 Section Using No-protocol Communications 6-1 6-1 Overview Data can be sent or received without a protocol and without conversion by connecting an external device to the RS-232C port and executing the TXD(––) or RXD(––) instruction from the ladder program. Start and end codes can be attached to the data or the amount of data to be received can be specified. The communications frame cannot be specified for no-protocol communications in the way it can be for protocol macros. Retry processing, data conversion, and procedural branching according to received data are also not possible. No-protocol communications are thus good for communicating with bar code readers and other external devices with RS-232C ports that do not required commandresponse procedures. Data is sent in one direction only, using TXD(––) to send data from the port or RXD(––) to read data received on the port. Note When TXD(––) is executed in No-protocol Mode, data from I/O memory is sent from the port without conversion. When TXD(––) is executed in Host Link mode (for slave-initiated communications), the contents of the specified words in I/O memory is converted to ASCII before being sent. No-protocol Specifications The specifications of no-protocol communications are given in the following table. Item Messages (communications frame) Specification One of the following. Data only Start code + data Data + end code Start code + data + end code Data + CR + LF Start code + data + CR + LF Settings are made in the PC Setup: Start code enable, end code enable, start code, end code, number of receive bytes (when end code is disabled) Start code Disabled or 00 to FF Hex End code Disabled, 00 to FF Hex, or CR+LF Number of receive bytes 1 to 256 bytes if transmission ends in data (data only or start code + data) Message transmissions Message receptions Maximum message length Data conversion TXD(––) in ladder program Communications protocol Transmission delay None Reception counter 98 RXD(––) in ladder program 256 bytes including start code and end codes (253 bytes without start/end codes) for either sending or receiving None 0 to 99,990 ms (set in PC Setup in units of 10 ms) The transmission delay is from the beginning of TXD(––) execution until execution of the next TXD(––) can be started. The number of bytes received at the port can be counted from 0 to 256 bytes. Section Using No-protocol Communications 6-1 Send/Receive Message Frames End code Start code No Yes CR+LF No Data Data 256 bytes max. ED Data 256 bytes max. CR+LF 256 bytes max. Yes ST Data ST Data 256 bytes max. ED ST Data CR+LF 256 bytes max. 256 bytes max. • Only the first start code is valid if there is more than one start code. • Only the first end code is valid if there is more than one end code. • Use CF+LF if using an end code may cause receptions to be interrupted because the end code exists in the receive data. • A transmission delay can be set for PC-initiated communications as a minimum interval between sending commands to the host. The delay is not used in sending the first command. The delay will affect other commands only if the time set for the transmission delay has not expired when the next command is ready to be sent. If the delay time has already expired when the next command is ready, the command will be spent immediately. If the delay time has not expired, the command will be delayed until the time set for the transmission delay has expired. The operation of the transmission delay for PC-initiated communications is illustrated below. Transmission delay Transmission delay Command sent 1st TXD(––) command Command sent 2nd TXD(––) command Transmission delay Command sent 3rd TXD(––) command Command sent 4th TXD(––) command Time Refer to the CQM1H Programming Manual for details on TXD(––) and RXD(––). 99 Section Using No-protocol Communications 6-2 6-2 Application Procedure 1, 2, 3... 1. Turn OFF the power supply to the PC. 2. Mount the Board. 3. Connections Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port. The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required. 4. Turn ON power. 5. Set the PC Setup settings for the Serial Communications Board. Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6500 and DM 6559. Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed. The following table shows the settings for using STX as the start code, CR+LF as the end code, and no transmission delay. Port 1 DM 6555 Port 2 DM 6550 DM 6556 DM 6551 DM 6557 DM 6552 DM 6558 DM 6553 DM 6559 DM 6554 Bit(s) Setting Function 00 to 03 0 Hex Standard port settings (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 04 to 11 12 to 15 --1 Hex 00 to 07 08 to 15 00 to 15 00 Hex 00 Hex 0000 (BCD) Not used. Serial communications mode No-protocol Baud rate setting disabled. Frame format setting disabled. Transmission delay: 0 ms 0000 to 9999 (BCD): Set in units of 10 ms 00 to 07 08 to 11 12 to 15 --1 Hex 2 Hex 00 to 07 08 to 15 02 Hex 00 Hex Not used. Start code enabled End code enabled as CR+LF 0: Disable (number of receive bytes set) 1: Set (specified end code) 2: CR, LF Start code: STX Number of receive bytes (Disabled when end code is set.) 6. Write and execute the ladder program. Use TXD(––) to send data to an external device and RXD(––) to receive data from an external device. 100 Section Using No-protocol Communications 6-3 6-3 Connections The connection examples in this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 2-3 Wiring for actual wiring methods. Connecting to a Bar Code Reader via RS-232C The following diagram shows the connections between an OMRON V500-series Bar Code Reader and the RS-232C port on the Serial Communications Board. Serial Communications Board (D-sub, 9-pin female connector) Signal Pin V509-W012 Cable V520-RH21-6 Bar Code Reader Pin Signal Serial Communications Board V509-W012 Cable V520-RH21-6 Bar Code Reader 100 VAC 5-V external power supply (e.g., 82S-0305) Note If the external device has a FG terminal, connect the shield wire to ground at both the external device and the Serial Communications Board to prevent faulty operation. 101 Section Using No-protocol Communications 6-4 6-4 Using No-protocol Communications 6-4-1 TRANSMIT – TXD(––) and RECEIVE – RXD(––) This section describes using TXD(––) and RXD(––) for no-protocol communications. TRANSMIT – TXD(––) in No-protocol Mode TXD(––) S First source word C Control word N Number of bytes (4 digits BCD, 0000 to 0256) Control Word: C 15 00 0 0 Byte order 0: Most significant bytes first 1: Least significant bytes first Not used. (Set to 0.) Port 0: RS-232C port on CPU Unit 1: Port 1 on Serial Communications Board 2: Port 2 on Serial Communications Board Not used. (Set to 0.) The specified number of bytes will be read starting from S and transmitted through the specified port. • Up to 256 bytes of data can be sent each time the instruction is executed. • The bytes of source data shown below will be sent in the following order. If most significant bytes first is specified (0): 12345678.. If least significant bytes first is specified (1): 21436587.. S S+1 S+2 S+3 MSB LSB 1 2 3 4 5 6 7 8 Communications parameters are set in the PC Setup settings for the Serial Communications Board. Refer to information in the CQM1H Programming Manual on serial communications and TXD(––) for details. 102 Section Using No-protocol Communications 6-4 RECEIVE – RXD(––) in No-protocol Mode RXD(––) D First destination word C Control word N Number of bytes (4 digits BCD, 0000 to 0256) Control Word: C 15 00 0 0 Byte order 0: Most significant bytes first 1: Least significant bytes first Not used. (Set to 0.) Port 0: RS-232C port on CPU Unit 1: Port 1 on Serial Communications Board 2: Port 2 on Serial Communications Board Not used. (Set to 0.) The specified number of bytes are read from the specified port as specified in the control word and stored starting at D. • Up to 256 bytes of data can be read each time the instruction is executed. • The bytes of received data will be received in the following order. Digit 0 = 0 D D+1 D+2 D+3 MSB LSB 1 2 3 4 5 6 7 8 Digit 0 = 1 D D+1 D+2 D+3 MSB LSB 2 1 4 3 6 5 8 7 • If the value of N is larger than the number of receive bytes, only the number of bytes actually received will be read into memory. • Communications parameters for the Serial Communications Board are set in the PC Setup. Refer to the CQM1H Programming Manual for details. 103 Section Using No-protocol Communications 6-4 6-4-2 TXD(––) Communications Procedure Confirm that the Transmission Enabled Flag is ON before executing TXD(––). The Port 1 Transmission Enabled Flag is IR 20105 and the Port 2 Transmission Enabled Flag is IR 20113. The Transmission Enabled Flag will turn OFF while TXD(––) is being executed and will turn ON when the send has been completed. C: Control Word 15 TXD(––) 00 0 S First source word C Control word N Number of bytes (4 digits BCD, 0000 to 0256) 0 Byte order 0: Most significant bytes first 1: Least significant bytes first Not used. (Set to 0.) Port 0: RS-232C port on CPU Unit 1: Port 1 on Serial Communications Board 2: Port 2 on Serial Communications Board Not used. (Set to 0.) Note Do not let TXD(––) be executed unless the Transmission Enabled Flag is ON. 6-4-3 RXD(––) Communications Procedure The Reception Completed Flag will turn ON when data reception has been completed. The Port 1 Reception Completed Flag is IR 20106 and the Port 2 Reception Completed Flag is IR 20114. When RXD(––) is executed, the receive data is stored in the specified data without any start or end code and the Reception Completed Flag is turned OFF. Reception is started when the start code is received. If the start code is disabled, then data is received continually. Reception is completed when the end code is received. If the end code is disabled, then reception is completed when the specified number of bytes or 259 bytes have been received. C: Control Word 15 RXD(––) 00 0 D First destination word C Control word N Number of bytes (4 digits BCD, 0000 to 0256) 0 Byte order 0: Most significant bytes first 1: Least significant bytes first Not used. (Set to 0.) Port 0: RS-232C port on CPU Unit 1: Port 1 on Serial Communications Board 2: Port 2 on Serial Communications Board Not used. (Set to 0.) The following flags and status information are available in the IR area. All bits are cleared when RXD(––) is executed. 104 Section Using No-protocol Communications Port 1 Port 2 6-4 Function IR 20100 to IR 20103 IR 20108 to IR 20111 Error Code 0: Normal operation 1: Parity error 2: Framing error 3: Overrun error IR 20104 IR 20112 Communications Error Flag IR 20107 IR 20115 Reception Overflow Flag (Turns ON when data is received again before the previous data is read with RXD(––).) IR 20200 to IR 20215 IR 20300 to IR 20315 Reception counter Provides the number of bytes of data received in 4-digit BCD (0 to 256). The Port 1 Restart Bit (IR 20700) and Port 2 Restart Bit (IR 20701) can be turned ON to initialize the serial communications ports. These bits will be turned OFF automatically after the ports have been initialized. 6-4-4 Application Example This example shows how to send data from DM 0100 to DM 0104 (each word contains 3454) to a computer and then store data received from the computer starting at DM 0200. Conditions PC Settings The following settings are made in the PC Setup before executing the program. Communications mode: No-protocol Port settings: Standard Start code: None End code: CR + LF Other: Default settings Computer Settings Set the same communications parameters as the PC and prepare the programs to send and receive data. Ladder Programming 00100 DIFU (13) 00101 00101 Transmission Enabled Flag TXD DM0100 #0100 Reception Competed Flag #0010 20106 RXD DM0200 #0100 #0256 1, 2, 3... 1. When IR 00100 turns ON, the contents of DM 0100 to DM 0104 will be sent with most significant bytes first from port 1 on the Serial Communications Board if IR 20105 is ON (Transmission Enabled Flag). The following data will be received at the computer: 34543454345434543454CRLF 2. When IR 20106 (Reception Competed Flag) turns ON, 256 bytes of data received on port 1 on the Serial Communications Board will be read and stored starting at DM 0200 with most significant bytes first. 105 SECTION 7 Communications for 1:1 Data Links This section provides information required to create 1:1 Data Links through a Serial Communications Board port. 7-1 7-2 7-3 7-4 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1-1 Starting Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1-2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using 1:1 Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 108 109 109 110 111 107 Section Overview 7-1 7-1 Overview If two PCs are linked one-to-one by connecting them together through RS-232C or 4-wire RS-422A/485 cable, they can share up to 64 words of their LR areas. The 1:1 Data Links are the same as normal Data Links in that data is not shared bidirectionally, i.e., the link words written by one PC are transferred to the other PC. One of the following three ranges of words can be set to be linked: LR 00 to LR 63, LR 00 to LR 31, or LR 00 to LR 15 A 1:1 Data Link communications system can be created between the CQM1H and another CQM1H, or between the CQM1H and the CQM1, C200HX/HG/HE, C200HS, CPM1, CPM1A, CPM2A, CPM2C, or SRM1(-V2). One of the PCs is set as a 1:1 Data Link master and the other as a 1:1 Data Link slave. The linked words are separated into two groups of words, and the words written by each PC is transferred to the other PC, as illustrated in the following diagram. For example, if LR 00 to LR 63 are linked, the status of LR 00 to LR 31 written by the master CQM1H will be transferred to LR 00 to LR 31 of the slave CQM1H, and the status of LR 32 to LR 63 written by the slave CQM1H will be transferred to LR 32 to LR 63 of the master CQM1H. CQM1H or other C-series PC CQM1H or other C-series PC Link RS-232C Serial Communications Board CQM1H or other C-series PC CQM1H or other C-series PC LR 00 to LR 00 to Master area (sent) LR 31 LR 32 to LR 31 LR 32 to Slave area (received) Master area (received) Slave area (sent) LR 63 LR 63 The words in the LR area that will be linked are set in the PC Setup as shown in the following table. PC Setup Setting Port 1 DM 6555 Port 2 DM 6550 Bits 04 to 07 Function Link words for 1:1 link Setting Master words Slave words 0 Hex: LR 00 to LR 63 1 Hex: LR 00 to LR 31 2 Hex: LR 00 to LR 15 LR 00 to LR 31 LR 00 to LR 15 LR 00 to LR 07 LR 32 to LR 63 LR 16 to LR 31 LR 08 to LR 15 7-1-1 Starting Data Links Connect two PCs one-to-one through RS-232C or 4-wire RS-422A/485 cable, make the proper settings in the PC Setup, and turn ON the power supplies. The 1:1 Data Link will start automatically. 108 Section Using 1:1 Data Links 7-2 7-1-2 Specifications Item Connection method Applicable PCs Specification Connection of 2 PCs through their RS-232C ports (prepared cable). Note RS-422A/485 ports can also be connected if a 4-wire connection method is used. CQM1H, CQM1, CPM1, CPM1A, CPM2A, CPM2C, or SRM1(-V2), C200HX/HG/HE, C200HS There are restrictions in the number of words that can be linked for some PCs. Number of nodes linked Number of words linked Linked words 64 words, LR 00 to LR 63 32 words sent per node 32 words, LR 00 to LR 31 16 words sent per node 16 words, LR 00 to LR 15 8 words sent per node One of three groups listed above Link word setting PC Setup in master PC Order of allocation Words allocated to master PC first and then to slave PC. Startup method Automatic startup after turning ON power to master and slave PCs. None Status flags 7-2 2 Application Procedure 1, 2, 3... 1. Turn OFF the power supply to the PC. 2. Mount the Board. 3. Connections Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port. The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required. 4. Turn ON power. 5. Set the PC Setup settings for the Serial Communications Board. Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559. Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed. The following table shows the master PC settings for a 1:1 Data Link for LR 00 to LR 63. 109 Section Overview Port 1 DM 6555 Port 2 DM 6550 Bits 00 to 07 08 to 11 12 to 15 Setting 7-3 Function --0 Hex Not used. Link words for 1:1 Data Link 3 Hex 0: LR 00 to LR 63 (default) 1: LR 00 to LR 31 2: LR 00 to LR 15 Communications mode DM 6556 DM 6551 00 to 15 --- 2: 1:1 Data Link slave 3: 1:1 Data Link master Not used. DM 6557 DM 6552 00 to 15 --- Not used. DM 6558 DM 6553 00 to 15 --- Not used. DM 6559 DM 6554 00 to 15 --- Not used. 6. Write and executed the ladder program. The Always ON Flag (SR 25313) can be use to program instructions such as MOV(21) to write data to be sent to the other PC to the sending words in the LR area and to read data received from the other PC in the receiving words in the LR area. 7-3 Connections The connection examples in this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 2-3 Wiring for actual wiring methods. CQM1H Signal CQM1H Pin Connector edge D-sub, 9-pin male connector on cable 110 Pin Signal Connector edge D-sub, 9-pin male connector on cable Section Using 1:1 Data Links 7-4 7-4 Using 1:1 Data Links This section provides an example of using 1:1 Data Links. Conditions The following settings are made in the PC Setup before executing the program. Master PC Settings Communications mode: 1:1 Data Link master Link words: LR 00 to LR 15 Slave PC Settings Communications mode: 1:1 Data Link slave Ladder Programming Master PC Slave PC Always ON Flag Always ON Flag MOV (21) MOV (21) 001 001 LR00 LR08 MOV (21) MOV (21) LR08 LR00 100 100 When the programs in the two PCs are executed, the status of input word IR 001 of both PCs will be transferred to the other PC and will be output to output word IR 100. 111 SECTION 8 NT Link Communications This section describes the procedure and other information required to use 1:N-mode and 1:1-mode NT Links to Programmable Terminals (PTs). 8-1 8-2 8-3 Overview of NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1-1 NT Links — 1:N Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1-2 NT Links — 1:1 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1-3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 114 114 114 116 117 113 Section Connections 8-1 8-1 Overview of NT Links This section explains the application of a Serial Communications Board for an NT Link in either 1:N or 1:1 mode. For details on the operation of the PT, refer to the operation manual for the PT. Note In an NT Link using 1:N mode, a PC can be connected to either one or more than one PTs. There is no difference in functionality determined by the number of PTs connected. The 1:1 mode, however, uses a different communications protocol from the 1:N mode and these two modes are not compatible. 8-1-1 NT Links — 1:N Mode A PC can be connected to one or more Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PC is allocated as a Status Control Area and a Status Notification Area for the PT, as well as to objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PC to be controlled and monitored by operations from the PT, without the use of ladder programming in the PC. One PC can be connected to up to eight PTs. The user does not need to be aware of the 1:N NT Links commands. All that is necessary is to allocate PC memory for the PTs. Serial Communications Board Serial Communications Board 1:N connections 1:1 connection PT PT PT 8-1-2 NT Links — 1:1 Mode Although the functionality of an NT Link in 1:1 mode is the same as an NT Links in 1:N mode, only one PT can be connected to the PC. The 1:1 mode is not compatible with the 1:N mode as a communications protocol. Serial Communications Board 1:1 connection PT 8-1-3 Precautions 1, 2, 3... 114 1. Set the serial port on the PT to a 1:N NT Link whenever the Serial Communications Board is set to a 1:N NT Link, and set the serial port on the PT to a 1:1 NT Link whenever the Serial Communications Board is set to a 1:1 NT Link. The Serial Communications Board will not be able to communicate if the PT port is set to a different mode. 2. The NT20S, NT600S, NT30/30C, and NT620S/620C/625C cannot be used if the cycle time of the PC is 800 ms or longer. This is true in both 1:1 and 1:N mode (even when a 1:1 connection is used in 1:N mode). Section Connections 8-1 3. The Programming Console functions of the PT (Expansion Mode) cannot be used when connected to Serial Communications Board ports. They can be used only by connecting to the peripheral port or RS-232C port on the CPU Unit. This is true in both 1:1 and 1:N mode. 4. When using 1:N-mode NT Links, set a unique unit number for each PT connected to the same PC. If the same unit number is set for more than one PT, malfunctions will occur. 5. The number of PTs that can be connected to one port in 1:N mode is limited by the CPU Unit’s cycle time when a Serial Communications Board is used, as shown in the following diagrams. Although some communications will be possible even if these restrictions are exceeded, communications errors will occur depending on the PT operating conditions and communications load. Always abide by these restrictions when using 1:N mode. Example for NT31/NT631(C) PTs Priority Registered PTs per port CPU Unit’s cycle time (ms) Priority Not Registered PTs per port CPU Unit’s cycle time (ms) 115 Section Connections 8-2 6. With some PTs, timeout settings can be changed to eliminate some of the communications errors. Refer to the operation manual for the PT for details. This is true in both 1:1 and 1:N mode. 7. If more PTs are required by the system than allowed by the above restrictions in 1:N mode, connect the PTs in smaller groups to different ports. 8-2 Application Procedure 1, 2, 3... 1. Turn OFF the power supply to the PC. 2. Mount the Board. 3. Connections Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port. The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required. 4. Turn ON power. 5. Set the PC Setup settings for the Serial Communications Board. Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559. Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed. NT Link Settings for 1:N Mode The following table shows the settings for connecting more than one PT when the highest PT unit number is 5. Port 1 DM 6555 Port 2 DM 6550 Bit(s) Setting 00 to 07 08 to 11 --5 (BCD) Function 12 to 15 5 Hex Communications mode 00 to 15 00 to 15 00 to 15 00 to 15 --- NT Link in 1:N mode Not used. Not used. Maximum Programmable Terminal unit number 1 to 7 (BCD) NT Link in 1:N mode DM 6556 DM 6557 DM 6558 DM 6559 DM 6551 DM 6552 DM 6553 DM 6554 Port Settings are always the same for 1:N-mode NT Links. Settings of the start bits, stop bits, parity, and baud rate are not necessary and will be ignored. Set the communications mode to a 1:N-mode NT Link (5 Hex). Up to 8 PTs can be connected in 1:N mode. Set the highest unit number of the PTs to be connected as the maximum Programmable Terminal unit number. NT Link Settings for 1:1 Mode The following table shows the settings for a 1:1-mode NT Link. Port 1 DM 6555 Port 2 DM 6550 Bit(s) Setting 00 to 11 12 to 15 --4 Hex Function Not used. Communications mode NT Link in 1:1 mode 116 Section Connections Port 1 Port 2 Bit(s) DM 6556 DM 6557 DM 6558 DM 6559 DM 6551 DM 6552 DM 6553 DM 6554 00 to 15 00 to 15 00 to 15 00 to 15 Setting --- 8-3 Function Not used. Port Settings are always the same for 1:1-mode NT Links. Settings of the start bits, stop bits, parity, and baud rate are not necessary and will be ignored. Set the communications mode to a 1:1-mode NT Link (4 Hex). 6. Operate the system. Refer to the operation manual for your PT for operating instructions. 8-3 Connections The connection examples in this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 2-3 Wiring for actual wiring methods. Direct 1:1 Connection from RS-232C to RS-232C Ports (1:1 or 1:N Mode) Serial Communications Board PT Pin Signal Pin Signal FG Hood FG SD RS-232C RD Interface RTS CTS 5V DSR DTR SG Hood FG -SD RD RS-232C RTS Interface CTS 5V --SG D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) • Communications Mode: 1:1 or 1:N-mode NT Link • OMRON Cables with Connectors: XW2Z-200T-1: 2 m XW2Z-500T-1: 5 m Direct 1:1 Connection from RS-422A/485 to RS-422A/485 Ports (1:1 or 1:N Mode) Serial Communications Board Signal Pin Short piece Signal RS-422A/ 485 Interface RS-422A/ 485 Interface Hood D-sub, 9-pin connector (male) Functional ground Terminal block or D-sub connector • Communications Mode: 1:1 or 1:N-mode NT Link Note Serial Communications Board settings: Terminating resistance ON, 4-wire. 117 Section Connections 8-3 1:N, 4-wire Connections from RS-422A/485 to RS-422A/485 Ports (1:N Mode) Serial Communications Board PT Signal Signal Pin RS-422A /485 Interface RS-422 A/485 Interface Hood D-sub, 9-pin connector (male) FG Terminal block or D-sub connector Short bar PT Signal RS-422A /485 Interface FG Terminal block or D-sub connector Communications Mode: 1:N NT Link Note Serial Communications Board settings: Terminating resistance ON, 4-wire. 1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports (1:N Mode) Serial Communications Board Signal Pin PT Signal RS-422A/ 485 Interface RS-422A /485 Interface Hood D-sub, 9-pin connector (male) FG Terminal block Short bar PT Signal RS-422A /485 Interface FG Terminal block Communications Mode: 1:N NT Link Note Serial Communications Board settings: Terminating resistance ON, 2-wire. 118 SECTION 9 Troubleshooting and Maintenance This section describes the troubleshooting and maintenance procedures for the Serial Communications Boards. 9-1 9-2 9-3 9-4 Front-panel Indicator Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2-2 Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2-3 1:N NT Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cleaning and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3-1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3-2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4-1 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4-2 Settings after Replacing the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4-3 Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 121 121 125 129 130 130 131 132 132 132 132 119 Section Board Replacement 9-1 9-1 Front-panel Indicator Error Displays Indicators Board RDY Possible cause Remedy CPU Unit ERR/ALM Lit Not lit The Serial Communications Board has started normally. --- Not lit Lit The Serial Communications Board is faulty (hardware self-diagnostic function). Board watchdog timer error: IR 20000 will turn ON. If the ERR and ALM indicators light when the Serial Communications Board is mounted to another CPU Unit, replace the Serial Communications Board. A bus error has occurred. Firmly secure the Serial Communications Board to the CPU Unit. An initialization recognition error has occurred (the Serial Communications Board is not correctly recognized by the CPU Unit). Not lit Not lit The CPU Unit is not receiving normal power supply. Check the power supply voltage and supply the correct electric power to the Unit. The Serial Communications Board is not correctly secured to the CPU Unit. Firmly secure the Serial Communications Board. The Serial Communications Board is faulty. An error (such as a CPU Unit WDT error) has occurred in the CPU Unit. If all the indicators are not lit when the Serial Communications Board is mounted to another CPU Unit, replace the Serial Communications Board. Eliminate the cause of the error. If the error persists, replace the CPU Unit. Lit Lit The Serial Communications Board is faulty. If all the indicators are lit when the Serial Communications Board is mounted in another CPU Unit, replace the Serial Communications Board. A bus error has occurred. Check the operating environment and eliminate the cause of the error. Firmly secure the Serial Communications Board. Lit Flashing An error has occurred in the CPU Unit. (Cause of error eliminated, but error not cleared.) Eliminate the cause of the error. If the error persists, replace the CPU Unit. Flashing Flashing A protocol data write error has occurred or protocol data has been destroyed. (Protocol data error: IR 20002) If the indicator status remains the same when the protocol data is retransmitted, replace the Serial Communications Board. Connector may have become loose or the PC power supply may have turned OFF while transferring protocol data. Transfer protocol data to the Serial Communications Board. 120 There is no protocol data. Conduct a loopback test. If an error occurs, replace the Serial Communications Board. The communications circuit is faulty. (Board Identification Error Flag: IR 20001) Correct the protocol data and transfer it to the Serial Communications Board. A protocol data syntax error has occurred. (Protocol macro error code: 4) Try executing a normal sequence for the serial port where the error is occurring or switch the CPU Unit to PROGRAM mode and remove the cause of the error. A PC Setup error has occurred. (PC Setup Error Flags: IR 20013 to IR 20015) Correct the PC Setup settings. Section Board Replacement 9-2 Serial Communications Board Error Information For Serial Communications Boards, refer to the following error flags. When an error occurs, the corresponding flag is turned ON. All of these flags represent non-fatal errors. Word IR 200 Name Bit Probable cause 00 Serial Communications Board Hardware Error Flag The Board has failed. 01 Port Identification Error Flag (hardware error) Protocol Data Error Flag There is a problem with the communications port. A checksum error was found in the protocol data. 12/11 Protocol Macro Execution Error Flag (Port 1/2) An error occurred when the PMCR instruction was executed. 15 PC Setup Error Flag SR 254 14 13 15 Port 1 PC Setup Error Flag Port 2 PC Setup Error Flag Slot 1 Inner Board Error Flag There is an error in the settings in the PC Setup. Error in settings for port12. AR 04 00 to 07 Slot 1 Inner Board Error Code 01: Hardware error 02 02: Hardware error 10: Serial Communications Board error Error in settings for port 2. Turns ON when an error occurs in the slot 1 Inner Board. The error code for slot 1 is stored in AR 0400 to AR 0407. The Board has failed (watchdog timer error). IR 20000 will also be ON. The Board has failed. Refer to the errors in IR 200. Possible remedy Secure the Board firmly in the slot or try it in a different CPU Unit. If the problem persists, replace the Board. Replace the Board. Retransfer the protocol data. If the problem persists, replace the Board. Take countermeasures according to the error codes stored in bits 08 to 11 (port 1) or bits 12 to 15 (port 2) in word 204. Check the settings for the Board in the PC Setup and restart the Board. See remedies for AR 04. Secure the Board firmly in the slot or try it in a different CPU Unit. If the problem persists, replace the Board. See remedies for IR 20000, IR 20001, IR 20002, IR 20011, IR20012, and IR 20015. When a fatal error occurs, the ERR/ALM indicator on the CPU Unit will light. When a non-fatal error occurs, the ERR/ALM indicator on the CPU Unit will flash. Refer to the indicator error displays. Note The ERR/ALM indicator will continue to flash even after the cause of a non-fatal error has been removed for the Serial Communications Board. The indicator can be stopped by clearing the error from a Programming Console or other Programming Device. Press the FUN Key and then the MONITOR Key from the Programming Console. Refer to the CX-Programmer Operation Manual for the CXProgrammer procedure. 9-2 Troubleshooting This section describes how to resolve transmission and reception problems. 9-2-1 Host Link Communications Serial communications mode Indicator status Status information, etc. I/O memory Cause Remedy 121 Section Board Replacement Serial communications mode Indicator status Status information, etc. Serial communications mode is not set to Host Link. --- --- Serial communications mode is set to Host Link. --The COMM indicators do not flash at all. (Communications have not been electrically established.) 9-2 I/O memory Cause Remedy Bits 12 to 15 (Serial Communications Mode) of DM 6555/DM 6550 are set to a value other than 0 Hex. --- Serial communications mode is not set correctly. Set bits 12 to 15 of DM 6555/DM 6550 to 0 Hex. (Host Link). Cables are incorrectly connected. Check the wiring. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect (WIRE). Reset the port to the correct wiring setting. Wire all nodes using the 4-wire method. Adapters such as the NT-AL001-E are incorrectly wired or set. There is no The COMM transmission indicators are error. flashing, but the response has not been returned to the host. (Communications have been electrically established.) IR 20100 to IR 20103 or IR 20108 to IR 20177 are 0 Hex. Commands are not being set from the host. Reset the serial communications port at the host, and rewrite the program. There is a hardware error. The PC Setup settings for the Host Link unit No., Host Link transmission delay, or other settings do not match the settings for the remote device. Replace the Serial Communications Board. Reset the settings in the PC Setup for the Host Link unit No., Host Link transmission delay and other settings so that they match the settings at the host device. The command format and data length of the data sent from the host are incorrect. --- Cables are incorrectly connected. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect (WIRE). Correct the command frame (header, Host Link Unit No., terminator, etc.) and the program. Check the wiring and switch settings, and correct if necessary. Adapters such as the NT-AL001-E are incorrectly wired or set. --- 122 This is a transmission circuit hardware error. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board. The send delay time setting is too long. Reset the parameters in the PC Setup correctly. Section Board Replacement Serial communications mode Serial communications mode is set to Host Link. (Continued) Indicator status The COMM indicators are flashing, but the response has not been returned to the host. Status I/O memory information, etc. There is a The error code in transmission IR 20100 to error. IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is 1 (parity error), 2 (framing error), or 3 (overrun error). 9-2 Cause Remedy The communications conditions and baud rate do not match the settings at the host. Review the PC Setup, the host’s settings, and program (such as commands and frame format) based on the response and the error code. Use shielded twisted-pair cables. There is noise interference. Lay power lines separately using ducts. Review the installation environment to reduce noise interference. The COMM indicators are flashing, and an error response has returned to the host. There is no transmission error. IR 20100 to IR 20103 or IR 20108 to IR 20111 are 0 Hex. A command was sent from the host with incorrect parameters. Review the host’s settings and program (such as parameter settings) based on the response contents. There is a transmission error. The communications conditions and baud rate do not match the settings at the host. The COMM indicators are flashing, but sometimes there is no response returned. There is an intermittent transmission error. The error code in IR 20100 to IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is 1 (parity error), 2 (framing error), or 3 (overrun error). The error code in IR 20100 to IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is 1 (parity error), 2 (framing error), or 3 (overrun error). Terminating resistance switch (TERM) status Review the PC Setup, the host’s settings and program (such as commands and frame format) based on the response, and the error code in IR 20100 to IR 20103 or IR 20108 to IR 20111. Review the PC Setup. The error code in IR 20100 to IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is not 0. The baud rate is outside the allowable range, and the stop bits do not match, causing the bits to be out of alignment. Review the host’s settings and program (such as baud rate and frame format). Cables are incorrectly connected. Check the wiring. The RS-422A/485 port 2-wire/4-wire terminating resistance setting is incorrect. Turn ON the terminating resistance of the Serial Communications Board and the last node by using the terminating resistance switch. Turn OFF the terminating resistance of other nodes. Adapters such as the NT-AL001-E are incorrectly wired or the terminating resistance is incorrectly set. Transmission errors are occurring that are caused by noise interference. Use shielded twisted-pair cables. Lay power lines separately using ducts. Review the installation environment to reduce noise interference. 123 Section Board Replacement Serial communications mode Host Link, slave-initiated communications Indicator status The COMM indicators are flashing, but there is no response from the host. Status I/O memory information, etc. A transmis--sion error has not been detected at the host. ----- --- Communications parameters and baud rate settings in the PC Setup do not correspond with the settings at the host. 124 Cause 9-2 Remedy There is a hardware error in the reception circuit. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board. Cables are incorrectly wired. There is a hardware error in the reception circuit. Check the wiring and correct. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board. Adapters such as the NT-AL001-E are incorrectly wired or set. --- The communications conditions and baud rate do not match the settings at the host. Check the program at the host. When unsolicited communications are used with Host Link mode, there must be a response returned from the host for every command sent from the Serial Communications Board. Reset the parameters in the PC Setup and at the host correctly. Section Board Replacement 9-2 9-2-2 Protocol Macros Serial communications mode Serial communications mode is not set to protocol macro. Serial communications mode is set to protocol macro. Indicator display Status information, etc. I/O memory --- --- Bits 12 to 15 (Serial Communications Mode) of DM 6555/DM 6550 are set to a value other than 6 Hex. Serial communications Set bits 12 to 15 of mode is not set correctly. DM 6555/DM 6550 to 6 Hex. (protocol macros). The COMM indicators do not flash at all. (Communications has not been electrically established.) The PMCR(––) instruction was executed, but IR 20708 or IR 20712 (Protocol Macro Executing Flag) did not turn ON. IR 20708 or IR 20712 (Protocol Macro Executing Flag) is set as a NO execution condition for PMCR(––). The Error Flag (SR 25503) is ON. The program is incorrect. Set IR 20708 or IR 20712 (Protocol Macro Executing Flag) as a NC execution condition for PMCR(––). The problem cause is one of the following: – The data range for the PMCR(––) instruction C operand is incorrect. – The number of data words in the S or D operand exceeds 129. The sequence number specified in bits 00 to 11 of the PMCR(––) instruction C operand is a value other than 000 Hex to 999 BCD. Check the PMCR(––) instruction C, S, and D operand settings for errors. The error code in IR 20408 to IR 20411 or IR 20412 to IR 20415 is 2 Hex (Sequence Number Error). The error code in IR 20408 to IR 20411 or IR 20412 to IR 20415 is 3 Hex (Receive Data Write Range Overflow Error) Cause The specified communications sequence number does not exist in the protocol data. The data range of the specified area is exceeded when data is being written to or read from the I/O memory of the CPU Unit. Remedy Set bits 00 to 11 of the PMCR(––) instruction C operand to a value between 000 and 999 BCD. Check whether the communications sequence number is correct. Specify another area, or reduce the size of the data to be sent or received. 125 Section Board Replacement Serial communications mode Serial communications mode is set to protocol macro. Serial communications mode is set to protocol macro. Indicator display Status information, etc. I/O memory Cause Remedy The COMM indicators do not flash at all. (Communications have not been electrically established.) The PMCR(––) instruction is executed, but IR 20708 or IR 20712 (Protocol Macro Executing Flag) does not turn ON. IR 20708 or IR 20712 (Protocol Macro Executing Flag) turns ON when the PMCR(––) instruction is executed, but data cannot be sent or received properly. IR 20708 or IR 20712 (Protocol Macro Executing Flag) momentarily turns ON when the PMCR(––) instruction is executed, but it does not remain ON. IR 20708 or IR 20712 (Protocol Macro Executing Flag) remains ON when the PMCR(––) instruction is executed without setting the monitoring time for individual sequences Send data has already been transmitted, but there is no response from the remote node. The error code in IR 20408 to IR 20411 or IR 20412 to IR 20415 is 4 Hex (Protocol Data Syntax Error). The protocol data in the Serial Communications Board is incorrect. Use CX-Protocol to correct and transfer the protocol data. Send processing is not executed. The send wait time specified in communications sequence step units is too long. Use CX-Protocol to check whether the send wait time is correctly set. IR 20711 or IR 20715 (Forced Abort Bit) are ON. Forced Abort Bit is force- Release the Forced set. Abort Bit The sequence is running and does not end (the words allocated in the CIO Area is in receive status). Protocol macro data is not set correctly. The contents of the words allocated in settings in the PC Setup do not match those of the remote node. The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on. The error code in IR 20100 to IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is not 0. The wiring is faulty. --- 126 9-2 The PC Setup settings such as the baud rate and frame format differ from those of the remote node. The setting of the 2/4-wire switch for the RS-422A/485 port does not match the actual wiring (WIRE). Wiring of adapters (e.g., NT-AL001-E) is faulty. Hardware failure. Use CX-Protocol transmission line trace to check whether the protocol data and PC Setup settings are correct. Review the PC Setup settings. Review the remote node settings and the program (including the baud rate, frame format, and so on). Check the wiring. Turn ON the terminating resistances of the Serial Communications Board and the last node. Turn OFF the terminating resistances of other nodes. Replace the Serial Communications Board. Section Board Replacement Serial communications mode Serial communications mode is set to protocol macro. (Continued) 9-2 Indicator display Status information, etc. I/O memory Cause The COMM indicators are flashing, but the Serial Communications Board cannot perform communications or a communications error sometimes occurs. A transmission error occurs. The error code in IR 20100 to IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is not 0. The settings in the PC Setup do not match those of the remote node. --- The PC Setup settings such as the baud rate and frame format differ from those of the remote node. The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on. Review the PC Setup settings. Because response from the remote node is received too fast, the data received from the time the data send processing was completed until the Send operation was completed is discarded. Check the settings of the remote node and review programming (i.e., the timing of sending response data). --- The transmission timing is too fast for the remote node to receive data. Set or increase the transmission wait time (time to await data transmission) in step units. The error code in IR 20100 to IR 20103 for port 1 or IR 20108 to IR 20111 for port 2 is not 0. The wiring is faulty. Check the wiring. The RS-422A/485 port terminating resistance setting is incorrect. Turn ON the terminating resistance of the Serial Communications Board and the last node by using the terminating resistance switch. Turn OFF the terminating resistance of other nodes. The COMM indicators are flashing, but the Serial Communications Board cannot perform communications or a communications error sometimes occurs. Data is received through CX-Protocol transmission line trace, but the protocol macros behave as if no data is received. The remote node sometimes returns no response to sent data. Response may be received by performing retries. A transmission error sometimes occurs. Adapters such as the NT-AL001-E are incorrectly wired, or the terminating resistance setting is incorrect. A communications error frequently occurs due to noise and so on. Remedy Review the remote node settings and the program (including the baud rate, frame format, and so on). Use shielded twisted pair cables. House the communications cables in a different duct from those for power lines and so on. Review the operating environment to prevent noise problems. Note The following table shows the measures to correct error codes provided in IR 20408 to IR 20411 for port 1 and IR 20412 to IR 20415 for port 2. Error code Indicator Error details Cause Remedy 0 Hex No display Normal --- --- 1 Hex No display Reserved --- --- 127 Section Board Replacement Error code 2 Hex 3 Hex 4 Hex Indicator Error details No display Sequence number error ERR/ALM : Flashing ERR/ ALM: Flashing Receive data write range overflow error Protocol data syntax error 9-2 Cause Remedy The communications sequence number specified in bits 00 to 11 of the PMCR(––) instruction’s C operand is not registered. The data range of the specified area is exceeded when data is being written to or read from the I/O memory of the CPU Unit. Correct the communications sequence number. There is a code that cannot be executed during protocol execution. Check the following items and correct the problem. Use CX-Protocol to register the specified communications sequence number. For operand specification: Check the PMCR(––) instruction S and D operand specifications. For direct specification of link words: Use CX-Protocol to check the specified range. • Check whether the total specified number of link words in the area (O1, O2, I1, I2) exceeds 128. • The same area with link word specification is used by both ports 1 and 2. • A write instruction with constant specification is specified. • An EM Area read/write instruction is specified as an interrupt notification. • There are more than 30 write attributes set for one message. • The length of a send/receive message is set to 0 bytes. • The length of a send/receive message is longer than 127 bytes. • No messages are registered for matrix reception. • Both RTS/CTS flow control and Xon/Xoff flow control are set for the same transmission line. 5 Hex ERR/ ALM: Flashing Protocol macro execution error during port initialization The PMCR instruction was executed while the port was being initialized. Check if the PMCR instruction was executed during any one of the following processes. • While the serial communications port was being restarted. • While the serial communications mode in the PC system setup of the Serial Communications Board was being modified using the STUP instruction. • While the serial communications mode in the PC system setup of the Serial Communications Board was being modified using the Programming Device. 128 Section Board Replacement 9-2 9-2-3 1:N NT Link Mode Serial communications mode Indicator display Status information, etc. Serial communications mode is not set to NT Link. --- --- Serial communications mode is set to NT Link. --The COMM indicators do not flash at all. (Communications have not been electrically established.) The SD and --COMM indicators are flashing, but the Serial Communications Board cannot communicate with the Programmable Terminal (PT). I/O memory Cause Remedy Bits 12 to 15 Serial communica(Serial Commu- tions mode is not nications Mode) set correctly. of DM 6555/ DM 6550 are set to a value other than 5 Hex. Set bits 12 to 15 (Serial Communications Mode) of DM 6555/ DM 6550 to 5 Hex. --- There is a hardware error. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board. --- There is a setting error for the PT serial port. Correct the PT serial port settings. The I:N NT Link unit number of the PT is incorrect. Review the NT Link unit number of the PT. The same 1:N NT Link unit number has been set for more than one PT The maximum allowable NT Link unit number is incorrectly set for the system. Cables are incorrectly connected. Review the PC Setup settings. Review the wiring or switch settings. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect. Adapters such as the NT-AL001-E are incorrectly wired or set. A communications error frequently occurs due to noise, etc. There is a PT hardware error. Review the wiring and installation environment. Replace the PT. 129 Section Board Replacement Serial communications mode Serial communications mode is set to NT Link. Indicator display The COMM indicators are flashing, but a communications error sometimes occurs in the PT. Status information, etc. --- I/O memory --- Cause 9-3 Remedy Cables are incorrectly connected. Review the wiring or switch settings. