Moxa MGate MB3170I Cellular Network Device Specification Guide


Add to my manuals
3 Pages

advertisement

Moxa MGate MB3170I Cellular Network Device Specification Guide | Manualzz

Industrial Ethernet Gateways

MGate™ MB3170/3270

1 and 2-port advanced serial-to-Ethernet Modbus gateways

Accessible by up to 32 TCP master/client devices, or connect to up to 32 TCP slave/server devices

Supports up to 31 or 62 serial slave devices

Ethernet cascading for easy wiring

Serial port routing by IP address, TCP port, or ID mapping

Serial redirector function provided

Embedded Modbus traffic monitor

10/100BaseTX (RJ45) or 100BaseFX (single mode or multi-mode

› with SC/ST connector)

Emergency request tunnels ensure QoS control

1

Overview

The MGate MB3170 and MB3270 are 1 and 2-port Modbus gateways, respectively, that convert between Modbus TCP, ASCII, and RTU communications protocols. The gateways provide both serialto-Ethernet communication and serial (Master) to serial (Slave) communications. In addition, the gateways support simultaneously connecting serial and Ethernet masters with serial Modbus devices.

The MGate MB3170 and MB3270 series gateways can be accessed by up to 32 TCP master/clients or connect to up to 32 TCP slave/servers.

Routing through the serial ports can be controlled by IP address, TCP port number, or ID mapping. A featured priority control function allows urgent commands to obtain an immediate response. All models are rugged, DIN-rail mountable, and offer optional built-in optical isolation for serial signals.

Integrate TCP Masters without Altering the Modbus RTU/ASCII Network or Software

The MB3270 can integrate Modbus TCP with Modbus RTU/ASCII, without modifying the existing Modbus RTU/ASCII architecture or software. With the serial redirector function, a serial master can maintain direct access to serial slave devices through a specially mapped serial port. This allows the serial and TCP masters to access serial slaves simultaneously.

Optical Fiber for Ethernet Communications

The MGate MB3170 fiber series includes 100BaseFX fiber models that support transmission distances up to 4 km for multi-mode models, and up to 40 km for single-mode models. Optical fiber is well-suited for industrial applications because it is immune to electromagnetic

Priority Control for Urgent Commands (Patented)

As Modbus networks increase in size and complexity, the lag time between commands and responses becomes a major concern.

Advanced models of the MB3000 series provide a priority control function for urgent commands, allowing users to force certain commands to get an immediate response. Depending on your system’s requirements, different methods are available to define which commands receive priority. noise and interference. For environments that experience high ground loop voltages, fiber provides the best isolation protection, and because there is no danger of sparking, optical fiber is safer than copper wire to use in hazardous environments.

Patent Numbers: (US/TW)

US7,743,192 B2 / I332618

US7,725,635 B2 / I321007 w w w. m o x a . c o m

2

Industrial Ethernet Gateways

Specifications

Ethernet Interface

Protocols: Modbus TCP

Number of Ports: 2 (1 IP, Ethernet cascade)

Speed: 10/100 Mbps, Auto MDI/MDIX

Connector: 8-pin RJ45

Magnetic Isolation Protection: 1.5 kV (built-in)

Optical Fiber Interface

Fiber Cable Type OM1

100BaseFX

Multi-Mode

50/125 μm

800 MHz*km

Single-Mode

G.652

4 km 5 km 40 km

Wavelength

Typical Distance

Typical (nm)

TX Range (nm)

RX Range (nm)

TX Range (dBm)

1300

1260 to 1360

1100 to 1600

-10 to -20

1310

1280 to 1340

1100 to 1600

0 to -5

Optical

Power

RX Range (dBm)

Link Budget (dB)

-3 to -32

12

-3 to -34

29

Dispersion Penalty (dB) 3 1

Note: When connecting a single-mode fiber transceiver, we recommend using an attenuator to prevent damage caused by excessive optical power.

Note: Compute the “typical distance” of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).

Serial Interface

Protocol: Modbus RTU/ASCII Master/Slave

Number of Ports:

MB3170/3170I: 1

MB3270/3270I: 2

Serial Standards: RS-232/422/485, software selectable

Connectors:

MB3170/3170I: DB9 male for RS-232, terminal block for RS-422/485

MB3270/3270I: DB9 male x 2

Magnetic Isolation Protection: 2 kV (for “I” models)

ESD Protection: 15 kV for all signals

RS-485 Data Direction Control: ADDC® (automatic data direction control)

Pull High/Low Resistor for RS-485: 1 k Ω , 150 k Ω

Terminator for RS-485: 120 Ω

Serial Communication Parameters

Data Bits: 7, 8

Stop Bits: 1, 2

Parity: None, Even, Odd, Space, Mark

Flow Control: RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only)

Baudrate: 50 bps to 921.6 kbps

Serial Signals

RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND

RS-422: Tx+, Tx-, Rx+, Rx-, GND

RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND

RS-485-2w: Data+, Data-, GND

Software

Configuration Options: Web Console, Serial Console, Telnet Console,

Windows Utility

Utility: MGate Manager for Windows2000, Windows XP, Server 2003,

Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows

7/8/8.1 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2

Multi-master and Multi-drop:

Master mode: 32 TCP slaves

Slave mode: 32 TCP masters (request queue 32-deep for each master)

Support: Smart Routing, Serial Redirection, ProCOM, Priority Control,

MXview, SNMP v1 (read only)

Physical Characteristics

Housing: Plastic, IP30

Weight:

MGate MB3170: 360 g (0.79 lb)

MGate MB3270: 380 g (0.84 lb)

Dimensions:

Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)

With ears extended: 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)

Environmental Limits

Operating Temperature:

Standard Models: 0 to 60°C (32 to 140°F)

Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature: -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity: 5 to 95% (non-condensing)

Vibration: IEC 60068-2-6, IEC 60068-2-64

Shock: IEC 60068-2-27

Drop: IEC 60068-2-32

Power Requirements

Input Voltage: 12 to 48 VDC

Input Current:

MGate MB3170: 435 mA @ 12 VDC

MGate MB3170I: 555 mA @ 12 VDC

MGate MB3270: 435 mA @ 12 VDC

MGate MB3270I: 510 mA @ 12 VDC

MGate MB3170-M-SC: 510 mA @ 12 VDC

MGate MB3170-M-ST: 435 mA @ 12 VDC

MGate MB3170-S-SC: 555 mA @ 12 VDC

MGate MB3170I-M-SC: 555 mA @ 12 VDC

MGate MB3170I-S-SC: 555 mA @ 12 VDC

Power Connector: Terminal block

Relay Output: 1 digital relay output to alarm (normal closed), with current carrying capacity 1 A @ 30 VDC

Standards and Certifications

Safety: UL 508, EN 60950-1

Hazardous Location: Class 1 Division 2, ATEX, IECEx

EMC: EN 55032/24

EMI: CISPR 32, FCC Part 15B Class A

EMS:

IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV

IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m

IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV

IEC 61000-4-5 Surge: Power: 2 kV

IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m

IEC 61000-4-8 PFMF

IEC 61000-4-11

Marine: DNV

MTBF (mean time between failures)

Time:

MGate MB3170: 346,790 hrs

MGate MB3170-M-SC: 1,175,887 hrs

MGate MB3170-M-ST: 1,175,887 hrs

MGate MB3170-S-SC: 1,175,887 hrs

MGate MB3170I-M-SC: 768,343 hrs

MGate MB3170I-S-SC: 763,707 hrs

MGate MB3270: 342,098 hrs

Standard: Telcordia SR332

Warranty

Warranty Period: 5 years

Details: See www.moxa.com/warranty w w w. m o x a . c o m

3

Industrial Ethernet Gateways

Dimensions

9.2 (0.36)

7.2 (0.28)

7.1 (0.28)

7.2 (0.28)

7.1 (0.28)

29 (1.14)

14.5

(0.57)

Front View

29 (1.14)

29 (1.14)

14.5

(0.57)

Rear View

14.5

(0.57)

Top View

20.6 (0.81) 29.91 (1.18)

89.2 (3.51)

Unit: mm (inch)

MGate™ MB3170

35 (1.38) 25.9 (1.02)

MGate™ MB3270

35 (1.38) 25.9 (1.02)

SC Model ST Model Side View Bottom View

Ordering Information

Available Models

MGate MB3170: 1-port advanced Modbus gateway, 0 to 60°C operating temperature

Package Checklist

MGate MB3170I: 1-port advanced Modbus gateway with 2 kV isolation, 0 to 60°C operating temperature

MGate MB3270: 2-port advanced Modbus gateway, 0 to 60°C operating temperature

MGate MB3270I: 2-port advanced Modbus gateway with 2 kV isolation, 0 to 60°C operating temperature

• 1 MGate MB3170 or MB3270 Modbus gateway

• Documentation and software CD

• Quick installation guide (printed)

• Warranty card

MGate MB3170-T: 1-port advanced Modbus gateway, -40 to 75°C operating temperature

MGate MB3170I-T: 1-port advanced Modbus gateway with 2 kV isolation, -40 to 75°C operating temperature

MGate MB3270-T: 2-port advanced Modbus gateway, -40 to 75°C operating temperature

MGate MB3270I-T: 2-port advanced Modbus gateway with 2 kV isolation, -40 to 75°C operating temperature

MGate MB3170-M-SC: 1-port advanced Modbus gateway with 100BaseFX multi-mode fiber port (SC connector), 0 to 60°C operating temperature

MGate MB3170-M-SC-T: 1-port advanced Modbus gateway with 100BaseFX multi-mode fiber port (SC connector), -40 to 75°C operating temperature

MGate MB3170-M-ST: 1-port advanced Modbus gateway with 100BaseFX multi-mode fiber port (ST connector), 0 to 60°C operating temperature

MGate MB3170-M-ST-T: 1-port advanced Modbus gateway with 100BaseFX multi-mode fiber port (ST connector), -40 to 75°C operating temperature

MGate MB3170-S-SC: 1-port advanced Modbus gateway with 100BaseFX single-mode fiber port (SC connector), 0 to 60°C operating temperature

MGate MB3170-S-SC-T: 1-port advanced Modbus gateway with 100BaseFX single-mode fiber port (SC connector), -40 to 75°C operating temperature

MGate MB3170I-M-SC: 1-port advanced Modbus gateway with 100BaseFX multi-mode fiber port (SC connector) and 2 kV optical isolation, 0 to 60°C operating temperature

MGate MB3170I-M-SC-T: 1-port advanced Modbus gateway with 100BaseFX multi-mode fiber port (SC connector) and 2 kV optical isolation, -40 to

75°C operating temperature

MGate MB3170I-S-SC: 1-port advanced Modbus gateway with 100BaseFX single-mode fiber port (SC connector) and 2 kV optical isolation, 0 to 60°C operating temperature

MGate MB3170I-S-SC-T: 1-port advanced Modbus gateway with 100BaseFX single-mode fiber port (SC connector) and 2 kV optical isolation, -40 to

75°C operating temperature

Optional Accessories (can be purchased separately)

Mini DB9F-to-TB: DB9 female to terminal block connector

© Moxa Inc. All rights reserved. Updated Mar. 13, 2017. Specifications subject to change without notice. Please visit our website for the most up-to-date product information.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement