Omron CQM1H -SCB41 Serial Communications Board Operation Manual
Below you will find brief information for Serial Communications Board CQM1H CQM1H-SCB41. The CQM1H-SCB41 is an Inner Board for the CQM1H-series PCs that provides two serial communications ports for connecting host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Consoles). This makes it possible to easily increase the number of serial communications ports for a CQM1H-series PC. The Board supports protocol macros (which are not supported by the ports built into the CPU Units), allowing easy connection to general-purpose devices that have a serial port.
Advertisement
Advertisement
Cat. No. W365-E1-02
SYSMAC
CQM1H Series
CQM1H-SCB41
Serial Communications Board
OPERATION MANUAL
SYSMAC
CQM1H Series
CQM1H-SCB41
Serial Communications Board
Operation Manual
Revised April 2002
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!Caution
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1,2,3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xi
3
4
1
2
5
6
Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xii xii xii xiii xiii xv
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Protocol Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
8
2
4
SECTION 2
Board Components and Installation . . . . . . . . . . . . . . . . . . .
9
2-1 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
14
17
SECTION 3
Default Settings and Related Bits/Flags . . . . . . . . . . . . . . . .
27
3-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
28
30
SECTION 4
Host Link Communications. . . . . . . . . . . . . . . . . . . . . . . . . .
33
4-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Application Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 Changes from Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
36
39
45
53
SECTION 5
Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
5-1 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Restrictions in Using the CX-Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Application Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Protocol Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7 Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
65
66
70
76
80
84
SECTION 6
No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . .
99
6-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Application Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Using No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100
102
103
104
vii
viii
TABLE OF CONTENTS
SECTION 7
Communications for 1:1 Data Links. . . . . . . . . . . . . . . . . . . 109
7-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Application Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Using 1:1 Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
110
111
112
113
SECTION 8
NT Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
8-1 Overview of NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Application Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
116
118
119
SECTION 9
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . . . 121
9-1 Front-panel Indicator Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 Cleaning and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-4 Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122
124
133
135
Appendices
C
@K Digital Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D
@K Digital Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G
@J Temperature Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H
@ Digital Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I
231
245
285
155
173
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
About this Manual:
This manual describes the installation and operation of the SYSMAC CQM1H-series CQM1H-SCB41
Serial Communications Board and includes the sections described below.
The Serial Communications Board is classified as an Inner Board.
Read this manual and all related manuals listed in the following table carefully and be sure you understand the information provided before attempting to install and operate a Serial Communications
Board.
Name
SYSMAC CQM1H-series
CQM1H-SCB41
Serial Communications Board
Operation Manual
Cat. No.
W365-E1-1
W363-E1-1
Contents
Describes the use of the Serial Communications Board to perform serial communications with external devices, including hardware and the usage of standard system protocols for
OMRON products.
Host Link communications commands are described in the
SYSMAC CQM1H-series Programmable Controllers Pro-
gramming Manual (W364).
Creating protocol macros is described in the CX-Protocol
Operation Manual (W344).
Describes the installation and operation of the CQM1Hseries PCs.
SYSMAC CQM1H-series
Programmable Controllers
Operation Manual
SYSMAC CQM1H-series
Programmable Controllers
Programming Manual
SYSMAC WS02-PSTC1-E
CX-Protocol Operation Manual
W364-E1-1
W344-E1-1
Describes the ladder diagram programming instructions supported by CQM1H-series PCs, Host Link commands, and other programming information.
Describes the use of the CX-Protocol to create protocol macros as communications sequences to communicate with external devices.
Section 1 introduces the hardware and software functions of the Serial Communications Board, including the serial communications modes, system configurations, and specifications.
Section 2 describes the components of the Serial Communications Board, how to connect it in the
CPU Unit, and how to connect it to external devices.
Section 3 describes the settings, control bits, flags, and status information available in the CPU Unit for use with the Serial Communications Board.
Section 4 describes the procedure and other information required to use Host Link communications.
Section 5 describes the procedure and other information required to use protocol macros.
Section 6 provides information required to use no-protocol communications on a Serial Communications Board port.
Section 7 provides information required to create 1:1 data links through a Serial Communications
Board port.
Section 8 describes the procedure and other information required to use 1:N-mode and 1:1-mode NT
Links to Programmable Terminals (PTs).
Section 9 describes the troubleshooting and maintenance procedures for the Serial Communications
Boards.
Appendix A to Appendix N provide the specifications of the standard system protocols.
!WARNING
Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
x
PRECAUTIONS
This section provides general precautions for using the Serial Communications Boards.
The information contained in this section is important for the safe and reliable application of the Serial
Communications Boards and the PC in general. You must read this section and understand the information contained before attempting to set up or operate a PC system containing a Serial Communications Board.
Operating Environment Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conformance to EC Directives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Applicable Directives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xi
Intended Audience
1
2
3
1
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!WARNING
It is extremely important that a Serial Communications Board and all related units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a Serial Communications Board to the above mentioned applications.
Safety Precautions
!WARNING
Never attempt to disassemble any Units while power is being supplied. Doing so may result in electric shock.
!WARNING
The CPU Unit refreshes I/O even when the program is stopped (i.e., even in
PROGRAM mode). Confirm safety thoroughly in advance before changing the status of any part of memory allocated to I/O Units, Inner Boards, or Dedicated I/O Units. Any changes to the data allocated to any Unit may result in unexpected operation of the loads connected to the Unit. Any of the following operation may result in changes to memory status.
• Transferring I/O memory data to the CPU Unit from a Programming
Device.
• Changing present values in memory from a Programming Device.
• Force-setting/-resetting bits from a Programming Device.
• Transferring I/O memory files from a Memory Card or EM file memory to the CPU Unit.
• Transferring I/O memory from a host computer or from another PC on a network.
!WARNING
Never touch any of the terminals while power is being supplied. Doing so may result in electric shock.
!Caution
Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, input signals may not be read properly.
xii
Operating Environment Precautions
4
5
4
Operating Environment Precautions
!Caution
Do not operate the control system in the following locations:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!Caution
Take appropriate and sufficient countermeasures when installing systems in the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
!Caution
The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC
System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
Application Precautions
Observe the following precautions when using the PC.
!WARNING
Failure to abide by the following precautions could lead to serious or possibly fatal injury. Always heed these precautions.
• Always ground the system to 100
Ω
or less when installing the system to protect against electrical shock.
• Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
• Mounting or dismounting a Power Supply Unit, I/O Unit, CPU Unit, or
Memory Cassette.
• Assembling the Units or mounting the Serial Communications Board.
• Setting DIP switches or rotary switches.
• Connecting or wiring the cables.
• Connecting or disconnecting the connectors.
!Caution
Failure to abide by the following precautions could lead to faulty operation or the PC or the system or could damage the PC or PC Units. Always heed these precautions.
• Do not turn OFF the power supply while transferring protocol macro data.
xiii
Application Precautions
5
• Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
• Always discharge static electricity by touching a grounded metal part before mounting the Serial Communications Board.
• Always discharge static electricity by touching a grounded metal part before connecting cable connectors to RS-232C or RS-422A/485 port of the Serial Communications Board.
• Be sure that the connectors, terminal blocks, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
• Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PC.
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
• Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
• Confirm polarities before connecting RS-422A/485 cables. Some devices require that SDA/B and RDA/B or signal polarities be reversed.
• Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning.
• Check the user programming (ladder program, protocol macro data, etc.) for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation.
• Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation.
• Circuit boards have sharp or pointed edges, such as those on the leads of electrical parts. Do not touch the back of printed boards or mounted sections with your bare hands.
• Connect or set terminating resistance correctly when using RS-422A/485 cables.
• During transportation and storage, cover the circuit boards with conductive materials to prevent them from being damaged by static electricity caused by LSIs or ICs and keep them within the specified storage temperature.
• Refer to Section 2 Board Components and Installation and correctly wire and install the Units.
• Do not attempt to take any Units apart, to repair any Units, or to modify any Units in any way.
• Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning.
xiv
Conformance to EC Directives
6
6
6-1
6-1-1
6-1-2
6-1-3
Conformance to EC Directives
Applicable Directives
• EMC Directives
• Low Voltage Directive
Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related
EMC standards so that they can be more easily built into other devices or machines. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel in which the OMRON devices are installed.
The customer must, therefore, perform final checks to confirm that devices and the overall machine conform to EMC standards.
Note Applicable EMC (Electromagnetic Compatibility) standards are as follows:
EMS (Electromagnetic Susceptibility): EN61131-2
EMI (Electromagnetic Interference): EN50081-2
(Radiated emission: 10-m regulations)
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC or 75 to
1,500 VDC meet the required safety standards for the PC (EN61131-2).
Conformance to EC Directives
The CQM1H-series PCs comply with EC Directives. To ensure that the machine or device in which a CQM1H-series PC is used complies with EC directives, the PC must be installed as follows:
1,2,3...
1.
The PC must be installed within a control panel.
2.
Reinforced insulation or double insulation must be used for the DC power supplies used for the I/O power supplies.
3.
PCs complying with EC Directives also conform to the Common Emission
Standard (EN50081-2). When a PC is built into a machine, however, noise can be generated by switching devices using relay outputs and cause the overall machine to fail to meet the Standards. If this occurs, surge killers must be connected or other measures taken external to the PC.
The following methods represent typical methods for reducing noise, and may not be sufficient in all cases. Required countermeasures will vary depending on the devices connected to the control panel, wiring, the configuration of the system, and other conditions.
EMI Measures
The CQM1H-series PCs conform to the Common Emission Standards
(EN50081-2) of the EMC Directives. However, the noise generated from
Serial Communications Board communications cables may not satisfy these standards. In such a case, commercially available ferrite cores must be placed on the communications cable or other appropriate countermeasures must be provided external to the PC.
xv
Conformance to EC Directives
Recommended Ferrite Cores
The following ferrite core (data line noise filter) is recommended:
0443-164151 by Fair-Rite Products Corp.
Low impedance, 25 MHz: 90
Ω
, 100 MHz: 160
Ω
6
Recommended Mounting Method
Mount the core on one turn of the communications cable, as shown in the following illustration.
Mount the cores as closely to the end of the communications cable as possible, as shown in the following illustration.
Serial
Communications
Board
xvi
SECTION 1
Introduction
This section introduces the hardware and software functions of the Serial Communications Board, including the serial communications modes, system configurations, and specifications.
1-1-1 Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-2 Serial Communications Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-4 System Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-5 Mounting Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-1 Host Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-3 No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-4 PC 1:1 Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-5 NT Links — 1:N Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-6 NT Links — 1:1 Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-2 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
2
Overview
Section 1-1
1-1 Overview
1-1-1 Model Number
Name Model Specifications
Serial Communications Board CQM1H-SCB41 One RS-232 port
One RS-422A/485 port
1-1-2 Serial Communications Boards
The Serial Communications Board is an Inner Board for the CQM1H-series
PCs. One Board can be installed in Inner Board slot 1 of a CQM1H-series
CPU Unit. The Board cannot be installed in slot 2.
The Board provides two serial communications ports for connecting host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Consoles). This makes it possible to easily increase the number of serial communications ports for a
CQM1H-series PC.
Port 1: RS-232C
Port 2: RS-422A/485
1-1-3 Features
The Serial Communications Board is an option that can be mounted in the
CPU Unit to increase the number of serial ports without using an I/O slot. It supports protocol macros (which are not supported by the ports built into the
CPU Units), allowing easy connection to general-purpose devices that have a serial port.
Inside controlled machine
Serial Communications Board
RS-232C
RS-422A/485
Temperature controller or other device
OR
Bar code reader or other device
Dedicated controller or other device
External device with RS-232C or
RS-422A/485 port
Both RS-232C and RS-422A/485 ports are provided. The RS-422A/485 port enables 1:N connections to general-purpose external devices without going through Converting Link Adapters. The 1:N connections can be used with protocol macros or 1:N-mode NT Links.
Overview
Section 1-1
1-1-4 System Configuration
The following serial communications modes are supported by the Serial Communications Board: Host Link (SYSMAC WAY), protocol macro, no-protocol,
1:1 Data Links, 1:N-mode NT Link, and 1:1-mode NT Link modes. The devices shown in the following diagram can be connected.
Note The 1:1-mode NT Link and 1:N-mode NT Link communications modes use different protocols that are not compatible with each other.
General-purpose external device
Programmable
Terminal (PT)
C-series PC
Programming
Device
(excluding
Programming
Console)
Host computer
Protocol macros
NT Link
No-protocol
1:1
Data Link
Host Link
Host Link
RS-232C CQM1H-series CPU Unit
Serial Communications Board
RS-422A/485
General-purpose external device
Programmable
Terminal (PT)
Protocol macros
NT Link
C-series PC
1:1
Data Link
Programming
Device
(excluding
Programming
Console)
Host computer
Host Link
No-protocol
Host Link
Note An NT-AL001-E Converting Link Adapter can be used to convert between RS-
232C and RS-422A/485. This Link Adapter requires a 5-V power supply.
Power is provided by the RS-232C port on the Serial Communications Board when the Link Adapter is connected to it, but must be provided separately when connecting the Link Adapter to other devices.
3
Protocol Overview
Section 1-2
1-1-5 Mounting Location
The Serial Communications Board can be installed in Inner Board slot 1 of a
CQM1H-series CPU Unit. The Board cannot be installed in slot 2.
Serial Communications Board
4
1-2 Protocol Overview
The following six serial communications modes can be used as required for each serial communications port on the Serial Communications Board.
• Host Link:
For connections to host computers, personal computer peripheral devices, or Programmable Terminals
• Protocol Macros:
For communications with general-purpose external devices using protocols
• No-protocol:
For connections to general-purpose devices for no-protocol communications using TXD(
) and RXD(
) instructions
• 1:1 Data Links:
For 1:1 data links with a C-series PC, including another CQM1H
• 1:N-mode NT Link:
For communications with one or more Programmable Terminals (PTs)
• 1:1-mode NT Link:
For communications with one PT
Communications Ports and Serial Communications Modes
Board Port
Peripheral bus or
Programming
Console bus
No
Host Link
(SYSMAC
OK
WAY)
OK
Serial communications mode
Protocol macro
No- protocol
1:1 Data
Link
OK OK Serial
Communications
Boards
RS-232C
(port 1)
RS-422A/
485 (port 2)
No OK (See note 1.)
OK OK (See note 1.)
OK (See note 1.)
1:N-mode
NT Link
1:1-mode
NT Link
OK (See note 2.)
OK (See note 2.)
OK (See note 2.)
OK (See note 2.)
Note
1.
A 4-wire connection must be used when using Host Link, no-protocol, or
1:1 Data Link communications with an RS-422A/485 connector.
2.
The PT Programming Control functions are not supported.
Connection examples for the serial communications modes are shown in the following sections.
Protocol Overview
Section 1-2
1-2-1 Host Link Mode
In Host Link Mode, C-mode Host Link commands can be sent from a computer, PT, or other host to read or write I/O memory in the PC or to control the
PC’s operating modes.
The TXD(
) instruction can be used to send ASCII data to the host. This is called slave-initiated communications or unsolicited communications.
Note
1.
Programming Devices can also be connected in Host Link mode.
2.
A 4-wire connection must be used when using an RS-422A/485 port.
Sending C-mode Host Link Commands
Host computer
Serial Communications Board
Response
Host Link command
Slave-initiated Communications
Host computer
TXD(
)
Data
PC initiates communication.
CQM1H
Serial Communications Board
1-2-2 Protocol Macros
Data transfer procedures (called protocols) with general-purpose external devices can be created as macros using the CX-Protocol to match the communications specifications of the external device (but, half-duplex communications and start-stop synchronization must be used).
These protocols are stored in the Serial Communications Boards from the
CX-Protocol, and enable data to be exchanged with general-purpose external devices simply by executing the PMCR(
) instruction in the CPU Unit.
Standard system protocols for exchanging data with OMRON devices (such as Temperature Controllers, Intelligent Signal Processors, Bar Code Readers, and Modems) are provided as a standard feature in the Serial Communications Boards and the CX-Protocol. The CX-Protocol can also be used to change the standard system protocols according to user requirements.
Serial Communications Board
PMCR
(
)
CQM1H
External device with RS-232C port
Message
RS-232C
Protocol made specifically for the required communications specifications
Note There are some restrictions in using the CX-Protocol to manipulate protocols or perform other operations for the CQM1H-series Serial Communications
Board. These restrictions are described below.
5
Protocol Overview
Section 1-2
• Pin 8 on the DIP switch on the front of the CQM1H-series CPU Unit must be turned ON to use the CX-Protocol. While pin 8 is ON, you will not be able to use any of the CPU Unit or Board ports for the CX-Programmer,
SYSMAC-CPT, or SYSMAC Support Software.
• The model of PC must be set to the C200HG and the model of CPU Unit must be set to the CPU43.
• Refer to 5-2 Restrictions in Using the CX-Protocol for further details.
1-2-3 No-protocol Communications
The TXD(
) and RXD(
) instructions can be used in the ladder program to send and receive data without conversion through the RS-232C port to and from an external device.
A start code can be sent before the data and an end code can be sent after it.
Alternately, the amount of data being sent can be specified. A communications frame, however, cannot be created according to the specifications of the partner device, providing less flexibility than protocol macros. Retry processing, data form conversions, controlling processing based on a response, and other communications procedures cannot be performed.
No-protocol communications are suitable for communications with bar code readers and other devices that only send data or printers and other devices that only receive data.
Note A 4-wire connection must be used when using an RS-422A/485 port.
Serial Communications Board
TXD(
) or
RXD(
)
CQM1H
External device with RS-232C port
RS-232C
OR
Data only
1-2-4 PC 1:1 Data Links
Two PCs can be connected via RS-232C cable to create a data link between them of up to 64 words in the LR area. The link words written by one PC are automatically transferred to the other PC for reading.
One of the following three ranges of words can be set to be linked:
LR 00 to LR 63, LR 00 to LR 31, or LR 00 to LR 15
A 1:1 Data Link communications system can be created between the CQM1H and another CQM1H, or between the CQM1H and the CQM1, C200HX/HG/
HE, C200HS, CPM1, CPM1A, CPM2A, CPM2C, or SRM1(-V2).
6
Protocol Overview
Section 1-2
Note A 4-wire connection must be used when using an RS-422A/485 port.
Serial Communications Board
CQM1H
CQM1H or other C-series PC
RS-232C
LR 00 to
LR 31
LR 32 to
LR 63
Master PC
Master area
(sent)
Slave area
(received)
LR 00 to
LR 31
LR 32 to
LR 63
Slave PC
Master area
(received)
Slave area
(sent)
1-2-5 NT Links — 1:N Mode
A PC can be connected to one or more Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PC is allocated to the Status Control Areas and the Status Notification Areas used by the PTs, as well as to display objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PC to be controlled and monitored by operations from the PTs, without the use of a ladder diagram programming in the PC. Up to eight PTs can be connected to a PC.
Note The user does not need to be aware of NT Link commands. The user only has to allocate the PC memory to the PTs.
Serial Communications Board
CQM1H
1:1
Serial Communications Board
CQM1H
1:N
RS-422A/485
PT
PT PT
1-2-6 NT Links — 1:1 Mode
The functionality of the 1:1 mode is the same as that of the 1:N mode, but only a 1:1 connection is possible. The 1:1 and 1:N modes are not compatible as protocols.
Serial Communications Board
CQM1H
1:1
PT
7
8
Specifications
Section 1-3
1-3 Specifications
1-3-1 Serial Communications Board
Device name
Model number
Classification
Supporting CPU Units
Number of mountable Boards/PC and mounting location
Serial communications ports
Port 1
Port 2
Protocols Port 1
Port 2
Software interface with CPU Unit
PC Setup settings
Current consumption (See note.)
Dimensions
Weight
Standard accessories
Serial Communications Board
CQM1H-SCB41
CQM1H-series Inner Board
CQM1H-CPU51/61
One Board per PC maximum, must be in Inner Board slot 1
RS-232C
RS-422A/485
Host Link, protocol macro, no-protocol, 1:1 Data Link, 1:N-mode NT Link or 1:1-mode NT Link can be selected for each port.
IR 200 to IR 207 (words for Inner Board slot 1)
DM 6550 to DM 6559 (in read-only DM area in CPU Unit)
Set from Programming Device
200 mA max. at 5 V DC
25
×
110
×
107 (mm) (W
×
H
×
D)
90 g max.
Socket: XM2SA-0901 (OMRON) (two included)
Hood: XM2SA-0911-E (OMRON) (two included, ESD compatible)
Note The current consumption is for one Serial Communications Board. Power is supplied from the CQM1H
When an NT-AL001-E Link Adapter is connected to the Serial Communications Board, power is supplied to the Link Adapter from the Board. A current consumption of 150 mA must be added for each Link Adapter that is connected. In the above specifications, “x” indicates that 150 mA must be added for each port to which an NT-AL001-E Link Adapter is connected to provide the required 5-V power supply.
1-3-2 General Specifications
Conform to SYSMAC CQM1H-series CPU Unit specifications.
1-4 Basic Operating Procedure
An overview of the basic operating procedure is provided here. Details are provided in sections 4 to 8 of this manual according to the serial communications mode.
1,2,3...
1.
Turn OFF the power supply to the PC.
2.
Mount the Board.
3.
Connect the Board and the external device(s).
4.
Turn ON the power supply to the PC.
5.
Set the PC Setup settings from a Programming Device (e.g., Programming
Console or CX-Protocol).
6.
Execute communications.
Use the control bits, flags, and words allocated in the IR area in the ladder program to control communications.
SECTION 2
Board Components and Installation
This section describes the components of the Serial Communications Board, how to connect it in the CPU Unit, and how to connect it to external devices.
2-1 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 RS-422A/485 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Mounting the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 External Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-3 Mounting Height and Connector Cover Dimensions . . . . . . . . . . . .
2-2-4 Precautions in Handling the Board . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-2 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-3 Reducing Electrical Noise for External Wiring . . . . . . . . . . . . . . . .
2-3-4 Port Applicability and Restrictions for 2-Wire/4-Wire Connections
2-3-5 Recommended RS-232C Wiring Examples . . . . . . . . . . . . . . . . . . .
2-3-6 Recommended RS-422A/485 Wiring Examples . . . . . . . . . . . . . . .
2-3-7 Wiring Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-9 Assembling Connector Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-10 Connecting to the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Component Names and Functions
Section 2-1
2-1 Component Names and Functions
The components of the Serial Communications Board are described in this section.
Serial Communications Board
(Inner Board slot 1)
Terminating resistance switch
2-wire or 4-wire switch
Port 1:
RS-232C
Applicable Connectors
Socket: XM2SA-0901 (OMRON)
Hood: XM2SA-0911-E (OMRON)
(Two of each are included with the Board)
Port 2:
RS-422A/485
2-1-1 Indicators
Board Indicators
RDY
COMM1
COMM2
There are three LED indicators on the Board, as described below.
RDY: Lit when the Board is operational (green)
COMM1: Lit when data is being sent or received on the RS-232C port (Yellow)
COMM2: Lit when data is being sent or received on the RS-442A/485 port (Yellow)
Indicator Color
RDY
Green Lit
Status
COMM1
COMM2
Flashing
Not lit
Yellow Flashing
Not lit
Yellow Flashing
Not lit
Meaning
Operating normally, and protocol macro preparations have been completed.
There is an error in the PC Setup settings for the
Board or in the protocol macros contained in the
Board.
A hardware error has occurred in the Board.
Port 1 is being used for sending or receiving.
Port 1 is not being used for sending or receiving.
Port 2 is being used for sending or receiving.
Port 2 is not being used for sending or receiving.
10
Component Names and Functions
Section 2-1
CPU Unit Indicators
A Serial Communications Board is mounted as an Inner Board in the CPU
Unit and thus affects the CPU Unit ERR/ALM indicator.
Indicator Color
ERR/ALM
Red Lit
Status
Flashing
Not lit
Meaning
Fatal error If a fatal error occurs, the CPU
Unit will stop operation in either
RUN or MONITOR mode.
Non-fatal error
Normal operation
If a non-fatal error occurs, the
CPU Unit will continue operation in either RUN or MONI-
TOR mode.
The CPU Unit is operating normally. This indicator will also not be lit when a watchdog timer error occurs.
If an error in the Inner Board is the cause of the error indicated on the ERR/
ALM indicator, the Inner Board Error Flag (SR 25415) will turn ON and information on the error will be stored in AR 0400 to AR 0407. Refer to SECTION
9 Troubleshooting and Maintenance for details.
2-1-2 RS-232C Port
Protocol
Communications method
Synchronization
Baud rate
Host Link
Half-duplex
No-protocol Protocol macros
Start-stop synchronization (asynchronous)
1,200/2,400/4,800/9,600/ 19,200 bps
Connections
1:1
(1:N possible using Converting Link Adapters)
1:1 Data Links
19,200 bps
1:1
1:N NT Links 1:1 NT Links
38,400 bps
1:1
(1:N possible using
Link Adapters)
19,200 bps
1:1
Transmission distance
Interface
15 m max. (See note.)
Complies with EIA RS-232C
Note The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
Connector Pin Layout
Note
7
8
3
4
Pin No.
1 (See note 1.)
2
5
6 (See note 2.)
9
Shell (See note 1.)
Abbreviation
FG
SD
RD
RTS (RS)
CTS (CS)
5V
DSR (DR)
DTR (ER)
SG
FG
Signal name
Shield
Send data
Receive data
Request to send
Clear to send
Power supply
Data set ready
Data terminal ready (See note 4.)
Signal ground
Shield
---
Output
Input
Output
Input
---
Input
Output
---
---
I/O
1.
Pin No. 1 and the shell are connected to the ground terminal (GR) of the
Power Supply Unit inside the Serial Communications Board. Therefore, the cable shield can be grounded by grounding GR of the Power Supply Unit.
2.
Pin 6 (5 V) is required when the NT-AL001-E Link Adapter is connected.
For details on connection methods, refer to 2-3 Wiring.
11
Component Names and Functions
Section 2-1
!Caution
Do not connect the 5-V power supply of pin 6 to any external device other than an NT-AL001-E Link Adapter. Otherwise, the external device and the
Serial Communications Board may be damaged.
Applicable Connectors
Recommended Cables
The following cables are provided for connection to NT-AL001-E Link Adapters. We recommend that these cables be used.
NT-AL001-E connecting cables: XW2Z-070T-1 (0.7 m)
XW2Z-200T-1 (2 m)
Socket: XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0911-E (OMRON, conforms to ESD) or equivalent
One Socket and one Hood are provided for each port.
UL2464 AWG28
×
5P IFS-RVV-SB (UL-approved, Fujikura Ltd.)
AWG28
×
5P IFVV-SB (not UL-approved, Fujikura Ltd.)
UL2464-SB (MA) 5P
×
28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.)
CO-MA-VV-SB 5P
×
28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.)
Cable length: 15 m max.
2-1-3 RS-422A/485 Port
Protocol
Communications method
4-wire, 1:1
4-wire, 1:N
2-wire, 1:1
2-wire, 1:N
Synchronization
Host Link
Half-duplex
OK
OK
No
No
No-protocol
OK
OK
No
No
Protocol macros
OK
OK
OK
OK
Start-stop synchronous (asynchronous)
1:1 Data Links
OK
No
No
No
OK
OK
OK
OK
1:N NT Links 1:1 NT Links
OK
No
No
No
Baud rate
Connections
Transmission distance
Interface
1,200/2,400/4,800/9,600/ 19,200 bps
1:N (N: 32 Units max.)
19,200 bps
1:1
38,400 bps
1:N (N: 8 Units max.)
19,200 bps
1:1
500 m max.
(The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.)
Complies with EIA RS-485
Connector Pin Layout
Note
Pin No.
1 (See note 1.)
2 (See note 1.)
3
4
5
6 (See note 1.)
7
8 (See note 1.)
NC
RDB
9 NC
Shell (See note 2.) FG
Abbreviation
SDA
SDB
NC
NC
NC
RDA
Signal name
Send data –
Send data +
Not used
Not used
Not used
Receive data –
Not used
Receive data +
Not used
Shield
Output
Output
---
---
---
Input
---
Input
---
---
I/O
1.
When 2-wire connections are used, use pins 1 and 2, or pins 6 and 8.
2.
The shell is connected to the ground terminal (GR) of the Power Supply
Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit.
12
Component Names and Functions
Internal Circuits
The internal circuits for port 2 are shown below.
Section 2-1
Pin 8: RDB (+)
Receiver
Terminating resistance: 200
Ω
Terminating resistance switch
Pin 6: RDA (
−
)
2-wire/4-wire switch
Driver
Pin 2: SDB (+)
Pin 1: SDA (
−
)
!Caution
Confirm polarities before connecting RS-422A/485 cables. Some devices require that SDA/B and RDA/B or signal polarities be reversed.
Applicable Connectors
Recommended Cables
Socket: XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0911-E (OMRON, conforms to ESD) or equivalent
One Socket and one Hood are provided for each port.
CO-HC-ESV-3P
×
7/0.2 (Hirakawa Hewtech Corp.)
Cable length: 500 m max.
(The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.)
2-1-4 Switches
Terminating Resistance
Switch
The TERM and WIRE switches are on the front panel of the Serial Communi-
cations Board. Refer to page page 10 for a diagram of the Board.
When an RS-422/485 port is used, turn ON the switch if the Serial Communications Board is on the end of the transmission line. Refer to information on specific serial communications modes for the ON/OFF settings.
Label
TERM
Name
Terminating resistance switch
Settings
OFF: Terminating resistance
OFF
ON: Terminating resistance
ON
Factory setting
OFF: Terminating resistance OFF
2-Wire or 4-Wire Switch
When an RS-422/485 port is used, set the switch to 2 when 2-wire connections are used, and set the switch to 4 when 4-wire connections are used.
WIRE
Label Name
2-wire or 4-wire switch
Settings
2: 2-wire
4: 4-wire
Factory setting
2: 2-wire
Note Host Link, no-protocol, and 1:1 Data Link modes cannot use 2-wire RS-422A/
485 communications. Always use 4-wire connections when using RS-422A/
485 communications for these serial communications modes. Refer to 2-3
13
Installation
Section 2-2
2-2 Installation
2-2-1 Mounting the Board
This section describes how to mount a Serial Communications Board in Inner
Board slot 1 of a CPU Unit. Slot 1 is the slot on the left. Only one Serial Communications Board can be installed in each CPU Unit.
Note
1,2,3...
1.
The Serial Communications Board cannot be mounted in Inner Board slot
2.
2.
Always turn OFF the power before installing or removing the Serial Communications Board. Installing or removing the Serial Communications
Board with the power ON can cause the CPU Unit to malfunction, damage internal components, or cause communications errors.
3.
Before handling the Serial Communications Board, touch a grounded metallic object in order to discharge any static build-up from your body.
1.
Press the catches at the top and bottom of the Inner Board slot 1 compartment cover.
Press the top catch.
2.
Remove the compartment cover.
Press the bottom catch.
Inner Board Connector
3.
Insert the Serial Communications Board.
14
Installation
2-2-2 External Dimensions
CS1W-SCB41 Mounted in the CPU Unit
Unit: mm
Section 2-2
110
25 107
2-2-3 Mounting Height and Connector Cover Dimensions
When mounting the Serial Communications Board, make sure to provide space for the mounting height and connector cover dimensions shown below.
Serial Communication Unit mounted in the CPU Unit
Connecting Cable connector
223
123
Note The mounting heights shown above are applicable when the attached connectors, connector covers, and recommended cables are used. The mounting height may differ when other connectors, connector covers, and cables are used. Determine the mounting height, taking into account the connectors, connector covers, and the minimum bending radius of the cables.
15
Installation
Section 2-2
2-2-4 Precautions in Handling the Board
• Turn OFF the power supply to the CPU Unit before mounting or removing the Board.
• Turn OFF the power supply to the CPU Unit before connecting or disconnecting Board connectors or wiring.
• Separate the port connector lines from the high-tension or power lines to reduce external noise.
• Leave the port cover attached when not using a communications port.
Port cover
16
Wiring
2-3 Wiring
2-3-1 Connectors
Section 2-3
Prepare connecting cables for port 1 (RS-232C) and port 2 (RS422A/485) using the Sockets and Hoods provided with the Board and the recommended cables.
Connection methods vary with the serial communications mode that is being used. Refer to the following sections for connection examples.
Host Link:
SECTION 4 Host Link Communications
Protocol macros:
SECTION 5 Protocol Macros
No-protocol:
SECTION 6 No-protocol Communications
1:1 Data Links:
NT Links:
SECTION 7 Communications for 1:1 Data Links
SECTION 8 NT Link Communications
Hood
Socket
Standard Connectors (for
Both RS-232C and RS-
422A/485)
Name
Socket
Hood
Model
XM2A-0901 9-pin male
XM2S-0911-E For 9-pin, metric screws, conforms to
ESD
Specifications
Used together (provided with Serial Communications Board).
Recommended Cables
Socket:
XM2A-0901
Hood:
XM2S-0911-E
RS-232C Cables
Model
UL2464 AWG28
×
5P IFS-RVV-SB (UL-approved)
AWG28
×
5P IFVV-SB (not UL-approved)
UL2464-SB (MA) 5P
×
AWG28 (7/0.127) (UL-approved)
CO-MA-VV-SB 5P
×
AWG28 (7/0.127) (not UL-approved)
Manufacturer
Fujikura Ltd.
Hitachi Cable, Ltd.
17
Wiring
Section 2-3
RS422A/485 Cable
Model
CO-HC-ESV-3P
×
7/0.2
Manufacturer
Hirakawa Hewtech Corp.
Refer to pages 11 and 12 for the connector pin layouts. Refer to 2-3-5 Recom-
mended RS-232C Wiring Examples and 2-3-6 Recommended RS-422A/485
Wiring Examples for wiring examples, and to 2-3-7 Wiring Connectors for wir-
ing methods.
Standard cables are available for connection to personal computers and PTs.
Refer to SECTION 4 Host Link Communications for personal computer cables and to your PT user’s manual for PT cables.
2-3-2 Wiring Precautions
• Before connecting or disconnecting the communications cables, always make sure that the PC is turned OFF.
• Tighten the communications connector screws firmly with your fingers.
• Serial Communications Boards can be connected to various devices. For compatibility, refer to the operation manuals for the devices to which they are to be connected.
2-3-3 Reducing Electrical Noise for External Wiring
Observe the following precautions for external wiring.
• When multi-conductor signal cable is being used, avoid using I/O wires and other control wires in the same cable.
• If wiring racks are running in parallel, allow at least 300 mm between the racks.
Low-current cables
Communications cables
300 mm min.
Control cables
PC power supply and general control circuit wiring
Power lines
Power cables
300 mm min.
Ground to 100
Ω
or less.
• If the I/O wiring and power cables must be placed in the same duct, they must be shielded from each other using grounded steel sheet metal.
Communications cables
PC power supply and general control circuit wiring
Power lines
Steel sheet metal
200 mm min.
Ground to 100
Ω
or less.
18
Wiring
Section 2-3
2-3-4 Port Applicability and Restrictions for 2-Wire/4-Wire Connections
The following table shows the port connections that can be used for each serial communications mode.
Serial communications mode
RS-232C port
1:1 1:N 4-wire
RS-422A/485 port
2-wire
1:1 1:N 1:1 1:N
Host Link OK OK (See note 2.)
OK OK No No
Protocol macros
No-protocol
1:1 Data Links
1:N-mode NT Links
1:1-mode NT Links
OK
OK
OK
OK
OK
No
No
OK
OK
OK
OK
OK
OK
OK
No
OK
No
OK
No
No
OK
No
OK
No
No
OK
No
Note
1.
The 1:N connection method can be used by converting between RS-232C and RS-422A/485 through NT-AL001-E Converting Link Adapters.
2.
Use 4-wire connections between the Converting Link Adapters.
3.
The 2-wire RS-422A/485 connections cannot be used for Host Link communications. Use 4-wire connections.
The transmission circuits for 2-wire and 4-wire connections are different, as shown in the following diagram.
Example of 4-Wire Connections
Example of 2-Wire Connections
2/4-wire switch
(DPDT)
Other Unit
Other Unit
2/4-wire switch
(DPDT)
Other Unit
Not connected
Board
Other Unit
Board
NT-AL001-E Link Adapter
Settings
Note
1.
Use the same transmission circuit (2-wire or 4-wire) for all nodes.
2.
Do not use 4-wire connections when the 2/4-wire switch on the Board is set to 2-wire.
The NT-AL001-E Link Adapter has a DIP switch for setting RS-422A/485 communications conditions. When connecting the Board, refer to the DIP switch settings shown in the following table.
19
Wiring
Section 2-3
3
4
1
2
5
6
Pin Function
Not used. Always set this pin to ON.
Built-in terminating resistance setting
ON: Connects terminating resistance.
OFF: Disconnects terminating resistance.
2/4-wire setting
2-wire: Set both pins to ON.
4-wire: Set both pins to OFF.
Transmission mode (See note.)
Constant transmission: Set both pins to OFF.
Transmission performed when CTS signal in RS-
232C interface is at high level: Set pin 5 to OFF and pin 6 to ON.
Transmission performed when CTS signal in RS-
232C interface is at low level: Set pin 5 to ON and pin 6 to OFF.
Factory setting
ON
ON
OFF
OFF
ON
OFF
Note When connecting to a CQM1H-series CPU Unit, turn OFF pin 5 and turn ON pin 6.
2-3-5 Recommended RS-232C Wiring Examples
It is recommended that RS-232C cables be connected as described below, especially when the Serial Communications Board is used in an environment where it is likely to be subject to electrical noise.
1,2,3...
1.
Always use shielded twisted-pair cables as communications cables.
Model
UL2464 AWG28x5P IFS-RVV-SB (UL-approved)
AWG28x5P IFVV-SB (not UL-approved)
UL2464-SB (MA) 5Px28AWG (7/0.127) (UL-approved) CO-
MA-VV-SB 5Px28AWG (7/0.127) (not UL-approved)
Manufacturer
Fujikura Ltd.
Hitachi Cable, Ltd.
Serial
Communications
Board
Pin
Signal
Hood
SD
RD
RTS
CTS
SG
FG
FG
Shield
2.
Combine signal wires and SG (signal ground) wires in a twisted-pair cable.
At the same time, bundle the SG wires to the connectors on the Serial
Communications Board and the remote device.
3.
Connect the shield of the communications cable to the Hood (FG) terminal of the RS-232C connector on the Serial Communications Board. At the same time, ground the ground (GR) terminal of the Power Supply Unit to
100
Ω or less.
4.
A connection example is shown below.
Example: Twisted-pair Cable Connecting SD-SG, RD-SG, RTS-SG, and
CTS-SG Terminals
Actual Wiring Example
SG signal wires
Twist the braided shield to make it thinner and connect to Pin No.
1 (FG). Cover this section with heat-shrink tube to avoid contact with other sections.
Remote device
Signal
RD
SD
CTS
RTS
SG
FG
Bundle the SG wires.
Aluminum foil
XM2S-0911-E
20
Wiring
Section 2-3
Note The Hood (FG) is internally connected to the ground terminal (GR) on the
Power Supply Unit. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit. Although there is conductivity between the
Hood (FG) and pin 1 (FG), connect the Hood (FG) to the shield because the
Hood (FG) has smaller contact resistance with the shield than pin 1 (FG), and thus provides better noise resistance.
Serial Communications Board
Power Supply Unit
Ground to 100
Ω
or less
Hood and GR are internally connected.
Grounding the GR terminal grounds the Hood (FG).
2-3-6 Recommended RS-422A/485 Wiring Examples
Recommended RS-422A/
485 Cable
We recommend the following wiring methods to ensure quality transmissions for RS-422A/485 communications.
1,2,3...
1.
Always use shielded twisted-pair cables for the communications cables.
Model
CO-HC-ESV-3Px7/0.2
Manufacturer
Hirakawa Hewtech Corp.
2.
Connect the shield of the communications cable to the Hood (FG) of the
RS-422A/485 connector on the Serial Communications Board. At the same time, ground the ground (GR) terminal of the Power Supply Unit to
100
Ω or less.
Note Always ground the shield only at the Board end. Grounding both ends of the shield may damage the device due to the potential difference between the ground terminals.
Connection examples are shown below.
2-Wire Connections
Serial Communications
Board
Pin Signal
Remote device
Signal
Hood
Shield
21
Wiring
4-Wire Connections
Serial Communications
Board
Pin Signal
Hood
Shield
Using a 3G2A9-AL001 Link Adapter
Serial Communications
Board
Pin
Signal
3G2A9-AL001
Pin
Signal
RS-422 interface
Signal Pin
Hood
Signal
Pin
Remote device
Signal
Section 2-3
Remote device
Signal
Remote device
Signal
Using an NT-AL001-E RS-232C/RS-422 Link Adapter
Pin
No.
2
3
4
5
8
9
6
7
Hood
Signal
SD
RD
RS
CS
+5V
DR
ER
SG
FG
RS-232C
(See note.)
Shield
Pin
No.
4
5
3
2
6
7
8
9
Hood
Signal
SG
FG
RD
SD
RS
CS
+5V
DR
ER
NT-AL001
Signal
SDA
SDB
RDA
RDB
GRD
Pin
No.
6
5
4
3
1
RS-422
Remote device
Signal
RDA
RDB
SDA
SDB
Remote device
Signal
RDA
RDB
SDA
SDB
FG
Note The following cables are available for this connection.
Length
70 cm
2 m
XW2Z-070T-1
XW2Z-200T-1
Model
It is recommended that one of these cables be used to connect the RS-232C port on the Serial Communications Board to the NT-AL001-E Converting Link
Adapter.
22
Wiring
• Recommended cable (
XW2Z-070T-1S/XW2Z-200T-1) wiring
6
7
4
5
8
9
Shell
Pin
No.
1
2
3
XW2Z@@ OT-1 (10-conductor cable) wiring
SYSMAC side NT-AL001 side (inside NT-AL001)
Signal name
FG
SD
RD
RS
CS
+5V
DR
ER
SG
FG
Pin
No.
Unused
Signal name
1
RD
SD
RS
CS
+5V
DR
ER
SG
FG
6
7
8
4
5
3
2
9
Shell
*Arrows show signal direction
Loopback
Loopback
Shield
Section 2-3
Note
1.
The DS/RS signals are specially wired in the XW2Z@@ OT-1 connecting cable for use with the NT-AL001-E Converting Link Adapter. Do not use this cable for any other purpose. Use with any other equipment may result in malfunction.
2.
The Hood (FG) is internally connected to the ground terminal (GR) on the
Power Supply Unit. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit.
Serial Communications Board
Power Supply Unit
Ground to 100
Ω
or less
Hood and GR are internally connected.
Grounding the GR terminal grounds the Hood (FG).
3.
Be sure to turn ON the terminating resistance at the last Unit at the end of the RS-422A/485 cable.
2-3-7 Wiring Connectors
Use the following steps to wire connectors.
Cable Preparation
See the following diagrams for the length of the cable portion to be cut in each step.
Shield Connected to Hood
(FG)
1,2,3...
1.
Cut the cable to the required length.
23
Wiring
Section 2-3
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield.
25 mm (RS-422A)
40 mm (RS-232C)
3.
Trim off the braided shield using scissors so that the remaining shield length is 10 mm.
10 mm
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
5 mm
5.
Fold back the braided shield.
6.
Wrap aluminum foil tape around the folded shield.
Aluminum foil tape
Shield Not Connected to
Hood (FG)
1,2,3...
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield.
25 mm (RS-422A)
40 mm (RS-232C)
3.
Trim off all the braided shield using scissors.
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
5 mm
24
Wiring
Section 2-3
5.
Wrap adhesive tape around the conductor from which the braided shield was removed.
Adhesive tape
2-3-8 Soldering
1,2,3...
1.
Thread a heat-shrinking tube through each conductor.
2.
Temporarily solder each conductor to the corresponding connector terminals.
3.
Completely solder each conductor.
Soldering iron
Heat-shrinking tube
Inside diameter:
1.5 mm, l = 10
4.
Return the heat-shrinking tube to the soldered portion, then heat the tube to shrink it in place.
Heat-shrinking tube
25
Wiring
2-3-9 Assembling Connector Hood
Assemble the connector Hood as shown below.
Section 2-3
End connected to FG
Adhesive tape
Aluminum foil tape
Grounding plate
2-3-10 Connecting to the Board
Tighten the screws firmly with your fingers.
End not connected to FG
26
SECTION 3
Default Settings and Related Bits/Flags
This section describes the settings, control bits, flags, and status information available in the CPU Unit for use with the Serial Communications Board.
3-3 Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . .
27
Overview
3-1 Overview
Section 3-1
The following settings, control bits, flags, and information are available in the
CPU Unit memory for use with the Serial Communications Board.
Contents
PC Setup settings for the Serial Communications Board
Addresses
Port 1: DM 6555 to DM 6559
Port 2: DM 6550 to DM 6554
Control bits, flags, and status information for the Inner Board slot 1
IR 200 to IR 207
Error flags and information for Inner Boards SR 25415: Inner Board Error Flag
AR 04: Inner Board Error Code
CX-Protocol (for protocol macro mode operation)
CPU Unit
Serial Communications Board
Backup battery
PC Setup settings
(DM 6550 to DM 6559)
Read constantly
Flash memory
Protocol macro data (for protocol macro mode operation)
Inner Board Slot 1
Area
(IR 200 to IR 207) Refreshed
Inner Board Error Flag and Error Code
(SR 25415 and AR 04)
Protocol macro data
3-2 PC Setup Settings
Settings for the Serial Communications Board can be made from a Programming Device in the following words of the PC Setup.
Port 1: DM 6555 to DM 6559
Port 2: DM 6550 to DM 6554
The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed.
The settings in these words depend on the serial communications mode that is being used. Refer to the following sections for details.
Host Link:
SECTION 4 Host Link Communications
Protocol macros: SECTION 5 Protocol Macros
No-protocol:
SECTION 6 No-protocol Communications
1:1 Data Links:
SECTION 7 Communications for 1:1 Data Links
NT Links:
SECTION 8 NT Link Communications
An overview of the PC Setup settings for the Serial Communications Board is given next. The default setting for each word is all zeros (0000).
28
PC Setup Settings
Section 3-2
Word(s)
DM 6550
(port 2)
DM 6555
(port 1)
DM 6551
(port 2)
DM 6556
(port 1)
Bit(s)
00 to 03
04 to 07
08 to 11
Port settings
0: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
1: Settings in DM 6551 (DM 6556 for port 1)
CTS control settings (only port 1 enabled)
0: Disable; 1: Set
Function
Link words for 1:1 Data Link (when bits 12 to 15 are set to 3)
0: LR 00 to LR 63; 1: LR 00 to LR 31; 2: LR 00 to LR 15 or
Maximum Programmable Terminal unit number (when bits 12 to 15 are set to 5)
1 to 7 (BCD)
12 to 15 Serial communications mode
0: Host Link; 1: No-protocol; 2: 1:1 Data Link slave; 3: 1:1 Data Link master;
4: NT Link in 1:1 mode; 5: NT Link in 1:N mode; 6: Protocol macro
00 to 07 Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
08 to 15 Frame format
Start
00: 1 bit
01: 1 bit
02: 1 bit
03: 1 bit
04: 1 bit
05: 1 bit
06: 1 bit
07: 1 bit
08: 1 bit
09: 1 bit
10: 1 bit
11: 1 bit
Length
7 bits
7 bits
7 bits
7 bits
7 bits
7 bits
8 bits
8 bits
8 bits
8 bits
8 bits
8 bits
Stop
1 bit
1 bit
1 bit
2 bit
2 bit
2 bit
1 bit
1 bit
1 bit
2 bit
2 bit
2 bit
Parity
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
00 to 15 Transmission delay
0000 to 9999 (BCD): Set in units of 10 ms, e.g., a setting of 0001 equals 10 ms
Applicable mode
Host Link, noprotocol, protocol macros
Host Link, noprotocol, 1:1
Data Links
1:1 Data Link master (link words) or
NT Link (max. unit number)
All modes
Host Link, noprotocol, protocol macros
Host Link, noprotocol, protocol macros
Host Link, noprotocol
DM 6552
(port 2)
DM 6557
(port 1)
DM 6553
(port 2)
DM 6558
(port 1)
Host Link
No-protocol
DM 6554
(port 2)
DM 6559
(port 1)
00 to 07 Host Link unit number
00 to 31 (BCD)
08 to 11 Start code enable
0: Disable; 1: Set
12 to 15 End code enable
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
00 to 07 Start code (No-protocol)
00 to FF (hexadecimal)
08 to 15 When bits 12 to 15 of DM 6553 or DM 6558 are set to 0 Hex:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
When bits 12 to 15 of DM 6553 or DM 6558 are set to 1 Hex:
End code (No-protocol)
00 to FF (hexadecimal)
No-protocol
No-protocol
No-protocol
29
Control Bits, Flags, and Status Information
Section 3-3
3-3 Control Bits, Flags, and Status Information
Control bits, flags, and status information for the Serial Communications
Board is available in the Inner Board Slot 1 area. The addresses in this area are as follows:
Inner Board Slot 1 Area: IR 200 to IR 207
The following bits are often used in Protocol Macro Mode. Refer to 5-6 Control
Bits, Flags, and Status Information for details.
Word Bits Function Communications modes
All modes IR 200 00 Serial Communications Board Hardware Error Flag
01
02
Board Identification Error Flag (hardware error)
Protocol Data Error Flag
03 to 10 Not used.
11 Port 2 Protocol Macro Execution Error Flag
Protocol macro
12
13
14
15
12
13
Port 1 Protocol Macro Execution Error Flag
Port 2 PC Setup Error Flag
Port 1 PC Setup Error Flag
PC Setup Error Flag
IR 201 00 to 03 Port 1 Error Code
0: Normal operation 1: Parity error
3: Overrun error 4: FCS error
6: Checksum error 7: Command error
04
05
Communications Error Flag
Transmission Enabled Flag
2: Framing error
5: Timeout error
06
07
Turns ON when transmission is enabled, OFF when transmissions are being processed for TXD(
).
Use with flag as an execution condition for TXD(
) when using Noprotocol or Host Link Mode.
Reception Completed Flag
Turns ON when receptions for RXD(
) have been completed in Noprotocol Mode.
Reception Overflow Flag
In No-protocol Mode, turns ON when the next data is received before previous data is read out using RXD(
).
Sequence Abort Completion Flag
08 to 11 Port 2 Error Code
0: Normal operation 1: Parity error 2: Framing error
3: Overrun error
6: Checksum error
4: FCS error
7: Command error
5: Timeout error
All modes
All modes
Host Link or No-protocol
Protocol macro
All modes
14
15
Communications Error Flag
Transmission Enabled Flag
Turns ON when transmission is enabled, OFF when transmissions are being processed for TXD(
).
Use with flag as an execution condition for TXD(
) when using Noprotocol or Host Link Mode.
Reception Completed Flag
Turns ON when receptions for RXD(
) have been completed in Noprotocol Mode.
Reception Overflow Flag
In No-protocol Mode, turns ON when the next data is received before previous data is read out using RXD(
).
Sequence Abort Completion Flag
Host Link or No-protocol
Protocol macro
30
Control Bits, Flags, and Status Information
Section 3-3
Word Bits Function Communications modes
IR 202 00 to 07 Port 1 Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.) NT Link in 1:N mode
Repeat counter PV (00 to FF hexadecimal) Protocol macro
00 to 15 Reception counter No-protocol
The number of bytes of data received in No-protocol Mode (Hex).
Reset to 0 when data is read out using RXD(
).
IR 203 00 to 07 Port 2 Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.) NT Link in 1:N mode
Repeat counter PV (00 to FF hexadecimal) Protocol macro
No-protocol 00 to 15
IR 204 00
Reception counter
The number of bytes of data received in No-protocol Mode (Hex).
Reset to 0 when data is read out using RXD(
).
Port 1 Tracing Flag
01 Port 2
02 to 05 Not used.
06
07
Port 1 Echoback Disable Mode Monitor Flag (when modem control is desig-
Port 2 nated) (See note.)
Protocol macro
08 to 11 Port 1 Protocol Macro Error Code
12 to 15 Port 2
0: Normal operation 1: No protocol macro function
2: Sequence number error 3: Data read/write area overflow
4: Protocol data grammar error
5: Protocol macro execution error during port initialization
IR 205 00 to 03 Port 1 Completed Reception Case Number
04 to 07 Completed Step Number
08 to 14 Not used.
15 IR 204 (bits 08 to 11) Data Stored Flag
0: No data stored; 1: Data stored
IR 206 00 to 03 Port 2 Completed Reception Case Number
04 to 07 Completed Step Number
08 to 14
15
IR 207 00
01
02
Not used.
IR 204 (bits 12 to 15) Data Stored Flag
0: No data stored; 1: Data stored
Port 1 Serial Communications Port Restart Bits
Port 2
Port 1 Continuous Trace Start/Stop Bits
03
04
05
06
07
08
Port 2
Port 1 Shot Trace Start/Stop Bits
Port 2
Port 1 Echoback Disable Mode Flag (when modem control is designated)
Port 2
(See note.)
Port 1 Protocol Macro Executing Flag (instruction execution)
Protocol macro
Protocol macro
All modes
Protocol macro
No-protocol or Protocol macro
Protocol macro 09
10
11
12
Transfer Step Error Processing Flag
Sequence End Completion Flag
Forced Abort Bit
Port 2 Protocol Macro Executing Flag (instruction execution) No-protocol or Protocol macro
Protocol macro 13 Transfer Step Error Processing Flag
14
15
00 to 15 Not used.
Sequence End Completion Flag
Forced Abort Bit
--IR 208 to
IR 215
31
Control Bits, Flags, and Status Information
Section 3-3
Word
254
AR 04
15
Bit(s) Function
Inner Board Error Flag
Turns ON when an error occurs in an Inner Board mounted in slot 1 or slot 2. The error code for slot 1 is stored in AR 0400 to AR 0407 and the error code for slot 2 is stored in AR 0408 to AR
0415.
00 to 07
Slot 1 Inner Board Error Code (Hex)
00: Normal
01, 02: Hardware error
10: Serial Communications Board error
Note Supported on products with lot number of No. 0320* or later.
Reading lot numbers:
0 3 2 0
...Produced February 3, 2000
Production year: Last digit of the year
Production month: 1 to 9, X (10), Y (11), Z (12)
Production day: 01 to 31
32
SECTION 4
Host Link Communications
This section describes the procedure and other information required to use Host Link communications.
4-1-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Host Link Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Types of Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-2 Standard Cables from Board to Personal Computer . . . . . . . . . . . .
4-4-2 Example Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-3 Host Link Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-2 RS-422A/485 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
Host Link Communications
Section 4-1
4-1 Host Link Communications
A Host Link System can be used to send C-mode Host Link commands from a host (e.g., personal computer or PT) to a PC to read/write I/O memory, control operating modes, etc. The PC can also use the TXD(
) instruction to send specified I/O memory data to the host for slave-initiated communications.
Refer to the CQM1H-series PC Programming Manual for details on C-mode commands.
Host-initiated
Communications
Communications in a Host Link System are normally started by a host computer.
Slave-initiated
Communications
Command
Host computer
CQM1H-series PC
Response
The host sends a command to the PC. The PC processes the command and returns a response to the host computer. This process is repeated, allowing the host computer to monitor and control PC operation.
The PC can also initiate communications with the host to send data, as may be necessary when errors occur on the line controlled by the PC or to confirm the operating status of the host.
ASCII data
Host computer
CQM1H-series PC
When the TXD(
) instruction is executed in the ladder program of the PC, the contents of the I/O memory words specified for the instruction is converted to
ASCII and sent to the host. There is no response to this transmission.
TXD(
) Instruction
TXD(48) reads N bytes of data beginning from words S, converts it to ASCII, and outputs the data from the specified port as a Host Link command. Up to
122 bytes (61 words) of data can be sent. Refer to the CQM1H-series PC Pro-
gramming Manual for details.
TXD(48)
S
C
First source word
Control word
N
Number of bytes: 4 digits BCD, 0000 to 0061
The format of the Host Link command generated by TXD(
) is shown below.
The command header code is EX and is followed by the specified data converted to ASCII. There is no response to the EX command.
@ x 10
1 x 10
0
E X
Send data (ASCII)
*
↵
Node No.
Header code
122 characters max.
FCS Terminator
Note If the PC is sending a response to a Host Link command when the TXD(
) instruction is executed, the EX command for TXD(
) will be sent after the response.
If TXD(
) is executed in Host Link Mode, the specified data is converted to
ASCII before being sent. If TXD(
) is executed in No-protocol Mode, the specified data is sent without conversion.
34
Host Link Communications
Section 4-1
4-1-1 Host Link Communications
Host Link communications are supported by all CQM1H-series CPU Units. A
Serial Communications Board can be used to connect a single PC to more than one host computer for Host Link communications, including slave-initiated communications. Host Link communications provide the following features.
Connect One Computer to
Multiple PCs
An RS-422A/485 port can be used to connect one host computer to up to 32
CQM1H-series PCs.
Computer Monitoring and
Control of PCs
Redundant Error
Checking
Simultaneous Usage of
Both Ports
Slave-initiated
Communications
Host Link communications enable the host computer to monitor or control PC operations and to read and write I/O memory in the PCs.
Both vertical and horizontal (FCS) parity checks are performed on communications data to achieve essentially error-free communications. Combining error checking and retry processing goes one step further to eliminate nearly all the effects of communications problems.
The Serial Communications Board provides two serial communications ports that can be used simultaneously to connect to two different networks of host computers in addition to the connections made directly from the built-in CPU
Unit ports.
Communications can be performed either by sending a command from a host and having the PC return a response, or by sending data from a PC to the host.
Note A Host Link connection can also be used to connect the PC to a Programming
Device running on a personal computer. The following two modes can be used to connect to computers running Programming Devices. Only the Host
Link Mode can be used for the Serial Communications Board.
Serial communications mode
Host Link
Peripheral bus
Features
Functions as a communications protocol with standard host computers.
Either 1:1 or 1:N connections are possible.
Slower than a peripheral bus connection.
Connection is possible through a modem or Optical Link
Adapter, and long-distance and 1:N connections are possible using RS-422A/485.
Enables high-speed communications. A peripheral bus connection is thus the normal mode used to connect to a computer running the CX-Programmer.
Only 1:1 connections are possible.
With the CQM1H, the baud rate of the Programming
Device is detected when the connection is made.
35
Application Procedure
Section 4-2
4-1-2 Host Link Specifications
Item Description
Communications mode
Half-duplex (Full-duplex for slave-initiated communications)
Synchronization
Start-stop (asynchronous mode)
Baud rate (See note 1.)
RS-232C port and RS-422A/485 ports:
1,200/2,400/4,800/9,600/19,200 bps
Communications distance (See note 1.)
Default setting: 9,600 bps
RS-232C port: 15 m max. (See note 2.)
Connection configuration
RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.)
RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using an Converting Link Adapters.)
RS-422A/485 port: 1:N (N = 32 Units max.)
Number of connected
Units
Frame structure
32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection)
Error check codes
Command flow and support
Transmission delay time
C-mode Host Link commands
Header:
Data:
@, address: (Host Link unit number) 0 to 31 (BCD)
Header code + text
Error check code: FCS
Terminator:
*
+CR
Vertical parity: Even, odd. or none
FCS (horizontal parity converted to ASCII)
Contents Command flow
Host computer to
PC
Commands
C-mode Host Link commands
PC to host computer
Data only
1:1 or 1:N communications with directly connected
PCs (The specified frame format must be prepared on the host computer and then sent.)
Communications using TXD(
) from CPU Unit.
No response from host.
Connection between the host computer and PC must be 1:1.
0 to 99,990 ms (set in PC Setup in 10-ms units) Host computer to PC
The delay is from the return of a response by the PC until a response can be returned to the next command received from the host.
PC to host computer
The delay is from the beginning of
TXD(
) execution until execution of the next TXD(
) can be started.
Note
1.
Confirm the baud rates and communications distance supported by connected devices.
2.
The maximum cable length for RS-232C is 15 m.
4-2 Application Procedure
1,2,3...
1.
Turn OFF the power supply to the PC.
2.
Mount the Board.
3.
Connections
Connect the external devices using RS-232C or RS-422 cables. The
TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-4522A/485 port.
The host computer can be connected to a PC 1:1, or NT-AL001-E Converting Link Adapters can be used to convert from RS-232C to RS-422A/485 to connect the host computer to PCs 1:N. Standard connection examples
36
Application Procedure
Section 4-2
are shown below. Perform other processing as required, such as setting switches on the external device(s).
Serial Communications Board
RS-232C
RS-232C
RS-422A
/485
3G2A9-AL001
RS-422A
/485
NT-AL001-E
Terminating resistance
ON, 5-V power supply required
Terminating resistance
ON
The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required.
4.
Turn ON power.
5.
Set the PC Setup settings for the Serial Communications Board.
Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559.
Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed.
The following table shows the standard settings.
Port 1 Port 2 Bit(s) Default setting
DM 6555 DM 6550 00 to 03 0 Hex
Function
04 to 07 0 Hex
08 to 11 ---
Standard port settings
(1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
CTS control disabled
Not used.
12 to 15 0 Hex
DM 6556 DM 6551 00 to 07 ---
Communications mode
0: Host Link
Baud rate: invalid
08 to 15 --Frame format: Invalid
DM 6557 DM 6552 00 to 15 0000 Hex Transmission delay: 0 ms
DM 6558 DM 6553 00 to 07 00 BCD
08 to 11 ---
Node number 00
Not used.
12 to 15 --Not used.
37
Application Procedure
Section 4-2
6.
Program the host and the CPU Unit and execute the programs.
Host-initiated Communications: Host Link Commands
A program must be prepared in the host to send Host Link commands to the PC and receive responses.
Program to send commands and receive responses
Serial Communications Board
Host
Response
Command
PC-initiated Communications: TXD(
) Instruction
TXD(
) must be included in the ladder program to send data from the PC to the host.
Host
Program to send responses
Serial Communications Board
TXD(
)
Data
CPU Unit
38
Connections
Section 4-3
4-3 Connections
4-3-1 Types of Connection
Port connections for Host Link communications are shown in the following table. Up to 32 nodes can be connected for 1:N connections.
RS-232C
Port Configuration
1:1
Schematic diagram
RS-232C
RS-232C 1:N
NT-AL001-E
RS-232C
Resistance ON
5-V power
RS-422A/485
RS-232C
NT-AL001-E
Resistance ON
RS-232C RS-422A/485
NT-AL001-E
NT-AL001-E
Resistance ON
5-V power
RS-232C
Resistance ON
RS-232C
RS-232C
RS-422A/485 1:1
RS-422A/485 1:N
RS-232C
NT-AL001-E
RS-422A/485
Resistance ON
5-V power
RS-232C
RS-422A
/485
Resistance ON
3G2A9-AL001
RS-422A
/485
NT-AL001-E
Resistance ON
5-V power
Resistance ON
Note
1.
Four-wire connections must be used for RS-422A/485 connections with
Host Link communications.
2.
“Resistance ON” indicates the terminating resistance must be turned ON.
3.
“5-V power” indicates that a 5-V power supply is required for the Link
Adapter. Refer to the Link Adapter manual for details. A 5-V power supply is not required for a Link Adapter connected to a Serial Communications
Board because power is supplied from pin 6 of the connector.
4.
The maximum cable length for RS-232C is 15 m.
Connection Examples
The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twistedpair cables. Refer to 2-3 Wiring for actual wiring methods.
39
Connections
Host Computer Connections
1:1 Connections Using RS-232C Ports
IBM PC/AT or Compatible Computers
Serial Communications
Board
RS-232C interface
Signal
Pin
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
Using NT-AL001-E Converting Link Adapters
Computer
Pin Signal
CD
RD
SD
DTR
SG
DSR
RTS
CTS
CI
RS-232C interface
D-sub, 9-pin connector (female)
Section 4-3
Computer
DSR
DTR
SG
Shield
NT-AL001-E Link Adapter
Signal
RS-232C
Pin
FG
SD
RD
RS-232C
Interface
RTS
CTS
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal Pin
RS-422A
NT-AL001-E Link Adapter
Pin Signal
Signal
Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
(See note)
Serial Communications
Board
Pin Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
Interface
D-sub, 9-pin Terminal block connector (male)
Terminal block
D-sub, 9-pin connector (male)
D-sub, 9-pin connector (male)
5-V (+) power (
−
)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
!Caution
Do not use the 5-V power from pin 6 of the RS-232C port for anything but the
NT-AL001-E Link Adapter. Using this power supply for any other external device may damage the Serial Communications Board or the external device.
40
Connections
Section 4-3
5-V (+) power (
−
)
1:N Connections Using RS-232C Ports
Computer
Signal
Shield
FG
SD
RS-232C
Interface
RD
RTS
CTS
DSR
DTR
SG
NT-AL001-E Link Adapter
Pin Signal Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
RS-422A
D-sub, 9-pin Terminal block connector (male)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
NT-AL001-E Link Adapter
Pin Signal
Signal
Pin
Serial Communications
Board
RS-232C
(See note)
Pin
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
Interface
DIP Switch Settings
Pin 1: ON
Pin 2: OFF (no terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
NT-AL001-E Link Adapter
Pin Signal Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
Serial Communications
Board
Pin
RS-232C
(See note)
Pin Signal
FG
SD
RD
RTS
CTS
5V
DSR
RS-232C
Interface
DTR
SG
D-sub, 9-pin connector (male)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
41
Connections
Section 4-3
1:1 Connections Using RS-422A/485 Ports
Computer
Signal
FG
SD
RD
RS-232C
Interface
RTS
CTS
Shield
DSR
DTR
SG
NT-AL001-E Link Adapter
Pin Signal Pin Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin Terminal block connector (male)
5-V (+) power (
−
)
Serial Communications
Board
Pin
Signal
RS-422A
/ 485 Interface
Hood
Terminating resistance ON
4-wire
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
42
Connections
Section 4-3
1:N Connections Using RS-422A/485 Ports
Computer
NT-AL001-E Link Adapter
Signal
FG
SD
RS-232C
Interface
RD
RTS
CTS
DSR
DTR
SG
Shield
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
3G2A9-AL001 Link Adapter
Pin Signal Signal Pin
RS-422A/
485 Interface
Serial Communications
Board
Shield
Pin Signal
RS-422A/
485 Interface
Signal
Pin
Hood
Terminating resistance OFF
4-wire
D-sub, 9-pin connector (male)
D-sub, 9-pin Terminal block connector (male)
5-V (+) power (
−
)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
Shield
Serial Communications
Board
Pin Signal
RS-422A/
485 Interface
Hood
Terminating resistance ON
(last node)
4-wire
Computer
Signal
Shield
RS-232C
FG
SD
RD
RS-232C
Interface
RTS
CTS
DSR
DTR
SG
NT-AL001-E Link Adapter
Pin Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal Pin
D-sub, 9-pin Terminal block connector (male)
5-V (+) power (
−
)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
Serial Communications
Board
RS-422A Pin Signal
RS-422A/
485 Interface
Hood
Terminating resistance OFF
4-wire
Serial Communications
Board
Pin Signal
RS-422A/
485 Interface
Hood
Terminating resistance ON
(last node)
4-wire
43
Connections
Section 4-3
4-3-2 Standard Cables from Board to Personal Computer
Board port Computer Network type Model Length
RS-232C port
(D-sub, 9-pin female)
IBM PT/AT or compatible
Computer port
D-sub, 9-pin male
Host Link
(SYSMAC
WAY)
XW2Z-200S-CV 2 m
XW2Z-500S-CV 5 m
Board port Computer
RS-232C port
(D-sub, 9-pin female)
IBM PT/AT or compatible
Remarks
Conforms to
ESD.