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect. Check whether the terminating resistances of the host computer and the last node are set to ON, and the terminating resistances of other nodes are set to OFF. Adapters such as the NT-AL001-E are incorrectly wired or set. A communications error frequently occurs due to noise, etc. The communications monitoring time for the PT is insufficient. The load on the PC is too high. Review the wiring and installation environment. Increase the number of retries for the PT as required. Increase the communications monitoring time for the PT. Lighten the load on the PC. Reduce the number of PTs connected to each serial port by using other ports for some of the PTs. Adjust the timeout and retry settings in the PT. Note The PT serial port must be set for a 1:N NT Link. The PT will not be able to communicate with a Serial Communications Board if the PT is set for a 1:1 NT Link. 9-3 Cleaning and Inspection Use the cleaning and inspection methods described here for daily maintenance of the devices. 9-3-1 Cleaning To keep the Serial Communications Board in optimum condition, regularly clean the Serial Communications Board as follows: • Wipe the surface of the Serial Communications Board daily with a soft, dry cloth. • If any dirt cannot be removed with a dry cloth, moisten the cloth with a mild detergent diluted to 2%, and squeeze out any excess moisture before wiping the Serial Communications Board. • Do not adhere materials, such as gum, vinyl, or tape to the Serial Communications Board for long periods of time. Doing so may cause stains on the device. Remove any adhered materials when cleaning the Serial Communications Board. Note Never use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths. 130 Section Board Replacement 9-3 9-3-2 Inspection To keep the Serial Communications Board in optimum condition, regular inspections must be performed. Normally, inspect the devices once every six months or every year. Inspect the devices at more regular intervals when they are being used in environments subject to high temperatures, high humidity, or high dust levels. Materials for Inspection Prepare the following materials before performing any inspections. Materials Required Daily For daily inspection, a Phillips screwdriver, flat-blade screwdriver, tester (or digital voltmeter), industrial strength alcohol, and all-cotton cloth are required. Materials Required Occasionally For some inspections, a synchroscope, a pen oscilloscope, a temperature gauge, and a hygrometer will be required. Inspection Items Inspect the following items to check whether the Serial Communications Board is operating within the specified criterion. If the Serial Communications Board is not within the criterion, improve the ambient operating environment and readjust the device. Item Details Operating Check the ambient temperature environment and the temperature inside the control panel. Check the ambient humidify and the humidity inside the control panel. Check for accumulated dust. Installation Check that the Serial Communications Board is mounted securely. Criterion 0 to 55°C Inspection materials Temperature gauge 10% to 90% RH Hygrometer (no condensation or icing) No dust Visual inspection Board must be --mounted securely. Check for loose screws on the communications cables. Screws must be Phillips securely screwdriver tightened. Check for damaged communications cables. Cables should be fully intact. Visual inspection 131 Section Board Replacement 9-4 9-4 Board Replacement A malfunction of the Serial Communications Board may affect the operation of remote communications devices, so be sure to perform repairs or replace the faulty Board promptly. Make sure a spare Serial Communications Board is available to replace a faulty one, so that functionality can be restored without delay. 9-4-1 Precautions Observe the following precautions when replacing the Serial Communications Board. • Always turn OFF the power to the PC before replacing the Serial Communications Board. • Be sure to check that the Serial Communications Board replacing the faulty one is not defective. • If the defective Serial Communications Board is to be dispatched to the manufacturer for repair, be sure to include documentation stating the nature of the fault in as much detail as possible, and send to your nearest OMRON branch or sales office, listed at the back of this manual. If the contacts are defective, clean the contacts with a clean all-cotton cloth moistened with industrial-strength alcohol. Remove any cloth particles before mounting the Serial Communications Board. Note Turn OFF the power to all serial external devices when replacing the Serial Communications Board to prevent malfunctions. 9-4-2 Settings after Replacing the Board After replacing the Serial Communications Board, make sure that wiring and settings, such as hardware switch settings, the settings for the Serial Communications Board in the PC Setup, and protocol macro data are the same as the Serial Communications Board that was replaced. Note 1. If the CPU Unit is to be replaced, transfer to the replacement CPU Unit the contents of the Holding Areas and DM Area required for operation before starting operation. If the relationship between the DM Area and Holding Area and the program is not maintained, unexpected malfunctions may result. 2. The PC Setup of the Serial Communications Board is saved in the DM Area of the CPU Unit. If the CPU Unit is to be replaced, either transfer the PC Setup data to the CX-Programmer or CX-Protocol before replacing the CPU Unit or reset the PC Setup. 9-4-3 Replacement Procedure Standard System Protocols, Host Link Communications, No-protocol Communications, 1:1 Data Links, or NT Links 1, 2, 3... 1. Turn OFF the power to the PC to which the Serial Communications Board to be replaced is mounted, and to all serially connected external devices. 2. Disconnect the communications cables connected to the Serial Communications Board to be replaced, and also remove the Serial Communications Board. 3. Set the hardware switches of the replacement Board to the same settings of the Serial Communications Board being replaced before mounting, as follows: • Terminating resistance switch (TERM) • The 2/4-wire switch (WIRE) 132 Section Board Replacement 9-4 4. Turn ON the power of the PC to which the replacement Serial Communications Board is mounted, and to all serially connected external devices, and start operating the system. 5. Check from the indicators and status display that the system is operating normally. Protocol Macros Designed with CX-Protocol 1, 2, 3... 1. Connect Programming Console or CX-Protocol to the PC to which the replacement Serial Communications Board is mounted, and switch to PROGRAM mode. 2. Save the protocol macro data using the CX-Protocol. Refer to the CX-Protocol Operation Manual (W344) for details. 3. Turn OFF the power to the PC to which the Serial Communications Board to be replaced is mounted, and to all serially connected external devices. 4. Disconnect the communications cables connected to the Serial Communications Board to be replaced, and also remove the Serial Communications Board. 5. Set the hardware switches of the replacement Board to the same settings of the Serial Communications Board being replaced before mounting, as follows: • Terminating resistance switch (TERM) • The 2/4-wire switch (WIRE) 6. Turn ON the power of the PC to which the replacement Serial Communications Board is mounted, and to all serially connected external devices, and start operating the system. 7. Switch the CPU Unit to PROGRAM mode, and using the CX-Protocol, transfer the protocol macro data to the Serial Communications Board. 8. Switch the CPU Unit to MONITOR mode, and start operating the system. 9. Check from the indicators and status display that the system is operating normally. Note 1. The protocol macro data for the Serial Communications Board is stored in the flash memory of the Serial Communications Board. 2. When protocol macro data designed with the CX-Protocol is used, a backup of the protocol macro data created from the CX-Protocol must be transferred to the Serial Communications Board after replacing. 3. The PC Setup of the Serial Communications Board is allocated to the DM Area saved in the battery backup of the CPU Unit, and if the user-designed macro data is not used, the PC Setup can be used as before, simply by setting the hardware. 133 Appendix A Introduction Appendices B to N provide information on the standard system protocols provided with the CX-Protocol, the Serial Communications Boards. Refer to 5-7 Using Protocol Macros for details on using PMCR(––). Using Standard System Protocols Standard system protocols can be executed merely by specifying the sequences number to be executed in the second operand of PMCR(––) and settings the data described in the appendices in the proper format starting at the word specified with the third operand of PMCR(––). The data received as a response to executing the sequence will be automatically stored starting at the word specified with the fourth operand of PMCR(––). Procedure 1, 2, 3... 1. Set the port number (1 or 2) and the sequence number as BCD values in the first operand of PMCR(––). 2. Specify the address of the first word containing the data required for the sequence as the second operand (S: First word of send data) of PMCR(––). 3. Specify the address of the first word where respond data is to be stored as the third operand (D: First receive data storage word) of PMCR(––). Unless there is a reason to specify otherwise, set 0000 Hex in D at the initial value. Example The following data would be used to execute sequence number 600 in the CompoWay/F Master Protocol for a transmission with ASCII conversion. PMCR(––) Communications port: 1 (BCD) Communications sequence number: 600 (BCD) 1600 S D S: Send Data Word Allocation (3rd Operand) First word of send data +0 Number of send data words +1 (Undefined) Node number +2 (Undefined) SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data S+0 Number of send data words (4 digits BCD) 0005 to 0128 BCD S+1 (Undefined) Node No. (2 digits BCD) 00 to 99 S+2 MRC (2 digits Hex) SRC (2 digits Hex) Set the command code for the required service S+3 Number of send bytes (4 digits BCD) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 0492 S+4 on Send data (4-digit Hex) The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent. 135 Appendix A Introduction D: Receive Data Word Allocation (4th Operand) Receive data storage words +0 Number of receive data words +1 Response code +2 Receive data Offset Contents (data format) Data D+0 Number of receive data words (4 digits BCD) 0003 to 0128 BCD D+1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. D+2 on Receive data (4-digit Hex) The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here. Standard System Protocols The following 13 standard system protocols are provided with the CX-Protocol and the Serial Communications Boards. Protocol name Function CompoWay/F Master E5K Digital Controller Read E5K Digital Controller Write E5ZE Temperature Controller Read E5ZE Temperature Controller Write E5J Temperature Controller ES100 Controller Protocol for sending CompoWay/F commands as a Master to OMRON CompoWay/F slave components and receiving responses. Protocol for controlling an E5K Digital Controller via the Board. Procedures for reading the MV the operating parameter settings Protocol for controlling an E5K Digital Controller via the Board. Procedures for writing set points and operating parameters. Protocol for controlling an E5ZE Temperature Controller via the Board. Procedures for reading measured temperature and operating parameter settings. Protocol for controlling an E5ZE Temperature Controller via the Board. Procedures for writing control temperatures and operating parameters. Protocol for controlling a E5J Temperature Controller via the Board. Procedures for writing set points, reading output amounts, and reading/writing operating parameters. Protocol for controlling an ES100 Controller via the Board. Procedures for writing adjustment parameters, reading operation amounts, and writing/reading operating parameters. Protocol for controlling a Intelligent Signal Processor via the Board. Procedures for writing comparison values and reading display values are set. Protocol for controlling a Bar Code Reader via the Board. Procedures for controlling the Bar Code Reader in remote mode, reading the data that has been read by the Bar Code Reader, and reading/writing operating parameters. Intelligent Signal Processor V500/V520 Bar Code Reader 3Z4L Laser Micrometer F200/F300/F350 Visual Inspection Systems Protocol for controlling a Laser Micrometer via the Board. Procedures for controlling the Laser Micrometer in remote mode, reading measured data, and writing/reading operating parameters. Protocol for controlling a Visual Inspection System via the Board. Procedures for controlling the Visual Inspection System in remote mode, reading measured values, and writing/reading operating parameters. V600/V620 ID Controllers Hayes modem AT commands Protocol for controlling an ID Controller via the Board. Procedures for performing Read/Write operations of the ID Controller and writing/reading operating parameters. Protocol for controlling a Hayes modem (AT commands) via the Board. Procedures for initialization of the modem, dialing, data transmission, switching to escape mode, and disconnecting the line. Note Some of the standard system protocols do not allow communications with 32 nodes for one execution of a sequence (for 1:N connections). For example, it’s not possible when the number of Units in send data is 1 to 25 for unit numbers 00 to 31 (e.g., in the temperature controller read sequences). This restriction is due to a limit in the number of words that can be transferred between the CPU Unit and the Serial Communications Board. These sequences, however, allow the unit numbers of connected devices to be specified in the send data. You can thus set different unit numbers in the send data and execute PMCR(––) for the same sequence as many times as required for all unit numbers. 136 Appendix B CompoWay/F Master Protocol The CompoWay/F Master Protocol is used to send CompoWay/F commands with the CS1-series PC serving as the host (master). CompoWay/F CompoWay/F is a protocol used by many OMRON components for serial communications. A host computer of a PC can function as a host (master) to send CompoWay/F commands (message frames) to OMRON components, which function as slaves. The components will return responses to these commands. Using CompoWay/F commands, the host can read/write data, settings, and operating status to control the operation of the components. CompoWay/F has the following features. • The same message frame format is used, eliminating the need for special protocols for each component. The same commands can thus be used for serial communications with all CompoWay/F components. • The CompoWay/F protocol conforms to OMRON’s standard FINS command protocol, providing compatibility with other networks and more flexible expansions in the future. The CompoWay/F Master Protocol is provided as a standard system protocol to enable the CQM1H-series PC to executed read/write sequences for CompoWay/F commands. System Configuration for Standard System Protocol RS-232C Connections CQM1H-series PC: Host CompoWay/F response OMRON CompoWay/F component: Slave RS-232C CompoWay/F command RS-422A/485 Connections CQM1H-series PC: Host CompoWay/F response RS-422A/485 CompoWay/F command OMRON CompoWay/F components: Slaves 137 Appendix B CompoWay/F Master Protocol Communications Specifications Item Specification Transmission path connections Communications Multipoint Synchronization Start-stop Baud rate 1,200/2,400/4,800/9,600/19,200 bps Default: 9,600 bps ASCII Transmitted code Data length RS-232C, RS-422A/485, 4-wire half-duplex, 2-wire half-duplex 7 bits or 8 bits (Default: 7 bits) Note: A 7-bit code is used with 0 added to the beginning. 1 bit or 2 bits (Default: 2 bits) Stop bits Error detection Horizontal parity (none, even, or odd) (Default: Even) BCC (block check character) *1: Start-stop Sync Data Configuration for Protocol Macros LRC, 1 byte, equivalent to binary Transmission Procedure The PC or host computer serving as the master sends a command and the component serving as the slave returns a response for the command message contained in the command. One response message is returned for each command message. The movement of command and response messages is shown below. Master (PC or host computer) Command message Slave (component) Response message Command and Response Formats Note In the following diagrams “Hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters. Command Format Node No. 1 byte Subaddress Command ”00” ”0” 2 bytes 2 bytes 1 byte Node No. Subaddress End code ”00” ”00” 2 bytes 2 bytes Text Data 1 byte 1 byte 1 byte 1 byte Response Format 1 byte 2 bytes Response Text Data (See note.) Note 1. Data is not saved in the response if there is a command frame error (i.e., if the end code is not 00 or 0F). 2. Other values are possible for the subaddress and SID. 138 Appendix B CompoWay/F Master Protocol Command Frame Contents Item Meaning STX A code, 02 Hex, indicating the beginning of a communications frame (text). This code must always be set as the first byte. Node number The node number identifies the source of the command frame. Specify “XX” to broadcast a transmission. There will be no response made to a broadcast. Subaddress Set “00” for most components. Other values must be set for special components. SID Set “0” for most components. Other values must be set for special components. Command and text The command and required text are placed here. Refer to the command codes and text for individual sequences. MRC and SRC The command code specifies the service being used. Refer to the command codes and text for individual sequences. ETX A code, 03 Hex, indicating the end of text. BCC The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the STX to the ETX. Response Frame Contents Item Meaning STX A code, 02 Hex, indicating the beginning of a communications frame (text). This code must always be set as the first byte. Node number The node number identifies the source of the command frame. “XX” is specified to broadcast a transmission. There will be no response made to a broadcast. Subaddress “00” for most components. Other values must be set for special components. SID “0” for most components. Other values must be set for special components. End code (See note.) The results of executing the command frame. Note: The response code (MRES and SRES) indicates the results for the command code; the end code indicates the results for the command frame. These are not the same. Response and text MRES and SRES The response and requested text are placed here. Refer to the response and text for individual sequences. The response code specifies the results of processing the service requested by the command code. Refer to the response codes and text for individual sequences. ETX A code, 03 Hex, indicating the end of text. BCC The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the STX to the ETX. 139 Appendix B CompoWay/F Master Protocol Note The end codes are described in the following table. End code Name Meaning “00” Normal end The command frame was processed normally without any of the following errors. “0F” Command error The specified command could not be executed. Refer to the response code for more information. “10” Parity error A parity error was detected for one of the characters that was received. “11” Framing error A framing error was detected for one of the characters that was received. “12” Overrun error A overrun error was detected for one of the characters that was received. “13” BCC error The BCC for the receive frame was incorrect. “14” Format error An illegal command or illegal character was received in the command and text (characters other than ASCII 0 to 9 or A to F). “16” Subaddress error The receive frame contained an illegal subaddress. “18” Frame length error The receive frame was too long. Example The command and response frames for a K3N-series Intelligent Signal Processor are shown below. Command Frame Node No. Subaddress Command Text SID Data Command code Command Data contents VARIABLE AREA READ Command code “01” “01” Data contents Variable type Address VARIABLE AREA WRITE “01” “02” Variable type Address PARAMETER AREA READ “02” “01” Address PARAMETER AREA WRITE “02” “02” Parameter type Parameter type No. of elements “00” No. of elements No. of elements Address No. of elements PROCESSOR STATUS READ CONTROLLER STATUS READ ECHOBACK TEST “05” “06” “08” “03” “01” “01” Text data OPERATION COMMAND “30” “05” Command code “00” Write data Write data Response Format Node No. Subaddress End code Response Text Data Command code 140 Response code Appendix B CompoWay/F Master Protocol Example: VARIABLE AREA READ The following command and text are used to read the present value, maximum value, minimum value, and status of the Intelligent Signal Processor. Command and Text 2 bytes 1, 2, 3... 2 bytes Variable type First read address No. of elements 2 bytes 4 bytes 4 bytes 1. Variable Type Variable type “C0” Contents Present value, maximum value, minimum value, status , and comparison value 2. First Read Address Specify the address of the data to be read in 4 digits Hex. 3. Number of Elements: 4 Digits Hex Number of elements “0001” Process Read the data and end normally. Note If “0000” is specified, nothing will be read and a normal end will be returned. A parameter error will occur for any settings other than “0000” and “0001.” Response Text Response code 2 bytes 2 bytes 1, 2, 3... 4 bytes Read data 8 bytes 1. Response Code: MRES, SRES Response code Meaning “0000” Normal end “1001” Command too long “1002” Command too short “1100” Parameter error “1101” Area type error “1103” First address range error “2203” Operating error 2. Read Data The specified data is returned in 8 digits of hexadecimal data. 141 Appendix B CompoWay/F Master Protocol CompoWay/F Master Protocol Sequences The CompoWay/F Master Protocol provides six communications sequences that can be used for the following: • Converting to ASCII data or not converting to ASCII data • Sending to a specified Unit or broadcasting • Specifying from the command code or specifying from the subaddress and SID. Structure of the Protocol The following table shows the structure of the CompoWay/F Master Protocol. Sequence No. Communications sequence name Function 600 Send with ASCII conversion, with response Converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word. 601 Broadcast with ASCII conversion, no response Send with no conversion and with response 602 603 604 605 Ladder interface Send word allocation Yes Receive word allocation Yes A broadcast version of sequence No. 600. No responses are received. Sends specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. This is the same as sequence No. 600 without data conversion and can be used when conversion is not required. Yes No Yes Yes Broadcast with no conversion and no response General-purpose send with no conversion and with response A broadcast version of sequence No. 602. No responses are received. Sends specified data beginning with the subaddress and SID to the specified Unit. The response is stored starting at the specified word. This sequence can be used whenever it is necessary to specify the subaddress or SID. Yes No Yes Yes General-purpose broadcast with no conversion and no response A broadcast version of sequence No. 604. No responses are received. Yes No Sequence No. 600 can be used for the normal CompoWay/F Master function (ASCII conversion, specification from command code). Refer to the communications specifications for the OMRON CompoWay/F component to which the command is being sent and set the command code and required data starting at the words specified for the 3rd operand of PMCR(260). The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is described next. 142 Appendix B CompoWay/F Master Protocol CompoWay/F Message Frames and PMCR(260) Operands The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is shown below, using communications sequence No. 600 as an example. Command Frame Node No. Variable type Subaddress First read address Command No. of elements Send data PMCR(260) Instruction PMCR(260) #1600 Communications port: 1 Send/receive sequence number: 600 (0258 Hex) S S Number of send data words D S+1 (Undefined) Node number S+2 S+3 Number of send bytes S+4 Send data S+5 S+6 Response Frame Node No. Subaddress Response code Receive data Read data Response code Receive data End code PMCR(260) Instruction PMCR(260) #1600 S D D Number of receive data words D+1 Response code D+2 Receive data D+3 Send with ASCII Conversion, with Response: (Sequence No. 600) This sequence converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word. 143 Appendix B CompoWay/F Master Protocol Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Node No. +2 MRC SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 to 0128 +1 (Undefined) Node No. (2 digits BCD) 00 to 99 +2 MRC (2 digits Hex) SRC (2 digits Hex) Set the command code for the required service +3 Number of send bytes (4 digits BCD) +4 on Send data (4-digit Hex) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0 to 984 decimal The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent. Note 1. Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent. 2. When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units. Send data words Send frame 1 2 3 4 “56” “78” “12” “34” 5 6 7 8 Receive Data Word Allocation (3rd Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Response code +2 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 to 0128 +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 on Receive data (4-digit Hex) The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here. Note When ASCII data is converted to hexadecimal data, data is stored starting from the receive data word with the largest offset. This is done because ladder programming handles data in 4-byte units. Receive frame “01” “23” “45” Receive data words “67” 4 5 6 7 0 1 2 3 144 Appendix B CompoWay/F Master Protocol Example: The following example illustrates reading the present value from a K3N-series Intelligent Signal Processor. CS1-series PC CompoWay/F response Read data = present value Intelligent Signal Processor K3N--FLK1/2/3/4/5/6 CompoWay/F command VARIABLE AREA READ Command code: 01 01 First read address Sequence No. 600 (Send with ASCII Conversion, with Response) is used. The specified data beginning with the command code is converted ASCII and sent to the Intelligent Signal Processor with the specified node number. The response is converted to hexadecimal and stored starting at the specified word. The command frame for reading the present value for a K3N--FLK1/2/3/4/5/6 Intelligent Signal Processor (command code 01 01) is shown below. The following data is specified in the operands for PMCR(260). • Rightmost byte of S+1: Node number (2 digits BCD) • S+2: Command code: MRC + SRC = “0101” • S+4 on: Send data = Variable type + first read address + 00 + number of elements. STX Node No. (02Hex) (×101) (×101) Subaddress 00 Command code SID 0 Send data ETX MRC SRC Variable type First read address (Note) Always 00 No. of elements 01 01 C0 0000 00 0001 BCC (03Hex) Data in shaded portions is specified in the PMCR(260) instruction. Note A first read address of 0000 specifies the present value. An address of 0001 specifies the maximum value; 0002, the minimum value; and 0003, the status. The response frame is shown below. The response code and receive data are stored according to the operands for PMCR(260) as follows: • D+1: Response code • D+2 and on: Receive data STX Node No. Subaddress End code Command code MRC (02 Hex) (×101) (×101) 01 Response code Receive data Note 1 Read data (Note 2) SRC 01 00 00 0000 ETX BCC (03 Hex) Data in shaded portions is stored at the location specified by the operand in the PMCR(260) instruction. Note 1. Response Codes Response code Meaning “0000” Normal end “1001” Command too long “1002” Command too short “1100” Parameter error “1101” Area type error “1103” First address range error “2203” Operating error 2. The read data is returned as 4-digit hexadecimal as follows: F0019999 to 00099999 Hex. 145 Appendix B CompoWay/F Master Protocol The 2nd and 3rd operands of the PMCR(260) instruction are specified as follows. Send Data Word Allocation (2nd Operand of PMCR(260)) Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 +1 (Undefined) Node No. (2 digits BCD) 0000 Hex +2 MRC (2 digits Hex) SRC (2 digits Hex) 0101 Hex +3 Number of send bytes (4 digits BCD) 0012 (BCD) +4 Send data (12 digits Hex) C000 Hex +5 0000 Hex +6 0001 Hex Receive Data Word Allocation (3rd Operand of PMCR(260)) Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) EX is stored at reception (0004) +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 Receive data (8 digits Hex) The normal end response code is 0000. The 4 bytes of read data. +3 Broadcast with ASCII Conversion, No Response (Sequence No. 601) This sequence converts the specified data beginning with the command code to ASCII and broadcasts it. No responses are received. Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 MRC +2 SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 to 0128 +1 (Undefined) --- +2 MRC (2 digits Hex) +3 Number of send bytes (4 digits BCD) +4 on Send data (4-digit Hex) SRC (2 digits Hex) Set the command code for the required service Number of data bytes from the next byte after the command code until the byte just before the ETX. 0 to 984 decimal The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent. Note 1. Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent. 146 Appendix B CompoWay/F Master Protocol 2. When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units. Send data words Send frame 1 2 3 4 “56” “78” “12” “34” 5 6 7 8 Receive Data Word Allocation (3rd Operand of PMCR(260)) None. (Specify a dummy value for the operand, such as #0000.) Send with No Conversion and with Response (Sequence No. 602) This sequence sends the specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data. Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Node No. +2 MRC SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 to 0128 +1 (Undefined) Node No. (2 digits BCD) 00 to 99 +2 MRC (2 digits Hex) SRC (2 digits Hex) Set the command code for the required service +3 Number of send bytes (4 digits BCD) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0 to 492 decimal +4 on Send data +0 +1 +2 +3 +4 +5 The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent. +6 etc. Receive Data Word Allocation (3rd Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Response code +2 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 to 0128 +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 on Receive data (Hex) The data from just after the response code until just before the ETX is stored here without conversion. +0 +1 +2 +3 +4 +5 +6 etc. 147 Appendix B CompoWay/F Master Protocol Broadcast with No Conversion and No Response (Sequence No. 603) This sequence broadcasts the specified data beginning with the command code No responses are received and no conversions are performed on the send data. Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 MRC +2 SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 to 0128 +1 (Undefined) --- +2 MRC (2 digits Hex) +3 Number of send bytes (4 digits BCD) +4 on Send data SRC (2 digits Hex) Set the command code for the required service Number of data bytes from the next byte after the command code until the byte just before the ETX. 0 to 492 decimal +0 +1 +2 +3 +4 +5 +6 etc. Receive Data Word Allocation (3rd Operand of PMCR(260)) None. (Specify a dummy value for the operand, such as #0000.) 148 The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent. Appendix B CompoWay/F Master Protocol General-purpose Send with No Conversion and with Response (Sequence No. 604) This sequence sends the specified data beginning with the subaddress and SID to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data. Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Node No. +2 (Undefined) Subaddress +3 (Undefined) SID +4 Number of send bytes +5 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0128 +1 Always 00 Hex Node No. (2 digits BCD) 00 to 99 +2 MRC (2 digits Hex) Subaddress (2 digits Hex) Specify the subaddress of the device being communicated with. +3 Always 00 Hex SID (1 digit Hex) Set the service ID of the required service (e.g., retries). +4 Number of send bytes (4 digits BCD) Number of data bytes from the MCR until the byte just before the ETX. +5 on Send data 0 to 490 decimal +0 +1 +2 +3 +4 +5 The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent. +6 etc. Receive Data Word Allocation (3rd Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Response code +2 Response data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 to 0128 +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 on Receive data The data from just after the response code until just before the ETX is stored here without conversion. +0 +1 +2 +3 +4 +5 +6 etc. 149 Appendix B CompoWay/F Master Protocol General-purpose Broadcast with No Conversion and No Response (Sequence No. 605) This sequence broadcasts the specified data beginning with the subaddress and SID. No responses are received and no conversions are performed on the send data. Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 +2 (Undefined) Subaddress +3 (Undefined) SID +4 Number of send bytes +5 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0128 +1 Always 0000 Hex --- +2 MRC (2 digits Hex) Subaddress (2 digits Hex) Specify the subaddress of the device being communicated with. +3 Always 00 Hex SID (1 digit Hex) Set the service ID of the required service (e.g., retries). +4 Number of send bytes (4 digits BCD) Number of data bytes from the MCR until the byte just before the ETX. +5 on Send data 0 to 490 decimal +0 +1 +2 +3 +4 +5 +6 etc. Receive Data Word Allocation (3rd Operand of PMCR(260)) None. (Specify a dummy value for the operand, such as #0000.) 150 The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent. Appendix B CompoWay/F Master Protocol Connections Connection methods between a Serial Communications Board and the K3N-series Intelligent Signal Processor are shown below. RS-232C • RS-232C connections are one-to-one. • The max. cable length is 15 m. Use an RS-232C optical interface (Z3RN) when extending the transmission line beyond 15 m. • Use shielded, twisted-pair cable. Intelligent Signal Processor Serial Communications Board RS-232C RS-232C Abbrevi- Pin ation No. Pin No. Abbreviation FG 1 1 FG SG 9 7 SG SD 2 2 SD RD 3 3 RD RTS 4 4 RTS CTS 5 5 CTS DSR 7 6 DSR DTR 8 20 DTR Shield Abbreviation Pin No. Pin No. Abbreviation SG SD 9 2 3 5 3 2 SG SD DTR 4 5 7 8 7 8 6 4 FG 1/ Shell RD RTS CTS DSR TX RX K3N--FLK1 Intelligent Signal Processor RS-232C Serial Communications Board RS-232C MAX232C or equivalent MAX232C or equivalent RD RTS CTS DSR TX RX DTR Shield K3N--FLK4 151 Appendix B CompoWay/F Master Protocol RS-422 4-wire Connections • RS-422 connections can be one-to-one, or one-to-N when a 3G2A9-AL001 Link Adapter is used. A maximum of 32 Serial Communications Boards can be connected in one-to-N systems. • The total cable length can be 500 m max. • Use shielded, twisted-pair cable. • Be sure to turn ON the terminating resistance switches at the device at each end of the transmission line. Serial Communications Board RS-422 Intelligent Signal Processor Abbreviation Pin AbbreviNo. ation Shell SN751177N or equivalent Terminal 220 Ω block switch 6 8 1 2 *1: Set the 2-/4-wire switch to the 4-wire setting. *2: Turn ON the terminating resistance switch. 220 Ω Shield The terminator (220 Ω) is set with the terminal block switch. RS-485 2-wire Connections • RS-485 connections can be one-to-one or one-to-N. A maximum of 32 Serial Communications Boards can be connected in one-to-N systems. • The total cable length can be 500 m max. • Use shielded, twisted-pair cable. • Be sure to turn ON the terminator switches only in the devices at each end of the transmission line. Serial Communications Board RS-485 Intelligent Signal Processor Turn OFF all terminal block switches except at the end-station. Abbreviation Termi- Abbrevinal ation Shell 220 Ω SN751177N or equivalent Terminal block switch 1 2 + Shield *1: Set the 2-/4-wire switch to the 2-wire setting. Intelligent Signal Processor end-station *2: Turn ON the terminating resistance switch. Termi- Abbrevinal ation Terminal 220 Ω block switch ON + Terminal block switch ON at the end station. Shield Note SYSMAC BUS Wired Remote I/O devices cannot be connected. 152 Appendix C E5K Digital Controller Read Protocol The E5K Digital Controller Read Protocol reads and controls various parameters in remote mode for the Controller connected to the Serial Communications Board via RS-232C or RS-485 cable. Structure of the Protocol The following table shows the structure of the E5K Digital Controller Read Protocol. Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation Yes 000 Read process value Reads the process value. 001 Read set point during SP ramp Yes Yes 002 Read MV Reads the set point during SP ramp. Reads the MV (heating, cooling). Yes Yes 003 Read set point Reads the set point. Yes Yes 004 Read alarm value Reads alarm value 1, 2. Yes Yes 005 Read proportional band, integral time, and derivative time Reads the proportional band, integral (reset) time, and derivative (rate) time Yes Yes 006 Read cooling coefficient Reads the cooling coefficient. Yes Yes 007 Read dead band Reads the dead band. Yes Yes 008 Read manual reset value Reads the manual reset value. Yes Yes 009 Read hysteresis Yes Yes 010 Read control period Yes Yes 011 Yes Yes 012 Read SP ramp time unit and set value Read LBA detection time Reads the hysteresis (heating, cooling). Reads the control period (heating, cooling). Reads the SP ramp time unit and SP ramp set value. Reads the LBA detection time. Yes Yes 013 Read MV at stop and PV error Yes Yes 014 Read MV limits Reads the MV at stop and the MV at PV error. Reads the MV limits. Yes Yes 015 Read input digital filter Reads the input digital filter. Yes Yes 016 Read alarm hysteresis Reads the alarm 1, 2 hysteresis. Yes Yes 017 Read input shifts Reads the input shift limits. Yes Yes 018 Read level 0 parameters Reads parameters in level 0. Yes Yes 019 Read level 1 parameters 1 Reads parameters in level 1. Yes Yes 020 Read level 1 parameters 2 Reads parameters in level 1. Yes Yes 021 Read level 2 parameters 1 Reads parameters in level 2. Yes Yes 022 Read level 2 parameters 2 Reads parameters in level 2. Yes Yes 023 General-purpose read Reads the value of the specified parameter. Yes Yes Note Ladder Interface Settings YES: User settings are required for the 2nd or 3rd operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 2nd operand (S). Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D). 153 Appendix C E5jK Digital Controller Read Protocol Connection Configuration The connection configuration for using the E5K Digital Controller Read Protocol is shown below. RS-232C Connection E5K CQM1H Serial Communications Board RS-232C port → Serial Communications Board E5K RS-232C: D-sub 9 pin female Signal name RS-232C: Terminal block Pin No. Terminal No. Signal name Shielded cable Note 1. The communications configuration is a one-to-one configuration and the maximum cable length is 15 m. 2. Use a shielded twisted-pair cable (AWG28i or greater) for the cable. RS-485 Connection CQM1H E5K Serial Communications Board RS-485 port → E5K → Up to 31 Units can be connected. E5K → Note 1. The communications configuration is a one-to-one configuration or a one-to-N configuration. In the oneto-N configuration, up to 32 units including the Serial Communications Board can be connected. 2. The maximum cable length is 500 m. Use a shielded twisted-pair cable for the cable (AWG28i or greater). 3. Connect a terminator only at both ends of the transmission path. For instance, in the example shown below, connect a terminator to the Serial Communications Board and Unit No.30 and do not connect any 154 Appendix C E5jK Digital Controller Read Protocol terminator to units No.0 to No.29. Use a resistance of 120Ω (1/2W) for the terminators (the total resistance of both ends must be 54Ω or more). Serial Communications Board RS-485: D-sub 9 pin female Pin No. Shielded cable A<B: [1] Mark A>B: [0] Space E5CK (No. 0) E5CK (No. 30) RS-485: Terminal block RS-485: Terminal block Terminal No. Terminal No. Terminator (120 /2 W) Read Process Value (Sequence No. 000) Reads the process value and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Process value Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Process value (4 digits BCD) Scaling lower limit to upper limit Read Set Point during SP Ramp (Sequence No. 001) Reads the set point during the SP ramp and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set point during SP ramp 155 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Set point during SP ramp (4 digits BCD) Set point lower limit to upper limit Read MV (Sequence No. 002) Reads the MV (manipulated variable) for heating and cooling and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 MV (heating) +2 MV (cooling) Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 MV (heating) (4 digits BCD) F050 to 1050, 0000 to 1050 for heating/cooling control F indicates a negative value. +2 MV (cooling) (4 digits BCD) F050 to 1050 F indicates a negative value. Read Set Point (Sequence No. 003) Reads the set point and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set point Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Set point (4 digits BCD) Set point lower limit to upper limit Read Alarm Value (Sequence No. 004) Reads alarm value 1 and alarm value 2 and stores the results in the specified words. 156 Appendix C E5jK Digital Controller Read Protocol Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Alarm value 1 +2 Alarm value 2 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Alarm value 1 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +2 Alarm value 2 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Read Proportional Band, Integral Time, and Derivative Time (Sequence No. 005) Reads the proportional band, integral time, and derivative time and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Proportional band +2 Integral time +3 Derivative time Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0004 +1 Proportional band (4 digits BCD) 0000 to 9999 +2 Integral time (4 digits BCD) 0000 to 3999 +3 Derivative time (4 digits BCD) 0000 to 3999 Read Cooling Coefficient (Sequence No. 006) Reads the cooling coefficient and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) Unit No. 157 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Cooling coefficient Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Cooling coefficient (4 digits BCD) 0001 to 9999 Read Dead Band (Sequence No. 007) Reads the dead band and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Dead band Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Dead band (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Read Manual Reset Value (Sequence No. 008) Reads the manual reset value and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Manual reset value Offset 158 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Manual reset value (4 digits BCD) 0000 to 1000 Appendix C E5jK Digital Controller Read Protocol Read Hysteresis (Sequence No. 009) Reads the hysteresis for heating and for cooling and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Hysteresis (heating) +2 Hysteresis (cooling) Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Hysteresis (heating) (4 digits BCD) 0001 to 9999 +2 Hysteresis (cooling) (4 digits BCD) 0001 to 9999 Read Control Period (Sequence No. 010) Reads the control period for heating and for cooling and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Control period (heating) +2 Control period (cooling) Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Control period (heating) (4 digits BCD) 0001 to 0099 +2 Control period (cooling) (4 digits BCD) 0001 to 0099 Read SP Ramp Time Unit and Set Value (Sequence No. 011) Reads the SP ramp time unit and SP ramp set value and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. 159 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 SP ramp time unit +2 SP ramp set value Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 SP ramp time unit (4 digits BCD) 0000: s, 0001: hr +2 SP ramp set value (4 digits BCD) 0000 to 9999 Read LBA Detection Time (Sequence No. 012) Reads the LBA (loop break alarm) detection time and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 LBA detection time Offset 160 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 LBA detection time (4 digits BCD) 0000 to 9999 Appendix C E5jK Digital Controller Read Protocol Read MV at Stop Time and at PV Error (Sequence No.013) Reads the MV at stop time and at PV error and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 MV at stop time +2 MV at PV error Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 MV at stop time (4 digits BCD) F050 to 1050 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +2 MV at PV error (4 digits BCD) F050 to 1050 F indicates a negative value. Read MV Limits (Sequence No. 014) Reads the MV upper limit, MV lower limit, and MV change rate limit and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 MV upper limit +2 MV lower limit +3 MV change rate limit Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0004 +1 MV upper limit (4 digits BCD) MV lower limit + 1 to 1050 0000 to 1050 for heating/cooling control +2 MV lower limit (4 digits BCD) F050 to MV upper limit –1 F indicates a negative value values. A050 to 1050 for heating/cooling control A indicates a negative value. +3 MV change rate limit (4 digits BCD) 0000 to 1000 161 Appendix C E5jK Digital Controller Read Protocol Read Input Digital Filter (Sequence No. 015) Reads the input digital filter and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Input digital filter Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Input digital filter (4 digits BCD) 0000 to 9999 Read Alarm Hysteresis (Sequence No. 016) Reads the alarm 1 hysteresis and alarm 2 hysteresis and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Alarm 1 hysteresis +2 Alarm 2 hysteresis Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +2 Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 Read Input Shift Limits (Sequence No. 017) Reads the input shift upper limit and input shift lower limit and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset 162 Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Input shift upper limit +2 Input shift lower limit Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Input shift upper limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +2 Input shift lower limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Read Level 0 Parameters (Sequence No. 018) Reads parameters in level 0 (process value, set point during SP ramp, MV (heating), MV (cooling), and set point) from multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Process value +2 Set point during SP ramp +3 MV (heating) +4 MV (cooling) +5 Set point ~ 1st unit ~ +36 Process value +37 Set point during SP ramp +38 MV (heating) +39 MV (cooling) +40 Set point 8th unit (max.) 163 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 5 + 1 +1 1st unit Process value (4 digits BCD) Scaling lower limit to upper limit +2 1st unit Set point during SP ramp (4 digits BCD) Set point lower limit to upper limit +3 1st unit MV (heating) (4 digits BCD) F050 to 1050 F indicates a negative value. 0000 to 1050 for heating/cooling control +4 1st unit MV (cooling) (4 digits BCD) 0000 to 1050 +5 1st unit Set point (4 digits BCD) Set point lower limit to upper limit +40 (max.) 8th unit Set point (4 digits BCD) Set point lower limit to upper limit Read Level 1 Parameters 1 (Sequence No. 019) Reads parameters in level 1 (alarm value 1, alarm value 2 , alarm value 3, proportional band, integral time, and derivative time) from multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Alarm value 1 +2 Alarm value 2 +3 Alarm value 3 +4 Proportional band +5 Integral time +6 Derivative time ~ 164 1st unit ~ +43 Alarm value 1 +44 Alarm value 2 +45 Alarm value 3 +46 Proportional band +47 Integral time +48 Derivative time 8th unit (max.) Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 6 + 1 +1 1st unit Alarm value 1 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +2 1st unit Alarm value 2 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +3 1st unit Alarm value 3 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +4 1st unit Proportional band (4 digits BCD) 0001 to 9999 +5 1st unit Integral time (4 digits BCD) 0000 to 3999 +6 1st unit Derivative time (4 digits BCD) 0000 to 3999 +48 (max.) 8th unit Derivative time (4 digits BCD) 0000 to 3999 Read Level 1 Parameters 2 (Sequence No. 020) Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 165 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Cooling coefficient +2 Dead band +3 Manual reset value +4 Hysteresis (heating) +5 Hysteresis (cooling) +6 Control period (heating) +7 Control period (cooling) ~ 1st unit ~ Cooling coefficient +50 +51 Dead band +52 Manual reset value +53 Hysteresis (heating) +54 Hysteresis (cooling) +55 Control period (heating) +56 Control period (cooling) Offset 8th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 7 + 1 +1 1st unit Cooling coefficient (4 digits BCD) 0001 to 9999 +2 1st unit Dead band (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +3 1st unit Manual reset value (4 digits BCD) 0000 to 1000 +4 1st unit Hysteresis (heating) (4 digits BCD) 0001 to 9999 +5 1st unit Hysteresis (cooling) (4 digits BCD) 0001 to 9999 +6 1st unit Control period (heating) (4 digits BCD) 0001 to 0099 +7 1st unit Control period (cooling) (4 digits BCD) 0001 to 0099 +56 (max.) 166 8th unit Control period (cooling) (4 digits BCD) 0001 to 0099 Appendix C E5jK Digital Controller Read Protocol Read Level 2 Parameters 1 (Sequence No. 021) Reads parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop, MV at PV Error, MV upper limit, MV lower limit, and MV change rate limit) from multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 SP ramp time unit +2 SP ramp set value +3 LBA detection time +4 MV at stop +5 MV at PV error +6 MV upper limit +7 MV lower limit +8 MV change rate limit ~ 1st unit ~ +57 SP ramp time unit +58 SP ramp set value +59 LBA detection time +60 MV at stop +61 MV at PV error +62 MV upper limit +63 MV lower limit +64 MV change rate limit 8th unit (max.) 167 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 8 + 1 +1 1st unit SP ramp time unit (4 digits BCD) 0000: s, 0001: hr +2 1st unit SP ramp set value (4 digits BCD) 0000 to 9999 +3 1st unit LBA detection time (4 digits BCD)} 0000 to 9999 +4 1st unit MV at stop (4 digits BCD) F050 to 1050 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +5 1st unit MV at PV error (4 digits BCD) F050 to 1050 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +6 1st unit MV upper limit (4 digits BCD) MV lower limit + 1 to 1050 0000 to 1050 for heating/cooling control +7 1st unit MV lower limit (4 digits BCD) F050 to MV upper limit –1 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +8 1st unit MV change rate limit (4 digits BCD) 0000 to 1000 +64 (max.) 8th unit MV change rate limit (4 digits BCD) 0000 to 1000 Read Level 2 Parameters 2 (Sequence No. 022) Reads parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) from multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset 168 (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Input digital filter +2 Alarm 1 hysteresis +3 Alarm 2 hysteresis +4 Alarm 3 hysteresis +5 Input shift upper limit +6 Input shift lower limit 1st unit ~ ~ +43 Input digital filter +44 Alarm 1 hysteresis +45 Alarm 2 hysteresis +46 Alarm 3 hysteresis +47 Input shift upper limit +48 Input shift lower limit Offset 8th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 6 + 1 +1 1st unit Input digital filter (4 digits BCD) 0000 to 9999 +2 1st unit Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +3 1st unit Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 +4 1st unit Alarm 3 hysteresis (4 digits BCD) 0001 to 9999 +5 1st unit Input shift upper limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +6 1st unit Input shift lower limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +48 (max.) 8th unit Input shift lower limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. 169 Appendix C E5jK Digital Controller Read Protocol General-purpose Read (Sequence No. 023) Reads the specified parameter and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 (Undefined) Number of send data words Unit No. +2 (Undefined) Parameter No. Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Parameter No. (2 digits BCD) Refer to the manual for the E5K. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Read data (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Note To read parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No. 075) in advance. 170 Appendix D E5K Digital Controller Write Protocol The E5K Digital Controller Write Protocol writes and controls various settings in remote mode for the Controller connected to the Serial Communications Board via RS-232C or RS-485 cable. Note Negative values cannot be written. All values must be set as unsigned BCD. Structure of the Protocol The following table shows the structure of the E5K Digital Controller Write Protocol. Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation No 050 Write set point Writes the set point. 051 Write alarm value Writes alarm value 1, 2. Yes No 052 Write proportional band, integral time, and derivative time Writes the proportional band, integral time, and derivative time. Yes No 053 Write cooling coefficient Writes the cooling coefficient. Yes No 054 Write dead band Writes the dead band. Yes No 055 Write manual reset value Writes the manual reset value. Yes No 056 Write hysteresis Writes the hysteresis (heating, cooling) Yes No 057 Write control period Yes No 058 Write SP ramp time units and set value Write LBA detection time Writes the control period (heating, cooling) Writes the SP ramp time unit and SP ramp set value. Writes the LBA detection time. Yes No Yes No Writes the MV at stop and the MV at PC error. Writes the MV limits. Yes No 061 Write MV at stop time and PV error Write MV limits Yes No 062 Write input digital filter Writes the input digital filter. Yes No 063 Write alarm hysteresis Writes alarm 1, 2 hysteresis. Yes No 064 Write input shift values Writes the input shift values. Yes No 065 Write level 0 parameters Writes parameters in level 0. Yes No 066 Write level 1 parameters 1 Writes parameters in level 1. Yes No 067 Write level 1 parameters 2 Writes parameters in level 1. Yes No 068 Write level 2 parameters 1 Writes parameters in level 2. Yes No 069 Write level 2 parameters 2 Writes parameters in level 2. Yes No 070 General-purpose write Yes No 071 Yes No 072 Switch to level 0 (software reset) Run/stop Writes the value of the specified parameter. Switches the setting level to level 0. Initiates Run or Stop. Yes No 073 Remote/local Yes No 074 Execute/cancel AT Switches the mode to remote or local mode. Executes or cancels AT. Yes No 075 Switch to level 1 Switches the setting level to level 1. Yes No 076 Software reset Resets the E5K. Yes No 059 060 Note Ladder Interface Settings YES: User settings are required for the 2nd or 3rd operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 2nd operand (S). Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D). 171 Appendix D E5jK Digital Controller Write Protocol Connections The connections are the same as that for the E5K Digital Controller Read Protocol. Write Set Point (Sequence No. 050) Writes the set point. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. set point +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Set point (4 digits BCD) Set point lower limit to upper limit Receive Data Word Allocation (3rd Operand of PMCR) None. Write Alarm Value (Sequence No. 051) Writes alarm value 1 and alarm value 2. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. +2 Alarm value 1 +3 Alarm value 2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Alarm value 1 (4 digits BCD) 0000 to 999 +3 Alarm value 2 (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Proportional Band, Integral Time, and Derivative Time (Sequence No. 052) Writes the proportional band, integral time, and derivative time. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) +2 +3 Integral time +4 Derivative time Offset 172 Unit No. Proportional band Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Proportional band (4 digits BCD) 0001 to 9999 +3 Integral time (4 digits BCD) 0000 to 3999 +4 Derivative time (4 digits BCD) 0000 to 3999 Appendix D E5jK Digital Controller Write Protocol Receive Data Word Allocation (3rd Operand of PMCR) None. Write Cooling Coefficient (Sequence No. 053) Writes the cooling coefficient. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Cooling coefficient +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Cooling coefficient (4 digits BCD) 0001 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Dead Band (Sequence No. 054) Writes the dead band. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Dead band +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Dead band (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Manual Reset Value (Sequence No. 055) Writes the manual reset value. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Manual reset value +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Manual reset value (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Hysteresis (Sequence No. 056) Writes the hysteresis for heating and for cooling. 173 Appendix D E5jK Digital Controller Write Protocol Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Hysteresis (heating) +3 Hysteresis (cooling) Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Hysteresis (heating) (4 digits BCD) 0001 to 9999 +3 Hysteresis (cooling) (4 digits BCD) 0001 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Control Period (Sequence No. 057) Writes the control period for heating and for cooling. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Control period (heating) +3 Control period (cooling) Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Control period (heating) (4 digits BCD) 0001 to 0099 +3 Control period (cooling) (4 digits BCD) 0001 to 0099 Receive Data Word Allocation (3rd Operand of PMCR) None. Write SP Ramp Time Unit and Set Value (Sequence No. 058) Writes the SP ramp time unit and SP ramp set value. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 SP ramp time unit +3 SP ramp set value Offset 174 Unit No. +2 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 SP ramp time unit (4 digits BCD) 0000: 0001: +3 SP ramp set value (4 digits BCD) 0000 to 9999 Minutes Hours Appendix D E5jK Digital Controller Write Protocol Receive Data Word Allocation (3rd Operand of PMCR) None. Write LBA Detection Time (Sequence No. 059) Writes the LBA detection time. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. LBA detection time +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 LBA detection time (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write MV at Stop Time and at PV Error (Sequence No. 060) Writes the MV at stop time and the MV at PV error. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 MV at stop time +3 MV at PV error Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 MV at stop time (4 digits BCD) 0000 to 1050 +3 MV at PV error (4 digits BCD) 0000 to 1050 Receive Data Word Allocation (3rd Operand of PMCR) None. Write MV Limits (Sequence No. 061) Writes the MV upper limit, MV lower limit, and MV change rate limit. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. MV upper limit +2 +3 MV lower limit +4 MV change rate limit Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 MV upper limit (4 digits BCD) MV lower limit +1 to 1050 Heating/cooling control time: 0000 to 1050 +3 MV lower limit (4 digits BCD) 0000 to MV upper limit –1 +4 MV change rate limit (4 digits BCD) 0000 to 1000 175 Appendix D E5jK Digital Controller Write Protocol Receive Data Word Allocation (3rd Operand of PMCR) None. Write Input Digital Filter (Sequence No. 062) Writes the input digital filter. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Input digital filter +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Input digital filter (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Alarm Hysteresis (Sequence No. 063) Writes the alarm 1 hysteresis and alarm 2 hysteresis. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Alarm 1 hysteresis +3 Alarm 2 hysteresis Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +3 Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Input Shift Value (Sequence No. 064) Writes the input shift upper limit and input shift lower limit. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 +2 Input shift upper limit +3 Input shift lower limit Offset 176 Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Input shift upper limit (4 digits BCD) 0000 to 9999 +3 Input shift lower limit (4 digits BCD) 0000 to 9999 Appendix D E5jK Digital Controller Write Protocol Receive Data Word Allocation (3rd Operand of PMCR) None. Write Level 0 Parameters (Sequence No. 065) Writes parameters (set points) in level 0 to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. 1st unit Set point +3 (Undefined) +4 Unit No. 2nd unit Set point +5 ~ ~ (Undefined) +16 Unit No. 8th unit (max.) Set point +17 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Set point (4 digits BCD) Set point lower limit to upper limit +17 (max.) 8th unit Set point (4 digits BCD) Set point lower limit to upper limit Receive Data Word Allocation (3rd Operand of PMCR) None. 177 Appendix D E5jK Digital Controller Write Protocol Write Level 1 Parameters 1 (Sequence No. 066) Writes parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and derivative time) to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. +3 Alarm value 1 +4 Alarm value 2 +5 Alarm value 3 +6 Proportional band +7 Integral time +8 Derivative time 1st unit ~ +51 ~ (Undefined) Unit No. +52 Alarm value 1 +53 Alarm value 2 +54 Alarm value 3 +55 Proportional band +56 Integral time +57 Derivative time Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 7 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Alarm value 1 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +4 1st unit Alarm value 2 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +5 1st unit Alarm value 3 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +6 1st unit Proportional band (4 digits BCD) 0001 to 9999 +7 1st unit Integral time (4 digits BCD) 0000 to 3999 +8 1st unit Derivative time (4 digits BCD) 0000 to 3999 +57 (max.) 8th unit Derivative time (4 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. 178 0000 to 3999 Appendix D E5jK Digital Controller Write Protocol Write Level 1 Parameter 2 (Sequence No. 067) Writes parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. Cooling coefficient +3 +4 Dead band +5 Manual reset value +6 Hysteresis (heating) +7 Hysteresis (cooling) +8 Control period (heating) +9 Control period (cooling) ~ +58 1st unit ~ (Undefined) Unit No. Cooling coefficient +59 +60 Dead band +61 Manual reset value +62 Hysteresis (heating) +63 Hysteresis (cooling) +64 Control period (heating) +65 Control period (cooling) Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 8 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Cooling coefficient (4 digits BCD) 0001 to 9999 +4 1st unit Dead band (4 digits BCD) 0000 to 9999 +5 1st unit Manual reset value (4 digits BCD) 0000 to 1000 +6 1st unit Hysteresis (heating) (4 digits BCD) 0001 to 9999 +7 1st unit Hysteresis (cooling) (4 digits BCD) 0001 to 9999 +8 1st unit Control period (heating) (4 digits BCD) 0001 to 0099 +9 1st unit Control period (cooling) (4 digits BCD) 0001 to 0099 +65 (max.) 8th unit Control period (cooling) (4 digits BCD) 0001 to 0099 Receive Data Word Allocation (3rd Operand of PMCR) None. 179 Appendix D E5jK Digital Controller Write Protocol Write Level 2 Parameters 1 (Sequence No. 068) Writes parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop time, MV at PV error, MV upper limit, MV lower limit, and MV change rate limit) to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 +2 Number of units (Undefined) Unit No. SP ramp time unit +3 +4 SP ramp set value +5 LBA detection time +6 MV at stop +7 MV at PV error +8 MV upper limit +9 MV lower limit +10 MV change rate limit 1st unit ~ +65 ~ (Undefined) Unit No. +66 SP ramp time unit +67 SP ramp set value +68 LBA detection time +69 MV at stop +70 MV at PV error +71 MV upper limit +72 MV lower limit +73 MV change rate limit Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 9 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit SP ramp time unit (4 digits BCD) 0000 to 0001 +4 1st unit SP ramp set value (4 digits BCD) 0000 to 9999 +5 1st unit LBA detection time (4 digits BCD) 0000 to 9999 +6 1st unit MV at stop (4 digits BCD) 0000 to 1050 +7 1st unit MV at PV error (4 digits BCD) 0000 to 1050 +8 1st unit MV upper limit (4 digits BCD) MV lower limit +1 to 1050 +9 1st unit MV lower limit (4 digits BCD) 0000 to MV upper limit –1 +10 1st unit MV change rate limit (4 digits BCD) 0000 to 1000 +73 (max.) 8th unit MV change rate limit (4 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. 180 0000 to 1000 Appendix D E5jK Digital Controller Write Protocol Write Level 2 Parameters 2 (Sequence No. 069) Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 Input digital filter +4 alarm 1 hysteresis +5 alarm 2 hysteresis +6 alarm 3 hysteresis +7 Input shift upper limit +8 Input shift lower limit 1st unit ~ +51 ~ (Undefined) Unit No. +52 Input digital filter +53 alarm 1 hysteresis +54 alarm 2 hysteresis +55 alarm 3 hysteresis +56 Input shift upper limit +57 Input shift lower limit Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 7 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Input digital filter (4 digits BCD) 0000 to 9999 +4 1st unit Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +5 1st unit Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 +6 1st unit Alarm 3 hysteresis (4 digits BCD) 0001 to 0099 +7 1st unit Input shift upper limit (4 digits BCD) 000 to 9999 +8 1st unit Input shift lower limit (4 digits BCD) 000 to 9999 +57 (max.) 8th unit Input shift lower limit (4 digits BCD) 000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. 181 Appendix D E5jK Digital Controller Write Protocol General-purpose Write (Sequence No. 070) Writes the specified parameter. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Parameter No. Write data +3 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Parameter No. (2 digits BCD) Refer to the manual of E5K. +3 Write data (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Note To write parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No. 075) in advance. Switch to Level 0 (Software Reset) (Sequence No. 071) Resets the operation of the E5K and waits until communications are enabled. This sequence can be executed for multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Note When this sequence is executed, a software reset command is issued and the operation of the E5K is reset (equivalent to turning on the power supply). About five seconds will be required until communications are enabled. 182 Appendix D E5jK Digital Controller Write Protocol Run/Stop (Sequence No. 072) Switches the mode to Run or Stop according to the command code. This sequence can be executed for multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. 1st unit Command code +3 (Undefined) +4 Unit No. 2nd unit Command code +5 ~ ~ (Undefined) +16 Unit No. 8th unit (max.) Command code +17 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Command code (4 digits BCD) 0000: Run 0001: Stop +17 (max.) 8th unit Command code (4 digits BCD) 0000: Run 0001: Stop Receive Data Word Allocation (3rd Operand of PMCR) None. Remote/Local (Sequence No. 073) Switches to remote operation or local operation according to the command mode. This sequence can be executed for multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 +2 +3 +4 +5 Number of send data words Number of units (Undefined) Unit No. (Undefined) Unit No. +17 2nd unit Command code ~ +16 1st unit Command code ~ (Undefined) Unit No. 8th unit (max.) Command code 183 Appendix D E5jK Digital Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Command code (4 digits BCD) 0000: Local 0001: Remote +17 (max.) 8th unit Command code (4 digits BCD) 0000: Local 0001: Remote Receive Data Word Allocation (3rd Operand of PMCR) None. Execute/Cancel AT (Sequence No. 074) Executes or cancels AT (autotuning) according to the command code. This sequence can be executed for multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. 1st unit Command code +3 (Undefined) +4 Unit No. 2nd unit Command code +5 ~ ~ (Undefined) +16 Unit No. 8th unit (max.) Command code +17 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Command code (4 digits BCD) 0000: Stop 0001: Execute AT 40% 0002: Execute AT 100% +17 (max.) 8th unit Command code (4 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. 184 0000: Stop 0001: Execute AT 40% 0002: Execute AT 100% Appendix D E5jK Digital Controller Write Protocol Switch to Level 1 (Sequence No. 075) Switches the setting level to level 1 (setup mode, extended mode). This sequence can be executed for multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Software Reset (Sequence No. 076) Resets the operation of the E5K (equivalent to turning on the power supply). This sequence can be executed for multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Note Communications with the E5K are disabled for about five seconds after this sequence is executed. 185 Appendix E E5ZE Temperature Controller Read Protocol The E5ZE Temperature Controller Read Protocol reads and controls various parameters in remote mode for the Temperature Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable. Note All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks. Structure of the Protocol The following table shows the structure of the E5ZE Temperature Controller Read Protocol Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation Yes 100 Read set point Reads the set points. 101 Read process value Reads the process values. Yes Yes 102 Read output value Reads the output values. Yes Yes 103 Reads the set points, process values, and output values. Reads the proportional bands, integral times, and derivative times. Reads the control periods. Yes Yes Yes Yes 105 Read set point, process value, and output value Read proportional band, integral time, and derivative time Read control period Yes Yes 106 Read output mode Reads the output modes. Yes Yes 107 Read alarm mode Reads the alarm modes. Yes Yes 108 Read alarm temperature Reads the alarm temperatures. Yes Yes 109 Read hysteresis Reads the hysteresis. Yes Yes 110 Read operation status Reads the operation status. Yes Yes 111 Read error status Reads the error status. Yes Yes 112 Read setting unit Reads the setting units. Yes Yes 113 Read input shift value Reads the input shift values. Yes Yes 114 Read manual reset value Reads the manual reset values. Yes Yes 115 Read ramp value Reads the ramp values. Yes Yes 116 Read present set point Reads the present set points. Yes Yes 117 Read output value limits Reads the output value limits. Yes Yes 118 Yes Yes Yes Yes Yes Yes Yes Yes Yes 123 Read cooling coefficient Reads the output value change rate limits. Reads the HB alarm and HS alarm valid channels. Reads the heater burnout/SSR failure detection currents. Reads the heater currents and SSR leakage currents. Reads the dead bands and overlap bands. Reads the cooling coefficients. Yes 122 Read output value change rate limit Read HB alarm and HS alarm valid channels Read heater burnout/SSR failure detection currents Read heater current and SSR leakage current Read dead band/overlap band Yes Yes 104 119 120 121 Note Ladder Interface Settings YES: User settings are required for the 2nd or 3rd operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 2nd operand (S). Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D). 187 Appendix E E5ZE Temperature Controller Read Protocol Connections This section shows connections for using the E5ZE Temperature Controller Read Protocol. RS-232C Connections CQM1H E5ZE Serial Communications Board RS-232C port → RS-232C Signal Pin abbreviNo. ation Signal name Abbreviation Signal direction Pin No. Signal ground or common return line Send data SG – 7 SD Output 2 Receive data RD Input 3 Request to send RS Output 4 Clear to send CS Input 5 Data set ready DR Input 6 Data terminal ready ER Output 20 Disabled (Do not connect.) NC – 1, 8 to 19, 21 to 25 Serial Communications Board E5ZE RS-232C: D-sub 9-pin female Signal name Pin No. RS-232C: D-sub 9-pin female Shielded cable LT1181CS or equivalent Pin Signal No. name Note 1. The maximum communications cable length is 15 m. Use a shielded twisted-pair cable (AWG28 or greater) for the cable. 2. Use a 25-pin D-sub Plug (OMRON XM2A-2501). 3. Use XM2S-2511 Hood (OMRON) or an equivalent. 188 Appendix E E5ZE Temperature Controller Read Protocol RS422/485 Connections • RS-485 Abbreviation Signal direction 1 Pin No. Disabled (Do not connect.) Signal name – – 2 Disabled (Do not connect.) – – 3 Signal ground SG – 4 Terminal B (+ side) B I/O 5 Terminal A (– side) A I/O Turn off the communications switch to disconnect terminating resistance. Serial Communications Board RS-485: D-sub 9-pin female SN751177N or equivalent Terminating resistance E5ZE 240 Ω RS-485: Terminals Signal name Pin No. Terminal Signal name Shielded cable E5ZE RS-485: Terminals Shielded cable Terminating resistance Terminal Signal name Terminating resistance Note Terminal block pins 1 and 2 cannot be connected. If these blocks are used, operation of the E5ZE may fail. 189 Appendix E E5ZE Temperature Controller Read Protocol • RS-422A Pin No. Signal name Signal direction 1 Receive data B RDB Input 2 Receive data A RDA Input 3 Signal ground SG – 4 Send data B SDB Output 5 Send data A SDA Output Serial Communications Board RS-422A: D-sub Terminating 9-pin female resistance Signal Pin No. Turn off the communications switch to disconnect terminating resistance. SN751177N or equivalent E5ZE RS-422A: Terminals name Terminal Shielded cable Terminating resistance Abbreviation Terminating resistance Signal name Terminating resistance Terminal Shielded cable block Terminal Terminating resistance Signal name 240Ω Terminating resistance 190 Appendix E E5ZE Temperature Controller Read Protocol Switch Settings This section shows the switch settings for using the E5ZE Temperature Controller Read Protocol. Communications Parameter DIP Switch DTS-4 1 2 3 4 Pins 3 and 4: Terminating resistance Pins 1 and 2: RS-422A/RS-485 Factory defaults: All OFF OFF OFF 1 and 2 RS-422A or RS-485 OFF OFF ON ON 3 4 OFF 3 4 OFF OFF ON OFF 1 2 ON ON RS-485 3 4 RS-422A 3 4 Parameter Terminating ON resistance 1 2 Pins 3 and 4 Unit Number Switch Setting 0 1 2 3 4 5 6 7 8 9 A B C D E F Unit No. 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F Factory defaults Baud Rate DIP Switch ON 1 2 3 45 6 7 8 Factory default: 9,600 bps (pin 1 ON, pin 2 OFF) ON 2 ON 1 ON 2 ON 1 2,400 2 4,800 1 9,600 2 19,200 1 Baud rate (bps) Pins 1 and 2 Read Set Point (Sequence No. 100) Reads the set points and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) Unit No. 191 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set point (rightmost 4 digits) +2 Set point (leftmost 1 digit) ~ Offset Channel 0 ~ +15 Set point (rightmost 4 digits) +16 Set point (leftmost 1 digit) Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Set point (leftmost 1 digit) (1 digit BCD) F indicates a negative value. +15 Channel 7 Set point (rightmost 4 digits) (4 digits BCD) +16 Channel 7 Set point (leftmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer the manual for the E5ZE. F indicates a negative value. Read Process Value (Sequence No. 101) Reads the process values and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Process value (rightmost 4 digits) +2 Process value (leftmost 1 digit) +3 Process value (rightmost 4 digits) +4 Process value (leftmost 1 digit) ~ 192 Channel 0 Channel 1 ~ +15 Process value (rightmost 4 digits) +16 Process value (leftmost 1 digit) Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Process value (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Process value (leftmost 1 digit) (1 digit BCD) F indicates a negative value. +15 Channel 7 Process value (rightmost 4 digits) (4 digits BCD) +16 Channel 7 Process value (leftmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. F indicates a negative value. Read Output Values (Sequence No. 102) Reads the output values of the control outputs and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Output value +2 Cooling output value +3 Output value +4 Cooling output value ~ Channel 0 Channel 1 ~ +15 Output value +16 Cooling output value Channel 7 193 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Output value (4 digits BCD) 0000 to 1000 +2 Channel 0 Cooling output value (4 digits BCD) 0000 to 1000 +3 Channel 1 Output value (4 digits BCD) 0000 to 1000 +4 Channel 1 Cooling output value (4 digits BCD) 0000 to 1000 +15 Channel 7 Output value (4 digits BCD) 0000 to 1000 +16 Channel 7 Cooling output value (4 digits BCD) 0000 to 1000 Read Set Point, Process Value, and Output Value (Sequence No. 103) Reads the set points, process values, and output values and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to OF Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set point (rightmost 4 digits) +2 Set point (leftmost 1 digit) +3 Process value (rightmost 4 digits) +4 Process value (leftmost 1 digit) +5 Output value ~ +36 Set point (leftmost 1 digit) +38 Process value (rightmost 4 digits) +40 194 ~ Set point (rightmost 4 digits) +37 +39 Channel 0 Process value (leftmost 1 digit) Output value Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0041 +1 Channel 0 Set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Set point (leftmost 1 digit) (1 digit BCD) +3 Channel 0 Process value (rightmost 4 digits) (4 digits BCD) +4 Channel 0 Process value (leftmost 1 digit) (1 digit BCD) +5 Channel 0 Output value (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. 0000 to 1000 Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +36 Channel 7 Set point (rightmost 4 digits) (4 digits BCD) +37 Channel 7 Set point (leftmost 1 digit) (1 digit BCD) +38 Channel 7 Process value (rightmost 4 digits) (4 digits BCD) +39 Channel 7 Process value (leftmost 1 digit) (1 digit BCD) +40 Channel 0 Output value (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. 0000 to 1000 Read Proportional Band, Integral Time, and Derivative Time (Sequence No. 104) Reads the proportional bands (constant P), integral times (constant I), and derivative times (Constant D) and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Constant P +2 Constant I +3 Constant D ~ +22 Channel 0 ~ Constant P +23 Constant I +24 Constant D Channel 7 195 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0025 +1 Channel 0 Constant P (4 digits BCD) 0000 to 9999 +2 Channel 0 Constant I (4 digits BCD) 0000 to 3999 +3 Channel 0 Constant D (4 digits BCD) 0000 to 3999 +22 Channel 7 Constant P (4 digits BCD) 0000 to 9999 +2 3 Channel 7 Constant I (4 digits BCD) 0000 to 3999 +24 Channel 7 Constant D (4 digits BCD) 0000 to 3999 Read Control Period (Sequence No. 105) Reads the control periods and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Control period +2 Cooling control period +3 Control period +4 Cooling control period ~ Channel 1 ~ +15 Control period +16 Cooling control period Offset Channel 0 Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Control period (4 digits BCD) 0001 to 0099 +2 Channel 0 Cooling control period (4 digits BCD) 0001 to 0099 196 +15 Channel 7 Control period (4 digits BCD) 0001 to 0099 +16 Channel 7 Cooling control period (4 digits BCD) 0001 to 0099 Appendix E E5ZE Temperature Controller Read Protocol Read Output Mode (Sequence No. 106) Reads the output modes (normal/reverse) and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Offset Set code Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Set code (2 digits Hex) 00 to FF Read Alarm Mode (Sequence No. 107) Reads the alarm modes and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Alarm 1 set code +2 (Undefined) Alarm 2 set code +3 (Undefined) Alarm 1 set code +4 (Undefined) Alarm 2 set code ~ Channel 0 Channel 1 ~ +15 (Undefined) Alarm 1 set code +16 (Undefined) Alarm 2 set code Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Alarm 1 set code (2 digits Hex) 00 to 0C +2 Channel 0 Alarm 2 set code (2 digits Hex) 00 to 0C +15 Channel 7 Alarm 1 set code (2 digits Hex) 00 to 0C +16 Channel 7 Alarm 2 set code (2 digits Hex) 00 to 0C 197 Appendix E E5ZE Temperature Controller Read Protocol Read Alarm Temperatures (Sequence No. 108) Reads the alarm temperatures and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Alarm 1 set value (rightmost 4 digits) +2 Alarm 1 set value (leftmost 1 digit) +3 Alarm 2 set value (rightmost 4 digits) +4 Alarm 2 set value (leftmost 1 digit) ~ +29 Channel 0 ~ Alarm 1 set value (rightmost 4 digits) +30 Alarm 1 set value (rightmost 1 digit) +31 Alarm 2 set value (rightmost 4 digits) +32 Alarm 2 set value (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0033 +1 Channel 0 Alarm 1 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +2 Channel 0 Alarm 1 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. +3 Channel 0 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +4 Channel 0 Alarm 2 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. 198 +29 Channel 7 Alarm 1 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +30 Channel 7 Alarm 1 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. +31 Channel 7 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +32 Channel 07 Alarm 2 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. Appendix E E5ZE Temperature Controller Read Protocol Read Hysteresis (Sequence No. 109) Reads the hysteresis and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Hysteresis +2 Cooling hysteresis +3 Hysteresis +4 Cooling hysteresis ~ Channel 0 Channel 1 ~ +15 Hysteresis +16 Cooling hysteresis Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Hysteresis (4 digits BCD) 0000 to 0999 +2 Channel 0 Cooling hysteresis (4 digits BCD) 0000 to 0999 +15 Channel 7 Hysteresis (4 digits BCD) 0000 to 0999 +16 Channel 7 Cooling hysteresis (4 digits BCD) 0000 to 0999 Read Operation Status (Sequence No. 110) Reads the operation status of the E5ZE and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Status code Channel 0 +2 Status code Channel 1 ~ +8 ~ Status code Channel 7 199 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Channel 0 Status code (4 digits Hex) 0000 to FFFF +2 Channel 1 Status code (4 digits Hex) 0000 to FFFF +8 Channel 7 Status code (4 digits Hex) 0000 to FFFF Read Error Status (Sequence No. 111) Reads the contents of errors if they have occurred and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Status code Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Status code (4 digits BCD) 0000 to FFFF Read Setting Unit (Sequence No. 112) Reads the setting units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set code Offset 200 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Set code (4 digits BCD) 0000: unit of 1 0001: unit of 0.1 Appendix E E5ZE Temperature Controller Read Protocol Read Input Shift Value (Sequence No. 113) Reads the input shift values and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Input shift value +2 Input shift value Channel 0 Channel 1 ~ ~ +8 Input shift value Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Channel 0 Input shift value (4 digits BCD) 0000 to 0999 F indicates a negative number. +2 Channel 1 Input shift value (4 digits BCD) 0000 to 0999 F indicates a negative number. +8 Channel 7 Input shift value (4 digits BCD) 0000 to 0999 F indicates a negative number. Read Manual Reset Value (Sequence No. 114) Reads the manual reset value and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Manual reset value +2 Manual reset value ~ +8 Channel 0 Channel 1 ~ Manual reset value Channel 7 201 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Channel 0 Manual reset value (4 digits BCD) 0000 to 1000 +2 Channel 1 Manual reset value (4 digits BCD) 0000 to 1000 +8 Channel 7 Manual reset value (4 digits BCD) 0000 to 1000 Read Ramp Value (Sequence No. 115) Reads the ramp values and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words (Undefined) +1 Ramp value Time unit +2 (Undefined) +3 Time unit +4 Channel 1 (Undefined) ~ +15 Channel 0 (Undefined) Ramp value ~ (Undefined) Ramp value Time unit +16 Offset Channel 7 (Undefined) Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Ramp value (3 digits BCD) 000 to 999 +2 Channel 0 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours 202 +15 Channel 7 Ramp value (3 digits BCD) 000 to 999 +16 Channel 7 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours Appendix E E5ZE Temperature Controller Read Protocol Read Present Set Point (Sequence No. 116) Reads the present set points during ramp operation and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Present set point (rightmost 4 digits) +2 Present set point (leftmost 1 digit) ~ Channel 0 ~ +15 Present set point (rightmost 4 digits) +16 Present set point (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Present set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Present set point (leftmost 1 digit) (1 digit BCD) F indicates a negative value. +15 Channel 7 Present set point (rightmost 4 digits) (4 digits BCD) +16 Channel 7 Present set point (leftmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. F indicates a negative value. Read Output Value Limit (Sequence No. 117) Reads the output value limits and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F 203 Appendix E E5ZE Temperature Controller Read Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Output value lower limit +2 Output value upper limit +3 Cooling control output value lower limit +4 Cooling control output value upper limit ~ Channel 0 ~ +29 Output value lower limit +30 Output value upper limit +31 Cooling control output value lower limit Channel 7 +32 Cooling control output value upper limit Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0033 +1 Channel 0 Output value lower limit (4 digits BCD) 0000 to 1000 +2 Channel 0 Output value upper limit (4 digits BCD) 0000 to 1000 +3 Channel 0 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 +4 Channel 0 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 +31 Channel 7 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 +32 Channel 7 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 Read Output Value Change Rate Limit (Sequence No. 118) Reads the output value change rate limits and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Output value change rate limit Channel 0 +2 Output value change rate limit Channel 1 ~ +8 204 ~ Output value change rate limit Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Channel 0 Output value change rate limit (4 digits BCD) 0000 to 1000 +2 Channel 1 Output value change rate limit (4 digits BCD) 0000 to 1000 +8 Channel 7 Output value change rate limit (4 digits BCD) 0000 to 1000 Read HB Alarm and HS Alarm Valid Channels (Sequence No. 119) Reads the valid or invalid channels for HB alarms and HS alarms and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Offset Set code Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Set code (2 digits Hex) 00 to FF Read Heater Burnout and SSR Failure Detection Currents (Sequence No. 120) Reads the heater burnout and SSR failure detection currents and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F 205 Appendix E E5ZE Temperature Controller Read Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Heater burnout detection current +2 SSR failure detection current +3 Heater burnout detection current +4 SSR failure detection current Channel 0 Channel 1 ~ ~ +15 Heater burnout detection current +16 SSR failure detection current Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Heater burnout detection current (4 digits BCD) 0000 to 0500 +2 Channel 0 SSR failure detection current (4 digits BCD) 0000 to 0500 +15 Channel 7 Heater burnout detection current (4 digits BCD) 0000 to 0500 +16 Channel 7 SSR failure detection current (4 digits BCD) 0000 to 0500 Read Heater Current and SSR Leakage Current (Sequence No.121) Reads the heater currents and SSR leakage currents and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Heater current +2 SSR leakage current +3 Heater current +4 SSR leakage current ~ 206 Channel 0 Channel 1 ~ +15 Heater current +16 SSR leakage current Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0017 +1 Channel 0 Heater current (4 digits BCD) 0000 to 0500 +2 Channel 0 SSR leakage current (4 digits BCD) 0000 to 0500 +15 Channel 7 Heater current (4 digits BCD) 0000 to 0500 +16 Channel 7 SSR leakage current (4 digits BCD) 0000 to 0500 Note The read data will be 0000 for all channels for which HB and HS alarms are not enabled and for all channels for which control is stopped. Read Dead Band/Overlap Band (Sequence No. 122) Reads the dead bands/overlap bands and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Dead band/overlap band +2 Dead band/overlap band ~ +8 Channel 0 Channel 1 ~ Dead band/overlap band Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Channel 0 Dead band/overlap band (4 digits BCD) 0000 to 0999 Channel 1 Dead band/overlap band (4 digits BCD) 0000 to 0999 +2 F indicates a number. F indicates a number. +8 Channel 7 Dead band/overlap band (4 digits BCD) 0000 to 0999 F indicates a number. 207 Appendix E E5ZE Temperature Controller Read Protocol Read Cooling Coefficient (Sequence No. 123) Reads the cooling coefficients and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Cooling coefficient +2 Cooling coefficient ~ +8 Channel 0 Channel 1 ~ Cooling coefficient Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0009 +1 Channel 0 Cooling coefficient (4 digits BCD) 0000 to 0100 +2 Channel 1 Cooling coefficient (4 digits BCD) 0000 to 0100 +8 208 Channel 7 Cooling coefficient (4 digits BCD) 0000 to 0100 Appendix F E5ZE Temperature Controller Write Protocol The E5ZE Temperature Controller Write Protocol writes and controls various settings in remote mode for the Temperature Controller connected via a RS-232C or RS-422A/485 cable from the PC via the Serial Communications Board. Note 1. Negative values cannot be written. All values must be set as unsigned BCD. 2. All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks. Structure of the Protocol The following table shows the structure of the E5ZE Temperature Controller Write Protocol. Sequence No. Communications sequence name Function Ladder interface Send word allocation Receive word allocation 150 Write set point (setting unit 1) Writes the set points using a setting unit of 1. Yes No 151 Write set point (setting unit 0.1) Writes the set points using a setting unit of 0.1. Yes No 152 Write proportional band, integral time, and derivative time Writes the proportional bands, integral times, and derivative times. Yes No 153 Write control period Writes the control periods. Yes No 154 Write output mode Writes the output modes. Yes No 155 Write alarm mode Writes the alarm modes. Yes No 156 Write alarm temperature (setting unit 1) Writes the alarm temperatures using a setting unit of 1. Yes No 157 Write alarm temperature (setting unit 0.1) Writes the alarm temperatures using a setting unit of 0.1. Yes No 158 Write hysteresis Writes the hysteresis. Yes No 159 Start autotuning Starts autotuning. Yes No 160 Cancel autotuning Cancels autotuning. Yes No 161 Write setting unit Writes the setting units. Yes No 162 Write input shift value Writes the input shift values. Yes No 163 Write manual reset value Writes the manual reset values. Yes No 164 Write ramp value Writes the ramp values. Yes No 165 Write manual output value Writes the manual output values. Yes No 166 Write output value limit Writes the output value limits. Yes No 167 Write output value change rate limit Write output value change rate limits. Yes No 168 Save settings Saves settings. Yes No 169 Initialize settings Initializes settings. Yes No 170 Write HB alarm and HS alarm valid channels Writes the HB alarm and HS alarm valid channels. Yes No 171 Write heater burnout and SSR failure detection currents Writes the heater burnout and SSR failure detection currents. Yes No 172 Write dead band/overlap band Writes the dead bands/overlap bands. Yes No 173 Write cooling coefficient Writes the cooling coefficients. Yes No 174 Start control Starts temperature control. Yes No 175 Stop operation or control Stops temperature control or manual operation. Yes No 176 Start manual operation Starts manual operation. Yes No Note Ladder Interface Settings YES: User settings are required for the 2nd or 3rd operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 2nd operand (S). Receive word allocation: Set a dummy word (e.g., DM0000) address for the 3rd operand (D). 209 Appendix F E5ZE Temperature Controller Write Protocol Connections The connections are the same as that for the E5ZE Temperature Controller Read Protocol. Write Set Point (Setting Unit 1) (Sequence No. 150) Writes the set points using a setting unit of 1 (4 digits). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 +2 Set point +3 (Undefined) +4 Set point +5 (Undefined) Unit No. Channel 0 Channel 1 ~ ~ +16 Set point +17 (Undefined) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Set point (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +16 Channel 7 Set point (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +17 Not used --- Receive Data Word Allocation (3rd Operand of PMCR) None. Note When the setting unit for the set point is 0.1 (5 digits), use Write Set Point (Setting Unit 0.1), Sequence No.151. 210 Appendix F E5ZE Temperature Controller Write Protocol Write Set Point (Setting Unit 0.1) (Sequence No. 151) Writes the set points using a setting unit of 0.1 (5 digits). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Set point (rightmost 4 digits) +3 Set point (leftmost 1 digit) +4 Set point (rightmost 4 digits) +5 Set point (leftmost 1 digit) ~ Channel 0 Channel 1 ~ +16 Set point (rightmost 4 digits) +17 Set point (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +3 Channel 0 Set point (leftmost 1 digit) (1 digit BCD) +16 Channel 7 Set point (rightmost 4 digits) (4 digits BCD) +17 Channel 7 Set point (rightmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. Receive Data Word Allocation (3rd Operand of PMCR) None. Note When the setting unit for the set point is 1 (4 digits), use Write Set Point (Setting Unit 1), Sequence No.150. 211 Appendix F E5ZE Temperature Controller Write Protocol Write Proportional Band, Integral Time, and Derivative Time (Sequence No. 152) Writes the proportional bands (constant P), integral times (constant I), and derivative times (constant D). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 +2 Constant P +3 Constant I +4 Constant D Unit No. Channel 0 ~ ~ +23 Constant P +24 Constant I +25 Constant D Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0026 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Constant P (4 digits BCD) 0000 to 9999 +3 Channel 0 Constant I (4 digits BCD) 0000 to 3999 +4 Channel 0 Constant D (4 digits BCD) 0000 to 3999 +23 Channel 7 Constant P (4 digits BCD) 0000 to 9999 +24 Channel 7 Constant I (4 digits BCD) 0000 to 3999 +25 Channel 7 Constant D (4 digits BCD) 0000 to 3999 Receive Data Word Allocation (3rd Operand of PMCR) None. 212 Appendix F E5ZE Temperature Controller Write Protocol Write Control Period (Sequence No. 153) Writes the control periods and cooling control periods. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Control period +3 Cooling control period +4 Control period +5 Cooling control period ~ Channel 1 ~ +16 Control period +17 Cooling control period Offset Channel 0 Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Control period (4 digits BCD) 0001 to 0099 +3 Channel 0 Cooling control period (4 digits BCD) 0001 to 0099 +4 Channel 1 Control period (4 digits BCD) 0001 to 0099 +5 Channel 1 Cooling control period (4 digits BCD) 0001 to 0099 +16 Channel 7 Control period (4 digits BCD) 0001 to 0099 +17 Channel 7 Cooling control period (4 digits BCD) 0001 to 0099 Receive Data Word Allocation (3rd Operand of PMCR) None. 213 Appendix F E5ZE Temperature Controller Write Protocol Write Output Mode (Sequence No. 154) Writes the output mode (normal/reverse). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Write code Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Write code (2 digits Hex) 00 to FF Receive Data Word Allocation (3rd Operand of PMCR) None. Write Alarm Mode (Sequence No. 155) Writes the alarm modes for alarm 1 and alarm 2. