Burkert 8693 Digital electropneumatic process controller Data Sheet
The Burkert 8693 is a compact, robust stainless steel digital electropneumatic process controller designed for integrated mounting on process control valves. It features a user-friendly graphic display with backlight and keypad, easy start-up by Tune function for position and process controller, and integrated control air routing with spring chamber aeration. With communication interfaces such as PROFIBUS DP-V1, DeviceNet, EtherNet/IP, PROFINET, Modbus TCP, or büS (Bürkert System Bus), it offers flexible communication options.
Advertisement
Advertisement
DATA SHEET
Type 8693
Digital electropneumatic process controller for the integrated mounting on process control valves
• Compact, robust stainless steel design
• Easy start-up by Tune function for position and process controller
• Contact-free position sensor
• Integrated control air routing with spring chamber aeration
• PROFIBUS DP-V1, DeviceNet, EtherNet/IP, PROFINET, Modbus
TCP or büS (Bürkert System Bus)
Product variants described in the data sheet may differ from the product presentation and description.
Can be combined with
Type 2301
Pneumatically operated
2 way Globe Control
Valve
Type 2300
Pneumatically operated
2 way angle seat control valve ELEMENT
Type 2103
2/2 way diaphragm valve with pneumatic stainless steel actuator
(Type ELEMENT) for decentralised automation
Type 8202 pH or redox potential measurement device
Type description
The compact process controller Type 8693 is optimized for integrated mount ing on the pneumatic actuators in the process valve series Type 23xx/2103 and is specially designed for the requirements of a hygienic process environ ment. The actual value of the process factor is directly supplied to the device as 4…20 mA, PT100 or a frequency signal. The process controller calculates the setpoint for the subordinated positioner through the variance comparison.
Due to the analogue feedback all analogue values on the controlling level can be transferred.
With integrated diagnostic functions operation conditions of the control valve can be monitored. Through status signals, valve diagnostic messages are transmitted according to NAMUR NE107 and recorded as history entries. The parameterization of process controller and positioner can be carried out auto matically. The easy handling and the selection of additional software functions are done either on a big graphic display with backlight and keypad or over the
COMMUNICATOR.
The positioner registers the valve position without deterioration through a contact-free, analogue position sensor. The control of single or double-acting actuators is done without internal air consumption. Communication interfaces such as PROFIBUS DP-V1, DeviceNet, EtherNet/IP, PROFINET, Modbus TCP, büS (based on CANopen) and analogue as well as binary feedback can also be chosen.
Type 8400
Screw-in temperature threshold detector/ transmitter with display
Type 8045
Insertion magnetic inductive flowmeter
Hygienic process valves
1000110929 | Standard | EU | en | 202101 | 20
© Christian Bürkert GmbH & Co. KG, Subject to alteration
Visit product website
Type 8693
Table of contents
4. Device/Process connections 8
5. Performance specifications 13
Visit product website
2 | 20
Type 8693
1. General technical data
Product properties
Dimensions
Material
Body
Seal
Cover
Operation
Display
Operating keys
Service interface
Configuration tool
Commissioning
Initialization positioner/process controller
Manual operation of pilot valve
Status display
Display of device and valve status
Communication
Fieldbus
Digital
Position sensor
Measuring principle
Position detection module
Stroke range Valve spindle
Electrical data
Operating voltage
Protection class
Residual ripple
Power consumption
Input/Output
Digital input
Digital output
Current limitation
Analogue output
Input data setpoint and actual value
Setpoint signal
Setpoint value setting default
Input resistance
Setpoint signal
Setting 4…20 mA
Frequency setting
Setting Pt 100
Electrical connection
Multipole
Cable gland
Detailed information can be found in chapter
PPS, stainless steel
EPDM
PC
Graphic display with backlighting and intuitive menu navigation
Membrane keypad with 4 keys
Connected to PC via USB connection
Bürkert Communicator
PACTware (only for device versions with PROFIBUS, DeviceNet resp. analogue version with serial interface)
Automatic by P.TUNE function (Self-optimization of the PID-Parameter)
In manual mode via push-button on control panel
LEDs (Colours acc. to NAMUR); Only valid for Ethernet and büS versions
EtherNet/IP, PROFINET, Modbus TCP, PROFIBUS DP-V1, DeviceNet
Bürkert system bus (büS) - based on CANopen
Inductive
Contactless (wear-free) analogue position sensor
3…45 mm
24 V DC ± 10 %
UL: NEC Class 2
3 acc. to DIN EN 61140 (VDE 0140 - 1)
10 %, no technical DC voltage!
