4090-9118 Relay IAM with T-Sense
Installation Instructions
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX
®
PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
•
Ground yourself before opening or installing components.
•
Prior to installation, keep uninstalled component wrapped in anti-static material at all times.
Introduction
Installation
The 4090-9118 Relay IAM with T-Sense provides the 4100U FACP output control of one Form-C contact set and input status from a T-Sense monitoring zone. The
Relay IAM with T-sense provides the 4100U FACP with the status/state of the monitored zone. The 4 states that it can indicate are: OPEN, NORMAL,
LIMITED, and SHORT. The LIMITED state occurs when a normally-open device, electrically located between the series resistor and the EOL resistor, activates. The FACP can then annunciate the status of closed devices depending on whether they are before or after the series resistor.
The IDNet channel provides the communication link between the Relay IAM with
T-Sense and 4100U FACP while powering the entire circuit.
The range of possible temperatures under which the 4090-9118 Relay IAM with T-
Sense can function is between 32
°
F (0
°
C) and 120
°
F (49
°
C). This Relay IAM operates normally under non-condensing humidity conditions up to 93% relative humidity at 90° F (32° C).
Relay IAM with T-Sense installation consists of the following:
•
Setting the address of the Relay IAM with T-Sense
•
Making electrical connections to the Relay IAM with T-Sense
•
Mechanically installing the Relay IAM with T-Sense
Mounting
Bracket
Assembly
PID Label
T-Sense Input
Terminals
IDNet
Terminals
DIP Switch
(Under Re-sealable
Label)
Relay Output
Terminals
LED
(See Note)
Note: The LED flashes approximately once every three seconds to indicate valid communications with the 4100U FACP.
Figure 1. Relay IAM with T-Sense Assembly
©
2005, 2010 SimplexGrinnell LP . All rights reserved.
Specifications and other information shown were current as of publication and are subject to change without notice.
Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.
574-874
Rev. C
Setting the Address of the
Relay IAM with T-Sense
Note: The IDNet channel supports address codes 1 through 250.
Each Relay IAM with T-Sense has a unique address. The address of the Relay
IAM with T-Sense is set via an eight position dip switch (Figure 1). DIP switch position 1 is the least significant bit (LSB) and position 8 is the most significant bit (MSB). Set the address using Figure 2 as reference. Use a small screwdriver or pen to set the switches. The device address for the Relay IAM with T-Sense should be written on the re-sealable label; this information provides an aid in troubleshooting the system.
Note: DIP switch in “1” position is “ON” while DIP switch in “0” position is “OFF”.
FigureTag FD4-874-01
MSB DIPSWITCH IS SHOWN SET AT ADDRESS 7.
LSB
ON
1 2 3 4 5 6 7 8
OFF
1 = ON 0 = OFF
Panel Configuration
DIP SWITCHES 5 THRU 8
0000
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0
1000 1
0100 2
16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
17
18
33
34
49
50
65
66
81
82
97
98
113 129 145 161 177 193 209 225 241
114 130 146 162 178 194 210 226 242
1100 3
0010 4
1010 5
0110
0001
6
1110 7
8
1001 9
21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
1101 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235
0011
1011 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237
0111
12
14
19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
28
30
44
46
60
62
76
78
92
94
108 124 140 156 172 188 204 220 236
110 126 142 158 174 190 206 222 238
251
252
253
254
1111 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255
Figure 2. Relay IAM with T-Sense Address Chart
Configure the Relay IAM with T-Sense to the 4100U panel using the 4100U
Fire Alarm – Programmer’s Manual (574-849) .
2
Making Electrical Connections to the Relay IAM with T-Sense
Terminal connections for the Relay IAM with T-Sense are illustrated in Figure 3.
CAUTION: Do not loop wire under terminals. Break wire runs to provide supervision.
SEE NOTE 6
733-984
(1.8K 1/2W)
733-886
(4.7K 1/2 W)
1 5 N.C.
2 6 COMMON
FROM
PREVIOUS
DEVICE
OR F.A.C.P
IDNet +
IDNet -
R
B 3 7 N.O.