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Alarm 1 set code +3 (Undefined) Alarm 2 set code +4 (Undefined) Alarm 1 set code +5 (Undefined) Alarm 2 set code ~ Channel 0 Channel 1 ~ +16 (Undefined) Alarm 1 set code +17 (Undefined) alarm 2 set code Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Alarm 1 set code (2 digits Hex) 00 to 0C +3 Channel 0 Alarm 2 set code (2 digits Hex) 00 to 0C +4 Channel 1 Alarm 1 set code (2 digits Hex) 00 to 0C +5 Channel 1 Alarm 2 set code (2 digits Hex) 00 to 0C +16 Channel 7 Alarm 1 set code (2 digits Hex) 00 to 0C +17 Channel 7 Alarm 2 set code (2 digits Hex) 00 to 0C Receive Data Word Allocation (3rd Operand of PMCR) None. 214 Appendix F E5ZE Temperature Controller Write Protocol Write Alarm Temperature (Setting Unit 1) (Sequence No. 156) Writes the alarm temperatures using a setting unit of 1 (4 digits) Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Alarm 1 set value +2 +3 (Undefined) +4 Alarm 2 set value +5 (Undefined) ~ ~ +30 Alarm 1 set value +31 (Undefined) +32 Alarm 2 set value +33 (Undefined) Offset Channel 0 Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0034 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Alarm 1 set value (4 digits BCD) 0000 to 9999 +3 Not used +4 Channel 0 Alarm 2 set value (4 digits BCD) +5 Not used 0000 to 9999 +32 Channel 7 Alarm 2 set value (4 digits BCD) +33 Not used 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. 215 Appendix F E5ZE Temperature Controller Write Protocol Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157) Writes the alarm temperatures using a setting unit of 0.1 (5 digits) Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Alarm 1 set value (rightmost 4 digits) +2 +3 Alarm 1 set value (leftmost 1 digit) +4 Alarm 2 set value (rightmost 4 digits) +5 Alarm 2 set value (leftmost 1 digit) ~ Channel 0 ~ +30 Alarm 1 set value (rightmost 4 digits) +31 Alarm 1 set value (leftmost 1 digit) +32 Alarm 2 set value (rightmost 4 digits) +33 Alarm 2 set value (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0034 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Alarm 1 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 +3 Channel 0 Alarm 1 set value (leftmost 1 digits) (4 digits BCD) 0000 to 0009 +4 Channel 0 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 +5 Channel 0 Alarm 2 set value (leftmost 1 digits) (4 digits BCD) 0000 to 0009 +32 Channel 7 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 +33 Channel 7 Alarm 2 set value (leftmost 1 digits) (4 digits BCD) 0000 to 0009 Receive Data Word Allocation (3rd Operand of PMCR) None. 216 Appendix F E5ZE Temperature Controller Write Protocol Write Hysteresis (Sequence No. 158) Writes the hysteresis for control outputs for ON/OFF control. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Hysteresis +3 Cooling hysteresis +4 Hysteresis +5 Cooling hysteresis Channel 0 Channel 1 ~ ~ +16 Hysteresis +17 Cooling hysteresis Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Hysteresis (4 digits BCD) 0000 to 0999 +3 Channel 0 Cooling hysteresis (4 digits BCD) 0000 to 0999 +4 Channel 1 Hysteresis (4 digits BCD) 0000 to 0999 +5 Channel 1 Cooling hysteresis (4 digits BCD) 0000 to 0999 +16 Channel 7 Hysteresis (4 digits BCD) 0000 to 0999 +17 Channel 7 Cooling hysteresis (4 digits BCD) 0000 to 0999 Receive Data Word Allocation (3rd Operand of PMCR) None. Start Autotuning (Sequence No. 159) Starts autotuning (AT). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. (Undefined) +2 Offset Channel Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel (Channel) No. (1 digit BCD) 0 to 7 Receive Data Word Allocation (3rd Operand of PMCR) None. 217 Appendix F E5ZE Temperature Controller Write Protocol Cancel Autotuning (Sequence No. 160) Cancels Autotuning (AT) for all channels. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) None. Write Setting Unit (Sequence No. 161) Writes the setting unit. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Write code +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Write code (4 digits BCD) 0000: unit of 1 0001: unit of 0.1 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Input Shift Value (Sequence No. 162) Writes the input shift values. Send Data Word Allocation (2nd Operand of PMCR) First word of send data 218 +0 +1 Number of send data words (Undefined) Unit No. +2 Input shift value Channel 0 +3 Input shift value Channel 1 +4 Input shift value Channel 2 +5 Input shift value Channel 3 +6 Input shift value Channel 4 +7 Input shift value Channel 5 +8 Input shift value Channel 6 +9 Input shift value Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0010 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Input shift value (4 digits BCD) 0000 to 0999 +3 Channel 1 Input shift value (4 digits BCD) 0000 to 0999 +4 Channel 2 Input shift value (4 digits BCD) 0000 to 0999 +8 Channel 6 Input shift value (4 digits BCD) 0000 to 0999 +9 Channel 7 Input shift value (4 digits BCD) 0000 to 0999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Manual Reset Value (Sequence No. 163) Writes the manual reset values. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Manual reset value Channel 0 +3 Manual reset value Channel 1 +4 Manual reset value Channel 2 +5 Manual reset value Channel 3 +6 Manual reset value Channel 4 +7 Manual reset value Channel 5 +8 Manual reset value Channel 6 +9 Manual reset value Channel 7 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0010 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Manual reset value (4 digits BCD) 0000 to 1000 +3 Channel 1 Manual reset value (4 digits BCD) 0000 to 1000 +4 Channel 2 Manual reset value (4 digits BCD) 0000 to 1000 +8 Channel 6 Manual reset value (4 digits BCD) 0000 to 1000 +9 Channel 7 Manual reset value (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (3rd Operand of PMCR) None. 219 Appendix F E5ZE Temperature Controller Write Protocol Write Ramp Value (Sequence No. 164) Writes the ramp values. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 +2 (Undefined) Ramp value Time unit +3 +4 Unit No. (Undefined) Ramp value Time unit +5 ~ (Undefined) Ramp value Time unit +17 Offset Channel 1 (Undefined) ~ +16 Channel 0 (Undefined) Channel 7 (Undefined) Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Ramp value (3 digits BCD) 000 to 999 +3 Channel 0 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours +4 Channel 1 Ramp value (3 digits BCD) 000 to 999 +5 Channel 1 Time unit (one ASCII character) S: Second M: Minute H: Hour +16 Channel 7 Ramp value (3 digits BCD) 000 to 999 +17 Channel 7 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours Receive Data Word Allocation (3rd Operand of PMCR) None. Write Manual Output Value (Sequence No. 165) Writes the manual output values for control output in manual operation. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 Output value +3 Cooling output value +4 Output value +5 Cooling output value ~ 220 Channel 0 Channel 1 ~ +16 Output value +17 Cooling output value Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Output value (4 digits BCD) 0000 to 1000 +3 Channel 0 Cooling output value (4 digits BCD) 0000 to 1000 +4 Channel 1 Output value (4 digits BCD) 0000 to 1000 +5 Channel 1 Cooling output value (4 digits BCD) 0000 to 1000 +16 Channel 7 Output value (4 digits BCD) 0000 to 1000 +17 Channel 7 Cooling output value (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Output Value Limit (Sequence No. 166) Writes the output value limits that restrict the values of the control outputs. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 +2 Number of send data words (Undefined) Unit No. Output value lower limit +3 Output value upper limit +4 Cooling output value lower limit +5 Cooling output value upper limit ~ Channel 0 ~ +30 Output value lower limit +31 Output value upper limit +32 Cooling output value lower limit +33 Cooling output value upper limit Channel 7 221 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0034 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Output value lower limit (4 digits BCD) 0000 to 1000 +3 Channel 0 Output value upper limit (4 digits BCD) 0000 to 1000 +4 Channel 0 Cooling output value lower limit (4 digits BCD) 0000 to 1000 +5 Channel 0 Cooling output value upper limit (4 digits BCD) 0000 to 1000 +32 Channel 7 Cooling output value lower limit (4 digits BCD) 0000 to 1000 +33 Channel 7 Cooling output value upper limit (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Output Value Change Rate Limit (Sequence No. 167) Writes the output value change rate limits that restrict the rates of change in the control value output. Send Data Word Allocation (2nd Operand of PMCR) First word of send data 222 +0 +1 Number of send data words (Undefined) Unit No. +2 Output change rate limit Channel 0 +3 Output change rate limit Channel 1 +4 Output change rate limit Channel 2 +5 Output change rate limit Channel 3 +6 Output change rate limit Channel 4 +7 Output change rate limit Channel 5 +8 Output change rate limit Channel 6 +9 Output change rate limit Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0010 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Output change rate limit (4 digits BCD) 0000 to 1000 +3 Channel 1 Output change rate limit (4 digits BCD) 0000 to 1000 +4 Channel 2 Output change rate limit (4 digits BCD) 0000 to 1000 +8 Channel 6 Output change rate limit (4 digits BCD) 0000 to 1000 +9 Channel 7 Output change rate limit (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (3rd Operand of PMCR) None. Save Settings (Sequence No. 168) Saves the settings. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) None. Initialize Settings (Sequence No. 169) Initializes all the settings to the factory defaults. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) None. 223 Appendix F E5ZE Temperature Controller Write Protocol Write HB and HS Alarm Valid Channels (Sequence No. 170) Writes the valid or invalid channels of HB alarm and HS alarm. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Write code Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Write code (2 digits Hex) 00 to FF Receive Data Word Allocation (3rd Operand of PMCR) None. Write Heater Burnout and SSR Failure Detection Current (Sequence No. 171) Writes the currents for detecting heater burnouts and SSR failures. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Heater burnout detection current +3 SSR failure detection current +4 Heater burnout detection current +5 SSR failure detection current ~ Channel 1 ~ +16 Heater burnout detection current +17 SSR failure detection current Offset Channel 0 Channel 7 Contents (data format) Data +0 Number of send data words (4 digits BCD) 0018 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Heater burnout detection current (4 digits BCD) 0000 to 0500 +3 Channel 0 SSR failure detection current (4 digits BCD) 0000 to 0500 +4 Channel 1 Heater burnout detection current (4 digits BCD) 0000 to 0500 +5 Channel 1 SSR failure detection current (4 digits BCD) 0000 to 0500 +16 Channel 7 Heater burnout detection current (4 digits BCD) 0000 to 0500 +17 Channel 7 SSR failure detection current (4 digits BCD) 0000 to 0500 Receive Data Word Allocation (3rd Operand of PMCR) None. 224 Appendix F E5ZE Temperature Controller Write Protocol Write Dead Band/Overlap Band (Sequence No. 172) Writes the dead bands or overlap bands for control outputs during heating/cooling control. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Dead band/overlap band Channel 0 +3 Dead band/overlap band Channel 1 +4 Dead band/overlap band Channel 2 +5 Dead band/overlap band Channel 3 +6 Dead band/overlap band Channel 4 +7 Dead band/overlap band Channel 5 +8 Dead band/overlap band Channel 6 +9 Dead band/overlap band Channel 7 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0010 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Dead band/overlap band (4 digits BCD) 0000 to 0999 +3 Channel 1 Dead band/overlap band (4 digits BCD) 0000 to 0999 +4 Channel 2 Dead band/overlap band (4 digits BCD) 0000 to 0999 +8 Channel 6 Dead band/overlap band (4 digits BCD) 0000 to 0999 +9 Channel 7 Dead band/overlap band (4 digits BCD) 0000 to 0999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Cooling Coefficient (Sequence No. 173) Writes the cooling coefficients for the cooling proportional bands for heating/cooling control. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 Cooling coefficient Channel 0 +3 Cooling coefficient Channel 1 +4 Cooling coefficient Channel 2 +5 Cooling coefficient Channel 3 +6 Cooling coefficient Channel 4 +7 Cooling coefficient Channel 5 +8 Cooling coefficient Channel 6 +9 Cooling coefficient Channel 7 225 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0010 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Cooling coefficient (4 digits BCD) 0000 to 0100 +3 Channel 1 Cooling coefficient (4 digits BCD) 0000 to 0100 +4 Channel 2 Cooling coefficient (4 digits BCD) 0000 to 0100 +8 Channel 6 Cooling coefficient (4 digits BCD) 0000 to 0100 +9 Channel 7 Cooling coefficient (4 digits BCD) 0000 to 0100 Receive Data Word Allocation (3rd Operand of PMCR) None. Start Control (Sequence No. 174) Starts temperature control for all channels in the specified Unit. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) None. Stop Operation or Control (Sequence No. 175) Stops temperature control or manual operation for all channels of the specified Unit. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) None. 226 Data Appendix F E5ZE Temperature Controller Write Protocol Start Manual Operation (Sequence No. 176) Starts manual operation based on the output values that were set for all channels of the specified Unit. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (3rd Operand of PMCR) None. 227 Appendix G E5J Temperature Controller Protocol The E5J Temperature Controller Protocol performs various settings and controls in remote mode for the Temperature Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable. Note Negative values cannot be written. All values must be set as unsigned BCD. Structure of the Protocol The following table shows the structure of the E5J Temperature Controller Protocol. Sequence No. Communications sequence name Function Ladder interface 200 Select remote mode Switches the Controller to remote mode. Send word allocation Yes Receive word allocation No 201 Select local mode Switches the Controller to local mode. Yes No 202 Select backup mode Yes No 203 Yes No 204 Select RAM write mode Save set point Switches from set point write mode to backup mode. Switches from set point write mode to RAM write mode. Saves the set point. Yes No 205 Write parameters 1 Yes No 206 Write parameters 2 Yes No 207 Write input shift value Writes the set point, alarm value 1, alarm value 2, and heater burnout alarm value. Writes the proportional band, integral time, and derivative time. Writes the input shift value. Yes No 208 Read parameters 1 Yes Yes 209 Read parameters 2 Yes Yes 210 Read input shift value Yes Yes 211 Read output value Reads the set point, alarm value 1, alarm value 2, and heater burnout alarm value. Reads the proportional band, integral time, and derivative time. Reads the input shift value and writes it in IOM. Reads the output value and stores it in IOM. Yes Yes 212 Read process value Yes Yes 213 Read set point limit Yes Yes 214 Read heater current Yes Yes 215 Read initial status Reads the process value and stores it in IOM. Reads the set point limits and stores them in IOM. Reads the heater current and stores it in IOM. Reads the initial status and stores it in IOM. Yes Yes 216 General-purpose write Yes No 217 General-purpose read Writes the specified parameter by setting a header code. Reads the specified parameter by setting a header code. Yes Yes Note Ladder Interface Settings YES: User settings are required for the 2nd or 3rd operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 2nd operand (S). Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D). 229 Appendix G E5jJ Temperature Controller Protocol Connections The connections for using the E5J Temperature Controller Protocol are shown below. RS-232C Connections CQM1H E5J Serial Communications Board RS-232C port → RS-232C Signal name Abbreviation Signal direction Pin No. Signal ground or common return line Send data SG – 25, 27 SD Output 26 Receive data RD Input 28 Serial Communications Board RS-232C: D-sub 9-pin female E5AJ RS-232C: Terminal Block Signal Pin name No. Termi- Signal name nal MAX232C or equivalent Shielded cable Note 1. The connection configuration is a one-to-one configuration and the maximum cable length is 15 m. 2. Use shielded twisted-pair cable (AWG28i or greater). RS422A/485 Connections CQM1H E5J Serial Communications Board RS-422A/485 port → RS-422A/485 E5J → RS-422A/485 Up to 32 units can be connected. E5J → RS-422A/485 230 Appendix G E5jJ Temperature Controller Protocol • RS-422A Signal name Abbreviation Signal direction Pin No. Send data A SDA Output 26 Send data B SDB Output 25 Receive data A RDA Input 28 Receive data B RDB Input 29 Signal ground SG – 27 Serial Communications Board Terminating resistance RS-422A: Terminal Block Signal Pin name No. Termi- Signal nal name Terminating resistance 240 Ω E5AJ Shielded cable Terminating resistance (terminator) SN751177N or equivalent E5AJ RS-422A: D-sub 9-pin female Terminating resistance (240 Ω) is connected via the terminator switch. RS-422A: Terminal Block Shielded cable Termi- Signal nal Terminator switch name • RS-485 Abbreviation Signal direction Terminal A Signal name A I/O 26, 28 Terminal B B I/O 25, 29 Signal ground SG – 27 SN751177N or equivalent Serial Communications Board RS-485: D-sub 9-pin female Terminating resistance Signal Pin name No. Pin No. E5AJ Terminating RS-485: Terminal Block resistance Termi- Signal nal name Shielded cable Terminating resistance (240 Ω) is connected via the terminator switch. E5AJ Terminator switch RS-485: Terminal Block Signal Shielded cable Terminame nal 231 Appendix G E5jJ Temperature Controller Protocol Note 1. The connection configuration is a one-to-one or a one-to-N configuration. Using a one-to-N configuration, up to 32 units can be connected including the Serial Communications Board. 2. The maximum cable length is 500 m. Use shielded twisted-pair cable (AWG28i or greater). 3. Connect terminating resistance to the devices only at both ends of the transmission path. 4. The total terminating resistance at both ends must be at least 100 Ω for RS-422A or 54 Ω for RS-485. Select Remote Mode (Sequence No. 200) Switches the Controller to remote mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Select Local Mode (Sequence No. 201) Switches the Controller to local mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Select Backup Mode (Sequence No. 202) Switches from the set point write mode to backup mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Select RAM Write Mode (Sequence No. 203) Switches from set point write mode to RAM write mode. 232 Appendix G E5jJ Temperature Controller Protocol Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Save Set Point (Sequence No. 204) Saves the set point. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Parameters 1 (Sequence No. 205) Writes the set point, alarm value 1, alarm value 2, and a heater burnout alarm value to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 +2 Number of send data words Number of units (Undefined) Unit No. +3 set point +4 Alarm value 1 +5 Alarm value 2 +6 Heater burnout alarm value ~ +122 1st unit ~ (Undefined) Unit No. +123 set point +124 Alarm value 1 +125 Alarm value 2 +126 Heater burnout alarm value 25th unit (max.) 233 Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 5 + 2 +1 Number of units (4 digits BCD) 0001 to 0025 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit set point (4 digits BCD) 0000 to 9999 +4 1st unit Alarm value 1 (4 digits BCD) 0000 to 9999 +5 1st unit Alarm value 2 (4 digits BCD) 0000 to 9999 +6 1st unit Heater burnout alarm value 2 (4 digits BCD) 0000 to 9999 +7 2nd unit Unit No. (2 digits BCD) 00 to 31 +126 (max.) 25th unit Heater burnout alarm value 2 (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Parameters 2 (Sequence No. 206) Writes the proportional bands, integral times, and derivative times to multiple units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 +3 (Undefined) Unit No. Proportional band +4 Integral time +5 Derivative time ~ +122 234 1st unit ~ (Undefined) Unit No. +123 Proportional band +124 Integral time +125 Derivative time 31th unit (max.) Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 4 + 2 +1 Number of units (4 digits BCD) 0001 to 0031 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Proportional band (4 digits BCD) 0000 to 9999 +4 1st unit Integral time (4 digits BCD) 0000 to 9999 +5 1st unit Derivative time (4 digits BCD) 0000 to 9999 +6 2nd unit Unit No. (2 digits BCD) 00 to 31 +125 (max.) 31th unit Derivative time (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. Write Input Shift Value (Sequence No. 207) Writes the input shift value. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Input shift value +2 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Input shift value (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None 235 Appendix G E5jJ Temperature Controller Protocol Read Parameters 1 (Sequence No. 208) Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. ~ ~ (Undefined) +26 Offset (max.) Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0025 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set point +2 Alarm value 1 +3 Alarm value 2 +4 Heater burnout alarm value ~ 236 1st unit ~ +97 Set point +98 Alarm value 1 +99 Alarm value 2 +100 Heater burnout alarm value 25th unit (max.) Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 4 + 1 +1 1st unit Set point (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 1st unit Alarm value 1 (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +3 1st unit Alarm value 2 (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +4 1st unit Heater burnout alarm value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +5 2nd unit Set point (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +100 (max.) 25th unit Heater burnout alarm value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Parameters 2 (Sequence No. 209) Reads the proportional bands, integral times, and derivative times for multiple units and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. (Undefined) Unit No. ~ +32 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units+ 2 +1 Number of units (4 digits BCD) 0001 to 0031 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +32 (max.) 31th unit Unit No. (2 digits BCD) 00 to 31 237 Appendix G E5jJ Temperature Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Proportional band +2 Integral time +3 Derivative time 1st unit ~ ~ +91 Proportional band +92 Integral time +93 Derivative time Offset 31th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 3 + 1 +1 1st unit Proportional band (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 1st unit Integral time (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +3 1st unit Derivative time (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +4 2nd unit Proportional band (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +93 (max.) 31th unit Derivative time (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Input Shift Value (Sequence No. 210) Reads the input shift value and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Input shift value Offset 238 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Input shift value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Appendix G E5jJ Temperature Controller Protocol Read Output Value (Sequence No. 211) Reads the output value and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Output value Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 +1 Output value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Process Value (Sequence No. 212) Reads the process value and status data and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Process value +2 Status data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Process value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 Status data (4 digits Hex) 0000 to 9999 Read Set Point Limit (Sequence No. 213) Reads the set point limits and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) Unit No. 239 Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Set point lower limit +2 Set point upper limit Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Set point lower limit (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 Set point upper limit (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Heater Current (Sequence No. 214) Reads the heater current and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Heater current +2 Status data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Heater current (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 Status data (4 digits Hex) 0000 to 0011 Read Initial Status (Sequence No. 215) Reads the initial status and stores the results in the specified word. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset 240 Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix G E5jJ Temperature Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 +1 Number of receive data words (Undefined) +2 (Undefined) Offset Alarm 1 type Status Alarm 2 type Input type Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0003 +1 Status (2 digits Hex) 00 to 99 +2 Alarm 1 type (1 digit Hex) Alarm 2 type (1 digit Hex) Input type (1 digit BCD) 0 to 9 0 to 9 0 to 9 General-purpose Write (Sequence No. 216) Writes the parameter specified by setting a header code. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. Header code (ASC) +2 (Undefined) +3 Data code Send data +4 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Header code (two ASCII characters) Header codes that can be set MB, WS, W%, WW, WB, WN, WV +3 Data code (2 digits BCD) 01 to 02 +4 Write data (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR) None. General-purpose Read (Sequence No. 217) Reads the parameter specified by setting a header Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Header code (ASC) +2 (Undefined) +3 Offset Data code Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Header code (two ASCII characters) Header codes that can be set RS, R%, RW, RB, RN, RV, RO +3 Data code (2 digits BCD) 01 to 02 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Receive data 241 Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0002 +1 Read data (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Note The completion code is not included in the read data. 242 Data Appendix H ES100j Digital Controller Protocol The ES100 Digital Controller Protocol controls in remote mode and reads various settings from the Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable. Note Negative values cannot be written. All values must be set as unsigned BCD. Structure of the Protocol The structure of the ES100 Digital Controller Protocol is shown below. Sequence No. Transmission sequence name Function Ladder interface Send word allocation Yes Receive word allocation Yes 250 Read event data Reads events 1 to 10 in the variable area. 251 Read time signals Yes Yes 252 Yes Yes Yes Yes 254 Read error detection data Read heater burnout data Read PV data Reads time signals 1 to 10 in the variable area. Reads error groups 1 to 15 in the variable area. Reads the heater burnout alarm. Reads PV data in the variable area. Yes Yes 255 Read SP data Reads SP data in the variable area. Yes Yes 256 Read MV Reads the MV in the variable area. Yes Yes 257 Read control monitor data Read adjustment parameters Write adjustment parameters Read PID control parameters 1 Reads control monitor data (SP, PV, and MV) in the variable area. Reads adjustment parameters in the parameter area. Writes adjustment parameters in the parameter area. Reads PID parameters No. 1 to 4 from the PID control parameters in the parameter area. Yes Yes Yes Yes Yes No Yes Yes 261 Read PID control parameters 2 Reads PID parameters No. 5 to 8 from the PID control parameters in the parameter area. Yes Yes 262 No Yes No Yes Yes 265 Write local SP Yes No 266 Read program parameters Writes PID parameters No. 1 to 4 from PID control parameters in the parameter area. Writes PID parameters No. 5 to 8 from PID control parameters in the parameter area. Reads the local SP in the program parameter area. Writes local SP in the program parameter area. Reads local SP, step time, PID No. wait code, and events 1 to 10 set values in the program parameter area. Yes 264 Write PID control parameters 1 Write PID control parameters 2 Read local SP Yes Yes 267 Write program parame- Writes the local SP, step time, PID No., wait ters code, and event 1 to 10 set values in the program parameter area. Yes No 268 Remote setting mode Switches the setting mode to remote setting. Yes No 269 Local setting mode Switches the setting mode to local setting. Yes No 270 External setting mode Yes No 271 Run command Switches the setting mode to external setting. Starts control. Yes No 272 Reset (stop) Stops control. Yes No 253 258 259 260 263 243 Appendix H ES100j Digital Controller Protocol Sequence No. Transmission sequence name Function Ladder interface Send word Receive word allocation allocation Yes No 273 Auto mode Switches the control mode to auto. 274 Manual mode Switches the control mode to a manual. Yes No 275 Execute A.T. Executes A.T. Yes No 276 Cancel A.T. Cancels A.T. Yes No 277 Change pattern No. Changes the pattern No. Yes No 278 Change bank No. Changes the bank No. Yes No 279 Read controller status Reads the controller status. Yes Yes 280 General-purpose command Sends specified data and stores the received data in the specified words. Yes Yes Note Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). Connections Connections for using the ES100 Digital Controller Protocol are shown below. RS-232C Connections ES100 CQM1H Serial Communications Board RS-232C port → Serial Communications Board ES100-01 RS-232C: D-sub 9-pin female Signal name RS-232C: Terminal Block Pin No. Terminal 17 16 15 Shielded cable 244 Signal name Appendix H ES100j Digital Controller Protocol RS-422A/485 Connections CQM1H ES100 Serial Communications Board RS-422A/485 port → RS-422A/485 ES100 → RS-422A/485 Up to 32 units can be connected. ES100 → RS-422A/485 • RS-422A Serial Communications Board ES100-04 RS--422 Terminal Block RS-422A: D-sub 9-pin female Signal name Pin No. Shielded cable Terminal Signal name Next ES100 • RS-485 Serial Communications Board ES100-04 RS-485: D-sub 9-pin female Pin No. RS--485 Terminal Block Shielded cable Terminal Next ES100 245 Appendix H ES100j Digital Controller Protocol Switch Settings There are two switches located on the board on the left of the Unit. Set SW1 to the interface: RS-422A or RS-485. Set SW2 to the center on all terminating Units and to the same setting as SW1 on all other Units. 422← →485 422← →485 Read Event Data (Sequence No. 250) Reads events 1 to 10 in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +26 ~ Offset 25th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0025 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Event 1 Event 2 +2 Event 3 Event 4 +3 Event 5 Event 6 +4 Event 7 Event 8 +5 Event 9 Event 10 ~ 246 1st unit ~ +121 Event 1 Event 2 +122 Event 3 Event 4 +123 Event 5 Event 6 +124 Event 7 Event 8 +125 Event 9 Event 10 25th unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units x 5 + 1 +1 1st unit Event data 1 (2 digits Hex) Event data 2 (2 digits Hex) 00 to FF 00 to FF +2 1st unit Event data 3 (2 digits Hex) Event data 4 (2 digits Hex) 00 to FF 00 to FF +3 1st unit Event data 5 (2 digits Hex) Event data 6 (2 digits Hex) 00 to FF 00 to FF +4 1st unit Event data 7 (2 digits Hex) Event data 8 (2 digits Hex) 00 to FF 00 to FF +5 1st unit Event data 9 (2 digits Hex) Event data 10 (2 digits Hex) 00 to FF 00 to FF +125 (max.) 25th unit Event data 9 (2 digits Hex) Event data 10 (2 digits Hex) 00 to FF 00 to FF Read Time Signal (Sequence No. 251) Reads time signals from 1 to 10 in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ 2nd unit ~ (Undefined) +26 1st unit Offset Unit No. 25th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0025 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 247 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Time signal 1 Time signal 2 +2 Time signal 3 Time signal 4 +3 Time signal 5 Time signal 6 +4 Time signal 7 Time signal 8 +5 Time signal 9 Time signal 10 +121 Time signal 1 Time signal 2 +122 Time signal 3 Time signal 4 +123 Time signal 5 Time signal 6 +124 Time signal 7 Time signal 8 +125 Time signal 9 Time signal 10 ~ 1st unit ~ Offset 25th unit (max.) Contents (data format) Data +0 Number of receive data words (4digits BCD) Number of units 5 + 1 +1 1st unit Time signal 1 data (2 digits Hex) Time signal 2 data (2 digits Hex) 00 to FF 00 to FF +2 1st unit Time signal 3 data (2 digits Hex) Time signal 4 data (2 digits Hex) 00 to FF 00 to FF +3 1st unit Time signal 5 data (2 digits Hex) Time signal 6 data (2 digits Hex) 00 to FF 00 to FF +4 1st unit Time signal 7 data (2 digits Hex) Time signal 8 data (2 digits Hex) 00 to FF 00 to FF +5 1st unit Time signal 9 data (2 digits Hex) Time signal 10 data (2 digits Hex) 00 to FF 00 to FF +125 (max.) 25th unit Time signal 9 data (2 digits Hex) Time signal 10 data (2 digits Hex) 00 to FF 00 to FF Read Error Detection Data (Sequence No. 252) Reads error groups from 0 to 15 in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +17 248 ~ 16th unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +17 (max.) 16th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Error group 0 Error group 1 +2 Error group 2 Error group 3 +3 Error group 4 Error group 5 +4 Error group 6 Error group 7 +5 Error group 8 Error group 9 +6 Error group 10 Error group 11 +7 Error group 12 Error group 13 Error group 14 Error group 15 Error group 14 Error group 15 +8 ~ +128 1st unit ~ Offset 16th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 8 + 1 +1 1st unit Error group 0 data (2 digits Hex) Error group 1 data (2 digits Hex) 00 to FF 00 to FF +2 1st unit Error group 2 data (2 digits Hex) Error group 3 data (2 digits Hex) 00 to FF 00 to FF +7 1st unit Error group 12 data (2 digits Hex) Error group 13 data (2 digits Hex) 00 to FF 00 to FF +8 1st unit Error group 14 data (2 digits Hex) Error group 15 data (2 digits Hex) 00 to FF 00 to FF +9 2nd unit Error group 0 data (2 digits Hex) Error group 1 data (2 digits Hex) 00 to FF 00 to FF +128 (max.) 16th unit Error group 14 data (2 digits Hex) Error group 15 data (2 digits Hex) 00 to FF 00 to FF 249 Appendix H ES100j Digital Controller Protocol Read Heater Burnout Data (Sequence No. 253) Reads the heater burnout alarm in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit ~ ~ (Undefined) +33 Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Heater burnout alarm 1st unit +2 (Undefined) Heater burnout alarm 2nd unit +3 (Undefined) Heater burnout alarm 3rd unit +4 (Undefined) Heater burnout alarm ~ 4th unit ~ (Undefined) +32 Offset Heater burnout alarm Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units +1 +1 1st unit Heater burnout alarm (2 digits Hex) 00 to FF +2 2nd unit Heater burnout alarm (2 digits Hex) 00 to FF +3 3rd unit Heater burnout alarm (2 digits Hex) 00 to FF +4 4th unit Heater burnout alarm (2 digits Hex) 00 to FF +32 (max.) 250 32nd unit (max.) 32nd unit Heater burnout alarm (2 digits Hex) 00 to FF Appendix H ES100j Digital Controller Protocol Read PV Data (Sequence No. 254) Reads the PV data for the variable type “analog data” in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 PV data (rightmost 4 digits) +2 PV data (leftmost 4 digits) +3 PV data (rightmost 4 digits) +4 PV data (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 PV data (rightmost 4 digits) +64 PV data (leftmost 4 digits) 32nd unit 251 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4digits BCD) Number of units 2 + 1 +1 1st unit PV data (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit PV data (leftmost 4 digits) (4 digits BCD) +3 2nd unit PV data (rightmost 4 digits) (4 digits BCD) +4 2nd unit PV data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +63 32nd unit PV data (rightmost 4 digits) (4 digits BCD) +64 32nd unit PV data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. Read SP Data (Sequence No. 255) Reads the SP data for the variable type “analog data” in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 252 32nd unit Unit No. (2 digits BCD) 00 to 31 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 SP data (rightmost 4 digits) +2 SP data (leftmost 4 digits) +3 SP data (rightmost 4 digits) +4 SP data (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 SP data (rightmost 4 digits) +64 SP data (leftmost 4 digits) Offset 32nd unit Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 2 + 1 +1 1st unit SP data (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit SP data (leftmost 4 digits) (4 digits BCD) +3 2nd unit SP data (rightmost 4 digits) (4 digits BCD) +4 2nd unit SP data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +63 32nd unit SP data (rightmost 4 digits) (4 digits BCD) +64 32nd unit SP data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. Read MV Data (Sequence No. 256) Reads the MV for the variable type “analog data” in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ 32nd unit (max.) 253 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 MV (rightmost 4 digits) +2 MV (leftmost 4 digits) +3 MV (rightmost 4 digits) +4 MV (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 MV (rightmost 4 digits) +64 MV (leftmost 4 digits) Offset 32nd unit Contents (data format) Data +0 Number of receive data words (4 digits BCD) Number of units 2 + 1 +1 1st unit MV (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit MV (leftmost 4 digits) (4 digits BCD) +3 2nd unit MV (rightmost 4 digits) (4 digits BCD) +4 2nd unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +63 32nd unit MV (rightmost 4 digits) (4 digits BCD) +64 32nd unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. Read Control Monitor Data (Sequence No. 257) Reads the control monitor data (SP/PV/MV) in the variable area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ +22 254 1st unit 2nd unit ~ (Undefined) Unit No. 21st unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0021 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +22 (max.) 21st unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 SP data (rightmost 4 digits) +2 SP data (leftmost 4 digits) +3 PV data (rightmost 4 digits) +4 PV data (leftmost 4 digits) +5 MV (rightmost 4 digits) +6 MV (leftmost 4 digits) ~ 1st unit ~ +121 SP data (rightmost 4 digits) +122 SP data (leftmost 4 digits) +123 PV data (rightmost 4 digits) +124 PV data (leftmost 4 digits) +125 MV (rightmost 4 digits) +126 MV (leftmost 4 digits) Offset 21st unit Contents (data format) Data +0 1st unit Number of receive data words (4 digits BCD) Number of units 6 + 1 +1 1st unit SP data (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit SP data (leftmost 4 digits) (4 digits BCD) +3 1st unit PV data (rightmost 4 digits) (4 digits BCD) +4 1st unit PV data (leftmost 4 digits) (4 digits BCD) +5 1st unit MV (rightmost 4 digits) (4 digits BCD) +6 1st unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. 00000000 to 09999000 F indicates a negative number. +125 21st unit MV (rightmost 4 digits) (4 digits BCD) +126 21st unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. 255 Appendix H ES100j Digital Controller Protocol Read Adjustment Parameters (Sequence No. 258) Reads the adjustment parameters in the parameter area and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset 256 Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 Number of receive data words Fixed SP Control output 1 pulse cycle Control output 2 pulse cycle Fuzzy strength Cooling coefficient Heater burnout alarm setting Position-proportional dead band Switching output hysteresis ON/OFF count alarm setting ON/OFF control hysteresis Manual reset SP setting lower limit SP setting upper limit +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 SP rise rate limit SP fall rate limit MV rate-of-change limit Secondary loop fixed SP Secondary loop P (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) +36 (leftmost 4 digits) +37 (rightmost 4 digits) Secondary loop I +38 +39 Secondary loop D (leftmost 4 digits) (rightmost 4 digits) +40 (leftmost 4 digits) +41 (rightmost 4 digits) +42 Secondary loop manual reset (leftmost 4 digits) 257 Appendix H ES100j Digital Controller Protocol Offset 258 Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0043 +1 to 2 Fixed SP (8 digits BCD) +3 to 4 Control output 1 pulse cycle (8 digits BCD) 00000000 to 09999000 F indicates a negative number. +5 to 6 Control output 2 pulse cycle (8 digits BCD) +7 to 8 Fuzzy strength (8 digits BCD) +9 to 10 Cooling coefficient (8 digits BCD) +11 to 12 Heater burnout alarm setting (8 digits BCD) +13 to 14 Position-proportional dead band (8 digits BCD) +15 to 16 Switching output hysteresis (8 digits BCD) +17 to 18 ON/OFF count alarm setting (8 digits BCD) +19 to 20 ON/OFF control hysteresis (8 digits BCD) +21 to 22 Manual reset (8 digits BCD) +23 to 24 SP setting lower limit (8 digits BCD) +25 to 26 SP setting upper limit (8 digits BCD) +27 to 28 SP rise rate limit (8 digits BCD) +29 to 30 SP fall rate limit (8 digits BCD) +31 to 32 MV rate-of-change limit (8 digits BCD) +33 to 34 Secondary loop fixed SP (8 digits BCD) +35 to 36 Secondary loop P (8 digits BCD) +37 to 38 Secondary loop I (8 digits BCD) +39 to 40 Secondary loop D (8 digits BCD) +41 to 42 Secondary loop manual reset (8 digits BCD) Appendix H ES100j Digital Controller Protocol Write Adjustment Parameters (Sequence No. 259) Writes the adjust parameters in the parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) +2 +3 Fixed SP +4 +5 Control output 1 pulse cycle +6 +7 Control output 2 pulse cycle +8 +9 Fuzzy strength +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 Cooling coefficient Heater burnout alarm setting Position-proportional dead band Switching output hysteresis ON/OFF count alarm setting +20 +21 ON/OFF control hysteresis +22 +23 Manual reset +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 +36 +37 +38 +39 +40 +41 +42 +43 SP setting lower limit SP setting upper limit SP rise rate limit SP fall rate limit MV change rate limit Secondary loop fixed SP Secondary loop P Secondary loop I Secondary loop D Secondary loop manual reset Unit No. (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) 259 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0044 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 to 3 Fixed SP (8 digits BCD) 00000000 to 09999000 +4 to 5 Control output 1 pulse cycle (8 digits BCD) +6 to 7 Control output 2 pulse cycle (8 digits BCD) +8 to 9 Fuzzy strength (8 digits BCD) +10 to 11 Cooling coefficient (8 digits BCD) +12 to 13 Heater burnout alarm setting (8 digits BCD) +14 to 15 Position-proportional dead band (8 digits BCD) +16 to 17 Switching output hysteresis (8 digits BCD) +18 to 19 ON/OFF count alarm setting (8 digits BCD) value +20 to 21 ON/OFF control hysteresis (8 digits BCD) +22 to 23 Manual reset (8 digits BCD) +24 to 25 SP setting lower limit (8 digits BCD) +26 to 27 SP setting upper limit (8 digits BCD) +28 to 29 SP rise rate limit (8 digits BCD) +30 to 31 SP fall rate limit (8 digits BCD) +32 to 33 MV rate-of-change limit (8 digits BCD) +34 to 35 Secondary loop fixed SP (8 digits BCD) +36 to 37 Secondary loop P (8 digits BCD) +38 to 39 Secondary loop I (8 digits BCD) +40 to 41 Secondary loop D (8 digits BCD) +42 to 43 Secondary loop manual reset (8 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. Read PID Control Parameters 1 (Sequence No. 260) Reads PID parameters No. 1 to 4 from PID control parameters in the parameter area and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset 260 Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 PID No. 1 P (rightmost 4 digits) +2 PID No. 1 P (leftmost 4 digits) +3 PID No. 1 I (rightmost 4 digits) +4 PID No. 1 I (leftmost 4 digits) +5 PID No. 1 D (rightmost 4 digits) +6 PID No. 1 D (leftmost 4 digits) +7 PID No. 1 MV lower limit (rightmost 4 digits) +8 PID No. 1 MV lower limit (leftmost 4 digits) (rightmost 4 digits) +9 PID No. 1 MV upper limit +10 PID No. 1 MV upper limit (leftmost 4 digits) +11 PID No. 1 PV bias value (rightmost 4 digits) +12 PID No. 1 PV bias value (leftmost 4 digits) +13 PID No. 1 Automatic selection range upper limit (rightmost 4 digits) +14 PID No. 1 Automatic selection range upper limit (leftmost 4 digits) ~ ~ +51 PID No. 4 MV upper limit (rightmost 4 digits) +52 PID No. 4 MV upper limit (leftmost 4 digits) +53 PID No. 4 PV bias value (rightmost 4 digits) +54 PID No. 4 PV bias value (leftmost 4 digits) +55 PID No. 4 Automatic selection range upper limit (rightmost 4 digits) +56 PID No. 4 Automatic selection range upper limit (leftmost 4 digits) Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0057 +1 to 2 PID No. 1 P (8 digits BCD) 00000000 to 09999000 +3 to 4 PID No. 1 I (8 digits BCD) +5 to 6 PID No. 1 D (8 digits BCD) +7 to 8 PID No. 1 MV lower limit (8 digits BCD) +9 to 10 PID No. 1 MV upper limit (8 digits BCD) +11 to 12 PID No. 1 PV bias value (8 digits BCD) +13 to 14 PID No. 1 Automatic selection range upper limit (8 digits BCD) +43 to 44 PID No. 4 P (8 digits BCD) +45 to 46 PID No. 4 I (8 digits BCD) +47 to 48 PID No. 4 D (8 digits BCD) +49 to 50 PID No. 4 MV lower limit (8 digits BCD) +51 to 52 PID No. 4 MV upper limit (8 digits BCD) +53 to 54 PID No. 4 PV bias value (8 digits BCD) +55 to 56 PID No. 4 Automatic selection range upper limit (8 digits BCD) 261 Appendix H ES100j Digital Controller Protocol Read PID Control Parameters 2 (Sequence No. 261) Reads PID parameters No. 5 to 8 from the PID control parameters in the parameter area and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 PID No. 5 P (rightmost 4 digits) +2 PID No. 5 P (leftmost 4 digits) +3 PID No. 5 I (rightmost 4 digits) +4 PID No. 5 I (leftmost 4 digits) +5 PID No. 5 D (rightmost 4 digits) +6 PID No. 5 D (leftmost 4 digits) +7 PID No. 5 MV lower limit (rightmost 4 digits) +8 PID No. 5 MV lower limit (leftmost 4 digits) +9 PID No. 5 MV upper limit (rightmost 4 digits) +10 PID No. 5 MV upper limit (leftmost 4 digits) +11 PID No. 5 PV bias value (rightmost 4 digits) +12 PID No. 5 PV bias value (leftmost 4 digits) +13 PID No. 5 Automatic selection range upper limit (rightmost 4 digits) +14 PID No. 5 Automatic selection range upper limit (leftmost 4 digits) ~ 262 ~ +51 PID No. 8 MV upper limit (rightmost 4 digits) +52 PID No. 8 MV upper limit (leftmost 4 digits) +53 PID No. 8 PV bias value (rightmost 4 digits) +54 PID No. 8 PV bias value (leftmost 4 digits) +55 PID No. 8 Automatic selection range upper limit (rightmost 4 digits) +56 PID No. 8 Automatic selection range upper limit (leftmost 4 digits) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0057 +1 to 2 PID No. 5 P (8 digits BCD) 00000000 to 09999000 +3 to 4 PID No. 5 I (8 digits BCD) +5 to 6 PID No. 5 D (8 digits BCD) +7 to 8 PID No. 5 MV lower limit (8 digits BCD) +9 to 10 PID No. 5 MV upper limit (8 digits BCD) +11 to 12 PID No. 5 PV bias value (8 digits BCD) +13 to 14 PID No. 5 Automatic selection range upper limit (8 digits BCD) +43 to 44 PID No. 8 P (8 digits BCD) +45 to 46 PID No. 8 I (8 digits BCD) +47 to 48 PID No. 8 D (8 digits BCD) +49 to 50 PID No. 8 MV lower limit (8 digits BCD) +51 to 52 PID No. 8 MV upper limit (8 digits BCD) +53 to 54 PID No. 8 PV bias value (8 digits BCD) +55 to 56 PID No. 8 Automatic selection range upper limit (8 digits BCD) 263 Appendix H ES100j Digital Controller Protocol Write PID Control Parameters 1 (Sequence No. 262) Writes PID parameters No. 1 to 4 to the PID control parameters in the parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 PID No. 1 P (rightmost 4 digits) +3 PID No. 1 P (leftmost 4 digits) +4 PID No. 1 I (rightmost 4 digits) +5 PID No. 1 I (leftmost 4 digits) +6 PID No. 1 D (rightmost 4 digits) +7 PID No. 1 D (leftmost 4 digits) +8 PID No. 1 MV lower limit (rightmost 4 digits) +9 PID No. 1 MV lower limit (leftmost 4 digits) +10 PID No. 1 MV upper limit (rightmost 4 digits) +11 PID No. 1 MV upper limit (leftmost 4 digits) +12 PID No. 1 PV bias value (rightmost 4 digits) +13 PID No. 1 PV bias value (leftmost 4 digits) +14 PID No. 1 Automatic selection range upper limit (rightmost 4 digits) +15 PID No. 1 Automatic selection range upper limit (leftmost 4 digits) ~ 264 ~ +52 PID No. 4 MV upper limit (rightmost 4 digits) +53 PID No. 4 MV upper limit (leftmost 4 digits) +54 PID No. 4 PV bias value (rightmost 4 digits) +55 PID No. 4 PV bias value (leftmost 4 digits) +56 PID No. 4 Automatic selection range upper limit (rightmost 4 digits) +57 PID No. 4 Automatic selection range upper limit (leftmost 4 digits) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0058 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 to 3 PID No. 1 P (8 digits BCD) 00000000 to 09999000 +4 to 5 PID No. 1 I (8 digits BCD) +6 to 7 PID No. 1 D (8 digits BCD) +8 to 9 PID No. 1 MV lower limit (8 digits BCD) +10 to 11 PID No. 1 MV upper limit (8 digits BCD) +12 to 13 PID No. 1 PV bias value (8 digits BCD) +14 to 15 PID No. 1 Automatic selection range upper limit (8 digits BCD) +44 to 45 PID No. 4 P (8 digits BCD) +46 to 47 PID No. 4 I (8 digits BCD) +48 to 49 PID No. 4 D (8 digits BCD) +50 to 51 PID No. 4 MV lower limit (8 digits BCD) +52 to 53 PID No. 4 MV upper limit (8 digits BCD) +54 to 55 PID No. 4 PV bias value (8 digits BCD) +56 to 57 PID No. 4 Automatic selection range upper limit (8 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. 