< 5 W
1 binary input, 0…5 V = log “0”, 10…30 V = log “1”
2 binary output (optional), galvanically isolated
100 mA, output will be synchronised when overloaded
1 output (optional)
0/4…20 mA, 0…5/10 V
0/4…20 mA
0…5/10 V
0/4…20 mA: 180 Ω
0…5/10 V: 19 kΩ
180 Ω Input resistance
17 kΩ Input resistance, 0…1000 Hz
- 20…+ 220 °C, resolution < 0.1 °C
M12, 8 pin resp. 4- or 5 pin acc. to device version (see “4. Device/Process connections” on page 8 )
2xM16 × 1.5 (cable Ø 5…10 mm) with terminals for cable cross-sections
0.14…1.5 mm²
Visit product website
3 | 20
Type 8693
Pneumatic data
Control medium
Dust content
Particle density
Pressure dew point
Oil content
Air intake filter
Mesh size
Neutral gases, air, quality class acc. to ISO 8573 - 1
Class 7 (< 40 µm particle size)
Class 5 (< 10 mg/m 3 )
Class 3 (<- 20 °C)
Class X (< 25 mg/ m
Exchangeable
~0.1 mm
3 )
Supply pressure
Low air capacity 0…7 bar 1.)
High air capacity
Pilot air ports
3…7 bar
Threaded connection G ⅛ stainless steel
Positioning system (control function and air capacity)
Low air capacity
Single and double-acting 7 l
N
/min for aeration and ventilation (Q
Nn from 7 to 6 bar absolute)
Type 23xx, Ø actuator 70/90 mm
value acc. to definition at pressure drop
Actuator series/size
High air capacity
Single-acting
Actuator series/size
130 l
N
/min for aeration and ventilation (Q
Nn
value acc. to definition at pressure drop from 7 to 6 bar absolute)
Type 23xx, Ø actuator 70/90 mm
Type 27xx, Ø actuator 175/225 mm
Approvals and certificates
Conformity
Ignition protection
UL
ATEX
IECEx
EMC directive 2014/30/EU
II 3D Ex tc IIIC T135 °C Dc
II 3G Ex ec IIC T4 Gc cULus certificate: E238179
II 3D Ex tc IIIC T135 °C Dc
II 3G Ex ec IIC T4 Gc
Certificate: BVS 14 ATEX E 008 X
Ex tc IIIC T135 °C Dc
Ex ec IIC T4 Gc
Certificate: IECEx BVS 14.0009 X
Environment and installation
Installation and mechanical data
Installation position
Valve actuator (art and size)
As required, preferably with actuator in upright position
ELEMENT Type 23xx (actuator size Ø70/90/130 mm)
CLASSIC Type 27xx (actuator size Ø175/225 mm)
Detailed information can be found in chapter
Adapter kits
Operating conditions
Ambient temperature (max.)
Degree of protection
Operating altitude
- 10…+ 55 °C
IP65/IP67 acc. to EN 60529, 4X acc. to NEMA 250 Standard
Up to 2000 m above sea level
1.) The supply pressure applied must be 0.5 to 1 bar above the minimum required pilot pressure of the valve actuator.