The following Connecting Cables can be used to connect an RS-232C to the computer.
Network type Model Length Remarks Computer port
D-sub, 9-pin male
Host Link
(SYSMAC
WAY)
XW2Z-200S-V
XW2Z-500S-V
2 m
5 m
---
Preparing an RS-232C Cable for the Computer
The following cables and connectors can be used to manufacture a cable to connect the Serial Communications Board to the PC.
Applicable Connectors
The following connector connects to the Serial Communication Board.
Name
Socket
Hood
Model
XM2A-0901 9-pin male
Specifications
Used together (provided with Board).
XM2S-0911-E For 9-pin socket, metric screws, ESD countermeasures
The following connector connects to an IBM PC/AT or compatible
Socket
Name
Hood
Model
XM2D-0901
XM2S-0913
Specifications
9-pin male
For 9-pin socket, inch screws
Used together.
Hood: XM2S-0913
IBM PC/AT or compatible
(9-pin, male)
Socket:
XM2D-0901
(9-pin, female)
CQM1H CPU Unit
RS-232C port on Serial
Communications Board
Recommended cable
Hood: XM2S-0911-E Socket: XM2A-0901
Hood and Socket provided with Board.
Recommended Cables
UL2464 AWG28
×
5P IFS-RVV-SB (UL-approved, Fujikura Ltd.)
AWG28
×
5P IFVV-SB (not UL-approved, Fujikura Ltd.)
UL2464-SB (MA) 5P
×
28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.)
CO-MA-VV-SB 5P
×
28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.)
44
Host Link Communications
Section 4-4
4-4 Host Link Communications
4-4-1 Protocol
Command Frame Format
Host Link communications are executed by means of an exchange of commands and responses between the host computer and the PC. The command or response data that is transferred in one exchange is known as a frame and one frame can contain up to 131 characters of data.
The frame formats for Host Link commands transmitted from the host computer and responses returned from the PC are described below. The PC automatically returns an ASCII-code response when it receives an ASCII-code command from the host computer. The host computer must have a program that controls the transmission and reception of the commands and responses.
When transmitting a command from the host computer, prepare the command data in the format shown below.
@ x 10
1 x 10
0
∗
↵
Node No.
Header code
Text FCS Terminator
The header code and text depend on the Host Link command being transmitted. When a compound command is transmitted, there will be a second subheader code.
The FCS (Frame Check Sequence) code is calculated at the host computer and set in the command frame. The FCS calculation is described later in this section.
The command frame may be up to 131 characters long. A command of 132 characters or more must be divided into more than one frame. To split the command, use a carriage return delimiter (
↵
, CHR$(13)) instead of a terminator. A terminator must be used at the end of the last frame.
When dividing commands such as WR, WL, WC, or WD that execute write operations, be careful not to divide into separate frames data that is to be written into a single word. You must divide frames so that they coincide with the divisions between words.
Item Function
@
Destination
Node No.
An “@” symbol must be placed at the beginning of every command.
Identify the PCs by the Host Link node numbers (0 to 31) set in DM
6558 and DM 6553 of the PC Setup.
Header code Set the 2-character command code.
Text
FCS
Terminator
Set the command parameters.
Set a 2-character Frame Check Sequence code.
Set two characters, “
*
” and the carriage return (CHR$(13)) to indicate the end of the command.
Normal Response Frame
Format
A normal response from the PC is returned in the format shown below. Prepare a program at the host so that the response data can be interpreted and processed.
@ x 10 1 x 10 0 x 16 1 x 16 0
∗
↵
Node No.
Header code
End code Text FCS Terminator
The header code and text depend on the Host Link command that was received. The end code indicates the completion status of the command (e.g., whether or not an error has occurred).
45
Host Link Communications
Error Response Frame
Format
Section 4-4
When the response is longer than 131 characters, it will be divided into more than one frame. A carriage return delimiter (
↵
, CHR$(13)) instead of a terminator will automatically be set at the end of the frame. A terminator will be set at the end of the last frame.
@
Item
FCS
Terminator
Function
An “@” symbol is placed at the beginning of every response.
Local Host
Link Node No.
The PC’s Host Link node number set in DM 6553 or DM 6558 of the
PC Setup.
Header code The 2-character command code is returned.
End code The status of command execution is returned (normal end code).
Text The results of the command are returned.
The 2-character Frame Check Sequence code is returned.
Two characters, “
*
” and the carriage return (CHR$(13)) indicate the end of the response.
An error response from the PC is returned in the format shown below. Prepare a program at the host so that the response data can be interpreted and processed.
@ x 10 1 x 10 0 x 16 1 x 16 0
∗
↵
FCS (Frame Check
Sequence)
Node No.
Header code
End code FCS Terminator
The header code and text depend on the Host Link command that was received. The end code indicates the completion status of the command (e.g., whether or not an error has occurred).
@
Item Function
An “@” symbol is placed at the beginning of every response.
Local Host
Link Node No.
Header code The 2-character command code is returned.
End code The status of command execution is returned (error code).
FCS
Terminator
The PC’s Host Link node number set in DM 6553 or DM 6558 of the
PC Setup.
The 2-character Frame Check Sequence code is returned.
Two characters, “
*
” and the carriage return (CHR$(13)) indicate the end of the response.
When a frame is transmitted, an FCS code is placed just before the delimiter or terminator in order to check whether an error has occurred in the transmission. The FCS is 8-bit data converted into two ASCII characters. The 8-bit data is the result of an EXCLUSIVE OR performed on the data from the beginning of the frame until the end of the text in that frame (i.e., just before the FCS). Calculating the FCS each time a frame is received and checking the
46
Host Link Communications
Section 4-4
result against the FCS that is included in the frame makes it possible to check for data errors in the frame.
@ 1 0 R R 0 0 0 1 4 2
∗
↵
1
0
R
@
Node No. Header code
ASCII code
FCS calculation range
40
31
30
52
0100
EOR
0011
EOR
0011
EOR
0101
0000
0001
0000
0010
Text FCS Terminator
Communications
Sequence
1
Calculation result
31 0011
0100
↓
4
0001
0010
↓
2
Converted to hexadecimal.
Handled as ASCII characters.
The right to send a frame is called the “transmission right.” The Unit that has the transmission right is the one that can send a frame at any given time. The transmission right is traded back and forth between the host computer and the
PC each time a frame is transmitted. An example sequence for multiframe communications between the host computer and PC is described below. Multiframe communications are handled by exchanging delimiters and then using terminators to indicate the last frame.
• The host computer sets a delimiter at the end of the first command frame and transmits the frame.
• When the PC receives the delimiter, it returns the same delimiter to the host computer.
• After receiving the delimiter from the PC, the host computer transmits the next frame.
• Delimiters are used to send the rest of the frames.
• When the host computer sends the last command frame, it sets a terminator at the end.
• When the PC receives a frame with a terminator, it sends the response.
• If there was more than one response frame, delimiters would be used here too.
Frame 2 (command) Frame 3 (command)
Host computer
Frame 1 (command)
@ Unit No.
Header code
Text
FCS
Delimiter
Text
FCS
Delimiter
Text
FCS
Terminator
PC
Delimiter
Delimiter
@ Unit No.
Header code
End code
Text
FCS
Terminator
Frame (response)
47
Host Link Communications
Using the TXD (
)
Instruction
Section 4-4
The TXD(
) instruction can be used to transmit data from the PC’s data area to the host computer. There is no response from the host computer. The
TXD(
) instruction will be executed after the response has been transmitted if TXD(
) is executed while a response to a Host Link command is being returned to the host computer.
Host computer
No response
PC
@ Unit No.
Header code
Text
FCS
Terminator
4-4-2 Example Programs
Command Transmission
The following type of program must be prepared in the host computer to receive the data. This program allows the computer to read and display the data received from the PC while a Host Link read command is being executed to read data from the PC.
10 ’CQM1H SAMPLE PROGRAM FOR EXCEPTION
20 CLOSE 1
30 CLS
40 OPEN ”COM:E73” AS #1
50 *KEYIN
60 INPUT ”DATA – – – – – – – –”,S$
70 IF S$=” ” THEN GOTO 190
80 PRINT ”SEND DATA = ”;S$
90 ST$=S$
100 INPUT ”SEND OK? Y or N?=”,B$
110 IF B$=”Y” THEN GOTO 130 ELSE GOTO *KEYIN
120 S$=ST$
130 PRINT #1,S$
140 INPUT #1,R$
’Sends command to PC
’Receives response from PC
150 PRINT ”RECV DATA = ”;R$
160 IF MID$(R$,4,2)=”EX” THEN GOTO 210
’Identifies command from PC
170 IF RIGHT$(R$,1)<>”*” THEN S$=” ”:GOTO 130
180 GOTO *KEYIN
190 CLOSE 1
200 END
210 PRINT ”EXCEPTION!! DATA”
220 GOTO 140
Example Program for FCS
This example shows a BASIC subroutine program for executing an FCS check on a frame received by the host computer.
400 *FCSCHECK
410 L=LEN(RESPONSE$)
420 Q=0:FCSCK$=” ”
430 A$=RIGHT$(RESPONSE$,1)
440 PRINT RESPONSE$,A$,L
450 IF A$=”*” THEN LENGS=LEN(RESPONSE$)-3
ELSE LENGS=LEN(RESPONSE$)-2
460 FCSP$=MID$(RESPONSE$,LENGS+1,2)
’. . . . FCS data received
470 FOR I=1 TO LENGS
’. . . . . . . . . . Number of characters in FCS
48
Host Link Communications
Section 4-4
TXD(
) Application
Example
Note
480 Q=ASC(MID$(RESPONSE$,I,1)) XOR Q
490 NEXT I
500 FCSD$=HEX$(Q)
510 IF LEN(FCSD$)=1 THEN FCSD$=”0”+FCSD$
’FCS result
520 IF FCSD$<>FCSP$ THEN FCSCK$=”ERR”
530 PRINT”FCSD$=”;FCSD$,”FCSP$=”;FCSP$,”FCSCK$=”;FCSCK$
540 RETURN
1.
Normal reception data includes the FCS, delimiter or terminator, and so on. When an error occurs in transmission, however the FCS or some other data may not be included. Be sure to program the system to cover this possibility.
2.
In this program example, the CR code (CHR$(13)) is not entered for RE-
SPONSE$. When including the CR code, make the changes in lines 430 and 450.
This example shows a program for using the RS-232C port in the Host Link mode to transmit 10 bytes of data (DM 0000 to DM 0004) to a computer. From
DM 0000 to DM 0004, “1234” is stored in every word.
The default values are assumed for all of the PC Setup (i.e., the RS-232C port is used in Host Link mode, the node number is 00, and the standard communications parameters are used.)
Communications Control
Signals and
Communications Timing
00100 20105
@TXD(
)
DM 0000
#0100
#0010
If SR 20105 (the Transmission Ready Flag) is
ON when IR 00100 turns ON, ten bytes of data (DM 0000 to DM 0004) will be transmitted.
The transmitted data will appear on the host computer's screen as follows, assuming the text being sent is "1234" in all specified words:
@00EX1234123412341234123459*CR
The PC Setup has a setting that can be used to enable CTS control. If CTS control is enabled, processing will be placed on standby until the CS input turns ON after the RS output ON signal is sent for a transmission from the
Serial Communications Board. Connect the RS output from the host to the CS input on the Board and perform flow control at the host.
49
Host Link Communications
Section 4-4
Setting a Transmission
Delay
A transmission delay can be set in the PC Setup to create a minimum interval between sending a response from the PC to a Host Link command until the beginning of sending the response to the next command.
The delay is not used in the response to the first command. The delay will affect responses to other commands only if the normal time for the response comes before the time set for the transmission delay has expired.
If the delay time has already expired when the next command is received, the response will be spent immediately. If the delay time has not expired, the response will be delayed until the time set for the transmission delay has expired.
The operation of the transmission delay for responses to host commands is illustrated below.
Transmission delay Transmission delay Transmission delay
Response sent Response sent Response sent Response sent
Response to
1st command
Response to
2nd command
Response to
3rd command
Response to
4th command
Time
The transmission delay will also be effective in PC-initiated communications as a minimum interval between sending commands to the host.
The delay is not used in sending the first command. The delay will affect other commands only if the time set for the transmission delay has not expired when the next command is ready to be sent.
If the delay time has already expired when the next command is ready, the command will be spent immediately. If the delay time has not expired, the command will be delayed until the time set for the transmission delay has expired.
The operation of the transmission delay for PC-initiated communications is illustrated below.
Transmission delay Transmission delay Transmission delay
Command sent Command sent Command sent Command sent
1st TXD(
) command
2nd TXD(
) command
3rd TXD(
) command
4th TXD(
) command
Time
50
Host Link Communications
Section 4-4
KS
KR
FK
KC
W%
MS
SC
MF
WD
WE
WJ
R#
R$
R%
W#
W$
XZ
**
EX
IC
MM
TS
RP
WP
RD
RE
RJ
WR
WL
WH
WC
WG
RR
RL
RH
RC
RG
4-4-3 Host Link Commands
The Host Link commands listed in the following table can be sent to the
CQM1H for Host Link communications. Refer to the CQM1H-series Program-
ming Manual for details.
Header code Name
Not valid
Not valid
Not valid
Valid
Valid
Valid
Not valid
Not valid
Not valid
Valid
Valid
Valid
Not valid
Not valid
Not valid
Not valid
Valid
Valid
Valid
Not valid
Valid
Valid
Valid
Valid
---
RUN
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Not valid
Not valid
Not valid
Not valid
Not valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Not valid
---
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
PRG
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Not valid
Valid
Valid
Valid
Valid
---
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
PC mode
MON
Valid
Valid
Valid
Valid
Valid
IR/SR AREA READ
LR AREA READ
HR AREA READ
TC PV READ
TC STATUS READ
DM AREA READ
EM AREA READ
AR AREA READ
IR/SR AREA WRITE
LR AREA WRITE
HR AREA WRITE
TC PV WRITE
TC STATUS WRITE
DM AREA WRITE
EM AREA WRITE
AR AREA WRITE
SV READ 1
SV READ 2
SV READ 3
SV CHANGE 1
SV CHANGE 2
SV CHANGE 3
STATUS READ
STATUS WRITE
ERROR READ
FORCED SET
FORCED RESET
MULTIPLE FORCED SET/RESET
FORCED SET/RESET CANCEL
PC MODEL READ
TEST
PROGRAM READ
PROGRAM WRITE
COMPOUND COMMAND
ABORT (command only)
INITIALIZE (command only)
TXD RESPONSE (response only)
Undefined command (response only)
51
Host Link Communications
Section 4-4
4-4-4 End Codes
The response (end) codes listed in the following table are returned in the response frame for Host Link commands. When two or more errors occur, the end code for the first error will be returned.
End code
00
01
02
03
04
13
14
15
16
18
19
23
A3
A4
A5
A8
Contents Probable cause Corrective measures
Normal completion No problem exists.
Not executable in RUN mode The command that was sent cannot be executed when the PC is in RUN mode.
Not executable in MONITOR mode
UM write-protected
Address over
FCS error
The command that was sent cannot be executed when the PC is in MONITOR mode.
The PC’s UM is write-protected.
The program address setting in an read or write command is above the highest program address.
The FCS is wrong.
---
Check the relation between the command and the PC mode.
Turn OFF pin 1 of the CPU Unit’s
DIP switch (SW1).
Check the program.
Check the FCS calculation method. If there was influence from noise, transfer the command again.
Format error
Entry number data error
Command not supported
Frame length error
The command format is wrong, or a command that cannot be divided has been divided, or the frame length is smaller than the minimum length for the applicable command.
The data is outside of the specified range or too long.
Hexadecimal data has not been specified.
Check the format and transfer the command again.
Correct the data and transfer the command again.
The operand specified in an SV Read or SV
Change command does not exist in the program.
The maximum frame length of 132 bytes was exceeded.
If the frame exceeds 280 bytes, the Reception
Overflow Flag will be turned ON and there will not be a response.
Check search data or the search starting point.
Check the command and divide it into multiple frames if necessary.
Not executable
User memory protected
Aborted due to FCS error in transmission data
Aborted due to format error in transmission data
Aborted due to entry number data error in transmission data
Aborted due to frame length error in transmission data
The read SV exceeded 9,999, or an I/O memory batch read was executed when items to read were not registered for compound command.
The UM is write-protected.
Register items to read before attempting batch read.
An FCS error occurred in the second or later frame, or there were two bytes or less of data in an intermediate or final frame for multiple writing.
Turn OFF the write-protection
Correct the command data and transfer the command again.
The command format did not match the number of bytes in the second or later frame.
There was an entry number data error in the second or later frame, a data length error, or data was not set in hexadecimal.
The length of the second and later frames exceeded the maximum of 128 bytes.
52
Changes from Previous Products
Section 4-5
A response will not be received with some errors, regardless of the command.
These errors are listed in the following table.
Error
Parity, overrun, or framing error during command reception. (Same even for commands address to other Units.)
PC operation
The Communications Error Flag will be turned ON, an error code will be registered, and receptions will be reset. (The error will be cleared automatically if communications restart normally.)
The Communications Error Flags are as follows:
Peripheral port: AR 0812
Built-in RS-232C port: AR 0804
Serial Communications Board port 1: IR 20104,
Serial Communications Board port 2: IR 20112
The command will be discarded.
A command is received that does not have the
@ character at the beginning of the first frame.
Incorrect node number (Not a local unit or over
31)
The data in an intermediate or final frame for multiframe writes is 2 bytes or longer.
The command will be discarded.
An FCS error will occur.
4-5 Changes from Previous Products
There are differences between Host Link Systems created using the CQM1Hseries Serial Communications Boards in comparison to Host Link Systems created with Host Link Units and CPU Units in other PC product series. These differences are described in this section.
4-5-1 RS-232C Ports
Take the following differences into consideration when changing from an existing Host Link System to one using an RS-232C port on a CQM1H-series CPU
Unit or Serial Communications Boards.
Previous products
C-series Host
Link Units
Model number
3G2A5-LK201-E
C500-LK203
3G2A6-LK201-E
C200H-LK201
Changes required for CQM1H-series product
Wiring Other
The connector has been changed from a 25-pin to a 9pin connector.
The CQM1H-series products do not support the ST1, ST2, and RT signals and wiring them is not required.
The following changes are necessary for systems that sync with ST1, ST2, and RT.
Synchronized transfers will no longer be possible.
Half-duplex transmissions will be possible with the CQM1H-series product, but the host computer’s communications program, hardware, or both will need to be altered.
The following changes are necessary for systems that did not sync with ST1, ST2, and RT.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CQM1H command specifications. (See note.)
The connector has been changed from a 25-pin to a 9pin connector.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CQM1H command specifications. (See note.)
53
Changes from Previous Products
Section 4-5
Previous products
Model number
C-series CPU
Units
SRM1
CPM1
CPM1A
CPM2A/CPM2C
CQM1-CPU @@ -E
C200HS-CPU
@@
-E
C200HX/HG/HE-
CPU @@ -E
C200HW-COM
@@
-E
CS1G/H-CPU @@ CS1-series CPU
Unit
CS1-series
Serial Communications Board or
Unit
CVM1 or CVseries CPU Units
CS1W-SCB21/41
CS1W-SCU21
CVM1/CV-CPU @@
CVM1 or CVseries Host Link
Unit
CV500-LK201
Changes required for CQM1H-series product
Wiring Other
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
No changes have been made in wiring.
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
Port 1:
The connector has been changed from a 25-pin to a 9pin connector.
Port 2 set for RS-232C:
The SG signal has been changed from pin 7 to pin 9.
The following changes are necessary for half-duplex transmissions that use CD.
Check the system for timing problems when using SEND(90), RECV(98), or CMND(
) to initiate communications from the PC or timing problems in sending commands from the host computer. If necessary, switch to full-duplex transmissions.
The following changes are necessary for full-duplex transmissions that do not use
CD.
Half-duplex It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode Host Link commands is different for C-series
Host Link Units and CQM1H-series Serial Communications Boards. A host computer program previously used for C-series Host Link Units may not function correctly if used for CQM1H-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths.
54
Changes from Previous Products
Section 4-5
4-5-2 RS-422A/485 Ports
Take the following differences into consideration when changing from an existing Host Link System to one using an RS-422A/485 port on a CQM1H-series
Serial Communications Board.
Previous products
C-series Host Link
Units
C200HX/HG/HE
Communications
Board
Model number
3G2A5-LK201-E
C200H-LK202
3G2A6-LK202-E
Changes required for CQM1H-series product
Wiring Other
Wiring pins have been changed as shown below.
SDA: Pin 9 to pin 1
SDB: Pin 5 to pin 2
RDA: Pin 6 to pin 6
RDB: Pin 1 to pin 8
SG: Pin 3 to
Not connected
FG: Pin 7 to pin
Connector hood
C200HW-COM @@ -E No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CQM1H command specifications. (See note.)
CS1-series CPU
Unit
CS1-series Serial
Communications
Board or Unit
CS1G/H-CPU
CS1W-SCB21/41
CS1W-SCU21
@@ No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
CVM1 or CVseries CPU Units
CVM1 or CVseries Host Link
Unit
CVM1/CV-CPU
@@
CV500-LK201
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CQM1H command specifications.
Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode Host Link commands is different for C-series
Host Link Units and CQM1H-series Serial Communications Boards. A host computer program previously used for C-series Host Link Units may not function correctly if used for CQM1H-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths.
55
SECTION 5
Protocol Macros
This section describes the procedure and other information required to use protocol macros.
5-1 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-3 Using the Protocol Macro Function . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-4 Storage Memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Control Bits, Flags, and Status Information . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7-1 Executing Communications Sequences . . . . . . . . . . . . . . . . . . . . . .
5-7-2 Ladder Program Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7-3 Ladder Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
Overview of the Protocol Macro Functions
Section 5-1
5-1 Overview of the Protocol Macro Functions
5-1-1 Protocol Macros
The protocol macro function is used to control devices by using the PMCR(
) instruction in the ladder program to execute the data communications sequences (protocols) with the various communications devices, such as general-purpose devices, connected to the RS-232C or RS-422A/485 port.
Standard system protocols are provided in the Serial Communications Board for controlling OMRON devices (such as Digital Controllers and Temperature
Controllers).
Using the Protocol Support Tool called the CX-Protocol, the protocol macro function can be used to create new protocols for commercially available measuring instruments and devices, and to create protocols by modifying one of the standard system protocols. The standard system protocols are also provided with the CX-Protocol.
For details on the use of the CX-Protocol and the protocol macro function, refer to the CX-Protocol Operation Manual (W344).
5-1-2 Features
Wide Range of
Communications
Protocols
Customized Send and
Receive Frames
Communications-related
Functions
Send/Receive Monitoring
Retry Processing
PC Read/Write Variables in Send Frames and
Receive Frames
Switch 1:N
Communications or the
Data Write Destinations
Using Repeat Processing
PC Interrupts During Data
Reception
Next Process Switching
According to Receive
Messages
The main features of the protocol macro functions are described below. For details, refer to the CX-Protocol Operation Manual (W344).
Communications are possible with virtually any general-purpose external device, provided it has an RS-232C or RS-422A/485 port, supports halfduplex communications, and supports start-stop synchronization.
Send frames (command + data and other send frames) and receive frames
(response and other frames) can be created and registered according to the communications frame specifications of the external device.
Error check code calculations, frame length calculations during sending, and
ASCII
⇔
Hexadecimal conversion of numeric data are supported.
Receive wait monitoring, receive completion monitoring, and send completion monitoring are supported. If monitoring times are exceeded, either send/ receive processing can be terminated or retry processing can be performed.
Send/receive retry processing can be automatically executed when an error occurs, simply by setting the number of retries.
Variables for reading PC memory can be included in the send frames. These can be used as destination addresses or data when reading PC data. Variables for writing to PC memory can be also included in the actual receive frames. These can be used to write the contents of destination addresses or data to the PC during reception.
Repeat processing (repeat counters) for send/receive processing can be specified in communications sequences. This enables the same data to be sent by switching destination addresses during communications 1:N (N = 32 max. due to restrictions in the physical layer) or by switching the PC memory write destination addresses during data reception.
An interrupt can be created in the PC’s CPU Unit during data reception, and an interrupt program can be executed in the CPU Unit.
The contents of up to 15 expected receive messages can be compared with the message actually received to determine the next process.
58
Overview of the Protocol Macro Functions
Section 5-1
Protocol Macro Function Specifications
Item
Number of protocols (20 max.)
Number of sequences (1,000 max.)
Per protocol Number of sequences
Communications distance (See note.)
Can be created and registered with the Protocol Support Tool (CX-Protocol).
60 max.
Description
Protocol data memory
Number of messages
Number of reception matrixes
300 max.
100 max.
Sequence execution condition
Flash memory in the Serial Communications Board (Retained even when the power supply to the PC is turned OFF.)
Using the CPU Unit’s PMCR(
) instruction (specifying the sequence number)
Communications mode
Synchronous mode
Baud rate (See note.)
Half-duplex
Start-stop synchronization (asynchronous mode)
RS-232C port and RS-422A/485 ports:
1,200/2,400/4,800/9,600/19,200 bps
Default setting: 9,600 bps
RS-232C port: 15 m max.
RS-442A/485 port: 500 m max. (The total combined cable length is
500 m max. T-branch lines must be a maximum of 10 m long.)
Connection configuration
Number of connected Units
Maximum number of data exchange words between PC and protocol macro function
Operand setting
Link word setting
Direct setting
RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using a Converting Link Adapter.)
RS-422A/485 port: 1:N (N = 32 Units max.)
32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection)
127 words
128 words
128 words
Including the word that specifies the number of words (1 word)
O1, O2, I1, and I2: 128 words total
Maximum number of words per data attribute
59
Overview of the Protocol Macro Functions
Section 5-1
Item
Sequence contents
(step common parameters)
Number of steps per sequence
Transmission control parameters
Response notification method (operand)
16 max.
Description
X-on/X-off flow, RTS/CTS flow, delimiter control, or contention control, and modem control can be selected.
Scan notification or interrupt notification (i.e., writing the receive data in the I/O memory area specified in the 3rd operand of the PMCR(
) instruction) can be selected.
Scan notification:
Writes the receive data to I/O memory during CPU Unit scanning.
Interrupt notification:
Writes the receive data to I/O memory as soon as it is received, and at the same time specifies the execution of the interrupt program for the
CPU Unit.
Scan method (fixed) Yes
Interrupt notification Yes
Interrupt notification for reception case number
Yes
Receive wait, receive completion, or send completion can be monitored.
Setting range: 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 min
Monitoring time during send/ receive processing
Link word setting
Area in which data is exchanged between the CPU Unit and the Serial
Communications Board during Serial Communications Board refreshing. Two areas are possible for each device: An area for storing receive data and an area for storing send data.
60
Overview of the Protocol Macro Functions
Step contents
Section 5-1
Item
Commands
Repeat counter
Retry count
Send only (SEND), receive only (RECEIVE), or send and receive
(SEND&RECEIVE)
1 to 255 times
Description
0 to 9
(Only when the command is SEND&RECEIVE)
Send wait time
With or without response write
(operand)
Next processing
0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 min
(Only when the command is SEND or SEND&RECEIVE)
When receive processing is completed (when the receive data is stored in the area specified in the 3rd operand of the PMCR(
) instruction), whether or not to store the received messages can be selected.
When a step has ended normally, End (sequence completed), Next (proceed to the next step No.), Goto (go to the specified step No.), or Abort
(interrupt the step and terminate that sequence) can be selected.
Error processing
When a step has ended abnormally, End, Next, Goto, or Abort can be selected.
Send message
Data sent to the specified address when the command is SEND or
SEND&RECEIVE.
Receive message
Data sent from the specified address when the command is RECEIVE or
SEND&RECEIVE.
Reception matrix
When the command is RECEIVE or
SEND&RECEIVE, sets the expected receive messages
(15 max.), and switches to the next processing according to the message received.
Consists of a header (*1), address (*2), length, data (*2), error check code (*3), and terminator
(*1).
For an explanation of *1, *2, and *3, see the following pages.
Specifies the receive messages and the next processing for each of cases No. 00 to No. 15. Of the maximum 16 cases, one case must be set as
“Other” in the receive messages (in addition to the set receive messages).
Note The baud rate and the communications distance sometimes depend on the remote device.
61
Overview of the Protocol Macro Functions
Section 5-1
Message contents
Item
*1:
Header and terminator data attributes
*2:
Data attributes of addresses and data in send/receive messages
Constant
Constant
Variables
Description
ASCII data, hexadecimal data, or control code
ASCII data, hexadecimal data, or control code (with an address, no control code is possible)
No conversion, conversion to ASCII data, or conversion to hexadecimal data
(the read/write direction can be specified)
(X, Y) Designation method
X: Effective address (where read from, or where written to)
Y: Data size (1 to 256)
X
Y
Note
The data size is the number of bytes on the transmission path.
Word designation
Word read (I/O memory to send data)
Specify using the 2nd operand of the
PMCR(
) instruction.
Specify using a link word.
Set leading address + n
(The linear expression aN
+ b, including repeat counter
N, is also possible for n.)
I/O memory direct designation
Word write
(receive data to
I/O memory)
Wild card *
Specify using the 3rd operand of the
PMCR(
) instruction.
Specify using a link word.
I/O memory direct designation
Any data or address can be received (only in receive messages)
Repeat counter N
Linear expression including repeat counter aN + b
Wild card * a: 0 to 255; b: 1 to 255
N: Repeat counter value
Word designation
Word read (I/O memory to send data)
Can be received regardless of the length (only in receive messages)
Specify using the 2nd operand of the
PMCR(
) instruction.
Specify using a link word.
I/O memory direct designation
Set leading address + n
(The linear expression aN
+ b, including repeat counter
N, is also possible for n.)
62
Overview of the Protocol Macro Functions
Section 5-1
Message contents (continued)
Trace function
Item
*3:
Error check codes
Maximum length of send/receive messages
Maximum number of data attributes registered in one message
Maximum number of write data attributes registered in one message
LRC, LRC2, CRC-CCITT, CRC-16, SUM, SUM1, and SUM2 can be calculated.
256 bytes.
Description
96 attributes (See note 1.)
30 attributes (See note 2.)
A total of up to 1,700 bytes (characters) of time-series data can be traced in send and receive messages.
Changes to the step No. and control signals such as RTS and CTS can also be traced.
Note
1.
The CX-Protocol can be used to register up to 96 attributes per message.
2.
A macro syntax error will occur when the protocol macro is executed if more than 31 write attributes are registered in one message.
5-1-3 Using the Protocol Macro Function
The following three methods are available for using the protocol macro function.
Using the Standard
System Protocols
When connecting OMRON devices, data is sent and received between the
CQM1H-series CPU Unit and these devices by specifying the sequence number of the standard system protocol provided in the Serial Communications
Board and CX-Protocol, and executing the sequence using the PROTOCOL
MACRO instruction (PMCR(
)). The CX-Protocol is not required to use the standard system protocols.
CPU Unit
Sequence number
Serial Communications Board
Standard system protocol
Sequence No. 001
Sequence No. specification
Step 0
Step 1
Messages
* Send/receive messages are stored in the area one or more words after the send data address or the receive data address specified in the
PMCR(
) instruction.
RS-232C or
RS-422A/485
OMRON devices
I/O memory Shared memory
I/O refreshing
Note The devices for which standard system protocols are provided are listed
below. For details, refer to 5-7 Using Protocol Macros.
Digital Controllers (E5 @ K, ES100 @ ), Temperature Controllers (E5ZE,
E5 @ J), Intelligent Signal Processors (K3T @ ), Bar Code Readers (V500/
V520), Laser Micrometers (3Z4L), Visual Inspection Units (F200/F300/
F350), ID Controllers (V600/V620), Hayes Modem AT Command, and devices supporting the CompoWay/F protocol.
63
Overview of the Protocol Macro Functions
Modifying Standard
System Protocols
Section 5-1
If there is no standard system protocol for the required OMRON product or you wish to modify part of the protocol, you can use the CX-Protocol to modify a standard system protocol, transfer this as a separate communications sequence to the Serial Communications Board, and execute the PMCR(
) instruction.
CPU Unit
Sequence number
I/O memory
Modifying and transferring standard system protocols
Serial Communications Board
Sequence No. specification
Modified standard system protocol
Step 0
Step 1
Step 2
Command execution (SEND, RECEIVE,
SEND&RECEIVE)
Messages
RS-232C or
RS-422A/485
General-purpose external device
Shared memory
I/O refreshing
Creating a New Protocol
When connecting a general-purpose external device that has an RS-232C or
RS-422A/485 port, use the CX-Protocol to create a new protocol containing the communications specifications for the general-purpose external device, transfer these specifications to the Serial Communications Board, and execute the PMCR(
) instruction.
CPU Unit
Sequence number
I/O memory
Sequence No. specification
Creating and transferring a new protocol
Serial Communications Board
Newly created protocol
Command execution (SEND, RECEIVE,
SEND&RECEIVE)
Messages
Step 0
Step 1
Step 2
RS-232C or
RS-422A/485
General-purpose external device
Shared memory
I/O refreshing
64
Restrictions in Using the CX-Protocol
Section 5-2
In this manual, the protocol structure is explained in simple terms, and examples are given of the use of the PMCR(––) instruction when controlling
OMRON devices using standard system protocols. For details on the protocols, the method of modifying the standard system protocols, and the method of creating new sequences, refer to the CX-Protocol Operation Manual
(W344).
5-1-4 Storage Memory
The protocol macros are stored in flash memory in the Serial Communications Board and will be saved even if power to the CQM1H is turned OFF. The
PC Setup settings for the Serial Communications Board are stored in memory in the CPU Unit with a battery backup.
5-2 Restrictions in Using the CX-Protocol
There are some restrictions in using the CX-Protocol to manipulate protocols or perform other operations for the CQM1H-series Serial Communications
Board. These restrictions are described below.
• Pin 8 on the DIP switch on the front of the CQM1H-series CPU Unit must be turned ON to use the CX-Protocol. While pin 8 is ON, you will not be able to use any of the CPU Unit or Board ports for the CX-Programmer,
SYSMAC-CPT, or SYSMAC Support Software.
• The model of PC must be set to the C200HG and the model of CPU Unit must be set to the CPU43.
• Refer to the following table for details and for other restrictions. Unless specified, the functionality of the CX-Protocol will be the same as for the
C200HX/HG/HE.
Item
CQM1H DIP switch settings
Restriction
Turn ON pin 8 on the DIP switch on the front of the
CQM1H-series CPU Unit before attempting to use the
CX-Protocol. You will not be able to use the CX-Protocol while pin 8 is OFF.
While pin 8 is ON, you will not be able to use any of the
CPU Unit or Board ports for the CX-Programmer, SYS-
MAC-CPT, or SYSMAC Support Software. Always turn
OFF pin 8 after you are finished using the CX-Protocol.
Set the model of PC to the C200HG and the model of
CPU Unit to the CPU43-E.
Procedure
Turn ON pin 8 before using the CX-Protocol.
Turn OFF pin 8 after you are finished using the CX-Protocol.
PC model setting
(to create new protocols)
Transferring protocols to the computer
You will not be able to upload the data for the standard system protocols from the Board to the computer. If an attempt is made, the transfer will be canceled and the following message will appear. (The standard system protocol data in the Board will not be affected.)
Decompiler has detected an error. No protocol data or invalid protocol list on upload. It is likely that the previous download was interrupted or the PMSU memory has been cleared/damaged. Try to download a valid protocol and retry upload.
You will be able to download protocol data from the computer to the Board (including data for the standard system protocols) and will then be able to upload the data.
To modify the standard system protocols for your applications, modify the data provided with the CX-Protocol and then download the data to the Board.
1.
Select New from the File Menu.
2.
Select C200HG from the Change PLC
Dialog Box.
3.
Select CPU43-E from the Settings Dialog Box.
---
65
Application Procedure
Section 5-3
Item
Communications port settings on the Board
I/O memory operations: PLC Memory Window
Error log
I/O tables
Restriction
Use the same communications port settings for the
Board as those used for the C200HX/HG/HE. The communications port names will be as follows:
Communications Port A will be port 1 on the Board.
Communications Port B will be port 2 on the Board.
Procedure
1.
Double-click the PC icon while online.
2.
Double-click the Communications Port
A or Communications Port B Icon in the Project Window.
3.
Make the settings in the Communications Port Settings Dialog.
Use I/O memory addresses only within the ranges supported by the CQM1H. Do not attempt to edit addresses
IR 256 and higher in the IR Area (displayed without the prefix) even though these addresses will be displayed.
The following restrictions apply when transferring I/O memory.
When transferring from the computer to the PC, do not select All. Use Selection or Range and specify a range that lies between IR 000 and IR 255.
When transferring from the PC to the computer, do not select All. Use Visible area only or Selection and specify a range that lies between IR 000 and IR 255.
The error log cannot be used. If it is displayed, the contents will not agree with the error log in the CQM1H.
The I/O tables are not necessary for the CQM1H and will be disabled. If an attempt is made to create I/O tables, the following message will be displayed and the I/O tables will not be created.
! The PLC does not contain an IO Table.
---
1.
Click the PC icon and select Memory from the pop-up menu. The PLC Memory Window will be displayed.
2.
Select the I/O memory areas and address to be displayed or edited in the
Data Area Workspace.
1.
Double-click the memory area in the
Data Area Workspace. The PLC Data
Table will be displayed.
2.
Specify the range of addresses to be transferred if necessary.
3.
Select Transfer to PLC via Online or
Transfer from PLC via Online from the Online Menu.
---
5-3 Application Procedure
1,2,3...
1.
Turn OFF the power to the PC.
2.
Install the Board.
3.
Connect the system.
Connect the external devices using RS-232C or RS-422 cable. The settings of the TERM and WIRE switches on the front panel of the Board will need to be changed if the RS-422A/485 port on the Serial Communications Board is used.
Serial Communications Board
Terminating resistance ON
External device
External device
External device
Terminating resistance ON
External device
Connect a Programming Console, the CX-Programmer, or the CX-Protocol to the CPU Unit as required.
4.
Turn ON power to the PC.
5.
Set the PC Setup settings for the Serial Communications Board.
Use the Programming Console, CX-Programmer, or CX-Protocol to set the settings in DM 6550 to DM 6559.
66
Application Procedure
Section 5-3
Note The PC Setup settings for the Serial Communications Board are read constantly during PC operation. It is not necessary to restart the PC after changing these settings.
The default settings are shown in the following table. These are the standard settings for protocol macros.
Port 1 Port 2 Bit(s) Setting
DM 6555 DM 6550 00 to 03 0 Hex
04 to 07 ---
08 to 11 ---
12 to 15 6 Hex
DM 6556 DM 6551 00 to 07 ---
08 to 15 ---
DM 6557 DM 6552 00 to 15 ---
DM 6558 DM 6553 00 to 15 ---
DM 6559 DM 6554 00 to 15 ---
Function
Standard port settings (1 start bit,
7-bit data, even parity, 2 stop bits,
9,600 bps)
Not used.
Not used.
Communications mode:
Protocol macro
Baud rate setting disabled.
Frame format setting disabled.
Not used.
Not used.
Not used.
6.
Run the system as described below in Using Standard System Protocols or in Using User-created Protocols.
Using Standard System Protocols
CPU Unit
Executed with
PMCR(—)
Uses standard system protocol No. 600
Serial Communications
Board
External device
Example: K3N Series
Digital Panel Meter
Input condition
1,2,3...
1.
Setting the Send Data
Refer to information on the 2nd operand of PMCR(
) in Appendix B Com-
poWay/F Master Protocol and set the number of send data words in S, and set the send data starting in S+1.
2.
Coding PMCR(
)
The following example shows how to use a Serial Communications Board to read the present value for a K3N-series Digital Panel Meter using the
CompoWay/F Master standard system protocol sequence No. 600: Send/
Receive with ASCII Conversion and Response.
Protocol Macro
Executing Flag
PMCR
#1600
DM0000
DM1000
1: Use port 1, 600: Sequence No. 600
First word of send data
First storage word for receive data
If the input condition turns ON when the Protocol Macro Executing Flag
(IR 20708 for Port 1) is OFF, communications sequence No. 600 of the standard system protocol in the Serial Communications Board is called, and data is sent and received via port 1 of the Serial Communications
Board.
67
Application Procedure
Section 5-3
Send Data
S:D00000
D00001
D00002
D00003
D00004
D00005
D00006
0007
0000
0101
000C
C000
0000
0001
7 words from D00000 to D00006
K3N node No. : 00
CompoWay/F command "0101" (reads the K3N present value)
Number of send bytes
CompoWay/F command send data
(Variable type, read start address, 00, number of elements)
Receive Data
D:D00010
D00011
D00012
D00013
0004
4 words from D00010 to D00013
Response code is stored.
The read data (in this case, the present value of K3N) is stored.
3.
Executing the PMCR(
) instruction
4.
For details on confirming operation, see Section 12 Tracing and I/O Mem-
ory Monitoring in the CX-Protocol Operation Manual (W344).
• Transmission Line Tracing
The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced.
• I/O Memory Monitoring
Monitors send/receive data and the status of the various flags.
Using User-created Protocols
CX-Protocol
CPU Unit
Use the CX-Protocol to create protocols.
PMCR(—)
1,2,3...
External device
Serial
Communications
Board
Section references in the following procedure refer to the CX-Protocol
Operation Manual (W344).
1.
For details on designing protocols, see Section 4 and Section 5.
a) Create a communications sequence status transition chart.
b) From the status transition chart, divide the processing contents into sequence steps.
c) Determine the send/receive message contents.
2.
Use the CX-Protocol to create and send a project (protocol data).
a) Creating a new project:
See 5.1 Creating a New Project or Protocol.
b) Creating a new communications sequence:
See 5.2 Creating a New Sequence or 7.1 Setting a Sequence.
c) Creating steps:
See 5.2 Creating a New Sequence and 8.1 Setting a Step.
d) Creating messages:
See 9.1 Setting a Message.
Note After creating messages, steps can also be created by specifying message names.
68
Application Procedure
Section 5-3
Input condition e) Transferring the created project to the Board:
See 11.1 Transferring and Reading Protocol Data between Personal
Computers and Serial Communications Boards.
3.
Create the ladder program.
a) Setting Send Data
• Specifying Operands
Set the send data in the I/O memory after the S+1 operand of the PM-
CR(
) instruction. Set the number of send data words (including S itself) in S.
• Direct Designations
Set the send data in the I/O memory specified by the read variables in the send message.
• Specifying Link Words
Set the send data in the O1 or O2 area of the Link Word Area.
b) Coding PMCR(
)
Protocol Macro
Executing Flag
PMCR
#1100
DM0000
DM1000
1: Use port 1, 600: Sequence No. 100
First word of send data
First storage word for receive data
If the input condition turns ON when the Protocol Macro Executing Flag
(IR 20708 for port 1) is OFF, communications sequence No. 100 registered in the Serial Communications Board is called, and data is sent and received via port 1 of the Serial Communications Board.
The amount of send data depends on the number of words specified in
DM 0000 (the number of words after DM 0001 plus 1 for DM 0000 itself), and is sent from the next word after DM 0001.
Number of send words plus 1 for DM 0000
S: DM 0000
Number of words
Send data
Number of words
The receive data is stored in consecutive words beginning with DM 1000, and the number of words actually stored in DM 1000 (the number of words after DM 1001 plus 1 for DM 1000 itself) is stored.
Number of receive words plus 1 for DM 1000
D: DM 1000
DM 1001
Number of words
Receive data
Number of words c) Execute PMCR(
)
4.
For details on the confirming operation, see Section 12 Tracing and Moni-
toring.
• Transmission Line Tracing
The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced.
• I/O Memory Monitoring
Monitors send/receive data and the status of the various flags.
69
Connections
Section 5-4
5-4 Connections
Port
RS-232C
Configuration
1:1
This section describes the connections for protocol macros. Up to 32 nodes can be used for 1:N connections.
Schematic diagram
RS-232C
RS-232C 1:N
RS-232C interface
NT-AL001-E
RS-232C
RS-422A/485
Resistance
ON
NT-AL001-E
Resistance ON
5-V power
RS-232C interface
NT-AL001-E
RS-232C
RS-422A/485
Resistance
ON
RS-422A/
485 interface
NT-AL001-E
RS-232C
Resistance ON
RS-422A/485
RS-422A/485 interface
RS-422A/485 1:1
Resistance ON
NT-AL001-E
3G2A9-AL001
RS-232C
Resistance
ON
RS-422A
/485
RS-422A/485 interface
NT-AL001-E
RS-232C
Resistance
ON
RS-422A/485
Resistance ON
NT-AL001-E
RS-232C
RS-232C interface
RS-232C
RS-232C
Resistance ON
5-V power
RS-422A/485
RS-422A/485 interface
NT-AL001-E
RS-232C
RS-232C interface
RS-422A/485
Resistance ON
5-V power
70
Connections
Port
RS-422A/485
Configuration
1:N
Resistance
ON
Schematic diagram
RS-422A/485 interface
RS-422A/485
Resistance ON
Resistance
ON
RS-422A/485
3G2A9-AL001
RS-422A/485 interface
Section 5-4
Resistance ON
NT-AL001-E
RS-232C
RS-232C interface
Resistance
ON
RS-422A/485
RS-232C
RS-232C
Resistance ON
5-V power
Note
1.
The maximum cable length for RS-232C is 15 m.
2.
The maximum combined cable length for RS-422A/485 is 500 m including branch lines.
3.
The maximum cable length is limited to 2 m when an NT-AL001-E Link
Adapter is connected.
4.
Branch lines must be a maximum of 10 m long.
5.
Up to 32 nodes can be used for 1:N connections. With a 2-wire connection, this figure includes the Communications Board itself, whereas with a 4wire connection, it does not (i.e., up to 32 devices can be connected).
Connection Examples
The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twistedpair cables. Refer to 2-3 Wiring for actual wiring methods.
Connecting RS-232C
Ports 1:1
Connections to E5CK Controller
Serial Communications
Board
Signal Pin
FG
SD
RD
RTS
CTS
DSR
DTR
SG
D-sub, 9-pin connector (male)
RS-232C
Shield
OMRON E5CK Controller
Terminal Signal
SD
RD
SG
Terminal block
71
Connections
Section 5-4
Connecting a Host Computer with NT-AL001-E Converting Link Adapters
Serial Communications
Board
RS-232C
Interface
Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
Pin
RS-232C
Shield
NT-AL001-E Link Adapter
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
(See note)
D-sub, 9-pin connector (male)
Terminal block
RS-422A
NT-AL001-E Link Adapter
Pin
Signal
Signal
Pin
Computer
RS-232C
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
FG
SD
RD
RTS
CTS
DSR
DTR
SG
RS-232C
Interface
Terminal block D-sub, 9-pin connector (male)
D-sub, 9-pin connector (female)
5-V (+) power (
−
)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF (4-wire)
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF (4-wire)
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
Connections to a Modem
Modem
FG
SD
RD
RTS
CTS
DSR
SG
CD
Serial Communica tions Board
RS-232C port
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
ST2
RT
DTR
CI
ST1
D-sub, 25-pin connector
72
Connections
Section 5-4
1:N Connections Using RS232C Ports
Serial Communications
Board NT-AL001-E
Signal Pin
RS-232C
Shield
FG
SD
RD
RS-232C interface
RTS
CTS
5V
DSR
DTR
SG
Pin Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
Signal Pin
(See note)
D-sub, 9-pin Terminal block connector (male)
DIP SW
Pin 1: ON
Pin 2: ON Terminating resistance
Pin 3: OFF 4-wire
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
RS-422A
Shield
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A
/485 interface
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A
/485 interface
Serial Communications
Board
Signal
Pin
RS-232C
Shield
RS-232C interface
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
(See note)
Pin
NT-AL001-E
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal
Pin
D-sub, 9-pin Terminal block connector (male)
DIP SW
Pin 1: ON
Pin 2: ON Terminating resistance
Pin 3: ON 2-wire
Pin 4: ON
Pin 5: OFF
Pin 6: ON
Device supporting
RS-422A/485 communications
(2-wire)
Signal
RS-422A
/485 interface
Device supporting
RS-422A/485 communications
(2-wire)
Signal
RS-422A
/485 interface
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
73
Connections
Section 5-4
1:1 Connections Using RS422A/485 Ports
Serial Communications Board
Signal Pin
Shield
Device supporting
RS-422A/485 communications
(2-wire)
Signal
RS-422A
/485 interface
RS-422A
/485 interface
Hood
D-sub, 9-pin connector (male)
Serial Communications Board
Signal
Pin
Shield
RS-422A
/485 interface
Hood
D-sub, 9-pin connector (male)
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A
/485 interface
Serial Communications Board
Signal
Pin
RS-422A
Shield
RS-422A
/485 interface
Hood connector (male)
Terminating resistance ON
4-wire
D-sub, 9-pin
NT-AL001-E Link Adapter
Pin
Signal Signal
Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Computer
RS-232C
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
Terminal block
D-sub, 9-pin connector
(male)
D-sub, 9-pin connector (male)
5-V (+) power (
−
)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
74
Connections
Section 5-4
1:N Connections Using RS422A/485 Ports
Serial Communications Board
Signal Pin
RS-422A/
485 interface
Hood
Device supporting RS-422A/485 communications (2-wire)
Signal
RS-422A/
485 interface
Device supporting
RS-422A/485 communications
(2-wire)
D-sub, 9-pin connector (male)
Terminating resistance ON
4-wire
Serial Communications Board
RS-422A/
485 Interface
Signal
Pin
Hood
D-sub, 9-pin connector (male)
Terminating resistance ON
4-wire
Signal
Pin
Signal RS-422A/
485 interface
3G2A9-AL001
Pin
Signal
Signal Pin
Shield
Device supporting
RS-422A/485 communications
(4-wire)
RS-422A/
485 interface
Signal
RS-422A/
485 interface
D-sub, 9-pin connector (male)
Device supporting
RS-422A/485 communications
(4-wire)
Shield
Signal
RS-422A/
485 interface
Serial Communications Board
Signal
Pin
RS-422A/
485 Interface
Hood
D-sub, 9-pin connector (male)
Terminating resistance ON
4-wire
Shield
NT-AL001-E Link Adapter
Pin
Signal Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
Shield
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
DIP Switch
Pin 2: OFF, otherwise same as below.
D-sub, 9-pin connector (male)
(+) 5-V
(
−
) power
DIP Switch
Pin 1: ON
Pin 2: ON (terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Shield
NT-AL001-E Link Adapter
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Terminal block
D-sub, 9-pin connector
(male)
Shield
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
(+) 5-V
(
−
) power
75
Protocol Structure
Section 5-5
5-5 Protocol Structure
Protocols consist of communications sequences. A sequence consists of steps. These steps can be repeated, or they can be branched or ended depending on the responses received. A step consists of a command, send/ receive messages, processing results, and the next process (which depends on the processing results).
Example: Reading the process values for a Temperature Controller
Protocol
Communications sequence
Step 0
Step 1
Transmission of process value reading message and reception of response message
Messages
CPU Unit
A protocol consists of processing sequences (such as reading the process value for a Temperature Controller) for a general-purpose external device. A sequence consists of a group of steps, each of which consists of a send/ receive/control command, send/receive message, processing result, and a next step that depends on the processing results.
For example, with a sequence that reads the process value for a Temperature
Controller, the sequence sends the send message for the connected Temperature Controller (a character string in which the Process Value Read command is inserted between the header + address and the check code + terminator) and receives the receive message (a character string in which the
Process Value Read command response is inserted between the header + address and the check code + terminator).
Command
Send message (Example: PROCESS VALUE READ command)
SEND
RECEIVE
Header Address Send data Check code
Terminator
Receive message (Example: Response)
RS-232C or
RS-422A/485
Header Address Send data Check code
Terminator
Serial Communications Board
General-purpose external device
76
Protocol Structure
Section 5-5
Depending on the response received, the user can either choose to resend the same send message (retry processing), or to perform the next process
(for example, read the process value for a Temperature Controller with a different address).
One protocol
Sequence No. 000 to 999
(60 sequences max./protocol)
Step 0
Step 1
Step 0
Step 1
Transmission control parameter
Link word setting
Send/receive processing monitoring time
Response notification method
15 steps max.
15 steps max.
One-step structure
With the SEND, RECEIVE, or
SEND&RECEIVE command
Command (See note 1.)
Messages (See note 2.)
Normal end
N (error)
Y
Retry?
(See note 3.)
N (no)
Message list (See note 2.)
Send message list
Header Address Data Check Terminator
Receive message list
Repeated
Y
N (no)
Next process
•
Next step
•
To specified step
•
Sequence end
•
Sequence interrupt
Error processing
Header Address Data Check Terminator
Reception matrix list (See note 2.)
Reception matrix
Case No. 15
Case No. 00
Receive message Next process
Sequence Parameters
Note
1.
The SEND, RECEIVE, or SEND&RECEIVE commands can be used.
2.
Three types of reception matrix are available for switching the processing, depending on whether the messages are send messages, receive (wait) messages, or multiple receive (wait) messages. Unlike sequences, these matrixes are managed as lists.
3.
Retries are possible on for the SEND&RECEIVE command.
Parameter Meaning
Transmission control parameters Control methods, such as flow control
Link words Settings for shared words between the PC and the Serial Communications Board.
Monitoring time
Response notification method
Monitoring time for send/receive processing
Timing for writing received data to I/O memory in the PC
77
Protocol Structure
Section 5-5
Step Parameters
Command
Messages
Repeat counter
Retry count
Send wait time
Response write enable (for operand specification)
Next process
Parameter Meaning
One of the following: SEND, RECEIVE, or
SEND&RECEIVE
Send message The message sent for SEND.
Receive message
The expected message for RECEIVE.
Send message and receive message
Reception matrix
The message sent and the expected message for SEND&RECEIVE.
A group of expected messages that can be used to switch to different next processes when RECEIVE or
SEND&RECEIVE is used.
The number of times to repeat the step (0 to 255). The repeat counter can be used to change send/receive messages.
Used for SEND&RECEIVE to retry the command for errors
(0 to 9).
Used for SEND or SEND&RECEIVE to create a wait time before sending data.
Specification of whether or not to write the received data to memory.
Error processing
Specifies the next step or to end the sequence when the current step is completed normally.
Specifies the next step or to end the sequence when the current step ends in an error.
Standard System Protocol Example
Process Value Read Sequence for E5
@
K Controller Read Protocol
Sequence
Level
Steps
Item
Link words ---
Transmission control parameters
Response notification method
Modem control
Scan
Reception wait time Tr 3 s
Reception finished wait time Tfr
3 s
3 s Send finished wait time
Tfs
Step number
Repeat counter
Command
Retry count
Send wait time
Send message
Receive message
00
Reset/001
SEND&RECEIVE
3
---
SD (00) _1
RV (00) _1
Response write enable Write
Next process End
Error process Abort
Setting
78
Protocol Structure
Section 5-5
Level
Send message
SD (00) _1
Receive message
RV (00) _1
Handling
Communications
Problems for Standard
System Protocols
Item
Header <h>
Terminator <t>
Error check code <c>
Length <l>
Address <a>
Message edited
Header <h>
Terminator <t>
Error check code <c>
Length <l>
Address <a>
Message edited
Setting
“@”
[2A0D]
LRC (horizontal parity) (0) (2 bytes of ASCII)
---
$ (R (1) ) ,2)
<h> + <a> + "1" + "00" + "0000" + <c> + <t>
Data
“@”
[2A0D]
LRC (horizontal parity) (0) (2 bytes of ASCII)
---
& (R (1) ) ,2)
<h> + <a> + "00" + "00" + & (W (1) ,4) + <c> + <t>
Data
The CQM1H-series PCs provide standard system protocols to enable communications with OMRON components without having to create communications sequences. The sequences in the standard system protocols can be executed merely by setting operands for the PMCR(
) instruction.
Processing for communications line problems during communications for the standard system protocols are set to normal settings, as shown in the following table. If these settings are not suitable to the application or if improvements are desired, use the CX-Protocol to modify the following settings in the required sequences. For details on the use of the CX-Protocol, refer to the
CX-Protocol Operation Manual (W344). Refer to the appendices for the settings in the standard system protocols.
Level
Sequence parameters
Step parameters
Item
Link words
Transmission control parameters
Response notification method
Possible changes in settings
No reason to change.
Reception wait time Tr The monitoring times are set to 3 seconds for
Reception finished wait time Tfr
Send finished wait time Tfs most sequences. The settings are different for send-only and receive-only sequences, as well as for sequences that require time for responses.
Repeat counter
Command
No reason to change.
Retry count The retry count is general set to 3 retries (4 tries total) for sequences that use the
SEND&RECEIVE command. Different settings are used for sequences that have other commands.
No reason to change.
Send wait time
Send message
Receive message
Response write enable
Next process
Error process
79
Control Bits, Flags, and Status Information
Section 5-6
5-6 Control Bits, Flags, and Status Information
Control bits, flags, and status information for the Serial Communications
Board are available in the Inner Board Slot 1 area. The addresses in this area are as follows:
Inner Board Slot 1 Area: IR 200 to IR 207
All of the bits in the following table are initialized (cleared) when power to the
PC is turned ON, when the mode is changed between PROGRAM and RUN/
MONITOR mode, when the STUP(
) instruction is executed to change the serial communications mode, or when the communications port is restarted.
The bits are also reset at the timing indicated in the Reset column in the table.
Word
IR 200 00
01
02
11
12
13
14
15
Bits Name and Function
Serial Communications Board Hardware Error Flag
Turns ON if an error occurs in the Board. Replace the Board if this flag will not turn OFF even after remounting the Board securely or mounting it in a different CPU Unit.
Board Identification Error Flag (hardware error)
Replace the Board if this flag turns ON.
Protocol Data Error Flag
This flag turns ON if an error is detected in the protocol data checksum when the power is turned ON. The ERR indicator on the CPU Unit will also flash and the RDY indicator will flash.
This error may occur if the communications connector becomes disconnected or the PC power is turned OFF during protocol data transfer. Use the CX-Protocol to transfer of the protocol data again.
Port 2 Protocol Macro Execution Error Flag
The flag turns ON when the protocol macros are not supported (error code 1), there is a sequence number error
(error code 2), an attempt was made to write data receive data at an illegal address (error code 3), or a protocol data syntax error occurred (error code 4).
Port 1 Protocol Macro Execution Error Flag
Same as IR 20011.
PC Setup Error Flags
Bit 15 turns ON if a Setup error occurs in the PC Setup settings for the Board.
Bit 14 will turn ON if the error is for port 1.
Bit 13 will turn ON if the error is for port 2.
Correct the PC Setup.
The defaults will be used for the settings causing th error.
Classification
System error
Set
When error occurs
Reset
Power ON
Normal completion of protocol data transfer
Start of sequence
Power ON
80
Control Bits, Flags, and Status Information
Section 5-6
Word Bits Name and Function
IR 201 00 to 03 Port 1 Error Code (Transmission Error Status)
When an error occurs during transmissions for a protocol macro, an error code will be output to these bits.
0: Normal operation1: Parity error2: Framing error
Error codes 3 to 7 are not possible for protocol macros.
04
These error codes are the same regardless of the serial communications mode.
IR 20104 will also turn ON except when the error code contains all zeros. SEND&RECEIVE retry processing will be performed for any error.
If communications are recovered through protocol macro retry processing, the error code will be cleared, but will be maintained even if a different error occurs during the retry.
Port 1 Communications Error Flag
07
This flag turns ON when an error occurs in the communications path between the communications port and the external device or when communications parameters are not set correctly.
The operation of this flag is the same regardless of the serial communications mode.
Details on the error are output as an error code to IR 20100 to IR 20103.
Port 1 Sequence Abort Completion Flag
This flag turns ON when a sequence has been aborted due to ABORT in the next process or in the error process. It will be OFF if an abort has not occurred.
Classification
Transmission error
Sequence status
08 to 11 Port 2 Error Code (Transmission Error Status)
Same as bits IR 20100 to IR 20103, but works together with
IR 20112.
12
Port 2 Communications Error Flag
Same as bits IR 2014, but works together with IR 20108 to
IR 20111.
15
Port 2 Sequence Abort Completion Flag
Save as IR 20107.
Transmission error
Sequence status
Set
When error occurs
When sequence is aborted
When error occurs
IR 202 00 to 07 Port 1 Repeat Counter PV (00 to FF hexadecimal)
The repeat counter variable N is set. The value is cleared when the sequence execution starts.
The present value N varies according to the method used to initialize the value. For resets, the variable N is set to 0 when the step is started, and the step is executed according to the set number of times. For holds, the variable N for the present value is held when the step is started, and the step is executed according to the set number of times.
If the Repeat Counter Setting Value is set to read word
R ( ), and 0 is read, then 0 will be stored and this step will be skipped (the next process setting will be ignored), and the sequence will move to the next step (+1). For details, refer to the CX-Protocol Operation Manual (W344).
IR 203 00 to 07 Port 2 Repeat Counter PV (00 to FF hexadecimal)
Same as IR 20200 to IR 20207.
Sequence status
When sequence is aborted
When repeat count is refreshed
Reset
Start of sequence
81
Control Bits, Flags, and Status Information
Section 5-6
Word
IR 204 00
Bits Name and Function
Port 1 Tracing Flag
According to instructions from the CX-Protocol, this flag is turned ON while time-series data for send and receive messages is being traced.
Classification
Tracing
01
Port 2 Tracing Flag
Same as IR 20400.
08 to 11
Port 1 Protocol Macro Error Code
The list of error codes is provided at the end of this table on
If error code 1, 2, 3, or 4 is stored, the Port 1 Protocol Macro
Execution Error Flag (IR 20111) will be turned ON, the
ERR/ALM indicator on the CPU Unit will flash, and a nonfatal error will occur.
When an error occurs, the error code is held until the next sequence starts.
The error must be cleared from a Programming Console or other Programming Device after the cause of the error has been eliminated.
Protocol macro status
12 to 15
Port 2 Protocol Macro Error Code
Same as IR 20408 to IR 20411, but works together with
IR 20112.
IR 205 00 to 03 Port 1 Executed Reception Case No. (code)
Reception matrix case numbers 0 to 15 (0 to F hex) are stored for which reception has been completed. The number is cleared when the sequence execution starts.
The Executed Reception Case No. is stored only when the reception matrix is set using the RECEIVE or
SEND&RECEIVE command. If a reception matrix is not set, the case number will be set to 0 (cleared) when another command is executed.
Sequence status
04 to 07
Port 1 Completed Step Number
Step numbers 0 to 15 (0 to F hex) are stored for the steps for which execution has been completed.
15
IR 204 Port 1 Data Stored Flag
0: No data stored; 1: Data stored in IR 20408 to IR 20411
IR 206 00 to 03 Port 2 Executed Reception Case No. (code)
Same as IR 20500 to IR 20503.
04 to 07
Port 2 Completed Step Number
Same as IR 20504 to IR 20507.
IR 205 15
IR 204 Port 2 Data Stored Flag
0: No data stored; 1: Data stored in IR 20412 to IR 20415
Protocol macro
Sequence status
Protocol macro
Set
When error occurs
When matrix is received
When step is executed
When error occurs
When matrix is received
When step is executed
When error occurs
Reset
Start of trace Start of sequence or end of trace
Start of sequence
82
Control Bits, Flags, and Status Information
Section 5-6
Word
IR 207 00
01
02
03
04
05
08
09
10
Bits Name and Function
Port 1 Restart Bit
The communications port will be restarted when this bit is turned ON by the user.
Port 2 Restart Bit
Same as IR 20700.
Port 1 Continuous Trace Start/Stop Bit
The CX-Protocol will start a continuous trace when the bit is turned ON. The trace is ended when the bit is turned OFF.
The CPU Unit will manipulate the Shot Trace Bit and Continuous Trace Bit when trace operations are performed from the CX-Protocol. Do not manipulate these bits directly from a ladder diagram.
Classification
Tracing
Set
Port status User-set or
STUP(
)
From CX-
Protocol
Port 2 Continuous Trace Start/Stop Bit
Same as IR 20702.
Port 1 Shot Trace Start/Stop Bit
The CX-Protocol will start a one-shot trace when the bit is turned ON. The trace is ended when the bit is turned OFF.
The Serial Communications Board will be cleared when the trace buffer becomes full.
The CPU Unit will manipulate the Shot Trace Bit and Continuous Trace Bit when trace operations are performed from the CX-Protocol. Do not manipulate these bits directly from a ladder diagram.
Port 2 Shot Trace Start/Stop Bit
Same as IR 20704.
Port 1 Protocol Macro Executing Flag (instruction execution)
This flag is turned ON when a PMCR(––) instruction
(sequence) is executed. The flag will remain OFF if execution fails.
When the sequence is completed and receive data is written, the flag is turned OFF after all the receive data has been written to I/O memory.