265 Appendix H ES100j Digital Controller Protocol Write PID Control Parameters 2 (Sequence No. 263) Writes the PID parameters No. 5 to 8 to the PID control parameters in the parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 (Undefined) +1 Unit No. +2 PID No. 5 P (rightmost 4 digits) +3 PID No. 5 P (leftmost 4 digits) +4 PID No. 5 I (rightmost 4 digits) +5 PID No. 5 I (leftmost 4 digits) +6 PID No. 5 D (rightmost 4 digits) +7 PID No. 5 D (leftmost 4 digits) +8 PID No. 5 MV lower limit (rightmost 4 digits) +9 PID No. 5 MV lower limit (leftmost 4 digits) +10 PID No. 5 MV upper limit (rightmost 4 digits) +11 PID No. 5 MV upper limit (leftmost 4 digits) +12 PID No. 5 PV bias value (rightmost 4 digits) +13 PID No. 5 PV bias value (leftmost 4 digits) +14 PID No. 5 Automatic selection range upper limit (rightmost 4 digits) +15 PID No. 5 Automatic selection range upper limit (leftmost 4 digits) ~ 266 ~ +52 PID No. 8 MV upper limit (rightmost 4 digits) +53 PID No. 8 MV upper limit (leftmost 4 digits) +54 PID No. 8 PV bias value (rightmost 4 digits) +55 PID No. 8 PV bias value (leftmost 4 digits) +56 PID No. 8 Automatic selection range upper limit (rightmost 4 digits) +57 PID No. 8 Automatic selection range upper limit (leftmost 4 digits) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0058 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 to 3 PID No. 5 P (8 digits BCD) 00000000 to 09999000 +4 to 5 PID No. 5 I (8 digits BCD) +6 to 7 PID No. 5 D (8 digits BCD) +8 to 9 PID No. 5 MV lower limit (8 digits BCD) +10 to 11 PID No. 5 MV upper limit (8 digits BCD) +12 to 13 PID No. 5 PV bias value (8 digits BCD) +14 to 15 PID No. 5 Automatic selection range upper limit (8 digits BCD) +44 to 45 PID No. 8 P (8 digits BCD) +46 to 47 PID No. 8 I (8 digits BCD) +48 to 49 PID No. 8 D (8 digits BCD) +50 to 51 PID No. 8 MV lower limit (8 digits BCD) +52 to 53 PID No. 8 MV upper limit (8 digits BCD) +54 to 55 PID No. 8 PV bias value (8 digits BCD) +56 to 57 PID No. 8 Automatic selection range upper limit (8 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. Read Local SP (Sequence No. 264) Reads the local SP in the program parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 Pattern No. Step No. +4 (Undefined) Unit No. +5 Pattern No. Step No. ~ 1st unit 2nd unit ~ +64 (Undefined) Unit No. +65 Pattern No. Step No. 32nd unit 267 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 63 00 to 63 +64 32nd unit Unit No. (2 digits BCD) +65 (max.) 32nd unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 31 00 to 63 00 to 63 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Local SP (rightmost 4 digits) +2 Local SP (leftmost 4 digits) +3 Local SP (rightmost 4 digits) +4 Local SP (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 Local SP (rightmost 4 digits) +64 Local SP (leftmost 4 digits) Offset Contents (data format) 32nd unit Data +0 Number of receive data words (4 digits BCD) Number of units 2 + 1 +1 1st unit Local SP (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit Local SP (leftmost 4 digits) (4 digits BCD) +3 2nd unit Local SP (rightmost 4 digits) (4 digits BCD) +4 2nd unit Local SP (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 268 +63 32nd unit Local SP (rightmost 4 digits) (4 digits BCD) +64 32nd unit Local SP (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 Appendix H ES100j Digital Controller Protocol Write Local SP (Sequence No. 265) Writes the local SP to the program parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 Pattern No. Step No. 1st unit Local SP (rightmost 4 digits) +4 Local SP (leftmost 4 digits) +5 +6 (Undefined) Unit No. +7 Pattern No. Step No. 2nd unit Local SP (rightmost 4 digits) +8 Local SP (leftmost 4 digits) +9 ~ ~ +122 (Undefined) Unit No. +123 Pattern No. Step No. Local SP (rightmost 4 digits) +124 31st unit Local SP (leftmost 4 digits) +125 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 4 + 2 +1 Number of units (4 digits BCD) 0001 to 0031 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) +4 1st unit Local SP (rightmost 4 digits) (4 digits BCD) +5 1st unit Local SP (leftmost 4 digits) (4 digits BCD) 00 to 63 00 to 63 00000000 to 09999000 +122 31st unit Unit No. (2 digits BCD) +123 31st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) +124 31st unit Local SP (rightmost 4 digits) (4 digits BCD) +125 31st unit Local SP (leftmost 4 digits) (4 digits BCD) 00 to 31 00 to 63 00 to 63 00000000 to 09999000 Receive Data Word Allocation (3rd Operand of PMCR) None. 269 Appendix H ES100j Digital Controller Protocol Read Program Parameters (Sequence No. 266) Reads the local SP, step time, PID set No., wait code, and events from 1 to 10 set values in the program parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 Pattern No. Step No. +4 (Undefined) Unit No. +5 Pattern No. Step No. +6 (Undefined) Unit No. +7 Pattern No. Step No. +8 (Undefined) Unit No. Pattern No. Step No. +9 Offset 1st unit 2nd unit 3rd unit 4th unit Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0004 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 63 00 to 63 270 +8 4th unit Unit No. (2 digits BCD) +9 (max.) 4th unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 31 00 to 63 00 to 63 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Local SP (rightmost) +2 Local SP (leftmost) +3 Step bank time (rightmost) +4 Step bank time (leftmost) +5 PID set No. (rightmost) +6 PID set No. (leftmost) +7 Wait code (rightmost) +8 +9 +10 Event 1 setting (rightmost) Event 1 setting (leftmost) ~ ~ +27 Event 10 setting (rightmost) +28 Event 10 setting (leftmost) ~ ~ +85 Local SP (rightmost) +86 Local SP (leftmost) +87 Step bank time (rightmost) +88 Step bank time (leftmost) +89 PID set No. (rightmost) +90 +91 +92 +93 +94 PID set No. (leftmost) +112 4th unit (max.) Wait code (rightmost) Wait code (leftmost) Event 1 setting (rightmost) Event 1 setting (leftmost) ~ +111 1st unit Wait code (leftmost) ~ Event 10 setting (rightmost) Event 10 setting (leftmost) 271 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4digits BCD) Number of units 28 + 1 +1 to 2 1st unit Local SP (8 digits BCD) 00000000 to 09999000 F indicates a negative number. +3 to 4 1st unit Step time) (8 digits BCD) +5 to 6 1st unit PID set No. (8 digits BCD) +7 to 8 1st unit Wait code (8 digits BCD) +9 to 10 1st unit Event 1 setting (8 digits BCD) +11 to 12 1st unit Event 2 setting (8 digits BCD) +27 to 28 1st unit Event 10 setting (8 digits BCD) +29 to 30 1st unit Local SP (8 digits BCD) +109 to 110 4th unit Event 9 setting (8 digits BCD) +111 to 112 (max.) 4th unit Event 10 setting (8 digits BCD) Write Program Parameters (Sequence No. 267) Writes the local SP, step time, PID set No., wait code, and events from 1 to 10 settings in the program parameter area. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of units +2 (Undefined) Unit No. +3 Pattern No. Step No. +4 Local SP (rightmost) +5 Local SP (leftmost) +6 Step bank time (rightmost) +7 Step bank time (leftmost) +8 +9 +10 +11 +12 +13 PID set No. (rightmost) PID set No. (leftmost) Wait code (rightmost) Event 1 setting (rightmost) Event 1 setting (leftmost) ~ +30 +31 ~ Event 10 setting (rightmost) Event 10 setting (leftmost) ~ ~ +92 (Undefined) Unit No. +93 Pattern No. Step No. ~ 272 1st unit Wait code (leftmost) ~ +120 Event 10 setting (rightmost) +121 Event 10 setting (leftmost) 4th unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 30 + 2 +1 Number of units (4 digits BCD) 0001 to 0004 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 63 00 to 63 00000000 to 09999000 +4 to 5 1st unit Local SP (8 digits BCD) +6 to 7 1st unit Step time (8 digits BCD) +8 to 9 1st unit PID set No. (8 digits BCD) +10 to 11 1st unit Wait code (8 digits BCD) +12 to 13 1st unit Event 1 setting (8 digits BCD) +14 to 15 1st unit Event 2 setting (8 digits BCD) +30 to 31 1st unit Event 10 setting (8 digits BCD) +32 to 33 2nd unit Local SP (8 digits BCD) +111 to 112 4th unit Event 9 setting (8 digits BCD) +120 to 121 (max.) 4th unit Event 10 setting (8 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. Remote Setting Mode (Sequence No. 268) Switches the setting mode to the remote setting mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ 32nd unit (max.) 273 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Local Setting Mode (Sequence No. 269) Switches the setting mode to the local setting mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ 2nd unit ~ (Undefined) +33 1st unit Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. External Setting Mode (Sequence No. 270) Switches the setting mode to the external setting mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 274 ~ 32nd unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Run Command (Sequence No. 271) Starts control. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. 1st unit Pattern No./Bank No. +3 ~ +64 ~ (Undefined) Unit No. Pattern No. Bank No. +65 Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No./Bank No. (4 digits BCD) 0000 to 0063 +24 2nd unit Unit No. (2 digits BCD) 00 to 31 +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit Pattern No./Bank No. (4 digits BCD) 0000 to 0063 Receive Data Word Allocation (3rd Operand of PMCR) None. 275 Appendix H ES100j Digital Controller Protocol Reset (Stop) (Sequence No. 272) Stops control. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Auto Mode (Sequence No. 273) Switches the control mode to the auto mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit ~ ~ (Undefined) +33 Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. 276 00 to 31 Appendix H ES100j Digital Controller Protocol Manual Mode (Sequence No. 274) Switches the control mode to the manual mode. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) None. Execute A.T. (Sequence No. 275) Executes A.T. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 +2 +3 Number of send data words Number of units (Undefined) Unit No. 1st unit PID set No. ~ +64 +65 ~ (Undefined) PID set No. Unit No. 32nd unit (max.) 277 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit PID set No. (4 digits BCD) 0000 to 0008 +4 2nd unit Unit No. (2 digits BCD) 00 to 31 +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit PID set No. (4 digits BCD) 0000 to 0008 Receive Data Word Allocation (3rd Operand of PMCR) None. Cancel A.T. (Sequence No. 276) Cancels A.T. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ 2nd unit ~ (Undefined) +33 1st unit Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 +33 (max.) 32nd unit Unit No. (2 digits BCD) Receive Data Word Allocation (3rd Operand of PMCR) None. 278 00 to 31 Appendix H ES100j Digital Controller Protocol Change Pattern No. (Sequence No. 277) Changes the pattern number. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. 1st unit Pattern No. +3 ~ +64 ~ (Undefined) Unit No. 32nd unit (max.) Pattern No. +65 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (4 digits BCD) 0001 to 0063 +4 2nd unit Unit No. (2 digits BCD) 00 to 31 +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit Pattern No. (4 digits BCD) 0001 to 0063 Receive Data Word Allocation (3rd Operand of PMCR) None. Change Bank No. (Sequence No. 278) Changes the bank number. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 +2 +3 Number of send data words Number of units (Undefined) Unit No. 1st unit Bank No. ~ +64 +65 ~ (Undefined) Bank No. Unit No. 32nd unit (max.) 279 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units 2 + 2 +1 Number of units (4 digits BCD) 0001 to 0032 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Bank No. (4 digits BCD) 0000 to 0007 +4 2nd unit Unit No. (2 digits BCD) 00 to 31 +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit Bank No. (4 digits BCD) 0000 to 0007 Receive Data Word Allocation (3rd Operand of PMCR) None. Read Controller Status (Sequence No. 279) Reads the Controller status. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 1st unit Unit No. ~ ~ (Undefined) +26 Offset Unit No. 25th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits BCD) Number of units + 2 +1 Number of units (4 digits BCD) 0001 to 0025 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Operation status Hold +2 Auto/manual SP mode +3 Setting mode Valid pattern No. +4 A.T. Valid PID set No. +5 Wait Operation mode ~ 280 1st unit ~ +121 Operation status Hold +122 Auto/manual SP mode +123 Setting mode Valid pattern No. +124 A.T. Valid PID set No. +125 Wait Operation mode 25th unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) +0 Number of receive data words (4 digits BCD) +1 1st unit Operation status (2 digits BCD) Data Number of units 5 + 1 00: Reset 01: Run Hold (2 digits BCD) 00: Not hold 01: Hold +2 1st unit Auto/manual (2 digits BCD) 00: Auto mode 01: Manual mode SP mode (2 digits BCD) 00: Local SP mode 01: Remote SP mode 02: Fixed SP mode +3 1st unit Setting mode (2 digits BCD) 00: Local setting mode 01: Remote setting mode 02: External setting mode +4 Valid pattern No. (2 digits BCD) 00 to 63 1st unit A.T. (2 digits BCD) 00: Not A.T. 01: A.T. +5 Valid PD set No. (2 digits Hex) 01 to 08 1st unit Wait (2 digits BCD) 00: Not waiting 01: Waiting 02: Wait alarm output Operation mode (2 digits BCD) 00: Setting level 1 (without technical mode) 01: Setting level 1 (with technical mode) 02: Setting level 2 (without technical mode) 03: Setting level 2 (with technical mode) +125 (max.) 25th unit Wait (2 digits BCD) 00: Not waiting 01: Waiting 02: Wait alarm output Operation mode (2 digits BCD) 00: Setting level 1 (without technical mode) 01: Setting level 1 (with technical mode) 02: Setting level 2 (without technical mode) 03: Setting level 2 (with technical mode) General-purpose Command (Sequence No. 280) Sends the specified data and stores the received data in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Number of send data bytes +2 Send data (ASCII code) +3 Send data (ASCII code) ~ +126 ~ Send data (Undefined) (max. = 251 characters) 281 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0001 to 0128 +1 Number of send data bytes 0001 to 0251 The number of send bytes not including @, the FCS, or the terminator. +2 Refer to the manual for the ES100. Send data (ASCII 2 characters) Use ASCII (Up to 251 characters total.) +127 (max.) Send data (ASCII 1 characters) Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Receive data (ASCII code) +2 Receive data (ASCII code) ~ ~ Receive data +126 Offset (Undefined) (max.=251 characters) Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0001 to 0127 +1 Receive data (ASCII 2 characters) Refer to the manual for the ES100. Returned as ASCII (Up to 251 characters total.) +126 (max.) Receive data (ASCII 1 characters) Note 1. At transmission, a header code “@” is attached before the data and the FCS and a terminator “*”CR are attached following the send data. First word of send +0 data +1 0006 +2 “AB” +3 “CD” 0007 +4 “EF” +5 “GH” @ABCDEFG[FCS]*CR 2 bytes 2. At reception, data excluding the header code “@” at the beginning of the receive data and the FCS and terminator “*”CR at the end of the data is stored in the receive data storage words. First word of send +0 data +1 @ABCDEFG[FCS]*CR 2 bytes 0006 0007 +2 “AB” +3 “CD” +4 +5 “EF” “G” 3. Refer to the manual for the ES100 for the contents of send data and receive data. 282 Appendix I K3T Intelligent Signal Processor Protocol The K3T Intelligent Signal Processor Protocol is used to make various settings or control remotely the Intelligent Signal Processor connected to the Serial Communications Board via RS-232C or RS-422A/485 cable. Protocol Configuration The configuration of the K3T Intelligent Signal Processor Protocol is shown as follows: Sequence No. Communications sequence name Function 300 Reset (by unit number) Performs the same processing as when an input is received on the reset terminal. 301 Reset (continuous units) 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 Ladder interface Send word allocation Yes Receive word allocation No Performs the same processing as when an input is received on the reset terminal. Yes No Write set value (by unit number) Write set value HH (continuous units) Write set value H (continuous units) Write set value L (continuous units) Write set value LL (continuous units) Write set value with bank (by unit number) Writes the set value HH, H, L, or LL. Writes the set value HH. Yes No Yes No Writes the set value H. Yes No Writes the set value L. Yes No Writes the set value LL. Yes No Writes the set value to a bank which is not in use (K3TR: HH to LL, K3TC: O1 to O5). Yes No Write set value HH with bank (continuous units) Write set value H with bank (continuous units) Write set value L with bank (continuous units) Write set value LL with bank (continuous units) Write set value O5 with bank (continuous units) Write set value O4 with bank (continuous units) Write set value O3 with bank (continuous units) Write set value O2 with bank (continuous units) Write set value O1 with bank (continuous units) Read set value (by unit number) Read set value HH (continuous units) Read set value H (continuous units) Writes the set value HH to a bank which is not in use. Writes the set value H to a bank which is not in use. Writes the set value L to a bank which is not in use. Writes the set value LL to a bank which is not in use. Writes the set value O5 to a bank which is not in use. Writes the set value O4 to a bank which is not in use. Writes the set value O3 to a bank which is not in use. Writes the set value O2 to a bank which is not in use. Writes the set value O1 to a bank which is not in use. Reads the set value HH, H, L, or LL. Reads the set value HH. Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes Reads the set value H. Yes Yes Notes See Note1 See Note1 See Note1 See Note1 See Note1 See Note2 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 283 Appendix I K3Tj Intelligent Signal Processor Protocol Sequence No. 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 Communications sequence name Function Read set value L (continuous units) Read set value LL (continuous units) Read set value with bank (by unit number) Reads the set value L. Read set value HH with bank (continuous units) Read set value H with bank (continuous units) Read set value L with bank (continuous units) Read set value LL with bank (continuous units) Read set value O5 with bank (continuous units) Read set value O4 with bank (continuous units) Read set value O3 with bank (continuous units) Read set value O2 with bank (continuous units) Read set value O1 with bank (continuous units) Read holding data (by unit number) Read holding data PH (continuous units) Read holding data BH (continuous units) Read display value (PV) (by unit number) Read display value (PV ) (continuous units) Read model (by unit number) Read model (continuous units) General-purpose command Ladder interface Send word Receive word allocation allocation Yes Yes Reads the set value LL. Yes Yes Reads set value of a bank which is not in use (K3TR: HH to LL, K3TC: O1 to O5). Yes Yes Reads the set value HH of a bank which is not in use. Reads the set value H of a bank which is not in use. Reads the set value L of a bank which is not in use. Reads the set value LL of a bank which is not in use. Reads the set value O5 of a bank which is not in use. Reads the set value O4 of a bank which is not in use. Reads the set value O3 of a bank which is not in use. Reads the set value O2 of a bank which is not in use. Reads the set value O1 of a bank which is not in use. Reads the peak/bottom data (maximum, minimum). Reads the peak data (maximum). Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Reads the bottom data (minimum). Reads the display value (PV). Yes Yes Yes Yes Reads the display value (PV). Yes Yes Reads the model data. Yes Yes Reads the model data. Yes Yes Send specified data or receives specified data and writes it to the receive data words. Yes Yes Notes See Note1 See Note1 See Note2 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note3 See Note3 See Note3 Note 1. Special specifications are required to use communications + comparison output. 2. Special specifications are required to use communications + comparison output for the K3TR and K3TC. The operands HH, H, L, and LL are for the K3TR, and the operands O5, O4, O3, O2, and O1 are for the K3TC. 3. Not available for the K3TC. 4. Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). 284 Appendix I K3Tj Intelligent Signal Processor Protocol Connections The connections used for the K3T Intelligent Signal Processor Protocol are shown below. RS-232C Connections CQM1H K3T Serial Communications Board RS-232C port Signal name Abbreviation Signal direction Pin No. Protective ground or earth FG – 1 Signal ground or common return line SG – 7 Send data SD Output 2 Receive data RD Input 3 Request to send RS Output 4 Clear to send CS Input 5 Data set ready DR Input 6 Data terminal ready ER Output 20 Serial Communications Board Intelligent Signal Processor RS-232C: D-sub 9-pin female RS-232C: Terminal block Signal Pin Name No. Termi- Signal nal. Name Shielded cable MAX232C or equivalent Note 1. The connection configuration is a one-to-one configuration and the maximum cable length is 15 m. 2. Use shielded twisted-pair cable (AWG28i or greater). 285 Appendix I K3Tj Intelligent Signal Processor Protocol RS-422A/485 Connections CQM1H Serial Communications Board RS-422A/485 port K3T K3T Up to 32 units can be connected K3T • RS-422A Abbreviation Signal direction Pin No. Send data A Signal name SDA Output 9 Send data B SDB Output 5 Receive data A RDA Output 6 Receive data B RDB Input 1 Signal ground SG – 3 Protective ground FG – 7 Serial Board Terminating resistance Terminating resistance (terminator) 286 Communications RS-422A: D-sub 9-pin female Intelligent Signal Processor RS-422A: Terminal block Signal Pin Name No. Termi- Signal nal. Name Shielded cable Pin No. SN751177N or equivalent Terminal block SW Terminating resistance (approx. 220 Ω) is connected via the terminal block switch. Appendix I K3Tj Intelligent Signal Processor Protocol • RS-485 Signal name Abbreviation Signal direction Terminal Inverting output – Input or output 19 Non-inverting output + Input or output 18 Serial Communications Board RS-485: D-sub 9-pin female Signal Pin Name No. Intelligent Signal Processor Turn ON the terminal block switch for terminators only. RS-485: Terminal block SN751177N or equivalent Terminal block SW Termi- Signal nal. Name Shielded cable Intelligent Signal Processor Unit designated as terminator. RS-485: Terminal block Termi-Signal nal. Name Terminal block SW ON The terminal block switch is turned ON. Shielded cable Note 1. The connection configuration is a one-to-one or a 1-to-N configuration. For 1-to-N connections, up to 32 units including the Serial Communications Board can be connected. 2. The maximum cable length is 500 m. Use shielded twisted-pair cables (AWG28i or greater). 3. Connect terminating resistance at both ends of the transmission path. 4. Turn the terminal block switch ON at the terminators. 5. Turn the terminal block switches OFF for units that are not terminators. 287 Appendix I K3Tj Intelligent Signal Processor Protocol Reset (by Unit Number) (Sequence No. 300) This sequence performs the same processing as when an input is received on the reset terminal. Send Data Word Allocation (2nd Operand of PMCR) First word send data of +0 Number of send data words +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. ~ ~ (Undefined) +33 Offset Relevant unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0034 +1 Number of units (2 digits BCD) 00 to 32 +2 Relevant unit No. (2 digits BCD) 00 to 99 +33 Relevant unit No. (2 digits BCD) 00 to 99 Receive Data Word Allocation (3rd Operand of PMCR) None. Reset Control (Continuous Units) (Sequence No. 301) This sequence performs reset control for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 (Undefined) +1 Offset Number of units Contents (data format) Number of send data words (4 digits BCD) 0002 +1 Number of units (2 digits BCD) 00 to 32 Receive Data Word Allocation (3rd Operand of PMCR) None. 288 Data +0 Appendix I K3Tj Intelligent Signal Processor Protocol Write Set Value (by Unit Number) (Sequence No. 302) This sequence writes each set value (HH, H, L, LL). Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. Operand +3 Set value +4 (Undefined) +5 Set value ~ +122 ~ (Undefined) Relevant unit No. Operand +123 Set value +124 (Undefined) +125 Set value Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0126 +1 Number of units (2 digits BCD) 01 to 31 +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Operand (ASCII 2 characters) 4848 (“HH”), 4820 (“H”), +4 to +5 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 +4 +5 4C4C (“LL”) 4C20 (“L”) Example –1234 2345 +4 1234 0001 +5 000F +124 to +125 Set value (5 digits BCD) Same as above Receive Data Word Allocation (3rd Operand of PMCR) None. Write Set Value HH (Continuous Units) (Sequence No. 303) This sequence writes set value HH for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word send data of +0 +1 +2 +3 Number of send data words (Undefined) Number of units Set value (Undefined) ~ +64 +65 Set value ~ Set value (Undefined) Set value 289 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 to 0066 +1 Number of units (2 digits BCD) 01 to 32 +2 to +3 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 Example –1234 +2 2345 +2 1234 +3 0001 +3 000F +64 to +65 Set value (5 digits BCD) Same as above Receive Data Word Allocation (3rd Operand of PMCR) None. Write Set Value H (Continuous Units) (Sequence No. 304) This sequence writes set value H for continuous units. The word allocation is identical to that of sequence No. 303 (Write Set Value HH (Continuous Units)). Write Set Value L (Continuous Units) (Sequence No. 305) This sequence writes set value L for continuous units. The word allocation is identical to that of sequence No. 303 (Write Set Value HH (Continuous Units)). Write Set Value LL (Continuous Units) (Sequence No. 306) This sequence writes set value LL for continuous units. The word allocation is identical to that of sequence No. 303 (Write Set Value HH (Continuous Units)). Write Set Value with Bank (by Unit Number) (Sequence No. 307) This sequence writes set value of a bank which is not in use (K3TR: HH to LL, K3TC:O1 to O5). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. +3 (Undefined) Bank No. +4 +5 +6 Operand Set value (Undefined) Set value ~ (Undefined) Relevant unit No. +123 (Undefined) Bank No. +124 Operand +125 Set value +126 290 ~ +122 (Undefined) Set value Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 to 0127 +1 Number of units (2 digits BCD) 01 to 25 +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Bank No. (2 digits BCD) 01 to 04 +4 Operand (Two ASCII characters) 4848 (“HH”), 4820 (“H ”), 4C20 (“L ”), 4C4C (“LL”), +5 to +6 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) 4F31 (“O1”) 4F32 (“O2”) 4F33 (“O3”) 4F34 (“O4”) 4F35 (“O5”) Example 12345 +5 +6 Example –1234 2345 +5 1234 0001 +6 000F +125 to +126 Set value (5 digits BCD) Same as above Receive Data Word Allocation (3rd Operand of PMCR) None. Write Set Value HH with Bank (Continuous Units) (Sequence No. 308) This sequence writes set value HH of a bank not in use for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Number of units +2 (Undefined) Bank No. +3 +4 Set value (Undefined) Set value ~ +95 +96 +97 ~ (Undefined) Bank No. Set value (Undefined) Set value 291 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 to 0098 +1 Number of units (2 digits BCD) 01 to 32 +2 Bank No. (2 digits BCD) 01 to 04 +3 to +4 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 Example –1234 +2 2345 +2 1234 +3 0001 +3 000F +96 to +97 Set value (5 digits BCD) Same as above Receive Data Word Allocation (3rd Operand of PMCR) None. Write Set Value H with Bank (Continuous Units) (Sequence No. 309) This sequence writes set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value L with Bank (Continuous Units) (Sequence No. 310) This sequence writes set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value LL with Bank (Continuous Units) (Sequence No. 311) This sequence writes set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O5 with Bank (Continuous Units) (Sequence No. 312) This sequence writes set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O4 with Bank (Continuous Units) (Sequence No. 313) This sequence writes set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O3 with Bank (Continuous Units) (Sequence No. 314) This sequence writes set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). 292 Appendix I K3Tj Intelligent Signal Processor Protocol Write Set Value O2 with Bank (Continuous Units) (Sequence No. 315) This sequence writes set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O1 with Bank (Continuous Units) (Sequence No. 316) This sequence writes set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Read Set Value (by Unit Number) (Sequence No. 317) Reads set value HH, H, L, or LL. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. Operand +3 ~ ~ (Undefined) +64 Relevant unit No. Operand +65 Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0004 to 0066 Data +1 Number of units (2 digits BCD) 01 to 32 +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Operand (ASCII 2 characters) 4848 (“HH”), 4820 (“H”), 4C4C (“LL”) 4C20 (“L”) 4F31 (“01”) 4F35 (“05”) +64 to +65 Operand (ASCII 2 characters) Same as above Receive Data Word Allocation (3rd Operand of PMCR)) Receive data storage words +0 Number of receive data words +1 (Undefined) +2 +3 End code Set value (Undefined) Set value ~ +94 +95 +96 ~ (Undefined) End code Set value (Undefined) Set value 293 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0004 to 0097 +1 End code (2 digits Hex) 00 to 22 +2 to +3 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 Example –1234 +2 2345 +2 1234 +3 0001 +3 000F +95 to +96 Set value (5 digits BCD) Same as above Read Set Value HH (Continuous Units) (Sequence No. 318) This sequence reads set value HH for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 (Undefined) +1 Offset Number of units Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Number of units (2 digits BCD) 01 to 32 Receive Data Word Allocation (3rd Operand of PMCR) This sequence is similar to sequence No. 317 (Read Set Value (by Unit Number)). Read Set Value H (Continuous Units) (Sequence No. 319) This sequence reads set value H for continuous units. The word allocation is identical to that of sequence No. 318 (Read Set Value HH (Continuous Units)). Read Set Value L (Continuous Units) (Sequence No. 320) This sequence reads set value L for continuous units. The word allocation is identical to that of sequence No. 318 (Read Set Value HH (Continuous Units)). Read Set Value LL (Continuous Units) (Sequence No. 321) This sequence reads set value LL for continuous units. The word allocation is identical to that of sequence No. 318 (Read Set Value HH (Continuous Units)). 294 Appendix I K3Tj Intelligent Signal Processor Protocol Read Set Value with Bank (by Unit Number) (Sequence No. 322) Reads the set value of a bank which is not in use (K3TR: HH to LL, K3TC:01 to 05) and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. +3 (Undefined) Bank No. Operand +4 ~ ~ +95 (Undefined) Relevant unit No. +96 (Undefined) Bank No. Operand +97 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 to 0098 +1 Number of units (2 digits BCD) 01 to 32 +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Bank No. (2 digits BCD) 01 to 04 +4 Operand (ASCII 2 characters) 4848 (“HH”), 4820 (“H ”), 4C20 (“L ”), 4C4C (“LL”), 4F31 (“O1”) 4F32 (“O2”) 4F33 (“O3”) 4F34 (“O4”) 4F35 (“O5”) + 97 Operand (ASCII 2 characters) Same as above Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words Set value +1 (Undefined) +2 Set value ~ +63 ~ Set value +64 (Undefined) Set value Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0003 to 0065 Data +1 to +2 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 Example –1234 +1 2345 +1 1234 +2 0001 +2 000F +63 to +64 Set value (5 digits BCD) Same as above 295 Appendix I K3Tj Intelligent Signal Processor Protocol Read Set Value HH with Bank (Continuous Units) (Sequence No. 323) This sequence reads set value HH of a bank not in use for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word send data of Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Bank No. (Undefined) Bank No. ~ +33 ~ Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0034 +1 Number of units (2 digits BCD) 01 to 32 +2 Bank No. (2 digits BCD) 01 to 04 + 33 Bank No. (2 digits BCD) Same as above Receive Data Word Allocation (3rd Operand of PMCR) The word allocation is similar to sequence No. 322 (Read Set Value with Bank (by Unit Number)). Read Set Value H with Bank (Continuous Units) (Sequence No. 324) This sequence reads set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value L with Bank (Continuous Units) (Sequence No. 325) This sequence reads set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value LL with Bank (Continuous Units) (Sequence No. 326) This sequence reads set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O5 with Bank (Continuous Units) (Sequence No. 327) This sequence reads set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O4 with Bank (Continuous Units) (Sequence No. 328) This sequence reads set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). 296 Appendix I K3Tj Intelligent Signal Processor Protocol Read Set Value O3 with Bank (Continuous Units) (Sequence No. 329) This sequence reads set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O2 with Bank (Continuous Units) (Sequence No. 330) This sequence reads set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O1 with Bank (Continuous Units) (Sequence No. 331) This sequence reads set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Holding Data (Sequence No. 332) Reads the peak/bottom data (maximum, minimum) and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word send data of Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. Operand +3 ~ ~ (Undefined) +64 Relevant unit No. Operand +65 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 to 0066 +1 Number of units (2 digits BCD) 01 to 32 +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Operand (ASCII 2 characters) 5048 (“PH”) 4248 (“BH”) +65 Operand (ASCII 2 characters) Same as above 297 Appendix I K3Tj Intelligent Signal Processor Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Peak/bottom data (Undefined) +2 Peak/bottom data (Undefined) +3 Status ~ ~ +94 Peak/bottom data (Undefined) +95 Peak/bottom data Status (Undefined) +96 Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0004 to 0097 Data +1 to +2 Peak/bottom data (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 +3 Status (2 digits Hex) Example –1234 +1 2345 +1 1234 +2 0001 +2 000F d0 bit: If overflow: 1 Others: 0 d1 bit: If underflow: 1 Others: 0 d2 bit: Not used d3 bit: During forced zero operation: 1 (K3TH,K3TR: 0) Others: 0 d4 bit: Not used d5 bit: During hold input: 1 Others: 0 d6 bit: Bank input 1: 1 (K3TH, K3TX: 0) Others: 0 d7 bit: Bank input 2: 1 (K3TH, K3TX: 0) Others: 0 +96 Status Same as above Read Holding Data PH (Continuous Units) (Sequence No. 333) This sequence reads peak holding data for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word send data of Number of send data words +0 (Undefined) +1 Offset Number of units Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Number of units (2 digits BCD) 01 to 32 Receive Data Word Allocation (3rd Operand of PMCR) The data allocation is similar to sequence No. 332 (Read Holding Data (by Unit Number)). 298 Appendix I K3Tj Intelligent Signal Processor Protocol Read Holding Data BH (Continuous Units) (Sequence No. 334) This sequence reads bottom holding data for continuous units. The word allocation is identical to that of sequence No. 333 (Read Holding Data PH (Continuous Units)). Read Display Value (PV) (by Unit Number) (Sequence No. 335) Reads the display value (PV) and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. ~ ~ (Undefined) +33 Offset Relevant unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0034 +1 Number of units (2 digits BCD) 01 to 32 +2 Relevant unit No. (2 digits BCD) 00 to 99 + 33 Relevant unit No. (2 digits BCD) 00 to 99 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 +1 +2 +3 Number of receive data words Display value (Undefined) ~ +94 +95 +96 Display value Status ~ Display value (Undefined) Display value Status 299 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0004 to 0097 +1 to +2 Display value (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 +3 Status (4 digits Hex) Example –1234 +1 2345 +1 1234 +2 0001 +2 000F d0 bit: If overflow: 1 Others: 0 d1 bit: If underflow: 1 Others: 0 d2 bit: Not used d3 bit: During forced zero operation: 1 (K3TH, K3TR, K3TC: 0) d4 bit: In test mode: 1 Others: 0 d5 bit: While holding input: 1 Others: 0 d6 bit: Bank input 1: 1 (K3TH, K3TX: 0) Others: 0 d7 bit: Bank input 2: 1 (K3TH, K3TX: 0) Others: 0 d8 bit: LL comparison output: 1 Others: 0 OUT1 comparison output: 1 (K3TC) d9 bit: L comparison output: 1 Others: 0 OUT2 comparison output: 1 (K3TC) d10 bit: H comparison output: 1 Others: 0 OUT4 comparison output: 1 (K3TC) d11 bit: HH comparison output: 1 Others: 0 OUT5 comparison output: 1 (K3TC) d12 bit: PASS comparison output: 1 Others: 0 OUT3 comparison output: 1 (K3TC) d13 bit: Not used d14 bit: Not used d15 bit: Not used +96 300 Status (4 digits BIN) Same as above Others: 0 Appendix I K3Tj Intelligent Signal Processor Protocol Read Display Value (PV) (Continuous Units) (Sequence No. 336) This sequence reads display value (PV) for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 (Undefined) +1 Offset Number of units Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Number of units (2 digits BCD) 01 to 32 Receive Data Word Allocation (3rd Operand of PMCR) This sequence is similar to sequence No. 335 (Read Display Value (PV) (Continuous Units)). Model Data Read (by Unit Number) (Sequence No. 337) Reads model data and stores the results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 +1 (Undefined) Number of units +2 (Undefined) Relevant unit No. (Undefined) Relevant unit No. ~ ~ +26 Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0003 to 0027 Data +1 Number of units (2 digits BCD) 01 to 25 +2 Relevant unit No. (2 digits BCD) 00 to 99 + 26 Relevant unit No. (2 digits BCD) Same as above Note The number of Units can be up to 25 maximum. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 +1 +2 +3 Number of receive data words Input specifications Input specifications Display specifications Output specifications +4 Input contents +5 Operation mode ~ +121 +122 +123 ~ Input specifications Input specifications Display specifications Output specifications +124 Input contents +125 Operation mode 301 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0006 to 0126 +1 to +2 Input specifications (ASCII 3 characters) 544131 (“TA1”) (K3TH) 544231 (“TB1”) (K3TH) 564432 (“VD2”) (K3TX) 414432 (“AD2”) (K3TX) 564132 (“VA2”) (K3TX) 414132 (“AA2”) (K3TX) 524231 (“RB1”) (K3TR, K3TC) +2 Display specifications (ASCII 1 character) 41 (“A”) (common) 42 (“B”) (K3TH, K3TX) 43 (“C”) (K3TR, K3TC) +3 Output specifications (ASCII 2 characters) 5331 (“S1”) (RS-232C) 5332 (“S2”) (RS-485) 5333 (“S3”) (RS-422A) 5335 (“S5”) (RS-485 + comparison output) 5336 (“S6”) (RS-422A + comparison output) +4 Input contents (ASCII 2 characters) Leftmost digit: 30 (“0”) to 31 (“1”) +5 Operation mode (ASCII 2 characters) 3030 (“00”) (K3TH, K3TX) 3031 (“00”) to 3133 (“12”) (K3TR) 5542 (“UB”) (K3TC) 5543 (“UC”) (K3TC) Rightmost digit: 31 (“1”) to 45 (“E”) +125 Operation mode (ASCII 2 characters) Same as above Model Data Read (Continuous Units) (Sequence No. 338) This sequence reads model data for continuous units. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 (Undefined) +1 Offset Number of units Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Number of units (2 digits BCD) 01 to 25 Note The number of Units can be up to 25 maximum. Receive Data Word Allocation (3rd Operand of PMCR) The work allocation is similar to sequence No. 337 (Model Data Read (by Unit Number)). 302 Appendix I K3Tj Intelligent Signal Processor Protocol General-purpose Command (Sequence No. 339) Sends the specified data and writes the receive data to the receive data words. The characters such as “@”, FCS, terminators need not be set in the send and receive data words. These characters will be automatically added for transmission and automatically removed before saving data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data ~ ~ Send data +127 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0128 +1 Send data byte length (4 digits BCD) 0001 to 0251 Number of bytes of send data not including @, the FCS, and the terminator. +2 to +127 Send data (ASCII) ASCII code Send data: 251 characters max. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Receive data +2 Receive data +3 Receive data ~ ~ Receive data +126 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0001 to 0127 +1 to +126 Receive data (ASCII) ASCII code Receive data: 251 characters max. 303 Appendix J V500/V520 Bar Code Reader Protocol The V500/V520 Bar Code Reader Protocol is used to make various settings or control remotely the Bar Code Reader connected the Serial Communications Board via RS-232C cable. 305 Appendix J V500/V520 Bar Code Reader Protocol Protocol Configuration The configuration of the V500/V520 Bar Code Reader Protocol is shown below. Sequence No. Communications sequence name Function Ladder interface 350 BCR read start Instructs the Reader to start a BCR read. Send word allocation No 351 BCR read stop Instructs the Reader to stop a BCR read. No No 352 Data read No Yes 353 Complete data read No Yes 354 BCR function write (V500) BCR function read (V500) Log data output request (V500) Preset data set (V500) Data read by the Reader is received and saved in the receive words. Instructs the Reader to start a read. After the data read by the Reader is received and saved to the receive words, reading is stopped. Writes the operation mode and read functions. Reads the operation mode and read functions. Requests output of log data sent to host. Yes No No Yes Yes Yes 355 356 357 Receive word allocation No Writes preset data. Yes No BCR connection confirmation (V500) Log data clear (V500) Confirms if the Reader is correctly set. No No Clear log data. No No 360 Continuous data read (scan) (V500) No Yes 361 Continuous data read (interrupt) (V500) Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method. Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt No.100). No Yes 362 BCR initialize Yes No 363 Continuous data read (scan) (V520) No Yes 364 Continuous data read (interrupt) (V520) Clears the log, confirms BCR connection, and sets BCRs. Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method. Performing the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt No.100). No Yes 365 General-purpose command 1 Used to send data of a specified data length, and receive only ACK as the receive data. Yes No 366 General-purpose command 2 Used to send data of a specified data length, and receive ACK together with the return of other receive data. The frame format of the receive data, however, has to contain STX and ETX. Yes Yes 358 359 Note Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). 306 Appendix J V500/V520 Bar Code Reader Protocol Connections The connections for using the V500/V520 Bar Code Reader Protocol are shown below. V500 Connections 100 VAC V520-R12 CQM1H Reader Serial Communications Board RS-232C port V500-C11 ID Controller V509-W040 Reader Cable Serial Communications Board: D-sub 9 pin female Signal Name V500-C11: D-sub 9 pin female Pin No. Pin No. Signal Name V520 Connections V520-R121 Serial Communications Board Reader CQM1H Serial Communications Board RS-232C port V509-W011 Reader Cable Serial Communications Board: D-sub 9 pin female V520-R121: D-sub 9 pin female Signal Name Pin No. Pin No. Signal Name 307 Appendix J V500/V520 Bar Code Reader Protocol System Setting Shown below are the system settings of the V500-C11 and V520-R121 when this protocol is used. Note The portions enclosed by in boxes are used for this protocol. V500-C11 • BCR Functions Read trigger Read control method “READ SIGNAL INPUT”, “ONLINE READ COMMAND” “SINGLE READ”, “CONTINUOUS READ” • Host Interface Prefix Suffix Bar code output NONE, “STX” “ETX” , “CR ” “OUTPUT” , “NO OUTPUT” V520-R121 Start code Stop code Operation mode Data output mode 308 NONE, “STX” “ETX” , “CR” External trigger, host trigger 1-shot, continuous Appendix J V500/V520 Bar Code Reader Protocol BCR Read Start (Sequence No. 350) This sequence instructs the Bar Code Reader to start reading. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. BCR Read Stop (Sequence No. 351) This sequence instructs the Bar Code Reader to stop reading. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Data Read (Sequence No. 352) This sequence receives read data and saves it to the receive data storage words. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data +2 Read data +3 Read data +4 Read data ~ ~ +15 Read data +16 Read data Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0002 to 0017 Data +1 to +16 Read data (ASCII) 30 (‘0’) to 39 (‘9’), 41 (‘A’) to 5A (‘Z’), 3F (‘?’) Up to 32 characters in ASCII Note The reception wait time is not set for this sequence. Complete Data Read (Sequence No. 353) This sequence instructs the Bar Code Reader to start reading, receives the data read by the Bar Code Reader, stores the data in the receive data storage words, and then instructs the Reader to stop reading. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) It is similar to sequence No. 352 (Data read). Note The reception wait time is not set for this sequence. 309 Appendix J V500/V520 Bar Code Reader Protocol BCR Function Write (V500) (Sequence No. 354) This sequence sets the operation mode and read functions in the Bar Code Reader. Send Data Word Allocation (2nd Operand of PMCR) First word send data of Number of send data words +0 +1 Operation mode +2 Types of bar code (Undefined) +3 (Undefined) Number of digits +4 Modulus check (Undefined) (Undefined) Number of Multistep matches labels Horizontal control +5 Buzzer +6 In-zone control Offset Contents (data format) +0 Number of send data words Data 0007 (fixed) (4 digits BCD) +1 Operation mode (ASCII 1 character) 41 (‘A’) : ONLINE *42 (‘B’) : ONLINE CONTROL In-zone control (ASCII 1 character) *41 (‘A’) : 42 (‘B’) : +2 Bar code type (ASCII 1 character) 41 (‘A’) : JAN 42 (‘B’) : NW7 NORMAL 43 (‘C’) : NW7 SMALL 44 (‘D’) : NW7 HEX 45 (‘E’) : CODE39 NORMAL 46 (‘F’) : CODE39 ST/SP OUTPUT 47 (‘G’) : 2 of 5 (ITF) 48 (‘H’) : CODE128 49 (‘I’) : CODE93 4A (‘J’) : 2 of 5 (3BAR) 4B (‘K’) : 2 of 5 (5BAR) +3 Number of digits (2 digits BCD) 00 to 32 00: Any number of digits allowed. +4 Modulus check (ASCII 1 character) 41 (‘A’) : No-check 42 (‘B’) : Modulus 10 (all bar codes) 43 (‘C’) : Modulus 11 (except JAN) 44 (‘D’) : Modulus 16 (NW7 only) 45 (‘E’) : Modulus 43 (CODE39 only) 46 (‘F’) : Modulus 47 (CODE93 only) 47 (‘G’) : Modulus 103 (CODE128 only) +5 Number of matches (1 digit BCD) 1 to 5 Multistep labels (1 digit BCD) 1 to 4 Buzzer (ASCII 1 character) 41 (‘A’) : ON for normal read 42 (‘B’) : ON for no-read 43 (‘C’) : OFF Horizontal control mode (ASCII 1 character) 41 (‘A’) : Normal (continuous rotating) 42 (‘B’) : In-zone startup +6 ON OFF Note Selecting the values marked with asterisks is required for this protocol. Receive Data Word Allocation (3rd Operand of PMCR) None. 310 Appendix J V500/V520 Bar Code Reader Protocol BCR Function Read (V500) (Sequence No. 355) This sequence reads the settings of functions in the Bar Code Reader. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words Number of receive data words +0 +1 Operation mode In-zone control +2 Types of bar code (Undefined) +3 (Undefined) Number of digits +4 Modulus check (Undefined) +5 (Undefined) Number of Multistep matches. labels. Horizontal control Buzzer +6 Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0007 (fixed) +1 Operation mode (ASCII 1 character) 41 (‘A’) : ONLINE 42 (‘B’) : ONLINE CONTROL In-zone control (ASCII 1 character) 41 (‘A’) : ON 42 (‘B’) : OFF +2 Bar code type (ASCII 1 character) 41 (‘A’) : JAN 42 (‘B’) : NW7 NORMAL 43 (‘C’) : NW7 SMALL 44 (‘D’) : NW7 HEX 45 (‘E’) : CODE39 NORMAL 46 (‘F’) : CODE39 ST/SP Output 47 (‘G’) : 2 of 5 (ITF) 48 (‘H’) : CODE128 49 (‘I’) : CODE93 4A (‘J’) : 2 of 5 (3BAR) 4B (‘K’) : 2 of 5 (5BAR) +3 Number of digits (2 digits BCD) 00 to 32 +4 Modulus check (ASCII 1 character) 41 (‘A’) : No-check 42 (‘B’) : Modulus 10 (all bar codes) 43 (‘C’) : Modulus 11 (except JAN) 44 (‘D’) : Modulus 16 (NW7 only) 45 (‘E’) : Modulus 43 (CODE39 only) 46 (‘F’) : Modulus 47 (CODE93 only) 47 (‘G’) : Modulus 103 (CODE128 only) +5 Number of matches (1 digit BCD) 1 to 5 Multistep labels (1 digit BCD) 1 to 4 Buzzer (ASCII 1 character) 41 (‘A’) : ON for normal read 42 (‘B’) : ON for no-read 43 (‘C’) : OFF Horizontal control mode (ASCII 1 character) 41 (‘A’) : Normal (continuous rotating) 42 (‘B’) : In-zone startup +6 Data 311 Appendix J V500/V520 Bar Code Reader Protocol Log Data Output Request (V500) (Sequence No. 356) This sequence requests output of the log data sent to host. Send Data Word Allocation (2nd Operand of PMCR) First word send data of Number of send data words +0 (Undefined) +1 Number of units Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Number of units (2 digits BCD) 01 to 99 Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Log data +2 Log data ~ ~ +125 Log data +126 Log data Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0001 to 0127 +1 to +126 Log data (ASCII) Log data with the number of designated data is stored including the separator GS (1D). If the log data (including separator) exceeds 251 bytes, only 251 bytes are stored. Note No retries are performed for this sequence. 