Visit product website
4 | 20
Type 8693
2. Materials
2.1. Material specifications
1
2
3
4
5
6
7
8
9
3. Dimensions
3.1. Multipole connection
Note:
Dimensions in mm
No. Element
1 Cover
2 Seal
3 Outer casing
4 Seal
5 M12 circular plug
6 Screws
7 Screws
8 Push-in connector
Threaded ports G ⅛
9 Basic housing
Material
PC
EPDM
Stainless steel
EPDM
Stainless steel
Stainless steel
Stainless steel
POM/Stainless steel
Stainless steel
PPS
71.2
91
4.2
9.3
24.2 23.8
54.1
Visit product website
5 | 20
Type 8693
3.2. Cable gland connection
Note:
Dimensions in mm
91
13.5
101.6
31.7
135.8
54.1
3.3. Mounting on control valves of actuator series Type 23xx, actuator size 70/90/130 mm
Note:
Dimensions in mm
91
71.2
13.5
31.7
27
9.5
27
54.1
Visit product website
6 | 20
Type 8693
3.4. Mounting on control valves of actuator series Type 27xx, actuator size 175/225 mm
Note:
Dimensions in mm
91
71.2
13.5
31.7
24
43.5
9.5
24
54.1
38
13.5
31.7 13.5
Visit product website
7 | 20
Type 8693
4. Device/Process connections
4.1. Electrical connections
Multipole connection
Switch
3 2
4
1
8
5 6 7
M12 circular connector , 8 pin
(setpoint) 1
2
M8 circular connector, 4 pin
(process actual value) 1.)
M12 circular plug, 8 pin
(setpoint)
Pin Pin assignment
8 Setpoint + (0/4…20 mA /
0…5/10 V)
7 Setpoint GND
2
3 1
4
M12 circular connector, 4 pin
(operating voltage)
M12 circular plug, 8 pin
(in/output signal) 1.)
Pin Pin assignment
6 Analogue feedback +
5 Analogue feedback GND
4 Digital output 1
3 Digital output 2
2 Digital output GND
1 Digital input +
1.) With the option analogue feedback or binary output
M12 circular plug, 4 pin
(operating voltage)
Pin Pin assignment
1 Operating voltage + 24 V DC
3 Operating voltage GND
M8 circular plug, 4 pin (process actual value)
Note:
For reasons of wire compensation connect the Pt 100 sensor via 3 wires. Always bridge Pin 3 and Pin 4 on the sensor.
Input type 1.)
4…20 mA - internally supplied
4…20 mA - externally supplied
Frequency - internally supplied
Frequency - externally supplied
Pt 100 (see note above)
1
2
3
4
1
2
3
4
1
2
3
4
3
Pin
1
2
2
3
4
1
4
Pin assignment
+ 24 V Transmitter supply
Output from transmitter
GND
Bridge acc. to GND
Not assigned
Process actual value +
Not assigned
Process actual value –
+ 24 V Sensor supply
Clock input +
Clock input – (GND)
Not assigned
Not assigned
Clock input +
Clock input –
Not assigned
Not assigned
Process actual value 1 (power supply)
Process actual value 2 (GND)
Process actual value 3 (compensation)
Switch
Switch on left
Switch on right
Switch on left
Switch on right
Switch on right
1.) With the option analogue feedback or binary output
Visit product website
8 | 20
Type 8693
Cable gland connection
Switch
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
Connection terminals
10
11
12
13
8
9
6
7
14
15
16
Terminal Pin assignment
1 Analogue feedback GND
2
3
Analogue feedback +
Digital output GND
4
5
Digital output 2
Digital output 1
Digital input +
Setpoint GND
Setpoint +
Process actual value: Assignment depends on sensor type: Details see operating instructions
Not assigned
Digital input GND
Operating voltage GND
Operating voltage + 24 V
PROFIBUS DP connection
3
2
1
M12 circular plug, 4 pin
(operating voltage)
4
1
2
M8 circular plug, 4 pin
(Input signal, process actual value)
M12 socket, 5 pin
(inversely coded)
(PROFIBUS DP)
1
4
5
2
1
2
5
3
3
Socket/ M12 circular plug, 5 pin (fieldbus connection)
Pin Pin assignment
1
2
VP + 5
RxD/TxD-N
3
4
DGND
RxD/TxD-P
5 Not assigned
Thread Shielding/protective earth
4
M12 circular plug, 5 pin
(inversely coded)
(PROFIBUS DP)
Earthing screw (TE)
M12 circular plug, 4 pin (operating voltage)
Pin Wire colour 1.) Pin assignment
1 Brown
3 Blue
Operating voltage + 24 V
Operating voltage GND
1.) The indicated wire colours refer to the optional connector cable with ID no. 918038.
