Omega WT-2000 Owner Manual


Add to my manuals
30 Pages

advertisement

Omega WT-2000 Owner Manual | Manualzz
TM
User’s Guide
Shop online at
omega.com
e-mail: [email protected]
For latest product manuals:
www.omegamanual.info
WT-2000
Thermal Wind Tunnel
omega.com [email protected]
U.S.A.
Headquarters:
Servicing North America:
Omega Engineering, Inc.
Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660
Fax: (203) 359-7700
e-mail: [email protected]
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves
the right to alter specifications without notice.
WT-2000 Thermal Wind Tunnel
Table of
Contents
Table of Contents
Section ........................................................................... Page
Section 1 Introduction ................................................................................. 1-1
1.1 Description .............................................................................. 1-1
1.2 Unpacking ............................................................................... 1-1
Section 2
Operation ..................................................................................... 2-1
2.1 Setting Up the Wind Tunnel Precautions .......................... 2-1
2.2 Placing a Unit Under (UUT) in the Wind Tunnel ............ 2-2
2.3 Operating the Wind Tunnel ................................................. 2-2
2.4 PC Interface (Optional) ......................................................... 2-2
2.4.1 Introduction ................................................................... 2-2
2.4.2 System Requirements ................................................... 2-2
2.4.3 Software Installation ..................................................... 2-3
2.4.4 Driver Installation ......................................................... 2-7
2.5 WT-2000 PC Interface Program ......................................... 2-10
2.5.1 Launch Program .......................................................... 2-10
2.5.2 Connecting to the WT-2000 Controller .................... 2-10
2.5.3 Using the Program to Control the Wind Tunnel .... 2-11
Section 3 Sensing ......................................................................................... 3-1
3.1 Ports ......................................................................................... 3-1
3.2 Notes ........................................................................................ 3-1
Section 4 Calibration ................................................................................... 4-1
4.1 Hot Wire Anemometer Calibration ..................................... 4-1
Section 5
RS232 Communication ..............................................................
5.1 Introduction ............................................................................
5.2 Serial Communication Parameters ......................................
5.3 Commands ..............................................................................
5-1
5-1
5-1
5-1
Section 6 Specifications .............................................................................. 6-1
6.1 Specifications .......................................................................... 6-1
6.2 Hot Wire Anemometer Correction Factors ........................ 6-1
Section 7 Troubleshooting ......................................................................... 7-1
7.1 Troubleshooting ..................................................................... 7-1
Section 8 Maintenance ................................................................................ 8-1
8.1 Maintenance ........................................................................... 8-1
i
List of
Figures
WT-2000 Thermal Wind Tunnel
List of Figures
Figure
Description:........................................................ Page
1.
Wind Tunnel Door Slide and Exhaust End Views ............................. 1-2
2.
Wind Tunnel Top and In-take End Views ........................................... 1-3
3.
Electrical Control Box Front and Side Views ...................................... 2-1
4.
Electrical Control Box Rear Panel ......................................................... 2-1
5.
Welcome Screen........................................................................................ 2-3
6.
License Agreement Screen ..................................................................... 2-4
7.
Select Installation Folder Screen ............................................................ 2-4
8.
Add Desktop Icon and Quick Launch Icon Screen ............................. 2-5
9.
Confirm Installation Screen ................................................................... 2-5
10. Software Installation Screen ................................................................... 2-6
11. Software Installation Complete Screen ................................................ 2-6
12. Found New Hardware Notice Box ....................................................... 2-7
13. Welcome to the Found New Hardware Screen ................................... 2-8
14. Install Software Automatically Screen ................................................. 2-8
15. Completing the Found New Hardware Screen .................................. 2-9
16. Start Button/Launch Program Screen ................................................ 2-10
ii
Introduction
1
Section 1 - Introduction
1.1 Description
The new Thermal Wind Tunnel Model WT-2000 is designed to produce variable
flow rates inside a rectangular 17 by 3 1⁄4" cross sectional area test chamber. The
Wind Tunnel has an electronic control unit where it controls the four compact, high
power density fans. Velocity can be controlled via simple push button user input,
or by the Free PC based software control via USB cable for optimum performance.
The Thermal Wind Tunnel is recommended for the testing of circuit boards and
heat sinks, as well as other temperature related products. The four fans can be
controlled independently, in groups of two, or all together to produce a wide
range of different air flows.
OMEGA offers a complete line of temperature sensing equipment including
thermocouple and RTD probes and their corresponding panel and bench top
meters as well air velocity meters such as hot wire anemometers.
Figure 1 and 2 – Illustrate the important components of the wind tunnel as well
as its overall dimensions (1.2, 1.3). Figure 3 – Shows the front and side view of
the Electronic Control Box (2.1). Figure 4 – Shows the rear panel of the Electronic
Control Box (2.1).
1.2 Unpacking
Remove the packing list and verify that you have received all equipment. If
you have any questions a bout the shipment, please call Customer Service
Department at 1-800-622-2378 or 203-359-1660. We can also be reached on
the Internet at omega.com, e-mail: [email protected]. When you receive the
shipment, inspect the container and equipment for any signs of damage. Note
any evidence of rough handling in transit and immediately report any damage
to the shipping agent.
NOTE:
The carrier will not honor any claims unless all shipping
material is saved for their examination. After examining and
removing contents, save packing material and carton in the
event reshipment is necessary.
Items included with your WT-2000 Package:
1. Wind Tunnel
2. Electronic Control Box
3. Power Cord
4. PC Interface Control Software
5. USB Cable for PC Interface
6. Fan Control Cable
7. Package of Compression Fittings with PTFE Compression Ferrules
8. Package of Port Hole Caps
9. Operator’s Manual
1-1
1-2
Figure 1. Wind Tunnel Door Side and Exhaust End Views
DIMENSIONS mm (in)
CARRYING HANDLE
1
Introduction
Figure 2. Wind Tunnel Top and In-take End Views
Introduction
1
1-3
2
Operation
Figure 3. Electrical Control Box Front and Side Views
Figure 4. Electrical Control Box Rear Panel
Section 2 - Operation
2.1 Setting Up the Wind Tunnel – Precautions
A wind tunnel’s performance can be severely diminished if not used properly.
Please follow the following tips:
• Do not use the wind tunnel in rooms with less than 1800 cubic feet. The air
flow creates currents that undermine the wind tunnel’s accuracy.
• Place the wind tunnel on a flat and level surface.
• Avoid locating the intake and exhaust toward open windows, door ways or
corridors where people are walking. The effect of air current changes across
the intake has a severe affect on the flow rate changing in the wind tunnel.
• There should be at least 1.5 m (5 feet) clear space in front of and behind the
wind tunnel. No obstacles, moving objects, or open doors or windows.
• Locate the exhaust towards the largest open area of the room to minimize
room air currents. The higher the flow rate, the more chance of creating
currents.
• The air flow rate of the wind tunnel depends on the air temperature and
barometric pressure. Adjust it accordingly. See Section 6.2 for Hot Wire
Anemometer correction factors.
• This instrument should only be used for its intended purpose in accordance to
the instruction manual.
2-1
Operation
2
2.2 Placing a Unit Under Test (UUT) in the Wind Tunnel
• Ensure that the Electronic Control unit is off before opening the wind tunnel
door or access panel.
• Loosen the screws that secure the slides by turning them counterclockwise to
allow them to move freely.
• Secure the UUT by using the clips or slots in the slides. Secure the slides by
turning the screws clockwise. Ensure that the UUT is as close as possible to
the center of the slide assembly of the wind tunnel. Keep in mind that even the
smooth inner walls of the wind tunnel may introduce some turbulence in the
flow of air.
2.3 Operating the Wind Tunnel
Before operating the wind tunnel, please follow all the precautions stated in the
previous sections and then proceed as follows:
1- Make sure the power switch in the back of the electronic control unit is off,
then connect the cable from the DC Fans on the Wind Tunnel to the back of
the Electrical Control box labeled ‘Fan Control’.
2- Connect the AC input of the Control unit to a line voltage (90 to 264 VAC @
50/60 Hz) with the Power cord provided. Please refer to the accessory table
for power cords for other countries.
3- Turn on the Power switch in the back. The power LED indicator on the front
of the control box will turn on.
4- The four fan LEDs show which fan velocity is going to be modified using
the up and down arrows. Once a fan velocity has been set using the arrow
keys it will maintain the same velocity, even if the FAN button is pushed to
control a different fan or combination of fans. Pushing the FAN button cycles
through the possible selections: Fan1 only, Fan2 only, Fan3 only, Fan4 only,
Fan1&Fan3, Fan2&Fan4, Fan2&Fan3, Fan1&Fan4, or all 4 Fans. For optimum
performance use the supplied PC Interface Software to control the fans. See
Section 2.4 for details.
