Eaton PowerXL DG1 Series VFD is a powerful and versatile variable frequency drive that offers precise speed control for a wide range of applications. With its easy-to-use software and keypad programming interface, the DG1 is suitable for both basic and complex applications. The DG1 also features built-in communication options, including Modbus serial and Ethernet, making it easy to integrate with other devices and systems.
advertisement
![Eaton PowerXL DG1 Series VFD Quick Start Manual | Manualzz Eaton PowerXL DG1 Series VFD Quick Start Manual | Manualzz](http://s3.manualzz.com/store/data/057154460_1-069cf0f8180618bd644b592ade7dc073-360x466.png)
PowerXL DG1 Series VFD
Effective July 2014
Power Xpert
in
Control Quick Start Guide
Step 1 – Installation
Download the Power Xpert in Control Software with the One Installer found on the www.eaton.com/dg1 software tab.
Step 2 – Connecting
Keypad Port: Using the PowerXL DG1 programming cable (Part Number DXG-
CBL-PCCABLE) connect from your computer USB port to the keypad port.
Ethernet Port: Using any standard CAT5 Ethernet cable connect from your computer to the RJ45 Ethernet Port. Note: Your drive IP address will have to be set up in the drive keypad parameters (Group P20.3) to match the IP address structure in your computer before connecting.
Step 3 – Configuring Connection
Open Power Xpert in Control and double click on either the Modbus Serial (Keypad Port) or Modbus TCP (Ethernet Port) on the right side in the Device Catalog ( red ). Once complete, the device DTM should then show up in the Network View ( blue ).
If the Modbus Serial (Keypad Port) is selected the Communication Settings window will come up which should be set to the following values.
Configuration Parameter
Port
Parity*
Data Bits*
Baud Rate*
Stop Bits*
Transmission Mode*
Setting
Need to check in windows device properties for port
USB to RS485 adapter was installed at.
Even
8
38400
1
RTU
MZ040012EN
Effective July 2014
Power Xpert in Control Quick Start Guide
Step 4 – Loading Device
In the Device Catalog ( red ), double click on the PowerXL DG1 drive, it will be added to the Network View in ( blue ) under the communication DTM.
Next the Set Address window will appear and the communication address needs to be set based on the below. o Modbus Serial (Keypad Port)
Configuration Parameter
Slave Address
Setting
18 o Modbus TCP (Ethernet Port)
Configuration Parameter Setting
IP Address* XXX.XXX.XXX.XXX
* The IP address should be set via the keypad on the drive.
With the PowerXL DG1 drive selected, click the Go Online button. Then double click on the drive to load device parameters, these will be shown in the main window
( green ).
The PowerXL DG1 is now ready to be configured by the Power Xpert in Control software.
2 EATON CORPORATION www.eaton.com
MZ040012EN
Effective July 2014
Power Xpert in Control Quick Start Guide
Additional Help
In the US or Canada: please contact the Technical Resource Center at 1-877-ETN-CARE or 1-877-326-2273 option 2, option 6.
All other supporting documentation is located on the Eaton web site at www.eaton.com/Drives
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122 USA
Eaton.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. MZ040012EN
July 2014
Eaton is a registered trademark of Eaton Corporation.
All other trademarks are property of their respective owners
advertisement
Related manuals
advertisement