Visit product website
9 | 20
Type 8693
M8 circular plug, 4 pin (Input signal, process actual value)
Input type 1.) Pin Aderfarbe 2.) Pin assignment
4…20 mA - internally supplied 1 Brown + 24 V Transmitter supply
2 White
3 Blue
4 Black
Output from transmitter
GND
Bridge acc. to GND
4…20 mA - externally supplied
Frequency - internally supplied
1 Brown
2 White
3 Blue
4 Black
1 Brown
Not assigned
Process actual value +
Not assigned
Process actual value –
+ 24 V Sensor supply
Frequency - externally supplied
2 White
3 Blue
4 Black
1 Brown
2 White
3 Blue
4 Black
Clock input +
Clock input – (GND)
Not assigned
Not assigned
Clock input +
Clock input –
Not assigned
Pt 100 1 Brown
2 White
3 Blue
4 Black
Not assigned
Process actual value 1 (power supply)
Process actual value 3 (GND)
Process actual value 2 (compensation)
1.) Can be adjusted via software (see operating instructions Type 8692/8693 “Setting up the process controller”).
2.) The indicated colours refer to the connection cable available as an accessory with the article no. 264602.
Switch
Switch on left
Switch on right
Switch on left
Switch on right
Switch on right
DeviceNet connection
3
2
4
5
1
M12 circular plug, 5 pin
(DeviceNet)
3
3
4
2
1
2
M8 circular plug, 4 pin
(Input signal, process actual value)
1
M12 circular plug, 4 pin
(operating voltage)
4
Earthing screw (TE)
Switch
(to loosen the operatintg screw)
M12 circular plug, 5 pin (fieldbus connection)
Pin Pin assignment
1 Shielding
2 V+
3 V–
4 CAN H
5 CAN L
Colour
Not assigned
Not assigned
Not assigned
White
Blue
Connector diagram
3
2
4
5
1
Visit product website
10 | 20
Type 8693
EtherNet/IP, PROFINET, Modbus TCP connection
3
4
2
3
4
M12 circular plug, 4 pin
(operating voltage)
1
1
2
M8 circular plug, 4 pin
(input signal, process actual value)
3
2
4
1
M12 fieldbus connection
(2 p o r t E thernet switch)
M12 circular plug, 4 pin (operating voltage)
Pin Wire colour .) Pin assignment
1 Brown
3 Blue
Operating voltage + 24 V
Operating voltage GND
1.) The indicated wire colours refer to the optional connector cable with article no.
918038.
M12 fieldbus connection, D coded
Pin Pin assignment
1 Transmit +
2 Receive +
3 Transmit –
4 Receive –
Connector diagram
3
2
4
1
M8 Circular plug, 4 pin (input signal for process actual value)
Note:
For reasons of wire compensation connect the Pt 100 sensor via 3 wires. Always bridge Pin 3 and Pin 4 on the sensor.
Input type 1.)
4…20 mA - internally supplied
Pin Wire colour 2.) Pin assignment
1 Brown + 24 V Transmitter supply
2 White
3 Blue
Output from transmitter
GND (identical to GND operating voltage
4 Black Bridge acc. to GND (GND from
3 guide transmitter)
Switch
Switch on left
4…20 mA - externally supplied
Frequency - internally supplied
1 Brown
2 White
3 Blue
4 Black
1 Brown
2 White
3 Blue
4 Black
Not assigned
Process actual value +
Not assigned
Process actual value –
+ 24 V sensor supply
Clock input +
Clock input – (GND)
Not assigned
Switch on right
2
Switch on left
Frequency - externally supplied
Pt 100 (see note above)
1
2
3
4
1
2
3
4
Brown
White
Blue
Black
Brown
White
Blue
Black
Not assigned
Clock input +
Clock input –
Not assigned
Not assigned
Process actual value 1 (power supply)
Process actual value 3 (GND)
Process actual value 2 (compensation)
Switch on right
Switch on right
1.) Can be adjusted via software (see operating manual Type 8692/8693 “24.2.1 PV-INPUT – Setting up the process controller”).