This flag is turned OFF when the sequence is completed
(either when it is ended by End, or when it is ended by
Abort).
When the scan response notification method is set for the sequence, first a check is made to see if the received data has been written to I/O memory before the Protocol Macro
Executing Flag is turned OFF.
Port 1 Transfer Step Error Processing Flag
This flag is turned ON when a step has ended abnormally. It is turned OFF if the step ends normally as a result of a retry.
1: Step ended abnormally
0: Step ended normally
Port 1 Sequence END Completion Flag
This flag is turned ON when a sequence is completed for the next process or for an error process with an END command.
Setting END when a sequence has ended normally and setting ABORT when the sequence has ended abnormally enables this flag to be used to determine whether or not the sequence execution has ended normally.
1: Sequence ended
0: Sequence not ended
Protocol macro status
At instruction execution
Step error At compare error after reception
Sequence status
End of sequence
Reset
After settings are changed and port restarted
From CX-
Protocol
At end of short trace
At completion of execution
Start of sequence
83
Using Protocol Macros
Section 5-7
Word
IR 207 11
Bits
12
13
14
15
Port 2 Sequence END Completion Flag
Same as IR 20710.
Port 2 Forced Abort Bit
Same as IR 20711.
Name and Function
Port 1 Forced Abort Bit
Protocol processing will be aborted when this bit is turned
ON. (Processing may be completed if the bit is turned ON too late.)
Port 2 Protocol Macro Executing Flag (instruction execution)
Same as IR 20708.
Port 2 Transfer Step Error Processing Flag
Same as IR 20709.
Classification
Abort processing
Protocol macro status
Set
User-set
At instruction execution
Step error At compare error after reception
Sequence status
End of sequence
Abort processing
User-set
Reset
User-set
At completion of execution
Start of sequence
User-reset
Error Codes
The contents of the error codes are shown in the following table.
Code
0
2
3
4
5
No error
Error contents Protocol macro execution
Executed
Sequence Number Error
The sequence number specified by the PMCR(
) instruction does not exist in the Board.
Not executed
Receive Data/Write Area Exceeded Error
When data is written or read to the CPU Unit, the specified area range was exceeded.
Protocol Data Syntax Error
A code that cannot be executed occurs while the protocol macro was executed. (Example: A header occurs after a terminator.)
Execution stops after the error occurs.
Protocol Macro Execution Error During Port
Initialization
This error occurs when the PMCR instruction is executed while the port is being initialized (i.e., while the serial communications port is being restarted or while the serial communications mode in the PC Setup of the Serial Communications Board is being modified using the STUP instruction or the Programming Device).
Execution stops after the error occurs.
5-7 Using Protocol Macros
5-7-1 Executing Communications Sequences
Use the PMCR(
) instruction to execute communications sequences.
PMCR(
) Instruction Specifications
Control data
First send word
First receive data storage word
84
Using Protocol Macros
Section 5-7
Control Data: C
C:
15 00
Digits 2 to 4 (bits 00 to 11):
Communications sequence number (000 to 999)
Digit 1 (bits 12 to 15): Port specifier
1: Port 1 (RS-232C)
2: Port 2 (RS-422A/485)
First Send Data Word: S
S
S+1
:
:
S+n
15
S specifies the first word of the words containing the data required for sending.
00
Number of send words
Send data
:
:
Total number of words including S
The number of send words in S+1 and the following words is stored in S. The setting range is 0001 to 0129 (4 digits BCD). S is also included in the number of words.
Note When there is no send data, set S to #0000. If any other constant or a word address is set, an error will occur, the Error Flag (SR 25503) will turn ON, and
PMCR(
) will not be executed.
First Receive Data Storage
Word (D)
D specifies the first word of the area used to store the receive data.
If a word address is specified for D and a response is requested, the data through the highest location received in the reception buffer will be stored in memory starting at D+1. The number of words that was stored starting at D+1 will be stored in D. D is included in the number of words.
D
D+1
:
:
15
Number of receive words
Receive data
:
:
00
Total number of words including D
D+n
PMCR(
) Operation
The number of words of receive data in D+1 and the following words is stored in D. The range is 0001 to 0129 (4 digits BCD). D is also included in the number of words.
Note When there is no receive data, set D to to a dummy word address. If any constant is set, an error will occur, the Error Flag (SR 25503) will turn ON, and
PMCR(
) will not be executed.
When PMCR(
) is executed, the communications sequence specified in bits
00 to 11 of C is executed for the port specified in bits 12 to 15 of C (port 1 or
2).
If an operand is specified as a variable in the send message, data starting in
S+1 for the number of words specified in S is used as the send data. If an operand is specified as a variable in the receive message, data will be
85
Using Protocol Macros
Section 5-7
received in words starting from D+1 and the number of words of received data will be automatically stored in D.
Flags
Name
Error Flag
Address
SR 25503
ON
Indirectly addressed DM or EM word is non-existent. (Content of
*
DM/
*
EM word is not BCD, or the area boundary has been exceeded.)
Another PMCR(
) instruction was already in progress when the instruction was executed
(IR 20708 or IR 20712 is ON).
The port specifier was not 1 or 2.
Note: PMCR(
) will not be executed when SR
25503 is ON.
OFF
Other times.
Operand Areas and Address Ranges
Area C
IR and SR Areas
IR 000 to IR 255
HR Area
AR Area
LR Area
Timer and Counter
Area
HR 00 to HR 99
AR 00 to AR 27
LR 00 to LR 63
TIM/CNT000 to TIM/CNT511
S
Data Memory (DM)
Area
Extended Data
Memory (EM) Area
Indirect DM address
Indirect EM address
Constant Area
DM 0000 to DM 6655
EM 0000 to EM 6143
*DM 0000 to *DM 6655
*EM 0000 to *EM 6143
See description of control data.
#0000 to #FFFF
D
IR 000 to IR 252
DM 0000 to
DM 6143
---
5-7-2 Ladder Program Structure
When creating a ladder program, note the following points.
• To ensure that a PMCR(
) instruction is not executed while another
PMCR(
) instruction is being executed, use the Protocol Macro Executing Flag in an NC input condition.
• Use an OFF condition for the Protocol Macro Executing Flag and perform processing to read the results of sequence execution, or perform processing when a sequence ends in an error.
Programming Example
Input condition
Protocol Macro
Executing Flag
20708
PMCR
20708
A
DIFD (14) A
Reading of sequence execution results
Processing of sequence errors
86
Using Protocol Macros
Section 5-7
5-7-3 Ladder Program Example
The following diagram shows an example in which sequence number 000
(Present Value Read) for a Temperature Controller (E5 @ K Read Protocol) is executed using the protocol for an OMRON Temperature Controller connected to port 2 (RS-422A/485) of a Serial Communications Board.
Connections
Serial Communications Board
32 Units max.
Port 2
RS-422A/485
Specifies the Temperature Controller Unit No. , sends the PRESENT VALUE READ command send data, and receives the present value set in the response in the specified word.
Send data
Receive data
Temperature
Controller E5
Unit No. 00
@
K
Temperature
Controller E5
@
K
Unit No. 01
Temperature
Controller E5
@
K
Unit No. 31
31 Units max. for 2-wire connection
32 Units max. for 4-wire connection
Send Word Allocation for Sequence No. 000 (Present Value Read)
First word of send data
S
S + 1
Number of send data words
(Undefined) Unit No. S
Word Contents (data format)
Number of send data words
(4-digit BCD)
Data
0002 (fixed)
S + 1 Unit No.
(2-digit BCD)
00 to 31
Receive Word Allocation for Sequence No. 000 (Present Value Read)
Receive data storage words
D Number of receive data words
D + 1 Present value D
Word Contents (data format) Data
Number of receive data words
(4-digit BCD)
0002
D + 1 Present value
(4-digit BCD)
Scaling
Lower limit to upper limit
87
Using Protocol Macros
Section 5-7
Operand Settings for the
PMCR (
) Instruction
PMCR
#0000
D00100
D00200
Reading the present value of E5 @ K Unit No. 03 and storing it in DM 0201
C: Control data
1 0
Port 1
0 0
0000: Sequence No. 000
S: First send data word
S:
S+1:
DM 0100
DM 0101
Number of send data words = 2
Unit No. = 03
D: First receive data storage word
D:
D+1:
DM 0200
DM 0201
Present value
Number of receive data words = 2
Present value is stored.
(4-digit BCD)
88
Using Protocol Macros
Ladder Programming
Example
Section 5-7
The following diagram shows an example in which sequence number 000
(PRESENT VALUE READ) of a Temperature Controller (E5 @ K Read System) is executed using the PMCR(
) instruction. If the sequence has been completed normally, the present value that has been read is transferred to another word.
Input condition
000000
Protocol Macro
Executing Flag
20708
PMCR
#1000
DM 0100
DM 0200
If input condition IR 00000 is ON and the Protocol
Macro Executing Flag IR 20708 is OFF, then sequence
No. 000 is executed for Serial Communications Board port 1 and the present value is stored in DM 0201 and after.
Protocol Macro
Executing Flag
20708
Input condition
000100
Protocol Macro
Executing Flag
20708
Step Error
Processing Flag
20709
Step Error
Processing Flag
20709
DIFD (14) 00100
If Protocol Macro Executing Flag IR 20708 turns OFF,
IR 00100 turns ON (and remains ON for one cycle).
MOV (21)
DM 0201
DM 0300
If Protocol Macro Executing Flag IR 20708 is OFF and
Step Error Processing Flag IR 20709 is OFF when
IR 00100 turns ON, then the data received in DM 0201 is moved to DM 0300.
FAL (06) 01
If IR 00100 is ON (sequence end) and Step Error Processing Flag IR 20709 is ON, the sequence has ended abnormally and a FAL(06) instruction (FAILURE ALARM
AND RESET instruction) is executed.
Protocol Macro
Executing Flag
IR 20708
Sequence executed
Sequence completed
Sequence re-executed
00100
One cycle
Present value in DM 0201 moved to DM 0300
When sequence ended normally:
Step Error Processing
Flag IR 20709
FAL instruction executed
When sequence ended abnormally:
Step Error Processing
Flag IR 20709
Precaution on Reception Failures for PMCR(
)
The reception buffer is cleared to all zeros just before the communications sequence is executed. If programming is included in the ladder diagram to periodically read, it should be designed to read the data only when receptions are successful, and not when the contents of the buffer has been cleared to all zeros. The above ladder programming shows one way to achieve this.
89
Using Protocol Macros
Section 5-7
Transmission Methods
Although the following two transmission methods are commonly used, only half-duplex transmissions are supported for CQM1H protocol macros.
Half-duplex: Data can be sent only one direction at a time.
A B
Or
A B
Full-duplex: Data can be sent in both directions at the same time.
A B
The use of half-duplex transmissions presents some restrictions. Data received from just before the SEND operation through the end of the SEND operation cannot be received as receive data for the next RECEIVE operation because the reception buffer is cleared just before a sequence is executed and at the end of the SEND operation (i.e., for the SEND and
SEND&RECEIVE commands).
Transmission mode
Half-duplex
Reception buffer cleared Data reception Character trace
Just before sequence execution and at the end of SEND operation for SEND or SEND&RECEIVE commands
Between end of SEND operation and end of RECEIVE operation or between the end of SEND operation and just before beginning of next SEND operation
All characters while tracing is being performed
An example timing chart for the above situation is shown below.
Sequence execution
Reception buffer cleared
Receive Send Receive
Data received
Character trace
See note 1.
Note
1.
Data received before the completion of the SEND operation will be lost, but it will be included in the character trace.
2.
There is a time lag between the completion of data send processing and the end of the SEND operation. This time lag is time t1 and is shown in the following table. If the response from the external device is too quick, any receive data entering between the end of sending data for the SEND operation and the completion of the SEND operation will not be received.
SEND operation
Data send processing
Quick response
Data reception t1
Time lag (See table.)
Data not received here
Reception buffer cleared
90
Using Protocol Macros
Section 5-7
Time Lag t1
Baud rate (b/s)
1,200
2,400
4,800
9,600
19,200
30
5
3
15
8
Lag time (ms)
Note The lag time shown above is an approximate value. It may become longer depending on the protocol macro processing.
Error Flags for Overrun, Framing, and Parity Errors
When an overrun, framing, or parity error is detected during a protocol macro, the receive data will be stored in the reception buffer along with error information. The error flags will operate as described next.
Receive Data with Error Information that Matches Expected Receive
Messages
The expected receive message received for the RECEIVE operation is found in the reception buffer and handled as receive data. If the receive data contains error information, the corresponding error flags are turned ON.
The following example shows reception of 100 bytes of data that matches an expected receive message.
100 bytes
Error flags ON
Parity errors
Receive Data with Error Information that Does Not Match Expected
Receive Messages
If there is no expected receive message that matches the receive data, the data is discarded and the error flags are not affected. The trace information will contain any error information entering the reception buffer up to the capacity of the trace data.
The following example illustrated what happens when there is no expected receive message that matches the receive data.
Discarded
Error flags are not changed.
91
Using Protocol Macros
Section 5-7
In the following ladder programming, sequence number 000 (E5 @ K Digital
Controller Read) is executed through PMCR(
) to read the PV from the Digital Controller. When sequence execution has been completed, the PV is transferred to words to store it.
Execution condition
00000
Protocol Macro Exe cuting Flag
20708
Protocol Macro
Executing Flag
20708
00100
Protocol Macro
Executing Flag
20708
Transfer Step Error
Processing Flag
20709
PMCR
#1000
DM 0100
DM 0200
If IR 20708 is OFF when the execution condition turns ON, sequence #000 is executed and the PV is stored in DM 0201.
DIFD (14) 00100
When IR 20708 changes from ON to OFF, IR 00100 will turn ON for one cycle.
MOV (21)
DM 0201
DM 0300
If IR 00100 is ON, IR 20708 is OFF, and IR 20709 is
OFF, the PV in DM 0201 is moved to DM 0300.
Transfer Step Error
Processing Flag
20709
FAL (07) 01
If IR 00100 is ON and IR 20709 is ON, an error will have occurred in the sequence and a non-fatal error is generated.
Sequence executed nor mally:
Error in sequence execution:
Protocol Macro Executing Flag
(IR 20708)
1
0
Sequence executed
IR 00100
1
0
Sequence completed
Transfer Step Error
Processing Flag
(IR 20709)
1
0
Sequence executed
1 cycle
PV in DM 0201 moved to DM 0300
FAL executed
Transfer Step Error
Processing Flag
(IR 20709)
1
0
Processing When a Sequence Ends Abnormally
As shown in the following examples, if END is set when a sequence ends normally and ABORT is set when a sequence ends abnormally, it is possible to determine whether each sequence has ended normally or abnormally by using the Sequence End Completion Flag and the Sequence Abort Completion Flag.
92
Using Protocol Macros
Example 1
Sequence
Step No. 00
Example 2
Sequence
Step No. 00
Section 5-7
Error
Sequence ended abnormally
Error
Step No. 01
Sequence ended normally
Error
Sequence ended abnormally
Step No. 01 Step No. 02
Error
Sequence ended abnormally
Sequence ended normally
Sequence ended normally
When the Sequence Ends Normally
Protocol Macro
Executing Flag
Sequence End
Completion Flag
Sequence executed
Sequence completed
When the Sequence Ends Normally
Protocol Macro
Executing Flag
Sequence re-executed
Sequence End
Completion Flag
Sequence executed
Sequence completed
Sequence re-executed
Error processing for step No. 00
Step Error
Processing
Flag
Step Error
Processing
Flag
Step Error
Processing
Flag
When the Sequence Ends Abnormally
Protocol Macro
Executing Flag
Sequence Abort
Completion Flag
When the Sequence Ends Abnormally
Protocol Macro
Executing Flag
Sequence executed
Sequence completed
Sequence re-executed
Sequence Abort
Completion Flag
Sequence executed
Sequence completed
Error processing for step No. 00
Step Error
Processing
Flag
Sequence re-executed
Note The Step Error Processing Flag is used to see whether error processing has been executed for an individual step in a sequence, and not for the overall steps. Therefore, as shown in Ex ample 2 above, after executing error processing during a sequence (step No. 00), the flag will remain ON, even if the next step ends normally. Care is therefore required because it is not always possible to use this flag to determine whether the overall sequence has ended abnormally.
93
Using Protocol Macros
Section 5-7
Precautions on Using the Forced Abort Bit
The Protocol Macro Executing Flag will turn OFF as soon as the Forced Abort
Bit is turned ON from the ladder program. The Forced Abort Bit must remain
ON for at least 15 ms longer than the CPU Unit cycle time. Thus, the sequence will not be aborted if the Forced Abort Bit is turned OFF as soon as the Protocol Macro Executing Flag turns OFF.
If only the Protocol Macro Execution Flag is used in an NC condition for
PMCR(
), PMCR(
) will be executed during abort processing, and system error (FAL 9C) will occur. Wait at least 15 ms longer than the cycle time after turning ON the Forced Abort Bit before executing the next protocol macro.
In the following example, the Forced Abort Bit is turned ON and an interlock is created for the PMCR(
) instruction for 30 ms before the Forced Abort Bit is turned OFF.
Execution condition
Protocol Macro
Executing Flag
Forced Abort
Bit
PMCR
Abort condition
T000
A
A
A
T000
TIMH
000
#0003
20711
Forced Abort Bit
Abort condition
A
T000
Forced Abort
Bit (IR 20711)
Protocol Macro
Executing Flag
(IR 20708)
30 ms
1 cycle
94
Using Protocol Macros
Note
Section 5-7
1.
Observe the following precautions when using the Restart Flag.
• The Restart Flag is used to initialize the communications ports. When it is turned ON, either with a ladder program or with the monitor function of the
Support Tool, restart processing will begin after the protocol macro is executed. Once restart processing is completed, the Restart Flag will turn
OFF again. The protocol macro will not end if this flag is ON during its execution. To restart regardless of its executable/non-executable status, turn ON the Forced Abort Bit (20711/20715) also.
• To execute PMCR(
) following the restart processing, wait longer than the CPU Unit cycle time + 15 ms. This will allow the restart processing inside the communications board to be completed. If PMCR(
) is executed during the restart processing, a system error (FAL 9C) will occur, and the protocol macro may not be properly executed.
2.
If communications errors or retries occur with an RS-485 2-wire connection, use the following countermeasure.
This is possible with products of Lot No. 0320 or later.*
*Reading lot numbers
0 3 2 0
...Produced February 3, 2000
Production year:Last digit of the year
Production month: 1 to 9, X (10), Y (11), Z (12)
Production day: 01 to 31
When the serial communications mode for the port of the Serial Communications Board is set to Protocol Macro mode, and the send control parameter in the protocol macro is set to modem control, the following special auxiliary bit flags are enabled.
Bit address
20706
20707
20406
20407
Function
Port 1 Echoback Disable
Mode Flag
1: Echoback disabled, 0:
Echoback enabled
Port 2 Echoback Disable
Mode Flag
1: Echoback disabled, 0:
Echoback enabled
Port 1 Echoback Disable
Mode Monitor Flag
1: Echoback disabled, 0:
Echoback enabled
Port 2 Echoback Disable
Mode Monitor Flag
1: Echoback disabled, 0:
Echoback enabled
Description
Sets the Serial Communications Board.
Sets the Serial Communications Board.
Used to monitor the setting of the Serial Communications
Board.
Used to monitor the setting of the Serial Communications
Board.
With the
Echoback Disable Mode Flag (Port 1: 20706, Port 2: 20707) set to 1 (ON) and the RS-485 2-wire connection used, the data sent from the port of the Serial
Communications Board will be blocked by software from returning to the reception line of the same port as long as the RS signal is set to 1 (ON).
If communications errors or retries occur with the 2-wire connection, use a ladder program to form a circuit that sets the
Echoback Disable Mode Flag to
1 (ON).
Also, the data that is received during data transfer (while the RS signal is ON) with the Echoback Disable Mode is not input to the system, nor is it reflected in the CX-
Protocol trace data. Changes in the Echoback Disable Mode Flag (Port 1: 20706,
Port 2: 20707) from 0 (OFF) to 1 (ON) are always input to the system while the ladder program is running, but the 0 (OFF) state is only input to the Serial Communications Board at the start of the ladder program. Therefore, to cancel the Echoback
95
Using Protocol Macros
Ladder Diagram
Section 5-7
Disable Mode, it is not sufficient to simply set the Echoback Disable Mode Flags to
0 (OFF) while executing the protocol macro. Either switch once to the Program mode, and then start running again, or turn the power supply OFF and then ON.
The Echoback Disable Mode Monitor Flag (Port 1: 20406, Port 2: 20407) can be used to check the Echoback Disable Mode of each port.
Always ON
25313
Port 1 Echoback Disable Mode Flag
20706
Port 2 Echoback Disable Mode Flag
20707
Note The following describes the relationship between the RS-485 2-wire connection and the echoback.
Because the send line and receive line share a single, paired cable in the RS-
485 2-wire connection, the sent data returns to the cable’s own receive line
(see figure on following page). This is called “echoback” in this manual.
In the protocol macro function, in order to enable signals to be sent and received without the user having to specifically define this echoback data as an expected receive message, the system is designed to produce only a reception trace, via firmware, on the Serial Commmunications Board, while ignoring the data. However, in performance, it is sometimes difficult to distinguish between proper responses and echoback data responses due to variations in the echoback data delay, or variations in the processing time of the
Serial Communications Board firmware, and communication errors may result by mistaking echoback data for an expected receive message.
The reception of unnecessary echoback messages can thus be prevented by setting the Echoback Disable Mode Flag to 1 (ON).
■
2-wire connection using the RS-422A/485 port of the CQM1H-SCB41
Serial Commmunications Board
RS signal
RS-422A/485 port
SD signal
RS-485 2-wire connection
RD signal
External device
External device
Echoback
■
2-wire connection using NT-AL001 and the RS-232C port of the CQM1H-
SCB41
Serial Communications
Board
RS signal
RS-232C board
NT-AL001
RS-485 2-wire connection
SD signal
RD signal
External device
External device
Echoback
96
Using Protocol Macros
Section 5-7
■
Waveform image for send/receive signals in 2-wire connection
When the Echoback Disable Mode Flag is ON, signal reception will be disabled while the modem control RS signal is ON.
RS signal (PC side)
Send data
SD signal (PC side)
RD signal (PC side)
Echoback data receive data
When the Echoback Disable Mode
Flag is ON, this data is ignored.
Proper response receive data
Note The condition of the 20700 to 20707, 20711, and 20715 flags is also maintained during interruptions in the power supply.
When 20711 or 20715 (Forced Abort Bit for Port 1 or Port 2) is set to 1 (ON), signals will not be sent or received.
Use a Programming Device to clear the flag, or use a ladder program to form a circuit that sets these bits
to 0 (OFF).
ON during scan 1 at program start
25315
MOV
#0000
207
97
SECTION 6
No-protocol Communications
This section provides information required to use no-protocol communications on a Serial Communications Board port.
6-4 Using No-protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-1 TRANSMIT – TXD(
) and RECEIVE – RXD(
). . . . . . . . . . . .
6-4-2 TXD(
) Communications Procedure . . . . . . . . . . . . . . . . . . . . . . .
6-4-3 RXD(
) Communications Procedure . . . . . . . . . . . . . . . . . . . . . . .
6-4-4 Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
104
106
106
99
Overview
Section 6-1
6-1 Overview
No-protocol
Specifications
Data can be sent or received without a protocol and without conversion by connecting an external device to the RS-232C port and executing the TXD(
) or RXD(
) instruction from the ladder program. Start and end codes can be attached to the data or the amount of data to be received can be specified.
The communications frame cannot be specified for no-protocol communications in the way it can be for protocol macros. Retry processing, data conversion, and procedural branching according to received data are also not possible. No-protocol communications are thus good for communicating with bar code readers and other external devices with RS-232C ports that do not required command-response procedures. Data is sent in one direction only, using TXD(
) to send data from the port or RXD(
) to read data received on the port.
Note When TXD(
) is executed in No-protocol Mode, data from I/O memory is sent from the port without conversion. When TXD(
) is executed in Host Link mode (for slave-initiated communications), the contents of the specified words in I/O memory is converted to ASCII before being sent.
The specifications of no-protocol communications are given in the following table.
Item
Messages (communications frame)
One of the following.
Specification
Data only
Start code + data
Data + end code
Start code + data + end code
Data + CR + LF
Start code + data + CR + LF
Settings are made in the PC Setup: Start code enable, end code enable, start code, end code, number of receive bytes (when end code is disabled)
Start code
End code
Disabled or 00 to FF Hex
Disabled, 00 to FF Hex, or
CR+LF
Message transmissions
Message receptions
Number of receive bytes
TXD(
) in ladder program
RXD(
) in ladder program
1 to 256 bytes if transmission ends in data (data only or start code + data)
Maximum message length 256 bytes including start code and end codes (253 bytes without start/end codes) for either sending or receiving
Data conversion
Communications protocol
Transmission delay
Reception counter
None
None
0 to 99,990 ms (set in PC Setup in units of 10 ms)
The transmission delay is from the beginning of
TXD(
) execution until execution of the next TXD(
) can be started.
The number of bytes received at the port can be counted from 0 to 256 bytes.
100
Overview
Send/Receive Message Frames
Start code
No
No
Data
Yes
End code
Yes
Data
ED
256 bytes max.
Section 6-1
CR+LF
Data
CR+LF
256 bytes max.
256 bytes max.
ST
Data
ST
Data
ED
ST
Data
CR+LF
256 bytes max.
256 bytes max.
256 bytes max.
• Only the first start code is valid if there is more than one start code.
• Only the first end code is valid if there is more than one end code.
• Use CF+LF if using an end code may cause receptions to be interrupted because the end code exists in the receive data.
• A transmission delay can be set for PC-initiated communications as a minimum interval between sending commands to the host.
The delay is not used in sending the first command. The delay will affect other commands only if the time set for the transmission delay has not expired when the next command is ready to be sent.
If the delay time has already expired when the next command is ready, the command will be spent immediately. If the delay time has not expired, the command will be delayed until the time set for the transmission delay has expired.
The operation of the transmission delay for PC-initiated communications is illustrated below.
Transmission delay Transmission delay Transmission delay
Command sent Command sent Command sent Command sent
1st TXD(
) command
2nd TXD(
) command
3rd TXD(
) command
4th TXD(
) command
Time
Refer to the CQM1H Programming Manual for details on TXD(
) and
RXD(
).
101
Application Procedure
Section 6-2
6-2 Application Procedure
1,2,3...
1.
Turn OFF the power supply to the PC.
2.
Mount the Board.
3.
Connections
Connect the external devices using RS-232C or RS-422 cables. The
TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port.
The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required.
4.
Turn ON power.
5.
Set the PC Setup settings for the Serial Communications Board.
Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6500 and DM 6559.
Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed.
The following table shows the settings for using STX as the start code,
CR+LF as the end code, and no transmission delay.
Port 1
DM 6555
Port 2
DM 6550
Bit(s)
00 to 03
04 to 11
12 to 15
Setting
0 Hex
---
1 Hex
Function
Standard port settings
(1 start bit, 7-bit data, even parity,
2 stop bits, 9,600 bps)
Not used.
Serial communications mode
No-protocol
DM 6556 DM 6551 00 to 07 00 Hex Baud rate setting disabled.
08 to 15 00 Hex Frame format setting disabled.
DM 6557 DM 6552 00 to 15 0000
(BCD)
DM 6558 DM 6553 00 to 07 ---
Transmission delay: 0 ms
0000 to 9999 (BCD): Set in units of
10 ms
Not used.
08 to 11
12 to 15
1 Hex
2 Hex
Start code enabled
End code enabled as CR+LF
0: Disable (number of receive bytes set)
1: Set (specified end code)
2: CR, LF
DM 6559 DM 6554 00 to 07 02 Hex Start code: STX
08 to 15 00 Hex Number of receive bytes (Disabled when end code is set.)
6.
Write and execute the ladder program. Use TXD(
) to send data to an external device and RXD(
) to receive data from an external device.
102
Connections
Section 6-3
6-3 Connections
Connecting to a Bar Code
Reader via RS-232C
The connection examples in this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to
2-3 Wiring for actual wiring methods.
The following diagram shows the connections between an OMRON V500series Bar Code Reader and the RS-232C port on the Serial Communications
Board.
Serial Communications Board
(D-sub, 9-pin female connector)
Signal Pin
V509-W012 Cable
V520-RH21-6
Bar Code Reader
Pin Signal
Serial Communications Board
V509-W012
Cable
V520-RH21-6
Bar Code Reader
100 VAC
5-V external power supply
(e.g., 82S-0305)
Note If the external device has a FG terminal, connect the shield wire to ground at both the external device and the Serial Communications Board to prevent faulty operation.
103
Using No-protocol Communications
Section 6-4
6-4 Using No-protocol Communications
6-4-1 TRANSMIT – TXD(
) and RECEIVE – RXD(
)
This section describes using TXD(
) and RXD(
) for no-protocol communications.
TRANSMIT – TXD(
) in No-protocol Mode
TXD(
)
S
First source word
C
N
Control word
Number of bytes
(4 digits BCD, 0000 to 0256)
Control Word: C
15 00
0 0
Byte order 0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 0.)
Port 0: RS-232C port on CPU Unit
1: Port 1 on Serial Communications Board
2: Port 2 on Serial Communications Board
Not used. (Set to 0.)
The specified number of bytes will be read starting from S and transmitted through the specified port.
• Up to 256 bytes of data can be sent each time the instruction is executed.
• The bytes of source data shown below will be sent in the following order.
If most significant bytes first is specified (0): 12345678..
If least significant bytes first is specified (1): 21436587..
MSB LSB
S 1 2
S+1 3 4
S+2 5 6
S+3 7 8
Communications parameters are set in the PC Setup settings for the Serial
Communications Board. Refer to information in the CQM1H Programming
Manual on serial communications and TXD(
) for details.
104
Using No-protocol Communications
RECEIVE – RXD(
) in Noprotocol Mode
RXD(
)
D
C
N
First destination word
Control word
Number of bytes
(4 digits BCD, 0000 to 0256)
Section 6-4
Control Word: C
15 00
0 0
Byte order 0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 0.)
Port 0: RS-232C port on CPU Unit
1: Port 1 on Serial Communications Board
2: Port 2 on Serial Communications Board
Not used. (Set to 0.)
The specified number of bytes are read from the specified port as specified in the control word and stored starting at D.
• Up to 256 bytes of data can be read each time the instruction is executed.
• The bytes of received data will be received in the following order.
Digit 0 = 0
MSB LSB
D 1 2
D+1 3 4
D+2 5 6
D+3 7 8
Digit 0 = 1
MSB LSB
D 2 1
D+1 4 3
D+2 6 5
D+3 8 7
• If the value of N is larger than the number of receive bytes, only the number of bytes actually received will be read into memory.
• Communications parameters for the Serial Communications Board are set in the PC Setup. Refer to the CQM1H Programming Manual for details.
105
Using No-protocol Communications
Section 6-4
6-4-2 TXD(
) Communications Procedure
Confirm that the Transmission Enabled Flag is ON before executing TXD(
).
The Port 1 Transmission Enabled Flag is IR 20105 and the Port 2 Transmission Enabled Flag is IR 20113. The Transmission Enabled Flag will turn OFF while TXD(
) is being executed and will turn ON when the send has been completed.
TXD(
)
C: Control Word
15 00
0 0
S
First source word
C
Control word
Byte order 0: Most significant bytes first
1: Least significant bytes first
N
Number of bytes
(4 digits BCD, 0000 to 0256)
Not used. (Set to 0.)
Port 0: RS-232C port on CPU Unit
1: Port 1 on Serial Communications Board
2: Port 2 on Serial Communications Board
Not used. (Set to 0.)
Note Do not let TXD(
) be executed unless the Transmission Enabled Flag is ON.
6-4-3 RXD(
) Communications Procedure
The Reception Completed Flag will turn ON when data reception has been completed. The Port 1 Reception Completed Flag is IR 20106 and the Port 2
Reception Completed Flag is IR 20114.
When RXD(
) is executed, the receive data is stored in the specified data without any start or end code and the Reception Completed Flag is turned
OFF.
Reception is started when the start code is received. If the start code is disabled, then data is received continually.
Reception is completed when the end code is received. If the end code is disabled, then reception is completed when the specified number of bytes or
259 bytes have been received.
RXD(
)
D
First destination word
C: Control Word
15 00
0 0
C
N
Control word
Number of bytes
(4 digits BCD, 0000 to 0256)
Byte order 0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 0.)
Port 0: RS-232C port on CPU Unit
1: Port 1 on Serial Communications Board
2: Port 2 on Serial Communications Board
Not used. (Set to 0.)
The following flags and status information are available in the IR area. All bits are cleared when RXD(
) is executed.
106
Using No-protocol Communications
Section 6-4
Port 1 Port 2 Function
IR 20100 to IR 20103 IR 20108 to IR 20111 Error Code
0: Normal operation
1: Parity error
2: Framing error
3: Overrun error
IR 20104
IR 20107
IR 20112
IR 20115
Communications Error Flag
Reception Overflow Flag (Turns ON when data is received again before the previous data is read with RXD(
).)
IR 20200 to IR 20215 IR 20300 to IR 20315 Reception counter
Provides the number of bytes of data received in 4-digit BCD (0 to 256).
The Port 1 Restart Bit (IR 20700) and Port 2 Restart Bit (IR 20701) can be turned ON to initialize the serial communications ports. These bits will be turned OFF automatically after the ports have been initialized.
6-4-4 Application Example
This example shows how to send data from DM 0100 to DM 0104 (each word contains 3454) to a computer and then store data received from the computer starting at DM 0200.
Conditions
PC Settings
The following settings are made in the PC Setup before executing the program.
Communications mode: No-protocol
Port settings: Standard
Start code:
End code:
Other:
None
CR + LF
Default settings
Computer Settings
Set the same communications parameters as the PC and prepare the programs to send and receive data.
Ladder Programming
00100
DIFU (13) 00101
00101
Transmission
Enabled Flag
TXD
Reception
Competed Flag
20106
DM0100
#0100
#0010
RXD
DM0200
#0100
#0256
1,2,3...
1.
When IR 00100 turns ON, the contents of DM 0100 to DM 0104 will be sent with most significant bytes first from port 1 on the Serial Communications
Board if IR 20105 is ON (Transmission Enabled Flag).
The following data will be received at the computer:
34543454345434543454CRLF
2.
When IR 20106 (Reception Competed Flag) turns ON, 256 bytes of data received on port 1 on the Serial Communications Board will be read and stored starting at DM 0200 with most significant bytes first.
107
SECTION 7
Communications for 1:1 Data Links
This section provides information required to create 1:1 Data Links through a Serial Communications Board port.
7-1-1 Starting Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
109
Overview
7-1 Overview
Section 7-1
If two PCs are linked one-to-one by connecting them together through RS-
232C or 4-wire RS-422A/485 cable, they can share up to 64 words of their LR areas. The 1:1 Data Links are the same as normal Data Links in that data is not shared bidirectionally, i.e., the link words written by one PC are transferred to the other PC.
One of the following three ranges of words can be set to be linked:
LR 00 to LR 63, LR 00 to LR 31, or LR 00 to LR 15
A 1:1 Data Link communications system can be created between the CQM1H and another CQM1H, or between the CQM1H and the CQM1, C200HX/HG/
HE, C200HS, CPM1, CPM1A, CPM2A, CPM2C, or SRM1(-V2).
One of the PCs is set as a 1:1 Data Link master and the other as a 1:1 Data
Link slave. The linked words are separated into two groups of words, and the words written by each PC is transferred to the other PC, as illustrated in the following diagram.
For example, if LR 00 to LR 63 are linked, the status of LR 00 to LR 31 written by the master CQM1H will be transferred to LR 00 to LR 31 of the slave
CQM1H, and the status of LR 32 to LR 63 written by the slave CQM1H will be transferred to LR 32 to LR 63 of the master CQM1H.
CQM1H or other C-series PC
Link
CQM1H or other C-series PC
RS-232C
Serial Communications Board
CQM1H or other C-series PC
CQM1H or other C-series PC
LR 00 to
Master area
(sent)
LR 00 to Master area
(received)
LR 31
LR 32 to
LR 63
Slave area
(received)
LR 31
LR 32 to
LR 63
Slave area
(sent)
The words in the LR area that will be linked are set in the PC Setup as shown in the following table.
PC Setup Setting
Port 1 Port 2 Bits Function Setting Master words Slave words
DM 6555 DM 6550 04 to 07 Link words for 1:1 link 0 Hex: LR 00 to LR 63 LR 00 to LR 31 LR 32 to LR 63
1 Hex: LR 00 to LR 31 LR 00 to LR 15 LR 16 to LR 31
2 Hex: LR 00 to LR 15 LR 00 to LR 07 LR 08 to LR 15
7-1-1 Starting Data Links
Connect two PCs one-to-one through RS-232C or 4-wire RS-422A/485 cable, make the proper settings in the PC Setup, and turn ON the power supplies.
The 1:1 Data Link will start automatically.
110
Application Procedure
Section 7-2
7-1-2 Specifications
Item
Connection method
Applicable PCs
Number of nodes linked
Number of words linked
Linked words
Link word setting
Order of allocation
Startup method
Status flags
Specification
Connection of 2 PCs through their RS-232C ports (prepared cable).
Note
RS-422A/485 ports can also be connected if a 4wire connection method is used.
CQM1H, CQM1, CPM1, CPM1A, CPM2A, CPM2C, or
SRM1(-V2), C200HX/HG/HE, C200HS
There are restrictions in the number of words that can be linked for some PCs.
2
64 words, LR 00 to LR 63 32 words sent per node
32 words, LR 00 to LR 31 16 words sent per node
16 words, LR 00 to LR 15 8 words sent per node
One of three groups listed above
PC Setup in master PC
Words allocated to master PC first and then to slave PC.
Automatic startup after turning ON power to master and slave PCs.
None
7-2 Application Procedure
1,2,3...
1.
Turn OFF the power supply to the PC.
2.
Mount the Board.
3.
Connections
Connect the external devices using RS-232C or RS-422 cables. The
TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port.
The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required.
4.
Turn ON power.
5.
Set the PC Setup settings for the Serial Communications Board.
Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559.
Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed.
111
Connections
Section 7-3
The following table shows the master PC settings for a 1:1 Data Link for LR 00 to LR 63.
Port 1 Port 2 Bits
DM 6555 DM 6550 00 to 07
08 to 11
12 to 15
DM 6556 DM 6551 00 to 15
DM 6557 DM 6552 00 to 15
DM 6558 DM 6553 00 to 15
DM 6559 DM 6554 00 to 15
---
---
---
---
---
Setting
0 Hex
3 Hex
Function
Not used.
Link words for 1:1 Data Link
0: LR 00 to LR 63 (default)
1: LR 00 to LR 31
2: LR 00 to LR 15
Communications mode
2: 1:1 Data Link slave
3: 1:1 Data Link master
Not used.
Not used.
Not used.
Not used.
6.
Write and executed the ladder program.
The Always ON Flag (SR 25313) can be use to program instructions such as MOV(21) to write data to be sent to the other PC to the sending words in the LR area and to read data received from the other PC in the receiving words in the LR area.
7-3 Connections
The connection examples in this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to
2-3 Wiring for actual wiring methods.
CQM1H
Signal Pin
Connector edge
CQM1H
Pin
Connector edge
Signal
D-sub, 9-pin male connector on cable
D-sub, 9-pin male connector on cable
112
Using 1:1 Data Links
Section 7-4
7-4 Using 1:1 Data Links
This section provides an example of using 1:1 Data Links.
Conditions
The following settings are made in the PC Setup before executing the program.
Master PC Settings
Communications mode: 1:1 Data Link master
Link words: LR 00 to LR 15
Slave PC Settings
Communications mode: 1:1 Data Link slave
Ladder Programming
Master PC Slave PC
Always ON Flag Always ON Flag
MOV (21)
001
LR00
MOV (21)
001
LR08
MOV (21)
LR08
100
MOV (21)
LR00
100
When the programs in the two PCs are executed, the status of input word
IR 001 of both PCs will be transferred to the other PC and will be output to output word IR 100.
113
SECTION 8
NT Link Communications
This section describes the procedure and other information required to use 1:N-mode and 1:1-mode NT Links to
Programmable Terminals (PTs).
8-1-1 NT Links — 1:N Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1-2 NT Links — 1:1 Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115
Overview of NT Links
Section 8-1
8-1 Overview of NT Links
This section explains the application of a Serial Communications Board for an
NT Link in either 1:N or 1:1 mode. For details on the operation of the PT, refer to the operation manual for the PT.
Note In an NT Link using 1:N mode, a PC can be connected to either one or more than one PTs. There is no difference in functionality determined by the number of PTs connected. The 1:1 mode, however, uses a different communications protocol from the 1:N mode and these two modes are not compatible.
8-1-1 NT Links — 1:N Mode
A PC can be connected to one or more Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PC is allocated as a Status Control Area and a Status Notification Area for the PT, as well as to objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PC to be controlled and monitored by operations from the PT, without the use of ladder programming in the PC. One PC can be connected to up to eight PTs.
The user does not need to be aware of the 1:N NT Links commands. All that is necessary is to allocate PC memory for the PTs.
Serial Communications Board
Serial Communications Board
1:N connections
1:1 connection
PT
PT PT
8-1-2 NT Links — 1:1 Mode
Although the functionality of an NT Link in 1:1 mode is the same as an NT
Links in 1:N mode, only one PT can be connected to the PC. The 1:1 mode is not compatible with the 1:N mode as a communications protocol.
Serial Communications Board
1:1 connection
PT
8-1-3 Precautions
1,2,3...
1.
Set the serial port on the PT to a 1:N NT Link whenever the Serial Communications Board is set to a 1:N NT Link, and set the serial port on the
PT to a 1:1 NT Link whenever the Serial Communications Board is set to a 1:1 NT Link. The Serial Communications Board will not be able to communicate if the PT port is set to a different mode.
2.
The NT20S, NT600S, NT30/30C, and NT620S/620C/625C cannot be used if the cycle time of the PC is 800 ms or longer. This is true in both 1:1 and 1:N mode (even when a 1:1 connection is used in 1:N mode).
116
Overview of NT Links
Section 8-1
3.
The Programming Console functions of the PT (Expansion Mode) cannot be used when connected to Serial Communications Board ports. They can be used only by connecting to the peripheral port or RS-232C port on the
CPU Unit. This is true in both 1:1 and 1:N mode.
4.
When using 1:N-mode NT Links, set a unique unit number for each PT connected to the same PC. If the same unit number is set for more than one PT, malfunctions will occur.
5.
The number of PTs that can be connected to one port in 1:N mode is limited by the CPU Unit’s cycle time when a Serial Communications Board is used, as shown in the following diagrams. Although some communications will be possible even if these restrictions are exceeded, communications errors will occur depending on the PT operating conditions and communications load. Always abide by these restrictions when using 1:N mode.
Example for NT31/NT631(C) PTs
Priority
Registered
PTs per port
CPU Unit's cycle time (ms)
Priority Not
Registered
PTs per port
CPU Unit's cycle time (ms)
117
Application Procedure
Section 8-2
6.
With some PTs, timeout settings can be changed to eliminate some of the communications errors. Refer to the operation manual for the PT for details. This is true in both 1:1 and 1:N mode.
7.
If more PTs are required by the system than allowed by the above restrictions in 1:N mode, connect the PTs in smaller groups to different ports.
8-2 Application Procedure
1,2,3...
1.
Turn OFF the power supply to the PC.
2.
Mount the Board.
3.
Connections
Connect the external devices using RS-232C or RS-422 cables. The
TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port.
The CPU Unit can be connected to a Programming Console, the CX-Programmer, or the CX-Protocol as required.
4.
Turn ON power.
5.
Set the PC Setup settings for the Serial Communications Board.
Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559.
Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the settings. They will be updated automatically as soon as they are changed.
NT Link Settings for 1:N Mode
The following table shows the settings for connecting more than one PT when the highest PT unit number is 5.
Port 1
DM 6555
Port 2
DM 6550
Bit(s)
00 to 07
Setting
--Not used.
Function
08 to 11 5 (BCD) Maximum Programmable Terminal unit number
1 to 7 (BCD)
NT Link in 1:N mode
12 to 15 5 Hex Communications mode
NT Link in 1:N mode
DM 6556 DM 6551 00 to 15 ---
DM 6557 DM 6552 00 to 15
DM 6558 DM 6553 00 to 15
DM 6559 DM 6554 00 to 15
Not used.
Port Settings are always the same for 1:N-mode NT Links. Settings of the start bits, stop bits, parity, and baud rate are not necessary and will be ignored.
Set the communications mode to a 1:N-mode NT Link (5 Hex).
Up to 8 PTs can be connected in 1:N mode. Set the highest unit number of the PTs to be connected as the maximum Programmable Terminal unit number.
NT Link Settings for 1:1 Mode
The following table shows the settings for a 1:1-mode NT Link.
Port 1 Port 2 Bit(s) Setting
DM 6555 DM 6550 00 to 11 ---
12 to 15 4 Hex
Function
Not used.
Communications mode
NT Link in 1:1 mode
118
Connections
Section 8-3
Port 1 Port 2 Bit(s) Setting
DM 6556 DM 6551 00 to 15 ---
DM 6557 DM 6552 00 to 15
DM 6558 DM 6553 00 to 15
DM 6559 DM 6554 00 to 15
Not used.
Function
Port Settings are always the same for 1:1-mode NT Links. Settings of the start bits, stop bits, parity, and baud rate are not necessary and will be ignored.
Set the communications mode to a 1:1-mode NT Link (4 Hex).
6.
Operate the system.
Refer to the operation manual for your PT for operating instructions.
8-3 Connections
The connection examples in this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to
2-3 Wiring for actual wiring methods.
Direct 1:1 Connection from RS-232C to RS-232C Ports (1:1 or 1:N Mode)
Serial Communications
Board
Signal
FG
FG
SD
RD
RS-232C
Interface
RTS
CTS
5V
DSR
DTR
SG
Pin
Hood
D-sub, 9-pin connector (male)
PT
Pin
Signal
Hood
FG
--
SD
RD
RTS
CTS
5V
--
--
RS-232C
Interface
SG
D-sub, 9-pin connector (male)
• Communications Mode: 1:1 or 1:N-mode NT Link
• OMRON Cables with Connectors:
XW2Z-200T-1: 2 m
XW2Z-500T-1: 5 m
Direct 1:1 Connection from RS-422A/485 to RS-422A/485 Ports (1:1 or 1:N Mode)
Serial Communications
Board
Short piece
Signal
Signal Pin
RS-422A/
485 Interface
RS-422A/
485 Interface
Hood
D-sub, 9-pin connector (male)
Functional ground
Terminal block or
D-sub connector
• Communications Mode:1:1 or 1:N-mode NT Link
Note Serial Communications Board settings: Terminating resistance ON, 4-wire.
119
Connections
1:N, 4-wire Connections from RS422A/485 to RS422A/485 Ports (1:N Mode)
Serial Communications
Board
Signal
Pin
RS-422A
/485 Interface
Hood
D-sub, 9-pin connector (male)
Signal
PT
RS-422A
/485 In- terface
FG
Terminal block or
D-sub connector
Short bar
Signal
PT
Section 8-3
RS-422A
/485 Interface
FG
Terminal block or
D-sub connector
Communications Mode: 1:N NT Link
Note Serial Communications Board settings: Terminating resistance ON, 4-wire.
1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports (1:N Mode)
Serial Communications
Board
Signal
Pin
RS-422A/
485 Interface
Signal
PT
RS-422A
/485 Interface
Hood
D-sub, 9-pin connector (male) FG
Terminal block
Short bar
Signal
PT
RS-422A
/485 Interface
FG
Terminal block
Communications Mode: 1:N NT Link
Note Serial Communications Board settings: Terminating resistance ON, 2-wire.
120
SECTION 9
Troubleshooting and Maintenance
This section describes the troubleshooting and maintenance procedures for the Serial Communications Boards.
9-2-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2-3 1:N NT Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-4-2 Settings after Replacing the Board. . . . . . . . . . . . . . . . . . . . . . . . . .
9-4-3 Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
121
Front-panel Indicator Error Displays
Section 9-1
9-1 Front-panel Indicator Error Displays
Possible cause
Lit
Indicators
Board CPU Unit
RDY ERR/ALM
Not lit
Not lit
Not lit
Lit
Lit
Flashing
Lit
Not lit
Lit
Flashing
Flashing
Remedy
The Serial Communications Board has started normally.
The Serial Communications Board is faulty
(hardware self-diagnostic function).
Board watchdog timer error: IR 20000 will turn ON.
A bus error has occurred.
An initialization recognition error has occurred (the Serial Communications Board is not correctly recognized by the CPU
Unit).
The CPU Unit is not receiving normal power supply.
---
If the ERR and ALM indicators light when the Serial Communications Board is mounted to another CPU Unit, replace the
Serial Communications Board.
Firmly secure the Serial Communications
Board to the CPU Unit.
Check the power supply voltage and supply the correct electric power to the Unit.
Firmly secure the Serial Communications
Board.
The Serial Communications Board is not correctly secured to the CPU Unit.
The Serial Communications Board is faulty.
An error (such as a CPU Unit WDT error) has occurred in the CPU Unit.
The Serial Communications Board is faulty.
A bus error has occurred.
If all the indicators are not lit when the
Serial Communications Board is mounted to another CPU Unit, replace the Serial
Communications Board.
Eliminate the cause of the error. If the error persists, replace the CPU Unit.
If all the indicators are lit when the Serial
Communications Board is mounted in another CPU Unit, replace the Serial Communications Board.
Check the operating environment and eliminate the cause of the error.
Firmly secure the Serial Communications
Board.
Eliminate the cause of the error. If the error persists, replace the CPU Unit.
An error has occurred in the CPU Unit.
(Cause of error eliminated, but error not cleared.)
A protocol data write error has occurred or protocol data has been destroyed.
(Protocol data error: IR 20002)
Connector may have become loose or the
PC power supply may have turned OFF while transferring protocol data.
There is no protocol data.
The communications circuit is faulty.
(Board Identification Error Flag: IR 20001)
A protocol data syntax error has occurred.
(Protocol macro error code: 4)
If the indicator status remains the same when the protocol data is retransmitted, replace the Serial Communications Board.
Transfer protocol data to the Serial Communications Board.
Conduct a loopback test. If an error occurs, replace the Serial Communications Board.
Correct the protocol data and transfer it to the Serial Communications Board.
Try executing a normal sequence for the serial port where the error is occurring or switch the CPU Unit to PROGRAM mode and remove the cause of the error.
Correct the PC Setup settings.
A PC Setup error has occurred.
(PC Setup Error Flags: IR 20013 to
IR 20015)
122
Front-panel Indicator Error Displays
Section 9-1
Serial Communications
Board Error Information
For Serial Communications Boards, refer to the following error flags. When an error occurs, the corresponding flag is turned ON. All of these flags represent non-fatal errors.
Word
IR 200 00
Bit
02: Hardware error
10: Serial Communications
Board error
Name
Serial Communications Board
Hardware Error Flag
Probable cause
The Board has failed.
01
02
12/11
15
Port Identification Error Flag
(hardware error)
Protocol Data Error Flag
Protocol Macro Execution
Error Flag (Port 1/2)
PC Setup Error Flag
There is a problem with the communications port.
A checksum error was found in the protocol data.
An error occurred when the PMCR instruction was executed.
Replace the Board.
Retransfer the protocol data. If the problem persists, replace the Board.
Take countermeasures according to the error codes stored in bits 08 to 11 (port 1) or bits 12 to 15 (port 2) in word
204.
There is an error in the settings in the PC Setup.
Check the settings for the
Board in the PC Setup and restart the Board.
Error in settings for port12.
Error in settings for port 2.
14
13
Port 1 PC Setup Error Flag
Port 2 PC Setup Error Flag
SR 254
AR 04
15 Slot 1 Inner Board Error Flag Turns ON when an error occurs in the slot 1 Inner Board. The error code for slot 1 is stored in
AR 0400 to AR 0407.
00 to 07 Slot 1 Inner Board Error Code
See remedies for AR 04.
01: Hardware error The Board has failed (watchdog timer error). IR 20000 will also be
ON.
The Board has failed.
Refer to the errors in IR 200.
Possible remedy
Secure the Board firmly in the slot or try it in a different CPU
Unit. If the problem persists, replace the Board.
Secure the Board firmly in the slot or try it in a different CPU
Unit. If the problem persists, replace the Board.
See remedies for IR 20000,
IR 20001, IR 20002, IR 20011,
IR20012, and IR 20015.
When a fatal error occurs, the ERR/ALM indicator on the CPU Unit will light.
When a non-fatal error occurs, the ERR/ALM indicator on the CPU Unit will flash. Refer to the indicator error displays.
Note The ERR/ALM indicator will continue to flash even after the cause of a nonfatal error has been removed for the Serial Communications Board. The indicator can be stopped by clearing the error from a Programming Console or other Programming Device. Press the FUN Key and then the MONITOR Key from the Programming Console. Refer to the CX-Programmer Operation Man-
ual for the CX-Programmer procedure.
123
Troubleshooting
Section 9-2
9-2 Troubleshooting
This section describes how to resolve transmission and reception problems.
9-2-1 Host Link Communications
Serial communications mode
Serial communications mode is not set to
Host Link.
Serial communications mode is set to Host
Link.
---
Indicator status
The COMM @ indicators do not flash at all.
(Communications have not been electrically established.)
The COMM @ indicators are flashing, but the response has not been returned to the host. (Communications have been electrically established.)
Status information, etc.
---
I/O memory
Bits 12 to 15 (Serial
Communications
Mode) of DM 6555/
DM 6550 are set to a value other than 0
Hex.
-----
Cause
Serial communications mode is not set correctly.
Remedy
Set bits 12 to 15 of
DM 6555/DM 6550 to
0 Hex. (Host Link).
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect (WIRE).
Adapters such as the NT-AL001-E are incorrectly wired or set.
Commands are not being set from the host.
Check the wiring.
Reset the port to the correct wiring setting.
Wire all nodes using the 4wire method.
Reset the serial communications port at the host, and rewrite the program.
There is no transmission error.
IR 20100 to
IR 20103 or
IR 20108 to
IR 20177 are 0 Hex.
---
---
There is a hardware error.
The PC Setup settings for the Host
Link unit No., Host
Link transmission delay, or other settings do not match the settings for the remote device.
The command format and data length of the data sent from the host are incorrect.
Replace the Serial Communications Board.
Reset the settings in the
PC Setup for the Host Link unit No., Host Link transmission delay and other settings so that they match the settings at the host device.
Correct the command frame (header, Host Link
Unit No., terminator, etc.) and the program.
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect (WIRE).
Adapters such as the NT-AL001-E are incorrectly wired or set.
This is a transmission circuit hardware error.
The send delay time setting is too long.
Check the wiring and switch settings, and correct if necessary.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board.
Reset the parameters in the PC Setup correctly.
124
Troubleshooting
Section 9-2
Serial communications mode
Serial communications mode is set to Host
Link. (Continued)
Indicator status
The COMM @ indicators are flashing, but the response has not been returned to the host.
The COMM @ indicators are flashing, and an error response has returned to the host.
The COMM sometimes there is no response returned.
@ flashing, but indicators are
Status information, etc.
There is a transmission error.
There is no transmission error.
There is a transmission error.
There is an intermittent transmission error.
I/O memory
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is 1 (parity error), 2
(framing error), or 3
(overrun error).
Cause
The communications conditions and baud rate do not match the settings at the host.
There is noise interference.
IR 20100 to
IR 20103 or
IR 20108 to
IR 20111 are 0 Hex.
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is 1 (parity error), 2
(framing error), or 3
(overrun error).
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is 1 (parity error), 2
(framing error), or 3
(overrun error).
Terminating resistance switch
(TERM) status
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is not 0.
A command was sent from the host with incorrect parameters.
The communications conditions and baud rate do not match the settings at the host.
The baud rate is outside the allowable range, and the stop bits do not match, causing the bits to be out of alignment.
Cables are incorrectly connected.
The RS-422A/485 port 2-wire/4-wire terminating resistance setting is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or the terminating resistance is incorrectly set.
Transmission errors are occurring that are caused by noise interference.
Remedy
Review the PC Setup, the host’s settings, and program (such as commands and frame format) based on the response and the error code.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Review the installation environment to reduce noise interference.
Review the host’s settings and program (such as parameter settings) based on the response contents.
Review the PC Setup, the host’s settings and program (such as commands and frame format) based on the response, and the error code in IR 20100 to
IR 20103 or IR 20108 to
IR 20111.
Review the PC Setup.
Review the host’s settings and program (such as baud rate and frame format).
Check the wiring.
Turn ON the terminating resistance of the Serial
Communications Board and the last node by using the terminating resistance switch. Turn OFF the terminating resistance of other nodes.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Review the installation environment to reduce noise interference.
125
Troubleshooting
Section 9-2
Serial communications mode
Host Link, slave-initiated communications
Indicator status
The COMM @ indicators are flashing, but there is no response from the host.
Status information, etc.
A transmission error has not been detected at the host.
---
I/O memory Cause Remedy
---
---
---
Communications parameters and baud rate settings in the PC Setup do not correspond with the settings at the host.
There is a hardware error in the reception circuit.
Cables are incorrectly wired.
There is a hardware error in the reception circuit.
Adapters such as the NT-AL001-E are incorrectly wired or set.
---
The communications conditions and baud rate do not match the settings at the host.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board.
Check the wiring and correct.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board.
Check the program at the host. When unsolicited communications are used with Host Link mode, there must be a response returned from the host for every command sent from the Serial Communications Board.
Reset the parameters in the PC Setup and at the host correctly.
126
Troubleshooting
Section 9-2
9-2-2 Protocol Macros
Serial communications mode
Serial communications mode is not set to protocol macro.
Serial communications mode is set to protocol macro.
---
Indicator display
---
Status information, etc.
The
COMM @ indicators do not flash at all.
(Communications has not been electrically established.)
The PMCR(
) instruction was executed, but
IR 20708 or
IR 20712 (Protocol Macro
Executing Flag) did not turn ON.
I/O memory Cause Remedy
Bits 12 to 15 (Serial
Communications
Mode) of DM 6555/
DM 6550 are set to a value other than
6 Hex.
IR 20708 or
IR 20712 (Protocol
Macro Executing
Flag) is set as a NO execution condition for PMCR(
).
The Error Flag
(SR 25503) is ON.
Serial communications mode is not set correctly.
Set bits 12 to 15 of
DM 6555/DM 6550 to
6 Hex. (protocol macros).
The program is incorrect. Set IR 20708 or IR 20712
(Protocol Macro Executing Flag) as a NC execution condition for
PMCR(
).
Check the PMCR(
operand settings for errors.
) instruction C, S, and D
The error code in
IR 20408 to
IR 20411 or
IR 20412 to
IR 20415 is 2 Hex
(Sequence Number
Error).
The error code in
IR 20408 to
IR 20411 or
IR 20412 to
IR 20415 is 3 Hex
(Receive Data Write
Range Overflow
Error)
The problem cause is one of the following:
– The data range for the
PMCR(
) instruction C operand is incorrect.
– The number of data words in the S or D operand exceeds 129.
The sequence number specified in bits 00 to 11 of the PMCR(
) instruction C operand is a value other than 000 Hex to
999 BCD.
The specified communications sequence number does not exist in the protocol data.
The data range of the specified area is exceeded when data is being written to or read from the I/O memory of the CPU Unit.
Set bits 00 to 11 of the
PMCR(
) instruction C operand to a value between 000 and 999
BCD.
Check whether the communications sequence number is correct.
Specify another area, or reduce the size of the data to be sent or received.
127
Troubleshooting
Section 9-2
Serial communications mode
Serial communications mode is set to protocol macro.
Indicator display
Status information, etc.
I/O memory Cause Remedy
The
COMM @ indicators do not flash at all.
(Communications have not been electrically established.)
The PMCR(
) instruction is executed, but IR
20708 or IR
20712 (Protocol
Macro Executing Flag) does not turn ON.
The PMCR (
) instruction is not executed.
System error
FAL 9C does not occur.
IR 20708 or
IR 20712 (Protocol Macro
Executing Flag) turns ON when the PMCR(
) instruction is executed, but data cannot be sent or received properly.
IR 20708 or
IR 20712 (Protocol Macro
Executing Flag) momentarily turns ON when the PMCR(
) instruction is executed, but it does not remain
ON.
IR 20708 or
IR 20712 (Protocol Macro
Executing Flag) remains ON when the
PMCR(
) instruction is executed without setting the monitoring time for individual sequences
The error code in
IR 20408 to
IR 20411 or
IR 20412 to
IR 20415 is 4 Hex
(Protocol Data Syntax Error).
IR 20711 or
IR 20715 (Forced
Abort Bit) is ON.
Send processing is not executed.
IR 20711 or
IR 20715 (Forced
Abort Bit) is ON.
The sequence is running and does not end (the words allocated in the CIO
Area is in receive status).
The protocol data in the
Serial Communications
Board is incorrect.
---
The send wait time specified in communications sequence step units is too long.
Forced Abort Bit is forceset.
Protocol macro data is not set correctly.
The PC Setup settings such as the baud rate and frame format differ from those of the remote node.
Use CX-Protocol to correct and transfer the protocol data.
Release the Forced Abort
Bit
Use CX-Protocol to check whether the send wait time is correctly set.
Release the Forced Abort
Bit
Use CX-Protocol transmission line trace to check whether the protocol data and PC Setup settings are correct.
128
Troubleshooting
Section 9-2
Serial communications mode
Serial communications mode is set to protocol macro.
(Continued)
Indicator display
Status information, etc.
I/O memory Cause Remedy
The
COMM @ indicators do not flash at all.
(Communications have not been electrically established.)
Send data has already been transmitted, but there is no response from the remote node.
The
COMM @ indicators are flashing, but the
Serial Communications Board cannot perform communications or a communications error sometimes occurs.
A transmission error occurs.
Data is received through CX-Protocol transmission line trace, but the protocol macros behave as if no data is received.
The remote node sometimes returns no response to sent data. Response may be received by performing retries.
The contents of the words allocated in settings in the PC
Setup do not match those of the remote node.
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is not 0.
---
The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on.
Review the PC Setup settings.
Review the remote node settings and the program
(including the baud rate, frame format, and so on).
The wiring is faulty.
The setting of the 2/4wire switch for the RS-
422A/485 port does not match the actual wiring
(WIRE).
Wiring of adapters (e.g.,
NT-AL001-E) is faulty.
Hardware failure.
Check the wiring.
Turn ON the terminating resistances of the Serial
Communications Board and the last node. Turn
OFF the terminating resistances of other nodes.
Replace the Serial Communications Board.
Review the PC Setup settings.
Review the remote node settings and the program
(including the baud rate, frame format, and so on).
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is not 0.
The settings in the
PC Setup do not match those of the remote node.
---
The PC Setup settings such as the baud rate and frame format differ from those of the remote node. The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on.
---
Because response from the remote node is received too fast, the data received from the time the data send processing was completed until the
Send operation was completed is discarded.
The transmission timing is too fast for the remote node to receive data.
Check the settings of the remote node and review programming (i.e., the timing of sending response data).
Set or increase the transmission wait time (time to await data transmission) in step units.
129
Troubleshooting
Section 9-2
Serial communications mode
Serial communications mode is set to protocol macro.
(Continued)
Indicator display
Status information, etc.
The
COMM @ indicators are flashing, but the
Serial Communications Board cannot perform communications or a communications error sometimes occurs.
A transmission error sometimes occurs.
I/O memory Cause Remedy
The error code in
IR 20100 to
IR 20103 for port 1 or IR 20108 to
IR 20111 for port 2 is not 0.
The wiring is faulty.
The RS-422A/485 port terminating resistance setting is incorrect.
Adapters such as the NT-
AL001-E are incorrectly wired, or the terminating resistance setting is incorrect.
A communications error frequently occurs due to noise and so on.
Check the wiring.
Turn ON the terminating resistance of the Serial
Communications Board and the last node by using the terminating resistance switch. Turn
OFF the terminating resistance of other nodes.
Use shielded twisted pair cables.
House the communications cables in a different duct from those for power lines and so on.
Review the operating environment to prevent noise problems.
Note The following table shows the measures to correct error codes provided in
IR 20408 to IR 20411 for port 1 and IR 20412 to IR 20415 for port 2.
Error code
Indicator Error details
0 Hex No display Normal
1 Hex No display The PC Setup settings (DM
6550 to DM
6559) for the
Serial Communications Board are in
Protocol
Macro Mode.
2 Hex No display Sequence number error
---
---
3 Hex ERR/ALM:
Flashing
Receive data write range overflow error
Cause Remedy
---
Review the The PC Setup settings for the
Serial Communications Board in the relevant port.
The communications sequence number specified in bits 00 to 11 of the
PMCR(
) instruction’s C operand is not registered.
The data range of the specified area is exceeded when data is being written to or read from the I/
O memory of the
CPU Unit.
Correct the communications sequence number.
Use CX-Protocol to register the specified communications sequence number.
For operand specification:
Check the PMCR(
) instruction S and D operand specifications.
For direct specification of link words:
Use CX-Protocol to check the specified range.
130
Troubleshooting
Section 9-2
Error code
4 Hex ERR/
ALM:
Flashing
5 Hex
Indicator
ERR/
ALM:
Flashing
Error details
Protocol data syntax error
Protocol macro execution error during port initialization
Cause Remedy
There is a code that cannot be executed during protocol execution.
The PMCR instruction was executed while the port was being initialized.
Check the following items and correct the problem.
• Check whether the total specified number of link words in the area (
O
1,
O
2,
I1, I2) exceeds 128.
• The same area with link word specification is used by both ports 1 and 2.
• A write instruction with constant specification is specified.
• An EM Area read/write instruction is specified as an interrupt notification.
• There are more than 30 write attributes set for one message.
• The length of a send/receive message is set to 0 bytes.
• The length of a send/receive message is longer than 127 bytes.
• No messages are registered for matrix reception.
• Both RTS/CTS flow control and Xon/
Xoff flow control are set for the same transmission line.
Check if the PMCR instruction was executed during any one of the following processes.
• While the serial communications port was being restarted.
