Juno N1L Lighting Unit Installation Instructions
Add to My manuals3 Pages
Juno N1L Lighting Unit is a versatile and reliable lighting solution designed for emergency situations. During a power outage, it automatically switches on its LED lamps, providing illumination for at least 90 minutes. With its simple installation process and the ability to mount it on J-boxes or conduits, it's ideal for various indoor locations. The unit also features a "TEST" button for regular testing to ensure its readiness during emergencies.
advertisement
![Juno N1L Lighting Unit Installation Instructions | Manualzz Juno N1L Lighting Unit Installation Instructions | Manualzz](http://s1.manualzz.com/store/data/069751666_1-4334d7a863879c9aeb800b9b3ae14185-360x466.png)
INSTALLATION INSTRUCTIONS
FOR LED EMERGENCY LIGHTING FIXTURE
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS:
SAVE THESE INSTRUCTIONS
IMPORTANT: Let the battery charge up for at least 24 hours. Then normal operation of this unit should take eff ect. To check, press the “TEST” button. The LED lamps on the unit should turn ON. During an electrical power failure, the led lamps will automatically come on for a minimum of 90 minutes. In accordance with
NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer to your local codes for any additional requirements that may apply.
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN
DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE - For your protection, read and follow these warnings and instructions carefully before installing or maintaining this equipment. These instructions do not attempt to cover all installation and maintenance situations.
WARNING: RISK OF FIRE - Lamps are hot. Keep combustible material away from hot parts. Observe lamp manufacture’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed.
•
All service shall be performed by qualified service personnel. This product must be installed and maintained in accordance with the applicable installation codes by a person familiar with the construction operation of the product and the hazards involved.
•
This product must be installed in accordance with the applicable installation codes and ordinances.
•
Before wiring to power supply, turn off electricity at fuse or circuit breaker.
•
Disconnect A.C. power and unplug battery before servicing.
•
Consult your local building code for approved wiring and installation.
•
May be used outdoors under cover. (0°C50°C) .
• Do not let power supply cord touch hot surfaces.
•
Do not mount near gas or electric heater.
•
Equipment should be mounted in locations
and at heights where it will not readily be subjected to tampering by unauthorized personnel.
•
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
•
Do not use this equipment for other than intended use.
• The AC voltage rating of this equipment is specified on the product label.
Do not connect equipment to any other voltage.
DISCONTINUED
One Lithonia Way, Conyers GA 30012 Phone: 800-334-8694
©2016 Acuity Brands Lighting, Inc. Printed in the USA
Rev
8
/2017 P3508 pg 1 of 3
INSTALLATION INSTRUCTIONS
FOR LED EMERGENCY LIGHTING FIXTURE
IMPORTANT: Let the battery charge up for at least 24 hours. Then normal operation of this unit should take effect.
To check, press the “TEST” button. The
LED lamps on the unit should turn ON.
During an electrical power failure, the led lamps will automatically come on for a minimum of 90 minutes. In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for
90 minutes. Refer to your local codes for any additional requirements that may apply.
USE FLEXIBLE CONDUIT ONLY.
INSTALLATION
J-BOX MOUNTING
1.
Feed fixture leads through the back plate and connect to AC power supply (Fig A). For 120V use black and white wires and for
277V, use red and white wires.
2.
Attach back plate to J-Box and secure with screws.
3.
Complete the battery connection.
(Fig. B)
4.
Align snaps and push housing directly onto the back plate (Fig.
C). Apply continuous AC power and press “TEST” button to check light.
CONDUIT
1.
Secure back plate to wall surface.
Route wires through hole in conduit flange and make conduit connection. For 120V, use black and white wires and for 277V, use red and white wires.
2.
Complete the battery connection
(Fig. B).
3.
Align snaps and push housing directly onto the back plate (Fig.
C). Apply continuous AC power and press “TEST” button to check light.
WARNING: Unused wires must be capped using enclosed wire nuts.
FIG. A FIG. B
FIG. C DISCONTINUED
One Lithonia Way, Conyers GA 30012 Phone: 800-334-8694
P3508 pg 2 of 3 ©2016 Acuity Brands Lighting, Inc. the USA
Rev
8
/2017
INSTALLATION INSTRUCTIONS
FOR LED EMERGENCY LIGHTING FIXTURE
NOTE
1.
Max mounting height 8 ft to achieve at least 1 ft-candle of illuminance in emergency mode.
OPERATION
1.
During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
2.
To test, depress the “TEST” switch. The emergency LED lamps will illuminate. When the switch is released, the lamps will go off.
WIRING DIAGRAM
STANDARD HO OPTION (REMOTE CAPABLE)
AC INPUT CONNECTOR
(MOUNTING PLATE)
277V
120V
0V
RED
BLACK
WHITE
CHARGER
BOARD
LAMP
YELLOW(+)
BLUE(-)
YELLOW(+)
BLUE(-)
LAMP
YELLOW(+)
BLUE(-)
Note:
Unused input lead must be properly insulated with wire nut or other approved method.
AC INPUT CONNECTOR
(MOUNTING PLATE)
277V
120V
0V
RED
BLACK
WHITE
YELLOW(+)
BLUE(-)
YELLOW(+)
BLUE(-)
LAMP
CHARGER
BOARD
RED
BLACK
LAMP
BATTERY
READY
TEST
TO REMOTE
TEST
READY
Note:
Use 18-22 AWG stranded heads.
wire to connect remote lamp
DISCONTINUED
One Lithonia Way, Conyers GA 30012 Phone: 800-334-8694
P3508 pg 3 of 3 ©2016 Acuity Brands Lighting, Inc. Printed in the USA
Rev
8
/2017
BATTERY
RED
BLACK
advertisement