Simplex 4090-9118 Installation Instructions

Below you will find brief information for 4090-9118. This device is an Addressable Interface Module (IAM) that provides output control via a Form-C contact set and input status from a T-Sense monitoring zone to a 4100U Fire Alarm Control Panel. It communicates via the IDNet channel and can detect four states for its monitored zone: OPEN, NORMAL, LIMITED, and SHORT. It's designed for fire safety applications, offering robust control and supervision capabilities.

PDF
Document
Simplex 4090-9118 Relay IAM: AI Chat & PDF Download | Manualzz

Advertisement

Advertisement

/

Advertisement

Key features

  • Provides output control with one Form-C contact set

  • Features T-Sense monitoring zone with 4 status states (OPEN, NORMAL, LIMITED, SHORT)

  • Communicates and is powered via IDNet channel

  • Relay function is programmable

  • Addressable via an eight-position DIP switch (address codes 1-250)

  • Operates in temperatures between 32° F (0° C) and 120° F (49° C)

  • IDNet wiring is supervised and power-limited

  • Relay contacts rated for 2 A (30 VDC) and .5 A (120 VAC) for non-power-limited applications

Frequently asked questions

The Relay IAM with T-Sense can indicate four states for the monitored zone: OPEN, NORMAL, LIMITED, and SHORT.

The address is set using an eight-position DIP switch. Position 1 is the least significant bit (LSB) and position 8 is the most significant bit (MSB). Refer to the address chart provided in the instructions.

T-Sense input circuits are not to exceed 500 feet (152.4 meters).

This Relay IAM can function in temperatures between 32° F (0° C) and 120° F (49° C).

Only Normally Open (N/O) dry contacts are allowed on the T-Sense input circuits.

User questions

L L

Mary L.

How to connect a thermostat to the 4090-9118 Relay IAM with T-Sense and which terminals are used for this purpose?

To extract the status from a thermostat, it should be connected to the T-Sense input terminals, labeled R and B, on the 4090-9118 Relay IAM with T-Sense. Only dry normally open (N/O) contacts are allowed on the T-Sense input circuits. The device can detect four states: OPEN, NORMAL, LIMITED, and SHORT.

L L

Mary L.

What are the functions of terminals 5, 6, and 7 on the 4090-9118 Relay IAM with T-Sense?

Terminals 5, 6, and 7 represent the Form-C relay contacts used for output control:

  • Terminal 5 (N.C.): Normally Closed contact, closed when the relay is inactive.
  • Terminal 6 (COMMON): Common contact for the switching relay.
  • Terminal 7 (N.O.): Normally Open contact, open when the relay is inactive. These contacts allow the 4100U FACP to control an external device.
L L

Mary L.

What are terminals 1 and 2 on the 4090-9118 Relay IAM with T-Sense used for?

Terminals 1 and 2 are labeled IDNet + and IDNet -, respectively. They are used for communication with the 4100U FACP via the IDNet channel, which provides both communication and power to the entire circuit.