5- To change the fan speed, use the arrow up and arrow down keys. They may
be pressed and released for small adjustments, or held for larger adjustments.
2.4 PC Interface (Optional)
2.4.1 Introduction
After following the steps in the previous section for Operating the Wind Tunnel,
you can optionally connect the USB Cable from a PC with the Omega Wind
Tunnel Control Software to the Wind Tunnel Electrical Control Box. This simple
software allows for quick, precise open loop control of the DC Fan velocities.
Connecting the USB cable to the electrical control Box will “lockout” the front
panel buttons on the Electrical control box. The user can verify that the front
panel is “locked out” when the 4 Fan LEDs are extinguished.
In order to use the PC Interface, you must install the software from the CD-ROM
provided with your order of the WT-2000.
2-2
2
Operation
2.4.2 System Requirements
Your PC should meet the following minimum requirements:
• Pentium Class or higher processor
• Hard Drive Space: 30 MB
• Ram: 256 MB
• 1 Available USB Port
• 1 CD-ROM Drive
2.4.3 Software Installation
Insert the WT-2000 User Software CD that was included with your unit into the
CD-ROM drive on your PC. Your system should begin the installation process
automatically. If it does not automatically start, open my computer and double
click on the D: Drive (or the drive in which the User Software CD is located).
Then double click the Setup.exe installation file.
Figure 5. Welcome Screen
This Welcome Screen should be visible on your computer screen. Click the “Next
>” button to continue installing the program.
2-3
Operation
2
Figure 6. License Agreement Screen
Please read the license agreement and you must select “Agree” to continue
installing your program. After making your selection, click the “Next >” button.
The setup wizard will now install the software.
Figure 7. Select Installation Folder Screen
From this screen you can select the folder were you want the program files
installed on your PC. The default setting will install the software in your
“Program Folders” under the folder structure “Program Folders\Omega\
WT-2000.” You may optionally install the software for just the “Current user”
windows account or for “Anyone who uses this computer.” Click the “Next >”
button to continue installing the program.
2-4
2
Operation
Figure 8. Add Desktop Icon and Quick Launch Icon Screen
From this screen you can optionally add an Icon for the WT-2000 User Software
to your Windows desktop and/or quick launch toolbar.
Figure 9. Confirm Installation Screen
Click the “Next >” button to confirm installation settings.
2-5
Operation
2
Figure 10. Software Installation Screen
A progress bar indicates installation progress.
Figure 11. Software Installation Complete Screen
Congratulations! You have finished installing the WT-2000 User Software on
your computer. To close the finished setup program, click the “Close” button.
2-6
2
Operation
2.4.4 USB Driver Installation
To install the USB software drivers that are required for your WT-2000
Controller to work properly please follow these procedures.
NOTE:
You need to have the User Software CD that was supplied
with your WT-2000 Wind Tunnel and Controller loaded into
the CD-ROM drive of your PC.
1. Make sure the WT-2000 Controller power switch is in the off position before
connecting it to the computer using the USB cable.
2. Connect the WT-2000 Controller by connecting the supplied USB cable
between an unused USB port and the WT-2000 Controller.
3. Turn the power switch on the back of the WT-2000 Controller to the on “|”
position.
4. You should see a notice box that indicates that you computer has “Found New
Hardware.”
Figure 12. Found New Hardware Notice Box
5. Your computer will then launch the Found New Hardware Wizard. Follow
the instructions indicated on the Wizard boxes and the additional instructions
noted in this manual.
NOTE:
After completing the Found New Hardware Wizard, your
system will ask that you repeat this process. This is normal.
You should repeat the steps outlined here twice. After the
second driver is installed you should then get the “New
Hardware Ready for Use” notification.
2-7
Operation
2
Figure 13. Welcome to the Found New Hardware Wizard Screen
From this box you should check the “No, not this time” button. Then click the
“Next >” button to continue with the driver installation process.
Figure 14. Install Software Automatically Screen
Next, check the “Install the software automatically” button. Then click the “Next
>” button to continue.
2-8
2
Operation
Figure 15. Completing the Found New Hardware Wizard Screen
This screen will be displayed to indicate that the software drivers have been
installed. You should click the “Finish” button to complete the process.