2.) The indicated colours refer to the connection cable available as an accessory with the article no. 264602.
2
3
2
3
4
4
1
2
3
2
3
4
Outer circuitry
1
I
Clock +
Clock –
GND
4 ... 20 mA
GND 4 ... 20 mA
+24 V
Clock +
Clock -/ GND
(identical with GND, operating voltage)
Pt 100
Visit product website
11 | 20
Type 8693
Bürkert system bus (büS) connection
3
4
1
2
M8 circular plug , 4 pin
(input signal, process actual value)
4
1
M12 circular plug,
5 pin (büS)
3
2
M12 circular plug × 1, 5 pin (büS connection)
Pin Wire colour Pin assignment
1 CAN-Shield/Shield ing
CAN-Shield/Shielding
2 Not assigned
3 Black
4 White
5 Blue
GND / CAN_GND
CAN_H
CAN_L
3
2
1
M12 circular plug , 4 pin
(operating voltage)
4
M12 circular plug, 4 pin (operating voltage)
Pin Wire colour 1.) Pin assignment
1 Brown
2 Not assigned
Operating voltage + 24 V DC
3 Blue Operating voltage GND
1.) The indicated wire colours refer to the optional connector cable with article no.
918038.
Visit product website
12 | 20
Type 8693
5. Performance specifications
5.1. Process control circuit
Z2
Process setpoint
SP
+
-
Xd2
Process controller
CMD
Position control loop
Valve opening
Process
PV
Process factor
Transmitter
5.2. Signal flow diagram
Position control loop
Z1
Position setpoint
CMD
+
-
Xd1
Positioner
B1
E1
Pilot valve system
P
K
Control valve
POS
Valve opening
Position control loop
Position sensor system
Additional software options of the TopControl process controller Type 8693
• Automatic start of the control valve systems
• Automatic parameterization of the process control circuit
• Automatic or manual characteristic curves selection
• Setting of the seal and the maximum stroke threshold respectively
• Parameterization of the positioner
• Manual parameterization of the process controller
• Liwithation of the stroke range
• Liwithation of the manipulating speed
• Setting of the moving direction
• Configuration of the binary input
• Signal range splitting on several controllers
• Configuration of an analogue or double binary outputs
• Signal fault detection
• Safety position
Visit product website
13 | 20
Type 8693
• Code protection
• Contrast inversion of the display
• Language selection
• Parametisable diagnostic functions 1.) / Binary output (Option)
– Operating-hours counter
– Path accumulator
– Position monitoring
– Process actual value monitoring
– Monitoring of the mechanical end positions in the armature
– Graphical display of the dwell time density and movement range
– Direction reversal counter
– Temperature monitoring
1.) Further diagnostic functions with detailed description can be found in the operating instructions
Visit product website
14 | 20
Type 8693
5.3. Interface diagram
Version without fieldbus interface
Input for position or process setpoint,
4 - 20mA, 0-20 mA
0-10 V, 0-5 V
Input for actual process value 4-20 mA, frequency,
Pt 100
Binary inputs
24 V DC 1.)
Communications
Interface
Process controller
Operation
Analogue feedback 2.)
Analogue feedback + 2 binary outputs 2.)