• While the serial communications mode in the PC system setup of the Serial
Communications Board was being modified using the STUP instruction.
• While the serial communications mode in the PC system setup of the Serial
Communications Board was being modified using the Programming
Device.
131
Troubleshooting
Section 9-2
9-2-3 1:N NT Link Mode
Serial communications mode
Serial communications mode is not set to NT
Link.
Serial communications mode is set to NT Link.
---
Indicator display
The COMM @ indicators do not flash at all.
(Communications have not been electrically established.)
The SD and
COMM @ indicators are flashing, but the Serial
Communications Board cannot communicate with the Programmable Terminal (PT).
---
---
Status information, etc.
---
I/O memory Cause Remedy
Bits 12 to 15
(Serial Communications Mode) of DM 6555/
DM 6550 are set to a value other than 5 Hex.
---
Serial communications mode is not set correctly.
There is a hardware error.
Set bits 12 to 15 (Serial
Communications Mode) of
DM 6555/ DM 6550 to
5 Hex.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Serial Communications Board.
--There is a setting error for the PT serial port.
The I:N NT Link unit number of the PT is incorrect.
The same 1:N NT
Link unit number has been set for more than one PT
The maximum allowable NT Link unit number is incorrectly set for the system.
Correct the PT serial port settings.
Review the NT Link unit number of the PT.
Review the PC Setup settings.
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the
NT-AL001-E are incorrectly wired or set.
A communications error frequently occurs due to noise, etc.
There is a PT hardware error.
Review the wiring or switch settings.
Review the wiring and installation environment.
Replace the PT.
132
Cleaning and Inspection
Section 9-3
Serial communications mode
Serial communications mode is set to NT Link.
Indicator display
The COMM @ indicators are flashing, but a communications error sometimes occurs in the PT.
Status information, etc.
-----
I/O memory Cause Remedy
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the
NT-AL001-E are incorrectly wired or set.
A communications error frequently occurs due to noise, etc.
Review the wiring or switch settings.
Check whether the terminating resistances of the host computer and the last node are set to ON, and the terminating resistances of other nodes are set to OFF.
The communications monitoring time for the PT is insufficient.
The load on the PC is too high.
Review the wiring and installation environment.
Increase the number of retries for the PT as required.
Increase the communications monitoring time for the
PT.
Lighten the load on the PC.
Reduce the number of PTs connected to each serial port by using other ports for some of the PTs.
Adjust the timeout and retry settings in the PT.
Note The PT serial port must be set for a 1:N NT Link. The PT will not be able to communicate with a Serial Communications Board if the PT is set for a 1:1 NT
Link.
9-3 Cleaning and Inspection
Use the cleaning and inspection methods described here for daily maintenance of the devices.
9-3-1 Cleaning
To keep the Serial Communications Board in optimum condition, regularly clean the Serial Communications Board as follows:
• Wipe the surface of the Serial Communications Board daily with a soft, dry cloth.
• If any dirt cannot be removed with a dry cloth, moisten the cloth with a mild detergent diluted to 2%, and squeeze out any excess moisture before wiping the Serial Communications Board.
• Do not adhere materials, such as gum, vinyl, or tape to the Serial Communications Board for long periods of time. Doing so may cause stains on the device. Remove any adhered materials when cleaning the Serial
Communications Board.
Note Never use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths.
133
Cleaning and Inspection
9-3-2 Inspection
Materials for Inspection
Inspection Items
Section 9-3
To keep the Serial Communications Board in optimum condition, regular inspections must be performed. Normally, inspect the devices once every six months or every year. Inspect the devices at more regular intervals when they are being used in environments subject to high temperatures, high humidity, or high dust levels.
Prepare the following materials before performing any inspections.
Materials Required Daily
For daily inspection, a Phillips screwdriver, flat-blade screwdriver, tester (or digital voltmeter), industrial strength alcohol, and all-cotton cloth are required.
Materials Required Occasionally
For some inspections, a synchroscope, a pen oscilloscope, a temperature gauge, and a hygrometer will be required.
Inspect the following items to check whether the Serial Communications
Board is operating within the specified criterion. If the Serial Communications
Board is not within the criterion, improve the ambient operating environment and readjust the device.
Item Details Criterion
Operating environment
0 to 55
°
C
Inspection materials
Temperature gauge
Check the ambient temperature and the temperature inside the control panel.
Check the ambient humidify and the humidity inside the control panel.
Check for accumulated dust.
Installation Check that the Serial Communications Board is mounted securely.
Check for loose screws on the communications cables.
Check for damaged communications cables.
10% to 90% RH
(no condensation or icing)
No dust
Hygrometer
Visual inspection
--Board must be mounted securely.
Screws must be securely tightened.
Cables should be fully intact.
Phillips screwdriver
Visual inspection
134
Board Replacement
Section 9-4
9-4 Board Replacement
A malfunction of the Serial Communications Board may affect the operation of remote communications devices, so be sure to perform repairs or replace the faulty Board promptly. Make sure a spare Serial Communications Board is available to replace a faulty one, so that functionality can be restored without delay.
9-4-1 Precautions
Observe the following precautions when replacing the Serial Communications
Board.
• Always turn OFF the power to the PC before replacing the Serial Communications Board.
• Be sure to check that the Serial Communications Board replacing the faulty one is not defective.
• If the defective Serial Communications Board is to be dispatched to the manufacturer for repair, be sure to include documentation stating the nature of the fault in as much detail as possible, and send to your nearest
OMRON branch or sales office, listed at the back of this manual.
If the contacts are defective, clean the contacts with a clean all-cotton cloth moistened with industrial-strength alcohol. Remove any cloth particles before mounting the Serial Communications Board.
Note Turn OFF the power to all serial external devices when replacing the Serial
Communications Board to prevent malfunctions.
9-4-2 Settings after Replacing the Board
After replacing the Serial Communications Board, make sure that wiring and settings, such as hardware switch settings, the settings for the Serial Communications Board in the PC Setup, and protocol macro data are the same as the
Serial Communications Board that was replaced.
Note
1.
If the CPU Unit is to be replaced, transfer to the replacement CPU Unit the contents of the Holding Areas and DM Area required for operation before starting operation. If the relationship between the DM Area and Holding
Area and the program is not maintained, unexpected malfunctions may result.
2.
The PC Setup of the Serial Communications Board is saved in the DM
Area of the CPU Unit. If the CPU Unit is to be replaced, either transfer the
PC Setup data to the CX-Programmer or CX-Protocol before replacing the
CPU Unit or reset the PC Setup.
9-4-3 Replacement Procedure
Standard System Protocols, Host Link Communications, No-protocol Communications, 1:1 Data Links, or NT Links
1,2,3...
1.
Turn OFF the power to the PC to which the Serial Communications Board to be replaced is mounted, and to all serially connected external devices.
2.
Disconnect the communications cables connected to the Serial Communications Board to be replaced, and also remove the Serial Communications
Board.
3.
Set the hardware switches of the replacement Board to the same settings of the Serial Communications Board being replaced before mounting, as follows:
135
Board Replacement
Section 9-4
• Terminating resistance switch (TERM)
• The 2/4-wire switch (WIRE)
4.
Turn ON the power of the PC to which the replacement Serial Communications Board is mounted, and to all serially connected external devices, and start operating the system.
5.
Check from the indicators and status display that the system is operating normally.
Protocol Macros Designed with CX-Protocol
1,2,3...
Note
1.
Connect Programming Console or CX-Protocol to the PC to which the replacement Serial Communications Board is mounted, and switch to PRO-
GRAM mode.
2.
Save the protocol macro data using the CX-Protocol. Refer to the CX-Pro-
tocol Operation Manual (W344) for details.
3.
Turn OFF the power to the PC to which the Serial Communications Board to be replaced is mounted, and to all serially connected external devices.
4.
Disconnect the communications cables connected to the Serial Communications Board to be replaced, and also remove the Serial Communications
Board.
5.
Set the hardware switches of the replacement Board to the same settings of the Serial Communications Board being replaced before mounting, as follows:
• Terminating resistance switch (TERM)
• The 2/4-wire switch (WIRE)
6.
Turn ON the power of the PC to which the replacement Serial Communications Board is mounted, and to all serially connected external devices, and start operating the system.
7.
Switch the CPU Unit to PROGRAM mode, and using the CX-Protocol, transfer the protocol macro data to the Serial Communications Board.
8.
Switch the CPU Unit to MONITOR mode, and start operating the system.
9.
Check from the indicators and status display that the system is operating normally.
1.
The protocol macro data for the Serial Communications Board is stored in the flash memory of the Serial Communications Board.
2.
When protocol macro data designed with the CX-Protocol is used, a backup of the protocol macro data created from the CX-Protocol must be transferred to the Serial Communications Board after replacing.
3.
The PC Setup of the Serial Communications Board is allocated to the DM
Area saved in the battery backup of the CPU Unit, and if the user-designed macro data is not used, the PC Setup can be used as before, simply by setting the hardware.
136
Appendix A
Introduction
Appendices B to N provide information on the standard system protocols provided with the CX-Protocol, the
Serial Communications Boards. Refer to 5-7 Using Protocol Macros for details on using PMCR(
).
Using Standard System Protocols
Standard system protocols can be executed merely by specifying the sequences number to be executed in the second operand of PMCR(
) and settings the data described in the appendices in the proper format starting at the word specified with the third operand of PMCR(
). The data received as a response to executing the sequence will be automatically stored starting at the word specified with the fourth operand of PMCR(
).
Procedure
1,2,3...
1. Set the port number (1 or 2) and the sequence number as BCD values in the first operand of PM-
CR(
).
2. Specify the address of the first word containing the data required for the sequence as the second operand (S: First word of send data) of PMCR(
).
3. Specify the address of the first word where respond data is to be stored as the third operand (D:
First receive data storage word) of PMCR(
). Unless there is a reason to specify otherwise, set
0000 Hex in D at the initial value.
Example
The following data would be used to execute sequence number 600 in the CompoWay/F Master Protocol for a transmission with ASCII conversion.
PMCR(
)
1600
S
D
Communications port: 1 (BCD)
Communications sequence number: 600 (BCD)
S: Send Data Word Allocation (3rd Operand)
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Node number
(Undefined)
SRC
Number of send bytes
Send data
Offset
S+0
S+1
Contents (data format)
Number of send data words
(4 digits BCD)
(Undefined)
S+2 MRC
(2 digits Hex)
0005 to 0128 BCD
Data
Node No. (2 digits
BCD)
00 to 99
SRC (2 digits Hex) Set the command code for the required service
S+3 Number of send bytes (4 digits BCD)
S+4 on
Send data (4-digit Hex)
Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 0492
The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent.
137
Introduction
D: Receive Data Word Allocation (4th Operand)
Receive data storage words
+0
+1
+2
Number of receive data words
Response code
Receive data
Appendix A
Offset
D+0
D+1
D+2 on
Contents (data format)
Number of receive data words
(4 digits BCD)
0003 to 0128 BCD
Data
Response code (4 digits Hex) The response code will be stored in hexadecimal form.
Receive data (4-digit Hex) The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here.
Standard System Protocols
The following 13 standard system protocols are provided with the CX-Protocol and the Serial Communications
Boards.
Protocol name Function
CompoWay/F Master
E5 @ K Digital Controller Read
E5 @ K Digital Controller Write
Protocol for sending CompoWay/F commands as a Master to OMRON CompoWay/F slave components and receiving responses.
Protocol for controlling an E5 @ K Digital Controller via the Board. Procedures for reading the MV the operating parameter settings
Protocol for controlling an E5 @ K Digital Controller via the Board. Procedures for writing set points and operating parameters.
E5ZE Temperature
Controller Read
E5ZE Temperature
Controller Write
Protocol for controlling an E5ZE Temperature Controller via the Board. Procedures for reading measured temperature and operating parameter settings.
Protocol for controlling an E5ZE Temperature Controller via the Board. Procedures for writing control temperatures and operating parameters.
E5 @ J Temperature
Controller
Protocol for controlling a E5 @ J Temperature Controller via the Board. Procedures for writing set points, reading output amounts, and reading/writing operating parameters.
ES100 @ Controller Protocol for controlling an ES100 @ Controller via the Board. Procedures for writing adjustment parameters, reading operation amounts, and writing/reading operating parameters.
Intelligent Signal
Processor
V500/V520 Bar
Code Reader
3Z4L Laser
Micrometer
F200/F300/F350
Visual Inspection
Systems
V600/V620 ID Controllers
Hayes modem AT commands
Protocol for controlling a Intelligent Signal Processor via the Board. Procedures for writing comparison values and reading display values are set.
Protocol for controlling a Bar Code Reader via the Board. Procedures for controlling the Bar Code
Reader in remote mode, reading the data that has been read by the Bar Code Reader, and reading/ writing operating parameters.
Protocol for controlling a Laser Micrometer via the Board. Procedures for controlling the Laser
Micrometer in remote mode, reading measured data, and writing/reading operating parameters.
Protocol for controlling a Visual Inspection System via the Board. Procedures for controlling the
Visual Inspection System in remote mode, reading measured values, and writing/reading operating parameters.
Protocol for controlling an ID Controller via the Board. Procedures for performing Read/Write operations of the ID Controller and writing/reading operating parameters.
Protocol for controlling a Hayes modem (AT commands) via the Board. Procedures for initialization of the modem, dialing, data transmission, switching to escape mode, and disconnecting the line.
Note Some of the standard system protocols do not allow communications with 32 nodes for one execution of a sequence (for 1:N connections). For example, it’s not possible when the number of Units in send data is 1 to 25 for unit numbers 00 to 31 (e.g., in the temperature controller read sequences). This restriction is due to a limit in the number of words that can be transferred between the CPU Unit and the Serial
Communications Board. These sequences, however, allow the unit numbers of connected devices to be specified in the send data. You can thus set different unit numbers in the send data and execute
PMCR(
) for the same sequence as many times as required for all unit numbers.
138
Appendix B
CompoWay/F Master Protocol
The CompoWay/F Master Protocol is used to send CompoWay/F commands with the CS1-series PC serving as the host (master).
CompoWay/F
CompoWay/F is a protocol used by many OMRON components for serial communications. A host computer of a PC can function as a host (master) to send CompoWay/F commands (message frames) to OMRON components, which function as slaves. The components will return responses to these commands. Using CompoWay/
F commands, the host can read/write data, settings, and operating status to control the operation of the components.
CompoWay/F has the following features.
• The same message frame format is used, eliminating the need for special protocols for each component.
The same commands can thus be used for serial communications with all CompoWay/F components.
• The CompoWay/F protocol conforms to OMRON’s standard FINS command protocol, providing compatibility with other networks and more flexible expansions in the future.
The CompoWay/F Master Protocol is provided as a standard system protocol to enable the CQM1H-series PC to executed read/write sequences for CompoWay/F commands.
System Configuration for Standard System Protocol
RS-232C Connections
CQM1H-series PC: Host
CompoWay/F response
RS-232C
CompoWay/F command
RS-422A/485 Connections
CQM1H-series PC: Host
CompoWay/F response
OMRON CompoWay/F component: Slave
RS-422A/485
CompoWay/F command
OMRON CompoWay/F components: Slaves
139
CompoWay/F Master Protocol
Appendix B
Communications Specifications
Item
Transmission path connections
Communications
Synchronization
Baud rate
Transmitted code
Data length
Stop bits
Error detection
Multipoint
Specification
RS-232C, RS-422A/485, 4-wire half-duplex, 2-wire half-duplex
Start-stop
1,200/2,400/4,800/9,600/19,200 bps
Default: 9,600 bps
ASCII
7 bits or 8 bits (Default: 7 bits)
Note
A 7-bit code is used with 0 added to the beginning.
1 bit or 2 bits (Default: 2 bits)
Horizontal parity (none, even, or odd) (Default: Even)
BCC (block check character)
*1: Start-stop Sync Data Configuration for Protocol Macros
LRC, 1 byte, equivalent to binary
Transmission Procedure
The PC or host computer serving as the master sends a command and the component serving as the slave returns a response for the command message contained in the command. One response message is returned for each command message. The movement of command and response messages is shown below.
Command message
Master (PC or host computer)
Slave (component)
Response message
Command and Response Formats
Note In the following diagrams “Hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters.
Command Format
1 byte
Node No.
Subaddress
2 bytes
"00"
2 bytes
"0"
1 byte
Command
Text
Data
1 byte
1 byte
Response Format
1 byte
Node No.
2 bytes
Subaddress End code
"00"
2 bytes
"00"
2 bytes
Response
Text
Data
(See note.)
1 byte 1 byte
Note 1.
Data is not saved in the response if there is a command frame error (i.e., if the end code is not 00 or
0F).
2. Other values are possible for the subaddress and SID.
140
CompoWay/F Master Protocol
Command Frame Contents
Appendix B
STX
Item
Node number
Subaddress
Meaning
A code, 02 Hex, indicating the beginning of a communications frame (text). This code must always be set as the first byte.
The node number identifies the source of the command frame. Specify “XX” to broadcast a transmission. There will be no response made to a broadcast.
Set “00” for most components. Other values must be set for special components.
SID
Command and text
Set “0” for most components. Other values must be set for special components.
The command and required text are placed here. Refer to the command codes and text for individual sequences.
ETX
MRC and SRC The command code specifies the service being used.
Refer to the command codes and text for individual sequences.
A code, 03 Hex, indicating the end of text.
BCC The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the
STX to the ETX.
Response Frame Contents
STX
Item
Node number
Meaning
A code, 02 Hex, indicating the beginning of a communications frame (text). This code must always be set as the first byte.
The node number identifies the source of the command frame. “XX” is specified to broadcast a transmission.
There will be no response made to a broadcast.
Subaddress
SID
“00” for most components. Other values must be set for special components.
“0” for most components. Other values must be set for special components.
End code (See note.) The results of executing the command frame.
Response and text
MRES and
SRES
Note: The response code (MRES and SRES) indicates the results for the command code; the end code indicates the results for the command frame. These are not the same.
The response and requested text are placed here. Refer to the response and text for individual sequences.
The response code specifies the results of processing the service requested by the command code. Refer to the response codes and text for individual sequences.
ETX
BCC
A code, 03 Hex, indicating the end of text.
The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the
STX to the ETX.
141
CompoWay/F Master Protocol
Appendix B
Note The end codes are described in the following table.
End code
“00”
“0F”
“10”
“11”
“12”
“13”
“14”
“16”
“18”
Name
Normal end
Meaning
The command frame was processed normally without any of the following errors.
Command error The specified command could not be executed.
Refer to the response code for more information.
Parity error A parity error was detected for one of the characters that was received.
Framing error
Overrun error
A framing error was detected for one of the characters that was received.
A overrun error was detected for one of the characters that was received.
BCC error
Format error
The BCC for the receive frame was incorrect.
An illegal command or illegal character was received in the command and text (characters other than
ASCII 0 to 9 or A to F).
Subaddress error The receive frame contained an illegal subaddress.
Frame length error
The receive frame was too long.
Example
The command and response frames for a K3N @ -series Intelligent Signal Processor are shown below.
Command Frame
Node No.
Subaddress
Command
Text
SID
Data
Command
Command code
Command code
“01” “01” Variable type Address
Data contents
Data contents
VARIABLE AREA READ
VARIABLE AREA WRITE “01” “02” Variable type Address
PARAMETER AREA READ
PARAMETER AREA WRITE
“02” “01” Parameter type
“02” “02” Parameter type
PROCESSOR STATUS READ “05” “03”
CONTROLLER STATUS READ “06” “01”
ECHOBACK TEST
OPERATION COMMAND
“08” “01” Text data
“30” “05” Command code
Address
Address
Response Format
Node No.
Subaddress End code
Response Text
“00” No. of elements
“00” No. of elements
No. of elements
No. of elements
Write data
Write data
Data
Command code
Response code
142
CompoWay/F Master Protocol
Appendix B
Example: VARIABLE AREA READ
The following command and text are used to read the present value, maximum value, minimum value, and status of the Intelligent Signal Processor.
Command and Text
Variable type
First read address
No. of elements
2 bytes 2 bytes 2 bytes 4 bytes 4 bytes
1,2,3...
1.
Variable Type
“C0”
Variable type Contents
Present value, maximum value, minimum value, status, and comparison value
2.
First Read Address
Specify the address of the data to be read in 4 digits Hex.
3.
Number of Elements: 4 Digits Hex
“0001”
Number of elements Process
Read the data and end normally.
Note If “0000” is specified, nothing will be read and a normal end will be returned. A parameter error will occur for any settings other than “0000” and “0001.”
Response Text
2 bytes 2 bytes
Response code
4 bytes
Read data
8 bytes
1,2,3...
1.
Response Code: MRES, SRES
“0000”
“1001”
“1002”
“1100”
“1101”
“1103”
“2203”
Response code Meaning
Normal end
Command too long
Command too short
Parameter error
Area type error
First address range error
Operating error
2.
Read Data
The specified data is returned in 8 digits of hexadecimal data.
143
CompoWay/F Master Protocol
Appendix B
CompoWay/F Master Protocol Sequences
The CompoWay/F Master Protocol provides six communications sequences that can be used for the following:
• Converting to ASCII data or not converting to ASCII data
• Sending to a specified Unit or broadcasting
• Specifying from the command code or specifying from the subaddress and SID.
Structure of the Protocol
The following table shows the structure of the CompoWay/F Master Protocol.
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
Yes
Receive word allocation
Yes 600
601
602
603
604
605
Send with ASCII conversion, with response
Broadcast with ASCII conversion, no response
Send with no conversion and with response
Broadcast with no conversion and no response
General-purpose send with no conversion and with response
General-purpose broadcast with no conversion and no response
Converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word.
A broadcast version of sequence No. 600.
No responses are received.
Sends specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. This is the same as sequence No.
600 without data conversion and can be used when conversion is not required.
A broadcast version of sequence No. 602.
No responses are received.
Sends specified data beginning with the subaddress and SID to the specified Unit.
The response is stored starting at the specified word. This sequence can be used whenever it is necessary to specify the subaddress or SID.
A broadcast version of sequence No. 604.
No responses are received.
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
No
Sequence No. 600 can be used for the normal CompoWay/F Master function (ASCII conversion, specification from command code).
Refer to the communications specifications for the OMRON CompoWay/F component to which the command is being sent and set the command code and required data starting at the words specified for the 3rd operand of
PMCR(260).
The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is described next.
144
CompoWay/F Master Protocol
Appendix B
CompoWay/F Message Frames and PMCR(260) Operands
The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is shown below, using communications sequence No. 600 as an example.
Command Frame
Variable type
First read address
No. of elements
Node No.
Subaddress
Command
Send data
Response Frame
PMCR(260) Instruction
PMCR(260)
#1600
S
D
S
S+1
S+2
S+3
S+4
S+5
S+6
Communications port: 1
Send/receive sequence number:
600 (0258 Hex)
Number of send data words
(Undefined) Node number
Number of send bytes
Send data
Node No.
Subaddress End code
Response code
Response code
Receive data
Read data
Receive data
PMCR(260) Instruction
PMCR(260)
#1600
S
D
D
D+1
D+2
D+3
Number of receive data words
Response code
Receive data
Send with ASCII Conversion, with Response:
(Sequence No. 600)
This sequence converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word.
145
CompoWay/F Master Protocol
Appendix B
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Node No.
MRC
SRC
Number of send bytes
+4
Send data
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
(Undefined) Node No. (2 digits BCD)
+2 MRC
(2 digits Hex)
SRC
(2 digits Hex)
+3 Number of send bytes (4 digits
BCD)
+4 on
Send data (4-digit Hex)
0005 to 0128
00 to 99
Data
Set the command code for the required service
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0 to 984 decimal
The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent.
Note 1.
Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent.
2.
When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units.
Send data words
1 2 3 4
5 6 7 8
Send frame
"56" "78" "12" "34"
Receive Data Word Allocation (3rd Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Response code (4 digits Hex)
0003 to 0128
Data
+2 on
Receive data (4-digit Hex)
The response code will be stored in hexadecimal form.
The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here.
Note When ASCII data is converted to hexadecimal data, data is stored starting from the receive data word with the largest offset. This is done because ladder programming handles data in 4-byte units.
Receive frame
"01" "23" "45" "67"
Receive data words
4 5 6 7
0 1 2 3
146
CompoWay/F Master Protocol
Appendix B
Example: The following example illustrates reading the present value from a K3N @ -series Intelligent Signal
Processor.
CS1-series PC
CompoWay/F response
Read data = present value
CompoWay/F command
VARIABLE AREA READ
Command code: 01 01
First read address
Intelligent Signal Processor
K3N @ @@@@ -FLK1/2/3/4/5/6
Sequence No. 600 (Send with ASCII Conversion, with Response) is used. The specified data beginning with the command code is converted ASCII and sent to the Intelligent Signal Processor with the specified node number. The response is converted to hexadecimal and stored starting at the specified word.
The command frame for reading the present value for a K3N @ @@@@ -FLK1/2/3/4/5/6 Intelligent Signal Processor (command code 01 01) is shown below. The following data is specified in the operands for PMCR(260).
• Rightmost byte of S+1: Node number (2 digits BCD)
• S+2: Command code: MRC + SRC = “0101”
• S+4 on: Send data = Variable type + first read address + 00 + number of elements.
STX
(02Hex)
Node No.
(
×
10
1
) (
×
10
1
)
Subaddress
00 0
SID Command code
MRC SRC
01 01
Variable type
C0
Send data
First read address
(Note)
0000
Always
00
00
No. of elements
0001
ETX
(03Hex)
BCC
Data in shaded portions is specified in the PMCR(260) instruction.
Note A first read address of 0000 specifies the present value. An address of 0001 specifies the maximum value; 0002, the minimum value; and 0003, the status.
The response frame is shown below. The response code and receive data are stored according to the operands for PMCR(260) as follows:
• D+1: Response code
• D+2 and on: Receive data
STX
(02 Hex)
Node No.
(
×
10
1
) (
×
10
1
)
Subaddress
End code Command code
01
MRC
01
SRC
00
Response code
Note 1
00
Receive data
Read data
(Note 2)
0000
ETX
(03 Hex)
BCC
Data in shaded portions is stored at the location specified by the operand in the PMCR(260) instruction.
Note 1.
Response Codes
“0000”
“1001”
“1002”
“1100”
“1101”
“1103”
“2203”
Response code Meaning
Normal end
Command too long
Command too short
Parameter error
Area type error
First address range error
Operating error
2.
The read data is returned as 4-digit hexadecimal as follows: F0019999 to 00099999 Hex.
147
CompoWay/F Master Protocol
Appendix B
The 2nd and 3rd operands of the PMCR(260) instruction are specified as follows.
Send Data Word Allocation (2nd Operand of PMCR(260))
Offset
+0
+1 (Undefined) Node No. (2 digits BCD)
+2 MRC
(2 digits Hex)
+3
SRC
(2 digits Hex)
Number of send bytes (4 digits
BCD)
+4 Send data (12 digits Hex)
+5
+6
Contents (data format)
Number of send data words
(4 digits BCD)
0007
0000 Hex
0101 Hex
0012 (BCD)
C000 Hex
0000 Hex
0001 Hex
Data
Receive Data Word Allocation (3rd Operand of PMCR(260))
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Response code (4 digits Hex)
Data
EX is stored at reception (0004)
The response code will be stored in hexadecimal form.
The normal end response code is 0000.
The 4 bytes of read data.
+2
+3
Receive data (8 digits Hex)
Broadcast with ASCII Conversion, No Response
(Sequence No. 601)
This sequence converts the specified data beginning with the command code to ASCII and broadcasts it. No responses are received.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
MRC SRC
Number of send bytes
+4
Send data
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
(Undefined)
+2 MRC
(2 digits Hex)
+3
SRC
(2 digits Hex)
Number of send bytes (4 digits
BCD)
+4 on
Send data (4-digit Hex)
0005 to 0128
Data
---
Set the command code for the required service
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0 to 984 decimal
The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent.
Note 1.
Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent.
148
CompoWay/F Master Protocol
Appendix B
2.
When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units.
Send data words
1 2 3 4
5 6 7 8
Send frame
"56" "78" "12" "34"
Receive Data Word Allocation (3rd Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as 000.)
Send with No Conversion and with Response
(Sequence No. 602)
This sequence sends the specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Node No.
MRC
SRC
Number of send bytes
+4
Send data
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
(Undefined) Node No. (2 digits
BCD)
0005 to 0128
00 to 99
Data
+2 MRC
(2 digits Hex)
+3
SRC (2 digits Hex) Set the command code for the required ser-
Number of send bytes (4 digits BCD) vice
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0 to 492 decimal
+4 on
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent.
Receive Data Word Allocation (3rd Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Response code (4 digits Hex)
+2 on
Receive data (Hex)
+0 +1
+2
+4
+6 etc.
+3
+5
Data
0003 to 0128
The response code will be stored in hexadecimal form.
The data from just after the response code until just before the ETX is stored here without conversion.
149
CompoWay/F Master Protocol
Offset Contents (data format)
+0 Number of send data words
(4 digits BCD)
(Undefined) +1
+2 MRC
(2 digits Hex)
SRC
(2 digits Hex)
+3 Number of send bytes (4 digits
BCD)
Appendix B
Broadcast with No Conversion and No Response
(Sequence No. 603)
This sequence broadcasts the specified data beginning with the command code No responses are received and no conversions are performed on the send data.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
MRC
SRC
Number of send bytes
+4
Send data
Data
0005 to 0128
---
Set the command code for the required service
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0 to 492 decimal
The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent.
+4 on
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
Receive Data Word Allocation (3rd Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
150
CompoWay/F Master Protocol
Appendix B
Generalpurpose Send with No Conversion and with Response
(Sequence No. 604)
This sequence sends the specified data beginning with the subaddress and SID to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Node No.
(Undefined)
Subaddress
(Undefined)
SID
Number of send bytes
Send data
Offset
+0
+1
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Always 00 Hex Node No. (2 digits BCD)
+2 MRC
(2 digits Hex)
Subaddress (2 digits Hex)
0006 to 0128
00 to 99
Data
Specify the subaddress of the device being communicated with.
Always 00 Hex SID (1 digit Hex) Set the service ID of the required service (e.g., retries).
+4 Number of send bytes (4 digits
BCD)
+5 on
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
Number of data bytes from the MCR until the byte just before the ETX.
0 to 490 decimal
The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent.
Receive Data Word Allocation (3rd Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2
Response data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Response code (4 digits Hex)
+2 on
Receive data
+0
+2
+4
+6 etc.
+1
+3
+5
Data
0003 to 0128
The response code will be stored in hexadecimal form.
The data from just after the response code until just before the ETX is stored here without conversion.
151
CompoWay/F Master Protocol
Appendix B
Generalpurpose Broadcast with No Conversion and No Response
(Sequence No. 605)
This sequence broadcasts the specified data beginning with the subaddress and SID. No responses are received and no conversions are performed on the send data.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
(Undefined)
(Undefined)
Subaddress
SID
Number of send bytes
+5
Send data
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Always 0000 Hex +1
+2 MRC
(2 digits Hex)
Subaddress (2 digits Hex)
+3
+4
0006 to 0128
---
Data
Specify the subaddress of the device being communicated with.
Always 00 Hex SID (1 digit Hex) Set the service ID of the required service (e.g., retries).
Number of send bytes (4 digits
BCD)
Number of data bytes from the MCR until the byte just before the ETX.
0 to 490 decimal
+5 on
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent.
Receive Data Word Allocation (3rd Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
152
CompoWay/F Master Protocol
Appendix B
Connections
Connection methods between a Serial Communications Board and the K3N @ -series Intelligent Signal Processor are shown below.
RS-232C
• RS-232C connections are one-to-one.
• The max. cable length is 15 m. Use an RS-232C optical interface (Z3RN) when extending the transmission line beyond 15 m.
• Use shielded, twisted-pair cable.
Serial
Communications
Board
RS-232C
Abbreviation
Pin
No.
FG 1
SG 9
SD
RD
RTS
CTS
DSR
DTR
4
5
2
3
7
8
4
5
6
7
2
3
Intelligent
Signal
Processor
RS-232C
Pin
No.
Abbreviation
1 FG
SG
SD
RD
RTS
CTS
DSR
20 DTR
MAX232C or equivalent
TX
RX
Shield
K3N @ @@@@ -FLK1
Serial
Communications
Board
RS-232C
Abbreviation
SG
SD
RD
RTS
CTS
DSR
DTR
Pin
No.
7
8
4
5
9
2
3
FG
1/
Shell
Shield
Intelligent
Signal
Processor
RS-232C
Pin
No.
Abbreviation
5
3
2
6
4
7
8
SG
SD
RD
RTS
CTS
DSR
DTR
MAX232C or equivalent
K3N
@
-
@@@@
-FLK4
TX
RX
153
CompoWay/F Master Protocol
Appendix B
RS422 4wire Connections
• RS-422 connections can be one-to-one, or one-to-N when a 3G2A9-AL001 Link Adapter is used. A maximum of 32 Serial Communications Boards can be connected in one-to-N systems.
• The total cable length can be 500 m max.
• Use shielded, twisted-pair cable.
• Be sure to turn ON the terminating resistance switches at the device at each end of the transmission line.
Serial
Communications
Board
RS-422
Abbreviation
Intelligent Signal
Processor
Pin
No.
Abbreviation
220
Ω
Terminal block switch
SN751177N or equivalent
Shell
6
8
1
2
*1: Set the 2-/4-wire switch to the 4-wire setting.
*2: Turn ON the terminating resistance switch.
Shield
220
Ω
The terminator (220
Ω
) is set with the terminal block switch.
RS-485 2-wire Connections
• RS-485 connections can be one-to-one or one-to-N. A maximum of 32 Serial Communications Boards can be connected in one-to-N systems.
• The total cable length can be 500 m max.
• Use shielded, twisted-pair cable.
• Be sure to turn ON the terminator switches only in the devices at each end of the transmission line.
Serial
Communications
Board
RS-485
Abbreviation
Intelligent Signal Processor
Turn OFF all terminal block switches except at the end-station.
Terminal
Abbreviation
220
Ω
Terminal block switch
SN751177N or equivalent
Shell
1
2 +
Shield
*1: Set the 2-/4-wire switch to the 2-wire setting.
*2: Turn ON the terminating resistance switch.
Intelligent Signal
Processor end-station
Terminal
Abbreviation
220
Ω
Terminal block switch ON
+
Shield
Note SYSMAC BUS Wired Remote I/O devices cannot be connected.
Terminal block switch ON at the end station.
154
Appendix C
E5
@
K Digital Controller Read Protocol
The E5 @ K Digital Controller Read Protocol reads and controls various parameters in remote mode for the
Controller connected to the Serial Communications Board via RS-232C or RS-485 cable.
Structure of the Protocol
The following table shows the structure of the E5 @ K Digital Controller Read Protocol.
Sequence
No.
000
001
Communications sequence name
Read process value
Read set point during SP ramp
Function Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
Yes
002
003
004
005
006
007
008
009
010
011
012
013
014
015
016
017
018
019
020
021
022
023
Read MV
Read set point
Read alarm value
Read proportional band, integral time, and derivative time
Read cooling coefficient
Read dead band
Read manual reset value
Read hysteresis
Read control period
Read SP ramp time unit and set value
Read LBA detection time
Read MV at stop and PV error
Read MV limits
Read input digital filter
Read alarm hysteresis
Read input shifts
Read level 0 parameters
Read level 1 parameters 1
Read level 1 parameters 2
Read level 2 parameters 1
Read level 2 parameters 2
General-purpose read
Reads the process value.
Reads the set point during SP ramp.
Reads the MV (heating, cooling).
Reads the set point.
Reads alarm value 1, 2.
Reads the proportional band, integral (reset) time, and derivative
(rate) time
Reads the cooling coefficient.
Reads the dead band.
Reads the manual reset value.
Reads the hysteresis (heating, cooling).
Reads the control period (heating, cooling).
Reads the SP ramp time unit and
SP ramp set value.
Reads the LBA detection time.
Reads the MV at stop and the MV at PV error.
Reads the MV limits.
Reads the input digital filter.
Reads the alarm 1, 2 hysteresis.
Reads the input shift limits.
Reads parameters in level 0.
Reads parameters in level 1.
Reads parameters in level 1.
Reads parameters in level 2.
Reads parameters in level 2.
Reads the value of the specified parameter.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd or 3rd operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 2nd operand (S).
Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D).
155
E5
@K Digital Controller Read Protocol
Appendix C
Connection Configuration
The connection configuration for using the E5 @ K Digital Controller Read Protocol is shown below.
RS-232C Connection
CQM1H
E5 @ K
Serial Commu nications Board
RS-232C port
→
Serial Communications Board
RS-232C: D-sub 9 pin female
Signal name Pin No.
E5 @ K
RS-232C: Terminal block
Terminal No.
Signal name
Shielded cable
Note 1.
The communications configuration is a one-to-one configuration and the maximum cable length is
15 m.
2.
Use a shielded twisted-pair cable (AWG28i or greater) for the cable.
RS-485 Connection
CQM1H E5 @ K
Serial Communications Board
RS-485 port
→
E5 @ K
→
Up to 31 Units can be connected.
E5 @ K
→
Note 1.
The communications configuration is a one-to-one configuration or a one-to-N configuration. In the one-to-N configuration, up to 32 units including the Serial Communications Board can be connected.
2.
The maximum cable length is 500 m. Use a shielded twisted-pair cable for the cable (AWG28i or greater).
3.
Connect a terminator only at both ends of the transmission path. For instance, in the example shown below, connect a terminator to the Serial Communications Board and Unit No.30 and do not connect
156
E5
@K Digital Controller Read Protocol
Appendix C
any terminator to units No.0 to No.29. Use a resistance of 120
Ω
(1/2W) for the terminators (the total resistance of both ends must be 54
Ω
or more).
Serial Communications Board
RS-485: D-sub
9 pin female
Pin No.
Shielded cable
E5CK (No. 0)
RS-485: Terminal block
Terminal No.
E5CK (No. 30)
RS-485: Terminal block
Terminal No.
A<B: [1] Mark
A>B: [0] Space
Terminator (120
Ω
, 1/2 W)
Read Process Value (Sequence No. 000)
Reads the process value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
Number of receive data words
Process value
0002 (fixed)
00 to 31
Data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Process value (4 digits BCD)
0002
Data
Scaling lower limit to upper limit
Read Set Point during SP Ramp (Sequence No. 001)
Reads the set point during the SP ramp and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
Number of send data words
+1 (Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Set point during SP ramp
0002 (fixed)
00 to 31
Data
157
E5
@K Digital Controller Read Protocol
Appendix C
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Set point during SP ramp
(4 digits BCD)
Data
0002
Set point lower limit to upper limit
Read MV (Sequence No. 002)
Reads the MV (manipulated variable) for heating and cooling and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
Number of send data words
+1 (Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
MV (heating)
MV (cooling)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
MV (heating) (4 digits BCD)
0003
Data
+2 MV (cooling) (4 digits BCD)
F050 to 1050, 0000 to 1050 for heating/ cooling control
F indicates a negative value.
F050 to 1050
F indicates a negative value.
Read Set Point (Sequence No. 003)
Reads the set point and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Set point
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Set point (4 digits BCD)
0002 (fixed)
00 to 31
Data
Data
0002
Set point lower limit to upper limit
158
E5
@K Digital Controller Read Protocol
Appendix C
Read Alarm Value (Sequence No. 004)
Reads alarm value 1 and alarm value 2 and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Alarm value 1
Alarm value 2
0002 (fixed)
00 to 31
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Alarm value 1 (4 digits BCD)
0003
+2 Alarm value 2 (4 digits BCD)
Data
Data
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 005)
Reads the proportional band, integral time, and derivative time and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Number of receive data words
Proportional band
Integral time
Derivative time
0002 (fixed)
00 to 31
Data
+1
+2
+3
Offset
+0
Contents (data format)
Number of receive data words
(4 digits BCD)
Proportional band (4 digits BCD)
Integral time (4 digits BCD)
Derivative time (4 digits BCD)
0004
0000 to 9999
0000 to 3999
0000 to 3999
Data
159
E5
@K Digital Controller Read Protocol
Appendix C
Read Cooling Coefficient (Sequence No. 006)
Reads the cooling coefficient and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Cooling coefficient
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
0002
Cooling coefficient (4 digits BCD) 0001 to 9999
Data
Data
Read Dead Band (Sequence No. 007)
Reads the dead band and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Dead band
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Dead band (4 digits BCD)
0002 (fixed)
00 to 31
Data
Data
0002
A999 to 9999
F indicates a negative value and A indicates –1.
Read Manual Reset Value (Sequence No. 008)
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
160
E5
@K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Manual reset value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Manual reset value (4 digits BCD)
0002
0000 to 1000
Data
Read Hysteresis (Sequence No. 009)
Reads the hysteresis for heating and for cooling and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Hysteresis (heating)
Hysteresis (cooling)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
Hysteresis (heating)
(4 digits BCD)
Hysteresis (cooling)
(4 digits BCD)
0003
0001 to 9999
0001 to 9999
Data
Read Control Period (Sequence No. 010)
Reads the control period for heating and for cooling and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Control period (heating)
Control period (cooling)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
Control period (heating)
(4 digits BCD)
Control period (cooling)
(4 digits BCD)
0003
0001 to 0099
0001 to 0099
Data
161
E5
@K Digital Controller Read Protocol
Appendix C
Read SP Ramp Time Unit and Set Value (Sequence No. 011)
Reads the SP ramp time unit and SP ramp set value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined)
Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
SP ramp time unit
SP ramp set value
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
SP ramp time unit (4 digits BCD)
SP ramp set value (4 digits BCD)
0003
0000: s, 0001: hr
0000 to 9999
Data
Read LBA Detection Time (Sequence No. 012)
Reads the LBA (loop break alarm) detection time and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
LBA detection time
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
LBA detection time (4 digits BCD)
0002
0000 to 9999
Data
Read MV at Stop Time and at PV Error (Sequence No.013)
Reads the MV at stop time and at PV error and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
162
E5
@K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
MV at stop time
MV at PV error
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
MV at stop time (4 digits BCD)
+2 MV at PV error (4 digits BCD)
Data
0003
F050 to 1050
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
F050 to 1050
F indicates a negative value.
Read MV Limits (Sequence No. 014)
Reads the MV upper limit, MV lower limit, and MV change rate limit and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
Number of receive data words
MV upper limit
MV lower limit
MV change rate limit
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
MV upper limit (4 digits BCD)
0004
Data
+2
+3
MV lower limit (4 digits BCD)
MV change rate limit
(4 digits BCD)
MV lower limit + 1 to 1050
0000 to 1050 for heating/cooling control
F050 to MV upper limit –1
F indicates a negative value values.
A050 to 1050 for heating/cooling control
A indicates a negative value.
0000 to 1000
Read Input Digital Filter (Sequence No. 015)
Reads the input digital filter and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
163
E5
@K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Input digital filter
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Input digital filter (4 digits BCD)
0002
0000 to 9999
Data
Read Alarm Hysteresis (Sequence No. 016)
Reads the alarm 1 hysteresis and alarm 2 hysteresis and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Alarm 1 hysteresis
Alarm 2 hysteresis
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
Alarm 1 hysteresis
(4 digits BCD)
Alarm 2 hysteresis
(4 digits BCD)
0003
0001 to 9999
0001 to 9999
Data
Read Input Shift Limits (Sequence No. 017)
Reads the input shift upper limit and input shift lower limit and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
164
E5
@K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Input shift upper limit
Input shift lower limit
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Input shift upper limit (4 digits BCD)
+2 Input shift lower limit (4 digits BCD)
Data
0003
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
Read Level 0 Parameters (Sequence No. 018)
Reads parameters in level 0 (process value, set point during SP ramp, MV (heating), MV (cooling), and set point) from multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
(max.)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+36
+37
~
+38
+39
+40
Number of receive data words
Process value
Set point during SP ramp
MV (heating)
MV (cooling)
Set point
Process value
Set point during SP ramp
MV (heating)
MV (cooling)
Set point
~
1st unit
8th unit (max.)
165
E5
@K Digital Controller Read Protocol
Appendix C
+0
Offset
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Process value (4 digits BCD)
1st unit
Set point during SP ramp
(4 digits BCD)
1st unit
MV (heating) (4 digits BCD)
Data
Number of units
×
5 + 1
Scaling lower limit to upper limit
Set point lower limit to upper limit
+3
+4
+5
+40
(max.)
1st unit
MV (cooling) (4 digits BCD)
1st unit
Set point (4 digits BCD)
•
•
•
8th unit
Set point (4 digits BCD)
F050 to 1050
F indicates a negative value.
0000 to 1050 for heating/cooling control
0000 to 1050
Set point lower limit to upper limit
Set point lower limit to upper limit
Read Level 1 Parameters 1 (Sequence No. 019)
Reads parameters in level 1 (alarm value 1, alarm value 2 , alarm value 3, proportional band, integral time, and derivative time) from multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
~
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
(max.)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
+43
+44
~
+45
+46
+47
+48
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
~
1st unit
8th unit (max.)
166
E5
@K Digital Controller Read Protocol
Appendix C
+0
Offset
+1
+2
+3
+4
+5
+6
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Alarm value 1 (4 digits BCD)
1st unit
Alarm value 2 (4 digits BCD)
1st unit
Alarm value 3 (4 digits BCD)
1st unit
Proportional band
(4 digits BCD)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
•
•
•
8th unit
Derivative time (4 digits BCD)
Data
Number of units
×
6 + 1
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
0001 to 9999
0000 to 3999
0000 to 3999
+48
(max.)
0000 to 3999
Read Level 1 Parameters 2 (Sequence No. 020)
Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
(max.)
Number of units + 2
Data
0001 to 0008
00 to 31
167
E5
@K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+50
+51
+52
+53
~
+54
+55
+56
+4
+5
+6
+7
+0
+1
+2
+3
Number of receive data words
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Cooling coefficient (4 digits BCD)
1st unit
Dead band (4 digits BCD)
~
+3
+4
+5
+6
+7
+56
(max.)
1st unit
Manual reset value
(4 digits BCD)
1st unit
Hysteresis (heating)
(4 digits BCD)
1st unit
Hysteresis (cooling) (4 digits BCD)
1st unit
Control period (heating)
(4 digits BCD)
1st unit
Control period (cooling)
(4 digits BCD)
•
•
•
8th unit
Control period (cooling)
(4 digits BCD)
1st unit
8th unit (max.)
Data
Number of units
×
7 + 1
0001 to 9999
A999 to 9999
F indicates a negative value and A indicates –1.
0000 to 1000
0001 to 9999
0001 to 9999
0001 to 0099
0001 to 0099
0001 to 0099
168
E5
@K Digital Controller Read Protocol
Appendix C
Read Level 2 Parameters 1 (Sequence No. 021)
Reads parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop, MV at PV
Error, MV upper limit, MV lower limit, and MV change rate limit) from multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
Number of receive data words
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
+8
~
+57
+58
+59
+60
+61
+62
+63
+64
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
~
1st unit
8th unit (max.)
169
E5
@K Digital Controller Read Protocol
Appendix C
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
SP ramp time unit (4 digits BCD)
1st unit
SP ramp set value (4 digits BCD)
1st unit
LBA detection time (4 digits BCD)}
1st unit
MV at stop (4 digits BCD)
+5
+6
+7
1st unit
MV at PV error (4 digits BCD)
1st unit
MV upper limit (4 digits BCD)
1st unit
MV lower limit (4 digits BCD)
Data
Number of units
×
8 + 1
0000: s, 0001: hr
0000 to 9999
0000 to 9999
F050 to 1050
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
F050 to 1050
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
MV lower limit + 1 to 1050
0000 to 1050 for heating/cooling control
F050 to MV upper limit –1
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
0000 to 1000 +8
+64
(max.)
1st unit
MV change rate limit
(4 digits BCD)
•
•
•
8th unit
MV change rate limit
(4 digits BCD)
0000 to 1000
Read Level 2 Parameters 2 (Sequence No. 022)
Reads parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) from multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
Data
Number of units + 2
0001 to 0008
00 to 31
170
E5
@K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+43
+44
+45
+46
+47
+48
+0
+1
+2
+3
+4
+5
+6
~
Number of receive data words
Input digital filter
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
Input digital filter
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
+0
Offset
+1
+2
+3
+4
+5
~
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Input digital filter (4 digits BCD)
1st unit
Alarm 1 hysteresis
(4 digits BCD)
1st unit
Alarm 2 hysteresis
(4 digits BCD)
1st unit
Alarm 3 hysteresis
(4 digits BCD)
1st unit
Input shift upper limit (4 digits BCD)
1st unit
8th unit (max.)
Data
Number of units
×
6 + 1
0000 to 9999
0001 to 9999
0001 to 9999
0001 to 9999
+6 1st unit
Input shift lower limit (4 digits BCD)
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
+48
(max.)
•
•
•
8th unit
Input shift lower limit (4 digits BCD)
A999 to 9999
F indicates a negative value and A indicates –1.
171
E5
@K Digital Controller Read Protocol
Appendix C
General-purpose Read (Sequence No. 023)
Reads the specified parameter and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
Number of send data words
(Undefined)
Unit No.
(Undefined)
Parameter No.
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Parameter No. (2 digits BCD)
0003 (fixed)
Data
00 to 31
Refer to the manual for the E5 @ K.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Read data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Read data (4 digits BCD)
0002
Data
A999 to 9999
F indicates a negative value and A indicates –1.
Note To read parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No.
075) in advance.
172
Appendix D
E5
@
K Digital Controller Write Protocol
The E5 @ K Digital Controller Write Protocol writes and controls various settings in remote mode for the Controller connected to the Serial Communications Board via RS-232C or RS-485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The following table shows the structure of the E5
@
K Digital Controller Write Protocol.
Sequence
No.
050
051
052
058
059
060
061
062
063
064
065
066
067
068
069
070
053
054
055
056
057
071
072
073
074
075
076
Communications sequence name
Function
Write set point
Write alarm value
Writes the set point.
Writes alarm value 1, 2.
Write proportional band, integral time, and derivative time
Write cooling coefficient
Writes the proportional band, integral time, and derivative time.
Writes the cooling coefficient.
Write dead band Writes the dead band.
Write manual reset value Writes the manual reset value.
Write hysteresis
Write control period
Writes the hysteresis (heating, cooling)
Writes the control period (heating, cooling)
Write SP ramp time units and set value
Writes the SP ramp time unit and SP ramp set value.
Write LBA detection time Writes the LBA detection time.
Write MV at stop time and
PV error
Write MV limits
Write input digital filter
Write alarm hysteresis
Writes the MV at stop and the MV at PC error.
Writes the MV limits.
Writes the input digital filter.
Writes alarm 1, 2 hysteresis.
Write input shift values
Write level 0 parameters
Writes the input shift values.
Writes parameters in level 0.
Write level 1 parameters 1 Writes parameters in level 1.
Write level 1 parameters 2 Writes parameters in level 1.
Write level 2 parameters 1 Writes parameters in level 2.
Write level 2 parameters 2 Writes parameters in level 2.
General-purpose write
Switch to level 0 (software reset)
Writes the value of the specified parameter.
Switches the setting level to level 0.
Run/stop
Remote/local
Initiates Run or Stop.
Switches the mode to remote or local mode.
Execute/cancel AT
Switch to level 1
Software reset
Executes or cancels AT.
Switches the setting level to level 1.
Resets the E5 @ K.
Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Note Ladder Interface Settings
YES:
User settings are required for the 2nd or 3rd operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 2nd operand (S).
Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D).
173
E5
@K Digital Controller Write Protocol
Appendix D
Connections
The connections are the same as that for the E5 @ K Digital Controller Read Protocol.
Write Set Point (Sequence No. 050)
Writes the set point.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
set point
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Set point (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
Data
00 to 31
Set point lower limit to upper limit
Write Alarm Value (Sequence No. 051)
Writes alarm value 1 and alarm value 2.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
Alarm value 1
Alarm value 2
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Alarm value 1 (4 digits BCD)
Alarm value 2 (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0004 (fixed)
00 to 31
0000 to 999
0000 to 9999
Data
Write Proportional Band, Integral Time, and Derivative Time
(Sequence No. 052)
Writes the proportional band, integral time, and derivative time.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
Number of send data words
(Undefined)
Unit No.
Proportional band
Integral time
Derivative time
Data
+1
+2
+3
+4
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Proportional band (4 digits BCD)
Integral time (4 digits BCD)
Derivative time (4 digits BCD)
0005 (fixed)
00 to 31
0001 to 9999
0000 to 3999
0000 to 3999
174
E5
@K Digital Controller Write Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Cooling Coefficient (Sequence No. 053)
Writes the cooling coefficient.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
Cooling coefficient
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Cooling coefficient (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 31
0001 to 9999
Write Dead Band (Sequence No. 054)
Writes the dead band.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Dead band
Unit No.
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Dead band (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 31
0000 to 9999
Write Manual Reset Value (Sequence No. 055)
Writes the manual reset value.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Manual reset value
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Manual reset value (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 31
0000 to 1000
Data
Data
Data
Appendix D
175
E5
@K Digital Controller Write Protocol
Appendix D
Write Hysteresis (Sequence No. 056)
Writes the hysteresis for heating and for cooling.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Hysteresis (heating)
Hysteresis (cooling)
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Hysteresis (heating)
(4 digits BCD)
Hysteresis (cooling)
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Control Period (Sequence No. 057)
Writes the control period for heating and for cooling.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
Control period (heating)
Control period (cooling)
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Control period (heating)
(4 digits BCD)
Control period (cooling)
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0004 (fixed)
00 to 31
0001 to 9999
0001 to 9999
0004 (fixed)
00 to 31
0001 to 0099
0001 to 0099
Data
Data
Write SP Ramp Time Unit and Set Value (Sequence No. 058)
Writes the SP ramp time unit and SP ramp set value.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
SP ramp time unit
SP ramp set value
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
SP ramp time unit (4 digits BCD)
+3 SP ramp set value (4 digits BCD)
0004 (fixed)
00 to 31
0000:Minutes
0001:Hours
0000 to 9999
176
E5
@K Digital Controller Write Protocol
Appendix D
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write LBA Detection Time (Sequence No. 059)
Writes the LBA detection time.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
LBA detection time
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
LBA detection time (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 31
0000 to 9999
Data
Write MV at Stop Time and at PV Error (Sequence No. 060)
Writes the MV at stop time and the MV at PV error.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
MV at stop time
MV at PV error
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
MV at stop time (4 digits BCD)
MV at PV error (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0004 (fixed)
00 to 31
0000 to 1050
0000 to 1050
Data
Write MV Limits (Sequence No. 061)
Writes the MV upper limit, MV lower limit, and MV change rate limit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+4
Number of send data words
(Undefined)
MV upper limit
Unit No.
MV lower limit
MV change rate limit
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
MV upper limit (4 digits BCD)
+3
+4
MV lower limit (4 digits BCD)
MV change rate limit
(4 digits BCD)
0005 (fixed)
Data
00 to 31
MV lower limit +1 to 1050
Heating/cooling control time: 0000 to 1050
0000 to MV upper limit –1
0000 to 1000
177
E5
@K Digital Controller Write Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Digital Filter (Sequence No. 062)
Writes the input digital filter.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
Input digital filter
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Input digital filter (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 31
0000 to 9999
Write Alarm Hysteresis (Sequence No. 063)
Writes the alarm 1 hysteresis and alarm 2 hysteresis.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
Alarm 1 hysteresis
Alarm 2 hysteresis
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Alarm 1 hysteresis
(4 digits BCD)
Alarm 2 hysteresis
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0004 (fixed)
00 to 31
0001 to 9999
0001 to 9999
Write Input Shift Value (Sequence No. 064)
Writes the input shift upper limit and input shift lower limit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
Input shift upper limit
Input shift lower limit
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Input shift upper limit (4 digits BCD)
Input shift lower limit (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0004 (fixed)
00 to 31
0000 to 9999
0000 to 9999
Data
Data
Data
Appendix D
178
E5
@K Digital Controller Write Protocol
Appendix D
Write Level 0 Parameters (Sequence No. 065)
Writes parameters (set points) in level 0 to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+16
~
+17
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Set point
Unit No.
Set point
(Undefined)
Set point
Unit No.
~
1st unit
2nd unit
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Data
Number of units
×
2 + 2
0001 to 0008
00 to 31
+3
+17
(max.)
Unit No. (2 digits BCD)
1st unit
Set point (4 digits BCD)
•
•
•
8th unit
Set point (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Set point lower limit to upper limit
Set point lower limit to upper limit
179
E5
@K Digital Controller Write Protocol
Appendix D
Write Level 1 Parameters 1 (Sequence No. 066)
Writes parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and derivative time) to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
Number of send data words
Number of units
(Undefined)
Unit No.
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
1st unit
~ ~
+51
+52
+53
+54
+55
+56
+57
(Undefined)
Unit No.
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+4
+5
Unit No. (2 digits BCD)
1st unit
Alarm value 1 (4 digits BCD)
1st unit
Alarm value 2 (4 digits BCD)
1st unit
Alarm value 3 (4 digits BCD)
+6
+7
+8
+57
(max.)
1st unit
Proportional band (4 digits BCD)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
•
•
•
8th unit
Derivative time (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
7 + 2
0001 to 0008
00 to 31
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
0001 to 9999
0000 to 3999
0000 to 3999
0000 to 3999
180
E5
@K Digital Controller Write Protocol
Appendix D
Write Level 1 Parameter 2 (Sequence No. 067)
Writes parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+58
+59
+60
+61
+62
+63
~
+64
+65
+7
+8
+9
+4
+5
+6
+0
+1
+2
+3
Number of send data words
Number of units
(Undefined) Unit No.
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
(Undefined) Unit No.
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
~
1st unit
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+4
+5
+6
+7
+8
+9
+65
(max.)
Unit No. (2 digits BCD)
1st unit
Cooling coefficient (4 digits BCD)
1st unit
Dead band (4 digits BCD)
1st unit
Manual reset value (4 digits BCD)
1st unit
Hysteresis (heating)
(4 digits BCD)
1st unit
Hysteresis (cooling)
(4 digits BCD)
1st unit
Control period (heating)
(4 digits BCD)
1st unit
Control period (cooling)
(4 digits BCD)
•
•
•
8th unit
Control period (cooling)
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
8 + 2
0001 to 0008
00 to 31
0001 to 9999
0000 to 9999
0000 to 1000
0001 to 9999
0001 to 9999
0001 to 0099
0001 to 0099
0001 to 0099
181
E5
@K Digital Controller Write Protocol
Appendix D
Write Level 2 Parameters 1 (Sequence No. 068)
Writes parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop time, MV at PV error, MV upper limit, MV lower limit, and MV change rate limit) to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+65
~
+66
+67
+68
+69
+70
+71
+72
+73
+4
+5
+6
+7
+8
+9
+10
+0
+1
+2
+3
Number of send data words
(Undefined)
Number of units
Unit No.
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
(Undefined)
SP ramp time unit
SP ramp set value
Unit No.
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
~
1st unit
8th unit (max.)
Offset
+0
+1
+3
Number of units (4 digits BCD) unit
Unit No. (2 digits BCD)
1st unit
SP ramp time unit (4 digits BCD)
+4
+5
+6
+7
1st unit
SP ramp set value (4 digits BCD)
1st unit
LBA detection time (4 digits BCD)
1st unit
MV at stop (4 digits BCD)
1st unit
MV at PV error (4 digits BCD)
+8
Contents (data format)
Number of send data words
(4 digits BCD)
+9
+10
+73
(max.)
1st unit
MV upper limit (4 digits BCD)
1st unit
MV lower limit (4 digits BCD)
1st unit
MV change rate limit (4 digits BCD)
•
•
•
8th unit
MV change rate limit
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
9 + 2
0001 to 0008
00 to 31
0000 to 0001
0000 to 9999
0000 to 9999
0000 to 1050
0000 to 1050
MV lower limit +1 to 1050
0000 to MV upper limit –1
0000 to 1000
0000 to 1000
182
E5
@K Digital Controller Write Protocol
Appendix D
Write Level 2 Parameters 2 (Sequence No. 069)
Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+51
+52
+53
+54
+55
+56
+57
~
+5
+6
+7
+8
+0
+1
+2
+3
+4
Number of send data words
Number of units
(Undefined)
Input digital filter
Unit No.
alarm 1 hysteresis alarm 2 hysteresis alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
(Undefined)
Input digital filter alarm 1 hysteresis
Unit No.
alarm 2 hysteresis alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
~
1st unit
8th unit (max.)
+0
Offset
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Data
Number of units
×
7 + 2
0001 to 0008
00 to 31
+3
+4
+5
+6
+7
+8
+57
(max.)
Unit No. (2 digits BCD)
1st unit
Input digital filter (4 digits BCD)
1st unit
Alarm 1 hysteresis
(4 digits BCD)
1st unit
Alarm 2 hysteresis
(4 digits BCD)
1st unit
Alarm 3 hysteresis
(4 digits BCD)
1st unit
Input shift upper limit (4 digits BCD)
1st unit
Input shift lower limit (4 digits BCD)
•
•
•
8th unit
Input shift lower limit (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000 to 9999
0001 to 9999
0001 to 9999
0001 to 0099
000 to 9999
000 to 9999
000 to 9999
183
E5
@K Digital Controller Write Protocol
Appendix D
General-purpose Write (Sequence No. 070)
Writes the specified parameter.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
(Undefined)
Parameter No.
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Parameter No. (2 digits BCD)
Write data (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0004 (fixed)
Data
00 to 31
Refer to the manual of E5
@
K.
0000 to 9999
Note To write parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No.
075) in advance.
Switch to Level 0 (Software Reset) (Sequence No. 071)
Resets the operation of the E5 @ K and waits until communications are enabled. This sequence can be executed for multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units
(4 digits BCD)
+2 to 9 Unit No.
(2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Number of units + 2
Data
0001 to 0008
00 to 31
Note When this sequence is executed, a software reset command is issued and the operation of the E5 @ K is reset (equivalent to turning on the power supply). About five seconds will be required until communications are enabled.
184
E5
@K Digital Controller Write Protocol
Appendix D
Run/Stop (Sequence No. 072)
Switches the mode to Run or Stop according to the command code. This sequence can be executed for multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+16
~
+17
Number of send data words
Number of units
(Undefined)
Unit No.
Command code
(Undefined) Unit No.
Command code
(Undefined)
Unit No.
Command code
~
1st unit
2nd unit
8th unit (max.)
+0
Offset
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Data
Number of units
×
2 + 2
0001 to 0008
00 to 31
+3
+17
(max.)
Unit No. (2 digits BCD)
1st unit
Command code (4 digits BCD)
•
•
•
8th unit
Command code (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000: Run
0001: Stop
0000: Run
0001: Stop
Remote/Local (Sequence No. 073)
Switches to remote operation or local operation according to the command mode. This sequence can be executed for multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+16
+17
~
Number of send data words
Number of units
(Undefined) Unit No.
Command code
(Undefined)
Command code
Unit No.
(Undefined)
Unit No.
Command code
~
1st unit
2nd unit
8th unit (max.)
185
E5
@K Digital Controller Write Protocol
Appendix D
+0
Offset Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Data
Number of units
×
2 + 2
+1 0001 to 0008
00 to 31
+3
+17
(max.)
Unit No. (2 digits BCD)
1st unit
Command code (4 digits BCD)
•
•
•
8th unit
Command code (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000: Local
0001: Remote
0000: Local
0001: Remote
Execute/Cancel AT (Sequence No. 074)
Executes or cancels AT (autotuning) according to the command code. This sequence can be executed for multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+16
~
+17
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Command code
Unit No.
Command code
(Undefined) Unit No.
Command code
~
1st unit
2nd unit
8th unit (max.)
+0
Offset
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Data
Number of units
×
2 + 2
0001 to 0008
00 to 31
+3
Unit No. (2 digits BCD)
1st unit
Command code (4 digits BCD)
0000: Stop
0001: Execute AT 40%
0002: Execute AT 100%
+17
(max.)
•
•
•
8th unit
Command code (4 digits BCD)
0000: Stop
0001: Execute AT 40%
0002: Execute AT 100%
Receive Data Word Allocation (3rd Operand of PMCR)
None.
186
E5
@K Digital Controller Write Protocol
Appendix D
Switch to Level 1 (Sequence No. 075)
Switches the setting level to level 1 (setup mode, extended mode). This sequence can be executed for multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Number of units + 2
Data
0001 to 0008
00 to 31
Software Reset (Sequence No. 076)
Resets the operation of the E5 @ K (equivalent to turning on the power supply). This sequence can be executed for multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of units (4 digits BCD)
+2 to 9 Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Number of units + 2
Data
0001 to 0008
00 to 31
Note Communications with the E5
@
K are disabled for about five seconds after this sequence is executed.
187
Appendix E
E5ZE Temperature Controller Read Protocol
The E5ZE Temperature Controller Read Protocol reads and controls various parameters in remote mode for the Temperature Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable.
Note All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks.
Structure of the Protocol
The following table shows the structure of the E5ZE Temperature Controller Read Protocol
Sequence
No.
100
101
102
103
104
112
113
114
115
116
117
118
105
106
107
108
109
110
111
119
120
121
122
123
Communications sequence name
Function
Read set point
Read process value
Read output value
Read set point, process value, and output value
Read proportional band, integral time, and derivative time
Reads the set points.
Reads the process values.
Reads the output values.
Reads the set points, process values, and output values.
Read control period
Read output mode
Read alarm mode
Read alarm temperature
Read hysteresis
Read operation status
Read error status
Reads the proportional bands, integral times, and derivative times.
Reads the control periods.
Reads the output modes.
Reads the alarm modes.
Reads the alarm temperatures.
Reads the hysteresis.
Reads the operation status.
Reads the error status.
Read setting unit
Read input shift value
Read manual reset value
Read ramp value
Read present set point
Read output value limits
Read output value change rate limit
Read HB alarm and HS alarm valid channels
Read heater burnout/SSR failure detection currents
Read heater current and SSR leakage current
Read dead band/overlap band
Read cooling coefficient
Reads the setting units.
Reads the input shift values.
Reads the manual reset values.
Reads the ramp values.
Reads the present set points.
Reads the output value limits.
Reads the output value change rate limits.
Reads the HB alarm and HS alarm valid channels.
Reads the heater burnout/SSR failure detection currents.
Reads the heater currents and
SSR leakage currents.
Reads the dead bands and overlap bands.
Reads the cooling coefficients.
Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd or 3rd operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 2nd operand (S).
Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D).
189
E5ZE Temperature Controller Read Protocol
Connections
This section shows connections for using the E5ZE Temperature Controller Read Protocol.
RS-232C Connections
CQM1H
E5ZE
Serial Commu nications Board
RS-232C port
→
RS-232C
Appendix E
Pin
No.
Signal abbreviation
Signal name Abbreviation
Signal ground or common return line
Send data
Receive data
Request to send
Clear to send
SG
SD
RD
RS
CS
Data set ready DR
Data terminal ready ER
Disabled (Do not connect.)
NC
Serial Communications
Board
RS-232C: D-sub
9-pin female
Signal name
Pin
No.
Shielded cable
E5ZE
RS-232C: D-sub
9-pin female
Pin
No.
Signal name
LT1181CS or equivalent
–
Signal direction
7
Pin No.
Output
Input
Output
Input
Input
Output
–
2
3
4
5
6
20
1, 8 to 19,
21 to 25
Note 1.
The maximum communications cable length is 15 m. Use a shielded twisted-pair cable (AWG28 or greater) for the cable.
2.
Use a 25-pin D-sub Plug (OMRON XM2A-2501).
3.
Use XM2S-2511 Hood (OMRON) or an equivalent.
190
E5ZE Temperature Controller Read Protocol
RS422/485 Connections
• RS-485
Appendix E
1
2
3
4
5
Pin No.
Signal name
Disabled (Do not connect.) –
Disabled (Do not connect.) –
Signal ground SG
Abbreviation
Terminal B (+ side)
Terminal A (– side)
B
A
–
–
Signal direction
–
I/O
I/O
Serial Communications
Board
RS-485: D-sub
9-pin female
Signal name
Pin No.
Turn off the communications switch to disconnect terminating resistance.
SN751177N or equivalent
E5ZE
RS-485: Terminals
Terminating resistance
240
Ω
Terminal
Signal name
Terminating resistance
Shielded cable
Shielded cable
E5ZE
RS-485: Terminals
Terminal
Signal name
Terminating resistance
Note Terminal block pins 1 and 2 cannot be connected. If these blocks are used, operation of the E5ZE may fail.
191
E5ZE Temperature Controller Read Protocol
• RS-422A
Appendix E
Pin No.
Signal name Abbreviation
1
2
3
4
5
Receive data B
Receive data A
Signal ground
Send data B
Send data A
RDB
RDA
SG
SDB
SDA
Serial Communications
Board
Terminating resistance
RS-422A: D-sub
9-pin female
Signal name
Pin No.
Turn off the communications switch to disconnect terminating resistance.
E5ZE
RS-422A:
Terminals
Terminating resistance
Terminal
Signal name
SN751177N or equivalent
Input
Input
–
Signal direction
Output
Output
Terminating resistance
Shielded cable
Terminating resistance
Shielded cable
Terminal block
Terminal
Signal name
Terminating resistance
240
Ω
Terminating resistance
192
E5ZE Temperature Controller Read Protocol
Appendix E
Switch Settings
This section shows the switch settings for using the E5ZE Temperature Controller Read Protocol.
Communications Parameter DIP Switch
Pins 3 and 4: Terminating resistance
Pins 1 and 2: RS-422A/RS-485
Unit Number Switch
Pins
3 and 4
Factory defaults: All OFF
Parameter
Terminating resistance
ON
ON
ON
RS-422A
OFF
OFF
OFF
1 and 2 RS-422A or RS-485
OFF
OFF
OFF
ON
OFF
OFF
RS-485
ON
ON
Baud Rate DIP Switch
Setting
0 1 2 3 4 5 6 7 8 9 A B C D E F
Unit No. 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F
▲
Factory defaults
Baud rate
(bps)
Pins 1 and 2
ON
1 2 3 4 5 6 7 8
Factory default: 9,600 bps
(pin 1 ON, pin 2 OFF)
19,200 9,600
ON
1 2
ON
1 2
4,800
ON
1 2
2,400
ON
1 2
193
E5ZE Temperature Controller Read Protocol
Appendix E
Read Set Point (Sequence No. 100)
Reads the set points and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+15
+16
~
Number of receive data words
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
~
0002 (fixed)
00 to 0F
Channel 0
Channel 7
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
0017
Data
Data
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
+15
+16
Set point (leftmost 1 digit) (1 digit BCD)
•
•
•
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Set point (leftmost 1 digit) (1 digit BCD)
Varies according to the temperature sensor type. Refer the manual for the E5ZE.
F indicates a negative value.
Read Process Value (Sequence No. 101)
Reads the process values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
Number of receive data words
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
+15
+16
~
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
~
0002 (fixed)
00 to 0F
Channel 0
Channel 1
Channel 7
Data
194
E5ZE Temperature Controller Read Protocol
Appendix E
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
Data
0017
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
+15
+16
Process value (leftmost 1 digit)
(1 digit BCD)
•
•
•
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
Read Output Values (Sequence No. 102)
Reads the output values of the control outputs and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
Number of receive data words
Output value
Cooling output value
Output value
Cooling output value
+15
~
+16
Output value
Cooling output value
~
0002 (fixed)
00 to 0F
Channel 0
Channel 1
Channel 7
Data
Data Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Output value (4 digits BCD)
+3
+4
+15
+16
Cooling output value (4 digits BCD)
Channel 1
Output value (4 digits BCD)
Channel 1
Cooling output value (4 digits BCD)
•
•
•
Channel 7
Output value (4 digits BCD)
Channel 7
Cooling output value (4 digits BCD)
0017
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
195
E5ZE Temperature Controller Read Protocol
Appendix E
Read Set Point, Process Value, and Output Value
(Sequence No. 103)
Reads the set points, process values, and output values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+36
~
+37
+38
+39
+40
Number of receive data words
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Output value
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Output value
~
0002 (fixed)
00 to OF
Channel 0
Channel 7
Data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
+3
+4
+36
+37
+38
+39
+40
0041
Data
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Set point (leftmost 1 digit) (1 digit BCD)
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
0000 to 1000
Output value (4 digits BCD)
•
•
•
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Set point (leftmost 1 digit) (1 digit BCD)
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
Channel 0
Output value (4 digits BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
0000 to 1000
196
E5ZE Temperature Controller Read Protocol
Appendix E
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 104)
Reads the proportional bands (constant P), integral times (constant I), and derivative times (Constant D) and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Constant P
Constant I
Constant D
0002 (fixed)
00 to 0F
Channel 0
+22
~
+23
+24
Constant P
Constant I
Constant D
~
Channel 7
Data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Constant P (4 digits BCD)
0025
0000 to 9999
0000 to 3999
0000 to 3999
Data
+3
+22
+2 3
+24
Constant I (4 digits BCD)
Channel 0
Constant D (4 digits BCD)
•
•
•
Channel 7
Constant P (4 digits BCD)
Channel 7
Constant I (4 digits BCD)
Channel 7
Constant D (4 digits BCD)
Read Control Period (Sequence No. 105)
Reads the control periods and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
0000 to 9999
0000 to 3999
0000 to 3999
0002 (fixed)
00 to 0F
Data
197
E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Control period
Cooling control period
Control period
Cooling control period
Control period
Cooling control period
~
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Control period (4 digits BCD)
Channel 0
Channel 1
Channel 7
0017
0001 to 0099
0001 to 0099
+15
+16
Cooling control period
(4 digits BCD)
•
•
•
Channel 7
Control period (4 digits BCD)
Channel 7
Cooling control period
(4 digits BCD)
0001 to 0099
0001 to 0099
Read Output Mode (Sequence No. 106)
Reads the output modes (normal/reverse) and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
(Undefined)
Set code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Set code (2 digits Hex)
0002 (fixed)
00 to 0F
0002
00 to FF
Read Alarm Mode (Sequence No. 107)
Reads the alarm modes and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Data
Data
Data
Appendix E
198
E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
(Undefined)
Alarm 1 set code
(Undefined)
Alarm 2 set code
(Undefined)
Alarm 1 set code
(Undefined)
Alarm 2 set code
(Undefined)
(Undefined)
Alarm 1 set code
Alarm 2 set code
~
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Alarm 1 set code (2 digits Hex)
Channel 0
Channel 1
Channel 7
0017
00 to 0C
00 to 0C
+15
+16
Alarm 2 set code (2 digits Hex)
•
•
•
Channel 7
Alarm 1 set code (2 digits Hex)
Channel 7
Alarm 2 set code (2 digits Hex)
00 to 0C
00 to 0C
Read Alarm Temperatures (Sequence No. 108)
Reads the alarm temperatures and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
Number of receive data words
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
+29
~
Alarm 1 set value (rightmost 4 digits)
~
+30 Alarm 1 set value (rightmost 1 digit)
+31
+32
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
0002 (fixed)
00 to 0F
Channel 0
Channel 7
Data
Data
Appendix E
199
E5ZE Temperature Controller Read Protocol
Appendix E
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
+3
+4
+29
+30
+31
+32
0033
0000 to 9999
Data
F indicates a negative number.
Alarm 1 set value (leftmost 1 digit)
(4 digits BCD)
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 0
Alarm 2 set value (leftmost 1 digit)
(4 digits BCD)
•
•
•
Channel 7
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Alarm 1 set value (leftmost 1 digit)
(4 digits BCD)
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 07
Alarm 2 set value (leftmost 1 digit)
(4 digits BCD)
0000 to 0009
F indicates a negative number.
0000 to 9999
F indicates a negative number.
0000 to 0009
F indicates a negative number.
0000 to 9999
F indicates a negative number.
0000 to 0009
F indicates a negative number.
0000 to 9999
F indicates a negative number.
0000 to 0009
F indicates a negative number.
Read Hysteresis (Sequence No. 109)
Reads the hysteresis and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Hysteresis
Cooling hysteresis
Hysteresis
Cooling hysteresis
Hysteresis
Cooling hysteresis
~
0002 (fixed)
00 to 0F
Channel 0
Channel 1
Channel 7
Data
200
E5ZE Temperature Controller Read Protocol
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Hysteresis (4 digits BCD)
0017
0000 to 0999
0000 to 0999
+15
+16
Cooling hysteresis (4 digits BCD)
•
•
•
Channel 7
Hysteresis (4 digits BCD)
Channel 7
Cooling hysteresis (4 digits BCD)
0000 to 0999
0000 to 0999
Read Operation Status (Sequence No. 110)
Reads the operation status of the E5ZE and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+8
~
Number of receive data words
Status code
Status code
Status code
Channel 0
Channel 1
~
Channel 7
0002 (fixed)
00 to 0F
Data
Data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Status code (4 digits Hex)
0009
0000 to FFFF
Data
0000 to FFFF
+8
Status code (4 digits Hex)
•
•
•
Channel 7
Status code (4 digits Hex)
0000 to FFFF
Read Error Status (Sequence No. 111)
Reads the contents of errors if they have occurred and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Appendix E
201
E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Status code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Status code (4 digits BCD)
Read Setting Unit (Sequence No. 112)
Reads the setting units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Set code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Set code (4 digits BCD)
0009
0000 to FFFF
0002 (fixed)
00 to 0F
0002
0000: unit of 1
0001: unit of 0.1
Read Input Shift Value (Sequence No. 113)
Reads the input shift values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+8
~
Number of receive data words
Input shift value
Input shift value
Input shift value
Channel 0
Channel 1
~
Channel 7
0002 (fixed)
00 to 0F
Data
Data
Data
Data
Appendix E
202
E5ZE Temperature Controller Read Protocol
Appendix E
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Input shift value (4 digits BCD)
0009
Data
0000 to 0999
F indicates a negative number.
0000 to 0999
F indicates a negative number.
+8
Input shift value (4 digits BCD)
•
•
•
Channel 7
Input shift value (4 digits BCD)
0000 to 0999
F indicates a negative number.
Read Manual Reset Value (Sequence No. 114)
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Manual reset value
Manual reset value
~
+8
Manual reset value
~
Channel 0
Channel 1
Channel 7
0002 (fixed)
00 to 0F
Data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Manual reset value
(4 digits BCD)
0009
0000 to 1000
Data
0000 to 1000
+8
Manual reset value
(4 digits BCD)
Channel 7
Manual reset value
(4 digits BCD)
•
•
•
Read Ramp Value (Sequence No. 115)
Reads the ramp values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
0000 to 1000
0002 (fixed)
00 to 0F
Data
203
E5ZE Temperature Controller Read Protocol
Appendix E
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
Number of receive data words
(Undefined) Ramp value
Time unit
(Undefined)
Time unit
(Undefined)
Ramp value
(Undefined)
+15
+16
~
(Undefined)
Time unit
Ramp value
(Undefined)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Ramp value (3 digits BCD)
~
0017
000 to 999
Channel 0
Channel 1
Channel 7
Data
S: Seconds; M: Minutes; H: Hours
+15
+16
Time unit (one ASCII character)
•
•
•
Channel 7
Ramp value (3 digits BCD)
Channel 7
Time unit (one ASCII character)
000 to 999
S: Seconds; M: Minutes; H: Hours
Read Present Set Point (Sequence No. 116)
Reads the present set points during ramp operation and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+15
~
+16
Number of receive data words
Present set point (rightmost 4 digits)
Present set point (leftmost 1 digit)
Present set point (rightmost 4 digits)
Present set point (leftmost 1 digit)
~
0002 (fixed)
00 to 0F
Channel 0
Channel 7
Data
204
E5ZE Temperature Controller Read Protocol
Appendix E
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Present set point (rightmost 4 digits)
(4 digits BCD)
Data
0017
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
+15
+16
Present set point (leftmost 1 digit)
(1 digit BCD)
•
•
•
Channel 7
Present set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Present set point (leftmost 1 digit)
(1 digit BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
Read Output Value Limit (Sequence No. 117)
Reads the output value limits and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Output value lower limit
+2
+3
Output value upper limit
Cooling control output value lower limit
+4
Cooling control output value upper limit
+29
+30
~
Output value lower limit
Output value upper limit
+31
Cooling control output value lower limit
+32
Cooling control output value upper limit
~
0002 (fixed)
00 to 0F
Channel 0
Channel 7
Data
205
E5ZE Temperature Controller Read Protocol
Appendix E
Offset
+0
+1
+3
+4
+31
+32
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Output value lower limit
(4 digits BCD)
0033
0000 to 1000
0000 to 1000
Output value upper limit
(4 digits BCD)
Channel 0
Cooling control output value upper limit
(4 digits BCD)
Channel 0
Cooling control output value upper limit
(4 digits BCD)
•
•
•
Channel 7
Cooling control output value upper limit
(4 digits BCD)
Channel 7
Cooling control output value upper limit
(4 digits BCD)
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0009
0000 to 1000
Data
Read Output Value Change Rate Limit (Sequence No. 118)
Reads the output value change rate limits and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Output value change rate limit
Output value change rate limit
+8
~
Output value change rate limit
Channel 0
Channel 1
~
Channel 7
0002 (fixed)
00 to 0F
Data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Output value change rate limit
(4 digits BCD)
Data
0000 to 1000
+8
Output value change rate limit
(4 digits BCD)
•
•
•
Channel 7
Output value change rate limit
(4 digits BCD)
0000 to 1000
206
E5ZE Temperature Controller Read Protocol
Appendix E
Read HB Alarm and HS Alarm Valid Channels
(Sequence No. 119)
Reads the valid or invalid channels for HB alarms and HS alarms and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
(Undefined) Set code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Set code (2 digits Hex)
0002 (fixed)
00 to 0F
0009
00 to FF
Data
Read Heater Burnout and SSR Failure Detection Currents
(Sequence No. 120)
Reads the heater burnout and SSR failure detection currents and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Heater burnout detection current
SSR failure detection current
Heater burnout detection current
SSR failure detection current
Heater burnout detection current
SSR failure detection current
~
0002 (fixed)
00 to 0F
Channel 0
Channel 1
Channel 7
Data
207
E5ZE Temperature Controller Read Protocol
Appendix E
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Heater burnout detection current
(4 digits BCD)
0017
0000 to 0500
Data
0000 to 0500
+15
+16
SSR failure detection current
(4 digits BCD)
•
•
•
Channel 7
Heater burnout detection current
(4 digits BCD)
Channel 7
SSR failure detection current
(4 digits BCD)
0000 to 0500
0000 to 0500
Read Heater Current and SSR Leakage Current
(Sequence No.121)
Reads the heater currents and SSR leakage currents and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Heater current
SSR leakage current
Heater current
SSR leakage current
+4
+15
+16
~
Heater current
SSR leakage current
~
0002 (fixed)
00 to 0F
Channel 0
Channel 1
Channel 7
Data
Data Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Heater current
(4 digits BCD)
+15
+16
SSR leakage current
(4 digits BCD)
Channel 7
Heater current
(4 digits BCD)
Channel 7
SSR leakage current
(4 digits BCD)
•
•
•
0017
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
208
E5ZE Temperature Controller Read Protocol
Appendix E
Note The read data will be 0000 for all channels for which HB and HS alarms are not enabled and for all channels for which control is stopped.
Read Dead Band/Overlap Band (Sequence No. 122)
Reads the dead bands/overlap bands and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+8
~
Number of receive data words
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Channel 0
Channel 1
~
Channel 7
0002 (fixed)
00 to 0F
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Dead band/overlap band
(4 digits BCD)
0009
Data
Data
0000 to 0999
F indicates a number.
0000 to 0999
F indicates a number.
+8
Dead band/overlap band
(4 digits BCD)
•
•
•
Channel 7
Dead band/overlap band
(4 digits BCD)
0000 to 0999
F indicates a number.
Read Cooling Coefficient (Sequence No. 123)
Reads the cooling coefficients and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
209
E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+8
~
Number of receive data words
Cooling coefficient
Cooling coefficient
Cooling coefficient
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Channel 0
Cooling coefficient (4 digits BCD)
0009
0000 to 0100
0000 to 0100
+8
Cooling coefficient (4 digits BCD)
•
•
•
Channel 7
Cooling coefficient (4 digits BCD)
0000 to 0100
Data
Appendix E
210
Appendix F
E5ZE Temperature Controller Write Protocol
The E5ZE Temperature Controller Write Protocol writes and controls various settings in remote mode for the
Temperature Controller connected via a RS-232C or RS-422A/485 cable from the PC via the Serial Communications Board.
Note 1.
Negative values cannot be written. All values must be set as unsigned BCD.
2.
All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks.
Structure of the Protocol
The following table shows the structure of the E5ZE Temperature Controller Write Protocol.
Sequence
No.
150
151
152
157
164
165
166
167
168
169
170
158
159
160
161
162
163
153
154
155
156
171
172
173
174
175
176
Communications sequence name Function
Write set point (setting unit 1)
Write set point (setting unit 0.1)
Write proportional band, integral time, and derivative time
Write control period
Writes the set points using a setting unit of 1.
Writes the set points using a setting unit of 0.1.
Writes the proportional bands, integral times, and derivative times.
Writes the control periods.
Write output mode
Write alarm mode
Writes the output modes.
Writes the alarm modes.
Write alarm temperature (setting unit 1) Writes the alarm temperatures using a setting unit of 1.
Write alarm temperature (setting unit 0.1) Writes the alarm temperatures using a setting unit of 0.1.
Write hysteresis
Start autotuning
Cancel autotuning
Write setting unit
Write input shift value
Write manual reset value
Writes the hysteresis.
Starts autotuning.
Cancels autotuning.
Writes the setting units.
Writes the input shift values.
Writes the manual reset values.
Write ramp value
Write manual output value
Write output value limit
Write output value change rate limit
Save settings
Initialize settings
Write HB alarm and HS alarm valid channels
Write heater burnout and SSR failure detection currents
Write dead band/overlap band
Write cooling coefficient
Start control
Stop operation or control
Start manual operation
Writes the ramp values.
Writes the manual output values.
Writes the output value limits.
Write output value change rate limits.
Saves settings.
Initializes settings.
Writes the HB alarm and HS alarm valid channels.
Writes the heater burnout and SSR failure detection currents.
Writes the dead bands/overlap bands.
Writes the cooling coefficients.
Starts temperature control.
Stops temperature control or manual operation.
Starts manual operation.
Ladder interface
Send word allocation
Receive word allocation
Yes No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Note Ladder Interface Settings
YES:
User settings are required for the 2nd or 3rd operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 2nd operand (S).
Receive word allocation: Set a dummy word (e.g., DM0000) address for the 3rd operand (D).
211
E5ZE Temperature Controller Write Protocol
Appendix F
Connections
The connections are the same as that for the E5ZE Temperature Controller Read Protocol.
Write Set Point (Setting Unit 1) (Sequence No. 150)
Writes the set points using a setting unit of 1 (4 digits).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
~
Number of send data words
(Undefined)
Set point
Unit No.
(Undefined)
Set point
(Undefined)
+16
+17
Set point
(Undefined)
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
0018 (fixed)
Data
00 to 0F
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Set point
(4 digits BCD)
+16 Channel 7
Set point
(4 digits BCD)
Not used +17
Receive Data Word Allocation (3rd Operand of PMCR)
None.
•
•
•
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
---
Note When the setting unit for the set point is 0.1 (5 digits), use Write Set Point (Setting Unit 0.1), Sequence
No.151.
212
E5ZE Temperature Controller Write Protocol
Appendix F
Write Set Point (Setting Unit 0.1) (Sequence No. 151)
Writes the set points using a setting unit of 0.1 (5 digits).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
~
Number of send data words
(Undefined)
Unit No.
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
+16
+17
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
0018 (fixed)
Data
00 to 0F
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
+16
+17
Set point (leftmost 1 digit) (1 digit BCD)
•
•
•
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Set point (rightmost 1 digit)
(1 digit BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note When the setting unit for the set point is 1 (4 digits), use Write Set Point (Setting Unit 1), Sequence
No.150.
213
E5ZE Temperature Controller Write Protocol
Appendix F
Write Proportional Band, Integral Time, and Derivative Time
(Sequence No. 152)
Writes the proportional bands (constant P), integral times (constant I), and derivative times (constant D).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Constant P
Unit No.
Constant I
Constant D
Channel 0
+23
~
+24
+25
Constant P
Constant I
Constant D
~
Channel 7
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Constant P (4 digits BCD)
0026 (fixed)
00 to 0F
0000 to 9999
0000 to 3999
+4
+23
+24
+25
Constant I (4 digits BCD)
Channel 0
Constant D (4 digits BCD)
•
•
•
Channel 7
Constant P (4 digits BCD)
Channel 7
Constant I (4 digits BCD)
Channel 7
Constant D (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000 to 3999
0000 to 9999
0000 to 3999
0000 to 3999
214
E5ZE Temperature Controller Write Protocol
Write Control Period (Sequence No. 153)
Writes the control periods and cooling control periods.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Control period
Unit No.
Cooling control period
Control period
Cooling control period
+16
+17
~
Control period
Cooling control period
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Control period (4 digits BCD)
0018 (fixed)
00 to 0F
0001 to 0099
0001 to 0099
+4
Cooling control period
(4 digits BCD)
Channel 1
Control period (4 digits BCD)
0001 to 0099
0001 to 0099
+16
+17
Cooling control period
(4 digits BCD)
•
•
•
Channel 7
Control period (4 digits BCD)
Channel 7
Cooling control period
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0001 to 0099
0001 to 0099
Data
Appendix F
215
E5ZE Temperature Controller Write Protocol
Write Output Mode (Sequence No. 154)
Writes the output mode (normal/reverse).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
(Undefined)
Write code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Write code (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 0F
00 to FF
Write Alarm Mode (Sequence No. 155)
Writes the alarm modes for alarm 1 and alarm 2.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+16
~
+17
Number of send data words
(Undefined)
Unit No.
(Undefined)
Alarm 1 set code
(Undefined)
(Undefined)
(Undefined)
Alarm 2 set code
Alarm 1 set code
Alarm 2 set code
(Undefined)
(Undefined)
Alarm 1 set code
Alarm 2 set code
~
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Alarm 1 set code (2 digits Hex)
Channel 0
Channel 1
Channel 7
0018 (fixed)
00 to 0F
00 to 0C
00 to 0C
+4
Alarm 2 set code (2 digits Hex)
Channel 1
Alarm 1 set code (2 digits Hex)
00 to 0C
00 to 0C
+16
+17
Alarm 2 set code (2 digits Hex)
•
•
•
Channel 7
Alarm 1 set code (2 digits Hex)
Channel 7
Alarm 2 set code (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
00 to 0C
00 to 0C
Data
Data
Appendix F
216
E5ZE Temperature Controller Write Protocol
+4
+5
Channel 0
Alarm 2 set value
(4 digits BCD)
Not used
+32 Channel 7
Alarm 2 set value
(4 digits BCD)
Not used +33
Receive Data Word Allocation (3rd Operand of PMCR)
None.
•
•
•
0000 to 9999
Appendix F
Write Alarm Temperature (Setting Unit 1) (Sequence No. 156)
Writes the alarm temperatures using a setting unit of 1 (4 digits)
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+30
~
+31
+32
+33
Number of send data words
(Undefined)
Unit No.
Alarm 1 set value
(Undefined)
Alarm 2 set value
(Undefined)
Alarm 1 set value
(Undefined)
Alarm 2 set value
(Undefined)
~
Channel 0
Channel 7
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Alarm 1 set value
(4 digits BCD)
0034 (fixed)
00 to 0F
0000 to 9999
0000 to 9999
217
E5ZE Temperature Controller Write Protocol
Appendix F
Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157)
Writes the alarm temperatures using a setting unit of 0.1 (5 digits)
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+3
+4
+5
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
+30
~
Alarm 1 set value (rightmost 4 digits)
~
+31
Alarm 1 set value (leftmost 1 digit)
+32
+33
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
Channel 0
Channel 7
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
0034 (fixed)
00 to 0F
0000 to 9999
0000 to 0009
+4
+5
+32
+33
Alarm 1 set value (leftmost 1 digits)
(4 digits BCD)
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 0
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
•
•
•
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000 to 9999
0000 to 0009
0000 to 9999
0000 to 0009
218
E5ZE Temperature Controller Write Protocol
Write Hysteresis (Sequence No. 158)
Writes the hysteresis for control outputs for ON/OFF control.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Hysteresis
Unit No.
Cooling hysteresis
Hysteresis
Cooling hysteresis
+5
+16
~
+17
Hysteresis
Cooling hysteresis
~
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Hysteresis (4 digits BCD)
Channel 0
Channel 1
Channel 7
0018 (fixed)
00 to 0F
0000 to 0999
0000 to 0999
+4
Cooling hysteresis (4 digits BCD)
Channel 1
Hysteresis (4 digits BCD)
0000 to 0999
0000 to 0999
+16
+17
Cooling hysteresis (4 digits BCD)
•
•
•
Channel 7
Hysteresis (4 digits BCD)
Channel 7
Cooling hysteresis (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000 to 0999
0000 to 0999
Start Autotuning (Sequence No. 159)
Starts autotuning (AT).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
(Undefined)
Channel
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel (Channel) No. (1 digit BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 0F
0 to 7
Data
Data
Appendix F
219
E5ZE Temperature Controller Write Protocol
Cancel Autotuning (Sequence No. 160)
Cancels Autotuning (AT) for all channels.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 (fixed)
00 to 0F
Write Setting Unit (Sequence No. 161)
Writes the setting unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Write code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Write code (4 digits BCD)
0003 (fixed)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Shift Value (Sequence No. 162)
Writes the input shift values.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
(Undefined)
Unit No.
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
00 to 0F
0000: unit of 1
0001: unit of 0.1
Data
Data
Appendix F
220
E5ZE Temperature Controller Write Protocol
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Input shift value (4 digits BCD)
+4
+8
+9
Input shift value (4 digits BCD)
Channel 2
Input shift value (4 digits BCD)
•
•
•
Channel 6
Input shift value (4 digits BCD)
Channel 7
Input shift value (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0010 (fixed)
00 to 0F
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
Write Manual Reset Value (Sequence No. 163)
Writes the manual reset values.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
(Undefined)
Unit No.
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Manual reset value
(4 digits BCD)
1
Manual reset value
(4 digits BCD)
+4 Channel 2
Manual reset value
(4 digits BCD)
+8
+9
Channel 6
Manual reset value
(4 digits BCD)
Channel 7
Manual reset value
(4 digits BCD)
•
•
•
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
0010 (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Data
Data
Appendix F
221
E5ZE Temperature Controller Write Protocol
Appendix F
Write Ramp Value (Sequence No. 164)
Writes the ramp values.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Unit No.
Ramp value
(Undefined)
Time unit
(Undefined)
(Undefined)
Time unit
Ramp value
(Undefined)
+16
~
(Undefined)
+17 Time unit
Ramp value
(Undefined)
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Ramp value (3 digits BCD)
~
0018 (fixed)
00 to 0F
000 to 999
Channel 0
Channel 1
Channel 7
Data
S: Seconds; M: Minutes; H: Hours
+4
Time unit (one ASCII character)
Channel 1
Ramp value (3 digits BCD)
000 to 999
S: Second M: Minute H: Hour
+16
+17
Time unit (one ASCII character)
•
•
•
Channel 7
Ramp value (3 digits BCD)
Channel 7
Time unit (one ASCII character)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
000 to 999
S: Seconds; M: Minutes; H: Hours
Write Manual Output Value (Sequence No. 165)
Writes the manual output values for control output in manual operation.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined) Unit No.
Output value
Cooling output value
Output value
Cooling output value
Channel 0
Channel 1
+16
~
+17
Output value
Cooling output value
~
Channel 7
222
E5ZE Temperature Controller Write Protocol
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Output value (4 digits BCD)
+4
Cooling output value
(4 digits BCD)
Channel 1
Output value (4 digits BCD)
+16
+17
Cooling output value
(4 digits BCD)
•
•
•
Channel 7
Output value (4 digits BCD)
Channel 7
Cooling output value
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0018 (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Write Output Value Limit (Sequence No. 166)
Writes the output value limits that restrict the values of the control outputs.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+30
~
+31
+32
+33
Number of send data words
(Undefined)
Unit No.
Output value lower limit
Output value upper limit
Cooling output value lower limit
Cooling output value upper limit
Output value lower limit
Output value upper limit
Cooling output value lower limit
Cooling output value upper limit
~
Channel 0
Channel 7
Data
Appendix F
223
E5ZE Temperature Controller Write Protocol
Appendix F
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Output value lower limit
(4 digits BCD)
+4
+5
+32
+33
Output value upper limit
(4 digits BCD)
Channel 0
Cooling output value lower limit
(4 digits BCD)
Channel 0
Cooling output value upper limit
(4 digits BCD)
•
•
•
Channel 7
Cooling output value lower limit
(4 digits BCD)
Channel 7
Cooling output value upper limit
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0034 (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Data
Write Output Value Change Rate Limit (Sequence No. 167)
Writes the output value change rate limits that restrict the rates of change in the control value output.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
(Undefined)
Unit No.
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
224
E5ZE Temperature Controller Write Protocol
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Output change rate limit
(4 digits BCD)
+4
+8
+9
Output change rate limit
(4 digits BCD)
Channel 2
Output change rate limit
(4 digits BCD)
•
•
•
Channel 6
Output change rate limit
(4 digits BCD)
Channel 7
Output change rate limit
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Save Settings (Sequence No. 168)
Saves the settings.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Initialize Settings (Sequence No. 169)
Initializes all the settings to the factory defaults.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0010 (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
Data
Appendix F
0000 to 1000
0000 to 1000
0002 (fixed)
00 to 0F
Data
0002 (fixed)
00 to 0F
Data
225
E5ZE Temperature Controller Write Protocol
Appendix F
Write HB and HS Alarm Valid Channels (Sequence No. 170)
Writes the valid or invalid channels of HB alarm and HS alarm.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
Unit No.
Write code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Write code (2 digits Hex)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 0F
00 to FF
Data
Write Heater Burnout and SSR Failure Detection Current
(Sequence No. 171)
Writes the currents for detecting heater burnouts and SSR failures.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+16
+17
~
Number of send data words
(Undefined) Unit No.
Heater burnout detection current
SSR failure detection current
Heater burnout detection current
SSR failure detection current
Heater burnout detection current
SSR failure detection current
~
Channel 0
Channel 1
Channel 7
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Heater burnout detection current
(4 digits BCD)
0018 (fixed)
00 to 0F
0000 to 0500
0000 to 0500
+4
SSR failure detection current
(4 digits BCD)
Channel 1
Heater burnout detection current
(4 digits BCD)
0000 to 0500
0000 to 0500
+16
+17
SSR failure detection current
(4 digits BCD)
•
•
•
Channel 7
Heater burnout detection current
(4 digits BCD)
Channel 7
SSR failure detection current
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000 to 0500
0000 to 0500
226
E5ZE Temperature Controller Write Protocol
Write Dead Band/Overlap Band (Sequence No. 172)
Writes the dead bands or overlap bands for control outputs during heating/cooling control.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+5
+6
+7
+8
+9
+0
+1
+2
+3
+4
+1
+2
Number of send data words
(Undefined) Unit No.
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Dead band/overlap band
(4 digits BCD)
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
0010 (fixed)
00 to 0F
0000 to 0999
0000 to 0999
+4
+8
+9
Dead band/overlap band
(4 digits BCD)
Channel 2
Dead band/overlap band
(4 digits BCD)
•
•
•
Channel 6
Dead band/overlap band
(4 digits BCD)
Channel 7
Dead band/overlap band
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0000 to 0999
0000 to 0999
0000 to 0999
Data
Write Cooling Coefficient (Sequence No. 173)
Writes the cooling coefficients for the cooling proportional bands for heating/cooling control.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+4
+5
+6
+7
+8
+9
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Appendix F
227
E5ZE Temperature Controller Write Protocol
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex)
Channel 0
Cooling coefficient (4 digits BCD)
+4
+8
+9
Cooling coefficient (4 digits BCD)
Channel 2
Cooling coefficient (4 digits BCD)
•
•
•
Channel 6
Cooling coefficient (4 digits BCD)
Channel 7
Cooling coefficient (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Start Control (Sequence No. 174)
Starts temperature control for all channels in the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0010 (fixed)
00 to 0F
0000 to 0100
0000 to 0100
0000 to 0100
0000 to 0100
0000 to 0100
0002 (fixed)
00 to 0F
Stop Operation or Control (Sequence No. 175)
Stops temperature control or manual operation for all channels of the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 (fixed)
00 to 0F
Data
Data
Data
Appendix F
228
E5ZE Temperature Controller Write Protocol
Appendix F
Start Manual Operation (Sequence No. 176)
Starts manual operation based on the output values that were set for all channels of the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits Hex) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 (fixed)
00 to 0F
Data
229
Appendix G
E5
@
J Temperature Controller Protocol
The E5 @ J Temperature Controller Protocol performs various settings and controls in remote mode for the Temperature Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The following table shows the structure of the E5 @ J Temperature Controller Protocol.
Sequence
No.
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
Communications sequence name
Function
Select remote mode
Select local mode
Switches the Controller to remote mode.
Switches the Controller to local mode.
Select backup mode Switches from set point write mode to backup mode.
Select RAM write mode Switches from set point write mode to RAM write mode.
Save set point
Write parameters 1
Saves the set point.
Writes the set point, alarm value 1, alarm value 2, and heater burnout alarm value.
Write parameters 2 Writes the proportional band, integral time, and derivative time.
Write input shift value Writes the input shift value.
Read parameters 1
Read parameters 2
Reads the set point, alarm value 1, alarm value 2, and heater burnout alarm value.
Reads the proportional band, integral time, and derivative time.
Read input shift value Reads the input shift value and writes it in
IOM.
Read output value
Read process value
Read set point limit
Reads the output value and stores it in IOM.
Reads the process value and stores it in IOM.
Reads the set point limits and stores them in
IOM.
Read heater current
Read initial status
Reads the heater current and stores it in IOM.
Reads the initial status and stores it in IOM.
General-purpose write Writes the specified parameter by setting a header code.
General-purpose read Reads the specified parameter by setting a header code.
Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd or 3rd operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 2nd operand (S).
Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D).
231
E5
@J Temperature Controller Protocol
Appendix G
Connections
The connections for using the E5 @ J Temperature Controller Protocol are shown below.
RS-232C Connections
CQM1H
E5 @ J
Serial Communications Board
RS-232C port
Signal name
Signal ground or common return line
Send data
Receive data
SG
Abbreviation
→
RS-232C
–
Signal direction
SD
RD
Output
Input
Pin No.
25, 27
26
28
Serial Communications
Board
RS-232C: D-sub
9-pin female
Signal
name
Pin
No.
Shielded cable
E5AJ
RS-232C:
Terminal Block
Terminal
Signal
name
MAX232C or equivalent
Note 1.
The connection configuration is a one-to-one configuration and the maximum cable length is 15 m.
2.
Use shielded twisted-pair cable (AWG28i or greater).
RS422A/485 Connections
CQM1H
E5 @ J
Serial Communications Board
RS-422A/485 port
→
RS-422A/485
E5 @ J
→
RS-422A/485
Up to 32 units can be connected.
E5 @ J
→
RS-422A/485
232
E5
@J Temperature Controller Protocol
• RS-422A
Signal name
Send data A
Send data B
Receive data A
Receive data B
Signal ground
Serial Communications
Board
RS-422A: D-sub
9-pin female
Signal name
Pin
No.
E5AJ
RS-422A:
Terminal Block
Terminal
Signal name
SDA
SDB
RDA
RDB
SG
Abbreviation
Terminating resistance
Appendix G
Signal direction
Output
Output
Input
Input
–
26
Pin No.
25
28
29
27
SN751177N or equivalent
Terminating resistance
(terminator)
Shielded cable
Terminating resistance
240
Ω
E5AJ
RS-422A:
Terminal Block
Shielded cable
Terminal
Signal name
Terminator switch
Terminating resis tance (240
Ω
) is connected via the terminator switch.
• RS-485
Signal name
Terminal A
Terminal B
Signal ground
A
B
SG
Abbreviation
Terminat ing resis tance
Serial Communications
Board
RS-485: D-sub
9-pin female
Signal name
Pin
No.
E5AJ
RS-485:
Terminal Block
Terminating resistance
Terminal
Signal name
Signal direction
I/O
I/O
–
Pin No.
26, 28
25, 29
27
SN751177N or equivalent
Shielded cable
E5AJ
RS-485:
Terminal Block
Shielded cable
Terminal
Signal name
Terminator switch
Terminating resis tance (240
Ω
) is connected via the terminator switch.
233
E5
@J Temperature Controller Protocol
Appendix G
Note 1.
The connection configuration is a one-to-one or a one-to-N configuration. Using a one-to-N configuration, up to 32 units can be connected including the Serial Communications Board.
2.
The maximum cable length is 500 m. Use shielded twisted-pair cable (AWG28i or greater).
3.
Connect terminating resistance to the devices only at both ends of the transmission path.
4.
The total terminating resistance at both ends must be at least 100
Ω
for RS-422A or 54
Ω
for RS-485.
Select Remote Mode (Sequence No. 200)
Switches the Controller to remote mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
Number of send data words
+1 (Undefined) Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Select Local Mode (Sequence No. 201)
Switches the Controller to local mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Select Backup Mode (Sequence No. 202)
Switches from the set point write mode to backup mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 (fixed)
00 to 31
0002 (fixed)
00 to 31
0002 (fixed)
00 to 31
Data
Data
Data
234
E5
@J Temperature Controller Protocol
Appendix G
Select RAM Write Mode (Sequence No. 203)
Switches from set point write mode to RAM write mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0 Number of send data words
+1
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 (fixed)
00 to 31
Save Set Point (Sequence No. 204)
Saves the set point.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 (fixed)
00 to 31
Data
Data
Write Parameters 1 (Sequence No. 205)
Writes the set point, alarm value 1, alarm value 2, and a heater burnout alarm value to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
Number of units
(Undefined) set point
Unit No.
Alarm value 1
Alarm value 2
Heater burnout alarm value
+122
~
+123
+124
+125
+126
(Undefined) Unit No.
set point
Alarm value 1
Alarm value 2
Heater burnout alarm value
~
1st unit
25th unit (max.)
235
E5
@J Temperature Controller Protocol
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+4
+5
+6
+7
+126
(max.)
Unit No. (2 digits BCD)
1st unit set point (4 digits BCD)
1st unit
Alarm value 1 (4 digits BCD)
1st unit
Alarm value 2 (4 digits BCD)
1st unit
Heater burnout alarm value 2
(4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Heater burnout alarm value 2
(4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
5 + 2
0001 to 0025
00 to 31
0000 to 9999
0000 to 9999
0000 to 9999
0000 to 9999
00 to 31
0000 to 9999
Write Parameters 2 (Sequence No. 206)
Writes the proportional bands, integral times, and derivative times to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+122
+123
~
+124
+125
Number of send data words
Number of units
(Undefined) Unit No.
Proportional band
Integral time
Derivative time
(Undefined)
Unit No.
Proportional band
Integral time
Derivative time
~
1st unit
31th unit (max.)
Appendix G
236
E5
@J Temperature Controller Protocol
Offset
+0
+1
+2
+3
+4
+5
+6
+125
(max.)
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit Unit No. (2 digits BCD)
1st unit
Proportional band (4 digits BCD)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
31th unit
Derivative time (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
4 + 2
0001 to 0031
00 to 31
0000 to 9999
0000 to 9999
0000 to 9999
00 to 31
0000 to 9999
Write Input Shift Value (Sequence No. 207)
Writes the input shift value.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
Input shift value
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Input shift value (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003 (fixed)
00 to 31
0000 to 9999
Data
Appendix G
237
E5
@J Temperature Controller Protocol
Appendix G
Read Parameters 1 (Sequence No. 208)
Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+26
~
Number of send data words
Number of units
(Undefined)
Unit No.
~
+1
(Undefined)
Offset
+0
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
(max.)
Number of units + 2
Data
0001 to 0025
00 to 31
+3
+26
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+97
+98
+99
+100
~
Number of receive data words
Set point
Alarm value 1
Alarm value 2
Heater burnout alarm value
Set point
Alarm value 1
Alarm value 2
Heater burnout alarm value
~
1st unit
00 to 31
00 to 31
25th unit (max.)
238
E5
@J Temperature Controller Protocol
Appendix G
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Set point (4 digits BCD)
+2
+3
1st unit
Alarm value 1 (4 digits BCD)
1st unit
Alarm value 2 (4 digits BCD)
+4
+5
+100
(max.)
1st unit
Heater burnout alarm value
(4 digits BCD)
2nd unit
Set point (4 digits BCD)
•
•
•
25th unit
Heater burnout alarm value
(4 digits BCD)
Data
Number of units
×
4 + 1
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Parameters 2 (Sequence No. 209)
Reads the proportional bands, integral times, and derivative times for multiple units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+32
~
Number of send data words
Number of units
(Undefined)
Unit No.
~
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
(max.)
Number of units+ 2
Data
0001 to 0031
00 to 31
+3
+32
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
31th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
239
E5
@J Temperature Controller Protocol
Appendix G
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+91
~
+92
+93
Number of receive data words
Proportional band
Integral time
Derivative time
Proportional band
Integral time
Derivative time
~
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Proportional band (4 digits BCD)
1st unit
31th unit (max.)
Data
Number of units
×
3 + 1
+2
+3
+4
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
2nd unit
Proportional band (4 digits BCD)
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
+93
(max.)
•
•
•
31th unit
Derivative time (4 digits BCD)
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Input Shift Value (Sequence No. 210)
Reads the input shift value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Input shift value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Input shift value (4 digits BCD)
0002 (fixed)
00 to 31
0002
Data
Data
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
240
E5
@J Temperature Controller Protocol
Appendix G
Read Output Value (Sequence No. 211)
Reads the output value and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Output value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Output value
(4 digits BCD)
0002 (fixed)
00 to 31
Data
Data
0002
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Process Value (Sequence No. 212)
Reads the process value and status data and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Process value
Status data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Process value (4 digits BCD)
0002 (fixed)
00 to 31
0003
+2 Status data (4 digits Hex)
Data
Data
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
Read Set Point Limit (Sequence No. 213)
Reads the set point limits and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
241
E5
@J Temperature Controller Protocol
Appendix G
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD) +1
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Set point lower limit
Set point upper limit
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Set point lower limit
(4 digits BCD)
+2 Set point upper limit
(4 digits BCD)
0002 (fixed)
00 to 31
Data
Data
0003
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Heater Current (Sequence No. 214)
Reads the heater current and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Heater current
Status data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Heater current
(4 digits BCD)
+2 Status data (4 digits Hex)
Read Initial Status (Sequence No. 215)
Reads the initial status and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
0002 (fixed)
00 to 31
Data
Data
0003
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 0011
Data
242
E5
@J Temperature Controller Protocol
Appendix G
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined)
Status
(Undefined) Alarm 1 type Alarm 2 type Input type
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits BCD)
Status (2 digits Hex)
Alarm 1 type (1 digit Hex)
Alarm 2 type (1 digit Hex)
Input type (1 digit BCD)
0003
00 to 99
0 to 9
0 to 9
0 to 9
Data
General-purpose Write (Sequence No. 216)
Writes the parameter specified by setting a header code.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
Header code (ASC)
(Undefined)
Data code
Send data
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Header code (two ASCII characters)
+3
+4
Data code (2 digits BCD)
Write data (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0005 (fixed)
Data
00 to 31
Header codes that can be set
MB, WS, W%, WW, WB, WN, WV
01 to 02
0000 to 9999
General-purpose Read (Sequence No. 217)
Reads the parameter specified by setting a header.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
Header code (ASC)
(Undefined) Data code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Header code (two ASCII characters)
0004 (fixed)
Data
00 to 31
Header codes that can be set
RS, R%, RW, RB, RN, RV, RO
01 to 02 +3 Data code (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Receive data
243
E5
@J Temperature Controller Protocol
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
Read data (4 digits BCD)
Note The completion code is not included in the read data.
Appendix G
Data
0002
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
244
Appendix H
ES100
@
Digital Controller Protocol
The ES100 @ Digital Controller Protocol controls in remote mode and reads various settings from the Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
268
269
270
271
272
262
263
264
265
266
258
259
260
250
251
252
253
254
255
256
257
Structure of the Protocol
The structure of the ES100 @ Digital Controller Protocol is shown below.
Sequence
No.
Transmission
sequence name
Function
261
267
Read event data
Read time signals
Read error detection data
Read heater burnout data
Read PV data
Read SP data
Read MV
Read control monitor data
Read adjustment parameters
Write adjustment parameters
Read PID control parameters 1
Read PID control parameters 2
Write PID control parameters 1
Write PID control parameters 2
Read local SP
Write local SP
Reads events 1 to 10 in the variable area.
Reads time signals 1 to 10 in the variable area.
Reads error groups 1 to 15 in the variable area.
Reads the heater burnout alarm.
Reads PV data in the variable area.
Reads SP data in the variable area.
Reads the MV in the variable area.
Reads control monitor data (SP, PV, and MV) in the variable area.
Reads adjustment parameters in the parameter area.
Writes adjustment parameters in the parameter area.
Reads PID parameters No. 1 to 4 from the
PID control parameters in the parameter area.
Reads PID parameters No. 5 to 8 from the
PID control parameters in the parameter area.
Writes PID parameters No. 1 to 4 from PID control parameters in the parameter area.
Writes PID parameters No. 5 to 8 from PID control parameters in the parameter area.
Reads the local SP in the program parameter area.
Writes local SP in the program parameter area.
Read program parameters
Write program parameters
Reads local SP, step time, PID No. wait code, and events 1 to 10 set values in the program parameter area.
Writes the local SP, step time, PID No., wait code, and event 1 to 10 set values in the program parameter area.
Remote setting mode Switches the setting mode to remote setting.
Local setting mode Switches the setting mode to local setting.
External setting mode Switches the setting mode to external setting.
Run command Starts control.
Reset (stop) Stops control.
Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
No
No
No
No
No
No
245
ES100
@ Digital Controller Protocol
Appendix H
Sequence
No.
273
274
275
276
277
278
279
280
Transmission
sequence name
Function
Auto mode
Manual mode
Execute A.T.
Cancel A.T.
Switches the control mode to auto.
Switches the control mode to a manual.
Executes A.T.
Cancels A.T.
Change pattern No.
Change bank No.
Changes the pattern No.
Changes the bank No.
Read controller status Reads the controller status.
General-purpose command
Sends specified data and stores the received data in the specified words.
Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
Connections
Connections for using the ES100 @
RS-232C Connections
CQM1H
Serial Communications Board
RS-232C port
Digital Controller Protocol are shown below.
ES100 @
→
Serial Communications Board
RS-232C: D-sub
9-pin female
Signal name Pin No.
ES100 @ @ 01 @
RS-232C:
Terminal Block
Terminal
17
16
15
Signal name
Shielded cable
246
ES100
@ Digital Controller Protocol
RS422A/485 Connections
CQM1H
Serial Communications Board
RS-422A/485 port
• RS-422A
Serial Communications Board
RS-422A: D-sub
9-pin female
Signal name Pin No.
Shielded cable
ES100 @
Appendix H
→
RS-422A/485
ES100
@
→
RS-422A/485
Up to 32 units can be connected.
ES100
@
→
RS-422A/485
ES100 @ @ 04 @
RS--422
Terminal Block
Terminal Signal name
Next
ES100
• RS-485
Serial Communications Board
RS-485: D-sub
9-pin female
Pin No.
Shielded cable
ES100j-j04j
RS--485
Terminal Block
Terminal
Next
ES100
247
ES100
@ Digital Controller Protocol
Appendix H
Switch Settings
There are two switches located on the board on the left of the Unit. Set SW1 to the interface: RS-422A or RS-
485. Set SW2 to the center on all terminating Units and to the same setting as SW1 on all other Units.
422
← • →
485
422
← • →
485
Read Event Data (Sequence No. 250)
Reads events 1 to 10 in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+26
~
+1
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Offset
+0
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
~
1st unit
2nd unit
25th unit (max.)
Number of units + 2
Data
0001 to 0025
00 to 31
+3
+26
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+121
+122
+123
+124
+125
~
+0
+1
+2
+3
+4
+5
Number of receive data words
Event 1 Event 2
Event 3
Event 5
Event 4
Event 6
Event 7
Event 9
Event 8
Event 10
Event 1
Event 3
Event 5
Event 7
Event 9
Event 2
Event 4
Event 6
Event 8
Event 10
~
1st unit
25th unit (max.)
248
ES100
@ Digital Controller Protocol
Offset
+0
+1
+2
+3
+4
+5
+125
(max.)
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Event data 1 (2 digits Hex)
Event data 2 (2 digits Hex)
1st unit
Event data 3 (2 digits Hex)
Event data 4 (2 digits Hex)
1st unit
Event data 5 (2 digits Hex)
Event data 6 (2 digits Hex)
1st unit
Event data 7 (2 digits Hex)
Event data 8 (2 digits Hex)
1st unit
Event data 9 (2 digits Hex)
Event data 10 (2 digits Hex)
•
•
•
25th unit
Event data 9 (2 digits Hex)
Event data 10 (2 digits Hex)
Data
Number of units x 5 + 1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Read Time Signal (Sequence No. 251)
Reads time signals from 1 to 10 in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
+3
~
+26
Offset
+0
+1
(Undefined)
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
~
1st unit
2nd unit
25th unit (max.)
Number of units + 2
Data
0001 to 0025
00 to 31
+3
+26
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Appendix H
249
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+121
~
+122
+123
+124
+3
+4
+5
+0
+1
+2
+125
Number of receive data words
Time signal 1 Time signal 2
Time signal 3
Time signal 5
Time signal 7
Time signal 9
Time signal 4
Time signal 6
Time signal 8
Time signal 10
Time signal 1
Time signal 3
Time signal 5
Time signal 7
Time signal 9
Time signal 2
Time signal 4
Time signal 6
Time signal 8
Time signal 10
~
Offset
+0
+1
+2
+3
+4
+5
+125
(max.)
Contents (data format)
Number of receive data words
(4digits BCD)
1st unit
Time signal 1 data (2 digits Hex)
Time signal 2 data (2 digits Hex)
1st unit
Time signal 3 data (2 digits Hex)
Time signal 4 data (2 digits Hex)
1st unit
Time signal 5 data (2 digits Hex)
Time signal 6 data (2 digits Hex)
1st unit
Time signal 7 data (2 digits Hex)
Time signal 8 data (2 digits Hex)
1st unit
Time signal 9 data (2 digits Hex)
Time signal 10 data (2 digits Hex)
•
•
•
25th unit
Time signal 9 data (2 digits Hex)
Time signal 10 data (2 digits Hex)
1st unit
25th unit (max.)
Data
Number of units
×
5 + 1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Read Error Detection Data (Sequence No. 252)
Reads error groups from 0 to 15 in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+17
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Unit No.
1st unit
2nd unit
~
16th unit (max.)
Appendix H
250
ES100
@ Digital Controller Protocol
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
+3
+17
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
16th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+128
~
Number of receive data words
Error group 0
Error group 2
Error group 1
Error group 3
Error group 4
Error group 6
Error group 8
Error group 10
Error group 12
Error group 14
Error group 5
Error group 7
Error group 9
Error group 11
Error group 13
Error group 15
Error group 14 Error group 15
~
Offset
+0
+1
+2
+7
+8
+9
+128
(max.)
1st unit
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Error group 0 data (2 digits Hex)
Error group 1 data (2 digits Hex)
1st unit
Error group 2 data (2 digits Hex)
Error group 3 data (2 digits Hex)
•
•
1st unit
Error group 12 data (2 digits Hex)
Error group 13 data (2 digits Hex)
1st unit
Error group 14 data (2 digits Hex)
Error group 15 data (2 digits Hex)
2nd unit
Error group 0 data (2 digits Hex)
Error group 1 data (2 digits Hex)
•
•
16th unit
Error group 14 data (2 digits Hex)
Error group 15 data (2 digits Hex)
16th unit (max.)
Data
Number of units
×
8 + 1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Appendix H
251
ES100
@ Digital Controller Protocol
Read Heater Burnout Data (Sequence No. 253)
Reads the heater burnout alarm in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
Offset
+0
+1
+3
(Undefined)
+33
(max.)
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
1st unit
~
2nd unit
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+32
~
Number of receive data words
(Undefined)
Heater burnout alarm
(Undefined)
(Undefined)
Heater burnout alarm
Heater burnout alarm
(Undefined)
Heater burnout alarm
~
1st unit
2nd unit
3rd unit
4th unit
Offset
+0
+1
+2
+3
+4
+32
(max.)
(Undefined)
Heater burnout alarm
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Heater burnout alarm (2 digits Hex)
2nd unit
Heater burnout alarm (2 digits Hex)
3rd unit
Heater burnout alarm (2 digits Hex)
4th unit
Heater burnout alarm (2 digits Hex)
•
•
•
32nd unit
Heater burnout alarm (2 digits Hex)
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
32nd unit (max.)
Number of units +1
Data
Appendix H
252
ES100
@ Digital Controller Protocol
Read PV Data (Sequence No. 254)
Reads the PV data for the variable type “analog data” in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+33
~
Offset
+0
+1
(Undefined)
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
~
2nd unit
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+63
~
+64
Number of receive data words
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
~
1st unit
2nd unit
32nd unit
Appendix H
253
ES100
@ Digital Controller Protocol
Appendix H
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4digits BCD)
1st unit
PV data (rightmost 4 digits)
(4 digits BCD)
1st unit
PV data (leftmost 4 digits)
(4 digits BCD)
2nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
2nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
•
•
•
32nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
32nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
Data
Number of units
×
2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
Read SP Data (Sequence No. 255)
Reads the SP data for the variable type “analog data” in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Offset
+0
+1
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
~
1st unit
2nd unit
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
254
ES100
@ Digital Controller Protocol
Appendix H
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+63
~
+64
Number of receive data words
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
~
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
SP data (rightmost 4 digits)
(4 digits BCD)
1st unit
SP data (leftmost 4 digits)
(4 digits BCD)
2nd unit
SP data (rightmost 4 digits)
(4 digits BCD)
2nd unit
SP data (leftmost 4 digits)
(4 digits BCD)
•
•
•
32nd unit
SP data (rightmost 4 digits)
(4 digits BCD)
32nd unit
SP data (leftmost 4 digits)
(4 digits BCD)
1st unit
2nd unit
32nd unit
Data
Number of units
×
2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
Read MV Data (Sequence No. 256)
Reads the MV for the variable type “analog data” in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
~
+33
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
255
ES100
@ Digital Controller Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Number of units + 2
Data
0001 to 0032
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
Number of receive data words
MV (rightmost 4 digits)
MV (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
~
+63
+64
MV (rightmost 4 digits)
MV (leftmost 4 digits)
~
1st unit
2nd unit
32nd unit
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
MV (rightmost 4 digits) (4 digits BCD)
1st unit
MV (leftmost 4 digits) (4 digits BCD)
2nd unit
MV (rightmost 4 digits) (4 digits BCD)
2nd unit
MV (leftmost 4 digits) (4 digits BCD)
•
•
•
32nd unit
MV (rightmost 4 digits) (4 digits BCD)
32nd unit
MV (leftmost 4 digits) (4 digits BCD)
Data
Number of units
×
2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
Read Control Monitor Data (Sequence No. 257)
Reads the control monitor data (SP/PV/MV) in the variable area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+22
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
21st unit (max.)
256
ES100
@ Digital Controller Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Number of units + 2
Data
0001 to 0021
00 to 31
+3
+22
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
21st unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
+121
~
+122
+123
+124
+125
+126
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
~
1st unit
21st unit
Offset
+0
+1
+2
+3
+4
+5
+6
+125
+126
Contents (data format)
1st unit
Number of receive data words
(4 digits BCD)
1st unit
SP data (rightmost 4 digits)
(4 digits BCD)
1st unit
SP data (leftmost 4 digits)
(4 digits BCD)
1st unit
PV data (rightmost 4 digits)
(4 digits BCD)
1st unit
PV data (leftmost 4 digits)
(4 digits BCD)
1st unit
MV (rightmost 4 digits) (4 digits BCD)
1st unit
MV (leftmost 4 digits) (4 digits BCD)
•
•
•
21st unit
MV (rightmost 4 digits) (4 digits BCD)
21st unit
MV (leftmost 4 digits) (4 digits BCD)
Data
Number of units
×
6 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
257
ES100
@ Digital Controller Protocol
Appendix H
Read Adjustment Parameters (Sequence No. 258)
Reads the adjustment parameters in the parameter area and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
258
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+29
+30
+31
+32
+33
+34
+35
+36
+37
+38
+39
+40
+41
+42
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+14
+15
+16
+17
+18
Fixed SP
Number of receive data words
Control output 1 pulse cycle
Control output 2 pulse cycle
Fuzzy strength
Cooling coefficient
Heater burnout alarm setting
Position-proportional dead band
Switching output hysteresis
ON/OFF count alarm setting
ON/OFF control hysteresis
Manual reset
SP setting lower limit
SP setting upper limit
SP rise rate limit
SP fall rate limit
MV rate-of-change limit
Secondary loop fixed SP
Secondary loop P
Secondary loop I
Secondary loop D
Secondary loop manual reset
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Appendix H
259
ES100
@ Digital Controller Protocol
Appendix H
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
+11 to 12
+13 to 14
+15 to 16
+17 to 18
+19 to 20
+21 to 22
+23 to 24
+25 to 26
+27 to 28
+29 to 30
+31 to 32
+33 to 34
+35 to 36
+37 to 38
+39 to 40
+41 to 42
Contents (data format)
Number of receive data words
(4 digits BCD)
Fixed SP (8 digits BCD)
Control output 1 pulse cycle
(8 digits BCD)
Control output 2 pulse cycle
(8 digits BCD)
Fuzzy strength (8 digits BCD)
Cooling coefficient (8 digits BCD)
Heater burnout alarm setting
(8 digits BCD)
Position-proportional dead band
(8 digits BCD)
Switching output hysteresis
(8 digits BCD)
ON/OFF count alarm setting
(8 digits BCD)
ON/OFF control hysteresis
(8 digits BCD)
Manual reset (8 digits BCD)
SP setting lower limit
(8 digits BCD)
SP setting upper limit
(8 digits BCD)
SP rise rate limit (8 digits BCD)
SP fall rate limit (8 digits BCD)
MV rate-of-change limit (8 digits BCD)
Secondary loop fixed SP
(8 digits BCD)
Secondary loop P (8 digits BCD)
Secondary loop I (8 digits BCD)
Secondary loop D (8 digits BCD)
Secondary loop manual reset
(8 digits BCD)
0043
Data
00000000 to 09999000
F indicates a negative number.
260
ES100
@ Digital Controller Protocol
Write Adjustment Parameters (Sequence No. 259)
Writes the adjust parameters in the parameter area.
+31
+32
+33
+34
+35
+36
+37
+38
+39
+18
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+29
+30
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+40
+41
+42
+43
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
Number of send data words
(Undefined)
Fixed SP
Unit No.
(rightmost 4 digits)
(leftmost 4 digits)
Control output 1 pulse cycle
Control output 2 pulse cycle
Fuzzy strength
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Cooling coefficient
Heater burnout alarm setting
Position-proportional dead band
Switching output hysteresis
ON/OFF count alarm setting
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
ON/OFF control hysteresis
Manual reset
SP setting lower limit
SP setting upper limit
SP rise rate limit
SP fall rate limit
MV change rate limit
Secondary loop fixed SP
Secondary loop P
Secondary loop I
Secondary loop D
Secondary loop manual reset
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Appendix H
261
ES100
@ Digital Controller Protocol
Appendix H
+0
Offset
+1
+2 to 3
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+16 to 17
+18 to 19
+20 to 21
+22 to 23
+24 to 25
+26 to 27
+28 to 29
+30 to 31
+32 to 33
+34 to 35
+36 to 37
+38 to 39
+40 to 41
+42 to 43
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
Fixed SP (8 digits BCD)
Control output 1 pulse cycle
(8 digits BCD)
Control output 2 pulse cycle
(8 digits BCD)
Fuzzy strength (8 digits BCD)
Cooling coefficient (8 digits BCD)
Heater burnout alarm setting
(8 digits BCD)
Position-proportional dead band
(8 digits BCD)
Switching output hysteresis
(8 digits BCD)
ON/OFF count alarm setting
(8 digits BCD) value
ON/OFF control hysteresis
(8 digits BCD)
Manual reset (8 digits BCD)
SP setting lower limit
(8 digits BCD)
SP setting upper limit
(8 digits BCD)
SP rise rate limit (8 digits BCD)
SP fall rate limit (8 digits BCD)
MV rate-of-change limit (8 digits BCD)
Secondary loop fixed SP
(8 digits BCD)
Secondary loop P (8 digits BCD)
Secondary loop I (8 digits BCD)
Secondary loop D (8 digits BCD)
Secondary loop manual reset
(8 digits BCD)
0044 (fixed)
Data
00 to 31
00000000 to 09999000
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Read PID Control Parameters 1 (Sequence No. 260)
Reads PID parameters No. 1 to 4 from PID control parameters in the parameter area and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
262
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+4
+5
+6
+7
+8
+0
+1
+2
+3
+9
+10
+11
+12
+13
+14
Number of receive data words
PID No. 1 P
PID No. 1 P
PID No. 1 I
PID No. 1 I
PID No. 1 D
PID No. 1 D
PID No. 1 MV lower limit
PID No. 1 MV lower limit
PID No. 1 MV upper limit
PID No. 1 MV upper limit
PID No. 1 PV bias value
PID No. 1 PV bias value
PID No. 1 Automatic selection range upper limit
PID No. 1 Automatic selection range upper limit
+51
~
+52
+53
+54
+55
+56
PID No. 4 MV upper limit
PID No. 4 MV upper limit
PID No. 4 PV bias value
PID No. 4 PV bias value
PID No. 4 Automatic selection range upper limit
PID No. 4 Automatic selection range upper limit
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
+11 to 12
+13 to 14
+43 to 44
+45 to 46
+47 to 48
+49 to 50
+51 to 52
+53 to 54
+55 to 56
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Contents (data format)
Number of receive data words
(4 digits BCD)
PID No. 1 P (8 digits BCD)
PID No. 1 I (8 digits BCD)
PID No. 1 D (8 digits BCD)
PID No. 1 MV lower limit (8 digits BCD)
PID No. 1 MV upper limit
(8 digits BCD)
PID No. 1 PV bias value (8 digits BCD)
PID No. 1 Automatic selection range upper limit (8 digits BCD)
•
•
•
PID No. 4 P (8 digits BCD)
PID No. 4 I (8 digits BCD)
PID No. 4 D (8 digits BCD)
PID No. 4 MV lower limit (8 digits BCD)
PID No. 4 MV upper limit
(8 digits BCD)
PID No. 4 PV bias value (8 digits BCD)
PID No. 4 Automatic selection range upper limit (8 digits BCD)
0057
Data
00000000 to 09999000
Appendix H
263
ES100
@ Digital Controller Protocol
Appendix H
Read PID Control Parameters 2 (Sequence No. 261)
Reads PID parameters No. 5 to 8 from the PID control parameters in the parameter area and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+3
+4
+5
+6
+0
+1
+2
+7
+8
+9
+10
+11
+12
+13
+14
Number of receive data words
PID No. 5 P
PID No. 5 P
PID No. 5 I
PID No. 5 I
PID No. 5 D
PID No. 5 D
PID No. 5 MV lower limit
PID No. 5 MV lower limit
PID No. 5 MV upper limit
PID No. 5 MV upper limit
PID No. 5 PV bias value
PID No. 5 PV bias value
PID No. 5 Automatic selection range upper limit
PID No. 5 Automatic selection range upper limit
~
+51
+52
+53
+54
+55
+56
PID No. 8 MV upper limit
PID No. 8 MV upper limit
PID No. 8 PV bias value
PID No. 8 PV bias value
PID No. 8 Automatic selection range upper limit
PID No. 8 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
264
ES100
@ Digital Controller Protocol
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
+11 to 12
+13 to 14
+43 to 44
+45 to 46
+47 to 48
+49 to 50
+51 to 52
+53 to 54
+55 to 56
Contents (data format)
Number of receive data words
(4 digits BCD)
PID No. 5 P (8 digits BCD)
PID No. 5 I (8 digits BCD)
PID No. 5 D (8 digits BCD)
PID No. 5 MV lower limit (8 digits BCD)
PID No. 5 MV upper limit
(8 digits BCD)
PID No. 5 PV bias value (8 digits BCD)
PID No. 5 Automatic selection range upper limit (8 digits BCD)
•
•
•
PID No. 8 P (8 digits BCD)
PID No. 8 I (8 digits BCD)
PID No. 8 D (8 digits BCD)
PID No. 8 MV lower limit (8 digits BCD)
PID No. 8 MV upper limit
(8 digits BCD)
PID No. 8 PV bias value (8 digits BCD)
PID No. 8 Automatic selection range upper limit (8 digits BCD)
0057
Data
00000000 to 09999000
Appendix H
265
ES100
@ Digital Controller Protocol
Write PID Control Parameters 1 (Sequence No. 262)
Writes PID parameters No. 1 to 4 to the PID control parameters in the parameter area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+52
~
+53
+54
+55
+56
+57
+10
+11
+12
+13
+14
+15
+0
+1
+2
+3
+4
+5
+6
+7
Number of send data words
(Undefined)
Unit No.
PID No. 1 P
PID No. 1 P
PID No. 1 I
PID No. 1 I
PID No. 1 D
+8
+9
PID No. 1 D
PID No. 1 MV lower limit
PID No. 1 MV lower limit
PID No. 1 MV upper limit
PID No. 1 MV upper limit
PID No. 1 PV bias value
PID No. 1 PV bias value
PID No. 1 Automatic selection range upper limit
PID No. 1 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
PID No. 4 MV upper limit
PID No. 4 MV upper limit
PID No. 4 PV bias value
PID No. 4 PV bias value
PID No. 4 Automatic selection range upper limit
PID No. 4 Automatic selection range upper limit
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Appendix H
266
ES100
@ Digital Controller Protocol
+0
Offset
+1
+2 to 3
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+44 to 45
+46 to 47
+48 to 49
+50 to 51
+52 to 53
+54 to 55
+56 to 57
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
PID No. 1 P (8 digits BCD)
PID No. 1 I (8 digits BCD)
PID No. 1 D (8 digits BCD)
PID No. 1 MV lower limit (8 digits BCD)
PID No. 1 MV upper limit
(8 digits BCD)
PID No. 1 PV bias value
(8 digits BCD)
PID No. 1 Automatic selection range upper limit
(8 digits BCD)
•
•
•
PID No. 4 P (8 digits BCD)
PID No. 4 I (8 digits BCD)
PID No. 4 D (8 digits BCD)
PID No. 4 MV lower limit (8 digits BCD)
PID No. 4 MV upper limit
(8 digits BCD)
PID No. 4 PV bias value
(8 digits BCD)
PID No. 4 Automatic selection range upper limit
(8 digits BCD)
0058 (fixed)
Data
00 to 31
00000000 to 09999000
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Appendix H
267
ES100
@ Digital Controller Protocol
Write PID Control Parameters 2 (Sequence No. 263)
Writes the PID parameters No. 5 to 8 to the PID control parameters in the parameter area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+52
+53
+54
+55
+56
+57
+5
+6
+7
+8
+9
+0
+1
+2
+3
+4
+10
+11
+12
+13
+14
+15
~
Number of send data words
(Undefined) Unit No.
PID No. 5 P
PID No. 5 P
PID No. 5 I
PID No. 5 I
PID No. 5 D
PID No. 5 D
PID No. 5 MV lower limit
PID No. 5 MV lower limit
PID No. 5 MV upper limit
PID No. 5 MV upper limit
PID No. 5 PV bias value
PID No. 5 PV bias value
PID No. 5 Automatic selection range upper limit
PID No. 5 Automatic selection range upper limit
PID No. 8 MV upper limit
PID No. 8 MV upper limit
PID No. 8 PV bias value
PID No. 8 PV bias value
PID No. 8 Automatic selection range upper limit
PID No. 8 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Appendix H
268
ES100
@ Digital Controller Protocol
+0
Offset
+1
+2 to 3
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+44 to 45
+46 to 47
+48 to 49
+50 to 51
+52 to 53
+54 to 55
+56 to 57
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
PID No. 5 P (8 digits BCD)
PID No. 5 I (8 digits BCD)
PID No. 5 D (8 digits BCD)
PID No. 5 MV lower limit (8 digits BCD)
PID No. 5 MV upper limit
(8 digits BCD)
PID No. 5 PV bias value
(8 digits BCD)
PID No. 5 Automatic selection range upper limit
(8 digits BCD)
•
•
•
PID No. 8 P (8 digits BCD)
PID No. 8 I (8 digits BCD)
PID No. 8 D (8 digits BCD)
PID No. 8 MV lower limit (8 digits BCD)
PID No. 8 MV upper limit
(8 digits BCD)
PID No. 8 PV bias value
(8 digits BCD)
PID No. 8 Automatic selection range upper limit
(8 digits BCD)
0058 (fixed)
Data
00 to 31
00000000 to 09999000
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Read Local SP (Sequence No. 264)
Reads the local SP in the program parameter area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+64
+65
~
Number of send data words
Number of units
(Undefined)
Unit No.
Pattern No.
Step No.
(Undefined)
Unit No.
Pattern No.
Step No.
(Undefined)
Pattern No.
Unit No.
Step No.
~
1st unit
2nd unit
32nd unit
Appendix H
269
ES100
@ Digital Controller Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Data
Number of units
×
2 + 2
0001 to 0032
00 to 31
+3
Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
•
•
•
00 to 63
00 to 63
00 to 31
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
00 to 63
00 to 63
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
Number of receive data words
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
+63
+64
~
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
~
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Local SP (rightmost 4 digits)
(4 digits BCD)
1st unit
Local SP (leftmost 4 digits)
(4 digits BCD)
2nd unit
Local SP (rightmost 4 digits)
(4 digits BCD)
2nd unit
Local SP (leftmost 4 digits)
(4 digits BCD)
•
•
•
32nd unit
Local SP (rightmost 4 digits)
(4 digits BCD)
32nd unit
Local SP (leftmost 4 digits)
(4 digits BCD)
1st unit
2nd unit
32nd unit
Data
Number of units
×
2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
00000000 to 09999000
270
ES100
@ Digital Controller Protocol
Write Local SP (Sequence No. 265)
Writes the local SP to the program parameter area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+3
+4
+5
+6
+7
+8
+0
+1
+2
+9
Number of send data words
Number of units
(Undefined)
Unit No.
Pattern No.
Step No.
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
(Undefined)
Unit No.
Pattern No.
Step No.
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
~
+122
+123
+124
+125
(Undefined)
Unit No.
Pattern No.
Step No.
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
2nd unit
31st unit
Data
Number of units
×
4 + 2
0001 to 0031
00 to 31
+3
+4
+5
+122
+123
+124
+125
Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
1st unit
Local SP (rightmost 4 digits)
(4 digits BCD)
1st unit
Local SP (leftmost 4 digits)
(4 digits BCD)
•
•
•
31st unit
Unit No. (2 digits BCD)
31st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
31st unit
Local SP (rightmost 4 digits)
(4 digits BCD)
31st unit
Local SP (leftmost 4 digits)
(4 digits BCD)
00 to 63
00 to 63
00000000 to 09999000
00 to 31
00 to 63
00 to 63
00000000 to 09999000
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Appendix H
271
ES100
@ Digital Controller Protocol
Appendix H
Read Program Parameters (Sequence No. 266)
Reads the local SP, step time, PID set No., wait code, and events from 1 to 10 set values in the program parameter area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+5
+6
+7
+8
+9
+0
+1
+2
+3
+4
+1
Number of send data words
Number of units
(Undefined)
Unit No.
Pattern No.
Step No.
(Undefined)
Unit No.
Pattern No.
Step No.
(Undefined)
Unit No.
Pattern No.
Step No.
(Undefined)
Unit No.
Pattern No.
Step No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
2nd unit
3rd unit
4th unit
Data
Number of units
×
2 + 2
0001 to 0004
00 to 31
+3
+8
+9
(max.)
Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
•
•
•
4th unit
Unit No. (2 digits BCD)
4th unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
00 to 63
00 to 63
00 to 31
00 to 63
00 to 63
272
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+85
+86
+87
+88
+89
+90
+91
+92
+93
+94
~
+111
+112
~
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
~
+27
+28
Number of receive data words
Local SP (rightmost)
Local SP (leftmost)
Step bank time (rightmost)
Step bank time (leftmost)
PID set No. (rightmost)
PID set No. (leftmost)
Wait code (rightmost)
Wait code (leftmost)
Event 1 setting (rightmost)
Event 1 setting (leftmost)
Event 10 setting (rightmost)
Event 10 setting (leftmost)
Local SP (rightmost)
Local SP (leftmost)
Step bank time (rightmost)
Step bank time (leftmost)
PID set No. (rightmost)
PID set No. (leftmost)
Wait code (rightmost)
Wait code (leftmost)
Event 1 setting (rightmost)
Event 1 setting (leftmost)
Event 10 setting (rightmost)
Event 10 setting (leftmost)
~
~
~
1st unit
4th unit (max.)
Appendix H
273
ES100
@ Digital Controller Protocol
Appendix H
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
Contents (data format)
Number of receive data words
(4digits BCD)
1st unit
Local SP (8 digits BCD)
1st unit
Step time) (8 digits BCD)
1st unit
PID set No. (8 digits BCD)
1st unit
Wait code (8 digits BCD)
1st unit
Event 1 setting (8 digits BCD)
+11 to 12
+27 to 28
+29 to 30
1st unit
Event 2 setting (8 digits BCD)
•
•
1st unit
Event 10 setting (8 digits BCD)
1st unit
Local SP (8 digits BCD)
•
•
+109 to 110 4th unit
Event 9 setting (8 digits BCD)
+111 to 112
(max.)
4th unit
Event 10 setting (8 digits BCD)
Data
Number of units
×
28 + 1
00000000 to 09999000
F indicates a negative number.
Write Program Parameters (Sequence No. 267)
Writes the local SP, step time, PID set No., wait code, and events from 1 to 10 settings in the program parameter area.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
Number of send data words
Number of units
(Undefined)
Unit No.
Pattern No.
Step No.
Local SP (rightmost)
Local SP (leftmost)
Step bank time (rightmost)
Step bank time (leftmost)
PID set No. (rightmost)
PID set No. (leftmost)
Wait code (rightmost)
Wait code (leftmost)
Event 1 setting (rightmost)
Event 1 setting (leftmost)
1st unit
~
+30
~
+31
+92
~
+93
+120
~
+121
Event 10 setting (rightmost)
Event 10 setting (leftmost)
(Undefined)
Pattern No.
Unit No.
Step No.
Event 10 setting (rightmost)
Event 10 setting (leftmost)
~
~
4th unit (max.)
274
ES100
@ Digital Controller Protocol
+0
+1
+2
+3
Offset
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+30 to 31
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
1st unit
Local SP (8 digits BCD)
1st unit
Step time (8 digits BCD)
1st unit
PID set No. (8 digits BCD)
1st unit
Wait code (8 digits BCD)
1st unit
Event 1 setting (8 digits BCD)
1st unit
Event 2 setting (8 digits BCD)
•
•
1st unit
Event 10 setting (8 digits BCD)
+32 to 33 2nd unit
Local SP (8 digits BCD)
•
•
+111 to 112 4th unit
Event 9 setting (8 digits BCD)
+120 to 121
(max.)
4th unit
Event 10 setting (8 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Remote Setting Mode (Sequence No. 268)
Switches the setting mode to the remote setting mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
1st unit
2nd unit
~
32nd unit (max.)
Data
Number of units
×
30 + 2
0001 to 0004
00 to 31
00 to 63
00 to 63
00000000 to 09999000
Appendix H
275
ES100
@ Digital Controller Protocol
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Number of units + 2
Data
0001 to 0032
00 to 31
00 to 31
00 to 31
Local Setting Mode (Sequence No. 269)
Switches the setting mode to the local setting mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
(Undefined)
Offset
+0
+1
+3
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+33
(max.)
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
1st unit
~
2nd unit
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
External Setting Mode (Sequence No. 270)
Switches the setting mode to the external setting mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
~
+33
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Appendix H
276
ES100
@ Digital Controller Protocol
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Number of units + 2
Data
0001 to 0032
00 to 31
00 to 31
00 to 31
Run Command (Sequence No. 271)
Starts control.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
Number of units
(Undefined)
Unit No.
Pattern No./Bank No.
~
+64
+65
(Undefined)
Unit No.
Pattern No. Bank No.
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
32nd unit (max.)
Data
Number of units
×
2 + 2
0001 to 0032
00 to 31
+3
+24
Unit No. (2 digits BCD)
1st unit
Pattern No./Bank No.
(4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
0000 to 0063
00 to 31
00 to 31
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
Pattern No./Bank No.
(4 digits BCD)
0000 to 0063
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Appendix H
277
ES100
@ Digital Controller Protocol
Reset (Stop) (Sequence No. 272)
Stops control.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
+1
(Undefined)
Offset
+0
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
1st unit
~
2nd unit
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Auto Mode (Sequence No. 273)
Switches the control mode to the auto mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
2nd unit
~
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Appendix H
278
ES100
@ Digital Controller Protocol
Manual Mode (Sequence No. 274)
Switches the control mode to the manual mode.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+1
(Undefined)
Offset
+0
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
~
2nd unit
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Execute A.T. (Sequence No. 275)
Executes A.T.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+64
+65
~
Number of send data words
Number of units
(Undefined)
Unit No.
PID set No.
(Undefined)
Unit No.
PID set No.
~
1st unit
32nd unit (max.)
Appendix H
279
ES100
@ Digital Controller Protocol
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+4
Unit No. (2 digits BCD)
1st unit
PID set No. (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
PID set No. (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
2 + 2
0001 to 0032
00 to 31
0000 to 0008
00 to 31
00 to 31
0000 to 0008
Cancel A.T. (Sequence No. 276)
Cancels A.T.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+1
(Undefined)
Offset
+0
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
2nd unit
~
32nd unit (max.)
Number of units + 2
Data
0001 to 0032
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Appendix H
280
ES100
@ Digital Controller Protocol
Change Pattern No. (Sequence No. 277)
Changes the pattern number.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+64
+65
~
Number of send data words
Number of units
(Undefined)
Unit No.
Pattern No.
(Undefined)
Unit No.
Pattern No.
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1
+3
Number of units (4 digits BCD) unit
Unit No. (2 digits BCD)
1st unit
Pattern No. (4 digits BCD)
+4 2nd unit
Unit No. (2 digits BCD)
•
•
•
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
Pattern No. (4 digits BCD)
~
1st unit
32nd unit (max.)
Data
Number of units
×
2 + 2
0001 to 0032
00 to 31
0001 to 0063
00 to 31
00 to 31
0001 to 0063
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Change Bank No. (Sequence No. 278)
Changes the bank number.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+64
~
+65
Number of send data words
Number of units
(Undefined)
Bank No.
Unit No.
(Undefined)
Bank No.
Unit No.
~
1st unit
32nd unit (max.)
Appendix H
281
ES100
@ Digital Controller Protocol
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
+3
+4
Unit No. (2 digits BCD)
1st unit
Bank No. (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
Bank No. (4 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Number of units
×
2 + 2
0001 to 0032
00 to 31
0000 to 0007
00 to 31
00 to 31
0000 to 0007
Read Controller Status (Sequence No. 279)
Reads the Controller status.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+26
~
Number of send data words
Number of units
(Undefined)
Unit No.
+1
(Undefined)
Offset
+0
Unit No.
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (4 digits BCD)
1st unit
~
25th unit (max.)
Number of units + 2
Data
0001 to 0025
00 to 31
+26
(max.)
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
Operation status Hold
Auto/manual
Setting mode
A.T.
SP mode
Valid pattern No.
Valid PID set No.
Wait Operation mode
+121
~
+122
+123
+124
+125
Operation status
Auto/manual
Setting mode
A.T.
Wait
Hold
SP mode
Valid pattern No.
Valid PID set No.
Operation mode
~
1st unit
25th unit (max.)
Appendix H
282
ES100
@ Digital Controller Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits BCD)
1st unit
Operation status (2 digits BCD)
+2
Hold (2 digits BCD)
1st unit
Auto/manual (2 digits BCD)
SP mode (2 digits BCD)
+3
+4
+5
1st unit
Setting mode (2 digits BCD)
Valid pattern No. (2 digits BCD)
1st unit
A.T. (2 digits BCD)
Valid PD set No. (2 digits Hex)
1st unit
Wait (2 digits BCD)
Operation mode (2 digits BCD)
Data
Number of units
×
5 + 1
00: Reset
01: Run
00: Not hold
01: Hold
00: Auto mode
01: Manual mode
00: Local SP mode
01: Remote SP mode
02: Fixed SP mode
00: Local setting mode
01: Remote setting mode
02: External setting mode
00 to 63
00: Not A.T.
01: A.T.
01 to 08
00: Not waiting
01: Waiting
02: Wait alarm output
00: Setting level 1 (without technical mode)
01: Setting level 1 (with technical mode)
02: Setting level 2 (without technical mode)
03: Setting level 2 (with technical mode)
+125
(max.)
25th unit
Wait (2 digits BCD)
•
•
•
Operation mode (2 digits BCD)
00: Not waiting
01: Waiting
02: Wait alarm output
00: Setting level 1 (without technical mode)
01: Setting level 1 (with technical mode)
02: Setting level 2 (without technical mode)
03: Setting level 2 (with technical mode)
General-purpose Command (Sequence No. 280)
Sends the specified data and stores the received data in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+126
~
Number of send data words
Number of send data bytes
Send data (ASCII code)
Send data (ASCII code)
Send data
(Undefined)
~
(max. = 251 characters)
283
ES100
@ Digital Controller Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of send data bytes
0001 to 0128
Data
+2 Send data (ASCII 2 characters)
•
•
•
Send data (ASCII 1 characters)
0001 to 0251
The number of send bytes not including @, the FCS, or the terminator.
Refer to the manual for the ES100 @ .
Use ASCII (Up to 251 characters total.)
+127
(max.)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+126
~
Offset
+0
+1
Number of receive data words
Receive data (ASCII code)
Receive data (ASCII code)
Receive data
+126
(max.)
(Undefined)
~
(max.=251 characters)
Contents (data format)
Number of receive data words
(4 digits BCD)
Receive data
(ASCII 2 characters)
•
•
•
Receive data
(ASCII 1 characters)
0001 to 0127
Data
Refer to the manual for the ES100 @ .
Returned as ASCII (Up to 251 characters total.)
1.
At transmission, a header code “@” is attached before the data and the FCS and a terminator “*”CR are attached following the send data.
First word of send +0 data
+1
+2
+3
+4
+5
0006
0007
"AB"
"CD"
"EF"
"GH"
@ABCDEFG[FCS]*CR
2 bytes
2.
At reception, data excluding the header code “@” at the beginning of the receive data and the FCS and terminator “*”CR at the end of the data is stored in the receive data storage words.
@ABCDEFG[FCS]*CR
2 bytes
First word of send +0 data
+1
+2
+3
+4
+5
"G"
0006
0007
"AB"
"CD"
"EF"
3.
Refer to the manual for the ES100 @ for the contents of send data and receive data.
284
Appendix I
K3T
@
Intelligent Signal Processor Protocol
The K3T @ Intelligent Signal Processor Protocol is used to make various settings or control remotely the Intelligent Signal Processor connected to the Serial Communications Board via RS-232C or RS-422A/485 cable.
Protocol Configuration
The configuration of the K3T @ Intelligent Signal Processor Protocol is shown as follows:
Sequence
No.
300
Communications sequence name
Function Ladder interface
Send word allocation
Yes
Receive word allocation
No
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
Reset (by unit number) Performs the same processing as when an input is received on the reset terminal.
Reset (continuous units) Performs the same processing as when an input is received on the reset terminal.
Write set value (by unit number)
Write set value HH (continuous units)
Write set value H (continuous units)
Writes the set value HH, H, L, or
LL.
Writes the set value HH.
Writes the set value H.
Write set value L (continuous units)
Write set value LL (continuous units)
Write set value with bank
(by unit number)
Writes the set value L.
Writes the set value LL.
Write set value HH with bank (continuous units)
Write set value H with bank (continuous units)
Write set value L with bank (continuous units)
Writes the set value to a bank which is not in use (K3TR: HH to
LL, K3TC: O1 to O5).
Writes the set value HH to a bank which is not in use.
Writes the set value H to a bank which is not in use.
Writes the set value L to a bank which is not in use.
Write set value LL with bank (continuous units)
Write set value O5 with bank (continuous units)
Write set value O4 with bank (continuous units)
Write set value O3 with bank (continuous units)
Write set value O2 with bank (continuous units)
Write set value O1 with bank (continuous units)
Read set value (by unit number)
Read set value HH (continuous units)
Read set value H (continuous units)
Read set value L (continuous units)
Writes the set value LL to a bank which is not in use.
Writes the set value O5 to a bank which is not in use.
Writes the set value O4 to a bank which is not in use.
Writes the set value O3 to a bank which is not in use.
Writes the set value O2 to a bank which is not in use.
Writes the set value O1 to a bank which is not in use.
Reads the set value HH, H, L, or
LL.
Reads the set value HH.
Reads the set value H.
Reads the set value L.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Notes
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note2
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
285
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Sequence
No.
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
Communications sequence name
Function
Read set value LL (continuous units)
Read set value with bank
(by unit number)
Reads the set value LL.
Reads set value of a bank which is not in use (K3TR: HH to LL, K3TC:
O1 to O5).
Read set value HH with bank (continuous units)
Read set value H with bank (continuous units)
Read set value L with bank (continuous units)
Read set value LL with bank (continuous units)
Read set value O5 with bank (continuous units)
Read set value O4 with bank (continuous units)
Read set value O3 with bank (continuous units)
Read set value O2 with bank (continuous units)
Reads the set value HH of a bank which is not in use.
Reads the set value H of a bank which is not in use.
Reads the set value L of a bank which is not in use.
Reads the set value LL of a bank which is not in use.
Reads the set value O5 of a bank which is not in use.
Reads the set value O4 of a bank which is not in use.
Reads the set value O3 of a bank which is not in use.
Reads the set value O2 of a bank which is not in use.
Reads the set value O1 of a bank which is not in use.
Reads the peak/bottom data (maximum, minimum).
Reads the peak data (maximum).
Read set value O1 with bank (continuous units)
Read holding data (by unit number)
Read holding data PH
(continuous units)
Read holding data BH
(continuous units)
Read display value (PV)
(by unit number)
Read display value (PV )
(continuous units)
Read model (by unit number)
Read model (continuous units)
General-purpose command
Reads the bottom data (minimum).
Reads the display value (PV).
Reads the display value (PV).
Reads the model data.
Reads the model data.
Send specified data or receives specified data and writes it to the receive data words.
Ladder interface
Send word allocation
Receive word allocation
Yes Yes
Yes Yes
Notes
See
Note1
See
Note2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note 1.
Special specifications are required to use communications + comparison output.
2.
Special specifications are required to use communications + comparison output for the K3TR and
K3TC. The operands HH, H, L, and LL are for the K3TR, and the operands O5, O4, O3, O2, and O1 are for the K3TC.
3.
Not available for the K3TC.
4.
Ladder Interface Settings
YES: User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note1
See
Note3
See
Note3
See
Note3
286
K3T
@ Intelligent Signal Processor Protocol
Connections
The connections used for the K3T @ Intelligent Signal Processor Protocol are shown below.
RS-232C Connections
CQM1H
K3T @
Serial Communications Board
RS-232C port
Appendix I
Signal name
Protective ground or earth FG
Signal ground or common return line SG
Send data
Receive data
Request to send
Clear to send
Data set ready
Data terminal ready
DR
ER
SD
RD
RS
CS
Abbreviation Signal direction
–
–
Output
Input
Output
Input
Input
Output
Pin No.
4
5
2
3
1
7
6
20
Serial Communications
Board
RS-232C: D-sub
9-pin female
Signal
Name
Pin
No.
Shielded cable
Intelligent Signal
Processor
RS-232C:
Terminal block
Terminal.
Signal
Name
MAX232C or equivalent
Note 1.
The connection configuration is a one-to-one configuration and the maximum cable length is 15 m.
2.
Use shielded twisted-pair cable (AWG28i or greater).
287
K3T
@ Intelligent Signal Processor Protocol
RS422A/485 Connections
CQM1H
Serial Communications Board
RS-422A/485 port
• RS-422A
K3T @
Appendix I
K3T @
Up to 32 units can be connected
K3T @
Signal name
Send data A
Send data B
Receive data A
Receive data B
Signal ground
Protective ground
Serial Communications
Board
RS-422A: D-sub
9-pin female
Terminating resistance
Signal
Name
Pin
No.
Abbreviation
SDA
SDB
RDA
RDB
SG
FG
Signal direction Pin No.
Output 9
Output
Output
5
6
Input
–
–
1
3
7
Intelligent Sig nal Processor
RS-422A:
Terminal block
Terminal.
Signal
Name
Pin
No.
Terminal block SW
SN751177N or equivalent
Terminating resistance
(terminator)
Shielded cable
Terminating resistance (approx. 220
Ω
) is connected via the terminal block switch.
288
K3T
@ Intelligent Signal Processor Protocol
• RS-485
Signal name
Inverting output
Non-inverting output
–
+
Abbreviation Signal direction
Input or output
Input or output
Serial Communications
Board
RS-485: D-sub
9-pin female
Signal
Name
Pin
No.
Intelligent Signal Processor
Turn ON the terminal block switch for terminators only.
RS-485:
Terminal block
Terminal.
Signal
Name
Terminal block SW
SN751177N or equivalent
Appendix I
Terminal
19
18
Shielded cable
Intelligent Signal Processor
Unit designated as terminator.
RS-485:
Terminal block
Terminal.
Signal
Name
Terminal block SW ON
The terminal block switch is turned ON.
Shielded cable
Note 1.
The connection configuration is a one-to-one or a 1-to-N configuration. For 1-to-N connections, up to
32 units including the Serial Communications Board can be connected using a 2-wire connection. Using a 4-wire connection, up to 32 units can be connected with only the K3T @ .
2.
The maximum cable length is 500 m. Use shielded twisted-pair cables (AWG28i or greater).
3.
Connect terminating resistance at both ends of the transmission path.
4.
Turn the terminal block switch ON at the terminators.
5.
Turn the terminal block switches OFF for units that are not terminators.
289
K3T
@ Intelligent Signal Processor Protocol
Reset (by Unit Number) (Sequence No. 300)
This sequence performs the same processing as when an input is received on the reset terminal.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+33
~
Number of send data words
(Undefined)
(Undefined)
Number of units
Relevant unit No.
(Undefined) Relevant unit No.
~
Data Offset
+0
+1
+2
+33
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
Relevant unit No.
(2 digits BCD)
•
•
•
Relevant unit No.
(2 digits BCD)
0003 to 0034
00 to 32
00 to 99
00 to 99
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Reset Control (Continuous Units) (Sequence No. 301)
This sequence performs reset control for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Number of units
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
0002
00 to 32
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Appendix I
290
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Write Set Value (by Unit Number) (Sequence No. 302)
This sequence writes each set value (HH, H, L, LL).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+3
+4
+5
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
Number of units
Relevant unit No.
Operand
Set value
(Undefined)
Set value
+122
~
+123
+124
+125
(Undefined) Relevant unit No.
Operand
Set value
(Undefined)
~
Set value
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
Relevant unit No.
(2 digits BCD)
+3 Operand
(ASCII 2 characters)
+4 to +5 Set value
(5 digits BCD)
0006 to 0126
01 to 31
00 to 99
Data
4848 (“HH”),4C4C (“LL”)
4820 (“H”),4C20 (“L”)
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+4 2345 +4 1234
+5 0001
+5
000F
+124 to
+125
Set value
(5 digits BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
•
•
•
Same as above
Write Set Value HH (Continuous Units) (Sequence No. 303)
This sequence writes set value HH for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+64
~
+65
Number of send data words
(Undefined) Number of units
Set value
(Undefined)
Set value
(Undefined)
~
Set value
Set value
291
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
+2 to +3 Set value
(5 digits BCD)
0004 to 0066
01 to 32
Data
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+2 2345 +2 1234
+3
0001 +3 000F
+64 to
+65
Set value
(5 digits BCD)
•
•
•
Same as above
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Set Value H (Continuous Units) (Sequence No. 304)
This sequence writes set value H for continuous units. The word allocation is identical to that of sequence No.
303 (Write Set Value HH (Continuous Units)).
Write Set Value L (Continuous Units) (Sequence No. 305)
This sequence writes set value L for continuous units. The word allocation is identical to that of sequence No.
303 (Write Set Value HH (Continuous Units)).
Write Set Value LL (Continuous Units) (Sequence No. 306)
This sequence writes set value LL for continuous units. The word allocation is identical to that of sequence No.
303 (Write Set Value HH (Continuous Units)).
Write Set Value with Bank (by Unit Number) (Sequence No. 307)
This sequence writes set value of a bank which is not in use (K3TR: HH to LL, K3TC:O1 to O5).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+4
+5
+6
+0
+1
+2
+3
Number of send data words
(Undefined)
(Undefined)
Number of units
Relevant unit No.
(Undefined)
Operand
Bank No.
Set value
(Undefined)
Set value
+122
~
+123
+124
+125
+126
(Undefined) Relevant unit No.
(Undefined)
Operand
Bank No.
Set value
(Undefined)
~
Set value
292
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
Relevant unit No.
(2 digits BCD)
Bank No.
(2 digits BCD)
Operand
(Two ASCII characters)
0007 to 0127
01 to 25
00 to 99
01 to 04
Data
4848 (“HH”), 4F31 (“O1”)
4820 (“H ”), 4F32 (“O2”)
4C20 (“L ”),
4C4C (“LL”),
4F35 (“O5”)
4F33 (“O3”)
4F34 (“O4”)
+5 to +6 Set value
(5 digits BCD)
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+5
+6
2345
0001
+5
+6
1234
000F
+125 to
+126
Set value
(5 digits BCD)
•
•
•
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Same as above
Write Set Value HH with Bank (Continuous Units)
(Sequence No. 308)
This sequence writes set value HH of a bank not in use for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Number of units
(Undefined)
Bank No.
(Undefined)
Set value
Set value
+95
~
+96
+97
(Undefined)
Set value
Bank No.
(Undefined)
~
Set value
293
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
+2 Bank No.
(2 digits BCD)
+3 to +4 Set value
(5 digits BCD)
0004 to 0098
01 to 32
01 to 04
Data
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+2 2345 +2 1234
+3 0001 +3 000F
+96 to
+97
Set value
(5 digits BCD)
•
•
•
Same as above
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Set Value H with Bank (Continuous Units)
(Sequence No. 309)
This sequence writes set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value L with Bank (Continuous Units)
(Sequence No. 310)
This sequence writes set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value LL with Bank (Continuous Units)
(Sequence No. 311)
This sequence writes set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O5 with Bank (Continuous Units)
(Sequence No. 312)
This sequence writes set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O4 with Bank (Continuous Units)
(Sequence No. 313)
This sequence writes set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O3 with Bank (Continuous Units)
(Sequence No. 314)
This sequence writes set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
294
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Write Set Value O2 with Bank (Continuous Units)
(Sequence No. 315)
This sequence writes set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O1 with Bank (Continuous Units)
(Sequence No. 316)
This sequence writes set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Read Set Value (by Unit Number) (Sequence No. 317)
Reads set value HH, H, L, or LL.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+64
~
+65
Number of send data words
(Undefined)
Number of units
(Undefined)
Relevant unit No.
Operand
(Undefined)
Relevant unit No.
Operand
~
Data Offset
+0
+1
+2
+3
+64 to
+65
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
Relevant unit No.
(2 digits BCD)
Operand
(ASCII 2 characters)
•
•
•
Operand
(ASCII 2 characters)
0004 to 0066
01 to 32
00 to 99
4848 (“HH”),4C4C (“LL”)4F31 (“01”)
4820 (“H”),4C20 (“L”)4F35 (“05”)
Same as above
Receive Data Word Allocation (3rd Operand of PMCR))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
(Undefined)
Set value
End code
(Undefined)
+94
~
+95
+96
(Undefined)
Set value
End code
(Undefined)
~
Set value
Set value
295
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Offset
+0
Contents (data format)
Number of receive data words
(4 digits BCD)
End code (2 digits Hex) +1
+2 to +3 Set value
(5 digits BCD)
Data
0004 to 0097
00 to 22
00000 to 99999
Negative sign: F (most significant digit)
Example 12345
Example
−
1234
+2 2345 +2 1234
+3
0001
+3
000F
•
•
•
+95 to
+96
Set value
(5 digits BCD)
Same as above
Read Set Value HH (Continuous Units) (Sequence No. 318)
This sequence reads set value HH for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (2 digits BCD)
0002
01 to 32
Data
Receive Data Word Allocation (3rd Operand of PMCR)
This sequence is similar to sequence No. 317 (Read Set Value (by Unit Number)).
Read Set Value H (Continuous Units) (Sequence No. 319)
This sequence reads set value H for continuous units. The word allocation is identical to that of sequence No.
318 (Read Set Value HH (Continuous Units)).
Read Set Value L (Continuous Units) (Sequence No. 320)
This sequence reads set value L for continuous units. The word allocation is identical to that of sequence No.
318 (Read Set Value HH (Continuous Units)).
Read Set Value LL (Continuous Units) (Sequence No. 321)
This sequence reads set value LL for continuous units. The word allocation is identical to that of sequence No.
318 (Read Set Value HH (Continuous Units)).
296
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Read Set Value with Bank (by Unit Number) (Sequence No. 322)
Reads the set value of a bank which is not in use (K3TR: HH to LL, K3TC:01 to 05) and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
(Undefined)
Number of units
Relevant unit No.
(Undefined)
Bank No.
Operand
+4
+95
~
+96
+97
(Undefined)
(Undefined)
Relevant unit No.
Bank No.
Operand
~
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (2 digits BCD)
Relevant unit No. (2 digits BCD)
Bank No. (2 digits BCD)
Operand (ASCII 2 characters)
0005 to 0098
Data
01 to 32
00 to 99
01 to 04
4848 (“HH”), 4F31 (“O1”)
4820 (“H ”), 4F32 (“O2”)
4C20 (“L ”),
4C4C (“LL”),
4F35 (“O5”)
4F33 (“O3”)
4F34 (“O4”)
+ 97
•
•
•
Operand (ASCII 2 characters) Same as above
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+63
+64
~
Number of receive data words
Set value
(Undefined)
Set value
(Undefined)
~
Offset
+0
Contents (data format)
Number of receive data words
(4 digits BCD)
+1 to +2 Set value
(5 digits BCD)
Set value
Set value
0003 to 0065
Data
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+1 2345 +1 1234
+2 0001
+2
000F
•
•
•
+63 to
+64
Set value
(5 digits BCD)
Same as above
297
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Read Set Value HH with Bank (Continuous Units)
(Sequence No. 323)
This sequence reads set value HH of a bank not in use for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
Number of units
Bank No.
+33
~
(Undefined) Bank No.
~
Offset
+0
+1
+2
+ 33
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (2 digits BCD)
Bank No. (2 digits BCD)
•
•
•
Bank No. (2 digits BCD)
0003 to 0034
01 to 32
01 to 04
Same as above
Data
Receive Data Word Allocation (3rd Operand of PMCR)
The word allocation is similar to sequence No. 322 (Read Set Value with Bank (by Unit Number)).
Read Set Value H with Bank (Continuous Units)
(Sequence No. 324)
This sequence reads set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value L with Bank (Continuous Units)
(Sequence No. 325)
This sequence reads set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value LL with Bank (Continuous Units)
(Sequence No. 326)
This sequence reads set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O5 with Bank (Continuous Units)
(Sequence No. 327)
This sequence reads set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O4 with Bank (Continuous Units)
(Sequence No. 328)
This sequence reads set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
298
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Read Set Value O3 with Bank (Continuous Units)
(Sequence No. 329)
This sequence reads set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O2 with Bank (Continuous Units)
(Sequence No. 330)
This sequence reads set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O1 with Bank (Continuous Units)
(Sequence No. 331)
This sequence reads set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Holding Data (Sequence No. 332)
Reads the peak/bottom data (maximum, minimum) and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+64
~
+65
Number of send data words
(Undefined)
Number of units
(Undefined) Relevant unit No.
Operand
(Undefined) Relevant unit No.
~
Operand
Data
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (2 digits BCD)
Relevant unit No. (2 digits BCD)
Operand (ASCII 2 characters)
0004 to 0066
01 to 32
00 to 99
5048 (“PH”)
4248 (“BH”)
+65
•
•
•
Operand (ASCII 2 characters) Same as above
299
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Peak/bottom data
(Undefined)
(Undefined)
Status
+94
~
+95
+96
Peak/bottom data
(Undefined)
(Undefined) Status
~
Offset
+0
Contents (data format)
Number of receive data words
(4 digits BCD)
+1 to +2 Peak/bottom data
(5 digits BCD)
Peak/bottom data
Peak/bottom data
0004 to 0097
Data
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+1 2345 +1 1234
+2
0001
+2
000F
+3 Status
(2 digits Hex) d0 bit:
If overflow: 1 d1 bit:
If underflow: 1 d4 bit:
Not used d5 bit:
During hold input: 1
Others: 0
Others: 0 d2 bit:
Not used d3 bit:
During forced zero operation: 1 Others: 0
(K3TH,K3TR: 0)
Others: 0 d6 bit:
Bank input 1: 1
(K3TH, K3TX: 0) d7 bit:
Bank input 2: 1
(K3TH, K3TX: 0)
Others: 0
Others: 0
•
•
•
+96 Status Same as above
Read Holding Data PH (Continuous Units) (Sequence No. 333)
This sequence reads peak holding data for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Number of units
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (2 digits BCD)
0002
01 to 32
Receive Data Word Allocation (3rd Operand of PMCR)
The data allocation is similar to sequence No. 332 (Read Holding Data (by Unit Number)).
300
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Read Holding Data BH (Continuous Units) (Sequence No. 334)
This sequence reads bottom holding data for continuous units. The word allocation is identical to that of sequence No. 333 (Read Holding Data PH (Continuous Units)).
Read Display Value (PV) (by Unit Number) (Sequence No. 335)
Reads the display value (PV) and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+33
~
Number of send data words
(Undefined)
Number of units
(Undefined)
Relevant unit No.
(Undefined)
Relevant unit No.
~
Data Offset
+0
+1
+2
+ 33
Contents
(data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
Relevant unit No.
(2 digits BCD)
•
•
•
Relevant unit No.
(2 digits BCD)
0003 to 0034
01 to 32
00 to 99
00 to 99
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+94
+95
+96
~
Number of receive data words
Display value
(Undefined)
Status
Display value
(Undefined)
Status
~
Display value
Display value
301
K3T
@ Intelligent Signal Processor Protocol
Offset Contents (data format)
+0 Number of receive data words
(4 digits BCD)
+1 to +2 Display value
(5 digits BCD)
+3 Status (4 digits Hex)
Appendix I
Data
0004 to 0097
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example
−
1234
+1 2345 +1 1234
+2
0001 +2 000F d0 bit:
If overflow: 1 d1 bit:
If underflow: 1
Others: 0
Others: 0 d2 bit:
Not used d3 bit:
During forced zero operation: 1 Others: 0
(K3TH, K3TR, K3TC: 0) d4 bit:
In test mode: 1 d5 bit:
While holding input: 1 d6 bit:
Bank input 1: 1
(K3TH, K3TX: 0) d7 bit:
Bank input 2: 1
(K3TH, K3TX: 0)
Others: 0
Others: 0
Others: 0
Others: 0 d8 bit:
LL comparison output: 1 Others: 0
OUT1 comparison output: 1 (K3TC) d9 bit:
L comparison output: 1 Others: 0
OUT2 comparison output: 1 (K3TC) d10 bit:
H comparison output: 1 Others: 0
OUT4 comparison output: 1 (K3TC) d11 bit:
HH comparison output: 1 Others: 0
OUT5 comparison output: 1 (K3TC) d12 bit:
PASS comparison output: 1 Others: 0
OUT3 comparison output: 1 (K3TC) d13 bit: Not used d14 bit: Not used d15 bit: Not used
+96
•
•
•
Status (4 digits BIN) Same as above
302
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Read Display Value (PV) (Continuous Units) (Sequence No. 336)
This sequence reads display value (PV) for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Number of units
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
0002
01 to 32
Receive Data Word Allocation (3rd Operand of PMCR)
This sequence is similar to sequence No. 335 (Read Display Value (PV) (Continuous Units)).
Model Data Read (by Unit Number) (Sequence No. 337)
Reads model data and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+26
~
Number of send data words
(Undefined)
Number of units
(Undefined)
Relevant unit No.
(Undefined)
Relevant unit No.
~
Data Offset
+0
+1
+2
+ 26
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
Relevant unit No.
(2 digits BCD)
•
•
•
Relevant unit No.
(2 digits BCD)
0003 to 0027
01 to 25
00 to 99
Same as above
Note The number of Units can be up to 25 maximum.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
Input specifications
Input specifications Display specifications
Output specifications
Input contents
Operation mode
+121
~
+122
+123
Input specifications
Input specifications
Display specifications
Output specifications
Input contents
~
+124
+125
Operation mode
303
K3T
@ Intelligent Signal Processor Protocol
Appendix I
Offset
+0
+1 to
+ 2
+2
+3
+4
+5
+125 ters)
Contents (data format)
Number of receive data words
(4 digits BCD)
Input specifications (ASCII 3 charac-
0006 to 0126
Data
Display specifications (ASCII 1 character)
Output specifications (ASCII 2 characters)
Input contents
(ASCII 2 characters)
Operation mode
(ASCII 2 characters)
544131 (“TA1”) (K3TH)
544231 (“TB1”) (K3TH)
564432 (“VD2”) (K3TX)
414432 (“AD2”) (K3TX)
564132 (“VA2”) (K3TX)
414132 (“AA2”) (K3TX)
524231 (“RB1”) (K3TR, K3TC)
41 (“A”) (common)
42 (“B”) (K3TH, K3TX)
43 (“C”) (K3TR, K3TC)
5331 (“S1”) (RS-232C)
5332 (“S2”) (RS-485)
5333 (“S3”) (RS-422A)
5335 (“S5”) (RS-485 + comparison output)
5336 (“S6”) (RS-422A + comparison output)
Leftmost digit: 30 (“0”) to 31 (“1”)
Rightmost digit: 31 (“1”) to 45 (“E”)
3030 (“00”) (K3TH, K3TX)
3031 (“00”) to 3133 (“12”) (K3TR)
5542 (“UB”) (K3TC)
5543 (“UC”) (K3TC)
•
•
•
Operation mode
(ASCII 2 characters)
Same as above
Model Data Read (Continuous Units) (Sequence No. 338)
This sequence reads model data for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(2 digits BCD)
0002
01 to 25
Data
Note The number of Units can be up to 25 maximum.
Receive Data Word Allocation (3rd Operand of PMCR)
The work allocation is similar to sequence No. 337 (Model Data Read (by Unit Number)).
304
K3T
@ Intelligent Signal Processor Protocol
Appendix I
General-purpose Command (Sequence No. 339)
Sends the specified data and writes the receive data to the receive data words. The characters such as “@”,
FCS, terminators need not be set in the send and receive data words. These characters will be automatically added for transmission and automatically removed before saving data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+127
~
Number of send data words
Send data byte length
Send data
Send data
Send data
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Send data byte length (4 digits BCD)
0003 to 0128
Data
+2 to
+127
Send data (ASCII)
0001 to 0251
Number of bytes of send data not including
@, the FCS, and the terminator.
ASCII code
Send data: 251 characters max.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+126
~
Number of receive data words
Receive data
Receive data
Receive data
Receive data
~
Offset
+0
+1 to
+126
Contents (data format)
Number of receive data words
(4 digits BCD)
Receive data (ASCII)
0001 to 0127
Data
ASCII code
Receive data: 251 characters max.
305
Appendix J
V500/V520 Bar Code Reader Protocol
The V500/V520 Bar Code Reader Protocol is used to make various settings or control remotely the Bar Code
Reader connected the Serial Communications Board via RS-232C cable.
307
V500/V520 Bar Code Reader Protocol
Appendix J
Protocol Configuration
The configuration of the V500/V520 Bar Code Reader Protocol is shown below.
Sequence
No.
Communications sequence name
Function
350
351
352
353
354
355
356
357
358
359
360
BCR read start
BCR read stop
Data read
Complete data read
BCR function write
(V500)
BCR function read
(V500)
Log data output request
(V500)
Preset data set (V500)
BCR connection confirmation (V500)
Log data clear (V500)
Continuous data read
(scan) (V500)
Instructs the Reader to start a BCR read.
Instructs the Reader to stop a BCR read.
Data read by the Reader is received and saved in the receive words.
Instructs the Reader to start a read. After the data read by the Reader is received and saved to the receive words, reading is stopped.
Writes the operation mode and read functions.
Reads the operation mode and read functions.
Requests output of log data sent to host.
Writes preset data.
Confirms if the Reader is correctly set.
Ladder interface
Send word allocation
Receive word allocation
No
No
No
No
No
Yes
No
Yes
No
Yes
Yes
No
No
No
Yes
No
Yes
Yes
No
No
No
Yes
361
362
363
364
365
366
Continuous data read
(interrupt) (V500)
BCR initialize
Continuous data read
(scan) (V520)
Continuous data read
(interrupt) (V520)
General-purpose command 1
General-purpose command 2
Clear log data.
Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method.
Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt
No.100).
Clears the log, confirms BCR connection, and sets BCRs.
Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method.
Performing the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt
No.100).
Used to send data of a specified data length, and receive only ACK as the receive data.
Used to send data of a specified data length, and receive ACK together with the return of other receive data. The frame format of the receive data, however, has to contain STX and ETX.
No
Yes
No
No
Yes
Yes
Yes
No
Yes
Yes
No
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
308
V500/V520 Bar Code Reader Protocol
Connections
The connections for using the V500/V520 Bar Code Reader Protocol are shown below.
V500 Connections
100 VAC
V520-R12
@
CQM1H
Reader
Serial Communications Board
RS-232C port
V500-C11
ID Controller
Appendix J
Serial Communications Board:
D-sub 9 pin female
Signal
Name
Pin No.
V509-W040
Reader Cable
V500-C11:
D-sub 9 pin female
Pin No.
Signal
Name
V520 Connections
Serial Communications Board
CQM1H
Serial Communications Board
RS-232C port
Serial Communications Board:
D-sub 9 pin female
Signal
Name
Pin No.
V520-R121
Reader
V509-W011
Reader Cable
V520-R121:
D-sub 9 pin female
Pin No.
Signal
Name
309
V500/V520 Bar Code Reader Protocol
Appendix J
System Setting
Shown below are the system settings of the V500-C11 and V520-R121 when this protocol is used.
Note The portions enclosed by in boxes are used for this protocol.
V500-C11
• BCR Functions
Read trigger
"READ SIGNAL INPUT", "ONLINE READ COMMAND"
Read control method
"SINGLE READ", "CONTINUOUS READ"
• Host Interface
Prefix
Suffix
Bar code output
NONE, "STX"
"ETX" , "CR "
"OUTPUT" , "NO OUTPUT"
V520-R121
Start code
Stop code
Operation mode
Data output mode
NONE, "STX"
"ETX" , "CR"
External trigger, host trigger
1-shot, continuous
BCR Read Start (Sequence No. 350)
This sequence instructs the Bar Code Reader to start reading.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
BCR Read Stop (Sequence No. 351)
This sequence instructs the Bar Code Reader to stop reading.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
310
V500/V520 Bar Code Reader Protocol
Appendix J
Data Read (Sequence No. 352)
This sequence receives read data and saves it to the receive data storage words.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Read data
Read data
Read data
Read data
Read data
Read data
~
Offset
+0
+1 to
+16
Contents (data format)
Number of receive data words
(4 digits BCD)
Read data (ASCII)
0002 to 0017
Data
30 (‘0’) to 39 (‘9’), 41 (‘A’) to 5A (‘Z’),
3F (‘?’)
Up to 32 characters in ASCII
Note The reception wait time is not set for this sequence.
Complete Data Read (Sequence No. 353)
This sequence instructs the Bar Code Reader to start reading, receives the data read by the Bar Code Reader, stores the data in the receive data storage words, and then instructs the Reader to stop reading.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
It is similar to sequence No. 352 (Data read).
Note The reception wait time is not set for this sequence.
BCR Function Write (V500) (Sequence No. 354)
This sequence sets the operation mode and read functions in the Bar Code Reader.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
Operation mode
Types of bar code
In-zone control
(Undefined)
(Undefined)
Number of digits
Modulus check
(Undefined)
(Undefined)
Buzzer
Number of matches
Multistep labels
Horizontal control
311
V500/V520 Bar Code Reader Protocol
Appendix J
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
0007 (fixed)
Data
+2
+4
(ASCII 1 character)
In-zone control
(ASCII 1 character)
Bar code type
(ASCII 1 character)
(2 digits BCD)
Modulus check
(ASCII 1 character)
41 (‘A’): ONLINE
*42 (‘B’): ONLINE CONTROL
*41 (‘A’): ON
42 (‘B’): OFF
41 (‘A’): JAN
42 (‘B’): NW7 NORMAL
43 (‘C’): NW7 SMALL
44 (‘D’): NW7 HEX
45 (‘E’): CODE39 NORMAL
46 (‘F’): CODE39 ST/SP OUTPUT
47 (‘G’): 2 of 5 (ITF)
48 (‘H’): CODE128
49 (‘I’): CODE93
4A (‘J’): 2 of 5 (3BAR)
4B (‘K’): 2 of 5 (5BAR)
00 to 32
00: Any number of digits allowed.
41 (‘A’): No-check
42 (‘B’): Modulus 10 (all bar codes)
43 (‘C’): Modulus 11 (except JAN)
44 (‘D’): Modulus 16 (NW7 only)
45 (‘E’): Modulus 43 (CODE39 only)
46 (‘F’): Modulus 47 (CODE93 only)
47 (‘G’): Modulus 103 (CODE128 only)
1 to 5 +5 Number of matches
(1 digit BCD)
Multistep labels
(1 digit BCD)
Buzzer
(ASCII 1 character)
1 to 4
+6
Horizontal control mode
(ASCII 1 character)
41 (‘A’): ON for normal read
42 (‘B’): ON for no-read
43 (‘C’): OFF
41 (‘A’): Normal (continuous rotating)
42 (‘B’): In-zone startup
Note Selecting the values marked with asterisks is required for this protocol.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
312
V500/V520 Bar Code Reader Protocol
Appendix J
BCR Function Read (V500) (Sequence No. 355)
This sequence reads the settings of functions in the Bar Code Reader.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
Operation mode
Types of bar code
In-zone control
(Undefined)
(Undefined)
Number of digits
Modulus check
(Undefined)
(Undefined)
Buzzer
Number of matches.
Multistep labels.
Horizontal control
Offset
+0
+2
+4
+5
+6
Contents (data format)
Number of receive data words
(4 digits BCD)
0007 (fixed)
Data
(ASCII 1 character)
In-zone control
(ASCII 1 character)
Bar code type
(ASCII 1 character)
41 (‘A’): ONLINE
42 (‘B’): ONLINE CONTROL
41 (‘A’): ON
42 (‘B’): OFF
41 (‘A’): JAN
42 (‘B’): NW7 NORMAL
43 (‘C’): NW7 SMALL
44 (‘D’): NW7 HEX
45 (‘E’): CODE39 NORMAL
46 (‘F’): CODE39 ST/SP Output
47 (‘G’): 2 of 5 (ITF)
48 (‘H’): CODE128
49 (‘I’): CODE93
4A (‘J’): 2 of 5 (3BAR)
4B (‘K’): 2 of 5 (5BAR)
00 to 32
(2 digits BCD)
Modulus check
(ASCII 1 character)
41 (‘A’): No-check
42 (‘B’): Modulus 10 (all bar codes)
43 (‘C’): Modulus 11 (except JAN)
44 (‘D’): Modulus 16 (NW7 only)
45 (‘E’): Modulus 43 (CODE39 only)
46 (‘F’): Modulus 47 (CODE93 only)
47 (‘G’): Modulus 103 (CODE128 only)
1 to 5 Number of matches
(1 digit BCD)
Multistep labels
(1 digit BCD)
Buzzer
(ASCII 1 character)
Horizontal control mode (ASCII
1 character)
1 to 4
41 (‘A’): ON for normal read
42 (‘B’): ON for no-read
43 (‘C’): OFF
41 (‘A’): Normal (continuous rotating)
42 (‘B’): In-zone startup
313
V500/V520 Bar Code Reader Protocol
Appendix J
Log Data Output Request (V500) (Sequence No. 356)
This sequence requests output of the log data sent to host.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units (2 digits BCD)
0002 (fixed)
01 to 99
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+125
+126
~
Number of receive data words
Log data
Log data
Log data
Log data
~
Offset
+0
+1 to
+126
Contents (data format)
Number of receive data words
(4 digits BCD)
Log data (ASCII)
0001 to 0127
Data
Log data with the number of designated data is stored including the separator GS (1D).
If the log data (including separator) exceeds 251 bytes, only 251 bytes are stored.
Note No retries are performed for this sequence.
314
V500/V520 Bar Code Reader Protocol
Appendix J
Preset Data Set (V500) (Sequence No. 357)
This sequence sets preset data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+18
~
+19
Number of send data words
(Undefined)
(Undefined)
(Undefined)
Number of units
Preset data
Preset data
Preset data
Preset data
~
Number of presets
Preset data No.
~
+(18N+2)
+(18N+3)
+(18N+4)
+(18N+5)
+(18N+18)
~
+(18N+19)
(Undefined)
(Undefined)
Number of units
Preset data
Preset data
~
~
Preset data
Preset data
Offset
+0
+1
+2
+3
+4 to
+19
Contents (data format)
Number of send data words
(4 digits BCD)
Number of presets
(1 digit BCD)
Preset data No.
(1 digit BCD)
Data length
(2 digits BCD)
Preset data (ASCII)
Preset data No.
Data
18N+2 (N is number of presets 1 to 5)
1 to 5
1 to 5
01 to 32
+20 to
+91
Combination of the following ASCII characters and up to 32 characters maximum:
30 (’0’) to 39 (’9’)
41 (’A’) to 5A (’Z’), 3F (’?’)
The area that is not used is undefined
Store repeatedly the contents of words with offsets +2 to +19 the same number of times as the number of presets
(N)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
BCR Connection Confirmation (V500) (Sequence No. 358)
This sequence confirms whether the Bar Code Reader is connected correctly or not.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
315
V500/V520 Bar Code Reader Protocol
Appendix J
Log Data Clear (V500) (Sequence No. 359)
This sequence clears the log data.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data Continuous Read (Scan) (V500) (Sequence No. 360)
This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data word allocation is similar to that of sequence No. 352 (Data read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Bar Code Reader still keeps reading. Execute sequence No. 351
(BCR read stop) to end the sequence.
Note The reception wait time is not set for this sequence.
Data Continuous Read (Interrupt) (V500) (Sequence No. 361)
This sequence performs the following operations repeatedly: Instruct the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation similar to that of sequence No. 352 (data read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Bar Code Reader keeps reading. Execute sequence No. 351 (BCR read stop) to end the sequence.
Note The reception wait time is not set for this sequence.
BCR Initialize (V500) (Sequence No. 362)
This sequence clears the log data, confirms BCR connection and sets the BCR functions.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of sequence No. 354 (BCR Function Set).
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data Continuous Read (Scan) (V520) (Sequence No. 363)
This sequence performs the following operations repeatedly: instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data.
Send Data Word Allocation (2nd Operand of PMCR)
None.
316
V500/V520 Bar Code Reader Protocol
Appendix J
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 352 (Data Read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR
Read Stop) to end the sequence.
3.
The reception wait time is not set for this sequence.
Data Continuous Read (Interrupt) (V520) (Sequence No. 364)
This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The send data word allocation is similar to that of sequence No. 352 (Data Read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR
Read Stop) to end the sequence.
3.
The reception wait time is not set for this sequence.
General-purpose Command 1 (Sequence No. 365)
This general-purpose command is used to send data with a specified data length, and receive back only ACK.
STX and ETX are automatically attached to the send data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+127
~
+128
Number of send data words
Send data byte length
Send data
Send data
Send data
Send data
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Send data byte length
(4 digits BCD)
+2 to
+128
Send data (ASCII)
0003 to 0129
Data
0001 to 0254
The byte length of the send data excluding STX and ETX.
Inscribe send data up to 254 bytes
(max.) by ASCII.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
317
V500/V520 Bar Code Reader Protocol
Appendix J
General-purpose Command 2 (Sequence No. 366)
This general-purpose command is used to send data with a specified data length, and receive back ACK in addition to other receive data. The frame format of the receive data, however, has to contain STX and ETX.
STX and ETX are automatically attached to the send data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+127
~
+128
Number of send data words
Send data byte length
Send data
Send data
Send data
Send data
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Send data byte length
(3 digits BCD)
+2 to
+128
Send data (ASCII)
0003 to 0129
Data
1 to 254
The byte length of the send data excluding STX and ETX.
Set send data up to 254 bytes (max.) by ASCII.
Receive Data Storage Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+126
~
+127
Number of receive data words
Receive data
Receive data
Receive data
Receive data
~
Offset
+0
+1 to
+127
Contents (data format)
Number of receive data words
(4 digits BCD)
Receive data (ASCII)
0001 to 0128
Data
If the receive data exceed 253 bytes, only 253 bytes are stored.
Note Shown below is the receive data frame format. The reception data without ACK, STX, and ETX is stored.
Receive data (253 bytes max.)
ACK
STX ETX
318
Appendix K
3Z4L Laser Micrometer Protocol
The 3Z4L Laser Micrometer Protocol is used to make various settings or control remotely the Laser Micrometer connected to the Serial Communications Board via RS-232C cable.
Protocol Configuration
The configuration of the 3Z4L Laser Micrometer Protocol is shown below.
Sequence
No.
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
Communications sequence name
Function
3Z4L clear
Memory switch set mm unit set
E unit set
Calibration set
Calibration release
Statistic processing execution
(3000-series)
Statistic processing non-execution (3000-series)
All statistic memory clear
(3000-series)
Resets errors, data, analog output, decision result and places the Laser Micrometer into standby.
Sets memory switches and the area for the work position LED.
Sets the display unit to mm.
Sets the display unit to E.
Calibrates the Laser Micrometer.
Calibration setting release.
Releases the calibration of the Laser
Micrometer.
Switches the program number to a specified number.
Sets measurement conditions.
Program number set (3000series)
Measurement condition set
(3000-series)
Measurement condition release (3000-series)
Measurement condition list request (3000-series)
Single run measurement start
(3000-series)
Zero run measurement start
(3000-series)
Continuous measurement start
(scan) (3000-series)
Continuous measurement start
(interrupt) (3000-series)
Measurement termination
(3000-series)
Data request (3000-series)
Releases measurement conditions that have been set.
Requests the measurement conditions that have been set and other settings.
When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results.
If the sample measurement condition is zero, starts a zero run measurement.
Starts a continuous measurement. The scan notification method is used for receive data.
Starts a continuous measurement. The interrupt notification method is used for receive data.
Measurement termination (3000-series)
Terminates a continuous measurement.
Requests display data in the idle measurement status or the latch data generated by the measurement command.
Lights the statistic processing LED and processes the statistics.
Turns OFF the statistic processing LED.
Statistics are not processed.
Clears statistic processing memories of all programs.
Ladder interface
Send word allocation
Receive word allocation
No No
Yes
No
No
Yes
No
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
No
Yes
Yes
No
*1
Yes
No
No
No
319
3Z4L Laser Micrometer Protocol
Appendix K
Sequence
No.
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
Communications sequence name
Function
Statistic memory clear (3000series)
Statistic result request (3000series)
Memory switch set 1 (3000series)
Memory switch set 2 (3000series)
Simple AVG times set (3000series)
AVG move interval set (3000series)
AVG move (H) times set (3000series)
AVG move (L) times set (3000series)
Automatic detection set (3000series)
Automatic detection release
(3000-series)
Automatic detection list request (3000-series)
3Z4L initialize (3000-series)
Clears statistic processing memories of program under display.
Requests statistic processing result.
Sets memory switches.
Sets memory switches.
Taking the simple average as the averaging method, sets the averaging times per measurement interval 4.
Taking the average move as the averaging method, sets the measurement interval number.
Taking the average move and high-speed data output as the averaging method, sets the averaging times per measurement interval 4.
Taking the average move and low-speed data output as the averaging method, sets the averaging times per measurement interval 4.
Sets work automatic detection function.
Releases the settings of work automatic detection function.
Requests the settings of work automatic detection function.
Clears the 3Z4L, sets the mm unit, sets the memory unit, does not processes statistics, and clears all statistic memory.
Sets measurement conditions.
Measurement condition set
(4000-series)
Measurement condition release (4000-series)
Measurement condition list request (4000-series)
Single run measurement start
(4000-series)
Releases measurement conditions that have been set.
Requests the measurement conditions that have been set and other settings.
When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results.
Starts a deflection measurement.
Deflection measurement start
(4000-series)
Continuous measurement start
(scan) (4000-series)
Continuous measurement start
(interrupt) (4000-series)
Starts a continuous measurement. The scan notification method is used for receive data.
Starts a continuous measurement. The interrupt notification method is used for receive data.
Terminates continuous measurement.
Measurement termination
(4000-series)
Data request (4000-series)
Forced positive zero (4000series)
Forced negative zero (4000series)
Requests measurement data in the idle measurement status or the latch data generated by the measurement command.
Sets the forced zero direction to positive
(+).
Sets the forced zero direction to negative
(–).
Ladder interface
Send word allocation
Receive word allocation
No No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
No
Yes
No
No
No
Yes
Yes
No
Yes
Yes
No
*1
Yes
No
No
320
3Z4L Laser Micrometer Protocol
Appendix K
Sequence
No.
Communications sequence name
Function
442 Forced zero release (4000series)
3Z4L initialize (4000-series)
Releases the forced zero direction.
443
444
445
General-purpose command 1 Used to send data of a specified data length, and receive only OK as the receive data.
General-purpose command 2 Used to send data of a specified data length, and receive data other than OK.
*1Depends on the measurement contents.
Clears the 3Z4L, sets the mm unit, and clears the memory unit settings.
Ladder interface
Send word allocation
Receive word allocation
No No
Yes
Yes
Yes
No
No
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
Connections
The connections for the 3Z4L Laser Micrometer Protocol are shown below.
RS-232C Connection
Sensor
Signal cable
CQM1H
Serial Communications Board
RS-232C Port
Controller
Serial Communications Board:
D-sub 9 pin (female)
Signal name
Pin No.
FG
SD
RD
RS
CS
DR
ER
SG
5
7
8
9
1
2
3
4
Controller: D-sub
25 pin (female)
Pin No.
Signal name
5
6
7
20
1
2
3
4
FG
TXD
RXD
RTS
CTS
DSR
SG
DTR
321
3Z4L Laser Micrometer Protocol
Appendix K
DIP Switch Settings
Shown below are the settings of 3Z4L-3000, 3Z4L-4000-series DIP switches required to use the system protocol sequences.
3Z4L-3000 Series
• DIP Switch 1
1
4
5
2
3
6
No.
Setting
Baud rate
Status
ON/OFF
ON/OFF
Handshaking procedure ON/OFF
RS-232C interface use selection
ON/OFF
ON/OFF
ON/OFF
• DIP Switch 2
5
6
7
3
4
1
2
No.
8
Setting
Selection for measurement section
Status
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Setting of minimum read value
ON/OFF
ON/OFF
ON/OFF Setting of transparent body measurement function
Setting of simultaneous measurement function
ON/OFF
Set these settings according to the sensor connected.
Set these settings for
4 digits in the decimal portion.
• DIP Switch 3
3
4
5
1
2
No.
6
Setting
Setting of measurement function by 2 measurement instruments
Status
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF Error data exclusion function
Multistep selection function
ON/OFF
This protocol does not support the error data exclusion function
3Z4L-4000 Series
• DIP Switch 1
6
7
4
5
1
2
3
8
No.
Setting
Baud rate
Status
ON/OFF
ON/OFF
Hand-shake procedure ON/OFF
Delimiter
RS-232C interface use selection
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
322
3Z4L Laser Micrometer Protocol
Appendix K
• DIP Switch 2
6
7
8
4
5
2
3
1
No.
Setting
Selection for measurement section
Setting of minimum read value
Display unit
External command setting
Status
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Set these settings according to the sensor connected.
Set these settings for
4 digits in the decimal portion.
Delimiter Control Code Setting
3Z4L-4000 Series
The delimiter control codes must be set on DIP switch SW1 for the 3Z4L-4000 Series. Turn off pins 4 and 5, set the delimiter codes to CR+LF, and set the delimiter code control setting in the sequence to CR+LF. See the setting for CR+LF in the following diagram.
1 2 3 4 5 6 7 8
Turn OFF.
Turn OFF (to use a general-purpose interface)
Turn ON (to use a general-purpose interface)
Delimiter Setting
Pin
Delimiter
CR+LF
Pin 4
OFF
Pin 5
OFF
CR
ON
OFF
Handshaking
ON: Control (recognize DRT input)
OFF: 3-wire method (non-protocol)
LF
OFF
ON
Baud Rate
Pin
Baud rate
1200 2400 4800 9600
Pin 1
OFF
ON OFF ON
Pin 2 OFF
OFF
ON
ON
323
3Z4L Laser Micrometer Protocol
Appendix K
3Z4L-3000 Series
The delimiter control code does not need to be set on the DIP switch for the 3Z4L-3000 Series. Set the delimiter control codes in the sequence to CR+LF for the send code and to CR or CR+LF for the receive code. See the settings in the following diagram.
1 2 3 4 5 6
Turn OFF.