2-9
Operation
2
2.5 WT-2000 PC Interface Program
2.5.1 Launch Program
To launch the WT-2000 PC Interface program on your PC, begin by accessing
the “Programs” list under your “Start” menu. Next, scroll through the list of
program folders to find the “Omega” folder. Inside that folder click on the “WT2000 PC Interface” program link. (Additionally, if you selected the appropriate
options during installation, there should also be a WT-2000 PC Interface Icon on
the Desktop and/or in the Quick Launch toolbar that you can click to start the
program.)
Figure 16. Start Button/Launch Program Screen
2.5.2 Connecting to the WT-2000 Controller
Ensure that the line cord, fan control cable and USB cable are connected to the
WT-2000 Controller as specified in sections 2.3 and 2.4.1.
The available Com ports will load when the program is started. To refresh
this list, Click “File” on the menu bar and click “Refresh COM Ports.” Select
the COM Port which has been assigned to the WT-2000 Controller, and click
Connect. The rest of the controls will become accessible after a proper connection
has been established.
2-10
2
Operation
2.5.3 Using the Program to Control the Wind Tunnel
There are two distinct ways to control the wind tunnel using the WT-2000 PC
interface:
1) On the left of the window are the single fan controls. The user can enter a
value between 0% and 100% by either typing a value in the text box, using the
mouse to click the up or down buttons on the program, or by using the up and
down arrows on the keyboard. When typing in a value, the user must press
“Enter,” “Return,” or “Tab” on the keyboard to update the value and move to
the next control; or use the mouse to navigate to another control.
2) On the right, there are fan selection boxes and group preset buttons. To use
them, check off the fans for which you want to control, and use the preset
buttons to change the velocity for each selected fan. The new velocities will be
reflected in the Single Controls on the left side of the page, and fine tuning can
be completed in the Single Controls box.
NOTE:
The value in the control represents a linear percentage of fan
velocity within the reliable operation of the fan. The values
are NOT a true percent of fan velocity, because the fans
do not operate reliably below a certain threshold. Both the
Controller alone and the Software interface establish the 1%
value as slightly above that threshold so that the fans are
always running within their reliable operation range.
2-11
Sensing
3
Section 3 - Sensing
3.1 Ports
The WT-2000 Wind tunnel has been built with the ability to accommodate
for a wide variety of sensors, including temperature sensing devices (such
as thermocouples, RTDs, and thermistors), and air velocity sensors (such as
hot wire anemometers). There are several ports that can be used to allow for
sensors to be inserted into the wind tunnel for measurement during operation.
Compression fittings and port hole caps have been included for insertion into
desired ports.
3.2 Notes
There are many factors to consider while sensing temperature and flow inside
the wind tunnel. Please consider the following points:
• Open ports may dramatically affect air flow. Please seal measurement ports
and close the door tightly to ensure proper flow.
• Air flow will change with the size and shape of the unit under test.
• Avoid the use of large temperature sensing probes on small devices. They may
act as heat sinks; especially with high air velocity. It is suggested to use surface
mounted types of temperature sensors for better accuracy.
• Avoid damage to the Honeycomb flow straightener.
• When using the compression fittings for holding probes in place, use the
Teflon ferrule inserts to hold the probe by hand tightening the compression
fitting. Do not use tools or wrenches.
3-1
4
Calibration
Section 4 - Calibration
4.1 Hot Wire Anemometer Calibration
The wind tunnel produces a highly uniform flow and is therefore capable of
calibrating hot wire anemometers. It is recommended to use one calibrated
probe as a standard and place the probe to be calibrated in close proximity but
not in opposition to airflow. The probes should be of the same type for the best
results. See section 6.2 for hot wire anemometer correction factors.
4-1
RS232 Communication
5
Section 5 - RS232 Communication
5.1 Introduction
The Wind Tunnel controller has the ability for RS 232 communication through
a USB port. There is a USB to Serial RS 232 communication chip within the
controller that allows for a PC with the proper drivers installed to recognize the
WT-2000 controller as a serial RS 232 device connected through a COM Port.
This allows for the simplicity of RS 232 communication and the convenience of
using any open USB port.
5.2 Serial Communication Parameters
NOTE:
Note that both the WT-2000 Controller and the computer
must be communicating with the same serial communications
parameters to establish a working communication link.
The serial communications parameters should be as follows:
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
5.3 Commands
Valid commands are in the following format:
1) ENQ [CR/LF] - a command that causes the controller to return with the
following message:
WT-2000
xxxxxx
where xxxxxx is the firmware version number.
2) PWM *fan#* *vel* [CR/LF]
where *fan#* is a value between 0 and 3; each number representing one of the
4 fans to control. Fan 0 is the highest fan in the assembly and Fan 3 is the fan
closest to the base of the wind tunnel.
*vel* is a value between 0 and 2400. The fans will not start reliably below a value
of 300, so they should never be issued a command that would have them run at
a value greater than 0 but less than 300.
The controller will echo back the command in the following format:
PWM *fan#* = *vel* to confirm that the message was received.
5-1
5
RS232 Communication
If the message was attempting to force a parameter out of range, the controller
will send a message to show what the value was actually changed to (typically
the highest or lowest value depending upon which direction the outgoing
message was out of range). The controller may send back BAD COMMAND if it
receives an invalid message. Note, only the RS232 protocol is supported by the
USB serial port. A standard USB cable with one “A” connector end on the PC
side end and a “mini B” connector end on the controller side should be used.
[CR/LF] - Every transmission must be terminated with a carriage return
[CR] character. The line feed [LF] character is optional. This can usually be
accomplished by pressing the enter or return key.
5-2
Specifications
6
Section 6 - Specifications
6.1 Specifications
Test Chamber:
17 x 3.25" Cross Section
Flow Rates:
0 to 5 m/s (1000 FPM)
Speed:
3800 RPM
DC Fan Motor:
12 Vdc @ 0.47A ea. (5.6W ea.)
Noise:
61 dBA from 1 meter away
Power Input:
90-264 Vac @ 47-63Hz
Fuse:
2A Fast Acting 5x20mm Cartridge Type
Operating Temperature:
5 to 45°C (41 to 113°F)
Operating Relative Humidity:
Less than 80% RH without condensation
Size:
Wind Tunnel:
80.5 L x 18.4 W x 48.4 cm H
(31.7 L x 7.3 W x 19.1" H)
Electrical Control Box:
16 L x 13.8 W x 6.7 cm H
(6 1⁄4 L x 4 7⁄16 W x 2 11⁄16" H)
Weight:
Wind Tunnel:
12.48 kg (27.5 lb)
Electrical Control Box:
0.9 kg (2 lb)
NOTE:
All specifications measurements taken at an ambient room
temperature of 70°F (22.2°C) with less than 80% relative
humidity and 29.92 inches of Hg barometric pressure.
6.2 Hot Wire Anemometer Correction Factors
When using Hot Wire Anemometers in conditions that are other than the
standard condition - 29.92 inches of Hg and 70°F (22.2°C), correction factors
must be used. The correction factor equation for K1 is as follows.
K1 = (29.92/P) x (460 + T)/530; where
P = the Barometric pressure in inches of Hg
T = the ambient temperature in °F.
There is a second correction factor which is a function of the air probe geometry
(K2).
6-1
5
Specifications
Table 1 lists K2 for different Hot Wire Anemometer probes offered by Omega
Engineering. So the actual air velocity is as follows:
Actual Velocity (FPM) = Measured average value over one minute time interval
(FPM) x K1 x K2.
Model No.
Description
Half Velocity Full Velocity
FMA-904Hot Wire 0 -2000 FPM
1.04
1.00
FMA-905Hot Wire 0 -5000 FPM
1.00
1.00
HHF42Hot Wire 40-3940 FPM
1.04
1.00
Table 1 – K2 Correction Factor
Example: An FMA-904 Hot Wire anemometer is being used in the Wind Tunnel
at half velocity (~500 FPM). The measured environmental conditions are:
Barometric Pressure = 27.88 inches of Hg
Ambient Temperature = 80°F
The FMA measures 442 FPM. Calculate the actual air speed:
Actual Air speed (FPM) = Measured average value over one minute time
interval (FPM) x K1 x K2.
K1 = (29.92/P) x (460 + T)/530
K1= (29.92/27.88) x (460 + 80)/530
K1 = 1.093
From Table 1, K2 for FMA-904 @ Half Velocity is 1.04.
Actual Air speed = 502 FPM
6-2
Troubleshooting
7
Section 7 - Troubleshooting
7.1 Troubleshooting
Problem
Solution
Scraping noise from area of fan Check for obstructions, Realign position of
the fans
The wind tunnel is not
on- LED power
indicator is not on
• Make sure the motor controller is plugged
into a live outlet.
• Make sure the ON/OFF switch on the electrical control box is in the “ON” position
• Check the fuse in the electrical control box
controller-if blown replace with same type
and rating.