Version with fieldbus interface
With PROFIBUS DP, DeviceNet, EtherNet/IP, PROFINET, Modbus TCP and Bürkert system bus (büS)
Bus
Input for process setpoint 4-20 mA, frequency,
Pt 100
24 V DC 1.)
Communications
Interface
Process controller
PROFIBUS DP
DeviceNet
Ethernet/IP
PROFINET
Modbus TCP büS
Operation
Bus
1.) The operating voltage is supplied with a 3-wire unit independent from the setpoint signal
2.) Alternative options
Visit product website
15 | 20
Type 8693
6. Product installation
6.1. Combination options with pneumatic process valves
Note:
TopControl Control valve system consists of a process controller Type 8693 and an ELEMENT control Type 23xx, resp. 2103.
The following information is required to select a complete system:
• Article no.
of the desired process controller TopControl Type 8693
• Article no . of the desired control valve Type 23xx/ 2103 (see separate data sheets Type 2301 , Type 2300 , Type 2103 )
You order two components and receive a completely assembled and tested valve.
Example for variations of the control valve system:
Positioner Type 8693 Pneumatic process control valves
Type 2301
Globe valve
Type 2300
Angle seat valve
Type 2103
Diaphragm valve Hygienic Process valve
(Third party)
Control valve system
Type 8802-GD-J
Control valve system
ELEMENT
2301 + 8693
Type 8802-YG-J
Control valve system
ELEMENT
2300 + 8693
1.) See data sheet adaptations for third-party drives, KK01 or contact the appropriate Bürkert sales office.
Type 8802-DF-J
Control valve system
ELEMENT
2103 + 8693
Mounting on third party actuators 1.)
Visit product website
16 | 20
Type 8693
7. Ordering information
7.1. Bürkert eShop – Easy ordering and quick delivery
Bürkert eShop – Easy ordering and fast delivery
You want to find your desired Bürkert product or spare part quickly and order directly?
Our online shop is available for you 24/7. Sign up and enjoy all the benefits.
Order online now
7.2. Bürkert product filter
Visit product website
Bürkert product filter – Get quickly to the right product
You want to select products comfortably based on your technical requirements?
Use the Bürkert product filter and find suitable articles for your application quickly and easily.
Try out our product filter
7.3. Ordering chart
Note:
• Standard versions are UL approved
• The following applies to all variants listed below: Pilot air ports threaded connection G ⅛
Circuit function
Pilot valve system
Communication Electrical connections
Analogue feedback
0/4…20 mA
Actuator series Type 23xx Actuator size Ø 70/90 mm
Low air capacity, single- acting
Without fieldbus communication
Cable gland –
M12 circular plug
–
–
–
PROFIBUS
DP-V1
Via Bus
DeviceNet
EtherNet/IP
Via Bus
Via Bus
Low air capacity, double- acting
PROFINET
Modbus TCP
Bürkert system bus (büS)
Without fieldbus communication
Via Bus
Via Bus
M12 circular plug
Via Bus
Cable gland –
M12 circular plug
–
–
PROFIBUS
DP-V1
DeviceNet
–
Via Bus
Via Bus
Analogue feedback
0/4…20 mA + 2 binary output
–
Yes
–
Yes
–
–
–
Yes
–
Yes
–
–
Yes
Yes
Yes
–
Diagnostics 1.)
–
Yes
Yes
–
–
Yes
Yes
Yes
Yes
Yes
Yes
–
–
Yes
Yes
Yes
Yes
–
–
Yes
Yes
Yes
Yes
–
–
–
–
–
–
Binary input
Article no.
