INTENDED USE — Suitable for applications requiring both exit sign and unit equipment. Attractive, 8" tall, streamlined design is great for above-the-door applications and other tight fits. Optional high-output version with remote lamps are ideal for emergency egress lighting. Certain airborne contaminants can diminish integrity of acrylic and/or polycarbonate. Click here for Acrylic- Polycarbonate

Compatibility table for suitable uses.

CONSTRUCTION — Engineering-grade thermoplastic housing is impact-resistant, scratch-resistant and corrosion-proof. UL94V-O flame rating. UV-stable resin resists discoloration from natural and man-made light sources.

Rugged unibody housing snaps together with no additional fasteners. Faceplate and back cover are interchangeable on housing. Positive snap-fit tabs hold faceplate securely, yet are easily removable for lamp compartment access. Universal, directional chevron inserts are easily removed and reinserted.

Uniform graphics illumination without shadows or hot spots. Letters are 6" high with 3/4" stroke, with 100 ft. viewing distance rating based upon UL924 standard.

LEDs mounted on primary circuit boards for sign illumination. Low-energy LED lamp in sign operates in normal

(AC input) and emergency (DC input) modes.

Low-profile, integrated test switch/pilot light. Easily viewed bright red status indicator.

Unique track-and-swivel arrangement permits full range of direction of lamp head adjustment. Universal J-box mounting pattern. Tool-less access for maintenance. Conduit entry position on top of unit.

U.S. Patent No. 6,848,798; 6,499,866; 6,142,648; 5,797,673; D379,373; 5,526,251; D484,272;

D473,672; 5,611,163; 5,646,502.

OPTICS — Twin LED lamp heads operate in emergency (DC input) mode with 12 series-parallel white LEDs in each head. Provides redundant light sources to ensure emergency lighting performance. The typical life of the exit LED lamp is 10 years.

ELECTRICAL — Dual-voltage input capability (120/277V). Edge connector on printed circuit board ensures long-term durability.

Current-limiting charger maximizes battery life and minimizes energy consumption. Provides low operating costs.

Short-circuit protection — current-limiting charger circuitry protects printed circuit board from shorts.

Thermal compensation adjusts charger output to provide optimum charge voltage relative to ambient temperature.

Regulated charge voltage maintains constant-charge voltage over a wide range of line voltages. Prevents over/ undercharging that shortens battery life and reduces capacity.

Filtered charger input minimizes charge voltage ripple and extends battery life.

AC/LVD reset allows battery connection before AC power is applied and prevents battery damage from deep discharge.

Single multi-color LED indicator to display two-state charging, test activation and three-state diagnostic test.

Test switch provides manual activation of 30-second diagnostic testing for on-demand visual inspection.

Self-diagnostic testing for 30 seconds every 30 days, 30 minutes at 180-day interval, and 90 minutes annually.

Diagnostic evaluation of LED light source, AC-to-DC transfer, charging and battery condition.

Battery: Sealed, maintenance-free nickel-cadmium battery delivers 90-minute capacity to emergency lamps. Two-state contstant-current charge maximizes battery life and automatically recharges after battery discharge. Low-voltage disconnect prevents excessively deep discharge that can permanently damage the battery. Optional high-output battery to power both local and optional LED remote lamp heads simultaneously.

Notes

Type

HO R0

Thermoplastic Exits

LHQM LED

LED Lamp Head

Nickel-Cadmium Battery

INSTALLATION — Top, end or back mounting. Housing snaps to canopy with positive-locking tabs. Cam locking pin secures housing to canopy.

Easily removed mounting knockouts. Conduit entry knockout for 1/2" flexible conduit. J-box pattern on back panel.

LISTINGS — UL damp location listed standard 50°-104°F (10°-40°C). Meets UL 924, NFPA 101 (current Life

Safety Code), NEC and OSHA illumination standards.

WARRANTY — 5-year limited warranty. (Battery is prorated). Complete warranty terms located at www.AcuityBrands.com/CustomerResources/Terms_and_Conditions.aspx.

Note: Actual performance may differ as a result of end-user environment and application.

All values are design or typical values, measured under laboratory conditions at 25 °C.

Specifications subject to change without notice.

ORDERING INFORMATION

LHQM

Family

LHQM Stencil face, single face plate with extra face plate

Lead times will vary depending on options selected. Consult with your sales representative.

LED

Lamp type

LED Two

1.5W/9.6V white LED

Housing color

(blank) White

B Black

Letter color

R

G

Red

Green

Options

HO

SD

High-output Ni-cad battery

Self-diagnostics

NOM

Example:

Meets Mexican standards 1

HO R0 High-output option, less lamp heads NOM SALIDA Salida signage (non-UL) 2

LHQM LED G

Accessories: Order as separate catalog number.