Turn OFF (to use a general-purpose interface)
Turn ON (to use a general-purpose interface)
Handshaking
ON: Control (recognize DRT input)
OFF: 3-wire method (non-protocol)
Baud Rate
Pin
Baud rate
1200 2400
4800
9600
Pin 1
OFF
ON OFF ON
Pin 2 OFF
OFF ON
ON
The High-speed 3Z4L-3000-series Meters must have the delimiter control codes set using the memory switches. Set both the send and receive codes to CR+LF.
3Z4L Clear (Sequence No. 400)
This sequence resets errors, data, analog output, and decision result, and puts the Laser Micrometer into standby.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
324
3Z4L Laser Micrometer Protocol
Appendix K
Memory Switch Set (Sequence No. 401)
This sequence sets memory switches and the area for the work position LED.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
W
Number of send data words
X
(Undefined)
Y Z
V
Offset Contents
(data format)
+0
3000-series
0003 (fixed)
+1
Number of send data words (4 digits BCD) w (1 digit BCD)
+2 x (1 digit BCD) y (1 digit BCD) z (1 digit BCD) v (1 digit BCD)
Data
4000-series
0003 (fixed)
Using buzzer sound: 0 to 3 Number of digits for extinguishing indicator: 0 to 2
Automatic latch release time:
0 to 9
I/O IF RUN Input: 0 or 1
Display of Err-0: 0 or 1 Using print timer, the setting for simultaneous measurement: 0 to 3 (high-speed), 0 to 1 (other)
Display of the comma for 1/
1000s digit, number of display digits: 0 to 5 (highspeed), 0 to 3 (other)
Measurement interval 4: 0 to
6
Averaging method: 0 to 2
(high-speed), 0 (other)
Use of comma: 0 or 1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
mm Unit Set (Sequence No. 402)
This sequence sets the display unit to mm.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
E Unit Set (Sequence No. 403)
This sequence sets the display unit to E.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
325
3Z4L Laser Micrometer Protocol
Appendix K
Calibration Set (Sequence No. 404)
This sequence calibrates the Laser Micrometer.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
Decimal portion
(Undefined)
Sign
Decimal integer portion
(Undefined)
Decimal portion
(Undefined) (Decimal integer portion)
Sign (Undefined)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
HC gauge dimension (Decimal portion)
(4 digits BCD)
0007 (fixed)
0000 to 9999
High calibration gauge dimension
Low calibration gauge dimension
Data
Example
−
123.4567
+1
+2
+3
4 5 6 7
0 1 2 3
2 D 0 0
+2
+3
HC gauge dimension (integer portion)
(3 digits BCD)
HC gauge dimension (Sign)
(ASCII 1 character)
000 to 999 if +: 20(‘ ’) if –: 2D(‘–’)
+4 to +6 LC gauge dimensions
Example
−
123.4567
+1
+2
+3
4 5 6 7
0 1 2 3
2 D 0 0
Same as HC gauge dimensions
Note 1.
For this sequence, both the high and low calibration gauges must be set.
2.
The limit value, reference value, and offset value can be set to 3 digits for the integer portion and to
4 digits for the decimal portion.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Calibration Release (Sequence No. 405)
This sequence releases the calibration of the Laser Micrometer.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence releases both the high and low calibration.
326
3Z4L Laser Micrometer Protocol
Appendix K
Program Number Set (3000-series) (Sequence No. 406)
This sequence switches the program number to a specified number.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Program number (1 digit BCD)
Program number (1 digit BCD)
Data
0002 (fixed)
0 to 9
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Retry processing is not performed for this sequence.
Measurement Condition Set (3000-series) (Sequence No. 407)
This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+29
+13
+14
+15
+16
+17
+18
+5
+6
+7
+8
+9
+10
+11
+12
Number of send data words
(Unused)
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined) Integer portion
Sign (Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined) Integer portion
Sign (Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined) Integer portion
Sign (Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined) Integer portion
Sign (Undefined)
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
327
3Z4L Laser Micrometer Protocol
Appendix K
+47
+48
+49
+50
+51
+52
+53
+41
+42
+43
+44
+45
+46
+36
+37
+38
+39
+40
+30
+31
+32
+33
+34
+35
Decimal portion
Integer portion
(Undefined)
Sign
(Undefined)
(Undefined)
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
(Undefined)
(Undefined)
Schedule output timer
Sample measurement pulse
0
0
0
0
0
0
0
0
(Unused)
(Unused)
(Undefined)
Reference value (REF)
Analog output scale number (SCL)
Offset classification (OF)
Offset value
Data output conditions (PR)
(PRT)
(SMP)
Sample measurement classification
Setting Yes/No flags
+9 to
+11
+12 to
+14
+15 to
+17
+18 to
+20
+21 to
+23
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Unused +1
+2 to +4 Segment number
(ASCII 6 characters)
+5 Measurement interval number (1 digit BCD)
+6
+7
Lower limit value (decimal portion)
(4 digits BCD)
Lower limit value (Integer portion)
(3 digits BCD)
+8 Lower limit value (Sign)
(ASCII 1 character)
Upper limit value
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
+24 to
+26
+27 to
+29
+30 to
+32
Multistep selection limit value (L5)
Multistep selection limit value (L6)
Reference value
0054 (fixed)
Undefined
Data
Combination of 31(‘1’) to 36(‘6’), 20(‘ ’)
1 to 4
0000 to 9999
000 to 999 if +: 20(‘ ’) if –: 2D(‘–’)
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Example
−
123.4567
+6
+7
+8
4 5 6 7
0 1 2 3
2 D 0 0
328
3Z4L Laser Micrometer Protocol
Appendix K
Offset
+33
+34 to
+35
+36 to
+38
+39
Contents (data format)
Analog output scale number
(1 digit BCD)
Offset classification (ASCII 3 characters)
Offset value
1 to 3
4F4620 (“OF”), 4F4D20 (“OM”)
Same as lower limit values
Data
+40
+41
+42 to
+43
Data output conditions
(1 digit BCD)
Scheduled output timer
(3 digits BCD)
Sample measurement pulse
(3 digits BCD)
Sample measurement classification
(ASCII 3 characters)
Unused
0 to 6
000 to 999
000 to 999
415647 (“AVG”), 4D4158 (“MAX”)
4D494E (“MIN”), 524E47 (“RNG”)
Undefined +44 to
+45
+46
+47
+48
+49
+50
+51
+52
+53
Yes/No for segment setting
(1 digit BCD)
Set: 1 (SG)
Don’t set: 0
Yes/No for measurement interval number setting
(1 digit BCD)
Yes/No for upper/lower limit value setting
(1 digit BCD)
Yes/No for multistep selection limit value
(1 digit BCD)
Yes/No for reference setting
(1 digit BCD)
Don’t set: 0
Set:
Don’t set: 0
Set:
1 (LL,LH)
1 (L1,L2,L3,L4,L5,L6)
Don’t set: 0
Yes/No for offset value setting (1 digit BCD)
Yes/No for data output condition setting
(1 digit BCD)
Yes/No for sample measurement pulse setting
(1 digit BCD)
Set: 1 (REF, SCL)
Don’t set: 0
Set: 1 (OF or OM)
Don’t set: 0
Set: 1 (PR, PRT)
Don’t set: 0
Set: 1 (SMP, MAX or MIN or RNG or AVG)
Don’t set: 0
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
This sequence cannot be used to set the error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function).
2.
The following settings must be made together with this sequence; they cannot be set separately.
Lower limit, upper limit
Multistep selection limit
Reference value, analog output scale number
Data output conditions, scheduled print timer
3.
The limit value, reference value, and offset value can be set to 3 digits for the integer portion and to
4 digits for the decimal portion.
329
3Z4L Laser Micrometer Protocol
Appendix K
Measurement Condition Release (3000-series)
(Sequence No. 408)
This sequence releases the measurement conditions that have been set.
Send Data Word Allocation (2nd Operand of PMCR)
Send data word allocation is similar to that of sequence No. 407 (Measurement Condition Set). However, only the setting Yes/No flags at +46 to +53 from the send data leading word can be used.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
The following conditions are used when the measurement conditions are released: Segment becomes 1, measurement interval becomes 1, the number of sample measurement pulses becomes 1.
2.
The following conditions cannot be released with this sequence: error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function).
3.
The following settings cannot be released separately using this sequence.
Lower limit, Upper limit
Multistep selection limit
Reference value, analog output scale number
Data output conditions, scheduled print timer
Measurement Condition List Request (3000-series)
(Sequence No. 409)
This sequence requests the measurement condition settings that have been set and other settings.
Send Data Word Allocation (2nd Operand of PMCR)
None.
330
3Z4L Laser Micrometer Protocol
Appendix K
Receive Data Word Allocation (3rd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+21
+22
+23
+24
+25
+26
+27
+28
+29
+30
+31
+32
+33
+34
+35
+36
+37
+38
+39
+40
+41
+42
+43
+44
+45
+14
+15
+16
+17
+18
+19
+20
Number of receive data words
(Undefined)
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
Sign
(Undefined)
Sign
(Undefined)
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
(Undefined)
Sign
(Undefined)
(Undefined)
(Undefined)
Decimal portion
Integer portion
(Undefined)
Scheduled output timer
Sample measurement pulse
(Undefined)
(Undefined)
Program number (P)
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
Reference value (REF)
Analog output scale number (SCL)
Offset classification (OF)
Offset value (LH)
Data output condition (PR)
(PRT)
(SMP)
Sample measurement classification
Statistical processing calculation classification
331
3Z4L Laser Micrometer Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of receive data words (4 digits BCD)
Program number
(1 digit BCD)
+2 to +4 Segment number
(ASCII 6 characters)
+5 Measurement interval number (1 digit BCD)
+6
+7
Lower limit value (Decimal portion)
(4 digits BCD)
Lower limit value (Integer portion)
(3 digits BCD)
+8 Lower limit value (Sign)
(BIN)
Upper limit value +9 to
+11
+12 to
+14
+15 to
+17
+18 to
+20
+21 to
+23
+24 to
+26
+27 to
+29
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
Reference value +30 to
+32
+33
+34 to
+35
+36 to
+38
+39
Analog output scale number
(1 digit BCD)
Offset classification (ASCII 3 characters)
Offset value
+40
+41
+42 to
+43
+44 to
+45
Data output condition
(1 digit BCD)
Scheduled output timer
(3 digits BCD)
Sample measurement pulse
(3 digits BCD)
Sample measurement classification
(ASCII 3 characters)
Statistical processing calculation classification (ASCII 3 characters)
0046 (fixed)
0 to 9
1 to 4
0000 to 9999
000 to 999
1 to 3
4F4620 (“OF”), 4F4D20 (“OM”)
0 to 6
000 to 999
000 to 999
Data
Combination of 31(‘1’) to 36(‘6’), 20(‘ ’)
If +: 0
If – : F
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Example
+6
+7
+8
415647 (“AVG”), 4D4158 (“MAX”)
4D494E (“MIN”), 524E47 (“RNG”)
535420 (“ST”), 4E5354 (“NST”)
−
123.4567
4 5 6 7
0 1 2 3
F 0 0 0
Note This sequence cannot be used to request the lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function).
332
3Z4L Laser Micrometer Protocol
Appendix K
Single Run Measurement Start (3000-series) (Sequence No. 410)
When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data stor age words
+0
+1
+2
+3
+4
+5
+6
+7
+8
(Undefined)
Sign
Number of receive data words
(Undefined)
Decision result
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Program number
Measurement value
Deviation value
Offset
+0
+1
Contents (data format)
Number of receive data words (4 digit BCD)
Program number
(1 digit BCD)
Decision result
(ASCII 2 characters)
Data
With no reference setting: 0006
With reference setting: 0009
0 to 9
+2 With no limit setting: 0000
With limit setting: 2B4E (“+N”), 4F4B (“OK”),
2D4E (“–N”)
0000 to 9999
Example
−
123.4567
+3
+4
+5
Measurement value (decimal portion)
(4 digits BCD)
Measurement value (integer portion) (3 digits BCD)
Measurement value (Sign)
(BIN)
+6 to +8 Deviation value
000 to 999
If +: 0
If –: F
+3
+4
+5
4 5 6 7
0 1 2 3
F 0 0 0
Same as measurement value
*The deviation will be stored in this area only when reference setting is made.
Zero Run Measurement Start (3000-series) (Sequence No. 411)
If the sample measurement condition is zero, a zero run measurement is started.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note The zero run measurement keeps measuring until sequence No. 414 (Measurement Termination) is executed.
Continuous Measurement Start (Scan) (3000-series)
(Sequence No. 412)
A continuous measurement is started. The scan notification method is used for the receive data.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
333
3Z4L Laser Micrometer Protocol
Appendix K
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
414 (Measurement Termination) to end the sequence.
Continuous Measurement Start (Interrupt) (3000-series)
(Sequence No. 413)
A continuous measurement is started. The interrupt notification method is used for the receive data and the interrupt No. is 101.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
414 (Measurement Termination) to end the sequence.
Measurement Termination (3000-series) (Sequence No. 414)
This sequence terminates a continuous measurement.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
For continuous measurement: Not available
For Zero Run Measurement
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Data Request (3000-series) (Sequence No. 415)
This sequence requests display data in the idle measurement status or the latch data generated by the measurement command.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Statistic Processing Execution (3000-series)
(Sequence No. 416)
This sequence lights the statistic processing LED and implements the statistic processing.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
334
3Z4L Laser Micrometer Protocol
Appendix K
Statistic Processing Non-execution (3000-series)
(Sequence No. 417)
This sequence turns the statistic processing LED off and does not carry out the statistic processing.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
All Statistic Memory Clear (3000-series) (Sequence No. 418)
This sequence clears statistic processing memories of all programs.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Statistic Processing Memory Clear (3000-series)
(Sequence No. 419)
This sequence clears statistic processing memories of the program under display.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Statistic Result Request (3000-series) (Sequence No. 420)
This sequence requests the statistic processing results.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+6
+7
+8
+1
+2
+3
+4
+5
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
Number of receive data words
(Undefined)
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Program number (P)
Number of statistic data (N)
Average value (AVG)
Maximum value (MAX)
Minimum value (MIN)
Range (R)
Standard deviation (SD)
335
3Z4L Laser Micrometer Protocol
Appendix K
Offset
+0
+1
Contents
(data format)
Number of receive data words (4 digits BCD)
Program number
(1digit BCD)
0019 (fixed)
0 to 9
+2 to +3 Number of statistic data
(6 digits BCD)
+4 Average value (decimal portion) (4 digits BCD)
+5
+6
000000 to 999999
0000 to 9999
Average value (integer portion) (4 digits BCD)
000 to 999
Average value (Sign) (BIN) If +: 0
If –: F
+7 to +9 Maximum value
+10 to
+12
Minimum value
+13 to
+15
+16 to
+18
Range
Standard deviation
Same as average value
Same as average value
Same as average value
Same as average value
Data
Example
−
123.4567
+4
+5
+6
4 5 6 7
0 1 2 3
F 0 0 0
Note The number of digits of the Decimal portion is fixed to 4 digits. If a deviation calculation results in a value with 5 decimal places, it will be stored with one digit overflowing into the integer portion.
Examples: The value –0.1234 is stored as follows:
Area of decimal portion: 1234; Area of integer portion: 0000; Sign area: F000
The value –0.12345 is stored as follows:
Area of decimal portion: 2345; Area of integer portion: 0001; Sign area: F000
Memory Switch Set 1 (3000-series, High-speed Type)
(Sequence No. 421)
This sequence sets memory switches.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
W
Number of send data words
X
(Undefined)
Y Z
V
Offset
+0
Contents
(data format)
Number of send data words
(4 digits BCD) w (1 digits BCD)
0003 (fixed)
Data
+1 x (1 digit BCD) y (1 digit BCD) z (1 digit BCD)
0: For single run or zero run measurement start displaying ‘---.’
1: For single run or zero run measurement start displaying the previous measured value
0: Perform single run measurement to the RUN signal of I/O IF
1: Repeat measurement while the RUN signal of I/O
IF is input
*0: RS-232C Delimiter CR+LF
1: RS-232C Delimiter CR
2: RS-232C Delimiter LF
0: RS-232C no parity check
1: RS-232C odd parity check
2: RS-232C even parity check
+2 v (1 digit BCD) 0: Displaying ‘Err-0’
1: Displaying ‘0’
Note Settings marked with asterisks are required for this protocol.
336
3Z4L Laser Micrometer Protocol
Appendix K
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned
ON.
2.
The setting (y, z) of RS-232C takes effect when the power supply is turned back on.
Memory Switch Set 2 (3000-series, High-speed Type)
(Sequence No. 422)
This sequence sets memory switches.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
W
Number of send data words
X
(Undefined)
Y Z
V
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD) w (1 digit BCD)
0003 (fixed)
Data
+1
+2 x (1 digit BCD) y (1 digit BCD) z (1 digit BCD) v (1 digit BCD)
0: Work automatic detection is not performed
1: Work automatic detection is performed
Diameter detection method (1 scan)
2: Work automatic detection is performed
Diameter detection method (8 scan)
3: Work automatic detection is performed
Position detection method (1 scan)
For expansion
0 (fixed)
For expansion
0 (fixed)
For expansion
0 (fixed)
*0:Error data exclusion function is not used
1:Error data exclusion function is used
Note Settings marked with asterisks are required for this protocol.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
Simple AVG Times Set (3000-series, High-speed Type)
(Sequence No. 423)
This sequence uses the simple average as the averaging method and sets the averaging times per measurement interval 4.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
Number of averaging times
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of averaging times
(4 digits BCD)
0002 (fixed)
1 to 2048
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
337
3Z4L Laser Micrometer Protocol
Appendix K
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
AVG Move Interval Set (3000-series, High-speed Type)
(Sequence No. 424)
This sequence uses the average move as the averaging method and sets the measurement interval number.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
(Undefined)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Measurement interval number
(1 digit BCD)
Measurement interval number
Data
0002 (fixed)
1 to 4
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
AVG Move (H) Times Set (3000-series, High-speed Type)
(Sequence No. 425)
This sequence uses the average move and high-speed data output as the averaging method and sets the averaging times per measurement interval 4.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
Number of send data words
Number of averaging times
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of averaging times
(4 digits BCD)
0002 (fixed)
16 to 2048
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
AVG Move (L) Times Set (3000-series, High-speed Type)
(Sequence No. 426)
This sequence uses the average move and low-speed data output as the averaging method and sets the averaging times per measurement interval 4.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
Number of send data words
Number of averaging times
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Number of averaging times
(4 digits BCD)
0002 (fixed)
32 to 2048
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
338
3Z4L Laser Micrometer Protocol
Appendix K
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
Automatic Detection Set (3000-series, High-speed Type)
(Sequence No. 427)
This sequence sets the work automatic detection function.
Send Data Word Allocation (2nd Operand of PMCR)
Receive data storage words
+4
+5
+6
+7
+8
+0
+1
+2
+3
Number of send data words
(Undefined) The number of measuring times
Invalid time
Decimal portion
Integer portion
(Undefined)
Sign
Decimal portion
(Undefined)
(Undefined)
Sign
Integer portion
(Undefined)
Detection lower limit
Detection upper limit
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits BCD)
Number of measurements
(3 digits BCD)
Invalid time (4 digits BCD)
Detection lower limit (decimal portion)
(4 digits BCD)
+4
+5
Detection lower limit (integer portion)
(3 digits BCD)
Detection lower limit (Sign)
(ASCII 1 character)
+6 to +8 Detection upper limit
0009 (fixed)
001 to 999
0001 to 9999
0000 to 9999
000 to 999
Data
Example
If +: 20 (‘ ’)
If – : 2D (‘–’)
Same as detection lower limit
+3
+4
+5
−
123.4567
4 5 6 7
0 1 2 3
2 D 0 0
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
Automatic Detection Release (3000-series, High-speed Type)
(Sequence No. 428)
This sequence releases the setting of work automatic detection function.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
Automatic Detection List Request (3000-series, High-speed
Type) (Sequence No. 429)
This sequence requests the settings of work automatic detection function.
Send Data Word Allocation (2nd Operand of PMCR)
None.
339
3Z4L Laser Micrometer Protocol
Appendix K
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+4
+5
+6
+7
+8
+0
+1
+2
+3
(Undefined)
Sign
Number of receive data words
(Undefined) The number of measuring times
Invalid time
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Detection lower limit
Detection upper limit
Offset
+0
+1
+2
+3
Contents (data format)
Number of receive data words (4 digits BCD)
The number of measuring times
(3 digits BCD)
Invalid time
(4 digits BCD)
Detection lower limit (decimal portion)
(4 digits BCD)
+4
+5
Detection lower limit (integer portion)
(3 digits BCD)
Detection lower limit (Sign)
(BIN)
+6 to +8 Detection upper limit
0009 (fixed)
000 to 999
0001 to 9999
0000 to 9999
000 to 999
If +: 0
If –: F
Data
Example -123.4567
+3
+4
+5
Same as detection lower limit
4 5 6 7
0 1 2 3
F 0 0 0
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
3Z4L Initialize (3000-series) (Sequence No. 430)
This sequence clears the 3Z4L, sets the mm unit, sets memory switches, does not process statistics, and clears the statistic memory.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
340
3Z4L Laser Micrometer Protocol
Appendix K
Measurement Condition Set (4000-series) (Sequence No. 431)
This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
+23
+24
Number of send data words
(Undefined)
(Undefined)
Sign
(Undefined)
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
(Undefined)
(Unused)
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Reference value (REF)
Analog output scale number (SCL)
(Unused)
(Unused)
(Undefined)
(Undefined) Data output timer (BCD 3 digits)
(Undefined)
(PRT)
Number of seconds for latch timer (RLT)
0
Data output conditions (PR)
0
0
Setting Yes/No flags
0
0
0
341
3Z4L Laser Micrometer Protocol
Appendix K
Offset
+0
+1
+2
+3
+23
+24
Contents (data format)
Number of send data words
(4 digits BCD)
Segment number
(1 digit BCD)
Measurement interval number (1 digit BCD)
Lower limit value (Decimal portion)
(4 digits BCD)
+4
+5
+6 to +8 Upper limit value
+9 to
+11
Reference value
+12
Lower limit value (integer portion) (3 digits BCD)
Lower limit value (Sign)
(ASCII 1 character)
Analog output scale number
(1 digit BCD)
Unused +13 to
+15
+16
+17
Data output conditions
(1 digit BCD)
Data output timer value
(3 digits BCD)
+18
+19
+20
+21
Number of seconds for latch timer
(2 digits BCD)
Yes/No for segment setting
(1 digit BCD)
Yes/No for measurement interval number setting
(1 digit BCD)
Yes/No for upper/lower limit value setting
(1 digit BCD)
+22 Yes/No for reference setting
(1 digit BCD)
Yes/No for data output condition setting
(1 digit BCD)
Yes/No for latch timer setting
(1 digit BCD)
0025 (fixed)
1 to 5
1 to 7
0000 to 9999
000 to 999
Data
If +: 20 (‘ ’)
If – : 2D (‘–’)
Same as lower limit value
Same as lower limit value
0 to 3
0 to 6
000 to 999
00 to 99
Set: 1(SG)
Don’t set: 0
Set: 1(M)
Don’t set: 0
Set: 1(LL, LH)
Don’t set: 0
Set: 1(REF, SCL)
Don’t set: 0
Set: 1(PR, PRT)
Don’t set: 0
Set: 1(RLT)
Don’t set: 0
Example
−
123.4567
+3
+4
+5
4 5 6 7
0 1 2 3
2 D 0 0
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
The following settings must be made together with this sequence; they cannot be set separately.
Lower limit, upper limit
Reference value, data output timer
Data output conditions, scheduled print timer
2.
The limit value and reference value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion.
342
3Z4L Laser Micrometer Protocol
Appendix K
Measurement Condition Release (4000-series)
(Sequence No. 432)
This sequence clears the measurement conditions that have been set.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of sequence No. 431 (Measurement Condition Setting). However, only the setting Yes/No flags at +19 to +24 from the send data leading word can be used.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
The following conditions are used when the measurement conditions are released: Segment becomes 1 and the measurement interval becomes 1.
2.
The following settings cannot be cleared separately using this sequence. They all must be cleared at the same time.
Lower limit, Upper limit
Data output conditions, Scheduled print timer
The scale (SCL) and data output timer (PRT) cannot be cleared.
3.
This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned
ON.
Measurement Condition List Request (4000-series)
(Sequence No. 433)
This sequence requests the measurement condition settings that have been set and other settings.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+12
+13
+14
+15
+16
+17
+18
+4
+5
+6
+7
+0
+1
+2
+3
+8
+9
+10
+11
Number of receive data words
(Undefined)
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
(Undefined)
Integer portion
(Undefined)
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Reference value (REF)
Analog output scale number (SCL)
Forced zero number (ZERO+)
(Undefined)
(Undefined)
(Undefined)
(Undefined)
Data output timer (BCD 3 digits)
Data output condition (PR)
(PRT)
Number of seconds for latch timer (RLT)
343
3Z4L Laser Micrometer Protocol
Appendix K
Offset
+0
+1
+2
+3
Contents (data format)
Number of receive data words (4 digits BCD)
Segment number
(1 digit BCD)
Measurement interval number (1 digit BCD)
Lower limit value (Decimal portion)
(4 digits BCD)
+4
+5
+13 to
+15
Lower limit value (Integer portion)
(3 digits BCD)
Lower limit value (Sign)
(BIN)
+6 to +8 Upper limit value
+9 to
+11
Reference value
+12 Analog output scale number
(1 digit BCD)
Forced zero number (ASCII
5 characters)
+16
+17
+18
0019 (fixed)
1 to 5
1 to 7
0000 to 9999
000 to 999
If +: 0
If –: F
Same as lower limit value
Same as lower limit value
0 to 3
Data output condition
(1 digit BCD)
Data output timer value
(3 digits BCD)
Number of seconds for latch timer
(2 digits BCD)
5A45524F2B (“ZERO+”)
4E4F524D20 (“NORM ”)
5A45524F2D (“ZERO–”)
0 to 6
000 to 999
00 to 99
Data
Example
−
123.4567
+3
+4
+5
4 5 6 7
0 1 2 3
F 0 0 0
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
Single Run Measurement Start (4000-series) (Sequence No. 434)
When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+4
+5
+6
+7
+0
+1
+2
+3
Number of receive data words
Decision result
(Undefined)
Decimal portion
Integer portion
Sign
(Undefined)
Sign
(Undefined)
Decimal portion
Integer portion
(Undefined)
Measurement value
Deviation value
344
3Z4L Laser Micrometer Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of receive data words (4 digits BCD)
Decision result
(ASCII 2 characters)
Data
With no reference setting: 0005
With reference setting: 0008
With no limit setting: 0000
With limit setting: 2B4E (“+N”), 4F4B (“OK”),
2D4E (“–N”)
0000 to 9999
Example
−
123.4567
+2
+3
+4
Measurement value (decimal portion)
(4 digits BCD)
Measurement value (integer portion)
(3 digits BCD)
Measurement value (Sign)
(BIN)
000 to 999
+5 to +7 Deviation value
+2
+3
+4
4 5 6 7
0 1 2 3
F 0 0 0
If +: 0
If –: F
Same as measurement value
*The deviation will be stored in this area only when reference setting is made.
Deflection Measurement Start (4000-series) (Sequence No. 435)
This sequence starts a deflection measurement.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note The deflection measurement keeps measuring until sequence No. 438 (Measurement Termination) is executed.
Continuous Measurement Start (Scan) (4000-series)
(Sequence No. 436)
This sequence starts a continuous measurement. The scan notification method is used for the receive data.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
438 (Measurement Termination) to end the sequence.
Continuous Measurement Start (Interrupt) (4000-series)
(Sequence No. 437)
This sequence starts a continuous measurement. The interrupt notification method is used for the receive data and the interrupt No. is 101.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
438 (Measurement Termination) to end the sequence.
345
3Z4L Laser Micrometer Protocol
Appendix K
Continuous Measurement Termination (4000-series)
(Sequence No. 438)
This sequence terminates continuous measurement.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
For continuous measurement:None.
For Deflection Measurement
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Data Request (4000-series) (Sequence No. 439)
This sequence requests display data in the idle measurement status or latch data generated by the measurement command.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Forced Positive Zero (4000-series) (Sequence No. 440)
This sequence sets the forced zero direction to positive (+)
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Forced Negative Zero (4000-series) (Sequence No. 441)
This sequence sets the forced zero direction to negative (–)
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Forced Zero Release (4000-series) (Sequence No. 442)
This sequence releases the forced zero direction.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
3Z4L Initialize (4000-series) (Sequence No. 443)
This sequence clears the 3Z4L, sets the mm unit, and sets memory switches.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting).
Receive Data Word Allocation (3rd Operand of PMCR)
None.
346
3Z4L Laser Micrometer Protocol
Appendix K
General-purpose Command 1 (4000-series) (Sequence No. 444)
This general-purpose command is used to send data with a specified data length, and receive back only OK.
The terminator (CR) is automatically attached to the send data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
Send data byte length
Send data
Send data
+128
+129
•
•
Send data
Send data
CR
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Send data byte length (4 digits BCD)
0003 to 0129
Data
+2 to
+129
Send data (ASCII)
0001 to 0255
The number of bytes of send data excluding the terminator (CR)
Send data up to 255 bytes maximum
Specify in ASCII.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
347
3Z4L Laser Micrometer Protocol
Appendix K
General-purpose Command 2 (4000-series) (Sequence No. 445)
This general-purpose command is used to send data with a specified data length, and receive back receive data other than OK. The terminator (CR) is automatically attached to the send data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
Send data byte length
Send data
Send data
+128
+129
•
•
Send data
Send data
CR
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Send data byte length
(4 digits BCD)
+2 to
+129
Send data (ASCII)
0003 to 0129
Data
0001 to 0255
The number of bytes of send data excluding the terminator (CR)
Send data up to 255 bytes maximum
Specify in ASCII.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
Receive data
Receive data
+126
+127
•
•
Receive data
Receive data
Offset
+0
+1 to
+127
Contents (data format)
Number of receive data words
(4 digits BCD)
Receive data (ASCII)
0001 to 0128
Data
When the receive data exceed 254 bytes, only 254 bytes are stored.
348
Appendix L
Visual Inspection System Protocol
The Visual Inspection System Protocol is used to make various settings or control remotely the Visual Recognition Device connected to the Serial Communications Board via RS-232C cable.
Protocol Configuration
The configuration of the Visual Inspection System Protocol is shown below.
Sequence
No.
Communications sequence name
Function
450
Ladder interface
Send word allocation
Receive word allocation
No Yes
451
452
453
454
455
456
457
460
461
462
463
464
465
Measurement execution
(F200)
Continuous measurement execution (scan)
(F200)
Continuous measurement execution (interrupt)
(F200)
Reference object registration (group) (F200)
Reference object registration (reference position) (F200)
Reference object registration (evaluation criterion) (F200)
Evaluation condition change (F200)
Carries out one measurement one and stores the measurement results in the specified words.
Carries out continuously setting the F200 and storing the measurement results in the specified words.
Carries out continuously setting the F200 and storing the measurement results in the specified words.
Performs reference position registration and evaluation criterion registration at the same time.
Registers the reference position for measuring the amount of position displacement when a position displacement compensation is used.
Registers the reference value to discriminate the output format.
Arbitrary measurement value acquisition (F200)
Changes the upper and lower limit values of the evaluation condition of the designated output No.
Stores the measurement values of arbitrary measurement item regardless of output format in the specified words.
Measurement execution
(F300)
Continuous measurement execution (scan)
(F300)
Continuous measurement execution (interrupt)
(F300)
Reference object registration command 1 execution (F300)
Reference object registration command 2 execution (F300)
Illumination fluctuation follow execution (F300)
Carries out one measurement and stores the measurement results in the specified words.
Carries out continuously setting the F300 and storing the measurement results in the specified words.
Carries out continuously setting the F300 and storing the measurement results in the specified words.
Performs a measurement for the input image and updates the reference object data of the full window.
Performs a measurement for the input image and updates the reference object data of the full window
Executes an illumination fluctuation follow.
No
No
No
No
No
Yes
Yes
No
No
No
No
Yes
No
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
349
Visual Inspection System Protocol
Appendix L
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
No
Receive word allocation
Yes 470
471
472
473
474
480
481
482
483
490
491
492
493
494
495
Measurement execution and positioning (F350)
Camera designation and positioning (F350)
Scene switching and positioning (F350)
Inspection execution and character inspection
(F350)
Character string inspection and character inspection (F350)
Camera change
(decrease by 1) (F200/
300)
Carries out one measurement and stores the measurement results in the specified words.
Designates the camera for measurement.
Switches to a designated scene No.
Carries out one inspection and outputs inspection results to the video monitor.
Changes the inspection character string of a designated inspection area No. to a designated character string.
Decreases the display camera No. by 1.
Camera change
(increase by 1) (F200/
300)
Binary level modification
(F200/300)
Reset (F200/300)
Scene switch (decrease by 1)
Increases the display camera No. by 1.
Modifies the binary levels (upper limit and lower limit values) of a designated window number No.
Resets the F200/F300.
Decreases the scene No. by 1.
Scene switch (increase by 1)
Increases the scene No. by 1.
Scene switch (arbitrary) Switches to a designated scene No.
Measurement, inspection termination
General-purpose command (send)
Terminates the measurement and returns to the home menu.
Sets and executes commands that are otherwise not supported.
General-purpose command (send/receive)
Sets and executes commands that are otherwise not supported.
Yes
Yes
No
Yes
No
No
Yes
No
No
No
Yes
No
Yes
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
350
Visual Inspection System Protocol
Connections
The connections for using the Visual Inspection System Protocol are shown below.
RS-232C Connections
CQM1H F200/300/350
Appendix L
Serial Communications Board
RS-232C port
1
4
5
2
3
6
7
8
Pin No.
20
→
RS-232C Unit
Signal name
Protective ground or earth FG (GND)
Send data
Receive data
Request to send
Clear to send
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
Data set ready
Signal ground
Carrier detection (Data word receive)
Data terminal ready
DR (DSR)
SG (GND)
CD (DCD)
ER (DTR)
Abbreviation
Serial Communications
Board: D-sub 9 pin (female)
Signal Name Pin No.
F300-E:
D-sub 25 pin (female)
Pin No.
Signal Name
• For RS/CS Flow Control
Serial Communications
Board: D-sub 9 pin (female)
Signal Name Pin No.
F300-E:
D-sub 25 pin (female)
Pin No.
Signal Name
351
Visual Inspection System Protocol
Appendix L
Measurement Execution (F200) (Sequence No. 450)
This sequence carries out one measurement and stores the measurement results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
(Undefined) Output No.
(Undefined)
Evaluation result
Decimal portion
Sign
Integer portion
0
Measurement value
Offset
+0
+1
+2
+3 to
+5
Content (data format)
Number of receive data words
(4 digits BCD)
Output No. (2 digits BCD)
Evaluation result (1 digit BCD)
Measurement value (decimal portion) (3 digits BCD)
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
0006
Data
00 to 07
0: OK
1: NG
Example
−
123.456
Example
+123.456
+3
+4
+5
3456
0012
F000
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Note 1.
Only one output No. can be stored.
2.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.647
For calibration ON setting: –9999999.999 to 9999999.999
3.
If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words.
Continuous Measurement Execution (Scan) (F200)
(Sequence No. 451)
This sequence carries out continuously the setting of the F200 and stores measurement results in the specified words. The scan notification method is used for the receive data.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
(Undefined) Output No.
(Undefined)
Evaluation result
Decimal portion
Integer portion
Sign 0
Measurement value
352
Visual Inspection System Protocol
Appendix L
Offset
+0
+1
+2
+3 to
+5
Content (data format)
Number of receive data words
(4 digits BCD)
Output No. (2 digits BCD)
Evaluation result (1 digit BCD)
Measurement value (decimal portion) (3 digits BCD)
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
0006
Data
00 to 07
0: OK
1: NG
Example
−
123.456
+3
+4
+5
3456
0012
F000
Example
+123.456
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Note 1.
Only one output No. can be designated.
2.
Turn OFF CIO 28911 (if port A is used) or CIO 28915 (if port B is used) to terminate this sequence.
3.
The ranges of measurement values are as follows:
For calibration OFF setting : –2147483.648 to 2147483.647
For calibration ON setting : –9999999.999 to 9999999.999
4.
If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words.
Continuous Measurement Execution (Interrupt) (F200)
(Sequence No. 452)
This sequence carries out continuously setting the F200 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
(Undefined)
Output No.
(Undefined) Evaluation result
Decimal portion
Integer portion
Sign
0
Measurement value
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits BCD)
Output No. (2 digits BCD)
Evaluation result (1 digit BCD)
0006
Data
+3 to
+5
Measurement value (decimal portion) (3 digits BCD)
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
00 to 07
0: OK
1: NG
Example
−
123.456
+3
+4
+5
3456
0012
F000
Example
+123.456
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Note 1.
Only one output No. can be designated.
2.
Turn OFF CIO 28911 (if port A is used) or CIO 28915 (if port B is used) to terminate this sequence.
353
Visual Inspection System Protocol
Appendix L
3.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.647
For calibration ON setting: –9999999.999 to 9999999.999
4.
If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words.
Reference Object Registration (Group) (F200)
(Sequence No. 453)
This sequence performs reference position registration and criterion registration at the same time.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Reference Object Registration (Reference Position) (F200)
(Sequence No. 454)
This sequence registers the reference position for measuring the amount of position displacement when a position displacement compensation is used.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Reference Object Registration (Criterion) (F200)
(Sequence No. 455)
This sequence registers a reference value to discriminate the output format.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Evaluation Condition Change (F200) (Sequence No. 456)
This sequence changes the upper and lower limit values of evaluation condition of the designated output No.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
(Undefined)
Output No.
Decimal portion
Integer portion
+4
(Undefined)
+5
Sign (Undefined)
+6 (Undefined) Decimal portion
+7
+8
(Undefined)
+9
Sign
Integer portion
(Undefined)
Upper limit value
Lower limit value
354
Visual Inspection System Protocol
Appendix L
Offset
+0
+1
+2 to
+5
Content (data format)
Number of send data words
(4 digits BCD)
Output No. (2 digits BCD)
Upper limit value (decimal portion)
(3 digits BCD)
Upper limit value (integer portion)
(7 digits BCD)
Upper limit value (sign) (ASCII
2 digits)
0010
00 to 07
Example
−
123.456
+2
+3
+4
0567
1234
0000
+5 2D00
+6 to
+9
Data
Lower limit value (decimal portion)
(3 digits BCD)
Lower limit value (integer portion)
(7 digits BCD)
Lower limit value (sign) (ASCII
2 digits)
Same as upper limit.
+2
+3
+4
+5
Example
+123.456
0678
2345
0001
3000
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Only one output No. can be designated.
2.
Enter values so that upper limit
≥
lower limit.
3.
Enter upper limit and lower limit values within the range –2147483.648 to 2147483.648.
Arbitrary Measurement Value Acquisition (F200)
(Sequence No. 457)
This sequence stores measurement values of arbitrary measurement items regardless of output format in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
Data 1
Data 2
Offset
+0
+1
Content (data format)
Number of send data words
(4 digits BCD)
Data 1 (2 digits BCD)
0003
Data
+2 Data 2 (2 digits BCD)
00: Area
01: Center of gravity x
02: Center of gravity y
03: Main axis angle
04: Output format
05: Reference value of output format
06: X displacement
07: Y displacement
08: Angle displacement
09: X reference position
10: Y reference position
11: Angle reference position
When 00 to 03 is set to data 1
Window No.:00 to 07
When 04 to 05 is set to data 1
Output No.:00 to 07
When 06 to 11 is set to data 1
Camera No.:00 to 01
355
Visual Inspection System Protocol
Appendix L
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined)
Decimal portion
Integer portion
+3 Sign 0
Measurement value
Offset
+0
+1 to
+3
Content (data format)
Number of receive data words
(4 digits BCD)
Measurement value (decimal portion) (3 digits BCD)
0004
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
Data
Example
−
123.456
+3
+4
+5
3456
0012
F000
Example
+123.456
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Note 1.
Only one output No. can be designated.
2.
Measurement is not performed with this command. The measurement results of the last measurement will be stored in the specified words.
3.
This command can acquire only the measurement value of the window No. set by output format.
4.
For data 1 and 2 , the receive data is compared with the send data. If the receive data is not the same as the send data, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON.
5.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.647
For calibration ON setting: –9999999.999 to 9999999.999
6.
If a measurement value exceeds the range of measurement values when calibration is turned off, unexpected data is stored in the specified words.
Measurement Execution (F300) (Sequence No. 460)
This sequence carries out one measurement and stores measurement results in the specified words
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
Number of receive data words
(Undefined)
(Undefined)
Window No.
Evaluation
result
Decimal portion
Integer portion
Sign
0
Sign
Sign
Decimal portion
Integer portion
0
Decimal portion
Integer portion
0
Decimal portion
Integer portion
Sign
Sign
0
Decimal portion
Integer portion
0
Data 1
Data 2
Data 3
Data 4
Data 5
356
Visual Inspection System Protocol
Appendix L
Offset
+0
+1
+2
+3 to
+5
Content (data format)
Number of receive data words
(4 digits BCD)
Window number (2 digits BCD)
Evaluation result (1 digit BCD)
Measurement value (decimal portion) (3 digits BCD)
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
Data
0006: 1 measurement item
0009: 2 measurement items
0012: 3 measurement items
0015: 4 measurement items
0018: 5 measurement items
00 to 07
0:OK
1:NG
Example
−
123.456
+3
+4
+5
3456
0012
F000
Example
+123.456
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Same as +3 to +5.
+6 to
+8
+9 to
+11
+12 to
+14
+15 to
+17
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Note 1.
Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9.
2.
The number of measurement items is up to 5, but only one window number can be read.
3.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.648
For calibration ON setting: –9999999.999 to 9999999.999
4.
The priority of measurement items being output are as follows:
Area
Center of gravity X, Center of gravity Y
Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved)
Main axis angle
Main axis angle aberration (reserved)
Edge angle
Edge angle (reserved)
Center X, center Y
Center X aberration (reserved), center Y aberration (reserved)
Inclination
Inclination aberration (reserved)
Intersecting point X, intersecting point Y
Intersecting point X aberration (reserved), intersecting point Y aberration (reserved)
Continuous Measurement Execution (Scan) (F300)
(Sequence No. 461)
This sequence carries out continuously the settings of F300 and stores measurement results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
None.
357
Visual Inspection System Protocol
Appendix L
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
Number of receive data words
(Undefined)
Window No.
(Undefined)
Evaluation result
Decimal portion
Sign
Integer portion
0
Sign
Decimal portion
Integer portion
0
Sign
Decimal portion
Integer portion
0
Sign
Decimal portion
Integer portion
0
Sign
Decimal portion
Integer portion
0
Data 1
Data 2
Data 3
Data 4
Data 5
Offset
+0
+1
+2
+3 to
+5
Content (data format)
Number of receive data words
(4 digits BCD)
Window No. (2 digits BCD)
Evaluation result (1 digit BCD)
Measurement value (decimal portion) (3 digits BCD)
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
Data
0006: 1 measurement item
0009: 2 measurement items
0012: 3 measurement items
0015: 4 measurement items
0018: 5 measurement items
00 to 07
0: OK
1: NG
Example
−
123.456
+3
+4
3456
0012
+5 F000
Example
+123.456
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Same as +3 to +5.
+6 to
+8
+9 to
+11
+12 to
+14
+15 to
+17
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Note 1.
Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9.
2.
The number of measurement items are up to 5, but only one window number can be read.
3.
The range of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.648
For calibration ON setting: –9999999.999 to 9999999.999
4.
The priority order of measurement items being output are as follows:
Area
Center of gravity X, Center of gravity Y
Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved)
358
Visual Inspection System Protocol
Appendix L
Main axis angle
Main axis angle aberration (reserved)
Edge angle
Edge angle (reserved)
Center X, center Y
Center X displacement (reserved), center Y displacement (reserved)
Inclination
Inclination displacement (reserved)
Intersecting point X, intersecting point Y
Intersecting point X displacement (reserved), intersecting point Y displacement (reserved)
Continuous Measurement Execution (Interrupt) (F300)
(Sequence No. 462)
This sequence carries out continuously setting the F300 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+9
+10
+11
+12
+13
+14
+15
+16
+17
+0
+1
+2
+3
+4
+5
+6
+7
+8
Number of receive data words
(Undefined)
(Undefined)
Window No.
Evaluation result
Decimal portion
Sign
Sign
Integer portion
0
Decimal portion
Integer portion
0
Decimal portion
Sign
Sign
Sign
Integer portion
0
Decimal portion
Integer portion
0
Decimal portion
Integer portion
0
Data 1
Data 2
Data 3
Data 4
Data 5
359
Visual Inspection System Protocol
Appendix L
Offset
+0
+1
+2
+3 to
+5
Content (data format)
Number of receive data words
(4 digits BCD)
Window No. (2 digits BCD)
Evaluation result (1 digit BCD)
Measurement value (decimal portion) (3 digits BCD)
Measurement value (integer portion) (7 digits BCD)
Measurement value (sign)
(1 digit)
Data
0006: 1 measurement item
0009: 2 measurement items
0012: 3 measurement items
0015: 4 measurement items
0018: 5 measurement items
00 to 07
0: OK
1: NG
Example
−
123.456
+3
+4
+5
3456
0012
F000
+3
+4
+5
Example
+123.456
3456
0012
0000
F is stored for negative values.
Same as +3 to +5.
+6 to
+8
+9 to
+11
+12 to
+14
+15 to
+17
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Note 1.
Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9.
2.
The number of measurement items is up to 5, but only one window number can be read.
3.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.648
For calibration ON setting: –9999999.999 to 9999999.999
4.
The priority of measurement items being output are as follows:
Area
Center of gravity X, Center of gravity Y
Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved)
Main axis angle
Main axis angle displacement (reserved)
Edge angle
Edge angle(reserved)
Center X, center Y
Center X displacement (reserved), center Y displacement (reserved)
Inclination
Inclination displacement (reserved)
Intersecting point X, intersecting point Y
Intersecting point X displacement (reserved), intersecting point Y displacement (reserved)
Reference Object Registration Command 1 Execution (F300)
(Sequence No. 463)
This sequence performs a measurement for the input image and updates reference object data of the full window.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
360
Visual Inspection System Protocol
Appendix L
Reference Object Registration Command 2 Execution (F300)
(Sequence No. 464)
This sequence performs a measurement for the input image and updates the reference object data of a designated window.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
Number of send data words
(Undefined) Window No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Window No. (2 digits BCD)
0002
00 to 07
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Illumination Fluctuation Follow Execution (F300)
(Sequence No. 465)
This sequence executes an illumination fluctuation follow.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Measurement Execution and Positioning (F350)
(Sequence No. 470)
This sequence carries out one measurement and stores the measurement results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
Decimal portion
Sign
Sign
Integer portion
Decimal portion
Integer portion
Decimal portion
Sign
0 Integer portion
X displacement
Y displacement
Correlation value
361
Visual Inspection System Protocol
Appendix L
Offset
+0
+1 to
+2
Content (data format)
Number of receive data words
X displacement (decimal portion)
(3 digits BCD)
X displacement (integer portion)
(3 digits BCD)
X displacement (sign) (1 digit)
(See note.)
+3 to
+4
+5 to
+6
Y displacement (decimal portion)
(3 digits BCD)
Y displacement (integer portion)
(3 digits BCD)
Y displacement (sign) (1 digit)
(See note.)
Correlation value (decimal portion)
(3 digits BCD)
Correlation value (integer portion)
(3 digits BCD)
Correlation value (sign) (1 digit)
(See note.)
Data
0007
Example
−
123.456
+1
+2
3456
F012
Example
+123.456
+1
+2
3456
0012
F is stored for negative values.
Example
−
123.456
+1
+2
3456
F012
Example
+123.456
+1
+2
3456
0012
F is stored for negative values.
Example
−
12.345
+1
+2
2345
F001
Example
+12.345
+1
+2
2345
0001
F is stored for negative values.
Note 1.
The number of models that can be stored in a designated word is 1.
2.
If a measurement is carried out without executing a camera designation, a measurement is executed for all cameras in which the measurement model is registered.
3.
When the correlation value is less than 70 and the measurement value overflows, CIO 28909 (if port
A is used) or CIO 28913 (if port B is used) will turn ON.
4.
Data to be output is within the range 999.999 (upper limit) to –999.999 (lower limit).
5.
Retry processing is not performed for this sequence.
6.
Turn the Abort Bit ON and then OFF to end this sequence.
Camera Designation and Positioning (F350) (Sequence No. 471)
This sequence designates the cameras for measurement.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
First camera
No.
Last camera
No.
Offset
+0
+1
+2
Content (data format)
Number of send data words
(4 digit BCD)
First camera No. (1 digit BCD)
Last camera No. (1 digit BCD)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0003
0 to 7
0 to 7
Data
Note 1.
Set values so that the first camera No.< last camera No.
2.
If a designated camera No. is abnormal, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON.
362
Visual Inspection System Protocol
Appendix L
Scene Switching and Positioning (F350) (Sequence No. 472)
This sequence switches to a designated scene No.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Scene No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Scene No. (2 digits BCD)
0002
00 to 15
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
If a scene No. is abnormal, CIO 28909 (if port A is used) or CIO 28913 (if port B is used) will turn ON.
2.
Retry processing is not performed for this sequence.
3.
Turn the Abort Bit ON and then OFF to end this sequence.
Inspection Execution and Character Inspection (F350)
(Sequence No. 473)
This sequence carries out one inspection and outputs the inspection results to a video monitor.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Character String Inspection and Character Inspection (F350)
(Sequence No. 474)
This sequence changes the inspection character string of a designated inspection area No. to a designated character string.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
~
Number of send data words
Inspection area No.
(Undefined)
Number of designated character strings
Designated character string
~
Designated character string
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Number of designated character strings (4 digits BCD)
Inspection area No.
(2 digits BCD)
+3 to Number of designated character strings (ASCII)
0004 to 0015
0 to 24
00 to 07
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
363
Visual Inspection System Protocol
Appendix L
Camera Change (Decrease by 1) (F200/300) (Sequence No. 480)
This sequence decreases the display camera No. by 1.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Camera Change (Increase by 1) (F200/300) (Sequence No. 481)
This sequence increases the display camera No. by 1.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Binary Level Modification (F200/300) (Sequence No. 482)
This sequence modifies the binary levels (upper limit and lower limit values) of a designated output No. (F200) or window number No. (F300).
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
(Undefined)
(Undefined)
Number of send data words
(Undefined)
Window No.
or Output No.
Upper limit value
Lower limit value
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
Window No. (1 digit BCD)
Upper limit value (3 digits BCD)
Lower limit value (3 digits BCD)
0004
0 to 7
000 to 255
000 to 255
Data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Enter values so that the upper limit
≥
lower limit.
Reset (F200/300) (Sequence No. 483)
This sequence resets the F200/F300 (to starting status).
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Scene Switching (Decrease by 1) (Sequence No. 490)
This sequence decreases the scene No. by 1.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
364
Visual Inspection System Protocol
Appendix L
Scene Switching (Increase by 1) (Sequence No. 491)
This sequence increases the scene No. by 1.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Scene Switching (Arbitrary) (Sequence No. 492)
This sequence switches to a designated scene No.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined)
Scene No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Scene No. (2 digits BCD)
0002
00 to 15
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Data
Measurement, Inspection Termination (Sequence No. 493)
This sequence terminates the measurement and returns to the home menu.
Send Data Word Allocation (2nd Operand of PMCR)
None.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
General-purpose Command (Send) (Sequence No. 494)
This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
Number of send data words
Command length
(Undefined) Command
~ ~
Data Offset
+0
+1
+2 to
Contents (data format)
Number of send data words
(4 digits BCD)
Command length (4 digits BCD)
Command (ASCII)
003 to 0129
0001 to 0253
Specify ASCII data.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
The processing depends on the command.
2.
For a command with a response, use sequence #495.
365
Visual Inspection System Protocol
Appendix L
General-purpose Command (Send/Receive) (Sequence No. 495)
This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
~
Number of send data words
Command length
(Undefined)
Command
~
Offset
+0
Contents (data format)
Number of send data words
(4 digits BCD)
+1 Command length (4 digits BCD)
+2 to Command (ASCII)
0003 to 0129
Data
Receive Data Word Allocation (3rd Operand of PMCR)
The reception data is stored in the reception data words without the delimiter (CR+LF),
Receive data storage words
+0
+1
+2
~
Number of receive data words
Command length
(Undefined) Command
~
Offset
+0
Contents (data format)
Number of receive data words
(4 digits BCD)
+1 Command length (4 digits BCD)
+2 to Command (ASCII)
Data
ASCII data is returned.
Note 1.
The processing depends on the command.
2.
For a command with a response, use sequence #495.
0001 to 0253
Specify ASCII data.
366
Appendix M
V600/V620 ID Controller Protocol
The V600/V620 ID Controller Protocol is used to make various settings or control remotely the ID Controller
Connected to the Serial Communications Board via RS-232C or RS-422A cable.
Protocol Configuration
The configuration of the V600/V620 ID Controller Protocol is shown below.
Sequence
No.
Communications sequence name
Function
500
Ladder interface
Send word allocation
Receive word allocation
Yes Yes
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
Read (ASCII/1)
Read (ASCII/2)
Read (ASCII/4)
Read (ASCII/8)
Read (Hexadecimal/
1)
Read (Hexadecimal/
2)
Read (Hexadecimal/
4)
Read (Hexadecimal/
8)
Polling Auto-read
Subcommand (ASCII/
4)
Polling Auto-read
Subcommand (ASCII/
8)
Polling Auto-read
(Hexadecimal)
Polling Auto-read
Subcommand (Hexadecimal/2)
Used when the number of Heads to be read from the Carrier is 1.
Used when the number of Heads to be read from the Carrier is 2.
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
Used when the number of Heads to be read from the Carrier is 1.
Used when the number of Heads to be read from the Carrier is 2.
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
Auto-read (ASCII/1) Used when the number of Heads to be read from the Carrier is 1.
Auto-read (Hexadecimal/1)
Used when the number of Heads to be read from the Carrier is 1.
Polling Auto-read
(ASCII)
Polling Auto-read
Subcommand (ASCII/
2)
Used when the number of Heads to be read from the Carrier is from 1 to 8.
Used when the number of Heads to be read from the Carrier is 2.
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
Used when the number of Heads to be read from the Carrier is from 1 to 8.
Used when the number of Heads to be read from the Carrier is 2.
Polling Auto-read
Subcommand (Hexadecimal/4)
Polling Auto-read
Subcommand (Hexadecimal/8)
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
367
V600/V620 ID Controller Protocol
Appendix M
524
525
526
527
528
529
518
519
520
521
522
523
Sequence
No.
Communications sequence name
530
531
532
533
534
535
536
537
538
539
540
541
542
Function
Write (ASCII/1)
Write (ASCII/2)
Write (ASCII/4)
Write (ASCII/8)
Write (Hexadecimal/
1)
Write (Hexadecimal/
2)
Used when the number of Heads to be written to the Carrier is 1.
Used when the number of Heads to be written to the Carrier is 2.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 8.
Used when the number of Heads to be written to the Carrier is 1.
Used when the number of Heads to be written to the Carrier is 2.
Write (Hexadecimal/
4)
Write (Hexadecimal/
8)
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 8.
Auto-write (ASCII/1) Used when the number of Heads to be written to the Carrier is 1.
Auto-write (Hexadecimal/1)
Used when the number of Heads to be written to the Carrier is 1.
Polling Auto-write
(ASCII/2)
Polling Auto-write
Subcommand (ASCII/
2)
Polling Auto-write
(ASCII/4)
Polling Auto-write
Subcommand (ASCII/
4)
Used when the number of Heads to be written to the Carrier is 2.
Used when the number of Heads to be written to the Carrier is 2.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 4.
Polling Auto-write
(ASCII/8)
Polling Auto-write
Subcommand (ASCII/
8)
Polling Auto-write
(Hexadecimal/2)
Polling Auto-write
Subcommand (Hexadecimal/2)
Polling Auto-write
(Hexadecimal/4)
Polling Auto-write
Subcommand (Hexadecimal/4)
Polling Auto-write
(Hexadecimal/8)
Polling Auto-write
Subcommand (Hexadecimal/8)
Used when the maximum number of Heads to be written to the Carrier is 8.
Used when the maximum number of Heads to be written to the Carrier is 8.
Used when the number of Heads to be written to the Carrier is 2.
Used when the number of Heads to be written to the Carrier is 2.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 8.
Used when the maximum number of Heads to be written to the Carrier is 8.
Data check Writes and verify the CRC code for the check blocks designated by the user.
Control management Performs I/O or an I/O read.
Error information read Reads information from the latest error log.
Yes
Yes
Yes
Yes
Yes
Yes
Ladder interface
Send word allocation
Yes
Receive word allocation
No
Yes No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
368
V600/V620 ID Controller Protocol
Appendix M
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
Yes
Receive word allocation
Yes 543
544
545
546
Command processing cancel
Polling auto-read command processing cancel
Cancels command processing except polling command processing and returns to the command waiting status.
Cancels polling auto-read processing.
Polling auto-write command processing cancel
General-purpose command
Cancels polling auto-write processing.
Sends arbitrary data and stores receive data to receive data words.
Yes
Yes
Yes
Note Ladder Interface Settings
YES:
User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
Yes
Yes
Yes
Connections
Connections when using the V600/V620 ID Controller Protocol are shown below.
RS-232C Connections
CQM1H
Head
Serial Communications Board
RS-232C port
ID Controller
Data Carrier
Serial Communications Board:
D-sub 9 pin (female)
Signal name
Pin No.
ID Controller (CD1D):
D-sub 9 pin (female)
Pin No.
Signal name
ID Controller (CA1A):
D-sub 25 pin (female)
Shielded cable
Serial Communications Board:
D-sub 9 pin (female)
Shielded cable
369
V600/V620 ID Controller Protocol
RS422A Connections
CQM1H
Serial Communications Board
RS-422A port
Appendix M
Head Data Carrier
ID Controller
ID Controller
Head Data Carrier
Serial Communications Board:
D-sub 9 pin (female)
Signal name
Pin No.
Up to 16 units can be connected
ID Controller (CD1D):
D-sub 9 pin (female)
Pin No.
Signal name
Shielded cable
Note 1.
Ground the cable shield at either the ID Controller or the Serial Communications Board to prevent malfunction.
2.
Turn ON the pin 6 on DIP switch SW6 to set the host communications procedure to the 1-to-N procedure for 1-to-N connections.
370
V600/V620 ID Controller Protocol
DIP Switch Settings
V600/620-CD1D DIP Switches
DIP Switch 1
1 2 3 4 5 6 7 8
Appendix M
Baud rate
(bps)
2400
4800
9600
19,200
Display mode
Error display mode
I/O display mode
Not used (Always keep it OFF.)
Local communications mode setting
Speed priority setting
Distance priority setting
•
SW7 Setting
This setting is only valid if the EEPROM-type (batterylesstype) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (battery-type) DC. SW7 must be set to OFF when the V620 is used.
Data length (bit)
7
7
7
7
8
8
8
8
STOP bits (bit)
2
2
1
1
2
1
1
1
Parity type
E
O
E
O
N
N
E
O
371
V600/V620 ID Controller Protocol
DIP Switch 2
1 2 3 4 5 6 7 8
Appendix M
Not used (Always keep it OFF.)
Communications protocol setting with host devices
1-to-N protocol
1-to-1 protocol
Note When selecting the "1-to-N" protocol, setting is limited to
N=1. In this case, the FCS check code may be added.
•
ID Controller Unit Number Setting (Valid Only for 1-to-N Protocol)
Unit No.
No. 0
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
Note 1. Be careful not to set to the same unit number twice.
2. Set them to OFF for the 1-to-1 protocol.
Synchronous condition
OFF (LL level)
ON (HL level)
Trailing edge
Leading edge
372
V600/V620 ID Controller Protocol
V600-CA
@
A DIP Switches
DIP Switch 1
Appendix M
Note Factory Setting: All OFF
•
Baud Rate
Setting
1=ON, 0=OFF
Mode 1
1 2 3 4 5 6 7 8
Baud rate
(bps)
1200
2400
4800
9600
19200
SW7 and SW8: Be sure to set to OFF.
•
Communications Format
Data length (bit)
STOP bit (bit)
1=ON, 0=OFF
8
8
8
8
7
7
7
7
(See note 1.)
2
2
1
1
2
1
1
1
Note 1. Data length setting
7 bits: ASCII code
8 bits: JIS8 unit code
2. Parity setting
E: Even parity
O: Odd parity
N: No parity designation
Parity type
E
O
E
O
N
N
E
O
(See note 2.)
DIP Switch 2
1 2 3 4 5 6 7 8
•
SW8: Receive Side Terminal Resistance Setting (Valid Only for the V600-CA2A)
Connected (ID Controller send side)
Not connected
•
SW7: Receive Side Terminal Resistance Setting (Valid Only for the V600-CA2A)
Connected (ID Controller receive side)
Not connected
•
SW6: Communications Protocol Setting
1-to-N protocol
1-to-1 protocol
•
ID Controller Unit Number Setting (Valid Only for the 1-to-N Protocol)
Unit No.
•
SW1 Setting
This setting is only valid if the EEPROM-type (battery less-type) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (batterytype) DC.
•
SW6 Setting
When selecting the 1-to-N protocol for the
V600-CA1A/RS-232C interface, the setting is limited to N=1. In this case, the FCS check code may be added.
•
Local Communications Mode Setting
Speed priority setting
Distance priority setting
No. 0
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
No. 8
No. 9
No. 10
No. 11
No. 12
No. 13
No. 14
No. 15
Note 1. Be careful not to set to the same unit number twice.
2. Set them to OFF for the 1-to-1 protocol.
373
V600/V620 ID Controller Protocol
Appendix M
Read (ASCII/1) (Sequence No. 500)
This sequence is used when the number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0005 (fixed)
+2
+3
R/W Head channel
(CH) No. (1 digit BCD)
Data
00 to 07 (CD1D)
00 to 15 (CA
@
A)
R/W Head CH 1 designation:1
R/W Head CH 2 designation:2
The CD1D must be set to 1.
0000 to FFFF
+4
Leading address No.
(4 digits Hexadecimal)
Read bytes
(2 digits Hexadecimal)
01 to F4 (1 to 244 bytes)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
~
+122
Number of receive data words
Read data
Read data
Read data
~
+0
Offset Contents (data format)
Number of receive data words (4 digits BCD)
+1 to +122 Read data (ASCII)
0002 to 0123
Data
Number of read bytes stored in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
374
V600/V620 ID Controller Protocol
Appendix M
Read (ASCII/2) (Sequence No. 501)
This sequence is used when the number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
CH 1
CH 2
+0
Offset Contents (data format)
Number of send data words (4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(4(N–1)+2) Unit No. (2 digits BCD)
0006 to 0010
0001 to 0002
+(4(N–1)+3) R/W Head CH No.
(1 digit BCD)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(4(N–1)+5) Read bytes
(2 digits Hexadecimal)
N: Number of Heads
01 to 76 (1 to 118 bytes)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+59
+60
~
+61
~
+119
Number of receive data words
Read data
Read data
Not used
Read data
Read data
~
~
CH 1
CH 2
+0
Offset
+(60(N–1)+1) to
+(60(N–1)+59)
N: Number of Heads
Contents (data format)
Number of receive data words (4 digits BCD)
Read data (ASCII)
0002 to 0120
Data
Number of read bytes store in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
375
V600/V620 ID Controller Protocol
Appendix M
Read (ASCII/4) (Sequence No. 502)
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
+14
~
+15
+16
+17
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
CH 1
CH 2
4 CH
+0
Offset Contents (data format)
Number of send data words
(4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(4(N–1)+2) Unit No. (2 digits BCD)
0006 to 0018
0001 to 0004
+(4(N–1)+3) R/W Head CH No.
(1 digit BCD)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(4(N–1)+5) Read bytes
(2 digits Hexadecimal)
N: Number of Heads
01 to 30 (1 to 48 bytes)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
~
+24
+25
+48
~
Number of receive data words
Read data
Read data
Read data
Read data
~
~
CH 1
CH 2
~ ~
Read data
+73
+96
~
Read data
~
4 CH
376
V600/V620 ID Controller Protocol
Appendix M
+0
Offset Contents (data format)
Number of receive data words (4 digits BCD)
Read data (ASCII) +(24(N–1)+1) to
+(24(N–1)+24)
N: Number of Heads
0002 to 0097
Data
Number of read bytes stored in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
Read (ASCII/8) (Sequence No. 503)
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
~
CH 1
CH 2
+30
+31
+32
+33
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
8 CH
+0
Offset Contents (data format)
Number of send data words (4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(4(N–1)+2) Unit No. (2 digits BCD)
+(4(N–1)+3) R/W Head CH No.
(1 digit BCD)
0006 to 0034
0001 to 0008
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(4(N–1)+5) Read bytes
(2 digits Hexadecimal)
N: Number of Heads
01 to 14 (1 to 20 bytes)
377
V600/V620 ID Controller Protocol
Appendix M
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+10
+11
~
+20
~
Number of receive data words
Read data
Read data
Read data
Read data
~
~
~
CH 1
CH 2
~
+71
~
+80
Read data
Read data
~
CH 8
Offset Contents (data format)
+0
+(10(N–1)+1) to
+(10(N–1)+10)
N: Number of Heads
Number of receive data words (4 digits BCD)
Read data (ASCII)
0002 to 0081
Data
Number of read bytes stored in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
Read (Hexadecimal/1) (Sequence No. 504)
This sequence is used when the number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+4
Number of send data words
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined) Read bytes
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0005 (fixed)
+2
+3
R/W Head CH No. (1 digit BCD)
Data
00 to 07 (CD1D)
00 to 15 (CA @ A)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
+4
Leading address No.
(4 digits Hexadecimal)
Read bytes
(2 digits Hexadecimal)
01 to 7A (1 to 122 bytes)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+2
+61
~
Number of receive data words
Read data
Read data
Read data
~
378
V600/V620 ID Controller Protocol
Appendix M
+0
Offset
+1 to +61
Contents (data format)
Number of receive data words (4 digits BCD)
0002 to 0062
Data
Read data (Hexadecimal) Number of read bytes stored in hexadecimal data
Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words.