The wind tunnel is not
on – fan does not turn
• Be sure the fan control cable is connected to
both the wind tunnel and the electrical control box.
• Check for Fan obstructions
•P
ress the FAN key until all 4 fans’ LEDs
are lit indicating control of all 4 fans. Press
and hold the UP arrow key to ramp up the
fans in order to confirm that all 4 fans are
working properly.
Electrical Control Box
• Disconnect the USB cable from the
keys are inoperative, but
computer and the Electrical Control Box to
the LED power indicator unlock the keypad.
is lit
•C
ycle Electrical Control Box Power by
switching the ON/OFF switch into the OFF
position and then turning back ON to reset
the Control Box.
7-1
8
Maintenance
Section 8 - Maintenance
8.1 – Maintenance
The following points should be adhered to for a maintenance-free operation of
the wind tunnel.
• Make sure the wind tunnel is operating in a relatively dirt-free room that is at
least 1,800 cubic feet.
• If the fan blades, guards, or honeycomb flow straightener should get dirty for
any reason, they can be cleaned very easily using a mild soap or detergent. Do
not use any solvents.
• Use only light touch to clean the honeycomb flow straightener. Do not use
excessive pressure, as this will damage it.
Spare Parts and Replacement Parts
8-1
Description
Omega Part Number
Compression Fittings (1/4")
SSLK-14-14
Compression Fittings (1/2")
SSLK-12-12
Reducer (1/2 to 1/4")
RB-12-14-SS
Honeycomb Flow Straightener
WTT-0014
Thumb Screws
WT-0060
USB Cable
UWTC-0006
Fan Control Cable
WTT-0063
Power cord (USA, Mexico, Canada)
POWER CORD-MOLDED
Power cord (Denmark)
POWER CORD-DM
Power Cord (Continental Europe)
POWER CORD-E-10A
Power cord (Italy and Ireland)
POWER CORD-IT
Power cord (United Kingdom)
POWER CORD-UK
Power cord for all countries
(Stripped Ends) 250VAC max
POWER CORD-SE
WT-2000 Thermal Wind Tunnel
NOTES:
8-2
WT-2000 Thermal Wind Tunnel
NOTES:
8-3
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal one (1) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for
any damages that result from the use of its products in accordance with information provided
by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR NON-WARRANTY REPAIRS, consult
FOR WARRANTY RETURNS, please have the
OMEGA for current repair charges. Have
following information available BEFORE contacting
the following information available BEFORE
OMEGA:
contacting OMEGA:
1.Purchase Order number under which the product
1. Purchase Order number to cover the COST
was PURCHASED,
of the repair,
2.Model and serial number of the product under
2. Model and serial number of the product, and
warranty, and
3. Repair instructions and/or specific problems
3. Repair instructions and/or specific problems
relative to the product.
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
OMEGA is a trademark of OMEGA ENGINEERING, INC.
© Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
TEMPERATURE
M
U Thermocouple, RTD & Thermistor Probes, Connectors,
Panels & Assemblies
M
U Wire: Thermocouple, RTD & Thermistor
M
U Calibrators & Ice Point References
M
U Recorders, Controllers & Process Monitors
M
U Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
M
U Transducers & Strain Gages
M
U Load Cells & Pressure Gages
M
U Displacement Transducers
M
U Instrumentation & Accessories
FLOW/LEVEL
M
U Rotameters, Gas Mass Flowmeters & Flow Computers
M
U Air Velocity Indicators
M
U Turbine/Paddlewheel Systems
M
U Totalizers & Batch Controllers
pH/CONDUCTIVITY
M
U pH Electrodes, Testers & Accessories
M
U Benchtop/Laboratory Meters
M
U Controllers, Calibrators, Simulators & Pumps
M
U Industrial pH & Conductivity Equipment
DATA ACQUISITION
M
U Communications-Based Acquisition Systems
M
U Data Logging Systems
M
U Wireless Sensors, Transmitters, & Receivers
M
U Signal Conditioners
M
U Data Acquisition Software
HEATERS
M
U Heating Cable
M
U Cartridge & Strip Heaters
M
U Immersion & Band Heaters
M
U Flexible Heaters
M
U Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
M
U Metering & Control Instrumentation
M
U Refractometers
M
U Pumps & Tubing
M
U Air, Soil & Water Monitors
M
U Industrial Water & Wastewater Treatment
M
U pH, Conductivity & Dissolved Oxygen Instruments
M4634/0118

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement