DURAWATT
®
ELECTRIC • PACKAGED WATER HEATER
AquaPLEX
®
- STORAGE TANK (UNLINED DUPLEX ALLOY)
TANK SERIES 150 GALLONS
MODEL
NUMBER
45 L 150A-VE
90 L 150A-VE
140 L 150A-VE
180 L 150A-VE
230 L 150A-VE
270 L 150A-VE
320 L 150A-VE
370 L 150A-VE
410 L 150A-VE
460 L 150A-VE
510 L 150A-VE
550 L 150A-VE
650 L 150A-VE
740 L 150A-VE
830 L 150A-VE
RECOVERY RATE
GPH
40°-120°F 40°-140°F
45
90
140
180
230
270
320
370
410
460
510
550
650
740
830
37
70
111
150
184
220
256
300
330
370
400
440
515
590
664
ASHRAE 90.1 compliant.
For standard and optional equipment, see form #PV 8130.
Dimensions in inches, unless otherwise noted.
Contact PVI representative for higher inputs.
* 3-phase only.
** For 208V 3 models, see PV 9031.
INPUT kW
9 *
18
27
36
45
54
63
72
81
90
99
108
126
144
162
240V, 1Ø
225
263
300
338
375
413
450
~
75
113
150
188
Consult factory
ELEMENT AMPS **
240V, 3Ø
22
44
65
87
109
130
152
174
195
217
239
260
304
347
390
480V, 3Ø
11
22
33
44
55
65
76
87
98
109
120
130
152
174
195
SHIPPING
WEIGHT lbs
1050
1050
1050
1050
1060
1060
1060
1060
1070
1070
1090
1090
1100
1120
1130
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL CIRCUIT TRANSFORMER SUPPLIED ON 480V ONLY. TAPPED CONTROL CIRCUIT INTERNALLY WIRED FOR 208V AND 240V.
208V AND 240V MODELS REQUIRE AC NEUTRAL CONDUCTOR FOR GROUNDING OF CONTROL CIRCUIT.
ALTERNATE VOLTAGES: FOR 230/460V, MULTIPLY kW AND RECOVERY BY .92. MULTIPLY AMPS BY .96.
FOR 220/440V, MULTIPLY kW AND RECOVERY BY .84. MULTIPLY AMPS BY .92.