312 Data Appendix J V500/V520 Bar Code Reader Protocol Preset Data Set (V500) (Sequence No. 357) This sequence sets preset data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data Number of send data words +0 +1 (Undefined) Number of presets +2 (Undefined) Preset data No. (Undefined) +3 Number of units +4 Preset data +5 Preset data ~ ~ +18 Preset data +19 Preset data ~ ~ +(18N+2) (Undefined) +(18N+3) (Undefined) Preset data No. Number of units +(18N+4) Preset data +(18N+5) Preset data ~ ~ +(18N+18) Preset data +(18N+19) Preset data Offset Contents (data format) +0 Number of send data words (4 digits BCD) 18N+2 (N is number of presets 1 to 5) +1 Number of presets (1 digit BCD) 1 to 5 +2 Preset data No. (1 digit BCD) 1 to 5 +3 Data length (2 digits BCD) 01 to 32 +4 to +19 Preset data (ASCII) Combination of the following ASCII characters and up to 32 characters maximum: 30 (’0’) to 39 (’9’) 41 (’A’) to 5A (’Z’), 3F (’?’) The area that is not used is undefined +20 to +91 Data Store repeatedly the contents of words with offsets +2 to +19 the same number of times as the number of presets (N) Receive Data Word Allocation (3rd Operand of PMCR) None. BCR Connection Confirmation (V500) (Sequence No. 358) This sequence confirms whether the Bar Code Reader is connected correctly or not. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. 313 V500/V520 Bar Code Reader Protocol Appendix J Log Data Clear (V500) (Sequence No. 359) This sequence clears the log data. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Data Continuous Read (Scan) (V500) (Sequence No. 360) This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data word allocation is similar to that of sequence No. 352 (Data read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Bar Code Reader still keeps reading. Execute sequence No. 351 (BCR read stop) to end the sequence. Note The reception wait time is not set for this sequence. Data Continuous Read (Interrupt) (V500) (Sequence No. 361) This sequence performs the following operations repeatedly: Instruct the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation similar to that of sequence No. 352 (data read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Bar Code Reader keeps reading. Execute sequence No. 351 (BCR read stop) to end the sequence. Note The reception wait time is not set for this sequence. BCR Initialize (V500) (Sequence No. 362) This sequence clears the log data, confirms BCR connection and sets the BCR functions. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of sequence No. 354 (BCR Function Set). Receive Data Word Allocation (3rd Operand of PMCR) None. Data Continuous Read (Scan) (V520) (Sequence No. 363) This sequence performs the following operations repeatedly: instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data. Send Data Word Allocation (2nd Operand of PMCR) None. 314 Appendix J V500/V520 Bar Code Reader Protocol Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 352 (Data Read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR Read Stop) to end the sequence. 3. The reception wait time is not set for this sequence. Data Continuous Read (Interrupt) (V520) (Sequence No. 364) This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The send data word allocation is similar to that of sequence No. 352 (Data Read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR Read Stop) to end the sequence. 3. The reception wait time is not set for this sequence. General-purpose Command 1 (Sequence No. 365) This general-purpose command is used to send data with a specified data length, and receive back only ACK. STX and ETX are automatically attached to the send data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data ~ ~ +127 Send data +128 Send data Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0003 to 0129 Data +1 Send data byte length (4 digits BCD) 0001 to 0254 The byte length of the send data excluding STX and ETX. +2 to +128 Send data (ASCII) Inscribe send data up to 254 bytes (max.) by ASCII. Receive Data Word Allocation (3rd Operand of PMCR) None. General-purpose Command 2 (Sequence No. 366) This general-purpose command is used to send data with a specified data length, and receive back ACK in addition to other receive data. The frame format of the receive data, however, has to contain STX and ETX. STX and ETX are automatically attached to the send data. 315 Appendix J V500/V520 Bar Code Reader Protocol Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data ~ ~ +127 Send data +128 Send data Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0003 to 0129 Data +1 Send data byte length (3 digits BCD) 1 to 254 The byte length of the send data excluding STX and ETX. +2 to +128 Send data (ASCII) Set send data up to 254 bytes (max.) by ASCII. Receive Data Storage Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Receive data +2 Receive data ~ ~ +126 Receive data +127 Receive data Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0001 to 0128 Data +1 to +127 Receive data (ASCII) If the receive data exceed 253 bytes, only 253 bytes are stored. Note Shown below is the receive data frame format. The reception data without ACK, STX, and ETX is stored. Receive data (253 bytes max.) STX ACK 316 ETX Appendix K 3Z4L Laser Micrometer Protocol The 3Z4L Laser Micrometer Protocol is used to make various settings or control remotely the Laser Micrometer connected to the Serial Communications Board via RS-232C cable. Protocol Configuration The configuration of the 3Z4L Laser Micrometer Protocol is shown below. Sequence No. Communications sequence name 400 3Z4L clear 401 Memory switch set 402 Function Ladder interface Send word allocation Receive word allocation Resets errors, data, analog output, decision result and places the Laser Micrometer into standby. No No Yes No mm unit set Sets memory switches and the area for the work position LED. Sets the display unit to mm. No No 403 E unit set Sets the display unit to E. No No 404 Calibration set Calibrates the Laser Micrometer. Yes No 405 Calibration release No No 406 Program number set (3000-series) Measurement condition set (3000-series) Measurement condition release (3000-series) Measurement condition list request (3000-series) Single run measurement start (3000-series) Yes No Yes No Releases measurement conditions that have been set. Requests the measurement conditions that have been set and other settings. When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results. If the sample measurement condition is zero, starts a zero run measurement. Starts a continuous measurement. The scan notification method is used for receive data. Yes No No Yes No Yes No No No Yes Starts a continuous measurement. The interrupt notification method is used for receive data. No Yes Calibration setting release. 407 408 409 410 411 412 413 Zero run measurement start (3000-series) Continuous measurement start (scan) (3000-series) Continuous measurement start (interrupt) (3000-series) Releases the calibration of the Laser Micrometer. Switches the program number to a specified number. Sets measurement conditions. Measurement termination (3000-series) 414 415 416 417 Measurement termination (3000-series) Data request (3000-series) Terminates a continuous measurement. No No*1 Requests display data in the idle measurement status or the latch data generated by the measurement command. No Yes Statistic processing execution (3000-series) Statistic processing nonexecution (3000-series) Lights the statistic processing LED and processes the statistics. Turns OFF the statistic processing LED. Statistics are not processed. No No No No 317 Appendix K 3Z4L Laser Micrometer Protocol Sequence No. Communications sequence name 418 All statistic memory clear (3000-series) Clears statistic processing memories of all programs. No No 419 Statistic memory clear (3000-series) Clears statistic processing memories of program under display. No No 420 Statistic result request (3000-series) Requests statistic processing result. No Yes 421 Memory switch set 1 (3000-series) Sets memory switches. Yes No 422 Memory switch set 2 (3000-series) Sets memory switches. Yes No 423 Simple AVG times set (3000-series) Taking the simple average as the averaging method, sets the averaging times per measurement interval 4. Yes No 424 AVG move interval set (3000-series) Taking the average move as the averaging method, sets the measurement interval number. Yes No 425 AVG move (H) times set (3000-series) Taking the average move and high-speed data output as the averaging method, sets the averaging times per measurement interval 4. Yes No 426 AVG move (L) times set (3000-series) Taking the average move and low-speed data output as the averaging method, sets the averaging times per measurement interval 4. Yes No 427 Automatic detection set (3000-series) Sets work automatic detection function. Yes No 428 Automatic detection release (3000-series) Releases the settings of work automatic detection function. No No 429 Automatic detection list request (3000-series) Requests the settings of work automatic detection function. No Yes 430 3Z4L initialize (3000-series) Clears the 3Z4L, sets the mm unit, sets the memory unit, does not processes statistics, and clears all statistic memory. Yes No 431 Measurement condition set (4000-series) Sets measurement conditions. Yes No 432 Measurement condition release (4000-series) Releases measurement conditions that have been set. Yes No 433 Measurement condition list request (4000-series) Requests the measurement conditions that have been set and other settings. No Yes 434 Single run measurement start (4000-series) When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results. No Yes 435 Deflection measurement start (4000-series) Starts a deflection measurement. No No 436 Continuous measurement start (scan) (4000-series) Starts a continuous measurement. The scan notification method is used for receive data. No Yes 437 Continuous measurement start (interrupt) (4000-series) Starts a continuous measurement. The interrupt notification method is used for receive data. No Yes 438 Measurement termination (4000-series) Terminates continuous measurement. No No *1 318 Function Ladder interface Receive Send word word allocation allocation Appendix K 3Z4L Laser Micrometer Protocol Sequence No. Communications sequence name 439 Data request (4000-series) 440 441 442 443 444 445 Function Ladder interface Receive Send word word allocation allocation Requests measurement data in the idle measurement status or the latch data generated by the measurement command. Forced positive zero Sets the forced zero direction to positive (4000-series) (+). Forced negative zero Sets the forced zero direction to negative (4000-series) (–). Forced zero release (4000-se- Releases the forced zero direction. ries) 3Z4L initialize (4000-series) Clears the 3Z4L, sets the mm unit, and clears the memory unit settings. General-purpose command 1 Used to send data of a specified data length, and receive only OK as the receive data. General-purpose command 2 Used to send data of a specified data length, and receive data other than OK. No Yes No No No No No No Yes No Yes No Yes Yes *1 Depends on the measurement contents. Note Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). Connections The connections for the 3Z4L Laser Micrometer Protocol are shown below. RS-232C Connection Sensor Signal cable CQM1H Serial Communications Board RS-232C Port Serial Communications Board: D-sub 9 pin (female) Controller Controller: D-sub 25 pin (female) Signal name Pin No. Pin No. Signal name FG SD RD RS CS DR ER SG 1 2 3 4 5 7 8 9 1 2 3 4 5 6 7 20 FG TXD RXD RTS CTS DSR SG DTR 319 Appendix K 3Z4L Laser Micrometer Protocol DIP Switch Settings Shown below are the settings of 3Z4L-3000, 3Z4L-4000-series DIP switches required to use the system protocol sequences. 3Z4L-3000 Series • DIP Switch 1 No. Setting Baud rate 1 2 Status ON/OFF ON/OFF 3 Handshaking procedure ON/OFF 4 RS-232C interface use selection ON/OFF 5 6 ON/OFF ON/OFF • DIP Switch 2 No. Setting Selection for measurement section 1 2 3 Status ON/OFF Set these settings according to the sensor connected. ON/OFF ON/OFF 4 ON/OFF Setting of minimum read value ON/OFF 7 Setting of transparent body measurement function ON/OFF 8 Setting of simultaneous measurement function ON/OFF 5 6 Set these settings for 4 digits in the decimal portion. ON/OFF • DIP Switch 3 No. Setting Setting of measurement function by 2 measurement instruments 1 2 3 Status ON/OFF ON/OFF ON/OFF 4 ON/OFF 5 Error data exclusion function ON/OFF 6 Multistep selection function ON/OFF This protocol does not support the error data exclusion function 3Z4L-4000 Series • DIP Switch 1 No. 1 Setting Baud rate 2 ON/OFF 3 Hand-shake procedure ON/OFF 4 Delimiter ON/OFF 5 6 7 8 320 Status ON/OFF ON/OFF RS-232C interface use selection ON/OFF ON/OFF ON/OFF Appendix K 3Z4L Laser Micrometer Protocol • DIP Switch 2 No. 1 2 Setting Status Selection for measurement section ON/OFF 3 ON/OFF 4 ON/OFF ON/OFF 6 Setting of minimum read value 7 Display unit ON/OFF 8 External command setting ON/OFF 5 Set these settings according to the sensor connected. ON/OFF Set these settings for 4 digits in the decimal portion. ON/OFF Delimiter Control Code Setting 3Z4L-4000 Series The delimiter control codes must be set on DIP switch SW1 for the 3Z4L-4000 Series. Turn off pins 4 and 5, set the delimiter codes to CR+LF, and set the delimiter code control setting in the sequence to CR+LF. See the setting for CR+LF in the following diagram. 1 2 3 4 5 6 7 8 Turn OFF. Turn OFF (to use a general-purpose interface) Turn ON (to use a general-purpose interface) Delimiter Setting Delimiter CR+LF CR LF Pin 4 OFF ON OFF Pin 5 OFF OFF ON Pin Handshaking ON: OFF: Control (recognize DRT input) 3-wire method (non-protocol) Baud Rate Baud rate 1200 2400 4800 9600 Pin 1 OFF ON OFF ON Pin 2 OFF OFF ON ON Pin 3Z4L-3000 Series The delimiter control code does not need to be set on the DIP switch for the 3Z4L-3000 Series. Set the delimiter 321 Appendix K 3Z4L Laser Micrometer Protocol control codes in the sequence to CR+LF for the send code and to CR or CR+LF for the receive code. See the settings in the following diagram. 1 2 3 4 5 6 Turn OFF. Turn OFF (to use a general-purpose interface) Turn ON (to use a general-purpose interface) Handshaking ON: OFF: Control (recognize DRT input) 3-wire method (non-protocol) Baud Rate Baud rate 1200 2400 4800 9600 Pin 1 OFF ON OFF ON Pin 2 OFF OFF ON ON Pin The High-speed 3Z4L-3000-series Meters must have the delimiter control codes set using the memory switches. Set both the send and receive codes to CR+LF. 322 Appendix K 3Z4L Laser Micrometer Protocol 3Z4L Clear (Sequence No. 400) This sequence resets errors, data, analog output, and decision result, and puts the Laser Micrometer into standby. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Memory Switch Set (Sequence No. 401) This sequence sets memory switches and the area for the work position LED. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words W X Y (Undefined) +2 Offset Contents (data format) Z V Data 3000-series 4000-series +0 Number of send data words (4 digits BCD) 0003 (fixed) 0003 (fixed) +1 w (1 digit BCD) Using buzzer sound: 0 to 3 Number of digits for extinguishing indicator: 0 to 2 x (1 digit BCD) Automatic latch release time: 0 to 9 I/O IF RUN Input: 0 or 1 y (1 digit BCD) Using print timer, the setting for simultaneous measurement: 0 to 3 (high-speed), 0 to 1 (other) Display of Err-0: 0 or 1 z (1 digit BCD) Display of the comma for 1/1000s digit, number of display digits: 0 to 5 (high-speed), 0 to 3 (other) Averaging method: 0 to 2 (high-speed), 0 (other) v (1 digit BCD) Measurement interval 4: 0 to 6 Use of comma: 0 or 1 +2 Receive Data Word Allocation (3rd Operand of PMCR) None. mm Unit Set (Sequence No. 402) This sequence sets the display unit to mm. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. E Unit Set (Sequence No. 403) This sequence sets the display unit to E. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. 323 Appendix K 3Z4L Laser Micrometer Protocol Calibration Set (Sequence No. 404) This sequence calibrates the Laser Micrometer. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Decimal portion +2 (Undefined) +3 Sign Decimal integer portion (Undefined) High calibration gauge dimension Decimal portion +4 +5 (Undefined) +6 Sign (Decimal integer portion) (Undefined) Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0007 (fixed) +1 HC gauge dimension (Decimal portion) (4 digits BCD) 0000 to 9999 +2 +3 +4 to +6 Low calibration gauge dimension Data Example –123.4567 +1 4567 +2 0123 +3 2D00 Example –123.4567 HC gauge dimension (integer portion) (3 digits BCD) 000 to 999 HC gauge dimension (Sign) (ASCII 1 character) if +: 20(‘ ’) if –: 2D(‘–’) LC gauge dimensions Same as HC gauge dimensions +1 4567 +2 0123 +3 2D00 Note 1. For this sequence, both the high and low calibration gauges must be set. 2. The limit value, reference value, and offset value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion. Receive Data Word Allocation (3rd Operand of PMCR) None. Calibration Release (Sequence No. 405) This sequence releases the calibration of the Laser Micrometer. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence releases both the high and low calibration. 324 Appendix K 3Z4L Laser Micrometer Protocol Program Number Set (3000-series) (Sequence No. 406) This sequence switches the program number to a specified number. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Program number (1 digit BCD) Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Program number (1 digit BCD) 0 to 9 Receive Data Word Allocation (3rd Operand of PMCR) None. Note Retry processing is not performed for this sequence. Measurement Condition Set (3000-series) (Sequence No. 407) This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Unused) +2 Segment number (SG) +3 +4 +5 (Undefined) Measurement interval number (M) Decimal portion +6 +7 (Undefined) +8 Sign Integer portion Lower limit value (LL) (Undefined) Decimal portion +9 +10 (Undefined) +11 Sign Integer portion Upper limit value (LH) (Undefined) Decimal portion +12 +13 (Undefined) +14 Sign Integer portion Multistep selection limit value (L1) (Undefined) Decimal portion +15 +16 (Undefined) +17 Sign Integer portion Multistep selection limit value (L2) (Undefined) Decimal portion +18 +19 (Undefined) +20 Sign Integer portion Multistep selection limit value (L3) (Undefined) Decimal portion +21 +22 (Undefined) +23 Sign +24 Integer portion Multistep selection limit value (L4) (Undefined) Decimal portion +25 (Undefined) +26 Sign +27 Integer portion Multistep selection limit value (L5) (Undefined) Decimal portion +28 (Undefined) +29 Sign Integer portion Multistep selection limit value (L6) (Undefined) 325 Appendix K 3Z4L Laser Micrometer Protocol Decimal portion +30 +31 (Undefined) +32 Sign +33 (Undefined) Reference value (REF) Integer portion (Undefined) Analog output scale number (SCL) +34 Offset classification (OF) (Undefined) +35 Decimal portion +36 +37 (Undefined) +38 Sign +39 (Undefined) +40 (Undefined) +41 (Undefined) Integer portion Offset value (Undefined) Data output conditions (PR) Schedule output timer Sample measurement pulse (PRT) (SMP) +42 (Undefined) +43 +44 (Unused) +45 (Unused) +46 0 +47 0 +48 0 +49 0 +50 0 +51 0 +52 0 +53 0 Setting Yes/No flags Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0054 (fixed) +1 Unused Undefined +2 to +4 Segment number (ASCII 6 characters) Combination of 31(‘1’) to 36(‘6’), 20(‘ ’) +5 Measurement interval number (1 digit BCD) 1 to 4 +6 Lower limit value (decimal portion) (4 digits BCD) Lower limit value (Integer portion) (3 digits BCD) 0000 to 9999 +8 Lower limit value (Sign) (ASCII 1 character) if +: 20(‘ ’) if –: 2D(‘–’) +9 to +11 Upper limit value Same as lower limit values +12 to +14 Multistep selection limit value (L1) Same as lower limit values +15 to +17 Multistep selection limit value (L2) Same as lower limit values +18 to +20 Multistep selection limit value (L3) Same as lower limit values +21 to +23 Multistep selection limit value (L4) Same as lower limit values +24 to +26 Multistep selection limit value (L5) Same as lower limit values +27 to +29 Multistep selection limit value (L6) Same as lower limit values +7 326 Sample measurement classification Data Example –123.4567 +6 000 to 999 4567 +7 0123 +8 2D00 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +30 to +32 Reference value Same as lower limit values +33 Analog output scale number (1 digit BCD) 1 to 3 +34 to +35 Offset classification (ASCII 3 characters) 4F4620 (“OF”), 4F4D20 (“OM”) +36 to +38 Offset value Same as lower limit values +39 Data output conditions (1 digit BCD) 0 to 6 +40 Scheduled output timer (3 digits BCD) 000 to 999 +41 Sample measurement pulse (3 digits BCD) 000 to 999 +42 to +43 Sample measurement classification (ASCII 3 characters) 415647 (“AVG”), 4D4158 (“MAX”) 4D494E (“MIN”), 524E47 (“RNG”) +44 to +45 Unused Undefined +46 Yes/No for segment setting (1 digit BCD) Set: Yes/No for measurement interval number setting (1 digit BCD) Set: Yes/No for upper/lower limit value setting (1 digit BCD) Set: Yes/No for multistep selection limit value (1 digit BCD) Set: Yes/No for reference setting (1 digit BCD) Set: +51 Yes/No for offset value setting (1 digit BCD) Set: +52 Yes/No for data output condition setting (1 digit BCD) Set: Yes/No for sample measurement pulse setting (1 digit BCD) Set: +47 +48 +49 +50 +53 Data 1 (SG) Don’t set: 0 1 (M) Don’t set: 0 1 (LL,LH) Don’t set: 0 1 (L1,L2,L3,L4,L5,L6) Don’t set: 0 1 (REF, SCL) Don’t set: 0 1 (OF or OM) Don’t set: 0 1 (PR, PRT) Don’t set: 0 1 (SMP, MAX or MIN or RNG or AVG) Don’t set: 0 Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. This sequence cannot be used to set the error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function). 2. The following settings must be made together with this sequence; they cannot be set separately. Lower limit, upper limit Multistep selection limit Reference value, analog output scale number Data output conditions, scheduled print timer 3. The limit value, reference value, and offset value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion. 327 3Z4L Laser Micrometer Protocol Appendix K Measurement Condition Release (3000-series) (Sequence No. 408) This sequence releases the measurement conditions that have been set. Send Data Word Allocation (2nd Operand of PMCR) Send data word allocation is similar to that of sequence No. 407 (Measurement Condition Set). However, only the setting Yes/No flags at +46 to +53 from the send data leading word can be used. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. The following conditions are used when the measurement conditions are released: Segment becomes 1, measurement interval becomes 1, the number of sample measurement pulses becomes 1. 2. The following conditions cannot be released with this sequence: error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function). 3. The following settings cannot be released separately using this sequence. Lower limit, Upper limit Multistep selection limit Reference value, analog output scale number Data output conditions, scheduled print timer Measurement Condition List Request (3000-series) (Sequence No. 409) This sequence requests the measurement condition settings that have been set and other settings. Send Data Word Allocation (2nd Operand of PMCR) None. 328 Appendix K 3Z4L Laser Micrometer Protocol Receive Data Word Allocation (3rd Operand of PMCR) First word of send data +0 Number of receive data words (Undefined) +1 Program number (P) +2 Segment number (SG) +3 +4 (Undefined) +5 Measurement interval number (M) Decimal portion +6 +7 (Undefined) +8 Sign Integer portion Lower limit value (LL) (Undefined) Decimal portion +9 +10 (Undefined) +11 Sign Integer portion Upper limit value (LH) (Undefined) Decimal portion +12 +13 (Undefined) +14 Sign Integer portion Multistep selection limit value (L1) (Undefined) Decimal portion +15 +16 (Undefined) Integer portion +17 Sign (Undefined) Multistep selection limit value (L2) Decimal portion +18 +19 (Undefined) +20 Sign Integer portion Multistep selection limit value (L3) (Undefined) Decimal portion +21 +22 (Undefined) Integer portion +23 Sign (Undefined) Multistep selection limit value (L4) Decimal portion +24 +25 (Undefined) Integer portion +26 Sign (Undefined) Multistep selection limit value (L5) Decimal portion +27 +28 (Undefined) Integer portion +29 Sign (Undefined) Multistep selection limit value (L6) Decimal portion +30 +31 (Undefined) Integer portion +32 Sign (Undefined) (Undefined) +33 Reference value (REF) Analog output scale number (SCL) +34 (Undefined) +35 Decimal portion +36 +37 (Undefined) Integer portion +38 Sign (Undefined) +40 (Undefined) +41 (Undefined) Scheduled output timer Sample measurement pulse +39 (Undefined) +44 +45 Offset value (LH) Data output condition (PR) +42 +43 Offset classification (OF) (PRT) (SMP) Sample measurement classification Statistical processing calculation classification (Undefined) 329 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0046 (fixed) +1 Program number (1 digit BCD) 0 to 9 +2 to +4 Segment number (ASCII 6 characters) Combination of 31(‘1’) to 36(‘6’), 20(‘ ’) +5 Measurement interval number (1 digit BCD) 1 to 4 +6 Lower limit value (Decimal portion) (4 digits BCD) Lower limit value (Integer portion) (3 digits BCD) 0000 to 9999 Example –123.4567 +6 4567 000 to 999 +7 0123 +8 F000 +8 Lower limit value (Sign) (BIN) If +: 0 If – : F +9 to +11 Upper limit value Same as lower limit values +12 to +14 Multistep selection limit value (L1) Same as lower limit values +15 to +17 Multistep selection limit value (L2) Same as lower limit values +18 to +20 Multistep selection limit value (L3) Same as lower limit values +21 to +23 Multistep selection limit value (L4) Same as lower limit values +24 to +26 Multistep selection limit value (L5) Same as lower limit values +27 to +29 Multistep selection limit value (L6) Same as lower limit values +30 to +32 Reference value Same as lower limit values +33 Analog output scale number (1 digit BCD) 1 to 3 +34 to +35 Offset classification (ASCII 3 characters) 4F4620 (“OF”), 4F4D20 (“OM”) +36 to +38 Offset value Same as lower limit values +39 Data output condition (1 digit BCD) 0 to 6 +40 Scheduled output timer (3 digits BCD) 000 to 999 +41 Sample measurement pulse (3 digits BCD) 000 to 999 +42 to +43 Sample measurement classification (ASCII 3 characters) 415647 (“AVG”), 4D4158 (“MAX”) 4D494E (“MIN”), 524E47 (“RNG”) +44 to +45 Statistical processing calculation classification (ASCII 3 characters) 535420 (“ST”), 4E5354 (“NST”) +7 Data Note This sequence cannot be used to request the lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function). 330 Appendix K 3Z4L Laser Micrometer Protocol Single Run Measurement Start (3000-series) (Sequence No. 410) When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data stor- +0 age words +1 Number of receive data words (Undefined) Program number Decision result +2 Decimal portion +3 +4 (Undefined) +5 Sign Integer portion Measurement value (Undefined) Decimal portion +6 +7 (Undefined) Integer portion Sign (Undefined) +8 Deviation value Offset Contents (data format) +0 Number of receive data words (4 digit BCD) With no reference setting: 0006 With reference setting: 0009 Data +1 Program number (1 digit BCD) 0 to 9 +2 Decision result (ASCII 2 characters) With no limit setting: 0000 With limit setting: 2B4E (“+N”), 4F4B (“OK”), 2D4E (“–N”) Measurement value (decimal portion) (4 digits BCD) Measurement value (integer portion) (3 digits BCD) 0000 to 9999 Example –123.4567 +3 4567 000 to 999 +4 0123 +5 F000 +5 Measurement value (Sign) (BIN) If +: 0 +6 to +8 Deviation value Same as measurement value *The deviation will be stored in this area only when reference setting is made. +3 +4 If –: F Zero Run Measurement Start (3000-series) (Sequence No. 411) If the sample measurement condition is zero, a zero run measurement is started. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Note The zero run measurement keeps measuring until sequence No. 414 (Measurement Termination) is executed. Continuous Measurement Start (Scan) (3000-series) (Sequence No. 412) A continuous measurement is started. The scan notification method is used for the receive data. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). 331 3Z4L Laser Micrometer Protocol Appendix K Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 414 (Measurement Termination) to end the sequence. Continuous Measurement Start (Interrupt) (3000-series) (Sequence No. 413) A continuous measurement is started. The interrupt notification method is used for the receive data and the interrupt No. is 101. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 414 (Measurement Termination) to end the sequence. Measurement Termination (3000-series) (Sequence No. 414) This sequence terminates a continuous measurement. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) For continuous measurement: Not available For Zero Run Measurement The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Data Request (3000-series) (Sequence No. 415) This sequence requests display data in the idle measurement status or the latch data generated by the measurement command. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Statistic Processing Execution (3000-series) (Sequence No. 416) This sequence lights the statistic processing LED and implements the statistic processing. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. 332 Appendix K 3Z4L Laser Micrometer Protocol Statistic Processing Non-execution (3000-series) (Sequence No. 417) This sequence turns the statistic processing LED off and does not carry out the statistic processing. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. All Statistic Memory Clear (3000-series) (Sequence No. 418) This sequence clears statistic processing memories of all programs. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Statistic Processing Memory Clear (3000-series) (Sequence No. 419) This sequence clears statistic processing memories of the program under display. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Statistic Result Request (3000-series) (Sequence No. 420) This sequence requests the statistic processing results. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Program number (P) +2 +3 Number of statistic data (N) (Undefined) Decimal portion +4 +5 (Undefined) +6 Sign Integer portion Average value (AVG) (Undefined) Decimal portion +7 +8 (Undefined) +9 Sign Integer portion Maximum value (MAX) (Undefined) Decimal portion +10 +11 (Undefined) +12 Sign Integer portion Minimum value (MIN) (Undefined) Decimal portion +13 +14 (Undefined) +15 Sign Integer portion Range (R) (Undefined) Decimal portion +16 +17 (Undefined) Integer portion +18 Sign (Undefined) Standard deviation (SD) 333 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0019 (fixed) +1 Program number (1digit BCD) 0 to 9 +2 to +3 Number of statistic data (6 digits BCD) 000000 to 999999 +4 Average value (decimal portion) (4 digits BCD) 0000 to 9999 +5 Average value (integer portion) (4 digits BCD) 000 to 999 +6 Average value (Sign) (BIN) If +: 0 If –: F +7 to +9 Maximum value Same as average value +10 to +12 Minimum value Same as average value +13 to +15 Range Same as average value +16 to +18 Standard deviation Same as average value Example –123.4567 +4 4567 +5 0123 +6 F000 Note The number of digits of the Decimal portion is fixed to 4 digits. If a deviation calculation results in a value with 5 decimal places, it will be stored with one digit overflowing into the integer portion. Examples: The value –0.1234 is stored as follows: Area of decimal portion: 1234; Area of integer portion: 0000; Sign area: F000 The value –0.12345 is stored as follows: Area of decimal portion: 2345; Area of integer portion: 0001; Sign area: F000 334 Appendix K 3Z4L Laser Micrometer Protocol Memory Switch Set 1 (3000-series, High-speed Type) (Sequence No. 421) This sequence sets memory switches. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words W X Y (Undefined) +2 Offset Z V Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 w (1 digits BCD) 0: For single run or zero run measurement start displaying ‘–––.’ 1: For single run or zero run measurement start displaying the previous measured value x (1 digit BCD) 0: Perform single run measurement to the RUN signal of I/O IF 1: Repeat measurement while the RUN signal of I/O IF is input y (1 digit BCD) *0: RS-232C Delimiter CR+LF 1: RS-232C Delimiter CR 2: RS-232C Delimiter LF z (1 digit BCD) 0: RS-232C no parity check 1: RS-232C odd parity check 2: RS-232C even parity check +2 v (1 digit BCD) 0: Displaying ‘Err-0’ 1: Displaying ‘0’ Note Settings marked with asterisks are required for this protocol. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 2. The setting (y, z) of RS-232C takes effect when the power supply is turned back on. 335 Appendix K 3Z4L Laser Micrometer Protocol Memory Switch Set 2 (3000-series, High-speed Type) (Sequence No. 422) This sequence sets memory switches. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words W X Y (Undefined) +2 Z V Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0003 (fixed) Data +1 w (1 digit BCD) 0: Work automatic detection is not performed 1: Work automatic detection is performed Diameter detection method (1 scan) 2: Work automatic detection is performed Diameter detection method (8 scan) 3: Work automatic detection is performed Position detection method (1 scan) +2 x (1 digit BCD) For expansion 0 (fixed) y (1 digit BCD) For expansion 0 (fixed) z (1 digit BCD) For expansion 0 (fixed) v (1 digit BCD) *0: Error data exclusion function is not used 1: Error data exclusion function is used Note Settings marked with asterisks are required for this protocol. Receive Data Word Allocation (3rd Operand of PMCR) None. Note Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. Simple AVG Times Set (3000-series, High-speed Type) (Sequence No. 423) This sequence uses the simple average as the averaging method and sets the averaging times per measurement interval 4. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of averaging times Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Number of averaging times (4 digits BCD) 1 to 2048 Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 336 Appendix K 3Z4L Laser Micrometer Protocol AVG Move Interval Set (3000-series, High-speed Type) (Sequence No. 424) This sequence uses the average move as the averaging method and sets the measurement interval number. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Measurement interval number Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Measurement interval number (1 digit BCD) 1 to 4 Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. AVG Move (H) Times Set (3000-series, High-speed Type) (Sequence No. 425) This sequence uses the average move and high-speed data output as the averaging method and sets the averaging times per measurement interval 4. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of averaging times Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Number of averaging times (4 digits BCD) 16 to 2048 Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. AVG Move (L) Times Set (3000-series, High-speed Type) (Sequence No. 426) This sequence uses the average move and low-speed data output as the averaging method and sets the averaging times per measurement interval 4. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of averaging times Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Number of averaging times (4 digits BCD) 32 to 2048 Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 337 Appendix K 3Z4L Laser Micrometer Protocol Automatic Detection Set (3000-series, High-speed Type) (Sequence No. 427) This sequence sets the work automatic detection function. Send Data Word Allocation (2nd Operand of PMCR) Receive data storage words +0 +1 Number of send data words (Undefined) The number of measuring times Invalid time +2 Decimal portion +3 (Undefined) +4 Integer portion Sign +5 Detection lower limit (Undefined) Decimal portion +6 (Undefined) +7 Integer portion Sign +8 Detection upper limit (Undefined) Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0009 (fixed) +1 Number of measurements (3 digits BCD) 001 to 999 +2 Invalid time (4 digits BCD) 0001 to 9999 +3 Detection lower limit (decimal portion) (4 digits BCD) Detection lower limit (integer portion) (3 digits BCD) 0000 to 9999 +5 Detection lower limit (Sign) (ASCII 1 character) If +: 20 (‘ ’) If – : 2D (‘–’) +6 to +8 Detection upper limit Same as detection lower limit +4 Data Example –123.4567 +3 000 to 999 4567 +4 0123 +5 2D00 Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. Automatic Detection Release (3000-series, High-speed Type) (Sequence No. 428) This sequence releases the setting of work automatic detection function. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. Automatic Detection List Request (3000-series, High-speed Type) (Sequence No. 429) This sequence requests the settings of work automatic detection function. Send Data Word Allocation (2nd Operand of PMCR) None. 338 Appendix K 3Z4L Laser Micrometer Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 +1 Number of receive data words (Undefined) The number of measuring times +2 Invalid time +3 Decimal portion +4 (Undefined) +5 Sign Integer portion Detection lower limit (Undefined) Decimal portion +6 +7 (Undefined) Integer portion +8 Sign (Undefined) Detection upper limit Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0009 (fixed) +1 The number of measuring times (3 digits BCD) 000 to 999 +2 Invalid time (4 digits BCD) 0001 to 9999 +3 Detection lower limit (decimal portion) (4 digits BCD) Detection lower limit (integer portion) (3 digits BCD) 0000 to 9999 +5 Detection lower limit (Sign) (BIN) If +: 0 If –: F +6 to +8 Detection upper limit Same as detection lower limit +4 Data Example –123.4567 +3 000 to 999 4567 +4 0123 +5 F000 Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 3Z4L Initialize (3000-series) (Sequence No. 430) This sequence clears the 3Z4L, sets the mm unit, sets memory switches, does not process statistics, and clears the statistic memory. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting) Receive Data Word Allocation (3rd Operand of PMCR) None. 339 Appendix K 3Z4L Laser Micrometer Protocol Measurement Condition Set (4000-series) (Sequence No. 431) This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Segment number (SG) +2 (Undefined) Measurement interval number (M) Decimal portion +3 +4 (Undefined) +5 Sign +7 (Undefined) +8 Sign +10 (Undefined) +11 Sign Integer portion Integer portion Reference value (REF) (Undefined) (Undefined) (Unused) +14 (Unused) +15 (Unused) +18 Upper limit value (LH) (Undefined) +13 +17 340 (Undefined) Decimal portion +9 +16 Lower limit value (LL) Decimal portion +6 +12 Integer portion (Undefined) Analog output scale number (SCL) Data output conditions (PR) (Undefined) Data output timer (BCD 3 digits) (PRT) (Undefined) Number of seconds for latch timer (RLT) +19 0 +20 0 +21 0 +22 0 +23 0 +24 0 Setting Yes/No flags Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0025 (fixed) Data +1 Segment number (1 digit BCD) 1 to 5 +2 Measurement interval number (1 digit BCD) 1 to 7 +3 Lower limit value (Decimal portion) (4 digits BCD) 0000 to 9999 +4 Lower limit value (integer portion) (3 digits BCD) 000 to 999 Example –123.4567 +3 +5 Lower limit value (Sign) (ASCII 1 character) If +: 20 (‘ ’) If – : 2D (‘–’) +6 to +8 Upper limit value Same as lower limit value +9 to +11 Reference value Same as lower limit value +12 Analog output scale number (1 digit BCD) 0 to 3 +13 to +15 Unused +16 Data output conditions (1 digit BCD) 0 to 6 +17 Data output timer value (3 digits BCD) 000 to 999 +18 Number of seconds for latch timer (2 digits BCD) 00 to 99 +19 Yes/No for segment setting (1 digit BCD) Set: 1(SG) Don’t set: 0 +20 Yes/No for measurement interval number setting (1 digit BCD) Set: 1(M) Don’t set: 0 +21 Yes/No for upper/lower limit value setting (1 digit BCD) Set: 1(LL, LH) Don’t set: 0 +22 Yes/No for reference setting (1 digit BCD) Set: 1(REF, SCL) Don’t set: 0 +23 Yes/No for data output condition setting (1 digit BCD) Set: 1(PR, PRT) Don’t set: 0 +24 Yes/No for latch timer setting (1 digit BCD) Set: 1(RLT) Don’t set: 0 4567 +4 0123 +5 2D00 Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. The following settings must be made together with this sequence; they cannot be set separately. Lower limit, upper limit Reference value, data output timer Data output conditions, scheduled print timer 2. The limit value and reference value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion. 341 Appendix K 3Z4L Laser Micrometer Protocol Measurement Condition Release (4000-series) (Sequence No. 432) This sequence clears the measurement conditions that have been set. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of sequence No. 431 (Measurement Condition Setting). However, only the setting Yes/No flags at +19 to +24 from the send data leading word can be used. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. The following conditions are used when the measurement conditions are released: Segment becomes 1 and the measurement interval becomes 1. 2. The following settings cannot be cleared separately using this sequence. They all must be cleared at the same time. Lower limit, Upper limit Data output conditions, Scheduled print timer The scale (SCL) and data output timer (PRT) cannot be cleared. 3. This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. Measurement Condition List Request (4000-series) (Sequence No. 433) This sequence requests the measurement condition settings that have been set and other settings. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Segment number (SG) +2 (Undefined) Measurement interval number (M) Decimal portion +3 +4 (Undefined) Integer portion +5 Sign (Undefined) Decimal portion +6 +7 (Undefined) +8 Sign Integer portion Upper limit value (LH) (Undefined) Decimal portion +9 +10 (Undefined) Integer portion +11 Sign (Undefined) +12 Lower limit value (LL) (Undefined) Reference value (REF) Analog output scale number (SCL) +13 Forced zero number (ZERO+) +14 (Undefined) +15 +16 +17 +18 342 (Undefined) (Undefined) Data output condition (PR) Data output timer (BCD 3 digits) (PRT) (Undefined) Number of seconds for latch timer (RLT) Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0019 (fixed) +1 Segment number (1 digit BCD) 1 to 5 +2 Measurement interval number (1 digit BCD) 1 to 7 +3 Lower limit value (Decimal portion) (4 digits BCD) Lower limit value (Integer portion) (3 digits BCD) 0000 to 9999 +5 Lower limit value (Sign) (BIN) If +: 0 If –: F +6 to +8 Upper limit value Same as lower limit value +9 to +11 Reference value Same as lower limit value +12 Analog output scale number (1 digit BCD) 0 to 3 +13 to +15 Forced zero number (ASCII 5 characters) 5A45524F2B (“ZERO+”) 4E4F524D20 (“NORM ”) 5A45524F2D (“ZERO–”) +16 Data output condition (1 digit BCD) 0 to 6 +17 Data output timer value (3 digits BCD) 000 to 999 +18 Number of seconds for latch timer (2 digits BCD) 00 to 99 +4 Data Example –123.4567 +3 000 to 999 4567 +4 0123 +5 F000 Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. Single Run Measurement Start (4000-series) (Sequence No. 434) When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Decision result +2 Decimal portion +3 (Undefined) +4 Sign Integer portion Measurement value (Undefined) Decimal portion +5 +6 (Undefined) Integer portion +7 Sign (Undefined) Deviation value 343 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) With no reference setting: 0005 +1 Decision result (ASCII 2 characters) With no limit setting: 0000 With reference setting: 0008 With limit setting: 2B4E (“+N”), 4F4B (“OK”), 2D4E (“–N”) Measurement value (decimal portion) (4 digits BCD) Measurement value (integer portion) (3 digits BCD) 0000 to 9999 Example –123.4567 000 to 999 +3 0123 +4 F000 +4 Measurement value (Sign) (BIN) If +: 0 +5 to +7 Deviation value Same as measurement value +2 +3 +2 4567 If –: F *The deviation will be stored in this area only when reference setting is made. Deflection Measurement Start (4000-series) (Sequence No. 435) This sequence starts a deflection measurement. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Note The deflection measurement keeps measuring until sequence No. 438 (Measurement Termination) is executed. Continuous Measurement Start (Scan) (4000-series) (Sequence No. 436) This sequence starts a continuous measurement. The scan notification method is used for the receive data. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 438 (Measurement Termination) to end the sequence. Continuous Measurement Start (Interrupt) (4000-series) (Sequence No. 437) This sequence starts a continuous measurement. The interrupt notification method is used for the receive data and the interrupt No. is 101. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 438 (Measurement Termination) to end the sequence. 344 3Z4L Laser Micrometer Protocol Appendix K Continuous Measurement Termination (4000-series) (Sequence No. 438) This sequence terminates continuous measurement. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) For continuous measurement: None. For Deflection Measurement The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Data Request (4000-series) (Sequence No. 439) This sequence requests display data in the idle measurement status or latch data generated by the measurement command. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Forced Positive Zero (4000-series) (Sequence No. 440) This sequence sets the forced zero direction to positive (+) Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Forced Negative Zero (4000-series) (Sequence No. 441) This sequence sets the forced zero direction to negative (–) Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Forced Zero Release (4000-series) (Sequence No. 442) This sequence releases the forced zero direction. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. 3Z4L Initialize (4000-series) (Sequence No. 443) This sequence clears the 3Z4L, sets the mm unit, and sets memory switches. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting). Receive Data Word Allocation (3rd Operand of PMCR) None. 345 Appendix K 3Z4L Laser Micrometer Protocol General-purpose Command 1 (4000-series) (Sequence No. 444) This general-purpose command is used to send data with a specified data length, and receive back only OK. The terminator (CR) is automatically attached to the send data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data Send data +128 +129 Offset Send data Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0129 +1 Send data byte length (4 digits BCD) 0001 to 0255 The number of bytes of send data excluding the terminator (CR) +2 to +129 Send data (ASCII) Send data up to 255 bytes maximum Receive Data Word Allocation (3rd Operand of PMCR) None. 346 CR Specify in ASCII. Appendix K 3Z4L Laser Micrometer Protocol General-purpose Command 2 (4000-series) (Sequence No. 445) This general-purpose command is used to send data with a specified data length, and receive back receive data other than OK. The terminator (CR) is automatically attached to the send data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data Send data +128 +129 Offset Send data CR Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0129 +1 Send data byte length (4 digits BCD) 0001 to 0255 The number of bytes of send data excluding the terminator (CR) +2 to +129 Send data (ASCII) Send data up to 255 bytes maximum Specify in ASCII. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Receive data +2 Receive data +126 Receive data +127 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0001 to 0128 +1 to +127 Receive data (ASCII) When the receive data exceed 254 bytes, only 254 bytes are stored. 