ELA Q L0309 SD Single LED indoor remote head, white, self-diagnostics 3,4,5 ELA WG3

ELA T Q L0309 SD Twin LED indoor remote head, white, self-diagnostics 3,4,5 ELA WG2M

ELA LQMUS12 ELA QWP L0309 SD Single LED weather-proof remote head, gray, selfdiagnostics 3,4,5

ELA T QWP L0309 SD Twin LED weather-proof remote head, gray, selfdiagnostics 3,4,5

ELA LED M12

ELA Q L0309

ELA T Q L0309

Single LED indoor remote head, white

Twin LED indoor remote head, white 4,5

4,5

ELA QWP L0309 Single LED weather-proof remote head, gray

ELA T QWP L0309 Twin LED weather-proof remote head, gray 4,5

4,5

Wireguard, 30” W x 13-1/2” H x 6” D

Wireguard, 21-1/4” W x 15” H x 12” D

12” white stem kit 7

Single LED remote lamp 8,9

6

6

ELA LED T M12 Twin LED remote lamp 8,9

ELA LED WP M12 Single LED Weather proof remote lamp 8,9

ELA LED T WP M12 Twin LED Weather proof remote lamp 8,9

Notes

1 Available in black or white. Consult factory for options.

2 Only available in white. NOM standard.

3 Only compatible with self-diagnostic option. (ex: HO SD)

4 Also available in black. Add "B" after ELA to order black finish. Example: ELA B Q L0309.

5 Only compatible with HO option . See spec sheet ELA-Q-LED .

6 See spec sheet ELA-WG .

7 See spec sheet ELA-Stemkits .

8 See spec sheet ELA LED (Contractor Select LED Remotes).

9 Not available with SD.

EMERGENCY LHQM-LED

LHQM LED QUANTUM® Exit/Unit Combo

SPECIFICATIONS

Electrical

Primary Circuit

Typical

LED life 1

Red and green LED 10 years

Supply voltage

120

277

Max amps

.05

.03

Max watts

4.3

4.3

BATTERY

Ni-Cad

Voltage

9.6

Typical

Shelf life

3 years

2

Typical life 2

7-9 years

Maintenance none

3

Optimum temperature 4

50-104°F

(10-40°C)

1 Based on continuous operation.

2 At 77°F (25°C).

3 All life safety equipment, including emergency lighting path of egress, must be maintained, serviced and tested in accordance with all National Fire Protection Association and local codes. Failure to perform the required maintenance, service or testing could jeopardize the safety of occupants and will void all warranties.

4 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower temperatures affect life and capacity.

5. Battery life is negatively impacted by many variables including temperature, charging rates, number of cycles and deep discharges due to long periods of time without AC power.

MOUNTING

All dimensions are inches (centimeters).

Shipping weight: 3.6 lbs. (1.6 kgs.).

Top

4-3/4

(11.1)

2-1/4

(5.7)

9

(22.9)

Face

19-1/4

(48.9)

8

(20.3)

12

(30.5)

Test switch/ pilot light

End

1/2” flexible conduit entry knockout

5-5/8

(14.3)

Backplate

Remote Output Capacity

Standard unit

NA

Combo

NA

Combo/high-output battery(HO)

3W

Combo/high-output (HO) and no heads (RO)

6W

4

(10.2)

8

(20.3)

Universal knockout pattern for various standard j-boxes

6

(15.2)

12

(30.5)

LAMP PHOTOMETRICS

QUANTUM LED SERIES – SINGLE COVERAGE

3W Total White LEDs

Using a single unit at a typical 7.5’ mounting height delivers an average illuminance of 1.0 FC over a distance of 24’ on a 3’ path of egress and 18’ on a 6’ path of egress.

1 FC average

1 FC average

24'

Example of single LHQM LED exit illuminating a 3' path of egress

25'

1 FC average

3'

18'

Example of single LHQM LED exit illuminating a 6' path of egress

6'

20'

1 FC average

QUANTUM LED SERIES – MULTIPLE COVERAGE

3W Total White LEDs

Using multiple units at a typical 7.5’ mounting height delivers 25’ center-to-center spacing on a

3’ path of egress and 20’ center-to-center spacing on a 6’ path of egress.

3'

6'

Example of multiple LHQM LED exits illuminating a 3' path of egress

Example of multiple LHQM LED exits illuminating a 6' path of egress

EXTENDED RUN-TIME FOR HIGH-OUTPUT EXITS

Product Run time

LHQM LED HO (no remotes)

LHQM LED HO R0 (no remotes)

3.8 hours

7.5 hours

LHQM-LED

EMERGENCY: One Lithonia Way Conyers, GA 30012 Phone: 800-334-8694 www.lithonia.com © 2012-2017 Acuity Brands Lighting, Inc. All rights reserved. Rev. 08/02/17