Standard ATEX II
Cat. 3G/D,
IECEx
306936 306990
306965 306991
307082 307103
307105 307104
311800 311801
265092 265094
306867 306865
306871 306869
306876 306874
306881 306878
306931 306992
306994 306993
307107 307109
307108 307110
311802 311803
265104 265106
17 | 20
Type 8693
Circuit function
Pilot valve system
Communication Electrical connections
Analogue feedback
0/4…20 mA
Actuator series Type 23xx Actuator size Ø 130 mm
High air capacity, single- acting
Without fieldbus
communication
Cable gland –
M12 circular plug
–
–
–
PROFIBUS
DP-V1
Via Bus
DeviceNet
EtherNet/IP
PROFINET
Modbus TCP
Via Bus
Via Bus
Via Bus
Via Bus
Bürkert system bus (büS)
Actuator series Type 27xx Actuator size Ø 175/225 mm
High air capacity, single- acting
Without fieldbus communication
Cable gland –
M12 circular plug
–
–
–
PROFIBUS
DP-V1
DeviceNet
Via Bus
Via Bus
Via Bus
EtherNet/IP
PROFINET
Modbus TCP
Bürkert system bus (büS)
Via Bus
Via Bus
Via Bus
Via Bus
Analogue feedback
0/4…20 mA + 2 binary output
–
Yes
–
Yes
–
–
–
–
–
–
–
Yes
–
Yes
–
–
–
–
–
–
1.) See
“Additional software options of the TopControl process controller Type 8693” on page 13
Diagnostics 1.)
Yes
Yes
Yes
–
–
Yes
Yes
Yes
Yes
Yes
–
–
Yes
Yes
Yes
Yes
–
–
Binary input
Yes
Yes
Yes
Yes
–
–
–
–
–
–
Yes
Yes
Yes
Yes
–
–
–
Article no.
Standard ATEX II
Cat. 3G/D,
IECEx
306946 306995
306973 306997
307112 307114
307113 307115
311804 311805
265113 265115
306868 306866
306872 306870
306877 306875
306882 306880
306950
307070
233356
265141
313276
313269
313271
313283
306952 307004
307068 307121
Further versions on request
Additional
EtherNet/IP, PROFINET, Modbus TCP and büS (Bürkert System Bus): double-acting versions with low air capacity
307003
307122
265138
265140
313275
313268
313270
313282
Visit product website
18 | 20
Type 8693
7.4. Ordering chart accessories
Standard Accessories
Description
M12 socket, 8 pin with 5 m cable for input and output signals
M12 socket, 4 pin with 5 m cable for power supply
M8 socket, 4 pin with 5 m cable for process actual value from sensor
USB büS-Interface Set (büS Stick + connecting cable with M12 connector + connecting cable M12 to micro USB for büS service interface) for connecting to the PC tool Bürkert Communicator (only for device versions with EtherNet/IP, PROFINET, Modbus TCP Bürkert system bus (büS) resp. analogue version with service büS interface) büS cable extension M12, length 1 m büS cable extension M12, length 3 m büS cable extension M12, length 5 m büS cable extension M12, length 10 m
Silencer G ⅛
Sensor puck (spare part)
USB interface for serial communication (only for device versions with PROFIBUS, DeviceNet resp. ana logue version with serial interface / fluid volume controller Type 8750)
Bürkert Communicator Software
Article no.
919267
918038
264602
772551
772404
772405
772406
772407
780779
682240
227093
LINK
Adapter kits
Note:
The accessories for adapter kits must be ordered separately
Adapter kits for third-party actuators can be found in the data sheet Adaptation for third-party actuators, KK01 or contact the appropriate Bürkert sales office.
Description
Adapter kit for actuator series Type
23xx/2103
Adapter kit for actuator series Type 27xx
Actuator size
Ø 70/90/130 mm
Ø 175/225 mm
Control function
Universal
A (NO), B (NC)
Article no.
679917
679935
Visit product website
19 | 20
Bürkert – Close to You
For up-to-date addresses please visit us at www.burkert.com
Austria
Belgium
Czech Republic
Denmark
Finland
France
Germany
Italy
Netherlands
Norway
Poland
Spain
Sweden
Switzerland
Turkey
United Kingdom
Russia
Canada
USA
Brazil
Uruguay
South Africa
United
Arab
Emirates
Australia
New Zealand
China
Hong Kong
India
Japan
Korea
Malaysia
Philippines
Singapore
Taiwan
Credits, © and concept: Christian Bürkert GmbH & Co. KG | Photographs: Marc Eggimann Fotografie - 4051 Basel | Scanner GmbH - Werbeagentur Künzelsau -