347 Appendix L Visual Inspection System Protocol The Visual Inspection System Protocol is used to make various settings or control remotely the Visual Recognition Device connected to the Serial Communications Board via RS-232C cable. Protocol Configuration The configuration of the Visual Inspection System Protocol is shown below. Sequence No. Communications sequence name Function Ladder interface Send word allocation No Receive word allocation Yes 450 Measurement execution (F200) Carries out one measurement one and stores the measurement results in the specified words. 451 Continuous measurement execution (scan) (F200) Carries out continuously setting the F200 and storing the measurement results in the specified words. No Yes 452 Continuous measurement execution (interrupt) (F200) Carries out continuously setting the F200 and storing the measurement results in the specified words. No Yes 453 Reference object registration (group) (F200) Performs reference position registration and evaluation criterion registration at the same time. No No 454 Reference object registration (reference position) (F200) No No 455 Reference object registration (evaluation criterion) (F200) Registers the reference position for measuring the amount of position displacement when a position displacement compensation is used. Registers the reference value to discriminate the output format. No No 456 Evaluation condition change (F200) Changes the upper and lower limit values of the evaluation condition of the designated output No. Yes No 457 Arbitrary measurement value acquisition (F200) Stores the measurement values of arbitrary measurement item regardless of output format in the specified words. Yes Yes 460 Measurement execution (F300) Carries out one measurement and stores the measurement results in the specified words. No Yes 461 Continuous measurement execution (scan) (F300) Carries out continuously setting the F300 and storing the measurement results in the specified words. No Yes 462 Continuous measurement execution (interrupt) (F300) Carries out continuously setting the F300 and storing the measurement results in the specified words. No Yes 463 Reference object registration command 1 execution (F300) Performs a measurement for the input image and updates the reference object data of the full window. No No 464 Reference object registration command 2 execution (F300) Performs a measurement for the input image and updates the reference object data of the full window Yes No 465 Illumination fluctuation follow execution (F300) Measurement execution and positioning (F350) Executes an illumination fluctuation follow. No No Carries out one measurement and stores the measurement results in the specified words. No Yes 470 349 Appendix L Visual Inspection System Protocol Sequence No. Communications sequence name Function Camera designation and positioning (F350) Scene switching and positioning (F350) Inspection execution and character inspection (F350) Designates the camera for measurement. 474 480 471 472 Ladder interface Send word Receive word allocation allocation Yes No Switches to a designated scene No. Yes No Carries out one inspection and outputs inspection results to the video monitor. No No Character string inspection and character inspection (F350) Changes the inspection character string of a designated inspection area No. to a designated character string. Yes No Camera change (decrease by 1) (F200/300) Camera change (increase by 1) (F200/300) Binary level modification (F200/300) Decreases the display camera No. by 1. No No Increases the display camera No. by 1. No No Modifies the binary levels (upper limit and lower limit values) of a designated window number No. Yes No 483 Reset (F200/300) Resets the F200/F300. No No 490 Scene switch (decrease by 1) Scene switch (increase by 1) Scene switch (arbitrary) Decreases the scene No. by 1. No No Increases the scene No. by 1. No No Switches to a designated scene No. Yes No Measurement, inspection termination General-purpose command (send) General-purpose command (send/receive) Terminates the measurement and returns to the home menu. Sets and executes commands that are otherwise not supported. Sets and executes commands that are otherwise not supported. No No Yes No Yes Yes 473 481 482 491 492 493 494 495 Note Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). 350 Appendix L Visual Inspection System Protocol Connections The connections for using the Visual Inspection System Protocol are shown below. RS-232C Connections CQM1H F200/300/350 Serial Communications Board RS-232C port → RS-232C Unit Pin No. Signal name Abbreviation 1 Protective ground or earth FG (GND) 2 Send data SD (TXD) 3 Receive data RD (RXD) 4 Request to send RS (RTS) 5 Clear to send CS (CTS) 6 Data set ready DR (DSR) 7 Signal ground SG (GND) 8 Carrier detection (Data word receive) CD (DCD) 20 Data terminal ready ER (DTR) Serial Communications Board: D-sub 9 pin (female) Signal Name Pin No. F300-E: D-sub 25 pin (female) Pin No. Signal Name • For RS/CS Flow Control Serial Communications Board: D-sub 9 pin (female) Signal Name Pin No. F300-E: D-sub 25 pin (female) Pin No. Signal Name 351 Appendix L Visual Inspection System Protocol Measurement Execution (F200) (Sequence No. 450) This sequence carries out one measurement and stores the measurement results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Evaluation result Decimal portion +3 Integer portion +4 +5 Output No. (Undefined) +2 Sign Measurement value 0 Offset Content (data format) Data +0 Number of receive data words (4 digits BCD) 0006 +1 Output No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 Measurement value (integer portion) (7 digits BCD) +3 +3 3456 +4 0012 +4 0012 Measurement value (sign) (1 digit) +5 F000 +5 0000 3456 F is stored for negative values. Note 1. Only one output No. can be stored. 2. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 3. If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words. Continuous Measurement Execution (Scan) (F200) (Sequence No. 451) This sequence carries out continuously the setting of the F200 and stores measurement results in the specified words. The scan notification method is used for the receive data. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) +2 Integer portion +4 352 Evaluation result Decimal portion +3 +5 Output No. (Undefined) Sign 0 Measurement value Appendix L Visual Inspection System Protocol Offset Content (data format) Data +0 Number of receive data words (4 digits BCD) 0006 +1 Output No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. Note 1. Only one output No. can be designated. 2. Turn OFF CIO 28911 (if port A is used) or CIO 28915 (if port B is used) to terminate this sequence. 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 4. If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words. Continuous Measurement Execution (Interrupt) (F200) (Sequence No. 452) This sequence carries out continuously setting the F200 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) +2 Evaluation result Decimal portion +3 Integer portion +4 +5 Output No. (Undefined) Sign Offset Measurement value 0 Content (data format) Data +0 Number of receive data words (4 digits BCD) 0006 +1 Output No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. Note 1. Only one output No. can be designated. 2. Turn OFF CIO 28911 (if port A is used) or CIO 28915 (if port B is used) to terminate this sequence. 353 Appendix L Visual Inspection System Protocol 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 4. If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words. Reference Object Registration (Group) (F200) (Sequence No. 453) This sequence performs reference position registration and criterion registration at the same time. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Reference Object Registration (Reference Position) (F200) (Sequence No. 454) This sequence registers the reference position for measuring the amount of position displacement when a position displacement compensation is used. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Reference Object Registration (Criterion) (F200) (Sequence No. 455) This sequence registers a reference value to discriminate the output format. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Evaluation Condition Change (F200) (Sequence No. 456) This sequence changes the upper and lower limit values of evaluation condition of the designated output No. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 +2 Number of send data words (Undefined) (Undefined) +3 +4 +5 +6 (Undefined) Sign (Undefined) +7 +8 +9 354 (Undefined) Sign Output No. Decimal portion Integer portion Upper limit value (Undefined) Decimal portion Integer portion (Undefined) Lower limit value Appendix L Visual Inspection System Protocol Offset Content (data format) Data +0 Number of send data words (4 digits BCD) 0010 +1 Output No. (2 digits BCD) 00 to 07 +2 to +5 Upper limit value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 +2 0567 +2 0678 +3 Upper limit value (integer portion) (7 digits BCD) Upper limit value (sign) (ASCII 2 digits) +6 to +9 Lower limit value (decimal portion) (3 digits BCD) 1234 +3 2345 +4 0000 +4 0001 +5 2D00 +5 3000 Same as upper limit. Lower limit value (integer portion) (7 digits BCD) Lower limit value (sign) (ASCII 2 digits) Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Only one output No. can be designated. 2. Enter values so that upper limit ≥ lower limit. 3. Enter upper limit and lower limit values within the range –2147483.648 to 2147483.648. Arbitrary Measurement Value Acquisition (F200) (Sequence No. 457) This sequence stores measurement values of arbitrary measurement items regardless of output format in the specified words. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) Data 1 +2 (Undefined) Data 2 Offset Content (data format) Data +0 Number of send data words (4 digits BCD) 0003 +1 Data 1 (2 digits BCD) 00: Area 01: Center of gravity x 02: Center of gravity y 03: Main axis angle 04: Output format 05: Reference value of output format 06: X displacement 07: Y displacement 08: Angle displacement 09: X reference position 10: Y reference position 11: Angle reference position +2 Data 2 (2 digits BCD) When 00 to 03 is set to data 1 Window No.: 00 to 07 When 04 to 05 is set to data 1 Output No.: 00 to 07 When 06 to 11 is set to data 1 Camera No.: 00 to 01 355 Appendix L Visual Inspection System Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 +1 Number of receive data words (Undefined) +2 +3 Decimal portion Integer portion Sign Measurement value 0 Offset Content (data format) Data +0 Number of receive data words (4 digits BCD) 0004 +1 to +3 Measurement value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) F is stored for negative values. Note 1. Only one output No. can be designated. 2. Measurement is not performed with this command. The measurement results of the last measurement will be stored in the specified words. 3. This command can acquire only the measurement value of the window No. set by output format. 4. For data 1 and 2 , the receive data is compared with the send data. If the receive data is not the same as the send data, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON. 5. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 6. If a measurement value exceeds the range of measurement values when calibration is turned off, unexpected data is stored in the specified words. Measurement Execution (F300) (Sequence No. 460) This sequence carries out one measurement and stores measurement results in the specified words Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data stor-+0 age words +1 Number of receive data words (Undefined) Window No. Decimal portion +3 Integer portion +4 +5 Sign Decimal portion Integer portion +7 Sign Decimal portion Integer portion +10 Sign Decimal portion Integer portion +13 Sign Decimal portion Integer portion +16 356 Data 4 0 +15 +17 Data 3 0 +12 +14 Data 2 0 +9 +11 Data 1 0 +6 +8 Evaluation result (Undefined) +2 Sign 0 Data 5 Appendix L Visual Inspection System Protocol Offset +0 Content (data format) Number of receive data words (4 digits BCD) Data 0006: 1 measurement item 0009: 2 measurement items 0012: 3 measurement items 0015: 4 measurement items 0018: 5 measurement items +1 Window number (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. +6 to +8 Same as +3 to +5. Same as +3 to +5. +9 to +11 Same as +3 to +5. Same as +3 to +5. +12 to +14 Same as +3 to +5. Same as +3 to +5. +15 to +17 Same as +3 to +5. Same as +3 to +5. Note 1. Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9. 2. The number of measurement items is up to 5, but only one window number can be read. 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.648 For calibration ON setting : –9999999.999 to 9999999.999 4. The priority of measurement items being output are as follows: Area Center of gravity X, Center of gravity Y Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved) Main axis angle Main axis angle aberration (reserved) Edge angle Edge angle (reserved) Center X, center Y Center X aberration (reserved), center Y aberration (reserved) Inclination Inclination aberration (reserved) Intersecting point X, intersecting point Y Intersecting point X aberration (reserved), intersecting point Y aberration (reserved) Continuous Measurement Execution (Scan) (F300) (Sequence No. 461) This sequence carries out continuously the settings of F300 and stores measurement results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) None. 357 Appendix L Visual Inspection System Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Integer portion +4 Sign Decimal portion Integer portion +7 Sign Decimal portion Integer portion +10 Sign Decimal portion Integer portion +13 Sign Data 4 0 Decimal portion +15 Integer portion +16 +17 Data 3 0 +12 +14 Data 2 0 +9 +11 Data 1 0 +6 +8 Evaluation result Decimal portion +3 +5 Window No. (Undefined) +2 Sign Offset +0 Data 5 0 Content (data format) Number of receive data words (4 digits BCD) Data 0006: 1 measurement item 0009: 2 measurement items 0012: 3 measurement items 0015: 4 measurement items 0018: 5 measurement items +1 Window No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 +3 Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. +6 to +8 Same as +3 to +5. Same as +3 to +5. +9 to +11 Same as +3 to +5. Same as +3 to +5. +12 to +14 Same as +3 to +5. Same as +3 to +5. +15 to +17 Same as +3 to +5. Same as +3 to +5. Note 1. Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9. 2. The number of measurement items are up to 5, but only one window number can be read. 3. The range of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.648 For calibration ON setting : –9999999.999 to 9999999.999 4. The priority order of measurement items being output are as follows: Area Center of gravity X, Center of gravity Y Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved) Main axis angle 358 Appendix L Visual Inspection System Protocol Main axis angle aberration (reserved) Edge angle Edge angle (reserved) Center X, center Y Center X displacement (reserved), center Y displacement (reserved) Inclination Inclination displacement (reserved) Intersecting point X, intersecting point Y Intersecting point X displacement (reserved), intersecting point Y displacement (reserved) Continuous Measurement Execution (Interrupt) (F300) (Sequence No. 462) This sequence carries out continuously setting the F300 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Integer portion +4 Sign Decimal portion Integer portion +7 Sign Decimal portion Integer portion +10 Sign Decimal portion Integer portion +13 Sign Data 4 0 Decimal portion +15 Integer portion +16 +17 Data 3 0 +12 +14 Data 2 0 +9 +11 Data 1 0 +6 +8 Evaluation result Decimal portion +3 +5 Window No. (Undefined) +2 Sign Data 5 0 359 Appendix L Visual Inspection System Protocol Offset +0 Content (data format) Number of receive data words (4 digits BCD) Data 0006: 1 measurement item 0009: 2 measurement items 0012: 3 measurement items 0015: 4 measurement items 0018: 5 measurement items +1 Window No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 Measurement value (integer portion) (7 digits BCD) +3 3456 +3 3456 +4 0012 +4 0012 Measurement value (sign) (1 digit) +5 F000 +5 0000 +6 to +8 Same as +3 to +5. Same as +3 to +5. +9 to +11 Same as +3 to +5. Same as +3 to +5. +12 to +14 Same as +3 to +5. Same as +3 to +5. +15 to +17 Same as +3 to +5. Same as +3 to +5. F is stored for negative values. Note 1. Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9. 2. The number of measurement items is up to 5, but only one window number can be read. 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.648 For calibration ON setting : –9999999.999 to 9999999.999 4. The priority of measurement items being output are as follows: Area Center of gravity X, Center of gravity Y Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved) Main axis angle Main axis angle displacement (reserved) Edge angle Edge angle(reserved) Center X, center Y Center X displacement (reserved), center Y displacement (reserved) Inclination Inclination displacement (reserved) Intersecting point X, intersecting point Y Intersecting point X displacement (reserved), intersecting point Y displacement (reserved) Reference Object Registration Command 1 Execution (F300) (Sequence No. 463) This sequence performs a measurement for the input image and updates reference object data of the full window. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. 360 Appendix L Visual Inspection System Protocol Reference Object Registration Command 2 Execution (F300) (Sequence No. 464) This sequence performs a measurement for the input image and updates the reference object data of a designated window. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Window No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Window No. (2 digits BCD) 00 to 07 Receive Data Word Allocation (3rd Operand of PMCR) None. Illumination Fluctuation Follow Execution (F300) (Sequence No. 465) This sequence executes an illumination fluctuation follow. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Measurement Execution and Positioning (F350) (Sequence No. 470) This sequence carries out one measurement and stores the measurement results in the specified words. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words Decimal portion +1 +2 Sign Integer portion Decimal portion +3 +4 Integer portion Sign Y displacement Decimal portion +5 +6 X displacement Sign 0 Integer portion Correlation value 361 Appendix L Visual Inspection System Protocol Offset Content (data format) Data +0 Number of receive data words +1 to +2 X displacement (decimal portion) (3 digits BCD) 0007 Example –123.456 X displacement (integer portion) (3 digits BCD) +1 3456 +1 3456 +2 F012 +2 0012 X displacement (sign) (1 digit) (See note.) +3 to +4 F is stored for negative values. Y displacement (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 Y displacement (integer portion) (3 digits BCD) +1 3456 +1 3456 +2 F012 +2 0012 Y displacement (sign) (1 digit) (See note.) +5 to +6 Example +123.456 F is stored for negative values. Correlation value (decimal portion) (3 digits BCD) Example –12.345 Example +12.345 Correlation value (integer portion) (3 digits BCD) +1 2345 +1 2345 +2 F001 +2 0001 Correlation value (sign) (1 digit) (See note.) F is stored for negative values. Note 1. The number of models that can be stored in a designated word is 1. 2. If a measurement is carried out without executing a camera designation, a measurement is executed for all cameras in which the measurement model is registered. 3. When the correlation value is less than 70 and the measurement value overflows, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON. 4. Data to be output is within the range 999.999 (upper limit) to –999.999 (lower limit). 5. Retry processing is not performed for this sequence. 6. Turn the Abort Bit ON and then OFF to end this sequence. Camera Designation and Positioning (F350) (Sequence No. 471) This sequence designates the cameras for measurement. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 (Undefined) +2 (Undefined) Offset First camera No. Last camera No. Content (data format) Data +0 Number of send data words (4 digit BCD) 0003 +1 First camera No. (1 digit BCD) 0 to 7 +2 Last camera No. (1 digit BCD) 0 to 7 Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Set values so that the first camera No.< last camera No. 2. If a designated camera No. is abnormal, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON. Scene Switching and Positioning (F350) (Sequence No. 472) This sequence switches to a designated scene No. Send Data Word Allocation (2nd Operand of PMCR) First word of send data 362 +0 +1 Number of send data words (Undefined) Scene No. Appendix L Visual Inspection System Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Scene No. (2 digits BCD) 00 to 15 Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. If a scene No. is abnormal, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON. 2. Retry processing is not performed for this sequence. 3. Turn the Abort Bit ON and then OFF to end this sequence. Inspection Execution and Character Inspection (F350) (Sequence No. 473) This sequence carries out one inspection and outputs the inspection results to a video monitor. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Character String Inspection and Character Inspection (F350) (Sequence No. 474) This sequence changes the inspection character string of a designated inspection area No. to a designated character string. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Inspection area No. (Undefined) +2 Number of designated character strings Designated character string +3 ~ ~ Designated character string Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 to 0015 +1 Number of designated character strings (4 digits BCD) 0 to 24 +2 Inspection area No. (2 digits BCD) 00 to 07 +3 to Number of designated character strings (ASCII) Receive Data Word Allocation (3rd Operand of PMCR) None. Camera Change (Decrease by 1) (F200/300) (Sequence No. 480) This sequence decreases the display camera No. by 1. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. 363 Appendix L Visual Inspection System Protocol Camera Change (Increase by 1) (F200/300) (Sequence No. 481) This sequence increases the display camera No. by 1. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Binary Level Modification (F200/300) (Sequence No. 482) This sequence modifies the binary levels (upper limit and lower limit values) of a designated output No. (F200) or window number No. (F300). Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Window No. +2 (Undefined) Upper limit value +3 (Undefined) Lower limit value Offset or Output No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 +1 Window No. (1 digit BCD) 0 to 7 +2 Upper limit value (3 digits BCD) 000 to 255 +3 Lower limit value (3 digits BCD) 000 to 255 Receive Data Word Allocation (3rd Operand of PMCR) None. Note Enter values so that the upper limit ≥ lower limit. Reset (F200/300) (Sequence No. 483) This sequence resets the F200/F300 (to starting status). Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Scene Switching (Decrease by 1) (Sequence No. 490) This sequence decreases the scene No. by 1. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. Scene Switching (Increase by 1) (Sequence No. 491) This sequence increases the scene No. by 1. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. 364 Appendix L Visual Inspection System Protocol Scene Switching (Arbitrary) (Sequence No. 492) This sequence switches to a designated scene No. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words (Undefined) +1 Offset Scene No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Scene No. (2 digits BCD) 00 to 15 Receive Data Word Allocation (3rd Operand of PMCR) None. Measurement, Inspection Termination (Sequence No. 493) This sequence terminates the measurement and returns to the home menu. Send Data Word Allocation (2nd Operand of PMCR) None. Receive Data Word Allocation (3rd Operand of PMCR) None. General-purpose Command (Send) (Sequence No. 494) This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Command length (Undefined) +2 Command ~ ~ Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 003 to 0129 +1 Command length (4 digits BCD) 0001 to 0253 +2 to Command (ASCII) Specify ASCII data. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. The processing depends on the command. 2. For a command with a response, use sequence #495. General-purpose Command (Send/Receive) (Sequence No. 495) This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 +1 +2 ~ Number of send data words Command length (Undefined) Command ~ 365 Appendix L Visual Inspection System Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0129 +1 Command length (4 digits BCD) 0001 to 0253 +2 to Command (ASCII) Specify ASCII data. Receive Data Word Allocation (3rd Operand of PMCR) The reception data is stored in the reception data words without the delimiter (CR+LF), Receive data storage words +0 Number of receive data words Command length +1 (Undefined) +2 Command ~ Offset ~ Contents (data format) +0 Number of receive data words (4 digits BCD) +1 Command length (4 digits BCD) +2 to Command (ASCII) Note 1. The processing depends on the command. 2. For a command with a response, use sequence #495. 366 Data ASCII data is returned. Appendix M V600/V620 ID Controller Protocol The V600/V620 ID Controller Protocol is used to make various settings or control remotely the ID Controller Connected to the Serial Communications Board via RS-232C or RS-422A cable. Protocol Configuration The configuration of the V600/V620 ID Controller Protocol is shown below. Sequence No. Communications sequence name 500 Read (ASCII/1) 501 Read (ASCII/2) 502 Read (ASCII/4) 503 Read (ASCII/8) 504 Read (Hexadecimal/1) Read (Hexadecimal/2) Read (Hexadecimal/4) Read (Hexadecimal/8) Auto-read (ASCII/1) 505 506 507 508 509 510 511 Auto-read (Hexadecimal/1) Polling Auto-read (ASCII) Polling Auto-read Subcommand (ASCII/2) Function Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is 2. Used when the maximum number of Heads to be read from the Carrier is 4. Used when the maximum number of Heads to be read from the Carrier is 8. Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is 2. Used when the maximum number of Heads to be read from the Carrier is 4. Used when the maximum number of Heads to be read from the Carrier is 8. Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is from 1 to 8. Used when the number of Heads to be read from the Carrier is 2. Ladder interface Send word allocation Yes Receive word allocation Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes 512 Polling Auto-read Subcommand (ASCII/4) Used when the maximum number of Heads to be read from the Carrier is 4. Yes Yes 513 Polling Auto-read Subcommand (ASCII/8) Used when the maximum number of Heads to be read from the Carrier is 8. Yes Yes 514 Polling Auto-read (Hexadecimal) Polling Auto-read Subcommand (Hexadecimal/2) Used when the number of Heads to be read from the Carrier is from 1 to 8. Used when the number of Heads to be read from the Carrier is 2. Yes No Yes Yes 515 516 Polling Auto-read Used when the maximum number of Heads to Subcommand (Hexa- be read from the Carrier is 4. decimal/4) Yes Yes 517 Polling Auto-read Used when the maximum number of Heads to Subcommand (Hexa- be read from the Carrier is 8. decimal/8) Yes Yes 518 Write (ASCII/1) Yes No Used when the number of Heads to be written to the Carrier is 1. 367 Appendix M V600/V620 ID Controller Protocol Sequence No. Communications sequence name 519 Write (ASCII/2) 520 Write (ASCII/4) 521 Write (ASCII/8) 522 Write (Hexadecimal/1) Write (Hexadecimal/2) Write (Hexadecimal/4) Write (Hexadecimal/8) Auto-write (ASCII/1) 523 524 525 526 527 528 529 530 Auto-write (Hexadecimal/1) Polling Auto-write (ASCII/2) Polling Auto-write Subcommand (ASCII/2) Function Used when the number of Heads to be written to the Carrier is 2. Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 8. Used when the number of Heads to be written to the Carrier is 1. Used when the number of Heads to be written to the Carrier is 2. Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 8. Used when the number of Heads to be written to the Carrier is 1. Used when the number of Heads to be written to the Carrier is 1. Used when the number of Heads to be written to the Carrier is 2. Used when the number of Heads to be written to the Carrier is 2. Ladder interface Send word Receive word allocation allocation Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Polling Auto-write (ASCII/4) Polling Auto-write Subcommand (ASCII/4) Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 4. Yes No Yes No Polling Auto-write (ASCII/8) Polling Auto-write Subcommand (ASCII/8) Used when the maximum number of Heads to be written to the Carrier is 8. Used when the maximum number of Heads to be written to the Carrier is 8. Yes No Yes No Polling Auto-write (Hexadecimal/2) Polling Auto-write Subcommand (Hexadecimal/2) Used when the number of Heads to be written to the Carrier is 2. Used when the number of Heads to be written to the Carrier is 2. Yes No Yes No Polling Auto-write (Hexadecimal/4) Polling Auto-write Subcommand (Hexadecimal/4) Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 4. Yes No Yes No Used when the maximum number of Heads to be written to the Carrier is 8. Used when the maximum number of Heads to be written to the Carrier is 8. Yes No 539 Polling Auto-write (Hexadecimal/8) Polling Auto-write Subcommand (Hexadecimal/8) Yes No 540 Data check Yes Yes 541 Control management Writes and verify the CRC code for the check blocks designated by the user. Performs I/O or an I/O read. Yes Yes 542 Error information read Command processing cancel Reads information from the latest error log. Yes Yes Cancels command processing except polling command processing and returns to the command waiting status. Yes Yes 531 532 533 534 535 536 537 538 543 368 Appendix M V600/V620 ID Controller Protocol Sequence No. Communications sequence name Function Ladder interface Send word Receive word allocation allocation Yes Yes 544 Polling auto-read command processing cancel Cancels polling auto-read processing. 545 Polling auto-write command processing cancel Cancels polling auto-write processing. Yes Yes 546 General-purpose command Sends arbitrary data and stores receive data to receive data words. Yes Yes Note Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). Connections Connections when using the V600/V620 ID Controller Protocol are shown below. RS-232C Connections CQM1H Head Serial Communications Board RS-232C port Data Carrier ID Controller Serial Communications Board: D-sub 9 pin (female) Signal name ID Controller (CD1D): D-sub 9 pin (female) Pin No. Pin No. Signal name Shielded cable Serial Communications Board: D-sub 9 pin (female) ID Controller (CA1A): D-sub 25 pin (female) Shielded cable 369 Appendix M V600/V620 ID Controller Protocol RS-422A Connections CQM1H Serial Communications Board RS-422A port Head Data Carrier Head Data Carrier ID Controller ID Controller Up to 16 units can be connected Serial Communications Board: D-sub 9 pin (female) Signal name ID Controller (CD1D): D-sub 9 pin (female) Signal Pin No. name Pin No. Shielded cable Note 1. Ground the cable shield at either the ID Controller or the Serial Communications Board to prevent malfunction. 2. Turn ON the pin 6 on DIP switch SW6 to set the host communications procedure to the 1-to-N procedure for 1-to-N connections. 370 Appendix M V600/V620 ID Controller Protocol DIP Switch Settings V600/620-CD1D DIP Switches DIP Switch 1 1 2 3 4 5 6 7 8 Not used (Always keep it OFF.) Local communications mode setting Speed priority setting Distance priority setting • SW7 Setting This setting is only valid if the EEPROM-type (batterylesstype) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (battery-type) DC. SW7 must be set to OFF when the V620 is used. Baud rate (bps) 2400 4800 9600 19,200 Display mode Error display mode I/O display mode Data length (bit) STOP bits (bit) Parity type 7 7 7 7 8 8 8 8 2 2 1 1 2 1 1 1 E O E O N N E O 371 Appendix M V600/V620 ID Controller Protocol DIP Switch 2 1 2 3 4 5 6 7 8 Not used (Always keep it OFF.) Communications protocol setting with host devices 1-to-N protocol 1-to-1 protocol Note When selecting the “1-to-N” protocol, setting is limited to N=1. In this case, the FCS check code may be added. • ID Controller Unit Number Setting (Valid Only for 1-to-N Protocol) Unit No. No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 Note 1. Be careful not to set to the same unit number twice. 2. Set them to OFF for the 1-to-1 protocol. Synchronous condition OFF (LL level) ON (HL level) Trailing edge Leading edge 372 Appendix M V600/V620 ID Controller Protocol V600-CAA DIP Switches DIP Switch 1 Note Factory Setting: All OFF Mode 1 1 2 3 4 5 6 7 8 SW7 and SW8: Be sure to set to OFF. • Baud Rate Setting • Communications Format Baud rate (bps) Data length (bit) STOP bit (bit) Parity type 1200 2400 4800 9600 19200 7 7 7 7 8 8 8 8 (See note 1) 2 2 1 1 2 1 1 1 E O E O N N E O (See note 2) 1=ON, 0=OFF 1=ON, 0=OFF Note 1. Data length setting 7 bits: ASCII code 8 bits: JIS8 unit code 2. Parity setting E: Even parity O: Odd parity N: No parity designation DIP Switch 2 1 2 3 4 5 6 7 8 • SW8: Receive Side Terminal Resistance Setting (Valid Only for the V600-CA2A) Connected (ID Controller send side) Not connected • SW7: Receive Side Terminal Resistance Setting (Valid Only for the V600-CA2A) Connected (ID Controller receive side) Not connected • SW6: Communications Protocol Setting 1-to-N protocol 1-to-1 protocol • ID Controller Unit Number Setting (Valid Only for the 1-to-N Protocol) Unit No. • Local Communications Mode Setting No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10 No. 11 No. 12 No. 13 No. 14 No. 15 Speed priority setting Distance priority setting • SW1 Setting This setting is only valid if the EEPROM-type (batteryless-type) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (batterytype) DC. • SW6 Setting When selecting the 1-to-N protocol for the V600-CA1A/RS-232C interface, the setting is limited to N=1. In this case, the FCS check code may be added. Note 1. Be careful not to set to the same unit number twice. 2. Set them to OFF for the 1-to-1 protocol. 373 Appendix M V600/V620 ID Controller Protocol Read (ASCII/1) (Sequence No. 500) This sequence is used when the number of Heads to be read from the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Undefined) +2 Head CH No. Leading address No. +3 (Undefined) +4 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CAA) +2 R/W Head channel (CH) No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hexadecimal) 0000 to FFFF +4 Read bytes (2 digits Hexadecimal) 01 to F4 (1 to 244 bytes) Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data +2 Read data ~ ~ Read data +122 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0123 +1 to +122 Read data (ASCII) Number of read bytes stored in ASCII Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 374 Appendix M V600/V620 ID Controller Protocol Read (ASCII/2) (Sequence No. 501) This sequence is used when the number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads +2 (Undefined) +3 Unit No. (Undefined) +4 Head CH No. CH 1 Leading address No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0010 +1 Number of Heads (4 digits BCD) 0001 to 0002 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) 01 to 76 (1 to 118 bytes) N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ CH 1 ~ CH 2 Read data +59 +60 Not used +61 Read data ~ Read data +119 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0120 +(60(N–1)+1) to +(60(N–1)+59) Read data (ASCII) Number of read bytes store in ASCII N: Number of Heads Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 375 Appendix M V600/V620 ID Controller Protocol Read (ASCII/4) (Sequence No. 502) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads +2 (Undefined) +3 Unit No. (Undefined) +4 Head CH No. CH 1 Leading address No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 +9 (Undefined) Read bytes (Undefined) Unit No. ~ +14 ~ (Undefined) +15 Head CH No. 4 CH Leading address No. +16 (Undefined) +17 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0018 +1 Number of Heads (4 digits BCD) 0001 to 0004 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) 01 to 30 (1 to 48 bytes) N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data ~ +24 Read data +25 Read data ~ +48 376 ~ CH 2 ~ Read data ~ +96 CH 1 Read data ~ +73 ~ ~ Read data 4 CH Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0097 +(24(N–1)+1) to +(24(N–1)+24) Read data (ASCII) Number of read bytes stored in ASCII N: Number of Heads Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. Read (ASCII/8) (Sequence No. 503) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Read bytes ~ +30 ~ (Undefined) Unit No. (Undefined) +31 Head CH No. Leading address No. +32 (Undefined) +33 Offset 8 CH Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0034 +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) 01 to 14 (1 to 20 bytes) N: Number of Heads 377 Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data ~ +10 Read data +11 Read data ~ ~ CH 1 ~ CH 2 Read data +20 ~ ~ Read data +71 ~ ~ +80 CH 8 Read data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0081 +(10(N–1)+1) to +(10(N–1)+10) Read data (ASCII) Number of read bytes stored in ASCII N: Number of Heads Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. Read (Hexadecimal/1) (Sequence No. 504) This sequence is used when the number of Heads to be read from the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Undefined) +2 Head CH No. Leading address No. +3 (Undefined) +4 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CAA) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hexadecimal) 0000 to FFFF +4 Read bytes (2 digits Hexadecimal) 01 to 7A (1 to 122 bytes) Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data +2 Read data ~ +61 378 ~ Read data Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0062 +1 to +61 Read data (Hexadecimal) Number of read bytes stored in hexadecimal data Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words. Read (Hexadecimal/2) (Sequence No. 505) This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads +2 (Undefined) +3 Unit No. (Undefined) +4 Head CH No. CH 1 Leading address No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0010 +1 Number of Heads (4 digits BCD) 0001 to 0002 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) 01 to 3C (1 to 60 bytes) N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ +30 Read data +31 Not used ~ ~ +60 Not used +61 Read data ~ +90 CH 1 ~ CH 2 Read data 379 Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0091 +(60(N–1)+1) to +(60(N–1)+30) Read data (Hexadecimal) Number of read bytes stored in hexadecimal code N: Number of Heads Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words. Read (Hexadecimal/4) (Sequence No. 506) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Read bytes ~ +14 ~ (Undefined) +15 Unit No. (Undefined) +16 Head CH No. Leading address No. +17 (Undefined) Offset CH 4 Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0018 +1 Number of Heads (4 digits BCD) 0001 to 0004 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) 01 to 18 (1 to 24 bytes) N: Number of Heads 380 Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ +12 Read data +13 (Not used) ~ CH 1 ~ +24 (Not used) +25 Read data ~ ~ CH 2 Read data +36 ~ ~ Read data +73 ~ ~ CH 4 Read data +84 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0085 +(24(N–1)+1) to +(24(N–1)+12) Read data (Hexadecimal) Number of read bytes stored in hexadecimal data Note Data for Data Carriers designated for hexadecimal is received beginning with the largest offset from the receive data words. Read (Hexadecimal/8) (Sequence No. 507) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 +2 +3 +4 Number of send data words Number of Heads (Undefined) (Undefined) Unit No. Head CH No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. +7 +8 +9 (Undefined) Head CH No. +31 +32 +33 CH 2 Leading address No. (Undefined) Read bytes ~ +30 CH 1 Leading address No. ~ (Undefined) (Undefined) Unit No. Head CH No. Leading address No. (Undefined) CH 8 Read bytes 381 Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0034 +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) 01 to 0A (1 to 10 bytes) N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ +5 Read data +6 Not used ~ CH 1 ~ +10 Not used +11 Read data ~ ~ CH 2 Read data +15 ~ ~ Read data +71 ~ ~ CH 8 Read data +75 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0076 +(10(N–1)+1) to +(10(N–1)+5) Read data (CH 1) (Hexadecimal) Number of read bytes stored in hexadecimal data N: Number of Heads Note Data for Data Carriers designated for hexadecimal is sent beginning with the largest offset from the receive data words. Auto-read (ASCII/1) (Sequence No. 508) This sequence is used when the maximum number of Heads to be read from the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)). Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. 382 Appendix M V600/V620 ID Controller Protocol Auto-read (Hexadecimal/1) (Sequence No. 509) This sequence is used when the maximum number of Heads to be read from the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 504 (Read (Hexadecimal/1)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 504 (Read (Hexadecimal/1)). Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Polling Auto-read (ASCII) (Sequence No. 510) This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8. Send Data Word Allocation (2nd Operand of PMCR) Number of send data words First word of send +0 data +1 Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 (Undefined) +5 Read bytes ~ +(4(N–1)+2) ~ (Undefined) Unit No. (Undefined) +(4(N–1)+3) Head CH No. Leading address No. +(4(N–1)+4) (Undefined) +(4(N–1)+5) Offset CH N * N: Number of Heads Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0034 +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) If number of Heads is 2 or less 01 to 76 (1 to 118 bytes) If number of Heads is 4 or less 01 to 30 (1 to 48 bytes) If number of Heads is 8 or less 01 to 20 (1 to 20 bytes) N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 510 before executing Sequence No. 511, 512, 513. 2. Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read. 3. Retry processing is not performed for this sequence. 383 V600/V620 ID Controller Protocol Appendix M Polling Auto-read Sub-command (ASCII/2) (Sequence No. 511) This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)). Note 1. Execute Sequence No. 510 before executing Sequence No. 511. 2. Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 3. Retry processing is not performed for this sequence. Polling Auto-read Sub-command (ASCII/4) (Sequence No. 512) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)). Note 1. Execute Sequence No. 510 before executing Sequence No. 512. 2. Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 3. Retry processing is not performed for this sequence. Polling Auto-read Sub-command (ASCII/8) (Sequence No. 513) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)). Note 1. Execute Sequence No. 510 before executing Sequence No. 513. 2. Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 3. Retry processing is not performed for this sequence. 384 Appendix M V600/V620 ID Controller Protocol Polling Auto-read (Hexadecimal) (Sequence No. 514) This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8. Send Data Word Allocation (2nd Operand of PMCR) Number of send data words First word of send +0 data +1 Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 (Undefined) +5 Read bytes ~ +(4(N–1)+2) ~ (Undefined) Unit No. (Undefined) +(4(N–1)+3) Head CH No. Leading address No. +(4(N–1)+4) (Undefined) +(4(N–1)+5) Offset CH N * N: Number of Heads Read bytes Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0034 +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 +(4(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hexadecimal) If number of Heads is 2 or less 01 to 3C (1 to 60 bytes) R/W Head CH 2 designation: 2 If number of Heads is 4 or less 01 to 18 (1 to 24 bytes) If number of Heads is 8 or less 01 to 0A (1 to 10 bytes) N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 514 before executing Sequence No. 515, 516, 517. 2. Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read. Polling Auto-read Sub-command (Hexadecimal/2) (Sequence No. 515) This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 505 (Read (Hexadecimal/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 505 (Read (Hexadecimal/2)). Note 1. Execute Sequence No. 514 before executing Sequence No. 515. 385 Appendix M V600/V620 ID Controller Protocol 2. Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words. 3. Retry processing is not performed for this sequence. Polling Auto-read Sub-command (Hexadecimal/4) (Sequence No. 516) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 506 (Read (Hexadecimal/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 506 (Read (Hexadecimal/4)). Note 1. Execute Sequence No. 514 before executing Sequence No. 516. 2. Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words. Polling Auto-read Sub-command (Hexadecimal/8) (Sequence No.517) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of sequence No.507 (Read (Hexadecimal/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514. Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of sequence No.507 (Read (Hexadecimal/8)). Note 1. Execute sequence No.514 before executing sequence No.517. 2. Data from Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words. 3. Retry processing is not performed for this sequence. Write (ASCII/1) (Sequence No.518) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 +2 Number of send data words (Undefined) (Undefined) Head CH No. +3 Leading address No. +4 Number of write bytes +5 Write data ~ ~ Max +128 386 Unit No. Write data Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0129 +1 Relevant Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CA2A) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hexadecimal) 0000 to FFFF +4 Number of write bytes (4 digits BCD) 0001 to 0248 +5to +128 Write data (ASCII) Input in ASCII Up to 248 bytes (max.) can be set Receive Data Word Allocation (3rd Operand of PMCR) None. Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words. Write (ASCII/2) (Sequence No. 519) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 +2 +3 Number of send data words Number of Heads (Undefined) (Undefined) Unit No. Head CH No. +4 Leading address No. +5 Number of write bytes +6 Write data ~ +64 +65 +66 +67 ~ Write data (Not used) (Undefined) (Undefined) Unit No. Head CH No. +68 Leading address No. +69 Number of write bytes +70 Write data ~ +128 CH 1 CH 2 ~ Write data 387 Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 to 0129 +1 Number of Heads (4 digits BCD) 0001 to 0002 +(64(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(64(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(64(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(64(N–1)+5) Number of write bytes (4 digits BCD) 0001 to 0118 +(64(N–1)+6) to (64(N–1)+64) Write data (ASCII) Input in ASCII. Up to 118 bytes (max.) can be set N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words. 388 Appendix M V600/V620 ID Controller Protocol Write (ASCII/4) (Sequence No. 520) This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write bytes +6 Write data ~ CH 1 ~ Write data +29 (Undefined) +30 Unit No. (Undefined) +31 Head CH No. +32 Leading address No. +33 Number of write bytes +34 Write data ~ CH 2 ~ Write data +57 ~ +86 ~ (Undefined) +87 Unit No. (Undefined) Head CH No. +88 Leading address No. +89 Number of write bytes +90 Write data ~ CH 4 ~ Write data +113 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 to 0114 +1 Number of Heads (4 digits BCD) 0001 to 0004 +(28(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(28(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(28(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(28(N–1)+5) Number of write bytes (4 digits BCD) 0001 to 0048 +(28(N–1)+6) to (28(N–1)+29) Write data (ASCII) Input in ASCII. Up to 48 bytes (max.) can be set N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note Write designated for ASCII is sent beginning with the smallest offset from the send data words. 389 Appendix M V600/V620 ID Controller Protocol Write (ASCII/8) (Sequence No. 521) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write bytes +6 Write data ~ CH 1 ~ Write data +15 (Undefined) +16 Unit No. (Undefined) +17 Head CH No. +18 Leading address No. +19 Number of write bytes +20 Write data ~ CH 2 ~ Write data +29 ~ +100 ~ (Undefined) +101 Unit No. (Undefined) Head CH No. +102 Leading address No. +103 Number of write bytes +104 Write data ~ CH 8 ~ Write data +113 Offset Contents (data format) Data +0 Number of send data words(4 digits BCD) 0007 to 0114 +1 Number of Heads (4 digits BCD) 0001 to 0008 +(14(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(14(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(14(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(14(N–1)+5) Number of write bytes (4 digits BCD) 0001 to 0020 +(14(N–1)+6) to (14(N–1)+15) Write data (ASCII) Input in ASCII Up to 20 bytes (max.) can be set N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words. 