S
4 8 NOT USED
OPTIONAL
SHIELD IF STYLE 4:
TO NEXT
DEVICE
(IF USED)
S
IDNet +
IDNet -
R
B
IF STYLE 6:
TO NEXT
DEVICE
OR F.A.C.P
SEE NOTES 1, 2, & 3
Notes:
1.
Maximum allowable run from FACP to farthest device is not to exceed 2,500 feet
(762 meters). Maximum total wire (including all T-Taps) from FACP is 10,000 feet
(3,048 meters). IDNet lines are 18 AWG (0.823 mm/squared) twisted pair (shield recommended). When using shield, wire nut, splice, or solder the shield wires. Also insulate shield from the electrical box.
2.
The Relay IAM with T-Sense counts as a one-unit load.
3.
IDNet wiring is supervised and Power-Limited. An IDNet circuit has a communications power rating of 36.25 volts (maximum) at .5 A, 3333 Baud.
4.
Contractor wiring to relay contacts is unsupervised. Wire to local code (14 AWG
[2.081 mm/squared] recommended with 12 AWG [3.309 mm/squared] maximum).
Relay contacts are rated for 2 A (1 A for inductive load), 30 VDC and .5 A (0.25 A for inductive load), 120 VAC (non-power-limited). Inductive loads must be suppressed with a suitable suppression device. If switching 120VAC, the power source to the contacts should be externally fused by the user with a 1 Amp 250V quick blow fuse, UL listed to Guide #JDYX – Littlefuse AGC1 or equivalent. For power-limited operation, power must be provided from a power-limited auxiliary power output from the FACP or from a power-limited output of a power supply listed for fire protective signaling use. When both power-limited and non-powerlimited sources are present, use Type FPL, FPLR, or FPLP power-limited cable for power-limited circuits. If the relay is used to control a fire safety function, it must be wired within 3 feet (91.44 cm) of the control circuit. Provisions to conform to NEC
760 power-limited and non-power-limited wiring separation must be made in the field wiring if non-power-limited wiring is used on the relay output.
5.
If AC is used on relay terminals, you must add Label 526-831 to electrical box cover to indicate high voltage, ground electrical box and bracket to safety ground, and wire input circuit with twisted-shielded wire (shield connected to grounded bracket).
6.
T-Sense input circuits are not to exceed 500 feet (152.4 meters). Only Normally
Open (N/O) dry contacts are allowed on the input circuits. T-Sense lines are 18
AWG (0.823 mm/squared) wire. T-Sense inputs are pulled up to 5 VDC by a 17.4 K resistor, which can source up to 287 uA (supervised and power-limited). T-Sense inputs may be tested using ¼ watt, 1% resistors as follows: 6.81 K (normal), 16.9 K
(open), 1.65 K (current-limited), & 845 Ohms (shorted).
7.
Relay function is programmable.
Figure 3. Relay IAM with T-Sense Connections
SEE
NOTES
4, 5 & 7
3
Mechanically Installing the
Relay IAM with T-Sense
Install the Relay IAM with T-Sense into a grounded, 4-inch (10.16 cm)
UL-Listed back box (not supplied) using Figure 4 as a reference. Mount the
Relay IAM with T-Sense to the back box as follows:
1.
Loosen the two screws on the square back box.
2.
Mount the Relay IAM with T-Sense to the back box using the teardrop holes on the mounting bracket.
3.
Secure the Relay IAM with T-Sense to the back box using the two #8/32 panhead screws.
UL-Listed
4-Inch (10.16 cm)
#8/32 Panhead Screw
(Not Supplied)
Square
(2-Inch [5.08 cm]
Deep)
Back Box
(Not Supplied)
Cover
(Not Supplied)
4090-9118
Relay IAM with T-Sense
#6/32 Flathead Screw
(Not Supplied)
Note: Simplex offers semi-flush and surface covers (ordered separately) with a light pipe. The cover(s) with light pipe allow viewing of the communications LED without taking the cover off. Installation of the
4090-9801 semi-flush cover and 4090-9802 surface cover are detailed in publication 4090 IDNet
™
Semi-Flush/Surface Covers and IAM
Bracket Installation Instruction (574-796).
Figure 4. Relay IAM with T-Sense Back Box Installation
574-874
Rev. C