Read (Hexadecimal/2) (Sequence No. 505)
This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+5
+6
+7
+2
+3
+4
+8
+9
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
CH 1
CH 2
+0
+1
Offset
+(4(N–1)+2)
Contents (data format)
Number of send data words (4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
0006 to 0010
0001 to 0002
Data
+(4(N–1)+3) R/W Head CH No.
(1 digit BCD)
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4)
+(4(N–1)+5)
Leading address No.
(4 digits Hexadecimal)
Read bytes
(2 digits Hexadecimal)
N: Number of Heads
01 to 3C (1 to 60 bytes)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+30
+31
~
Number of receive data words
Read data
Read data
Not used
+60
~
+61
+90
~
Not used
Read data
Read data
~
~
~
CH 1
CH 2
379
V600/V620 ID Controller Protocol
Appendix M
+0
Offset Contents (data format)
Number of receive data words (4 digits BCD)
0002 to 0091
Data
+(60(N–1)+1) to
+(60(N–1)+30)
N: Number of Heads
Read data (Hexadecimal) Number of read bytes stored in hexadecimal code
Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words.
Read (Hexadecimal/4) (Sequence No. 506)
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
+14
+15
+16
+17
+6
+7
+8
+9
~
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
CH 1
CH 2
CH 4
+0
Offset Contents (data format)
Number of send data words (4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(4(N–1)+2) Unit No. (2 digits BCD)
0006 to 0018
0001 to 0004
+(4(N–1)+3) R/W Head CH No.
(1 digit BCD)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(4(N–1)+5) Read bytes
(2 digits Hexadecimal)
N: Number of Heads
01 to 18 (1 to 24 bytes)
380
V600/V620 ID Controller Protocol
Appendix M
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
~
+12
+13
+24
+25
~
+36
~
Number of receive data words
Read data
Read data
(Not used)
(Not used)
Read data
Read data
~
~
~
~
~
CH 1
CH 2
+73
~
+84
Read data
~
CH 4
+0
Offset
+(24(N–1)+1) to +(24(N–
1)+12)
Read data
Contents (data format)
Number of receive data words (4 digits BCD)
0002 to 0085
Data
Read data (Hexadecimal) Number of read bytes stored in hexadecimal data
Note Data for Data Carriers designated for hexadecimal is received beginning with the largest offset from the receive data words.
Read (Hexadecimal/8) (Sequence No. 507)
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
CH 1
CH 2
+30
+31
+32
+33
~
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
CH 8
381
V600/V620 ID Controller Protocol
Appendix M
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words (4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
0006 to 0034
0001 to 0008
R/W Head CH No.
(1 digit BCD)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4)
+(4(N–1)+5)
Leading address No.
(4 digits Hexadecimal)
Read bytes
(2 digits Hexadecimal)
N: Number of Heads
01 to 0A (1 to 10 bytes)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+5
+6
~
Number of receive data words
Read data
Read data
Not used
+10
+11
~
+15
~
Not used
Read data
Read data
~
~
~
~
~
CH 1
CH 2
+71
~
+75
Read data
~
CH 8
Read data
+0
Offset Contents (data format)
Number of receive data words (4 digits BCD)
+(10(N–1)+1) to
+(10(N–1)+5)
N: Number of Heads
Read data (CH 1) (Hexadecimal)
0002 to 0076
Data
Number of read bytes stored in hexadecimal data
Note Data for Data Carriers designated for hexadecimal is sent beginning with the largest offset from the receive data words.
Auto-read (ASCII/1) (Sequence No. 508)
This sequence is used when the maximum number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)).
Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
382
V600/V620 ID Controller Protocol
Appendix M
Auto-read (Hexadecimal/1) (Sequence No. 509)
This sequence is used when the maximum number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 504 (Read (Hexadecimal/1)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 504 (Read (Hexadecimal/1)).
Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Polling Auto-read (ASCII) (Sequence No. 510)
This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data +1
+2
+3
+4
+5
+(4(N-1)+2)
+(4(N-1)+3)
+(4(N-1)+4)
+(4(N-1)+5)
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
CH 1
CH N
* N: Number of Heads
+0
+1
Offset
+(4(N–1)+2)
Contents (data format)
Number of send data words (4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
0006 to 0034
0001 to 0008
Data
+(4(N–1)+3)
+(4(N–1)+4)
R/W Head CH No.
(1 digit BCD)
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
+(4(N–1)+5)
Leading address No.
(4 digits Hexadecimal)
Read bytes
(2 digits Hexadecimal)
If number of Heads is 2 or less
01 to 76 (1 to 118 bytes)
If number of Heads is 4 or less
01 to 30 (1 to 48 bytes)
If number of Heads is 8 or less
01 to 20 (1 to 20 bytes)
N: Number of Heads
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 510 before executing Sequence No. 511, 512, 513.
2.
Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read.
3.
Retry processing is not performed for this sequence.
383
V600/V620 ID Controller Protocol
Appendix M
Polling Auto-read Sub-command (ASCII/2) (Sequence No. 511)
This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)).
Note 1.
Execute Sequence No. 510 before executing Sequence No. 511.
2.
Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (ASCII/4) (Sequence No. 512)
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)).
Note 1.
Execute Sequence No. 510 before executing Sequence No. 512.
2.
Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (ASCII/8) (Sequence No. 513)
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)).
Note 1.
Execute Sequence No. 510 before executing Sequence No. 513.
2.
Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
384
V600/V620 ID Controller Protocol
Appendix M
Polling Auto-read (Hexadecimal) (Sequence No. 514)
This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
~
+(4(N-1)+2)
+(4(N-1)+3)
+(4(N-1)+4)
+(4(N-1)+5)
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
+0
+1
Offset
+(4(N–1)+2)
Contents (data format)
Number of send data words (4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
CH 1
CH N
* N: Number of Heads
0006 to 0034
0001 to 0008
+(4(N–1)+3)
+(4(N–1)+4)
+(4(N–1)+5)
R/W Head CH No.
(1 digit BCD)
Leading address No.
(4 digits Hexadecimal)
Read bytes
(2 digits Hexadecimal)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
0000 to FFFF
If number of Heads is 2 or less
01 to 3C (1 to 60 bytes)
If number of Heads is 4 or less
01 to 18 (1 to 24 bytes)
If number of Heads is 8 or less
01 to 0A (1 to 10 bytes)
N: Number of Heads
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 514 before executing Sequence No. 515, 516, 517.
2.
Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read.
Polling Auto-read Sub-command (Hexadecimal/2) (Sequence
No. 515)
This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 505 (Read (Hexadecimal/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 505 (Read (Hexadecimal/2)).
Note 1.
Execute Sequence No. 514 before executing Sequence No. 515.
385
V600/V620 ID Controller Protocol
Appendix M
2.
Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (Hexadecimal/4) (Sequence
No. 516)
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 506 (Read (Hexadecimal/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 506 (Read (Hexadecimal/4)).
Note 1.
Execute Sequence No. 514 before executing Sequence No. 516.
2.
Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words.
Polling Auto-read Sub-command (Hexadecimal/8) (Sequence
No.517)
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of sequence No.507 (Read (Hexadecimal/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514.
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of sequence No.507 (Read (Hexadecimal/8)).
Note 1.
Execute sequence No.514 before executing sequence No.517.
2.
Data from Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Write (ASCII/1) (Sequence No.518)
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send +0 data
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Max
~
+128 Write data
~
386
V600/V620 ID Controller Protocol
Appendix M
Offset
+0
+1
+2
+3
+4
+5 to
+128
Contents (data format)
Number of send data words
(4 digits BCD)
0006 to 0129
Data
Relevant Unit No. (2 digits BCD) 00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
Leading address No.
(4 digits Hexadecimal)
Number of write bytes
(4 digits BCD)
Write data (ASCII)
0000 to FFFF
0001 to 0248
Input in ASCII
Up to 248 bytes (max.) can be set
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words.
Write (ASCII/2) (Sequence No. 519)
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
+3
+4
+5
+6
~
+64
+65
+66
+67
+68
+69
+70
+128
~
Number of send data words
Number of Heads
(Undefined) Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
(Not used)
(Undefined) Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
~
CH 1
CH 2
387
V600/V620 ID Controller Protocol
Appendix M
+0
Offset Contents (data format)
Number of send data words (4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(64(N–1)+2) Unit No. (2 digits BCD)
0007 to 0129
0001 to 0002
+(64(N–1)+3) R/W Head CH No.
(1 digit BCD)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(64(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(64(N–1)+5) Number of write bytes
(4 digits BCD)
Write data (ASCII) +(64(N–1)+6) to (64(N–
1)+64)
N: Number of Heads
0001 to 0118
Input in ASCII.
Up to 118 bytes (max.) can be set
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words.
388
V600/V620 ID Controller Protocol
Appendix M
Write (ASCII/4) (Sequence No. 520)
This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
+6
+29
+30
~
+31
+32
+33
+34
+57
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
~
CH 1
CH 2
~ ~
+86
+87
+88
+89
+90
+113
~
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
~
CH 4
+0
+1
Offset
Write data
+(28(N–1)+2)
Contents (data format)
Number of send data words (4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
+(28(N–1)+3) R/W Head CH No.
(1 digit BCD)
0007 to 0114
0001 to 0004
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(28(N–1)+4)
+(28(N–1)+5)
+(28(N–1)+6) to
(28(N–1)+29)
N: Number of Heads
Leading address No.
(4 digits Hexadecimal)
Number of write bytes
(4 digits BCD)
Write data (ASCII)
0001 to 0048
Input in ASCII.
Up to 48 bytes (max.) can be set
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Write designated for ASCII is sent beginning with the smallest offset from the send data words.
389
V600/V620 ID Controller Protocol
Appendix M
Write (ASCII/8) (Sequence No. 521)
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+15
+16
+17
+18
+19
+20
+4
+5
+6
~
+29
~
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
(Undefined) Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
~
CH 1
CH 2
~ ~
+100
+101
+102
+103
+104
+113
~
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
+0
Offset Contents (data format)
Number of send data words(4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(14(N–1)+2) Unit No. (2 digits BCD)
CH 8
0007 to 0114
0001 to 0008
+(14(N–1)+3) R/W Head CH No.
(1 digit BCD)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(14(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(14(N–1)+5) Number of write bytes
(4 digits BCD)
+(14(N–1)+6) to (14(N–
1)+15)
Write data (ASCII)
N: Number of Heads
0001 to 0020
Input in ASCII
Up to 20 bytes (max.) can be set
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words.
390
V600/V620 ID Controller Protocol
Appendix M
Write (Hexadecimal/1) (Sequence No. 522)
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
+0
First word of send data
+1
+2
+3
+4
+5
Number of send data words
(Undefined) Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write digits
Write data
~ ~
Max +35 (Undefined)
Write data
Offset
+0
+1
+2
+3
+4
+5 to
35
Contents (data format)
Number of send data words
(4 digits BCD)
0006 to 0036
Data
Relevant Unit No. (2 digits BCD) 00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
Leading address No.
(4 digits Hexadecimal)
Number of write digits
(4 digits BCD)
Write data (Hexadecimal)
0000 to FFFF
0002 to 0122
Input in hexadecimal
Up to 122 digits (max.)
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Data of which Data Carrier designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
391
V600/V620 ID Controller Protocol
Appendix M
Write (Hexadecimal/2) (Sequence No. 523)
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
+6
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
~
CH 1
+19
+20
+65
~
+66
Write data
(Not used)
~
+67
+68
+69
+70
(Not used)
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
CH 2
+83
~
Write data
~
+0
Offset Contents (data format)
Number of send data words (4 digits BCD)
+1 Number of Heads
(4 digits BCD)
+(64(N–1)+2) Unit No. (2 digits BCD)
0007 to 0084
0002 to 0002
Data
+(64(N–1)+3) R/W Head CH No.
(1 digit BCD)
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(64(N–1)+4) Leading address No.
(4 digits Hexadecimal)
+(64(N–1)+5) Number of write digits
(4 digits BCD)
+(64(N–1)+6) to
(64(N–1)+19)
0002 to 0056
Write data (Hexadecimal) Input in hexadecimal
Up to 56 digits (max.) can be set
N: Number of Heads
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Write data designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
392
V600/V620 ID Controller Protocol
Appendix M
Write (Hexadecimal/4) (Sequence No. 524)
This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 24 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
+6
~
+11
+12
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
Not used
~
CH 1
+29
+30
~
+31
+32
+33
+34
+39
~
Not used
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
+86
~
+87
+88
+89
+90
+95
~
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
~
~
~
~
CH 2
CH 4
+0
+1
Offset Contents (data format)
Number of send data words (4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
0007 to 0096
0001 to 0004
Data
+(28(N–1)+2)
+(28(N–1)+3) R/W Head CH No.
(1 digit BCD)
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(28(N–1)+4)
+(28(N–1)+5)
Leading address No.
(4 digits Hexadecimal)
Number of write digits
(4 digits BCD)
0002 to 0024
+(28(N–1)+6) to
(28(N–1)+11)
Write data (Hexadecimal)
N: Number of Heads
Input in hexadecimal code
Up to 24 digits (max.) can be set
Receive Data Word Allocation (3rd Operand of PMCR)
None.
393
V600/V620 ID Controller Protocol
Appendix M
Note 1.
Write data designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
Write (Hexadecimal/8) (Sequence No. 525)
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
+4
+5
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
CH 1
+6
Write data
~ ~
+8
+9
(Undefined)
Not used
Write data
+15
~
+16
+17
+18
+19
+20
~
Not used
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
+22
~
+100
~
+101
+102
+103
+104
+106
~
(Undefined)
(Undefined)
Write data
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
~
~
~
CH 2
CH 8
394
V600/V620 ID Controller Protocol
Appendix M
+0
+1
Offset Contents (data format)
Number of send data words
(4 digits BCD)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
0007 to 0107
0001 to 0004
Data
+(14(N–1)+2)
+(14(N–1)+3) R/W Head CH No.
(1 digit BCD)
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(14(N–1)+4)
+(14(N–1)+5)
Leading address No.
(4 digits Hexadecimal)
Number of write digits
(4 digits BCD)
+(14(N–1)+6) to
(14(N–1)+8)
Write data (Hexadecimal)
N: Number of Heads
Receive Data Word Allocation (3rd Operand of PMCR)
None.
0002 to 0010
Input in hexadecimal code
Up to 10 digits (max.) can be set
Note 1.
Write data designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
Auto-write (ASCII/1) (Sequence No. 526)
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 518 (Write(ASCII/1)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 518 (Write(ASCII/1)).
Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Auto-write (Hexadecimal/1) (Sequence No. 527)
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 522 (Write (Hexadecimal/1)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 522 (Write (Hexadecimal/1)).
Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Polling Auto-write (ASCII/2) (Sequence No. 528)
This sequence is used when the number of Heads to be written to the Carrier is 2.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
395
V600/V620 ID Controller Protocol
Appendix M
Polling Auto-write Subcommand (ASCII/2) (Sequence No. 529)
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 528 before executing Sequence No. 529.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (ASCII/4) (Sequence No. 530)
This sequence is used when the number of Heads to be written to the Carrier is 4.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 520 (Write(ASCII/4)).
Note Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling autowrite.
Polling Auto-write Subcommand (ASCII/4) (Sequence No. 531)
This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 530 before executing Sequence No. 531.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (ASCII/8) (Sequence No. 532)
This sequence is used when the number of Heads to be written to the Carrier is 8.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (ASCII/8) (Sequence No. 533)
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). However, the leading address No., number of write, and write data are not used and become undefined.
396
V600/V620 ID Controller Protocol
Appendix M
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 532 before executing Sequence No. 533.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (Hexadecimal/2) (Sequence No. 534)
This sequence is used when the number of Heads to be written to the Carrier is 2.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 523 (Write (Hexadecimal/2)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 523 (Write (Hexadecimal/2)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (Hexadecimal/2) (Sequence
No. 535)
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 523 (Write (Hexadecimal/2)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 534 before executing Sequence No. 535.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (Hexadecimal/4) (Sequence No. 536)
This sequence is used when the number of Heads to be written to the Carrier is 4.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 524 (Write (Hexadecimal/4)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 524 (Write (Hexadecimal/4)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (Hexadecimal/4) (Sequence
No. 537)
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 24 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 524 (Write (Hexadecimal/4)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
397
V600/V620 ID Controller Protocol
Appendix M
Note 1.
Execute Sequence No. 536 before executing Sequence No. 537.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (Hexadecimal/8) (Sequence No. 538)
This sequence is used when the number of Heads to be written to the Carrier is 8.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 525 (Write (Hexadecimal/8)).
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 525 (Write (Hexadecimal/8)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (Hexadecimal/8) (Sequence
No. 539)
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 525 (Write (Hexadecimal/8)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1.
Execute Sequence No. 538 before executing Sequence No. 539.
2.
Retry processing is not performed for this sequence.
Data Check (Sequence No. 540)
This sequence writes and verifies the CRC code for check blocks designated by the user.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
+2
(Undefined)
+3
Processing designation
+4
+5
Head CH No.
(Undefined)
Leading address of check object
(Undefined)
Number of check block bytes
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0006 (fixed)
Data
+2
+3
+4
+5
R/W Head CH No.
(1 digit BCD)
Processing designation
(2 digits Hexadecimal)
Leading address of check object
(4 digits Hexadecimal)
Number of check block bytes
(2 digits Hexadecimal)
00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH 1 designation:1
R/W Head CH 2 designation:2
The CD1D must be set to 1.
Verification:43 (C)
Calculation:4B (K)
Management of number of write times: 4C (L)
0000 to FFFF
(If management of number of write times is designated,
H’ @@@ 0 to H’ @@@ 5 or H’ @@@ 8 to H’ @@@ D)
If verification, calculation is designated:
03 to FF (set 00 for 256 bytes)
If management of number of write times is designated:
00 to FF
398
V600/V620 ID Controller Protocol
Appendix M
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+1
Number of receive data words
(Undefined)
Completion code
Offset
+0
Contents (data format)
Number of receive data words (4 digits BCD)
Completion code
(2 digits Hexadecimal)
0002 (fixed)
Data
(Verification, calculation designation)
00:Normal completion for calculation processing
75: Data in normal condition for verification processing
76: Error Data alarm for verification processing
(If management of number of write times is designated)
75:Number of write times is under those which is specified.
76:alarm for number of write times is over those which is specified.
Note If L (management of number of write times) is designated by processing designation, management of number of write times for Data Carrier of EEPROM is performed.
Control (Sequence No. 541)
This sequence performs I/O operations or I/O reads.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
Number of send data words
(Undefined) Unit No.
+2 (Undefined)
OUT1 operation OUT2 operation
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
OUT1 operation (1 digit BCD)
0003 (fixed)
Data
OUT2 operation (1 digit BCD)
00 to 07 (CD1D)
0: No operation
1: turned ON
2: turned OFF
0: No operation
1: turned ON
2: turned OFF
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
Current input status
Output status after operation
+0
Offset Contents (data format)
Number of receive data words
(4 digits BCD)
+1
Leftmost 1 byte
Current input status
Leftmost 4 bits:IN1 operation
Rightmost 4 bits:IN2 operation
Output status after operation
Leftmost 4 bits:OUT1 operation
Rightmost 4 bits:OUT2 operation
0002 (fixed)
Note 1.
The V600/620-CA @ A does not support this command.
2.
This sequence executes the equivalent of the CONTROL command.
1: ON status
0: OFF status
1: ON status
0: OFF status
Data
399
V600/V620 ID Controller Protocol
Appendix M
Error Information Read (Sequence No. 542)
This sequence reads information from the latest error log.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0 Number of send data words
+1 (Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 07 (CD1D)
Data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
+75
~
Number of receive data words
Error log
Error log
+0
Offset
+1 to +75
~
Contents (data format)
Number of receive data words
(4 digits BCD)
Error log (ASCII)
0004 to 0076
Data
One item of data is stored with
5 characters of generated command, generated Head No., generated error code.
Note 1.
The V600/620-CA @ A does not support this command.
2.
Up to 30 error records can be stored.
3.
The most resent error records are stored first.
Command Processing Cancel (Sequence No. 543)
This sequence cancels command processing except for polling command processing. The command waiting status is entered.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0 Number of send data words
+1 (Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0002 (fixed)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
(Undefined)
Unit No.
400
V600/V620 ID Controller Protocol
Appendix M
Offset
+0
+1
Contents (data format)
Number of receive data words (4 digits BCD)
Completion code
(2 digits Hexadecimal)
Data
0002 (fixed)
00: Normal termination
14: Auto or communications command processing not executed
75: Cancelled before the end of expansion command receive or before sync input went active or before detection of the existence of Data Carrier
76: Cancelled during read/write processing for Data
Carrier
Polling Auto-read Command Processing Cancel
(Sequence No. 544)
This sequence cancels polling auto-read processing.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
+0 data
+1
+2
+3
Number of send data words
(Undefined)
Unit No.
(Not used)
(Undefined)
Head channel No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Unit No. (2 digits BCD)
0004 (fixed)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
+2
+3
Not used
R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
+1
Number of receive data words
(Undefined)
Completion code
Offset
+0
+1
Contents (data format)
Number of receive data words (4 digits BCD)
Completion code
(2 digits Hexadecimal)
0002 (fixed)
Data
75: Cancelled before communications processing with Data Carrier
76: Cancelled after communications processing with
Data Carrier
Polling Auto-write Command Processing Cancel (Sequence
No. 545)
This sequence cancels polling auto-write processing
Send Data Word Allocation (2nd Operand of PMCR)
The send data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing
Cancel)
Receive Data Word Allocation (3rd Operand of PMCR)
The receive data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing Cancel)
401
V600/V620 ID Controller Protocol
Appendix M
General-purpose Command (Sequence No. 546)
This sequence transmits arbitrary data and stores receive data to the receive data words. The characters “@”,
FCS (terminator) are not required in the send data words and receive data words. These characters will be automatically added for transmission and automatically removed before saving data.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send data
+0
+1
+2
~
+127
Number of send data words
Send data byte length
Send data
Send data
(Undefined)
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Send data byte length
(4 digits BCD)
0003 to 0128
Data
+2 to
+127
Send data (ASCII)
0001 to 0251
The number of bytes in the send data except for @, the FCS, and the terminator.
Input send data up to 251 characters
(max.) in ASCII
Receive Data Storage Word Allocation (3rd Operand of PMCR)
Receive data storage words
+0
Number of receive data words
Receive data
+1
+126
~
Receive data
(Undefined)
~
Offset
+0
+1 to
+126
Contents (data format)
Number of receive data words
(4 digits BCD)
Receive data
(ASCII)
0002 to 0127
Data
Receive data is stored in ASCII.
Up to 251 characters (max.)
402
Appendix N
Hayes Modem AT Command Protocol
The Hayes Modem AT Command Protocol is used to make various settings or control remotely a Hayes modem connected to the Serial Communications Board via RS-232C cable.
Protocol Configuration
The configuration of the Hayes Modem AT Command Protocol is shown below.
Sequence
No.
Communications sequence name
Function
550 Initialize modem (general-purpose)
Initialize modem (specialized)
Initializes the modem connected to the
Serial Communications Board. The initialization command is set in the words specified for the second operand of PMCR.
Initializes certain OMRON Modems.
Ladder interface
Send word allocation
Receive word allocation
Yes No
No No 560
570
580
561
571
581
Dial Yes No
552
553
554
555
562
572
582
590
Password
Data send/receive
(general purpose sequence)
Escape
Hang up
Initialize and dial
Escape to hang up
Dials from the modem connected to the
Serial Communications Board. AT commands and telephone numbers are set set in the words specified for the second operand of PMCR. This sequence can be used only for certain OMRON modems.
After the line is connected, the password sent from the other exchange is verified to confirm that the line is connected to the desired exchange. The normal value of a password is set in the words specified for the second operand of PMCR.
Sends arbitrary data to the exchange which the line is connected. Send data is set in the words specified for the second operand of
PMCR. Receive data is stored in the words specified for the third operand of PMCR.
Shifts the modem to escape mode (the condition in which command input is available during data communications). The escape code is fixed to “+++”
After shifting to escape mode, the line is disconnected.
Executes continuously from initialization to dialling operations for certain OMRON
Modems.
Executes continuously from shifting to the escape mode to hanging up.
Yes
Yes
No
No
Yes*
No
No
Yes
No
No
No
No
1.
Ladder Interface Settings
YES: User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
2.
For details about dialling, refer to sequences 561, 571 and 581.
403
Hayes Modem AT Command Protocol
Connections
The connections when using the Hayes Modem AT Command Protocol is shown below.
RS-232C Connection
Appendix N
Modem
Telephone line
Modem
Modem: D-sub
25 pin (female)
CQM1H D-sub 9 pin
(female)
Compatible Modems
Although most of the sequences in this protocol can be used regardless of modem, the sequences Initialize
Modem (specialized) and Dial sequences can be used only for the following Modems:
• MD24FB10V (OMRON Modem)
• MD144FB5V (OMRON Intelligent Modem)
• ME1414VB2/B2 (OMRON FAX/DATA Modem)
For other modems, create a modem initialization sequence using the general-purpose Initialize Modem sequence and dial using the Data Send/Receive sequence (Sequence No. 553).
404
Hayes Modem AT Command Protocol
Appendix N
Modem Settings
When this protocol is used, it is required that the modem connected to the Serial Communications Board be initialized to the following conditions:
Command echo
Result code display format
Speed display, busy/dialling tone detection at connection
Error correction data compression display
MNP setting
MNP class setting
V.42 compression, Error correction
Flow control between terminal modems
ER signal control
Escape code
No
Numeric format
Baud rate display enabled, busy and dialling tone detection enabled.
Error correction/data compression display enabled
Error correction provided (auto-reliable mode)
MNP class 4
Not enabled
Not enabled
Always ON
+
Note 1. It is recommended that, in addition to the above settings, the abort timer should be set so that communications are cut off if a communications error happened due to incidents such as cable disconnection between the Serial Communications Board and modem. Set the abort timer to 10 minutes for the modem initialization (specialized) (Sequence No. 560, 570, 580). Refer to modem’s manual for further information about abort timers.
2. The data format of the modem (baud rate, data length, parity, stop bit) is set by AT commands issued from a device connected to the modem. Its settings should conform to communications conditions of the device which issues AT commands. Therefore when communications are made between the modem and Serial Communications Board, it is required that communications conditions should be set by issuing AT commands from the Serial Communications Board.
3. Modem settings become invalid if the power supply is turned off and must be set again. However, a memory backup function can be used to protect settings so that even after the power supply to the modem is turned off, it can communicate with the previous setting conditions.
For Initialize Modem (specialized), the modem initialization command is built in as message data. However, for
Initialize Modem (general-purpose), the command must be specified in PMCR.
Operand 1
Operand 2
Operand 3
#x550 (x: Communications port)
First address for storing initialization command character string C
None
4 digits BCD
4 digits BCD
ASCII
C+0
C+1
C+2
:
C+n
Number of words from address set for operand 2 to end of data
Number of bytes for send data (initialization command)
Send data (initialization command)
(Fill data to left for odd numbers of bytes)
Setting Example for Modem Initialization Command
• MD24FB10V Using Sequence #550 (OMRON)
The following command is set in the words specified by the second operand of PMCR.
ATE0V0X4\V2\N3%C0*C0\X1&M0S26=10
0018 0032
AT E0 V0 X4 \ V 2 \ N3 %C 0 * C 0 \ X 1 & M 0 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR when it is used (words)
Note Turn ON pin 4 of DIP switches SW3 on for this Modem (ER signal always ON).
405
Hayes Modem AT Command Protocol
Appendix N
MD144FB5V (OMRON)
The following command is set in the words specified by the second operand of PMCR.
ATE0V0X4\V2\N3%C0*C0\Q0&M0&D0%B9600S26=10
0023 0041
AT E0 V0 X4 \ V 2 \ N 3 %C 0 * C 0 \ Q 0 & M 0 & D 0 % B 9 6 0 0 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR when it is used (words)
ME1414VBII/ME1414BII (OMRON)
The following command is set in the words specified by the second operand of PMCR.
AT\J1B8E0V0S0=1X4\V2\N3&M0%C0&D0&E0\X1S26=10
0024 0044
AT \ J 1 B 8 E 0 V 0 S 0 = 1 X 4 \ V 2 \ N 3 & M 0 %C 0 & D 0 & E 0 \ X 1 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR when it is used (words)
Note Turn ON DIP switch SW3 on in the rear of the Modem.
Dialling
To dial telephone numbers for the OMRON Modems using sequences No. 561, 571, 581, set the dialling command and telephone number in the words specified by the second operand of PMCR. However, for other
Modems, make the following settings for the Data Send/Receive sequence.
This is an example of telephone number settings for the above mentioned 3 OMRON Modems.
Operand and Word Settings of PMCR
Operand 1
Operand 2
Operand 3
MD24FB10V
MD144FB5V
ME1414VB2/B2 #x581
First address C of send data (dialling operation)
None
#x561 (x: Communications port)
#x571
C+0
C+1
C+2
:
C+n
Number of words from address set for operand 2 to end of data 4 digits BCD
Number of bytes of send data (dialling operation) 4 digits BCD
Send data (dialling operation)
(Fill data to left for odd numbers of bytes)
ASCII
406
Hayes Modem AT Command Protocol
Appendix N
Setting Example
If telephone number is 03-0123-4567
0010 0016 4154
A T
4454
D T
3033
0 3
2D30
−
0
3132
1 2
332D
3
−
3435
4 5
3637
6 7
Character string length of dialling operation sent to modem (bytes)
Code length of PMCR when it is used (words)
Note 1.
This example uses a tone line. Change ATDT to ATDP for pulse lines.
2.
Fill the telephone number to the left in the words if the character string length of the dialling operation is an odd number of bytes.
0008 0011 4154
A T
4454
D T
3031
0 1
2D32
−
2
3334
3 4
3500
5 @
Character string length of dialling operation sent to modem (bytes)
Code length of PMCR when it is used (words)
Password Verification
A password can be verified by executing sequence No. 552 of this protocol. It is required to set in advance the value of the password in the words specified by the second operand of PMCR.
Operand and Word Settings of PMCR
Operand 1
Operand 2
Operand 3
#x550 (x: Communications port)
First address of the words where the password is set
None
Setting Example
When password is OMRON-CO.
C+0
C+1
C+2
:
C+n
Number of words from address set for operand 2 to end of data 4 digits BCD
Number of bytes of comparison data (normal value of password) 4 digits BCD
Comparison value (password normal value)
(Fill data to left for odd numbers of bytes)
ASCII
0006 0008 4F4D
O M
524F
R O
4E2D
N
−
434F
C O
Character string length of password sent to modem (bytes)
Code length of PMCR when it is used (words)
407
Hayes Modem AT Command Protocol
Password Verification Operation
The number of retries is 3 for password verification.
PC
Password verification
(starting #552)
Personal computer
(remote exchange)
Appendix N
Dispatching character string
(Retry up to 3 times)
Receiving password
Verifying password
"Password: "
Password
Receiving character string
Issuing password
Verification result
When Instruction
Execution Flag
(SR 28908 or
SR 28913) turns
ON.
Terminating process
Data Send/Receive
Data Send/Receive can be executed using sequence No. 553. The send data sent to another exchange is set in the words specified by the second operand of PMCR. Data received by the PC is stored in the words specified by the third operand of PMCR.
Operand and Word Settings of PMCR
Operand 1
Operand 2
Operand 3
#x553 (x: Communications port)
First address C1 of the words where send data is set
First address C2 of the words where receive data is stored
• Operand 2
C1+0
C1+1
C1+2
:
C1+n
Number of words from address set for operand 2 to end of data 4 digits BCD
Number of bytes of send data 4 digits BCD
Send data (dialling operation)
(Fill data to left for odd numbers of bytes)
ASCII
• Operand 3
C2+0
C2+1
:
C2+n
Number of bytes of receive data
Receive data (dialling operation)
(Fill data to left for odd numbers of bytes)
4 digits BCD
ASCII
408
Hayes Modem AT Command Protocol
Appendix N
Setting Example
When send data is THIS IS SAMPLE.
0009 0014 5448
T H
4953
I S
2049
I
5320
S
5341
S A
4D50
M P
4C45
L E
Character string length of send data sent to modem (bytes)
Code length of PMCR when it is used (words)
A maximum of 200 bytes (including the CR) can be received. When the received data is RETURN OK, the content stored in the receive words is as follows:
0006 5245
R E
5455
T U
524E
R N
204F
O
4B00
K
Length of received character string (words)
Note An error will occur is the reception data is not received within 90 seconds after the data is sent.
Escape Mode
Shifting to the escape mode can be made using sequence No. 554. No setting is necessary for this sequence.
Note The character string to shift the online mode to the escape mode (i.e., the escape code) is ‘+’ for modem settings.
Hang Up Command
The hang up command (to disconnect the line) can be executed using sequence No. 555. No setting is necessary for this sequence.
Communication Errors
Three result codes are monitored after an AT command is sent to the modem. When a result code is returned, it will be checked. If the code is not the normal result code (“OK”, “CONNECT 9600/REL4”, “CONNECT 2400/
REL4”, in words), after a fixed time of waiting to send, the following retry processing will be repeated 2 times to send the AT command again and waiting for another result code.
The receive monitoring time and send wait time for each sequence are shown below.
Sequence
No.
#550
#560
#570
#580
#561
#571
#581
#552
#553
#554
#555
#562
Sequence name
Initialize modem (general-purpose)
Initialize modem (specialized)
Dial
Receive monitoring time
10 s
10 s
90 s
Password None
Data send/receive (general-purpose) 90 s
Escape
Hang up
Initialize and dial
10 s
10 s
90s
1 s
1 s
Send wait time for retries
90 s
None
1.5 s (after first try)
1.5 s (after first try)
Initializing: 1 s
Dialling: 90 s
#572
#582
#590 Escape and hang up 10 s 1.5 s (after first try)
409
Index
Numerics
1:1 Data Link
,
3
,
4
,
6
,
109 functions
,
110 ports connections
,
112 specifications starting
,
110
,
111
1:1 NT Link
,
3
,
4
,
7
1:N NT Link errors
,
132
,
3
,
4
,
7
2-wire and 4-wire connections transmission circuits
,
19
2-wire or 4-wire switch
,
13
3Z4L Laser Micrometer
,
63 connections
,
protocols sequences
A
applications precautions
, xiii
B
B500-AL001-E Link Adapter
,
22 bar code reader connections
,
103
Bar Code Readers
,
5 baud rate no-protocol communications protocol macros
,
59
,
102
C
C200H Communications Boards
,
55
C200HX/HG/HE Communications Board changes in communications specifications
,
55 cables
,
12
,
13 preparation
,
23
See also installation cleaning
,
133
C-mode commands
,
5 communications distance
Host Link
,
36 protocol macros
,
59 communications ports
See also ports communications sequences
See also PMCR(
,
84
) instructions, protocol macros, standard system protocols
comparison previous products
,
55 components names and functions
,
10
CompoWay/F protocols
,
63
CompoWay/F Master command and response formats
,
communications specifications
connections
,
message frames protocols
,
,
sequences
transmission procedure
connectors
,
12
,
13
,
17
,
26 connector hoods cover dimensions
,
26
,
15
See also installation wiring
,
23
CPU Units supporting CPU Units
,
8
CS1-series CPU Units changes in communications specifications
,
54
,
55
CS1-series Serial Communications Unit/Board changes in communications specifications
,
54
,
55
C-series CPU Units changes in communications specifications
,
54
C-series Host Link Units changes in communications specifications
,
53
,
55 current consumption
,
8
CVM1 CPU Units changes in communications specifications
,
54
,
55
CVM1 Host Link Units changes in communications specifications
,
54
,
55
CV-series CPU Units changes in communications specifications
,
54
,
55
CV-series Host Link Units changes in communications specifications
,
54
,
55
CX-Protocol
,
5
,
37
,
66
,
102
,
111
,
118
D
dimensions
,
8
Serial Communications Boards
,
15
E
E5_J Temperature Controller
,
63 connections
,
protocols sequences
E5_K Digital Controller
,
63 connections read
write
read protocols sequences
E5ZE Temperature Controller
,
63 connections read
write
read protocols sequences
write protocols sequences
EC Directives
, xv
EMI measures
, xv
411
412
error check codes
Host Link
,
36 errors
1:N NT Link
,
132 error codes error flags
,
30
,
81
,
84
,
107
,
30 flags
,
123
Host Link
,
124 end codes
,
52 indicators
,
122 protocol macros
,
127 troubleshooting
,
124
ES100 Digital Controller connections
,
protocols sequences
Executed Reception Case No. (code)
,
82 external dimensions connector cover
,
15
F
F200/F300/F350 Visual Inspection Unit
,
63 ferrite cores
, xvi flags
,
30 errors
,
123
Frame Check Sequence
See also frames, FCS frames dividing precautions
,
45
FCS
,
46
H
Hayes Modem AT Command
,
63 compatible modems connections
,
,
protocols sequences
heat-shrinking tubes
,
25
Host Link
,
3
,
5
,
33 commands
,
5
,
51 communications procedures
,
45 end codes
,
52 errors
,
124 host-initiated communications
,
34
PC-initiated communications
,
34 ports connections
,
39 specifications
,
36 transmission delay unit number setting
,
50
,
29
Host Link Units changes in communications specifications
,
55
I
indicators
CPU Unit
,
11
Index
error displays
,
122
Serial Communications Boards
,
10 inspection
,
134 installation
1:1 Data Link connections
,
112 cables
Host Link
,
44
Host Link connections
,
39 preparing cables
,
44 mounting location
,
4 no-protocol communications connections
,
103
NT Links connections
,
119 protocol macros connections
,
70
Serial Communications Boards
,
14 instructions
PMCR(
)
RXD(
)
TXD(
)
,
,
,
34
84
104
,
,
,
88
106
104
,
106
Intelligent Signal Processors
,
5
K
K3T_ Intelligent Signal Processor connections
,
protocols sequences
L
Link Adapters
,
19
,
22
,
23
,
40
,
72 link words settings
,
29
M
maintenance
,
121 cleaning
,
133 inspection
,
134 memory allocations
,
27 messages no-protocol communications
,
101 modems
,
5 compatibility
settings
,
mounting height
,
15
N
noise reduction
,
18 no-protocol communications
,
3
,
4
,
6
,
99 overview
,
100 ports connections
,
103
specifications
,
100
NT Link commands
,
7
NT Links
,
115
1:1
,
116
1:N
,
116 commands
,
116 overview
,
116 ports connections
,
119
NT-AL001-E Link Adapter
DIP switch settings
,
19
O
operating environment precautions
, xiii operation basic procedure
,
8 procedure
1:1 Data Link
,
111
Host Link
,
36 no-protocol communications
,
102
NT Links
,
118 protocol macros
,
66
P
PC Setup
,
8
,
28
,
130 link words
1:1 Data Link
,
110 standard settings
1:1 Data Link
,
112
Host Link
,
37 no-protocol communications
,
102
NT Links
,
118 protocol macros
,
67
PC-initiated communications
,
34
PMCR(
) instruction
,
84
,
operand settings
,
88 specifications
,
84 ports
,
8
See also RS-232C ports
See also RS-422A/485 ports settings
,
29 power supply
,
8 precautions applications
, xiii
Board replacement
,
135
Forced Abort Bit
,
94 general
, xii installing Serial Communications Boards
,
16 noise reduction
,
18
NT Links
,
116 operating environment
, xiii replacement
,
135 safety
, xii wiring
,
18 previous products comparison
,
55 program examples
1:1 Data Link
,
113
Index
Host Link
,
48 no-protocol communications
,
107
NT Links
,
116 protocol macros
,
86
,
87 protocol macros applications
,
3
,
5
,
57
,
84 errors
,
127 flags and control bits
,
80 functions
,
58 ladder programs
,
86 ports connections
,
70 specifications
,
59 standard system protocols
,
63 transmission methods
,
90 protocols
,
4
,
3Z4L Laser Micrometer sequences
,
CompoWay/F sequences
,
creating
,
64
E5_J Temperature Controller sequences
,
E5_K Digital Controller read sequences
,
E5ZE Temperature Controller read sequences
,
E5ZE Temperature Controller write sequences
,
ES100 Digital Controller sequences
,
Hayes Modem AT Command sequences
,
Host Link
,
45
K3T_ Intelligent Signal Processor sequences
,
Protocol Support Software list
See also standard system protocols structure
,
76
V500/V520 Bar Code Reader sequences
,
V600/V620 ID Controller sequences
,
Visual Inspection System sequences
,
R
reception case number
,
31
,
82 reception counter
,
31
,
100 reception matrixes
,
77 repeat counter
,
31
RS-232C communications one-to-one link
,
110 connecting Units
,
110
RS-232C connections
,
RS-232C ports
1:1 connections
,
71
1:N connections
,
73
413
414
changes from previous products connector pin layout
,
11 host computer connections
,
40 specifications wiring
,
20
,
11
,
53
RS-422 connections
,
RS-422A/485 ports
1:1 connections
,
74
1:N connections
,
75 changes from previous products host computer connections
,
42 specifications wiring
,
21
,
12
,
55
RS-485 connections
,
RXD(
) instruction
,
104
,
106
S
safety precautions
See also precautions sequences
CompoWay/F Master
Broadcast with ASCII Conversion, No Response (Sequence No. 601)
,
Broadcast with No Conversion and No Response (Sequence No. 603)
,
General-purpose Broadcast with No Conversion and
No Response (Sequence No. 605)
,
General-purpose Send with No Conversion and with
Response (Sequence No. 604)
Send with ASCII Conversion, with Response (Sequence No. 600)
,
Send with No Conversion and with Response (Sequence No. 602)
,
sequences, 3Z4L Laser Micrometer
3Z4L Clear (Sequence No. 400)
3Z4L Initialize (3000-series) (Sequence No. 430)
3Z4L Initialize (4000-series) (Sequence No. 443)
,
,
All Statistic Memory Clear (3000-series) (Sequence No.
418)
,
Automatic Detection List Request (3000-series) (Sequence
No. 429)
,
Automatic Detection Release (3000-series) (Sequence No.
428)
,
Automatic Detection Set (3000-series) (Sequence No. 427)
,
AVG Move (H) Times Set (3000-series) (Sequence No. 425)
,
AVG Move (L) Times Set (3000-series) (Sequence No. 426)
,
AVG Move Interval Set (3000-series) (Sequence No. 424)
,
Calibration Release (Sequence No. 405)
,
Calibration Set (Sequence No. 404)
Continuous Measurement Start (Interrupt) (3000-series) (Sequence No. 413)
Continuous Measurement Start (Interrupt) (4000-series) (Sequence No. 437)
Continuous Measurement Start (Scan) (3000-series) (Sequence No. 412)
Continuous Measurement Start (Scan) (4000-series) (Sequence No. 436)
Continuous Measurement Termination (4000-series) (Sequence No. 438)
Data Request (3000-series) (Sequence No. 415)
Data Request (4000-series) (Sequence No. 439)
Index
Deflection Measurement Start (4000-series) (Sequence No.
435)
,
E Unit Set (Sequence No. 403)
Forced Negative Zero (4000-series) (Sequence No. 441)
Forced Positive Zero (4000-series) (Sequence No. 440)
Forced Zero Release (4000-series) (Sequence No. 442)
,
,
General-purpose Command 1 (4000-series) (Sequence No.
444)
,
General-purpose Command 2 (4000-series) (Sequence No.
445)
,
Measurement Condition List Request (3000-series) (Sequence No. 409)
Measurement Condition List Request (4000-series) (Sequence No. 433)
Measurement Condition Release (3000-series) (Sequence
No. 408)
,
Measurement Condition Release (4000-series) (Sequence
No. 432)
,
Measurement Condition Set (3000-series) (Sequence No.
407)
,
Measurement Condition Set (4000-series) (Sequence No.
431)
,
Measurement Termination (3000-series) (Sequence No.
414)
,
Memory Switch Set (Sequence No. 401)
,
Memory Switch Set 1 (3000-series) (Sequence No. 421)
,
,
Memory Switch Set 2 (3000-series) (Sequence No. 422) mm Unit Set (Sequence No. 402)
Program Number Set (3000-series) (Sequence No. 406)
,
Settings
Simple AVG Times Set (3000-series) (Sequence No. 423)
,
Single Run Measurement Start (3000-series) (Sequence No.
410)
,
Single Run Measurement Start (4000-series) (Sequence No.
434)
,
Statistic Processing Calculation Non-execution (3000-series)
(Sequence No. 417)
,
Statistic Processing Execution (3000-series) (Sequence No.
416)
,
Statistic Processing Memory Clear (3000-series) (Sequence
No. 419)
,
Statistic Result Request (3000-series) (Sequence No. 420)
,
Zero Run Measurement Start (3000-series) (Sequence No.
411)
,
sequences, E5_J Temperature Controller
General-purpose Read (Sequence No. 216)
General-purpose Write (Sequence No. 216)
,
,
,
Read Heater Current (Sequence No. 214)
Read Initial Status (Sequence No. 215)
,
Read Input Shift Value (Sequence No. 210)
,
Read Output Value (Sequence No. 211)
Read Parameters 1 (Sequence No. 208)
,
Read Parameters 2 (Sequence No. 209)
Read Process Value (Sequence No. 212)
,
,
Read Set Point Limit (Sequence No. 213)
Save Set Point (Sequence No. 204)
Select Backup Mode (Sequence No. 202)
Select Local Mode (Sequence No. 201)
,
,
Select RAM Write Mode (Sequence No. 203)
Select Remote Mode (Sequence No. 200)
,
Write Input Shift Value (Sequence No. 207)
,
Write Parameters 1 (Sequence No. 205)
Write Parameters 2 (Sequence No. 206)
sequences, E5_K Digital Controller
Execute/Cancel AT (Sequence No. 074)
,
General-purpose Read (Sequence No. 023)
General-purpose Write (Sequence No. 070)
,
,
Index
Read Alarm Hysteresis (Sequence No. 016)
,
Read Alarm Value (Sequence No. 004)
Read Control Period (Sequence No. 010)
Read Cooling Coefficient (Sequence No. 006)
,
Read Dead Band (Sequence No. 007)
,
Read Hysteresis (Sequence No. 009)
,
Read Input Digital Filter (Sequence No. 015)
Read Input Shift Limits (Sequence No. 017)
,
Read LBA Detection Time (Sequence No. 012)
Read Level 0 Parameters (Sequence No. 018)
,
Read Level 1 Parameters 1 (Sequence No. 019)
,
Read Level 1 Parameters 2 (Sequence No. 020)
,
Read Level 2 Parameters 1 (Sequence No. 021)
,
Read Level 2 Parameters 2 (Sequence No. 022)
,
Read Manual Reset Value (Sequence No. 008)
,
Read MV (Sequence No. 002)
,
Read MV at Stop Time and at PV Error (Sequence No.013)
,
Read MV Limits (Sequence No. 014)
,
Read Process Value (Sequence No. 000)
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 005)
Read Set Point (Sequence No. 003)
,
Read Set Point during SP Ramp (Sequence No. 001)
,
Read SP Ramp Time Unit and Set Value (Sequence No. 011)
,
Remote/Local (Sequence No. 073)
Run/Stop (Sequence No. 072)
Software Reset (Sequence No. 076)
,
Switch to Level 0 (Software Reset) (Sequence No. 071)
Switch to Level 1 (Sequence No. 075)
Write Alarm Hysteresis (Sequence No. 063)
,
Write Alarm Value (Sequence No. 051)
,
Write Control Period (Sequence No. 057)
Write Cooling Coefficient (Sequence No. 053)
,
Write Dead Band (Sequence No. 054)
,
Write Hysteresis (Sequence No. 056)
,
Write Input Digital Filter (Sequence No. 062)
Write Input Shift Value (Sequence No. 064)
,
Write LBA Detection Time (Sequence No. 059)
,
Write Level 0 Parameters (Sequence No. 065)
Write Level 1 Parameter 2 (Sequence No. 067)
Write Level 1 Parameters 1 (Sequence No. 066)
,
Write Level 2 Parameters 1 (Sequence No. 068)
,
Write Level 2 Parameters 2 (Sequence No. 069)
,
Write Manual Reset Value (Sequence No. 055)
,
Write MV at Stop Time and at PV Error (Sequence No. 060)
,
Write MV Limits (Sequence No. 061)
,
Write Proportional Band, Integral Time, and Derivative Time
(Sequence No. 052)
Write Set Point (Sequence No. 050)
,
Write SP Ramp Time Unit and Set Value (Sequence No.
058)
sequences, E5ZE Temperature Controller
Cancel Autotuning (Sequence No. 160)
,
Initialize Settings (Sequence No. 169)
Read Alarm Mode (Sequence No. 107)
,
Read Alarm Temperatures (Sequence No. 108)
Read Control Period (Sequence No. 105)
Read Cooling Coefficient (Sequence No. 123)
,
Read Dead Band/Overlap Band (Sequence No. 122)
,
Read Error Status (Sequence No. 111)
,
Read HB Alarm and HS Alarm Valid Channels (Sequence
No. 119)
,
Read Heater Burnout and SSR Failure Detection Currents
(Sequence No. 120)
Read Heater Current and SSR Leakage Current (Sequence
No.121)
Read Hysteresis (Sequence No. 109)
,
Read Input Shift Value (Sequence No. 113)
,
Read Manual Reset Value (Sequence No. 114)
,
Read Operation Status (Sequence No. 110)
,
Read Output Mode (Sequence No. 106)
,
Read Output Value Change Rate Limit (Sequence No. 118)
,
Read Output Value Limit (Sequence No. 117)
,
Read Output Values (Sequence No. 102)
,
Read Present Set Point (Sequence No. 116)
Read Process Value (Sequence No. 101)
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 104)
Read Ramp Value (Sequence No. 115)
,
Read Set Point (Sequence No. 100)
,
Read Set Point, Process Value, and Output Value (Sequence
No. 103)
,
Read Setting Unit (Sequence No. 112)
,
Save Settings (Sequence No. 168)
Start Autotuning (Sequence No. 159)
,
Start Control (Sequence No. 174)
,
Start Manual Operation (Sequence No. 176)
,
Stop Operation or Control (Sequence No. 175)
,
Write Alarm Mode (Sequence No. 155)
Write Alarm Temperature (Setting Unit 0.1) (Sequence No.
157)
Write Alarm Temperature (Setting Unit 1) (Sequence No.
156)
Write Control Period (Sequence No. 153)
Write Cooling Coefficient (Sequence No. 173)
,
Write Dead Band/Overlap Band (Sequence No. 172)
,
Write HB and HS Alarm Valid Channels (Sequence No.
170)
Write Heater Burnout and SSR Failure Detection Current
(Sequence No. 171)
Write Hysteresis (Sequence No. 158)
,
Write Input Shift Value (Sequence No. 162)
,
Write Manual Output Value (Sequence No. 165)
,
Write Manual Reset Value (Sequence No. 163)
,
Write Output Mode (Sequence No. 154)
,
Write Output Value Change Rate Limit (Sequence No. 167)
,
Write Output Value Limit (Sequence No. 166)
,
Write Proportional Band, Integral Time, and Derivative Time
(Sequence No. 152)
Write Ramp Value (Sequence No. 164)
,
Write Set Point (Setting Unit 0.1) (Sequence No. 151)
,
Write Set Point (Setting Unit 1) (Sequence No. 150)
Write Setting Unit (Sequence No. 161)
,
sequences, ES100_ Digital Controller
Auto Mode (Sequence No. 273)
,
Cancel A.T. (Sequence No. 276)
,
Change Bank No. (Sequence No. 278)
,
Change Pattern No. (Sequence No. 277)
,
Execute A.T. (Sequence No. 275)
External Setting Mode (Sequence No. 270)
,
General-purpose Command (Sequence No. 280)
Local Setting Mode (Sequence No. 269)
,
Manual Mode (Sequence No. 274)
Read Adjustment Parameters (Sequence No. 258)
Read Control Monitor Data (Sequence No. 257)
Read Controller Status (Sequence No. 279)
,
Read Error Detection Data (Sequence No. 252)
,
Read Event Data (Sequence No. 250)
,
Read Heater Burnout Data (Sequence No. 253)
,
Read Local SP (Sequence No. 264)
,
Read MV Data (Sequence No. 256)
,
415
416
Read PID Control Parameters 1 (Sequence No. 260)
Read PID Control Parameters 2 (Sequence No. 261)
Read Program Parameters (Sequence No. 266)
,
,
,
Read PV Data (Sequence No. 254)
,
Read SP Data (Sequence No. 255)
Read Time Signal (Sequence No. 251)
Remote Setting Mode (Sequence No. 268)
Reset (Stop) (Sequence No. 272)
,
Run Command (Sequence No. 271)
,
Write Adjustment Parameters (Sequence No. 259)
Write Local SP (Sequence No. 265)
,
,
Write PID Control Parameters 1 (Sequence No. 262)
Write PID Control Parameters 2 (Sequence No. 263)
Write Program Parameters (Sequence No. 267)
,
sequences, Hayes Modem AT Command
Data Send/Receive (General-purpose) (Sequence No. 553)
,
Dial (Sequence No. 561)
Dial (Sequence No. 571)
Dial (Sequence No. 581)
Escape (Sequence No. 554)
,
Escape to Hang Up (Sequence No. 590)
,
Hang Up (Sequence No. 555)
,
Initialize and Dial (Sequence No. 562)
Initialize and Dial (Sequence No. 572)
Initialize and Dial (Sequence No. 582)
Initialize Modem (Specialized) (Sequence No. 560)
Initialize Modem (Specialized) (Sequence No. 570)
Initialize Modem (Specialized) (Sequence No. 580)
,
,
,
Password (Sequence No. 552)
Set Modem (General-purpose) (Sequence No. 550)
,
sequences, K3T_ Intelligent Signal Processor
General-purpose Command (Sequence No. 339)
,
Model Data Read (by Unit Number) (Sequence No. 337)
,
Model Data Read (Continuous Units) (Sequence No. 338)
,
Read Display Value (PV) (by Unit Number) (Sequence No.
335)
,
Read Display Value (PV) (Continuous Units) (Sequence No.
336)
,
Read Holding Data (Sequence No. 332)
Read Holding Data BH (Continuous Units) (Sequence No.
334)
,
Read Holding Data PH (Continuous Units) (Sequence No.
333)
,
Read Set Value (by Unit Number) (Sequence No. 317)
,
Read Set Value H (Continuous Units) (Sequence No. 319)
,
Read Set Value H with Bank (Continuous Units) (Sequence
No. 324)
,
Read Set Value HH (Continuous Units) (Sequence No. 318)
,
Read Set Value HH with Bank (Continuous Units) (Sequence
No. 323)
,
Read Set Value L (Continuous Units) (Sequence No. 320)
,
Read Set Value L with Bank (Continuous Units) (Sequence
No. 325)
,
Read Set Value LL (Continuous Units) (Sequence No. 321)
,
Read Set Value LL with Bank (Continuous Units) (Sequence
No. 326)
,
Read Set Value O1 with Bank (Continuous Units) (Sequence
No. 331)
,
Read Set Value O2 with Bank (Continuous Units) (Sequence
No. 330)
,
Read Set Value O3 with Bank (Continuous Units) (Sequence
No. 329)
,
Index
Read Set Value O4 with Bank (Continuous Units) (Sequence
No. 328)
,
Read Set Value O5 with Bank (Continuous Units) (Sequence
No. 327)
,
Read Set Value with Bank (by Unit Number) (Sequence No.
322)
,
Reset (by Unit Number) (Sequence No. 300)
,
Reset Control (Continuous Units) (Sequence No. 301)
Write Set Value (by Unit Number) (Sequence No. 302)
,
Write Set Value H (Continuous Units) (Sequence No. 304)
,
Write Set Value H with Bank (Continuous Units) (Sequence
No. 309)
,
Write Set Value HH (Continuous Units) (Sequence No. 303)
,
Write Set Value HH with Bank (Continuous Units) (Sequence No. 308)
Write Set Value L (Continuous Units) (Sequence No. 305)
,
Write Set Value L with Bank (Continuous Units) (Sequence
No. 310)
,
Write Set Value LL (Continuous Units) (Sequence No. 306)
,
Write Set Value LL with Bank (Continuous Units) (Sequence
No. 311)
,
Write Set Value O1 with Bank (Continuous Units) (Sequence
No. 316)
,
Write Set Value O2 with Bank (Continuous Units) (Sequence
No. 315)
,
Write Set Value O3 with Bank (Continuous Units) (Sequence
No. 314)
,
Write Set Value O4 with Bank (Continuous Units) (Sequence
No. 313)
,
Write Set Value O5 with Bank (Continuous Units) (Sequence
No. 312)
,
Write Set Value with Bank (by Unit Number) (Sequence No.
307)
,
sequences, V500/V520 Bar Code Reader
BCR Connection Confirmation (V500) (Sequence No. 358)
,
BCR Function Read (V500) (Sequence No. 355)
BCR Function Write (V500) (Sequence No. 354)
BCR Initialize (V500) (Sequence No. 362)
,
BCR Read Start (Sequence No. 350)
,
BCR Read Stop (Sequence No. 351)
,
Complete Data Read (Sequence No. 353)
,
Data Continuous Read (Interrupt) (V500) (Sequence No.
361)
,
Data Continuous Read (Interrupt) (V520) (Sequence No.
364)
,
Data Continuous Read (Scan) (V500) (Sequence No. 360)
,
Data Continuous Read (Scan) (V520) (Sequence No. 363)
,
Data Read (Sequence No. 352)
,
General-purpose Command 1 (Sequence No. 365)
General-purpose Command 2 (Sequence No. 366)
Log Data Clear (V500) (Sequence No. 359)
,
Log Data Output Request (V500) (Sequence No. 356)
Preset Data Set (V500) (Sequence No. 357)
,
System Setting
sequences, V600/V620 ID Controller
Auto-read (ASCII/1) (Sequence No. 508)
,
Auto-read (Hexadecimal/1) (Sequence No. 509)
Auto-write (ASCII/1) (Sequence No. 526)
,
,
Auto-write (Hexadecimal/1) (Sequence No. 527)
,
Command Processing Cancel (Sequence No. 543)
Control (Sequence No. 541)
,
Data Check (Sequence No. 540)
,
Index
Error Information Read (Sequence No. 542)
,
General-purpose Command (Sequence No. 546)
Polling Auto-read (ASCII) (Sequence No. 510)
Polling Auto-read (ASCII/2) (Sequence No. 511)
Polling Auto-read (ASCII/4) (Sequence No. 512)
Polling Auto-read (ASCII/4) (Sequence No. 513)
Polling Auto-read (Hexadecimal) (Sequence No. 514)
Polling Auto-read (Hexadecimal/2) (Sequence No. 515)
Polling Auto-read (Hexadecimal/4) (Sequence No. 516)
Polling Auto-read (Hexadecimal/8) (Sequence No. 517)
Polling Auto-read Command Processing Cancel (Sequence
No. 544)
,
Polling Auto-write (ASCII/2) (Sequence No. 528)
,
Polling Auto-write (ASCII/4) (Sequence No. 530)
,
Polling Auto-write (ASCII/8) (Sequence No. 532)
,
Polling Auto-write (Hexadecimal/2) (Sequence No. 534)
,
Polling Auto-write (Hexadecimal/4) (Sequence No. 536)
,
Polling Auto-write (Hexadecimal/8) (Sequence No. 538)
,
Polling Auto-write Command Processing Cancel (Sequence
No. 545)
,
Polling Auto-write Subcommand (ASCII/2) (Sequence No.
529)
Polling Auto-write Subcommand (ASCII/4) (Sequence No.
531)
Polling Auto-write Subcommand (ASCII/8) (Sequence No.
533)
Polling Auto-write Subcommand (Hexadecimal/2) (Sequence No. 535)
,
Polling Auto-write Subcommand (Hexadecimal/4) (Sequence No. 537)
,
Polling Auto-write Subcommand (Hexadecimal/8) (Sequence No. 539)
,
Read (ASCII/1) (Sequence No. 500)
Read (ASCII/2) (Sequence No. 501)
Read (ASCII/4) (Sequence No. 502)
Read (ASCII/8) (Sequence No. 503)
Read (Hexadecimal/1) (Sequence No. 504)
,
Read (Hexadecimal/2) (Sequence No. 505)
,
Read (Hexadecimal/4) (Sequence No. 506)
,
Read (Hexadecimal/8) (Sequence No. 507)
,
Write (ASCII/1) (Sequence No.518)
Write (ASCII/2) (Sequence No. 519)
Write (ASCII/4) (Sequence No. 520)
Write (ASCII/8) (Sequence No. 521)
Write (Hexadecimal/1) (Sequence No. 522)
,
Write (Hexadecimal/2) (Sequence No. 523)
,
Write (Hexadecimal/4) (Sequence No. 524)
,
Write (Hexadecimal/8) (Sequence No. 525)
,
sequences, Visual Inspection System
Arbitrary Measurement Value Acquisition (F200) (Sequence
No. 457)
,
Binary Level Modification (F200/300) (Sequence No. 482)
,
Camera Change (Decrease by 1) (F200/300) (Sequence No.
480)
Camera Change (Increase by 1) (F200/300) (Sequence No.
481)
Camera Designation and Positioning (F350) (Sequence No.
471)
Character String Inspection and Character Inspection (F350)
(Sequence No. 474)
Continuous Measurement Execution (Interrupt) (F200) (Sequence No. 452)
,
Continuous Measurement Execution (Interrupt) (F300) (Sequence No. 462)
,
Continuous Measurement Execution (Scan) (F200) (Sequence No. 451)
,
Continuous Measurement Execution (Scan) (F300) (Sequence No. 461)
,
Evaluation Condition Change (F200) (Sequence No. 456)
,
General-purpose Command (Send) (Sequence No. 494)
General-purpose Command (Send/Receive) (Sequence No.
495)
Illumination Fluctuation Follow Execution (F300) (Sequence
No. 465)
,
Inspection Execution and Character Inspection (F350) (Sequence No. 473)
,
Measurement Execution (F200) (Sequence No. 450)
Measurement Execution (F300) (Sequence No. 460)
Measurement Execution and Positioning (F350) (Sequence
No. 470)
,
Measurement, Inspection Termination (Sequence No. 493)
,
Reference Object Registration (Criterion) (F200) (Sequence
No. 455)
,
Reference Object Registration (Group) (F200) (Sequence No.
453)
Reference Object Registration (Reference Position) (F200)
(Sequence No. 454)
Reference Object Registration Command 1 Execution (F300)
(Sequence No. 463)
Reference Object Registration Command 2 Execution (F300)
(Sequence No. 464)
Reset (F200/300) (Sequence No. 483)
,
Scene Switching (Arbitrary) (Sequence No. 492)
,
Scene Switching (Decrease by 1) (Sequence No. 490)
,
Scene Switching (Increase by 1) (Sequence No. 491)
Scene Switching and Positioning (F350) (Sequence No. 472)
,
Serial Communications Boards error information
,
123 installation
,
14 replacement
,
135 specifications
,
8 serial communications modes
1:1 Data Link
,
3
,
4
,
6
,
110
1:1 NT Link
,
3
,
4
,
7
1:N NT Link
,
3
,
4
,
7
Host Link
,
3
,
5
,
34 no-protocol
,
2
,
4
,
6
,
100
NT Link
,
116 protocol macro
,
3
,
5
,
58 setting
,
29 settings flags and control bits
,
27
See also PC Setup switches
,
13 soldering
,
25 specifications
Serial Communications Boards
,
8 standard system protocols
,
63
,
communications problems
,
79 examples
,
78 modifying
,
64 switches
,
13 synchronization
RS-232C ports
,
11
RS-422A/485 ports
,
12
SYSMAC WAY
See also Host Link
417
418
T
Temperature Controllers
,
5 terminating resistance switch
,
13 trace function protocol macros
,
63 troubleshooting
,
121
,
124
1:N NT Link errors
Host Link errors
,
132
,
124 protocol macro errors
,
127
TXD(
) instruction
,
34
,
104
,
106
Host Link
,
36
V
V500/V520 Bar Code Reader
,
63 connections
,
protocols sequences
V600/V620 ID Controller
,
63 connections
,
protocols sequences
Visual Inspection System connections
,
protocols sequences
Visual Inspection Units
,
63
W
weight
,
8 wiring
,
17 connectors precautions
,
23
,
18
RS-232C ports
,
20
RS-422A/485 ports
,
21
Index
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W365-E1-02
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
01
02
Date
September 1999 Original production
April 2002
Revised content
The following changes were made.
Page xiii: Line added to warning.
Page 22: Third graphic changed.
Page 23: Graphic added before note.
Page 29: Information added to second row.
Pages 32, 71: Note added.
Page 88: Text in graphic changed in one place.
Page 95: Information added after graphics.
Page 126: New row inserted after first row.
Page 127: Changes made to bottom table.
Page 147: “#0000” changed to “000.”
Page 287: Changes made to Note 1.
Pages 289, 290, 291, 292, 295, 298, 300: “Most significant bit” changed to “5th digit BCD.”
419
OMRON CORPORATION
FA Systems Division H.Q.
66 Matsumoto
Mishima-city, Shizuoka 411-8511
Japan
Tel: (81)559-77-9181/Fax: (81)559-77-9045
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
1 East Commerce Drive, Schaumburg, IL 60173
U.S.A.
Tel: (1)847-843-7900/Fax: (1)847-843-8568
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
Singapore 239920
Tel: (65)6835-3011/Fax: (65)6835-2711
Authorized Distributor:
Cat. No. W365-E1-02 Note: Specifications subject to change without notice.
Printed in Japan
Download
Advertisement
Key features
Provides 2 serial comms ports
Supports protocol macros
Supports NT Links
Increases number of serial ports
Compatible with CQM1H-series PCs
Supports Host Link communications
Supports No-protocol communications
Supports 1:1 Data Links
Increases PC’s functionality
Easy to install and use
Frequently asked questions
The Serial Communications Board is installed in Inner Board slot 1 of a CQM1H-series CPU Unit. This is explained in detail in Section 2 of the manual, which covers board components and installation.
You can connect a wide range of devices to the Serial Communications Board, including host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Consoles). The type of device you can connect depends on the communication mode you choose.
You can configure the Serial Communications Board using various settings and control bits. These are described in detail in Section 3, which covers default settings and related bits/flags.