390 Appendix M V600/V620 ID Controller Protocol Write (Hexadecimal/1) (Sequence No. 522) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) (Undefined) +2 Unit No. Head CH No. +3 Leading address No. +4 Number of write digits +5 Write data ~ ~ (Undefined) Max +35 Offset Write data Contents (data format) Data +0 Number of send data words (4 digits BCD) 0006 to 0036 +1 Relevant Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CA2A) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hexadecimal) 0000 to FFFF +4 Number of write digits (4 digits BCD) 0002 to 0122 +5 to 35 Write data (Hexadecimal) Input in hexadecimal Up to 122 digits (max.) Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Data of which Data Carrier designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. 391 Appendix M V600/V620 ID Controller Protocol Write (Hexadecimal/2) (Sequence No. 523) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write digits +6 Write data ~ CH 1 ~ +19 Write data +20 (Not used) ~ ~ +65 (Not used) (Undefined) +66 Unit No. (Undefined) +67 Head CH No. +68 Leading address No. +69 Number of write digits +70 Write data ~ CH 2 ~ Write data +83 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 to 0084 +1 Number of Heads (4 digits BCD) 0002 to 0002 +(64(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(64(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(64(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(64(N–1)+5) Number of write digits (4 digits BCD) 0002 to 0056 +(64(N–1)+6) to (64(N–1)+19) Write data (Hexadecimal) Input in hexadecimal Up to 56 digits (max.) can be set N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Write data designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. 392 Appendix M V600/V620 ID Controller Protocol Write (Hexadecimal/4) (Sequence No. 524) This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 24 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write digits +6 Write data ~ CH 1 ~ +11 Write data +12 Not used ~ ~ +29 Not used +30 (Undefined) +31 Unit No. (Undefined) Head CH No. +32 Leading address No. +33 Number of write digits +34 Write data ~ CH 2 ~ Write data +39 ~ +86 ~ (Undefined) Unit No. (Undefined) +87 Head CH No. +88 Leading address No. +89 Number of write digits +90 Write data ~ CH 4 ~ Write data +95 Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 to 0096 +1 Number of Heads (4 digits BCD) 0001 to 0004 +(28(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(28(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(28(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(28(N–1)+5) Number of write digits (4 digits BCD) 0002 to 0024 +(28(N–1)+6) to (28(N–1)+11) Write data (Hexadecimal) Input in hexadecimal code Up to 24 digits (max.) can be set N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. 393 Appendix M V600/V620 ID Controller Protocol Note 1. Write data designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. Write (Hexadecimal/8) (Sequence No. 525) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 +2 +3 Number of send data words Number of Heads (Undefined) (Undefined) Unit No. Head CH No. +4 Leading address No. +5 Number of write digits +6 Write data ~ +8 +9 ~ (Undefined) Write data Not used ~ +15 +16 +17 ~ Not used (Undefined) (Undefined) Unit No. Head CH No. +18 Leading address No. +19 Number of write digits +20 Write data ~ +22 +101 (Undefined) Write data (Undefined) Unit No. ~ (Undefined) Head CH No. +102 Leading address No. +103 Number of write digits +104 Write data ~ +106 394 CH 2 ~ ~ +100 CH 1 CH 8 ~ (Undefined) Write data Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits BCD) 0007 to 0107 +1 Number of Heads (4 digits BCD) 0001 to 0004 +(14(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(14(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(14(N–1)+4) Leading address No. (4 digits Hexadecimal) 0000 to FFFF +(14(N–1)+5) Number of write digits (4 digits BCD) 0002 to 0010 +(14(N–1)+6) to (14(N–1)+8) Write data (Hexadecimal) Input in hexadecimal code Up to 10 digits (max.) can be set N: Number of Heads Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Write data designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. Auto-write (ASCII/1) (Sequence No. 526) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 518 (Write(ASCII/1)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 518 (Write(ASCII/1)). Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Auto-write (Hexadecimal/1) (Sequence No. 527) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 522 (Write (Hexadecimal/1)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 522 (Write (Hexadecimal/1)). Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Polling Auto-write (ASCII/2) (Sequence No. 528) This sequence is used when the number of Heads to be written to the Carrier is 2. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. 395 V600/V620 ID Controller Protocol Appendix M Polling Auto-write Subcommand (ASCII/2) (Sequence No. 529) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 528 before executing Sequence No. 529. 2. Retry processing is not performed for this sequence. Polling Auto-write (ASCII/4) (Sequence No. 530) This sequence is used when the number of Heads to be written to the Carrier is 4. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 520 (Write(ASCII/4)). Note Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling autowrite. Polling Auto-write Subcommand (ASCII/4) (Sequence No. 531) This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 530 before executing Sequence No. 531. 2. Retry processing is not performed for this sequence. Polling Auto-write (ASCII/8) (Sequence No. 532) This sequence is used when the number of Heads to be written to the Carrier is 8. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (ASCII/8) (Sequence No. 533) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). However, the leading address No., number of write, and write data are not used and become undefined. 396 V600/V620 ID Controller Protocol Appendix M Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 532 before executing Sequence No. 533. 2. Retry processing is not performed for this sequence. Polling Auto-write (Hexadecimal/2) (Sequence No. 534) This sequence is used when the number of Heads to be written to the Carrier is 2. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 523 (Write (Hexadecimal/2)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 523 (Write (Hexadecimal/2)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (Hexadecimal/2) (Sequence No. 535) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 523 (Write (Hexadecimal/2)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 534 before executing Sequence No. 535. 2. Retry processing is not performed for this sequence. Polling Auto-write (Hexadecimal/4) (Sequence No. 536) This sequence is used when the number of Heads to be written to the Carrier is 4. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 524 (Write (Hexadecimal/4)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 524 (Write (Hexadecimal/4)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (Hexadecimal/4) (Sequence No. 537) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 24 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 524 (Write (Hexadecimal/4)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (3rd Operand of PMCR) None. 397 Appendix M V600/V620 ID Controller Protocol Note 1. Execute Sequence No. 536 before executing Sequence No. 537. 2. Retry processing is not performed for this sequence. Polling Auto-write (Hexadecimal/8) (Sequence No. 538) This sequence is used when the number of Heads to be written to the Carrier is 8. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 525 (Write (Hexadecimal/8)). Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 525 (Write (Hexadecimal/8)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (Hexadecimal/8) (Sequence No. 539) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head. Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 525 (Write (Hexadecimal/8)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (3rd Operand of PMCR) None. Note 1. Execute Sequence No. 538 before executing Sequence No. 539. 2. Retry processing is not performed for this sequence. Data Check (Sequence No. 540) This sequence writes and verifies the CRC code for check blocks designated by the user. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) +2 (Undefined) +3 Processing designation Unit No. Head CH No. (Undefined) +4 Leading address of check object +5 (Undefined) Number of check block bytes Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0006 (fixed) Data +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CA2A) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Processing designation (2 digits Hexadecimal) Verification: 43 (C) Calculation: 4B (K) Management of number of write times: 4C (L) +4 Leading address of check object (4 digits Hexadecimal) 0000 to FFFF +5 398 Number of check block bytes (2 digits Hexadecimal) (If management of number of write times is designated, H’ 0 to H’ 5 or H’ 8 to H’ D) If verification, calculation is designated: 03 to FF (set 00 for 256 bytes) If management of number of write times is designated: 00 to FF Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Completion code Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0002 (fixed) Data +1 Completion code (2 digits Hexadecimal) (Verification, calculation designation) 00: Normal completion for calculation processing 75: Data in normal condition for verification processing 76: Error Data alarm for verification processing (If management of number of write times is designated) 75:Number of write times is under those which is specified. 76:alarm for number of write times is over those which is specified. Note If L (management of number of write times) is designated by processing designation, management of number of write times for Data Carrier of EEPROM is performed. Control (Sequence No. 541) This sequence performs I/O operations or I/O reads. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 Number of send data words data +1 (Undefined) Unit No. +2 (Undefined) Offset OUT1 operation OUT2 operation Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) +2 OUT1 operation (1 digit BCD) 0: No operation 1: turned ON 2: turned OFF OUT2 operation (1 digit BCD) 0: No operation 1: turned ON 2: turned OFF Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Current input status Offset Output status after operation Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 (fixed) +1 Leftmost 1 byte Current input status Leftmost 4 bits: IN1 operation Rightmost 4 bits: IN2 operation 1: ON status 0: OFF status Output status after operation Leftmost 4 bits: OUT1 operation Rightmost 4 bits: OUT2 operation 1: ON status 0: OFF status Note 1. The V600/620-CAA does not support this command. 2. This sequence executes the equivalent of the CONTROL command. 399 Appendix M V600/V620 ID Controller Protocol Error Information Read (Sequence No. 542) This sequence reads information from the latest error log. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Error log ~ ~ Error log +75 Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0004 to 0076 +1 to +75 Error log (ASCII) One item of data is stored with 5 characters of generated command, generated Head No., generated error code. Note 1. The V600/620-CAA does not support this command. 2. Up to 30 error records can be stored. 3. The most resent error records are stored first. Command Processing Cancel (Sequence No. 543) This sequence cancels command processing except for polling command processing. The command waiting status is entered. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Number of send data words (4 digits BCD) 0002 (fixed) +1 Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words 400 Data +0 +0 Number of receive data words +1 (Undefined) Unit No. Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 (fixed) +1 Completion code (2 digits Hexadecimal) 00: Normal termination 14: Auto or communications command processing not executed 75: Cancelled before the end of expansion command receive or before sync input went active or before detection of the existence of Data Carrier 76: Cancelled during read/write processing for Data Carrier Polling Auto-read Command Processing Cancel (Sequence No. 544) This sequence cancels polling auto-read processing. Send Data Word Allocation (2nd Operand of PMCR) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Not used) +2 (Undefined) +3 Offset Head channel No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0004 (fixed) +1 Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +2 Not used +3 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. Receive Data Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 (Undefined) Completion code Offset Contents (data format) +0 Number of receive data words (4 digits BCD) 0002 (fixed) Data +1 Completion code (2 digits Hexadecimal) 75: Cancelled before communications processing with Data Carrier 76: Cancelled after communications processing with Data Carrier Polling Auto-write Command Processing Cancel (Sequence No. 545) This sequence cancels polling auto-write processing Send Data Word Allocation (2nd Operand of PMCR) The send data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing Cancel) Receive Data Word Allocation (3rd Operand of PMCR) The receive data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing Cancel) 401 Appendix M V600/V620 ID Controller Protocol General-purpose Command (Sequence No. 546) This sequence transmits arbitrary data and stores receive data to the receive data words. The characters “@”, FCS (terminator) are not required in the send data words and receive data words. These characters will be automatically added for transmission and automatically removed before saving data. Send Data Word Allocation (2nd Operand of PMCR) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data ~ +127 ~ Send data Offset (Undefined) Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0128 +1 Send data byte length (4 digits BCD) 0001 to 0251 The number of bytes in the send data except for @, the FCS, and the terminator. +2 to +127 Send data (ASCII) Input send data up to 251 characters (max.) in ASCII Receive Data Storage Word Allocation (3rd Operand of PMCR) Receive data storage words +0 Number of receive data words +1 Receive data ~ +126 ~ Receive data Offset 402 (Undefined) Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0002 to 0127 +1 to +126 Receive data (ASCII) Receive data is stored in ASCII. Up to 251 characters (max.) Appendix N Hayes Modem AT Command Protocol The Hayes Modem AT Command Protocol is used to make various settings or control remotely a Hayes modem connected to the Serial Communications Board via RS-232C cable. Protocol Configuration The configuration of the Hayes Modem AT Command Protocol is shown below. Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation No 550 Initialize modem (general-purpose) Initializes the modem connected to the Serial Communications Board. The initialization command is set in the words specified for the second operand of PMCR. 560 570 580 Initialize modem (specialized) Initializes certain OMRON Modems. No No 561 571 581 Dial Dials from the modem connected to the Serial Communications Board. AT commands and telephone numbers are set set in the words specified for the second operand of PMCR. This sequence can be used only for certain OMRON modems. Yes No 552 Password After the line is connected, the password sent from the other exchange is verified to confirm that the line is connected to the desired exchange. The normal value of a password is set in the words specified for the second operand of PMCR. Yes No 553 Data send/receive (general purpose sequence) Sends arbitrary data to the exchange which the line is connected. Send data is set in the words specified for the second operand of PMCR. Receive data is stored in the words specified for the third operand of PMCR. Yes Yes 554 Escape No No 555 Hang up No No 562 572 582 Initialize and dial Shifts the modem to escape mode (the condition in which command input is available during data communications). The escape code is fixed to “+++” After shifting to escape mode, the line is disconnected. Executes continuously from initialization to dialling operations for certain OMRON Modems. Yes* No 590 Escape to hang up No No Executes continuously from shifting to the escape mode to hanging up. Note 1. Ladder Interface Settings YES: User settings are required for the 2nd and 3rd operands of PMCR. NO: Send word allocation: Set a dummy word address for the 3rd operand (D). Receive word allocation: Set the constant 0000 for the 2rd operand (S). 2. For details about dialling, refer to sequences 561, 571 and 581. 403 Appendix N Hayes Modem AT Command Protocol Connections The connections when using the Hayes Modem AT Command Protocol is shown below. RS-232C Connection Modem Modem: D-sub 25 pin (female) Telephone line Modem CQM1H D-sub 9 pin (female) Compatible Modems Although most of the sequences in this protocol can be used regardless of modem, the sequences Initialize Modem (specialized) and Dial sequences can be used only for the following Modems: • MD24FB10V (OMRON Modem) • MD144FB5V (OMRON Intelligent Modem) • ME1414VB2/B2 (OMRON FAX/DATA Modem) For other modems, create a modem initialization sequence using the general-purpose Initialize Modem sequence and dial using the Data Send/Receive sequence (Sequence No. 553). 404 Appendix N Hayes Modem AT Command Protocol Modem Settings When this protocol is used, it is required that the modem connected to the Serial Communications Board be initialized to the following conditions: Command echo No Result code display format Numeric format Speed display, busy/dialling tone detection at connection Error correction data compression display Baud rate display enabled, busy and dialling tone detection enabled. Error correction/data compression display enabled MNP setting Error correction provided (auto-reliable mode) MNP class setting MNP class 4 V.42 compression, Error correction Not enabled Flow control between terminal modems Not enabled ER signal control Always ON Escape code + Note 1. It is recommended that, in addition to the above settings, the abort timer should be set so that communications are cut off if a communications error happened due to incidents such as cable disconnection between the Serial Communications Board and modem. Set the abort timer to 10 minutes for the modem initialization (specialized) (Sequence No. 560, 570, 580). Refer to modem’s manual for further information about abort timers. 2. The data format of the modem (baud rate, data length, parity, stop bit) is set by AT commands issued from a device connected to the modem. Its settings should conform to communications conditions of the device which issues AT commands. Therefore when communications are made between the modem and Serial Communications Board, it is required that communications conditions should be set by issuing AT commands from the Serial Communications Board. 3. Modem settings become invalid if the power supply is turned off and must be set again. However, a memory backup function can be used to protect settings so that even after the power supply to the modem is turned off, it can communicate with the previous setting conditions. For Initialize Modem (specialized), the modem initialization command is built in as message data. However, for Initialize Modem (general-purpose), the command must be specified in PMCR. Operand 1 #x550 (x: Communications port) Operand 2 First address for storing initialization command character string C Operand 3 None C+0 Number of words from address set for operand 2 to end of data 4 digits BCD C+1 Number of bytes for send data (initialization command) 4 digits BCD C+2 : C+n Send data (initialization command) (Fill data to left for odd numbers of bytes) ASCII Setting Example for Modem Initialization Command • MD24FB10V Using Sequence #550 (OMRON) The following command is set in the words specified by the second operand of PMCR. ATE0V0X4\V2\N3%C0*C0\X1&M0S26=10 0018 0032 A T E 0 V 0 X 4 \ V 2 \ N 3 %C 0 * C 0 \ X 1 & M 0 S 2 6 = 1 0 Character string length of modem initialization command (bytes) Code length of PMCR when it is used (words) Note Turn ON pin 4 of DIP switches SW3 on for this Modem (ER signal always ON). 405 Appendix N Hayes Modem AT Command Protocol MD144FB5V (OMRON) The following command is set in the words specified by the second operand of PMCR. ATE0V0X4\V2\N3%C0*C0\Q0&M0&D0%B9600S26=10 0023 0041 A T E 0 V 0 X 4 \ V 2 \ N 3 %C 0 * C 0 \ Q 0 & M 0 & D 0 % B 9 6 0 0 S 2 6 = 1 0 Character string length of modem initialization command (bytes) Code length of PMCR when it is used (words) ME1414VBII/ME1414BII (OMRON) The following command is set in the words specified by the second operand of PMCR. AT\J1B8E0V0S0=1X4\V2\N3&M0%C0&D0&E0\X1S26=10 0024 0044 A T \ J 1 B 8 E 0 V 0 S 0 = 1 X 4 \ V 2 \ N 3 & M 0 %C 0 & D 0 & E 0 \ X 1 S 2 6 = 1 0 Character string length of modem initialization command (bytes) Code length of PMCR when it is used (words) Note Turn ON DIP switch SW3 on in the rear of the Modem. Dialling To dial telephone numbers for the OMRON Modems using sequences No. 561, 571, 581, set the dialling command and telephone number in the words specified by the second operand of PMCR. However, for other Modems, make the following settings for the Data Send/Receive sequence. This is an example of telephone number settings for the above mentioned 3 OMRON Modems. Operand and Word Settings of PMCR Operand 1 MD24FB10V #x561 (x: Communications port) MD144FB5V #x571 ME1414VB2/B2 #x581 406 Operand 2 First address C of send data (dialling operation) Operand 3 None C+0 Number of words from address set for operand 2 to end of data 4 digits BCD C+1 Number of bytes of send data (dialling operation) 4 digits BCD C+2 : C+n Send data (dialling operation) (Fill data to left for odd numbers of bytes) ASCII Appendix N Hayes Modem AT Command Protocol Setting Example If telephone number is 03-0123-4567 0010 0016 4154 4454 3033 2D30 3132 332D 3435 3637 AT DT 03 –0 12 3– 45 67 Character string length of dialling operation sent to modem (bytes) Code length of PMCR when it is used (words) Note 1. This example uses a tone line. Change ATDT to ATDP for pulse lines. 2. Fill the telephone number to the left in the words if the character string length of the dialling operation is an odd number of bytes. 0008 0011 4154 4454 3031 2D32 3334 3500 AT DT 01 –2 34 5 Character string length of dialling operation sent to modem (bytes) Code length of PMCR when it is used (words) Password Verification A password can be verified by executing sequence No. 552 of this protocol. It is required to set in advance the value of the password in the words specified by the second operand of PMCR. Operand and Word Settings of PMCR Operand 1 #x550 (x: Communications port) Operand 2 First address of the words where the password is set Operand 3 None C+0 Number of words from address set for operand 2 to end of data 4 digits BCD C+1 Number of bytes of comparison data (normal value of password) 4 digits BCD C+2 : C+n Comparison value (password normal value) (Fill data to left for odd numbers of bytes) ASCII Setting Example When password is OMRON-CO. 0006 0008 4F4D 524F 4E2D 434F OM RO N– CO Character string length of password sent to modem (bytes) Code length of PMCR when it is used (words) 407 Appendix N Hayes Modem AT Command Protocol Password Verification Operation The number of retries is 3 for password verification. PC Personal computer (remote exchange) Password verification (starting #552) Dispatching character string “Password: ” Receiving character string (Retry up to 3 times) Password Issuing password Receiving password Verifying password Verification result When Instruction Execution Flag (SR 28908 or SR 28913) turns ON. Terminating process Data Send/Receive Data Send/Receive can be executed using sequence No. 553. The send data sent to another exchange is set in the words specified by the second operand of PMCR. Data received by the PC is stored in the words specified by the third operand of PMCR. Operand and Word Settings of PMCR Operand 1 #x553 (x: Communications port) Operand 2 First address C1 of the words where send data is set Operand 3 First address C2 of the words where receive data is stored • Operand 2 C1+0 Number of words from address set for operand 2 to end of data 4 digits BCD C1+1 Number of bytes of send data 4 digits BCD C1+2 : C1+n Send data (dialling operation) (Fill data to left for odd numbers of bytes) ASCII • Operand 3 408 C2+0 Number of bytes of receive data 4 digits BCD C2+1 : C2+n Receive data (dialling operation) (Fill data to left for odd numbers of bytes) ASCII Appendix N Hayes Modem AT Command Protocol Setting Example When send data is THIS IS SAMPLE. 0009 0014 5448 4953 2049 5320 5341 4D50 4C45 TH IS I S SA MP LE Character string length of send data sent to modem (bytes) Code length of PMCR when it is used (words) A maximum of 200 bytes (including the CR) can be received. When the received data is RETURN OK, the content stored in the receive words is as follows: 0006 5245 5455 524E 204F 4B00 RE TU RN O K Length of received character string (words) Note An error will occur is the reception data is not received within 90 seconds after the data is sent. Escape Mode Shifting to the escape mode can be made using sequence No. 554. No setting is necessary for this sequence. Note The character string to shift the online mode to the escape mode (i.e., the escape code) is ‘+’ for modem settings. Hang Up Command The hang up command (to disconnect the line) can be executed using sequence No. 555. No setting is necessary for this sequence. Communication Errors Three result codes are monitored after an AT command is sent to the modem. When a result code is returned, it will be checked. If the code is not the normal result code (“OK”, “CONNECT 9600/REL4”, “CONNECT 2400/REL4”, in words), after a fixed time of waiting to send, the following retry processing will be repeated 2 times to send the AT command again and waiting for another result code. The receive monitoring time and send wait time for each sequence are shown below. Sequence No. #550 #560 Sequence name Receive monitoring time Send wait time for retries Initialize modem (general-purpose) 10 s 1s Initialize modem (specialized) 10 s 1s Dial 90 s 90 s #552 Password None 3s #553 Data send/receive (general-purpose) 90 s None #554 Escape 10 s 1.5 s (after first try) #555 Hang up 10 s 1.5 s (after first try) #562 Initialize and dial 90s Initializing: 1 s Dialling: 90 s Escape and hang up 10 s 1.5 s (after first try) #570 #580 #561 #571 #581 #572 #582 #590 409 Index Numbers 1:1 Data Link, 3, 4, 6, 107 functions, 108 ports, connections, 110 specifications, 109 starting, 108 1:1 NT Link, 3, 4, 7 1:N NT Link, 3, 4, 7 errors, 129 2-wire and 4-wire connections, transmission circuits, 19 2-wire or 4-wire switch, 13 3Z4L Laser Micrometer, 63 connections, 319 protocols, sequences, 317–347 components, names and functions, 10 CompoWay/F, protocols, 63 CompoWay/F Master command and response formats, 138 communications specifications, 138 connections, 151 message frames, 143 protocols, 142 sequences, 137, 142 transmission procedure, 138 connectors, 12, 13, 17, 26 See also installation connector hoods, 25 cover dimensions, 15 wiring, 23 CPU Units, supporting CPU Units, 8 CS1-series CPU Units, changes in communications specifications, 54, 55 A–B CS1-series Serial Communications Unit/Board, changes in communications specifications, 54, 55 applications, precautions, xiii current consumption, 8 B500-AL001-E Link Adapter, 22 CV-series CPU Units, changes in communications specifications, 54, 55 bar code reader, connections, 101 Bar Code Readers, 5 CV-series Host Link Units, changes in communications specifications, 54, 55 baud rate no-protocol communications, 100 protocol macros, 59 CVM1 CPU Units, changes in communications specifications, 54, 55 CVM1 Host Link Units, changes in communications specifications, 54, 55 C C-mode commands, 5 C-series CPU Units, changes in communications specifications, 54 C-series Host Link Units, changes in communications specifications, 53, 55 C200H Communications Boards, 55 C200HX/HG/HE Communications Board, changes in communications specifications, 55 cables, 12, 13 See also installation preparation, 23 cleaning, 130 communications distance Host Link, 36 protocol macros, 59 communications ports. See ports CX-Protocol, 5, 37, 66, 100, 109, 116 D–E dimensions, 8 Serial Communications Boards, 15 E5J Temperature Controller, 63 connections, 230 protocols, sequences, 229–242 E5K Digital Controller, 63 connections read, 154 write, 154 read protocols, sequences, 153–170, 171–185 E5ZE Temperature Controller, 63 connections read, 188 write, 188 read protocols, sequences, 187–208 write protocols, sequences, 209–227 communications sequences, 85 See also PMCR(––) instructions, protocol macros, standard system protocols; sequences EC Directives, xv comparison, previous products, 55 error check codes, Host Link, 36 EMI measures, xv 411 Index errors 1:N NT Link, 129 error codes, 30, 81, 85, 105 error flags, 30 flags, 121 Host Link, 121 end codes, 52 indicators, 120 protocol macros, 125 troubleshooting, 121 ES100 Digital Controller, 63 connections, 244 protocols, sequences, 243–282 Executed Reception Case No. (code), 82 external dimensions, connector cover, 15 F F200/F300/F350 Visual Inspection Unit, 63 ferrite cores, xvi flags, 30 errors, 121 Frame Check Sequence. See frames, FCS frames dividing, precautions, 45 FCS, 46 H Hayes Modem AT Command, 63 compatible modems, 404 connections, 404 protocols, sequences, 403–409 heat-shrinking tubes, 25 Host Link, 3, 4, 5, 33 commands, 5, 51 communications, procedures, 45 end codes, 52 errors, 121 host-initiated communications, 34 PC-initiated communications, 34 ports, connections, 39 specifications, 36 transmission delay, 50 unit number setting, 29 Host Link Units, changes in communications specifications, 55 I indicators CPU Unit, 11 error displays, 120 Serial Communications Boards, 10 inspection, 131 412 installation 1:1 Data Link, connections, 110 cables, Host Link, 44 Host Link connections, 39 preparing cables, 44 mounting location, 4 no-protocol communications, connections, 101 NT Links, connections, 117 protocol macros, connections, 70 Serial Communications Boards, 14 instructions PMCR(––), 85, 89 RXD(––), 102, 104 TXD(––), 34, 102, 104 Intelligent Signal Processors, 5 K–M K3T Intelligent Signal Processor, 63 connections, 285 protocols, sequences, 283–303 Link Adapters, 19, 22, 40, 72 link words, settings, 29 maintenance, 119 cleaning, 130 inspection, 131 memory, allocations, 27 messages, no-protocol communications, 99 modems, 5 compatibility, 404 settings, 405 mounting height, 15 N no-protocol communications, 3, 4, 6, 97 overview, 98 ports, connections, 101 specifications, 98 noise reduction, 18 NT Link commands, 7 NT Links, 113 1:1, 114 1:N, 114 commands, 114 overview, 114 ports, connections, 117 NT-AL001-E Link Adapter, DIP switch settings, 19 O operating environment, precautions, xiii operation basic procedure, 8 procedure 1:1 Data Link, 109 Host Link, 36 no-protocol communications, 100 NT Links, 116 protocol macros, 66 Index P parameters sequence, 77 step, 78 PC Setup, 8, 28 link words, 1:1 Data Link, 108 standard settings 1:1 Data Link, 109 Host Link, 37 no-protocol communications, 100 NT Links, 116 protocol macros, 67 PC-initiated communications, 34 PMCR(––) instruction, 85, 143 operand settings, 89 specifications, 85 ports, 8 See also RS-232C ports; RS-422A/485 ports settings, 29 protocols, 4, 136 See also standard system protocols 3Z4L Laser Micrometer, sequences, 317–347 CompoWay/F, sequences, 137 creating, 64 E5J Temperature Controller, sequences, 229–242 E5K Digital Controller read, sequences, 153–170, 171–185 E5ZE Temperature Controller read, sequences, 187–208 E5ZE Temperature Controller write, sequences, 209–227 ES100 Digital Controller, sequences, 243–282 Hayes Modem AT Command, sequences, 403–409 Host Link, 45 K3T Intelligent Signal Processor, sequences, 283–303 Protocol Support Software, list, 136 structure, 76 V500/V520 Bar Code Reader, sequences, 305–316 V600/V620 ID Controller, sequences, 367–402 Visual Inspection System, sequences, 349–366 R power supply, 8 precautions, xi applications, xiii Board replacement, 132 Forced Abort Bit, 95 general, xii installing Serial Communications Boards, 16 noise reduction, 18 NT Links, 114 operating environment, xiii replacement, 132 safety, xii wiring, 18 previous products, comparison, 55 program examples 1:1 Data Link, 111 Host Link, 48 no-protocol communications, 105 NT Links, 114 protocol macros, 87, 88 protocol macros, 3, 4, 5, 57 applications, 85 errors, 125 flags and control bits, 80 functions, 58 ladder programs, 87 ports, connections, 70 specifications, 59 standard system protocols, 63 transmission methods, 91 reception case number, 31, 82 reception counter, 31, 98 reception matrixes, 77 repeat counter, 31 RS-232C communications, one-to-one link, 108 connecting Units, 108 RS-232C connections, 151 RS-232C ports 1:1 connections, 71 1:N connections, 73 changes from previous products, 53 connector pin layout, 11, 12 host computer connections, 40 specifications, 11 wiring, 20 RS-422 connections, 152 RS-422A/485 ports 1:1 connections, 74 1:N connections, 75 changes from previous products, 55 host computer connections, 42 specifications, 12 wiring, 21 RS-485 connections, 152 RXD(––) instruction, 102, 104 413 Index S safety precautions. See precautions sequence parameters, 77 sequences, CompoWay/F Master Broadcast with ASCII Conversion, No Response, 146 Broadcast with No Conversion and No Response, 148 General-purpose Broadcast with No Conversion and No Response, 150 General-purpose Send with No Conversion and with Response, 149 Send with ASCII Conversion, with Response, 143 Send with No Conversion and with Response, 147 sequences, 3Z4L Laser Micrometer 3Z4L Clear, 323 3Z4L Initialize (3000-series), 339 3Z4L Initialize (4000-series), 345 All Statistic Memory Clear (3000-series), 333 Automatic Detection List Request (3000-series), 338 Automatic Detection Release (3000-series), 338 Automatic Detection Set (3000-series), 338 AVG Move (H) Times Set (3000-series), 337 AVG Move (L) Times Set (3000-series), 337 AVG Move Interval Set (3000-series), 337 Calibration Release, 324 Calibration Set, 324 Continuous Measurement Start (Interrupt) (3000-series), 332 Continuous Measurement Start (Interrupt) (4000-series), 344 Continuous Measurement Start (Scan) (3000-series), 331 Continuous Measurement Start (Scan) (4000-series), 344 Continuous Measurement Termination (4000-series), 345 Data Request (3000-series), 332 Data Request (4000-series), 345 Deflection Measurement Start (4000-series), 344 E Unit Set, 323 Forced Negative Zero (4000-series), 345 Forced Positive Zero (4000-series), 345 Forced Zero Release (4000-series), 345 General-purpose Command 1 (4000-series), 346 General-purpose Command 2 (4000-series), 347 Measurement Condition List Request (3000-series), 328 Measurement Condition List Request (4000-series), 342 Measurement Condition Release (3000-series), 328 Measurement Condition Release (4000-series), 342 Measurement Condition Set (3000-series), 325 Measurement Condition Set (4000-series), 340 Measurement Termination (3000-series), 332 Memory Switch Set, 323 Memory Switch Set 1 (3000-series), 335 Memory Switch Set 2 (3000-series), 336 mm Unit Set, 323 Program Number Set (3000-series), 325 Settings, 320 Simple AVG Times Set (3000-series), 336 Single Run Measurement Start (3000-series), 331 Single Run Measurement Start (4000-series), 343 Statistic Processing Calculation Non-execution (3000-series), 333 Statistic Processing Execution (3000-series), 332 Statistic Processing Memory Clear (3000-series), 333 Statistic Result Request (3000-series), 333 Zero Run Measurement Start (3000-series), 331 414 sequences, E5J Temperature Controller General-purpose Read, 241 General-purpose Write, 241 Read Heater Current, 240 Read Initial Status, 240 Read Input Shift Value, 238 Read Output Value, 239 Read Parameters 1, 236 Read Parameters 2, 237 Read Process Value, 239 Read Set Point Limit, 239 Save Set Point, 233 Select Backup Mode, 232 Select Local Mode, 232 Select RAM Write Mode, 232 Select Remote Mode, 232 Write Input Shift Value, 235 Write Parameters 1, 233 Write Parameters 2, 234 sequences, E5K Digital Controller Execute/Cancel AT, 184 General-purpose Read, 170 General-purpose Write, 182 Read Alarm Hysteresis, 162 Read Alarm Value, 156 Read Control Period, 159 Read Cooling Coefficient, 157 Read Dead Band, 158 Read Hysteresis, 159 Read Input Digital Filter, 162 Read Input Shift Limits, 162 Read LBA Detection Time, 160 Read Level 0 Parameters, 163 Read Level 1 Parameters 1, 164 Read Level 1 Parameters 2, 165 Read Level 2 Parameters 1, 167 Read Level 2 Parameters 2, 168 Read Manual Reset Value, 158 Read MV, 156 Read MV at Stop Time and at PV Error, 161 Read MV Limits, 161 Read Process Value, 155 Read Proportional Band, Integral Time, and Derivative Time, 157 Read Set Point, 156 Read Set Point during SP Ramp, 155 Read SP Ramp Time Unit and Set Value, 159 Remote/Local, 183 Run/Stop, 183 Software Reset, 185 Switch to Level 0 (Software Reset), 182 Switch to Level 1, 185 Write Alarm Hysteresis, 176 Write Alarm Value, 172 Write Control Period, 174 Write Cooling Coefficient, 173 Write Dead Band, 173 Write Hysteresis, 173 Write Input Digital Filter, 176 Write Input Shift Value, 176 Write LBA Detection Time, 175 Write Level 0 Parameters, 177 Write Level 1 Parameter 2, 179 Write Level 1 Parameters 1, 178 Index Write Level 2 Parameters 1, 180 Write Level 2 Parameters 2, 181 Write Manual Reset Value, 173 Write MV at Stop Time and at PV Error, 175 Write MV Limits, 175 Write Proportional Band, Integral Time, and Derivative Time, 172 Write Set Point, 172 Write SP Ramp Time Unit and Set Value, 174 sequences, E5ZE Temperature Controller Cancel Autotuning, 218 Initialize Settings, 223 Read Alarm Mode, 197 Read Alarm Temperatures, 198 Read Control Period, 196 Read Cooling Coefficient, 208 Read Dead Band/Overlap Band, 207 Read Error Status, 200 Read HB Alarm and HS Alarm Valid Channels, 205 Read Heater Burnout and SSR Failure Detection Currents, 205 Read Heater Current and SSR Leakage Current, 206 Read Hysteresis, 199 Read Input Shift Value, 201 Read Manual Reset Value, 201 Read Operation Status, 199 Read Output Mode, 197 Read Output Value Change Rate Limit, 204 Read Output Value Limit, 203 Read Output Values, 193 Read Present Set Point, 203 Read Process Value, 192 Read Proportional Band, Integral Time, and Derivative Time, 195 Read Ramp Value, 202 Read Set Point, 191 Read Set Point, Process Value, and Output Value, 194 Read Setting Unit, 200 Save Settings, 223 Start Autotuning, 217 Start Control, 226 Start Manual Operation, 227 Stop Operation or Control, 226 Write Alarm Mode, 214 Write Alarm Temperature (Setting Unit 0.1), 216 Write Alarm Temperature (Setting Unit 1), 215 Write Control Period, 213 Write Cooling Coefficient, 225 Write Dead Band/Overlap Band, 225 Write HB and HS Alarm Valid Channels, 224 Write Heater Burnout and SSR Failure Detection Current, 224 Write Hysteresis, 217 Write Input Shift Value, 218 Write Manual Output Value, 220 Write Manual Reset Value, 219 Write Output Mode, 214 Write Output Value Change Rate Limit, 222 Write Output Value Limit, 221 Write Proportional Band, Integral Time, and Derivative Time, 212 Write Ramp Value, 220 Write Set Point (Setting Unit 0.1), 211 Write Set Point (Setting Unit 1), 210 Write Setting Unit, 218 sequences, ES100 Digital Controller Auto Mode, 276 Cancel A.T., 278 Change Bank No., 279 Change Pattern No., 279 Execute A.T., 277 External Setting Mode, 274 General-purpose Command, 281 Local Setting Mode, 274 Manual Mode, 277 Read Adjustment Parameters, 256 Read Control Monitor Data, 254 Read Controller Status, 280 Read Error Detection Data, 248 Read Event Data, 246 Read Heater Burnout Data, 250 Read Local SP, 267 Read MV Data, 253 Read PID Control Parameters 1, 260 Read PID Control Parameters 2, 262 Read Program Parameters, 270 Read PV Data, 251 Read SP Data, 252 Read Time Signal, 247 Remote Setting Mode, 273 Reset (Stop), 276 Run Command, 275 Write Adjustment Parameters, 259 Write Local SP, 269 Write PID Control Parameters 1, 264 Write PID Control Parameters 2, 266 Write Program Parameters, 272 sequences, Hayes Modem AT Command Data Send/Receive (General-purpose), 408 Dial, 406 Escape, 409 Escape to Hang Up, 403 Hang Up, 409 Initialize and Dial, 403 Initialize Modem (Specialized), 405 Password, 407 Set Modem (General-purpose), 405 415 Index sequences, K3T Intelligent Signal Processor General-purpose Command, 303 Model Data Read (by Unit Number), 301 Model Data Read (Continuous Units), 302 Read Display Value (PV) (by Unit Number), 299 Read Display Value (PV) (Continuous Units), 301 Read Holding Data, 297 Read Holding Data BH (Continuous Units), 299 Read Holding Data PH (Continuous Units), 298 Read Set Value (by Unit Number), 293 Read Set Value H (Continuous Units), 294 Read Set Value H with Bank (Continuous Units), 296 Read Set Value HH (Continuous Units), 294 Read Set Value HH with Bank (Continuous Units), 296 Read Set Value L (Continuous Units), 294 Read Set Value L with Bank (Continuous Units), 296 Read Set Value LL (Continuous Units), 294 Read Set Value LL with Bank (Continuous Units), 296 Read Set Value O1 with Bank (Continuous Units), 297 Read Set Value O2 with Bank (Continuous Units), 297 Read Set Value O3 with Bank (Continuous Units), 297 Read Set Value O4 with Bank (Continuous Units), 296 Read Set Value O5 with Bank (Continuous Units), 296 Read Set Value with Bank (by Unit Number), 295 Reset (by Unit Number), 288 Reset Control (Continuous Units), 288 Write Set Value (by Unit Number), 289 Write Set Value H (Continuous Units), 290 Write Set Value H with Bank (Continuous Units), 292 Write Set Value HH (Continuous Units), 289 Write Set Value HH with Bank (Continuous Units), 291 Write Set Value L (Continuous Units), 290 Write Set Value L with Bank (Continuous Units), 292 Write Set Value LL (Continuous Units), 290 Write Set Value LL with Bank (Continuous Units), 292 Write Set Value O1 with Bank (Continuous Units), 293 Write Set Value O2 with Bank (Continuous Units), 293 Write Set Value O3 with Bank (Continuous Units), 292 Write Set Value O4 with Bank (Continuous Units), 292 Write Set Value O5 with Bank (Continuous Units), 292 Write Set Value with Bank (by Unit Number), 290 sequences, V500/V520 Bar Code Reader BCR Connection Confirmation (V500), 313 BCR Function Read (V500), 311 BCR Function Write (V500), 310 BCR Initialize (V500), 314 BCR Read Start, 309 BCR Read Stop, 309 Complete Data Read, 309 Data Continuous Read (Interrupt) (V500), 314 Data Continuous Read (Interrupt) (V520), 315 Data Continuous Read (Scan) (V500), 314 Data Continuous Read (Scan) (V520), 314 Data Read, 309 General-purpose Command 1, 315 General-purpose Command 2, 315 Log Data Clear (V500), 314 Log Data Output Request (V500), 312 Preset Data Set (V500), 313 System Setting, 308 416 sequences, V600/V620 ID Controller Auto-read (ASCII/1), 382 Auto-read (Hexadecimal/1), 383 Auto-write (ASCII/1), 395 Auto-write (Hexadecimal/1), 395 Command Processing Cancel, 400 Control, 399 Data Check, 398 Error Information Read, 400 General-purpose Command, 402 Polling Auto-read (ASCII), 383 Polling Auto-read (ASCII/2), 384 Polling Auto-read (ASCII/4), 384 Polling Auto-read (ASCII/4), 384 Polling Auto-read (Hexadecimal), 385 Polling Auto-read (Hexadecimal/2), 385 Polling Auto-read (Hexadecimal/4), 386 Polling Auto-read (Hexadecimal/8), 386 Polling Auto-read Command Processing Cancel, 401 Polling Auto-write (ASCII/2), 395 Polling Auto-write (ASCII/4), 396 Polling Auto-write (ASCII/8), 396 Polling Auto-write (Hexadecimal/2), 397 Polling Auto-write (Hexadecimal/4), 397 Polling Auto-write (Hexadecimal/8), 398 Polling Auto-write Command Processing Cancel, 401 Polling Auto-write Subcommand (ASCII/2), 396 Polling Auto-write Subcommand (ASCII/4), 396 Polling Auto-write Subcommand (ASCII/8), 396 Polling Auto-write Subcommand (Hexadecimal/2), 397 Polling Auto-write Subcommand (Hexadecimal/4), 397 Polling Auto-write Subcommand (Hexadecimal/8), 398 Read (ASCII/1), 374 Read (ASCII/2), 375 Read (ASCII/4), 376 Read (ASCII/8), 377 Read (Hexadecimal/1), 378 Read (Hexadecimal/2), 379 Read (Hexadecimal/4), 380 Read (Hexadecimal/8), 381 Write (ASCII/1), 386 Write (ASCII/2), 387 Write (ASCII/4), 389 Write (ASCII/8), 390 Write (Hexadecimal/1), 391 Write (Hexadecimal/2), 392 Write (Hexadecimal/4), 393 Write (Hexadecimal/8), 394 Index sequences, Visual Inspection System Arbitrary Measurement Value Acquisition (F200), 355 Binary Level Modification (F200/300), 364 Camera Change (Decrease by 1) (F200/300), 363 Camera Change (Increase by 1) (F200/300), 364 Camera Designation and Positioning (F350), 362 Character String Inspection and Character Inspection (F350), 363 Continuous Measurement Execution (Interrupt) (F200), 353 Continuous Measurement Execution (Interrupt) (F300), 359 Continuous Measurement Execution (Scan) (F200), 352 Continuous Measurement Execution (Scan) (F300), 357 Evaluation Condition Change (F200), 354 General-purpose Command (Send), 365 General-purpose Command (Send/Receive), 365 Illumination Fluctuation Follow Execution (F300), 361 Inspection Execution and Character Inspection (F350), 363 Measurement Execution (F200), 352 Measurement Execution (F300), 356 Measurement Execution and Positioning (F350), 361 Measurement, Inspection Termination, 365 Reference Object Registration (Criterion) (F200), 354 Reference Object Registration (Group) (F200), 354 Reference Object Registration (Reference Position) (F200), 354 Reference Object Registration Command 1 Execution (F300), 360 Reference Object Registration Command 2 Execution (F300), 361 Reset (F200/300), 364 Scene Switching (Arbitrary), 365 Scene Switching (Decrease by 1), 364 Scene Switching (Increase by 1), 364 Scene Switching and Positioning (F350), 362 Serial Communications Boards error information, 121 installation, 14 replacement, 132 specifications, 8 serial communications modes 1:1 Data Link, 3, 4, 6, 108 1:1 NT Link, 3, 4, 7 1:N NT Link, 3, 4, 7 Host Link, 3, 4, 5, 34 no-protocol, 2, 3, 4, 6, 98 NT Link, 114 protocol macro, 3, 4, 5, 58 setting, 29 settings See also PC Setup flags and control bits, 27 switches, 13 soldering, 25 specifications, Serial Communications Boards, 8 standard system protocols, 63, 135 communications problems, 79 examples, 78 modifying, 64 step parameters, 78 switches, 13 synchronization RS-232C ports, 11 RS-422A/485 ports, 12 SYSMAC WAY. See Host Link T Temperature Controllers, 5 terminating resistance switch, 13 trace function, protocol macros, 63 troubleshooting, 119, 121 1:N NT Link errors, 129 Host Link errors, 121 protocol macro errors, 125 TXD(––) instruction, 34, 102, 104 Host Link, 36 V V500/V520 Bar Code Reader, 63 connections, 307 protocols, sequences, 305–316 V600/V620 ID Controller, 63 connections, 369 protocols, sequences, 367–402 Visual Inspection System connections, 351 protocols, sequences, 349–366 Visual Inspection Units, 63 W weight, 8 wiring, 17 connectors, 23 precautions, 18 RS-232C ports, 20 RS-422A/485 ports, 21 417 Revision History A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. W365-E1-1 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. Revision code 1 Date September 1999 Revised content Original production 419 Authorized Distributor: Cat. No. W365-E1-1 Note: Specifications subject to change without notice. Printed in Japan ">
Download
Advertisement
Key features
Provides both RS-232C and RS-422A/485 serial communication ports.
Supports Host Link, protocol macro, no-protocol, and NT Link communication modes.
Enables connection to host computers, Programmable Terminals (PTs), and other external devices.
Integrates custom protocols using CX-Protocol for general-purpose device communication.
Frequently asked questions
The Serial Communications Board can be installed in Inner Board slot 1 of a CQM1H-series CPU Unit.
The Serial Communications Board supports Host Link, protocol macro, no-protocol, 1:1 Data Links, 1:N-mode NT Link, and 1:1-mode NT Link modes.
Protocol macros allow the creation of custom data transfer procedures (protocols) with external devices using the CX-Protocol to match the communications specifications of those devices.
No-protocol communications are suitable for communications with devices that only send or receive data, such as bar code readers or printers.
Up to eight PTs can be connected to a PC using the 1:N NT Link mode.